Professional Documents
Culture Documents
CONTENTS
5. NOISE
5.1 Noise Generation Principles ...................................................................................... 102
5.2 Noise Types and Transmission Routes ...................................................................... 103
5.3 Noise Reduction Techniques..................................................................................... 106
5.3.1 Noise reduction techniques ............................................................................ 106
5.3.2 Specific noise reduction examples.................................................................. 110
5.3.3 Noise filters ................................................................................................... 112
5.4 Leakage Currents ..................................................................................................... 114
5.4.1 Earth leakage current..................................................................................... 114
5.4.2 Line leakage currents..................................................................................... 115
5.5 Grounding (Earthing) ................................................................................................ 116
5.5.1 Grounding method and grounding work........................................................... 116
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
6.1 Environment and Installation Conditions .................................................................... 118
6.1.1 Inverter reliability and temperature ................................................................. 118
6.1.2 Ambient temperature ..................................................................................... 118
6.1.3 Heat generated by the inverter ....................................................................... 119
6.1.4 Heat interference and ventilation in an enclosure ............................................ 120
6.1.5 Installation of discharge resistors ................................................................... 121
6.1.6 Direction of inverter installation ...................................................................... 121
6.1.7 Standard installation environment specifications ............................................. 121
6.1.8 Dirt-protection structure ................................................................................. 123
6.1.9 Considerations for installing the inverter in an enclosure ................................. 123
6.1.10 Inverter-driven explosion-proof motor ............................................................. 125
6.2 Inverter W iring ......................................................................................................... 126
6.2.1 Terminal connection diagram ......................................................................... 126
6.2.2 Main circuit wiring .......................................................................................... 127
6.2.3 Control circuit wiring ...................................................................................... 128
6.2.4 I/O cable wiring distances .............................................................................. 130
6.2.5 BU brake unit wiring....................................................................................... 131
6.2.6 FR-BU brake unit wiring ................................................................................. 132
6.2.7 High-duty brake resistor (FR-ABR) wiring ....................................................... 133
This chapter deals with the basic characteristics of a squirrel-cage, three-phase, induction motor to
be considered for capacity selection and operation when it is driven by an inverter.
Since motors operated with a commercial power supply and operated by an inverter differ in charac-
teristics, it is essential to understand the following points.
POINTS OF UNDERSTANDING
1. Relationships between speed, current and torque.
2. V/f (voltage/frequency ratio) pattern and basic motor characteristics.
3. Differences in characteristics of the motor when operated by inverter and when operated with
commercial power supply, e.g. torque, current, temperature.
4. Definition of torque boost.
Motors may be classified in various ways. W hen they are divided by the operation principle and
structure, there are the following motor types. Among them, inverter-driven motors are mainly
three-phase squirrel-cage motors.
Classification Classification by Classification
by power supply operation principle by structure
DC motor
Synchronous
Motor
motor
Wound-rotor
AC motor
motor
Split-phase start motor
Single-phase
Induction motor Capacitor motor
motor
Repulsion-start motor
Squirrel-cage
motor
Drip-proof motor
Three-phase
Indoor motor
motor
(Standard motor) Totally-enclosed,
fan-cooled motor
Constant-torque motor
Geared motor
–1–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Due to its rigid and simple structure, a squirrel-cage motor can be used in a wide variety of environ-
ments such as outdoors, underwater and potentially dangerous circumstances (explosion-proof
motor).
From a structural point of view, motors are largely classified into a totally enclosed, fan-cooled type
and a drip-proof protection type. Fig. 1.1 shows an example of totally enclosed, fan-cooled type motor
structure. W hen roughly divided in structure, the motor consists of a fixed area and a rotary area and
each area is made up of mechanical parts and electrical parts. A fan coupled to the shaft is provided
for cooling as the motor itself will generate heat.
W hen the motor is run by an inverter at low speed, its speed decreases and the cooling effect of the
fan reduces. To suppress the temperature rise of the motor within the specified value, permissible
load torque must be reduced.
Coil
Fan (for cooling) Bracket
Bearing
–2–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Generator region
Current
N
Speed [r/min]
Synchronous
speed (N 0 )
Fig. 1.2 Relationships between Speed, Current and Torque of Motor when started direct-on line
–3–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
As seen in equation (1.1), motor speed can be varied by changing the power supply frequency applied
to the motor or the number of poles. Alternatively, the voltage applied to the motor may be changed.
Frequency is changed .................. Inverter
Number of poles is changed ......... Pole-change motor
Voltage is changed ...................... PS motor (primary voltage control)
Slip is changed ............................ W ound-rotor motor
An eddy-current coupling type variable speed motor (Mitsubishi AS motor) has an eddy-current type
electric coupling between the output shaft and the drive motor which keeps rotating at the rated
speed. As the speed of the output shaft is varied by slip caused by the coupling section, this motor is
similar to a slip (S) changing system.
(1) At start (zero speed), "slip" is 100% (often represented "slip 1"). W hen the frequency is increased
gradually by the inverter (called frequency start), "slip" is about several %.
(2) W hen the motor is run at the rated torque, "slip" is generally about 3 to 5%. W hen load torque
increases (overload), "slip" and motor current also increase.
(3) Slip is negative when the speed is greater than the synchronous speed (N>N 0 ).
–4–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
T L large
T L small
N 2 N 1 Speed [r/min]
Output torque
Voltage low
TL
N 2 N 1 Speed [r/min]
–5–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Note: The "rated speed" is the speed at the rated motor torque when the rated voltage and frequency
are applied.
Exercise
Find the rated torque (T M ) of a 3.7kW four-pole motor whose rated speed is 1730 [r/min].
3.7
Rated torque (TM) = 974 × = 2.08 {kgf ⋅ m}
1730
3.7
Rated torque (TM) = 9550 × = 20.4 {N ⋅ m}
1730
W hen the motor is inverter-operated, the rated speed may be replaced by synchronous speed (N 0 ) in
the calculation of the rated torque. For exact calculation, use the rated speed.
–6–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Fig. 1.5 shows the comparison results of motor torque and current characteristics between operation
of a motor with a commercial power supply (commercial power supply operation) and operation of a
motor by an inverter (inverter operation). [%] indicates the ratios of torque and current to the rated
torque and rated current, respectively. (Example: 4-pole motor)
Speed-
torque Tm
300 (Maximum
curve torque)
250
Torque
Torque
200 [%]
[%] T S (Starting torque)
150 150
Rated
Rated torque torque
100 100
50
50Hz 60Hz 50
0 15Hz 20Hz 30Hz 50Hz 60Hz
0 1500 1800 [r/min] 0
0 450 600 900 1500 1800 [r/min]
Features • Starting torque (Ts) is large but starting • To suppress the starting current, the motor
current (Is) is also large. is started at low frequency. Starting torque
• Speed is fixed by the power supply is also small.
frequency. • Speed can be set as desired independent
of the power supply frequency.
Approximate characteristic values of a standard motor operated with a commercial power supply
(1) Starting current, Is = 600 to 700 [%] (2) Starting torque, Ts = 150 to 250 [%]
(3) Maximum torque, Tm = 200 to 300 [%] (4) Slip under rated load, S = 3 to 5 [%]
–7–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Table 1.2 Comparison of Values for Common Use with Three Ratings
Power Supply Rated Current [A] Rated Speed [r/min] Rated Torque
{kgf·m} [N·m]
200V 50Hz 14.6 1420 2.54 24.9
200V 60Hz 14.2 1710 2.11 20.7
220V 60Hz 13.4 1730 2.08 20.4
Supposing that the rated currents for the corresponding power supply ratings are I 200/50 , I 200/60 and
I 220/60 (I 400/50 , I 400/60 and I 440/60 for 400V power supplies) respectively, the following relationship is
established, the current at 50Hz is maximum current.
I 200/50 > I 200/60 > I 220/60 (I 400/50 > I 400/60 > I 440/60 )
As seen from equation (1.3) in Section 1.3.6, the magnitude of the rated motor torque differs between
50Hz and 60Hz.
P [kW ] P
Torque at 50Hz TM = 974 × = 974 × = 0.649 × P
N [r / min] 1500
20% higher
P [kW ] P
Torque at 60Hz TM = 974 × = 974 × = 0.541 × P
N [r / min] 1800
At 50Hz, torque (force) is large but motor current is also large. Hence, the temperature rise of the
motor is greater than that at 60Hz.
Temperature high
Temperature low
50Hz 60Hz
Large current Smaller current
–8–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Here, "at 50Hz" does not indicate the magnitude of the power supply frequency. Please
CAUTION
understand that it indicates "at the output of the rated torque calculated at 50Hz."
1.5.3 Why is voltage also varied when motor speed is varied by an inverter?
To vary the motor speed, only the frequency may be changed as indicated in equation (1.1). However,
if the output frequency is changed to 50Hz or less with the voltage kept constant (for example, 200V),
the magnetic flux of the motor increases (saturates). Therefore, the current increases and the motor
becomes overheated, then burnt.
To prevent this, the magnetic flux should be kept constant. As the magnetic flux is directly
proportional to the voltage and inversely proportional to the frequency as indicated in equation (1.5),
the application of a voltage which will always establish this relationship will solve this problem.
Voltage (V)
Magnetic flux ∝ = Constant ........................................................................ (1.5)
Frequency (f)
Supposing that the speed is halved (from 60Hz to 30Hz), for example, V/f is as follows:
W hen the motor temperature is taken into consideration, the problem can be solved by also varying
the voltage as described above. However, it is also necessary to think of the torque.
–9–
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Voltage ( V )
Torque (T ) = K ⋅ ⋅ I ........................................................................................... (1.6)
Frequency ( f )
K: Constant, I: Current
– 10 –
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Fig. 1.8 shows the output characteristics of Mitsubishi standard squirrel-cage motors (4 poles) used
with an inverter of the same capacity.
Continuous Short-time
100 operation
maximum torque
90 torque
85
80 75
70 70
65
50
45
35 38
30 30
25
36 20 30 60 120 36 20 30 50 120
Output frequency [Hz] Output frequency [Hz]
Output voltage
V/f pattern
Output voltage
V/f pattern
(1) Continuous operation torque is permissible load torque restricted by the temperature rise of the
motor. It is not the maximum value of motor-generated torque.
(2) Short-time maximum torque is maximum torque generated by the motor within the overload
capacity (150%) of the inverter. Accordingly, as the inverter capacity is increased, the maximum
torque also increases.
The short time of the short-time maximum torque indicates the permissible overload current flow
time of the inverter, i.e. within 1 minute.
* There are constant torque motors which can be run continuously at low speed and high torque.
The frame size is increased, and it is designed to suppress heat generated by the winding.
– 11 –
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
I1 r1 jX 1 jX 2
V : Primary voltage
Im V' : Primary induced electromagnetic voltage
I2
I1 : Primary current
I2 : Secondary current (Converted from primary value)
Im : Excitation current
rm r1 : Primary resistance
V V’ r2 : Secondary resistance (Converted from primary
r 2 /S value)
rm : Core loss resistance
Xm Xm : Excitation reactance
X1 : Primary leakage reactance
X2 : Secondary leakage reactance
S : Slip
W hen the motor is run without load in a secondary circuit open state, the equivalent circuit is as shown
in Fig. 1.10.
r1 jx1
Im
Im
∆V
rm
V Im: Excitation current
V’
Xm
– 12 –
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
V V
220V 220V
Torque
boost
f ∆V f
Base frequency Base frequency
Fig. 1.11 Ideal V/f Pattern of Motor Fig. 1.12 Actual V/f Pattern of Inverter
In magnetic flux vector control, ∆V is automatically controlled according to a voltage drop resulting
from the resistive components (r) and reactive components (x), etc. of the motor.
Manual torque boost is as shown in Fig. 1.13.
∆V
f
Base frequency
The increase in voltage is kept constant to the frequency (f) (independent of motor current).
– 13 –
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Fig. 1.14 shows relationships between motor torque and current when the voltage is increased by
torque boost.
Since there is a current limit (150% of the rated current) on an inverter, the maximum value of starting
torque is determined within this current range. If the torque boost setting is too large, the motor
current will exceed the current limit, activating overcurrent protection.
Current
Torque boost large
[%]
100
0
Load factor [%]
– 14 –
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
W hen the torque boost setting is large, the current will vary as described below according to the load
condition:
1) Light load ........... Since the magnetic flux of the motor core saturates, the current will increase and
overcurrent protection is more liable to be activated.
2) Heavy load ......... As torque boost compensates for a voltage drop caused by the primary winding
and cables of the motor to develop large motor torque, motor slip reduces and
the current is smaller than under light load. (Refer to Fig. 1.15 "Example of Load
Factor vs. Motor Current.")
Exercise
W hen the torque boost setting of the inverter is increased, how does the motor current value
change?
Though it depends on the load condition (light or heavy load), increasing the torque boost setting
will increase the motor current, generating large starting torque. During acceleration under heavy
load, torque increases and motor slip decreases. As a result, the average current can be kept
small during acceleration.
If the torque boost setting is too large, the motor current immediately after a start will exceed the
current limit, activating overcurrent protection.
– 15 –
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
Load torque characteristics differ according to application. Their typical examples and applicable V/f
patterns are shown below. W hen a motor is operated by an inverter, a V/f characteristic matching the
load characteristic can be selected.
Load
torque
type
2
T = constant: T/N = constant: T × N = constant:
constant torque load squared variable torque constant output load
load
Fig. 1.18 Load Types and V/f Patterns
– 16 –
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
2
1.9 Acceleration/Deceleration Time and GD
Acceleration/
Deceleration
T ime Acceleration Time Deceleration Time
Operation
Commercial 2
Total GD ⋅ N
2
Total GD ⋅ N
power ta = [s] td = [s]
operation 375 × {TM × {15
. to 2} − TL } 375 × TL
N : Rated speed [r/min] N : Rated speed [r/min]
T M : Rated motor torque [kgf·m] T L : Load torque [kgf·m]
T L : Load torque [kgf·m]
2 2
Total GD ⋅ N Total GD ⋅ N
ta = [s] td = [s]
38.2 × {TM × {15
. to 2} − TL } 38.2 × TL
N : Rated speed [r/min] N : Rated speed [r/min]
T M : Rated motor torque [N·m] T L : Load torque [N·m]
T L : Load torque [N·m]
Inverter 2
Total GD ⋅ ∆N 2
TotalGD ⋅ ∆N
operation ta = [s] td = [s]
375 × (TM ⋅ α − TL ) 375 × ( TM ⋅ β + TL )
∆N : Difference between motor speed before and ∆N : Difference between motor speed before and
after acceleration [r/min] after deceleration [r/min]
T L : Maximum load torque [kgf·m] T L : Minimum load torque [kgf·m]
α : Average acceleration torque factor (about β : Average deceleration torque factor
1.1 boost standard) (regenerative braking torque factor)
2
Total GD ⋅ ∆N TotalGD ⋅ ∆N
2
ta = [s] td = [s]
38.2 × (TM ⋅ α − TL ) 38.2 × ( TM ⋅ β + TL )
∆N : Difference between motor speeds before and ∆N : Difference between motor speeds before and
after acceleration [r/min] after deceleration [r/min]
T L : Maximum load torque [N·m] T L : Minimum load torque [N·m]
α : Average acceleration torque factor (about β : Average deceleration torque factor
1.1 boost standard) (regenerative braking torque factor)
2 2 2 2
Total GD = motor GD + load GD [kgf·m ]
(1) Due to a difference in average acceleration torque factor, acceleration time from commercial
power supply operation is shorter than using inverter operation.
