Professional Documents
Culture Documents
Pierce Ultimate
Configuration (PUC)
Pumpers
SECTION 3. GENERAL
3-1 DESCRIPTION OF PIERCE ULTIMATE CONFIGURATION (PUC) PUMP ................................................................ 3-1
3-2 GENERAL OPERATION .................................................................................................................................. 3-1
3-2.1 DEFINITIONS ...................................................................................................................................... 3-1
3-2.2 OPERATING THE ENGINE ................................................................................................................... 3-2
3-2.3 COOLING THE ENGINE ....................................................................................................................... 3-2
3-2.4 SUCTION STRAINERS ......................................................................................................................... 3-2
3-2.5 SUCTION LINE ................................................................................................................................... 3-2
3-2.6 TESTING FOR AIR LEAKS ................................................................................................................... 3-3
3-2.7 SOURCE OF WATER SUPPLY ............................................................................................................. 3-4
3-2.8 PUMPING IN COLD WEATHER ............................................................................................................. 3-4
3-2.9 WHEN FINISHED PUMPING ................................................................................................................. 3-4
3-2.10 PUMPING SALT WATER ...................................................................................................................... 3-4
3-3 TESTING OF EQUIPMENT FOR PRACTICE ....................................................................................................... 3-4
3-3.1 MEASURING PUMP PERFORMANCE ..................................................................................................... 3-5
3-3.2 ACCEPTANCE TESTS .......................................................................................................................... 3-5
3-3.3 ENGINES ........................................................................................................................................... 3-5
3-4 EFFECTS OF ATMOSPHERIC CONDITIONS ON ENGINE AND PUMP PERFORMANCE .......................................... 3-6
3-5 OPERATING CHARACTERISTICS OF PUMPS .................................................................................................... 3-6
SECTION 4. OPERATION
4-1 APPROACHING THE APPARATUS .................................................................................................................... 4-1
4-1.1 STEPPING AND WALKING SURFACES ................................................................................................... 4-1
4-1.2 COMPARTMENT DOORS ...................................................................................................................... 4-2
4-1.3 HOSE BED COVERS ........................................................................................................................... 4-2
4-1.4 FOLDING STEPS OR PLATFORMS ........................................................................................................ 4-2
4-2 HOSE ........................................................................................................................................................... 4-3
4-2.1 HOSE STORAGE ................................................................................................................................. 4-3
4-2.2 HOSE RESTRAINT .............................................................................................................................. 4-3
4-2.3 HOSE CHUTES ................................................................................................................................... 4-3
4-2.4 HOSE BEDS ....................................................................................................................................... 4-4
4-2.5 HOSE DEPLOYMENT ........................................................................................................................... 4-4
4-2.6 HOSE CONNECTIONS ......................................................................................................................... 4-5
4-3 POSITIONING THE APPARATUS ...................................................................................................................... 4-6
4-3.1 FIRE SCENE POSITIONING .................................................................................................................. 4-6
4-3.2 POSITIONING ON ROADS .................................................................................................................... 4-6
4-3.3 LIGHTING ........................................................................................................................................... 4-6
4-3.4 CHOCK THE WHEELS ......................................................................................................................... 4-6
4-4 OPERATION OF PUC FIRE PUMP ................................................................................................................... 4-7
4-4.1 OPERATION OF PUMP ......................................................................................................................... 4-7
4-4.2 TO ENGAGE THE PUMP—STATIONARY OPERATION ............................................................................ 4-7
4-4.3 ENGAGING PUMP WHEN VEHICLE IS DRIVING – BASIC PACKAGE (STANDARD) ...................................... 4-8
4-4.4 ENGAGING PUMP WHEN VEHICLE IS DRIVING – ADVANCED PACKAGE (OPTIONAL) ................................ 4-9
4-4.5 SUPPLY WATER TO PUMP ................................................................................................................ 4-10
4-5 MANUAL PUMP ENGAGEMENT ..................................................................................................................... 4-13
4-6 ADJUSTING THE PUMP PRESSURE ............................................................................................................... 4-13
4-6.1 DETERMINE DISCHARGE PRESSURE ................................................................................................. 4-13
4-6.2 ENGINE SPEED AND PUMP PRESSURE .............................................................................................. 4-14
4-6.3 CONTROLLING ENGINE SPEED, PUMPING—PRESSURE GOVERNOR OPERATION ................................. 4-14
4-6.4 CONTROLLING ENGINE SPEED, NOT PUMPING—PRESSURE GOVERNOR OPERATION .......................... 4-14
4-6.5 CONTROLLING ENGINE SPEED WITH MULTIPLE CONTROLS ................................................................ 4-15
4-7 DISCHARGING WATER ................................................................................................................................. 4-15
4-7.1 CONNECTING ATTACK LINE HOSE ..................................................................................................... 4-15
4-7.2 CHARGING LINE ............................................................................................................................... 4-17
4-8 DISCHARGING FOAM ................................................................................................................................... 4-18
4-9 CHANGING FROM TANK TO EXTERNAL PRESSURIZED WATER SUPPLY (WITH GATED INTAKE VALVE) ............ 4-18
4-9.1 CONNECT INTAKE HOSE ................................................................................................................... 4-19
4-9.2 CHARGE THE INTAKE LINE (PRESSURIZED SUPPLY) ........................................................................... 4-20
4-9.3 SUPPLY THE PUMP .......................................................................................................................... 4-21
SECTION 5. MAINTENANCE
5-1 INSPECTION, CLEANING, AND MAINTENANCE ................................................................................................ 5-1
5-1.1 MAINTENANCE SCHEDULE ................................................................................................................. 5-1
5-2 DRAINING THE PUMPING SYSTEM ................................................................................................................. 5-1
5-3 FLUSHING THE DRAIN VALVES ..................................................................................................................... 5-2
5-3.1 FORWARD FLUSHING ......................................................................................................................... 5-2
5-3.2 BACK FLUSHING ................................................................................................................................ 5-3
5-4 FLUSHING AND DRAINING THE PUMP ............................................................................................................ 5-4
5-5 PUMP STORAGE .......................................................................................................................................... 5-4
5-6 PREVENTIVE MAINTENANCE CHECKS & SERVICES ........................................................................................ 5-4
5-7 PRIMER PUMP LUBRICATION ........................................................................................................................ 5-5
5-8 INTAKE & DISCHARGE RELIEF VALVE DRAINS (OPTIONAL) ........................................................................... 5-6
5-9 MASTER GAUGE PORTS ............................................................................................................................... 5-6
5-10 PUMP TRANSMISSION LUBRICATION ............................................................................................................. 5-7
5-11 ANODE RODS (OPTIONAL) ......................................................................................................................... 5-11
5-12 MECHANICAL SHAFT SEAL ......................................................................................................................... 5-12
5-12.1 MECHANICAL SEAL BASICS .............................................................................................................. 5-12
5-12.2 MECHANICAL SEAL OPERATION AND MAINTENANCE ......................................................................... 5-12
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / iii
TABLE OF CONTENTS
This manual explains the operation of a Pierce® fire apparatus equipped with a Pierce Ultimate Configuration (PUC)
water pump. The manual reviews basic principles of operation, highlights common safety concerns and procedures,
and gives recommendations for using the pump.
This manual assumes that you are a pump operator and that:
• You have already been fully trained and certified to operate a pump.
• You have had formal education from a technical college or other fire fighter training institution.
• You understand, are proficient in, and meet all of the requirements set forth in NFPA 1002 Standard on Fire
Apparatus Driver/Operator Professional Qualifications (latest edition).
• You already understand water pump operation.
All Pierce vehicles are delivered with a set of manuals for major components that your fire department selected.
If you need replacement manuals, or safety warning labels, contact Pierce customer service at 888-Y-PIERCE (888-
974-3723).
BEFORE operating the pumping system, you, the operator, must read, understand, and follow the instructions found
in:
• Pump manufacturer's operator and maintenance manuals.
• Operator and maintenance manuals for pumping components, such as valves, pressure controllers, flow
controls, manual overrides, foam systems, and primer pumps.
• IFSTA Pumping Apparatus Driver/Operator Handbook (latest edition).
