You are on page 1of 6

A PV MODULE-INTEGRATED INVERTER USING A ĆUK CONVERTER

IN DCM WITH ISLAND DETECTION SCHEME

Henrique G. Cabral, Paulo F. S. R. de Faria, Igor L. Guisso, Carlos E. B. Rambo, Bruno L. Vigna,
Maurício S. Santos, Vanderlei A. Vieira Jr., Renan C. Viero and Fernando S. dos Reis
Pontifícia Universidade Católica do Rio Grande do Sul, Porto Alegre, Brazil
e-mail: f.dosreis@gmail.com

Abstract – This paper reports a study on a grid-tied In order to safely and successfully inject the electrical
photovoltaic system, using a microinverter based on Ćuk power generated by distributed generation systems (DGS)
converter working in DCM. Since, when the Ćuk into the electrical power system, a series of control measures
converter is working in DCM, its output voltage presents must be taken. To avoid unsafe conditions, the DGS must
a linear behavior in relationship to its duty cycle. sense when the utility grid is disconnected either for
Therefore, the duty cycle must have a sinusoidal maintenance, by fault or human error. The islanding occurs
behavior, in absolute value, in order to generate a when the grid is offline, for any of the reasons above
rectified sine current waveform, at its output. The described, but the DGS still feeds the point of common
connection of a full bridge current source inverter in coupling (PCC). For this purpose, an anti-islanding (AI)
cascade with the Ćuk converter, allows obtaining a protection scheme must be used so as to avoid this unsafe
sinusoidal current waveform at the microinverter output. condition, effectively protecting the personnel and equipment
One of the most important challenges on microgeneration of the system. Strict test conditions for this phenomenon are
systems is the island detection. In this sense, if the system defined under IEEE 929 (Recommended Practice for Utility
is unable to detect the islanding, this may cause power Interface of Residential and Intermediate Photovoltaic (PV)
quality degradation, electrical safety threats, especially Systems) and must be followed to avoid islanding of
related to maintenance crews, and damage to third-party distributed resources.
devices connected to the same power grid. Several AI protection schemes have been developed and
are classified in two main categories: passive and active
Keywords – Anti-islanding, PV systems, DG, methods. Passive AI protection schemes sense the electrical
microinverter, renewable energy, Ćuk converter, DCM. parameters of the commercial power grid, and take action if
one of them is outside the desired standards. Active methods
I. INTRODUCTION try to cause disturbances at the PCC by altering the
magnitude, frequency or phase at the inverter output [2]. By
From the economic perspective, the microgeneration observing if the perturbation effectively occurs, the system
technology can offer benefits to both electric distribution and can detect an islanding condition and disconnect itself from
generation companies and consumers, since in this paradigm, the grid, given that in the presence of the power grid the
namely the distributed microgeneration, consumers also electrical parameters at the PCC are imposed by it.
assume the role of producers of electricity [1]. This is In this paper, a microinverter based on Ćuk converter is
especially true for photovoltaic (PV) panels, given that, proposed. This converter was chosen because it presents a
densely populated areas can also generate great amounts of current source behavior in its input and output. The presence
electric power by installing PV panels on its rooftops. Thus, of the output inductor gives to this circuit a current source
the main objective of this work is to develop a microinverter, characteristic, which turns out to be suitable for connection
including active islanding detection system, in order to inject to the power grid, which has voltage source characteristics,
the electric power generated by photovoltaic panels into the as is well known [3].
commercial power grid. In the following sections, a brief design methodology
The proposed microinverter is divided into two main based on the quasi-static approach will be presented for the
parts: the first one is based on the Ćuk converter, operating at Ćuk converter, as well as the component values used for the
high frequency (20 kHz), and the second section is actual prototype. Using a simulation tool and an
implemented by a full bridge current source inverter (CSI), experimental prototype, the proposed active anti-islanding
working at low frequency (mains frequency, in this case protection scheme was validated, and the obtained results are
60 Hz). The Ćuk converter is responsible for the synthesis of presented and discussed in the sequence of this paper.
sine current waveform, in absolute value, synchronized with
the power grid. The full bridge inverter in cascade with the II. OPERATION OF THE MICROINVERTER
converter ensures a sinusoidal current waveform at the
microinverter output. Considering the aforementioned Low power DC-DC converters operating in discontinuous
microinverter configuration, it is right ensure that, it provides conduction mode (DCM) are widely used for implementation
galvanic insulation, which is required in many countries. In of microinverters dedicated to PV systems, being one of the
this topology, the switching losses are also reduced. Once, best solutions for applications in low power [4]. This is due
only the Ćuk converter operates at high frequency. to several factors such as: a) their topological simplicity, b)
low implementation cost, c) simplicity of the control loop

