You are on page 1of 11

DX SPLIT UNITS

PRODUCT
catalogue R410A
Ducted Split Units

Ducted units or 'Split' systems consist of an outdoor unit and an indoor unit installed in the ceiling space.
The cooled air is then directed to multiple rooms or zones within the building via a system of concealed
ducting.

• The ability to cool or heat the entire house.


• A control system that allows you to set conditioned zones and control the temperature in each zone.
• The cost-effective ability to turn off the system in rooms where it is not needed.

Indoor Unit Outdoor Unit

Model Names of Indoor/Outdoor Units

Indoor Unit Outdoor Unit


Nominal Capacity
Model Power Supply Model Power Supply
1.5 TR RKM-06-DX 220-240V~, 50Hz, 1Ph VTB 1.5ZF-SD 220-240V~, 50Hz, 1Ph
2 TR RKM-08-DX 220-240V~, 50Hz, 1Ph VTB 02ZF-SD 220-240V~, 50Hz, 1Ph
2.5 TR RKM-10-DX 220-240V~, 50Hz, 1Ph VTB 2.5ZF-SD 220-240V~, 50Hz, 1Ph
3 TR RKM-12-DX 220-240V~, 50Hz, 1Ph VTB 03ZF-SD 380-415V~, 50Hz, 3Ph
4 TR RKM-14-DX 220-240V~, 50Hz, 1Ph VTB 04ZF-SD 380-415V~, 50Hz, 3Ph
5 TR RKM-18-DX 220-240V~, 50Hz, 1Ph VTB 05ZF-SD 380-415V~, 50Hz, 3Ph
Indoor Unit Features

General

Ideal for mounting above the ceiling, these ducted type indoor
units have a capacity ranging from 1.5 to 5 tons. These are
factory assembled, hard-wired and tested for performance and
quality before leaving the factory.

Casing

The units are constructed with heavy gauge zinc coated steel
sheets and is provided with thermal and acoustic insulation on
the inside to prevent heat transfer and dripping.

Evaporator

The copper tubes mechanically bonded to a configured hydrophilic aluminum fin is the standard. Coils are
leak tested at the factory to ensure the pressure integrity, with the evaporator coil leak tested to 3,100kPa
(450 psig). Anti-corrosion treatment for coils are available optionally.

Drain Pan

The condensate drain pan is fabricated from corrosion resistant materials for durability and is shielded with
high-quality fire retardant foam insulation.

Indoor Fan

The indoor units have DIDW centrifugal, forward-curving galvanized steel impeller that are statically and
dynamically balanced as per AMCA 204 standard.

Filter

The filter comes prefixed on the return air side and is made up of nylon mesh woven media. These can be
easily cleaned by water or compressed air and is highly durable.
Outdoor Unit Features

General

The outdoor units are side-discharge type with a weatherproof heavy


gauge base. They are factory assembled and hard-wired, with fully
charged refrigerant and the unit is tested for performance (cooling
operation, fan rotation and control sequence) and quality, before
leaving the factory.

Casing

The unit casing is zinc coated and built from heavy gauge galvanized
steel, with the exterior surfaces wholly weatherized for outdoor
installation and properly reinforced and brazed. Performs a salt spray
test for steel sheet under 1,000 hours and more (customized.). The
cabinet construction allows for easy maintenance; the service panels
can be easily removed and reinstalled.

Compressor

The outdoor units, with a capacity ranging from 3TR to 5TR have a single wholly enclosed and hermetical-
ly sealed scroll compressor – Copeland. And for units with capacities lesser than 3TR comes with a Rotary
compressor. By default, there is high-pressure and low-pressure switch.

Condenser

The copper tubes are mechanically bonded to a configured aluminum fin, by default (standard). Coils are
leak tested at the factory to ensure the pressure integrity; with the evaporator coil leak tested to
4,500kPa (650 psig). Anti-corrosion treatment for coils are available optionally.

Outdoor fan

To ensure uninterrupted and reliable operation, the fan is direct driven by weatherproof and durable
motor. With maintenance free bearing for outdoor installation, the drive motor is designed statically and
dynamically balanced, with the fan the operating quietly (no noise) and is durable.

