You are on page 1of 11

1732 CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, VOL. 9, NO.

5, SEPTEMBER 2023

Research on a Multiport Parallel Type Hybrid


Circuit Breaker for HVDC Grids: Modeling
and Design
Xinming Guo, Student Member, IEEE, Jin Zhu, Member, IEEE, Qingpeng Zeng, Student Member, IEEE,
Hao Xiao, Member, IEEE, and Tongzhen Wei

Abstract—This paper proposes a star type multiport hybrid circuit breaker to reduced the cost [4]. It should be admitted
circuit breaker (Star-HCB) topology for protection of multi- there will be a large number of HCBs when constructing multi-
terminal DC transmission. Reliability and stability of high terminal DC transmission [5], [6]. It will occupy a large part
voltage DC (HVDC) grids are determined by their capabilities
to withstand DC-side faults. In order to maintain reliability of the cost of the system, resulting in low economy of HVDC
of HVDC grids, both ends of each line should be equipped grids.
with hybrid circuit breakers (HCB). This method will increase The application of a multiport DC current interrupter device
expenditure of the HVDC, especially the meshed topology. The can be an effective method to solve this problem. A multi-
n-port Star-HCB consists of ultra-fast mechanical disconnectors, port hybrid DC circuit breaker is shown in [7], n main
load current switch and only one transferring branch which is
formed by improved half-bridge sub-module. Compared with breaker branch, n load current switches (LCS) and n − 1
existing traditional hybrid circuit breakers and other multi- ultra-fast mechanical disconnectors (UFD) are needed for n
port hybrid circuit breakers, the proposed topology can realize connected lines. Although the main disconnect switch only
the same short-circuit blocking goal using fewer components. needs to have one-way current breaking capacity, it still needs
Detailed mathematical transient process calculation and time- to independently bear all transient breaking voltages in the
domain simulation of the proposed Star-HCB are given to verify
its superiority. process of fault breaking, which increases the manufacturing
cost of HCB. An interlink HCB proposed by [8] uses path
Index Terms—Fault blocking, HVDC grids half-bridge multiplexing between lines to form a multi terminal DC
submodule, hybrid circuit breaker, multi-port. circuit breaker. The unidirectional type only needs half the
components of the typical separate HCB. It cannot handle
a DC fault in a DC bus. The bidirectional type requires
3/4 of the components of typical separate HCBs, which has
I. I NTRODUCTION some economic significance. However, the disadvantage of this
structure is not easy to expand and can only be applied to
T HE direct-current circuit breaker (DCCB) is essential
equipment in DC grids, and has gradually gotten re-
searchers’ attention in recent years, such as mechanical types,
three end scenarios. Literature [9] realizes sharing of main
circuit breakers by adding nominal current branches (NCB).
solid state types and hybrid types. In these topologies, hybrid Each DC line of this structure is connected to the positive
and negative bus, respectively, through two NCB to form a
circuit breakers (HCB) have been widely applied since it can
bridge structure. When breaking the fault current, the upper
balance interruption time and conduction loss.
and lower NCB will force the fault current to flow through the
Various HCBs and their applications are analyzed in [1]–
transfer branch. However, this topology is difficult to break
[3]. Classic HCB topology is formed by IGBTs in series and
load currents in different directions. A DC switch yard [10]
ultra-fast disconnectors (UFD). It has been successfully tested
adopts an array of main circuit breakers and load transfer
by ABB [1]. Another HCB topology proposed by the State
switches to deal with multi terminal faults. The number of
Grid Corporation of China (SGCC) [2], [3] replaces IGBTs in
components is slightly less than of typical separate HCB and
series with cascaded IGBT full-bridge sub-modules (FBSM) to
it has rich backup protection functions. [11], [12] provides a
prevent voltage imbalance. The scholar in North China Electric
bridge-type structure, which uses a diode string to transfer the
Power University develops a low-loss and compact hybrid DC
current, which protects the LCS from peak fault current.
Manuscript received July 12, 2021; revised November 21, 2021; accepted Most of the topologies mentioned above use series type
December 31, 2021. Date of online publication August 18, 2022; date of main breakers (MB). It will be connected in series to the
current version September 19, 2022. This work was supported by the Institute
of Electrical Engineering, CAS under grant (E155610101, E155610201 and fault circuit. [13]–[15] have different designs. The fault current
E155610301). will flow into the MB rather than the fault circuit. This
X. M. Guo, J. Zhu (corresponding author, e-mail: zhujin@mail.iee.ac.cn), novel structure can realize short-circuit current suppression
Q. P. Zeng, H. Xiao, T. Z. Wei are with Institute of Electrical Engineering,
Chinese Academy of Sciences and University of Chinese Academy of with many fewer components. For multi-terminal application,
Sciences, Beijing 100190, China. a parallel DC circuit breaker with auxiliary switching is
DOI: 10.17775/CSEEJPES.2021.05040 proposed in [16]. The main circuit breaker connects the DC
2096-0042 © 2021 CSEE. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
GUO et al.: RESEARCH ON A MULTIPORT PARALLEL TYPE HYBRID CIRCUIT BREAKER FOR HVDC GRIDS: MODELING AND DESIGN 1733

