You are on page 1of 19

STULZ C7000 IO-CONTROL 01 (V6.

62)
16:08:29 29.11.2022

ioc 01:>
STULZ C7000 IO-CONTROL 01 (V6.62)
16:08:30 29.11.2022

ioc 01:>
STULZ C7000 IO-CONTROL 01 (V6.62)
16:08:30 29.11.2022

ioc 01:>STULZ C7000 IO-CONTROL 01 (V6.62)


16:08:30 29.11.2022

ioc 01:>AIN
Analog in 00:4
Analog in 01:2210
- Sensor 01 (Room temperature)
Analog in 02:2557
- Sensor 02 (Room humidity)
Analog in 03:4
Analog in 04:4
Analog in 05:1320
Analog in 06:4
Analog in 07:4
Analog in 08:4
Analog in 09:4
Analog in 10:4
Analog in 11:0
Analog in 12:0
Analog in 13:0
Analog in 14:0
Analog in 15:0
Analog in 16:0
Analog in 17:0
Analog in 18:0
Analog in 19:0
Analog in 20:0
Analog in 21:0
ioc 01:>AOUT
Analog out 00:0 (0.0 V)
Analog out 01:3480 (8.5 V)
- Fan 1
Analog out 02:0 (0.0 V)
Analog out 03:0 (0.0 V)
Analog out 04:0 (0.0 V)
Analog out 05:0 (0.0 V)
Analog out 06:0 (0.0 V)
Analog out 07:0 (0.0 V)
Analog out 08:0 (0.0 V)
Analog out 09:0 (0.0 V)
Analog out 10:0 (0.0 V)
Analog out 11:0 (0.0 V)
Analog out 12:0 (0.0 V)
Analog out 13:0 (0.0 V)
Analog out 14:0 (0.0 V)
Analog out 15:0 (0.0 V)
Analog out 16:0 (0.0 V)
Analog out 17:0 (0.0 V)
Analog out 18:0 (0.0 V)
Analog out 19:0 (0.0 V)
Analog out 20:0 (0.0 V)
ioc 01:>DIN
Digital in 00 not active
- Remote on/off
- Fire
- Water
- Phase
- Waterflow
- UPS
- CW off
- Alarm in compressor 2
Digital in 01 active
- Alarm in fan 1
Digital in 02 active
- Highpressure 1
Digital in 03 not active
Digital in 04 not active
Digital in 05 active
- Alarm in filter fan 1
Digital in 06 not active
Digital in 07 not active
Digital in 08 active
- Highpressure 2
Digital in 09 active
- Alarm in LP compressor 2
Digital in 10 not active
Digital in 11 active
Digital in 12 not active
Digital in 13 not active
Digital in 14 not active
Digital in 15 not active
Digital in 16 not active
Digital in 17 not active
Digital in 18 not active
Digital in 19 not active
Digital in 20 not active
Digital in 21 not active
Digital in 22 not active
Digital in 23 not active
Digital in 24 not active
Digital in 25 not active
Digital in 26 not active
Digital in 27 not active
Digital in 28 not active
Digital in 29 not active
Digital in 30 not active
Digital in 31 not active
Digital in 32 not active
Digital in 33 not active
Digital in 34 not active
Digital in 35 not active
Digital in 36 not active
Digital in 37 not active
Digital in 38 not active
Digital in 39 not active
Digital in 40 not active
Digital in 41 not active
Digital in 42 not active
Digital in 43 not active
ioc 01:>DOUT
Digital out 00 active
- Wintermode
- BMS stop 1
- Local Stop
- Unit on/off
- EC-fan running
- Free Cooling
- Alarmprio fan 1
- Alarmprio filter fan 1
- Alarmprio compressor 2
- Alarmprio LP compressor 2
- Alarmprio sensor 01
- Alarmprio break sensor 01
- Alarmprio sensor 02
- Alarmprio break sensor 02
- Alarmprio temp sensor EEV 02
- Alarmprio pressure sensor EEV 02
- Alarmprio motor EEV 02
- Alarmprio EVD not available
- Alarmprio fire
- Alarmprio water
- Alarmprio phase
- Alarmprio waterflow
- Alarmprio highpressure 1
- Alarmprio highpressure 2
- Alarmprio busalarm
- Alarmprio addressconflict
- Alarmprio roomtemp too high
- Alarmprio roomtemp too low
- Alarmprio roomhumidity too high
- Alarmprio roomhumidity too low
- Alarmprio supplytemp too high
- Alarmprio supplytemp too low
- Alarmprio supplyhumidity too high
- Alarmprio supplyhumidity too low
- Alarmprio Watertemp. inlet 1 too high
- Alarmprio Watertemp. inlet 1 too low
- Alarmprio Watertemp. inlet 2 too high
- Alarmprio Watertemp. inlet 2 too low
- Alarmprio Pre-alarm: Supply air pressure too low
- Alarmprio Supply air pressure too low
- Alarmprio Pre-alarm: Supply air pressure too high
- Alarmprio Supply air pressure too high
- ICC Alarmpriority not available
- ICC Alarmpriority icc Error
- ICC Alarmpriority low pressure
- Ref block valve 1
- Ref block valve 2
Digital out 01 active
- Fan 1
Digital out 02 not active
Digital out 03 not active
Digital out 04 not active
Digital out 05 not active
Digital out 06 not active
- Common alarm
Digital out 07 not active
- Compressor 2
Digital out 08 not active
Digital out 09 not active
Digital out 10 not active
Digital out 11 not active
Digital out 12 not active
Digital out 13 not active
Digital out 14 not active
Digital out 15 not active
Digital out 16 not active
Digital out 17 not active
Digital out 18 not active
Digital out 19 not active
Digital out 20 not active
Digital out 21 not active
Digital out 22 not active
Digital out 23 not active
Digital out 24 not active
Digital out 25 not active
Digital out 26 not active
Digital out 27 not active
Digital out 28 not active
Digital out 29 not active
Digital out 30 not active
Digital out 31 not active
ioc 01:>EQUIP
Compressors.................:2
Suctionvalve................:0
HGBP........................:0
EEV.........................:1
GE/CW-valve.................:0
ECO-COOL louver.............:0
AE-louvers..................:0
G-valve.....................:0
Condenser fan...............:0
Humidifier..................:0
Dehumidifier valve..........:0
Dehumidifier hotgas bypass..:0
Drycooler...................:0
Pumps.......................:0
E-heating...................:0
Hotgas reheating............:0
PWW-heating.................:0
Fan.........................:1
Louver......................:0
Sensors.....................:2
Ext Alarm in................:0
Digital extension card......:0
Analoge extension card......:0
EEV extension card..........:0
Bus extension card..........:1
ICC.........................:1
Refrigerant block valve.....:0

