Professional Documents
Culture Documents
8, AUGUST 2020
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
XIAO AND PENG: NOVEL FAULT RIDE-THROUGH STRATEGY BASED ON CAPACITOR ENERGY STORAGE INSIDE MMC 7961
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
7962 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 35, NO. 8, AUGUST 2020
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
XIAO AND PENG: NOVEL FAULT RIDE-THROUGH STRATEGY BASED ON CAPACITOR ENERGY STORAGE INSIDE MMC 7963
⎧
⎪ −kpE ·t/2
⎪ 2ΔP̃ / 4k − k 2 · e · sin 4k − k 2 · t/2 , 2
kiE > kpE /4
⎨ dc iE pE iE pE
−kpE ·t/2
ΔẼ(t) = ΔP̃dc · t · e , 2
kiE = kpE /4 (7)
⎪
⎪ √ 2 √ 2
⎩ ΔP̃ / k 2 − 4k −(kpE − kpE −4kiE )·t/2
− e−(kpE + kpE −4kiE )·t/2 , kiE < kpE
iE · e
2
dc pE /4
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
7964 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 35, NO. 8, AUGUST 2020
=
⎪ ·ΔẼ (i − 1)Tf /2 /6, k is odd (10) equally by N SMs in one arm. Combining (13) with (14), the
⎪
⎩ k i
energy deviation ΔẼFB_arm derived in (10) must satisfy
i=1 (−1) · ΔẼ (i − 1)Tf /2 /6, k is even.
Δ
ΔẼFB_arm ≥ − 1 − M 2 ẼFB_arm = ΔẼlim (15)
Besides, MMC inner CES deviation nadir ΔẼ min can be
derived with letting the derivative of (7) equal to zero. First, where M is the ratio of rated ac voltage and dc voltage, given as
the corresponding moment tz can be solved out. M = 2/3Vs (Vdc /2). ẼFB_arm = EFB_arm /Prate and ΔẼlim
Substituting (11), shown at the bottom of this page, into (7), is defined as the lowest limit.
the CES deviation nadir ΔẼ min can be calculated out as Fig. 5(a) presents the 3-D graph of ΔẼFB_arm and the lowest
limit ΔẼlim along with the change of parameter pair (kpE , kiE ).
ΔẼmin = ΔP̃dc / kiE · e−kpE ·tz /2 . (12)
The main parameters of MMC are listed in Table II of Section VI.
Because of only FBSMs generating the negative arm voltage The condition (15) will be satisfied when surface ΔẼFB_arm is
after dc fault, the capacitor voltages of N/2 FBSMs each arm higher than plane ΔẼlim . The data points of their intersections
must be large enough to sustain the negative-level output of are collected and then replotted in Fig. 5(b) with utilizing the
ac-side terminal voltage, which yields curve-fitting method. The blue fitting curve is the borderline
of the condition (15), and the corresponding parameter pair
−N VC_FB (t)/2 ≤ − 2/3Vs (13)
(kpE , kiE ) should meet the relationship of
where VC_FB (t) is the capacitor voltage of an FBSM, assuming 3
kiE > 0.01579kpE − 0.6089kpE
2
− 35.66kpE + 1395. (16)
that the capacitor voltages of FBSMs each arm are equal. Vs is ac
⎧
⎪
⎪ 2arctan 4kiE − kpE
2 /k
pE / 4kiE − kpE ,
2 2
kiE > kpE /4
⎨
2
tz = 2/kpE , kiE = kpE /4 (11)
⎪
⎪
⎩ ln k − k 2 − 4k 2 − 4k 2 − 4k , k 2
pE pE iE / kpE + kpE iE / kpE iE iE < kpE /4
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
XIAO AND PENG: NOVEL FAULT RIDE-THROUGH STRATEGY BASED ON CAPACITOR ENERGY STORAGE INSIDE MMC 7965
Fig. 6. (a) 3-D graph. (b) Intersecting line of tz and 40 ms. Fig. 7. (a) 3-D graph. (b) Intersecting line of Pover and 5%.
