2) Moda of operation of regulator
‘The generator voltage is fed to te regulator via plug
‘connector X1 in a singe phase, two-crcuit arrangement.
Transformer T1 steps down the generator voltage wich
's then rectifid by the oad-sie rectifier bridge Vi, va
This rected voltage provides the actual puse signal "Us"
the setpoint voltage Usoll and the supply votage @ for
the reguator
ifthe system uses reactive current compensator,
‘current transformer T15 or interposing transformer T8
‘ofthe excitation units connected to load resistor Rt via
plugin contacts 2/5 and X29
In this operating mode the actual voltage is composed
‘ofthe secondary voltage of transformer T¥ and the
voltage of fae resistor R1
‘The magnitude ofthe resuiting reduction in generator
voltage can be set with potentiometers.
fan external setpoint selector is used, tis is connected
by contacts X2/1 (A) and 2/3 (A.
In this case microswaten $13 of the regulator must be
opened.
ADC voltage of 0 to 10 V can be fed in via plugin
contacts x2/6 and X2/2
Tis voltage acts on the comparator point ofthe control
amplifier.
‘The setpoint can thus, for instance, be preset by higher-
level equipment.
contro amplifier (proportional again adjustable by
potentiometer K and reset time by potentiometer 7)
‘outputs a DC voltage whichis converted into atime
adjustable fring puse for thyristor V18 oF V28 via the
loadside pulse unit
The generator excitation circuit is fed from rectiter
bridge v2,
Resist Red aw Urpin V2B ont @ tae Uys
Circuit to the fell winding through which part ofthe
current supped by the excitation unit lows.
This methad provides for gonerator voltage contro},
In order to optimize the correcting action, aaisturbance
variables injected into the contsol amplifier via resistor
Ra?
COvervotages above OC 600 Vn the excitation circuit
cause the overvoltage protector to operate and
continuously fre the thyristor
Protection Is thus provided forte stationary excitation
Circuit ofthe generator.
2) Installation
‘The excitation equipment, thyristor votage regulator,
main machine, and exciter are factory-wire.
If necessary, the main leads andthe reference-value
selector must be connected to the terminals in the
terminal box according to the connecting ciagram
supped with the machine
25 Operation (6 GA 2491)
1) Thyristor voltage regulator
The voltage regulates the voltage so that it complies
with the setpoint selected
Frequency changes due to the droop characteristics of
the prime mover do not affect the voltage accuracy.
‘The design and adjustment ofthe generator and the
excitation equipment permit continuous changes ofthe
terminal voltage in the range of +5% rate voltage via
the setpoint selector under steady-state conditions and
at loads varying from no load to rated load, and power
factors trom 0.8 to unity unless specied otherwise on
the rating pate
Hf several ated voltages and frequencies are inacated on
the rating pate, the above data apply to each of the rated
voltages stated
If the generators are operated at voltages exceeding
5%, the generator output must be reduced.
Unrestricted operation at no load is permitted ifthe speed
is reduced
During operation, the excitation circuit must not be
Interrupted since this would gverse to voltage surges
Ifthe generator must be de-excted, this can be
‘accomplished by short-circulting the secondary side of
rectiier transformer (16) Fig. 1)
2) Transformer adjustment
“The tappings used on the transformers are shown inthe
test report.
itis strongly advised nat to change the orginal
adjustments.
‘No responsibilty can be assumed by the supplier for any
‘damage or incorrect operation resulting from a change in
‘the orginal agustments.
In the case of identical plants, the THYRIPART excitation
‘system or the individual components ca be interchanged
ifmecessary,
The transformer tappings, however, must be used in
accordance withthe original ones,