You are on page 1of 12

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 70, NO.

5, MAY 2023 4727

Multiport Current-Limiting Hybrid DC Circuit


Breaker for MTdc Grids
Shuo Zhang , Student Member, IEEE, Guibin Zou , Member, IEEE,
Xiuyan Wei , Student Member, IEEE, Chenghan Zhou, Student Member, IEEE, and Chengquan Zhang

Abstract—The coordination configuration of current-


limiting inductors (CLIs) and hybrid dc circuit breakers
(HCBs) is currently the most commonly used fault handling
method to ensure fault ride-through of multi-terminal dc
grids after the dc-side fault occurs. However, the high cost
of HCB limits its large-scale application. In addition, the
installation of the large CLIs will adversely affect the HCB
performance, such as extending the fault current interrup-
tion time and increasing the energy dissipation pressure of Fig. 1. Topology of the typical HCB.
the arrester. To solve these problems, a multiport current-
limiting HCB (MCL–HCB) is proposed in this article. Com-
pared with the typical HCBs, the MCL–HCB can achieve full rapidly isolated to achieve the converter continuous operation
selective protection of all connected dc lines with signifi- and healthy network fault ride-through [2].
cantly reduced investment costs. Besides, it can suppress The dc circuit breaker (DCCB) can selectively isolate dc
the rising speed of the fault current by embedded CLIs,
while eliminating their negative impacts on the fault current faults with minimum impact on the healthy network. The com-
interruption. The feasibility and superiority of the proposed prehensive review of DCCB technologies has been reported
MCL–HCB are verified by simulations in the PSCAD/EMTDC in [3]. Among the currently proposed DCCBs, the hybrid dc
software and experiments in the scaled-down experimental circuit breaker (HCB) has high action speed and low power loss,
setup. Besides, the performance comparison between the which has a good prospect for applications in MTdc grids [4].
MCL–HCB and existing solutions is elaborated.
The typical HCB is composed of a load current path (LCP), a
Index Terms—Current-limiting inductor (CLI), energy dis- main breaker (MB), and a residual current breaker (RCB), as
sipation, fault ride-through, multiport current-limiting hy- illustrated in Fig. 1. The LCP consists of a load commutation
brid dc circuit breaker (MCL–HCB), multiterminal dc grid
(MTdc).
switch (LCS) and an ultrafast disconnector (UFD). The MB con-
tains hundreds of fully controlled semiconductor switches, and
parallel arresters to dissipate fault current, which is extremely
I. INTRODUCTION expensive and dominates the total cost of the HCB. Since large
number of HCBs is required to achieve full selective protection
HE modular multilevel converter (MMC)-based multiter-
T minal dc (MTdc) grid has the advantages of decoupled
active and reactive power control, no commutation failure, pas-
of the MTdc grid, it is difficult to bear the high cost. To solve this
problem, several economical multiport hybrid dc circuit breakers
(MHCBs) are proposed [5]–[11].
sive network power supply capability, etc., which is suitable
Liu et al. [5] proposed an assembly HCB that can isolate
for the integration of large-scale renewable power generations
the fault on any protected line through the shared MB installed
and has become a research hotspot worldwide [1]. However,
on the dc bus. The dc switchyard proposed in [6] commutates
it is vulnerable to dc-side faults, and the fault current can rise
the fault current into the shared MBs by LCPs in redundant
to tens of times the rated current in several milliseconds after
configuration. The three-port HCB designed for the Tangjiawan
a dc-side fault occurs. Therefore, the dc-side fault must be
±10 kV three-terminal dc distribution network in [7] includes
two complete HCBs based on coupled negative voltage and a
fast mechanical switch. It can interrupt the fault current of 10 kA
Manuscript received 20 October 2021; revised 27 March 2022 and 10 within 2.7 ms. The diode-bridge MHCB in [8] can commutate
June 2022; accepted 28 June 2022. Date of publication 13 July 2022;
date of current version 3 January 2023. This work was supported by the the fault into the MB by LCP on the fault port and diode branches,
National Natural Science Foundation of China under Grant 52077124 and isolate the fault by opening the MB. In [9], the proposed
and Grant 51677109. (Corresponding author: Guibin Zou.) MHCB realizes the current commutation by an integrated LCS
The authors are with the School of Electrical Engineering, Shandong
University, Ji’nan 250061, China (e-mail: 201714182@mail.sdu.edu. instead of individual LCS on each port. The control system of
cn; guibinzou@sdu.edu.cn; weixiuyan@sdu.edu.cn; zhouch1994@ the proposed breaker can be simplified at the expense of lower
mail.sdu.edu.cn; 201914261@mail.sdu.edu.cn). reliability caused by an additional current commutation. The
Color versions of one or more figures in this article are available at
https://doi.org/10.1109/TIE.2022.3189106. MHCB in [10] is composed of a bidirectional MB and a selector
Digital Object Identifier 10.1109/TIE.2022.3189106 branch for each port. The selector branch is made up by one
0278-0046 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
4728 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 70, NO. 5, MAY 2023