When (16) is satisfied, i.e., ΔẼFB_arm > ΔẼlim , arm volt- After MMC inner CES deviation arrives at the nadir ΔẼ min ,
ages are generated without distortion to safeguard MMC dc-side the CES becomes charged to its nominal value Ẽ MMC gradually
and ac-side terminal voltage characteristics, which is beneficial in the effect of CESDC, as depicted in Fig. 3, which is beneficial
for eliminating dc fault current and improving ac-side transient for postfault stable operation and fast recovery after dc fault
characteristics with the proposed strategy. Therefore, the condi- cleared. However, the charging power of inner CES comes from
tion (16) is the prerequisite of MMC inner CES utilization. And ac grid, so there exists an overshoot in ac-side active power. The
ΔẼlim indicates the available utilization of MMC inner CES. power overshoot P̃ over can be calculated by letting the derivative
The larger the absolute value of ΔẼ lim is, the better the ac-side of (8) equal to zero, so the corresponding moment tp can be
transient characteristics can be designed. derived
tp = 2tz . (18)
B. Universal Design of Improving Transient Characteristics
Substituting (18) into (8), P̃ over will be calculated out
When the prerequisite is satisfied, MMC internal and dc-side
characteristics will be controlled as expected. In order to improve P̃over = 1 + ΔP̃dc · 1 + e−kpE ·tp /2 . (19)
ac-side transient characteristics, universal design based on FRT-
CES strategy is proposed here to excavate the potential capability During the regulating process, the power overshoot should
of MMC inner CES to achieve short-term frequency support after be small. Otherwise, ac-side dynamic characteristics may be
dc fault. deteriorated. When P̃ over is designed to be no more than 5%,
The moment tz , zero-crossing point of P̃ ac , reflects the the 3-D graph and intersecting line are depicted in Fig. 7. When
transient response time of ac-side active power after dc fault. the boundary condition (20) is satisfied, the overshoot P̃ over will
Different from usual control strategies, the transient time tz be less than 5% so that the impact of the ac-side power overshoot
should be longer possibly here so that the transient change of on ac grid is suppressed
ac-side active power will be slower. Then, the threat of frequency 2
kiE < 0.06546kpE + 0.07044kpE − 1.169. (20)
oscillation and voltage instability caused by dc fault will be
milder for ac grid.
According to (11), the 3-D graph of tz can be plotted in From (11), (18), and (19), the power overshoot P̃ over is only
Fig. 6(a). Supposing that the acceptable transient time is longer dependent on (kpE , kiE ) as well, so the universal design of P̃ over
than two fundamental periods (40 ms) in terms of ac-grid is also applicable to other MMCs with different capacity ratings
security and stability, surface tz needs to be designed higher on the prerequisite of (16), i.e., ΔẼFB_arm > ΔẼlim .
than the plane 40 ms. Similarly, with the curve-fitting method,
the intersecting line can be obtained, as drawn in Fig. 6(b). C. Optimized Value Region
The boundary condition is derived as (17). Compared with the Summing up the value range consistent with the quantified
transient time in Table I, the transient change of ac-side active results in Figs. 5–7, an optimal region marked with underpaint-
power is attenuated a lot with the proposed strategy. Therefore, ing is determined, as depicted in Fig. 8. When the parameter
the short-term frequency support will be achieved by MMC inner pair (kpE , kiE ) locates within the optimal region, the desired
CES providing power regulation transient characteristics, i.e., ΔẼFB_arm > ΔẼlim , tz > 40 ms,
and P̃ over < 5%, are satisfied. Compared with the results in
kiE < −0.0003089kpE
3 2
+ 0.1451kpE − 24.67kpE + 1533. Table I, the transient time of ac-side active power is extended
(17) over ten times with limited overshoot.
Furthermore, if ac-side transient characteristics are required
Remarkably, the transient time tz derived in (11) is just stricter for the security and stability of ac grid system, the
dependent on the parameter pair (kpE , kiE ). On the prerequisite parameter region can be optimized again with above-mentioned
of (16), i.e., ΔẼFB_arm > ΔẼlim , the boundary condition (17) universal design. The boundary conditions of tz > 60 ms and
is applicable to other MMCs with different capacity ratings when P̃ over < 3% are also added in Fig. 8, which are marked with
the transient time is desired longer than 40 ms. Therefore, the Curve 5 and 7 , respectively. As a result, the optimized region
proposed design of transient time tz is universal. is further divided into four regions. Region a represents the
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
7966 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 35, NO. 8, AUGUST 2020
Fig. 8. Optimized value region based on the derived prerequisite and universal Fig. 9. Closed-loop eigenvalues of the small-signal state-space model with
design of ac-side transient characteristics. the change of (a) kpE and (b) kiE .
region that satisfies ΔẼFB_arm > ΔẼ lim , 40 ms < tz < 60 ms, the small-signal model according to [34]
and 3% < P̃ over < 5%, while Region d represents the region Δẋ = A(x0 , u0 )Δx + B(x0 , u0 )Δu (23)
that satisfies ΔẼFB_arm > ΔẼ lim , tz > 60 ms, and P̃ over < 3%.
