Order No.

MAC0210069C1
E25

Room Air Conditioner


CS-C9CKPG CU-C9CKP6G
CS-C12CKPG CU-C12CKP6G

CONTENTS
Page Page
1 Features 2 11 2-way, 3-way Valve 39
2 Functions 3 12 Servicing Information 46
3 Product Specifications 6 13 Troubleshooting Guide 50
4 Dimensions 10 14 Technical Data 52
5 Refrigeration Cycle Diagram 12 15 Exploded View 54
6 Block Diagram 13 16 Replacement Parts List 55
7 Wiring Diagram 14 17 Exploded View 56
8 Operation Details 15 18 Replacement Parts List 57
9 Operating Instructions 24 19 Electronic Circuit Diagram 58
10 Installation Instructions 29

© 2002 Matsushita Industrial Corp. Sdn. Bhd.


(11969-T). All rights reserved. Unauthorized copying
and distribution is a violation of law.
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

1 Features
• High Efficiency • Quality Improvement
− Gas leakage protection
• Compact Design − Prevent compressor reverse cycle
− OLP to protect compressor
• Comfort Environment − Noise prevention during soft dry operation
− Air filter with function to reduce dust and smoke − Blue Coated Condenser
− Wider range of horizontal discharge air − High resistance to corrosion.

• Auto Restart • Operation Improvement


− Random auto restart after power failure for safety restart − Quiet mode to provide extra quiet operation
operation − Powerful mode to reach the desired room temperature
quickly
• Removable and Washable Front Panel − Economy mode to reduce electrical power consumption

• Remote Control Self-illuminating Button • Long Installation Piping


− CS/CU-C9CK, long piping up to 10 meter
• Air Purifying Filter − CS/CU-C12CK, long piping up to 15 meter
− Trap dust, tobacco smoke and tiny particles
− Prevent the growth of bacteria and viruses trapped • 24-hour Timer Setting

• Solar Refreshing Deodorizing Filter


− Remove unpleasant odour from the air

2
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

2 Functions

Remote Control

Self illuminating
button

OFF / ON I TEMP.
Operation OFF / ON Room Temperature Setting
Cooling, Soft Dry, Air Circulation Operation.
• Temperature Setting (16°C to 30°C)
MODE
Operation Mode Selection
Automatic Operation
• AUTO Automatic Operation Mode • Operation with 2°C higher than
• COOL Cooling Operation Mode standard temperature.
• DRY Soft Dry Operation Mode • Operation with standard temperature.
• FAN Air Circulation Mode • Operation with 2°C lower than
standard temperature.
FAN SPEED
Indoor Fan Speed Selection ON-TIMER
OFF-TIMER
Timer Operation Selection
• FAN Low Fan Speed
• FAN Medium Fan Speed • 24-hour, OFF / ON Real Timer Setting.
• FAN High Fan Speed
• AUTO Automatic Fan Speed
FAN TIME
Time / Timer Setting
• Hours and minutes setting.
AIR SWING
Vertical Airflow Direction Control SET
CANCEL
• AUTO Automatic Vertical Airflow Timer Operation Set / Cancel
Direction Control
• ON Timer and OFF Timer setting and
• MANUAL Vertical Airflow Direction
cancellation.
Manual Control (5 stages of
adjustment)
CLOCK
Clock Setting
POWERFUL
Powerful Mode Operation OFF/ON • Current time setting.

QUIET
Quiet Mode Operation OFF/ON ECONOMY
Economy Operation OFF / ON

3
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Indoor Unit

AUTO
OFF / ON
Automatic Operation Button Random Auto Restart Control
• Press for < 5s to operate Automatic • Operation is restarted randomly after power
operation mode. failure at previous setting mode.
(Used when the remote control cannot be used.)
• Press continuously for 5s or < 10s to Anti-Freezing Control
operate Test Run/Pump down. “Beep”
sound will be heard at the 5th second. • Anti-Freezing control for indoor heat
(Used when test running or servicing.) exchanger. (Cooling and Soft Dry)
• Press continuously for 10s and above to
omit or resume the remote control signal
receiving sound. “Beep, beep” sound will Economy Operation
be heard at the 10th second. • To reduce electrical power consumption.

Operation Indication Lamps (LED) Indoor Fan Speed Control


• POWER (Green) ......... Lights up in operation, • High, Medium and Low.
blinks in Automatic • Automatic Fan Speed Mode
Operation Mode judging. – Cooling : Fan rotates at Hi, Me and SLo
• QUIET (Orange) ......... Lights up in Quiet Mode speed. Deodorizing control is
Operation. available.
• TIMER (Orange) ......... Lights up in Timer – Soft Dry : Fan rotates at Lo- speed.
Setting. Deodorizing control is
available.
• POWERFUL (Orange) ... Lights up in Powerful
Mode Operation.
• ECONOMY (Green) ...... Lights up in Economy Airflow Direction Control
Mode Operation. • Automatic air swing and manual adjusted
by remote control for vertical airflow.
• Manually adjusted by hand for horizontal
Operation Mode airflow.
• Cooling, Soft Dry, Air Circulation and
Automatic Mode. Starting Current Control
• Fan motor is delayed for 1.6 seconds when
Powerful Operation compressor starts simultaneously.
• Reaches the desired room temperature
quickly. Time Delay Safety Control
• Restarting is inhibited for appro. 3
Quiet Operation minutes.

• To provide extra quiet operation.


7 Minutes Time Save Control
• Cooling Operation only.

4
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Outdoor Unit

Compressor Reverse Rotation


Protection Control
• To protect compressor from reverse
rotation when there is a instantaneous
power failure.

Overload Protector
• OLP to protect the compressor. Overload
Protector will trip when
– High temperature or high current flows
to compressor.

60 Secs. Forced Operation Control


• Once the compressor is activated, it
does not stop within the first 60 secs.
However, it stops immediately with
remote control stop signal.

Outdoor Fan Operation Control


• Temperature Fuse.

5
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

3 Product Specifications
Unit CS-C9CK CU-C9CK

Power Source Phase, Voltage, Cycle Single, 115, 60 Hz

Cooling Capacity kW (BTU/h) (1) 2.58 (8,800)


(2) 2.60 (8,800)
Moisture Removal l/h (Pint/h) 0.8 (1.7)

Airflow Method OUTLET SIDE VIEW TOP VIEW

INTAKE

Air Volume Indoor Air (Lo) m3/min (cfm) 6.1 (220) —


Indoor Air (Me) m3/min (cfm) 7.2 (250) —
Indoor Air (Hi) m3/min (cfm) 8.9 (310) 33.8 (1,190)
Indoor Air (SHi) m3/min (cfm) 9.8 (340) —
Noise Level dB (A) High 36, Low 26 High 49
Power level dB — —
Electrical Data Input Power W (1) 790
(2) 800
Running Current A (1) 7.2
(2) 7.3
EER W/W (BTU/hW) (1) 3.265 (11.10)
(2) 3.25 (11.00)
Starting Current A 42.0
Piping Connection Port inch G ; Half Union 3/8” G ; 3-way valve 3/8”
(Flare piping) inch L ; Half Union 1/4” L ; 2-way valve 1/4”
Pipe Size inch G ; (gas side) 3/8” G ; (gas side) 3/8”
(Flare piping) inch L ; (liquid side) 1/4” L ; (liquid side) 1/4”
Drain Inner diameter mm 12 —
Hose Length mm 650 —
Power Cord Length m — —
Number of core-wire — —
Dimensions Height inch (mm) 10 - 13/16 (275) 21 - 1/4 (540)
Width inch (mm) 31 - 15/32 (799) 30 - 23/32 (780)
Depth inch (mm) 8 - 9/32 (210) 11 - 3/8 (289)
Net Weight lb (kg) 20 (9.0) 64 (29.0)
Compressor Type — Rotary (1 cylinder)
rolling piston type
Motor Type — Induction (2-poles)
Rated Output W — 600
Air Circulation Type Cross-flow Fan Propeller Fan
Material AS + Glass Fiber 20% PP Resin
Motor Type Induction (4-poles) Induction (6-poles)
Input W 55.1 78.0
Rated Output W 15 30
Fan Speed Low rpm 780 —
Medium rpm 920 —
High rpm 1,140 845
SuperHigh rpm 1,250 —
Heat Exchanger Description Evaporator Condenser
Tube material Copper Copper
Fin material Aluminium (Pre Coat) Aluminium (Blue Coat)
Fin Type Slit Fin Louver Fin
Row / Stage (Plate fin configuration, forced draft)
2 × 15 1 × 20
FPI 19 16
Size (W × H × L) mm 610 × 315 × 25.4 841 × 508 × 22
Refrigerant Control Device — Capillary Tube

6
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Unit CS-C9CK CU-C9CK


Refrigeration Oil (cm3) SUNISO 4GDID or ATMOS
— M60 (290)
Refrigerant (R-22) g (oz) — 790 (27.9)
Thermostat Electronic Control —
Protection Device — Overload Protector
Capillary Tube Length mm — 870
Flow Rate l/min — 12.0
Inner Diameter mm — 1.6
Air Filter Material P.P. —
Style Honeycomb
Capacity Control Capillary Tube
Compressor Capacitor µF, VAC — 35 µF, 370VAC
Fan Motor Capacitor µF, VAC 5.0 µF, 230VAC 8.0 µF, 230VAC

Note:
• Specifications are subject to change without notice for further improvement.
• (1) — CS-C9CKPG-4 / CU-C9CKP6G-4 (USA).
• (2) — CS-C9CKPG-5 / CU-C9CKP6G-5 (Canada).

