Professional Documents
Culture Documents
Henrique G. Cabral, Paulo F. S. R. de Faria, Igor L. Guisso, Carlos E. B. Rambo, Bruno L. Vigna,
Maurício S. Santos, Vanderlei A. Vieira Jr., Renan C. Viero and Fernando S. dos Reis
Pontifícia Universidade Católica do Rio Grande do Sul, Porto Alegre, Brazil
e-mail: f.dosreis@gmail.com
Abstract – This paper reports a study on a grid-tied In order to safely and successfully inject the electrical
photovoltaic system, using a microinverter based on Ćuk power generated by distributed generation systems (DGS)
converter working in DCM. Since, when the Ćuk into the electrical power system, a series of control measures
converter is working in DCM, its output voltage presents must be taken. To avoid unsafe conditions, the DGS must
a linear behavior in relationship to its duty cycle. sense when the utility grid is disconnected either for
Therefore, the duty cycle must have a sinusoidal maintenance, by fault or human error. The islanding occurs
behavior, in absolute value, in order to generate a when the grid is offline, for any of the reasons above
rectified sine current waveform, at its output. The described, but the DGS still feeds the point of common
connection of a full bridge current source inverter in coupling (PCC). For this purpose, an anti-islanding (AI)
cascade with the Ćuk converter, allows obtaining a protection scheme must be used so as to avoid this unsafe
sinusoidal current waveform at the microinverter output. condition, effectively protecting the personnel and equipment
One of the most important challenges on microgeneration of the system. Strict test conditions for this phenomenon are
systems is the island detection. In this sense, if the system defined under IEEE 929 (Recommended Practice for Utility
is unable to detect the islanding, this may cause power Interface of Residential and Intermediate Photovoltaic (PV)
quality degradation, electrical safety threats, especially Systems) and must be followed to avoid islanding of
related to maintenance crews, and damage to third-party distributed resources.
devices connected to the same power grid. Several AI protection schemes have been developed and
are classified in two main categories: passive and active
Keywords – Anti-islanding, PV systems, DG, methods. Passive AI protection schemes sense the electrical
microinverter, renewable energy, Ćuk converter, DCM. parameters of the commercial power grid, and take action if
one of them is outside the desired standards. Active methods
I. INTRODUCTION try to cause disturbances at the PCC by altering the
magnitude, frequency or phase at the inverter output [2]. By
From the economic perspective, the microgeneration observing if the perturbation effectively occurs, the system
technology can offer benefits to both electric distribution and can detect an islanding condition and disconnect itself from
generation companies and consumers, since in this paradigm, the grid, given that in the presence of the power grid the
namely the distributed microgeneration, consumers also electrical parameters at the PCC are imposed by it.
assume the role of producers of electricity [1]. This is In this paper, a microinverter based on Ćuk converter is
especially true for photovoltaic (PV) panels, given that, proposed. This converter was chosen because it presents a
densely populated areas can also generate great amounts of current source behavior in its input and output. The presence
electric power by installing PV panels on its rooftops. Thus, of the output inductor gives to this circuit a current source
the main objective of this work is to develop a microinverter, characteristic, which turns out to be suitable for connection
including active islanding detection system, in order to inject to the power grid, which has voltage source characteristics,
the electric power generated by photovoltaic panels into the as is well known [3].
commercial power grid. In the following sections, a brief design methodology
The proposed microinverter is divided into two main based on the quasi-static approach will be presented for the
parts: the first one is based on the Ćuk converter, operating at Ćuk converter, as well as the component values used for the
high frequency (20 kHz), and the second section is actual prototype. Using a simulation tool and an
implemented by a full bridge current source inverter (CSI), experimental prototype, the proposed active anti-islanding
working at low frequency (mains frequency, in this case protection scheme was validated, and the obtained results are
60 Hz). The Ćuk converter is responsible for the synthesis of presented and discussed in the sequence of this paper.
sine current waveform, in absolute value, synchronized with
the power grid. The full bridge inverter in cascade with the II. OPERATION OF THE MICROINVERTER
converter ensures a sinusoidal current waveform at the
microinverter output. Considering the aforementioned Low power DC-DC converters operating in discontinuous
microinverter configuration, it is right ensure that, it provides conduction mode (DCM) are widely used for implementation
galvanic insulation, which is required in many countries. In of microinverters dedicated to PV systems, being one of the
this topology, the switching losses are also reduced. Once, best solutions for applications in low power [4]. This is due
only the Ćuk converter operates at high frequency. to several factors such as: a) their topological simplicity, b)
low implementation cost, c) simplicity of the control loop
V1 V2
where,
L1 L2 2 Leq
Leq = ; K = .
L1 + L2 TR
Fig 4. Equivalent circuit of a Ćuk converter operating in DCM,
second stage, while the diode is conducting.
D. Design Method and Parameters
In order to guarantee the operation of the Ćuk converter in
This stage ends when the diode turns off (t = tDon) as iL1
DCM, for all duty cycle values, the operation in the
and iL2 reach their minimal values (Imin for iL1 and – Imin for
boundary mode must be guaranteed, at the worst case. In the
iL2), resulting in (8).
boundary mode, static gain equations are the same, for both
converter-operating modes, DCM and CCM. The converter
V1 ton (8) static gain for CCM is obtained through the volt-second
t Don =
V2 balancing in the inductors, resulting in (12), since the
average voltage upon the inductors should be zero. As such,
C. Third Stage of Operation ( ton + tDon < t < T ) the equivalent inductance should be as described by (13) for
The third stage of operation of the converter begins when operation in DCM.
