STULZ C7000 IO-CONTROL 01 (V6.62)
14:21:51 29.11.2022
ioc 01:>
STULZ C7000 IO-CONTROL 01 (V6.62)
14:22:00 29.11.2022
ioc 01:>AIN
Analog in 00:4
Analog in 01:2055
- Sensor 01 (Room temperature)
Analog in 02:2846
- Sensor 02 (Room humidity)
Analog in 03:4
Analog in 04:4
Analog in 05:1320
Analog in 06:0
Analog in 07:0
Analog in 08:0
Analog in 09:0
Analog in 10:0
Analog in 11:0
Analog in 12:0
Analog in 13:0
Analog in 14:0
Analog in 15:0
Analog in 16:0
Analog in 17:0
Analog in 18:0
Analog in 19:0
Analog in 20:0
Analog in 21:0
ioc 01:>AOUT
Analog out 00:0 (0.0 V)
Analog out 01:3276 (8.0 V)
- Fan 1
Analog out 02:0 (0.0 V)
Analog out 03:0 (0.0 V)
Analog out 04:0 (0.0 V)
Analog out 05:0 (0.0 V)
Analog out 06:0 (0.0 V)
Analog out 07:0 (0.0 V)
Analog out 08:0 (0.0 V)
Analog out 09:0 (0.0 V)
Analog out 10:0 (0.0 V)
Analog out 11:0 (0.0 V)
Analog out 12:0 (0.0 V)
Analog out 13:0 (0.0 V)
Analog out 14:0 (0.0 V)
Analog out 15:0 (0.0 V)
Analog out 16:0 (0.0 V)
Analog out 17:0 (0.0 V)
Analog out 18:0 (0.0 V)
Analog out 19:0 (0.0 V)
Analog out 20:0 (0.0 V)
ioc 01:>DIN
Digital in 00 not active
- Remote on/off
- Fire
- Water
- Phase
- Waterflow
- Highpressure 2
- UPS
- CW off
- Alarm in compressor 2
Digital in 01 active
- Alarm in fan 1
Digital in 02 active
- Highpressure 1
Digital in 03 not active
Digital in 04 not active
Digital in 05 active
- Alarm in filter fan 1
Digital in 06 active
Digital in 07 not active
Digital in 08 active
Digital in 09 active
- Alarm in LP compressor 2
Digital in 10 not active
Digital in 11 active
Digital in 12 not active
Digital in 13 not active
Digital in 14 not active
Digital in 15 not active
Digital in 16 not active
Digital in 17 not active
Digital in 18 not active
Digital in 19 not active
Digital in 20 not active
Digital in 21 not active
Digital in 22 not active
Digital in 23 not active
Digital in 24 not active
Digital in 25 not active
Digital in 26 not active
Digital in 27 not active
Digital in 28 not active
Digital in 29 not active
Digital in 30 not active
Digital in 31 not active
Digital in 32 not active
Digital in 33 not active
Digital in 34 not active
Digital in 35 not active
Digital in 36 not active
Digital in 37 not active
Digital in 38 not active
Digital in 39 not active
Digital in 40 not active
Digital in 41 not active
Digital in 42 not active
Digital in 43 not active
ioc 01:>DOUT
Digital out 00 active
- Wintermode
- BMS stop 1
- Local Stop
- Unit on/off
- EC-fan running
- Free Cooling
- Alarmprio fan 1
- Alarmprio filter fan 1
- Alarmprio compressor 2
- Alarmprio LP compressor 2
- Alarmprio sensor 01
- Alarmprio break sensor 01
- Alarmprio sensor 02
- Alarmprio break sensor 02
- Alarmprio temp sensor EEV 02
- Alarmprio pressure sensor EEV 02
- Alarmprio motor EEV 02
- Alarmprio EVD not available
- Alarmprio fire
- Alarmprio water
- Alarmprio phase
- Alarmprio waterflow
- Alarmprio highpressure 1
- Alarmprio highpressure 2
- Alarmprio busalarm
- Alarmprio addressconflict
- Alarmprio roomtemp too high
- Alarmprio roomtemp too low
- Alarmprio roomhumidity too high
- Alarmprio roomhumidity too low
- Alarmprio supplytemp too high
- Alarmprio supplytemp too low
- Alarmprio supplyhumidity too high
- Alarmprio supplyhumidity too low
- Alarmprio Watertemp. inlet 1 too high
- Alarmprio Watertemp. inlet 1 too low
- Alarmprio Watertemp. inlet 2 too high
- Alarmprio Watertemp. inlet 2 too low
- Alarmprio Pre-alarm: Supply air pressure too low
- Alarmprio Supply air pressure too low
- Alarmprio Pre-alarm: Supply air pressure too high
- Alarmprio Supply air pressure too high
- ICC Alarmpriority not available
- ICC Alarmpriority icc Error
- ICC Alarmpriority low pressure
- Ref block valve 1
- Ref block valve 2
Digital out 01 active
- Fan 1
Digital out 02 not active
Digital out 03 not active
Digital out 04 not active
Digital out 05 not active
Digital out 06 not active
- Common alarm
Digital out 07 not active
- Compressor 2
Digital out 08 not active
Digital out 09 not active
Digital out 10 not active
Digital out 11 not active
Digital out 12 not active
Digital out 13 not active
Digital out 14 not active
Digital out 15 not active
Digital out 16 not active
Digital out 17 not active
Digital out 18 not active
Digital out 19 not active
Digital out 20 not active
Digital out 21 not active
Digital out 22 not active
Digital out 23 not active
Digital out 24 not active
Digital out 25 not active
Digital out 26 not active
Digital out 27 not active
Digital out 28 not active
Digital out 29 not active
Digital out 30 not active
Digital out 31 not active
ioc 01:>EQUIP
Compressors.................:2
