You are on page 1of 12

A P P L I C AT I O N N OT E 3 .0

Cables
Overvoltage protection
The APPLICATION NOTES (AN) are intended to be used in
conjunction with the

APPLICATION GUIDELINES
Overvoltage protection
Metal-oxide surge arresters in medium-voltage systems.

Each APPLICATION NOTE gives in a concentrated form


additional and more detailed information for the selection
and application of MO surge arresters in general or for a
specific equipment.

First published March 2020


3
O V E R V O LTA G E P R OT E C T I O N


Overvoltage protection of cables
Disruptive breakdowns in cable insulation lead to grave damages
and require expensive repairs. Flashovers along cable bushings
can damage them and lead to the same consequences as an insulation
breakdown. Further, repeated overvoltages influence negatively
the ageing behavior of the cable insulation. Therefore, cables must be
protected like all other electrical equipment.

1 Introduction A single lightning or switching overvoltage will not


lead to a breakdown of the insulation of a new ca-
Environmental influences and the requirements ble. But aged and pre-damaged insulations may
imposed by the licensing authorities are breakdown suddenly under a single event. Cable
making it necessary to install medium-voltage bushings are endangered by overvoltages ­generally.
distribution systems with more and more cables,
even in sparsely populated areas. Examples are, 2 Overvoltages in cables and cable systems
besides urban areas, on-shore and off-shore
wind power parks. This poses the question which 2.1 Overvoltages due to lightning
overvoltages can occur in such systems and how On overhead lines lightning overvoltages are
to protect the equipment of such distribution ­usually limited to the sparkover voltage of the line
systems against overvoltages. insulators, assuming a few insulators between
the point of strike and the cable bushing. It must
Cables have a relatively high self-capacitance. consequently be assumed that the peak value of
For this reason, it is sometimes assumed the overvoltage wave travelling in the direction of
that a cable can protect itself against overvolt- the cable is equal to the sparkover voltage of
ages. This is not correct, cables must be the line insulator. Assuming a flashover distance
protected like all other electrical equipment of 50 cm of a line insulator (e. g. in a 24 kV-system
against ­overvoltages. and poles with earthed cross arms) a flashover
voltage of 300 kV to 350 kV can be expected at
Whereas in medium-voltage distribution systems least, depending on the steepness of the incom-
with a major proportion of overhead lines the ing overvoltage. In case of wooden poles the
lightning overvoltages govern the protection flashover distance is given by the height of the
concepts and the stresses in the surge arresters, pole, and consequently the flashover voltage will
in systems with a high proportion of underground be much higher.
cables the switching overvoltages are the domi-
nant phenomenon. 2.2 Overvoltages due to switching
Switching overvoltages are slow front overvolt-
Two aspects must be considered: insulation ages per definition and occur as transient phe-
breakdown and ageing of the insulation. It is well nomena during every change in the system condi-
known that repeated overvoltage stresses tions. If a current circuit is opened or closed
(steepness and magnitude) negatively influence the transition takes place in form of an oscillation.
the ageing behavior of the cable insulation, The frequency and duration of such an overvolt-
which means that the service life of the cable is age oscillation is highly dependent on the system
shortened. parameters. A rise time of a few 10 to a few 100 µs
is to be anticipated. The time to half value can
Considering the effect of aging of the insulation be up to some ms. For insulation withstand tests
and the voltage increase at reflection points, the a voltage waveshape of 250/2500 µs is used in
stresses due to switching transients may reach the switching impulse withstand test. However,
the dielectric strength levels of the equipment switching operations of vacuum breakers can
and network components used in the system. ­produce very steep overvoltages.
4 A P P L I C AT I O N N O T E C A B L E S

