Manufacturer assumes no responsibility for a hazard or

damage caused by incorrect or non-application of any of the


instructions attached herein. Under no circumstance shall 1.Features
Larsen & Toubro be liable for any consequential or resulting
injury or for loss, damage or expense directly or indirectly from · Accuracy class 1 as per IEC 62053-21, class 0.5, 0.5S as per IEC 62053-22
the use of this product. Sufficient care is taken to provide all · True RMS measurement
INSTRUCTION MANUAL information regarding the product but Larsen & Toubro does
not claim any responsibility for the damage caused by using the · Password protection provision
product directly or indirectly. Use according to the operating · Site selectable for 3 Phase 4 Wire, 3 Phase 3 Wire, 1 Phase
Digital Panel Meter instructions, professional practices, wiring rules, codes, safety
regulations applicable to the given installation. · Site programmable CT/PT ratio
Basic Multifunction Meter · Auto-scaling of kilo, mega & giga values
During normal operation of this instrument ,hazardous · Positive accumulation of active energy
4400 LED series voltages are present at the rear terminals, which can cause · Autoscrolling & freeze mode provision is available
injury or death. Installation ,disconnection or removal of the
meter should be carried out only by qualified, trained · User selectable energy measurement : Wh/VAh
personnel, after de-energizing connected circuits. Improper
installation , including improper grounding will void warranty.
Product warranty void if seal is broken.

2. LED Indication 3. Display of Parameters 4. Technical Specification


WL 4400
Display Meaning Total Watts 3 Ph 4 W, 3 Ph 3 W, 1 Ph
LL Voltage Line to Line PF Power Factor Type of Type True RMS, 64 samples
measurement per cycle 1 sec update
Lag (ON) Voltage Line to Neutral Active Energy Received time
M Mega Both on
41 5.0 P.P -

Kilo
{Giga Voltage RY Phase Load Hour Class 1 as per
K
IEC 62053-21
Reverse
Communication Voltage YB Phase Power Factor R Phase/Y Phase/B Phase Measurement
REV DO
Class 0.5 as per
ON
Voltage BR Phase VA - R Phase/Y Phase/B Phase accuracy IEC 62053-22
Digital Output PRG
Pulse
MULTIFUNCTION METER A Average Current Voltage R / Y / B Phase Class 0.5S as per
IEC 62053-22
To select the value F Frequency Current R / Y / B Phase 4 digit for instantaneous
To edit the
or accept the value
Display type LED
value/Parameter & 6 digits for cumulative
in programming in programming UA Total VA Watts R / Y / B Phase & resolution
mode mode

50 - 550 VLL Impulse voltage test ±6 kV as per IEC 62052-11


Insulation
PT Primary and Secondary user programmable AC voltage test 4 kV double insulation as per IEC 62053-21
Input voltage for LT and HT applications properties
Insulation resistance 500 V DC as per IS 13779
Burden: 0.2VA max per phase Operating temperature O
-10 C to +55 C
O

