Professional Documents
Culture Documents
1993
-
-
-
`
,
,
`
,
`
,
,
`
,
,
`
-
`
-
,
`
`
,
`
`
`
`
`
`
,
`
`
,
`
`
`
,
`
`
,
,
,
`
`
`
,
,
`
`
-
-
-
-
-
`
,
,
`
,
`
,
,
`
,
,
`
-
-
-
`
,
,
`
,
`
,
,
`
,
,
`
Contents
`
`
`
,
`
`
,
`
`
`
`
`
`
,
`
`
,
-
`
-
`
,
,
`
,
,
Page
`
,
`
,
,
`
-
Foreword ii
1 Scope 1
2 Informative references 1
3 Definitions 1
4 Sprinkle in-field equipment 1
5 Trickle/bubbler in-field equipment 7
6 Pipes and fittings 9
7 Suction and delivery pipework 14
8 Valves 15
9 Flow meters 18
10 Pump installations 18
11 Applying chemicals 24
12 Safety 24
Table 1 — A classification of irrigation systems used in the UK 2
List of references Inside back cover
© BSI 07-1999
Copyright British Standards Institution
i
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
Foreword
This Part of BS 7562 has been prepared under the direction of the Agricultural
Machinery and Implements Standards Policy Committee and contains
recommendations on good practice in the planning, design and installation of
irrigation schemes in the UK, together with information and guidance. It is
intended for the use of engineers and farmers having some knowledge of the
subject. It embodies the experience of engineers successfully engaged on the
design and construction of irrigation schemes so that other reasonably qualified
engineers may use it as a basis for the design of similar irrigation schemes.
This Part of BS 7562 contains information and represents good practice at the
time it was written and, inevitably, technical developments may render parts of
it obsolescent in time. It is the responsibility of engineers concerned with the
design and construction of schemes to remain conversant with developments
which have taken place since publication.
This standard has been prepared in six Parts as follows.
— Part 1: Glossary of terms;
— Part 2: Guide for acquisition of site data;
— Part 3: Irrigation water requirements1);
— Part 4: Guide to water resources;
— Part 5: Guide for irrigation equipment;
— Part 6: Guide for feasibility and implementation procedures.
A British Standard does not purport to include all the necessary provisions of a
contract. Users of British Standards are responsible for their correct application.
Summary of pages
This document comprises a front cover, an inside front cover, pages i an d ii,
pages 1 to 26, an inside back cover and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on
the inside front cover.
1) In preparation.
--``,,```,,,``,```,``,``````,``,-`-`,,`,,`,`,,`---
ii © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
-
-
`
`
,
,
`
`
`
,
,
,
`
`
,
`
`
`
,
`
`
,
`
`
`
`
`
`
,
`
`
,
-
© BSI 07-1999
Copyright British Standards Institution
1
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
Conventional systems — portable — hand move Mainly use small rotary impact
— roll move sprinkers, but guns, fixed sprays and
— tow line bubblers are also used
— semi-permanent — sprinkler hop
— pipe grid
— hose pull
— permanent
Mobile gun systems — hose drag Mainly guns, but in some cases the
— hose pull gun is replaced with a boom device
with small rotary impact sprinklers or
fixed sprays
Mobile lateral systems — centre pivot Small rotary impact sprinklers or
— linear move fixed sprays
Spray — stationary Fixed sprays
lines — oscillating
— rotating
Wind will distort the wetting patterns of sprinklers. Water droplet sizes from guns may be unacceptably
The amount of distortion depends upon the wind large for certain soil types and crops, causing
speed and the size of the water droplets. The greater damage to both soil and crop. Careful selection of
the wind speed and the smaller the water droplets nozzle diameter and type and operating pressure
the more distortion will occur. Wind distortion can should be made to ensure that the resultant droplets
be counteracted by spacing the sprinklers closer are suitable for the soil and the crop.
together but care should be taken as this may also Gun nozzle diameters can vary from 12 mm up to
increase the application rate. If the application rate and above 40 mm.
exceeds the infiltration rate of the soil, run-off may
Two main types of nozzle are available; ring nozzles
occur. The direction of the wind may be an
and taper nozzles. Ring nozzles are designed to
additional problem especially if the wind direction
produce acceptable droplet sizes at lower operating
changes during the irrigation set. In this situation
pressures. Taper nozzles are designed to produce
the best results may be obtained by ignoring the
the maximum wetted throw but droplet sizes are
effects of wind altogether and operating the
increased.
sprinklers on their recommended spacings for low
wind speeds. The throw is not only affected by the operating
pressure and nozzle diameter and type but also by
4.2.3 Guns
the construction of the gun. The length of the range
Guns are large rotary sprinklers which have a large tube and its diameter, plus the use of straightening
wetted diameter. They are commonly used in mobile vanes inside the range tube, combine to affect the
systems in the UK but they can also be used in maximum throw.
conventional systems. The application rate tends to be greater than for the
Guns may be used on various irrigation systems small rotary impact sprinklers. The recommended
either fixed or mobile. They normally have spacing depends upon the wetted diameter, wind
discharges from 10 m3/h up to and above 125 m3/h speed and direction and the required coefficient of
and operate at pressures from 2.0 bar2) up to and uniformity. Gun spacing recommendations vary
above 8.0 bar. The selection of the operating according to whether the gun is working on a grid
pressure depends upon nozzle size and type and system, a mobile unit or is used on a centre pivot or
droplet size required. linear move.
2)
1 bar = 105 N/m2 = 105 Pa.
--``,,```,,,``,```,``,``````,``,-`-`,,`,,`,`,,`---
2 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
Guns may be used for full or part circle irrigation. The thrust forces resulting from gun operation may
Full circle irrigation would usually be applicable to be high due to the flows and pressures used and the
fixed grid irrigation systems. Mobile gun systems construction of the riser is critical for correct gun
usually use part circle applications of 270° to 300° performance. The riser strength should be sufficient
arc. Guns may also be used on the end of centre with its support to prevent flexing of the riser which
pivots and linear move machines to irrigate an arc may cause either failure or poor gun performance.
of 180° or less. Risers used on grid systems should be designed with
There are two main types of drive systems used for adequate support structures to ensure that when
rotating the gun. Impact drives operate using the the gun is operating the riser is sufficiently stable.
water flow that leaves the nozzle moving an impact The riser should be of suitable diameter to ensure
arm up and down or sideways causing the gun to that the velocity of water through it is not excessive
rotate. Gear drives operate by passing a small causing high turbulence which may affect the
quantity of the main supply through or over a performance from the gun. Risers fitted to the
turbine gear drive assembly. This causes the gun trolley units used on self travellers should be
itself to rotate via a gear mechanism. sufficiently strong to resist breakage. The trolley
base should be so designed that there is no risk of
The drive mechanism may be affected by water
tipping over when operating under normal
quality. Care should be taken with gear drive
irrigation conditions.
systems to ensure that grit or other particles do not
cause the drive system to fail. Filtration equipment 4.2.4 Fixed spray heads
may be required for some systems. Fixed spray heads may be used to apply water either
Guns normally operate with trajectory angles to the total ground area or to a specific area around
between 18° and 25°. Low angle guns may be used a plant.
on applications where wind affects the gun Spray jets may be used on conventional irrigation
performance, but the wetted diameter of the gun is systems, such as under tree irrigation and also on
reduced. Adjustable trajectory guns may be suitable centre pivots and linear move machines.
for certain situations such as operating in high wind
4.3 Sprinkle irrigation systems
conditions where reduced wind drift is required.
