Professional Documents
Culture Documents
A P P L I C AT I O N N OT E 3 .0
Cables
Overvoltage protection
The APPLICATION NOTES (AN) are intended to be used in
conjunction with the
APPLICATION GUIDELINES
Overvoltage protection
Metal-oxide surge arresters in medium-voltage systems.
—
Overvoltage protection of cables
Disruptive breakdowns in cable insulation lead to grave damages
and require expensive repairs. Flashovers along cable bushings
can damage them and lead to the same consequences as an insulation
breakdown. Further, repeated overvoltages influence negatively
the ageing behavior of the cable insulation. Therefore, cables must be
protected like all other electrical equipment.
The amplitudes can reach up to 4 p.u in unfavor- For overhead lines in medium-voltage distribu-
able constellations. tion systems the surge impedance lies in
the range of ZL = 450 Ω to 500 Ω and for cables
Notable switching overvoltages occur especially between ZK = 30 Ω and 60 Ω.
in systems with isolated or arc suppression
neutral as a result of With the help of Figure 1 travelling waves in cables
• Switching on cables and overhead lines, can be explained. In the simplified arrangement
and of complete networks of an overhead line and a cable section the over-
• Disconnection of cables with re-striking head line has a surge impedance of ZL = 450 Ω
• Initiation of ground faults and the cable ZK = 30 Ω, see Figure 1a. A step
• Clearing of system faults by corresponding voltage U travels along the overhead line at a ve-
c ircuit breakers locity of 300 m/µs in the direction of the c able,
Figure 1b. The travel velocity in the cable is
3 Overvoltage waves in cables assumed to be 150 m/µs. At the transition over-
head line/cable reflections and transmissions
Overvoltage waves in cables and cable systems occur due to the change in the surge impedances.
are generally treated with the travelling wave A part of the incoming wave is transmitted into
theory. One essential difference between the cable, the larger part is reflected.
the electrical data of overhead lines and cables is
the surge impedance Z of their conductors to The reflected and transmitted parts of the volt-
earth. age impulse can be calculated with the reflection
factor ru and the transmission factor bu.
The surge impedance is given by the equation Both factors depend on the surge impedances of
Z = L’ / C’. the overhead line ZL and the cable ZK .
2 × ZK
L’ is the inductance per unit length in H/km and C’ bu = ---------
is the capacitance per unit length in F/km. ZL + ZK
The travelling speed is given to ZK – ZL
v = 1 / L’ × C’. ru = ---------
ZL + ZK
—
Figure 1: Reflections of X1 X2
a travelling wave
(square wave) with
ZL ZK ZL
the amplitude U
at the transition a)
overhead line/cable.
v
U
b)
x
c)
x
d) U
x
O V E R V O LTA G E P R OT E C T I O N 5
With the given surge impedances, a transmission It follows, that in the case of a cable installed
factor bu = 0.125 and a reflection factor in the path of an overhead line, say for passing
ru = –0.875 results for the junction (X1) from the beneath a highway, the maximum value of
overhead line to the cable. the voltage u(t) in the cable is U. This means that
the wave behind the cable is also just as high
This means a voltage wave travels through the as the incoming wave.
cable with the amplitude of U/8 and is positively
reflected at the end of the cable (X2), travelling In case of an open circuit breaker or a transformer
back to the entry point of the cable, Figure 1c. at the end of the cable, see Figure 3, the time
There the v oltage is again positively reflected, constant is given to
Figure 1d. It is easy to realize how this wave, ZL × LK
travelling back and forth in the cable, builds the τ = ---------
voltage s tep-wise up to the end value. ZK × vK
If the cable is terminated with an open circuit
3.1 Time curve of the voltage in the cable breaker or a transformer the voltage will reach
a maximum of two times the incoming voltage.
In Figure 1 the voltage reflections at the begin- The time constant will be τ = 10 µs.
ning and at the end of the cable are explained.
In Figure 2 the time curve of the voltage in a cable The increase of the voltage in the cable, as shown
with an assumed length of LK = 100 m is shown. in Figures 2 and 3, follows exactly the time
The time curve of this voltage buildup follows function of a capacitor that is charged with
the time function 1 – e –t/τ as shown in the exam- a DC step voltage. This is logic, because a cable
ples of Figure 2 and Figure 3. The time constant can be considered to be a long coaxial capacitor.
is given by the equation
ZL × LK
τ = -------------
2 × ZK × v K
LK cable length
vK travelling speed in the cable
— —
Figure 2: Time Figure 3: Same as
characteristic of Figure 2, but with
the voltage in the cable an open circuit
on the occurrence of breaker at the end
a square wave. of the cable.