breaker cell and a string of thyristors. Compared to the MHCB


in [8], the proposed MHCB is more expensive and complex. The
multiline DCCB in [11] consists of a unidirectional MB and 2n
LCPs for n protected lines. After a dc fault occurs, half of the
LCPs, that is, n LCPs should be operated to commutate the fault
current into the MB, which is complex and hard to control. The
MHCB in [12] can reduce the fault current interruption time
(FCIT) by bypassing the current-limiting inductor (CLI) on the
fault port with a small resistor. Since only a CLI in the MHCB is
bypassed, the performance gain is limited. Another advantage of
the MHCB is that it can softly reclose the fault port by inserting
a large resistor in the fault loop.
However, due to the hardware limitation and reliability re-
quirement, the line protection and HCB take at least several Fig. 2. Topology of the proposed MCL–HCB.
milliseconds in total to isolate the fault, which still cannot match
the dc fault propagation speed. Therefore, fault current limiting
techniques are essential to guarantee the fault ride-through of precharged capacitors. Besides, compared to directly install the
the MTdc grid. At present, the CLIs are usually installed to CLIs, the MCL–HCBs need several milliseconds (the total ac-
suppress the rising speed of the fault current, which is effective tion time of the line protection and the UFD) before limiting the
and easy to implement [13], [14]. However, the large CLIs have fault current.
adverse impacts on the operation of the HCBs, such as extending Therefore, considering the problems existing in the currently
the FCIT and increasing the energy dissipation pressure of proposed FCLs and HCBs, such as the high cost, the complicated
the arrester. To avoid the negative impacts of the CLIs, the topology and control, the inevitable time delay before fault
typical hybrid current limiting circuit (HCLC) in [15] and its current limitation, the high energy dissipation pressure of the
improved topology in [16] are proposed. They can limit the arrester, and long FCIT, a novel MCL–HCB is proposed in this
fault current by the embedded CLI and bypass the CLI by the article, which has the advantages as follows:
energy dissipation circuit (EDC) during the energy dissipation 1) The expensive MB that consists of many fully controlled
of the HCB. Since they do not need full-controlled semicon- semiconductor switches and large-capacity arresters are
ductor switches, their total costs are acceptable. However, the shared by all ports, resulting in low cost.
resistors in the EDC should dissipate large amount of energy, 2) The fault current can be limited by the embedded CLIs
which may require special design. Instead of directly configuring without time delay, and the performance of the line pro-
the CLIs, several fault current limiters (FCLs) are proposed tections based on the boundary effect of CLIs will not be
to limit the fault current [17]–[19]. The superconducting FCL influenced.
can insert large impedance in the fault loop immediately af- 3) The FCIT and the dissipated energy of the arrester can be
ter the fault occurs, which has wide application prospects in greatly reduced by turning on the inductor bypass branch
MTdc grids [17], [18]. However, the problems of long recovery (IBB) during energy dissipation process.
time and high investment cost need to be further addressed. The rest of this article is organized as follows. The topology
The FCL based on mutual inductance in [19] has a compact and operation principles of the MCL–HCB are elaborated in
structure and simple control. However, if the load current and Section II. In Sections III and IV, the effectiveness of the MCL–
the fault current flow in opposite directions, the load current HCB is verified by simulations and experiments, respectively. In
has to flow through the diodes and large power losses will be addition, the performance comparison between the MCL–HCB
generated. and existing solutions is conducted. Finally, Section V concludes
The coordinated operation of HCBs and FCLs is expectable in this article.
the MTdc grids. Therefore, there is an opportunity to integrate
the HCB and the FCL into a single device. In addition to the II. TOPOLOGY AND OPERATION PRINCIPLE OF MCL–HCB
fault current interruption capability, the bridge-type HCB in
[20] can limit the fault current in two stages by an embedded A. Basic Topology
inductor and two resistors, respectively. The HCB proposed The topology of the proposed MCL–HCB is illustrated in
in [21] contains a controllable CLI, whose inductance can be Fig. 2, which has n ports and can substitute n typical HCBs and
increased to limit the fault current and can be decreased to FCLs. It has a CLI Lck , an LCP including LCSk and UFDk , two
facilitate the energy dissipation of the arresters by a controlled diode branches Duk and Dlk , a thyristor branch Tk for port Pk
solid-state switch. The multiport current limiting (MCL)–HCBs (k = 1, 2, …, n), a shared IBB, and a shared MB. Compared
in [22], [23] can limit the fault current by inserting a large with the typical HCB, the MB in the MCL–HCB only needs
inductor in the fault loop. However, the insertion process needs unidirectional current interruption capability. Therefore, half of
one or more precharged capacitors to provide negative voltage the insulated gate bipolar transistors (IGBTs) can be saved. The
to turn-off the thyristor branches, and the reliable turn-off of the IBB has same structure but different rating as the MB. The CLIs
thyristors is hard to guarantee owing to the fast discharging of the are responsible for limiting the fault current.

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
ZHANG et al.: MULTIPORT CURRENT-LIMITING HYBRID DC CIRCUIT BREAKER FOR MTDC GRIDS 4729

Fig. 3. Simplified model of n-terminal dc grid.

B. Analysis Model 2, …, n) satisfy


⎧ di
The equivalent model of the n-terminal dc grid illustrated ⎪ −vck + (Leqk + Lk + Lck ) dtpk + Rk ipk


in Fig. 3 is used to analyze the operation principles of the ⎪
⎪ di
+(Lc1 + Lr1 ) dtp1 + Rr1 ip1 = 0

⎪ t
MCL–HCB. To simplify the analysis with sufficient accuracy, ⎨
the following aspects should be considered: vck (t) = Udc − Ceqk1
t0 ipk dt (1)

⎪ n  t di
1) The Line k is modeled as a series branch of the lumped ⎪
⎪ ip1 (t) = ipk (t) = Ipre1 + t0 dtp1 dt


inductor Lk and the lumped resistor Rk . ⎪
⎩ k=2  t di
2) The MMCk is modeled as a capacitor Ceqk with the initial ipk (t) = Iprek + t0 dtpk dt.
voltage Udc in series with an inductor Leqk [24].
3) The load current of port k is denoted by Iprek . By solving (1), the port currents can be obtained in Laplace
4) The ideal model of the arrester in MB and IBB is domain as follows:

adopted, which means its voltage will change imme- Udc +s[(Leqk +Lk +Lck )Iprek +(Lc1 +Lr1 )Ipre1 ]


n
diately to the residual voltage once the fault current ⎪
⎪ k=2
s2 (Leqk +Lk +Lck )+sRk +C −1

⎪ Ip1 (s) = eqk
e−st0
is commutated into it. In addition, the residual volt- ⎪
⎨ n
1+ k=2
s2 (Lc1 +Lr1 )+sR1
s2 (Leqk +Lk +Lck )+sRk +C −1
ages of the arrester in MB and IBB are Ur1 and Ur2 , eqk

⎪ I (s) =
Udc +s[(Leqk +Lk +Lck )Iprek +(Lc1 +Lr1 )Ipre1 ] −st0
e
respectively. ⎪

pk 2
s (Leqk +Lk +Lck )+sRk +Ceqk −1


5) The conduction resistances of the CLIs, the UFDs, and ⎪
⎩ [ 1
sR +s 2
(L +L r1 ] p1
) I (s)
− s2 (L +L +L )+sR +C −1 .
c1

the semiconductor switches are neglected. eqk k ck k eqk

6) The semiconductor switches in the MCL–HCB are con- (2)