7
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Unit CS-C12CK CU-C12CK

Power Source Phase, Voltage, Cycle Single, 115, 60 Hz

Cooling Capacity kW (BTU/h) 3.60 (12,300)

Moisture Removal l/h (Pint/h) 1.4 (3.0)

Airflow Method OUTLET SIDE VIEW TOP VIEW

INTAKE

Air Volume Indoor Air (Lo) m3/min (cfm) 6.9 (240) —


Indoor Air (Me) m3/min (cfm) 8.3 (290) —
Indoor Air (Hi) m3/min (cfm) 9.7 (340) 31.1 (1,100)
Indoor Air (SHi) m3/min (cfm) 10.0 (350) —
Noise Level dB (A) High 39, Low 29 High 49
Power level dB — —
Electrical Data Input Power kW (1) 1.16
(2) 1.15
Running Current A (1) 10.3
(2) 10.2
EER W/W (BTU/hW) (1) 3.100 (10.60)
(2) 3.10 (10.65)
Starting Current A 57.0
Piping Connection Port inch G ; Half Union 1/2” G ; 3-way valve 1/2”
(Flare piping) inch L ; Half Union 1/4” L ; 2-way valve 1/4”
Pipe Size inch G ; (gas side) 1/2” G ; (gas side) 1/2”
(Flare piping) inch L ; (liquid side) 1/4” L ; (liquid side) 1/4”
Drain Inner diameter mm 12 —
Hose Length mm 650 —
Power Cord Length m — —
Number of core-wire — —
Dimensions Height inch (mm) 10 - 13/16 (275) 21 - 1/4 (540)
Width inch (mm) 31 - 15/32 (799) 30 - 23/32 (780)
Depth inch (mm) 8 - 9/32 (210) 11 - 3/8 (289)
Net Weight lb (kg) 20 (9.0) 73 (33.0)
Compressor Type — Rotary (1 cylinder) rolling
piston type
Motor Type — Induction (2-poles)
Rated Output kW — 0.85
Air Circulation Type Cross-flow Fan Propeller Fan
Material AS + Glass Fiber 20% PP Resin
Motor Type Induction (4-poles) Induction (6-poles)
Input W 55.1 78.0
Rated Output W 15 30

Fan Speed Low rpm 900 —


Medium rpm 1,080 —
High rpm 1,260 850
SuperHigh rpm 1,300 —
Heat Exchanger Description Evaporator Condenser
Tube material Copper Copper
Fin material Aluminium (Pre Coat) Aluminium (Blue Coat)
Fin Type Slit Fin Louver Fin
Row / Stage (Plate fin configuration, forced draft)
2 × 15 2 × 24
FPI 21 16
Size (W × H × L) mm 610 × 315 × 25.4 744.2 × 504 × 25.4
723.5
Refrigerant Control Device — Capillary Tube
Refrigeration Oil (cm3) — SUNISO 4GDID or ATMOS
M60 (350)

8
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Unit CS-C12CK CU-C12CK


Refrigerant (R-22) g (oz) — 970 (34.2)
Thermostat Electronic Control —
Protection Device — Overload Protector
Capillary Tube Length mm — 583
Flow Rate l/min — 16
Inner Diameter mm — 1.7
Air Filter Material P.P. —
Style Honeycomb
Capacity Control Capillary Tube
Compressor Capacitor µF, VAC — 50 µF, 370VAC
Fan Motor Capacitor µF, VAC 5.0 µF, 230VAC 8.0 µF, 230VAC

Note:
• Specifications are subject to change without notice for further improvement.
• (1) — CS-C12CKPG-4 / CU-C12CKP6G-4 (USA).
• (2) — CS-C12CKPG-5 / CU-C12CKP6G-5 (Canada).

9
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

4 Dimensions

10
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

11
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

5 Refrigeration Cycle Diagram

12
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

6 Block Diagram

13
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

7 Wiring Diagram

14
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

8 Operation Details
8.1. Cooling Mode Operation
Cooling in operation according to Remote Control setting.

Time Delay Safety Control (3 minutes)

• When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.

7 minutes Time Save Control

• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.

Starting Current Control

• When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.

Anti-Freezing Control

• If the temperature of the indoor heat exchanger falls


continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
• Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.

Compressor Reverse Rotation Protection Control

• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)

▲ T = Intake air temperature - Indoor heat exchanger temperature


This is to protect reverse rotation of the compressor when there is a instantaneous power failure.

15
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Automatic Fan Speed Mode

When Automatic Fan Speed is selected at Remote Control during cooling operation.
• Fan speed rotates in the range of Hi to Me.
• Deodorizing Control.

Cooling Operation Time Diagram

16
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Quiet Operation Control

(For Cooling Mode or cooling region of Soft Dry Mode)


• Purpose of this operation is to provide quite cooling operation compare to normal operation.
• When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased
2 dB (Lo), decreased 3 dB (Hi, Me), against the present sound level operation.
• Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
• Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1h 30 min (1h QLo, 30 min QLo + 50).
After that, it goes back to Lo cool (However Quiet LED remains on).
• Manual Airflow Direction:-
− RPM control during Lo cool

− RPM control during Hi & Me cool

• Auto Airflow Direction:-

• Quiet Mode Operation will stop if:-


− Quiet mode button is pressed again.
− Stopped by ON/OFF switch.
− Timer OFF activates.
− Powerful mode button is pressed.
− When change mode to Air Circulation mode.

17
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

8.2. Soft Dry Mode Operation

• The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
• During Soft Dry operation, the Indoor Fan will operate at Lo- speed.
• The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned
off, it stops for 6 minutes.

Time Delay Safety Control

• Once the compressor stops, it will not start for 3 minutes during Cooling operation.

Starting Current Control

• Same as Starting Current Control for Cooling Mode operation.

Anti-Freezing Control

• Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)

Compressor Reverse Rotation Protection Control

• Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)

Automatic Fan Speed Mode

When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
• Fan speed off and on at Lo- speed.
• Deodorizing Control.

18
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Soft Dry Operation Time Diagram

Quiet Operation Control

(For Dry region of Soft Dry Mode)

19
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

8.3. Air Circulation Mode Operation


• When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low
airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
Air Circulation Mode Operation Time Diagram

8.4. Automatic Mode Operation


Standard for Determining Operation Mode

• Indoor fan operates at SLo fan speed for 20 seconds.


• After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
• After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
• Room temperature adjustment.
The following are added to the setting temperature specified as above.

• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at indoor
electronic controller.

20
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

8.5. Powerful Mode Operation


• Purpose of this operation is to obtain the setting temperature quickly.
• When the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting
temperature (Lower temperature: 16°C).
• This operation automatically will be running under SHi Fan Speed (Cooling), Lo- Fan Speed (Soft Dry).
• Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
• Powerful Mode will operate for 15 minutes only, after that it will shift back to previous operation mode.
• Powerful Mode will stop if:-
- Powerful mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Quiet mode button is pressed.
- Operation mode button is changed.

8.6. Economy Mode Operation


• Purpose of this operation is to save or reduced electrical power consumption of the room air conditioner.
• When the Economy Mode is set, the set temperature will be automatically increased 0.5°C against the preset setting
temperature (Higher temperature: 30°C).
• This operation automatically will be running under Lo- Fan Speed.
• Vertical Airflow Direction:-
In “Manual” or “Auto” setting, the vane will automatically change to Auto Air Swing.
• Economy Mode will stop if:-
- Economy Mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Powerful mode button is pressed.
- Auto or Manual air swing button is pressed.
- Fan Speed control button is pressed.
- Quiet Mode button is pressed ON.
- Operation Mode is changed.

8.7. Random Auto Restart Control


• If there is a power failure during air conditioner operation, operation will be automatically restarted after 3 to 4 minutes when the
power is resumed.
It will start with previous operation mode and airflow direction.
• Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
• Auto Restart Control is not available when Timer is set.
• This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)

21
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

8.8. Indoor Fan Speed Control


• Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
• Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote
control.

22
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

8.9. Vertical Airflow Direction Control


Vertical Airflow Direction Auto-Control

• When set a Airflow Direction Auto-Control with remote


control, the louver swings up and down as shown in the
diagram.
• The louver does not swing when the Indoor Fan Motor
stops during operation at the upper limit.
• When stopped with remote control, the discharge vent is
reset, and stopped at the closing position.

1. There is no swinging while indoor fan motor is stopped during Cooling, Ion and Soft Dry operation.
2. In Air Circulation operation, when the intake air temperature reaches set temperature, the airflow direction is changed from upper limit to
lower limit. When the intake air temperature falls to 2°C lower than set temperature, the airflow direction is changed from lower limit to
upper limit.

Vertical Airflow Direction manual Control

• When the manual Airflow Direction Selection Button is


pressed, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in
the diagram.
The louver can be adjusted by pressing the button to the
desired louver position.
• When the remote control is used to stop the operation, the
discharge vent is reset, and stopped at the closing position.

8.10. Delay ON Timer Control


• When the Delayed ON Timer is set by using the remote control, the unit will start operate slightly before the set time, so that
the room will reach nearly to the set temperature by the desired time.
• For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time.
• For Automatic mode, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.

8.11. Remote Control Signal Receiving Sound


• Long beep sound will be heard when:-
− Stopping the Air Conditioner using ON/OFF switch.
− Stopping the Quiet Mode.
− Stopping the Powerful Mode.
− Stopping the Economy Mode.
• Short beep sound will be heard for others.
• To switch off the beep sound:-
Press the “Automatic Operation Button” continuously for 10 seconds or more (“beep” “beep” will be heard at the 10th second).
Repeat the above if you want to switch ON the beep sound.

However, if the “Automatic Operation Button” has been pressed the Automatic operation will be activated.
If you do not require this operation, you may change it by using the remote control.

23
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

9 Operating Instructions

SAFETY PRECAUTIONS
■ Installation Precautions ■ Operation Precautions
Before operating, please read the following
“Safety Precautions” carefully.
! Warning ! Warning
● To prevent personal injury, injury to others and This sign warns of death or serious injury.
property damage, the following instructions must be ● Do not install, remove and reinstall the unit by
followed. yourself. ● Do not operate with wet hands.
Improper installation will cause leakage, electric ● Do not insert finger or other objects into the
● Incorrect operation due to failure to follow instructions shock or fire. Please engage an authorized dealer indoor or outdoor units.
will cause harm or damage, the seriousness of which or specialist for the installation work. ● Do not expose directly to cold air for a long
is classified as follow: period of time.

! Warning ! Caution
● Use specified power cord.

This sign warns of death or serious injury.

