Professional Documents
Culture Documents
ROLLAY
An Arc-Resistant LVMCC
This article deals with arc-resistant equipment as it applies to an LVMCC, i.e., NEMA 600V
class LVMCC and IEC 690V LV controlgear. An arc-resistant LVMCC can be thought of as a sub-
set of a standard Underwriters Laboratory (UL) 845 motor control center or IEC 61439 controlgear.
(In 2009, the IEC 60439 series of standards were revised and renumbered as the IEC 61439 series.)
In addition to complying with the requirements of one of these standards, the designation of arc resist-
ant is an indication that the LVMCC has satisfied certain performance criteria when subjected to internal
1077-2618/11/$26.00©2011 IEEE
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.
arcing conditions. An arc-resistant LVMCC may con- Internal Arcing Test Guides
tain additional features that are normally not present There are no standards when it comes to arc-resistant equip-
in a standard LVMCC and may have additional installa- ment but rather internal arcing test guides. The difference
tion requirements. between a standard and guide is that a standard specifies
While UL 845 [1] and IEC 61439 [2] outline a series of mandatory requirements and performance levels that must
required short-circuit type tests to ensure that the LVMCC be met and verified, while a guide provides information,
will be able to withstand the effects of bolted faults, over- including recommended procedures and explanations, while
load currents, etc., neither of these documents requires leaving performance levels subject to an agreement between
testing or specifies a level of performance that the equip- the customer and manufacturer [6]. As a result, arc-resistant
ment must meet when subjected to specific arcing fault ratings can vary by manufacturer, and users should ensure
conditions. An arcing fault differs from a bolted fault in that they understand not only how a specific manufacturer
that the circuit is completed through air (as a result of insu- has tested his/her arc-resistant equipment but also the levels
lation breakdown, ionized gases, etc.) rather than a conduc- (voltage, current, arcing duration, and accessibility type) to
tor. The equations in IEEE 1584, which are based on test which the equipment has been tested.
data, predict that arcing currents in a typical LVMCC can On a global level, there are two documents that are appli-
be as low as 40% of the rms-bolted fault current level [3]. cable to the testing and qualification of the arc-resistant
One of the reasons that arcing faults are typically more LVMCC: IEC/TR 61641 and IEEE C37.20.7. Each test
severe than bolted faults is because the lower arcing current guide outlines the scope of equipment intended to be cov-
may not cause the short-circuit-protective device (SCPD), ered by the particular document. For instance, IEC/TR
located in or upstream of the LVMCC, to trip in a timely 61641 Enclosed Low-Voltage Switchgear and Controlgear Assem-
manner. Clearing time during an arcing event is critical; blies—Guide for Testing Under Conditions of Arcing Due to Inter-
longer fault durations can result in increased equipment nal Fault provides guidance for testing the IEC style
damage and incident energy exposure. Adding provisions LVMCC that is manufactured according to IEC 61439. Both
to the equipment that allow the enclosure to be rated as arc documents are maintained by the IEC SC (subcommittee)
resistant will help limit and contain some of the undesir- 17D—LV Switchgear and Controlgear Assemblies. Cur-
able mechanical and thermal effects that result from an rently, there are no internal arcing test guides that directly
internal arcing fault. include in their scope the NEMA style LVMCC that com-
The arc-resistant LVMCC has been fairly common, plies with UL 845. The most relevant document is IEEE
particularly throughout Europe, for many years. To some C37.20.7 IEEE Guide for Testing Metal-Enclosed Switchgear
extent, this is a result of the fact that low-voltage switch- Rated Up to 38 kV for Internal Arcing Faults. Originally, a
gear and controlgear assemblies must comply with the medium-voltage test guide, the 2007 release of IEEE
same standards and codes. When controlgear is used in a C37.20.7 incorporated some guidance for testing low-volt-
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.
for internal arcing faults; this indicates that during testing actual arc-resistant ratings may not be equivalent since the
doors and covers are secured and latched. guides are not harmonized.
It is important to point out that even on equipment
rated as arc resistant, safe work practices are paramount Selection of Compartments for Testing
and must always be followed. Arc-resistant equipment When qualifying configurable equipment such as an
alone is not enough to satisfy the requirements for safe LVMCC for an arc-resistant rating, a series of internal arc-
work practices outlined in NFPA 70E or CSA Z462. Arc- ing tests may be necessary. Because the nature of an arcing
resistant equipment is not exempt from the arc-flash haz- fault can be unpredictable, it is often difficult to determine
ard analysis described in these documents, and it must the fault location that will lead to a worst-case condition
still be field marked with the available incident energy or without testing. Therefore, a thorough test program is nec-
the required level of personal protective equipment. essary to assess the effects of an internal arcing fault in
When doors and covers are open while the equipment several locations including bus compartments, outgoing
is energized, an arc-resistant LVMCC, like a standard units and feeders, and incoming units (mains).
