You are on page 1of 7

TECHNICAL SPECIFICATION SHEET

Unit No.: FP-22-9971601-01-0


Dubai Industrial City, Dubai - UAE
Email: Info@fin-power.com
Tel: 00971 4 4219900 Fax: 00971 4 3603604
Version: FINPOWER AHU SELECT V 4.12 Sales Quotation No.:
Issue Date: Jan 2022 CDB Ver No.: 2022.01.06.011
Finpower Aircon ,is participating in the Eurovent Certification Programme for Air Handling Units. The range SK50T is certified under the number
(14.06.003) and presented in the directory of certified Air Handling Units.
PROJECT DETAILS
Project SHISHA CAFE
Project No. 9971601 Date 16 Feb 2022 Unit No. FP-22-9971601-01-0
Reference AT DUBAI

EUROVENT NOTES:
Minimum and Maximum operating limits are -20°C to + 60°C.
Casing air leakage class L1 (R ) -400 Pa / L1 ( R) +400 Pa
The fan selection is considering the fan system effect
The fan static is considering DRY Pressure drop of cooling coil

UNIT CONSTRUCTION
Unit Model SK50T-PO-FM-43
Construction Range SK50T
Customer Unit Reference FAHU-01
Customer
Quantity 1
Unit Location Internal
Access Side Right
Frame Material Aluminum
Frame Finish Anodized
Panel Insulation PUF Density 40 Kg/M³
Panel Depth 48 +/- 2 mm
Panel Internal Sheet 0.6mm Galvanised Steel
Panel External Sheet 0.6mm Prepainted Steel
Floor Panel Internal Sheet 0.6mm Galvanised Steel
Floor Panel External Sheet 0.6mm Prepainted Steel
Roof Panel External Sheet 0.6mm Prepainted Steel
Thermal break Yes
Roof Type None
Base Frame 80x30 Galv.base ( 50 mm panel )
Eurovent Condition 100% Re-Circulation air at 46.00 °C
Length 2155 mm
Width 1015 mm
Height 780 mm
Weight Approx +-5% 311 kg
Surface Area 9.32m/2
Supply Units
3
Air Volume 3398 m /h
Total Static Pressure 974 Pa
External Static Pressure 500 Pa
Unit Velocity 1.52 m/s
Fan Speed 2826 RPM
Motor Power 2.20 kW
Motor Volt/Phase/Freq 380-415/3/50 V/Ph/Hz
Motor FLC 4 A
Specific Fan Power 2.10 (W/(l/sec))
Unit Specific Fan Power 2.10 (W/(l/sec))
Unit Specific Fan Powerint 1929.80 (W/(M3/sec))
EcoDesign Type UVU (Uni directional Ventilation Unit)
EcoDesign Class NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h

SECTION WEIGHTS AND DIMENSIONS


Section No. Length Width Height Weight Approx +/-5%
A 2155 mm 1015 mm 780 mm 311 kg

Printed On: 16 February 2022 Page 1 of 5


TECHNICAL SPECIFICATION SHEET
Unit No.: FP-22-9971601-01-0
Dubai Industrial City, Dubai - UAE
Email: Info@fin-power.com
Tel: 00971 4 4219900 Fax: 00971 4 3603604
Version: FINPOWER AHU SELECT V 4.12 Sales Quotation No.:
Issue Date: Jan 2022 CDB Ver No.: 2022.01.06.011
Finpower Aircon ,is participating in the Eurovent Certification Programme for Air Handling Units. The range SK50T is certified under the number
(14.06.003) and presented in the directory of certified Air Handling Units.
PROJECT DETAILS
Project SHISHA CAFE
Project No. 9971601 Date 16 Feb 2022 Unit No. FP-22-9971601-01-0
Reference AT DUBAI

AHU ACOUSTIC DATA SUPPLY SECTION


Description 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Overall dB(A)
Outlet Sound Power(dB) 87 96 86 87 86 76 67 93
Inlet Sound Power(dB) 81 75 74 71 64 58 48 76
Airborne sound power (dB) 76 70 59 58 65 54 49 69
SUPPLY HEADER SECTION A

001 INLET SECTION


Type Fresh Air Inlet Extra 50mm C Flange
Blade Type None
Position Onair Pressure Drop 6.00 Pa

Damper Opening Size (HxW) Material Velocity Position


None 680 x 915 mm None 3.81 m/s Onair

002 COMBINED PANEL AND BAG FILTERS


Type Panel Type Bag
Filter Grade/Frame Material G4 - coarse 60% Filter Grade/Frame Material F7 - ePM10 85%
Efficiency 90% Efficiency 85%
Filter Size 1 (WxHxD) 1 x 592 x 592 x 46 mm Filter Size 1 (WxHxD) 1 x 592 x 592 x 300 mm
Filter Size 2 (WxHxD) 1 x 292 x 592 x 46 mm Filter Size 2 (WxHxD) 1 x 287 x 592 x 300 mm
Face Velocity 1.8 m/s Face Velocity 1.81 m/s
Pressure Drop Calculation Clean Pressure Drop Calculation Clean
Initial Pressure Drop 47.6 Pa Initial Pressure Drop 97.1 Pa
Final Pressure Drop 97.6 Pa Final Pressure Drop 197.1 Pa
Design Pressure Drop 72.6 Pa Design Pressure Drop 147.1 Pa
Filter Frame and Withdrawal Side Filter Frame and Withdrawal Side
Filter Media Synthetic Pleated Filter Media Microfine glass fibre
Spare Filters None Spare Filters None
Energy Class N.A. Energy Class B
Power Consumption 0.35 Kwh

