You are on page 1of 13

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
1

Zone I Distance Relaying Scheme of Lines Connected


to MMC-HVDC Stations During Asymmetrical Faults:
Problems, Challenges and Solutions
Yingyu Liang, Member, IEEE, Wulin Li, and Yaotong Huo

Abstract—The exclusive fault behaviors of MMC-HVDC stations MMC-HVDC stations on distance protection and propose a
bring great challenges to the correct operations of distance relays. new distance relaying scheme considering the unique fault
This paper presents a new zone I distance relaying scheme that can characteristics of MMC-HVDC stations during asymmetrical
accurately calculate fault distance in the case of integration of
faults that account for the majority of faults.
MMC-HVDC system. The two calculation formulas of fault
distance are derived from mathematical perspective and Based on the assumption of the fault path being purely
geometrical relationship of impedances, respectively. Phase angle resistive, Xu et al. [9]-[11] presented distance relaying schemes
of fault current is the key to calculate fault distance. In power against fault resistance, which can accurately locate the fault
system without MMC-HVDC stations, the existing method for location. Ma et al. [12]-[13] presented two adaptive distance
solving this phase angle is based on two premises, that is, the relaying schemes, minimizing the negative effects of fault
positive- and negative-sequence current distribution factors are
resistance on distance relays. In [14], another adaptive distance
equal and real numbers. However, owing to the integration of
MMC-HVDC system, aforementioned premises are both not true. relaying scheme was proposed, featuring an adaptive setting
Consequently, the existing method cannot obtain accurate phase following structural and operational changes to prevent zone-1
angle of fault current. To solve this problem, the three solutions malfunction. However, if fault point is outside the fixed
corresponding to three different types of asymmetrical faults are boundary, 2 cycles delay is essential for the relay to achieve the
provided. The proposed scheme has the advantages of satisfactory trip decision. Reference [15] presented a novel digital distance
immunity against fault resistance, applicable to various
relaying scheme that eliminates the errors introduced by fault
asymmetrical faults, and performing well under rectifier as well
as inverter modes. The performance of the proposed scheme is resistance. The proposed scheme neglects system impedance,
evaluated by simulation results in PSCAD/EMTDC and which is not feasible for the line connected to the MMC-HVDC
compared with prior-art schemes. station. In [16], distance protection using artificial neural
Index Terms—Distance protection, MMC-HVDC system, fault networks (ANNs) for transmission lines was presented, which
distance, negative-sequence impedance shaping. can estimate the line impedance from the relay to fault point. As
Prasad and Nayak stated in [17], besides complexity of the
I. INTRODUCTION structures and training data, ANNs-based distance protection

D UEto its advantages of modularity, scalability, low


switching loss and low distortion of output current,
modular multilevel converter (MMC) has been a promising
incurred large storage and a heavy calculation burden. In [18],
the authors presented a new distance protection scheme that
correctly discriminates in-zone and out-of-zone faults by
candidate for high voltage direct current application (HVDC) comparing the amplitudes of the improved original and virtual
[1]-[3]. Since the Trans Bay Cable project in March 2010, measured voltages. In [25], the authors presented a new line
dozens of MMC-HVDC projects have been put into operation fault impedance calculation method, which can locate the fault
worldwide [4]-[5]. Significant differences in fault location. Compared with conventional distance protection, the
characteristics between conventional synchronous sources and aforementioned schemes offer a better performance. However,
MMC-HVDC stations may result in malfunction of protective these schemes were designed for protecting transmission lines
relaying schemes of the line emanating from an MMC-HVDC connected to conventional synchronous sources at both ends
station. Distance protection is an attractive option for line and the unique fault characteristics of MMC-HVDC stations
protection, and it is widely applied in high voltage transmission were not considered.
lines [6]-[8]. Therefore, this paper aims to study the effects of Considering the fault characteristics of DFIG-based wind
farm, two distance relaying schemes were presented to protect
This work was supported in part by the National Natural Science Foundation
of China under Grant 51707193, in part by the Yue Qi Young Scholar Project of transmission lines connected to DFIG-based wind farm
China University of Mining and Technology (Beijing), and in part by the [19]-[20]. However, fault characteristics of DFIG-based wind
Fundamental Research Funds for the Central Universities under Grant farm are significantly different with those of MMC-HVDC
2020YQJD01. (Corresponding author: Yingyu Liang.)
Y. Liang, W. Li, and Y. Huo are with School of Mechanical Electronic and
stations. Alam et al. [21]-[22] studied the impact of the
Information Engineering, China University of Mining and VSC-HVDC station on the operation of distance relay. The
Technology(Beijing), Beijing 100083, China (e-mail: results showed that distance relay was prone to under-reach
liangyingyu2013@163.com; lmmx1995@163.com; huoyaotong2018
@163.com)
problem because of limited fault current amplitude of
VSC-HVDC station. Nevertheless, the solution to removing the

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
2

adverse effect caused by VSC-HVDC station was not XT=0.14pu, RT=0.032pu.


mentioned. Reference [23] presented an apparent impedance ER ZR S1
Grid
calculation method to identify miscoordinated backup M IM IN N ES
SW Uf ZS
protection relays caused by VSC-HVDC during three-phase CT CT
F
fault. However, the authors in [23] did not study asymmetrical MMC-HVDC station PT PT

MMC If Rf
faults that account for the majority of faults. Zolfaghari et al. transformer R2
R1
[24] pointed that in-feed current of the HVDC converter can DC
side
cause zone-2 distance relay to overestimate the fault distance. S2

A robust control approach for voltage source converter of


Fig. 1. Analysis model for the effects of MMC-HVDC station on distance
HVDC system was presented to overcome this problem. Still, a protection.
zone-1 distance relaying scheme that eliminates adverse effects To compare the effects of MMC-HVDC station and
of MMC-HVDC stations remains none. References [28]-[30] synchronous source on distance protection, the switch SW, in
presented novel distance protection schemes for lines Fig. 1, is used to choose synchronous source or MMC-HVDC
connecting full-scale converter-interfaced renewable energy station to connected to bus M. In Fig. 1, relay R1 is on the
power plants. The fault distance cannot be calculated by the MMC-side of line MN, while relay R2 is on the grid-side of line
proposed schemes. Based on the assumption that grid strength MN. When a fault occurs in the transmission line, the measured
is sufficiently large compared to PV plants, an approximation impedances of relay R1 and relay R2 are both the ratio of the
relation between the fault current and the current at the relay measured voltage U m over the measured current I m :
point was derived in reference [31]. However, when solar
Um
plants or MMC-HVDC stations are connected to a weak grid, a Zm = = xZ L1 + Z (1)
Im
non-negligible error may be introduced. Given the increasing
number of MMC-HVDC projects and the importance of zone-1 where x is fault distance from the relay point to the fault point,
distance protection, it is of great significance to propose a zone ZL1 is positive-sequence impedance per unit length of line MN,
I distance relaying scheme that is applicable to the transmission ∆Z is the additional impedance caused by the fault resistance.
lines connected to MMC-HVDC stations. A. Effects of MMC-HVDC Station on Ground Distance Relays
Herein, a new zone I distance relaying scheme that considers
the unique fault characteristics of MMC-HVDC station is Assuming that a phase-A-to-ground fault (AG) occurs with a
proposed. This paper is organized as follows. The effects of fault resistance Rf, the effects of MMC-HVDC station on
MMC-HVDC station on distance relays on grid-side and ground distance relays are investigated in this subsection. As
MMC-side were analyzed in Section II. The challenges and shown in (1), regardless of relay R1 or relay R2, the measured
solutions of solving phase angle of fault current were impedances consist of additional impedance and line fault
expounded. Moreover, two equivalent calculation methods of impedance, i.e., line impedance from the relay point to fault
fault distance were presented in Section III. Simulation results point. The performances of distance relays are primarily
were provided to verify the correctness and effectiveness of affected by additional impedance ∆Z, caused by the fault
proposed distance relaying scheme in Section IV. The main resistance Rf. When synchronous source R is connected to bus
contributions and the limitations of this study were provided in M, additional impedance of relay R1 in (1) is expressed:
I fa 3 I fa0
Section V. Finally, conclusions were drawn in Section VI. Z ss
R1
= Rf = Rf
I Ma + 3KI Ma 0 I Ma + 3KI Ma 0
II. PROBLEM STATEMENT 3I fa0 (2)
= [0] Rf
Fig. 1 illustrates the analysis model for the effects of I Ma + I Ma1 + I Ma 2 + (1 + 3K ) I Ma 0
MMC-HVDC station on distance protection. In Fig. 1, switch I Ma1
SW is used to choose a synchronous source or an MMC-HVDC
station to connected to bus M. Point F represents the fault point. where superscript “[0]” denotes prefault quantity, so I Ma
[0]
is
U f and I f are the voltage at the fault point and current prefault load current at the relay point M. Subscripts “1”, “2”
flowing through the fault path, respectively. The parameters of and “0” denote positive-, negative- and zero-sequence
the 200-km-long 500 kV line MN are: R1 =0.01839 Ω/km, components, respectively. IMa1 is postfault current, and ∆IMa1 is
XL1 = 0.263 Ω/km, XC1 =500.1314 MΩ*m, R0 = 0.1417 Ω/km, superimposed current that is the difference between postfault
XL0 = 0.6027 Ω/km, and XC0 = 800.5217 MΩ*m. The current and prefault load current. K is zero-sequence
parameters of system R are: ZR1 = 0.6278 + j8.9781 Ω, compensation factor and K=(ZL0−ZL1)/ (3ZL1).
ZR0 = 3.3743 + j 14.6156 Ω, and ER= 525∠15°. The parameters For conventional power system with synchronous sources, in
of system S are: ZS1 = 0.6278 + j8.9781 Ω, the case of AG faults, the following relations are satisfied:
ZS0 = 3.3743 + j14.6156 Ω, and ES = 525∠0°. Zone-1 distance arg(I Ma1) = arg( I Ma 2 )  arg( I Ma 0 )  arg( I fa0 ) (3)
relay is set to protect 80% of line MN. The parameters of Additionally, compared with superimposed positive-
MMC-HVDC station are: S=1000MVA, DC link sequence current, prefault load current can be negligible.
voltage=700kV. The parameters of transformer are: Therefore, (2) can be further simplified as follows:
S=1100MVA, rated transformation ratio is 525/375 kV,