NOTE The irrigation systems most commonly used in the UK
The part circle mechanism fitted to guns should are listed and classified in Table 1.
-
-
-
`
4.3.1.1 General
`
high speed. In this case the riser assembly should be system in use and comprise pipes, small rotary
`
,
`
`
`
,
should be considered where there is a risk that a by hand, around the field to complete an irrigation.
`
,
,
`
`
-
© BSI 07-1999
Copyright British Standards Institution
3
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
developments have been made to this system to either 6 m or 9 m. Pipes that are 6 m are lighter in ,
`
,
,
`
-
ensure as little pressure variation as possible Sprinkler risers should be of sufficient height to
`
,
,
,
`
`
operated down the slope provided that the crop and should be adequately supported to avoid
maximum pressure variation along the lateral does bending and vibration as the sprinkler rotates.
not exceed 20 % of the sprinkler’s recommended Both aluminium and steel lightweight galvanized
operating pressure. If the slope would cause a steel pipes may be subject to corrosion if fertilizers
greater pressure variation, then pressure regulators or other chemicals are applied through the
should be fitted to the sprinklers to produce correct irrigation system. The manufacturer of the pipe and
operation. A pressure regulator may be fitted under fittings should be consulted if this practice is
the sprinkler inlet connection or a pressure considered.
regulating/flow controlling nozzle may be inserted
The ease of connection and disconnection of coupling
at the nozzle. Sprinkler laterals may be laid out up
lateral pipes should be considered carefully when
the slope where this is the only possible layout.
selecting the type to be used. Couplings that can be
Pressure regulating or flow regulating devices
operated by one person may be favoured where
should be fitted to the sprinkler where the pressure
labour is short.
variation along the lateral is greater than 20 % of
the sprinkler’s recommended operating pressure. Sprinkler risers may have either permanent or
quick coupling connections to the sprinkler lateral.
Ideally, sprinkler laterals should be laid out at right
The type of riser used depends upon the method of
angles to the prevailing wind for a more u niform
operation of the system, the riser height and the
irrigation. This should take preference over layout
stability required.
in relation to contours.
The following briefly describes types of portable
The number of irrigation sets per day depends on
hand-move systems.
the depth of water to be applied at the rate per hour
and the time it takes to move the sprinkler laterals. a) Roll-move system
The fewer the number of irrigation sets per day and The roll-move system comprises a sprinkler
the longer the number of hours per set the greater lateral mounted on wheel assemblies so that the
will be the total possible operating hours per day. lateral forms the axle for the wheels. The
The application rate (in millimetres per hour) sprinkler lateral is stationary while irrigating.
relates to the application heads applying water on a The water supply to the lateral is closed off when
unit area operating on a grid system, either square, it is moved. A power unit provides the power
rectangular or triangular The application rate per source for driving the wheels.
hour calculated here is used to estimate the total It is preferable that the system is operated in
depth applied during the irrigation set. level fields to alleviate potential problems that
Several factors affect the sprinkler spacing, both may be caused by uneven ground. If used on
along the lateral and between laterals. These sloping ground, the system should be aligned
include wind speed, coefficient of uniformity, with the lateral at right angles to the land
application rate, the crop and the soil. Sprinkler contours. If it is operated running parallel to the
spacing should be reduced according to wind speed. contours there is a risk that the unit may run
down the slope while the system is operating.
The lateral pipe diameter is chosen so that the
Brake equipment may be fitted to the wheel
pressure loss along the lateral is less than 20 % of
assembly to prevent this happening.
the recommended operating pressure of the
sprinkler. In this way the changes in pressure will A balance weight self-levelling device is included
not seriously affect sprinkler performance and in the connection for each of the sprinklers to
uniformity. ensure that the sprinkler operates in the vertical
position when irrigating.
4 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
point position.
-
`
,
,
`
4.3.1.4.1 General
,
`
,
,
4.3.1.4.2 Hop systems gun, at the end of the field. The tow cable is pulled
A hop system combines the basic characteristics of out to the other end of the field and anchored. The
the portable hand move system with the ability to flexible hose is connected to the chassis and to the
move the sprinklers to alternative positions along water supply valve point. As the gun irrigates, the
the lateral. This reduces the number of times that cable drum gradually winds in, pulling itself along
the laterals are moved. the cable and at the same time dragging the lay-flat
hose behind it. If a central water supply valve is
It may be possible to operate for a greater number of
used for the supply of water, the irrigation unit can
hours per day using this system.
cover twice the area as it is able to irrigate both
The application rate is calculated for a single sides of the valve point. For example, if the machine
sprinkler head application as there is no immediate uses 200 m of hose then it is possible to cover
overlap between the sprinklers. Application rates a 400 m wetted strip per irrigation set.
are therefore suitable for a wide range of soils and
crops. 4.3.3 Mobile lateral systems
A pipe grid system consists of a complete field layout Many new irrigation systems have been developed
of pipes, made of either aluminium or lightweight in recent years to try and combine the advantages of
galvanized steel. The pipes, usually 25 mm conventional sprinkler systems with the mobility of
diameter, are normally laid down at the beginning rainguns. These are called mobile lateral systems
of the season. Only the sprinklers are moved to because they use laterals which move continuously
complete the irrigation cycles. while irrigating.
© BSI 07-1999
Copyright British Standards Institution
5
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
crop. The effects of windrift and evaporation may be The sprayline is usually supported above the crop
`
`
,
-
`
-
6 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
plant spacing and the soil type. pressure compensating emitters should be used.
