Instruction manual

Line differential Protection IED

GR200 series (GRL200)

GRL200---

S, G, and T positions

TOSHIBA ENERGY SYSTEMS & SOLUTIONS CORPORATION


Notice: GRL200 manual is issued for ‘033’, and
‘037’ software code, which you can identify at
the ’S,G&T positions’ on Software nameplate.
6F2S1914 (0.37)

Safety Precautions
Before using this equipment, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GR
equipment. Before installing and using the equipment, this chapter must be thoroughly read
and understood.
Explanation of symbols used
Signal words such as DANGER, WARNING, and CAUTION, will be followed by
important safety information that must be carefully reviewed.

DANGER Indicates an imminently hazardous situation which will result in


death or serious injury if you do not follow the instructions.
Indicates a potentially hazardous situation which could result in
WARNING
death or serious injury if you do not follow the instructions.
CAUTION Indicates a potentially hazardous situation which if not avoided,
may result in minor injury or moderate injury or property damage.

DANGER
•Current transformer circuit
Never allow the current transformer (CT) secondary circuit connected to this equipment to
be opened while the primary system is live. Opening the CT circuit will produce a
dangerously high voltage.

WARNING
•Exposed terminals
Do not touch the terminals of this equipment while the power is on, as the high voltage
generated is dangerous.
•Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.
•Fiber optic
CLASS 1 LASER PRODUCT.

ii
6F2S1914 (0.37)

CAUTION
•Earth
The earthing terminal of the equipment must be securely earthed.

CAUTION
•Operating environment
The equipment must only be used within the range of ambient temperature, humidity and
dust detailed in the specification and in an environment free of abnormal vibration.
•Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check
that they conform to the equipment ratings.
•Printed circuit board
Do not attach and remove printed circuit boards when the DC power to the equipment is
on, as this may cause the equipment to malfunction.
•External circuit
When connecting the output contacts of the equipment to an external circuit, carefully
check the supply voltage used in order to prevent the connected circuit from overheating.
•Connection cable
Carefully handle the connection cable without applying excessive force.
•Modification
Do not modify this equipment, as this may cause the equipment to malfunction.
•Short-wire(link)
Do not remove the short-link wire(s) connected to the frame earth (FG) at the terminal block
on the rear of the relay.
•Electric wire between #35 - #37 on the power-supply terminal block
Make sure the wire is connected.
(Exception: This wire needs to be detached for performing the dielectric voltage test.)

iii
6F2S1914 (0.37)

•Disposal
This equipment contains neither expendable supplies nor parts that can be recycled. When
disposing of this equipment, the customer must contact an operator responsible for
industrial waste disposal, and request that the operator dispose of this equipment in
accordance with the local waste disposal regulations; otherwise the person who disposes
of this equipment may be punished under local regulations. When disposing of this
equipment is practiced by the customer acting on their own behalf, it must be done so in a
safe manner according to local regulations. For further information in terms of the disposal,
the customer shall contact to a local dealer and sales staff at Toshiba Energy Systems &
Solutions Corporation (Toshiba ESS, Japan).
This equipment contains neither expendable supplies nor recyclables.
•Plastics material
This equipment contains the following plastics material.
- ABS, Polycarbonate, Acrylic resins, Nylon 66, and others.

Equipment installation and operation


•Equipment installation
Never remove cables at frame ground terminals (FGs) while the AC/DC power supplies.

•Equipment operation
The user shall have responsibilities to use and install the equipment where the
specifications are designated by the manufacture. Never operate the equipment on the
condition where the manufacture cannot intend. Otherwise, the safety function furnished
into the equipment may not be operated properly.

•Symbols
Symbol Description

Protective conductor terminal

Caution, risk of electric shock

iv
6F2S1914 (0.37)

Liability, copyright and others


•Disclaimer of liability
We have checked the description of this manual against the hardware and software
described, but we cannot guarantee that all deviations have been eliminated from the
description completely; hence, no liability can be accepted for any errors or omissions
contained in the information given. We review the information in this manual regularly
and there will be some corrections in subsequent editions. We reserve the right to make
technical improvements without notice.

•Copyright
© Toshiba Energy Systems & Solutions Corporation 2019.
All rights reserved.

•Registered Trademarks
Product/Equipment names (mentioned herein) may be trademarks of their respective
companies.

v
6F2S1914 (0.37)

Contents
1 Introduction ............................................................................................................................................ 1
Protection functions ........................................................................................................................ 2
1.1.1 Purposes of the protection ....................................................................................................... 2
1.1.2 Requirements in the protection functions .............................................................................. 2
1.1.3 Behavior of backup protections ............................................................................................... 4
1.1.4 Concepts of current differential protection (DIF) function ................................................... 6
1.1.5 Concepts of distance protection (ZS/ZG) function.................................................................. 6
1.1.6 Concepts of carrier command protection (DISCAR/DEFCAR) function ............................ 10
1.1.7 Tripping CB by the protection functions ................................................................................ 10
1.1.8 Autoreclosing CB (ARC) after the operation of the protection functions .......................... 11
1.1.9 Conventional applications ..................................................................................................... 11
Control............................................................................................................................................ 12
Monitoring and metering functions ............................................................................................. 12
Hardware overview ....................................................................................................................... 13
Symbols used in logical diagrams ................................................................................................ 14
Abbreviation .................................................................................................................................. 18
Function Block (FB), Function ID, Signal number (Data ID) .................................................... 19
2 Relay application .................................................................................................................................. 20
Current differential protection for the line ................................................................................. 21
Segregated-phase current differential protection function (DIFL) ........................................... 22
2.2.1 Differential protection characteristics (DIFL) ..................................................................... 22
2.2.2 Check relays characteristics (OCs and UVs) ....................................................................... 28
2.2.3 CT circuit-failure detection (DIFL-CTF) .............................................................................. 30
2.2.4 Charging-current compensation (DIFL-Ic) .......................................................................... 31
2.2.5 Differential current monitor (DIFL-IDSV) .......................................................................... 32
2.2.6 Setting ..................................................................................................................................... 34
2.2.7 Data ID ................................................................................................................................... 35
Zero-sequence current differential protection (DIFGL) ............................................................. 38
2.3.1 Differential protection characteristics (DIFGL) .................................................................. 38
2.3.2 Check relay characteristic (EFD).......................................................................................... 41
2.3.3 CT circuit-failure detection (DIFGL-CTF) ........................................................................... 42
2.3.4 Charging-current compensation (DIFGL-Ic) ....................................................................... 42
2.3.5 Setting ..................................................................................................................................... 44
2.3.6 Data ID ................................................................................................................................... 45
CT saturation countermeasure in DIFL (CTsat in DIFL) .......................................................... 46
2.4.1 Stabilization for CT saturation owing to through-fault current ........................................ 46
2.4.2 Settings against CT saturation ............................................................................................. 49
2.4.3 Setting ..................................................................................................................................... 51

vi
6F2S1914 (0.37)

Setting DIFL accounting for CT ratio/rating and fault currents ............................................... 52


2.5.1 Nature of CT ratios matching ............................................................................................... 52
2.5.2 Nature of CT ratings matching ............................................................................................. 53
2.5.3 Nature for fault current setting ............................................................................................ 53
DIFL operations for 1.5CB arrangement .................................................................................... 56
2.6.1 Through-fault-current encountered by DIF (TFC in DIFL and DIFGL) ........................... 56
2.6.2 Settings in TFC ...................................................................................................................... 64
2.6.3 Data IDs in TFC ..................................................................................................................... 64
2.6.4 Stub protected by DIFL (Stub-DIFL) ................................................................................... 65
2.6.5 Settings in Stub...................................................................................................................... 67
2.6.6 Data ID in Stub ...................................................................................................................... 68
2.6.7 DIFL applied to double circuit line with a fault (Fault current outflowing) ..................... 69
DIFL applied to three-terminal line (RDIF and Fault current flowing) ................................... 70
2.7.1 Remote different trip ............................................................................................................. 70
2.7.2 Setting ..................................................................................................................................... 77
2.7.3 Data ID ................................................................................................................................... 77
2.7.4 Nature of outflowing current in case of internal fault ........................................................ 79
2.7.5 Nature of CT saturation in case of external fault ............................................................... 80
DIFL applied to protect the blind zone ........................................................................................ 81
Stub protection with overcurrent relay (STUB-OC) ................................................................... 83
2.9.1 Stub-OC characteristic .......................................................................................................... 84
2.9.2 Scheme logic ........................................................................................................................... 84
2.9.3 Setting ..................................................................................................................................... 86
2.9.4 Data ID ................................................................................................................................... 87
Distance protection (ZS/ZG) ......................................................................................................... 88
2.10.1 Principle of distance measurement ...................................................................................... 89
2.10.2 Equations in distance protection function ........................................................................... 93
2.10.3 Element characteristic in distance relay............................................................................ 100
2.10.4 Common application for ZS and ZG.................................................................................... 114
2.10.5 Command protection feature............................................................................................... 121
2.10.6 Extended application ........................................................................................................... 126
2.10.7 Scheme logic ......................................................................................................................... 129
2.10.8 Tips to set the main/remote backup relays ........................................................................ 145
2.10.9 Tips to set the distance zones for multi-terminal lines ..................................................... 149
2.10.10 ZS/ZG test ......................................................................................................................... 151
2.10.11 Setting ............................................................................................................................... 152
2.10.12 Data ID .............................................................................................................................. 168
Direct transfer trip (DTT) ........................................................................................................... 177
2.11.1 Setting for the operation...................................................................................................... 178

vii
6F2S1914 (0.37)

2.11.2 Scheme logic ......................................................................................................................... 179


2.11.3 Setting ................................................................................................................................... 180
2.11.4 Data ID ................................................................................................................................. 180
Distance carrier command protection (DISCAR) ...................................................................... 182
2.12.1 Permissive underreach protection (PUP) ........................................................................... 183
2.12.2 Permissive overreach protection (POP) .............................................................................. 184
2.12.3 Unblocking overreach protection (UOP) ............................................................................ 187
2.12.4 Blocking overreach protection (BOP) ................................................................................. 189
2.12.5 Protection for week infeed terminal ................................................................................... 192
2.12.6 Countermeasure for current reversal ................................................................................. 194
2.12.7 Programing DISCAR using PLC function .......................................................................... 196
2.12.8 Setting ................................................................................................................................... 197
2.12.9 Data ID ................................................................................................................................. 198
Directional earth fault command protection (DEFCAR) .......................................................... 200
2.13.1 Permissive overreach protection (POP) .............................................................................. 201
2.13.2 Unblocking overreach protection (UOP) ............................................................................ 204
2.13.3 Blocking overreach protection (BOP) ................................................................................. 204
2.13.4 Coordination with DISCAR protection ............................................................................... 206
2.13.5 Programing DEFCAR using PLC function ........................................................................ 207
2.13.6 Setting ................................................................................................................................... 208
2.13.7 Data ID ................................................................................................................................. 209
Switch on to fault (SOTF-OC) .................................................................................................... 211
2.14.1 Scheme logic ......................................................................................................................... 212
2.14.2 Setting ................................................................................................................................... 214
2.14.3 Data ID ................................................................................................................................. 214
Overcurrent protection (OC)....................................................................................................... 215
2.15.1 Relay polarity ....................................................................................................................... 216
2.15.2 Inverse time and definite time delay characteristic .......................................................... 219
2.15.3 Threshold value for operation ............................................................................................. 226
2.15.4 Reset Ratio............................................................................................................................ 226
2.15.5 Miscellaneous functions....................................................................................................... 226
2.15.6 Scheme logic ......................................................................................................................... 228
2.15.7 Setting ................................................................................................................................... 230
2.15.8 Data ID ................................................................................................................................. 235
Earth fault protection (EF) ......................................................................................................... 238
2.16.1 Relay polarity ....................................................................................................................... 239
2.16.2 Inverse time and definite time delay characteristic .......................................................... 241
2.16.3 Threshold level for operation .............................................................................................. 246
2.16.4 Reset Ratio............................................................................................................................ 246

viii
6F2S1914 (0.37)

2.16.5 Miscellaneous functions....................................................................................................... 246


2.16.6 Scheme logic ......................................................................................................................... 247
2.16.7 Setting ................................................................................................................................... 249
2.16.8 Data ID ................................................................................................................................. 254
Negative sequence overcurrent protection (OCN) .................................................................... 256
2.17.1 Relay polarity ....................................................................................................................... 257
2.17.2 Inverse time and definite time delay characteristic .......................................................... 259
2.17.3 Threshold value .................................................................................................................... 264
2.17.4 Reset Ratio............................................................................................................................ 264
2.17.5 Miscellaneous functions....................................................................................................... 264
2.17.6 Scheme logic ......................................................................................................................... 265
2.17.7 Setting ................................................................................................................................... 267
2.17.8 Data ID ................................................................................................................................. 272
Thermal overload function (THM) ............................................................................................. 274
2.18.1 Thermal state determination .............................................................................................. 275
2.18.2 Thermal characteristic ........................................................................................................ 276
2.18.3 Scheme logic ......................................................................................................................... 277
2.18.4 Setting ................................................................................................................................... 278
2.18.5 Data ID ................................................................................................................................. 279
Broken conductor protection (BCD) ........................................................................................... 280
2.19.1 Equivalent circuit for a one-phase series fault .................................................................. 281
2.19.2 Characteristic and setting ................................................................................................... 283
2.19.3 Miscellaneous functions....................................................................................................... 283
2.19.4 Scheme logic ......................................................................................................................... 284
2.19.5 Setting ................................................................................................................................... 284
2.19.6 Data ID ................................................................................................................................. 285
Circuit breaker fail protection (CBF)......................................................................................... 286
2.20.1 CBF operation and its elements ......................................................................................... 287
2.20.2 Re-trip feature ...................................................................................................................... 287
2.20.3 Backup feature ..................................................................................................................... 288
2.20.4 Scheme logic ......................................................................................................................... 290
2.20.5 Operation timing .................................................................................................................. 292
2.20.6 Setting ................................................................................................................................... 293
2.20.7 Data ID ................................................................................................................................. 294
Overvoltage protection for phase-to-neutral (OV) .................................................................... 296
2.21.1 Drop-off and pickup characteristic ..................................................................................... 297
2.21.2 Delay for the operation of the OV element ........................................................................ 297
2.21.3 Time characteristic .............................................................................................................. 297
2.21.4 Miscellaneous functions....................................................................................................... 300

ix
6F2S1914 (0.37)

2.21.5 Scheme logic ......................................................................................................................... 300


2.21.6 Setting list ............................................................................................................................ 302
2.21.7 Data ID ................................................................................................................................. 303
Overvoltage protection for phase-to-phase (OVS)..................................................................... 304
2.22.1 Drop-off and pickup setting ................................................................................................. 305
2.22.2 Delay for the operation of the OVS element ...................................................................... 305
2.22.3 Time characteristic .............................................................................................................. 305
2.22.4 Miscellaneous functions....................................................................................................... 307
2.22.5 Scheme logic ......................................................................................................................... 308
2.22.6 Setting list ............................................................................................................................ 309
2.22.7 Data ID ................................................................................................................................. 310
Earth fault overvoltage protection (OVG) ................................................................................. 311
2.23.1 Drop-off and pickup setting ................................................................................................. 312
2.23.2 Delay of the operation of the OVG element ....................................................................... 312
2.23.3 Time characteristic .............................................................................................................. 312
2.23.4 Miscellaneous functions....................................................................................................... 315
2.23.5 Scheme logic ......................................................................................................................... 315
2.23.6 Setting ................................................................................................................................... 317
2.23.7 Data ID ................................................................................................................................. 318
Phase under-voltage protection (UV) ......................................................................................... 319
2.24.1 Drop-off and pick-up characteristic .................................................................................... 320
2.24.2 Time characteristic .............................................................................................................. 320
2.24.3 Miscellaneous functions....................................................................................................... 323
2.24.4 Scheme logic ......................................................................................................................... 323
2.24.5 Setting ................................................................................................................................... 325
2.24.6 Data ID ................................................................................................................................. 326
Phase-to-phase under-voltage protection (UVS) ....................................................................... 327
2.25.1 Drop-off and pick-up characteristic .................................................................................... 328
2.25.2 Time characteristic .............................................................................................................. 328
2.25.3 Miscellaneous functions....................................................................................................... 331
2.25.4 Scheme logic ......................................................................................................................... 331
2.25.5 Setting ................................................................................................................................... 333
2.25.6 Data ID ................................................................................................................................. 334
Frequency protection (FRQ/DFRQ) ........................................................................................... 336
2.26.1 FRQ features and characteristics ....................................................................................... 337
2.26.2 DFRQ features and characteristics .................................................................................... 339
2.26.3 Setting ................................................................................................................................... 341
2.26.4 Data ID ................................................................................................................................. 343
Out of step tripping by voltage (OSTV) ..................................................................................... 346

x
6F2S1914 (0.37)

2.27.1 Operation characteristic ...................................................................................................... 347


2.27.2 Scheme logic and settings ................................................................................................... 349
2.27.3 Setting ................................................................................................................................... 350
2.27.4 Data ID ................................................................................................................................. 351
Inrush current detection function (ICD).................................................................................... 352
2.28.1 Operation and characteristic............................................................................................... 353
2.28.2 Scheme logic ......................................................................................................................... 353
2.28.3 Setting ................................................................................................................................... 354
2.28.4 Data ID ................................................................................................................................. 354
Fail safe (FS)................................................................................................................................ 355
2.29.1 Overcurrent element (OCFS) .............................................................................................. 356
2.29.2 Phase current change detector element (OCDFS) ............................................................. 356
2.29.3 Earth fault current element (EFFS) ................................................................................... 356
2.29.4 Multi-level overcurrent elements (OCMFS) ...................................................................... 357
2.29.5 Under-voltage element for phase-to-earth (UVFS) ........................................................... 358
2.29.6 Under-voltage element for phase-to-phase (UVSFS) ........................................................ 358
2.29.7 Under-voltage change detection element (DUVFS) .......................................................... 358
2.29.8 Scheme logic ......................................................................................................................... 359
2.29.9 Setting ................................................................................................................................... 361
2.29.10 Data ID list ....................................................................................................................... 362
VT failure detection (VTF).......................................................................................................... 363
2.30.1 VTF features ......................................................................................................................... 364
2.30.2 Operation for the VTF function .......................................................................................... 364
2.30.3 VTF Logic ............................................................................................................................. 365
2.30.4 Setting ................................................................................................................................... 367
2.30.5 Data ID ................................................................................................................................. 368
CT failure detection (CTF).......................................................................................................... 369
2.31.1 CTF features ......................................................................................................................... 370
2.31.2 Operation for the CTF function .......................................................................................... 370
2.31.3 Scheme logic ......................................................................................................................... 370
2.31.4 Setting ................................................................................................................................... 372
2.31.5 Data ID ................................................................................................................................. 373
Multi-end fault locator (FL-A and FL-Z) ................................................................................... 374
2.32.1 FL calculation with data at a local-terminal and remote-terminals ................................ 375
2.32.2 FL calculation with data at a local-terminal only ............................................................. 382
2.32.3 Selection of calculation results............................................................................................ 388
2.32.4 Screen of FL output ............................................................................................................. 389
2.32.5 Preparation and consideration of setting ........................................................................... 392
2.32.6 Setting procedure ................................................................................................................. 394

xi
6F2S1914 (0.37)

2.32.7 Setting ................................................................................................................................... 398


2.32.8 Data ID ................................................................................................................................. 400
Trip circuit (TRC) ........................................................................................................................ 401
2.33.1 Command for tripping CB and signal to block reclosing CB#1/CB#2 .............................. 404
2.33.2 Recording identifiers for respective fault types ................................................................. 407
2.33.3 Scheme logic ......................................................................................................................... 408
2.33.4 Setting ................................................................................................................................... 413
2.33.5 Data ID ................................................................................................................................. 414
Autoreclose (ARC) ....................................................................................................................... 416
2.34.1 Overview ............................................................................................................................... 417
2.34.2 Terminology .......................................................................................................................... 422
2.34.3 Function block diagram ....................................................................................................... 427
2.34.4 Timing diagram .................................................................................................................... 436
2.34.5 Autoreclosing logics ............................................................................................................. 439
2.34.6 Setting ................................................................................................................................... 463
2.34.7 Data ID ................................................................................................................................. 465
Voltage check for autoreclose (VCHK) ....................................................................................... 471
2.35.1 VCHK1 for 1CB system ....................................................................................................... 472
2.35.2 VCHK1 and VCHK2 for 1.5CB system .............................................................................. 473
2.35.3 Scheme for synchronism ...................................................................................................... 474
2.35.4 VCHK1 setting for 1CB system .......................................................................................... 479
2.35.5 VCHK1 and VCHK2 settings for 1.5CB system ................................................................ 483
2.35.6 Scheme and activation ......................................................................................................... 485
2.35.7 Setting ................................................................................................................................... 487
2.35.8 Data ID ................................................................................................................................. 489
Transmission control function (DIF_COMM)............................................................................ 490
2.36.1 Data communication interface ............................................................................................ 491
2.36.2 Synchronization control ....................................................................................................... 492
2.36.3 Topology of telecommunication ........................................................................................... 500
2.36.4 Communication setup .......................................................................................................... 501
2.36.5 Setting ................................................................................................................................... 503
2.36.6 Data ID ................................................................................................................................. 504
Communication application (COMM_APPL) ............................................................................ 505
2.37.1 Relay-address configuration................................................................................................ 506
2.37.2 Sub-communication channel for 1CB arrangement .......................................................... 507
2.37.3 Sub-communication channel for 1.5CB arrangement ....................................................... 509
2.37.4 Integral communication bits ............................................................................................... 510
2.37.5 Communication bits for OSTV ............................................................................................ 511
2.37.6 Usage of sub-communication channel ................................................................................ 511

xii
6F2S1914 (0.37)

2.37.7 Setting of open terminal detection...................................................................................... 511


2.37.8 Communication test ............................................................................................................. 512
2.37.9 Setting ................................................................................................................................... 513
2.37.10 Data ID .............................................................................................................................. 514
Protection common (PROT_COMMON) .................................................................................... 531
2.38.1 Selection of breaker system ................................................................................................. 532
2.38.2 Decision of CB open/close status ......................................................................................... 532
2.38.3 Decision of DS open/close status ......................................................................................... 535
2.38.4 Dead line detection .............................................................................................................. 536
2.38.5 Detection of current change (OCD)..................................................................................... 537
2.38.6 User logic switches ............................................................................................................... 538
2.38.7 Setting ................................................................................................................................... 539
2.38.8 Data ID ................................................................................................................................. 540
Cold load protection (CLP) ......................................................................................................... 543
2.39.1 Scheme logic ......................................................................................................................... 544
2.39.2 Setting ................................................................................................................................... 546
2.39.3 Data ID ................................................................................................................................. 547
3 General control function .................................................................................................................... 548
Control scheme ............................................................................................................................ 549
Control mode................................................................................................................................ 552
3.2.1 Select-before-operation mode (SBO) ................................................................................... 552
3.2.2 Direct-operation mode (DIR) ............................................................................................... 553
Control hierarchy ........................................................................................................................ 555
3.3.1 Control level and control point............................................................................................ 556
3.3.2 Selector switches and bay operations ................................................................................. 556
3.3.3 Programming of control-right distributions ....................................................................... 556
Common controls (CMNCTRL) .................................................................................................. 558
3.4.1 Double command blocking (DCB) ....................................................................................... 559
3.4.2 PLC_BIT/UNIT/BOOL signal ............................................................................................. 561
3.4.3 Provision of selected status ................................................................................................. 561
3.4.4 Miscellaneous settings ......................................................................................................... 561
3.4.5 Setting ................................................................................................................................... 562
3.4.6 Signal .................................................................................................................................... 563
Local, remote and PLC control ................................................................................................... 567
3.5.1 Local control ......................................................................................................................... 568
3.5.2 Remote control...................................................................................................................... 568
3.5.3 Programmable logic control (PLC)...................................................................................... 568
3.5.4 Signal for Local/Remote control .......................................................................................... 569
3.5.5 Signal .................................................................................................................................... 570

xiii
6F2S1914 (0.37)

LED reset function (LEDR) ........................................................................................................ 571


3.6.1 Select logic for resetting LEDs ............................................................................................ 572
3.6.2 Cancel logic in SBO mode .................................................................................................... 575
3.6.3 Operate logic for SBO/DIR mode ........................................................................................ 576
3.6.4 Settings in LED logics ......................................................................................................... 578
3.6.5 Mapping for IEC61850 communication.............................................................................. 579
3.6.6 Setting ................................................................................................................................... 583
3.6.7 Signal .................................................................................................................................... 584
Counter function for the general (GCNT) ................................................................................. 585
3.7.1 Counter setting for a signal................................................................................................. 586
3.7.2 Select logics for SBO/DIR modes ........................................................................................ 588
3.7.3 Cancel logic for SBO mode .................................................................................................. 593
3.7.4 Operate logic for SBO/DIR modes....................................................................................... 595
3.7.5 Mapping for IEC61850 communication.............................................................................. 598
3.7.6 Setting ................................................................................................................................... 602
3.7.7 Signal .................................................................................................................................... 603
Mode control function (MDCTRL).............................................................................................. 605
3.8.1 Function ................................................................................................................................ 606
3.8.2 Mapping for IEC61850 communication.............................................................................. 607
3.8.3 Setting ................................................................................................................................... 611
3.8.4 Signal .................................................................................................................................... 612
4 Control and monitoring application .................................................................................................. 614
Single position device function (SPOS)...................................................................................... 615
4.1.1 Selection logic for SBO/DIR modes ..................................................................................... 616
4.1.2 Cancel logic for SBO mode .................................................................................................. 631
4.1.3 Operate logic for SBO/DIR modes....................................................................................... 635
4.1.4 Setup for BIO module .......................................................................................................... 650
4.1.5 Mapping for IEC 61850 communication............................................................................. 658
4.1.6 Setting ................................................................................................................................... 662
4.1.7 Signal .................................................................................................................................... 663
Double position controller with synchronizing-checking (DPSY) ............................................ 666
4.2.1 Select logic for SBO/DIR modes .......................................................................................... 667
4.2.2 Cancel logic for SBO mode .................................................................................................. 682
4.2.3 Operate logic for SBO/DIR modes....................................................................................... 686
4.2.4 Operation counter ................................................................................................................ 702
4.2.5 Measurement of operation intervals .................................................................................. 706
4.2.6 Setup for BIO module .......................................................................................................... 708
4.2.7 Mapping for IEC 61850 communication............................................................................. 719
4.2.8 Setting ................................................................................................................................... 723

xiv
6F2S1914 (0.37)

4.2.9 Signal .................................................................................................................................... 725


Software switch controller function (SOFTSW) ........................................................................ 730
4.3.1 SOFTSW controlling ............................................................................................................ 731
4.3.2 Control logics for SBO/DIR modes ...................................................................................... 734
4.3.3 Cancel logic for SBO mode .................................................................................................. 743
4.3.4 Operate logic for SBO/DIR modes....................................................................................... 743
4.3.5 Mapping for IEC 61850 communication............................................................................. 751
4.3.6 Setting ................................................................................................................................... 755
4.3.7 Signal .................................................................................................................................... 756
Operation time reset function (OPTIM) .................................................................................... 765
4.4.1 Select logic for SBO/DIR modes .......................................................................................... 767
4.4.2 Cancel logic in SBO mode .................................................................................................... 770
4.4.3 Operate logic for SBO/DIR modes....................................................................................... 771
4.4.4 Mapping for IEC61850 communication.............................................................................. 773
4.4.5 Setting ................................................................................................................................... 777
4.4.6 Signal .................................................................................................................................... 778
Total time measurement function (TOTALTIM) ....................................................................... 779
4.5.1 Operation feature ................................................................................................................. 780
4.5.2 Preparation for operation .................................................................................................... 782
4.5.3 Mapping for IEC 61850 communication............................................................................. 783
4.5.4 Setting ................................................................................................................................... 787
4.5.5 Signal .................................................................................................................................... 788
Synchronizing check for different network (SYNDIF) ............................................................. 792
4.6.1 Relays to check line-outage ................................................................................................. 793
4.6.2 Synchronization check relays .............................................................................................. 795
4.6.3 Line-outage check ................................................................................................................ 801
4.6.4 Synchronization check ......................................................................................................... 806
4.6.5 Relay selection for checking synchronization .................................................................... 810
4.6.6 Voltage selection for line arrangement ............................................................................... 812
4.6.7 Setting ................................................................................................................................... 814
4.6.8 Signal .................................................................................................................................... 816
Software interlock function (ILK) .............................................................................................. 819
4.7.1 ILK specification .................................................................................................................. 820
4.7.2 Interlock-check formula ....................................................................................................... 821
4.7.3 Interlock-check method ....................................................................................................... 823
4.7.4 Configuration of Interlock formulae ................................................................................... 829
4.7.5 Signal .................................................................................................................................... 830
Double position device function (DPOS) .................................................................................... 837
4.8.1 Select logic for SBO/DIR modes .......................................................................................... 838

xv
6F2S1914 (0.37)

4.8.2 Cancel logic for SBO mode .................................................................................................. 856


4.8.3 Operate logic for SBO/DIR modes....................................................................................... 860
4.8.4 Operation counter ................................................................................................................ 877
4.8.5 Measurement of operation intervals .................................................................................. 881
4.8.6 Setup for BIO module .......................................................................................................... 883
4.8.7 Mapping for IEC61850 communication.............................................................................. 894
4.8.8 Setting ................................................................................................................................... 898
4.8.9 Signal .................................................................................................................................... 900
Three position device function (TPOS) ...................................................................................... 903
4.9.1 Select logic for SBO/DIR modes .......................................................................................... 905
4.9.2 Cancel logic for SBO mode .................................................................................................. 926
4.9.3 Operate logic for SBO/DIR modes....................................................................................... 930
4.9.4 Operation counter ................................................................................................................ 954
4.9.5 Measurement of operation Intervals .................................................................................. 958
4.9.6 Setup for BIO module .......................................................................................................... 961
4.9.7 Mapping for IEC61850 commination ................................................................................. 972
4.9.8 Setting ................................................................................................................................... 976
4.9.9 Signal .................................................................................................................................... 978
Event detection function for general BIs (GENBI) ................................................................... 983
4.10.1 Operation features ............................................................................................................... 984
4.10.2 Mapping for IEC61850 communication.............................................................................. 987
4.10.3 Setting ................................................................................................................................... 989
4.10.4 Signals .................................................................................................................................. 990
Automatic sequence control function (ASEQ) ........................................................................... 992
4.11.1 Function setup...................................................................................................................... 993
4.11.2 Preparation of the operation ............................................................................................... 994
4.11.3 Example of automatic sequence operation ......................................................................... 995
4.11.4 Control hierarchy conditions ............................................................................................... 997
4.11.5 Input for emergency stop ..................................................................................................... 997
4.11.6 Mapping for IEC61850 communication.............................................................................. 999
4.11.7 Setting ................................................................................................................................. 1003
4.11.8 Signal .................................................................................................................................. 1004
5 Technical Description ....................................................................................................................... 1006
IED case and module slot ......................................................................................................... 1009
5.1.1 1/1 Case ............................................................................................................................... 1009
5.1.2 3/4 case ................................................................................................................................ 1011
5.1.3 1/2 case ................................................................................................................................ 1013
Transformer module for AC analog input (VCT)..................................................................... 1015
5.2.1 VCT11B ............................................................................................................................... 1016

xvi
6F2S1914 (0.37)

5.2.2 VCT12B............................................................................................................................... 1017


5.2.3 Constitution of VCT ........................................................................................................... 1018
5.2.4 Setting VCT ratio ............................................................................................................... 1019
5.2.5 Changing VCT rated current ............................................................................................ 1020
5.2.6 Settings for residual voltage, CT polarity, and busbar arrangements ........................... 1023
Signal processing and communication module (CPU) ............................................................ 1028
5.3.1 Signal processing ............................................................................................................... 1028
5.3.2 Configuration switch.......................................................................................................... 1029
5.3.3 Communication modules ................................................................................................... 1030
5.3.4 Location of communication modules................................................................................. 1034
5.3.5 Implementation rules ........................................................................................................ 1037
Binary IO module (BI, BO, and BIO)....................................................................................... 1038
5.4.1 Binary input feature .......................................................................................................... 1039
5.4.2 Binary input circuit ........................................................................................................... 1040
5.4.3 Binary output feature ........................................................................................................ 1049
5.4.4 Binary output circuit ......................................................................................................... 1051
5.4.5 Structure of binary IO Module .......................................................................................... 1057
5.4.6 Settings of binary input circuits ....................................................................................... 1063
5.4.7 Signals (Data ID) of binary input circuits ........................................................................ 1065
5.4.8 Settings of binary output circuits ..................................................................................... 1068
5.4.9 Signals (Data ID) of binary output circuits...................................................................... 1070
Power supply module (PWS) .................................................................................................... 1072
Human Machine Interface (HMI) ............................................................................................ 1075
5.6.1 Outlook................................................................................................................................ 1075
5.6.2 LED Indicators ................................................................................................................... 1076
5.6.3 Function keys with LEDs .................................................................................................. 1081
5.6.4 Monitoring jacks................................................................................................................. 1086
5.6.5 Operation keys ................................................................................................................... 1088
Clock function ............................................................................................................................ 1089
5.7.1 Clock setting ....................................................................................................................... 1089
5.7.2 Selection of date and time formats ................................................................................... 1089
5.7.3 Time Synchronization ........................................................................................................ 1090
5.7.4 Setting time zone ............................................................................................................... 1094
5.7.5 DST setting (Summer time setting).................................................................................. 1095
5.7.6 Setting ................................................................................................................................. 1097
Group setting for protection functions ..................................................................................... 1098
6 Engineering tool................................................................................................................................ 1101
Overview of GR-TIEMS ............................................................................................................ 1102
Connection ................................................................................................................................. 1103

xvii
6F2S1914 (0.37)

Common tools ............................................................................................................................ 1103


Monitoring tools......................................................................................................................... 1104
Record tools ................................................................................................................................ 1104
Generic configuration tools ....................................................................................................... 1105
IEC 61850 configuration tool.................................................................................................... 1105
IEC 60870-5-103 configuration tool ......................................................................................... 1105
MIMIC configuration tool ......................................................................................................... 1106
7 PLC function ..................................................................................................................................... 1107
Overview of PLC function ......................................................................................................... 1108
PLC data error ........................................................................................................................... 1108
PLC driver.................................................................................................................................. 1109
PLC setting samples ..................................................................................................................1113
7.4.1 Tele-protection scheme using DISCAR and DEFCAR commands ..................................1113
7.4.2 Transfer trip using DTT scheme ........................................................................................1119
7.4.3 Remote DIFL/DIFGL trip using communication scheme ............................................... 1123
8 Recording function ............................................................................................................................ 1128
Fault recorder ............................................................................................................................ 1129
8.1.1 Types of recording information ......................................................................................... 1129
8.1.2 Screen information............................................................................................................. 1132
8.1.3 Setup for the fault recorder ............................................................................................... 1133
8.1.4 Scheme logic ....................................................................................................................... 1136
8.1.5 Setting ................................................................................................................................. 1137
8.1.6 Signal (Data ID) ................................................................................................................. 1137
Event recorder ........................................................................................................................... 1138
8.2.1 Trigger signals .................................................................................................................... 1138
8.2.2 Trigger modes ..................................................................................................................... 1143
8.2.3 Screen information............................................................................................................. 1144
8.2.4 Setup for the event recorder.............................................................................................. 1144
8.2.5 Setting ................................................................................................................................. 1145
8.2.6 Signal (Data ID) ................................................................................................................. 1145
Disturbance recorder................................................................................................................. 1146
8.3.1 Recording time and amount .............................................................................................. 1146
8.3.2 Relays within disturbance recorder .................................................................................. 1146
8.3.3 Maximum number for recording disturbance phenomena ............................................. 1147
8.3.4 Number of analog quantities and logical signals for disturbance recorder ................... 1147
8.3.5 Trigger settings for PLC programming ............................................................................ 1150
8.3.6 Screen information............................................................................................................. 1150
8.3.7 Interpolation of transferred data ...................................................................................... 1151
8.3.8 Setting ................................................................................................................................. 1152

xviii
6F2S1914 (0.37)

8.3.9 Signal (Data ID) ................................................................................................................. 1153


Transferred information during fault ...................................................................................... 1154
8.4.1 Transferred metering values ............................................................................................. 1155
8.4.2 Transferred information about tripped phase and mode ................................................ 1157
8.4.3 Transferred state information ........................................................................................... 1157
8.4.4 Transferring record value and information ..................................................................... 1158
9 Monitoring function .......................................................................................................................... 1169
Outline ....................................................................................................................................... 1170
Metering data (Metering group)............................................................................................... 1170
9.2.1 Metering information on the screen ................................................................................. 1171
9.2.2 Setting for measurements ................................................................................................. 1172
9.2.3 Diminishing a very small value to display zero ............................................................... 1173
9.2.4 Flow settings for active/reactive/apparent powers .......................................................... 1173
9.2.5 Polarity setting for power factor values ........................................................................... 1174
9.2.6 Setting for the report (Dead band feature) ...................................................................... 1176
Statistics data (Power value group) ......................................................................................... 1178
9.3.1 Power information on the screen ...................................................................................... 1178
9.3.2 Setting for power values .................................................................................................... 1178
9.3.3 Regulation of power values ............................................................................................... 1178
Statistics data (Demand value group) ..................................................................................... 1179
9.4.1 Demand information on the screen .................................................................................. 1179
9.4.2 Max/Min/Averaged information about the demand feature ........................................... 1179
9.4.3 Demand cycle...................................................................................................................... 1180
9.4.4 Resetting data in demand features .................................................................................. 1180
Statistics data (Peak-demand value group) ............................................................................ 1181
9.5.1 Max/Min/Averaged information about the peak-demand feature .................................. 1181
9.5.2 Resetting data of peak-demand features.......................................................................... 1181
Statistics data (Counter group) ................................................................................................ 1182
9.6.1 Count information on the screen ...................................................................................... 1182
9.6.2 Report setting for GCNT (Dead band feature)................................................................. 1182
Statistics data (Accumulated time) .......................................................................................... 1183
Statistics data (Total time group) ............................................................................................ 1184
9.8.1 Time information on the screen ........................................................................................ 1184
9.8.2 Report setting for TOTALTIM (Dead band feature) ........................................................ 1184
Monitoring for miscellaneous functions................................................................................... 1185
Setting ........................................................................................................................................ 1186
Data ID....................................................................................................................................... 1187
10 Automatic supervision .................................................................................................................. 1192
Outline of automatic supervision ............................................................................................. 1193

xix
6F2S1914 (0.37)

Generic supervision tasks ......................................................................................................... 1196


10.2.1 Mismatch between ROM and RAM data (ROM/RAM error) .......................................... 1198
10.2.2 Supervision of check-sum error (SUM error) ................................................................... 1199
10.2.3 Supervision of RAM (RAM error) ..................................................................................... 1200
10.2.4 Supervision of ECC on memory (ECC error) ................................................................... 1201
10.2.5 Supervision of MRAM (MRAM) ........................................................................................ 1202
10.2.6 Supervision of FPGA (FPGA error)................................................................................... 1203
10.2.7 Supervision of program codes (CPU error) ...................................................................... 1204
10.2.8 Supervision of task operation (RUN error) ...................................................................... 1205
10.2.9 Detecting non-maskable interrupt (NMI error)............................................................... 1206
10.2.10 Supervision of sampling period (SMP error) ................................................................ 1207
10.2.11 Supervision of setting data (Setting error) ................................................................... 1208
10.2.12 Supervision of real-time clock (RTC error) ................................................................... 1209
10.2.13 Supervision of analog input data on VCTs (AI ACC error) ......................................... 1210
10.2.14 Abnormal currents flowing in CTs (CT error) .............................................................. 1211
10.2.15 Current transformer failure (CT fail) ........................................................................... 1212
10.2.16 Supervision of the current in zero-sequence (I0 error) ................................................ 1213
10.2.17 Supervision of voltage in negative-sequence (V2 error) .............................................. 1214
10.2.18 Supervision of voltage in zero-sequence (VZ error) ..................................................... 1215
10.2.19 Supervision of binary IO module#1 (BIO#1 error) ...................................................... 1216
10.2.20 Supervision of binary IO module#2 (BIO#2 error) ...................................................... 1217
10.2.21 Supervision of binary IO module#3 (BIO#3 error) ...................................................... 1218
10.2.22 Supervision of binary IO module#4 (BIO#4 error) ...................................................... 1219
10.2.23 Supervision of binary IO module#5 (BIO#5 error) ...................................................... 1220
10.2.24 Supervision of binary IO module#6 (BIO#6 error) ...................................................... 1221
10.2.25 Supervision of binary IO module#7 (BIO#7 error) ...................................................... 1222
10.2.26 Supervision of binary IO module#8 (BIO#8 error) ...................................................... 1223
10.2.27 Supervision of human machine interface (HMI error) ................................................ 1224
10.2.28 Supervision of power supply module (Power error) ..................................................... 1225
10.2.29 Supervision of data in PLC function (PLC data error) ................................................ 1226
10.2.30 Voltage transformer failure (VT fail) ............................................................................ 1227
10.2.31 Supervision of circuit breaker contacts (CB1/CB2 fail) ............................................... 1228
10.2.32 Supervision of disconnector contacts (DS fail) ............................................................. 1229
10.2.33 Supervision of LAN status (LAN error) ........................................................................ 1230
10.2.34 Supervision of response for pinging (Ping error) ......................................................... 1231
10.2.35 Supervision of link redundant entity (LRE error) ....................................................... 1232
10.2.36 Supervision of data in 61850 settings (Commslv error) .............................................. 1233
10.2.37 Supervision of GOOSE publishing (LAN(GOOSE)error) ............................................ 1234
10.2.38 Aux. contacts monitoring (DPSY/DOPS/TOPS faulty or undefined) .......................... 1235

xx
6F2S1914 (0.37)

10.2.39 Setting ............................................................................................................................. 1237


10.2.40 Signal (Data ID) ............................................................................................................. 1243
Trip circuit supervision task..................................................................................................... 1249
10.3.1 Detecting erroneous operation .......................................................................................... 1250
10.3.2 Trip circuit error (TC error)............................................................................................... 1253
10.3.3 Setting ................................................................................................................................. 1254
10.3.4 Signal (Data ID) ................................................................................................................. 1255
Supervision task of interruption capability on CB ................................................................. 1257
10.4.1 Operation of sigma Iy ........................................................................................................ 1258
10.4.2 Sigma Iy error (CHK_SGMIY error) ................................................................................ 1259
10.4.3 Setting ................................................................................................................................. 1260
10.4.4 Signal (Data ID) ................................................................................................................. 1261
Supervision tasks for device dependent features.................................................................... 1262
10.5.1 Error detection of differential current in DIF (Id)........................................................... 1263
10.5.2 Current transformer failure detected with DIF (DIF-CT) .............................................. 1264
10.5.3 Synchronizing and sampling error (Com sync fail) ......................................................... 1265
10.5.4 Communication failure (Com fail) .................................................................................... 1266
10.5.5 Error signal level for sending (TX level) .......................................................................... 1267
10.5.6 Error signal level for receiving (RX level) ........................................................................ 1268
10.5.7 Propagation delay error (Com Td) .................................................................................... 1269
10.5.8 Error terminal configuration (Term ID) ........................................................................... 1270
10.5.9 Monitoring ready state at the remote (Term rdy)............................................................ 1271
10.5.10 Transmission error (Com fail-R).................................................................................... 1272
10.5.11 Master-slave monitoring (MSCHK) .............................................................................. 1273
10.5.12 Supervision of Relay ID (RYID) .................................................................................... 1274
10.5.13 Setting ............................................................................................................................. 1275
10.5.14 Signal (Data ID) ............................................................................................................. 1278
11 Communication protocol ............................................................................................................... 1281
Interface setting and protocol selection ................................................................................... 1282
LAN operation ........................................................................................................................... 1283
11.2.1 LAN address (IP address).................................................................................................. 1283
11.2.2 Redundant LAN (Hot-standby) ......................................................................................... 1284
11.2.3 Redundant LAN (PRP/HSR operation) ............................................................................ 1291
11.2.4 Redundant LAN (RSTP operation) ................................................................................... 1295
11.2.5 Settings ............................................................................................................................... 1297
11.2.6 Signals (DataID) ................................................................................................................ 1299
IEC 61850 communication........................................................................................................ 1301
11.3.1 About protocol .................................................................................................................... 1303
11.3.2 Communication service ..................................................................................................... 1306

xxi
6F2S1914 (0.37)

11.3.3 How to manage engineering work .................................................................................... 1309


11.3.4 Settings for 61850 communications .................................................................................. 1328
11.3.5 Selection of IEC61850 protocol among IED embedded protocols ................................... 1330
11.3.6 How to supervise in 61850 communications .................................................................... 1330
11.3.7 Quality signal in 61850 communication ........................................................................... 1331
11.3.8 Goose monitoring status in 61850 communication.......................................................... 1332
11.3.9 Feature of IEC61850 Edition1 option............................................................................... 1333
11.3.10 Setting ............................................................................................................................. 1334
11.3.11 Signal (Data ID) ............................................................................................................. 1335
IEC 60870-5-103 communication ............................................................................................. 1351
11.4.1 Overview ............................................................................................................................. 1352
11.4.2 Requirements in the Master station................................................................................. 1354
11.4.3 Interoperability .................................................................................................................. 1355
11.4.4 Communication interface in the IEC 60870-5-103 standard .......................................... 1356
11.4.5 Editing data of the configuration ...................................................................................... 1357
11.4.6 Protocol selection................................................................................................................ 1375
11.4.7 Tips for settings.................................................................................................................. 1376
11.4.8 Setting ................................................................................................................................. 1377
11.4.9 Signal (Data ID) ................................................................................................................. 1378
USB communication.................................................................................................................. 1379
RS485 communication .............................................................................................................. 1380
12 User interface ................................................................................................................................ 1381
Outline ....................................................................................................................................... 1382
HMI operation ........................................................................................................................... 1385
Record sub-menu ....................................................................................................................... 1388
Monitoring sub-menu ................................................................................................................ 1393
Setting sub-menu ...................................................................................................................... 1401
I/O setting sub-menu................................................................................................................. 1414
Time sub-menu .......................................................................................................................... 1422
Test sub-menu............................................................................................................................ 1428
Information sub-menu .............................................................................................................. 1434
Security setting sub-menu .................................................................................................... 1435
Control sub-menu .................................................................................................................. 1437
13 Installation and replacement ....................................................................................................... 1439
Caution for storage .................................................................................................................... 1440
Handling precautions ................................................................................................................ 1440
Unpack and inspection of hardware and software ................................................................. 1441
Changing rated current ............................................................................................................ 1446
PWS alarm threshold setting ................................................................................................... 1451

xxii
6F2S1914 (0.37)

Removing and installation of an inside module ...................................................................... 1452


Rack mounting........................................................................................................................... 1462
Wiring work ............................................................................................................................... 1467
14 Commissioning and maintenance ................................................................................................ 1472
Scope of required test ................................................................................................................ 1473
Cautions ..................................................................................................................................... 1474
Preparations .............................................................................................................................. 1474
Test operations........................................................................................................................... 1476
14.4.1 Test for communication ..................................................................................................... 1476
14.4.2 Test for relay application ................................................................................................... 1477
14.4.3 Test for control application ................................................................................................ 1479
14.4.4 Test for BI and BO circuits ................................................................................................ 1479
14.4.5 Test for mode change (MDCTRL)...................................................................................... 1479
14.4.6 Signal monitor .................................................................................................................... 1479
14.4.7 LED light test ..................................................................................................................... 1479
Setting ........................................................................................................................................ 1480
Signal ......................................................................................................................................... 1481
Appendix 1 Signal list for common function ....................................................................................... 1482
Appendix 2 Case outline ........................................................................................................................ 1489
Appendix 3 Typical external connection ............................................................................................... 1496
Appendix 4 IEC61850 MICS, PICS, PIXIT, and TICS ........................................................................ 1501
Appendix 5 IEC60870-5-103 interoperability ...................................................................................... 1567
Appendix 6 Ordering.............................................................................................................................. 1581
Appendix 7 Technical data .................................................................................................................... 1600
Appendix 8 Manufacture setting .......................................................................................................... 1623
Appendix 9 Matrix between VCT terminals and relay applications .................................................. 1628
Appendix 10 CT requirement .............................................................................................................. 1633
Appendix 11 Rack mounting................................................................................................................ 1643
Appendix 12 Notes for the dielectric voltage test .............................................................................. 1648
Appendix 13 Engineering exercise ...................................................................................................... 1650

xxiii
6F2S1914 (0.37)

1 Introduction
Contents Page Page
Abbreviation 18 Control –
Autoreclose (ARC) 11 -Counter function (GCNT) 12
Backup protections – Function identifies and signals (FB) 19
-Distance protection (ZS/ZG) 6 Hardware overview 13
-Pilot schemes (DISCAR, DEFCAR) 10 Main protections –
-Over current protection (OC) 11 -Current differential protection (DIF) 6
-Earth fault protection (EF) 11 Monitoring and metering functions 12
-Switch on to fault relay (SOTF) 11 Symbols used in logical diagrams 14
-VT failure relay (VTF) 11 Trip circuit (TRC) 10
-CT failure relay (CTF) 11
-Fault locator (FL) 11
-Voltage check relay (VCHK) 11

GRL200 (Soft 033 & 037)


- 1 -
6F2S1914 (0.37)

GRL200 line differential protection has been designed to provide phase-segregated current
differential protection with digital telecommunications, together with control applications. The
GRL200—intelligent electronic device (IED)—provides the user with the flexibility to meet
their application and engineering requirements in addition to offering excellent performance,
the high quality and reliability.

Protection functions
The IED has a number of protection functions and these functions are being optimized for
transmission or distribution systems. The followings functions incorporated and programmed
with the user’s settings using the menus on the IED or in the engineering tools can operate
well with mutual linkage between protection functions.

1.1.1 Purposes of the protection


In order to secure the stability in the power system, the protection function provides three
significant fundamentals for the protection in response to various faults:
(1) Prevention of power supply interruption is to clear the faults and recover the faulted power
transmission as soon as possible.
(2) Prevention of damage to equipment is serviced not to damage the primary device even if
faults occur successively. For example, destruction of insulators, rupture of lines, burning of
transformers, and others may result in severe damages in devices in the power system. The
protection function can serve the device not be vulnerable severely for such damages.
(3) Prevention of system instability is to clear faults in the power system speedy by the
operation in the protection functions. Otherwise, a generator will be in out-of-step if a fault
does not clear speedy.

1.1.2 Requirements in the protection functions


Several essences shall be considered for the operation within the relays:
(i) Selectivity
If any fault occurs in the power system, it shall be cleared. At the same time, we should
consider that the unfaulted segments of the power system must be isolated from the faulted
segment in which the fault may clear. Figure 1.1-1 illustrates the protection areas constructed
with two different protection schemes; the two schemes are overlapped so that the entire areas
are protected.

Figure 1.1-2 illustrates the locations of a circuit breaker (CB) and a current transformer
(CT) connected with the relays. In Figure 1.1-2(a), for example, two CTs locates on the both
sides of the CB(N): a CT is connected with the relay Ry(S) seeing into the line and another CT is
connected with the relay Ry(X) seeing to the busbar; the zones protected by the two relays are
overlapped.

GRL200 (Soft 033 & 037)


- 2 -
6F2S1914 (0.37)

Figure 1.1-2(b) exemplifies that both the forward line and the busbar are protected using
a CT. Once a fault occurs between the CT and the CB(N), the relay Ry(S) for the forward line can
operate, but the relay Ry(X) for the busbar may fail to operate to clear the fault. That is, we
should keep in mind that a blind spot never exits in the power system for designing the
protection.
Busbar G Busbar H

M N K L Line

Ry(V) Ry(U) Ry(S) Ry(X) Ry(T) Ry(O) Ry(P) Ry(Q)

: Current transformer (which is connected with a relay)

M : Circuit Breaker (which is located at M)

Ry(V) : Protection relay (which is located at V)

: Protection area by line protection scheme

: Protection area by busbar protection scheme

Figure 1.1-1 Two protection schemes for line and busbar

Busbar G Busbar G

N Line N Line

Ry(S) Ry(X) Ry(S) Ry(X)

(a)Line and Busbar protected relays with two CTs isolated (b)Line and Busbar protected relays with a CT

Figure 1.1-2 Protection schemes and the location of the CB

(ii) Speediness
As mentioned earlier, shortening the fault duration is realized by the speedy operation of the
relay; it is achieved by the high speed signal processing module. However, we have to note that
the operating time of the CB is slower comparted with the one of the processing module.
Additionally, the propagation delay of the communion should also be considered when the
carrier command protection function is considered for the protection.

GRL200 (Soft 033 & 037)


- 3 -
6F2S1914 (0.37)

(iii) Reliability
The relay is in a quiescent state normally, but the relay shall respond to a fault instantly once
it occurs on the power system. Hence, the operation availability shall be checked whenever the
line is energized in unfaulted state. Additionally, to improve the operation reliability, the
protection scheme is checked externally by fail-safe function (FS). That is, the relay operations
are checked not to issue a trip command mistakenly by the FS relay; consequently, erroneous
tripping can be prevented dramatically if the prime (main) relay operates mistakenly. The
check results of the FS relay are combined together with the operation results of the prime
relay at the last stage (i.e., AND logics runs on the trip circuit).

1.1.3 Behavior of backup protections


Faults shall be securely cleared and clearing the faults shall be made as soon as possible, or
the power system may result in the outage. As to protect the power system, as a rule, a main
(primary) relay operates along with a number of backup relays. A protection function
represents the main (primary) relay, whereas the other protection functions operate as the
backup relays. Accordingly, faults could be clear if the main (primary) relay were in the failure
to operate.

(i) Protection for the line


The element† in the current differential protection function (DIF) is designed to operate for
the main relay. However, we shall note that the main protection cannot operate perfectly at
any time. For example, the DIF protection function cannot operate correctly once the
telecommunication incident or others occur. Thus, we shall design that clearing the faults could
be performed by the operation in backup relays in any case. Note that we should figure the
capability for clearing the faults being dependent on the system integrity. The conventional
relays (such as distance relay and others) are serviced as the backup protections, which we
discuss successively.

GRL200 (Soft 033 & 037)


- 4 -
6F2S1914 (0.37)

Busbar R Busbar G Busbar H


Zone2(N)
Zone1(N)
DIF (N)
N O M K Line

Trip command

Tele communication

Relay(N)
Relay(O) Relay(M) Relay(K)
Main (primary) TRC
Relay(
DIF(N)
DIF(O)
Backup (local) Delay timer Zone1 in
Zone1 in ZS(N) t 0 Zone1 in ZS(O)
≥ OC(M)
t 0 OC(O)
OC(N) & EF(M)
EF(O)
t 0 Zone2 in
EF(N)
Zone2 in ZS(O)
Backup (remote) Fail safe (
Fail safe (FS) (O)
Zone2 in ZS(N) t 0
Extra F

Fail safe (FS) relay(N)

t 0

Extra FS relay

Figure 1.1-3 Protection zones provided by the main relay and backup relays
†Note:When the carrier command protection function (DISCAR or DEFCAR) is
available, the function can also service as a local backup protection. We shall also
note that the function cannot operate in the device failure in the
telecommunication.

(ii) Coordination between the main and the backup protections


The operation of the backup protection is realized by retarding the operation of the backup
protection rather than the main protection; retarding is made with setting the delay timer of
the backup protection. We shall note that the setting value for the delay timer should be chosen
so that the coordination between the main protection and the backup protection is realized.
The degree for retarding the backup protection is determined by the consideration of operating
and reset time margins:
• Operating time of the main protection
• Reset time of backup protections
• Operating time of the circuit breaker

(iii) Types of the backup protections


The backup protections are grouped into two: 1.backup protections serviced from the remote
end far from the location of the main protection and 2.backup protections serviced locally as
same as the main protection.

GRL200 (Soft 033 & 037)


- 5 -
6F2S1914 (0.37)

Remote backup protection (Retarded backup protection)


Due to practical problems such as the incidents of power supply and others, there is possibility
to fail to operate the main protection. Therefore, providing a backup protection from the remote
end is essential so that the main protection is backed up remotely. For the ZS/ZG protection,
the zone2 and zone3 for the relaying elements can be serviced as the remote backup protections.

Local backup protection (High-speed backup protection):


If the circuit breaker has failed to trip by the commands of the main protection, the CB could
be tripped by the commands of the backup protections located beside the main protection. For
the DIF function, the zone1 element of the ZS/ZG function and others are serviced as the local
backup protection.

1.1.4 Concepts of current differential protection (DIF) function


Current differential protection compares the currents flowing into and out of the protected line.
The difference of the currents, that is, the differential current, is almost zero when a fault is
external or there is no fault, and is equal to the fault current when the fault is internal. The
differential protection operates when the difference of the currents exceeds a set value.
The DIF function in the GR200 series relay located at the ends of the line can examines the
entering and outgoing currents in every 7.5 electrical degrees; they are transmitted to the other
terminals in every four samples using the telecommunication. As the DIF function can obtain
the current data at all remote-ends using the telecommunication, the DIF function at any
locations can perform as the master.

As synchronized sampling can be performed at all terminals, the current data are the
instantaneous values, which are sampled simultaneously at each terminal. Therefore, by using
the identical sampling address, the value of the differential currents can be obtained
straightforward by summing current data at the local and the remote. Thus, compensation of
transmission delay time is not required in the DIF function.

The GR200 series relay takes respective three-phase currents and a residual current in
so that performing segregated-phase and zero-phase current differential protection are
achieved.

1.1.5 Concepts of distance protection (ZS/ZG) function


In the distance protection function, the line protection is grouped into six zones; the zones are
protected with six measuring elements: zone1(Z1), zone1X(Z1X), zone2(Z2), zone3(Z3),
zone4(Z4) and zone5(Z5). Figure 1.1-4 illustrates the six elements in the Mho characteristic.

GRL200 (Soft 033 & 037)


- 6 -
6F2S1914 (0.37)

Z1S–Z5S in Mho characteristic with blinders


X

Z4S-Mho.Reach
Z3S

Z2S

Z1XS
Z5S-R.Reach

Z4S-R.Reach

Z1S

R Z5S-R.Angle

Z5S
Z5S-Mho.Angle

Z4S Z4S-R.Angle

Figure 1.1-4 Six zones in Mho characteristic

(i) The reach of the zone1 element


The user shall notice that the reach of the zone1 element is usually set to approximately 80 to
90% of the length of the line (the reach of the zone1 should not include the busbar at the remote
end. That is, the zone1 element shall not operate for a fault occurring beyond the remote
busbar). Accordingly, if a fault occurs out of the zone1 and lies behind the remote busbar, the
zone2 element starts to operate to clear the fault, but its operation will be retarded by the
comparison of the operation of the zone1 element†.

†Note:Operation of the carrier command protection function (DISCAR or DEFCAR) is


practical when the user wishes to clear instantly the fault that occurs in that area.

(ii) Measuring error and its influence


In the case of a fault with resistance, the reactance component seen by the relay at the terminal
sending power is smaller than the actual value and it tends to overreach. On the contrary, the
reactance component seen by the relay at the terminal receiving power is greater than the
actual value and it tends to underreach. The line impedance has different values in different
phases. When its average value is used for the relay setting, underreaching will occur in a
phase with greater impedance than the average value. In the case of fault resistance, its
impedance is greater for earth faults where the fault is grounded via a steel tower or tree
rather than a phase fault consisting of arc resistance only. Therefore, measuring errors about
the earth fault relay are generally greater than the errors about the phase fault relay. The

GRL200 (Soft 033 & 037)


- 7 -
6F2S1914 (0.37)

fault arc is considered to be almost equivalent to pure resistance. But if the phase of a current
that flows into a fault point from the remote end is different from the phase of the local current,
the voltage at the fault will have a phase angle difference with respect to the local current,
producing a measuring error in the distance relay with the principle of measuring the
reactance component. The existence of a zero-sequence current on the protected line and
adjacent line can also cause errors in the earth fault relay. The zero-sequence current normally
acts in the direction of relay underreaching due to the effect of the induced voltage. The
compensation method will be described in detail in the next section. The earth fault relay
contains more errors than the phase fault relays even with these compensation methods.
Therefore, the earth fault relays are usually set with a greater margin than the phase fault
relays.

Regarding measuring errors in the relay, it is also necessary to consider hardware errors
in the relay itself, errors introduced by coupling capacitor voltage transformers (CCVT), and
transient overreach errors caused by the DC component of the fault current. For the GR200
series relays, the errors are defined to be less than 5%.

(iii) Detection of power swing and out-of-step


Power swings occur when the output voltages of generators at different points in the power
system slip relative to each other, which result in system instabilities that may be caused by
sudden changes in load magnitude or direction, or by power system faults and their subsequent
clearance. During the course of such a power swing, the impedance seen by a distance relay
may move (relatively slowly) from the load area into the operating characteristic of the distance
protection. In fact, this phenomenon appears to the distance protection measuring elements
like a three phase fault condition and may result in tripping if no countermeasure is applied.
Most power swings are transient conditions from which the power system can recover after a
short interval, and distance protection tripping is therefore highly undesirable in such cases.
GR200 series relay provides the block function for power swing (PSB) so that preventing
unwanted tripping is possible during the power swing. Figure 1.1-5 illustrates the typical
impedance locus as seen by the distance relay during the transient power swing.

GRL200 (Soft 033 & 037)


- 8 -
6F2S1914 (0.37)

X Distance protection
characteristic
(Mho)

Impedance locus during


transient power swing

R
Load Area

Figure 1.1-5 Impedance locus during transient power swing

A special case of the power swing condition occurs when the power system disturbance is
so severe that generators lose synchronism with each other and are said to be out-of-step.
During an out-of-step condition the phase angle between generators continues to increase and
pass through 180°, at which point a distance relay measures an impedance equal to that for a
three phase fault at the center of the power system. The impedance locus typically describes
an arc passing through the electrical center, as shown in Figure 1.1-6.
X
Distance protection
characteristic
(Mho)

Impedance locus during


out-of-step condition

R
Load Area

Figure 1.1-6 Impedance locus during out-of-step condition

In the case of a full out-of-step condition (as opposed to a transient power swing), it is
desirable to separate the system in the vicinity of the center of the out-of-step condition. GR200
series can provide an out-of-step detection element (OST) which can provide tripping in these
circumstances.

Although the power swing and out-of-step conditions are very closely related (in fact one
is simply the most severe form of the other), completely different actions are required from the
protection relay. The PSB function must ensure stability of the distance protection during

GRL200 (Soft 033 & 037)


- 9 -
6F2S1914 (0.37)

transient power system conditions, while the OST element initiates system separation by
tripping in the event that a severe power swing results in potentially irrecoverable loss of
stability in the power system. The PSB and OST elements are therefore completely separate
functions within the relay, with different characteristics, separate scheme logic and different
settings.

1.1.6 Concepts of carrier command protection (DISCAR/DEFCAR) function


(i) DISCAR Command protection by the distance (ZS/ZG) protection
If information picked up in the distance protection (ZS/ZG) function located at the ends of the
protected line are exchanged mutually by means of the telecommunication, it is possible to
determine accurately whether a fault occurs within the protecting zone or not. Consequently,
at each ends, the trip command can be issued faster. The GR200 series can provide the
following carrier command schemes using the elements of the ZS/ZG function.
• Permissive underreach protection (PUP)
• Permissive overreach protection (POP)
• Unblocking overreach protection (UOP)
• Blocking overreach protection (BOP)

(ii) DEFCAR command protection by the earth fault (EF) protection


Like in the DISCAR function, the DEFCAR function is designed to operate using the
directional characteristic of the earth fault protection (EF) function. The DEFCAR function
can provide the following carrier command schemes:
• Permissive overreach protection (POP)
• Unblocking overreach protection (UOP)
• Blocking overreach protection (BOP)

(iii) Operation with autoreclosing (ARC)


The user should notice that the operation in respective command protections initiate the
operation of the autoreclose (ARC) for the circuit breaker very fast.

1.1.7 Tripping CB by the protection functions


After issuing the trip commands by the protection functions, the trip commands are grouped
within the trip circuit (TRC) function; then, the TRC function drives the binary output circuits
within the relay for transferring the trip commands to the CB. The TRC function can operate
for tripping single-pole or multi-poles. Before the protection functions is reset, the auxiliary
contacts of the CB must be derived to open; this is because, the protection function cannot
interrupt straightforward the current flowing on the tripping coil circuit of the CB.

GRL200 (Soft 033 & 037)


- 10 -
6F2S1914 (0.37)

1.1.8 Autoreclosing CB (ARC) after the operation of the protection functions


Most faults that occur on high voltage or extra-high voltage overhead lines are transient faults
caused by lightning. Once a transient fault occurs, the circuit breaker (CB) is tripped to clear
the fault; reclosing the CB is performed after the confirmation of the de-ionized gases in the
CB. The time between clearing the fault and reclosing the CB should be made as short as
possible to keep the power system stable. Given the de-ionization generated by the fault arc,
we should take enough time for the de-ionization, which commences once the CBs at all
terminals are tripped. However, we can take the time in minimum if all CBs at the terminals
are tripped at the same time.

1.1.9 Conventional applications


[OC] Directional/non-directional phase over current protection
The OC function provides some relay elements. The OC function includes inverse time and
definite time characteristics.

[EF] Directional/Non-directional phase earth fault protection


The EF function provides some relay elements. The choice of characteristic is selectable
between inverse time, and definite time.

[SOTF-OC] Switch on to fault protection


In order to quickly remove a fault which may occur when a faulted line or bus-bar is energized,
the SOTF protection will be operational for a certain period after the circuit breaker closes.

[FS] Fail-safe protection


The IED is provided with Fail-safe elements which function as a check relay and enhance
security against a fault a power system with week infeed, or prevent a false tripping due to a
signal failure in the protection system.

[VTF] VT failure detection function


When a fault occurs in the secondary circuit of a voltage transformer (VT), voltage dependent
measuring elements may operate incorrectly. Thereby when the VTF function detects a failure
in the VT, the VTF function blocks the voltage dependent relay.

[CTF] CT failure detection function


When a fault occurs in the secondary circuit of a current transformer (CT), current dependent
measuring elements may operate incorrectly. Thereby when the CTF function detects a failure
in the CT, the CTF function blocks the current dependent relay.

[FL-AZ] Fault locator with communication


When a fault is detected, such function, which communicates with a far end IED, determines
fault location with data in the IEDs between. Were to the IED to fail to communicate with the
far end IED, another fault locator function, which is cited below, would be used as a substitute
for this function.

GRL200 (Soft 033 & 037)


- 11 -
6F2S1914 (0.37)

[VCHK] Voltage check for auto-re-close function


This function is used in corporation with the function of auto-re-close (ARC). The VCHK checks
voltage and frequency differences between a Bus-bar and Lines, and permits the ARC the
operation.

Control
The control functions are provided for circuit breakers and isolators, other switchgear and
transformers. The user can operate the functions using the human machine interface; the
functions are able to operate together with such as automatic sequence control, interlocking
safeguard function and manual overridden function.

[GCNT] General pulse counter function


This function can observe a signal, for example the output of a PLC function and counts the
number of pulses for the signal. The total number of pulses counted is recorded.

[MDCTRL] Mode control function


This function enables an interface for test function block (TSET-FB). With this interface, a
mode change command is made within the IED for the TEST-FB.

[LRST] LED reset function


The LRST function can turn off a LED when the LED is lit by tripping.

Monitoring and metering functions


Using the HMI, the monitoring and metering functions can display status, settings, data and
others. The user can also see information using “GR-series Toshiba IED Engineering and
Monitoring Software (GR-TIEMS)” both at local and remote end.

Monitoring function:
This function supervises status of protection functions, and displays power system quantities.
It also shows failure information in the CT and VT.

Fault record function:


Such function records the state of a fault when the trip command is issued. It also memorizes
the fault data. The user can see, with the IED screen, these data with additional information:
date & time, fault phase, tripping phase, tripping mode, fault location, operating mode and
power system quantities.

Event record function:


The function provides recording feature that memorizes any event occurred in the IED.

GRL200 (Soft 033 & 037)


- 12 -
6F2S1914 (0.37)

Disturbance record function:


Disturbance record is triggered by fault detection. The user can see the waveform recorded by
this function using GR-TIEMS.

Hardware overview
The IED has human machine interface (HMI), which is made of LCD screen, indication lights,
operation and function keys, monitoring jacks, and a USB connector. Voltage, current input
terminals, and binary input and output circuits are provided on the rear..

HMI features:
- Menu-driven human interfaces for settings or viewing of stored data.
- A standard LCD or a large LCD (MIMIC) screen, LEDs, function keys and operation keys

Communication features:
- USB for GR-TIEMS
- RS485 for Substation control and Automation System (SAS) with IEC60870-5-103 protocol
- Fiber Optic (FO, option) for SAS with IEC60870-5-103 protocol
- 100BASE-TX, or -FX for SAS with IEC61850 protocol

Module circuits and others:


- Binary input circuits and binary output circuits with configurable features
- AC inputs
- Programmable logic for I/O configuration, alarms, indications, recording and others
- Automatic supervision

GRL200 (Soft 033 & 037)


- 13 -
6F2S1914 (0.37)

Symbols used in logical diagrams


Symbols used in the scheme logic and their meanings are as follows:

(i) Relay element, signal-monitoring point, PLC connection point, and


Mapping point
1. Marked with : Relay elements

2. Marked with : Signal-monitoring point designated by Element ID number

Note that the symbol can be connected with what follows:


A binary output (BO) circuit
A LED circuit
Like in the BO and LED circuits, it can also be connected or mapped to what follows:
A PLC connection point
The IEC 61850 logical node (LN) to send a signal for the SAS

An alternative point (discussed in Chapter PLC function) is provided in place of the


signal-monitoring point for starting the user-programmed logic.

3. Marked with : PLC connection points designated by Element ID and its name

Element ID (or Signal No.) Signal name corresponding to Element or Signal No.(Data ID)

Note that the symbol can be used for the reception point coming from the output of PLC
logics.

4. Marked with : Mapping points designated by Signal No. (Data ID) and its name

Signal number (Data ID) Signal name corresponding to Signal No. (Data ID)

1Note that the symbol can be used as a signal reception-point coming from the SAS. The
reception point is mapped to the LN of the IEC61850.

GRL200 (Soft 033 & 037)


- 14 -
6F2S1914 (0.37)

(ii) Timer symbol


 Delay timer
Delayed pick-up timer
t 0 Fixed timer (XXX: Set time)

XXX
t 0
Variable timer (XXX ─ YYY: Setting range)

XXX ─ YYY
Delayed drop-off timer
0 t Fixed timer (XXX: Set time)

XXX
0 t
Variable timer (XXX ─ YYY: Setting range)

XXX ─YYY

 One-shot timer

A Output A

XXX - YYY Output


XXX - YYY: Setting range

GRL200 (Soft 033 & 037)


- 15 -
6F2S1914 (0.37)

(iii) Logic symbol


 AND gate

A B Output
A
1 1 1
& Output
B 1 0 0
0 1 0
0 0 0
 OR gate

A B Output
A
1 1 1
≥1 Output
B 1 0 1
0 1 1
0 0 0
 XOR gate

A B Output
A
1 1 0
=1 Output
B 1 0 1
0 1 1
0 0 0

 Signal inversion

A Output
0 1
A 1 Output
1 0

GRL200 (Soft 033 & 037)


- 16 -
6F2S1914 (0.37)

(iv) Flip-flop symbol


A B Output

A S 0 0 No change
Output 1 0 1
B R 0 1 0
1 1 0

(v) Scheme switch


A Switch Output
1 On 1
A Output
On 1 Off 0

Switch Output
+ Output
On On 1
Off 0

GRL200 (Soft 033 & 037)


- 17 -
6F2S1914 (0.37)

Abbreviation
Abbreviation Description
ADC Analog to digital converter

BCU Bay Control Unit

BCPU Bay Control and Protection Unit

BI Binary Input module or circuit

BO Binary Output module or circuit

BIO Binary Input and Output module or circuit

CB Circuit Breaker

CPU Signal processing and communication module

CT Current Transformer

DS Disconnecting Switch

EF Earth Fault

ES Earthing Switch

EWS Engineering Workstation in the substation

GPS Global Positioning System

GR-TIEMS GR-series Toshiba IED Engineering and Monitoring Software

GUI Graphical User Interface

HMI Human Machine Interface

IED Intelligent Electronic Device

IDMT Inverse Definite Minimum Time

LCD Liquid Crystal Display for IED screen (standard LCD screen)

LCP Local Panel for Controlling

LED Light Emitting Diode

MIMIC Touchscreen operation configured by user’s program to operate control application

NA Not Applicable

NGR Neutral Grounding Resistance

N/C Normally Closed

N/O Normally Open

OWS Operator Workstation in the substation

PC Personal Computer for maintenance

PCB Printed circuit board

PLC Programmable Logic Controller

RCC Remote Control Centre

SAS Substation Automation System

SC Station Computer

SCMS Substation Control and Monitoring System

TCP/IP Transmission Control Protocol/ Internet Protocol

GRL200 (Soft 033 & 037)


- 18 -
6F2S1914 (0.37)

Abbreviation Description
UTC Coordinated Universal Time

SyncSrc Synchronization Source

VT Voltage Transformer

VCT Transformer module including VTs and CTs

43 Selector device or selector switch

Function Block (FB), Function ID, Signal number (Data ID)


Function Block (FB) is the software module and GR-series IED implements FBs for protections,
controls and communications. The function ID is unique ID described by six digits in
hexadecimal; each function ID represents each FB. Signal number (or Data ID) is the logical
address of the input and output data of the FB. The signal number (Data ID) consists of a
function ID and an element ID. The function ID is common within the FB; accordingly the
element ID will be shown to make description simple. The element ID is 10 hexadecimal and
it has the element ID name for easy to read. Figure 1.7-1 exemplifies the symbols, the function
ID, and the element ID. The table below shows the structure of the signal.

Function ID Element ID Note

Format (Hex) FFFFFF XXXXXXXXXX Content


Signal example 123456 80000xxxx0 XX relay in phase-A is operated.
Element ID

FB (Function ID=123456)
80000xxxx0 8000xxxxx
A & ≥1 XX1_OPT
81000xxxx1
XX1 B &
82000xxxx2
C
&
Element ID Signal name
&
8000011xxxx0 XX_BLOCK 1

3. PLC connection point† 1. Relay element 2. Signal monitoring point


Figure 1.7-1 Example of symbols and others
†Note that a PLC connection point can be shown with the function ID (12345) plus
element ID (8000011xxxx0) expressed in 16 delights in hexadecimal, in some
scheme logics. The ‘PLC connection point’ could be found to search the letter ‘E’ of
element ID (i.e., ‘8000011Exxx0’).

GRL200 (Soft 033 & 037)


- 19 -
6F2S1914 (0.37)

2 Relay application
Contents Pages Pages
Autoreclosing – Earth fault protection (EF) 238
-Reclosing CB (ARC) 416 Fail safe schemes –
-Blocking reclose in CBF 290 -using Common relay (FS) 355
-Blocking reclose in ZS, ZG 120 ---with Overcurrent element 356
-Blocking reclose in DIFL 27 ---with Phase current change detector 356
-Blocking reclose in DIFGL 40 ---with Earth fault current element 356
-Blocking reclose in OC 227 ---with Multi-level OC elements 357
-Blocking reclose in EF 247 ---with UV element in single phase 358
-Blocking reclose in OCN 265 ---with UV element in phases 358
Broken conductor protection (BCD) 280 ---with UV change element 358
Breaker failure protection (CBF) 286 -in Distance relay (ZS/ZG) 119
Cold load protection (CLP) 543 Fault locator (FL-A and FL-Z) 374
Communication – Frequency protection (FRQ/DFRQ) 336
-Common control (COMM_APPL) 505 Inrush current detection(ICD) 352
-DIF control (DIF_COMM) 490 Overcurrent protection (OC) 215
CT failure detection scheme – Overcurrent protection in negative (OCN) 256
-CT failure detection (CTF) 369 Overvoltage protection (OV) 296
-CT circuit-failure detection in DIFL 30 Overvoltage protection in phases (OVS) 304
-CT circuit-failure detection in DIFGL 42 Overvoltage protection in ground (OVG) 311
Current diffential protection – Out of step with voltage (OSTV) 346
-Outline for segregated-phase (DIFL) 22 Pilot (carrier) scheme –
-Outline for earth fault (DIFGL) 38 -POP with directional earth (DEFCAR) 201
-Check relays characteristics in DIFL 28 -POP with distance relay (DISCAR) 184
-Check relay characteristic in DIFGL 41 -UOP with directional earth (DEFCAR) 204
-Charge-current compensation in DIFL 31 -UOP with distance relay (DISCAR) 187
-Charge-current compensation in DIFGL 42 -BOP with directional earth (DEFCAR) 204
-CT saturation countermeasure in DIFL 46 -BOP with distance relay (DISCAR) 189
-Differential current monitor in DIFL 32 -PUP with distance relay (DISCAR) 183
-Through-fault-current in DIFL 56 -Direct transfer trip (DTT) 177
-Fault on double circuit-lines in DIFL 69 -DISCAR relay characteristics 121
-Fault on Three-terminals line in DIFL 70 -Remote DIF trip (RDIF) 70
Common function – Stub scheme –
-Common relays (PROT_COMMON) 531 -Stub protection with OC (STUB-OC) 83
-Detection of current change 537 -Stub protection in DIFL 65
Distance protection (ZS/ZG) – Switch on to fault scheme –
-Pinciple and equations 88 -SOTF with OC (SOTF-OC) 211
-Z1 element control 120 -SOTF with Distance relay 126
-Z1,Z1X,Z2 to Z5 element characteristics. 100 Thermal overload function (THM) 274
-Load enchroachment block relay (LEB) 118 Trip command (TRC) 401
-Power swing block relay (PSB) 114 Under-voltage function (UV) 319
-Blocking phase-ground elements 126 Under-voltage function for phases(UVS) 327
-Enhancing faulted phases detection 126 Voltage check for ARC(VCHK) 471
VT failure detection (VTF) 363

GRL200 (Soft 033 & 037)


- 20 -
6F2S1914 (0.37)

Current differential protection for the line


Current differential protection function (DIF) at local-terminal and remote-terminal can
operate by comparing the currents flow in and out in the line. The value of the current-
difference is close to zero when a fault does not occur (i.e., No fault). The DIF function consists
of a current segregated current differential protection (DIFL) and a zero-sequence current
differential protection (DIFG); they can detect phase-to-phase fault, phase-to-ground fault, and
a phase-to-ground fault. The DIFL and DIFGL functions can operate for on the three-terminal
line; remote differential trip (RDIF) function can substitute the operation of the DIFL and
DIFGL functions when an error occurs on the communication channel.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the ‘G&T position’ referring to the comparison
table below. For more information, see Appendix: Ordering.
Table 2.1-1 Comparative table in respective ordering numbers
Ordering No. at ‘G&T’
Section feature Relay function/ features
33 37
2.2.1 Current differential ✓ ✓
2.2.2 Check relay OC (OCs) ✓ ✓
2.2.2 Check relay UV (UVs) ✓ ✓
2.2.2 DIFL CT failure detection using Id (DIFL-CTF) ✓ ✓
2.2.3 CT circuit failure detection (DIFL-CTF) ✓ ✓
2.2.4 Charging current compensation (DIFL-Ic) ✓ ✓
2.2.5 Id current monitoring (DIFL-IdSV) ✓ ✓
2.3.1 Zero sequence current differential ✓ ✓
2.3.2 Check relay EF (EFD) ✓ ✓
DIFGL
2.3.3 CT circuit failure detection (DIFGL-CTF) ✓ ✓
2.3.4 Charging current compensation (DIFGL-Ic) ✓ ✓
2.4 CTsat CT saturation countermeasure ✓ ✓
2.5 CT matching CT ratio/rating and fault currents ✓ ✓
2.6 Usage in 1.5CB TFC and Stub features ✓ ✓
2.7 RDIF Remote differential trip ✓ ✓
2.8 Misc. Blind zone protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 21 -
6F2S1914 (0.37)

Segregated-phase current differential protection function (DIFL)


The principle of current differential protection (DIFL) function is to compare the currents
flowing into and out of the transmission line; the differential current is obtained by the
comparison between two currents in the DIFL function. In the DIFL function the value of the
differential current is almost zero when a fault occurs out of the protection zone (i.e., external
fault). Conversely the value of the differential current is nearly equal to the fault current when
the fault occurs in the protection zone (i.e., internal fault) The DIFL function can issue a trip
signal when the value of differential current is beyond to the DIFL settings.

The DIFL function can calculate the differential current when current data of two-
terminal line are obtained. That is, the relays at local-terminal and remote-terminal should be
connected by the communication. If a failure occurs on the communication, the DIFL function
may be affected by the error data due to the failure. Therefore, five check relays are provided
and are used to prevent the spurious operation in the DIFL function.

When a failure occurs on the CT circuit, the DIFL function cannot operate correctly.
Therefore, CT circuit failure-detection function is available in the DIFL function. Monitoring
function for differential current (DIFL-IDSV) is also provided so that the spuriousness of the
differential current can be detected during the CT circuit failure

Countermeasure features for through-fault-current and stub area are also available in
the DIFL function. These features are useful for the protection of the close-up external fault
and the stub-area fault.

The user can use the DIFL function for lines connected via a one-and-a-half breaker
busbar system; the DIFL function can sense stub faults and through fault currents.

2.2.1 Differential protection characteristics (DIFL)


(i) Characteristic of differential (Id) and restraint (Ir) current plane
The DIFL element has dual percentage-restraint characteristics. Figure 2.2-1 shows two
characteristics on the plane between differential current (Id) axis and restraining current (Ir)
axis. The Id is referred as a vector sum of the phase currents at all terminals. The Ir is referred
as a scalar sum of the phase currents at all terminals. The DIFL function is operated if a cross
point between the Id and the Ir moves into the hatched area of Figure 2.2-1. The DIFL function
can removes charging phase-current using the function of charging current compensation (See
section 2.2.1(vi))

GRL200 (Soft 033 & 037)


- 22 -
6F2S1914 (0.37)

Id

o
[DIFL-I2]
Ir

Y Small current region Large current region

Figure 2.2-1 DIFL element on Ir-Id plane

The characteristic A shows weaker restraint; this characteristic ensures sensitivity


against low-level faults. Conversely, the characteristic B has stronger restraint. That is, the
DIFL characteristic varies its sensitivity depending on the Ir.

Suppose that a fault occurs out of a line and the CT is saturated by the external fault.
The DIFL function can be operated falsely because the differential current due to the increases
erroneously. This is because either by the CT saturation or the CT transient error. Accordingly,
the slope of the characteristic B is steeper than the slope of the characteristic A; as a result,
the increasing Id current does not give rise to the erroneous DIFL operation owing to the CT
saturation or the CT transient error.

However, the DIFL operation in the characteristic B can block this false operation
although the DIFL operation depends on the magnitude of restraining current in the
characteristic B.

The characteristic A and B both are expressed using the following equations:

𝐼𝑑 ≥ α × 𝐼𝑟 + X (2.2-1)

𝐼𝑑 ≥ β × 𝐼𝑟 − Y (2.2-2)

X = (1 − α) × setting[DIFL-I1] (2.2-3)

Y = (β − α) × setting[DIFL-I2] − (1 − α) × setting[DIFL-I1] (2.2-4)

GRL200 (Soft 033 & 037)


- 23 -
6F2S1914 (0.37)

setting[DIFL-Slope1]
α= (2.2-5)
100

setting[DIFL-Slope2]
β= (2.2-6)
100

Equation (2.2-1) and (2.2-2) shows the characteristic A and B, respectively. The user can
set minimum internal fault current using setting [DIFL-I1]. The user can set the knee, which
is referred as crossing point characteristic A and B, using setting [DIFL-I2]. Restraint settings
of the characteristic A and B in percentage are available using settings [DIFL-Slope1] and
[DIFL-Slope2].

(ii) Characteristic of Inflowing and Outflowing currents plane


Figure 2.2-2 provides another expression corresponding to the Figure 2.2-1; the characteristic
is expressed on the plane between the outflowing current (Iout) axis and inflowing current (Iin)
axis. Regarding to the Iout–Iin plain, the DIF operation is performed in the hatched area of
this figure.
Iout

Y / (1 + β)

o X Iin
1−α

Figure 2.2-2 Segregated-phase current differential element (Iin-Iout Plane)

The Iin–Iout plane also has characteristic A and characteristic B; hence, the A and B both
are described in the following equations:

1−α X
Iout ≤ × Iin − (2.2-7)
1+𝛼 1+α

1−β Y
Iout ≤ × Iin + (2.2-8)
1+𝛽 1+𝛽

Equations (2.2-7) and (2.2-8) show the characteristic A and B, respectively. Figure 2.2-2

GRL200 (Soft 033 & 037)


- 24 -
6F2S1914 (0.37)

shows that the characteristic B. It defines the maximum outflowing current when an internal
fault occurs so that the internal fault can be detected by the characteristic B. The outflowing
current can be very much significant for the double-circuit line having three terminals or the
line having three terminals accompanying an outer loop circuit. A part of the fault current
flows out at one terminal and the other part of the fault current flows into at another terminal
depending on the fault location. The fault current flow is discussed later.

(iii) Trip delay timer in main logic


The DIFL function has a delay timer to issue a trip signal so that the DIFL function and the
other protection relays can be well organized. The delay timer, made of definite time type with
setting [TDIFL], can delay to issue a trip signal for the TRC function†. The delay timer is
illustrated in Figure 2.2-3.
DIFL-EN On
8000001C20 TDIFL To TRC
8000001B61 8000001B20
A t 0
& ≥1 8100001C21 & & & ≥1 DIFL-TRIP-A
≥1
B 8100001B62 8100001B21
DIFL#1 t 0
& ≥1 & & & ≥1
8200001C22 ≥1 DIFL-TRIP-B
C 8200001B63 8200001B22
& ≥1 & & & t 0 ≥1
≥1 DIFL-TRIP-C

0.00 to
A 100.00s
&
DIFL#2‡ 8300001B64
B
& &
& ≥1
C &
&
From COMM_APPL 8000001B65
& &
RYBLK-CH1 RELAY BLOCK #1 ≥1 DIFL-ARC-BLOCK

RYBLK-CH2 RELAY BLOCK #2 ≥1


To Fail-safe
From TFC
8000001B67 DIFL-A
TFC.DIFL-A_OP
8100001B68 DIFL-A
TFC.DIFL-B_OP
8200001B69 DIFL-C
TFC.DIFL-C_OP

From Fail-safe ≥1 8000001B60


DIFLFS_OP DIFL-OR

From CT Failure detection 8000021B65

DIFL-CTF_DETECT-A ≥1 & ≥1 ≥1
8100021B66
DIFL-CTF_DETECT-B
≥1
8200021B67
& ≥1 ≥1
DIFL-CTF_DETECT-C
≥1 & ≥1 ≥1
8400021BB1 ≥1
840002EBB0 EXTERNAL_DIFL_CTF

Non &
Block-PerP
DIFL-CTFBlk Block-3P

8000001BB0
800000EBB0 DIFL-TP_BLOCK
≥1
8F00001BB2
8F0000EBB4 DIFL_BLOCK

800000EBB5 8000001BB3
DIFL-INST_OP

810000EBB6 8100001BB4
DIFL-3PTP
≥1 ≥1
DIFL-TPMD 3P

800000EBB5 8200001BB5
DIFL-ARCBLOCK
≥1
DIFL-ARCBlk Block

From PROT_COMMON
DS_OPEN
≥1 8100001B66
DIFL-STUB-Test On
DIFL-STUB-COND
DIFL-STUB &
On

Figure 2.2-3 Generation of trip signals in the DIFL function

GRL200 (Soft 033 & 037)


- 25 -
6F2S1914 (0.37)

†Note:The TRC function is discussed separately. See Chapter Relay application: Trip
circuit.
‡Note: The DIFL#2 element is designed to operate when the DIF function runs in the
dual mode using dual channel (setting [TERM_TOPOLOGY]=2Term-Dual). That is,
the DIFL#1 element operates using the data provided with the first channel
(CH1); the DIFL#2 element operates using the data provided with the second
channel (CH2). Accordingly, the difference of the transmission delays in the both
channels will be cleared, if the communication delays in the both channels vary
depending on the time and place. For more information of the mode, see chapter
Relay application: Transmission control function.

(iv) Trip mode


TRIP commands for opening the CB poles
The DIFL function issues a per-phase trip signal so that a per-phase TRIP COMMAND will be
generated in the TRC function; set a single-phase trip (1P) mode for scheme switch [DIFL-
TPMD]. The user can also set a three-phase trip (3P) mode if TRIP_COMMANDs are not
required to generated in an individual phase. Note that the TRIP_COMMANDs will be issued
for the CB in the TRC function after collecting signals from the other functions. In the ‘1P
mode’ operation, set Per-PHASE for the switch [TP-MODE]. Remember that TRIP
_COMMANDs will be issued in three-phases unconditionally if 3-PHASE is set for the [TP-
MODE]. The user should recognize that the settings of the [DIFL-TPMD] (see Figure 2.2-3) and
the setting [TP-MODE] (see Figure 2.33-3) have cooperation to trip the CB correctly.
Note: Setting 1-PHASE is used to issue TRIP_COMMANDs in three-phases if phase-to-
phase faults occur. For your information, the settings in TRC function affect the
other trip signals from the ZG and other functions. See Chapter Relay application:
Trip circuit for more information.

TRIP commands during CTF


The trip signal can be influenced by the operation in CT circuit-failure detection function (CTF-
DIFL†). The user can select a block signal in response to the CT circuit-failure using scheme
switch [DIFL-CTFBlk]. If blocking a trip signal upon occurrence of the CT circuit-failure is not
required, the user should set Non for scheme switch [DIFL-CTFBlk]. If the failed phase is only
required to blocked on occurrence of the CT circuit-failure, the user should set Block-PerP for
the scheme switch [DIFL-CTFBlk]. On the other hand, if required is to block a trip signal to all
three phases upon occurrence of the CT circuit-failure, the user has to set Block-3P for the
scheme switch [DIFL-CTFBlk].

†Note: The operation and the logic of the CTF-DIFL function is discussed in section
2.2.3.

GRL200 (Soft 033 & 037)


- 26 -
6F2S1914 (0.37)

(v) Switch for DIFL operation


The user should set On for scheme switch [DIFL-EN] prior to the DIFL operation, as illustrated
in Figure 2.2-3. The DIFL#1 element and the DIFL#2 element can be operated per phase basis;
thus the DIFL function can issue respective trip signals “DIFL-TRIP-A, -B, and -C”. Note both
DIFL elements run in parallel; the DILF elements are not designed to operate in hot-standby
mode.

(vi) Setting for autoreclose function


Autoreclose (ARC) function is to re-close the CB again to restore service after tripping the CB.
If the user wishes to operate the ARC function, the user should set Non for scheme switch
[DIFL-ARCBlk]. If the user wishes to not to operate the ARC function on the DIFL operation,
set Block for the scheme switch [DIFL-ARCBlk] so that signal “DIFL-ARC-BLOCK” is injected
not to operate the autoreclose function (ARC). The ARC function is discussed separately. (See
Chapter Relay application: Autoreclose function)

(vii) Blocking trip issuing by communication failure supervision


The trip signals are blocked when communication failure is detected†. Communication
application function (DIF_COMM) can monitor data error, sampling synchronism and
reception from the remote terminal.

Communication failure is monitored for each channel and is combined with the results of
such as self-supervision, sampling synchronism and CRC. It is assigned to each signal (RELAY
BLOCK #1 and #2, which are used to block the output of DIFL#1 and #2 elements
instantaneously to avoid unwanted tripping while the communication failure is detected.

†Note:For more information, see Chapter Relay application: Communication application


function. The chapter tabulates relevant communication failure monitoring points
in Data ID list.
‡Note:See device dependent features in Chapter Automatic supervision: Supervision
tasks.

(viii) Blocking trip issuing by by PLC connection


When the user wishes the DIFL function not to issue a trip signal, the user can use PLC
connection point “DIFL_BLOCK” so that the DIFL function cannot issue a trip signal, as seen
in Figure 2.2-3. The PLC connection point is useful when the user wishes to program no to
operate the DIFL function externally.

GRL200 (Soft 033 & 037)


- 27 -
6F2S1914 (0.37)

2.2.2 Check relays characteristics (OCs and UVs)


8000011C20
A ≥1 8000011B60
OC- 8100011C21
DIFL B
8200011C22
C
& To DIFL main logic
≥1
DIFLFS-OC-EN On
DIFLFS-OP

8400011C24
A ≥1 ≥1 8100011B61
OCD- 8500011C25
DIFL B ≥1
8200011C26
C ≥1 &
S 1
R
S 1
R
S 1
DIFLFS-OCD-EN On R

8800011C28
UVD- A ≥1 ≥1 8A00011B62
DIFL 8900011C29
(†) B ≥1
8A00011C2A
C ≥1 &
S 1
R
S 1
R
S 1
DIFL-DUV-EN On R
To CT failure detection

UVD-DIFL-AT (†)
UVD-DIFL-BT (†)
UVD-DIFL-CT (†)
From DIFL main logic
DIFL-A ≥1

DIFL-B ≥1

DIFL-C ≥1
From RDIF
REMOTE.DIFL-A

REMOTE.DIFL-B

REMOTE.DIFL-C
8000111C20
A ≥1 8800111B60 To CT failure detection
UV- 8100111C21
DIFL B UV-DIFL-OP
8200111C22
C & UVS-DIFL-OP

DIFL-UV-EN On

8400011C20
AB ≥1 8900011B61
UVS- 8500011C21
DIFL BC
8600011C22
CA &

DIFL-UVS-EN On

8300011BB0

830001EBB0 ADD.DIFLFS
DIFLFS-EN (‡) Off

Figure 2.2-4 Check relays logic


†Note:UVD-DIFL element and signal are programmed with settings [DUV-DIFL] etc.
Refer to (v).
‡Note:The user should set Off for the scheme switch [DIFLFS-EN] when the operation of
check relays is not required.

To remove unnecessary operations in the DIFL function, check relays are introduced and
the DIFL function is allowed to operate during the check relays being in operation. The check
relays consists of five relay elements, a signal aggregated with the five relay elements is
injected into the DIFL logic, as shown in Figure 2.2-4. The user should set On for scheme

GRL200 (Soft 033 & 037)


- 28 -
6F2S1914 (0.37)

switch [DIFLFS-EN] when the operation of the check relays is required to operate for the DIFL
function.

(i) Current change detection element (OCD-DIFL)


Figure 2.2-5 shows a current vector (IM) measured at the present and a pre-current vector (IN)
measured at one sampling cycle† ago. When the magnitude of difference between (Is) is larger
than a setting, the OCD-DIFL element is operated. The OCD-DIFL element is expressed by
the following equation:

|𝐼𝑀 − 𝐼𝑁 | > 𝐼𝑠 (2.2-9)

where Is is referred in order to determine the operation of the OCD-DIFL element; the
user can set the value using setting [OCD-DIFL], which is applied to adjust the decision point
for the operation. The user can set the value among 0.05 to 0.20A when 1A rating‡ is applied
for the VCT module. When 5A rating‡ is applied for the VCT module, the setting value is
chosen among 0.25 to 1.00A.

The quiescent load current does not affect the sensitivity of the OCD-DIFL element; thus,
the OCD-DIFL element can detect a fault current sensitively.

IN
Is

IM

Figure 2.2-5 Current change Is detected by IM and IN


†Note:We define a sampling cycle as 7.5 electrical degrees.
‡Note:For the rating and the VCT module, see Chapter Technical description:
Transformer module for AC analog input.

(ii) Over-current detection (OC-DIFL)


For OC-DIFL relay element the user can set the sensitivity using setting [OC-DIFL]. When 1A
rating, OC-DIFL value is selected from 0.05 to 50.00A. When 5A rating, the setting value is
placed from 0.10 to 250.00A.

(iii) Under-voltage element (UV-DIFL)


For UV-DIFL relay element the user can set the sensitivity using setting [UV-DIFL]. The value
is selected from 5.0 to 130.0 V.

GRL200 (Soft 033 & 037)


- 29 -
6F2S1914 (0.37)

(iv) Under-voltage element for phase-to-phase (UVS-DIFL)


For UVS-DIFL relay element the user can set the sensitivity using setting [UVS-DIFL]. The
setting value is selected from 5.0 to 130.0V.

(v) Under-voltage change detection element (UVD-DIFL)


Suppose there is a difference between the voltage vector at present (VM) and the pre-voltage
vector measured one sampling cycle ago (VN). When the magnitude of the difference between
is larger than setting [DUV-DIFL], the UVD-DIFL element† is operated. The setting value is
chosen among 1 to 20V.
†Note: UVD-DIFL element (shown in Figure 2.2-4) is programmed with setting [DUV-
DIFL] as described above. Similarly, signals for monitoring and PLC output signals
are referred ‘UVD-DIFL-AT’ etc., as shown in Figure 2.2-4 and Figure 2.2-6.

(vi) Check relays activation


The user can set On for respective scheme switches [DIFLFS-OCD-EN], [DIFLFS-OC-EN],
[DIFL-UV-EN], [DIFL-UVS-EN], and [DIFL-DUV-EN] so that the user can select the operation of
the respective check relays.

