Professional Documents
Culture Documents
*RTDS Technologies Inc., Canada, †University of Manitoba, Canada, ‡TransGrid Solutions Inc., Canada
arunprasanth@ieee.org, udaya@ieee.org, ckarawita@tgs.biz, rk@rtds.com
Keywords: High-voltage direct current, modular multilevel the VSC terminal and also when the VSC is connected at a
converter, real-time digital simulator, short circuit ratio, distance from the generator. The simulation studies were
transient stability. performed using the electro-magnetic transient (EMT) model
of power system developed on the real-time digital simulator
Abstract (RTDS). The simulation results are presented to show that the
presence of MMC-VSC system helps to extend the CCT of
This paper investigates the impact of different control modes the synchronous generator that is connected to the power
of VSC HVdc to the transient stability of power systems. system.
VSC HVdc offers fast bi-directional power control in addition
to fast ac voltage control. This feature is utilized in this study 2 Power System Stability
to enhance the transient stability of a conventional generator
in a power system. Simulations are carried-out for three Although, the penetration of renewable energy generations
scenarios: (i) the generator is connected to the VSC terminal, such as wind and solar is increasing, many utilities around the
(ii) the generator is connected at a distance from the VSC world depend on conventional electricity generations by large
terminal, and (iii) the VSC is connected at a distance from the scale synchronous machines. Typically, the system frequency
generator terminal. The critical fault clearing time is used as is governed by these synchronous machines. Therefore,
the indicator of the stability of power system. In each maintaining synchronism of these generators is very
scenario, effects of both ac voltage control and reactive power important for the stable operation of power system.
control are studied. This paper shows that the transient
stability of power system can be improved by having a VSC The transient stability of a power system is defined as the
with fast ac voltage control near to synchronous generators. ability of a power system to remain in stable operation after
being subjected to transient disturbances such as faults [2].
1 Introduction Typically, the transient stability of a power system is defined
in terms of the CCT of the power system. During a fault in a
At present, power systems are operated close to the stability power system, the synchronous generators close to that fault
limits due to the high electricity demand and penetration of acquire kinetic energy. The ability of those generators to stay
renewable energy generations. Heavily loaded power systems in synchronism after clearing the fault depends on the speed
will have small critical fault clearing time (CCT) and may at which the acquired kinetic energy is transferred to the ac
experience transient stability issues if fast protection actions power system. Since the power systems are operated close to
are not available. [1, 2]. Recent development in voltage the stability limits, it is very important to take remedies to
source converter (VSC) technology has convinced the improve the CCT for better reliability.
industry to use VSCs for present and future HVdc
implementations [3]. The ability of fast bi-directional control There is an increasing trend in power electronic application to
of active and reactive powers of VSCs can facilitate the ac power system. The latest invention of VSC known as the
system with fast recovery from ac faults. Therefore, VSC MMC provides inherent control features such fast ac voltage
HVdc systems can be used to extend the CCT of power control. The rapid ac voltage controlling capability of the
systems to improve the transient stability margin. VSC facilitates quick transfer of kinetic energy from the
generator to the ac power system after a fault. Therefore,
This paper explores the transient stability enhancement by VSCs can be used to enhance the transient stability of power
having a two-terminal modular multilevel converter (MMC) systems.
type VSC system in an ac power system. The stability of a
conventional synchronous generator connected in the vicinity 3 Test Power System
of the MMC-VSC system is investigated. The short circuit
ratio (SCR) is used to define the strength of the ac system. The power system used in this study consists of a
The impact of fast ac voltage control capabilities of the VSC conventional synchronous generator (up to 1100 MVA), an
system on the CCT is evaluated by comparing against the MMC-VSC system (500 MW, 500 kV dc), and Thévenin
generator under the influence of the VSC system with the equivalents of large power systems (SCR of 3.0 at 230 kV
reactive power control. The stability of the system is further ac). The configuration of the simulated power system network
evaluated when the generator is connected at a distance from is shown in Fig. 1.