● This room air conditioner must be


earthed.
! Caution
Improper grounding could cause
electric shock.
OFF
● If abnormal condition (burnt smell, etc.)
occurs, switch off the power supply.
This sign warns of damage to property.
● Ensure that the drainage piping is
connected properly.
● The instructions to be followed are classified by the
following symbols:
Otherwise, water will leak out. ! Caution
● Do not install the unit in a This sign warns of injury.
potentially explosive atmosphere.
Gas leak near the unit could cause ● Do not wash the unit with water.
fire. ● Do not use for other purposes such as
preservation.
● Do not use any combustible equipment at
This symbol (with a white background) denotes an airflow direction.
action that is PROHIBITED. ● Do not sit or place anything on the outdoor
unit.

● Switch off the power supply before cleaning.


● Ventilate the room regularly.
● Pay attention as to whether the installation
rack is damaged after a long period of usage.
OFF

These symbols (with a black background) denote ● Switch off the power supply if the unit is not
OFF

actions that are COMPULSORY. used for a long period.

NAME OF EACH PART


■ Indoor Unit ● Indoor Unit ■ Accessories
(when the front panel is opened)
1 2
● Remote Control
1 3
AU
TO
T
HE
AT
ON CO
OL
OF AU
F F TTO DRY
FAAN
N
AU
QU TE FA
AN TTO
IE MP N
T

MO
DE
AIR OF
EC F/O

2
Ste SW ON N
p ING OM
1 Y
POWER QUIET
QUIET TIMER ON SL
ECONOMY POWERFUL EE
OFF 2 P
FAN
SP
EE
CHE 3 D
CK TIM SE
RES ER T
ET CA
CLO NC
CK EL
BAT +
TER
Y

6 5 4 3

1 Front Panel 1 Front Panel ● Remote Control Holder

2 Air Intake Vent 2 Air Filters

3 Air Outlet Vent 3 Air Purifying Filter

4 Vertical Airflow Direction Louver


■ Outdoor Unit
5 Horizontal Airflow Direction Louver ● Two RO3 (AAA) dry-cell batteries or equivalent
(manually adjusted) 1
2
6 Indicator Panel

3
1 2 3 456
● Air Purifying Filter
6
ECONOMY POWERFUL POWER QUIET TIMER
4
5

1 Auto Operation Button


(when the front panel is opened)

2 Economy Mode Indicator – GREEN 1 Air Intake Vents


2 Ground Terminal
3 Powerful Mode Indicator – ORANGE (Inside cover)
(Air Purifying Filter)

4 Power Indicator – GREEN 3 Piping

5 Quiet Mode Indicator – ORANGE 4 Conduit


5 Drain Hose
6 Timer Mode Indicator – ORANGE
6 Air Outlet Vents

(Solar Refreshing Deodorizing Filter)

24
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

● How to Insert the Batteries


NAME OF EACH PART
AU
TO
HE
AT

■ Remote Control 1 Signal Transmitter


CO

2 OF
AU
TO
OL
AU
TO DRY
FA
N
PO A
WER FA UTO

2 Operation Display
N
FUL

1 MO
DE
AU AIR EC
TO ON
3 Quiet Mode Operation Button
SW
IN OM
1 MA G
Y
ON NU SL
AL E
OF 2
F FAN
SP
EE
4 Room Temperature Setting Button
CH 3 D
EC
K
TIM SE
ER T
2
RE
SE
T
CL
CA
NC
AUTO HEA
AUT HEAT COOL DR
DRY FAN
AN (Illuminating button) OCK
EL

AUTO 1.5
1.5 V
F 5 Operation Mode Selection Button V

ON
OFF AUTO
FAN 6 Economy Mode Operation Button 1
TEMP
7 Auto Airflow Direction Button
3 QUIET OFF/ON

4
! 8 ON-Timer Button 1 Slide down the remote control cover completely
to remove it.
5 MODE ECONOMY POWERFUL
# 9 OFF-Timer Button
6 2 Insert the batteries
$
AIR SWING
AUTO MANUAL FAN SPEED 0 Reset Point – Be sure the direction is correct
7 $ (Press with fine-tipped object to clear the memory)
1 2 3 – 12:00 on display - flashing
8 %
ON SET • Set the current time (CLOCK) immediately to
9 ^ ! OFF/ON Button prevent battery exhaustion.
OFF CANCEL
(Illuminating button)
TIMER &
0 *
3 Re-install the remote control cover by inserting it
CHECK RESET CLOCK @ Powerful Mode Operation Button in the side groves and pushing inward.
( # Fan Speed Selection Button ● About the batteries
• Can be used for approximately one year.
$ Manual Airflow Direction Selection Button
● Observe the following when replacing the
● Remote Control Signal % Timer Set Button batteries
• Make sure it is not obstructed. • Replace with new batteries of the same type.
• Maximum distance : 10 m (32.8 ft.). ^ Timer Cancellation Button • Do not use rechargeable batteries (Ni-Cd).
• Signal received sound : • Remove the batteries if the unit is not going to be
One short beep or one long beep. & Time-Setting Button used for a long period.
● Notes for Remote Control * Clock Button
• Do not throw or drop.
• Do not get it wet. ( Remote Control Cover
• Certain types of fluorescent lamps may affect
signal reception. Consult your dealer.

PREPARATION BEFORE OPERATION HOW TO OPERATE ■ Setting Temperature


• Press 3 to increase or decrease the temperature.
• The temperature can be set between 60°F ~ 86°F.
■ Indoor Unit • Recommended temperature:
AU
TO
HE
AT Cooling Model Heat Pump Model
1 2 OF
F
ON CO
AU L D
O
TO RY
FA
N
A COOL –> 75°F ~ 78°F COOL –> 75°F ~ 78°F
5 QU
IE
T
TE
MP
FA UTO
N

3 MO DRY –> 2°F ~ 4°F DRY –> 2°F ~ 4°F


2 5 AU AIR
DE
EC OF lower than the lower than the
1 room temperature
TO ON F/O

4 3
SW N
IN OM
ON
1 MA G
NU
Y
PO room temperature
6
WER
OF
F
2
AL
FAN
FUL HEAT –> 68°F ~ 75°F
SP
4
EE
CH 3 D
EC
K
TIM SE
T
1
RE ER

Open the front panel • During AUTO Operation, press 3 to select:-


SE
T
CL
CA
OCK NC
EL
AUTO HEAT COOL DRY FAN
AUTO
2 Remove the air filters • Operation with 4°F higher than the standard
■ To start the operation temperature.
3 Fit the air purifying filters in place • Press 1.
AUTO
FAN • POWER indicator (green) on the indoor unit will light • Operation with the standard temperature.
4 Insert the air filters up.
• To stop, press once more. • Operation with 4°F lower than the standard
5 Close the front panel
temperature.
■ Setting Mode
■ Remote Control – To set the current time • Press 2 to select:- ● Standard Temperature

AIR SWING
Cooling Model Cooling Model
AUTO MANUAL FAN SPEED
AUTO – Automatic Operation Indoor Standard
1 2 3 Operation
temperature temperature
ON SET COOL – Cooling Operation
DRY – Soft Dry Operation Cooling 77°F
OFF CANCEL
FAN – Air Circulation Operation
TIMER 2 73°F Soft Dry 72°F

CHECK RESET CLOCK


1
• Once the Automatic Operation is selected, the indoor
Heat Pump Model temperature sensor operates automatically to select
the desired operation mode with Cooling or Soft Dry.
AUTO – Automatic Operation • After the operation mode has been selected, the
1 Press 1. HEAT – Heating Operation mode does not change.
2 Then press 2 to increase or decrease the time. COOL – Cooling Operation
DRY – Soft Dry Operation Heat Pump Model
3 Press 1 again. Indoor Standard
temperature Operation temperature
Set time on display will light up.
Cooling 77°F
73°F Soft Dry 72°F
68°F Heating 70°F

• At the beginning of the automatic operation, Heating,


Cooling or Soft Dry is automatically selected according
to the indoor temperature.
• The operation mode changes every hour, when
necessary.

25
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

■ Setting the Fan Speed ■ Setting the Horizontal Airflow Direction ● Operation Details
• Press 4 to select:-
FAN – Low Fan Speed COOL – Cooling Operation
FAN – Medium Fan Speed • To set the room temperature at your preference
FAN – High Fan Speed cooling comfort.
AUTO
FAN – Automatic Fan Speed POWER QUIET TIMER
AUTO – Automatic Operation
The speed of the indoor fan is adjusted
POWERFUL

• Sense indoor temperature to select the optimum


ECONOMY

automatically according to the operation. mode.


The indoor fan stops occasionally during • Adjust it manually • Temperature is not displayed on the remote control
cooling operation. during AUTO operation.

■ Setting the Vertical Airflow Direction ● Use this air conditioner under the following DRY – Soft Dry Operation
• Press 5 or 6 to select:- conditions: • A very gentle Cooling Operation, prior to
dehumidification. It does not lower the room
Cooling Model Cooling Model temperature.
• During Soft Dry operation, the indoor fan operates at
COOL / DRY Operation FAN Operation (Unit in °F) Low fan speed.
AUTO AUTO Indoor Outdoor
DBT: Dry Bulb Temp
HEAT – Heating Operation
WBT: Wet Bulb Temp DBT WBT DBT WBT (for Heat Pump Model only)
Maximum Temperature 89.6 73.4 109.4 78.8 • Heat is obtained from outdoor air to warm up the
36° 61° room. When the outdoor ambient air temperature
Minimum Temperature 60.8 51.8 60.8 51.8 falls, the heating capacity of the unit might be
reduced.
Swing up/down Move up/down
Automatically • Defrosting Operation
Automatically
Depending on the outdoor temperature, the operation
MANUAL MANUAL Heat Pump Model
occasionally stops to melt the frost on the outdoor
Five stages of adjustment Five stages of adjustment
(Unit in °F) unit.
can be made between can be made between
14 ~ 36 angle. 0 ~ 61 angle. Indoor Outdoor
DBT: Dry Bulb Temp FAN – Air Circulation Operation
Heat Pump Model WBT: Wet Bulb Temp DBT WBT DBT WBT (for Cooling Model only)
• When the room temperature reaches the set
Maximum Temperature-Cooling 89.6 73.4 109.4 78.8 temperature, operation commences at Low airflow
COOL / DRY Operation HEAT Operation
(Maximum Temperature-Heating) (86) (–) (75.2) (64.4) volume. It stops when the room temperature drops to
AUTO AUTO
4°F below the set temperature.
– When the discharge air Minimum Temperature-Cooling 60.8 51.8 60.8 51.8
(Minimum Temperature-Heating) (60.8) (–) (23) (21.2) (It is useful when using a heater).
temperature is low such
• Hi fan speed will not operate when using the air
as at the start of heating
operation, the air blows
circulation Fan mode.
36° ● Notes
in a horizontal direction.
As the temperature • If the unit is not going to be used for an extended
rises, the hot air blows period of time, turn off the main power supply. If it is
Swing up/down in a downward direction. left at the ON position, approximately 2.5 W of
Automatically – To stop this operation, electricity will be used even if the indoor unit has been
press MANUAL. turned off with the remote control.
MANUAL MANUAL • If operation is stopped, then restart immediately, the
Five stages of adjustment Five stages of adjustment unit will resume operation only after 3 minutes.
can be made between can be made between
14 ~ 36 angle. 0 ~ 61 angle.

