SIL-G

Line, Feeder & Generator Protection Relay

Primary & Secondary Distribution Protection


WIFI

• The SIL-G is a feeder relay with current, voltage and frequency functions Server.
for primary and secondary distribution with auxiliary power supply of » Rear RJ45 or SFP Cage: IEC61850 and Redundancy (PRP or
24- 230 Vdc/ac, 48-230 Vdc/ac or 24-48 Vdc (depending on model). HSR).
• 4 current channels and up to 5 voltage channels with conventional VTs. • Wireless communication (WiFi) and synchronization through IRIG-B
• Capability of measuring up to 1.000 volts when it is connected directly optional depending on the model.
to the low voltage line. • The SIL-G is provided with (depending on the model):
• Metallic box with high electromagnetic compatibility level (EMC) and » 8 configurable inputs and 7 configurable outputs.
wide range of operating temperature. » 24 configurable inputs and 7 configurable outputs.
• Protection of decoupling, load shedding and loss of main (islanding). » 8 configurable inputs and 18 configurable outputs.
Loss of Main (islanding) occurs when part of the public utility network » 16 configurable inputs and 11 configurable outputs.
loses connection with the rest of the system. If this situation is not » 8 configurable inputs, 7 configurable outputs, 4 AFD inputs, and
detected, then the generator could remain connected, causing a safety 4 High-Speed outputs.
hazard within the network. Automatic reconnection of the generator • SIL-G is fitted with the demand of power (Load Data Profiling) with
to the network may occur causing damage to the generator and the the following characteristics:
network. SIL-G protection relay detects this situation thanks to its » Number of records: 2160.
voltage and frequency functions focused on the Rate of change of » Recording mode circular.
frequency (ROCOF) method. » Sampling rate (interval): configurable through communications
• Signaling/control of the circuit breaker (52 function) and the recloser (1-60 min).
(79 function). • Alarms panel is available.
• Arc Flash detection (AFD) with 4 AFD inputs and 4 high-speed outputs • SIL-G is provided with non-volatile RAM memory in order to store up to
available depending on model. This functionality, along with the 3072 events and disturbance fault recording (DFR), maintaining date &
possibility of having WIFI communication, allows the users to set and time thanks to its internal RTC (real Time Clock).
configure the relay through Fanox free software and to operate the relay » 5 records in data and COMTRADE format (300 cycles each
without being present in the installation prioritizing the security. record): 1 to 8 pre-fault cycles + 292 to 299 postfault cycles.
• In case a CB is manually closed, a switch on to an existing fault may » 25 records in data and COMTRADE format (60 cycles each
occur. This fault condition is critical if the overcurrent protection function record): 1 to 8 pre-fault cycles + 52 to 59 postfault cycles.
does not clear the fault until the adjusted time delay is finished. It is » 50 records in data and COMTRADE format (30 cycles each
necessary, in those cases, to clear the fault quickly by means of SOTF record): 1 to 8 pre-fault cycles + 22 to 29 postfault cycles.
function. » 100 records in data and COMTRADE format (15 cycles each
• To allow the communication, relays are provided with a local micro USB record): 1 to 8 pre-fault cycles + 7 to 14 postfault cycles.)
front port and with remote communication with different options (ports • Each oscillographic record contains 10 analog channels and up to 96
and protocols) on the rear side: configurable digital channels. The oscillography is downloaded by the
» Rear RS485 Port: IEC60870-5-103, Modbus RTU or DNP3.0 communications port. The SICom communications program allows
Serial (selectable by general settings). the oscillography record to be downloaded and saved in COMTRADE
» Rear RJ45 Port: Modbus TCP/IP, DNP3.0 TCP/IP, IEC60870- format (IEEE C37.111-1991).
5-104 (selectable by general settings) + SNTP Protocol + Web