2.2.3 CT circuit-failure detection (DIFL-CTF)


The CT circuit-failure-detection function (DIFL-CTF) is to detection of the breaking wire in
the CT circuit. Signals of the check relays are injected into the below logic so that a trip signal
is not issued upon occurrence of CT failure.
8400021ABB1
840002EBB0 EXTERNAL_DIFL-CTF
To DIFL main logic
8000021C20 8000021B65
A ≥1 DIFL-CTF_DETECT-A
DIFL- 8100021C21 & ≥1 8100021B66
CTF B ≥1 DIFL-CTF_DETECT-B
8200021C22 & ≥1 8200021B67
C ≥1 DIFL-CTF_DETECT-C
& ≥1
≥1 8300021B23 8000021B64
≥1 1
≥1 t 0 DIFL-CTF_ALARM
1
CTFL-EN OPT-ON
10.00s To DIFG
ON t 0 1
1 & DIFL-CTF_DET

From check relays 10.00s S 1 ≥1 To CT failure detection


R
UVD-DIFL-AT (†) S 1
≥1 & DIFL-CTF-A_DET_T
UVD-DIFL-BT (†) R
UVD-DIFL-CT (†) t 0 ≥1
& 1 DIFL-CTF-B_DET_T

0.1s DIFL-CTF-C_DET_T
UV-DIFL-CT &
UVS-DIFL-CT

From CT failure detection


DIFL-CTF-A_DET_T S 1
& 1
R
t 0 ≥1
DIFL-CTF-B_DET_T 1
& 1
DIFL-CTF-C_DET_T 0.1s
& 1

≥1 &
1 S 1
8F00001BB2
8F0000EBB4 DIFL_BLOCK ≥1 R
t 0 ≥1
8100021BB0 1
810002BB1 DIFL-CTF_BLOCK ≥1 0.1s
From AMF
AMF-ON

Figure 2.2-6 CT failure detection logic

The user can select the detection type for the CT circuit-failure using setting [DIFL-CTF].

GRL200 (Soft 033 & 037)


- 30 -
6F2S1914 (0.37)

If the user wishes to reset the DIFL-CTF operation after the breaking wire is removed, the
user should set On for scheme switch [CTFL-EN]. If the user wishes to reset the DIFL-CTF
operation after any operation of the DUV-DIFL relays, the user should set OPT-On for the
scheme switch [CTFL-EN]. On the other hand, if the user wishes not to operate the DIFL-CTF
function, set Off for the scheme switch.

If the failure in the CT circuit lasts for 10sec or longer, signal “DIFL-CTF-ALARM” is
also provided‡. The user can use an external CT circuit-failure function, provided the user
wishes to use the external function in place of the DIFL-CTF function; a PLC connection point
“EXTERNAL-DIFL-CTF” is provided for this purpose.

If the CT circuit-failure detection function is required not to operate, the user can remove
the operation using PLC connection point “DIFL-CTF_BLOCK”. The CT circuit-failure
detection function can also be stopped when the AMF-ON signal is injected.

†Note:AMF feature is used for the test. To generate the AMF signal for the test, see
chapter User interface: Test sub-menu.
‡Note:They are transferred to the automatic supervision function, which we shall
discuss separately.

2.2.4 Charging-current compensation (DIFL-Ic)


As illustrated in Figure 2.2-7, when the DIFL function is used for underground cables or long
overhead transmission lines, charging-current flows due to the influence of the line capacitance.
The changing-current may be observed as an erroneous differential current.

Bus G Bus H

IED G IED H

Ic

Figure 2.2-7 Phenomenon of charging current

The DIFL sensitivity can be compensated using the charging current, but its
compensation can be performed at the expense of reduced sensitivity to internal faults. In
addition, the charging current can vary strongly in response to the running line-voltage. Thus,
the user should take into account it for the setting.

The DIFL function provides a charging current compensation function in order to avoid
the effect of the charging current so that the DIFL sensitivity is maintained. The compensation

GRL200 (Soft 033 & 037)


- 31 -
6F2S1914 (0.37)

function keeps calculating the charging current in response to the running line-voltage
provided by the VT on the line. As a result, the DIFL function can compensate for the charging
current.

To apply the compensation into the DIFL function, the user should set line charging
current for setting [DIFL-IcC] and rated-line voltage for setting [DIFL-Vn]. The line capacitance
is computed between the relays at local and remote-terminals using the settings. That is, the
line capacitance is divided by two when the number of the IEDs is two. On the other hand, the
line capacitance is divided by three when the number of the relays is three†.

†Note:If one of the three relays is not operated during testing, the line capacitance is
divided by two.

For the provision of the line voltage, the relays can keep calculating the sharing charging
current per sample-by-sample basis. The equation is denoted as follows:

𝑑𝑉
Ic = C (2.2-10)
𝑑𝑡

where,
Ic = line charging current
C = line capacitance calculated using the settings [DIFL-IcC] and [DIFL-Vn]
V = line voltage measured

By using the Ic, the DIFL function can calculate a line current compensated per a sample-
by-sample basis as follows:

I = I ′ − Ic (2.2-11)

where,
I = compensated current
I’ = actual measured current

All necessary phase information has to be taken account basically. This is because the
DIFL function calculates both the charging current and the compensated line current per
sample-by-sample basis.

2.2.5 Differential current monitor (DIFL-IDSV)


Monitoring function for differential current (DIFL-IDSV) is provided so that detecting
spuriousness in the differential current is feasible during the CT circuit failure. The user can
adjust the removal period for issuing using setting [TDIFL-IdSV]. To operate the DIFL-IDSV

GRL200 (Soft 033 & 037)


- 32 -
6F2S1914 (0.37)

function, the user should set scheme switch [DIFL-IdSV-EN] On; setting [DIFL-IdSV] is also
provided to set the monitoring level. As shown in Figure 2.2-8, the results of the monitoring
function are provided at PLC connection point “DIFL-IDSV”; they are transferred to the
automatic supervision function, which we shall discuss separately.
TDIFL-IdSV
8000031C20 8000001B61
t 0
A DIFL-IDSV-A
DIFL 8100031C21 & 8100001B62
-SV B t 0
DIFL-IDSV-B
8200031C22 & 8200001B63
C t 0 DIFL-IDSV-C
&
0 to 300s
830003EBB0 8300031BB2
DIFL-SV_BLOCK ≥1 &
≥1 8300001B64
8F00001BB2
8F0000EBB4 DIFL_BLOCK DIFL-IDSV
≥1
From AMF

AMF_OFF ≥1

DIFL-IDSV-EN
On

Figure 2.2-8 Differential current monitor logic


If the monitoring function is unrequired, the user can remove the operation using PLC
connection point “DIFL-SV_BLOCK”. The monitoring function can also be stopped when the
AMF_OFF signal† is injected.

†Note:The user can switch off the monitoring function during the test. To generate the
AMF_OFF signal, set Off for setting [A.M.F]. For the operation, see chapter User
interface: Test sub-menu.

GRL200 (Soft 033 & 037)


- 33 -
6F2S1914 (0.37)

2.2.6 Setting
DIFL (Function ID: 410001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
DIFL-EN Off / On - DIFL protection scheme switch On
0.10 - 0.50 -
DIFL-I1 A Minimum operating value 1.00 5.00
2.00 10.00
0.6 - 3.0 -
DIFL-I2 A Knee point of large current region 8.2 41.0
60.0 300.0
Small current region percent slope of Id-Ir
DIFL-Slope1 10 - 50 % 17
characteristic
Large current region percent slope of Id-Ir
DIFL-Slope2 50 - 100 % 100
characteristic
IcC DIFL-IcC.EN Off / On - Charging current compensation use or not Off
0.00 - 0.00 -
DIFL-IcC A DIFL charging current compensation 0.00 0.00
1.00 5.00
DIFL-Vn 100 - 120 V DIFL rated voltage 110
Output Non / Block-3P / Block-
DIFL-CTFBlk - DIFL operation block by CTF Non
PerP
CTF CTFL-EN Off / On / OPT-On - CTF detection enable On
0.05 - 0.25 -
DIFL-CTF A DIF relay for CTF detection, operating value 0.10 0.50
2.00 10.00
Fail DIFLFS-EN Off / On - Fail safe enable Off
safe DIFLFS-OC-EN Off / On - Fail safe OC-DIFLFS enable On
DIFLFS-OCD-EN Off / On - Fail safe OCD-DIFLFS enable On
DIFL-UV-EN Off / On - Fail safe UV-DIFL enable On
DIFL-UVS-EN Off / On - Fail safe UVS-DIFL enable On
DIFL-DUV-EN Off / On - Fail safe DUV-DIFL enable On
0.02 - 0.10 -
OC-DIFL A OC relay for fail-safe, operating value 1.00 5.00
50.00 250.00
0.05 - 0.25 -
OCD-DIFL A OCD relay for fail safe, operating value 0.10 0.50
0.20 1.00
UV relay for fail-safe and CTF blocking, operating
UV-DIFL 5.0 - 130.0 V 46.0
value
UVS relay for fail-safe and CTF blocking, operating
UVS-DIFL 5.0 - 130.0 V 80.0
value
DUV relay for fail-safe and CTF blocking, operating
DUV-DIFL 1 - 20 V 5
value
DIFL-ARCBlk Non / Block - Autoreclose execution block by DIFL-trip Non
DIFL trip mode, phase segregated trip or 3-phase
DIFL-TPMD 1P / 3P - 1P
trip
TDIFL 0.00 - 100.00 s DIFL trip delay time 0.00
IdSV DIFL-IdSV-EN Off / On - Differential current monitoring enable Off
0.05 - 0.25 -
DIFL-IdSV A DIF relay for Id-SV, operating value 0.10 0.50
2.00 10.00
TDIFL-IdSV 0 - 300 s Differential current monitoring, detection time 10

GRL200 (Soft 033 & 037)


- 34 -
6F2S1914 (0.37)

2.2.7 Data ID
 Signal monitoring point
DIFL (Function ID: 410001)
Element ID Name Description
8300011BB0 ADD.DIFLFS Add File-safe condition

8000001C20 DIFL-A DIFL relay element operated (phase-A)

8000001B65 DIFL-ARC-BLOCK Autoreclose block signal by DIF-L protection operation

8100001C21 DIFL-B DIFL relay element operated (phase-B)

8200001C22 DIFL-C DIFL relay element operated (phase-C)

8000021C20 DIFL-CTF-A DIFL-CTF relay element operated (phase-A)

8100021C21 DIFL-CTF-B DIFL-CTF relay element operated (phase-B)

8200021C22 DIFL-CTF-C DIFL-CTF relay element operated (phase-C)

8000021B64 DIFL-CTF_ALARM Alarm signal by CT failure detection

8100021BB0 DIFL-CTF_BLOCK DIF-L ctf detect block

8300021B63 DIFL-CTF_DET CT failure detection

8000021B60 DIFL-CTF_DET-A CT failure detection (phase-A)

8100021B61 DIFL-CTF_DET-B CT failure detection (phase-B)

8200021B62 DIFL-CTF_DET-C CT failure detection (phase-C)

8300021B23 DIFL-CTF_DETECT CT failure detection

8000021B65 DIFL-CTF_DETECT-A CT failure detection (phase-A)

8100021B66 DIFL-CTF_DETECT-B CT failure detection (phase-B)

8200021B67 DIFL-CTF_DETECT-C CT failure detection (phase-C)

8300031B23 DIFL-IDSV Differential current monitoring

8000031B60 DIFL-IDSV-A Differential current monitoring (phase-A)

8100031B61 DIFL-IDSV-B Differential current monitoring (phase-B)

8200031B62 DIFL-IDSV-C Differential current monitoring (phase-C)

8300001B64 DIFL-OPT DIF-L protection operated

8000001B61 DIFL-OPT-A DIF-L protection operated (phase-A)

8100001B62 DIFL-OPT-B DIF-L protection operated (phase-B)

8200001B63 DIFL-OPT-C DIF-L protection operated (phase-C)

8000001B60 DIFL-OR DIFL relay element operated (3-phases OR)

8200001BB1 DIFL-RDIF_BLOCK Remote differential detect block

8100001B66 DIFL-STUB-COND DIF-L STUB condition

8000031C20 DIFL-SV-A DIFL-SV relay element operated (phase-A)

8100031C21 DIFL-SV-B DIFL-SV relay element operated (phase-B)

8200031C22 DIFL-SV-C DIFL-SV relay element operated (phase-C)

8300031BB0 DIFL-SV_BLOCK Differential current monitoring block

8000001BB0 DIFL-TP_BLOCK DIF-L trip block

8000001B20 DIFL-TRIP-A Trip signal by DIF-L protection operation (phase-A)

8100001B21 DIFL-TRIP-B Trip signal by DIF-L protection operation (phase-B)

8200001B22 DIFL-TRIP-C Trip signal by DIF-L protection operation (phase-C)

8F00011B23 DIFLFS_OP Fail safe for DIF-L trip

8100001BB4 DIFL_3PTP Trip signal by DIF-L protection operation (3-phase)

8200001BB5 DIFL_ARCBLOCK Autoreclose block signal by DIF-L protection operation

8F00001BB2 DIFL_BLOCK Block all the above four

8000001BB3 DIFL_INST_OP DIF-L protection instant operation command

8400021BB1 EXTERNAL_DIFL-CTF External CTF condition

GRL200 (Soft 033 & 037)


- 35 -
6F2S1914 (0.37)

 Signal monitoring point


DIFL (Function ID: 410001)
Element ID Name Description
8000011B60 OC-DIFL Fail safe permitted by OC

8000011C20 OC-DIFL-A OC-DIFL relay element operated (phase-A)

8100011C21 OC-DIFL-B OC-DIFL relay element operated (phase-B)

8200011C22 OC-DIFL-C OC-DIFL relay element operated (phase-C)

8100011B61 OCD-DIFL Fail safe permitted by OCD

8400011C24 OCD-DIFL-A OCD-DIFL relay element operated (phase-A)

8500011C25 OCD-DIFL-B OCD-DIFL relay element operated (phase-B)

8600011C26 OCD-DIFL-C OCD-DIFL relay element operated (phase-C)

8000001BB6 R1.DIFL-A_OP Receiving signal from Remote Terminal 1 (phase-A)

8100001BB7 R1.DIFL-B_OP Receiving signal from Remote Terminal 1 (phase-B)

8200001BB8 R1.DIFL-C_OP Receiving signal from Remote Terminal 1 (phase-C)

8000001BB9 R2.DIFL-A_OP Receiving signal from Remote Terminal 2 (phase-A)

8100001BBA R2.DIFL-B_OP Receiving signal from Remote Terminal 2 (phase-B)

8200001BBB R2.DIFL-C_OP Receiving signal from Remote Terminal 2 (phase-C)

8000001BBC R3.DIFL-A_OP Receiving signal from Remote Terminal 3 (phase-A)

8100001BBD R3.DIFL-B_OP Receiving signal from Remote Terminal 3 (phase-B)

8200001BBE R3.DIFL-C_OP Receiving signal from Remote Terminal 3 (phase-C)

8000001BBF R4.DIFL-A_OP Receiving signal from Remote Terminal 4 (phase-A)

8100001BC0 R4.DIFL-B_OP Receiving signal from Remote Terminal 4 (phase-B)

8200001BC1 R4.DIFL-C_OP Receiving signal from Remote Terminal 4 (phase-C)

8000001B6A REMOTE.DIFL-A Remote differential protection (phase-A)

8100001B6B REMOTE.DIFL-B Remote differential protection (phase-B)

8200001B6C REMOTE.DIFL-C Remote differential protection (phase-C)

8200001B6E REMOTE.DIFL-OPT Remote differential protection

8300001B6D REMOTE.DIFL-OR Remote differential protection (3-phase OR)

8000001B67 TFC.DIFL-A_OP Remote terminal DIFL relay element operated for TFC (phase-A)

8100001B68 TFC.DIFL-B_OP Remote terminal DIFL relay element operated for TFC (phase-B)

8200001B69 TFC.DIFL-C_OP Remote terminal DIFL relay element operated for TFC (phase-C)

8800111B60 UV-DIFL Fail safe permitted by UV

8000111C20 UV-DIFL-A UV-DIFL relay element operated (phase-A)

8100111C21 UV-DIFL-B UV-DIFL relay element operated (phase-B)

8200111C22 UV-DIFL-C UV-DIFL relay element operated (phase-C)

8A00011B62 UVD-DIFL Fail safe permitted by UVD

8800011C28 UVD-DIFL-A UVD-DIFL relay element operated (phase-A)

8900011C29 UVD-DIFL-B UVD-DIFL relay element operated (phase-B)

8A00011C2A UVD-DIFL-C UVD-DIFL relay element operated (phase-C)

8900111B61 UVS-DIFL Fail safe permitted by UVS

8400111C24 UVS-DIFL-AB UVS-DIFL relay element operated (phase-AB)

8500111C25 UVS-DIFL-BC UVS-DIFL relay element operated (phase-BC)

8600111C26 UVS-DIFL-CA UVS-DIFL relay element operated (phase-CA)

GRL200 (Soft 033 & 037)


- 36 -
6F2S1914 (0.37)

 Connection point in PLC logic


DIFL (Function ID: 41001)
Element ID Name Description
830001EBB0 ADD.DIFLFS Add File-safe condition

810002EBB1 DIFL-CTF_BLOCK DIF-L ctf detect block

820000EBB2 DIFL-RDIF_BLOCK Remote differential detect block

830003EBB3 DIFL-SV_BLOCK Differential current monitoring block

800000EBB0 DIFL-TP_BLOCK DIF-L trip block

810000EBB6 DIFL_3PTP Trip signal by DIF-L protection operation (3-phase)

820000EBB7 DIFL_ARCBLOCK Autoreclose block signal by DIF-L protection operation

8F0000EBB4 DIFL_BLOCK Block all the above four

800000EBB5 DIFL_INST_OP DIF-L protection instant operation command

840002EBB0 EXTERNAL_DIFL-CTF External CTF condition

800000EBB8 R1.DIFL-A_OP Receiving signal from Remote Terminal 1 (phase-A)

810000EBB9 R1.DIFL-B_OP Receiving signal from Remote Terminal 1 (phase-B)

820000EBBA R1.DIFL-C_OP Receiving signal from Remote Terminal 1 (phase-C)

800000EBBB R2.DIFL-A_OP Receiving signal from Remote Terminal 2 (phase-A)

810000EBBC R2.DIFL-B_OP Receiving signal from Remote Terminal 2 (phase-B)

820000EBBD R2.DIFL-C_OP Receiving signal from Remote Terminal 2 (phase-C)

800000EBBE R3.DIFL-A_OP Receiving signal from Remote Terminal 3 (phase-A)

810000EBBF R3.DIFL-B_OP Receiving signal from Remote Terminal 3 (phase-B)

820000EBC0 R3.DIFL-C_OP Receiving signal from Remote Terminal 3 (phase-C)

800000EBC1 R4.DIFL-A_OP Receiving signal from Remote Terminal 4 (phase-A)

810000EBC2 R4.DIFL-B_OP Receiving signal from Remote Terminal 4 (phase-B)

820000EBC3 R4.DIFL-C_OP Receiving signal from Remote Terminal 4 (phase-C)

GRL200 (Soft 033 & 037)


- 37 -
6F2S1914 (0.37)

Zero-sequence current differential protection (DIFGL)


Zero-sequence current differential protection (DIFGL) function is provided to enhance
sensitivity upon occurrence of an earth fault having high impedance. To perform sensitive
protection in the DIFGL function, residual current (Ie) is applied. Note that the residual
current is introduced by the CT for the residual circuit.

2.3.1 Differential protection characteristics (DIFGL)


(i) Ir-Id plane for DIFGL function
Figure 2.3-1 shows the percentage restraining characteristic in the DIFGL element.
Differential current (Id0) denotes a vector summation of the residual currents in all terminals;
restraining current (Ir0) denotes a scalar summation of the residual currents in all terminals.
The Id0 and Ir0 currents are also derived using Equations (2.3-1) and (2.3-2):

Id0 = |I10 + I20 + I30 | (2.3-1)

Ir0 =|I10 |+|I20 |+|I30 | (2.3-2)

where,
I10: Current in zero-sequence flowing at the local terminal1
I20: Current in zero-sequence flowing at the remote terminal2
I30: Current in zero-sequence flowing at the other remote terminal3

Id0

Operating Zone

[DIFGL-Slope]
Z
o
Ir0

Figure 2.3-1 Zero-sequence current differential element (Ir0-Id0 Plane for DIFGL)

The DIFGL characteristic is identical to the DIFL characteristic for which is defined in
the small current region. The DIFGL characteristic is expressed using the following equations:

Id0 ≥ γ × 𝐼𝑟0 + 𝑍 (2.3-3)

Z = (1 − γ) × setting [DIFGL-I] (2.3-4)

GRL200 (Soft 033 & 037)


- 38 -
6F2S1914 (0.37)

setting [DIFGL-Slope]
γ= (2.3-5)
100

The user should set a minimum residual current for setting [DIFGL-I] for the occurrence
of a fault. The user should also set slop characteristic for setting [DIFGL-Slope].

(ii) Inflow current (Iin) and Outflow current (Iout) plain for DIFGL function
Figure 2.2-2 provides another expression corresponding to the Figure 2.3-1 characteristic; the
user can notice that the characteristic is expressed on the plane between the outflowing current
(Iout) axis and inflow current (Iin) axis. The element of the DIFGL function operates for the
hatched area on the Iout–Iin plain.
Iout

[DIFGL-Slope]

Operating zone

o [DIFGL-I] 2×In Iin

Figure 2.3-2 Zero-sequence current differential element (Iin-Iout Plane)

The hatched area is expressed using the following equation

100 − [DIFGL_Slope] [DIFGL_Slope] − 100


Iout ≤ × Iin −
100 + [DIFGL_Slope] 100 + [DIFGL_Slope] (2.3-6)
× [DIFGL_I]

where the Iin should be less than two times a rated current (In); the In is defined in the
VCT of the relay (for more information with regard to the VCT, see the Chapter Technical
description: Transformer module for AC analogue input).

(iii) Trip delay timer in main logic


The DIFGL function has a delay timer to issue a trip signal; thereby, the operation of DIFGL
function can be coordinated with the operations of the other protection relays. The delay timer
is a kind of definite time type; the user can set a delay time for setting [TDIFGL]. Figure 2.3-3
illustrates issuing the trip signal for the TRC function† together with the delay timer.

GRL200 (Soft 033 & 037)


- 39 -
6F2S1914 (0.37)

To TRC
8000001C23 TDIFGL 8000001B23
t 0
≥1 & & & ≥1 DIFGL-TRIP
DIFGL#1
0.00 to 300.00s

8000001B60
& &
DIFGL#2 DIFGL-ARC-BLOCK

DIFGL-EN On

From TFC
8000001B61
TFC.DIFGL_OP

From Fail-safe
DIFGLFS_OP

From DIFL
DIFL-CTF_DETECT ≥1 ≥1

DIFGL-CTFBlk Off
Block

800000EBB0 8000001BB0
DIFGL-TP_BLOCK
≥1
8F00001BB2
8F0000EBB2 DIFGL_BLOCK

800000EBB3 8000001BB3
DIFGL-INST_OP

810000EBB4 8100001BB4
DIFGL-ARCBLOCK
≥1
DIFGL-ARCBlk
Block

Figure 2.3-3 Generation of trip signal in the DIFGL function


†Note:The TRC function is discussed separately. See Chapter Relay application: Trip
circuit.

(iv) Trip mode


The trip signal generated in the DIFGL function is a “three-phase trip (DIFGL-TRIP)” singnal.
The “three-phase trip” signal switches off the CB in the three-poles.

(v) Operation switch


The user should set On for scheme switch [DIFGL-EN] prior to the DIFGL operation; the
scheme switch is also illustrated in Figure 2.3-3.

(vi) Setting for autoreclose function


When autoreclose function (ARC) is provided together with the DIFGL function, the ARC
function can re-close the CB again after tripping the CB. When the user wishes to operate the
ARC function, the user should set Non for scheme switch [DIFGL-ARCBlk]. On the other hand,
the user wishes to not to operate the ARC function during the DIFGL operation, set Block for
the scheme switch [DIFGL-ARCBlk] so that a block signal “DIFGL-ARC-BLOCK” is generated
and injected to the autoreclose function (ARC). The ARC function is discussed separately. (See
Chapter Relay application: Autoreclose function)

GRL200 (Soft 033 & 037)


- 40 -
6F2S1914 (0.37)

(vii) Block of issuing a trip signal


If the user does not wish that the DIFGL function issues a trip signal, the user can use PLC
connection point “DIFGL_BLOCK” so that the DIFGL function cannot issue a trip signal when
a block signal enters. The PLC connection point “DIFGL_BLOCK” is also shown in Figure
2.3-3; the one is useful when a user-made-program is required to instruct to block externally.

2.3.2 Check relay characteristic (EFD)


To remove unnecessary operations in the DIFGL function, a check relay are accommodated;
consequently, the operation of the DIFGL function is possible during the check relay being in
operation. Figure 2.3-4 shows the check relay and its logic.

EFD- 8000011B60
8000011C23 To DIFGL main logic
DIFGL ≥1 & ≥1
8000011B23

DIFGLFS-OP
DIFGL#1 1 S 1
≥1 R

DIFGL#2

DIFGLFS-FED-EN

On

8200011BB0

820001EBB0 ADD.DIFGLFS

DIFGLFS-EN

Off

Figure 2.3-4 Check relay logic

(i) Earth-fault-current-change detection element (EFD-DIFGL)


Figure 2.3-5 shows a current vector (IM) measured at the present and a pre-current vector (IN)
measured at one sampling cycle† ago. When the magnitude of difference between (Is) is larger
than a setting, the operation the EFD-DIFGL element is introduced. The EFD-DIFGL element
is expressed by the following equation:

|𝐼𝑀 − 𝐼𝑁 | > 𝐼𝑠 (2.3-7)

where Is is referred in order to determine the operation of the EFD-DIFGL element; the
user can set the value using setting [EFD-DIFGL], which is applied to adjust the decision point
for the operation. The user can set the value among 0.05 to 0.20A when 1A rating‡ is set for
the VCT module. When 5A rating‡ is set for the VCT module, the setting value is chosen among
0.25 to 1.00A.

GRL200 (Soft 033 & 037)


- 41 -
6F2S1914 (0.37)

IN
Is

IM

Figure 2.3-5 Current change Is detected by IM and IN


†Note:One sampling cycle is discussed later.
‡Note:For the rating and the VCT module, see Chapter Technical description:
Transformer module for AC analog input.

(ii) Check relay activation


For the operation of the check relay the user should set On for scheme switch [DIFGL-EFD-EN].
On the other hand, the user should set Off for scheme switch [DIFGLFS-EN] if the check relay
is not required for the operation of the DIFGL function.

2.3.3 CT circuit-failure detection (DIFGL-CTF)


The user can set the DIFGL function not to operate upon occurrence of the failure in the CT
circuit. As shown in Figure 2.3-3, the logic of DIFGL function can acquire a detection signal
“DIFL-CTF-DETECT” from the DIFL function so that the DIFGL function cannot operate
when the signal “DIFL-CTF-DETECT” enters. The user should set On for scheme switch
[DIFGL-CTFBlk] to acquire the detection signal. (For more information of the CT circuit-failure
detection, see section CT circuit-failure detection in DIFL function)

2.3.4 Charging-current compensation (DIFGL-Ic)


(i) Setting for the compensation
When the DIFGL function is applied for the protection of underground cables or long overhead
transmission lines, charging-current should be taken account. In other word, the DIFGL
function is influenced by the line capacitance. The user may see charging-current as an
erroneous differential-current†. Therefore, the user should set the values of “line charging
current” and “line voltage” using settings [DIFGL-IcC] and [DIFGL-Vn] when the charging
current compensation function is used in the DIFGL function. The setting values are used to
calculate the line capacitance. The setting values are divided by two when there are two relays
in the system, whereas the setting values are divided by three when there are three relays in
the system.

If line-voltage is not absent, charging-current is shared continuously per-sample-by-


sample basis. The equation is denoted as follows:

GRL200 (Soft 033 & 037)


- 42 -
6F2S1914 (0.37)

𝑑𝑉
Ic = C (2.3-8)
𝑑𝑡

where,
Ic = line charging current
C = line capacitance calculated using settings [DIFGL-IcC] and [DIFGL-Vn]
V = line voltage measured

After that, the line current compensated for the charging-current is calculated per-
sample-by-sample basis:

I = I ′ − Ic (2.3-9)

where,
I = compensated current
I’ = actual measured current

All necessary phase information has to be taken account basically. This is because the
DIFL function calculates both the charging current and the compensated line current per
sample-by-sample basis.

(ii) Activation switch


The user should set On for scheme switch [DIFGL-IcC.EN] for the DIFGL-Ic operation.

†Note:The differential-current also discussed in the DIFL function. See section 2.2.

GRL200 (Soft 033 & 037)


- 43 -
6F2S1914 (0.37)

2.3.5 Setting
DIFGL (Function ID: 411001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
DIFGL-EN Off / On - DIFGL protection scheme switch On
0.05 - 0.25 - Minimum operating value
DIFGL-I A 0.50 2.50
1.00 5.00
DIFGL-Slope 10 - 50 % Percent slope of Id-Ir characteristic 17
IcC DIFGL-IcC.EN Off / On - Charging current compensation use or not Off
0.00 - 0.00 - DIFGL charging current compensation
DIFGL-IcC A 0.00 0.00
1.00 5.00
DIFGL-Vn 100 - 120 V DIFGL rated voltage 110
Output DIFGLFS-EN Off / On - Fail safe scheme switch Off
DIFGL-CTFBlk Non / Block - DIFGL operation block by CTF Non
DIFGL-ARCBlk Non / Block - Autoreclose execution block by DIFGL-trip Block

GRL200 (Soft 033 & 037)


- 44 -
6F2S1914 (0.37)

2.3.6 Data ID
 Signal monitoring point
DIFGL (Function ID: 411001)
Element ID Name Description
8200011BB0 ADD.DIFGLFS Add File-safe condition

8000001C23 DIFGL DIFGL relay element operated

8000001B60 DIFGL-ARC-BLOCK Autoreclose block signal by DIFG-L protection operation

8100001BB1 DIFGL-RDIF_BLOCK Remote differential detect block

8000001BB0 DIFGL-TP_BLOCK DIFG-L trip block

8000001B23 DIFGL-TRIP Trip signal by DIFG-L protection operation

8000011B23 DIFGLFS_OP Fail safe for DIFG-L trip

8100001BB4 DIFGL_ARCBLOCK Autoreclose block signal by DIFG-L protection operation

8F00001BB2 DIFGL_BLOCK Block all the above 2

8000001BB3 DIFGL_INST_OP DIFG-L protection instant operation command

8000011C23 EFD-DIFGL EFD-DIFGL relay element operated

8000011B60 EFD-DIFGLFS Fail safe permitted by EFD

8000001B61 TFC.DIFGL_OP Remote terminal DIFGL relay element operated for TFC

 Connection point in PLC logic


DIFGL (Function ID: 411001)
Element ID Name Description
820001EBB0 ADD.DIFGLFS Add File-safe condition

800000EBB0 DIFGL-TP_BLOCK DIFG-L trip block

810000EBB4 DIFGL_ARCBLOCK Autoreclose block signal by DIFG-L protection operation

8F0000EBB2 DIFGL_BLOCK Block all the above 2

800000EBB3 DIFGL_INST_OP DIFG-L protection instant operation command

GRL200 (Soft 033 & 037)


- 45 -
6F2S1914 (0.37)

CT saturation countermeasure in DIFL (CTsat in DIFL)


Counter measure for CT saturation is required when a large current is induced by the
occurrence of through-fault current† and so on. If any CT saturation occurs, the DIFL function
may see a differential current erroneously; thus, the counter measure for the CT saturation is
requisite in the DIFL operation. Consequently, the DIFL function can operate stably even if
the CT saturation occurs. The operation availability for the counter measure is dependent upon
the communication capacity‡ and the number of CTs§ in the IED.
†Note:We shall see the countermeasure of through-fault current in the DIFL application
of 1.5CB arrangement in section 2.6.1.
‡Note:Communication capacity is determined by the transmission control function (TC).
Notation “N” is referred to the bandwidth of communication channel. When N=1,
the bandwidth is referred normal (scheme switch [CH*_COM_WIDTH] = Normal]).
When N=3, the bandwidth is referred wide (scheme switch [CH*_COM_WIDTH] =
Wide]). Extended data frame at N=3 is ready for exclusive analog input
quantities, which are only used in WDE element. Data frame at N=1 is ready for
the other analog input quantities, which are not used in the WDE (say,
conventional DIF calculations are only performed with the data transferred at
N=1 frame). For more information about Wide, see Chapter Relay application:
Transmission control function, separately.
§Note:The number of CTs is decided by switch [APPL-CTSELECT]. For more
information, see Chapter Technical description: Settings for residual voltage, CT
polarity, and busbar arrangements.

2.4.1 Stabilization for CT saturation owing to through-fault current


(i) Principle of operation
Even when CTs begins to be saturated due to very large primary currents, the waveform of the
saturated CT secondary current has two periods in each cycle: a non-saturation period and a
saturation period. This phenomenon is utilized to provide very secure operation for external
faults with a large through-fault current.

Figure 2.4-1 shows the block diagram for the CT saturation countermeasure (CTSC).
CTSC has a waveform discriminating element (WDE) and a starting element (SE). The WDE
will operate if a change in the instantaneous value of the differential current is less than a
specified percentage corresponding change in the instantaneous value of the restraining
current. For through-fault currents, during the CT non-saturation period, the differential
current is theoretically zero and hence, this element will operate during this period.

An evolving fault detection element (EVD) is included to monitor the no-change period of
differential current, and will reset the CTSC function in the case of an evolving fault i.e. in

GRL200 (Soft 033 & 037)


- 46 -
6F2S1914 (0.37)

this case a fault that evolves from an external fault to an internal fault.

Current
Input Differential Element
(DIFL) Tripping
& Output

Waveform Discriminating
Element (WDE) 0 t
& &
3 cycles

Starting Element (SE)


CTSC

Starter
Evolving fault detection t 0
element (EVD)
1 cycle
EVD

Figure 2.4-1 Differential element with CT saturation countermeasure

The algorithm used in this element is given by Equations (2.4-1) to (2.4-3):


∆Id < 0.15 × (∆Ip + ∆In) (2.4-1)
∆Id = |𝐼𝑑𝑚 − 𝐼𝑑𝑚−1 | + |𝐼𝑑𝑚−1 − 𝐼𝑑𝑚−2 | (2.4-2)
∆𝐼𝑝 + ∆𝐼𝑛 = |𝐼𝑝𝑚 − 𝐼𝑝𝑚−1 | + |𝐼𝑝𝑚−1 − 𝐼𝑝𝑚−2 |
(2.4-3)
+|𝐼𝑛𝑚 − 𝐼𝑛𝑚−1 | + |𝐼𝑛𝑚−1 − 𝐼𝑛𝑚−2 |

where,
ΔId: Change in the differential current Id
(ΔIp + ΔIn): Change in the restraining current in the positive and negative half cycles
Id: Differential current
Ip: Sum of positive input currents
In: Sum of negative input currents
m, m-1, m-2: Sampling timing

The SE will operate when the sum of the absolute values of the difference between the
instantaneous values of current data from one cycle is greater than a specified percentage of
minDIF-I.
𝐼𝑗𝑚 − 𝐼𝑗(𝑚−1𝑐𝑦𝑐𝑙𝑒) > 0.5 × min DIF– I (2.4-4)
where,
Ij: Current at j
minDIF-I: A minimum value of between settings [DIFL-I1] and [DIFL-I2]

GRL200 (Soft 033 & 037)


- 47 -
6F2S1914 (0.37)

The SE can discriminate a faulted state from the steady state in the power system; it
blocks the WDE operation which otherwise may operate under the steady state.

(ii) CT secondary current waveforms


Figure 2.4-2 shows three current waveforms: two currents at the incoming and outgoing
terminals on CT secondary circuits and a differential current at the outgoing terminal upon
occurrence of an external fault with the CT saturation.

Incoming
terminal current

Outgoing
terminal current

Differential
current

No change period

Figure 2.4-2 Waveforms for CT saturation

From the inception of a fault until the saturation at the outgoing terminal on the CT
secondary circuit, the differential current (Id) is zero; the change of the Id (ΔId) is obtained
from the equation (2.4-2) is zero. Conversely, the change in the restraining current (Ir) given
by the equation (2.4-3) is a sufficiently large positive value. That is, the equation (2.4-1) is
satisfied; the WDE can operate.

The SE detects current changes at the terminals and operates rapidly, when producing
an AND output with the WDE. After this, a certain time delay is inserted to block the operation
of the DIFL element. This is because there is a period during which the equation (2.4-1) is not
satisfied.

If, during an internal fault, there is a period during which the change in the
instantaneous value of the differential current (Id) is small due to CT saturation, the WDE
will not operate because the change in the restraining current (Ir) is also small during the
period. Thus, during the internal fault, the operation of the DIFL element is not blocked falsely.

In the case of an evolving fault from an external fault to an internal fault, the CTSC is
reset by the evolving fault detection element (EVD) if a change in the instantaneous value of
the differential current (Id) is more than a specified value. The DIFL function issues a trip
command with the absence of delay under such faults.

GRL200 (Soft 033 & 037)


- 48 -
6F2S1914 (0.37)

2.4.2 Settings against CT saturation


The operation of the counter measure is available when setting coordination is made for the
three settings, as tabulated in Table 2.4-1.

Table 2.4-1 Setting combination for operating the counter measure for CT saturation
CH*_COM_WIDTH1 APPL-CTSELECT2 DIFL-CTSat Counter measure
Settings Normal Wide 1CT 2CT Non Block Operation
1    Not available
2    Not available
3    Not available
4    Not available
5    Not available
6    Available
7    Not available
8    Available
1Note: For more information, see Chapter Relay application: Transmission control
function.
2Note: For more information, see Chapter Technical description: Settings for residual
voltage, CT polarity, and busbar arrangements.

(i) When Wide is applied in 1CB (Setting No.6)


When the communication width is Wide (N=3) and the DIFL function operates for 1CB
arrangement, the user can use the counter measure when Block is set for scheme switch [DIFL-
CTSat]. Consequently, the counter measure is triggered upon occurrence of the CT saturation;
then issuing a trip signal is blocked.

(ii) When Normal is applied in 1CB (Settings No. 1 and 2)


When Normal (N=1) is used for the 1CB arrangement, the internal DIFL software is not
available for the counter measure for the CT saturation. That is, the operation of the counter
measure is not dependent upon the setting [DIFL-CTSat]. Keep in mind that the user should
arrange that the TFC function† should be operated.

(iii) Counter measure for 1.5CB (Setting No. 8)


If the DIFL function is entailed to operate in 1.5CB arrangement, the relay computation is
only available when the setting [CH*_COM_WIDTH]=Wide (N=3). Analog input quantities,
obtained at center CT and busbar CT, will be transferred by the extended frames in N=3.

GRL200 (Soft 033 & 037)


- 49 -
6F2S1914 (0.37)

†Note:The TFC countermeasure (TFC in DIFL) is discussed separately. See section 2.6.1

GRL200 (Soft 033 & 037)


- 50 -
6F2S1914 (0.37)

2.4.3 Setting
CTsat relating to DIFL (Function ID: 410001)
Range Default
Setting item Unit Contents Note
1A rating 5A rating 1A 5A
DIFL – – – –
DIFL-CTSat Non / Block - CT saturation blocking by DIFL-trip Non

GRL200 (Soft 033 & 037)


- 51 -
6F2S1914 (0.37)

Setting DIFL accounting for CT ratio/rating and fault currents


The user should take coordination about the DIFL settings when the difference exists between
the CT ratios at the local-terminal and at the remote-terminal. Additionally, the user should
consider a minimum fault current for the internal fault and an earth fault current flowing in
a high-impedance for grounding. The user should note that the monitoring values—currents
at the local and the remote-ends (Ia-L, Ia-R1, etc.) and differential currents (Id), which are
shown in Chapter Monitoring function—will not screened and recorded even if matching
procedures below has been performed.

2.5.1 Nature of CT ratios matching


(i) DIFL setting for CT ratios being identical
In the foregoing discussions, the DIFL settings at the local and remote-terminals are made,
which are based on the assumption that the detection thresholds of a fault current are identical
for the both terminals. Figure 2.5-1 exemplifies settings of the DIFL functions having the
assumption; the DIFL sensitivity is taken account of 800 A in terms of the primary side of the
CT. Thereby, at the both terminals, the settings ([DIFL-I1], [DIFL-I2] and others) have to be set
identically.
Busbar-G Busbar-H

CT ratio: DIFL sensitivity required on line GH CT ratio:


2000/1 A = 800A on the primary current 2000/1 A

DIFL DIFL

Sensitivity (primary) Sensitivity (primary)


Setting [DIFL-I1] = Setting [DIFL-I1] =
CT ratio CT ratio
= 800 A = 800 A
2000 / 1 A 2000 / 1 A
= 0.4 A = 0.4 A

Figure 2.5-1 Setting example when ratios being identical

(ii) DIFL setting for CT ratios being not identical


When the CT ratio at the remote-terminal is not identical to the CT ratio at the local-terminal,
the user should make matching ratios between two CTs. Figure 2.5-2 shows the two different
CTs are arranged on the line GH. Thereby, for example, the user should have a setting [DIFL-
I1] at terminal-G and another setting [DIFL-I1] at terminal-H. In like manner, we have different
setting values for [DIFL-I2] and others.

GRL200 (Soft 033 & 037)


- 52 -
6F2S1914 (0.37)

Busbar-G Busbar-H

CT ratio: DIFL sensitivity required on line GH CT ratio:


2000/1 A = 800A on the primary current 4000/1 A

DIFL DIFL

Sensitivity (primary) Sensitivity (primary)


Setting [DIFL-I1] = Setting [DIFL-I1] =
CT ratio CT ratio
= 800 A = 800 A
2000 / 1 A 4000 / 1 A
= 0.4 A = 0.2 A

Figure 2.5-2 Setting example when ratios being not identical

2.5.2 Nature of CT ratings matching


In the previous section (i) and (ii), we have the setting examples in terms of making matching
CT ratios, but we have another example when the CT rating at the remote-terminal is not
identical to the one at the local-terminal.
Busbar-G Busbar-H

CT ratio: DIFL sensitivity required on line GH CT ratio:


2000/1 A = 800A on the primary current 2000/5 A

DIFL operation DIFL operation


at 1A rated current at 5A rated current

Sensitivity (primary) Sensitivity (primary)


Setting [DIFL-I1] = Setting [DIFL-I1] =
CT ratio CT ratio
= 800 A = 800 A
2000 / 1 A 2000 / 5 A
= 0.4 A = 2.0 A

Figure 2.5-3 Setting example when ratings being not identical

In terms of the sensitivity at the CT primary side, setting values for detecting a fault is
the same at both the terminal-G and the terminal-H; thereby the user can introduce the setting
values by dividing the sensitivity to the rated current. Figure 2.5-3 shows the example of
computation; the settings [DIFL-I2] and others are also obtained in the same means.

2.5.3 Nature for fault current setting


(i) Setting DIFL-I1 characteristic
The user should set the [DIFL-I1] by considering the minimum internal fault current to operate;
whereas, expect for a fault condition the user should also consider the maximum erroneous
differential current†. Accordingly, the user should set the [DIFL-I1] using below equation:

If
K×Ic <setting [DIFL-I1]< (2.5-1)
K

where,
K: Setting margin (1.2 to 1.5)

GRL200 (Soft 033 & 037)


- 53 -
6F2S1914 (0.37)

Ic: Internal charging current


If: Minimum internal fault current

†Note:The maximum erroneous differential current is mainly due to an internal


charging current. We shall discuss it in section 2.5.3(v). The user does not need to
consider a condition relating to the charging current flowing. This is because the
function of charging-current compensation can operate.

The user should set the same value for the [DIFL-I1] at all terminals; hence, if CT ratios
of all terminals are not identical, the user should set the [DIFL-I1] respectively so that the DIFL
characteristics of the primary side are coordinated.

(ii) Setting DIFL-I2 characteristic


When setting [DIFL-I2], the user should have three considerations below:
(1) Maximum erroneous current generated during CT saturation upon occurrence of an
external fault. That is, the setting [DIFL-I2] should be set as small as possible; consequently,
the DIFL function does not operate undesirably by the generation of a maximum erroneous
current induced by CT saturation on the primary side when a through current flows due to an
external fault. Thereby, the user should set two times rated current (2×In†) for the [DIFL-I2].

(2) Maximum load current: A sufficient value should be set for the [DIFL-I2] such that it does
not encroach on load current.

(3) Maximum outflow current upon occurrence of an internal fault: This must be just
considered when the DIFL function operates for three-terminal double-circuit lines (‡), lines
with outer loop circuit(‡), or double-circuit lines with one-and-a-half busbar system (1.5CB‡).
That is, for the [DIFL-I2], the user should set a value larger than the possible largest value of
outflow current in case of an internal fault.
An outflow current flowing depends on the configuration or the operation in the power
system. Thus, the user has to check whether it is possible for the fault current to flow out of
the line. If so, the user must consider the influence when setting the [DIFL-I2].

†Note:The rated current (In) is defined while setting the VCT. For more information, see
the Chapter Technical description: Transformer module for AC analog input .
‡Note:When the DIFL function is not used in those arrangements, the user does not
need to consider the outflow current flowing.

(iii) Setting DIFGL-I characteristic


The user should set a value for the [DIFGL-I] by considering an earth fault current flowing in

GRL200 (Soft 033 & 037)


- 54 -
6F2S1914 (0.37)

the high-impedance; the user should set the same value for the [DIFGL-I] at all terminals.
When the terminals do not have an identical CT ratio, the user should set respective values so
that the DIFGL characteristics on the primary side are coordinated.

(iv) Setting DIFL-IDSV monitor


When the differential current monitoring function is used, the setting [DIFL-IDSV] should be
determined using equation (2.5-2) by considering a maximum erroneous differential current
(Ierr) except the occurrence of a fault.

setting[DIFL-I1]
K×Ierr <setting [DIFL-IDSV]< (2.5-2)
1.5 to 2.0

where,
Ierr: Maximum erroneous differential current
K: Setting margin (K= 1.2 to 1.5)

The user does not need to consider the condition relating to the charging current because
the function of charging-current compensation can operate.

The user should set the same value for the setting [DIFL-IDSV] for all terminals. When
the terminals do not have an identical CT ratio, the user should set respective values so that
the Id monitors on the primary side are coordinated.

(v) Setting DIFL-IcC compensation


The user should set an internal charging current (Ic) and a rated power system voltage (V) for
the [DIFL-IcC] and the [DIFL-Vn]; the user can measure the charging current (Ic) using a
protected line being energized and another line being open.

If the power system has different rated voltages (V), the charging current (Ic) measured
should be corrected. Additionally, the user should set the same value for the settings [DIFL-
IcC] at all terminals. When the terminals do not have an identical CT ratio, the user should
set respective values so that the compensations on the primary side are coordinated.

GRL200 (Soft 033 & 037)


- 55 -
6F2S1914 (0.37)

DIFL operations for 1.5CB arrangement


The DIFL function may be used to protect a line that is connected with busbars in a one-and-
a-half breaker arrangement (1.5CB). Therefore, the DIFL function has protection features for
a stub fault and a through-fault-current countermeasure†. Additionally, the user should have
special attentions for the DIFL settings when an outflow current flows on the adjacent line,
provided the parallel lines are configured in the 1.5CB.

†Note: Scheme switch [DIFL-CTSat] Non is also required for the through-fault
counter measure when the DIFL operates in the 1.5CB arrangement. For more
information, see section 2.4.2(iii)

2.6.1 Through-fault-current encountered by DIF (TFC in DIFL and DIFGL)


Figure 2.6-1 shows a one-and-a-half CB arrangement (1.5CB). We assume that a close-in fault
occurs externally. A fault-current (IG) may flow very much on the current transformers (CT1G
and CT2G) at the terminal-G, whereas another fault-current (IH) may flow a little on the other
current transformers (CT1H and CT2H) at the terminal-H. Consequently, the through-fault
current may cause a differential current (Id) erroneously in the DIFL function if the CT1G
characteristic is not identical to the CT2G characteristic.

CT1H
CT1G IH1
IG1
CB
CB

Transmission line GH

CB CB
CT2H IH2
IG2 CT2G

IG IH
= IG1+IG2 = IH1+IH2 Current data
IED_G IED_H
Current data

Communication channels
CB CB
Close-in fault

Terminal-G Terminal-H

Figure 2.6-1 Through-fault-current flowing in an external close-in fault

GRL200 (Soft 033 & 037)


- 56 -
6F2S1914 (0.37)

When the IED_G has a VCT12B†for secondary currents from the CT1G and the CT2G,
in the DIFL function a restraining current (Ir) may be obtained sufficiently by summing the
secondary currents in scalar. In the IED_G the Ir can be generated sufficiently compared with
the Id that may be measured erroneously due to the non-identical CT1 and CT2 characteristics;
thus the DIFL function does not operate. Conversely, in the IED_H, the Ir may not be generated
sufficiently; accordingly, in the IED_H the DIFL function may operate erroneously in response
to the close-in fault.

The through-fault-current countermeasure (TFC) is designed not to issue a trip signal


until the DIFL functions in the IED_G and the IED_H operate simultaneously. The TFC can
operate in the DIFL function when On is set for scheme switch [DIFL-TFC-EN]. The user can
use the TFC in the DIFGL function when scheme switch [DIFGL-TFC-EN] On, as well. Note
that the issuing the trip signal is delayed due to the communication propagation.

†Note:The VCT12B is designed to obtain a pair of three-phase currents. For more


information, see Chapter Technical description: Transformer module for AC
analogue input (VCT).

(i) Operation of TFC countermeasure in DIFL


For the operation of the TFC function, the local DIFL function (i.e., at terminal-G) should
obtain the DIFL operating information at the opposite-terminal (i.e., at terminal-H). Thus, the
DIFL function is required to receive the signal from the opposite-terminal for the TFC function.

The user can use the TFC function when On is set for scheme switch [DIFL-TFC-EN].
During the TFC operation, issuing a trip signal is only carried out when the local DIFL element
and the remote DIFL element operate at the same time. If the TFC function is not required,
the user should set Non for the scheme switch.

Sending DIFL operation signal for the opposite


The signals of the DIFL elements at the both-terminals are exchanged mutually. Figure 2.6-2
shows the DIFL elements; the operated signals (DIFL-A, DIFL-B, and DIFL-C) are sent for
the opposite terminal by the communication.

GRL200 (Soft 033 & 037)


- 57 -
6F2S1914 (0.37)

8000101C20
A DIFL-A
≥1 8100101C21 & &
DIFL#1 B DIFL-B
≥1 8200101C22 & &
C DIFL-C
≥1 & &

DIFL#2 B
C

Figure 2.6-2 Sending DIFL operation signals for remote terminals


†Note: The DIFL#2 element is only available in the [TERM_TOPOLOGY]=2Term-Dual.

Figure 2.6-3 exemplifies the IEEE C37.94 frame format for sending the signals “DIFL-
A,-B, and -C”; the COM5-4, COM5-5, and COM5-6 bits are assigned. The communication
application function (COMM_APPL) function provides transmitting feature. Thus, we should
map the signals “DIFL-A, DIFL-B, and DIFL-C” to PLC connection points “COM5-4_S, COM5-
5_S, COM5-6_SӠ.

a. Sending frames for remote IEDs in IEEE C37.94


N=1 Header I0 Ia V Ib Ic CRC

N=2 Header Ia2 Ib2 Ic2 I0 CRC

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6
b. Connections for sending using PLC function†

From DIFL 8000101C20

DIFL-A 830216EBB3 COM5-4_S


8100101C21
840216EBB4 COM5-5_S
DIFL-B
8200101C22
DIFL-C 850216EBB5 COM5-6_S

DIFL function COMM_APPL function (Function ID: 4A9001)

Figure 2.6-3 Mapping for sending signals using COM5 bits†


†Note:For more information, see Chapter Relay application: Communication application.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].

Reception of DIFL-operation signal from the remote


Similarly, the DIFL function has reception points from the opposite-terminals. Figure

GRL200 (Soft 033 & 037)


- 58 -
6F2S1914 (0.37)

2.6-4 exemplifies the points: “R1.DIFL-A_OP, R1.DIFL-B_OP, R1.DIFL-C_OP” for the Remote-
1_IED, “R2.DIFL-A, R2.DIFL-B, R2.DIFL-C_OP” for the Remote-2_IED. The received signals
are sent to the DIFL main-logic in Figure 2.2-3.

8000001BB6 To DIFL main logic


800000EBB8 R1.DIFL-A_OP 8000001B67
≥1 & & TFC.DIFL-A_OP
8100001BB7 ≥1 ≥1
810000EBB9 R1.DIFL-B_OP 8100001B68
≥1 & &
8200001BB8 ≥1 ≥1 TFC.DIFL-B_OP
820000EBBA R1.DIFL-C_OP 8200001B69
≥1 & &
≥1 ≥1 TFC.DIFL-C_OP

≥1 & &

≥1 & &

≥1 & &

OPEN_R1

EXECUTE-NORM-R1 1

8000001BB9
800000EBBB R2.DIFL-A_OP
≥1
8100001BBA
810000EBBC R2.DIFL-B_OP
≥1
8200001BBB
820000EBBD R2.DIFL-C_OP
≥1

≥1

≥1

≥1

OPEN_R2

EXECUTE-NORM-R2 1

EXECUTE-NORM

EXECUTE-DUAL
Off
DIFL-TFC-EN
On

Figure 2.6-4 Reception logic for TFC operation

Figure 2.6-5 (a) exemplifies the receiving signals from the Remote-1_IED using the
COM3-4, COM3-5, COM3-6 bits; as for the example, we can map the PLC connection points
“COM3-4_R1, COM3-5_R1, COM3-6_R1” with PLC connection points “R1.DIFL-A, R1.DIFL-
B, R1.DIFL-C_OP”. Similarly, Figure 2.6-5 (b) exemplifies that we can map the signals from
the Remote-2_IED with other PLC connection points.

GRL200 (Soft 033 & 037)


- 59 -
6F2S1914 (0.37)

a. Receiving frames from Remote-1 IED in IEEE C37.94


N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6

8310061C85 8000001BB6 To DIFL


COM5-4-R1 800000EBB8 R1.DIFL-A_OP
8410061C86 8100001BB7
COM5-5-R1 810000EBB9 R1.DIFL-B_OP
8200001BB8
8510061C87
COM5-6-R1 820000EBBA R1.DIFL-C_OP

b. Receiving frames from Remote-2 IED in IEEE C37.94


N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6

8310071CAD 8000001BB9 To DIFL

COM5-4-R2 800000EBBB R2.DIFL-A_OP


8100001BBA
8410071CAE
COM5-5-R2 810000EBBC R2.DIFL-B_OP
8200001BBB
8510071CAF
820000EBBD R2.DIFL-C_OP
COM5-6-R2

COMM_APPL function (Function ID: 4A9001) RDIF function

Figure 2.6-5 Mapping for reception signals using COM5 bits†


†Note:For more information, see Chapter Relay application: Communication application.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].

(ii) Operation of TFC countermeasure in DIFLG


The user should set On for scheme switch [DIFGL-TFC-EN] when the TFC countermeasure is
required in the DIFGL function. Note that Off is set in the scheme switch, as default.

Sending DIFGL operation signal for the opposite


The signals of the DIFGL elements should be exchanged mutually for the both terminals.
Figure 2.6-6 shows the DIFGL elements; the operated signal “DIFGL” is set for the opposite
by the communication.
8000001C23
DIFGL
DIFGL#1 ≥1

DIFGL#2

Figure 2.6-6 Sending DIFGL operation signal for remote terminals

GRL200 (Soft 033 & 037)


- 60 -
6F2S1914 (0.37)

Figure 2.6-7 exemplifies the IEEE C37.94 frame format; we should map the SCOM4-SA0
bit for sending the signal “DIFGL”.

a. Sending frames for remote IEDs in IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

SCOM1 SCOM2 SCOM3 SCOM4


SA0 MS0 MS1 MS2
SA1 RA0 RA1 RA2
SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

b. Connections for sending using PLC function

From DIFGL 8000001C23

DIFGL 800211EBB0 SCOM4-SA0_S

DIFGL function COMM_APPL function (Function ID: 4A9001)

N=2 Header Ia2 Ib2 Ic2 I0 CRC

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

Figure 2.6-7 Mapping for sending signal using SCOM bit†


†Note:For more information, see Chapter Relay application: Communication application.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].

Reception of DIFGL-operation signal from the remote


Figure 2.6-8 shows the TFC reception logic; PLC connection point “R1.DIFGL_OP” is used for
the signal receiving from the Remote-1_IED, another PLC connection point “R2.DIFGL_OP”
is used from the Remote-2_IED.

GRL200 (Soft 033 & 037)


- 61 -
6F2S1914 (0.37)

8000001BB5 To DIFGL main logic


800000EBB5 R1.DIFGL_OP 8000001B61
& & TFC.DIFGL_OP
≥1 ≥1

≥1 & &

≥1

OPEN_R1

EXECUTE-NORM-R1 1

810001BB6
810000EBB6 R2.DIFGL _OP
≥1

≥1

OPEN_R2

EXECUTE-NORM-R2 1

EXECUTE-NORM

EXECUTE-DUAL

Off
DIFGL-TFC-EN
On

Figure 2.6-8 Reception logic of TFC operation

The receiving signals are obtained in the logic of Figure 2.3-2.

GRL200 (Soft 033 & 037)


- 62 -
6F2S1914 (0.37)

a. Receiving frames from Remote-1 IED in IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

8010051CE4
SCOM1 SCOM2 SCOM3 SCOM4
SA0 MS0 MS1 MS2 SCOM4-SA0-R1

SA1 RA0 RA1 RA2


SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

To DIFGL
8000001BB5
800000EBB5 R1.DIFGL_OP

b. Receiving frames from Remote-2 IED in IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

8010071C6C
SCOM1 SCOM2 SCOM3 SCOM4
SA0 MS0 MS1 MS2 SCOM4-SA0-R2

SA1 RA0 RA1 RA2


SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

8100001BB6 To DIFGL
810000EBB6 R2.DIFGL_OP

Figure 2.6-9 Mapping for reception signals using SCOM bits†


†Note:For more information, see Chapter Relay application: Communication application.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].

GRL200 (Soft 033 & 037)


- 63 -
6F2S1914 (0.37)

2.6.2 Settings in TFC


DIFL (Function ID: 410001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
DIFL – – – –
DIFL-TFC-EN Off / On - Through fault current countermeasure enable Off

DIFGL (Function ID: 411001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
DIFGL – – – –
DIFGL-TFC-EN Off / On - Through fault current countermeasure enable Off

2.6.3 Data IDs in TFC


 Signal monitoring point
DIFL (Function ID: 41001)
Element ID Name Description
8000001C20 DIFL-A DIFL relay element operated (phase-A)

8100001C21 DIFL-B DIFL relay element operated (phase-B)

8200001C22 DIFL-C DIFL relay element operated (phase-C)

8000001B67 TFC.DIFL-A_OP Remote terminal DIFL relay element operated for TFC (phase-A)

8100001B68 TFC.DIFL-B_OP Remote terminal DIFL relay element operated for TFC (phase-B)

8200001B69 TFC.DIFL-C_OP Remote terminal DIFL relay element operated for TFC (phase-C)

 Connection point in PLC logic


DIFL (Function ID: 41001)
Element ID Name Description
800000EBB8 R1.DIFL-A_OP Receiving signal from Remote Terminal 1 (phase-A)

810000EBB9 R1.DIFL-B_OP Receiving signal from Remote Terminal 1 (phase-B)

820000EBBA R1.DIFL-C_OP Receiving signal from Remote Terminal 1 (phase-C)

800000EBBB R2.DIFL-A_OP Receiving signal from Remote Terminal 2 (phase-A)

810000EBBC R2.DIFL-B_OP Receiving signal from Remote Terminal 2 (phase-B)

820000EBBD R2.DIFL-C_OP Receiving signal from Remote Terminal 2 (phase-C)

 Signal monitoring point


DIFGL (Function ID: 411001)
Element ID Name Description
8000001C23 DIFGL DIFGL relay element operated

8000001B61 TFC.DIFGL_OP Remote terminal DIFGL relay element operated for TFC

 Connection point in PLC logic


DIFGL (Function ID: 411001)
Element ID Name Description
800000EBB5 R1.DIFGL_OP Receiving signal from Remote Terminal 1

810000EBB6 R2.DIFGL_OP Receiving signal from Remote Terminal 2

820000EBB7 R3.DIFGL_OP Receiving signal from Remote Terminal 3

830000EBB8 R4.DIFGL_OP Receiving signal from Remote Terminal 4

GRL200 (Soft 033 & 037)


- 64 -
6F2S1914 (0.37)

2.6.4 Stub protected by DIFL (Stub-DIFL)


Figure 2.6-10 depicts that a one-and-a-half CB arrangement (1.5CBs) with a single
transmission line having a disconnector (DS). A ‘stub zone’ is defined within two CBs and a DS,
which is hatched in the figure.

CT1G
CB(Closed) CB(Closed)

CT1H
Fault
DS
Line GH

CB(Closed) IED_G IED_H CB(Closed)

CT2G Current CT2H


data
Line
Line

CB(Closed) CB(Closed)

Terminal-G Terminal-H

Figure 2.6-10 Fault occurred beyond Stub zone

(i) DIFL operation at terminal-G


As the Figure 2.6-10 is illustrated, the IED_G and the IED_H are used to protect the line GH.
We suppose that a fault occurs beyond the local DS. If a countermeasure is absent from the
DIFL function, a trip signal for CBs may be issued in spite of the line GH being taken out of
service. Thus, the DIFL function is required to have the countermeasure when the fault occurs
beyond the local DS that is open. Issuing no trip signal is made by letting the current data
receiving from the opposite be zero. Note that the DIFL function begins to issue a three-phase
trip signal locally when the countermeasure is enabled.

Figure 2.6-11 depicts the DIFL logic for the stub protection. On should be set for scheme
switch [DIFL-STUB] if the user wishes not to operate the DIFL function when a fault occurs
beyond the local DS; the current data receiving from the opposite terminal is set to be zero
while the DS is open. Incidentally the information signal (DS_OPEN), which starts to be
TRUE(1) when the DS is taken to be open, is provided by the protection common function
(PROT_COMMON), which is discussed separately.

GRL200 (Soft 033 & 037)


- 65 -
6F2S1914 (0.37)

To TRC‡
A ≥1
8000001B67
≥1 &
DIFL#1 DIFL-TRIP_A
B 8100001B68
≥1 DIFL-TRIP_B
C 8200001B69
≥1 DIFL-TRIP_C

A
DIFL#2§
B

From PROT-COMM 8300001B64

DS_OPEN ≥1 & 8100001B66

DIFL-STUB-COND
DIFL-STUB-Test†
On

DIFL-STUB
On

Figure 2.6-11 STUB logic furnished in the local IED


†Note:For testing the stub protection, set On for scheme switch [DIFL-STUB-Test];
consequently, the user can examine the function regardless of the DS condition.
‡Note:The trip circuit (TRC) is discussed separately. See Chapter Relay application: Trip
circuit. Note that the trip signal generated opens the three-poles.
§Note:The DIFL#2 element is only available in the [TERM_TOPOLOGY]=2Term-Dual.

(ii) DIFL operation at terminal-H


On the other hand, the current data received from the opposite terminal is set to be zero when
the opposite terminal does not operate. That is, the IED_H gets to sense the operation of the
terminal G; the operation of the opposite can be sensed by using open terminal detection
function†. Consequently, the DIFL function does not need to have a respace for a fault such
that it is illustrated Figure 2.6-12.

CT1G CT1H
CB(Closed) CB(Closed)

Fault
DS Line GH

CB(Closed) IED_G IED_H CB(Closed)

CT2G Current CT2H


data
Line
Line
CB(Closed) CB(Closed)
Terminal-G Terminal-H
Figure 2.6-12 Fault occurred beyond Stub zone
†Note:On should be set for the [OTD] for the operation. For more information, see the
Chapter Relay application: Communication application.

GRL200 (Soft 033 & 037)


- 66 -
6F2S1914 (0.37)

2.6.5 Settings in Stub


DIFL (Function ID: 410001)
Setting items Range Unit Contents Default Note

DIFL – – – –
DIFL-STUB Off / On - Stub-DIFL protection enable Off

Test tool (Function ID: 410001)


Items Range Unit Contents Default Note

Function test – – – –
DIFL-STUB-TEST Off / On - Forcibly establishing the stub condition Off

GRL200 (Soft 033 & 037)


- 67 -
6F2S1914 (0.37)

2.6.6 Data ID in Stub


 Signal monitoring point
DIFL (Function ID: 41001)
Element ID Name Description
8100001B66 DIFL-STUB-COND DIF-L STUB condition

GRL200 (Soft 033 & 037)


- 68 -
6F2S1914 (0.37)

2.6.7 DIFL applied to double circuit line with a fault (Fault current outflowing)
Figure 2.6-13 shows that a fault occurs in the line GJ; we can see an outflow current induced
by the fault on the line HK. At the station-A, we can find the outflow significantly when the
fault occurs in close proximately to the station-B. The degree of the outflow current depends
on the conditions of the power sources at the station-A and the station-B, but a half of the fault
current flows out to the line HK. Thereby, the user should have an attention for the DIFL
settings when the DIFL function is applied for the double-circuit lines.

IED_A IED_B

CB CB CB CB
Busbar-G Busbar-J

Fault

Line GJ

Busbar-H Busbar-K
CB CB

Line HK

Station-A Station-B

Figure 2.6-13 DIFL applied for double circuit

GRL200 (Soft 033 & 037)


- 69 -
6F2S1914 (0.37)

DIFL applied to three-terminal line (RDIF and Fault current flowing)


The user can trip a CB remotely when the communication failure occurs. The remote CB is
tripped when the function of remote differential trip is available.

On the other hand, the user should have a special attention for the DIFL settings when
the DIFL function is applied for the line having three-terminals (three-terminal line). This is
because the fault current flows out of the line when a fault occurs internally. Additionally, the
user should have another attention for the occurrence of an external fault on the outgoing line,
because the CT saturation may be induced by the external fault.

2.7.1 Remote different trip


Figure 2.7-1 exemplifies the transmission line and the communication structure on the three-
terminal line. Suppose a fault occurs on the three-terminal line; suppose that the
communication from the terminal-H to the terminal-J is broken down. Then the DIFL function
at the terminal-J cannot issue a trip signal (that is, the terminal-J cannot calculate because of
the absent of remote-current data at terminal-H). However, the terminals G and H can
generate a trip signal because that the DIFL functions at both are able to receive the data from
the terminal-J. In Figure 2.7-1, trip signals should be issued at all terminals as for the fault
occurrence; we know that DIFL functions can calculate in spite of the communication failure.
That is, when the terminal-G starts to provide a trip signal to the terminal-J, the CB at the
terminal-J begins to trip. Remote differential trip function (RDIF) is possible for the above
operation when sub-channels† are provided in the communication. Note that the RDIF
function is just possible to issue a trip signal under the following conditions: (1) a trip signal
being received from a remote terminal, (2) a failure of local-DIFL operation being determined,
(3) communication failure being determined, and (4) settings being completed for the RDIF
operation.

The RDIF function is available for the DIFGL function, as well. In other words, the RDIF
function can operate for both the DIFL and DIFGL functions.

GRL200 (Soft 033 & 037)


- 70 -
6F2S1914 (0.37)

Terminal J Terminal G

Fault
Local_relay Remote-1_relay at
at terminal J terminal G
(Local)

Communication failure

Remote-2_relay at
terminal H
Terminal H

Figure 2.7-1 Occurrences of communication failure and fault on the three-terminal line
†Note:The sub-communication channels are provided when the communication between
relays operates in the IEEE C37.94 (N=3) frame. (i.e., set Wide for scheme switch
[CH*-COM_WIDTH]). With regard to the IEEE C37.94, several bits in the frame
(N=3) are defined as auxiliary bits; users can use the auxiliary bits as the sub-
communication channels for the RDIF operation. For more information, see
Chapter Relay application: Transmission control function” and “Communication
application (COMM_APPL)”.

(i) RDIF operation relating to DIFL function


For the RDIF operation the user is required to send the local DIFL output-signals for the
remote terminal by the communication; the user should set the local terminal to receive the
remote DIFL output-signals.

Sending local-DIFL-operation signal


As mentioned earlier, the operation signals of the local DIFL function should be sent to the
remote DIFL functions. Figure 2.7-2 shows PLC monitoring points “DIFL-A,-B, and -C” are
provided for the sending.

8000101C20
A DIFL-A
≥1 8100101C21
DIFL#1 B DIFL-B
≥1 8200101C22
C DIFL-C
≥1

DIFL#2† B
C

Figure 2.7-2 Sending local DIFL operation signals for remote relays
†Note: The DIFL#2 element is only available in the dual mode (setting

GRL200 (Soft 033 & 037)


- 71 -
6F2S1914 (0.37)

[TERM_TOPOLOGY]=2Term-Dual). Therefore, the operation signals in the


DIFL#2 is not generated in the RDIF.

Figure 2.7-3 examples the PLC monitoring signals “DIFL-A,-B, and -C” are sent for the
remote relays using sub-communication channels COM5-4,5,6 bits; communication application
function (COMM_APPL) function provides the features of the sub-communication channel. In
other words, the user should connect the PLC monitoring signals with PLC connection points
“COM5-1,-2,-3_S”†.

a. Sending frames for remote IEDs in IEEE C37.94


N=1 Header I0 Ia V Ib Ic CRC

N=2 Header Ia2 Ib2 Ic2 I0 CRC

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6
b. Connections for sending using PLC function†

From DIFL 8000001C20

DIFL-A 800216EBB0 COM5-1_S


8100001C21
810216EBB1 COM5-2_S
DIFL-B
8200001C22
DIFL-C 820216EBB2 COM5-3_S

DIFL function COMM_APPL function (Function ID: 4A9001)

Figure 2.7-3 Mapping for sending signals using COM5 bits


†Note:For more information, see Chapter Relay application: Communication Application.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].

Reception of remote-DIFL-operation signal


We should receive remote-operation signals at the local RDIF function. Figure 2.7-4 shows the
RDIF reception logic: PLC connection points “R1.DIFL-A,-B, -C_OP” are provided for the
Remote-1_relay, the other PLC connection points “R2.DIFL-A,-B, -C_OP” are provided for the
Remote-2_relay. The signals received from both remote-relays are ORed; then they are ANDed
with the local signals provided the user sets On for scheme switch [DIFL-RDIF-EN].
Consequently, the local DIFL function begins to provide trip signals despite that the local DIFL
function fails to operate.

GRL200 (Soft 033 & 037)


- 72 -
6F2S1914 (0.37)

TDIFL To TRC
8000001BB6 8000001B61 8000001B20
t 0
800000EBB8 R1.DIFL-A_OP ≥1
& ≥1 & & ≥1 DIFL-TRIP-A
8100001BB7 8100001B62
t 0 8100001B21
810000EBB9 R1.DIFL-B_OP ≥1
& ≥1 & & ≥1 DIFL-TRIP-B
8200001BB8 8200001B63 8200001B22
820000EBBA R1.DIFL-C_OP t 0 ≥1
& ≥1 & & ≥1 DIFL-TRIP-C

0.00 to
R1 channel being in sound 100.00s
8300001B64
8000001BB9
800000EBBB R2.DIFL-A_OP
& ≥1 &
8100001BBA &
810000EBBC
&
R2.DIFL-B_OP
8200001BBB
&
&
820000EBBD R2.DIFL-C_OP &

R2 channel being in sound


DIFL-RDIF-EN
On

&
A

Local DIFL logicDIFL Logic B ≥1


1

8200001BB1 ≥1
820000EBB2 DIFL.RDIF_BLOCK
1
8F00001BB2
8F0000EBB4 DIFL_BLOCK

From Fail-safe of DIFL


DIFLFS_OP

800000EBB5 8000001BB3
DIFL-INST_OP

800000EBB5 8000001BB3
DIFL-3PTP
≥1
DIFL-TPMD 3P

Figure 2.7-4 Reception of DIFL operation signals from remote relays

Figure 2.7-5 (a) exemplifies the signals received from the Remote-1_relay in the COM5-
1,-2,-3 bits; the PLC connection points “COM5-1,-2,-3_R1” are required to be connected with
PLC connection points “R1.DIFL-A,-B,-C_OP”. Figure 2.7-5 (b) also exemplifies that the
signals from the Remote-2_relay.

a. Receiving frames from Remote-1 IED in IEEE C37.94


N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6

8010061C82 8000001BB6 To DIFL


COM5-1-R1 800000EBB8 R1.DIFL-A_OP
8110061C83 8100001BB7
COM5-2-R1 810000EBB9 R1.DIFL-B_OP
8200001BB8
8210061C84
COM5-3-R1 820000EBBA R1.DIFL-C_OP

b. Receiving frames from Remote-2 IED in IEEE C37.94


N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6

8010071CAA 8000001BB9 To DIFL

COM5-1-R2 800000EBBB R2.DIFL-A_OP


8100001BBA
8110071CAB
COM5-2-R2 810000EBBC R2.DIFL-B_OP
8200001BBB
8210071CAC
820000EBBD R2.DIFL-C_OP
COM5-3-R2

COMM_APPL function (Function ID: 4A9001) RDIF function

Figure 2.7-5 Mapping for reception signals using COM5 bits†

GRL200 (Soft 033 & 037)


- 73 -
6F2S1914 (0.37)

†Note:For more information, see Chapter Relay application: Communication application.


For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].

(ii) RDIF operation relating to DIFGL function


The RDIF function is also available for the DIFGL function; hence, the operation signals of the
DIFGL function are sent mutually for the opposite terminals.

Sending local-DIFGL-operation signal


An operation signal at the local DIFGL function is required to transferred for the remote.
Figure 2.7-6 shows PLC monitoring point “DIFGL” used at the local DIFGL function; the
SCOM4-SA1 is used in the sub-communication channel.

8000001C23

DIFGL
DIFGL#1 ≥1

DIFGL#2

Figure 2.7-6 Sending local operation signal for remote relay

a. Sending frames for remote IEDs in IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

SCOM1 SCOM2 SCOM3 SCOM4


SA0 MS0 MS1 MS2
SA1 RA0 RA1 RA2
SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

b. Connections for sending using PLC function

From DIFGL 8000001C23

DIFGL 810211EBB1 SCOM4-SA1_S

DIFGL function COMM_APPL function (Function ID: 4A9001)

N=2 Header Ia2 Ib2 Ic2 I0 CRC

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

Figure 2.7-7 Mapping for sending signal using SCOM bit†

GRL200 (Soft 033 & 037)


- 74 -
6F2S1914 (0.37)

†Note:For more information, see Chapter Relay application: Communication application.


For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].

Reception of remote-DIFGL-operation signal


Figure 2.7-8 shows the RDIF reception logic for the DIFLG function: PLC connection point
“R1.DIFGL_OP” is provided for the signal reception from the Remote-1_relay, another PLC
connection point “R2.DIFGL_OP” is provided for the Remote-2_relay. The receipt signals of
both remote-relays are ORed; then they are ANDed with the local DIFGL operation signal
when the user set On for scheme switch [DIFGL-RDIF-EN]. Finally, the RDIF function begins
to issue a trip signal. The SCOM4-SA1 in the sub-communication channel is applied.
TDIFGL To TRC
8000001BB5 800001B62 8000001B23
t 0
800000EBB5 R1.DIFGL_OP ≥1
& ≥1 & & DIFGL-TRIP
0.00 to 300.00s
R1 channel being in sound

8100001BB6
810000EBB6 R2.DIFGL_OP
&

R2 channel being in sound


&
EXECUTE-NORM-R2

DIFGL-RDIF-EN
On

800001C23 &

Local DIFGL logic 1

8100001BB1
810000EBB1 DIFGL.RDIF_BLOCK ≥1
1
8F00001BB2
8F0000EBB2 DIFGL_BLOCK
8000001BB0
800000EBB0 DIFGL-TP_BLOCK

From Fail-safe of DIFGL


DIFGLFS_OP
8000001BB3
800000EBB3 DIFGL-INST_OP

Figure 2.7-8 Reception of remote operation signal in RDIF

GRL200 (Soft 033 & 037)


- 75 -
6F2S1914 (0.37)

a. Receiving frames from Remote-1 IED in IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

SCOM1 SCOM2 SCOM3 SCOM4


8110051CE5
SA0 MS0 MS1 MS2
SA1 RA0 RA1 RA2 SCOM4-SA1-R1

SA2 MS0 MS1 MS2


SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

8000001BB5 To DIFGL
800000EBB5 R1.DIFGL_OP

b. Receiving frames from Remote-2 IED in IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

SCOM1 SCOM2 SCOM3 SCOM4


SA0 MS0 MS1 MS2 8110071C6D

SA1 RA0 RA1 RA2 SCOM4-SA1-R2


SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

8100001BB6 To DIFGL
810000EBB6 R2.DIFGL_OP

Figure 2.7-9 Mapping for reception signals using SCOM bits†


†Note:For more information, see Chapter Relay application: Communication application.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].

GRL200 (Soft 033 & 037)


- 76 -
6F2S1914 (0.37)

2.7.2 Setting
RDIF relating to DIFL (Function ID: 410001)
Range Default
Setting item Unit Content Note
1A rating 5A rating 1A 5A
DIFL – – – –
DIFL-RDIF-EN Off / On - Remote differential protection enable Off

RDIF relating to DIFGL (Function ID: 411001)


Range Default
Setting item Unit Content Note
1A rating 5A rating 1A 5A
DIFGL – – – –
DIFGL-RDIF-EN Off / On - Remote differential protection enable Off

2.7.3 Data ID
 Signal monitoring point
RDIF relating to DIFL (Function ID: 410001)
Element ID Name Description
8000001BB6 R1.DIFL-A_OP Receiving signal from Remote Terminal 1 (phase-A)

8100001BB7 R1.DIFL-B_OP Receiving signal from Remote Terminal 1 (phase-B)

8200001BB8 R1.DIFL-C_OP Receiving signal from Remote Terminal 1 (phase-C)

8000001BB9 R2.DIFL-A_OP Receiving signal from Remote Terminal 2 (phase-A)

8100001BBA R2.DIFL-B_OP Receiving signal from Remote Terminal 2 (phase-B)

8200001BBB R2.DIFL-C_OP Receiving signal from Remote Terminal 2 (phase-C)

8000001BBC R3.DIFL-A_OP Receiving signal from Remote Terminal 3 (phase-A)

8100001BBD R3.DIFL-B_OP Receiving signal from Remote Terminal 3 (phase-B)

8200001BBE R3.DIFL-C_OP Receiving signal from Remote Terminal 3 (phase-C)

8000001BBF R4.DIFL-A_OP Receiving signal from Remote Terminal 4 (phase-A)

8100001BC0 R4.DIFL-B_OP Receiving signal from Remote Terminal 4 (phase-B)

8200001BC1 R4.DIFL-C_OP Receiving signal from Remote Terminal 4 (phase-C)

8000001B6A REMOTE.DIFL-A Remote differential protection (phase-A)

8100001B6B REMOTE.DIFL-B Remote differential protection (phase-B)

8200001B6C REMOTE.DIFL-C Remote differential protection (phase-C)

8200001B6E REMOTE.DIFL-OPT Remote differential protection

8300001B6D REMOTE.DIFL-OR Remote differential protection (3-phase OR)

RDIF relating to DIFGL (Function ID: 411001)


Element ID Name Description
8000001BB5 R1.DIFGL_OP Receiving signal from Remote Terminal 1

8100001BB6 R2.DIFGL_OP Receiving signal from Remote Terminal 2

8200001BB7 R3.DIFGL_OP Receiving signal from Remote Terminal 3

8300001BB8 R4.DIFGL_OP Receiving signal from Remote Terminal 4

8000001B62 REMOTE.DIFGL Remote differential trip

8100001B63 REMOTE.DIFGL-OPT Remote differential trip operation

GRL200 (Soft 033 & 037)


- 77 -
6F2S1914 (0.37)

 Connection point in PLC logic


RDIF relating to DIFL (Function ID: 410001)
Element ID Name Description
800000EBB8 R1.DIFL-A_OP Receiving signal from Remote Terminal 1 (phase-A)

810000EBB9 R1.DIFL-B_OP Receiving signal from Remote Terminal 1 (phase-B)

820000EBBA R1.DIFL-C_OP Receiving signal from Remote Terminal 1 (phase-C)

800000EBBB R2.DIFL-A_OP Receiving signal from Remote Terminal 2 (phase-A)

810000EBBC R2.DIFL-B_OP Receiving signal from Remote Terminal 2 (phase-B)

820000EBBD R2.DIFL-C_OP Receiving signal from Remote Terminal 2 (phase-C)

800000EBBE R3.DIFL-A_OP Receiving signal from Remote Terminal 3 (phase-A)

810000EBBF R3.DIFL-B_OP Receiving signal from Remote Terminal 3 (phase-B)

820000EBC0 R3.DIFL-C_OP Receiving signal from Remote Terminal 3 (phase-C)

800000EBC1 R4.DIFL-A_OP Receiving signal from Remote Terminal 4 (phase-A)

810000EBC2 R4.DIFL-B_OP Receiving signal from Remote Terminal 4 (phase-B)

820000EBC3 R4.DIFL-C_OP Receiving signal from Remote Terminal 4 (phase-C)

RDIF relating to DIFGL (Function ID: 411001)


Element ID Name Description
810000EBB1 DIFGL-RDIF_BLOCK Remote differential detect block

800000EBB5 R1.DIFGL_OP Receiving signal from Remote Terminal 1

810000EBB6 R2.DIFGL_OP Receiving signal from Remote Terminal 2

820000EBB7 R3.DIFGL_OP Receiving signal from Remote Terminal 3

830000EBB8 R4.DIFGL_OP Receiving signal from Remote Terminal 4

GRL200 (Soft 033 & 037)


- 78 -
6F2S1914 (0.37)

2.7.4 Nature of outflowing current in case of internal fault


The user should consider outflows when the DIFL function is applied for the following lines:

(i) Account of DIFL settings for a single line with outer loop
Figure 2.7-10 shows a three-terminal line (lines GJ, JH, and JK) with an outer loop (loop-
circuit HK). Suppose a fault occurs on the line JH. The fault current (IF) flowing at the
terminal-G is divided into IF1 and IF2 at the junction-J, then the IF2 re-enters into the line
JH. This is because the terminal-H is connected by the loop-circuit HK.

Terminal-G Junction-J Terminal-H


IF IF1 IF2

IF2
Fault
Terminal-K
IF2

Figure 2.7-10 Single line with three-terminals with outer loop circuit

(ii) Account of DIFL settings for parallel lines


Figure 2.7-11 shows a double-circuit line with three terminals; the outer loop is generated
when the CB on the line-GJ is open. The fault current IF flowing out at the terminal G divided
into IF1 and IF2 at the junction-J’; then the IF2 re-enter into the line J’H’ through the parallel
line JH. The larger current outflows from the terminal-K when a fault is in close proximate
the terminal-G and the power source behind the terminal-K is weaker. In general, a half of the
fault current leaving from the terminal-G may re-enter in the line-J’H’, provided the terminal-
J
K is very close to the junction-J and the terminal-K does not have a power source itself.

Terminal-G Junction-J Terminal-H


CB (Open) IF2
Line GJ Line JH
IF IF1 IF2
Line G’J’ Line J’H’

Fault
Line J’K’ Line JK

IF2
IF2
Terminal-K

Figure 2.7-11 Double lines with three-terminals

GRL200 (Soft 033 & 037)


- 79 -
Fault
6F2S1914 (0.37)

2.7.5 Nature of CT saturation in case of external fault


IK occurs out of the protected line GH. In the DIFL
Figure 2.7-12 shows that an external fault
function the magnitude of an entering current (IG) is approximately equal to the one of a
Terminal-K
leaving current (IH). Thereby, the error made by the CT saturation can be offset in the DIFL
calculation, if both CTs have the same characteristic.
Terminal-G Terminal-H
IG IH
Terminal-G Terminal-H
IG IH
Fault

Fault

Figure 2.7-12 CT saturation induced by an external fault beyond the protected line

On the other hand, as shown in Figure 2.7-13, if an external fault occurs beyond the
terminal-H, the DIFL function applied for the three-terminal line cannot offset the error. This
is because the same magnitude of the fault current does not flow at respective terminals; the
terminal-H, which is in close proximately the external fault, may experience the outflowing
fault current larger than the terminal-G and the terminal-K. In other words, the DIFL function
cannot offset the error yielded by the CT saturation, unlike in the above case. Thus, the user
has to check a case that CT saturation is particularly produced in when a terminal has an
outflow; the CT saturation must be accommodated utilizing the DIFI2 setting in the DIFL
function.

Terminal-G Junction-J Terminal-H


IG IH

Fault

IK

Terminal-K

Figure 2.7-13 CT saturation induced by an external fault on a three-terminal line

GRL200 (Soft 033 & 037)


- 80 -
6F2S1914 (0.37)

DIFL applied to protect the blind zone


A blind zone can be protected at which the DIFL function operates together with open-
terminal-detection function† that can detect the line being taken out of service using the signal
of a breaker(CB) or a disconnector(DS) opened remotely. Consequently, when the line is taken
out of service, the DIFL function turns current data received from the remote-terminal to zero;
then the DIFL function starts to operate with the absence of remote current data. That is, the
DIFL function begins to operate like a simple over current relay.

†Note:The open-terminal-detection function opiates when the user set On for the scheme
switch [OTD]. For more information, see the chapter Relay application:
Transmission control function.

Figure 2.8-1 illustrates the blind zone, which lies between DSH and CBH. If a fault occurs
within the bind zone, a busbar protection at the busbar-H may issue a trip signal for the CBH
at first. However, if the fault remains after the issue‡, the fault current (IF) enters from the
busbar-G. This phenomenon is an external fault in the DIFL function; we know that the DIFL
function cannot issue a trip signal for the occurrence of the fault. The open-terminal-detection
function is effective for the fault where a blind zone.

‡Note:The fault may be cleared by remote backup protection following a time delay, but
there is a danger of damage being caused to power system plant. The removal of
kinds of this fault is desirable quickly.

The Figure 2.8-1 also illustrates that the CBH and DSH conditions are obtained remotely;
hence, the DIFL function at the terminal-G can operate with only local current data (IG).
Consequently, the fault can be cleared by issuing the trip signal at the terminal-G. This is
because the remote current data (IH) turns to zero as explained above.

The user should note that a CB closing command should be injected to the function of
communication application (COMM_APPL‡) at the remote terminal. This is because that the
DIFL function should be secured from an unwanted operation that can be brought by the CB
closing of manual operation and/or autoreclosing operation. The unwanted operation may be
caused due to that the close timing of the CB auxiliary contact (52a) is delayed relative to the
CB main contact. Therefore, the CB closing command should be injected to the open-terminal-
detection function prior to the CB main contact being closed; the injection points are provided
at PLC connection points “CB1 CLOSE COMMAND” and “CB2 CLOSE COMMAND” in the
COMM_APPL.

GRL200 (Soft 033 & 037)


- 81 -
6F2S1914 (0.37)

Busbar-G Blind Zone Busbar-H


IH (=IF)
IG (=IF) Fault
Line GH

DSH CBH

To a busbar
protection relay
DIFL function at DIFL function
terminal-G at terminal-H (+)

89a

52aA 52aB 52aC

CBDS-A CBDS-A ≥1 Signal ‡


Communication
≥1 “CB1 CLOSE COMMAND”
CBDS-B CBDS-B ≥1

CBDS-C CBDS-C ≥1
IH IH

Terminal-H turns to be “OPEN”


1 Detection of the line GH
being taken out of service

IH turns to zero by constraint when the CBH comes to trip.

IH 1
&

IG
Σ Differential Current (Id) †

Figure 2.8-1 Bind zone protected by the DIFL function


†Note:If any auxiliary contact (89a, 52aA, 52aB, or 52aC) is brought to be open, current
data at the terminal-H (IH) is turn to be zero (0) unconditionally. Accordingly, the
DIFL function at a terminal-G computes the Id computed with the IG only. The
signals ‘CBDS-A, CBDS-B, and CBDS-C’ are able to be transferred when the user
set Wide for scheme switch [CH*_COM_WIDTH]; the user should inject and
retrieve the CBDS-A,-B,-C signals using PLC connection and monitoring points.
To find the PLC points with regard to the CBDS-A,-B,-C signals in the
communication frame, see Chapters Relay application: Communication
application.
‡Note:Signals “CB1 CLOSE COMMAND” and “CB2 CLOSE COMMAND” should be
injected at remote terminals, respectively. For more information, see the Chapter
Relay application: Communication application.

GRL200 (Soft 033 & 037)


- 82 -
6F2S1914 (0.37)

Stub protection with overcurrent relay (STUB-OC)


Figure 2.9-1 depicts that a one-and-a-half breaker (1.5CBs) arrangement with a transmission
line including a disconnector (DS). An area ‘stub zone’ is defined within two CBs and the DS,
which is expressed by hatching in the figure.

For the 1.5CB arrangement, a voltage transformer (VT) is generally installed along the
line GH. Figure 2.9-1 shows that the line GH is taken out of service because of the DS being
open; hence, a distance relay in the IED_G cannot detect a fault when a fault occurs in the
‘stub’ zone. This is because a faulted voltage cannot be measured correctly using the VTG.
Thereby, an overcurrent relay (OC) is provided to protect the ‘stub’ zone and the OC relay
operates speedy upon occurrence of the fault.

CT1G CT1H
CB CB

Fault

DS Line GH

VTG VTH
IED_G IED_H
CB CB
CT2G CT2H
Line Line

CB CB

Terminal-G Terminal-H

Figure 2.9-1 Fault occurred in stub zone


(2.44.1)

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the “G&T position” referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 2.9-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Section feature Relay function/ features
33 37
– STUB-OC OC relay for stub protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 83 -
6F2S1914 (0.37)

2.9.1 Stub-OC characteristic


The characteristic of the stub-OC element is shown as a circle that has a center at the origin,
as shown in Figure 2.9-2. The user can set the threshold value of the stub-OC element using
setting [OCSTUB]. The STUB-OC function can operate when the user set scheme switch
[STUB] On.

0 I

Figure 2.9-2 Characteristic of stub-OC

2.9.2 Scheme logic


Figure 2.9-3 shows the stub-OC logic; the stub-OC function can issue trip signals during the
DS being opened (i.e., logic signal ‘DS_OPEN’ = 1 (TRUE1)).
To TRC
8000001B60
OCSTUB-OR
≥1
8000011C20

A 8000001B20
& & STUBOC-TRIP-A
8100011C21
OCSTUB B
8100001B21
& & STUBOC-TRIP-B
8200011C22
& 8200001B22
C & STUBOC-TRIP-C

From ICD 8300001B23


≥1
ICD-A & ≥1 & STUBOC-TRIP

ICD-B & ≥1
STUBOC-ARC-BLOCK
ICD-C & ≥1
STUBOC-OPT-A
≥1
& STUBOC-OPT-B

STUBOC-OPT-C

Block-3P
STUBOC-2PBlk
Block-PerP

STUBOC-EN On
&
To Recording
800000EBB0 STUBOC_BLOCK 1 STUBOC-TRIP
&
From PROT COMMON

DS_OPEN
≥1
STUB-Test On

Figure 2.9-3 Scheme logic in STUB function

Scheme switch [OCSTUB-2fBlk] is provided in order that the OCSTBU element should
be blocked when second-harmonic frequency components (2f) are detected on the flowing

GRL200 (Soft 033 & 037)


- 84 -
6F2S1914 (0.37)

currents. Either Block-3P or Block-PerP should be set for the scheme switch [OCSTUB-2fBlk]:
the Block-3P is used when the trip signal should be blocked when the 2f is observed in three-
phase; whereas the Block-PerP is used when the trip signal should be blocked when 2f is
observed in a phase. The user can program a block signal using PLC connection point
“STUBOC_BLOCK”.

If an STUB-OC operation test is required in Stub protection area, the user can have a
test by setting [STUB-Test]=On. Consequently, the user can examine the function regardless
of the DS condition in the stub area.

GRL200 (Soft 033 & 037)


- 85 -
6F2S1914 (0.37)

2.9.3 Setting
STUBOC(Function ID: 455001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
STUBOC-EN Off / On - Stub-OC protection enable Off
OCSTUB 0.02 - 0.10 -
A OC relay for stub threshold 1.20 6.00
3.00 15.00
OCSTUB-2fBlk Non / Block-3P /
- OCSTUB operation block by 2f-detection Non
Block-PerP

GRL200 (Soft 033 & 037)


- 86 -
6F2S1914 (0.37)

2.9.4 Data ID
 Signal monitoring point
STUB_OC(Function ID: 455001)
Element ID Name Description
8000001C20 OCSTUB-A STUBOC relay element operated (phase-A)

8100001C21 OCSTUB-B STUBOC relay element operated (phase-B)

8200001C22 OCSTUB-C STUBOC relay element operated (phase-C)

8000001B60 OCSTUB-OR STUBOC relay element operated (3-phases OR)

8200001B65 STUB-R_COND Remote terminal DS condition

8500001B63 STUBOC-ARC-BLOCK Autoreclose block signal by OC protection operation

8000001B61 STUBOC-OPT STUBOC protection operated (3-phases OR)

8300001B23 STUBOC-TRIP STUBOC protection operated

8000001B20 STUBOC-TRIP-A STUBOC protection operated (phase-A)

8100001B21 STUBOC-TRIP-B STUBOC protection operated (phase-B)

8200001B22 STUBOC-TRIP-C STUBOC protection operated (phase-C)

8000001BB0 STUBOC_BLOCK STUBOC protection block command

8000001B64 STUBOC_ENABLE STUBOC is enable

 Connection point in PLC logic


STUB_OC(Function ID: 455001)
Element ID Name Description
800000EBB0 STUBOC_BLOCK STUBOC protection block command

GRL200 (Soft 033 & 037)


- 87 -
6F2S1914 (0.37)

Distance protection (ZS/ZG)


The distance protection function can provide the user the zone information of the fault
occurrence using relay elements. The user can determine the boundaries of respective zones
using reactance-reaches.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have ZS/ZG features. To determine whether the features
are implemented in the IED or not, locate the IED ordering number; and check the order
number at “G&T position” referring to the comparison table below. For more information, see
Appendix: Ordering.
Table 2.10-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
Distance protection(for phase fault) with 6 zones ✓ ✓
ZS Power swing block ✓ ✓
Switch on to fault protection ✓ ✓
Distance protection(for earth fault) with 6 zones ✓ ✓
ZG Power swing block ✓ ✓
Switch on to fault protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 88 -
6F2S1914 (0.37)

2.10.1 Principle of distance measurement


(i) Phase-to-phase fault
The distance protection function used to detect phase-to-phase faults measures the impedance
from the relay to the fault point using delta voltage and current. The positive-sequence
impedance is used to represent the line impedance.

Figure 2.10-1 provides an illustration of the power system for the condition of a phase-to-
phase fault. The impedance from the relay to the fault is the same in phase-B and phase-C,
the self-impedance is Zs and the mutual impedance between phases is Zm. If the voltages and
currents of phase-B and phase-C are Vb, Vc, Ib and Ic and the fault point voltage is VF, then
Vb and Vc are given by the following equations.

𝑉𝑏 = 𝑍𝑠 × 𝐼𝑏 + 𝑍𝑚 × 𝐼𝑐 + 𝑉𝐹 (2.10-1)

𝑉𝑐 = 𝑍𝑠 × 𝐼𝑐 + 𝑍𝑚 × 𝐼𝑏 + 𝑉𝐹 (2.10-2)

From equations (2.10-1) and (2.10-2), the following equation is obtained.

𝑉𝑏 − 𝑉𝑐 = (𝑍𝑠 − 𝑍𝑚) × (𝐼𝑏 − 𝐼𝑐 ) (2.10-3)

where,
Zs: Self impedance
Zm: Mutual impedance

Since the effect of the phase-A current is small, and hence negligible in equation (2.10-3),
there is no need to introduce it in equations (2.10-1) and (2.10-2).

When each phase of the line is symmetric with the other, the positive-sequence and zero-
sequence impedances are Z1 and Z0 according to the method of symmetrical components. Z1
and Z0 are defined by the following equations, using the self-impedance Zs and the mutual
impedance Zm:

𝑍1 = 𝑍𝑠 − 𝑍𝑚 (2.10-4)

𝑍0 = 𝑍𝑠 + 2𝑍𝑚 (2.10-5)

where,
Z1: Positive-sequence impedance
Z0: Zero-sequence impedance

Equation (2.10-3) can be rewritten as follows:

GRL200 (Soft 033 & 037)


- 89 -
6F2S1914 (0.37)

𝑉𝑏 − 𝑉𝑐
𝑍1 = (2.10-6)
𝐼𝑏 − 𝐼𝑐

As shown above, the positive-sequence impedance is used when determining settings for
phase faults.