978-1-4799-8779-5/15/$31.00 ©2015 IEEE


design, d) capacity to synthesize a sinusoidal current
waveform through simple variation of the duty cycle,
according to a sinusoidal pulse width modulation (SPWM)
law, as shown in (1), when the converter is working in DCM.
The sinusoidal modulation ensures that the harmonic current
injected into the power grid is not affected by variations in
irradiance and temperature since the DCM operation is Fig 1. Full energy conversion system.
guaranteed [5], [6]. The highlighted advantages, besides
many others, point the Ćuk converter as a satisfactory TABLE I
solution to distributed microgeneration based on PV PV Module Specification at STC Panel Model SR50 [11]
modules. Electrical PV module parameters Value
Maximum power Pmax 50.00 [Wp]
Current @ maximum power point - IMPP 2.95 [A]
d( ω t) = d max sin( ω t + ϕ ) (1) Voltage @ maximum power point - VMPP 17.00 [V]
Short-circuit current ISC 3.20 [A]
where, dmax is determined through a maximum power point Open-circuit voltage VOC 21.60 [V]
tracking (MPPT) algorithm and ϕ is the absolute value of the
phase displacement introduced by the Ćuk microinverter. III. DESIGN CRITERIA FOR A ĆUK CONVERTER IN
The studied system, the microinverter, can be divided into DCM
three stages, as is shown in Fig. 1: The first stage consists of
two Siemens© PV panels model SR50 (table I) connected in When the Ćuk converter works in discontinuous
series generating a rated power of 100 Wp (under Standard conduction mode, it presents three stages of operation. In the
Test Conditions - STC). These panels are connected in first stage, the main switch is on (ton) and in the second and
parallel to a decoupling capacitor (CPV), whose function is third stages, it remains off (toff). The diode conducts only on
storing energy arising from the panels (Fig. 1). In the present the second stage, when it is forward biased. The conduction
implementation, the capacitor has to be bulky, since the time of the diode (tDon) is a function of the switch conduction
converter synthesizes a rectified sinusoidal current waveform time (ton) and of the voltage static gain (input-output voltage
in its output, in low frequency [4]. However, the input ratio) of the Ćuk converter. A simplified topology of the Ćuk
current that is supplied by PV panels is almost constant. converter shown on Fig 1 reflected to the primary side
Therefore, the capacitor (CPV) must be designed for storage considering a unitary turns ratio can be seen in Fig 2. Given
and to supply power during one semi-cycle of the power that the switching frequency is much higher than the line
mains. frequency synthetized at the microinverter output, the
A Ćuk converter is implemented in the second stage, capacitor voltages can be assumed as a constant and ripple-
which is responsible for the galvanic isolation, for free during one switching cycle.
synthesizing a rectified sinusoidal current waveform on its
output and for the impedance matching between the PV L1 L2
module and the power grid. Therefore, the Ćuk converter V1 + V2

