Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
Evaluation of a Communication-Assisted
Overcurrent Protection Scheme for Photovoltaic
Based DC Microgrid
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
PV2
PV3
ESS
PV1
DC
DC
DC
DC
Load1 Load2 Load4
DC
DC
DC
Load3
DC
B1 B2 B3 B4
Zone 12
Zone 23
Zone 34
Zone 43
Zone 32
Zone 21
overcurrent relays is a challenging issue due to the high raising current flows from buses 1 to 2.
rate of DC fault currents. Thus, high-speed measuring and Intelligent electronic devices (IEDs) relays in combination
protective devices are required. Protection of the low voltage with solid-state circuit breakers can be used for the
DC microgrid using overcurrent relays has been discussed in implementation of this scheme. The selectivity and
[24] without considering the effects of distributed generations coordination problems of the overcurrent relays in the presence
(DGs) and operation modes of the microgrid on the system of the PV units are solved by implementing blocking and
protection. Integration of the DGs in the system affects the intertripping schemes using communication infrastructures of
amplitude and the direction of the fault current. This makes the the smart grids. Detailed descriptions of the proposed scheme
setting of the overcurrent relays more complex. The overcurrent are given in the next sections. However, before applying the
based schemes need to be modified in order to consider the proposed protection scheme for setting the overcurrent relays,
effects of the DGs on the DC microgrids protection. the possibility of the system protection by the overcurrent relays
This paper proposes a communication-based overcurrent needs to be analyzed.
protection scheme for DC microgrids with multiple DG units.
A. Evaluation the possibility of using the overcurrent
Prior to setting the relays, a new strategy is presented for
protection
evaluating the application of the proposed protection scheme
for the system protection. If the DC microgrid can be protected This paper proposes a comprehensive strategy as shown in
using the overcurrent scheme, the method determines which Fig. 2 for selecting a proper protection scheme for the DC
relays have to be set for protecting the microgrid in the grid- microgrid protection. The strategy evaluates the possibility of
connected and islanded operation modes. Otherwise, the using the overcurrent protection for every line section of the
differential-based protection scheme is suggested. The system. If a section can be protected using the proposed
proposed strategy is tested on a typical DC microgrid. overcurrent scheme, the strategy determines which relays
should to be set for the grid-connected and islanded operation
II. PROPOSED PROTECTION SCHEME modes of the microgrid. It is assumed that a relay at one end of
the section can send a trip command to the circuit breakers at
For protection of the LVDC distribution systems, the both sides of it. Thus, if all the faults inside the section can be
overcurrent-based protection is the first choice and the detected by one of the relays, the relay at the other side of the
differential protection is the last choice. The differential section does not require to be set. Therefore, the proposed
protection needs the synchronizing and comparing functions. strategy presents an economical approach to protect the system
Implementing these functions for the LVDC system with high with minimum number of the relays.
fault transients is difficult and expensive. Also, the differential A line section Lij can be protected using the overcurrent
protection does not provide the backup protection. On the other protection if at least one of the relays installed at both ends of
hand, it does not have complexities of the overcurrent the section detects all the possible faults occurring inside the
protection like coordination and setting issues. This paper section for every configuration of the PVs. Otherwise, the
proposes an overcurrent protection scheme that is based on the differential protection is proposed for the section. Also, the
use of the overcurrent relays for the protection of a radial LVDC relay Rij should not trip during the healthy operating condition
system with PV units. The proposed scheme uses directional of the system. Therefore, the maximum operation current Iopmaxij
overcurrent relays at both ends of every line section as shown sensed by the relay Rij should be calculated. In the normal
in Fig. 1. Every relay is represented by the symbol R with the operating condition of the grid, the current flowing in the
subscripts which show the forward direction of the relay. The direction of the relay Rij is obtained for every configuration of
directional overcurrent relays have a directional element which the PVs and its maximum is considered as Iopmaxij. In cases when
distinguishes the fault current direction. The relays can be set the PVs are in front of the relay, the current sensed by the relay
to trip for the fault currents flowing in the forward direction. is decreased. Therefore, these cases can be omitted from the
For example, the relay R12 trips for a forward fault that its calculation process of the maximum operation current.
