You are on page 1of 9

This article has been accepted for inclusion in a future issue of this journal.

Content is final as presented, with the exception of pagination.

IEEE SYSTEMS JOURNAL 1

A Practical Approach to Inertia Distribution


Monitoring and Impact of Inertia Distribution
on Oscillation Baselining Study for Renewable
Penetrated Power Grid
Gayathri K, Student Member, IEEE, and Manas Kumar Jena , Senior Member, IEEE

Abstract—The high penetration of inverter-based resources the system via power electronic converters. These back-to-back
(IBRs) will substantially change the dynamic behavior of the power converters electrically decouple the generators from the grid.
system including inertia distribution. Real-time inertia distribution
Therefore, net inertia provided by these power plants to the
monitoring is important to support power system operation in
future low inertia grids. This article presents the development and system is nearly zero. It can cause stability issues in the system
validation of a center of power-based inertia distribution estimation and can even lead to blackouts [1], [2].
technique utilizing the measurements available from the phasor It is evident from the prediction done on the U.K. power grid
measurement units of the wide-area measurement systems. The that the system inertia will reduce to 30% by the year 2033/34
suggested technique is validated on the 246-bus northern regional as compared to 2013/14 [3]. A system with low inertia will be
power grid of Indian power system. The impact of different pen-
etration levels of IBRs on the proposed inertia distribution index highly prone to issues, such as stress, instability, and insecure
(IDI) is also studied. The suggested index works purely on power operation. Secure operation of a deregulated system with high
system measurements and does not need any model information. renewable energy source (RES) penetration is a major task for
Further, the impact of change in IDI on oscillation baselining study operators due to its uncertainty. In this regard, there is a need to
is explored. monitor the power system with higher agility to enhance wide-
Index Terms—Inertia distribution index (IDI), phasor area situational awareness (WASA). Power system monitoring
measurement unit (PMU), power system inertia, power system can be broadly defined as collection, processing, and presenting
monitoring, renewable energy sources (RES). large data available from the grid. As more renewable sources
are getting integrated to the grid, real-time estimation of power
I. INTRODUCTION
system inertia will help the system operators to manage grid
A. Background inertia and thereby ensure stable operation [4], [5]. In this regard,
system operators are already looking for innovative and scalable
N POWER systems, inertia refers to the stored energy in
I rotating masses. Energy generation in traditional power sys-
tems is mainly from thermal, hydro, and nuclear power plants
wide-area monitoring system (WAMS) solutions for enhanced
power system monitoring, control, and protection. General Elec-
tric (GE) phasorpoint, real-time dynamics monitoring system
where synchronous generators (SG) are employed. The rota-
(RTDMS) are examples of such industry software developed
tional inertia of the SG provides kinetic energy in case of any
for power system monitoring [6], [7]. Further, power system
load-generation imbalance in the system. It helps to maintain the
inertia monitoring is going to be one of the most relevant WAMS
frequency deviation within limits and thereby ensures system
solutions for the control rooms of future power systems with
stability. Rising environmental concerns lead to increased pen-
major power generation from RES. The scope of this article is to
etration of green energy sources, such as solar and wind power
enhance WASA of the power system by incorporating an inertia
plants into the existing power grid. The integration of renewable
distribution index (IDI) monitoring scheme into the power sys-
energy into the system has caused a drastic reduction in the
tem monitoring application in the energy management system.
system rotational inertia. The solar power plants do not have any
Further, the possible impact of change in IDI on oscillation
rotating mass and hence are inertia less. Even though the blades
baselining study (OBS) is explored.
of wind generators can provide inertia, they are connected to

B. Related Works
Manuscript received 2 May 2022; revised 19 October 2022; accepted 9 Several methods are proposed in the literature for power
December 2022. This work was supported by the Science and Engineering
Research Board, Department of Science and Technology, Government of India system inertia constant estimation [8], [9], [10], [11], [12],
under project SRG/2021/000190. (Corresponding author: Manas Kumar Jena.) [13], [14], [15], [16]. Inertia estimation can be classified into
The authors are with the Department of Electrical Engineering, In- two categories: i) estimation based on ambient data, and ii)
dian Institute of Technology Palakkad, Palakkad 678007, India (e-mail:
122114006@smail.iitpkd.ac.in; mkj@iitpkd.ac.in). estimation based on disturbance data. From ambient data,
Digital Object Identifier 10.1109/JSYST.2022.3228966 inertia can be estimated using system identification method [8].
1937-9234 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

