A pad footing is required to resist characteristic axial loads of 1000kN permanent and 350kN variable from a
400mm square column. The safe bearing pressure on the soil is 200kN/m2 and the characteristic material strengths
are fck = 30 N/mm2 and fyk = 500 N/mm2.
Solution
Column dimensions: c1 ≔ 400 mm c2 ≔ 400 mm
Materials:
Concrete characteristic strength: fck ≔ 30 MPa
kN
Safe soil bearing capacity: qa ≔ 200 ――
Loading: m2
Gk ≔ 1000 kN
Qk ≔ 350 kN
Assume a footing weight approximately equal to 10% to 15% of the total service load, so that the total permanent
load is calculated and base the design on the Prescriptive Method.
The weight of the footing:
Wpad ≔ 0.111 ⋅ ((1000 + 350)) kN = 150 kN
1. The base plan area is determined for serviceability limit state, the total design axial load
P ≔ 1.0 ⋅ Gk + 1.0 ⋅ Qk + Wpad = 1500 kN
P
Minimum pad area: Amin ≔ ―= 7.5 m 2 Take base area: Ab ≔ 7.84 m 2
qa
2. Structural design of footing is performed for ultimate limit state – where load combination 1 will give the
largest set of actions for this simple structure. Hence, using the partial safety factors for load combination 1:
Column design axial load excluding pad's self-weight,
At the column perimeter, or the perimeter of the loaded area, the maximum punching shear resistance of
concrete base:
CEng
Written by: Abebe W.
At the column perimeter, or the perimeter of the loaded area, the maximum punching shear resistance of
concrete base:
Column perimeter and area: u ≔ 2 ⋅ c1 + 2 ⋅ c2 = 1.6 m Acp ≔ c1 ⋅ c2
VEd N
vEd ≔ ―― = 2.21 ――
u⋅d mm 2
Check1 ≔ if vEd < vRdmax | = “Max. Shear is OK”
‖ “Max. Shear is OK” |
‖ |
else |
‖ “Not OK” |
‖ ||
And carry out preliminary check for punching shear resistance of concrete at the basic control perimeter to
ensure that the footing thickness gives a punching shear stress which is within the likely range of acceptable
performance. The basic control perimeter for checking punching shear is at a distance 2d.
Basic control perimeter: u1 ≔ 2 ⋅ c1 + 2 ⋅ c2 + 4 π ⋅ d = 8135 mm
Area within perimeter: Ap ≔ ⎛⎝c1 + 4 ⋅ d⎞⎠ ⋅ ⎛⎝c2 + 4 ⋅ d⎞⎠ - ⎛⎝4 ⋅ ((2 ⋅ d)) 2 - π ⋅ ((2 ⋅ d)) 2 ⎞⎠ = 5.22 m 2
This applied punching shear stress shall be less than the punching shear resistance of concrete, which will
be checked later on.
4. Bending moment resistance - the critical section for bending is at the column face and one of the two sides is
enough for check for square geometry.
The applied bending moment:
⎛ B c2 ⎞ 2
⎜―- ―⎟
⎝2 2⎠
MEd ≔ qu ⋅ L ⋅ ―――― = 482 kN ⋅ m
2
MEd
K ≔ ―――― = 0.021
fck ⋅ L ⋅ d 2
Check2 ≔ if K < 0.167 | = “Provide only bot. tension steel”
‖ “Provide only bot. tension steel” |
‖ |
else |
‖ “Provide bot. and top steel” |
‖ |
The lever arm
⎛ ⎛ ⎞ ⎞
z ≔ min ⎝0.5 ⋅ d ⋅ ⎝1 + ‾‾‾‾‾‾‾‾‾‾
1 - 3.527 ⋅ K ⎠ , 0.95 ⋅ d⎠ = 494 mm
100 ⋅ Asreq
Therefore, the rebar percentage: ρs ≔ ―――― = 0.154
L⋅d
⎛ ⎛ fck ⎞ 0.667 ⎞
⎜ 26 ⋅ 0.3 ⋅ ⎜――― ⎟ ⎟
⎜ ⎝ 1 MPa ⎠ ⎟
ρsmin ≔ max ―――――――MPa , 0.13 = 0.151
⎜ f ⎟
⎝ yk ⎠
ρsprov ≔ max ⎛⎝ρs , ρsmin⎞⎠ = 0.154
ρsprov ⋅ L ⋅ d
The area of rebar to be provided: Aprov ≔ ―――― = 2244 mm 2
100
π ⋅ ϕ2
Asprov ≔ n ⋅ ―― = 2413 mm 2
4
⎛ fck ⎞ 0.5
vmin ≔ 0.035 MPa ⋅ k 1.5 ⋅ ⎜――― ⎟ = 0.4 MPa
⎝ 1 MPa ⎠
⎛ ⎛ fck ⎞ 0.333 ⎞
⎜
vRdc ≔ max 0.12 MPa ⋅ k ⋅ ⎜100 ⋅ ρ1 ⋅ ――― ⎟ , vmin⎟ = 0.4 MPa
⎝ ⎝ 1 MPa ⎠ ⎠
7. Where applicable, both foundation and structure shall be checked for overall stability at ULS:
8. Detailing - bending reinforcements at the bottom of the base should extend at least a full tension anchorage
length beyond the critical section of bending using bends if necessary at the outer edges of the base.
