Professional Documents
Culture Documents
3, JULY 2005
Abstract—This paper presents a procedure for the calculation that could detect those parameters for which more accurate in-
of lightning flashover rates of transmission lines using a Monte formation is required and the range of values that can be of con-
Carlo method. The procedure has been implemented in the Alter- cern for each parameter; see Section IX of this paper.
native Transients Program version of the Electromagnetic Tran-
sients Program. Parametric studies using this procedure can also The main contribution of this paper is the Alternative Tran-
be performed to determine the sensitivity of the flashover rate with sients Program (ATP) implementation of a new Monte Carlo
respect to some parameters of the transmission line and the return procedure for calculation of lightning flashover rates of over-
stroke. Some refinements are proposed to decrease the computer head transmission lines. The ATP is a well-known member of
time while preserving the accuracy of calculations. the Electromagnetic Transients Program (EMTP) family; there-
Index Terms—Modeling, Monte Carlo method, overvoltages, fore, its main solution algorithms are common to most electro-
power system lightning effects, sensitivity, statistics. magnetic transients programs [1]. For a summary of ATP capa-
bilities that can be useful for the present work, see [2].
I. INTRODUCTION The paper is organized as follows. Section II includes a sum-
mary on modeling guidelines for representing transmission lines
HE lightning performance of an overhead line can be
T measured by the flashover rate, usually expressed as the
number of flashovers per 100 km and year. Due to the random
in lightning overvoltage calculations. Two critical aspects when
calculating lightning overvoltages in transmission lines are the
representation of footing impedances and lightning strokes. An
nature of lightning, calculations must be based on a statistical analysis of the footing impedance and an introduction to the
approach. A Monte Carlo simulation is a very common method characteristic parameters of the return stroke are provided in
for this purpose. Sections III and IV, respectively. Section V gives a summary
Transmission lines are usually shielded by one or several of methods developed to date for the calculation of lightning
wires; therefore, lightning failures can be caused by strokes to flashover rates in overhead transmission lines. A description of
either a shield wire or a phase conductor, since overvoltages the Monte Carlo procedure and its implementation in ATP is de-
induced by strokes to ground can be neglected. Shielding tailed in Section VI. The application of the procedure to a test
failures cannot be totally prevented, but the number of strokes line is presented in Section VII. Some refinements of the proce-
to phase conductors is usually very low. The flashover rate of dure are analyzed in Section VIII. A parametric study of the test
a transmission line is therefore divided into the backflashover line aimed at determining the relationship of the flashover rate
rate (BFOR) and the shielding failure flashover rate (SFFOR). with respect to some parameters of the line and some variables
To obtain both quantities, an incidence model is required to of the return stroke are detailed in Section IX.
discriminate strokes to shield wires from those to phase con-
ductors and those to ground. II. MODELING FOR LIGHTNING OVERVOLTAGE CALCULATIONS
A Monte Carlo procedure for calculation of lightning
flashover rates can consist of the following steps: generation Several documents have been published to provide modeling
of random numbers to obtain those parameters of the lightning guidelines of power components in lightning overvoltage sim-
stroke and the overhead line of random nature; application ulations [3]–[8]. The following paragraphs summarize models
of an incidence model to deduce the point of impact of every and guidelines to be considered for overhead transmission lines.
lightning stroke; calculation of the overvoltage generated by 1) A transmission line is modeled by two or three spans at
each stroke, depending on the point of impact; and calculation each side of the point of impact. Each span is represented
of the flashover rate. by a multiphase untransposed distributed parameter line
Some of these steps are usually carried out with incomplete section. This representation can be made by using either
information or models of limited accuracy. For instance, the a frequency-dependent or a constant parameter model.
knowledge of the lightning parameters is usually incomplete, or If the second option is chosen, then it is recommended
the incidence model is not accurate enough. Some limitations to calculate parameters at a frequency between 400 and
can be partially overcome by performing a sensitivity analysis 500 kHz [7]. More accurate results are derived when the
corona effect is included in the model.
