Professional Documents
Culture Documents
Range: CLCP
1
Quantity
Tag Number UMA #P2-1
Job Comments
Unit Airflow 2780 cfm Min. Htg. & Clg. Face Vel. 394 ft/min
Country of Origin Malaysia Coil Max. Htg Face Vel. 1181 ft/min
Standard Unit Size 005 Coil Max. Clg Face Vel. 689 ft/min
Casing Construction 0.5mm Painted Skin Ext/Int 0.4mm GI Break Point Pricing Field Trigger Break Point Pricing
Efficiency Class
Unit Roof No Diploma Number 04.01.049
Run Acoustics Unit Sound Power Data Shipping Split 6 weight 2506.0 lb
Page 1 of 27
Product Report Print Date: 11-Jun-19
Filter Module Module Position: 1
Filter Media 2" TA, G4: EN779 Filter - Pre-filter PD 0.000 in H2O
Filter Loading Method Side Sliding Method Module End of Unit Back of Unit
Spare Filter (Filter Media) No Filter - Hi-eff Cart or Bag PD 0.000 in H2O
Page 2 of 27
Product Report Print Date: 11-Jun-19
Coil Module Module Position: 2
Coil Mo [2]-1
Coil Section Horizontal Coil Drain Pipe Connection Std (Same as Coil Supply Conn.)
Coil - Sensible Cap. 50.76 MBh Air Pressure Drop 0.263 in H2O
Water Press. Drop 0.83 ft H2O Coil Module Press. Drop 0.263 in H2O
Coil Casing & Coil Support Galvanized Position Flag (First in stream) Coil Not First In Stream
Fouling Factor 0.00000 hr-sq ft-deg F/Btu Design Sequence Pls Delete Result - Coil Updates
Fin Type 1/2" Tube Wavy 3BS (Delta Flo H) 100% Dry Surfac APD 0.263 in H2O
Page 3 of 27
Product Report Print Date: 11-Jun-19
UVC Module Module Position: 3
UVC Mod [3]-1
UVC System Coil & Drainpan disinfection (P) Shipping Split ID 1.00 Number
Voltage 220-240 vac, 50/60Hz, 1Phase (VPC) UVCM length (Price) 18.308 in
Total Current 0.14 A Electrical Safety Devices Include Differential Pressure Air
Flow Switch & Door Switch.
Module Components Yes UVC Electrical Notes UVC Scope Of Supply Includes:
UVC Emitters, Industrial Type
Steel Enclosure, Run-Hour Meter,
Auto-Off-Manual(A-O-M) Selector
Switch, LED Indicator , Starter c/w
Contactor & MCB
Starter Enclosure Type Indoor Weight Factor 0.3 lb
Page 4 of 27
Product Report Print Date: 11-Jun-19
Fan Module Module Position: 4
Fan Mod [4]-1
Motor Class TECO, 3Phase, 4P, PREM Eff (IE3) Casing - 250Hz 69 dB
Total Motor Full Load Amp 6.23 A Fan Discharge - Overall 84 dBA
Motor(Pulley&Belt)
Spare Drive For Stby No Fan Intake - Overall 81 dBA
Motor(Pulley&Belt)
Motor Protection No Velocity for Eurovent Energy 555 ft/min
Calculation
Motor Starter No Housed / Plenum Housed Fan (DIDW)
Page 5 of 27
Product Report Print Date: 11-Jun-19
Motor Termination Box No Fan Size Option Oversize Fan
Fan - Module Weight 512.9 lb Design Sequence Motor Power Input formula update
Discharge - 63Hz 90 dB Position Flag (First in stream) Fan Not First In The Stream
Discharge - 4kHz 79 dB Fan Condition Fan has been designed for design
point.
