You are on page 1of 70

TECHNICAL SPECIFICATION SHEET

Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC


Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-2F-S REST KIT-05 06 Unit No. 20-ST-LAC-1509-06401-1
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3480 mm 1340 mm 840 mm 1656 mm 699 kg
Nominal Airflow 3600 m3/h Nominal Airflow 0 m3/h
Supply ESP 150 Pa Return ESP 0 Pa
Velocity 1.15 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1340 mm 840 mm 313 kg
B 1740 mm 1340 mm 840 mm 387 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 5000 B 75 Pa
QTY / Width x Height Length
1 / 1243 x 540 620 mm
Weight Efficiency
90 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 1 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-2F-S REST KIT-05 06 Unit No. 20-ST-LAC-1509-06401-1
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 680 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.34 m/s Clean 37.03 Pa 2 / 610x610
Type Synthetic pre filter Withdrawal Side Design 93.51 Pa
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.34 m/s Clean 66.12 Pa 2 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 183.06 Pa
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2610.82 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.34 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 158.70 Pa 229.35 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
2 / 610x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 2 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-2F-S REST KIT-05 06 Unit No. 20-ST-LAC-1509-06401-1
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 53.71%
Model SYQ250R Motor Design. Q2E100L2C Fan Eff. 56.82%
Fan Make Yilida Motor Make WAT Outlet Velocity 9.6 m/s
Impeller Diam. 250 mm Drive Type Belt Drive ESP 150 Pa
Quantity 1 Poles 2 TSP 975 Pa
Duty % Per Fan Single Fan Motor Power 3.00 kW Fan Dynamic Pr. 57 Pa
Air Flow 3600 m3/h Input Power 2.38 kW Total Pressure 1032Pa
Fan Speed 3508 rpm Motor Speed 2885 rpm
Fan max speed 4100 rpm Motor Eff. 85%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 322 x 322 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 1.82 kW FLC 5.80A
Motor Base Q2E100L2C/3.00kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 140 / 2012 Dia 20Motor pulley/Bush 2 SPA 170 / 2012 Dia 28 Belt 2 SPA 1382 C/C 446 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 107.38 96.11 93.88 92.02 88.44 85.79 82.86 79.41
Outlet (2) 112.3 101.19 95 99.52 91.39 87.6 83.9 79.97
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
101.1
Outlet Sound Power(dB) 95.42 99.52 91.39 87.6 83.9 79.97 99
9
Inlet Sound Power(dB) 89.11 85.88 83.02 79.44 70.79 66.86 61.41 84
Airborne sound power (dB) 96.11 93.88 92.02 88.44 85.79 82.86 79.41 94
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power .91 kW Absorbed Power NaN kW
Air Volume 3600 m3/h Air Volume m3/h
AHU SFP 1.19 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 3 of 70


16/09/2020 ClimaUno Page 4 of 70
16/09/2020 ClimaUno Page 5 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-S REST KIT-01 Unit No. 20-ST-LAC-1509-06401-2
Model box CU EC 30 Unit Model CU-EC-87
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3580 mm 1970 mm 1100 mm 1751 mm 1051 kg
Nominal Airflow 7200 m3/h Nominal Airflow 0 m3/h
Supply ESP 350 Pa Return ESP 0 Pa
Velocity 1.11 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1970 mm 1100 mm 437 kg
B 1840 mm 1970 mm 1100 mm 614 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 7500 B 75 Pa
QTY / Width x Height Length
1 / 1790 x 540 620 mm
Weight Efficiency
122 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 6 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-S REST KIT-01 Unit No. 20-ST-LAC-1509-06401-2
Model box CU EC 30 Unit Model CU-EC-87
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 940 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.79 m/s Clean 49.37 Pa 3 / 610x610
Type Synthetic pre filter Withdrawal Side Design 99.68 Pa
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.79 m/s Clean 88.17 Pa 3 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 194.08 Pa
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2773.09 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 940 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.79 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 211.61 Pa 255.80 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
3 / 610x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 7 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-S REST KIT-01 Unit No. 20-ST-LAC-1509-06401-2
Model box CU EC 30 Unit Model CU-EC-87
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 70.59%
Model SYQ355R Motor Design. Q2E132M4B Fan Eff. 74.06%
Fan Make Yilida Motor Make WAT Outlet Velocity 9.8 m/s
Impeller Diam. 355 mm Drive Type Belt Drive ESP 350 Pa
Quantity 1 Poles 4 TSP 1175 Pa
Duty % Per Fan Single Fan Motor Power 5.50 kW Fan Dynamic Pr. 58 Pa
Air Flow 7200 m3/h Input Power 4.11 kW Total Pressure 1233Pa
Fan Speed 2479 rpm Motor Speed 1460 rpm
Fan max speed 2800 rpm Motor Eff. 88%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 453 x 453 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 3.33 kW FLC 11.30A
Motor Base Q2E132M4B/5.50kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 106 / 1610 Dia 30Motor pulley/Bush 2 SPA 180 / 2012 Dia 38 Belt 2 SPA 957 C/C 250 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 92.13 83.75 79.23 91.86 81.82 80.77 76.6 70.08
Outlet (2) 96.7 88.53 81 95.05 84.24 82.21 77.36 70.54
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 940 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 88.53 80.61 95.05 84.24 82.21 77.36 70.54 93
Inlet Sound Power(dB) 76.75 71.23 82.86 72.82 65.77 60.6 52.08 81
Airborne sound power (dB) 83.75 79.23 91.86 81.82 80.77 76.6 70.08 91
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 2.19 kW Absorbed Power NaN kW
Air Volume 7200 m3/h Air Volume m3/h
AHU SFP 1.35 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 8 of 70