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
3

3 I fa0 synchronous source R is connected to bus M, ignoring pre-fault


Z ss
R1
 Rf (4) current, additional impedance of relay R1 is expressed:
I Ma1 + I Ma 2 + (1 + 3K ) I Ma 0
I fb − I fc I − I Nc 
When an MMC-HVDC station is connected to bus M, Z ss
R1
= R f = 1+ Nb Rf
I Mb − I Mc  I Mb − I Mc 
[0]
I Ma + I Ma1 + I Ma 2 is generally significantly less than (7)
 ( I Nb1 − I Nc1 ) + ( I Nb 2 − I Nc 2 )   I Na1 
 1+  R f  1+  R f
 ( I
(1 + 3K ) I Ma0 because of the poor overcurrent capacity of  Mb1 − I Mc1 ) + ( I Mb 2 − I Mc 2 )   I Ma1 
MMC. As a result, additional impedance of relay R1 can be When an MMC-HVDC station is connected to bus M,
simplified to (5): additional impedance of relay R1 in (1) is expressed:
3 I fa0  ( I Nb1 − I Nc1 ) + ( I Nb 2 − I Nc 2 ) 
Z MMC
R1
 Rf (5) Z MMC
R1
 1+  R f
 ( I Mb1 − I Mc1 )
(1 + 3K ) I Ma0  
(8)
 2I Na1 
Comparing (4) with (5), Z MMC
R1
is greater than Z ss
R1
.  1+ Rf
 I Ma1 
Thereby, compared with synchronous sources, MMC-HVDC
stations further aggravate the adverse effect of fault resistance Comparing (7) with (8), phase angle of Z ssR1 approximates
on distance relay on MMC-side, i.e., relay R1. 0°, while phase angle of Z MMC
R1
is highly affected by control
Similar to the previous analysis and derivation process,
system of MMC-HVDC. Generally, there is not much
additional impedances of relay R2 are expressed:

difference between I Ma1 and I Na1 in (7). Due to the poor
3 I fa0
Z ss
R2

 I Na1 + I Na 2 + (1 + 3K ) I Na 0
Rf overcurrent capacity of MMC, I Na1 is much larger than

 (6) I Ma1 in (8). Therefore, compared with synchronous source,
 R2 3 I fa0
 Z MMC  Rf
 I fa1 + I fa 2 + (1 + 3K ) I Na 0 integration of MMC-HVDC stations significantly aggravates
 the adverse effect of fault resistance on relay R1.
As shown in (6), Z MMC
R2
is less than Z ssR 2 . This indicates Similar to the previous analysis and derivation process,
additional impedances of relay R2 are expressed:
that integration of MMC-HVDC stations mitigates the adverse
 R2  I 
effect of fault resistance on distance relay on grid-side, i.e.,  Z ss  1+ Ma1  R f
 
relay R2.   I Na1 
 (9)
Fig. 2 shows the additional impedances under an AG fault  R2  I Ma1 
occurring at the midpoint of line MN with a fault resistance of Z MMC  1+ 2I Rf  Rf
  Na1 
10Ω. The station operates in inverter mode. In Fig. 2, Z ssR1 <
As observed from (9), Z ss
R2
is larger than Z MMC
R2
. This
Z MMC
R1
, and Z ss
R2
> Z MMC
R2
. Additional impedance ∆Z indicates that integration of MMC-HVDC station mitigates the
represents the error between measured impedance Zm and line adverse effect of fault resistance on relay R2.
fault impedance xZL1. The smaller the additional impedance ∆Z, Fig. 3 shows the additional impedances under a BC fault
the better the performance of distance relay. As observed from occurring at the midpoint of line MN with a fault resistance of
Fig. 2, compared with synchronous source, integration of 10Ω. The results shown in Fig. 3 are highly consistent with the
MMC-HVDC station further aggravates the adverse effect of theoretical analysis above.
30
fault resistance on relay R1, while it mitigates the adverse effect 30
20
of fault resistance on relay R2. This conclusion is highly
10
ZssR1 25

consistent with the theoretical analysis above. ZMMC


R1
20
X/Ω
X/Ω

0 15
Z ssR 2
30 35

25 30 -10 10

20
25 -20 5 Z MMC
R2

xZL1 20
X/Ω
X/Ω

-30 0
15 xZL1
Z ssR 2
0 10 20 30 40 50 60 0 5 10 15 20 25
ZssR1
15
R/Ω R/Ω
10
10
Z MMC
R2
(a) (b)
5 ZMMC
R1
5
Fig. 3. Additional impedances under a BC fault. (a) relay R1. (b) relay R2.
0 0
0 5 10 15 20 25 0 5 10 15 20
R/Ω R/Ω
It should be noted that the analysis process described above
(a) (b)
Fig. 2. Additional impedances under an AG fault. (a) relay R1. (b) relay R2.
is not applicable to the high-resistance faults. According to the
previous analysis, in the presence of MMC-HVDC stations,
B. Effects of MMC-HVDC Station on Phase Distance Relays even though the value of fault resistance is not large, the
Assuming that a phase B-to-phase C fault (BC) occurs with a distance relay may operate incorrectly. In the case of
fault resistance 2Rf, the effects of MMC-HVDC station on high-resistance faults, a large additional impedance causes
phase distance relays are investigated in this subsection. When distance relay a high risk of incorrect operations. This paper