68
Functions diagram SIL-G

BUS SIL-G

3 or 4
27 27V1 59 59N/G 47 81 81R 78

32 60VTS

3
67NI 67N/51N 67/51 SOFT 50 50N 46 46BC 37 49 SHB

60CTS
AFD* 64REF

1 67GI 67G/51G 50BF


50G

CLP

52
HLT 79 52 74TCS 68 86 25*

3
27-L* 59-L*

49T

tº SER ALRM PGC HMI LDP DFR

RTC MET STTG CMMD CNT


LINE

1/2 1 1 1/2 1 1 * Optional

FO* IRG-B* WIFI* ETHERNET RS485* USB

ANSI CODES PROTECTIONS


50 Instantaneous phase overcurrent Instantaneous Positive sequence undervoltage (Bus
27V1
Bar)
67/51 Inverse Time Directional* Phase Overcurrent 32 Directional Overpower
50N Instantaneous calculated neutral overcurrent 81O/U Under/Overfrequency
50G Instantaneous measured neutral overcurrent 81R Rate of change of Frequency (ROCOF)
Inverse Time Directional* Calculated Neutral
67N/51N 78 Out of Step (Vector Shift)
Overcurrent
Inverse Time Directional* Measured Neutral 24 Overfluxing
67G/51G
Overcurrent
67GI Directional Isolated Measured Neutral Overcurrent CLP Cold Load pickup
67NI Directional Isolated Calculated Neutral Overcurrent 79 AC Reclosing device
SOTF Switch On To Fault HLT Hot Line Tag
46 Phase balance current protection 52 Breaker wear monitoring
46BC Broken Conductor Detection 25 Synchro Check
64REF Restricted earth fault 50BF Circuit Breaker Failure
37 Instantaneous phase undercurrent 74TCS Trip Circuit Supervision
49 Thermal overload 60CTS Phase CT Supervision
49T External Trip 60VTS Phase VT Supervision
SHB Second Harmonic Blocking AFD Arc Flash detection
59 Instantaneous phase overvoltage (Bus Bar) 86 Trip lockout
Instantaneous Calculated/Measured neutral 68 Zone selection interlocking
59N/G
overvoltage (Bus Bar)
PGC Programmable logic control
59L Instantaneous phase overvoltage (Line)
* ANSI 67, ANSI 67G and ANSI 67N can be converted into ANSI 51,
47 Phase Balance voltage protection (Bus Bar) ANSI 51G and ANSI 51N respectively by setting the “Directionality”
27 Instantaneous Phase undervoltage (Bus Bar) parameter to NO.
27L Instantaneous Phase undervoltage (Line)

ADDITIONAL FUNCTIONS
DFR Disturbance Fault Recording
CNT Counters
LDP Load Data Profiling
RTC Real-Time Clock
MET Metering
ALRM Alarm panel
STTG Settings Groups
PGC Programmable Logic Control
CMMD Commands
HMI Human Machine Interface
SER Sequential Event Recording

69
Technical parameters SIL-G

Function enable: No/Alarm/Trip/SHB Trip Function enable: No/Alarm/Trip/SHB Trip


Current tap: 0.010 to 30.000 xIn (step 0.001xIn) Curve Type: IEC 60255-151 and IEEE curves.
Time delay: 0.000 to 300.000 s (step 0.001 s)
Function 50-1 IEC (Definite time, standard inverse, very inverse,
Activation level: 100% extremely inverse, long time inverse, short time
Function 50-2 inverse) and IEEE (Moderately inverse, very inverse,
Deactivation level: 95%
extremely inverse).
Temporized deactivation
Time delay: 0.000 to 300.000 s (step 0.001 s)
Timing accuracy: ± 35 ms or ± 0.5% (greater of both) Time dial (TMS): 0.05 to 25.00 (step 0.01)
Function enable: No/Alarm/Trip/SHB Trip
If Curve type IEC: 0.05 to 1.00 (step 0.01)
Current tap: 0.050 to 30.000 xIn (step 0.001xIn)
Time delay: 0.000 to 300.000 s (step 0.001 s) If Curve type IEEE: 0.10 to 25.00 (step
Function 50N-1 Activation level: 100% 0.01)

Deactivation level: 95% Current tap: 0.050 to 20.000 xIn (step 0.001xIn)

Temporized deactivation Directionality: No/Forward/Reverse


Function 67N/51N-1
Timing accuracy: ± 35 ms or ± 0.5% (greater of both) Polarization voltage: 0.08 to 2.00 xUn (step 0.01xUn)
Function 67N/51N-2 Operating angle: 0 to 359º (step 1º)
Function enable: No/Alarm/Trip/SHB Trip
Current tap: 0.010 to 30.000 xIn (step 0.001xIn) Halfcone angle: 10 to 170º (step 1º)

Time delay: 0.000 to 300.000 s (step 0.001 s) Curve, current activation level: 110%

Function 50G-1 Activation level: 100% Curve, current deactivation level: 100%

Deactivation level: 95% Defined time, current activation level: 100%

Temporized deactivation Defined time, current deactivation level: 95%


Voltage activation level: 100%
Timing accuracy: ± 35 ms or ± 0.5% (greater of both)
Voltage deactivation level: 95%
Function enable: No/Alarm/Trip/SHB Trip
Temporized deactivation
Curve Type: IEC 60255-151 and IEEE curves.
Timing accuracy for IEC and IEEE curves selection:
IEC (Definite time, standard inverse, very inverse,
extremely inverse, long time inverse, short time ± 30 ms or ± 5% (greater of both)
inverse) and IEEE (Moderately inverse, very inverse,
extremely inverse). Timing accuracy for defined time curve selection:
Time delay: 0.000 to 300.000 s (step 0.001 s)
± 35 ms or ± 0.5% (greater of both)
Time dial (TMS): 0.05 to 25.00 (step 0.01)

If Curve type IEC: 0.05 to 1.00 (step 0.01)