16/09/2020 ClimaUno Page 9 of 70
16/09/2020 ClimaUno Page 10 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-CAFE-01 Unit No. 20-ST-LAC-1509-06401-3
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3330 mm 1030 mm 830 mm 1654 mm 543 kg
Nominal Airflow 2160 m3/h Nominal Airflow 0 m3/h
Supply ESP 350 Pa Return ESP 0 Pa
Velocity 0.92 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1030 mm 830 mm 239 kg
B 1590 mm 1030 mm 830 mm 304 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 2500 B 75 Pa
QTY / Width x Height Length
1 / 694 x 540 620 mm
Weight Efficiency
55 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 11 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-CAFE-01 Unit No. 20-ST-LAC-1509-06401-3
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 670 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.07 m/s Clean 29.62 Pa 1 / 610x610
Type Synthetic pre filter Withdrawal Side Design 89.81 Pa 1 / 305x610
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.07 m/s Clean 52.90 Pa 1 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 176.45 Pa 1 / 305x610
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2513.49 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.07 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 126.96 Pa 213.48 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
1 / 610x610 1 / 305x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 12 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-CAFE-01 Unit No. 20-ST-LAC-1509-06401-3
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 55.68%
Model SYQ225R Motor Design. Q2E90L2D Fan Eff. 57.19%
Fan Make Yilida Motor Make WAT Outlet Velocity 7.2 m/s
Impeller Diam. 225 mm Drive Type Belt Drive ESP 350 Pa
Quantity 1 Poles 2 TSP 1175 Pa
Duty % Per Fan Single Fan Motor Power 2.20 kW Fan Dynamic Pr. 32 Pa
Air Flow 2160 m3/h Input Power 1.70 kW Total Pressure 1207Pa
Fan Speed 3857 rpm Motor Speed 2880 rpm
Fan max speed 4500 rpm Motor Eff. 83%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 288 x 288 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 1.27 kW FLC 4.40A
Motor Base Q2E90L2D/2.20kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 106 / 1610 Dia 20Motor pulley/Bush 2 SPA 132 / 2012 Dia 24 Belt 2 SPA 1120 C/C 370 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 105.76 95.14 93.49 89.92 85.58 84.01 80.54 77.58
Outlet (2) 110.9 100.32 95 93.37 88.82 86.28 81.96 78.59
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
100.3
Outlet Sound Power(dB) 95.25 93.37 88.82 86.28 81.96 78.59 95
2
Inlet Sound Power(dB) 88.14 85.49 80.92 76.58 69.01 64.54 59.58 83
Airborne sound power (dB) 95.14 93.49 89.92 85.58 84.01 80.54 77.58 92
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power .69 kW Absorbed Power NaN kW
Air Volume 2160 m3/h Air Volume m3/h
AHU SFP 1.54 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 13 of 70


16/09/2020 ClimaUno Page 14 of 70
16/09/2020 ClimaUno Page 15 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-B COOK-01 Unit No. 20-ST-LAC-1509-06401-4
Model box CU EC 50 Unit Model CU-EC-207
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3950 mm 2030 mm 1800 mm 1898 mm 1698 kg
Nominal Airflow 20336 m3/h Nominal Airflow 0 m3/h
Supply ESP 400 Pa Return ESP 0 Pa
Velocity 1.83 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 50mm TB Corner Profile - Al Panel Insulation 46mm polyurethane 44kg/m3
Panel External Sheet PPGI 0.8mm Panel Internal Sheet SS304 0.8mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L3 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1800 mm 2030 mm 1800 mm 609 kg
B 2150 mm 2030 mm 1800 mm 1089 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 7500 B 75 Pa
QTY / Width x Height Length
2 / 1790 x 540 620 mm
Weight Efficiency
244 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 16 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-B COOK-01 Unit No. 20-ST-LAC-1509-06401-4
Model box CU EC 50 Unit Model CU-EC-207
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 1600 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 2.02 m/s Clean 55.78 Pa 6 / 610x610
Type Synthetic pre filter Withdrawal Side Design 102.89 Pa 3 / 610x305
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 2.02 m/s Clean 99.61 Pa 6 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 199.80 Pa 3 / 610x305
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2857.39 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 1600 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
2.02 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 239.07 Pa 269.53 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
6 / 610x610 3 / 610x305 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 17 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-B COOK-01 Unit No. 20-ST-LAC-1509-06401-4
Model box CU EC 50 Unit Model CU-EC-207
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 72.05%
Model SYQ560R Motor Design. Q2E160L4A Fan Eff. 76.42%
Fan Make Yilida Motor Make WAT Outlet Velocity 11.1 m/s
Impeller Diam. 560 mm Drive Type Belt Drive ESP 400 Pa
Quantity 1 Poles 4 TSP 1225 Pa
Duty % Per Fan Single Fan Motor Power 15.00 kW Fan Dynamic Pr. 74 Pa
Air Flow 20336 m3/h Input Power 11.47 kW Total Pressure 1299Pa
Fan Speed 1634 rpm Motor Speed 1460 rpm
Fan max speed 1800 rpm Motor Eff. 91%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 715 x 715 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 9.60 kW FLC 28.80A
Motor Base Q2E160L4A/15.00kW