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
No No
No t>tset2ij t>tset1ij
Is i<j ?
Is Is
No No
Iopmaxij<Ifm in(i-1, j-1)<Ifm inij Iset2ij cannot be defined Iopmaxij<Ifm in(i+1, j+1)<Ifm inij
? ?
Yes Yes
Block first-stage element
Trip CBij & CBj+1,i+1 Trip CBij & CBji of upstream relays
Iset2ij= Ifm in(i-1, j-1) Iset2ij= Ifm in(i+1, j+1)
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
[28]. This problem can be eliminated by installation of an III. SYSTEM MODELING AND CONTROL
automatic channel tester which is called “automatic checkback
This section describes modeling of PV units, energy storage
system”. This system checks the communication channel
systems, and the DC loads in the DC microgrid in order to do
periodically to ensure the integrity of the channel and provide
the fault analysis.
alarm in case of communication failure [28]–[32]. The time
interval of the automatic testing is usually determined by the A. Modeling of PV system
experience of the local utility and current practices, which is Fig. 8 shows a PV array which is connected to the LVDC
typically daily or weekly [28], [31]. Also, backup system through a DC/DC boost converter. Modeling of the PV
communication channels can be used to increase the arrays and control algorithms of the converter depend on the
effectiveness of the primary channel [33].
duration of the study. For long-term studies, especially in the
D. Fault analysis field of the operation and control of the AC/DC microgrids, a
As described earlier, minimum of the fault current within the detailed model of the PV arrays is proposed, which considers
primary zone of every relay should be calculated for setting the the ambient temperature and solar radiation. In the grid-
overcurrent relays. Thus, a detailed fault analysis is required connected mode, a maximum power point tracking (MPPT)
considering all possible configurations of the PVs and algorithm is utilized in the converter to deliver the maximum
grounding arrangements of the system. Required characteristics available power to the grid. In islanded mode, the converter
of the PV units for the analysis are their maximum capacities, works in voltage-mode control to support the balance of power
possible connection points, and control modes. and regulate the DC voltage [34], [35].
Different types of the DC faults are pole-to-pole and pole-to- In the literature which studies the protection of microgrids
ground faults. The faults in the DC systems are usually pole-to- and power quality issues, The PV arrays are modeled as a
ground faults. Pole-to-pole faults occur seldom in these systems constant DC voltage source interfaced with the grid through a
and have larger fault currents than the pole-to-ground faults. power-electronic converter. Fast control algorithms are
Therefore, pole-to-ground fault is considered as the fault type implemented to the converter to regulate current and voltage in
for calculation of minimum fault current. If the relays are set to grid-connected and islanded modes of operation so that the PV
the calculated value, they will operate for both types of the DC system acts like a constant power source. This assumption is
faults. In the pole-to-ground fault analysis, the grounding of the
possible because the system is studied during fault transients
DC system is an important issue because it provides the return
which are fractions of a second. In this short period of time, the
pass for the fault current. The fault current in an ungrounded
system does not increase. Thus, the relays cannot detect the ambient temperature and solar radiation is almost constant
pole-to-ground faults. In this paper, the midpoint of the VSC’s [36]–[40].
output capacitors is grounded through a resistor. However, This paper considers the PV array as a constant voltage
another grounding point is required for the islanded mode of the source because of very fast transients of the DC faults. Also,
microgrid. It is proposed to install a supercapacitor arrangement fast current and voltage mode control algorithms are applied to
with the schematic shown in Fig. 7 at bus 4. The arrangement the DC/DC boost converter. The converter is switched between
consists of two series equal capacitors (Cg) which their the two control modes depending on the system operating
midpoint is connected to the earth. modes.
