You are on page 1of 9

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO.

4, OCTOBER 2010 3035

Analytical Surveys of Transient and


Frequency-Dependent Grounding Characteristics
of a Wind Turbine Generator System on
the Basis of Field Tests
Kazuo Yamamoto, Member, IEEE, Shunichi Yanagawa, Koichi Yamabuki, Member, IEEE,
Shozo Sekioka, Member, IEEE, and Shigeru Yokoyama, Fellow, IEEE

Abstract—To exploit high wind conditions, wind turbine gen- Lightning damage to wind turbine generator systems affects
erator systems are constructed in places with few tall structures; the safety and reliability of these systems. Most breakdowns and
as a consequence, they are often struck by lightning. This results malfunctions of the electrical and control systems inside wind
in breakdown and malfunction of electrical, communications, and
control systems inside and adjacent to the wind turbine generator turbines are caused by ground potential rise due to lightning [5],
system because of ground potential rise. Impulse tests were con- [6]. To understand this ground potential rise, we researched the
ducted on an actual wind turbine generator system and analyt- transient characteristics of grounding by experimental and ana-
ical surveys based on field tests were carried out using electro- lytical methods using a reduced-size model of current wind tur-
magnetic field analysis. The ground potential rise of the system bine foundations [7]. Research using simulations of the transient
and that around its foundation was measured and analyzed. The
grounding system employed in this study consisted of the founda- and steady-state grounding characteristics of wind turbine foun-
tion, grounding mesh, and foundation feet. The frequency charac- dations have already been presented [8]–[18]. However, few pa-
teristics were calculated using the Laplace transform to get voltage pers which report transient and frequency-dependent grounding
responses for all types of lightning current waveforms. Step and characteristics of an actual wind turbine generator system exist
typical lightning current waveforms were used to calculate poten- [19].
tial rise responses.
The wind turbine generator system used for the field test in
Index Terms—Electromagnetic fields, electromagnetic transient this study is located at a unique disposal site. When lightning
analysis, grounding, Laplace transforms, lightning, overvoltage
strikes the wind turbine generator system constructed at a site
protection, surges, wind power generation.
where the grounding resistivity is very low, the potential rise
at the wavefront typically becomes larger than that of the steady
state. This is because of the inductivity of the grounding system.
I. INTRODUCTION Therefore, the transient characteristics of the grounding system
become more important to its steady-state characteristics.

N ATURAL disasters, such as lightning and typhoons, have


caused much damage to wind turbine generator systems
in recent years. Damages caused by lightning are particularly
In this paper, experimental studies of the impulse tests con-
ducted on an actual wind turbine generator system at a disposal
site are presented. The ground potential rise of the system it-
serious [1]–[4]. Wind turbine generator systems are built in lo- self and around its foundations was measured. All measure-
cations where there are few tall structures so as to obtain good ment results were verified using the finite-difference time-do-
wind conditions; thus, they are often struck by lightning. To pro- main (FDTD) method [20]. Numerical simulation was useful to
mote wind power generation, lightning protection methodolo- remove instrumental influences such as the induced voltage on
gies for wind turbine generator systems must be established. the voltage measuring wire from the measured results. The fre-
quency characteristics were calculated from the numerical cal-
Manuscript received October 09, 2009; revised January 15, 2010. First pub- culated results using the Laplace transform [21] to get voltage
lished March 29, 2010; current version published September 22, 2010. Paper responses to all types of lightning current waveforms. The re-
no. TPWRD-00758-2009.
K. Yamamoto is with the Department of Electrical Engineering, Kobe sponses to step and typical lightning currents were calculated.
City College of Technology, Kobe, Hyogo 651-2194, Japan (e-mail: kya- The grounding system consisted of the foundation, grounding
mamoto@mem.iee.or.jp). mesh and wires, and foundation feet. The effects from those el-
S. Yanagawa is with the Shoden Company, Chiba, Chiba 263-0002, Japan
(e-mail: yanagawa@sdn.co. jp). ements were also researched.
K. Yamabuki is with the Department of Electrical Engineering, Wakayama
National College of Technology, Gobo, Wakayama 644-0023, Japan (e-mail:
yamab@wakayama-nct.ac.jp). II. GROUNDING OF WIND TURBINE GENERATOR SYSTEM
S. Sekioka is with the Department of Electrical and Electronic Engineering,
Shonan Institute of Technology, Fujisawa, Kanagawa 251-8511, Japan (e-mail:
sekioka@elec.shonan-it.ac.jp).
A. Importance of Transient Characteristics
S. Yokoyama is with the Central Research Institute of Electric Power Industry Both transient and steady-state characteristics are important
(CRIEPI), Yokosuka, Kanagawa 240-0196, Japan (e-mail: yokoyama@criepi.
denken.or.jp). for understanding the grounding phenomena of a wind turbine
Digital Object Identifier 10.1109/TPWRD.2010.2043748 generator system. However, the steady state is emphasized in
0885-8977/$26.00 © 2010 IEEE