Measuring -/5A and -/1A site selectable Storage temperature O


-25 C to +70 C
O
Operating
circuit Current range from 10% to 120% of In (50mA-5A), conditions Humidity 5% to 95% relative humidity non-condensing
Input current Starting current : 0.4% of full scale
Recommended wire 2.5 sq mm
CT Primary and Secondary user Shock As per standard IEC 60068-2
programmable for LT and HT applications Mechanical Vibration 10 to 55 Hz, 0.15 mm amplitude
Frequency 40 - 70 Hz conditions
Casing Plastic mould protected to IP51 from front side
Aux voltage 80 - 300V AC/DC Measurement category CAT III
Auxiliary <5VA
circuit Aux burden Safety Pollution degree 2
Freq range 40 - 70 Hz Protection IP20 at terminals, IP51 on front
Test of power consumption as per IEC 62053-21 Product weight 300 gms
Electrical
Voltage dips and interrupts as per IEC 62053-21 Weight & Bezel dimension (W x H x D) 96 x 96 x 58 mm
requirements dimensions
Short time over current protection 10A max continuous, 20 times of In for 3 sec Panel cutout 92 x 92 mm +0.8
- 0.0
Fast transients burst test ±4 kV as per IEC 61000-4-4
Outputs Meter constant: 1250/(external CT ratio x PT ratio)
Immunity to ±8 kV air discharge, ±6 kV contact
electrostatic discharge discharge as per IEC 61000-4-2 Type RS485 port Modbus RTU
Electro- Radiated, Radio-frequency, Baud rate 2400, 4800, 9600, 19200 bps (site selectable)
10 V/m as per 61000-4-3
magnetic Electromagnetic field immunity test Parity Odd, Even, None
compatibility Immunity to electromagnetic HF Communication
10 V/m as per IEC 61000-4-6 Slave id 1 to 247 (programmable)
(EMC) fields through conducted lines
Surge immunity test ±6 kV as per IEC 61000-4-5 Isolation 2 kVAC isolation for 1 minute between
Rated power frequency magnetic fields 1 A/m as per IEC 61000-4-8 communication and other circuits
Emission Class B as per CISPR 22 Certifications CE, RoHS
5. Programming Mode 5.2.2. Programming Mode PT Secondary 4150P.S 415.0 50V to 550V
5.1 Programming keys · Press DOWN to enter Programming Mode
CT Primary 5000C.P 5.000 0.5A - 99kA
· Press UP key to select the Edit Mode
To select Edit Mode and save parameter  Blink indicates Edit Mode is ON CT Secondary 5000C.S 5.000 0.5A - 6A
DOWN to decrement value or parameter · Press DOWN to decrement values or Yes/No
to select from available options Reverse Lock No If YES it blocks energy accumulation in
5.2 General Programming Guide case the CT polarity reverse.
· Press UP to accept the value of the parameter
· Press UP + Down to enter Programming Mode · Press DOWN to edit next parameters till end Method of VA Selection:
VA Selection UE C.H UA. VECH Arithmetic /Vector harmonics /Vector
· Enter Password (default value 0000) after the configuration of last parameter display
· Blink indicates Edit Mode is ON screen will prompt “SAVE”, Display reads “Y” (YES) *Digital output 1 disable Single Phase/Wh/Under PF, F, A, V/ Over W, F, A, V
· Press DOWN to decrement value · Press DOWN to change to “ ” (NO) *Threshold value 1 1000 000-999.9 M
0/9/8/7/6/5/4/3/2/1 · Press UP to save *Digital Output Delay 3.000 1-180 sec
· Press UP to move to the next digit till 4th digit
If Password is correct, meter display reads 5.3. Display Baud Rate 9600 2400, 4800, 9600 19.2k
For Clear Mode move to step 5.2.1 First four digit : Parameter value Parity Even Even/Odd/none
For Programming Mode move to step 5.2.2 41 5.0 P.P 5th & 6th digit : Parameter to edit Slave Id 1 . 0 0 0 S L 1.000 1 to 247

5.2.1.Clear Mode Programming PASSWORD 0000 0000 to 9999


Default Option/Range
· Press UP to Enter Clear Mode Display reads “ ” Parameter Energy Resolution Resolution/Counter
· Press UP to clear parameter. Display prompts “ ” Pulse Output ON time 2 5 0 . 0 p o 250 50 to 500 msec
ConFIG
· Press DOWN to change for “y” (yes) to clear values Defines the 3P 4W Energy Selection Wh Wh/VAh
· Press UP to clear power system 3P 4W 3P 3W
configuration. * Optional for select product variants
1 Phase
If password is incorrect, meter will display next 5.4. Enabling and Disabling Auto Scrolling
parameter but cannot be edited. 100V-999kV Press DOWN for 6 secs
To set 33kV Set first four digits
PT Primary (3300) as explained above press Display Shows: EnbL. Au.
415 UP/DOWN key to place decimal point
Again press DOWN for 6 sec
4150P.P at appropriate location.
Letter K/M will indicate the Kilo/Mega. Display Shows: dSbL. Au.
M & K both LED will glow for Giga

6. Memory Map

Address Parameter Data type Address Parameter Data type Address Parameter Data type Address Parameter Data type