,
`
,
,
`
,
,
`
The usual range of emitter operating pressure is Self-flushing emitters may often be pressure
-
`
-
,
`
`
which are pressure compensating. about 0.8 bar to 1 bar the emitter operates in the
`
,
`
`
,
,
,
`
The sensitivity of emitters to clogging plays an correct drip mode. The pump capacity and irrigation
`
`
,
,
`
`
important part in their correct performance. The system design should be such that the system will
-
-
manufacturer should recommend the maximum operate correctly when the emitters are flushing.
particle size filtration requirement for emitters to Emitters automatically self-flush, they may also be
operate correctly. The susceptibility of emitters to manually flushed.
clogging from chemical deposits and algae growth Trickle irrigation systems may be installed above or
should be considered carefully to ensure that the below ground. On above ground installations the
correct type of device is selected. Emitters may have emission devices can be checked and visually seen to
a built-in filter system which is able to remove some be operating, but may be damaged by either persons
suspended material from the water flow. Self or animals. Growth of algae at the outlet of the
flushing emitters also have the ability to flush emitters may occur but this depends on the design
particles with the irrigation water. of the emission device.
Not all of the root zone of the crop needs to be wetted Trickle irrigation laterals may be installed
with trickle irrigation. The percentage of wetted underground using mole ploughing techniques or by
area irrigated depends upon the type of crop. For individual narrow trenching. Tubing may be
wide-spaced crops, wetting may only need to connected to the emitters to bring the water from
cover 33 % to 50 % of the soil area, while close the emitter up to ground level or water may pass
grown crops may require 100 % wetting of the directly from the emitter into the soil to the root
ground area. zone of the crop.
Note that this does not mean that only 33 % to 50 % 5.2.2 Bubblers
of the water needs to be applied. The crop still
requires the same amount of water irrespective of Bubblers are used to apply water either as a small
the application method. stream of water or as a spray to a localized area
around individual plants.
Laminar flow emitters (that is micro tubes, capillary
tubes and spiral path emitters) are simple, reliable Typical flow rates for bubblers range from 1 l/m
and inexpensive but need proper system design and to 10 l/m for solid-set bubblers. Flow rates for
operation to perform well. They are relatively bubblers used on mobile irrigation systems range
pressure sensitive and are susceptible to clogging from 1 l/m to 80 l/m. It is possible to adjust the flow
because of their low velocity flow, small path rate from some bubblers by operating the screwed
diameters and varying flow rate with temperature. adjusters fitted to them.
© BSI 07-1999
Copyright British Standards Institution
7
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
sufficient. ,
,
`
-
with the crop and comprise a control head unit and eliminate expansion/contraction in the pipe and
,
`
`
`
,
`
3)
In preparation.
8 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
-
-
`
`
,
,
`
`
`
,
,
,
`
`
,
`
`
`
,
`
`
,
The potential efficiency of trickle/bubbler irrigation 6.2.4 Plans
systems is approximately 90 %, with a correctly
`
`
© BSI 07-1999
Copyright British Standards Institution
9
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
Friction losses for different pipe materials should be Plastics pipes have good hydraulic characteristics
available from manufacturers. resulting in low frictional losses and high flow
6.4.2 Waterhammer and surge capacities. They will not corrode in contact with
water ensuring that their good hydraulic
Both waterhammer and surge can cause problems characteristics are maintained throughout their
in irrigation systems especially failure of pipelines. life.
Waterhammer is a pressure wave which can occur The coefficients of expansion of plastics materials
when water flowing in a pipeline is s uddenly are generally much greater than those of metals and
-
power failure.
-
-
-
If the irrigation system is designed and operated 6.5.2 installing buried pipes
with velocities of less than 1.5 m/s in the pipeline, Pipe with diameters up to 150 mm can be jointed on
the risk of waterhammer and surge is reduced, the surface and subsequently arranged in a
although not eliminated. snake-like form in the trench, this eliminates the
The total pressure in pipelines includes the need for wide trenches. Plastics pipes may also be
operating pressure of the pipeline and the mole-ploughed into the ground.
additional pressure caused by potential Good trenching practices should be followed to
waterhammer or surge. achieve correct installation of the pipe, including
Waterhammer and surge may be reduced by one or bedding, side filling and backfilling.
more of the following methods. 6.5.3 Testing
Reducing the effective length of the pipeline by After installation it is essential that all pipework,
the incorporation of more valves of a suitable fittings and appliances be inspected and tested
specification in the line. hydraulically to ensure the safety and efficiency of
Reducing the velocity. the system.
Increasing the closing time of the valve. Before the start of any test the system should be
Installing suitable pressure regulating valves. visually inspected to ensure that the pipework has
been correctly installed. The test procedure followed
Installing suitable air valves. should be as recommended by the manufacturer or
6.4.3 Thrust blocks as stipulated by the approving authority.
Pipelines operating under pressure can be subject to 6.5.4 Limitations
movement caused by thrust forces, at any change in Plastics are not conductors of electricity and
direction or termination. External anchorage should therefore no attempt should be made to use the
be provided, usually in the form of concrete thrust pipework as a means of earthing electrical
blocks, to resist the thrust forces. equipment.
External anchorage should be provided at all Provision should be made for emptying pipes in
changes in direction and at points where exposed positions above ground or shallow buried
termination of water flow may occur Thrust blocks pipes if they are not otherwise protected against
are therefore recommended at all tees, end caps, frost damage.
bends, valves, etc.
6.5.5 Unplasticized PVC pipe
6.5 Plastics pipework (thermoplastic material)
Above 20 ° C water temperature and ambient
6.5.1 General principles and choice of temperature unplasticized PVC pipe (PVC-U)
materials should be derated according to the manufacturer’s
Materials considered here include unplasticized recommendations.
PVC pipe (for cold water services), low density
polyethylene and high density polyethylene pipe.
10 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
PVC-U pipe may be supplied plain ended for High density polyethylene (HDPE) is rather stiffer
jointing with separate couplings or supplied with and is a stronger material. Therefore the pipe walls
integral sockets already formed on one end of each are thinner and larger bore pipes at the higher
pipe. Joints may be solvent cement, push fit pressure classifications are possible.
insertion or mechanical joint. Both push fit and Polyethylene is not liable to attack from water or
mechanical joints offer little resistance to end thrust from soils which are corrosive to metals.
forces such as those set up at bends, junctions,
Polyethylene is an electrical insulator and cannot be
valves, etc. The pipeline therefore should be
used for earthing electrical insulations.
suitably anchored when these joints are used. The
correct methods for completing the jointing of pipes Polyethylene softens with heat and it is essential
and fittings as advised by the manu facturer should that it is not used for applications adjacent to heated
be followed. surfaces. LDPE softens at lower temperatures than
HDPE.
Either saddles or tees may be used for service
connections, the choice of the most suitable for each Polyethylene pipe may be laid in exposed positions
situation depends upon diameters used and site without the need for special protection against frost
conditions. damage, but will not prevent the water from
freezing in the pipe.