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.
3036 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 4, OCTOBER 2010

planning the grounding system, because it is not easy to mea-


sure its transient characteristic; therefore, the transient charac-
teristics are often neglected.
When a wind turbine generator system is constructed in a
mountain area where the soil resistivity is comparatively high,
the steady-state grounding resistance becomes more important
than the transient grounding resistance in many cases. A poten-
tial rise caused by a lightning strike to a wind turbine generator
system is more remarkable at the wave tail than at the wavefront.
The potential rise at the wave tail depends on the steady-state
grounding resistance. When a wind turbine generator system is
constructed at a low resistivity site, such as a coastal area or a
disposal site, a significant potential rise occurs due to the induc-
tivity of the grounding system. The transient grounding resis-
tance at the wavefront, which depends on the inductivity of the
grounding system, is larger than the steady-state resistance.
The abovementioned contents are qualitatively known in the
field of the grounding; quantitative studies have become very
important for wind turbine generator systems constructed in di-
verse locations. In such studies, the FDTD method, which is one
type of electromagnetic field analysis, was applied to grounding
simulations [19], [22]; its applicable accuracy was verified in
Chapter IV.

B. Grounding of Offshore Wind Turbine Generator System


The soil around the actual wind turbine generator system at the Fig. 1. Foundation of the actual wind turbine generator system.
disposal site where the measurements were performed had elec-
trical characteristics similar to seawater; this was because the soil
at the disposal site contained a lot of seawater. The target wind tur- are connected through the anchor. When the grounding char-
bine generator system had four long foundation feet, like those of acteristics of a wind turbine generator system are researched, a
offshore wind turbines, to increase the bearing capacity of the soil. grounding system including both the grounding wires and foun-
The grounding characteristics of the foundation constructed on dation should be considered.
the disposal site exhibited inductivity as explained in the previous As shown in Fig. 1, the shape of the foundation was rectan-
section. The construction of offshore wind turbine generator sys- gular and parallel-piped, with dimensions of 8.5 m 8.5 m 2
tems has been prohibited in Japan because of fishery rights, de- m. The foundation was constructed with reinforced concrete; the
struction of the environment, etc. However, there are several wind intervals between reinforcing were about 30 cm. The tower was
turbine generator systems in coastal areas. Depending on gov- connected to the foundation at ground level. The depth of the
ernmental energy policy, investigations into the feasibility of off- foundation was 2 m, and the length and diameter of the founda-
shore wind turbine generator systems at Choshi, Chiba are in the tion feet were 50 m and 1 m respectively to enhance the bearing
offing. Therefore, the grounding characteristics of the wind tur- capacity of soil. The foundation feet were also made of rein-
bine foundation at disposal sites should be researched to estimate forced concrete. A grounding mesh existed underneath the foun-
the grounding characteristics of low-resistivity sites. dation; its size was about 8.5 m 8.5 m, the cross section of the
wires for the grounding mesh was 60 mm , and the intervals
of the wires were about 4.25 m. It is connected to the foun-
III. MEASUREMENTS dation feet. The stratiform ground resistivity at the site of the
wind turbine generator system is shown in Fig. 2. The Wenner
A. Grounding System Including Foundation method was utilized to measure the resistivity. The steady-state
Fig. 1 shows in detail the foundation of the actual wind tur- grounding resistance of the grounding system of the wind tur-
bine generator system, grounding mesh and foundation feet used bine generator system was 0.062 .
in our measurements. A quadrangle and octagon exist as the
top surface of the foundation. In many cases, the tower foot is B. Experimental Conditions
buried by a few meters; however, it was not buried in this wind
turbine. The grounding system was not connected to any sur- Fig. 3 shows the experimental setup. The current was led to
rounding wind turbines. For many wind turbines in Japan, the the foundation from the impulse generator with insulated copper
lightning current is actively led to the grounding mesh under- wire (length: 150 m; cross section: 5.5 mm ) as the current lead
neath the foundation from the tower through grounding wires wire. The height of the current lead wire was about 1 m. The
covering the foundation, not to the foundation itself. However, fast front current generated by the impulse generator was in-
the foundation is not explicitly isolated from the tower; these jected into the foundation through a resistance of 500 from