Similarly, the meanings of other regions can also be known. The where Δx = [Δx1 , Δx2 , Δid , Δ(ΔE)]T , Δu = [ΔPrate , ΔPdc ,
parameters (kpE , kiE ) can be adjusted according to the desired ΔPdis ]T , and A(x0 ,u0 ) and B(x0 ,u0 ) are given as
transient characteristics. Besides, the boundary condition of ⎡ ⎤
0 0 0 −1
2ΔẼ lim equipped in MMC is also provided in Fig. 8, which is ⎢ kpE ⎥
denoted with Curve 2 . Clearly, when MMC inner CES is larger, ⎢ − 1.5V kiE
0 −1 1.5Vsd ⎥
⎢
A(x0 , u0 ) = ⎢ kiE kpA k sd ⎥
e.g., larger SM capacitance or MMC integrated with batteries, kpA +Rac kpE kpA ⎥
⎣ − 1.5Vsd Lac LiA ac
− Lac 1.5Vsd Lac ⎦
more energy can be utilized to provide short-term frequency
0 0 −1.5Vsd 0
support to ac grid. The threat of power and frequency oscillation
can be suppressed further. (24)
⎡ ⎤
When inner CES is reduced to 35 kJ/MVA (35 ms) [33], 0 0 0
the performance of the proposed strategy is also analyzed and ⎢ ⎥
⎢ 1/ (1.5Vsd ) 0 0 ⎥
evaluated. The corresponding energy lowest limit is ΔẼlim_usu , B(x0 , u0 ) = ⎢ ⎥. (25)
⎣ kpA / (1.5Vsd Lac ) 0 0 ⎦
which is depicted with Curve 3 in Fig. 8. Although MMC inner
CES is reduced, there is still an optimized region that satisfies 0 1 −1
ΔẼFB_arm > ΔẼlim_usu , tz > 60 ms, and P̃ over < 3%. And Based on (23), the closed-loop eigenvalues of the small-signal
P̃ over will be further reduced. In this case, the short-term fre- state-space model with the change of controller parameters
quency support can also be provided with the proposed strategy (kpE , kiE ) can be obtained, as shown in Fig. 9. The parameters
after the dc fault. of the active power controller are selected as kpA = Lac /τac
and kiA = Rac /τac , so the order of the small-signal model will
V. SMALL-SIGNAL STABILITY ANALYSIS be reduced to three due to zero-pole cancelation. In Fig. 9,
there are three trend lines of the closed-loop eigenvalues with
Since the parameter pair (kpE , kiE ) is adjusted based on the the change of (kpE , kiE ). When kpE is increased gradually,
desired ac-side transient characteristics, the influence of the two eigenvalues are approaching to the line with a real part of
variation of (kpE , kiE ) on the stability of the control system −500, and another one is approaching to the origin. All poles
should be carefully evaluated. will be located in the left-half s-plane, so the control system is
The postfault control loop (sw = 1) is considered here. The stable with the change of kpE . Similarly, all poles are located in
state-space model of the control system can be established the left-half s-plane with the change of kiE . Merely, one pole is
according to CESDC, active power controller, ac-side plant, the close to the origin when the value of kiE is very small, but the
plant of CES, and their input–output relationships in Fig. 2. Two control system is still stable.
state variables of them are defined as follows: Considering the finite CES inside MMC, the prerequisite
dx1 of inner CES utilization should be satisfied first. As a result,
= 0 − ΔE (21) when (kpE , kiE ) are adjusted based on the proposed quantified
dt
analysis in Section IV, the stability of the control system can be
dx2 Prare − Padj
= − id . (22) guaranteed.
dt 1.5Vsd
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
XIAO AND PENG: NOVEL FAULT RIDE-THROUGH STRATEGY BASED ON CAPACITOR ENERGY STORAGE INSIDE MMC 7967
Fig. 11. (a) DC current. (b) AC-side active power and reactive power with
conventional FRT strategy.