bus and the ground to construct a virtual short circuit point. It 1) Nominal current branch
creates the condition for the mechanical switch to realize zero An NCB that consists of UFD and unidirectional LCS is
current switching. However, each line has an extra auxiliary required for each port of the Star-HCB. It connects each line
discharge switch composed of a thyristor and an anti-parallel at the central point A of the star type connection. Unlike
diode, which increases the cost. traditional DCCB with bidirectional LCS, the Star-HCB reuses
Based on parallel type research, a multi-terminal Star-HCB the multi-terminal unidirectional LCS to realize bidirectional
is proposed in this paper based on the concept of using current transfer. It can reduce conduction loss by half.
only one MB for n connected lines. It aims to decrease the 2) Star structure of diodes
overall cost of the MB without extra UFD, LCS or any other The cathodes of diodes D1 -D3 strings are connected to the
additional auxiliary switches. Different from the bidirectional central point B. The anodes of diode strings are connected to
LCS in [15], the Star-HCB can reuse the unidirectional LCS each port of Star-HCB. The main function of the star structure
to achieve the interruption goal, which further reduces conduct of diodes is to lower the peak current value of the LCS of
loss. It is easy to expand from n lines to n + 1 lines and no non-fault lines and bring a zero-current environment of UFD.
matter which line has a short-circuited fault, the corresponding Reduced number of parallel IGBTs in LCS can achieve lower
line can be cut off. conduction loss.
An operation principle of the HCB is provided in Section II. 3) Freewheeling diode strings
The comparative analysis between the proposed star-type HCB Each line needs a freewheeling diode circuit to absorb
and other multi-port HCB solutions is detailed in Section III. the energy of the short-circuit current after the NCB is
Simulation verification in MATLAB is presented in Section IV. opened. Different from series topology, the MB does not have
The Section V summaries the merits and drawbacks of the to dissipate the energy of the line inductance. Due to the
topology. DC reactor and low damping circuit structure, the current
freewheeling process will last for a long time. However, the
II. C IRCUIT C ONFIGURATION AND O PERATION P RINCIPLE maximum current flowing through the diode is equal to that in
A. Topology of Star-HCB LCS, which will decrease exponentially and does not exceed
Based on the characteristics of parallel structure and the the nominal maximum diode current. This process can be
demand of cost reduction, a multi-port Star-HCB is proposed represented in (1).
in this section. To better illustrate, a three-terminal monopolar ID (t) = ILCS (t2 )e− L t
R
(1)
HVDC system is analyzed as an example.
Figure 1 shows the basic structure of the proposed 3-port Meanwhile, the freewheeling diode strings will be equipped
star-HCB topology. Fig. 1(a) is a monopolar type and suitable with a reasonable heat dissipation structure to prevent damage
for unipolar HVDC grids. Fig. 1(b) is a symmetrical structure to the device.
and can be applied in bipolar HVDC grids. The bipolar type 4) Main breaker branch:
can handle both single polar faults and bipolar faults. The main Same as other HCB topologies, the MB is used to break the
components are as follows: final current capability. The main breaker branch is formed

ne 2
2 Li e2
M Lin
2 SR L dc 2
UFD 2 SRM L dc
LCS
2
2 UFD
Line 1 SRM 1 UFD 1 LCS 1 D2 LCS
A UFD 1 LCS 1 Line 1 SRM 1 A D2
LCS
3
D5

Ldc D1 UFD LCS


B 3 SR Ldc 3 U
M3 D1 B FD 3
Line SRM
Per-charge Circuit 3 3
Per-charge Circuit Line
D3 3
Energy Absorption Branch

Ldc
D4

D3 Ldc
D5

Main Breaker Branch


Energy Absorption Branch
MOV

MOV
Main Breaker Branch
D4

MOV

D6

D6
MOV
MOV

(a) (b)

Fig. 1. Structure of a 3-port Star-HCB. (a) monopolar type; (b) bipolar type.
1734 CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, VOL. 9, NO. 5, SEPTEMBER 2023

by improved half-bridge sub-modules (HBSM). The capaci- are discharging circuits to prevent overvoltage state of the
tance in a sub-module can realize dynamic voltage balancing capacitor after the interruption.
when the IGBTs in series switch off at the same time [17]. Assuming the first capacitor is bypassed, and n − 1 capac-
In addition, compared with IGBT-in-series structure [1] or itors are put into the charging circuit. The voltage of each
Udc
diode bridge type structure [18], the HBSM structure reduces capacitor can be charged to n−1 . Then, the second capacitor
parasitic resistance and inductance because the current path is bypassed and first one is switched in. After all the capacitors
in MB is design as a unidirectional parallel structure. It can are bypassed and charged, the sum of n capacitors voltage can
ensure the LCS in this topology will withstand less voltage. reach to
Less number of IGBT means less loss. n
Vc = Udc (3)
5) Per-charge circuit n−1
The capacitor in MB needs to be charged first. To prevent (3) shows the voltage of a capacitor is higher than nominal
surge current from damaging the device, the charging resis- DC voltage Udc . Voltage can be adjusted by the number of
tance and a switch are added in MB. when the start-up is bypassed capacitors each time. This capacitors voltage can
finished, the switch closes and bypasses the resistance. The provide a larger reverse current and in turn create the current
charging current can be represented as zero crossing for the star-HCB.
Udc − 1 t In this condition, the per-charged capacitor will limit the
Ic (t) = e RC (2) fault current after the IGBTs in HBSM switch off. The
R
process of capacitor charging by fault current will be sig-
The current Ic should be lower than the maximum current nificantly shortened compared with FBSM-HCB proposed by
of diode in HBSM Dsm and Di to prevent device damage. SGCC [21].
The charging resistance R will determine this value.
6) Soft reclosing modular (SRM) C. Operation Principles of the Proposed Star-HCB
The soft reclosing model is proposed in [19]. It aims to Due to the symmetry of the Star-HCB topology, the control
limit surge current when the HCB recloses. The switch in this strategy to handle a short-circuit fault is similar. The control
modular does not need fast operation and arc extinguishing diagram of Star-HCB is shown in Fig. 3. The complete fault
function. Therefore, it will not cost too much. Parallel high interruption process is divided into 5 steps.
resistance can provide enough time for UFD reaction in
permeant faults. Fault occurs in Line 2
t0

B. Characteristic of Half Bridge Sub-modules


t1 Fault detected The IGBTs in MB
When the short-circuit fault occurs, the fault current does conduct
not have zero crossing in the DC grid. Therefore, how to
extinguish the arc quickly and safely is the most important LCS2 turns off and
t2
task of DC fault breaking. UFD2 begins to open
Most of HCBs use series IGBTs to interrupt the fault
current. To overcome the asynchronous problem in IGBTs,
snubber capacitance is used. However, the charge current t3 UFD2 completely open
of capacitance in fault interruption will lead to the lag of
peak current. Research [20] points out the lag time will last The IGBTs of MB
t4
50∼200 us. In our study, sub-module capacitors are pre- turn off
charged to reduce this time.
In HBSM design, the capacitance can be charged to a higher
t5 Surge arrester blocking
voltage by alternating conduction. As shown in Fig. 2, each
capacitor of the HBSMs can be put into charging circuit
or bypass by switching the IGBTs in HBSM. Voltage bal- t6 Fault clear
ancing control method is introduced to control the number
of capacitors put into the charging circuit. The Sc and Rc
Fig. 3. Fault clear flow chart.

