• The SIL-G is a feeder relay with current, voltage and frequency functions Server.
for primary and secondary distribution with auxiliary power supply of » Rear RJ45 or SFP Cage: IEC61850 and Redundancy (PRP or
24- 230 Vdc/ac, 48-230 Vdc/ac or 24-48 Vdc (depending on model). HSR).
• 4 current channels and up to 5 voltage channels with conventional VTs. • Wireless communication (WiFi) and synchronization through IRIG-B
• Capability of measuring up to 1.000 volts when it is connected directly optional depending on the model.
to the low voltage line. • The SIL-G is provided with (depending on the model):
• Metallic box with high electromagnetic compatibility level (EMC) and » 8 configurable inputs and 7 configurable outputs.
wide range of operating temperature. » 24 configurable inputs and 7 configurable outputs.
• Protection of decoupling, load shedding and loss of main (islanding). » 8 configurable inputs and 18 configurable outputs.
Loss of Main (islanding) occurs when part of the public utility network » 16 configurable inputs and 11 configurable outputs.
loses connection with the rest of the system. If this situation is not » 8 configurable inputs, 7 configurable outputs, 4 AFD inputs, and
detected, then the generator could remain connected, causing a safety 4 High-Speed outputs.
hazard within the network. Automatic reconnection of the generator • SIL-G is fitted with the demand of power (Load Data Profiling) with
to the network may occur causing damage to the generator and the the following characteristics:
network. SIL-G protection relay detects this situation thanks to its » Number of records: 2160.
voltage and frequency functions focused on the Rate of change of » Recording mode circular.
frequency (ROCOF) method. » Sampling rate (interval): configurable through communications
• Signaling/control of the circuit breaker (52 function) and the recloser (1-60 min).
(79 function). • Alarms panel is available.
• Arc Flash detection (AFD) with 4 AFD inputs and 4 high-speed outputs • SIL-G is provided with non-volatile RAM memory in order to store up to
available depending on model. This functionality, along with the 3072 events and disturbance fault recording (DFR), maintaining date &
possibility of having WIFI communication, allows the users to set and time thanks to its internal RTC (real Time Clock).
configure the relay through Fanox free software and to operate the relay » 5 records in data and COMTRADE format (300 cycles each
without being present in the installation prioritizing the security. record): 1 to 8 pre-fault cycles + 292 to 299 postfault cycles.
• In case a CB is manually closed, a switch on to an existing fault may » 25 records in data and COMTRADE format (60 cycles each
occur. This fault condition is critical if the overcurrent protection function record): 1 to 8 pre-fault cycles + 52 to 59 postfault cycles.
does not clear the fault until the adjusted time delay is finished. It is » 50 records in data and COMTRADE format (30 cycles each
necessary, in those cases, to clear the fault quickly by means of SOTF record): 1 to 8 pre-fault cycles + 22 to 29 postfault cycles.
function. » 100 records in data and COMTRADE format (15 cycles each
• To allow the communication, relays are provided with a local micro USB record): 1 to 8 pre-fault cycles + 7 to 14 postfault cycles.)
front port and with remote communication with different options (ports • Each oscillographic record contains 10 analog channels and up to 96
and protocols) on the rear side: configurable digital channels. The oscillography is downloaded by the
» Rear RS485 Port: IEC60870-5-103, Modbus RTU or DNP3.0 communications port. The SICom communications program allows
Serial (selectable by general settings). the oscillography record to be downloaded and saved in COMTRADE
» Rear RJ45 Port: Modbus TCP/IP, DNP3.0 TCP/IP, IEC60870- format (IEEE C37.111-1991).