ioc 01:>STATUS
Unit:Running
- Runtime:17474 h
- Stoptime:82 h

- Fan 1:85 %

Cooling:active (12358 h)
- ICC 1:69.0 %

Heating:not active (0 h)

Humidification:not active (0 h)

Dehumidification:not active (933 h)

Alarms:

ioc 01:>COMP 1
Compressor 1
Configured..................:0
Digital out.................:2
Digital alarm in............:0
Alarmpriority...............:0
Common alarm................:1
Alarmdelay..................:5 s
Digital alarm in low press..:3
Alarmpriority low press.....:0
Common alarm low press......:1
Alarmdelay low press........:5 s

Type........................:1
Start temperature summer....:0.4 K
Stop hysteresis summer......:0.7 K
Start temperature winter....:0.7 K
Stop hysteresis winter......:0.7 K
Minimum runtime.............:180 s
Pause.......................:180 s

LP management time..........:0 h
LP management min press.....:5.0 bar
LP management tries.........:0
HP management time..........:0 h (0)
HP management max press.....:21.0 bar
HP management tries.........:0
HP management mode..........:0

ASTP threshold..............:0.0 bar


ASTP hysteresis.............:0.0 bar

Runtime.....................:0 h
Manual operation............:0
Manual on...................:0

On..........................:0 (0/0)
Alarm.......................:0
Alarm low press.............:0

ioc 01:>COMP 2
Compressor 2
Configured..................:1
Digital out.................:7
Digital alarm in............:0
Alarmpriority...............:0
Common alarm................:1
Alarmdelay..................:5 s
Digital alarm in low press..:9
Alarmpriority low press.....:0
Common alarm low press......:1
Alarmdelay low press........:5 s

Type........................:1
Start temperature summer....:2.0 K
Stop hysteresis summer......:0.5 K
Start temperature winter....:0.9 K
Stop hysteresis winter......:0.7 K
Minimum runtime.............:180 s
Pause.......................:180 s

LP management time..........:0 h
LP management min press.....:5.0 bar
LP management tries.........:0
HP management time..........:0 h (0)
HP management max press.....:21.0 bar
HP management tries.........:0
HP management mode..........:0

ASTP threshold..............:0.0 bar


ASTP hysteresis.............:0.0 bar

Runtime.....................:364 h
Manual operation............:0
Manual on...................:0

On..........................:0 (1/4)
Alarm.......................:0
Alarm low press.............:0

ioc 01:>EEV 1
EEV 1
Configured.........................:0
Controller.........................:1 (EVD)

Net id.............................:198
Availability.......................:100 %
Alarmpriority availability.........:0
Common alarm availability..........:0

Refrigerant........................:4 (R407C)
MOP temperature....................:30.0 °C
Superheat setpoint.................:7.0 K
Dehumidification superheat setpoint:12.0 K
Current superheat setpoint.........:7.0 K
Start-up opening...................:50 %
Valve type.........................:1 (CAREL EXV)
Valve steps........................:480
Sensortype Evaporating pressure....:3 (-1...9.3bar)
Alarmpriority pressure.............:0
Common alarm pressure..............:0
Alarmpriority Temp.................:0
Common alarm temp..................:0
Alarmpriority motor................:0
Common alarm motor.................:0
Manual operation...................:0
Manual on..........................:0.00 %

