SUMMARY OF TEST RESULT

TRANSFORMER INSULATION RESISTANCE TEST RESULT

DEC.16,2022 300 KVA TRANSFORMER 3RD LEVEL E-1 EE ROOM


A B C REMARKS
HIGH TO LOW VOLTAGE 100 M ohms 100 M ohms 100 M ohms PASS
HIGH( V ) TO GROUND 100 M ohms 100 M ohms 100 M ohms PASS
DEC.17,2022 500 KVA TRANSFORMER 2ND LEVEL E-1 EE ROOM
A B C REMARKS
HIGH TO LOW VOLTAGE 200 M ohms 200 M ohms 200 M ohms PASS
HIGH( V ) TO GROUND 200 M ohms 200 M ohms 200 M ohms PASS
DEC.18,2022 400 KVA TRANSFORMER 2ND LEVEL E-1 EE ROOM
A B C REMARKS
HIGH TO LOW VOLTAGE 100 M ohms 100 M ohms 100 M ohms PASS
HIGH( V ) TO GROUND 100 M ohms 100 M ohms 100 M ohms PASS
DEC.19,2022 200 KVA TRANSFORMER UPPER 3RD E-1 EE ROOM
A B C REMARKS
HIGH TO LOW VOLTAGE 160 M ohms 160 M ohms 160 M ohms PASS
HIGH( V ) TO GROUND 160 M ohms 160 M ohms 160 M ohms PASS
DEC.20,2022 500 KVA TRANSFORMER 3RD LEVEL E-2 EE ROOM
A B C REMARKS
HIGH TO LOW VOLTAGE 0 M ohms 0 M ohms 0 M ohms FAIL
HIGH( V ) TO GROUND 0 M ohms 0 M ohms 0 M ohms FAIL

TESTED BY: ENGR. ARESTHY S. BOCADO REE

ENGR. LLOYD A. SEMILLA