Fig. 12. Frequency of PCC with (a) conventional FRT strategy and (b) pro-
posed FRT-CES strategy.
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
7968 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 35, NO. 8, AUGUST 2020
Fig. 13. Simulation results of Case II: ΔẼFB_arm < ΔẼ lim .
Fig. 14. Simulation results of Case III: 2ΔẼ lim in MMC.
B. Case II: (kpE , kiE ) Locates Where ΔẼFB_arm < ΔẼ lim
Fig. 13 presents the simulation results of the proposed strategy Double CES is achieved with SM capacitance doubled here
with (kpE = 22, kiE = 5) located below the Curve 1 in Fig. 8. (C = 2.6 mF). The lowest limit of CES deviation is increased to
Similarly, dc fault occurs at t = 0.3 s. More energy is released to 2ΔẼ lim , so more energy can be utilized to provide short-term
attenuate the transient change of ac-side active power, as shown frequency support to ac grid. The parameter pair is selected as
in Fig. 13(c) and (e). However, Fig. 13(h) clearly shows that (kpE = 18, kiE = 3), and Fig. 14 presents the corresponding
the sum of FBSM capacitor voltages each arm is lower than the simulation results. Similarly, the dc fault current is eliminated
phase peak voltage Vm after dc fault, which means ΔẼFB_arm quickly, and 167 MVar of reactive power is generated to support
< ΔẼ lim . Therefore, the negative-level output capability of ac grid voltage after dc fault. Besides, the transient time tz of
FBSMs will be insufficient to synthesize the desired negative ac-side active power is extended to 258 ms, and power overshoot
arm voltages, which causes negative arm voltages flat-topped, P̃ over is limited to 1.63%, as shown in Fig. 14(e). Although more
as seen in Fig. 13(j). The distorted arm voltages cause dc energy is released to attenuate the transient change of ac-side
fault current unextinguished and ac-side currents distorted, as active power in Fig. 14(c) compared with the two cases above,
presented in Fig. 13(b) and (g). Therefore, the dc fault is not Fig. 14(h) shows that the sum of FBSM capacitor voltages each
ridden through. Notably, positive arm voltages are generated arm is still larger than phase peak voltage Vm of ac grid due
normally in Fig. 13(j). Although the sum of capacitor voltages to 2ΔẼ lim in MMC. Therefore, the waveform quality of arm
in HBSMs is also lower than Vm in Fig. 13(i), both HBSMs voltages and ac-side currents can be guaranteed, as presented in
and FBSMs can synthesize positive arm voltages together. This Fig. 14(j) and (g).
sufficiently declares that the capacitor voltages of FBSMs should The simulation results of conventional FRT strategy with
be concerned first. 2ΔẼ lim inside MMC are almost the same as those in Fig. 11
In consequence, the prerequisite ΔẼFB_arm > ΔẼ lim should (ΔẼ lim in MMC). Fig. 15 presents the frequency responses
be satisfied first, and then the improvement of ac-side transient with conventional FRT strategy and the proposed FRT-CES
characteristics can be considered. Otherwise, dc fault current strategy under the condition of 2ΔẼ lim equipped in MMC.
cannot be eliminated, and ac grid currents will be deteriorated. Clearly, the amount of stored energy has little impact on the
frequency response with conventional FRT strategy. However,
when the proposed FRT-CES strategy is applied, the frequency is
C. Case III: 2ΔẼ lim in MMC
scarcely affected by the dc fault because more energy is utilized
The performance of FRT-CES strategy with two times of to attenuate the transient change of ac-side active power. The
CES inside MMC is also investigated during dc-side PTP fault. frequency nadir is 49.4 Hz.
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
XIAO AND PENG: NOVEL FAULT RIDE-THROUGH STRATEGY BASED ON CAPACITOR ENERGY STORAGE INSIDE MMC 7969
Fig. 15 Frequency of PCC with (a) conventional FRT strategy and (b) proposed
FRT-CES strategy under 2ΔẼ lim in MMC.
Fig. 17. Frequency of PCC with the proposed strategy in Case IV.