(2) Due to regenerative brake operation in inverter operation as opposed to a coasting stop in
commercial power operation, deceleration time in inverter operation is much shorter than in
commercial power operation.
To make a sudden stop in commercial power operation, a mechanical brake is used or a DC
dynamic brake or negative-phase braking system is employed.
– 17 –
1. CHARACTERISTICS OF AN INVERTER-DRIVEN MOTOR
2
1.9.2 What is GD ?
2
(1) GD is the inertia of an object converted into a numerical value. A heavy object with a large
diameter has high inertia and a light object has low inertia.
Fast start
Large Slow start Small Fast stop
Slow stop
2
(2) Finding GD of a rotating cylinder
1 π
D [m] GD 2 = × W ⋅ D 2 = × ρ ⋅ L ⋅ D 4 [kgf ⋅ m 2 ]
2 8
: 7.2 × 10
3
Cast iron
2
(3) For the calculation of acceleration/deceleration time, load GD ( GD L2 ) must be converted into the
equivalent value at the motor shaft.
GD converted into the equivalent value at the motor shaft = GD L2 × i (i=reduction ratio)
2 2
2
(4) A load having a large GD takes a long time to accelerate or decelerate. Hence, a large motor
torque is required for acceleration or deceleration in a short time.
– 18 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
This chapter describes the operational principles of the fundamental circuits of an inverter which
develop the variable frequency and variable voltage output to control motor speed.
In an inverter, which is a power converter designed for a motor (from constant frequency and voltage
input to variable frequency and voltage output), the input power is a commercial power supply but the
current is different in waveform from a sine wave, and its output waveform is different from the input
waveform.
These characteristic waveforms created due to the inverter's operational principles deeply concern
the selection of a motor, peripheral equipment and measurements of current, voltage, etc. For this
reason, it is important to understand the operation of each circuit of the inverter and their
relationships.
Fig. 2.1 shows the structure of a transistorized inverter which makes alternating-current power of any
frequency from commercial power (50Hz or 60Hz AC) to run a motor at variable speed. It consists of
a main circuit composed of a converter circuit (which converts commercial power into a direct current
and smooths ripples included in this direct current) and an inverter circuit (which converts the direct
current into an alternating current of variable frequency), and a control circuit which controls these
circuits.
Inverter unit
Main circuit Motor
AC Converter Inverter
IM
power circuit circuit
Control circuit
The converter circuit converts an alternating current into a direct current. The inverter circuit then
reconverts the direct current into the alternating current. In the transistorized inverter unit, the whole
unit including the converter circuit is referred to as the inverter.
As described above, the main circuit of the inverter is made up of two power converters which differ
greatly in devices used and characteristics. The operational principles of the inverter and converter
circuits will be described.
– 19 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
Switch S1 Switch S3
Lamp
+
DC
power E + – S1, S4 ON
supply A L B 0
– + S2, S3 ON Time
–
Switch S2 Switch S4
• By turning switches S1 and S4 on, a current flows in lamp L in the direction of arrow A.
• By turning switches S2 and S3 on, a current flows in lamp L in the direction of arrow B.
Therefore, turning on-off the S1-S4 and S2-S3 combinations alternately makes an alternating
current in which the direction of the current flowing in lamp L reverses alternately.
Time
S1, S4 ON
S2, S3 ON
– 20 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
Generally, S1-S4 and S2-S3 are turned on for the same duration. Supposing that the sum of
durations in one cycle is t 0 seconds, frequency (f) is as follows:
1
f=
t0
[Hz] Time
t0
– 21 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
These different control systems provide different motor characteristics (such as vibration, noise,
torque ripple, motor current ripple, torque response). (Refer to Table 2.1.)
– 22 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
1 carrier
In the PW M system, several switching pulses are generated during a single cycle and varied in width
to vary the output voltage. The number of switching pulses generated during one second is called the
carrier frequency. In the PW M system, motor vibration and motor noise of frequency components
proportional to this carrier frequency are generated.
– 23 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
The carrier frequency of a low acoustic noise inverter is extremely high, 15kHz to 20kHz, and is high
when compared to the human audio-frequency range (approximately 15Hz to 20kHz). Hence, we
hardly hear electromagnetic acoustic noise from a motor and a low acoustic noise inverter has been
achieved. However, since transistors in the inverter circuit are generally limited to about 2kHz, IGBTs
(Insulated Gate Bipolar Transistors) are used.
The FR-A500 series inverters adopt Power modules which use IGBTs as power switching devices.
– 24 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
Current waveform
Voltage waveform
10ms/DIV
Fig. 2.10 Measurement Examples of Output Current and Voltage Waveforms
Fig. 2.10 of the FR-A500 Series Inverter (40Hz) (2kHz carrier frequency)
Current waveform
Voltage waveform
2ms/DIV
Fig. 2.11 Measurement Examples of Output Current and Voltage Waveforms
Fig. 2.11 of the FR-A500 Series Inverter (Fig. 2.10 with smaller time base)
(2kHz carrier frequency)
– 25 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
D4 D5 D6
N
2V E
Voltage D1 D2
I
Inverter
AC power
V C E circuit
supply
(load)
Current (I)
t1 D3 D4
t2
D1
D4 D2
ON D3
ON Fig. 2.13 Converter Principle
• W hen a sine-wave voltage of effective value (V) (peak value 2 × V ) is input to the converter
from an AC power supply, a current flows only during portion t 1 , where supply voltage is higher
than voltage (E) of the converter DC output section, through diodes D 1 , D 4 .
• In the negative half cycle of the AC voltage, diodes D 2 , D 3 conduct in portion t 2 and a negative
input current flows in the AC side.
Therefore, the AC input current of the converter is not a sine wave but a distorted current wave
including harmonics.
– 26 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
D2
Diode D3
current
D4
Output voltage
D5 (without smoothing capacitor)
D6
Current flowing in D1
Phase R
Current flowing in D4 Smoothed DC voltage
Current flowing in D3
Phase T
Current flowing in D6
– 27 –
2. INVERTER PRINCIPLES AND ACCELERATION/DECELERATION
CHARACTERISTICS
N
When there is no inrush When there is an inrush
current suppression circuit current suppression circuit Fig. 2.16 Inrush Current Suppression
Fig. 2.16 Circuit
I
I The peak value is
Peak value large decreased to
prevent converter
module damage.
Time Time
About 50ms
It is not recommended that this method of Inverter power control is used regularly.
If the inverter is frequently switched on-off with a magnetic contractor (MC) etc, a peak current will
flow in the converter every time the inverter is switched on-off, shortening the life of the diodes.
This will also affect the switching life of the inrush current suppression circuit.
The converter circuit is designed to make DC power. The motor is started by switching on the
transistor base current. (Switch on the control input terminals STF or STR.)
Charging current
DC voltage Power supply voltage
Inrush
current
Fig. 2.18 Measurement Example of Inverter Input Current and Voltage Waveforms
– 28 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Frequency (f)
Fig. 2.19 V/F Control
* If the torque boost setting is too large, sufficient torque will be developed but an excessive current
will flow, causing the inverter to be more liable to an OCT (overcurrent) trip.
To generate more torque at low speeds without the risk of OCT trip, advanced magnetic flux vector
control and general-purpose magnetic flux vector control are available.
– 29 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Load Load
torque 300 torque 300
(%) 200 (%) 200
150
100 Output 100
3 6 10 20 30 40 50 60 frequency
0 (Hz) 0 Output
3 10 30 50 60 frequency
−100 −100 (Hz)
−150
−200 −200
– 30 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
W ith this control system, the functions in half-tone portions are added to general-purpose magnetic
flux vector control to ensure that high torque can be developed at low speed. Also, the auto tuning
function allows the inverter to measure and store the motor circuit constants, ensuring accurate
arithmetic operation and a wide speed control range.
Advanced Magnetic Flux Vector Control Conventional V/F Control
200% 200%
40 torque 40 torque
50Hz 60Hz
Load 20 100% Load 20 10Hz 30Hz 100%
torque torque
torque 6Hz 30Hz 60Hz torque 3Hz
0 200 400 600 800 1000 1200 1400 1600 1800 2000
0 300 900 1500 1800
(Nxm) (Nxm) 1Hz
Speed Speed
↑ −20 (r/min) ↑ −20 (r/min)
−40
Fig 2.23 Speed-Characteristic Example under Advanced Magnetic Flux Vector Control
– 31 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Ñìïîòâ
0 1500 3000
Speed r/min
(For 5.5K to 22K)
Fig. 2.25 Output Characteristic Example Fig. 2.26 Appearance of Vector Control-Dedicated
of Vector Control-Dedicated Motor Motor (SF-VR)
– 32 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
L1 L2
r1
r1 : Primary resistance
r2 : Secondary resistance
r2
L1 : Primary inductance
L2 : Secondary inductance
M M : Excitation inductance
(1 − S) r2 : Mechanical output equivalent
(1 − S) r2 S ; resistance
S
• Since the inverter itself measures the constants of any motor such as a special motor or another
company's motor, advanced magnetic flux vector control and vector control can be used more easily
in a wider range of applications.
• As the motor constants can be measured accurately, starting torque and low-speed torque have
been improved for advanced magnetic flux vector control.
• If the wiring length exceeds 30m, the inverter can be run under advanced magnetic flux vector
control and vector control if autotwring has been performed.
• Either of two tuning modes (FR-A500 series) can be selected to match the machine's state.
• Easier and faster constant measurement without the motor being rotated. (Offline auto tuning)
• Performance of automatic magnetic flux vector control is enhanced by more accurate constant
measurement with the motor being rotated. (Offline auto tuning)
• Advanced magnetic flux vector control
Online auto tuning is designed to make fast tuning of the starting motor conditions to ensure
accurate operation which is unaffected by motor temperature and producing high-torque and steady
operation down to ultra-low speed.
– 33 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Undervoltage UVT
Overload THT
– 34 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
External
thermal
relay
operation
Voltage detection Current detection OH
Power supply
voltage detection
Brake transistor
Instantaneous power conduction detection
failure protection Parameter unit
Brake transistor fault FR-PU04 PARAMETER UNIT
detection
60.00Hz
STF FWD PU
Temperature
detection MON SET EXT PU
device 7 8 9
overhead
4 5 6 FWD
CPU
1 2 3 REV
STOP
0 READ
WRITE
RESET
Connection fault
Connector
Open collector output
– 35 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
About 400V
200% Inverter output shut-off current Inverter output shut-off voltage
(About 800V)
} "Overload" inverse-time
characteristics
About 385V
(About 770V)
"Stall prevention" operation voltage
*1: When the operation current level is *2: About 150V (about 300V) when
changed, the new current (%) applies. converted to AC input voltage.
– 36 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Parameter unit
FR-PU04
FR-PU04 PARAMETER UNIT
Liquid crystal
display
Inverter trip.
OC During Acc
0.00Hz
Note 1: The alarm output signal may depend upon the setting of the inverter parameters. Please
refer to the relevant inverter manual for detailed information.
– 37 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Protective function
activated
Time
Output
Inverter shut-off
output
Time
Output stop held 10ms
Fault output signal terminal A-C Time
Reset signal terminal RES-SD Time
Start signal terminal STF-SD Time
– 38 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
2.6.1 Start
W hen the inverter start signal (terminals STF-SD or 100
Torque
STR-SD) and frequency command signal are input to the 80 TL
(%)
inverter, the inverter outputs the starting frequency, and
the motor generates torque. 50
W hen the starting torque of the motor at the starting
frequency is larger than the starting torque of the load, the 4Hz 6Hz 8Hz
motor begins to rotate. If the load torque is larger, the 0
output frequency is increased gradually with the motor
locked, and when the motor starting torque exceeds the Current 150 Current limit
(%) 100 of inverter
load torque T L as shown in Fig. 2.33, the motor starts.
However, if the frequency at start increases, the motor lock
50
current will also increase and may reach the current limit, 4Hz 6Hz 8Hz
resulting in an overcurrent (OC1) or overload (THT) trip. 0
Speed (r/min)
The starting torque of an inverter-driven (V/F control) motor is different from that of a motor
operated with a commercial power supply and defined as follows:
The starting torque of an inverter is the maximum torque that can be developed within the 150%
overcurrent immunity range of the inverter in a low frequency region. Since the starting torque of the
inverter-driven motor is defined differently from that of the motor operated with a commercial power
supply, this starting torque is called "maximum starting torque".
For example, the maximum output frequency within the current limit of the inverter is 6Hz in Fig. 2.33.
Hence, the maximum torque at 6Hz is the maximum starting torque.
At the frequency of less than 6Hz, the inverter will not result in an overcurrent trip if the motor shaft
is locked. Note that if the motor shaft is locked for a long time, the inverter may result in overload
shut-off (THM).
– 39 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
2.6.2 Acceleration
After it has started, the inverter increases the output frequency gradually up to the frequency
command value according to the acceleration time setting.
As described in Section 1.3.3 "W hat is "slip" ?", if the motor increases its speed greater than
synchronous speed proportional to output frequency (f), a delay will correspond to the slip.
2
This slip is influenced by the values of load GD , load torque and motor-generated torque. W hen the
acceleration time setting is long enough, output frequency (f) and motor speed (N) rise in proportion
to each other. (Refer to Fig. 2.34.)
However, if the acceleration time setting is too small, a difference between f and N is large and slip
remains large (refer to Fig. 2.35). This will increase motor current and may activate the stall
prevention function or current shut-off protection function due to overcurrent. (If the motor capacity is
unchanged and the inverter capacity is increased, immunity increases relative to overcurrent, and the
protective function is less liable to be activated.)
In a transistorized inverter which suppresses the starting current, acceleration time must be set to
match the load.
(%)
Rated Motor Current
↑ ↑
Rated current Rated current
150 150
100 100
Time Time
– 40 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
– 41 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Action to be taken when overcurrent shut-off OC2 is activated during constant speed operation.
(a) During operation at less than the base frequency.
• Increase manual torque boost.
(b) During operation at less than 10 Hz.
• Decrease manual torque boost gradually.
(c) W hen load torque is temporarily larger than 150% of the motor rating, increase the inverter
capacity.