Va
Ib

Vb
Ic Zm VF

Vc VF
Zs

ZS

Figure 2.10-1 Phase-to-phase fault

(ii) Single-phase-earth fault


Figure 2.10-2 shows the power system in the event of a single-phase-earth fault. It is very
difficult to measure precisely the distance to the fault point for a single-phase-earth fault. This
is because the impedance of the zero-sequence circuit including the earth return is generally
different from the positive-sequence impedance. Therefore, the faulted phase voltage is not
simply proportional to the faulted phase current.

Ia

Va
Ib VaF

Vb
Ic

Vc

ZG

Figure 2.10-2 Single-phase-earth fault


It is necessary to analyze the impedance seen by the relay in the event of a single-phase-
earth fault according to the method of symmetrical components. Figure 2.10-3 shows an
equivalent circuit for a single-phase-earth fault based on the method of symmetrical
components. If we define the positive-sequence, negative-sequence and zero-sequence voltages
as being V1F, V2F and V0F, then the voltage at the relaying point of each symmetrical circuit
will be given by the following equations based upon the assumption that the positive-sequence

GRL200 (Soft 033 & 037)


- 90 -
6F2S1914 (0.37)

impedance and negative-sequence impedance are the same and that the influences of the fault
resistance are ignored.

𝑉1 = 𝑍1 × 𝐼1 + 𝑉1 𝐹 (2.10-7)

𝑉2 = 𝑍1 × 𝐼2 + 𝑉2 𝐹 (2.10-8)

𝑉0 = 𝑍0 × 𝐼0 + 𝑍0 𝑚 × 𝐼0 𝑚 + 𝑉0 𝐹 (2.10-9)

where,
V1: Relay point positive-sequence voltage
V2: Relay point negative-sequence voltage
V0: Relay point zero-sequence voltage
V1F: Fault point positive-sequence voltage
V2F: Fault point negative-sequence voltage
V0F: Fault point zero-sequence voltage
I1: Relay point positive-sequence current
I2: Relay point negative-sequence current
I0: Relay point zero-sequence current
I0m: Adjacent line zero-sequence current
Z1: Fault point - relay point positive-sequence impedance
Z0: Fault point - relay point zero-sequence impedance
Z0m: Adjacent line zero-sequence mutual impedance

Considering the faulted phase voltage VaF at the point of fault is,

𝑉𝑎 𝐹 = 𝑉1 𝐹 + 𝑉2 𝐹 + 𝑉0 𝐹 = 0 (2.10-10)

Phase-A voltage Va at the relay is calculated from the following equation:

𝑍0 − 𝑍1 𝑍𝑚0
𝑉𝑎 = 𝑉1 + 𝑉2 + 𝑉0 = 𝑍1 (𝐼𝑎 + × 𝐼0 + × 𝐼0𝑚 ) (2.10-11)
𝑍1 𝑍1

Where, Ia is the current of phase-A at the relay and is defined in the following equation
by the symmetrical component of the current:

𝐼𝑎 = 𝐼1 + 𝐼2 + 𝐼0 (2.10-12)

Here, defining the current synthesized using the phase-A current at the relay as Ia', and

(𝑍0 − 𝑍1 )
Ia′ = 𝐼𝑎 + × 𝐼0 + 𝑍0 𝑚/𝑍1 × 𝐼0 𝑚 (2.10-13)
𝑍1

Then equation (2.10-11) can be re-written in the following form:

GRL200 (Soft 033 & 037)


- 91 -
6F2S1914 (0.37)

𝑉𝑎 = 𝑍1 × 𝐼𝑎 ′ (2.10-14)

That is, the positive-sequence impedance Z1 up to the fault point can be obtained from
the simple ratio of voltage Va to compensated current Ia' according to equation (2.10-14).

Obtaining the compensated current according to equation (2.10-13) is called "zero-


sequence compensation." Note that in this implementation of zero-sequence compensation, the
compensation coefficient
𝑍0 − 𝑍1
𝑍1
and
𝑍0𝑚
𝑍1
are not real numbers, but complex numbers. The distance protection function has a
configuration that allows this compensation coefficient to be set as a complex number and
setting the coefficient correctly makes it possible to measure exactly the distance to the fault
point.

In equations (2.10-7) to (2.10-9), the fault resistance is ignored. Since the measurement
of the distance up to the fault point, based on equation (2.10-14) is carried out using the
reactance component, in principle there is no influence on the voltage component due to the
fault resistance. However, under real operating conditions, distance measurement errors are
introduced because of the fault resistance combined with the power flow or the current flowing
into the fault point from the remote terminal opposite to the relay location.

Z1
I1

V1
V1F
Positive-sequence circuit

Z2
I2

V2
V2F
Negative-sequence circuit

Z0
I0

V0
Zero-sequence circuit V0F

ZG

Figure 2.10-3 Equivalent circuit of single-phase earth fault

GRL200 (Soft 033 & 037)


- 92 -
6F2S1914 (0.37)

2.10.2 Equations in distance protection function


(i) Element equations for Mho characteristic
The element of the Mho characteristic is achieved by comparing the angle between S1 and S2
phases, which are obtained in Equations (2.10-15) and (2.10-16) . If the angle between the S1
and the S2 is greater than 90°, a fault is being detected in the element in the Mho
characteristic; then a trip signal will be issued.
S1 = V − I × Zs (2.10-15)
S2=Vp (2.10-16)
where
V = fault voltage
I = fault current
Zs = reach setting
Vp = polarizing voltage
X Mho element

S1=V–IZs

S2=Vp

IZs

o R

Figure 2.10-4 Element in Mho characteristic

Figure 2.10-4 shows the Mho characteristic obtained by comparing phases, provided the
fault voltage (V) and the polarizing voltage (Vp) are in phase. In Figure 2.10-4 the Mho
characteristic is obtained by dividing the voltage (V) by the current (I).

The Mho characterize is provided to detect for both the distance relays in phase-to-phase
(ZS) and in ground-fault (ZG); a self-polarization in accompany with cross-polarization (i.e., a
dual polarization) is employed for the both characteristic. The polarizing voltage (Vp) is
expressed using Equations (2.10-17) and (2.10-18).
To the ZS element (for a fault in phase-bc):
Vpbc =√3×(Va − V0 )∠-90° + Vbc (2.10-17)
To the ZG element (for an earth fault in phase-a):
Vpa =√3×(Va − V0 ) + Vbc ∠90° (2.10-18)

GRL200 (Soft 033 & 037)


- 93 -
6F2S1914 (0.37)

where,
Va = Voltage in phase-a
V0 = Voltage in zero-sequence
Vbc = Voltage in phase-ab

The dual-polarization can improve the directional security when applied to heavily loaded
lines or weak infeed terminals. If a close-in fault in three-phase occurs, the polarizing voltage
is memorized in the relay (i.e., memory action). That is, voltage information (Va and Vbc) just
before the occurrence of the fault is memorized; the memory action will be held for two-cycles
after the fault.
X

S2=Vp

Mho element

R IZs
o

Offset Mho element

Figure 2.10-5 Offset action in Mho characters for a three-phases fault

Figure 2.10-5 shows that an offset Mho characteristic is applied when the relay detects a
fault in three-phase. That is, the ZS element having the memory action is able to issue a trip
signal with a time delay; the ZS element is able to issue an instantaneous tripping for the
close-in fault in three-phase.

Note that the memory action is not performed in the ZG element; the offset action is only
available for the ZS elements.

(ii) Element equations for offset Mho characteristic


The element in offset Mho characteristic is obtained by comparing the angle between the S1
and S2 phases, which are denoted in Equation (2.10-19) and (2.10-20). If the angle is greater
than 90°, the element in the offset Mho characteristic detects a fault.
S1 = V − I × Zs (2.10-19)
S2=V+IZSO (2.10-20)
where
V = fault voltage

GRL200 (Soft 033 & 037)


- 94 -
6F2S1914 (0.37)

I = fault current
Zs = reach setting
Vso = offset reach setting

Offset Mho element


S1=V–IZs

IZs

V
o S2=Vp
R

–IZso

S2=V+IZso
V

Figure 2.10-6 Offset Mho characteristic on impedance plane


Figure 2.10-6 illustrates a voltage diagram in the offset Mho characteristic; the angle
comparison between the S1 and S2 phases are performed using Equations (2.10-19) and
(2.10-20). The offset Mho characteristic is obtained by dividing the voltage of Figure 2.10-6 by
current I.

(iii) Element equations for reactance characteristic


It is possible that the Mho characteristic operate with reactance characteristic; a level line or
a gradual descent line toward the R-axis is provided for the reactance characteristic. The
gradual descent one is set using variables Xs, θ1, and θ2, as shown in Figure 2.10-7.

X Reactance element X
Mho element

Xs Xs knee
θ2

θ1
o R o R

a. Reactance element with a level line b. Reactance element with a gradual descent line

Figure 2.10-7 Reactance characteristics

The composite characteristic is available only when the load current flows from the local-
end to the remote-end. If the load current flows oppositely from the remote-end to the local-

GRL200 (Soft 033 & 037)


- 95 -
6F2S1914 (0.37)

end, the reactance characteristic will be a horizontal line, which is parallel to the R-axis. The
horizontal characteristic is taken when no load current flowing; it is also taken when the θ1
angle is set to zero (0). The level element in the reactance characteristic is shown using
Equation (2.10-21); the element in the gradual descent characteristic is shown in Equation
(2.10-22):
X ≤ XS (2.10-21)
R ≤ X S × tan(90° − 𝜃2) + ( X S − X) tan(90° − 𝜃1) (2.10-22)
where,
R = resistance component of measured impedance
X = reactance component of measured impedance
Xs = reach setting

The R and X components are calculated using an integration approximation algorithm.


Using the reactance characteristic, the relay is able to have high measurement accuracy even
in the presence of frequency fluctuations in the power system and distorted transient
waveforms containing low-frequency spectral components.

The values of the θ1 and θ2 are obtained using Equations (2.10-23) and (2.10-24):

θ2 < tan−1 (X⁄R ) (2.10-23)


F

I
θ1 < tan−1 ( Lmax⁄(I ) (2.10-24)
Lmax +IFmin )

where,
X = reactance component
RF = fault resistance
ILmax = maximum load current
IFmin = minimum fault current

To commence the element of the distance relay (Z) in accompany with the reactance
characteristic, a fault recognition is executed every one-sixth of a power-cycle (system
frequency), using Equations (2.10-21) and (2.10-22). The Z relay shall operate if two fault
recognitions are obtained consecutively in a power-cycle, if the fault occurs within 90% of the
reach setting (Zs). If the fault is beyond the 90% of the Zs, the Z relay shall operate when four
fault are recognized consecutively in a power-cycle. Six-times-fault-recognitions in a power
cycle can prevent an erroneous operation in the transient phenomena; that is, the means of
the six-times-fault-recognitions to avoid overreach results when a fault occurs close to the
boundary of two zones (e.g., a boundary of the Z1 and Z2 relay elements).

GRL200 (Soft 033 & 037)


- 96 -
6F2S1914 (0.37)

(iv) Element equations for blinder characteristic


The characteristics about the forward and the reverse blinders are provided as shown in Figure
2.10-8. The operating area (Figure 2.10-8.a) is enclosed with forward blinders (BFR and BFL
lines); the BFL line is placed as the mirror image of the BFR line. Similarly, the operating area
(Figure 2.10-8.b) is enclosed with the reverse blinders (BRR and BRL lines).
X X
R Rs o R
BFL blinder BFR blinder
X θ

BRR

θ X
o R BRR blinder BRL blinder
Rs R
BRL
a. Forward blinder b. Reverse blinder

Figure 2.10-8 Blinder elements

The characteristics about the BFR and BRR lines are obtained by Equations (2.10-25)
and Equation (2.10-26), respectively:
X ≥ (R − R s ) tan 𝜃 (2.10-25)
X ≤ (R + R s ) tan 𝜃 (2.10-26)
where,
R = resistance component of measured impedance
X = reactance component of measured impedance
Rs = reach setting

If the minimum load impedance (ZLmin) is predictable, we can take the Rs setting for
the worst case such that the load angle is of 30° and the margin is of 80% in case of θ=75°;
Equation (2.10-27) can be applied to obtain the resistive setting for the blinder element:
sin 30°
Rs < 0.8 × ZLmin × (cos 30° − ) (2.10-27)
tan 75°

(v) Element equations for directional characteristic


Figure 2.10-9 illustrates that a directional element used for the element in Quadrilateral
characteristic. The characteristic of the directional element is obtained using Equation
(2.10-28); the polarizing voltage (Vp) is the same one as employed in the Mho characteristic.
I × Vp cos(𝜃 − 𝜑) ≥ 0 (2.10-28)
where,
I = fault current
Vp = polarizing voltage

GRL200 (Soft 033 & 037)


- 97 -
6F2S1914 (0.37)

𝜑 = lagging angle of I to Vp
θ = directional angle setting
X
Quad element

lagging
I R
o θ
Directional element

Figure 2.10-9 Directional element

For the element for the fault in phase-bc, the polarizing voltage (Vpbc) is given using
Equation (2.10-29):
𝑉𝑝𝑏𝑐 = √3 × (𝑉𝑎 − 𝑉0 )∠ − 90° + 𝑉𝑏𝑐 (2.10-29)

For the element for the fault in phase-a, the polarizing voltage (Vpa) is given using
Equation (2.10-30):
𝑉𝑝𝑎 = √3 × (𝑉𝑎 − 𝑉0 ) + 𝑉𝑏𝑐 ∠90° (2.10-30)
where,
V0 = voltage in zero-sequence
Va = voltage in phase-A
Vbc = voltage in phase-bc

In Equation (2.10-29), the Vpbc voltage is subject to the memory action if the close-in
fault occurs in three-phases; that is, the values of the Va and Vbc voltages are set from the pre-
fault voltages. The memory is retained for two cycles after the fault occurs. Note that the
polarizing voltage (Vpa) in Equation (2.10-30) is not subject to the memory action.

If a close-in fault in three-phases occurs, the Quad element can be enhanced for an offset
Quad element, as shown in Figure 2.10-10. Similar to issuing the instantaneous trip signal for
the close-in three-phase fault, this enables the Quad element to issue a trip signal with a
delayed time together using the memory action.

GRL200 (Soft 033 & 037)


- 98 -
6F2S1914 (0.37)

Offset directional element


θ
ZB

o R

Quad element in reverse

Figure 2.10-10 Offset element in Quad characteristic for close-in fault

The element of the offset directional characteristic is obtained using Equation (2.10-31):
X + R tan 𝜃 ≤ 𝑍𝐵 (2.10-31)
where,
X = reactance component of measured impedance
R = resistance component of measured impedance
θ = directional angle setting (= directional element angle setting in (2.10-28))
ZB = offset reach setting (fixed to be 1.5Ω in 5A rating and 7.5Ω in 1A rating)

GRL200 (Soft 033 & 037)


- 99 -
6F2S1914 (0.37)

2.10.3 Element characteristic in distance relay


The distance protection function has six measurement zones; it is possible to identify the fault
point using these zones. This function has ZS elements to determine phase-to-phase faults and
ZG elements to determine single-phase-earth faults.

This distance protection function can be selected to have either a Mho characteristic
(Mho) or a Quadrilateral characteristic (Quad) for both ZS and ZG. Each of the measuring
zones in this function has a directional characteristic.

Note: The Asterisk (*) in the setting is used to show the zone number in ZS/ZG (either
"1", "1X", "2", "3", "4", or "5"). The numbering and application of ZS/ZG are
described later.

(i) Common characteristic of ZS and ZG


The distance protection function has a Mho characteristic (Mho) element and a Quadrilateral
characteristic (Quad) element and either the Mho characteristic or the Quad characteristic is
selected by the scheme switches [ZS-Chara] and [ZG-Chara].

Note: The complete elements and their characteristics, ZS and ZG are based on the
scheme switches [ZS-Chara] and [ZG-Chara].

Mho characteristic
(i)-1-1 Conventional Mho characteristic
Figure 2.10-11(a) and (b) show Z*S and Z*G with the Mho characteristic. The Z*S can
be set using the settings [Z*S-Mho.Reach] and [Z*S-Mho.Angle].

The blinder positions (left line and right line) are defined by the resistance and the
angle in the Figure 2.10-11; they are set using settings [Z*S-R.Reach] and [Z*S-
R.Angle]. The blinders are aligned symmetrically with the X-coordinate. Scheme
switches [Z*S-MhoR.EN] should be set On to enable the blinders.

GRL200 (Soft 033 & 037)


- 100 -
6F2S1914 (0.37)

a. Z1S Mho element b. Z1G MHO element


X X
Z1S-Mho.Reach Z1G-Mho.Reach

Z1S-Mho.Angle Z1G-Mho.Angle
Z1S-R.Angle Z1S-R.Angle Z1G-R.Angle Z1G-R.Angle

R R

Z1S-R.Reach (in the left) Z1S-R.Reach (in the right) Z1G-R.Reach (in the left) Z1G-R.Reach (in the right)

Figure 2.10-11 Z1S Mho element (Zone1 Mho element with Blinders)

(i)-1-2 Mho with reactance characteristic


Figure 2.10-12 (a) and (b) show Z1S MHO element and Z1G MHO element set with
reactance X.

The ZS with the MHO reactance characteristic should be set using the setting [Z*S-
X.Reach], when the user set On for the scheme switch [Z*S-MhoX.EN]. Similarly, ZG
should be set using the setting [Z*G-X.Reach], when On set for the [Z*G-MhoX.EN].

The ‘knee’ function is configured by using the settings [ZSF-X.GrAngle1] and [ZSF-
X.GrAngle2]. When On-Adapt is set for the scheme switch [ZS-X.GrAngleEN], the
‘knee’ function operates when power flow is detected.

For the Mho characteristic, a composition component (Z-X) is provided. As shown in


Figure 2.10-12 (a), if Z1S is set with reactance components (X), other components can
be set using impedance components (Z).

A directional reactance element ‘DX’ (left line crossing the originate) can be set by the
settings [Z*S-DX.Angle] when On set for the [Z*S-MhoDX.EN]. Similarly, ZG should
be set using the setting [Z*G-DX.Angle] when On set for the [Z*G-MhoDX.EN].

GRL200 (Soft 033 & 037)


- 101 -
6F2S1914 (0.37)

a. Z1S MHO with reactance X b. Z1G MHO with reactance X

Z1S-DX.Angle
X Z1G-DX.Angle X

Z1S-X.Reach Z1G-X.Reach

ZSF-X.GrAngle1 ZGF-X.GrAngle1

Z1S-R.Angle ZSF-X.GrAngle2 Z1S-R.Angle Z1G-R.Angle ZGF-X.GrAngle2


Z1G-R.Angle
R R
Z1S-Mho.angle Z1G-Mho.angle

Z1S-R.Reach (in the left) Z1S-R.Reach (in the right) Z1G-R.Reach (in the left) Z1G-R.Reach (in the right)

Figure 2.10-12 Zone1 MHO element set with reactance X in forward direction

Quad characteristic
Figure 2.10-13(a) and (b) show the Z*S and the Z*G used in the Quad characteristics. For
example, the reach of Z*S (top line) is defined by reactance X and the reach value should be
set for the scheme switch [Z*S-X.Reach]. A resistive element (left line) and a directional
element (bottom line) can be set by the settings [Z*S-DX.Angle] and [Z*S-DR.Angle]
respectively. The resistive elements (right and left lines) can be configured by the settings [Z*S-
R.Reach] and [Z*S-R.Angle]; the blinder (left line) is used to cut the area of the Quad
characteristic by applying settings [Z*S-R.Reach] and [Z*S-R.Angle].

The ‘knee’ function is configured by the settings [ZSF-X.GrAngle1] and [ZSF-X.GrAngle2].


When On-Adapt is set for the scheme switch [ZS-X.GrAngleEN], the ‘knee’ function operates
when power flow is detected, similar to the MHO element.

a. Z1S Quadrilateral a. Z1G Quadrilateral


X X

Z1S-X.Reach Z1G-X.Reach

ZSF-X.GrAngle1 ZGF-X.GrAngle1

Z1S-R.Angle ZSF-X.GrAngle2 Z1S-R.Angle Z1G-R.Angle ZGF-X.GrAngle2 Z1G-R.Angle

R R

Z1S-DR.Angle Z1G-DR.Angle
Z1S-DX.Angle Z1G-DX.Angle
Z1S-R.Reach (in the left) Z1S-R.Reach (in the right) Z1G-R.Reach (in the left) Z1G-R.Reach (in the right)

Figure 2.10-13 Zone1 Quadrilateral element in forward direction

GRL200 (Soft 033 & 037)


- 102 -
6F2S1914 (0.37)

Number of zones
The distance protection for phase-to-phase faults (ZS) includes six measuring zones and these
are termed Z1S, Z1XS, Z2S, Z3S, Z4S and Z5S. The distance protection for single-phase-earth
faults (ZG) also includes six measuring zones that are similarly termed Z1G, Z1XG, Z2G, Z3G,
Z4G and Z5G.
Z1XS–Z5S Mho with impedance Z
X

Z3S-Mho.Reach
Z3S

Z2S

Z1XS

Z5S-R.Reach Z1S

Z3S-R.Angle
R
Z5S-R.Angle
Z5S-Mho.Angle

Z4S
Z3S-R.Reach

Z5S

Figure 2.10-14 Composition feature for Mho characteristic


Selection of Forward, Reverse, or Non-directional for the respective zones
The selection of the element direction is provided with the setting [Z*S-Dir]. For instance, if
Forward is set, then Z*S is set in forward direction, as shown in Figure 2.10-11 to Figure
2.10-13. If Reverse is set, then Z*S is set in reverse direction, as shown in Figure 2.10-15 to
Figure 2.10-17. Z*S can be set non-directional by setting NonDir, as shown in Figure 2.10-18
and Figure 2.10-19. The other elements can be set in a similar manner.

Elements in the reverse direction of ZG are not drawn in Figure 2.10-15 to Figure 2.10-17,
but they are similar to the ZS elements.

GRL200 (Soft 033 & 037)


- 103 -
6F2S1914 (0.37)

Z1S-DX.Angle
X
Z1S-R.Reach Z1S-R.Reach

Z1S-Mho.angle
R

Z1S-R.Angle Z1S-R.Angle

Z1S-DR.Angle

Z1S-Mho.Reach

Figure 2.10-15 Z1S MHO element in reverse direction

Z1S-Mho.angle Z1S-R.Reach
Z1S-R.Reach
R
Z1S-R.Angle Z1S-R.Angle

Z1S-X.Reach

Z1S-DX.Angle

Figure 2.10-16 Z1S MHO element set with reactance X in reverse direction

Z1S-DR.Angle X

Z1S-R.Reach Z1S-R.Reach
R
Z1S-R.Angle Z1S-R.Angle

Z1S-DX.Angle

Z1S-X.Reach

Figure 2.10-17 Z1S Quadrilateral element in reverse direction

GRL200 (Soft 033 & 037)


- 104 -
6F2S1914 (0.37)

Z1S-Mho.Reach

Z1S-Mho.angle
Z1S-R.Angle

Z1S-R.Reach R

Figure 2.10-18 Z1S MHO element non-directional†


†Note:The tilted line, crossing the originate, instructs the function of the non-directional
element.

X
Z1S-X.Reach

Z1S-R.Angle
R
Z1S-R.Reach

Figure 2.10-19 Z1S Quad element non-directional

Function and classification of 6 zones


Table 2.10-2 provides a summary of the zones and characteristics for each element. Z1XS and
Z1XG can be set to cover ≤ 100% of the protected line in their respective zones of protection in
order to provide extended coverage beyond the settings of Z1S and Z1G. On the other hand,
Z5S and Z5G, can be set to protect beyond 100% of the protected line. The element
characteristic used for Z1XS and Z5S is similar and so is the element characteristic for Z1XG
and Z5G.

Note that the elements Z2S to Z5S and the Z2G to Z5G can have either the Mho or the
Quad characteristic element, but these elements do not have the ‘knee’ function.

GRL200 (Soft 033 & 037)


- 105 -
6F2S1914 (0.37)

Table 2.10-2 Zone element, characteristics and directional

Zone

Element

Purpose

Directional

Characteristic

Set the ‘Knee’


Forward

Reverse

Non-directional

Quadrilateral

MHO
Set Z

Set X
1 Z1S Protection for Zone 1 (Relay Yes Yes Yes Yes Yes Yes Yes
/Z1G reach ≤ 80 % )
1X Z1XS Protection for Zone 1 extension Yes Yes Yes Yes Yes Yes Yes
Z1XG (Relay reach ≤ 100 %)
2 Z2S Back up for Z1S, Z1X Yes Yes Yes Yes Yes Yes No
/Z2G
3 Z3S Back up for Z1S, Z1X Yes Yes Yes Yes Yes Yes No
/Z3G
/
4 Z4S Back up for Z1S, Z1X Yes Yes Yes Yes Yes Yes No
/Z4G
5 Z5S Protection for over Zone 1 Yes Yes Yes Yes Yes Yes Yes
/Z5G extension (Relay reach > 100 %)

Charging current compensation


When this distance protection function is applied to underground cables or long-distance
overhead lines, the effect of charging current is to be considered; it appears as a distance
measurement error to the fault. In order to suppress the effect and maintain the high-accuracy
distance-measurement capability, the charging current compensation function should be used.
Compensation is recommended if the minimum fault current is three times less than the
charging current.

The charging current compensation function has common scheme switches for both ZS
and ZG. The On setting is selected for the scheme switch [Z-IcC.EN] along with a setting value
for the setting [Z-IcC].

GRL200 (Soft 033 & 037)


- 106 -
6F2S1914 (0.37)

(ii) Special characteristic in ZS


Overreach countermeasure
If we consider ZS, when a phase-to-phase fault occurs, the setting of the ZS reactance element
tends to be less than the fault impedance. For example, Figure 2.10-20 shows the relationship
between the phase-to-phase impedances in a three-phase system when a phase-to-phase BC
fault arises across Bus H. Here, ZS is not required to operate because the fault lies outside of
the protection zone. However, ZS may operate because the impedance of the phase-to-phase
impedance AB is located inside the setting of the reactance element (X1). This means that the
phase-to-phase protection element AB, which is not connected with the faulted phase, may
operate although the other elements do not operate.
jX

Zca
Zbc
X1
Zab
o R

60°
60°
Operation zone of X1
S
element

Bus G Bus H
F
O Ia

Zbc

ZS

ZL1

F: Fault location
S: Infinite bus system
O: Location of Protective relay
ZL1: Fault impedance seen from S
Zbc: Fault impedance of phase-to-phase bc in the fault

Figure 2.10-20 Impedance seen from ZS on occurrence of phase-to-phase BC fault

The previous phenomenon is referred to as overreaching of the leading phase in distance


protection terminology. A countermeasure is necessary to deal with this phenomenon. The
countermeasure is to utilize a Zmin element as shown in section 2.10.7. It is generally
recognised as being the result of a phase-to-phase fault impedance which is smaller than the
normal impedance.In the above instance, the element Zmin-BC of the faulted phase would
operate but the Zmin-AB and Zmin-CA elements of the healthy phases would not operate, so
that the unnecessary overreaching operation of ZS-AB can be blocked.

GRL200 (Soft 033 & 037)


- 107 -
6F2S1914 (0.37)

Offset characteristics in ZS
Some elements in ZS are used for the detection of faults in the reverse direction and these
elements can have an offset characteristic, which assures the detection of a close-up three-
phase fault. Offset characteristic1 is provided in Z1S, Z1XS, and Z5S; the offset characteristic
instructs to start the memory action at which the voltage drops to zero upon the occurrence of
a fault. That is, for dropping to zero voltage, the memory action services an important role for
deciding whether the fault is located in the forward or in the reverse direction based upon the
relay location. In the offset characteristic, its offset value is fixed at 1.5Ω for 5A rating2,
whereas it is fixed at 7.5Ω for 1A rating2. Figure 2.10-21 exemplifies the action of the Mho
offset characteristic of Z1S in the reverse direction; Figure 2.10-22 illustrates that the action
of the Quad characteristic is applied. Note that the offset characteristic in the reverse direction
is not provided in Z2S and Z3S.
1Note: As a rule, Z1S, Z1XS, and Z5S are utilized for a close-up three-phase fault. For
example, the Z1S element can be instructed to operate in the reverse direction; the
operation of the Z1S element should be covered the origin (i.e., voltage=0), as
shown in Figure 2.10-21. Owing to the memory action for the close-up fault, the
Z1S element is able to detect a fault even if the memory does not hold voltage data
(say, in the memory the voltage data is set to zero for the close-up three-phase
fault). The operation of the memory action has been available for the last three-
cycles at the occurrence of the close-up fault; the memory action has not been
available for the last four-cycles. The same memory action is also provided in the
Z1XS and the Z5S.
2Note: Either 1A or 5A rating is fixed to operate on a transfer modules (VCT). For more
information about the VCT, see Chapter Technical Description: Transformer
module for AC analog input.

Static MHO characteristic


X

Z1S-Mho.Angle
Z1S-R.Reach
Z1S-R.Angle
R

Offset MHO characteristic


during close-up fault

Z1S-X.Reach

Figure 2.10-21 Z1S Mho element during close up fault (Offset action)

GRL200 (Soft 033 & 037)


- 108 -
6F2S1914 (0.37)

X Offset Quadrilateral characteristic during close-up fault


ZS-DirRθ(R abscissa)
Static Quadrilateral characteristic

Z1S-R
R
ZS-Rθ

Z1S

ZS-DirXθ(X ordinate)

Figure 2.10-22 Z1S Quad element close-up fault (Offset action)

Operation of ZS for earth and multi-phase-faults


ZS can operate for any of the following faults: a phase-to-phase fault, phase-to-phase ground
fault, and a fault evolving into a multi-phase fault. To strengthen dependability in detecting
the multi-phase fault, it is possible to add the judgement of fault phase identifier. The fault
phase identifier consists of ZG elements. The judgement condition will be added when On is
set for setting [Z*S-MSDET]†. In order not to add the judgement in ZS, the user can set Off for
the setting.

†Note:It is recommended to set [Z*S-MSDET]=On in the instantaneous main protection


element only. Since operating condition of Z*S elements is increased by setting
On, it is desirable to set Off in the backup protection easier to operate.

(iii) Special characteristic in ZG


Earth fault compensation (Zero sequence current compensation)
On the detection of an earth fault, ZG requires a compensation function that corrects
measuring errors caused by the earth return of zero-sequence current. By using the
compensation function, the positive-sequence impedance to the fault point can be determined
precisely by the reactance element in the faulted phase. For a double-circuit line, the zero-
sequence current from the adjacent line is introduced to compensate for influences from zero-
sequence mutual coupling. Considering a case where the angle of the positive-sequence
impedance and the zero-sequence impedance differs, the distance protection function carries
out zero-sequence current compensation vectorially. We can see this case commonly in cable
circuits.

GRL200 (Soft 033 & 037)


- 109 -
6F2S1914 (0.37)

In ZG, this function provides the compensation factors for all elements and these factors
are defined with settings. For example, for Z1G, the settings [Z1G-Krs], [Z1G-Kxs], [Z1G-Krm],
[Z1G-Kxm] are provided. Where, “s” refers to the protected line; the resistance “r”; the
reactance “x” reflect its property and “m” refers to a mutual circuit line for parallel line
applications.
Table 2.10-3 ZG compensation factors in lines
Element Settings for Protected line Settings for Parallel line
Z1G [Z1G-Krs], [Z1G-Kxs] [Z1G-Krm], [Z1G-Kxm]
Z1XG [Z1XG-Krs], [Z1XG-Kxs] [Z1XG-Krm], [Z1XG-Kxm]
Z2G [Z2G-Krs], [Z2G-Kxs] [Z2G-Krm], [Z2G-Kxm]
Z3G [Z3G-Krs], [Z3G-Kxs] [Z3G-Krm], [Z3G-Kxm]
Z4G [Z4G-Krs], [Z4G-Kxs] [Z4G-Krm], [Z4G-Kxm]
Z5G [Z5G-Krs], [Z5G-Kxs] [Z5G-Krm], [Z5G-Kxm]

Measuring the positive-sequence impedance to the fault point is necessary. Therefore, for
a single circuit line, the current input to the earth fault-measuring element is compensated by
the residual current (3I0) of the protected line.

On the other hand, for a double circuit line, the current input is compensated by the
residual current (3I0) of the protected line and residual current (3I0’) of the adjacent line.

Generally, the following equation is used to compensate the zero-sequence voltage drop,
in this example for the case of phase “a”.
Va = (Ia − 𝐼0 ) × Z1 + 𝐼0 × 𝑍0 + 𝐼0𝑚 × 𝑍0𝑚 (2.10-32)
where,
Va: Phase “a” voltage
Ia: Phase “a” current
I0: Zero-sequence current of the protected line
I0m: Zero-sequence current of the adjacent line
Z1: Positive-sequence impedance (Z1 = R1 + jX1)
Z0: Zero-sequence impedance (Z0 = R0 + jX0)
Zom: Zero-sequence mutual impedance (Zom = Rom + jXom)

Equation (2.10-32) can be presented as follows:

GRL200 (Soft 033 & 037)


- 110 -
6F2S1914 (0.37)

Va = (R 1 + j X1 )Ia + (R 0 R 1 ) + j(X 0  X 1 )I 0

+ (R 𝑜𝑚 + j X 𝑜𝑚 ) I𝑜𝑚
𝑅0 − 𝑅1 𝑅0 𝑚
=R 1 (I 𝑎 + I 0 + I 𝑜𝑚 ) + 𝑗𝑋1 (𝐼𝑎 (2.10-33)
𝑅1 𝑅1
𝑋0 − 𝑋1 𝑋𝑚
+ I 0 + I 𝑜𝑚 )
𝑋1 𝑋1
In the relay, the voltage is compensated independently for resistance and reactance
components as shown in equation (2.10-33) instead of equation (2.10-32).
𝐾𝑟𝑠
−1
VaR + jVaX = R1( IaR + 100  3I0R
3
𝐾𝑟𝑚
+ 100  3𝐼𝑜𝑚𝑅 ) X1( IaX
3
𝐾𝑥𝑠 𝐾𝑥𝑚
−1
+ 100  3I0X + 100  3I
0mX )
3 3
(2.10-34)
𝐾𝑟𝑠
−1
+ jR1( IaX + 100  3I0X
3
𝐾𝑟𝑚
+ 100  3I0mX ) + X1( IaR
3
𝐾𝑥𝑠 𝐾𝑥𝑚
−1
+ 100  3I0R + 100  3I0mR )
3 3
where,
Kxs: compensation factor (Kxs = X0/X1 × 100)
Krs: compensation factor (Krs = R0/R1 × 100)
Kxm: compensation factor (Kxm = Xom/X1 × 100)
Krm: compensation factor (Krm = Rom/R1 × 100)
X: imaginary part of the measured impedance
R: real part of the measured impedance
VaX: imaginary part of phase “a” voltage
VaR: real part of phase “a” voltage
IaX: imaginary part of phase “a” current
IaR: real part of phase “a” current
I0X: imaginary part of zero-sequence current of the protected line
I0R: real part of zero-sequence current of the protected line
IomX: imaginary part of zero-sequence current of the adjacent line
IomR: real part of zero-sequence current of the adjacent line

GRL200 (Soft 033 & 037)


- 111 -
6F2S1914 (0.37)

I 0’

Zom
I 1, I 2, I 0 Fault

Va

ZG
Z1, Z2, Z0

Figure 2.10-23 Earth fault compensation

The Zero-sequence Current Compensation function (ZPCC) controls the zero-sequence


compensation required as a consequence of the influence of the adjacent line in parallel line
applications.

When an earth fault occurs on the protected line, the ZPCC function will operate, in this
case parallel line compensation is performed to prevent under-reach caused by the mutual
zero-sequence current of the adjacent line.

When an earth fault occurs on the adjacent line, the ZPCC function does not operate,
compensation for the adjacent line is not performed to prevent overreach. The operating
condition of the ZPCC function is as follows:
3𝐼0
≥ 0.8 (2.10-35)
3𝐼0𝑚

Operation of ZG for earth-faults and multi-phase faults


ZG uses an EFL function for the detection of earth faults; hence, ZG will operate when the EFL
function operates. However, the operation of Z*G can be set to be either dependent or
independent of the operation of EFL; that is, On is set for the scheme switch [Z*G-EFL] for the
Z*G operation with EFL and Off is set for the scheme switch [Z*G-EFL] for the Z*G operation
without EFL.

There is a possibility that ZG even operates against a multi-phase fault. Because of the
effect of zero-phase compensation adjustment calculation, ZG elements tends to calculate
overreach (underreach) against a multi-phase fault when the direction of power flow is positive
(negative), it is recommended to make just ZS operate against the multi-phase fault.

ZG elements can be blocked by an operation of a multi-phase (2-phase or 3-phase) earth


fault detection by elements of ZG*COV as shown in scheme logics of the distance protection
element described later.

GRL200 (Soft 033 & 037)


- 112 -
6F2S1914 (0.37)

In order for ZG not to operate against the multi-phase fault, it is possible for the user to
set Block for setting [Z*G-MPFBlk]†. If this operation condition shall not be added in ZG
operation, it is possible to set Non for the setting [Z*G-MPFBlk].

†Note:It is recommended to set [Z*G-MPFBlk]=Block for main protection elements, such


as Zone 1, which need to operate instantaneously. Since operating condition for
Z*G elements is restricted by setting Block, it is desirable to set Non for backup
protection elements, such as a forward looking element and a reverse looking
element, which can operate with a pick-up delay timer to cover remote end;
accordingly, protection measurement and operating condition could be less
restricted.

With regard to the leading-phase-block function, the leading phase ZG element could
operate in the event of a multi-phase fault.

The leading phase ZG element can be blocked by an operation of a ZG*COV element as


shown in scheme logics of the distance protection element described later. For example, when
an A-phase (or B-phase or C-phase) ZG1COV is picked up, an operation of C-phase (or A-phase
or B-phase) Z1G output can be blocked. (Note that the ZG*COV functions as a fault detection
as well as for fault phase detection as described for the multi-phase fault detection logic.) The
similar logics are prepared for other zones as well.

Thus, it is possible to set Non for scheme switch [Z*G-LPBlk] in order not to block the
operation of the leading phase of Z*G.

However, Block can be set for this scheme switch in order to block the operation of Z*G.

GRL200 (Soft 033 & 037)


- 113 -
6F2S1914 (0.37)

2.10.4 Common application for ZS and ZG


Applications in ZS and ZG are divided into common features and special features. Each feature
secures this distance protection function.

(i) Power swing block


Operation of power swing block (PSB)
Power swings occur when the output voltages of generators located at different points in the
power system slip relative to one another because of system instabilities. This may be caused
by sudden changes in load magnitude or direction, or by power system faults and their
subsequent clearance. During the course of such a power swing, the impedance locus seen by
the distance protection relay may move (relatively slowly) from the load area into the operating
region of the distance protection. Actually, the relay may see this phenomenon as a three-phase
fault condition and may issue a trip signal if no countermeasure is applied. The majority of
power swings are transient and the power system recovers after a short period. Since a trip
signal from the relay is undesirable in such cases, the function of power swing blocking (PSB)
is provided enabling the operation of the distance protection to be blocked during the power
swing. Figure 2.10-24 illustrates a typical impedance locus as seen by the relay during the
transient power swing.

X
Distance protection zone (Mho char.)

Impedance locus
during transient
power swing

R
Load Area

Figure 2.10-24 Impedance locus during transient power swing

As shown in Figure 2.10-25 (a), for ZS, power swing blocking elements (PSBSOUT and
PSBSIN) are formed as shown in the shaded area. As shown in Figure 2.10-25 (b), for ZG, the
PSBGOUT and PSBGIN elements are provided with the similar characteristic and feature.
Both PSB (PSBS and PSBG) functions do not operate when an earth fault overcurrent (EFL)
element or a negative-sequence phase overcurrent (OCN-PS) element is operating. Note that
the EFL and OCN-PS thresholds are defined with VCT rated value multiplied by 0.2 (i.e.,
secondary rated 1A×0.2 or 5A×0.2).

GRL200 (Soft 033 & 037)


- 114 -
6F2S1914 (0.37)

The PSB operation is permitted when phase-overcurrent elements (OCCR) are operating.
The thresholds of OCCR elements are defined with VCT rated current multiplied by 0.08 (i.e.,
secondary rated 1A×0.08 or 5A×0.08).

X X
PSBSOUT PSBGOUT
PSBSZ PSBGZ
PSBSIN Z2S PSBGIN Z2G

PSBGZ

PSBGZ
PSBSZ

PSBSZ

0 R 0 R

Z3S Z3G
PSBSZ PSBGZ

a. PSBSIN and PSBSOUT in ZS b. PSBGIN and PSBGOUT in ZG

Figure 2.10-25 Example of PSB element characteristic

The setting of PSBSIN adjusts automatically so that the PSBS operates properly in
accordance with the operation of ZS. The shaded area formed by the rectangle, which is
tangential with the elements (circles) in both directions of ZS, determines the size of PSBSIN.
For example, in Figure 2.10-25, Z2S is the most distant measuring element in the forward
direction; Z3S is the most distant measuring element in reverse direction; the top line of the
PSBSIN function is similar to the tangent of Z2S, the bottom line of the PSBSIN function is
similar to the tangent of Z3S. The outer element PSBSOUT encloses the inner element
PSBSIN with a width which can be set using the setting [PSBSZ].

Figure 2.10-25 illustrates the ZS elements are separately placed in the forward and
reverse directions. If all ZS elements are placed in one direction (in other words, elements are
not placed in the forward and the reverse), the inner and outer are constructed with the ZS
element and the other symmetrical element (see Figure 2.10-26). The symmetrical element is
as large as the largest ZS element; the symmetrical one will be placed by pivoting the largest
one around the origin.

GRL200 (Soft 033 & 037)


- 115 -
6F2S1914 (0.37)

X
PSBSOUT
ZGF-X.GrAngle2
Z1G-R.Angle Z1G-R.Angle PSBSZ
R
PSBSIN
Largest ZS

Z1G-DR.Angle

PSBSZ

PSBSZ
Z1G-DX.Angle
Z1G-R.Reach (in the left) Z1G-R.Reach (in the right)
0 R

Pivoted ZS
Z3S

PSBSZ

PSB constructed with ZS and pivoted ZS

Figure 2.10-26 PSB characteristic made with only forward ZSs

Z2S is similar to that of the Mho characteristic, as shown


The case of the Quad characteristic
in Figure 2.10-27.
X X
PSBSOUT PSBGOUT
PSBSZ PSBGZ
PSBSIN PSBGIN
Z2S Z2G
PSBGZ

PSBGZ
PSBSZ

PSBSZ

0 R 0 R

Z3S Z3G

PSBSZ PSBGZ

a. PSBSIN and PSBSOUT in ZS b. PSBGIN and PSBGOUT in ZG

Figure 2.10-27 Example of PSB element in Quad characteristic

Figure 2.10-28 shows the PSBS-out and PSBS-in logic. During a power swing, the
impedance viewed from the PSB elements passes through the area between the PSBSOUT and
PSBSIN in a certain time. In the event of a system fault, the impedance passes through this
area instantaneously. A power swing, therefore, can be detected in the time that the locus of

GRL200 (Soft 033 & 037)


- 116 -
6F2S1914 (0.37)

the power swing remains within the shaded area of the rectangle between the outer and inner
elements. A delayed pick-up timer, [TPSBS] is initiated when the locus passes through the
PSBSOUT element and continues until the PSBSIN element operates in order to measure the
time duration for the locus to pass through the shaded area. If this time duration is longer
than the set value of the delayed pick-up timer [TPSBS], the PSBS element will operate to
block the operation of the distance protection trip signal.

Other than the power swing condition, measured impedance locus may stay in the PSBS
zone for a certain time which is much longer than the PSBS detection timer [TPSBS]. In this
case, the PSBS output can be reset forcibly when the locus remains in the PSBS zone for
another timer setting [TPSBSFR] and scheme switch [PSBSFR] is set to On.

If PSB operation is not required when a fault is occurring during the power swing event,
set On for the scheme switch [PSBSRS]; accordingly, PSB operation cannot work when the
fault is detected by the operation of EFL or OCN-PS element (i.e., ZS/ZG element is able to
work even if the PSB operates). It is also possible to remove the PSB operation by utilizing an
external reset signal, which can be injected at PLC connection point ‘PSBS F.RESET’.

Another delayed timer resets the trip block signal that is generated by the PSBS element
when the power swing is detected after the PSBSOUT operation is removed; 500ms is the value
set for the delayed pick-up timer.

Similarly, a PSB element is also provided for ZG and its operation is termed as PSBG
(See Figure 2.10-29). The setting of PSBGs is similar to those of PSBSs.
8400081B65
AB To VTF and CTF
PSBS & ≥1 1 &
BC 8500081B66 & 8100081B60
OUT S
&
PSBS-CVTF-BLK
CA 8600081B67
R
&

8000081B62
AB
&
≥1 TPSBS
PSBS BC 8100081B63 8000081B61
t 0
& 1 S
IN
From CA 8200081B64 PSBS DET
DISTANCE COMMON
& 0.02 to 0.100s R

8000001C20
OCCR-A
&
8100001C21
OCCR-B
&
8200001C22
OCCR-C
& 1 &
8300001C27 t 0 ≥1
EFL
≥1
OCN-PS
0.5s
1
8000081BB0
800008EBB0 PSBS_BLOCK

≥1
&
PSBSRS
& TPSBSFR
On t 0
PSBSFR
On
0.0 to 10.00s
8100081BB1 ≥1
810008EBB1 PSBS F.RESET

Figure 2.10-28 PSBS logic

GRL200 (Soft 033 & 037)


- 117 -
6F2S1914 (0.37)

8400081B63 To VTF and CTF


A &
& 1
8500081B64 ≥1 & 8100081B6F
PSBG B S
& PSBG-CVTF-BLK
OUT 8600081B65
C R
&
8000081B66
A
& TPSBG
8100081B67 ≥1 t 0 8000081B70
PSBG B S
& 1
IN 8200081B68 PSBG DET
From C R
DISTANCE COMMON & 0.02 to 0.100s
8000001C20
OCCR-A
&
8100001C21
OCCR-B
&
8200001C22
OCCR-C
& 1 &
8300001C27 t 0 ≥1
EFL ≥1
OCN-PS 1 0.5s
8000081BB0
800008EBB0 PSBG_BLOCK

≥1
& TPSBGFR
PSBGRS t 0
On &
PSBGFR
0.0 to 10.00s
On
8100081BB1 ≥1
810008EBB1 PSBG F.RESET

Figure 2.10-29 PSBG logic

Setting for blocking operation of Distance protection


Scheme switches [Z*S-PSBBlk] and [Z*G-PSBBlk] are provided to block the operation of the
respective Z*S and Z*G elements. Generally, it is desirable to block the operation of the
respective ZS elements and ZG elements during a power swing. Thus, Block is set for the
respective scheme switches [Z*S-PSBBlk] and [Z*G-PSBBlk].

However, when it is required to continue the operation of respective ZS and ZG elements


during a power swing, Non is set for respective scheme switches.

(ii) Load encroachment


The load encroachment element is used to improve security when heavy load current flows in
a line. When the impedance remains within the hatched area as shown in Figure 2.10-30, a
signal that reflects the operation of the load encroachment element is yielded; respective ZS
elements are blocked to operate by blocking signals, which can be issued at which Block is set
for the scheme switches [Z*S-LEBlk].

As shown in Figure 2.10-30(a), for ZS the minimum load resistance R is defined by the
setting of scheme switches [LESR] and [LESL]. Setting of the maximum load angles across the
R ordinate is performed using scheme switches [LESR-Angle] and [LESL-Angle].

For ZG, when Block is set for the scheme switches [Z*G-LEBlk], similar settings and
scheme switches are available: settings [LEGR], [LEGL], [LEGR-Angle], and [LEGL-Angle],

GRL200 (Soft 033 & 037)


- 118 -
6F2S1914 (0.37)

are shown in Figure 2.10-30(b).

X X

LESL-Angle LEGL-Angle
LESR-Angle LEGR-Angle

R R

LESR LEGR
LESL LEGL

a. LESL and LESR for ZS b. LEGL and LEGR for ZG

Figure 2.10-30 Load encroachment characteristic

The load encroachment element can operate for the command protection functions (ZCS
and ZCG elements) when the user sets Block for the scheme switches [ZCS-LEBlk] and [ZCG-
LEBlk]. We shall see the ZCS and ZCG functions later.

(iii) Fail safe function


Both ZS and ZG provide overcurrent elements, which can be used for fail-safe operation.

For example, an overcurrent element is provided in Z*S, termed Z*S-OCFS-EN. The


option of Z*S-OCFS-EN operation can be included when On is set for the scheme switch [Z*S-
OCFS-EN], the overcurrent element is subject to the setting of [OCF*S] in Z*S. The setting
value is chosen between 0.02–5.00 A (1 A rating) or 0.10–25.00 A (5 A rating).

Similarly, ZG is also provided with overcurrent elements for fail-safe operation. If On is


set for the scheme switch [Z*G-OCFS-EN], the overcurrent element is subject to the setting of
[OCF*G] in Z*G.

(iv) Definite time delay operation


In accordance with the location of the fault, the timing of trip signals can be adjusted with
delayed timers. For instance, a delay timer in Z*S tripping can be set by applying a time delay
setting using [TZ*S] whose value can be chosen between 0.00–100.00s. Similarly, for ZG
delayed timers can be applied using [TZ*G].

GRL200 (Soft 033 & 037)


- 119 -
6F2S1914 (0.37)

For Z1S and Z1G tripping, either instantaneous tripping or time delayed tripping can be
selected; hence, the scheme switch [Z1CNT-INSTOP] is provided for the selection of the trip
mode, which is described later.

(v) Autoreclose initiation blocking


If ZS and ZG detect a fault, the output signals of ZS and ZG are generated in trip circuit (TRC)
and the CB is tripped. If autoreclose (ARC) is not required following the operation of Z*S, Block
can be set using the scheme switch [Z*S-ARCBlk]. Conversely, if ARC is required following the
operation of Z*S, then Non can be set using the scheme switch [Z*S-ARCBlk]. Similarly, for ZG
scheme the following switch is provided: [Z*G-ARCBlk].

The function for blocking the initiation of autoreclose is also represented in Figure
2.10-43 and Figure 2.10-51 of section 2.10.7.

Note: The operation and setting of the ARC are discussed separately. For more
information on ARC, see Chapter Relay application: Autoreclose and voltage
check.

(vi) Zone 1 control


Both Z1S and Z1G offer a variety of trip modes in order to satisfy the diverse nature of the
many schemes and applications in which the relay is required to operate. The following scheme
switches provide the flexibility required to meet the wide range of applications. Figure 2.10-31
shows the scheme logic for Zone 1 control. When signal “Z1CNT_MPROT” is active, user can
control Z1S and Z1G as follows:
 A trip signal is blocked if On is set for the scheme switch [Z1CNT-TPBlk].
 A three-phase trip is initiated by Z1G on the occurrence of a fault if On is set for the
scheme switch [Z1CNT-3PTP].
 Autoreclose is blocked if On is set for the scheme switch [Z1CNT-ARCBlk].
 Both Z1S and Z1G generate an instantaneous operation signal if On is set for the
scheme switch [Z1CNT-INSTOP].

GRL200 (Soft 033 & 037)


- 120 -
6F2S1914 (0.37)

8000001BB0 Z1CNT_MPROT

8000001B62

Z1CNT-TPBLK
&
Z1CNT-TPBlk On

8100001B63

Z1CNT-3PTP
&
Z1CNT-3PTP On

8200001B64

Z1CNT-ARCBLK
&
Z1CNT-ARCBlk On

8300001B65

1 Z1CNT-INSTOP
&
Z1CNT-INSTOP On

Figure 2.10-31 Scheme logic of Zone1 operation control

2.10.5 Command protection feature


The means of telecommunication makes possible for protective relays to exchange its operation
information. If the protective relays locate at each end of the protected line with the
telecommunication, the distance protection functions can determine whether the fault is
internal or external to the protected line.

As for the ZS, we provide the user the function of distance protection telecommunicated
as command protection (ZCSF and ZCSR). As for the ZG, we also provide the user the ZCSF
and ZCSR for the command protection. The user should take case that, discussed here are the
elements and characteristic of the command protection only; we provide the operation
instruction of this function separately. (See Chapter Relay application: Distance carrier
command protection.)

For the operation, the user should set On for the scheme switches [ZCS-EN] and [ZCG-
EN], respectively.

(i) ZS command protection


Figure 2.10-32 and Figure 2.10-33 show the ZS characteristic of the command protection. You
can find the Mho or the Quad characteristic; and you can select its characteristic when you
place the set of Mho or Quad for the scheme switch [ZS-Chara].

As shown in Figure 2.10-32, if you require placing an element in the Mho characteristic
in forward direction (ZCSF), you should place the reach setting of the ZCSF for settings [ZCSF-
Mho.Reach] and [ZCSF-Mho.Angle] both. On the other hand, when you need to prescribe the
reach setting of the ZCSF in reactance X, you should place its setting value for setting [ZCSF-

GRL200 (Soft 033 & 037)


- 121 -
6F2S1914 (0.37)

X.Reach] with a set of On being placed for scheme switch [ZCSF-MhoX.EN]. You can also
prescribe resistive elements as shown on right and left side with settings [ZCSF-R.Reach] and
[ZCSF-R.Angle]; the resistive elements are applicable when you place a set of On for scheme
switch [ZCSF-MhoR.EN].

On the other hand, as shown in Figure 2.10-33, when you require placing an element in
the Quad characteristic in forward direction, you should place the reach of the ZCSF with
setting [ZCSF-X.Reach]. You can also place resistive elements, right side and left side in the
figure with setting [ZCSF-R.Reach] and [ZCSF-R.Angle]. The resistive elements are
symmetrical and the right side is placed across the origin from the left side. Additionally, you
can place a directional element—as shown with a bottom line—with setting [ZCSF-DR.Angle].

The same holds true for an element in the Mho characteristic in reverse direction (ZCSR) and
you can place the ZCSR with settings and scheme switches:
for the Mho, [ZCSR-Mho.Reach], [ZCSR-Mho.Angle], [ZCSR-X.Reach] [ZCSR-
R.Reach], [ZCSR-R.Angle], [ZCSR-MhoX.EN] and [ZCSR-MhoR.EN]
and
for the Quad, [ZCSR-X.Reach], [ZCSR-R.Reach], [ZCSRF-R.Angle], and [ZCSR-
DR.Angle].

You should place a set of Block for setting [ZCSF-PSBBlk] because the operation of the ZCSF
should stop when the power swing is detected. You should place a set of Non for the setting
when you require the ZCSF operation keeping in the power swing detection.

You also should place a set of a set of Block for setting [ZCSR-VTFBlk] because the operation
of the ZCSR should stop when the VTF is detected. Conversely, you should place a set of Non
for the setting were you to require the ZCSR operation keeping in the VTF detection.

Make sure that the ZCSF does not supply the offset feature while the ZCSR supplies the offset
feature. The settings for the offset element are fixed at 7.5 Ω for 1 A rating or 1.5 Ω for 5 A
rating. The fix offset makes the ZCSR operate constantly even when the three-phase fault
appears close in the reverse side. However, the ZCSF blocks its operation in the three-phase
fault because the ZCSR runs together with the ZCSF. As a result, the command protection can
avoid improper operations.

GRL200 (Soft 033 & 037)


- 122 -
6F2S1914 (0.37)

X
ZCSF-Mho.Angle
ZCSF-Mho.Reach
ZCSF-R.Angle ZCSF-R.Angle

ZCSF-X.Reach

ZCSR-R.Reach ZCSR-R.Reach
R
ZCSR-R.Angle ZCSF-R.Reach ZCSF-R.Reach

ZCSR-R.Angle

ZCSR-X.Reach

ZCSR-Mho.Reach

ZCSB-Mho.Angle

Figure 2.10-32 ZCSF and ZCSR in Mho characteristic

ZCSF-DX.Angle X

ZCSF-X.Reach

ZCSF-R.Angle ZCSF-R.Angle

ZCSR-DR.Angle

ZCSF-R.Reach
ZCSR-R.Reach
R
ZCSR-R.Angle ZCSF-R.Reach

ZCSF-DR.Angle

ZCSR-X.Reach
ZCSR-R.Angle

Figure 2.10-33 ZCSF and ZCSR in Quad characteristic

(ii) ZG command protection


With respect to the ZCGF and the ZCGR both, these characteristics and functions are similar
to the ZCSF and the ZCSR. However, you should make sure that the ZCGR does not have an

GRL200 (Soft 033 & 037)


- 123 -
6F2S1914 (0.37)

offset action in revers zone as shown in Figure 2.10-34 and Figure 2.10-35. That is, only static
characteristics are drawn in the characteristic figures.

As for the cancellation of the ZCGF and the ZCGR, provided are settings [ZCGF-PSBBlk] and
[ZCGR-VTFBlk].

ZCGF-Mho.Angle

ZCGF-Mho.Reach
ZCGF-R.Angle ZCGF-R.Angle

ZCGF-X.Reach

ZCGR-R.Reach ZCGR-R.Reach
R
ZCGR-R.Angle ZCGF-R.Reach ZCGF-R.Reach

ZCGR-R.Angle

ZCGR-X.Reach

ZCGR-Mho.Reach

ZCGR-Mho.Angle

Figure 2.10-34 ZCGF and ZCGR in Mho characteristic

GRL200 (Soft 033 & 037)


- 124 -
6F2S1914 (0.37)

X
ZCGF-DX.Angle

ZCGF-X.Reach

ZCGF-R.Angle

ZCGB-DR.Angle
ZCGF-R.Reach
ZCGR-R.Reach
R
ZCGR-R.Angle
ZCGF-DR.Angle

ZCGR-DX.Angle

ZCGR-X.Reach

Figure 2.10-35 ZCGF and ZCGR in Quad characteristic

GRL200 (Soft 033 & 037)


- 125 -
6F2S1914 (0.37)

2.10.6 Extended application


(i) Switch-onto-fault (SOTF)
If a dead line has a fault prior to energization the CB should trip quickly upon when the line
is energized. To trip the CB when the faulted line is energized, a switch-onto-fault (SOTF)
protection function is provided. This function is armed for a certain period after the CB is
closed.1

The SOTF function can operate, in the case when a line remains in a non-energized state
for a certain time, which is termed as the deadline time defined by the protection common
(PROT_COMMON2) function.

If Z*S is required to operate for the SOTF function, On is set for the scheme switch [Z*S-
SOTF]. When Z*S is not required to operate for the SOTF operation, the scheme switch is set
to Off.

The SOTF function is provided for all of the ZS/ZG elements; hence, all of the elements
are provided with similar scheme switches and these switches are termed “SOTF” with the
zone names [Z*S-SOTF] for ZS, [Z*G-SOTF] for ZG.

1Note: The distance- measuring element can operate for faults other than close-up three-
phase faults.
2Note: The operation and settings of the PROT_COMMON is described separately, (See
Chapter Relay application: Protection common)

(ii) Blocking all phase-ground elements


Each Z*G zone has an option to block all phase-ground elements from operating if more than
one phase is involved in a ground fault. This is achieved using settings [Z1G-MPFBlk], [Z1XG-
MPFBlk], [Z2G-MPFBlk], [Z3G-MPFBlk], [Z4G-MPFBlk], [Z5G-MPFBlk]. When any of these
settings are set to Block, the associated zone phase-ground elements will only operate in the
event of a single phase to ground fault. On the other hand, where more than one phase is
involved, the phase-ground elements are blocked, allowing the phase-phase elements to detect
the fault & trip.

(iii) Enhancing the detection of faulted-phases


Faulted phase can be detected by ‘Covering zones’, which are independent distance elements
designed solely for enhancing the faulted phase detection. This ‘Covering zone’ is not used for
the determination of the he fault location. The ‘Covering zones’ does not have zero-sequence
compensation; accordingly, the faulted phase(s) can be determined more securely.

GRL200 (Soft 033 & 037)


- 126 -
6F2S1914 (0.37)

Enhances in Z1G, Z1XG & Z5G zones


The Z1G, Z1XG, and Z5G zones are normally applied for instantaneous tripping; they can have
their own, dedicated ‘Covering zones’. The user can program the reactance reaches using
settings [Z1G-CovCoeff], [Z1XG-CovCoeff] and [Z5G-CovCoeff] in the associated operating
zone reach.

The user is recommended so that the reach of ‘Covering zones’ is set to at least 1.5 times
the reach of the associated operating zones. This ‘Covering zones’ does not have zero-sequence
compensation; hence, the user can select maximum, compensated reach of the operating zone
as the base value.

The resistance reaches of the ‘Covering zones’ are automatically set to be identical to the
operating zone resistance reaches; hence the user does not need to consider them.

Figure 2.10-36 illustrates the Z1G covering zone (Z1GCOV) characterized with setting
[Z1G-CovCoeff]; it shows the Z1GCOV element can operate between the zone2 and the zone3.

X 300% X
Z3G-X.Reach

Expansion made with setting [Z1G-CovCoeff]

Z2G-X.Reach

150%

Z1G-X.Reach
100%

Resistive element (R)

R R
Directional element (DR)

Z1G element Z1GCOV element

Figure 2.10-36 Quad covering zone in Z1G programmed with Z1G-CovCoeff

Enhances in Z2G, Z3G & Z4G zones


A common covering zone is provided in Z2G, Z3G, and Z4G zones. This common zone is
automatically set to be the same as the largest of three zones; hence, the user need not have
settings.

GRL200 (Soft 033 & 037)


- 127 -
6F2S1914 (0.37)

Calculation in Z*G-CovCoeff
The user can have recommended [Z1G-CovCoeff] calculated by Equation (2.10-36):
Compensated 'setting [Z1G-X.Reach]'
Setting [Z1G-CovCoeff] = 1.5× (2.10-36)
Setting [Z1G-X.Reach]
The user can also have simplified Equation (2.10-37), because the compensated reach is a
function of the set reach.
Kxs
Setting [Z1G-CovCoeff]=1+ (2.10-37)
200
For example, when Kxs=400, the user can have the following setting.
400
Setting [Z1G-CovCoeff]=1+ =3 (2.10-38)
200

Enhances in Z1S, Z1XS& Z5S zones


Similar to Z1G, Z1XG and Z5G zones, dedicated covering zones are provided for Z1S, Z1XS
and Z5S zones as they are used for internal fault phase detection logics. The settings [Z1S-
CovCoeff], [Z1XS-CovCoeff] and [Z5S-CovCoeff] are used for each reactance each setting
by multiplying this coefficient to each zone reach setting.

Since ZS elements do not need to consider zero-phase sequence compensation, and the
purpose of this coefficient setting is to detect a fault phase, 1.5 – 2.0 is recommended for the
settings.

Another common covering zone is used for Z2S, Z3S and Z4S elements, and as it is set
automatically inside the application calculation, the setting for this covering zone is not
required.

GRL200 (Soft 033 & 037)


- 128 -
6F2S1914 (0.37)

2.10.7 Scheme logic


(i) ZS logic
Figure 2.10-37 shows the ZS logic and corresponding SOTF logics.
Z1S element
Zab ≤ Z1S &
≥1
Zbc ≤ Z1S
&
Zca ≤ Z1S Checking ≥1 8300011B63
particular reach ≥1
ZminF-AB & TZ1S ≥1
Z-min ≥1 ≥1
8000011C20
ZminF-BC PERM Check Z1S-AB t 0
8000011B23
& & & To Grouping logic
ZminF-CA To Z1XS,Z5S 8100011C21 Z1S-BC t 0 Z1S-OPT
ZminR-AB ZminF-PERM-AB & & & ≥1
ZminF-PERM-BC 8200011C22 Z1S-CA
ZminR-BC t 0
ZminF-PERM-CA & & & ≥1
ZminR-CA ZminR-PERM-AB 0.00-100.00s
ZminR-PERM-BC 8000011B66
Z1S-OPT-AB
ZminR-PERM-CA OFF & 8100011B67
From ZG Z1S-MDDET Z1S-OPT-BC
≥1 &
& 8200011B68 Z1S-OPT-CA
Z1_M.PHASE_FAULT
Z1S-ARCBlk On ≥1
& &
≥1 Z1S-ARC-BLOCK
8000001BBB2 Z1S_ARCBLOCK ≥1

Distance common function


Z1CNT-ARCBlk
On
&
A & & &
OCCR B &
& &
C 8000011B6A
& & SOTF-Z1S-OPT-AB
Z1CNT-INSTOP &
On 8100011B6B
& ≥1 SOTF-Z1S-OPT-BC
Z1CNT-TPBlk 8200011B6C
On EFL
& 1 SOTF-Z1S-OPT-CA

OCN-PS
& ≥1
800000EBB0 Z1CNT_MPROT 1 8000011B2B
SOTF-Z1S-TRIP
&
8000011BB1 Z1S_INST_OP

≥1
From VTF &
VTF-DETECT 1 Z1S-EN On
&
From DISCAR 1
DISCAR=PUP
Z1S-SOTF On

&
800001EBB0 SOTF-Z1S BLOCK 1
From SOTF-OC
SOTF-EN-COND
&
800001EBB0 Z1STP_BLOCK 1
8000011C24
AB ≥1
8100011C25
OCF1S BC ≥1
8200011C26
CA

Z1S-OCFS Off

8000081B68 8000081B6F
AB ≥1 & 1 ≥1
8100081B69 8100081B6F
LES-R BC ≥1 & 1 ≥1
8200081B6A 8200081B70
CA ≥1 & 1 ≥1
8000081B6B To CTF,VTF
S
AB 8400081B65 1 &
8100081B6C PSBS-VCTF-BLK
LES-L BC AB & ≥1 R
8200081B6D PSBS 8500081B66 & TPSBS
CA OUT BC & t 0 S
8600081B67 &
CA & 0.020-0.100s R
8000081B61
800008EBB2 LES BLOCK 1 8000081B62 1
AB 8100081B63 & ≥1
Z1S-LEBlk ON PSBS 1 Z1S-PSBBlk
IN BC &
8200081B64 Block
CA &

≥1 &
800008EBB0 PSBS BLOCK 1 t 0 ≥1
≥1 1 0.05s
& TPSBSFR
PSBSRS
PSBSFR t 0
ON &
ON
0.00-10.00s
810008EBB1 PSBS F.RESET

Figure 2.10-37 Z1S/SOTF-Z1S scheme logics generating trip signals

GRL200 (Soft 033 & 037)


- 129 -
6F2S1914 (0.37)

Z1XS element
Zab ≤ Z1XS &
≥1
Zbc ≤ Z1XS
&
Zca ≤ Z1XS Checking ≥1 8700011B63
particular reach ≥1
From Z1S & TZ1XS
≥1 ≥1 ≥1
ZminF-PERM-AB Z-min 8400011C20
ZminF-PERM-BC PERM Check Z1XS-AB t 0
8100061B23
& & & To Grouping logic
ZminF-PERM-CA 8500011C21
ZminR-PERM-AB Z1XS-BC t 0 Z1XS-OPT
& & & ≥1
ZminR-PERM-BC 8600011C22
ZminR-PERM-CA
Z1XS-CA t 0
& & & ≥1
0.00-100.00s
8400011B66
Z1XS-OPT-AB
Z1XS-MDDET OFF & 8500011B67
From ZG
Z1XS-OPT-BC
≥1 &
& 8600011B68 Z1XS-OPT-CA
Z1X_M.PHASE_FAULT
Z1XS-ARCBlk On ≥1
& &
≥1 Z1XS-ARC-BL
8100006EBB2 Z1XS_ARCBLOCK
OCK

Distance common function

A & & &


OCCR B &
& &
C 8400061B6A
& & SOTF-Z1XS-OPT-AB
&
8500061B6B
SOTF-Z1XS-OPT-BC
8600061B6C
EFL 1 SOTF-Z1XS-OPT-CA

OCN-PS
& ≥1
8100061B2B
SOTF-Z1XS-TRIP
&
810006EBB1 Z1XS_INST_OP

≥1
From VTF &
VTF-DETECT 1 Z1XS-EN On

Z1XS-SOTF On

&
810006EBB3 SOTF-Z1XS BLOCK 1
From SOTF-OC
SOTF-EN-COND
&
810006EBB0 Z1XSTP_BLOCK 1
8400011C24
AB ≥1
8500011C25
OCF1XS BC ≥1
8600011C26
CA

Z1XS-OCFS Off

8000081B68 8000081B6F
AB ≥1 & 1 ≥1
8100081B69 8100081B6F
LES-R BC ≥1 & 1 ≥1
8200081B6A 8200081B70
CA ≥1 & 1 ≥1
8000081B6B To CTF,VTF
S
AB 8400081B65 1 &
8100081B6C PSBS-VCTF-BLK
LES-L BC AB & ≥1 R
8200081B6D PSBS 8500081B66 & TPSBS
CA OUT BC & t 0 S
8600081B67 &
CA & 0.020-0.100s R
800008EBB2 LES BLOCK 1 8000081B62 1
AB 8100081B63 & ≥1
Z1XS-LEBlk ON PSBS 1 Z1XS-PSBBlk
IN BC &
8200081B64 Block
CA &

≥1 &
800008EBB0 PSBS BLOCK 1 t 0 ≥1
≥1 1 0.05s
& TPSBSFR
PSBSRS
PSBSFR t 0
ON &
ON
0.00-10.00s
810008EBB1 PSBS F.RESET

Figure 2.10-38 Z1XS/SOTF-Z1XS scheme logics generating trip signals

GRL200 (Soft 033 & 037)


- 130 -
6F2S1914 (0.37)

Z2S element
Zab ≤ Z2S &
≥1
Zbc ≤ Z2S
&
Zca ≤ Z2S Checking ≥1 8300021B63
particular reach ≥1
From Z1S & TZ2S
≥1 ≥1 ≥1
ZminF-PERM-AB Z-min 8000021C20
ZminF-PERM-BC PERM Check Z2S-AB t 0
8200021B23
& & & To Grouping logic
ZminF-PERM-CA 8100021C21
ZminR-PERM-AB Z2S-BC t 0 Z2S-OPT
& & & ≥1
ZminR-PERM-BC 8200021C22
ZminR-PERM-CA
Z2S-CA t 0
& & & ≥1
NonDir 0.00-100.00s
8000021B66
Z2S-Dir Forward Z2S-OPT-AB
Z2S-MDDET OFF & 8100011B67
Reverse Z2S-OPT-BC
From ZG ≥1 &
& 8200011B68 Z2S-OPT-CA
M.PHASE_FAULT-F & ≥1
&
M.PHASE_FAULT-R &
Z2S-ARCBlk On Z2S-ARC-BLOCK
≥1 &
8200002EBB2 Z2S_ARCBLOCK

Distance common function

A & & &


OCCR B &
& &
C 8000021B6A
& & SOTF-Z2S-OPT-AB
&
8100021B6B
SOTF-Z2S-OPT-BC
8200061B6C
EFL 1 SOTF-Z2S-OPT-CA

OCN-PS
& ≥1
8200021B2B
SOTF-Z2S-TRIP
&
820002EBB1 Z2S_INST_OP

≥1
From VTF &
VTF-DETECT 1 Z2S-EN On

Z2S-SOTF On

&
820002EBB3 SOTF-Z2S BLOCK 1
From SOTF-OC
SOTF-EN-COND
&
820002EBB0 Z2STP_BLOCK 1
8000021C24
AB ≥1
8100021C25
OCF2S BC ≥1
8200021C26
CA

Z2S-OCFS Off

8000081B68 8000081B6F
AB ≥1 & 1 ≥1
8100081B69 8100081B6F
LES-R BC ≥1 & 1 ≥1
8200081B6A 8200081B70
CA ≥1 & 1 ≥1
8000081B6B To CTF,VTF
S
AB 8400081B65 1 &
8100081B6C PSBS-VCTF-BLK
LES-L BC AB & ≥1 R
8200081B6D PSBS 8500081B66 & TPSBS
CA OUT BC & t 0 S
8600081B67 &
CA & 0.020-0.100s R
800008EBB2 LES BLOCK 1 8000081B62 1
AB 8100081B63 & ≥1
Z2S-LEBlk ON PSBS 1 Z2S-PSBBlk
IN BC &
8200081B64 Block
CA &

≥1 &
800008EBB0 PSBS BLOCK 1 t 0 ≥1
≥1 1 0.05s
& TPSBSFR
PSBSRS
PSBSFR t 0
ON &
ON
0.00-10.00s
810008EBB1 PSBS F.RESET

Figure 2.10-39 Z2S/SOTF-Z2S scheme logics generating trip signals

GRL200 (Soft 033 & 037)


- 131 -
6F2S1914 (0.37)

Z3S element
Zab ≤ Z3S
Zbc ≤ Z3S
Zca ≤ Z3S 8700021B63
≥1
TZ3S ≥1
8400031C20 ≥1
Z3S-AB t 0
8300031B23
& & & To Grouping logic
8500031C21 Z3S-BC t 0 Z3S-OPT
& & & ≥1
8600031C22 Z3S-CA t 0
& & & ≥1
NonDir 0.00-100.00s
8400031B66
Z3S-Dir Forward Z3S-OPT-AB
Z3S-MDDET OFF & 8500031B67
Reverse Z3S-OPT-BC
From ZG ≥1 &
& 8600031B68 Z3S-OPT-CA
M.PHASE_FAULT-F & ≥1
&
M.PHASE_FAULT-R &
Z3S-ARCBlk On Z3S-ARC-BLOCK
≥1 &
830003EBB2 Z3S_ARCBLOCK

Distance common function

A & & &


OCCR B &
& &
C 8400031B6A
& & SOTF-Z3S-OPT-AB
&
8500031B6B
SOTF-Z3S-OPT-BC
8600031B6C
EFL 1 SOTF-Z3S-OPT-CA

OCN-PS
& ≥1
8300031B2B
SOTF-Z3S-TRIP
&
830003EBB1 Z3S_INST_OP

≥1
From VTF &
VTF-DETECT 1 Z3S-EN On

Z3S-SOTF On

&
830003EBB3 SOTF-Z3S BLOCK 1
From SOTF-OC
SOTF-EN-COND
&
830003EBB0 Z3STP_BLOCK 1
8400031C24
AB ≥1
8500031C25
OCF3S BC ≥1
8600031C26
CA

Z3S-OCFS Off

8000081B68 8000081B6F
AB ≥1 & 1 ≥1
8100081B69 8100081B6F
LES-R BC ≥1 & 1 ≥1
8200081B6A 8200081B70
CA ≥1 & 1 ≥1
8000081B6B To CTF,VTF
S
AB 8400081B65 1 &
8100081B6C PSBS-VCTF-BLK
LES-L BC AB & ≥1 R
8200081B6D PSBS 8500081B66 & TPSBS
CA OUT BC & t 0 S
8600081B67 &
CA & 0.020-0.100s R
800008EBB2 LES BLOCK 1 8000081B62 1
AB 8100081B63 & ≥1
Z3S-LEBlk ON PSBS 1 Z3S-PSBBlk
IN BC &
8200081B64 Block
CA &

≥1 &
800008EBB0 PSBS BLOCK 1 t 0 ≥1
≥1 1 0.05s
& TPSBSFR
PSBSRS t 0
PSBSFR
ON
&
ON
0.00-10.00s
810008EBB1 PSBS F.RESET

Figure 2.10-40 Z3S/SOTF-Z3S scheme logics generating trip signals

GRL200 (Soft 033 & 037)


- 132 -
6F2S1914 (0.37)

Z4S element
Zab ≤ Z4S
Zbc ≤ Z4S
Zca ≤ Z4S 8B00041B63
≥1
TZ4S ≥1
8800041C20 ≥1
Z4S-AB t 0
8400041B23
& & & To Grouping logic
8900041C21
Z4S-BC t 0 Z4S-OPT
& & & ≥1
8A00041C22 Z4S-CA t 0
& & & ≥1
NonDir 0.00-100.00s
8800041B66
Z4S-Dir Forward Z4S-OPT-AB
Z4S-MDDET OFF & 8900041B67
Reverse Z4S-OPT-BC
From ZG ≥1 &
& 8A00041B68 Z4S-OPT-CA
M.PHASE_FAULT-F & ≥1
&
M.PHASE_FAULT-R &
Z4S-ARCBlk On Z4S-ARC-BLOCK
≥1 &
840004EBB2 Z4S_ARCBLOCK

Distance common function

A & & &


OCCR B &
& &
C 8800041B6A
& & SOTF-Z4S-OPT-AB
&
8900041B6B
SOTF-Z4S-OPT-BC
8A00041B6C
EFL 1 SOTF-Z4S-OPT-CA

OCN-PS
& ≥1
8400041B2B
SOTF-Z4S-TRIP
&
840004EBB1 Z4S_INST_OP

≥1
From VTF &
VTF-DETECT 1 Z4S-EN On

Z4S-SOTF On

&
840004EBB3 SOTF-Z4S BLOCK 1
From SOTF-OC
SOTF-EN-COND
&
840004EBB0 Z4STP_BLOCK 1
8800041C24
AB ≥1
8900041C25
OCF4S BC ≥1
8A00041C26
CA

Z4S-OCFS Off

8000081B68 8000081B6F
AB ≥1 & 1 ≥1
8100081B69 8100081B6F
LES-R BC ≥1 & 1 ≥1
8200081B6A 8200081B70
CA ≥1 & 1 ≥1
8000081B6B To CTF,VTF
S
AB 8400081B65 1 &
8100081B6C PSBS-VCTF-BLK
LES-L BC AB & ≥1 R
8200081B6D PSBS 8500081B66 & TPSBS
CA OUT BC & t 0 S
8600081B67 &
CA & 0.020-0.100s R
800008EBB2 LES BLOCK 1 8000081B62 1
AB 8100081B63 & ≥1
Z4S-LEBlk ON PSBS 1 Z4S-PSBBlk
IN BC &
8200081B64 Block
CA &

≥1 &
800008EBB0 PSBS BLOCK 1 t 0 ≥1
≥1 1 0.05s
& TPSBSFR
PSBSRS
PSBSFR t 0
ON &
ON
0.00-10.00s
810008EBB1 PSBS F.RESET

Figure 2.10-41 Z4S/SOTF-Z4S scheme logics generating trip signals

GRL200 (Soft 033 & 037)


- 133 -
6F2S1914 (0.37)

Z5S element
Zab ≤ Z5S &
≥1
Zbc ≤ Z5S
&
Zca ≤ Z5S Checking ≥1 8B00051B63
particular reach ≥1
From Z1S & TZ5S
≥1 ≥1 ≥1
ZminF-PERM-AB Z-min 8800051C20
ZminF-PERM-BC PERM Check Z5S-AB t 0
8100061B23
& & & To Grouping logic
ZminF-PERM-CA 8900051C21
ZminR-PERM-AB Z5S-BC t 0 Z1XS-OPT
& & & ≥1
ZminR-PERM-BC 8A00051C22
ZminR-PERM-CA
Z5S-CA t 0
& & & ≥1
0.00-100.00s
8400011B66
Z1XS-OPT-AB
Z5S-MDDET OFF & 8500011B67
From ZG
Z1XS-OPT-BC
≥1 &
& 8600011B68 Z1XS-OPT-CA
Z5_M.PHASE_FAULT
Z5S-ARCBlk On ≥1
& &
≥1 Z1XS-ARC-BL
8500005EBB2 Z5S_ARCBLOCK
OCK

Distance common function

A & & &


OCCR B &
& &
C 8800051B6A
& & SOTF-Z5S-OPT-AB
&
8900051B6B
SOTF-Z5S-OPT-BC
8A00051B6C
EFL 1 SOTF-Z5S-OPT-CA

OCN-PS
& ≥1
8500051B2B
SOTF-Z5S-TRIP
&
850005EBB1 Z5S_INST_OP

≥1
From VTF &
VTF-DETECT 1 Z5S-EN On

Z5S-SOTF On

&
850005EBB3 SOTF-Z5S BLOCK 1
From SOTF-OC
SOTF-EN-COND
&
850005EBB0 Z5STP_BLOCK 1
8800051C24
AB ≥1
8900051C25
OCF5S BC ≥1
8A00051C26
CA

Z5S-OCFS Off

8000081B68 8000081B6F
AB ≥1 & 1 ≥1
8100081B69 8100081B6F
LES-R BC ≥1 & 1 ≥1
8200081B6A 8200081B70
CA ≥1 & 1 ≥1
8000081B6B To CTF,VTF
S
AB 8400081B65 1 &
8100081B6C PSBS-VCTF-BLK
LES-L BC AB & ≥1 R
8200081B6D PSBS 8500081B66 & TPSBS
CA OUT BC & t 0 S
8600081B67 &
CA & 0.020-0.100s R
800008EBB2 LES BLOCK 1 8000081B62 1
AB 8100081B63 & ≥1
Z5S-LEBlk ON PSBS 1 Z5S-PSBBlk
IN BC &
8200081B64 Block
CA &

≥1 &
800008EBB0 PSBS BLOCK 1 t 0 ≥1
≥1 1 0.05s
& TPSBSFR
PSBSRS
PSBSFR t 0
ON &
ON
0.00-10.00s
810008EBB1 PSBS F.RESET

Figure 2.10-42 Z5S/SOTF-Z5S scheme logics generating trip signals

GRL200 (Soft 033 & 037)


- 134 -
6F2S1914 (0.37)

The Z1S element generates a trip signal for the trip function (TRC) immediately when
the instantaneous mode is selected using the scheme switch [Z1CNT_INSTOP]. Note that the
scheme switch [LES_EN] can be used to block the Z1S element. The scheme switches [Z1S-
PSBBLK] and [Z1G-PSBBLK] can be used to block CB tripping when a power swing occurs in
the system. The scheme switch [Z1S-MSDET] is also used to cancel the operation condition,
which we have discussed with regard to the selection of the operation of ZS effected by the
occurrences of multi-phase fault or earth-fault. (see section 2.10.3(ii)-3).

The ZS elements generate trip signals if On is set for all of the scheme switches termed
“EN” with zone names [Z*S-EN]. The user should set Off for scheme switch [Z*S-EN] to disable
for issuing the trip signals. Using PLC signal ‘Z*S_ARCBLOCK’, the Z*S elements can issue
‘ARC-BLOCK’ signals for the ARC function via the TRC function; we shall see it later in
Chapter Relay application: Autoreclose.
To TRC
From Z1S to Z5S logics 8300001B23To DISCARC
Z1S-OPT ≥1 ZS-OPT-TRIP
Z1XS-OPT
Z2S-OPT
Z3S-OPT
Z4S-OPT
Z5S-OPT 8500001B61
Z1S-ARC-BLOCK ≥1 ZS-ARC-BLOCK
Z1XS-ARC-BLOCK
Z2S-ARC-BLOCK
Z3S-ARC-BLOCK
Z4S-ARC-BLOCK
Z5S-ARC-BLOCK
8C00001B62
Z1S-OPT-AB ≥1 ZS-OPT-ABR
8D00001B63
Z1S-OPT-BC ZS-OPT-BCR
8E00001B64
Z1S-OPT-CA ZS-OPT-CAR

Z1XS-OPT-AB

Z1XS-OPT-BC
≥1
Z1XS-OPT-CA

Z2S-OPT-AB

Z2S-OPT-BC

Z2S-OPT-CA

Z3S-OPT-AB

≥1
Z3S-OPT-BC

Z3S-OPT-CA

Z4S-OPT-AB

Z4S-OPT-BC

Z4S-OPT-CA

Z5S-OPT-AB

Z5S-OPT-BC

Z5S-OPT-CA

Figure 2.10-43 ZS grouping logic for TRC/Recording functions

GRL200 (Soft 033 & 037)


- 135 -
6F2S1914 (0.37)

To TRC
From Z1S to Z5S logics 8300001B28 To DISCARC
SOTF-Z1S-OPT ≥1 SOTF-ZS-OPT-TRIP
SOTF-Z1XS-OPT
SOTF-Z2S-OPT
SOTF-Z3S-OPT
SOTF-Z4S-OPT
SOTF-Z5S-OPT

SOTF-ZS-ARC-BLOCK

8C00001B66
SOTF-Z1S-OPT-AB ≥1 SOTF-ZS-OPT-ABR
8D00001B67
SOTF-Z1S-OPT-BC SOTF-ZS-OPT-BCR
8E00001B68
SOTF-Z1S-OPT-CA SOTF-ZS-OPT-CAR

SOTF-Z1XS-OPT-AB

SOTF-Z1XS-OPT-BC
≥1
SOTF-Z1XS-OPT-CA

SOTF-Z2S-OPT-AB

SOTF-Z2S-OPT-BC

SOTF-Z2S-OPT-CA

SOTF-Z3S-OPT-AB

≥1
SOTF-Z3S-OPT-BC

SOTF-Z3S-OPT-CA

SOTF-Z4S-OPT-AB

SOTF-Z4S-OPT-BC

SOTF-Z4S-OPT-CA

SOTF-Z5S-OPT-AB

SOTF-Z5S-OPT-BC

SOTF-Z5S-OPT-CA

Figure 2.10-44 SOTF-ZS grouping logic for TRC/Recording functions

(ii) ZG logic
Figure 2.10-45 to Figure 2.10-50 to shows the ZG logics and corresponding SOTF logics. All
logic operations (Z1G, Z1GX, Z2G, Z3G, Z4G, and Z5G) can be selected using the scheme
switches. Scheme switch [Z*G-EFL] is used to select the EFL element for the detection of earth
faults; when the EFL element operates, detection of the PSB is canceled.

Scheme switch [Z*G-LPBlk] is used to enable blocking of the operation of the leading-
phase-block function. The ARC_BLOCK signals allow the Z*G element to perform final three-
phase tripping for all faults. The Z*G_3PTP configures the Z*G element to perform the three-
phase trip.