1
DC Line Outer-Loops Inner-Loops vtd(m)
Vdc(r) _+
Idc +_ PI itd(r)
+_ PI vd(o)
(or Pt(r)) +
2
The distance between the VSC terminal and the generator was
varied by changing 'x' from 0 to 0.75. in steps of 0.25. At each
'x', the rating of the generator was changed from 100 MW to
1000 MW in steps of 100 MW. The CCT values of reactive
power control mode and voltage control mode are given in
Table 1. The variation of CCT values for x = 0 was shown in
Fig. 3 and variations for other 'x' values are shown in Figs.
5(a)-5(c).
Vs1 Vt1
(1-x)Zs1 xZs1 MMC-
VSC
System
AC System-1
G
Vg1
3
PGEN y=0 y = 0.25 y = 0.50 y = 0.75
(MW) C1 C2 C1 C2 C1 C2 C1 C2
100 480 390 410 395 370 350 345 350
200 385 335 380 365 330 315 315 320
300 360 300 340 330 300 290 285 285
400 335 280 315 305 280 265 260 255
500 315 265 280 280 255 235 230 225
600 300 245 270 265 230 215 210 200
700 280 230 250 240 205 180 185 180
800 260 210 235 220 180 160 165 150
900 230 190 220 215 165 135 135 125
1000 170 180 210 200 120 70 UN UN
The variation of CCT values for y=0 was shown in Fig. 3 and
variations for other 'y' values are shown in Fig. 7(a)-7(c).
(c) x = 0.75
Fig. 5: Variation of CCT values for scenario-2.
4.2 Scenario-3
The MMC-VSC system is connected (to terminal-1) at a
distance from the synchronous machine and towards the
Thévenin equivalent model of the large power system as
shown in Fig. 6.
(a) y = 0.25
Vs1 Vt1 Vg1
(1-y)Zs1 yZs1
G
AC System-1
MMC-
VSC
System
The distance between the VSC terminal and the generator was
varied by changing the value of 'y' from 0 to 0.75 in steps of
0.25. At each 'y', the rating of the generator was changed from
100 MW to 1000 MW in steps of 100 MW. The CCT values (b) y = 0.50
of voltage control mode and reactive power control mode are
given in Table 2.
4
tuning procedure for vsc s\VWHPV´ IEEE Trans. on
Power Del., vol. 31, no. 2, pp. 732-742, Apr. 2016.
Biographies
Sakthivel Arunprasanth received the B.Sc. (Eng.) and M.Sc.
(Eng.) degrees in electrical engineering from the University of
Peradeniya, Peradeniya, Sri Lanka, in 2010 and 2013, respectively,
the Ph.D. degree in Electrical Engineering from the University of
Manitoba, Winnipeg, MB, Canada in 2016.
He is now working as a Simulation Specialist at the RTDS
Technologies Inc., Winnipeg, MB, Canada. He was a Researcher and
Instructor in the Department of Electrical and Electronic
Engineering, University of Peradeniya, Peradeniya, Sri Lanka, from
2010 to 2012. His research interests include transient and small-
signal stability studies of HVDC and HVAC systems and real-time
(c) y = 0.75 electromagnetic transient simulation of power systems.
Fig. 7: Variation of CCT values for scenario-3. Udaya Annakkage received the B.Sc. (Eng.) degree in electrical
engineering from the University of Moratuwa, Sri Lanka, in 1982,
and the M.Sc. and Ph.D. degrees in electrical engineering from the
5 Conclusions University of Manchester Institute of Science and Technology
(UMIST), Manchester, U.K., in 1984 and 1987, respectively.
This paper discussed the transient stability improvement He is presently a Professor with the University of Manitoba,
achieved by means of a two-terminal MMC-VSC system in a Winnipeg, MB, Canada. He was the Head of Electrical and
power system. The critical fault clearing time was used as the Computer Engineering Department, University of Manitoba, from
measure of the stability. It has been shown that the presence 2008 to 2012. His research interests include power system stability
of a VSC HVdc system with fast ac voltage control can and control, security assessment and control, operation of
significantly improve the transient stability of the generator in restructured power systems, and power system simulation.