L K = 100 m
L K = 100 m
τ = 10 μs
τ = 5 μs
2u
U U U
t t
6 A P P L I C AT I O N N O T E C A B L E S
—
Table 1: The maximum admissible length LK of a cable if the arrester protection is only on one side. The cable
is connected to a lightning endangered line. The connection length between the arrester and the cable should be
at most 1 m. The numerical values are valid for an arrester with Upl = 4 p.u. and In = 10 kA (arrester class SL).
LK LK
U U
Type of overhead line Wooden poles Earthed cross arm Wooden poles Earthed cross arm
Us in kV ZK in Ω LK in m LK in m LK in m LK in m
3.6 30 ∞ ∞ 8 19
60 ∞ ∞ 4 13
7.2 30 85 110 11 27
60 75 100 5 17
12 30 45 50 8 22
60 33 39 4 16
17.5 30 35 36 6 19
60 27 30 3 15
24 30 34 36 9 21
60 27 30 4 17
36 30 30 30 7 19
60 24 26 4 17
O V E R V O LTA G E P R OT E C T I O N 7
Damping effects in the cables are not considered Following the steps given in selection flow chart
in all the calculations made for the given Application Note 1.1 A1 it follows:
examples.
Step a) Continuous operating voltage Uc
5 Selection of MO surge arresters The choice of the continuous operating voltage
for cable protection according to Application Note 1.2 is
Us
The MO surge arresters should be selected as Uc ≥ ----
described in the Application Guidelines T
and the Application Notes 1.1 Selection of A surge arrester class SL was chosen, e. g. the
MO surge arresters. type MWK. T follows according TOV curve to
T = 1.19 (fault duration 1’800 s, with prior duty).
The example given below guides through the
principle of the selection process step by step. With 10% additional safety margin for Uc,
Other system configurations are possible and this results in:
have to be considered from case to case. Uc = 24 kV / 1.19 × 1.1 = 22.18 kV.
Depending on the expected stresses, electrical According data sheet an arrester with Uc = 23 kV
and environmental, and the importance of the is chosen.
equipment to be protected it is necessary to
decide which characteristics of the MO surge Step b) Rated voltage Ur
arresters are most important to provide best pro- According data sheet the rated voltage is
tection. In this way the type of arrester (arrester Ur = 28.8 kV.
class) can be chosen from the very beginning.
Step c) Nominal discharge current In
As cables can store a relatively high energy it is The nominal discharge current for MO surge
advisable to choose arresters with a higher arresters class DH, SL, SM is In = 10 kA, for class
charge transfer rating than used for the protec- SH the nominal discharge current is In = 20 kA.
tion of overhead lines or distribution substations. The type MWK (class SL) has In = 10 kA. See also
This offers at the same time a better protection data sheet.
due to the normally lower residual voltage of
the arrester at the same continuous operating Step d) Charge and thermal rating Qrs and Wth
voltage Uc . Based on the given information the type MWK
with the
The following example is based on system • Repetitive charge transfer rating Qrs = 1.6 C and
conditions typical for cable systems in Germany. • Rated thermal energy Wth = 6.25 kJ/ kVUc
was chosen for this application.
See also data sheet.
8 A P P L I C AT I O N N O T E C A B L E S
With LIWV = 125 kV and Ks = 1.15 for outdoor Lightning voltage impulse 1.2/50 μs:
i nsulation, the maximum allowed voltage 1.3 × Upl = 1.3 × 70.7 kV = 91.91 kV
at the electrical equipment results in 108.7 kV.
a. c. voltage test 1 min., wet:
The MWK 23 has a Upl of 70.7 kV and meets the 1.06 × Ups (switching current impulse 500 A =>
demands with a good additional safety margin. Ups = 56.6 kV) = Utest ,pv = 60 kV,pv.
This results in a withstand value of
With the steps a) to e) the active part of 60 kV / 2 = 42.4 kV, rms, 1 min., wet.
the MO surge arrester is selected. Now follows
selection of the arrester housing and The proved withstand values according to
confirmation of mechanical data. the datasheet are:
Lightning discharge voltage 1.2/50 μs: 179 kV
Step f) Creepage distance a. c. voltage test: 76 kV, rms, 1 min. wet.
The creepage distance is related to pollution
problems. Flashovers due to pollution are long- Therefore, the housing of MWK 23 has
term effects (in the range of one or more hours) higher withstand values than are required
and occur only under continuous voltage stress according to IEC.
with a. c. od d. c. Short-term overvoltages (TOV)
need generally not to be considered. Therefore, Step h) Consider short circuit rating Is
the voltage across the insulator, or insulating The MWK 23 is proved with a short circuit current
housing in case of an MO surge arrester, is deci- of 20 kA and meets the demands for a short
sive. This is the phase-to-earth voltage Us / 3. c ircuit current of 20 kA, as it was assumed.