Control active.....................:0
Alarm availability.................:0
Suction pressure...................:0.0 bar
Saturation temperature.............:0.0 °C
Coil out temperature...............:0.0 °C
Superheat..........................:0.0 K

Valve opening......................:0.0 %

Pressure sensor error..............:0


Temperature sensor error...........:0
Stepper motor error................:0

ioc 01:>EEV 2
EEV 2
Configured.........................:1
Controller.........................:1 (EVD)

Net id.............................:198
Availability.......................:100 %
Alarmpriority availability.........:0
Common alarm availability..........:0

Refrigerant........................:5 (R410A)
MOP temperature....................:30.0 °C
Superheat setpoint.................:7.0 K
Dehumidification superheat setpoint:12.0 K
Current superheat setpoint.........:7.0 K
Start-up opening...................:50 %
Valve type.........................:1 (CAREL EXV)
Valve steps........................:480
Sensortype Evaporating pressure....:4 (0...17.3bar)
Alarmpriority pressure.............:0
Common alarm pressure..............:0
Alarmpriority Temp.................:0
Common alarm temp..................:0
Alarmpriority motor................:0
Common alarm motor.................:0
Manual operation...................:0
Manual on..........................:0.00 %

Control active.....................:1
Alarm availability.................:0
Suction pressure...................:9.5 bar
Saturation temperature.............:8.8 °C
Coil out temperature...............:20.7 °C
Superheat..........................:11.9 K
Valve opening......................:55.2 %

Pressure sensor error..............:0


Temperature sensor error...........:0
Stepper motor error................:0

ioc 01:>ICC 1
Integrated Cooling Circuit 1

Configured..................................................:1
Modbus Address..............................................:1
Compressor Pmin limit.......................................:30.0 %
Compressor Pmax limit.......................................:70.0 %
Start temperature offset....................................:1.0 K
Hysteresis..................................................:2.5 K
Low after start.............................................:240 s
Low after dehumi............................................:240 s
pressure equalize threshold.................................:0.0 bar
pressure equalize opening grade.............................:0.0 %
pressure equalize period....................................:0 s
compressor minimum speed while dehumidification.............:100.0 %

P-coefficient...............................................:10
I-coefficient...............................................:40
D-coefficient...............................................:0

Common alarm availability...................................:0


Alarmpriority availability..................................:0
Common alarm icc............................................:0
Alarmpriority icc...........................................:0
Common alarm low pressure...................................:0
Alarmpriority low pressure..................................:0

Runtime.....................................................:12357 h

Availability................................................:100 % (10|0|0|0)

Manual operation............................................:0
Manual on...................................................:0.0 %

( 8) suction temperature - EE valve........................:21.4 °C


( 5) suction pressure......................................:9.1 bar
( 9) Evaporation temperature - EE valve....................:7.4 °C
( 4) discharge gas temperature.............................:40.8 °C
( 6) discharge pressure....................................:25.5 bar
( 10) Condensing temperature - EE valve.....................:44.0 °C
( 11) Superheat - EE valve..................................:14.0 K
( 53) Setpoint superheat - EE valve.........................:10.0 K
(220) EE valve position.....................................:91.8 %
(219) Envelope working zone.................................:1
(226) Compressor model......................................:3 (ANB52F-400V)

( 7) Speed request to inverter (filtered by envelop).......:60.1 %


( 16) Compressor rotor speed (rps)..........................:76.2
( 17) Compressor rotor speed (%)............................:63.5 %
( 30) Compressor power request (%)..........................:32.9 %
ioc 01:>FAN 1
Fan 1
Configured.....................:1
Analog out.....................:1
Digital out....................:1
Digital alarm in...............:1
Alarmpriority..................:0
Common alarm...................:1
Alarmdelay.....................:10 s

Type...........................:2 (continuous)
Minimum speed..................:70 %
nMin CW Dual Fluid.............:50 %
nMax...........................:85 %
nMax CW Dual Fluid.............:85 %
nMax EFC (DFC).................:85 %
Offset.........................:0 %
Pre runtime....................:10 s (0)
After runtime..................:60 s (60)
Start temperature..............:0.0 K
Start speed....................:0 %
DTC start temperature diff.....:10.0 K
DTC temperature range..........:0.0 K
DTC type.......................:0
100% start runtime.............:5 s
Reduce time....................:30 min (30)
Reduce speed...................:0 %
Time until dehumi reduction....:0 min (0 sec)
Reduce dehumidification........:0 %
Reduce UPS.....................:0 %
Filteralarmoffset..............:0 %
Start emergency................:0.0 K
End emergency..................:0.0 K
nMax emergency.................:0 %
Control cycle..................:5 s
Max adjust.....................:2 %
Control factor.................:40
P-coefficient..................:10
I-coefficient..................:40
D-coefficient..................:0
Stop on cooling error..........:0

Runtime........................:17473 h
Manual operation...............:0
Manual on......................:0 %

