You are on page 1of 1

Carbon Monoxide (CO) Series

Carbon Monoxide Sensor


Product Description Specification
The CO Sensor Series is the latest Power Supply: 24 VAC +/- 10%, 24 VDC +/-10%,
electrochemical carbon monoxide Modbus: 24 VDC +/-10%.
sensor technology for high accuracy Output Signal: 4-20 mA with loop isolation standard.
of readings in various conditions. The Optional output: Relay form C, 10 A, 277 VAC rating.
Adjustable trip point at 25, 60 and
sensor has an IP65 enclosure for a
150 PPM by selectable jumper with
wide range of applications and a long 3% relay hysteresis.
service life of over 5 years and Consumption: < 50 mA
features a linear analog output of 4-20 Optional: Modbus Communications
mA (0-300 PPM) with relay output or Range: 0-300 PPM
Modbus communication options. Coverage Area: ≈ 7500 ft2 (700 m2) or 49 ft (15 m) radius
Accuracy: +/- 5% of full scale or 5 PPM,
whichever is higher.
Operating Conditions: -4° to 122° F (-20° to 50° C), 15 to 95% RH
Enclosure Rating: IP65
Long Term Stability: < 4.5% signal loss per year
Sensory Type: Electrochemical
Sampling Method: Diffusion
Field Recalibration: By using calibrated gas kit.
Approvals: CE, Sensor is UL listed, File E240671
under ANSI/ UL-2034 and ANSI/ UL2075.
Service Life Duration: > 5 years
Wiring Connections: Screw terminal, 14 to 20AWG.
Dimensions: 3.5 x 4.5 x 2.0 in (90 x 115 x 50 mm)
Weight: 0.6 lbs (0.28 kg)

CO-B-22.04S
Device Dimensions
Ordering Information Space Mount Model

S - SPACE MOUNT
D - DUCT MOUNT

Bluetech Corporation. All Rights Reserved.


4.5”
115 mm

0 - NO RELAY Duct Mount Model


1 - NO/NC RELAY*
0.9”
22 mm

00 - NO COMM
3.5”
90 mm
1.8”
10 - MODBUS COMM* 4.1” 46 mm
105 mm

4.7”
118 mm 2.0” 6.5”

CO - B - x - x - 00
50 mm 165 mm

2.0”
50 mm
* Relay not available with Modbus option

0.9”
22 mm

Installation
Copyright

6850 N. Haggerty Road,


Canton, MI 48187, USA Refer to the installation manual for the complete mounting
E contactus@bluetechcorp.com and termination details.
W www.bluetechcorp.com