Professional Documents
Culture Documents
Research Article
Mohammed Elgeziry1, Mahmoud Elsadd2, Nagy Elkalashy2, Tamer Kawady2 , Abdel-Maksoud Taalab2,
Mohamed A. Izzularab2
1Egyptian New and Renewable Energy Authority, Cairo, Egypt
2ElectricalEngineering Department, Minoufiya University, 32511, Shebin El-Kom, Egypt
E-mail: t_kawady@ieee.org
Abstract: High-voltage direct current (HVDC) transmission systems are nowadays ideal candidates for interconnecting
renewable energy resources to the electrical grids. This study presents a communication-less protection scheme for HVDC
transmission systems with a multi-terminal voltage source converter (VSC). The existence of a tie-busbar is also considered,
which represents a challenge for protection selectivity functions without the aid of a communication channel. The proposed
scheme identifies the faulted segment on either a DC busbar or a line segment based on monitoring the calculated rate of
change of the current-to-voltage ratio. This criterion is sensitive to detect the faults as the current increases rapidly in a few
milliseconds, while the voltage decreases in the same time frame remarkably. Once the fault detection criterion is satisfied, the
faulted section can be identified by checking the summation and direction of all branch currents at each busbar individually
without utilising communication links. For investigation purposes, the proposed scheme is tested via a four-terminal HVDC
system with two tie-busbars. Different simulation cases are evaluated with a variety of fault conditions using MATLAB/
SIMULINK. The results corroborate the reliability, security, and efficacy of the proposed protection scheme for multi-terminal
HVDC transmission systems.
IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042 3033
© The Institution of Engineering and Technology 2019
a communication channel. The proposed scheme provides the main
protection for busbars and transmission lines based on local
measuring of the busbar voltage and branch currents to calculate
the rate of change of the current–voltage ratio for each branch. The
scheme can discriminate between busbar and line faults
successfully. After the detection stage, the faulted segment is
identified based on the summation and direction of all branch
currents connected to the busbar. As compared with other past
travelling wave-based schemes, the proposed scheme overcomes
its most common problems such as the possible mis-coordination
of the protective devices with the existing of tie-busbars. On the
other hand, the reliability of the proposed scheme is enhanced
remarkably owing to the non-communication operation. Moreover,
its security against mal-operation in transient cases is guaranteed
via two security conditions depending on the sign of the rate of
change of both current and voltage signals. Also, its immunity
against noisy signals is verified with robust three-sample
windowing using a reasonable sampling frequency. This facilitates
its implementation and utilisation in the field successfully. The
proposed scheme is tested with a four-terminal HVDC grid with a
symmetrical monopole configuration with two tie-busbars. A
detailed analysis of different faults and abnormal conditions is
carried out using MATLAB/SIMULINK. The results confirm the
efficacy and practicality of the presented scheme.
3034 IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042
© The Institution of Engineering and Technology 2019
selected threshold value, the detection stage is satisfied. This
detection phase is issued based on the first propagated surge
created by the fault event. Hence, the fault detection process is
completely achieved before the travelling wave reflection stage.
N−1
If = ∑ In (2)
n=1
IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042 3035
© The Institution of Engineering and Technology 2019
station sides. This time delay must be profiled according to the
following constraints:
• The forced delay time must be more than the clearing time of
the fault from the tie-busbar relaying point (i.e. 1.25 ms).
• The forced delay time in addition to the blocking time of the
DCCB of the faulted line must be lower than the delay time of
the backup protection scheme (i.e. 3 ms).
3036 IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042
© The Institution of Engineering and Technology 2019
4.1 Load variation impacts
Investigating the impacts of load variations is essential to
determine the sufficient threshold level of d´Ʊ to avoid false
operation during normal conditions. A sudden increase in the load
from 0.15 to 1.15 p.u. resulted in a maximum value of d´Ʊ of 205
p.u. as shown in Figs. 6a and b.
IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042 3037
© The Institution of Engineering and Technology 2019
time line of the proposed protection scheme, where d´Ʊ reached
the threshold value after 50 μs from the fault instant at 1.5 s. The
protective relay takes only 0.2 ms for executing the algorithm and
initiates a trip signal at 1.50025 s to the solid-state DCCB to
interrupt the fault within 1 ms at a time of 1.50125 s. Fig. 11c
shows the measuring currents at substation S2, where there is no
current between stations S2 and S1 due to the operation of
DCCB21. As noted from the results, clearing the fault did not
affect the operation of station S2, which was continued to operate
near its normal operation in the inverting mode. The currents in the
other lines IL26 and IL24 were increased to maintain the required
current for station S2. Fig. 11d illustrates the status of all station
currents keeping their original current levels before the fault.
As depicted from Fig. 12, the voltages of both DC and AC sides
of substation S1 were insignificantly impacted with the applied
fault at F1. Hence, the capability of the proposed protection
scheme to identify and isolate the faulted line is verified without
Fig. 7 System performance under the pole to earth fault at F1 utilising communication facilities.
(a) Station1 AC voltage, (b) Station1 AC current, (c) B1 branches currents, (d) B1-DC
voltage 5.2 Faults close to the tie-busbar
For a fault at F5 on line L53 close to the tie-busbar, the value of d
´Ʊ for the protective relay on the tie-busbar reaches the threshold
value within 20 μs from the fault instant as shown in Fig. 13a.
Then, a tripping signal was issued to the DCCB53 to isolate the
fault from the tie-busbar side as shown in Fig. 13c after the
relaying time of 0.2 ms. Therefore, the fault was blocked from the
B5 side within 1.22 ms (considering a solid-state DCCB with a
blocking time of 1 ms). For the other side of L53, all branches
connected with the busbar B3 fed the fault through the segment
L53. d´Ʊ reached the threshold value within 0.3 ms after the fault
instance as shown in Fig. 13a. Then, the corresponding protective
relay detected the fault on line segment L53 from busbar B3 within
0.2 ms. Accordingly, a tripping signal was issued to DCCB35 to
block the gate signal of the insulated-gate bipolar transistors
feeding the fault from B3 side within 1 ms. Hence, the fault was
detected and isolated within 1.5 ms as depicted in Fig. 13d.
The results visualised a successful detection and isolation of the
faulted line from both line sides without utilising communication
Fig. 8 d´Ʊ values in case of the pole to earth fault at F1 facilities. Then, the related stations maintained their normal
(a) d´Ʊ for B1, (b) d´Ʊ for B2, (c) d´Ʊ for B3, (d) d´Ʊ for B4 operation as demonstrated in Fig. 14. On the other hand, d´Ʊ of
other branches connected to the tie-busbar (L15, L26, and L46) did
not reach the threshold level as shown in Fig. 13a with the
originally designed DC reactors at the tie-busbar. By utilising the
refined DC reactors at the tie-busbar, d´Ʊ of the other healthy
branches connected to the tie-busbar (L15, L26, and L46) did not
reach the threshold level as shown in Fig. 13b. Fig. 14a shows the
instantaneous current distribution after the fault instant, where all
branches connected with the tie-busbar feed the fault. The
identification criterion is achieved for L53, L35, and L26. After the
fault clearing by blocking DCCB53 and DCCB35, the system
Fig. 9 d´Ʊ values in case of the pole to earth fault at F1 for the tie-busbar restored its normal operation with the current distribution shown in
Fig. 14b. Although the summation criterion is achieved at L26, the
within the maximum allowable time for the main protection fault detection criterion was not satisfied as the values of d´Ʊ did
scheme (2 ms after the fault instant) as shown in Figs. 8c and d. not reach the threshold value as shown in Fig. 13a. Hence, line L26
Similar situations were realised as well for pole-to-pole faults. was still connected and successful relaying coordination was
Table 3 summarises the resulting d´Ʊ under different fault cases. achieved under this critical case.