If Curve type IEEE: 0.10 to 25.00 (step


0.01)
Current tap: 0.010 to 20.000 xIn (step 0.001xIn)
Function 67/51-1
Directionality: No/Forward/Reverse
Function 67/51-2 Polarization voltage: 0.08 to 2.00 xUn (step 0.01xUn)
Operating angle: 0 to 359º (step 1º)
Function 67/51-3
Halfcone angle: 10 to 170º (step 1º)
Function 67/51-4 Curve, current activation level: 110%
Curve, current deactivation level: 100%
Defined time, current activation level: 100%
Defined time, current deactivation level: 95%
Voltage activation level: 100%
Voltage deactivation level: 95%
Temporized deactivation
Timing accuracy for IEC and IEEE curves selection:

± 30 ms or ± 5% (greater of both)

Timing accuracy for defined time curve selection:

± 35 ms or ± 0.5% (greater of both)

70
Technical parameters SIL-G

Function enable: No/Alarm/Trip/SHB Trip Function enable: No/Alarm/Trip/SHB Trip


Curve Type: IEC 60255-151 and IEEE curves. Directionality: No/Forward/Reverse
IEC (Definite time, standard inverse, very inverse, Low Current Tap: 0.010 to 30.000 xIn (step 0.001xIn)
extremely inverse, long time inverse, short time
inverse) and IEEE (Moderately inverse, very inverse, High Current Tap: 0.010 to 30.000 xIn (step
extremely inverse). 0.001xIn)

Time delay: 0.000 to 300.000 s (step 0.001 s) Low Voltage Tap: 0.08 to 2.00 xUn (step 0.01xUn)

Time dial (TMS): 0.05 to 25.00 (step 0.01) High Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Function 67GI
If Curve type IEC: 0.05 to 1.00 (step 0.01) Time delay: 0.000 to 300.000 s (step 0.001 s)
If Curve type IEEE: 0.10 to 25.00 (step Operating angle: 0 to 359º (step 1º)
0.01)
Halfcone angle: 10 to 170º (step 1º)
Current tap: 0.010 to 20.000 xIn (step 0.001xIn)
Activation level: 100%
Directionality: No/Forward/Reverse
Deactivation level: 95%
Function 67G/51G-1 Polarization voltage: 0.08 to 2.00 xUn (step 0.01xUn)
Temporized deactivation
Operating angle: 0 to 359º (step 1º)
Function 67G/51G-2 Timing accuracy: ± 30 ms or ± 5% (greater of both)
Halfcone angle: 10 to 170º (step 1º)
Function enable: No/Alarm/Trip/ SHB Trip
Curve, current activation level: 110%
Current tap: 0.050 to 20.000 xIn (step 0.001xIn)
Curve, current deactivation level: 100%
Time delay: 0.020 to 300.000 s (step 0.001 s)
Defined time, current activation level: 100%
Neutral SHB Tap: 5 to 50% (step 1%)
Defined time, current deactivation level: 95% Function 64REF
Activation level: 100%
Voltage activation level: 100%
Deactivation level: 90%
Voltage deactivation level: 95%
Temporized deactivation
Temporized deactivation
Timing accuracy: ± 30 ms or ± 5% (greater of both)
Timing accuracy for IEC and IEEE curves selection:
Function enable: No/Alarm/Trip/SHB Trip
± 30 ms or ± 5% (greater of both)
Current tap: 0.010 to 30.000 xIn (step 0.001xIn)
Timing accuracy for defined time curve selection:
Time delay: 0.000 to 295.000 s (step 0.001 s)
± 35 ms or ± 0.5% (greater of both)
Safe Time: 0.020 to 300.000 s (step 0.001 s)
Function enable: No/Alarm/Trip/SHB Trip Function SOTF
Activation level: 100%
Directionality: No/Forward/Reverse
Deactivation level: 95%
Low Current Tap: 0.050 to 30.000 xIn (step 0.001xIn)
Temporized deactivation
High Current Tap: 0.050 to 30.000 xIn (step
0.001xIn) Timing accuracy: ± 35 ms or ± 0.5% (greater of both)
Low Voltage Tap: 0.08 to 2.00 xUn (step 0.01xUn) Function enable: No/Alarm/Trip
High Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn) Current tap: 0.100 to 2.400 In (step 0.001xIn)
Function 67NI ζ heating: 3 to 600 min (step 1 min)
Time delay: 0.000 to 300.000 s (step 0.001 s)
Operating angle: 0 to 359º (step 1º) ζ cooling: 1 to 6 xζ heating (step 1)
Function 49
Halfcone angle: 10 to 170º (step 1º) Alarm: 20 to 99% (step 1%)
Activation level: 100% Trip level: 100%
Deactivation level: 95% Deactivation level: 95% of alarm level
Temporized deactivation Timing accuracy: ± 5% respect of theorical value.
Timing accuracy: ± 30 ms or ± 5% (greater of both) Function enable: No/Yes
Current Tap: 5- 50% (step 1%)
Reset Time: 0.000 to 300.000 (step 0.001 s)
Function SHB Block Threshold: 0.010 to 30.000xIn (step 0.001xIn)
Activation level: 100%
Deactivation level: 95%
Temporized deactivation
Function enable: Yes/No
Settings group: 1 to 4 (step 1)
No load time: 0.020 to 300.000 s (step 0.001 s)
Function CLP
Cold load time: 0.020 to 300.000 s (step 0.001 s)
Open breaker activation 0.8% In and reset
threshold: 1% In