On.............................:85 % (21)
Alarm..........................:0

Digital Alarm in Filter........:5


Max pressure drop filter.......:0 Pa
Alarmpriority filter...........:0
Commonalarm filter.............:1
Alarmdelay filter..............:20 s

Alarm filter...................:0
ioc 01:>SEN 1
Configured..................:1
Analog in...................:1
Type........................:1 (Current)
Min output value............:4.0 mA
Max output value............:20.0 mA
Alarmpriority sensor break..:0
Commonalarm sensor break....:1
Alarmdelay sensor break.....:5 s

Use.........................:1 (Room temperature)


Min messure value...........:0.0 °C
Max messure value...........:50.0 °C
Trim offset.................:0.0 K
Max diverge.................:10 %
Alarmpriority...............:0
Common alarm................:1
Alarmdelay..................:5 s

BMS value active............:0


BMS value...................:0.0 °C
Manual operation............:0
Manual on...................:0.0 °C

Current value...............:21.5 °C (10.9 mA)


Sensor break................:0
Alarm.......................:0

ioc 01:>SEN 2
Configured..................:1
Analog in...................:2
Type........................:1 (Current)
Min output value............:4.0 mA
Max output value............:20.0 mA
Alarmpriority sensor break..:0
Commonalarm sensor break....:1
Alarmdelay sensor break.....:5 s

Use.........................:2 (Room humidity)


Min messure value...........:0.0 %rH
Max messure value...........:100.0 %rH
Trim offset.................:0.0 %rH
Max diverge.................:10 %
Alarmpriority...............:0
Common alarm................:1
Alarmdelay..................:5 s

BMS value active............:0


BMS value...................:0.0 %rH
Manual operation............:0
Manual on...................:0.0 %rH

Current value...............:53.7 %rH (12.6 mA)


Sensor break................:0
Alarm.......................:0
ioc 01:>IOBUS 1
Status and configuration of IO-bus

ID glob.adr. dev.type reliab. config.


0 - AdvancedTerminal 100% 1
1 1 IO-Controller me 1
2 - unknown 0% 0
3 - unknown 0% 0
4 - unknown 0% 0
5 - unknown 0% 0
6 - unknown 0% 0
7 - unknown 0% 0
8 - unknown 0% 0
9 - unknown 0% 0
10 - unknown 0% 0
11 - unknown 0% 0
12 - unknown 0% 0
13 - unknown 0% 0
14 - unknown 0% 0
15 - unknown 0% 0
16 - unknown 0% 0
17 - unknown 0% 0
18 - unknown 0% 0
19 - unknown 0% 0
ioc 01:>IS 1
Temperature setpoint..............:21.0 °C
Temperature setpoint corrected....:21.0 °C
Night temperature setpoint........:27.0 °C
Humidity setpoint.................:50.0 %rH
Humidity setpoint corrected.......:50.0 %rH
Dew point.........................:10.1 °C
I-coefficient.....................:0 %
Zone..............................:0
Current temperature...............:21.5 °C
Current humidity..................:53.7 %rH
Dew point.........................:11.7 °C
Air volume flow...................:-
Room temperature..................:Zone:- Unit:21.5 °C min:5.0 °C max:35.0 °C
(active)
Room humidity.....................:Zone:- Unit:53.8 %rH min:5.0 %rH max:85.0 %rH
(active)
Supply air temperature............:Zone:- Unit:- min:5.0 °C max:35.0 °C
Supply air humidity...............:Zone:- Unit:- min:5.0 %rH max:90.0 %rH
Outside air temperature...........:Zone:- Unit:-
Outside air humidity..............:-
Outside air moisture content......:-
Water temperature inlet 1.........:Zone:- Unit:- min:-20.0 °C max:45.0 °C
Water temperature inlet 2.........:Zone:- Unit:- min:-20.0 °C max:45.0 °C
Water temperature outlet 1........:-
Water temperature outlet 2........:-

Condensation pressure 1 setp. mix.:12.0 bar


Condensation pressure 1 setp. DX..:18.0 bar
Condensation pressure 1 setp. dyn.:-
Condensation pressure 1...........:24.7 bar
Hotgas temperature 1..............:40.9 °C
Evaporation pressure 1............:9.9 bar
Suction gas temperature 1.........:21.4 °C
Condensation pressure 2 setp. mix.:12.0 bar
Condensation pressure 2 setp. DX..:18.0 bar
Condensation pressure 2 setp. dyn.:-
Condensation pressure 2...........:-
Hotgas temperature 2..............:-
Evaporation pressure 2............:6.6 bar
Suction gas temperature 2.........:17.8 °C

Supply air pressure setpoint......:0.00 Pa


Supply air pressure...............:Zone:- Unit:- min:0.00 Pa max:100.00 Pa
Room pressure setpoint............:0 Pa
Room pressure.....................:Zone:- Unit:-
Water pressure setpoint...........:0.0 bar
Water pressure....................:-
Water volume flow.................:-
Water volume flow 2...............:-
Water volume flow 3...............:-

ioc 01:>IS 2
Alarmdelay roomtemp too low..........:30 s
Alarmprio roomtemp too low...........:0
Common alarm roomtemp too low........:1
Alarmdelay roomtemp too high.........:30 s
Alarmprio roomtemp too high..........:0
Common alarm roomtemp too high.......:1