2 IEEE SYSTEMS JOURNAL

Swing equation-based techniques are commonly used for inertia expressions to establish the impact of change in IDI on power
estimation of systems after a large disturbance [10]. Further, a system oscillatory modes are derived in Section III. The details
microperturbation method-based inertia estimation technique is of the test system used and results of various case studies
discussed in [13]. However, perturbation is not desirable in an conducted are explained in Section IV. Salient features of
actual system. In [11] the total inertia of the GB power system the proposed scheme are highlighted in Section V. Finally,
is estimated using the the frequency transients. Further, there are Section VI concludes the manuscript.
machine learning-based inertia calculation techniques discussed
in the literature [3], [17]. In [17] random forest technique is used II. FORMULATION OF COP-BASED IDI
for inertia estimation from ambient data. In the case of machine
Inertia of a single machine can be represented by the inertia
learning-based techniques, the main constraint is the availability
constant, H
of data and processing speed. Further, in all these cases, inertia
of the total system will be calculated. With the high integration Jω 2
H = (1)
of renewable sources, the assumption that frequency is a global 2SB
signal is no longer valid. Renewable generators will be installed where J is the moment of inertia, ω is the angular frequency, and
where natural resources are available. The future power system SB is the base apparent power. However, the individual machine
will witness a greater and regional variability in frequency. frequencies may not be always same during a disturbance [22].
Center of inertia (COI) is a more meaningful way of rep- In such cases, the total inertia for large system can be expressed
resenting system inertia for a multimachine system [18]. The in an efficient manner using the concept of COI. The COI can
COI location calculation is useful for multiple purposes. One be calculated using the inertia and frequency information from
such example is to find the best location for employing inertia all the network generators [19]
emulation controllers. However, COI calculation is not efficient n
for large and meshed power systems. In such case, inertia i=1 Hi fgi
fCOI =  n (2)
distribution monitoring (IDM) will be more useful to the system i=1 Hi
operator [19]. IDI is an estimation of the electrical distance of where n is the number of generators, Hi and fgi are inertia and
each bus from the COI location. frequency of the ith generator, respectively.
System classification using IDI is a relatively unexplored area However, the inertia time constant is difficult to access in
of research. In [19] and [20], IDI is calculated based on the COI. real time because the number of units being dispatched from
However, this method requires real-time inertia information of a generation plant can vary during operation. Thus, in this
the system, which is not reported by the phasor measurement study a center of power (COP)-based IDI is suggested using
units (PMUs) connected. IDI calculation based on model infor- measurements available from PMUs. It is to be noted that the
mation is discussed in [21]. However, only measurement-based moment of inertia for the COI reference frame is equivalent to
solutions are generally preferred over model based solutions the actual electric power output for the COP-based reference
for real-time monitoring applications. Hence, the motivation frame for all practical reasons [23], [24]. This condition holds
of this article is to come up with a purely measurement-based good if generators are operated very close to their rated power
IDM scheme, which can be easily integrated into state-of-the-art and thankfully, for economic reasons, this is followed in actual
power system monitoring software solutions. practice [23]. Thus, the COP frequency reference of an n-bus
system can be defined as
C. Contribution n
i=1 Pi fgi
The research gap in the existing literature motivated us to work fCOP =  n (3)
i=1 Pi
on this problem statement. The contributions of this article are
as follows. where Pi is current power generation schedule of ith generator.
1) We proposed a method to estimate IDI based on measure- Now, the electrical distance of each bus to the COP location can
ments obtained from PMUs. be calculated by comparing the COP frequency to the frequency
2) The suggested scheme is validated on the largest regional of each bus following a small disturbance:
power grid of the Indian power system.  T +t0
3) The work is extended to see the impact of RES integration dk = (fbk (τ ) − fCOP (τ ))2 dτ (4)
on the power system inertia distribution. t0

4) The effect of IDI on small signal stability is analytically where t0 represents the instance at which disturbance is created,
established and the inferences drawn are validated through T is the window length, and fb is the bus frequency. The alphabet
time-domain simulation. k represents bus number. The IDI for each bus can be calculated
5) The impact of change in IDI on triggering thresholds by normalizing it to the highest index
used for oscillatory stability monitoring (OSM) is demon- dk
strated. IDIk = (5)
max dk
k{1,....N }
D. Organization where N is the total number of buses in the system. This index
The rest of this article is organized as follows. Section II represents the electrical distance of each bus from the COP. A
explains the proposed method for IDI calculation.The analytical low value of IDI indicates that the bus is near to COP and vice

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

K AND JENA: PRACTICAL APPROACH TO IDM AND IMPACT OF INERTIA DISTRIBUTION ON OBS FOR RENEWABLE PENETRATED POWER GRID 3

defined as the electrical distance from bus 1 to bus 3. Therefore,


it can be inferred that
0 ≤ αmin ≤ α ≤ αmax ≤ 1 (11)
 
where αmin = (Xd1
+ XT 1 )/X and αmax = (X − − Xd2
XT 2 )/X. The total reactance of the system is given by
 
Fig. 1. Single line diagram of two-machine system. X = Xd1 + XT 1 + Xd2 + XT 2 + XL . The electromechanical
eigenvalue of the above-mentioned system is represented by

