TJ170PE6 (220/127V)

60 Hz Diesel Generator Sets

Output Power

kVA 171
Standby Power (ESP) 137
kW
kVA 155
Prime Power (PRP) 124
kW

Size WxLxH Weight Fuel Tank Noise dB(A)


(mm) (kg) (lt) @ 7m
Canopied 1200 x 3860 x 1850 2171 330 TBA
Open Skid 1200 x 2700 x 1470 1630 330 N/A

Continuous Power Standby Power Prime Power


The maximum power which a The max power available during a The maximum power which a
generating set is capable of delivering variable electrical power sequence, generating set is capable of delivering
continuously whilst supplying a under the stated operating conditions, continuously whilst supplying a
constant electrical load. Average load for which a generating set is capable variable electrical load. Average load
can be 100%. The generator must not of delivering in the event of a utility should be 70%. The generator can be
be overloaded. power outage or under test conditions overloaded 10% for 1 hour per 12 hrs.
for up to 200 hrs of operation per year
under average of 70% load.
Overloading isn’t permissible.

TTDTJ175PE620210923EN
TJ170PE6 (220/127V)
60 Hz Diesel Generator Sets

Engine

Manufacturer PERKINS
Model 1106A-70TG1
Cylinder Configuration INLINE
No of Cylinders 6
Displacement lt 7,01
Stroke mm 135
Bore mm 105
Compression Ratio 18,2:1
Aspiration TURBOCHARGE-INTERCOOLER
Governor Type MECHANIC
Cooling System WATER
Coolant Capacity lt 21
Lubrication Oil Capacity lt 16,5
Electrical System VDC 12
Speed / Frequency 60 Hz Hz 1800 rpm / 60 Hz
Engine Gross Power (Standby 60 Hz) kW 160
Fuel Consumption %110 ESP 60 Hz lt/h 38,8
Fuel Consumption %100 PRP 60 Hz lt/h 35,2
Fuel Consumption %75 PRP 60 Hz lt/h 26,5
Fuel Consumption %50 PRP 60 Hz lt/h 18
Exhaust Outlet Temperature 60 Hz °C 526
Exhaust Gas Flow 60 Hz m3/min 29,72
Combustion Air Flow 60 Hz m3/min 11,86
Cooling Air Flow 60 Hz m3/min 182

Alternator

No of Phases 3
Power Factor 0,8
No of Bearings SINGLE
No of Poles 4
No of Leads 6-12
Insulation Class H-F
Degree of Protection IP 21-23
Excitation System AVR (Automatic Voltage Regulator),
Brushless
Connection Type STAR

TTDTJ175PE620210923EN
TJ170PE6 (220/127V)
60 Hz Diesel Generator Sets

Standard Equipments

Engine
In Teksan generator sets, leading engine brands that have state of
the art technology and have compliance with ISO 8528, ISO 3046,
BS 5514, DIN 6271 standarts, are being used. These engines with
low fuel consumption, provide accurate speed setting and order,
mount to the fuel pump, also have mechanic or electronic type
governors.
Alternator
In products Teksan produced, leading alternator brands of the
world that have state of the art technology, high quality,
productivity and durability, are being used. All alternators, which
pass necessary test process and found appropriate according to EC
60034-1; CEI EN 60034-1; BS 4999-5000; VDE 0530, NF 51- 100,111; Canopy Features
OVE M-10, NEMA MG 1.22. standarts, have bearing system that
does not need maintenance, with electronic type voltage regulator TEK SAN Standard Canopies' default features are as follows;
providing voltage setting. ■ Compatible with 2000/14/EC directives, certified noise emission
level,
Control Panel ■ 2 or 4 points transport possibility according to cabin size,
Standard control panel, that is used in Teksan generator sets, ■ Hidden exhaust inside the canopy,
ensures comfortable and safe usage. All measured and statistical ■ Emergency stop button located on the canopy,
parameters, operating modes, notice and alarms and condition of ■ Improved air suction channel to ensure homogenous cooling in the
generator, are monitored easily from the control panel. On the
front of the panel’s metal body has electronic control module and canopy,
the emergency stop button and the panel’s metal body is made of ■ Radiator air outlet and exhaust with designed towards above,
steel sheet and is painted with electrostatic powder paint. ■ Lid on cab that provides to be filled up water and antifreeze easily
to the radiator,
Teksan offers panel design and solutions that comply with ■ Amplified paint system against corrosion and rust,
special requirements of customers as well as quality standard ■ Improved performance in terms of sound insulation,
panels. ■ Demounted parts that make transportation and maintenance
easier,
Chassis and Fuel Tank
Chassis is manufactured from steel that has features and As well as the standard range of canopies, TEKSAN can also design
durability for carrying burden of generator set. Thanks to its tailormade canopies with specific sound level or size upon customer
rigid structural design and anti-vibration mounts, it reduces requests.
vibration level to minimum. All chassis contain lifting lugs.
Apart from chassises that are produce by Teksan, special
solutions that design in accordance with customer desires,
make transportation and positioning easier.
In less than 1600 kVA power generator sets, fuel tank is produced
integratedly to the chassis. In more than 1600 kVA power generator
sets, rectangular type fuel tank is provided with generator set
seperately. In all types of fuel tank have its level and indicator.

Cooling System
System, that consists of quality industrial - type radiator,
expansion tank and cooler fan, keeps the temprature of generator
set’s equipments constant at a proper level.

TTDTJ175PE620210923EN
TJ170PE6 (220/127V)
60 Hz Diesel Generator Sets

Control Panel Features-DSE-7320

■ 4-Line back-lit LCD text display


■ Five key menu navigation
■ Front panel editing with PIN protection
■ Customisable status screens
■ Power save mode
■ Support for up to three remote display units
■ 9 configurable inputs
■ 8 configurable outputs
■ Flexible sender inputs
■ Configurable timers and alarms
■ 3 configurable maintenance alarms
■ Multiple date and time scheduler
■ Configurable event log (250)
■ Tier 4 CAN engine support Functions
■ Integral PLC editor
■ Easy access diagnostic page
■ CAN and Magnetic Pick-up/Alt. sensing ■ AMF unit
■ Fuel usage monitor and low fuel alarms ■ Remote start controller
■ Charge alternator failure alarm ■ Manuel start controller
■ Manual speed control (on compatible CAN engines) ■ Engine controller
■ Manual fuel pump control ■ Remote display & control unit
■ Engine exerciser ■ CTs at genset or load side
■ “Protections disabled” feature
■ kW & kV Ar protection Communications
■ Reverse power (kW & kV Ar) LED and LCD alarm indication
■ Power monitoring (kW h, kV Ar, kV A h, kV Ar h) ■ Web monitoring
■ Load switching (load shedding and dummy load outputs) ■ GSM-SMS (requeired externally modem)
■ Automatic load transfer (DSE7320) ■ e-mail
■ Unbalanced load protection ■ USB Device
■ Independent Earth Fault trip ■ RS-232
■ True dual mutual standby with load balancing timer (DSE7310 only) ■ J1939-CANBUS
■ USB connectivity
■ Backed up real time clock
■ Fully configurable via DSE Configuration Suite PC software Topologies
■ Configurable display languages
■ Remote SCADA monitoring via DSE Configuration Suite PC software ■ 2 phase 3 wires, L1-L2
■ User selectable RS232 and RS485 communications ■ 2 phase 3 wires, L1-L3
■ Configurable Gencomm pages ■ 3 phase 3 wires
■ Advanced SMS messaging(additional external modem required) ■ 3 phase 4 wires, star
■ Start & stop capability via SMS messaging ■ 3 phase 4 wires, delta
■ Additional display screens to help with modem diagnostics ■ 1 phase 2 wires
■ Idle control for starting & stopping.
■ DSENet® expansion compatible
■ Heated display option available

