2012 IBC ® Accessibility

and Usability for


Commercial Buildings
Based on the 2012 International Building
Code® and the ICC/ANSI A117.1 - 2009
Accessible and Usable Buildings and
Facilities
Accreditation

 The International Code Council has been accredited as


an Authorized Provider by the International Association
for Continuing Education and Training (IACET).
 As a result of their Authorized Provider accreditation status, ICC
is authorized to offer IACET CEUs for its programs that qualify
under the ANSI/IACET Standard.
 You will obtain full CEUs for this course, if you actively
participate in the training activities and stay for the entire
session. Evidence of this will be the sign out sheet.

2012 IBC Accessibility and Usability for Commercial Buildings 2


Pre-Test
 This short pre-test is designed to measure
content areas covered in this class and will
indicate what you already know about
these areas.

 At the end of this class, you will be asked


to take the test again in order to measure
your learning.

2012 IBC Accessibility and Usability for Commercial Buildings 3


Contents
 Overview
 Module 1 Introduction to Accessibility
 Module 2 Exterior Accessible Route
 Module 3 Accessible Entry and Means of Egress
 Module 4 Interior Accessible Route
 Module 5 Building Features and Facilities
 Module 6 Special Occupancy Requirements
 Module 7 Dwelling and Sleeping units
 Module 8 Existing Structures

2012 IBC Accessibility and Usability for Commercial Buildings 4


Page iii-iv
Goal
. . . determine the minimum
requirements for accessibility.
• 2012 International Building Code.
• 2009 ICC A117.1 Accessible
and Usable Buildings
and Facilities.
This seminar primarily addresses accessibility in commercial
buildings. Residential type facilities covered in this class is
limited to the facilities that are not permanent residences. There
are types of facilities that may have some overlap, such as
dormitories, assisted living facilities and nursing homes.

2012 IBC Accessibility and Usability for Commercial Buildings 5


Page 1
Objectives
 Upon completion of this seminar, you will be
better able to:
 Identify accessibility requirements in context of:
 Who they benefit.
 Where and why they originated.
 Distinguish between:
 Federal laws.
 Accessibility code requirements.
 Determine the extent to which accessibility code
provisions apply.
 Identify scoping and technical requirements
2012 IBC Accessibility and Usability for Commercial Buildings 6
Page 1
Graphic Conventions
 Drawings presented today, and in the workbook, use the
following graphic conventions for showing dimensions on
figures. All dimensions are shown in inches above the
measure line with the metric equivalent below.

2012 IBC Accessibility and Usability for Commercial Buildings 7


Page 5
Built Environment
 Physical impairments

8
What are we talking about?

disability
ability
Focus on a person’s ability to have access to places to live,
work and play.
Don’t focus on their disability.

2012 IBC Accessibility and Usability for Commercial Buildings 9


Module 1

Introduction to Accessibility

2012 IBC Accessibility and Usability for Commercial Buildings 10


A Look at Accessibility
 Scope and Technical Requirements of
Accessibility Provisions.
 Coordination with Federal Documents.

2012 IBC Accessibility and Usability for Commercial Buildings 11


Page 7
Disability Definition

“A physical or mental
impairment which substantially
limits one or more of a person’s
major life activities.”

2012 IBC Accessibility and Usability for Commercial Buildings 12


Page 7
2012 IBC - Philosophy 101
Everything must be accessible, and
then allow for a degree of
inaccessibility that is logical and
reasonable.

2012 IBC Accessibility and Usability for Commercial Buildings 13


Page 7
Requirements
 Scoping  Technical
Requirements: Requirements:
 “What, Where  “How”
and How Many”  (ICC/ANSI A117.1-
 (2012 IBC®) 2009)

2012 IBC Accessibility and Usability for Commercial Buildings 14


Page 9
Mainstreaming

2012 IBC Accessibility and Usability for Commercial Buildings 15


Page 9
Coordination Efforts

Federal laws

2012 IBC Accessibility and Usability for Commercial Buildings


Page 11 16
ICC Goals
 Coordinate the building code requirements with
the

2012 IBC Accessibility and Usability for Commercial Buildings 17


Page 11
ICC Goals

2012 IBC Accessibility and Usability for Commercial Buildings 18


Page 11
American’s with Disabilities Act
(ADA) - 1990
 Civil Rights law against discrimination for
persons with disabilities.
 Consists of five areas:
 Title I – Employment
 Title II – Accessibility public transportation and
governmental services
 Title III – Accessibility to all other buildings
 Title IV – Telecommunication
 Title V – Miscellaneous

2012 IBC Accessibility and Usability for Commercial Buildings 19


Page 11
American’s with Disabilities Act
(ADA) - 1990
 Scoping and technical requirements found in:
 Originally in 1991 -
 American’s with Disabilities Act Accessibility Guidelines
(ADAAG).
 Uniform Federal Accessibility Standards (UFAS).
 Currently –
 2010 ADA Standard for Accessible Design
 Previously called the 2004 ADA/ABA Accessibility Guidelines

2012 IBC Accessibility and Usability for Commercial Buildings 20


Page 12
2010 ADA Standard for
Accessible Design
 Dept. of Justice adopted July 23, 2010.
 Published in Federal Registry on Sept. 15, 2010.
 Requirements were mandatory for new
construction started after March 15, 2012.

2012 IBC Accessibility and Usability for Commercial Buildings 21


Page 12
Fair Housing Act (FHA) –
1968 & 1988
 Civil Rights law against discrimination in
housing.
 1968 - no discrimination on the basis
of race, color, religion, sex and national origin.
 1988 - amended to include disabilities and
familial status.

2012 IBC Accessibility and Usability for Commercial Buildings 22


Page 13
Fair Housing Act
 Covers all housing built for first occupancy after
March 13, 1991.

 Scoping and technical requirements found in the


Fair Housing Accessibilities Guidelines (FHAG).

2012 IBC Accessibility and Usability for Commercial Buildings 23


Page 13
2012 IBC Accessibility and Usability for Commercial Buildings 24
Page 13
“Safe Harbor” means…
 that requirements in the document have been
reviewed by HUD and meet or exceed the
building construction requirements in the FHA.

 2009 IBC, 2012 IBC and 2009 ICC A117.1 are


currently under review by HUD.

2012 IBC Accessibility and Usability for Commercial Buildings 25


Page 13
Role of the Code Official

2012 IBC Accessibility and Usability for Commercial Buildings 26


Page 15
Enforcement of Federal
Requirements

Inspection and
Review Mediation
Complaints

Through the courts


2012 IBC Accessibility and Usability for Commercial Buildings 27
Page 15
General Exceptions

28
Collective Reference

2012 IBC Accessibility and Usability for Commercial Buildings 29


Existing Buildings

2012 IBC Accessibility and Usability for Commercial Buildings 30


Employee Work Area

2012 IBC Accessibility and Usability for Commercial Buildings 31


Page 17
Detached Dwellings
2012 IBC Accessibility and Usability for Commercial Buildings 32
Utility Structure
2012 IBC Accessibility and Usability for Commercial Buildings 33
Construction Sites

2012 IBC Accessibility and Usability for Commercial Buildings 34


Raised Area

2012 IBC Accessibility and Usability for Commercial Buildings 35


Limited Access Space

2012 IBC Accessibility and Usability for Commercial Buildings 36


Equipment Spaces

2012 IBC Accessibility and Usability for Commercial Buildings 37


Page 17
Single Occupant Structure

2012 IBC Accessibility and Usability for Commercial Buildings 38


Page 17
Residential R-1
Day Care Facility in a
Single Family Home

2012 IBC Accessibility and Usability for Commercial Buildings 40


Live/Work
Units

2012 IBC Accessibility and Usability for Commercial Buildings 41


Page 17
Detention and
Correctional Facilities
2012 IBC Accessibility and Usability for Commercial Buildings 42
Walk-in Coolers and Freezers
2012 IBC Accessibility and Usability for Commercial Buildings 43
Page 18
Not Exempted Under IBC
Religious Buildings

Private Clubs

2012 IBC Accessibility and Usability for Commercial Buildings 44


Page 18
Special Occupancies
 Group I.
 Group R.
 Assembly seating.
 Self-service storage areas.
 Judicial facilities.