ω s V 0 H1 + H2 E1 E2
versa. COP may not be located exactly on a particular bus. In λα = j . (12)
2X H1 H2 (1 − α)E1 + αE2
such cases, the nearest bus to COP is the one having lowest value
of IDI. V0 is the voltage at bus 3. The COI location of the system, α∗
The nearest bus to COP can be calculated as is given by
kmin = argmin dk . (6) E1 H2
α∗ = (13)
k{1,....N } E1 H2 + E2 H1
Similarly, the furthest location from COP can be calculated 1
as α∗ = E2 H1
. (14)
1+ E1 H2
kmax = argmax dk . (7)
k{1,....N } The above-mentioned expressions are reported in [19]. We
have extended this work further to find out the eigenvalue sensi-
It is to be noted that the power system is always prone to small tivity. Eigenvalue sensitivity is a measure of how certain factors
disturbances. Thus, (4) can be further extended for real-time IDI are influencing small-signal stability of the system under study.
calculation. In that case COP at each instant can be calculated This analysis can be carried out for improving the small-signal
using the following: stability as well as to study the impact of change in parameters
n on small-signal stability. In this particular work, eigenvalue
i=1 Pi (t)fi (t)
fCOP (t) =  n . (8) sensitivity analysis is carried out to investigate the influence of
i=1 Pi (t)
change in inertia at different locations on interarea oscillation. In
Instead of scheduled power, real-time active power measure- effect, we are exploring the impact of IDI on interarea oscillation.
ments from each generator are used for the above-mentioned Sensitivity with respect to the IDI is given by
calculation. The distance of each bus from COP location is given
∂λα j ωs V0 H1 + H2 E1 E2 (E1 − E2 )
by the following: = (15)
 t ∂α 2β 2X H1 H2 [(1 − α)E1 + αE2 ]2

dk (t) = (fbk (τ ) − fCOP (τ ))2 dτ (9) ωs V0 H1 + H2 E1 E2
t−t β= . (16)
2X H1 H2 (1 − α)E1 + αE2
where t is the instance at which the calculation is carried out and
t is the window length considered for calculation. IDI equation Further simplifying the above-mentioned equation
will be further modified as given in the following: 
∂λα j  ω s V 0 H1 + H2 E1 E2
dk (t) = (E1 − E2 ) .
IDIk (t) = . (10) ∂α 2 2X H1 H2 [(1 − α)E1 + αE2 ]3
max dk (t) (17)
k{1,....n}
Now consider a large system with many generators and in-
III. EFFECT OF IDI ON EIGENVALUE SENSITIVITY terconnected transmission lines. It can be reduced to a system
having two areas: one area having higher inertia and the other
In an actual multimachine power system, multiple electrome- area having lower inertia. Therefore, H1 is much higher than H2 .
chanical oscillatory modes are expected. However, in reality The two areas are separated by a large distance. The eigenvalue
there will a few critical modes, which are of interest to the system sensitivity is analyzed at two different locations in the system.
operator. Thus, the complexity in analysis is greatly reduced by The first one is at the COI location and the second one is at
focussing on those few critical interarea modes of the system. In low inertia area. Since H1 is much higher compared to H2 the
this section, an attempt to analyze the impact of change in IDI COI location will be close to bus 1, and hence, the term H2 is
on mode characteristics is carried out. neglected in (14). The modified equation for COI will become
Two machine model, as shown in Fig. 1, is used for the
E1
calculation of COI location and eigenvalue sensitivity analysis. α∗ = (18)
The SG and synchronous motor connected to bus 1 and bus 5 E1 + E2 H1
are represented by the classical model. E  is the terminal voltage 1

and Xd is the d-axis transient reactance of both the machines. A = E2 H1
. (19)
1+ E1
general bus (bus 3) is represented for referencing purposes. α is

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

4 IEEE SYSTEMS JOURNAL

Fig. 2. Single line diagram of NRPG system corresponding to case I grouping.

Eigenvalue sensitivity at the COI location is derived and is The system has a total generating capacity of 26652.1 MVA. The
given by topology single line diagram of the base case system is shown
 in Fig. 2. The test system is modeled using dynamic security
 E1 E2
∂λα j    ω s V 0 H1 + H2 assessment tool (DSA tools) power system simulator [26]. The
|α=α∗ = (E1 − E2 )   .
∂α 2 2X H1 H2 E2 H1 +E1 H2 3 IDI index is obtained for the NRPG system considering different
E1 +E2 H1
test scenarios as detailed in the following.
(20)
1) Case I: Base case scenario where all the generators are
The next location considered to find out eigenvalue sensitivity
synchronous machines.
is the farthest location from COI, which is at a distance of αmax
2) Case II: Generators at bus 1, 24, 36, and two of the three
from bus 1. This location is having low inertia. Considering the
generators at bus 38 are replaced with type IV wind turbine
distance between two areas, αmax can be approximated to 1.
generator (WTG). Second generation Western Electricity
Therefore the eigenvalue sensitivity at this location becomes
 Coordinating Council (WECC) models are used to repre-
∂λα j  ωs V0 H1 + H2 E1 E2 sent WTG. In this case, the group 1 generators of case I