Cold bending or hot bending of PVC-U pipes may be
applied to allow changes in direction; either method The outside diameters of the pipes are based on the
requires skill. outside diameters of steel pipes.
The storage, handling and transport of PVC-U pipe Polyethylene pipe may be jointed using
should be as recommended by the PVC-U pipe thermofusion techniques, compression joints, or
manufacturer, taking care to protect against the threaded joints.
effects of prolonged exposure to sunlight. Bending of polyethylene pipe may be by either hot or
Installation of PVC-U pipe below and above ground cold techniques, hot techniques achieve tighter
should follow the manufacturer’s instructions. For bends.
above ground installations preventive measures Polyethylene pipe may be laid satisfactorily by
should be taken to reduce the effects of freezing, mole-plough providing the equipment is capable of
expansion and heat and adequate support should be maintaining the correct depth of cover over the pipe.
provided. The piping is liable to be cut by sharp surfaces above
Before testing, anchor blocks should be allowed or below ground and therefore extreme care should
sufficient time to develop their strength, e.g. be taken.
concrete to set properly. All intermediate control 6.5.6.2 Medium density polyethylene pipe
valves should be positioned open for the duration of
It is a recommendation of the UK water industry
the test.
that the use of blue medium density polyethylene
The test should be deemed satisfactory if the pipe (MDPE) be adopted as the standard type of
-
-
-
`
,
,
recommended. The recommendation in the UK is as size range over 63 mm the use of MDPE pipes is a
`
`
,
`
`
`
follows.
`
3 l per 1 000 m of pipe per 25 mm of nominal In this range of sizes MDPE piping is often
`
`
,
`
`
,
soil for surrounding buried pipes. Although these recommendations do not apply to
Details of working pressures, classes and wall agricultural irrigation systems, the engineer or the
thicknesses of PVC-U pipes may be found in the end user may specify MDPE pipe.
manufacturers’ technical data. Pipes up to and including 63 mm may be supplied in
6.5.6 Polyethylene plastics pipe coils up to 150 m long, while pipes larger
than 63 mm may be supplied in 6 m, 9 m or 12 m
6.5.6.1 Low and high density polyethylene plastics lengths.
pipe
Jointing methods vary depending on the pipe
Low density polyethylene (LDPE) has a relatively diameter, but they include compression fittings,
low tensile strength and pressure pipes made from electrofusion methods and insert fittings.
it are generally restricted to those of smaller bore.
© BSI 07-1999
Copyright British Standards Institution
11
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
-
-
BS 7562-5:1993
`
`
,
,
`
`
`
,
,
,
`
`
,
`
`
`
,
`
`
,
`
`
`
`
`
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-
12 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
iron, cast iron or aluminium). joints or mechanical joints if it is PVC or may use
mechanical couplings if the tee is of steel,
The use of cement joint fittings is not recommended
cast iron, etc.
on fittings above 100 mm to 150 mm as it is likely
that the cement applied to the fitting will have
partially dried before the fittings can be connected
together. It is therefore advisable that mechanical
joints are used above 100 mm to 150 mm sizes
where seals make the joint instead of cement.
© BSI 07-1999
Copyright British Standards Institution
13
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
Hydrant tees provide the take off in a vertical The radius of the fittings used should be generous
direction to above ground irrigation equipment. The and sweep bends should always be u sed, in order to
connection to the above ground fitting is usually discourage excessive turbulence in the water being
threaded on the smaller diameters and flanged on pumped.
the larger diameters. The type of material from The lengths of suction pipe used should be kept as
which the hydrant is made should be considered short as possible to reduce friction losses in the
carefully in relation to the application of the suction pipework.
connected item to the hydrant tee. On the larger
The pipe connections (flanges, threads or couplings)
diameter hydrant tee take offs, such as 75 mm
should be kept to as few as possible, reducing the
where a hydrant valve is fitted to the top, it is usual
risk of air entering the suction line at the joints and
to use a steel or cast iron hydrant tee. This material
limiting the friction losses caused by the
should give greater strength and support to the
-
-
connections.
hydrant riser and reduce the risk of damage to the
`
`
,
,
`
14 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
The suction pipework should be installed so that it A pressure relief valve, which might be fitted either
rises gradually from the water source to the pump. on the top of the non-return valve or to a separate
There should be no high spots in the suction tee, may be installed in the delivery fittings, to
pipework where air could be trapped resulting in provide protection and flow bypass facilities.
reduced flow through the pipe. An air/vacuum relief valve may be installed to expell
The velocity of water in the suction pipe should be air from the mains while the pipework is filled and
kept to below 1.5 m/s. to allow air to enter when pumping stops.
A floating suction intake (where used) has its inlet A pressure gauge may be installed on the delivery
to the suction pipe sited just below the surface level side of the pump unit, in such a position that it does
of the water. This location should reduce the not give inaccurate readings due to turbulence in
amount of contaminants entering the suction pipe the pipework. A gauge cock should be fitted
because this point is usually where the cleanest underneath the pressure gauge to provide isolation.
water is situated. Structural support should be provided for all the
The suction intake should be located at the correct fittings and valves to ensure that no weight is put
minimum distance away from walls, baffles and onto the delivery connection of the pump. Clamps
other such pipes to ensure correct performance. fitted around the pipework should ensure that it
Both horizontal and vertical pipes should be well cannot move.
supported. Thrust blocks should be provided at the calculation
If the suction pipe passes through a wall close to the design points connecting from the delivery fittings
pump connection, a flexible coupling may be used to into the supply mains. Thrust blocks should be used
connect from the pump to the suction pipework. The at all changes of direction both horizontal and
flexible coupling reduces the transfer of vibration vertical.
and makes access to the pump connection and Motor vibration is common on internal combustion
suction fittings easier. engine powered pumps and if transmitted to fittings
7.2 Delivery pipework and supports could cause their failure. To avoid a
transfer of motor vibration from the motor to the
The delivery fittings should be designed and fittings it may be advisable to u se a suitable adaptor
specified to carry out the functions required. These or flexible coupling.
functions may include control of the flow and
pressure, measurement of the flow, and protection 8 Valves
of the system. Installation of both the valves and the
pipe and fittings should be designed correctly to 8.1 Pressure regulating valves
achieve optimum system performance. The function of pressure regulating valves is to
If the pump delivery flange has a different diameter control and regulate a higher upstream pressure to
a lower downstream regulated pressure.
-
gradual transition in size to the diameter of the and should maintain a preset regulated
`
-
`
-
,
`
the concentric taper to prevent flow reversal. The to the irrigation equipment being operated. `
,
`
`
,
,
,
© BSI 07-1999
Copyright British Standards Institution
15
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
where a change in downward slope occurs a depending on the type of irrigation system and its `
-
,
`
`
,
requirements.