The system is modeled and a pole-to-ground fault is placed The block diagram of the proposed control modes for the PV
at the end of the primary zone of the relay Rij. The fault current system is shown in Fig. 9. In current-mode control (CMC), the
sensed by the relay is obtained for every configuration of PVs injected current of the PV is measured and is compared with its
and its minimum is considered as Ifminij. The minimum fault reference value. The error signal is applied to the PI controller
current is calculated for the grid-connected and the islanded and PWM block generates the gate pulses according to the
modes separately. If there is a large difference in the minimum output of the PI block. In voltage-mode control (VMC), the
fault currents of two modes, different setting groups are defined reference value of the PV voltage is calculated by using (1), and
for the relays. In this case, a communication link is required then is compared with the PV measured voltage. The Saturation
between the isolating circuit breaker and the relays to choose an block imposes upper and lower bounds on the error signal.
appropriate setting group based on the microgrid operating ௗூುೇ
mode. ܸ = ܸ + 2ܴ ܫ + 2ܮ
(1)
ௗ௧
Capacitor Bank where ܸ is the PV reference voltage, ܸ is the grid
reference voltage, ܫ is the PV current, and ܴ and ܮ
are
+ the PV cable resistance and inductance, respectively.
Cg I PV
L R cPV L PV
c
PV Arrays
DC Bus 4 + +
C V PV V g
Cg
- -
-
Fig. 8. A boost DC/DC converter connected to the PV arrays
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
+
load to the system in regenerative mode of the load.
I PV K ( Z − 1)
-
The resistive load at the output of the buck converter is given
Saturation
TsZ by
Discrete Derivative
VPV (ೠ )మ
2 L PVc ܴௗ = (3)
ೞ
Fig. 9. The control system of PV
where Vout and Pconst are the output voltage of the regulator
and the constant power of the load, respectively.
B. Modeling of Energy Storage System
B4
Overall diagram of the energy storage system is shown in ESS Bus
Fig. 10. The energy storage is assumed as a constant DC voltage ESS Cable Controlled
DC
source which is connected to the ESS output bus through a bi- DC Switch
directional DC/DC converter shown in Fig. 11. A control
system similar to the voltage-mode control of the PV converter
Storage
Energy
regulates the output voltage of the ESS. The ESS can operate in Switching
both charging and discharging modes regarding the grid Logic
operating conditions. The ESS bus is connected to bus 4
Fig. 10. Overall diagram of the energy storage system
through a controlled switch. The control logic of the switch
must be able to distinguish two cases; the voltage instability Ls
because of the fault, and the voltage instability because of the
unbalance between the generation and the consumption. For the
ES
Cs
first case, the bus voltage returns inside its standard range after
Rs
isolating the faulty section. Thus, further presence of the energy
storage system in the network is not required. However, in the Fig. 11. Bi-directional converter connected to the ESS
second case, the energy storage must remain connected to the
grid to overcome the unbalance condition and to keep the
voltage in the standard range. A switching logic based on
successive closing and opening operations is proposed as (2) for [Vb4] NOT
T OR Output
the switch to determine whether the ESS must remain Interval Test
0.001 s
Monostable
connected to the grid or be disconnected after a short period of
time.
C-1ms-OC-1ms-OC (2)
Counter >=3
where closing and opening operations of the switch are
denoted by C and O, respectively. The switch closes when the AND
measured voltage exceeds the standard range. OC represents [CB] NOT
opening operation immediately followed by a closing operation
without any intentional time delay. The time interval between
two operations is 1ms. After the second opening operation, if Fig. 12. The proposed switching logic for ESS
the measured voltage still does not meet the standard range, the Constant Power Load (CPL)
unbalance condition is detected. The switch closes for the third
Lf
time and remains in that position. The energy storage
compensates the difference between the generation and the Cf +
DC Bus DC/DC Buck
Vout Rload
consumption and stabilizes the voltage. The block diagram of Rc
Converter
-
the proposed switching logic is shown in Fig. 12.
Input Filter
Rp
Fig. 13. The load model
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
TABLE II
the line L12 at a distance of 90 m far from the bus B2. The fault
FAULT CURRENTS AND MAXIMUM OPERATION CURRENTS SENSED BY THE current and the setting values of the relays R21 and R32 are
RELAYS R12, R23 , AND R34 IN THEIR PRIMARY ZONE shown in Fig. 14. The fault current exceeds the threshold setting
If (A) values of the relays and reaches to 586.2 A within 1ms.