■ Technical information and values are according to ISO8528, ISO3046,NEMA MG-1.22, IEC 600341, BS 4999-5000, VDE 0530 standards.
■ Producing with ISO9001, ISO14001, OHSAS18001, TSE, CE standards.
■ All information given in this leaflet is intended for general purposes only.
■ Due to a policy continuous improvement Teksan reserves the right to amend details and specifications without notice and all information given is subject to the
Teksan's current condition of sales.
TBA: To Be Asked TBD: To Be Determined NA: Not Avaliable N/A: Not Applicable TTDTJ175PE620210923EN
1100 Series 1106A-70TG1 Diesel Engine – ElectropaK
133.5 kWm (179 hp) net prime power @ 1800 rpm
148.4 kWm (199 hp) net standby power @ 1800 rpm

Building upon Perkins proven reputation within the power


generation industry, the 1100 Series range of ElectropaK
engines now fit even closer to customers needs.

In the world of power generation success is only gained


by providing more for less. With the 1106A-70TG Perkins
has engineered even higher levels of reliability, yet lowered
the cost of ownership.

1100A units are designed for territories that do not


require compliance to EPA or EU emissions legislation. These
engines are assembled around optimal, efficient manufactuing
processes with state-of-the-art technology. They are built to
provide the exact power solution for customers who sell their
applications into lesser regulated countries.

Focusing on our common platform theme, changes to


engine envelope dimensions and connection points have been kept
to a minimum.

Specification
Number of cylinders 6 vertical in-line
Bore and stroke 105 x 135 mm 4.13 x 5.31 in
Displacement 7.01 litres 428 in3
Aspiration Turbocharged
Cycle 4 stroke
Combustion system Direct injection
Compression ratio 18.2:1
Rotation Anti-clockwise, viewed on flywheel
Total lubricating capacity 18 litres 4.7 US gal
Cooling system Liquid
Total coolant capacity 21 litres 5.5 US gal

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.
All information in this document is substantially correct at time of printing and may be altered subsequently.
Final weight and dimensions will depend on completed specification.

Publication No. PN3075/04/15 Produced in England ©2015 Perkins Engines Company Limited
1100 Series 1106A-70TG1 Diesel Engine – ElectropaK
133.5 kWm (179 hp) net prime power @ 1800 rpm
148.4 kWm (199 hp) net standby power @ 1800 rpm

Features and benefits

Dependable power
l The Perkins® 1106A-70TG1 delivers up to 152 kVA prime and 169 kVA standby at 60 Hz, providing greater
productivity through an improved power to weight ratio
l This world-class power density has been achieved in a 7 litre engine, using a mechanical fuel injection system;
making this engine robust for all markets, with the ability to cope with the variation of fuel qualities around the world
The 1106A has been designed for excellent load acceptance to ensure your facility is powered quickly at all
conditions

Low operating costs


l Service intervals are set at 500 hours as standard
l Warranties and Service Contracts

We provide one-year warranties for constant speed engines and two-year warranties for variable speed models, as
standard. These are supported by multilevel Extended Service Contracts that can be bought additionally
Discover more: www.perkins.com/esc
l Low usage warranty package is also available

World class product support


l Through an experienced global network of distributors and dealers, fully trained engine experts deliver total service
support around the clock, 365 days a year. They have a comprehensive suite of web based tools at their finger
tips, covering technical information, parts identification and ordering systems, all dedicated to maximising the
productivity of your engine
l Perkins actively pursues product support excellence by insisting our distribution network invest in their territory to
provide you with a consistent quality of support across the globe
l Throughout the entire life of a Perkins engine, we provide access to genuine OE specification parts giving 100%
reassurance that you receive the very best in terms of quality for lowest possible cost… wherever your Perkins
powered machine is operating in the world
l To find your local distributor: www.perkins.com/distributor

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.
All information in this document is substantially correct at time of printing and may be altered subsequently.
Final weight and dimensions will depend on completed specification.

Publication No. PN3075/04/15 Produced in England ©2015 Perkins Engines Company Limited
1100 Series 1106A-70TG1 Diesel Engine – ElectropaK
133.5 kWm (179 hp) net prime power @ 1800 rpm
148.4 kWm (199 hp) net standby power @ 1800 rpm

Technical information
l Tropical radiator pipes and guards
l Flywheel housing

l Flywheel and starter ring

l Oil filters

l Starter motor

l Air cleaners and brackets

l Lubricating oil sump

l Alternator

l Induction manifolds

l Exhaust manifolds

l Fuel filter

l Engine mountings

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.
All information in this document is substantially correct at time of printing and may be altered subsequently.
Final weight and dimensions will depend on completed specification.

Publication No. PN3075/04/15 Produced in England ©2015 Perkins Engines Company Limited
1100 Series 1106A-70TG1 Diesel Engine – ElectropaK
133.5 kWm (179 hp) net prime power @ 1800 rpm
148.4 kWm (199 hp) net standby power @ 1800 rpm

760 mm

1092 mm
1648 mm

Engine package weights and dimensions


Length with air cleaner 1648 mm 64.8 in
Width 760 mm 29.9 in
Height 1092 mm 42.9 in
Weight (dry) 725 kg 1598 lb

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.
All information in this document is substantially correct at time of printing and may be altered subsequently.
Final weight and dimensions will depend on completed specification.

Publication No. PN3075/04/15 Produced in England ©2015 Perkins Engines Company Limited
1100 Series 1106A-70TG1 Diesel Engine – ElectropaK
133.5 kWm (179 hp) net prime power @ 1800 rpm
148.4 kWm (199 hp) net standby power @ 1800 rpm

Typical generator Engine power


Speed Type of output (Net) Gross Net
rpm operation
kVA kWe kWm hp kWm hp
Prime power 152.0 122.0 140.5 188.0 133.5 179.0
1800
Standby (maximum) 169.0 135.0 155.4 208.0 148.4 199.0

Fuel consumption at 1800 rpm Fuel consumption at 1800 rpm


Percent of prime power
g/kWh l/hr
110% 209.7 38.8
Prime power 210.9 35.2
75% 210.8 26.5
50% 209.3 18.0
25% 243.1 10.5

www.perkins.com

Photographs are for illustrative purposes only and may not reflect final specification.
All information in this document is substantially correct at time of printing and may be altered subsequently.
Final weight and dimensions will depend on completed specification.