Pump control systems require you to understand the function of each valve, each switch, each gauge, each
Emergency Stop, and each manual override.
Before your fire department allows you to operate this pump, you already must be educated, trained, and have
passed a test for pump logic and operations.
You also must know the principles of operation, so you can change operation when circumstances change.
Each valve, switch, or gauge has an important function. If you are uncertain about the function or don't know
something, inform your fire department's training officer.
You are always welcome to call Pierce Customer Service at 888-Y-PIERCE (888-974-3723) with questions.
You are the only person who knows what you don't know. You must speak up about the things you don't know, so
you can learn about them before someone is injured or killed because of your lack of knowledge.
You are responsible for learning how to operate the pumper under all conditions without having to read this manual
at a fire or other emergency.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 1-1
TO THE OWNER
DANGER signals an imminently hazardous situation that, if not avoided, will result in death or serious
injury.
WARNING signals a potentially hazardous situation that, if not avoided, could result in death or serious
injury.
CAUTION with the safety triangle signals a potentially hazardous situation that, if not avoided, might
result in minor or moderate injury.
CAUTION used without the safety triangle symbol signals a potentially hazardous situation that, if not
avoided, might result in property damage.
1-2 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
TO THE OWNER
1-4. Safety
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 1-3
TO THE OWNER
Your PUC pump is equipped with a powershift PTO. During extreme cold weather operation [32° F (0° C) and lower],
a disengaged Powershift Power Take-Off (PTO) can momentarily transmit high torque that will cause unexpected
output shaft rotation. This is caused by the high viscosity of the transmission oil when it is extremely cold. As slippage
occurs between the PTO clutch plates, the oil will rapidly heat up and the viscous drag will quickly decrease.
The PTO output shaft rotation could cause unexpected movement of the driven equipment resulting in serious
personal injury, death, or equipment damage.
Allow engine and transmission to warm up before engaging pump.
• Rotating auxiliary driveshafts are dangerous. They can snag clothes, skin, hair, hands, etc. This
can cause serious injury or death.
• Do not go under the vehicle when the engine is running.
• Do not work on or near an exposed shaft when the engine is running.
• Shut off the engine before working on the Power Take-Off (PTO) or driven equipment.
• Rotating parts will injure or kill.
1-5. Responsibility
Study carefully this manual and the manuals for major components such as pump, engine, and other allied
equipment. Make sure that all operators and other users also completely understand their contents.
The warnings, cautions, and procedures listed in these manuals must be part of the fire department's safety
program.
As the operator of this vehicle and pumping equipment, you are responsible for:
• Understanding the function of each component of the pumping system.
• Understanding how to adjust each control to obtain the results you want.
• Maintaining control of the pumping system at all times.
1-4 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
TO THE OWNER
• Remaining proficient in use, so at a fire you can operate and make successful changes in the operation quickly,
without having to read the operator's instructions or safety warning labels.
• Practicing proper manual override and emergency shutdown procedures, so you can respond immediately in
an emergency or during the failure of a component. Remember stress is high. Your failure to practice increases
the odds you will forget or do it wrong in the heat of the moment.
Your department developed specifications for this fire apparatus. It purchased a Pierce apparatus that is built to meet
those specifications. The information in this manual will be generic at times.
Due to the highly customized nature of each Pierce fire apparatus, the exact location of each component in the
pumper system will vary.
This manual describes basic controls. Not every apparatus will have all controls. Some will have extra controls, as
determined by each fire department's specification.
Pictures describe typical components or devices. Actual parts might vary from those pictured.
You must learn the location and function of all controls, switches, gauges, valves, inlets, and discharges.
Major inconsistencies between your vehicle and the information contained in this manual should be directed to your
Pierce Dealer or Sales Representative.
To keep up-to-date on knowledge and new standards that affect all facets of fire fighting, make sure that you check
these organizations' catalogues and websites each month:
National Fire Protection Association (for standards and requirements)
One Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9101
617-770-3000
www.nfpa.org
Make sure you read the latest editions.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 1-5
TO THE OWNER
If you believe your vehicle or any associated component might have a design defect that could result in failure or
injury, please report this information immediately to Pierce Manufacturing.
Additionally, should any information in this manual prove to be seriously inconsistent with your Pierce fire apparatus
also inform Pierce Customer Service.
Most service and support issues should be handled by the local Pierce dealer or sales representative. However, to
report any design defects or request support directly from Pierce contact:
Customer Service
Pierce Manufacturing, Inc.
2600 American Drive, P.O. Box 2017
Appleton, WI, 54913
888-Y-PIERCE (888-974-3723)
www.piercemfg.com
This manual will be revised from time to time. Check the Pierce website, www.piercemfg.com, to stay current.
Also review the latest edition of the IFSTA (www.ifsta.org) manual Pumping Apparatus Driver/Operator Handbook.
Remember, if there's anything you don't understand, call Pierce Customer Service at 888-Y-PIERCE (888-974-
3723).
1-6 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
SECTION 2 BEFORE PLACING IN SERVICE
Use a Pump Chart to determine the pump discharge pressure that will provide desired nozzle pressure for various
hose lay configurations and combinations.
The IFSTA Pumping Apparatus Driver/Operator Handbook tells how to develop a pump chart. Develop the chart for
all situations.
Make sure this chart is always available during pump operation.
POM0016
All pumps have a relief valve on the intake side (Figure 2-1). It prevents a pressure spike in intake water from
passing to hoses through the discharge side of the pump.
The intake relief valve is a pressure regulator. If intake pressure goes over the pressure setting, the valve opens and
allows water to flow out the relief outlet.
Some departments choose to connect a hose to the relief valve outlet to direct the water discharge away from the
apparatus. Pressure surges in this hose can occur without warning.
To adjust this valve for desired pressure, the intake pressure to the pump must be higher than the normal static
pressure of the municipal water supply. The best method to adjust the valve is to use another pumper to supply water
at the desired pressure.
1. Increase inlet pressure until the master inlet pressure gauge reads the relief pressure you want.
2. With a wrench, slowly open the adjusting screw on the valve until water starts to flow from the valve outlet.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 2-1
BEFORE PLACING IN SERVICE
3. Slowly close the adjusting screw until the water stops flowing.
Read the valve manufacturer's documentation for complete instructions.
2-2 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
SECTION 3 GENERAL
The PUC pump is a high speed, single stage, UL rated, centrifugal Fire Fighting Pump.
Inherent characteristics of the PUC are compactness, lightweight, high efficiency, and a wide range of pumping
capabilities.
The PUC pump is midship mounted rearward of the chassis engine and powered via the Rear Engine Power Take-
Off (REPTO).
3-2.1 Definitions
HEAD OF WATER: vertical depth of water measured in feet or in pressure per unit or area. In hydraulics, head
always represents pressure and it is expressed interchangeably in feet of water or pounds per square inch and
sometimes in inches of depth of mercury.
STATIC HEAD: the pressure that is exerted by a stationary column of water of a given height or depth.
TOTAL HEAD OR TOTAL DYNAMIC HEAD: the maximum height above the source of supply to which the pump
would elevate the water plus all the resistance to flow in the pipe or hose line.
DISCHARGE HEAD: the pressure measured at the discharge outlet of a pump.
SUCTION HEAD: the positive pressure measured at the suction entrance of a pump (when pumping from an
elevated tank or hydrant).
VELOCITY HEAD: the equivalent pressure represented by fluid in motion as measured by means of a Pitot gauge.
STATIC LIFT: the vertical height of the center of the pump above the source of supply (when pump from draft).
TOTAL SUCTION LIFT: the static lift plus the friction in suction line plus entrance losses.
NET PUMP PRESSURE: the total dynamic head of the pump.
EFFECTIVE NOZZLE PRESSURE: the pump discharge pressure minus hose friction plus or minus the difference
in elevation above or below pump.
WATER HORSEPOWER: the theoretical power required to deliver a given quantity of water per minute against a
given head.
BRAKE HORSEPOWER: Actual power as delivered by a motor or engine to a driven machine.
PUMP EFFICIENCY: The quotient of the water horsepower divided by brake horsepower required to produce it.