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.
YAMAMOTO et al.: ANALYTICAL SURVEYS OF TRANSIENT AND FREQUENCY-DEPENDENT GROUNDING CHARACTERISTICS 3037

Fig. 2. Stratiform ground resistivity at the site of the wind turbine generator
system estimated by the Wenner method.

Fig. 4. Measuring point of the potential rise around the foundation.

m from the edge of the foundation, as shown in Fig. 4) for fur-


ther distance. The potential rise was measured at 21 locations.
The bottom of the conductive rod (length: 0.3 m; diameter: 10
mm) was buried about a 0.1 m depth at each measured point to
measure the potential rise, the ground terminal of the passive
probe was connected to conductive rod so that the case of the
oscilloscope can be same potential at the measuring point. As
shown in Fig. 3, the current lead wire and voltage measurement
wire were not orthogonalized around the wind turbine. Mutual
Fig. 3. Experimental setup.
electromagnetic induction between the current lead and voltage
measuring wires may have existed.
a current lead wire, as shown in Fig. 3. The peak value of the
current was 60 A, and the wavefront was about 0.3 s. The C. Measuring Instruments
comparatively large resistance of 500 was connected in se- The impulse generator had a capacitance of 1.5 F, and it was
ries with the impulse generator; the power source could there- discharged using a gap switch. The charging voltage was about
fore be considered as a current source. The resistance worked 30 kV for these measurements.
as a matching impedance to reduce the current reflections on A TDS3054C oscilloscope (Tektronix) was used to measure
the current lead wire. The impulse generator was grounded by the voltage and current waveforms; its bandwidth was dc-500
several grounding rods (length: 1.5 m; diameter: 20 mm); the MHz. A P5100 passive probe (Tektronix) was used for voltage
steady-state grounding resistance was 7.5 . measurements; its bandwidth was dc-250 MHz, and its input
The injected current was measured at the end of the current capacitance was up to 2.75 pF. A PEARSON 150 was used as
lead wire near the foundation with a current probe, as shown the current probe; its bandwidth and usable rise time were 40
in Fig. 3. The potential rise of the foundation was measured as kHz–20 MHz and over 20 ns, respectively. The measurements
the voltage difference between the top of the foundation and the performed using these instruments were accurate, with a rise
voltage measurement wire (length: 70 m; cross-section: 2 mm ). time of several hundred nanoseconds.
The ground terminal of the passive probe was connected to the
top of the foundation so that the case of the oscilloscope can be D. Measured Results
same potential at the measuring point. The height of the voltage The measurement results are shown in Fig. 5. Fig. 5(a) and (b),
measurement wire was 1 m, and it was grounded at the remote respectively, shows the injected current and potential rise at
end through a matching impedance. The surge impedance of the the top of the foundation. The injected current showed a ramp
voltage measuring wire was about 500 ; therefore, the 400 wave which includes wide frequency component, and its peak
resistance was connected between the remote end of the voltage value and rise time were approximately 60 A and 0.3 s, respec-
measuring wire and a grounding rod (length: 0.5 m; diameter: tively. The voltage was inductive at the wavefront. The ratio of
20 mm). The bottom of the grounding rod was buried about a the maximum voltage at the wavefront to the current at the same
0.1 m depth, and the grounding resistance was about 100 . time was approximately 13 V/A. This value was greater than the
This was how the noise induced on the voltage measuring wire steady-state grounding resistance. The voltage waveform oscil-
was discharged to the ground readily. The potential rise around lated after the wavefront. The medium value of the voltage grad-
the wind turbine generator system was measured as the voltage ually decreased to the steady-state grounding resistance of 0.062
between the conductive rods and the voltage measurement wire . We believe that the oscillations were caused by the inductance
at intervals of 1 m (0 to 10 m from the edge of the foundation, and capacitance of the grounding system and the traveling wave
as shown in Fig. 4) around the foundation, and 2–4 m (over 10 phenomena on the tower and down conductors in the blades.