Publication No. PN3075/04/15 Produced in England ©2015 Perkins Engines Company Limited
TAL 044

Low Voltage Alternator - 4 pole


Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz
Dedicated single-phase 57 to 82 kVA - 50 Hz / 80 to 125 kVA - 60 Hz
Electrical and mechanical data
TAL 044 - Three-phase & Single-phase

The best of performance


Nidec Leroy-Somer TAL 044 alternator has been designed to offer you
the best power generation performances. With its meticulous design and
optimized architecture, the TAL 044 strikes the perfect balance between
compactness, reliability, performance and longevity.
Whatever your application, the TAL 044 will meet your needs and will adapt
to all situations.
Standards
Nidec Leroy-Somer TAL 044 alternator meets all key international standards
and regulations, including IEC 60034, NEMA MG 1.32-33, ISO 8528-3,
CSA C22.2 n°100-14 and UL 1446 (UL 1004 on request).
Also compliant with IEC 61000-6-2, IEC 61000-6-3, IEC 61000-6-4,
VDE 0875G, VDE 0875N and EN 55011, group 1 class A for European zone.
Nidec Leroy-Somer TAL 044 alternator can be integrated in EC marked
generator set, and bears EC, EAC and CMIM markings.
It is designed, manufactured and marketed in an ISO 9001 and ISO 14001
quality assurance environment.
Electrical characteristics and performances
● Class H insulation
● Shunt excitation
● Low voltage winding:
- Three-phase 50 Hz: 220V - 240V and 380V - 415V (440V)
60 Hz: 208V - 240V and 380V - 480V
- Single-phase 50 Hz: 230V
60 Hz: 240V
● 4-terminal plates in 6-wire version
● Optimized performance
Excitation and regulation system
Excitation system Regulation options
C.T.
AVR SHUNT AREP+ PMG ULC/US Remote voltage Current transformer
(option) (option) potentiometer for paralleling
R120 Standard
Three-phase R150 Option √
6-wire R180 Standard Standard √ √
D350 Option Option Option √ √ √*
R120 Standard
Three-phase R250 Option √ √
12-wire R180 Standard Standard √ √
D350 Option Option Option √ √ √*
R121 Standard √
Single-phase
R250 Option √ √
*: only with AREP+ or PMG
Protection system and options
● Degree of protection: IP 23
● Complete winding protection for non-harsh environment with relative humidity ≤ 95%
● Options:
- Three-phase 12-wire with 8-terminal plates
- AREP+ or PMG excitation
- ULc/us
- Customized painting (unpainted machine as standard)
- Space heater
- Flying leads
- Droop kit for alternator paralleling
- Dedicated single-phase
- Stator sensors
- Winding 8 optimized for three-phase 380V / 416V - 60Hz
- Reinforced winding protection for harsh environments and relative humidity greater than 95% (system 2 - 4):
for TAL 044 K apply a derating coefficient of 0.97
Mechanical construction
● Compact and rugged assembly to withstand engine vibrations
● Steel frame
● Aluminum flanges and shields
● Single-bearing design compatible with most diesel engines
● Greased for life bearings
● Direction of rotation: clockwise and counterclockwise without derating
Terminal box design
● Easy access to AVR and terminals
● Possibility of current transformer for parallel operation

2 Electric Power Generation


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

General characteristics
Insulation class H Excitation system 6-wire SHUNT AREP+ / PMG
Winding pitch 2/3 (wind.6S - 6-wire / wind.6 - 12-wire) AVR type R120 R180
Number of wires 6 (12 option) Excitation system 12-wire (option) SHUNT AREP+ / PMG
Protection IP 23 AVR type R120 R180
Altitude ≤ 1000 m Voltage regulation (**) ±1% ± 0.5 %
Overspeed 2250 R.P.M. Total Harmonic Distortion THD (***) in no-load <2%
Air flow 50 Hz 0.29 m3/s Total Harmonic Distortion THD (***) in linear load <5%
Air flow 60 Hz 0.34 m3/s Waveform: NEMA = TIF (***) < 50
AREP+/PMG Short-circuit current = 2.7 In : 5 seconds (*) Waveform: I.E.C. = FHT (***) < 2%
(*) D350: 10 seconds (**) Steady state (***) Total harmonic distortion between phases, no-load or on-load (non-distorting)

Ratings 50 Hz - 1500 R.P.M.


kVA / kW - P.F. = 0.8
Duty / T° C Continuous / 40 °C Continuous / 40 °C Stand-by / 40 °C Stand-by / 27 °C
Class / T° K H / 125° K F / 105° K H / 150° K H / 163° K
Phase 3 ph. 1 ph. 3 ph. 1 ph. 3 ph. 1 ph. 3 ph. 1 ph.
Y 380V 400V 415V 440V 380V 400V 415V 440V 380V 400V 415V 440V 380V 400V 415V 440V
∆ 220V 230V 240V 230V 220V 230V 240V 230V 220V 230V 240V 230V 220V 230V 240V 230V
YY (*) 200V 220V 200V 220V 200V 220V 200V 220V
∆∆ (*) 230V 230V 230V 230V
TAL 044 A kVA 70 70 70 63 42 64 64 64 57 38 74 74 74 67 45 77 77 77 69 46
kW 56 56 56 50 33.5 51 51 51 46 30.5 59 59 59 54 36 62 62 62 55 37
TAL 044 B kVA 80 80 80 72 48 73 73 73 66 44 85 85 85 76 51 88 88 88 79 53
kW 64 64 64 58 38.5 58 58 58 53 35 68 68 68 61 41 70 70 70 63 42
TAL 044 C kVA 90 90 90 81 54 82 82 82 74 49 95 95 95 86 57 100 100 100 89 59
kW 72 72 72 65 43 66 66 66 59 39 76 76 76 69 46 80 80 80 71 47
TAL 044 D kVA 100 100 100 90 60 91 91 91 82 55 106 106 106 95 64 110 110 110 99 66
kW 80 80 80 72 48 73 73 73 66 44 85 85 85 76 51 88 88 88 79 53
TAL 044 E kVA 125 125 125 113 67 114 114 114 103 61 133 133 133 120 71 138 138 138 124 74
kW 100 100 100 90 54 91 91 91 82 49 106 106 106 96 57 110 110 110 99 59
TAL 044 H kVA 135 135 135 122 73 123 123 123 111 66 143 143 143 129 77 150 150 150 134 80
kW 108 108 108 98 58 98 98 98 89 53 114 114 114 103 62 120 120 120 107 64
TAL 044 J kVA 150 150 150 135 80 137 137 137 123 73 159 159 159 143 85 165 165 165 149 88
kW 120 120 120 108 64 110 110 110 98 58 127 127 127 114 68 132 132 132 119 70
TAL 044 K kVA 165 165 165 138 88 150 150 150 126 80 175 175 175 150 93 182 182 182 157 97
kW 132 132 132 110 70 120 120 120 101 64 140 140 140 120 74 146 146 146 126 78
TAL 044 L kVA 180 180 180 171 90 164 164 164 156 82 191 191 191 181 95 200 200 200 188 99
kW 144 144 144 137 72 131 131 131 125 66 153 153 153 145 76 160 160 160 150 79
TAL 044 M kVA 192 200 200 192 100 175 182 182 175 91 204 212 212 204 106 211 220 220 211 110
kW 154 160 160 154 80 140 146 146 140 73 163 170 170 163 85 169 176 176 169 88
(*) 12-wire option