2.7.1 Deceleration
By switching off the inverter starting signal (STF, STR) or
setting the frequency setting signal to a value lower than
the output frequency, the output frequency is decreased N f
gradually according to the deceleration time setting. Motor speed (N)
↑ ↑
During deceleration, motor speed is higher than Slip (negative)
synchronous speed equivalent to the output frequency of Frequency (f)
the inverter and the motor acts as a generator to return
energy to the inverter (this operation is called
→ Time
regeneration). Therefore, the DC voltage (voltage of the Deceleration
smoothing capacitor) rises. time setting
W hen the motor is operated with a commercial power
supply, switching off the motor run stopping magnetic Fig. 2.38 Deceleration Characteristic
contactor causes the motor to coast to a stop with only load
torque acting as braking force. (For stopping time, refer to Section 1.9.1.)
W hen the motor is operated with the inverter, switching off the start signal does not cause the motor
to coast to a stop immediately but to decelerate to a stop according to the deceleration time setting.
At this time, the motor state is as indicated below according to the deceleration time setting:
– 42 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
2.7.2 Stop f
(1) W hen the inverter starting signal (STF, STR) is ↑
DC dynamic brake
switched off, output frequency decreases as shown in Deceleration operation frequency
Fig. 2.40. W hen it falls to or below the DC dynamic
brake operation frequency, a DC voltage is applied to
→ Time
the motor to make it stop. This is called DC dynamic
braking.
A given period after DC dynamic braking, the
transistor base signal is switched off to shut off the DC dynamic braking
output.
Fig. 2.40 DC Dynamic Brake Operation
(2) W hen the magnetic contactor (MC) on the inverter
input side is switched off, the inverter detects a power failure and shuts off the transistor base,
coasting the motor to a stop. W hen the deceleration-to-stopping function of the inverter is to be
used, do not switch off the inverter input power.
DC braking
W hen the DC voltage is applied to the motor which is rotating, brake torque is generated. W hen
the motor comes to a stop, brake torque is stopped.
(For the FR-A500 series, the operation frequency, operation time and operation voltage of this
brake can be changed.)
– 43 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
DC bus voltage
Motor current
DC bus voltage
Motor current
– 44 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
2.8.1 Efficiency
As the inverter is a power converter consisting of a converter circuit and an inverter circuit as
described in Section 2.1, losses are produced in these circuits. It is generally said that the use of an
inverter saves power. This reason will be described using related equations.
Motor
Power
supply PIN PM POUT
Inverter IM Load
IINV IM
Loss W M
P: Power
Loss W INV I: Current
Efficiency ηM
Efficiency ηINV
Output Output
Efficiency = = .......................................................................................... (2.1)
Input Output + loss
Inverer output power Inverter output power (PM)
Inverter input power (PIN) = (PM) + Inverter loss ( W INV ) = ........ (2.2)
(Motor input power ) Inverter efficiency(ηINV )
Motor output (POUT )
Motor input power (PM) = Motor output (POUT ) + Motor loss ( W M) = ............................. (2.3)
Motor efficiency(ηM)
Machine power
Motor output (POUT ) = Motor output torque × Motor speed = ...................................... (2.4)
Machine efficiency
Motor output
Inverter input power = Motor output + Motor loss + Inverter loss = .................... (2.5)
Overall efficiency
where, Overall efficiency = Inverter efficiency(ηINV) × Inverter driven motor efficiency (ηM) ................ (2.6)
As seen from formula (2.5), inverter loss is added to motor loss which is larger when a motor is
operated with an inverter than when it is operated with a commercial power supply under the influence
of harmonics, etc. W hen the motor is inverter-operated at the same speed as when it is operated with
a commercial power supply, therefore, the input power of the inverter-operated motor is always larger
than that of the motor operated with a commercial power supply. However, since the reduction in
motor speed by the inverter decreases motor output, input power is smaller as speed is lower if load
torque is constant. (For variable torque load such as a fan or pump, input power becomes much
smaller, leading to energy saving.)
– 45 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
– 46 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Inverter
NFB FR-BAL
R X
R
Power S Y
supply S
T Z
T
FR-BEL
P1 P
* The length of the cables
Always disconnect the jumper between the reactor and
across terminals P1-P. the inverter should be as
Wiring distance should be 5m max.
short as possible (5m
max.), and their size should
be equal to or larger than
that of the power supply
NFB N P1 P (PR)
Motor cables.
R U
Power supply S V IM
Inverter
T W
– 47 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
Exercise
Find the input power, motor current and inverter input current when a conveyor (constant torque
load output 7.5kW ) is operated with a commercial power supply at 30m/min and when the conveyor
is operated by an inverter at 30m/min and 15m/min.
Suppose that the power supply is 200V 60Hz, motor efficiency ( η M ) is 0.9 and motor power factor
(cos φ ) is 0.88.
(3) Inverter operation (15m/min) ..... POUT = 7.5 [kW] × 15 / 30 = 3.75 [kW]
– 48 –
2. INVERTER PRINCIPLES AND. ACCELERATION/DECELERATION
CHARACTERISTICS
DC bus voltage
Motor current
10ms/DIV 10ms/DIV
Fig. 2.47 Input/Output Current Waveform Fig. 2.48 Input/Output Current Waveform
Fig. 2.47 Measurement Example (50Hz) Fig. 2.47 Measurement Example
(50Hz, with power factor improving reactor)
10ms/DIV 10ms/DIV
Fig. 2.49 Input/Output Current Waveform Fig. 2.50 Input/Output Current Waveform
Fig. 2.47 Measurement Example (20Hz) Fig. 2.47 Measurement Example
(20Hz, with power factor improving reactor)
– 49 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
This chapter describes points to be considered, such as the capacity of a motor to be driven, the
number of motors, operation status, etc. for selection of an inverter, and corrective actions to be taken
when a fault occurs.
As details about specific capacity selection are given in Technical Notes, this chapter mainly provides
details on how to select the inverter capacity.
W hen regarded as a motor power supply, an inverter having higher capacity is better and allows a
motor to be direct-on line started (to be switched on/off by the inverter output) like a commercial power
supply. However, in consideration of economy, dimensions, etc., it is not be wise to increase the
capacity unnecessarily.
To select the optimum capacity at which trouble-free operation can be performed, first understand the
following:
– 50 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
(a) It is not totally correct to select an inverter according to motor capacity in "kW ". It
CAUTION
is better to select an inverter which will satisfy the condition in formula (3.1) based
on the rated current of a motor.
Reason: If the inverter and motor have the same capacity (kW ), an increase in the
number of motor poles reduces the efficiency and power factor of the motor,
increasing the rated current value.
For standard 2, 4, and 6 pole motors, selection of an inverter based on "kW " will
hardly pose any problems.
(b) A motor having a capacity larger than the inverter cannot be used.
– 51 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
2) Driving two or more motors with a single inverter at the same time.
I1
IM 1
Inverter
I2
IM 2
In
IM n
W hen two or more motors are to be run in parallel, inverter electronic overcurrent
CAUTION
protection cannot be used to protect the motors. Provide a thermal relay for each motor
on the inverter output side. W hen motors are to be run continuously at low speed,
thermal relays cannot adequately protect the motors. Instead, use a temperature
detector in each motor.
[Example] Supposing that four motors are started sequentially as shown below, the motor
current is maximum when the last motor (IM 4 ) is started (MC 4 is switched on) while the
other three motors are running. W hen a motor starts, motor current I 4 is 6 to 8 times
larger than the rated current.
MC 1 I1
IM 1
Inverter MC 2 I2
IM 2
MC 3 I3
IM 3
MC 4 I4
IM 4
(a) W hen one motor is switched on-off on the output side of the inverter or when a
CAUTION
motor output shaft is switched on-off by a clutch, select the inverter capacity as in
the above sequential start. Regard the motor currents during running as zero and
use only the starting current of the motor to be switched on-off to select the
inverter capacity.
(b) W hen two or more motors are to be run in parallel, the inverter electronic
overcurrent protection cannot protect the motors, a thermal relay should be
provided for each motor on the inverter output side. W hen the motors are to be run
continuously at low speed, thermal relays cannot adequately protect the motors.
Instead, use a temperature detector in each motor.
– 52 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
(c) If the current limit function is activated, the frequency varies suddenly. For
sequential starts, the speeds of motors already started may vary suddenly.
Hence, according to the machine specifications:
• W hen the current limit function of the inverter is utilized to minimize the inverter
capacity
Rated output current of inverter ≥
sum of rated currents of motors (IM1 to 4) × 1.1
• W hen it is not desired to affect the speed of the motors already started
<The point is to make a selection so that the current limit function is
not activated>
Rated output current of inverter ≥
sum of rated currents of motors already started × 1.1
+ starting current of motor started last *
* Starting current of motor: Select an inverter on the assumption that the starting
current is around 6 to 8 times larger than the rated motor current.
[Example] For three motors SF-JR 1.5KW 4P (rated current 6.0A, starting current 48.4A)
• W hen the current limit function of the inverter is utilized to minimize the inverter
capacity
Select the FR-A520-5.5K inverter with current limit function having the rating of
19.8A (= 6.0A × 3 units × 1.1).
• W hen it is not desired to affect the motors already started
Select the FR-A520-18.5K inverter with current limit function having the rating of
61.6A (= 6.0A × 2 units × 1.1 + 48.4A) or more.
– 53 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Can a motor be used with an inverter whose capacity is one rank higher?
W hen the inverter capacity is increased, the motor torque (power) increases.
The motor-generated torque is lower in inverter operation than in commercial power supply
operation. Therefore, depending on the load magnitude, the current may increase due to
insufficient torque (power), activating the protective function.
Generally, insufficient torque may be solved by increasing the motor capacity (the inverter
capacity must also be increased) or by increasing the inverter capacity only with the motor
capacity unchanged.
Since the price will be higher and the motor size will be larger using the former method than
in the latter method, the latter method is often used.
As the increased inverter capacity will increase the output current of the inverter, motor-
generated torque can be increased.
– 54 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
The basic operation pattern of a motor is made up of a start, acceleration, constant speed,
deceleration and a stop. Points of selection in each process will be described below.
Time
ta (s) td (s)
Acceleration Deceleration
time time
Load torque (T L )
Time
Ta =
375 × ta
2
GD ⋅ N
Td =
GD ⋅ N
2
Ta = 375 × td
38.2 × ta
2
GD ⋅ N
Td =
38.2 × td
Ta
Required motor torque
<Ta + T L >
TL
Time
Required brake
The key is the magnitude of motor
torque
output torque. Torque changes
<Td – T L >
according to motor capacity,
inverter capacity, control system The key is the regenerative capability
and boost amount. of inverter. Regenerative capability
changes according to selection of
inverter capacity, brake unit model
and power return converter.
– 55 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
3.2.1 Start
A motor starts at a point where motor-generated torque exceeds load torque (point A in Fig. 3.2).
Since the motor is locked while the inverter output frequency is between 0 and point A, the point of
intersection must be less than the maximum starting frequency at which the inverter does not trip due
to locked rotor current. (Refer to Section 2.6.1.)
0 Output frequency
fa’
Motor starts at this frequency.
3.2.2 Acceleration
The output torque of the motor must be not less than torque required for acceleration (T a + T L ).
Acceleration is classified into non-linear acceleration in which speed increases with the stall
prevention (current limit) function activated, and linear acceleration in which speed increases
smoothly without the stall prevention function activated. Non-linear acceleration is generally used for
examination. For fixed-position stop of a lift etc., use linear acceleration to make an examination.
– 56 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
3.2.3 Deceleration
Regenerative braking torque is determined by motor loss and inverter loss. Therefore, the capability
of an inverter with a built-in brake is determined by inverter loss, and that of an inverter without built-in
brake is determined by motor loss. To increase regenerative braking torque, an increase in the
inverter capacity with a built-in brake is effective but not for an inverter without a built-in brake.
Therefore, use the BU brake unit.
If the inverter has satisfied the brake torque requirement, whether the brake resistor is thermally
acceptable during deceleration must be examined. Energy returned to the inverter (W INV ) during
deceleration must be fully consumed within the capability of the brake resistor.
W hen larger brake capability is needed, use a power return option (FR-RC) or an inverter having
built-in power return function (FR-A201 series) which returns regenerative energy (W RC ) to the power
supply to generate braking force.
Inverter without power return converter Inverter with built-in power return function
During
During acceleration
acceleration
NFB Motor
NFB
Motor Power
Power Inverter IM Load
Inverter IM Load supply
supply
WM Overall Power
energy return
Brake c onv ert er
W INV WM Overall
during
resistor energy
regeneration
during
W MECH
regeneration
W MECH
Inverter having built-in
power return function
– 57 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
W hether the BU brake unit is required or not can be judged as described below:
The brake unit is needed if the DC voltage measured across terminals P(+)-N(–) with a meter
immediately after deceleration starts rises to nearly the stall prevention operation voltage
described in Section 2.5.3. Also, if a voltage above the brake operation voltage continues in an
inverter used with the brake unit, the brake capability may be insufficient, the brake unit capacity
should be increased.
– 58 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
For lift operation - single-cycle time, lifting height (m), and load torque during negative torque
(especially machine efficiency) are important selection factors because of the generally long
regenerative operation time.
– 59 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Speed
Speed
Forward Time
Time rotation
Reverse
rotation
Insulation Rank Max. Permissible Temperature [°C] Temperature Rise Limit of Coil [°C]
(Resistance method)
E 120 75
B 125 80
F 155 100
– 60 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Small-capacity standard motors (7.5kW 4P or less) can be used up to 120Hz. W hile the reduction
ratio of a machine conventionally determined with the maximum machine speed at 50Hz or 60Hz, the
following advantages are given for increasing the reduction ratio and inverter output frequency
2
(between 60Hz and 120Hz) to reduce load torque and load GD at the motor shaft:
(1) Motor can be started more easily as the reduction ratio is higher.
(2) Continuous duty is enabled even at low speed. (A standard motor may be selected instead of a
constant torque motor exclusively designed for inverter operation).
(3) Variable speed range can be increased.
Relationships between Reduction Ratio (i), Load Torque Converted into Equivalent Value at
2
Motor Shaft (T L ), and Load (GD L )
TL = TLL ⋅ i TLL : Load torque at load shaft
GD 2 L = GD 2 LL ⋅ i 2 GD 2 LL : Load GD 2 at load shaft
Exercise
Select a geared motor for continuous use of a conveyor requiring 1.2kW power (torque constant)
in a 1:5 variable speed range. Calculation examples in International System of Units (SI) are
half-tone screened.
(1) W hen maximum running frequency is 60Hz and gear ratio is 1/30 Motor
Gear ratio 1/30
9550 9550
6.367 [N·m]
974 × P 974 × 1.2
• Load torque (TL ) = = =0.649[kgf ⋅ m]
N 1800
6.367 191.01 [N·m] Conveyor
• Load torque at reduction gear output shaft (TLL ) = 0.649 × 30 = 19.47[kgf ⋅ m]
(5.17 N·m)
• As continuous motor output torque at low speed of 12Hz is 65% (0.53kgf·m) of the
rating, capacity is insufficient for a 1.5kW motor.