DRIVE DETAILS
Fan pulley/Bush 3 SPB 125 / 2012 Dia 40Motor pulley/Bush 3 SPB 140 / 2012 Dia 42 Belt 3 SPB 1250 C/C 306 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 82.58 80.82 78.5 90.72 82.75 80.1 75.21 69.24
Outlet (2) 87.26 85.72 80 94.01 85.29 81.67 76.09 69.82
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 1600 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 85.72 79.99 94.01 85.29 81.67 76.09 69.82 93
Inlet Sound Power(dB) 73.82 70.5 81.72 73.75 65.1 59.21 51.24 80
Airborne sound power (dB) 80.82 78.5 90.72 82.75 80.1 75.21 69.24 90
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 6.81 kW Absorbed Power NaN kW
Air Volume 20336 m3/h Air Volume m3/h
AHU SFP 1.44 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 18 of 70


16/09/2020 ClimaUno Page 19 of 70
16/09/2020 ClimaUno Page 20 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-PASTRY-01 Unit No. 20-ST-LAC-1509-06401-5
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3330 mm 1030 mm 830 mm 1637 mm 432 kg
Nominal Airflow 2347 m3/h Nominal Airflow 0 m3/h
Supply ESP 400 Pa Return ESP 0 Pa
Velocity 1 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 0.6mm Panel Internal Sheet SS304 0.6mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1030 mm 830 mm 185 kg
B 1590 mm 1030 mm 830 mm 247 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 2500 B 75 Pa
QTY / Width x Height Length
1 / 694 x 540 620 mm
Weight Efficiency
55 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 21 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-PASTRY-01 Unit No. 20-ST-LAC-1509-06401-5
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 670 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.17 m/s Clean 32.18 Pa 1 / 610x610
Type Synthetic pre filter Withdrawal Side Design 91.09 Pa 1 / 305x610
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.17 m/s Clean 57.47 Pa 1 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 178.73 Pa 1 / 305x610
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2547.10 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.17 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 137.94 Pa 218.97 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
1 / 610x610 1 / 305x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 22 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-PASTRY-01 Unit No. 20-ST-LAC-1509-06401-5
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 55.97%
Model SYQ225R Motor Design. Q2E90L2D Fan Eff. 57.69%
Fan Make Yilida Motor Make WAT Outlet Velocity 7.9 m/s
Impeller Diam. 225 mm Drive Type Belt Drive ESP 400 Pa
Quantity 1 Poles 2 TSP 1225 Pa
Duty % Per Fan Single Fan Motor Power 2.20 kW Fan Dynamic Pr. 38 Pa
Air Flow 2347 m3/h Input Power 1.91 kW Total Pressure 1263Pa
Fan Speed 3988 rpm Motor Speed 2880 rpm
Fan max speed 4500 rpm Motor Eff. 83%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 288 x 288 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 1.43 kW FLC 4.40A
Motor Base Q2E90L2D/2.20kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 100 / 1610 Dia 20Motor pulley/Bush 2 SPA 132 / 2012 Dia 24 Belt 2 SPA 1107 C/C 370 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 106.7 96.23 94.56 90.87 86.6 84.68 81.39 78.36
Outlet (2) 111.87 101.49 96 94.61 89.84 86.84 82.74 79.25
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
101.4
Outlet Sound Power(dB) 96.32 94.61 89.84 86.84 82.74 79.25 96
9
Inlet Sound Power(dB) 89.23 86.56 81.87 77.6 69.68 65.39 60.36 84
Airborne sound power (dB) 96.23 94.56 90.87 86.6 84.68 81.39 78.36 93
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power .82 kW Absorbed Power NaN kW
Air Volume 2347 m3/h Air Volume m3/h
AHU SFP 1.68 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 23 of 70


16/09/2020 ClimaUno Page 24 of 70
16/09/2020 ClimaUno Page 25 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-BANQ FIN KIT-01 Unit No. 20-ST-LAC-1509-06401-6
Model box CU EC 30 Unit Model CU-EC-87
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3580 mm 1970 mm 1100 mm 1703 mm 827 kg
Nominal Airflow 7132 m3/h Nominal Airflow 0 m3/h
Supply ESP 400 Pa Return ESP 0 Pa
Velocity 1.1 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 0.6mm Panel Internal Sheet SS304 0.6mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1970 mm 1100 mm 344 kg
B 1840 mm 1970 mm 1100 mm 483 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 7500 B 75 Pa
QTY / Width x Height Length
1 / 1790 x 540 620 mm
Weight Efficiency
122 Kg 95 %
001 ACCESSORIES
UV Lamp fro ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 26 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-BANQ FIN KIT-01 Unit No. 20-ST-LAC-1509-06401-6
Model box CU EC 30 Unit Model CU-EC-87
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 940 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.77 m/s Clean 48.90 Pa 3 / 610x610
Type Synthetic pre filter Withdrawal Side Design 99.45 Pa
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.77 m/s Clean 87.33 Pa 3 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 193.66 Pa
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2766.96 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 940 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.77 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 209.61 Pa 254.80 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
3 / 610x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 27 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-BANQ FIN KIT-01 Unit No. 20-ST-LAC-1509-06401-6
Model box CU EC 30 Unit Model CU-EC-87
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 70.82%
Model SYQ355R Motor Design. Q2E132S2C Fan Eff. 74.10%
Fan Make Yilida Motor Make WAT Outlet Velocity 9.7 m/s
Impeller Diam. 355 mm Drive Type Belt Drive ESP 400 Pa
Quantity 1 Poles 2 TSP 1225 Pa
Duty % Per Fan Single Fan Motor Power 5.50 kW Fan Dynamic Pr. 57 Pa
Air Flow 7132 m3/h Input Power 4.29 kW Total Pressure 1282Pa
Fan Speed 2513 rpm Motor Speed 2935 rpm
Fan max speed 2800 rpm Motor Eff. 87%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 453 x 453 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 3.43 kW FLC 10.20A
Motor Base Q2E132S2C/5.50kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 118 / 1610 Dia 30Motor pulley/Bush 2 SPA 100 / 1610 Dia 38 Belt 2 SPA 857 C/C 250 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 92.52 84.07 79.62 92.28 82.11 81.12 76.97 70.7
Outlet (2) 97.2 88.87 81 95.26 84.77 82.88 77.96 71.39
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 940 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 88.87 81.08 95.26 84.77 82.88 77.96 71.39 94
Inlet Sound Power(dB) 77.07 71.62 83.28 73.11 66.12 60.97 52.7 81
Airborne sound power (dB) 84.07 79.62 92.28 82.11 81.12 76.97 70.7 91
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 2.3 kW Absorbed Power NaN kW
Air Volume 7132 m3/h Air Volume m3/h
AHU SFP 1.45 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 28 of 70