As an example, d´Ʊ reached the setting limit within 70 and 600 μs
for fault at F2 on the line L24 for both sides of the faulted line. 5.3 Faults on the tie-busbar
Similar results were obtained for faults at F3, F4, F5, and F6 as
well. Thus, the suitability of the selected setting edge for d´Ʊ was For the fault at F6 on tie-busbar B5, d´Ʊ for all branches connected
verified. to tie-busbar B5 exceeded the threshold value within 70 μs from
the fault instant as shown in Fig. 15a. After the relaying time (0.2
5 Performance evaluation of the proposed ms), the busbar protective relay detected the fault and identified it
as a busbar one, where all currents are incoming towards B5.
protection scheme Therefore, the corresponding protective relay blocked all DCCBs
5.1 Faults at station terminals connected to B5 (DCCB56, DCCB51, and DCCB53). Thus, the
fault was blocked from B5 within 1.27 ms considering the DCCB
As illustrated in Fig. 11a, a pole-to-ground fault at F1 on line L12 blocking time of 1 ms.
at 1.5 s. The role of the protection scheme is to detect the fault and In this case, the identification criterion is achieved for L35 and
isolate faulty line L12 only. Then, the DC system should be L26. As shown in Fig. 15b, d´Ʊ reached the threshold value for
restored to its normal operation after clearing the fault. As station L35 within 0.8 ms and for L26 within 1.2 ms before clearing the
S1 still has its rated value, currents IL13 and IL15 are increased to faulted tie-busbar. Therefore, the protective relays installed on B2
compensate for the current of the isolated line. Fig. 11b shows the
3038 IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042
© The Institution of Engineering and Technology 2019
and B3 detected the fault and identified the faulted line wrongly protective relay detects the fault and identifies the busbar fault as
and blocked the DCCB26 and DCCB35, respectively, as discussed all current directions are incoming towards B5.
in Section 2.3. Then, the refined DC reactors at tie-busbar The fault is cleared within 1.27 ms. On the other hand, as
overcome this problem. Fig. 15c illustrates the recorded d´Ʊ values shown in Fig. 15d, d´Ʊ reached the threshold value for L35 within
for all branches connected at tie-busbar where it reaches the 1.3 ms and for L26 within 2.5 ms. Therefore, the fault was cleared
threshold value within 70 μs from the fault instant. The busbar before the protective relays at B2 and B3 detect the fault. As shown
in Fig. 16a, the busbar protection algorithm detected the fault and
identified a busbar fault condition blocking all DCCBs connected
to the busbar B5 (DCCB56, DCCB51, and DCCB53). Then, the
system restored its normal operation with the resulting current
distribution shown in Fig. 16b.
IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042 3039
© The Institution of Engineering and Technology 2019
Fig. 14 Current distribution under fault F5 closed to the tie-busbar B5
(a) Current distribution during the fault at F5, (b) Current distribution after blocking
the fault at F5
Fig. 11 Evaluation of the proposed protection scheme under fault case
‘F1’
(a) B1 branch currents, (b) Time line of protection scheme operation, (c) B2 branches
currents, (d) Stations DC currents
Fig. 12 AC and DC voltages profile under F1 fault Fig. 15 Evaluation of the proposed protection scheme under fault F6 on
(a) DC voltage at B1, (b) Station 1 AC voltages the tie-busbar B5
(a) d´Ʊ for all branches connected with B5 and B6, (b) d´Ʊ for all branches connected
with B5 and B6 from station sides, (c) d´Ʊ for all branches connected with B5 and B6
with refined reactors, (d) d´Ʊ for all branches connected with B5 and B6 from station
sides with refined reactors
7 References
[1] Mitra, B., Chowdhury, B., Manjrekar, M.: ‘HVDC transmission for access to
off-shore renewable energy: a review of technology and fault detection
techniques’, IET Renew. Power Gener., 2018, 12, (13), pp. 1563–1571
[2] Kalair, A., Abas, N., Khan, N.: ‘Comparative study of HVAC and HVDC
transmission systems’, Renew. Sustain. Energy Rev., 2016, 59, (1), pp. 1653–
1675
[3] Leterme, W., Azad, S., Hertem, D.: ‘HVDC grid protection algorithm design
in phase and modal domains’, IET Renew. Power Gener., 2018, 12, (13), pp.