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
4

aims to solve this problem. derived from a mathematical perspective in the first method,
while it is derived from the geometrical relationship of
C. Performance Problem of Distance Relay on the MMC-side
measured impedance Zm, line fault impedance xZL1 and
According to the previous analysis, the integration of additional impedance ∆Z in the second method.
MMC-HVDC stations aggravates the adverse effect of fault 1) The first method
resistance on distance relay on MMC-side, i.e., relay R1, (10) can be rewritten as:
whereas it mitigates the adverse effect of fault resistance on Rm + jX m = x ( RL1 + jX L1 ) +
distance relay on grid-side, i.e., relay R2. Therefore, relay R1 is
( ) ( )
If (11)
prone to maloperation. This subsection will illustrate the R f cos I f − I m + j sin I f − I m 
performance problem of distance relay on the MMC-side. Im  
The reach setting of relay R1’s zone I is 80% of line MN. (
− j I f −I m )
Two case studies are used to illustrate performance problem of Multiplying both sides of (11) with e , (12) can be
distance relay on the MMC-side. In case 1, a obtain
phase-A-to-ground fault occurs at 60% of line MN from bus M ( ) ( ) If
( Rm + jX m ) e = x ( RL1 + jX L1 ) e
− j I f −I m − j I f −I m
with a fault resistance of 8Ω, which is within the protected zone + Rf
Im
of relay R1’s zone I. In this case, the station operates in rectifier
mode. In case 2, a phase-B-to-phase C fault occurs at 90% of (12)
line MN from bus M with a fault resistance of 2Ω, which is Thus,
( ) − j ( I f −I m ) 
Im ( Rm + jX m ) e = Im  x ( RL1 + jX L1 ) e
outside the protected zone of relay R1’s zone I. In this case, the − j I f −I m
station operates in inverter mode. The impedances measured by    
relay R1 are shown in Fig. 4. (13)
As observed from Fig. 4, the measured impedance in case 1
where Im[•] represents the operation of taking the imaginary
is outside the operation zones of mho and quadrilateral
characteristics, whereas the measured impedance in case 2 part of a complex number.
enters into the operation zones of mho and quadrilateral Then, fault distance can be obtained from (13):
characteristics in steady state. Consequently, the internal fault
x=
( )
X m cos I f − I m − Rm sin I f − I m ( ) (14)
in case 1 is misidentified as an external fault, and relay R1 fails ( )
X L1 cos I f − I m − RL1 sin I f − I m ( )
to operate. The external fault in case 2 is misidentified as an
internal fault, causing unwanted operation of relay R1. This 2) The second method
paper aims to present a new zone I distance relaying scheme to Geometrical relationship of measured impedance Zm, line
solve the performance problem of distance relay on the fault impedance xZL1 and additional impedance ∆Z is shown in
MMC-side. Fig. 5. In Fig. 5, φline is the phase of the line impedance. φzm is
200
the phase of measured impedance. In Fig. 5, OQ is
Case 1 mho characteristic
perpendicular to AB. Accordingly, ∆OAQ and ∆OBQ are both
150 quadrilateral characteristic right triangles.

100 Case 2
jX
X/Ω

A
50 Q I m − I f
xZL1

0 ∆Z
-50
-20 0 20 40 60 80 100 120 line B
R/Ω Zm
Fig. 4. Impedances measured by relay R1 for cases 1 and 2.  zm I m − I f
o R
Fig. 5. Geometrical relationship of measured impedance, line fault impedance
III. A NEW ZONE I DISTANCE RELAYING SCHEME and additional impedance in the complex plane.
A. Basic Principle
From Fig. 5, the following relations are obtained:
According to Fig. 1, the measured impedance of relay R1 can
OAQ =  − line +I f − I m
be expressed:
Um If OBQ =  zm − I f + I m (15)
Zm = = xZ L1 + Z = xZ L1 + Rf (10)
Im Im OA = x Z L1 , OB = Z m
If fault distance x is accurately calculated, the distance relay In ∆OAQ, OQ is calculated as:
can achieve accurate fault location. As a result, distance relay
can determine whether the fault is within the protection zone.
(
OQ = OA  sin OAQ = x Z L1 sin  − line+I f − I m ) (16)
This paper presents two equivalent calculation methods of In ∆OBQ, OQ is calculated as
fault distance. The computational formula of fault distance is

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
5

(
OQ = OB  sin OBQ = Z m sin  zm − I f + I m ) (17)
xZ L1 = Z L1
( ) (
X m cos I f − I m − Rm sin I f − I m ) (21)
According to (16) and (17), fault distance is obtained: X L1 cos ( I f − I m ) − RL1 sin ( I f − I m )

x=
(
Z m sin  zm − I f + I m ) (18)
In (20) and (21), except I f , other quantities can be obtained
(
Z L1 sin line − I f + I m ) based on local electrical quantities and discrete Fourier transform.
Substituting (19) into (18), Hence, solving I f is the key to calculate fault distance and
X m = Z m sin  zm , Rm = Z m cos  zm line fault impedance.
(19)
X L1 = Z L1 sin line , RL1 = Z L1 cos line B. Challenges in Solving I f
we obtain
Although the fault current If cannot be measured, I f can
x=
( ) (
X m cos I f − I m − Rm sin I f − I m ) (20) be still obtained according to the phase relationship of the fault
X L1 cos ( I f − I m ) − RL1 sin ( I f − I m ) current If and the current at the relay point M, as stated in [25].
Comparing (14) with (20), they are exactly identical. For different types of asymmetrical faults, AG, BC and BCG
Therefore, the two proposed calculation methods are faults are taken as examples. According to reference [25], the
equivalent. calculation formulas of I f are shown in (22). In (22), C1 and
The line fault impedance can be expressed as follows: C2 are positive- and negative-sequence current distribution
factors, respectively.
  I 
 I fa =  Ma1   I Ma1, phase A - to - ground fault(AG)
  C 1 

  3I Ma1  
I f =  (
 I fb − I fc =   − j

2
)   I Ma1 − , phase B - to - phase C fault(BC) (22)
  C1  2

 
 I − I = I Mb1 − I Mc1 + I Mb2 − I Mc2   ( I − I ) , phase B - to - phase C - to - ground fault(BCG)
 fb (
fc  )  Mb Mc
  C1 C2 
The correctness of (22) depends on the following two The reference current phasors of the MMC-HVDC station
premises. can be expressed as follows [3]:
Premise 1: C1 is almost a real number, i.e., C1 ≈0°.
Premise 2: C1 = C2.
I ref =
2
3(U1 )2
(U 1Pref + U1Qref )
For conventional synchronous sources-based power system, (25)
these two premises are true. However, for power system Iref =
2
3(U1 ) 2
(U1Pref + U 1Qref )
including MMC-HVDC system, like Fig. 1, this is not the case.
According to Fig. 6, C 1, C2 and C0 are expressed as follows: where Pref and Qref are reference values of active and reactive
I M 1 ( LMN − x ) Z L1 + Z S1 power.
C1 = = Owing to excellent performance of MMC’s control system,
I f 1 Z MMC1 + LMN Z L1 + Z S1 the output currents can track the reference values. In the steady
IM 2 ( LMN − x ) Z L 2 + Z S 2 state, the positive-sequence current of the MMC-HVDC station
C2 = = (23) can be expressed as follows:
I f2 Z MMC 2 + LMN Z L 2 + Z S 2
2 Q
I M1 = Pref2 +Qref
2
(1 +  − arctan ref )
IM 0 ( LMN − x ) Z L0 + Z S 0 3U1 Pref
(26)
C0 = =
I f0 Z T0 + LMN Z L 0 + Z S 0 In normal condition, the pre-fault voltage and current
where x is fault distance from bus M to fault point F, and LMN is phasors of the MMC-HVDC station can be expressed:
the length of line MN. ZT0 is zero-sequence impedance of the U1 2k P
U M[0] = (1 +  −  ), I M[0] =  0 (1 +  −  ) (27)
transformer in the MMC-HVDC station. = a, b, c. k 3U1
When an asymmetrical fault occurs, the three-phase terminal where kλ is positive-sequence voltage drop factor, which is the
voltage phasors of the MMC-HVDC station can be expressed ratio of positive sequence voltage after and before the fault. P0
as follows: is the active power of the station during normal condition. ∆δ is
U M = U M1 + U M 2 the angular difference of positive-sequence voltages after and
(24)
= U1(1 +  ) + U 2 ( 2 −  ) before the fault. Superscript [0] denotes pre-fault voltage or
current.
where U1 and U2 are the amplitudes of the positive- and
Equivalent positive-sequence impedance of MMC-HVDC
negative-sequence voltages, respectively. δ1 and δ2 are the
station ZMMC1 is derived as follows:
initial phase angles of the positive- and negative-sequence
phase-A voltages, respectively. δa = 0°, δb = −120°, and δc =
120°.

