Professional Documents
Culture Documents
1
J. Neymark & Associates, Golden, Colorado, USA
2
Mike D. Kennedy, Inc., Port Townsend, Washington, USA
3
National Renewable Energy Laboratory, Golden, Colorado, USA
4
AAON, Inc., Tulsa, Oklahoma, USA
5
GARD Analytics, Inc., Arlington Heights, Illinois, USA
6
Lawrence Berkeley National Laboratory, Berkeley, California, USA
7
Thermal Energy System Specialists, LLC, Madison, Wisconsin, USA
8
Tsinghua University, Beijing, China
S S S
A
A C A C
Zone Supply
VAVTerminals
VAV Terminal Air Splitter
with
with
A
Reheat
Reheat Coils A
C c A c A
Zone 1 Supply Air
Zone 2 Supply Air
(z1s)
Bypass (z2s)
A
Damper
S
Zone 1 S
Zone 2
Exhaust Fan
Zone 1 Exhaust Fan
Recirculated
Air Node
Air Zone 1* (z1) Zone 2*
System A S Zone 2 Air
Relief Air Node (z2)
Table 1. Airside HVAC equipment analytical verification test case descriptions—VAV system (SI units)
Ambient Zone Zone Zone Loadsa (W)
Case ODB ODP Num. IDB Sensible Latent Coil Load Type Section Number
(C) (C) (C) Heating Cooling
No Economizer
AE401 -29.0 -29.0 1 21.111 2931 0 586.1 High Heating 5.5.4.1
2 22.222 2345 0 879.2
AE403 15.5 -3.0 1 23.333 0 1465 586.1 Low Cooling, dry coil 5.5.4.2.1
2 24.444 0 2345 879.2
AE404 26.9 22.1 1 23.889 0 2931 586.1 High Cooling, wet coil 5.5.4.2.2
2 25.000 0 3517 879.2
AE405 24.9 2.4 1 23.333 0 1465 586.1 Low Cooling, dry coil 5.5.4.2.3
2 24.444 0 2345 879.2
AE406 23.0 20.9 1 23.333 0 1465 586.1 Low Cooling, wet coil 5.5.4.2.4
2 24.444 0 2345 879.2
Return Air Comparative Dry-Bulb Economizer Outdoor Air Control
AE426 23.0 20.9 1 23.333 0 1465 586.1 Low Cooling, wet coil 5.5.4.3.1. AE406 with
2 24.444 0 2345 879.2 dry-bulb economizer
Return Air Comparative Enthalpy Economizer Outdoor Air Control
AE445 24.9 2.4 1 23.333 0 1465 586.1 Low Cooling, dry coil 5.5.4.3.2. AE405 with
2 24.444 0 2345 879.2 enthalpy economizer
a
Zone loads do not include outdoor air ventilation loads introduced by the mechanical equipment.
