NOTES:

NORTH
NORTH
1. ALL DIMENSION ARE IN MILLIMETERS UNLESS OTHERWISE NOTED.

2. THE GROUNDING LAYOUT INDICATED ON THIS DRAWING IS

INDICATIVE ONLY.

PLANT
H

TRUE
A

3. INSTALLATION DETAIL NEED TO REFERENCE


¡
KK

29 A00-P-CBL-VA-375984-001~005.
A

OF
4. BURIED GROUNDING CONDUCTORS FOR GROUND GRID SHALL BE
M

BARE TINNED COPPER.


202623

CONSENT
5. ALL BURIED GROUNDING CONDUCTORS SHALL BE INSTALLED

750mm BELOW GRADE.


DRAWING LIMIT N 9559.703
6. ALL GROUND CONNECTIONS SHALL BE CLEANED AND TINNED
CONNECT WITH IGCC #5 GROUNDING GRID
BEFORE TERMINATION.

7. CABLE TRAY SHALL BE BONDED TO THE GROUNDING GRID

TTEN
AT INTERVALS OF 25 METERS ALONG THE LENGTH OF THE TRAY

WRI
RUN AND CABLE TRAY ENDS SHALL BE BONDED TO MAIN GROUND

GRID AS PER SAUDI ARAMCO LIBRARY DRAWING DD-950022 SHEET

007.

THE
D01 D02 D03

D05

8. BURIED GROUNDING CONDUCTOR SHALL HAVE CLEARANCE OF

300MM (MIN) FROM ANY UNDERGROUND OBSTRUCTIONS.

THOUT
SLOPE SLOPE
9. ALL PLATFORMS AND STAIRS BOLTED TOGETHER NEED TO BE
1/50 1/12

CONNECTED WITH BONDING JUMPERS.

10. GROUNDING CONDUCTORS EXTENDING THROUGH CONCRETE OR

WI
ASPHLT SHALL BE RUN IN PVC CONDUIT.

NG
11. GROUNDING SHALL COMPLY WITH SEAS-P-111.

DRAWI
12. ALL GROUNDING CONDUCTORS NEED RUN IN 4’’ PVC CONDUIT,

750MM MIN BELOW GROUND GRAD. EACH END OF PVC CONDUIL

A10-P-CBL-VA-241355-401
EXTEND ROAD EDGE 500MM.

S
THI
FROMNED
N 9500

OBTAI
LEGEND

UNDERGROUND BARE TINNED COPPER


CONDUCTOR 185SQMM

BE
GROUND TEST WELL WITH GROUND ROD

PART,SHALL
GROUND ROD (DIA=20MM, L=2400MM, TWO RODS
INSTALLED IN PARALLEL)

CADWEID JOINT (T CONNECTION)

CADWEID JOINT (CROSS CONNECTION)

DWG

N
I
FULL,OR
SEE
000

ON
8050.

N
NUATI

I ON
219700

REPRODUCTI
CONTI
EMIT

REFERENCE DRAWINGS
LI

PLOT PLAN BLOCK 5 A10-A-VA-034421-501

SAUDIARAMCO.NO
FOR
NOTES AND LEGEND A00-P-CBL-VA-240459-001
NG

GROUNDING INSTALLATION DETAIL A00-P-CBL-VA-375984-001~005


DRAWI

GROUNDING GRID SYSTEM DESIGN A00-P-DOC-VE-240494

623
OVERALL GROUNDING LAYOUT A00-P-CBL-VA-241354-001
PB5 MAIN UNDERGROUND PIPING PLAN A10-S-UTI-VA-209624-501~506

8252.
KEY PLAN

OF
NORTH
NORTH
PLANT
H

TRUE
KA
¡
29

AK
M

PROPERTY
E NE
MATCHLI
N 9400

SOLE
THE
THIS DRAWING

ARE
G04

N
HEREI
G02
A L L

0 10 20 30 40
G01 G03

D04
F IR E W

D08
METERS

NED
G06

G05
SCALE: 1 : 400M

CONTAI
REVISION VALIDATION

THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
10-01525-0004-006

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

LC.CHEN B.ANDERS
07/22/16 07/22/16

REV.NO. DATE REVISION DESCRIPTION

I
00 07/22/16 ISSUED FOR CONSTRUCTION

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-01525-0004 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING LIMIT N 9340.003
DRAWING TYPE

GROUNDING PLAN/LAYOUT/DETAIL CBL

NG
8200
8100

GROUNDING GRID LAYOUT (PB5)

DRAWI
POWER GENERATION UNIT
E

JAZAN SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
A10 P VA-241355 501 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01