Professional Documents
Culture Documents
Rundong Lv Ke Zhu
Shandong University Shandong University
Jinan, China Jinan, China
e-mail: 18856311051@163.com e-mail: zhuke@sdu.edu.cn
Abstract—The DC bias caused by single pole-ground mode or time of CT and the DC bias, and deduces the quantitative
bipolar unbalanced mode of HVDC transmission or relationship between CT measuring error and DC bias. The
geomagnetic induced current phenomenon may lead to the reference [11] deduces the relationship between CT
measuring CT saturation, which may affect the measurement measuring error and magnetic permeability, and summarizes
performance. Therefore, it is necessary to evaluate the the influence trend of DC bias on the measuring error and
saturation degree of the CT. By using the effective harmonics through experiments. In [12], the influence of DC
permeability, analyzing the equivalent model of CT under DC bias on the saturation start time of CT and its differential
bias state and combining with the electromagnetic relationship protection on transformers is analyzed. The influence of GIC
between flux and voltage, the expression of the saturation
on CT is studied in [13], especially considering its
degree, DC current and circuit parameters is analyzed and
derived. By simulating different types of CT, the effectiveness
characteristics different from HVDC.
of the analytical expression is verified, and the influence on the The above references have analyzed and studied the
saturation degree is analyzed. The actual power system influence of DC bias on error of CT. But these papers need
parameters are used for numerical analysis, and the rough to know some information obtained difficultly, such as CT
estimation of the measurement error is used to show the hysteresis loop, and to calculate in the complex iterative
specific application of the method for analyzing the DC bias process. , Therefore, these methods are not convenient for
magnetic conditions of the measuring CT. evaluating the influence of DC bias on numerous CTs in
practice. Based on the parameters of CT, such as
Keywords-measurement CT; DC bias; effective magnetic magnetization curve, this paper establishes an expression to
permeability; saturation depth quantify the relationship between the CT saturation degree
and the DC bias by analyzing the CT saturation mechanism.
I. INTRODUCTION And then the CT affected significantly by the DC bias is
selected, which can facilitate the subsequent analysis of
High-voltage direct current (HVDC) that works in single transmission characteristics and other effects of the CT.
pole-ground mode, bipolar unbalanced mode or geomagnetic
induced current (GIC) phenomenon may cause DC current to II. ANALYSIS OF EQUIVALENT MODEL
rush into the AC system. Then it may result in the DC bias of
When a geomagnetic storm occurs or HVDC works in
the electromagnetic equipment in the system [1-5], which
single pole-ground mode, the surface potential is unevenly
will threaten the security of the power system. The DC
distributed, and a potential difference is generated between
component of the exciting current causes the DC bias of the
the two transformer grounding points. The transformer
operating point of the electromagnetic device. Then due to
grounding point and the transmission line form a DC loop
the nonlinearity of the core excitation characteristics, the
with the earth, resulting in DC current inrushing. The system,
excitation current increases sharply, and the current is
severely distorted. In recent years, with the increasing as Figure 1 shows, is a simple model of DC bias, where T1
number of HVDC transmission projects, the impact of DC and T2 are represented as the transformer, and I d is DC that
inrushing on the CT operating state of AC systems has been causes DC bias.
attracting more attentions. Therefore, the evaluation of the
influence of DC bias on the operating state of CT has
practical significance for the planning of DC transmission Id
system and the installation and selection of CT. Id
In order to evaluate the influence of DC bias on the Id
operating state of CT, the distribution of inrushing DC in the
AC system is needed to know at first [6-9],and then the T1 T2
working status of each CT distributed in the AC system is
also needed to analyze and evaluate. The research of the
latter currently focuses on the effects of DC bias on the CT 3I d 3I d
transfer characteristics and initial saturation time. Reference
[10] analyzes the relationship between the saturation start
Figure 1. Current loop with DC bias.
2
Where iL is the exciting current on the magnetizing e [ I ds b s k2
(15)
I ds b s k2
2
inductor L , and the DC component of the voltage on the 4k2b s ] / 2k2
magnetizing inductor can be obtained by the (6), The saturation degree is defined as
t
e
I d R2 e 1 (0 t t s ) Ke (16)
uL (7) s
t t t
s s
1 2 When Ke 1 , CT is not saturated. When Ke 1 , CT is
I d R2 e e (t t s )
saturated. The expression of saturation can be obtained from
Where 1 L1 /R2 , 2 L 2 /R2 . The integral (15) and (16),
relationship between voltage and magnetic flux can be Ke [ I ds b s k2
obtained (8), (17)
I ds b s k2 4k2b s ] / 2e k2
2
ts
0
uL dt s m (8)
It can be seen from Fig.3 that due to the error between
Where m is the peak of the magnetic flux when there is the segmental magnetization curve and the original
no inrushing DC. The time when the magnetic flux firstly magnetization curve, in order to reduce the error, I e can be
crosses the inflection point of the magnetic flux can be obtained by (12) and (15). According to Fig.3, the
obtained by substituting the (7) into the (8),
corresponding corrected saturation flux e ' on the original
s m
ts 1 ln( 1) (9) magnetization curve can be obtained. The corrected
I d L1 saturation level can be obtained by substituting the e ' into
If there is no real solution in (9), it means that the equation (17) .
magnetic flux is not in the saturation zone. At this time, the
inductance can be regarded as a linear inductance. According IV. SATURATION SENSITIVITY ANALYSIS
to (7) and the integral relationship between voltage and According to the analysis method of this paper, equation
magnetic flux, the e can be obtained by (10). (17) is used to calculate the of three different types of CT
e m I d R21 (10) saturation degree under different inrushing DC current. The
parameters of CT are shown in Table 1, and the calculated
t
If s is a real number, it means that the magnetic flux saturation value is compared with the simulation value in
starts to enter the saturation zone, and CT starts to have Simulink, as Figure 4 shows.