sidered as ideal components. At time t1 , the MCL–HCB receives the trip signal from the
line protection. The action time of the line protection ranges in
the timeframe of milliseconds [2]. Then, the thyristor branch
C. Operation Principle T1 on the fault port is turned on and the LCS1 is turned off
Before the fault occurs, the LCP of each port, the IBB, and the to commutate the fault current into the MB. This commutation
MB are in the on state, while the thyristor branches T1 –Tn are in process lasts tens of microseconds [9] and ends at time t2 . Then,
the off state. Therefore, the load currents only flow through LCPs the UFD1 is commanded to open, as illustrated in Fig. 4(b). The
and CLIs, and no additional power losses are generated. After UFD based on Thomson-coil actuator has extremely fast action
the fault occurs, the operation process of the MCL–HCB can speed in the zero-current state, and its typical opening time is
be divided into three stages: fault current limiting, fault current 2 to 3 ms [25]. It is assumed that the UFD1 is fully opened at
interruption, and CLI freewheeling current clearance, which will time t3 . During the time period from time t0 to time t3 , the port
be analyzed below in detail. currents still satisfy (1) and (2). Besides, since dic1 /dt and dick /dt
1) Stage 1—Fault Current Limiting: It is assumed that the are positive, according to (3), the voltage potentials vu2 , …, vun
short-circuit fault F occurs at time t0 . Then, the fault current are higher than the voltage potential vu1 . Therefore, the diode
starts to rise and is injected into the fault point, as illustrated in branches Du2 , …, Dun of healthy ports are blocked by the reverse
Fig. 4(a). The rising speed of the fault current will be suppressed voltage and the fault current will not flow through the IBB
by the embedded CLIs without any time delay. In this period, dic1 dick
the fault port current ip1 and the healthy port current ipk (k = vuk = vu1 + Lc1 + Lck . (3)
dt dt

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
4730 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 70, NO. 5, MAY 2023

Fig. 4. Current paths of the MCL–HCB in different periods. (a) t0 < t < t2 . (b) t2 < t < t3 . (c) t3 < t < t4 . (d) t > t4 .

2) Stage 2—Fault Current Interruption: After the UFD is arrester in the MB is defined as the FCIT, which is |t4 −t3 | for
fully opened at time t3 , the MB is turned off and the fault current the proposed MCL–HCB. The dissipated energy of the arrester
in the MB is commutated into the arrester to be dissipated. At in the MB can be obtained as follows:
the same time, due to the high residual voltage of the arrester  t4
in the MB, the voltage potential vu1 is higher than the voltage Ea1 = Ur1 ip1 dt. (6)
potentials vu2 , …, vun . Therefore, the diode branches Du2 , …, t3
Dun are conducted and the CLI currents will freewheel through 3) Stage 3—CLI Freewheeling Current Clearance: Af-
the IBB, as shown in Fig. 4(c). The freewheeling path of the CLI ter the fault current is interrupted at time t4 , the IBB
current is: Lc1 –T1 –Ti (IBB)–Duk –Lck –Lc1 . In this period, the is turned off, and the CLI freewheeling current will be
following equations are satisfied: forced into the parallel arrester to be dissipated, as illus-
⎧ di trated in Fig. 4(d). The freewheeling current decays to zero

⎪ −vck + (Leqk + Lk ) dtpk + Rk ipk + Ur1

⎪ at time t5 . During this process, the following equations are
⎪ dip1
⎪+Lr1 dt + Rr1 ip1 = 0  t

⎨ satisfied:
vck (t) = vck (t3 ) − Ceqk
1
t3 ipk dt

(4) ⎨ Lck didtck + Lc1 didtc1 + Ur2 = 0

⎪ 
n  t dip1
⎪ 
⎪ip1 (t) = k=2 ipk (t) = ip1 (t3 ) + t3 dt dt
n
⎪ (7)

⎪ ⎩ iBB (t) = ic1 (t) = ick (t).
⎩  t di k=2
ipk (t) = ipk (t3 ) + t3 dtpk dt.
Then, the current iBB (t) of the IBB can be obtained as follows:
By solving (4), the port currents can be obtained in Laplace 
domain as follows: Ur2 nk=2 L−1
iBB (t) = ic1 (t4 ) −  ck
t. (8)
⎧ n vck −Ur1 +s[(Leqk +Lk )ipk (t3 )+Lr1 ip1 (t3 )] 1 + Lc1 nk=2 L−1


ck


k=2
s2 (Leqk +Lk )+sRk +C −1

⎪ Ip1 (s) = n
k
e−st3 Since the CLI current of the fault port remains unchanged
⎨ 1+ k=2
s2 Lr1 +sR1
s2 (Leqk +Lk )+sRk +C −1 during Stage 2, ic1 (t4 ) in (8) is equal to ip1 (t3 ). The CLI free-
k

⎪ Ipk (s) =
vck −Ur1 +s[(Leqk +Lk )ipk (t3 )+Lr1 ip1 (t3 )] −st3
e wheeling time Tf and the dissipated energy Ea2 of the arrester

⎪ 2
s (Leqk +Lk )+sRk +Ck −1

⎪ (sR1 +s2 Lr1 )Ip1 (s) in the IBB can be obtained as follows:
⎩ − s2 (L +L )+sR +C −1 . ⎧ n
⎨ Tf = t5 − t4 = c1 4 U( c1 k=2 Lck )
−1
eqk k k k
⎪ i (t ) 1+L
(5) n
r2 L−1k=2 ck
It is assumed that the fault current in the MB decays to zero ⎪ 
⎩ Ea2 = t5 Ur2 iBB dt = 1
Lc1 + n 1 [ic1 (t4 )]2 .
at time t4 . After that, the RCB1 can be opened to totally isolate t4 2 k=2 L−1
ck
the fault line. In this article, the energy dissipation time of the (9)

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
ZHANG et al.: MULTIPORT CURRENT-LIMITING HYBRID DC CIRCUIT BREAKER FOR MTDC GRIDS 4731

in the MB is as follows:
n n n
Ea10 = El1 + Elk + Esk + Eck (12)
k=2 k=2 k=1

where

⎪ El1 = 2 Lr1 Ip1. max , Elk = 2 (Leqk + Lk ) Ipk. max
1 2 1 2


Eck = 12 Lck Ipk.
2
max (13)

⎪  t3 +Tc0

Esk = t3 Udc ipk dt = 12 Udc Ipk. max Tc0
where El1 and Elk denote the stored energy in the dc line; Eck
denotes the stored energy in the CLI; and Esk denotes the energy
provided by the converters. As for the MCL–HCB, the stored
energy will be dissipated by the MB and the IBB together, and
the dissipated energy Ea1 and Ea2 of the arrester in MB and IBB
is
⎧ n n