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
6

U M1 U M1 − U M[0] ZMMC1


Z MMC1 = − =− = 1000 200
I M1 I M1 − I [0]
M amplitude
phase angle
( k − cos  ) + ( sin  )2
2 800 100
3U 2
− 1

phase angle/(°)
(28)

amplitude/Ω
(P − k P0 cos  ) + ( k P0 sin  − Qref )
2 2
2k
ref 600 0

  sin    k P0 sin  − Qref  


  arctan  − arctan  
  Pref − k P0 cos   
400 -100
  k − cos  
    
As shown in (28), ZMMC1 is related to many factors, e.g., U1, 200
0 20 40 60 80
-200
100
kλ, P0, ∆δ, Pref and Qref. Therefore, equivalent positive-sequence fault resistance/Ω

impedance of MMC-HVDC station ZMMC1 is affected by Fig. 7. Equivalent positive-sequence impedance of MMC-HVDC station
(ZMMC1) under phase A-to-ground faults occurring at the middle of line MN
control system of MMC, fault conditions and system with different fault resistances.
parameters. This leads to a varying ZMMC1 and a significant
difference in the phase angle between ZMMC1 and 0.2 240
amplitude phase angle 200
positive-sequence line impedance ZL1. As shown in Fig. 7,
amplitude and phase angle of ZMMC1 vary with the fault 0.15
100

phase angle/(°)
Zero degree line(0°)
resistance. As a result, C1 is a variable quantity and is not a real

amplitude
number. Fig. 8 shows C1 under phase A-to-ground faults 0
0.1
occurring at the middle of line MN with different fault
resistances. As observed from Fig. 8, amplitude of C1 varies -100
0.05
with the fault resistance, which is significantly different with
that of conventional synchronous source. Moreover, phase 0 20 40 60 80
-200
100
angle of C1 deviates significantly from 0°. Therefore, premise 1 fault resistance/Ω

is not true in the case of an MMC-HVDC station connecting Fig. 8. Positive-sequence current distribution factor under phase A-to-ground
bus M. faults occurring at the middle of line MN with different fault resistances.
To protect the power electronic components of MMC and C. Solutions to Solve I f
prevent overcurrent problem, negative-sequence current is
usually eliminated during asymmetrical faults. Thus, Considering the difference between MMC-HVDC station
I M 2  0 (29) and synchronous source, the solutions to solve I f are
provided in this subsection.
In this case, ZMMC2 is close to infinity, i.e., ZMMC2≈∞. Based
1) Single-phase-to-ground fault
on (23), C2 is approximately zero, and thereby C1≠C2.
Take an AG fault as an example. Since ZMMC1 is affected by
Consequently, premise 2 is not true, either.
control strategy of MMC-HVDC, C1 is not a real number.
Based on the previous analysis, due to the unique fault
Therefore, (22) is not applicable to the lines emanating from
characteristics of MMC-HVDC system, the two premises are
MMC-HVDC stations during single-phase-to-ground faults. As
both not true and the existing solution of solving I f fails.
shown in Fig. 1, transformer of MMC-HVDC station is in Ygd
This brings great challenges in solving I f . connection; therefore, zero-sequence network is unaffected by
 =a,b,c MMC-HVDC stations. Consequently, zero-sequence current
MMC-HVDC I M1 I N1 distribution factor C0 can be seen as a real number, i.e., C0
Grid
station M xZ
L1
F U f 1(LMN–x)ZL1
N ≈0°. Therefore, when an AG fault occurs, I f can be obtained
superimposed ZMMC1
positive-sequence
U M1 Rf I f 1 U N1 based on the method presented in [15].
network ZS1
2) Phase-to-phase fault
I M 2 I N 2
(i) Negative-sequence impedance shaping scheme
M xZ N
(LMN–x)ZL2
Take a BC fault as an example. The fault current is
L2 F U f2
superimposed ZMMC2 expressed:
negative-sequence
Rf I f2 U N 2
network U M 2 ZS2 2 3I Ma 2
I f =I fb − I fc = j (30)
C2
I M 0 I N 0
M xZ N Based on the assumption that C 2 ≈0°, I f can be obtained:
L0 F U f  0 (LMN–x)ZL0
ZT0  2 3I Ma 2  
superimposed zero-
sequence network
U M 0 Rf I f0 U N 0
ZS0 I f =  j   I Ma 2+ (31)
 C 2  2
However, for MMC-HVDC station with conventional
Fig. 6. Superimposed sequence networks in the case of an asymmetrical fault. control strategy, since negative-sequence current is eliminated,

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
7

the assumption is false. Therefore, to obtain I f , a new 1800


Z MMC 2
89

control strategy is required.


1600
Z MMC 2 line 88
1400

phase angle/(°)
To make the assumption that C 2 ≈0° true, the following 87

amplitude/Ω
1200
86
relation must be satisfied according to (23):
1000
Z MMC 2  Z S 2  Z L 2=line (32) 85
800
84
To achieve the relation in (32), a negative-sequence 600
impedance shaping scheme for MMC is proposed. Since 0 10 20 30 40
83
50
fault resistance/Ω
negative-sequence impedance is the ratio of negative-sequence
(a)
voltage over negative-sequence current, negative-sequence
10
impedance of MMC can be shaped by controlling the injected
negative-sequence current. 5
C 2

phase angle/(°)
According to (24) and (32), we can obtain
 U M 2  0
Z MMC 2=  −  = line  I M 2= 2 −  − line+ (33)
 I M 2 
  -5

Hence, negative-sequence reference current of MMC in -10


5 10 15 20 25 30 35 40 45 50
stationary frame is expressed as: fault resistance/Ω

(
i*M 2 =  I rated cos t +  2 −  − line+ ) (34) (b)
Fig. 9. Performance evaluation of negative-sequence impedance shaping
where Irated is the rated current of MMC. λ is the ratio of scheme. (a) ZMMC2. (b) ∠C2.
negative-sequence amplitude to the rated current. To prevent
power electronic components of MMC overcurrent and make (ii) Negative-sequence voltage-based scheme
three-phase current almost balanced, λ is set to a small value. When the aforementioned negative-sequence impedance
In negative-sequence synchronous frame, (34) is rewritten shaping scheme is adopted, I f can be obtained under
− j( 2 −line + )
2 = id 2 + jiq 2 =  I rated e
* * *
idq (35) phase-to-phase faults. However, to enable MMC to generate
By arranging and simplifying (35), negative-sequence the desired negative-sequence current, the software of MMC
reference current of MMC in dq synchronous frame can be must be upgraded, which increases the software cost and
obtained: complexity of the control system. To tackle this issue, an

id 2 = − I rated ( ud 2 cos line − uq 2 sin line ) U 2


effective and simpler scheme is provided, namely
*
negative-sequence voltage-based scheme. For this scheme,
* (36)
iq 2 = − I rated ( ud 2 sin line + uq 2 cos line ) U 2
I f can be obtained without the requirement of injecting
negative-sequence current. This brings two benefits: 1) lower
where λ, Irated and φline are constants. ud2 and uq2 can be obtained overcurrent risk; 2) conventional control strategy of MMC can
by rotating coordinate transformation. U2= ud 2 + uq 2 .
2 2
be used and software of MMC remains unchanged.
For a BC fault,  =a in Fig. 6. Applying the Kirchhoff’s
Classic dual current control scheme is generally adopted by
current and voltage laws in superimposed negative-sequence
MMC, which can regulate both positive- and
network shown in Fig. 6, the following relations can be
negative-sequence currents to track their respective reference
obtained:
currents [26].
Fig. 9 displays equivalent negative-sequence impedance and I fa 2 = I Ma 2 +I Na 2 , U fa 2 =U Ma 2 − x pu Z L 2 I Ma 2