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.
3038 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 4, OCTOBER 2010

Fig. 5. Transient characteristic of the grounding system for an actual wind tur-
bine generator system. (a) Injected current into the foundation. (b) Potential rise
of the foundation.

As mentioned above, the grounding characteristics of the


system showed strong inductiveness at the wavefront; the
steady-state grounding resistance was as low as 0.062 . For
offshore wind turbine generator systems, similar grounding
characteristics should be observed. Transient phenomena obvi-
ously become more important than steady-state phenomena for
lightning protection design. Fig. 6. Potential rise around the wind turbine generator system. (a) Waveforms
The potential around a wind turbine generator system in- of the potential rise. (b) Peak values of the potential rise.
creases when it is struck by lightning. To investigate the poten-
tial rise, the fast-front current was injected into the grounding The time characteristics of the wind turbine grounding system
system, as shown in Figs. 3 and 4. The injected current was are shown in Fig. 5. Its frequency characteristics are shown in
much the same as the results shown in Fig. 5(a), where the peak Fig. 7(a) and (b). The grounding characteristics of the wind tur-
value was 60 A and the wavefront was about 0.3 s. bine were inductive over 10 kHz. From the transfer function
Fig. 6(a) shows the measured potential rise around the wind of the grounding system, the time responses to all the different
turbine generator system at several points. Fig. 6(b) shows the lightning waveshapes could be calculated.
relationship between the maximum potential rise and the dis- The abovementioned measured results included the influence
tance. The waveshape shown in Fig. 6(a) was almost analogous of the surge propagations on the tower and blades, the induced
to the potential rise shown in Fig. 5(b). If the skin effect of the voltage on the voltage measuring wire, an input capacitance of
ground is not considered and the shape of the grounding system the voltage probe, the position of the current lead wire, and so on.
is assumed to be a semisphere, the grounding impedance is as- If we want to obtain the independent grounding characteristics of
sumed to be a pure resistance, the maximum potential rise is the foundation, a model of a wind turbine with a grounding system
found to be inversely proportional to the distance from the foun- should be established in numerical electromagnetic field analysis
dations. A few differences existed in comparison with the in- such as through the FDTD method, and the independent model
versely proportional waveform because the measurement results of the grounding system should be calculated. In the following
in Fig. 6(a) showed surge behavior. section, the FDTD calculated results are presented.

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.
YAMAMOTO et al.: ANALYTICAL SURVEYS OF TRANSIENT AND FREQUENCY-DEPENDENT GROUNDING CHARACTERISTICS 3039

Fig. 7. Frequency responses of the grounding system on the actual wind turbine
generator system. (a) Absolute value of the grounding impedance. (b) Phase
value of the grounding impedance. The frequency responses are calculated from
the measurements shown in Fig. 5. Fig. 8. Analytical setup for the FDTD analyses.