⎪ Ea1 = El1 + Elk + Esk



⎨ k=2 k=2
Fig. 5. Flowchart of the operation sequences of the proposed n
MCL–HCB. Ea2 = Eck




k=1

n 
n n

⎩ Esum = Ea1 + Ea2 = El1 + Elk + Esk + Eck
It should be noted that small arrester residual voltage in the k=2 k=2 k=1
IBB will satisfy the requirement of the current clearance. After (14)
time t5 , the thyristor unit T1 will be automatically turned off. where El1 , Elk , and Eck in (14) are the same as those in (13),
Then, the MCL–HCB is ready for the next fault. while Esk in (14) is as follows:
 t3 +Tc
1
D. Flowchart Esk = Udc ipk dt = Udc Ipk. max Tc . (15)
t3 2
The operation sequences of the proposed MCL–HCB are
summarized in the flowchart in Fig. 5. Since Tc is much smaller than Tc0 , Esk in (14) is smaller than
that in (12). Therefore, the total dissipated energy of the arrester
E. Influence of IBB on Fault Isolation in the MB and the IBB is much smaller than that of the typical
HCB. Besides, since the fault current energy is dissipated by
As analyzed in Section II-C, the CLI currents will freewheel the MB and the IBB together in the MCL–HCB, the energy
through the IBB in Stage 2 and then be cleared by the arrester dissipation pressure of the MB can be greatly reduced.
in the IBB in Stage 3. In this part, the influences of the IBB on
fault isolation are discussed in detail.
III. PARAMETER DESIGN
In order to simplify the analysis, the line resistance Rk in (5) is
omitted due to its small value (several milliohms per kilometer). A. CLI
In addition, the capacitor voltage is considered constant at Udc . The CLIs are responsible for limiting the fault current and are
By applying the above assumptions, the FCIT Tc of the fault designed based on the system requirements such as the converter
port P1 can be obtained by (5) as follows: fault ride-through [26]. The optimization configuration of the

1 + Lr1 nk=2 (Leqk + Lk )−1 CLI has been thoroughly investigated in the literature [26]–[30],
Tc = ip1 (t3 )  . (10) which will not be discussed here.
(Ur1 − Udc ) nk=2 (Leqk + Lk )−1
In contrast, if only CLIs and the typical HCBs are configured, B. Residual Voltage and Capacity of Arrester in MB
the FCIT Tc0 is as follows:
 The residual voltage of arrester in the MB determines the
1 + (Lc1 + Lr1 ) nk=2 (Leqk + Lk + Lck )−1 FCIT and further influences its dissipated energy during the
Tc0 = ip1 (t3 )  .
(Ur1 − Udc ) nk=2 (Leqk + Lk + Lck )−1 fault isolation. As can be seen in (10), the increase of the
(11) residual voltage Ur1 will lead to smaller FCIT, which will
It is obvious that Tc0 is much larger than Tc (Tc0 is nearly further decrease the arrester dissipated energy according to (12)
three times Tc for the simulation model in Section V). Besides, and (13). However, more IGBT modules will be required if the
the energy dissipated by the arrester in the MB includes the residual voltage of the arrester increases, which will increase
energy stored in the inductance component in the fault loop and the total cost of the MCL–HCB. Therefore, considering the
the energy provided by the converters. As for the solution based above tradeoff relationship, this article refers to the design
on CLIs and typical HCBs, the dissipated energy of the arrester parameters of the HCB that has been put into operation in the

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
4732 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 70, NO. 5, MAY 2023

±500 kV Zhangbei four-terminal dc grid [25], the residual TABLE I


MAJOR PARAMETERS OF SIMULATION MODEL
voltage of the arrester in the MB is selected as 1.6 p.u.
Once the residual voltage of the arrester is determined, its
capacity should be derived. The MCL–HCB should interrupt the
fault current after the short-circuit fault occurs on any location
of the connected dc lines. Therefore, assume that several faults
are set on each dc line at interval of 5% of the line length, and
the dissipated energy of the arrester in the MB after the above
fault scenarios are calculated using (2), (5), and (6). The arrester
capacity should be larger than the maximum value Ecm1 of the
calculated results. In real applications, some safe margin should
be considered to ensure the reliability. Therefore, considering
the reliable coefficient Krel , the arrester capacity of the arrester
in the MB is determined as Krel Ecm .

C. Residual Voltage and Capacity of Arrester in IBB


voltage will also be endured by the diode branch Du1 and the
As can be seen in (9), the residual voltage of the arrester thyristor branches T2 , …, Tn .
in the IBB only influences the CLI freewheeling time Tf , It should be noted that the fault can occur on any port.
but is irrelevant to its dissipated energy Ea2 . The increase of Therefore, the IGBTs in the MB and the IBB should withstand
the residual voltage of the arrester in the IBB will lead to the voltage of Ur1 , Ur2 , respectively. In addition, during the fault
shorter CLI freewheeling time, which will also increase the isolation process, the maximum voltages of the diode branches
implementation cost of the IBB since the IGBT modules in the Du1 , …, Dun , and the thyristor branches T1 , …, Tn are the dc
IBB should withstand higher voltage. Therefore, considering grid voltage Udc , while the maximum voltages of the diode
the above tradeoff relationship, the residual voltage of the branches Dl1 , …, Dln are the arrester residual voltage Ur1 in
arrester in the IBB is selected as 10% of the rated dc voltage. the MB. Besides, the maximum current of each branch can be
As for the capacity of the arrester in the IBB, after the obtained by Section II-C. Therefore, based on the withstand volt-
dissipated energy of the arrester in the MB under different fault age and maximum current magnitude of each branch obtained
locations is calculated as shown in Section III-B, the dissipated in this part and the datasheets of the selected semiconductor
energy of the IBB is also calculated by (9). The arrester capacity switches, the total number of semiconductor switches can be
of IBB should be larger than the maximum value Ecm2 of the obtained.
calculated results. By considering the reliable coefficient Krel ,
the capacity of the arrester in the IBB is determined as Krel Ecm2 . IV. SIMULATION VERIFICATION

