LEGEND FM 200 GAS NOZZLE (FOR ROOM SPACE) FM 200 GAS CYLINDER A ACTUATOR P PRESSURE SWITCH PIPE (FOR ROOM SPACE) FECP FIRE EXITINGUISHING CONTROL PANEL FIRST STAGE ALARM BELL SECOND STAGE SIREN COMBINED HORN & BEACON LIGHT OPTICAL TYPE SMOKE DETECTOR OPTICAL TYPE HEAT DETECTOR 1.5 HOUR FIRE RATED DOOR EMERGENCY LIGHT EMERGENCY LIGHT WITH EXIT SIGN PRESSURE SWITCH SOLONOID VALVE A/C SHUT DOWN END OF LINE RESISTOR ABORT SWITCH SEQUENCE OF OPERATION FM-200 SYSTEM IS GAS SUPPRESSION SYSTEM EXTINGUISHED IN THE SPACE AS GAS VAPOR AT HIGH PRESSURE ( 4-6 ) BAR TO COVER THE PROTECTED AREA IN THE FOLLOWING SEQUENCE OF OPERATION :- 1- ONCE FIRST DETECTOR IN THE PAEC SENDING SMOKE DIRECTLY SEND SIGNAL TO CONTROL PANEL . 2. CONTROL PANEL SENDING THE FOLLOWING SIGNALS :- - ACTUATING 1ST STAGE ALARM - SHUT DOWN A/C OR VENTILATION SYSTEM . GULF CONSULTING GROUP - CLOSING AUTOMATIC ROLL UP SHUTTER . 3. ON CONTROL PANEL RECEIVING SIGNAL FROM 2ND DETECTOR SENDING THE FOLLOWING SIGNALS :- - ACTUATING 2ND STAGE ALARM SYSTEM - TO FIRE ALARM SYSTEM IN THE BUILDING - ACTUATING FM-200 SOLENOID VALE DIRECTLY CONTROLLING THE FM -200 GAS FLOW - AFTER (30-60) sec. THE SOLENOID VALE START RELAPSING THE GAS FROM CYLINDER - AFTER (20-40) sec. THE SOLENOID VALE START RELAPSING THE GAS 4. ANY ONE IN HTE BUILDING CAN RELEAS MANUALLY THE GAS IN CASE THERE IS FIRE AND THE SYSTEM NOT RESPONED AUTOMATICALLY .