Alarmdelay roomhumidity too low......:30 s


Alarmprio roomhumidity too low.......:0
Common alarm roomhumidity too low....:1
Alarmdelay roomhumidity too high.....:30 s
Alarmprio roomhumidity too high......:0
Common alarm roomhumidity too high...:1

Alarmdelay supplytemp too low........:30 s


Alarmprio supplytemp too low.........:0
Common alarm supplytemp too low......:1
Alarmdelay supplytemp too high.......:30 s
Alarmprio supplytemp too high........:0
Common alarm supplytemp too high.....:1

Alarmdelay supplyhumidity too low....:30 s


Alarmprio supplyhumidity too low.....:0
Common alarm supplyhumidity too low..:1
Alarmdelay supplyhumidity too high...:30 s
Alarmprio supplyhumidity too high....:0
Common alarm supplyhumidity too high.:1

Watertemp. inlet 1 too low


Alarmdelay...........................:30 s
Alarmpriority........................:0
Common alarm.........................:1

Watertemp. inlet 1 too high


Alarmdelay...........................:30 s
Alarmpriority........................:0
Common alarm.........................:1

Watertemp. inlet 2 too low


Alarmdelay...........................:30 s
Alarmpriority........................:0
Common alarm.........................:1

Watertemp. inlet 2 too high


Alarmdelay...........................:30 s
Alarmpriority........................:0
Common alarm.........................:1

Pre-alarm: Supply air pressure too low


Alarmdelay...........................:30 s
Alarmpriority........................:0
Common alarm.........................:1

Supply air pressure too low


Alarmdelay...........................:30 s
Alarmpriority........................:0
Common alarm.........................:1

Pre-alarm: Supply air pressure too high


Alarmdelay...........................:30 s
Alarmpriority........................:0
Common alarm.........................:1

Supply air pressure too high


Alarmdelay...........................:30 s
Alarmpriority........................:0
Common alarm.........................:1

ioc 01:>IS 3
Unit start delay..................:0 s (0)
Control type......................:1 (Room air)
Limitation:Start temp.............:16.0 °C
Limitation:Start temp 2...........:0.0 °C
Limitation:Prop temp..............:0.5 K
Limitation:Min temp...............:0.0 °C
Limitation:Max temp...............:40.0 °C
Limitation:Start humidity.........:70.0 %rH
Limitation:Prop humidity..........:0.5 %
Limitation:Humidifier break.......:40.0 %rH
Coolingpriority...................:0 (GE) (0)
Summer/Winter switch..............:16.0 °C
Summer/Winter hysteresis..........:2.0 K
Wintermode........................:0
Outside moist. content minimum....:0.0 g/kg
Outside moist. content hysteresis.:0.0 g/kg
UPS-mode..........................:0
Winter start delay................:180 s
Busaddress........................:1
Global address....................:1
System name.......................:System name
Unit name.........................:Unit name
Air volume flow k-value nozzle....:0
Boost for cooling.................:0.0 K
Boost for humidifying.............:0.0 %rH
Boost for dehumidifying...........:0.0 %rH
OTE mode..........................:1 (STULZ mode)
Protocol..........................:1 (SCP for WIB/NMC)
Datapointlist.....................:1 (Classic)

Global alarm digital out..........:6


Winter operation digital out......:0
Free Cooling digital out..........:0
BMS stop 1 digital out............:0
Local Stop digital out............:0
Unit on/off digital out...........:0
EC-fan running digital out........:0
UPS-operation digiLOtal in..........:0
CW cooling off digital in.........:0

ioc 01:>LOG 1 1
STULZ C7000 IO-CONTROL 01 (V6.62)
16:09:50 29.11.2022

ioc 01:>LOG 2 1
0001. 29.11.2022 16:07:00 54.1 %rH
0002. 29.11.2022 16:02:00 55.8 %rH
0003. 29.11.2022 15:57:00 56.0 %rH
0004. 29.11.2022 15:52:01 56.3 %rH
0005. 29.11.2022 15:47:00 56.4 %rH
0006. 29.11.2022 15:42:00 57.0 %rH
0007. 29.11.2022 15:37:00 57.7 %rH
0008. 29.11.2022 15:32:01 58.6 %rH
0009. 29.11.2022 15:27:00 58.0 %rH
0010. 29.11.2022 15:22:00 55.2 %rH
0011. 29.11.2022 15:17:00 55.1 %rH
0012. 29.11.2022 15:12:00 55.3 %rH
0013. 29.11.2022 15:07:01 56.2 %rH
0014. 29.11.2022 15:02:00 56.3 %rH
0015. 29.11.2022 14:57:00 57.0 %rH
0016. 29.11.2022 14:52:00 57.5 %rH
0017. 29.11.2022 14:47:00 56.3 %rH
0018. 29.11.2022 14:42:00 55.2 %rH
0019. 29.11.2022 14:37:00 54.9 %rH
0020. 29.11.2022 14:32:00 54.5 %rH