71
Technical parameters SIL-G

Function enable: No/Alarm/Trip/SHB Trip Function enable: No/Alarm/Trip


Curve Type: IEC 60255-151 and IEEE curves. Voltage tap: 0.15 to 2.00 xUn (step 0.01xUn)
Minimum level: 0.00 to 1.00 xUn (step 0.01xUn)
IEC (Definite time, standard inverse, very inverse,
extremely inverse, long time inverse, short time Time delay: 0.060 to 300.000 s (step 0.001 s)
inverse) and IEEE (Moderately inverse, very inverse, Reset time: 0.020 to 300.000 s (step 0.001 s)
Function 27V1
extremely inverse).
Activation level: 99%
Time delay: 0.000 to 300.000 s (step 0.001 s)
Deactivation level: 101%
Time dial (TMS): 0.05 to 25.00 (step 0.01)
Temporized deactivation
If Curve type IEC: 0.05 to 1.00 (step 0.01)
Timing accuracy: ± 30 ms or ± 0.5% (greater of both)

If Curve type IEEE: 0.10 to 25.00 (step Function enable: No/Alarm/Trip


0.01) Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Function 46 Current tap: 0.050 to 20.000 xIn (step 0.001xIn) Minimum level: 0.00 to 1.00 xUn (step 0.01xUn)
Curve, current activation level: 110% Time delay: 0.060 to 300.000 s (step 0.001 s)
Curve, current deactivation level: 100% Function 27L (*) Reset time: 0.020 to 300.000 s (step 0.001 s)
Defined time, current activation level: 100% Activation level: 99%
Defined time, current deactivation level: 95% Deactivation level: 101%
Temporized deactivation Temporized deactivation
Timing accuracy for IEC and IEEE curves selection: Timing accuracy: ± 30 ms or ± 0.5% (greater of both)

± 30 ms or ± 5% (greater of both) Function enable: No/Alarm/Trip


Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Timing accuracy for defined time curve selection:
Time delay: 0.045 to 300.000 s (step 0.001 s)
± 35 ms or ± 0.5% (greater of both) Function 59-1 Reset time: 0.020 to 300.000 s (step 0.001 s)
Function enable: No/Alarm/Trip/ Function 59-2 Activation level: 101%
Tap: 15 to 100 % (step 1%) Deactivation level: 99%
Time delay: 0.030 to 300.000 s (step 0.001 s) Temporized deactivation
Function 46BC
Activation level: 100% Timing accuracy: ± 30 ms or ± 0.5% (greater of both)
Deactivation level: 95% Function enable: No/Alarm/Trip
Timing accuracy: ± 30 ms or ± 0.5% (greater of both) Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Function enable: No/Alarm/Trip Time delay: 0.045 to 300.000 s (step 0.001 s)
Current tap: 0.010 to 30.000 xIn (step 0.001xIn) Function 59N/G-1 Reset time: 0.020 to 300.000 s (step 0.001 s)
Minimum level: 0.000 to 1.000 xIn (step 0.001xIn) Function 59N/G-2 Activation level: 101%
Time delay: 0.060 to 300.000 s (step 0.001 s) Deactivation level: 99%
Function 37
Activation level: 100% Temporized deactivation
Deactivation level: 105% Timing accuracy: ± 30 ms or ± 0.5% (greater of both)
Temporized deactivation Function enable: No/Alarm/Trip
Timing accuracy: ± 30 ms or ± 0.5% (greater of both) Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Function enable: No/Alarm/Trip Time delay: 0.045 to 300.000 s (step 0.001 s)
Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn) Reset time: 0.020 to 300.000 s (step 0.001 s)
Function 47
Minimum level: 0.00 to 1.00 xUn (step 0.01xUn) Activation level: 101%
Time delay: 0.060 to 300.000 s (step 0.001 s) Deactivation level: 99%
Function 27-1
Reset time: 0.020 to 300.000 s (step 0.001 s) Temporized deactivation
Function 27-2
Activation level: 99% Timing accuracy: ± 30 ms or ± 0.5% (greater of both)
Deactivation level: 101% Function enable: No/Alarm/Trip
Temporized deactivation Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Timing accuracy: ± 30 ms or ± 0.5% (greater of both) Time delay: 0.045 to 300.000 s (step 0.001 s)
Reset time: 0.020 to 300.000 s (step 0.001 s)
Function 59L (*)
Activation level: 101%
Deactivation level: 99%
Temporized deactivation
Timing accuracy: ± 30 ms or ± 0.5% (greater of both)

