You are on page 1of 6

Impact of VSC HVdc on AC System Generation

S Arunprasanth*, U D Annakkage†, C Karawita‡, R Kuffel*

*RTDS Technologies Inc., Canada, †University of Manitoba, Canada, ‡TransGrid Solutions Inc., Canada
arunprasanth@ieee.org, udaya@ieee.org, ckarawita@tgs.biz, rk@rtds.com

Keywords: High-voltage direct current, modular multilevel the VSC terminal and also when the VSC is connected at a
converter, real-time digital simulator, short circuit ratio, distance from the generator. The simulation studies were
transient stability. performed using the electro-magnetic transient (EMT) model
of power system developed on the real-time digital simulator
Abstract (RTDS). The simulation results are presented to show that the
presence of MMC-VSC system helps to extend the CCT of
This paper investigates the impact of different control modes the synchronous generator that is connected to the power
of VSC HVdc to the transient stability of power systems. system.
VSC HVdc offers fast bi-directional power control in addition
to fast ac voltage control. This feature is utilized in this study 2 Power System Stability
to enhance the transient stability of a conventional generator
in a power system. Simulations are carried-out for three Although, the penetration of renewable energy generations
scenarios: (i) the generator is connected to the VSC terminal, such as wind and solar is increasing, many utilities around the
(ii) the generator is connected at a distance from the VSC world depend on conventional electricity generations by large
terminal, and (iii) the VSC is connected at a distance from the scale synchronous machines. Typically, the system frequency
generator terminal. The critical fault clearing time is used as is governed by these synchronous machines. Therefore,
the indicator of the stability of power system. In each maintaining synchronism of these generators is very
scenario, effects of both ac voltage control and reactive power important for the stable operation of power system.
control are studied. This paper shows that the transient
stability of power system can be improved by having a VSC The transient stability of a power system is defined as the
with fast ac voltage control near to synchronous generators. ability of a power system to remain in stable operation after
being subjected to transient disturbances such as faults [2].
1 Introduction Typically, the transient stability of a power system is defined
in terms of the CCT of the power system. During a fault in a
At present, power systems are operated close to the stability power system, the synchronous generators close to that fault
limits due to the high electricity demand and penetration of acquire kinetic energy. The ability of those generators to stay
renewable energy generations. Heavily loaded power systems in synchronism after clearing the fault depends on the speed
will have small critical fault clearing time (CCT) and may at which the acquired kinetic energy is transferred to the ac
experience transient stability issues if fast protection actions power system. Since the power systems are operated close to
are not available. [1, 2]. Recent development in voltage the stability limits, it is very important to take remedies to
source converter (VSC) technology has convinced the improve the CCT for better reliability.
industry to use VSCs for present and future HVdc
implementations [3]. The ability of fast bi-directional control There is an increasing trend in power electronic application to
of active and reactive powers of VSCs can facilitate the ac power system. The latest invention of VSC known as the
system with fast recovery from ac faults. Therefore, VSC MMC provides inherent control features such fast ac voltage
HVdc systems can be used to extend the CCT of power control. The rapid ac voltage controlling capability of the
systems to improve the transient stability margin. VSC facilitates quick transfer of kinetic energy from the
generator to the ac power system after a fault. Therefore,
This paper explores the transient stability enhancement by VSCs can be used to enhance the transient stability of power
having a two-terminal modular multilevel converter (MMC) systems.
type VSC system in an ac power system. The stability of a
conventional synchronous generator connected in the vicinity 3 Test Power System
of the MMC-VSC system is investigated. The short circuit
ratio (SCR) is used to define the strength of the ac system. The power system used in this study consists of a
The impact of fast ac voltage control capabilities of the VSC conventional synchronous generator (up to 1100 MVA), an
system on the CCT is evaluated by comparing against the MMC-VSC system (500 MW, 500 kV dc), and Thévenin
generator under the influence of the VSC system with the equivalents of large power systems (SCR of 3.0 at 230 kV
reactive power control. The stability of the system is further ac). The configuration of the simulated power system network
evaluated when the generator is connected at a distance from is shown in Fig. 1.