2012 IBC Accessibility and Usability for Commercial Buildings 45


Page 18
Non-accessible Levels
 < 3000 square feet except in:
 Health care providers.
 Multi-tenant mercantile.
 Transportation facilities.
 Items specifically addressed in 1107 and 1108.
 Air traffic control towers.
 Non-public areas with < = 5 occupants.
 Press boxes

2012 IBC Accessibility and Usability for Commercial Buildings 46


Page 19
Press Boxes

2012 IBC Accessibility and Usability for Commercial Buildings 47


Page 19
Existing Buildings
 Maintenance.
 Change of occupancy.
 Addition.
 Alteration.
 Historic buildings.

2012 IBC Accessibility and Usability for Commercial Buildings 48


Page 20
2006 IBC - Philosophy 102
Existing Buildings – Part 1
 When altering an existing building, everything
that is altered must meet new construction
requirements for accessibility.

2012 IBC Accessibility and Usability for Commercial Buildings 49


Page 20
Exceptions
 Type B units.
 Accessible means of egress.
 Technically infeasible.
 When historical significance is adversely
affected.

2012 IBC Accessibility and Usability for Commercial Buildings 50


Page 20
2006 IBC - Philosophy 102
Existing Buildings – Part 2
 If the area being altered contains a primary
function area, the route to that area and any
toilet rooms or drinking fountains that serve that
area must be evaluated for accessibility.

 If they are not accessible, additional


improvements are required.

2012 IBC Accessibility and Usability for Commercial Buildings 51


Page 20-23
Primary Function Area

2012 IBC Accessibility and Usability for Commercial Buildings 52


Page 20-23
Primary Function Area

2012 IBC Accessibility and Usability for Commercial Buildings 53


Page 20-23
Exceptions
 > 20% of the cost of the alteration.

 Elements being altered do not change the


physical configuration or utilization of the space.

 The alteration is to increase accessibility.

2012 IBC Accessibility and Usability for Commercial Buildings 54


Page 20-23
Basis for Technical
Requirements

55
Dimensions
of Adult-Sized Wheelchair

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 56


Page 25
Wheelchair Turning Space

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 57


Page 26
Unobstructed
Forward Reach Limit

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 58


Page 27
Unobstructed
Side Reach Limit

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 59


Page 27
Cane Ranges
and Techniques

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 60


Page 30
Children Requirements
Unobstructed Children’s Reach Ranges
Forward or Ages Ages Ages
Side Reach 3 and 4 5 through 8 9 through 12
High (maximum) 36 in. 40 in. 44 in.
Low (minimum) 20 in. 15 in. 16 in.

2012 IBC Accessibility and Usability for Commercial Buildings 61


Page 30
Module 2

Exterior Accessible Route

2012 IBC Accessibility and Usability for Commercial Buildings 62


Exterior Accessible Route
 Exterior Accessible Routes
 Locations and Elements
 Accessible Parking Spaces
 Locations and Elements
 Passenger Loading Zones
 Curb Ramps
 Location and Access
 Signage.

2012 IBC Accessibility and Usability for Commercial Buildings 63


Page 33
Public Arrival Points

2012 IBC Accessibility and Usability for Commercial Buildings 64


Page 33-36
Public Arrival Points

2012 IBC Accessibility and Usability for Commercial Buildings 65


Page 33-36
Accessible Entrances

2012 IBC Accessibility and Usability for Commercial Buildings 66


Page
Other elements on the site

2012 IBC Accessibility and Usability for Commercial Buildings 67


Page 33-36
Exterior Work Areas

2012 IBC Accessibility and Usability for Commercial Buildings 68


Page 33-36
Minimum Clear Width for a
Single Wheelchair

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 69


Page 38
Accessible Route
Width for Turns

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 70


Page 38
Changes in Elevation

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 71


Page 39
Protruding Objects
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 72


Protruding Objects
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 73


Parking Locations

2012 IBC Accessibility and Usability for Commercial Buildings 74


Page 40
Dispersion by Type

2012 IBC Accessibility and Usability for Commercial Buildings 75


Page 40
Number Required
 Based on number provided.
 Number required per zoning laws.
 Table 1106.1 for general parking.
 2% for Group R-2 and R-3.
 10% at hospitals facilities.
 20% at mobility treatment centers.

2012 IBC Accessibility and Usability for Commercial Buildings 76


Page 41
Dimensions of Parking Spaces
in Parking Lot

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 77


Page 44
Alternative Space

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 78


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 79


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 80


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 81


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 82


Passenger Loading Zones
 Group I-1 and I-2
 Valet parking
 Where provided, they must be accessible

2012 IBC Accessibility and Usability for Commercial Buildings 83


Page 44
Passenger Loading Zones

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 84


Page 44
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 85


Cut-in Curb Ramps

X = 36” minimum in new construction


On existing sites, if landing is <36” then slope of flared sides shall not
exceed 1:12.
For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 86


Page 49
Built-Up Curb Ramps

36” minimum

On existing sites, if landing is <36” then slope of flared sides


shall not exceed 1:12.
For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 87


Page 50
Detectable
Warnings

For SI: I inch = 25.4 mm.

2012 IBC Accessibility and Usability for Commercial Buildings 88


Page 52
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 89


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 90


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 91


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 92


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 93


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 94


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 95


Signage
 Accessible parking
 Entrances

2012 IBC Accessibility and Usability for Commercial Buildings 96


Page 53
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 97


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 98


Module 2 Problem
 Evaluate the accessible
parking and the exterior
accessible route on this
site.

 Might there be different


considerations if this is an
existing site?

2012 IBC Accessibility and Usability for Commercial Buildings 99


Page
Module 3

Accessible Entry vs. Exits

2012 Accessibility and Usability for Commercial Buildings 100


Entrance/Exit
Requirements—Introduction
 Requirements for both entry and egress must be
addressed and the most restrictive applied.

2012 Accessibility and Usability for Commercial Buildings 101


Page 57
Accessible Entry vs. Accessible
Exit
TERM DEFINITION EXAMPLE REQUIRED #

Consists of:
Accessible •Exterior accessible route. 60% of the
Elevator
Entry •Accessible entrances. entrances
•Interior accessible route.

Consists of: 1 with


Accessible
•Exit access via interior
Exit 1 MOE
accessible route.
Exit •Area of refuge/Exit.
Stairway 2 with
•Exit discharge. 2+ MOE

2012 Accessibility and Usability for Commercial Buildings 102


Page 59
Accessible Entry vs. Exits
 Comparison of Requirements.
 Accessible Entrances.
 Accessible Means of Egress.
 Visible and Audible Alarms.

2012 Accessibility and Usability for Commercial Buildings 103


Page 57
Problem
#1
Consider a small
nonsprinklered mercantile
or business with a main
entrance out the front and
a service entrance out the
back.

2012 Accessibility and Usability for Commercial Buildings 104


Page 60
Problem
#1
How many entrances are
required to be accessible?
 One entrance is required
to be accessible (IBC
Section 1105.1)

If one means of egress is


required, how many exits
are required to be
accessible?
 One exit is required to be
accessible (IBC Section
1007.1).

2012 Accessibility and Usability for Commercial Buildings 105


Page 60
Problem
#1
If two means or egress are
required, how many exits
are required to be
accessible?
 Two exits are required to
be accessible (IBC
Section 1007.1).

What are the options if the


exit discharge is not
accessible?
 Options are interior area
of refuge or exterior area
of assisted rescue.

2012 Accessibility and Usability for Commercial Buildings 106


Page 60
Problem
#1
Is there an exception
for sprinklered
buildings?

 No. The requirements


are the same for
sprinklered and non-
sprinklered buildings.

Exterior Area of
Assisted Rescue
2012 Accessibility and Usability for Commercial Buildings 107
Page 60
Problem #2
Picture a large one-story,
unlimited-area building,
with one main entrance
and four required exits
provided around the
perimeter of the store.