GRL200 (Soft 033 & 037)


- 136 -
6F2S1914 (0.37)

800001EBB2 Z1G_3PTP
8300011B63
≥1 ≥1
8000011C20 TZ1G
t 0 ≥1
A & & & 8000011B69 To Grouping logic
Z1G 8100011C21
B t 0
≥1 Z1G-OPT
& & &
8200011C22
C t 0
& & &
≥1
≥1 0.00-100.00s 8000011B66
A & ≥1 &
≥1 & Z1G-OPT-A
≥1 8100011B67
Z1GCOV B &
& &
Non ≥1 Z1G-OPT-B
Z1G-LPBlk 8200011B68
C 1 &
& &
Z1G-OPT-C
≥1 1
Z1G-MPFBlk ≥1
& & Z1G-ARC-BLOCK
Non
≥1
&
≥1
&
≥1 Z1G-TRIP-A
≥1
≥1 1 &
≥1 Z1G-TRIP -B
1
1 ≥1 Z1G-TRIP -C

1 Z1G-TPMD
≥1 &

3P

& ≥1 8000011B2B
SOTF-Z1G-TRIP
&

&
From VTF

VTF-DETECT 1 8000011B6B
SOTF-Z1G-OPT-A
Distance common function
8100011B6C
&
A SOTF-Z1G-OPT-B
OCCR 8200011B6D
B &
SOTF-Z1G-OPT-C
C &
Z1G-EFL
EFL ≥1
Off
OCN-PS
To ZS
Z1_M.PHASE_FAULT

8000081B60
A & 1 NON_PWIBLK-C
8100081B61
UVPWI B & 1 NON_PWIBLK-A
8200081B62 1 NON_PWIBLK-B
C &

From TRC 8000011C24


GEN.TRIP 1 & A ≥1
8100011C25
OCF1G B ≥1
From PROT_COMM
8200011C26
C &
CB_ALLPH_CLOSE
≥1
Z1G-OCFS Off Z1G-EN
ZG-UVPWIEN On
=ON

From DISCAR Z1G-EN On &


Z1G-TPEN=ON
DISCAR=PUP
1
From SOTF-OC Z1G-SOTF On
SOTF-EN-COND

800001EBB0 Z1GTP_BLOCK &

1
Z1G-ARCBlk On
≥1
800001EBB3 Z1GARC_BLOCK

Distance common function ≥1


8000081B69 8000081B71
Z1CNT-ARCBlk
On A ≥1 & 1 ≥1
& 8100081B6A 8100081B72
Z1CNT-TPBlk LEG-R B ≥1 1 ≥1 Z1G-PSBBlk Block
On &
& 8200081B6B 8200081B73 &
C 1 1
Z1CNT-3PTP ≥1 & ≥1
On
8000081B6B To CTF,VTF
&
Z1CNT-INSTOP S
On A 1 & PSBG-VCTF-BLK
8100081B6D 8400081B63
& & ≥1 R
LEG-L B A
8200081B6E PSBG 8500081B64 & TPSBG
C OUT B & t 0 S
800000EBB0 Z1CNT_MPROT 1
8600081B65
1 C & 0.020-0.100s R
800001EBB1 Z1G_INST_OP
Z1G-LEBlk Block 8000081B66
800008EBB2 LEG BLOCK A & ≥1
PSBG 8100081B67
1
IN B &
8200081B68
C &

≥1 &
1 t 0
800008EBB0 PSBG BLOCK ≥1

1 0.05s
≥1
& TPSBGFR
PSBGRS ON ≥1 PSBGFR
t 0
&
ON 0.00-10.00s
810008EBB1 PSBG F.RESET

Figure 2.10-45 Z1G/SOTF-Z1G Scheme logic generating trip signals

GRL200 (Soft 033 & 037)


- 137 -
6F2S1914 (0.37)

810006EBB2 Z1XG_3PTP 8700011B63


≥1 TZ1XG ≥1
8400061C20 ≥1
t 0 To Grouping logic
A & & & 8100061B69
Z1XG 8500061C21
B t 0
≥1 Z1XG-OPT
& & &
8600061C22
C t 0
& & &
≥1
≥1 0.00-100.00s 8400011B20
A & ≥1 &
≥1 & Z1XG-OPT-A
≥1 8500011B21
Z1XGCOV B &
& &
Non ≥1 Z1XG-OPT-B
Z1XG-LPBlk 8600011B22
C 1 &
& &
Z1XG-OPT-C
≥1 1
Z1XG-MPFBlk ≥1
& & Z1XG-ARC-BLOCK
Non
≥1
&
≥1
&
≥1 Z1XG-TRIP-A
≥1
≥1 1 &
≥1 Z1XG-TRIP -B
1
1 ≥1 Z1XG-TRIP -C
≥1
1 &
Z1XG-TPMD

3P

& ≥1 8100061B2B
SOTF-Z1XG-TRIP
&

&
From VTF

VTF-DETECT 1 8400011B6B
SOTF-Z1XG-OPT-A
Distance common function
8500011B6C
&
A SOTF-Z1XG-OPT-B
OCCR 8600011B6D
B &
SOTF-Z1XG-OPT-C
C &
Z1XG-EFL
EFL ≥1
Off
OCN-PS
To ZS
Z1X_M.PHASE_FAULT

8000081B60
A & 1 NON_PWIBLK-C
8100081B61
UVPWI B & 1 NON_PWIBLK-A
8200081B62 1 NON_PWIBLK-B
C &

From TRC 8400011C24


GEN.TRIP 1 & A ≥1
8500011C25
OCF1XG B ≥1
From PROT_COMM
8600011C26
C &
CB_ALLPH_CLOSE
≥1
Z1XG-OCFS Off Z1XG-EN
ZG-UVPWIEN On
=ON

Z1XG-EN On Z1XG-TPEN=ON

From SOTF-OC Z1XG-SOTF On


SOTF-EN-COND

810006EBB0 Z1XGTP_BLOCK &

1
Z1XG-ARCBlk
On
≥1
810006EBB3 Z1XG_ARCBLOCK

Distance common function


8000081B69 8000081B71
Z1CNT-ARCBlk
On A ≥1 & 1 ≥1
& 8100081B6A 8100081B72 Z1XG-PSBBlk
LEG-R B ≥1 1 ≥1 Block
&
8200081B6B 8200081B73 &
C 1 1
≥1 & ≥1
8000081B6B To CTF,VTF
S
A 1 & PSBG-VCTF-BLK
8100081B6D 8400081B63
LEG-L B A & ≥1 R
8200081B6E PSBG 8500081B64 & TPSBG
800000EBB0 Z1CNT_MPROT
C OUT B & t 0 S
8600081B65
1 C & 0.020-0.100s R
810006EBB1 Z1XG_INST_OP
Z1XG-LEBlk Block 8000081B66
800008EBB2 LEG BLOCK A & ≥1
PSBG 8100081B67
1
IN B &
8200081B68
C &

≥1 &
1 t 0
800008EBB0 PSBG BLOCK ≥1

1 0.05s
≥1
& TPSBGFR
PSBGRS ON ≥1 PSBGFR
t 0
&
ON 0.00-10.00s
810008EBB1 PSBG F.RESET

Figure 2.10-46 Z1XG/SOTF-Z1XG Scheme logic generating trip signals

GRL200 (Soft 033 & 037)


- 138 -
6F2S1914 (0.37)

820002EBB2 Z2G_3PTP 8300011B63


≥1 TZ2G ≥1
8000021C20 ≥1
t 0 To Grouping logic
A & & & 8200021B69
Z2G 8100021C21
B t 0
≥1 Z2G-OPT
& & &
8200021C22
C t 0
& & &
≥1
Z2G-MPFBlk 0.00-100.00s 8000021B60
&
Non ≥1 & Z2G-OPT-A
8100021B67
&
NonDir Z2G-LPBlk & Z2G-OPT-B
& 8200021B68
Reverse &
Z2G-Dir
Forward
Z2G-OPT-C

8400001B66
& & Z2G-ARC-BLOCK
A & ≥1
8500001B67 1
ZGRCOV B & ≥1
&
8600001B68 &
C ≥1
& Z2G-TRIP-A
1 & ≥1 ≥1 ≥1 Z2G-TRIP -B
1 & ≥1
≥1 ≥1 Z2G-TRIP -C
1 ≥1
& &
≥1 ≥1 Z2G-TPMD
8000001B63
& ≥1 3P
A
8100001B64 1
ZGFCOV B
& &
≥1 ≥1 & ≥1 8200021B2B
8200001B65
C
& & SOTF-Z2G-TRIP
1 ≥1 ≥1 &
& &
1 & ≥1 ≥1
& &
1
&
From VTF &
VTF-DETECT 1 8000021B6B
&
SOTF-Z2G-OPT-A
Distance common function
8100021B6C
A & SOTF-Z2G-OPT-B
OCCR 8200021B6D
B &
SOTF-Z2G-OPT-C
C &
Z2G-EFL
EFL
Off ≥1
OCN-PS
To ZS
M.PHASE_FAULT-F
M.PHASE_FAULT-R
8000081B60
A & 1 NON_PWIBLK-C
8100081B61
UVPWI B & 1 NON_PWIBLK-A
8200081B62 1 NON_PWIBLK-B
C &

From TRC 8000021C24


GEN.TRIP 1 & A ≥1
8100021C25
OCF2G B ≥1
From PROT_COMM
8200021C26
C &
CB_ALLPH_CLOSE
≥1
Z2G-OCFS Off Z2G-EN
ZG-UVPWIEN On
=ON

Z2G-EN On Z2G-TPEN=ON

From SOTF-OC Z2G-SOTF On


SOTF-EN-COND

820002EBB0 Z2GTP_BLOCK &

1
Z2G-ARCBlk
On
≥1
820002EBB3 Z2G_ARCBLOCK

Distance common function


8000081B69 8000081B71
Z1CNT-ARCBlk
On A ≥1 & 1 ≥1
& 8100081B6A 8100081B72 Z2G-PSBBlk
LEG-R B ≥1 1 ≥1 Block
&
8200081B6B 8200081B73 &
C 1 1
≥1 & ≥1
8000081B6B To CTF,VTF
S
A 1 & PSBG-VCTF-BLK
8100081B6D 8400081B63
LEG-L B A & ≥1 R
8200081B6E PSBG 8500081B64 & TPSBG
800000EBB0 Z1CNT_MPROT
C OUT B & t 0 S
8600081B65
1 C & 0.020-0.100s R
820002EBB1 Z2G_INST_OP
Z2G-LEBlk Block 8000081B66
800008EBB2 LEG BLOCK A & ≥1
PSBG 8100081B67
1
IN B &
8200081B68
C &

≥1 &
1 t 0
800008EBB0 PSBG BLOCK ≥1

1 0.05s
≥1
& TPSBGFR
PSBGRS ON ≥1 PSBGFR
t 0
&
ON 0.00-10.00s
810008EBB1 PSBG F.RESET

Figure 2.10-47 Z2G/SOTF-Z2G Scheme logic generating trip signals

GRL200 (Soft 033 & 037)


- 139 -
6F2S1914 (0.37)

830003EBB2 Z3G_3PTP 8700031B63


≥1 TZ3G ≥1
8400031C20 ≥1
t 0 To Grouping logic
A & & & 8300021B69
Z3G 8500031C21
B t 0
≥1 Z3G-OPT
& & &
8600031C22
C t 0
& & &
≥1
Z3G-MPFBlk 0.00-100.00s 8400031B66
&
Non ≥1 & Z3G-OPT-A
8500031B67
&
NonDir Z3G-LPBlk & Z3G-OPT-B
& 8600031B68
Reverse &
Z3G-Dir
Forward
Z3G-OPT-C

8400001B66
& & Z3G-ARC-BLOCK
A & ≥1
8500001B67 1
ZGRCOV B & ≥1
&
8600001B68 &
C ≥1
& Z3G-TRIP-A
1 & ≥1 ≥1 ≥1 Z3G-TRIP -B
1 & ≥1
≥1 ≥1 Z3G-TRIP -C
1 ≥1
& &
≥1 ≥1 Z3G-TPMD
8000001B63
& ≥1 3P
A
8100001B64 1
ZGFCOV B
& &
≥1 ≥1 & ≥1 8300021B2B
8200001B65
C
& & SOTF-Z3G-TRIP
1 ≥1 ≥1 &
& &
1 & ≥1 ≥1
& &
1
&
From VTF &
VTF-DETECT 1 8400031B6B
&
SOTF-Z3G-OPT-A
Distance common function
8500021B6C
A & SOTF-Z3G-OPT-B
OCCR 8600021B6D
B &
SOTF-Z3G-OPT-C
C &
Z3G-EFL
EFL
Off ≥1
OCN-PS
To ZS
M.PHASE_FAULT-F
M.PHASE_FAULT-R
8000081B60
A & 1 NON_PWIBLK-C
8100081B61
UVPWI B & 1 NON_PWIBLK-A
8200081B62 1 NON_PWIBLK-B
C &

From TRC 8400021C24


GEN.TRIP 1 & A ≥1
8500021C25
OCF3G B ≥1
From PROT_COMM
8600021C26
C &
CB_ALLPH_CLOSE
≥1
Z3G-OCFS Off Z3G-EN
ZG-UVPWIEN On
=ON

Z3G-EN On Z3G-TPEN=ON

From SOTF-OC Z3G-SOTF On


SOTF-EN-COND

830003EBB0 Z3GTP_BLOCK &

1
Z3G-ARCBlk
On
≥1
830003EBB3 Z3G_ARCBLOCK

Distance common function


8000081B69 8000081B71
Z1CNT-ARCBlk
On A ≥1 & 1 ≥1
& 8100081B6A 8100081B72 Z3G-PSBBlk
LEG-R B ≥1 1 ≥1 Block
&
8200081B6B 8200081B73 &
C 1 1
≥1 & ≥1
8000081B6B To CTF,VTF
S
A 1 & PSBG-VCTF-BLK
8100081B6D 8400081B63
LEG-L B A & ≥1 R
8200081B6E PSBG 8500081B64 & TPSBG
800000EBB0 Z1CNT_MPROT
C OUT B & t 0 S
8600081B65
1 C & 0.020-0.100s R
830003EBB1 Z3G_INST_OP
Z3G-LEBlk Block 8000081B66
800008EBB2 LEG BLOCK A & ≥1
PSBG 8100081B67
1
IN B &
8200081B68
C &

≥1 &
1 t 0
800008EBB0 PSBG BLOCK ≥1

1 0.05s
≥1
& TPSBGFR
PSBGRS ON ≥1 PSBGFR
t 0
&
ON 0.00-10.00s
810008EBB1 PSBG F.RESET

Figure 2.10-48 Z3G/SOTF-Z3G Scheme logic generating trip signals

GRL200 (Soft 033 & 037)


- 140 -
6F2S1914 (0.37)

840004EBB2 Z4G_3PTP 8B00041B63


≥1 TZ4G ≥1
8400031C20 ≥1
t 0 To Grouping logic
A & & & 8400041B69
Z4G 8500031C21
B t 0
≥1 Z4G-OPT
& & &
8600031C22
C t 0
& & &
≥1
Z4G-MPFBlk 0.00-100.00s 8800041B66
&
Non ≥1 & Z4G-OPT-A
8800041B67
&
NonDir Z4G-LPBlk & Z4G-OPT-B
& 8800041B68
Reverse &
Z4G-Dir
Forward
Z4G-OPT-C

8400001B66
& & Z4G-ARC-BLOCK
A & ≥1
8500001B67 1
ZGRCOV B & ≥1
&
8600001B68 &
C ≥1
& Z4G-TRIP-A
1 & ≥1 ≥1 ≥1 Z4G-TRIP -B
1 & ≥1
≥1 ≥1 Z4G-TRIP -C
1 ≥1
& &
≥1 ≥1 Z4G-TPMD
8000001B63
& ≥1 3P
A
8100001B64 1
ZGFCOV B
& &
≥1 ≥1 & ≥1 8400041B2B
8200001B65
C
& & SOTF-Z4G-TRIP
1 ≥1 ≥1 &
& &
1 & ≥1 ≥1
& &
1
&
From VTF &
VTF-DETECT 1 8800041B6B
&
SOTF-Z4G-OPT-A
Distance common function
8900041B6C
A & SOTF-Z4G-OPT-B
OCCR 8A00041B6D
B &
SOTF-Z4G-OPT-C
C &
Z4G-EFL
EFL
Off ≥1
OCN-PS
To ZS
M.PHASE_FAULT-F
M.PHASE_FAULT-R
8000081B60
A & 1 NON_PWIBLK-C
8100081B61
UVPWI B & 1 NON_PWIBLK-A
8200081B62 1 NON_PWIBLK-B
C &

From TRC 8800041C24


GEN.TRIP 1 & A ≥1
8900041C25
OCF4G B ≥1
From PROT_COMM
8A00041C26
C &
CB_ALLPH_CLOSE
≥1
Z4G-OCFS Off Z4G-EN
ZG-UVPWIEN On
=ON

Z4G-EN On Z4G-TPEN=ON

From SOTF-OC Z4G-SOTF On


SOTF-EN-COND

840004EBB0 Z4GTP_BLOCK &

1
Z4G-ARCBlk
On
≥1
840004EBB3 Z4G_ARCBLOCK

Distance common function


8000081B69 8000081B71
Z1CNT-ARCBlk
On A ≥1 & 1 ≥1
& 8100081B6A 8100081B72 Z4G-PSBBlk
LEG-R B ≥1 1 ≥1 Block
&
8200081B6B 8200081B73 &
C 1 1
≥1 & ≥1
8000081B6B To CTF,VTF
S
A 1 & PSBG-VCTF-BLK
8100081B6D 8400081B63
LEG-L B A & ≥1 R
8200081B6E PSBG 8500081B64 & TPSBG
800000EBB0 Z1CNT_MPROT
C OUT B & t 0 S
8600081B65
1 C & 0.020-0.100s R
840004EBB1 Z4G_INST_OP
Z4G-LEBlk Block 8000081B66
800008EBB2 LEG BLOCK A & ≥1
PSBG 8100081B67
1
IN B &
8200081B68
C &

≥1 &
1 t 0
800008EBB0 PSBG BLOCK ≥1

1 0.05s
≥1
& TPSBGFR
PSBGRS ON ≥1 PSBGFR
t 0
&
ON 0.00-10.00s
810008EBB1 PSBG F.RESET

Figure 2.10-49 Z4G/SOTF-Z4G Scheme logic generating trip signals

GRL200 (Soft 033 & 037)


- 141 -
6F2S1914 (0.37)

850005EBB2 Z1XG_3PTP 8800051B63


≥1 TZ5G ≥1
8800051C20 ≥1
t 0 To Grouping logic
A & & & 8100061B69
Z5G 8900051C21
B t 0
≥1 Z5G-OPT
& & &
8A00051C22
C t 0
& & &
≥1
≥1 0.00-100.00s 8800051B20
A & ≥1 &
≥1 & Z5G-OPT-A
≥1 8900051B21
Z5GCOV B &
& &
Non ≥1 Z5G-OPT-B
Z5G-LPBlk 8A00051B22
C 1 &
& &
Z5G-OPT-C
≥1 1 1
Z5G-MPFBlk ≥1
& & Z5G-ARC-BLOCK
Non
≥1
&
≥1
&
≥1 Z5G-TRIP-A
≥1
≥1 1 &
≥1 Z5G-TRIP -B
1
1 ≥1 Z5G-TRIP -C
≥1
1 &
Z5G-TPMD

3P

& ≥1 8500051B2B
SOTF-Z5G-TRIP
&

&
From VTF

VTF-DETECT 1 8800051B6B
SOTF-Z5G-OPT-A
Distance common function
8800051B6C
&
A SOTF-Z5G-OPT-B
OCCR 8A00051B6D
B &
SOTF-Z5G-OPT-C
C &
Z5G-EFL
EFL ≥1
Off
OCN-PS
To ZS
Z5_M.PHASE_FAULT

8000081B60
A & 1 NON_PWIBLK-C
8100081B61
UVPWI B & 1 NON_PWIBLK-A
8200081B62 1 NON_PWIBLK-B
C &

From TRC 8800051C24


GEN.TRIP 1 & A ≥1
8900051C25
OCF5G B ≥1
From PROT_COMM
8A00051C26
C &
CB_ALLPH_CLOSE
≥1
Z5G-OCFS Off Z5G-EN
ZG-UVPWIEN On
=ON

Z5G-EN On Z5G-TPEN=ON

From SOTF-OC Z5G-SOTF On


SOTF-EN-COND

850005EBB0 Z5GTP_BLOCK &

1
Z5G-ARCBlk
On
≥1
850005EBB3 Z5G_ARCBLOCK

Distance common function


8000081B69 8000081B71
Z1CNT-ARCBlk
On A ≥1 & 1 ≥1
& 8100081B6A 8100081B72 Z5G-PSBBlk
LEG-R B ≥1 1 ≥1 Block
&
8200081B6B 8200081B73 &
C 1 1
≥1 & ≥1
8000081B6B To CTF,VTF
S
A 1 & PSBG-VCTF-BLK
8100081B6D 8400081B63
LEG-L B A & ≥1 R
8200081B6E PSBG 8500081B64 & TPSBG
800000EBB0 Z1CNT_MPROT
C OUT B & t 0 S
8600081B65
1 C & 0.020-0.100s R
850005EBB1 Z5G_INST_OP
Z5G-LEBlk Block 8000081B66
800008EBB2 LEG BLOCK A & ≥1
PSBG 8100081B67
1
IN B &
8200081B68
C &

≥1 &
1 t 0
800008EBB0 PSBG BLOCK ≥1

1 0.05s
≥1
& TPSBGFR
PSBGRS ON ≥1 PSBGFR
t 0
&
ON 0.00-10.00s
810008EBB1 PSBG F.RESET

Figure 2.10-50 Z5G/SOTF-Z5G Scheme logic generating trip signals

GRL200 (Soft 033 & 037)


- 142 -
6F2S1914 (0.37)

Instantaneous and blocking TRIP commands


The Z*G element is able to operate in an instantaneous mode by using the scheme switch
[Z1CNT_INSTOP]. Furthermore, the scheme switch [LEG_EN] can block this element. The
scheme switch [Z*G-PSBBLK] is selected for blocking the tripping when a power swing occurs
in the system. A residual overcurrent element (EFL) is provided as a common function. A value
can be set using the setting [EFL].
From Z1G to Z5G logics To TRC
Z1G-TRIP-A ≥1 To DISCARC
8000001B20
ZG-TRIP-A

Z1G-TRIP-B ≥1
8100001B21
ZG-TRIP-B

Z1G-TRIP-C ≥1 8200001B22

ZG-TRIP-C
Z1XG-TRIP-A
Z1XG-TRIP-B
Z1XG-TRIP-C

Z2G-TRIP-A
Z2G-TRIP-B
Z2G-TRIP-C

Z3G-TRIP-A
Z3G-TRIP-B
Z3G-TRIP-C

Z4G-TRIP-A
Z4G-TRIP-B
Z4G-TRIP-C

Z5G-TRIP-A
Z5G-TRIP-B
Z5G-TRIP-C

Z1G-OPT-A ≥1
8800001B70
ZG-OPT-AR

Z1G-OPT-B ≥1
8900001B7E
ZG-OPT-BR

Z1G-OPT-C ≥1 8A00001B7F

ZG-OPT-CR
Z1XG-OPT-A
Z1XG-OPT-B
Z1XG-OPT-C

Z2G-OPT-A
Z2G-OPT-B
Z2G-OPT-C

Z3G-OPT-A
Z3G-OPT-B
Z3G-OPT-C

Z4G-OPT-A
Z4G-OPT-B
Z4G-OPT-C

Z5G-OPT-A
Z5G-OPT-B
Z5G-OPT-C
8500001B7C
Z1G-ARC-BLOCK ≥1 ZG-ARC-BLOCK
Z1XG-ARC-BLOCK
Z2G-ARC-BLOCK
Z3G-ARC-BLOCK
Z4G-ARC-BLOCK
Z5G-ARC-BLOCK

Figure 2.10-51 ZG grouping logic for TRC/Recording functions

GRL200 (Soft 033 & 037)


- 143 -
6F2S1914 (0.37)

To TRC
From Z1G to Z5G logics 8300001B28 To DISCARC
SOTF-Z1G-OPT ≥1 SOTF-ZG-OPT-TRIP
SOTF-Z1XG-OPT
SOTF-Z2G-OPT
SOTF-Z3G-OPT
SOTF-Z4G-OPT
SOTF-Z5G-OPT

SOTF-ZG-ARC-BLOCK

8800001B81
SOTF-Z1G-OPT-A ≥1 SOTF-ZG-OPT-AR
8900001B82
SOTF-Z1G-OPT-B SOTF-ZG-OPT-BR
8A00001B83
SOTF-Z1G-OPT-C SOTF-ZG-OPT-CR

SOTF-Z1XG-OPT-A

SOTF-Z1XG-OPT-B
≥1
SOTF-Z1XG-OPT-C

SOTF-Z2G-OPT-A

SOTF-Z2G-OPT-B

SOTF-Z2G-OPT-C

SOTF-Z3G-OPT-A

≥1
SOTF-Z3G-OPT-B

SOTF-Z3G-OPT-C

SOTF-Z4G-OPT-A

SOTF-Z4G-OPT-B

SOTF-Z4G-OPT-C

SOTF-Z5G-OPT-A

SOTF-Z5G-OPT-B

SOTF-Z5G-OPT-C

Figure 2.10-52 SOTF-ZG grouping logic for TRC/Recording functions

TRIP commands for opening the CB poles


The ZG function issues a per-phase trip signal so that a per-phase TRIP COMMAND will be
generated in the TRC function; set a single-phase trip (1P) mode for scheme switch [Z*G-TPMD].
The user can also set a three-phase trip (3P) mode if the TRIP_COMMANDs does not need to
issue separately. Note that the TRIP_COMMANDs will be issued for the CB in the TRC
function after collecting signals from the other functions. Remember that the user should set
1-PHASE for the scheme switch [TP-MODE] in the TRC for 3P mode. The user should recognize
that the settings of the [Z*G-TPMD] (see Figure 2.10-45 etc. and Figure 2.10-51) and the setting
[TP-MODE] (see Figure 2.33-3) have cooperation to trip the CB correctly.
Note: For your information, the settings of TRC function affect the other trip signals
from other functions. See Chapter Relay application: Trip circuit.

GRL200 (Soft 033 & 037)


- 144 -
6F2S1914 (0.37)

2.10.8 Tips to set the main/remote backup relays


To make the coordination between the main (primary) relay and backup relays on lines, using
a reach1 setting and a delay timer setting2 can resolve the problems. Figure 2.10-53 exemplifies
that respective reaches and delays in the distance protection (ZS/ZG) functions result in the
coordination between the main (primary) relay and backup relays on the lines.

Busbar A Busbar B Busbar C Busbar D


G X R Y Q Z P
CTI Line AB Line BC Line CD

Zone5(X) Zone5(Y) Zone5(Z)


TZ5
Zone4(X) Zone4(Y) Zone4(Z)
TZ4

Zone3(X) Zone3(Y)
TZ3

Zone2(X) Zone2(Y) Zone2(Z)


TZ2

TZ1 Zone1(X) Zone1(Y) Zone1(Z) Reach in the forward


X R Y Q Z P
Reach in the forward TZ1
Zone1(R) Zone1(Q) Zone1(P)

TZ2
Zone2(R) Zone2(Q) Zone2(P)

TZ3
Zone3(Q) Zone3(P)
TZ4
Zone4(R) Zone4(Q) Zone4(P)
TZ5
Zone5(R) Zone5(Q)

CTI

Figure 2.10-53 Zones and time coordination between terminals3


1Note: For the ZS elements, the ‘reach’ setting is possible using the settings [Z*S-
Mho.Reach] and [Z*S-Mho.Angle] for the Mho characteristic. If the Quad
characteristic is applied, the value of the reach setting is projected on the
reactance-axis.
2Note: To realize the coordination time interval (CTI), the user can apply delay times for
the operation in respective elements. For the ZS elements, for example, use the
settings [TZ*S].
3Note: ‘Zone1’, ‘zone2’, and ‘zone3’ are zones seen by the ZS/ZG relays looking into the
forward. On the other hand, ‘zone4’ and ‘zone5’ are zones seen by the ZS/ZG relays
looking into the backward. The locations of the ZS/ZG relays are shown with
parentheses. That is, the zone1(X), which is operated at the location X, trips ‘circuit
breaker (X)’.

(i) Setting for the primary line (Zone1)


The zone1 of the ZS/ZG function can be used as a backup relay substituted into the DIF (main)

GRL200 (Soft 033 & 037)


- 145 -
6F2S1914 (0.37)

function; the operation for the zone1 shall retarded rather than the main relay. As shown in
Figure 2.10-53, the reach of the zone1(X) is required to cover the majority of the line length AB,
whereas the zone1(X) should be independent on faults that occur beyond the busbar B. Given
the existence of the measuring errors in the VT and the CT, approximate 80 to 90% of the line
AB is required to set for the reach setting at the zone1(X).

For the CTI as the backup relay, the delay timer in the zone1(X) should be set to retard.
The delay timer is programmed using the setting [TZ1S or TZ1G].

(ii) Setting for adjacent lines (Zone2 serviced as a backup relay)


The reach setting in the zone2(X) is required to cover 100% of the line AB plus about 20% of the
adjacent line BC. To preserve the operation selectivity for the adjacent line BC (i.e., the
operation in the zone1(Y)), the user should set the reach of the zone2(X) not beyond the reach of
the zone1(Y).

Note that setting TZ2(X) does not influence the CTI regarding the zone1(Y). If delayed
tripping in the zone1(X) is preferred, the CTI between the zone2(X) and the zone1(Y) should be
taken into account. Note that setting TZ2(X) should be satisfied with Equations (2.10-39) and
(2.10-40):

(𝑌) (𝑌) (𝑋)


𝑇𝑍2(𝑋) > 𝑇𝑃 + 𝑇𝐶𝐵 + 𝑇𝑍𝑜𝑛𝑒2 − 𝑇2(𝑋) (2.10-39)

𝑇𝑍2(𝑋) > 𝑇𝑍1(𝑋) (2.10-40)

where we have defined


Tp(Y): Maximum operating time in the main (primary) relay(Y),
Tcb(Y): Opening time in the circuit breaker(Y),
T2(X): Minimum operating time for the zone2(X),
TZone2(X): Reset time for the zone2(X)

Figure 2.10-54 shows that the adjacent line BC is too short so that the coordination
between the zone1(Y) and the zone2(X) is not realized straightforward. Hence, setting TZ2(X) is
required to be larger than setting TZ2(Y); consequently, the coordination between is achieved.

GRL200 (Soft 033 & 037)


- 146 -
6F2S1914 (0.37)

Busbar A Busbar B Busbar C


X Y
Line AB Line BC
CTI

Zone3(X)
TZ3
Zone2(X)
TZ2(X)

Zone2(Y)
TZ2(Y)

Zone1(X) Zone1(Y)
TZ1
X Y Reach

Figure 2.10-54 Setting zone2 when line BC is shorter than line AB


Tips: For the reach and delay settings about the CTI to the zone 2, the user is generally
required to check the selectivity that is influenced with the slowest timer of the
following protection relays: (1) Busbar, transformer, and breaker-failure relays at
the remote end and (2) line protection relay on the adjacent lines.

(iii) Setting for far adjacent lines (Zone3 serviced as a backup relay)
The zone3(X) will be served as a backup relay for far adjacent lines, if the coordination could be
satisfied with the zone2(Y); then, the user should set the reach of the zone3(x) that can cover the
remote-end of the longest adjacent line whenever possible. Note that the effect of fault infeed
should be taken into account at the remote busbars. If the line-configuration is similar to the
one in Figure 2.10-53, the user is only required to think of the coordination between the
settings TZ3(X), TZ2(X), and TZ2(Y).
Busbar A Busbar B Busbar C
X Y
Line AB Line BC

Busbar E

Line BE
CTI
Zone3(X)
TZ3(X)
Zone3(Y)
TZ3(Y)
Zone2(X)

Zone2(Y)

Zone1(X) Zone1(Y)
TZ1
X Y Reach

Figure 2.10-55 Zone3 setting when the line BC is shorter than the line BE

Figure 2.10-55 illustrates that the adjacent line BC is shorter than the adjacent line BE.
For the CTI between the adjacent lines BC and BE, if it is difficult to achieve the coordination

GRL200 (Soft 033 & 037)


- 147 -
6F2S1914 (0.37)

by using only the reach settings, the user may be required to set the TZ3(X) longer than the
TZ2(Y).

(iv) Setting for backward lines (Zones4 and 5 serviced as backup relays)
If backward adjacent lines are required to protect by the relay(X), the zone4(X) or the zone5(X) is
suitable to protect. For example, as shown in Figure 2.10-53, if setting the reach of the zone4(X)
can be performed in the reverse to cover the busbar and the transformer, the zone4(X) will
operate as a back-up relays.

(v) Extra setting for the primary zone (Zone1X with autoreclosing)
The user should notice that disadvantages exist in the CTI schemes, because a fault occurred
a bit beyond the zone1 may be cleared in delay by the zone2. That is, the zone1 plus the zone2
cannot clear speedily for any fault on the line AB†. Thus, the extra zone1 (zone1X) is designed
to clear the fault occurred near the busbar B; its operation is taken together with the operation
of the autoreclose function (ARC‡).

Busbar A Busbar B Busbar C


G X R Y Q
CTI Line AB Line BC

Zone5(X)
TZ5
Zone4(X)
TZ4
1
Zone3(X)
TZ3

Zone2(X) Zone2(Y)
TZ2

Zone1X(X)
TZ1 Zone1(X) Zone1(Y)
X Y Q Reach

Figure 2.10-56 CTIs for zone1 and zone1X

As shown in Figure 2.10-56, the reach of the zone1X should be set to overreach the
protected line AB. Once a fault occurs near busbar B, the ARC function must operate to follow
the TRIP COMMAND issued by the zone1X. The user must know that the zone1X is just
effective about the transient fault for which the ARC operation§ can recover the power
transmission.

If evolving faults occur, the zone1X will issue one-more TRIP COMMAND successively to
follow a CB reclose command issued by the ARC function. If the permanent fault occurs, the
zone1X will issue no TRIP COMMAND respond to a reclose-on-to-fault condition.

†Note:The command distance protection (DISCAR) is provided for the speedy protection

GRL200 (Soft 033 & 037)


- 148 -
6F2S1914 (0.37)

when the telecommunication is provided. See chapter Relay application:


Command distance protection.
‡Note:For more information about the ARC function, see chapter Relay application:
Autoreclosing function.
§Note:For the transient fault, the power transmission could be recovered transiently by
the operation of the ARC function, whereas the zone1X cannot operate effectively
for the permanent fault (i.e., more of the network will be lost than necessary). We
recommend one to use the DISCAR function when the DISCAR function is
available.

2.10.9 Tips to set the distance zones for multi-terminal lines


(i) Setting for reverse zones (Zone4 served as a backup relay)
Suppose multi-terminal lines (AJ, FJ, and JK) are configured behind the busbar A, as shown
in Figure 2.10-57. The line AB may be required to protect with the remote-backup relay(S or O)
together with the main (primary) relay(X). However, the zone4(W) may operate more effectively
than the zone3(S). That is, it is difficult for the zone3(S) (or the zone3(O)) to service a remote
backup relay for the line AB once a fault occurs on the line AB, because a fault current is fed
from several busbars. On the other hand, the fault current feeding will not influence the
operation of the zone4(W).
Busbar F Busbar A Line AB Busbar B
Line FJ J Line AJ
S W X
Fault
Busbar K

Line JK
O
CTI

TZ3 Zone3(S)

Zone2(S)
TZ2

TZ1 Zone1(S) Zone1(X)


S W X Reach
TZR1 Zone1(W) Zone4(W)

Figure 2.10-57 Reverse zone protection for multi-terminal lines

(ii) Setting for the primary zone (Zone1 and a junction)


Suppose that a line CJ is connected at line AB at junction J, as shown in Figure 2.10-58. The
zone1(S) may underreach due that busbar A has feeding current from the far end, whereas, the
zone1(S) is not allowed to overreach for any fault on the busbar B. Hence, the zone1(S) must be
set so that it can operate correctly for any faults within the protected zone even if a power

GRL200 (Soft 033 & 037)


- 149 -
6F2S1914 (0.37)

source does not exist behind busbar B. Accordingly, as for the fault on the line AB, the user
should have underreach setting in enough to the zone1(S).

Busbar A Busbar B
Line AJ J Line BJ CTI
S U
TZ3
Fault

Line CJ X TZ2

O TZ1 Zone1(S
Busbar C
S
TZR1
Figure 2.10-58 Line CJ tapped at junction J

(iii) Setting for the primary zone (Zone1 and a short tapped line)
Suppose the busbar C is tapped at the junction J on the line AB, as shown in Figure 2.10-59.
It is required to have the reach setting in both the zone1(S) and the zone1(U) so as to hold a
part of the entire length of the line as shown in the long-dashed-short-dashed -circle line to
avoid unwanted operations for external faults at busbar C. Consequently, clearing faults by a
delayed zone2 are performed mostly, as shown in the broken-circle line that is operated at an
end of the line AB†.

Busbar A Busbar B
Line FJ J Line AJ
S U
Line JK
O
Busbar C

Busbar A Busbar B

S U

O
Busbar C
long-dashed-short-dashed-circle line
broken-circle line
dotted-circle line

Figure 2.10-59 Short line CJ tapped at junction J


†Note:To solve the problem, we recommend using the distance carrier command
protection or the current differential protection for the multi-terminals line shown
in the dotted-circle line.

GRL200 (Soft 033 & 037)


- 150 -
6F2S1914 (0.37)

2.10.10 ZS/ZG test


(i) ZS-Test.CTRL
When the user wishes to have the relay characteristic test without the influence of the Zmin
feature, On should be set for the setting [ZS-Test.CTRL] not to operate the Zmin feature.

(ii) ZS-Offset.CTRL
As shown in Figure 2.10-60, if the offset characteristic is required during the test regardless
of the fault occurrences, the user should set Offset for the setting [ZS-Offset.CTRL]. Contrarily,
if the offset one is not required, set Non-Offset for the setting. Note that Normal shall be set
for the setting after the test.

(iii) ZS-Test.XAngle, ZG-Test.XAngle


Figure 2.10-60 illustrates that the ZS element with knee point, which can be ruled with the
angles made with θ1 and θ2. Should On-Adapt be set for setting [Z*S-X.GrAngleEN], the knee
slop can be made with θ1, which will be computed internally using a current difference
measured before and after the fault. For the test, if a fixed ‘θ1’ is preferred during the On-
Adapt has been set, the user can take the fixed ‘θ1’ by the setting [ZS-Test.XAngle]=On. Note
that fixed ‘θ1’ will be taken from setting [ZSF-X.GrAngle1] during the test.

Similarly, the user can have the take the [ZG-Test.XAngle] for the ZG element.
Reactance(X)

Knee point

Z*S-X.Reach

θ1

Offset char, θ2
Resistance(R)
Z*S-R.Reach

θ1=setting [ZSF-X.GrAngle1]
θ2=setting [ZSF-X.GrAngle2]

Figure 2.10-60 Example of ZS element with knee point

GRL200 (Soft 033 & 037)


- 151 -
6F2S1914 (0.37)

2.10.11 Setting

Distance common(Function ID: 432001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
IcC 0.00 - 0.00 - Charging current compensation for ZG and ZS
Z-IcC A 0.00 0.00
1.00 5.00
Z-Vn 100 - 120 V Rated voltage for ZG and ZS 110
Charging current compensation use or not for
Z-IcC.EN Off / On - Off
ZG and ZS
Z1 trip block when main-protection is out-of-
Z1CNT-TPBlk Off / On - Off
service
Z1 instant trip when main-protection is out-of-
Z1CNT-INSTOP Off / On - Off
service
Z1 3-phases trip when main-protection is out-
Z1CNT-3PTP Off / On - Off
of-service
arc block by Z1 operation when main-
Z1CNT-ARCBlk Off / On - Off
protection is out-of-service

GRL200 (Soft 033 & 037)


- 152 -
6F2S1914 (0.37)

ZS (Function ID: 430001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z1S-EN Off / On - Z1S protection enable Off
Z2S-EN Off / On - Z2S protection enable Off
Z3S-EN Off / On - Z3S protection enable Off
Z4S-EN Off / On - Z4S protection enable Off
Z5S-EN Off / On - Z5S protection enable Off
Z1XS-EN Off / On - Z1XS protection enable Off
Comm. ZS-Chara Quad / Mho - Selection of ZS relay character Quad
ZSF- ZS-forward gradient characteristic angle (for
0 - 45 deg 0
X.GrAngle1 Quad and Mho-X)
ZSF- ZS-forward gradient characteristic angle (for
45 - 90 deg 75
X.GrAngle2 Quad and Mho-X)
PSBS 2.50 - 0.50 -
PSBSZ - Power swing block detection 10.00 2.00
75.00 15.00
TPSBS 0.020 - 0.100 s Power swing block detection timer 0.040
PSBSFR Off / On - Power swing block reset enable On
TPSBSFR 0.00 - 10.00 s Power swing block reset timer 1.00
Power swing block reset enable when a fault
PSBSRS Off / On - Off
has occurred
LES 0.10 - 0.01 -
LESR - Minimum load resistance on the right 25.50 5.10
500.00 100.00
LESR-Angle 5 - 75 deg Maximum load angle on the right 10
0.10 - 0.01 -
LESL - Minimum load resistance on the left 25.50 5.10
500.00 100.00
LESL-Angle 5 - 75 deg Maximum load angle on the left 10
Z1S Forward / Reverse /
Z1S-Dir - Z1S directional characteristic Forward
NonDir
Mho Z1S-Mho.Angle 30 - 90 deg Z1S mho characteristic angle (for Mho) 85
0.10 - 0.01 -
Z1S-Mho.Reach - Z1S mho reach (for Mho) 8.00 1.60
500.00 100.00
Z1S-MhoX.EN Off / On - Z1S reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z1S-X.Reach - Z1S reactance reach 8.00 1.60
500.00 100.00
Z1S- Off / On-Set / On-
- ZS gradient characteristic Off
X.GrAngleEN Adapt
Z1S-MhoR.EN Off / On - Z1S resistive reach use or not (for Mho) Off
Z1S-R.Angle 30 - 90 deg Z1S resistive reach characteristic angle 75
0.10 - 0.01 -
Z1S-R.Reach - Z1S resistive reach 25.50 5.10
500.00 100.00
Z1S- Z1S directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Z1S-DX.Angle 0 - 60 deg Z1S directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z1S-X.Reach - Z1S reactance reach 8.00 1.60
500.00 100.00
Z1S- Off / On-Set / On-
- ZS gradient characteristic Off
X.GrAngleEN Adapt
Z1S-R.Angle 30 - 90 deg Z1S resistive reach characteristic angle 75
0.10 - 0.01 -
Z1S-R.Reach - Z1S resistive reach 25.50 5.10
500.00 100.00
Z1S-DX.Angle 0 - 60 deg Z1S directional-X characteristic angle 30
Z1S directional-R characteristic angle (for
Z1S-DR.Angle 0 - 60 deg 5
Quad)
TZ1S 0.00 - 100.00 s Z1S operation delay time 0.00
Z1S-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5

GRL200 (Soft 033 & 037)


153
6F2S1914 (0.37)

ZS (Function ID: 430001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Output Multi-phase or non-earth-fault condition is
Z1S-MSDET Off / On - On
used or not
Z1S-PSBBlk Non / Block - Z1S operation blocked or not by PSB detection Block
Z1S-LEBlk Non / Block - Z1S blocked or not by Load encroachment Non
Z1S-ARCBlk Non / Block - Autoreclose execution block by Z1S-trip Non
Z1S-OCFS-EN Off / On - Fail-safe OC for Z1S-trip Off
0.02 - 0.10 -
OCF1S A Fail-safe OC operation level for Z1S-trip 0.20 1.00
5.00 25.00
Z1S-SOTF Off / On - SOTF using Z1S Off
Z2S Forward / Reverse /
Z2S-Dir - Z2S directional characteristic Forward
NonDir
Mho Z2S-Mho.Angle 30 - 90 deg Z2S mho characteristic angle (for Mho) 85
0.10 - 0.01 -
Z2S-Mho.Reach - Z2S mho reach (for Mho) 20.00 4.00
500.00 100.00
Z2S-MhoX.EN Off / On - Z2S reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z2S-X.Reach - Z2S reactance reach 20.00 4.00
500.00 100.00
Z2S-MhoR.EN Off / On - Z2S resistive reach use or not (for Mho) Off
Z2S-R.Angle 30 - 90 deg Z2S resistive reach characteristic angle 75
0.10 - 0.01 -
Z2S-R.Reach - Z2S resistive reach 25.50 5.10
500.00 100.00
Z2S- Z2S directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Z2S-DX.Angle 0 - 60 deg Z2S directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z2S-X.Reach - Z2S reactance reach 20.00 4.00
500.00 100.00
Z2S-R.Angle 30 - 90 deg Z2S resistive reach characteristic angle 75
0.10 - 0.01 -
Z2S-R.Reach - Z2S resistive reach 25.50 5.10
500.00 100.00
Z2S-DX.Angle 0 - 60 deg Z2S directional-X characteristic angle 30
Z2S directional-R characteristic angle (for
Z2S-DR.Angle 0 - 60 deg 5
Quad)
TZ2S 0.00 - 100.00 s Z2S operation delay time 0.30
Output Multi-phase or non-earth-fault condition is
Z2S-MSDET Off / On - Off
used or not
Z2S-PSBBlk Non / Block - Z2S operation block or not by PSB detection Non
Z2S-LEBlk Non / Block - Z2S blocked or not by Load encroachment Non
Z2S-ARCBlk Non / Block - Autoreclose execution block by Z2S-trip Block
Z2S-OCFS-EN Off / On - Fail-safe OC for Z2S-trip Off
0.02 - 0.10 -
OCF2S A Fail-safe OC operation level for Z2S-trip 0.20 1.00
5.00 25.00
Z2S-SOTF Off / On - SOTF using Z2S Off
Z3S Forward / Reverse /
Z3S-Dir - Z3S directional characteristic Forward
NonDir
Mho Z3S-Mho.Angle 30 - 90 deg Z3S mho characteristic angle (for Mho) 85
0.10 - 0.01 -
Z3S-Mho.Reach - Z3S mho reach (for Mho) 30.00 6.00
500.00 100.00
Z3S-MhoX.EN Off / On - Z3S reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z3S-X.Reach - Z3S reactance reach 30.00 6.00
500.00 100.00
Z3S-MhoR.EN Off / On - Z3S resistive reach use or not (for Mho) Off
Z3S-R.Angle 30 - 90 deg Z3S resistive reach characteristic angle 75
0.10 - 0.01 -
Z3S-R.Reach - Z3S resistive reach 25.50 5.10
500.00 100.00

GRL200 (Soft 033 & 037)


154
6F2S1914 (0.37)

ZS (Function ID: 430001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z3S- Z3S directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Z3S-DX.Angle 0 - 60 deg Z3S directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z3S-X.Reach - Z3S reactance reach 30.00 6.00
500.00 100.00
Z3S-R.Angle 30 - 90 deg Z3S resistive reach characteristic angle 75
0.10 - 0.01 -
Z3S-R.Reach - Z3S resistive reach 25.50 5.10
500.00 100.00
Z3S-DX.Angle 0 - 60 deg Z3S directional-X characteristic angle 30
Z3S directional-R characteristic angle (for
Z3S-DR.Angle 0 - 60 deg 5
Quad)
TZ3S 0.00 - 100.00 s Z3S operation delay time 0.40
Output Multi-phase or non-earth-fault condition is
Z3S-MSDET Off / On - Off
used or not
Z3S-PSBBlk Non / Block - Z3S operation block or not by PSB detection Non
Z3S-LEBlk Non / Block - Z3S blocked or not by Load encroachment Non
Z3S-ARCBlk Non / Block - Autoreclose execution block by Z3S-trip Block
Z3S-OCFS-EN Off / On - Fail-safe OC for Z3S-trip Off
0.02 - 0.10 -
OCF3S A Fail-safe OC operation level for Z3S-trip 0.20 1.00
5.00 25.00
Z3S-SOTF Off / On - SOTF using Z3S Off
Z4S Forward / Reverse /
Z4S-Dir - Z4S directional characteristic Reverse
NonDir
Mho Z4S-Mho.Angle 30 - 90 deg Z4S mho characteristic angle (for Mho) 85
0.10 - 0.01 -
Z4S-Mho.Reach - Z4S mho reach (for Mho) 20.00 4.00
500.00 100.00
Z4S-MhoX.EN Off / On - Z4S reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z4S-X.Reach - Z4S reactance reach 20.00 4.00
500.00 100.00
Z4S-MhoR.EN Off / On - Z4S resistive reach use or not (for Mho) Off
Z4S-R.Angle 30 - 90 deg Z4S resistive reach characteristic angle 75
0.10 - 0.01 -
Z4S-R.Reach - Z4S resistive reach 25.50 5.10
500.00 100.00
Z4S- Z4S directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Z4S-DX.Angle 0 - 60 deg Z4S directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z4S-X.Reach - Z4S reactance reach 20.00 4.00
500.00 100.00
Z4S-R.Angle 30 - 90 deg Z4S resistive reach characteristic angle 75
0.10 - 0.01 -
Z4S-R.Reach - Z4S resistive reach 25.50 5.10
500.00 100.00
Z4S-DX.Angle 0 - 60 deg Z4S directional-X characteristic angle 30
Z4S directional-R characteristic angle (for
Z4S-DR.Angle 0 - 60 deg 5
Quad)
TZ4S 0.00 - 100.00 s Z4S operation delay time 0.60
Output Multi-phase or non-earth-fault condition is
Z4S-MSDET Off / On - Off
used or not
Z4S-PSBBlk Non / Block - Z4S operation block or not by PSB detection Non
Z4S-LEBlk Non / Block - Z4S blocked or not by Load encroachment Non
Z4S-ARCBlk Non / Block - Autoreclose execution block by Z4S-trip Block
Z4S-OCFS-EN Off / On - Fail-safe OC for Z4S-trip Off
0.02 - 0.10 -
OCF4S A Fail-safe OC operation level for Z4S-trip 0.20 1.00
5.00 25.00
Z4S-SOTF Off / On - SOTF using Z4S Off

GRL200 (Soft 033 & 037)


155
6F2S1914 (0.37)

ZS (Function ID: 430001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z5S Forward / Reverse /
Z5S-Dir - Z5S directional characteristic Reverse
NonDir
Mho Z5S-Mho.Angle 30 - 90 deg Z5S mho characteristic angle (for Mho) 85
0.10 - 0.01 -
Z5S-Mho.Reach - Z5S mho reach (for Mho) 10.00 2.00
500.00 100.00
Z5S-MhoX.EN Off / On - Z5S reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z5S-X.Reach - Z5S reactance reach 10.00 2.00
500.00 100.00
Z5S-MhoR.EN Off / On - Z5S resistive reach use or not (for Mho) Off
Z5S- Off / On-Set / On-
- ZS gradient characteristic Off
X.GrAngleEN Adapt
Z5S-R.Angle 30 - 90 deg Z5S resistive reach characteristic angle 75
0.10 - 0.01 -
Z5S-R.Reach - Z5S resistive reach 25.50 5.10
500.00 100.00
Z5S- Z5S directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Z5S-DX.Angle 0 - 60 deg Z5S directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z5S-X.Reach - Z5S reactance reach 10.00 2.00
500.00 100.00
Z5S- Off / On-Set / On-
- ZS gradient characteristic Off
X.GrAngleEN Adapt
Z5S-R.Angle 30 - 90 deg Z5S resistive reach characteristic angle 75
0.10 - 0.01 -
Z5S-R.Reach - Z5S resistive reach 25.50 5.10
500.00 100.00
Z5S-DX.Angle 0 - 60 deg Z5S directional-X characteristic angle 30
Z5S directional-R characteristic angle (for
Z5S-DR.Angle 0 - 60 deg 5
Quad)
TZ5S 0.00 - 100.00 s Z5S operation delay time 0.50
Z5S-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output Multi-phase or non-earth-fault condition is
Z5S-MSDET Off / On - Off
used or not
Z5S-PSBBlk Non / Block - Z5S operation block or not by PSB detection Non
Z5S-LEBlk Non / Block - Z5S blocked or not by Load encroachment Non
Z5S-ARCBlk Non / Block - Autoreclose execution block by Z5S-trip Block
Z5S-OCFS-EN Off / On - Fail-safe OC for Z5S-trip Off
0.02 - 0.10 -
OCF5S A Fail-safe OC operation level for Z5S-trip 0.20 1.00
5.00 25.00
Z5S-SOTF Off / On - SOTF using Z5S Off
Z1XS Forward / Reverse /
Z1XS-Dir - Z1XS directional characteristic Forward
NonDir
Mho Z1XS-
30 - 90 deg Z1XS mho characteristic angle (for Mho) 85
Mho.Angle
Z1XS- 0.10 - 0.01 -
- Z1XS mho reach (for Mho) 12.00 2.40
Mho.Reach 500.00 100.00
Z1XS-
Off / On - Z1XS reactance reach use or not (for Mho) Off
MhoX.EN
0.10 - 0.01 -
Z1XS-X.Reach - Z1XS reactance reach 12.00 2.40
500.00 100.00
Z1XS- Off / On-Set / On-
- ZS gradient characteristic Off
X.GrAngleEN Adapt
Z1XS-R.Angle 30 - 90 deg Z1XS resistive reach characteristic angle 75
0.10 - 0.01 -
Z1XS-R.Reach - Z1XS resistive reach 25.50 5.10
500.00 100.00

GRL200 (Soft 033 & 037)


156
6F2S1914 (0.37)

ZS (Function ID: 430001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z1XS-
Off / On - Z1XS resistive reach use or not (for Mho) Off
MhoR.EN
Z1XS-R.Angle 30 - 90 deg Z1XS resistive reach characteristic angle 75
0.10 - 0.01 -
Z1XS-R.Reach - Z1XS resistive reach 25.50 5.10
500.00 100.00
Z1XS- Z1XS directional-X characteristic use or not
Off / On - Off
MhoDX.EN (for Mho)
Z1XS-DX.Angle 0 - 60 deg Z1XS directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z1XS-X.Reach - Z1XS reactance reach 12.00 2.40
500.00 100.00
Z1XS- Off / On-Set / On-
- ZS gradient characteristic Off
X.GrAngleEN Adapt
Z1XS-R.Angle 30 - 90 deg Z1XS resistive reach characteristic angle 75
0.10 - 0.01 -
Z1XS-R.Reach - Z1XS resistive reach 25.50 5.10
500.00 100.00
Z1XS-DX.Angle 0 - 60 deg Z1XS directional-X characteristic angle 30
Z1XS directional-R characteristic angle (for
Z1XS-DR.Angle 0 - 60 deg 5
Quad)
TZ1XS 0.00 - 100.00 s Z1XS operation delay time 0.00
Z1XS-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output Multi-phase or non-earth-fault condition is
Z1XS-MSDET Off / On - On
used or not
Z1XS-PSBBlk Non / Block - Z1XS operation block or not by PSB detection Block
Z1XS-LEBlk Non / Block - Z1XS blocked or not by Load encroachment Non
Z1XS-ARCBlk Non / Block - Autoreclose execution block by Z1XS-trip Non
Z1XS-OCFS-
Off / On - Fail-safe OC for Z1XS-trip Off
EN
0.10 -
OCF1XS 0.02 - 5.00 A Fail-safe OC operation level for Z1XS-trip 0.20 1.00
25.00
Z1XS-SOTF Off / On - SOTF using Z1XS Off
Note 1: On-Adapt is only applicable when Forward is set for ZS.
Note 2: When On-Adapt is set for the scheme switch [Z*S-X.GrAngleEN], the setting
value [ZSF-X.GrAngle1] will be calculated by itself. However, the user should
enter a value for [ZSF-X.GrAngle2] regardless of the setting of the [ZS-
X.GrAngleEN].

GRL200 (Soft 033 & 037)


157
6F2S1914 (0.37)

ZCS (Function ID: 430001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ZCS-EN Off / On - ZCS scheme swtich Off
Comm. ZCS-LEBlk Non / Block - ZCS LE block switch Non
ZCSF Mho ZCSF-
30 - 90 deg ZCSF mho characteristic angle (for Mho) 85
Mho.Angle
ZCSF- 0.10 - 0.01 -
- ZCSF mho reach (for Mho) 30.00 6.00
Mho.Reach 500.00 100.00
MhoX ZCSF-
Off / On - ZCSF reactance reach use or not (for Mho) Off
MhoX.EN
0.10 - 0.01 -
ZCSF-X.Reach - ZCSF reactance reach 30.00 6.00
500.00 100.00
MhoR ZCSF-
Off / On - ZCSF resistive reach use or not (for Mho) Off
MhoR.EN
ZCSF-R.Angle 30 - 90 deg ZCSF resistive reach characteristic angle 75
0.10 - 0.01 -
ZCSF-R.Reach - ZCSF resistive reach 25.50 5.10
500.00 100.00
MhoDX ZCSF- ZCSF directional-X characteristic use or not
Off / On - Off
MhoDX.EN (for Mho)
ZCSF-
0 - 60 deg ZCSF directional-X characteristic angle 30
DX.Angle
ZCSF-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output ZCSF-PSBBlk Non / Block - ZCSF operation block or not by PSB detection Block
ZCSR Mho ZCSR-
30 - 90 deg ZCSR mho characteristic angle (for Mho) 85
Mho.Angle
ZCSR- 0.10 - 0.01 -
- ZCSR mho reach (for Mho) 40.00 8.00
Mho.Reach 500.00 100.00
MhoX ZCSR-
Off / On - ZCSR reactance reach use or not (for Mho) Off
MhoX.EN
0.10 - 0.01 -
ZCSR-X.Reach - ZCSR reactance reach 40.00 8.00
500.00 100.00
MhoR ZCSR-
Off / On - ZCSR resistive reach use or not (for Mho) Off
MhoR.EN
ZCSR-R.Angle 30 - 90 deg ZCSR resistive reach characteristic angle 75
0.10 - 0.01 -
ZCSR-R.Reach - ZCSR resistive reach 25.50 5.10
500.00 100.00
MhoDX ZCSR- ZCSR directional-X characteristic use or not
Off / On - Off
MhoDX.EN (for Mho)
ZCSR-
0 - 60 deg ZCSR directional-X characteristic angle 30
DX.Angle
ZCSR-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output ZCSR-VTFBlk Non / Block - ZCSR operation block or not by VTF detection Block
ZCSF Quad 0.10 - 0.01 -
ZCSF-X.Reach - ZCSF reactance reach 30.00 6.00
500.00 100.00
ZCSF-R.Angle 30 - 90 deg ZCSF resistive reach characteristic angle 75
0.10 - 0.01 -
ZCSF-R.Reach - ZCSF resistive reach 25.50 5.10
500.00 100.00
ZCSF-
0 - 60 deg ZCSF directional-X characteristic angle 30
DX.Angle
ZCSF- ZCSF directional-R characteristic angle (for
0 - 60 deg 5
DR.Angle Quad)
ZCSF-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output ZCSF-PSBBlk Non / Block - ZCSF operation block or not by PSB detection Block
ZCSR Quad 0.10 - 0.01 -
ZCSR-X.Reach - ZCSR reactance reach 40.00 8.00
500.00 100.00
ZCSR-R.Angle 30 - 90 deg ZCSR resistive reach characteristic angle 75

GRL200 (Soft 033 & 037)


158
6F2S1914 (0.37)

ZCS (Function ID: 430001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
0.10 - 0.01 -
ZCSR-R.Reach - ZCSR resistive reach 25.50 5.10
500.00 100.00
ZCSR-
0 - 60 deg ZCSR directional-X characteristic angle 30
DX.Angle
ZCSR- ZCSR directional-R characteristic angle (for
0 - 60 deg 5
DR.Angle Quad)
Output ZCSR-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5

GRL200 (Soft 033 & 037)


159
6F2S1914 (0.37)

ZG (Function ID: 431001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z1G-EN Off / On - Z1G protection enable Off
Z2G-EN Off / On - Z2G protection enable Off
Z3G-EN Off / On - Z3G protection enable Off
Z4G-EN Off / On - Z4G protection enable Off
Z5G-EN Off / On - Z5G protection enable Off
Z1XG-EN Off / On - Z1XG protection enable Off
Comm. ZG-Chara Quad / Mho - ZG relay characteristic Quad
ZGF- ZG-forward gradient characteristic angle (for
0 - 45 deg 0
X.GrAngle1 Quad and Mho-X)
ZGF- ZG-forward gradient characteristic angle (for
45 - 90 deg 60
X.GrAngle2 Quad and Mho-X)
PSB 2.50 - 0.50 -
PSBGZ - Power swing block detection 10.00 2.00
75.00 15.00
TPSBG 0.020 - 0.100 s Power swing block detection timer 0.040
PSBGFR Off / On - Power swing block reset enable Off
TPSBGFR 0.00 - 10.00 s Power swing block reset timer 1.00
LEG 0.10 - 0.01 -
LEGR - Minimum load resistance on the right 25.50 5.10
500.00 100.00
LEGR-Angle 5 - 75 deg Maximum load angle on the right 10
0.10 - 0.01 -
LEGL - Minimum load resistance on the left 25.50 5.10
500.00 100.00
LEGL-Angle 5 - 75 deg Maximum load angle on the left 10
EFL 0.50 -
EFL 0.10 - 1.00 A EFL threshold 0.20 1.00
5.00
UVPWI ZG-UVPWI-EN Off / On - UV for positive weak infeed Off
UVPWI 5.0 - 130.0 V UVPWI relay operation level 30.0
Z1G Forward / Reverse /
Z1G-Dir - Z1G direction to protect Forward
NonDir
Mho Z1G-Mho.Angle 30 - 90 deg Z1G mho characteristic angle (for Mho) 85
Z1G- 0.10 - 0.01 -
- Z1G mho reach (for Mho) 8.00 1.60
Mho.Reach 500.00 100.00
Z1G-MhoX.EN Off / On - Z1G reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z1G-X.Reach - Z1G reactance reach 8.00 1.60
500.00 100.00
Z1G-MhoR.EN Off / On - Z1G resistive reach use or not (for Mho) Off
Z1G-R.Angle 30 - 90 deg Z1G resistive reach characteristic angle 75
0.10 - 0.01 -
Z1G-R.Reach - Z1G resistive reach 25.50 5.10
500.00 100.00
Z1G- Z1G directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Z1G-DX.Angle 0 - 60 deg Z1G directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z1G-X.Reach - Z1G reactance reach 8.00 1.60
500.00 100.00
Z1G- Off / On-Set / On-
- ZG gradient characteristic Off
X.GrAngleEN Adapt
Z1G-R.Angle 30 - 90 deg Z1G resistive reach characteristic angle 75
0.10 - 0.01 -
Z1G-R.Reach - Z1G resistive reach 25.50 5.10
500.00 100.00
Z1G-DX.Angle 0 - 60 deg Z1G directional-X characteristic angle 30
Z1G directional-R characteristic angle (for
Z1G-DR.Angle 0 - 60 deg 5
Quad)
I0K Z1G-Krs 0 - 1000 % Zero phase current factor, Self line R0/R1 100
Z1G-Kxs 0 - 1000 % Zero phase current factor, Self line X0/X1 100

GRL200 (Soft 033 & 037)


- 160 -
6F2S1914 (0.37)

ZG (Function ID: 431001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Zero phase current factor, Adjacent line
Z1G-Krm 0 - 1000 % 0
R0m/R1
Zero phase current factor, Adjacent line
Z1G-Kxm 0 - 1000 % 0
X0m/X1
TZ1G 0.00 - 100.00 s Z1G operation delay time 0.00
Z1G-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output EFL operation condition used or not for Z1G
Z1G-EFL Off / On - On
operation
Z1G-MPFBlk Non / Block - Z1G operation block or not in multi phase fault Block
Z1G-PSBBlk Non / Block - Z1G operation block or not by PSB detection Block
Z1G-LEBlk Non / Block - Load encroachment enable Non
Z1G-LPBlk Non / Block - Z1G leading phase operation block Non
Z1G trip mode, phase segregated trip or 3-
Z1G-TPMD 1P / 3P - 1P
phase trip
Z1G-ARCBlk Non / Block - Autoreclose execution block by Z1G-trip Non
Z1G-OCFS-EN Off / On - Fail-safe OC for Z1G-trip Off
0.10 -
OCF1G 0.02 - 5.00 A Fail-safe OC operation level for Z1G-trip 0.20 1.00
25.00
Z1G-SOTF Off / On - SOTF using Z1G Off
Z2G Forward / Reverse /
Z2G-Dir - Z2G direction to protect Forward
NonDir
Mho Z2G-Mho.Angle 30 - 90 deg Z2G mho characteristic angle (for Mho) 85
Z2G- 0.10 - 0.01 -
- Z2G mho reach (for Mho) 20.00 4.00
Mho.Reach 500.00 100.00
Z2G-MhoX.EN Off / On - Z2G reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z2G-X.Reach - Z2G reactance reach 20.00 4.00
500.00 100.00
Z2G-MhoR.EN Off / On - Z2G resistive reach use or not (for Mho) Off
Z2G-R.Angle 30 - 90 deg Z2G resistive reach characteristic angle 75
0.10 - 0.01 -
Z2G-R.Reach - Z2G resistive reach 25.50 5.10
500.00 100.00
Z2G- Z2G directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Z2G-DX.Angle 0 - 60 deg Z2G directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z2G-X.Reach - Z2G reactance reach 20.00 4.00
500.00 100.00
Z2G-R.Angle 30 - 90 deg Z2G resistive reach characteristic angle 75
0.10 - 0.01 -
Z2G-R.Reach - Z2G resistive reach 25.50 5.10
500.00 100.00
Z2G-DX.Angle 0 - 60 deg Z2G directional-X characteristic angle 30
Z2G directional-R characteristic angle (for
Z2G-DR.Angle 0 - 60 deg 5
Quad)
I0K Z2G-Krs 0 - 1000 % Zero phase current factor, Self line R0/R1 100
Z2G-Kxs 0 - 1000 % Zero phase current factor, Self line X0/X1 100
Zero phase current factor, Adjacent line
Z2G-Krm 0 - 1000 % 0
R0m/R1
Zero phase current factor, Adjacent line
Z2G-Kxm 0 - 1000 % 0
X0m/X1
TZ2G 0.00 - 100.00 s Z2G operation delay time 0.30
Output EFL operation condition used or not for Z2G
Z2G-EFL Off / On - On
operation
Z2G-MPFBlk Non / Block - Z2G operation block or not in multi phase fault Non
Z2G-PSBBlk Non / Block - Z2G operation block or not by PSB detection Non
Z2G-LEBlk Non / Block - Load encroachment enable Non

GRL200 (Soft 033 & 037)


- 161 -
6F2S1914 (0.37)

ZG (Function ID: 431001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z2G-LPBlk Non / Block - Z2G leading phase operation block Non
Z2G trip mode, phase segregated trip or 3-
Z2G-TPMD 1P / 3P - 3P
phase trip
Z2G-ARCBlk Non / Block - Autoreclose execution block by Z2G-trip Block
Z2G-OCFS-EN Off / On - Fail-safe OC for Z2G-trip Off
0.10 -
OCF2G 0.02 - 5.00 A Fail-safe OC operation level for Z2G-trip 0.20 1.00
25.00
Z2G-SOTF Off / On - SOTF using Z2G Off
Z3G Forward / Reverse /
Z3G-Dir - Z3G direction to protect Forward
NonDir
Mho Z3G-Mho.Angle 30 - 90 deg Z3G mho characteristic angle (for Mho) 85
Z3G- 0.10 - 0.01 -
- Z3G mho reach (for Mho) 40.00 8.00
Mho.Reach 500.00 100.00
Z3G-MhoX.EN Off / On - Z3G reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z3G-X.Reach - Z3G reactance reach 40.00 8.00
500.00 100.00
Z3G-MhoR.EN Off / On - Z3G resistive reach use or not (for Mho) Off
Z3G-R.Angle 30 - 90 deg Z3G resistive reach characteristic angle 75
0.10 - 0.01 -
Z3G-R.Reach - Z3G resistive reach 25.50 5.10
500.00 100.00
Z3G-DX.Angle 0 - 60 deg Z3G directional-X characteristic angle 30
Z3G- Z3G directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Quad 0.10 - 0.01 -
Z3G-X.Reach - Z3G reactance reach 40.00 8.00
500.00 100.00
Z3G-R.Angle 30 - 90 deg Z3G resistive reach characteristic angle 75
0.10 - 0.01 -
Z3G-R.Reach - Z3G resistive reach 25.50 5.10
500.00 100.00
Z3G-DX.Angle 0 - 60 deg Z3G directional-X characteristic angle 30
Z3G directional-R characteristic angle (for
Z3G-DR.Angle 0 - 60 deg 5
Quad)
I0K Z3G-Krs 0 - 1000 % Zero phase current factor, Self line R0/R1 100
Z3G-Kxs 0 - 1000 % Zero phase current factor, Self line X0/X1 100
Zero phase current factor, Adjacent line
Z3G-Krm 0 - 1000 % 0
R0m/R1
Zero phase current factor, Adjacent line
Z3G-Kxm 0 - 1000 % 0
X0m/X1
TZ3G 0.00 - 100.00 s Z3G operation delay time 0.40
Output EFL operation condition used or not for Z3G
Z3G-EFL Off / On - On
operation
Z3G-MPFBlk Non / Block - Z3G operation block or not in multi phase fault Non
Z3G-PSBBlk Non / Block - Z3G operation block or not by PSB detection Non
Z3G-LEBlk Non / Block - Load encroachment enable Non
Z3G-LPBlk Non / Block - Z3G leading phase operation block Non
Z3G trip mode, phase segregated trip or 3-
Z3G-TPMD 1P / 3P - 3P
phase trip
Z3G-ARCBlk Non / Block - Autoreclose execution block by Z3G-trip Block
Z3G-OCFS-EN Off / On - Fail-safe OC for Z3G-trip Off
0.10 -
OCF3G 0.02 - 5.00 A Fail-safe OC operation level for Z3G-trip 0.20 1.00
25.00
Z3G-SOTF Off / On - SOTF using Z3G Off
Z4G Forward / Reverse /
Z4G-Dir - Z4G direction to protect Reverse
NonDir
Mho Z4G-Mho.Angle 30 - 90 deg Z4G mho characteristic angle (for Mho) 85

GRL200 (Soft 033 & 037)


- 162 -
6F2S1914 (0.37)

ZG (Function ID: 431001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z4G- 0.10 - 0.01 -
- Z4G mho reach (for Mho) 20.00 4.00
Mho.Reach 500.00 100.00
Z4G-MhoX.EN Off / On - Z4G reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z4G-X.Reach - Z4G reactance reach 20.00 4.00
500.00 100.00
Z4G-MhoR.EN Off / On - Z4G resistive reach use or not (for Mho) Off
Z4G-R.Angle 30 - 90 deg Z4G resistive reach characteristic angle 75
0.10 - 0.01 -
Z4G-R.Reach - Z4G resistive reach 25.50 5.10
500.00 100.00
Z4G- Z4G directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)
Z4G-DX.Angle 0 - 60 deg Z4G directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z4G-X.Reach - Z4G reactance reach 20.00 4.00
500.00 100.00
Z4G-R.Angle 30 - 90 deg Z4G resistive reach characteristic angle 75
0.10 - 0.01 -
Z4G-R.Reach - Z4G resistive reach 25.50 5.10
500.00 100.00
Z4G-DX.Angle 0 - 60 deg Z4G directional-X characteristic angle 30
Z4G directional-R characteristic angle (for
Z4G-DR.Angle 0 - 60 deg 5
Quad)
I0K Z4G-Krs 0 - 1000 % Zero phase current factor, Self line R0/R1 100
Z4G-Kxs 0 - 1000 % Zero phase current factor, Self line X0/X1 100
Zero phase current factor, Adjacent line
Z4G-Krm 0 - 1000 % 0
R0m/R1
Zero phase current factor, Adjacent line
Z4G-Kxm 0 - 1000 % 0
X0m/X1
EFL operation condition used or not for Z4G
Z4G-EFL Off / On - On
operation
TZ4G 0.00 - 100.00 s Z4G operation delay time 0.60
Output Z4G-MPFBlk Non / Block - Z4G operation block or not in multi phase fault Non
Z4G-PSBBlk Non / Block - Z4G operation block or not by PSB detection Non
Z4G-LEBlk Non / Block - Load encroachment enable Non
Z4G-LPBlk Non / Block - Z4G leading phase operation block Non
Z4G trip mode, phase segregated trip or 3-
Z4G-TPMD 1P / 3P - 3P
phase trip
Z4G-ARCBlk Non / Block - Autoreclose execution block by Z4G-trip Block
Z4G-OCFS-EN Off / On - Fail-safe OC for Z4G-trip Off
0.10 -
OCF4G 0.02 - 5.00 A Fail-safe OC operation level for Z4G-trip 0.20 1.00
25.00
Z4G-SOTF Off / On - SOTF using Z4G Off
Z5G Forward / Reverse /
Z5G-Dir - Z5G direction to protect Reverse
NonDir
Mho Z5G-Mho.Angle 30 - 90 deg Z5G mho characteristic angle (for Mho) 85
Z5G- 0.10 - 0.01 -
- Z5G mho reach (for Mho) 10.00 2.00
Mho.Reach 500.00 100.00
Z5G-MhoX.EN Off / On - Z5G reactance reach use or not (for Mho) Off
0.10 - 0.01 -
Z5G-X.Reach - Z5G reactance reach 10.00 2.00
500.00 100.00
Z5G-MhoR.EN Off / On - Z5G resistive reach use or not (for Mho) Off
Z5G-R.Angle 30 - 90 deg Z5G resistive reach characteristic angle 75
0.10 - 0.01 -
Z5G-R.Reach - Z5G resistive reach 25.50 5.10
500.00 100.00
Z5G- Z5G directional-X characteristic use or not (for
Off / On - Off
MhoDX.EN Mho)

GRL200 (Soft 033 & 037)


- 163 -
6F2S1914 (0.37)

ZG (Function ID: 431001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z5G-DX.Angle 0 - 60 deg Z5G directional-X characteristic angle 30
Quad 0.10 - 0.01 -
Z5G-X.Reach - Z5G reactance reach 10.00 2.00
500.00 100.00
Z5G- Off / On-Set / On-
- ZG gradient characteristic Off
X.GrAngleEN Adapt
Z5G-R.Angle 30 - 90 deg Z5G resistive reach characteristic angle 75
0.10 - 0.01 -
Z5G-R.Reach - Z5G resistive reach 25.50 5.10
500.00 100.00
Z5G-DX.Angle 0 - 60 deg Z5G directional-X characteristic angle 30
Z5G directional-R characteristic angle (for
Z5G-DR.Angle 0 - 60 deg 5
Quad)
I0K Z5G-Krs 0 - 1000 % Zero phase current factor, Self line R0/R1 100
Z5G-Kxs 0 - 1000 % Zero phase current factor, Self line X0/X1 100
Zero phase current factor, Adjacent line
Z5G-Krm 0 - 1000 % 0
R0m/R1
Zero phase current factor, Adjacent line
Z5G-Kxm 0 - 1000 % 0
X0m/X1
TZ5G 0.00 - 100.00 s Z5G operation delay time 0.50
Z5G-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output EFL operation condition used or not for Z5G
Z5G-EFL Off / On - On
operation
Z5G-MPFBlk Non / Block - Z5G operation block or not in multi phase fault Non
Z5G-PSBBlk Non / Block - Z5G operation block or not by PSB detection Non
Z5G-LEBlk Non / Block - Load encroachment enable Non
Z5G-LPBlk Non / Block - Z5G leading phase operation block Non
Z5G trip mode, phase segregated trip or 3-
Z5G-TPMD 1P / 3P - 3P
phase trip
Z5G-ARCBlk Non / Block - Autoreclose execution block by Z5G-trip Block
Z5G-OCFS-EN Off / On - Fail-safe OC for Z5G-trip Off
0.10 -
OCF5G 0.02 - 5.00 A Fail-safe OC operation level for Z5G-trip 0.20 1.00
25.00
Z5G-SOTF Off / On - SOTF using Z5G Off
Z1XG Forward / Reverse /
Z1XG-Dir - Z1XG direction to protect Forward
NonDir
Mho Z1XG-
30 - 90 deg Z1XG mho characteristic angle (for Mho) 85
Mho.Angle
Z1XG- 0.10 - 0.01 -
- Z1XG mho reach (for Mho) 12.00 2.40
Mho.Reach 500.00 100.00
Z1XG-
Off / On - Z1XG reactance reach use or not (for Mho) Off
MhoX.EN
0.10 - 0.01 -
Z1XG-X.Reach - Z1XG reactance reach 12.00 2.40
500.00 100.00
Z1XG-
Off / On - Z1XG resistive reach use or not (for Mho) Off
MhoR.EN
Z1XG-R.Angle 30 - 90 deg Z1XG resistive reach characteristic angle 75
0.10 - 0.01 -
Z1XG-R.Reach - Z1XG resistive reach 25.50 5.10
500.00 100.00
Z1XG- Z1XG directional-X characteristic use or not
Off / On - Off
MhoDX.EN (for Mho)
Z1XG-
0 - 60 deg Z1XG directional-X characteristic angle 30
DX.Angle
Quad 0.10 - 0.01 -
Z1XG-X.Reach - Z1XG reactance reach 12.00 2.40
500.00 100.00

GRL200 (Soft 033 & 037)


- 164 -
6F2S1914 (0.37)

ZG (Function ID: 431001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Z1XG- Off / On-Set / On-
- ZG gradient characteristic Off
X.GrAngleEN Adapt
Z1XG-R.Angle 30 - 90 deg Z1XG resistive reach characteristic angle 75
0.10 - 0.01 -
Z1XG-R.Reach - Z1XG resistive reach 25.50 5.10
500.00 100.00
Z1XG-
0 - 60 deg Z1XG directional-X characteristic angle 30
DX.Angle
Z1XG- Z1XG directional-R characteristic angle (for
0 - 60 deg 5
DR.Angle Quad)
I0K Z1XG-Krs 0 - 1000 % Zero phase current factor, Self line R0/R1 100
Z1XG-Kxs 0 - 1000 % Zero phase current factor, Self line X0/X1 100
Zero phase current factor, Adjacent line
Z1XG-Krm 0 - 1000 % 0
R0m/R1
Zero phase current factor, Adjacent line
Z1XG-Kxm 0 - 1000 % 0
X0m/X1
TZ1XG 0.00 - 100.00 s Z1XG operation delay time 0.00
Z1XG-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output EFL operation condition used or not for Z1XG
Z1XG-EFL Off / On - On
operation
Z1XG operation block or not in multi phase
Z1XG-MPFBlk Non / Block - Block
fault
Z1XG-PSBBlk Non / Block - Z1XG operation block or not by PSB detection Block
Z1XG-LEBlk Non / Block - Load encroachment enable Non
Z1XG-LPBlk Non / Block - Z1XG leading phase operation block Non
Z1XG trip mode, phase segregated trip or 3-
Z1XG-TPMD 1P / 3P - 1P
phase trip
Z1XG-ARCBlk Non / Block - Autoreclose execution block by Z1XG-trip Non
Z1XG-OCFS-
Off / On - Fail-safe OC for Z1XG-trip Off
EN
0.10 -
OCF1XG 0.02 - 5.00 A Fail-safe OC operation level for Z1XG-trip 0.20 1.00
25.00
Z1XG-SOTF Off / On - SOTF using Z1XG Off
Note 1: On-Adapt is only applicable when Forward is set for ZG. If On-Adapt is set
for Reverse operation, it is necessary to set scheme switch [ZG-X.GrAngleEN]=Off.
Note 2: When On-Adapt is set for scheme switch [ZG-X.GrAngleEN], the setting
value [ZGF-X.GrAngle1] will be calculated by itself. However, the user should set
a value be set for [ZGF-X.GrAngle2] regardless of the setting of scheme switch
[ZG-X.GrAngleEN

GRL200 (Soft 033 & 037)


- 165 -
6F2S1914 (0.37)

ZCG (Function ID: 431001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ZCG-EN Off / On - ZCG scheme switch Off
ZCG-
Commo ZCG-LEBlk Non / Block - Load encroachment enable Non
n
ZCGF Mho ZCGF-
30 - 90 deg ZCGF mho characteristic angle (for Mho) 85
Mho.Angle
ZCGF- 0.10 - 0.01 -
- ZCGF mho reach (for Mho) 40.00 8.00
Mho.Reach 500.00 100.00
ZCGF-
Off / On - ZCGF reactance reach use or not (for Mho) Off
MhoX.EN
0.10 - 0.01 -
ZCGF-X.Reach - ZCGF reactance reach 40.00 8.00
500.00 100.00
ZCGF-
Off / On - ZCGF resistive reach use or not (for Mho) Off
MhoR.EN
ZCGF-R.Angle 30 - 90 deg ZCGF resistive reach characteristic angle 75
0.10 - 0.01 -
ZCGF-R.Reach - ZCGF resistive reach 25.50 5.10
500.00 100.00
ZCGF- ZCGF directional-X characteristic use or not
Off / On - Off
MhoDX.EN (for Mho)
ZCGF-
0 - 60 deg ZCGF directional-X characteristic angle 30
DX.Angle
Quad 0.10 - 0.01 -
ZCGF-X.Reach - ZCGF reactance reach 40.00 8.00
500.00 100.00
ZCGF-R.Angle 30 - 90 deg ZCGF resistive reach characteristic angle 75
0.10 - 0.01 -
ZCGF-R.Reach - ZCGF resistive reach 25.50 5.10
500.00 100.00
ZCGF-
0 - 60 deg ZCGF directional-X characteristic angle 30
DX.Angle
ZCGF- ZCGF directional-R characteristic angle (for
0 - 60 deg 5
DR.Angle Quad)
I0K ZCGF-Krs 0 - 1000 % Zero phase current factor, Self line R0/R1 100
ZCGF-Kxs 0 - 1000 % Zero phase current factor, Self line X0/X1 100
Zero phase current factor, Adjacent line
ZCGF-Krm 0 - 1000 % 0
R0m/R1
Zero phase current factor, Adjacent line
ZCGF-Kxm 0 - 1000 % 0
X0m/X1
ZCGF-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output ZCGF-PSBBlk Non / Block - ZCGF operation block or not by PSB detection Block
ZCGR Mho ZCGR-
30 - 90 deg ZCGR mho characteristic angle (for Mho) 85
Mho.Angle
ZCGR- 0.10 - 0.01 -
- ZCGR mho reach (for Mho) 40.00 8.00
Mho.Reach 500.00 100.00
ZCGR-
Off / On - ZCGR reactance reach use or not (for Mho) Off
MhoX.EN
0.10 - 0.01 -
ZCGR-X.Reach - ZCGR reactance reach 40.00 8.00
500.00 100.00
ZCGR-
Off / On - ZCGR resistive reach use or not (for Mho) Off
MhoR.EN
ZCGR-R.Angle 30 - 90 deg ZCGR resistive reach characteristic angle 75
0.10 - 0.01 -
ZCGR-R.Reach - ZCGR resistive reach 25.50 5.10
500.00 100.00
ZCGR- ZCGR directional-X characteristic use or not
Off / On - Off
MhoDX.EN (for Mho)

GRL200 (Soft 033 & 037)


- 166 -
6F2S1914 (0.37)

ZCG (Function ID: 431001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ZCGR-
0 - 60 deg ZCGR directional-X characteristic angle 30
DX.Angle
Quad 0.10 - 0.01 -
ZCGR-X.Reach - ZCGR reactance reach 40.00 8.00
500.00 100.00
ZCGR-R.Angle 30 - 90 deg ZCGR resistive reach characteristic angle 75
0.10 - 0.01 -
ZCGR-R.Reach - ZCGR resistive reach 25.50 5.10
500.00 100.00
ZCGR-R.Angle 30 - 90 deg ZCGR resistive reach characteristic angle 75
0.10 - 0.01 -
ZCGR-R.Reach - ZCGR resistive reach 25.50 5.10
500.00 100.00
ZCGR-
0 - 60 deg ZCGR directional-X characteristic angle 30
DX.Angle
ZCGR- ZCGR directional-R characteristic angle (for
0 - 60 deg 5
DR.Angle Quad)
I0K ZCGR-Krs 0 - 1000 % Zero phase current factor, Self line R0/R1 100
ZCGR-Kxs 0 - 1000 % Zero phase current factor, Self line X0/X1 100
Zero phase current factor, Adjacent line
ZCGR-Krm 0 - 1000 % 0
R0m/R1
Zero phase current factor, Adjacent line
ZCGR-Kxm 0 - 1000 % 0
X0m/X1
ZCGR-CovCoeff 1.5 - 10.0 - Covered characteristic size coefficient 1.5
Output ZCGR-VTFBlk Non / Block - ZCGR operation block or not by VTF detection Block

Test tool (Function ID: 430001)

Unit Default setting


Items Range Contents Notes
s value

Function test
ZS-Test.CTRL Off/On – ZS-test mode Off/On selection Off
ZS-Test.XAngle Off/On – ZS-reactance test mode Off/On selection Off

Test tool(Function ID: 431001)

Unit Default setting


Item Range Contents Notes
s value

Function test
ZG-Test.XAngle Off/On – ZG-reactance test mode Off/On selection Off

GRL200 (Soft 033 & 037)


- 167 -
6F2S1914 (0.37)

2.10.12 Data ID
 Signal monitoring point
ZS ZG Common (Function ID: 432001)
Element ID Name Description
8300001C27 EFL Earth fault relay element operated

8000001C20 OCCR-A OCCR relay element operated(phase-A)

8100001C21 OCCR-B OCCR relay element operated(phase-B)

8200001C22 OCCR-C OCCR relay element operated(phase-C)

8100001B63 Z1CNT-3PTP Z1 control command (3-phase trip)

8200001B64 Z1CNT-ARCBLK Z1 control command (Autoreclose block)

8300001B65 Z1CNT-INSTOP Z1 control command (Instantaneous operation)

8000001B62 Z1CNT-TPBLK Z1 control command (Trip block)

8000001BB0 Z1CNT_MPROT Z1 control signal for multi protection

 Connection point on PLC logic


ZS ZG Common (Function ID: 432001)
Element ID Name Description
800000EBB0 Z1CNT_MPROT Z1 control setting for multi protection

GRL200 (Soft 033 & 037)


- 168 -
6F2S1914 (0.37)

 Signal monitoring point


ZS (Function ID: 430001)
Element ID Name Description
8000081B6E LD_ENC-AB Load encroachment operated (phase-AB)

8100081B6F LD_ENC-BC Load encroachment operated (phase-BC)

8200081B70 LD_ENC-CA Load encroachment operated (phase-CA)

8000081B6B LES-L A LES-L relay element operated (phase-AB)

8100081B6C LES-L B LES-L relay element operated (phase-BC)

8200081B6D LES-L C LES-L relay element operated (phase-CA)

8000081B68 LES-R A LES-R relay element operated (phase-AB)

8100081B69 LES-R B LES-R relay element operated (phase-BC)

8200081B6A LES-R C LES-R relay element operated (phase-CA)

8000011B64 OCF1S OP OCF1S operated

8000011C24 OCF1S-AB OCF1S relay element operated (phase-AB)

8100011C25 OCF1S-BC OCF1S relay element operated (phase-BC)

8200011C26 OCF1S-CA OCF1S relay element operated (phase-CA)

8100061B64 OCF1XS OP OCF1XS element operated

8400061C24 OCF1XS-AB OCF1XS relay element operated (phase-AB)

8500061C25 OCF1XS-BC OCF1XS relay element operated (phase-BC)

8600061C26 OCF1XS-CA OCF1XS relay element operated (phase-CA)

8200021B64 OCF2S OP OCF2S operated

8000021C24 OCF2S-AB OCF2S relay element operated (phase-AB)

8100021C25 OCF2S-BC OCF2S relay element operated (phase-BC)

8200021C26 OCF2S-CA OCF2S relay element operated (phase-CA)

8300031B64 OCF3S OP OCF2S operated

8400031C24 OCF3S-AB OCF2S relay element operated (phase-AB)

8500031C25 OCF3S-BC OCF2S relay element operated (phase-BC)

8600031C26 OCF3S-CA OCF2S relay element operated (phase-CA)

8400041B64 OCF4S OP OCF2S operated

8800041C24 OCF4S-AB OCF2S relay element operated (phase-AB)

8900041C25 OCF4S-BC OCF2S relay element operated (phase-BC)

8A00041C26 OCF4S-CA OCF2S relay element operated (phase-CA)

8500051B64 OCF5S OP OCF2S operated

8800051C24 OCF5S-AB OCF2S relay element operated (phase-AB)

8900051C25 OCF5S-BC OCF2S relay element operated (phase-BC)

8A00051C26 OCF5S-CA OCF2S relay element operated (phase-CA)

8000081B61 PSBS DET PSBS detection

8000081B62 PSBSIN-AB PSBS-IN operated (phase-AB)

8100081B63 PSBSIN-BC PSBS-IN operated (phase-BC)

8200081B64 PSBSIN-CA PSBS-IN operated (phase-CA)

8400081B65 PSBSOUT-AB PSBS-OUT operated (phase-AB)

8500081B66 PSBSOUT-BC PSBS-OUT operated (phase-BC)

8600081B67 PSBSOUT-CA PSBS-OUT operated (phase-CA)

8000011B6A SOTF-Z1S-OPT-AB SOTF operated for Z1S (phase-AB)

8100011B6B SOTF-Z1S-OPT-BC SOTF operated for Z1S (phase-BC)

8200011B6C SOTF-Z1S-OPT-CA SOTF operated for Z1S (phase-CA)

GRL200 (Soft 033 & 037)


- 169 -
6F2S1914 (0.37)

 Signal monitoring point


ZS (Function ID: 430001)
Element ID Name Description
8000011B2B SOTF-Z1S-TRIP SOTF operated for Z1S (3-phases OR)

8400061B6A SOTF-Z1XS-OPT-AB SOTF operated for Z1XS (phase-AB)

8500061B6B SOTF-Z1XS-OPT-BC SOTF operated for Z1XS (phase-BC)

8600061B6C SOTF-Z1XS-OPT-CA SOTF operated for Z1XS (phase-CA)

8100061B2B SOTF-Z1XS-TRIP SOTF operated for Z1XS (3-phases OR)

8000021B6A SOTF-Z2S-OPT-AB SOTF operated for Z2S (phase-AB)

8100021B6B SOTF-Z2S-OPT-BC SOTF operated for Z2S (phase-BC)

8200021B6C SOTF-Z2S-OPT-CA SOTF operated for Z2S (phase-CA)

8200021B2B SOTF-Z2S-TRIP SOTF operated for Z2S (3-phases OR)

8400031B6A SOTF-Z3S-OPT-AB SOTF operated for Z3S (phase-AB)

8500031B6B SOTF-Z3S-OPT-BC SOTF operated for Z3S (phase-BC)

8600031B6C SOTF-Z3S-OPT-CA SOTF operated for Z3S (phase-CA)

8300031B2B SOTF-Z3S-TRIP SOTF operated for Z3S (3-phases OR)

8800041B6A SOTF-Z4S-OPT-AB SOTF operated for Z4S (phase-AB)

8900041B6B SOTF-Z4S-OPT-BC SOTF operated for Z4S (phase-BC)

8A00041B6C SOTF-Z4S-OPT-CA SOTF operated for Z4S (phase-CA)

8400041B2B SOTF-Z4S-TRIP SOTF operated for Z4S (3-phases OR)

8800051B6A SOTF-Z5S-OPT-AB SOTF operated for Z5S (phase-AB)

8900051B6B SOTF-Z5S-OPT-BC SOTF operated for Z5S (phase-BC)

8A00051B6C SOTF-Z5S-OPT-CA SOTF operated for Z5S (phase-CA)

8500051B2B SOTF-Z5S-TRIP SOTF operated for Z5S (3-phases OR)

8C00001B66 SOTF-ZS-OPT-ABR SOTF AB phase operated

8D00001B67 SOTF-ZS-OPT-BCR SOTF BC phase operated

8E00001B68 SOTF-ZS-OPT-CAR SOTF CA phase operated

8300001B2B SOTF-ZS-TRIP SOTF protection trip

8000011C20 Z1S-AB Z1S relay element operated (phase-AB)

8100011C21 Z1S-BC Z1S relay element operated (phase-BC)

8200011C22 Z1S-CA Z1S relay element operated (phase-CA)

8000011B23 Z1S-OPT Z1S operated (3-phases OR)

8000011B66 Z1S-OPT-AB Z1S operated (phase-AB)

8100011B67 Z1S-OPT-BC Z1S operated (phase-BC)

8200011B68 Z1S-OPT-CA Z1S operated (phase-CA)

8300011B63 Z1S-ORX Z1S-X operation level pick up (3-phases OR)

8400061C20 Z1XS-AB Z1XS relay element operated (phase-AB)

8500061C21 Z1XS-BC Z1XS relay element operated (phase-BC)

8600061C22 Z1XS-CA Z1XS relay element operated (phase-CA)

8100061B23 Z1XS-OPT Z1XS operated (3-phases OR)

8400061B66 Z1XS-OPT-AB Z1XS operated (phase-AB)

8500061B67 Z1XS-OPT-BC Z1XS operated (phase-BC)

8600061B68 Z1XS-OPT-CA Z1XS operated (phase-CA)

8700061B63 Z1XS-ORX Z1XS-ORX operation level pick up (3-phases OR)

8000021C20 Z2S-AB Z2S relay element operated (phase-AB)

8100021C21 Z2S-BC Z2S relay element operated (phase-BC)

8200021C22 Z2S-CA Z2S relay element operated (phase-CA)

GRL200 (Soft 033 & 037)


- 170 -
6F2S1914 (0.37)

 Signal monitoring point


ZS (Function ID: 430001)
Element ID Name Description
8200021B23 Z2S-OPT Z2S operated (3-phases OR)

8000021B66 Z2S-OPT-AB Z2S operated (phase-AB)

8100021B67 Z2S-OPT-BC Z2S operated (phase-BC)

8200021B68 Z2S-OPT-CA Z2S operated (phase-CA)

8300021B63 Z2S-ORX Z2S-ORX operated (3-phases OR)

8400031C20 Z3S-AB Z3S relay element operated (phase-AB)

8500031C21 Z3S-BC Z3S relay element operated (phase-BC)

8600031C22 Z3S-CA Z3S relay element operated (phase-CA)

8300031B23 Z3S-OPT Z3S operated (3-phases OR)

8400031B66 Z3S-OPT-AB Z3S operated (phase-AB)

8500031B67 Z3S-OPT-BC Z3S operated (phase-BC)

8600031B68 Z3S-OPT-CA Z3S operated (phase-CA)

8700031B63 Z3S-ORX Z3S-ORX operated (3-phases OR)

8800041C20 Z4S-AB Z4S relay element operated (phase-AB)

8900041C21 Z4S-BC Z4S relay element operated (phase-BC)

8A00041C22 Z4S-CA Z4S relay element operated (phase-CA)

8400041B23 Z4S-OPT Z4S operated (3-phases OR)

8800041B66 Z4S-OPT-AB Z4S operated (phase-AB)

8900041B67 Z4S-OPT-BC Z4S operated (phase-BC)

8A00041B68 Z4S-OPT-CA Z4S operated (phase-CA)

8B00041B63 Z4S-ORX Z4S-ORX operated (3-phases OR)

8800051C20 Z5S-AB Z5S relay element operated (phase-AB)

8900051C21 Z5S-BC Z5S relay element operated (phase-BC)

8A00051C22 Z5S-CA Z5S relay element operated (phase-CA)

8500051B23 Z5S-OPT Z5S operated (3-phases OR)

8800051B66 Z5S-OPT-AB Z5S operated (phase-AB)

8900051B67 Z5S-OPT-BC Z5S operated (phase-BC)

8A00051B68 Z5S-OPT-CA Z5S operated (phase-CA)

8B00051B63 Z5S-ORX Z5S-ORX operated (3-phases OR)

8000071B60 ZCSF-AB ZCSF protection operated (phase-AB)

8100071B61 ZCSF-BC ZCSF protection operated (phase-BC)

8200071B62 ZCSF-CA ZCSF protection operated (phase-CA)

8400071B69 ZCSR-AB ZCSR protection operated (phase-AB)

8500071B6A ZCSR-BC ZCSR protection operated (phase-BC)

8600071B6B ZCSR-CA ZCSR protection operated (phase-CA)

8500001B61 ZS-ARC-BLOCK Autoreclose block signal by ZS

8C00001B62 ZS-OPT-ABR ZS protection operated (phase-A)

8D00001B63 ZS-OPT-BCR ZS protection operated (phase-B)

8E00001B64 ZS-OPT-CAR ZS protection operated (phase-C)

8300001B23 ZS-TRIP ZS trip

3000081B71 ZS_BLKZN BlkZn status signal in RPSB of IEC61580 LN

GRL200 (Soft 033 & 037)


- 171 -
6F2S1914 (0.37)

 Connection point on PLC logic


ZS (Function ID: 430001)
Element ID Name Description
800008EBB2 LES BLOCK LES block

800008EBB0 PSBS BLOCK PSBS block

810008EBB1 PSBS F.RESET PSBS forcible reset

800001EBB3 SOTF-Z1S BLOCK SOTF block signal for Z1S

810006EBB3 SOTF-Z1XS BLOCK SOTF block signal for Z1XS

820002EBB3 SOTF-Z2S BLOCK SOTF block signal for Z2S

830003EBB3 SOTF-Z3S BLOCK SOTF block signal for Z3S

840004EBB3 SOTF-Z4S BLOCK SOTF block signal for Z4S

850005EBB3 SOTF-Z5S BLOCK SOTF block signal for Z5S

800001EBB0 Z1STP_BLOCK Z1S trip block signal

800001EBB2 Z1S_ARCBLOCK Autoreclose block signal for Z1S

800001EBB1 Z1S_INST_OP Z1S instantaneously operated

810006EBB0 Z1XSTP_BLOCK Z1XS trip block signal

810006EBB2 Z1XS_ARCBLOCK Autoreclose block signal for Z1XS

810006EBB1 Z1XS_INST_OP Z1XS instantaneously operated

820002EBB0 Z2STP_BLOCK Z2S trip block signal

820002EBB2 Z2S_ARCBLOCK Autoreclose block signal for Z2S

820002EBB1 Z2S_INST_OP Z2S instantaneously operated

830003EBB0 Z3STP_BLOCK Z3S trip block signal

830003EBB2 Z3S_ARCBLOCK Autoreclose block signal for Z3S

830003EBB1 Z3S_INST_OP Z3S instantaneously operated

840004EBB0 Z4STP_BLOCK Z4S trip block signal

840004EBB2 Z4S_ARCBLOCK Autoreclose block signal for Z4S

840004EBB1 Z4S_INST_OP Z4S instantaneously operated

850005EBB0 Z5STP_BLOCK Z5S trip block signal

850005EBB2 Z5S_ARCBLOCK Autoreclose block signal for Z5S

850005EBB1 Z5S_INST_OP Z5S instantaneously operated

(2.28)

GRL200 (Soft 033 & 037)


- 172 -
6F2S1914 (0.37)

 Signal monitoring point


ZG (Function ID: 431001)
Element ID Name Description
8000081B71 LD_ENC-A Load encroachment operated (phase-A)

8100081B72 LD_ENC-B Load encroachment operated (phase-B)

8200081B73 LD_ENC-C Load encroachment operated (phase-C)

8000081B6C LEG-L-A LEG-L relay element operated (phase-A)

8100081B6D LEG-L-B LEG-L relay element operated (phase-B)

8200081B6E LEG-L-C LEG-L relay element operated (phase-C)

8000081B69 LEG-R-A LEG-R relay element operated (phase-A)

8100081B6A LEG-R-B LEG-R relay element operated (phase-B)

8200081B6B LEG-R-C LEG-R relay element operated (phase-C)

8000011B64 OCF1G OP OCF1G operated

8000011C24 OCF1G-A OCF1G relay element operated (phase-A)

8100011C25 OCF1G-B OCF1G relay element operated (phase-B)

8200011C26 OCF1G-C OCF1G relay element operated (phase-C)

8100061B64 OCF1XG OP OCF1XG operated

8400061C24 OCF1XG-A OCF1XG relay element operated (phase-A)

8500061C25 OCF1XG-B OCF1XG relay element operated (phase-B)

8600061C26 OCF1XG-C OCF1XG relay element operated (phase-C)

8200021B64 OCF2G OP OCF2G operated

8000021C24 OCF2G-A OCF2G relay element operated (phase-A)

8100021C25 OCF2G-B OCF2G relay element operated (phase-B)

8200021C26 OCF2G-C OCF2G relay element operated (phase-C)

8300031B64 OCF3G OP OCF3G operated

8400031C24 OCF3G-A OCF3G relay element operated (phase-A)

8500031C25 OCF3G-B OCF3G relay element operated (phase-B)

8600031C26 OCF3G-C OCF3G relay element operated (phase-C)

8400041B64 OCF4G OP OCF4G operated

8800041C24 OCF4G-A OCF4G relay element operated (phase-A)

8900041C25 OCF4G-B OCF4G relay element operated (phase-B)

8A00041C26 OCF4G-C OCF4G relay element operated (phase-C)

8500051B64 OCF5G OP OCF5G operated

8800051C24 OCF5G-A OCF5G relay element operated (phase-A)

8900051C25 OCF5G-B OCF5G relay element operated (phase-B)

8A00051C26 OCF5G-C OCF5G relay element operated (phase-C)

8000081B70 PSBG DET PSBG detection

8000081B66 PSBGIN-A PSBGIN relay element operated (phase-A)

8100081B67 PSBGIN-B PSBGIN relay element operated (phase-B)

8200081B68 PSBGIN-C PSBGIN relay element operated (phase-C)

8400081B63 PSBGOUT-A PSBGOUT relay element operated (phase-A)

8500081B64 PSBGOUT-B PSBGOUT relay element operated (phase-B)

8600081B65 PSBGOUT-C PSBGOUT relay element operated (phase-C)

8000011B6B SOTF-Z1G-OPT-A SOTF operated for Z1G (phase-A)

8100011B6C SOTF-Z1G-OPT-B SOTF operated for Z1G (phase-B)

8200011B6D SOTF-Z1G-OPT-C SOTF operated for Z1G (phase-C)

GRL200 (Soft 033 & 037)


- 173 -
6F2S1914 (0.37)

 Signal monitoring point


ZG (Function ID: 431001)
Element ID Name Description
8000011B2B SOTF-Z1G-TRIP SOTF operated for Z1G (3-phases OR)

8400061B6B SOTF-Z1XG-OPT-A SOTF operated for Z1XG (phase-A)

8500061B6C SOTF-Z1XG-OPT-B SOTF operated for Z1XG (phase-B)

8600061B6D SOTF-Z1XG-OPT-C SOTF operated for Z1XG (phase-C)

8100061B2B SOTF-Z1XG-TRIP SOTF operated for Z1XG (3-phases OR)

8000021B6B SOTF-Z2G-OPT-A SOTF operated for Z2G (phase-A)

8100021B6C SOTF-Z2G-OPT-B SOTF operated for Z2G (phase-B)

8200021B6D SOTF-Z2G-OPT-C SOTF operated for Z2G (phase-C)

8200021B2B SOTF-Z2G-TRIP SOTF operated for Z2G (3-phases OR)

8400031B6B SOTF-Z3G-OPT-A SOTF operated for Z3G (phase-A)

8500031B6C SOTF-Z3G-OPT-B SOTF operated for Z3G (phase-B)

8600031B6D SOTF-Z3G-OPT-C SOTF operated for Z3G (phase-C)

8300031B2B SOTF-Z3G-TRIP SOTF operated for Z3G (3-phases OR)

8800041B6B SOTF-Z4G-OPT-A SOTF operated for Z4G (phase-A)

8900041B6C SOTF-Z4G-OPT-B SOTF operated for Z4G (phase-B)

8A00041B6D SOTF-Z4G-OPT-C SOTF operated for Z4G (phase-C)

8400041B2B SOTF-Z4G-TRIP SOTF operated for Z4G (3-phases OR)

8800051B6B SOTF-Z5G-OPT-A SOTF operated for Z5G (phase-A)

8900051B6C SOTF-Z5G-OPT-B SOTF operated for Z5G (phase-B)

8A00051B6D SOTF-Z5G-OPT-C SOTF operated for Z5G (phase-C)

8500051B2B SOTF-Z5G-TRIP SOTF operated for Z5G (3-phases OR)

8300001B2B SOTF-ZG-TRIP SOTF protection trip

8000081B60 UVPWI-A UVPWI relay element operated (phase-A)

8100081B61 UVPWI-B UVPWI relay element operated (phase-B)

8200081B62 UVPWI-C UVPWI relay element operated (phase-C)

8000011C20 Z1G-A Z1G relay element operated (phase-A)

8100011C21 Z1G-B Z1G relay element operated (phase-B)

8200011C22 Z1G-C Z1G relay element operated (phase-C)

8000011B69 Z1G-OPT Z1G operated (3-phases OR)

8000011B66 Z1G-OPT-A Z1G operated (phase-A)

8100011B67 Z1G-OPT-B Z1G operated (phase-B)

8200011B68 Z1G-OPT-C Z1G operated (phase-C)

8300011B63 Z1G-ORX Z1G-ORX operated (3-phases OR)

8400061C20 Z1XG-A Z1XG relay element operated (phase-A)

8500061C21 Z1XG-B Z1XG relay element operated (phase-B)

8600061C22 Z1XG-C Z1XG relay element operated (phase-C)

8100061B69 Z1XG-OPT Z1XG operated (3-phases OR)

8400061B66 Z1XG-OPT-A Z1XG operated (phase-A)

8500061B67 Z1XG-OPT-B Z1XG operated (phase-B)

8600061B68 Z1XG-OPT-C Z1XG operated (phase-C)

8700061B63 Z1XG-ORX Z1XG-ORX operated (3-phases OR)

8000021C20 Z2G-A Z2G relay element operated (phase-A)

8100021C21 Z2G-B Z2G relay element operated (phase-B)

8200021C22 Z2G-C Z2G relay element operated (phase-C)

GRL200 (Soft 033 & 037)


- 174 -
6F2S1914 (0.37)

 Signal monitoring point


ZG (Function ID: 431001)
Element ID Name Description
8200021B69 Z2G-OPT Z2G operated (3-phases OR)

8000021B66 Z2G-OPT-A Z2G operated (phase-A)

8100021B67 Z2G-OPT-B Z2G operated (phase-B)

8200021B68 Z2G-OPT-C Z2G operated (phase-C)

8300021B63 Z2G-ORX Z2G-ORX operated (3-phases OR)

8400031C20 Z3G-A Z3G relay element operated (phase-A)

8500031C21 Z3G-B Z3G relay element operated (phase-B)

8600031C22 Z3G-C Z3G relay element operated (phase-C)

8300031B69 Z3G-OPT Z3G operated (3-phases OR)

8400031B66 Z3G-OPT-A Z3G operated (phase-A)

8500031B67 Z3G-OPT-B Z3G operated (phase-B)

8600031B68 Z3G-OPT-C Z3G operated (phase-C)

8700031B63 Z3G-ORX Z3G-ORX operated (3-phases OR)

8800041C20 Z4G-A Z4G relay element operated (phase-A)

8900041C21 Z4G-B Z4G relay element operated (phase-B)

8A00041C22 Z4G-C Z4G relay element operated (phase-C)

8400041B69 Z4G-OPT Z4G operated (3-phases OR)

8800041B66 Z4G-OPT-A Z4G operated (phase-A)

8900041B67 Z4G-OPT-B Z4G operated (phase-B)

8A00041B68 Z4G-OPT-C Z4G operated (phase-C)

8B00041B63 Z4G-ORX Z4G-ORX operated (3-phases OR)

8800051C20 Z5G-A Z5G relay element operated (phase-A)

8900051C21 Z5G-B Z5G relay element operated (phase-B)

8A00051C22 Z5G-C Z5G relay element operated (phase-C)

8500051B69 Z5G-OPT Z5G operated (3-phases OR)

8800051B66 Z5G-OPT-A Z5G operated (phase-A)

8900051B67 Z5G-OPT-B Z5G operated (phase-B)

8A00051B68 Z5G-OPT-C Z5G operated (phase-C)

8B00051B63 Z5G-ORX Z5G-ORX operated (3-phases OR)

8000071B75 ZCGF-A ZCGF relay element operated (phase-A)

8100071B76 ZCGF-B ZCGF relay element operated (phase-B)

8200071B77 ZCGF-C ZCGF relay element operated (phase-C)

8400071B78 ZCGR-A ZCGR relay element operated (phase-A)

8500071B79 ZCGR-B ZCGR relay element operated (phase-B)

8600071B7A ZCGR-C ZCGR relay element operated (phase-C)

8500001B7C ZG-ARC-BLOCK Autoreclose block signal by ZG

8800001B7D ZG-OPT-AR ZG A phase operated

8900001B7E ZG-OPT-BR ZG B phase operated

8A00001B7F ZG-OPT-CR ZG C phase operated

8000001B20 ZG-TRIP-A ZG A phase trip

8100001B21 ZG-TRIP-B ZG B phase trip

8200001B22 ZG-TRIP-C ZG C phase trip

8000001B63 ZGFCOV-A ZGFCOV relay element operated (phase-A)

8100001B64 ZGFCOV-B ZGFCOV relay element operated (phase-B)

GRL200 (Soft 033 & 037)


- 175 -
6F2S1914 (0.37)

 Signal monitoring point


ZG (Function ID: 431001)
Element ID Name Description
8200001B65 ZGFCOV-C ZGFCOV relay element operated (phase-C)

8400001B66 ZGRCOV-A ZGRCOV relay element operated (phase-A)

8500001B67 ZGRCOV-B ZGRCOV relay element operated (phase-B)

 Connection point on PLC logic


ZG (Function ID: 431001)
Element ID Name Description
800008EBB2 LEG BLOCK LEG block

800008EBB0 PSBG BLOCK PSBG block

810008EBB1 PSBG F.RESET PSBG forcible reset

800001EBB4 SOTF-Z1G BLOCK SOTF block signal for Z1G

810006EBB4 SOTF-Z1XG BLOCK SOTF block signal for Z1XG

820002EBB4 SOTF-Z2G BLOCK SOTF block signal for Z2G

830003EBB4 SOTF-Z3G BLOCK SOTF block signal for Z3G

840004EBB4 SOTF-Z4G BLOCK SOTF block signal for Z4G

850005EBB4 SOTF-Z5G BLOCK SOTF block signal for Z5G

800001EBB0 Z1GTP_BLOCK Z1G trip block signal

800001EBB2 Z1G_3PTP Z1G trip (3-phases)

800001EBB3 Z1G_ARCBLOCK Autoreclose block signal for Z1G

800001EBB1 Z1G_INST_OP Z1G instantaneously operated

810006EBB0 Z1XGTP_BLOCK Z1XG trip block signal

810006EBB2 Z1XG_3PTP Z1XG trip (3-phases)

810006EBB3 Z1XG_ARCBLOCK Autoreclose block signal for Z1XG

810006EBB1 Z1XG_INST_OP Z1XG instantaneously operated

820002EBB0 Z2GTP_BLOCK Z2G trip block signal

820002EBB2 Z2G_3PTP Z2G trip (3-phases)

820002EBB3 Z2G_ARCBLOCK Autoreclose block signal for Z2G

820002EBB1 Z2G_INST_OP Z2G instantaneously operated

830003EBB0 Z3GTP_BLOCK Z3G trip block signal

830003EBB2 Z3G_3PTP Z3G trip (3-phases)

830003EBB3 Z3G_ARCBLOCK Autoreclose block signal for Z3G

830003EBB1 Z3G_INST_OP Z3G instantaneously operated

840004EBB0 Z4GTP_BLOCK Z4G trip block signal

840004EBB2 Z4G_3PTP Z4G trip (3-phases)

840004EBB3 Z4G_ARCBLOCK Autoreclose block signal for Z4G

840004EBB1 Z4G_INST_OP Z4G instantaneously operated

850005EBB0 Z5GTP_BLOCK Z5G trip block signal

850005EBB2 Z5G_3PTP Z5G trip (3-phases)

850005EBB3 Z5G_ARCBLOCK Autoreclose block signal for Z5G

850005EBB1 Z5G_INST_OP Z5G instantaneously operated

(2.28)

GRL200 (Soft 033 & 037)


- 176 -
6F2S1914 (0.37)

Direct transfer trip (DTT)


When direct transfer trip (DTT) function receives a trip signal from the remote, the DTT
function will issue the trip signal for the trip circuit (TRC) to open a circuit breaker (CB). The
DTT function consists of two shemes1: DTT1 and DTT2. Each can receive the trip signal
separately; the trip signal can be transferred with the communication2.