The amplitudes can reach up to 4 p.u in unfavor- For overhead lines in medium-voltage distribu-
able constellations. tion systems the surge impedance lies in
the range of ZL = 450 Ω to 500 Ω and for cables
Notable switching overvoltages occur especially ­between ZK = 30 Ω and 60 Ω.
in systems with isolated or arc suppression
­neutral as a result of With the help of Figure 1 travelling waves in cables
• Switching on cables and overhead lines, can be explained. In the simplified arrangement
and of complete networks of an overhead line and a cable section the over-
• Disconnection of cables with re-striking head line has a surge impedance of ZL = 450 Ω
• Initiation of ground faults and the cable ZK = 30 Ω, see Figure 1a. A step
• Clearing of system faults by corresponding voltage U travels along the overhead line at a ve-
­c ircuit breakers locity of 300 m/µs in the direction of the c ­ able,
Figure 1b. The travel velocity in the cable is
3 Overvoltage waves in cables ­assumed to be 150 m/µs. At the transition over-
head line/cable reflections and transmissions
Overvoltage waves in cables and cable systems ­occur due to the change in the surge impedances.
are generally treated with the travelling wave A part of the incoming wave is transmitted into
­theory. One essential difference between the cable, the larger part is reflected.
the electrical data of overhead lines and cables is
the surge impedance Z of their conductors to The reflected and transmitted parts of the volt-
earth. age impulse can be calculated with the reflection
factor ru and the transmission factor bu.
The surge impedance is given by the equation Both factors depend on the surge impedances of
Z =  L’ /  C’. the overhead line ZL and the cable ZK .
2 × ZK
L’ is the inductance per unit length in H/km and C’ bu = ---------
is the capacitance per unit length in F/km. ZL + ZK
The travelling speed is given to ZK – ZL
v = 1 /  L’ × C’. ru = ---------
ZL + ZK


Figure 1: Reflections of X1 X2
a travelling wave
(square wave) with
ZL ZK ZL
the ­amplitude U
at the transition a)
­overhead line/cable.

v
U

b)
x

c)
x

d) U
x
O V E R V O LTA G E P R OT E C T I O N 5

With the given surge impedances, a transmission It follows, that in the case of a cable installed
factor bu = 0.125 and a reflection factor in the path of an overhead line, say for passing
ru = –0.875 results for the junction (X1) from the ­beneath a highway, the maximum value of
overhead line to the cable. the voltage u(t) in the cable is U. This means that
the wave behind the cable is also just as high
This means a voltage wave travels through the as the incoming wave.
­cable with the amplitude of U/8 and is positively
reflected at the end of the cable (X2), travelling In case of an open circuit breaker or a transformer
back to the entry point of the cable, Figure 1c. at the end of the cable, see Figure 3, the time
There the v ­ oltage is again positively reflected, ­constant is given to
Figure 1d. It is easy to realize how this wave, ZL × LK
­travelling back and forth in the cable, builds the τ = ---------
voltage s­ tep-wise up to the end value. ZK × vK
If the cable is terminated with an open circuit
3.1 Time curve of the voltage in the cable breaker or a transformer the voltage will reach
a maximum of two times the incoming voltage.
In Figure 1 the voltage reflections at the begin- The time constant will be τ = 10 µs.
ning and at the end of the cable are explained.
In Figure 2 the time curve of the voltage in a cable The increase of the voltage in the cable, as shown
with an assumed length of LK = 100 m is shown. in Figures 2 and 3, follows exactly the time
The time curve of this voltage buildup follows ­function of a capacitor that is charged with
the time function 1 – e –t/τ as shown in the exam- a DC step voltage. This is logic, because a cable
ples of Figure 2 and Figure 3. The time constant can be ­considered to be a long coaxial capacitor.
is given by the equation
ZL × LK
τ = -------------
2 × ZK × v K
LK cable length
vK travelling speed in the cable

For a cable length of LK = 100 m the time constant


results to τ = 5 µs.

— —
Figure 2: Time Figure 3: Same as
­characteristic of Figure 2, but with
the voltage in the cable an open circuit
on the occurrence of breaker at the end
a square wave. of the cable.

