You are on page 1of 5

C ATA LO G

SafeRing/SafePlus 12-24kV
Gas-insulated ring main unit SafeRing and
Compact switchgear SafePlus

• No live parts exposed


• High reliability and safety
• Safe and easy for operators in both
maintenance and operating conditions
DISTRIBUTION SOLUTIONS 13


Safety

Internal Arc Classification (IAC)
During development of all ABB products, focus is

01 Arc duration on personnel safety. The SafeRing/SafePlus Energy
kA²s
and damage
portfolio is designed and tested to withstand a
caused
variety of internal arc scenarios at the same current 0.2 sec steel fire

level as the maximum short-circuit current. The tests


show that the metal enclosure of SafeRing/SafePlus is
able to protect personnel standing close to the
0.15 sec copper fire
switchgear during internal arc fault.
0.1 sec cable fire

Causes and effects of internal arcs


Although an internal arc fault is highly unlikely it can Time
Sec
theoretically be caused by various factors, such as: 0 0.03-0.05 0.1 0.15 0.2 0.7 0.8 0.9 1

• Insulation defects due to quality deterioration —


of the components. The reasons can be adverse 01

environmental conditions and a highly polluted R

atmosphere
• Inadequate training of the personnel in charge of
L
the installation leading to incorrect installation
of the cables
• Broken or modified safety interlocks
L
• Overheating of the contact area, e.g. when the
connections are not sufficiently tightened
F
• Short circuits caused by small animals that have
entered into the cable compartment F (front) = Access from the front
(i.e. through cable entrance) L (lateral) = Access from sides
R (rear) = Access from the rear
The energy produced by the internal arc causes the
following phenomena: Accessible sides of switchgear = Area that
• Increase of the internal pressure personnel can enter freely. For accessibility A this
• Increase of the temperature means a 300 mm safety distance + 500 mm or
• Visual and acoustic effects more in safe moving area.
• Mechanical stresses on the switchgear structure
• Melting, decomposition and evaporation of Non-accessible side of switchgear = Area that is
materials physically blocked or clearly marked as not safe
for personnel.
Tested according to IEC standard 62271-200
The capability of SafeRing/SafePlus switchgear to All test specimens passed the following test
withstand internal arc is proven by type tests criteria according to the standards:
performed according to internal arc classification 1. Correctly secured doors and covers do not
(IAC) as described in the standard IEC 62271-200 as open
follows. Accessibility A and B (switchgear) 2. No fragmentation of the enclosure occurs
within the time specified for the test.
A = Accessible to authorized personnel only Projection of small parts up to an individual
300 mm safety distance on accessible sides of mass of 60 g are accepted
the switchgear (also distance to sensors during 3. Arcing does not cause holes in the enclosure
testing) of the switchgear up to a height of 2 m
4. Indicators do not ignite due to the effect of
B = Public access hot gases
100 mm safety distance on accessible sides of the 5. The enclosure remains connected to its
switchgear (also distance to sensors during testing) earthing point
14 SAFERING / SAFEPLUS 12-24KV

­—
Internal Arc Classification (IAC)

— SafeRing/SafePlus is available for a wide range of IAC AFLR or AFL - downwards ventilation with
01 *290 mm base frame
available as an option. installations and applications in order to ventilation down to the cable trench.
Note: The height of the secure the highest safety for operators.
exhaust channel must
always be 2002 mm in Switchgears are designed and type-tested for With this setup, hot gases and pressure are
order to comply with internal arc classification according to the evacuated downwards in the cavity in the floor
the requirements in IEC
standards. When the following configurations: beneath the switchgear. Hot gases are led to the
base frame is 290 mm, cable trench by means of a back plate installed on
the exhaust channel
is extended to reach IAC AFLR - with ventilation upwards through an the rear side of the switchgear, forcing the hot
2002 mm height exhaust channel gases down during an arc fault. The switchgear

02 1100 mm version must be arranged as instructed according to the
available as an option With this setup, hot gasses and pressure are basic parameters below.
evacuated into the safe area of the switchgear
room above the switchgear through the gas Basic parameters of set-up:
exhaust channel. In this setup the switchgear can • IAC AFLR or AFL up to 20 kA / 1s
be installed as free standing. This solution is not • Minimum height of ceiling: 2000 mm
available for M-module. With this solution, a base • Recommended distance to back wall:
frame of 450 mm (optional 290 mm) is included - 800 mm with accessible rear side
as standard. - 100 mm recommended for non-accessible
rear side (possible down to 20mm)
Basic parameters of setup: • Back plate installed on the switchgear
• IAC AFLR up to 25 kA / 1s • Requires a minimum opening between
• Minimum height of ceiling: 2600 mm switchgear and cable trench in the “pressure
• Minimum distance from backwall: relief area” for each module shown as
- 800 mm with accessible rear side opening “A” in illustration “02”.
- 100 mm with non-accessible rear side - Opening “A” in a 1-way module: 250x205mm
• Switchgear needs to be installed and fixed to - Opening “A” in 2-5 way modules: 150x205mm
the floor in accordance with “SafeRing/ It is optional to cover opening “B” between
SafePlus 12-24kV Installation and operating the switchgear cable compartment and the
instructions” cable trench with a gland plate. This is not an
allowed option for low version switchgears.
For number of modules, availability, heights and • Minimum width of cable trench: 475 mm
specifications, see table no. 5.1.1. • Minimum depth of cable trench: 450 mm
• A pressure relief channel to a safe area is
required and it must have a free opening area
of 0.1m²
• Switchgear needs to be installed and fixed to
the floor in accordance with “SafeRing/
SafePlus 12-24kV Installation and operating
instructions".