Take a three-terminal Star-HCB as an example. It is assumed


the DC short-circuit fault occurs on Line2. The handling
Sc Ccb D Sc Ccb D
strategy is as follows:
MOV
MOV

Rc T Rc T 1) Step 1: When the fault is detected at t1 , the IGBTs in


the HBSM switch on immediately. As shown in Fig. 4(a), the
fault current flows from station 1 and 3 into the fault point
(a) (b) and the MB through D1 and D3 . The voltage between joints
A and B will be equipotential. Therefore, the LCS2 will not
Fig. 2. Capacitors per-charge process. (a) Bypass stage; (b) Charge stage. withstand high voltage.
GUO et al.: RESEARCH ON A MULTIPORT PARALLEL TYPE HYBRID CIRCUIT BREAKER FOR HVDC GRIDS: MODELING AND DESIGN 1735

e1
e1 Lin
Lin D1
1 F
UFD 1 U
1 UFD 2 LCS 2 LCS
UFD 2 LCS 2 LCS D1 Line 2 A D1
Line 2 LCS

D4
A LCS 3 UF
3 UF B D 3

D4
D2 B D3 D3
D2 Line
D3 Line 3
3

D5

MOV
D5

MOV

D6
D6
(a) (b)

e1 e1
Lin Lin
1
F D1 UFD
1 U LCS
1
UFD 2 LCS 2 LCS D1
UFD 2 LCS 2
Line 2 A Line 2 A D1
LCS LCS

D4
D4
3 UF 3 UF
B D3 B D3
D3 D2 D3 Line
D2 Line 3
3

D5
D5

MOV
MOV

D6
D6

(c) (d)

e1
Lin
F D1
1 U
UFD 2 LCS 2 LCS 1
Line 2 A LCS D
D4

3 UF
B D3
D2 D3 Line
3
D5

MOV

D6

(e)

Fig. 4. DC fault handling strategy. (a) Step 1 of the strategy; (b) Step 2 of the strategy; (c) Step 3 of the strategy; (d) Step 4 of the strategy; (e) Step 5 of
the strategy.

2) Step 2: When the LCS2 turns off at t2 , the current path, and it rapidly decreases because of higher voltage of the
which flows through it will be interrupted. The fault current capacitor in HBSM sub-modules.
from station 1 and 3 only flows into the MB through D1 and 5) Step 5: The protected voltage will be set by the metal
D3 respectively, as shown in Fig. 4(b). D1 and D3 construct oxide varistor (MOV). When the capacitor voltage of the
two new fault current paths of Line1 and Line3 to limit the HBSM sub-modules reaches it, the current will be commutated
maximum current value of LCS1 and LCS3. The energy of again to the MOV, and continue to drop to zero, the fault-
inductance in Line2 is consumed through the freewheeling clearance is finished, as illustrated in Fig. 4(e).
diode string D5 and fault point. At this time, the current loops
of fault and non-fault are separated. D. Normal Isolation Operation
3) Step 3: About 2 ms later, the UFD opens completely at Normal isolation operation is similar to the fault process.
t3 , as shown in Fig. 4(c). The fault line is separated from the The main difference is there will be no judgment time in the
DC grid physically. load interruption. Therefore, peak current will be smaller than
4) Step 4: The IGBTs of MB turn off at t4 , as illustrated the fault condition. The Star-HCB needs to create an active
in Fig. 4(d). The fault current is transferred to the capacitor short-circuit to ensure the UFD opens without an arc. This
1736 CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, VOL. 9, NO. 5, SEPTEMBER 2023

will generate a short-circuit current in the system. However, are short circuited simultaneously, the equivalent short-circuit
nearly 2 ms short-circuit duration will be permitted because impedance is smaller and the current in a DC bus will rise
the current traveling wave will be smoothed by the DC reactor more during t0 ∼ t1 . But in t1 ∼ t2 the MB will not
equipped in the port of the breaker. It will not cause the miss- endure larger current because the active short-circuit branch
operation of other DCCB protection. is closer to the DC bus than other short-circuit branches. The
main task is to ensure the two UFDs open in an acceptable
E. Reclosing Operation time. In practice, the time difference of fault occurrences may
When the fault is permanent, the Star-HCB will not reclose. not exceed the whole breaking period. This urges the MB to
Most of the fault is instantaneous and DC grids need to recover conduct more time and leads to a higher magnitude of fault
from the fault status. The recovery process is shown in Fig. 5. current. This is the common drawback in multiterminal HCB.
When Star-HCB isolates the fault, the Sc closes and lowers
the voltage of the capacitor. It helps the DCCB restore to III. M ODELING A NALYSIS OF S TAR -HCB
the initial state. At the same time, the SRM opens without Different with the series type DCCB, the parallel type
arc and the high resistance access in the short-circuit. Then, DCCB has complex impacts on a grid. To analyze the transient
after deionization of the system, the UFD recloses directly. process of the Star-HCB clearly, a simplified model of the DC
There will be two conditions. One is fault elimination, the grid with it is established in this section. Traditional analysis
SMR will then close and the system recovers. Another is of circuit breakers focuses on each stage in HCB. It can
the fault still exists. The SMR prevents the surge current calculate the current at any time of short circuit, according
affecting the system. when the UFD is enabled, the MB will to the parameters of any line [7]–[11]. However, the influence
trip and the UFD will open again. This strategy has some of a circuit breaker on a power system is not considered. The
drawbacks such as shorter lifetime of UFD, current stress of math equation of a grid with DCCB is necessary to analysis
MOV and IGBT. But all topologies with the ‘O-C-O’ reclosing each state of the whole system. The basic structure of the
strategy have the same problem. In fact, in the field of fault radial three-terminal monopolar HVDC system with a DC
detection, researchers try to directly judge whether the fault short-circuit fault is shown in Fig. 6.
still exists through data analysis such as transient operating
A. RLC Equivalent Circuit of DC Grid
voltages before the reclosing [22]. Applying that strategy in
this topology will avoid the drawback of the strategy. Figure 7 shows the RLC equivalent circuit of the radial DC
grid with three terminals. In this simplified model, the positive
Star-HCB isolates the fault
short-circuit
Line 1 fault Line 2
Sc closes and discharges the HCB
capacitor
HCB
SRM opens Proposed Star-HCB
Line 3
HCB
After deionization, UFD recloses
HCB

Yes Fig. 6. Radial HVDC network with three terminals with a DC short-circuit
Fault clear ? fault.