L K = 100 m

L K = 100 m
τ = 10 μs

τ = 5 μs
2u
U U U

t t
6 A P P L I C AT I O N N O T E C A B L E S

4 Protection of cables Cables longer than about 1000 m need a surge


­arrester only on the side of the incoming overvolt-
For cables, the reflection of the transient voltage age. In the Annex an example illustrates the
wave at the end of the cable represents a high risk ­calculation of the critical length LK* for a cable,
and may cause flashovers at the bushings with which may need protection on both sides.
subsequent damages to the cable insulation as
well. This risk can only be reduced by the applica- The specified values are valid for cable sections
tion of surge arresters at the cable ends. Therefore, with constant surge impedance. Otherwise,
cables should be treated like substation equipment the voltage reflections produce a shortening of
with respect to insulation coordination. the cable length LK . This is the case, for instance,
with cable branches or if two cables are c ­ onnected
If protection on one side of the cable or on both is with a single one.
needed, depends on the cable length, and if the
cable is endangered by overvoltages on one side A cable that connects an overhead line with
or on both sides. a substation is often only endangered by lightning
on the side of the overhead line. Therefore,
Depending on the system voltage Us and the type the arrester must be installed at the junction
of the poles (wooden or with earthed cross arms) ­between the overhead line and the cable. It is
of the overhead line, cables longer than some not necessary to protect the other end of
­meters up to some tens of meters need arresters the cable if the length LK of the cable does not
on both sides. See Table 1 for details. Note that exceed the values given in Table 1. See also
the figures in Table 1 are based on general Application Note 2.1 Transformers connected via
­assumptions for a typical case. Other assump- a cable.
tions lead naturally to different figures. Especially
the steepness of the incoming overvoltage, the The arresters are to be placed directly next to the
surge impedance Z and the arrester characteris- cable ends. The connection leads should be as
tic influence the calculated length of the cable. short and strait as possible. The earth connection
However, as a rule of thumb the figures in Table 1 of the arrester must be connected directly to the
can be used. cable sheath.


Table 1: The maximum admissible length LK of a cable if the arrester protection is only on one side. The cable
is connected to a lightning endangered line. The connection length between the arrester and the cable should be
at most 1 m. The numerical values are valid for an arrester with Upl = 4 p.u. and In = 10 kA (arrester class SL).

LK LK
U U

Type of overhead line Wooden poles Earthed cross arm Wooden poles Earthed cross arm
Us in kV ZK in Ω LK in m LK in m LK in m LK in m
3.6 30 ∞ ∞ 8 19
60 ∞ ∞ 4 13
7.2 30 85 110 11 27
60 75 100 5 17
12 30 45 50 8 22
60 33 39 4 16
17.5 30 35 36 6 19
60 27 30 3 15
24 30 34 36 9 21
60 27 30 4 17
36 30 30 30 7 19
60 24 26 4 17
O V E R V O LTA G E P R OT E C T I O N 7

At a first glance, LK is unlimited in 3.6 kV systems. Supplied information


The reason is that the LIWV is relatively high at • System with earth fault compensation
this system level. Even the reflected overvoltage (­Petersen coil), fault duration ≤ 30 min
at the end of the cable lies under the LIWV, so that • Overvoltage protection in a cable system.
the insulation is not in danger. This, however, is • System voltage Us = 24 kV
not valid for the equipment inside the substation.
The equipment can be endangered by additional Without other specifications it is assumed
voltage reflections, so that arresters should be • Um = 24 kV
planned if necessary. • LIWV = 125 kV (see Application Note 1.1 or
IEC 60071-1)
The protection of the cable ends and substations • Duration of the earth fault = 30 min
against overvoltages can be improved by applying • Nominal discharge current In = 10 kA
shield wires along the last 3 to 4 spans of the • Arrester class SL (station low), provides
overhead line. For a better protection of the over- a ­favorable, i. e. a low protection level for a cable
head line low footing impedance for the last poles with high energy handling capability.
at the cable terminations are recommended. • Short circuit current of the system Is = 20 kA
See also Application Note 2.1 Transformers con- • Degree of pollution b (light)
nected via a cable. • Installation height below 1000 m

