Calculation of Motor Starting Time As First Approximation
Calculation of Motor Starting Time As First Approximation
com
http://electrical-engineering-portal.com/calculation-of-motor-starting-time-as-first-approximation
Ca = CM – C L
and shall be well calibrated to prevent it from being either too low, so as starting is not too long and heavy – which
causes risks of temperature rise for the motor – or from being too high on the joints or on the operating
machines.
A generic curve of the above mentioned quantities is shown in the Figure 1 below.
The concept of motor starting time “ta” can be associated to this concept of properly calibrated starting and can
be evaluated making reference to concepts linked to the motion dynamics, but also by introducing simplifying
hypotheses which allows, however, an evaluation with a good approximation.
It is possible to relate the acceleration torque, expressed as a difference between the motor operational torque
and the load torque, to the moment of inertia of the motor “JM”, of the load “JL” and to the motor angular speed,
to obtain the following formula:
The first one consists in considering an average value for the motor
operational torque to be expressed as:
CM = 0.45 x (C s + Cmax)
where CS represents the inrush torque and Cmax the maximum torque;
The second one concerns the torque due to the load and which can be correct by
applying the multiplying factor KL linked to the load typology as in Table 1 below.
KL 1 0.33 0.5 0
In order to better understand the significance of the coefficient K L we associate to the type of load indicated in
the table the torque characterizing the starting phase of the load by means of the following assumptions:
Table 2 – Typical values of some electrical and mechanical parameters of a three-phase asynchronous motor
Table 2 – Typical values of some electrical and mechanical parameters of a three-phase asynchronous motor (CLICK TO ENLARGE)
Frequency 50 Hz
from which
ta = (2 · π · 1500 · (2.9 + 60)) / 60 · 851.6 = 11.6 s
from which
ta = (2 · π · 1500 · (2.9 + 60)) / 60 · 1923.6 = 5.14 s
For both typologies of load, the esteemed motor starting time results to comply with the instruction given by the
manufacturer regarding the maximum time admitted for DOL starting . This indication can be also taken as a
cue for a correct evaluation of the thermal protection device to be chosen.
Reference // Three-phase asynchronous motors: generalities and proposals for the coordination of protective
devices – ABB