allows tracking the maximum available power on different


V1 D V2
weather conditions (solar irradiation and PV panel
temperature). Also, given that the Ćuk converter operates at
high switching frequencies (fs), its switches have significant
switching losses. Fig 2. Equivalent circuit of a Ćuk converter reflected to the primary
The third and final stage consists of a full-bridge current side.
source inverter. This device allows obtaining a sinusoidal
current waveform from the output current synthesized by the A. First Stage of Operation ( 0 < t < ton )
Ćuk converter, which is a rectified sinusoidal current The equivalent circuit for the first stage of operation of a
waveform synchronized with the power grid voltage. Hence, Ćuk converter is shown on Fig 3, where the switch is on and
the full bridge inverter works at mains frequency, i.e. 50 Hz the diode is off.
or 60 Hz, its switching losses are negligible, so it presents
only conduction losses. L1 L2
The third and final stage consists of a full-bridge current V1 + V2
source inverter. This device allows obtaining a sinusoidal
current waveform from the output current synthesized by the V1 D V2
Ćuk converter, which is a rectified sinusoidal current
waveform synchronized with the power grid voltage. Hence,
the full bridge inverter works at mains frequency, i.e. 50 Hz Fig 3. Equivalent circuit of a Ćuk converter operating in DCM, first
or 60 Hz, its switching losses are negligible, so it presents stage, while the switch is conducting.
only conduction losses.
As such, the input and output currents on the first stage
can be defined by (2) and (3).
V1 (2)
iL1( t ) = t + I min The input and output currents remain in their minimal
L1
values (iL1 = Imin and iL2 = -Imin) while the converter stays in
this stage, that is, until the switch is closed again.
V1 (3)
iL 2 ( t ) = t − I min Through the use of the power balance principle, the
L2 minimum value of the currents in the inductors (Imin) can be
determined, considering a loss-free scenario. Consequently,
When t = ton, this stage is succeeded by the second stage. the input power must be equal to the output power, as (9)
B. Second Stage of Operation ( ton < t < ton + tDon ) describes, and (10) can be defined.
The forward bias of the diode and the opening of the
switch characterize the second stage of operation, as shown V1 I L1 = V 2 I L 2 (9)
in Fig 4.
On the instant t = ton, the currents iL1 and iL2 reach their
maximum values, as defined by (4) and (5), and their d 2 ⎡V1 2 L2 − V1 V 2 L1 ⎤ (10)
I m in = ⎢ ⎥
instantaneous value, as declared by (6) and (7). f s ⎣ 2 L1 L2 V 2 ⎦
V (4)
I L1max ( t ) = 1 ton + I min
L1 where 1 and 2 are the current average values in the
inductors in the switching period (T), fs is the switching
V1 (5) frequency, d is the duty cycle, with d = ton / T.
I L 2 max ( t ) = ton − I min
L2 Conversely, the output voltage of the converter can be
obtained from the product of the average value of the iL2
V2 current ( 2 ) by the resistance of the load (R), which is
i L 1 ( t ) = I L 1 m ax − t (6)
L1 represented in (11). The validity of (1) is justified by (11).
However, from (11) it is easy to conclude that if K is
constant, the waveform of the converter output voltage only
V2 (7)
i L 2 ( t ) = I L 2 m ax − t depends on the pattern of variation of the duty cycle (d).
L2
d (11)
V2 = V1
L1 L2 K
V1 + V2

V1 V2
where,

L1 L2 2 Leq
Leq = ; K = .
L1 + L2 TR
Fig 4. Equivalent circuit of a Ćuk converter operating in DCM,
second stage, while the diode is conducting.
D. Design Method and Parameters
In order to guarantee the operation of the Ćuk converter in
This stage ends when the diode turns off (t = tDon) as iL1
DCM, for all duty cycle values, the operation in the
and iL2 reach their minimal values (Imin for iL1 and – Imin for
boundary mode must be guaranteed, at the worst case. In the
iL2), resulting in (8).
boundary mode, static gain equations are the same, for both
converter-operating modes, DCM and CCM. The converter
V1 ton (8) static gain for CCM is obtained through the volt-second
t Don =
V2 balancing in the inductors, resulting in (12), since the
average voltage upon the inductors should be zero. As such,
C. Third Stage of Operation ( ton + tDon < t < T ) the equivalent inductance should be as described by (13) for
The third stage of operation of the converter begins when operation in DCM.
the currents iL1 and iL2 reach their minimal values. At that
moment, both currents flow in freewheeling, resulting in the d max
2 V2 = V1 (12)
diode blocking, as Fig 5 shows. 1 − d max