Discharge - 8kHz 76 dB Module End of Unit Front of Unit
Page 6 of 27
Product Report Print Date: 11-Jun-19
Range: CLCP
1
Quantity
Tag Number D-UMA#1
Job Comments
Country of Origin Malaysia Break Point Pricing Field Trigger Break Point Pricing
Casing Construction 0.5mm Painted Skin Ext/Int 0.4mm GI Diploma Number 04.01.049
EUROVENT- AHU Energy C (2016) Sum of Length for all levels 378.471 in
Efficiency Class
Unit Roof Roof w/ Inlet Hood & Wire Mesh Panel Weight 679.2 lb
Unit Length for Unit Level 2 136.097 in Shipping Split 3 weight 1358.0 lb
Run Acoustics Unit Sound Power Data 1st Shipping Split Length 72.157 in
Coil Target Face Vel. 551 ft/min 6th Shipping Split Length 23.347 in
Min. Htg. & Clg. Face Vel. 394 ft/min 7th Shipping Split Length 17.245 in
Coil Max. Htg Face Vel. 1181 ft/min 8th Shipping Split Length 78.271 in
Page 7 of 27
Product Report Print Date: 11-Jun-19
Fan Module Module Position: 1
Fan Mod [1]-1
Motor Class TECO, 3Phase, 4P, PREM Eff (IE3) Casing - 250Hz 86 dB
Total Motor Full Load Amp 23.40 A Fan Discharge - Overall 97 dBA
Motor(Pulley&Belt)
Spare Drive For Stby No Fan Intake - Overall 95 dBA
Motor(Pulley&Belt)
Motor Protection No Velocity for Eurovent Energy 496 ft/min
Calculation
Motor Starter No Housed / Plenum Housed Fan (DIDW)
Page 8 of 27
Product Report Print Date: 11-Jun-19
Motor Termination Box No Fan Size Option Oversize Fan
Fan - Module Weight 2098.0 lb Design Sequence Motor Power Input formula update
Discharge - 63Hz 96 dB Position Flag (First in stream) Fan Not First In The Stream
Discharge - 4kHz 86 dB Fan Condition Fan has been designed for design
point.
Discharge - 8kHz 80 dB Module End of Unit Back of Unit
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Drain Pan No Position Flag (First in stream) Blank Module Not First In The
Stream
Additional Inlet/Outlet No Blank Module Application Service Section
Page 9 of 27
Product Report Print Date: 11-Jun-19
Break Point Module Module Position: 5
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Page 10 of 27
Product Report Print Date: 11-Jun-19
Filter Module Module Position: 9
Filter Media 2" TA, G4: EN779 Filter - Pre-filter PD 0.000 in H2O
Filter Loading Method Side Sliding Method Module End of Unit Front of Unit
Spare Filter (Filter Media) No Filter - Hi-eff Cart or Bag PD 0.000 in H2O
Intake Section Back Damper and Front FFO (VPC) INMD length (Price) 24.411 in
Actuator
Intake Module CFM 20825 cfm Weight Factor 0.6 lb
Page 11 of 27
Product Report Print Date: 11-Jun-19
Filter Module Module Position: 11
Filter Media 2" TA, G4: EN779 Filter - Pre-filter PD 0.000 in H2O
Filter Loading Method Side Sliding Method Filter Manufacturer Factory Default
Door Handle Type Std. Latched Position Flag (First in stream) Filter Not First in Stream
Drain Pan No Position Flag (First in stream) Blank Module Not First In The
Stream
Additional Inlet/Outlet No Blank Module Application Service Section
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Page 12 of 27
Product Report Print Date: 11-Jun-19
Break Point Module Module Position: 14
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Page 13 of 27
Product Report Print Date: 11-Jun-19
Coil Module Module Position: 18
Coil M [18]-1
Coil Section Horizontal Coil Drain Pipe Connection Std (Same as Coil Supply Conn.)
Coil - Sensible Cap. 608.92 MBh Air Pressure Drop 0.693 in H2O
Water Press. Drop 19.51 ft H2O Coil Module Press. Drop 0.693 in H2O
Coil Casing & Coil Support Galvanized Position Flag (First in stream) Coil Not First In Stream
Fouling Factor 0.00000 hr-sq ft-deg F/Btu Design Sequence Pls Delete Result - Coil Updates
Fin Type 1/2" Tube Wavy 3BS (Delta Flo H) 100% Dry Surfac APD 0.476 in H2O
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Page 14 of 27
Product Report Print Date: 11-Jun-19
Break Point Module Module Position: 20
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
UVC System Coil & Drainpan disinfection (P) Shipping Split Type Factory Split
Total Current 0.60 A Electrical Safety Devices Include Differential Pressure Air
Flow Switch & Door Switch.