LVMCC, has the potential to release energy should an 1) Bus compartments: Although energy levels will vary by
arcing fault occur. manufacturers and designs, in the case of an LVMCC,
the highest energy levels generally are expected to
Equipment Testing occur in the bus compartment. This is due to the fact
Arc-resistant equipment provides several benefits within the that there is less impedance at this point in the cir-
previously described framework. The extent of these benefits cuit, and unless the bus is insulated, an arc that devel-
depends on the assessment criteria and the degree to which ops in the bus compartment is not likely to self-
the test guide was followed when testing took place. extinguish. Both the main power and distribution
bus should be considered for testing.
Assessment Criteria and Accessibility Type 2) Outgoing compartments (units and feeders): When an
After an internal arcing test is conducted, equipment is arc fault occurs, high temperatures cause materials to
typically inspected for, at a minimum, the following crite- vaporize, resulting in rapidly expanding gases that
ria [7], [8]: produce a pressure wave. In an LVMCC unit, or
n doors and covers do not open (some distortion bucket, the volume is typically much smaller than
is allowed) the volume of the bus compartment. Smaller volumes
n parts are not ejected (i.e., the enclosure remains leave less space for gases to expand, which could lead
intact and does not fragment) to higher pressures and more stress on the equipment.
n arcing does not cause holes to develop in external Since the effects of an arcing fault are mitigated
parts of the enclosure (i.e., assessment of burn- by distance, barriers and proximity to areas of the
IEEE INDUSTRY APPLICATIONS MAGAZINE JULY j AUG 2011 WWW.IEEE.ORG/IAS
through, a thermal effect) equipment that are accessible by personnel are the
n thermal indicators do not ignite (i.e., any gases factors that need to be considered when developing
released are not hot enough to cause ignition at an arc-resistant test strategy. When units are
a specific distance from the enclosure) and installed in an LVMCC, they are typically located
n the grounding or protective circuit remains effective. toward the front of the enclosure that is usually
The above criteria are primarily focused on the protec- more accessible than the bus compartment.
tion of personnel who are in the vicinity of the LVMCC Conversely, depending on the location in the unit
from the thermal and mechanical effects of an internal arc- where the fault occurs, the arcing current and clearing
ing fault. Some internal arc test guides, including IEC/TR time might be considerably less than a similar fault in
61641, provide additional criteria that can be used to assess a bus compartment, leading to lower energy levels.
the equipment. Optional criteria [8] that can also be used There may be a protective device within the unit
as part of the assessment include the following: upstream of the fault, or the unit may be designed
n the arc is confined to the compartment in which it with careful attention to spacing and insulation that
was initiated (e.g., an arc initiated in a unit does not would make an arcing fault likely to self-extinguish
flash over and ignite in the bus compartment) even before an upstream protective device would open.
n emergency operation of equipment is possible 3) Incoming compartments (mains): The line side of an
(verified by a dielectric test). LVMCC incoming device or main lug compartment
The criteria for personnel and equipment protection has the potential for the highest arc-flash energy,
may apply to one or more external surfaces described by because if a fault were to occur at this location, the
accessibility type. Two accessibility types are defined in upstream device may be slow to operate. The volume
IEEE C37.20.7: Type 1—front only and Type 2—front, of the compartment, spacing and arrangement of con-
sides, and back [7]. (IEEE C37.20.7 also defines suffixes ductors and components, and speed of the upstream
that can be applied, but these are typically used only for clearing device all factor into evaluating this com-
medium- or high-voltage equipment and do not apply to partment for testing.
LVMCCs.) Distinction is not made between different levels
of accessibility types of IEC/TR 61641; the document Test Sample
states that all sides of the equipment readily accessible by The test sample(s) should be constructed so that the worst-
personnel must be evaluated [8]. This is essentially equiva- case scenarios can be evaluated. Since an LVMCC is typi-
lent to IEEE Accessibility Type 2 assessment. Note that cally configurable with an almost infinite combination of
64
although the accessibility-type assessments are similar, the options, bus sizes, and unit layouts, it would not be
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.
realistic to test every possible arrangement. Thus, engi-
neering judgment must be used in establishing a test
program. An example of the worst-case construction
could be a bus compartment with the smallest spacing
between phases or a unit compartment with the highest
rated device packaged in the smallest possible volume.