5-104 (selectable by general settings) + SNTP Protocol + Web
68
Functions diagram SIL-G
BUS SIL-G
3 or 4
27 27V1 59 59N/G 47 81 81R 78
32 60VTS
3
67NI 67N/51N 67/51 SOFT 50 50N 46 46BC 37 49 SHB
60CTS
AFD* 64REF
CLP
52
HLT 79 52 74TCS 68 86 25*
3
27-L* 59-L*
49T
ADDITIONAL FUNCTIONS
DFR Disturbance Fault Recording
CNT Counters
LDP Load Data Profiling
RTC Real-Time Clock
MET Metering
ALRM Alarm panel
STTG Settings Groups
PGC Programmable Logic Control
CMMD Commands
HMI Human Machine Interface
SER Sequential Event Recording
69
Technical parameters SIL-G
Deactivation level: 95% Current tap: 0.050 to 20.000 xIn (step 0.001xIn)
Time delay: 0.000 to 300.000 s (step 0.001 s) Curve, current activation level: 110%
Function 50G-1 Activation level: 100% Curve, current deactivation level: 100%
± 30 ms or ± 5% (greater of both)
70
Technical parameters SIL-G
Time delay: 0.000 to 300.000 s (step 0.001 s) Low Voltage Tap: 0.08 to 2.00 xUn (step 0.01xUn)
Time dial (TMS): 0.05 to 25.00 (step 0.01) High Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Function 67GI
If Curve type IEC: 0.05 to 1.00 (step 0.01) Time delay: 0.000 to 300.000 s (step 0.001 s)
If Curve type IEEE: 0.10 to 25.00 (step Operating angle: 0 to 359º (step 1º)
0.01)
Halfcone angle: 10 to 170º (step 1º)
Current tap: 0.010 to 20.000 xIn (step 0.001xIn)
Activation level: 100%
Directionality: No/Forward/Reverse
Deactivation level: 95%
Function 67G/51G-1 Polarization voltage: 0.08 to 2.00 xUn (step 0.01xUn)
Temporized deactivation
Operating angle: 0 to 359º (step 1º)
Function 67G/51G-2 Timing accuracy: ± 30 ms or ± 5% (greater of both)
Halfcone angle: 10 to 170º (step 1º)
Function enable: No/Alarm/Trip/ SHB Trip
Curve, current activation level: 110%
Current tap: 0.050 to 20.000 xIn (step 0.001xIn)
Curve, current deactivation level: 100%
Time delay: 0.020 to 300.000 s (step 0.001 s)
Defined time, current activation level: 100%
Neutral SHB Tap: 5 to 50% (step 1%)
Defined time, current deactivation level: 95% Function 64REF
Activation level: 100%
Voltage activation level: 100%
Deactivation level: 90%
Voltage deactivation level: 95%
Temporized deactivation
Temporized deactivation
Timing accuracy: ± 30 ms or ± 5% (greater of both)
Timing accuracy for IEC and IEEE curves selection:
Function enable: No/Alarm/Trip/SHB Trip
± 30 ms or ± 5% (greater of both)
Current tap: 0.010 to 30.000 xIn (step 0.001xIn)
Timing accuracy for defined time curve selection:
Time delay: 0.000 to 295.000 s (step 0.001 s)
± 35 ms or ± 0.5% (greater of both)
Safe Time: 0.020 to 300.000 s (step 0.001 s)
Function enable: No/Alarm/Trip/SHB Trip Function SOTF
Activation level: 100%
Directionality: No/Forward/Reverse
Deactivation level: 95%
Low Current Tap: 0.050 to 30.000 xIn (step 0.001xIn)
Temporized deactivation
High Current Tap: 0.050 to 30.000 xIn (step
0.001xIn) Timing accuracy: ± 35 ms or ± 0.5% (greater of both)
Low Voltage Tap: 0.08 to 2.00 xUn (step 0.01xUn) Function enable: No/Alarm/Trip
High Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn) Current tap: 0.100 to 2.400 In (step 0.001xIn)
Function 67NI ζ heating: 3 to 600 min (step 1 min)
Time delay: 0.000 to 300.000 s (step 0.001 s)
Operating angle: 0 to 359º (step 1º) ζ cooling: 1 to 6 xζ heating (step 1)
Function 49
Halfcone angle: 10 to 170º (step 1º) Alarm: 20 to 99% (step 1%)
Activation level: 100% Trip level: 100%
Deactivation level: 95% Deactivation level: 95% of alarm level
Temporized deactivation Timing accuracy: ± 5% respect of theorical value.
Timing accuracy: ± 30 ms or ± 5% (greater of both) Function enable: No/Yes
Current Tap: 5- 50% (step 1%)
Reset Time: 0.000 to 300.000 (step 0.001 s)
Function SHB Block Threshold: 0.010 to 30.000xIn (step 0.001xIn)
Activation level: 100%
Deactivation level: 95%
Temporized deactivation
Function enable: Yes/No
Settings group: 1 to 4 (step 1)
No load time: 0.020 to 300.000 s (step 0.001 s)
Function CLP
Cold load time: 0.020 to 300.000 s (step 0.001 s)
Open breaker activation 0.8% In and reset
threshold: 1% In
71
Technical parameters SIL-G
72
Technical parameters SIL-G
73
Technical parameters SIL-G
74
Technical parameters SIL-G
Burden of current inputs: Current Angles: IA, IB, IC, IN and 3I0.
75
Connections diagram SIL-G
C B
A
BUS B
C
A1 A2 A3 A4 A5 A6 A7 A8
D1
In9
D12
INPUTS
D13
In10
D14
D15
In11
D16
D17
In12
D18
VOLTAGE In13 D19
INPUTS D20
D21
B3
In14
D22
B4 D23
In15
D24
B5 D25
In16
B6 D26
B7 E1
output4 output3 output2 output1
B8 SIL-G E2
B9 Protection Relay E3
E4
B10 E5
B11
52
E6
E7
B12 E8
E9
E10
E11
E12
OUTPUTS
E13
output9 output8 output7 output6 output5
LINE E14
E15
SAFETY
GND GROUND E16
E17
E18
E19
E20
E21
E22
E23
output11 output10
E24
E25
E26
AC/DC
B1
POWER
Power Supply
AUX.