Prof. Annakkage was an editor for the IEEE TRANSACTIONS ON
an ac network. The improvement is more prominent when the
POWER SYSTEMS from 2009 to 2012. He is currently the
generator with a low rating is placed close to the VSC convenor of CIGRE Working Group on Application of Phasor
terminal. Measurement Units for monitoring power system dynamic
performance.
References
Chandana Karawita received the B.Sc. (Eng.) degree in electrical
[1] $ 3DL ³(QHUJ\ IXQFWLRQ DQDO\VLV IRU SRZHU V\VWHP engineering from the University of Moratuwa, Sri Lanka, in 2002
VWDELOLW\´ Springer Science & Business Media, Dec. and the M.Sc. and Ph.D. degrees in electrical engineering with a
2012. specialization in power and energy systems from the University of
Manitoba, Winnipeg, MB, Canada, in 2006 and 2009, respectively.
[2] 3.XQGXU1-%DOXDQG0*/DXE\³3RZHUV\VWHP
He joined TransGrid Solutions Inc., Winnipeg, in 2007 and is
VWDELOLW\ DQG FRQWURO´ McGraw-Hill, New York, Jan. currently Manager-Research and Development. He has specialized in
1994. power systems planning studies for HVDC and HVAC integrations
[3] S. Debnath, J. Qin, B. Bahrani, M. Saeedifard, and P. and wind power generation. He is also a specialist in small-signal
%DUERVD ³2SHUDWLRQ FRQWURO DQG DSSOLFDWLRQV RI WKH stability assessment and power system stabilizer tuning, HVDC
PRGXODU PXOWLOHYHO FRQYHUWHU $ UHYLHZ´ IEEE Trans. interaction studies, and sub-synchronous oscillation studies of power
Power Electron., vol. 30, no. 1, pp. 37-53, Jan. 2015. systems. He was instrumental in developing a soft-ware package to
[4] ³Excitation system models for power system stability analyze sub-synchronous interactions in power systems. He is
studies´, IEEE Trans. Power App. Syst., vol. PAS-100, involved in academic research as an Adjunct Professor at the
University of Manitoba.
pp. 494-509, Feb. 1981.
[5] ³Dynamic models for steam and hydro turbines in power Rick Kuffel received the B.Sc. and M.Sc. degrees from the
system studies,´ IEEE Trans. Power App. Syst., vol. University of Manitoba, Winnipeg, MB, Canada in 1984 and 1986
PAS-92, no. 6, pp. 1904-1915, Nov. 1973. respectively. After graduating, he first joined Brown Boveri (BBC),
[6] &6FKDXGHUDQG+0HKWD³9HFWRUDQDO\VLVDQGFRQWURO Baden, Switzerland working in their HVDC Project Simulation
of advanced static var compHQVDWRUV´Proc. IEE Gener. Center. He later returned to Winnipeg and joined Teshmont
Transmiss. Distrib., vol. 140, no. 4, pp. 299±306, Jul. Consultants where he worked primarily in their simulation and
1993. studies group. In 1990, Mr. Kuffel moved to the Manitoba HVDC
[7] 4 7X = ;X DQG - =KDQJ ³&irculating current Research Centre where he was involved in development of the
RTDS real-time digital simulator and in 1994 became a founding
suppressing controller in PRGXODU PXOWLOHYHO FRQYHUWHU´
principal of RTDS Technologies Inc. His interests include
Proc. IECON 2010 - 36th Annual Conference on IEEE electromagnetic transient simulation, real time testing of control and
Ind. Electron. Soc., pp. 3198±3202, Nov. 2010. protection systems, HVDC control strategies, Modular Multilevel
[8] S. Arunprasanth, U. D. Annakkage, C. Karawita and R. Converters, DC Grids and the integration of renewable energy
Kuffel, ³Generalized frequency-domain controller sources in traditional power systems.
5
Appendix
Ȧ Ef
if Vs Power Voltage
Thermal
governor Tm G V
AC exciter system
stabilizer
droop
control
Terminal bus-1
DC system
Converter
station
Zs1
MMC-1 vdc1 and
AC system-2
Vt1 it1
Pt1, Qt1 iarm1, vcap1