ioc 01:>ZONE 1
Sequencing time..............:0 h (0 min)
5 minutes testsequencing.....:0
Room temperature.............:-
Room humidity................:-
Supply air temperature.......:-
Supply air humidity..........:-
Outside air temperature......:-
Water temperature 1/2........:-/-
T/H averaging................:1
T/H averaging delay..........:120 s
Supply air pressure..........:-
Supply air press. selection..:1
Room pressure................:-
Room pressure averaging......:1
Stopped units in averaging...:0
GE start temp. air absolute..:18.0 °C (0/0)
GE start temp. air relative..:0.0 K
GE hysteresis air............:0.0 K
GE start temp. water absolute:10.0 °C
GE start temp. water relative:0.0 K
GE hysteresis water..........:0.0 K
nMax (SAPSM).................:0 %
nMax.........................:85 %
CW-Energysave mode...........:0

(Sequencing stop:00000000000000000000)
(Unit running...:00000000000000000000)

Number of faulty
Units for Emergency Oper.:0
Emergency temp...........:16.0 °C
Emergency Operation......:0

Valid alarms:
--.Not available 01.Local stop
04.E-heating failure 05.Humidifier failure
06.Humidifier 5uS 07.Humidifier 20uS
08.Fan error 10.External alarm
11.Pump failure 12.Drycooler failure
13.Water detector 24.Fire/smoke detector
25.Sensor failure 26.Sensor broken
27.Hotgas reheat failure 28.Phase failure
29.BMS stop 1 30.Refrigerant circuit 1
31.Refrigerant circuit 2 32.Refrigerant circuits 1 & 2