Damping effects in the cables are not considered Following the steps given in selection flow chart
in all the calculations made for the given Application Note 1.1 A1 it follows:
­examples.
Step a) Continuous operating voltage Uc
5 Selection of MO surge arresters The choice of the continuous operating voltage
for cable ­protection according to Application Note 1.2 is
Us
The MO surge arresters should be selected as Uc ≥ ----
­described in the Application Guidelines T
and the Application Notes 1.1 Selection of A surge arrester class SL was chosen, e. g. the
MO surge arresters. type MWK. T follows according TOV curve to
T = 1.19 (fault duration 1’800 s, with prior duty).
The example given below guides through the
principle of the selection process step by step. With 10% additional safety margin for Uc,
Other system configurations are possible and this ­results in:
have to be considered from case to case. Uc = 24 kV / 1.19 × 1.1 = 22.18 kV.

Depending on the expected stresses, electrical According data sheet an arrester with Uc = 23 kV
and environmental, and the importance of the is chosen.
equipment to be protected it is necessary to
­decide which characteristics of the MO surge Step b) Rated voltage Ur
­arresters are most important to provide best pro- According data sheet the rated voltage is
tection. In this way the type of arrester (arrester Ur = 28.8 kV.
class) can be chosen from the very beginning.
Step c) Nominal discharge current In
As cables can store a relatively high energy it is The nominal discharge current for MO surge
advisable to choose arresters with a higher ­arresters class DH, SL, SM is In = 10 kA, for class
charge transfer rating than used for the protec- SH the nominal discharge current is In = 20 kA.
tion of overhead lines or distribution substations. The type MWK (class SL) has In = 10 kA. See also
This offers at the same time a better protection data sheet.
due to the normally lower residual voltage of
the arrester at the same continuous operating Step d) Charge and thermal rating Qrs and Wth
­voltage Uc . Based on the given information the type MWK
with the
The following example is based on system • Repetitive charge transfer rating Qrs = 1.6 C and
­conditions typical for cable systems in Germany. • Rated thermal energy Wth = 6.25 kJ/ kVUc
was chosen for this application.
See also data sheet.
8 A P P L I C AT I O N N O T E C A B L E S

Step e) Check lightning impulse protection level Step g) Flashover distance


Upl and withstand voltage LIWV The minimum necessary withstand values of
Control of the protection level. Required is: the empty arrester housing are calculated
Upl ≤ LIWV / Ks ­according to IEC 60099-4, Ed. 3.0 as:

With LIWV = 125 kV and Ks = 1.15 for outdoor Lightning voltage impulse 1.2/50 μs:
i­ nsulation, the maximum allowed voltage 1.3 × Upl = 1.3 × 70.7 kV = 91.91 kV
at the electrical equipment results in 108.7 kV.
a. c. voltage test 1 min., wet:
The MWK 23 has a Upl of 70.7 kV and meets the 1.06 × Ups (switching current impulse 500 A =>
­demands with a good additional safety margin. Ups = 56.6 kV) = U­test ,pv = 60 kV,pv.
This results in a withstand value of
With the steps a) to e) the active part of 60 kV / 2  = 42.4 kV, rms, 1 min., wet.
the MO surge arrester is selected. Now follows
­selection of the arrester housing and The proved withstand values according to
­confirmation of mechanical data. the datasheet are:
Lightning discharge voltage 1.2/50 μs: 179 kV
Step f) Creepage distance a. c. voltage test: 76 kV, rms, 1 min. wet.
The creepage distance is related to pollution
problems. Flashovers due to pollution are long- Therefore, the housing of MWK 23 has
term effects (in the range of one or more hours) higher withstand values than are required
and occur only under continuous voltage stress according to IEC.
with a. c. od d. c. Short-term overvoltages (TOV)
need generally not to be considered. Therefore, Step h) Consider short circuit rating Is
the voltage across the insulator, or insulating The MWK 23 is proved with a short circuit current
housing in case of an MO surge arrester, is deci- of 20 kA and meets the demands for a short
sive. This is the phase-to-earth voltage Us /  3. ­c ircuit current of 20 kA, as it was assumed.