According the assumption low pollution (pollu- Step i) Consider mechanical loads
tion class b – light according IEC/TS 60815-1) Special requirements for mechanical loads are
is considered. Therefore, the reference unified not given. Therefore, no further considerations
specific creepage distance (RUSCD) between necessary.
phase and earth is 27.8 mm/kV.
—
Note: In previous standards the definition of It follows: the MWK 23 fulfills all
the creepage distance was related to the system
voltage phase-to-phase and defined as “specific
requirements and is the right
creepage distance” SCD. In this case the SCD arrester from all points of view
would be 27.8 / 3 = 16 mm/kV.
for this application.
This results in a minimum requirement of 384 mm
creepage distance. With silicone housing and
light pollution (pollution class b, see Table 4 in the
Application Guidelines) the creepage distance can
be reduced by 30%. This ultimately results
in a creepage distance of 269 mm. The MWK 23
has a creepage distance of 567 mm according
the data sheet and fulfills the requirement.
—
A P P L I C AT I O N N OT E 3 . 0 A N N E X
This Annex explains why short cables and very The single travelling time of a wave in the cable is
long cables need protection against overvoltages LK/vK . The rise time of an overvoltage wave on
on one side only. The following example is a very the overhead line, and hence on the arrester next
general one, and different assumptions as made to the cable head, is assumed to be T as shown in
below will lead to different results. Figure A1. If this rise time is not shorter than four
Further, damping effects are not considered. times LK/vK , then despite of the multiple reflec-
tions the voltage at the cable end is almost of the
With the considerations made up to this time same amplitude as at the front end of the cable.
the wave travelling from the line in the direction Consequently, the voltage at the end of the cable
of the cable was assumed to be a square wave or increases at most to the protection level of the
a wave with strongly simplified wave shape. arrester at the front end of the cable. The a rrester
In practice this theoretical assumption is too at the end of the cable does not contribute
simple. If realistic values for the rise time and half anything to the protection. If a rise time of 0.4 µs
value of the tail for the overvoltage wave on is assumed, corresponding to the conditions
the overhead line are assumed, this leads to the of medium-voltage systems, then according to
conclusion that with very short and very long Figure A1 a) with a single arrester a cable of
cables the overvoltage protection using surge maximum length of 15 m is adequately protected.
arresters can be simplified. Then, only one set of
arresters is needed at one of the two ends of Lightning currents rise very fast, reach their peak
a cable. value, and then drop rather quickly to zero. The
electrical charge in a lightning strike is therefore
in any case limited, as is the portion of the charge
which can flow in an overhead line. In addition,
a cable can be regarded as a capacitance between
conductor and earth which increases propor-
tional to the cable length LK . Consequently, for
a given lightning charge a long cable with a high
capacitance is charged to a lesser extent than
a short cable with low capacitance.
— U U
Figure A1: Critical
lengths for cables with 1
arrester protection only
at one end of the cable.
0.5
x x
T T₂
LK 3 × ZF × LK
a) T > 4 × = 0.4 μs b) T2 <
vK ZK × vK
LK = 15 m LK* = 1000 m
11 O V E R V O LTA G E P R OT E C T I O N 11
It can therefore be assumed that a critical cable Summarizing, with the assumptions made,
length LK* exists, at which the unprotected cable the following protection concept arises for cables:
end is only charged to the same voltage as the end • Arrester protection at only one cable end for ca-
protected by an arrester. This critical length LK* ble lengths < 15 m or > 1000 m.
will naturally depend on how quickly the lightning • Arrester protection at both cable ends accord-
decays, or on the length of the tail h
alf-value time ing to Figure A2 for all cables lengths between
T2 of the incoming overvoltage wave in F igure A1 15 m and 1000 m.
b). Under the simplifying a ssumption that the
voltage in the tail of the overvoltage wave decays In a more general way, it can be stated that
linearly, the equation was derived medium-voltage cables in the range of some me-
T 2 × ZK × vK ters to some tens of meters and cables of around
LK* ≥ -------------- 1000 m and more need overvoltage protection
3 × ZF on one side only. This depends strongly on the
If this equation is valid, the voltages on the two system voltage, the type of pole and the assumed
ends of the cable are almost equal. waveshape of the incoming overvoltage.
Typical f igures for medium-voltage cables are
With the realistic assumption of T 2 = 300 µs given in T able 1.
a critical length of 1000 m is obtained for a cable.
This means that for all cables of a length > 1000 m It goes without saying that cables that are prone
arrester protection at one end of the cable is to overvoltages at both ends need overvoltage
sufficient. protection on both ends of the cable.
—
Figure A2: Medium- LK
voltage cables with
lengths between 15 m U
and 1000 m are to be
protected at each end of
the cable by an arrester.
abb.com/arrestersonline
Additional information
We reserve the right to make technical
changes or modify the content of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB AG does not
accept any responsibility whatsoever for
potential errors or possible lack of
information in this document.