16/09/2020 ClimaUno Page 29 of 70
16/09/2020 ClimaUno Page 30 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-STAF DIN KIT-01 Unit No. 20-ST-LAC-1509-06401-7
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3480 mm 1340 mm 840 mm 1648 mm 697 kg
Nominal Airflow 3697 m3/h Nominal Airflow 0 m3/h
Supply ESP 400 Pa Return ESP 0 Pa
Velocity 1.18 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1340 mm 840 mm 314 kg
B 1740 mm 1340 mm 840 mm 383 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 5000 B 75 Pa
QTY / Width x Height Length
1 / 1243 x 540 620 mm
Weight Efficiency
90 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 31 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-STAF DIN KIT-01 Unit No. 20-ST-LAC-1509-06401-7
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 680 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.38 m/s Clean 38.02 Pa 2 / 610x610
Type Synthetic pre filter Withdrawal Side Design 94.01 Pa
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.38 m/s Clean 67.90 Pa 2 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 183.95 Pa
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2623.94 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.38 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 162.97 Pa 231.48 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
2 / 610x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 32 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-STAF DIN KIT-01 Unit No. 20-ST-LAC-1509-06401-7
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 55.03%
Model SYQ250R Motor Design. Q2E100L2C Fan Eff. 57.71%
Fan Make Yilida Motor Make WAT Outlet Velocity 9.9 m/s
Impeller Diam. 250 mm Drive Type Belt Drive ESP 400 Pa
Quantity 1 Poles 2 TSP 1225 Pa
Duty % Per Fan Single Fan Motor Power 3.00 kW Fan Dynamic Pr. 60 Pa
Air Flow 3697 m3/h Input Power 2.99 kW Total Pressure 1285Pa
Fan Speed 3811 rpm Motor Speed 2885 rpm
Fan max speed 4100 rpm Motor Eff. 85%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 322 x 322 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 2.29 kW FLC 5.80A
Motor Base Q2E100L2C/3.00kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 106 / 1610 Dia 20Motor pulley/Bush 2 SPA 132 / 2012 Dia 28 Belt 2 SPA 1272 C/C 446 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 109.39 98.42 96.35 93.9 90.13 87.59 84.61 81.26
Outlet (2) 114.15 103.42 98 101.23 92.98 89.35 85.61 81.84
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
103.4 101.2
Outlet Sound Power(dB) 97.86 92.98 89.35 85.61 81.84 101
2 3
Inlet Sound Power(dB) 91.42 88.35 84.9 81.13 72.59 68.61 63.26 86
Airborne sound power (dB) 98.42 96.35 93.9 90.13 87.59 84.61 81.26 96
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 1.39 kW Absorbed Power NaN kW
Air Volume 3697 m3/h Air Volume m3/h
AHU SFP 1.77 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 33 of 70


16/09/2020 ClimaUno Page 34 of 70
16/09/2020 ClimaUno Page 35 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-P WASH B KIT-01 Unit No. 20-ST-LAC-1509-06401-8
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3330 mm 1030 mm 830 mm 1654 mm 543 kg
Nominal Airflow 2250 m3/h Nominal Airflow 0 m3/h
Supply ESP 350 Pa Return ESP 0 Pa
Velocity 0.96 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1030 mm 830 mm 239 kg
B 1590 mm 1030 mm 830 mm 304 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 2500 B 75 Pa
QTY / Width x Height Length
1 / 694 x 540 620 mm
Weight Efficiency
55 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 36 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-P WASH B KIT-01 Unit No. 20-ST-LAC-1509-06401-8
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 670 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.12 m/s Clean 30.85 Pa 1 / 610x610
Type Synthetic pre filter Withdrawal Side Design 90.42 Pa 1 / 305x610
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.12 m/s Clean 55.10 Pa 1 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 177.55 Pa 1 / 305x610
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2529.64 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.12 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 132.25 Pa 216.12 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
1 / 610x610 1 / 305x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 37 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-P WASH B KIT-01 Unit No. 20-ST-LAC-1509-06401-8
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 55.90%
Model SYQ225R Motor Design. Q2E90L2D Fan Eff. 57.55%
Fan Make Yilida Motor Make WAT Outlet Velocity 7.5 m/s
Impeller Diam. 225 mm Drive Type Belt Drive ESP 350 Pa
Quantity 1 Poles 2 TSP 1175 Pa
Duty % Per Fan Single Fan Motor Power 2.20 kW Fan Dynamic Pr. 35 Pa
Air Flow 2250 m3/h Input Power 1.75 kW Total Pressure 1210Pa
Fan Speed 3888 rpm Motor Speed 2880 rpm
Fan max speed 4500 rpm Motor Eff. 83%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 288 x 288 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 1.31 kW FLC 4.40A
Motor Base Q2E90L2D/2.20kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 106 / 1610 Dia 20Motor pulley/Bush 2 SPA 132 / 2012 Dia 24 Belt 2 SPA 1120 C/C 370 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 106 95.48 93.81 90.17 85.88 84.07 80.72 77.71
Outlet (2) 111.15 100.7 96 93.8 89.1 86.25 82.08 78.63
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 100.7 95.56 93.8 89.1 86.25 82.08 78.63 96
Inlet Sound Power(dB) 88.48 85.81 81.17 76.88 69.07 64.72 59.71 83
Airborne sound power (dB) 95.48 93.81 90.17 85.88 84.07 80.72 77.71 93
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power .72 kW Absorbed Power NaN kW
Air Volume 2250 m3/h Air Volume m3/h
AHU SFP 1.54 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 38 of 70