9550
7.587 [N·m] 6.367 [N·m]
974 × 2.2
• 60% torque of 2.2kW motor = × 0.65 = 0.774 [kgf ⋅ m] >TL = 0.649 [kgf ⋅ m]
1800
Hence, if a 2.2kW geared motor of 1/30 gear ratio is selected, the conveyor can be used
continuously at 12 to 60Hz.
(2) W hen the reduction ratio of the geared motor is 1/37.5 and the maximum running frequency
is increased to 75Hz.
• Low-speed frequency is 75Hz/5=15Hz (continuous output torque can be up to 70%
of the rating) 191.01
5.094 [N·m]
19.47
• Load torque at motor shaft (TL ) =TLL ⋅ i = =0.519[kgf ⋅ m]
37.5
9550
5.57 [N·m] 5.094 [N·m]
974 × 15
.
• 70% torque of 1.5kW motor = × 0.7 = 0.57 [kgf ⋅ m] > TL = 0.519 [kgf ⋅ m]
1800
Hence, if a 1.5kW geared motor of 1/37.5 gear ratio is selected, the conveyor can be used
between 15 to 75Hz.
– 61 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
f2 N2
Machine side Time
conditions [s]
Load torque
converted into T LS
equivalent value T L max
at motor shaft T L min
Time
Ta
Acceleration torque
Time
Deceleration torque
–Td
Ta+T L max
Examination
items Time
– (Td–T L max)
I1
I2
I4
Motor current Time
I3
C2
Cooling coefficient (c) C3
C1
C4
C5
Time
t1 (=ta) t2 t3 t4 t5
tc (1 cycle)
– 62 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
– 63 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
YES
5) • Examine whether or not the Continuous motor operation torque (T MC )
5) magnitude of the load causes the > load torque (T L )
Can continuous permissible temperature of the
NO operation be motor to be exceeded.
performed?
– 64 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
8) • Regenerative power from the load • Technical Note No. 22 • The capability of regenerative power
(W MECH ) Refer to Chapter 3 "BRAKING (permissible power) differs according to
• Motor-absorbed power (W M ) CAPABILITY DATA" [Braking the type and capacity of the inverter.
• Regenerative power to the inverter Capability Torque Type]. • For continuous regeneration, the power
(W INV ) = W MECH – W M [W] W RS : Short-time permissible power return converter may be needed.
W RC : Continuous permissible
power
– 65 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
– 66 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Examination of machine
side specifications
Selection Outline
W×V
Load power calculation Required power (PL ) = [kW]
6120 × η
Temporary selection of (1) Select the motor capacity which is not less than 1.5 times of the required power.
motor capacity (2) Increase the motor capacity to increase starting torque
(1) Select the inverter equivalent to the motor capacity.
Temporary selection of (2) Increase the inverter capacity to increase acceleration torque.
inverter capacity
– 67 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
NOTE:
Lift applications are different from other applications in that there are two modes of positive load
torque (generally rising) and negative load torque (generally lowering), also cyclic operation is always
performed with a stop at a fixed position. A transistorized inverter can be used in such applications in
the following cases:
Reduction
Electromagnetic
gear
brake
MC
Motor
NFB
Lift case
Counterweight
(W LS )
Inverter (W C )
Load (W L )
Vertical motion
Brake unit
• Lowering operation
The lift is often driven by the load, resulting in regenerative operation.
As the inverter itself cannot compensate for regenerative energy, a braking unit (such as a
power return converter or brake unit) is always required.
• Motor selection
If continuous operation at low speed is not performed, a constant torque motor need not be
adopted.
– 68 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Flow of energy in
regenerative mode
P
AC reactor
Power IM
supply
N
Regenerative energy is
returned to power supply in
this area.
W hen the motor is rotated by an external force (such as gravity) during lift lowering operation etc.,
energy generated by the motor functioning as a generator is accumulated in the smoothing capacitor
which raises the voltage across the DC-bus capacitor (across terminals P-N).
Such a state is called regenerative operation.
This regenerative energy is compensated for in the following system to generate braking force in the
motor:
Resistor consumption system : W ith regenerative energy converted to heat, this system is low in
initial cost and is suitable for small capacity use.
Power return system : W ith regenerative energy returned to the power supply, this system
provides a large braking force, produces an energy-saving effect,
and is adequate for large capacity applications.
• Note that if the braking unit capacity is low, the voltage across the capacitor (across terminals
P-N) rises, causing the inverter to trip due to OVT (regenerative overvoltage).
Set Pr. 19 (base frequency voltage) of the inverter according to the power supply voltage to
minimize the occurrence of an OCT (overcurrent) alarm in the regenerative mode.
– 69 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
• Stable operation
High torque at start/low speed is slightly different from smooth operation at low speed.
A speed control range indicates the lowest speed at which operation can be performed
smoothly. Vector control (speed control range 1:1500) is the most suitable for use in
applications where smooth operation is desired at ultra low speeds.
<Example>
A speed control range of 1:120 (advanced magnetic flux vector control) indicates that when the
maximum speed is 60Hz, the lowest usable low speed range in which smooth operation can be
performed is to 1/120 of 60Hz or 0.5Hz. (Note: speed control range is 1:100 for 50Hz inverters.)
– 70 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Inverter Model
Item
FR-E500 FR-A024S/A044 FR-A500 FR-A100 FR-A201 FR-V200
Ultracompact,
Compact, High For fans/pumps, High
low price, High accuracy,
Features medium performance, low acoustic performance,
medium high functions
functions high functions noise high functions
functions
3-phase, 200V Single phase,
Power supply 3-phase, 200V 3-phase, 200V 3-phase, 200V 3-phase, 200V
Single-phase, 200V
specifications 3-phase, 400V 3-phase, 400V 3-phase, 400V 3-phase, 400V
100/200V 3-phase, 400V
0.1kW to 3.7kW
Capacity 0.1kW to 7.5kW (400V: 0.4kW to 0.4kW to 55kW 0.75kW to 55kW 5.5kW to 55kW 1.5kW to 45kW
3.7kW)
V/F control or V/F control or V/F control or
V/F control or
general-purpose general-purpose advanced
magnetic flux
Control system magnetic flux magnetic flux magnetic flux V/F control Vector control
vector control
vector control vector control vector control
selectable
selectable selectable selectable
Low acoustic
noise
{ { { { { {
Reset/Output
stop
{ { { { { Output stop
selective
Multiple speeds 15 speeds 15 speeds 15 speeds 7 speeds 7 speeds 7 speeds
Brake Built-in — — 7.5K or less — — 5.5K or less
resistor Option 0.4K or more 0.4K or more { — — 5.5K or less
Brake unit
connection
{ { { { — {
0 to 5, 10VDC 0 to 5, 10VDC 0 to 5, 10VDC
0 to 5, 10VDC 0 to 5, 10VDC 0 to 5, 10VDC
Speed command ±5VDC, ±10VDC ±5VDC, ±10VDC ±5VDC, ±10VDC
4 to 20mA 4 to 20mA ±10VDC
4 to 20mA 4 to 20mA 4 to 20mA
1 changeover 1 changeover 1 changeover 1 changeover 1 changeover 1 changeover
Alarm output
contact contact contact contact contact contact
Output signal 2 type 2 types 5 types 5 types 5 types 3 types
Automatic restart
after
instantaneous
{ { { { { {
power failure
1Hz 150% 1Hz 150% 1r/min 100%
Low speed torque 0.5Hz 150% 6Hz 80% 1Hz 150%
3Hz 200% 3Hz 200% continuous
Stall prevention { { { { { —
Fast-response
current limit
{ { { { { —
0.75kW floor
31 55 100 115 — —
space ratio %
0.75kW standard
61 76 100 97 — —
price ratio %
(400V class) (400V class)
EMC (Dedicated noise (Dedicated noise (Dedicated noise (No confor-
(Dedicated noise (Dedicated noise
EC Directive filter available) filter available) filter available) mance)
filter available) filter available)
Direc-
Low
tives
Voltage { { { (400V class
only)
(No confor-
mance)
(400V class
only)
Directive
UL Standard { { { { { {
cUL Standard { { { { { {
For use when For use when For use when For use when low For use when For use when
some degree of compact size high starting acoustic noise is regenerative large torque,
functions are and regenerative torque and required in torque is called high accuracy
called for, e.g. brake are tripless feature fan/pump for in vertical and fast
multi-speed required. are needed or applications. motion response are
Selection point operation and when operating applications. required.
brake motor conditions are
operation. unclear.
Adequate for use
in most
applications.
General Conveyors, Conveyors, Air conditioners. Lifts, Lifts,
industrial General Machine tools, Winding Winding
machines, industrial General machines, machines,
Infinitely machines. industrial Machine tools, Conveyors.
Main applications
variable speed machines, General
Pulleys, Lifts. industrial
Starters, machines.
Conveyor drive.
– 71 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Inverter
NFB MC
FR-A500 Motor
R U
Power IM
S V
supply
T R
SD
RH
Running frequency
selected by contact RM
change-over
RL
10
Frequency setting 2
potentiometer
5
External input signal FR-PU04 PARAMETER UNIT
(0 to 5, 0 to 10VDC,
4 60.00Hz
4 to 20mADC) STF FWD PU
Option
MON SET EXT PU
12-bit digital input FR-A5AX HELP SHIFT ESC
(BCD, binary) 9
7 8
Digital output 4 5 6 FWD
– 72 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Switch on the input Set the values of Switch on the start Vary the speed with Switch off the start Shut off the input
side magnetic the required func- signal to start/ the frequency signal to decelerate side magnetic
contactor MC. tions using the accelerate. setting signal. to a stop. contactor MC.
parameter unit. Switch STF (STR) Switch STF (STR)
(For the first op- ON. OFF.
eration)
Minimum
Function Parameter Name Screen Setting Range Setting Factory Setting
Number Display Increment
6%/4%/3%/2%
Basic 0 Torque boost Trq.Bst1 0 to 30% 0.1%
(Note 1)
functions 1 Maximum frequency Max.F1 0 to 120Hz 0.01Hz 120Hz
2 Minimum frequency Min.F1 0 to 120Hz Same as above 0Hz
VFbaseF
3 Base frequency 0 to 400Hz Same as above 60Hz
1
Multi-speed setting
4 PresetF1 0 to 400Hz Same as above 60Hz
(high speed)
Multi-speed setting
5 PresetF2 0 to 400Hz Same as above 30Hz
(middle speed)
Multi-speed setting
6 PresetF3 0 to 400Hz Same as above 10Hz
(low speed)
0 to 3600 seconds/ 0.1 seconds/ 5 seconds/15
7 Acceleration time Acc.T1
0 to 360 seconds 0.01 seconds seconds (Note 2)
5 seconds/
0 to 3600 seconds/ 0.1 seconds/
8 Deceleration time Dec.T1 15 seconds
0 to 360 seconds 0.01 seconds
(Note 2)
Electronic thermal O/L Rated output
9 Set THM 0 to 500A 0.01A
relay current
DC injection brake
10 DC Br.F 0 to 120Hz, 9999 0.01Hz 3Hz
operation frequency
DC injection brake 0 to 10 seconds,
11 DC Br.T 0.1 seconds 0.5 seconds
operation time 8888
DC injection brake
12 DC Br.V 0 to 30% 0.1% 4%/2% (Note 2)
voltage
13 Starting frequency Start F 0.01 to 60Hz 0.01Hz 0.5Hz
14 Applied load selection Load VF 0 to 5 1 0
Note 1: These set values differ according to the inverter capacity: (0.4K, 0.75K)/(1.5K to 3.7K)/
(5.5K, 7.5K)/(11K or more).
Note 2: These set values differ according to the inverter capacity: 7.5K or less/11K or more.
– 73 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Pr. 0 Torque boost (manual) setting Pr. 4 Pr. 5 Pr. 6 3-speed setting
• Motor torque in the low-frequency range can be adjusted Pr. 4 3-speed setting (high speed)
according to the load.
Pr. 5 3-speed setting (middle speed)
100%
Pr. 6 3-speed setting (low speed)
• Any speed can be selected by switching the external
Output contact signal (across terminals RH/RM/RL-SD).
voltage • Each speed (frequency) may be specified as appropriate
(V)
between 0 and 400Hz during inverter operation. The [▲]
and [▼] keys may also be used for setting.
Pr. 0 Setting Speed 1
Output
range (high speed)
frequency
Base (Hz)
frequency Speed 2
Output (middle speed)
frequency
Speed 3
Pr. 1 Pr. 2 Upper and lower frequency limit (Hz)
(low speed)
settings
Pr. 1 Maximum frequency Time
Pr. 2 Minimum frequency
ON
• The upper and lower limits of the output frequency can be RH-SD
clamped. ON
RM-SD
ON
RL-SD
100%
• The base frequency (reference frequency at rated motor • In Pr. 7 "acceleration time", set the period of time required
torque) can be set as appropriate between 0 and 400Hz to reach the value set in Pr. 20 (reference frequency) from
according to the motor rating. 0Hz. In Pr. 8 "deceleration time", set the period of time
required to reach 0Hz from the value set in Pr. 20.
• Use Pr. 21 "acceleration/deceleration time increments" to
Base frequency setting range
change the setting range and minimum increments.
100% Set value 0: 0 to 3600 seconds (minimum setting
increments: 0.1 seconds)
Output Set value 1: 0 to 360 seconds (minimum setting
voltage increments: 0.01 seconds)
(V)
Pr. 20
Frequency
Pr. 3 Base frequency 400Hz (Hz)
Running
frequency
(Hz)
Time
– 74 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
60
100% 100%
– 75 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Motor speed/ N N N
Coast to stop
inverter output
Coast to stop
Speed
Speed
Speed
Inverter trip
f f f
Output Frequency
Output Frequency
Output frequency
Remarks Switch on the signal across Frequent ON-OFF of MC1 will When MC2 is on, overcurrent
terminals STF-SD to start, switch cause inverter damage. protection is activated to trip the
off the signal across terminals inverter.
STF-SD to decelerate the motor to
stop.
– 76 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
3.5.5 Starting and stopping using the input side magnetic contactor MC
(1) The inverter is designed on the assumption that the input side magnetic contactor (MC1) is not
used to start/stop the inverter.
(2) W hen AC power is switched on by the magnetic contactor (MC1), a large inrush current flows in
the large-capacity smoothing capacitor of the inverter. To suppress this current, a current limiting
resistor of short-time duty rating is installed as shown in Fig. 3.11. A relay, magnetic contactor
(MC3) or thyristor is used to short the resistor on completion of charging.