How many entrances


Sales Area would be required to be
accessible?

 One entrance is required


to be accessible (IBC
Section 1105.1).

Main Entrance

2012 Accessibility and Usability for Commercial Buildings 108


Page 61
Problem #2
How many exits are required to
be accessible?
 Two exits are required to be
accessible (IBC Section
1007.1).

Which exits would they have to


be? What about travel
distances?
Sales Area  It is the designer’s choice as
to which exit is accessible.
There are no special travel
distance requirements;
however the exit must be
distinct.

Main Entrance

2012 Accessibility and Usability for Commercial Buildings 109


Page 61
Problem #2
If they built a storage area in
the back that included an
Employee employee entrance and
Storage employee break room (greater
Lounge than 50 occupants), how would
that affect entrance and means
of egress requirements?
 At least two accessible
means of egress must be
provided from each space
Sales Area (IBC Section 1107.1).
Therefore, the rear door
must be accessible and
signage must be provided at
the nonaccessible entrances
or exits (IBC Sections
1110.1, 1110.2 and 1110.3).

Main Entrance

2012 Accessibility and Usability for Commercial Buildings 110


Page 61
Problem #3
Consider a banquet facility
with a main lobby/entrance
hall, and a large hall with
moveable partitions.

You could divide the hall into


three banquet rooms, each Moveable Partitions
with an occupant load of
greater than 50 occupants.

Lobby

2012 Accessibility and Usability for Commercial Buildings 111


Page 62
Problem #3
How many entrances are
required to be accessible?
 One accessible entrance is
required (IBC Sections
1104.3 and 1105.1).
Moveable Partitions
How many exits are required
(i.e., from the building, from
each space)?
 Two accessible means of Lobby
egress from each space,
therefore all exits from this
facility must be accessible
(IBC Section 1007.1).

2012 Accessibility and Usability for Commercial Buildings 112


Page 62
Problem #4
In a multistory office building,
the elevator in a central core
provides the accessible route to
the upper floors.

The requirement for two means


of egress from each level is met
by two stair towers located in
opposite corners.

First, assume this building is


five stories and sprinklered
throughout.

Which elements would be


involved in creating the
accessible means of egress?

2012 Accessibility and Usability for Commercial Buildings 113


Page 64
Problem #4
 At least one exit stairway and
the elevator shall serve as part
of the accessible means of
egress (IBC Section 1007.2.1).
 With a sprinkler system the
stairway is exempted from the
48-inch (1219 mm) clear width
and the areas of refuge (IBC
Section 1007.3, Exception 2).
The elevator must have standby
power, but with a sprinkler
system, the area of refuge
would be exempted (IBC
Section 1007.4, Exception 2).
Two way communications must
be provided in the elevator lobby
(IBC Section 1007.8)

2012 Accessibility and Usability for Commercial Buildings 114


Page 64
Problem #4
Second, same layouts, but
assume that this building is two
stories, and not sprinklered.

What are the options for an area


of refuge?
 At stairways, areas of refuge
can be within a stairway
enclosure or immediately
adjacent to the stairway
enclosure.
 At the elevator, standby power
and an area of refuge are
required. However, the fire
department does not like to
use the elevator is low rise
building.

2012 Accessibility and Usability for Commercial Buildings 115


Page 64
Problem #4
Are there any special
signage considerations?
 In addition to the signage at
the areas of refuge, directional
signage must be provided at
the elevator and any
nonaccessible means of
egress (IBC Section 1007.10).
Instructional signage must be
provided at the two way
communication system (IBC
Section 1007.8.2). Tactile
signage is required at
stairways (IBC Sections
1110.3 and 1011.3).

2012 Accessibility and Usability for Commercial Buildings 116


Page 64
Problem #4
What would be the requirements if a building had elevators in more than
one location?
 The location chosen for the two-way communication system is normally based on the
fact that people will try and go out the way they came in. Therefore, if more than one
elevator bank serves as part of an accessible route into a space, two way
communication should be provided in each elevator lobby.
 In buildings where the elevators are used as part of the accessible means of egress,
the question would be if the elevators were zoned. An elevator with standby power
must be accessible from all floors. Therefore, standby power may need to be supplied
to different banks if they serve different floors. Standby power must be switchable
between elevators in the same bank. If the elevators serve as a route into the space,
but do not serve as part of the accessible means of egress, they should have
appropriate directional signage.

2012 Accessibility and Usability for Commercial Buildings 117


Page 64
Accessible
Entrance

2012 Accessibility and Usability for Commercial Buildings 118


Page 65
Required Building Entrances
 Special entrances – at least one:
 Parking garages
 Tunnels
 Elevated walkways
 Restricted
 Inmates or detainees
 Public entrances – 60%.

2012 Accessibility and Usability for Commercial Buildings 119


Page 65
Required Individual Entrances
 Tenants – at least one

 Accessible Group I and R dwelling and sleeping


units – at least one

2012 Accessibility and Usability for Commercial Buildings 120


Page 65
Exceptions
 Areas not required to be accessible.

 Doors that serve as means of egress only.

 Service entrances that are not the only entrance


to a tenant.

2012 Accessibility and Usability for Commercial Buildings 121


Page 65
Interior Routes

Elevator

Horizontal surfaces

Ramps

Platform
lifts
2012 Accessibility and Usability for Commercial Buildings 122
Page 67
Interior Routes
 Connect accessible elements.
 Except within dwelling units the only route
should not be through:
 Kitchens
 Storage rooms
 Toilet or bathing rooms
 Closets
 The accessible route into the space must allow
access unassisted.

2012 Accessibility and Usability for Commercial Buildings 123


Page 67
Entrance/Exit Requirements —
Accessible Means of Egress
 Elements of Accessible Means of Egress

2012 Accessibility and Usability for Commercial Buildings 124


Page 72
Elements of Accessible MOE
 Exit access — all elements of interior accessible
route.

 Exit — enclosed exit stairways, elevators, area


of refuge, horizontal exits, exit doors.

 Exit discharge — exterior accessible route.

2012 Accessibility and Usability for Commercial Buildings 125


Page 73
Accessible Means of Egress
 One if one MOE required.
 Two if two or more MOE required.
 If five stories or higher, at least one via elevator
with standby power.

2012 Accessibility and Usability for Commercial Buildings 126


Page 74
Exceptions

 Existing buildings

 Areas not required to be accessible

2012 Accessibility and Usability for Commercial Buildings 127


Page 74-75
Special Consideration
 Mezzanines.
 Wheelchair spaces in Assembly seating with
sloped or stepped floors.
 Areas accessed only by platform lifts.

2012 Accessibility and Usability for Commercial Buildings 128


Page 74-75
Accessible Exit Access

Ramps

Horizontal surfaces

Platform lifts with


standby power

2012 Accessibility and Usability for Commercial Buildings 129


Page 76
Accessible Exit
Exit Stairs

Exit Door

Horizontal Exit Elevator with standby power


2012 Accessibility and Usability for Commercial Buildings 130
Page 76
Exit Doors
 Maneuvering clearances.
 Zero level entry.
 Clear width.
 Hardware.
 Vestibules.

2012 Accessibility and Usability for Commercial Buildings 131


Page 76
Elevators
 Required in buildings four or more stories above
or below the level of exit discharge.
 Standby power.
 Accessed from an area of refuge.

2012 Accessibility and Usability for Commercial Buildings 132


Page 77
Elevator
 How to measure
height
 Standby-power for
assisted
evacuation by
emergency
responders – not
self evacuation

133
Exceptions to IBC 1007.4
 Areas of refuge are not required if the elevator is
accessed from a horizontal exit.
 Areas of refuge are not required in open parking
garages.
 Areas of refuge are not required when a building
sprinklered with an NFPA13 or NFPA13R system.
 Areas of refuge are not required when the elevator is not
in a shaft.
 Areas of refuge are not required in smoke protected
seating.