L1 L2
V12 V2 2 (13)
V1 + V2 Leq <
2 P f s ( V1 + 2 V2 )2
V1 V2
Imin where dmax is the maximum value of the duty cycle, which is
required when the output voltage is equal to the mains peak
Fig 5. Equivalent circuit of a Ćuk converter operating in DCM, value, V2 is the mains rms value, V1 is the PV maximum
third stage, when neither the diode nor the switch is conducting. power point voltage, fs is the switching frequency and P is
the output power. Therefore, by making both inductors twice generated by the inverter, if the impact of the anti-islanding
the inductance of Leq found on (13), operation in DCM can algorithm is imperceptible on PCC, it means that the power
be guaranteed. grid is on. Likewise, if the impact of the perturbation in the
For this particular implementation, the microinverter input electrical magnitudes on PCC is significant, a power failure
voltage is V1 = 34 Vdc considering the maximum power point is assumed and the DGS is disconnected.
(MPP) PV voltage (VMPP). The single-phase power mains
voltage establishes the output voltage V2 = 127 Vrms. Using TABLE II
the proposed design criteria, considering fs = 20 kHz, the IEEE 929 STANDARD – RESPONSE TO ABNORMAL
values of the inductors were determined, resulting VOLTAGES
L1 = L2 = 360 µH and dmax = 0.78. Voltage (at the PCC) Maximum Trip Time
V < 50 % 0.1 s
50 % ≤ V < 88 % 2.0 s
IV. ANTI-ISLANDING METHODS
88 % ≤ V ≤ 110 % Continuous operation
110 % < V < 137 % 2.0 s
An anti-islanding algorithm can be classified in two main 137 % ≤ V 0.03 s
categories: the passive and active methods. Passive
algorithms continuously sense the electrical characteristics at These perturbations, while small in comparison to the
the PCC, such as magnitude, frequency or phase. If the above power grid, can cause losses in the power extracted from PV
parameters diverge from the expected values as established panel and losses in power quality, when compared with the
by IEEE 929, the DGS disconnect itself from the grid [8]. normal operating conditions without any perturbations [8].
Active methods try to perturb the electrical parameters at When implementing an anti-islanding algorithm on a DC-DC
the PCC and can be further classified in three subcategories: converter, these perturbations are carried out by changing the
the residents in the inverter, those who are not resident in the duty cycle of the converter. If an MPPT algorithm is also
inverter and the methods based on the use of communication implemented on the same converter, this means that while
between the power grid operator and the anti-islanding the AI algorithm is active, the MPP is lost, thus, reducing the
detection scheme of the DGS [9]. time that the maximum power is extracted from the panel and
reducing the overall efficiency of the system.
A. Passive Methods
Usual passive anti-islanding methods consist of observing V. IMPLEMENTATION OF THE ANTI-ISLANDING
abnormal over or under voltage, as well as over or under ALGORITHM
frequency conditions. The IEEE 929 standard sets the
parameters for disconnection at the PCC, as shown on table On this paper, an active islanding detection method was
II with the voltage limits expressed as percentages of the described to a microinverter based on the Ćuk converter,
rated voltage at the PCC [10]. given that passive methods are not very effective when the
If a power outage occurs in the commercial power grid, load connected to the microinverter is balanced. The
three scenarios can be expected when observing solely the algorithm consists in the generation of a periodic disturbance
voltage at the PCC: at microinverter output voltage by reducing the maximum
• The power generated by the DGS surpasses the power value of the duty cycle (dmax) of the Ćuk converter. Given
consumed by the load and an increase in voltage at the that this momentary reduction on dmax withdraw the converter
PCC occurs. The system is, then, disconnected; from MPP, resulting in an electrical power production
• The power generated by the DGS is insufficient to reduction, a one second delay, between perturbations was
supply the load and voltage decreases at the PCC. The established in order to meet the IEEE 929 standard and to
system is, then, disconnected; maximize the electrical power production. Thus, every
• The load and the DGS are in balance and the voltage at second, the output voltage of the microinverter is disturbed
the PCC does not vary. The system fails to disconnect. and the voltage at the PCC is measured. If a voltage
Likewise, a very similar behavior can be seen on the disturbance at the PCC is observed, or its value is out of the
detection of under/over frequency: an increase or decrease of bounds specified in table II, the DGS should be
the frequency at the PCC occurs when the commercial power disconnected. Fig 6 summarizes the proposed anti-islanding
grid is disconnected. If the change in frequency is small algorithm.
enough, it may go undetected and the anti-islanding system This algorithm determines the PCC voltage rms value,
may fail. The IEEE 929 standard sets a maximum trip time every power mains cycle, in order to detect any voltage
of 0.1 s whenever the frequency at the PCC is not within disturbance that indicates an islanding occurrence. Figure 7
59.3 and 60.5 Hz [2]. shows the behavior of the maximum value of the duty cycle,
during a dmax perturbation, which occurs every second. The
B. Active Methods adopted reduction on dmax value it is fifty percent of its rated
Active anti-islanding methods that do not rely on the value in order to generate a sizable voltage drop at the
communication to the power grid operator essentially try to inverter output (VPCC), when an islanding condition occurs.
disturb electrical magnitudes on PCC by injecting In this event, the inverter is disabled, and physically
disturbance voltage, frequency, voltage harmonic content and disconnected from PCC, by a power contactor, through the
phase displacement, at the inverter output. Given that the output enable command signal as depicted in Fig 7. After the
power grid can effectively reject these disturbances
power grid reestablishment, a five minuttes delay is required is reduced, every 60 cycles, due to the action of the active
by IEEE 929 standard, before the inverterr reconnection. anti-islanding algorithm.