AUTOHEAT COOL DRY FAN


AUTO

AUTO
FAN

8 QUIET OFF/ON CONVENIENCE OPERATION


■ Powerful Mode Operation ■ Quiet Mode Operation
To obtain the set temperature quickly. To provide quiet operation.
MODE ECONOMY POWERFUL • Press 6. • Press 8.
7 6
AIR SWING * Powerful mode indicator (orange) on the indoor * Quiet mode indicator on the indoor unit will light up.
AUTO MANUAL FAN SPEED unit will light up. • To cancel this operation, press once more.
1 2 3 * Powerful mode will operate for 15 minutes only.
1 3 • To cancel this operation, press once more.
ON SET ● Operation Details
5 4 • Air flow sound will reduce during operation.
OFF CANCEL ■ Economy Mode Operation
TIMER 2 To save electrical power consumption.
CHECK RESET CLOCK Please use this mode when the room has reached
SETTING THE TIMER your desired temperature.
Ensure that the current time is correct before setting • Press 7.
the timer. The timer cannot be set if the time display * Economy mode indicator (green) on the indoor unit
is flashing. will light up.
• Press once more to cancel this operation.
■ ON-TIMER Operation
To start the air conditioner operation automatically. ● Economy/Powerful Mode Operation Details
• Press 1 to set the operation. • Economy and Powerful operation cannot be
• Press 2 to increase or decrease the time.
selected simultaneously.
• Then press 3.
• To cancel this operation, press 4. • The changes of the temperature and airflow volume
are automatic.
■ OFF-TIMER Operation • The remote control display remains unchanged.
To stop the air conditioner operation automatically. • If operation mode button is pressed, economy or
• Press 5 to set the operation. powerful operation will be cancelled.
• Press 2 to increase or decrease the time. • During FAN – Air circulation operation, the powerful
• Then press 3. and economy operation are not available.
• To cancel this operation, press 4. (for Cooling Model only)

● Timer Mode Operation Details


• When the ON-Timer is set, operation will start Economy Mode Temperature Airflow
before the actual set time. This is to enable the Operation volume
room temperature reaches the set temperature at
the set time. 1°F higher
COOL / DRY than set temp. Super Low

Cooling Model Heat Pump Model HEAT 1°F lower


(for Heat Pump than set temp. Automatic
model only)
COOL,DRY, –>15 minutes COOL,DRY, –>15 minutes
AUTO in advance in advance
HEAT, AUTO –>30 minutes
Powerful Mode Temperature Airflow
in advance
Operation volume
• Once the ON/OFF Timer is set, operation will
start/stop at the set time everyday. 5°F lower
COOL / DRY than set temp. Super High
• The current time is not displayed when the timers
are set. HEAT 5°F higher
• When both timers are used together, the TIMER (for Heat Pump Automatic
than set temp.
mode indicator on the indoor unit remains lit even model only)
when the operation is stopped by the OFF-TIMER.

26
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

CARE AND MAINTENANCE


■ Cleaning the Indoor Unit and Remote ■ Air Purifying Filters ■ Pre-season Inspection
Control ● Is the discharged air cold/warm?
• Wipe gently with a soft, dry cloth. Operation is normal if 15 minutes after the start of
• Do not use water hotter than 104˚F or polishing fluid 1 operation, the difference between the air intake and
to clean the unit. Raise the
front panel outlet vents temperature is:-
■ Cleaning the Air Filter
(Recommendation:- If the unit is operated in a dusty Cooling Model
environment, clean the filters every two weeks. Solar Refreshing
Continuous use of this dirty filters will reduce cooling Deodorizing Filter COOL –> 14°F or above
or heating efficiency)
1 Remove dirt using a vacuum cleaner. Air Purifying Filter Heat Pump Model
2 Wash back of the air filter with water.
COOL –> 14°F or above
3 If badly soiled, wash it with soap or a mild household
2 Remove the air filters HEAT –> 25°F or above
detergent.
● Are the air intake or outlet vents of the indoor or
4 Let it dry and reinstall it. outdoor units obstructed?
Be sure the “FRONT” mark is facing you.
* Damaged air filter. ● Solar Refreshing Deodorizing Filter ● Are the remote control batteries weak?
• Used to remove unpleasant odor and deodorize If the remote control display appears weak, replace
Consult the nearest authorized dealer. the batteries.
Part No.: CWD001098. the air in the room.
• Do not use benzene, thinner, scouring powder or • Reusable. ■ When the Air Conditioner is Not Used
clothes soaked in caustic chemical to clean the unit. • Vacuum, place under direct sunlight for 6 hours and for an Extended Period of Time
fit it back in place.
■ Cleaning the Front Panel (Recommended: every 6 months)
1 To dry the internal parts of the indoor unit, operate
(Must be removed before washing) the unit for 2 - 3 hours using:-
• Recommended to change this filter every 3 years.
1 Raise the front panel higher than the horizontal and
pull to remove it. Cooling Model
● Air Purifying Filter
2 Gently wash with water and a sponge. • This new filter helps trap small airborne particles FAN operation
• Do not press the front panel too hard when washing. such as dust, pollen and tobacco smoke.
• When use kitchen cleaning fluid (neutral detergent), • Recommended : change this filter every 3 months.
rinse throughly. Heat Pump Model
• Do not dry the front panel under direct sunlight. • Do not reuse damaged filters. COOL operation with 86°F
3 To affix the front panel, raise the front panel Consult the nearest authorized dealer to purchase a set temperature
horizontally, match the protruding portion on the new filter.
indoor unit to the fulcrum and push into place. Air Purifying Filter No.: CZ-SF51P
2 Stop the operation by remote control and switch off
the circuit breaker.
Solar Refreshing Deodorizing Filter No.: CZ-SFD70P Note : If the unit is not switched off by the remote
control, it will start operating when the circuit
• If you operate the air conditioner with dirty filters:- breaker is switched to ON. (The unit is equipped
– Air is not purified with Auto Restart Control.)
– Cooling or heating capacity decreases 3 Remove the remote control batteries.
– Foul odor is emitted ■ Recommended Inspection
Fulcrum • After used over several seasons, the unit will
become dirty and thus decreases the unit’s
performance. Depending on the operation
conditions, a dirty unit may produce odor and dust
may pollute dehumidification system. Therefore, a
seasonal inspection is recommended in addition to
Protruding portion on indoor unit regular cleaning. (Consult an authorized dealer.)

HELPFUL INFORMATION ENERGY SAVING AND OPERATION


HINTS
■ Auto Operation Button
■ Auto Restart Control
• If power is resumed after a power failure, the ■ Setting the Temperature
ECONOMY POWERFUL POWER QUIET TIMER
operation will restart automatically after 3 - 4 • Approximately 10% of electricity can be saved.
minutes. • Set the temperature higher or lower than the
• Operation will be restarted automatically under the desired temperature.
• Raise the front panel and press.
previous operation mode and airflow direction when
power is resumed as the operation is not stopped Cooling Model
● Automatic Operation by the remote control.
• If the remote control fails to function or has been Cooling Operation : 2°F higher
misplaced, press the Auto Operation button to start ■ Timer Setting
the Automatic operation. • When power failure occurs, the timer setting will be
Heat Pump Model
cancelled. Once power is resumed, reset the timer.
• The Automatic operation will be activated
Cooling Operation : 2°F higher
immediately once the Auto operation button is
■ Thunder and Lightning Heating Operation : 4°F lower
pressed. However, temperature cannot be adjusted • This air conditioner is equipped with a built-in surge
when in this mode. protective device. However, in order to further
• The power indicator on the indoor unit will blink until protect your air conditioner from being damaged by ■ Air Filters
the operation mode is selected automatically. abnormally strong lightning activity, you may switch • Clean the air filters every 2 weeks.
• To cancel this operation, press once more. off the circuit breaker. • Dirty filters may reduces cooling or heating
efficiency.
● Remote Control Signal Receiving Sound
• To switch off the beep (Signal Receiving Sound), ■ Keep All Doors and Windows Closed
• Otherwise, cooling or heating performance will be
press the Auto Operation button for 10 seconds
reduced and electricity cost is wasted.
continuously or longer.
A “beep”, “beep” sound will be heard at the ■ Outdoor Unit
tenth seconds. • Do not block the air outlet vents. Otherwise, it will
Note : A “beep” sound will be heard at the fifth lower the cooling or heating performance.
seconds;
However please press continuously until you ■ Timer
heard “beep”, “beep” sound. • To prevent wastage of electricity, use Timer when
• Repeat the above steps if you want to switch on the going out.
Signal Receiving Sound.
■ Avoid Direct Sunlight
• Keep curtains or drapes closed to avoid direct
● (This is for Servicing purposes only.) sunlight during cooling operation.
Note: If you press this button continuously for 5 to 10
seconds, Test Run operation will be performed. A
“beep” sound will be heard after five seconds
indicating the Test Run starts to operate.