Suctionvalve................:0
HGBP........................:0
EEV.........................:1
GE/CW-valve.................:0
ECO-COOL louver.............:0
AE-louvers..................:0
G-valve.....................:0
Condenser fan...............:0
Humidifier..................:0
Dehumidifier valve..........:0
Dehumidifier hotgas bypass..:0
Drycooler...................:0
Pumps.......................:0
E-heating...................:0
Hotgas reheating............:0
PWW-heating.................:0
Fan.........................:1
Louver......................:0
Sensors.....................:2
Ext Alarm in................:0
Digital extension card......:0
Analoge extension card......:0
EEV extension card..........:0
Bus extension card..........:1
ICC.........................:1
Refrigerant block valve.....:0
ioc 01:>STATUS
Unit:Running
- Runtime:42102 h
- Stoptime:216 h
- Fan 1:80 %
Cooling:active (30217 h)
- ICC 1:100.0 %
Heating:not active (0 h)
Humidification:not active (0 h)
Dehumidification:active (8051 h)
- Dehumidification:1
Alarms:
ioc 01:ICC 1
Integrated Cooling Circuit 1
Configured..................................................:1
Modbus Address..............................................:1
Compressor Pmin limit.......................................:17.0 %
Compressor Pmax limit.......................................:100.0 %
Start temperature offset....................................:0.4 K
Hysteresis..................................................:0.8 K
Low after start.............................................:240 s
Low after dehumi............................................:240 s
pressure equalize threshold.................................:0.0 bar
pressure equalize opening grade.............................:0.0 %
pressure equalize period....................................:0 s
compressor minimum speed while dehumidification.............:100.0 %
P-coefficient...............................................:10
I-coefficient...............................................:40
D-coefficient...............................................:0
Runtime.....................................................:29761 h
Availability................................................:100 % (9|0|0|239)
Manual operation............................................:0
Manual on...................................................:0.0 %
ioc 01:>EEV 1
EEV 1
Configured.........................:0
Controller.........................:1 (EVD)
Net id.............................:198
Availability.......................:100 %
Alarmpriority availability.........:0
Common alarm availability..........:0
Refrigerant........................:4 (R407C)
MOP temperature....................:30.0 °C
Superheat setpoint.................:7.0 K
Dehumidification superheat setpoint:12.0 K
Current superheat setpoint.........:12.0 K
Start-up opening...................:50 %
Valve type.........................:1 (CAREL EXV)
Valve steps........................:480
Sensortype Evaporating pressure....:3 (-1...9.3bar)
Alarmpriority pressure.............:0
Common alarm pressure..............:0
Alarmpriority Temp.................:0
Common alarm temp..................:0
Alarmpriority motor................:0
Common alarm motor.................:0
Manual operation...................:0
Manual on..........................:0.00 %
Control active.....................:0
Alarm availability.................:0
Suction pressure...................:0.0 bar
Saturation temperature.............:0.0 °C
Coil out temperature...............:0.0 °C
Superheat..........................:0.0 K
Valve opening......................:0.0 %
ioc 01:>COMP 1
Compressor 1
Configured..................:0
Digital out.................:2
Digital alarm in............:0
Alarmpriority...............:0
Common alarm................:1
Alarmdelay..................:5 s
Digital alarm in low press..:3
Alarmpriority low press.....:0
Common alarm low press......:1
Alarmdelay low press........:5 s
Type........................:1
Start temperature summer....:0.4 K
Stop hysteresis summer......:0.7 K
Start temperature winter....:0.7 K
Stop hysteresis winter......:0.7 K
Minimum runtime.............:0 s
Pause.......................:180 s
LP management time..........:0 h
LP management min press.....:5.0 bar
LP management tries.........:0
HP management time..........:0 h (0)
HP management max press.....:21.0 bar
HP management tries.........:0
HP management mode..........:0
Runtime.....................:1 h
Manual operation............:0
Manual on...................:0
On..........................:0 (0/0)