(3) If the input side MC is switched on-off frequently, an inrush current occurs repeatedly and heats
the current limiting resistor, resulting in wire breakage. If the resistor shorting relay or the
magnetic contactor (MC1) switches on in this state, a large inrush current for charging the
smoothing capacitor passes through the converter devices (diodes) and flows into the smoothing
capacitor. This unsuppressed inrush current will damage the converter devices.
MC3
Converter
R
MC1
Current
Power limiting C Smoothing
supply resistor capacitor
(4) Such operation must be avoided because it will not only damage the converter devices but also
shorten the lives of the smoothing capacitor, current limiting resistor, shorting relay and magnetic
contactor (MC3).
(5) W hen the magnetic contactor (MC1) is switched off to stop the motor, the regenerative braking
effect of the inverter does not operate. The motor coasts to a stop.
Similarly, at the time of an instantaneous power failure or a power failure accident, the motor
coasts to a stop.
– 77 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
To continue operation without stopping the motor after an instantaneous power failure etc.,
selection of automatic restart after instantaneous power failure is effective. (This function is
available as standard for the FR-A500 series.)
BR
BK Electromagnetic
brake
NFB MC INVERTER
Power R U
supply S V IM Motor
T W
Tr
F
C F
Stop Start STF
F B
SD
F
F
Reset
BR
CR
RES
SD
MRS
BR
CR
– 78 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
(1) Brake power must be supplied from the input side of the inverter.
(2) W hen bringing a motor with electromagnetic brake to a stop, switch on the signal across inverter
output stop terminal MRS-SD to switch off the inverter output. Otherwise, a locking current may
flow when the brake operates, resulting in overcurrent (OC3).
(3) The brake lining may chatter during continuous operation in the speed range of 30Hz or less,
depending on the brake type. Such motors can be used without fault for short durations such as
positioning at low speed.
(4) W hen the inverter is used with a 400V power supply, the operation circuit voltage is dropped to
400V/100V or 400V/200V by the transformer (Tr).
Acceleration/deceleration
Proportional relationship
time (ta) set from parameter
unit
60
Output
frequency
[Hz] 60Hz
30
Output
frequency
[Hz]
0 2.5 5V
0 Time
Frequency setting signal to *
5V
– 79 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
RL-SD ON RL-SD ON
Time Time
to
RM-SD ON RM-SD ON
Time Time
Inverter
NFB Motor
FR-PU04 PARAMETER UNIT
R R
60.00Hz
IM
STF FWD PU
S S
MON SET EXT PU
STOP
calibrated.
0
<When meter is used
WRITE
READ RESET
10
2
x "Maximum, minimum frequency" set in
[Pr. 1] [Pr. 2] are incorrect.
5 x "Frequency at 5V input" set in [Pr. 73] is
incorrect.
x For "frequency at 20mA input", terminals
The frequency setting
FR-A500 AU-SD are not connected.
signal level is wrong. x "Gain, bias" is not set correctly.
Measure voltage across [Pr. 902] to [Pr. 905].
terminals 2-5.
– 80 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
If the motor does not run at all after the start signal is input
(1) Check the areas related to the main circuit.
1) Check the incoming power supply.
2) Check that a power supply phase R, S or T is not open.
3) Check that the motor is securely connected to the inverter.
(4) Others
• Check that the alarm lamp is not lit.
– 81 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
NFB NFB
Power Power
supply supply Forward Inverter
Inverter rotation start
Stop
Forward rotation start STF STF
Output
Output
frequency
frequency
Time Time
Start Time
Across STF(STR)-SD ON
Time
Stop Time
Fig. 3.15 Two-Wire System Connection Fig. 3.16 Three-Wire System Connection
Example Example
– 82 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
NFB T (Note) 3
MC
R U Motor
Inverter
Power No. 1
S V IM
supply
T W
B
Alarm signal (closed for
normal, opened for alarm)
C
(+5V) Start signal
10 STF
Frequency 2
SD
setting
5
potentiometer
2W1kΩ
Grounding
R U Motor
Inverter
S No. 2 V IM
T W
STF
SD
10 B
Alarm signal
2
C
5
– 83 –
3. CAPACITY SELECTION AND OPERATION METHODS FOR MOTOR
AND INVERTER
Inverter
NFB MC
R U
T W
T (Note 4)
Grounding When FR-BU brake
F unit is used
C
Ready Brake Resistor
“ON” unit unit
“OFF”
PB 1
PB 2 FR-BU FR-BR
MC B
MC HB HC T H1 T H2
PR PR P
P P
HA
Forward TH1
Stop rotation N N HB TH2
MC PB 5 PB 3 R HC
F
F Brake unit Resistor unit
FR-BU FR-BR
Reverse
rotation
PB 4 F When regenerative brake duty is large
R (7.5K or less)
R
P External regenerative brake
discharge resistor
F (Note 5)
BR PX R
R
PR
Hz FM
Moving-oil type
frequency meter 1mA Reset PB 6
SD RES
F
STF SD
R (Note 1) BR
STR MRS
10
Frequency setting
potentiometer 2
2W 1kΩ
5
Note: 1. To bring the motor with electromagnetic brake to a stop, use the output stop terminal MRS-SD of the inverter.
Otherwise, when braking is applied to the motor, a locking current may flow in the motor, resulting in OCT.
2. Similar care should also be taken when using a mechanical brake.
3. When a motor with a brake is run continuously at 30Hz or less, the brake disc may chatter. However, the motor may
be used without fault for low speed operation of short duration, e.g. positioning. Also, because of the limitation on
braking capacity, use the motor at 60Hz or less speed.
4. For a 400V power supply, use a control transformer.
5. When an external brake resistor or brake unit is used, disconnect the jumper from across PR-PX.
– 84 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
This chapter describes the influence of inverter-generated harmonics on the power supply and the
power system to which the inverter is connected. The degree of influence on peripheral devices can
be judged from the amount of harmonics generated to make specific examination of measures
against harmonics.
The influence of power fluctuation (such as instantaneous power failure, voltage drop etc.) on the
inverter will be described. It is essential to understand both the operation of the inverter and motor.
It is defined that a harmonic has a frequency that is an integral multiple of the fundamental frequency
(generally a power supply frequency). The composition of a single fundamental wave and several
harmonics is called a distorted wave. (Refer to Fig. 4.2.)
A distorted wave generally includes harmonics in a high-frequency region (kHz to MHz order), but
harmonics handled as those in a power distribution system are usually of up to 40th to 50th degrees
(up to 3kHz). Generally, harmonics are different in nature from the problem of a high frequency region
noise which assumes a random form. For example, such problems as electromagnetic interference
and noise generated by personal computers (see Chapter 5) are local problems closely associated
with equipment hardware and differ in both influence and corrective actions from harmonics
applicable to power circuit networks. This is an important point which must be understood.
∞
i = i0 + ∑ in ⋅ sin (2 π f n t + φ n) ............................................................................................... (4.1)
n =1
n = 1, 2, 3, ......
f = fundamental frequency
– 85 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
i1 Fundamental i1
wave i3
Time Time
Second degree
i2 Composition
harmonic
Time
Distorted wave
Third degree
Time
i3 harmonic
Time
Fig. 4.1 Fundamental Wave and Harmonics Fig. 4.2 Distorted Wave
Sources of harmonics include rectifiers, AC power regulators, etc. The converter circuit of a transis-
torized inverter consists of a rectifier circuit and generates many harmonics.
As shown in Table 4.2, there are various rectifier circuits according to the main circuit system. A
three-phase bridge system is most often used in transistorized inverters.
The harmonic degree n is theoretically n = PK ± 1 (P = number of pulses, K = 1, 2, 3, .....) and
harmonics of 5th, 7th, 11th, 13th degrees etc. take place in a transistorized inverter three-phase
bridge system. Its harmonic level (harmonic content) is 1/n, and the amount of harmonics generated
reduces as the harmonic degree increases. In a single-phase power input inverter, 4K ± first degree
(third, fifth, seventh, ninth) harmonics are generated.
– 86 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
Inverter.
Three-phase n = 6K ± 1 Kn × 1/n DC electric railway.
bridge K = 1, 2, ...... Transformer substation.
Electrochemistry.
Other general devices.
W hen harmonics come into question in a power distribution system, the power supply harmonics are
not general commercial power supply harmonics, but refers to the source of harmonics (converter
circuit for a transistorized inverter) and the commercial power supply (low or high voltage power
transformer) acts as part of a load for harmonics. Hence, a harmonic equivalent circuit of a power
distribution system (diagram example as shown in Fig. 4.3) is as shown in Fig 4.4. A harmonic current
In (In = I 2 + I 3 + I 4 + etc. supposing that n is a degree) generated by an inverter branches in proportion
to the reciprocal ratio (1/Z) of the impedance of the power transformer ( ZL = RL + jnXL ) and those
devices connected to that transformer in parallel (motor B and the capacitor in the example of Fig.
4.3), i.e. the impedance of motor B ( ZM = RM + jnXM ) and the impedance of the capacitor
( ZC = jnXr − jXC / n ).
– 87 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
Power transformer
XL
RL
Fig. 4.5 shows an example of a power distribution system diagram including a high-voltage circuit. In
this example, low-voltage side loads (such as motors) are omitted because load impedance ( Z M ) is
generally extremely large compared to the impedance of the power transformer ( Z L ) and most of the
harmonic currents generated by the inverters flow into the power transformer. A high-voltage side
harmonic current (In) is found by dividing the sum of harmonic currents from the low-voltage inverters
by the transformation ratio of the transformer.
Commercial Z C
power supply ILn = In ×
Z S + Z C
XS, RS
Z S
ILn I Cn ICn = In ×
Z S + Z C
m2
In = (In1 + In2) In
m1
XL Transformer Transformer ILn I Cn
Xr
RL Primary m1 [V]
Secondary m2 [V] nXL
Xc
Capacitor RL nXS nXr
In1 + In2
Z S Z C
RS
XC/n
In1 In2
Inverter
Inverter 1 Inverter 2
Power Capacitor
supply
Fig. 4.5 Power Distribution System Diagram Fig. 4.6 Harmonic Equivalent Circuit
– 88 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
(a) The installation of a power factor improving reactor produces the same effect as when the
power supply side impedance of the inverter has increased, decreasing harmonic
components. As compared to the impedance of a power transformer, that of a reactor is much
larger, eliminating a difference due to the capacity of the power transformer.
(b) W hen a power factor improving reactor is not installed, harmonic components are greatly
influenced by the capacity of the power transformer (including line impedance).
(c) W hen the inverter output frequency or motor load factor is low, the harmonic content to the
inverter input current increases. However, since the input current itself is small, the absolute
value of the harmonic current will not be larger than under full load. For a variable torque load
such as a fan or pump, calculate the harmonic current at the maximum operating frequency of
50Hz or 60Hz.
– 89 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
Power harmonics are generated not only by inverters but also by most electrical devices, posing
social problems. The power harmonic suppression guidelines were published by the Ministry of
International Trade and Industry in September, 1994, and the "harmonic suppression technology
guideline" was further issued by Japan Electric Association in October, 1995.
1) Scope
• <Japanese harmonic suppression guideline for household appliances and general-purpose
products> applies to 200V class 3.7kW or less inverters used with power factor improving
reactors (option).
• <Japanese harmonic suppression guideline for consumers receiving power of high volt-
age/specially high voltage> applies to 200V class 5.5kW or more and 400V class inverters.
4.4.1 Japanese harmonic suppression guideline for household appliances and general-purpose products
For each equipment of 300V 20A or less, the maximum amount of harmonics generated must be
suppressed within the following values.
The maximum harmonic current output of each equipment must be lower than the following values:
Harmonic Degree n 3rd 5th 7th 9th 11th 13th 15th to 39th
Maximum permissible
harmonic current [mA]* 2.30 1.14 0.77 0.40 0.33 0.21 0.15×(15/n)
*Converted into values at the voltage of 230V.
The guidelines apply to the transistorized inverters of 200V class 3.7kW and less models. These
inverters must be used with power-factor improving reactors.
4.4.2 Japanese harmonic suppression guideline for consumers receiving power of a high voltage
The maximum amount of harmonic currents generated must be lower than the following values per
1kW contract power:
Table 4.3 Maximum Outgoing Harmonic Current per 1kW Contract Power
(Unit: mA/kW)
Received Power Voltage 5th 7th 11th 13th 17th 19th 23rd Over 23rd
6.6kV 3.5 2.5 1.6 1.3 1.0 0.9 0.76 0.70
22. 1.8 1.3 0.82 0.69 0.53 0.47 0.39 0.36
33. 1.2 0.86 0.55 0.46 0.35 0.32 0.26 0.24
66. 0.59 0.42 0.27 0.23 0.17 0.16 0.13 0.12
77. 0.50 0.36 0.23 0.19 0.15 0.13 0.11 0.10
110. 0.35 0.25 0.16 0.13 0.10 0.09 0.07 0.07
154. 0.25 0.18 0.11 0.09 0.07 0.06 0.05 0.05
220. 0.17 0.12 0.08 0.06 0.05 0.04 0.03 0.03
275. 0.14 0.10 0.06 0.05 0.04 0.03 0.03 0.02
– 90 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
– 91 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
Hence, if the contact power is 982/3.5 = 281kW or less, harmonic suppression is necessary.
P
verter by transistors to control the cur- N
box
ACL1 ACL2
rent waveform to be closer to a sine
wave. W ithout any other techniques,
Inverter
this inverter can clear the guideline. High-power factor converter
As the amount of harmonics generated
by the inverter is decreased, this is the most desirable technique.
(B) AC reactor
Install an AC reactor in the power supply • ACL connection example
side of the inverter to increase line im-
pedance, suppressing harmonics.
(a) Features
• As the input power factor is im- Motor
proved to about 0.9, the AC reactor
may also be used as a power factor ACL
improving reactor when the inverter
is used.
• The most typical technique for harmonic suppression.
– 92 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
(C) DC reactor
Install a DC reactor in the DC circuit of • DCL connection example
the inverter to increase impedance, DCL
suppressing harmonics.
(a) Features P P1
• As the input power factor is im-
proved to about 0.95, the DC reactor Motor
may also be used as a power factor
improving reactor when the inverter
is used.
• Since the DC reactor is connected in
the DC circuit, the voltage drop is only that of the DC resistance (1% or less).
Therefore, the DC reactor scarcely has an influence on such things as motor torque
shortage and gives many advantages.
• The DC reactor is smaller in size and weight and produces a greater power factor
improving effect than the AC rector.
(b) Selection method
Select the type according to the capacity of the motor connected to the inverter.
F R-BEL-H 22 K
Basic type Capacity ... Motor capacity [kW]
Voltage class ... • 200V: None
• 400V: H
– 93 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
(c) Note
• As the DC reactor is connected in the DC circuit of the inverter, the DC reactor cannot
be used with a model which does not have terminals P and P1. Specifically, the DC
reactor can be used with the following inverter models:
• All models of FR-A500 and FR-E500
• All models of the FR-A100
• Since only the installation of a DC reactor will not allow the inverter to meet the rele-
vant guidelines, this technique must be used with other techniques.
