You are on page 1of 2

Cable Catalog

N2XSY POWER CABLE SINGLE CORE, 18 / 30 kV

1. APPLICATION:
Power Distribution in Medium Voltage. As transformer feeders in substations. In Power Plants,
Industrial and Operation Installations, In Residential Areas and Mining Installations, In Dry Or
Wet Locations.

2. CONSTRUCTION:
1) Conductor: Compact stranded copper conductor, Cl.2 as per IEC 60228
2) Conductor Screen: Extruded semi-conductor
3) Insulation: XLPE(cross-linked polyethylene) rated at 90 ℃
4) Insulation Screen: Extruded semi-conductor
5) Metal Screen: Copper tape screen
6) Sheath: PVC

3. VOLTAGE:
Uo / U (Um) = 18/30 (36) kV

4. OPERATING TEMPERATURE
Maximum Conductor Temperature: under normal (90℃), emergency (130℃) or short circuit
no more than 5 s (250℃) conditions.
Min. Ambient Temp. 0℃, after installation and only when cable is in a fixed position

5. INSTALLATION
1). The installation temperature should not over 20℃, If the ambient temperature is lower than
0℃, the cable should be preheated.
2). The bending radius of cable should not less than 8 times.

6. STANDARD:
IEC 60502-2, IEC 60228

7. COLOR:
Insulation Color:: Natural
Outer sheath color: Red
Cable Catalog

N2XSY POWER CABLE SINGLE CORE, 18 / 30 kV

N2XSY POWER CABLE SINGLE CORE, 18/30kV


Approx. Apprx. Max. Conductor
Section Number of Conductor Insulation Outer Sheath Current Capacity
outer Conductor DC Resistance at
Area threads Diameter thickness thickness at 20℃
diameter weight 20℃

mm2 pcs mm mm mm mm kg/km Ω/km A

1x50 19 8.3 8.0 1.9 32.16 1,350 0.387 203

1x70 19 10 8.0 2 34.06 1,618 0.268 246

1x95 19 11.6 8.0 2.1 35.86 1,928 0.193 293

1x120 37 13 8.0 2.1 37.26 2,214 0.153 332

1x150 37 14.6 8.0 2.1 38.86 2,555 0.124 366

1x185 37 16.2 8.0 2.2 40.66 2,958 0.0991 410

1x240 37 18.6 8.0 2.3 43.26 3,580 0.0754 470

1x300 37 20.6 8.0 2.3 45.26 4,211 0.0601 524

1x400 61 23.8 8.0 2.5 48.86 5,300 0.047 572

1x500 61 26.6 8.0 2.5 52.54 6,367 0.0366 651

1x630 61 30.24 8.0 2.7 56.58 7,751 0.0283 695