Devices that allow the largest current let-through (I2 t)
should also be considered. When designing a test sam-
ple, externally mounted options should be taken into
account (e.g., pilot lights and buttons, viewing win-
dows, meters). Enclosure strength is critical, and any
options that may weaken the integrity of the LVMCC
should be evaluated.
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.
instructions) for the device-limited arc-resistant rating to utilize specific protective device(s) may limit the flexibility
remain valid. of the user in selecting a device that will achieve the
Device-limited ratings are a simple method of applying system coordination and performance desired in a spe-
arc-resistant equipment since any application that uses the cific application.
defined protective device(s) will be protected as long as 1) Current-limiting devices: These devices are most fre-
the system voltage and maximum available fault current quently used, and they can be either current-limiting
are not exceeded for which the manufacturer conducted fuses or fast-acting circuit breakers. These devices
the arc-resistant testing. However, the requirement to will limit the peak current and time duration of the
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.
arcing fault. Table 2 lists how some common protec-
TABLE 2. TYPICAL DEVICE PERFORMANCE UNDER
tive devices performed under arcing conditions in a
INTERNAL ARCING CONDITIONS IN AN LVMCC.
typical LVMCC. With either of these protective
devices, the user should consider both the bolted Actual Arcing
fault and reduced arcing fault currents. Both fuses Device Rating (A) Duration (ms)
and circuit breakers can be effectively used when Test per IEC/TR 61641 at 415 V and 65 kA
their current-limiting characteristics are understood.
Typically larger protective devices are not as effec- MCCB 25 1.7
tive at lower arcing currents. 1.7
a) Current-limiting fuses: These fuses are very effec-
tive, particularly at lower currents, but may have 225 3.7
more limitations as fuse ampere ratings increase. 6.2
Typical arcing currents seen in LVMCC applica-
4.2
tions may not put larger current-limiting fuses
(fuses rated above 1,200 A) into the current- 7.2
limiting range. This results in longer clearing 600 7.1
times and reduced protection (Figure 3). How-
ever, current-limiting fuses may offer advantages 10.4
in achieving coordination with downstream pro- Test per IEEE C37.20.7 at 480 V and 65 kA
tective devices.
b) Fast-acting circuit breakers: These breakers that Class L fuse 1,200 9.7
provide current-limiting or current-reduction char- 12.9
acteristics may also be used. Circuit breakers may
provide better protection as part of a device- 8.5
limited rating package than the time–current 9.9
curve of the circuit breaker would indicate. Under
9.6
arcing conditions, current-limiting circuit break-
ers reduce both the fault current and duration [9]. 9.6
Note that circuit breaker (and fuse) curves repre- 10.0
sent the worst-case conditions and what is shown
on the curve is often conservative. 7.6
c) Additional testing for current-limiting devices: Since MCCB 1,200 13.5
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.
Methods to limit the duration of an arcing fault include label must identify the equipment as device limited and
diverting the arcing current to a low-impedance short-circuit list the specific devices that must be utilized. There are no
device (e.g., metallic short circuit or crowbar) or transfer- guidelines or calculations for extrapolating test data for
ring the arc to an isolated arc chamber to reduce arc-inci- longer arcing durations at lower currents or voltages, so the
dent energy exposure. These methods can be quite fast requirements on the rating label should not be exceeded.
(Table 2) but requires the user to consider any stresses that It is possible that different compartments may carry dif-
this may cause to the electrical system. ferent arc-resistant ratings. If this is the case, the rating for
each compartment should be clearly marked.
Duration Ratings
Duration arc-resistant ratings are based on rating the Considerations for Applying Arc-Resistant
equipment to withstand an internal arcing fault for the Equipment to LVMCC Systems
maximum time duration. The maximum system voltage
and maximum available prospective short-circuit current Considerations for Electrical System Design
are also part of the duration rating, similar to a device- Many of the same techniques that help reduce arc-flash
limited rating. energy levels at the LVMCC will also reduce the arc-resistant
This rating method provides the user with more flexi- rating requirements of the LVMCC equipment. Some tech-
bility in selecting a main protective device to achieve niques that will improve performance include the following:
desired system performance and coordination. Nonethe- 1) Reduce the ampacity of the LVMCC bus system: This will
less, the selection of the upstream short-circuit protec- reduce the size of the main SCPD. Smaller devices
tion is still critical. When using this method, an arc- clear faster under the arcing currents that are typical
flash hazard analysis should be performed to determine in LVMCC applications. The typical arcing currents
the potential arcing current levels at the LVMCC. This allow lower rated protective devices (typically devices
information is then used to select an appropriate pro- up to 1,200 A) to operate in their current-limiting
tective device that will clear a potential arcing fault range, leading to faster fault clearing times (Figure 3).