SF6

SF6
min. 2600

1786 (1626)*

min. 2000

1336 (1100)*
2002
450 (290)*

450

A B

100
800 475
— —
01 02
DISTRIBUTION SOLUTIONS 15


01 If the distance IAC AFL – Backwards ventilation • Larger distances can be accepted if the area
from the side wall is with ventilation behind the switchgear. between the switchgear and back wall is
greater than 20 mm, arc
shields on both sides non-accessible.
are required. Marked With this setup, hot gases and pressure are • Switchgear needs to be installed and fixed to
area is restricted, but
installation is allowed evacuated behind the switchgear. Hot gases are the floor in accordance with “SafeRing /
if mounting of arc led to the safe areas of the switchgear room by SafePlus 12-24kV Installation and operating
shield is feasible.
— means of arc shields installed on accessible lateral instructions”
02 Arc shield sides of the switchgear or as a combined solution
He of arc shield for
M-module is 1317 mm. with additional ventilation down into a cable For number of modules, availability, heights and
— trench. specifications, see table no. 5.1.1.
03 Arc shield with
base frame.
— Basic parameters of set-up:
04 1100 mm version
available as option. • IAC AFL up to 20 kA / 1s Non-arc proof version
• Minimum height of ceiling: 2400 mm
• Arc shields need to be installed if the distance The non-arc proof version of the switchgear is not
between the switchgear and respective verified for any of the IAC-classes. In the highly
sidewall(s) is more than 20 mm to maintain its unlikely event of an internal arc fault in the switch-
AFL gear, hot gases and pressure could evacuate
• Arc shields are 100 mm randomly in any direction at any place of
• Minimum distance to back wall: 100 mm enclosure.

SF₆
2400
min. 2400
min.

13361336
650
650

100
100

— —
01 02

SF₆

SF₆
min.min.2400
2400

min.2400
1786
1786

2400

1336
min.

1336
1101
1101

100
100 100
100

— —
03 04
16 SAFERING / SAFEPLUS 12-24KV

Table

ISC Height of switchgear Roof height Max sets of current


IAC class Ventilation Base frame
(kA/1s) (mm) (mm) transformers

1336 (standard) 2400 (standard) Optional


AFL Backwards 2 2)
1100 (low) 2400 (low) (290/450 mm)

1336 (standard) 2000 (standard) Optional


AFL Downwards 3) 2 2)
1100 (low) 6) 2000 (low) (290/450 mm)
16

1336 (standard) 2000 (standard) Optional


AFLR Downwards 3) 2 2)
1100 (low) 6) 2000 (low) (290/450 mm)

Mandatory 5)
AFLR Upwards 4) 2002 1) 2600 2 2)
(290/450 mm)

1336 (standard) 2400 (standard) Optional


AFL Backwards 2 2)
1100 (low) 2400 (low) (290/450 mm)

1336 (standard) 2000 (standard) Optional


AFL Downwards 3) 2 2)
1100 (low) 6) 2000 (low) (290/450 mm)
20
1336 (standard) 2000 (standard) Optional
AFLR Downwards 3) 2 2)
1100 (low) 6) 2000 (low) (290/450 mm)

Mandatory 5)
AFLR Upwards 4) 2002 1) 2600 2 2)
(290/450 mm)

Mandatory 5)
25 AFLR Upwards 4) 2002 1) 2600 2 2)
(450 mm)

1) Height of exhaust channel is always 2002 mm. This dimension is independent


of the height of the base frame and switchgear.
2) In case two sets of CT’s are required, additional base frame is mandatory and
gland plate is not allowed as second set of CT’s will be installed in base
frame.
3) IAC classification is unavailable in case of installation deviating from basic
parameter set-up described in "downwards ventilation" section on previous
pages.
4) Upwards ventilation solution requires a base frame for attaching the gas
exhaust channel. Only available from 2-way to 5-way switchgears.
5) Not allowed with gland plate between switchgear and base frame, gland plate
can be installed below base frame.
6) Not allowed with gland plate on low version for this ventilation direction

You might also like