IV. ANALYTICAL CONSIDERATIONS Fig. 5(a), the calculated injected current agreed well with the
measured current.
A. Analytical Conditions At the wavefront, there were a few differences. However, the
The measurements presented in Section III were reproduced potential rise of the foundation as shown in Fig. 9(b) showed
by using electromagnetic field analysis through the FDTD inductive characteristics, which also agreed well with the mea-
method. The analytical setup is shown in Fig. 8. sured values overall.
The dimensions of the analytical space were 120 m 90 Fig. 10 shows comparisons of the potential rise around the
m 200 m, and it was divided into cube cells with a side foundation at several points. As seen in the potential rise of the
length of 1.0 m. The absorbing boundary condition was 2nd foundation, inductivity was observed in the FDTD simulations.
order Liao. The ground level was 100 m from the bottom of the Fig. 11 shows the comparisons of the calculated and measured
analytical space; the resistivity of the ground was the same as peak values of the grounding potential rise. The calculated re-
that shown in Fig. 2. Thin-wire models to model the current sults near the foundation agreed well with the measured results,
lead wire, voltage measuring wire, grounding mesh, and light- as shown in Fig. 6. However, the values at points far from the
ning conductors in blades were used [23]. The nacelle was a foundation had small differences. The straiform ground resis-
rectangular parallelepiped conductor of 2 m 2 m 5 m, and tivity measured by Wenner method as shown in Fig. 2 doesn’t
the tower was a tube conductor with a stair-like surface, 3 m in agree with the actual stratiform ground resistivity completely.
diameter and 43 m in height. The foundation was a rectangular It is an approximate result, and might influence the above men-
parallelepiped of dimensions 8 m 8 m 2 m; the foundation tioned differences.
foot was also modeled as a rectangular parallelepiped of 1
m 1 m 50 m. The current source parallel with the resistance C. Pure Characteristics of the Grounding System and Effects
of 500 was connected between the foundation and current of Each Element Composing the Grounding System
lead wire. The current lead wire and voltage measuring wire The FDTD calculations were performed without the tower
were connected to the absorbing boundaries. and down conductors in the blades. Other calculated conditions
were the same as the calculation shown in Fig. 8. Compared with
B. Comparisons of Measurements and Calculations the calculated results of the potential rise in Fig. 9(b), there was
Fig. 9(a) shows the calculated and measured injected currents. about a 10% difference at the wavefront, as shown in Fig. 12,
The rise time and peak value were approximately 0.3 s and because of the positive reflection of the voltage traveling wave
60 A, respectively. Compared with the measurements shown in from the tips of the blades.

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.
3040 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 4, OCTOBER 2010

Fig. 9. FDTD calculated results of the grounding system compared with the
measured results. (a) Injected currents into the foundation. (b) Potential rises of
the foundation.

To get the pure characteristics of the grounding system, the


FDTD calculation was performed without the tower and the
down conductors in the blades. In these calculations, the cur-
rent was led from the -direction wire connected to the overhead
boundary to the foundation to reduce electromagnetic induction
to the ground surface and voltage measuring wire, as shown in
Fig. 13. The current waveform also changed a little at the wave-
front, as shown in Fig. 14(a), because the direction of the cur- Fig. 10. Comparison of measured and calculated potential rises around the
rent injection was changed; the influence from the current in wind turbine generator system. (a) 0 m from the edge of the foundation as shown
the ground was reduced. As shown in Fig. 14(b), the potential in Fig. 4. (b) 5 m from the foundation. (c) 10 m from the foundation.
rises were compared for four conditions. Case 1 was a funda-
mental case that included the foundation, grounding mesh, and as shown in Figs. 13 and 14. The results in Fig. 15 show the ef-
foundation feet. Case 2 studied the influence of the grounding fects of the incidental, such as the grounding mesh and founda-
mesh underneath the foundation and included the foundation tion feet. Depending on the grounding resistivity, the foundation
and foundation feet. Case 3 studied the influence of the founda- feet affected the grounding impedance at the wave tail but not
tion feet connected to the bottom of the foundation and included so much at the wavefront. The grounding mesh underneath the
the foundation and grounding mesh. Case 4 had just the foun- foundation did not affect the grounding impedance significantly
dation. As shown in Fig. 14(b), there was not much difference at both wave tail and wavefront. From these results, it is clear
in the waveforms. The skin depth of the ground was about 2 m that the inductance of the foundation caused the steep potential
at a frequency of 1 MHz and grounding resistivity of 15 m; rise at the wavefront.
therefore, the current in the ground mainly flowed on the sur- The frequency characteristics of the grounding system in
face at the wavefront. At the wave tail, there was also not much Case 1, as shown in Fig. 13 and 14, are shown in Fig. 16(a)
difference in the wave forms. The ground resistivity was very and (b). The frequency characteristics of Cases 2–4 also had
low, as shown in Fig. 2, thus the potential rise at the wave tail the same results. The grounding characteristics of the wind
was far smaller than that at the wavefront; the differences in the turbine were inductive over 10 kHz. From the transfer function
potential rises at the wave tail were not remarkable. of the grounding system, the time responses to all the different
Fig. 15 shows the calculation result for the ground with a re- lightning wave shapes can be calculated. As examples, potential
sistivity of 100 m. Other calculated conditions were the same rise responses to a step current with a peak value of 1 A and a