Electrical Control Box

In the electrical control box provided, the internal wires of the unit are clearly marked (colored) and num-
bered for easy identification purpose; the exterior of the box is made of metal and is powder-coated.
^ƉĞĐŝĮĐĂƟŽŶƐͲZϰϭϬ

SPECIFICATION - R410A SPLIT UNITS - SIDE DISCHARGE ODU


Indoor unit model RKM-06-DX RKM-08-DX RKM-10-DX RKM-12-DX RKM-14-DX RKM- 18-DX
Outdoor unit model VTB 1.5ZF-SD VTB 02ZF-SD VTB 2.5ZF-SD VTB 03ZF-SD VTB 04ZF-SD VTB 05ZF-SD
Indoor uni t V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50
Power s uppl y
Outdoor uni t V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 380-415/3/50 380-415/3/50 380-415/3/50
T1 Ca pa ci ty Btu/h 18,000 24,000 30,000 36,000 48,000 60,000
Cool i ng
T3 Ca pa ci ty Btu/h 16,200 18,300 23,884 29,172 39,920 49,986
T1 Ca pa ci ty Wa tts 1,630 1,959 2,495 2,856 4,020 5,176
Power Input
T3 Ca pa ci ty Wa tts 1,930 2,227 2,763 3,546 4,910 6,156
Type - Rota ry Rota ry Rota ry Scrol l Scrol l Scrol l
Compres s or Power Input (T1) Wa tts 1480 1632 2102 2350 3140 3900
Power Input (T3) Wa tts 1780 1900 2370 3040 4030 4880
Indoor uni t - AC type AC type AC type AC type AC type AC type
Motor
Outdoor uni t - AC type AC type AC type AC type AC type AC type
Indoor uni t * m3/h 1,008 1,354 1,704 2,035 2,791 3,440
Ai r fl ow
Outdoor uni t m3/h 4,122 4,122 5,697 5,697 7,895 8,890
Power Input Indoor uni t * Wa tts 120 232 281 299 508 536
Indoor Sta nda rd ESP (Med) Pa 40 40 35 45 60 65
Indoor Ma x. ESP Pa 100 100 100 150 150 150
Li qui d s i de mm Φ9.52 Φ9.52 Φ9.52 Φ12.7 Φ12.7 Φ12.7
Connecti on pi pe
Ga s s i de mm Φ15.87 Φ15.87 Φ19.05 Φ19.05 Φ22.22 Φ28.57
Indoor uni t mm 1097 × 265 × 507 1307 × 265 × 507 1532 × 265 × 507 1825 × 265 × 507 1545 × 365 × 665 1735 × 365 × 665
Net di mens i on (W×H×D)
Outdoor uni t mm 656 × 642 × 355 656 × 642 × 355 756 × 735 × 355 756 × 735 × 355 856 × 1092 × 450 956 × 1092 × 450
Indoor uni t mm 1185 × 286 × 547 1411 × 286 × 547 1654 × 286 × 547 1971 × 286 × 547 1668 × 394 × 718 1874 × 394 × 718
Pa cki ng (W×H×D)
Outdoor uni t mm 680 × 650 × 385 680 × 650 × 385 780 × 744 × 385 780 × 744 × 385 880 × 1100 × 480 980 × 1100 × 480
Indoor uni t kg 38/41 45/49 58/63 67/73 71/77 84/91
Net/Gros s wei ght
Outdoor uni t kg 65/69 68/71 78/82 78/82 92/97 98/103

Notes:

1. The capacity is based on the following conditions:


T3 cooling: Indoor temperature 26.6 C DB/19.4 C WB; Outdoor temperature 46 C DB.
T1 cooling: Indoor temperature 26.6 C DB/19.4 C WB; Outdoor temperature 35 C DB.
The refrigerant piping length between indoor unit and outdoor unit is 30m.

2. ESP: External static pressure.

3. Wired controller is not included.

*: Indoor unit air flow & power input is based on the standard ESP.

Nomenclature

/EKKZ KhdKKZ

Z<DͲϬϲͲy sdϬϮ&Ͳ^

Direct Expansion VTB series

06, 08, 10, 12, 14, 18 Nominal Cooling


Capacity(TONS)
ZĞĨƌŝŐĞƌĂŶƚdLJƉĞͲZϰϭϬ

^ŝĚĞͲĚŝƐĐŚĂƌŐĞ

Z<D^ĞƌŝĞƐ
Dimensional details - Indoor unit

Anchor Hole Slot


Ø10x14 - 4Nos
C

P2 P1

F
P3 P4

B
A

AIR FLOW
LHS RHS

C
30 E

30 3/4" MPT
DRAIN CONN.