D. Semiconductor Switch Count A. Simulation Model

During the period from time t0 to time t3 , according to Fig. 3(a) The three-terminal asymmetrical monopolar model is built
and (b) and (3), the diode branches Du2 , …, Dun and the thyristor in PSCAD/EMTDC software to verify the effectiveness of the
branches T2 , …, Tn should withstand the voltage across the proposed MCL–HCB, whose topology is the same as the MTdc
CLIs, and the following relationship is satisfied: grid in Fig. 3 with three terminals. The detailed models of the
MMC and the arrester are adopted. The other key parameters of
0 < vu1 < vuk < vck < Udc . (16) the simulation model are listed in Table I. The current reference
directions are defined in Fig. 3. Besides, the voltage and the
Then, the above equation can be obtained, which means the
current are associated reference directions.
withstand voltages of the diode branches Du2 , …, Dun and the
thyristor branches T2 , …, Tn are less than the dc grid voltage
Udc , as follows: B. Simulation Results
The short-circuit fault F occurs at 5.0 s, which is set in the
vuk − vu1 < Udc . (17)
middle of Line 1. The MCL–HCB receives the trip signal at
In the Stage 2, the CLI currents freewheel through the IBB, 5.003 s and starts to isolate the fault. The operation sequences of
and the voltage potentials vu1 , …, uvn are theoretically the same. the MCL–HCB are illustrated in Fig. 5. The simulation results of
Therefore, the diode branches Du2 , …, Dun and the thyristor the MCL–HCB during the fault isolation are shown in Figs. 6 and
branches T2 , …, Tn will not withstand voltage. However, the 7. Besides, the MCL–HCB in the simulation model is replaced
IGBTs in the MB should withstand the residual voltage Ur1 of by the same CLIs as in the MCL–HCB and the typical HCBs
the parallel arrester, which is also endured by the diode branches in Fig. 1, and another simulation with the same fault scenario
Dl2 , …, Dln . is conducted. The performance comparison between the MCL–
In the Stage 3, the IGBTs in the IBB are turned off and should HCB and the solution based on typical HCBs is illustrated in
withstand the residual voltage Ur2 of the parallel arrester. This Figs. 8 and 9.

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
ZHANG et al.: MULTIPORT CURRENT-LIMITING HYBRID DC CIRCUIT BREAKER FOR MTDC GRIDS 4733

Fig. 6. Simulation results of the fault isolation with the MCL–HCB.


(a) Port currents ip1 –ip3 . (b) Currents ic1 –ic3 of the CLIs. (c) Currents
iMB and iIBB of the MB and IBB. (d) Dissipated energy Ea1 and Ea2 of
the arresters in the MB and IBB.

As can be seen from Fig. 6, the fault currents of the ports


P1 , P2 , and P3 reach peak values of 9.17, 2.36, and 6.88 kA,
respectively, during the fault isolation process. After the MB is
turned off at 5.005 s, its voltage rises to the residual voltage of the Fig. 7. Voltage waveforms of the key components in the MCL–HCB
during fault isolation. (a) CLI voltages. (b) Voltages of thyristor branches
parallel arrester. Then, the fault current decays to zero 5.0080 T1 –T3 . (c) Voltages of diode branches Du1 –Du3 . (d) Voltages of diode
s. Therefore, the FCIT of the MCL–HCB can be determined branches Dl1 –Dl3 . (e) Voltages of MB and IBB.
as 3.0 ms. Besides, the dissipated energy of the arrester in the
MB is 11.1 MJ. During the energy dissipation process of the
arrester in the MB, the CLI currents freewheel through the IBB to Fig. 7, during the fault isolation process, the voltages across
and remain nearly unchanged. After the fault current decays to the thyristor branches T1 –T3 and the diode branches Du1 –Du3
zero, the IBB is turned off and its voltage rises to the residual are less than the system nominal voltage. Besides, the maximum
voltage of the parallel arrester. Then, the CLI currents start to voltage of the diode branches Dl2 and Dl3 on the nonfault ports
be dissipated by the arrester in the IBB. The current clearance is around 800 kV, which is the residual voltage of the arresters in
process lasts about 45 ms. During this period, the dissipated the MB. In conclusion, the simulation results of the component
energy of the arrester in the IBB is 9.7 MJ. In addition, according voltages are consistent with the analysis in Section III-C.

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
4734 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 70, NO. 5, MAY 2023

Fig. 10. Topology and photograph of the scaled-down experimental


setup. (a) Topology. (b) Photograph.

can be reduced by 67.4% and 66.7%. Even considering the


dissipated energy of the arrester in the IBB, the MCL–HCB
Fig. 8. Simulation results of the fault isolation with the typical HCB. can reduce the dissipated energy of the arrester by 37.5%. It
(a) Port current ip1 –ip3 . (b) Current iMB of MB. (c) Dissipated energy
Ea10 of arresters in the MB. should be noted that the above analysis only takes the dissipated
energy of a single HCB into consideration. If multiple lines are
considered, the cost of the solution based on typical HCBs will
increase linearly, while the cost of the MCL–HCB only increase
slightly.
The currents of the healthy ports in Fig. 9 indicate that
although the clearance of the CLI freewheeling currents in the
MCL–HCB needs tens of milliseconds, the recovery of the
healthy lines is still faster than the solution based on the typical
HCBs.

C. Performance Comparison
The MCL–HCB proposed in this article is compared with
the existing solutions. The configuration details of different
solutions are as follows: Solution I—the MCL–HCB proposed
in this article; Solution II—only the CLIs and the typical HCBs;
Solution III—the HCLCs in [15] and the typical HCBs; Solution
IV—the improved HCLC in [16] and the typical HCBs; Solution
V—only the CLIs and the MHCB in [8]; Solution VI—only
the CLIs and the MHCB in [11]; Solution VII—the MHCB in
Fig. 9. Simulation waveforms of the healthy port currents under differ-
[12]; and Solution VIII—the MCL–HCB proposed in [22]. It
ent solutions. (a) Port current ip2 . (b) Port current ip3 . is assumed that the IGBT module 5SNA3000K452300 (4.5 kV,
4961 USD), the thyristor K0900ME650 (6.5 kV, 400.5 USD),
and the diode VS-SD1100C20C (2 kV, 72.3 USD) are utilized in
As can be seen in Fig. 8, if only the CLIs and the typical all solutions. The redundant configuration of the components is
HCBs are configured, the peak values of all the ports are the not considered. The number of IGBTs in the LCS is omitted.
same with those of the MCL–HCB. However, the FCIT and Besides, the costs of the arrester and the energy dissipation
the dissipated energy of the arrester in the MB are 9.2 ms and resistor in [12] are both considered as 15485 USD/MJ. The
33.3 MJ, respectively. Therefore, by adopting the MCL–HCB, cost of the UFD is considered as 0.15 MUSD. The performance
the FCIT and the dissipated energy of the arrester in the MB factors of different solutions are listed in Table II. It should be

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
ZHANG et al.: MULTIPORT CURRENT-LIMITING HYBRID DC CIRCUIT BREAKER FOR MTDC GRIDS 4735