2012 Accessibility and Usability for Commercial Buildings 134


Page 77
Exceptions to IBC 1007.4
 Standby power is not required in buildings with
horizontal exits (i.e., defend in place scenarios like a
hospital)
 Standby power is not required when ramps are proved
from all floor levels (i.e., sports facilities or parking
garage)

2012 Accessibility and Usability for Commercial Buildings 135


Page 77
Stairways
 Exit stairway.
 48” clear width.
 Accessed from area
of refuge.

Fireman’s carry

2012 Accessibility and Usability for Commercial Buildings 136


Page 78
Exceptions to IBC 1007.3
 Areas of refuge are not required if the stairway is
accessed from a horizontal exit.
 Areas of refuge are not required in buildings with
an NFPA13 or NFPA 13R sprinkler system.
 Area of refuge is not required in open parking
garages.
 Areas of refuge are not required in smoke
protected seating.
 Areas of refuge are not required in Group R-2.

2012 Accessibility and Usability for Commercial Buildings 137


Page 78
Exceptions to IBC 1007.3
 48” clear width is not
required in buildings with a
NFPA13 or NFPA 13R
sprinkler system.
 48” clear width is not
required if the stairway is
accessed from a horizontal
exit.

2012 Accessibility and Usability for Commercial Buildings 138


Page 78-79
Horizontal Exit

2012 Accessibility and Usability for Commercial Buildings 139


Page 79
Area of Refuge
 Accessed by an accessible route.
 Separated by a smoke barrier.
 Direct access to an exit stairway, elevator with
emergency power or accessible exit.
 A horizontal exit is an alternative for and area of
refuge.

2012 Accessibility and Usability for Commercial Buildings 140


Page 81-82
Areas of Refuge
 30” x 48” space.
 One space for every
200 occupants.
 Access to a space
may be through one
other space.
 Do not block general
means of egress
path.

2012 Accessibility and Usability for Commercial Buildings 141


Page 81-82
Area of Refuge
 Two way emergency
communication
system
 Identification
 Instructional signage

2012 Accessibility and Usability for Commercial Buildings 142


Page 81-82
How They Work

143
Figure courtesy of District of Columbia government website
Signage
 At non-accessible exits
and
 At elevators indicating the
location of accessible
means of egress.
 Areas of refuge
 Exterior areas of rescue
assistance.
Area of
 Tactile signage at exit and
exit discharge doors. Refuge

2012 Accessibility and Usability for Commercial Buildings 144


Page 82
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 145


Two-way Communication
 Variety of options
 Allow for communication and feedback between
emergency responders and people who need
assistance
 In areas of refuge in non-sprinklered buildings
 At elevator lobbies in sprinklered buildings

2012 Accessibility and Usability for Commercial Buildings 146


Page 82
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 147


Accessible Exit Discharge

2012 Accessibility and Usability for Commercial Buildings 148


Page 84
Accessible Exit Discharge
 If exit discharge is not accessible:
 Steps
 Steep site
 Snow
 Interior area of refuge, or
 Exterior area of rescue assistance.
 No exceptions for sprinklered buildings.

2012 Accessibility and Usability for Commercial Buildings 149


Page 84
Exterior Area of Assisted Rescue

150
Exterior Area of Assisted Rescue

151
Audible and Visible alarms

 Where required by Section 907.


 Installed in accordance with NFPA 72.
 Manual fire alarm boxes must be accessible.

2012 Accessibility and Usability for Commercial Buildings 152


Page 88
Visible Alarms
 All public spaces.
 All common spaces.
 Group I-1 and
R-1 units per
Table 907.9.1.3.
 Future expansion for:
 Individual employee
work areas.
 Group R-2 units.

2012 Accessibility and Usability for Commercial Buildings 153


Page 88
Module 3 Problem
 How many exterior
doors are required?
 Which doors will most
likely serve as the
entrances, and how
many are required to
be accessible?
 Assuming the
occupant load is 750,
how many doors will
serve as exit doors,
and how many are
required to be
accessible?

2012 Accessibility and Usability for Commercial Buildings 154


Page 90
Module 4

Interior Accessible Route


Elements

2012 Accessibility and Usability for Commercial Buildings 155


Interior Accessible Route
 Technical requirements.
 Doors.
 Elevators and Platform Lifts.
 Stairways and Ramps.

2012 Accessibility and Usability for Commercial Buildings 156


Page 91
Minimum Clear Width for Single
Wheelchair

2012 Accessibility and Usability for Commercial Buildings 157


Page 91-92
Accessible Route Width for
Turns

2012 Accessibility and Usability for Commercial Buildings 158


Page 91-92
Changes in Elevation

2012 Accessibility and Usability for Commercial Buildings 159


Page
Protruding Objects Along
A Walking Surface

2012 Accessibility and Usability for Commercial Buildings 160


Page 94
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 161


Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 162


Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 163


Overhead Protruding Objects

2012 Accessibility and Usability for Commercial Buildings 164


Page 94
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 165


Doors

Door Size
1008.1.1

Doors in a Series
1008.1.8

Door Swing
1008.1.2

2012 Accessibility and Usability for Commercial Buildings 166


Page 96
Door Opening Clearances

2012 Accessibility and Usability for Commercial Buildings 167


Page 96
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 168


Hardware

2012 Accessibility and Usability for Commercial Buildings 169


Page 103
Maneuvering Clearances

Front
Front Approach, Approach,
Pull Side Push Side

2012 Accessibility and Usability for Commercial Buildings 170


Page 99
Maneuvering Clearances

2012 Accessibility and Usability for Commercial Buildings 171


Page 99
Door Surface

Bottom 10” clear of obstructions


2012 Accessibility and Usability for Commercial Buildings 172
Page 102
Maneuvering Clearance

2012 Accessibility and Usability for Commercial Buildings 173


Page 99
Maneuvering Clearance
 Required at power
assist doors
 Not required a low-
power automatic
doors and fully
automatic doors

2012 Accessibility and Usability for Commercial Buildings 174


Page 99
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 175


Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 176


Vestibules

2012 Accessibility and Usability for Commercial Buildings 177


Page 101
Vestibules

2012 Accessibility and Usability for Commercial Buildings 178


Page 101
Elevators
 ASME A17.1.
 ICC A117.1.
 Permitted to serve as part
of the accessible route
anywhere.
 5 story buildings or
higher:
 Standby power for
accessible MOE.
 One sized for a stretcher.

2012 Accessibility and Usability for Commercial Buildings 179


Page 111
Elevator 80 MIN
2030
68 MIN
1725

Car Sizes

54 MIN
51 MIN

54 MIN
1370
1295

51 MIN
1370

1295
 Access to
controls. 42 MIN 36 MIN
915
 60” turning
1065
(a) Centered Door Loc ation (b) Off-Centered Door Loc ation
54 MIN 60 MIN
1525
circle not 1370

required.
80 MIN

60 MIN
2030

1525
36 MIN 36 MIN
915 915
(c ) Any Door Loc ation (d) Any Door Loc ation

2012 Accessibility and Usability for Commercial Buildings 180


Page 112
LULAs
 ASME A17.1.
 ICC A117.1.
 Application limited by
product:
 Limited capacity.
 25’ max. travel.
 Slow speed.
 * LULA Limited
Use/Limited
Application

2012 Accessibility and Usability for Commercial Buildings 181


Page 113
LULA Car Size

2012 Accessibility and Usability for Commercial Buildings 182


Page 113
Platform Lifts
 ASME A18.1.
 ICC A117.1.
 Permitted anywhere in
existing buildings.
 Limited application in
new construction.

2012 Accessibility and Usability for Commercial Buildings 183


Page 113-114
Platform Lifts
 Performing areas.
 Wheelchair spaces in assembly seating.
 Restricted spaces with <6 occupants.
 Within dwelling and sleeping units.
 Outdoor dining areas in Group A-5.

2012 Accessibility and Usability for Commercial Buildings 184


Page 113
Platform Lifts
 Areas in courtrooms.
 Amusement rides.
 Play structures.
 Team or player seating.
 Existing exterior constraints.
 This location cannot also serve as part of an
accessible means of egress.