002 REMOVABLE PANEL


Dimensions Type
348 x 680 mm Removable Door

Printed On: 16 February 2022 Page 2 of 5


TECHNICAL SPECIFICATION SHEET
Unit No.: FP-22-9971601-01-0
Dubai Industrial City, Dubai - UAE
Email: Info@fin-power.com
Tel: 00971 4 4219900 Fax: 00971 4 3603604
Version: FINPOWER AHU SELECT V 4.12 Sales Quotation No.:
Issue Date: Jan 2022 CDB Ver No.: 2022.01.06.011
Finpower Aircon ,is participating in the Eurovent Certification Programme for Air Handling Units. The range SK50T is certified under the number
(14.06.003) and presented in the directory of certified Air Handling Units.
PROJECT DETAILS
Project SHISHA CAFE
Project No. 9971601 Date 16 Feb 2022 Unit No. FP-22-9971601-01-0
Reference AT DUBAI

003 HEAT PIPE


Flow Coil Width Coil Height Fin Type Rows FPI
3
3398 m /h 585 mm 635 mm Louvre 3 10
Fin Material Casing Material Effectiveness Precool Saving Reheat Saving Pressure Drop
Aluminium Galvanised 31 % 12.01 kW 12.01 kW 206 Pa
Precool Conditions
Air on Dry Bulb Air on Wet Bulb Air on RH Air off Dry Bulb Air off Wet Bulb Air off RH
o o o o
46.0 C 29.0 C 29 % 35.8 C 26.8 C 50 %
Reheat Conditions
Air off Dry Bulb Air off Wet Bulb Air off Relative Humidity
o o
24.0 C 17.1 C 50 %
003 DX COOLING COIL
Type Main Medium R407c
Coil Code FP-DX-1/2"- 0.35-A-0.12-20TH-23FL-8R-11-10C-1 3/8"-G-R-P
Rows/FPI 8 / 11 Coil Qty 1
o
Air On (DB)/(WB)/(RH) 35.8 / 26.8 C /49.83% No. of Circuits 10
o o
Air Off (DB)/(WB)/(RH) 13.8 / 13.6 C /97.29% Evaporating Temp 8.0 C
Total Load 48.44 kW Refrig. Pressure Drop 35.4 kPa
Sensible Load 24.39 kW Number of Connections 2
Air Pressure Drop 323 Pa Bypass Factor 0.06
o
Dry Air Pressure Drop 117.9 Pa Coil leaving ADP 12.4 C
Face Velocity 2.5 m/s Condensation 37.60 l/hr
Coil Wet Pressure Drop 231 Pa Coil Dry Pressure Drop 117.9 Pa

Fin Material/Thickness Aluminium 0.12 Connection Type MPT


Tube OD/Material/Thickness 1/2" CU - 0.35mm Connection Side Right
Header Material Copper Eliminators None
Coil Casing Galvanized steel Treatment Type Plain
Liquid Connection Size Suction Connection Size
General
2
Face Area 0.37 m Total Pressure Drop 323 Pa
Length 676 mm Weight 36 kg

INCLUSIVES
ACCESSORIES
ODU MODEL: FPC 08ZE : 2 NO
CAPACITY : 24.3 kW / UNIT
POWER INPUT : 8.84 kW / UNIT
Connections/ CDU : Suction : 1 x 1 3/8" & Liquid : 1 x 5/8"
Unit Dimensions (H x W x L) / Oper. Weight : 1350 x 860 x 860 mm / 215 KG
DRAIN TRAY
Type Fixed Width 915 x 676 mm
Material Epoxy painted Drain Pan Connection Side / Dia Right / 50 mm

Printed On: 16 February 2022 Page 3 of 5


TECHNICAL SPECIFICATION SHEET
Unit No.: FP-22-9971601-01-0
Dubai Industrial City, Dubai - UAE
Email: Info@fin-power.com
Tel: 00971 4 4219900 Fax: 00971 4 3603604
Version: FINPOWER AHU SELECT V 4.12 Sales Quotation No.:
Issue Date: Jan 2022 CDB Ver No.: 2022.01.06.011
Finpower Aircon ,is participating in the Eurovent Certification Programme for Air Handling Units. The range SK50T is certified under the number
(14.06.003) and presented in the directory of certified Air Handling Units.
PROJECT DETAILS
Project SHISHA CAFE
Project No. 9971601 Date 16 Feb 2022 Unit No. FP-22-9971601-01-0
Reference AT DUBAI