40101 Watts Total float 40123 PF B phase float 40137 VY B phase float 40151 Current R phase float
40103 Watts R phase float 40125 VA total float 40139 VB R phase float 40153 Current Y phase float
40105 Watts Y phase float 40127 VA R phase float 40141 VL N average float 40155 Current B phase float
40107 Watts B phase float 40129 VA Y phase float 40143 V R phase float 40157 Frequency float
40117 PF Avg (inst) float 40131 VA B phase float 40145 V Y phase float 40159 Wh float
40119 PF R phase float 40133 VL L average float 40147 V B phase float 40161 VAh float
40121 PF Y phase float 40135 VR Y phase float 40149 Current Total float 40217 Load Hours Unsigned long

7. Wiring Diagram 8. Mounting Dimensions


In case of complaint please contact

WL44000501A
+2.0
90 - 0.0 Steps for Mounting
CUSTOMER INTERACTION CENTRE (CIC)
Insert meter to panel
Received (Import) Delivered (Export) Received (Import) Delivered (Export) Received (Import) Delivered (Export) 1 TOLL-Free: 1800 233 5858, 1800 200 5858
without clamps
Telephone : 022 6774 5858
2 2
Load Line Load Line Load Line 1 Insert both clamps email: cic@LNTEBG.com
3

+2.0
90 - 0.0

L&T Electrical & Automation


AMF IP AMF IP AMF IP
240V AC 240V AC 240V AC

Electrical Standard Products


L&T Business Park, Tower 'B' / 3rd Floor
54mm
3 Saki Vihar Road, Powai Mumbai 400 072
3 Phase 4 Wire System 3 Phase 3 Wire System Single Phase System 4mm
Website: www.Lntebg.com
Manufacturer assumes no responsibility for a hazard or
damage caused by incorrect or non-application of any of the
instructions attached herein. Under no circumstance shall 1.Features
Larsen & Toubro be liable for any consequential or resulting
injury or for loss, damage or expense directly or indirectly from · Accuracy class 1 as per IEC 62053-21, class 0.5 as per IEC 62053-22
the use of this product. Sufficient care is taken to provide all · True RMS measurement
INSTRUCTION MANUAL information regarding the product but Larsen & Toubro does
not claim any responsibility for the damage caused by using the · Password protection provision
product directly or indirectly. Use according to the operating · Site selectable for 3 Phase 4 Wire, 3 Phase 3 Wire, 1 Phase
Digital Panel Meter instructions, professional practices, wiring rules, codes, safety
regulations applicable to the given installation. · Site programmable CT/PT ratio
Basic Multifunction Meter · Auto-scaling of kilo, mega & giga decimal value
During normal operation of this instrument ,hazardous · Positive accumulation of active energy
4400 LCD series voltages are present at the rear terminals, which can cause · Autoscrolling & freeze mode provision is available
injury or death. Installation ,disconnection or removal of the · User selectable energy measurement : Wh/VAh
meter should be carried out only by qualified, trained
personnel, after de-energizing connected circuits. Improper
installation , including improper grounding will void warranty.
Product warranty void if seal is broken.

2. LED Indication 3. Display of Parameters 4. Technical Specification


WC 4400
Display Meaning PF Power Factor 3 Ph 4 W, 3 Ph 3 W, 1 Ph
LL Voltage Line to Line Active Energy Received Type of Type True RMS, 64 samples
measurement per cycle 1 sec update
Voltage Line to Neutral Load Hour
time
Voltage RY Phase Power Factor R Phase/Y Phase/B Phase
Class 1 as per
Voltage YB Phase VA - R Phase/Y Phase/B Phase IEC 62053-21
Voltage R / Y / B Phase Measurement Class 0.5 as per
Voltage BR Phase accuracy IEC 62053-22
Pulse
A Average Current Current R / Y / B Phase
PRG Class 0.5S as per
MULTIFUNCTION METER F Frequency Watts R / Y / B Phase IEC 62053-22
Communication To edit the To select the value UA Total VA Display type LCD 4 digit for instantaneous
value/Parameter or accept the value
ON in programming in programming Total Watts and resolution & 7 digits for cumulative
mode mode

