You are on page 1of 1

MEP COMPARISON SHEET - ELECTRICAL LOAD DENSITY

Pre- Concept (
Concept- MEP BOD ( Previous Development (
Description 30.04.2020 & BUJAIRI F&B ( ARCADIS) DGDA Recommendation Remarks
12.07.2020) ( AECOM) UAE)
17.06.2020) (ATKINS)

Retail ( 0-70 m2) 14 KW 12 KW NA 200 W/m2 200 W/m2 AECOM to confirm the
Load calcullation
Retail ( 71-150 m2) 170 W/m2 160 W/m2 NA 200 W/m2 200 W/m2 strategy.( Line Units,
Anchors, F&B etc) based
Retail ( 151-400 m2) 150 W/m2 140 W/m2 NA 200 W/m2 200 W/m2
on which DGDA
Retail ( 401-600 m2) 120 W/m2 100 W/m2 NA 200 W/m2 150 W/m2 recommendation to be
evaluated and final figure
Retail ( 600 - 1000 m2) 100 W/m2 80 W/m2 NA 200 W/m2 150 W/m2 to be derived.

Mini Anchor ( 1000-


100 W/m2 95 W/m2 NA 150 W/m2 150 W/m2
2499 m2)
Major Anchor ( 2499 -
100 W/m2 90 W/m2 NA 150 W/m2 150 W/m2
4999 m2)
Anchor ( > 1000 m2) 100 W/m2 NA 150 W/m2 150 W/m2 AECOM to consider VT &
Escalator Load where-
Leisure 230 W/m2 170 W/m2 NA 250 W/m2 ever applicable.
Supermarket ( < 2500
240 W/m2 NA 300 W/m2 250 W/m2
m2)
Supermarket ( > 2500
200 W/m2 NA 300 W/m2 250 W/m2
m2)

F&B ( 0-199 m2) Min 125 KW Max 100 KW


F&B ( 200-249 m2) Min 145 KW Max 135 KW
F&B ( 250-350 m2) Min 165 KW Max 145 KW
650 W/m2 600 W/m2 600 W/m2
F&B ( 351-450 m2) Min 190 KW Max 165 KW AECOM to consider 50
W/m2 Load for external
F&B ( > 450 m2) 450 W/m2 450 W/m2 sitting area
F&B ( > 1000 m2) 350 W/m2 350 W/m2
Cave Dining Same as above Same as above
Bazar Same as above Same as above