1Note: An asterisk (*) is used to express either DTT1 or DTT2 schemes.


2Note: The communication feature is available with the communication features. See
Chapter Relay application: Transmission control function and Communication
application. The user should make the PLC logic for this DTT operation. See
Chapter PLC function: PLC setting samples for more information.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the “G&T position” referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 2.11-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
DTT Direct transfer trip function (DTT) ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 177 -
6F2S1914 (0.37)

2.11.1 Setting for the operation


To the operation, the user should set On for scheme switch [DTT*-EN]; then, the user should
set for the scheme switch [DTT*-Output] to select an mode when the DTT function receives a
command from the remote terminal. The user should set TRIP for the scheme switch [DTT*-
Output] when tripping the CB1 is required. Conversely, set BO for the scheme switch [DTT*-
Output] when tripping the CB is not required but issuing an alarm is required using the binary
output circuit2.

To delay for issuing the trip signal, the user can set the delay time using [TDTT*] among
0.00 to 300.00sec.

If the operation of the autoreclose (ARC3) function must be blocked when the DTT
function receives a signal from the remote end, set Block for scheme switch [DTT*-ARCBlk].

1Note: Issuing the trip command is performed in trip circuit (TRC). For more
information, see chapter Relay application: Trip circuit, separately.
2Note: For programing binary output circuits, see chapter Technical description: Binary
IO module.
3Note: ARC is discussed separately. See chapter Relay application: Autoreclose.

GRL200 (Soft 033 & 037)


- 178 -
6F2S1914 (0.37)

2.11.2 Scheme logic


Figure 2.11-1shows the DTT scheme logics. For the reception of a pair of trip signals from a
remote terminal, the logic has two PLC connection points ‘R1.DTT1’ and ‘R1.DTT2’. The user should
connect a remote trip signal provided by the communication with the PLC connection points using
PLC function.

Blocking the DTT1 function is also available when an external signal is injected to the
logic using PLC connection point “DTT1_BLOCK”. Incidentally, the user can program to
operate the DTT1 function with the absence of the delaying [TDD1] using PLC connection point
“DTT1_INST_OP”. The user should notice that issuing for the TRC function is just designed
for the three-phase tripping command.

From the communication

COMM.DATA FAIL_R1
COMM.DATA FAIL_R2

From Remote1
8000011BB0
800001EBB0 R1_DTT1 &
8000021BB0 BO
800002EBB0 R1_DTT2 DTT1-Output Trip
1 ≥1
From Remote2
8100011BB1 TDTT1
& To TRC
810001EBB1 R2_DTT1 t 0
& ≥1 8000011B60 &
8100021BB1
0.00 to 300.00s ≥1 8300001B23
810001EBB1 R2_DTT2 1
DTT-OPT-TRIP
&
On
&
DTT1-EN
8000011BB4
800001EBB4 DTT1_BLOCK 1
8000011BB5
DTT1-ARCBlk & 8000011B61 8500001B61
800001EBB5 DTT1_INST_OP
Block ≥1 DTT-ARC-BLOCK

DTT2-ARCBlk
Block & 8100021B61

& COMM.DATA

1 ≥1

TDTT2
COMM.D
& t 0
& ≥1 8100021B60
1 0.00 to 300.00s
&

&
BO
On DTT2-Output Trip

&
8100021BB4 DTT2-EN

800001EBB4 DTT2_BLOCK 1

8100021BB5
810002EBB5 DTT2_INST_OP

Figure 2.11-1 DTT1 and DTT2 scheme logics

GRL200 (Soft 033 & 037)


- 179 -
6F2S1914 (0.37)

2.11.3 Setting
DTT(Function ID: 485001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
DTT1-EN Off / On - Switch for Direct transfer trip 1 Off
DTT2-EN Off / On - Switch for Direct transfer trip 2 Off
DTT1 TDTT1 0.00 - 300.00 s DTT1 delay time 0.00
DTT1-Output Trip / BO - DTT1 trip signal output position Trip
DTT1-ARCBlk Non / Block - Autoreclose blocked by DTT1 Block
DTT2 TDTT2 0.00 - 300.00 s DTT2 delay time 0.00
DTT2-Output Trip / BO - DTT2 trip signal output position Trip
DTT2-ARCBlk Non / Block - Autoreclose blocked by DTT2 Block

2.11.4 Data ID
 Signal monitoring point
DTT(Function ID: 485001)
Element ID Name Description
8500001B61 DTT-ARC-BLOCK Autoreclose block signal by DTT protection operation

8300001B23 DTT-OPT-TRIP Direct transfer trip operation

8000011B61 DTT1-ARC-BLOCK Autoreclose block signal by DTT1 protection operation

8000011B60 DTT1-OPT Direct transfer trip 1 operation

8000011BB4 DTT1_BLOCK DTT1 scheme block

8000011BB5 DTT1_INST_OP DTT1 protection instant operation command

8100021B61 DTT2-ARC-BLOCK Autoreclose block signal by DTT2 protection operation

8100021B60 DTT2-OPT Direct transfer trip 2 operation

8100021BB4 DTT2_BLOCK DTT2 scheme block

8100021BB5 DTT2_INST_OP DTT2 protection instant operation command

8000011BB0 R1.DTT1 Transfer trip command 1 receiving from terminal 1

8000021BB0 R1.DTT2 Transfer trip command 2 receiving from terminal 1

8100011BB1 R2.DTT1 Transfer trip command 1 receiving from terminal 2

8100021BB1 R2.DTT2 Transfer trip command 2 receiving from terminal 2

8200011BB2 R3.DTT1 Transfer trip command 1 receiving from terminal 3

8200021BB2 R3.DTT2 Transfer trip command 2 receiving from terminal 3

8300011BB3 R4.DTT1 Transfer trip command 1 receiving from terminal 4

8300021BB3 R4.DTT2 Transfer trip command 2 receiving from terminal 4

 Connection point in PLC logic


DTT(Function ID: 485001)
Element ID Name Description
800001EBB4 DTT1_BLOCK DTT1 scheme block

800001EBB5 DTT1_INST_OP DTT1 protection instant operation command

810002EBB4 DTT2_BLOCK DTT2 scheme block

810002EBB5 DTT2_INST_OP DTT2 protection instant operation command

800001EBB0 R1.DTT1 Transfer trip command 1 receiving from terminal 1

800002EBB0 R1.DTT2 Transfer trip command 2 receiving from terminal 1

810001EBB1 R2.DTT1 Transfer trip command 1 receiving from terminal 2

810002EBB1 R2.DTT2 Transfer trip command 2 receiving from terminal 2

820001EBB2 R3.DTT1 Transfer trip command 1 receiving from terminal 3

820002EBB2 R3.DTT2 Transfer trip command 2 receiving from terminal 3

830001EBB3 R4.DTT1 Transfer trip command 1 receiving from terminal 4

GRL200 (Soft 033 & 037)


- 180 -
6F2S1914 (0.37)

 Signal monitoring point


DTT(Function ID: 485001)
Element ID Name Description
830002EBB3 R4.DTT2 Transfer trip command 2 receiving from terminal 4

GRL200 (Soft 033 & 037)


- 181 -
6F2S1914 (0.37)

Distance carrier command protection (DISCAR)


When every IED can exchange operational information mutually using communication system,
accurate decision of whether or not a fault is internal on the line can be made. Distance carrier
command protection (DISCAR) can provide such protection using the distance protection
(ZS/ZG). Consequently, the whole length of the line can be protected promptly for any fault.
The following techniques are provided in DISCAR:
1. Permissive underreach protection (PUP)
2. Permissive overreach protection (POP)
3. Unblocking overreach protection (UOP)
4. Blocking overreach protection (BOP)

The function of autoreclose (ARC) can be operated speedy using these protections above;
and these can issue either a single-pole trip signal or three-poles trip signal in accordance with
DISCAR settings and the states of faults.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have carrier features. To determine whether the features
are implemented in the IED or not, locate the IED ordering number; and check the order
number at “G&T position” referring to the comparison table below. For more information, see
Appendix: Ordering.
Table 2.12-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
DISCAR Distance carrier command protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 182 -
6F2S1914 (0.37)

2.12.1 Permissive underreach protection (PUP)


(i) Application
When an underreach element operates at local terminal, and when the circuit breaker (CB) is
tripped by this element, a trip permission signal† is sent to other opposite terminals. When
the opposite terminals receive the signal, CBs at these terminals are tripped instantly if an
overreaching element at respective these terminals has been operated. In PUP, Z1S/Z1G
elements in ZS/ZG are used for the underreach element, and ZCSF/ZCGF elements are used
for the overreaching element.

The trip permission signal is not sent until it is observed that the fault exists in the
protection zone of Z1S/Z1G; hence, PUP can provide excellent security., but PUP cannot provide
sufficient dependability if faults exist on the line including open terminals or weak infeed
terminals. This is because Z1S/Z1G cannot operate for this case‡.

†Note: The trip permission signal yielded by the underreaching element is transmitted
only; hence, respective terminals can share a telecommunication channel; and a
simplex channel can be used.
‡Note: At remote terminals, Z1X/ Z2 have a delay timer. Thus, they can remove the
faults.

(ii) Scheme logic


Figure 2.12-1 shows PUP logic. When Z1S/Z1G operate at the local terminal, Z1S/Z1G issue a
single-phase trip signal or three-phase trip signal instantaneously; and a trip permission
signal (DISCAR-CS-*) is sent to the opposite terminals through the sending circuit. Figure
2.12-2 shows the sending circuit of PUP; the trip permission signals are given at PLCs signal
monitoring point (INT.DISCAR-S-*). The selection of either the single-phase trip (1P) or the
three-phase trip (3P) is carried out using scheme switch [DisCAR-TPMD].

When the opposite terminal receives the trip permission signal, PUP at the opposite
terminal also issues a trip signal instantly when either ZCSF/ZCGF have been operated.
Receipt of the trip permission signals are found at PLC connection points (INT.DISCAR-R*).

PUP can operate when PUP is set for scheme switch [Dis-CAR]. If PUP requires operating
ARC, set scheme switch [DisCAR-ARCBlk] Non. (For more information of ARC, see chapter
Relay application: Autoreclose.)

GRL200 (Soft 033 & 037)


- 183 -
6F2S1914 (0.37)

To carrier
From Z1S/Z1G in local Terminal send circuit
Z1G-AX OP DISCAR-CS-A_PUP
Z1G-BX OP DISCAR-CS-B_PUP
Z1G-CX OP DISCAR-CS-C_PUP
Z1S-ABX OP DISCAR-CS-S_PUP
≥1
Z1S-BCX OP
8000001B73
Z1S-CAX OP
DISCAR-OPT-A
8100001B74
DISCAR-OPT-B
8200001B75
DISCAR-OPT-C
8300001B76
From ZG in local Terminal 8000001B68 DISCAR-OPT-S

ZCGF-AX 8000001B20
& ≥1 ≥1 8100001B69 ≥1 DISCAR-TRIP-A
≥1
ZCGF-BX 8100001B21
≥1
& ≥1 ≥1 8200001B6A ≥1 DISCAR-TRIP-B
ZCGF-CX 8200001B22
& ≥1 ≥1 ≥1 DISCAR-TRIP-C
≥1
From ZS in local Terminal
ZCSF-ABX ≥1
≥1 &
-CX
ZCSF-BCX &
&
-CX
ZCSF-CAX
&
-CX

& ≥1
& ≥1
Receipt of trip permission signals
From Terminal 1 & DISCAR_TPMD

800000EB55 INT.DISCAR-R1-A 3P
≥1
810000EB56 INT.DISCAR-R1-B ≥1 8100001B77
≥1 & DISCAR-ARC-BLOCK
820000EB57 INT.DISCAR-R1-C
≥1
830000EB58 INT.DISCAR-R1-S DISCAR-ARCBlk To TRC
≥1 ≥1
Block
EXT.DISCAR-R1

From Terminal 2
DISCAR_PERM1-A
840000EB59 INT.DISCAR-R2-A DISCAR_PERM1-B
DISCAR_PERM1-C
850000EB5A INT.DISCAR-R2-B
DISCAR_PERM
860000EB5B INT.DISCAR-R2-C

870000EB5C INT.DISCAR-R2-S ≥1
DISCAR_PERM2-A
EXT.DISCAR-R2 DISCAR_PERM2-B
DISCAR_PERM2-C
From CARRIER-COMMON
CAR_BLOCK DISCAR_PERM
≥1
1 To ECHO
800000EBB0 DISCAR_BLK
8000001BB0

800000EBBF DISCAR_3PTP

810000EBC0 DISCAR_ARCBLOCK

Figure 2.12-1 PUP scheme logic

ECHO logic

8000001B78
DISCAR-CS-A_PUP ≥1 INT.DISCAR-S-A
8100001B79
DISCAR-CS-B_PUP ≥1 INT.DISCAR-S-B
8200001B7A
DISCAR-CS-C_PUP ≥1 INT.DISCAR-S-C
8300001B7B
DISCAR-CS-S_PUP ≥1 INT.DISCAR-S-S

≥1
& ≥1 &
1 8F00001B7C

DISCAR-S

800000EB55 DISCAR_F.BLOCK

810000EB56 DISCAR_PERMIT
Dis-CAR
PUP

Figure 2.12-2 Sending circuit in PUP

2.12.2 Permissive overreach protection (POP)


(i) Application
When a forward overreaching element operates at a terminal, the terminal sends a trip
permission signal to the other opposite terminals. When the forward overreaching element
operates at a terminal, and when a trip permission signal† has been received from an opposite

GRL200 (Soft 033 & 037)


- 184 -
6F2S1914 (0.37)

terminal, the CB at the terminal is tripped in permission overreach protection (POP).

In other words, POP can determine if the fault exists inside the protected line based on
the overlapping operation of the forward overreaching elements at both terminals. ZCSF/ZCGF
elements are used for the forward overreaching element.

†Note:POP sends a trip permission signal when the forward overreaching element
operates. Thus, multiplex signaling channels or one channel for each direction is
required in POP. This is because that the terminal sending signals shall not trip
erroneously due to reception of its own sending signal if an external fault occurs in
the zone of forward overreaching element.

(ii) Operation of echo (ECHO) and week infeed trip (WKIT)


POP has an echo function (ECHO) and a weak infeed trip function (WKIT) in order that the
line including an open terminal or a weak infeed terminal can be protected by POP. Thus, POP
enables to trip CBs fast at both terminals for any fault along the whole length of the protected
line. (For more information of ECHO and WKIT, see section 2.12.5)

(iii) Countermeasure of current reversal (CRL)


When a fault exist on one of parallel lines, tripping CBs sequential may cause a current
reversal on another of parallel lines. The current reversal results in the false operation of POP,
hence, countermeasure logic is provided for the current reversal (CRL). (For more information
of CRL, see section 2.12.6)
(iv) Criterion of POP tripping
POP at the local terminal issues either a single-phase tripping signal or a three-phase trip
signal when the following conditions are satisfied:
 Trip permission signal is received from the opposite terminal
 The current reversal has not been observed
 One of the following conditions is established:
 The forward overreaching element operates.
 When On is set for scheme switch [Dis-WIKT], the undervoltage element UVL†
(UVLS or UVLG) operates and the forward overreaching element and the
reverse looking element have not operated.

†Note: UVL is provided in the function of protection common (PROT_COMMON).


For more information, see Chapter Relay application: Protection common.

(v) Scheme logic


Figure 2.12-3 shows POP scheme logics. POP sends a trip permission signal for the opposite

GRL200 (Soft 033 & 037)


- 185 -
6F2S1914 (0.37)

terminals when any of the following conditions are satisfied:


1. The forward overreaching element operates; and CRL has not observed the current
reversal.
2. When On is set for scheme switch [Dis-ECHO], CB is opened; and a trip permission
signal (DISCAR-CS-*) is received from the other terminal.
3. When On is set for scheme switch [Dis-ECHO], the forward overreaching element
(ZCSF/ZCGF) and the reverse looking element (ZCSR/ZCGR) have not operated; and
a trip permission signal is received from the other terminal.

To carrier
send circuit
DISCAR-CS-AB_POUP

DISCAR-CS-BC_POUP

DISCAR-CS-CA_POUP

DISCAR-CS-A_POUP

DISCAR-CS-B_POUP

DISCAR-CS-C_POUP

DISCAR-CS-S_POUP
8000001B73

Week infeed trip logic (WKIT) DISCAR-OPT-A


8100001B74
DISCAR-OPT-B
8200001B75
DISCAR-OPT-C
From ZG in local Terminal 8300001B76
8000001B68
ZCGF-AX & DISCAR-OPT-S
& ≥1
1 8000001B20
≥1 ≥1 8100001B69 ≥1
ZCGF-BX ≥1 ≥1 DISCAR-TRIP-A
& &
1 ≥1 8200001B6A ≥1 8100001B21
≥1 ≥1 DISCAR-TRIP-B
≥1
ZCGF-CX ≥1 ≥1 8200001B22
& & ≥1 DISCAR-TRIP-C
1
From ZS in local Terminal ≥1
≥1
ZCSF-ABX &
≥1 &
-CX
ZCSF-BCX
-CX &

ZCSF-CAX &
-CX
≥1

DISCAR_TPMD
&
& 3P
≥1
& 8100001B77
& & DISCAR-ARC-BLOCK
≥1
& &
1
DISCAR-ARCBlk To TRC

Block

From ZG in local Terminal


ZCGR-AX
-CX
ZCGR-BX Current
-CX reversal
ZCGR-CX logic
-CX (CRL)
ZCSF-X
-CX
ZCSR-X
-CX
Receipt of trip permission signals
From Terminal 1
800000EB55 INT.DISCAR-R1-A =1
≥1
&
810000EB56 INT.DISCAR-R1-B =1 ≥1
&
820000EB57 INT.DISCAR-R1-C =1 ≥1 &

830000EB58 INT.DISCAR-R1-S =1 ≥1 ≥1 &

EXT.DISCAR-R1 =1

From Terminal 2

840000EB59 INT.DISCAR-R2-A =1 ≥1

850000EB5A INT.DISCAR-R2-B =1 ≥1

860000EB5B INT.DISCAR-R2-C =1 ≥1

870000EB5C INT.DISCAR-R2-S =1 ≥1 ≥1

EXT.DISCAR-R2 =1

Dis-CAR UOP
POP
From CARRIER-COMMON
CH1-USE 1

CH2-USE 1
8000001BB0
CAR_BLOCK
≥1
1
800000EBB0 DISCAR_BLK

800000EBBF DISCAR_3PTP

800000EBBF DISCAR_ARCBLOCK

Figure 2.12-3 POP and UOP scheme logic

GRL200 (Soft 033 & 037)


- 186 -
6F2S1914 (0.37)

(vi) Delay of trip permission signal


Figure 2.12-4 shows POP sending circuit. The trip permission signals are given at PLCs signal
monitoring point (INT.DISCAR-S-*). The selection of either the single-phase trip (1P) or the
three-phase trip (3P) is carried out using scheme switch [DisCAR-TPMD].

Transmission of the trip permission signal continues for setting [TSBCT-dis] even after
the local terminal issues a trip signal.

In many cases, at both ends of the line, the overreaching elements operate at the same
time. However, there may be some cases where they cannot operate simultaneously because
fault currents do not flow symmetrically. That is, the overreaching elements far from a fault
cannot operate by the fault, but the overreaching elements far from the fault will be operated
indirectly if the other terminals are induced to trip. To avoid this case, transmission of the trip
permission signal continues for a while set by [TSBCT-dis] after reset of ZCSF/ZCSG operation.
Consequently, the overreaching elements far from the fault can also generate a trip signal
because the trip permission signal is picked up delayed.

Thus, this command protection ensures its operation at the remote terminal.
TSBCT-DIS
DISCAR-OPT-A t 0
≥1
DISCAR-OPT-B t 0
≥1
DISCAR-OPT-C t 0
≥1
Trip permission
t 0 signals for POP
& ≥1 8000001B78
From Z1G 0.00 to 1.00s INT.DISCAR-S-A
Z1G-TRIP-A 8100001B79
INT.DISCAR-S-B
8200001B7A
Z1G-TRIP-B
INT.DISCAR-S-C
Z1G-TRIP-C 8300001B7B
INT.DISCAR-S-S
Z1S-OPT
From SOTF-OC
OCH-RETRIP
Trip permission
signals for UOP
8000001B78
DISCAR-CS-A_POUP ≥1 =1 INT.DISCAR-S-A
8100001B79
DISCAR-CS-B_POUP ≥1 =1 INT.DISCAR-S-B
8200001B7A
DISCAR-CS-C_POUP INT.DISCAR-S-C
≥1 =1
8300001B7B
DISCAR-CS-S_POUP =1 INT.DISCAR-S-S
≥1

≥1
ECHO logic
& ≥1 &
≥1 8F00001B7C
1
DISCAR-S

≥1 & &
800000EB55 DISCAR_F.BLOCK 1

810000EB56 DISCAR_PERMIT

POP
Dis-CAR
UOP

Figure 2.12-4 Sending circuit in POP and UOP

2.12.3 Unblocking overreach protection (UOP)


When information are exchanged using a transmission line (the power line carrier), PUP and
POP cannot trip dependably. This is because a trip permission signal may not be exchanged
through the transmission line because that the transmission line includes a fault; the fault

GRL200 (Soft 033 & 037)


- 187 -
6F2S1914 (0.37)

may reduce the power of the signal and then PUP and POP may fail to operate. Unblocking
overreach protection (UOP) is introduced in order to negate this issue.

We can regard a transmitted signal as a trip block signal; and the trip block signal is
transmitted continuously except for the fault conditions. When the forward overreaching
element operates, signal transmission is stopped; hence, a trip block signal is not reached at
an opposite terminal. Consequently, the opposite terminal is allowed to trip; and CB tripping
is carried out when the forward overreaching element on its own operates.

ZCSF/ZCGF elements are used for the forward overreaching element. On the other hand,
ZCSR/ZCGR elements are used for the reverse looking element.

In UOP, the signal is required to send except for the occurrence of internal faults.
Therefore, a failure to operate or false operation due to attenuation of the signal will be
removed even if the power line carrier is used to exchange operation information.

(i) Operation of echo (ECHO) and week infeed trip (WKIT)


UOP can have the functions of ECHO and WKIT, as well as POP. To operate these function,
user should set [Dis-ECHO] On or [Dis-WIKT] On. (For more information of ECHO and WKIT,
see section 2.12.5)

(ii) Countermeasure of current reversal (CRL)


UOP has the countermeasure of current reversal, as well as POP. (For more information of
CRL, see section 2.12.6)

(iii) Delay of trip block signal


As similar to POP, UOP has setting [TSBCT-dis] not to send the trip block signal even after
the local terminal issues a trip signal.

(iv) Scheme logic


Figure 2.12-3 and Figure 2.12-4 also show UOP scheme logic. In UOP, a trip block signal is
observed PLCs signal monitoring point (INT.DISCAR-S-*) when the logic level in UOP is equal
to “1”. Conversely, a trip block signal is not observed when the logic level is equal to “0”.

UOP does not send a trip block signal when one of the following conditions are observed:
 The forward overreaching element operates and the current reversal is not occurred.
 When On is set for scheme switch [Dis-ECHO], CB is open and the trip block signal
is not received from the other terminals.
 When On is set for scheme switch [Dis-ECHO], both the forward overreaching

GRL200 (Soft 033 & 037)


- 188 -
6F2S1914 (0.37)

element and the reverse looking element are not operating and a trip block signal is
not received from the other terminals.

The trip block signals are given at PLCs signal monitoring point (INT.DISCAR-S-*). The
selection of either the single-phase trip (1P) or the three-phase trip (3P) is carried out using
scheme switch [DisCAR-TPMD].

UOP issues single-phase tripping signal or three-phase trip signal locally when the
following conditions are established:
 Trip block signal is not received from the opposite terminals.
 Current reversal is not observed
 One of the following conditions are observed:
 The forward overreaching element operates.
 When On is set for scheme switch [Dis-WIKT], the undervoltage element UVL
(UVLS or UVLG) operates and the forward overreaching element (ZCSF/ZCGF)
and the reverse looking element (ZCSR/ZCGR) have not operated.

2.12.4 Blocking overreach protection (BOP)


BOP sends a trip block signal if the reverse overreach element operates and the forward
overreaching element dose not operate. Thus, at local terminal, CB tripping is performed when
the forward overreaching element has operated and a trip block signal has not been received
from the opposite terminal.

BOP does not send a trip block signal normally; and a trip block signal is sent only when
the reverse looking element operates. In BOP, a trip block signal is required to send in the
event of an external fault. Hence, failure operation or false operation can be removed when the
communication is performed by power line carrier,

BOP does not receive a trip block signal except by the occurrence of internal fault. If an
external fault occurs in forward, the forward overreaching element at a local terminal issues
a trip signal instantly. However, if an internal fault occurs, the reverse looking element at an
opposite terminal can operate and it transmits a trip block signal. At the local terminal, the
trip block signal will be received in the delay due to the propagation of communication channel.
Therefore, a short delay is required for CB tripping to check for the reception of a trip block
signal.

BOP can trip for any fault along the whole length of the protected line even if an open
terminal exists. A strong infeed terminal operates for all internal faults even if a weak infeed
terminal exists; therefore, ECHO is not required in BOP. WIKT is not applicable in BOP; hence,

GRL200 (Soft 033 & 037)


- 189 -
6F2S1914 (0.37)

the weak infeed terminal cannot operate.

(i) Countermeasure of current reversal (CRL)


BOP has the countermeasure of current reversal, as well as PUP. (For more information of
CRL, see section 2.12.6)

(ii) Scheme logic


Figure 2.12-5 and Figure 2.12-6 show BOP scheme logic. In BOP, a trip block signal is observed
at PLC signal monitoring point (INT.DISCAR-S-*) when the logic level in BOP is equal to “1”.
Conversely, a trip block signal is not observed when the logic level is equal to “0”.

In BOP, a trip block signal is not transmitted. If the reverse overreaching element
operates while the forward overreaching element does not operate, a trip block signal is
transmitted.

A trip block signal is not sent for setting [TREBK-dis] even after the local terminal issues
a trip signal so that command tripping at the remote terminal is secured.

The selection of either the single-phase trip (1P) or the three-phase trip (3P) is carried
out when the trip block signal is not received.

The delayed pick-up timer [TCHD-dis] is provided to allow for the transmission delay for
receipt of the trip block signal from the remote terminal in the event of a forward external
fault.

GRL200 (Soft 033 & 037)


- 190 -
6F2S1914 (0.37)

To carrier
send circuit

DISCAR-CS-A_BOP

DISCAR-CS-B_BOP

DISCAR-CS-C_BOP

DISCAR-CS-S_BOP
8000001B73
DISCAR-OPT-A
8100001B74

From ZS and ZG DISCAR-OPT-B


8200001B75

TCHD-Dis DISCAR-OPT-C
8300001B76
t 0 8000001B68 DISCAR-OPT-
ZCGF-AX &
1 & ≥1
1 8000001B20
t 0
≥1 ≥1 8100001B69 ≥1 DISCAR-TRIP-A
ZCGF-BX & & ≥1 8100001B21
1
≥1 1 ≥1 8200001B6A ≥1 DISCAR-TRIP-B
t 0 ≥1 8200001B22
ZCGF-CX & & ≥1 DISCAR-TRIP-C
1 ≥1
≥1 1

ZCSF-ABX t 0
≥1
& ≥1 &
1 &
t 0
ZCSF-BCX
& &
t 0 1
ZCSF-CAX
& &
1
0.000 to 0.100s 1
≥1
8000001B64

& DISCAR_TPMD
8100001B65 ≥1 1 &
1
≥1
ZCGR-AX Current 8200001B66 & 3P
1
-CX reversal 1 &
ZCGR-BX 8100001B77
logic 8300001B67 &
-CX
ZCGR-CX 1 & ≥1 DISCAR-ARC-BLOCK
(CRL)
-CX 1 &
ZCSF-X & DISCAR-ARCBlk To TRC
-CX 1
ZCSR-X
-CX Block

1 &

1 &

1 &

1 &

Permission signals received:


From Terminal 1
800000EB55 INT.DISCAR-R1-A =1
≥1
&
810000EB56 INT.DISCAR-R1-B =1 ≥1
&
820000EB57 INT.DISCAR-R1-C =1 ≥1 &

830000EB58 INT.DISCAR-R1-S =1 ≥1 ≥1 &

EXT.DISCAR-R1 =1

From Terminal 2

840000EB59 INT.DISCAR-R2-A =1 ≥1

850000EB5A INT.DISCAR-R2-B =1 ≥1

860000EB5B INT.DISCAR-R2-C =1 ≥1

870000EB5C INT.DISCAR-R2-S =1 ≥1 ≥1

EXT.DISCAR-R2 =1
Dis-CAR
BOP

From CARRIER-COMMON
CH1-USE 1

CH2-USE 1
8000001BB0
CAR_BLOCK
≥1
1
800000EBB0 DISCAR_BLK

800000EBBF DISCAR_3PTP

800000EBBF DISCAR_ARCBLOCK

Figure 2.12-5 BOP scheme logic

GRL200 (Soft 033 & 037)


- 191 -
6F2S1914 (0.37)

TSCT-Dis To opposite
t 0 terminal
DISCAR-OPT-A & ≥1 8000001B78
1 &
DISCAR-OPT-B t 0 INT.DISCAR-S-A
& ≥1 8100001B79
1
&
DISCAR-OPT-C t 0 INT.DISCAR-S-B
& 8200001B7A
≥1 1
& INT.DISCAR-S-C
t 0 8300001B7B
& ≥1 1
INT.DISCAR-S-S
&
From Z1G 0.00 to 1.00s
Z1G-TRIP-A
≥1
Z1G-TRIP-B

Z1G-TRIP-C

Z1S-OPT 8F00001B7C
From SOTF-OC ≥1 & & DISCAR-S
OCH-RETRIP
1
DISCAR-CS-A_BOP

DISCAR-CS-B_BOP

DISCAR-CS-C_BOP

DISCAR-CS-S_BOP

800000EB55 DISCAR_F.BLOCK

810000EB56 DISCAR_PERMIT
Dis-CAR
BOP

Figure 2.12-6 Sending circuit of BOP

2.12.5 Protection for week infeed terminal


Both POP and UOP are provided with ECHO and WIKT; both are used for a line including
weak infeed terminals.

(i) ECHO function


With regard to POP, if a terminal receives a trip permission signal when neither forward
overreaching element nor reverse looking element have operated, ECHO sends back the
received signal to the opposite terminal.

With regard to UOP, if a terminal receives a block signal when neither forward
overreaching element nor reverse looking element have operated, ECHO stops sending the
block signal to the opposite terminal.

When CB is open, ECHO sends back the trip permission signal or stops sending the trip
block signal. User can set the time from CB opened to ECHO enabled using setting
[TCARECCB].

The terminal on which the forward overreaching element has operated can issue a trip
signal speedy by using the signal by ECHO.

Once the forward overreaching element or reverse looking element have operated,
transmission of the echo signal is inhibited for 250 ms by delayed drop-off timer T1 even after
these elements are reset.

To prevent any spurious echo signal from looping round between the terminals in a

GRL200 (Soft 033 & 037)


- 192 -
6F2S1914 (0.37)

healthy state, the echo signal is restricted to last for 200 ms by delayed pickup timer T2.

Figure 2.12-7 and Figure 2.12-8 shows ECHO logic. Users can enable ECHO operation
using scheme switch [Dis-ECHO] by setting it to Off.

From ZS and ZG

ZCGF-AX ≥1
ZCGF-BX
ZCGF-CX T1
0 t
1 & ECHO1_CONDITION
ZCGR-AX
0.25s
ZCGR-BX
ZCGR-CX

ZCSF-ABX
ZCSF-BCX
ZCSF-CAX

ZCSR-ABX
ZCSR-BCX
ZCSR-CAX

From PROT-COMMON

CB_ANYPH_CLOSE
TCARECCB
t 0 ECHO2_CONDITION
CB_ANYPH_OPEN

0.00 to 200.00s

Figure 2.12-7 ZCS and ZCG for ECHO/WKIT operation


Permission signals received: 8000001B6B
From Terminal 1 & ECHO_CS-A
T2 ≥1
=1 0 t t 0
800000EB55 INT.DISCAR-R1-A ≥1 1
&

810000EB56 INT.DISCAR-R1-B =1 ≥1 0.05s 0.2s


&
8100001B6C
820000EB57 INT.DISCAR-R1-C =1 ≥1 & ≥1 ECHO_CS-B
&
0 t t 0
830000EB58 INT.DISCAR-R1-S =1 1
≥1 & ≥1
EXT.DISCAR-R1 0.05s 0.2s
=1
8200001B6D
&
From Terminal 2 ≥1 ECHO_CS-C
0 t t 0
& 1
840000EB59 INT.DISCAR-R2-A =1
0.05s 0.2s
850000EB5A INT.DISCAR-R2-B =1 & 8300001B6E
& ≥1 ECHO_CS
860000EB5B INT.DISCAR-R2-C =1 & 0 t t 0
1
870000EB5C INT.DISCAR-R2-S =1 ≥1 & 0.05s 0.2s
EXT.DISCAR-R2 =1

DISCAR=POP+UOP

ECHO1_CONDITION
&
Dis-ECHO On

810000EBBE DIS-ECHO BLOCK 1

& ≥1
DISECHO=ON ≥1
&

& ≥1

& ≥1

&

&

&

&

ECHO2_CONDITION &

Figure 2.12-8 ECHO logic

(ii) WIKT function


Figure 2.12-9 shows WIKT logic. WIKT can issue a trip signal on condition that a trip
permission signal has been received when POP operates. On the other hand, when UOP
operates, WIKT can issue a trip signal when a trip block signal has been stopped.

To operate WIKT, the following conditions are required:

GRL200 (Soft 033 & 037)


- 193 -
6F2S1914 (0.37)

 Undervoltage elements (UVLS or UVLG) being operated.


 Neither forward overreaching element nor reverse looking element being operated.

From PROT COMMON

0 t
UVLG-A
≥1 & WKIT-A_CONDITION
0 t
UVLG-B
≥1 & WKIT-B_CONDITION
0 t
UVLG-C
≥1 & WKIT-C_CONDITION
≥1
≥1 1
UVLS-AB
UVLS-BC TWICOORD
UVLS-CA t 0
&
DEAD_LINE_DEDTECT
1 0.000 to 0.100 s

Figure 2.12-9 UV for WIKT


DISCAR_PARM1-A
& 8000001B6F
≥1 & ≥1
& DISCAR_WITIP-A
DISCAR_PARM1-B
& 8100001B70
≥1 & ≥1
& DISCAR_WITIP-B
DISCAR_PARM1-C 8200001B71
& & ≥1
≥1 & DISCAR_WITIP-C
DISCAR_PARM1 8300001B72
& &
≥1 ≥1 DISCAR_WITIP
From CARRIER-COMMON
CH1-USE 1

DISCAR_PARM1-A
& ≥1
DISCAR_PARM1-B
& ≥1
DISCAR_PARM1-C
&
≥1
DISCAR_PARM1 &
From CARRIER-COMMON ≥1
CH2-USE 1
ECHO1_CONDITION &
DIS-WKIT On

810000EBBE DIS-WKIT BLOCK 1

From CARRIER-COMMON
WKIT-A_CONDITION
WKIT-B_CONDITION
WKIT-C_CONDITION
POP
Dis-CAR UOP ≥1
From Z1G

Figure 2.12-10 WIKT logic

UV responds to three phase-to-phase voltages and three phase-to-ground voltages. UV


prevents false weak infeed tripping due to spurious operation of the channel.

WIKT can be enabled using scheme switch [Dis-WKIT] On.

2.12.6 Countermeasure for current reversal


When a fault occurs on one of the parallel lines, the reversal of fault current may be found on
another line owing to sequential CB opening. In the worst case, the current reversal can result
in false operation in POP, UOP and BOP. Thus, POP, UOP and BOP have current reversal logic
(CRL) to prevent the false operation.

Figure 2.12-11(a) shows the arrangement of parallel lines, as an example. Suppose that
a fault occurs at location F on line L1 at time t1. CBA1 is tripped at time t2; and later, CBB1
is tripped at time t3. The current direction on line L2 can be reversed at time t2. That is, the
current ( ) from terminal B to terminal A is found from time t1 to t2. However, the
current ( ) from terminal A to terminal B is found from time t2 to t3. The current

GRL200 (Soft 033 & 037)


- 194 -
6F2S1914 (0.37)

reversal may be found when an external looped circuit exists if not for parallel lines.

B1
A1 F L1

A B

L2 B2
A2

:Fault current flow before CBA1 being opened


:Fault current flow after CBA1 being opened

(a) Direction of fault current


t1 t2 t3

Forward looking element


A2
Reverse looking element

CRL
TREBK setting

Forward looking element


B2
Reverse looking element

CRL

TREBK setting
(b) Sequence diagram

Figure 2.12-11 Current reversal phenomeon

Figure 2.12-11 (b) shows sequentially the operation of the forward looking element, the
reverse looking element, and CRL on line L2 before and after the occurrence of the current
reversal.

At terminal A2, the forward looking element does not run, but the reverse looking
element runs when the current reversal is yielded. At terminal B2, the forward looking element
runs, but the reverse looking element does not run.

Provided that the forward looking element runs at terminal A2 before the forward looking
element does not run at terminal B2. This may cause false operation of POP, UOP and BOP on
line L2.

GRL200 (Soft 033 & 037)


- 195 -
6F2S1914 (0.37)

Figure shows CRL logic. CRL logic can determine the current reversal when the reverse
looking element runs and the forward looking element does not run. If the current reversal is
found, CRL declares for the opposite terminal to block the trip operation immediately. At the
same time, CRL blocks CB tripping at its own terminal. If the condition of current reversal
continues longer than 20ms, CRL lasts to run for setting [TREBK-Dis] even after the current
reversal ceases.
TREBK-Dis 8000001B64
t 0 0 t
Forward looking element in phase A 1 & DIS-REVBLK-A
≥1
-CX
Reverse looking element in phase A 0.02s 0.00-10.00s

TREBK-Dis 8100001B65
t 0 0 t
Forward looking element in phase B 1 & DIS-REVBLK-B
≥1
-CX
Reverse looking element in phase B 0.02s 0.00-10.00s

TREBK-Dis 8200001B66
t 0 0 t
Forward looking element in phase C 1 & DIS-REVBLK-C
≥1
-CX
Reverse looking element in phase C 0.02s 0.00-10.00s

TREBK-Dis 8300001B67
t 0 0 t
Forward looking element in three-phase 1
& DIS-REVBLK-S
≥1
-CX
Reverse looking element in three-phase 0.02s 0.00-10.00s

Figure 2.12-12 Current reversal logic

The operation of CRL and its effect in the current reversal are follows:
 CRL at terminal A2 runs immediately after the fault occurs.
 The operation of CRL continues to last for another period of off-delay timer setting
[TREBK-dis] even after the reverse looking element does not run and the forward
looking element runs; CRL continuously blocks the local tripping and transmitting a
trip block signal to terminal B2.

Even if operation overlap of the forward looking elements between terminal A2 and
terminal B2 arises due to the current reversal, the operation overlap will disappear during the
operation of CRL. Thus, the false operation on the healthy line of parallel lines can be removed.
When the current reversal occurs in the direction opposite to the above, CRL at terminal B2
will respond similarly.

CRL does not pick up for internal faults; thus, high-speed operation of any protection
scheme is not obstructed.

2.12.7 Programing DISCAR using PLC function


It is required to make the connection between the DISCAR function and the DIF_COMM
function. This is because the DISCAR function needs to operate with the communication. The
PLC function can provide the means of the connections; see Chapter PLC function.

GRL200 (Soft 033 & 037)


- 196 -
6F2S1914 (0.37)

2.12.8 Setting
CARCOM(Function ID: 438001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
CAR-CHNUM 2-TERM / 3-TERM - Carrier scheme terminal number 2-TERM
TCARECCB 0.00 - 200.00 s Echo enable timer from CB opened 0.10
TWICOORD 0.000 - 0.100 s Time coordination for UV relay operation 0.000

DISCAR (Function ID: 436001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Carrier_Distance Dis-CAR Off/PUP/POP/UOP/BOP DISCAR scheme enable Off
PUP/POP/UOP/BOP Dis-ECHO Off / On - Echo function enable Off
Dis-WKIT Off / On - Weak infeed trip function enable Off
DisCAR-CHSEL Single / And / Guard - Carrier channel configuration Single
TREBK-Dis 0.00 - 10.00 s Current reverse blocking time 0.10
TCHD-Dis 0.000 - 0.100 s Coordination timer in BOP function 0.012
TSBCT-Dis 0.00 - 1.00 s SBCNT timer 0.10
Output Distance carrier trip mode, phase segregated trip or
DisCAR-TPMD 1P / 3P - 1P
3-phase trip
DisCAR-ARCBlk Non / Block - Autoreclose block by distance carrier trip Non

GRL200 (Soft 033 & 037)


- 197 -
6F2S1914 (0.37)

2.12.9 Data ID
 Signal monitoring point
CARRIER_COMMON (Function ID: 438001)
Element ID Name Description
8000001BB0 CAR_BLOCK Carrier block signal

8000001B67 CH1-USE Channel 1 use

8100001B68 CH2-USE Channel 2 use

8400001B64 ECH01_CONDITION Echo1 condition

8500001B65 ECH02_CONDITION Echo2 condition

8000001B61 WKIT-A_CONDITION Weak infeed trip A phase condition

8100001B62 WKIT-B_CONDITION Weak infeed trip B phase condition

8200001B63 WKIT-C_CONDITION Weak infeed trip C phase condition

 Connection point on PLC logic


CARRIER_COMMON (Function ID: 438001)
Element ID Name Description
800000EBB0 CAR_BLOCK Carrier block signal

 Signal monitoring point


DISCAR(Function ID: 436001)
Element ID Name Description
8000001B60 EXT.DISCAR-R1

8000001B61 LOSS-DISCAR1

8100001B62 EXT.DISCAR-R2

8100001B63 LOSS-DISCAR2

8000001B64 DIS-REVBLK-A

8100001B65 DIS-REVBLK-B

8200001B66 DIS-REVBLK-C

8300001B67 DIS-REVBLK-S

8000001B68 PPUB_TRIP-A PPUB trip signal(phase-A)

8100001B69 PPUB_TRIP-B PPUB trip signal(phase-B)

8200001B6A PPUB_TRIP-C PPUB trip signal(phase-C)

8000001B6B ECHO_CS-A

8100001B6C ECHO_CS-B

8200001B6D ECHO_CS-C

8300001B6E ECHO_CS

8000001B6F DISCAR_WITRIP-A WI trip signal(phase-A)

8100001B70 DISCAR_WITRIP-B WI trip signal(phase-B)

8200001B71 DISCAR_WITRIP-C WI trip signal(phase-C)

8300001B72 DISCAR_WITRIP

8000001B73 DISCAR-OPT-A DISCAR operation(phase-A)

8100001B74 DISCAR-OPT-B DISCAR operation(phase-B)

8200001B75 DISCAR-OPT-C DISCAR operation(phase-C)

8300001B76 DISCAR-OPT DISCAR operation

8000001B20 DISCAR-TRIP-A Distance carrier trip signal(phase-A)

8100001B21 DISCAR-TRIP-B Distance carrier trip signal(phase-B)

GRL200 (Soft 033 & 037)


- 198 -
6F2S1914 (0.37)

 Signal monitoring point


DISCAR(Function ID: 436001)
Element ID Name Description
8200001B22 DISCAR-TRIP-C Distance carrier trip signal(phase-C)

8100001B77 DISCAR-ARC-BLOCK Distance carrier ARC block signal

8000001B78 INT.DISCAR-S-A

8100001B79 INT.DISCAR-S-B

8200001B7A INT.DISCAR-S-C

8300001B7B INT.DISCAR-S-S

8F00001B7C DISCAR-S

8800001B7E DISCAR-OPT-AR Distance carrier operation(phase-A)

8900001B7F DISCAR-OPT-BR Distance carrier operation(phase-B)

8A00001B80 DISCAR-OPT-CR Distance carrier operation(phase-C)

8C00001B81 DISCAR-OPT-ABR Distance carrier operation(phase-AB)

8D00001B82 DISCAR-OPT-BCR Distance carrier operation(phase-BC)

8E00001B83 DISCAR-OPT-CAR Distance carrier operation(phase-CA)

8000001BB0 DISCAR_BLOCK Distance carrier block signal

8000001BB1 DISCAR-R1

8000001BB2 DISCAR-R1-2

8100001BB3 DISCAR-R2

8100001BB4 DISCAR-R2-2

 Connection point on PLC logic


DISCAR(Function ID: 436001)
Element ID Name Description
800000EBB0 DISCAR_BLOCK Distance carrier block signal

800000EBB1 DISCAR-R1

800000EBB2 DISCAR-R1-2

810000EBB3 DISCAR-R2

810000EBB4 DISCAR-R2-2

800000EBB5 INT.DISCAR-R1-A

810000EBB6 INT.DISCAR-R1-B

820000EBB7 INT.DISCAR-R1-C

830000EBB8 INT.DISCAR-R1-S

840000EBB9 INT.DISCAR-R2-A

850000EBBA INT.DISCAR-R2-B

860000EBBB INT.DISCAR-R2-C

870000EBBC INT.DISCAR-R2-S

800000EBBD DIS-ECHO BLOCK

810000EBBE DIS-WKIT BLOCK

800000EBBF DISCAR_3PTP DISCAR 3phase trip command

810000EBC0 DISCAR_ARCBLOCK DISCAR ARC block command

800000EBC1 DISCAR_F.BLOCK

810000EBC2 DISCAR_F.PERMIT

GRL200 (Soft 033 & 037)


- 199 -
6F2S1914 (0.37)

Directional earth fault command protection (DEFCAR)


Directional earth fault command protection (DEFCAR) provides POP, UOP and BOP
techniques† using two elements of earth fault protection between in forward and in reverse
(DEFCF and DEFCR‡). POP, UOP and BOP can issue either a single-pole trip (1P) or three-
phase trip (3P). These can also enable to run the function of autoreclose (ARC). User can select
either first tripping or delayed tripping in DEFCAR with set of delay timer. Thus, it is possible
to give priority to the function of distance carrier protection (DISCAR) so that DISCAR runs
faster than DEFCAR. DEFCAR send a trip block signal for the opposite terminal when one or
two poles in CB are open and when the failure of voltage transformer occurs.

†Note:When both DISCAR and DEFCAR are used mutually for the command protection,
user should coordinate the technique between DISCAR and DEFCAR. For the
selection of the techniques in DEFCAR, see section 2.12.
‡Note:In DEFCAR, EF1 is used for a forward element (DEFCF); EF2 is used for a
reverse element (DEFCR). Both EF1 and EF2 are the function of earth fault
protection (EF). For more information, see Chapter Relay application: Earth fault
protection.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have carrier features. To determine whether the features
are implemented in the IED or not, locate the IED ordering number; and check the order
number at “G&T position” referring to the comparison table below. For more information, see
Appendix: Ordering.
Table 2.13-1 Comparative table in respective ordering numbers
feature Ordering No. at “G&T” 33 37
DEFCAR Directional-earth-fault carrier command protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 200 -
6F2S1914 (0.37)

2.13.1 Permissive overreach protection (POP)


DEFCAR sends a trip permission signal in POP; and POP does not send a trip permission
signal for non-internal fault. Figure 2.13-1 shows POP scheme logic. The elements of OCD are
used to select a phase which should be tripped in CB.

When POP receives a trip permission signal, POP issues a trip signal on condition that
DEFCF has operated. To assure issuing a trip signal at the opposite terminal, POP continues
to send a trip permission signal for setting [TSBCT-DEF] after DEFCF stops. (Figure 2.13-2)

DEFCR is used for CRL as a revers looking element; DEFCF is used as a forward looking
element, as shown in Figure 2.13-3. (For more information of CRL, see section 2.12.6) When
DEFCR runs but DEFCF continues to stop for 20 ms or more—even if DEFCF starts to run or
DEFCR stops later—tripping CB at local terminal or transmission of the trip permission signal
is blocked for setting [TREBK-DEF].

In POP, users can delay the DEFCAR sending using settings [TDEFCF] and [TDEFCB].
Users can also delay the DEFCAR tripping using setting [TDEFC]. Thus, if users wish to carry
out the DEFCAR sending and the DEFCAR tripping separately, users should set a value for
the setting [TDEFCF] and another value for the setting [TDEFC]. For example, when 0 ms set
for the [TDEFCF] and 50 ms set for the [TDEFC], the DEFCAR sending is performed faster
than the DEFCAR tripping. (See section 2.13.4 for more information)

POP can provide ECHO and WKIT functions, which are used for the line having weak
infeed terminals. ECHO allows fast CB tripping at the terminal on which DEFCF has operated
when applied to the line having an open terminal or a weak infeed earth fault current terminal.
(Figure 2.13-4 to Figure 2.13-7) (For more information of ECHO and WKIT, see section 2.12.5)

When a trip permission signal is received if neither DEFCF nor DEFCR operates, ECHO
sends back the received signal to the opposite terminal. When CB is open, ECHO also sends
back the trip permission signal.

Once DEFCF or DEFCR operates, ECHO inhibits to send the echo signal for 250 ms by
delayed drop-off timer T1 even after DEFCF and DEFCR stop to operate.

In order to prevent any spurious echo signal from looping round between terminals in a
healthy state, sending ECHO signal is restricted for 200 ms by delayed pick-up timer T2. Echo
can operate using scheme switch [DEF-ECHO] On.

GRL200 (Soft 033 & 037)


- 201 -
6F2S1914 (0.37)

To CRL
TDEFCB 8400001B68
From EF (EF2)
t 0 DEFCR-X
DEFCR &
-CX 0.00 to 0.30s
8300001B67
≥1 DEFCF-X
From VTF
≥1 To carrier send circuit
VTF_DETECT
From PROT COMMON 1 DEFCAR-CS-A_POUP

CB_LOSS_PHASE DEFCAR-CS-B_POUP

DEFCAR-CS-C_POUP

8000001B74
& DEFCAR-OPT-AR
8100001B75
& DEFCAR-OPT-BR
8200001B76
& DEFCAR-OPT-CR
TDEFCF TDEFC 8300001B77
DEFCF t 0 0 8000001B6A DEFCAR-OPT-S
& & &
t
-CX &
From PROT-COMMON ≥1 8000001B20
& &
t 0 t 0 8100001B6B ≥1 DEFCAR-TRIP-A
OCD-AT S & & ≥1 8100001B21
& 8200001B6C
-CX R ≥1 t 0 ≥1 DEFCAR-TRIP-B
≥1 & t 0
≥1 8200001B22
OCT-BT & &
S ≥1 DEFCAR-TRIP-C
-CX 0.00 to 0.30s 0.00 to 0.30s
R ≥1 ≥1
OCT-CT S Week infeed ≥1
-CX R ≥1 ≥1 trip logic &
(WIKT)

1 ≥1 1

Current
800000EBBB EFF PHSEL-A Reversal 1
Logic ≥1
800000EBBC EFF PHSEL-B (CRL)
DEFCAR_TPMD
800000EBBD EFF PHSEL-C 3P
1P DEFCAR-TPMD=1P
8100001B77
& DEFCAR-ARC-BLOCK
Permission signals received: ≥1
From Terminal 1
DEFCAR-ARCBlk
800000EBB5 INT.DEFCAR-R1-A =1 To TRC
≥1 ≥1
& Block
810000EBB6 INT.DEFCAR-R1-B =1 ≥1 ≥1
&
820000EBB7 INT.DEFCAR-R1-C =1 ≥1 ≥1 &

EZT.DISCAR-R1 =1

From Terminal 2
DEFCAR_PERM1-A
840000EBB8 INT.DEFCAR-R2-A =1 ≥1 ≥1 DEFCAR_PERM1-B
DEFCAR_PERM1-C
850000EBB9 INT.DEFCAR-R2-B =1 ≥1 ≥1

860000EBBA INT.DEFCAR-R2-C =1 ≥1 ≥1

DEFCAR_PERM2-A
EZT.DISCAR-R2
=1 DEFCAR_PERM2-B
DEFCAR UOP
DEFCAR_PERM2-C
POP

From CARRIER-COMMON To ECHO/EIKT


CH1-USE 1

CH2-USE 1

CAR_BLOCK
≥1
1
800000EBB0 DEFCAR_BLK

810000EBC1 DEFCAR_3PTP

800000EBC0 DEFCAR_ARCBLOCK

Figure 2.13-1 POP and UOP scheme logic

TSBCT-DEF
t 0
DEFCAR-OPT-A
t 0
DEFCAR-OPT-B
t 0
DEFCAR-OPT-C
0.00 to 1.00s

8000001B79
DEFCAR-CS-A_POUP ≥1 =1 INT.DEFCAR-S-A
8100001B7A
DEFCAR-CS-B_POUP ≥1 =1 INT.DEFCAR-S-B
8200001B7B
DEFCAR-CS-C_POUP INT.DEFCAR-S-C
≥1 =1

≥1
ECHO logic =1
& ≥1 &
≥1 8F00001B7C
1
DEFCAR-S

≥1 & &
800000EBC2 DEFCAR_F.BLOCK
1

810000EBC3 DEFCAR_PERMIT

DEFCAR UOP
POP

Figure 2.13-2 Sending circuit in POP and UOP

GRL200 (Soft 033 & 037)


- 202 -
6F2S1914 (0.37)

TREBK-DEF 8000001B69
t 0 t 0
DEFCF-X & DEF-REVBLK
≥1
-CX 1 -CX
DEFCR-X 0.02s 0.0s
-CX

Figure 2.13-3 Current reversal logic

From PROT COMMON

0 t
UVLG-A
≥1 & WKIT-A_CONDITION
0 t
UVLG-B
≥1 & WKIT-B_CONDITION
0 t
UVLG-C
≥1 & WKIT-C_CONDITION
≥1
≥1 1
UVLS-AB
UVLS-BC TWICOORD
UVLS-CA t 0
&
DEAL_LINE_DEDTECT
1 0.000 to 0.100 s

Figure 2.13-4 UVL for WKIT operation


DEFCAR_PARM1-A TDEFC
& 8000001B70
≥1 & t 0
& DEFCAR_WITIP-A
DEFCAR_PARM1-B
& & 8100001B71
≥1 t 0
& DEFCAR_WITIP-B
DEFCAR_PARM1-C 8200001B72
& &
≥1 & t 0 DEFCAR_WITIP-C
8300001B73

0.00 to 0.30s ≥1 DEFCAR_WITIP


From CARRIER-COMMON
CH1-USE 1

DEFCAR_PARM1-A
& ≥1
DEFCAR_PARM1-B
& ≥1
DEFCAR_PARM1-C
&
≥1
From CARRIER-COMMON
CH2-USE 1
ECHO1_CONDITION &
DEF-WKIT On
CAR

810000EBBE DEF-WKIT BLOCK 1

From CARRIER-COMMON
WKIT-A_CONDITION
WKIT-B_CONDITION
WKIT-C_CONDITION
POP
≥1
UOP
DEFCAR BOP

Figure 2.13-5 WKIT logic

From CARRIER_COMMON
T1
DEFCFX
≥1 0 t
1 & ECHO1_CONDITION
DEFCRX
0.25s
From PROT-COMMON
CB_ANYPH_CLOSE
TCARECCB
t 0 ECHO2_CONDITION
CB_ANYPH_OPEN

0.00 to 200.00s

Figure 2.13-6 EF for ECHO/WKIT operation

GRL200 (Soft 033 & 037)


- 203 -
6F2S1914 (0.37)

Permission signals received: 8000001B6E


&
From Terminal 1 T2 DEF-ECHO_CS-A
≥1
=1 0 t t 0
800000EB55 INT.DEFCAR-R1-A ≥1 1
&

810000EB56 INT.DEFCAR-R1-B =1 ≥1 0.05s 0.2s


&
8100001BE
820000EB57 INT.DEFCAR-R1-C =1 ≥1 & ≥1 DEF-ECHO_CS-B
&
0 t t 0
1

0.05s 0.2s
8000001B6F
& DEF-ECHO_CS-C
From Terminal 2 ≥1
0 t t 0
& 1
840000EBB8 INT.DEFCAR-R2-A =1
0.05s 0.2s
850000EBB9 INT.DEFCAR-R2-B =1 &

860000EBBA INT.DEFCAR-R2-C =1 &

POP
DEFCAR ≥1
UOP

ECHO1_CONDITION &

DEF-ECHO On

810000EBBE DEF-ECHO BLOCK 1

& ≥1

≥1
&

& ≥1

&

&

&

ECHO2_CONDITION &

Figure 2.13-7 ECHO logic

2.13.2 Unblocking overreach protection (UOP)


DEFCAR sends a trip block signal in UOP. Thus, UOP stops to send a trip block signal for an
internal fault. Settings and operation of UOP is the same as POP.

2.13.3 Blocking overreach protection (BOP)


BOP send a trip block signal except for an internal fault. When DEFCF operates, BOP issues
a trip single unless a trip blocking single is received.

The delayed pick-up timer [TCHD-DEF] is provided to allow for the transmission delay of the
trip block signal from the opposite terminal. Therefore, user should set a time depending on
the delay of communication channel.
Setting [TCHD-DEF] = maximum signal transmission delay time†+ 5ms
†Note: Including operation time of circuits of Binary IO modules; these circuits are used
to send/receive a trip blocking signal.

For setting [TREBK-DEF], see section 2.13.1.

GRL200 (Soft 033 & 037)


- 204 -
6F2S1914 (0.37)

To CRL
TDEFCB 8400001B68
From EF (EF2) DEFCR-X
t 0
DEFCR &
-CX 0.00 to 0.30s
From VTF 8300001B67
≥1 ≥1 DEFCF-X
VTF_DETECT
From PROT COMMON 1

CB_LOSS_PHASE

From EF (EF1)
TDEFCF 8000001B64
DEFCF t 0 DEFCF-AX
& &
-CX
From PROT-COMMON 8100001B65
& t 0 DEFCF-BX
&
OCD-AT S
& t 0 8200001B66
-CX R ≥1 &
≥1
DEFCF-CX
OCT-BT S
-CX 0.00 to 0.30s
R ≥1 ≥1
OCT-C S
-CX R ≥1 ≥1

1 ≥1 1

800000EBBB EFF PHSEL-A

800000EBBC EFF PHSEL-B

800000EBBD EFF PHSEL-C

Figure 2.13-8 OCD circuit for BOP

8000001B74

& DEFCAR-OPT-A
8100001B75

& DEFCAR-OPT-B
8200001B76

& DEFCAR-OPT-C
TCHD-DEF TDEFC
t 0 8000001B6A
DEFCF-AX & t 0
& 8000001B20
t 0 8100001B6B ≥1
DEFCF-BX t 0 ≥1 DEFCAR-TRIP-A
& & ≥1 8100001B21
8200001B6C
DEFCF-CX t 0 ≥1 DEFCAR-TRIP-B
t 0 8200001B22
& ≥1
& ≥1 DEFCAR-TRIP-C
0.00 to 0.100s
0.00 to 0.30s

Week infeed ≥1
trip logic &

Current
Reversal 1
detection ≥1
logic
DEFCAR_TPMD
3P
1P

8100001B77
Permission signals received: ≥1 & DEFCAR-ARC-BLOCK
From Terminal 1
=1 DEFCAR-ARCBlk
800000EBB5 INT.DEFCAR-R1-A ≥1 ≥1 To TRC
& Block
850000EBB6 INT.DEFCAR-R1-B =1 ≥1 ≥1
&
820000EBB7 INT.DEFCAR-R1-C =1 ≥1 ≥1 &

800000EBB1 DEFCAR-R1 =1

From Terminal 2
DEFCAR_PERM1-A
840000EBB8 INT.DEFCAR-R2-A =1 ≥1 ≥1 DEFCAR_PERM1-B
DEFCAR_PERM1-C
850000EBB9 INT.DEFCAR-R2-B =1 ≥1 ≥1

860000EBBA INT.DEFCAR-R2-C =1 ≥1 ≥1

DEFCAR_PERM2-A
810000EBB3 DEFCAR-R2 DEFCAR_PERM2-B
=1
DEFCAR DEFCAR_PERM2-C
BOP To ECHO/EIKT
From Terminal 2
CH1-USE 1

CH2-USE

CAR_BLOCK
≥1
1
800000EBB0 DEFCAR_BLK

810000EBC1 DEFCAR_3PTP

800000EBC0 DEFCAR_ARCBLOCK

Figure 2.13-9 BOP scheme logic

GRL200 (Soft 033 & 037)


- 205 -
6F2S1914 (0.37)

DEF-REVBLK

& 8000001B79
& INT.DEFCAR-S-A
& 1
8100001B7A
& INT.DEFCAR-S-B
& 1 8200001B7B
& INT.DEFCAR-S-C
1
TSBCT-DEF
t 0
DEFCAR-OPT-A
t 0
DEFCAR-OPT-B ≥1
t 0
DEFCAR-OPT-C

8F00001B7C
800000EB55 DEFCAR_F.BLOCK ≥1 &
& DEFCAR-S

810000EB56 DEFCAR_PERMIT
1

DEFCAR BOP

Figure 2.13-10 Sending circuit of BOP

2.13.4 Coordination with DISCAR protection


The DEFCAR function, as rule, is used together with the distance carrier command protection
(DISCAR†); hence, the user is required to establish the coordination between the DEFCAR
function and the DISCAR function so that both can operate without interference. The
followings exemplify how to establish the coordination using the DEFCAR settings sand
signals.
†Note:For more information of the DISCAR, see chapter Relay application: Distance
carrier command protection.

(i) DISCAR and DEFCAR signals being separated


When the DISCAR signal and the DEFCAR signal are used separately, the user should set 0
for the [TDEFCF]. Consequently, the DEFCAR function can trip in TDEFC after the reception
of the DEFCAR signal. Figure 2.13-11 shows the relationship of sending-signal, receiving-
signal, and tripping in the DEFCAR function.

DEFCAR pickup

BO Off delay
[TDEFCF]=0ms

Sending DEFCAR signal

Communication delay

Receiving DEFCAR signal


[TDEFC]

DEFCAR issuing a trip signal

Figure 2.13-11 Sending signal and receiving signal in DEFCAR


Note: It is recommend prolonging DEFCAR signal.

(ii) DISCAR and DEFCAR signals being shared


When the DISCAR signal and the DEFCAR signal are used as a shared signal, the user should
set should set 0 for the [TDEFC]. Consequently, the DEFCAR function can issue a trip signal

GRL200 (Soft 033 & 037)


- 206 -
6F2S1914 (0.37)

after the reception of the DEFCAR signal that is prolonged by the setting [TDEFCF]. Figure
2.13-12 shows the relationship of sending-signal, receiving-signal, and tripping in the
DEFCAR function.

DEFCAR pickup

[TDEFCF] BO Off delay

Sending DEFCAR signal

Communication delay

Receiving DEFCAR signal


[TDEFC]=0

DEFCAR issuing a trip signal

Figure 2.13-12 Sending signal and receiving signal shared in DEFCAR

2.13.5 Programing DEFCAR using PLC function


It is required to make the connection between the DEFCAR function and the DIF_COMM
function. This is because the DEFCAR function needs to operate with the communication. The
PLC function can provided the means of the connections; see Chapter PLC function.

GRL200 (Soft 033 & 037)


- 207 -
6F2S1914 (0.37)

2.13.6 Setting
DEFCAR (Function ID: 437001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Carrier_DEF DEF-CAR Off/POP/UOP/BOP DISCAR scheme enable Off
DEF-ECHO Off / On - Echo function enable Off
DEF-WKIT Off / On - Weak infeed trip function enable Off
DEFCAR-CHSEL Single / And / Guard - Carrier channel configuration Single
TDEFCF 0.00 - 0.30 s DEF carrier trip delay time 0.15
TDEFCB 0.00 - 0.30 s DEF carrier trip delay time 0.15
TDEFC 0.00 - 0.30 s DEF carrier trip delay time 0.00
TREBK-DEF 0.00 - 10.00 s Current reverse blocking time 0.10
TCHD-DEF 0.000 - 0.100 s Coordination timer in BOP function 0.012
TSBCT-DEF 0.00 - 1.00 s SBCNT timer 0.10
Output DEF carrier trip mode, phase segregated trip or 3-
DEFCAR-TPMD 1P / 3P - 3P
phase trip
DEFCAR-ARCBlk Non / Block - Autoreclose block by DEF carrier trip Block

GRL200 (Soft 033 & 037)


- 208 -
6F2S1914 (0.37)

2.13.7 Data ID
 Signal monitoring point
CARRIER_DEF (Function ID: 437001)
Element ID Name Description
8000001BBB DEF PHSEL-A DEF selected A phase

8100001BBC DEF PHSEL-B DEF selected B phase

8200001BBD DEF PHSEL-C DEF selected C phase

8000001BBE DEF-ECHO BLOCK Echo function blocked

8000001B6D DEF-ECHO_CS-A ECHO carrier send (A phase)

8100001B6E DEF-ECHO_CS-B ECHO carrier send (B phase)

8200001B6F DEF-ECHO_CS-C ECHO carrier send (C phase)

8000001B69 DEF-REVBLK

8100001BBF DEF-WKIT BLOCK Weak infeed trip function blocked

8100001B78 DEFCAR-ARC-BLOCK ARC block signal by DEF carrier

8300001B77 DEFCAR-OPT DEF carrier operation (3-phases OR)

8000001B74 DEFCAR-OPT-A DEF carrier operation of A phase

8800001B7E DEFCAR-OPT-AR DEF carrier operation of A phase (For record)

8100001B75 DEFCAR-OPT-B DEF carrier operation of B phase

8900001B7F DEFCAR-OPT-BR DEF carrier operation of B phase (For record)

8200001B76 DEFCAR-OPT-C DEF carrier operation of C phase

8A00001B80 DEFCAR-OPT-CR DEF carrier operation of C phase (For record)

8000001BB1 DEFCAR-R1 DEF carrier received from remote 1

8000001BB2 DEFCAR-R1-2 DEF carrier received from remote 1-2

8100001BB3 DEFCAR-R2 DEF carrier received from remote 2

8100001BB4 DEFCAR-R2-2 DEF carrier received from remote 2-2

8F00001B7C DEFCAR-S DEF carrier send (3-phases OR)

8000001B20 DEFCAR-TRIP-A DEF carrier trip of A phase

8100001B21 DEFCAR-TRIP-B DEF carrier trip of B phase

8200001B22 DEFCAR-TRIP-C DEF carrier trip of C phase

8000001B83 DEFCAR=ON DEF carrier scheme enabled condition

8000001BC0 DEFCAR_3PTP DEF Carrier 3 phase trip

8100001BC1 DEFCAR_ARCBLOCK ARC block signal by DEF carrier

8000001BB0 DEFCAR_BLOCK DEF carrier block signal

8000001BC2 DEFCAR_F.BLOCK Blocked DEF carrier send

8100001BC3 DEFCAR_F.PERMIT Permitted DEF carrier send

8300001B73 DEFCAR_WITRIP Weak infeed trip (3-phases OR)

8000001B70 DEFCAR_WITRIP-A Weak infeed trip of A phase

8100001B71 DEFCAR_WITRIP-B Weak infeed trip of B phase

8200001B72 DEFCAR_WITRIP-C Weak infeed trip of C phase

8000001B64 DEFCF-AX DEF carrier A phase (Forward)

8100001B65 DEFCF-BX DEF carrier B phase (Forward)

8200001B66 DEFCF-CX DEF carrier C phase (Forward)

8300001B67 DEFCF-X DEF carrier 3-phases OR (Forward)

8400001B68 DEFCR-X DEF carrier (Reverse)

8000001B6A DEFPPUB_TRIP-A DEF carrier trip of A phase (For POP+UOP)

8100001B6B DEFPPUB_TRIP-B DEF carrier trip of B phase (For POP+UOP)

8200001B6C DEFPPUB_TRIP-C DEF carrier trip of C phase (For POP+UOP)

GRL200 (Soft 033 & 037)


- 209 -
6F2S1914 (0.37)

 Signal monitoring point


CARRIER_DEF (Function ID: 437001)
Element ID Name Description
8000001B60 EXT.DEFCAR-R1 External DEF carrier received from remote 1

8100001B62 EXT.DEFCAR-R2 External DEF carrier received from remote 2

8000001BB5 INT.DEFCAR-R1-A DEF carrier of A phase received from remote 1 (Integral type)

8100001BB6 INT.DEFCAR-R1-B DEF carrier of B phase received from remote 1 (Integral type)

8200001BB7 INT.DEFCAR-R1-C DEF carrier of C phase received from remote 1 (Integral type)

8400001BB8 INT.DEFCAR-R2-A DEF carrier of A phase received from remote 2 (Integral type)

8500001BB9 INT.DEFCAR-R2-B DEF carrier of B phase received from remote 2 (Integral type)

8600001BBA INT.DEFCAR-R2-C DEF carrier of C phase received from remote 2 (Integral type)

8000001B79 INT.DEFCAR-S-A DEF carrier of A phase send (Integral type)

8100001B7A INT.DEFCAR-S-B DEF carrier of B phase send (Integral type)

8200001B7B INT.DEFCAR-S-C DEF carrier of C phase send (Integral type)

8000001B61 LOSS-DEFCAR1 DEF carrier loss condition for remote 1

8100001B63 LOSS-DEFCAR2 DEF carrier loss condition for remote 2

 Connection point on PLC logic


CARRIER_DEF (Function ID: 437001)
Element ID Name Description
800000EBBB DEF PHSEL-A DEF selected A phase

810000EBBC DEF PHSEL-B DEF selected B phase

820000EBBD DEF PHSEL-C DEF selected C phase

800000EBBE DEF-ECHO BLOCK Echo function blocked

810000EBBF DEF-WKIT BLOCK Weak infeed trip function blocked

800000EBB1 DEFCAR-R1 DEF carrier received from remote 1

800000EBB2 DEFCAR-R1-2 DEF carrier received from remote 1-2

810000EBB3 DEFCAR-R2 DEF carrier received from remote 2

810000EBB4 DEFCAR-R2-2 DEF carrier received from remote 2-2

800000EBC0 DEFCAR_3PTP DEF Carrier 3 phase trip

810000EBC1 DEFCAR_ARCBLOCK ARC block signal by DEF carrier

800000EBB0 DEFCAR_BLOCK DEF carrier block signal

800000EBC2 DEFCAR_F.BLOCK Blocked DEF carrier send

810000EBC3 DEFCAR_F.PERMIT Permitted DEF carrier send

800000EBB5 INT.DEFCAR-R1-A DEF carrier of A phase received from remote 1 (Integral type)

810000EBB6 INT.DEFCAR-R1-B DEF carrier of B phase received from remote 1 (Integral type)

820000EBB7 INT.DEFCAR-R1-C DEF carrier of C phase received from remote 1 (Integral type)

840000EBB8 INT.DEFCAR-R2-A DEF carrier of A phase received from remote 2 (Integral type)

850000EBB9 INT.DEFCAR-R2-B DEF carrier of B phase received from remote 2 (Integral type)

860000EBBA INT.DEFCAR-R2-C DEF carrier of C phase received from remote 2 (Integral type)

GRL200 (Soft 033 & 037)


- 210 -
6F2S1914 (0.37)

Switch on to fault (SOTF-OC)


The switch-onto-fault function (SOTF-OC) is used to detect and rapidly clear faults when
circuit breakers (CBs) are closed onto a pre-existing fault in the protected zone. If a circuit
breaker is closed onto a permanent fault, the memory circuit in the IED will be unable to
memorize the voltage data required to retain the pre-fault values. This is because the voltage
input to distance measuring elements is absent continuously prior to and after the fault
particularly with voltage transformers installed on the line side; as a result, the fault cannot
be detected by conventional standard protection functions. Therefore, in order to avoid such
failures, SOTF-OC is applied so that the fault can be detected for a specific period following
the closure of the CB.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have switch-on-to-fault features. To determine whether the
features are implemented in the IED or not, locate the IED ordering number; and check the
order number at “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 2.14-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
SOTF-OC Switch on to fault protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 211 -
6F2S1914 (0.37)

2.14.1 Scheme logic


The SOTF-OC function provides signals to the TRC function: SOTFOC-OPT-A,-B,-C, SOTFOC-
TRIP, and SOTFOC-ARC-BLOCK. The SOTF-OC function issues a trip signal upon the
operation of the OCSOTF element if CBs are closed onto a fault when energizing a
transmission line following a period of non-operation. The criterion for the transmission line
being in the non-operation state are when (1) the CBs are open for more than 0.5 seconds and
(2) the undervoltage elements in the PROT COMMON function remain operated for more than
0.5 seconds. The TRIP and PROT COMMON functions are discussed separately. (See chapter
Relay application: Trip circuit and Protection common.)

Setting [OCSOTF] is provided to determine the SOTF threshold. Setting [OCSOTF-2fBlk]


is used to override the SOTF function when the SOTF-OC detects a second harmonic. If Block-
3P is set for the setting [OCSOTF-2fBlk], all of the OCSOTF elements are overridden when
second harmonic is present. Alternatively, if Block-PerP is set for the setting [OCSOTF-2fBlk],
each individual OCSOTF element of the SOTF function is overridden for second harmonic
currents. The detection of the second harmonic is determined by the function of the inrush
current detector (ICD). The ICD function is discussed separately. (See chapter Relay
application: Inrush current detection function.)

The SOTF-OC function is active when On is set for the setting [SOTFOC-EN]. Setting
[SOTF-test] is used for the mandatory condition of cold load when testing. When wishing to
add another condition into the logic for the SOTF operation, the user can inject the signal using
PLC connection point “ADD.SOTF.EN”.

GRL200 (Soft 033 & 037)


- 212 -
6F2S1914 (0.37)

To DISCAR
800000EBB1 OC-RTP.EN
OC-RETRIP
From ARC & To TRC
SHOT_MULTI ≥1 SOTFOC-TRIP

8000001B60
≥1
SOTFOC-ARC-BLOCK
≥1
8000011C20

A & & 8800011B62


8100011C21 & SOTFOC-OPT-A
OCSOTF B & & 8900011B63
8200011C22 & SOTFOC-OPT-B
C & & 8A00011B64
& SOTFOC-OPT-C

From ICD
ICD-A & ≥1

ICD-B & ≥1
To Recording

ICD-C & ≥1
SOTFOC-TRIP

≥1
&

Block-PerP
OCSOTF-2PBlk
Block-3P

SOTFOC-EN On

800000EBB0 SOTFOC_BLOCK 1 &

From PROT COMMON

DEAD_LINE_DETECT
≥1 To ZS,ZG
800000EBB2 ADD.SOTF_EN 0 t
SOTF_EN_COND
SOTF-Test On 0.5s

Figure 2.14-1 Scheme logic for the SOTF-OC

GRL200 (Soft 033 & 037)


- 213 -
6F2S1914 (0.37)

2.14.2 Setting
SOTF-OC(Function ID: 454001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
SOTFOC-EN Off / On - SOTF-OC protection enable Off
0.02 - 0.10 -
OCSOTF A OC relay for SOTF threshold 1.20 6.00
3.00 15.00
Non / Block-3P /
OCSOTF-2fBlk - OCSOTF operation block by 2f-detection Non
Block-PerP

Test tool (Function ID: 454001)


Range Default
Item Unit Contents Note
1A rating 5A rating 1A 5A
Function test SOTF-Test Off / On - Test cold load state given with setting Off

2.14.3 Data ID
 Monitoring point for operation
SOTF-OC(Function ID: 454001)
Element ID Name Description
8000001BB2 ADD.SOTF_EN Additional SOTFOC enable

8000001B67 OC-RETRIP OC-RETRIP

8000001BB1 OC-RTP.EN OC-retrip enable

8000001C20 OCSOTF-A SOTFOC relay element operated (phase-A)

8100001C21 OCSOTF-B SOTFOC relay element operated (phase-B)

8200001C22 OCSOTF-C SOTFOC relay element operated (phase-C)

8000001B60 OCSOTF-OR SOTFOC relay element operated (3-phases OR)

8000001B66 SOTFOC-OPT SOTFOC protection operated (3-phases OR)

8800001B62 SOTFOC-OPT-A SOTFOC protection operated (phase-A)

8900001B63 SOTFOC-OPT-B SOTFOC protection operated (phase-B)

8A00001B64 SOTFOC-OPT-C SOTFOC protection operated (phase-C)

8300001B23 SOTFOC-TRIP Trip signal by SOTFOC protection operation

8000001BB0 SOTFOC_BLOCK SOTFOC protection block command

8000001B65 SOTF_EN_COND SOTFOC protection operated permit

 Connection point on PLC logic


SOTF-OC(Function ID: 454001)
Element ID Name Description
800000EBB2 ADD.SOTF_EN Additional SOTFOC enable

800000EBB1 OC-RTP.EN OC-retrip enable

800000EBB0 SOTFOC_BLOCK SOTFOC protection block command

GRL200 (Soft 033 & 037)


- 214 -
6F2S1914 (0.37)

Overcurrent protection (OC)


The phase overcurrent (OC) protection is the major protection function and has both time
characteristic and directional elements. Four stages (elements) are available in the OC
protection. The user can select various features using the scheme switches provided. The
elements are named OC1, OC2, OC3, and OC4; and they operate independently.

To simplify the description, only OC1 is discussed but is applicable to the other OCs;
hence, read the expression for OC1 as OC2, OC3, and OC4 at each stage unless a special
explanation or instruction has been provided.

─────────────────────────────────────────────────────────────────
Note: The number of relay elements depends on the IED model. To know the number in
respective IED models, locate the IED ordering number; and check the order number at “G&T
position” referring to the comparison table below. For more information, see Appendix:
Ordering.
Table 2.15-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
No. of stages
33 37
Non-directional/directional definite time OC protection 4 ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 215 -
6F2S1914 (0.37)

2.15.1 Relay polarity


The user can choose either non-directional OC or directional OC for each OC stage. In addition,
the user can further select either the forward or the reverse direction for each of the directional
OC elements selected.

(i) Characteristic of non-directional OC


The characteristic of the non-directional type OC is a circle that has a center at the origin. A
setting and a scheme switch is used to configure each non-directional OC element; i.e., the user
can set the threshold value of the non-directional OC element for stage 1 using setting [OC1],
provided time characteristic is required for define time delay (DT) described in section
2.15.2(ii). Nondir should be set for the scheme switch [OC1-Dir].

(ii) Characteristic of directional-OC element in the forward direction


As shown in Figure 2.15-1, the characteristic of the directional-OC elements in the forward
direction is a semi-circle based upon the border-line; the hatched area shows the operating
region of a directional-OC element.
Non-operation (No trip) zone

Reference voltage or
θ1 Polarizing voltage2 (Vpol)

Operation (Trip) zone

Figure 2.15-1 Characteristic of the directional-OC element in the forward direction


1Note: Directional characteristic angle (θ) forms the angle between the reference
quantity and the directional characteristic angle line. The half plane represents
the zone of operation bordered on one side by the border line and extending in the
direction that contains both the reference (polarizing) and operating quantities.
2Note: For the polarizing voltage (Vpol), greater than 1.0 voltage should be applied for
sensing.

A reference signal, that is, a polarization signal is required by the directional OC element,
the reference signal is derived from a phase-to-phase voltage: for example, the directional OC

GRL200 (Soft 033 & 037)


- 216 -
6F2S1914 (0.37)

element for phase-A (OC-A) uses the phase-B-to-phase-C voltage rotated by 90° (VBC90°) in
the leading direction, this reference signal is illustrated in Figure 2.15-2. The direction of the
current in the protected circuit, in this case the phase-A current (IA), is determined from the
angle measured for IA against VBC90°. The purpose of using VBC in the 90° leading position
is so that the reference voltage (VBC90°) takes the same direction as the phase-A voltage (VA)
because the directional-sensing element requires a reference quantity that is reasonably
constant against which the current in the protected circuit can be compared. As a result, when
a fault occurs, the fault current IA will lag VBC90°. Similarly, for the phase-B directional OC
element (OC-B) where the object current is (IB) the reference voltage (VCA90°) is adopted. The
phase-C directional element (OC-C) uses the same approach as the OC-A and OC-B elements.
Table 2.15-2 shows the relationship between each current and its respective reference voltage.
VBC90°

Leading 90°
VA

VBC

VBC

Figure 2.15-2 Object current (IA) and reference voltage (VBC90°)

Table 2.15-2 Directional polarizing signal


Directional element Object current Reference voltage
OC-A IA VBC90
OC-B IB VCA90
OC-C IC VAB90

For a close-in three-phase fault, the three reference voltages VBC90°, VCA90° and
VAB90° may fall below the minimum threshold voltage for the directional OC element. In
order to cover this case, a voltage memory function is used to provide a polarizing signal. The
polarizing signals are provided during three-phase faults so that the OC element is able to
determine the direction of the fault. In addition, the directional element function determines
its output based on the loss of voltage memory and is effective while the fault current flows in
accordance with Figure 2.15-3.

GRL200 (Soft 033 & 037)


- 217 -
6F2S1914 (0.37)

Phase difference calculation


|V||I|cos() 0 &
1 Output of
directional element
Amplitude calculation F/F &
1 1
|l| OC pickup current

Amplitude calculation
|Vpol| Set voltage (OV-Vpol)

Figure 2.15-3 Direction determination after loss of voltage memory


If a single phase is connected to a heavy load, and the other phases are not connected to
heavy loads, the user can program separately the directional OC element such that OC will
send a trip signal only when the fault current detected is in the same direction among two
phases or more of the three-phases.

A setting and a scheme switch, as well as the non-directional OC element, provide the
settings for the directional OC element: for example, the user can set the threshold value of
the OC at stage 1 with the setting [OC1] and Forward can be set for the scheme switch [OC1-
Dir]. Setting of the sensing angle (θ) is configured by the setting [OC1-Angle] with the value of
θ set in the range of 0–180°. Figure 2.15-4 shows an example of an angle and a characteristic
set with θ.

Reverse

Vpol Vpol Vpol

θ=30°
θ=90°
Max. torque

Forward
Reverse Forward Reverse Forward

θ=0° θ=30° θ=90°

Forward Reverse

Reverse

Vpol Vpol

Forward
θ=170°
θ=100°

θ=100° θ=170°

Figure 2.15-4 Examples of directional characteristic angle (θ)

GRL200 (Soft 033 & 037)


- 218 -
6F2S1914 (0.37)

(iii) Characteristic of directional OC in the reverse direction


The reverse characteristic is a mirror image of the forward characteristic. The setting and the
scheme switch, as well as the setting of the directional OC element in the forward direction,
provides the setting of the directional OC element in the reverse direction: for example,
Reverse is set for the scheme switch [OC1-Dir] when the direction of the OC on stage 1 is
considered.

2.15.2 Inverse time and definite time delay characteristic


The OC element monitors the currents; when one of the currents is beyond the threshold of
operation, the OC element will operate within a period that is defined by the time
characteristic feature. The user can choose the OC operate time delay characteristics, either
dependent (inverse) time characteristic delay (i.e., IDMT) or independent (definite) time
characteristic delay (i.e., DT). The operate time of the IDMT depends upon the level of the
energizing current, and the operate time in the DT is a constant.

For the reset-time-delay in the IDMT, either inverse (dependent)-time-reset or definite


(independent)-time-reset is characterized by setting..

The user can select which characteristic will be applied to each stage of the OC element
by setting a scheme switch. We shall see the scheme switch later.

(i) Operation principle


Dependent time characteristic (inverse time delay)
The inverse time OC element has an inverse time feature for both operation and resetting; for
resetting, both definite time and dependent time resetting are available.

With inverse time operation, provided that the fault current has the magnitude required
to enable the determination of the location of the fault and provided that the fluctuation in the
impedance of the power source does not affect the correct determination, an inverse time OC
function provides an effective protection. With regard to the inverse time characteristic, for
example, the function can provide a fast trip for close-in faults, but will enable a delayed trip
for remote faults. The characteristic curve of the inverse time element can be selected from
among 10 characteristic curves† in conformance with IEC, IEEE, US, and UK standards.

†Note: A user-defined ‘Original’ curve can also be applied in addition to the 10


predefined characteristics provided.

With dependent time resetting selected, if during the resetting period the energizing
current exceeds the threshold current of the OC element, then the OC element will pick-up.

GRL200 (Soft 033 & 037)


- 219 -
6F2S1914 (0.37)

The OC element will reset later in a period determined by the characteristics of dependent
time resetting. In other words, the user can choose the behavior of the OC element for either
faults that are repetitive intermittent or faults that occur in rapid succession. The
characteristic for dependent time resetting is selectable from five dependent time
characteristics in conformance with IEEE and US standards.

When definite time resetting is selected with the operation of the inverse time OC
selection and the reset time set to zero (instantaneous), no intentional delay is added for the
resetting: that is, when the energizing current falls below the reset threshold of the OC element,
the OC element returns to its reset condition. If a value is set to the reset time in seconds, the
resetting of the OC element is delayed by the reset time.

Definite time delay (independent time characteristic)


In a system in which the fault current does not vary a great deal relative to the location of the
fault, definite time overcurrent protection is usually applied. Because the fault current does
not change greatly with respect to fault position the previous advantages described with regard
to the inverse time function are not applicable. Therefore, the definite time OC element is used
instead of the inverse time OC element. The definite time OC element has a fixed operating
time regardless of the magnitude of the fault current.

The operating time of the definite time OC element is set depending on the distance from
the power source and should be set shorter for relays furthest from the power source. Definite
time OC protection provides selectivity dependent on the difference between relay operating
times. It is limited to use in networks with a power source at one side only i.e. in radial
networks. The threshold values can be set identically at each terminal, but preferably, the
threshold value is reduced, little-by-little to provide a margin in terms of the current sensitivity
of the OC element. Moreover, a higher sensitivity of threshold current is required for a
protective relay that is located remote from the power source, that is, the threshold of the
definite time OC element is required to be lower than the ordinary threshold.

The operate time of the definite time OC element is constant irrespective of the
magnitude of the fault current and the threshold level of operation of the definite time OC
element with an on-delay timer provides a selective protection. As a result, the circuit breaker
(CB) at the remote terminal far from the power source can be tripped in the shortest time. The
on-delay timer, which generates a delay in starting the operation of the OC element, provides
a time grading margin (Tc); Tc is discussed later.

Definite time resetting as well as the on-delay starting setting of the definite time OC
element is provided. The operate time for the on-delay timer for starting and for the resetting

GRL200 (Soft 033 & 037)


- 220 -
6F2S1914 (0.37)

time is set using the OC element settings.

(ii) DT characteristic
The operate time in the DT characteristic will be a constant time and is not affected by the
level of current. The reset time is set to zero so that resetting is performed immediately. The
user can set the operate time using a setting; it is discussed in in sections (vi) and (vii).

(iii) IDMT characteristic


The operate time in the IDMT characteristic is inversely proportional to the level of the fault
current. The user can determine the operate time from a preset curve. Ten characteristic curves
are available; i.e. nine pre-installed curves covering IEC, IEEE, US and UK standard
characteristic curves and one original (user programmable) characteristic curve for which the
user can set the equation parameters. The IDMT curve equation and parameters will be
explained in section (iv).

The reset time in the IDMT is user-selectable; either inverse-time-reset or definite-time-


reset is selected. For the inverse-time-reset, the user can choose the reset time for the preset
characteristic from six characteristic curves; i.e. IEEE and US standard five pre-installed
characteristic curves and one user original characteristic curve where the user can set the
equation parameters. The inverse-time-reset curve equation and parameters will be discussed
in section (vi).

(iv) Operate time of IDMT


The operate time in the IDMT is defined by Equation (2.15-1). (ref. IEC 60255-151):

k
t(I) = TMS × {[ α ] + 𝑐} (2.15-1)
(𝐼⁄𝐼 ) − 1
𝑠

where:
t = operate time with constant current I (seconds),
I = operate (energizing) current (amperes),
Is = overcurrent setting (amperes),
TMS = time multiplier setting number,
k, α, c = constants defining curve.

The nine pre-programmed standard characteristic curves are defined in Table 2.15-3. In
addition, one original (user-programmable) curve can be applied. One curve can be chosen for
each OC stage. Figure 2.15-5 illustrates these characteristic curves. For example, the user
should set one for the scheme switch [OC1-Timer]. (“IEC-NI" is for IEC Normal Inverse

GRL200 (Soft 033 & 037)


- 221 -
6F2S1914 (0.37)

characteristic; “IEC-VI” for IEC Very inverse; “IEC-EI” for IEC Extremely Inverse; “UK-LTI” for
UK Long Time Inverse; “IEEE-MI” for IEEE Moderately Inverse; “IEEE-VI” for IEEE Very
Inverse; “IEEE-EI” for IEEE Extremely Inverse; “US-CO8” for US CO8 Inverse; “US-CO2” for
US CO2 Short Time Inverse, and “Original” for user-programmable characteristic.)

In the IDMT, the user can also program the characteristic using time-multiplier-setting
(TMS) for the required operate time. For example, when the IEC characteristic is selected, the
user can set the TMS value using the setting [OC1-TMS-IEC] (incidentally, the default value
for the TMS is 1.00). The other TMSs are also available by the [OC1-TMS-UK], [OC1-TMS-
IEEE], [OC1-TMS-US] and [OC1-TMS-ORG].
Table 2.15-3 Constants for IDMT
Curve type k c
Curve Description α
(IEC 60255-151) sec sec
A IEC Normal Inverse (IEC-NI) 0.14 0.02 0
B IEC Very Inverse (IEC-VI) 13.5 1 0
C IEC Extremely Inverse (IEC-EI) 80 2 0
- UK Long Time Inverse (UK-LTI) 120 1 0
D IEEE Moderately Inverse (IEEE-MI) 0.0515 0.02 0.114
E IEEE Very Inverse (IEEE-VI) 19.61 2 0.491
F IEEE Extremely Inverse (IEEE-EI) 28.2 2 0.1217
- US CO8 inverse (US-CO8) 5.95 2 0.18
- US CO2 short time inverse (US-CO2) 0.02394 0.02 0.01694

Figure 2.15-5 IDMT characteristic curves

GRL200 (Soft 033 & 037)


- 222 -
6F2S1914 (0.37)

(v) Operate time of DT


The operate time in the DT is a constant.
Time characteristic
The user should set DT for the scheme switches [OC1-Timer]. The value of the required operate
time is set for the setting [TOC1] in the range 0.00–300.00s.

Instantaneous activation
The operate time of the instantaneous characteristic is achieved by setting zero for the [TOC1],
but the instantaneous one can also obtained when the logic signal ‘1(High)’ is programmed to
be injected at PLC connection point “OC1_INST_OP”.

(vi) Reset time of IDMT


Programming the reset time characteristic is available in the IEEE, US standards. It is also
allowed in original (user-programmable) inverse-time-reset characteristic. To get this
characteristic, the user should set DEP for setting [OC1-Rtimer]†. The following equation
defines the reset time for the inverse-time-reset characteristic. (ref. IEC 60255-151):

kr
t(I) = RTMS × [ β
] (2.15-2)
1 − (𝐼⁄𝐼 )
𝑠

where,
t = time required for the element to reset fully after complete operation (seconds),
I = energizing current (amperes),
Is = threshold setting (amperes),
RTMS = time multiplier setting for resetting,
kr = time required to reset fully after complete operation when the energizing current is
zero (seconds),
β = constants defining curve.

For the IEEE standard, the user should use the setting [OC1-RTMS-IEEE] (incidentally,
the default value is 1.000). For the US standard and the original, settings [OC1-RTMS-US] and
[OC1-RTMS-ORG] are provided, respectively (For more information w.r.t the value for kr and
β, see Table 2.15-4; Figure 2.15-6 shows the characteristic curves).

†Note: To select the inverse-time-reset characteristic, set [OC1-Rtimer]=DEP.


Conversely set [OC1-Rtimer]=DEF to select definite-time-reset characteristic,.
Note: For the setting [OC1-Rtimer]=DEP (inverse-time-reset), the integrated value will
be reduced in accordance to the magnitude of an energized current, when the

GRL200 (Soft 033 & 037)


- 223 -
6F2S1914 (0.37)

energized current is smaller than the setting [OC1]. The reducing degree will be
determined with the reset curve characteristics defined in the standards.
Note: For the setting [OC1-Rtimer]=DEF (definite-time-reset), the integrated value shall
be zero when an energized current is smaller than the setting [OC1], when the
small energized current is continued for timer setting [TOC1R]. The integrated
value will not be zero when the energized current does not flow small for the
setting [TOC1R]. DEF is allowed to set in the IEEE, US, and ORG. DEF is set
unconditionally in the IEC and UK (see Table 2.15-5).