27
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

TROUBLESHOOTING
■ Normal Operation ■ Call the Dealer Immediately

Is it okay? Solution If the following conditions occur, turn off the circuit
breaker, and then call your authorized Panasonic dealers
• Air conditioner has been restarted, but does not • This is to protect the air conditioner. Wait until the air or servicenter.
operate for 3 minutes. conditioner begins to operate.

• A sound like water flowing can be heard. • This is the sound of refrigerant flowing inside the air • Abnormal noise is heard during operation.
conditioner.
• Water or foreign material gets into the remote
• It seems that fog is coming out from the air • Condensation occurs when the airflow from the air control by mistake.
conditioner. conditioner cools the room.

• The room has a peculiar odor. • This may be a damp smell emitted by the wall, • Water leak from the indoor unit.
carpet, furniture or clothing in the room.
• Switches or buttons do not operate properly.
• During Automatic Vertical Airflow setting, • This is to remove smell emitted by the surroundings.
indoor fan stops occasionally.
• The circuit breaker switches off frequently.
• The outdoor unit emits water or steam. • In COOL/DRY operation, moisture in the air
condenses into water on the cool surface of outdoor • Power supply cord becomes unusually warm.
unit piping that causes dripping.
Service information can be obtained by calling
• (For Heat Pump Model only) • This is to melt the frost which has accumulated on
Operation stops for about 12 minutes during the outdoor unit (defrosting operating). This will take (866)-292-7292, for Hawaii residents call (808)-488-7779.
heating (The power indicator blinks.) no longer than about 12 minutes. Water drips from
the outdoor unit. Wait until this operation ends. (The To expedite the repair of your air conditioner:
power indicator will light up.) • Please have your proof of purchase.
(Frost accumulates on the outdoor unit when the
outdoor temperature is low and humidity is high.) • List all symptoms the unit is exhibiting.

• (For Heat Pump Model only) • This is to prevent undesired cooling effect during
During heating operation, indoor fan may heating operation.
run at on and off conditions.
■ Abnormal Operation
Check the following points before calling for repairs or service. If the malfunction persists, please contact your nearest
servicenter. For assistance, please call: (866)-292-7292, for Hawaii residents call (808)-488-7779.
Symptoms? Please check

• The air conditioner does not operate. • Has the circuit breaker been tripped?
• Is the timer being used correctly?
• Air conditioner produces loud noise during • Is the installation work slanted?
operation. • Is the front grille closed properly?
• The air conditioner does not cool or warm • Has the temperature been set incorrectly?
effectively. • Are the filters dirty?
• Are the intake or outlet vents of the outdoor unit
obstructed?
• Are all windows and doors closed?
• Remote control / display doesn’t work. • Batteries not inserted?
• Batteries correctly inserted (+) and (–)?

PRODUCT SPECIFICATIONS
CS-C9CKPG CS-C12CKPG CS-A9CKPG CS-A12CKPG
Models CU-C9CKP6G CU-C12CKP6G CU-A9CKP6G CU-A12CKP6G ■ REFERENCE
ELECTRICAL Phase 1 1 1 1
RATING Frequency (Hz) 60 60 60 60
Voltage (V) 115 115 115 115

Capacity (Btu/h) 8,800 12,300 8,200 12,000 Model Number:


Current (Amp) 7.2 10.3 7.4 10.6
Input Power (Watts) 790 1,160 810 1,200
--------------------------------------------------------
COOLING EER (Btu/Watt.h) 11.10 10.60 10.12 10.00
SEER 12.4 11.20 10.8 10.6 Dealer’s Address:
Room Air Circulation (cf/min) 310 340 310 340

Capacity (Btu/h) – – 9,200 13,500 --------------------------------------------------------


Current (Amp) – – 6.7 10.5 Dealer’s Tel :
HEATING Input Power (Watts) – – 730 1,190
COP (Btu/Watt.h) – – 12.60 11.34
--------------------------------------------------------
HSPF – – 8.0 7.4
Room Air Circulation (cf/min) – – 350 360 Serial Number :
(Located on the side of unit)
MOISTURE
(pints/h) 1.7 3.0 1.5 2.7
REMOVAL
--------------------------------------------------------
DIMENSIONS Indoor Height cm (inches) 27.5 (10 – 13/16) ➞ ➞ ➞ Date of Purchase :
Width cm (inches) 79.9 (31 – 15/32) ➞ ➞ ➞
Depth cm (inches) 21.0 (8 – 9/32) ➞ ➞ ➞
--------------------------------------------------------
Outdoor Height cm (inches) 54.0 (21 – 1/4) ➞ ➞ ➞ Dealer’s Name:
Width cm (inches) 78.0 (30 – 23/32) ➞ ➞ ➞
Depth cm (inches) 28.9 (11 – 3/8) ➞ ➞ ➞
--------------------------------------------------------
NET Indoor kg (Ib) 9 (20) ➞ ➞ ➞
WEIGHT
Outdoor kg (Ib) 29 (64) 33 (73) 31 (68) 35 (77)

GROSS Indoor kg (Ib) 11 (24) ➞ ➞ ➞


WEIGHT
Outdoor kg (Ib) 33 (73) 37 (82) 35 (77) 39 (86)
Please affix your proof of purchase here for
future reference.
• Specifications are subject to change without notice for further improvement.

© 2002 Matsushita Electrical Co, Ltd. All Right Reserved.

28
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

10 Installation Instructions
Required tools for Installation Works
1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter
2. Level gauge 6. Pipe cutter 10. Measuring tape 14. Torque wrench
18 N.m (1.8 kgf.m)
42 N.m (4.2 kgf.m)
55 N.m (5.5 kgf.m)
3. Electric drill, hole core drill 7. Reamer 11. Thermometer 15. Vacuum pump
(ø70 mm)
4. Hexagonal wrench (4 mm) 8. Knife 12. Megameter 16. Gauge manifold

10.1. Safety Precautions


• Read the following “SAFETY PRECAUTIONS” carefully before installation.
• Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit
for the model to be installed.
• The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seriousness is classified by the following indications.

This indication shows the possibility of causing death or serious injury.

This indication shows the possibility of causing injury or damage to properties only.

The items to be followed are classified by the symbols:

Symbol with background white denotes item that is PROHIBITED from doing.

• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.

1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6. Use the UL listed or CSA approved AWG16 wire (or heavier wire) and connect tightly for indoor/outdoor connection. Connect tightly and
clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at
the connection.
7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.

29
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.

2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.

3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.

1. Selection of the installation location.


Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
2. Power supply connection to the room air conditioner.
Connect the power supply cord of the room air conditioner to the mains.
Power supply point should be in an easily accessible place for power disconnection in case of emergency.
Power supply connection to a circuit breaker for the permanent connection. Use an approved 15A (CU-C9CKP6G) and 20A (CU-
C12CKP6G) fuse or circuit breaker for the permanent connection.
It must be a double pole switch with a minimum 3 mm contact gap.
3. Do not release refrigerant.
Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the
liquid refrigerant, it may cause frostbite.
4. Installation work.
It may need two people to carry out the installation work.
5. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

30
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

Attached accessories

Indoor/Outdoor Unit Installation Diagram

Applicable piping kit


CZ-3F5, 7AEN (CS-C9CKPG)
CZ-4F5, 7, 10AN (CS-C12CKPG)

SELECT THE BEST LOCATION

INDOOR UNIT
• There should not be any heat source or steam near the
unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure there is adequate space (indicated by arrows)
from the wall, ceiling, fence or other obstacles.
• Recommended installation height for indoor unit shall be
at least 7.5 ft (2.3 m).

OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• Keep animals or plants away from the unit as they may
be affected by the hot air discharged.
• Keep the spaces (indicated by arrows) from wall, ceiling,
fence or other obstacles.
• Do not place near any obstacles which may cause a
short circuit of the discharged air. • This illustration is for explanation purposes only.
• If piping length is over the common length, additional The indoor unit will actually face a different way.
refrigerant should be added as shown in the table.

31
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

10.2. INDOOR UNIT


10.2.1. SELECT THE BEST LOCATION 10.2.3. TO DRILL A HOLE IN THE WALL
(Refer to “Select the best location” AND INSTALL A SLEEVE OF
section) PIPING

1. Insert the piping sleeve to the hole.


10.2.2. HOW TO FIX INSTALLATION
2. Fix the bushing to the sleeve.
PLATE
3. Cut the sleeve until it extrudes about 15 mm from the wall.

The mounting wall is strong and solid enough to prevent it from Caution
the vibration. When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.

4. Finish by sealing the sleeve with putty or caulking


compound at the final stage.

The centre of installation plate should be at more than 550 mm


at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit’s left side is 47 mm.
From installation plate right edge to unit’s right is 73 mm.
: For left side piping, piping connection for liquid should be
about 126 mm from this line.
: For left side piping, piping connection for gas should be
about 174 mm from this line.
: For left side piping, piping connecting cable should be
about 984 mm from this line. 10.2.4. INDOOR UNIT INSTALLATION
1. For the right rear piping

1. Mount the installation plate on the wall with 5 screws or


more.
(If mounting the unit on the concrete wall consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.

2. Drill the piping plate hole with ø70 mm hole-core drill.


• Line according to the arrows marked on the lower left
and right side of the installation plate. The meeting point
of the extended line is the centre of the hole. Another
method is by putting measuring tape at position as
shown in the diagram above. The hole centre is
obtained by measuring the distance namely 150 mm
and 125 mm for left and right hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.

32
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

2. For the embedded piping

(This can be used for left rear piping & left bottom piping also.)

33
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

10.2.5. INDOOR UNIT ELECTRICAL WIRING


1. Remove the control board metal cover.

• Secure the wire onto the control board with the holder
2. Unscrew the conduit cover & fix the conduit connector to (clamper).
conduit cover with lock nut, then secure it against chassis.

4. After completed wiring connection, fix back the metal cover


to the original location.

INSTALLATION OF AIR PURIFYING FILTERS

1. Open the front panel.


2. Remove the air filters.
3. Put air purifying filters (left) and solar refreshing deodorizing
filter (right) into place as shown in illustration below.