1
DC Line Outer-Loops Inner-Loops vtd(m)
Vdc(r) _+
Idc +_ PI itd(r)
+_ PI vd(o)
(or Pt(r)) +

MMC-1 Vdc1 Vdc2


 MMC-2
Vdc(m) ȦL
itd(m)
(or Pt(m)) Magnitude
Vt1 Vs1 Vs2 Vt2 |Vt|(m)
Limiter
itq(m)
Zs1 Zs2 (or Qt(m)) ȦL
Pt2, Qt2 |Vt|(r) _
PI
itq(r) _
PI _
_
+ +
+ vq(o)
AC System-2 (or Qt(r))
Pt1, Qt1
G vtq(m)

AC System-1 Fig. 2: d-q decoupled control system (r-reference, m-


measured, o-order).
Fig. 1: AC power system with a two-terminal MMC-VSC In this analysis, the VSC was operated in two different modes
System. known as the ac voltage (|Vt|) control mode and the reactive
power (Qt) control mode. In the 'Q' control mode, the steady
The EMT simulation model of the power system was state reactive power supplied to the ac system was set to zero.
developed on RTDS. Under steady state operating conditions, This means that the q-axis current reference (itq(r)) is always
the HVdc system was set to transfer 500 MW of power from set to zero and therefore, the reactive current support during
ac system-1 to ac system-2. The RTDS is capable to perform the transient is negligible. This was used as a reference to
real-time simulation of power systems using two different determine the impact of ac voltage control of VSC HVdc.
integration time-steps to keep the accuracy at a higher level.
The ac grids, the synchronous machine, and control The stability of VSC systems highly depend on the controller
components were simulated using a large integration time- parameters of d-q decoupled control. In this study, the
step ȝV ZKLOHWKHGF network and MMCs were simulated controller parameters were obtained using the generalized
using a small integration time-VWHS a ȝV  The block control tuning method proposed in [7]. In addition to the d-q
diagram of the complete control of the test power system is decoupled control, each MMC is equipped with a circulation
shown in Fig. 8 in the Appendix. suppression controller introduced in [8].
3.1 Control of Synchronous Generator
4 Time-Domain Simulation Studies
The synchronous generator (G) is modelled using the sixth
The transient stability enhancement was studied using time-
order synchronous generator model available in RSCAD, the
domain simulations on the RTDS simulators. The critical
user interface of RTDS. The generator controls include an
clearing time (CCT) of the generator was determined by
IEEE-AC4 type excitation system [4] for the voltage
applying a three phase solid fault at the generator terminal
regulation, a TGOV1 type thermal governor [5] for the
and increasing the fault clearing time until the generator
frequency regulation, and an IEEE-PSS1A type power system
becomes unstable. Two cases were considered;
stabilizer for the low frequency oscillation damping purposes.
In addition, a voltage droop control is also used for the
case-1: MMC-1 controls the terminal voltage (|Vt1|) at 1.0 p.u.
generator as it is connected to a point close to the converter
(MMC-1) that controls the terminal voltage (|Vt1|).
case-2: MMC-1 controls the reactive power (Qt1) supplied to
ac system-1 at 0 p.u.
3.2 Control of MMC-VSC
The commonly used d-q decoupled control scheme [6] is Three different scenarios were considered as described below;
adopted in this study to control each MMC. This control
scheme consists of cascaded PI-control loops referred to as 4.1 Scenario-1
outer-loop (power-loop) controllers and inner-loop (current-
The synchronous generator and the MMC-VSC system were
loop) controllers as shown in Fig. 2. The outer-loop
connected to terminal-1 as shown in Fig. 1. The CCT values
controllers are responsible to produce the reference values for
of the synchronous generator were obtained for both case-1
the d-q frame currents. In the outer-loop, either dc voltage or
and case-2. For each cases, the generator rating was changed
active power is selected as the control variable to produce d-
from 100 MW to 1000 MW in steps of 100 MW (110 MVA
axis current reference. Similarly, either ac voltage or reactive
to 1100 MVA in 110 MVA steps). The variations of CCT
power is selected as the q-axis control variable. Then, at the
values of both cases are shown in Fig. 3. It can be observed
inner-loop, the measured d-q currents are regulated to meet
that when the VSC is in ac voltage control mode, it
the reference currents. In this study, the MMC-1 functions as
significantly improves the CCT of the generator. However, if
the rectifier to control the dc voltage (Vdc1) and MMC-2 is the
the rating of the generator is much larger than that of VSC,
inverter that controls the active power (Pt2).
the improvement is not significant.