(d) Specific calculation example
(1) W hen the FR-BEL-H30K is connected across P-P1 according to the motor capacity
under the conditions in Section 3), the rated capacity is 34.7 [kVA] according to Table
4.5.
• 6-pulse equivalent capacity = rated capacity × conversion factor (Ki)
= 34.7 × 1.8 = 62.5 [kVA]
As this value is higher than 50 [kVA] and the guideline applies, find the outgoing
harmonic current in the following procedure:
• Rated current converted from received power voltage = fundamental wave current
× (400V/received power voltage) = 49.8 × 400/6600 = 3.02 [A]
• Outgoing harmonic current = rated current converted from received power voltage
× operation ratio × harmonic content
See the following table. It is assumed that the operation ratio is 50%.
– 94 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
– 95 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
Z S RS + jnXS
Icn = In × = In ×
Z S + Z S RS + jnXS + jnXr − jXc / n
nXS
≈ In × ............................................................................................... (4.2)
n(XS + Xr) − Xc / n
Supposing that a capacitor fundamental wave current is Ic1 , the capacitors effective current (Ic) is:
∞
Ic = Ic 2 + ∑ Icn2 ............................................................................................................. (4.3)
n=2
– 96 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
2
n
Equivalent negative-phase current = ∑ 4 × (In − 1 + In + 1) .......................................... (4.6)
2
– 97 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
W hen an instantaneous power failure occurs, the control circuit of the inverter loses power. To
prevent control misoperation caused by the lost voltage, the instantaneous power failure protection is
activated (if selected) to stop the inverter output, and keep it stopped. The FR-A500 series is used as
an example to describe this protection which differs according to instantaneous power failure
duration.
Operation continues.
Time
Time
Kept on.
Time
Alarm output/display
Fig. 4.7 Instantaneous Power Failure of
Fig. 4.8 Instantaneous Power Failure of
Fig. 4.7 15ms or Less
Fig. 4.7 15 to 100ms
100ms or
[Caution]
Power If the start signal (STF, STR) is on, the inverter
supply longer
Time will restart when power is restored. If the motor
is coasting at this time, overvoltage or
Motor Inverter 15ms overcurrent protection may activate to trip the
speed output f inverter. To restart the inverter automatically
(N) frequency when power is restored, use the automatic
Output
(f) N shut-off restart after instantaneous power failure
Motor coasts function. (This function is available as
to a stop. standard for the FR-A500 series. As the
automatic restart function is not factory-set,
Time
set "0" in parameter Pr. 57.)
For more information on automatic restart
Alarm output/display is not provided. after instantaneous power failure, refer to
Fig. 4.9 Instantaneous Power Failure of Section 4.6.3.
Fig. 4.7 100ms or longer
– 98 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
4.6.2 Inverter peripheral circuits and inverter operation at occurrence of instantaneous power.
failure
(1) W hen there are no magnetic contactors in the primary and secondary circuits of the inverter
NFB
Inverter IM
RA
STF
SD
If instantaneous power failure time is short and the relay RA does not switch off (start signal STF
remains on), operation performed is as described in Section 4.6.1.
If instantaneous power failure protection is activated to stop the inverter output and coast the
motor, the inverter may trip at restart. Therefore, the automatic restart after instantaneous power
failure function must be used or the start signal switched off during inverter output stop.
(2) W hen there is a magnetic contactor (MC) in the inverter supply circuit.
NFB MC
Inverter IM
RA
STF
SD
If instantaneous power failure time is short and the magnetic contactor MC and relay RA do not
switch off, operation performed is as described in above (1).
If only the magnetic contactor MC switches off, the motor coasts to a stop. To restart after power
is restored, switch MC on again after the motor has coasted to a stop (coasting interlock timer is
needed).
(3) W hen there is only a magnetic contactor (MC) in the inverter output circuit.
NFB MC
Inverter IM
RA
STF
SD
If instantaneous power failure time is short and the magnetic contactor MC and relay RA do not
switch off, operation performed is as described in above (1).
If only the magnetic contactor MC switches off, the motor coasts to a stop but the inverter
continues its output depending on the instantaneous power failure time or only the inverter
restarts after an initial reset of the inverter due to power restoration. Hence, when the MC is
switched on again, the motor is direct-on line started at the inverter frequency being output, and
overcurrent may occur to trip the inverter.
– 99 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
(4) W hen there are magnetic contactors (MCs) in the inverter primary and secondary circuits.
SD
(a) If an instantaneous power failure occurs on the high voltage power supply, a (complete)
instantaneous power failure rarely occurs at the lower voltage inverter input terminals (R, S,
T) and in most cases only an instantaneous voltage drop takes place.
(b) The inverter has both instantaneous power failure protection and undervoltage protection.
Undervoltage protection is designed to function when the DC circuit voltage of the inverter is
lower than a given value for a given period of time. W hen an instantaneous voltage drop
occurs the inverter will operate differently according to its load output (kW ): the protective
function of an inverter with a large load output will be activated; while an inverter having a
small load will continue operation.
(c) Meanwhile, the magnetic contactors and relays once switched on may not switch off if an
instantaneous voltage drop occurs. They generally switch off at voltages 30 to 50% or less of
the coil rating.
– 100 –
4. INVERTER POWER SUPPLY
(HARMONICS AND INSTANTANEOUS POWER FAILURE)
(c) A signal from the current detector is sent to the CPU and the period of ripples is counted to
judge motor speed.
(d) The inverter outputs a frequency matching the motor speed. (Refer to (B) in Fig. 4.10.) By
increasing the output voltage gradually after that, the inverter operation is resumed with the
motor starting current suppressed.
AC220V
Power supply voltage
0 Time
60Hz 60Hz
0 Time
1800r/min 1800r/min
Motor coasting
Motor speed
Time
50A DC voltage
application (A)
Motor current
0 Time
Instantane-
ous power Acceleration
failure time Reset time time
440ms 600ms 520ms
Speed Voltage
detection reduction time
time 300ms
140ms
Fig. 4.10 Example of Automatic Restart after Instantaneous Power Failure
W hen the inverter has the function for automatic restart after instantaneous power failure
(e.g. FR-A500 series).
NFB
Inverter IM
RA
STF CS
SD SD
Fig. 4.11 Wiring for Automatic Restart after Instantaneous Power Failure
– 101 –
5. NOISE
W ith the widespread use of electronic equipment, problems attributable to noise are tending to
increase.
As the inverter will generate noise because of its operational principles, it will effect equipment, and
devices around it. The degree of influence is not certain because it is related to the inverter control
system, the affected equipment's noise immunity, wiring conditions, installation distance, grounding
method, etc. W hen the following equipment and devices are to be installed near the inverter, it is
recommended to take the following measures according to the circumstances:
[Equipment requiring noise reduction techniques]
Sensors (proximity switch, etc.), video cameras (ITV, image scanner, etc.), radio transmitters
(including AM radio), acoustic equipment (microphone, video cassette recorder, audio equipment,
etc.), CRT displays, medical equipment
[Equipment recommended for reduction techniques]
Measuring instruments, private telephones
As described in Chapter 2, the DC voltage is switched at high speed in the inverter circuit to control
the output voltage waveform. An expanded view of the output waveform is as shown in Fig. 2.10 in
Chapter 2 (page 25). The sharp rise and fall include many high-frequency components, these
components are sources of noise generation.
Noise described here and harmonics described in Chapter 4 are often confused because they both
affect other electronic equipment. However, harmonics are generally 40th to 50th degrees (2⋅4 to
3kHz) and noise are often several to 10kHz or more.
+300V
−300V
– 102 –
5. NOISE
Noise generated by the inverter is roughly classified into noise directly radiated by the inverter and
cables connected to the inverter main circuit (I/O), noise induced magnetically and statically into
signal lines of peripheral devices close to the main circuit cables, and noise transmitted through
power supply channels.
Fig. 5.2 indicates noise types and Fig. 5.3 shows noise routes.
5) Telephone
7) 7)
7) 2)
1)
Sensor
2) power supply
Inverter
Instru- Receiver 3)
ment
6)
8)
4)
Sensor
Motor IM 3)
The noise levels tend to drop as the frequency band rises, and will generally be low enough to be
ignored above 30MHz.
Therefore, they will not affect most televisions and FM radios using 30MHz or higher frequencies, but
will affect AM and other radios in the low frequency band (0.5 to 10MHz). Thus, it will be reasonable
to consider this noise frequency band and examine reduction techniques.
– 103 –
5. NOISE
2) 3)
3)
Power IM
Inverter
supply
2)
(Motor frame grounding)
Grounding
Affected
device
Signal source
– 104 –
5. NOISE
The levels of such noise may either be measured by measuring field strength in the air or as a noise
voltage at the power terminals. (Refer to Fig. 5.8 Measurement Example.) Noise transmitted in the air
can be measured by the former method and noise transmitted through electric channels by the latter
method. As there are no ways of accurately measuring magnetic and static induction noise, the
measurement data of the above two noise types are generally used to size the noise.
Noise Noise
field terminal
strength voltage Inverter: FR-A520-3.7K
Running frequency: 30Hz
dB dB
V Measurement distance: 15m
µV / m µ
100
80
60
40
20
0
0.1 0.2 0.4 0.6 0.8 1 2 4 6 8 10 20 30
Frequency (MHz)
AM radio band
Fig. 5.8 Noise Measurement Example
– 105 –
5. NOISE
R
Inverter
Power
S
supply
T
GND
FR-BIF
– 106 –
5. NOISE
Minimum
NFB distance
Minimum Inverter Within 3 winds
distance U (4 turns)
Power R Motor
supply V
S W IM
Minimum
NFB distance
Inverter
Power R
supply
S
FR-BIF
Connect the
cables directly to
the inverter input Grounding
terminals with the
shortest cable
distance possible.
– 107 –
5. NOISE
Inverter
Noise filter
1 4 R U Motor
SF type
Power 2 5 S V IM
supply
3 6 T W
Do not bundle
these cables. Make these cables
as short as possible.
– 108 –
5. NOISE
Metal casing
Metal conduit
Power
Inverter IM
supply
Grounding
Noise filter
Metal conduit
Power
Inverter IM
supply
Grounding
– 109 –
5. NOISE
Inverter
A
Reduce the carrier frequency (Pr. 72)
(for the FR-A series). ~ ~ ~ ~ ~ ~ ~
B
Increase the input filter constant
(Pr. 74) (for the FR-A series). ∆ ∆ ∆ { ∆ — —
C
Install FR-BIF(-H) radio noise filter.
— ~ — — — ~ —
D
Install the FR-BSF01 or FR-BLF line
noise filter. — ~ — — — ~ ∆
Input
side
E
Run the power supply cables in a metal
conduit or use shielded cables. — ~ — — — ~ —
F
Install an insulating transformer or
noise cutting transformer. — ∆ — — — ~ —
G
Separate the power supply system.
— — — — — ~ ~
H
Install FR-BSF01 or FR-BLF line noise
filter. — — ~ ∆ ∆ — ~
Output
side
I
Run the output cables in a metal
conduit or use shielded cables. — — ~ { { — —
J
Use a 4-core motor power cable and
use one wire as a ground wire. — — ∆ ∆ ∆ — ~
K
Use a twisted pair cable for sensor
signals. { { { ~ ~ — —
L
Connect the shield to the common wire
of the sensor signal. — — — ~ ~ — ~
M
Do not ground the sensor power unit
directly to the control box. — — — — — ∆ ~
N
Ground the sensor power unit to the
capacitor. — — — — — ∆ {
Use a shielded cable for signal input
O and connect the shield to the
common (input terminal) SD.
∆ ∆ ∆ { ~ — ∆
Use a twisted pair shielded cable for
Affected
P speed input and connect the shield to
terminal 5.
{ { { ~ ~ — ∆
device Q
Insert a ferrite core into the feed input
cable (output side of affected device). ∆ ∆ ∆ { — — —
R
Decrease the impedance of the
affected device output circuit. ∆ ∆ ∆ { — — —
S
Separate the device from inverter and
power lines more than 30cm ~ ~ ~ ~ ~ — —
T
Do not run cables in parallel, do not
bundle them. ∆ ∆ ∆ ~ ~ — —
U Provide a shield plate. { ∆ ∆ ∆ ∆ — —
V Place the device away from the earth. ∆ { { ∆ ∆ — —
W
Insert a ferrite core into the input
side of the affected device. — — — — — { ∆
– 110 –
5. NOISE
Noise filter
– 111 –
5. NOISE
300
φ5
42
58 29 7
44
The FR-BIF (200V class) and FR-BIF-H (400V class) have the same dimensions.
<FR-BLF> <FR-BSF01>
2− φ 5 hole
31.5
22.5
130
2− φ 7
85 (65)
(33)
80 35 (65)
4.5
2.3 95
160
110
180
(c) SF type
Noise Filter Applicable Inverter
W H D W1 H1 C 2-φC hole
Model Model
SF1258 FR-A520-0.4K/0.75K 112 360 40 85 340 6
SF1259 FR-A520-1.5K to 3.7K 142 410 65 105 386 6
SF1260 FR-A520-5.5K to 11K 222 468 80 190 449 7
200V
– 112 –
5. NOISE
b
Noise 80
terminal
voltage c
(dB)
60
40
20
Noise 80
terminal
voltage b
(dB)
60 c
40
20
– 113 –
5. NOISE
80
EN50081-2
70 OP level
Noise
terminal
voltage 60
(dBuV)
50
40
30
Average
20
0.15 1 10 30
Freq (MHz)
Leakage currents flow through capacitances existing in the inverter input/output wiring and the motor.
These values depend on the capacitances, carrier frequency, etc. W hen a low acoustic noise inverter
is used, leakage currents will increase and the following technique should be used.
C
(1) Technique Earth leakage breaker
• Decrease the carrier frequency (Pr.72) of
the inverter. Note that motor noise will
Fig. 5.17 Leakage Current Routes
increase.
• Use harmonic/surge reduction products * For the selection of earth leakage breakers,
(such as Mitsubishi's New Super NV refer to page 136.
series) with the inverter system and other
systems to keep motor noise low (carrier frequency increased).
– 114 –
5. NOISE
Note that long wiring lengths will result in large leakage Long wiring lengths will result in large leakage currents.
currents. Decrease the inverter carrier frequency to Leakage currents of 400V class are larger than those of
reduce leakage currents. 200V class.
1000
400
Conditions Carrier frequency
Leakage Leakage 700
• Motor : SF-J3.7kW 4P 14.5kHz (FR-A540) current 500
current • Output frequency : 30Hz
(mA)
(mA) 300
10kHz (FR-A540) 300
FR-A540
FR-A520
200
200
Fig. 5.18 Differences between Earth Fig. 5.19 Difference between Earth
Fig. 5.18 Leakage Currents according to Fig. 5.18 Leakage Currents according to
Fig. 5.18 Carrier Frequency and Wiring Length Fig. 5.18 Motor Capacity
• Use the electronic overcurrent protection • Carrier frequency: 14.5kHz standard cable
of the inverter. ★ Leakage currents of 400V series will be about twice larger
than those of 200V series.