Module Components Yes UVC Electrical Notes UVC Scope Of Supply Includes:
UVC Emitters, Industrial Type
Steel Enclosure, Run-Hour Meter,
Auto-Off-Manual(A-O-M) Selector
Switch, LED Indicator , Starter c/w
Contactor & MCB
Starter Enclosure Type Outdoor Weight Factor 0.6 lb
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Page 15 of 27
Product Report Print Date: 11-Jun-19
Fan Module Module Position: 24
Fan Mo [24]-1
Motor Class TECO, 3Phase, 4P, PREM Eff (IE3) Casing - 250Hz 86 dB
Total Motor Full Load Amp 35.10 A Fan Discharge - Overall 98 dBA
Motor(Pulley&Belt)
Spare Drive For Stby No Fan Intake - Overall 97 dBA
Motor(Pulley&Belt)
Motor Protection No Velocity for Eurovent Energy 496 ft/min
Calculation
Motor Starter No Housed / Plenum Housed Fan (DIDW)
Page 16 of 27
Product Report Print Date: 11-Jun-19
Motor Termination Box No Fan Size Option Oversize Fan
Fan - Module Weight 2446.4 lb Design Sequence Motor Power Input formula update
Discharge - 63Hz 98 dB Position Flag (First in stream) Fan Not First In The Stream
Discharge - 4kHz 88 dB Fan Condition Fan has been designed for design
point.
Discharge - 8kHz 82 dB Module End of Unit Front of Unit
Page 17 of 27
Product Report Print Date: 11-Jun-19
Range: CLCP
1
Quantity
Tag Number D-UMA #2
Job Comments
Unit Airflow 20400 cfm Coil Max. Clg Face Vel. 689 ft/min
Standard Unit Size 035 Break Point Pricing Field Trigger Break Point Pricing
Casing Construction 0.5mm Painted Skin Ext/Int 0.4mm GI CAL Class + 700 -
Efficiency Class
Unit Roof Roof w/ Inlet Hood & Wire Mesh Sum of Length for all levels 370.912 in
Unit Length for Unit Level 2 131.058 in Shipping Split 2 weight 196.8 lb
Run Acoustics Unit Sound Power Data Shipping Split 8 weight 2506.0 lb
Coil Target Face Vel. 551 ft/min 5th Shipping Split Length 35.553 in
Min. Htg. & Clg. Face Vel. 394 ft/min 6th Shipping Split Length 78.271 in
Page 18 of 27
Product Report Print Date: 11-Jun-19
Fan Module Module Position: 1
Fan Mod [1]-1
Motor Class TECO, 3Phase, 4P, PREM Eff (IE3) Casing - 250Hz 86 dB
Total Motor Full Load Amp 23.40 A Fan Discharge - Overall 96 dBA
Motor(Pulley&Belt)
Spare Drive For Stby No Fan Intake - Overall 95 dBA
Motor(Pulley&Belt)
Motor Protection No Velocity for Eurovent Energy 486 ft/min
Calculation
Motor Starter No Housed / Plenum Housed Fan (DIDW)
Page 19 of 27
Product Report Print Date: 11-Jun-19
Motor Termination Box No Fan Size Option Oversize Fan
Fan - Module Weight 2098.0 lb Design Sequence Motor Power Input formula update
Discharge - 63Hz 96 dB Position Flag (First in stream) Fan Not First In The Stream
Discharge - 4kHz 86 dB Fan Condition Fan has been designed for design
point.