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.
YAMAMOTO et al.: ANALYTICAL SURVEYS OF TRANSIENT AND FREQUENCY-DEPENDENT GROUNDING CHARACTERISTICS 3041

Fig. 11. Comparisons of the calculated and measured results of the peak value
of the grounding potential rise.

Fig. 13. Analytical setup for the FDTD analyses. The current is led from the z
direction wire connected to the overhead boundary.

Fig. 12. FDTD calculated results to study the influence of the tower and down
conductors in the blades. Injected current into the foundation was the same as
that shown in Fig. 9(a). Above figure is the potential rises of the foundation in
cases with and without the tower and down conductors.

typical lightning current with a peak value of 30 kA, the wave-


front of 5.5 s and the stroke duration of 75 s [24] are shown
in Fig. 17. The step current is adopted because the waveform
includes wide frequency component. The above mentioned
measured results do not include the influence of surge propa-
gations at the tower and blades; they are the independent and
pure characteristics of the grounding system.

V. CONCLUSION
This paper has presented the results of experimental and
analytical studies investigating the grounding characteristics
of an actual wind turbine generator system at a disposal site
and the potential rise around it. The analytical results using
the FDTD method agreed well with the measured results of
the field tests.
The characteristics of the grounding system showed strong
inductivity at the wavefront. The tower and down conductors in
the blade clearly affect the transient of the potential rise at the Fig. 14. FDTD calculations to study the influence of the incidental elements.
wavefront. Depending on the grounding resistivity and wave- (a) Injected currents into the foundation. (b) Potential rises of the foundation.
front, the foundation feet affect the grounding impedance at Case 1 includes the foundation, grounding mesh, and foundation feet. Case 2
includes the foundation and foundation feet. Case 3 includes the foundation and
the wave tail but not so much at the wavefront. The grounding grounding mesh. Case 4 includes just the foundation.
mesh underneath the foundation does not significantly affect the
grounding impedance at either the wave tail or front. The in-
ductance of the foundation causes the steep potential rise at the The frequency responses of the pure characteristics of the
wavefront. grounding system were presented to obtain voltage responses to

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.
3042 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 4, OCTOBER 2010

Fig. 15. FDTD calculated results of the grounding system when the ground has
100
m resistivity. (a) Injected currents into the foundation. (b) Potential rises
of the foundation.

Fig. 17. Potential rise responses to step and typical lightning currents. (a) Po-
tential rise response to a step current. (b) Typical lightning current waveform.
(c) Potential rise response to the typical lightning current.

will provide useful basic data for lightning protection of wind


turbine generator systems at low resistivity sites, including off-
shore wind turbine generator systems.