Ratings 60 Hz - 1800 R.P.M.


kVA / kW - P.F. = 0.8
Duty / T° C Continuous / 40 °C Continuous / 40 °C Stand-by / 40 °C Stand-by / 27 °C
Class / T° K H / 125° K F / 105° K H / 150° K H / 163° K
Phase 3 ph. 1 ph. 3 ph. 1 ph. 3 ph. 1 ph. 3 ph. 1 ph.
Y 380V 416V 440V 480V 380V 416V 440V 480V 380V 416V 440V 480V 380V 416V 440V 480V
∆ 220V 240V 240V 220V 240V 240V 220V 240V 240V 220V 240V 240V
YY (*) 208V 220V 240V 208V 220V 240V 208V 220V 240V 208V 220V 240V
∆∆ (*) 240V 240V 240V 240V
TAL 044 A kVA 69 76 80 88 46 63 69 73 80 42 73 81 85 93 49 76 84 88 97 51
kW 55 61 64 70 37 50 55 58 64 33.5 58 65 68 74 39 61 67 70 78 41
TAL 044 B kVA 79 87 92 100 52 72 79 84 91 47 84 92 98 106 55 87 96 101 110 57
kW 63 70 74 80 42 58 63 67 73 37.5 67 74 78 85 44 70 77 81 88 46
TAL 044 C kVA 89 98 103 113 59 81 89 94 103 54 94 104 109 120 63 98 108 113 124 65
kW 71 78 82 90 47 65 71 75 82 43 75 83 87 96 50 78 86 90 99 52
TAL 044 D kVA 99 108 115 125 65 90 98 105 114 59 105 114 122 133 69 109 119 127 138 72
kW 79 86 92 100 52 72 78 84 91 47 84 91 98 106 55 87 95 102 110 58
TAL 044 E kVA 124 135 143 156 76 113 123 130 142 69 131 143 152 165 81 136 149 157 172 84
kW 99 108 114 125 61 90 98 104 114 55 105 114 122 132 65 109 119 126 138 67
TAL 044 H kVA 134 146 155 169 81 122 133 141 154 74 142 155 164 179 86 147 161 171 186 89
kW 107 117 124 135 65 98 106 113 123 59 114 124 131 143 69 118 129 137 149 71
TAL 044 J kVA 148 163 172 188 95 135 148 157 171 86 157 173 182 199 101 163 179 189 207 105
kW 118 130 138 150 76 108 118 126 137 69 126 138 146 159 81 130 143 151 166 84
TAL 044 K kVA 165 179 189 206 105 150 163 172 187 96 175 190 200 218 111 182 197 208 227 116
kW 132 143 151 165 84 120 130 138 150 77 140 152 160 174 89 146 158 166 182 93
TAL 044 L kVA 180 195 210 225 113 164 177 191 205 102 191 207 223 239 119 200 215 231 250 124
kW 144 156 168 180 90 131 142 153 164 82 153 166 178 191 95 160 172 185 200 99
TAL 044 M kVA 200 215 230 250 125 182 196 209 228 114 212 228 244 265 133 220 237 253 275 136
kW 160 172 184 200 100 146 157 167 182 91 170 182 195 212 106 176 190 202 220 109
(*) 12-wire option

Electric Power Generation 3


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

Efficiencies 400 V - 50 Hz (— P.F.: 0.8) (...... P.F.: 1)


% TAL 044 A % TAL 044 H
100 100

95 93.4 93.6 93.5 96 94.7 95.1 94.9 94.7


92.4
92.1
90 88.0 92 93.0
90.4 90.8 90.4 90.1 92.8
92.1 91.7
91.0
85 86.6 88

80 kVA 84 kVA
0 20 40 60 80 100 0 50 100 150 200

% TAL 044 B % TAL 044 J


100 100

95 92.9 93.6 93.5 93.3


96 94.9 95.3 95.1 95.0

90 89.1
90.7 90.7 90.0 92.4
89.5 93.3
92 93.2
87.6 92.4
85 92.0
91.3

80 kVA 88 kVA
0 20 40 60 80 100 0 50 100 150 200

% TAL 044 C % TAL 044 K


100 100

95 94.1 94.2 94.1


93.3
96 95.0 95.4 95.3 95.2
89.5
90 91.4 91.7 91.2 90.8 92.4
93.4 93.4
88.2 92 92.8 92.4
85
91.3

80 kVA 88 kVA
0 20 40 60 80 100 120 0 50 100 150 200

% TAL 044 D % TAL 044 L


100 100

95 93.6 94.2 94.1 94.0


95.4 95.8 95.6 95.4
96
90.3
90 91.6 91.6 90.8 93.2
90.4 94.1 94.0
88.9 93.4
92 93.1
85 92.3

80 kVA 88 kVA
0 20 40 60 80 100 120 0 50 100 150 200 250

% TAL 044 E % TAL 044 M


100 100

96 95.1 95.0 94.9


94.5 95.6 95.7
96 95.4 95.2
91.7 93.7
92 92.9 92.9 92.3 92.0 94.1 93.8
90.6 92 92.7 93.0
92.6
88

84 kVA 88 kVA
0 50 100 150 0 50 100 150 200 250

4 Electric Power Generation


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

Efficiencies 480 V - 60 Hz (— P.F.: 0.8) (...... P.F.: 1)


% TAL 044 A % TAL 044 H
100 100

95 93.2 93.6 93.6 96 95.0 95.0 94.9


94.3
91.8

90 92 91.2 93.1
91.0 90.9 90.7 92.9 92.5
86.6 90.1 92.2
90.2
85 88
85.5

80 kVA 84 kVA
0 20 40 60 80 100 120 0 50 100 150 200

% TAL 044 B % TAL 044 J


100 100

95 93.4 93.6 93.5 95.2 95.2 95.1


92.3 94.6
95

90 91.0 91.5 93.2 93.4


87.9 90.5 90.6 90.3 92.9 92.6
90
90.6
85 86.6

80 kVA 85 kVA
0 20 40 60 80 100 120 0 50 100 150 200 250

% TAL 044 C % TAL 044 K


100 100

95 93.9 94.2 94.2 95.3 95.4 95.3


92.8 94.6
95

90 88.3 91.2 91.9 91.6 91.4 91.4 93.6


93.3 93.2 93.0
90 90.6
85 87.2

80 kVA 85 kVA
0 20 40 60 80 100 120 140 0 50 100 150 200 250

% TAL 044 D % TAL 044 L


100 100

95 94.1 94.2 94.1


93.2 95.6 95.6
96 95.1 95.5

90 89.2 91.5 91.8 91.4 91.1


92.3 93.9 94.1
93.6 93.4
88.0 92
85
91.5

80 kVA 88 kVA
0 50 100 150 0 50 100 150 200 250 300

% TAL 044 E % TAL 044 M


100 100

96 94.9 95.0 95.0


94.1 95.3 95.6 95.5 95.4
96

92 90.6 93.1 92.9


92.7 92.7 92.5 94.0 94.0
92 93.4 93.0
88 89.7 92.1

84 kVA 88 kVA
0 50 100 150 200 0 50 100 150 200 250 300

Electric Power Generation 5


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

Reactances (%). Time constants (ms) - Class H / 400 V


A B C D E H J K L M
Kcc Short-circuit ratio 0.57 0.5 0.53 0.48 0.43 0.4 0.4 0.42 0.37 0.33