WATER HAMMER: a series of shock waves produced in a pipeline or pump by a sudden change in water velocity.
A sudden change in flow velocity can result from rapid closure of valves. A pressure wave is set up which travels
back and forth in the water column at extremely high speed producing rapid vibrations that may be violent and
destructive if the water column is long.
The MAXIMUM THEORETICAL LIFT of a pump is 34 feet, which is the pressure of the atmosphere at sea level.
The maximum practical total lift at sea level is 20 to 25 feet (depending on the type and condition of the pump) and
this decreases with drops in barometric pressure.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 3-1
GENERAL
3-2 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
GENERAL
3. SUCTION LINE ENTRANCE TOO CLOSE TO BOTTOM: If the end of suction line is laid on the bottom of the
source of supply, a part of the suction opening will be shut off; and if the bottom is soft the hose will suck itself
down into the earth, closing more of the opening and loosening sand and mud to be carried into the pump.
The suction entrance should be suspended a foot or more above the bottom, or if this is not possible, it should
be laid on a board or piece of sheet metal. A rope tied to the suction strainer is a convenient means of holding
it off the bottom.
4. OBSTRUCTION OF SUCTION STRAINER BY FOREIGN MATTER: The high velocity of water entering the
suction line will carry loose foreign bodies in against the strainer from a considerable distance. Therefore, all
weeds and refuse should be removed from close proximity of the suction entrance.
5. SUCTION LINE TOO SMALL OR TOO LONG: The flow of water into the pump is opposed by the frictional
resistance in the suction line. This friction loss must be added to the height of the pump above the water (static
lift) to determine the “total lift” of the pump. When all of the vacuum in the pump (atmospheric pressure) is
consumed in raising water through this total life, then the limit of capacity has been reached. This capacity can
be increased only by decreasing total lift. If the static lift cannot be reduced, then the friction loss must be
reduced by using a shorter or larger suction hose.
The rated capacity of the pump is guaranteed for a static lift of 10 feet, with 20 feet of recommended suction
hose at sea level. To increase the capacity without reducing the static lift, or to increase lift without sacrificing
capacity, requires larger suction hose.
An excessively long suction line is a handicap to any pump, for besides reducing capacity through the added
friction loss, it retards priming and it produces a detrimental effect known as “cavitation”. This means a
separation of the water column in the pump suction, or void spaces, produced by the inertia of the heavy mass
of water in the line resisting sudden change in the velocity when the pump starts to deliver or when discharge
valves are opened or closed. This phenomenon reduces capacity further, and usually sets up a vibratory motion
and “water hammer” as the water surges in and out of the void spaces.
When operating with a long suction line, the driving engine should be accelerated gradually, the discharge gates
opened gradually, and the capacities of the pump should be held down to within the range of smooth
performance.
6. AIR TRAP IN SUCTION LINE: If the suction line is laid so that part of it is higher than any other part that is
nearer to the pump, as when hose is laid over a high bridge rail, an air trap is formed at the highest part of the
hose from which the air cannot be sucked out by the primer. This trapped air is expanded and carried into the
pump with the first rush of water causing the pump to immediately lose its prime.
If suction line cannot be laid so that it slopes all the way from pump to water, it can still be primed easily by simply
allowing the primer to continue to function until all the trapped air in the hose has been carried into the pump
and picked up by the primer.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 3-3
GENERAL
It frequently happens that operators of fire apparatus, who are not thoroughly familiar with its operations, become
confused under the stress of emergency and neglect some little detail that may cause trouble or delay in getting the
equipment into operation. Therefore, we urge that practice tests be conducted repeatedly until operators are
thoroughly trained. More than one person in the department should be a competent operator.
Practice should include pumping from low lifts, high lifts with short and long suction lines, with suction line elevated
to form an air trap, and from hydrants, at large and small capacities.
It is well, also, to note the effects of air leaks in hose, insufficient submergence and restriction of suction line. (Suction
line can be restricted by placing a can or other strong closure around the suction strainer).
3-4 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
GENERAL
Do not allow personnel to hold a large nozzle while working at high pressures for serious accidents
may result if hose breaks loose.
NEVER BREAK OR RESTRICT SUCTION OR ALLOW AIR TO ENTER SUCTION LINE WHILE ENGINE IS
OPERATING WITH THROTTLE OPEN. This will release the load and allow engine to run away.
3-3.3 Engines
An Underwriter fire pump imposes heavy loads on the engine that drives it, often absorbing all of the power the
engine is capable of delivering at full throttle. Continuous pumping gives the engine no time to rest. Therefore, a new
engine and pump unit must be thoroughly broken-in before it is required to deliver prolonged maximum pump
performance.
We recommend a minimum break in period of 20 hours at light pumping loads, with occasional spurt tests and
interruptions. Temperature and lubrication should be checked during this period.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 3-5
GENERAL
Engine manufacturers’ power ratings usually show maximum performance of a selected, factory adjusted engine,
operating without fan, generator, muffler or other accessories, and corrected for “ideal” conditions, i.e. sea level
barometer (29.92” of mercury) 60° F and high humidity. Therefore, the actual power delivered by an average truck
mounted engine is considerably lower than the manufacturers’ rating, and allowances must be made in predicting
pump performance.
Each one inch of drop in Barometric pressure or each 1000 feet of elevation of the pumping site reduces engine
power approximately 3 1/2% for engines not equipped with a turbo charger.
Each 12° rise in temperature above 60° F of carburetor intake air reduces engine power approximately 1%.
Lowering of humidity reduces power slightly.
Each one inch drop in Barometric pressure or each 1000 feet of elevation reduces the maximum possible static lift
of a pump approximately one foot.
Temperature of the water supply affects the attainable suction lift of a pump. The effect is slight at low water
temperatures but becomes increasingly detrimental as the temperature rises.
A 10° rise from 70° F will subtract about 1/2 foot from the maximum attainable suction lift, while an equal rise from
100° F will reduce the lift at least 1 1/2 feet.
Temperature is an important consideration when pumping from a test pit where the water is heated by recirculation.
CENTRIFUGAL PUMPS: A centrifugal pump develops pressure by centrifugal force of the liquid rotating in the
impeller wheel. The pressure developed depends upon the peripheral speed of the impeller (increasing as the
square of the speed) and it remains fairly constant over a wide range of capacities up to the maximum output of the
pump, if speed remains constant.
If the discharge outlet of a centrifugal pump is entirely shut off, with speed kept constant, there is a small rise in
pressure, the water churns in the pump casing and the power drops to a low value. If the discharge is opened wide,
with little resistance to flow the pressure drops while the capacity and power both increase to their maximum.
A centrifugal pump is an extremely simple mechanism mechanically, but rather complex hydraulically; in that many
factors enter into the design of the impeller and water ways which will affect the pump’s efficiency.
DISPLACEMENT PUMPS: Rotary and piston pumps are termed “Positive Displacement” pumps because each
revolution displaces or discharge (theoretically) an exact amount of liquid, regardless of the resistance. The capacity
is, therefore, proportional to the number of revolutions of the pump per minute and independent of the discharge
pressure except as it is reduced by “slip” (leakage past the pistons or rotors). For a given speed the power is directly
proportional to the head. If the discharge is completely shut off, the pressure, power, and torque climb indefinitely
until the drive power is stalled or breakage occurs.
Slip is the greatest factor affecting efficiency of a displacement pump, and this factor is greatly influenced by the
condition of and wear on the working parts.
3-6 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
SECTION 4 OPERATION
ALWAYS be careful when climbing up or down to avoid a slip and fall, and potential injury to yourself
and others.
Enter and exit cabs slowly, deliberately, and carefully.
NEVER jump to ground. You can injure yourself.
Keep steps and hand-holds in good repair, and free of grease, mud, dirt, fuel, ice, and snow.
Make sure all attaching bolts and hardware are tight, thus eliminating any movement of steps and hand-
holds.
NEVER step or climb on any vehicle surface unless it is slip-resistant and hand-holds are provided.
Replace slip-resistant material when worn.