• Install the reactor (FR-BOL) on the output
side.
• Decrease the carrier frequency. Note that motor noise will increase.
To securely protect the motor from line leakage currents, it is recommended to detect the
temperature of the motor body directly with a temperature sensor.
– 115 –
5. NOISE
An electric device generally has a ground terminal, which must be connected to the earth.
An electrical circuit is usually isolated by an insulating material and contained in a case. However, in
reality it is impossible to manufacture an insulating material which can isolate currents completely, so
slight currents will leak to the case. The ground terminal is primarily designed to ground the case to
prevent someone from getting an electric shock when they touch the case of the electric device.
For devices which handle low-level signals, such as audio equipment, sensors and computers, and
machines operating at extremely high speed, grounding is also important to protect them against
external noise.
As described above, there are two types of grounding (safety and noise reduction) different in nature.
If these two grounding techniques are used without differentiation, problems will occur. Therefore,
grounding must be considered by dividing it into dirty grounding for electric shock prevention and
clean grounding for noise prevention.
W hen the inverter is used, its output voltage does not have a sine wave but a sharp wave as shown
in Fig. 2.10 in Chapter 2 (page 26). Hence, charging/discharging currents to/from capacitances
existing in the isolation section will also flow as leakage currents.
Further, similar charging/discharging currents will flow in the inverter supplied motor. As shown in
Fig. 5.9, larger currents with high frequency components flow during inverter operation than in
commercial power operation. This tendency increases as the carrier frequency of the inverter
increases.
– 116 –
5. NOISE
In high buildings, it will be advisable to ground steel frames for noise fault prevention and use the
independent grounding technique for electric shock prevention.
Class 3
Class 3
grounding
grounding
(a) Independent grounding (b) Joint grounding (Good) (c) Joint grounding
(Best) (Not allowed)
(b) Use the class 3 grounding technique (grounding resistance 100Ω or less) for the 200V class
inverters and special class 3 grounding technique (grounding resistance 10Ω or less) for the 400V
class.
(c) Use the largest possible gauge for the ground cable. Use the size indicated in Table 5.4 or larger.
(d) The grounding points should be as near as possible to the inverter to minimize the grounding
cable length.
(e) Run the ground cable as far as possible from the I/O wiring of equipment sensitive to noise and
over the shortest possible parallel distance.
(f) The ground terminal of the motor should be connected to one wire in the four-core cable and
grounded on the inverter side.
If the ground cable of the inverter, ground cable of the inverter-driven motor, or the ground cable of
audio equipment, sensor, computer etc. are connected together, leakage currents will be a source of
noise, affecting the equipment.
To solve this problem, dirty grounding work for the inverter must be done separately from clean
grounding for audio equipment, sensor, computer, etc.
Current 0
Time
0.4ms
– 117 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
This chapter deals with inverter reliability and life-span according to the installation environment and
operating conditions.
Also inverter circuit design, wiring instructions and operation procedures will be described.
Example factors
5cm
– 118 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
Useful
Useful Inverter
Inverter Check
Check Points
Point "Arrhenius law"
Inverter Life
Life
A 10°C rise in ambient temperature will halve
the inverter life (a 10°C fall will double life).
This is called "Arrhenius law". The
smoothing electrolytic capacitor used in the
inverter is one device to which "Arrhenius
law" applies. Similarly, the lives of the other
devices are also temperature dependent.
Temperature
Relationship between failure rate and
temperature. Premature
failure Random Wearout
The inverter consists of many electronic period failure period failure period
Failure
components including semiconductor
rate
devices. Such devices have a close
relationship between ambient temperature
Ambient
and failure rate. To reduce the failure rate temperatures
use the inverter at the lowest possible 50°C
permissible temperature. 45°C
40°C
Time (Year)
– 119 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
Table 6.1 Heat Generated by Inverter and Power Factor Improving Reactors
Heat Generated by Inverter (W) Heat Generated by Power
Motor Inverter Type When outside heat sink mount- Factor Improving Reactors
Capacity ing attachment is used (W)
(kW) 200V series 400V series Heat generated Heat dissipated FR-BEL FR-BAL
in enclosure from enclosure
0.4 FR-A520-0.4K FR-A540-0.4K 55 2 6
0.75 FR-A520-0.75K FR-A540-0.75K 70 3 8
1.5 FR-A520-1.5K FR-A540-1.5K 120 36 84 6 16
2.2 FR-A520-2.2K FR-A540-2.2K 150 45 105 8 15
3.7 FR-A520-3.7K FR-A540-3.7K 240 72 168 14 21
5.5 FR-A520-5.5K FR-A540-5.5K 330 99 231 19 30
7.5 FR-A520-7.5K FR-A540-7.5K 440 132 308 25 30
11 FR-A520-11K FR-A540-11K 670 201 469 31 45
15 FR-A520-15K FR-A540-15K 860 258 602 36 55
18.5 FR-A520-18.5K FR-A540-18.5K 1100 330 770 40 60
22 FR-A520-22K FR-A540-22K 1300 390 910 52 65
30 FR-A520-30K FR-A540-30K 1750 525 1225 60 90
37 FR-A520-37K FR-A540-37K 2100 630 1470 67 110
45 FR-A520-45K FR-A540-45K 2400 720 1680 95 140
55 FR-A520-55K FR-A540-55K 2700 810 1890 100 170
Note: Heat generated by the built-in brake resistor (for the FR-A520 series, 7.5K or less) is not included.
Enclosure
6.1.4 Heat interference and ventilation in an Inside
enclosure Mounting bracket FR-A5CN
enclosure (option)
The position of the inverters and ventilation fans Inverter
must also be noted when installing inverters in an Heat sink
enclosure.
Depending upon the installation positions, two or
more inverters installed in an enclosure or a
ventilation fan incorrectly mounted in an enclosure Cooling fan
may raise the ambient temperature of the inverters,
by reducing the ventilation effect.
Cooling air
Inverter
Air
Inverter Inverter guide Inverter Inverter
Inverter
Fig. 6.3 Example of Installing Two Inverters Fig. 6.4 Position of Ventilation Fan
Fig. 6.2 in Enclosure
– 120 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
Provide a cover which Note: The surface temperature of the resistor may rise up to about
will dissipate heat and Use a 300°C. Also, note the material of the mounting surface and
prevent any hazards cooling fan the positions of resistors when two or more of them are used.
such as a burn. as required.
Discharge resistor
Separation
Discharge resistor 7cm or more.
– 121 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
• Temperature
(1) Measures for high temperature prevention.
(a) Adopt a cooling technique such as forced ventilation.
(b) Install in an air-conditioned electric chamber.
(c) Do not subject direct sunlight.
(d) Shield or avoid direct exposure to radiated heat or warm air.
(e) Provide smooth air flow around the enclosure.
(2) Measures for low temperature prevention.
(a) Install a space heater in the enclosure.
(b) Do not switch off the inverter. (Switch off the inverter start signal only.)
(3) Prevention methods for sudden temperature changes.
(a) Select an installation place where sudden temperature changes will not occur.
(b) Avoid positioning near the inlet/outlet of an air conditioner.
(c) Install the inverter away from a door if the door opening/closing causes sudden temperature
changes.
• Humidity
Operate the inverter at ambient humidity between 45% and 90%. If humidity is too high, reduced
insulation and metal corrosion problems will take place. If humidity is too low, insulation breakdown
may occur.
The insulation distance specified in JEM1103 "Insulators for Control Equipment" has the humidity
condition of 45 to 85%.
(1) Measures for high humidity prevention.
(a) Use an enclosure of dirt-protection structure type and put moisture absorbent in it.
(b) Blow dry air into the enclosure.
(c) Install a space heater in the enclosure.
(2) Measures for low humidity prevention.
Blow air of the correct humidity into the enclosure. In addition, when installing or inspecting the
unit in this state, important points to note are to discharge the inspectors body (static electricity)
first and not to touch the parts.
(3) Measures for condensation prevention.
Condensation may take place if the temperature in the enclosure changes suddenly due to
frequent starting and stopping or if the outside temperature changes suddenly. Condensation
will cause faults such as reduced insulation, corrosion, etc.
(a) Take measures against high humidity as described in point (1).
(b) Do not switch off the inverter. (Switch off the inverter start signal only.)
– 122 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
Air filter
Clean and inspect periodically
to prevent clogging.
– 123 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
• High altitudes
Use the inverter at an altitude of 1000m or less. At a higher altitude the air will be thinner and will
lead to a decrease in the cooling effect.
• Vibration, shock
2
The vibration immunity of the inverter is 10Hz to 55Hz vibration up to 5.9m/s {0.6G} acceleration at
1mm amplitude in conformance with JIS C0911. If vibration or shock is less than the specified value
but is applied for a long time, the mechanical section may become loose or contactors may
misoperate.
Especially when shock is applied repeatedly, the mounting legs may be broken.
Countermeasures
(a) Fit rubber vibration insulators to the enclosure.
(b) Strengthen the structure of the enclosure to prevent resonance.
(c) Install the enclosure away from source of vibration.
– 124 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
(2) W hen the operation rating desired is outside the examination conditions or it is desired to use a
model that has not yet passed the safety examination, the motor must pass the safety
examination.
(3) W hen the motor is to be used with any inverter options, refer to the corresponding manuals.
(4) W hen a safety-increased explosion-proof motor is to be used with an inverter, there are severe
restrictions on operating conditions (such as generated loss reduction, cooling effect
improvement) and this motor-inverter combination is not economical. It is recommended to use a
pressure-resistant explosion-proof motor that has passed the safety examination.
(5) The inverter is not designed to be explosion-proof. Therefore, install the inverter in an
explosion-proof place.
Note: The above information (Section 6.1.10) only relates to inverters and motors used in Japan.
– 125 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
Connect after fully con- The input signal The output signal
firming the power supply terminal group is terminal group is If the phase sequence
voltage. Phase sequence on this side. on this side. of the motor is
need not be matched. switched, the direction
of rotation will change.
Inverter
NFB
Motor
R U
Power
supply S V M
T W
Grounding
PU connector Jumper
Control circuit power is (RS-485) Power factor
R1 P1 improving DC
supplied from phases
R and S. S1 P reactor FR-BEL
Jumper R P indicates
Jumper High-duty brake
24VDC power supply and external positive and N
resistor FR-ABR
transistor common control input signals PC PX negative. (DC)
(voltage input is impossible) PR R
– 126 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
Do not apply a voltage Do not use this magnetic contactor (MC) to repeat frequent
higher than the permissible starts/stops.
voltage of the inverter. • Basic sequence example without MC
NFB
Power supply 200V R
power S
supply
T
NFB F
Start CR2
CR1 STF(STR)
Stop CR1
CR2 SD
MC
R S T
Inverter
(3) 10
If power is connected to terminals U, V, W, the
(2)
2 inverter will be damaged.
(1) 5
Provide electrical and mechanical interlocks to
U V W ensure that MC C and MC F are not switched on
simultaneously. (Power is applied to terminals
U, V, W.) Otherwise, power will flow incorrectly
(including arc shorting).
10 (3) 10
(3)
(2) Fig. 6.10 Main Circuit Wiring
2 2
(2)
(1) 5 (1) 5
Incorrect examples
– 127 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
Contact input (switch) Contact input (relay) Open collector Open collector
(External power system)
Fig. 6.11 Input Signal Connections
2) Analog input terminals (not isolated from the inverter internal circuit)
The cables to these terminals must
be fully separated from the 200V Induction noise R
(400V) power circuit cables, etc. so Power supply S
that they are not bundled. Shielded T
cables must also be used to protect
them from external noise.
10
Do not
bundle. 2
5
Shielded cables
External noise
– 128 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
2
Characteristic C
Characteristic B
3
10
Resistance Characteristic A
2
value
Inverter
5
24VDC
SE
Permissible
current is 0.1A.
– 129 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
¥
R U
Power FR A500
supply S V IM Motor
Inverter
T W
Start
STF(STR),etc
SD
Contact input signal
50m or less
For long wiring distance,
RES
it is recommended to
provide a junction relay Reset
SD
near the inverter.
50m or less
Shielded cables
10 Twisted or
shielded cables
Frequency setting
2 FM
potentiometer
Frequency meter
5 SD
AM
5
Analog input signal 30m or less
– 130 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
INVERTER
P P
R R R R
N N
PR
Discharge resistors
Brake unit
P
R R R R
N
PR
Discharge resistors
Brake unit
(2) The maximum wiring length between the inverter and BU brake unit and between the BU brake
unit and discharge resistors must be 5m. If less than 5m, but longer than 2m the cables must be
twisted.
INVERTER
P P R R R
Brake
unit
N N
PR
Within 2m Within 2m
2m to 5m 2m to 5m
– 131 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
CAUTION CAUTION Terminals P and N of the brake unit must not be connected oppositely and
must always be matched with the terminal symbols P and N of the inverter.
Otherwise, the inverter will be damaged.
To ensure safety, configure a circuit which will shut off the primary magnetic
contactor of the inverter when the alarm contact signal of the brake unit or resistor
unit is activated.
(2) The maximum wiring length between the inverter and FR-BU brake unit and between the FR-BU
brake unit and FR-BR resistor unit must be 10m. If less than 10m, but longer than 5m the cables
must be twisted.
Inverter Brake Resistor
unit unit
P P P P
N N PR PR
Within 5m Within 5m
– 132 –
6. INVERTER OPERATING PROBLEMS AND CORRECTIVE ACTIONS
PX R
PR
Within 5m (Cables of longer
than 2m should be twisted.)
– 133 –
7. PERIPHERAL DEVICES AND OPTIONS
– 134 –
7. PERIPHERAL DEVICES AND OPTIONS
To ensure effective use of the transistorized inverter, the following options are available for various
applications, and to provide other characteristic improvements.
Table 7.1 FR-A500 Series Inverter Options and Applicable Option Examples
Applicable Option
Use Required Specifications
Examples
• It is desired to set the running frequency with a digital switch. FR-A5AX (12-bit digital input)
• It is desired to set the running frequency from a programmable controller. FR-A5NR
(Computer link RS-485)
FR-A5NC (CC-link)
FR-A5NP (Profibus)
FR-A5ND (Device Net)
FR-A5NM (Modbus Plus)
• It is desired to monitor the output frequency, output voltage and output FR-A5NR
current at the same time. (Computer link RS-485)
• It is desired to operate the inverter from a remote location. FR-A5NC (CC-link)
• It is desired to operate the inverter automatically. FR-A5NP (Profibus)
Operation FR-A5ND (Device Net)
• It is desired to operate the inverter with a personal computer or
FR-A5NM (Modbus Plus)
programmable controller.