50 - 550 VLL Impulse voltage test ±6 kV as per IEC 62052-11


Insulation
PT Primary and Secondary user programmable AC voltage test 4 kV double insulation as per IEC 62053-21
Input voltage for LT and HT applications properties
Insulation resistance 500 V DC as per IS 13779
Burden: 0.2VA max per phase Operating temperature
O
-10 C to +55 C
O

Measuring -/5A and -/1A site selectable Storage temperature


O
-25 C to +70 C
O
Operating
circuit Current range from 10% to 120% of In (50mA-6A), conditions Humidity 5% to 95% relative humidity non-condensing
Input current Starting current : 0.6% of full scale
Recommended wire 2.5 sq mm
CT Primary and Secondary user Shock As per standard IEC 60068-2
programmable for LT and HT applications Mechanical Vibration 10 to 55 Hz, 0.15 mm amplitude
Frequency 40 - 70 Hz conditions
Casing Plastic mould protected to IP51 from front side
Aux voltage 80 - 300V AC/DC Measurement category CAT III
Auxiliary <5VA
circuit Aux burden Safety Pollution degree 2
Freq range 40 - 70 Hz Protection IP20 at terminals, IP51 on front
Test of power consumption as per IEC 62053-21 Product weight 300 gms
Electrical
Voltage dips and interrupts as per IEC 62053-21 Weight & Bezel dimension (W x H x D) 96 x 96 x 58 mm
requirements dimensions
Short time over current protection 10A max continuous, 20 times of In for 3 sec Panel cutout 92 x 92 mm +0.8
- 0.0
Fast transients burst test ±4 kV as per IEC 61000-4-4
Outputs Meter constant: 2500/(external CT ratio x PT ratio)
Immunity to ±8 kV air discharge, ±6 kV contact
electrostatic discharge discharge as per IEC 61000-4-2 Type RS485 port Modbus RTU
Electro- Radiated, Radio-frequency, Baud rate 2400, 4800, 9600, 19200 bps (site selectable)
10 V/m as per 61000-4-3
magnetic Electromagnetic field immunity test Parity Odd, Even, None
compatibility Immunity to electromagnetic HF Communication
10 V/m as per IEC 61000-4-6 Slave id 1 to 247 (programmable)
(EMC) fields through conducted lines
Surge immunity test ±6 kV as per IEC 61000-4-5 Isolation 2 kVAC isolation for 1 minute between
Rated power frequency magnetic fields 1 A/m as per IEC 61000-4-8 communication and other circuits
Emission Class B as per CISPR 22 Certifications CE, RoHS
5. Programming Mode 5.2.2. Programming Mode PT Secondary P.SY415.0 415.0 50V to 550V
5.1 Programming keys · Press DOWN to enter Programming Mode CT Primary 5.000 0.5A - 99kA
· Press UP key to select the Edit Mode
To select Edit Mode and save parameter  Blink indicates Edit Mode is ON CT Secondary C.SY5.000 5.000 0.5A - 6A
DOWN to decrement value or parameter · Press DOWN to decrement values or Yes/No
to select from available options Reverse Lock No If YES it blocks energy accumulation in
case the CT polarity reverse.
5.2 General Programming Guide · Press UP to accept the value of the parameter
· Press UP + Down to enter Programming Mode Method of VA Selection: Arithmetic /
· Press DOWN to edit next parameters till end VA Selection ua.uech VECH Vector harmonics /Vector
· Enter Password (default value 0000) after the configuration of last parameter display
· Blink indicates Edit Mode is ON
* Digital Output 1 disable disable, Wh, Under/Over - PF, V, A, F
screen will prompt “SAVE”, Display reads “Y” (YES)
· Press DOWN to decrement value · Press DOWN to change to “ ” (NO) * Threshold value 1000 0.001-999.9
0/9/8/7/6/5/4/3/2/1 · Press UP to save * Digital Output 2 2 disable disable, Wh, Under/Over - PF V, A, F
· Press UP to move to the next digit till 4th digit
If Password is correct, meter display reads 5.3. Display * Threshold value 2 2 1000 0.001-999.9
For Clear Mode move to step 5.2.1 First three digit : Parameter to edit * Digital Output Delay 3.000 1-180 sec
For Programming Mode move to step 5.2.2 4th to 7th digit : Parameter value
Baud Rate 9600 2400, 4800, 9600 19.2k
5.2.1.Clear Mode Programming Option/Range Parity Even Even/Odd/none
Parameter Default
· Press UP to Enter Clear Mode Display reads “ ” Slave Id sl1000 1.000 1 to 247
· Press UP to clear parameter. Display prompts “ ” ConFIG
Defines the 3P 4W PASSWORD 0000 0000 to 9999
· Press DOWN to change for “y” (yes) to clear values
power system 3P 4W 3P 3W Energy Resolution Resolution/Counter
· Press UP to clear configuration.
1 Phase Pulse Output ON Time p 0 2 5 0 . 0 250 50 to 500 msec
If password is incorrect, meter will display next parameter Energy Selection Wh Wh/VAh
but cannot be edited. 100V-999kV
PT Primary To set 33kV Set first four digits 5.4. Enabling and Disabling Auto Scrolling * optional for select product variants
(3300) as explained above press Press DOWN for 6 secs
415 UP/DOWN key to place decimal point
at appropriate location. Display Shows: EnbL. Au.
Letter K/M will indicate the Kilo/Mega. Again press DOWN for 6 sec
Display Shows: dSbL. Au.