Islanded Operation Grid Connected Operation Therefore, both relays see the fault. However, the blocking
PV at R12 R23 R34 R12 R23 R34 scheme as the applied coordination technique causes that the
None No LF No LF No LF 914 511 335.5
B1 No LF No LF No LF 956.5 520 350 upstream relay is blocked and only the downstream relay
B2 No LF No LF No LF 803 524.7 347 activates. Once the current exceeds 202.86 A, the fault is
B3 No LF No LF No LF 809 377.7 390 detected by the relay R21 and a blocking signal is sent to the
B1 (2 units) 332.4 244.2 151 934.12 504.26 328.8 first-stage element of the upstream relay R32. Therefore, when
B2 (2 units) NS 307.14 173.6 644.63 540.97 352 the fault current exceeds 325.5 A, the relay R32 will not operate
B3 (2 units) NS NS 342.46 699.8 287.2 423.5
B1 & B2 140.45 294.96 169.7 810.89 522.93 340.5
in its primary zone. A trip command is sent by the relay R21
B1 & B3 197.5 119.2 195.9 854.75 381.38 392.6 using intertripping scheme to the circuit breakers at both ends
B2 & B3 NS 141.9 278.1 708.86 403.64 401.7 of the line L12 to isolate the faulty section within 1ms. In cases
Iopmax (A) 128 85.5 43 138.64 96.2 53.75 where the relay R21 fails to operate, the relay R32 acts in its
* ‘No LF’ means that the load flow cannot be solved because of the limitations backup zone and the faulty section is isolated within 2ms.
of the network. The proposed protection scheme can be conducted for a DC
** ‘NS’ means that the fault cannot be sensed by the relays because of its
direction. microgrid with different configurations of the PVs and
grounding arrangements. Different setting groups will be
TABLE III presented and maybe the differential protection scheme is
FAULT CURRENTS AND MAXIMUM OPERATION CURRENTS SENSED BY THE proposed for some sections of the system.
RELAYS R21, R32 , AND R43 IN THEIR PRIMARY ZONE
In this paper, the radial configuration is considered because
If (A)
Islanded Operation Grid Connected Operation it is the most commonly used distribution system configuration.
PV at R21 R32 R43 R21 R32 R43 In a meshed DC network with different circuit loops and DG
None No LF No LF No LF NS NS NS connection points, implementing the proposed protection
B1 No LF No LF No LF NS NS NS scheme for the coordination of the overcurrent relays becomes
B2 No LF No LF No LF NS NS NS highly complex since a large combination of off-line studies is
B3 No LF No LF No LF NS 136 NS
B1 (2 units) 202.86 325.5 631.7 NS NS NS
required. In some cases it may be impossible to find an
B2 (2 units) 573.26 332.6 719.5 159.4 NS NS appropriate relay setting for all network and DG configurations.
B3 (2 units) 464.56 629.5 729.1 93.8 258.5 NS In those cases, the proposed protection scheme must be
B1 & B2 342.5 326.8 701.6 2.6 NS NS developed or the differential protection may be preferred for the
B1 & B3 327.8 498.8 709 NS 135.7 NS network protection. Meshed distribution grids especially from
B2 & B3 491.2 483 689.5 98 110.7 NS
DC type are seldom covered in literature and their Protection is
Iopmax (A) 53.3 95.2 0 74 115.3 0
out of the scope of this paper. It will be investigated in details
TABLE IV in future work.
SETTING PARAMETERS OF THE RELAYS
Islanded Operation Grid-Connected Operation
C. Comparison of the proposed scheme with the
Iset1ij (A) Iset2ij (A) Iset1ij (A) Iset2ij (A) schemes based on local measurements
R12 - - 644.63 287.2 As mentioned earlier, the proposed protection scheme
R23 - - 287.2 -
requires high-speed communication between the relays to
R34 - - 328.8 -
R21 202.86 - - - guarantee the selectivity and the relays coordination. Recently,
R32 325.5 202.86 - - some schemes have been presented in [41]–[44] for the fault
R43 631.7 325.5 - - detection in the DC microgrid which are based on local
measurements. They use first and second order derivatives for
the faults detection. Since they are based on local
measurements, the problems associated with the
communication channel such as delay and dependability are
avoided. However, the relays coordination, backup protection,
and grounding issues are not discussed in these schemes. Also,
first order and second order derivatives of the signal are very
sensitive to noise level and switching of power electronic
devices which may lead to unwanted tripping.