No A1
L 14
ic1
R 14
SRM closes Wait for UFD A2 L24 R24 A4 uc2+ C
to be enabled − c1
ic2
+ R
Cc2 − uc2 34 Lc1
L
34
Reclosing Star-HCB A3
success isolates the fault Lc2
ic3 Rc1

Fig. 5. Reclosing process. Rc2 uc3+ Cc3


F. Extreme Conditions Operation Lc3

Research [7] indicates the transmission line is not physically Rc3


close together, and the fault of a different line is dependent.
Therefore, the possibility of two lines short circuiting at the Fig. 7. RLC equivalent circuit of the radial HVDC network with three
same time is very low. In extreme conditions, when two lines terminals.
GUO et al.: RESEARCH ON A MULTIPORT PARALLEL TYPE HYBRID CIRCUIT BREAKER FOR HVDC GRIDS: MODELING AND DESIGN 1737

line resistance and inductance are the same as the negative A1


L 14 ic1
since the system is a bipolar structure. R 14 i 14
A2 Lf24 Rf24 if24 Ls24 Rs24 A4 uc1 + Cc1
Before analyzing the calculation, the stations and branches −
i if
in a DC grid should be defined first. In Fig. 7, the stations +c2 R
Cc2 uc2 34 Lc1
A1 , A2 and A3 are the “real stations” which are connected − L i3
34 4
to a converter. A4 is defined as a common joint of three Lc2 Rf A3
ic3
transmissions. The Rij and Lij (i, j = 1, 2, 3, 4) represent Rc1
line resistance and line inductor, including current limiting Rc2 uc3 + Cc3
inductance between stations Ai to Aj , the Rci , Lci and Cci −
(i = 1, 2, 3) represent on-state resistance, AC reactor and Lc3
sub-module capacitor of station Ai (i = 1, 2, 3).
Rc3
B. Math Equations of Stage1
Fig. 8. Equivalent circuit of star-HCB in HVDC system at stage 1.
When the short-circuit fault occurs, a path with resistance
Rf will be formed between the positive and negative transmis-
sion lines. As described in section II, there are five steps to And
break this short-circuit fault.
Because the fault point is between stations A2 and R=
A4 , the impedance on Branch 24 is divided into two  
Rc2 + 2Rf24 + Rf Rf Rf
impedances Ls24 &Rs24 and Lf 24 &Rf 24 , The Ls24 &Rs24  Rf Rc1 + 2R14 + Rf + 2Rs24 Rf + 2Rs24 
includes the limiting impedance and part of line impedance. Rf Rf + 2Rs24 Rc3 + 2R34 + Rf + 2Rs24
The Lf 24 &Rf 24 only contains the rest of line impedance. (10)
The branch current is written as L=
 
T 2Lf24 + Lc2 0 0
I1 = [if24 i14 i34 ] (4)
 0 2L14 + 2Ls24 + Lc1 2Ls24 
The voltage of equivalent converter capacitor is chosen as 0 2Ls24 2L34 + 2Ls24 + Lc3
the state variable to shows the influence of short circuit fault (11)
on a converter station.
T These equations describe the process of capacitor discharge
Uc = [uc2 uc1 uc3 ] (5)
after the fault occurs. When the state equation (8) is transferred
Figure 8 is stage 1 of the fault interruption. The differential into a discrete format, each variable of the system can be
equations can be formed by KVL and KCL. The circuit calculated step by step.
equations from A2 to A4 are derived as follow
C. Math Equations of Step 2∼3
uc2 = −Rc2 ic2 − Lc2 didtc2 + 2Rf24 if24



+ 2Lf24 didtf24 + Rf if

At the time of fault detection, the MB will conduct imme-

(6)

 ic2 = −if24 diately. The current in UFD2 will immediately transfer to the


if = if24 + i14 + i34 MB. The LCS2 switches off simultaneously to block the rest
of the current. The UFD2 begins to open to form electrical
Simplified (6) can be written as isolation. The Ron is the on-resistance of all IGBTs in the
dif24 dif24 MB.
uc2 = Rc2 if24 + Lc2 + 2Rf24 if24 + 2Lf24
dt dt The system is divided into two parts. One is formed by
+ Rf if24 + Rf i14 + Rf i34 (7) Star-HCB and normal transmission line. It should be noted the
current from A1 and A3 flows into the artificial short circuit
It can be seen from (7), the current from A2 can be replaced point naturally. Another is formed by the traditional series
by the line’s current and converter’s voltage. The other lines’ type DCCB and fault transmission line. With the freewheeling
current and voltage can be obtained in the same way, and then diode, the residual energy in line inductance can be consumed
the equivalent equation can be established. gradually. At the same time, the LCS2 will withstand almost
(
I˙1 = R 1 zero voltage. The equivalent equation and circuit impedance
L I1 + L Uc (8) matrix should be changed at the same time.
U̇c = −CI1
The equivalent equation
where C is the equivalent capacitor matrix of converter,
(
(R)3×3 and (L)3×3 are the circuit impedance matrix. Uc = R0 I1 + L0 I˙1
C can be written as (12)
  U̇c = −CI1
1 1 1
C = diag (9)
Cc2 Cc1 Cc3 R0 can be written as
1738 CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, VOL. 9, NO. 5, SEPTEMBER 2023

A1 A1
L 14
R 14 i 14 ic1 L 14 ic1
A2 Lf24 Rf24 Ls24 Rs24 A4 uc1+ Cc1 R 14 i 14
ic2