REFERENCES
[1] I. Cotton, B. Mcniff, T. Soerenson, W. Zischank, P. Christiansen, M.
Hoppe-Kilpper, S. Ramakers, P. Pettersson, and E. Muljadi, “Light-
ning protection for wind turbines,” in Proc. 25th Int. Conf. Lightning
Protection, 2000, pp. 848–853.
[2] “Wind turbine generator systems—Part 24: Lightning protection,” IEC
Fig. 16. Frequency responses of the grounding system on the actual wind tur- Tech Rep. 61400-24, 2002.
bine generator system. (a) Absolute value of the grounding impedance. (b) Phase [3] “Wind turbine failures and troubles investigating committee annual re-
value of the grounding impedance. The frequency responses are calculated from port,” (in Japanese) 2006, NEDO.
the analytical results shown in Fig. 14. [4] “Wind turbine failures and troubles investigating committee annual re-
port,” (in Japanese) 2007, NEDO.
[5] K. Yamamoto, T. Noda, S. Yokoyama, and A. Ametani, “An experi-
mental study of lightning overvoltages in wind turbine generation sys-
all types of lightning current waveforms. As examples, the po- tems using a reduced-size model,” Elect. Eng. Jpn., vol. 158, no. 4, pp.
tential rise responses to step and typical lightning currents are 22–30, Mar. 2007.
[6] K. Yamamoto, T. Noda, S. Yokoyama, and A. Ametani, “Experimental
calculated. and analytical studies of lightning overvoltages in wind turbine gener-
The installation features of the wind turbine generator system ator systems,” Elect. Power Syst. Res., vol. 79, no. 3, pp. 436–442, Mar.
employed in this study were very similar to those used at sea. 2009, ISSN:0378-7796.
[7] K. Yamamoto, T. Noda, S. Yokoyama, and A. Ametani, “Grounding
The long foundation feet were much like those of an offshore characteristics of a wind turbine generation system and voltage rise
wind turbine generator system. The results given in this paper around it,” in Proc. Int. Conf. Grounding and Earthing, pp. 415–419.

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.
YAMAMOTO et al.: ANALYTICAL SURVEYS OF TRANSIENT AND FREQUENCY-DEPENDENT GROUNDING CHARACTERISTICS 3043