All surfaces intended for stepping or walking are designed or treated with slip-resistant material your department
specified. NEVER step or walk on surfaces not designed for stepping or walking, such as:
• Chromed surfaces or objects
• Painted surfaces
• Hose rollers
• Compartment doors or hatches
• Valves
• Controls
• Inlet or Outlet Connections
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-1
OPERATION
Always close swing-up or swing-out compartment doors. People can walk into doors left open at lower levels.
Personnel working on top of the apparatus can mistake an open horizontal door for a walking surface.
Some apparatus are equipped with aluminum hose bed covers. Always close after use. They protect hose from sun
and weather. Hose bed covers are heavy. They might require two or more people to open or close safely.
Before beginning pump operations, make sure that folding steps or platforms are DOWN and firmly engaged in their
weight-bearing position.
When operating the pump on an aerial apparatus, always stand with both feet on the operator's platform and off the
ground.
Your body will become an electrical path to ground if you stand with one foot on the platform and one on the ground,
or with both feet on the ground and your hands on the apparatus. If the aerial device contacts or comes close to high
voltage power lines, electricity can shoot through you. You can die.
4-2 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
4-2. Hose
Entanglement Hazard
Secure hose and other equipment before placing vehicle in motion.
Loose hose may drag behind vehicle and injure or kill.
Hose restraints (nets, doors, webbing, ropes, etc.) must be used to secure the hoses after repacking.
Failure to comply may result in hoses deploying while the vehicle is in motion, causing injury to
bystanders and/or damage to equipment.
This vehicle may be provided with a means to store water hose. Anytime hose is stored on this vehicle it must be
restrained to ensure that it does not fall out of its storage area while the vehicle is in motion. NFPA standards state
that “any hose storage area shall be equipped with a positive means to prevent unintentional deployment of the hose
from the top, sides, front, and rear of the hose storage area while the apparatus is underway in normal operations.”
Fire departments and manufacturers have developed various methods of preventing inadvertent deployment,
including fully enclosed hose bed covers, buckled straps, hook-and-loop straps, fabric covers, webbing mesh, wind
deflectors, and other material restraints or combination of restraints.
Operational methods vary between fire departments, and methods of restraining the hose may vary as a result.
Whether you use the hose restrain feature provided with your apparatus, or develop your own means, it is your
responsibility to ensure that whatever method you employ will adequately restrain the hose in those working
environment the apparatus will be exposed to. Always restrain the hose properly before placing the vehicle in
motion.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-3
OPERATION
Pack hose carefully in any hose bed to minimize the risk of hose snags or snarls as it lays out.
Hose that snags or snarls during layout from a moving vehicle can fly about, causing serious injury or
death to bystanders.
Hose beds come in many shapes and sizes. Hose characteristics vary with the size, type, and age of the hose.
Experiment with different methods of packing a specific hose, bed, and chute combination to determine a packing
method that will lay out without snagging or snarling. Make sure you learn the maximum MPH at which hose can be
laid out.
If hose is to be laid from a moving apparatus, first test the packing method under controlled conditions to learn the
MPH at which hose will lay out smoothly, without snags or snarls.
Any operation where people are working around a moving vehicle is dangerous. All occupants must be seated and
belted while the vehicle is in motion. NEVER ride on rear steps or other areas outside the cab.
4-4 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
When laying hose, an anchorman must protect himself from the dangers of flying hose.
It is safest to use rope to tie the hose to the hydrant. In the absence of rope, anchor the hose by wrapping the end
half way around the hydrant in a J-pattern only. Never wrap more than half way around the hydrant. Wedge the end
fitting against the hydrant with a booted foot. Stand clear of the hose so that you will be away from the hose if it
becomes taut and swings out from the hydrant. A snag in the hose bed can pull the hose loose. The metal fitting can
swing around and break your leg.
Keep people clear of the hose being laid before driving the vehicle.
When laying hose, limit vehicle speed to 5 MPH to minimize risk to personnel, equipment, and bystanders.
Avoid kinks, crimps, and twists when laying fire hose.
Hose fittings are critical to safe delivery of water to a fire. Treat hose connections with care and inspect regularly.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-5
OPERATION
Operate apparatus away from burning embers that can be sucked into the air intake system.
Burning embers in the engine air filter can cause engine fire.
Engine fire can cause property damage, serious injury, or death.
Heat from a fire can damage electrical systems, rubber seals and gaskets, and plastic components. Always place
apparatus upwind from the fire and at a safe distance away from flames.
Diesel engines consume as much as 1200 cubic feet of clean air every minute. Hot embers sucked into the air intake
can cause the air cleaner element to ignite. Although Pierce Custom Chassis are equipped with ember barriers
composed of mesh screens or perforated metal, they are not a foolproof guarantee of protection.
Always leave a way out. Always position the apparatus in a location that allows a quick retreat if conditions change.
Always park upwind of the fire. Never park the apparatus downwind of the fire.
Always avoid electrical lines. Never park under electrical lines.
4-3.3 Lighting
As soon as possible, provide good lighting for people working on and around the apparatus. Use extendable lighting
or lighting from another apparatus.
Make sure that the pump operator can clearly observe controls, gauges, and hose connections, and can watch the
condition of hoses and attack personnel to the greatest extent possible.
4-6 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
Never run the pump dry except momentarily and at low speeds.
Do not use this pump for hose testing.
A Rear Engine Power Take-off (REPTO) transmits power to the pump transmission input shaft whenever the chassis
engine is operating. The fire pump impeller is engaged or disengaged through a high capacity, multi-plate, electric
clutch. This configuration enables the pump transmission to power an auxiliary pump transmission mounted Power
Take-off (PTO) independent of pump impeller engagement.
NOTE: If the parking brake is released during pump operation, the hand throttle or pressure governor is
disconnected AND the engine speed falls to IDLE. Water pressure to the hose will drop. The pump
speed will then be controlled only by the driver's throttle pedal. That is the manual override.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-7
OPERATION
1. Stop Vehicle
2. Pull Parking Brake
Auto Neutral feature automatically engages transmission to NEUTRAL.
3. Engage the Pump
Figure 4-1: Water Pump & Foam System Control Switches (Basic Package)
1135
Confirm engine is at idle rpm. Activate the desired water pump or foam system control switch located on the
driver's panel in the cab. Switches are multi-function; see See Table 4-1.
4-8 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
Table 4-1: Water Pump & Foam System Control Switches - Modes of Operation
*Optional
4. Observe Indicator Light
The PUMP ENGAGED indicator lights only when PTO has been engaged and the pump is spinning.
5. Provide Water Supply to Pump
Operator must leave the cab and set up Pump at Pump Panel:
— Open the Tank-to-Pump valve to provide water to the pump.
— Open the Recirculating Valve (if applicable), or crack open the tank fill valve, to allow water to circulate.
6. Shift Transmission into 1st Gear
For pump-and-roll operation the transmission must be in the 1st Gear (1) position.
7. Release Parking Brake
8. Look at Indicator Light
The OK TO PUMP AND ROLL light turns ON when:
— Parking Brake is released.
9. Use foot throttle and brake pedal as needed
Pump will maintain Pump and Roll mode unless transmission shifts out of 1st gear, OR WATER PUMP control
switch is turned OFF.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-9
OPERATION
1136
4-10 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
The Tank-to-Pump valve (Figure 4-2) controls the flow between the water tank and pump inlet. With this valve
OPEN, water from the tank floods the pump intake manifold and slowly primes the pump.
2. Open Primer Valve
If the pump is dry, engage primer to expel air in the pump to get prime.
1137
The Tank Fill valve (Figure 4-3) opens the connection from the discharge side of the pump to the water tank.
Open Tank Fill Valve to refill the water tank from a water source that is connected to an intake fitting.
With the Tank-to-Pump valve and the Tank Fill valve both OPEN, water recirculates from the tank, through the
pump, and back to the tank. This cools the pump before you begin flowing water to a discharge line.
ALWAYS crack open the Tank Fill Valve when running the pump. If you fail to continuously circulate water
through the pump chamber, the water trapped in the pump chamber heats to boiling in seconds. Boiling water
and steam can injure people. It also damages pump seals and gaskets.
When recirculating water, the water in the tank will eventually become too hot to cool the pump. Exchange tank
water with fresh water to keep pump cooled.