ioc 01:>E
001. 28.11.2022 10:26:03 Unit start
002. 28.11.2022 10:26:03 no Local Stop
003. 28.11.2022 10:22:46 Unit switch on
004. 28.11.2022 09:06:59 Unit switch off
005. 28.11.2022 09:04:12 Unit stop
006. 28.11.2022 09:04:11 Local Stop
007. 13.11.2022 22:30:35 Automatic alarmreset to uPC
008. 13.11.2022 22:27:03 (37) Alarm state that shut off compressor (envelop
alarms not included)
009. 13.11.2022 22:27:03 (35) General Inverter Alarm
010. 13.11.2022 22:27:03 (15) Alarm state that shut off compressor (included
envelop alarms)
011. 13.11.2022 22:27:03 inverter 4: Undervoltage
012. 09.11.2022 14:11:53 Unit start
013. 09.11.2022 14:11:53 no Local Stop
014. 09.11.2022 13:39:35 Unit stop
015. 09.11.2022 13:39:32 Local Stop
016. 26.10.2022 14:08:35 Alarmreset to uPC
017. 26.10.2022 14:08:34 Alarmreset
018. 26.10.2022 14:08:28 (37) Alarm state that shut off compressor (envelop
alarms not included)
019. 26.10.2022 14:08:28 (15) Alarm state that shut off compressor (included
envelop alarms)
020. 26.10.2022 14:08:21 Air flow failure 1
021. 26.10.2022 13:58:21 Unit start
022. 26.10.2022 13:58:20 no Local Stop
023. 26.10.2022 13:58:16 Unit switch on
024. 26.10.2022 12:41:24 Unit switch off
025. 26.10.2022 12:40:26 Unit stop
026. 26.10.2022 12:40:19 Local Stop
027. 26.10.2022 12:40:17 Unit start
028. 26.10.2022 12:40:16 no Local Stop
029. 26.10.2022 12:40:14 Unit stop
030. 26.10.2022 12:40:13 Local Stop
031. 26.10.2022 10:47:10 Unit start
032. 26.10.2022 10:47:10 no Local Stop
033. 26.10.2022 10:47:05 Unit switch on
034. 26.10.2022 09:15:52 Unit switch off
035. 26.10.2022 08:43:14 Unit stop
036. 26.10.2022 08:43:14 Local Stop
037. 19.10.2022 09:41:43 Unit switch on
038. 19.10.2022 08:59:45 Unit switch off
039. 19.10.2022 08:53:57 Alarmreset to uPC
040. 19.10.2022 08:53:56 Alarmreset
041. 19.10.2022 08:53:54 Alarmreset to uPC
042. 19.10.2022 08:53:53 Alarmreset
043. 11.10.2022 17:53:35 Low pressure 2 failure
044. 07.10.2022 08:32:56 Alarmreset to uPC
045. 07.10.2022 08:32:54 Alarmreset
046. 07.10.2022 08:32:52 Alarmreset to uPC
047. 07.10.2022 08:32:51 Alarmreset
048. 26.09.2022 16:25:28 Low pressure 2 failure
049. 26.09.2022 15:56:22 Alarmreset to uPC
050. 26.09.2022 15:56:21 Alarmreset
051. 26.09.2022 15:56:19 Alarmreset to uPC
052. 26.09.2022 15:56:18 Alarmreset
053. 26.09.2022 14:30:39 (37) Alarm state that shut off compressor (envelop
alarms not included)
054. 26.09.2022 14:30:39 (15) Alarm state that shut off compressor (included
envelop alarms)
055. 26.09.2022 14:30:33 Air flow failure 1
056. 06.09.2022 16:49:33 Low pressure 2 failure
057. 25.08.2022 14:21:36 Alarmreset to uPC
058. 25.08.2022 14:21:35 Alarmreset
059. 25.08.2022 14:21:33 Alarmreset to uPC
060. 25.08.2022 14:21:32 Alarmreset
061. 23.08.2022 14:48:38 Low pressure 2 failure
062. 22.08.2022 15:48:45 Unit start
063. 22.08.2022 15:48:45 no Local Stop
064. 19.08.2022 10:44:33 Unit stop
065. 19.08.2022 10:44:32 Local Stop
066. 05.08.2022 10:37:48 Alarmreset to uPC
067. 05.08.2022 10:37:47 Alarmreset
068. 05.08.2022 10:37:45 Alarmreset to uPC
069. 05.08.2022 10:37:44 Alarmreset
070. 24.07.2022 19:05:38 Low pressure 2 failure
071. 11.07.2022 11:26:17 Unit start
072. 11.07.2022 11:26:17 no Local Stop
073. 11.07.2022 11:26:10 Unit switch on
074. 11.07.2022 10:57:54 Unit switch off
075. 11.07.2022 10:57:52 Unit stop
076. 11.07.2022 10:57:52 Local Stop
077. 11.07.2022 10:57:17 Alarmreset to uPC
078. 11.07.2022 10:57:16 Alarmreset
079. 08.06.2022 15:25:32 Low pressure 2 failure
080. 06.06.2022 12:03:10 Unit start
081. 06.06.2022 12:03:10 no Local Stop
082. 06.06.2022 12:34:27 Unit stop
083. 06.06.2022 12:34:24 Local Stop
084. 06.06.2022 12:12:23 no Local Stop
085. 06.06.2022 12:12:20 Unit start
086. 06.06.2022 11:47:29 Unit stop
087. 06.06.2022 11:47:29 Local Stop
088. 18.05.2022 14:22:51 Unit switch on
089. 18.05.2022 14:20:17 Unit switch off
090. 22.03.2022 11:15:34 Unit start
091. 22.03.2022 11:15:34 no Local Stop
092. 22.03.2022 11:15:03 Unit switch on
093. 22.03.2022 10:14:50 Unit switch off
094. 22.03.2022 10:14:49 Unit stop
095. 22.03.2022 10:14:46 Unit start
096. 22.03.2022 10:14:43 Unit stop
097. 22.03.2022 10:14:40 Local Stop
098. 15.02.2022 14:15:38 Unit start
099. 15.02.2022 14:15:38 no Local Stop
100. 15.02.2022 14:15:10 Unit switch on
101. 15.02.2022 13:55:45 Unit switch off
102. 15.02.2022 13:55:41 Unit stop
103. 15.02.2022 13:55:41 Local Stop
104. 15.02.2022 13:20:56 Unit start
105. 15.02.2022 13:20:56 no Local Stop
106. 15.02.2022 13:20:39 Unit switch on
107. 15.02.2022 13:02:05 Unit switch off
108. 15.02.2022 13:01:29 Unit stop