Alarm.......................:0
Alarm low press.............:0
ioc 01:>COMP 2
Compressor 2
Configured..................:1
Digital out.................:7
Digital alarm in............:0
Alarmpriority...............:0
Common alarm................:1
Alarmdelay..................:5 s
Digital alarm in low press..:9
Alarmpriority low press.....:0
Common alarm low press......:1
Alarmdelay low press........:5 s
Type........................:1
Start temperature summer....:0.6 K
Stop hysteresis summer......:0.7 K
Start temperature winter....:0.9 K
Stop hysteresis winter......:0.7 K
Minimum runtime.............:0 s
Pause.......................:180 s
LP management time..........:0 h
LP management min press.....:5.0 bar
LP management tries.........:0
HP management time..........:0 h (0)
HP management max press.....:21.0 bar
HP management tries.........:0
HP management mode..........:0
Runtime.....................:508 h
Manual operation............:0
Manual on...................:0
On..........................:0 (0/2)
Alarm.......................:0
Alarm low press.............:0
ioc 01:>EEV 2
EEV 2
Configured.........................:1
Controller.........................:1 (EVD)
Net id.............................:198
Availability.......................:100 %
Alarmpriority availability.........:0
Common alarm availability..........:0
Refrigerant........................:5 (R410A)
MOP temperature....................:30.0 °C
Superheat setpoint.................:7.0 K
Dehumidification superheat setpoint:12.0 K
Current superheat setpoint.........:12.0 K
Start-up opening...................:50 %
Valve type.........................:1 (CAREL EXV)
Valve steps........................:480
Sensortype Evaporating pressure....:4 (0...17.3bar)
Alarmpriority pressure.............:0
Common alarm pressure..............:0
Alarmpriority Temp.................:0
Common alarm temp..................:0
Alarmpriority motor................:0
Common alarm motor.................:0
Manual operation...................:0
Manual on..........................:0.00 %
Control active.....................:0
Alarm availability.................:0
Suction pressure...................:11.5 bar
Saturation temperature.............:15.0 °C
Coil out temperature...............:15.4 °C
Superheat..........................:0.4 K
Valve opening......................:0.0 %
Type...........................:2 (continuous)
Minimum speed..................:70 %
nMin CW Dual Fluid.............:50 %
nMax...........................:80 %
nMax CW Dual Fluid.............:85 %
nMax EFC (DFC).................:85 %
Offset.........................:0 %
Pre runtime....................:10 s (0)
After runtime..................:60 s (60)
Start temperature..............:0.0 K
Start speed....................:0 %
DTC start temperature diff.....:10.0 K
DTC temperature range..........:0.0 K
DTC type.......................:0
100% start runtime.............:10 s
Reduce time....................:30 min (30)
Reduce speed...................:0 %
Time until dehumi reduction....:0 min (0 sec)
Reduce dehumidification........:0 %
Reduce UPS.....................:0 %
Filteralarmoffset..............:0 %
Start emergency................:0.0 K
End emergency..................:0.0 K
nMax emergency.................:0 %
Control cycle..................:10 s
Max adjust.....................:2 %
Control factor.................:40
P-coefficient..................:10
I-coefficient..................:40
D-coefficient..................:0
Stop on cooling error..........:0
Runtime........................:42102 h
Manual operation...............:0
Manual on......................:0 %
On.............................:80 % (21)
Alarm..........................:0
Alarm filter...................:0
ioc 01:>HUMI 1
Humidifier 1
Configured.............:0
Type...................:2 (continuous)
Analog out.............:3 (active)
Digital out............:13
Digital alarm in.......:6
Alarmpriority..........:0
Common alarm...........:1
Alarmdelay.............:5 s
Conductivity configured:0
Runtime................:0 h
Manual operation.......:0
Manual on..............:0 %
On.....................:0 % (0)
Alarm..................:0
Alarm 5uS..............:0
Alarm 20uS.............:0
ioc 01:>DEHUMI 1
Dehumidification
Start humidity.................:10.0 %rH
Hysteresis.....................:5.0 %rH
Start dewpoint.................:11.6 °C
Stop dewpoint..................:10.1 °C
Type...........................:0
Digital out....................:5
Stop...........................:2.0 K
Dehumidificate watertemp min...:5.0 °C
Dehumidificate watertemp max...:14.0 °C