Keep track of water temperature:
a. Touch the outlet pipe to see how warm it is. If it is hot to the touch, it is time to bring fresh, cool water into
the water tank or turn OFF pump.
b. Watch tank temperature gauge (if your fire department selected this option). When temperature reaches
175° F, then add fresh cool water or turn OFF pump.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-11
OPERATION
1155
A dedicated Recirculating Valve (Figure 4-4) opens a small water flow from the pump to the tank. The flow
through this line cools the pump. The recirculating line does not let water flow from the tank to the pump, so it
works only if the Tank to Pump valve is OPEN, or if the intake is supplied by a water source.
5. Observe Pump-Overheat Indicator (Optional)
1138
Watch the Pump-Overheat indicator (Figure 4-5) during pumping operations to make sure that the pump stays
cool.
If the Overheat indicator light turns ON, add fresh water, recirculate, discharge water, or shut engine OFF to cool
the pump.
4-12 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
Manual pump engagement is intended for limited use in the event of a failure in the primary control
system. If conditions warrant the use of this override, pumping operations may continue, but the truck
should be examined by a service technician upon return to the station to identify and repair the cause
of the failure.
NOTE: If this override is used, make sure it is disengaged once pump operations are complete.
If power is lost to the pump shift switch in the cab, the following steps can be used to manually engage the pump.
1. Ensure the parking brake is set and the pump shift in the cab is in the OFF position.
2. Proceed to the pump operator’s panel.
3. Open the access panel door located in the lower right of the pump panel.
4. Flip up the switch guard.
5. Turn the switch to the ON position.
6. A yellow indicator light will illuminate if the pump is engaged. Repeat if necessary.
7. Proceed with normal operating functions.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-13
OPERATION
Apparatus equipped with pressure governors normally do not have pressure relief valves. The
pressure governor performs the function of the relief valve.
Always pump in pressure control mode.
Pumping in throttle (RPM) control mode can cause high pressure and/or pressure spikes. Pressure
spikes can injure or kill.
NOTE: For additional information concerning the operation of the pressure governor, refer to the Pierce
Pressure Governor Interactive Manual (2012V1) on CD-ROM and the FRC PMA300 Pressure
Governor service group (2825-V-007) included in the service manual.
4-14 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
NOTE: For additional information concerning the operation of the pressure governor, refer to the PUC
Pressure Governor Operator’s Guide CD-ROM (PV-P-TM450) and/or the FRC PMA300 Pressure
Governor service group (2825-V-007) included in the service manual.
Transferring engine speed control between Hand Throttle and Pressure Governor can cause a jump in
engine speed.
Engine speed changes can cause discharge water pressure spikes.
Spikes in discharge pressure can cause hoses to kick with great force, causing injury.
Some apparatus have both a Hand Throttle and a Pressure Governor. The Throttle Selector Switch determines
which control is ON.
If Hand Throttle is selected, you will control engine speed manually.
If Pressure Governor is selected, the Pressure Governor controls engine speed.
ALWAYS return the control you are not using to the IDLE position.
1139
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-15
OPERATION
1140/POM0021
4-16 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
1142
Water level in the water tank drops as water flows to the attack lines. Watch the Tank Level Indicator. Plan ahead
to add external water before you empty the tank.
Learn how to open and close valves using these controls on your pump panel:
Lever Controls
— Pull to open valve
— Push to close valve
— Rotate knob clockwise to the right to lock
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-17
OPERATION
4-9. Changing from Tank to External Pressurized Water Supply (with Gated Intake Valve)
Soon after the pump is running and water is being supplied to the discharge lines, you need to establish an external
source of water BEFORE the water tank is empty. This supply can come from a hydrant, from another apparatus,
or from a draft source, such as a pond, river, or portable tank.
A gate intake allows you to maintain water flow at the same pressure at the same time you switch to an external
water supply.
In the absence of a gate intake valve, clear fire fighters from the attack area before you change to external water
supply, because you will lose all water pressure.
Most fire departments provide their own gate valves. Pierce recommends use of a gate valve.
Before using water from a hydrant, open and vent the hydrant for about 30 seconds to flush out gravel or debris.
Always use intake strainers. Gravel can damage the pump and reduce pressure.
4-18 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
1143
Close the gate valve on the intake connection to which the intakes hose will be attached.
Always OPEN Drain Valve or Bleed Valve BEFORE removing Intake Cap.
Intake Lines can trap pressure.
Intake Cap under pressure will blow off with explosive force.
Exploding cap will injure or kill.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-19
OPERATION
POM0024
Remove the Intake Cap only after you are certain that trapped air pressure has escaped.
Make sure to OPEN the Air Bleed Valve or Drain Valve so that trapped air pressure escapes.
NOTE: Make sure that the pressure control has been set before charging the intake hose.
4-20 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-21
OPERATION
NOTE: 20 PSI may not be attainable in certain areas, depending on the hydrant system. For additional
information, consult your Fire Department standard operating procedures.
4-22 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
ALWAYS refill water tank as soon as possible. If the supply source is interrupted, a full tank of water allows you to
continue flowing water to the attack lines while an external water source is being restored.
1. Open Tank Fill Valve
OPEN the Tank Fill Valve slowly to ¼ OPEN to divert some supply water into the water tank.
2. Watch Intake and Discharge Pressure
Watch the discharge pressure gauges to make sure that you maintain attack hose flow at the desired pressure
while you also fill the water tank.
If intake or discharge pressure drops below the desired pressure, either CLOSE the Tank Fill Valve to divert less
water to the tank OR increase engine speed to maintain pressure.
Always keep the water tank full so that a steady discharge flow can be maintained if the intake supply must be
shifted.
4-13. Changing from Tank to External Water Supply (without Gated Intake Valve)
If you change from the water tank to an external water source without an Intake Gate Valve, the water flow to the
discharge attack lines must be stopped.
Pierce recommends that every pumper apparatus have an Intake Gate Valve.
Use these procedures if Gate Valve is absent.
Make sure fire fighters are withdrawn from attack area, because hoses will lose water.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-23
OPERATION
1144
The Engine Status Display is either a group of gauges and indicator lights or an electronic display that gives you
critical information on engine performance.
You must watch this information often during pump operation, and react to any abnormal readings.
4-24 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
If the Stop Engine light turns ON, the engine's ECU (electronic control unit) has detected a critical error condition.
That means engine failure is possible at any moment. Read and study the engine manufacturer's operations manual
so you know how to react. Practice your reaction to all different kinds of failure. You need to be prepared in
advance so you can react properly in an emergency.
Fire apparatus programming does not allow a critical engine failure to automatically stop the engine. The engine will
continue to run until it self-destructs or fails.
It is your judgment call to balance the risks of damage to the engine with the need for the fire apparatus to remain
operational.
If possible, replace the apparatus with another apparatus RIGHT AWAY if this light comes on.
• Check Engine Light
If the Check Engine light turns ON, the engine's ECU detects a non-critical error condition. Immediately check
all gauges at the pump panel and compare with the readings of those in the cab. Compare both readings to
normal operating parameters. This will help you make the decision to continue to run the apparatus or replace
it with another. If the Check Engine light remains ON, schedule the engine for maintenance.
• Check Transmission Message
A Check Transmission message is displayed if the transmission's control unit detects a non-critical error. If the
Check Transmission message remains ON, schedule the transmission for maintenance.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-25
OPERATION
The pumping system should be drained during cold weather. See “Draining the Pumping System” on
page 5-1 for additional information.
4-26 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
OPERATION
5. Flush Pump
Flush the pumping system with clean, fresh water if required.
6. Purge Primer
If equipped with a fluid-lubricated primer pump, operate the primer pump until primer fluid comes out of the
primer pump discharge. Check primer fluid tank level, and fill if needed.
Operating the pump from a draft source is the most demanding type of pump operation. Learn about the complexities
and hazards of this operation by studying the IFTSA Pumping Apparatus Driver/Operator Handbook and through
formal training.
Once the apparatus is prepared for draft operation and the appropriate suction lines are deployed, prime the pump
as follows:
1. Close Valves
First, close all discharge valves, drain valves, bleed valves, and tank valves or the primer will fail to work.