 Z S 2 + (1 − x pu ) Z L 2  I Na 2 + U fa 2 = 0
current distribution factor under phase B-to-phase C faults (37)
 
occurring at the middle of line MN with different fault
resistances. As shown in Fig. 9, when the proposed As explained in subsection III.B, for conventional control
negative-sequence impedance shaping scheme is adopted, strategy of MMC, negative-sequence current is usually
phase angle of equivalent negative-sequence impedance eliminated. Thus, the relation in (29) is satisfied. Substituting
approximates phase angle of line impedance, i.e., Z MMC 2 ≈ (29) into (37), the following relations are derived [28]:
line . Consequently, C 2 is very close to 0°, so I f can be U fa 2 U Ma 2
I fa 2  I Na 2 = − −
solved by (31). Z S 2 + ( LMN − x ) Z L 2 Z S 2 + ( LMN − x ) Z L 2
(38)
Generally, negative-sequence impedances of the grid and
line have a similar X/R ratio, i.e.,
Z S 2  Z L 2 =line (39)
Based on (38) and (39), we obtain
I fa 2  U Ma 2 − line −  (40)

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
8

For a BC fault, the fault current can be expressed as follows evaluated in a test system established in PSCAD/EMTDC (Fig.
( 2
)
I f =I fb − I fc = a − a ( I fa1 − I fa 2 ) =j2 3I fa 2 (41) 1). The SW is connected to S2. In PSCAD, the power system
with MMC-HVDC system is set up based on components of
Thus, master library. The control system of MMC-HVDC is realized
  using a user defined component and FORTRAN language. To
I f =I fa 2 + =U Ma 2 − line − (42)
2 2 evaluate performance of the proposed scheme and compare it
From (42), I f can be solved according to the relation with the prior-art schemes, a user defined component named
“relay” is built, which is used to simulate a real distance relay.
between the fault current and negative-sequence voltage at the
The proposed scheme and chosen prior-art schemes are
relay point.
implemented in “relay” using FORTRAN language. In PSCAD,
3) Phase-to-phase- to-ground fault
the simulation waveforms can be displayed and corresponding
Taking a BCG fault as an example, the voltages of phase B
data can be exported. According to the simulation results below,
and phase C at the relay point are expressed:
the performance of the proposed scheme is evaluated.
U Mb = ( I Mb + 3KI M 0 )  xZ L1 + U fb (43)
A. Different Fault Locations
U Mc = ( I Mc + 3KI M 0 )  xZ L1 + U fc (44) Assume that phase A-to-ground faults occur at different fault
Subtracting (44) from (43), the conventional formula of locations (20km, 60km, 100km, 140km and 180km from bus M)
measured impedance can be obtained with a fault resistance of 5Ω. Since MMC-HVDC station can
operate as a rectifier or inverter station, the simulation results of
U Mb − U Mc I fb − I fc
Zm = = xZ L1 + Rf (45) rectifier and inverter modes for MMC-HVDC station are both
I Mb − I Mc I Mb − I Mc shown in Table I and Fig. 10. In Table I and Fig. 10, xZL1 is line
Thus, impedance from the relay point to the fault point, Zpro represents
the line fault impedance calculated by the proposed scheme (eq.
 I − I Mc1 I Mb2 − I Mc2 
I f = ( I fb − I fc ) =  Mb1 +  21), and Zconv represents the line fault impedance calculated by
 C1 C2  the conventional scheme that regards measured impedance as
(46) line fault impedance.
 I Ma1 I Ma2  
=  − + + TABLE I
 C1 C2  2 SIMULATION RESULTS FOR DIFFERENT FAULT LOCATIONS UNDER PHASE
A-TO-GROUND FAULT
As explained in [25], I f can be obtained only when xZL1/Ω Zconv/Ω Zpro/Ω
Operation
premise 1 and premise 2 are both satisfied. However, premise 1 mode XRL1 xXL1 Rconv Xconv Rpro Xpro
is not true in the presence of MMC-HVDC stations, which has
0.37 5.26 7.38 8.84 0.37 5.28
been expounded in subsection III.B. As a result, (46) cannot be
used to calculate fault distance in the case of an MMC-HVDC 1.10 15.78 9.67 20.82 1.10 15.78
Rectifier
station connecting bus M. 1.84 26.3 13.01 33.97 1.84 26.38
mode
To solve this issue, a new formula for measured impedance 2.57 36.82 18.9 49.98 2.59 36.98
is developed by adding (43) to (44)[29]: 3.31 47.34 33.98 79.0 3.33 47.60
I fb + I fc
Z m = xZ L1 + Rf (47)
0.37 5.26 7.88 4.51 0.37 5.27
I Mb +I Mc +6 KI M 0 1.10 15.78 10.29 14.36 1.10 15.79
Inverter
Thus, 1.84 26.3 13.81 23.88 1.84 26.35
mode
I f = ( I fb +I fc ) =I f 0  I M 0 (48) 2.57 36.82 19.68 32.55 2.59 37.0
3.31 47.34 33.53 38.32 3.33 47.68
As mentioned earlier, I f is expressed as  ( I fb − I fc ) for
the conventional scheme, whereas I f is expressed as As shown in Table I and Fig. 10, there is a significant
 ( I fb +I fc ) in the case of MMC-HVDC station connecting difference between the calculated line fault impedances and
their actual values for the conventional scheme, causing
bus M. Accordingly, the expression of the measured impedance
distance relay to operate incorrectly. However, irrespective of
is also changed, which is different from the expression used by
operation mode and fault location, the line fault impedances
the conventional relay. The measured voltage and measured
calculated by the proposed scheme are very close to their actual
current are respectively expressed as (U Mb +U Mc ) and values. This indicates that the proposed scheme provides
( I Mb +I Mc +6 KI M 0 ) . The measured impedance is the ratio of satisfactory robustness to fault location and operation mode of
MMC-HVDC station. The proposed scheme shows a better
the measured voltage over the measured current.
performance than the conventional scheme.
IV. PERFORMANCE EVALUATION
The performance of the proposed distance relaying scheme is

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
9

100 inverter modes both enter into operation zone within the first
80 cycle after fault inception. As a result, the distance relay
xZL1 operates to clear internal fault. As seen from Fig. 11, when
60
conventional scheme is adopted, xconv fails to enter into
reactance/Ω

Zpro (Rectifier)
40 Zpro (Inverter) operation zone. The faults are misidentified as external faults,
20 Zconv (Rectifier) causing distance relay to refuse to operate. According to
Zconv (Inverter)
simulation results in Table II and Fig. 9, the proposed scheme is
0
superior to the conventional scheme.
-20 Owing to the transient process caused by power system fault
0 20 40 60 80 100 120
resistance/Ω and discrete Fourier transform, distance relay may incur
transient overreach issue. To solve this issue, two effective
Fig. 10. Steady-state impedance loci for different fault locations under phase
B-to-phase C-to-ground faults. solutions were presented. In [11], equation (49) is used as a
necessary condition of tripping distance relay to avoid transient
B. Different Fault Resistances
overreach issue.
To evaluate the immunity of the proposed scheme against xk − xk −1   (49)
fault resistance, suppose that phase A-to-ground faults occurs at
100km from bus M with different fault resistances that range where xk and xk-1 are two consecutively calculated fault distance
from 5Ω to 200Ω. The calculated fault distances by values. ε is a small threshold.
conventional and proposed schemes are shown in Table II. As In [25] and [27], to avoid the transient overreach problem, if
seen from Table II, due to the existence of fault resistance, the and only if the criterion for an internal fault is always satisfied
fault distances calculated by the conventional scheme deviate during a continuous period of time, the fault is identified as an
from the actual fault distances. The greater the fault resistance, internal fault.
500
the greater the error. This is because the conventional method 450
directly takes the measured impedance Zm as the line fault
xpro (Rectifier)
impedance xZL1 to calculate the fault distance. The error caused
fault distance/km