2012 Accessibility and Usability for Commercial Buildings 185


Page 113-114
Platform Lifts

2012 Accessibility and Usability for Commercial Buildings 186


Page 114
Types

2012 Accessibility and Usability for Commercial Buildings 187


Page 114
When must doors be automatic?

2012 Accessibility and Usability for Commercial Buildings 188


Page 114
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 189


Good or Bad?

Platform lift in the Louvre in Paris!


2012 Accessibility and Usability for Commercial Buildings 190
Controls
 Key access no longer
required by the
standard.

2012 Accessibility and Usability for Commercial Buildings 191


Page 114
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 192


Stairways
 Not part of the accessible route into building.
 Part of an accessible means of egress out of
building – assisted utilization.
 Mainstreamed requirements.
 Safety provisions for persons with mobility and
visually impairments addressed in IBC.

2012 Accessibility and Usability for Commercial Buildings 193


Page 115
11 inches min. tread depth
Rise height 4” to 7”
½” max beveling of nosings

Handrails
1009. 15 & 1012.
Handrail
Extensions
1012.5

34” to 38” height


1012.2

Stairway width
1007.3 or 1009.1
2012 Accessibility and Usability for Commercial Buildings 194
Handrail Extension

2012 Accessibility and Usability for Commercial Buildings 195


Page 115
Good or Bad?
 Solid tread and risers?

2012 Accessibility and Usability for Commercial Buildings 196


Good or Bad?
 Handrail extensions?

2012 Accessibility and Usability for Commercial Buildings 197


Ramps
 >1:20 slope.
 1:12 slope maximum on accessible routes.
 1:8 slope maximum in assembly that are
not accessible routes.
 1:8 slope maximum for ramps that are not
means of egress.
 Existing buildings with 6” or less rise.

2012 Accessibility and Usability for Commercial Buildings 198


Page 122
Ramps
 Change in level
 Surfaces
 Cross slope
 Minimum width
 Maximum rise
 Adequate landings

2012 Accessibility and Usability for Commercial Buildings 199


Page 123
Ramp Landings

2012 Accessibility and Usability for Commercial Buildings 200


Page 123
Ramp Landings

Ramp landing adjacent to lockable doors


2012 Accessibility and Usability for Commercial Buildings 201
Page 123
Edge Protection, Handrails & Guards

>30” drop off No drop off

Curb or rail edge protection with <= 30” drop off


2012 Accessibility and Usability for
Commercial Buildings 202
Page 127
Good or Bad?
2012 Accessibility and Usability for Commercial Buildings 204
2012 Accessibility and Usability for Commercial Buildings 205
2012 Accessibility and Usability for Commercial Buildings 206
2012 Accessibility and Usability for Commercial Buildings 207
2012 Accessibility and Usability for Commercial Buildings 208
2012 Accessibility and Usability for Commercial Buildings 209
2012 Accessibility and Usability for Commercial Buildings 210
Good or Bad?

2012 Accessibility and Usability for Commercial Buildings 211


Module 4 Problem

Are the means of


egress elements
shown in this plan
accessible?
Identify any
noncompliance.

2012 Accessibility and Usability for Commercial Buildings 212


Page 130
Module 5

Building Features and


Facilities

2012 IBC Accessibility and Usability for Commercial Buildings 213


Building Features and Facilities
 Plumbing Facilities.
 Customer Service.
 Other Features.

2012 IBC Accessibility and Usability for Commercial Buildings 214


Page 133
Bathrooms
 Type A and Type B unit bathrooms are not
addressed in this class.
 All other bathrooms will be covered here:
 Public bathrooms
 Private bathrooms
 Accessible dwelling and sleeping units
 Child size bathrooms

2012 IBC Accessibility and Usability for Commercial Buildings 215


Page 134
Bathrooms
 Required fixtures per IPC.
 Designers choice for how required fixtures are
separated:
 Multi-stall bathrooms
 Single occupant bathrooms
 All bathrooms must be accessible per Chapter 6
of ICC A117.1.

2012 IBC Accessibility and Usability for Commercial Buildings 216


Page 134
Exceptions
 Accessed through a private office.
 Non-accessible dwelling or sleeping units.
 50% of clustered single occupant bathrooms.
 When only one urinal is provided in a bathroom,
that urinal is not required to be accessible.
 Critical care or Intensive care.

2012 IBC Accessibility and Usability for Commercial Buildings 217


Page 134
Bathrooms
 One of each type of fixture provided in each
bathroom:
 Water closets
 Lavatories
 Urinals
 Bathtubs
 Showers
 When 6 or more water closets and/or urinals are
provided in a room, an ambulatory stall is
required.
2012 IBC Accessibility and Usability for Commercial Buildings 218
Page 135
Sinks/Lavatories
 Lavatories are for bathing purposes.
 Sinks are typically a work sink.
 5% constructed with front approach.
 When 6 or more lavatories are provided in a
room, a lavatory with an enhances reach range
faucet is required.

2012 IBC Accessibility and Usability for Commercial Buildings 219


Page 135
Exceptions
 Non-accessible:
 Part of individual work stations
 Mop or service sinks
 Limited accessibility:
 Sinks for children’s use
 Kitchenettes permitted to have side approach

2012 IBC Accessibility and Usability for Commercial Buildings 220


Page 135
Family Use/Assisted Use
Accessible Toilet Rooms
 Mercantile or assembly facilities; and
 6 or more required water closets;
 1 unisex toilet room required;
 Not an exception for accessible fixtures in the
men’s and women’s toilet rooms.

2012 IBC Accessibility and Usability for Commercial Buildings 221


Page 135
Family Use/Assisted Use
Accessible Toilet Rooms
 Family Use toilet room counts toward required
fixture count.
 Designers choice to take from men’s or women’s
fixture count.
 Room must include one water closet and one
lavatory.
 Room may include one urinal.
 Room must include any amenities provided in
men’s and women’s toilet rooms.

2012 IBC Accessibility and Usability for Commercial Buildings 222


Page 136
Family Use /Assisted Use
Accessible Bathing Rooms
 Recreational facilities where bathing rooms are
provided.
 One family use bathing room is required.
 Exception:
 If only one shower is provided in men’s and women’s
bathing room.

2012 IBC Accessibility and Usability for Commercial Buildings 223


Page 135
Family Use/Assisted Use
Accessible Bathing Rooms
 Room must include one water closet, one
lavatory and one bathing fixture.
 Bathing fixture may be bathtub, transfer shower,
roll-in shower or combination transfer/roll-in
shower.
 Room must include any amenities provided in
men’s and women’s bathing rooms.

2012 IBC Accessibility and Usability for Commercial Buildings 224


Page 136
Purpose
 Person with mobility impairment may require
assistance.
 Families with small children.
 Persons with temporary disabilities may require
assistance.
 Customer friendly.

2012 IBC Accessibility and Usability for Commercial Buildings 225


Page 136
Location
 Maximum of 500 feet and one story travel from
the men’s and women’s rooms.
 In transportation facilities, travel shall not be
through a security checkpoint.

2012 IBC Accessibility and Usability for Commercial Buildings 226


Page 136
Additional
Requirements
 Privacy locks
 Signage

2012 IBC Accessibility and Usability for Commercial Buildings 227


Page 136
Clear Floor Space at Water
Closet

2012 IBC Accessibility and Usability for Commercial Buildings 228


Page 137
Side Transfer

2012 IBC Accessibility and Usability for Commercial Buildings 229


Page 137
1991 ADAAG – Fig. 28

Clear Floor Space at Water Closets


2012 IBC Accessibility and Usability for Commercial Buildings 230
Page 137
Single Occupant Toilet Rooms
 60” turning space required in the room
 A door can swing over the space where
someone sits to use the lavatory, toilet or urinal
provided a 30” x 48” space is provided past the
swing of the door
 A fixture cannot overlap the clear floor space of
another fixture

2012 IBC Accessibility and Usability for Commercial Buildings 231


Page 137
Examples

2012 IBC Accessibility and Usability for Commercial Buildings 232


Page 138
Water Closet: Side View

2012 IBC Accessibility and Usability for Commercial Buildings 233


Page 140
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 234


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 235


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 236


Children’s Water Closets
 See the Adult/Child comparison chart in the
workbook.

