Professional Documents
Culture Documents
Marriott Hotels
Marriott Hotels
13 Laundry Facility
A. Coordination: See Laundry for criteria and applicable design requirements, see
<11A>.
1. Diffusers: Locate adjustable type ceiling mounted diffusers for cooling within
2.7 m (9 ft.) of work stations.
a. Provide dedicated, welded 304 stainless steel exhaust duct and slope
back to equipment for condensation drainage. Run duct directly outdoors.
b. Equip ducts exceeding 7.6 m (25 ft.) in overall length with in-line booster
fans having a capacity equal to the equipment exhaust capacity.
C. Valet: Provide individual FCU with thermostat over each work station.
October 2022 marriott international. all rights reserved. Marriott Hotels Laundry Facility 1