in a time that is less than the rated arcing duration of 2) Select high-performance current-limiting protective devices:
the equipment. The selection of the main SCPD for applications
using arc-resistant LVMCC equipment is an impor-
Identifying Arc-Resistant Equipment tant activity. If a device-limited rating is used, a
(Rating Nameplates) specific main SCPD may be required. Even for arc-
Arc-resistant equipment should be clearly marked with a resistant equipment with a duration rating, it is
nameplate, or rating label, located on the exterior of the advantageous to select a device that will clear any
enclosure, where the level to which the equipment has faults as quickly as possible to limit personnel expo-
IEEE INDUSTRY APPLICATIONS MAGAZINE JULY j AUG 2011 WWW.IEEE.ORG/IAS
been tested is indicated (Figure 4). The internal arcing test sure and equipment damage. Current-limiting pro-
guides indicate that the arc-resistant rating label should tective devices are designed to reduce the amount of
specify attributes such as the maximum prospective short- energy released during a fault. At the same time,
circuit current, maximum nominal operational voltage, these devices can provide other desirable electrical
maximum arcing duration, and accessibility type. If system performance, such as system coordination.
the arc-resistant rating is a device-limited rating, then the Another benefit of using a high-speed current-lim-
iting device is that it will help reduce potential
incident energy levels when an arc-flash hazard
analysis is conducted.
a) Use high-performance current-limiting fuses: Some
Arc-Resistant Equipment
fuses provide more current-limiting performance
Per IEEE C37.20.7
than others. Evaluate both the clearing time and
Accessibility: Type X let-through characteristics when selecting current-
Arc Short-Circuit Current: XX kA limiting fuses.
Arc Duration: XXX ms b) Use high-speed current-limiting or -reduction molded
(a) case circuit breakers: Molded case circuit breakers
may provide better performance in protecting
Arc-Resistant Equipment equipment against internal arcing faults than
Per IEEE C37.20.7 their clearing time curves indicate because of
their current-reduction characteristics. When a
Accessibility: Type X
Arc Short-Circuit Current: XX kA
circuit breaker clears a fault, an arc develops
Arc Duration: Device Limited between its contacts. The impedance of the arc
Protective Device: Manufacturer and Part Number(s) between the contacts reduces the fault current,
Rated Max Clearing Time resulting in lower incident energies [9]. This
Protective Device: XX ms advantage, combined with the fact that the cir-
cuit breaker will often clear faster than the
(b) time–current curve would indicate, can be use-
4 ful when specific breakers are tested in conjunc-
Typical arc-resistant nameplate: (a) duration rating and tion with a device-limited arc-resistant rating.
68
(b) device limited. However, in cases where a duration rating is
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.
used, the circuit breaker must be selected based
on the trip curves that may not show this im- 45
proved performance. 42 kA Available Current
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.
times for upstream devices while still maintaining enough to ensure safety or compliance with NFPA 70E or
selective coordination. Consider an approach such CSA Z462.
as zone-selective interlocking or bus differential Arc-resistant equipment is governed by test guides,
protections. The use of these methods can provide not by standards. For this reason, arc-resistant ratings can
a broad range of selective protection operating in vary by manufacturer. Users should ensure that they
minimum time [10]. understand the level and extent to which the manufac-
turer has tested the equipment. Additionally, users
Considerations for Installing Equipment should be aware of the type of arc-resistant rating the
To meet the criteria established in arc-resistant test guides, equipment carries (device limited or duration rating)
an arc-resistant LVMCC may have some additional fea- and understand any limitations or restrictions that rat-
tures that are not provided in a standard LVMCC. When a ing might include.
device is used to limit the fault (device-limited arc-resist- Careful consideration and planning when designing
ant rating), the arc-resistant LVMCC may be constructed an electrical system will help reduce both incident
very similar to the standard LVMCC equipment. This is energy levels when an arc-flash hazard analysis is con-
because the device will typically limit the peak current ducted and the necessary rating for arc-resistant equip-
and clear the fault in a relatively short time before exces- ment. The balance between arc-flash safety, system
sive pressures and thermal energies build up. Similarly, performance, and coordination may present difficulties,
with short duration arc-resistant ratings, the equipment is but there are many techniques that can be used to help
typically not subjected to extreme thermal stresses. Arc- overcome these challenges.