|α=αmax = (E1 − E2 ) . (21) scenario are replaced with type IV WTG.
∂α 2 2X H1 H2 (E2 )3
3) Case III: Generators at bus 19, 20, 21, and 37 are replaced
Comparing both (20) and (21), the authors could infer that with type IV WTG. In this case, SG in group 6 of case I
sensitivity is high at the region having higher IDI compared to the is replaced by type IV WTG.
region having lower IDI. The simulation results demonstrated Initially, the IDI is obtained for case I and the geographical
in Section V validate the above-mentioned conclusion. representation of the groups of NRPG system based on proposed
COP-based IDI is shown in Fig. 3. The system is divided into
IV. CASE STUDY USING TEST SYSTEM DATA six groups based on IDI. It is to be noted that buses belonging to
group 1 are the ones with the least IDI. That means these buses
A. Evaluation on Indian Power Systems are closest to the COI location. On the other hand, buses that are
The suggested COP-based IDI scheme is validated on the part of group 6 are the ones with the highest IDI. That means
Northern Regional Power Grid (NRPG) of the Indian power this is the farthest region from the COI. Group 6 covers the state
system. It is the largest among all regional power grids and of Rajasthan and it is the least meshed group whereas group
consists of 246 buses, 376 lines, and 43 exciters. The network 1 is the most meshed group of the NRPG system. Similarly,
and dynamic data of the NRPG system can be referred from [25]. the IDI is obtained for case II scenario of the NRPG system

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

K AND JENA: PRACTICAL APPROACH TO IDM AND IMPACT OF INERTIA DISTRIBUTION ON OBS FOR RENEWABLE PENETRATED POWER GRID 5

Fig. 3. Geographical representation of groups of NRPG system based on IDI Fig. 5. Geographical representation of groups of NRPG system based on IDI
index with all synchronous machines (case I). index with type IV WTG models at group 6 of basecase (case III).

Fig. 6. Frequency deviation at bus 1 following a generation loss contingency.

Fig. 4. Geographical representation of groups of NRPG system based on IDI the frequency deviation at bus 1. Readers may note that bus
index with type IV WTG models at group 1 of basecase (case II). 1 belongs to group 1, group 2, and group 4 for case I, case
II, and case III test scenarios, respectively. That means bus 1
is the bus closest (group 1) to the COI location as far as case
and the geographical representation of different groups of the I is concerned. However, the distance of bus 1 from the COI
NRPG system is shown in Fig. 4. Fig. 5 shows the geographical location is increased if we move from case I to case II and case
representation of the groups in NRPG system for case III. The III. Thus, it is expected that bus 1 frequency deviation following
COI location as well as the groups have changed in both cases. a particular contingency will be more in case III compared to
Readers may visualize the impact of RES penetration on IDI. We the frequency deviation obtained in case I and case II. Fig. 6
notice that the generation mix does affect the IDI and real-time confirms the above-mentioned observation. Further, deviation
information of IDI will assist the system operator in real-time in the frequency and phase angle observed at a bus following a
operation of the power system. A plot of frequency deviation contingency depends on its IDI. The bus frequency and phase
at bus 1 following a generator tripping contingency is shown in angle deviation is minimum for buses closest to the COI and it
Fig. 6. All three test scenarios are considered while monitoring will be maximum for buses farthest from the COI. To verify this,

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

6 IEEE SYSTEMS JOURNAL

Fig. 9. Real-time monitoring framework.

Fig. 7. Frequency deviation for case I.

Fig. 10. Real-time IDI calculated at bus 159.

conditions and it results in variation of IDI. Therefore, IDI is to


be considered as a time-varying quantity. Real-time monitoring
Fig. 8. Frequency deviation for case II.
of IDI will provide the operator with better information of inertia
available at each instant. It, therefore, helps for scheduling gen-
eration more efficiently with minimal risk of cascaded tripping.
Thus, we have extended the work by introducing Algorithm 1
a generation loss contingency is created for both case I and case
for real-time IDI monitoring. For this calculation active power,
II scenarios of the NRPG system using the Transient Security
generator frequency, and bus frequency are taken into consider-
Assessment Tool module of the DSA tools. The frequency
ation. The objective of this downstream application is to enable
deviation is monitored at bus 36 (group 1) and bus 19 (group
the operator to monitor the real-time trend of IDI at any bus
6) of the NRPG system, as shown in Figs. 7 and 8. It is observed
of interest. The framework for real-time monitoring of IDI is
that bus 36 is having least frequency deviation following the
shown in Fig. 9. PMUs will stream the required measurements
contingency as compared to bus 19 and these results validate the
to control room where the IDI monitoring algorithm is executed.
IDI obtained for the NRPG system using the proposed technique.
A moving window is shifted by one sample after each iteration.
The objective is to provide the real-time trend of IDI along with
B. Real-Time IDI Monitoring information on COP location and group formulation based on
Power system inertial response resist change in frequency IDI. A test case is considered for demonstration purposes. The
following any contingency and provides time for other control reference power setting of the renewable generator at bus 24
systems to respond in case of supply and demand imbalance. is increased at 180 s. The variation in IDI at bus 159 is shown
The stored kinetic energy of the SG contributes toward inertial in Fig. 10. Bus 159 is located at group 1, which is the nearest
response. Thus, at a given instant of time, the amount of inertial group to COP. For normal operating conditions, the IDI of this
response available for a power system is primarily dependant on bus is close to zero. When the renewable generation increases,
the number of synchronous machines, which are operational. the active power supplied by the SG reduces automatically to
However, during real-time operation, the power contribution maintain generation-load balance. There will be a shift in COP
from conventional SG-based resources may vary with system to the area where more SG are located. Therefore, the IDI at bus