TABLE II
PERFORMANCE COMPARISON OF DIFFERENT SOLUTIONS

noted that the term “total arrester capacity” in Table II means TABLE III
MAJOR PARAMETERS OF EXPERIMENTAL SETUP
the total required capacity of the arresters in the typical HCBs
or MHCBs to protect all the dc lines.
As can be seen, since the MB in the typical HCB requires
a large number of IGBTs to withstand a transient interruption
voltage of hundreds of kilovolts, the total cost of all the solutions
based on the typical HCBs (Solutions II–IV) is several times that
of the solutions based on the MHCB. In addition, since the CLIs
have negative impacts on the performance of the DCCBs, the
solutions with only the CLIs configured (e.g., Solutions II, V,
and VI) require much larger arrester capacity and have longer
FCIT than the other solutions. For example, the total required
reverse voltage on the thyristors to help them turn OFF. Therefore,
arrester capacity and the FCIT of Solutions II are nearly two
the costs of the capacitor and its charging equipment should be
times those of Solution III and three times those of Solution
considered. Besides, since the precharged capacitor discharges
IV, respectively. Besides, the total required arrester capacity and
rapidly, it is difficult to guarantee the reliable turn OFF of the
the FCIT of Solutions V are nearly 1.5 times and 3 times that of
thyristors.
Solution I, respectively.
In summary, the solution based on the MCL–HCB proposed
As for the MCL–HCBs in Solutions I and VII, Solution I has
in this article has the smallest investment cost. Besides, it can
the superiorities over Solution VII as follows:
interrupt the fault current faster than the other solutions and
1) Significantly reduce the component cost. The diode
dissipate less energy during the fault isolation.
branches and the thyristor branches in the MCL–HCB
of Section VII should withstand the residual voltage
of the MB, which is 1–2 times of the nominal sys- V. EXPERIMENTAL VERIFICATION
tem voltage. However, only the diode branches Dl1 – A. Experimental Setup
Dln in Solution I should withstand the residual volt-
The topology schematic and photograph of the scaled-down
age of the MB, while the diode branches Du1 –Dun and
experimental setup established in the laboratory to verify the
the thyristor branches T1 –Tn should withstand the volt-
feasibility of the proposed MCL–HCB are illustrated in Fig. 10.
age less than the nominal system voltage. According
The key parameters of the experimental setup are listed in
to Table II, if Solution I is adopted, 18.8% of diodes
Table III. Since LCSs, UFDs, RCBs, and thyristors of the ports
and 37.9% of thyristors can be saved compared with
P2 and P3 will not operate during the experiment, they are not
Solution VII.
configured in the experimental setup, which are marked by the
2) Significantly reduce the arrester cost and the energy dis-
dotted squares. The UFD is implemented by IGBT modules.
sipation pressure. The MCL–HCB in Solution VII only
Once the LCS is turned off, the UFD will be turned off with a
bypasses the CLI on the faulted line through a resistor
delay of 1 ms. The voltage and current are measured by sensors
during the energy dissipation of the arrester in the MB,
and uploaded to a personal computer by series communication.
while the MCL–HCB in Solution I bypasses all the CLIs
by the IBB. Therefore, the performance of Solution I
is much better than Solution VII. It can be seen from B. Experimental Results
Table II that the required arrester capacity and the FCIT During normal operation, LCS1 , UFD1 , RCB1 , and Ti in the
of Solution I are only 50.8% and 68.9% of Solution VII, IBB and the MB the MCL–HCB are in the on state, while the
respectively. thyristors T1 , the MB, and the fault unit F are in the off state.
The MCL–HCB in Solution VIII commutates the fault current The fault unit F is turned on at first, and the fault current rises
into a large CLI to suppress its rising speed. Since the com- rapidly. After 1 ms, the thyristor T1 is turned on and the LCS1 is
mutation process takes several milliseconds, it has the longest turned off. Then, the UFD and the MB are turned off after 1 ms.
FCIT. Besides, a precharged capacitor is required to applying The experimental results are illustrated in Fig. 11. Then, after

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
4736 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 70, NO. 5, MAY 2023

Fig. 12. Port currents of configuration scheme of CLIs and typical


HCBs.

VI. CONCLUSION
A. Contributions
To reliably limit and interrupt the fault current, a simple and
easily applied MCL–HCB is proposed in this article. The pro-
posed device integrates the function of the FCL and the DCCB
together. It utilizes embedded CLIs to limit the fault current
without any time delay and eliminates the negative impacts of
the CLIs by configuring an additional IBB.
By adopting the proposed MCL–HCB, the FCIT and the dis-
sipated energy of the arrester can be greatly reduced. Compared
to the solution based on the CLIs and the typical HCBs, the
total cost, the dissipated energy of the arrester, and the FCIT
of the MCL–HCB can all be reduced by more than 2/3 for the
studied case in this article. Besides, it has compact structure and
simple control. Simulations and experiments have verified the
effectiveness of the proposed MCL–HCB.

B. Practical Limitations of MCL–HCB


Although the proposed MCL–HCB performs well in simula-
tions and scaled-down experiments, there are still some practical
limitations to consider before being applied to HVdc grids,
which are as follows:
1) The MCL–HCB contains many units, including signal
Fig. 11. Experimental results of the fault isolation with the MCL–HCB. measurement, UFD operation, and component driving,
(a) Port currents. (b) CLI currents. (c) MB and the IBB currents. (d)
Voltages across the MB and the IBB. which work at different voltage potential and require
power supply. Besides, the operation voltage of the MCL–
HCB is very high. Therefore, the power supply system of
the fault current decays to zero, the IBB is turned off. The MOV the MCL–HCB should be specially designed.
in the IBB starts to dissipate the CLI freewheeling current. In 2) There are a large number of detection, processing, calcu-
addition, the port currents when only the CLIs and typical HCBs lation, and drive units in the MCL–HCB. Therefore, the
being configured are presented in Fig. 12. strict electromagnetic compatibility requirements should
As can be seen from Fig. 11, if the MCL–HCB is adopted, the be satisfied to avoid the misoperation of the breaker.
FCIT is about 0.2 ms. Besides, the dissipated energy of the MOV 3) The arrester is the core component of the MCL–HCB
in the MB and the IBB is 0.15 and 8.77 J, respectively. As for during the fault current interruption. To dissipate the large
the condition that only CLIs and typical HCBs are configured, fault energy, the arresters are required to be connected in
the FCIT is about 2.82 ms, and the dissipated energy of the parallel to increase their capacity. However, due to inher-
typical HCB is 19.99 J. Therefore, by adopting the proposed ent imperfections in the manufacturing process, not all
MCL–HCB, the FCIT can be reduced by 92.9%. Besides, the the arresters have identical V-I characteristics. Therefore,
dissipated energy of the arrester can be reduced by 55.4%. It the dissipated energy among the parallel arresters is un-
should be noted that a single MCL–HCB connects to multiple equally distributed, which will cause thermal overloading
dc lines, and the reduced arrester capacity of all the HCBs are of one or more arresters and further result in their damage.
considerable. Although the proposed MCL–HCB can reduce the total

