Professional Documents
Culture Documents
,(((
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 2
A. Normal Condition
The normal condition of transmission line is shown in Fig. 2, (a)
im.2(t) and in.2(t) are secondary currents sample data of current Δin.2 (t )
transformer. im.1(t) and in.1(t) are primary currents sample data of
current transformer.
im.2 (t ) in.2 (t )
Δim.2 (t )
im.1 (t ) in.1 (t )
,(((
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 3
of plane ᇞim.1(t)-ᇞin.1(t).ᇞim.2(t) and ᇞin.2(t) are in zone II or IV Boundaries of three zones are
of plane ᇞim.2(t)-ᇞin.2(t). Y = −1.2X + 7 (10)
D. Faults of single source system − X = 0.05Y + 1 (11)
For single source system faults (Fig. 6(a)), the fault part is
lts
by satu
au
For internal faults of single source system, ᇞin.1(t)=0 and ex r at
f
al
t er i o n
rn
na ca
l f us
te
ᇞin.2(t)=0. ᇞim.1(t) and ᇞim.2(t) are in horizontal axis of plane au ed
In
lts
im.2 (t ) in.2 (t )
CT
lts
by satu
au
im.1 (t ) in.1 (t ) ex r at i
f
t er o n
al
na ca
rn
l f us
te
au ed
In
lts
(a)
Δim.2 (t ) (a)
Δim.1 (t )
lts
ter on
au
na ca
f
l f us
al
au ed
rn
lts
te
(b)
In
Fig. 6. (a) The internal faults network of single source system and (b) its fault
part.
,(((
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 4
kA
transmission lines are determined using RTDS simulation 1000
environment.
500
-50 0
A
-100 -50
-20 -10 0 10 20 30 40 50 60 70 80
-100
ms -20 0 20 40 60 80
MB┦䓝ὶ
100
Phase-B ms
MB┦䓝ὶ
50 100
50
Phase-B
0
A
0
A
-50
-50
-100
-20 -10 0 10 20 30 40 50 60 70 80 -100
ms -20 0 20 40 60 80
MC┦䓝ὶ
100 ms
Phase-C
MC┦䓝ὶ
50 100
50
Phase-C
0
A
0
A
-50
-50
-100
-20 -10 0 10 20 30 40 50 60 70 80 -100
ms -20 0 20 40 60 80
ms
(a) M side
(a) M side
100
┦䓝ὶ
N A
50
100
50
NA┦䓝ὶ
0
A
0
A
-50
-50
-100
-20 -10 0 10 20 30 40 50 60 70 80 -100
-20 0 20 40 60 80
ms ms
100
50
┦䓝ὶ
N B
100
50
N B┦䓝ὶ
0 0
A
A
-50 -50
-100
-100 -20 0 20 40 60 80
-20 -10 0 10 20 30 40 50 60 70 80 ms
100
ms
┦䓝ὶ
N C
100
50
N C┦䓝ὶ
50
0
A
0
A
-50
-50
-100
-100 -20 0 20 40 60 80
-20 -10 0 10 20 30 40 50 60 70 80 ms
ms
(b) N side
(b) N side
Fig. 13. Currents of (a) M side and (b) N side when three-phase-short fault in
Fig. 11. Currents of (a) M side and (b) N side when three-phase-short fault in
F1.
F2.
The current transformer saturation identification results are
The current transformer saturation identification results are
shown in Fig.14. It can be seen from it that (X, Y) of three
shown in Fig.12. It can be seen from it that (X, Y) of three
phases current transformers increase from zone II to zone I. It
phases current transformers increase from zone II to zone III. It
shows the fault is an internal fault. Current differential
shows current transformer is saturation caused by external faults.
The identification time of three phases current transformers are protections of transmission line are opened.
,(((
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 5
ˈ
to detect current transformer saturation,” IET Generation Transmission
2500
┦椙ᖹ㠃⚦
A
and Distribution, vol.9, no.12, pp.1430-1438, 2015.
┦椙ᖹ㠃⚦
B
┦椙ᖹ㠃⚦
C [5] Esmail Ehab M, Elkalashy Nagy, Kawady Tamer A, et al, “ Detection of
2000 partial saturation and waveform compensation of current transformers,”
IEEE Transactions on Power Delivery, vol.30, no.3, pp. 1620-1622, Jul.
2015.
1500
[6] Hooshyar Ali, Sanaye-Pasand Majid, El-Saadany Ehab F, “CT saturation
detection based on wave shape properties of current difference
kA
,(((
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 6
Recommended Revisions:
Reviewer 1:
Comments: The paper suggests a method to determine a CT saturation during an external fault as comparing
two ends CT sampling data, which is a good subject. However, the following questions are needed to clarify:
1. How to derive the equations (10) & (11)?
In this paper,
Eq 10: Y = −1.2X + 7
Eq 11: − X = 0.05Y + 1
They are boundaries of three zones (external fault, internal fault and CT saturation zone )
In Eq 10, when X=0, Y = 7kA . The setting value is to identify faults of single source system. For faults of
single source system shown in figure 6, suppose ᇞim.1=Imsin(Ȧt).
T/ 2 2I m § ωT · 4 I m 4 I m N
Σ Δim.1 = 2 ³ I m sin(ωt ) = [cos ( 0 ) − cos ¨ ¸] = =
0 ω © 2 ¹ ω 2π
In Eq 11, when Y=0, X = −1kA and it is maximum value of zero drift current.
3. Can this method handle the transformer inrush (typically 100 ms) or remote faults with large X/R
ratios that cleared slowly?
This method is used for transmission line. It is not impacted by transformer inrush. It also can be used for
transformer, because the time of identifying CT saturation is no more than 20ms, it is not impacted by
transformer inrush (typically 100 ms).
For remote faults with large X/R ratios, the current is on Y axis of figure 9. The setting value of equations
(10) can ensure clearing them.
4. Too many typos such as the current ø2' in equation (2), many places of "Date" vs "Data", "from" vs
"form", It needs to clean up.
In revised paper, typos are cleaned up.
Thanks reviewer and the suggestion of this paper.
,(((