`
The size of air valves should be calculated taking 8.5 Drain valves ,
`
`
`
,
`
`
account of the diameter of the supply mains and the The function of drain valves is to enable the system
,
,
,
`
`
`
There are two main types of air valve, small orifice against damage from water freezing in the pipework
or large orifice, both may be used in the irrigation and to allow repair or maintenance to be completed.
system. Drain valves should be installed at all low points.
Small orifice air valves should be installed to allow The drain valves should be able to drain the
expulsion of air while the system is operating. complete system including suction and delivery
Large orifice air valves allow air to be expelled from fittings, supply mains and in-field equipment.
the main or for air to enter quickly.
16 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
The drainage water from the drain valve should Brass valves are more expensive but may provide
either pass into a soakaway or be fed via a pipe into greater strength and corrosion resistance.
a surface water course or ditch. If the valve is fitted with a pressure regulation
Access to underground drain valves should be via a facility, a pressure difference is required between
valve chamber and a key to operate the valve. the inlet and outlet, varying from 0.5 bar to 1.0 bar,
8.6 Riser valves and hydrants for these valves to operate successfully. The aim of
the pressure regulating facility is to maintain a
The function of riser valves or hydrants is to provide constant outlet pressure downstream of the valve,
a take-off to irrigation equipment, or a sub-main , within ± 0.3 bar.
from either an above ground or underground supply
A Schrader valve installed on the side of the valve
mains.
provides the facility for checking the pressure
The operating pressure ranges over which the setting of the valve. Alternatively, a pressure gauge
hydrant valve will operate should be considered to assembly may be fitted to the valve, providing an
make sure that it is suitable for the application. instant readout of the pressure.
The friction loss through the hydrant valve should A grit filter may be fitted to the valve to prevent
be known to ensure that the design diameter is debris from jamming the solenoid plunger and
correct for the duties to be performed. causing it to fall to operate. A mainstream filter may
The opening and closing of the valve should be be fitted, commonly constructed of a nylon screen.
possible without causing damage either to This is able to filter water entering the bonnet
equipment or to persons operating the valve. cavity of the valve.
8.7 Volumetric control valves 8.8.3 Hydraulically operated valves
The function of metering valves is to automatically The functions that hydraulically operated valves
shut off the flow after delivering a preset volume of are able to carry out are similar to those of an
water, regardless of changing pressure or flow rate. electric automatic valve.
The manufacturer’s recommendations for maximum Location limits apply to these types of valves for
and minimum flow rates through the valve should both the distance from the controller that they can
be followed to ensure that the valve will deliver the be sited and the height above or below the controller
required volume of water and accurately measure position.
the flow passed. Operating distance away from the controller will
The volumetric valve may be fitted with the facility vary according to the manufacturer’s specification.
to sequentially operate and regulate the Normally open valves may be installed up to
downstream pressure. approximately 300 m from the controller while
The installation of the valve may require straight normally closed valves may be installed up to
lengths of pipe both upstream and downstream of approximately 60 m from the controller.
the valve. 8.8.4 Mechanically operated valves
The valve opening and closing times may be Similarly, the function of mechanically operated
adjustable and should be such that waterhammer valves is to provide on/off control of flow.
and surges in the line are discouraged.
8.9 Controllers
8.8 Automatic valves
The main function of controllers is to automatically
8.8.1 General open and close control valves. Controllers may be
Automatic valves may be operated electrically, used to open and close valves operating irrigation
hydraulically or mechanically. laterals, to work in conjunction with flushing valves
on filter units and to perform other specialist duties.
8.8.2 Electric automatic valves
A controller to be used on an agricultural irrigation
The function of electric automatic valves is to
system needs to be versatile and may include
provide on/off control of flow.
features such as the number of stations operated,
The applications for all electric automatic valves are the time of operation per station, day and hour
wide and include automatic flushing for filter units, programming, and multi or split cycle
automatic drain down of systems, and many other programming.
uses. Electric automatic valves may be used to
Pump switches, cancel switches, rain switches,
control the flow to sprinkler or drip irrigation
master valve control and moisture control circuits
laterals or to centre pivot or other similar
may also be required and utilized within the control
equipment.
system.
--``,,```,,,``,```,``,``````,``,-`-`,,`,,`,`,,`---
© BSI 07-1999
Copyright British Standards Institution
17
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
8.10 Valve boxes The meter readout on the dial may have a lockable
All remote control valves, manual control valves, cover which provides additional protection. It
isolation valves, etc. should be installed in valve should also be fitted with anti-condensation glass so
access boxes made of concrete, thermoplastics or that the inside does not fog up.
other suitable material. For correct installation and operation of the meter,
The valve box should provide protection for the the pipeline should be full of water at all times, the
valve and should be of adequate size to allow access flow meter should be installed with the correct
to the valve for operation, maintenance and repair. direction of flow, and upstream of the flow m eter
There should be enough room to allow removal of there should be the equivalent of 10 pipe diameters
the valve and access to the connectors each side of of straight pipe without fittings or flanges.
the valve. Downstream of the flow meter there should be the
equivalent of at least 1 pipe diameter free from
The valve box should be installed on a suitable base valves, fittings or flanges. It may be advisable to
of gravel to provide a sound foundation for the box install the flow meter on the suction side of the
and to facilitate its easy levelling so as to provide pump unit where there may be less turbulence and
proper drainage. thus greater accuracy of recording.
The valve box housing should be so constructed that
9.3 Ultrasonic flow meters
it will rest on bedding and not interfere with pipes
and cables entering or leaving the valve box. The The velocity range over which the ultrasonic flow
housing should be strong enough to s upport the meter will operate accurately depends upon the
cover. manufacturer but the average range is 0.3 m/s
to 0.5 m/s.
The valve box should be provided with length and
side extensions if it is required to bring the valve box An ultrasonic flow meter has no moving parts and
level with the finished ground level, rather than operates with a flow sensor which fits externally to
burying the valve box below ground. the required diameter of tube and is complete with
a tube assembly.
The box should be supplied with an approved cast
iron, concrete or thermoplastics cover. The cover The flow converter transmitter may be connected to
should be of sufficient strength to resist failure due the length of pipe onto which the flow sensor is fitted
to foreseeable causes, such as a vehicle driving over or it may be sited up to a maximum distance of 20 m
it. to 30 m away from the sensor. This type of meter
may be more suitable for flow measurement of
9 Flow meters irrigation water containing debris and other
contaminants.
9.1 General
The function of flow meters is to measure the 10 Pump installations -
-
-
`
,
,
18 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
An electrical motor driven pump requires an Air moisture condensing on components may cause
electricity supply. The electricity authority may corrosion. The fittings should be s uitably protected.
advise on the siting of the step-down transformer A space heater may assist in reducing condensation.