COM B2
76
Connections diagram SIL-G
C B
A
BUS B
C
A1 A2 A3 A4 A5 A6 A7 A8
D1
In9
D12
INPUTS
D13
In10
D14
D15
In11
D16
D17
In12
D18
VOLTAGE D19
In13
INPUTS D20
D21
B3
In14
D22
B4 D23
In15
D24
B5 D25
In16
B6 D26
B7 E1
output4 output3 output2 output1
B8 SIL-G E2
B9 Protection Relay E3
52 B10
E4
E5
B11 E6
E7
B12 E8
E9
E10
E11
E12
OUTPUTS
E13
output9 output8 output7 output6 output5
LINE E14
E15
SAFETY
GND GROUND E16
E17
E18
E19
E20
E21
E22
E23
output11 output10
E24
E25
E26
AC/DC
B1
POWER
Power Supply
AUX.
COM B2
77
Dimensions and cutout SIL-G
78
Selection & Ordering data SIL-G
SIL-G
Feeder & Generator Protection Relay
PHASE CURRENT MEASUREMENT
0 1 A or 5 A
NEUTRAL CURRENT MEASUREMENT
0 1 A or 5 A
VOLTAGE MEASUREMENT
0 Up to 1000 V (direct connection) or 250 V (with VTs)
POWER SUPPLY
A 24-48 Vdc
B 48-230 Vac/dc
C 24-230 Vac/dc (Only for communication models: A, B, F and G)
ADDITIONAL FUNCTIONS
0 -
1 +25 + 27-L + 59-L
COMMUNICATIONS
A A: USB (Modbus RTU) + RS485: (Modbus RTU, IEC60870-5-103 or DNP3.0
Serial)
B B: USB (Modbus RTU) + RS485 (Modbus RTU, IEC60870-5-103 or DNP3.0
Serial) + RJ45 (Modbus TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server
C SNTP Protocol + IRIG-B
C: USB (Modbus RTU) + RJ45 (IEC 61850) + RJ45 (Modbus TCP, DNP3.0 TCP
D or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
D: USB (Modbus RTU) + HSR – (*) SFP Cage (IEC 61850) + RJ45 (Modbus
E TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
E: USB (Modbus RTU) + PRP – (*) SFP Cage (IEC 61850) + RJ45 (Modbus
F TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
F: USB (Modbus RTU) + WiFi + RS485 (Modbus RTU, IEC60870-5-103 or
G DNP3.0 Serial)
G: USB (Modbus RTU) + WiFi + RS485 (Modbus RTU, IEC60870-5-103 or
H DNP3.0 Serial) + RJ45 (Modbus TCP, DNP3.0 TCP or IEC60870-5-104) + Web
Server SNTP Protocol + IRIG-B
I H: USB (Modbus RTU) + WiFi + RJ45 (IEC 61850) + RJ45 (Modbus TCP,
DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
J I: USB (Modbus RTU) + WiFi + HSR – (*) SFP Cage (IEC 61850) RJ45 (Modbus
TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
K J: USB (Modbus RTU) + WiFi + PRP – (*) SFP Cage (IEC61850) + RJ45
(Modbus TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol
L + IRIG-B
K: USB (Modbus RTU) + (*) SFP Cage (IEC 61850) + RJ45 (Modbus TCP,
DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
L: USB (Modbus RTU) + WiFi + (*) SFP Cage (IEC 61850) + RJ45 (Modbus
TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
INPUTS AND OUTPUTS
0 8 Inputs + 7 Outputs
5 24 Inputs + 7 Outputs
6 8 Inputs + 18 Outputs
7 16 Inputs + 11 Outputs
A 8 Inputs + 7 Outputs + 4 AFD Inputs + 4 High-speed Outputs
MECHANICAL ASSEMBLY
4 Vertical Assembly
5 Vertical Assembly with tropicalization
LANGUAGE
A English, Spanish, German and French
E English, Spanish, Turkish and Russian
F English, Spanish, German and Portuguese
ADAPTATION
B (2) 50 + SOTF + 50G + 50N + (4) 67/51 + (2) 67G/51G + (2) 67N/51N + 67GI +
67NI + 64REF + 46 + 46BC + 49 + 49T + 37 + (2) 27+ 27V1 + (2) 59 + (2) 59N/G
+ 47 + (4) 32 + (4) 81U/O + (4) 81R + 78 + (2) 24 + 79 + 74TCS + 60CTS +
60VTS + 50BF + SHB + CLP + 52 + 86 + HLT
0 0 0 C 1 F 0 4 A B SIL G 0 0 0 C 1 F 04 A B
SIL-G
(*) The SFPs for the models with optical fiber should be included by the user.
NOTES:
» ANSI 67, ANSI 67G and ANSI 67N can be converted into ANSI 51, ANSI 51G and ANSI 51N respectively by setting the “Directionality”
parameter to NO.
» Not all combinations are possible. Please, confirm with Fanox chosen model.
79