Manuscript received September 11, 2003; revised January 7, 2004. Paper no. 2) The representation of a line termination is needed at each
TPWRD-00467-2003. side of the above model to avoid reflections that could
The authors are with the Departament d’Enginyeria Elèctrica, Univer- affect the simulated overvoltages around the point of im-
sitat Politècnica de Catalunya, Barcelona 08028, Spain (e-mail: martinez@
ee.upc.edu). pact. This can be achieved by adding a long enough sec-
Digital Object Identifier 10.1109/TPWRD.2005.848454 tion at each side of the line, or by inserting a resistance
0885-8977/$20.00 © 2005 IEEE
MARTINEZ AND CASTRO-ARANDA: LIGHTNING PERFORMANCE ANALYSIS OF OVERHEAD TRANSMISSION LINES USING THE EMTP 2201
factor . Although the three waveforms have the same rise and
tail times, the time intervals between the start of the wave and
the crest are different.
(4)
(5a)
where
(5b)
(5c)
(5d)
(6a)
Fig. 3. Heidler model. Effect of factor n (t = 1:2 s, t = 50 s).
where
the first stroke is a better representation since it does not show (6b)
a discontinuity at .
(6c)
Several expressions have been proposed for such a waveform.
One of the most widely used is the so-called Heidler model. It This new function has a median value , which is the antilog
is given by of and a standard deviation given by (6c).
where is the peak current, is a correction factor of the peak Procedures for the calculation of lightning flashovers can be
current, is the current steepness factor, and and split into two main groups.
are time constants determining current rise and decay • Methods based on simplified models and approximated
time, respectively [25]. calculations of lightning overvoltages; they are derived
Fig. 2 depicts the waveform of a concave return stroke. The from guidelines proposed by IEEE [3]–[4], [27], IEC [24],
main parameters used to define this waveform in the present and CIGRE [5].
work are the peak current magnitude , the rise time • Methods based on more rigorous models and calculations;
, and the tail time (i.e., the time interval be- they usually rely on results derived from EMTP-like tools.
tween the start of the wave and the 50% of peak current on tail). The main differences between procedures are related to the
The main difficulty to synthesize a concave waveform is the following issues:
determination of the parameters to be specified in (3) from those • lightning stroke waveform and parameters;
of the return stroke [26]. Fig. 3 shows the effect of • lightning incidence models;
MARTINEZ AND CASTRO-ARANDA: LIGHTNING PERFORMANCE ANALYSIS OF OVERHEAD TRANSMISSION LINES USING THE EMTP 2203
TABLE I
LINE CONDUCTORS CHARACTERISTICS
paring the two distributions of Fig. 6, one can see that there is a
range of values for every type of failure and a range of peak cur- • Return stroke parameters play an important role in the
rent magnitudes that cause no failure. The procedure is stopped lightning performance of a transmission line. Since only
when the probability density function of all the random variables negative polarity strokes were assumed, more accurate re-
matches their theoretical functions within the specified error. In sults would be derived by assuming that a percentage of
this work, the resulting and the theoretical distributions were return strokes is of positive polarity. A seasonal variation
compared at 10%, 30%, 50%, 70%, and 90% of the cumulative of this percentage could also be considered [21].
distribution functions. More than 10 000 runs were needed to • The return stroke parameters that were included in the
match them within an error margin of 10%. For an error margin study and the way in which they were generated were
of 5%, no less than 30 000 runs were needed. Results shown in motivated by the fact that only the maximum over-
Fig. 6 were obtained after 40 000 runs. The flashover rate, for voltage across insulator strings was of concern. However,
fl/km , was 1.477 per 100 km and year. flashover caused by subsequent strokes could also be
Fig. 7 shows the rise-time distribution of lightning strokes considered [14]. Additional random parameters (e.g., the
to shield wires and towers. It is evident from this plot that the number of strokes per flash and the probability density
probability of failure with rise times above 5 s is negligible. functions for each multiplicity), should be calculated
when other aspects (e.g., line arrester failures) were of
concern.