-
-
`
`
,
and the main switch gear and isolators. The location The pump base should be suitably constructed of
,
`
`
`
,
,
,
of the pump starter gear within the pumphouse concrete, reinforced where necessary, to the
should be such that the operator can reach this
`
`
,
`
`
`
,
specified size, dimensions and depth. The concrete
`
`
,
`
`
equipment as soon as he enters the pump house. foundations for the pump and motor should be such
`
`
`
`
,
`
`
,
-
All the equipment sited at the pump station should that both the pump and motor are raised off the
be adequately protected from the weather. Rain, ground by at least 150 mm.
`
-
`
,
,
`
sun onto the motor or pump should be avoided as back to the water source. This pipe should be of
this could lead to overheating. sufficient diameter to allow the pressure relief valve
The Health and Safety at Work etc. Act 1974 [1] to operate correctly.
applies within the pump house, and is applicable to If a hand priming pump is used to prime the pump,
not just moving parts but electrical and other a return pipe or a return gulley should take the
components. water that is discharged from the hand priming
The floor surface should be solid, even, of non-slip pump back to the water source or drain.
construction and should not become slippery. A Fertilizer injection equipment and filtration
concrete brushed surface should be safe. There equipment may be sited within the pump hous e.
should be no pipes, cables, valves or fittings in the Both will need regular maintenance and therefore
access areas that could present a hazard to the easy access to this equipment is important.
operator. Piping and other fittings, where possible,
should be installed below ground level and suitable 10.2 Portable pump installations
covers placed over fittings that are within the Portable pump installations are generally designed
operator access areas. for irrigation pump units which are to be re-sited
The pump house should be adequately ventilated so fairly frequently, often during the irrigation cycle.
that the equipment does not operate in extremes of Mobility is therefore a key factor in this type of
temperature or humidity. installation.
The lighting in the pump house should be adequate Small light pump units may be mounted on a simple
for the operator to work and for maintenance work base and supplied with a handle for hand carrying.
to be carried out. Light may be from a combination Larger units may be mounted on a wheeled trolley
of both natural and artificial sources. assembly so that the unit can be towed.
It may be necessary to install overhead gantry gear If the pumpset is to be towed and is mounted on
to assist in removal and/or installation of the pump wheels, jacks should be fitted to provide stability
and motor for repair and maintenance. The need for when pumping.
lifting gear depends upon the size of the equipment For ease of connection and disconnection the
installed. couplings on the pump unit should be of the quick
Drainage gulleys should be constructed in the floor connect and disconnect type.
of the pump house to allow any water to run out of The quick couplings on the suction side should
the pump house into a soakaway or drain. Water provide complete sealing under vacuum so that air
may drip from packed glands or it may leak from the cannot enter the suction via these couplings.
pipework. The floor should slope slightly so that Quick couplings used on the delivery side of the
water can run off into the drainage gulleys. pump should be of the type that will seal under
Where chemicals are used (e.g. via chemical pressure and will not leak when the system is
injection equipment) they should be stored in a operating.
secure area, away from water and the pump house, The suction assembly should incorporate quick
preferably in a separate building. coupling at the pump, and be portable and easy to
Drain down facilities should be fitted to the suction move. It should be possible to drain the suction hose
and delivery pipework and pumping and other and pipe by opening a valve on the f oot valve, thus
equipment to ensure that water can be drained from facilitating re-siting.
the equipment when not in use. This should prevent The portable pump unit should be positioned so that
the risk of damage caused by freezing. it is not able to move, especially towards the water
source, while it is pumping.
© BSI 07-1999
Copyright British Standards Institution
19
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
The pump unit should be protected against a back The minimum safe flow that the pump will handle is
flow of water in the mains, which could occur when critical for the protection and performance of the
the system stops pumping. This protection should pump. The pump manufacturer should advise on
be provided by a non-return valve fitted in the first this minimum safe flow referring to temperature
piping in the supply mains and protected against rise, effect on performance and nett positive suction
thrust forces. head required. A bypass assembly or orifice plate
A diesel engine pumpset may require a portable fuel may be used to allow the pump to operate under low
tank, unless a fuel tank is built into the pumpset. flow conditions.
Both the suction and delivery pipes should be The maximum flow that the pump will handle may
supported adequately to prevent excessive weights be critical in the selection and sizing of the power
being placed on the suction and delivery connections unit. The sizing depends on the control and range of
of the pump. duties that may be demanded. Motor overloading
should be avoided by the correct design and
The suction pipe should be installed so that it rises
selection of the pump and motor.
slowly from the water source up to the pump inlet.
10.4.1.2 Total dynamic head
10.3 Floating pumps
The total dynamic head should be evaluated in
Floating pumps may be used on surface water
terms of the duty head and the shut down
sources where the site conditions are suitable, e.g.
head i.e. when equipment is no longer operating and
where there is great variation between maximum
there is no flow.
and minimum water levels in the water source, such
as in a reservoir with a water level variation greater The duty head may vary according to where the
than 5 m. in-field equipment is being operated. The static
head, the head loss in the main s and the equipment
The normal power unit to drive a floating pump unit
operating pressure may all vary, thus changing the
is an electric motor, as an electrical supply is
operating duty head at the pump.
usually easier than supplying fuel for an internal
combustion engine. The pump shut down head should be considered
when selecting pumps as well as the irrigation
The floating unit should be constructed so that it is
system design requirement. Protection equipment
stable and will support the weight of the pump and
may be needed to prevent overload occurring due to
accessories.
high shut down head which may be greater than the
The floating pump should be anchored securely so normal operating head.
that it will not be able to detach itself f rom its
10.4.1.3 Efficiency
moorings.
The motor specification should be suitable for The efficiency of the pump unit is directly related to
operating in the adverse conditions which may exist the power required for the pump. Efficiency should
at a floating pump installation. be as high as possible at the duty point. If a pump
has to operate over a wide range of pressures and
The cable should be correctly rated and be discharges, variations in efficiency can be expected.
supported with adequate fixings.
10.4.1.4 Absorbed power
The delivery pipe from the pump unit to land may be
by either solid or flexible pipe. Whichever type of The absorbed power required at the pump shaft will
pipe is used, it should allow vertical pump vary if there is a range of pump duties to be met. The
movement without straining the connections. selection of the power unit should be based on the
Access to the pump should allow repairs and range of duties required plus a factor for safety and
maintenance to be carried out. wear and tear.