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

K AND JENA: PRACTICAL APPROACH TO IDM AND IMPACT OF INERTIA DISTRIBUTION ON OBS FOR RENEWABLE PENETRATED POWER GRID 7

Algorithm 1: Real-Time IDI Calculation.


1: Input: Generator active power, generator frequency,
bus frequency.
2: Calculate COP of the samples in the selected window
using (8).
3: Compute the distance of each bus from COP using (9).
4: Compute IDI by dividing with maximum distance
using (10).
5: Output: IDI of all buses.
6: Update the window by removing last sample and add
next sample.
7: Repeat steps 3 to 6. Fig. 11. Histogram plot for NRPG system.

159 will increase. After contingency, the SG are slowly picking for the mode frequencies. OBS is part of most of the offline
up to their scheduled generation, which results in the reduction engineering analysis software solutions, such as phasoranalytics
of IDI at bus 159. from general electric (GE) [30]. Most of the utilities opt for OBS
every 4–5 years in order to set reliable triggering thresholds for
C. Impact of Noise and Data Loss the oscillatory modes. With high penetration of RES oscillatory
The presence of noise and loss of data for a particular time modes of the system may vary depending upon the percentage
period may affect the calculation of IDI. These two cases are generation as well as the location of RES. Predefined triggering
discussed in this section as follows. threshold cannot guarantee reliable operation in such cases.
1) Impact of Noise: It is observed that PMU measurements Therefore, an attempt has been made to analyze the impact of
corresponding to transmission systems are found to be Gaus- IDI on OBS. The following steps are followed in the OBS [31].
sian with mean zero and signal-to-noise ratio (SNR) of around 1) Step 1: Reviewing long term oscillations.
45 dB [27]. Thus, authors have included white Gaussian noise 2) Step 2: Identify subbands.
of SNR = 45 dB to the measurements utilized for the com- 3) Step 3: Threshold selection using statistical results.
putation of IDI. It is observed that presence of noise affects In the first step, long-term oscillations are analyzed using
the IDI-based grouping of buses. However, the grouping of months of historian data. The outcome of the first step is a
buses is least affected if a wavelet transform-based denoising histogram plot, which details the modes of oscillation present in
function is embedded within the IDI monitoring algorithm. It a power system and the number of occurrences of such modes.
is to be noted that such denoising functions are part of data Fig. 11 shows a typical example of histogram plot for the NRPG
preprocessing module of most of the available power system system. Considering 0.76 Hz critical oscillatory mode a subband
monitoring software solutions [28]. with a lower cutoff frequency of 0.75 Hz and a higher cutoff
2) Impact of Data Loss: IDI cannot be accurately calculated frequency of 0.77 Hz is selected based on histogram results.
in case of data loss. Therefore, an algorithm to check data loss Usually “Alert” and “Alarm” thresholds are subband specific.
has to be incorporated to this method. For a window length, However, the current study investigated the impact of change in
a minimum number of data points should be specified in the IDI on the mode frequency and its damping and it is observed
following, which the IDI monitoring algorithm will not be that change of IDI may result in shifting of oscillatory modes
processed [6], [29]. from one subband to another. In that case, the “Alert” and
Some of the WAMS-based monitoring softwares, such as GE “Alarm” thresholds need to be updated. In order to demonstrate
phasorpoint [6] have algorithm to check the packet loss of data. the impact of IDI on the OBS, small-signal stability analysis
Even though this algorithm is not included in this manuscript, it is performed on the test system including all the test scenarios,
can be incorporated when the algorithm is implemented in the as detailed in the previous section. The small-signal stability
actual system. study on the base case provided information related to the most
critical interarea oscillatory mode of the NRPG system. This
interarea oscillatory mode is having a frequency of oscillation
D. Impact on OBS
of 0.71 Hz with 4.52% damping. When small signal-stability
OSM is one of the most popular control room use cases where analysis is performed on test case II and test case III, the impact
PMU measurements are utilized in real time to access oscillatory of RES penetration is clearly observed on both the frequency of
stability of the system [6]. OSM application needs triggering oscillation and damping ratio of the critical oscillatory mode of
thresholds to provide “Alert” and “Alarm” signals to the operator. the system. Readers may visualize the relative impact of change
The triggering thresholds should detect any high-energy poorly in IDI on the mode frequency and its corresponding damping.
damped oscillation and at the same time, they should avoid When generators placed near COI are replaced with WTG, it
providing false alarms to the operator. To achieve this target, results in a slight increase of mode frequency and its corre-
OBS is performed to find out reliable triggering thresholds sponding damping of the critical oscillatory mode. However,