72
Technical parameters SIL-G

Function enable: No/Alarm/Trip Function enable: No/Alarm/Trip


Activation level: 0.02 to 2.00 xSn (step 0.01xSn) Curve Type: Inverse A, Inverse B, Inverse C, and
Function 32-1 Defined Time.
Operating angle: 0 to 359º (step 1º)
Function 32-2 Time delay: 0.020 to 300.000 s (step 0.001 s) Time delay: 0.020 to 300.000 s (step 0.001 s)
Function 32-3 Activation level: 100% Time dial (TMS): 0.10 to 25.00 (step 0.01)
Deactivation level: 95% Activation level: 0.50 to 2.00 xUn/Fn (step 0.01 xUn/
Function 32-4 Fn)
Instantaneous deactivation
Time delay: 0.020 to 300.000 s (step 0.01 s)
Timing accuracy: ± 30 ms or ± 0.5% (greater of both)
Reset Time: 0.000 to 300.000 s (step 0.01 s)
Function enable: No/Alarm/Trip
Function 24-1
Curve, activation level: 110%
Type: Underfrequency or Overfrequency
Function 24-2 Curve, deactivation level: 100%
Activation level: 45.000 to 65.000 Hz (step 0.001 Hz)
Defined time, activation level: 100%
Time delay: 0.020 to 300.000 s (step 0.001 s)
Defined time, deactivation level: 95%
Reset time: 0.020 to 300.000 s (step 0.001 s)
Temporized deactivation
Function 81-1 Function blocked if phase B voltage is lower than 20
volts P-N (35 volts P-P) Timing accuracy for curves selection:
Function 81-2 Activation level: 100%
± 30 ms or ± 5% (greater of both)
Function 81-3 Underfrequency reset level: activation level +
50mHz Timing accuracy for defined time curve selection:
Function 81-4
Overfrequency reset level: activation level - 50 mHz ± 30 ms or ± 0.5% (greater of both)
Temporized deactivation Dead tap: 0.08 to 2.00 xUn (step 0.01xUn)
The frequency measurement is an average value Live tap: 0.08 to 2.00 xUn (step 0.01xUn)
of the frequency measured during 8 cycles. The
accuracy of the Time Delay is the adjusted value Voltage supervision time: 0.060 to 300.000 s (step
plus the necessary time to achieve the measurement 0.001 s)
during 8 cycles.
Voltage difference: 0.05 to 2.00 xUn (step 0.01xUn)
Function enable: No/Alarm/Trip Function 25 (*)
Phase difference: 2 to 90 º (step 1º)
Type: Increase/Decrease
Frequency difference: 0.060 to 10.000 Hz (step
Activation level: 0.100 to 5.000 Hz/s (step 0.001 0.001 Hz)
Hz/s)
Synchro check time: 0.020 to 300.000 s (step 0.001
Time delay: 0.060 to 40.000 s (step 0.001 s) s)
Function 81R-1
Reset time: 0.020 to 300.000 s (step 0.001 s) Number of recloses: 0 to 4 (step 1)
Function 81R-2
Function blocked if phase B voltage is lower than 20 Reclose time 1, 2, 3, 4: 0.020 to 2000.000 s (step
volts P-N (35 volts P-P)
0.01 s)
Function 81R-3
Hold Enable: No/Yes/No Time
Activation level: 100%
Function 81R-4 Function 79 Hold time: 0.000 to 2000.000 s (step 0.01 s)
Temporized deactivation
Reset time: 0.02 to 2000.000 s (step 0.01 s)
The frequency measurement is an average value
of the frequency measured during 8 cycles. The Safe time: 0.020 to 2000.000 s (step 0.01 s)
accuracy of the Time Delay is the adjusted value
plus the necessary time to achieve the measurement Locking possibilities: pulse inputs, level inputs,
during 8 cycles. commands.
Function enable: No/Alarm/Trip Maximum number of openings: 1 to 100,000 (step 1)
Activation level: 1 to 25º (step 1º) Maximum accumulated amperes: 1 to 100,000
M(A2) (step 1)
Reset time: 0.020 to 300.000 s (step 0.001 s)
Repetitive number of openings: 1 to 100,000 (step 1)
Function 78 Function blocked if phase B voltage is lower than 20
volts P-N (35 volts P-P) Time for a repetitive number of openings: 1 to 300
min (step 1 min)
Temporized deactivation
Function 52 Maximum opening time: 0.020 to 300.000 s (step
Measurement accuracy: ±1º or ±10% (greater of 0.001 s)
both)
Maximum closing time: 0.020 to 300.000 s (step
0.001 s)
Circuit breaker status monitoring:
Current measurements: Open breaker activation and
reset threshold: 0.8% In (Without using contacts)
Using contacts: 52a or 52b and 52a and 52b
Function enable: No/Yes
Time delay: 0.020 to 300.000 s (step 0.001 s)
Function 74TCS
Continuity in coils A and B through configurable
inputs