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
ZHANG et al.: MULTIPORT CURRENT-LIMITING HYBRID DC CIRCUIT BREAKER FOR MTDC GRIDS 4737

dissipated energy and split the remaining energy to be semiconductor switches or other economical methods to realize
dissipated by two units, the issue of the arresters should the functions of MB and IBB to further reduce the cost.
also be considered.
4) The existed current sensors may have maximum de-
REFERENCES
tectable current magnitude and limited bandwidth for
HVdc application. The current sensors based on Ro- [1] O. Gomis-Bellmunt, J. Sau-Bassols, E. Prieto-Araujo, and M.
Cheah-Mane, “Flexible converters for meshed HVDC grids: From flexible
gowski coil can carry tens of kiloamps over an extended AC transmission systems (FACTS) to flexible DC grids,” IEEE Trans.
bandwidth up to tens of MHz [31], which can satisfy the Power Del., vol. 35, no. 1, pp. 2–15, Feb. 2020.
requirement of the HVdc breaker. [2] W. Xiang, S. Yang, G. P. Adam, H. Zhang, W. Zuo, and J. Wen, “DC
fault protection algorithms of MMC HVDC grids: Fault analysis, method-
5) During the normal operation, the LCS in the proposed ologies, experimental validations and future trends,” IEEE Trans. Power
MCL–HCB should conduct the load current. To ensure Electron., vol. 36, no. 10, pp. 11245–11264, Oct. 2021.
that the junction temperature of the IGBT is lower than the [3] F. Mohammadi et al., “HVDC circuit breakers: A comprehensive review,”
IEEE Trans. Power Electron., vol. 36, no. 12, pp. 13726–13739, Dec. 2021.
limit, it is necessary to configure a more efficient cooling [4] M. Callavik, A. Blomberg, J. Häfner, and B. Jacobson, “The hybrid HVDC
system for the LCS, like the water-cooling system. Be- breaker: An innovation breakthrough enabling reliable HVDC grids,” ABB
sides, the LCS in the MCL–HCB should withstand larger Grid Systems, ABB, Zürich, Switzerland, Tech. Rep., 2012.
[5] G. Liu, F. Xu, Z. Xu, Z. Zhang, and G. Tang, “Assembly HVDC breaker
voltage than the LCS in the typical HCB in Fig. 1 during for HVDC grids with modular multilevel converters,” IEEE Trans. Power
current commutation. In the typical HCB, the voltage Electron., vol. 32, no. 2, pp. 931–941, Feb. 2017.
across the LCS should be larger than the voltage drop [6] R. Majumder, S. Auddy, B. Berggren, G. Velotto, P. Barupati, and T. U.
Jonsson, “An alternative method to build DC switchyard with hybrid DC
on the MB to commutate the fault current into the MB. breaker for DC grid,” IEEE Trans. Power Del., vol. 32, no. 2, pp. 713–722,
However, in the proposed breaker, the voltage across the Apr. 2017.
LCS should be larger than the total voltage drops of [7] L. Qu et al., “Engineering application of three-terminal hybrid DC cir-
cuit breaker,” Autom. Elect. Power Syst., vol. 43, no. 23, pp. 141–148,
the MB, a thyristor branch Tk , and a diode branch Dlk . Dec. 2019.
Therefore, more IGBT modules should be included in [8] S. Zhang, G. Zou, X. Wei, and C. Sun, “Diode-bridge multiport hybrid DC
the LCS of the MCL–HCB. Fortunately, the LCS in the circuit breaker for multiterminal DC grids,” IEEE Trans. Ind. Electron.,
vol. 68, no. 1, pp. 270–281, Jan. 2021.
proposed breaker is unidirectional, which can save half [9] A. Mokhberdoran, D. Van Hertem, N. Silva, H. Leite, and A. Carvalho,
IGBT modules compared to the bidirectional LCS in the “Multiport hybrid HVDC circuit breaker,” IEEE Trans. Ind. Electron.,
typical HCB. vol. 65, no. 1, pp. 309–320, Jan. 2018.
[10] E. Kontos, T. Schultz, L. Mackay, L. M. Ramirez-Elizondo, C. M. Franck,
6) The MCL–HCB cannot handle the dc bus fault. Although and P. Bauer, “Multiline breaker for HVDC applications,” IEEE Trans.
the dc bus is usually configured indoors and has low Power Del., vol. 33, no. 3, pp. 1469–1478, Jun. 2018.
fault probability, the dc bus fault isolation should be [11] W. Liu, F. Liu, Y. Zhuang, X. Zha, C. Chen, and T. Yu, “A multiport circuit
breaker-based multiterminal DC system fault protection,” IEEE J. Emerg.
considered. If the proposed breakers are adopted in the Sel. Topics Power Electron., vol. 7, no. 1, pp. 118–128, Mar. 2019.
MTdc grid, the dc bus fault isolation will rely on the [12] S. Zhang, G. Zou, X. Wei, and C. Zhang, “Multiport hybrid DC circuit
breakers on the remote end of the dc line connected to breaker with reduced fault isolation time and soft reclosing capability,”
IEEE Trans. Ind. Electron., vol. 69, no. 4, pp. 3776–3786, Apr. 2022.
the dc bus. [13] W. Leterme, J. Beerten, and D. Van Hertem, “Nonunit protection of HVDC
7) Compared to semiconductor switches, the UFDs in the grids with inductive DC cable termination,” IEEE Trans. Power Del.,
MCL–HCB have higher possibility to fail due to its me- vol. 31, no. 2, pp. 820–828, Apr. 2016.
[14] C. Li, A. M. Gole, and C. Zhao, “A fast DC fault detection method using
chanical operation. Once the UFD fails to operate, the DC reactor voltages in HVdc grids,” IEEE Trans. Power Del., vol. 33,
breaker will not perform as intended. Therefore, the reli- no. 5, pp. 2254–2264, Oct. 2018.
able open of the UFD is extremely important. The UFD [15] J. Liu, N. Tai, C. Fan, and S. Chen, “A hybrid current-limiting circuit
for DC line fault in multiterminal VSC-HVDC system,” IEEE Trans. Ind.
in the MCL–HCB can be designed as several vacuum Electron., vol. 64, no. 7, pp. 5595–5607, Jul. 2017.
breakers in series as have been adopted in the typical [16] B. Li, J. He, Y. Li, Q. Sun, Q. Mao, and W. Wen, “The improved topology
HCB, which cannot only improve the open speed, but and control strategy for the HCLC in multi-terminal flexible DC grid,”
IEEE J. Emerg. Sel. Topics Power Electron., vol. 9, no. 2, pp. 1795–1807,
also increase the reliability by redundant configuration. Apr. 2021.
[17] B. Li, C. Wang, W. Hong, S. Yang, and Y. Xin, “Modeling of the DC induc-
tive superconducting fault current limiter,” IEEE Trans. Appl. Supercond.,
C. Future Article vol. 30, no. 4, Jun. 2020, Art. no. 5601105.
[18] X. Tan et al., “Analysis of R-SFCL with shunt resistor in MMC-HVDC
Next step, we plan to design a medium-voltage prototype of system using novel R-Q method,” IEEE Trans. Appl. Supercond., vol. 30,
the MCL–HCB to further verify its performance. The LCS in no. 4, Jun. 2020, Art. no. 5601405.
[19] Z. Fu et al., “A mutual-inductance-type fault current limiter in MMC-
the proposed MCL–HCB causes power losses during normal HVDC systems,” IEEE Trans. Power Del., vol. 35, no. 5, pp. 2403–2413,
operation and requires cooling systems, which will reduce grid Oct. 2020.
efficiency and increase costs. To overcome these limitations, we [20] A. Heidary, K. Rouzbehi, M. Hesami, M. Bigdeli, and C. Bor-
dons, “Bridge-type fault current limiter and hybrid breaker for HVDC
will explore a better approach to achieve reliable current com- grids applications,” IET Gener., Transmiss. Distrib., vol. 14, no. 18,
mutation with low power losses to replace the LCS in the future pp. 3913–3919, Sep. 2020.
article. Besides, the MB and the IBB of the proposed MCL–HCB [21] A. Heidary, M. Bigdeli, and K. Rouzbehi, “Controllable reactor based
hybrid HVDC breaker,” High Voltage, vol. 5, no. 5, pp. 543–548, 2020.
consist of a large number of fully controlled semiconductor [22] N. Han, Q. Fan, X. Jia, X. Zhao, J. Xu, and C. Zhao, “A multi-port DC
switches, resulting in high implementation cost. Therefore, in circuit breaker with current limiting capability,” Proc. CSEE, vol. 39,
future article, we will investigate the use of half-controlled no. 17, pp. 5172–5181, Sep. 2019.