DEEAPg 1.1.2 AAON, Inc., United States AAON, Inc., United States DEEAP/AAON
TRNSYS
TESSr/UWMs, United States TESSr, United States TRNSYS/TESS
17.01.0028
a l
PSU: The Pennsylvania State University, United States DOE-BT: U.S. Department of Energy, Office of Building
b
UNO: University of Nebraska - Omaha, United States Technologies, Energy Efficiency and Renewable Energy,
c
TAMU: Texas A&M University, United States United States
d m
NREL: National Renewable Energy Laboratory, United IES-VE: Integrated Environmental Solutions - Virtual
States Environment
e n
J. Neymark & Associates, United States IES: Integrated Environmental Solutions, United Kingdom
f o
Mike D. Kennedy, Inc., United States LCEM: Life Cycle Energy Management tool
g p
DEEAP: Detailed Energy and Economic Analysis Program MLIT: Ministry of Land, Infrastructure, Transportation and
h
DeST: Designer's Simulation Toolkit Tourism, Japan
i q
LBNL: Lawrence Berkeley National Laboratory, United TTE: Takasago Thermal Engineering, Japan
r
States TESS: Thermal Energy System Specialists, United States
j s
JJH: James J. Hirsch & Associates, United States UWM: University of Wisconsin – Madison, United States
k
UC: University of California, United States
0
AET101a AET103a AET104a AET201a AET203a AET204a AET205a AET206a AET226a AET245a
FC Heat FC Dry Coil FC Wet Coil SZ Heat SZ Dry Coil SZ Wet Coil SZ Dry Coil SZ Wet Coil SZ Wet Coil SZ Dry Coil
-29.0/-29.0 15.5/7.2 26.9/23.4 -29.0/-29.0 15.5/7.2 26.9/23.4 24.9/13.0 23.0/21.5 23.0/21.5 24.9/13.0
No Econo No Econo Dry Bulb Enthalpy
Econo Econo
Figure 2. Airside HVAC BESTEST—total coil load, FC and SZ, before BESTESTing
(Abbreviations along x-axis describe test cases, numeric values are ODB/OWB; see Nomenclature)
5
Coil Load (kWh/h)
0
AE101 AE103 AE104 AE201 AE203 AE204 AE205 AE206 AE226 AE245
FC Heat FC Dry Coil FC Wet Coil SZ Heat SZ Dry Coil SZ Wet Coil SZ Dry Coil SZ Wet Coil SZ Wet Coil SZ Dry Coil
-29.0/-29.0 15.5/-3.0 26.9/22.1 -29.0/-29.0 15.5/-3.0 26.9/22.1 24.9/2.4 23.0/20.9 23.0/20.9 24.9/2.4
No Econo No Econo Dry Bulb Enthalpy
Econo Econo
QAS/PSU-TAMU-NREL DEEAP/AAON DeST/TsinghuaU-LBNL DOE-2.2/NREL EnergyPlus/GARD
IES-VE/IES LCEM/MLIT-TTE TRNSYS/TESS Tested Prg/Org
Figure 3. Airside HVAC BESTEST—total coil load, FC and SZ, after BESTESTing
(Abbreviations along x-axis describe test cases, numeric values are ODB/ODP; see Nomenclature)
20
15
10
0
AET301 AET303 AET304 AET305 AET306 AET326 AET345 AET401 AET403 AET404 AET405 AET406 AET426 AET445
Heat Dry Coil Wet Coil Dry Coil Wet Coil Wet Coil Dry Coil Heat Dry Coil Wet Coil Dry Coil Wet Coil Wet Coil Dry Coil
-29.0/-29.0 15.5/7.2 26.9/23.4 24.9/13.0 23.0/21.5 23.0/21.5 24.9/13.0 -29.0/-29.0 15.5/7.2 26.9/23.4 24.9/13.0 23.0/21.5 23.0/21.5 24.9/13.0
No Econo No Econo DB Econo Enth. Eco No Econo No Econo DB Econo Enth. Eco
Figure 4. Airside HVAC BESTEST—total coil load, CV and VAV, before BESTESTing
(Abbreviations along x-axis describe test cases, numeric values are ODB/OWB; see Nomenclature)
20
Coil Load (kWh/h)
15
10
0
AE301 AE303 AE304 AE305 AE306 AE326 AE345 AE401 AE403 AE404 AE405 AE406 AE426 AE445
Heat Dry Coil Wet Coil Dry Coil Wet Coil Wet Coil Dry Coil Heat Dry Coil Wet Coil Dry Coil Wet Coil Wet Coil Dry Coil
-29.0/-29.0 15.5/-3.0 26.9/22.1 24.9/2.4 23.0/20.9 23.0/20.9 24.9/2.4 -29.0/-29.0 15.5/-3.0 26.9/22.1 24.9/2.4 23.0/20.9 23.0/20.9 24.9/2.4
No Econo No Econo DB Econo Enth. Eco No Econo No Econo DB Econo Enth. Eco
Figure 5. Airside HVAC BESTEST—total coil load, CV and VAV, after BESTESTing
(Abbreviations along x-axis describe test cases, numeric values are ODB/ODP; see Nomenclature.)