73
Technical parameters SIL-G

Function enable: No/Yes 32 samples/cycle


Time delay: 0.020 to 300.000 s (step 0.001 s) 10 analog channels and 96 configurable digital
channels
Timing accuracy: ± 30 ms or ± 0.5% (greater of
Function 60CTS both) Fault start configurable
Open breaker activation and reset threshold: 0.8% Configurable number of records depending on the
In size:
Detection of the loss of one phase CT
5 records in data and COMTRADE format (300
Function enable: No/Yes cycles each record): 1 to 8 pre-fault cycles + 292 to
299 postfault cycles.
Time delay: 0.020 to 300.000 s (step 0.001 s)
V1, V2 and VP Tap: 0.08 to 2.00 xUn (step 0.01xUn) 25 records in data and COMTRADE format (60
Disturbance fault cycles each record): 1 to 8 pre-fault cycles + 52 to
Function 60VTS
I1, I2 and 3I0 Tap: 0.010 to 20.000 xIn (step recording (DFR) 59 postfault cycles.
0.001xIn)
Timing accuracy: ± 30 ms or ± 0.5% (greater of 50 records in data and COMTRADE format (30
both) cycles each record): 1 to 8 pre-fault cycles + 22 to
29 postfault cycles.
Function enable: No/Yes
Time delay: 0.020 to 1.000 s (step 0.001 s) 100 records in data and COMTRADE format (15
Function 50BF
cycles each record): 1 to 8 pre-fault cycles + 7 to 14
Open breaker activation and reset threshold: 0.8%
In postfault cycles.)
Function enable: No/Alarm/Trip COMTRADE IEEE C37.111-1991
Function AFD (*) Current tap:1 to 20xIn (step 1xIn) Up to 100 fault reports (data format) with maximum
29 events each one
Time delay: 1 to 4 samples (step 1 sample)
The demand for power with the following
Available through configurable inputs thanks to the characteristics:
Function 49T
programmable logic
Load Data Profiling - Number of records: 2160
It allows latching (lockout) the contact trip due to
Function 86 (LDP) - Recording mode circular
programmable logic (PGC: RSFF or SRFF).
Available through configurable inputs and outputs - Sampling rate (interval): configurable through
Function 68 communications (1-60 min)
thanks to the programmable logic (PGC).
OR, OR_1PULSE, OR_PULSES, OR_BLINKING, Depending on Model:
OR_TIMER UP, OR_TIMER DOWN
NOR, NOR_1PULSE, NOR_PULSES, NOR_ - 8 configurable inputs
BLINKING, NOR_TIMER UP, NOR_TIMER DOWN - 24 configurable inputs
AND, AND_1PULSE, AND_PULSES, AND_ - 8 configurable inputs + 4 AFD inputs
BLINKING, AND_TIMER UP, AND_TIMER DOWN
- 16 configurable inputs
NAND, NAND_1PULSE, NAND_PULSES, NAND_ Inputs (*)
BLINKING, NAND_TIMER UP, NAND_TIMER DOWN The voltage of the inputs is the same as the auxiliary
power supply
Programmable logic XOR, OR_1PULSE, XOR_PULSES, XOR_BLINKING,
control (PGC) XOR_TIMER UP, XOR_TIMER DOWN Burden: 24 Vdc: <20 mW
SRFF, SRFF_1PULSE, SRFF_PULSES, SRFF_ 230 Vdc: <200 mW
BLINKING, SRFF_TIMER UP, SRFF_TIMER DOWN
and NON-VOLATILE FF. 24 Vac: <50 mW

RSFF, RSFF_1PULSE, RSFF_PULSES, RSFF_ 230 Vac: < 500 mW


BLINKING, RSFF_TIMER UP, RSFF_TIMER DOWN Depending on Model:
and NON-VOLATILE FF
R_EDGE, R_EDGE_1PULSE - 7 configurable outputs
F_EDGE, F_EDGE_1PULSE - 18 configurable outputs
4 settings groups - 7 configurable outputs + 4 High-Speed Outputs
Settings tables Selectable by input, communications, user - 11 configurable outputs
commands or general setting.
Outputs (*) Model with 7 outputs: 250 V AC – 8 A; 30 V DC – 8 A
SER 3072 events
Model with 11 outputs: 9 outputs 250 V AC – 8 A;
30 V DC – 8 A + 2 outputs250 V AC – 16 A; 30 V
DC – 16 A
Model with 18 outputs: 16 outputs 250 V AC – 8
A; 30 V DC – 8 A + 2 outputs 250 V AC – 16 A; 30
V DC – 16 A
Contact current short duration: 30A – 200ms
Frequency 50/60Hz

74
Technical parameters SIL-G

Burden of current inputs: Current Angles: IA, IB, IC, IN and 3I0.