2
The distance between the VSC terminal and the generator was
varied by changing 'x' from 0 to 0.75. in steps of 0.25. At each
'x', the rating of the generator was changed from 100 MW to
1000 MW in steps of 100 MW. The CCT values of reactive
power control mode and voltage control mode are given in
Table 1. The variation of CCT values for x = 0 was shown in
Fig. 3 and variations for other 'x' values are shown in Figs.
5(a)-5(c).

It can be observed that the CCT is higher when the VSC


operates in ac voltage control mode rather than in reactive
power control mode. Generally, the improvement is larger
when the rating of the generator is small. Also, it can be
observed that the improvement in CCT decreases as the VSC
system moves away from the generator terminal. One
Fig. 3: Variation of critical clearing time for scenario-1. exception was noticed when the generator is far away from
the VSC and close to the infinite bus (x=0.75). When the
The contribution of VSC to the improvement of CCT can be generator rating was increased beyond 500 MW, there was a
explained using the fundamental equation for the power significant drop in CCT in case-2 (reactive power control). In
transfer between the generator/VSC terminal and the infinite these cases, the ac voltage control was helpful for the VSC to
bus, given in Equation (1). recover fast. Therefore, with the VSC in ac voltage control, a
significant improvement in CCT was observed as shown in
Vs1 Vt1 sin G1 (1)
Fig. 5(c)
P
X1 PGEN x=0 x = 0.25 x = 0.50 x = 0.75
(MW) C1 C2 C1 C2 C1 C2 C1 C2
Where, Vs1, Vt1, į1, and X1 are the infinite bus voltage, 100 480 390 460 390 470 395 450 405
terminal voltage, angle difference (between Vs1 and Vt1), and 200 385 335 385 360 380 355 385 365
reactance of the Thévenin source of ac system-1 respectively. 300 360 300 350 330 355 330 365 340
400 335 280 310 305 335 310 345 320
In classical stability assessment, the stability is mainly 500 315 265 305 290 315 295 330 245
explained using the angle difference (į1). However, in this 600 300 245 295 280 300 280 315 230
research, the terminal ac voltage (Vt1) is used to explain the 700 280 230 280 270 280 265 300 215
stability as the control of ac voltage is different when the 800 260 210 265 260 265 255 290 205
VSC is in ac voltage control and in reactive power control. 900 230 190 255 260 250 245 280 185
Fast ac voltage control helps terminal voltage to recover fast 1000 170 180 245 265 230 230 265 180
and hence, improves the power transfer across the Thévenin
impedance. Improvement in power transfer offers Table 1: Critical clearing time of generator for scenario-2 in
improvement in CCT and transient stability of power system. milliseconds (C1: case-1 and C2: case-2).
4.2 Scenario-2
The synchronous machine was connected at a distance (x)
from the VSC terminal-1 and towards to the Thévenin
equivalent source of large power system as shown in Fig. 4.

Vs1 Vt1
(1-x)Zs1 xZs1 MMC-
VSC
System
AC System-1

G
Vg1

Fig. 4: Circuit diagram for scenario-2. (a) x = 0.25

3
PGEN y=0 y = 0.25 y = 0.50 y = 0.75
(MW) C1 C2 C1 C2 C1 C2 C1 C2
100 480 390 410 395 370 350 345 350
200 385 335 380 365 330 315 315 320
300 360 300 340 330 300 290 285 285
400 335 280 315 305 280 265 260 255
500 315 265 280 280 255 235 230 225
600 300 245 270 265 230 215 210 200
700 280 230 250 240 205 180 185 180
800 260 210 235 220 180 160 165 150
900 230 190 220 215 165 135 135 125
1000 170 180 210 200 120 70 UN UN

Table 2: Critical clearing time of generator for scenario-3 in


(b) x = 0.50 milliseconds (C1: case-1, C2: case-2, and UN: unstable).