3. Connecting between indoor unit and outdoor unit should be


UL listed or CSA approved 4 × AWG16 wire.
• Ensure the color of wires of outdoor unit and the
terminal Nos. are the same as the indoor’s respectively.
• Earth lead wire should be longer than the other lead
wires as shown in the figure for the electrical safety in
case the cord slips out from the anchorage.

34
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

HOW TO TAKE OUT FRONT GRILLE 10.3. OUTDOOR UNIT


Please follow the steps below to take out front grille if
10.3.1. SELECT THE BEST LOCATION
necessary such as when servicing.
(Refer to “Select the best location”
1. Set the vertical airflow direction louver to the horizontal
position. section)
2. Slide down the three caps on the front grille as shown in the
illustration below, and then remove the three mounting
screws. 10.3.2. INSTALL THE OUTDOOR UNIT
3. Pull the lower section of the front grille towards you to
remove the front grille. • After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
When reinstalling the front grille, first set the vertical 1. Fix the unit on concrete or rigid frame firmly and horizontally
airflow direction louver to the horizontal position and
then carry out above steps 2 - 3 in the reverse order. by bolt nut. (ø10 mm).
2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly with
bolt or nails.

AUTO SWITCH OPERATION

The below operations will be performed by pressing the


“AUTO” switch. 10.3.3. CONNECTING THE PIPING
1. AUTO OPERATION MODE Connecting The Piping To Indoor Unit
The Auto operation will be activated immediately once the Please make flare after inserting flare nut (locate at joint portion
Auto Switch is pressed. of tube assembly) onto the copper pipe. (In case of using long
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING piping)
PURPOSE) Connect the piping
The Test Run operation will be activated if the Auto Switch • Align the center of piping and sufficiently tighten the flare
is pressed continuously for more than 5 sec. to below 10 nut with fingers.
sec.. A “pep” sound will occur at the fifth sec., in order to
• Further tighten the flare nut with torque wrench in specified
identify the starting of Test Run operation
torque as stated in the table.
3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote Controller receiving sound can be
change over by pressing the “AUTO” Switch continuously
for 10 sec. and above. A “pep”, “pep” sound will occur at the
tenth sec., in order to indicate the “ON/OFF” change over of
remote control receiving sound.

MODEL Piping size (Torque)


Gas Liquid
CS-C9CKPG 3/8” (42 N.m) 1/4” (18 N.m)
CS-C12CKPG 1/2” (55 N.m) 1/4” (18 N.m)

Connecting The Piping To Outdoor Unit


Decide piping length and then cut by using pipe cutter. Remove
burrs from cut edge. Make flare after inserting the flare nut
(located at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque
wrench to the specified torque as stated in the table.

35
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

CUTTING AND FLARING THE PIPING


1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder
entering the pipe.
3. Please make flare after inserting the flare nut onto the
copper pipes.

10.3.4. EVACUATION OF THE EQUIPMENT

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.

1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the valve of both the Low and High sides of the charging set and turn off the vacuum pump. Make sure that the needle
in the gauge does not move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.

CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.

36
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

10.3.5. OUTDOOR UNIT ELECTRICAL WIRING


1. Remove Top Panel.
2. Remove Control Board Cover (Metal & Resin).
3. Remove Plugs.
4. Fix the conduit connector to the conduit hole with lock-nut,
then secure it.
5. Connecting wire between indoor unit and outdoor unit
should be UL listed or CSA approved 4 × AWG16 wire.

6. Secure the wire onto the control board with the holder
(clamper).
7. Wire connection to the power supply (115V 60Hz) through
circuit breaker.
• Connect the UL listed or CSA approved wires (AWG14)
to the terminal board, and connect the other end of the
wires to circuit breaker.

Note: Secure the wires onto the control board


with the holder (clamper).
8. After completed wiring connection, fix back the control
board cover (metal and resin) and the top panel to the
original position with the screws.

10.3.6. PIPE INSULATION


1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM
with thickness 6 mm or above.

CHECK THE DRAINAGE

• Open front panel and remove air filters.


(Drainage checking can be carried out without removing the
front grille.)
• Pour a glass of water into the drain tray-styrofoam.
• Ensure that water flows out from drain hose of the indoor
unit.

37
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

EVALUATION OF THE PERFORMANCE

• Operate the unit at cooling operation mode for fifteen


minutes or more.
• Measure the temperature of the intake and discharge air.
• Ensure the difference between the intake temperature and
the discharge is more than 8°C (46.4°F).

CHECK ITEMS

Is there any gas leakage at flare nut connections? Is the indoor unit properly hooked to the installation plate?

Has the heat insulation been carried out at flare nut Is the power supply voltage complied with rated value?
connection?
Is there any abnormal sound?
Is the connecting wire being fixed to terminal board firmly?
Is the cooling operation normal?
Is the connecting wire being clamped firmly?
Is the thermostat operation normal?
Is the drainage OK?
(Refer to “Check the drainage” section) Is the remote control’s LCD operation normal?

Is the earth wire connection properly done? Is the air purifying filter installed?

38
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

11 2-way, 3-way Valve


2-way Valve (Liquid Side) 3-way Valve (Gas Side)

Works Shaft Position Shaft Position Service Port

Shipping Close Close Close


(With valve cap) (With valve cap) (With cap)

Evacuation Close Close Open


(Installation and (Counter-Clockwise) (Clockwise) (Push-pin)
Re-installation)

Operation Open Open Close


(With valve cap) (With valve cap) (With cap)

Pumping down Close Open Open


(Transferring) (Clockwise) (Counter-Clockwise) (Connected manifold
gauge)

Evacuation Open Open Open


(Servicing) With vacuum pump

Gas charging Open Open Open


(Servicing) (With charging cylinder)

Pressure check Open


(Servicing) Open Open (Connected manifold
gauge)

Gas releasing Open


(Servicing) Open Open (Connected manifold
gauge)

39
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

11.1. Air Purging of the Piping and Indoor Unit


11.1.1. Air purging (Installation)

Required tools: hexagonal wrench, adjustable wrench, torque The air in the indoor unit and in the piping must be purged. If air
wrenches, wrench to hold the joints and gas leak detector. remains in the refrigeration pipings, it will affect the
The additional gas for air purging has been charged in the compressor, reduce the cooling capacity, and could lead to a
outdoor unit. malfunction.
However, if the flare connections have not been done correctly
and there gas leaks, a gas cylinder and the charge set will be
needed.

Service port cap


Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas
leakage from the refrigeration cycle.

Procedure:
1. Recheck the piping connections. 6. Set the 3-way valve to the opened position.
2. Open the valve stem of the 2-way valve counter- 7. Mount the valve stem nuts to the 2-way and 3-way
clockwise approximately 90°, wait 10 seconds, and valves.
then set it to closed position. 8. Check for gas leakage.
• Be sure to use a hexagonal wrench to operate the valve • At this time, especially check for gas leakage from the 2-
stem. way and 3-way’s stem nuts, and from the service port
3. Check for gas leakage. cap.
• Check the flare connection for gas leakage.
4. Purge the air from the system Caution
If gas leakage is discovered in step (3) above, take
• Set the 2-way valve to the open position and remove the the following measures:
cap from the 3-way valve’s service port. If the leaks stop when the piping connections are
• Using the hexagonal wrench to press the valve core pin, tightened further, continue working from step (4).
discharge for three seconds and then wait for one If the gas leaks do not stop when the connections are
retightened, repair the location of the leak, discharge
minute.
all of the gas through the service port, and then
Repeat this three times. recharge with the specified amount of gas from a gas
5. Use torque wrench to tighten the service port cap to a cylinder.
torque of 1.8 kg.m. (18 N.m).

40
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

11.1.2. Pumping down (Re-installation)

Procedure:
1. Confirm that both the 2-way and 3-way valves are set to 5. Set the 2-way valve to the close position.
the opened position.
• Remove the valve stem caps and confirm that the valve 6. Operate the air conditioner at the cooling cycle and
stems are in the opened position. stop it when the gauge indicates 1 kg/cm2G (0.1 MPa).
• Be sure to use a hexagonal wrench to operate the valve
stems.
7. Immediately set the 3-way valve to the closed position.
• Do this quickly so that the gauge ends up indicating 3 to
2. Operate the unit for 10 to 15 minutes. 5 kg/cm2G (0.3 to 0.5 MPa).

3. Stop operation and wait for 3 minutes, then connect the 8. Disconnect the charge set, and mount the 2-way and 3-
charge set to the service port of the 3-way valve. way valve’s stem nuts and the service port caps.
• Connect the charge hose with the push pin to the Gas • Use a torque wrench to tighten the service port cap to a
service port. torque of 1.8 kg.m (18 N.m).
• Be sure to check for gas leakage.
4. Air purging of the charge hose.
• Open the low-pressure valve on the charge set slightly
to purge air from the charge hose.

41
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

11.1.3. Re-air purging (Re-installation)

Procedure:
1. Confirm that both the 2-way and 3-way valves are set to 5. Discharge the refrigerant.
the closed position. • Close the valve on the charging cylinder and discharge
the refrigerant until the gauge indicates 3 to 5 kg/cm2G
2. Connect the charge set and a charging cylinder to the (0.3 to 0.5 MPa)
service port of the 3-way valve.
• Leave the valve on the charging cylinder closed. 6. Disconnect the charge set and the charging cylinder,
and set the 2-way and 3-way valves to the open
position.
3. Air purging.
• Be sure to use a hexagonal wrench to operate the valve
• Open the valves on the charging cylinder and the
stems.
charge set. Purge the air by loosening the flare nut on
the 2-way valve approximately 45° for 3 seconds then
closing it for 1 minute; repeat 3 times. 7. Mount the valve stem nuts and the service port cap.
• After purging the air, use a torque wrench to tighten the • Be sure to use a torque wrench to tighten the service
flare nut on the 2-way valve. port cap to a torque 1.8 kg.m (18 N.m).
• Be sure to check for gas leakage.
4. Check for gas leakage.
• Check the flare connections for gas leakage.

42
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

11.1.4. Balance refrigerant of the 2-way, 3-way valves


(Gas leakage)

Procedure:
1. Confirm that both the 2-way and 3-way valves are set to
the open position.