Voltage Angles: VA, VB, VC, VR, VL*, 3V0, UAB,


<0.015 VA (1 A) & <0.375 VA (5 A) UBC and UCA.
Angle measurements
Burden of voltage inputs: Power factor: Cos PHI-A, Cos-PHI-B and Total
Cos-PHI-C
Accuracy: ±2º
< 70 mVA
Total and per phase active power
Burden of power supply unit: Total and per phase reactive power
Energizing Power
measurements Total and per phase apparent power
Quantities
24-48 Vdc/48-230 Vac/dc: < 10 VA 2% accuracy in rated values with power factor
between 1 and 0.7 (phase shift from 0 to ±45º).
24-230 Vdc/Vac: < 20 VA Energy Positive and negative active energy
measurement Positive and negative reactive energy
Burden for binary inputs:
Busbar Frequency, Line Frequency, df/dt, V/Hz
24 Vdc: <20 mW
Frequency Minimum required voltage: 20V P-N (35 P-P)
230 Vdc: <200 mW
measurements Accuracy: ±0.005 Hz
24 Vac: <50 mW
Range: From 0 to 359 degrees
230 Vac: < 500 mW
Local port (micro USB): Modbus RTU
Phase currents (IA, IB, IC), neutral (IN, 3I0), positive
sequence (I1) and negative sequence (I2) I2/ Remote port RS485: Modbus RTU, DNP3.0 and
I1 Maximum current (Imax), thermal Image (TI), IEC60870-5-103 (selectable by general settings) (*)
Second-harmonic (IA2H, IB2H IC2H), Current Total
Harmonic Distortion (THD-A, THD-B, and THD-C). Communications Remote port RJ45 (10/100 Base-Tx): DNP3.0 TCP/
IP, Modbus TCP/IP (selectable by general settings) +
Current Fundamental values (DFT) SNTP Protocol + Web Server + IRIG-B (*)
measurements
Sampling: 32 samples/cycle RJ45 (10/100 Base-Tx) or SFP Cage (100 Base-Fx):
IEC 61850 without/with redundancy (HSR or PRP) (*)
2% precision in a band covering ±20% of nominal
current and ±4% in the rest of the range 24-48 Vdc (Tolerance: -20%/+10%)
Current measurement range: From 0.01 to 30 times 48-230 Vac/dc (Tolerance: -20%/+10%)
the nominal current
24-230 Vac/dc (24-220 Vdc (±20%) / 100-230 Vac
Power supply (*)
Phase voltage (VA, VB, VC), Line Voltage (VL)*, (±15%))
phase-phase voltage (UAB, UBC, UCA), neutral
voltage (VR, 3V0), positive sequence (V1) and Burdent: 24-48 Vdc/48-230 Vac/dc: < 10 VA
negative sequence (V2), Maximum voltage (VMAX) 24-230 Vdc/Vac: < 20 VA
and V/f.
Operating temperature: -40 to 70ºC
Fundamental values (DFT) Environmental
Storage temperature: -40 to 80ºC
Sampling: 32 samples/cycle conditions
Relative humidity: 95%
Voltage Measured voltage: 1% precision in a band covering
measurements ±20% of nominal voltage and 4% in the rest of the Metallic box
range (ambient temperature)
Panel mounted
Calculated voltage: 2% precision in a band covering
±20% of nominal voltage and 4% in the rest of the Mechanical Height x Width: 198x 187 (mm)
range (ambient temperature) characteristics Depth: 160.8 mm
- With VTs: 3-250 V measured voltage (6-250 V IP-54
calculated voltage)
The required screws to fix the relay should be M4
- Direct connection: From 12 to 1000 V
(*) Optional depending on model
NOTE: ANSI 67, ANSI 67G, and ANSI 67N can be converted into ANSI 51,
ANSI51G, and ANSI 51N respectively by setting the “Directionality” parameter
to NO.

75
Connections diagram SIL-G

Phase-phase + residual voltage, 3 current transformers

C B

A
BUS B
C

A1 A2 A3 A4 A5 A6 A7 A8
D1

In4 In3 In2 In1


A B C N D2
D3
MEASUREMENT
D4
COMMON D5
D6

In8 In7 In6 In5


D7
D8
D9
COMMON D10
D11

In9
D12

INPUTS
D13

In10
D14
D15

In11
D16
D17

In12
D18
VOLTAGE In13 D19
INPUTS D20
D21
B3
In14

D22
B4 D23
In15

D24
B5 D25
In16

B6 D26

B7 E1
output4 output3 output2 output1

B8 SIL-G E2

B9 Protection Relay E3
E4
B10 E5

B11
52
E6
E7
B12 E8
E9
E10
E11
E12
OUTPUTS

E13
output9 output8 output7 output6 output5

LINE E14
E15
SAFETY
GND GROUND E16
E17
E18
E19
E20
E21
E22
E23
output11 output10

E24
E25
E26
AC/DC

B1
POWER

Power Supply
AUX.

COM B2

3 VTs CONFIGURATION (PHASE-PHASE) + RESIDUAL VOLTAGE


3 STANDARD CURRENT TRANSFORMERS
(*) Example of connections diagram

76
Connections diagram SIL-G

3 VTs (Phase-neutral) + residual voltage + 1 VT for synchonism , 4 current transformers

C B

A
BUS B
C

A1 A2 A3 A4 A5 A6 A7 A8
D1

In4 In3 In2 In1


A B C N D2
D3
MEASUREMENT
D4
COMMON D5
D6

In8 In7 In6 In5


D7
D8
D9
COMMON D10
D11

In9
D12

INPUTS
D13

In10
D14
D15

In11
D16
D17

In12
D18
VOLTAGE D19
In13
INPUTS D20
D21
B3
In14

D22
B4 D23
In15

D24
B5 D25
In16

B6 D26

B7 E1
output4 output3 output2 output1

B8 SIL-G E2

B9 Protection Relay E3

52 B10
E4
E5

B11 E6
E7
B12 E8
E9
E10
E11
E12
OUTPUTS

E13
output9 output8 output7 output6 output5

LINE E14
E15
SAFETY
GND GROUND E16
E17
E18
E19
E20
E21
E22
E23
output11 output10

E24
E25
E26
AC/DC

B1
POWER

Power Supply
AUX.