1538–1546
[4] Yang, J., Fletcher, J., Reilly, J.: ‘Multi-terminal DC wind farm collection grid
internal fault analysis and protection design’, IEEE Trans. Power Deliv.,
2010, 25, (4), pp. 2308–2318
Fig. 17 Evaluation of the proposed protection scheme under fault F1 with [5] Bucher, M., Franck, C.: ‘Analytic approximation of fault current contributions
fault resistance 150 Ω from capacitive components in HVDC cable networks’, IEEE Trans. Power
Deliv., 2015, 30, (1), pp. 74–81
(a) d´Ʊ values for all branches connected with B1, (b) d´Ʊ values for all branches [6] Ahmed, W., Manohar, A.: ‘DC line protection for VSC-HVDC system’. Proc.
connected with B2, (c) Currents values for all branches connected with B1, (d) IEEE Int. Conf. on Power Electronics, Drive and Energy Systems, Bengaluru,
Operating times of the protection scheme India, 16–19 December 2012
[7] Candelaria, J., Park, J.: ‘VSC-HVDC system protection: a review of current
methods’. IEEE/PES Proc. Power Systems Conf. and Exposition (PSCE),
Table 4 Time for d’Ʊ to reach the threshold level by utilising Phoenix, AZ, U.S.A. 20–23 March 2011
the refined DC reactors [8] Fletcher, S., Norman, P., Galloway, S., et al.: ‘Optimizing the roles of unit and
Fault case Line Time in µs for solid Time in µs for high non-unit protection methods within DC microgrids’, IEEE Trans. Smart Grid,
2012, 3, (4), pp. 2079–2087
faults resistive faults [9] Abu-Elanien, A., Elserougi, A., Abdel-Khalik, A., et al.: ‘A differential
F5 L35 300 500 protection technique for multi-terminal HVDC’, Electr. Power Syst. Res.,
2016, 130, (1), pp. 78–88
L53 50 800 [10] Li, C., Gole, A., Zhao, C.: ‘A fast DC fault detection method using DC
L26 5000 NS reactor voltages in HVDC grids’, IEEE Trans. Power Deliv., 2018, 33, (5), pp.
F6 B5 100 100 2254–2264
[11] Tzelepis, D., Dysko, A., Fusiek, G., et al.: ‘Single-ended differential
L35 1300 NS protection in MTDC networks using optical sensors’, IEEE Trans. Power
L26 2500 NS Deliv., 2017, 32, (3), pp. 1605–1615
[12] Zheng, X., Tai, N., Yang, G., et al.: ‘A novel protection scheme for HVDC
F7 L26 30 125 transmission line’. Proc. Int. Conf. on Advanced Power System Automation
L62 480 800 and Protection, Beijing, China, 2011, pp. 341–345
[13] Zheng, J., Wen, M., Chen, Y., et al.: ‘A novel differential protection scheme
NS, the detection criterion was not satisfied. for HVDC transmission lines’, Int. J. Electr. Power Energy Syst., 2018, 94,
(1), pp. 171–178
[14] Yang, J., Fletcher, J., Reilly, J.: ‘Multiterminal DC wind farm collection grid
internal fault analysis and protection design’, IEEE Trans. Power Deliv.,
2010, 25, (4), pp. 2308–2318
[15] Farhadi, M., Mohammed, O.: ‘Protection of multi-terminal and distributed
DC systems: design challenges and techniques’, Electr. Power Syst. Res.,
2016, 143, (2), pp. 715–727
[16] Abu-Elanien, A., Abdel-Khalik, A., Massoud, A., et al.: ‘A non-
communication based protection algorithm for multi-terminal HVDC grids’,
Electr. Power Syst. Res., 2017, 144, (1), pp. 41–51
[17] Liu, J., Tai, N., Fan, C.: ‘Transient-voltage based protection scheme for DC
line faults in multi-terminal VSC-HVDC system’, IEEE Trans. Power Deliv.,
2016, 32, (3), pp. 1483–1494
[18] Torres-Olguin, R., Kristian, H.: ‘Inverse time overcurrent protection scheme
Fig. 18 Variation of d´Ʊ under a fault at F5 on L35 close to B5 with fault for fault location in multi-terminal HVDC’. Proc. IEEE Eindhoven Power
resistance 70 Ω Tech Conf., Holland, July 2015
[19] Azad, S., Hertem, D.: ‘A fast local bus current-based primary relaying
algorithm for HVDC grids’, IEEE Trans. Power Deliv., 2017, 32, (1), pp.