According the assumption low pollution (pollu- Step i) Consider mechanical loads
tion class b – light according IEC/TS 60815-1) Special requirements for mechanical loads are
is considered. Therefore, the reference unified not given. Therefore, no further considerations
­specific creepage distance (RUSCD) between necessary.
phase and earth is 27.8 mm/kV.

Note: In previous standards the definition of It follows: the MWK 23 fulfills all
the creepage distance was related to the system
voltage phase-to-phase and defined as “specific
requirements and is the right
creepage distance” SCD. In this case the SCD ­arrester from all points of view
would be 27.8 /  3  = 16 mm/kV.
for this application.
This results in a minimum requirement of 384 mm
creepage distance. With silicone housing and
light pollution (pollution class b, see Table 4 in the
Application Guidelines) the creepage distance can
be reduced by 30%. This ultimately results
in a creepage distance of 269 mm. The MWK 23
has a creepage distance of 567 mm according
the data sheet and fulfills the requirement.

Note: The creepage distance for a MO surge


­arrester is sometimes specified in relation to the
continuous operating voltage Uc of the arrester.
Therefore, it is in any case important to know
to which voltage the creepage requirements are
­related.
9 O V E R V O LTA G E P R OT E C T I O N 9

Summary It is advisable that a surge arrester should be


­provided at the following points in a cable s
­ ystem:
Electrical distribution systems are subject to • at all switchgear bays that are open during
lightning strikes, switching transients and system ­system operation
faults at nearly anytime. Such occurrences can be • at arc suppression coils (Petersen coil)
damaging to electrical systems as well as to • at the end points of the network,
­various installed equipment. Therefore, surge i. e. at the ­cable end of open rings
protection is needed which provides protection
for cables as for all other installed equipment. Furthermore, surge arresters must be installed at
Gapless Metal-Oxide surge arresters (MO arrest- the conjunction of cable/overhead lines.
ers) provide best protection against all kind of
transient overvoltages. The function of the For short cable sections a protection on one side
MO a­ rrester is to guard the insulation of the cable can be enough. This is possible because the
and the cable bushing. ­protective range of an arrester at one end of the
cable can still offer enough protection at the other
In case a transient overvoltage, e. g. a lightning end. In Table 1 information is given if an MO surge
overvoltage, travels along an overhead line and arrester at one end of the cable is sufficient,
enters a cable, the voltage in the cable will reach or if both ends need protection. As a rule of
the same value as the incoming voltage. If the end thumb, a cable longer than indicated in Table 1
of the cable is terminated with a very high and shorter than 1000 m needs protection at both
­impedance (open circuit breaker or transformer) ends of the cable.
the voltage in the cable will reach even twice
the incoming voltage. If both ends of a cable are endangered
by l­ightning or other transient overvoltages
Cables can store a relatively high energy, which in ­protection at both sides is advisable.
case of an overvoltage, can be discharged into
the MO surge arrester. For this reason, MO surge Large cable systems may require system studies
arresters with a high energy handling capability to find an optimized protection solution.
should be used. MO surge arresters with higher
energy handling capability provide also a better
protection level.

The application of MO surge arresters reduces


ageing effects of the cable insulation and,
­therefore, provide increased lifetime of the cable.
10 A P P L I C AT I O N N O T E C A B L E S