16/09/2020 ClimaUno Page 39 of 70
16/09/2020 ClimaUno Page 40 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-WASTE RM-01 Unit No. 20-ST-LAC-1509-06401-9
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3330 mm 1030 mm 830 mm 1667 mm 549 kg
Nominal Airflow 1761 m3/h Nominal Airflow 0 m3/h
Supply ESP 300 Pa Return ESP 0 Pa
Velocity 0.75 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1030 mm 830 mm 239 kg
B 1590 mm 1030 mm 830 mm 310 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 2500 B 75 Pa
QTY / Width x Height Length
1 / 694 x 540 620 mm
Weight Efficiency
55 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 41 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-WASTE RM-01 Unit No. 20-ST-LAC-1509-06401-9
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 670 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 0.88 m/s Clean 24.15 Pa 1 / 610x610
Type Synthetic pre filter Withdrawal Side Design 87.07 Pa 1 / 305x610
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 0.88 m/s Clean 43.13 Pa 1 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 171.56 Pa 1 / 305x610
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2441.47 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
0.88 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 103.51 Pa 201.75 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
1 / 610x610 1 / 305x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 42 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-WASTE RM-01 Unit No. 20-ST-LAC-1509-06401-9
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 54.88%
Model SYQ200R Motor Design. Q2E90L2C Fan Eff. 56.53%
Fan Make Yilida Motor Make WAT Outlet Velocity 7.5 m/s
Impeller Diam. 200 mm Drive Type Belt Drive ESP 300 Pa
Quantity 1 Poles 2 TSP 1125 Pa
Duty % Per Fan Single Fan Motor Power 1.50 kW Fan Dynamic Pr. 34 Pa
Air Flow 1761 m3/h Input Power 1.40 kW Total Pressure 1159Pa
Fan Speed 4246 rpm Motor Speed 2890 rpm
Fan max speed 4500 rpm Motor Eff. 81%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 256 x 256 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 1.00 kW FLC 3.30A
Motor Base Q2E90L2C/1.50kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 170 / 2012 Dia 20Motor pulley/Bush 2 SPA 250 / 2517 Dia 24 Belt 2 SPA 1357 C/C 346 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 105.07 94.48 92.81 89.24 84.97 83.19 79.83 76.73
Outlet (2) 109.76 99.36 94 92.78 88.26 85.57 81.2 77.76
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 99.36 94.36 92.78 88.26 85.57 81.2 77.76 95
Inlet Sound Power(dB) 87.48 84.81 80.24 75.97 68.19 63.83 58.73 82
Airborne sound power (dB) 94.48 92.81 89.24 84.97 83.19 79.83 76.73 92
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power .49 kW Absorbed Power NaN kW
Air Volume 1761 m3/h Air Volume m3/h
AHU SFP 1.41 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 43 of 70


16/09/2020 ClimaUno Page 44 of 70
16/09/2020 ClimaUno Page 45 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-WARE WASH-01 Unit No. 20-ST-LAC-1509-06401-10
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3480 mm 1030 mm 830 mm 1730 mm 569 kg
Nominal Airflow 2970 m3/h Nominal Airflow 0 m3/h
Supply ESP 300 Pa Return ESP 0 Pa
Velocity 1.27 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1030 mm 830 mm 239 kg
B 1740 mm 1030 mm 830 mm 330 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 2500 B 75 Pa
QTY / Width x Height Length
1 / 694 x 540 620 mm
Weight Efficiency
55 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 46 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-WARE WASH-01 Unit No. 20-ST-LAC-1509-06401-10
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 670 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.48 m/s Clean 40.73 Pa 1 / 610x610
Type Synthetic pre filter Withdrawal Side Design 95.36 Pa 1 / 305x610
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.48 m/s Clean 72.74 Pa 1 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 186.37 Pa 1 / 305x610
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2659.53 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.48 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 174.57 Pa 237.28 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
1 / 610x610 1 / 305x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 47 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-WARE WASH-01 Unit No. 20-ST-LAC-1509-06401-10
Model box CU EC 30 Unit Model CU-EC-34
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 54.16%
Model SYQ225R Motor Design. Q2E100L2C Fan Eff. 57.06%
Fan Make Yilida Motor Make WAT Outlet Velocity 10.0 m/s
Impeller Diam. 225 mm Drive Type Belt Drive ESP 300 Pa
Quantity 1 Poles 2 TSP 1125 Pa
Duty % Per Fan Single Fan Motor Power 3.00 kW Fan Dynamic Pr. 60 Pa
Air Flow 2970 m3/h Input Power 2.24 kW Total Pressure 1185Pa
Fan Speed 4143 rpm Motor Speed 2885 rpm
Fan max speed 4500 rpm Motor Eff. 85%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 288 x 288 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 1.71 kW FLC 5.80A
Motor Base Q2E100L2C/3.00kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 132 / 2012 Dia 20Motor pulley/Bush 2 SPA 190 / 2012 Dia 28 Belt 2 SPA 1357 C/C 425 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 108.43 97.3 95.14 93.01 89.34 86.73 83.78 80.38
Outlet (2) 114.24 104 97 97.41 92.61 88.74 85.58 81.91
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 670 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 104 97.12 97.41 92.61 88.74 85.58 81.91 99
Inlet Sound Power(dB) 90.3 87.14 84.01 80.34 71.73 67.78 62.38 86
Airborne sound power (dB) 97.3 95.14 93.01 89.34 86.73 83.78 80.38 95
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 1.01 kW Absorbed Power NaN kW
Air Volume 2970 m3/h Air Volume m3/h
AHU SFP 1.6 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 48 of 70