TABLE III
SINGLE-PHASE MMC EXPERIMENTAL PARAMETERS
D. Case IV: ΔẼlim_usu in MMC
The performance of FRT-CES strategy under the condition
of the CES reduced to 35 kJ/MVA [33] is also investigated.
The corresponding SM capacitance is C = 0.57 mF, and the
controller parameters are designed as (kpE = 120, kiE = 1).
From Fig. 16, the transient time tz is 65 ms and the power over-
shoot P̃ over is limited to 0.59%, which still satisfy ΔẼFB_arm >
ΔẼlim_usu , tz > 60 ms, and P̃ over < 3%. The optimized region
in Fig. 8 is reduced along with the reduction of inner CES, and
the power overshoot is greatly reduced. Because lesser active
power is absorbed from ac grid to charge MMC inner CES, the
time to obtain ΔE = 0 again will be long. Since the prerequisite
provided in Table III. The control system is implemented with
(ΔẼFB_arm > ΔẼ lim ) has been satisfied to guarantee stable
using a TMS320F28335 DSP and an EP4CE10E22C8 FPGA.
operation, the longer recovery time will not bring negative
Active and reactive power (Pac , Qac ), CES deviation (ΔE), and
impacts.
adjusting variable (Padj ) are output by a 12-bit digital-to-analog
Compared with conventional FRT strategy, the frequency
chip MAX5742. The others are gathered by voltage or current
characteristic has also improved a lot, and the frequency nadir
probes, and all experimental waveforms are acquired by a scope
has increased from 43.5 to 48 Hz, as depicted in Fig. 17. The
recorder YOKOGAWA DL850E. Noticeably, the switch S3 is
short-term frequency support can also be provided with the
closed to emulate dc line PTP fault, and switch S2 is open
proposed strategy.
subsequently for protecting dc source.
First, the experimental results with the same parameters
VII. EXPERIMENTAL RESULTS as simulation in Case I, (kpE = 45, kiE = 45), are shown in
The proposed strategy is also experimentally validated on a Fig. 20. In normal operation, MMC delivers 550 W of active
single-phase hybrid SMs-based MMC prototype, as shown in power to ac grid. It is clear that the dc-side fault current is
Fig. 18. And its layout is depicted in Fig. 19. In order to verify eliminated immediately once dc-side PTP fault occurs. And
the universal design that is applicable to MMCs of different 137 Var of reactive power is output to support ac grid voltage.
capacity ratings, ΔẼ lim of the MMC prototype is designed same Meanwhile, MMC inner CES is utilized to attenuate the change
as three-phase MMC in simulation. Therefore, the experiments rate of ac-side active power. The transient time tz is extended
under the same controller parameters (kpE , kiE ) as Case I−III to 90 ms with power overshoot P̃ over limited to 2.14%. And the
in simulation are carried out. The experimental parameters are sum of capacitor voltages in FBSMs each arm is always larger
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
7970 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 35, NO. 8, AUGUST 2020
Fig. 20. Experimental results in Case I. Fig. 22. Experimental results in Case III.
VIII. CONCLUSION
Fig. 21. Experimental results in Case II. A novel FRT-CES has been proposed in this article. With the
proposed strategy, the clearance of dc fault current, ac-side grid
than the phase peak voltage, which indicates the prerequisite support, and stable operation of the converter (MMC) can be
ΔẼFB_arm > ΔẼ lim is satisfied. accomplished simultaneously. After dc fault, MMC is not off-
In single-phase MMC, inner CES is just the total stored energy grid only for its self-protection, but actively adjusts its operation
in the leg. There exists a second-order harmonic ripple in the to cope with the dc fault. MMC inner CES is utilized to attenuate
CES deviation ΔE as analyzed in [36] and [37], which causes the transient change of ac-side active power after dc fault, as a
a second-order harmonic (2nd ω ) component in the leg circulating result of which an additional function of the stored energy in
current icir . In the effect of CESDC, its output Padj will include MMC is developed to provide short-term frequency support to
2nd
ω component. Because Padj is utilized to regulate ac-side ac grid. Besides, the prerequisite of inner CES utilization and
∗
active power reference Pac after dc fault, the 2nd
ω component universal design of improving ac-side transient characteristics
will be introduced into Pac . Furthermore, a third-order harmonic are also proposed and quantified through mathematical analysis,
component will be introduced into ac-side current ia . However, which can not only guide the design of controller parameters
in three-phase MMC, the 2nd ω components of leg CES deviations to acquire the desired ac-side transient characteristics, but also
cancel with each other. Therefore, the total CES deviation ΔE guide the design of the CES requirement in MMC. As long
in MMC excludes harmonic components so that the proposed as the prerequisite is satisfied, the proposed universal design
strategy will not introduce harmonic components into ac-side is applicable to other MMCs with different capacity ratings.
