You are on page 1of 2

COMPAÑÍA MINERA ANTAMINA

SISTEMA DE BOMBEO DE RELAVES LÍNEAS NORTE Y SUR - ELEVACIÓN 4165


DATA SHEET
UPS
420-UPS-1013
Rev.
Datasheet N° 104-13479-MOB02918-DSH-420-J-0012 0
1 Tech.Specification 104-13479-MOB02918-ESP-420-J-0002 Equip. No. GENERAL
L.L.F.
GENERAL

2 P&ID Nº, N.A. 0 14/11/19 D.P.C. D.S.P.


3 Location ELECTRICAL ROOM (1ST FLOOR) Altitude 4 300 m a.s.l. B 15/10/19 D.P.C. D.S.P. L.L.F.
4 Service POWER SYSTEM Moisture 70% A 17/5/19 D.P.C. D.S.P. L.L.F.
5 Area class UNCLASSIFIED Ambiance temperature -0.1 a 12.0°C Rev Date: By Appr Proj. Mg
Rev.
6 Manufacturer POWERWARE-EATON / EMERSON / LIEBERT 0
7 Model TBD 0
FEATURES

8 Dimensions 2 200 x 1 200 x 600 mm (TBC) 0


9 Mounting SELF SUPPORTED 0
10 Enclosure NEMA 1 0
11 Cable Entry TOP 0
11
12 Nominal Voltage 480 VAC 0
0
AC INPUT

13 Input Range ± 10%


14 Phases 3 0
15 Frequency 60 Hz 0
16
17 UPS Rating 15 KVA (NOTE 3) 0
AC OUTPUT

18 Power Factor 0.8 OR 1 0


19 Output Voltage 480 VAC / 3 PHASES 0
20 Voltage Adjusment ± 5% 0
21
22 AC Output Voltage REQUIRED (NOTE 2) 0
23 AC Output Current REQUIRED (NOTE 2) 0
SYSTEM MEASUREMNET

24 AC Output Frequency REQUIRED (NOTE 2) 0


25 Charger / Rectifier Output Current REQUIRED (NOTE 2) 0
26 Battery Voltage (with rectifier configuration) REQUIRED (NOTE 2) 0
27 Total Operation Time on UPS REQUIRED (NOTE 2) 0
28 Total Operation Time on Bypass REQUIRED (NOTE 2) 0
29 Total Operation Time on Inverter REQUIRED (NOTE 2) 0
30
31 Low DC Voltage REQUIRED 0
32 Low DC Disconnect REQUIRED 0
33 Over Temperature REQUIRED 0
ALARMS

34 Overload Shutdown REQUIRED 0


35 Bypass Failure REQUIRED 0
36 Inverter Failure REQUIRED 0
37
38 Capacity Bank TBD 0
39 Autonomy Time 540 min AT 15 kVA 0
BATTERY BANK

40 Battery Type Ni-Cd, SEALED (RACK MOUNT) 0


41 Protection Breaker REQUIRED 0
42 Enclosure Class Cabinet NEMA 1 0
43 Dimensions TBD 0
44 Installation TBD 0
45
46 Communication NOT REQUIRED 0
OPTIONS

47 Equipments Installations INCLUDED 0


48
49 Manufacturer TBD 0
PURCHASE

50 Model N° TBD 0
51 P. O. N° Item N°
52 Serial N°
53 Electrical Aproval
54 1. AFFIX ENGRAVED SS TAG CABINET
55 2. ALL THE MEASUREMENTS HAVE TO BE DISPLAYED ON A LCD PANEL
NOTES

56 3. PROVIDER MUST GUARANTEE UPS RATING ACCORDING TO DRAWING 420-J-20059, DOCUMENT 104-13479-MOB02918-MEC-420-J-0002 AND ENVIROMENTAL CONDITIONS
57 4. TBD: TO BE DEFINED BY VENDOR
58 5. TBC: TO BE CONFIRMED BY VENDOR
59 6. N/A: NOT APPLY

Golder Associates 2/2