Advisory Specifications for Water Closets Serving Children Ages 3 -12


Age 3 & 4 Age 5-8 Age 9-12
Water closet centerline 12” 12”-15” 15”-18”
Toilet seat height 11”-12” 12”-15” 15”-17”
Grab bar height 18”-20” 20”-25” 25”-27”
Dispenser height 14” 14”-17” 17”-19”

2012 IBC Accessibility and Usability for Commercial Buildings 237


Page 146
Multi-stall Toilet Rooms
 60” turning space required in the room.
 A door cannot swing over the space where
someone sits to use the lavatory or urinal.
 A fixture cannot overlap the clear floor space of
another fixture.
 Stall size limits in Table 604.9.3.1.
 The configurations do not change for minimum size
stalls, however the table allows for new options for
larger stalls.

2012 IBC Accessibility and Usability for Commercial Buildings 238


Page 137
Multi-stall Toilet Rooms
 The stall and door arrangement will not change for the
minimum size stall, however, the table does address
door location options for larger size stalls.

2012 IBC Accessibility and Usability for Commercial Buildings 239


Page 137
Wheelchair Accessible Toilet
Stall: Door Swings In

2012 IBC Accessibility and Usability for Commercial Buildings 240


Page 142
Wheelchair Accessible Toilet
Stall: Door Swings Out

2012 IBC Accessibility and Usability for Commercial Buildings 241


Ambulatory Accessible Stall

2012 IBC Accessibility and Usability for Commercial Buildings 242


Page 143
Multi-stall Toilet Rooms

2012 IBC Accessibility and Usability for Commercial Buildings 243


Page 137
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 244


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 245


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 246


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 247


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 248


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 249


Urinals
 Rim height
 Clear floor space
 Alcove
 Flush controls

2012 IBC Accessibility and Usability for Commercial Buildings 250


Page 147
Lavatories & Sinks
 Scoping
 5% in each room
 When 6 or more, then
1 with enhanced reach
range
 Exceptions for sinks
that are part of a work
station, mop sinks and
service sinks.

2012 IBC Accessibility and Usability for Commercial Buildings 251


Page 148
Lavatories & Sinks
 Technical
 Height
 Clearance
 Clear floor space
 Pipe protection
 Controls

2012 IBC Accessibility and Usability for Commercial Buildings 252


Page 148
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 253


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 254


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 255


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 256


Good or Bad?
 Lavatories with
enhanced reach range
includes water and
soap controls (A117.1
606.5).
 Room requirements
include towel
dispensers or hand
dryers (A117.1 606.7).
 Other elements covered
by operable part
requirements.

2012 IBC Accessibility and Usability for Commercial Buildings 257


Page149
Bathtubs or Shower
 Minimum dimensions for showers
 Clearances/approach
 Seats
 Grab bars
 Controls
 Shower unit
 Enclosures/doors
 Thresholds

2012 IBC Accessibility and Usability for Commercial Buildings 258


Page 151
Bathtub Without Permanent Seat

2012 IBC Accessibility and Usability for Commercial Buildings 259


Page 152
Bathtub With Permanent Seat

2012 IBC Accessibility and Usability for Commercial Buildings 260


Page 152
Transfer Shower

2012 IBC Accessibility and Usability for Commercial Buildings 261


Page 153
Roll-in Shower

2012 IBC Accessibility and Usability for Commercial Buildings 262


Page 153
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 263


Good or Bad?
 Hospital patient
bathroom with toilet,
lavatory and roll-in
shower.

2012 IBC Accessibility and Usability for Commercial Buildings 264


Good or Bad?
 Accessible hotel
room

2012 IBC Accessibility and Usability for Commercial Buildings 265


Drinking Fountains (Scoping)
 50% of drinking fountains provided on each floor
configured for persons using wheelchairs.
 50% of drinking fountains provided on each floor
configured for standing persons.
 Exception for drinking fountains sized for
children

2012 IBC Accessibility and Usability for Commercial Buildings 266


Page 155
Good or Bad?
 One water supply, but
bowls will serve two
persons.
 The dog fountain
exceeds code.

2012 IBC Accessibility and Usability for Commercial Buildings 267


Drinking Fountains (Technical)
 Clear floor
space/approach
 Protruding objects
 Operable parts
 Spout location
 Water flow

2012 IBC Accessibility and Usability for Commercial Buildings 268


Page 155
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 269


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 270


Good
or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 271


Good
or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 272


Dressing Rooms (Scoping)
 5% minimum.
 At least one of each group.

2012 IBC Accessibility and Usability for Commercial Buildings 273


Page 157
Dressing Rooms (Technical)
 Turning circle.
 Bench.
 Same amenities as in
other dressing rooms.

2012 IBC Accessibility and Usability for Commercial Buildings 274


Page 158
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 275


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 276


Locker Rooms
 All locker rooms accessible.
 5% of lockers.
 Provide accessible bench.

2012 IBC Accessibility and Usability for Commercial Buildings 277


Page 160
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 278


Benches
 Against a wall or with a
back for support
 Sized to allow for
transfer and for a person
to raise their legs onto
the bench to aid in
dressing and undressing
 Should be bolted down
or very stable to
minimize the chance of
tipping

2012 IBC Accessibility and Usability for Commercial Buildings 279


Page 159
Transfer to a Bench
 Recommended to ease transfer

2012 IBC Accessibility and Usability for Commercial Buildings 280


Page 160
Built-in Counters
 Check out aisles.
 Table 1109.12.2 based on number provided.
 Sales and service counters.
 At least on of each type.

2012 IBC Accessibility and Usability for Commercial Buildings 281


Page 162
Check-out Counters –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 282


Check-out Counters –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 283


Service Window –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 284


Service Window –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 285


Service Window –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 286


Service Window –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 287


Service Window –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 288


Service Window –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 289


Built-in Counters
 Built-in counters and work surfaces
 5% or work surfaces.
 5% of dining surfaces.

 Food service lines:


 All cafeteria style lines accessible
 50% of self service areas.

 Queue and waiting lines:


 All that serve accessible elements.

2012 IBC Accessibility and Usability for Commercial Buildings 290


Page 164
Built-in Work Surface –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 291


Food Service Line or Service
Window – Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 292


Food Service –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 293


Food Service Lines –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 294


Queue lines – Good or Bad?

2012 IBC Accessibility and


295
Usability for Commercial Buildings
Queue & Waiting Line -
Options

2012 IBC Accessibility and Usability for Commercial Buildings 296


Page 164
Storage
 At least one of each type in accessible spaces:
 Cabinets
 Closets
 Drawers
 Mail boxes
 5% of lockers.
 Display shelves must be on an accessible route,
but not within reach ranges.

2012 IBC Accessibility and Usability for Commercial Buildings 297


Page 166
Storage Shelves and Closets

2012 IBC Accessibility and Usability for Commercial Buildings 298


Page 166
Lockers – Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 299


Storage –
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 300


Storage – Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 301


Operable Parts
 All operable parts
within accessible
spaces and intended
for occupant usage.

2012 IBC Accessibility and Usability for Commercial Buildings 302


Page 168
Control Reach Limitations

1994 ADAAG ICC A117.1 and 2010 Standard


2012 IBC Accessibility and Usability for Commercial Buildings 303
Page 168
Windows
 Accessible units in Groups I-1, I-2, R-1, R-2 and
R-4.
 When required for ventilation or emergency
escape.
 At least one in each room.
 Exception:
 Kitchens
 Bathrooms

2012 IBC Accessibility and Usability for Commercial Buildings 304


Page 168
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 305


Module 5 Problem
 Assuming elevations
of fixtures and other
elements are correct;
does the toilet room
shown in this plan
meet the requirements
for accessibility?