Fig 8. Equipment under test, setuup IEEE 929.

Fig 6. Implemented anti-islanding algorithm.

Fig 9. Voltage at PCC and the microinverter


m output current.

The effectiveness of the isslanding detection method can be


verified by observation of the Fig 10, in which is shown that
the inverter shuts down wheen an islanding occurs. The time
interval for islanding detectioon can take up to one second that
corresponds to the periodd in which the duty cycle
perturbation occurs.

Fig 7. Main waveforms of the anti-islanding system.


s

VI. SIMULATION AND EXPERIMENTAL RESULTS

The standard IEEE 929 describes how w the load should be


sized for the anti-islanding test, where thhe load consists of a
RLC parallel circuit, as shown in Fig 8. In this arrangement,
the inductor (L) and the capacitor (C) are a forming a tuned
filter at the power mains frequency, thuus providing a high
quality voltage waveform at its terminalss. Therefore, even if
the power grid is disconnected the vooltage at the output
terminals of the inverter remains unchangged, considering that
the load is balanced, as recommended byy IEEE 929 standard.
The micro inverter and the RLC load are a connected to the Fig 10. Voltage at PCC andd the microinverter output current
utility grid by a power contactor, whichh will be opened to during an islanding condition under
u IEEE 929 test conditions.
simulate an islanding occurrence.
A microinverter prototype was built using the proposed TAB
BLE III
design criteria (table III) for the Ćuk coonverter operating in MICROINVERT
TER PARAMETERS
DCM. Figure 9 shows the voltage at PCC and the Parameters Value
Maximum power Pmax 100 [W]
microinverter output current at rated operation.
o From this
Nominal Input Voltagee 34 [V]
figure, it is remarkable that in the presennce of power mains, Output voltage 127 [V]
the microinverter output current, which is injected into grid, Switching frequency 20 [kHz]
Output frequency 60 [Hz]
[2] IEEE Recommended Practice for Utility Interface of
VII. CONCLUSIONS Photovoltaic (PV) Systems," in IEEE Std 929-2000 ,
vol., no., pp.i-, 2000.
In this paper was presented a study on a microinverter, [3] H. G. Cabral, A. R. Marques, G. R. Pedrollo, P. F. de
based on the Ćuk converter working on DCM. A quasi- Faria and F. S. dos Reis, "Performance comparison of
sinusoidal current waveform was obtained at inverter output, Buck-boost family converters for driving led lamps,"
when it is powered by a set of PV panels. The proposed Industry Applications (INDUSCON), 2014 11th
active islanding detection method consists in to reduce the IEEE/IAS International Conference, pp.1,8, 7-10 Dec.
inverter maximum duty cycle (dmax), during a short period, 2014
every second and to observe the voltage at PCC. When this [4] Z. Zhiliang, H. Xiao-Fei, and L. Yan-Fei, "An Optimal
perturbation results in a voltage sag at PCC, an islanding Control Method for Photovoltaic Grid-Tied-Interleaved
occurrence is detected. Flyback Microinverters to Achieve High Efficiency in
The 50% reduction on dmax was chosen in order to Wide Load Range," Power Electronics, IEEE
generate a voltage drop at PCC compatible with the Transactions on, vol. 28, pp. 5074-5087, 2013.