A4 uc1 + Cc1
if24 if −
Cc2 +
−uc2
R
34 Lc1
L i3 R
34 4
Lc2 Ron A3 34 Lc1
Rf
ic3 Rc1 L i3
34 4
Ccb +
ucb A3
Rc2 uc3+ Cc3 − ic3
− Rc1
Lc3

Rc3 +
uc3 Cc3

Fig. 9. Equivalent circuit of star-HCB in HVDC system at stage 2∼3. Lc3

R0 = Rc3
 
Rc2 + 2Rf24 + Rf 0 0
 0 Rc1 + 2R14 + Ron Ron  Fig. 10. Equivalent circuit of star-HCB in HVDC system at stage 4.
0 Ron Rc3 + 2R34 + Ron  
(13) 2R14 + Rc1 0
R1 = (19)
0 2R34 + Rc3
L0 can be written as  
2L14 + Lc1 0

2Lf24 + Lc2 0 0
 L1 = (20)
0 2L34 + Lc3
L0 =  0 2L14 + Lc1 0  (14)
C can be changed as C1
0 0 2L34 + Lc3  
1 1 1
The freewheeling circuit is not included in the equation due C1 = diag (21)
Ccb Cc1 Cc3
to its independent structure. It can be seen from (13) and (14),
the line impedances Ls24 &Rs24 are removed from the circuit Since the capacitors of the HBSM Ccb are pre-charged and
impedance matrix. It means the short-circuit current will rise their voltages are higher than the voltage of Cc1 or Cc3 , the
in a fixed rate due to the artificial short-circuit point. It may voltage of inductance L14 and L34 will be reversed at once.
be a drawback of the Star-HCB. However, compared with the It means the inductance current will decrease without delay.
converter smoothing reactor, the reduced line impedance can
E. Math Equations of Step 5
be ignored to some degree. In addition, no matter parallel or
series type, the design of MB should consider extreme cases, In Fig. 11, when the Ccb is charged to the protected voltage
especially the short-circuit point closed to the DCCB. of the MOV, the fault current will be commutated to a surge
arrester. Then the vector Uc1 degenerates into the Uc2 . Due to
D. Math Equations of Step 4 the change of networks, the voltage vector can be written as
T
When the UFD2 in the TB achieve adequate isolation, Uc2 = [uc1 uc3 ] (22)
the IGBTs in the MB begin to turn off. As the residual
The equation can be written as
inductive current has decreased to zero, station A2 is locked. (
The capacitors in the HBSMs Ccb are plugged into the circuit Uc2 = R1 I1 + L1 I˙1 + Uadd
and replace the on-resistance, as shown in Fig. 10. (23)
U̇c2 = −C2 I1
The Uc vector expand the voltage of the capacitors Ccb
as Uc1 where the Uadd represents the protect voltage of a surge arrester
T
Uc1 = [ucb uc1 uc3 ]
T
(15) Uadd = [1.5Udc 1.5Udc ] (24)

The branch current is written as C can be narrowed as C2


 
T 1 1
I11 = [i14 i34 ] (16) C2 = diag (25)
Cc1 Cc3
And the equation changes to Finally, this state will last until the fault current decays to
( zero. The fault is eliminated.
T Uc1 = R1 I11 + L1 I˙11
(17) From an operation process, it can be concluded that during
U̇c1 = −C1 T T I11 the process of handling the short-circuit fault, Line1 and Line3
where the T is transmission matrix can be written as have no need to be isolated from the HVDC system. Station
  A1 and A3 can keep working properly.
−1 1 0
T = (18) This RLC equivalent model can calculate the transient value
−1 0 1
of the Star-HCB in fault interruption. It can guide the circuit
R1 and L1 can be written as breaker according to grid configuration.
GUO et al.: RESEARCH ON A MULTIPORT PARALLEL TYPE HYBRID CIRCUIT BREAKER FOR HVDC GRIDS: MODELING AND DESIGN 1739

A1 solutions. Based on the above calculation method, the number


L 14
i 14 ic1 of IGBT in MB of the proposed solution is ns np , the other
R 14
A4 uc1+ Cc1
− solution IGBT number can also be calculated based on similar
approaches, and results are shown in Table I.
R Lc1
34
L
It can be observed the solution in [9], [10], [12] and the
Ccb 34 i3 proposed solution require the least number of IGBTs, but the
+u 4
A3
− cb ic3 solution in [9] needs an additional double number of LCS and
Rc1
UFD, the solution in [10] needs additional n thyristor strings
for n lines, that still increases the overall cost of the system.
uc3 + Cc3
− The proposed solution only needs an additional 2n diode string
Lc3 for n lines, the system cost is significantly reduced.

Rc3 B. Extensibility
In the multi-terminal DC network (MTDC), a converter
Fig. 11. Equivalent circuit of star-HCB in HVDC system at stage 5. station always connects with multiple lines. Thus, in the
typical separate solution, three or more HCBs are needed
IV. C OMPARISON to meet each line protection. Excessive HCBs means huge
equipment investment.
This section takes several characteristics of DCCB into This proposed solution integrates multiple HCBs into a
consideration. Comparison of the proposed multiport HCB single multiport MB through a star-connection. It is clear that
topology with other existing multiport HCB topologies are the Star-HCB can be easily extended from n port HCB to
shown in Table I. n + 1 port HCB due to its symmetrical structure and without
a greater number of MB branches.
A. Economic Considerations
Such as solution in [7], [9] and [10] also have symmetrical
The MB is the main cost in HCB, and the number of structures. The solution in [7] increases the number of MB
semiconductor devices mainly determines the cost of MB, and branches while extending the ports, the solution in [9] must
can be calculated by (26). need more UFD and MB branches. The solution in [10]
NMB = ns np nd (26) will not increase the number of MB branches but have huge
implementation difficulty of MB. Detailed comparison results
where ns is the number of series IGBT modules in the MB, are shown in Table I.
np is number of parallel IGBT modules, nd is the direction
parameter. C. Other Important Features
The IGBTs in a series of MB need to withstand maximum 1) Structure of MB: Grounded active modular main breaker
pole-to-ground voltage. Therefore, protected voltage should be structure is adopted in the proposed solution. A half-bridge
1.5 times nominal DC grid voltage [23]. The IGBT module sub-module cascade structure is used to replace the IGBTs-
HiPak 5SNA 3000K452300 is applied in MB and LCS part, in-series structure to avoid the IGBT string synchronization
which can withstand 4.5 kV. Considering the safety of each and dynamic voltage balancing problem. The capacitor in sub-
module, a single IGBT module will bear half of the rated module can be pre-charged in a flexible value. Some other
voltage [24], 2.3 kV. The number of parallel IGBT modules unidirectional main breaker structures such as traditional IGBT
ns in the proposed solution is 652. Based on (8) (12), the in series structure can also be used in the proposed star-type
peak fault current can be calculated. The rated current of the HCB topology.
IGBT module is 3 kA. Considering the maximum current of 2) Fault line isolation: According to the working process
MB is the sum of multiple lines to ground current, the parallel mentioned above, the fault line Line2 can be cut off by LCS2
index np is usually several times larger than original HCB. In and UFD2, but Line1 and Line3 are able to continue working
this case, it is 4. The direction index nd is only 1 because and connect via LCS1, UFD1, LCS3, UFD3. This means that
only unidirectional blocking capacity is required in proposed no matter on which line the fault occurs, the normal operation