004 SUPPLY FAN


GENERAL FAN MOTOR
Ext. Static Pressure 500 Pa Type Centrifugal Type/IP/Insl IE2-IP55-Insl.Cl.F
Total Static Pressure 974 Pa Model BDB280CM Motor Rated Power 2.20 kW
Total Fan Pressure 1060.9 Pa Qty 1 Qty/Arrangement 1/Single motor
3
Air Volume 3398 m /h Fan Outlet Velocity 7.28 m/s Elec Supply(V/Ph/Hz) 380-415V / 3 / 50.00Hz
Starting Method DOL Fan Speed 2826 RPM Motor Speed 1440 RPM
50mm C
Fan Outlet Fan Max Speed 3500 RPM Motor Pole 4
Flange
Outlet Size (H x W) 360x360 mm Fan Absorbed Power 1.44 kW Power Input 1.98 kW
Fan Arrangement Single Fan Fan Efficiency 66.09 % Full Load Current 4.40 A
2 SPA 160 /
Motor Arrangement Single motor Fan Pulley/Bush Motor Pulley/Bush 2 SPA 315 / 2517 Dia 28
2012 Dia 25
Pulley centre distance 406 Belt 2 SPA 1557 Motor Frame Size ND100L

Fan Sound Power 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Lwi(Lin) Inside Inlet Duct (dB) 88 86 84 84 79 78 74 69
Lwi(A) Inside
62 69 75 81 79 79 75 68
Inlet Duct (dB A)
Lpi(A) Inside
0 0 0 0 0 0 0 0
Inlet Duct (dB A)
ANTIVIBRATION MOUNTS
Type All
AVM Code JD-30 JD-30 JD-30 JD-30
AVm Number 1 2 3 4 5 6 7 8

INCLUSIVES
ACCESSORIES
Flexible connection at Fan Outlet
Spare

004 HINGED ACCESS DOOR


Dimensions Type
540 x 680 mm Hinged door

POINT LOADS AND CENTER OF GRAVITY


Section No. Point 1 Point 2 Point 3 Point 4 Weight
A 74 kg 74 kg 82 kg 82 kg 311 kg
Unit Center Of Gravity 1132.3 mm

NOTES:
- Finpower reserves right to change the make and model of components as per the availability
Disclaimer : ± 5% Tolerance on physical & performance attributes is acceptable on a standard manufacturing practice
Note: The values given are valid under the specified measuring conditions and may vary due to conditions of installation and
current parameters.
For deviations from the standard configuration, the parameters have to be checked on the installed unit.

Printed On: 16 February 2022 Page 4 of 5


TECHNICAL SPECIFICATION SHEET
Unit No.: FP-22-9971601-01-0
Dubai Industrial City, Dubai - UAE
Email: Info@fin-power.com
Tel: 00971 4 4219900 Fax: 00971 4 3603604
Version: FINPOWER AHU SELECT V 4.12 Sales Quotation No.:
Issue Date: Jan 2022 CDB Ver No.: 2022.01.06.011
Finpower Aircon ,is participating in the Eurovent Certification Programme for Air Handling Units. The range SK50T is certified under the number
(14.06.003) and presented in the directory of certified Air Handling Units.
PROJECT DETAILS
Project SHISHA CAFE
Project No. 9971601 Date 16 Feb 2022 Unit No. FP-22-9971601-01-0
Reference AT DUBAI

ECODESIGN DIRECTIVE DATA


Unit typology UVU (Uni directional Ventilation Unit)
Unit typology (operation) NRVU (Non Residential Ventilation Unit), Airflow >1000m3/h
Nominal flow rate (qnom) 0.94 m3/s
Supply Extract
Nominal flow rate (qnom_SUP) 0.94 m3/s Nominal flow rate(qnom_EXT) Not applicable
Velocity 1.52 m/s Velocity Not applicable
Fan static efficiency 63.99% Fan static efficiency Not applicable
Motor efficiency 84.00% Motor efficiency Not applicable
Drive efficiency 86.40% Drive efficiency Not applicable
Inverter efficiency 100.00% Inverter efficiency Not applicable
Internal specific fan power Internal specific fan power
1929.77 W/m3/s Not applicable
of ventilation components of ventilation components
Internal specific fan power of ventilation components (SFPint) 1929.77 W/m3/s
Heat Recovery System
Type Not applicable
Thermal efficiency (?t_nrvu) EN308 Not applicable
Filter correction
Filter correction Not applicable
Requirement Calculated ERP 2016 ERP 2018
Internal specific fan power of
1929.77 W/m3/s 250.00 W/m3/s 230.00 W/m3/s
ventilation components (SFPint_SUP)
SFPInt conform No
SFPInt message

Printed On: 16 February 2022 Page 5 of 5