Meanwhile, a detailed analysis is presented to demonstrate
the necessity of the communication for the local measurement
based schemes as follows:
The local measurement based schemes presented in [41]–
Fig. 14. The fault current sensed by the relays R21 and R32 [44] are applied on the multi-terminal DC microgrids which
have a ring configuration. In this configuration, all the faults
occurred inside a cable are sensed by respective relays
It is assumed that the microgrid is operated in islanding mode
connected on both sides of the cable. However, if a radial
and both PV units are integrated in bus B3. A fault is placed on
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
configuration is considered for the DC microgrid, some faults ends of the section. Thus, a line section can be protected using
are sensed only by a relay at one end of the cable and the relay the overcurrent relays if at least one of the relays at both ends
at other end doesn’t sense the fault as shown in Tables II and III of the section detects all the possible faults occurring inside the
(NS states). Thus, each relay should have possibility of sending section for every configuration of the PVs. This is investigated
the trip command to the circuit breakers located at both sides of using a new proposed evaluation strategy. If a section can be
the cable to isolate the faulty section. Therefore, the protected using the proposed overcurrent protection, the
intertripping scheme and the related communication paths are strategy determines minimum number of the relays which have
required. to be set. Otherwise, the differential based protection is
Also, the method presented in [41] is applied on the test suggested for the section. Therefore, possibility of using the
system of this paper to show the blocking scheme importance cost-effective overcurrent protection is firstly analyzed by the
for the relays coordination. The fault current is sampled and its proposed strategy and the differential protection is considered
first order derivative is calculated. The sampling frequency is as the last option for the protection of a section.
chosen as 10 KHz and the second sample is utilized for tripping A sample DC microgrid is modeled in detail and the
decision. To simplify the analysis, it is assumed that the DC proposed method is validated.
microgrid is operated in grid-connected mode and only a PV TABLE V
can be integrated in buses 1-3. Minimum of the fault current FAULT CURRENT DERIVATIVE SENSED BY THE RELAYS R23 AND R34 IN THEIR
PRIMARY ZONE
derivative within the primary zone of every relay should be dI/dt (KA/s)
calculated. The results are shown in Table V for the relays R23 Grid Connected Operation
and R34 and the setting values have been highlighted. PV at R23 R34
Performance of the protection system is investigated by an None 581.1 476.1
example: The DC microgrid is assumed to be in grid-connected B1 576.1 461.8
B2 575.3 450.6
mode without any PV integration. A fault occurs at 0.3 of the
B3 567.8 506.3
line L34 far from the bus B3. The fault current derivatives sensed
by the relays R23 and R34 with their samples are shown in Fig.
15. The second sample is compared with the respective
threshold setting. The fault current derivative of the relay R34
(dIf34/dt) is 545.5 KA/s and the derivative of the fault current
sensed by the relay R23 (dIf23/dt) is 575.7 KA/s. Both values are
greater than the setting values of the relays. Thus, both relays
see the fault in their primary zones which it leads to their
simultaneous operation. Therefore, the blocking scheme is
required to overcome this coordination problem. On the other
hand, if the system is considered without the possibility of the
PVs integration, the relays R23 and R34 are set respectively at
581.1 KA/s and 476.1 KA/s as shown in Table V. dIf23/dt is less
than its respective setting value. Thus, the relay R23 doesn’t see Fig. 15. The fault current derivative sensed by the relays R23 and R34
the fault. Therefore, the faulty section is isolated by the relay
R34 operation without any coordination problem. VI. REFERENCES
As a result, in the presence of the DG units, implementing [1] A. T. Elsayed, A. A. Mohamed, and O. A. Mohammed, “DC
the blocking scheme is required for the relays coordination. microgrids and distribution systems: An overview,” Electr. Power
Syst. Res., vol. 119, pp. 407–417, 2015.