350 xpro (Inverter)


by fault resistance between Zm and xZL1 is neglected. Based on xconv (Rectifier) Operation
zone
(10), in general, the larger the fault resistance value is, the 250 xconv (Inverter)
larger the additional impedance is. In contrast, even though 180
fault resistance varies over a wide range, the fault distances
100
calculated by the proposed scheme are approximate to the 50
actual fault distances. From the derivation process of fault 0
distance, the adverse effect of fault resistance is eliminated, and 1.5 1.6 1.7 1.8 1.9 2
time/s
thereby the fault distance calculated by (14) is unaffected by Fig. 11. Simulation results under phase A-to-ground faults occurring at 100km
fault resistance. The proposed scheme shows a superior from bus M with 25Ω fault resistance.
immunity against fault resistance under rectifier mode as well
C. Performance Comparison with a Novel Scheme Under
as inverter mode.
Various Types of Asymmetrical Faults
TABLE II To show the superiority of the proposed scheme, the
SIMULATION RESULTS UNDER DIFFERENT FAULT RESISTANCES proposed scheme is compared with a novel scheme that was
The proposed The conventional recently proposed by reference [25] in this subsection. A series
Fault scheme scheme of simulations under different asymmetrical faults with a fault
Operation
resistance Fault Fault
mode Error Error resistance of 15Ω and operation modes are carried out, and
(Ω) distance distance
(%) (%)
(km) (km) simulation results are shown in Table III. The actual fault
5 100.3 0.3 138.0 38.0 distance is 100km.
TABLE III
Rectifier 25 100.8 0.8 427.2 327.2
SIMULATION RESULTS FOR PROPOSED SCHEME AND NOVEL SCHEME IN [25]
mode 100 96.9 -3.1 2401.5 2301.5 UNDER DIFFERENT ASYMMETRICAL FAULTS
200 98.2 -1.8 1581.6 1481.6 Novel scheme in The proposed scheme
[25] in this paper
5 100.2 0.2 104.7 4.7 Operation Fault
Fault Fault
mode type Error Error
25 100.5 0.5 213.4 113.4 distance distance
Inverter (%) (%)
(km) (km)
mode 100 100.9 0.9 525.2 425.2 AG 592.3 492.3 100.5 0.5
200 101.2 1.2 708.5 608.5 Rectifier
BC 491.4 391.4 96.9 -3.1
mode
BCG 285.5 185.5 100.3 0.3
Fig. 11 shows the simulation results under phase AG 117.1 17.1 100.4 0.4
A-to-ground faults occurring at 100km from bus M with a fault Inverter
BC 430.6 330.6 103.0 3.0
resistance of 25Ω. When the faults occur at t=1.5s, the fault mode
distances calculated by the proposed scheme under rectifier and BCG 517.6 417.6 100.3 0.3

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
10

180
Rf =1Ω
The novel scheme has superior performance for transmission Rf =10Ω
150
lines connected to conventional synchronous source at both Rf =20Ω
External fault
Rf =30Ω
ends, as verified in reference [25]. However, integration of

phase angle/degree
120
MMC-HVDC station seriously deteriorates the performance of
90
the novel scheme presented by [25]. As observed from Table III,
the fault distance calculated by the novel scheme deviates 60
significantly from the actual fault distance in most cases, Internal fault
causing maloperation of distance relay. By comparison, the 30

proposed scheme of this paper can accurately calculate faut 1.75 1.8 1.85 1.9 1.95 2 2.05 2.1 2.15
time/s
distance in the case of integration of MMC-HVDC station. The
Fig. 12. Simulation results of memory polarization scheme.
maximum absolute error is within 3.1%. As shown in Table III, 180
operation mode and fault type have great influence on 160
calculation results of the novel scheme; however, they have

fault distance/km
little influence on the proposed scheme. According to 120
Rf =1Ω
simulation results in Table III, the proposed scheme is clearly Rf =10Ω
80 Rf =20Ω
superior to the novel scheme. Rf =30Ω
D. Performance Comparison with the Memory Polarization 40
X: 1.955
Scheme Y: 1.029
0
Memory polarization scheme uses the pre-fault voltage for 1.75 1.8 1.85 1.9 1.95 2 2.05 2.1 2.15
polarization. Considering a BC fault as an example, the time/s
operating and polarizing signals are expressed as follows: Fig. 13. Simulation results of the proposed protection scheme.
SOP = ( I Mb − I Mc ) Z set − (U Mb − U Mc ) E. Performance Evaluation Under Different System
(50)
S POL = U Mb
[0]
− U Mc
[0] Impedances
[0] [0] To evaluate the robustness of the proposed scheme against
where U Mb and U M c are memory voltages, i.e., pre-fault variation of system impedance, several simulation tests under
voltages. different system impedances are implemented. The simulation
The tripping characteristic for a distance relay with pre-fault results are shown in Fig. 14. The system impedance parameter
voltage polarization can be expressed by the following presented in section II is original system impedance, i.e., 100%
equation. system impedance.
 S  In the simulations, phase-A-to-ground faults occur at 100km
−90  arg  OP   90 (51) from bus M with a fault resistance of 10Ω. As observed from
 S POL  Fig. 14, the fault distance curves under different system
Assuming that BC faults occur at 1km from bus M with impedances are almost coincident; therefore, the proposed
different fault resistance, i.e., 1, 10, 20, and 30Ω, the simulation protection scheme shows superior robustness against variation
results of memory polarization and the proposed schemes are of system impedance. It is worth noting that when the system
respectively shown in Fig. 12 and Fig. 13. The fault location is impedance is set to 400% system impedance, the short-circuit
very close to the relay point. ratio is approximately 3.0. In this case, the AC system is a weak
As shown in Fig.12, when Rf = 1 and 10Ω, the relation in power grid for the MMC-HVDC station. Simulation results
equation (51) is satisfied in steady-state. Consequently, the confirm that the proposed scheme performs well under weak
faults are correctly identified as internal faults. However, when grid condition.
Rf = 20 and 30Ω, arg(SOP/SPOL) is greater than 90°.
400
Consequently, the faults with fault resistances of 20 and 30Ω 100% system impedance
are misidentified as external faults, and distance relay fails to 200% system impedance
300
fault distance/km

operate. The performance of memory polarization scheme is 300% system impedance


400% system impedance
greatly affected by fault resistance. As shown in Fig. 13,
200
irrespective of the fault resistance, the calculated fault distances X: 1.791
are close to the actual fault distance (1km). As a result, all the Y: 100.7
100
faults are correctly identified as internal faults. The comparison
results confirm that the proposed protection scheme is superior
0
to memory polarization scheme. 1.7 1.75 1.8 1.85 1.9
time/s
Fig. 14. Simulation results under different system impedance.

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
11

F. Performance Evaluation in a Modified IEEE 39-Bus 70 69.8 -0.29 70.7 1.0 70.1 0.14
System with an MMC-HVDC System 90 91.9 2.1 91.3 1.4 91.2 1.3
To further evaluate the proposed protection scheme in a
standard test system, a modified IEEE 39-bus system with an 2) Performance evaluation during power swing
MMC-HVDC system is established. In Fig. 15, the length of To emulate the power swing, a 2Hz fluctuating component is
transmission line 1-2 is 100km. The positive- and superimposed on the power angle of source G8 at t=1s. From
zero-sequence impedances of line 1-2 are 0.076+j0.338 Ω/km Fig. 16, owing to power swing, the active power and current
and 0.284+j0.824 Ω/km, respectively. The positive- and amplitude of line 2-25 are no longer constant. Since there is no
zero-sequence capacitances of line 33-19 are 0.0086 µF/km and fault, the three-phase currents are symmetrical.
0.0061 µF/km, respectively. Other parameters of IEEE 39-bus
system can be found in [32]-[33]. Relay R1 is taken as an

active power / MW
160
example to evaluate the performance of the proposed scheme. 140
G10 120
37
2 30 G8
R2 100

80
1

three-phase currents / kA
25 26 29
R1 18 28 0.5
17
1 27
0
3
MMC-HVDC -0.5
system 16 38
15
4 -1
1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3
39 21
14 G9 time/s
12 Fig. 16. Active power and three-phase currents of line 2-25 during power
24 22 swing.
9
G1 5