D. Discussion
• Return strokes with a nonvertical path, when the leader
The following paragraphs are aimed at discussing the limita- approaches ground, have been reported [14]. Therefore, a
tions of the models used in this work and some future work. probability density function for the leader angle could be
• One of the steps that has received more criticism is the ap- considered in future versions of the procedure.
plication of the electrogeometic model, used to determine
the point of impact of a return stroke. Although it has been
adopted by some standards [27], it is recognized that other VIII. REFINING THE PROCEDURE
models (e.g., the Leader Progression model), represent an 1) With the criterion chosen for checking the convergence of
improvement [33]. the Monte Carlo method, one can assume that the number
• The limitations of models used in transients simulations of runs will be fixed for a given convergence error. That is,
are usually due to two reasons: lack of reliable data and this criterion guarantees the convergence of the input vari-
limited built-in capabilities of the simulation tool. Several ables, but since only a small percentage of the randomly
parts of the implemented model are not accurate enough: generated strokes will impact the line, the convergence of
the corona effect was not included in the line span models, the output variables (i.e., the distribution of stroke peak cur-
voltages induced by the electric and magnetic fields of rent magnitudes to shield wires and phase conductors), is
lightning channels to shield wires and phase conductors generally not achieved. This can only be improved by in-
were neglected, footing impedance and insulator string creasing the number of impacts to the line. A very simple
models were too simple. The calculation of induction ef- solution that keeps the above convergence criterion and im-
fects in transmission lines is a new subject for which not proves the solution of the Monte Carlo procedure can be
much work has been performed, see [34]–[35]; however, based on a reduction of the area of impact of return strokes;
they can significantly affect the flashover rate, as reported that is, on decreasing the maximum distance from vertical
in [35]. A new random variable, the return stroke velocity, paths and the line. Locations of vertical path strokes are
must be generated when induction effects are simulated. randomly generated by assuming a uniform ground distri-
Present ATP capabilities are a drawback for an easy and bution. Therefore, only a span length of the line has to be
accurate implementation of corona and induction effects. analyzed. If the area where stroke channels are located is
2206 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 3, JULY 2005
TABLE II
PERFORMANCE OF THE REFINED PROCEDURE
ACKNOWLEDGMENT
The second author would like to express his gratitude to the
Universidad del Valle (Cali, Colombia) for the support received
during the preparation of his Ph.D.
REFERENCES
[1] H. W. Dommel, Electromagnetic Transients Program. Reference
Manual. Portland, OR: Bonneville Power Administration, 1986.
[2] J. A. Martinez and J. Martin-Arnedo, “Expanding capabilities of EMTP-
like tools: From analysis to design,” IEEE Trans. Power Del., vol. 18, no.
4, pp. 1569–1571, Oct. 2003.
[3] IEEE Working Group on Lightning Performance of Transmission Lines,
“A simplified method for estimating lightning performance of trans-
mission lines,” IEEE Trans. Power App. Syst., vol. PAS-104, no. 4, pp.
919–932, Apr. 1985.
[4] IEEE Working Group on Lightning Performance of Transmission
Lines, “Estimating lightning performance of transmission lines II:
Updates to analytical models,” IEEE Trans. Power Del., vol. 8, no. 3,
pp. 1254–1267, Jul. 1993.
[5] Guide to Procedures for Estimating the Lightning Performance of Trans-
mission Lines, 1991. CIGRE WG 33-01, CIGRE Brochure 63.
[6] Guidelines for Representation of Network Elements When Calculating
Transients, 1990. CIGRE WG 33-02, CIGRE Brochure 39.
[7] IEEE TF on Fast Front Transients, “Modeling guidelines for fast tran-
sients,” IEEE Trans. Power Del., vol. 11, no. 1, pp. 493–506, Jan. 1996.
