Professional Documents
Culture Documents
Auto-Reclosure Synchro-Check & Voltage Check
Auto-Reclosure Synchro-Check & Voltage Check
REL316*4
Technology and Solutions Auto- Reclosure;
Protection and Substation Automation
Synchro- Check &
Voltage Check
BASICS
RE.316_ AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 1
ABB
REL316*4 Auto Reclosure; Synchro- & Voltage Check
Objectives
Auto Reclosure (79)
Rules / Facts
Important Settings
Supervision of the breaker (CB memory)
the four AR cycles
Function of the operating time
Examples
Substations with single busbar or multiple busbar
RE.316_AR_Syn / 2003-10-01 / RW
ABB
REL316*4 Auto Reclosure; Synchro- & Voltage Check
Objectives
Synchro Check (25) & Voltage Check (27/59)
Auto Reclosure interfaces
3-pole tripping with 3-pole AR
1-pole tripping with 1-pole AR
Operating Modes
Synchronism Monitoring
Application Example
Voltage Selection
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 3
ABB
REL316*4 Auto Reclosure (79)
Application Load
SYSTEM
TRIP LP TRIP LP
SYSTEM
AR Close CB AR Close CB
SYSTEM
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 4
SYSTEM
Load
ABB
REL316*4 79 - Rules / Facts
ABB
REL316*4 79 - Rules / Facts
ABB
REL316*4 79 - Rules / Facts
During the 1-pole dead time (one pole from the breaker is
open) all other functions who react on unsymmetry and
have a shorter tripping time then t-dead-1P-setting must
be blocked
Example:
- Directional earth fault with tripping scheme POTT
- Pole discrepancy protection
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 7
ABB
REL316*4 79 - Important Settings
1-pole dead time One pole opens and closes after t-dead -1P
(t dead 1P) Typical dead time: 0.3 – 0.5 s in high voltage
systems
3-pole dead time All 3 pole open and close after t-dead-3P
(t dead 3P) Typical dead time: 0.5 s – sev. minutes
Operating time Prevents an AR for a long during fault
(t oper) (eg. in the 2nd zone)
Discrimination time Decision about 1-pole AR, 3 pole AR or
(t discrim.1P, definitive trip after evolving fault
t discrim.3P)
RE.316_AR_Syn / 2003-10-01 / RW
ABB
REL316*4 79 - Important Settings
ABB
REL316*4 79 - Supervision of the breaker (CB memory)
ABB
REL316*4 79 – four AR cycles
Why several AR cycles?
First AR: With the opening of the breaker the voltage which
supplies the arc is switched off ⇒ the arc will extinguish
The dead time is set as short as possible. So the line can
be back in normal service as fast as possible.
Second AR: If the arc is not extinguished with the first AR attempt
(tree, bamboo) a second attempt with a longer dead time
will be started (2nd and 3rd attempt are 3-phase cycles)
Third AR: This attempt is just an automatic voltage check
One side will be switched on. An immediate trip occurs if
the fault is still present. The opposite station will only
RE.316_AR_Syn / 2003-10-01 / RW
ABB
REL316*4 79 - Function of the operating time t-oper
Fault duration < operating time Fault duration > operating time
Example: Trip in zone 1 initates an Example: Trip in a higher zone stops the a
AR cycle fast AR cycle
Starting
Starting
Tripping Tripping
Operating time
Discrimination time
Discrimination time
On pulse
Dead time
Definitive trip
Q0 Ph R t dead 1P
Q0 Ph S
Q0 Ph T
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 12
ABB
REL316*4 79 - Examples
AR Mode: fast AR 1 / 3 - pole Fault:: 1- phase Fault
Example: - fast AR successful
Starting 1-phase
Tripping 1-pole
Discrimination time
On - pulse
Dead time fast AR 1-pole,
RE.316_AR_Syn / 2003-10-01 / RW
Q0 Phase R
© ABB Switzerland Ltd. - 13
Q0 Phase S
Q0 Phase T
fast AR 1-pole
ABB
REL316*4 79 - Examples
AR Mode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase fault
Example: - fast AR not successful, - slow AR successful