8 11
19 To evaluate robustness of the proposed scheme against
13 35
7
power swing under asymmetrical faults, a BC fault occurs with
G6
a fault resistance of 10Ω at t=2s during power swing. The fault
6 20 23
10 location is 50km from bus 1. The simulation results are shown
in Fig. 17. As shown in Fig. 17, regardless of
negative-sequence impedance shaping scheme or
31 32 34 33 36
negative-sequence voltage-based scheme, the estimated fault
G3 G5 G4
G2 G7 distances are both close to the actual fault distance (50km) in
Fig. 15. A modified IEEE 39-bus system with an MMC-HVDC system. steady-state. As observed from Fig. 17, the estimated fault
1) Performance evaluation under different fault locations distance of negative-sequence impedance shaping scheme has a
and fault types larger fluctuation than that of negative-sequence voltage-based
Assuming that three types of asymmetrical faults occur at scheme. Furthermore, transient process of negative-sequence
different fault locations of line 1-2, the simulation results are voltage-based scheme is much shorter than that of
shown in Table IV. The fault locations are 30, 50, 70 and 90 km negative-sequence impedance shaping scheme.
from bus 1. The MMC-HVDC station connecting bus 1 In conclusion, two schemes can achieve accurate fault
operates in inverter mode. In Table IV, negative-sequence location and are robust to power swing. Compared with
voltage-based scheme is adopted under BC faults. negative-sequence impedance shaping scheme,
As observed from Table IV, irrespective of fault location and negative-sequence voltage-based scheme offers superior
fault type, the calculated fault distance is always close to actual steady-state and transient performance.
fault distance. The simulation results confirm that the proposed
protection scheme performs well under different fault locations 200
fault distance/km

60
and fault types in a modified IEEE 39-bus system with an X: 2.615
Y: 50.17
negative-sequence impedance
50
MMC-HVDC system. 150 40
shaping scheme
negative-sequence voltage-based
fault distance/km

TABLE IV 2.5 2.6 2.7 2.8 scheme


SIMULATION RESULTS UNDER DIFFERENT FAULT LOCATIONS AND FAULT Transient process of negative-
time/s

RESISTANCES IN THE MODIFIED IEEE 39-BUS SYSTEM 100 sequence impedance shaping
scheme
AG BC BCG
Fault 50
Fault Fault Fault
locati Error Error Error
distance distance distance
on (%) (%) (%)
(km) (km) (km)
(km) 0
2 2.2 2.4 2.6 2.8 3
30 30.1 0.33 29.5 -1.67 30.1 0.33
time/s
50 49.8 -0.4 50.2 0.4 49.9 -0.2

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
12

Fig. 17. Simulation results of the proposed scheme when a BC fault occurs this paper presents a new distance relaying scheme that can
during power swing.
calculate fault distance for transmission lines connected to
MMC-HVDC stations. Two equivalent calculation methods of
V. DISCUSSION
fault distance are presented from mathematical perspective and
As more and more MMC-HVDC projects are put into use, it geometrical relationship of impedances, respectively. The
is necessary to study the effects of MMC-HVDC stations on performances of the proposed scheme are evaluated in
distance protection and propose a solution. Considering the simulation cases under different conditions. The main
unique fault behaviors of MMC-HVDC stations, this paper conclusions are summarized below:
presents a new zone I distance relaying scheme that can 1) Compared with synchronous source, the integration of
accurately calculate fault distance in the case of integration of MMC-HVDC station further aggravates the adverse effect of
MMC-HVDC system. The advantages of the proposed scheme fault resistance on distance relay on MMC-side, especially for
and main contributions of this paper are as follows: phase distance relay; however, it mitigates the adverse effect of
1) The effects of an MMC-HVDC station on ground and fault resistance on distance relay on grid-side.
phase distance relays are investigated and illustrated. 2) The proposed scheme shows much better performance
2) The two calculation formulas of fault distance are derived than the conventional scheme and a novel scheme recently
from mathematical perspective and geometrical proposed by [25].
relationship of impedances, respectively. Moreover, the 3) The proposed scheme provides satisfactory tolerance
two proposed calculation methods proved to be equivalent.
against fault resistance and good robustness to fault location.
3) The main reasons that the conventional method of solving
Moreover, it operates well under various types of asymmetrical
I f in [25] is not applicable to the lines connected to
faults, irrespective of rectifier mode or inverter mode.
MMC-HVDC stations are analyzed and clarified.
4) Considering the unique fault characteristics of REFERENCES
MMC-HVDC stations, two schemes of solving I f under
[1] T. H. Nguyen, K. A. Hosani, and M. S. El Moursi, “Alternating
phase-to-phase faults are provided. Compared with submodule configuration based MMCs with carrier-phase-shift
negative-sequence impedance shaping scheme, modulation in HVdc systems for DC-fault ride-through capability,” IEEE
Trans. Ind. Informat., vol. 15, no. 9, pp. 5214–5224, Sep. 2019.
negative-sequence voltage-based scheme has three [2] J. Lyu, X. Cai, and M. Molinas, “Optimal design of controller parameters
advantages: (1) better steady-state and transient for improving the stability of MMC-HVDC for wind farm integration,”
performance; (2) without the requirement of upgrading the IEEE J. Emerging Sel. Topics Power Electron., vol. 6, no. 1, pp. 40–53,
software of MMC; (3) lower overcurrent risk. Mar. 2018.
[3] Y. Liang, J. Liu, T. Zhang, and Q. Yang, “Arm current control strategy for
5) Simulation results confirm that the proposed protection MMC-HVDC under unbalanced conditions,” IEEE Trans. Power Del.,
scheme is applicable to the lines connected to vol. 32, no. 1, pp. 125–134, Feb. 2017.
MMC-HVDC stations. Compared with the conventional [4] S. P. Teeuwsen, “Modeling the Trans Bay Cable project as voltage
distance protection, memory polarization scheme, and the sourced converter with modular multilevel converter design,” in Proc.
IEEE Power Energy Soc. Gen. Meet., Detroit, MI, USA, 2011, pp. 1–8.
scheme in [25], the proposed scheme offers superior [5] A. Stepanov, H. Saad, U. Karaagac, and J. Mahseredjian, “Initialization
performance. The proposed scheme shows excellent of modular multilevel converter models for the simulation of
robustness against fault resistance, and perform well under electromagnetic transients,” IEEE Trans. Power Del., vol. 34, no. 1, pp.
various conditions, including different fault locations, 290–300, Feb. 2019.
[6] S. M. Hashemi, M. Sanaye-Pasand and M. Sanaye-Pasand, “Fault
different types of asymmetrical faults, different system detection during power swings using the properties of fundamental
impedances, and power swing. frequency phasors,” IEEE Trans. Smart Grid, vol. 10, no. 2, pp.
Although this study has revealed the effects of MMC-HVDC 1385–1394, Mar. 2019.
stations on distance relay and presented a zone I distance [7] X. Jin, R. Gokaraju, R. Wierckx and O. Nayak, “High speed digital
distance relaying scheme using FPGA and IEC 61850,” IEEE Trans.
relaying scheme of lines connected to MMC-HVDC stations, Smart Grid, vol. 9, no. 5, pp. 4383–4393, Sep. 2018.
there are still some unsolved issues: [8] J. H. Hong, R. F. Nuqui, A. Kondabathini, D. Ishchenko, and A. Martin,
1) There are two wiring modes on the secondary side of “Cyber attack resilient distance protection and circuit breaker control for
digital substations,” IEEE Trans. Ind. Informat., vol. 15, no. 7, pp.
transformer, i.e., wye connection with high resistance at 4332–4341, Jul. 2019.
the neutral point (Luxi back-to-back HVDC project [9] Z. Xu, S. Jiang, Q. Yang and T. Bi, “Ground distance relaying algorithm
[34]-[35]) and delta connection (Trans Bay Cable project for high resistance fault,” IET Gen., Transm. Distrib., vol. 4, no. 1, pp.
[4]). For the first connection mode, zero-sequence current 27-35, Jan. 2010.
[10] Z. Xu, S. Jiang, and L. Ran, “Phase distance relaying algorithm for
is not generated in the case of ground faults. As a result, the unbalanced inter-phase faults,” IET Gen. Transm. Distrib., vol. 4, no. 12,
scheme of solving I f under ground faults cannot be pp. 1326–1333, Dec. 2010.
[11] Z. Xu, G. Xu, L. Ran, S. Yu, and Q. Yang, “A new fault-impedance
used.
algorithm for distance relaying on a transmission line,” IEEE Trans.
2) When MMC-HVDC stations are connected to transmission Power Del., vol. 25, no. 3, pp. 1384–1392, Jul. 2010.
lines, the solution to accurately calculate the fault distance [12] J. Ma, W. Ma, Y. Qiu, and J. Thorp, “An adaptive distance protection
for symmetrical faults has not been presented yet. scheme based on the voltage drop equation,” IEEE Trans. Power Del., vol.
30, no. 4, pp. 1931–1940, Aug. 2015.
[13] J. Ma, X. Xiang, P. Li, Z. Deng and J. S. Thorp, “Adaptive distance
VI. CONCLUSION protection scheme with quadrilateral characteristic for extremely
Considering the exclusive fault characteristics of high-voltage/ultra-high-voltage transmission line,” IET Gen., Transm.
Distrib., vol. 11, no. 7, pp. 1624-1633, Jun. 2017.
MMC-HVDC station and the adverse effect of fault resistance,