On the other hand, as described in Section II-C, the required [2] M. E. Baran and N. R. Mahajan, “DC distribution for industrial
parameters for the fault detection are measured and analyzed systems: opportunities and challenges,” IEEE Trans. Ind. Appl., vol.
locally and only the logical signals are exchanged between the 39, no. 6, pp. 1596–1601, 2003.
protective devices. Therefore, the communication delay will be [3] M. Brenna, G. C. Lazaroiu, G. Superti-Furga, and E. Tironi,
“Bidirectional Front End Converter for DG With Disturbance
insignificant by utilizing a proper communication technology. Insensitivity and Islanding-Detection Capability,” IEEE Trans.
Power Deliv., vol. 23, no. 2, pp. 907–914, 2008.
V. CONCLUSION [4] D. Georgakis, S. Papathanassiou, N. Hatziargyriou, A. Engler, and C.
Hardt, “Operation of a prototype microgrid system based on micro-
Overcurrent based protection is commonly applied for sources quipped with fast-acting power electronics interfaces,” in
distribution systems with radial structure. In LVDC systems, 2004 IEEE 35th Annual Power Electronics Specialists Conference,
the fault current has fast transients which make the coordination 2004, pp. 2521–2526.
[5] K. Mizuguchi, S. Muroyama, Y. Kuwata, and Y. Ohashi, “A new
of the overcurrent relays a challenging issue. By utilizing the decentralized DC power system for telecommunications systems,” in
communication infrastructures of the modern smart grids, the 12th International Conference on Telecommunications Energy, 1990,
blocking scheme is presented to overcome the coordination pp. 55–62.
problems. On the other hand, integration of the PV units in the [6] D. Salomonsson and A. Sannino, “Low-Voltage DC Distribution
System for Commercial Power Systems With Sensitive Electronic
grid affects the amplitude and the direction of the fault currents. Loads,” IEEE Trans. Power Deliv., vol. 22, no. 3, pp. 1620–1627,
Thus, the directional overcurrent relays are used at both ends of 2007.
the lines and their settings are upgraded for islanded and grid- [7] Y.-S. Oh, J. Han, G.-H. Gwon, D.-U. Kim, and C.-H. Kim,
connected modes of the microgrid. By implementing the “Development of Fault Detector for Series Arc Fault in Low Voltage
DC Distribution System using Wavelet Singular Value
intertripping scheme, each one of the relays at one end of a line Decomposition and State Diagram,” J. Electr. Eng. Technol., vol. 10,
section can send a trip command to the circuit breakers at both no. 3, pp. 766–776, 2015.
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2019.2923769, IEEE
Transactions on Smart Grid
10
[8] D. Hur and R. Baldick, “An Economic Analysis of Potential Cost [31] R. Patterson, E. Price, and M. Sanders, “Directional comparison
Savings from the Use of Low Voltage DC (LVDC) Distribution blocking system fundamentals,” in 2014 67th Annual Conference for
Network,” J. Electr. Eng. Technol., vol. 9, no. 3, pp. 812–819, 2014. Protective Relay Engineers, 2014, pp. 50–71.
[9] D. Afamefuna, I.-Y. Chung, D. Hur, J.-Y. Kim, and J. Cho, “A [32] R. Moxley and K. Fodero, “High-Speed Distribution Protection Made
Techno-Economic Feasibility Analysis on LVDC Distribution Easy: Communications-Assisted Protection Schemes for Distribution
System for Rural Electrification in South Korea,” J. Electr. Eng. Applications,” in 2006 Power Systems Conference: Advanced
Technol., vol. 9, no. 5, pp. 1501–1510, 2014. Metering, Protection, Control, Communication, and Distributed
[10] G. Byeon et al., “Complementary Power Control of the Bipolar-type Resources, 2006, pp. 123–138.
Low Voltage DC Distribution System,” J. Electr. Eng. Technol., vol. [33] Jiapeng Zhang and Yingfei Dong, “Preventing false trips of zone 3
10, no. 3, pp. 786–794, 2015. protection relays in Smart Grid,” Tsinghua Sci. Technol., vol. 20, no.
[11] A. Hooshyar and R. Iravani, “Microgrid Protection,” Proc. IEEE, vol. 2, pp. 142–154, Apr. 2015.
