Global Electrical Laboratory
am EL
Certiicale No TO 6545
TEST REPORT Sheet Lot 2
Name and address of customer Report No: GEL/R/I71A3-36
Laxmi Assotlates (R.KM, Powegen Pvt. Ltd.) Date —_| 31.08.2017 _ =
Sun Enclave, office ne.13,14,15, Customer Ref. No. and Date | Letter dated 23” Aug.2017
Near Suneity Paradise, Date of sample receipt 73,08 2017
Manjalpur ,Vadodarar390020 Datecoftesting | 29.08.2017
Sample description Sample identificationeode | GEL/17143-26
Transformer oll of Sampling: -
34 MVA, 20/11.5 kW Transformer, 1, Oil sample drawn by customer
Sr. No, 682000665-0-11208, Tag No. UAT2-B fi, Sampled on : 20.08.2017
Schneider Make, It, Sampling point : Main Tank Top
Location: 4360 Therenal plant,Unit-2, Uchhpinds _|IV, Top ailtemperature during sampling 'C
Test deta st Specification -
1S 1866 - 2000
No. | Name of Test Clause Nos. of I$ 1866 ~ 2000
‘Appearance 7
2 | Electrical steength 72
3 Water content 73
@__| Neutralization value 7a
[s Sediment & Sludge 2
6___| Dielvetric Dissipation Factor (Tan delta) —
7 Specific Resistance (Resistivity) =
8 Interfacial Tension
9 Flash Point
10 | Pour Poin
[a1 | Density
12__| viscosity
f2__[ wicosity
Remark: The sample conforms to the requirements of all the above mention tests.
ee
Z (DrMShrinet , Director)
Testedby —— Approved by.
Note | §, This report relates only to the particular sample received far testing in go it GEL.
2, This report cannot be reproduced in part under any circumstances.
3, Publication of this report requires prior permission in writing from Dine
4, nly the tests asked by the customer have been carted out.
5. Incase of any dispute, Vadodara will be the exclusive jurisdiction, \
6. GEL is not responsible for the authenticity of photocopied or reproduced
302, Sun Enclave, Near Sun City Paradise, Manjalpur, VABODARA— 390020, IndiaGlobal Electrical Laboratory
Caieate No TC-S546
| TEST REPORT No -GEL/R/17143-26 Date-31" August 2017 Sheet 2 of 2
t
st | Clause Requirement a5
lth Test Particulars perepeetticntion | Obtained value | Remark
Clear free trom | Clear, free from
2/71 | Appearance Sediments & Sediments & Conforms
matter | Suspended matter
Electric Strength; kV a i ne
2 |7.2 | Typesof Electrodes : Spherieat Min. 30 Conforms
5/463 6)518
Frequency of test voltage : 61.8 Hz
‘Ave. 55
13 [7.3__ | Water content: ppm Max;50 7 Conforms
a [pq | Neutralization Value (Total Acids | yg 5 ony ceca
* | mg kone
5 |75 | Sediment and siudge | Not etectable | Not Detected Conforms
Dielectric Dissipation Factor Mees | |
mS. | ee ereryate Max: 10 0.0006 Conforms
Specific Resistance (Resistivivdat | ay, gay gol? 2 fi
H ]362 | Se amctn Mins 94x30" | 7oGRLO! Conforrss
a [2.7 — | Imerfaciattension at27°C; mN/m | Min: 35 47 Conforms
9 [7.9 | Flash Point (mice); *c Min. 125 142 ‘Conforms
30 [7.10 | Pour Point; “c Maxs-6 <6 Conforms
a1 [#11 _| Density at 29°C; am/em3 Max:0.89 0.820 ‘Conforms
12 [7.42 | Viseosity at 27°C, eSt Max:27 2 Conforms
Test Condition for Specific Resistance and Dielectric Dissipation factor:
> Type of eel! used: 1S 6262-1971 (Fig 4)
> Average voltage gradient in the sample while under test: 250. Vimm_
> Frequency of applied voltage: SO Hz
Temperature of the reom during test: 26.9°C
Humidity of the room during test: 48.636
Tasted by
302, Sun Enclave, Near Sun City Paradise, Manjalpur, VADODARA~ 390020, IndiaGlobal Electrical Laboratory
Certiheate No TO-S545
Methane (Cra)
TEST REPORT Sheet Loft
‘Name and address of custamer Report No: ‘GEL/RA7143-26
Laxmi Associates (R.K.M. Powegen Pvt, Ltd.) Date 31,08, 207
Sun Enclave, office na.13,14,215, store’ Ref, No, and Date | Letter dated 23° Av, 2017
Near Suncity Paradise, Date of sample receipt 23.08.2017
Manjalpur Wadedara-390020 Date of tenting 29.08.2017
Sample description Sample identification code | GEL/17143-26
Transformer oil of "Sampling: - -
33 MVA,20/11.5kW Transformer, |, Oil sample drawn by customer
Sr. No. 682000665-D-11205, Tag No. UAT-2-8 1, Sampled on : 20,08,2017
‘Sehneider Make, ill, Sampling point : Main Tank Top
| Location: 4x360 Thermal plant, Unit-2, Uehinpinda liv, Top oll temperature during samaling °C 47°C
Test details = ‘Test Specification ~
Dissolved Gas Analyéls (OGA) of Transformer O11 | NEC 60567 - 200-06 (C1. 7.5, Headspace method)
No. Name of Gas ‘Obtained value (ppm)
i Hydrogen (Hy) BOL
2 Oxygen (03) 4508 - ==
3___ | Nitrogen (N;) 14093 —
Lf Carbon monoxide (CO) =
be
6
[ethane (C,H)
iT
‘Acetylene (Cy) |
10 Propanes Propylene (GH Gil) |
[ BDL = Below Deteetion Level
‘Comments: 1) These results will be considered as a roforence for future analysis.
2) Please getit retested after one year tomonitor the rate of rise of individual gases.