Valve configured...............:0
Hotgas bypass configured.......:0
Manual operation...............:0
Manual on......................:0
On.............................:1 (2)
Valve..........................:1 (not active)
Hotgasbypass...................:1 (not active)
ioc 01:>EHEAT 1
E-heating 1
Configured.........:0
Type...............:1 (2-point)
Digital out........:3
Digital alarm in...:4
Alarmpriority......:0
Common alarm.......:1
Alarmdelay.........:4 s
Start temperature..:1.5 K
Hysteresis.........:0.5 K
Runtime............:0 h
Manual operation...:0
Manual on..........:0
On.................:0 (0)
Alarm..............:0
ioc 01:>SEN 1
Configured..................:1
Analog in...................:1
Type........................:1 (Current)
Min output value............:4.0 mA
Max output value............:20.0 mA
Alarmpriority sensor break..:0
Commonalarm sensor break....:1
Alarmdelay sensor break.....:5 s
ioc 01:>SEN 2
Configured..................:1
Analog in...................:2
Type........................:1 (Current)
Min output value............:4.0 mA
Max output value............:20.0 mA
Alarmpriority sensor break..:0
Commonalarm sensor break....:1
Alarmdelay sensor break.....:5 s
ioc 01:>IS 1
Temperature setpoint..............:21.0 °C
Temperature setpoint corrected....:21.0 °C
Night temperature setpoint........:27.0 °C
Humidity setpoint.................:45.0 %rH
Humidity setpoint corrected.......:45.0 %rH
Dew point.........................:8.6 °C
I-coefficient.....................:0 %
Zone..............................:0
Current temperature...............:19.1 °C
Current humidity..................:62.3 %rH
Dew point.........................:11.7 °C
Air volume flow...................:-
Room temperature..................:Zone:- Unit:19.1 °C min:15.0 °C max:25.0 °C
(active)
Room humidity.....................:Zone:- Unit:62.3 %rH min:5.0 %rH max:90.0 %rH
(active)
Supply air temperature............:Zone:- Unit:- min:5.0 °C max:35.0 °C
Supply air humidity...............:Zone:- Unit:- min:5.0 %rH max:90.0 %rH
Outside air temperature...........:Zone:- Unit:-
Outside air humidity..............:-
Outside air moisture content......:-
Water temperature inlet 1.........:Zone:- Unit:- min:0.0 °C max:0.0 °C
Water temperature inlet 2.........:Zone:- Unit:- min:0.0 °C max:0.0 °C
Water temperature outlet 1........:-
Water temperature outlet 2........:-
ioc 01:>IS 2
Alarmdelay roomtemp too low..........:30 s
Alarmprio roomtemp too low...........:0
Common alarm roomtemp too low........:1
Alarmdelay roomtemp too high.........:30 s
Alarmprio roomtemp too high..........:0
Common alarm roomtemp too high.......:1
ioc 01:>IS 3
Unit start delay..................:0 s (0)
Control type......................:1 (Room air)
Limitation:Start temp.............:16.0 °C
Limitation:Start temp 2...........:0.0 °C
Limitation:Prop temp..............:0.5 K
Limitation:Min temp...............:0.0 °C
Limitation:Max temp...............:40.0 °C
Limitation:Start humidity.........:70.0 %rH
Limitation:Prop humidity..........:0.5 %
Limitation:Humidifier break.......:40.0 %rH
Coolingpriority...................:0 (GE) (0)
Summer/Winter switch..............:16.0 °C
Summer/Winter hysteresis..........:2.0 K
Wintermode........................:0
Outside moist. content minimum....:0.0 g/kg
Outside moist. content hysteresis.:0.0 g/kg
UPS-mode..........................:0
Winter start delay................:180 s
Busaddress........................:1
Global address....................:1
System name.......................:System name
Unit name.........................:SH 9
Air volume flow k-value nozzle....:0
Boost for cooling.................:0.0 K
Boost for humidifying.............:0.0 %rH
Boost for dehumidifying...........:0.0 %rH
OTE mode..........................:1 (STULZ mode)
(Sequencing stop:00000000000000000000)
(Unit running...:00000000000000000000)
Number of faulty
Units for Emergency Oper.:0
Emergency temp...........:16.0 °C
Emergency Operation......:0
Valid alarms:
--.Not available 01.Local stop
04.E-heating failure 05.Humidifier failure
06.Humidifier 5uS 07.Humidifier 20uS
08.Fan error 10.External alarm
11.Pump failure 12.Drycooler failure
13.Water detector 24.Fire/smoke detector
25.Sensor failure 26.Sensor broken
27.Hotgas reheat failure 28.Phase failure
29.BMS stop 1 30.Refrigerant circuit 1
31.Refrigerant circuit 2 32.Refrigerant circuits 1 & 2
ioc 01:>IOBUS 1
Status and configuration of IO-bus
ioc 01:>
STULZ C7000 IO-CONTROL 01 (V6.62)
14:25:48 29.11.2022
ioc 01:>
STULZ C7000 IO-CONTROL 01 (V6.62)
14:27:35 29.11.2022
ioc 01:>