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

8 IEEE SYSTEMS JOURNAL

TABLE I TABLE III


SMALL SIGNAL STABILITY ANALYSIS RESULTS FOR CASE I, CASE II, AND COMPARISON OF THE PROPOSED WORK WITH RELATED WORKS
CASE III

TABLE II
PRONY ANALYSIS RESULT FOR CASE I, CASE II, AND CASE III

when generators of group 6 are replaced with WTG, it results


in a decrease in both oscillation frequency and damping of the
critical oscillatory mode. The results are depicted in Table I.
The results from the simulation are in arrangement with the
analysis done using derived (20) and (21). The relative change
in magnitude is high in case III compared to case II.
We extended this analysis further by initiating a load shedding
contingency at bus 40 of the NRPG system and prony analysis is
been made to explore the impact of change in IDI on OBS for
performed on the postcontingency signal to observe the impact
the first time in this manuscript.
of change in IDI on the critical oscillatory mode. The results of
prony analysis are detailed in Table II. In this case too the ob-
servations are similar to those of small signal stability analysis. V. SALIENT FEATURES OF THE PROPOSED METHOD
Usually, operators go for OBS every 4–5 years. However, this The unique features of the proposed method for IDI monitor-
study demonstrates that the triggering thresholds for OSM need ing are mentioned in the following.
to be updated in near real-time depending on the generation mix 1) The proposed method of IDI calculation is based on COP
of a particular power system. reference and hence is dependent only on PMU measure-
ments.
E. Qualitative Comparison With Other Related Works 2) The impact of inertia distribution on OBS is explored,
and the inferences drawn are verified using analytical
A qualitative comparison is carried out with the existing
equations, time-domain simulations as well as small sig-
schemes for IDI calculation and the suggested scheme. The
nal stability analysis. To the best of our knowledge, this
comparison result is shown in Table III. Four parameters are
relationship is explored for the first time in literature.
taken into consideration as follows.
3) We proposed a method for real-time IDI monitoring. The
1) Data inputs considered.
suggested method is highly suitable for online applications
2) Dependency on state variables/inertia.
as the calculation depends only on PMU measurements.
3) Model based/ measurement based.
4) The scheme proposed in this article can be integrated into
4) Suitability for online application.
existing state-of-the-art software solutions, such as GE
For the existing schemes as well as the proposed scheme, the
phasorpoint [30] and RTDMS [34].
number of inputs involved in the calculation is three. It means
that the proposed scheme does not require any extra inputs. It
is to be highlighted that the proposed scheme uses active power VI. CONCLUSION
as one of the inputs instead of inertia, which is used in existing The concept of COP-based IDI is proposed. The suggested
schemes, such as [19], [32], [33]. In [21], a model-based method IDI monitoring scheme uses PMU measurements. The IDI is
is used for IDI calculation, which needs generator state variables evaluated on NRPG system of India and the impact of different
as inputs. The active power measurements from PMUs are easily penetration of RES on IDI is explored. Time-domain simulation
available in the control room whereas real-time inertia data or is performed to validate the results obtained through suggested
the generator state variables are usually not reported by PMUs. COP-based IDI monitoring scheme. Furthermore, the impact
For this reason, the proposed scheme is highly suitable for online of change in IDI on the OBS is explored and it is concluded
applications compared to other schemes. that in the future power system operators may need to update
Further, the analytical expressions for the eigenvalue sensitiv- the triggering thresholds for OSM in near real time. Further, a
ity with respect to IDI is explored and verified with the full-order technique to monitor COP and IDI in real time is also proposed.
phasor-domain simulations and modal analysis carried out on The suggested IDI monitoring scheme can be integrated into
the NRPG system. To the best of our knowledge, an attempt has state-of-the-art control room software solutions. The future work