10.4 Pumps 10.4.1.5 Nett positive suction head required
10.4.1 Centrifugal pumps The nett positive suction head required (NPSHR) is
the pressure required at the inlet of the pump to
NOTE Most of the pumps used for irrigation are centrifugal
pumps. achieve the specified duty. It is a function of the
pump inlet design and impeller speed. (NPSHR)
10.4.1.1 Discharge
varies with the type and size of pump and increases
Many irrigation systems operate over a range of with both discharge and pump speed. NPSHR
flows, rather than at one fixed duty point depending curves should be given on the manufacturer’s pump
on the equipment, operation and type of irrigation performance data sheets, covering the range of
system. Where a wide range of flows is needed it speeds at which pump performance is shown on the
may be necessary to install more than one pump curves.
unit and operate them in parallel.
--``,,```,,,``,```,``,``````,``,-`-`,,`,,`,`,,`---
20 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
10.4.1.6 Nett positive suction head available Submersible pumps are electrically driven. For
The nett positive suction head available (NPSHA) is correct installation and performance of the pump,
the resultant pressure at the entrance to the pump the factors considered should include maintenance,
impeller after all losses and performance borehole straightness, removal for servicing,
requirements have been met. The NPSHA shou ld be operating depth and depth of water above the pump.
positive otherwise the pump unit will not operate. For all boreholes there should be close liaison
between the borehole engineer and the pump
10.4.1.7 Pump unit configuration
supplier to ensure that all features of the borehole
Where more than one pump unit is used in the are assessed.
irrigation system, they may be operated in series or
10.5 Power units
in parallel.
Pumps operating in series use a first pump which 10.5.1 General
supplies water under pressure to a second pump. The power unit may be either an electric motor, an
The second pump delivers the same discharge but internal combustion engine or a PTO shaft,
boosts the pressure. It is essential that the pumps depending on the type of pump. The choice between
are balanced with regard to discharge. The the alternatives depends on many factors both on
maximum casing pressure of the booster pump site and with regard to the client’s requirements.
should be capable of handling the total pressure Economic factors also apply: both fixed costs and
produced. variable cost elements need to be considered
Pumps operating in parallel combine to increase the carefully when selecting the power unit.
discharge whilst the pressure remains the same. 10.5.2 Electric motors
The pressure produced by each pump should be
Electric motors should be suitable for the UK
similar to ensure balanced pumping from all the
electricity supply voltage, phases and cycles and
pumps.
able to operate within the range of voltage
10.4.1.8 Cavitation variations permissible on the national grid.
Most centrifugal pumps cavitate but some may Their power consumption should be considered
suffer cavitation damage if incorrectly installed or if taking account of the efficiencies of both pump and
the pump is incorrectly used. This may seriously motor. The efficiency of the pump and the efficiency
damage the pump impeller and result in poor pump and power factor of the motor should be as high as
performance. possible for the duty range required.
Cavitation may occur when the flow from the pump The type of electric motor used will depend upon the
is greater than the design flow. type of pump that is to be driven. For most pumps,
If the suction lift becomes too great, the NPSHR excluding submersible pumps, a totally enclosed fan
could exceed NPSHA, with resulting risk of ventilated motor should be adequate to meet the
cavitation. requirements of the typical operating conditions in
which an irrigation pump would be working in the
If a pump is cavitating it tends to be noisy with a
UK.
continuous crackling sound. There may also be
excessive vibration. For submersible pumps, a special submersible
motor will be required. Usually the pump and the
10.4.2 Borehole pumps motor are supplied as an integral unit by the
Borehole pumps are a form of centrifugal type pump manufacturer.
specially adapted for use in boreholes. They may be Alternative motor enclosure types are available to
driven either by a power unit mounted at ground suit the different conditions under which the motor
level (shaft drive) or by a power unit fitted may be operating, especially if outside or in a
underneath the pump itself and installed within the pumphouse. These include drip proof and totally
well (submersible motor driven). enclosed fan cooled. The temperature motor rating
For shaft driven pumps the diameter of the pump, is dependent on the type of insulation used in the
length of fittings and borehole straightness should windings. The correct rating should be applied.
be correct for the installation of the pump unit in the Various types of enclosure protection to different IP
borehole. The diameter of the borehole and its specifications (see BS EN 60529) are available.
straightness may limit the size of pump that can be IP 54 and IP 55 specifications should be suitable for
used and hence the yield from the borehole. most irrigation applications. IP 65 may be used on
certain motor installations.
--``,,```,,,``,```,``,``````,``,-`-`,,`,,`,`,,`---
© BSI 07-1999
Copyright British Standards Institution
21
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
Additional matters that may require consideration Engine and pump protection may be fitted to the
for motors include provision of heaters, protection, engine to protect against engine overheating and
motor derating, speed, slip and service factor. The low oil and no water in the pump.
manufacturer should be consulted for the correct It is essential that the engine power available at the
specification for the application. various duty points required by the pump is
The starter selected for operation with the electric carefully matched to ensure that performance over
motor should be compatible and may need to the duty range can be achieved.
incorporate protection equipment and other When selecting and specifying the engine size a n
features as required. Single-phase electric motors allowance of about 10 % should be made to allow for
normally use direct on-line starters. Three-phase wear and tear in the engine.
electric motors may use either direct on-line
The engine speed should be matched to the speed of
starters, star delta starters, auto-transformer
the pump to give optimum performance at the duty
starters or other suitable types of starter.
point or duty range.
Each starter type has its own particular
The gross power requirements for a diesel engine
performance characteristics for torque and current.
pump unit should include the power absorbed by the
The starting torque and current vary greatly
pump, the losses incurred through the gear drive
between the various types of starters available.
attached to the pump, derating factors, engine
Direct on-line starters are usually only suitable for
accessories and service factor.
smaller motors.
The general build of the starter should prevent 10.5.4 Power-take-off shaft power
entry of moisture, dust etc., while mounting Power from the power-take-off (PTO) shaft on a
supports should be adequate. Facilities tractor may be used to drive an irrigation pump.
incorporated within the starter may include The power available at a tractor PTO should be
isolator, overloads, protection circuits, meters. The checked with the tractor manufacturer to ensure
starter specification should be made in conjunction that the power required by the pump can be met by
with the electric motor. the PTO shaft. The power available at the PTO is at
10.5.3 Internal combustion engines least 10 % less than the power available at the
engine and is specified at the speed for the PTO
Only diesel internal combustion engines are
shaft, usually 540 rpm or 1 000 rpm.
considered here, as these are the type of engine most
commonly installed on irrigation schemes in the The safety guards that protect persons from the
UK. They offer the advantages of fuel economy and PTO shaft should be properly fitted.
good power output, characteristics which are very The actual maximum angle of deviation of the PTO
suitable for the requirements of irrigation pumping. shaft and the actual maximum PTO speed should be
Small diesel engines (having one or two cylinders) checked against that specified to ensure that the
are usually hand started, have no protection PTO shaft does not fall at the couplings due to
facilities for either the engine or the pump and have excessive angle of operation or excessive velocity.
no electrics. The pump may be connected to the power unit via
Engine accessories will cause additional loads on either a three-point linkage or a trolley assembly.
the engine. These may include radiator fans, Engine protection equipment should be considered
alternators, oil coolers. An allowance of up to 10 % for installation on the tractor to provide protection
should be made for these losses. for both the engine and the pump.