TABLE I
C OMPARISON OF D IFFERENT M ULTIPORT HCB S OLUTIONS

Solution based Proposed


Component description Solution in [7] Solution in [8] Solution in [9] Solution in [10] Solution in [12]
on Typical HCB Solution
Number of LCS 3 3 2 6 3 3 3
Number of UFD 3 3 2 6 3 3 3
Number of MB 3 3 3 6 1 1 1
Number of MOV in MB 3m 3m 3m m m m m
Number of IGBT in MB 6ns np 3ns np 3ns np ns np ns np ns np ns np
Number of thyristor string 0 0 0 0 3 0 0
Number of diode string 0
√ 0√ 0 0
√ 3√ 6
√ 6√
Extensibility ×
1740 CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, VOL. 9, NO. 5, SEPTEMBER 2023

of other non-fault lines will not be terminated. However, in 15


iUFD2

Current (kA)
the solution of [7] and [8], all lines need to be cut off in some 10 iIGBT
special cases. iMOV
5

V. C ASE S IMULATION 0

In this section, to verify the feasibility of the proposed 2 2.002 2.004 2.006 2.008 2.01
(a)
Star-HCB, a three-terminal HVDC system is built in MAT-
LAB/Simulink platform, as shown in Fig. 6. The simulation 5 iLCS1

Current (kA)
iLCS2
parameters of the star-HCB and equivalent model of MMC iLCS3
are listed in Table II. The MMC model uses a simplified RLC 0
model to simulate its capacitor discharge. To make the result
of simulation more convincing, all parameters are chosen from −5
practical projects. The HiPak 5SNA 3000K452300 is applied 2 2.002 2.004 2.006 2.008 2.01
in the HBSM sub-module. Station A1 is seen as a regulating (b)
voltage station which balance the DC line voltage. Stations 10
iDiode1
A2 and A3 are set as active power regulation mode, which is

Current (kA)
iDiode2
−1500 MW and 3000 MW, respectively. 5 iDiode3

TABLE II
T HE PARAMETER OF MMC AND HCB 0

2 2.002 2.004 2.006 2.008 2.01


Parameter Value
DC cable inductance 0.22 mH/km (c)
DC cable resistance 0.014 mohm/km 2000
uC
DC cable capacitance 0.22 uF/km
Voltage (kV)

Arrester protective voltage in HCB 1500 kV


DC voltage ± 500 kV 1500
AC voltage 525 kV
Sub-module capacitor in HCB 2 mF
Arm inductor 75 mH
Arm resistance 0.147 ohm 1000
Limiting current inductor 100 mH 2 2.002 2.004 2.006 2.008 2.01
SRM Resistance 1500 ohm (d)

Fig. 12. Simulation curve of the proposed star-HCB. (a) Current of separate
components; (b) Current of the LCS; (c) Current of diodes; (d) Voltage of the
A. Fault Current Interruption capacitor.
In the simulation model, a pole-to-ground fault occurs
between stations A2 and A4 at t = 2 s. The fault current Finally, when the capacitance’s voltage charges to the
breaking waveforms of the star-HCB are illustrated in Fig. 12. threshold voltage of the arresters, the fault current will be
As can be seen from Fig. 12(a)(b), when a fault occurs, the consumed by the MOV.
current of UFD2 and LCS2 increase rapidly. Then, at t =
2.001 s, the fault is detected by the system and the IGBTs of B. Influence Degree of Branches Current
HBSM in the MB branch are immediately conducted. At the From the analysis of different parts of the star-HCB, the
same time, LCS2 turns off and UFD2 begins to open to force fault current breaking process could be obtained. However, for
the residual current transfer from UFD1 to the MB branch. the whole HVDC system, the impact of the proposed HCB on
From t = 2.001 to t = 2.003 s, the MB branch continues to the branches also needs to be evaluated.
conduct until the UFD2 recovers dielectric strength. During For the three terminals HVDC system simulation model, the
this period, current flow through LCS1 and LCS3 will be influence degree of lines’ current when the fault occurs can be
relatively lower. The D1 and D3 withstand the current flowing seen from Fig. 13. When the fault occurs at t = 2 s, because
into the artificial short-circuit point, which protects the LCSs
from the fault current.
At t = 2.003 s, the UFD2 opens completely. Considering iLine1
5
Current (kA)

the UFD2 recovers dielectric strength and can withstand the iLine2
iLine3
DC voltage, the IGBTs in the MB begin to turn off. Then, the 0
fault current transfers to the capacitors branch in the HBSM.
As described in Fig. 12(d), the voltage of the pre-charging −5
capacitors increases sharply. Since the capacitors have been
2 2.002 2.004 2.006 2.008 2.01
pre-charged, the sum of the capacitor’s voltage is higher than
the DC bus voltage of the converter station A1 , the fault Fig. 13. Current in each branch of the three-terminal MTDC system during
current drops immediately. fault current breaking process.
GUO et al.: RESEARCH ON A MULTIPORT PARALLEL TYPE HYBRID CIRCUIT BREAKER FOR HVDC GRIDS: MODELING AND DESIGN 1741

of the short-circuit point on Line2, the fault current of Line2 iLine1


rises faster than the other two branches. Then, 1 ms later, the 5

Current (kA)
iLine2
LCS2 turns off and a part of the fault current transfers to the iLine3
0
MB branch. The rest of the fault current flows through Line2
and decreases to zero through the freewheeling diode. The −5
current in this line can be maintained at a low level.
After Line2 is disconnected, the non-fault Line1 and Line3 1 1.5 2 2.5 3 3.5 4 4.5 5
have been separated from the fault. They will withstand the (a)
current caused by the artificial short-circuit point. However, iLine1
5