resistant equipment ratings that do not require a specific While the manufacturer is responsible for the design
protective device may contain additional features such as a and testing of arc-resistant equipment, it is the responsibil-
pressure relief system, additional insulation, thicker or ity of the user to ensure that the equipment is suitable for
reinforced sheet metal, as well as require the use of larger the application, installed as intended, and properly used
enclosures. If additional features or requirements are in- and maintained. Safe work practices (training, equipment,
cluded in an arc-resistant-rated LVMCC, the user must be etc.) must always be observed around arc-resistant equip-
aware of any special installation considerations. For exam- ment, especially when doors and covers are open. This is
ple, if a pressure relief feature is part of the arc-resistant true for any electrical equipment, not just arc-resistant
LVMCC design, it is critical that when the LVMCC is designs. If possible, work on a deenergized system is
installed there is adequate free space around the feature to always preferred.
allow for proper operation without interfering, impeding, The use of arc-resistant equipment is a good way to help
or blocking the operation of the system or the controlled contain the mechanical and thermal effects associated with
release of gases that build up during an arcing fault. The an arc flash as well as limit personnel exposure should an
IEEE INDUSTRY APPLICATIONS MAGAZINE JULY j AUG 2011 WWW.IEEE.ORG/IAS
energy experienced during an arcing fault in low-voltage internal arcing fault occur. In many instances, the use of
equipment is typically lower than that associated with arc-resistant LVMCC equipment could be yet another
medium-voltage equipment. Although medium-voltage aspect of a comprehensive arc-flash safety strategy.
arc-resistant equipment often requires some type of ple-
num, ductwork, or chimney to channel hot gases and/or References
molten metal and particles to a specific location, this addi- [1] The UL Standard for Safety for Motor Control Centers, UL 845 Fifth
Edition, UL 845-2005.
tional feature will not necessarily be a requirement for [2] Low-Voltage Switchgear and Controlgear Assemblies—Part 1: General
LVMCCs (although such a system could be used if a user Rules, IEC 61439-1:2009.
opted to have one installed). [3] IEEE Guide for Performing Arc Flash Hazard Calculations, IEEE 1584-
Once the initial pressure is relieved, as the arc continues 2002.
to burn, the effects on the LVMCC enclosure are mostly [4] NFPA 70E Standard for Electrical Safety in the Workplace 2009 Edition,
NFPA 70E-2009.
thermal. A manufacturer can employ several strategies to [5] Workplace Electrical Safety, CSA Z462-08.
design the equipment to sustain these thermal effects. [6] 2009 IEEE Standards Style Manual, New York, NY, IEEE.
Examples of features or techniques used to mitigate these [7] IEEE Guide for Testing Metal-Enclosed Switchgear Rated Up to 38 kV for
thermal stresses include the use of strategically placed insu- Internal Arcing Faults, IEEE C37.20.7-2007.
[8] Enclosed Low-Voltage Switchgear and Controlgear Assemblies—Guide for
lation or barriers, careful design and placement of compo- Testing Under Conditions or Arcing Due to Internal Fault, IEC/TR
nents with respect to electrical spacing, and the use of 61641:2008.
thicker external sheet metal. It is important that the user [9] G. Gregory and K. J. Lippert, “Applying low-voltage circuit breakers
follows all instructions from the manufacturer to ensure to limit arc flash energy,” IEEE PCIC Conf. Rec., 2006.
that these types of features are correctly installed when the [10] M. Valdes, P. Hamer, T. Papallo, R. Narel, and B. Premerlani, “Zone
based protection for low voltage systems; Zone selective interlocking,
equipment is energized and operational. bus differential and the single processor concept,” IEEE PCIC Conf.
Rec., 2007.
Conclusions
When arc-flash safety is a concern, using equipment that
offers both arc prevention features and arc containment fea- Rachel M. Bugaris (rmbugaris@ra.rockwell.com) and David
tures is a good strategy for developing a comprehensive T. Rollay are with Rockwell Automation in Milwaukee, Wiscon-
solution to dealing with the many dangers associated with sin. Bugaris is a Member of the IEEE. Rollay is a Senior Mem-
arc-flash hazards. Arc-resistant equipment offers enhanced ber of the IEEE. This article first appeared as “Arc-Resistant
protection against the thermal and mechanical effects of an Equipment for Low-Voltage Motor Control Center Applications”
70
internal arcing fault, but an arc-resistant rating alone is not at the 2010 IEEE Pulp and Paper Industry Conference.
Authorized licensed use limited to: Universidad de Concepcion. Downloaded on May 27,2022 at 15:19:10 UTC from IEEE Xplore. Restrictions apply.