Model P1 P2 P3 P4
RKM-06-DX 13.37 13.37 6.68 6.68
RKM-08-DX 15.74 15.74 7.93 7.93
RKM-10-DX 21.09 21.09 9.29 9.29
RKM-12-DX 24.32 24.32 10.95 10.95
RKM-14-DX 25.39 25.39 12.80 12.80
RKM-18-DX 30.93 30.93 13.80 13.80

Di mens i ons (mm) Number of Std Fi l ter Di m (mm) Wei ght Li ne Si ze - Inch
Model
A B C D E F Fa n (s ) Motor (s ) LxH (kgs ) Sucti on Li qui d
RKM-06-DX 1097 873 507 888 265 190 2 1 838 x 203 38 5/8 3/8
RKM-08-DX 1307 1102 507 1117 265 190 2 1 1067 x 203 45 5/8 3/8
RKM-10-DX 1532 1331 507 1346 265 190 3 2 1296 x 203 58 3/4 3/8
RKM-12-DX 1825 1610 507 1625 265 190 4 2 1575 x 203 67 3/4 1/2
RKM-14-DX 1545 1308 665 1320 365 285 2 1 1270 x 300 71 7/8 1/2
RKM-18-DX 1735 1486 665 1498 365 285 3 2 1448 x 300 84 1 1/8 1/2
Dimensional details - Outdoor unit

B
A

Nominal capacity: 1.5 to 3 Tr


C

Di mens i ons (mm) Wei ght Li ne Si ze - Inch


Model
A B C (kgs ) Sucti on Li qui d
VTB 1.5ZF-SD 656 642 355 65 1/2 3/8
VTB 02ZF-SD 656 642 355 68 1/2 3/8
VTB 2.5ZF-SD 756 735 355 78 1/2 3/8
VTB 03ZF-SD 756 735 355 78 5/8 3/8

B
A
C

Nominal capacity: 4 to 5 Tr

Di mens i ons (mm) Wei ght Li ne Si ze - Inch


Model
A B C (kgs ) Sucti on Li qui d
VTB 04ZF-SD 856 1092 450 92 7/8 1/2
VTB 05ZF-SD 956 1092 450 98 7/8 1/2
Airflow Data

Airflow in L/S
Fan Speed = High
ESP Model 0 20 40 60 80 100
RKM-06-DX 387 359 331 299 262 226
RKM-08-DX 482 465 447 424 397 369
RKM-10-DX 633 551 495 440 412 347
RKM-12-DX 712 660 608 553 495 438
RKM-14-DX 898 889 880 854 810 768

RKM-18-DX 1122 1111 1100 1067 1013 959

Airflow in L/S
Fan Speed = Medium
ESP Model 0 20 40 60 80 100
RKM-06-DX 336 308 280 251 221 190
RKM-08-DX 408 392 376 355 331 306
RKM-10-DX 533 485 438 388 335 305
RKM-12-DX 640 607 574 526 465 403
RKM-14-DX 830 816 803 775 741 731

RKM-18-DX 1037 1020 1004 969 926 914

Airflow in L/S
Fan Speed = Low
ESP Model 0 20 40 60 80 100
RKM-06-DX 286 262 238 213 188 162
RKM-08-DX 347 333 320 302 281 260
RKM-10-DX 453 412 372 330 285 259
RKM-12-DX 544 516 488 447 395 343
RKM-14-DX 706 694 683 659 630 621
RKM-18-DX 881 867 853 824 787 777
Note :The airflow provided are without the plenum and filter. The airflow at low PIN motor(s) is under selection software. Please contact
the local distributor.
Sound Data

Di s cha rge Sound Pres s ure l evel dB(A)


(In accordance with ISO 3744 standard)
Octa ve Ba nd Center Frequency Hz
Fa n Speed Uni t Si ze
125 250 500 1000 2000 4000 8000 NC
RKM-06-DX 35 38 32 17 13 13 10 30
RKM-08-DX 37 40 34 19 15 15 12 30
RKM-10-DX 38 41 35 20 16 16 13 30
H
RKM-12-DX 39 42 36 21 17 17 14 35
RKM-14-DX 47 50 41 27 21 23 22 40
RKM-18-DX 48 51 42 28 22 24 23 40
RKM-06-DX 32 35 29 14 10 <10 <10 25
RKM-08-DX 34 37 31 16 12 11 <10 25
RKM-10-DX 35 38 32 17 13 12 <10 30
M
RKM-12-DX 36 39 33 18 14 13 <10 30
RKM-14-DX 46 49 39 25 17 19 17 40
RKM-18-DX 47 50 40 26 20 22 20 40
RKM-06-DX 27 33 23 <10 <10 <10 <10 20
RKM-08-DX 29 35 25 10 <10 <10 <10 25
RKM-10-DX 30 36 26 11 <10 <10 <10 25
L
RKM-12-DX 31 37 27 12 <10 <10 <10 25
RKM-14-DX 42 44 35 20 14 16 13 35
RKM-18-DX 46 47 38 23 17 19 16 40
Note: Sound data is estimated with 1m acoustically lined duct, lined 90 degree elbow, double deflection grille and at 1m distance in the room (horizontally & vertically)