16/09/2020 ClimaUno Page 49 of 70
16/09/2020 ClimaUno Page 50 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-B MZ KIT-01 Unit No. 20-ST-LAC-1509-06401-11
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3480 mm 1340 mm 840 mm 1658 mm 701 kg
Nominal Airflow 3600 m3/h Nominal Airflow 0 m3/h
Supply ESP 300 Pa Return ESP 0 Pa
Velocity 1.15 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1340 mm 840 mm 313 kg
B 1740 mm 1340 mm 840 mm 388 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 5000 B 75 Pa
QTY / Width x Height Length
1 / 1243 x 540 620 mm
Weight Efficiency
90 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 51 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-B MZ KIT-01 Unit No. 20-ST-LAC-1509-06401-11
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 680 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.34 m/s Clean 37.03 Pa 2 / 610x610
Type Synthetic pre filter Withdrawal Side Design 93.51 Pa
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.34 m/s Clean 66.12 Pa 2 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 183.06 Pa
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2610.82 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.34 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 158.70 Pa 229.35 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
2 / 610x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 52 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-B MZ KIT-01 Unit No. 20-ST-LAC-1509-06401-11
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 54.82%
Model SYQ250R Motor Design. Q2E100L4D Fan Eff. 57.58%
Fan Make Yilida Motor Make WAT Outlet Velocity 9.6 m/s
Impeller Diam. 250 mm Drive Type Belt Drive ESP 300 Pa
Quantity 1 Poles 4 TSP 1125 Pa
Duty % Per Fan Single Fan Motor Power 3.00 kW Fan Dynamic Pr. 57 Pa
Air Flow 3600 m3/h Input Power 2.68 kW Total Pressure 1182Pa
Fan Speed 3672 rpm Motor Speed 1435 rpm
Fan max speed 4100 rpm Motor Eff. 85%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 322 x 322 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 2.05 kW FLC 6.60A
Motor Base Q2E100L4D/3.00kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 100 / 1610 Dia 20Motor pulley/Bush 2 SPA 250 / 2517 Dia 28 Belt 2 SPA 1432 C/C 446 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 108.43 97.4 95.3 92.96 89.23 86.66 83.7 80.33
Outlet (2) 113.2 102.4 97 100.31 92.08 88.42 84.69 80.89
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
100.3
Outlet Sound Power(dB) 102.4 96.8 92.08 88.42 84.69 80.89 100
1
Inlet Sound Power(dB) 90.4 87.3 83.96 80.23 71.66 67.7 62.33 85
Airborne sound power (dB) 97.4 95.3 92.96 89.23 86.66 83.7 80.33 95
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 1.16 kW Absorbed Power NaN kW
Air Volume 3600 m3/h Air Volume m3/h
AHU SFP 1.52 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 53 of 70


16/09/2020 ClimaUno Page 54 of 70
16/09/2020 ClimaUno Page 55 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-L MACH-01 Unit No. 20-ST-LAC-1509-06401-12
Model box CU EC 50 Unit Model CU-EC-104
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3700 mm 2010 mm 1240 mm 1857 mm 1256 kg
Nominal Airflow 9000 m3/h Nominal Airflow 0 m3/h
Supply ESP 120 Pa Return ESP 0 Pa
Velocity 1.26 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 50mm TB Corner Profile - Al Panel Insulation 46mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L3 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1800 mm 2010 mm 1240 mm 477 kg
B 1900 mm 2010 mm 1240 mm 779 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 7500 B 75 Pa
QTY / Width x Height Length
1 / 1790 x 540 620 mm
Weight Efficiency
122 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 56 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-L MACH-01 Unit No. 20-ST-LAC-1509-06401-12
Model box CU EC 50 Unit Model CU-EC-104
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 1040 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.49 m/s Clean 41.14 Pa 3 / 610x610
Type Synthetic pre filter Withdrawal Side Design 95.57 Pa 3 / 610x305
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.49 m/s Clean 73.47 Pa 3 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 186.73 Pa 3 / 610x305
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2664.91 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 1040 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.49 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 176.34 Pa 238.17 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
3 / 610x610 3 / 610x305 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 57 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-RF-L MACH-01 Unit No. 20-ST-LAC-1509-06401-12
Model box CU EC 50 Unit Model CU-EC-104
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 70.60%
Model SYQ400R Motor Design. Q2E132M4B Fan Eff. 74.90%
Fan Make Yilida Motor Make WAT Outlet Velocity 9.7 m/s
Impeller Diam. 400 mm Drive Type Belt Drive ESP 120 Pa
Quantity 1 Poles 4 TSP 945 Pa
Duty % Per Fan Single Fan Motor Power 5.50 kW Fan Dynamic Pr. 57 Pa
Air Flow 9000 m3/h Input Power 4.14 kW Total Pressure 1002Pa
Fan Speed 2006 rpm Motor Speed 1460 rpm
Fan max speed 2400 rpm Motor Eff. 88%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 507 x 507 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 3.35 kW FLC 11.30A
Motor Base Q2E132M4B/5.50kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 132 / 2012 Dia 30Motor pulley/Bush 2 SPA 180 / 2012 Dia 38 Belt 2 SPA 1032 C/C 250 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 84.48 82.68 80.38 92.61 84.58 81.94 77.08 71.08
Outlet (2) 88.58 87.1 82 95.65 87.08 83.61 77.86 71.66
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 1040 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 87.1 81.54 95.65 87.08 83.61 77.86 71.66 94
Inlet Sound Power(dB) 75.68 72.38 83.61 75.58 66.94 61.08 53.08 82
Airborne sound power (dB) 82.68 80.38 92.61 84.58 81.94 77.08 71.08 92
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 1.72 kW Absorbed Power NaN kW
Air Volume 9000 m3/h Air Volume m3/h
AHU SFP .85 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 58 of 70