Xd Direct-axis synchronous reactance unsaturated 294 336 307 341 334 361 359 343 343 381

Xq Quadrature-axis synchronous reactance unsaturated 150 171 156 174 170 184 183 175 175 194

T’do No-load transient time constant 2475 2475 2308 2308 2154 2154 2112 2077 2025 2025

X’d Direct-axis transient reactance saturated 11.9 13.6 13.3 14.7 15.5 16.7 17 16.5 16.9 18.8

T’d Short-circuit transient time constant 100 100 100 100 100 100 100 100 100 100

X”d Direct-axis subtransient reactance saturated 7.1 8.1 7.9 8.8 9.3 10 10.2 9.9 10.1 11.3

T”d Subtransient time constant 10 10 10 10 10 10 10 10 10 10

X”q Quadrature-axis subtransient reactance saturated 16.1 18.3 17 18.9 18.9 20.4 20.4 19.5 19.7 21.9

Xo Zero sequence reactance 0.49 0.56 0.55 0.61 0.64 0.69 0.7 0.68 0.7 0.78

X2 Negative sequence reactance saturated 11.62 13.28 12.53 13.92 14.12 15.25 15.31 14.74 14.96 16.62

Ta Armature time constant 15 15 15 15 15 15 15 15 15 15

Other class H / 400 V data


io (A) No-load excitation current SHUNT 0.84 0.84 0.80 0.80 0.67 0.67 0.66 0.68 0.64 0.64

io (A) No-load excitation current AREP+ 1.08 1.08 1.03 1.03 0.87 0.87 0.85 0.88 0.82 0.82

ic (A) On-load excitation current SHUNT 2.60 2.95 2.75 3.08 2.57 2.78 2.79 2.82 2.69 3.01

ic (A) On-load excitation current AREP+ 3.35 3.80 3.54 3.96 3.31 3.59 3.60 3.63 3.46 3.88

uc (V) On-load excitation voltage SHUNT 28.9 32.5 30.1 33.2 31.9 34.3 34.1 34.1 20.1 22.2

uc (V) On-load excitation voltage AREP+ 23.2 26.1 24.1 26.7 25.6 27.5 27.4 27.4 15.8 17.5

ms Response time (∆U = 20% transient) 500 500 500 500 500 500 500 500 500 500

kVA Start (∆U = 20% cont. or ∆U = 30% trans.) SHUNT* 124 124 143 143 204 205 225 254 318 318

kVA Start (∆U = 20% cont. or ∆U = 30% trans.) AREP+* 203 203 233 233 333 334 366 413 542 543

% Transient ∆U (on-load 4/4) SHUNT - P.F.: 0.8 LAG 17.2 18.8 18.5 19.9 18.2 19.1 19.3 18.9 17.3 18.6

% Transient ∆U (on-load 4/4) AREP+ - P.F.: 0.8 LAG 12.5 13.6 13.4 14.4 13.2 13.8 13.9 13.7 12.2 13

W No-load losses 1980 1980 2175 2175 2322 2322 2478 2785 2665 2665

W Heat dissipation 5903 7091 6931 8053 8255 9254 9769 10184 10134 11898

* P.F. = 0.6

6 Electric Power Generation


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

Reactances (%). Time constants (ms) - Class H / 480 V


A B C D E H J K L M
Kcc Short-circuit ratio 0.55 0.48 0.5 0.46 0.41 0.38 0.38 0.41 0.36 0.32

Xd Direct-axis synchronous reactance unsaturated 308 350 321 355 348 377 375 356 358 397

Xq Quadrature-axis synchronous reactance unsaturated 157 178 164 181 177 192 191 182 182 202

T’do No-load transient time constant 2475 2475 2308 2308 2154 2154 2112 2077 2025 2025

X’d Direct-axis transient reactance saturated 12.4 14.1 13.9 15.4 16.1 17.5 17.7 17.1 17.6 19.6

T’d Short-circuit transient time constant 100 100 100 100 100 100 100 100 100 100

X”d Direct-axis subtransient reactance saturated 7.4 8.5 8.3 9.2 9.7 10.5 10.6 10.3 10.6 11.7

T”d Subtransient time constant 10 10 10 10 10 10 10 10 10 10

X”q Quadrature-axis subtransient reactance saturated 16.8 19.1 17.8 19.7 19.6 21.3 21.3 20.3 20.5 22.8

Xo Zero sequence reactance 0.51 0.59 0.58 0.64 0.67 0.72 0.74 0.71 0.73 0.81

X2 Negative sequence reactance saturated 12.17 13.83 13.1 14.49 14.69 15.91 15.99 15.34 15.59 17.32

Ta Armature time constant 15 15 15 15 15 15 15 15 15 15

Other class H / 480 V data


io (A) No-load excitation current SHUNT 0.84 0.84 0.79 0.79 0.67 0.67 0.66 0.68 0.63 0.63

io (A) No-load excitation current AREP+ 1.08 1.08 1.02 1.02 0.87 0.87 0.85 0.87 0.82 0.82

ic (A) On-load excitation current SHUNT 2.60 2.91 2.72 3.01 2.58 2.79 2.79 2.79 2.69 3.00

ic (A) On-load excitation current AREP+ 3.34 3.76 3.51 3.88 3.32 3.59 3.60 3.59 3.47 3.87

uc (V) On-load excitation voltage SHUNT 29.3 32.6 30.3 33.3 32.4 34.8 34.7 34.4 20.4 22.6

uc (V) On-load excitation voltage AREP+ 23.5 26.2 24.4 26.7 26 28 27.8 27.6 16.1 17.8

ms Response time (∆U = 20% transient) 500 500 500 500 500 500 500 500 500 500

kVA Start (∆U = 20% cont. or ∆U = 30% trans.) SHUNT* 149 150 172 172 246 246 270 304 381 381

kVA Start (∆U = 20% cont. or ∆U = 30% trans.) AREP+* 244 244 279 281 401 402 438 498 648 650

% Transient ∆U (on-load 4/4) SHUNT - P.F.: 0.8 LAG 17.7 19.3 19.1 20.4 18.6 19.7 19.9 19.4 17.8 19.1

% Transient ∆U (on-load 4/4) AREP+ - P.F.: 0.8 LAG 12.9 14 13.8 14.7 13.5 14.2 14.3 14 12.5 13.4