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

K AND JENA: PRACTICAL APPROACH TO IDM AND IMPACT OF INERTIA DISTRIBUTION ON OBS FOR RENEWABLE PENETRATED POWER GRID 9

will focus on the development of a day ahead IDI forecasting [21] D. Brahma and N. Senroy, “Sensitivity-based approach for assessment
scheme. Further, an extensive study considering the synthetic of dynamic locational grid flexibility,” IEEE Trans. Power Syst., vol. 35,
no. 5, pp. 3470–3480, Sep. 2020.
inertia of renewable generators and inertia contribution from [22] S. You et al., “Calculate center-of-inertia frequency and system RoCoF
loads will be carried out in future. using PMU data,” in Proc. IEEE Power Energy Soc. Gen. Meeting, 2021,
pp. 1–5.
[23] M. K. Jena and B. Panigrahi, “Dynamic stress assessment in power
REFERENCES transmission network to support wide area early warning system,” in Proc.
14th IEEE India Council Int. Conf., 2017, pp. 1–6.
[1] M. Dreidy, H. Mokhlis, and S. Mekhilef, “Inertia response and frequency
[24] H. Suprême, L.-A. Dessaint, I. Kamwa, and A. Heniche-Oussédik, “De-
control techniques for renewable energy sources: A review,” Renewable
velopment of new predictors based on the concept of center of power
Sustain. Energy Rev., vol. 69, pp. 144–155, 2017. [Online]. Available:
for transient and dynamic instability detection,” IEEE Trans. Smart Grid,
https://www.sciencedirect.com/science/article/pii/S1364032116309212
vol. 9, no. 4, pp. 3605–3615, Jul. 2018.
[2] K. Gayathri, M. K. Jena, and A. K. Moharana, “Impact of different
[25] 246 bus northern regional power grid data, 2015. [Online]. Available:
penetration level of type-IV renewable energy resources on power system
https://www.iitk.ac.in/eeold/facilities/Research_labs/Power_System/
dynamics,” in Proc. 9th IEEE Int. Conf. Power Syst., 2021, pp. 1–6.
NRPG-DATA.pdf
[3] E. S. N. R. Paidi, H. Marzooghi, J. Yu, and V. Terzija, “Development and
[26] DSA Tools User Manual, Ver. 19.0, Powertech Labs, Inc., Canada, 2011.
validation of artificial neural network-based tools for forecasting of power
[27] S. Brahma, R. Kavasseri, H. Cao, N. R. Chaudhuri, T. Alexopoulos, and Y.
system inertia with wind farms penetration,” IEEE Syst. J., vol. 14, no. 4,
Cui, “Real-time identification of dynamic events in power systems using
pp. 4978–4989, Dec. 2020.
PMU data, and potential applications–models, promises, and challenges,”
[4] ‘Sonar of the power grid’: New inertia measurement tools planned
IEEE Trans. Power Del., vol. 32, no. 1, pp. 294–301, Feb. 2017.
for Great Britain’s electricity system, 2020. [Online]. Available:
[28] P. Shaw and M. K. Jena, “A novel event detection and classification
https://www.nationalgrideso.com/news/sonar-power-grid-new-inertia-
scheme using wide-area frequency measurements,” IEEE Trans. Smart
measurement-tools-planned-great-britains//-electricity-system
Grid, vol. 12, no. 3, pp. 2320–2330, May 2021.
[5] D. Yang et al., “Data-driven estimation of inertia for multiarea intercon-
[29] A. Anshuman, B. K. Panigrahi, and M. K. Jena, “Enhanced visualization
nected power systems using dynamic mode decomposition,” IEEE Trans.
and characterization of low frequency oscillations in power system,” IEEE
Ind. Informat., vol. 17, no. 4, pp. 2686–2695, Apr. 2021.
Syst. J., early access, doi: 10.1109/JSYST.2022.3169491.
[6] Wide area monitoring system applications, 2019. [Online]. Available:
[30] Phasoranalytics-engineering analysis package for post-operation and plan-
https://www.ge.com/digital/sites/default/files/download_assets/wide-
ning, 2019. [Online]. Available: https://www.ge.com/digital/applications/
area-monitoring-system-phasorpoint-applications-from-ge-digital.pdf
transmission/phasoranalytics
[7] A. Agarwal, J. Balance, B. Bhargava, J. Dyer, K. Martin, and J. Mo, “Real
[31] Oscillation source location and long term dynamic performance baselining
time dynamics monitoring system (RTDMS) for use with SynchroPhasor
study using ISO-NE’s synchrophasor data, 2015. [Online]. Available:
technology in power systems,” in Proc. IEEE Power Energy Soc. Gen.
https://www.naspi.org/sites/default/files/2016-09/isone_zhang_oscilla
Meeting, 2011, pp. 1–8.
tion_source_location_20150324.pdf
[8] K. Tuttelberg, J. Kilter, D. Wilson, and K. Uhlen, “Estimation of power
[32] Y. Xiao, X. Lin, and Y. Wen, “A framework for assessing the inertia
system inertia from ambient wide area measurements,” IEEE Trans. Power