currents in three-phase MMC, which can be verified in the Compared with conventional FRT strategy, the transient time
simulation results. of ac-side active power can be extended to tens to hundreds of
Fig. 21 presents the experimental results in Case II, milliseconds with the proposed strategy. Better ac-side transient
ΔẼFB_arm < ΔẼ lim with (kpE = 22, kiE = 5). After dc fault, characteristics can be acquired with larger CES in MMC. As a
the sum of capacitor voltages in FBSMs each arm is not sufficient result, the threat of dc fault to the security and stability of MMC
to synthesize the negative arm voltage, which causes both dc- and ac grid system will be suppressed with the proposed strategy.
side and ac-side terminal voltages distorted. As a result, dc fault
current icir cannot be extinguished, and ac-side current ia is also REFERENCES
distorted. Therefore, in order to acquire better MMC internal,
[1] S. Debnath, J. Qin, B. Bahrani, M. Saeedifard, and P. Barbosa, “Operation,
dc-side, and ac-side transient characteristics, the prerequisite control, and applications of the modular multilevel converter: A review,”
ΔẼFB_arm > ΔẼ lim should be satisfied at first. IEEE Trans. Power Electron., vol. 30, no. 1, pp. 37–53, Jan. 2015.
Fig. 22 presents the experimental results under Case III, [2] T. H. Nguyen, K. A. Hosani, M. S. E. Moursi, and F. Blaabjerg, “An
overview of modular multilevel converters in HVDC transmission systems
2ΔẼ lim in MMC with (kpE = 18, kiE = 3). Similarly, the SM with STATCOM operation during pole-to-pole DC short circuits,” IEEE
capacitance is doubled (C = 4 mF). Once PTP fault occurs, Trans. Power Electron., vol. 34, no. 5, pp. 4137–4160, May 2019.
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.
XIAO AND PENG: NOVEL FAULT RIDE-THROUGH STRATEGY BASED ON CAPACITOR ENERGY STORAGE INSIDE MMC 7971
[3] M. A. Perez, S. Bernet, J. Rodriguez, S. Kouro, and R. Lizana, “Circuit [25] D. Wu and L. Peng, “Analysis and suppressing method for the output
topologies, modeling, control schemes, and applications of modular mul- voltage harmonics of modular multilevel converter,” IEEE Trans. Power
tilevel converters,” IEEE Trans. Power Electron., vol. 30, no. 1, pp. 4–17, Electron., vol. 31, no. 7, pp. 4755–4765, Jul. 2016.
Jan. 2015. [26] C. Dong, S. Yang, H. Jia, and P. Wang, “Padé-based stability analysis for
[4] M. Priya, P. Ponnambalam, and K. Muralikumar, “Modular-multilevel a modular multilevel converter considering the time delay in the digital
converter topologies and applications – A review,” IET Power Electron., control system,” IEEE Trans. Ind. Electron., vol. 66, no. 7, pp. 5242–5253,
vol. 12, no. 2, pp. 170–183, Feb. 2019. Jul. 2019.
[5] X. Li, Q. Song, W. Liu, H. Rao, S. Xu, and L. Li, “Protection of nonperma- [27] S. Cui, S. Kim, J. Jung, and S. Sul, “A comprehensive cell capacitor energy
nent faults on DC overhead lines in MMC-based HVDC systems,” IEEE control strategy of a modular multilevel converter (MMC) without a stiff
Trans. Power Del., vol. 28, no. 1, pp. 483–490, Jan. 2013. DC bus voltage source,” in Proc. 29th Annu. IEEE Appl. Power Electron.
[6] S. Cui and S. K. Sul, “A comprehensive DC short-circuit fault ride through Conf. Expo., Mar. 2014, pp. 602–609.
strategy of hybrid modular multilevel converters (MMCs) for overhead line [28] A. E. Leon and S. J. Amodeo, “Energy balancing improvement of modular
transmission,” IEEE Trans. Power Electron., vol. 31, no. 11, pp. 7780– multilevel converters under unbalanced grid conditions,” IEEE Trans.
