You are on page 1of 14

Ecostruxure IT Gateway Installation &

Configurations
Manjunath Pulukunta
Javier Baena

Confidential Property of Schneider Electric


System chart
EcoStruxure
Asset Advisor

UPS Customer Proactive contact for Schneider Electric Big Data, Analytics,
alarm resolution Connected Services Hub Insights, Predictive,
Cooling Device Opportunity

PDU

Rack PDU

Rack Access

Environmental Customer
SNMP /
Modbus TCP Smartphone App

Critical physical Gateway Customer Schneider Electric Cloud


infrastructure or Firewall
Data Center Expert
7.4.x
Free download on
EcoStruxureit.com Monthly report

Confidential Property of Schneider Electric | Page 2


System Pre-Requirements

Before Downloading the Gateway, be sure to verify System


1 Requirements to avoid connection Issues

Server or Computer (always ON) Browsers


• Server with Microsoft Windows 64bits • Microsoft IE 10,11
• Red Hat Enterprise Linux 7 or CentOS 7 • Mozilla Firefox 39.0
• At least 2 cores and 4Gb RAM • Google Chrome 43.0
• 2 Gb of hard disk space • Safari
* Gateway v1.1.0 was tested in Microsoft Server Minimmun screen resolution 1024x768
2008 R2 SP1, 2012 SP1 and 2016. It requires
255Mb of hard disk space and the server keeps Smartphone
a max of 8 days of data, 128Mb / day. • iPhone 4S or later
• iOS 8.0 or higher
Critical physical • Android 4.4 or later
infrastructure
Connected Devices
Firewall • Intellingent Management card
• Outbound Port 443 TCP • Modbus TCP or SNMP v1&v3
• To connect using static IP, add • Connected to TCP/IP Network
40.84.62.190 & 23.99.90.28 where Gateway has access
Step 1: You can log into URL: www.ecostruxureit.com and click on Get Started.
Note : Check the system requirement before Installing the Gateway

Confidential Property of Schneider Electric | Page 4


Step 2: Fill all the details and Once the registration is completed, the Ecostruxure Gateway Account is
created and click on go to Login

Confidential Property of Schneider Electric | Page 5


Step 3: Give Username and Password which was given at the time of registration and Click Login.
Step 4: After successful Login you have to Install the Ecostruxure IT mobile app from play store

Confidential Property of Schneider Electric | Page 6


Step 5: Click on I’ve already downloaded and it will be redirected to QR scan has to be completed after
installing mobile app and make a note of recovery code (which is important in case you lose the
password)

Confidential Property of Schneider Electric | Page 7


Step 6: It will send the push notification to Mobile App and click on Allow, and it will redirect to the
manage portal where we can download the Gateway.

Confidential Property of Schneider Electric | Page 8


Step 7: After Completion of Gateway Download, Open the browser and give the URL as
https://localhost/dce or Click on Ecostruxure Gateway Icon
Step 8: Give Username : admin
Password : admin ( then it will ask to create new password )

Confidential Property of Schneider Electric | Page 9


Step 9: Click on more option and click on Discovery ( We are connecting the devices to Gateway)

Confidential Property of Schneider Electric | Page 10


Step 10: Click on create discovery and give the device details and click on Run ,device will be connected
successfully and it will show as per the below image.

Confidential Property of Schneider Electric | Page 11


Step 11: After adding the devices click on the Ecostruxure IT and we can see the Gateway Registration
status and click on register it will be redirecting to other page.
Step 12 : Login by giving username and password it will ask the Gateway Name ( Give any name) and click
on connect

Confidential Property of Schneider Electric | Page 12


Step 13: You can click on Ecostruxure IT in the Gateway Dashboard and we can see the status Registered
and Communicating.

Note : If the Ecostruxure Gateway is not communicating with the services then make sure that
Proxy settings are correct to communicate to our Cloud Servers
This can be checked

Confidential Property of Schneider Electric | Page 13