109. 15.02.2022 13:01:29 Local Stop
110. 10.12.2021 10:53:28 Unit switch on
111. 10.12.2021 10:51:17 Unit switch off
112. 10.12.2021 10:38:05 Unit switch on
113. 10.12.2021 10:26:57 Unit switch off
114. 10.12.2021 10:26:42 Unit switch on
115. 10.12.2021 10:26:29 Unit switch off
116. 18.10.2021 13:22:12 Unit start
117. 18.10.2021 13:22:12 no Local Stop
118. 18.10.2021 13:21:25 Unit switch on
119. 18.10.2021 13:20:08 Unit switch off
120. 18.10.2021 13:20:06 Unit stop
121. 18.10.2021 13:20:06 Local Stop
122. 18.10.2021 13:19:53 Unit switch on
123. 18.10.2021 10:25:52 Unit switch off
124. 20.09.2021 13:39:17 Low pressure 2 failure
125. 26.08.2021 13:59:05 Alarmreset to uPC
126. 26.08.2021 13:59:05 Alarmreset
127. 12.08.2021 08:34:08 Low pressure 2 failure
128. 29.06.2021 12:17:21 Unit start
129. 29.06.2021 12:17:21 no Local Stop
130. 29.06.2021 12:16:19 Unit switch on
131. 29.06.2021 11:00:01 Unit switch off
132. 29.06.2021 11:00:00 Unit stop
133. 29.06.2021 11:00:00 Local Stop
134. 27.06.2021 11:35:41 Low pressure 2 failure
135. 03.06.2021 17:15:12 Unit switch on
136. 03.06.2021 15:17:48 Unit switch off
137. 03.06.2021 15:17:03 Air flow failure 1
138. 03.06.2021 15:16:49 (37) Alarm state that shut off compressor (envelop
alarms not included)
139. 03.06.2021 15:16:49 (15) Alarm state that shut off compressor (included
envelop alarms)
140. 03.06.2021 15:16:48 inverter 4: Undervoltage
141. 03.06.2021 15:16:48 (35) General Inverter Alarm
142. 03.06.2021 15:02:39 Automatic alarmreset to uPC
143. 03.06.2021 14:59:08 (37) Alarm state that shut off compressor (envelop
alarms not included)
144. 03.06.2021 14:59:08 (15) Alarm state that shut off compressor (included
envelop alarms)
145. 03.06.2021 14:59:07 inverter 4: Undervoltage
146. 03.06.2021 14:59:06 (35) General Inverter Alarm
147. 03.06.2021 14:57:54 Unit switch on
148. 03.06.2021 14:57:50 Unit switch off
149. 12.05.2021 13:41:31 Unit start
150. 12.05.2021 13:41:31 no Local Stop
151. 12.05.2021 13:41:16 Unit switch on
152. 12.05.2021 12:44:53 Unit switch off
153. 12.05.2021 12:37:37 Unit stop
154. 12.05.2021 12:37:37 Local Stop
155. 01.04.2021 12:02:42 Unit start
156. 01.04.2021 12:02:42 no Local Stop
157. 01.04.2021 10:59:49 Unit stop
158. 01.04.2021 10:59:46 Local Stop
159. 30.03.2021 11:19:28 Unit start
160. 30.03.2021 11:19:28 no Local Stop
161. 30.03.2021 11:14:47 Unit stop
162. 30.03.2021 11:14:46 Local Stop
163. 30.03.2021 10:46:28 Unit start
164. 30.03.2021 10:46:28 no Local Stop
165. 30.03.2021 10:44:49 Alarmreset to uPC
166. 30.03.2021 10:44:49 Alarmreset
167. 30.03.2021 10:44:47 Alarmreset to uPC
168. 30.03.2021 10:44:46 Alarmreset
169. 30.03.2021 10:36:24 (36) Communication loss with Power + Inverter
170. 30.03.2021 10:35:34 (37) Alarm state that shut off compressor (envelop
alarms not included)
171. 30.03.2021 10:35:34 (35) General Inverter Alarm
172. 30.03.2021 10:35:34 (15) Alarm state that shut off compressor (included
envelop alarms)
173. 30.03.2021 10:35:33 inverter 4: Undervoltage
174. 30.03.2021 10:33:02 Unit stop
175. 30.03.2021 10:33:01 Local Stop
176. 24.03.2021 18:46:47 Automatic alarmreset to uPC
177. 24.03.2021 18:43:13 (37) Alarm state that shut off compressor (envelop
alarms not included)
178. 24.03.2021 18:43:13 (35) General Inverter Alarm
179. 24.03.2021 18:43:13 (15) Alarm state that shut off compressor (included
envelop alarms)
180. 24.03.2021 18:43:12 inverter 4: Undervoltage
181. 24.03.2021 18:06:36 Automatic alarmreset to uPC
182. 24.03.2021 18:03:05 (37) Alarm state that shut off compressor (envelop
alarms not included)
183. 24.03.2021 18:03:05 (15) Alarm state that shut off compressor (included
envelop alarms)
184. 24.03.2021 18:03:03 (35) General Inverter Alarm
185. 24.03.2021 18:03:03 inverter 4: Undervoltage
186. 19.03.2021 15:04:50 Unit start
187. 19.03.2021 15:04:49 no Local Stop
188. 19.03.2021 14:55:29 Unit switch on
189. 19.03.2021 14:55:21 Unit switch off
190. 19.03.2021 14:54:21 Unit switch on
191. 19.03.2021 14:52:10 Unit switch off
192. 19.03.2021 14:48:38 Unit stop
193. 19.03.2021 14:48:38 Local Stop
194. 18.03.2021 10:41:57 Unit start
195. 18.03.2021 10:41:56 no Local Stop
196. 18.03.2021 10:41:12 Unit switch on
197. 18.03.2021 10:41:01 Unit switch off
198. 18.03.2021 10:38:05 Unit stop
199. 18.03.2021 10:38:01 Local Stop
200. 18.03.2021 10:36:59 Unit start
Latest event..:28.11.2022 10:26:03
Oldest event..:18.03.2021 10:36:59

ioc 01:>

STULZ C7000 IO-CONTROL 01 (V6.62)


16:10:30 29.11.2022

ioc 01:>STULZ C7000 IO-CONTROL 01 (V6.62)


16:10:31 29.11.2022

ioc 01:>STULZ C7000 IO-CONTROL 01 (V6.62)


16:10:31 29.11.2022

ioc 01:>