6. Memory Map

Address Parameter Data type Address Parameter Data type Address Parameter Data type Address Parameter Data type

40101 Watts Total float 40123 PF B phase float 40137 VY B phase float 40151 Current R phase float
40103 Watts R phase float 40125 VA total float 40139 VB R phase float 40153 Current Y phase float
40105 Watts Y phase float 40127 VA R phase float 40141 VL N average float 40155 Current B phase float
40107 Watts B phase float 40129 VA Y phase float 40143 V R phase float 40157 Frequency float
40117 PF Avg (inst) float 40131 VA B phase float 40145 V Y phase float 40159 Wh float
40119 PF R phase float 40133 VL L average float 40147 V B phase float 40161 VAh float
40121 PF Y phase float 40135 VR Y phase float 40149 Current Total float 40217 Load Hours Unsigned long

7. Wiring Diagram 8. Mounting Dimensions


In case of complaint please contact

WC44000501A
+2.0 Steps for Mounting
90 - 0.0 CUSTOMER INTERACTION CENTRE (CIC)
Insert meter to panel
Received (Import) Delivered (Export) Received (Import) Delivered (Export) Received (Import) Delivered (Export) 1 TOLL-Free: 1800 233 5858, 1800 200 5858
without clamps
Telephone : 022 6774 5858
2 2
Load Line Load Line Load Line Insert both clamps email: cic@LNTEBG.com
1 3

+2.0
90 - 0.0

L&T Electrical & Automation


AMF IP AMF IP AMF IP
240V AC 240V AC 240V AC

Electrical Standard Products


L&T Business Park, Tower 'B' / 3rd Floor
3 Phase 4 Wire System 3 Phase 3 Wire System Single Phase System 54mm Saki Vihar Road, Powai Mumbai 400 072
3
4mm Website: www.Lntebg.com
Manufacturer assumes no responsibility for a hazard or
damage caused by incorrect or non-application of any of the
instructions attached herein. Under no circumstance shall 1.Features
Larsen & Toubro be liable for any consequential or resulting
injury or for loss, damage or expense directly or indirectly from · Accuracy class 1 as per IEC 62053-21, class 0.5, 0.5S as per IEC 62053-22
the use of this product. Sufficient care is taken to provide all · True RMS measurement
INSTRUCTION MANUAL information regarding the product but Larsen & Toubro does
not claim any responsibility for the damage caused by using the · Password protection provision
product directly or indirectly. Use according to the operating · Site selectable for 3 Phase 4 Wire, 3 Phase 3 Wire, 1 Phase
Digital Panel Meter instructions, professional practices, wiring rules, codes, safety
regulations applicable to the given installation. · Site programmable CT/PT ratio
Basic Multifunction Meter · Auto-scaling of kilo, mega & giga values
During normal operation of this instrument ,hazardous · Positive accumulation of active energy
4405 LED series voltages are present at the rear terminals, which can cause · Autoscrolling & freeze mode provision is available
injury or death. Installation ,disconnection or removal of the
meter should be carried out only by qualified, trained · User selectable energy measurement : Wh/VAh
personnel, after de-energizing connected circuits. Improper
installation , including improper grounding will void warranty.
Product warranty void if seal is broken.