2. Connect the charge set to the 3-way valve’s service


port.
• Leave the valve on the charge set closed.
• Connect the charge hose with the push pin to the
service port.

3. Open the valves (Low side) on the charge set and


discharge the refrigerant until the gauge indicates 0.5
to 1 kg/cm2G (0.05 to 0.1 MPa) .
• If there is no air in the refrigeration cycle [the pressure
when the air conditioner is not running is higher than 1
kg/cm2G (0.1 MPa)], discharge the refrigerant until the
gauge indicates 0.5 to 1 kg/cm2G (0.05 to 0.1 MPa). If
this is the case, it will not be necessary to apply a
evacuation.
• Discharge the refrigerant gradually; if it is discharged
too suddenly, the refrigeration oil will be discharged.

43
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

11.1.5. Evacuation (Installation)


(No refrigerant in the refrigeration cycle)

Procedure:
1. Connect the vacuum pump to the charge set’s centre
hose.

2. Evacuation for approximately one hour.


• Confirm that the gauge needle has moved toward -0.1
MPa (-76 cmHg) [vacuum of 4 mmHg or less.]

3. Close the valve (Low side) on the charge set, turn off
the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning
off the vacuum pump).

4. Disconnect the charge hose from the vacuum pump.


• Vacuum pump oil
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.

44
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

11.1.6. Gas charging


(After Evacuation)

Procedure:
1. Connect the charge hose to the charging cylinder.
• Connect the charge hose which you disconnected from This is different from previous procedures. Because you are
charging with liquid refrigerant from the gas side, absolutely do
the vacuum pump to the valve at the bottom of the no attempt to charge with large amount of liquid refrigerant
cylinder. while operating the air conditioner.
2. Purge the air from the charge hose.
• Open the valve at the bottom of the cylinder and press 4. Immediately disconnect the charge hose from the 3-
the check valve on the charge set to purge the air (be way valve’s service port.
careful of the liquid refrigerant). • Stopping partway will allow the refrigerant to be
3. Open the valve (Low side) on the charge set and charge discharged.
the system with liquid refrigerant. • If the system has been charged with liquid refrigerant
• If the system cannot be charged with the specified while operating the air conditioner, turn off the air
amount of refrigerant, it can be charged with a little at a conditioner before disconnecting the hose.
time (approximately 150 g each time) while operating 5. Mount the valve stem caps and the service port cap.
the air conditioner in the cooling cycle; however, one
• Use torque wrench to tighten the service port cap to a
time is not sufficient, wait approximately 1 minute and
torque of 18 N.m.
then repeat the procedure. (pumping down-pin)
• Be sure to check for gas leakage.

45
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

12 Servicing Information
Caution:
• Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use
a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
• Pb free solder will tend to splash when heated too high (about 1100° F/600°C).

12.1. Indoor Electronic Controllers Removal Procedures

1. The Electronic Controller, a Signal Receiver and an


Indicator (Fig. 3) can be seen by the below steps:

• Remove the 2 caps and 2 screws at the bottom of the


Front Grille. (Fig. 1)

• Remove the Front Grille by releasing the 2 hooks at the


top of the Front Grille. (Fig. 1)

Fig. 1

• Remove the Control Board Cover by releasing the 2


tabs at left, 1 tab on top and 1 tab at right side of the
Control Board Cover. (Fig. 2)

Fig. 2

2. To remove the Electronic Controller:


• Release the Particular Piece. (Fig. 3)
• Release the hook that hold the Electronic Controller.
(Fig. 3)

Fig. 3

12.2. Indoor Fan Motor and Cross Flow Fan Removal Procedures

• Remove the Control Board by:-

− Releasing CN-REC/DISP connectors. (Fig. 4)


− Releasing CN-FM connectors. (Fig. 4)
− Releasing CN-STM connector. (Fig. 4)
− Removing the Earth Wire screw. (Fig. 4)
− Releasing the Intake Air Sensor. (Fig. 4)
− Releasing the Piping Sensor. (Fig. 4)

Fig. 4

46
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

− Pulling out the Drain Hose from outlet to remove the


Discharge Grille. (Fig. 5)

− Removing the right and left screws. (Fig. 5)

− Then remove the Control Board by pressing down the


hook at the left and pushing up the right hook. (Fig. 5)

Fig. 5

− Release the Fan Motor leadwire by pressing the hook at


the center of the connector. (Fig. 6)

Fig. 6

− Remove the screw at the Cross Flow Fan. (Fig. 7)

− REMINDER - To reinstall the Fan Motor, adjust the


connector of the Fan Motor as shown in the Fig. 7.

Fig. 7

47
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

− Remove the screws at the left of the Evaporator. (Fig. 8)

Fig. 8

− Remove the Bearing. (Fig. 9)

− Push up the Evaporator and pull out the Cross Flow Fan
from shaft. By then, Fan Motor can be taken out. (Fig. 9)

Fig. 9

48
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

• Remote Control Reset

When the batteries are inserted for the first time, or the
batteries are replaced, all the indications will blink and the
remote control might not work.
If this happen, remove the cover of the remote control and
you will find a resetting terminal, and by shorting it with a
minus screwdriver, it will return to normal.

• Changing the wireless remote control transmission


code

When two indoor units are installed in the same room, in


order to prevent operating errors caused by using two
remote controls, cut a jumper wire at the remote control
printed circuit board (J - A) and cut a jumper wire at the
indoor printed circuit board (JX4). It is possible to select
from 4 types of transmission codes including one at time of
delivery condition (0).

49
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

13 Troubleshooting Guide
13.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.

50
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

13.1.1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode
Condition of the air
conditioner Low Pressure High Pressure Electric current during operation

Insufficient refrigerant (gas


leakage)

Clogged capillary tube or


Strainer

Short circuit in the indoor unit

Heat radiation deficiency of


the outdoor unit

Inefficient compression

• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.

13.1.2. Diagnosis methods of a malfunction of a compressor

Nature of fault Symptom

• Electric current during operation becomes approximately 20% lower than the normal value.

Insufficient compressing of a compressor • The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).

• The difference between high pressure and low pressure becomes almost zero.

• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.

51
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

14 Technical Data

52
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

53
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

15 Exploded View

Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.

54
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

16 Replacement Parts List


<Model: CS-C9CK / CS-C12CK>
REF. NO. PART NAME & DESCRIPTION QTY. CS-C9CK CS-C12CK REMARKS
1 CHASSY COMPLETE 1 CWD50C1257 ←
2 FAN MOTOR 1 CWA921143 ← 0
3 CROSS FLOW FAN COMPLETE 1 CWH02C1012 ←
4 BEARING ASS’Y 1 CWH64K007 ←
5 SCREW - CROSS FLOW FAN 1 CWH4580304 ←
6 EVAPORATOR 1 CWB30C1261 CWB30C1245
7 FLARE NUT 1 CWH6002140(1/4”) ←
8 FLARE NUT 1 CWT25005 (3/8”) CWT25007 (1/2”)
9 INTAKE AIR SENSOR HOLDER 1 CWH32142 ←
10 DISCHARGE GRILLE COMPLETE 1 CWE20C2166 ←
11 VERTICAL VANE 12 CWE241068 ←
12 CONNECTING BAR 2 CWE261024 ←
13 AIR SWING MOTOR 1 CWA98260 ← 0
14 LEAD WIRE - AIR SWING MOTOR 1 CWA67C3977 ←
15 CAP - DRAIN TRAY 1 CWH52C1001 ←
16 HORIZONTAL VANE 1 CWE241070 ←
17 PARTICULAR PIECE 1 CWD932162 ←
18 CONTROL BOARD 1 CWH102103B ←
19 TERMINAL BOARD COMPLETE 1 CWA28C2145 ← 0
20 POWER SUPPLY CORD 1 - -
21 ELECTRONIC CONTROLLER - MAIN 1 CWA742985 CWA742986 0
22 LEAD WIRE - FAN MOTOR 1 CWA67C3961 ←
23 ELECTRONIC CONTROLLER - RECEIVER 1 CWA742724 ← 0
24 SENSOR COMPLETE 1 CWA50C2135 ← 0
25 CONTROL BOARD FRONT COVER 1 CWH131090 ←
26 ELECTRONIC CONTROLLER - INDICATOR 1 CWE39C1068 ← 0
27 LEAD WIRE - INDICATOR 1 CWA67C3637 ←
28 INDICATOR HOLDER 1 CWD932163 ←
29 CONTROL BOARD TOP COVER 1 CWH131091 ←
30 REMOTE CONTROL COMPLETE 1 (1) CWA75C2297 ← 0
(2) CWA75C2299 ←
31 FRONT GRILLE COMPLETE 1 (1) CWE11C2713 ←
(2) CWE11C2755 ←
32 INTAKE GRILLE 1 CWE221036A ←
33 CONTROL PANEL 1 CWE312300 ←
34 DECORATION BASE (R) 1 CWE351067 ←
35 DECORATION BASE (L) 1 CWE351068 ←
36 GRILLE DOOR 1 CWE141047 ←
37 AIR FILTER 2 (1) CWD001047 ←
(2) CWD001098 ←
38 SCREW - FRONT GRILLE 2 XTN4+16C ←
39 CAP - FRONT GRILLE 2 CWH521062 ←
40 DRAIN HOSE 1 (1) CWH85287 ←
(2) CWH851044 ←
41 INSTALLATION PLATE 1 CWH36K1006 ←
42 ANTI-VIBRATION BUSHING 1 - -
43 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C067 ←
44 AIR PURIFYING FILTER 1 (1) CWD00C1088 ← 0
(2) CWMD00C0001 ←
45 SOLAR DEODORIZING FILTER 1 CWMD00C0002 ←
46 WIRE NET 1 CWD041033A ←
47 CONTROL BOARD COVER COMPLETE 1 CWH13C1053 ←
48 CONTROL BOARD COVER 1 CWH131113 ←
49 FULCRUM 1 CWH621013 ←

(Note)
• All parts are supplied from MAICO, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
• (1) — CS-C9CKPG-4, CS-C12CKPG-4 (USA).
• (2) — CS-C9CKPG-5, CS-C12CKPG-5 (Canada).