105, no. 7, pp. 1332–1353, Jul. 2017. [34] N. Eghtedarpour and E. Farjah, “Control strategy for distributed
[12] J. Yang, J. E. Fletcher, and J. O’Reilly, “Multiterminal DC Wind integration of photovoltaic and energy storage systems in DC micro-
Farm Collection Grid Internal Fault Analysis and Protection Design,” grids,” Renew. Energy, vol. 45, pp. 96–110, Sep. 2012.
IEEE Trans. Power Deliv., vol. 25, no. 4, pp. 2308–2318, 2010. [35] Duong Minh Bui, Keng-Yu Lien, and Shi-Lin Chen, “Investigate
[13] J. Yang, J. E. Fletcher, and J. O’Reilly, “Short-Circuit and Ground Dynamic and Transient Characteristics for Islanded/Grid-connected
Fault Analyses and Location in VSC-Based DC Network Cables,” Operation Modes of Microgrid and Develop a Fast-Scalable-
IEEE Trans. Ind. Electron., vol. 59, no. 10, pp. 3827–3837, 2012. Adaptable Fault Protection Algorithm,” in 12th IET International
[14] J. Candelaria and J.-D. Park, “VSC-HVDC system protection: A Conference on Developments in Power System Protection (DPSP
review of current methods,” in 2011 IEEE/PES Power Systems 2014), 2014, p. 8.1.4-8.1.4.
Conference and Exposition, 2011, pp. 1–7. [36] C. Yuan, M. A. Haj-ahmed, and M. S. Illindala, “Protection Strategies
[15] M. K. Bucher, M. M. Walter, M. Pfeiffer, and C. M. Franck, “Options for Medium-Voltage Direct-Current Microgrid at a Remote Area
for ground fault clearance in HVDC offshore networks,” in 2012 Mine Site,” IEEE Trans. Ind. Appl., vol. 51, no. 4, pp. 2846–2853,
IEEE Energy Conversion Congress and Exposition (ECCE), 2012, Jul. 2015.
pp. 2880–2887. [37] M. Carminati, S. Grillo, L. Piegari, E. Ragaini, and E. Tironi, “Fault
[16] P. Kundur, N. J. Balu, and M. G. Lauby, Power system stability and protection analysis in low voltage DC microgrids with PV
control. McGraw-Hill, 1994. generators,” in 2015 International Conference on Clean Electrical
[17] R. K. Mallick and R. K. Patnaik, “Fault analysis of voltage-source Power (ICCEP), 2015, pp. 184–191.
converter based multi-terminal HVDC transmission links,” in 2011 [38] R. Majumder, M. Dewadasa, A. Ghosh, G. Ledwich, and F. Zare,
International Conference on Energy, Automation and Signal, 2011, “Control and protection of a microgrid connected to utility through
pp. 1–7. back-to-back converters,” Electr. Power Syst. Res., vol. 81, no. 7, pp.
[18] J. Yang, J. Zheng, G. Tang, and Z. He, “Characteristics and Recovery 1424–1435, Jul. 2011.
Performance of VSC-HVDC DC Transmission Line Fault,” in 2010 [39] H. Hooshyar and M. E. Baran, “Fault Analysis on Distribution
Asia-Pacific Power and Energy Engineering Conference, 2010, pp. Feeders With High Penetration of PV Systems,” IEEE Trans. Power
1–4. Syst., vol. 28, no. 3, pp. 2890–2896, Aug. 2013.
[19] S. Dhar, R. K. Patnaik, and P. K. Dash, “Fault Detection and Location [40] A. P. Moura, J. A. P. Lopes, A. A. F. de Moura, J. Sumaili, and C. L.
of Photovoltaic Based DC Microgrid Using Differential Protection Moreira, “IMICV fault analysis method with multiple PV grid-
Strategy,” IEEE Trans. Smart Grid, pp. 1–1, 2017. connected inverters for distribution systems,” Electr. Power Syst.
[20] S. D. A. Fletcher, P. J. Norman, K. Fong, S. J. Galloway, and G. M. Res., vol. 119, pp. 119–125, Feb. 2015.
