13 Laundry Facility

A. Coordination: See Laundry for criteria and applicable design requirements, see
<11A>.

B. Facility Features: Provide the following:

1. Diffusers: Locate adjustable type ceiling mounted diffusers for cooling within
2.7 m (9 ft.) of work stations.

2. Dryers: If dryer enclosure is located adjacent to an exterior wall, provide


louvers for combustion air and size to prevent significant negative pressure in
the enclosure when dryers operate. If dryer enclosure is not on an exterior
wall, provide an outside air supply fan equal to the total exhaust volume.

3. Flatwork Ironer Vacuum Exhaust Air Duct:

a. Provide dedicated, welded 304 stainless steel exhaust duct and slope
back to equipment for condensation drainage. Run duct directly outdoors.

b. Equip ducts exceeding 7.6 m (25 ft.) in overall length with in-line booster
fans having a capacity equal to the equipment exhaust capacity.

c. Do not combine vacuum exhaust duct with other ductwork systems.

C. Valet: Provide individual FCU with thermostat over each work station.