CEng
Written by: Abebe W.
kN
Safe soil bearing capacity: qa ≔ 200 ――
Loading: m2
Gk ≔ 1200 kN Gmk ≔ 250 kN ⋅ m
Qk ≔ 550 kN Qmk ≔ 200 kN ⋅ m
Assume a footing weight approximately equal to 10% to 15% of the total service load, so that the total permanent
load is calculated, and base the design on the Prescriptive Method.
Assume weight of the pad: Wpad ≔ 0.15 ⋅ ⎛⎝Gk + Qk⎞⎠ = 263 kN
1. The base plan area is determined for serviceability limit state, the total design axial load is
P ≔ 1.0 ⋅ Gk + 1.0 ⋅ Qk + Wpad = 2013 kN
P
Pad area: A ≔ ―= 10.06 m 2 Take base area: A' ≔ 10.1 m 2
qa
Adding additional 25% area for moment, the minimum pad area: Amin ≔ 1.25 ⋅ A' = 12.6 m 2
Ab ≔ 14.06 m 2
Provide a square base with: B ≔ ‾‾‾
Ab = 3.75 m L≔B
Calculate the load eccentricity, e
M ≔ Gmk + Qmk = 450 kN ⋅ m
M
e ≔ ―= 0.224 m
P
For no tension requirement:
B |
if e < ― | = “No tension”
6 |
‖ “No tension” |
‖ |
else |
‖ “Adjust the base” |
‖ |
1
y ≔ 0.5 ⋅ B I ≔ ― ⋅ L ⋅ B3
12
P M⋅y kN P M⋅y kN
qmax ≔ ― + ――= 194 ―― qmin ≔ ― - ――= 92 ――
Ab I m2 Ab I m2
check1 ≔ if qmax > qa | = “Base area is OK!”
‖ “Increase the base area” |
‖ |
else |
‖ “Base area is OK!” |
‖ ||
2. Structural design of footing is performed for ultimate limit state – where load combination 1 will give the
largest set of actions for this simple structure. Hence, using the partial safety factors for load combination 1,
column design axial load pad's excluding self-weight
CEng
Written by: Abebe W.
2. Structural design of footing is performed for ultimate limit state – where load combination 1 will give the
largest set of actions for this simple structure. Hence, using the partial safety factors for load combination 1,
column design axial load pad's excluding self-weight
MEdx
Kx ≔ ―――― = 0.02
fck ⋅ B ⋅ d 2
Check2 ≔ if Kx < 0.167 | = “Provide only bot. tension steel”
‖ “Provide only bot. tension steel” |
‖ |
else |
‖ “Provide bot. and top steel” |
‖ ||
The lever arm
zx ≔ min ⎛⎝0.5 ⋅ d ⋅ ⎛⎝1 + ‾‾‾‾‾‾‾‾‾‾
1 - 3.527 ⋅ Kx ⎞⎠ , 0.95 ⋅ d⎞⎠ = 522.5 mm
The required rebar area is
MEdx
Asreqx ≔ ――――= 3904 mm 2
0.87 ⋅ fyk ⋅ zx
100 ⋅ Asreqx
Therefore, the rebar percentage: ρsx ≔ ―――― = 0.189
B⋅d
⎛ ⎛ fck ⎞ 0.667 ⎞
⎜ 26 ⋅ 0.3 ⋅ ⎜――― ⎟ ⎟
⎜ ⎝ 1 MPa ⎠ ⎟
ρsminx ≔ max ―――――――MPa , 0.13 = 0.183
⎜ f ⎟
⎝ yk ⎠
ρprovx ⋅ B ⋅ d
The area of rebar to be provided: Aprovx ≔ ――――= 3904 mm 2
100
Therefore from table 6.9 the maximum allowable bar size is 16 mm. Hence, minimum area and bar size
requirements as specified by the code for the purposes of crack control are met.