16/09/2020 ClimaUno Page 59 of 70
16/09/2020 ClimaUno Page 60 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-BF-LAUNDRY-01 Unit No. 20-ST-LAC-1509-06401-13
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3530 mm 1340 mm 840 mm 1673 mm 705 kg
Nominal Airflow 4878 m3/h Nominal Airflow 0 m3/h
Supply ESP 120 Pa Return ESP 0 Pa
Velocity 1.56 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1340 mm 840 mm 313 kg
B 1790 mm 1340 mm 840 mm 392 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 5000 B 75 Pa
QTY / Width x Height Length
1 / 1243 x 540 620 mm
Weight Efficiency
90 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 61 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-BF-LAUNDRY-01 Unit No. 20-ST-LAC-1509-06401-13
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 680 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.82 m/s Clean 50.17 Pa 2 / 610x610
Type Synthetic pre filter Withdrawal Side Design 100.08 Pa
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.82 m/s Clean 89.60 Pa 2 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 194.80 Pa
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2783.67 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.82 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 215.04 Pa 257.52 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
2 / 610x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 62 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-BF-LAUNDRY-01 Unit No. 20-ST-LAC-1509-06401-13
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 63.10%
Model SYQ280R Motor Design. Q2E100L2C Fan Eff. 67.49%
Fan Make Yilida Motor Make WAT Outlet Velocity 10.4 m/s
Impeller Diam. 280 mm Drive Type Belt Drive ESP 120 Pa
Quantity 1 Poles 2 TSP 945 Pa
Duty % Per Fan Single Fan Motor Power 3.00 kW Fan Dynamic Pr. 66 Pa
Air Flow 4878 m3/h Input Power 2.65 kW Total Pressure 1011Pa
Fan Speed 3046 rpm Motor Speed 2885 rpm
Fan max speed 4000 rpm Motor Eff. 85%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 361 x 361 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 2.03 kW FLC 5.80A
Motor Base Q2E100L2C/3.00kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 125 / 1610 Dia 25Motor pulley/Bush 2 SPA 132 / 2012 Dia 28 Belt 2 SPA 1357 C/C 473 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 86.21 91.3 85.26 90.21 86.26 83.21 80.26 72.26
Outlet (2) 91.52 97.84 87 94.44 89.41 85.2 81.65 73.34
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 97.84 86.89 94.44 89.41 85.2 81.65 73.34 95
Inlet Sound Power(dB) 84.3 77.26 81.21 77.26 68.21 64.26 54.26 82
Airborne sound power (dB) 91.3 85.26 90.21 86.26 83.21 80.26 72.26 92
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 1.18 kW Absorbed Power NaN kW
Air Volume 4878 m3/h Air Volume m3/h
AHU SFP 1.14 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 63 of 70


16/09/2020 ClimaUno Page 64 of 70
16/09/2020 ClimaUno Page 65 of 70
TECHNICAL SPECIFICATION SHEET
Name/Version:Visual Ahu / V2.02 CU Air Conditioning Industries LLC
Version Date: 12/02/2018 Dubai Investment Park-1, Dubai, UAE
Email : info@climaunoglobal.com
Website : www.climaunoglobal.com
Tel : 971 – 4 820 9700 Fax : 971 – 4 885 3534

PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-BF-AHU CIGAR BAR-01 Unit No. 20-ST-LAC-1509-06401-14
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

BASIC DETAILS
Unit Typology UVU (Uni directional Ventilation Unit)
Unit Typology Operation NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Length Width Height COG Weight
Overall Unit Dimensions 3480 mm 1340 mm 840 mm 1647 mm 695 kg
Nominal Airflow 3960 m3/h Nominal Airflow 0 m3/h
Supply ESP 120 Pa Return ESP 0 Pa
Velocity 1.26 m/s Velocity NA m/s
COMPONENT LIST
SUPPLY
ESFILTER ElectroStatic Filter
PBFILT Pre and Bag Filter
CFILT Carbon Filter
FAN Fan
UNIT CONSTRUCTION
Aluminium Framework 30mm Plain Corner Profile - Al Panel Insulation 25mm polyurethane 44kg/m3
Panel External Sheet PPGI 1.0mm Panel Internal Sheet GI 1.5mm
Base Frame 100mm X 2mm GI Base Roof Type Canopy Aluminum
Access Side Right Unit Location External