[8] A. M. Gole, J. A. Martinez-Velasco, and A. J. F. Keri, Modeling and
Analysis of System Transients Using Digital Programs: IEEE PES Spe-
cial Publication, 1999, TP-133-0.
[9] W. A. Chisholm, Y. L. Chow, and K. D. Srivastava, “Lightning surge
Fig. 15. Sensitivity analysis. Influence of the coefficient of correlation (Peak response of transmission towers,” IEEE Trans. Power App. Syst., vol.
current magnitude = 34 kA, rise time = 2 s, N = 1 fl/km ). (a) Total PAS-102, no. 9, pp. 3232–3242, Sep. 1983.
flashover rate. (b) Backflashover rate. [10] M. Ishii et al., “Multistory transmission tower model for lightning surge
analysis,” IEEE Trans. Power Del., vol. 6, no. 3, pp. 1327–1335, Jul.
1991.
[11] T. Yamada et al., “Experimental evaluation of a UHV tower model for
• According to (6b), the median value of the conditioned lightning surge analysis,” IEEE Trans. Power Del., vol. 10, no. 1, pp.
393–402, Jan. 1995.
peak current magnitude decreases with the given rise-time
[12] T. Hara and O. Yamamoto, “Modeling of a transmission tower for light-
value. The effect is very dependent on the coefficient of ning surge analysis,” Proc. Inst. Elect. Eng., Gen. Transm. Distrib., vol.
correlation; the greater this coefficient is, the greater the 143, no. 3, pp. 283–289, May 1996.
reduction of the median value will be. [13] Y. Baba and M. Ishii, “Numerical electromagnetic field analysis on light-
ning surge response of tower with shield wire,” IEEE Trans. Power Del.,
• The BFOR decreases as increases because most back- vol. 15, no. 3, pp. 1010–1015, Jul. 2000.
flashovers are caused by return strokes with a rise time [14] A. R. Hileman, Insulation Coordination for Power Systems. New
equal or shorter than 2 s (see Fig. 7). York: Marcel Dekker, 1999.
• Direct stroke flashovers are caused by strokes with a peak [15] W. A. Chisholm and W. Janischewskyj, “Lightning surge response
of ground electrodes,” IEEE Trans. Power Del., vol. 14, no. 2, pp.
current magnitude ranging from 14 to 28, but the per- 1329–1337, Apr. 1989.
centage of strokes with these values remains practically [16] A. M. Mousa, “The soil ionization gradient associated with discharge
constant, regardless of the value of . of high currents into concentrated electrodes,” IEEE Trans. Power Del.,
vol. 9, no. 3, pp. 1669–1677, Jul. 1994.
[17] M. E. Almeida and M. T. Correia de Barros, “Accurate modeling of
rod drive tower footing,” IEEE Trans. Power Del., vol. 11, no. 3, pp.
X. CONCLUSION 1606–1609, Jul. 1996.
[18] A. Geri, “Behavior of grounding systems excited by high impulse cur-
This paper has presented a new procedure for lightning anal- rents: The model and its validation,” IEEE Trans. Power Del., vol. 14,
ysis of overhead transmission lines based on new ATP capabili- no. 3, pp. 1008–1017, Jul. 1999.
ties. All results presented in this document have been derived by [19] R. B. Anderson and A. J. Eriksson, “Lightning parameters for engi-
using a single input file. One of the main goals was to analyze neering applications,” Electra, no. 69, pp. 65–102, Mar. 1980.
[20] P. Chowdhuri, Electromagnetic Transients in Power Systems. New
the influence that some parameters can have on the flashover rate York: RSP Press/Wiley, 1996.
of a transmission line. Sensitivity studies can be useful for eval- [21] IEEE TF on Parameters of Lightning Strokes, “Parameters of lightning
uating the influence of every parameter involved in the lightning strokes: A review,” IEEE Trans. Power Del., vol. 20, no. 1, pp. 346–358,
Jan. 2005.
performance and deciding with which accuracy some parame- [22] H. Motoyama, “Experimental study and analysis of breakdown charac-
ters should be specified. teristics of long air gaps with short tail lightning impulse,” IEEE Trans.