the currents iL1 and iL2 reach their minimal values. At that
moment, both currents flow in freewheeling, resulting in the d max
2 V2 = V1 (12)
diode blocking, as Fig 5 shows. 1 − d max
L1 L2
V12 V2 2 (13)
V1 + V2 Leq <
2 P f s ( V1 + 2 V2 )2
V1 V2
Imin where dmax is the maximum value of the duty cycle, which is
required when the output voltage is equal to the mains peak
Fig 5. Equivalent circuit of a Ćuk converter operating in DCM, value, V2 is the mains rms value, V1 is the PV maximum
third stage, when neither the diode nor the switch is conducting. power point voltage, fs is the switching frequency and P is
the output power. Therefore, by making both inductors twice generated by the inverter, if the impact of the anti-islanding
the inductance of Leq found on (13), operation in DCM can algorithm is imperceptible on PCC, it means that the power
be guaranteed. grid is on. Likewise, if the impact of the perturbation in the
For this particular implementation, the microinverter input electrical magnitudes on PCC is significant, a power failure
voltage is V1 = 34 Vdc considering the maximum power point is assumed and the DGS is disconnected.
(MPP) PV voltage (VMPP). The single-phase power mains
voltage establishes the output voltage V2 = 127 Vrms. Using TABLE II
the proposed design criteria, considering fs = 20 kHz, the IEEE 929 STANDARD – RESPONSE TO ABNORMAL
values of the inductors were determined, resulting VOLTAGES
L1 = L2 = 360 µH and dmax = 0.78. Voltage (at the PCC) Maximum Trip Time
V < 50 % 0.1 s
50 % ≤ V < 88 % 2.0 s
IV. ANTI-ISLANDING METHODS
88 % ≤ V ≤ 110 % Continuous operation
110 % < V < 137 % 2.0 s
An anti-islanding algorithm can be classified in two main 137 % ≤ V 0.03 s
categories: the passive and active methods. Passive
algorithms continuously sense the electrical characteristics at These perturbations, while small in comparison to the
the PCC, such as magnitude, frequency or phase. If the above power grid, can cause losses in the power extracted from PV
parameters diverge from the expected values as established panel and losses in power quality, when compared with the
by IEEE 929, the DGS disconnect itself from the grid [8]. normal operating conditions without any perturbations [8].
Active methods try to perturb the electrical parameters at When implementing an anti-islanding algorithm on a DC-DC
the PCC and can be further classified in three subcategories: converter, these perturbations are carried out by changing the
the residents in the inverter, those who are not resident in the duty cycle of the converter. If an MPPT algorithm is also
inverter and the methods based on the use of communication implemented on the same converter, this means that while
between the power grid operator and the anti-islanding the AI algorithm is active, the MPP is lost, thus, reducing the
detection scheme of the DGS [9]. time that the maximum power is extracted from the panel and
reducing the overall efficiency of the system.
A. Passive Methods
Usual passive anti-islanding methods consist of observing V. IMPLEMENTATION OF THE ANTI-ISLANDING
abnormal over or under voltage, as well as over or under ALGORITHM
frequency conditions. The IEEE 929 standard sets the
parameters for disconnection at the PCC, as shown on table On this paper, an active islanding detection method was
II with the voltage limits expressed as percentages of the described to a microinverter based on the Ćuk converter,
rated voltage at the PCC [10]. given that passive methods are not very effective when the
If a power outage occurs in the commercial power grid, load connected to the microinverter is balanced. The
three scenarios can be expected when observing solely the algorithm consists in the generation of a periodic disturbance
voltage at the PCC: at microinverter output voltage by reducing the maximum
• The power generated by the DGS surpasses the power value of the duty cycle (dmax) of the Ćuk converter. Given
consumed by the load and an increase in voltage at the that this momentary reduction on dmax withdraw the converter
PCC occurs. The system is, then, disconnected; from MPP, resulting in an electrical power production
• The power generated by the DGS is insufficient to reduction, a one second delay, between perturbations was
supply the load and voltage decreases at the PCC. The established in order to meet the IEEE 929 standard and to
system is, then, disconnected; maximize the electrical power production. Thus, every
• The load and the DGS are in balance and the voltage at second, the output voltage of the microinverter is disturbed
the PCC does not vary. The system fails to disconnect. and the voltage at the PCC is measured. If a voltage
Likewise, a very similar behavior can be seen on the disturbance at the PCC is observed, or its value is out of the
detection of under/over frequency: an increase or decrease of bounds specified in table II, the DGS should be
the frequency at the PCC occurs when the commercial power disconnected. Fig 6 summarizes the proposed anti-islanding
grid is disconnected. If the change in frequency is small algorithm.
enough, it may go undetected and the anti-islanding system This algorithm determines the PCC voltage rms value,
may fail. The IEEE 929 standard sets a maximum trip time every power mains cycle, in order to detect any voltage
of 0.1 s whenever the frequency at the PCC is not within disturbance that indicates an islanding occurrence. Figure 7
59.3 and 60.5 Hz [2]. shows the behavior of the maximum value of the duty cycle,
during a dmax perturbation, which occurs every second. The
B. Active Methods adopted reduction on dmax value it is fifty percent of its rated
Active anti-islanding methods that do not rely on the value in order to generate a sizable voltage drop at the
communication to the power grid operator essentially try to inverter output (VPCC), when an islanding condition occurs.
disturb electrical magnitudes on PCC by injecting In this event, the inverter is disabled, and physically
disturbance voltage, frequency, voltage harmonic content and disconnected from PCC, by a power contactor, through the
phase displacement, at the inverter output. Given that the output enable command signal as depicted in Fig 7. After the
power grid can effectively reject these disturbances
power grid reestablishment, a five minuttes delay is required is reduced, every 60 cycles, due to the action of the active
by IEEE 929 standard, before the inverterr reconnection. anti-islanding algorithm.