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.
4738 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 70, NO. 5, MAY 2023

[23] J. Xu, B. Song, Y. Lv, C. Zhao, J. Liang, and G. Li, “A multi-port current- Guibin Zou (Member, IEEE) received the M.Sc.
limiting hybrid DC circuit breaker,” IEEE Trans. Power Del., vol. 36, no. 3, and Ph.D. degrees in automation of elec-
pp. 1672–1682, Jun. 2021. tric power systems from Shandong University,
[24] C. Li, C. Zhao, J. Xu, Y. Ji, F. Zhang, and T. An, “A pole-to-pole short- Ji’nan, China, in 2000 and 2009, respectively.
circuit fault current calculation method for DC grids,” IEEE Trans. Power Since 2013, he has been a Professor of elec-
Syst., vol. 32, no. 6, pp. 4943–4953, Nov. 2017. trical engineering with the School of Electri-
[25] X. Zhang et al., “A state-of-the-art 500-kV hybrid circuit breaker for a dc cal Engineering, Shandong University, Ji’nan,
grid: The world’s largest capacity high-voltage dc circuit breaker,” IEEE China. His research interests include the protec-
Ind. Electron. Mag., vol. 14, no. 2, pp. 15–27, Jun. 2020. tion and control techniques of ac/dc grids, the
[26] Y. Wang, W. Wen, C. Zhang, Z. Chen, and C. Wang, “Reactor siz- protection and control of active distribution net-
ing criterion for the continuous operation of meshed HB-MMC-based works, and the distribution system automation.
MTDC system under DC faults,” IEEE Trans. Ind. Appl., vol. 54, no. 5,
pp. 5408–5416, May 2018.
Xiuyan Wei (Student Member, IEEE) received
[27] R. Li, L. Xu, D. Holliday, F. Page, S. J. Finney, and B. W. Williams,
the B.Sc. degree in applied physics from Hu-
“Continuous operation of radial multiterminal HVDC systems under DC nan University, Changsha, China, in 2011, and
fault,” IEEE Trans. Power Del., vol. 31, no. 1, pp. 351–361, Feb. 2016.
the M.Sc. degree in microelectronics and solid-
[28] E. Kontos, S. Rodrigues, R. T. Pinto, and P. Bauer, “Optimization
state electronics from Xiamen University, Xia-
of limiting reactors design for DC fault protection of multi-terminal
men, China, in 2014. She is currently working
HVDC networks,” in Proc. IEEE Energy Convers. Congr. Expo., 2014,
toward the Ph.D. degree in electrical engineer-
pp. 5347–5354.
ing with the School of Electrical Engineering,
[29] E. Kontos and P. Bauer, “Reactor design for DC fault ride-through in
Shandong University, Ji’nan, China.
MMC-based multi-terminal HVDC grids,” in Proc. IEEE 2nd Annu. Her research interests include MVdc protec-
Southern Power Electron. Conf., 2016, pp. 1–6.
tion and control.
[30] Y. Li and Y. Gong, “Optimal design scheme of current limiting reactor for
multi-terminal DC power grid,” Autom. Elect. Power Syst., vol. 42, no. 23, Chenghan Zhou (Student Member, IEEE)
pp. 120–128, Dec. 2018. received the B.Sc. degree from the Shanghai
[31] D. Tzelepis et al., “Voltage and current measuring technologies for high University of Electric Power, Shanghai, China, in
voltage direct current supergrids: A technology review identifying the 2017, and the M.Sc. degree from the Shandong
options for protection, fault location and automation applications,” IEEE University, Jinan, China, in 2020, both in electri-
Access, vol. 8, pp. 203398–203428, 2020. cal engineering. He is currently working toward
the Ph.D. degree in electrical engineering with
the School of Electrical Engineering, Shandong
University, Ji’nan, China.
His research interests include power system
protection and active distribution networks.
Shuo Zhang (Student Member, IEEE) received Chengquan Zhang received the B.Sc. and
the B.Sc. and Ph.D. degrees in electrical en- M.Sc. degrees in electrical engineering from
gineering from Shandong University, Ji’nan, Shandong University, Ji’nan, China, in 2019 and
China, in 2017 and 2022, respectively. 2022, respectively.
He is currently a Postdoctoral Researcher His research interests include HVdc protec-
with the Shandong University, Ji’nan, China. His tion and circuit breaker.
research interests include HVdc control and pro-
tection and power electronics.

Authorized licensed use limited to: UNIVERSITY OF SOUTHAMPTON. Downloaded on April 01,2023 at 17:12:21 UTC from IEEE Xplore. Restrictions apply.

You might also like