2. LED Indication 3. Display of Parameters Total Watts 4. Technical Specification

Display Meaning PF Power Factor 3 Ph 4 W, 3 Ph 3 W, 1 Ph


Lag (ON)
Voltage Line to Line Active Energy Received Type of Type True RMS, 64 samples
Both on Mega measurement
Giga{ Kilo
230.5 L Voltage Line to Neutral
Load Hour per cycle 1 sec update
time
Power Factor R Phase/Y Phase/B Phase
5.000 A Voltage RY Phase
VA - R Phase/Y Phase/B Phase
Class 1 as per
IEC 62053-21
50.00 F Voltage YB Phase Measurement Class 0.5 as per
Voltage R / Y / B Phase
Voltage BR Phase accuracy IEC 62053-22
Communication Pulse Current R / Y / B Phase
ON
Average Current Class 0.5S as per
Watts R / Y / B Phase IEC 62053-22
To edit the To select the value Frequency Active energy received old 4 digit for instantaneous
value/Parameter or accept the value Display type LED
in programming in programming UA Total VA Load Hour Old & resolution & 6 digits for cumulative
mode mode

50 - 550 VLL Impulse voltage test ±6 kV as per IEC 62052-11


Insulation
PT Primary and Secondary user programmable AC voltage test 4 kV double insulation as per IEC 62053-21
Input voltage for LT and HT applications properties
Insulation resistance 500 V DC as per IS 13779
Burden: 0.2VA max per phase Operating temperature O
-10 C to +55 C
O