2012 IBC Accessibility and Usability for Commercial Buildings 306


Page 170
Module 6

Special Occupancies
Requirements

2012 IBC Accessibility and Usability for Commercial Buildings 307


Special Occupancies
Requirements
 Fixed assembly seating.
 Recreational facilities.
 Dining areas.
 Self-service storage facilities.
 Judicial facilities.

2012 IBC Accessibility and Usability for Commercial Buildings 308


Page
Assembly Seating - Fixed

2012 IBC Accessibility and Usability for Commercial Buildings 309


Page 171
Assembly Seating - Fixed

2012 IBC Accessibility and Usability for Commercial Buildings 310


Page 171
Number of Spaces
 Fixed seats provided.
 Table 1108.2.2.1.
 Luxury boxes, club boxes or suites.
 Each box based on Table 1108.2.2.1.
 Other box seats.
 20% of total box seats based on Table 1108.2.2.1.
 Lawn seating.
 Team seating.

2012 IBC Accessibility and Usability for Commercial Buildings 311


Page 172
Dispersion
 Access to services.
 Integration.
 Different levels.
 Exceptions:
 Balconies in religious facilities with <25% of the total
seats.
 Balconies in assembly with both <300 seats and
<25% of the total seats.

2012 IBC Accessibility and Usability for Commercial Buildings 312


Page 175
Dispersion
 Dispersion
 Line of Sight – standing or seated spectators
 Horizontal (side-to-side)
 Vertical (front-to back)
 Type (seating type or services)

2012 IBC Accessibility and Usability for Commercial Buildings 313


Page 175
Dispersion

 Number of
wheelchairs spaces
(IBC Table
1108.2.2.1)
 Number of wheelchair
space locations (ICC
A117.1 Table 802.10)
‘Wheelchair space locations’ include the companion seat
and can include multiple wheelchair spaces.

2012 IBC Accessibility and Usability for Commercial Buildings 314


Page 175
Wheelchair Space
 Adjacent companion seat.
 Size dependent on approach and if 1 or 2
wheelchair spaces.
 1:48 maximum slope.
 Provided on accessible route.

2012 IBC Accessibility and Usability for Commercial Buildings 315


Page
Wheelchair Space – Size and
Access

2012 IBC Accessibility and Usability for Commercial Buildings 316


Page
Wheelchair Space – Size and
Access

2012 IBC Accessibility and Usability for Commercial Buildings 317


Page 174
Wheelchair Space
 The wheelchair space
must have should
alignment with the
companion seat to
allow interaction.

2012 IBC Accessibility and Usability for Commercial Buildings 318


Page 174
Accessible Route Requirements
 1:12 maximum slope.
 Guards at drop-offs.
 Platform lifts for entry and exit.
 Common path of travel for means of egress.

2012 IBC Accessibility and Usability for Commercial Buildings 319


Page 174
Line of Sight
 Looking over the heads of seated
spectators

2012 IBC Accessibility and Usability for Commercial Buildings 320


Page 175
Line of Sight
 Looking between the heads of seated
spectators

2012 IBC Accessibility and Usability for Commercial Buildings 321


Page 175
Line of Sight
 Looking over the heads of standing
spectators

2012 IBC Accessibility and Usability for Commercial Buildings 322


Page 175
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 323


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 324


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 325


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 326


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 327


Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 328


Designated Aisle Seats
 5% of all aisle seats.
 Best design practice:
 Located along
accessible route.
 Folding or retractable
armrests when adjacent
seating has armrests.

2012 IBC Accessibility and Usability for Commercial Buildings 329


Page 178
Assistive Listening System
 Where audible communications are integral to
the use of the space; and
 An audio amplification system is provided.

2012 IBC Accessibility and Usability for Commercial Buildings 330


Page 180
Assistive Listening System
 Number based on IBC Table 1108.2.5.1.
 Some devices hearing-aid compatible.
 Signage.

2012 IBC Accessibility and Usability for Commercial Buildings 331


Page 180
Text Messaging
 Stadiums, arenas and
grandstands.
 With audible public
announcements.
 Equivalent text
messages must be
provided.

2012 IBC Accessibility and Usability for Commercial Buildings 332


Page 181
Performance Areas
 Access to all performing areas:
 Stage
 Orchestra pit
 Choir loft
 Speaker’s platform
 Access to all supporting spaces.
 Exception for catwalks.

2012 IBC Accessibility and Usability for Commercial Buildings 333


Page 182
Recreational Areas
 Access to recreational areas.
 Exceptions:
 Raised areas for refereeing, judging or scoring
 Animal containment
 Raised boxing or wrestling rings
 95% of bowling lanes

2012 IBC Accessibility and Usability for Commercial Buildings 334


Page 184
Areas of Sports Activity
 That portion of a room or space where the play
or practice of a sport occurs

2012 IBC Accessibility and Usability for Commercial Buildings 335


Amusement Rides
 Route to the ride
 Transfer space or
wheelchair space on
the ride

2012 IBC Accessibility and Usability for Commercial Buildings 336


Amusement Rides
 Exceptions:
 Mobile rides
 Controlled by rider
 Primarily for children
an assisted by adults
 No ride seats

2012 IBC Accessibility and Usability for Commercial Buildings 337


Recreational Boating and
Fishing
 Access to docks
 Access to a
percentage of the
slips
 Allowances for
changes in water
level
 Coordination with
barriers and guards

2012 IBC Accessibility and Usability for Commercial Buildings 338


Exercise Equipment
 Space for transfer or
to use at least one of
each type of machine
 Not intended to
change machines

2012 IBC Accessibility and Usability for Commercial Buildings 339


Golf
 Access to course
using an accessible
golf cart
 Access to driving
range, practice
greens, bag drop off

2012 IBC Accessibility and Usability for Commercial Buildings 340


Miniature Golf
 Access to at least
50% of holes
 Route on or adjacent
to the holes

2012 IBC Accessibility and Usability for Commercial Buildings 341


Play areas
 Percentage of ground
level and raised
components on a
route via ramp or
transfer steps
 Access to soft
contained play
structures

2012 IBC Accessibility and Usability for Commercial Buildings 342


Pools
 Access to pools
based on types and
size
 Options for type of
entry
 Exceptions:
 Diving boards
 Slides
 Catchment pools

2012 IBC Accessibility and Usability for Commercial Buildings 343


Shooting Facilities
 A turning space at
one station in each
type of shooting
facility

2012 IBC Accessibility and Usability for Commercial Buildings 344


Assembly Seating - Dining

2012 IBC Accessibility and Usability for Commercial Buildings 345


Page 190
Dining Areas
 All dining areas accessible.
 Exceptions:
 Mezzanines with <25% of the total seating.
 Sports facilities with tiered dining, at least 25% of the
seating area must be accessible.

2012 IBC Accessibility and Usability for Commercial Buildings 346


Page 190
Fixed Tables and Chairs
 5% of the seating and standing spaces must be
accessible.
 Distributed throughout the facility.

2012 IBC Accessibility and Usability for Commercial Buildings 347


Page 191
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 348


Self-service Storage

2012 IBC Accessibility and Usability for Commercial Buildings 349


Page 193
Self-service Storage
 <=200 units, 5% accessible.
 >200 units, 10 units plus 2% accessible.
 Dispersed by type.
 Not required to dispersed by location.

2012 IBC Accessibility and Usability for Commercial Buildings 350


Page 193
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 351


Judicial Facilities

2012 IBC Accessibility and Usability for Commercial Buildings 352


Page 195
Courtrooms
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 353


Courtrooms
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 354


Holding Cells
 At least one central holding cell for each
type provided.
 At least one court-floor holding cell for
each type provided.

2012 IBC Accessibility and Usability for Commercial Buildings 355


Page 199
Visiting Areas
 5% of the spaces for detainees.
 Exception for areas not serving accessible holding
cells.
 5% of the spaces for visitors.
 At least one cubical accessible on both sides.
 At least one of each type of security partition or
communication system.

2012 IBC Accessibility and Usability for Commercial Buildings 356


Page 199
Good or Bad?