Sucti on Sound Pres s ure l evel dB(A)


(In accordance with ISO 3744 standard)
Octa ve Ba nd Center Frequency Hz
Fa n Speed Uni t Si ze
125 250 500 1000 2000 4000 8000 NC
RKM-06-DX 41 47 46 44 40 34 25 45
RKM-08-DX 43 49 48 46 42 36 27 45
RKM-10-DX 44 50 49 47 43 37 28 50
H
RKM-12-DX 45 51 50 48 44 38 29 50
RKM-14-DX 53 59 54 51 51 44 35 55
RKM-18-DX 54 60 55 52 52 45 36 55
RKM-06-DX 39 45 43 41 36 30 21 45
RKM-08-DX 41 47 45 43 38 32 23 45
RKM-10-DX 42 48 46 44 39 33 24 45
M
RKM-12-DX 43 49 47 45 40 34 25 45
RKM-14-DX 52 57 52 48 49 42 32 50
RKM-18-DX 53 58 53 49 50 43 33 55
RKM-06-DX 33 43 38 35 29 22 12 35
RKM-08-DX 35 45 40 37 31 24 14 40
RKM-10-DX 36 46 41 38 32 25 15 40
L
RKM-12-DX 37 47 42 39 33 26 16 40
RKM-14-DX 51 55 50 45 46 38 28 50
RKM-18-DX 52 56 51 46 47 39 29 50
Note: Measured at @ 1m (horizontally and vertically) from the grille in the room
Sound Data
Ra di a ted Sound Pres s ure l evel dB(A)(Si ngl e Ski n)
(In accordance with ISO 3744 standard)
Octa ve Ba nd Center Frequency Hz
Fa n Speed Uni t Si ze
125 250 500 1000 2000 4000 8000
RKM-06-DX 35 36 31 16 <10 <10 <10
RKM-08-DX 37 38 33 18 11 <10 <10
RKM-10-DX 38 39 34 19 12 <10 <10
H
RKM-12-DX 39 40 35 20 13 <10 <10
RKM-14-DX 47 48 40 26 17 16 <10
RKM-18-DX 48 49 41 27 18 17 <10
RKM-06-DX 32 33 28 13 <10 <10 <10
RKM-08-DX 34 35 30 15 <10 <10 <10
RKM-10-DX 35 36 31 16 <10 <10 <10
M
RKM-12-DX 36 37 32 17 10 <10 <10
RKM-14-DX 46 47 38 24 13 12 <10
RKM-18-DX 47 48 39 25 16 15 <10
RKM-06-DX 27 31 22 <10 <10 <10 <10
RKM-08-DX 29 33 24 <10 <10 <10 <10
RKM-10-DX 30 34 25 <10 <10 <10 <10
L
RKM-12-DX 31 35 26 <10 <10 <10 <10
RKM-14-DX 42 42 34 19 10 <10 <10
RKM-18-DX 46 45 37 22 13 12 <10

Ra di a ted Sound Pres s ure l evel dB(A)(Doubl e Ski n - 25mm thi ck)
(In accordance with ISO 3744 standard)
Octa ve Ba nd Center Frequency Hz
Fa n Speed Uni t Si ze
125 250 500 1000 2000 4000 8000
RKM-06-DX 21 25 18 <10 <10 <10 <10
RKM-08-DX 23 27 20 <10 <10 <10 <10
RKM-10-DX 24 28 21 <10 <10 <10 <10
H
RKM-12-DX 25 29 22 <10 <10 <10 <10
RKM-14-DX 35 36 28 13 <10 <10 <10
RKM-18-DX 36 37 29 14 <10 <10 <10
RKM-06-DX 18 22 15 <10 <10 <10 <10
RKM-08-DX 20 24 17 <10 <10 <10 <10
RKM-10-DX 21 25 18 <10 <10 <10 <10
M
RKM-12-DX 22 26 19 <10 <10 <10 <10
RKM-14-DX 34 35 26 11 <10 <10 <10
RKM-18-DX 35 36 27 12 <10 <10 <10
RKM-06-DX 13 20 <10 <10 <10 <10 <10
RKM-08-DX 15 22 11 <10 <10 <10 <10
RKM-10-DX 16 23 12 <10 <10 <10 <10
L
RKM-12-DX 17 24 13 <10 <10 <10 <10
RKM-14-DX 30 30 22 <10 <10 <10 <10
RKM-18-DX 34 33 25 <10 <10 <10 <10

Note: Sound data is estimated with 1m acoustically lined duct, lined 90 degree elbow, double deflection grille and at 1m distance in the room
(horizontally & vertically). As per acoustic data setup arrangement (discharge) refer page no 16
FP-DX-0518