The variation of CCT values for y=0 was shown in Fig. 3 and
variations for other 'y' values are shown in Fig. 7(a)-7(c).

It can be observed that the improvement in CCT with the


VSC in ac voltage control mode compared to the reactive
power control mode becomes small when both VSC and
Thévenin source are away from the generator.

(c) x = 0.75
Fig. 5: Variation of CCT values for scenario-2.

4.2 Scenario-3
The MMC-VSC system is connected (to terminal-1) at a
distance from the synchronous machine and towards the
Thévenin equivalent model of the large power system as
shown in Fig. 6.
(a) y = 0.25
Vs1 Vt1 Vg1
(1-y)Zs1 yZs1
G
AC System-1

MMC-
VSC
System

Fig. 6: Circuit diagram for scenario-3.

The distance between the VSC terminal and the generator was
varied by changing the value of 'y' from 0 to 0.75 in steps of
0.25. At each 'y', the rating of the generator was changed from
100 MW to 1000 MW in steps of 100 MW. The CCT values (b) y = 0.50
of voltage control mode and reactive power control mode are
given in Table 2.

4
tuning procedure for vsc s\VWHPV´ IEEE Trans. on
Power Del., vol. 31, no. 2, pp. 732-742, Apr. 2016.

Biographies
Sakthivel Arunprasanth received the B.Sc. (Eng.) and M.Sc.
(Eng.) degrees in electrical engineering from the University of
Peradeniya, Peradeniya, Sri Lanka, in 2010 and 2013, respectively,
the Ph.D. degree in Electrical Engineering from the University of
Manitoba, Winnipeg, MB, Canada in 2016.
He is now working as a Simulation Specialist at the RTDS
Technologies Inc., Winnipeg, MB, Canada. He was a Researcher and
Instructor in the Department of Electrical and Electronic
Engineering, University of Peradeniya, Peradeniya, Sri Lanka, from
2010 to 2012. His research interests include transient and small-
signal stability studies of HVDC and HVAC systems and real-time
(c) y = 0.75 electromagnetic transient simulation of power systems.