Table 2.15-4 Constants for inverse-time-reset characteristics


Curve Type kr
Curve Description Β
IEC 60255-151 sec
A IEC Normal Inverse (IEC-NI) N/A N/A
B IEC Very Inverse (IEC-VI) N/A N/A
C IEC Extremely Inverse (IEC-EI) N/A N/A
- UK Long Time Inverse (UK-LTI) N/A N/A
D IEEE Moderately Inverse (IEEE-MI) 4.85 2
E IEEE Very Inverse (IEEE-VI) 21.6 2
F IEEE Extremely Inverse (IEEE-EI) 29.1 2
- US CO8 inverse (US-CO8) 5.95 2
- US CO2 short time inverse (US-CO2) 2.261 2

Figure 2.15-6 Inverse-time-reset characteristics curves

Figure 2.15-7 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[OC1], will make an integrating value, which can determine how the element operates. If the

GRL200 (Soft 033 & 037)


- 224 -
6F2S1914 (0.37)

energized quantity (I) falls below the threshold setting [OC1], the element operation will
return to its reset stage after the time t(I) calculated in Equation (2.15-2).
Time 

Energizing current
Energizing current
cleared by tripping

Pickup threshold in relay [OC1] threshold

Measuring quantity 0A

Inverse-time-reset characteristic

Stage to element
return

Setting
[*-Rtimer]=DEP
Integrator

Trip signal

The integration will be deceased depending on the


[OC1-RTMS-*] reset characteristics.

Definite-time-reset characteristic
Stage to element
return

Setting
[*-Rtimer]=DEF

Integrator

Trip signal

Reset time
Integration will be kept in timer [TOC1R].
The integration will start again when the energizing current The integration will be reset when the energizing current
becomes larger than [OC1] within [TOC1R]. does not become larger than [OC1] in [TOC1R].

Figure 2.15-7 Inverse-time-reset characteristics

(vii) Reset time of DT


In the DT characteristic, the reset time is designed to be instant.

GRL200 (Soft 033 & 037)


- 225 -
6F2S1914 (0.37)

(viii) Summary of OC operation


Table 2.15-5 shows the summary of OC operation. Note that DEF will be set unconditionally in
IEC-NI, VI, EI and UK-LTI characteristics (†).
Table 2.15-5 Type and standard board in the OC1 (A tick shows a selectable function)
IDMT
Characteristics DT
IEC-NI IEC-VI IEC-EI UK-LTI IEEE-MI IEEE-VI IEEE-EI US-CO2 US-CO8 Original

DT 

Scheme switch [OC1-Timer]

IEC-NI
IEC-VI ✓
IEC-EI ✓
UK LTI ✓
IEEE-MI ✓
IEEE-VI ✓
IEEE-EI ✓
US-CO2 ✓
US-CO8 ✓
Original ✓
DEF N.A ✓† ✓† ✓† ✓† ✓ ✓ ✓ ✓ ✓ ✓

Scheme switch

N.A
[OC1-Rtimer]

N.A ✓
N.A ✓
DEP
N.A ✓
N.A ✓
N.A ✓

2.15.3 Threshold value for operation


The value of threshold current at which the OC element will pick-up is configured by a setting;
the setting [OC1] is provided for both the IDMT and DT characteristics. Note that the settings
of the threshold levels have distinct values in the respective OC elements. A rating current for
the input is defined either 1A or 5A; the input rating is defined on a VCT. (For more information
about the VCT, see Chapter Technical description: Transformer module for AC analogue input).
(2.34.3a)

2.15.4 Reset Ratio


The ratio of the threshold current for pick-up to reset is applied using a setting; for example,
the ratio for the OC1 element is set using the setting [OC1-DPR]. The reset ratios for the other
OC elements are also provided.

2.15.5 Miscellaneous functions


(i) Trip mode
Every OC element has a selectable tripping mode; the mode is selected using a scheme switch.
For the OC1 element, for example, a scheme switch [OC1-OPMD] is provided. When a trip is
required for any faults that are detected, 3POR (a fault occurs in one or more phases) is set for

GRL200 (Soft 033 & 037)


- 226 -
6F2S1914 (0.37)

the scheme switch [OC1-OPMD]. Conversely, when a trip is only required for faults that occur
in two or more phases, 2OUTOF3 (a fault occurs in two or more phases) is set for the scheme
switch [OC1-OPMD].
Table 2.15-6 Fault type and tripping mode
Fault type Setting [OC1-OPMD]
Phase-A Phase-B Phase-C 3POR 2OUTOF3
X – – ✓ No trip
– X – ✓ No trip
– – X ✓ No trip
X X – ✓ ✓
– X X ✓ ✓
X – X ✓ ✓
X X X ✓ ✓
Note: A tick (✓) indicates that a trip is issued when faults are detected.
A mark (X) indicates the occurrence of a fault on a particular phase. A mark
shown thus (–) indicates that no fault has occurred on that particular phase.

(ii) Blocking OC by ICD


The operation of each OC element can be blocked if the ICD function detects a second
harmonic current caused by the magnetizing inrush current phenomenon when a
transformer is energized. For example, for the OC1 element, the scheme switch [OC1-
2fBlk] is provided, and Block-3P should be set when the user wishes to block all three-
phases of the OC1 element when the second harmonic associated with the magnetizing
inrush current is present. Alternatively, Block-PerP is set if blocking is just required for a
single phase concerting to the phenomenon. Non is set for the scheme switch [OC1-2fBlk]
as the default setting. For more information about the ICD function, see Chapter Relay
application: Inrush current detection function.

(iii) Blocking OC by VTF


The operation of the OC element can be blocked by the voltage transformer failure (VTF)
function via a scheme switch. For example, Block can be set for the scheme switch [OC1-
VTFBlk] to block the operation of the OC1 element during a VTF condition. Non is set for
the scheme switch [OC1-VTFBlk] as a default. For more information about the VTF, see
Chapter Relay application: VT failure detection.

(iv) OC operation for auto-reclose


The OC element activates the auto-reclose (ARC) function. However, if for example ARC
is not required, Block is set for the scheme switch [OC1-ARCBlk]. Block is set for the
scheme switch [OC1-ARCBlk] as a default.

GRL200 (Soft 033 & 037)


- 227 -
6F2S1914 (0.37)

(v) Signal of OC trip


When a user requires an alarm signal in place of the trip signal; for example, set Alarm
for the scheme switch [OC1-UseFor]. Trip is set for the scheme switch [OC1-UseFor] for
the normal trip operation.

2.15.6 Scheme logic


The scheme logic for both the non-directional and the directional OC1 element is illustrated in
Figure 2.15-8; Figure 2.15-9 shows grouping commands for the trip circuit (TRC). Each phase
of the OC1 element issues a pick-up when a current has been exceeded over the setting; then
the pick-up signal is transferred to into the TRC as trip signals. (For more information, see
Chapter Relay application: Trip circuit function)
8100011B60
≥1
OC1-OR†
8100011B61
≥1
OC1PU-OR†

For DT characteristic 8000011C20

A TOC1 To Grouping logic


& & & t 0
8100011C21 ≥1
OC1 &
B & & OC1-OPT-AR
& t 0
8200011C22 ≥1
&
C & & & t 0
OC1-OPT-BR
≥1
&
For IDMT characteristic 8000011C24 0.00–300.00s OC1-OPT-CR
≥1
A & & ≥1 & & ≥1
&
8100011C25
OC1 PU B ≥1 &
& & & &
8200011C26
C & & ≥1 & & 8000011B68
& ≥1
& OC1-OPT
OC1-Timer DT &
From ICD IEC-NI
ICD-A &
& ≥1 OC1-OPT-TRIP
IEC-VI
3POR
ICD-B IEC-EI &
& ≥1 OC1-OPMD 2OUTOF3 OC1-OPT-ALARM
UK-LTI Trip
ICD-C & ≥1 &
OC1-UseFor OC1-ARC-BLOCK
IEEE-MI Alarm

≥1
IEEE-VI OC1-ARCBlk Block
&
IEEE-EI

US-C02
Block-3P US-C08
OC1-2PBlk
Block-PerP
ORIGINAL
OC1-EN On

From VTF
VTF_DETECT
OC1-VTFBlk Block &
≥1
8000011BB0
800001EBB0 OC1_BLOCK
8000011BB1
800001EBB4 OC1_INST_OP

Figure 2.15-8 Scheme logic for the OC1


†Note:The presence of ‘OC1-OR’ and ‘OC1PU-OR’ signals depends on the operation
characteristic defined with setting [OC1_Timer], as shown in Table 2.15-7.

Table 2.15-7 Signal behaviors of PLC monitoring points ‘OC1-OR’ and ‘OC1PU-OR’
Setting [OC1_Timer]
PLC monitoring points
DT IEC-NT,VI,EI, UK-LTI, IEET-MI,VI,EI, US-CO2,CO8, ORIGINAL
OC1-OR ○
1 ○
3
OC1PU-OR ○
2 ○
4
1 :
○ A pick-up signal is generated instantly when the element operates.

GRL200 (Soft 033 & 037)


- 228 -
6F2S1914 (0.37)

2 :
○ No signal due that the PU element is killed. Use ‘OC1-OR’ in place of this.
3 :
○ A pick-up signal is generated, but delayed with the IDMT characteristic.
4 :
○ A pick-up signal is generated instantly.

From OC1 to OC4 logics To TRC


OC1-OPT-TRIP ≥1 OC-OPT-TRIP
OC2-OPT-TRIP
OC3-OPT-TRIP
OC4-OPT-TRIP

OC1-OPT-ALARM ≥1 OC-OPT-ALARM
OC2-OPT- ALARM
OC3-OPT- ALARM
OC4-OPT- ALARM

OC1-ARC-BLOCK ≥1 OC-ARC-BLOCK
OC2- ARC-BLOCK
OC3- ARC-BLOCK
OC4- ARC-BLOCK

OC1-OPT-AR ≥1 OC-OPT-AR

OC1-OPT-BR OC-OPT-BR

OC1-OPT-CR OC-OPT-CR

OC2-OPT-AR
≥1
OC2-OPT-BR

OC2-OPT-CR

OC3-OPT-AR
≥1

OC3-OPT-BR

OC3-OPT-CR

OC4-OPT-AR

OC4-OPT-BR

OC4-OPT-CR
To Recording

OC1-OPT OC1-OPT
OC2-OPT OC2-OPT
OC3-OPT OC3-OPT
OC4-OPT OC4-OPT

Figure 2.15-9 Grouping logic for TRC/Recording functions

GRL200 (Soft 033 & 037)


- 229 -
6F2S1914 (0.37)

2.15.7 Setting
OC (Function ID: 440001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OC1-EN Off / On - OC1 protection scheme switch Off
OC2-EN Off / On - OC2 protection scheme switch Off
OC3-EN Off / On - OC3 protection scheme switch Off
OC4-EN Off / On - OC4 protection scheme switch Off
OC1 NonDir / Forward /
OC1-Dir - OC1 directional characteristic NonDir
Reverse
OC1-Angle 0 - 180 deg OC1 directional characteristic angle 45
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OC1-Timer IEEE-MI / IEEE-VI / - OC1 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OC1 A OC1 threshold (in DT mode) 1.00 5.00
50.00 250.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
TOC1 0.00 - 300.00 s OC1 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-IEC 0.010 - 50.000 - OC1 time multiplier of IEC inverse curve 1.000
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
UK 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-UK 0.010 - 50.000 - OC1 time multiplier of UK inverse curve 1.000
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-
0.010 - 50.000 - OC1 time multiplier of IEEE inverse curve 1.000
IEEE
OC1-Rtimer DEF / DEP - OC1 reset delay type of IEEE DEF
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
OC1-RTMS- OC1 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-US 0.010 - 50.000 - OC1 time multiplier of US inverse curve 1.000
OC1-Rtimer DEF / DEP - OC1 reset delay type of US DEF
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
OC1 dependent reset time multiplier of US
OC1-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-ORG 0.010 - 50.000 - OC1 time multiplier of ORG inverse curve 1.000
OC1-Rtimer DEF / DEP - OC1 reset delay type of US DEF
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
OC1-RTMS- OC1 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OC1-k 0.00000 - 500.00000 - OC1 user original curve coefficient 0.00000

GRL200 (Soft 033 & 037)


- 230 -
6F2S1914 (0.37)

OC (Function ID: 440001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OC1-a 0.00000 - 10.00000 - OC1 user original curve coefficient 0.00000
OC1-c 0.00000 - 10.00000 - OC1 user original curve coefficient 0.00000
OC1-kr 0.00000 - 500.00000 - OC1 user original curve coefficient 0.00000
OC1-b 0.00000 - 10.00000 - OC1 user original curve coefficient 0.00000
Output Non / Block-3P /
OC1-2fBlk - OC1 operation block by 2f-detection Non
Block-PerP
OC1-VTFBlk Non / Block - OC1 operation block by VTF Non
OC1-OPMD 3POR / 2OUTOF3 - OC1 operation mode 3POR
OC1-UseFor Trip / Alarm - OC1 used for trip or alarm Trip
OC1-ARCBlk Non / Block - Autoreclose block by OC1 Block
OC2 NonDir / Forward /
OC2-Dir - OC2 directional characteristic NonDir
Reverse
OC2-Angle 0 - 180 deg OC2 directional characteristic angle 45
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OC2-Timer IEEE-MI / IEEE-VI / - OC2 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OC2 A OC2 threshold (in DT mode) 1.00 5.00
50.00 250.00
OC2-DPR 10 - 100 % OC2 drop-out/pick-up ratio 100
TOC2 0.00 - 300.00 s OC2 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
OC2 A OC2 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC2-DPR 10 - 100 % OC2 drop-out/pick-up ratio 100
OC2-TMS-IEC 0.010 - 50.000 - OC2 time multiplier of IEC inverse curve 1.000
TOC2R 0.00 - 300.00 s OC2 definite time reset delay 0.00
UK 0.02 - 0.10 -
OC2 A OC2 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC2-DPR 10 - 100 % OC2 drop-out/pick-up ratio 100
OC2-TMS-UK 0.010 - 50.000 - OC2 time multiplier of UK inverse curve 1.000
TOC2R 0.00 - 300.00 s OC2 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OC2 A OC2 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC2-DPR 10 - 100 % OC2 drop-out/pick-up ratio 100
OC2-TMS-
0.010 - 50.000 - OC2 time multiplier of IEEE inverse curve 1.000
IEEE
OC2-Rtimer DEF / DEP - OC2 reset delay type of IEEE DEF
TOC2R 0.00 - 300.00 s OC2 definite time reset delay 0.00
OC2-RTMS- OC2 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
OC2 A OC2 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC2-DPR 10 - 100 % OC2 drop-out/pick-up ratio 100
OC2-TMS-US 0.010 - 50.000 - OC2 time multiplier of US inverse curve 1.000
OC2-Rtimer DEF / DEP - OC2 reset delay type of US DEF
TOC2R 0.00 - 300.00 s OC2 definite time reset delay 0.00
OC2 dependent reset time multiplier of US
OC2-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
OC2 A OC2 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC2-DPR 10 - 100 % OC2 drop-out/pick-up ratio 100
OC2-TMS-ORG 0.010 - 50.000 - OC2 time multiplier of ORG inverse curve 1.000
OC2-Rtimer DEF / DEP - OC2 reset delay type of US DEF

GRL200 (Soft 033 & 037)


- 231 -
6F2S1914 (0.37)

OC (Function ID: 440001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
TOC2R 0.00 - 300.00 s OC2 definite time reset delay 0.00
OC2-RTMS- OC2 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OC2-k 0.00000 - 500.00000 - OC2 user original curve coefficient 0.00000
OC2-a 0.00000 - 10.00000 - OC2 user original curve coefficient 0.00000
OC2-c 0.00000 - 10.00000 - OC2 user original curve coefficient 0.00000
OC2-kr 0.00000 - 500.00000 - OC2 user original curve coefficient 0.00000
OC2-b 0.00000 - 10.00000 - OC2 user original curve coefficient 0.00000
Output Non / Block-3P /
OC2-2fBlk - OC2 operation block by 2f-detection Non
Block-PerP
OC2-VTFBlk Non / Block - OC2 operation block by VTF Non
OC2-OPMD 3POR / 2OUTOF3 - OC2 operation mode 3POR
OC2-UseFor Trip / Alarm - OC2 used for trip or alarm Trip
OC2-ARCBlk Non / Block - Autoreclose block by OC2 Block
OC3 NonDir / Forward /
OC3-Dir - OC3 directional characteristic NonDir
Reverse
OC3-Angle 0 - 180 deg OC3 directional characteristic angle 45
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OC3-Timer IEEE-MI / IEEE-VI / - OC3 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OC3 A OC3 threshold (in DT mode) 1.00 5.00
50.00 250.00
OC3-DPR 10 - 100 % OC3 drop-out/pick-up ratio 100
TOC3 0.00 - 300.00 s OC3 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
OC3 A OC3 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC3-DPR 10 - 100 % OC3 drop-out/pick-up ratio 100
OC3-TMS-IEC 0.010 - 50.000 - OC3 time multiplier of IEC inverse curve 1.000
TOC3R 0.00 - 300.00 s OC3 definite time reset delay 0.00
UK 0.02 - 0.10 -
OC3 A OC3 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC3-DPR 10 - 100 % OC3 drop-out/pick-up ratio 100
OC3-TMS-UK 0.010 - 50.000 - OC3 time multiplier of UK inverse curve 1.000
TOC3R 0.00 - 300.00 s OC3 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OC3 A OC3 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC3-DPR 10 - 100 % OC3 drop-out/pick-up ratio 100
OC3-TMS-
0.010 - 50.000 - OC3 time multiplier of IEEE inverse curve 1.000
IEEE
OC3-Rtimer DEF / DEP - OC3 reset delay type of IEEE DEF
TOC3R 0.00 - 300.00 s OC3 definite time reset delay 0.00
OC3-RTMS- OC3 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
OC3 A OC3 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC3-DPR 10 - 100 % OC3 drop-out/pick-up ratio 100
OC3-TMS-US 0.010 - 50.000 - OC3 time multiplier of US inverse curve 1.000
OC3-Rtimer DEF / DEP - OC3 reset delay type of US DEF
TOC3R 0.00 - 300.00 s OC3 definite time reset delay 0.00
OC3 dependent reset time multiplier of US
OC3-RTMS-US 0.010 - 50.000 - 1.000
inverse curve

GRL200 (Soft 033 & 037)


- 232 -
6F2S1914 (0.37)

OC (Function ID: 440001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ORG 0.02 - 0.10 -
OC3 A OC3 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC3-DPR 10 - 100 % OC3 drop-out/pick-up ratio 100
OC3-TMS-ORG 0.010 - 50.000 - OC3 time multiplier of ORG inverse curve 1.000
OC3-Rtimer DEF / DEP - OC3 reset delay type of US DEF
TOC3R 0.00 - 300.00 s OC3 definite time reset delay 0.00
OC3-RTMS- OC3 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OC3-k 0.00000 - 500.00000 - OC3 user original curve coefficient 0.00000
OC3-a 0.00000 - 10.00000 - OC3 user original curve coefficient 0.00000
OC3-c 0.00000 - 10.00000 - OC3 user original curve coefficient 0.00000
OC3-kr 0.00000 - 500.00000 - OC3 user original curve coefficient 0.00000
OC3-b 0.00000 - 10.00000 - OC3 user original curve coefficient 0.00000
Output Non / Block-3P /
OC3-2fBlk - OC3 operation block by 2f-detection Non
Block-PerP
OC3-VTFBlk Non / Block - OC3 operation block by VTF Non
OC3-OPMD 3POR / 2OUTOF3 - OC3 operation mode 3POR
OC3-UseFor Trip / Alarm - OC3 used for trip or alarm Trip
OC3-ARCBlk Non / Block - Autoreclose block by OC3 Block
OC4 NonDir / Forward /
OC4-Dir - OC4 directional characteristic NonDir
Reverse
OC4-Angle 0 - 180 deg OC4 directional characteristic angle 45
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OC4-Timer IEEE-MI / IEEE-VI / - OC4 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OC4 A OC4 threshold (in DT mode) 1.00 5.00
50.00 250.00
OC4-DPR 10 - 100 % OC4 drop-out/pick-up ratio 100
TOC4 0.00 - 300.00 s OC4 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
OC4 A OC4 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC4-DPR 10 - 100 % OC4 drop-out/pick-up ratio 100
OC4-TMS-IEC 0.010 - 50.000 - OC4 time multiplier of IEC inverse curve 1.000
TOC4R 0.00 - 300.00 s OC4 definite time reset delay 0.00
UK 0.02 - 0.10 -
OC4 A OC4 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC4-DPR 10 - 100 % OC4 drop-out/pick-up ratio 100
OC4-TMS-UK 0.010 - 50.000 - OC4 time multiplier of UK inverse curve 1.000
TOC4R 0.00 - 300.00 s OC4 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OC4 A OC4 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC4-DPR 10 - 100 % OC4 drop-out/pick-up ratio 100
OC4-TMS-
0.010 - 50.000 - OC4 time multiplier of IEEE inverse curve 1.000
IEEE
OC4-Rtimer DEF / DEP - OC4 reset delay type of IEEE DEF
TOC4R 0.00 - 300.00 s OC4 definite time reset delay 0.00
OC4-RTMS- OC4 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
OC4 A OC4 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC4-DPR 10 - 100 % OC4 drop-out/pick-up ratio 100
OC4-TMS-US 0.010 - 50.000 - OC4 time multiplier of US inverse curve 1.000

GRL200 (Soft 033 & 037)


- 233 -
6F2S1914 (0.37)

OC (Function ID: 440001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OC4-Rtimer DEF / DEP - OC4 reset delay type of US DEF
TOC4R 0.00 - 300.00 s OC4 definite time reset delay 0.00
OC4 dependent reset time multiplier of US
OC4-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
OC4 A OC4 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC4-DPR 10 - 100 % OC4 drop-out/pick-up ratio 100
OC4-TMS-ORG 0.010 - 50.000 - OC4 time multiplier of ORG inverse curve 1.000
OC4-Rtimer DEF / DEP - OC4 reset delay type of US DEF
TOC4R 0.00 - 300.00 s OC4 definite time reset delay 0.00
OC4-RTMS- OC4 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OC4-k 0.00000 - 500.00000 - OC4 user original curve coefficient 0.00000
OC4-a 0.00000 - 10.00000 - OC4 user original curve coefficient 0.00000
OC4-c 0.00000 - 10.00000 - OC4 user original curve coefficient 0.00000
OC4-kr 0.00000 - 500.00000 - OC4 user original curve coefficient 0.00000
OC4-b 0.00000 - 10.00000 - OC4 user original curve coefficient 0.00000
Output Non / Block-3P /
OC4-2fBlk - OC4 operation block by 2f-detection Non
Block-PerP
OC4-VTFBlk Non / Block - OC4 operation block by VTF Non
OC4-OPMD 3POR / 2OUTOF3 - OC4 operation mode 3POR
OC4-UseFor Trip / Alarm - OC4 used for trip or alarm Trip
OC4-ARCBlk Non / Block - Autoreclose block by OC4 Block

GRL200 (Soft 033 & 037)


- 234 -
6F2S1914 (0.37)

2.15.8 Data ID
 Signal monitoring points
OC(Function ID: 440001)
Element ID Name Description
8500001B62 OC-ARC-BLOCK Autoreclose block signal by OC protection operation

8400001B61 OC-OPT-ALARM Alarm signal by OC protection operation

8800001B63 OC-OPT-AR OC protection operated (phase-A)

8900001B64 OC-OPT-BR OC protection operated (phase-B)

8A00001B65 OC-OPT-CR OC protection operated (phase-C)

8300001B23 OC-OPT-TRIP Trip signal by OC protection operation

8000011C20 OC1-A OC1 relay element operated (phase-A)

8200011B6A OC1-ARC-BLOCK Autoreclose block signal by OC1 protection operation

8100011C21 OC1-B OC1 relay element operated (phase-B)

8200011C22 OC1-C OC1 relay element operated (phase-C)

8000011B68 OC1-OPT OC1 protection operated

8000011B62 OC1-OPT-A OC1 protection operated (phase-A)

8100011B69 OC1-OPT-ALARM Alarm signal by OC1 protection operation

8000011B65 OC1-OPT-AR OC1 protection operated (phase-A)

8100011B63 OC1-OPT-B OC1 protection operated (phase-B)

8100011B66 OC1-OPT-BR OC1 protection operated (phase-B)

8200011B64 OC1-OPT-C OC1 protection operated (phase-C)

8200011B67 OC1-OPT-CR OC1 protection operated (phase-C)

8000011B23 OC1-OPT-TRIP Trip signal by OC1 protection operation

8000011B60 OC1-OR OC1 relay element operated (3-phases OR)

8000011C24 OC1PU-A OC1 relay operation level pick up (phase-A)

8100011C25 OC1PU-B OC1 relay operation level pick up (phase-B)

8200011C26 OC1PU-C OC1 relay operation level pick up (phase-C)

8000011B61 OC1PU-OR OC1 relay operation level pick up (3-phases OR)

8000011BB0 OC1_BLOCK OC1 protection block command

8000011BB1 OC1_INST_OP OC1 protection instant operation command

8400021C20 OC2-A OC2 relay element operated (phase-A)

8200021B6A OC2-ARC-BLOCK Autoreclose block signal by OC2 protection operation

8500021C21 OC2-B OC2 relay element operated (phase-B)

8600021C22 OC2-C OC2 relay element operated (phase-C)

8100021B68 OC2-OPT OC2 protection operated

8400021B62 OC2-OPT-A OC2 protection operated (phase-A)

8100021B69 OC2-OPT-ALARM Alarm signal by OC2 protection operation

8400021B65 OC2-OPT-AR OC2 protection operated (phase-A)

8500021B63 OC2-OPT-B OC2 protection operated (phase-B)

8500021B66 OC2-OPT-BR OC2 protection operated (phase-B)

8600021B64 OC2-OPT-C OC2 protection operated (phase-C)

8600021B67 OC2-OPT-CR OC2 protection operated (phase-C)

8000021B23 OC2-OPT-TRIP Trip signal by OC2 protection operation

8100021B60 OC2-OR OC2 relay element operated (3-phases OR)

8400021C24 OC2PU-A OC2 relay operation level pick up (phase-A)

8500021C25 OC2PU-B OC2 relay operation level pick up (phase-B)

8600021C26 OC2PU-C OC2 relay operation level pick up (phase-C)

GRL200 (Soft 033 & 037)


- 235 -
6F2S1914 (0.37)

 Signal monitoring points


OC(Function ID: 440001)
Element ID Name Description
8100021B61 OC2PU-OR OC2 relay operation level pick up (3-phases OR)

8100021BB0 OC2_BLOCK OC2 protection block command

8100021BB1 OC2_INST_OP OC2 protection instant operation command

8800031C20 OC3-A OC3 relay element operated (phase-A)

8200031B6A OC3-ARC-BLOCK Autoreclose block signal by OC3 protection operation

8900031C21 OC3-B OC3 relay element operated (phase-B)

8A00031C22 OC3-C OC3 relay element operated (phase-C)

8200031B68 OC3-OPT OC3 protection operated

8800031B62 OC3-OPT-A OC3 protection operated (phase-A)

8100031B69 OC3-OPT-ALARM Alarm signal by OC3 protection operation

8800031B65 OC3-OPT-AR OC3 protection operated (phase-A)

8900031B63 OC3-OPT-B OC3 protection operated (phase-B)

8900031B66 OC3-OPT-BR OC3 protection operated (phase-B)

8A00031B64 OC3-OPT-C OC3 protection operated (phase-C)

8A00031B67 OC3-OPT-CR OC3 protection operated (phase-C)

8000031B23 OC3-OPT-TRIP Trip signal by OC3 protection operation

8200031B60 OC3-OR OC3 relay element operated (3-phases OR)

8800031C24 OC3PU-A OC3 relay operation level pick up (phase-A)

8900031C25 OC3PU-B OC3 relay operation level pick up (phase-B)

8A00031C26 OC3PU-C OC3 relay operation level pick up (phase-C)

8200031B61 OC3PU-OR OC3 relay operation level pick up (3-phases OR)

8200031BB0 OC3_BLOCK OC3 protection block command

8200031BB1 OC3_INST_OP OC3 protection instant operation command

8C00041C20 OC4-A OC4 relay element operated (phase-A)

8200041B6A OC4-ARC-BLOCK Autoreclose block signal by OC4 protection operation

8D00041C21 OC4-B OC4 relay element operated (phase-B)

8E00041C22 OC4-C OC4 relay element operated (phase-C)

8300041B68 OC4-OPT OC4 protection operated

8C00041B62 OC4-OPT-A OC4 protection operated (phase-A)

8100041B69 OC4-OPT-ALARM Alarm signal by OC4 protection operation

8C00041B65 OC4-OPT-AR OC4 protection operated (phase-A)

8D00041B63 OC4-OPT-B OC4 protection operated (phase-B)

8D00041B66 OC4-OPT-BR OC4 protection operated (phase-B)

8E00041B64 OC4-OPT-C OC4 protection operated (phase-C)

8E00041B67 OC4-OPT-CR OC4 protection operated (phase-C)

8000041B23 OC4-OPT-TRIP Trip signal by OC4 protection operation

8300041B60 OC4-OR OC4 relay element operated (3-phases OR)

8C00041C24 OC4PU-A OC4 relay operation level pick up (phase-A)

8D00041C25 OC4PU-B OC4 relay operation level pick up (phase-B)

8E00041C26 OC4PU-C OC4 relay operation level pick up (phase-C)

8300041B61 OC4PU-OR OC4 relay operation level pick up (3-phases OR)

8300041BB0 OC4_BLOCK OC4 protection block command

8300041BB1 OC4_INST_OP OC4 protection instant operation command

8000001C71 OC_FL_ST1 Recording start signal (forward)

GRL200 (Soft 033 & 037)


- 236 -
6F2S1914 (0.37)

 Signal monitoring points


OC(Function ID: 440001)
Element ID Name Description
8100001C72 OC_FL_ST2 Recording start signal (reverse)

8200001C73 OC_FL_ST3 Fault location start signal (forward)

8300001C74 OC_FL_ST4 Fault location start signal (reverse)

 Connection point in PLC logic


OC(Function ID: 440001)
Element ID Name Description
800001EBB0 OC1_BLOCK OC1 protection block command

800001EBB4 OC1_INST_OP OC1 protection instant operation command

810002EBB1 OC2_BLOCK OC2 protection block command

810002EBB5 OC2_INST_OP OC2 protection instant operation command

820003EBB2 OC3_BLOCK OC3 protection block command

820003EBB6 OC3_INST_OP OC3 protection instant operation command

830004EBB3 OC4_BLOCK OC4 protection block command

830004EBB7 OC4_INST_OP OC4 protection instant operation command

GRL200 (Soft 033 & 037)


- 237 -
6F2S1914 (0.37)

Earth fault protection (EF)


The earth fault protection (EF) function has four stages (elements); each element can have
either a directional characteristic or non-directional characteristic.

To simplify the description, only EF1 is discussed but is applicable to the other EFs; hence,
read the expression for EF1 as EF2, EF3 and EF4 at each EF stage unless a special explanation
or instruction has been provided.

─────────────────────────────────────────────────────────────────
Note: The number of relay elements depends on the IED model. To know the number in
respective IED models, locate the IED ordering number; and check the order number at “G&T
position” referring to the comparison table below. For more information, see Appendix:
Ordering.
Table 2.16-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
No. of stages
33 37
Non-directional/directional definite time EF protection 4 ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 238 -
6F2S1914 (0.37)

2.16.1 Relay polarity


The user can choose either non-directional EF or directional EF for each EF stage. In addition,
the user can further select between the forward or the direction for each of the directional EF
elements selected.

(i) Characteristic of non-directional EF


The characteristic of the non-directional type EF function is a circle at the origin. A setting and
a scheme switch is used to configure each non-directional EF element; i.e., the user can set the
threshold value of the non-directional EF element for stage1 using setting [EF1-DT], provided
time characteristic is required for define time delay (DT) described in section 2.16.2(i). The
user should set NonDir for the scheme switch [EF1-Dir].

(ii) Characteristic of directional-EF in the forward direction


As shown in Figure 2.16-1, the characteristic of the directional-EF elements in the forward
direction is a semi-circle based upon the border line; the hatched area shows the operating
region of the directional-EF element.

Non-operation (No trip) zone

Reference voltage or
θ Polarizing voltage (−3Vo)
φ

Operation (Trip) zone

Figure 2.16-1 Characteristic of the directional-EF element in the forward direction


Note: Directional characteristic angle (θ) forms the angle between the reference quantity
and the directional characteristic angle line. The half plane represents the zone of
operation bordered on one side by the border line and extending in the direction
that contains both the reference (polarizing) and operating quantities.

A setting and a scheme switch, as well as the non-directional EF element, provide the
settings for the directional EF element: for example, the user can set the threshold value (IEF)
for stage 1 with the setting [EF1-DT] and Forward can be set for the scheme switch [EF1-Dir].

GRL200 (Soft 033 & 037)


- 239 -
6F2S1914 (0.37)

Setting of the sensing angle (θ) is configured by the setting [EF1-Angle] with the value of θ set
in the range of 0–180°. Figure 2.16-2 shows an example of an angle and a characteristic using
the θ. The operation of the EF element is based upon the following equation.
3𝐼0 ≥ 𝐼𝐸𝐹 (2.16-1)
3𝐼0 × cos(φ − θ) ≥ 0 (2.16-2)
3𝑉0 ≥ 𝐸𝐹_𝑉𝑝𝑜𝑙 (2.16-3)
where
3Io = residual current
3Vo = residual voltage
−3Vo = reference voltage (or polarizing voltage)
φ= lagging angle
θ = EF setting angle
IEF = Setting value of the EF element ([EF1-DT] and the others)
EF_Vpol = Setting value of the polarizing voltage ([EF1-Vpol])
Note: In the case of an internal fault, the phase angle is equal to the angle of the zero-
sequence impedance of the system, in a directly-earthed system this value is in
the range of approximately 50° to 90°. The sensing angle θ of the EF element can
be set between 0° to 180°. The minimum voltage necessary to maintain
directionality can be set from 0.5 to 100.0 V.

Reverse

−3Vo −3Vo −3Vo

θ=30°
θ=90°
Angle line

Forward
Reverse Forward Reverse Forward

θ=0° θ=30° θ=90°

Forward Reverse

Reverse

−3Vo −3Vo

Forward
θ=170°
θ=100°

θ=100° θ=170°

Figure 2.16-2 Examples of directional characteristic angle (θ)

GRL200 (Soft 033 & 037)


- 240 -
6F2S1914 (0.37)

(iii) Characteristic of directional EF in the reverse direction


The reverse characteristic is a mirror image of the forward characteristic. The setting and the
scheme switch, in addition to providing the setting of the directional EF element in the forward
direction, provides the setting of the directional EF element in the reverse direction: for
example, Reverse is set for the scheme switch [EF1-Dir] when the direction of the EF element
for stage 1 is considered.

2.16.2 Inverse time and definite time delay characteristic


The EF element monitors the earth-fault currents; when one of the currents is beyond the
threshold for the operation, the EF element will operate within a period that is defined by the
time characteristic feature. The user can choose the EF operate time delay characteristics,
either dependent (inverse) time characteristic delay (i.e., IDMT) or independent (definite) time
characteristic delay (i.e., DT). The operate time of the IDMT depends upon the level of the
energizing current, and the operate time in the DT is a constant.

For the reset time delay in the IDMT, either inverse(dependent)-time-reset or


definite(independent)-time-reset is characterized by the setting.

The user can select which characteristic will be applied to each stage of the EF
element by setting a scheme switch. We shall see the scheme switches later.

(i) DT characteristic
The operate time in the DT characteristic will be a constant time and is not affected by the
level of current. The reset time is set to zero so that resetting is performed immediately. The
user can set the operate time using a setting; it is discussed in section (iv).

(ii) IDMT characteristic


The operate time in the IDMT characteristic is inversely proportional to the level of the fault
current. The user can choose the operate time from a preset curve. Ten characteristic curves
are available; i.e. nine pre-installed curves covering IEC, IEEE, US and UK standard
characteristic curves and one original (user programmable) characteristic curve for which the
user can set the equation parameters. The IDMT curve equation and parameters will be
explained in section (iii).

The reset time of the IDMT is user selectable; either inverse-time-reset or definite-time-
reset is selected. For the inverse-time-rest, the user can choose the reset time for the preset
characteristic from six characteristic curves; i.e. IEEE and US standard five pre-installed
characteristic curves and one user original characteristic carver where the user can set the
equation parameters. The inverse-time-reset curve equation and parameters will be discussed

GRL200 (Soft 033 & 037)


- 241 -
6F2S1914 (0.37)

in section (v).

(iii) Operate time of IDMT


The dependent time in the IDMT is defined by Equation (2.16-4). (ref IEC 60255-151):

k
𝑡(𝐼) = 𝑇𝑀𝑆 × {[ α ] + c} (2.16-4)
(I⁄I ) − 1
s

where:
t = operating time for constant current I (seconds),
I = energizing current (amperes),
Is = earth fault current setting (amperes),
TMS = time multiplier setting,
k, α, c = constants defining curve.

The nine pre-programmed standard characteristic curve are defined in Table 2.16-2. In
addition, one original (user-programmable) curve can be applied. One curve can be chosen for
each EF stage. Figure 2.16-3 illustrates these characteristic curves. For example, the user
should set one for the scheme switches [EF1-Timer]. (That is, “IEC-NI” is for IEC Normal
Inverse, “IEC-VI” for IEC Very Inverse, “IEC-EI” for IEC Extremely Inverse, “UK-LTI” for UK
Long Time Inverse, “IEEE-MI “ for IEEE Moderately Inverse, “IEEE-VI” for IEEE Very Inverse,
“IEEE-EI” for IEEE Extremely Inverse, “US-CO2” for US CO2 short time inverse, “US-CO8” for
US CO8 inverse, and “Original” for user-programmable characteristic.)

In the IDMT operation, the user can also program the characteristic using time-
multiplier-setting (TMS) for the required operate time. For example, the IEC characteristic is
selected, the user can set the TMS value using the setting [EF1-TMS-IEC] (incidentally, the
default value of the TMS is 1.00). The other TMSs are also available by the [EF1-TMS-UK],
[EF1-TMS-IEEE], [EF1-TMS-US] and [EF1-TMS-ORG].
Table 2.16-2 Constants for IDMT
Curve type
Curve Description k α c
(IEC 60255-151)
A IEC Normal Inverse (IEC-NI) 0.14 0.02 0
B IEC Very Inverse (IEC-VI) 13.5 1 0
C IEC Extremely Inverse (IEC-EI) 80 2 0
- UK Long Time Inverse (UK-LTI) 120 1 0
D IEEE Moderately Inverse (IEEE-MI) 0.0515 0.02 0.114
E IEEE Very Inverse (IEEE-VI) 19.61 2 0.491
F IEEE Extremely Inverse (IEEE-EI) 28.2 2 0.1217
- US CO8 inverse (US-CO8) 5.95 2 0.18
- US CO2 short time inverse (US-CO2) 0.02394 0.02 0.01694

GRL200 (Soft 033 & 037)


- 242 -
6F2S1914 (0.37)

Figure 2.16-3 IDMT Characteristics curves

(iv) Operate time of DT


The operate time in the DT is a constant.

Time characteristic
The user should set DT for the scheme switch [EF1-Timer]. The value of the required operate
time is set for the setting [TEF1] in the range 0.00–300.00s.

Instantaneous activation
The instantaneous operation characteristic is achieved by setting zero for the [TEF1], but the
instantaneous one can be also obtained when the logic signal ‘1(High)” is programmed to be
injected at the PLC connection point “EF1_INST_OP”.

(v) Reset time for IDMT


Programming the reset time characteristic is available for the IEEE standard, US standard
and original (user-programmable) inverse-time-reset characteristic†. In the IEEE standard,
for example, the user can set DEP for the scheme switch [EF1-Rtimer]. The following equation

GRL200 (Soft 033 & 037)


- 243 -
6F2S1914 (0.37)

defines the reset time for the inverse-time-reset characteristic (ref. IEC 60255-151):

kr
𝑡(I) = 𝑅𝑇𝑀𝑆 × [ β
] (2.16-2)
I
1 − ( ⁄I )
s

where:
t = time required for the element to reset fully after complete operation (seconds),
I = energizing current (amperes),
Is = threshold setting (amperes),
kr = time required to reset fully after complete operation when the energizing current is
zero
RTMS = time multiplier setting for resetting.
β = constants defining curve.

For setting RTMS for the IEEE standard, the user can use setting [EF1-RTMS-IEEE]
(incidentally, the default value is 1.000). Similarly, settings [EF1-RTMS-US] and [EF1-RTMS-
ORG] are provided for the US standard and the original, respectively (For more information
w.r.t the values for the kr and β, see Table 2.16-3; Figure 2.16-4 shows the characteristic curves).
Table 2.16-3 Constants for inverse-time-reset characteristics
Curve Type kr
Curve Description β
IEC 60255-151 sec
A IEC Normal Inverse (IEC-NI‡) N/A N/A
B IEC Very Inverse (IEC-VI‡) N/A N/A
C IEC Extremely Inverse (IEC-EI‡) N/A N/A
- UK Long Time Inverse (UK-LTI‡) N/A N/A
D IEEE Moderately Inverse (IEEE-MI) 4.85 2
E IEEE Very Inverse (IEEE-VI) 21.6 2
F IEEE Extremely Inverse (IEEE-EI) 29.1 2
- US CO8 inverse (US-CO8) 5.95 2
- US CO2 short time inverse (US-CO2) 2.261 2

†Note: To select the inverse-time-reset characteristic, set [EF1-Rtimer]=DEP. Conversely


set [EF1-Rtimer]=DEF to select definite-time-reset characteristic,.
Note: For the setting [EF1-Rtimer]=DEP (inverse-time-reset), the integrated value will
be reduced in accordance to the magnitude of an energized current, when the
energized current is smaller than the setting [EF1]. The reducing degree will be
determined with the reset curve characteristics defined in the standards.
Note: For the setting [EF1-Rtimer]=DEF (definite-time-reset), the integrated value shall
be zero when an energized current is smaller than the setting [EF1], when the
small energized current is continued for timer setting [TEF1R]. The integrated
value will not be zero when the energized current does not flow small for the
setting [TEF1R]. DEF is allowed to set in the IEEE, US, and ORG. DEF is set
unconditionally in the IEC and UK.

GRL200 (Soft 033 & 037)


- 244 -
6F2S1914 (0.37)

Figure 2.16-4 Inverse-time-reset characteristics curves

Figure 2.16-5 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[EF1], will make an integrating value, which can determine how the element operates. If the
energized quantity (I) falls below the threshold setting [EF1], the element operation will return
to its reset stage after the time t(I) calculated in Equation (2.16-2).
Time 

Energizing current
Energizing current
cleared by tripping

Pickup threshold in relay [EF1] threshold

Measuring quantity 0A

Inverse-time-reset characteristic

Stage to element
return

Setting
[*-Rtimer]=DEP
Integrator

Trip signal

The integration will be deceased depending on the


[EF1-RTMS-*] reset characteristics.

Definite-time-reset characteristic
Stage to element
return

Setting
[*-Rtimer]=DEF

Integrator

Trip signal

Reset time
Integration will be kept in timer [TEF1R].
The integration will start again when the energizing current The integration will be reset when the energizing current
becomes larger than [EF1] within [TEF1R]. does not become larger than [EF1] in [TEF1R].

Figure 2.16-5 Inverse-time-reset characteristics

GRL200 (Soft 033 & 037)


- 245 -
6F2S1914 (0.37)

(vi) Reset time of DT


In the DT characteristic, the reset time is designed to be instant.

(vii) Summary of EF operation


Table 2.16-4 shows a summary for EF operation. Note that DEF will be set unconditionally in
IEC-NI, VI, EI and UK-LTI characteristics (†).
Table 2.16-4 Type and standard board in the EF (A tick represents a selectable function)
IDMT
Characteristics DT
IEC-NI IEC-VI IEC-EI UK-LTI IEEE-MI IEEE-VI IEEE-EI US-CO2 US-CO8 Original

DT 

Scheme switch [EF1-Timer]

IEC-NI
IEC-VI ✓
IEC-EI ✓
UK LTI ✓
IEEE-MI ✓
IEEE-VI ✓
IEEE-EI ✓
US-CO2 ✓
US-CO8 ✓
Original ✓
DEF N.A ✓† ✓† ✓† ✓† ✓ ✓ ✓ ✓ ✓ ✓

Scheme switch

N.A
[EF1-Rtimer]

N.A ✓
N.A ✓
DEP
N.A ✓
N.A ✓
N.A ✓

2.16.3 Threshold level for operation


The value of threshold current at which the EF (IEF) element will pick-up is configured by a
setting; the setting [EF1] is provided for both the IDMT and the DT characteristic. Note that
the settings of the threshold levels are allowed to have distinct values in the respective EF
elements. A rating current for the input is defined either 1A or 5A; the input rating is defined
on a VCT. (For more information about the VCT, see Chapter Technical description:
Transformer module for AC analogue input).

2.16.4 Reset Ratio


The ratio of the threshold current for pick-up to reset is applied using a setting; for example,
the ratio for the EF1 element is set using the setting [EF1-DPR]. The reset ratios for the other
EF elements are also provided.

2.16.5 Miscellaneous functions

GRL200 (Soft 033 & 037)


- 246 -
6F2S1914 (0.37)

(i) Blocking EF by ICD


The operation of each EF element can be blocked if the ICD function detects a second harmonic
current caused by the magnetizing inrush current phenomenon when a transformer is
energized. For example, for the EF1 element, the scheme switch [EF1-2fBlk] is provided, and
Block should be set when the user wishes to block the EF1 element when the second harmonic
associated with magnetizing inrush is present. Non is set for the scheme switch [EF1-2fBlk] as
the default setting. For more information about the ICD function, see Chapter Relay
application: Inrush current detection function.

(ii) Blocking EF by VTF


The operation of the EF element can be blocked by the voltage transformer failure (VTF)
function via a scheme switch. For example, Block is set for the scheme switch [EF1-VTFBlk] to
block the operation of the EF1 element during a VTF condition. Non is set for the scheme
switch [EF1-VTFBlk] as a default.

(iii) Blocking EF by CTF


The operation of the EF element can be blocked by the current transformer failure (CTF)
function via a scheme switch. For example, Block is set for the scheme switch [EF1-CTFBlk] to
block the operation of the EF1 element during a CTF condition. Non is set for the scheme
switch [EF1-CTFBlk] as a default.

(iv) EF operation for autoreclose


The EF element activates the auto-reclose (ARC) function. However, if ARC is not required,
Block is set for the scheme switch [EF1-ARCBlk]. Block is set for the scheme switch [EF1-
ARCBlk] as a default.

(v) Signal of EF trip


When a user requires an alarm signal in place of the trip signal; for example, set Alarm for the
scheme switch [EF1-UseFor]. Trip is set for the scheme switch [EF1-UseFor] for the normal
trip operation.

2.16.6 Scheme logic


The scheme logic for both the non-directional and the directional EF1 element is illustrated in
Figure 2.16-6; Figure 2.16-7 shows grouping commands for the trip circuit (TRC). The EF1
signal is generated when the pickup current exceeds a threshold, and then trip signals are
injected into the TRC. (For more information, see Chapter Relay application: Trip circuit
function)

GRL200 (Soft 033 & 037)


- 247 -
6F2S1914 (0.37)

8000011C23
EF1†
8000011C27

For DT characteristic EF1-PU†

EF1 TEF1
&
8000011B60 To Grouping logic
& &
t 0

For IDMT characteristic ≥1 EF1-OPT


0.00-300.00s
EF1 PU &
&
≥1 &
&
From ICD & EF1-OPT-TRIP
EF1_Timer DT
Trip
ICD-OR
& EF1-Usefor
IEC-NI & EF1-OPT-ALARM
EF1-2PBlk Alarm
IEC-VI
Block
IEC-EI EF1-ARCBlk
EF1-EN Block & EF1-ARC-BLOCK
On UK-LTI
From VTF
VTF_DETECT IEEE-MI
&
EF1-VTFBlk IEEE-VI

From CTF Block IEEE-EI


≥1 1
CTF_DETECT & US-C02
EF1-CTFBlk
US-C08
Block
8000011B63 ORIGINAL
800001EBB0 EF1_BLOCK
8000011B64
800001EBB1 EF1_INST_OP

Figure 2.16-6 Scheme logic for the EF1


†Note:The presence of ‘EF1’ and ‘EF1PU’ signals depends on the operation characteristic
defined with setting [EF1_Timer], as shown in Table 2.16-5.
Table 2.16-5 Signal behaviors of PLC monitoring points ‘EF1’ and ‘EF1PU’
Setting [EF1_Timer]
PLC monitoring points
DT IEC-NT,VI,EI, UK-LTI, IEET-MI,VI,EI, US-CO2,CO8, ORIGINAL
EF1-OR ○
1 ○
3
EF1PU-OR ○
2 ○
4

1 : A pick-up signal is generated instantly when the element operates.

2 : No signal due that the PU element is killed. Use ‘EF1’ in place of this.

3 : A pick-up signal is generated, but delayed with the IDMT characteristic.

4 : A pick-up signal is generated instantly.
From EF1 to EF4 logics
To TRC
EF1-OPT-TRIP ≥1 EF-OPT-TRIP
EF2-OPT-TRIP
EF3-OPT-TRIP
EF4-OPT-TRIP

EF1-OPT-ALARM ≥1 EF-OPT-ALARM
EF2-OPT- ALARM
EF3-OPT- ALARM
EF4-OPT- ALARM

EF1-ARC-BLOCK ≥1 EF-ARC-BLOCK
EF2- ARC-BLOCK
EF3- ARC-BLOCK
EF4- ARC-BLOCK

To Recording

EF1-OPT EF1-OPT
EF2-OPT EF2-OPT
EF3-OPT EF3-OPT
EF4-OPT EF4OPT

Figure 2.16-7 Grouping logic for TRC/Recording

GRL200 (Soft 033 & 037)


- 248 -
6F2S1914 (0.37)

2.16.7 Setting
EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
EF1-EN Off / On - EF1 protection scheme switch Off
EF2-EN Off / On - EF2 protection scheme switch Off
EF3-EN Off / On - EF3 protection scheme switch Off
EF4-EN Off / On - EF4 protection scheme switch Off
EF1 NonDir / Forward /
EF1-Dir - EF1 directional characteristic NonDir
Reverse
Fwd/ EF1-Angle 0 - 180 deg EF1 directional characteristic angle 45
Rev EF1-Vpol 0.5 - 100.0 V EF1 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
EF1-Timer IEEE-MI / IEEE-VI / - EF1 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
EF1 A EF1 threshold (in DT mode) 0.30 1.50
50.00 250.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
TEF1 0.00 - 300.00 s EF1 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-IEC 0.010 - 50.000 - EF1 time multiplier of IEC inverse curve 1.000
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
UK 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-UK 0.010 - 50.000 - EF1 time multiplier of UK inverse curve 1.000
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-
0.010 - 50.000 - EF1 time multiplier of IEEE inverse curve 1.000
IEEE
EF1-Rtimer DEF / DEP - EF1 reset delay type of IEEE DEF
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
EF1-RTMS- EF1 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-US 0.010 - 50.000 - EF1 time multiplier of US inverse curve 1.000
EF4-Rtimer DEF / DEP - EF1 reset delay type of US DEF
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
EF1 dependent reset time multiplier of US
EF1-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-ORG 0.010 - 50.000 - EF1 time multiplier of Original inverse curve 1.000
EF1-Rtimer DEF / DEP - EF1 reset delay type of ORG DEF
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
EF1-RTMS- EF1 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve

GRL200 (Soft 033 & 037)


- 249 -
6F2S1914 (0.37)

EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
EF1-k 0.00000 - 500.00000 - EF1 user original curve coefficient 0.00000
EF1-a 0.00000 - 10.00000 - EF1 user original curve coefficient 0.00000
EF1-c 0.00000 - 10.00000 - EF1 user original curve coefficient 0.00000
EF1-kr 0.00000 - 500.00000 - EF1 user original curve coefficient 0.00000
EF1-b 0.00000 - 10.00000 - EF1 user original curve coefficient 0.00000
Output EF1-VTFBlk Non / Block - EF1 operation block by VTF Non
EF1-CTFBlk Non / Block - EF1 operation block by CTF Non
EF1-UseFor Trip / Alarm - EF1 used for trip or alarm Trip
EF1-ARCBlk Non / Block - Autoreclose block by EF1 Block
EF2 NonDir / Forward /
EF2-Dir - EF2 directional characteristic NonDir
Reverse
Fwd/ EF2-Angle 0 - 180 deg EF2 directional characteristic angle 45
Rev EF2-Vpol 0.5 - 100.0 V EF2 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
EF2-Timer IEEE-MI / IEEE-VI / - EF2 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
EF2 A EF2 threshold (in DT mode) 0.30 1.50
50.00 250.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
TEF2 0.00 - 300.00 s EF2 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-IEC 0.010 - 50.000 - EF2 time multiplier of IEC inverse curve 1.000
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
UK 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-UK 0.010 - 50.000 - EF2 time multiplier of UK inverse curve 1.000
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-
0.010 - 50.000 - EF2 time multiplier of IEEE inverse curve 1.000
IEEE
EF2-Rtimer DEF / DEP - EF2 reset delay type of IEEE DEF
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
EF2-RTMS- EF2 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-US 0.010 - 50.000 - EF2 time multiplier of US inverse curve 1.000
EF4-Rtimer DEF / DEP - EF2 reset delay type of US DEF
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
EF2 dependent reset time multiplier of US
EF2-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-ORG 0.010 - 50.000 - EF2 time multiplier of Original inverse curve 1.000

GRL200 (Soft 033 & 037)


- 250 -
6F2S1914 (0.37)

EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
EF2-Rtimer DEF / DEP - EF2 reset delay type ORG DEF
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
EF2-RTMS- EF2 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
EF2-k 0.00000 - 500.00000 - EF2 user original curve coefficient 0.00000
EF2-a 0.00000 - 10.00000 - EF2 user original curve coefficient 0.00000
EF2-c 0.00000 - 10.00000 - EF2 user original curve coefficient 0.00000
EF2-kr 0.00000 - 500.00000 - EF2 user original curve coefficient 0.00000
EF2-b 0.00000 - 10.00000 - EF2 user original curve coefficient 0.00000
Output EF2-VTFBlk Non / Block - EF2 operation block by VTF Non
EF2-CTFBlk Non / Block - EF2 operation block by CTF Non
EF2-UseFor Trip / Alarm - EF2 used for trip or alarm Trip
EF2-ARCBlk Non / Block - Autoreclose block by EF2 Block
EF3 NonDir / Forward /
EF3-Dir - EF3 directional characteristic NonDir
Reverse
Fwd/ EF3-Angle 0 - 180 deg EF3 directional characteristic angle 45
Rev EF3-Vpol 0.5 - 100.0 V EF3 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
EF3-Timer IEEE-MI / IEEE-VI / - EF3 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
EF3 A EF3 threshold (in DT mode) 0.30 1.50
50.00 250.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
TEF3 0.00 - 300.00 s EF3 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-IEC 0.010 - 50.000 - EF3 time multiplier of IEC inverse curve 1.000
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
UK 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-UK 0.010 - 50.000 - EF3 time multiplier of UK inverse curve 1.000
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-
0.010 - 50.000 - EF3 time multiplier of IEEE inverse curve 1.000
IEEE
EF3-Rtimer DEF / DEP - EF3 reset delay type of IEEE DEF
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
EF3-RTMS- EF3 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-US 0.010 - 50.000 - EF3 time multiplier of US inverse curve 1.000
EF4-Rtimer DEF / DEP - EF3 reset delay type of US DEF
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
EF3 dependent reset time multiplier of US
EF3-RTMS-US 0.010 - 50.000 - 1.000
inverse curve

GRL200 (Soft 033 & 037)


- 251 -
6F2S1914 (0.37)

EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ORG 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-ORG 0.010 - 50.000 - EF3 time multiplier of Original inverse curve 1.000
EF3-Rtimer DEF / DEP - EF3 reset delay type of ORG DEF
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
EF3-RTMS- EF3 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
EF3-k 0.00000 - 500.00000 - EF3 user original curve coefficient 0.00000
EF3-a 0.00000 - 10.00000 - EF3 user original curve coefficient 0.00000
EF3-c 0.00000 - 10.00000 - EF3 user original curve coefficient 0.00000
EF3-kr 0.00000 - 500.00000 - EF3 user original curve coefficient 0.00000
EF3-b 0.00000 - 10.00000 - EF3 user original curve coefficient 0.00000
Output EF3-VTFBlk Non / Block - EF3 operation block by VTF Non
EF3-CTFBlk Non / Block - EF3 operation block by CTF Non
EF3-UseFor Trip / Alarm - EF3 used for trip or alarm Trip
EF3-ARCBlk Non / Block - Autoreclose block by EF3 Block
EF4 NonDir / Forward /
EF4-Dir - EF4 directional characteristic NonDir
Reverse
Fwd/ EF4-Angle 0 - 180 deg EF4 directional characteristic angle 45
Rev EF4-Vpol 0.5 - 100.0 V EF4 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
EF4-Timer IEEE-MI / IEEE-VI / - EF4 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
EF4 A EF4 threshold (in DT mode) 0.30 1.50
50.00 250.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
TEF4 0.00 - 300.00 s EF4 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-IEC 0.010 - 50.000 - EF4 time multiplier of IEC inverse curve 1.000
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
UK 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-UK 0.010 - 50.000 - EF4 time multiplier of UK inverse curve 1.000
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-
0.010 - 50.000 - EF4 time multiplier of IEEE inverse curve 1.000
IEEE
EF4-Rtimer DEF / DEP - EF4 reset delay type of IEEE DEF
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
EF4-RTMS- EF4 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-US 0.010 - 50.000 - EF4 time multiplier of US inverse curve 1.000

GRL200 (Soft 033 & 037)


- 252 -
6F2S1914 (0.37)

EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
EF4-Rtimer DEF / DEP - EF4 reset delay type of US DEF
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
EF4 dependent reset time multiplier of US
EF4-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-ORG 0.010 - 50.000 - EF4 time multiplier of Original inverse curve 1.000
EF4-Rtimer DEF / DEP - EF4 reset delay type of ORG DEF
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
EF4-RTMS- EF4 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
EF4-k 0.00000 - 500.00000 - EF4 user original curve coefficient 0.00000
EF4-a 0.00000 - 10.00000 - EF4 user original curve coefficient 0.00000
EF4-c 0.00000 - 10.00000 - EF4 user original curve coefficient 0.00000
EF4-kr 0.00000 - 500.00000 - EF4 user original curve coefficient 0.00000
EF4-b 0.00000 - 10.00000 - EF4 user original curve coefficient 0.00000
Output EF4-VTFBlk Non / Block - EF4 operation block by VTF Non
EF4-CTFBlk Non / Block - EF4 operation block by CTF Non
EF4-UseFor Trip / Alarm - EF4 used for trip or alarm Trip
EF4-ARCBlk Non / Block - Autoreclose block by EF4 Block

GRL200 (Soft 033 & 037)


- 253 -
6F2S1914 (0.37)

2.16.8 Data ID
 Signal monitoring point
EF(Function ID: 441001)
Element ID Name Description
8500001B62 EF-ARC-BLOCK Block for issuing autoreclose signal in the EF function

8400001B61 EF-OPT-ALARM Alarm signal issued in EF function

8300001B23 EF-OPT-TRIP Trip signal issued in EF function

8000011C23 EF1 EF1 relay element operated

8200011B62 EF1-ARC-BLOCK Block for issuing autoreclose signal in the EF1 element

8000011B60 EF1-OPT EF1 protection operated

8100011B61 EF1-OPT-ALARM Alarm signal in EF1 element

8000011B23 EF1-OPT-TRIP Trip signal issued in EF1 element

8000011C27 EF1PU Pick up signal in IDMT in EF1 element

8000011B63 EF1_BLOCK Command to block the EF1 element

8000011B64 EF1_INST_OP Command to operate the EF1 element instantly

8100021C23 EF2 EF2 relay element operated

8200021B62 EF2-ARC-BLOCK Block for issuing autoreclose signal in the EF2 element

8100021B60 EF2-OPT EF2 protection operated

8100021B61 EF2-OPT-ALARM Alarm signal in EF2 element

8000021B23 EF2-OPT-TRIP Trip signal issued in EF2 element

8100021C27 EF2PU Pick up signal in IDMT in EF2 element

8100021B63 EF2_BLOCK Command to block the EF2 element

8100021B64 EF2_INST_OP Command to operate the EF2 element instantly

8200031C23 EF3 EF3 relay element operated

8200031B62 EF3-ARC-BLOCK Block for issuing autoreclose signal in the EF3 element

8200031B60 EF3-OPT EF3 protection operated

8100031B61 EF3-OPT-ALARM Alarm signal in EF3 element

8000031B23 EF3-OPT-TRIP Trip signal issued in EF3 element

8200031C27 EF3PU Pick up signal in IDMT in EF3 element

8200031B63 EF3_BLOCK Command to block the EF3 element

8200031B64 EF3_INST_OP Command to operate the EF3 element instantly

8300041C23 EF4 EF4 relay element operated

8200041B62 EF4-ARC-BLOCK Block for issuing autoreclose signal in the EF4 element

8300041B60 EF4-OPT EF4 protection operated

8100041B61 EF4-OPT-ALARM Alarm signal in EF4 element

8000041B23 EF4-OPT-TRIP Trip signal issued in EF4 element

8300041C27 EF4PU Pick up signal in IDMT in EF4 element

8300041B63 EF4_BLOCK Command to block the EF4 element

8300041B64 EF4_INST_OP Command to operate the EF4 element instantly

 Connection point on PLC logic


EF(Function ID: 441001)
Element ID Name Description
800001EBB0 EF1_BLOCK EF1 protection block command

800001EBB1 EF1_INST_OP EF1 protection instant operation command

810002EBB0 EF2_BLOCK EF2 protection block command

810002EBB1 EF2_INST_OP EF2 protection instant operation command

GRL200 (Soft 033 & 037)


- 254 -
6F2S1914 (0.37)

 Connection point on PLC logic


EF(Function ID: 441001)
Element ID Name Description
820003EBB0 EF3_BLOCK EF3 protection block command

820003EBB1 EF3_INST_OP EF3 protection instant operation command

830004EBB0 EF4_BLOCK EF4 protection block command

830004EBB1 EF4_INST_OP EF4 protection instant operation command

GRL200 (Soft 033 & 037)


- 255 -
6F2S1914 (0.37)

Negative sequence overcurrent protection (OCN)


Negative-sequence overcurrent protection (OCN) function has both time characteristic and
directional elements. Four stages (elements) are available in the OCN function. The user can
select various features using the scheme switches provided. The elements are named OCN1,
OCN2, and others; and they operate independently.

To simplify the description, only OCN1 is discussed but is applicable to the other OCNs;
hence, read the expression for OCN1 as OCN2, OCN3, and OCN4 at each stage unless a special
explanation or instruction has been provided.

─────────────────────────────────────────────────────────────────
Note: The number of relay elements depends on the IED model. To know the number in
respective IED models, locate the IED ordering number; and check the order number at “G&T
position” referring to the comparison table below. For more information, see Appendix:
Ordering.
Table 2.17-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
No. of stages
33 37
Non-Directional / directional NOC protection 4 ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 256 -
6F2S1914 (0.37)

2.17.1 Relay polarity


The user can choose either non-directional OCN or directional OCN for each OCN stage. In
addition, the user can further select either the forward or the direction for each of the
directional OCN elements selected.

(i) Characteristic of a non-directional OCN


The characteristic of the non-directional type (non-directional OCN) is a circle at the origin. A
setting and a scheme switch is used to configure each non-directional OCN element; i.e., the
user can set the threshold value of non-directional OCN element for state 1 using setting
[OCN1], provided time characteristic is required for define time delay (DT) described in section
2.17.2(i). NonDir is set for the scheme switch [OCN1-Dir].

(ii) Characteristic of directional OCN in the forward


As shown in Figure 2.17-1, the characteristic of the directional-OCN elements in the forward
direction is a semi-circle based upon the border-line; the hatched area shows the operating
region of the directional-OCN.

Non-operation (No trip) zone

Reference voltage or
θ Polarizing voltage (−V2)
φ

I2

Operation (Trip) zone

Figure 2.17-1 Characteristic of the directional-OCN element in the forward direction


Note: Directional characteristic angle (θ) forms the angle between the reference
quantity and the directional characteristic angle line. The half plane
represents the zone of operation bordered on one side by the border line and
extending in the direction that contains both the reference (polarizing) and
operating quantities.

A setting and a scheme switch, as well as the non-directional OCN element, provide the
settings for the directional OCN element: for example, the user can set the threshold value

GRL200 (Soft 033 & 037)


- 257 -
6F2S1914 (0.37)

(IOCN) for stage 1 with the setting [OCN1] and Forward can be set for the scheme switch [OCN1-
Dir]. Setting of the sensing angle (θ) is configured by the setting [OCN1-Angle] with the value
of θ in the range of 0–180°. Figure 2.17-2 shows an example of an angle and a characteristic
using the θ.
The operation decision of OCN uses the following equation:
𝐼2 ≥ 𝐼𝑂𝐶𝑁 (2.17-1)
𝐼2 × cos(φ − θ) ≥ 0 (2.17-2)
𝑉2 ≥ 𝑂𝐶𝑁_𝑉𝑝𝑜𝑙 (2.17-3)
where
I2 = Negative phase sequence current
V2 = Negative phase sequence voltage
−V2 = reference voltage (or polarizing voltage)
Φ = lagging angle
θ = OCN setting angle ([OCN1-Angle])
IOCN = Setting value of OCN ([OCN1] and the others])
OCN_Vpol = Setting value of the polarizing voltage ([OCN1-Vpol])

Note: The phase angle in the event of an internal fault is equal to the angle of the zero-
sequence impedance of the system; this value ranges approximately from 50° to
90°. The θ of OCN can be set from 0° to 180°. The minimum voltage necessary to
maintain directionality can be set from 0.5 to 180 V.

Reverse

Vpol Vpol Vpol

θ=30°
θ=90°
Angle line

Forward
Reverse Forward Reverse Forward

θ=0° θ=30° θ=90°

Forward Reverse

Reverse

Vpol Vpol

Forward
θ=170°
θ=100°

θ=100° θ=170°

Figure 2.17-2 Examples of directional characteristic angle (θ)

GRL200 (Soft 033 & 037)


- 258 -
6F2S1914 (0.37)

(iii) Characteristic of directional OCN in the reverse


The reverse characteristic is a mirror image of the forward characteristic. The setting and the
scheme switch, in addition to providing the setting of the directional OCN element in the
forward direction, provides the setting of the directional EF element in the reverse direction:
for example, Reverse is set for the scheme switch [OCN1-Dir] when the direction of the OCN
element for stage 1 is considered.

2.17.2 Inverse time and definite time delay characteristic


The OCN element monitors the negative-sequence current; when the negative-sequence
current is beyond the threshold for the operation, the OCN element will operate within a period
that is defined by the time characteristic feature. The user can choose the one of the operate
time delay characteristics: (i) dependent (inverse) time characteristic delay (i.e., IDMT) or (ii)
independent (definite) time characteristic delay (i.e., DT). The operate time of the IDMT
depends upon the level of the negative-sequence current, whereas the operate time in the DT
is a constant.

For the reset time delay in the IDMT, either inverse (dependent)-time-reset or
definite(independent)-time-reset is characterized by the setting.

The user can select which characteristic will be applied to each stage of the OCN
element using scheme switches. We shall see the scheme switches later.

(i) DT characteristic
The operate time in the DT characteristic will be a constant time; it is not affected by the level
of the negative-sequence current. The reset time is set to zero so that resetting is performed
immediately. The user can set the operate time using a setting; it is discussed in sections (iv).

(ii) IDMT characteristic


The operate time in the IDMT characteristic is inversely proportional to the level of the fault
current. The user can choose the operate time from a preset curve. Ten characteristic curves
are available; i.e. nine pre-installed curves covering IEC, IEEE, US and UK standard
characteristic curves and one original (user programmable) characteristic curve for which the
user can set the equation parameters. The IDMT curve equation and parameters will be
explained in section (iii).

The reset time of the IDMT is also user-selectable; either inverse-time-reset or definite-
time-reset is selected. For the inverse-time-rest, the user can choose the reset time for the
preset characteristic from six characteristic curves; i.e. IEEE and US standard five pre-

GRL200 (Soft 033 & 037)


- 259 -
6F2S1914 (0.37)

installed characteristic curves and one user-original characteristic carver where the user can
set the equation parameters. The inverse-time-reset curve equation and parameters will be
discussed in section (v).

(iii) Operate time of IDMT


The dependent time in the IDMT is defined by Equation (2.17-4). (ref IEC 60255-151):

k
𝑡(𝐼) = 𝑇𝑀𝑆 × {[ α ] + c} (2.17-4)
(I⁄I ) − 1
s

where:
t = operating time for constant current I (seconds),
I = energizing current (amperes),
Is = earth fault current setting (amperes),
TMS = time multiplier setting,
k, α, c = constants defining curve.

The nine pre-programmed standard characteristic curve are tabulated in Table 2.17-2;
additionally, one original (user-programmable) curve can be applied. One curve can be chosen
for each OCN stage by setting. Figure 2.17-3 illustrates these characteristic curves. For
example, the user should set one for the scheme switch [OCN1-Timer]: “IEC-NI” for IEC Normal
Inverse, “IEC-VI” for IEC Very Inverse, “IEC-EI” for IEC Extremely Inverse, “UK-LTI” for UK
Long Time Inverse, “IEEE-MI “ for IEEE Moderately Inverse, “IEEE-VI” for IEEE Very Inverse,
“IEEE-EI” for IEEE Extremely Inverse, “US-CO2” for US CO2 short time inverse, “US-CO8” for
US CO8 inverse, and “Original” for user-programmable characteristic.

In the IDMT operation, the user can also program the characteristic using time-
multiplier-setting (TMS) for the required operate time. For example, when the IEC
characteristic is selected, the user can set the TMS value using the setting [OCN1-TMS-IEC]
(incidentally, the default value of the TMS is 1.00). The other TMSs are also available by the
[OCN1-TMS-UK], [OCN1-TMS-IEEE], [OCN1-TMS-US] and [OCN1-TMS-ORG].
Table 2.17-2 Constants for IDMT
Curve type
Curve Description k α c
(IEC 60255-151)
A IEC Normal Inverse (IEC-NI) 0.14 0.02 0
B IEC Very Inverse (IEC-VI) 13.5 1 0
C IEC Extremely Inverse (IEC-EI) 80 2 0
- UK Long Time Inverse (UK-LTI) 120 1 0
D IEEE Moderately Inverse (IEEE-MI) 0.0515 0.02 0.114
E IEEE Very Inverse (IEEE-VI) 19.61 2 0.491
F IEEE Extremely Inverse (IEEE-EI) 28.2 2 0.1217
- US CO8 inverse (US-CO8) 5.95 2 0.18
- US CO2 short time inverse (US-CO2) 0.02394 0.02 0.01694

GRL200 (Soft 033 & 037)


- 260 -
6F2S1914 (0.37)

Figure 2.17-3 IDMT Characteristics curves

(iv) Operate time of DT


The operate time in the DT is a constant.

Time characteristic
The user should set DT for the scheme switch [OCN1-Timer]. The value of the required operate
time is set for the setting [TOCN1] in the range 0.00–300.00s.

Instantaneous activation
The instantaneous operation characteristic is achieved by setting zero for the [TOCN1], but the
instantaneous one can be also obtained when the logic signal “1 (High)” is programmed to be
injected at PLC connection point “OCN1_INST_OP”.

(v) Reset time of IDMT


Programming the reset time characteristic is available for the IEEE standard, US standard
and original (user-programmable) dependent time characteristic†. In the IEEE standard, for
example, the user can set DEP for the scheme switch [OCN1-Rtimer]. The following equation

GRL200 (Soft 033 & 037)


- 261 -
6F2S1914 (0.37)

defines the reset time for the inverse-time-reset characteristic (ref. IEC 60255-151):

kr
𝑡(I) = 𝑅𝑇𝑀𝑆 × [ β
] (2.17-2)
I
1 − ( ⁄I )
s

where:
t = time required for the element to reset fully after complete operation (seconds),
I = energizing current (amperes),
Is = threshold setting (amperes),
kr = time required to reset fully after complete operation when the energizing current is
zero
RTMS = time multiplier setting for resetting.
β = constants defining curve.

For setting RTMS for the IEEE standard, the user can use setting [OCN1-RTMS-IEEE]
(incidentally, the default value is 1.000). Similarly, settings [OCN1-RTMS-US] and [OCN1-
RTMS-ORG] are provided for the US standard and the original, respectively (For more
information w.r.t the values for kr and β, see Table 2.17-3; Figure 2.17-4 shows the
characteristic curves).
Table 2.17-3 Constants for inverse-time-reset characteristics
Curve Type kr β
Curve Description
IEC 60255-151 (sec)
A IEC Normal Inverse (IEC-NI‡) N/A N/A
B IEC Very Inverse (IEC-VI‡) N/A N/A
C IEC Extremely Inverse (IEC-EI‡) N/A N/A
- UK Long Time Inverse (UK-LTI‡) N/A N/A
D IEEE Moderately Inverse (IEEE-MI) 4.85 2
E IEEE Very Inverse (IEEE-VI) 21.6 2
F IEEE Extremely Inverse (IEEE-EI) 29.1 2
- US CO8 inverse (US-CO8) 5.95 2
- US CO2 short time inverse (US-CO2) 2.261 2
†Note: To select the inverse-time-reset characteristic, set [OCN1-Rtimer]=DEP.
Conversely set [OCN1-Rtimer]=DEF to select definite-time-reset characteristic,.
Note: For the setting [OCN1-Rtimer]=DEP (inverse-time-reset), the integrated value will
be reduced in accordance to the magnitude of an energized current, when the
energized current is smaller than the setting [OCN1]. The reducing degree will be
determined with the reset curve characteristics defined in the standards.
Note: For the setting [OCN1-Rtimer]=DEF (definite-time-reset), the integrated value
shall be zero when an energized current is smaller than the setting [OCN1], when
the small energized current is continued for timer setting [TOCN1R]. The
integrated value will not be zero when the energized current does not flow small
for the setting [TOCN1R]. DEF is allowed to set in the IEEE, US, and ORG. DEF is
set unconditionally in the IEC and UK (see Table 2.17-4).

GRL200 (Soft 033 & 037)


- 262 -
6F2S1914 (0.37)

Figure 2.17-4 Inverse-time-reset characteristics curves


Figure 2.17-5 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[OCN1], will make an integrating value, which can determine how the element operates. If the
energized quantity (I) falls below the threshold setting [OCN1], the element operation will
return to its reset stage after the time t(I) calculated in Equation (2.17-2).
Time 

Energizing current
Energizing current
cleared by tripping

Pickup threshold in relay [OCN1] threshold

Measuring quantity 0A

Inverse-time-reset characteristic

Stage to element
return

Setting
[*-Rtimer]=DEP
Integrator

Trip signal

The integration will be deceased depending on the


[OCN1-RTMS-*] reset characteristics.

Definite-time-reset characteristic
Stage to element
return

Setting
[*-Rtimer]=DEF

Integrator

Trip signal

Reset time
Integration will be kept in timer [TOCN1R].
The integration will start again when the energizing current The integration will be reset when the energizing current
becomes larger than [OCN1] within [TOCN1R]. does not become larger than [OCN1] in [TOCN1R].

Figure 2.17-5 Inverse-time-reset characteristics

GRL200 (Soft 033 & 037)


- 263 -
6F2S1914 (0.37)

(vi) Reset time of DT


In the DT characteristic, the reset time is designed to be instant.

(vii) Summary of OCN operation


Table 2.17-4 shows a summary for OCN operation. Note that DEF will be set unconditionally
in IEC-NI, VI, EI and UK-LTI characteristics (†).
Table 2.17-4 Type and standard board in the OCN1 (A tick represents a selectable function)
IDMT
Characteristics DT
IEC-NI IEC-VI IEC-EI UK-LTI IEEE-MI IEEE-VI IEEE-EI US-CO2 US-CO8 Original

DT 

Scheme switch [OCN1-Timer]

IEC-NI

IEC-VI ✓
IEC-EI ✓
UK LTI ✓
IEEE-MI ✓
IEEE-VI ✓
IEEE-EI ✓
US-CO2 ✓
US-CO8 ✓
Original ✓
DEF N.A ✓† ✓† ✓† ✓† ✓ ✓ ✓ ✓ ✓ ✓

Scheme switch
[OCN1-Rtimer]

N.A
N.A ✓
N.A ✓
DEP
N.A ✓
N.A ✓
N.A ✓

2.17.3 Threshold value


The value of threshold current at which the OCN (I2) element will pick-up is configured by
settings; the setting [OCN1] is provided for both the IDMT and the DT characteristic. Note
that the settings of the threshold levels are allowed to have distinct values in the respective
OCN elements. A rating current for the input is defined either 1A or 5A; the input rating is
defined on a VCT. (For more information about the VCT, see Chapter Technical description:
Transformer module for AC analogue input).

2.17.4 Reset Ratio


The ratio of the threshold current for pick-up to reset is applied using a setting; for example,
the ratio for the OCN1 element is set using the setting [OCN1-DPR]. The reset ratios for the
other OCN elements are also provided.

2.17.5 Miscellaneous functions

GRL200 (Soft 033 & 037)


- 264 -
6F2S1914 (0.37)

(i) Harmonic detection


The operation of each OCN element can be blocked using a scheme switch, if the ICD function
detects a second harmonic current caused by the magnetizing inrush current phenomenon
when a transformer is energized. For example, for the OCN1 element, the scheme switch
[OCN1-2fBlk] is provided, and Block should be set when the user wishes to block the OCN1
element when the second harmonic associated with magnetizing inrush is present. Non is set
for the scheme switch [OCN1-2fBlk] as the default setting. For more information about the ICD
function, see Chapter Relay application: Inrush current detection function.

(ii) Blocking OCN by VTF


The operation of the OCN element can be blocked by the voltage transformer failure (VTF)
function via a scheme switch. For example, Block is set for the scheme switch [OCN1-VTFBlk]
to block the operation of the OCN1 element during a VTF condition. Non is set for the scheme
switch [OCN1-VTFBlk] as a default. For more information about the VTF, see Chapter Relay
application: VT failure detection.

(iii) Blocking OCN by CTF


The operation of the OCN element can be blocked by the current transformer failure (CTF)
function via a scheme switch. For example, Block should be set for the scheme switch [OCN1-
CTFBlk] to block the operation of the OCN1 element during a CTF condition. Non is set for the
scheme switch [OCN1-CTFBlk] as a default. For more information about the CTF, see Chapter
Relay application: CT failure detection.

(iv) OCN operation for autoreclose


The OCN element activates the auto-reclose (ARC) function. However, if ARC is not required,
Block is set for the scheme switch [OCN1-ARCBlk]. Block is set for the scheme switch [OCN1-
ARCBlk] as a default.

(v) Signal of OCN trip


When a user requires an alarm signal in place of the trip signal; for example, set Alarm for the
scheme switch [OCN1-UseFor]. Trip is set for the scheme switch [OCN1-UseFor] for the normal
trip operation.

2.17.6 Scheme logic


The scheme logic of both the non-directional and the directional OCN1 is illustrated in Figure
2.17-6; Figure 2.17-7 shows grouping commands for the trip circuit (TRC). The OCN1 signal is
generated when the pickup current exceeds a threshold, and then trip signals are injected into
the TRC. (For more information, see Chapter Relay application: Trip circuit function)

GRL200 (Soft 033 & 037)


- 265 -
6F2S1914 (0.37)

8000011C23
OCN1†
8000011C27
For DT characteristic OCN1PU†
OCN1 TOCN1
&
8000011B60 To Grouping logic
& &
t 0

For IDMT characteristic ≥1 OCN1-OPT


0.00-300.00s
OCN1 PU &
&
≥1 &
From ICD &
& OCN1-OPT-TRIP
OCN1_Timer DT
TRIP
ICD-OR
& OCN1-USEFOR
IEC-NI & OCN1-OPT-ALARM
OCN1-2PBlk ALARM
IEC-VI
Block
IEC-EI OCN1-ARCBLK
OCN1-EN BLOCK & OCN1-ARC-BLOCK
ON UK-LTI
From VTF
IEEE-MI
VTF_DETECT &
IEEE-VI
OCN1-VTFBLK BLOCK
≥1
From CTF IEEE-EI
CTF_DETECT & US-C02
OCN1-CTFBLK BLOCK US-C08

8000011BB0
ORIGINAL
800001EBB0 OCN1_BLOCK
8000011BB1
800001EBB1 OCN1_INST_OP

Figure 2.17-6 Scheme logic of OCN1


†Note:The presence of ‘OCN1’ and ‘OCN1PU’ signals depends on the operation
characteristic defined with setting [OCN1_Timer], as shown in Table 2.17-5.
Table 2.17-5 Signal behaviors of PLC monitoring points ‘OCN1’ and ‘OCN1PU’
Setting [OCN1_Type]
PLC monitoring points
DT IEC-NT,VI,EI, UK-LTI, IEET-MI,VI,EI, US-CO2,CO8, ORIGINAL
OCN1-OR ○
1 ○
3
OCN1PU-OR ○
2 ○
4


1 : A pick-up signal is generated instantly when the element operates.

2 : No signal due that the PU element is killed. Use ‘OCN1’ in place of this.

3 : A pick-up signal is generated, but delayed with the IDMT characteristic.

4 : A pick-up signal is generated instantly.

From OCN1 to OCN4 logics


To TRC
OCN1-OPT-TRIP ≥1 OCN-OPT-TRIP
OCN2-OPT-TRIP
OCN3-OPT-TRIP
OCN4-OPT-TRIP

OCN1-OPT-ALARM ≥1 OCN-OPT-ALARM
OCN2-OPT- ALARM
OCN3-OPT- ALARM
OCN4-OPT- ALARM

OCN1-ARC-BLOCK ≥1 OCN-ARC-BLEFK
OCN2- ARC-BLOCK
OCN3- ARC-BLOCK
OCN4- ARC-BLOCK To Recording

OCN1-OPT OCN1-OPT
OCN2-OPT OCN2-OPT
OCN3-OPT OCN3-OPT
OCN4-OPT OCN4OPT

Figure 2.17-7 Grouping logic for TRC/Recording

GRL200 (Soft 033 & 037)


- 266 -
6F2S1914 (0.37)

2.17.7 Setting
OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OCN1-EN Off / On - OCN1 protection scheme switch Off
OCN2-EN Off / On - OCN2 protection scheme switch Off
OCN3-EN Off / On - OCN3 protection scheme switche Off
OCN4-EN Off / On - OCN4 protection scheme switch Off
OCN1 NonDir / Forward /
OCN1-Dir - OCN1 directional characteristic NonDir
Reverse
Fwd/ OCN1-Angle 0 - 180 deg OCN1 directional characteristic angle 45
Rev OCN1-Vpol 0.5 - 25.0 V OCN1 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OCN1-Timer IEEE-MI / IEEE-VI / - OCN1 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OCN1 A OCN1 threshold (in DT mode) 0.40 2.00
50.00 250.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
TOCN1 0.00 - 300.00 s OCN1 operating delay time 1.00
IEC 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-
0.010 - 50.000 - OCN1 time multiplier of IEC inverse curve 1.000
IEC
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-
0.010 - 50.000 - OCN1 time multiplier of UK inverse curve 1.000
UK
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-
0.010 - 50.000 - OCN1 time multiplier of IEEE inverse curve 1.000
IEEE
OCN1-Rtimer DEF / DEP - OCN1 reset delay type of IEEE DEF
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
OCN1-RTMS- OCN1 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-US 0.010 - 50.000 - OCN1 time multiplier of US inverse curve 1.000
OCN1-Rtimer DEF / DEP - OCN1 reset delay type of US DEF
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
OCN1-RTMS- OCN1 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-
0.010 - 50.000 - OCN1 time multiplier of US inverse curve 1.000
ORG
OCN1-Rtimer DEF / DEP - OCN1 reset delay type of ORG DEF

GRL200 (Soft 033 & 037)


- 267 -
6F2S1914 (0.37)

OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
OCN1-RTMS- OCN1 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OCN1-k 0.00000 - 500.00000 - OCN1 user original curve coefficient 0.00000
OCN1-a 0.00000 - 10.00000 - OCN1 user original curve coefficient 0.00000
OCN1-c 0.00000 - 10.00000 - OCN1 user original curve coefficient 0.00000
OCN1-kr 0.00000 - 500.00000 - OCN1 user original curve coefficient 0.00000
OCN1-b 0.00000 - 10.00000 - OCN1 user original curve coefficient 0.00000
Output OCN1-2fBlk Non / Block - OCN1 operation block by 2f-detection Non
OCN1-VTFBlk Non / Block - OCN1 operation block by VTF Non
OCN1-CTFBlk Non / Block - OCN1 operation block by CTF Non
OCN1-UseFor Trip / Alarm - OCN1 used for trip or alarm Trip
OCN1-ARCBlk Non / Block - Autoreclose block by OCN1 Block
OCN2 NonDir / Forward /
OCN2-Dir - OCN2 directional characteristic NonDir
Reverse
Fwd/ OCN2-Angle 0 - 180 deg OCN2 directional characteristic angle 45
Rev OCN2-Vpol 0.5 - 25.0 V OCN2 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OCN2-Timer IEEE-MI / IEEE-VI / - OCN2 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OCN2 A OCN2 threshold (in DT mode) 0.40 2.00
50.00 250.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
TOCN2 0.00 - 300.00 s OCN2 operating delay time 1.00
IEC 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-
0.010 - 50.000 - OCN2 time multiplier of IEC inverse curve 1.000
IEC
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-
0.010 - 50.000 - OCN2 time multiplier of UK inverse curve 1.000
UK
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-
0.010 - 50.000 - OCN2 time multiplier of IEEE inverse curve 1.000
IEEE
OCN2-Rtimer DEF / DEP - OCN2 reset delay type of IEEE DEF
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
OCN2-RTMS- OCN2 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-US 0.010 - 50.000 - OCN2 time multiplier of US inverse curve 1.000
OCN2-Rtimer DEF / DEP - OCN2 reset delay type of US DEF
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00

GRL200 (Soft 033 & 037)


- 268 -
6F2S1914 (0.37)

OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OCN2-RTMS- OCN2 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-
0.010 - 50.000 - OCN2 time multiplier of US inverse curve 1.000
ORG
OCN2-Rtimer DEF / DEP - OCN2 reset delay type of ORG DEF
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
OCN2-RTMS- OCN2 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OCN2-k 0.00000 - 500.00000 - OCN2 user original curve coefficient 0.00000
OCN2-a 0.00000 - 10.00000 - OCN2 user original curve coefficient 0.00000
OCN2-c 0.00000 - 10.00000 - OCN2 user original curve coefficient 0.00000
OCN2-kr 0.00000 - 500.00000 - OCN2 user original curve coefficient 0.00000
OCN2-b 0.00000 - 10.00000 - OCN2 user original curve coefficient 0.00000
Output OCN2-2fBlk Non / Block - OCN2 operation block by 2f-detection Non
OCN2-VTFBlk Non / Block - OCN2 operation block by VTF Non
OCN2-CTFBlk Non / Block - OCN2 operation block by CTF Non
OCN2-UseFor Trip / Alarm - OCN2 used for trip or alarm Trip
OCN2-ARCBlk Non / Block - Autoreclose block by OCN2 Block
OCN3 NonDir / Forward /
OCN3-Dir - OCN3 directional characteristic NonDir
Reverse
Fwd/ OCN3-Angle 0 - 180 deg OCN3 directional characteristic angle 45
Rev OCN3-Vpol 0.5 - 25.0 V OCN3 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OCN3-Timer IEEE-MI / IEEE-VI / - OCN3 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OCN3 A OCN3 threshold (in DT mode) 0.40 2.00
50.00 250.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
TOCN3 0.00 - 300.00 s OCN3 operating delay time 1.00
IEC 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-
0.010 - 50.000 - OCN3 time multiplier of IEC inverse curve 1.000
IEC
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-
0.010 - 50.000 - OCN3 time multiplier of UK inverse curve 1.000
UK
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-
0.010 - 50.000 - OCN3 time multiplier of IEEE inverse curve 1.000
IEEE
OCN3-Rtimer DEF / DEP - OCN3 reset delay type of IEEE DEF
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00

GRL200 (Soft 033 & 037)


- 269 -
6F2S1914 (0.37)

OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OCN3-RTMS- OCN3 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-US 0.010 - 50.000 - OCN3 time multiplier of US inverse curve 1.000
OCN3-Rtimer DEF / DEP - OCN3 reset delay type of US DEF
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
OCN3-RTMS- OCN3 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-
0.010 - 50.000 - OCN3 time multiplier of US inverse curve 1.000
ORG
OCN3-Rtimer DEF / DEP - OCN3 reset delay type of ORG DEF
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
OCN3-RTMS- OCN3 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OCN3-k 0.00000 - 500.00000 - OCN3 user original curve coefficient 0.00000
OCN3-a 0.00000 - 10.00000 - OCN3 user original curve coefficient 0.00000
OCN3-c 0.00000 - 10.00000 - OCN3 user original curve coefficient 0.00000
OCN3-kr 0.00000 - 500.00000 - OCN3 user original curve coefficient 0.00000
OCN3-b 0.00000 - 10.00000 - OCN3 user original curve coefficient 0.00000
Output OCN3-2fBlk Non / Block - OCN3 operation block by 2f-detection Non
OCN3-VTFBlk Non / Block - OCN3 operation block by VTF Non
OCN3-CTFBlk Non / Block - OCN3 operation block by CTF Non
OCN3-UseFor Trip / Alarm - OCN3 used for trip or alarm Trip
OCN3-ARCBlk Non / Block - Autoreclose block by OCN3 Block
OCN4 NonDir / Forward /
OCN4-Dir - OCN4 directional characteristic NonDir
Reverse
Fwd/ OCN4-Angle 0 - 180 deg OCN4 directional characteristic angle 45
Rev OCN4-Vpol 0.5 - 25.0 V OCN4 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OCN4-Timer IEEE-MI / IEEE-VI / - OCN4 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OCN4 A OCN4 threshold (in DT mode) 0.40 2.00
50.00 250.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
TOCN4 0.00 - 300.00 s OCN4 operating delay time 1.00
IEC 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-
0.010 - 50.000 - OCN4 time multiplier of IEC inverse curve 1.000
IEC
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-
0.010 - 50.000 - OCN4 time multiplier of UK inverse curve 1.000
UK
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00

GRL200 (Soft 033 & 037)


- 270 -
6F2S1914 (0.37)

OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
IEEE 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-
0.010 - 50.000 - OCN4 time multiplier of IEEE inverse curve 1.000
IEEE
OCN4-Rtimer DEF / DEP - OCN4 reset delay type of IEEE DEF
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
OCN4-RTMS- OCN4 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-US 0.010 - 50.000 - OCN4 time multiplier of US inverse curve 1.000
OCN4-Rtimer DEF / DEP - OCN4 reset delay type of US DEF
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
OCN4-RTMS- OCN4 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-
0.010 - 50.000 - OCN4 time multiplier of US inverse curve 1.000
ORG
OCN4-Rtimer DEF / DEP - OCN4 reset delay type of ORG DEF
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
OCN4-RTMS- OCN4 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OCN4-k 0.00000 - 500.00000 - OCN4 user original curve coefficient 0.00000
OCN4-a 0.00000 - 10.00000 - OCN4 user original curve coefficient 0.00000
OCN4-c 0.00000 - 10.00000 - OCN4 user original curve coefficient 0.00000
OCN4-kr 0.00000 - 500.00000 - OCN4 user original curve coefficient 0.00000
OCN4-b 0.00000 - 10.00000 - OCN4 user original curve coefficient 0.00000
Output OCN4-2fBlk Non / Block - OCN4 operation block by 2f-detection Non
OCN4-VTFBlk Non / Block - OCN4 operation block by VTF Non
OCN4-CTFBlk Non / Block - OCN4 operation block by CTF Non
OCN4-UseFor Trip / Alarm - OCN4 used for trip or alarm Trip
OCN4-ARCBlk Non / Block - Autoreclose block by OCN4 Block

GRL200 (Soft 033 & 037)


- 271 -
6F2S1914 (0.37)

2.17.8 Data ID
 Signal monitoring point
OCN(Function ID: 443001)
Element ID Name Description
OCN-ARC-BLOCK 8500001B62 Autoreclose block signal by OCN protection

OCN-OPT-ALARM 8400001B61 Alarm signal by OCN protection

OCN-OPT-TRIP 8300001B23 Trip signal by OCN protection

OCN1 8000011C23 OCN1 relay element operated

OCN1-ARC-BLOCK 8200011B62 Autoreclose block signal by OCN1 protection

OCN1-OPT 8000011B60 OCN1 protection operated

OCN1-OPT-ALARM 8100011B61 Alarm signal by OCN1 protection

OCN1-OPT-TRIP 8000011B23 Trip signal by OCN1 protection

OCN1PU 8000011C27 OCN1 relay operation level pick up

OCN1_BLOCK 8000011BB0 OCN1 protection block command

OCN1_INST_OP 8000011BB1 OCN1 protection instant operation command

OCN2 8100021C23 OCN2 relay element operated

OCN2-ARC-BLOCK 8200021B62 Autoreclose block signal by OCN2 protection

OCN2-OPT 8100021B60 OCN2 protection operated

OCN2-OPT-ALARM 8100021B61 Alarm signal by OCN2 protection

OCN2-OPT-TRIP 8000021B23 Trip signal by OCN2 protection

OCN2PU 8100021C27 OCN2 relay operation level pick up

OCN2_BLOCK 8100021BB0 OCN2 protection block command

OCN2_INST_OP 8100021BB1 OCN2 protection instant operation command

OCN3 8200031C23 OCN3 relay element operated

OCN3-ARC-BLOCK 8200031B62 Autoreclose block signal by OCN3 protection

OCN3-OPT 8200031B60 OCN3 protection operated

OCN3-OPT-ALARM 8100031B61 Alarm signal by OCN3 protection

OCN3-OPT-TRIP 8000031B23 Trip signal by OCN3 protection

OCN3PU 8200031C27 OCN3 relay operation level pick up

OCN3_BLOCK 8200031BB0 OCN3 protection block command

OCN3_INST_OP 8200031BB1 OCN3 protection instant operation command

OCN4 8300041C23 OCN4 relay element operated

OCN4-ARC-BLOCK 8200041B62 Autoreclose block signal by OCN4 protection

OCN4-OPT 8300041B60 OCN4 protection operated

OCN4-OPT-ALARM 8100041B61 Alarm signal by OCN4 protection

OCN4-OPT-TRIP 8000041B23 Trip signal by OCN4 protection

OCN4PU 8300041C27 OCN4 relay operation level pick up

OCN4_BLOCK 8300041BB0 OCN4 protection block command

OCN4_INST_OP 8300041BB1 OCN4 protection instant operation command

 Connection point on PLC logic


OCN(Function ID: 443001)
Element ID Name Description
800001EBB0 OCN1_BLOCK OCN1 protection block command

800001EBB1 OCN1_INST_OP OCN1 protection instant operation command

810002EBB0 OCN2_BLOCK OCN2 protection block command

810002EBB1 OCN2_INST_OP OCN2 protection instant operation command

GRL200 (Soft 033 & 037)


- 272 -
6F2S1914 (0.37)

 Connection point on PLC logic


OCN(Function ID: 443001)
Element ID Name Description
820003EBB0 OCN3_BLOCK OCN3 protection block command

820003EBB1 OCN3_INST_OP OCN3 protection instant operation command

830004EBB0 OCN4_BLOCK OCN4 protection block command

830004EBB1 OCN4_INST_OP OCN4 protection instant operation command

GRL200 (Soft 033 & 037)


- 273 -
6F2S1914 (0.37)

Thermal overload function (THM)


Apparatus such as cables, transformers, generators and others can become overheated when
overloaded beyond their respective design limits due to excessive demands being placed on the
system. The thermal overload function (THM) works by determining the temperature rise in
an item of primary equipment by monitoring the current in order to detect the thermal
overload of the apparatus.

THM has an exponential characteristics in accordance with the IEC 60255-149 standard.
THM determines both the I2R loss and the cooling effect of the coolant simultaneously; THM
also determines the pre-load condition and signals a trip signal when an overload condition
arises.

THM issues a trip signal in accordance with an alarm stage that reflects the temperature
of the thermal overload condition. The alarm stage is configured using a setting; hence, the
user should determine the appropriate setting so that a trip signal can be issued before the
apparatus is overheated

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have thermal overload features. To determine whether the
features are implemented in the IED or not, locate the IED ordering number; and check the
order number at “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 2.18-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
THM Thermal overload protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 274 -
6F2S1914 (0.37)

2.18.1 Thermal state determination


THM simulates the change of thermal state using an algorithm; THM can detect an overload
condition. Thermal state (θ) is determined with the following equation:
𝐼2 −𝑡⁄
θ= 2 (1 − 𝑒 τ ) × 100 (%) (2.18-1)
𝐼𝐴𝑂𝐿
where I is the load current applied; IAOL is the allowable overload current;  is the thermal time
constant. The value of  is set using setting [TTHM].

Thermal state 0% is the cold state, whereas 100% reflects the thermal limit—which is
the point at which no further temperature rise can be tolerated safely and the system should
be disconnected. The thermal limit for any given system is subject to setting [THM], which
determines the value of overload current. The THM signals a trip when the value of θ is at
100%.

THM determines I using the positive-sequence current (I1) and negative-sequence


current (I2) using Equation (2.18-2); and operates according to the characteristics defined in
IEC 60255-149† when the user has set scheme switch [THM-Itype] Equivalent.