7796, Nov. 2016. Power Electron., vol. 32, no. 8, pp. 6628–6637, Aug. 2017.
[7] J. Dorn, H. Gambach, J. Strauss, and T. Westerweller, “Trans bay cable—A [29] D. Wu and L. Peng, “Characteristics of nearest level modulation method
breakthrough of VSC multilevel converters in HVDC transmission,” in with circulating current control for modular multilevel converter,” IET
CIGRE Colloq., San Francisco, CA, USA, Mar. 2012. Power Electron., vol. 9, no. 2, pp. 155–164, Oct. 2016.
[8] G. Tang, Z. He, H. Pang, X. Huang, and X.-P. Zhang, “Basic topology and [30] M. Saeedifard and R. Iravani, “Dynamic performance of a modular multi-
key devices of the five-terminal DC grid,” CSEE J. Power Energy Syst., level back-to-back HVDC system,” IEEE Trans. Power Del., vol. 25, no. 4,
vol. 1, no. 2, pp. 22–35, Jun. 2015. pp. 2903–2912, Oct. 2010.
[9] G. P. Adam and I. E. Davidson, “Robust and generic control of full-bridge [31] M. Guan and Z. Xu, “Modeling and control of a modular multilevel
modular multilevel converter high-voltage DC transmission systems,” converter-based HVDC system under unbalanced grid conditions,” IEEE
IEEE Trans. Power Del., vol. 30, no. 6, pp. 2468–2476, Dec. 2015. Trans. Power Electron., vol. 27, no. 12, pp. 4858–4867, Dec. 2012.
[10] W. Lin, D. Jovcic, S. Nguefeu, and H. Saad, “Full-bridge MMC converter [32] J. Lee, J. Jung, and S. Sul, “Balancing of submodule capacitor voltage
optimal design to HVDC operational requirements,” IEEE Trans. Power of hybrid modular multilevel converter (MMC) under DC bus voltage
Del., vol. 31, no. 3, pp. 1342–1350, Jun. 2016. variation of HVDC system,” IEEE Trans. Power Electron., vol. 34, no. 11,
[11] X. Yu, Y. Wei, and Q. Jiang, “STATCOM operation scheme of the CDSM- pp. 10458–10470, Nov. 2019.
MMC during a pole-to-pole DC fault,” IEEE Trans. Power Del., vol. 31, [33] Z. Xu, H. Xiao, and Z. Zhang, “Selection methods of main circuit param-
no. 3, pp. 1150–1159, Jun. 2016. eters for modular multilevel converters,” IET Renewable Power Gener.,
[12] W. Xiang, W. Lin, T. An, J. Wen, and Y. Wu, “Equivalent electromag- vol. 10, no. 6, pp. 788–797, Jul. 2016.
netic transient simulation model and fast recovery control of overhead [34] P. S. Kundur, Power System Stability and Control. New York, NY, USA:
VSC-HVDC based on SB-MMC,” IEEE Trans. Power Del., vol. 32, no. 2, McGraw-Hill, 1994.
pp. 778–788, Apr. 2017. [35] D. Zhu, S. Zhou, X. Zou, and Y. Kang, “Improved design of PLL controller
[13] R. Zeng, L. Xu, and L. Yao, “An improved modular multilevel converter for LCL-type grid-connected converter in weak grid,” IEEE Trans. Power
with DC fault blocking capability,” in Proc. IEEE PES General Meeting Electron., to be published, doi: 10.1109/TPEL.2019.2943634.