Current (kA)
due to the large smoothing reactor, the line inductance has iLine2
iLine3
a finite effect on the fault current. Compared with the series 0
type DCCB, the current in Line1 and Line3 will not increase
more. Since Line1 and Line3 are still connected to the system, −5
load current transfer will occur between stations A1 and A3 .
As can be seen from Fig. 13, after the fault current breaking 1 1.5 2 2.5 3 3.5 4 4.5 5
(b)
process, station A1 keeps supplying current to A3 .
The whole fault current breaking process takes about 9 ms. Fig. 15. Reclosing process. (a) transient fault; (b) permeant fault.
After the isolation, the other non-fault lines such as Line1 and
Line3 will work normally, which is one of the characteristics
of this proposed Star-HCB. the voltage balance capacitor can be pre-charged to save
charging time during the interruption. Thanks to the symmetric
C. Load Current Interruption structure, the LCS in this design is unidirectional and it can
Line2 is isolated in t = 2.001 s. As illustrated in Fig. 14, block any line’s short-circuit fault. Besides, the freewheeling
when the MB conducts, the line current will reverse. Different circuit will reduce energy consumption of the arrester. By
from fault interruption, the current of the isolated line will sharing the expensive IGBT and surge arrester string, the
decrease rapidly to zero. It is because the freewheeling circuit whole protection cost can be relatively low.
is in a high resistance state. The other two lines should For load current interruption, an active short-circuit mecha-
withstand the residual current. nism will force the line current decline to zero rapidly but also
affect other lines. This is still a problem that should be further
iLine1
5 studied. The coordination of DRM and UFD will help identify
Current (kA)

iLine2
iLine3 the type of the fault and complete the reclosing operation.
0 Extreme conditions will require the MB to conduct more time,
which may lead to exceeding the current withstanding capacity
−5
of semiconductor devices. This is a common problem the
2 2.002 2.004 2.006 2.008 2.01 integrated HCB should face.
Fig. 14. Load current interruption.
R EFERENCES
D. Reclosing Verification [1] Callavik M, Blomberg A, Häfner J, et al. “The hybrid HVDC breaker,”
This section will use two types of fault duration in Line2 to in ABB Grid Systems Technical Paper, vol. 361, pp. 143–152, 2012.
[2] W. Grieshaber, J. P. Dupraz, D. L. Penache, and L. Violleau, “Develop-
verify the reclosing strategy. Transient fault occurs in t = 2 s ment and test of a 120 kV direct current circuit breaker,” in Proceedings
and lasts for 200 ms, while a permeant fault will last all the of CIGRE Paris Session 2014, Paris, 2014, pp. 1–11.
time. As shown in Fig. 15(a), the freewheel current descends [3] W. D. Zhou, X. G. Wei, S. Zhang, G. F. Tang, Z. Y. He, J. C. Zheng, Y. H.
Dan, and C. Gao, “Development and test of a 200kV full-bridge based
to zero at t = 2.2 s since the fault is eliminated. At t = 2.5 s, hybrid HVDC breaker,” in Proceedings of 17th European Conference
the SRM opens and high resistance accesses to Line2. At t = on Power Electronics and Applications, Geneva, Switzerland, 2015, pp.
3 s, when UFD recloses, the current will not rise too much. It 1–7.
[4] L. Qi, X. Qu, X. Chen, L. Zhan, X. Zhang and X. Cui, “A low-loss
is a criterion to judge whether the fault is eliminated or not. and compact hybrid DC circuit breaker scheme using self-commutated
The SRM recloses at t = 3.5 s and the system is restored. semiconductor switch module,” CSEE Journal of Power and Energy
Permeant fault condition is shown in Fig. 15(b), the operation Systems, pp. 1–9, Sep. 2022.
sequence of SRM and UFD are the same. At t = 3 s, the fault [5] D. Van Hertem, O. Gomis-Bellmunt, and J. Liang, HVDC Grids: for
Offshore and Supergrid of the Future, New York, NY, USA: Wiley,
current rapidly reaches to a relatively low steady state. The 2016
protection system will identify a permeant fault. At t = 3.5 s, [6] M. K. Bucher, R. Wiget, G. Andersson, and C. M. Franck, “Mul-
the UFD can operate and the MB will be triggered again to titerminal HVDC networks—What is the preferred topology?” IEEE
Transactions on Power Delivery, vol. 29, no. 1, pp. 406–413, Feb. 2014.
isolate the fault line. [7] A. Mokhberdoran, D. Van Hertem, N, Silva, H. Leite, and A. Carvalho,
“Multiport hybrid HVDC circuit breaker,” IEEE Transactions on Indus-
VI. C ONCLUSION trial Electronics, vol. 65, no. 1, pp. 309–320, Jan. 2018.
[8] C. Y. Li, J. Liang, and S. Wang, “Interlink hybrid DC circuit breaker,”
In this paper, a novel multi-port HCB topology with star IEEE Transactions on Industrial Electronics, vol. 65, no. 11, pp. 8677–
type structure is presented. It uses a parallel structure; thus, 8686, Nov. 2018.
1742 CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, VOL. 9, NO. 5, SEPTEMBER 2023