2. Switch Pressure Governor to THROTTLE (RPM) CONTROL Mode
If the apparatus is equipped with a pressure governor, place it in THROTTLE (RPM) CONTROL mode. For
governor equipped apparatus, this will hold the prime better than starting out in PRESSURE mode.
3. Increase Engine Speed
Increase the engine speed to 1000 RPM. This should provide about 50 PSI of water pressure once the prime is
established.
4. Open Primer Valve
Pull to OPEN the Primer Valve and engage the primer motor. Listen to the sound of the primer motor as it pumps
air out of the water pump to draw a vacuum. Listen for the tone change as the primer pump begins to expel a
mix of air & water, and then begins expelling only water.
5. Observe Pressure Gauge
Watch the pressure on the Master Pressure Gauge to make sure that the water has entered the pump and the
pressure is beginning to build.
6. Open Discharge Valve
Open the Discharge Valve slowly to begin water flow operation.
7. Switch Pressure Governor to PRESSURE CONTROL Mode
For pressure governor equipped apparatus, switch from THROTTLE (RPM) CONTROL mode back to
PRESSURE CONTROL mode.
8. Increase Pressure
Continue to watch the Master Pressure Gauge. Increase the pressure until you reach the desired discharge
pressure.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 4-27
OPERATION
4-28 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
SECTION 5 MAINTENANCE
Never run the pump dry except momentarily and at low speeds.
Do not use this pump for hose testing.
NOTE: If it is desired to retain water in the water tank, the Tank to Pump and Tank Fill valves should be left
in the closed position.
Every part of the water pump system must be drained if exposed to freezing temperatures.
1. Locate the lowest points on every plumbing line and the drain valve that opens it
2. Remove Caps
AFTER opening air bleeder valves, remove all intake and discharge caps.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 5-1
MAINTENANCE
1145
The master pump drain (Figure 5-1) will empty both the discharge and inlet manifolds of water when opened.
4. Open Discharge Line Drains
Locate each Discharge Line and open the Drain Valves.
5. Open Intake Line Drains
Locate each Intake Line and open the Drain Valves.
6. Open Intake Relief Valve Drain—on apparatus equipped with relief valves
7. Open Control Valves
Open all Intake and Discharge Valves.
8. Purge Primer
Primer should be purged regularly in cold weather to prevent the primer from freezing.
9. Allow Water to Drain
10. Close all Valves
NOTE: If your apparatus is equipped with a foam system, refer to the applicable foam system manual for
draining procedures.
5-2 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
MAINTENANCE
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 5-3
MAINTENANCE
Flush the pumping system after pumping dirty, contaminated, or salty water.
1. Supply Clean, Fresh Water
Supply clean, fresh water to the pumping system.
2. Open Discharge Valves
Open all discharge valves so that clean, fresh water flows through each discharge line and valve for one minute.
3. Fill Tank
Fill the water tank with clean, fresh water.
4. Flush Drain Valves
Flush all drain valves using the procedure listed under Flushing the Drain Valves.
In warm temperatures store pump either entirely full of water or completely empty.
Pumps stored partially full of water will rust at the air-to-water interface.
In freezing temperatures store pumps dry, without any water in the pump chamber.
Refer to Table 5-1 for a schedule of service and lubrication requirements. Perform services at the indicated interval
of miles or time, whichever comes first.
5-4 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
MAINTENANCE
Pump
Description Action Hours Time
Primer Pump Check primer pump lubricating fluid level and fill as - Daily
necessary. See “Primer Pump Lubrication” on page 5-5.
Intake/Discharge Drained trapped water. See “Intake & Discharge Relief - Daily
Relief Valves Valve Drains (Optional)” on page 5-6.
Pump Transmission Check the oil level. See “Pump Transmission 25 3-months
Lubrication” on page 5-7.
Pump Transmission Change the oil and filter. See “Pump Transmission 100 6-months
Lubrication” on page 5-7.
Anode Rods Inspect and replace as necessary. See “Anode Rods - 6-months
(Optional)” on page 5-11.
Master Gauges Test and calibrate. See “Master Gauge Ports” on - Annually
page 5-6.
Annual Testing See “Annual Testing” on page 5-13. - Annually
Use environmentally-friendly priming lubricants or use procedures that capture the oil as it is expelled.
Expelling standard motor oil used as a lubricating fluid in the primer pump does not meet EPA
regulations.
POM0031
Some primer pumps require a lubricating fluid or oil. The fluid reservoir (Figure 5-2) is normally located in the pump
house behind an access panel or access door.
For oil-type priming pumps, the lubricant is expelled with the air as the pump is primed.
Use only lubricating fluid that is approved by the manufacturer of the pump and approved for use in the environment.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 5-5
MAINTENANCE
POM0032
Inlet and discharge relief valves can trap water inside the mechanism of the valve.
Drain trapped water from the valve daily, and before operating apparatus in freezing temperatures.
Frozen water will damage the valve.
Vacuum and Pressure Test Ports are provided for use during the annual testing and certification of the pump.
Master gauge testing and calibration should only be performed by trained maintenance personnel.
NEVER remove plugs in these ports except for test purposes.
5-6 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
MAINTENANCE
Only use the recommended PUC lubricant in the PUC transmission. Failure to comply will cause
damage to equipment and void the warranty.
The Pierce Ultimate Configuration (PUC) pump transmission incorporates an internal lubrication pump providing
forced lubrication for power transmission components. The positive lubrication system provides an effective means
to filter, cool, and distribute the lubricant in a controlled manner. The pump transmission lubricant is circulated from
the gear case reservoir, through a heat exchanger, cooler, filter, and then back into the transmission assembly at the
outboard impeller shaft bearing. Internal oil passageways distribute oil to component contact surfaces, minimizing
contact wear.
In top mount applications, in-line, low pressure non-return valves are installed on transmission lubrication discharge
and return ports to prohibit draining of oil from the external lubrication components back to the pump transmission
reservoir tank. This ensures that the oil level dipstick will provide accurate and consistent readings.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 5-7
MAINTENANCE
1213
5-8 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
MAINTENANCE
1855834
Maintain gear case oil level to a point between the two grooves on the oil level dipstick. When checking oil level,
dipstick must be screwed all the way in and then removed for accurate readings.
Check the oil level every 25 hours of pumping operation or every three months. Change the oil and filter every 100
hours or 6 months.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 5-9
MAINTENANCE
Only use the recommended PUC lubricant in the PUC transmission. Failure to comply will cause
damage to equipment and void the warranty.
Do not overfill. Overfilling may cause excessive gear case operating temperatures.
Service driveline universal joint grease fittings at regular chassis service intervals.
NOTE: • The part number for the replacement spin-on filter element is Pierce PN 1777990.
• Approximate gear case oil reservoir capacity is 4 quarts of lubricant. Oil filter and cooler will
require an additional 2 quarts when completely drained.
Specification Specification
SAE Viscosity Grade 10W Viscosity:
- cP @ -20°C (ASTM D5293) 3130
- cSt @ 40°C (ASTM D445) 39.1
- cSt @ 100°C (ASTM D445) 6.1
Manufacturer’s Test: Viscosity Index (ASTM D2270) 97
- CAT TO-4
- Allison C-4, C-3
ISO Viscosity Grade 32 Calcium, % wt. .298
Gravity, °API (ASTM D287) 27.9 Sulfated Ash, % wt. (ASTM D874) 1.2
Appearance (Visual) Clear & Bright Zinc, % wt. (ASTM D1549) .127
Flash Point, °C (°F) (ASTM D92) 202 (395) Phosphorous, % wt. (ASTM D1091) .110
Pour Point, °C (°F) (ASTM D97) -36 (-33) min. TBN (ASTM D2896) 7.9
5-10 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
MAINTENANCE
Figure 5-6: Oil Level Dipstick and Fill Port and Drain Plug
1132
1419/1420/1421
Anodes help prevent damage caused by galvanic corrosion within the pump and plumbing. Galvanic corrosion
results when different conducting materials are connected and exposed to water. With the use of anodes, galvanic
corrosion will attack the less resistant of the two metals (anodes) while protecting the more resistant metal (the
pump). Using the proper sacrificial anodes extends the life of your pump by corroding the anode instead of the pump
and plumbing.