55
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

17 Exploded View

Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.

56
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

18 Replacement Parts List


<Model: CU-C9CK / CU-C12CK>
REF. NO. PART NAME & DESCRIPTION QTY. CU-C9CK CU-C12CK REMARKS
1 CHASSY ASS’Y 1 CWD50K2055A ←
2 SOUND PROOF MATERIAL 1 (1) CWG302125 CWG302154
(2) CWG302125 ←
3 FAN MOTOR BRACKET 1 CWD541030 ←
4 SCREW - FAN MOTOR BRACKET 2 CWH55413 ←
5 FAN MOTOR 1 CWA951235 ← 0
6 SCREW - FAN MOTOR MOUNT 3 CWH55406 ←
7 PROPELLER FAN ASS’Y 1 CWH03K1006 ←
8 NUT - PROPELLER FAN 1 CWH56053 ←
9 COMPRESSOR 1 2R13S126A6J 2P19S126C1A 0
10 ANTI - VIBRATION BUSHING 3 CWH50077 ←
11 NUT - COMPRESSOR MOUNT 3 CWH56000 ←
12 CONDENSER 1 CWB32C1291 CWB32C1267
13 TUBE ASS’Y (CAPILLARY TUBE) 1 CWB15K1070 CWB15K1096
14 STRAINER 1 CWB11025 CWB11004
15 HOLDER COUPLING ASS’Y 1 CWH351015A ←
16 2-WAY VALVE (LIQUID) 1 CWB021081 ← 0
17 3-WAY VALVE (GAS) 1 CWB011104 CWB011105 0
18 OVERLOAD PROTECTOR 1 CWA121113 CWA121114 0
19 HOLDER - O.L.P. 1 CWH7041200 ←
20 TERMINAL COVER 1 CWH171011 ←
21 NUT - TERMINAL COVER 1 CWH7080300 ←
22 SOUND PROOF BOARD 1 CWH151022A CWH151023A
23 CONTROL BOARD 1 CWH102186 ←
24 TERMINAL BOARD ASS’Y 1 CWA28C383 ←
25 CAPACITOR - COMPRESSOR 1 CWA312064 XS371506FP-B 0
(35µF, 370VAC) (50µF, 370VAC)
26 HOLDER CAPACITOR 1 CWH30057 ←
27 CAPACITOR - FAN MOTOR 1 CWA31270 ← 0
(8.0µF, 230VAC)
28 CABINET SIDE PLATE (L) 1 CWE041044A ←
29 CABINET SIDE PLATE (R) 1 CWE041043A CWE041073A
30 CABINET FRONT PLATE 1 CWE06K1036 ←
31 WIRE NET 1 CWD041028A CWD041037A
32 CABINET TOP PLATE 1 CWE031018A ←
33 PLATE - C. B. COVER 1 CWH131088 ←
34 CONTROL BOARD COVER 1 CWH131092 ←
35 HANDLE 1 CWE161010 ←
36 OPERATION INSTRUCTIONS 1 (1) CWF563841 ←
(2) CWF563842 ←
37 INSTALLATION INSTRUCTIONS 1 CWF612332 ←
38 MAGNET RELAYS 1 K6A1ALA00001 ←

(Note)
• All parts are supplied from MAICO, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
• (1) — CU-C9CKP6G-4, CU-C12CKP6G-4 (USA).
• (2) — CU-C9CKP6G-5, CU-C12CKP6G-5 (Canada).

57
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

19 Electronic Circuit Diagram

• CS-C9CK / CU-C9CK
• CS-C12CK / CU-C12CK

SCHEMATIC DIAGRAM 1/3

MAIN

R12 R08
1k 5.1k

C02

R11 C01 R07


RECEIVER 1k 10k

(MX3) R18 D05


CN-RCV1 R19 D06
3 1 D07
R20
2 2
1 3 R21 D08
5
4 — R22 D09
R23 D10
R24 D11
R25 D12
C29

INDICATOR
(PH10)
SW101 CN-DISP
AUTO
1 2 10
9
CN-DISP
8 R13
1 7 220
POWER GRN D101 2 6
3 5
R14
4 4 330
QUIET ORG D102
5 3
6 2 R15
D103
TIMER ORG 330
7 1

GRN D104 R16


ECONOMY 110

POWERFUL ORG D105 R17


C23 330

R60 C28
10k

R06
24k

(XH4)
C22 R58 R59
CN-HA 10k 1k
4
3
2
1

R30 C04
20k R33 C08
(PH4) 15k
AIR TEMP. SENSOR
(15k 3950) CN-TH
1
2
3
4
PIPE TEMP. SENSOR
1 R/B RS 8
(20k 3950)
2 Vcc GND 7
IC02
R05 R04
43 /2W 43 /2W 9
10 g 7
3 CS D0 6

11 6 C05
4 SK D1 5
RY-PWR f 0.1
12 5
e
13 4
d
(PH5) 14 c 3
CN-STM 15 2
b
1 1
2 2
16 a 1
3 3 8
4 4 IC05
5 5
A52A2003GR
(ZH5)
AIR SWING STEPPING MOTOR DRIVE
MOTOR

58
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

SCHEMATIC DIAGRAM 2/3

TEST R01 R02


1k
10k

BZ
Q01 BZ1
c
b R55
1k
4.7k 10k e

R34
51k

R10
10k
64

P46/AD6 63

P45/AD5 62

P44/AD4 61

P43/AD3 60

P42/AD2 59

P41/AD1 58

57

56

55

54

53

52

P74 51

P73 50

49
P40/AD0

P67

P66

P65

P64

P75

P72
P47/AD7

P71
1 P50/A8 48 SSR01
Q03 c
P51/A9 P70 b
2 RY-PWR DRIVE SIGNAL 47
STEPPING 4.7k 10k e
MOTOR TIMER SHORTEN
P52/A10 P03/INTP3 46
3 DRIVE
SIGNAL FAN SPEED
P53/A11 DRIVE SIGNAL P02/INTP2
4 BUZZER 45
AUTO OPERATION
P54/A12 TEST RUN P01/INTP1
5 DISPLAY 44
REMOTE CONTROL
P55/A13 SOUND
6 P00/INTP0 43

P56/A14 POWER CLOCK INPUT


7 Vss1 42
REMOTE-CONTROL
8 P57/A15 IC01 COMMAND INPUT X1
41
A52D0022GB75 X2
R32
Vss0 OSC 150k
9 40

10 VDD0 IC 39 X01
4.096MHz
11 P30 XT1 38 (47pF X 2)

INTAKE AIR TEMP


12 P31 XT2 37

Reset
13 P32 PIPE TEMP RESET 36

14 P33 AUTO RESTART GROUND AVd0 35


POWER C10
P34 AVref
15 34 R31
P22/SCK

P11/AN1

P35
P17/AN7

P16/AN6

P15/AN5

P14/AN4

P13/AN3

P12/AN2

16 P10 33
P20/S1

P21/S0

VDD1

/ANO
AVss

R56
P36

P23

P24

P25

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

JX2 R09
10k

59
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

SCHEMATIC DIAGRAM 3/3

1 1
2 2
3 3

L BR
MOTOR
N
POWER SUPPLY

R
AC B
RY-PWR
(WHT)
MAGNETIC
RELAY
B

5 1

W 6 4

B
FUSE
OVERLOAD
PROTECTOR B R

IC04 IC03
DB01 REGULATOR REGULATOR
T01
5 8 ~
+
2 13 I 12V O I 5V O
C17 C14 C11 Y
~
G G
35V 25V 16V
(NHG)
COMPRESSOR

R41 R44
1.0k 1k
Q04 R47 R57 C03 ZNR03
POWER CLOCK 39k/2W 39k/2W 511U
GENERATOR
R03 R26 4 PC01 1
C16 c R48
b 820 3.9k 510 SSR01
3 2
ZNR01 L01
e R29 C07 511U 125 H
4.7k
C19
C-FM
C12 R36
1k

CN-FM 1 2 3 4 5
JX1
ZD1
R43 7.5EL1
RX1 R50 R51 C21
R49 100k 10k R52
1k 6.2k 50V
c
R42 JX3 C18 R53 (PH-3)
24k b 10k
c
R37 C15 JX4 R40 e b CN-FB1 FAN
10k R38 10k
MOTOR
3
e R54
Q05 6.2k 2
1
RESET SIGNAL Q06
REMOTE CONTROL NO. GENERATION
RESET SIGNAL
JX3 JX4 RX1
GENERATION
0 SHORT SHORT
1 SHORT OPEN
2 OPEN OPEN 10K
3 SHORT OPEN 10K

60
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

61
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

How to use electronic circuit diagram

TIMER TABLE
Test Mode
Name Time (When test point Remarks
Short-circuited)
Real Timer 1 hr. 1 min.
10 min. 10 sec.
1 min. 1 sec.
Time Delay Safety Control 2 min. 58 sec. 0 sec.
Forced Operation 60 sec. 0 sec.
Time Save Control 7 min. 4.2 sec.
Anti-Freezing 4 min. 0 sec.
Auto Mode Judgement 20 sec. 0 sec.
Soft Dry OFF 6 min. 36 sec.
ON 10 min. 60 sec. Soft Dry: 10 min. operation
Cooling 40 sec. 4 sec.
70 sec. 7 sec.
Deodorizing Control 20 sec. 2 sec.
180 sec. 18 sec.
Soft Dry 40 sec. 4 sec.
360 sec. 36 sec.
Comp. Reverse Rotation Detection 5 min. 30 sec. Comp. ON 5 min. and above
2 min 0 sec.
Comp./ Fan Motor Delay Timer 1.6 sec. 0 sec.
Powerful Mode Operation 15 min. 15 sec
Random Auto Restart Control 0 ~ 62 sec. 0 ~ 6.2 sec.

62
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

19.1. REMOTE CONTROL

63
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

19.2. PRINT PATTERN


INDOOR UNIT PRINTED CIRCUIT BOARD

TOP VIEW

64
CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G

19.3. PRINT PATTERN


INDOOR UNIT PRINTED CIRCUIT BOARD

BOTTOM VIEW

65 [MAICO] Printed in Malaysia