[8] N. Jenkins and A. Vaudin, “Earthing of wind farms,” Wind Eng., vol. with the Infrastructure Research Center at Doshisha University. His research in-
18, no. 1, pp. 37–43, 1994. terests include lightning protection.
[9] M. Lorentzou, I. Cotton, N. Hatziargyriou, and N. Jenkins, “Electro-
magnetic analysis of wind turbine grounding systems,” in Proc. Eur.
Wind Energy Conf., 1997, CD-ROM.
[10] N. Hatziargyriou, M. Lorentzou, I. Cotton, and N. Jenkins, “Windfarm Shunichi Yanagawa was born in Kanagawa, Japan,
earthing,” in Proc. Inst. Elect. Eng. Colloq. “Lightning Protection of in 1961. He received the Bachelor’s degrees in engi-
Wind Turbines”, Nov. 1997, IEE Publ. 97/303. neering from Tokai University, Kanagawa, Japan, in
[11] N. Hatziargyriou, M. Lorentzou, I. Cotton, and N. Jenkins, “Trans- 1985.
ferred overvoltages by windfarm grounding systems,” in Proc. Int. He joined Shoden Corp., where he is currently
Conf. High Quality Power, 1998, pp. 342–347. an Executive Research Scientist. He had been the
[12] I. Cotton, “Windfarm earthing,” in Proc. 11th Int. Symp. High Voltage Director of the Techno Center at Shoden Corp.
Engineering, 1999, vol. 2, pp. 288–291. from 2004 to 2008. Currently, he is a Manager
[13] I. Cotton and N. Jenkins, “Windfarm earthing,” in Proc. Eur. Wind En- of the Technology Development Department. His
ergy Conf., 1999, pp. 725–728. research interest includes the research and product
[14] M. Lorentzou, N. Hatziargyriou, and B. Papadias, “Analysis of wind developments concerning lightning protection.
turbine grounding systems,” in Proc. 10th Mediterranean Electrotech-
nical Conf., 2000, pp. 936–939.
[15] J. M. Prousalidis, M. P. Philippakou, N. Hatziargyriou, and B. Papa-
dias, “The effects of ionization in wind turbine grounding modeling,” in
Proc. 10th Mediterranean Electrotechnical Conf., 2000, pp. 940–943. Koichi Yamabuki (M’99) was born in Osaka, Japan,
[16] V. T. Kontargyri, I. F. Gonos, and I. A. Stathopulos, “Frequency re- in 1970. He received the B.E., M.E., and Ph.D.
sponse of grounding system of wind turbine generators,” in Proc. 24th degrees in engineering from Doshisha University,
Int. Symp. High Voltage Engineering, 2005, p. B-13. Kyoto, Japan in 1994, 1997, and 2000, respectively.
[17] B. Hermoso, “Wind farm earthing installations: Rated and lightning In 1999, he jointed Wakayama National College
frequencies behaviour,” in Proc. Int. Conf. Grounding and Earthing, of Technology, where he is currently an Associate
2006, pp. 411–414. Professor. From 2006 to 2007, he was a Visiting Re-
[18] O. Ukar, I. Zamora, R. Idiondo, and A. Mugica, “Analysis for high searcher at University of Bologna, Bologna, Italy. His
frequencies of grounding systems, for wind turbines,” in Proc. 27th research interest includes lightning protection.
Int. Conf. Lightning Protection, 2004, vol. II, pp. 1053–1057. Dr. Yamabuki is a Research Fellow with the Infra-
[19] K. Yamamoto and S. Yanagawa, “Analytical and experimental studies structure Research Center at Doshisha University.
of grounding characteristics of wind turbines,” in Proc. Int. Conf.
Grounding and Earthing, 2006, pp. 391–395.
[20] K. S. Yee, J. S. Chen, and A. H. Chang, “Conformal finite-difference
time-domain (FDTD) with overlapping grids,” IEEE Trans. Antennas Shozo Sekioka (M’00) was born on December 30,
Propag., vol. 40, no. 9, pp. 1068–1075, Sep. 1992. 1963. He received the B.Sc. and Dr.Eng. degrees
[21] N. Nagaoka and A. Ametani, “A development of a generalized fre- in electrical engineering from Doshisha University,
quency-domain transient program—FTP,” IEEE Trans. Power Del., Kyoto, Japan in 1986 and 1997, respectively.
vol. 3, no. 4, pp. 1996–2004, Oct. 1988. He joined Kansai Tech Corp. in 1987. He was
[22] M. Tsumura, Y. Baba, N. Nagaoka, and A. Ametani, “FDTD simu- an Associate Professor at Shonan Institute of Tech-
lation of a horizontal grounding electrode and modeling of its equiv- nology from 2005 to 2007, where he is currently a
alent circuit,” IEEE Trans. Electromagn. Compat., vol. 48, no. 4, pp. Professor. He has been engaged in lightning surge
817–825, Nov. 2006. analysis in electric power systems.
[23] T. Noda and S. Yokoyama, “Thin wire representation in finite differ-
ence time domain surge simulation,” IEEE Trans. Power Del., vol. 17,
no. 3, pp. 840–847, Jul. 2002.
[24] H. D. Betz, U. Schumann, and P. Laroche, Lightning: Principles, In-
struments and Application: Review of Modern Lightning Research.
Berlin, Germany: Springer, 2009. Shigeru Yokoyama (M’83–S’91–F’96) was born
in Sendai, Japan, on March 5, 1947. He received
the B.Sc. and Ph.D. degrees from the University of
Kazuo Yamamoto (M’98) was born in Osaka, Japan Tokyo, Tokyo, Japan, in 1969 and 1986, respectively.
in 1974. He received the B.E., M.E., and Ph.D. He joined the Central Research Institute of Elec-
degrees in engineering from Doshisha University, tric Power Industry (CRIEPI), Japan, in 1969. Since
Kyoto, Japan, in 1997, 2000, and 2007, respectively. then, he has been engaged in the research of lightning
He was with Nara National College of Technology protection on power systems, buildings, and wind tur-
from 2000 to 2006. He was an Assistant Professor at bines. He holds posts of Research Advisor at CRIEPI.
Kobe City College of Technology from 2006 to 2007, He was Professor at Kyushu University from 2001
where he is currently an Associate Professor. From through 2007. He was a Vice President at the Insti-
1998 to 1999, he was a Visiting Researcher at the tute of Electrical Engineers of Japan in 2001.
Manitoba HVDC Research Centre, Winnipeg, MB, Dr. Yokoyama is a chairman of the IEC TC 81 (Lightning Protection)
Canada. Since 2008, he has been a Research Fellow Japanese committee.

Authorized licensed use limited to: ULAKBIM UASL - CELAL BAYAR UNIVERSITESI. Downloaded on December 12,2022 at 09:12:56 UTC from IEEE Xplore. Restrictions apply.

You might also like