COM B2

3 VTs CONFIGURATION (PHASE-NEUTRAL) + RESIDUAL VOLTAGE


+ 1 VT FOR SYNCHRONISM
(*) Example of connections diagram 4 STANDARD CURRENT TRANSFORMERS

77
Dimensions and cutout SIL-G

78
Selection & Ordering data SIL-G
SIL-G
Feeder & Generator Protection Relay
PHASE CURRENT MEASUREMENT
0 1 A or 5 A
NEUTRAL CURRENT MEASUREMENT
0 1 A or 5 A
VOLTAGE MEASUREMENT
0 Up to 1000 V (direct connection) or 250 V (with VTs)
POWER SUPPLY
A 24-48 Vdc
B 48-230 Vac/dc
C 24-230 Vac/dc (Only for communication models: A, B, F and G)
ADDITIONAL FUNCTIONS
0 -
1 +25 + 27-L + 59-L
COMMUNICATIONS
A A: USB (Modbus RTU) + RS485: (Modbus RTU, IEC60870-5-103 or DNP3.0
Serial)
B B: USB (Modbus RTU) + RS485 (Modbus RTU, IEC60870-5-103 or DNP3.0
Serial) + RJ45 (Modbus TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server
C SNTP Protocol + IRIG-B
C: USB (Modbus RTU) + RJ45 (IEC 61850) + RJ45 (Modbus TCP, DNP3.0 TCP
D or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
D: USB (Modbus RTU) + HSR – (*) SFP Cage (IEC 61850) + RJ45 (Modbus
E TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
E: USB (Modbus RTU) + PRP – (*) SFP Cage (IEC 61850) + RJ45 (Modbus
F TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
F: USB (Modbus RTU) + WiFi + RS485 (Modbus RTU, IEC60870-5-103 or
G DNP3.0 Serial)
G: USB (Modbus RTU) + WiFi + RS485 (Modbus RTU, IEC60870-5-103 or
H DNP3.0 Serial) + RJ45 (Modbus TCP, DNP3.0 TCP or IEC60870-5-104) + Web
Server SNTP Protocol + IRIG-B
I H: USB (Modbus RTU) + WiFi + RJ45 (IEC 61850) + RJ45 (Modbus TCP,
DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
J I: USB (Modbus RTU) + WiFi + HSR – (*) SFP Cage (IEC 61850) RJ45 (Modbus
TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
K J: USB (Modbus RTU) + WiFi + PRP – (*) SFP Cage (IEC61850) + RJ45
(Modbus TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol
L + IRIG-B
K: USB (Modbus RTU) + (*) SFP Cage (IEC 61850) + RJ45 (Modbus TCP,
DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
L: USB (Modbus RTU) + WiFi + (*) SFP Cage (IEC 61850) + RJ45 (Modbus
TCP, DNP3.0 TCP or IEC60870-5-104) + Web Server SNTP Protocol + IRIG-B
INPUTS AND OUTPUTS
0 8 Inputs + 7 Outputs
5 24 Inputs + 7 Outputs
6 8 Inputs + 18 Outputs
7 16 Inputs + 11 Outputs
A 8 Inputs + 7 Outputs + 4 AFD Inputs + 4 High-speed Outputs
MECHANICAL ASSEMBLY
4 Vertical Assembly
5 Vertical Assembly with tropicalization
LANGUAGE
A English, Spanish, German and French
E English, Spanish, Turkish and Russian
F English, Spanish, German and Portuguese
ADAPTATION
B (2) 50 + SOTF + 50G + 50N + (4) 67/51 + (2) 67G/51G + (2) 67N/51N + 67GI +
67NI + 64REF + 46 + 46BC + 49 + 49T + 37 + (2) 27+ 27V1 + (2) 59 + (2) 59N/G
+ 47 + (4) 32 + (4) 81U/O + (4) 81R + 78 + (2) 24 + 79 + 74TCS + 60CTS +
60VTS + 50BF + SHB + CLP + 52 + 86 + HLT

Example of ordering code:

0 0 0 C 1 F 0 4 A B SIL G 0 0 0 C 1 F 04 A B
SIL-G

(*) The SFPs for the models with optical fiber should be included by the user.

NOTES:

» ANSI 67, ANSI 67G and ANSI 67N can be converted into ANSI 51, ANSI 51G and ANSI 51N respectively by setting the “Directionality”
parameter to NO.

» Not all combinations are possible. Please, confirm with Fanox chosen model.

79