Starting 1-phase
Tripping 1-pole
Discrimination time 1-pole
On-pulse, interrupted with second tripping
Dead time fast AR 1-pole,
Starting 1-phase
Tripping 3-pole
Discrimination time 3-pole
Q0 Phase R
© ABB Switzerland Ltd. - 14
Q0 Phase S
Q0 Phase T
LAR
fast AR 1-pole
ABB
REL316*4 79 - Examples
AR Mode:fast AR 1 / 3 - pole, followed by a long dead time Fault: 1- phase fault
Example: - fast AR not successful; - slow AR not successful
Starting 1-phase
Tripping 1-pole
Discrimination time 1-pole
On-pulse, interrupted with second tripping
Dead time 1-pole,
Q0 Phase R
Q0 Phase S
Q0 Phase T
ABB
REL316*4 79 - Examples
Mode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase fault
Example: - Evolving fault before expiring of discrimination time
- fast AR not successful, slow AR successful
Starting 1-phase
Tripping 1-pole
Discrimination time 1-pole
Dead time 1-pole,
interrupted with 2nd fault before expiring of 3-pole discrimination time
Starting 1-phase(other phase)
Tripping 3-pole
Discrimination time 3-pole
On-pulse, interrupted with tripping
Dead time
fast AR 3-pole
Starting 1-phase
Tripping 3-pole
Discrimination time 3-pole
Q0 Phase R
Q0 Phase S
Q0 Phase T
fast AR 1-pole
interrupted
fast AR 3-pole Slow AR
ABB
REL316*4 79 - Examples
AR mode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase fault
Example: - Evolving fault after expiring of discrimination time of fast AR
- Definitive tripping
Starting 1-phase
Tripping 1-pole
Discrimination time 1-pole
Dead time 1-pole,
interrupted with 2ten fault after expiring
of 3-pole discrimination time
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 17
Q0 Phase R
Q0 Phase S
Q0 Phase T
fast AR 1-pole
interrupted
ABB
REL316*4 79 - Substations with single busbar or multiple busbar
Standard - solution
AR “Cheap” - solution
Main Main
Main 1 Main 2 Main 1 Main 2 1 2
AR
RE.316_AR_Syn / 2003-10-01 / RW
3
© ABB Switzerland Ltd. - 18
ABB
REL316*4 79 - 1 1/2 breaker scheme
Bus A
Bus A - CB Q0 A AR AR AR
Center - CB Q0 C AR AR AR AR
“Diameter”
Bus B - CB Q0 B AR AR
All breakers are closed
during normal service
Bus B
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 19
ABB
REL316*4 79 - Master / Follower scheme
1 1/2 breaker scheme
M
Line
dead time.
ABB
REL316*4 79 – Line Protection Interfaces
RE.316*4
Start RST Start Auto-reclosure
<Z Trip CB Trip CB function
Trip CB 3P Trip CB 3P
CO ready
Close CB
Start SOTF CondBlkAR
CB ready
CB open
1PolAR Trip 3-Pol
ZExtensionAR ZExtension
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 21
ABB
REL316*4 25; 27/59 – Auto Reclosure Interfaces
25
27/59
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 22
ABB
REL316*4 27/59 – Voltage Check
ABB
REL316*4 27/59 - 3-pole tripping with 3-pole AR
Check of only one phase to phase voltage for the busbar and
the line is enough
Q0
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 24
ABB
REL316*4 27/59 - 1-pole tripping with 1-pole AR
On the busbar the check of one phase to phase voltage is enough
On the line the check of all three phase to ground voltage is
recommended
Q0
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 25
ABB
REL316*4 25; 27/59 – Operating Modes
Selectable Operating Modes
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 26
ABB
REL316*4 25 – Synchro Check
ABB
REL316*4 25 – Synchronism Monitoring
fBusbar = ωBusbar /2 π
∆V
fLine = ωLine /2 π
∆f = fBusbar - fLine = fSchlupf < 0.10 Hz
∆ϕ < 15°
∆ϕ
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 28
SETTINGS
ABB
REL316*4 25 – Application Example
Feeder Connected to a double busbar
RE.316_AR_Syn / 2003-10-01 / RW
© ABB Switzerland Ltd. - 29
ABB
REL316*4 25 – Voltage Selection
ABB
© ABB Switzerland Ltd. - 31
RE.316_AR_Syn / 2003-10-01 / RW
ABB