Burt, “High-Speed Differential Protection for Smart DC Distribution [41] A. Meghwani, S. C. Srivastava, and S. Chakrabarti, “A Non-unit
Systems,” IEEE Trans. Smart Grid, vol. 5, no. 5, pp. 2610–2617, Sep. Protection Scheme for DC Microgrid Based on Local
2014. Measurements,” IEEE Trans. Power Deliv., vol. 32, no. 1, pp. 172–
[21] J.-D. Park and J. Candelaria, “Fault Detection and Isolation in Low- 181, 2017.
Voltage DC-Bus Microgrid System,” IEEE Trans. Power Deliv., vol. [42] D. D. Patil and S. Bindu, “Real time protection technique for DC
28, no. 2, pp. 779–787, Apr. 2013. microgrid using local measurements,” in 2018 Technologies for
[22] M. E. Baran and N. R. Mahajan, “Overcurrent Protection on Voltage- Smart-City Energy Security and Power (ICSESP), 2018, pp. 1–6.
Source-Converter-Based Multiterminal DC Distribution Systems,” [43] S. Som and S. R. Samantaray, “Efficient protection scheme for low-
IEEE Trans. Power Deliv., vol. 22, no. 1, pp. 406–412, Jan. 2007. voltage DC micro-grid,” IET Gener. Transm. Distrib., vol. 12, no. 13,
[23] S. R. B. Vanteddu, A. Mohamed, and O. Mohammed, “Protection pp. 3322–3329, 2018.
design and coordination of DC Distributed Power Systems [44] A. Meghwani, S. C. Srivastava, and S. Chakrabarti, “Local
Architectures,” in 2013 IEEE Power & Energy Society General measurement-based technique for estimating fault location in multi-
Meeting, 2013, pp. 1–5. source DC microgrids,” IET Gener. Transm. Distrib., vol. 12, no. 13,
[24] D. Salomonsson, L. Soder, and A. Sannino, “Protection of Low- pp. 3305–3313, 2018.
Voltage DC Microgrids,” IEEE Trans. Power Deliv., vol. 24, no. 3,
pp. 1045–1053, 2009.
[25] P. Kansal and A. Bose, “Smart grid communication requirements for Arash Shabani received the B.Sc. degree in electrical
the high voltage power system,” in 2011 IEEE Power and Energy engineering from Islamic Azad University, Iran, in
Society General Meeting, 2011, pp. 1–6. 2006, and the M.Sc. and Ph.D. degrees in electrical
[26] “Design Best Practices for Latency Optimization,” White Paper, engineering from University of Zanjan, Zanjan, Iran,
CISCO, Financial Services Technical Decision Maker. pp. 1–8, 2007. in 2008 and 2018, respectively. He is currently an
[27] A. A. S. Emhemed, K. Fong, S. Fletcher, and G. M. Burt, “Validation Assistant Professor with the Department of Electrical
of Fast and Selective Protection Scheme for an LVDC Distribution Engineering, Hidaj Branch, Islamic Azad University,
Network,” IEEE Trans. Power Deliv., vol. 32, no. 3, pp. 1432–1440, Hidaj, Iran. His research interests include DC grids
Jun. 2017. protection and smart grids.
[28] S. Ji, Y. I. Lu, M. Gregg, and J. Murphy, “Analysis of the
misoperation of DCB scheme for transmission line protection,” in KazemMazlumi(M’09) was born in Tehran, Iran, in
20th Annual Georgia Tech Fault and Disturbance Analysis 1976. He received the B.Sc. degree in Electrical
Conference, 2017, pp. 1–9. Engineering from Amirkabir University of
[29] D. Lin, G. Gunderson, J. Grimm, M. Weir, and R. Soper, Protection Technology, Tehran, Iran, in 2000, the M.Sc. degree
System Misoperations. MRO Protective Relay Subcommittee, 2016. from Sharif University of Technology, Tehran, Iran,
[30] M. P. Sanders et al., “Special considerations in applying power line in 2003, and the Ph.D. degree from Amirkabir
carrier for protective relaying - IEEE power systems relaying University of Technology, in 2009. He is currently an
committee special paper - relaying communications subcommittee, Associate Professor with University of Zanjan,
working group H9, 1-5-04,” in 57th Annual Conference for Zanjan, Iran. His research interests include power
Protective Relay Engineers, 2004, 2004, pp. 247–281. system protection and smart power grids.
1949-3053 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.