𝐼 = √𝐼12 + 𝑞 × 𝐼22 (2.18-2)

where,
q: Unbalance factor; the unbalance factor is used for motor/generator protection; the
user should set q=0 when setting [THM-q] except when it is applied to
motor/generator protection.

†Note:If the user prefers to use the thermal characteristic for the THM function specified
in IEC 60255-8, set Max phase for the scheme switch [THM-Itype]. In this case,
THM is determined using the largest of the three-phase currents.

The period of time for a trip to occur depends not only on the degree of overload, but also
on the degree of load current as far as reaching the overload state. The period of the trip, that
is, depends on whether the overload is applied from ‘cold’ or ‘hot’. THM has thresholds for
alarm and trip; hence, the two thresholds exist independently.

GRL200 (Soft 033 & 037)


- 275 -
6F2S1914 (0.37)

2.18.2 Thermal characteristic


THM characteristics are determined with two equations. Equation (2.18-3) is used to define
the cold state. Equation (2.18-4) is used to define the hot state:
𝐼2
t = τ ∙ Ln [ 2 ] (2.18-3)
𝐼 2 − 𝐼𝐴𝑂𝐿
𝐼 2 − 𝐼𝑃2
t = τ ∙ Ln [ 2 ] (2.18-4)
𝐼 2 − 𝐼𝐴𝑂𝐿
where t is time to trip for a constant overload current of I (minutes), I is the overload current
(largest phase current in amperes), IAOL is the permitted overload current (amperes), Ip is the
pre-load current (amperes), τ is the thermal time constant (minutes), and Ln is the natural
logarithm.

In Equation (2.18-3), cold curves are special versions of the hot curves where Ip is zero,
catering for the situation where a cold system is switched onto an immediate overload.

Figure 2.18-1.a shows the cold state where an overload has been switched onto a
previously un-loaded system. Figure 2.18-1.b shows the hot state where an overload is switched
onto a system that has previously been loaded to 90% of its capacity. The figures are in
conformity with the IEC 60255-149 curves, and these curves are drawn in a range of settings
of the time constant ().

a.Thermal Curves (Cold Curve - no prior load) b. Thermal Curves (Hot Curve - 90% prior load))


100
50
20
10
5

Figure 2.18-1 Thermal curves

GRL200 (Soft 033 & 037)


- 276 -
6F2S1914 (0.37)

2.18.3 Scheme logic


Figure 2.18-2 shows the scheme logic for THM. THM has two thresholds; threshold “A” is used
for alarming, threshold “T” for tripping. The name of the output signal for the alarm is termed
THM-OPT-ALARM and that of the output signal for tripping is termed “THM-OPT-TRIP”.

The threshold level for the alarm is set using setting [THM-Alarm] as a percentage of the
tripping threshold. The alarm signal is disabled when Off is set for scheme switch [THMA-EN].
The trip signal is prevented when Off is set for scheme switch [THMT-EN]. PLC signals
THMA_BLOCK and THMT_BLOCK are used to block the operation of THM.

8000011C23 8000011B60 8300021B23 To TRC

≥1 THM-OPT-TRIP
A 8100021C23 & & 8100021B60
THM 8400011B23
B THM-OPT-ALARM
&
& &

THMA-EN ON
& THM-ARC-BLOCK

THMT-EN ON

800001EBB0 THMA_BLOCK 1

810002EBB0 THMT_BLOCK 1

Trip
THMA-UseFor
Alarm

Figure 2.18-2 THM Logic

When wishing to have a test about pre-load current (Ip), the user should set a test value for
the setting [THM-IP] followed by setting [THM-Test]=On.

GRL200 (Soft 033 & 037)


- 277 -
6F2S1914 (0.37)

2.18.4 Setting
THM (Function ID: 451001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
THM-EN Off / On - Thermal protection scheme switch Off
0.40 - 2.00 -
THM A Thermal overload current 1.00 5.00
2.00 10.00
TTHM 0.5 - 500.0 min Thermal time constant 10.0
Type Max phase/
THM-Itype - Selection of THM equations Equivalent
Equivalent
THM-q 0 - 10 - Factor when Equivalent selected 0
SW THMT-EN Off / On - Thermal protection Off
THM-UseFor Trip / Alarm - THM used for trip or alarm Trip
ALM THMA-EN Off / On - Thermal alarm switch Off

THM-Alarm 50 - 100 % Thermal alarm level multiplier 80

Test tool(Function ID: 451001)


Range Default
Items Unit Contents Note
1A rating 5A rating 1A 5A
Function test THM-Test Off / On - Thermal protection scheme switch Off
0.00 - 0.00 -
THM-IP A Thermal overload current 0.00 0.00
1.00 5.00

GRL200 (Soft 033 & 037)


- 278 -
6F2S1914 (0.37)

2.18.5 Data ID
 Signal monitoring point
THM(Function ID: 451001)
Element ID Name Description
8000011C23 THM-A THM relay element operated (Alarm)

8000011B60 THM-ALARM THM protection Alarm signal

8400011B23 THM-OPT-ALARM THM protection operated (Alarm)

8300021B23 THM-OPT-TRIP THM protection operated (Trip)

8100021C23 THM-T THM relay element operated (Trip)

8100021B60 THM-TRIP THM protection Trip signal

8000011BB0 THMA_BLOCK THM protection for Alarm block command

8100021BB0 THMT_BLOCK THM protection for Trip block command

 Connection point on PLC logic


THM(Function ID: 451001)
Element ID Name Description
800001EBB0 THMA_BLOCK THM protection for Alarm block command

810002EBB0 THMT_BLOCK THM protection for Trip block command

GRL200 (Soft 033 & 037)


- 279 -
6F2S1914 (0.37)

Broken conductor protection (BCD)


A series fault or an open circuit fault can be caused by circuit breaker contact failure, the
operation of fuses, and false operation of single-phase switchgear. IEC60050 defines a series
fault as having impedances in each of three-phases that are not equal; hence, the series fault
is typified by the interruption of one or two phases, as a rule. The function of broken conductor
protection (BCD) is to detect series faults and signal a trip signal to the trip circuit.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have broken conductor protection feature. To determine
whether the features are implemented in the IED or not, locate the IED ordering number; and
check the order number at “G&T position” referring to the comparison table below. For more
information, see Appendix: Ordering.
Table 2.19-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
BCD Broken conductor protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 280 -
6F2S1914 (0.37)

2.19.1 Equivalent circuit for a one-phase series fault


Figure 2.19-1 shows the sequence diagram of the network connection when a single-phase
series fault occurs. We can represent the series fault by the positive sequence, negative
sequence and zero sequence impedances; the impedances are distributed to the left and right
as shown in the diagram of the primary circuit below. The ratio of the left to the right is
determined by the fault location such as k1:1-k1, k2:1-k2, and k0:1-k0.

E1A Series or open circuit fault E1B

k1 1– k1
I1F I1F
k1Z1 (1-k1)Z1

E1A
E1B

Positive sequence k2Z2 I2F I2F (1-k2)Z2

Negative sequence k0Z0 I0F I0F


(1-k0)Z0

Zero sequence

I1F
k1Z1 k2Z2 (1-k2)Z2 (1-k1)Z1

K0Z0 (1-k0)Z0
E1A E1B

I1F Z2
Z1

E1A Z0 E1B

Figure 2.19-1 Equivalent circuit for a single-phase fault

The series fault results in positive sequence current (I1F), negative sequence current (I2F)
and zero phase sequence current (I0F) in the single-phase. These are given by
𝐼1𝐹 + 𝐼2𝐹 + 𝐼0𝐹 = 0 (2.19-1)
𝑍2𝐹 𝐼2𝐹 ∙ 𝑍0𝐹 𝐼0𝐹 = 0 (2.19-2)
𝐸1𝐴 ∙ 𝐸1𝐵 = 𝑍1𝐹 𝐼1𝐹 ∙ 𝑍2𝐹 𝐼2𝐹 (2.19-3)
where,
E1A, E1B: power source voltage
Z1: positive sequence impedance
Z2: negative sequence impedance
Z0: zero sequence impedance

GRL200 (Soft 033 & 037)


- 281 -
6F2S1914 (0.37)

From Equation (2.19-1), (2.19-2), and (2.19-3), the following equations are derived:
𝑍2 + 𝑍0
𝐼1𝐹 = (𝐸 − 𝐸1𝐵 ) (2.19-4)
𝑍1 𝑍2 + 𝑍1 𝑍0 + 𝑍2 𝑍0 1𝐴
−𝑍0
𝐼2𝐹 = (𝐸 − 𝐸1𝐵 ) (2.19-5)
𝑍1 𝑍2 + 𝑍1 𝑍0 + 𝑍2 𝑍0 1𝐴
−𝑍2
𝐼0𝐹 = (𝐸 − 𝐸1𝐵 ) (2.19-6)
𝑍1 𝑍2 + 𝑍1 𝑍0 + 𝑍2 𝑍0 1𝐴

The magnitude of the fault current depends on the impedance across the system, the
difference in phase angle, and the magnitude between the power source voltages behind both
ends.

As noted earlier, the BCD element detects the presence of a fault by measuring the ratio
between the negative sequence current and the positive sequence current (I2F/I1F). The ratio is
obtained from the negative sequence impedance (Z2) and the zero sequence impedance (Z0);
hence, the equation of the ratio is expressed as follows:
𝐼2𝐹 |𝐼2𝐹 | 𝑍0
= = (2.19-7)
𝐼1𝐹 |𝐼1𝐹 | 𝑍2 + 𝑍0

A ratio value of 0.5 or higher is obtained when the zero sequence impedance is larger
than the negative sequence impedance. The ratio, thus, is close to 1.0 if the system is high-
impedance earthed or a single-end earthed system.

GRL200 (Soft 033 & 037)


- 282 -
6F2S1914 (0.37)

2.19.2 Characteristic and setting


The hatched area of Figure 2.19-2 illustrates the BCD characteristic; the BCD function will
operate when the positive sequence current (I1) is larger than 0.04×In, the negative sequence
current (I2) is larger than 0.01×In, and the ratio |I2/I1| is higher than setting [BCD].

I2

|𝐼2 |
൘|𝐼 | ≥ 𝐵𝐶𝐷 𝑠𝑒𝑡𝑡𝑖𝑛𝑔
1

BCD
|𝐼1 | ≥ 0.04 × 𝐼𝑛 &

|𝐼2 | ≥ 0.01 × 𝐼𝑛
0.01×In

o I1
0.04×In

Figure 2.19-2 Characteristic of BCD

2.19.3 Miscellaneous functions


(i) Harmonic detection function
The operation of BCD can be blocked when the IED detects 2nd harmonic caused by the
phenomenon of magnetizing inrush current when a transformer is energized. To block the
operation of the BCD function during the occurrence of the harmonic, set scheme switch [BCD-
2fBlk] Block.

(ii) Block operation of CTF for BCD


The operation of the BCD function can be blocked by the current transformer failure (CTF)
function using a scheme switch. Block is set for scheme switch [BCD-CTFBlk] if the user wishes
to disable the operation of the BCD function when a current transformer failure occurs.

GRL200 (Soft 033 & 037)


- 283 -
6F2S1914 (0.37)

2.19.4 Scheme logic


Figure 2.19-3 shows the scheme logic for the BCD function. The BCD function issues a trip
signal through a delayed pick-up timer, the value of which is set for [TBCD]. The operation of
the BCD function can be disabled using scheme switch [BCD-EN] Off.
8000001C23
From ICD
BCD
& &
ICD-OR 1
To Recording
BCD-2PBlk & TBCD
+ & t 0 8000001B60
BCD-OPT
BCDEN 0.00 - 300.00s
+
From CTF
On
CTF_DETECT
&
BCD-CTFBlk To TRC
≥1 1 8300001B23
+
Block & BCD-OPT-TRIP

800000EBB0 BCD_BLOCK Trip 8400001B62


BCD-UseFor BCD-OPT-ALARM
Alarm &
+
BCD-ARC-BLOCK

Figure 2.19-3 Broken conductor protection scheme logic

Normal power system levels of negative phase sequence restrict the setting value of
[BCD]. The BCD function continuously determines the ratio (I2F/I1F). User can check the
present ratio along with the maximum value (I21 max) that has been examined for 15 minutes
ago. We recommend that user should distinguish the present ratio against the value on
commissioning stage; and user should set a value for [BCD] from 130% to 150% of the ratio has
been checked.
Note: The ratio (I2F/ I1F) is displayed only when the current in positive-sequence (or load
current) on the secondary circuit is larger than 2% of the rated current on
secondary circuit.

2.19.5 Setting
Setting of BCD(Function ID: 452001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
BCD-EN Off / On - BCD protection scheme switch Off
BCD BCD 0.10 - 1.00 - BCD relay operating value (I2/I1) 0.20
TBCD 0.00 - 300.00 s BCD operating delay time 1.00
Output BCD-2fBlk Non / Block - BCD operation block by 2f-detection Non
BCD-CTFBlk Non / Block - BCD operation block by CTF Non
BCD-UseFor Trip / Alarm - BCD used for trip or alarm Trip

GRL200 (Soft 033 & 037)


- 284 -
6F2S1914 (0.37)

2.19.6 Data ID

 Signal monitoring point


BCD(Function ID: 452001)
Element ID Name Description
8000001C23 BCD BCD relay element operated

8000001B60 BCD-OPT BCD protection operated

8000001BB0 BCD_BLOCK BCD protection block command

8300001B23 BCD-OPT-TRIP Trip signal by BCD1 protection operation

8400001B62 BCD-OPT-ALARM Alarm signal by BCD1 protection operation

 Connection point on PLC logic


BCD(Function ID: 452001)
Element ID Name Description
800000EBB0 BCD_BLOCK BCD1 protection block command

GRL200 (Soft 033 & 037)


- 285 -
6F2S1914 (0.37)

Circuit breaker fail protection (CBF)


When a circuit breaker (CB) fails to remove a fault as a consequence of the CB failing to open,
the function of circuit breaker fail protection (CBF) is to remove the fault by the back-tripping
of other CBs. For example, if a fault current continues to flow following the issue of a trip
signal, the CBF function determines that a CB failure has occurred and issues another trip
signal to the adjacent CB(s) and/or the upstream CB.

Although a trip signal will have been issued by other protection functions, CBF protection
has relay elements and timers that are used to detect the continuing presence of a fault
following the issuance of a trip signal. The relay elements are termed OCCBF† and EFCBF†,
which run as protection functions within CBF.

†Note:The CBF function consists of two stages and their stages are operated
independently. Thus, the settings/switches/logics for two stages are provided
separately. To simply the description, only settings/switches/logics for the stage 1
are discussed as a representative, but the ones for the stage 2 are applicable in the
CBF function; hence the user can read the expression for the stage 1 as for the
stage 2 unless a special explanation or instructions has been provided.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have circuit breaker failure protection features. To
determine whether the features are implemented in the IED or not, locate the IED ordering
number; and check the order number at “G&T position” referring to the comparison table below.
For more information, see Appendix: Ordering.
Table 2.20-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
CBF Circuit breaker failure protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 286 -
6F2S1914 (0.37)

2.20.1 CBF operation and its elements


The operation of CBF is initiated by the operation of OCCBF and EFCBF, which monitors fault
current after the issuance of a trip signal by other protection functions. OCCBF or EFCBF
monitor the fault current so that the CBF feature can determine the failure of the CB to operate.
For CBF, the respective phase currents in three-phase system are monitored by the OCCBF-
A, OCCBF-B and OCCBF-C elements, while the zero-sequence current is monitored by the
EFCBF element.

The operation of these elements is reset if the threshold values of currents, applied by
the setting of [OCCBF1] and [EFCBF1], are below 80% of their setting value.

2.20.2 Re-trip feature


Once a CB failure occurs, the CBF protection would normally issue a back-trip signal to the
adjacent CB(s) and/or the upstream CB. However, the CBF protection is able to issue a further
trip signal to the faulted CB before issuing the back-trip signal. The second trip signal is
termed “re-trip”; “re-trip,” confirms the occurrence of a CB failure. In the event of an erroneous
CBF operation, the use of “re-trip” has the advantage of avoiding the issue of the back-trip
signal to the adjacent CB(s) or the upstream CB. The timing chart for “re-trip” and back-trip
are discussed later. (See Figure 2.20-1)

There are two operation modes (internal and external mode) for “re-trip”; the user can
select the desired mode using scheme switch [CBF1-Retrip]:
 Internal mode
If On is set for scheme switch [CBF1-Retrip] the CBF function is armed for issuing a
“re-trip” command. OCCBF and EFCBF control the “re-trip” signal along with trip
signals coming from other functions.

 External mode
When On-T is set for scheme switch [CBF1-Retrip], the CBF function is armed
forissuing a “re-trip” following tripping by external protection functions only. The
external protection functions can operate using PLC connection points in the TRC
function. If external mode is selected, an external CBF start signal must be present
continuously for as long as the fault is present.

For the re-trip operation, On should be set for both scheme switches [OCCBF1] and
[EFCBF1]. When a delay timer is needed for “re-trip”, a setting [TCBF1-RE] is available. A
setting time can be chosen between 0 and 300.000sec, the time setting to be applied must be
determined in accordance with the response time of the CB. The setting time is addressed later.
(section 2.20.5)

GRL200 (Soft 033 & 037)


- 287 -
6F2S1914 (0.37)

One of the benefits of the “re-trip” function is that it can used to avoid accidental tripping
of an adjacent CB or an upstream CB. This is particularly requisite during maintenance and
testing of the system.

Retrip
2.20.3 Backup feature Normal trip

As cited above, “re-trip” issues


Fault a further trip signal so that the CB receives an instruction to

trip again. If “re-trip” cannot remove the fault, CBF will issue a “back-trip” command. Back-
tripping is used as a last resort to remove the fault.

Fault occurence CBF Start Back-trip adjacent CB(s)

Adjacent CB(s) Closed


Open

On
Trip signal
Off Trip signal Trip signal Off
Normal trip Re-trip

Target CB Closed
Toc Tcb
Run
OCCBF element Stop Toc Toc Stop
Timer#1
Start TCBF-RE
Timer#1 (TCBF-RE) Off
On
Operation of Re-trip Off Off
Timer#2
Start TCBF-TP
Timer#2 (TCBF-TP) Off

On
CBF trip signal Off Off

Figure 2.20-1 Timing chart for re-trip and back trip during CBF operation

Figure 2.20-1 is a sequence diagram for the CBF function; the overall sequence illustrated
shows a target CB failing to remove a fault with the consequence that back tripping of the
adjacent CB(s) is required following operation of the CBF protection to finally clear the fault.
The CBF function is initiated via a signal from other protection functions.

If the target CB is tripped normally on receipt of a trip signal so that the fault is removed,
both OCCBF and EFCBF will reset before the time settings of timer #1 and timer #2 have
elapsed.

Following the issue of the first trip signal, if either OCCBF or EFCBF were to continue
to operate and if timer #1 were to time out according to the timer setting value [TCBF1-RE], a
“re-trip” command would be issued to the target CB. If the target CB were to open to clear the

GRL200 (Soft 033 & 037)


- 288 -
6F2S1914 (0.37)

fault in response to the “re-trip” command, OCCBF and EFCBF would reset and the CBF
sequence is stopped.

If the target CB were to fail to remove the fault with the “re-trip” command, and if
OCCBF or EFCBF continued to operate and if the timer #2 were to time out in accordance with
the setting time applied [TCBF1-TP], CBF will issue a trip signal to the adjacent CB(s) to clear
the fault, as a last resort.

GRL200 (Soft 033 & 037)


- 289 -
6F2S1914 (0.37)

2.20.4 Scheme logic


CBF function can issue a trip signal in each phase. The trip signal will be generated where
OCCBF1 or EFCBF1 element is being operated and signals ‘GEN.TRIP-*’† are generated
constantly. In other words, the circuit breaker has not been opened successfully with the
GEN.TRIP-* so that the fault has not been cleared yet; therefore, CBF trip command is
required separately.

†Note:The IED issues GEN.TRIP signals in trip circuit function (TRC), which is
discussed in Chapter Relay application: Trip circuit.

When wishing to issue the CBF trip command without the GEN.TRIP-* commands, the
IED can issue it with external signals come from other relay devices. The user should inject
the external signals at PLC connection points ‘EXT.CBF1_START*’.

On the other hand, when wishing to issue the CBF trip command without the operation
of OCCBF1 or EFCBF1 element, the IED can also issue it with external signals using PLC
connection points ‘SUB.CBF1*’. This technique will be achieved when the user programs to
inject a ‘CB close (closed) state signal’ at the ‘SUB.CBF1*’ points. It is useful if the CBF
function cannot determine the conditions of breaker failures, when OCCBF1 or EFCBF1
element fails to detect small fault currents.
CBF1_START-A
CBF1_START-B
CBF1_START-C
8000011C20
TCBF1-RE
OCCBF1 A t 0
& CBF1_RETRIP-A
≥1 &
8100011C21 & ≥1 ≥1 ○
1
B
& ≥1 t 0 CBF1_RETRIP-B
&
8200011C22 & ≥1 ≥1
C
& t 0
≥1 & CBF1_RETRIP-C
& ≥1 ≥1
OCCBF-EN ON 0.000-300.000s

8400011C27
EFCBF1 & ≥1 CBF1_RETRIP
&
EFCBF-EN &
ON
To TRC
8000001BB8 & 8000011B20
800000EBB8 SUB.CBF1-A ≥1 CBF1_RETRIP-A
8100001BB9 8100011B21
810000EBB9 SUB.CBF1-B ≥1 CBF1_RETRIP-B
8200001BBA 8200011B22
820000EBBA SUB.CBF1-C ≥1 CBF1_RETRIP-C
8300001BBB 8300011B23
830000EBBB SUB.CBF1 CBF1_RETRIP

From
TRC GEN.TRIP-A &
≥1
TRC
GEN.TRIP-B
≥1 &
GEN.TRIP-C
≥1 &
8000011BB0 OFF
800001EBB0 EXT.CBF1_START-A ON &
CBF1-Retrip
8100011BB1 ON-T
810001EBB1 EXT.CBF1_START-B &
8200011BB2 CBF-EN ON CBF-EN-ON
820001EBB2 EXT.CBF1_START-C
8300011BB3
830001EBB3 EXT.CBF1_START

800001EBB4 CBF1 _BLOCK ≥1 CBF1-NON_BLOCK

810001EBB5 CBF1-RE_INST

Figure 2.20-2 Elements logic in CBF1

GRL200 (Soft 033 & 037)


- 290 -
6F2S1914 (0.37)

TCBF1-TP
8800011B24
CBF1_START-A t 0
CBF1_TRIP-A
& ≥1 ≥1
t 0 8900011B25
CBF1_START-B CBF1_TRIP-B
& ≥1 ≥1
t 0 8A00011B26
CBF1_START-C CBF1_TRIP-C
& ≥1 ≥1
0.000-300.000s 8B00011B27

1
CBF1_TRIP
CBF1-RETRIP-A ≥1
& &
CBF1-RETRIP-B
& &
CBF1-RETRIP-C
& & To TRC

≥1 CBF1_ARC-BLOCK
CBF1-RETRIP

OFF
ON &
CBF1-Trip ON-AftRe
&

CBF-EN-ON

CBF1-NON_BLOCK

820001EBB6 CBF1-TP_INST

Figure 2.20-3 CBF1 logics (continued from Figure 2.20-2)

Figure 2.20-2 illustrates that CBF trip signals (CBF1-RETRIP) will be issued when
OCCBF1 or EFCBF1 element operates continuously until expiration of timer settings [TCBF1-
RE] and [TCBF1-TP]. Setting [TCBF1-RE] is overridden when On-AftRe is set for scheme
switch [CBF1-TRIP]. When On is set for scheme switch [CBF1-TRIP], timer setting [TCBF1-
RE] is bypassed; [TCBF1-TP] is applied for backup CBF trip.

GRL200 (Soft 033 & 037)


- 291 -
6F2S1914 (0.37)

2.20.5 Operation timing


The OCCBF and EFCBF elements can check that the target CB has opened normally and that
the fault current has disappeared completely. Because load current is usually present, the
OCCBF and EFCBF settings should be account for between 10% and 200% of the rated current.

The time settings [TCBF1-RE] and [TCBF1-TP] are determined in relation to the opening
time of the target CB and the reset time of the OCCBF or EFCBF elements (see Toc and Tcb
in Figure 2.20-1). The following description illustrates a setting calculation example when “re-
trip” is used:

Setting of TCBF-RE =Breaker opening time + OCCBF/EFCBF reset time + Margin


=40ms + 10ms + 20ms
=70ms

Setting of TCBF-TP =TCBF-RE + Output relay operating time + Breaker opening time +
OCCBF/EFCBF reset time + Margin
=70ms + 10ms + 40ms + 10ms + 10ms
=140ms

GRL200 (Soft 033 & 037)


- 292 -
6F2S1914 (0.37)

2.20.6 Setting
CBF(Function ID: 453001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
CBF-EN Off / On - CBF protection scheme switch Off
OC OCCBF-EN Off / On - Current flow is judged by OC relay operation On
0.10 - 0.50 - OCCBF1 relay operating level (Current flow
OCCBF1 A 1.00 5.00
5.00 25.00 judgment)
0.10 - 0.50 - OCCBF2 relay operating level (Current flow
OCCBF2 A 1.00 5.00
5.00 25.00 judgment)
EF EFCBF-EN Off / On - Current flow is judged by EF relay operation Off
0.10 - 0.50 - EFCBF1 relay operating level (Current flow
EFCBF1 A 1.00 5.00
5.00 25.00 judgment)
0.10 - 0.50 - EFCBF2 relay operating level (Current flow
EFCBF2 A 1.00 5.00
5.00 25.00 judgment)
Timer TCBF1-RE 0.000 - 300.000 s CBF1 retrip timer 0.150
TCBF1-TP 0.000 - 300.000 s CBF1 trip timer 0.200
TCBF2-RE 0.000 - 300.000 s CBF2 retrip timer 0.150
TCBF2-TP 0.000 - 300.000 s CBF2 trip timer 0.200
Output CBF1-Retrip Off / On / On-T - CBF1 retrip operation mode On
CBF1-Trip Off / On / On-AftRe - CBF1 trip operation mode On
CBF2-Retrip Off / On / On-T - CBF2 retrip operation mode On
CBF2-Trip Off / On / On-AftRe - CBF2 trip operation mode On

GRL200 (Soft 033 & 037)


- 293 -
6F2S1914 (0.37)

2.20.7 Data ID
 Signal monitoring points
CBF(Function ID: 453001)
Element ID Name Description
8000011C20 OCCBF1-A OCCBF1 relay element operated (phase-A)

8100011C21 OCCBF1-B OCCBF1 relay element operated (phase-B)

8200011C22 OCCBF1-C OCCBF1 relay element operated (phase-C)

8400011C27 EFCBF1 EFCBF1 relay element operated

8000011B20 CBF1_RETRIP-A OCCBF1 Retrip (phase-A)

8100011B21 CBF1_RETRIP-B OCCBF1 Retrip (phase-B)

8200011B22 CBF1_RETRIP-C OCCBF1 Retrip (phase-C)

8300011B23 CBF1_RETRIP OCCBF1 Retrip

8800011B24 CBF1_TRIP-A OCCBF1 trip (phase-A)

8900011B25 CBF1_TRIP-B OCCBF1 trip (phase-B)

8A00011B26 CBF1_TRIP-C OCCBF1 trip (phase-C)

8B00011B27 CBF1_TRIP OCCBF1 trip

8000011BB0 EXT.CBF1_START-A External CBF1 start(phase-A)

8100011BB1 EXT.CBF1_START-B External CBF1 start(phase-B)

8200011BB2 EXT.CBF1_START-C External CBF1 start(phase-C)

8300011BB3 EXT.CBF1_START External CBF1 start

8000021C20 OCCBF2-A OCCBF2 relay element operated (phase-A)

8100021C21 OCCBF2-B OCCBF2 relay element operated (phase-B)

8200021C22 OCCBF2-C OCCBF2 relay element operated (phase-C)

8400021C27 EFCBF2 EFCBF2 relay element operated

8000021B20 CBF2_RETRIP-A OCCBF2 Retrip (phase-A)

8100021B21 CBF2_RETRIP-B OCCBF2 Retrip (phase-B)

8200021B22 CBF2_RETRIP-C OCCBF2 Retrip (phase-C)

8300021B23 CBF2_RETRIP OCCBF2 Retrip

8800021B24 CBF2_TRIP-A OCCBF2 trip (phase-A)

8900021B25 CBF2_TRIP-B OCCBF2 trip (phase-B)

8A00021B26 CBF2_TRIP-C OCCBF2 trip (phase-C)

8B00021B27 CBF2_TRIP OCCBF2 trip

8000021BB0 EXT.CBF2_START-A External CBF2 start(phase-A)

8100021BB1 EXT.CBF2_START-B External CBF2 start(phase-B)

8200021BB2 EXT.CBF2_START-C External CBF2 start(phase-C)

8300021BB3 EXT.CBF2_START External CBF2 start

8000001BB8 SUB.CBF1-A CBF1 relay operated by an external signal additionally (in phase-A)

8100001BB9 SUB.CBF1-B CBF1 relay operated by an external signal additionally (in phase-B)

8200001BBA SUB.CBF1-C CBF1 relay operated by an external signal additionally (in phase-C)

8300001BBB SUB.CBF1 CBF1 relay operated by an external signal additionally (in three-phase)

8000001BBC SUB.CBF2-A CBF2 relay operated by an external signal additionally (in phase-A)

8100001BBD SUB.CBF2-B CBF2 relay operated by an external signal additionally (in phase-B)

8200001BBE SUB.CBF2-C CBF2 relay operated by an external signal additionally (in phase-C)

8300001BBF SUB.CBF2 CBF2 relay operated by an external signal additionally (in three-phase)

GRL200 (Soft 033 & 037)


- 294 -
6F2S1914 (0.37)

 Connection point in PLC logic


CBF(Function ID: 453001)
Element ID Name Description
800001EBB0 EXT.CBF1_START-A External CBF1 start(phase-A)

810001EBB1 EXT.CBF1_START-B External CBF1 start(phase-B)

820001EBB2 EXT.CBF1_START-C External CBF1 start(phase-C)

830001EBB3 EXT.CBF1_START External CBF1 start

800001EBB4 CBF1_BLOCK CBF1 protection block command

810001EBB5 CBF1-RE_INST CBF1 instantaneous retrip

820001EBB6 CBF1-TP_INST CBF1 instantaneous trip

800002EBB0 EXT.CBF2_START-A External CBF2 start(phase-A)

810002EBB1 EXT.CBF2_START-B External CBF2 start(phase-B)

820002EBB2 EXT.CBF2_START-C External CBF2 start(phase-C)

830002EBB3 EXT.CBF2_START External CBF2 start

800002EBB4 CBF2_BLOCK CBF2 protection block command

810002EBB5 CBF2-RE_INST CBF2 instantaneous retrip

820002EBB6 CBF2-TP_INST CBF2 instantaneous trip

800000EBB8 SUB.CBF1-A Additional external signal for CBF1 (phase-A)

810000EBB9 SUB.CBF1-B Additional external signal for CBF1 (phase-B)

820000EBBA SUB.CBF1-C Additional external signal for CBF1 (phase-C)

830000EBBB SUB.CBF1 Additional external signal for CBF1 (three phase combined)

800000EBBC SUB.CBF2-A Additional external signal for CBF2 (phase-A)

810000EBBD SUB.CBF2-B Additional external signal for CBF2 (phase-B)

820000EBBE SUB.CBF2-C Additional external signal for CBF2 (phase-C)

830000EBBF SUB.CBF2 Additional external signal for CBF2 (three phase combined)

GRL200 (Soft 033 & 037)


- 295 -
6F2S1914 (0.37)

Overvoltage protection for phase-to-neutral (OV)


The over voltage protection function for phase (OV) detects an over voltage condition that
phase-to-neutral voltage is larger than a setting and operates accordingly. The OV function
has two stages (elements; OV1 and OV2), which operate independently. The OV element has a
time delay characteristic; and the user can select either (1) independent (definite) time
characteristic delay or (2) dependent (inverse) time characteristic delay. The OV element is
configured both the setting of a pickup voltage (PU) and the setting of a drop-off voltage (DO).

To simplify the description, only OV1 is discussed, but the expression is applicable to the
OV2; hence, read the expression for OV1 as the OV2 unless a special explanation or instruction
has been provided.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have phase over-voltage protection features. To determine
whether the features are implemented in the IED or not, locate the IED ordering number; and
check the order number at “G&T position” referring to the comparison table below. For more
information, see Appendix: Ordering.
Table 2.21-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
OV Phase over-voltage protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 296 -
6F2S1914 (0.37)

2.21.1 Drop-off and pickup characteristic


Figure 2.21-1 shows the characteristic of the OV element. The outer circle shows the threshold
of pick-up threshold voltage (PU), whereas the inner dotted circle shows drop-off voltage point
(DO). The hatched area shows the operation area of the OV.

Pickup
V
Dropoff

0 V

Figure 2.21-1 Characteristic of OV element


For example, with regard to the OV1 element, suppose the user sets a pick-up value in
P.U for setting [OV1]. Then the user should set a drop-off value using setting [OV1-DPR], which
configures the ratio of the PU to the DO.

2.21.2 Delay for the operation of the OV element


The OV element has a delay timer for the operation. For the OV1 element, the user can set a
delay time using setting [TOV1]. The user can find the delay timer in the OV function logic.
(See section 2.21.5)

2.21.3 Time characteristic


The OV element has two characteristics between a voltage condition and an operation time;
hence, the user should select a mode either (i) definite (independent) time characteristic delay
or (ii) inverse (dependent) time characteristic delay. For the definite time characteristic delay,
the operation time is a constant. In the inverse time characteristic delay, the operation time
depends upon the level of the voltage condition.

(i) Definite time characteristic (DT)


To operate the definite (independent) time delay, set DT for scheme switch [OV1-Timer].
Resetting the OV element is performed when a voltage falls below the drop-off voltage.

(ii) Invers time characteristic (IDMT)


To operate the dependent (invers) time delay, set IDMT for scheme switch [OV1-Timer].

Pick-up characteristic
The operate time of the inverse (dependent) time characteristic is inversely proportional to the

GRL200 (Soft 033 & 037)


- 297 -
6F2S1914 (0.37)

level of the voltage condition. Figure 2.21-2 shows the invers time characteristic of the OV
element when a multiplier setting [OV1-TMS] is used. The OV element uses Equation (2.21-1)
to be in conformity to IEC 60255-127:

𝑘
t(G) = TMS × {[ 𝑎 ] + 𝑐} (2.21-1)
(𝑉⁄𝑉 ) − 1
𝑠

where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage), and
TMS = time multiplier setting to adjust a curve

If the user will require a user-programmable (original) curve in the inverse time
characteristic, it is provided when the constants of k, a, c are set, as shown in Table 2.21-2. For
example, the user-programmable (original) curve in the OV1 element will be acquired when
Original is set for the scheme switch [OV1-Timer], and when values of respective constants are
set for [OV1-k], [OV1-a], and [OV1-C].

Overvoltage Inverse Time Curves

1000.000

100.000
Operating Time (secs)

10.000

TMS = 10

TMS = 5

1.000
TMS = 2

TMS = 1

0.100
1 1.5 2 2.5 3
Applied Voltage (x Vs)

Figure 2.21-2 IDMT characteristic of OV element

GRL200 (Soft 033 & 037)


- 298 -
6F2S1914 (0.37)

Table 2.21-2 Constant value at each setting of IDMT curve


Set item k a C
IDMT 1 1 0
User-programmable 0.00000 – 500.00000 0.00000 – 10.00000 0.00000 – 10.00000
(Original) by 0.00001 step by 0.00001 step by 0.00001 step

Reset feature
The user should set the time for resetting. Figure 2.21-3 shows that examples of the pick-up
and the drop-off relevant to both the fault occurrences and the operation time. The value of the
time counter furnished in the OV1 element is incremented if faults occur.

As for an intermittent fault (the former in the figure), the time counter will not reach the
trip level. In the other words, the operation of the OV1 element is paralyzed in the reset time
set by [TOV1R].

If a series of fault occurs repeatedly (the latter in the figure), and if the value of the time
counter reaches at trip level, the OV1 element will issue a trip command after a certain delay.
After issuing the trip command, if a series of fault completely disappears after issuing the trip
command, the value of the time counter will be expired after the reset time [TOV1R].

When the user requires resetting the operation of the OV1 element immediately, setting
zero for the settings [TOV1R] is needed. Consequently, when a voltage falls below the reset
threshold (drop-off), the operation of the OV1 element is reset promptly.

GRL200 (Soft 033 & 037)


- 299 -
6F2S1914 (0.37)

Condition fault occurrence


Intermittent fault Series faults

T3

Fault observation by the relay

Issue of trip command

Relay operation reset


Incrimination of time counter
corresponding to the fault
duration. Trip level

Tripping

T1 T1 T1 T1

T2 T2
Increment process in time Reset of time counter
T1: Resetting time set by the user counter
T2: Actual resetting time in the relay operation Value maintenance of time counter
T3: Time gap between fault occurrence and relay start time

Figure 2.21-3 Faults occurrences and reset operation when IDMT being applied

2.21.4 Miscellaneous functions


(i) OV operation blocked by the occurrence of VT failure
Blocking the OV function may be required when a failure in the voltage transformer occurs. In
this case, the user shall set Block for scheme switch [OV1-VTFBlk]. Non (as a default) is set
for scheme switch [OV1-VTFBlk] in order that the OV function is not blocked by the failure.

(ii) OV trip signal


The OV function issues a trip command for the trip circuit (TRC†) when Trip is set for scheme
switch [OV1-UseFor] as the normal trip operation. However, when an alarm signal in place of
the trip command is required, the user can set Alarm for the scheme switch [OV1-UseFor].

†Note:For more information about the trip circuit, see Chapter Relay application: Trip
circuit.

(iii) Execution of OV function


Set On for scheme switch [OV1-EN]. Otherwise, set Off for the scheme switch [OV1-EN] if the
OV1 element is not required to operate.

2.21.5 Scheme logic


Figure 2.21-4 shows the OV1 logic. Signal connection points “OV1_BLOCK” are provided for
the block of the operation of the OV1 element. For testing, the OV1-PU element is provided; it

GRL200 (Soft 033 & 037)


- 300 -
6F2S1914 (0.37)

generates a pick-up signal when the entering voltage is excesses of the threshold anytime. For
example, in the IDMT characteristic, the user can measure the pickup time after the excess
using both PLC monitoring points “8000011C20” and “8000011C24”.
DT
IDMT
OV1-Timer Original ≥1

OV1-EN On
To Grouping logic
8000011C20 TOV1 8000011B62
A & &
t 0
8100011C21 & OV1-OPT-A
≥1 8100011B63
OV1 B & t 0
8200011C22 & & OV1-OPT-B
≥1
C 8200011B64
& & &
t 0
≥1 OV1-OPT-C
8000011B60
0.00 to 300.00s
≥1

8000011C24 8000011B65
A & OV1-OPT
8100011C25 ≥1
OV1 PU B &
8200011C26
8000011B23
C & OV1-OPT-TRIP
&
8100011B66
8000011B61 & OV1-OPT-ALARM
≥1

800001EBB0 OV1_BLOCK ≥1 1

OV1-VTFBlk Block
& Trip
From VTF OV1-UseFor
Alarm
VTF_DETECT

Figure 2.21-4 OV1 logic


From OV1 and OV2 logics To TRC
≥1 OV-OPT-TRIP
OV1-OPT-TRIP
OV2-OPT-TRIP

≥1
OV1-OPT-ALARM OV-OPT-ALARM
OV2-OPT- ALARM

≥1
OV1-ARC-BLOCK OV-ARC-BLOCK
OV2- ARC-BLOCK

OV1-OPT-AR ≥1 OV-OPT-AR

OV1-OPT-BR OV-OPT-BR

OV1-OPT-CR OV-OPT-CR

≥1
OV2-OPT-AR

OV2-OPT-BR

OV2-OPT-CR
≥1

To Recording

OV1-OPT OV1-OPT
OV2-OPT OV2-OPT

Figure 2.21-5 Grouping logic for TRC/Recording functions

GRL200 (Soft 033 & 037)


- 301 -
6F2S1914 (0.37)

2.21.6 Setting list


OV(Function ID: 460101)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OV1-EN Off / On - OV1 protection scheme switch Off
OV2-EN Off / On - OV2 protection scheme switch Off
OV1 OV1-Timer DT / IDMT / Original - OV1 delay type DT
DT OV1 1.0 - 220.0 V OV1 threshold 120.0
TOV1 0.00 - 300.00 s OV1 operating delay time (in DT mode) 1.00
OV1-DPR 10 - 100 % OV1 drop-out/pick-up ratio 100
IDMT OV1 1.0 - 220.0 V OV1 threshold 120.0
OV1-DPR 10 - 100 % OV1 drop-out/pick-up ratio 100
OV1-TMS 0.010 - 100.000 - OV1 time multiplier (in IDMT mode) 1.000
TOV1R 0.0 - 300.0 s OV1 definite time reset delay 0.0
ORG OV1 1.0 - 220.0 V OV1 threshold 120.0
OV1-DPR 10 - 100 % OV1 drop-out/pick-up ratio 100
OV1-TMS 0.010 - 100.000 - OV1 time multiplier (in ORG mode) 1.000
TOV1R 0.0 - 300.0 s OV1 definite time reset delay 0.0
OV1-k 0.00000 - 500.00000 - OV1 user original curve coefficient 0.00000
OV1-a 0.00000 - 10.00000 - OV1 user original curve coefficient 0.00000
OV1-c 0.00000 - 10.00000 - OV1 user original curve coefficient 0.00000
Output OV1-VTFBlk Non / Block - OV1 operation block by VTF Non
OV1-UseFor Trip / Alarm - OV1 used for trip or alarm Trip
OV2 OV2-Timer DT / IDMT / Original - OV2 delay type DT
DT OV2 1.0 - 220.0 V OV2 threshold 120.0
TOV2 0.00 - 300.00 s OV2 operating delay time (in DT mode) 1.00
OV2-DPR 10 - 100 % OV2 drop-out/pick-up ratio 100
IDMT OV2 1.0 - 220.0 V OV2 threshold 120.0
OV2-DPR 10 - 100 % OV2 drop-out/pick-up ratio 100
OV2-TMS 0.010 - 100.000 - OV2 time multiplier (in IDMT mode) 1.000
TOV2R 0.0 - 300.0 s OV2 definite time reset delay 0.0
ORG OV2 1.0 - 220.0 V OV2 threshold 120.0
OV2-DPR 10 - 100 % OV2 drop-out/pick-up ratio 100
OV2-TMS 0.010 - 100.000 - OV2 time multiplier (in ORG mode) 1.000
TOV2R 0.0 - 300.0 s OV2 definite time reset delay 0.0
OV2-k 0.00000 - 500.00000 - OV2 user original curve coefficient 0.00000
OV2-a 0.00000 - 10.00000 - OV2 user original curve coefficient 0.00000
OV2-c 0.00000 - 10.00000 - OV2 user original curve coefficient 0.00000
Output OV2-VTFBlk Non / Block - OV2 operation block by VTF Non
OV2-UseFor Trip / Alarm - OV2 used for trip or alarm Trip

GRL200 (Soft 033 & 037)


- 302 -
6F2S1914 (0.37)

2.21.7 Data ID
 Signal monitoring point
OV(Function ID: 460101)
Element ID Name Description
8800001B62 OV-OPT-A OV protection operated (phase-A)

8400001B61 OV-OPT-ALARM Alarm signal by OV protection

8900001B63 OV-OPT-B OV protection operated (phase-B)

8A00001B64 OV-OPT-C OV protection operated (phase-C)

8300001B23 OV-OPT-TRIP Trip signal by OV protection

8000011C20 OV1-A OV1 relay element operated (phase-A)

8100011C21 OV1-B OV1 relay element operated (phase-B)

8200011C22 OV1-C OV1 relay element operated (phase-C)

8000011B65 OV1-OPT OV1 protection operated

8000011B62 OV1-OPT-A OV1 protection operated (phase-A)

8100011B66 OV1-OPT-ALARM Alarm signal by OV1 protection

8100011B63 OV1-OPT-B OV1 protection operated (phase-B)

8200011B64 OV1-OPT-C OV1 protection operated (phase-C)

8000011B23 OV1-OPT-TRIP Trip signal by OV1 protection

8000011B60 OV1-OR OV1 relay element operated (3-phases OR)

8000011C24 OV1PU-A OV1 relay operation level pick up (phase-A)

8100011C25 OV1PU-B OV1 relay operation level pick up (phase-B)

8200011C26 OV1PU-C OV1 relay operation level pick up (phase-C)

8000011B61 OV1PU-OR OV1 relay operation level pick up (3-phases OR)

8000011BB0 OV1_BLOCK OV1 protection block command

8400021C20 OV2-A OV2 relay element operated (phase-A)

8500021C21 OV2-B OV2 relay element operated (phase-B)

8600021C22 OV2-C OV2 relay element operated (phase-C)

8100021B65 OV2-OPT OV2 protection operated

8400021B62 OV2-OPT-A OV2 protection operated (phase-A)

8100021B66 OV2-OPT-ALARM Alarm signal by OV2 protection

8500021B63 OV2-OPT-B OV2 protection operated (phase-B)

8600021B64 OV2-OPT-C OV2 protection operated (phase-C)

8000021B23 OV2-OPT-TRIP Trip signal by OV2 protection

8100021B60 OV2-OR OV2 relay element operated (3-phases OR)

8400021C24 OV2PU-A OV2 relay operation level pick up (phase-A)

8500021C25 OV2PU-B OV2 relay operation level pick up (phase-B)

8600021C26 OV2PU-C OV2 relay operation level pick up (phase-C)

8100021B61 OV2PU-OR OV2 relay operation level pick up (3-phases OR)

8100021BB0 OV2_BLOCK OV2 protection block command

 Connection point on PLC logic


OV(Function ID: 460101)
Element ID Name Description

800001EBB0 OV1_BLOCK OV1 protection block command

810002EBB0 OV2_BLOCK OV2 protection block command

GRL200 (Soft 033 & 037)


- 303 -
6F2S1914 (0.37)

Overvoltage protection for phase-to-phase (OVS)


The over voltage protection function in phase-to-phase (OVS) detects an over voltage condition
that phase-to-neutral voltage is larger than a setting and operates accordingly. The OVS
function has two stages (elements; OVS1 and OVS2), which operate independently. The OVS
element has a time delay characteristic; and the user can select either (1) independent
(definite) time characteristic delay or (2) dependent (inverse) time characteristic delay. The
OVS element is configured both the setting of a pickup voltage (PU) and the setting of a drop-
off voltage (DO).

To simplify the description, only OVS1 is discussed, but the expression is applicable to
OVS2; hence, read the expression for OVS1 as the OVS2 stage unless a special explanation or
instruction has been provided.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have phase-phase over-voltage protection features. To
determine whether the features are implemented in the IED or not, locate the IED ordering
number; and check the order number at “G&T position” referring to the comparison table below.
For more information, see Appendix: Ordering.
Table 2.22-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
OVS Phase-phase over-voltage protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 304 -
6F2S1914 (0.37)

2.22.1 Drop-off and pickup setting


Figure 2.22-1 shows the characteristic of the OVS element. The outer circle shows the
threshold of pick-up threshold voltage (PU), whereas the inner circle shows drop-off voltage
point (DO). The hatched area shows the operation area of the OVS.

Pickup
V
Dropoff

0 V

Figure 2.22-1 Characteristic of OVS element


For example, with regard to the OVS1 element, suppose the user sets a pick-up value in
P.U for setting [OVS1]. Then the user should set a drop-off value using setting [OVS1-DPR],
which configures the ratio of the PU to the DO.

2.22.2 Delay for the operation of the OVS element


The OVS element has a delay timer for the operation. For the OVS1 element, the user can set
a delay time using setting [TOVS1]. The user can find the delay timer in the OVS function
logic. (See section 2.22.5)

2.22.3 Time characteristic


The OVS element has two characteristics between a voltage condition and an operation time;
hence, the user should select a mode either (i) definite (independent) time characteristic delay
or (ii) inverse (dependent) time characteristic delay. For the definite time characteristic delay,
the operation time is a constant. In the inverse time characteristic delay, the operation time
depends upon the level of the voltage condition.
(i) Definite time characteristic (DT)
To operate the definite (independent) time delay, set DT for scheme switch [OVS1-Timer].
Resetting the OVS element is performed when a voltage falls below the drop-off voltage.

(ii) Invers time characteristic (IDMT)


To operate the dependent (invers) time delay, set IDMT for scheme switch [OVS1-Timer].
Operation feature
The operate time of the inverse (dependent) time characteristic is inversely proportional to the
level of the voltage condition. Figure 2.22-2 shows the invers time characteristic of the OVS
element when a multiplier setting is used. The OVS element uses Equation (2.22-1) to be in

GRL200 (Soft 033 & 037)


- 305 -
6F2S1914 (0.37)

conformity to IEC 60255-127:

𝑘
t(G) = TMS × {[ 𝑎 ] + 𝑐} (2.22-1)
(𝑉⁄𝑉 ) − 1
𝑠

where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage), and
TMS = time multiplier setting to adjust a curve

If the user will require a user-programmable (original) curve in the inverse time
characteristic, it is provided when the constants of k, a, c are set, as shown in Table 2.22-2. For
example, the user-programmable (original) curve in the OVS1 element will be acquired when
Original is set for the scheme switch [OVS1-Timer], and when values of respective constants
are set for [OVS1-k], [OVS1-a], and [OVS1-C].

Overvoltage Inverse Time Curves

1000.000

100.000
Operating Time (secs)

10.000

TMS = 10

TMS = 5

1.000
TMS = 2

TMS = 1

0.100
1 1.5 2 2.5 3
Applied Voltage (x Vs)

Figure 2.22-2 IDMT characteristic of OVS element


Table 2.22-2 Constant value at each setting of IDMT curve
Set item k a C
IDMT 1 1 0
User-programmable 0.00000 – 500.00000 0.00000 – 10.00000 0.00000 – 10.00000
(Original) by 0.00001 step by 0.00001 step by 0.00001 step

GRL200 (Soft 033 & 037)


- 306 -
6F2S1914 (0.37)

Reset feature
The user should set the time for resetting. Figure 2.22-3 shows that examples of the pick-up
and the drop-off relevant to both the fault occurrences and the operation time. The value of the
time counter furnished in the OVS1 element is incremented if faults occur.

As for an intermittent fault (the former in the figure), the time counter will not reach the
trip level. In the other words, the operation of the OVS1 element is paralyzed in the reset time
set by [TOVS1R].

If a series of fault occurs repeatedly (the latter in the figure), and if the value of the time
counter reaches at trip level, the OVS1 element will issue a trip command after a certain delay.
After issuing the trip command, if a series of fault completely disappears after issuing the trip
command, the value of the time counter will be expired after the reset time [TOVS1R].

When the user requires resetting the operation of the OVS1 element immediately, setting
zero for the settings [TOVS1R] is needed. Consequently, when a voltage falls below the reset
threshold (drop-off), the operation of the OVS1 element is reset promptly.
Intermittent fault
Condition fault occurrence Series faults
T3

Fault observation by the relay

Issue of trip command

Relay operation reset


Incrimination of time counter
corresponding to the fault
duration. Trip level

Tripping

T1 T1 T1 T1

T2 T2
T1: Resetting time set by the user Increment process in time Reset of time counter
T2: Actual resetting time in the relay operation counter
T3: Time gap between fault occurrence and relay start time Value maintenance of time counter

Figure 2.22-3 Faults occurrences and reset operation when IDMT being applied

2.22.4 Miscellaneous functions


(i) OVS operation blocked by the occurrence of VT failure
Blocking the OVS function may be required when a failure in the voltage transformer occurs.
In this case, the user shall set Block for scheme switch [OVS1-VTFBlk]. Non (as a default) is
set for scheme switch [OVS1-VTFBlk] in order that the OVS function is not blocked by the

GRL200 (Soft 033 & 037)


- 307 -
6F2S1914 (0.37)

failure.

(ii) Switch of OVS trip command


The OVS function issues a trip command for the trip circuit (TRC†) when Trip is set for scheme
switch [OVS1-UseFor] as the normal trip operation. However, when an alarm signal in place
of the trip command is required, the user can set Alarm for the scheme switch [OVS1-UseFor].
†Note:For more information, see Chapter Relay application: Trip circuit.

(iii) Execution of OVS function


Set On for scheme switch [OVS1-EN]. Otherwise, set Off for the scheme switch [OVS1-EN] if
the OVS1 element is not required to operate.

2.22.5 Scheme logic


Figure 2.22-4 shows the OVS function logic. Signal connection points “OVS1_BLOCK” are
provided for the block of the operation of the OVS elements. For testing, the OVS1-PU element
is provided; it generates a pick-up signal when the entering voltage is excesses of the threshold
anytime. For example, in the IDMT characteristic, using both monitoring points “8000011C20”
and “8000011C24” can facilitate to measure the pickup time after the excess.
8000011C20 TOVS1
8000011B62
AB & t 0 To TRC
8100011C21
& &
≥1 8100011B63 ≥1 OVS-OPT-AB
OVS1 BC & t 0
8200011C22 & &
≥1
8200011B64 ≥1 OVS-OPT-BC
CA & t 0
& & ≥1 ≥1 OVS-OPT-CA
≥1 8000011B60
0.00 to 300.00s

8000011B65
8000011C24 & OVS1-OPT
≥1
AB
8100011C25 & OVS2-OPT
OVS1 PU BC
8200011C26
& & OVS-OPT-TRIP
CA ≥1
& ≥1 OVS-OPT-ALARM
≥1 8000011B61

OVS-OPT-BLOCK

OVS1-EN On

Block
OVS1-VTFBlk & ≥1 1

800001EBB0 OVS1_BLOCK

DT
IDMT
Original ≥1
OVS1-Timer
Trip
Alarm
OVS1-UseFor

OVS2-OPT-AB
OVS2-EN On
OVS2-OPT-BC
Block & The logics of OVS2 and OVS2 PU are the same as the
OVS2-VTFBlk logics of OVS1 and OVS2 PU. OVS2-OPT-CA

810002EBB0 OVS2_BLOCK OVS2-OPT-TRIP

OVS2-OPT-ALAR
OVS2-Timer
M
OVS2-UseFor OVS2-OPT

From VTF

VTF_DETECT

Figure 2.22-4 OVS function logics

GRL200 (Soft 033 & 037)


- 308 -
6F2S1914 (0.37)

2.22.6 Setting list


OVS(Function ID: 461101)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OVS1-EN Off / On - OVS1 protection scheme switch Off
OVS2-EN Off / On - OVS2 protection scheme switch Off
OVS1 OVS1-Timer DT / IDMT / Original - OVS1 delay type DT
DT OVS1 1.0 - 220.0 V OVS1 threshold 120.0
TOVS1 0.00 - 300.00 s OVS1 operating delay time (in DT mode) 1.00
OVS1-DPR 10 - 100 % OVS1 drop-out/pick-up ratio 100
IDMT OVS1 1.0 - 220.0 V OVS1 threshold 120.0
OVS1-DPR 10 - 100 % OVS1 drop-out/pick-up ratio 100
OVS1-TMS 0.010 - 100.000 - OVS1 time multiplier (in IDMT mode) 1.000
TOVS1R 0.0 - 300.0 s OVS1 definite time reset delay 0.0
ORG OVS1 1.0 - 220.0 V OVS1 threshold 120.0
OVS1-DPR 10 - 100 % OVS1 drop-out/pick-up ratio 100
OVS1-TMS 0.010 - 100.000 - OVS1 time multiplier (in ORG mode) 1.000
TOVS1R 0.0 - 300.0 s OVS1 definite time reset delay 0.0
OVS1-k 0.00000 - 500.00000 - OVS1 user original curve coefficient 0.00000
OVS1-a 0.00000 - 10.00000 - OVS1 user original curve coefficient 0.00000
OVS1-c 0.00000 - 10.00000 - OVS1 user original curve coefficient 0.00000
Output OVS1-VTFBlk Non / Block - OVS1 operation block by VTF Non
OVS1-UseFor Trip / Alarm - OVS1 used for trip or alarm Trip
OVS2 OVS2-Timer DT / IDMT / Original - OVS2 delay type DT
DT OVS2 1.0 - 220.0 V OVS2 threshold 120.0
TOVS2 0.00 - 300.00 s OVS2 operating delay time (in DT mode) 1.00
OVS2-DPR 10 - 100 % OVS2 drop-out/pick-up ratio 100
IDMT OVS2 1.0 - 220.0 V OVS2 threshold 120.0
OVS2-DPR 10 - 100 % OVS2 drop-out/pick-up ratio 100
OVS2-TMS 0.010 - 100.000 - OVS2 time multiplier (in IDMT mode) 1.000
TOVS2R 0.0 - 300.0 s OVS2 definite time reset delay 0.0
ORG OVS2 1.0 - 220.0 V OVS2 threshold 120.0
OVS2-DPR 10 - 100 % OVS2 drop-out/pick-up ratio 100
OVS2-TMS 0.010 - 100.000 - OVS2 time multiplier (in ORG mode) 1.000
TOVS2R 0.0 - 300.0 s OVS2 definite time reset delay 0.0
OVS2-k 0.00000 - 500.00000 - OVS2 user original curve coefficient 0.00000
OVS2-a 0.00000 - 10.00000 - OVS2 user original curve coefficient 0.00000
OVS2-c 0.00000 - 10.00000 - OVS2 user original curve coefficient 0.00000
Output OVS2-VTFBlk Non / Block - OVS2 operation block by VTF Non
OVS2-UseFor Trip / Alarm - OVS2 used for trip or alarm Trip

GRL200 (Soft 033 & 037)


- 309 -
6F2S1914 (0.37)

2.22.7 Data ID
 Signal monitoring point
OVS(Function ID: 461101)
Element ID Name Description
8C00001B62 OVS-OPT-AB OVS protection operated (phase-AB)

8400001B61 OVS-OPT-ALARM Alarm signal by OVS protection

8D00001B63 OVS-OPT-BC OVS protection operated (phase-BC)

8E00001B64 OVS-OPT-CA OVS protection operated (phase-CA)

8300001B23 OVS-OPT-TRIP Trip signal by OVS protection

8000011C20 OVS1-AB OVS1 relay element operated (phase-AB)

8100011C21 OVS1-BC OVS1 relay element operated (phase-BC)

8200011C22 OVS1-CA OVS1 relay element operated (phase-CA)

8000011B65 OVS1-OPT OVS1 protection operated

8000011B62 OVS1-OPT-AB OVS1 protection operated (phase-AB)

8100011B66 OVS1-OPT-ALARM Alarm signal by OVS1 protection

8100011B63 OVS1-OPT-BC OVS1 protection operated (phase-BC)

8200011B64 OVS1-OPT-CA OVS1 protection operated (phase-CA)

8000011B23 OVS1-OPT-TRIP Trip signal by OVS1 protection

8000011B60 OVS1-OR OVS1 relay element operated (3-phases OR)

8000011C24 OVS1PU-AB OVS1 relay operation level pick up (phase-AB)

8100011C25 OVS1PU-BC OVS1 relay operation level pick up (phase-BC)

8200011C26 OVS1PU-CA OVS1 relay operation level pick up (phase-CA)

8000011B61 OVS1PU-OR OVS1 relay operation level pick up (3-phases OR)

8000011BB0 OVS1_BLOCK OVS1 protection block command

8400021C20 OVS2-AB OVS2 relay element operated (phase-AB)

8500021C21 OVS2-BC OVS2 relay element operated (phase-BC)

8600021C22 OVS2-CA OVS2 relay element operated (phase-CA)

8100021B65 OVS2-OPT OVS2 protection operated

8400021B62 OVS2-OPT-AB OVS2 protection operated (phase-AB)

8100021B66 OVS2-OPT-ALARM Alarm signal by OVS2 protection

8500021B63 OVS2-OPT-BC OVS2 protection operated (phase-BC)

8600021B64 OVS2-OPT-CA OVS2 protection operated (phase-CA)

8000021B23 OVS2-OPT-TRIP Trip signal by OVS2 protection

8100021B60 OVS2-OR OVS2 relay element operated (3-phases OR)

8400021C24 OVS2PU-AB OVS2 relay operation level pick up (phase-AB)

8500021C25 OVS2PU-BC OVS2 relay operation level pick up (phase-BC)

8600021C26 OVS2PU-CA OVS2 relay operation level pick up (phase-CA)

8100021B61 OVS2PU-OR OVS2 relay operation level pick up (3-phases OR)

8100021BB0 OVS2_BLOCK OVS2 protection block command

 Connection point on PLC logic


OVS(Function ID: 461101)
Element ID Name Description
800001EBB0 OVS1_BLOCK OVS1 protection block command

810002EBB0 OVS2_BLOCK OVS2 protection block command

GRL200 (Soft 033 & 037)


- 310 -
6F2S1914 (0.37)

Earth fault overvoltage protection (OVG)


The earth fault overvoltage protection (OVG) function has two stages (OVG1 and OVG2); and
the time characteristic of each stage can be taken from either definite time or inverse definite
minimum time. The purpose of each stage of the OVG is to detect earth fault on unearthed,
resistance-earthed system or AC generators.

The low voltage setting, which may be applied for an OVG element, is susceptible to any
third harmonic component that may be superimposed on an input signal. Therefore, the
function incorporates the filter to suppress the third harmonic component.

To simplify the description, only OVG1 is discussed but is applicable to OVG2; hence,
read the expression for OVG1 as OVG2 for the OVG 2nd stage unless a special explanation or
instruction has been provided.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have phase-phase over-voltage protection features. To
determine whether the features are implemented in the IED or not, locate the IED ordering
number; and check the order number at “G&T position” referring to the comparison table below.
For more information, see Appendix: Ordering.
Table 2.23-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
OVG Earth fault over-voltage protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 311 -
6F2S1914 (0.37)

2.23.1 Drop-off and pickup setting


Figure 2.23-1 shows the characteristic of the OVG element. The outer circle shows the
threshold of pick-up threshold voltage (PU), whereas the inner circle shows drop-off voltage
point (DO). The hatched area shows the operation area of the OVG.

Pickup
V
Dropoff

0 V

Figure 2.23-1 Setting points of OVG

For example, with regard to the OVG1 element, suppose the user sets a pick-up value in
P.U for setting [OVG1]. Then the user should set a drop-off value using setting [OVG1-DPR],
which configures the ratio of the PU to the DO.

2.23.2 Delay of the operation of the OVG element


The OVG element has a delay timer for the operation. For the OVG1 element, the user can set
a delay time using setting [TOVG1]. The user can find the delay timer in the OVG function
logic. (See section 2.23.5)

2.23.3 Time characteristic


The OVG element has two characteristics between a voltage condition and an operation time;
hence, the user should select a mode either (i) definite (independent) time characteristic delay
or (ii) inverse (dependent) time characteristic delay. For the definite time characteristic delay,
the operation time is a constant. In the inverse time characteristic delay, the operation time
depends upon the level of the voltage condition.

(i) Definite time characteristic (DT)


To operate the definite (independent) time delay, set DT for scheme switch [OVG1-Timer].
Resetting the OVG element is performed when a voltage falls below the drop-off voltage.

(ii) Invers time delay (IDMT)


To operate the dependent (invers) time delay, set IDMT for scheme switch [OVG1-Timer].

GRL200 (Soft 033 & 037)


- 312 -
6F2S1914 (0.37)

Operation feature
The operate time of the inverse (dependent) time characteristic is inversely proportional to the
level of the voltage condition. Figure 2.23-1 shows the invers time characteristic of the OVG
element when a multiplier setting is used. The OVG element uses (2.23-1) to be in conformity
to IEC 60255-127:

𝑘
t(G) = TMS × {[ 𝑎 ] + 𝑐} (2.23-1)
(𝑉⁄𝑉 ) − 1
𝑠

where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage), and
TMS = time multiplier setting to adjust a curve

If the user will require a user-programmable (original) curve in the inverse time
characteristic, it is provided when the constants of k, a, c are set, as shown in Table 2.23-2. For
example, the user-programmable (original) curve in the OVG1 element will be acquired when
Original is set for the scheme switch [OVG1-Timer], and when values of respective constants
are set for [OVG1-k], [OVG1-a], and [OVG1-C].

Overvoltage Inverse Time Curves

1000.000

100.000
Operating Time (secs)

10.000

TMS = 10

TMS = 5

1.000
TMS = 2

TMS = 1

0.100
1 1.5 2 2.5 3
Applied Voltage (x Vs)

Figure 2.23-2 IDMT characteristic of OVG element

GRL200 (Soft 033 & 037)


- 313 -
6F2S1914 (0.37)

Table 2.23-2 Constant value at each setting of IDMT curve


Set item k a C
IDMT 1 1 0
User-programmable 0.00000 – 500.00000 0.00000 – 10.00000 0.00000 – 10.00000
(Original) by 0.00001 step by 0.00001 step by 0.00001 step
Reset feature
The user should set the time for resetting. Table 2.23-2 shows that examples of the pick-up and
the drop-off relevant to both the fault occurrences and the operation time. The value of the
time counter furnished in the OVG1 element is incremented if faults occur.

As for an intermittent fault (the former in the figure), the time counter will not reach the
trip level. In the other words, the operation of the OVG1 element is paralyzed in the reset time
set by [TOVG1R].

If a series of fault occurs repeatedly (the latter in the figure), and if the value of the time
counter reaches at trip level, the OVG1 element will issue a trip command after a certain delay.
After issuing the trip command, if a series of fault completely disappears after issuing the trip
command, the value of the time counter will be expired after the reset time [TOVG1R].

When the user requires resetting the operation of the OVG1 element immediately, setting
zero for the settings [TOVG1R] is needed. Consequently, when a voltage falls below the reset
threshold (drop-off), the operation of the OVG1 element is reset promptly.
Intermittent fault Series faults
Condition fault occurrence
T3

Fault observation by the relay

Issue of trip command

Relay operation reset


Incrimination of time counter
corresponding to the fault
duration. Trip level

Tripping

T1 T1 T1 T1

T2 T2
T1: Resetting time set by the user Increment process in time Reset of time counter
T2: Actual resetting time in the relay operation counter
T3: Time gap between fault occurrence and relay start time Value maintenance of time counter

Figure 2.23-3 Faults occurrences and reset operation when IDMT being applied

GRL200 (Soft 033 & 037)


- 314 -
6F2S1914 (0.37)

2.23.4 Miscellaneous functions


(i) OVG operation blocked by the occurrence of VT failure
Blocking the OVG function may be required when a failure in the voltage transformer occurs.
The user shall set Block for scheme switch [OVG1-VTFBlk]. Non (as a default) is set for scheme
switch [OVG1-VTFBlk] in order that the OVG function is not blocked by the failure.

(ii) Switch of OVG trip command


The OVG function issues a trip command for the TRC† when Trip is set for scheme switch
[OVG1-UseFor] as the normal trip operation. However, when an alarm signal in place of the
trip command is required, the user can set Alarm for the scheme switch [OVG1-UseFor].
†Note:For more information of the trip circuit, see Chapter Relay application: Trip
circuit.

(iii) Execution of OVG function


Set On for scheme switch [OVG1-EN]. Otherwise, set Off for the scheme switch [OVG1-EN] if
the OVG1 element is not required to operate.

2.23.5 Scheme logic


Figure 2.23-4 shows the OVG function logic. Signal connection points “OVG*_BLOCK” are
provided for the block of the operation of the OV elements. For testing, the OVG1-PU element
is provided; it generates a pick-up signal when the entering voltage is excesses of the threshold
anytime. Thereby, in the IDMT characteristic, using both monitoring points “8000011C23” and
“8000011C27” can facilitate to measure the pickup time after the excess.

GRL200 (Soft 033 & 037)


- 315 -
6F2S1914 (0.37)

8000011C23

OVG1
& TOVG1 8000011B60
& t 0
8000011C27 & ≥1 OVG1-OPT

OVG1 PU 0.00-300.00s

OVG1-EN On &

VTF_DETECT
&
≥1 1

OVG1-VTFBlk
OV1-VTFBlk

CB_LOSS_PHASE

OVG1-BLOCK 8000011B23
8300011B23
DT &
IDMT ≥1 OVG-OPT-TRIP
OVG1-Timer
Original Trip 8100021B61
≥1
OVG1-UseFor 8400001B61
Alarm &
≥1 OVG-OPT-ALARM

OVG2 logic 8000021B23

OVG2-OPT-TRIP
OVG-ARC-BLOCK
8100021B61

OVG2-OPT-ALARM
8100021B60

OVG2-OPT

Figure 2.23-4 OVG function logics

GRL200 (Soft 033 & 037)


- 316 -
6F2S1914 (0.37)

2.23.6 Setting
OVG(Function ID: 462101)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OVG1-EN Off / On - OVG1 protection scheme switch Off
OVG2-EN Off / On - OVG2 protection scheme switch Off
OVG1 OVG1-Timer DT / IDMT / Original - OVG1 delay type DT
DT OVG1 1.0 - 220.0 V OVG1 threshold 20.0
TOVG1 0.00 - 300.00 s OVG1 operating delay time (in DT mode) 1.00
OVG1-DPR 10 - 100 % OVG1 drop-out/pick-up ratio 100
IDMT OVG1 1.0 - 220.0 V OVG1 threshold 20.0
OVG1-DPR 10 - 100 % OVG1 drop-out/pick-up ratio 100
OVG1-TMS 0.010 - 100.000 - OVG1 time multiplier (in IDMT mode) 1.000
TOVG1R 0.0 - 300.0 s OVG1 definite time reset delay 0.0
ORG OVG1 1.0 - 220.0 V OVG1 threshold 20.0
OVG1-DPR 10 - 100 % OVG1 drop-out/pick-up ratio 100
OVG1-TMS 0.010 - 100.000 - OVG1 time multiplier (in ORG mode) 1.000
TOVG1R 0.0 - 300.0 s OVG1 definite time reset delay 0.0
OVG1-k 0.00000 - 500.00000 - OVG1 user original curve coefficient 0.00000
OVG1-a 0.00000 - 10.00000 - OVG1 user original curve coefficient 0.00000
OVG1-c 0.00000 - 10.00000 - OVG1 user original curve coefficient 0.00000
Output OVG1-VTFBlk Non / Block - OVG1 operation block by VTF Non
OVG1-UseFor Trip / Alarm - OVG1 used for trip or alarm Trip
OVG2 OVG2-Timer DT / IDMT / Original - OVG2 delay type DT
DT OVG2 1.0 - 220.0 V OVG2 threshold 20.0
TOVG2 0.00 - 300.00 s OVG2 operating delay time (in DT mode) 1.00
OVG2-DPR 10 - 100 % OVG2 drop-out/pick-up ratio 100
IDMT OVG2 1.0 - 220.0 V OVG2 threshold 20.0
OVG2-DPR 10 - 100 % OVG2 drop-out/pick-up ratio 100
OVG2-TMS 0.010 - 100.000 - OVG2 time multiplier (in IDMT mode) 1.000
TOVG2R 0.0 - 300.0 s OVG2 definite time reset delay 0.0
ORG OVG2 1.0 - 220.0 V OVG2 threshold 20.0
OVG2-DPR 10 - 100 % OVG2 drop-out/pick-up ratio 100
OVG2-TMS 0.010 - 100.000 - OVG2 time multiplier (in ORG mode) 1.000
TOVG2R 0.0 - 300.0 s OVG2 definite time reset delay 0.0
OVG2-k 0.00000 - 500.00000 - OVG2 user original curve coefficient 0.00000
OVG2-a 0.00000 - 10.00000 - OVG2 user original curve coefficient 0.00000
OVG2-c 0.00000 - 10.00000 - OVG2 user original curve coefficient 0.00000
Output OVG2-VTFBlk Non / Block - OVG2 operation block by VTF Non
OVG2-UseFor Trip / Alarm - OVG2 used for trip or alarm Trip

GRL200 (Soft 033 & 037)


- 317 -
6F2S1914 (0.37)

2.23.7 Data ID
 Signal monitoring point
OVG(Function ID: 462101)
Element ID Name Description
8400001B61 OVG-OPT-ALARM Alarm signal by OVG protection

8300001B23 OVG-OPT-TRIP Trip signal by OVG protection

8000011C23 OVG1 OVG1 relay element operated

8000011B60 OVG1-OPT OVG1 protection operated

8100011B61 OVG1-OPT-ALARM Alarm signal by OVG1 protection

8000011B23 OVG1-OPT-TRIP Trip signal by OVG1 protection

8000011C27 OVG1PU OVG1 relay operation level pick up

8000011BB0 OVG1_BLOCK OVG1 protection block command

8100021C23 OVG2 OVG2 relay element operated

8100021B60 OVG2-OPT OVG2 protection operated

8100021B61 OVG2-OPT-ALARM Alarm signal by OVG2 protection

8000021B23 OVG2-OPT-TRIP Trip signal by OVG2 protection

8100021C27 OVG2PU OVG2 relay operation level pick up

8100021BB0 OVG2_BLOCK OVG2 protection block command

 Connection point on PLC logic


OVG(Function ID: 462101)
Element ID Name Description
800001EBB0 OVG1_BLOCK OVG1 protection block command

810002EBB0 OVG2_BLOCK OVG2 protection block command

GRL200 (Soft 033 & 037)


- 318 -
6F2S1914 (0.37)

Phase under-voltage protection (UV)


The under-voltage protection function for phase-to-earth (UV) consists of two stages (elements)
independently: UV1 and UV2. The time characteristic of the UV element is configured either
definite time (DT) or inverse definite minimum time (IDMT) using settings.

Each UV stage (element) detects the under-voltage condition of phase-to-earth. The user
can set a threshold and the ratio of a drip-out voltage (DO) to a pick-up voltage (PU) in the UV
element. To simplify the description, only the UV1 element is described, but the expression is
applicable to the UV2; hence, read the expression for the UV1 element as the UV2 unless a
special explanation or instruction has been provided.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have phase under-voltage protection features. To
determine whether the features are implemented in the IED or not, locate the IED ordering
number; and check the order number at “G&T position” referring to the comparison table below.
For more information, see Appendix: Ordering.
Table 2.24-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
UV Phase under-voltage protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 319 -
6F2S1914 (0.37)

2.24.1 Drop-off and pick-up characteristic


Figure 2.24-1 shows the UV characteristic as hatched area with concentric circles. The pick-
up threshold voltage (PU) is represented the outer circle; the drop-off voltage point (DO) is
represented the dotted circle. The PU voltage of the UV1 element is set using [UV1]. The DO
voltage of the UV1 element is set using [UV1-DPR].

The inner circle shows the area in which the UV function is blocked when the value of
the block voltage is set for [UVBLK]. Setting [TUVBLK] is also provided so that the user can
delay blocking the UV1 and UV2 elements using the setting.

Drop-off
Pickup

o V
UV block

Figure 2.24-1 UV1 element characteristic

2.24.2 Time characteristic


The UV element has the relationship between an input voltage and an operation time; the
relationship is divided into two time characteristics: (i) the definite time (DT) and (ii) the
inverse definite minimum time (IDMT).

(i) Definite time characteristic (DT)


Setting pick-up operation
The user is required to set DT for scheme switch [UV1-Timer] when the UV1 element should
operate in the DT characteristic. The UV1 element has a delay timer for the pick-up operation;
the user can set a delay time using setting [TUV1]. The user can find the delay timer in the UV
function logic. (See section 2.24.4)

Setting drop-off operation


Resetting the UV1 element is performed instantly when a voltage exceeds over the drop-off
voltage.

(ii) Inverse definite minimum time (IDMT) characteristic


To operate the IDMT characteristic in the UV1 element, set scheme switch [UV1-Timer] IDMT.

GRL200 (Soft 033 & 037)


- 320 -
6F2S1914 (0.37)

Setting pick-up operation


The IDMT characteristic is applied when the operation of the UV1 element is required
inversely in accordance with the level of input voltage. The IDMT characteristic curve is
illustrated in Figure 2.24-2 using a value of time multiplier is set for [UV1-TMS]. It is followed
to Equation (2.24-1) in conformed in IEC 60255-127

𝑘
t(G) = TMS × {[ 𝑎] + 𝑐} (2.24-1)
1 − (𝑉⁄𝑉 )
𝑠

where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage),
TMS = time multiplier setting.

Except for pre-programmed characteristics, the user can have a user-programmable


(original) characteristic curve. The user-programmable (original) curve is obtained when the
constants of k, a, c, as shown in Table 2.24-2, are set, and when Original is set for scheme
switch [UV1-Timer]. The constants are set with settings [UV1-k], [UV1-a], and [UV1-C].

Undervoltage Inverse Time Curves

1000.000

100.000
Operating Time (secs)

TMS=10
10.000
TMS=5

TMS=2

TMS=1
1.000
0 0.2 0.4 0.6 0.8 1
Applied Voltage (x Vs)

Figure 2.24-2 IDMT characteristics curves depending on TMS

GRL200 (Soft 033 & 037)


- 321 -
6F2S1914 (0.37)

Table 2.24-2 Values k, a, c for pre-programmable IDMT and user-programmable IDMT


Set item k a C
IDMT 1 1 0
User-programmable 0.00000 – 500.00000 0.00000 – 10.00000 0.00000 – 10.00000
(Original) by 0.00001 step by 0.00001 step by 0.00001 step
Setting drop-off operation
The user should set the time for resetting in the IDMT characteristic. Figure 2.24-3 shows
examples of the pick-up and the drop-off relevant to both the fault occurrences and the
operation time. The UV1 element has a time counter that increases in response to the fault
occurrence and duration. This figure also shows the increment degree of the time counter for
the fault occurrences.

As for an intermittent fault (the former in the figure), the time counter does not reach
the trip level. In the other word, the UV1 element will be paralyzed in the reset time [TUV1R].

If a series of fault occurs, the time counter increase corresponding to the duration of series
faults. When the time counter reaches the trip level, then the UV1 element issues a trip signal
after a certain delay. After issuing the trip signal, if a series of fault disappears completely, the
operation of the UV1 element is expired after the reset time [TUV1R].

When the user requires resetting the operation of the UV1 element immediately, setting
zero for the settings [TUV1R] is needed. Consequently, when a voltage is recovered over the
reset threshold (drop-off), the operation of the UV1 element is reset promptly.
Intermittent fault A series fault
Condition fault occurrence T3

Fault observation by the relay

Issue of trip command

Relay operation reset


Incrimination of time counter
corresponding to the fault
duration. Trip level

Tripping

T1 T1 T1 T1

T2 T2
T1: Resetting time set by the user Increment process in time
T2: Actual resetting time in the relay operation counter
T3: Time gap between fault occurrence and relay start time Value maintenance of time counter Reset of time counter

Figure 2.24-3 Faults occurrences and reset operation when IDMT being applied

GRL200 (Soft 033 & 037)


- 322 -
6F2S1914 (0.37)

2.24.3 Miscellaneous functions


(i) Blocking UV operation
Blocking the UV function may be required when a failure in the voltage transformer occurs.
In this case, the user shall set Block for scheme switch [UV1-VTFBlk]. Non (as a default) is set
for scheme switch [UV1-VTFBlk] in order that the UV function is not blocked by the failure.

(ii) UV trip signal


The UV1 element issues a trip signal for the trip circuit (TRC†) when Trip is set for scheme
switch [UV1-UseFor] as the normal tripping. However, when an alarm signal in place of the
trip signal is required, the user can set Alarm for the scheme switch [UV1-UseFor].

†Note:For more information about tripping, see Chapter Relay application: Trip circuit.

(iii) Operation of UV element


The user should set On for scheme switch [UV1-EN] for the operation of the UV1 element.
Otherwise, set Off for the scheme switch if the UV1 element is not required to operate.

(iv) Under voltage test


Setting [UV-Test] =On is not to operate UV blocking element (UVBLK) for testing.

2.24.4 Scheme logic


Figure 2.24-4 show the logic of the UV function. PLC connection points “UV*_BLOCK” are
provided for blocking the operation of the UV elements. Other PLC connection points
“CB_*PH_OPEN” are provided so that the UV function can determine its operation using the
open/closed information of a circuit breaker (CB). For testing, the UV1-PU element is provided;
it generates a pick-up signal when the entering voltage is below the threshold anytime. For
example, in the IDMT characteristic, using both PLC monitoring points “8000011B20” and
“8000011B24” can facilitate to measure the pickup time after the deficiency.

GRL200 (Soft 033 & 037)


- 323 -
6F2S1914 (0.37)

8000011B20 TUV1
8000011B62
A & t 0 To TRC
8100011B21
& &
≥1 8100011B63 ≥1 UV-OPT-A
UV1 B & t 0
8200011B22 & &
≥1
8200011B64 ≥1 UV-OPT-B
C & t 0
& & ≥1 ≥1 UV-OPT-C
≥1 8000011B60
0.00 to 300.00s

8000011B65
8000011B24 & UV1-OPT
≥1
A
8100011B25 & UV2-OPT
UV1 PU B
8200011B26
& & UV-OPT-TRIP
C ≥1
& ≥1 UV-OPT-ALARM
≥1 8000011B61

UV-ARC-BLOCK

UV1-EN On Trip
UV1-UseFor
Alarm

8000011B60
A ≥1
8100011B61 TUVBLK
UVBLK B t 0
8200011B62
1 ≥1
C
0.00 to
300.00s
UVBLK-EN On

UV-Test On

800001EBB0 CB_APH_OPEN 1

810001EBB1 CB_BPH_OPEN 1

820001EBB2 CB_CPH_OPEN 1 Trip


&
UV2-UseFor
DT Alarm
&
IDMT
Original ≥1 8100021B65
UV1-Timer
≥1
8400021C20 TUV2
8400021B62
A & &
t 0
8500021C21 &
≥1 8500021B63
UV2 B t 0
8600021C22 & & &
≥1
C 8600021B64
& & t 0
& ≥1
≥1 8100021B60
0.00 to 300.00s

8400021C20 &
A
8500021C25 &
UV2 PU B
8600021C26
&
C

≥1 8100021B61

UV2-EN On

800001EBB0 UV1_BLOCK ≥1
1
UV1-VTFBlk Block
&

≥1 1
810002EBB0 UV2_BLOCK

UV2-VTFBlk Block

From VTF &


VTF_DETECT

DT
IDMT
Original ≥1
UV2-Timer

Figure 2.24-4 Scheme logic of UV function

GRL200 (Soft 033 & 037)


- 324 -
6F2S1914 (0.37)

2.24.5 Setting
UV(Function ID: 470101)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
BLK UVBLK Off / On - Operation canceled when UVBLK operated Off
UVBLK 10.0 V Threshold of UVBLK element 10.0
TUVBLK 10.00 S UVBLK operation delay timer 10.00
UV1-EN Off / On - UV1 protection scheme switch Off
UV2-EN Off / On - UV2 protection scheme switch Off
UV1 UV1-Timer DT / IDMT / Original - UV1 delay type DT
DT UV1 5.0 - 130.0 V UV1 threshold 60.0
UV1-DPR 100 - 120 % UV1 drop-out/pick-up ratio 100
TUV1 0.00 - 300.00 s UV1 operating delay time (in DT mode) 1.00
IDMT UV1 5.0 - 130.0 V UV1 threshold 60.0
UV1-DPR 100 - 120 % UV1 drop-out/pick-up ratio 100
UV1-TMS 0.010 - 100.000 - UV1 time multiplier (in IDMT mode) 1.000
TUV1R 0.0 - 300.0 s UV1 definite time reset delay 0.0
ORG UV1 5.0 - 130.0 V UV1 threshold 60.0
UV1-DPR 100 - 120 % UV1 drop-out/pick-up ratio 100
UV1-TMS 0.010 - 100.000 - UV1 time multiplier (in ORG mode) 1.000
UV1-k 0.00000 - 500.00000 - UV1 user original curve coefficient 0.00000
UV1-a 0.00000 - 10.00000 - UV1 user original curve coefficient 0.00000
UV1-c 0.00000 - 10.00000 - UV1 user original curve coefficient 0.00000
TUV1R 0.0 - 300.0 s UV1 definite time reset delay 0.0
Output UV1-VTFBlk Non / Block - UV1 operation block by VTF Non
UV1-UseFor Trip / Alarm - UV1 used for trip or alarm Trip
UV2 UV2-Timer DT / IDMT / Original - UV2 delay type DT
DT UV2 5.0 - 130.0 V UV2 threshold 60.0
UV2-DPR 100 - 120 % UV2 drop-out/pick-up ratio 100
TUV2 0.00 - 300.00 s UV2 operating delay time (in DT mode) 1.00
IDMT UV2 5.0 - 130.0 V UV2 threshold 60.0
UV2-DPR 100 - 120 % UV2 drop-out/pick-up ratio 100
UV2-TMS 0.010 - 100.000 - UV2 time multiplier (in IDMT mode) 1.000
TUV2R 0.0 - 300.0 s UV2 definite time reset delay 0.0
ORG UV2 5.0 - 130.0 V UV2 threshold 60.0
UV2-DPR 100 - 120 % UV2 drop-out/pick-up ratio 100
UV2-TMS 0.010 - 100.000 - UV2 time multiplier (in ORG mode) 1.000
UV2-k 0.00000 - 500.00000 - UV2 user original curve coefficient 0.00000
UV2-a 0.00000 - 10.00000 - UV2 user original curve coefficient 0.00000
UV2-c 0.00000 - 10.00000 - UV2 user original curve coefficient 0.00000
TUV2R 0.0 - 300.0 s UV2 definite time reset delay 0.0
Output UV2-VTFBlk Non / Block - UV2 operation block by VTF Non
UV2-UseFor Trip / Alarm - UV2 used for trip or alarm Trip

Test tool(Function ID: 470101)


Range Default
Setting device Unit Contents Note
1A rating 5A rating 1A 5A
Function test UV-Test Off / On - Not to execute UVBLK element Off

GRL200 (Soft 033 & 037)


- 325 -
6F2S1914 (0.37)

2.24.6 Data ID
 Signal monitoring point
UV(Function ID: 470101)
Element ID Name Description
8000011C20 UV1-A UV1 relay element operated (phase-A)

8100011C21 UV1-B UV1 relay element operated (phase-B)

8200011C22 UV1-C UV1 relay element operated (phase-C)

8000011B60 UV1-OR UV1 relay element operated (3-phases OR)

8000011C24 UV1PU-A UV1 PU relay operation level pick up (phase-A)

8100011C25 UV1PU-B UV1 PU relay operation level pick up (phase-B)

8200011C26 UV1PU-C UV1 PU relay operation level pick up (phase-C)

8000011B61 UV1PU-OR UV1 PU relay operation level pick up (3-phases OR)

8000011B62 UV1-OPT-A UV1 protection operated (phase-A)

8100011B63 UV1-OPT-B UV1 protection operated (phase-B)

8200011B64 UV1-OPT-C UV1 protection operated (phase-C)

8000011B65 UV1-OPT UV1 protection operated (3-phases OR)

8400021C20 UV2-A UV2 relay element operated (phase-A)

8500021C21 UV2-B UV2 relay element operated (phase-B)

8600021C22 UV2-C UV2 relay element operated (phase-C)

8100021B60 UV2-OR UV2 relay element operated (3-phases OR)

8400021C24 UV2PU-A UV2 relay operation level pick up (phase-A)

8500021C25 UV2PU-B UV2 relay operation level pick up (phase-B)

8600021C26 UV2PU-C UV2 relay operation level pick up (phase-C)

8100021B61 UV2PU-OR UV2 relay operation level pick up (3-phases OR)

8400021B62 UV2-OPT-A UV2 protection operated (phase-A)

8500021B63 UV2-OPT-B UV2 protection operated (phase-B)

8600021B64 UV2-OPT-C UV2 protection operated (phase-C)

8100021B65 UV2-OPT UV2 protection operated (3-phases OR)

8000001B60 UVBLK-A UVBLK relay operation level pick up (phase-A)

8100001B61 UVBLK-B UVBLK relay operation level pick up (phase-B)

8200001B62 UVBLK-C UVBLK relay operation level pick up (phase-C)

 Connection point in PLC logic


UV(Function ID: 470101)
Element ID Name Description
800001EBB0 UV1_BLOCK UV1 protection block command

810002EBB0 UV2_BLOCK UV2 protection block command

800000EBB0 CB_APH_OPEN Circuit Breaker detection (phase-A)

810000EBB1 CB_BPH_OPEN Circuit Breaker detection (phase-B)

820000EBB2 CB_CPH_OPEN Circuit Breaker detection (phase-C)

GRL200 (Soft 033 & 037)


- 326 -
6F2S1914 (0.37)

Phase-to-phase under-voltage protection (UVS)


The under-voltage protection function for phase-to-phase (UVS) consists of two stages
(elements) independently: UVS1 and UVS2. The time characteristic of the UVS element is
configured either definite time (DT) or inverse definite minimum time (IDMT) using settings.

Each UVS element detects the under-voltage condition of phase-to-phase. The user can
set a threshold and the ratio of a drip-out voltage (DO) to a pick-up voltage (PU) in the UVS
element. To simplify the description, only the UVS1 element is described, but the expression
is applicable to the UVS2; hence, read the expression for the UVS1 element as the UVS2 unless
a special explanation or instruction has been provided.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have phase-phase under-voltage protection features. To
determine whether the features are implemented in the IED or not, locate the IED ordering
number; and check the order number at “G&T position” referring to the comparison table below.
For more information, see Appendix: Ordering.
Table 2.25-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
UVS Phase-phase under-voltage protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 327 -
6F2S1914 (0.37)

2.25.1 Drop-off and pick-up characteristic


Figure 2.25-1 shows the UVS characteristic as hatched area with concentric circles. The pick-
up threshold voltage (PU) is represented the outer circle; the drop-off voltage point (DO) is
represented the dotted circle. The PU voltage of the UVS1 element is set using [UVS1]. The
DO voltage of the UVS1 element is set using [UVS1-DPR].

The inner circle shows the area in which the UVS function is blocked when the value of
the block voltage is set for [UVSBLK]. Setting [TUVSBLK] is also provided so that the user can
delay blocking the UVS1 and UVS2 elements using the setting.

Drop-off
Pickup

o V
UVS block

Figure 2.25-1 UVS1 element characteristic

2.25.2 Time characteristic


The UVS element has the relationship between an input voltage and an operation time; the
relationship is divided into two time characteristics: (i) the definite time (DT) and (ii) the
inverse definite minimum time (IDMT).

(i) Definite time characteristic (DT)


Setting pick-up operation
The user is required to set DT for scheme switch [UVS1-Timer] when the UVS1 element should
run in the DT characteristic. The UVS1 element has a delay timer for the operation; the user
can set a delay time using setting [TUVS1]. The user can find the delay timer in the UVS
function logic. (See section 2.25.4)

Setting drop-off operation


Resetting the UVS1 element is performed instantly when a voltage exceeds over the drop-off
voltage.

(ii) Inverse definite minimum time (IDMT) characteristic


To operate the inverse definite minimum time (IDMT), set scheme switch [UVS1-Timer] IDMT.

GRL200 (Soft 033 & 037)


- 328 -
6F2S1914 (0.37)

Pick-up characteristic
The IDMT characteristic is applied when the operation of the UVS1 element is required
inversely in accordance with the level of input voltage. The IDMT characteristic curve is
illustrated in Figure 2.25-2 using a value of time multiplier is set for [UV1-TMS]. It is followed
to Equation (2.25-1) in conformed in IEC 60255-127

𝑘
t(G) = TMS × {[ 𝑎] + 𝑐} (2.25-1)
1 − (𝑉⁄𝑉 )
𝑠

where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage),
TMS = time multiplier setting.

Except for pre-programmed characteristics, the user can have a user-programmable


(original) characteristic curve. The user-programmable (original) curve is obtained when the
constants of k, a, c, as shown in Table 2.25-2, are set, and when Original is set for scheme
switch [UVS1-Timer]. The constants are set with settings [UVS1-k], [UVS1-a], and [UVS1-C].

Undervoltage Inverse Time Curves

1000.000

100.000
Operating Time (secs)

TMS=10
10.000
TMS=5

TMS=2

TMS=1
1.000
0 0.2 0.4 0.6 0.8 1
Applied Voltage (x Vs)

Figure 2.25-2 IDMT characteristics curves depending on TMS

GRL200 (Soft 033 & 037)


- 329 -
6F2S1914 (0.37)

Table 2.25-2 Values k, a, c for pre-programmable IDMT and user-programmable IDMT


Set item k a C
IDMT 1 1 0
User-programmable 0.00000 – 500.00000 0.00000 – 10.00000 0.00000 – 10.00000
(Original) by 0.00001 step by 0.00001 step by 0.00001 step

Drop-off characteristic
The user should set the time for resetting in the IDMT characteristic. Figure 2.25-3 shows
examples of the pick-up and the drop-off relevant to both the fault occurrences and the
operation time. The UVS1 element has a time counter that increases in response to the fault
occurrence and duration. This figure also shows the increment degree of the time counter for
the fault occurrences.

As for an intermittent fault (the former in the figure), the time counter does not reach
the trip level. In the other word, the UVS1 element will be paralyzed in the reset time
[TUVS1R]. If a series of fault occurs, the time counter increase corresponding to the duration
of series faults. When the time counter reaches the trip level, then the UVS1 element issues a
trip signal after a certain delay. After issuing the trip signal, if a series of fault disappears
completely, the operation of the UVS1 element is expired after the reset time [TUVS1R].

When the user requires resetting the operation of the UVS1 element immediately, setting
zero for the settings [TUVS1R] is needed. Consequently, when a voltage is recovered over the
reset threshold (drop-off), the operation of the UVS1 element is reset promptly.
Condition fault occurrence Intermittent fault A series fault

T3

Fault observation by the relay

Issue of trip command

Relay operation reset


Incrimination of time counter
corresponding to the fault
duration. Trip level

Tripping

T1 T1 T1 T1

T2 T2
T1: Resetting time set by the user Increment process in time Reset of time counter
T2: Actual resetting time in the relay operation counter
T3: Time gap between fault occurrence and relay start time Value maintenance of time counter

Figure 2.25-3 Faults occurrences and reset operation when DT being applied

GRL200 (Soft 033 & 037)


- 330 -
6F2S1914 (0.37)

2.25.3 Miscellaneous functions


(i) Block of UVS operation
Blocking the UVS function may be required when a failure in the voltage transformer occurs.
In this case, the user shall set Block for scheme switch [UVS1-VTFBlk]. Non (as a default) is
set for scheme switch [UVS1-VTFBlk] in order that the UVS function is not blocked by the
failure.

(ii) UVS trip signal


The UVS1 element issues a trip signal for the trip circuit (TRC†) when Trip is set for scheme
switch [UVS1-UseFor] as the normal tripping. However, when an alarm signal in place of the
trip signal is required, the user can set Alarm for the scheme switch [UVS1-UseFor].

†Note:For more information about tripping, see Chapter Relay application: Trip circuit.

(iii) Operation of UVS function


Set On for scheme switch [UVS1-EN]. Otherwise, set Off for the scheme switch [UVS1-EN] if
the UVS1 element is not required to operate.

(iv) Under voltage test


Setting [UVS-Test] =On is not to operate UVS blocking element (UVSBLK) for testing.

2.25.4 Scheme logic


Figure 2.25-4 show the logic of the UVS function. PLC connection points “UVS*_BLOCK” are
provided for blocking the operation of the UVS elements. Other PLC connection points
“CB_*PH_OPEN” are provided so that the UVS function can determine its operation using the
open/closed information of a circuit breaker (CB). For testing, the UVS1-PU element is
provided; it generates a pick-up signal when the entering voltage is below the threshold
anytime. For example, in the IDMT characteristic, using both PLC monitoring points
“8000011B20” and “8000011B24” can facilitate to measure the pickup time after the deficiency.