6 Conclusion 193–202
[20] Li, R., Xu, L., Yao, L.: ‘DC fault detection and location in meshed multi-
A new communication-less protection technique for MT HVDC terminal HVDC systems based on DC reactor voltage change rate’, IEEE
transmission systems has been proposed with an applicable Trans. Power Deliv., 2017, 32, (3), pp. 1516–1526
sampling rate. The proposed scheme has detected the fault via [21] Dekerf, K., Srivastava, K., Reza, M., et al.: ‘Wavelet-based protection
monitoring the calculated rate of change of the current–voltage strategy for DC faults in multi-terminal VSC HVDC systems’, IET Gener.
Transm. Distrib., 2011, 5, (4), pp. 496–503
ratio at all branches at each substation. The proposed scheme has [22] Cheng, J., Guan, M., Tang, L., et al.: ‘Paralleled multi-terminal DC
identified the faulted segment whether it is a busbar or a line fault. transmission line fault locating method based on travelling wave’, IET Gener.
The faulted section identification criterion has been realised by the Transm. Distrib., 2014, 8, (12), pp. 2092–2101
summation and the direction of the currents of all branches at each [23] Zou, G., Feng, Q., Huang, Q., et al.: ‘A fast protection scheme for VSC based
multi-terminal DC grid’, Int. J. Electr. Power Energy Syst., 2018, 98, (1), pp.
busbar individually without utilising communication links. The 307–314
security of the proposed protection scheme is enhanced to avoid [24] Cwikowski, O., Barnes, M., Shuttleworth, R.: ‘The impact of traveling waves
unnecessary tripping decision during the fault transient. Moreover, on HVDC protection’. Proc. IEEE PEDS, Sydney, Australia, June 2015
the impacts of tie-busbars are perfectly eliminated by either [25] Liu, X., Osman, A., Malik, O.: ‘Hybrid traveling wave/boundary protection
for monopolar HVDC line’, IEEE Trans. Power Deliv., 2009, 24, (2), pp.
delaying the blocking signal of the DCCBs of the branches 569–578
connected to the tie-busbar or by refining the value of the DC [26] Leterme, W., Ahmed, N., Beerten, J., et al.: ‘A new HVDC grid test system
reactors at the tie-busbar side. The second method has been for HVDC grid dynamics and protection studies in EMT-type software’. Proc.
IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042 3041
© The Institution of Engineering and Technology 2019
11th IET Int. Conf. on AC and DC Power Transmission, Birmingham, UK, [30] Mobarrez, M., Kashani, M., Bhattacharya, S., et al.: ‘Comparative study of
2015 DC circuit breakers using real time simulations’. 40th Annual Conf. Proc.
[27] Abu-Elanien, A.: ‘Protection of star connected multi-terminal HVDC systems IEEE Industrial Electronics Society, USA, November 2014, pp. 3736–3742
with offshore wind farms’. Proc. IEEE 12th Int. Conf. on Compatibility and [31] Abdullah, I., Amneh, A.: ‘Optimal length determination of the moving
Power Electronics and Power Engineering, Doha, Qatar, 2018 average filter for power system applications’, Int. J. Innov. Comput. Inf.
[28] Zhu, K., Lee, W., Pong, P.: ‘Fault-line identification of HVDC transmission Control, 2015, 11, (2), pp. 691–705
lines by frequency-spectrum correlation based on capacitive coupling and [32] Bob, M.: ‘Introduction to digital signal processing’. First published 2000,
magnetic field sensing’, IEEE Trans. Magn., 2018, 54, (11), Article no. School of Information System, University of East Anglia, (Great Britain),
4001805, https://ieeexplore-ieee-org.sdl.idm.oclc.org/xpl/tocresult.jsp? (MPG Books), Bodmin, ISBN: 0750650486
isnumber=8495102
[29] Yang, Q., Blond, S., Aggarwal, R., et al.: ‘New ANN method for multi-
terminal HVDC protection relaying’, Electr. Power Syst. Res., 2017, 148, (1),
pp. 192–201
3042 IET Renew. Power Gener., 2019, Vol. 13 Iss. 16, pp. 3033-3042
© The Institution of Engineering and Technology 2019