W No-load losses 2905 2905 3189 3189 3417 3417 3639 4070 3923 3923

W Heat dissipation 7042 8265 8222 9378 9683 10805 11438 11913 12145 14130

* P.F. = 0.6

Electric Power Generation 7


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

Transient voltage variation 400V - 50 Hz

A B CD E H J K L M A B CD E H J K L M
30% 30%

25% 25%

20% 20%
Voltage drop

Voltage drop
15% 15%

10% 10%

5% 5%

0% 0%
0 50 100 150 200 250 300 350 400 0 100 200 300 400 500 600

Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP+) - kVA at P.F. = 0.8

AB CD E H J K LM AB CD E H J K LM
30% 30%

25% 25%

20% 20%
Voltage rise

Voltage rise

15% 15%

10% 10%

5% 5%

0% 0%
0 50 100 150 200 250 0 50 100 150 200 250

Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP+) - kVA at P.F. = 0.8

AB CD EH J K L M AB CD EH J K L M
30% 30%

25% 25%

20% 20%
Voltage drop

Voltage drop

15% 15%

10% 10%

5% 5%

0% 0%
0 50 100 150 200 250 300 350 0 100 200 300 400 500 600

Motor starting (SHUNT) Motor starting (AREP+)


Locked rotor kVA at P.F. = 0.6 Locked rotor kVA at P.F. = 0.6

- For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
- For voltages other than 400V (Y), 230V (Δ) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.
- Transient performance of the PMG option, consult us.

8 Electric Power Generation


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

Transient voltage variation 480V - 60 Hz

A B CD E H J K L M A B CD E H J K L M
30% 30%

25% 25%

20% 20%
Voltage drop

Voltage drop
15% 15%

10% 10%

5% 5%

0% 0%
0 100 200 300 400 500 0 100 200 300 400 500 600 700

Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP+) - kVA at P.F. = 0.8

AB CD E H J K LM AB CD E H J K LM
30% 30%

25% 25%

20% 20%
Voltage rise

Voltage rise

15% 15%

10% 10%

5% 5%

0% 0%
0 50 100 150 200 250 300 0 50 100 150 200 250 300

Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP+) - kVA at P.F. = 0.8

AB CD EH J K L M AB CD EH J K L M
30% 30%

25% 25%

20% 20%
Voltage drop

Voltage drop

15% 15%

10% 10%

5% 5%

0% 0%
0 50 100 150 200 250 300 350 400 0 100 200 300 400 500 600 700

Motor starting (SHUNT) Motor starting (AREP+)


Locked rotor kVA at P.F. = 0.6 Locked rotor kVA at P.F. = 0.6

- For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
- For voltages other than 480V (Y), 277V (Δ), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
- Transient performance of the PMG option, consult us.

Electric Power Generation 9


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

3-phase short-circuit curves at no load and rated speed (star connection Y)

10000

TAL 044 A
1000
Symmetrical --------
Asymmetrical - - - AREP+
100 In
Current (A)

10 SHUNT

1
1 10 100 1000 5000

Time (ms)

10000

TAL 044 B
1000
Symmetrical --------
Asymmetrical - - - AREP+
100 In
Current (A)

10 SHUNT

1
1 10 100 1000 5000

Time (ms)

10000

TAL 044 C
1000

Symmetrical -------- AREP+


Asymmetrical - - -
In
100
Current (A)

10 SHUNT

1
1 10 100 1000 5000

Time (ms)

Influence due to connection


For (Δ) connection, use the following multiplication factor:
- Current value x 1.732.

10 Electric Power Generation


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

3-phase short-circuit curves at no load and rated speed (star connection Y)

10000

TAL 044 D
1000
Symmetrical -------- AREP+
Asymmetrical - - -
In
100
Current (A)

10 SHUNT

1
1 10 100 1000 5000

Time (ms)

10000

TAL 044 E
1000
Symmetrical -------- AREP+
Asymmetrical - - - In
100
Current (A)

10 SHUNT

1
1 10 100 1000 5000

Time (ms)

10000

TAL 044 H
1000

Symmetrical -------- AREP+


Asymmetrical - - - In
100
Current (A)

10 SHUNT

1
1 10 100 1000 5000

Time (ms)

Influence due to short-circuit 3 - phase 2 - phase L / L 1 - phase L / N


Curves are based on a three-phase short-circuit. Instantaneous (max.) 1 0.87 1.3
For other types of short-circuit, Continuous 1 1.5 2.2
use the following multiplication factors. Maximum duration (AREP+/PMG) 1.5

Electric Power Generation 11


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

3-phase short-circuit curves at no load and rated speed (star connection Y)

10000

TAL 044 J
1000
Symmetrical -------- AREP+
Asymmetrical - - - In
100
Current (A)

10
SHUNT

1
1 10 100 1000 5000

Time (ms)

10000

TAL 044 K
1000
Symmetrical -------- AREP+
Asymmetrical - - - In
100
Current (A)

SHUNT
10

1
1 10 100 1000 5000

Time (ms)

Influence due to connection


For (Δ) connection, use the following multiplication factor:
- Current value x 1.732.

12 Electric Power Generation


TAL 044 - Three-phase 70 to 200 kVA - 50 Hz / 88 to 250 kVA - 60 Hz

3-phase short-circuit curves at no load and rated speed (star connection Y)

10000

TAL 044 L
1000
AREP+
Symmetrical --------
In
Asymmetrical - - -
100
Current (A)

SHUNT
10

1
1 10 100 1000 5000

Time (ms)

10000

TAL 044 M
1000
AREP+
Symmetrical --------
In
Asymmetrical - - -
100
Current (A)
Current (A)

10
SHUNT

1
1 10 100 1000 5000

Time (ms)

Influence due to short-circuit 3 - phase 2 - phase L / L 1 - phase L / N


Curves are based on a three-phase short-circuit. Instantaneous (max.) 1 0.87 1.3
For other types of short-circuit, Continuous 1 1.5 2.2
use the following multiplication factors. Maximum duration (AREP+/PMG) 1.5

Electric Power Generation 13


TAL 044 - Dedicated single-phase 57 to 82 kVA - 50 Hz / 80 to 125 kVA - 60 Hz

General characteristics
Insulation class H Excitation system SHUNT
Winding pitch 2/3 (wind. M 50 Hz, M1 60 Hz) AVR type R121
Number of wires 4 Voltage regulation (*) ±1%
Protection IP 23 Total Harmonic Distortion THD (**) in no-load < 3.5 %
Altitude ≤ 1000 m Total Harmonic Distortion THD (**) in linear load <5%
Overspeed 2250 R.P.M. Waveform: NEMA = TIF (**) < 100
Air flow 0.25 m3/s (50 Hz) / 0.30 m3/s (60 Hz) Waveform: I.E.C. = FHT (**) <2%
(*) Steady state (**) Total harmonic distortion between phases, no-load or on-load (non-distorting)

Ratings / Efficiencies 50 Hz - 1500 R.P.M. - Winding M


kVA / kW - P.F. = 1(*)
Duty / T° C Continuous / 40 °C Stand-by / 40 °C Stand-by / 27 °C
Class / T° K H / 125° K F / 105° K H / 150° K H / 163° K
Serie (SE) 230 V Ƞ% 230 V 230 V 230V Ƞ%