CASING DATA
TT Class T3 Frontal extraction F9 filter @ -400 Pa F9(M)
TBF Class TB4 Frontal extraction F9 filter @ +400 Pa F9(M)
CS Class D1(M) Eurovent Class / Eurovent Energy Class /
CAL @ -400 Pa L2 (M) CAL @ -400 Pa L2 (R)
CAL @ +700 Pa L2 (M) CAL @ +400 Pa L3 (R)

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz


Casing Acoustic Insulation 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SECTION WEIGHTS AND DIMENSIONS
Section No. Length Width Height Weight
A 1740 mm 1340 mm 840 mm 313 kg
B 1740 mm 1340 mm 840 mm 382 kg

SUPPLY COMPONENTS
001 ESP Filter
ESP Filter Model Pressure Drop
RY 5000 B 75 Pa
QTY / Width x Height Length
1 / 1243 x 540 620 mm
Weight Efficiency
90 Kg 95 %
001 ACCESSORIES
UV Lamp for ESP

Date of Selection: 16 September 2020 Page 1 of


3

16/09/2020 ClimaUno Page 66 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-BF-AHU CIGAR BAR-01 Unit No. 20-ST-LAC-1509-06401-14
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

001 ACCESS DOOR


Dimension Type
750 x 680 mm Removable Door
002 PANEL AND BAG FILTER

PRE FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO Coarse 90% Velocity 1.48 m/s Clean 40.73 Pa 2 / 610x610
Type Synthetic pre filter Withdrawal Side Design 95.36 Pa
Model Flat Length 48 mm Final 150.00 Pa

BAG FILTER
SPECIFICATION PRESSURE DROP QTY/SIZE in mm
Class ISO ePM1 80% Velocity 1.48 m/s Clean 72.74 Pa 2 / 610x610
Type Synthetic Fibre soft bag filter Withdrawal Side Design 186.37 Pa
Model Flange Length 600 mm Final 300.00 Pa
Filter Energy Consumption 2659.53 kWh/a
002 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
003 CARBON FILTER
Velocity Class Type Model Filter Air Pressure Drop
Withdrawal Clean Design Final
1.48 m/s Activated Activated Cylindrical Front
Carbon carbon carbon 174.57 Pa 237.28 Pa 300.00 Pa
filter
Qty/Size1 mm Qty/Size2 mm Qty/Size3 mm Length
2 / 610x610 450 mm

Date of Selection: 16 September 2020 Page 2 of


3

16/09/2020 ClimaUno Page 67 of 70


PROJECT DETAILS
Project No. 20-ST-LAC-1509-06401 Project Ref. 5 Star Beach Hotel & Branded
Residences. - Genetco
Customer Unit Qty. 1
Customer Unit Ref. EF-HT-BF-AHU CIGAR BAR-01 Unit No. 20-ST-LAC-1509-06401-14
Model box CU EC 30 Unit Model CU-EC-51
Design winter outdoor Temp DB 100.00 °C Print Date 16/09/2020

004 CENTRIFUGAL FAN-SUPPLY


FAN MOTOR PERFORMANCE
Fan Type Backward Curved Motor Type IE2 Single Speed-50 Hz Fan Static Eff. 51.39%
Model SYQ250R Motor Design. Q2E100L2C Fan Eff. 55.11%
Fan Make Yilida Motor Make WAT Outlet Velocity 10.6 m/s
Impeller Diam. 250 mm Drive Type Belt Drive ESP 120 Pa
Quantity 1 Poles 2 TSP 945 Pa
Duty % Per Fan Single Fan Motor Power 3.00 kW Fan Dynamic Pr. 68 Pa
Air Flow 3960 m3/h Input Power 2.64 kW Total Pressure 1013Pa
Fan Speed 3610 rpm Motor Speed 2885 rpm
Fan max speed 4100 rpm Motor Eff. 85%
Fan Oulet Flange Volts/Ph/Hz 415/3/50
Fan Outlet Size 322 x 322 mm Starting Method Automatic (DOL/Star delta)
Fan Abs. Power 2.02 kW FLC 5.80A
Motor Base Q2E100L2C/3.00kW

DRIVE DETAILS
Fan pulley/Bush 2 SPA 100 / 1610 Dia 20Motor pulley/Bush 2 SPA 125 / 1610 Dia 28 Belt 2 SPA 1250 C/C 446 mm
FAN SOUND POWER
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
Inlet (1) 108.59 96.61 94.51 93.32 89.44 86.83 84.1 80.54
Outlet (2) 113.86 102.3 96 101.03 92.52 88.7 85.41 81.44
(1) SWL INSIDE The Inlet Duct (dB) (2) SWL INSIDE The Outlet Duct (dB)
004 ACCESSORIES
ELECTRICAL WP BOX 110X150X70 MM
004 ACCESS DOOR
Dimension Type
600 x 680 mm Hinged door
AHU ACOUSTIC DATA SUPPLY SECTION
Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
101.0
Outlet Sound Power(dB) 102.3 96.19 92.52 88.7 85.41 81.44 100
3
Inlet Sound Power(dB) 89.61 86.51 84.32 80.44 71.83 68.1 62.54 85
Airborne sound power (dB) 96.61 94.51 93.32 89.44 86.83 84.1 80.54 95
SPECIFIC FAN POWER
Supply Fan Extract Fan
Filter Conditions Clean Filter Conditions
Absorbed Power 1.03 kW Absorbed Power NaN kW
Air Volume 3960 m3/h Air Volume m3/h
AHU SFP 1.22 kW/m3/s

Date of Selection: 16 September 2020 Page 3 of


3

16/09/2020 ClimaUno Page 68 of 70


16/09/2020 ClimaUno Page 69 of 70
16/09/2020 ClimaUno Page 70 of 70

You might also like