• It is desired to change the parameter settings from a remote location.
• It is desired to start the inverter easily. FR-SW 0-SETUP-W J
• It is desired to make parameter settings from a personal computer easily. (inverter setup software)
• It is desired to set parameters by direct input. FR-PU04 (parameter unit)
• It is desired to have a parameter unit which displays English characters.
• It is desired to install the inverter in a control box and mount the parameter FR-CB201, FR-CB203,
unit on the door. FR-CB205
• It is desired to operate the inverter from a short distance from main unit. (connection cables)
Output signal • It is desired to drive an AC relay or contactor with the inverter output signal. FR-A5AR (relay output)
• If the power factor of the inverter is poor, it is necessary to increase the FR-BAL, FR-BEL (power
Power factor
power supply facility. factor improving reactors)
improvement
• Install the inverter near a large capacity power supply.
Harmonic • Harmonics may affect the power supply. FR-HC (high-power factor
suppression converter)
Noise • After installation of the inverter, a radio is affected by noise. FR-BIF (radio noise filter)
reduction FR-BLF (line noise filter)
technique • Leakage current may flow from the inverter. RF-BLF (line noise filter)
•
2
It is desired to decrease speed rapidly though machine GD is large. BU brake unit (brake unit +
Braking force • Enough braking capacity is needed for frequent speed increase and brake resistor)
increase decrease. FR-RC power return
converter
Application • It is desired to make various settings. FR series controller box
operation • It is desired to perform line control and joint operation.
• It is desired to place the inverter's heat generating section outside of the FR-A5CN
Installation enclosure to make inverter size smaller. Outside heat sink mounting
attachment
– 135 –
7. PERIPHERAL DEVICES AND OPTIONS
The power supply capacity (transformer capacity) on the inverter input side can be found by formula
(7.1):
The inverter power factor changes according to the load conditions and power supply conditions.
Hence, assuming that inverter power factor is 0.6 to 0.8 and considering the influence of a voltage
drop at power on of the inverter, suppose that the power supply capacity (transformer capacity) is 1.2
to 1.5 times larger the inverter output kVA. W hen the inverter is used with a power factor improving
reactor, set the power factor to 0.95 (FR-BEL) or 0.9 (FR-BAL) for calculations.
The power supply capacity (kVA) is indicated in the inverter manuals.
The NFB is used to protect the power supply cables to the inverter from damage by overload and
short-circuit currents.
1) Selection of NFB type
For the selection of the NFB's interrupting capacity, refer to the "Mitsubishi no-fuse breaker
technical information."
2) Selection of rated current
The inverter input current (effective value) varies according to the current form factor and the form
factor is influenced by power impedance.
Therefore, the rated current is set to not less than 1.4 times the input current effective value, with
not only the effective value but also the influence of harmonic components taken into
consideration.
3) For the selection of the NFB type and rated current, refer to "Peripheral Device Selection" in the
relevant catalog to prevent an incorrect trip when the peak value of inrush current occurs at power
on.
– 136 –
7. PERIPHERAL DEVICES AND OPTIONS
– 137 –
7. PERIPHERAL DEVICES AND OPTIONS
In a PW M type inverter, a surge voltage occurs at the motor terminals. Especially, a 400V class motor
insulation may deteriorate because of the surge voltage. Therefore, take the following measures
when a 400V class motor is to be driven by an inverter.
7.7.1 Measures
It is recommended to take either of the following measures:
(1) Techniques for enhancing motor insulation
Use an insulation-enhanced 400V class motor.
Specifically:
1) Specify the "inverter-driven, insulation-enhanced 400V class motor."
2) For dedicated motors such as a constant-torque motor and low-vibration motor, use a "motor
dedicated to inverter operation."
(2) Techniques for suppressing surge voltage on the inverter side
On the output side of the inverter, connect a filter designed to suppress a surge voltage so that
the motor terminal voltage is 850V or less.
W hen the motor is driven by a Mitsubishi inverter, connect the optional surge voltage suppression
filter in the output side of the inverter.
Ground screw K
Max. C
G F
D
Max. B
Terminal screw J E A
– 138 –
7. PERIPHERAL DEVICES AND OPTIONS
W hen a magnetic contactor (MC) is provided on the output side of the inverter, do not switch on the
output side magnetic contactor (MC) during inverter operation (in principle). If it is switched on during
inverter operation, a large starting current will trip the inverter due to overcurrent.
The output side magnetic contactor (MC) may be switched off during operation. At this time, the motor
coasts to a stop. The magnetic contactor (MC) is provided in the output side to:
1) Make up a commercial power supply-inverter switch-over circuit.
2) Use a single inverter to switch between two or more motors. (Switching should be made when the
inverter is at a stop.)
3) Separate the motor from the electric supply during a stop in an operation cycle.
For instructions to be followed when switching on-off the output side magnetic contactor MC, refer
to Section 3.5.4.
(1) The overcurrent protection of a standard motor provided by electronic overcurrent protection built
into the inverter cannot provide sufficient protection in the following cases. In these cases, install
a thermal relay between the motor and inverter.
1) W hen driving two or more motors by a single inverter
Inverter
NFB OCR Motor
Power
IM
supply
OCR
IM
2) W hen driving a special motor different in thermal characteristic from a standard motor
[Example] Submersible motor, multi-pole motor (8 or more poles)
3) W hen performing commercial power supply-inverter switch-over operation
MC C
Inverter
NFB Motor
MC F OCR
Power
supply IM
– 139 –
7. PERIPHERAL DEVICES AND OPTIONS
Select the size of the main circuit cables according to the voltage, current, ambient temperature and
wiring distance.
(1) Inverter input
Select the cable size matching the input current. (Refer to the sizes in the manual.)
(2) Inverter output
Select the size matching the motor current. W hen the distance between the inverter and motor is
long, a voltage drop may reduce the motor output torque or increase heat generated. Select a
cable size large enough to prevent this occuring. The wire size in the manuals uses a wiring length
of 20m.
– 140 –
7. PERIPHERAL DEVICES AND OPTIONS
7.12 Inverter Setup Software (FR-A500 series and FR-E500 series inverters)
The inverter setup software is a support tool designed to provide an easy inverter operating
environment from inverter startup to maintenance/checking.
Parameter setting, monitoring, etc. can be made easily and efficiently on the W indows screen of a
personal computer.
(1) Functions
• Parameter setting and editing ......... Four modes are available: all list, function list, individual
list and simple setting modes.
• Monitoring ..................................... Four modes are available: data display, meter display,
oscilloscope display and alarm history modes.
• Test operation ............................... Used to judge whether the inverter may be operated
properly without operation sequence to the inverter.
• Diagnostics .................................... Internal diagnostics for judging the operating status of the
inverter.
• System setting ............................... Setting made to write or read data to or from a
multi-inverter system.
• File................................................ Used to store parameters, operation data, etc. onto hard
disk/floppy disk etc.
• W indow ......................................... Able to show more than one screen.
00
00 00 00 00
FR-Q5000-0000K00
5 5
Inverter
Setup software
(Note: For RS-232C communication a standard
converter should be used (RS-485 to RS-232C). )
Note: The FR-E500 series inverter refers only to the Japanese version of the FR-E500.
– 141 –
8. MAINTENANCE AND INSPECTION
A transistorized inverter is a static unit consisting mainly of semiconductor devices. Daily inspection
must be performed to prevent any fault from occurring due to adverse influence of the installation
environment, such as temperature, humidity, dust, dirt, vibration, changes in the parts with time,
service life, and other factors.
For some time after the power is switched off, the smoothing capacitor remains at a high voltage.
Before accessing the inverter for inspection, make sure that the charge lamp is off and check that the
voltage across the main circuit terminals P-N of the inverter is 30VDC or less using a meter.
Note: Have a good understanding of the definitions of power and alarm indications provided by the
transistorized inverter. Also, have a good understanding of the electronic overcurrent
protection, acceleration/deceleration time and other settings using the parameter unit, and
record the set values.
– 142 –
8. MAINTENANCE AND INSPECTION
Note: The values for the 400V series are indicated in the parentheses.
For periodic inspection, contact your sales representative.
– 143 –
8. MAINTENANCE AND INSPECTION
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R, S, T, U, V, W , P and N, and
check for continuity.
– 144 –
8. MAINTENANCE AND INSPECTION
The inverter consists of many electronic parts such as semiconductor devices. The following parts
may deteriorate with age because of their structure or physical characteristics, leading to reduced
performance or failure of the inverter. For preventive maintenance, the following parts must be
changed periodically.
(1) Cooling fan
The cooling fan cools heat-generating parts such as the main circuit semiconductor devices. The
life of the cooling fan bearing is usually 10,000 to 35,000 hours. Hence, the cooling fan must be
changed every 2 to 3 years if the inverter is run continuously. W hen unusual noise and/or vibration
is noticed during inspection, the cooling fan must be changed immediately.
The FR-A500 series has a function to set the ON-OFF control of the cooling fan. W hen ON-OFF
control is set, the cooling fan life can be increased. Also, the cassette system ensures ease of
replacement.
(2) Smoothing capacitors
A large-capacity aluminum electrolytic capacitor is used for smoothing the DC in the main circuit,
and an aluminum electrolytic capacitor is also used for stabilizing the control power in the control
circuit. Their characteristics are adversely affected by ripple current, etc. W hen the inverter is
operated in ordinary, air-conditioned environment, change the capacitors about every 5 years.
W hen a given period has elapsed, the capacitors will deteriorate more rapidly. Check the
capacitors at least every year (less than six months if the life will be expired soon). Check the
following:
1) Case (side faces and bottom face for expansion)
2) Sealing plate (for warping and cracking)
3) Explosion-proof valve (for excessive valve expansion and operation)
4) Appearance, external cracks, discoloration, leakage.
W hen the measured capacitance of the capacitor has reduced below 85% of the rating,
change the capacitor.
(3) Relays
To prevent a contact fault, etc., relays must be changed according to the number of accumulative
switching operations (switching life). See the following table for the inverter parts replacement
guide. Lamps and other short-life parts must also be changed during periodic inspection.
– 145 –
8. MAINTENANCE AND INSPECTION
Input Output
voltage voltage
Input Output
current current
Inverter
Ar W11 R U Au W21
3-phase Vr Vu
At W13 T W Aw W22
Vt Vw
P N
2 5
+ –
Instrument
types
– 146 –
8. MAINTENANCE AND INSPECTION
8VDC
T2
Note 1: Do not use a meter because accurate data will not be obtained.
Note 2: When Pr. 195 "A, B, C terminal function selection" setting is positive logic.
* Values in parentheses indicate those for 400V series.
– 147 –
8. MAINTENANCE AND INSPECTION
The display of the parameter unit is switched as follows to indicate the cause of a faulty operation.
(For the FR-A500 series)
Display
Cause of Fault Check Point Remedy
Parameter unit
OC During Acc Overcurrent Acceleration too fast? Increase acceleration time. Change fan.
Main circuit device Check for output short circuit or ground Remove obstacle to cooling fan. (Note)
overheating fault.
Check for cooling fan stop.
Stedy Spd Oc Sudden load change? Keep load stable.
Check for output short circuit or ground Change fan.
fault. Remove obstacle to cooling fan. (Note)
Check for cooling fan stop.
OC During Dec Deceleration too fast? Increase deceleration time. Change fan.
Check for output short circuit or ground Remove obstacle to cooling fan. (Note)
fault. Check brake operation.
Check for cooling fan stop.
Mechanical brake of motor operate too
fast?
Ov During Acc Overvoltage on DC bus Acceleration too fast? Increase acceleration time.
(terminals P-N)
Stedy Spd Ov Sudden load change? Keep load stable.
Ov During Dec Deceleration too fast? Increase deceleration time.
(Set deceleration time which matches
load GD 2 .)
Reduce braking duty.
Motor Overload Thermal relay for motor Motor used under overload? Reduce load.
Inv. Overload Thermal relay for inverter Increase motor and inverter capacities.
Inst. Pwr. Loss Instantaneous power Check the cause of instantaneous power
failure failure.
Under Voltage Drop of power supply Large-capacity motor started? Check power system equipment such as
voltage power supply capacity.
H/Sink 0/Temp Heat sink overheat Ambient temperature too high? Lower ambient temperature to within
specifications.
Fan Failure • Cooling fan failure • Cooling fan stopped due to failure? • Change fan.
• Incorrect parameter • Operation different from cooling fan • Set correct value.
setting operation selection setting?
Br. Cct. Fault Brake transistor fault Braking duty too high? Reduce load GD 2 .
Reduce braking duty.
Ground Fault Ground fault occurred in Check motor and cables for ground fault. Resolve ground faults.
output circuit.
OH Fault External thermal relay Check motor for overheating. Reduce load and frequency of operation.
operated.
Stll Prev STP Stall prevention or current Motor used under overload? Reduce load.
limit activated too long. Increase motor and inverter size
Option Fault Option and inverter Check for loose connector. Connect securely.
connected improperly.
Corrupt Memry Storage device (E 2 PROM) Number of parameter write times too Change inverter.
faulty. many?
Retry No. Over Operation could not be Check cause of alarm occurrence.
resumed within the
number of retry times set.
CPU Fault CPU malfunction Check for loose connections. Change inverter.
PU Leave Out The PU has been Check that the PU is connected securely. Securely install the PU.
disconnected.
PU to Inverter • Reset signal ON • Check for incorrect wiring to the reset • Turn the reset signal off.
comms. Error • Connection between PU terminal. • Securely connect.
Inv. Reset ON and inverter loose *1 • Check for loose connector. • Change inverter.
• Communication circuit
fault
CPU malfunction *2 • Switch power off, then on.
• Switch reset signal on, then off.
• Change inverter.
Note: This alarm does not occur due to the cooling fan stop, but it will occur to prevent the main circuit devices from
overheating because of the fan failure.
*1: The parameter unit display remains unchanged but operation may be performed in the external operation mode.
*2: If the alarm is still displayed on the parameter unit after corrective action has been taken, the internal circuit may be
faulty. Consult your sales representative.
– 148 –
8. MAINTENANCE AND INSPECTION
– 149 –
8. MAINTENANCE AND INSPECTION
– 150 –
8. MAINTENANCE AND INSPECTION
* The stall prevention operation current can be set as appropriate. The factory setting is 150%.
– 151 –
8. MAINTENANCE AND INSPECTION
The training kit (FR-A training machine) can be used to confirm the capability of the
inverter-driven motor coupled with a load and the controllability and functions of the inverter.
Use this training kit to check the capability and functionality of the inverter.
(3) Inverter operation and monitoring (terminal I/O states, troubleshooting function, etc.) from the
interactive parameter unit.
Compensation
AM DV2
input
Power brake
DA
MC2
Load ON-OFF Load torque adjusting
variable resistor
– 152 –