TAL 044 C 57 91 52 60 63 90.7

TAL 044 D1 69 91.5 63 73 76 91.1

TAL 044 E - - - - - -

TAL 044 J 82 92.3 75 87 90 92

TAL 044 K - - - - - -

(*) For P.F. 0.8: derating 15%

Ratings / Efficiencies 60 Hz - 1800 R.P.M. - Winding M1


kVA / kW - P.F. = 1(*)
Duty / T° C Continuous / 40 °C Stand-by / 40 °C Stand-by / 27 °C
Class / T° K H / 125° K F / 105° K H / 150° K H / 163° K
Serie (SE) 240 V Ƞ% 240 V 240 V 240V Ƞ%

TAL 044 C 80 90 73 85 88 89.7

TAL 044 D1 100 90 91 106 110 89.7

TAL 044 E 115 90.7 105 122 127 90.2

TAL 044 J - - - - - -

TAL 044 K 125 91.7 114 133 138 91.4

(*) For P.F. 0.8: derating 15%

Starting motor 230V - 50Hz Starting motor 240V - 60Hz


C D1 J C D1
30% 30%
E

25% 25% K
Voltage droop

20% 20%

15% 15%

10% 10%

5% 5%

0% 0%
0 50 100 150 200 250 0 50 100 150 200 250

Locked rotor kVA at PF : 0.9

14 Electric Power Generation


TAL 044 - Three-phase & Single-phase

Single-bearing dimensions
L 572
LB 383
AH 285 84 187 Access to
A.V.R.
4 Xg Access to terminals

XBG Ø S holes
equid. on Ø M

330
266.5
Ø N - 0.127
- 0.050
Ø BX - 0.150

15°
+0
ØP

Ø444

+1
H -3
Access to
diodes X Ø Y holes
Z W equid. on Ø U
Air inlet 6*
Air outlet A1
137 Z2 184 A2 *L, M = 8 mm

6.5 C Z1

Dimensions (mm) and weight Shaft height (mm) Coupling


Type L maxi * LB Xg Weight (kg) Standard Option Flange 1 2 3 4
TAL 044 A 758 677 293 247 H 270 225* 280** Flex plate
TAL 044 B 758 677 293 247 Feet length 14 x - - -
TAL 044 C 758 677 313 280 C 405 332.5 429 11 ½ x x x -
TAL 044 D 758 677 313 280 A1 406 356 457 10 x x x x
TAL 044 D1 758 677 313 280 A2 474 474 541 8 - - x x
TAL 044 E 828 747 353 353 Z 20 14.5 20
TAL 044 H 828 747 353 353 Z1 25 20 25
TAL 044 J 828 747 365 383 Z2 50 40 50
TAL 044 K 868 787 383 418 W 150 120 150
TAL 044 L 953 872 416 539 * Not available for L and M
TAL 044 M 953 872 416 539 ** Available only for L and M
* L maxi = LB + AH maxi + 19
Flange (mm) Flex plate (mm)
S.A.E. P N M S XBG S.A.E. BX U X Y AH
4 400 361.95 381 11 12 14 466.72 438.15 8 14 25.4
3 445 409.58 428.62 11 12 11 ½ 352.42 333.38 8 11 39.6
2 485 447.68 466.72 11 12 10 314.32 295.28 8 11 53.8
1 560.5* 511.18 530.23 12 10 8 263.52 244.48 6 11 62
* L and M = 550 mm
Xr
Torsional analysis data
Ø 75*
Ø 40

Ø 72

Ø 40
Ø 70

*L, M = Ø 85 mm
Lr

Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flex plate S.A.E. 8 S.A.E. 10 S.A.E. 11 ½ S.A.E. 14
Type Xr Lr M J Xr Lr M J Xr Lr M J Xr Lr M J
TAL 044 A 352.4 727 107.1 0.739 362.4 719 107.2 0.753 349.3 704 106.8 0.769 298.6 711 113.8 0.899
TAL 044 B 352.4 727 107.1 0.739 362.4 719 107.2 0.753 349.3 704 106.8 0.769 298.6 711 113.8 0.899
TAL 044 C 362.5 727 120.9 0.863 353.2 719 121.0 0.877 340.3 704 120.6 0.893 310.0 711 127.6 1.023
TAL 044 D 362.5 727 120.9 0.863 353.2 719 121.0 0.877 340.3 704 120.6 0.893 310.0 711 127.6 1.023
TAL 044 D1 362.5 727 120.9 0.863 353.2 719 121.0 0.877 340.3 704 120.6 0.893 310.0 711 127.6 1.023
TAL 044 E 408.5 797 153.6 1.137 398.5 789 153.7 1.151 385.4 774 153.3 1.167 357.3 781 160.2 1.297
TAL 044 H 408.5 797 153.6 1.137 398.5 789 153.7 1.151 385.4 774 153.3 1.167 357.3 781 160.2 1.297
TAL 044 J 419.4 797 165.4 1.244 409.3 789 165.5 1.258 396.2 774 165.1 1.274 368.8 781 172.0 1.404
TAL 044 K 439.4 837 180.7 1.379 429.2 829 180.8 1.393 416.0 814 180.4 1.409 389.2 821 187.4 1.539
TAL 044 L 480.9 922 221.1 1.713 471.3 914 221.2 1.727 458.3 899 220.8 1.743 449.6 906 227.8 1.873
TAL 044 M 480.9 922 221.1 1.713 471.3 914 221.2 1.727 458.3 899 220.8 1.743 449.6 906 227.8 1.873

NOTE : Dimensions are for information only and may be subject to modifications. The torsional analysis of the transmission is imperative. All values are available
upon request.

Electric Power Generation 15


www.leroy-somer.com/epg

Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel

© Nidec 2020. The information contained in this brochure is for guidance only and does not form part of
any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of development
and reserve the right to change the specification of their products without notice.

Moteurs Leroy-Somer SAS. Siège : Bd Marcellin Leroy, CS 10015, 16915 Angoulême Cedex 9, France.
Capital social : 38 679 664 €, RCS Angoulême 338 567 258.