2012 IBC Accessibility and Usability for Commercial Buildings 357


Module 6 Problem
 The following is a plan
of a nightclub. Assume
the rectangular tables
and bar have built-in
seating and the round
tables are loose
seating.

 What are some of the


places you would look
for accommodations for
accessibility?

2012 IBC Accessibility and Usability for Commercial Buildings 358


Page 200
Module 8

Existing Structures

2012 IBC Accessibility and Usability for Commercial Buildings 359


Existing Buildings
 Maintenance.
 Change of occupancy.
 Addition.
 Alteration.
 Historic buildings.

2012 IBC Accessibility and Usability for Commercial Buildings 360


Page 236
Alterations
 Alterations must meet new construction requirements,
-or-
 If you touch it – fix it,
 If the area being altered contains a primary function
area, the route to that area and including any toilet
rooms or drinking fountains that serve that area must be
evaluated for accessibility.
 If they are not accessible, additional improvements are
required.

2012 IBC Accessibility and Usability for Commercial Buildings 361


Page 236
Alterations - Exceptions
 Technically infeasible.
 Adversely affect historic character.
 Type B dwelling units.
 Accessible means of egress.

2012 IBC Accessibility and Usability for Commercial Buildings 362


Page 236
Technically Infeasible
 Alteration or removal of major structural
member.

2012 IBC Accessibility and Usability for Commercial Buildings 363


Page 236
Primary Function Area
 A major activity for which the facility is intended.
 Excluding areas such as:
 Mechanical room or boiler room
 Supply storage
 Employee lounge or locker room
 Janitors closet
 Entrances
 Corridors
 Restrooms

2012 IBC Accessibility and Usability for Commercial Buildings 364


Page 237
Primary Function Area

2012 IBC Accessibility and Usability for Commercial Buildings 365


Page 237
Primary Function Area

2012 IBC Accessibility and Usability for Commercial Buildings 366


Page 237
Not Primary Function Areas
 Non-occupiable spaces which are frequented
only by repair personnel.
 Mechanical rooms.
 Boiler rooms.
 Supply storage rooms.
 Employee lounges or locker rooms.
 Janitorial closets.
 Restrooms.

2012 IBC Accessibility and Usability for Commercial Buildings 367


Page 237
Accessible Route
to Primary Function Area
 Parking.
 Exterior accessible route.
 Entrance.
 Interior accessible route.
 Toilet rooms.
 Drinking fountains.
 Signage.

2012 IBC Accessibility and Usability for Commercial Buildings 368


Page 237
When is a Route Required?
 When an alteration or addition affects a primary
function area, and evaluation of the existing
accessible route is required.

2012 IBC Accessibility and Usability for Commercial Buildings 369


Page 238
Exceptions
 The cost of the accessible route exceeds 20% of
the cost of the alteration.
 The alteration is limited to items that will not alter
the physical configuration or use of the space.
 Windows, hardware, operating controls, electrical
outlets, signage.
 Mechanical, electrical, fire protection systems or
hazardous abatement.
 The alteration is to improve accessibility.

2012 IBC Accessibility and Usability for Commercial Buildings 370


Page 238
Historic Building
 When compliance would be detrimental to the
historical significance of a registered building.
 Minimum requirements
 Site arrival points.
 Access to main level.
 Alternative entrance.
 Unisex toilet room.

2012 IBC Accessibility and Usability for Commercial Buildings 371


Page 243
Historic Buildings

Paarlberg Historical Farm and Museum

2012 IBC Accessibility and Usability for Commercial Buildings 372


Page 243
Special Scoping
 Entrances.
 Elevators.
 Platform lifts.
 Stair and Escalators.
 Ramps.
 Performance areas.
 Dwelling and sleeping units – Accessible, Type A
and Type B.

2012 IBC Accessibility and Usability for Commercial Buildings 373


Page 246
Special Scoping
 Jury boxes and witness stands.
 Toilet rooms.
 Dressing, fitting and locker rooms.
 Fuel dispensers.
 Thresholds.

2012 IBC Accessibility and Usability for Commercial Buildings 374


Page 246
Module 8
Problem
Suppose someone came to
you with these sketches of
an existing small-town
theater, wanting to know how
to make the facility more
accessible.

2012 IBC Accessibility and Usability for Commercial Buildings 375


Page 251
Module 8
Problem
What would you
suggest in the way of:

• Scoping
Requirements
• General
Recommendations
• Technical
Requirements?

2012 IBC Accessibility and Usability for Commercial Buildings 376


Page 253
Module 8 Problem : Topics
for Discussion
 Are the ticket and concession
counters accessible?
 Is the location for the pick-up of
assistive listening devices
accessible?
 If a permanent assistive listening
system is installed, would there be
assistive listening devices available to
the wheelchair spaces?
 Is a unisex accessible bathroom on
the first floor acceptable?
 If yes, where should the bathroom be
located?

2012 IBC Accessibility and Usability for Commercial Buildings 377


Page 253
Module 8 Problem : Topics
for Discussion
 Is dispersal of the wheelchair
spaces technically infeasible?
 Where should the wheelchair
spaces be located?
 Are the wheelchair spaces seating
on an accessible route?
 Does this wheelchair space
dispersal constitute a variety of
alternatives as available to the
general public (i.e., equal
access)?
 Where is the companion seating?

2012 IBC Accessibility and Usability for Commercial Buildings 378


Page 253
Module 8 Problem : Topics
for Discussion
 From which direction is the approach
to the wheelchair space: front, rear or
side access?
 Is the size of the wheelchair space
adequate for this approach?
 Often the public service side of
theater is considered for accessibility
requirements. Should the stage,
orchestra pit and dressing room also
be accessible?
 Can a platform lift be utilized in this
area?
 Are the catwalks required to be
accessible?
2012 IBC Accessibility and Usability for Commercial Buildings 379
Page 253
Final Reflection Problem
 Suppose someone
came to you with this
sketch for a proposed
department store
inside an existing
150-year-old factory
building, and asked
how to make the
facility more
accessible.

 What would you


suggest?

2012 IBC Accessibility and Usability for Commercial Buildings 380


Page254
Final Reflection Problem
 If parking is provided, what
are the requirements?
 What are customer service
facilities, and are they
accessible?
 Does the elevated cafeteria
meet accessibility entrance
and route requirements?
 What percentage of booths
and tables must be
accessible?

2012 IBC Accessibility and Usability for Commercial Buildings 381


Page
Final Reflection Problem
 Per the 2012 International Plumbing Code (IPC) the
store is required to have four water closet fixtures and
three lavatories for each sex, and one drinking fountain.
Since more than six total water closets are required, at
least one unisex toilet room is also required. How many
fixtures are required to be accessible?

 With an occupant load of 4,000, would the store meet


accessible entry and egress requirements?

 Where would visible alarms be required in this store?

2012 IBC Accessibility and Usability for Commercial Buildings 382


Page
Thank you for attending.

Questions?
Post-Test
 This post-test is designed to measure how
much you learned in this class.

 Please take your time to answer these


questions based on the knowledge that
you acquired in this seminar.

2012 IBC Accessibility and Usability for Commercial Buildings 384


International Code Council is a Registered Provider with The American
Institute of Architects Continuing Education Systems. Credit earned on
completion of this program will be reported to CES Records for AIA
members. Certificates of Completion for non-AIA members are available on
request.

This program is registered with the AIA/CES for continuing professional


education. As such, it does not include content that may be deemed or
construed to be an approval or endorsement by the AIA of any material of
construction or any method or manner of handling, using, distributing, or
dealing in any material or product. Questions related to specific materials,
methods, and services will be addressed at the conclusion of this
presentation.

2012 IBC Accessibility and Usability for Commercial Buildings 385


Copyright Materials

This presentation is protected by US and International


Copyright laws. Reproduction, distribution, display and use of
the presentation without written permission of the speaker is
prohibited.

© International Code Council 2006

2012 IBC Accessibility and Usability for Commercial Buildings 386


Thank you for participating