Anodes should be inspected semi-annually and replaced when over 75% of the material has been consumed.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 5-11
MAINTENANCE
This pump assembly incorporates a high quality mechanical shaft seal separating the pump housing components
from atmosphere. The seal size, design type, component materials, and housing configuration have been
specifically designed for this pump application and rated operating parameters.
PT1954
PT1954
5-12 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
MAINTENANCE
Properly selected and applied mechanical shaft seals are leak free and require no adjustment. Should the seal area
develop a leak, investigate the cause as soon as possible. Seal failure, leakage, may be the result of: worn seal
faces, leaking bellows, or damaged o-rings. These failures may be attributed to bearing failure, impeller blockage,
impeller imbalance, seal housing contamination, operating beyond pump design rating, or dry running,
Mechanical shaft seal design relies on the sealed media (in this case, water) to cool and lubricate the sealing
surfaces. Therefore, extended dry operation may cause overheating and scoring or damage to the sealing surfaces,
resulting in excessive leakage or a much shortened seal life.
To maximize seal life, minimize operation at pump pressures higher than pump rating. While operating at pressures
beyond rating will not immediately damage the seal, it will increase sealing surface wear rate.
Test all pumping apparatus annually per the specifications in NFPA 1911, Standard for the Inspection, Maintenance,
Testing and Retirement of In-Service Automotive Fire Apparatus (latest edition).
These tests are necessary to make sure that the apparatus will continue to perform to specification.
These tests help prevent breakdowns.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 5-13
MAINTENANCE
5-14 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
SECTION 6 REFERENCE TABLES
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 6-1
REFERENCE TABLES
Class A
TEST Recom- Min. Min. Min. Net Disch. Suction
No. GPM mended Nozzle Disch. Pump Lines Hose
Nozzles Press. PSI Press. PSI Press. PSI
500 GPM Pump
1 500 1-1/2" 57 143 150 1-50" 20' of 4"
2 350 1-1/4" 58 194 200
3 250 1" 72 245 250
4 500 1-1/2" 57 158 165
750 GPM Pump
1 750 1-3/4" or 68 142 150 2-50'
2, 1-1/4" 66
2 525 1-1/2" 62 193 200 or 20' of 4-1/2"
3 375 1-1/4" 66 244 250 2-100'
4 750 1-3/4" or 68 157 165 Siamesed
2, 1-1/4" 66
1000 GPM Pump
1 1000 1, 2" or 71 142 150 2-50'
2, 1-1/2" 57
2 700 1-3/4" or 60 193 200 or 20' of 5"
2, 1-1/4" 58
3 500 1-1/2" 57 244 250 3-100'
4 1000 1, 2" or 71 157 165 Siamesed
2, 1-1/2" 57
1250 GPM Pump
1 1250 2-1/4" or 69 143 150 3-50'
2, 1-1/2" 88
2 875 1, 2" or 55 194 200 or
2, 1-3/8" 61
3 625 1-1/2" 88 245 250 3-100' 20' of 6"
4 1250 2-1/4" or 69 158 165 and 1-50'
2, 1-1/2" 88
Siamesed
Min. discharge pressures listed above are for pumps operating with full 10’ static suction lift. These pressures
must be increased by 1 PSI for each 2.3 ft. less than 10’ of lift.
6-2 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
REFERENCE TABLES
Min. discharge pressures listed above are for pumps operating with full 10’ static suction lift. These pressures
must be increased by 1 PSI for each 2.3 ft. less than 10’ of lift.
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 6-3
REFERENCE TABLES
Table 6-2: Discharge From Smooth Bore Nozzle - Pressures Measured by Pitot Gauge
Nozzle
Pressure 1/4 3/8 1/2 5/8 3/4 7/8 1 1 1/8 1 1/4 1 3/8 1 1/2 1 5/8 1 3/4 2 2 1/4
PSI GALLONS PER MINUTE DELIVERED
5 4 9 16 26 37 50 66 84 103 125 149 175 203 266 337
6 4 10 18 28 41 55 72 92 113 137 163 192 223 292 369
7 4 11 19 30 44 59 78 99 122 148 176 207 241 315 399
8 5 11 21 32 47 64 84 106 131 158 188 222 257 336 427
9 5 12 22 34 50 67 89 112 139 168 200 235 273 357 452
10 6 13 23 36 53 71 93 118 146 177 211 248 288 376 477
12 6 15 25 40 58 78 102 130 160 194 231 271 315 412 522
14 7 15 27 43 63 84 110 140 173 210 249 293 340 445 564
16 7 16 29 46 67 90 118 150 185 224 267 313 364 475 603
18 7 17 31 49 71 95 125 159 196 237 283 332 386 504 640
20 8 18 33 51 75 101 132 167 206 250 298 350 407 532 674
22 8 19 34 54 79 105 139 175 216 263 313 367 427 557 707
24 8 20 36 56 82 110 145 183 226 275 327 384 446 582 739
26 9 21 37 59 85 115 151 191 235 286 340 400 464 606 769
28 9 21 39 61 89 119 157 198 244 297 353 415 481 629 799
30 10 22 40 63 92 123 162 205 253 307 365 429 498 651 826
32 10 23 41 65 95 127 167 212 261 317 377 443 514 673 854
34 11 23 43 67 98 131 172 218 269 327 389 457 530 693 880
36 11 24 44 69 100 135 177 224 277 336 400 470 546 713 905
38 11 25 45 71 103 138 182 231 285 345 411 483 561 733 930
40 11 26 46 73 106 142 187 237 292 354 422 496 575 752 954
42 11 26 47 74 109 146 192 243 299 363 432 508 589 770 978
44 12 27 49 76 111 149 196 248 306 372 442 520 603 788 1000
46 12 28 50 78 114 152 200 254 313 380 452 531 617 806 1021
48 12 28 51 80 116 156 205 259 320 388 462 543 630 824 1043
50 13 29 52 81 118 159 209 265 326 396 472 554 643 841 1065
52 13 29 53 83 121 162 213 270 333 404 481 565 656 857 1087
54 13 30 54 84 123 165 217 275 339 412 490 576 668 873 1108
56 13 30 56 86 125 168 221 280 345 419 499 586 680 889 1129
58 13 31 56 87 128 171 225 285 351 426 508 596 692 905 1149
60 14 31 57 89 130 174 229 290 357 434 517 607 704 920 1168
62 14 32 58 90 132 177 233 295 363 441 525 617 716 936 1187
64 14 32 59 92 134 180 237 299 369 448 533 627 727 951 1206
66 14 33 60 93 136 182 240 304 375 455 542 636 738 965 1224
68 14 33 60 95 138 185 244 308 381 462 550 646 750 980 1242
70 15 34 61 96 140 188 247 313 386 469 558 655 761 994 1260
72 15 34 62 97 142 191 251 318 391 475 566 665 771 1008 1278
74 15 35 63 99 144 193 254 322 397 482 574 674 782 1023 1296
76 15 35 64 100 146 196 258 326 402 488 582 683 792 1036 1313
78 15 36 65 101 148 198 261 330 407 494 589 692 803 1050 1330
6-4 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
REFERENCE TABLES
Table 6-2: Discharge From Smooth Bore Nozzle - Pressures Measured by Pitot Gauge (Continued)
80 16 36 66 103 150 201 264 335 413 500 596 700 813 1063 1347
82 16 37 66 104 152 204 268 339 418 507 604 709 823 1076 1364
84 16 37 67 105 154 206 271 343 423 513 611 718 833 1089 1380
86 16 37 68 107 155 208 274 347 428 519 618 726 843 1102 1396
88 16 38 69 108 157 211 277 351 433 525 626 735 853 1115 1412
90 17 39 70 109 159 213 280 355 438 531 633 743 862 1128 1429
92 17 39 70 110 161 215 283 359 443 537 640 751 872 1140 1445
94 17 39 71 111 162 218 286 363 447 543 647 759 881 1152 1460
96 17 40 72 113 164 220 289 367 452 549 654 767 890 1164 1476
98 17 40 73 114 166 223 292 370 456 554 660 775 900 1176 1491
100 18 41 73 115 168 225 295 374 461 560 667 783 909 1189 1506
105 18 42 75 118 172 230 303 383 473 574 683 803 932 1218 1542
110 19 43 77 121 176 236 310 392 484 588 699 822 954 1247 1579
115 19 43 79 123 180 241 317 401 495 600 715 840 975 1275 1615
120 19 44 80 126 183 246 324 410 505 613 730 858 996 1303 1649
125 20 45 82 129 187 251 331 418 516 626 745 876 1016 1329 1683
130 20 46 84 131 191 256 337 427 526 638 760 893 1036 1356 1717
135 21 47 85 134 195 262 343 435 536 650 775 910 1056 1382 1750
140 21 48 87 136 198 266 350 443 546 662 789 927 1076 1407 1780
145 21 49 88 139 202 271 356 450 556 674 803 944 1095 1432 1812
150 22 50 90 141 205 275 362 458 565 686 817 960 1114 1456 1843
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 6-5
REFERENCE TABLES
Table 6-3: Approximate Discharge Flow From Different Nozzles At the end of Fifty Feet of Average, 2 1/2”
Rubber Lined Fire Hose, for Various Pump Pressures with Discharge Valve Wide Open
This table is offered as an aide in testing pump performance where facilities for accurate measurement of capacity
are not available. The capacities given above are conservative, and will not vary more than 5% from actual
capacities with any of the standard hose that might be used.