Discharge - 8kHz 79 dB Module End of Unit Back of Unit
Drain Pan No Position Flag (First in stream) Blank Module Not First In The
Stream
Additional Inlet/Outlet No Blank Module Application Service Section
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Page 20 of 27
Product Report Print Date: 11-Jun-19
Break Point Module Module Position: 5
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Break Point Type Std Unit Front Airflow Front Air Entering
Break Point Section Length 2.520 in Unit Back Airflow Back Air Leaving
Filter Media 2" TA, G4: EN779 Filter - Pre-filter PD 0.000 in H2O
Filter Loading Method Side Sliding Method Module End of Unit Front of Unit
Spare Filter (Filter Media) No Filter - Hi-eff Cart or Bag PD 0.000 in H2O
Page 21 of 27
Product Report Print Date: 11-Jun-19
Intake Module Module Position: 8
Intake Section Back Damper and Front FFO (VPC) INMD length (Price) 26.930 in
Actuator
Intake Module CFM 20400 cfm Design Sequence A
Filter Media 2" TA, G4: EN779 Filter - Pre-filter PD 0.000 in H2O
Filter Loading Method Side Sliding Method Filter Manufacturer Factory Default
Door Handle Type Std. Latched Position Flag (First in stream) Filter Not First in Stream
Drain Pan No Position Flag (First in stream) Blank Module Not First In The
Stream
Additional Inlet/Outlet No Blank Module Application Service Section
Page 22 of 27
Product Report Print Date: 11-Jun-19
Break Point Module Module Position: 11
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Page 23 of 27
Product Report Print Date: 11-Jun-19
Coil Module Module Position: 16
Coil M [16]-1
Coil Section Horizontal Coil Drain Pipe Connection Std (Same as Coil Supply Conn.)
Coil - Sensible Cap. 599.14 MBh Air Pressure Drop 0.672 in H2O
Water Press. Drop 19.01 ft H2O Coil Module Press. Drop 0.672 in H2O
Coil Casing & Coil Support Galvanized Position Flag (First in stream) Coil Not First In Stream
Fouling Factor 0.00000 hr-sq ft-deg F/Btu Design Sequence Pls Delete Result - Coil Updates
Fin Type 1/2" Tube Wavy 3BS (Delta Flo H) 100% Dry Surfac APD 0.460 in H2O
Page 24 of 27
Product Report Print Date: 11-Jun-19
UVC Module Module Position: 17
UVC Mo [17]-1
UVC System Coil & Drainpan disinfection (P) Shipping Split Type Factory Split
Total Current 0.60 A Electrical Safety Devices Include Differential Pressure Air
Flow Switch & Door Switch.
Module Components Yes UVC Electrical Notes UVC Scope Of Supply Includes:
UVC Emitters, Industrial Type
Steel Enclosure, Run-Hour Meter,
Auto-Off-Manual(A-O-M) Selector
Switch, LED Indicator , Starter c/w
Contactor & MCB
Starter Enclosure Type Outdoor Weight Factor 0.6 lb
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Break Point Type Std Unit Front Airflow Front Air Leaving
Break Point Section Length 2.520 in Unit Back Airflow Back Air Entering
Page 25 of 27
Product Report Print Date: 11-Jun-19
Fan Module Module Position: 20
Fan Mo [20]-1
Motor Class TECO, 3Phase, 4P, PREM Eff (IE3) Casing - 250Hz 85 dB
Total Motor Full Load Amp 35.10 A Fan Discharge - Overall 98 dBA
Motor(Pulley&Belt)
Spare Drive For Stby No Fan Intake - Overall 97 dBA
Motor(Pulley&Belt)
Motor Protection No Velocity for Eurovent Energy 486 ft/min
Calculation
Motor Starter No Housed / Plenum Housed Fan (DIDW)
Page 26 of 27
Product Report Print Date: 11-Jun-19
Motor Termination Box No Fan Size Option Oversize Fan
Fan - Module Weight 2446.4 lb Design Sequence Motor Power Input formula update
Discharge - 63Hz 98 dB Position Flag (First in stream) Fan Not First In The Stream
Discharge - 4kHz 87 dB Fan Condition Fan has been designed for design
point.
Discharge - 8kHz 81 dB Module End of Unit Front of Unit
Page 27 of 27