A P P L I C AT I O N N OT E 3 . 0 A N N E X

This Annex explains why short cables and very The single travelling time of a wave in the cable is
long cables need protection against overvoltages LK/vK . The rise time of an overvoltage wave on
on one side only. The following example is a very the overhead line, and hence on the arrester next
general one, and different assumptions as made to the cable head, is assumed to be T as shown in
below will lead to different results. Figure A1. If this rise time is not shorter than four
Further, damping effects are not considered. times LK/vK , then despite of the multiple reflec-
tions the voltage at the cable end is almost of the
With the considerations made up to this time same amplitude as at the front end of the cable.
the wave travelling from the line in the direction Consequently, the voltage at the end of the cable
of the cable was assumed to be a square wave or increases at most to the protection level of the
a wave with strongly simplified wave shape. ­arrester at the front end of the cable. The a ­ rrester
In practice this theoretical assumption is too at the end of the cable does not contribute
­simple. If realistic values for the rise time and half ­anything to the protection. If a rise time of 0.4 µs
value of the tail for the overvoltage wave on is assumed, corresponding to the conditions
the overhead line are assumed, this leads to the of ­medium-voltage systems, then according to
­conclusion that with very short and very long ­Figure A1 a) with a single arrester a cable of
­cables the overvoltage protection using surge ­maximum length of 15 m is adequately protected.
­arresters can be simplified. Then, only one set of
arresters is needed at one of the two ends of Lightning currents rise very fast, reach their peak
a ­cable. value, and then drop rather quickly to zero. The
electrical charge in a lightning strike is therefore
in any case limited, as is the portion of the charge
which can flow in an overhead line. In addition,
a cable can be regarded as a capacitance between
conductor and earth which increases propor-
tional to the cable length LK . Consequently, for
a given lightning charge a long cable with a high
capacitance is charged to a lesser extent than
a short cable with low capacitance.

— U U
Figure A1: Critical
lengths for cables with 1
arrester protection only
at one end of the cable.

0.5

x x
T T₂

LK 3 × ZF × LK
a) T > 4 ×  = 0.4 μs b) T2 <
vK ZK × vK

LK = 15 m LK* = 1000 m
11 O V E R V O LTA G E P R OT E C T I O N 11

It can therefore be assumed that a critical cable Summarizing, with the assumptions made,
length LK* exists, at which the unprotected cable the following protection concept arises for cables:
end is only charged to the same voltage as the end • Arrester protection at only one cable end for ca-
protected by an arrester. This critical length LK* ble lengths < 15 m or > 1000 m.
will naturally depend on how quickly the ­lightning • Arrester protection at both cable ends accord-
decays, or on the length of the tail h
­ alf-value time ing to Figure A2 for all cables lengths between
T2 of the incoming overvoltage wave in F ­ igure A1 15 m and 1000 m.
b). Under the simplifying a ­ ssumption that the
voltage in the tail of the overvoltage wave decays In a more general way, it can be stated that
linearly, the equation was derived ­medium-voltage cables in the range of some me-
T 2 × ZK × vK ters to some tens of meters and cables of around
LK* ≥ -------------- 1000 m and more need overvoltage protection
3 × ZF on one side only. This depends strongly on the
If this equation is valid, the voltages on the two ­system voltage, the type of pole and the assumed
ends of the cable are almost equal. ­waveshape of the incoming overvoltage.
Typical f­ igures for medium-voltage cables are
With the realistic assumption of T 2 = 300 µs given in T ­ able 1.
a critical length of 1000 m is obtained for a cable.
This means that for all cables of a length > 1000 m It goes without saying that cables that are prone
arrester protection at one end of the cable is to overvoltages at both ends need overvoltage
­sufficient. protection on both ends of the cable.


Figure A2: Medium-­ LK
voltage cables with
lengths between 15 m U
and 1000 m are to be
protected at each end of
the cable by an arrester.

15 m < LK < 1000 m



ABB Power Grids Switzerland AG
PGHV
Surge Arresters
Jurastrasse 45
CH-5430 Wettingen/Switzerland
Tel. + 41 58585 2911
Fax + 41 58585 5570
Email: sales.sa@ch.abb.com

abb.com/arrestersonline

Additional information
We reserve the right to make technical
changes or modify the content of this
­document without prior notice. With
­regard to purchase orders, the agreed
­particulars shall prevail. ABB AG does not
accept any responsibility whatsoever for
potential errors or possible lack of
­information in this document.

We reserve all rights in this document and


in the subject matter and illustrations
­contained therein. Any reproduction,
­disclosure to third parties or utilization of
its contents – in whole or in parts – is
­forbidden without prior written consent
1HC0138879 EN AA

of ABB Power Grids S­ witzerland AG.

© Copyright 2020 ABB Power Grids Switzerland AG.


All rights reserved
Specifications subject to change without notice

You might also like