Measuring -/5A and -/1A site selectable Storage temperature O


-25 C to +70 C
O
Operating
circuit Current range from 10% to 120% of In (50mA-5A), conditions Humidity 5% to 95% relative humidity non-condensing
Input current Starting current : 0.4% of full scale
Recommended wire 2.5 sq mm
CT Primary and Secondary user Shock As per standard IEC 60068-2
programmable for LT and HT applications Mechanical Vibration 10 to 55 Hz, 0.15 mm amplitude
Frequency 40 - 70 Hz conditions
Casing Plastic mould protected to IP51 from front side
Aux voltage 80 - 300V AC/DC Measurement category CAT III
Auxiliary <5VA
circuit Aux burden Safety Pollution degree 2
Freq range 40 - 70 Hz Protection IP20 at terminals, IP51 on front
Test of power consumption as per IEC 62053-21 Product weight 300 gms
Electrical
Voltage dips and interrupts as per IEC 62053-21 Weight & Bezel dimension (W x H x D) 96 x 96 x 58 mm
requirements dimensions
Short time over current protection 10A max continuous, 20 times of In for 3 sec Panel cutout 90 x 90 mm +2-0
Fast transients burst test ±4 kV as per IEC 61000-4-4
Outputs Meter constant: 1250/(external CT ratio x PT ratio)
Immunity to ±8 kV air discharge, ±6 kV contact
electrostatic discharge discharge as per IEC 61000-4-2 Type RS485 port Modbus RTU
Electro- Radiated, Radio-frequency, Baud rate 2400, 4800, 9600, 19200 bps (site selectable)
10 V/m as per 61000-4-3
magnetic Electromagnetic field immunity test Parity Odd, Even, None
compatibility Immunity to electromagnetic HF Communication
10 V/m as per IEC 61000-4-6 Slave id 1 to 247 (programmable)
(EMC) fields through conducted lines
Surge immunity test ±6 kV as per IEC 61000-4-5 Isolation 2 kVAC isolation for 1 minute between
Rated power frequency magnetic fields 1 A/m as per IEC 61000-4-8 communication and other circuits
Emission Class B as per CISPR 22 Certifications CE, RoHS
5. Programming Mode · Press DOWN to decrement values or PT Secondary P.SEC 415.0 50V to 550V
5.1 Programming keys to select from available options CT Primary 5.000 0.5A - 99kA
· Press UP to accept the value of the parameter
To select Edit Mode and save parameter CT Secondary C.SEC 5.000 0.5A - 6A
· Press DOWN to edit next parameters till end
DOWN to decrement value or parameter after the configuration of last parameter display Yes/No
Reverse Lock no If YES it blocks energy accumulation in
screen will prompt “SAVE”, Display reads “YES” (YES) case the CT polarity reverse.
5.2 General Programming Guide · Press DOWN to change to “no” (NO)
· Press UP + Down to enter Programming Mode Method of VA Selection:
· Press UP to save VA Selection VA.SL VEC.H Arithmetic /Vector harmonics /Vector
· Enter Password (default value 0000)
· Blink indicates Edit Mode is ON Baud Rate 9600 2400, 4800, 9600 19.2k
· Press DOWN to decrement value 5.3. Display Parity Even Even/Odd/none
0/9/8/7/6/5/4/3/2/1 Slave Id 1.000 1 to 247
Row1: Options
· Press UP to move to the next digit till 4th digit PASSWORD 0000 0000 to 9999
If Password is correct, meter display reads
Row2: Parameter Energy Resolution Resolution/Counter
For Clear Mode move to step 5.2.1
For Programming Mode move to step 5.2.2 Pulse Output ON time 250 50 to 500 msec
Programming Energy Selection E . S E L Wh Wh/VAh
5.2.1.Clear Mode Default Option/Range
Parameter
· Press UP to Enter Clear Mode Display reads “SEt.CLr”
· Press UP to clear parameter. Display prompts “no” ConF
Defines the 3P 4W 5.4. Enabling and Disabling Auto Scrolling
· Press DOWN to change for “YES” (yes) to clear values power system Press DOWN for 6 secs
3P 4W 3P 3W
· Press UP to clear configuration. Display Shows: EnbL. AutO
1 Phase
Again press DOWN for 6 sec
If password is incorrect, meter will display next
100V-999kV Display Shows: dSbL. AutO
parameter but cannot be edited. To set 33kV Set first four digits
PT Primary (3300) as explained above press
5.2.2. Programming Mode 415 UP/DOWN key to place decimal point
P.p at appropriate location.
· Press DOWN to enter Programming Mode Letter K/M will indicate the Kilo/Mega.
· Press UP key to select the Edit Mode
 Blink indicates Edit Mode is ON

6. Memory Map

Address Parameter Data type Address Parameter Data type Address Parameter Data type Address Parameter Data type

40101 Watts Total float 40123 PF B phase float 40137 VYB phase float 40151 Current R phase float
40103 Watts R phase float 40125 VA total float 40139 VBR phase float 40153 Current Y phase float
40105 Watts Y phase float 40127 VA R phase float 40141 VLN average float 40155 Current B phase float
40107 Watts B phase float 40129 VA Y phase float 40143 V R phase float 40157 Frequency float
40117 PF Avg (inst) float 40131 VA B phase float 40145 V Y phase float 40159 Wh float
40119 PF R phase float 40133 VLL average float 40147 V B phase float 40161 VAh float
40121 PF Y phase float 40135 VRY phase float 40149 Current Total float 40217 Load Hours Unsigned long

7. Wiring Diagram 8. Mounting Dimensions


In case of complaint please contact

WL44050506A
+2.0
90 - 0.0 Steps for Mounting
CUSTOMER INTERACTION CENTRE (CIC)
Insert meter to panel
Received (Import) Delivered (Export) Received (Import) Delivered (Export) Received (Import) Delivered (Export) 1 TOLL-Free: 1800 233 5858, 1800 200 5858
without clamps
Telephone : 022 6774 5858
2 2
Load Line Load Line Load Line 1 Insert both clamps email: cic@LNTEBG.com
3

+2.0
90 - 0.0

L&T Electrical & Automation


AMF IP AMF IP AMF IP
240V AC 240V AC 240V AC

Electrical Standard Products


L&T Business Park, Tower 'B' / 3rd Floor
54mm
3 Saki Vihar Road, Powai Mumbai 400 072
3 Phase 4 Wire System 3 Phase 3 Wire System Single Phase System 4mm