6-6 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
REFERENCE TABLES
Table 6-4: Pump or Hydrant Pressure required to provide Effective Nozzle Pressure through various Lengths of
Rubber Lined Hose
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 6-7
REFERENCE TABLES
Size of
Nozzle 1/4" 3/8" 1/2" 5/8" 3/4" 7/8" 1" 1-1/4" 1-1/2"
NOZZLE
PRESSURE EFFECTIVE VERTICAL REACH - Feet
40 30 35 40 50 59 62 64 65 69
60 35 40 45 60 74 77 79 84 87
80 38 42 48 65 81 85 89 94 96
100 40 44 50 68 84 89 94 100 102
NOZZLE
PRESSURE MAXIMUM VERTICAL REACH - Feet
40 60 65 70 75 78 79 80 80 80
60 70 75 85 95 105 106 108 110 110
80 78 83 95 105 117 125 132 140 140
100 80 88 100 110 122 135 145 155 155
NOZZLE
PRESSURE EFFECTIVE HORIZONTAL REACH - Feet
40 20 25 30 40 44 50 55 62 66
60 25 32 37 50 54 61 67 75 80
80 28 35 40 57 62 70 76 84 88
100 30 37 42 60 66 76 84 93 95
NOZZLE
PRESSURE MAXIMUM HORIZONTAL REACH - Feet
40 65 80 90 100 108 120 125 138 140
60 80 95 95 120 127 142 156 176 183
80 90 105 105 135 143 160 175 201 210
100 95 110 110 140 153 180 205 215 223
6-8 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
REFERENCE TABLES
Table 6-6: Friction Loss in Fire Hose Loss in PSI per 100 Feet of Hose
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 6-9
REFERENCE TABLES
Table 6-6: Friction Loss in Fire Hose Loss in PSI per 100 Feet of Hose (Continued)
Losses in rough walled, rubber hose may be 50% higher than values given above.
Table 6-7: Friction Loss in 15-year-old Steel Pipe Loss in PSI per 100 Feet of Pipe
PIPE SIZE 1/8 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4 6 8
G.P.M.
1 52.0 12.0 2.8 0.9
2 45.0 10.0 3.2 4.0
5 55.0 18.0 4.5 1.4 0.4
10 64.0 16.0 5.0 1.3 0.6
15 135.0 34.0 11.0 2.7 1.3 0.5
20 59.0 18.0 4.7 2.2 0.8
25 89.0 27.0 7.1 3.4 1.2
30 125.0 39.0 10.0 4.7 1.7 0.6
35 51.0 13.0 6.3 2.2 0.7
40 66.0 17.0 8.0 2.9 0.9
45 82.0 21.0 10.0 3.6 1.2
50 99.0 26.0 12.0 4.3 1.4 0.6
60 140.0 38.0 17.0 6.1 2.0 0.8
70 49.0 23.0 8.0 2.7 1.1
80 63.0 29.0 10.0 3.4 1.5
90 78.0 36.0 13.0 4.3 1.8
100 96.0 44.0 15.0 5.1 2.2 0.5
125 144.0 66.0 24.0 7.8 3.3 0.8
150 93.0 33.0 11.0 4.6 1.1
175 125.0 44.0 15.0 6.1 1.5
200 56.0 19.0 7.8 1.9
250 84.0 28.0 12.0 2.9
300 114.0 40.0 16.0 4.0 0.6
350 53.0 22.0 5.4 0.8
400 68.0 28.0 6.9 1.0
450 84.0 35.0 8.6 1.2
500 102.0 42.0 10.0 1.4 0.4
600 60.0 15.0 2.1 0.6
800 25.0 3.5 1
1000 37.0 5.2 1.3
1500 11.0 2.7
2000 19.0 4.7
2500 29.0 7.1
3000 10
6-10 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
REFERENCE TABLES
Table 6-9: To Convert Pounds per Square Inch to Feet Elevation of Water
Feet 5 10 15 20 25 30 35 40 45 50 60 70 80 90
PSI 2.2 4.3 6.5 8.7 11 13 15 17 20 22 26 30 35 39
Feet 100 120 130 140 150 160 170 180 190 200 220 240 260 280
PSI 43 52 56 61 65 69 74 78 82 87 95 104 113 121
Feet 300 320 340 360 380 400 425 450 475 500 525 550 600 700
PSI 130 139 147 156 165 173 184 195 206 217 227 238 260 303
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / 6-11
REFERENCE TABLES
6-12 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
INDEX
D H
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / Index-1
INDEX
R
M
Refilling the Tank ..................................... 4-23
Maintenance Schedule ............................... 5-1
Responsibility ............................................ 1-3
Manual Pump Engagement ....................... 4-13
Resume Discharge Operation ..................... 4-24
Master Gauge Ports ................................... 5-6
Rotating Auxiliary Driveshafts ....................... 1-4
Measuring Pump Performance ..................... 3-5
Mechanical Seal ...................................... 5-12
Mechanical Seal Basics ............................ 5-12 S
Mechanical Seal Operation and Maintenance 5-12
Safety ...................................................... 1-3
Mechanical Shaft Seal .............................. 5-12
Safety Defect Reporting .............................. 1-6
Monitoring Intake Pressure ........................ 4-21
Safety Warning Labels ................................ 1-2
Screw Thread ......................................... 6-12
N Securing Pump System ............................. 4-26
Shutting Off Water Flow ............................ 4-25
Nozzle Pressure ........................................ 6-7
Smooth Bore Nozzle Discharge .................... 6-4
Source of Water Supply .............................. 3-4
O Stepping and Walking Surfaces .................... 4-1
Stop Flowing Water .................................. 4-23
Oil Level Dipstick and Fill Port and Drain Plug 5-11
Suction Line .............................................. 3-2
Operating Characteristics of Pumps .............. 3-6
Suction Strainers ....................................... 3-2
Operating from a Static (Draft) Water Supply . 4-27
Supply the Pump ..................................... 4-21
Operating the Engine ................................. 3-2
Supply Water to Pump .............................. 4-10
Operation of Pump ..................................... 4-7
Operation PUC Fire Pump ........................... 4-7
T
Testing for Air Leaks ................................... 3-3
Index-2 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.
INDEX
V
Various Nozzles Discharge .......................... 6-6
Vertical and Horizontal Nozzle Reach ............ 6-8
W
Warnings ................................................. 1-2
What To Do If You Lack Knowledge .............. 1-1
When Finished Pumping ............................. 3-4
Who Should Use, Service and Maintain
This Vehicle ................................... 1-1
© 2014 Pierce Manufacturing Inc. All Rights Reserved. PUC Pumpers / Index-3
INDEX
Index-4 / PUC Pumpers © 2014 Pierce Manufacturing Inc. All Rights Reserved.