[9] E. Kontos, T. Schultz, L. Mackay, L. M. Ramirez-Elizondo, C. Franck, Jin Zhu received his Ph.D. degree from the Insti-
and P. Bauer, “Multiline breaker for HVDC applications,” IEEE Trans- tute of Electrical Engineering, Chinese Academy of
actions on Power Delivery, vol. 33, no. 3, pp. 1469–1478, Jun. 2018. Sciences, Beijing, China, in 2015. He is presently
[10] R. Majumder, S. Auddy, B. Berggren, G. Velotto, P. Barupati, and T. working as a Senior Engineer in the Institute of
U. Jonsson, “An alternative method to build DC switchyard with hybrid Electrical Engineering, Chinese Academy of Sci-
DC breaker for DC grid,” IEEE Transactions on Power Delivery, vol. ences. His current research interests include control
32, no. 2, pp. 713–722, Apr. 2017. modeling and circuit design of modular converters
[11] S. Zhang, G. B. Zou, X. Y. Wei, and C. J. Sun, “Diode-bridge for high voltage applications.
multiport hybrid DC circuit breaker for multiterminal DC grids,” IEEE
Transactions on Industrial Electronics, vol. 68, no. 1, pp. 270–281, Jan.
2021.
[12] H. Q. Xiao, Z. Xu, L. Xiao, C. Gan, F. Xu, and L. S. Dai, “Components
sharing based integrated HVDC circuit breaker for meshed HVDC
grids,” IEEE Transactions on Power Delivery, vol. 35, no. 4, pp. 1856–
1866, Aug. 2020. Qingpeng Zeng received his B.S. degree from East
[13] H. Ye and W. Chen, “A novel hybrid DC circuit breaker based on pre- China Jiaotong University in 2019. He is presently
charged capacitors,” Proceedings of the CSEE, vol. 38, no. 20, pp. 5992– a doctoral student in the Institute of Electrical En-
6000, Oct. 2018. gineering, Chinese Academy of Sciences, and with
[14] T. K. Lan, Y. H. Li, and X. Z. Duan, “A novel voltage clamp type hybrid the University of Chinese Academy of Science.
direct current circuit breaker based on Thyristors,” Proceedings of the His current research interests include distribution
CSEE, vol. 39, no. 20, pp. 6159–6168, Oct. 2019. network protection and circuit breakers.
[15] J. Zhu, D. H. Liu, J. Y. Yin, and T. Z. Wei, “Research on hybrid DC
breaker based on modular cascaded structure,” Proceedings of the CSEE,
vol. 37, no. 5, pp. 1560–1567, Mar. 2017.
[16] G. R. Liu, F. Xu, Z. Xu, Z. R. Zhang, and G. Tang, “Assembly HVDC
breaker for HVDC grids with modular multilevel converters,” IEEE
Transactions on Power Electronics, vol. 32, no. 2, pp. 931–941, Feb.
2017.
[17] S. C. Li, C. H. Deng, Z. J. Long, F. Zheng, W. Ding, and Q. Zhou, “An Hao Xiao received the B.S. degree from Huazhong
inertial control method of doubly fed induction generators suitable for University of Science and Technology, Wuhan,
power grid with high wind power penetration,” Automation of Electric China, in 2009, and the Ph.D. degree in Electrical
Power Systems, vol. 40, no. 1, pp. 33–38, 135, Jan. 2016. Engineering from the Chinese Academy of Sciences,
[18] X. G. Wei, C. Gao, X. Luo, W. D. Zhou, and Y. N. Wu, “A novel design Beijing, China, in 2015. He is currently an Associate
of high-voltage DC circuit breaker in HVDC flexible transmission grid,” Professor with the Institute of Electrical Engineer-
Automation of Electric Power Systems, vol. 37, no. 15, pp. 95–102, Aug. ing, Chinese Academy of Sciences. His research
2013. interests include optimal operation and planning of
[19] J. Shu, S. L. Wang, and T. Q. Liu, “A soft reclosing model for hybrid power systems and application of artificial intelli-
DC circuit breaker in VSC-MTDC system,” in 2018 IEEE 4th Southern gence in power systems.
Power Electronics Conference (SPEC), 2018, pp. 1–5.
[20] F. Zhang, X. Yang, Y. Ren, Y. Chen, and R. F. Gou, “Voltage balancing
circuit for series-connected IGBTs in solid-state breaker,” Proceedings
of the CSEE, vol. 36, no. 3, pp. 656–663, Feb. 2016.
[21] J. Zhu, X. M. Guo, J. Y. Yin, Q. H. Huo, and T. Z. Wei, “Basic topology,
modeling and evaluation of a T-type hybrid DC breaker for HVDC grid,” Tongzhen Wei received his Ph.D. degree from
IEEE Transactions on Power Delivery, vol. 36, no. 5, pp. 2995–3004, the Institute of Electrical Engineering, Chinese
Oct. 2021, doi: 10.1109/TPWRD.2020.3031671. Academy of Sciences, Beijing, China, in 2004. He
[22] W. J. Wen, H. J. Liu, B. Li, P. Y. Li, N. Zhang, C. Gao, and C. S. is presently working as a Professor in the Insti-
Wang, “Novel reclosing strategy based on transient operating voltage in tute of Electrical Engineering, Chinese Academy
Pseudobipolar DC system with mechanical DCCB,” IEEE Transactions of Sciences, and with the University of Chinese
on Power Electronics, vol. 36, no. 4, pp. 4125–4133, Apr. 2021. Academy of Sciences. His current research interests
[23] J. K. Ke, X. G. Wei, B. J. Yang, Y. Gao, and Z. Y. He, “Control include power electronics, power storage, power
strategy of the full-bridge based hybrid DC breaker,” in 2015 IEEE quality analysis and mitigation.
First International Conference on DC Microgrids (ICDCM), Atlanta,
GA, 2015, pp. 315–320.
[24] J. H. He, Y. P. Luo, M. Li, Y. J. Zhang, Y. Xu, Q. F. Zhang, and G.
M. Luo, “A high-performance and economical multiport hybrid direct
current circuit breaker,” IEEE Transactions on Industrial Electronics,
vol. 67, no. 10, pp. 8921–8930, Oct. 2020.

Xinming Guo received his B.S. degree from China


University of Mining and Technology in 2017. He
is presently a doctoral student in the Institute of
Electrical Engineering, Chinese Academy of Sci-
ences, and with the University of Chinese Academy
of Sciences. His current research interests include
distributed generation and circuit breaker.

You might also like