Moment in y- direction:
To calculate the design bending moment on pad, first
⎛⎝qmax' - qmin'⎞⎠ kN
qcfy ≔ qmin' + ――――― ⋅ ⎛⎝B + c1⎞⎠ = 183 ――
2⋅B m2
lx ≔ 0.5 ⋅ ⎛⎝B - c1⎞⎠ = 1.65 m
Then,
2
lx 2
MEdy ≔ 0.5 ⋅ qcfy ⋅ L ⋅ lx ⎛ ⎞
+ ⎝qmax' - qcfy⎠ ⋅ L ⋅ ―― = 1149 kN ⋅ m
3
MEdy
Ky ≔ ―――― = 0.025
fck ⋅ L ⋅ d 2
Check3 ≔ if Ky < 0.167 | = “Provide only bot. tension steel”
‖ “Provide only bot. tension steel” |
‖ |
else |
‖ “Provide bot. and top steel” |
‖ ||
The lever arm
zy ≔ min ⎛⎝0.5 ⋅ d ⋅ ⎛⎝1 + ‾‾‾‾‾‾‾‾‾‾
1 - 3.527 ⋅ Ky ⎞⎠ , 0.95 ⋅ d⎞⎠ = 522.5 mm
The required rebar area is
MEdy
Asreqy ≔ ――――= 5056 mm 2
0.87 ⋅ fyk ⋅ zy
100 ⋅ Asreqy
Therefore, the rebar percentage: ρsy ≔ ―――― = 0.245
L⋅d
⎛ ⎛ fck ⎞ 0.667 ⎞
⎜ 26 ⋅ 0.3 ⋅ ⎜――― ⎟ ⎟
⎜ ⎝ 1 MPa ⎠ ⎟
ρsminy ≔ max ―――――――MPa , 0.13 = 0.183
⎜ f ⎟
⎝ yk ⎠
ρprovy ≔ max ⎛⎝ρsy , ρsminy⎞⎠ = 0.245
ρprovy ⋅ L ⋅ d
The area of rebar to be provided: Aprovy ≔ ―――― = 5056 mm 2
100
π ⋅ ϕy 2
Asprovy ≔ ny ⋅ ――― = 5341 mm 2
4
5. Punching shear resistance – check at both column face and basic control perimeter. The maximum punching
shear stress in concrete at any section considered should not be exceeded:
⎛ ⎛ fck ⎞⎞ fck N
vRdmax ≔ 0.5 ⋅ ⎜0.6 ⋅ ⎜1 - ―――― ⎟⎟ ⋅ ――= 6.72 ――
⎝ ⎝ 250 MPa ⎠⎠ 1.5 mm 2
The maximum punching shear resistance of concrete base at the section considered, at the column
perimeter, or the perimeter of the loaded area:
Column perimeter & area: u ≔ 2 ⋅ c1 + 2 ⋅ c2 = 1.8 m Acp ≔ c1 ⋅ c2
VEd N
vEd ≔ ―― = 2.43 ――
u⋅d mm 2
And carry out preliminary check for punching shear resistance of concrete at the basic control perimeter to
ensure that the footing thickness gives a punching shear stress which is within the likely range of acceptable
performance. The basic control perimeter for checking punching shear is at a distance 2d.
Basic control perimeter: u1 ≔ 2 ⋅ c1 + 2 ⋅ c2 + 4 π ⋅ d = 8712 mm
Area within perimeter: Ap ≔ ⎛⎝c1 + 4 ⋅ d⎞⎠ ⋅ ⎛⎝c2 + 4 ⋅ d⎞⎠ - ⎛⎝4 ⋅ ((2 ⋅ d)) 2 - π ⋅ ((2 ⋅ d)) 2 ⎞⎠ = 5.98 m 2
MEdav u1
β ≔ 1 + k' ⋅ ――― ⋅ ――= 1.5
VEd2 W1
VEd N
vEd' ≔ β' ⋅ ―― = 6.09 ―― VEd' ≔ vEd' ⋅ u ⋅ d = 6030 kN
u⋅d mm 2
Check4 ≔ if vEd' < vRdmax | = “Max. Shear is OK”
‖ “Max. Shear is OK” |
‖ |
else |
‖ “Not OK” |
‖ ||
kN
qdx ≔ qav = 174 ――
m2
VEd1x ≔ qav ⋅ B ⋅ ll = 717 kN
The beam shear resistance of concrete:
VRd.cx ≔ vRdc ⋅ B ⋅ d = 927 kN
Shear in y- direction:
The applied beam shear force at d where
lb ≔ 0.5 ⋅ ⎛⎝B - c1⎞⎠ - d
⎛⎝qmax' - qmin'⎞⎠ kN
qdy ≔ ――――― ⎛⎝0.5 ⋅ ⎛⎝B + c1⎞⎠ + d⎞⎠ + qmin' = 204 ――
B m2
VEd1y ≔ qdy ⋅ L ⋅ lb + 0.5 ⋅ ⎛⎝qmax' - qdy⎞⎠ ⋅ lb ⋅ L = 929 kN
7. Where applicable, both foundation and structure shall be checked for overall stability at ULS:
8. Detailing - bending reinforcements at the bottom of the base should extend at least a full tension anchorage
length beyond the critical section of bending using bends if necessary at the outer edges of the base.