magnetic bias saturation. According to (7) and the Based on the circuit principle, the saturation caused by
relationship between magnetic flux and excitation voltage, the DC bias isproportional to the magnitude of the inrushing
(11) is obtained. DC and the duration of the transient process. As can be seen
from Fig. 4, the greater the intensity of the inrushing DC is,
ts
uL dt e s (11) the greater the degree of CT saturation can be. In addition,
according to the magnetization curve shape of CT LB7-
According to Figure 4, the relationship e between I e 110W3 and LMZ-3, the flux inflection points are far away
from the CT normal operating point and the overall slope is
can be obtained,
large, so they are saturated under the influence of DC bias.
k1 e 0 t ts
The LB6-35W3 type CT does not saturate because the flux
Ie (12) inflection point is close to the CT normal operating point and
k2 e b(t ts )
the overall slope is small.
3
1.4 CT1-CT5 compared with the simulation are shown in Table
2-4. It can be seen that the calculated result of CT saturation
1.2 by using (17) is very close to the simulation value, which
indicates that the proposed algorithm can calculate the CT
saturation effectively under the influence of DC bias.
Saturation degree
4
This approximation method is used to estimate the CT REFERENCES
measurement error caused by DC bias, and the results are [1] Zhao W. HVDC transmission engineering technology . China Electric
shown in Table 5-7. Power Press,2005,pp 318-324
[2] Li X, Wen X, Lan L. “DC bias test and simulation of single-phase
TABLE V. COMPARISON OF CT ERROR CALCULATIONS AND SIMULATION transformer” . Proceedings of the CSEE, 2007, 27(9):pp 33-40.
RESULTS AT EACH LOCATION (INVASION DC 50A)
[3] He J, Yu Z, Zeng R, et al. “Vibration and Audible Noise
Characteristics of AC Transformer Caused by HVDC System Under
Position Calculation /% Simulation /% Monopole Operation”. IEEE Transactions on Power Delivery, 2012,
CT1 0.261 0.267 27(4):pp 1835-1842..
CT2 0.001 0.001
CT3 0.351 0.408 [4] Albertson V D, Bozoki B, Feero W E, et al. “Geomagnetic
CT4 0.312 0.357 disturbance effects on power systems”. IEEE Transactions on Power
Delivery, 2002, 8(3):pp 1206-1216.
CT5 0.001 0.001
[5] Price P R. “Geomagnetically Induced Current Effects on
Transformers”. IEEE Power Engineering Review, 2007, 22(6):pp 62-
TABLE VI. COMPARISON OF CT ERROR CALCULATIONS AND SIMULATION
62.
RESULTS AT EACH LOCATION (INVASION DC 100A)
[6] Zhang B, Zhao J, Zeng R. “Prediction method of DC current
Position Calculation /% Simulation /% distribution in AC system during DC earth operation” . Proceedings
CT1 0.262 0.310 of the CSEE, 2006, 26(13):pp 84-88
CT2 0.351 0.509 [7] Ruan L, Wen X, Kang J,. “AC system DC network model considering
CT3 0.354 0.513 deep earth resistivity” . Power System Technology, 2014, 38(10):pp
CT4 0.377 0.328 2888-2893.
CT5 0.168 0.179 [8] Pan Z, Zhang L, Tan B,. “Simulation Analysis of the Distribution of
HVDC Transmission Ground Current in AC Power Grid”.
TABLE VII. COMPARISON OF CT ERROR CALCULATIONS AND SIMULATION Automation of Electric Power Systems, 2011, 35(21):pp 110-115.
RESULTS AT EACH LOCATION (INVASION DC 150A) [9] Liu Q, Li L, Zheng J. “Current Distribution of HVDC System in
Single Maximum Operation under Compound Soil Model” .
Position Calculation /% Simulation /% Proceedings of the CSEE, 2007, 27(36):pp 8-13.
CT1 0.265 0.396 [10] Li C, Li Q, Li J,. “Transmutation characteristics of current
CT2 0.512 0.609 transformer under DC bias conditions” . Proceedings of the CSEE,
CT3 0.357 0.549 2010, 30(19):pp 127-132.
CT4 0.380 0.329
CT5 0.169 0.232 [11] Tan B, Lu W, Jiang B. “Analysis of Influence of DC Bias on
Performance of Current Transformer for Metering” . Power System
Technology, 2014, 38(5):pp 1408-1413.
VI. CONCLUSION
[12] Zheng T, Cheng P, Liu L,. “Influence of Transient Characteristics of
In this paper, the expression of saturation degree during Current Transformer Considering DC Bias on Differential
DC bias is derived. By comparing the calculated and Protection” . Automation of Electric Power Systems, 2012, 36(20):pp
simulated values of saturation, the effectiveness of the 89-93.
proposed algorithm is verified. [13] Zheng T, Cheng P, Mao A,. “CT saturation characteristics under the
action of geomagnetic induced current and its transformer differential
1) Through the analysis and simulation of the DC bias, it protection misoperation”. Power System Technology, 2014, 38(2):pp
is proved that the increase of the inrushing DC and transient 520-525.
duration will increase the saturation degree. [14] Tan Y. Electrical Engineering.. Mechanical Industry Press, 2011.
2) By setting up CT in the actual system for simulation, [15] Tan B, Lu J, Jiang B,. “Analysis of Influence of DC Bias on
the feasibility of applying the method in this paper to the Performance of Current Transformer for Metering” . Power System
calculation of saturation degree and rough estimation of Technology, 2014, 38(5):pp 1408-1413.
measurement error in the actual system is verified.