An air cleaner configuration which comprises a 10.6 Power transmission
pre-cleaner and a filter element should be suitable
Power can be transmitted from a power unit to a
for most applications.
pump via either a direct coupling, a flexible
If the pump is a portable unit, a fuel tank may be coupling, various belt configurations, or a gear
fitted to the pump set, otherwise a separate fuel drive.
storage tank may be used.
The pump may be directly coupled to the motor on
The type of exhaust system and configuration both electric motor drives and diesel engine drives,
depends on whether the pump unit is mobile or thus providing a short close coupling between the
installed permanently. power unit and the pump.
Starting of the engine may be by battery or A flexible coupling may be used where a pump unit
mechanical start depending on the site conditions and a power unit are separated. The flexible
and requirements. coupling is usually mounted on a base plate and
provides easier coupling and alignment.
--``,,```,,,``,```,``,``````,``,-`-`,,`,,`,`,,`---
22 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
V belts, if correctly set up and sized with the power Before the performance can be tested, the priming
to be transmitted, may be suitable for connection should be checked to make sure that the pump can
between the power unit and the pump. Losses be adequately and correctly primed before the motor
incurred should be low. is started. If there is a bleed valve on top of the
Gear drives, such as those used for engine driven pump, this should be opened to provide a physical
shaft drive borehole pumps, should only incur low method for checking that the pump unit is
losses in the gearbox. adequately primed.
10.7 Control and protection equipment The pump discharge at the duty point should be
measured using either a flow meter or flow test
The functions of the control and protection using one of the methods described in Part 3 4) of this
equipment are to provide control for starting and British Standard.
stopping the pumpset and to provide protection for
The operating pressure of the pump unit at the duty
both the pump and the power unit.
point should be checked by reading the pressure
Starting equipment should be suitable for the power gauge fitted to the delivery side of the pump unit.
unit with which it is required to operate. The The pressure reading should be taken in conjunction
equipment should have the facilities to incorporate with the flow rate to make sure that the correct duty
protection when and where necessary. point on the pump characteristic curve is being
Pump protection equipment usually takes the form studied.
of protecting the pump against low or high pressure The vacuum gauge on the suction side of the pump
and against poor discharge resulting from low unit should be read to check that the vacuum being
suction water levels or a depriming of the pump. produced by the pump is correct and conforms to the
An electric motor may be protected against design data.
overload, overheating, over and under voltage, The speed of rotation of the pump unit at the duty
phase imbalance, phase failure, low or high current, point should be checked to make sure that the flow
etc. The specific requirements should be considered and pressure produced are being achieved at the
in relation to reliability, cost etc. correct speed.
An engine may be protected against overload, When the pump unit is running at normal operating
excessive speed, overheating and low oil pressure. conditions, it should be checked for vibration to
The commonest protection facilities for the engine make sure that neither the pump unit nor the power
are overheating of the engine and low oil pressure. unit are vibrating excessively.
Both engine driven pump units and electric driven Pump bearings and glands should be checked for
pump units can be automated if and when required. any overheating. Glands of the packed-gland type
The degree of automation depends upon the should be dripping at the rate recommended by the
supervision requirement at site and general manufacturer.
requirements.
The pump suction should be checked very carefully
Automatic stopping of the pump set is a normal for air entering any of the joints or through any of
feature, where engine protection units are fitted. the fittings. The easiest way to check for leaks is by
This may be achieved by the use of a timer which is applying a soap solution or similar liquid to the
preset to close the engine down at a predetermined suspected leak points.
time. Alternatively the engine may also be closed -
-
-
4)
In preparation.
© BSI 07-1999
Copyright British Standards Institution
23
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
practice. ,
,
,
`
`
,
been caused by the impact of water j ets on overhead
`
`
`
,
`
power lines. The electricity authority should be
12 Safety
`
,
12.1 Introduction
,
-
`
-
`
,
,
` precautions are taken.
Safety in the operation of the irrigation equipment
,
,
`
,
24 © BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
Boom irrigators may present two hazards: height, Centre pivots, being located in one position and
and horizontal distance. The height of the machine rotating about that position, should not present a
when the booms are raised may be 6 m or 9 m above problem once correctly installed.
the ground. This type of machine should not be Linear moves, due to their moving while irrigating,
driven under power lines unless the booms can be should be designed after studying the area to be
kept in the lowered position. The minimum distance irrigated to avoid any potential dangers. Protection
between the boom and power lines should be 15 m equipment should prevent the machine from coming
from the tip of the boom. This distance closer than the recommended distance to hazards.
recommendation may alter depending on the type of
If contact is made between the equipment and a live
boom used, that is whether it rotates while
power line, no one should approach the equipment.
irrigating or moves while irrigating. Ground slopes
The electricity authority should be advised
over which the boom travels may have a particularly
immediately.
dangerous effect on the reaction of the boom to the
ground undulation, in the vicinity of power lines. Warning notices should be fitted to all equipment
Gateways are a common problem area where where a risk could occur.
uneven or sloping ground may exist. The booms, Operators should be made fully aware of the
when being moved, should be anchored at each end dangers of operating near power lines and the
to prevent rotation. potential dangers the equipment presents.
-
-
-
`
,
,
`
,
`
,
,
`
,
,
`
-
`
-
,
`
`
,
`
`
`
`
`
`
,
`
`
,
`
`
`
,
`
`
,
,
,
`
`
`
,
,
`
`
-
-
© BSI 07-1999
Copyright British Standards Institution
25
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
--``,,```,,,``,```,``,``````,``,-`-`,,`,,`,`,,`---
26
Copyright British Standards Institution
blank
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST
BS 7562-5:1993
Informative references
ISO publication
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO) , Geneva. (All publications are available
from BSI Sales.)
ISO 9260:1991, Agricultural irrigation equipment — Emitters — Specification and test methods.
Other references
[1] GREAT BRITAIN. Health and Safety at Work etc. Act 1974. London: HMSO.
--``,,```,,,``,```,``,``````,``,-`-`,,`,,`,`,,`---
© BSI 07-1999
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=AECOM EW & Canada/5906698006, User=Zaraket, Ahmad
No reproduction or networking permitted without license from IHS Not for Resale, 01/16/2016 04:55:36 MST