5674 en - 2021.06 / m
®

DSEGenset

DSE7310/20 ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY

AUTO START & AUTO MAINS FAILURE BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
CONTROL MODULES BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

The DSE7310 is an Auto Start The DSE7320 will also monitor the The extensive list of features TEMPERATURE
Control Module and the DSE7320 is mains (utility) supply. The modules includes enhanced event and BS EN 60068-2-1
o
Ab/Ae Cold Test -30 C
an Auto Mains (Utility) Failure include USB, RS232 and RS485 performance monitoring, remote BS EN 60068-2-2
Control Module suitable for a wide ports as well as dedicated communications, PLC functionality Bb/Be Dry Heat +70 oC
variety of single, diesel or gas, DSENet® terminals for system and dual mutual standby (DSE7310 VIBRATION
gen-set applications. expansion. only) to reduce engine wear. BS EN 60068-2-6
Ten sweeps in each of three
major axes
Monitoring an extensive number of Both modules are compatible with The modules can be easily 5 Hz to 8 Hz @ +/-7.5 mm,
engine parameters, the modules will electronic (CAN) and non-electronic configured using the DSE 8 Hz to 500 Hz @ 2 gn
display warnings, shutdown and (magnetic pick-up/alternator Configuration Suite PC software. HUMIDITY
engine status information on the sensing) engines and offer an Selected front panel editing is also BS EN 60068-2-30
back-lit LCD screen, illuminated extensive number of flexible inputs, available. Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
LEDs, remote PC and via SMS text outputs and extensive engine BS EN 60068-2-78
alerts (with external modem). protections so the system can be Cab Damp Heat Static 40 oC
easily adapted to meet the most @ 93% RH 48 Hours

demanding industry requirements. SHOCK


BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
MODEM MODBUS PC
DSE2130
DSE2157
DSE2548 8 4 4
DSE2510/20
232 485

DSENET® RS232 AND USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER


EXPANSION RS485 PORT INPUTS SENDERS STOP SUPPLY 8-35V

DEUTZ
DSE7310/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) N/C VOLT FREE N/O VOLT GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT FREE OUTPUT ALTERNATOR OUTPUTS ENGINES &
DSE7320 ONLY (Flexible with CAN) MAGNETIC PICK-UP

VOLTS CURRENT VOLTS


D+
W/L +

1ph 1 1 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N
N

ISSUE 6
®

DSEGenset

SPECIFICATION

DSE7310/20 DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
AUTO START & AUTO MAINS FAILURE CRANKING DROPOUTS
CONTROL MODULES Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
FEATURES LEDs and backlight will not be maintained
DSE7320 during cranking.

MAXIMUM OPERATING CURRENT


340 mA at 12 V, 160 mA at 24 V

MAXIMUM STANDBY CURRENT


DSE7310 160 mA at 12 V, 80 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

MAINS (UTILITY) DSE7320 ONLY


VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
KEY FEATURES • LED and LCD alarm indication KEY BENEFITS
• 4-Line back-lit LCD text display • Power monitoring (kW h, kV Ar, • 132 x 64 pixel ratio display for OUTPUT B (START)
15 A DC at supply voltage
• Five key menu navigation kV A h, kV Ar h) clarity
• Front panel editing with PIN • Load switching (load shedding • Real-time clock provides OUTPUTS C & D
protection and dummy load outputs) accurate event logging 8 A 250 V (Volt free)
• Customisable status screens • Automatic load transfer (DSE7320) • Multiple date and time scheduler AUXILIARY OUTPUTS E,F,G,H
• Power save mode • Unbalanced load protection • Set maintenance periods can 2 A DC at supply voltage
• Support for up to three remote • Independent Earth Fault trip be configured to maintain
GENERATOR
display units • True dual mutual standby with load optimum engine performance VOLTAGE RANGE
• 9 configurable inputs balancing timer (DSE7310 only) • Ethernet communications (via 15 V to 415 V AC (Ph to N)
• 8 configurable outputs • USB connectivity DSE855 module), provides 26 V to 719 V AC (Ph to Ph)
• Flexible sender inputs • Backed up real time clock advanced remote monitoring FREQUENCY RANGE
• Configurable timers and alarms • Fully configurable via DSE • Modules can be integrated into 3.5 Hz to 75 Hz
• 3 configurable maintenance Configuration Suite PC software building management systems
MAGNETIC PICK UP
alarms • Configurable display languages (BMS) VOLTAGE RANGE
• Multiple date and time scheduler • Remote SCADA monitoring via • Increased input and output +/- 0.5 V to 70 V
• Configurable event log (250) DSE Configuration Suite PC expansion capability via DSENet®
FREQUENCY RANGE
• Tier 4 CAN engine support software • Licence-free PC software 10,000 Hz (max)
• Integral PLC editor • User selectable RS232 and • IP65 rating (with supplied
• Easy access diagnostic page RS485 communications gasket) offers increased DIMENSIONS
OVERALL
• CAN and Magnetic Pick-up/Alt. • Configurable Gencomm pages resistance to water ingress 240 mm x 181 mm x 42 mm
sensing • Advanced SMS messaging • PLC editor allows user 9.4” x 7.1” x 1.6”
• Fuel usage monitor and low fuel (additional external modem configurable functions to meet
PANEL CUT-OUT
alarms required) specific application 220 mm x 160 mm
• Charge alternator failure alarm • Start & stop capability via SMS requirements 8.7” x 6.3”
• Manual speed control (on messaging
MAXIMUM PANEL THICKNESS
compatible CAN engines) • Additional display screens to 8 mm
• Manual fuel pump control help with modem diagnostics 0.3”
• Engine exerciser • Idle control for starting &
OPERATING TEMPERATURE RANGE
• “Protections disabled” feature stopping. -30°C to +70°C
• kW & kV Ar protection • DSENet® expansion compatible
• Reverse power (kW & kV Ar) • Heated display option available STORAGE TEMPERATURE RANGE
-40°C to +80°C
protection

RELATED MATERIALS
TITLE PART NO’S
DSE7310 Installation Instructions 053-028
DSE7320 Installation Instructions 053-029
DSE7200/7300 Quick Start Guide 057-101
DSE7200/7300 Operator Manual 057-074
DSE7200/7300 Configuration Suite PC Manual 057-077

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-051/10/11 (14)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457
1 2 3 4 5 6 7 8

Group Chasis Canopy


5 S2700T1200H25 K386H120

A Bolted maintenance cover A


Service doors Lifting point 2x
Air inlet Control panel door Exhaust cap

1601
1946
1879
B B

250
400 2700 760

150
1000 Cable inlet 325
1140 (120x70)

Air outlet 1200

C C

1132
1200
1234
695
3860
3872

D 14 Connection to ground D
1070

E E
Name Date Document No
Tolerances SM-170753761
400

0
150
380

765
995

1590
1820

2320
2550
2700

3460

Drawn Fatih Unlu 10-07-2017


ISO 2768
Checked Hurcan Sevincli 24-10-2018 Part Code
1. Projection Method Approval Ali Bilsel 25-10-2018
** Paper Size Scale Order No Rev. No Title
Group5 Gen-set
A3 1:29 - R00
Please do not take measures on the drawings.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

OPTIONAL CHASSIS - DOUBLE WALL Double Wall Lifting Point

A A

Fuel Drain
Fuel Fill / Gauge Fuel In / Out

B B

C C
L

Lifting Point

C W C

H
Cable Inlet

D D

SECTION C-C Fuel Tank


Drain Point SCALE 1 : 15 Double Wall Drain Point
Optional Fuel Heater

E E
Name Date Document No
Tolerances
Drawn Ozkan Kardas 13-02-2013
ISO 2768
Checked Part Code
1. Projection Method Approval Baris Dogan 13-06-2013
*1510112133* Paper Size Scale Order No Rev. No Title

Please do not take measures on the drawings.


A3 1:20 R00 OPTIONAL CHASSIS - DOUBLE WALL
1 2 3 4 5 6 7 8