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.3030332, IEEE
Transactions on Power Delivery
13

[14] S. Paladhi and A. K. Pradhan, “Adaptive zone-1 setting following [30] A. Banaiemoqadam, A. Hooshyar, and M. A. Azzouz, “A control-based
structural and operational changes in power system,” IEEE Trans. Power solution for distance protection of lines connected to converter-interfaced
Del., vol. 33, no. 2, pp. 560–569, Apr. 2018. sources during asymmetrical faults,” IEEE Trans. Power Del., vol. 35, no.
[15] V. H. Makwana and B. R. Bhalja, “A new digital distance relaying 3, pp. 1455–1466, Jun. 2020.
scheme for compensation of high-resistance faults on transmission line,” [31] S. Paladhi and A. K. Pradhan, “Adaptive distance protection for lines
IEEE Trans. Power Del., vol. 27, no. 4, pp. 2133–2140, Oct. 2012. connecting converter-interfaced renewable plants,” IEEE J. Emerg. Sel.
[16] R. C. dos Santos and E. C. Senger, “Transmission lines distance Topics Power Elect., to be published.
protection using artificial neural networks,” Int. J. Elect. Power Energy [32] I. Hiskens, “IEEE PES task force on benchmark systems for stability
Syst., vol. 33, pp.721-730, Feb. 2011. controls,” Tech. Rep., November 2013, [Online]. Available:
[17] Ch. D. Prasad, and P. K. Nayak, “Performance assessment of http://www.sel.eesc.usp.br/ieee/
swarm-assisted mean error estimation-based fault detection technique for [33] Manitoba Hydro International Ltd., “IEEE 39 Bus System,” ieee 39 bus
transmission line protection,” Computers and Electrical Engineering, vol. technical note, May. 2018, [Online]. Available:
71, pp.115-128, Aug. 2018. https://hvdc.ca/knowledge-base/read,article/28/ieee-39-bus-system/v:
[18] Y. Liang, W. Li, Z. Lu, G. Xu and C. Wang, “A new distance protection [34] W. Huang, Y. Lu, X. Li, Y. Huang, S. Xu, M. Li, and T. Liu, “A
scheme based on improved virtual measured voltage,” IEEE Trans. calculation method for maximum steady-state loss of VSC-HVDC
Power Del., vol. 35, no. 2, pp. 774-786, Apr. 2020. grounding resistor in Luxi back-back HVDC interconnector,” in 12th IET
[19] Y. Chen, M. Wen, X. Yin, Y. Cai, and J. Zheng, “Distance protection for International Conference on AC and DC Power Transmission (ACDC
transmission lines of DFIG-based wind power integration system,” Int. J. 2016), Beijing, China, May, 2016, pp. 1-5.
Elect. Power Energy Syst., vol. 100, pp.438-448, Mar. 2018. [35] X. Wang, W. Lin, L. Xu, and J. Wen, “Enhanced independent pole control
[20] A. Ghorbani, H. Mehrjerdi and N. A. Al-Emadi, “Distance-differential of hybrid MMC-HVdc system,” IEEE Trans. Power Del., vol. 33, no. 2,
protection of transmission lines connected to wind farms,” Int. J. Elect. pp. 861–872, Apr. 2018.
Power Energy Syst., vol. 89, pp.11-18, Jan. 2017.
[21] M. M. Alam, H. Leite, J. Liang, and A. D. S. Carvalho, “Effects of VSC
based HVdc system on distance protection of transmission lines,” Int. J. Yingyu Liang (M’19) received the B.S. degree from
Elect. Power Energy Syst., vol. 92, pp. 245–260, Nov. 2017. Northeast Electric Power University, Jilin, China, and the
[22] M. M. Alam, H. Leite, N. Silva, and A. D. S. Carvalho, “Performance Ph.D. degree in power system and its automation from
evaluation of distance protection of transmission lines connected with North China Electric Power University, Beijing, China, in
VSC-HVdc system using closed-loop test in RTDS,” Electric Power Syst. 2016.
Res., vol. 152, pp. 168–183, Nov. 2017. He is currently an associate professor of China University
[23] L. He, C.-C. Liu, A. Pitto, and D. Cirio, “Distance protection of AC grid of Mining and Technology(Beijing), Beijing, China. His
with HVDC-connected offshore wind generators,” IEEE Trans. Power research interests include power system protection and
Del., vol. 29, no. 2, pp. 493–501, Apr. 2014. control of renewable energy systems and VSC-HVDC.
[24] M. Zolfaghari, R. M. Chabanlo, M. Abedi, and M. Shahidehpour, “A
robust distance protection approach for bulk AC power system
considering the effects of HVDC interfaced offshore wind units,” IEEE Wulin Li was born in Shanxi Province, China. He received
Systems Journal, vol. 12, no. 4, pp. 3786 -3795, Dec 2018. the B.S. degree from Datong University, Datong, China,
[25] Y. Liang, Z. Lu, W. Li, W. Zha and Y. Huo, “A novel fault impedance in 2017, and is currently pursuing the M.Sc. degree in
calculation method for distance protection against fault resistance,” IEEE electrical engineering at China university of mining and
Trans. Power Del., vol. 35, no. 1, pp. 396-407, Feb. 2020. technology(Beijing), Beijing, China.
[26] M. Saeedifard and R. Iravani, “Dynamic performance of a modular His research interests include power system protection
multilevel back-to-back HVDC system,” IEEE Trans. Power Del., vol. 25, and control of renewable energy systems.
no. 4, pp. 2903–2912, Oct. 2010.
[27] J. Ma, X. Yan, B. Fan, C. Liu and J. S. Thorp, “A novel line protection
scheme for a single phase-to-ground fault based on voltage phase Yaotong Huo was born in Jilin Province, China. She
comparison,” IEEE Trans. Power Del., vol. 31, no. 5, pp. 2018-2027, Oct. received the B.S. degree from China University of
2016. Mining and Technology(Beijing), Beijing, China, in
[28] Y. Liang, W. Li, and W. Zha, “Adaptive mho characteristic-based 2018, and is currently pursuing the M.Sc. degree in
distance protection for lines emanating from photovoltaic power plants electrical engineering at China University of Mining and
under unbalanced faults,” IEEE Syst. Journal, to be published. Technology(Beijing), Beijing, China.
[29] A. Hooshyar, M. A. Azzouz, and E. F. El-Saadany, “Distance protection Her research interests include HVDC and power system
of lines emanating from full-scale converter-interfaced renewable energy protection.
power Plants—Part II: solution description and evaluation,” IEEE Trans.
Power Del., vol. 30, no. 4, pp. 1781–1791, Aug. 2015.

0885-8977 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 29,2020 at 00:26:56 UTC from IEEE Xplore. Restrictions apply.

You might also like