distribution of power systems,” in Proc. IEEE 3rd Conf. Energy Internet
Syst., vol. 33, no. 6, pp. 7249–7257, Nov. 2018.
Energy Syst. Integration, 2019, pp. 1418–1423.
[9] D. P. Chassin, Z. Huang, M. K. Donnelly, C. Hassler, E. Ramirez, and
[33] Y. Wang, H. Silva-Saravia, and H. Pulgar-Painemal, “Estimating inertia
C. Ray, “Estimation of WECC system inertia using observed frequency
distribution to enhance power system dynamics,” in Proc. North Amer.
transients,” IEEE Trans. Power Syst., vol. 20, no. 2, pp. 1190–1192,
Power Symp., 2017, pp. 1–6.
May 2005.
[34] M. Parashar and J. Mo, “Real time dynamics monitoring system (RTDMS):
[10] M. Sun, Y. Feng, P. Wall, S. Azizi, J. Yu, and V. Terzija, “On-line power
Phasor applications for the control room,” in Proc. 42nd Hawaii Int. Conf.
system inertia calculation using wide area measurements,” Int. J. Elect.
Syst. Sci., 2009, pp. 1–11.
Power Energy Syst., vol. 109, pp. 325–331, 2019. [Online]. Available:
https://www.sciencedirect.com/science/article/pii/S0142061518336640
[11] P. M. Ashton, C. S. Saunders, G. A. Taylor, A. M. Carter, and M. E.
Bradley, “Inertia estimation of the GB power system using synchrophasor
measurements,” IEEE Trans. Power Syst., vol. 30, no. 2, pp. 701–709, Gayathri K (Student Member, IEEE) received the
Mar. 2015. B.Tech. degree in electrical and electronics engineer-
[12] D. Zografos and M. Ghandhari, “Power system inertia estimation by ing from Government Engineering College, Thrissur,
approaching load power change after a disturbance,” in Proc. IEEE Power India, in 2018. She is currently working toward the
Energy Soc. Gen. Meeting, 2017, pp. 1–5. Ph.D. degree in electrical engineering from the Indian
[13] J. Zhang and H. Xu, “Online identification of power system equivalent in- Institute of Technology Palakkad, Palakkad, India.
ertia constant,” IEEE Trans. Ind. Electron., vol. 64, no. 10, pp. 8098–8107, Her research interests include power system dy-
Oct. 2017. namics and power system monitoring.
[14] D. Yang et al., “Ambient-data-driven modal-identification-based approach
to estimate the inertia of an interconnected power system,” IEEE Access,
vol. 8, pp. 118799–118807, 2020.
[15] L. Fan, Z. Miao, and Y. Wehbe, “Application of dynamic state and
parameter estimation techniques on real-world data,” IEEE Trans. Smart Manas Kumar Jena (Senior Member, IEEE) re-
Grid, vol. 4, no. 2, pp. 1133–1141, Jun. 2013. ceived the Ph.D. degree in power systems engineering
[16] M. Liu, J. Chen, and F. Milano, “On-line inertia estimation for synchronous from the Indian Institute of Technology Delhi, New,
and non-synchronous devices,” IEEE Trans. Power Syst., vol. 36, no. 3, Delhi, India, in 2018.
pp. 2693–2701, May 2021. He is currently an Assistant Professor with the
[17] Y. Cui, S. You, and Y. Liu, “Ambient synchrophasor measurement based department of Electrical Engineering, Indian Institute
system inertia estimation,” in Proc. IEEE Power Energy Soc. Gen. Meeting, of Technology Palakkad, Palakkad, India. Prior to
2020, pp. 1–5. joining IIT Palakkad, he was a Subject Matter Expert
[18] J. Zhao, Y. Tang, and V. Terzija, “Robust online estimation of power with GE-Power. His research interests include wide
system center of inertia frequency,” IEEE Trans. Power Syst., vol. 34, area monitoring system, wide area protection, im-
no. 1, pp. 821–825, Jan. 2019. proving wide area situational awareness using PMU
[19] H. Pulgar-Painemal, Y. Wang, and H. Silva-Saravia, “On inertia distri- information, application of signal processing, and data-mining in power systems.
bution, inter-area oscillations and location of electronically-interfaced re- Dr. Jena was a recipient of the Indian National Academy of Engineers (INAE)
sources,” IEEE Trans. Power Syst., vol. 33, no. 1, pp. 995–1003, Jan. 2018. Innovative Student Projects Award 2018—Doctoral Level, POSOCO Power
[20] M. Tuo and X. Li, “Dynamic estimation of power system inertia distri- System Award (PPSA)-2019, and GE-Impact Award-2019 for the development
bution using synchrophasor measurements,” in Proc. 52nd North Amer. and delivery of PhasorAnalytics Software Solution to ONS-Brazil, and Indian
Power Symp., 2020, pp. 1–6. National Academy of Engineers (INAE) Young Engineer Award 2021.

Authorized licensed use limited to: National Institute of Technology. Downloaded on December 26,2022 at 11:06:55 UTC from IEEE Xplore. Restrictions apply.

You might also like