Fig. 7: Variation of CCT values for scenario-3. Udaya Annakkage received the B.Sc. (Eng.) degree in electrical
engineering from the University of Moratuwa, Sri Lanka, in 1982,
and the M.Sc. and Ph.D. degrees in electrical engineering from the
5 Conclusions University of Manchester Institute of Science and Technology
(UMIST), Manchester, U.K., in 1984 and 1987, respectively.
This paper discussed the transient stability improvement He is presently a Professor with the University of Manitoba,
achieved by means of a two-terminal MMC-VSC system in a Winnipeg, MB, Canada. He was the Head of Electrical and
power system. The critical fault clearing time was used as the Computer Engineering Department, University of Manitoba, from
measure of the stability. It has been shown that the presence 2008 to 2012. His research interests include power system stability
of a VSC HVdc system with fast ac voltage control can and control, security assessment and control, operation of
significantly improve the transient stability of the generator in restructured power systems, and power system simulation.
Prof. Annakkage was an editor for the IEEE TRANSACTIONS ON
an ac network. The improvement is more prominent when the
POWER SYSTEMS from 2009 to 2012. He is currently the
generator with a low rating is placed close to the VSC convenor of CIGRE Working Group on Application of Phasor
terminal. Measurement Units for monitoring power system dynamic
performance.
References
Chandana Karawita received the B.Sc. (Eng.) degree in electrical
[1] $ 3DL ³(QHUJ\ IXQFWLRQ DQDO\VLV IRU SRZHU V\VWHP engineering from the University of Moratuwa, Sri Lanka, in 2002
VWDELOLW\´ Springer Science & Business Media, Dec. and the M.Sc. and Ph.D. degrees in electrical engineering with a
2012. specialization in power and energy systems from the University of
Manitoba, Winnipeg, MB, Canada, in 2006 and 2009, respectively.
[2] 3.XQGXU1-%DOXDQG0*/DXE\³3RZHUV\VWHP
He joined TransGrid Solutions Inc., Winnipeg, in 2007 and is
VWDELOLW\ DQG FRQWURO´ McGraw-Hill, New York, Jan. currently Manager-Research and Development. He has specialized in
1994. power systems planning studies for HVDC and HVAC integrations
[3] S. Debnath, J. Qin, B. Bahrani, M. Saeedifard, and P. and wind power generation. He is also a specialist in small-signal
%DUERVD ³2SHUDWLRQ FRQWURO DQG DSSOLFDWLRQV RI WKH stability assessment and power system stabilizer tuning, HVDC
PRGXODU PXOWLOHYHO FRQYHUWHU $ UHYLHZ´ IEEE Trans. interaction studies, and sub-synchronous oscillation studies of power
Power Electron., vol. 30, no. 1, pp. 37-53, Jan. 2015. systems. He was instrumental in developing a soft-ware package to
[4] ³Excitation system models for power system stability analyze sub-synchronous interactions in power systems. He is
studies´, IEEE Trans. Power App. Syst., vol. PAS-100, involved in academic research as an Adjunct Professor at the
University of Manitoba.
pp. 494-509, Feb. 1981.
[5] ³Dynamic models for steam and hydro turbines in power Rick Kuffel received the B.Sc. and M.Sc. degrees from the
system studies,´ IEEE Trans. Power App. Syst., vol. University of Manitoba, Winnipeg, MB, Canada in 1984 and 1986
PAS-92, no. 6, pp. 1904-1915, Nov. 1973. respectively. After graduating, he first joined Brown Boveri (BBC),
[6] &6FKDXGHUDQG+0HKWD³9HFWRUDQDO\VLVDQGFRQWURO Baden, Switzerland working in their HVDC Project Simulation
of advanced static var compHQVDWRUV´Proc. IEE Gener. Center. He later returned to Winnipeg and joined Teshmont
Transmiss. Distrib., vol. 140, no. 4, pp. 299±306, Jul. Consultants where he worked primarily in their simulation and
1993. studies group. In 1990, Mr. Kuffel moved to the Manitoba HVDC
[7] 4 7X = ;X DQG - =KDQJ ³&irculating current Research Centre where he was involved in development of the
RTDS real-time digital simulator and in 1994 became a founding
suppressing controller in PRGXODU PXOWLOHYHO FRQYHUWHU´
principal of RTDS Technologies Inc. His interests include
Proc. IECON 2010 - 36th Annual Conference on IEEE electromagnetic transient simulation, real time testing of control and
Ind. Electron. Soc., pp. 3198±3202, Nov. 2010. protection systems, HVDC control strategies, Modular Multilevel
[8] S. Arunprasanth, U. D. Annakkage, C. Karawita and R. Converters, DC Grids and the integration of renewable energy
Kuffel, ³Generalized frequency-domain controller sources in traditional power systems.

5
Appendix

Ȧ Ef
if Vs Power Voltage
Thermal
governor Tm G V
AC exciter ઱ system
stabilizer
droop
control

Terminal bus-1
DC system
Converter
station
Zs1
MMC-1 vdc1 and
AC system-2
Vt1 it1
Pt1, Qt1 iarm1, vcap1

Measurement & vabc1 Firing pulse Capacitor voltage


PLL
Per-unitization generator balancing
vabc1(m) iabc1(m) įm1
abc/d-q vdq1 d-q decoupled vabc1 d-q/abc
transform idq1 control transform
vabc1(o)
Pt1,Qt1,|Vt1| Control system-2
vdc1(r),|Vt1|(r)
iarm1
Pt1(r), Qt1(r)
abc/d-q Circulation d-q/abc
transform current control transform ઱

2įm1 Control system-1

Fig. 8: Control block diagram of the test system

You might also like