● Kala Flash Tool v1.3.1.8 and v1.3.3.3 are installed by default in the
same folder (C:\Program Files (x86)\KalaFlashTool)
● If Kala Flash Tool v1.3.1.8 is already installed, change the installation
folder for install Kala Flash Tool v1.3.3.3 (e.g. “C:\Program Files
(x86)\KalaFlashToolv1333”)
On some ATV630 frame size 6 the restart product (RP) command cannot
work. Hence, before to update an ATV630 frame size 6, verify the RP
command.
In this case, switch-off then switch-on the Altivar Process in order to restart it
manually. During the update process follow the specific procedure detailed in this
document.
[1]
● In Network Connection Properties
● Select the Advanced tab [1]
● In the Property: list, select Link
Speed & Duplex [2]
● In the Value: list, select Auto
Negotiation [3]
● Click the OK button
[2]
[3]
[1]
[2]
[2]
Schneider Electric - CCC Expert – 19/02/2016 17
Configuration of Kala Flash Tool
[3]
[4]
● In Open window:
● Select the firmware update package [1]
● Click the Open button [2]
[1]
[2]
Schneider Electric - CCC Expert – 19/02/2016 20
Configuration of Kala Flash Tool
[2]
[1]
● NOTICE: Before to apply the firmware update make sure that the
drive remains supplied during the whole firmware update process
● The Relays R1, R2 and R3 will be not remains in their normal states (NO
– Normally Open or NC – Normally Close) during the firmware update
process
● In FW Update Information
● Click the Continue button [1]
[1]
● Standard procedure
● Wait for the process to complete
NOTE: The drive will restart several times during the process
Schneider Electric - CCC Expert – 19/02/2016 26
Drive Update
● Follow the instruction of the window and wait the process to complete
Schneider Electric - CCC Expert – 19/02/2016 27
FAQ – Powered by P24 - 1/3
The message below and FWUP state will be displayed on the graphic
display terminal indicating that the flashing process is in pending of the
power only if the ATV6x0 is at least in v1.2IE06 otherwise no message
will be displayed.
As soon as the drive is fed by the main supply, the process will begin
automatically and update the power board (the drive will restart several
times)
When the process begin, wait for it to complete then press the OK button of the
graphic display terminal