abnormal voltage levels, according to IEEE 929 standard, [5] P. Neshaastegaran and H. R. Karshenas, "Investigation
considering an islanding scenario. Therefore, the passive of single-stage flyback inverter under different
islanding detection algorithm, which continuously monitors operating modes," in Power Electronics, Drive Systems
the rms voltage at the PCC detects the islanding occurrence, and Technologies Conference (PEDSTC), 2013 4th,
even in the presence of balanced loads. 2013, pp. 288-293.
The efficacy of the proposed islanding detection method [6] A. C. Kyritsis, E. C. Tatakis, and N. P. Papanikolaou,
was fully verified and despite its simplicity, it showed to be "Optimum Design of the Cur-rent-Source Flyback
potentially fast. Given that after every perturbation on dmax, Inverter for Decentralized Grid-Connected Photovoltaic
the islanding detection system is able to sense an islanding Systems," Energy Conversion, IEEE Transactions on,
occurrence in just two power mains cycles. Nevertheless, the vol. 23, pp. 281-293, 2008.
one-second delay, between perturbations was established in [7] Carugati, I.; Maestri, S.; Donato, P.G.; Carrica, D.;
order to maximize the electrical power production and Benedetti, M., "Variable Sampling Period Filter PLL
likewise to meet IEEE 929 standard in relationship to the for Distorted Three-Phase Systems," in Power
maximum trip time. Since, the dmax reduction, withdraw the Electronics, IEEE Transactions on , vol.27, no.1,
converter from MPP, which implies on momentary reduction pp.321-330, Jan. 2012
in electrical power production. [8] B. Blackstone;Y. Baghzouz;S. Premrudeepreechacharn,
"Determining MPPT and anti-islanding techniques in a
ACKNOLEDGEMENTS grid-tie PV inverter," Harmonics and Quality of Power
(ICHQP), 2012 IEEE 15th International Conference,
The authors would like to thank the support of PUCRS pp.409,413, 17-20 June 2012.
(Pontifícia Universidade Católica do Rio Grande do Sul), [9] F. De Mango;M. Liserre;AD Aquila;A. Pigazo,
FAPERGS (Fundação de Amparo à Pesquisa do Estado do "Overview of Anti-Islanding Algorithms for PV
Rio Grande do Sul), CAPES (Coordenação de Systems. Part I: Passive Methods," Power Electronics
Aperfeiçoamento de Pessoal de Nível Superior), CNPq and Motion Control Conference, 2006. EPE-PEMC
(Conselho Nacional de Desenvolvimento Científico e 2006. 12th International , pp.1878,1883, Aug. 30 2006-
Tecnológico) and Hewlett-Packard Brasil Ltda which made Sept. 1 2006.
this research possible. [10] A. Cataliotti;V. Cosentino; Ngoctrung Nguyen;P.
Russotto;D. Di Cara; G. Tine, "Hybrid passive and
REFERENCES communications-based methods for islanding detection
in medium and low voltage smart grids," Power
[1] L. Murphy, "Grid-tie arrangements for micro- Engineering, Energy and Electrical Drives
generation under EN50438; An Irish evaluation," (POWERENG), 2013 Fourth International Conference,
Power Engineering Conference (UPEC), 2013 48th pp.1563,1567, 13-17 May 2013.
International Universities, pp.1, 6, 2-5 Sept. 2013. [11] Siemens Solar Module SR50 Electrical Parameters
1997.

You might also like