Conf. Expo., National Harbor, MD, USA, Jul. 2014, pp. 1–5. [36] S. Fan, K. Zhang, J. Xiong, and Y. Xue, “An improved control system for
[14] L. Huang et al., “The evolution and variation of sub-module topologies modular multilevel converters with new modulation strategy and voltage
with DC-fault current clearing capability in MMC-HVDC,” in Proc. IEEE balancing control,” IEEE Trans. Power Electron., vol. 30, no. 1, pp. 358–
3rd Int. Future Energy Electron. Conf., Kaohsiung, Taiwan, Jun. 2017, 371, Jan. 2015.
pp. 1938–1943. [37] G. Bergna-Diaz, J. A. Suul, and S. D’Arco, “Energy-based state-space rep-
[15] S. Cui, S. Kim, J. Jung, and S. Sul, “Principle, control and comparison of resentation of modular multilevel converters with a constant equilibrium
modular multilevel converters (MMCs) with DC short circuit fault ride- point in steady-state operation,” IEEE Trans. Power Electron., vol. 33,
through capability,” in Proc. 29th Annu. IEEE Appl. Power Electron. Conf. no. 6, pp. 4832–4851, Jun. 2018.
Expo., Mar. 2014, pp. 610–616.
[16] J. Hu, K. Xu, L. Lin, and R. Zeng, “Analysis and enhanced control
of hybrid-MMC-based HVDC systems during asymmetrical DC voltage
faults,” IEEE Trans. Power Del., vol. 32, no. 3, pp. 1394–1403, Jun. 2017.
[17] J. Qin, M. Saeedifard, A. Rockhill, and R. Zhou, “Hybrid design of modular
multilevel converters for HVDC systems based on various submodule Yuntao Xiao was born in Henan, China, in 1994.
circuits,” IEEE Trans. Power Del., vol. 30, no. 1, pp. 385–394, Feb. 2015. He received the B.Eng. degree in electrical engineer-
[18] R. Li, J. E. Fletcher, L. Xu, D. Holliday, and B. W. Williams, “A hybrid ing from the Huazhong University of Science and
modular multilevel converter with novel three-level cells for DC fault Technology (HUST), Wuhan, China, in 2016. He
blocking capability,” IEEE Trans. Power Del., vol. 30, no. 4, pp. 2017– is currently working toward the Ph.D. degree with
2026, Aug. 2015. the School of Electrical and Electronic Engineering,
[19] M. Lu, J. Hu, L. Lin, and K. Xu, “Zero DC voltage ride through of a hybrid HUST.
modular multilevel converter in HVDC systems,” IET Renewable Power His research interests include modular multilevel
Gener., vol. 11, no. 1, pp. 35–43, Nov. 2017. converter, inverters, and grid-connected converters.
[20] Z. Suo, G. Li, L. Xu, R. Li, W. Wang, and Y. Chi, “Hybrid modular
multilevel converter based multi-terminal DC/DC converter with min-
imised full-bridge submodules ratio considering DC fault isolation,” IET
Renewable Power Gener., vol. 10, no. 10, pp. 1587–1596, Nov. 2016.
[21] M. Benini, S. Canevese, D. Cirio, and A. Gatti, “Battery energy storage
systems for the provision of primary and secondary frequency regulation
in Italy,” in Proc. IEEE 16th Int. Conf. Environ. Elect. Eng., Florence, Li Peng (Member, IEEE) received the B.S., M.S.,
Italy, Jun. 2016, pp. 1–6. and Ph.D. degrees from the Huazhong University of
[22] F. M. Gonzalez-Longatt and S. M. Alhejaj, “Enabling inertial response in Science and Technology (HUST), Wuhan, China, in
utility-scale battery energy storage system,” in Proc. IEEE Innov. Smart 1989, 1992, and 2004, respectively, all in electrical
Grid Technol. Asia, Nov. 2016, pp. 605–610. engineering.
[23] Y. J. A. Zhang, C. Zhao, W. Tang, and S. H. Low, “Profit-maximizing plan- From 1992, she is with the HUST, where she is
ning and control of battery energy storage systems for primary frequency currently a Full Professor with the School of Electri-
control,” IEEE Trans. Smart Grid, vol. 9, no. 2, pp. 712–723, Mar. 2018. cal and Electronic Engineering. Her research interests
[24] X. Zhang, L. Yang, and X. Zhu, “Integrated control of photovoltaic-energy include power electronic conversion, its control and
storage system for power oscillation damping enhancement,” in Proc. applications, modular power supply and parallel con-
IEEE 8th Int. Power Electron. Motion Control Conf., Hefei, China, May trol technique, renewable energy generation, power
2016, pp. 1571–1575. quality control and MMC for HVdc applications.
Authorized licensed use limited to: KU Leuven Libraries. Downloaded on November 27,2022 at 14:22:25 UTC from IEEE Xplore. Restrictions apply.