The study has been based on a simplified representation of Power Del., vol. 11, no. 2, pp. 972–979, Apr. 1996.
some important parts of the whole model. Future work will in- [23] A. Pigini et al., “Performance of large air gaps under lightning overvolt-
ages: Experimental study and analysis of accuracy of predetermination
clude a more accurate representation of some components (e.g., methods,” IEEE Trans. Power Del., vol. 4, no. 2, pp. 1379–1392, Apr.
footing impedances and insulator strings). 1989.
2210 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 3, JULY 2005
[24] Insulation Co-ordination, Part 2: Application Guide, 1996. IEC [34] S. Sekioka, T. Ueda, I. Matsubara, and S. Kojima, “Incoming lightning
60 071-2. surge analysis considering return stroke parameters,” in Proc. IPST’99,
[25] F. Heidler, J. M. Cvetic, and B. V. Stanic, “Calculation of lightning cur- Budapest, Hungary, Jun. 20–24, 1999, pp. 383–388.
rent parameters,” IEEE Trans. Power Del., vol. 14, no. 2, pp. 399–404, [35] P. Chowdhuri, S. Li, and P. Yan, “Rigorous analysis of back-flashover
Apr. 1999. outages caused by direct lightning strokes to overhead power lines,”
[26] J. A. Martinez, F. Castro-Aranda, and O. P. Hevia, “Generación aleatoria Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol. 149, no. 1, pp. 58–65,
de los parámetros del rayo en el cálculo de sobretensiones atmosféricas,” Jan. 2002.
ALTAE, Aug. 18–23, 2003. in Spanish. [36] G. J. Anders, Probability Concepts in Electric Power Systems. New
[27] IEEE Guide for Improving the Lightning Performance of Transmission York: Wiley, 1990.
Lines, 1997. IEEE Std. 1243-1997.
[28] W. A. Chisholm, “The IEEE Flash program: A structure for evaluation of
transmission lightning performance,” Trans. Inst. Elect. Eng. Jpn., vol.
121-B, no. 8, pp. 914–197, 2001.
[29] J. G. Anderson, Transmission Line Reference Book, 345 kV and Above, Juan A. Martinez (M’83) was born in Barcelona, Spain.
2nd ed. Palo Alto, CA: EPRI, 1981, ch. 12. Currently, he is Profesor Titular, Departament d’Enginyeria Elèctrica, Univer-
[30] M. A. Ismaili, P. Bernard, R. Lambert, and A. Xémard, “Estimating sitat Politècnica de Catalunya, Barcelona, Spain. His teaching and research in-
the probability of failure of equipment as a result of direct lightning terests include transmission and distribution, power system analysis, and EMTP
strikes on transmission lines,” IEEE Trans. Power Del., vol. 14, no. 4, applications.
pp. 1394–1400, Oct. 1999.
[31] R. Lambert, E. Tarasiewicz, A. Xémard, and G. Fleury, “Probabilistic
evaluation of lightning-related failure rate of power system apparatus,”
IEEE Trans. Power Del., vol. 18, no. 2, pp. 579–586, Apr. 2003.
[32] G. Furst, “Monte Carlo lightning backflash model for EHV lines. A Ferley Castro-Aranda was born in Tuluà, Colombia. He is currently pursuing
MODELS-based application example,” in EEUG Meeting, Budapest, the Ph.D. degree at the Universitat Politècnica de Catalunya, Barcelona, Spain.
Hungary, Nov. 10–12, 1996, pp. 10–12. He is Profesor Asociado at the Universidad del Valle, Cali, Colombia. His re-
[33] Lightning Exposure of Structures and Interception Efficiency of Air Ter- search interests are in the areas of insulation coordination and system modeling
minals, 1997. CIGRE TF 33.01.03, CIGRE Brochure 118. for transient analysis using EMTP.