GRL200 (Soft 033 & 037)


- 331 -
6F2S1914 (0.37)

8000011B20 TUVS1
8000011B62
AB & t 0 To TRC
8100011B21
& &
≥1 8100011B63 ≥1 UVS-OPT-AB
UVS1 BC & t 0
8200011B22 & &
≥1
8200011B64 ≥1 UVS-OPT-BC
CA & t 0
& & ≥1 ≥1 UVS-OPT-CA
≥1 8000011B60
0.00 to 300.00s

8000011B65
8000011B24 & UVS1-OPT
≥1
AB
8100011B25 & UVS2-OPT
V
UVS1 PU BC
8200011B26
& & UVS-OPT-TRIP
CA ≥1
& ≥1 UVS-OPT-ALAR
≥1 8000011B61 M
UVS-ARC-BLOCK

UV1-EN On Trip
UVS1-UseFor
Alarm

8000011B60
AB ≥1
8100011B61 TUVBLK
UVSBLK BC t 0
8200011B62
1 ≥1
CA
0.00 to
300.00s
UVSBLK-EN On

UVS-Test On

800001EBB0 CB_APH_OPEN 1

810001EBB1 CB_BPH_OPEN 1

820001EBB2 CB_CPH_OPEN 1 Trip


&
UVS2-UseFor
DT Alarm
&
IDMT
Original ≥1 8100021B65
UVS1-Timer
≥1
8400021C20 TUVS2
8400021B62
AB & &
t 0
8500021C21 &
≥1 8500021B63
UVS2 BC t 0
8600021C22 & & &
≥1
CA 8600021B64
& & t 0
& ≥1
≥1 8100021B60
0.00 to 300.00s

8400021C20 &
AB
8500021C25 &
UVS2 PU BC
8600021C26
&
CA

≥1 8100021B61

UVS2-EN On

800001EBB0 UVS1_BLOCK ≥1
1
UVS1-VTFBlk Block
&

≥1 1
810002EBB0 UV2_BLOCK

UVS2-VTFBlk Block

From VTF &


VTF_DETECT

DT
IDMT
Original ≥1
UVS2-Timer

Figure 2.25-4 Scheme logic of UVS function

GRL200 (Soft 033 & 037)


- 332 -
6F2S1914 (0.37)

2.25.5 Setting
UVS(Function ID: 471101)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
BLK UVSBLK-EN Off / On - Operation canceled when UVSBLK operated Off
UVSBLK 5.0 – 20.0 V Threshold of UVSBLK element 10.0
TUVBLK 0.00 – 300.00 s UVSBLK operation delay timer 10.00
UVS1-EN Off / On - UVS1 protection scheme switch Off
UVS2-EN Off / On - UVS2 protection scheme switch Off
UVS1 UVS1-Timer DT / IDMT / Original - UVS1 delay type DT
DT UVS1 5.0 - 130.0 V UVS1 threshold 60.0
UVS1-DPR 100 - 120 % UVS1 drop-out/pick-up ratio 100
TUVS1 0.00 - 300.00 s UVS1 operating delay time (in DT mode) 1.00
IDMT UVS1 5.0 - 130.0 V UVS1 threshold 60.0
UVS1-DPR 100 - 120 % UVS1 drop-out/pick-up ratio 100
UVS1-TMS 0.010 - 100.000 - UVS1 time multiplier (in IDMT mode) 1.000
TUVS1R 0.0 - 300.0 s UVS1 definite time reset delay 0.0
ORG UVS1 5.0 - 130.0 V UVS1 threshold 60.0
UVS1-DPR 100 - 120 % UVS1 drop-out/pick-up ratio 100
UVS1-TMS 0.010 - 100.000 - UVS1 time multiplier (in ORG mode) 1.000
UVS1-k 0.00000 - 500.00000 - UVS1 user original curve coefficient 0.00000
UVS1-a 0.00000 - 10.00000 - UVS1 user original curve coefficient 0.00000
UVS1-c 0.00000 - 10.00000 - UVS1 user original curve coefficient 0.00000
TUVS1R 0.0 - 300.0 s UVS1 definite time reset delay 0.0
Output UVS1-VTFBlk Non / Block - UVS1 operation block by VTF Non
UVS1-UseFor Trip / Alarm - UVS1 used for trip or alarm Trip
UVS2 UVS2-Timer DT / IDMT / Original - UVS2 delay type DT
DT UVS2 5.0 - 130.0 V UVS2 threshold 60.0
UVS2-DPR 100 - 120 % UVS2 drop-out/pick-up ratio 100
TUVS2 0.00 - 300.00 s UVS2 operating delay time (in DT mode) 1.00
IDMT UVS2 5.0 - 130.0 V UVS2 threshold 60.0
UVS2-DPR 100 - 120 % UVS2 drop-out/pick-up ratio 100
UVS2-TMS 0.010 - 100.000 - UVS2 time multiplier (in IDMT mode) 1.000
TUVS2R 0.0 - 300.0 s UVS2 definite time reset delay 0.0
ORG UVS2 5.0 - 130.0 V UVS2 threshold 60.0
UVS2-DPR 100 - 120 % UVS2 drop-out/pick-up ratio 100
UVS2-TMS 0.010 - 100.000 - UVS2 time multiplier (in ORG mode) 1.000
UVS2-k 0.00000 - 500.00000 - UVS2 user original curve coefficient 0.00000
UVS2-a 0.00000 - 10.00000 - UVS2 user original curve coefficient 0.00000
UVS2-c 0.00000 - 10.00000 - UVS2 user original curve coefficient 0.00000
TUVS2R 0.0 - 300.0 s UVS2 definite time reset delay 0.0
Output UVS2-VTFBlk Non / Block - UVS2 operation block by VTF Non
UVS2-UseFor Trip / Alarm - UVS2 used for trip or alarm Trip

Test tool(Function ID: 471101)


Range Default
Item Unit Contents Note
1A rating 5A rating 1A 5A
Function test UVS-Test Off / On - Not to execute UVSBLK element Off

GRL200 (Soft 033 & 037)


- 333 -
6F2S1914 (0.37)

2.25.6 Data ID
 Signal monitoring point
UVS(Function ID: 471101)
Element ID Name Description
8000001BB0 CB_APH_OPEN A phase CB open

8100001BB1 CB_BPH_OPEN B phase CB open

8200001BB2 CB_CPH_OPEN C phase CB open

8C00001B65 UVS-OPT-AB UVS protection operated (phase-AB)

8400001B64 UVS-OPT-ALARM Alarm signal by UVS protection

8D00001B66 UVS-OPT-BC UVS protection operated (phase-BC)

8E00001B67 UVS-OPT-CA UVS protection operated (phase-CA)

8300001B23 UVS-OPT-TRIP Trip signal by UVS protection

8000011C20 UVS1-AB UVS1 relay element operated (phase-AB)

8100011C21 UVS1-BC UVS1 relay element operated (phase-BC)

8200011C22 UVS1-CA UVS1 relay element operated (phase-CA)

8000011B65 UVS1-OPT UVS1 protection operated

8000011B62 UVS1-OPT-AB UVS1 protection operated (phase-AB)

8100011B66 UVS1-OPT-ALARM Alarm signal by UVS1 protection

8100011B63 UVS1-OPT-BC UVS1 protection operated (phase-BC)

8200011B64 UVS1-OPT-CA UVS1 protection operated (phase-CA)

8000011B23 UVS1-OPT-TRIP Trip signal by UVS1 protection

8000011B60 UVS1-OR UVS1 relay element operated (3-phases OR)

8000011C24 UVS1PU-AB UVS1 PU relay operation level pick up (phase-AB)

8100011C25 UVS1PU-BC UVS1 PU relay operation level pick up (phase-BC)

8200011C26 UVS1PU-CA UVS1 PU relay operation level pick up (phase-CA)

8000011B61 UVS1PU-OR UVS1 PU relay operation level pick up (3-phases OR)

8000011BB0 UVS1_BLOCK UVS1 protection block command

8400021C20 UVS2-AB UVS2 relay element operated (phase-AB)

8500021C21 UVS2-BC UVS2 relay element operated (phase-BC)

8600021C22 UVS2-CA UVS2 relay element operated (phase-CA)

8100021B65 UVS2-OPT UVS2 protection operated

8400021B62 UVS2-OPT-AB UVS2 protection operated (phase-AB)

8100021B66 UVS2-OPT-ALARM Alarm signal by UVS2 protection

8500021B63 UVS2-OPT-BC UVS2 protection operated (phase-BC)

8600021B64 UVS2-OPT-CA UVS2 protection operated (phase-CA)

8000021B23 UVS2-OPT-TRIP Trip signal by UVS2 protection

8100021B60 UVS2-OR UVS2 relay element operated (3-phases OR)

8400021C24 UVS2PU-AB UVS2 PU relay operation level pick up (phase-AB)

8500021C25 UVS2PU-BC UVS2 PU relay operation level pick up (phase-BC)

8600021C26 UVS2PU-CA UVS2 PU relay operation level pick up (phase-CA)

8100021B61 UVS2PU-OR UVS2 PU relay operation level pick up (3-phases OR)

8100021BB0 UVS2_BLOCK UVS2 protection block command

8000001B68 UVSBLK UVS protection block command by UVSBLK

8000001B60 UVSBLK-AB UVSBLK relay operation level pick up (phase-AB)

8100001B61 UVSBLK-BC UVSBLK relay operation level pick up (phase-BC)

8200001B62 UVSBLK-CA UVSBLK relay operation level pick up (phase-CA)

GRL200 (Soft 033 & 037)


- 334 -
6F2S1914 (0.37)

 Connection point in PLC logic


UVS(Function ID: 471101)
Element ID Name Description
800000EBB0 CB_APH_OPEN A phase CB open

810000EBB1 CB_BPH_OPEN B phase CB open

820000EBB2 CB_CPH_OPEN C phase CB open

800001EBB0 UVS1_BLOCK UVS1 protection block command

810002EBB0 UVS2_BLOCK UVS2 protection block command

GRL200 (Soft 033 & 037)


- 335 -
6F2S1914 (0.37)

Frequency protection (FRQ/DFRQ)


The frequency protection (FRQ and DFRQ) functions have six frequency elements (stages) to
detect frequency-deviations and frequency-changes, respectively. If the deviations or changes
are appeared, the FRQ and DFRQ function can issue a trip signal (or an alarm signal) in
response to the degree of the frequency-deviation and the frequency-change.

With respect to monitoring the frequency-deviation, either an under-frequency element


(UF) or an over-frequency element (OF) is used to monitor a frequency. The user can set the
degree of frequency deviation at each frequency. Generally, the UF element is applied to
monitor the balance between the power generation capability and the loads. The OF element
is used monitor the frequency to be within the normal range by load shedding; the OF element
is used to protect synchronous machines from possible damage owing to over-frequency
conditions.

With respect to monitoring the frequency-changes, either a frequency-rise element


(RISE) or a frequency-down element (DOWN) is used to monitor the frequency-change. To
monitor the frequency-change, the user should select either the RISE element or the DOWN
element at respective frequencies. The DFRQ is used to ensure the operation of load shedding
promptly when the change of frequency is very rapid.

To simplify the description, only stage 1 is discussed, but is applicable to the other stages;
hence, read the express for stage 1 as the other stages unless a special explanation or
instruction has been produced.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have frequency protection features. To determine whether
the features are implemented in the IED or not, locate the IED ordering number; and check
the order number at “G&T position” referring to the comparison table below. For more
information, see Appendix: Ordering.
Table 2.26-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
FRQ/DFRQ Frequency protection ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 336 -
6F2S1914 (0.37)

2.26.1 FRQ features and characteristics


(i) UF/OF characteristic
The UF and OF elements check the frequency every 5msec; they determines the frequency-
deviations whether the frequency is in under-frequency or over-frequency. Figure 2.26-1(a)
shows the UF characteristic; Figure 2.26-1(b) shows the OF characteristic; hatched area
reflects operation zone of the UF and the OF elements.

The user can select the stage 1 to detect either over-frequency state or under-frequency
state using scheme switch [FRQ1-Chara]. For example, If OverFrq is set for the scheme switch
[FRQ1-Chara], the stage 1 determines the over-frequency state when an over frequency is
observed (Figure 2.26-1(a)); the user can set the threshold value into [FRQ1]. Conversely, if
UnderFrq is set for the scheme switch, the stage 1 determines the under-frequency state when
an under frequency is observed (Figure 2.26-1(b)). The user can use a delay timer to postpone
to issue a trip signal using setting [TFRQ1].

Hz Hz

OF stage 1
operation zone
frequency
Pickup

frequency
Pickup

UF stage 1
operation zone

o o
V V
Pickup voltage (FRQBLK) Pickup voltage (FRQBLK)
a. Over frequency element at Stage 1 b. Under frequency element at Stage 1

Figure 2.26-1 Characteristics of UF and OF elements (e.g. Stage 1 of FRQ)

Regarding the operation of the UF and OF elements, the user should notice the element
not to pick-up when the measured voltage is below the threshold value set with the [FRQBLK]
in positive sequence. Any operation of the FRQ function is blocked when an acquired voltage
is smaller than the pickup voltage to be set.

(ii) Enabling FRQ function


The user should set On to enable the FRQ function using scheme switch [FRQ1-EN]. If the user
do not require the FRQ operation, Off should be set for the scheme switch.

GRL200 (Soft 033 & 037)


- 337 -
6F2S1914 (0.37)

(iii) FRQ trip signal


The FRQ can issue a trip signal for the function of trip circuit (TRC) when Trip is set for scheme
switch [FRQ1-UseFor]. However, when an alarm signal is required in place of the trip signal,
the user should set Alarm for scheme switch [FRQ1-UseFor]. The TRC function is discussed
separately. (See Chapter Relay application: Trip circuit.)

(iv) UF/OF scheme logic


Figure 2.26-2 shows the scheme logic for the UF and OF functions. Each stage operates
independently. PLC connection point “FRQ1-BLOCK” is provided to block the stage1 when
blocking is required by an external signal. The user can connect the PLC connection point with
an external signal using PLC function. (For more information of PLC function, see Chapter
PLC function)

The under-voltage block (FRQBLK) element is used to block the FRQ operation, as
mentioned earlier (section 2.26.1(i)).
To DFRQ
8700001C23
FRQBLK
(UVBLK)
1 NON FRQBLK

8000011BB1
8000011C23 TFRQ1 8000011B60
& ≥1 t 0
OF & & 800001EBB1 FRQ-S1-OPT FRQ-S1-OPT
FRQ1 1
0.00 - 300.00s To TRC
Trip
UF & ≥1
FRQ1-UseFor
& Alarm FRQ-OPT-TRIP
OverFrq &
UnderFrq
FRQ1-Chara
FRQ-OPT-ALARM
8100021C23 8100021B60 8100021BB1
TFRQ2
& ≥1 t 0 FRQ-OPT-BLOCK
OF & & 810002EBB1 FRQ-S2-OPT FRQ-S2-OPT
FRQ2 1
0.00 - 300.00s
Trip
UF &
FRQ2-UseFor
& Alarm
OverFrq &
UnderFrq
FRQ2-Chara

8500061BB1
8500061C23 TFRQ6 8500061B60
& ≥1 t 0
OF & & 850006EBB1 FRQ-S6-OPT FRQ-S6-OPT
FRQ6 1
0.00 - 300.00s
Trip
UF &
FRQ6-UseFor
& Alarm
OverFrq & ≥1
UnderFrq
FRQ6-Chara

On
FRQ1-EN
On
FRQ2-EN

On
FRQ6-EN

800001EBB0 FRQ1-BLOCK 1

810002EBB0 FRQ2-BLOCK 1

850006EBB0 FRQ6-BLOCK 1

Figure 2.26-2 Scheme logic for FRQ function

GRL200 (Soft 033 & 037)


- 338 -
6F2S1914 (0.37)

2.26.2 DFRQ features and characteristics


(i) RISE/DOWN characteristic
The RISE and DOWN elements calculate the gradient of frequency-change (Δf/Δt) every
5msec. Figure 2.26-3 shows how to calculate the gradient using Δf and Δt: the change of
frequency (Δf) over a time interval and Δt equalts to 100ms. Six elements are provided for the
DFRQ function; each element can operate independently. Each stage of the DFRQ function
issues a trip signal if Δf exceeds the setting value of 50 consecutive times.

The user can set the state 1 to detect whether a frequency to be rising or to be descending
using scheme switch [DFRQ1-Chara]. For example, when Rise is set for the scheme switch
[DFRQ1-Chara], the DFRQ examines the gradient of frequency-change (Δf/Δt) in up.
Conversely, when Down is set for the scheme switch, the DFRQ examines the gradient of
frequency-change (Δf/Δt) in down. Setting [DFREQ1] is used to configure an operation
threshold; the operation threshold is configured with Hertz per second.

The operation of the RISE/DOWN elements is blocked when the FRQBLK element runs.
That is, if an obtained voltage is below the setting [FRQBLK], any operation of the DFRQ
function is blocked. The FRQBLK element is discussed in section 2.26.1(i).

Hz
Δf

Δt

sec

Figure 2.26-3 Gradient of frequency rate-of-change

(ii) Enabling DFRQ function


The user should set On to enable the DFRQ function using scheme switch [DFRQ1-EN]. If the
user is not to operate the DFRQ function, Off should be set for the scheme switch.

(iii) DFRQ trip signal


The DFRQ can issue a trip signal for the function of trip circuit (TRC) when Trip is set for
scheme switch [DFRQ1-UseFor]. However, when an alarm signal is required in place of the
trip signal, the user should set Alarm for scheme switch [DFRQ1-UseFor]. The TRC function
is discussed separately. (See Chapter Relay application: Trip circuit)

GRL200 (Soft 033 & 037)


- 339 -
6F2S1914 (0.37)

(iv) DFRQ scheme logic


Figure 2.26-4 shows the scheme logic of the DFRQ function. Each stage operates independently.
PLC connection point “DFRQ1-BLOCK” is provided to block the stage1; hence the user can
connect an external signal to this PLC connection point when the external signal is provided
to block the stage 1. (For more information of PLC function, see Chapter PLC function)

The signal of the under-voltage block (FRQBLK) element is provided from the FRQ logic.
From FRQ
NON FRQBLK

8000111BB1
8000111C23 8000111B60
& ≥1 & & 800011EBB1 FRQ-S1-OPT DFRQ-S1-OPT
RISE
DFRQ1 1
Trip To TRC
DOWN & ≥1
DFRQ1-UseFor
& Alarm DFRQ-OPT-TRIP
OverFrq &
UnderFrq
FFRQ1-Chara
DFRQ-OPT-ALARM
8100121C23 8100121B60 8100121BB1
& ≥1 & & 810012EBB1 FRQ-S2-OPT DFRQ-S2-OPT DFRQ-OPT-BLOCK
RISE
DFRQ2 1
Trip
DOWN &
DFRQ2-UseFor
& Alarm
OverFrq &
UnderFrq
DFRQ2-Chara

8500161BB1
8500161C23 8500161B60
RISE & ≥1 & & 850016EBB1 FRQ-S6-OPT DFRQ-S6-OPT
DFRQ6 1
Trip
DOWN &
DFRQ6-UseFor
& Alarm
OverFrq & ≥1
UnderFrq
DFRQ6-Chara

On
DFRQ1-EN
On
DFRQ2-EN

On
DFRQ6-EN

800011EBB0 DFRQ1-BLOCK 1

810012EBB0 DFRQ2-BLOCK 1

850016EBB0 DFRQ6-BLOCK 1

Figure 2.26-4 Scheme Logic of Frequency Rate-of-change Protection


(2.53.1)

GRL200 (Soft 033 & 037)


- 340 -
6F2S1914 (0.37)

2.26.3 Setting
FRQ(Function ID: 475001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
FRQ-EN Off / On - FRQ protection enable Off
FRQ FRQBLK 40.0 - 100.0 V Threshold to cancel FRQ operations 40.0
FRQ1-EN Off / On - FRQ1 protection enable Off
FRQ2-EN Off / On - FRQ2 protection enable Off
FRQ3-EN Off / On - FRQ3 protection enable Off
FRQ4-EN Off / On - FRQ4 protection enable Off
FRQ5-EN Off / On - FRQ5 protection enable Off
FRQ6-EN Off / On - FRQ6 protection enable Off
DFRQ1-EN Off / On - DFRQ1 protection enable Off
DFRQ2-EN Off / On - DFRQ2 protection enable Off
DFRQ3-EN Off / On - DFRQ3 protection enable Off
DFRQ4-EN Off / On - DFRQ4 protection enable Off
DFRQ5-EN Off / On - DFRQ5 protection enable Off
DFRQ6-EN Off / On - DFRQ6 protection enable Off
FRQ1 FRQ1-Chara OverFrq / UnderFrq - The selection of FRQ1 character UnderFrq
FRQ1 -10.00 - 10.00 Hz FRQ1 threshold -1.00
TFRQ1 0.00 - 300.00 s FRQ1 operating delay time 1.00
Output FRQ1-UseFor Trip / Alarm - FRQ1 used for trip or alarm Trip
FRQ2 FRQ2-Chara OverFrq / UnderFrq - The selection of FRQ2 character UnderFrq
FRQ2 -10.00 - 10.00 Hz FRQ2 threshold -1.00
TFRQ2 0.00 - 300.00 s FRQ2 operating delay time 1.00
Output FRQ2-UseFor Trip / Alarm - FRQ2 used for trip or alarm Trip
FRQ3 FRQ3-Chara OverFrq / UnderFrq - The selection of FRQ3 character UnderFrq
FRQ3 -10.00 - 10.00 Hz FRQ3 threshold -1.00
TFRQ3 0.00 - 300.00 s FRQ3 operating delay time 1.00
Output FRQ3-UseFor Trip / Alarm - FRQ3 used for trip or alarm Trip
FRQ4 FRQ4-Chara OverFrq / UnderFrq - The selection of FRQ4 character UnderFrq
FRQ4 -10.00 - 10.00 Hz FRQ4 threshold -1.00
TFRQ4 0.00 - 300.00 s FRQ4 operating delay time 1.00
Output FRQ4-UseFor Trip / Alarm - FRQ4 used for trip or alarm Trip
FRQ5 FRQ5-Chara OverFrq / UnderFrq - The selection of FRQ5 character UnderFrq
FRQ5 -10.00 - 10.00 Hz FRQ5 threshold -1.00
TFRQ5 0.00 - 300.00 s FRQ5 operating delay time 1.00
Output FRQ5-UseFor Trip / Alarm - FRQ5 used for trip or alarm Trip
FRQ6 FRQ6-Chara OverFrq / UnderFrq - The selection of FRQ6 character UnderFrq
FRQ6 -10.00 - 10.00 Hz FRQ6 threshold -1.00
TFRQ6 0.00 - 300.00 s FRQ6 operating delay time 1.00
Output FRQ6-UseFor Trip / Alarm - FRQ6 used for trip or alarm Trip
DFRQ1 DFRQ1-Chara Rise / Down - The selection of DFRQ1 character Down
DFRQ1 0.1 - 15.0 Hz/s DFRQ1 threshold 0.5
Output DFRQ1-UseFor Trip / Alarm - DFRQ1 used for trip or alarm Trip
DFRQ2 DFRQ2-Chara Rise / Down - The selection of DFRQ2 character Down
DFRQ2 0.1 - 15.0 Hz/s DFRQ2 threshold 0.5
Output DFRQ2-UseFor Trip / Alarm - DFRQ2 used for trip or alarm Trip
DFRQ3 DFRQ3-Chara Rise / Down - The selection of DFRQ3 character Down
DFRQ3 0.1 - 15.0 Hz/s DFRQ3 threshold 0.5
Output DFRQ3-UseFor Trip / Alarm - DFRQ3 used for trip or alarm Trip
DFRQ4 DFRQ4-Chara Rise / Down - The selection of DFRQ4 character Down
DFRQ4 0.1 - 15.0 Hz/s DFRQ4 threshold 0.5
Output DFRQ4-UseFor Trip / Alarm - DFRQ4 used for trip or alarm Trip
DFRQ5 DFRQ5-Chara Rise / Down - The selection of DFRQ5 character Down
DFRQ5 0.1 - 15.0 Hz/s DFRQ5 threshold 0.5

GRL200 (Soft 033 & 037)


- 341 -
6F2S1914 (0.37)

FRQ(Function ID: 475001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Output DFRQ5-UseFor Trip / Alarm - DFRQ5 used for trip or alarm Trip
DFRQ6 DFRQ6-Chara Rise / Down - The selection of DFRQ6 character Down
DFRQ6 0.1 - 15.0 Hz/s DFRQ6 threshold 0.5
Output DFRQ6-UseFor Trip / Alarm - DFRQ6 used for trip or alarm Trip

GRL200 (Soft 033 & 037)


- 342 -
6F2S1914 (0.37)

2.26.4 Data ID
 Signal monitoring point
FRQ(Function ID: 475001)
Element ID Name Description
8400101B61 DFRQ-OPT-ALARM Alarm signal by DFRQ protection

8300101B23 DFRQ-OPT-TRIP Trip signal by DFRQ protection

8100111B61 DFRQ-S1-ALARM Alarm signal by DFRQ1 protection

8000111BB1 DFRQ-S1-OPT DFRQ1 protection operated

8000111B23 DFRQ-S1-TRIP Trip signal by DFRQ1 protection

8100121B61 DFRQ-S2-ALARM Alarm signal by DFRQ2 protection

8100121BB1 DFRQ-S2-OPT DFRQ2 protection operated

8000121B23 DFRQ-S2-TRIP Trip signal by DFRQ2 protection

8100131B61 DFRQ-S3-ALARM Alarm signal by DFRQ3 protection

8200131BB1 DFRQ-S3-OPT DFRQ3 protection operated

8000131B23 DFRQ-S3-TRIP Trip signal by DFRQ3 protection

8100141B61 DFRQ-S4-ALARM Alarm signal by DFRQ4 protection

8300141BB1 DFRQ-S4-OPT DFRQ4 protection operated

8000141B23 DFRQ-S4-TRIP Trip signal by DFRQ4 protection

8100151B61 DFRQ-S5-ALARM Alarm signal by DFRQ5 protection

8400151BB1 DFRQ-S5-OPT DFRQ5 protection operated

8000151B23 DFRQ-S5-TRIP Trip signal by DFRQ5 protection

8100161B61 DFRQ-S6-ALARM Alarm signal by DFRQ6 protection

8500161BB1 DFRQ-S6-OPT DFRQ6 protection operated

8000161B23 DFRQ-S6-TRIP Trip signal by DFRQ6 protection

8000111C23 DFRQ1 DFRQ1 relay element operated

8000111B60 DFRQ1-OPT DFRQ1 element operated

8000111BB0 DFRQ1_BLOCK DFRQ1 protection block command

8100121C23 DFRQ2 DFRQ2 relay element operated

8100121B60 DFRQ2-OPT DFRQ2 element operated

8100121BB0 DFRQ2_BLOCK DFRQ2 protection block command

8200131C23 DFRQ3 DFRQ3 relay element operated

8200131B60 DFRQ3-OPT DFRQ3 element operated

8200131BB0 DFRQ3_BLOCK DFRQ3 protection block command

8300141C23 DFRQ4 DFRQ4 relay element operated

8300141B60 DFRQ4-OPT DFRQ4 element operated

8300141BB0 DFRQ4_BLOCK DFRQ4 protection block command

8400151C23 DFRQ5 DFRQ5 relay element operated

8400151B60 DFRQ5-OPT DFRQ5 element operated

8400151BB0 DFRQ5_BLOCK DFRQ5 protection block command

8500161C23 DFRQ6 DFRQ6 relay element operated

8500161B60 DFRQ6-OPT DFRQ6 element operated

8500161BB0 DFRQ6_BLOCK DFRQ6 protection block command

8400001B61 FRQ-OPT-ALARM Alarm signal by FRQ protection

8300001B23 FRQ-OPT-TRIP Trip signal by FRQ protection

8100011B61 FRQ-S1-ALARM Alarm signal by FRQ1 protection

8000011BB1 FRQ-S1-OPT FRQ1 protection operated

8000011B23 FRQ-S1-TRIP Trip signal by FRQ1 protection

GRL200 (Soft 033 & 037)


- 343 -
6F2S1914 (0.37)

 Signal monitoring point


FRQ(Function ID: 475001)
Element ID Name Description
8100021B61 FRQ-S2-ALARM Alarm signal by FRQ2 protection

8100021BB1 FRQ-S2-OPT FRQ2 protection operated

8000021B23 FRQ-S2-TRIP Trip signal by FRQ2 protection

8100031B61 FRQ-S3-ALARM Alarm signal by FRQ3 protection

8200031BB1 FRQ-S3-OPT FRQ3 protection operated

8000031B23 FRQ-S3-TRIP Trip signal by FRQ3 protection

8100041B61 FRQ-S4-ALARM Alarm signal by FRQ4 protection

8300041BB1 FRQ-S4-OPT FRQ4 protection operated

8000041B23 FRQ-S4-TRIP Trip signal by FRQ4 protection

8100051B61 FRQ-S5-ALARM Alarm signal by FRQ5 protection

8400051BB1 FRQ-S5-OPT FRQ5 protection operated

8000051B23 FRQ-S5-TRIP Trip signal by FRQ5 protection

8100061B61 FRQ-S6-ALARM Alarm signal by FRQ6 protection

8500061BB1 FRQ-S6-OPT FRQ6 protection operated

8000061B23 FRQ-S6-TRIP Trip signal by FRQ6 protection

8000011C23 FRQ1 FRQ1 relay element operated

8000011B60 FRQ1-OPT FRQ1 element operated

8000011BB0 FRQ1_BLOCK FRQ1 protection block command

8100021C23 FRQ2 FRQ2 relay element operated

8100021B60 FRQ2-OPT FRQ2 element operated

8100021BB0 FRQ2_BLOCK FRQ2 protection block command

8200031C23 FRQ3 FRQ3 relay element operated

8200031B60 FRQ3-OPT FRQ3 element operated

8200031BB0 FRQ3_BLOCK FRQ3 protection block command

8300041C23 FRQ4 FRQ4 relay element operated

8300041B60 FRQ4-OPT FRQ4 element operated

8300041BB0 FRQ4_BLOCK FRQ4 protection block command

8400051C23 FRQ5 FRQ5 relay element operated

8400051B60 FRQ5-OPT FRQ5 element operated

8400051BB0 FRQ5_BLOCK FRQ5 protection block command

8500061C23 FRQ6 FRQ6 relay element operated

8500061B60 FRQ6-OPT FRQ6 element operated

8500061BB0 FRQ6_BLOCK FRQ6 protection block command

8700001C23 FRQBLK FRQBLK relay element operated

 Connection point in PLC logic


FRQ(Function ID: 475001)
Element ID Name Description
800001EBB0 FRQ1_BLOCK FRQ1 protection block command

800001EBB1 FRQ-S1-OPT FRQ1 protection operated

800011EBB0 DFRQ1_BLOCK DFRQ1 protection block command

800011EBB1 DFRQ-S1-OPT DFRQ1 protection operated

810002EBB0 FRQ2_BLOCK FRQ2 protection block command

810002EBB1 FRQ-S2-OPT FRQ2 protection operated

GRL200 (Soft 033 & 037)


- 344 -
6F2S1914 (0.37)

 Connection point in PLC logic


FRQ(Function ID: 475001)
Element ID Name Description
810012EBB0 DFRQ2_BLOCK DFRQ2 protection block command

810012EBB1 DFRQ-S2-OPT DFRQ2 protection operated

820003EBB0 FRQ3_BLOCK FRQ3 protection block command

820003EBB1 FRQ-S3-OPT FRQ3 protection operated

820013EBB0 DFRQ3_BLOCK DFRQ3 protection block command

820013EBB1 DFRQ-S3-OPT DFRQ3 protection operated

830004EBB0 FRQ4_BLOCK FRQ4 protection block command

830004EBB1 FRQ-S4-OPT FRQ4 protection operated

830014EBB0 DFRQ4_BLOCK DFRQ4 protection block command

830014EBB1 DFRQ-S4-OPT DFRQ4 protection operated

840005EBB0 FRQ5_BLOCK FRQ5 protection block command

840005EBB1 FRQ-S5-OPT FRQ5 protection operated

840015EBB0 DFRQ5_BLOCK DFRQ5 protection block command

840015EBB1 DFRQ-S5-OPT DFRQ5 protection operated

850006EBB0 FRQ6_BLOCK FRQ6 protection block command

850006EBB1 FRQ-S6-OPT FRQ6 protection operated

850016EBB0 DFRQ6_BLOCK DFRQ6 protection block command

850016EBB1 DFRQ-S6-OPT DFRQ6 protection operated

GRL200 (Soft 033 & 037)


- 345 -
6F2S1914 (0.37)

Out of step tripping by voltage (OSTV)


Certain power disturbance may cause the loss of synchronism between terminal ends. When
the loss occurs, the disturbance should be separated from the power system promptly. The
function of out-of-step-tripping by voltage (OSTV) can detect such fault; and the detection is
done by comparing the voltages at the terminals.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have out of step tripping features. To determine whether
the features are implemented in the IED or not, locate the IED ordering number; and check
the order number at “G&T position” referring to the comparison table below. For more
information, see Appendix: Ordering.
Table 2.27-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
OSTV Out of step tripping by voltage ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 346 -
6F2S1914 (0.37)

2.27.1 Operation characteristic


Two elements are provided to detect an out-of-step condition. Figure 2.27-1 shows the operation
principle of the OSTV function. Reference voltage (VA) is acquired in IED A at terminal A; and
a corresponding voltage (VB) is acquired in IED B at terminal B. Using the telecommunication1
voltage data at both terminals are provided to the respective opposite terminals. Electrical
center is located at which the respective impedances for respective terminals are equal.

Electrical center

VA

ZA ZL ZB

Terminal A VB Terminal B
Data of VB
IED A IED B
Data of VA
Telecommunication

Left impedance Right impedance


(ZA +ZL +ZB)/2 (ZA +ZL +ZB)/2

Figure 2.27-1 Typical impedance and electrical center


1Note: The data is transferred by the function of ‘Communication application’. For more
information, see Chapter Relay application: Communication application.

Figure 2.27-2 is the characteristic of the OSTV-1 element. Phasor VB will exist in the
second quadrant (α-zone) or the third quadrant (β-zone) if the out-of-step state is appeared.
This is because a reference voltage is obtained at terminal A.

-zone
VB

1V
VA

-zone

Figure 2.27-2 Voltage phase comparison between terminal A and terminal B (OSTV-1)

GRL200 (Soft 033 & 037)


- 347 -
6F2S1914 (0.37)

Another OSTV element (OSTV-2) is provided when the protection is carried out by three
IEDs. The characteristic of the OSTV-2 element is the same as the characteristic of the OSTV-
1 element.

Note that to detect the state of out-of-step, phasor VB should stay at each quadrant for
the setting time (1.5 cycles). This is because that the influence of any VT transient should be
cancelled. The voltages in positive-sequence are used for the calculation of the OSTV function;
and when amplitudes are larger than 1V, the operation of the OSTV function is valid.

-zone
VC

1V
VA

-zone

Figure 2.27-3 Voltage phase comparison between terminal A and terminal C (OSTV-2)

GRL200 (Soft 033 & 037)


- 348 -
6F2S1914 (0.37)

2.27.2 Scheme logic and settings


Figure 2.27-4 shows the scheme logic of the OSTV function. The user should set scheme switch
[OSTV-EN] On when the OSTV function is required to operate. The user should note that the
OSTV function should operate together multi-level overcurrent elements (OCMFS), which is
provided in the Failsafe function (FS. For more information of FS, see Chapter Relay
application: Fail safe).
8000011C23 8200001B61
t 0
α OSTV-OPT
OSTV-1 ≥1 ≥1 & & ≥1 To TRC
β 0.1s OSTV-OPT-TRIP
8100021C23
OSTV-ARC-BLOCK
α
OSTV-2 ≥1 &
β

OSTV-EN
On
Trip
OSTV-Output
1 BO
800000EBB0 OSTV BLOCK
From FS
OCMFS_OP_SEP

Figure 2.27-4 OSTV logic

The signal output of the OSTV function is directed by the scheme switch [OSTV-Output].
When BO is set for [OSTV-Output], the OSTV signal is issued for the binary output circuit of
binary IO modules (BIO1). Conversely, when Trip is set for the [OSTV-Output], the OSTV signal
is issued for the trip circuit (TRC2).

1Note: For more information about the binary output circuit, see Chapter Technical
description: Binary IO module.
2Note: The TRC function is discussed separately. See Chapter Relay application: Trip
circuit.

The can use PLC connection point ‘OSTV_BLOCK’ to program blocking the operation of
the OSTV function, if the user wishes to stop the operation by receiving an external signal.

GRL200 (Soft 033 & 037)


- 349 -
6F2S1914 (0.37)

2.27.3 Setting
OSTV(Function ID: 479001)
Setting items Range Unit Contents Default Note

OSTV OSTV-EN Off / On - OSTV protection scheme swtich Off


OSTV-Output Trip / BO - OSTV trip signal output position Trip

GRL200 (Soft 033 & 037)


- 350 -
6F2S1914 (0.37)

2.27.4 Data ID
 Signal monitoring point
OSTV(Function ID: 479001)
Element ID Name Description
8000001B60 OSTV OSTV protection operated

8000001BB0 OSTV BLOCK OSTV detect block

8000011C23 OSTV-1 OSTV-1 relay element operated

8100021C23 OSTV-2 OSTV-2 relay element operated

8200031C23 OSTV-3 OSTV-3 relay element operated

8300041C23 OSTV-4 OSTV-4 relay element operated

8200001B61 OSTV-OPT OSTV protection block command

8300001B23 OSTV-OPT-TRIP OSTV-OPT-TRIP scheme operated

 Connection point on PLC logic


OSTV(Function ID: 479001)
Element ID Name Description
800000EBB0 OSTV BLOCK OSTV detect block

GRL200 (Soft 033 & 037)


- 351 -
6F2S1914 (0.37)

Inrush current detection function (ICD)


When a current transformer (CT) is first energized, an inrush current flows into the CT
transiently to establish the magnetic field. The magnitude of the inrush current can greater
than the full load current so much; thus, the protection function can issue trip signals falsely.
That is, the inrush current is required to detected and the protection functions shall not
operate during CT energizing. Inrush current detection (ICD) function is designed to detect a
second harmonic inrush current. This is because, the inrush current has all order of harmonics,
but the second harmonics is the greatest†. Signals generated in the ICD function are
transferred to other protection functions to block their operations.

†Note:The second harmonic current is present all inrush currents in three-phases. The
proportion of the second harmonic current varies with the degree of the
energizing, but the ratio of the second harmonic current to the fundamental
current can be about 20% or greater during energizing.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the “G&T position” referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 2.28-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
ICD Inrush current detection function (ICD) ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 352 -
6F2S1914 (0.37)

2.28.1 Operation and characteristic


The ICD function examines the ratio of a second harmonic current (I2f) to the fundamental
current (I1f) in each phase. If the ratio|I2f |⁄|I1f | is larger than the setting [ICD-2f], the ICD
function is able to identify the presence of inrush currents. Figure 2.28-1 illustrates the
characteristic; the operation region is designated by the hatched area; the operation threshold
is set with the [ICD-OC].
I2f
ICD-2f (%) = tanθ×100

|I2f|/|I1f|ICD-2f(%) & ICD

|I1f|ICD–OC

I1f
0 ICD–OC

Figure 2.28-1 ICD characteristic and operation region

As shown in Figure 2.28-1, the user should set both the [ICD-2f] and [ICD-OC] when the
second harmonic inrush current should be detected. The user should set On for the scheme
switch [ICD-EN] to enable the ICD operation.

2.28.2 Scheme logic


Figure 2.28-2 illustrates the ICD logic. When second harmonic inrush current is detected, the
ICD signal will be received by other protection functional elements.

8000011C20 To OC, SOTF-OC, STUB-OC


A ICD-A
8100011C21
ICD B ICD-B
8200011C22
C
ICD-C

To EF, OCN, BCD


8000011C24
≥1 ICD-OR

Figure 2.28-2 ICD logic

GRL200 (Soft 033 & 037)


- 353 -
6F2S1914 (0.37)

2.28.3 Setting
ICD(Function ID: 480001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ICD-EN Off / On - ICD function scheme switch Off
ICD-2f 10 - 50 % Sensitivity of 2f 15
0.10 - 0.50 -
ICD-OC A Threshold of fundamental current 0.50 2.50
5.00 25.00

2.28.4 Data ID
 Signal monitoring point
ICD(Function ID: 480001)
Element ID Name Description
8000001C20 ICD-A ICD relay element operated (phase-A)

8100001C21 ICD-B ICD relay element operated (phase-B)

8200001C22 ICD-C ICD relay element operated (phase-C)

8300001C23 ICD-OR ICD relay element operated (3-phases OR)

GRL200 (Soft 033 & 037)


- 354 -
6F2S1914 (0.37)

Fail safe (FS)


Various protection functions are connected to trip function, which opens circuit breakers. The
operation of the trip function should be reliable enough to function correctly, for which the
function of fail-safe (FS) is provided. The Fail safe function includes overcurrent element
(OCFS), phase current change detector element (OCDFS), earth fault element (EFF), multi-
level overcurrent element (OCMF), under-voltage element for phase-to-ground (UVF), under-
voltage element for phase-to-phase fault (UVSF), and under-voltage change detection element
(UVDF). Each element has a scheme switch, and the scheme switch disables the element
independently. As a rule, the FS uses the OCFS. However, for the function of out of step
tripping (OST), the FS can use the OCMF. The OST is discussed separately. (See Chapter Relay
application: Out of step tripping) (2.60.0)

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have fail-safe features. To determine whether the features
are implemented in the IED or not, locate the IED ordering number; and check the order
number at “G&T position” referring to the comparison table below. For more information, see
Appendix: Ordering.
Table 2.29-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
FS Fail-safe function (FS) ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 355 -
6F2S1914 (0.37)

2.29.1 Overcurrent element (OCFS)


This function consists of overcurrent elements for the three-phases, that is, OCFS-A, OCFS-B,
and OCFS-C. The pickup value of the OCFS is set by setting [OCFS]; the OCFS can operate
by setting On for the scheme switch [OCFS-EN].

2.29.2 Phase current change detector element (OCDFS)


This function is used to detect the change in current per phase, and the OCDFS consists
elements for the three-phases, that is, OCDFS-A, OCDFS-B, and OCDFS-C. As shown in
Figure 2.29-1, the OCDFS operates when the vectorial difference between currents IM and IN
observed is one cycle apart which is larger than the setting [OCDFS]. Therefore, the quiescent
load current does not affect the operating sensitivity of the OCDFS element, and the OCDFS
can detect a fault current precisely.

IN
Is

IM

Figure 2.29-1 Current change detection

The operation is based on the following equation.

|𝐼𝑀 − 𝐼𝑁 | ≥ 𝐼𝑆 (2.29-1)

where,
IM = present current
IN = current one cycle before
Is = setting [OCDFS]

The setting of the OCDFS is set by setting [OCDFS]; the OCDFS can operate by setting On for
the scheme switch [OCDFS-EN]. Additionally, the OCDFS has off-delay timers and setting
[TOCDFS] is provided to adjust the timers.

2.29.3 Earth fault current element (EFFS)


The EFFS measures the residual current, and when the residual current exceeds a setting
level, the EFFS signals the detection of earth fault. The setting level of the EFFS is set by
setting [EFFS]. The EFFS operates when On is set for the scheme switch [EFFS-EN].

If the earth fault current is significant, because of unbalance in the network, the scheme

GRL200 (Soft 033 & 037)


- 356 -
6F2S1914 (0.37)

switch [EFFS-EN] should disable the operation of the EFFS.

2.29.4 Multi-level overcurrent elements (OCMFS)


(i) Characteristic of OCMFS
As a current may fluctuate during out of step conditions, seven overcurrent elements are
provided for the FS, and are placed at multiple levels.

LD7
LD6
LD5
LD4
LD3
LD2
LD1
I
0

D.O./P.U.=0.8

Figure 2.29-2 OCMF characteristics

As shown in Figure 2.29-2, the OCMFS has seven current level detectors (LDs). The Table
2.29-2 shows the threshold between operation and resetting of seven detectors, and these
thresholds are fixed. The overcurrent elements (level detector LD1 to LD7) operate when a
current exceeds operation threshold and resets when the current falls below 80% of the
operation threshold.

GRL200 (Soft 033 & 037)


- 357 -
6F2S1914 (0.37)

Table 2.29-2 Level Detector Settings


1A rating 5A rating
Detector Operate (A) Reset (A) Operate (A) Reset (A)
LD1 0.10 0.08 0.50 0.40
LD2 0.16 0.13 0.80 0.65
LD3 0.26 0.21 1.30 1.05
LD4 0.41 0.33 2.05 1.65
LD5 0.66 0.53 3.30 2.65
LD6 1.05 0.84 5.25 4.20
LD7 1.68 1.34 8.40 6.70

The OCMFS operates in five seconds when any of the level detectors operate and reset
without time delay when all the level detectors reset, as shown in the Figure 2.29-4.

(ii) Setting of OCMF


As described earlier, the signal of the OCMF is usually used for the trip function. However,
with scheme switch [OCMFS-EN], the OCMF can feed its signal to the OST exclusively. When
On-T is set for the scheme switch [OCMFS-EN], the OCMF operates the trip function, whereas
the OCMF activates for the OST when On-S is set for the scheme switch [OCMSF-EN]. If the
OCMF has to be disabled, Off is set for the scheme switch [OCMSF-EN].

2.29.5 Under-voltage element for phase-to-earth (UVFS)


The UVFS measures a phase-to-earth voltage and its sensitivity is set with setting [UVFS].
The operation of the UVFS is initiated when the phase-to-earth voltage drops below the setting
and On is set for the setting [UVFS-EN].

2.29.6 Under-voltage element for phase-to-phase (UVSFS)


In UVSFS, when a phase-to-phase voltage is below setting [UVSFS], the UVSFS is initiated.
The setting [UVSFS] is enabled when On is set for the setting [UVSFS-EN].

2.29.7 Under-voltage change detection element (DUVFS)


This element operates if a voltage drops below a setting voltage compared to that of the
previous cycle. The sensitivity of the DUVFS is configured by setting [DUVFS]. In addition, the
DUVFS has off-delay timers and setting [TDUVFS] is provided to adjust the timers.

GRL200 (Soft 033 & 037)


- 358 -
6F2S1914 (0.37)

2.29.8 Scheme logic


Figure 2.29-3 and Figure 2.29-4 show the scheme logic of the FS. As described earlier, each
element has a scheme switch that can either enable or disable the operation. To disable FS,
Off is set for the scheme switch [FS-EN], then the trip circuit can operate regardless of the
result of the FS.

8C00011C20 8000011B60
A
8D00011C21 ≥1
OCFS B OCFS_OP
8E00011C22 &
C

OCFS-EN On

TOCDFS
8800021C20 0 t 8100021B60
A
8900021C21 ≥1
OCDFS B
0 t & OCDFS_OP
8A00021C22 0 t
C
0.00-300.00s

OCDFS-EN On

8000051C20 8800051B60
A
8100051C21 ≥1 UVFS_OP
UVFS B &
8200051C22
C

UVFS-EN On

8400061C20 8900061B60
A
8500061C21 ≥1
UVSFS B & UVSFS_OP
8600061C22
C

UVSFS-EN On

TDUVFS
8800071C20 8A00071B60
0 t
A
8900071C21 ≥1
DUVFS B 0 t & DUVFS_OP
8A00071C22
C 0 t

0.00-300.00s

DUVFS-EN On

Figure 2.29-3 Soft fail scheme logic (1)

GRL200 (Soft 033 & 037)


- 359 -
6F2S1914 (0.37)

8300041B60
8000041C60
L1 &
≥1 OCMFS_OP
&
8100041C61 &
L2

8200041C62 &
L3 & 8000041B61 To OSTZ
OCM
8300041C63 ≥1 OCMFS_OP_SEP
FS L4 &

8400041C64
L5 &

8500041C65
L6 &

L7 8600041C66
&
5s

On-T
On-S
OCMFS-EN
Off

FS-EN=OFF

8F00031C23
EFFS
& EFFS-OP
EFFS-EN On
-EN

Figure 2.29-4 Soft fail scheme logic (2)

To TRC
OCFS-OP 8000001B23
FSRY_OP
OCDFS_OP
UVFS-OP
UVSFS-OP
≥1
DUVFS-OP
OCMFS_OP
EFFS-OP

FS-EN Off FS-EN=OFF

Figure 2.29-5 Output signal of the FS


(2.60.1)

GRL200 (Soft 033 & 037)


- 360 -
6F2S1914 (0.37)

2.29.9 Setting
FS (Function ID: 48B001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
FS-EN Off / On - Fail safe scheme switch Off
OCFS-EN Off / On - OCFS scheme switch Off
OCDFS-EN Off / On - OCDFS scheme switch Off
EFFS-EN Off / On - EFFS scheme switch Off
OCMFS-EN Off / On-T / On-S - OCMFS scheme switch Off
UVFS-EN Off / On - UVFS scheme switch Off
UVSFS-EN Off / On - UVSFS scheme switch Off
DUVFS-EN Off / On - DUVFS scheme switch Off
OC 0.10 - 0.50 -
OCFS A OCFS relay operating value 1.00 5.00
50.00 250.00
OCD 0.05 - 0.25 -
OCDFS A OCDFS relay operating value 0.10 0.50
0.20 1.00
TOCDFS 0.00 - 300.00 s Extended time of OCDFS operating 10.10
EF 0.10 - 0.50 -
EFFS A EFFS relay operating value 0.20 1.00
50.00 250.00
UV UVFS 5.0 - 130.0 V UVFS relay operating value 46.0
UVS UVSFS 5.0 - 130.0 V UVSFS relay operating value 80.0
DUV DUVFS 1 - 20 V DUVFS relay operating value 5
TDUVFS 0.00 - 300.00 s Extended time of DUVFS operating 10.10

GRL200 (Soft 033 & 037)


- 361 -
6F2S1914 (0.37)

2.29.10 Data ID list


 Signal monitoring point
FS(Function ID: 48B001)
Element ID Name Description
8800071C20 DUVFS-A DUVFS relay element operated (phase-A)

8900071C21 DUVFS-B DUVFS relay element operated (phase-B)

8A00071C22 DUVFS-C DUVFS relay element operated (phase-C)

8A00071B60 DUVFS-OR DUVFS relay element operated (3-phase OR)

8F00031C23 EFFS EFFS relay element operated

8000001B23 FSRY_OP Fail Safe Relay open signal by Fail Safe

8800021C20 OCDFS-A OCDFS relay element operated (phase-A)

8900021C21 OCDFS-B OCDFS relay element operated (phase-B)

8A00021C22 OCDFS-C OCDFS relay element operated (phase-C)

8100021B60 OCDFS-OR OCDFS relay element operated (3-phase OR)

8C00011C20 OCFS-A OCFS relay element operated (phase-A)

8D00011C21 OCFS-B OCFS relay element operated (phase-B)

8E00011C22 OCFS-C OCFS relay element operated (phase-C)

8000011B60 OCFS-OR OCFS relay element operated (3-phase OR)

8000041C60 OCMFS-L1 OCFS relay element operated (phase-L1)

8100041C61 OCMFS-L2 OCFS relay element operated (phase-L2)

8200041C62 OCMFS-L3 OCFS relay element operated (phase-L3)

8300041C63 OCMFS-L4 OCFS relay element operated (phase-L4)

8400041C64 OCMFS-L5 OCFS relay element operated (phase-L5)

8500041C65 OCMFS-L6 OCFS relay element operated (phase-L6)

8600041C66 OCMFS-L7 OCFS relay element operated (phase-L7)

8300041B60 OCMFS-OR OCMFS relay element operated (7-phase OR)

8000041B61 OCMFS_OP_SEP Fail Safe Relay open signal by OCMFS

8000051C20 UVFS-A UVFS relay element operated (phase-AB)

8100051C21 UVFS-B UVFS relay element operated (phase-BC)

8200051C22 UVFS-C UVFS relay element operated (phase-CA)

8800051B60 UVFS-OR UVFS relay element operated (3-phase OR)

8400061C20 UVSFS-AB UVSFS relay element operated (phase-A)

8500061C21 UVSFS-BC UVSFS relay element operated (phase-B)

8600061C22 UVSFS-CA UVSFS relay element operated (phase-C)

8900061B60 UVSFS-OR UVSFS relay element operated (3-phase OR)

GRL200 (Soft 033 & 037)


- 362 -
6F2S1914 (0.37)

VT failure detection (VTF)


If a failure occurs on the secondary circuit in the voltage transformer (VT), the operation in
relays cannot be obtained properly because the relays do not measure voltages correctly.
Therefore, the VT failure detection (VTF) function is provided to block operating the relays
upon occurrence of the VT failure. Accordingly, if a VT failure is detected by the VTF function,
an alarm signal is issued for the relays upon occurrence of the VT failure. Accordingly, an
alarm signal is issued if a VT failure is detected by the VTF function; a detection signal by the
VTF function blocks operating the relay for the voltage monitor 1.

After the disappearance of the VT failure, the VTF function can take account of the VT
secondary circuit being in healthy condition in the three-phase; the operation of the VTF
function is reset2. Thus, the blocked relays are allowed to operate again. Incidentally, issuing
the VTF alarm is automatically removed and then the user can find resetting the VTF alarm.

1Note: The VTF function can block the operation in several relays, but it does not block
the operation in other relays. To know the blocking, refer sections of the respective
protection functions.
2Note: The user can programmable the operation using the setting and the PLC signals.
(2.62.0)

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have VTF detection features. To determine whether the
features are implemented in the IED or not, locate the IED ordering number; and check the
order number at “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 2.30-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
VTF VTF detection (VTF) ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 363 -
6F2S1914 (0.37)

2.30.1 VTF features


The VTF function has three relay elements in order to decide the failure in the VT; hence two
criterions (i.e., for VTF1 and VTF2) exist to detect the failure in the VT.

(i) Phase-to-earth under voltage element (UVVTF)


For the VTF1 function, the under-voltage element (UVVTF) monitors the under voltage. The
threshold of the UVVTF relay is set using the [UVVTF].

(ii) Earth fault overcurrent element (EFVTF)


For the VTF2 function, the earth fault overcurrent element (EFVTF) monitors the overcurrent
in zero-sequence. The threshold of the EFVTF relay is set using the [EFVTF].

(iii) Earth fault overvoltage element (OVGVTF)


For the VTF2 function, the earth fault overvoltage element (OVGVTF) monitors the over
voltage in zero-sequence. The threshold of the OVGVTF relay is set the using [OVGVTF].

(iv) Detection criterion for the VTF1


The criterion for the VTF1 function is defined when the UVVTF relay operates whereas the
OCD relay does not operate.

(v) Detection criterion for the VTF2


The criterion for the VTF2 function is defined when both the EFVTF relay and the OCD relay
are not operated whereas the OVGVTF relay is operated.

2.30.2 Operation for the VTF function


When the VTF function detects the failure, issuing the VTF1_DETECT signal is continuing
regardless of the operation of the OCD relay, provided On is set for both the [VTF1EN] and the
[VTF2EN]. Issuing the VTF2_DETECT signal is also continuing regardless of the operation of
both the OCD and the EFVTF relays. Note that issuing the VTF_DETECT signal is cleared
when the operations of the UVVTF relay and the OVGVTF relay are reset.

However, nonetheless the OCD/EFVTF relay is still running after the VTF detection,
issuing the VTF_DETECT signal is cleared, provided OPT-On is set for the settings [VTF1-EN]
and the [VTF2EN].

When issuing the VTF_DETECT signal continues longer than ten seconds, the signal
VTF_DETCT clears to generate the VTF_ALARM signal.

GRL200 (Soft 033 & 037)


- 364 -
6F2S1914 (0.37)

2.30.3 VTF Logic


Figure 2.30-1 shows the logics of the VTF function. As described earlier, the VT failure is
grouped into the VTF1 criterion (VTF1_DETECT) and the VTF2 criterion (VTF2_DETECT).
When we consider the VTF1 criterion, the upper logic in Figure 2.30-1 is used; whereas we
consider the VTF2 criterion, lower one is used.

The user can select either the VTF1 or VTF2 criteria using the using the scheme switch
[VTF1EN] or [VTF2EN].
VTF1 DETECT
8000001C20
A &
8100011C60 8000001B61
≥1 ≥1 t 0
8100001C21 VTF1_ALARM
UVVTF B t 0
1 S
C 8200001C22 1 10.0s
t 0
0.015s ≥1
1 R
From PROT-CCOMMON1
0.1s
OCD-AT ≥1 S
OCD-BT
≥1
&
OCD-CT R

& 1

t 0
1 &
10.0s

On ≥1
VTF1-EN OPT-On

VTF2 DETECT
8800001C27
OVGVTF & 8200021C60 8200021C60
≥1 t 0 VTF2_ALARM
1 t 0
1 S 10.0s
8400001C28
t 0
0.015s ≥1
EFVTF 1 R
≥1 0.1s ≥1
S
800000B62
≥1 &
R VTF_ALARM

& To Automatic supervision


1

&

To OC3
On ≥1 To EF3
VTF2-EN OPT-On To UV3
To UVS3
To OV3
From PROT-COMMON1 To OVS3
To OVG3
To OVP3
CB_ALLPH_CLOSE 1 To OVN3
0. 2s To UVP3
1 To OCN3
From DISTANSE-ZS2 To CARRIER_DEF3
8000001B61 To DISTANCE-COMMON3
PSBS-VTF-BLK ≥1 ≥1
VTF_DETECT
From DISTANSE-ZG2
PSBG-VTF-BLK

From test

AMF_OFF 1

800000EBB0 VTF_BLOCK
8100001BB1
810000EBB1 EXTERNAL_VTF

Figure 2.30-1 Scheme logic in the VTF function


1Note: Signal CB_ALLPH_CLOSE is provided from Protection common function
(PROT_COMMON). The OCD relay is used for both the VTF1 DETECT and the
VTF2 DETECT. For more information, see Chapter Relay application: Protection
common.
2Note: Entering signals coming from distance protections (ZS/ZG) are available if the
ZS/ZG protections are provided in the IED. For more information with regard to

GRL200 (Soft 033 & 037)


- 365 -
6F2S1914 (0.37)

the ZS/ZG protections, see Chapter Relay application: Distance protection, when
available.
3Note: Output signals are provided for respective relays when the relays are available.
See Appendix: Ordering whether the relays are supplied into the IED.
4Note: AMF feature is used for the test. To generate the AMF signal, see chapter User
interface: test-submenu.

If a PLC signal is injected at the PLC connection point “VTF_BLOCK”, the operation of
the VTF function is blocked. The user can program to inject an external signal for the failure
detection using the PLC connection point EXTERNAL_VTF; the VTF_DETECT signal is
generated when the signal is injected at the EXTERNAL_VTF. (2.62.1)

GRL200 (Soft 033 & 037)


- 366 -
6F2S1914 (0.37)

2.30.4 Setting
VTF(Function ID: 490001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
VTF1 VTF1-EN Off / On / OPT-On - VTF1 scheme switch On
UVVTF 1.0 - 220.0 V Phase under voltage revel for VTF1 detection 20.0
VTF2 VTF2-EN Off / On / OPT-On - VTF2 scheme switch On
Threshold of over voltage detection in zero-
OVGVTF 1.0 - 220.0 V 20.0
sequence phase
0.10 - 0.50 - Threshold of over current in zero-sequence
EFVTF A 0.20 1.00
50.00 250.00 phase to block VTF2 detection

GRL200 (Soft 033 & 037)


- 367 -
6F2S1914 (0.37)

2.30.5 Data ID
 Signal monitoring point
VTF(Function ID: 490001)
Element ID Name Description
8400001C2B EFVTF EFVTF relay element operated

8100001BB1 EXTERNAL VTF External VTF receive

8800001C27 OVGVTF OVGVTF relay element operated

8000001C20 UVVTF-A UVVTF relay element operated(Phase-A)

8100001C21 UVVTF-B UVVTF relay element operated(Phase-B)

8200001C22 UVVTF-C UVVTF relay element operated(Phase-C)

8100001B60 UVVTF-OR UVVTF relay element operated (3-phases OR)

8000001B62 VTF ALARM VTF alarm (VTF1 ALARM/VTF2 ALARM OR)

8000001BB0 VTF BLOCK VTF block signal

8000001B61 VTF DETECT VTF detected (VTF1 DET/VTF2 DET OR)

8100011C61 VTF1 ALARM VTF1 alarm (10s timer)

8100011C60 VTF1 DET VTF1 detected

8200021C61 VTF2 ALARM VTF2 alarm (10s timer)

8200021C60 VTF2 DET VTF2 detected

 Connection point on PLC logic


VTF(Function ID: 490001)
Element ID Name Description
810000EBB1 EXTERNAL VTF External VTF receive

800000EBB0 VTF BLOCK VTF block signal

GRL200 (Soft 033 & 037)


- 368 -
6F2S1914 (0.37)

CT failure detection (CTF)


If a failure occurs on the secondary circuit in the current transformer (CT), the operation in
relays cannot be obtained properly because the relays do not measure incoming currents
correctly. Therefore, the CT failure detection (CTF) function is provided to block operating the
relays1 upon occurrence of the CT failure. Accordingly, an alarm signal is issued if a CT failure
is detected by the CTF function; a detection signal by the CTF function blocks operating the
relay for the current monitor1.

After the disappearance of the CT failure, the CTF function can take account of the CT
secondary circuit being in healthy condition in the three-phase; the operation of the CTF
function is reset2. Thus, the blocked relays are allowed to operate again. Incidentally, issuing
the CTF alarm is automatically removed and then the user can find resetting the CTF alarm.

1Note: The CTF function can block the operation in several relays, but it does not block
the operation in other relays. To know the blocking, refer sections of the respective
protection functions.
2Note: The user can programmable the operation using the setting and the PLC signals.
(2.63.0)

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have CTF detection features. To determine whether the
features are implemented in the IED or not, locate the IED ordering number; and check the
order number at “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 2.31-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
CTF CTF detection (CTF) ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 369 -
6F2S1914 (0.37)

2.31.1 CTF features


The CTF function has two relay elements in order to decide the failure in the CT; hence two
criterions exist to detect the failure in the CT in the CTF function.

(i) Earth fault overcurrent element (EFCTF)


The earth fault overcurrent element (EFCTF) monitors the zero-sequence current for the
failure in the CT. The threshold of the EFCTF element is set using the [EFCTF].

(ii) Earth fault overvoltage element (OVGCTF)


The earth fault overvoltage element (OVGCTF) monitors the zero-sequence voltage for the
failure in the CT. The OVGCTF element is set using the [OVGCTF].

(iii) Detection criterion (CTF_DETECT)


When the EFCTF element operates whereas the OVGCTF element does not operate, the
detection criterion (CTF_DETECT) is applied.

2.31.2 Operation for the CTF function


When the CTF function detects the failure, issuing the CTF_DETECT signal is continuing
regardless of the operation of the OVGCTF relay, provided On is set for the scheme switch
[CTF-EN]. Issuing the CTF _DETECT is continued until the operation of the EFCTF relay is
reset.

However, nonetheless the OVGCTF relay is still running after the CTF detection, issuing
the CTF_DETECT signal is cleared, provided OPT-On is set for the scheme switch [CTF-EN].

When issuing the CTF_DETECT signal continues longer than ten seconds, the signal
CTF_DETECT clears to generate the CTF_ALARM signal.

2.31.3 Scheme logic


Figure 2.31-1 shows the logic of the CTF function. CTF_DET signal is issued when the EFCTF
element is running and the OVGCTF element is not running.

GRL200 (Soft 033 & 037)


- 370 -
6F2S1914 (0.37)

8000001C23
EFCTF
&
1 8100001B60 8000001B61
≥1 t 0
CTF_ALARM
t 0
S
10.0s To Automatic supervision
t 0
0.015s ≥1
8100001C27 1 R
OVGCTF & 0.1s

On ≥1
CTF-EN OPT-On

& 1
From PROT-CCOMMON1

CB_ALLPH_CLOSE 1 To EF3

0.02s To BCD3
To OCN3
From DISTANSE-ZS2
8000001B62
PSBS-VCTF-BLK ≥1
1 ≥1
CTF_DETECT
From DISTANSE-ZG2
PSBG-VCTF-BLK

From test4

AMF_OFF 1

800000EBB0 CTF_BLOCK
8100001BB1

810000EBB1 EXTERNAL_CTF

Figure 2.31-1 Scheme logic in the CTF function


1Note: Signal CB_ALLPH_CLOSE is provided from Protection common function
(PROT_COMMON). For more information, see Chapter Relay application:
Protection common.
2Note: Entering signals come from distance protections (ZS/ZG) when the ZS/ZG are
available in the IED. For more information, see Chapter Relay application:
Distance protection.
3Note: Output signals are provided for respective relays when the relays are available.
See Appendix: Ordering whether the relays are supplied into the IED.
4Note: AMF feature is used for the test. To generate the AMF signal, see chapter User
interface: test-submenu.

If a PLC signal is injected at the PLC connection point “CTF_BLOCK”, the operation of
the CTF function is blocked. The user can program to inject an external signal for the failure
detection using the PLC connection point EXTERNAL_CTF; the CTF_DETECT signal is
generated when the signal is injected at the EXTERNAL_CTF.

GRL200 (Soft 033 & 037)


- 371 -
6F2S1914 (0.37)

2.31.4 Setting
CTF(Function ID: 491001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
CTF-EN Off / On / OPT-On - CTF scheme switch On
CTF Threshold of overvoltage in zero-sequence
OVGCTF 1.0 - 220.0 V 20.0
phase to stop CTF detection
0.10 - 0.50 - Threshold of overcurrent in zero-sequence
EFCTF A 0.20 1.00
50.00 250.00 phase to have CTF detection

GRL200 (Soft 033 & 037)


- 372 -
6F2S1914 (0.37)

2.31.5 Data ID
 Signal monitoring point
CTF(Function ID: 491001)
Element ID Name Description
8000001B61 CTF ALARM CTF alarm operated

8000001BB0 CTF BLOCK CTF block operated

8100001B60 CTF DET CTF det

8000001B62 CTF DETECT CTF detect

8000001C23 EFCTF EFCTF relay element operated

8100001BB1 EXTERNAL CTF External CTF receive

8100001C27 OVGCTF OVGCTF relay element operated

 Connection point in PLC logic


CTF(Function ID: 491001)
Element ID Name Description
800000EBB0 CTF BLOCK CTF block signal

810000EBB1 EXTERNAL CTF External CTF receive

GRL200 (Soft 033 & 037)


- 373 -
6F2S1914 (0.37)

Multi-end fault locator (FL-A and FL-Z)


The function of multi-end fault locator (FL) can determine a fault location on lines with high
reliability; it is useful in case of power system failure. The following two calculations run in
the FL; then the FL selects one of the calculation results to provide a fault location.
(1) FL calculation with data at a local-terminal and remote-terminals
(2) FL calculation with data at a local-terminal only

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have fault locator features. To determine whether the
features are implemented in the IED or not, locate the IED ordering number; and check the
order number at “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 2.32-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
FL-Z Fault locator (21FL) ✓ ✓
FL-A Fault locator (FL) ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 374 -
6F2S1914 (0.37)

2.32.1 FL calculation with data at a local-terminal and remote-terminals


When considering the FL calculation with data at a local-terminal and remote-terminals, user
should note the computation requires minimum two-cycles of fault continuing time. The FL
result includes calculation errors: fixed error and proportional error. The fixed error is because
of the arithmetic error, but the proportional error is because of the settings in Segregated-
current-differential protection1 (DIFL) function. The proportional error corresponds to the
setting2 [DIFL-I1], but this error is inversely proportional to the differential current2 (Id).

The FL calculation requires data of voltages and currents at a local-terminal and remote-
terminals. The FL does not calculate for a switch-onto-fault or for a fault when the line
energizes from one terminal and the other terminal is out-of-service.

When user considers the FL calculation in three-terminal application, if one of the three-
terminal is out-of-service, and when a fault arises between the junction and the out-of-service
terminal, the FL calculation assumes this fault being at the junction.

1Note: For more information of the DIFL, see Chapter Relay application: Segregated
current differential protection
2Note: Setting [DIFL-I1] and differential current (Id) are discussed in the DIFL.

GRL200 (Soft 033 & 037)


- 375 -
6F2S1914 (0.37)

(i) Calculation Principle


Calculation on two-terminal application
Figure 2.32-1 shows two IEDs exist at the end of the line GH. Voltages due to the fault are
calculated by Equation (2.32-1) and Equation (2.32-2).
Bus G F Bus H
TT
TT
Fault
VG VH
IED G IG VfTT IH IED H
TT TT

ZGH
× ZGH (1−)× ZGH

Figure 2.32-1 IED G and IED H on line GH

𝑉𝐺 − χ ∙ Z𝐺𝐻 ∙ 𝐼𝐺 = 𝑉𝑓 (2.32-1)

𝑉𝐻 − (1 − χ) ∙ Z𝐺𝐻 ∙ 𝐼𝐻 = 𝑉𝑓 (2.32-2)

where,
VG: Voltage at IED G
IG:Current at IED G
VH: Voltage at IED H
IH: Current at IED H
χ: Distance ratio of GF to GH
Vf: Voltage at fault point
ZGH1: Impedance on line GH

Substituting Equation (2.32-1) for Equation (2.32-2) gives,


𝑉𝐺 − 𝑉𝐻 + Z𝐺𝐻 ∙ 𝐼𝐻
χ= (2.32-3)
Z𝐺𝐻 ∙ (𝐼𝐺 + 𝐼𝐻 )
The distance ratio (χ) is also calculated with the differential current (Id) because the net
currents at the IED G and the IED H are equal to the differential current (Id= IG+IH):
𝑉𝐺 − 𝑉𝐻 + Z𝐺𝐻 ∙ 𝐼𝐻
χ= (2.32-4)
Z𝐺𝐻 ∙ 𝐼𝑑
1Note: User should set the ZGH into Line1_Element. For further information, see section
2.32.5(ii). For setting methods, see section 2.32.6(iii).

Calculation on three-terminal application


The principle mentioned above is also applicable for the operation of three terminals, as shown
in Figure 2.32-2. Note that one of three calculations (Calc. 1 to 3) determines the fault location.

GRL200 (Soft 033 & 037)


- 376 -
6F2S1914 (0.37)

The three calculations are in sequence performed and a calculation result is selected from
them:
(Calc. 1) Calculation for a fault being as far as the junction (a fault on line GJ)
(Calc. 2) Calculation for a fault being beyond the junction (a fault on line JH)
(Calc. 3) Calculation for a fault being beyond the junction (a fault on line JS)

Bus G ZGJ Junction J ZJH Bus H


TT TT TT TT TT

VG VH
IED G IG IH IED H
TT
TT TT

F
TT ZJS

VS, IS
TT
IED S

Bus S

Figure 2.32-2 IED G, H, and S on lines with a junction and a fault on line JS
The FL in IED G makes calculation with the following equations:

𝑉𝐺 − 𝑉𝐻 + 𝑍GJ (𝐼𝐻 + 𝐼𝑆 ) + 𝑍𝐽𝐻 ∙ 𝐼𝐻


χ𝐺𝐽 = (2.32-5)
𝑍𝐺𝐽 ∙ 𝐼𝑑

𝑉𝐺 − 𝑉𝐻 + 𝑍𝐽𝐻 ∙ 𝐼𝐻 − 𝑍𝐺𝐽 ∙ 𝐼𝐺
χ𝐽𝐻 = (2.32-6)
𝑍𝐽𝐻 ∙ 𝐼𝑑

𝑉𝐺 − 𝑉𝑆 + 𝑍𝐽𝑆 ∙ 𝐼𝑆 − 𝑍𝐺𝐽 ∙ 𝐼𝐺
χ𝐽𝑆 = (2.32-7)
𝑍𝐽𝑆 ∙ 𝐼𝑑

I𝑑 = 𝐼𝐺 + 𝐼𝐻 + 𝐼𝑆 (2.32-8)

where,
VG, VH, VS: Voltage at IED G, IED H, and IED S
IG, IH, IS: Current at IED G, IED H, and IED S
χ GJ: Distance ratio of GF to GJ when a fault (F) arises on line GJ
χ JH: Distance ratio of JF to JH when a fault (F) arises on line JH
χ JS: Distance ratio of JF to JS when a fault (F) arises on line JS
ZGJ: Section impedance2 on line GJ
ZJH: Section impedance2 on line JH
ZJS: Section impedance2 on line JS

GRL200 (Soft 033 & 037)


- 377 -
6F2S1914 (0.37)

2Note: User should set the values of each section impedances into each Line_Element.
For the consideration of the section and their Line_Element, see section 2.32.5(i)
and section 2.32.6(iii).

For instance, the IED G makes calculation in the following sequences:


 At the outset, the IED G makes calculation of the equation (2.32-5) assuming that the fault
arises on line GJ.

 If the calculation result is not identical to the input data from a line, then the IED G makes
calculation with Equation (2.32-6) assuming that the fault arises on line JH.

 Then, the IED G makes calculation with Equation (2.32-7), when both Equation (2.32-5)
and Equation (2.32-6) do not hold true for the input data from a line, and finally the IED
G decides that the fault arises on line JS, as shown in Figure 2.32-2.

Equations by symmetrical components


In practice, the FL calculation is carried out in symmetrical components; hence, Equations
(2.32-4) to (2.32-7) are converted to symmetrical equations in the FL.

For example, in Figure 2.32-1, the distance ratio (χ) can be expressed in symmetrical
components when we substitute symmetrical components† for Equation (2.32-4).

𝑉1𝐺 − 𝑉1𝐻 + (𝑍11 ∙ 𝐼1𝐻 + 𝑍12 ∙ 𝐼2𝐻 + 𝑍10 ∙ 𝐼0𝐻 )


χ= (2.32-9)
𝑍11 ∙ 𝐼1𝑑 + 𝑍12 ∙ 𝐼2𝑑 + 𝑍10 ∙ 𝐼0𝑑

where,
V1G: Positive-sequence voltage at IED G
V1H: Positive-sequence voltage at IED H
I1H, I2H and I0H: Current (IH) at IED H represented by positive-sequence,
negative-sequence, and zero-sequence
I1d, I2d and I0d: Differential current (Id) represented by positive-sequence,
negative-sequence, and zero-sequence
Z11, Z12 and Z10‡ Line impedance (ZGH) represented by positive-sequence,
negative-sequence, and zero-sequence
†Note: When we can assume that the respective mutual-impedances are equal (Zab=Zbc,
Zbc=Zca, and Zca=Zab), symmetrical components (Z11, Z12 and Z10) are obtained
from the following Equations (2.32-10) to (2.32-12):

GRL200 (Soft 033 & 037)


- 378 -
6F2S1914 (0.37)

𝑍𝑎𝑎 + 𝑍𝑏𝑏 + 𝑍𝑐𝑐 − (𝑍𝑎𝑏 +𝑍𝑏𝑐 + 𝑍𝑐𝑎 )


Z11 = (2.32-10)
3

𝑍𝑎𝑎 + 𝑎2 ∙ 𝑍𝑏𝑏 + a ∙ 𝑍𝑐𝑐 + 2(𝑎 ∙ 𝑍𝑎𝑏 + 𝑍𝑏𝑐 + 𝑎2 ∙ 𝑍𝑐𝑎 )


Z12 = (2.32-11)
3

𝑍𝑎𝑎 + a ∙ 𝑍𝑏𝑏 +𝑎2 ∙ 𝑍𝑐𝑐 − (𝑎2 ∙ 𝑍𝑎𝑏 + 𝑍𝑏𝑐 + 𝑎 ∙ 𝑍𝑐𝑎 )


Z10 = (2.32-12)
3

where, “a” and “a2” are represented as

a = 1∠120°, a2 = 1∠240°

‡Note: When we suppose that all the self-impedance and all the mutual-impedance are
identical (Zaa=Zbb=Zcc and Zab=Zbc=Zca), we can see that both Z12 and Z10 are
represented as zero when Z10 is identical to ZGH.
Note: To run the FL, user should set either the symmetrical components (Z11, Z12 and
Z10) or the self-impedance (Zaa, Zbb and Zcc) and mutual-impedance (Zab, Zbc and
Zca). For example, the value of Z11 is placed for setting [FL_1R1] and [FL_1X1]
when symmetrical setting is selected. If symmetrical setting is not selected, user
should set the value of the Zaa for setting [FL_1Raa] and [FL_1Xaa]. For more
information, see section 2.32.6(iii).

(ii) Data recording trigger and calculation trigger


The calculation is stated by signals; and following protection functions provide the trigger
signals:
(a) Current differential protection (DIFL)
(b) External protection

With regard to the trigger signal of the external protection function, user can program
the trigger signal for recording data and calculation by using Element IDs (PLC connection
points), as shown in Table 2.32-2.

Table 2.32-2 Element IDs of recording data and calculation


Element ID Name Description
310022EC64 FLAZ_RecF Trigger for data recording
310022EC66 FLAZ_LocF Trigger for calculation
Note: Element IDs are also listed in section 0.

GRL200 (Soft 033 & 037)


- 379 -
6F2S1914 (0.37)

Trigger signal for data recording


Figure 2.32-3 shows a trigger signal for data recording. If elements operate and switches are
closed, the FL records the data of current and voltage. It is also possible that the FL starts to
record these data when the PLC1 signal is appeared.

Operation signal from DIFL2 element


Trigger signal for data recording:
Operation signal from RDIF2 element
Current and voltage data are saved

Operation signal from DIFG2 element by the operation signals from

Operation signal from RDIFG2 element elements.

310022EC64 FLAZ_RecF

Figure 2.32-3 Data recording trigger from the DIFL and the PLC
1Note: User can configure a signal with the PLC logic. For more information on the PLC,
see Chapter PLC function.
2Note: Respective switches in the above figure are closed when respective elements
operate. After that, data recording is provided for the FL. Elements and
characteristics (DIFL, RDIF, DIFG, and RDIFG) are discussed in the DIFL. See
Chapter Relay application: Segregated current differential protection .

Trigger signal for FL calculation


Figure 2.32-4 shows a calculation trigger; the calculation is carried out when the FL receives
the result signals of the DIFL and the DIFG. The calculation also starts by the PLC signal.

Result signal from DIFL

Result signal from DIFG


Trigger signal for calculation:
Calculation of fault locator is
initiated by the DIFL or the DIFG.
310022EC66 FLAZ_LocF

Figure 2.32-4 Calculation trigger from the DIF function and PLC
(iii) Calculation error
User should note that the calculation error might be larger when a setting value is far from
the actual data of line impedance. For example, if abnormal settings1 are done, the calculation
error will be appeared notably.
1Note: Abnormal settings can be exist when values are far from actual impedance data of
transmission line. For example, resistance value is so larger then reactance value,

GRL200 (Soft 033 & 037)


- 380 -
6F2S1914 (0.37)

and so on.

Calculation error in two-terminal-ends operation


The nominal measurement error can be with in ±1km when the following conditions are
applied:
 The line length (L) is shorter than 100km.
 The setting value [DIFL-I1] is lower than a half of the rated current2 (0.5 × In ).
 The differential current (Id) is larger than double of the rated current2 (2 × In ).

In other words, the calculation error can be with in ±1% when the following conditions are
applied:
 The line length (L) is shorter than 100km.
 The setting value [DIFL-I1] setting is lower than a half of the rated current2 (0.5 × In).
 The differential current (Id) is larger than double of the rated current2 (2 × In ).

Calculation error in three-terminal-ends operation


The nominal measurement error can be with in ±2km when the following conditions are
applied:
 The line length (L) is shorter than 100km.
 The setting value [DIFL-I1] is larger than a quarter of the rated current2 (0.25 × In).

 The reactance per unit length (X1⁄L) is smaller than the value (0.05⁄I ).
n

 The reactance per unit length (X1⁄L) is lower than the value (6.0⁄I ).
n

 The differential current (Id) is larger than double of the rated current2 (2 × In ).

On the other hand, the calculation error can be with in ±2% when the following conditions are
applied:
 The line length (L) is shorter than 100km.
 The setting value [DIFL-I1] is lower than a quarter of the rated current2 (0.25 × In).

 The reactance per unit length (X1⁄L) is larger than the value (0.05⁄I ).
n

 The reactance per unit length (X1⁄L) is smaller than the value (6.0⁄I ).
n

 The differential current (Id) is larger than double of the rated current2 (2 × In).
2Note: Rated current (In) is described separately. (See Chapter Technical description:
Transformer module)

GRL200 (Soft 033 & 037)


- 381 -
6F2S1914 (0.37)

2.32.2 FL calculation with data at a local-terminal only


When considering the FL calculation with data at a local-terminal only, user should note the
time of this calculation is longer than the time of FL calculation with data at a local-terminal
and remote-terminals1. This FL calculation requires data of the reference current, which is
obtained by measuring the change in current before and after the fault occurrence. The
reference current is used to remove the influence of load voltage and arc voltage.
1Note: In the FL calculation with data at a local-terminal only, more calculation time—
that are longer than three-cycles as fault continuing time—is required.
Conversely, minimum two-cycles as fault continuing time are required in the FL
calculation with data at a local-terminal and remote-terminals.

If a phase-to-phase fault occurs, Calculation principle for phase-to-phase fault is used


with data of the reference current (Iβ"), which is obtained by measuring the change in current
before and after the fault occurrence.

If an earth fault occurs, Calculation principle for earth fault is used with another
reference current (Iα"), which is similarly obtained by measuring the change in the current
before and after the fault.

In order to maintain the measurement accuracy, the compensation factors for impedance
imbalance are considered in the calculation when the variation of the impedance in each phase
is large.

(i) Calculation principle for phase-to-phase fault


Equations for the calculation in the case of phase-b-to-phase-c fault
We suppose the occurrence of a phase-b-to-phase-c fault. The fault distance (χ) is calculated
with the following Equations (2.32-13) to (2.32-16). Equation (2.32-16) is a general expression
when lines are treated as having lumped constants; and this expression is sufficient for lines
within 100km.

𝐼𝑏𝑐 = 𝐼b − 𝐼c (2.32-13)

𝑉𝑏𝑐 = 𝑉b − 𝑉c (2.32-14)

𝐼𝛽 ′ = 𝐼bc − (𝐼𝐿𝑏 − 𝐼𝐿𝑐 ) (2.32-15)

𝐼𝑚 (𝑉𝑏𝑐 ∙ 𝐼β ") × L
χ= (2.32-16)
{𝐼𝑚 (𝑅1 ∙ 𝐼𝑏𝑐 ∙ 𝐼β ") + 𝑅𝑒 (𝑋1 ∙ 𝐼𝑏𝑐 ∙ 𝐼β ")} × 𝐾𝑏𝑐

where,

GRL200 (Soft 033 & 037)


- 382 -
6F2S1914 (0.37)

Ib, Ic: Line-to-neutral currents when a phase-bc fault arises


Ibc: Line-to-line currents when a phase-bc fault arises (=Ib−Ic)
Vbc: Line-to-line voltages when a phase-bc fault arises (=Vb−Vc)
ILb: Load-current in phase-b before the fault
ILc: Load-current in phase-c before the fault
Iβ’: Load-current change before and after the fault (=(Ib−Ic)−(ILb−ILc))
Iβ”: Complex conjugate of Iβ’
R1: Resistance component of line impedance1 in positive-sequence
Χ1: Reactance component of line impedance1 in positive-sequence
Kbc: Compensation factor2 for imbalance impedance
L: Line length3 in the kilometer or mile
Im( ): Expression of imaginary part when a value is placed in parentheses
Re( ): Expression of real part when a value is placed in parentheses
•: Symbol of Vector product

1Note: For example, user should set the R1 and the X1 with settings [FL_1R1] and
setting [FL_1X1] respectively, when the impedance of line GJ is considered in
symmetrical components, as shown in Figure 2.32-2. For further information, see
section 2.32.6(iii).
2Note: User should set the Kab, Kbc and Kca with settings [FL_Kab], [FL_Kbc], and
[FL_Kca], when the imbalance impedance is considered. For further information,
see section 2.32.6(vi).
3Note: User should set the line length for settings [FL_1line_km] when the length of line
GJ is considered and when the unit of length is represented by kilometer, as
shown in Figure 2.32-2. For further information, see section 2.32.6(v).

Compensation for long line


When the line length is beyond 100km, the result of Equation (2.32-16) requires compensation.
Equation (2.32-17) is used to find the compensated distance (χ”) with respect to the fault
distance (χ) which is the result of Equation (2.32-16):

𝜒3
χ" = 𝜒 − 𝑘 2 × (2.32-17)
3

where,
k: Propagation constant fixed of the line (0.001𝑘𝑚−1)

(ii) Calculation principle for earth fault


Equations
When we suppose the occurrence of an earth fault in phase-a, the fault distance (χ) is

GRL200 (Soft 033 & 037)


- 383 -
6F2S1914 (0.37)

determined with Equations (2.32-18) to (2.32-23):

2𝐼𝑎 − 𝐼𝑏 – 𝐼𝑐
𝐼α = (2.32-18)
3

2𝐼𝑎 − 𝐼𝑏 – 𝐼𝑐 2𝐼𝐿𝑎 − 𝐼𝐿𝑏 – 𝐼𝐿𝑐


𝐼α ′ = − (2.32-19)
3 3

𝑽 = 𝑉𝑎 ・𝐼α " (2.32-20)

𝑹 = 𝑅1 ∙ 𝐼α ∙ 𝐼α " + 𝑅0 ∙ 𝐼0s ∙ 𝐼α "+𝑅0𝑚 ∙ 𝐼0m ∙ 𝐼α " (2.32-21)

𝑿 = X1 ∙ 𝐼α ∙ 𝐼α " + X 0 ∙ 𝐼0s ∙ 𝐼α "+X 0𝑚 ∙ 𝐼0m ∙ 𝐼α " (2.32-22)

Im(𝑽) × L
χ= (2.32-23)
{Im(𝑹) + Re(𝑿)} × 𝐾𝑎

where,
Va:Fault voltage (Va=Va0)
Iα: Fault current (=(2Ia−Ib−Ic)/3)
Iα’: Current change before and after the fault (=(2Ia−Ib−Ic)/3−(2ILa−ILb−ILc)/3)
Iα”: Complex conjugate of Iα’
Ia, Ib, Ic: Fault currents in phase-a, phase-b, and phase-c
ILa, ILb, ILc: Load-current in phase-a, phase-b, and phase-c before the fault
I0s: Current in zero-sequence at local terminal
I0m: Adjacent-line current in zero-sequence in parallel lines
R1: Resistance component of line impedance1 in positive-sequence
Χ1: Reactance component of line impedance1 in positive-sequence
R0: Resistance component of line impedance2 in zero-sequence
Χ0: Reactance component of line impedance2 in zero-sequence
R0m: Mutual resistance3 between parallel lines in zero-sequence
X0m: Mutual reactance3 between parallel lines in zero-sequence
Ka: Compensation factor4 for imbalance impedance
Im( ): Expression of imaginary part when a value is placed in parentheses
Re( ): Expression of real part when a value is placed in parentheses
L: Line length5 in the kilometer or mile
•: Symbol of Vector product

1Note: For example, user should set the R1 and the X1 with settings [FL_1R1] and
setting [FL_1X1] respectively, when the impedance of line GJ is considered in

GRL200 (Soft 033 & 037)


- 384 -
6F2S1914 (0.37)

symmetrical components, as shown in Figure 2.32-2. For further information, see


section 2.32.6(iii).
2Note: In the calculation of earth fault, user is required to set the R0 and the X0 with
settings [FL_1R0] and setting [FL_1X0] respectively, when the impedance of line
GJ is considered in symmetrical components.
3Note: When the mutual impedance of line GJ is considered , and when parallel lines are
applied, user should set the R0m and the X0m with settings [FL_1R0m] and
setting [FL_1X0m] respectively,. If a single line is considered, user are not
required to set these settings.
4Note: User should set the Ka, Kb and Kc with settings [FL_Ka], [FL_Kb], and [FL_Kc],
when the imbalance impedance is considered. For further information, see section
2.32.6(vi).
5Note: User should set the line length for settings [FL_1line_km] when the length of line
GJ is considered and when the unit of length is represented by kilometer, as
shown in Figure 2.32-2. For further information, see section 2.32.6(v).

Compensation
Consider the influence of the distributed capacitance in Equation (2.32-23), likewise section
2.32.2(i)-2. When the line length is beyond 100km, the result of Equation (2.32-23) requires
compensation. Thus, Equation (2.32-17) is used to find the compensated distance (χ”) with
respect to the fault distance (χ) which Equation (2.32-23) calculates. The setting procedures
are discussed later. (See section 2.32.6(iii)-2)

(iii) Data recording trigger and calculation trigger


The calculation is started by signals; and following protection functions provide the trigger
signals:
(a) Distance protection1 (ZS/ZG)
(b) Over current protection2 (OC)
(c) Current differential protection (DIFL)
(d) External protection3

1Note: For more information of the ZS/ZG, see Chapter Relay application: Distance
protection.
2Note: For more information of the OC, see Chapter Relay application: Overcurrent
protection.
3Note: With regard to the trigger signal from the external protection function, user can
program this trigger signal by using Element IDs (PLC connection points), as
shown in Table 2.32-3, which are also listed in section 0.

GRL200 (Soft 033 & 037)


- 385 -
6F2S1914 (0.37)

Table 2.32-3 Element IDs for data recording and calculation


Element ID Name Description
310022EC60 FLZ_RecF Trigger for data save
310022EC61 FLZ_RecR Trigger for data save
310022EC62 FLZ_LocF Trigger for calculation
310022EC63 FLZ_LocR Trigger for calculation

Trigger signal for Data recording

Figure 2.32-5 shows a trigger signal for data recording. Respective elements of protective
functions (ZS/ZG, OC, and DIFL) output their operation signals when respective elements
operate; and then, these signals are summarized to the trigger signal by a logic “OR”. In
IR
response to scheme switch [FL-Dir], the FL can record the data of current and voltage if the
fault occurs in either forward or reverse.
Forward
Z1S DIR Reverse
Z1S
≥1
Forward
Z1XS DIR Reverse ≥1 Trigger signal
Z1XS Forward
Forward & for data
Z2S DIR Reverse recording
Z2S
Forward
Z3S DIR Reverse
Z3S

≥1
Operation signal of ZS elements

≥1
Forward
Z1G DIR Reverse Reverse
Z1G
≥1 Trigger signal
Forward
Z1XG DIR Reverse & for data
Z1XG
Forward
recording
Z2G DIR Reverse
Z2G
Forward
Z3G DIR Reverse
Z3G

≥1
Operation signal of ZG elements

Forward
OC1-Dir Reverse ≥1
OC1
Forward
OC2-Dir Reverse
OC2 Forward
FL-DIR Reverse
Operation signal of OC elements ≥1

DIFL
≥1
RDIF

DIFG Operation signal of DIF elements

RDIFG

Forward
310022EC60 FLZ_RecF ≥1

310022EC64 FLAZ_RecF
Reverse
310022EC61 FLZ_RecR
PLC signals

Figure 2.32-5 Data recording trigger from functions and PLC

GRL200 (Soft 033 & 037)


- 386 -
6F2S1914 (0.37)

Note: In the FL, user should verify the direction between the FL function and the other
protection function. For example, if Forward is set for the scheme switch [FL-Dir],
user should set Forward for the respective scheme switches [Z*S-DIR], [Z*G-DIR]
and [OC*-DIR]. If contradiction is found, the FL does not operate. For further
information, see section 2.32.6(iii).

Trigger signal for FL calculation


Z1S DIR
Figure 2.32-6 shows trigger signals for FL calculation. Result signals1 from the respective
protection functions are summarized by logic “OR”, which provides the trigger signal.
Forward
Z1S Z1S DIR Reverse
Forward ≥1

Z1XS Z1XS DIR Reverse ≥1


Forward Trigger signal
Forward &
Reverse for calculation
Z2S Z2S DIR
Forward
Z3S DIR Reverse
Z3S

≥1
Result signal of ZS function

≥1
Forward
Z1G DIR Reverse Reverse
Z1G
Forward ≥1
&
Trigger signal
Z1XG Z1XG DIR Reverse for calculation
Forward
Z2G Z2G DIR Reverse
Forward
Z3G DIR Reverse
Z3G

Result signal of ZG function ≥1

Forward
OC1-Dir Reverse ≥1
OC1
Forward
OC2 OC2-Dir Reverse
Forward
FL-DIR
Reverse
Result signal of OC function ≥1

DIFL
≥1
RDIF

Result signal of DIF function

310022EC62 FLZ_LocF
Forward
≥1
310022EC66 FLAZ_LocF

310022EC63 FLZ_LocR Reverse

PLC signals

Figure 2.32-6 Calculation trigger from functions and PLC


1Note: The result signals can start the FL calculation, but the result signals are not the same as the
operation signals of
Figure 2.32-5.

GRL200 (Soft 033 & 037)


- 387 -
6F2S1914 (0.37)

(iv) Calculation error


User should note that the calculation error could be larger when a setting value is far from
actual line impedance. For example, if abnormal settings1 are done, the calculation error will
be appeared notably.

The calculation error can be with in ± 2.5 km when the following conditions are applied:
 A fault is assumed to arise up to 100 km distance.
 The fault current is larger than double of the rated current2 (2 × In).

 The reactance3 per unit length (X1⁄L) is longer than a value (0.05⁄I ).
n

In other words, this calculation error can be with in ±2.5% when the following conditions
are applied:
 The line length (L) is shorter than 100km.

 The reactance per unit length (X1⁄L) is larger than a value (0.05⁄I ).
n

 The fault current is larger than double of the rated current2 (2 × In).

1Note: Abnormal settings can be exist when values are far from actual impedance data of
transmission line. For example, resistance value is so larger then reactance value,
and so on.
2Note: Rated current (In) is described separately. (See Chapter Technical description:
Transformer module)
3Note: The term X1 is the reactance component of line impedance.

2.32.3 Selection of calculation results


At the outset, we discuss that the FL calculation consist of two groups: (1) FL calculation with
data at a local-terminal and remote-terminals and (2) FL calculation with data at a local-
terminal only. Hence, either (1) or (2) is selected as a calculation result in accordance with a
fault condition. The FL selects the result of (2) FL calculation with data at a local-terminal
only when the FL finds the following conditions after the calculations:
 The calculation results are less than 20% of the line length (L).
 The result difference between (1) and (2) is within 5% of the line length (L).
 The calculation result is less than 40km.

GRL200 (Soft 033 & 037)


- 388 -
6F2S1914 (0.37)

2.32.4 Screen of FL output


Although the IED screen is shown separately in Chapter Recording function, the IED screen
of the fault determination is discussed here because the screen of fault determination is unique
compared with others. Thus, we brief the IED screen of the fault determination, as shown in
Figure 2.32-7.

a. Fault determination in the kilometer


b. Section info for fault

FL ****.*km Sec. 1

****% OB / NC /CF

d. Detailed info
c. Fault determination in percentage

Figure 2.32-7 IED screen of FL calculation in the kilometer and percentage

(i) Fault determination in kilometer or mile


The fault location is referred as a fault determination (fault distance), and the fault
determination is displayed in kilometer, as shown in Figure 2.32-8 (shaded portion a). If the
information of the line length includes an error, the screen is displayed with “—” (dash sign)
and the calculation dose not start. The fault determination is not shown when the trigger is
not provided for the FL.

As shown in Figure 2.32-8, if the IED at local-terminal runs along with other IEDs, the
IED at local-terminal displays the distance value from the local IED to the fault point.

Line GJ
Line GJ+JH
t
Distance GA
t
Distance GB
TT TT
Bus G
t Junction J Bus H Bus G t Junction J Bus H
Local TT Sec.1 Local TT Sec.1
Fault tA t t t
Local IED G Remote IED H Local IED G Fault B Remote IED H
TT
t t t TT t
Sec.2

Sec.2

t
t

Remote IED S Remote IED H


t t
Bus S Bus S
(1). Fault arises on line GJ (2) Fault arises on line JH

Figure 2.32-8 Fault determination when three IEDs are applied

The fault determination (fault distance) is displayed in mile or kilometer. To display the
fault distance in mile, user should change the setting, which is discussed later. (See

GRL200 (Soft 033 & 037)


- 389 -
6F2S1914 (0.37)

section2.32.6(v))

(ii) Fault determination in percentage


Figure 2.32-7 (shaded portion c) shows the result of the fault determination in percentage. The
screen is displayed as “—” (dash sign) when the result of the fault determination has an error.

As shown in Figure 2.32-7, when the IED at local-end (IED G) runs along with the other
IEDs (IED H and IED S), user should notice that the screen difference is appeared with fault
occurrence between (1) a fault arises on the line GJ and (2) a fault arises on the line JH.

Fault A arises on the line GJ


As shown in Figure 2.32-8 (1), when a fault A arises on the line GJ, the following equation
determines the result of fault determination in percentage:

Distance to fault A (GA)


Fault determination (%) = × 100 (2.32-24)
lenght of Line GJ (GJ)

Fault B arises on the line JH


As shown in Figure 2.32-8 (2), when a fault B arises on the line JH, the following equation
determines the result of fault determination in percentage:

Fault determination (%)


Distance to fault B (GB) (2.32-25)
= × 100
lenght of Line GH (GJ + JH)

(iii) Fault section information


When a junction exists on the line, and when the FL runs in the IED G at local-terminal, the
section information is useful. Figure 2.32-7 (shaded portion b) show the section information
displayed on the IED screen at the IED G when the IED H and the IED S run at remote-
terminals. Table 2.32-4 shows section notations. If a fault occurs, one of the section notations
is displayed on the IED screen. Note that no section information is shown when a junction does
not exist on the line.

GRL200 (Soft 033 & 037)


- 390 -
6F2S1914 (0.37)

Table 2.32-4 Section notation when a fault arises


Section Correspondent Correspondent
Meaning
notation1 line setting2
A fault arises from the local
Local Line GJ Line1_Element
terminal to a junction.
A fault arises from a junction to
Sec. 1 Line JH Line2_Element
remote end #1.
A fault arises from a junction to
Sec. 2 Line JS Line3_Element
remote end #2.
Junc. A fault arises near a junction. Junction N.A
1Note: Section notation and correspondent settings are relevant to communication ports.
For detail, section 2.32.5(i).
2Note: User can find the setting means in section 2.32.6(iii).

(iv) Detail information


As shown in Figure 2.32-7 (shaded portion d), the detail information is displayed along
with the fault determination, which is simplified with notations, Table 2.32-5 summarizes the
notations of fault determination.

Table 2.32-5 Notation of fault information for screen


Fault info.
Meaning Comment
Notation
Fault location is assumed over the boundary.In the case of
OB Over boundary three-terminal application, the boundary means the sum
of the two line length.
Fault location is assumed over the junction;
this information is applied only for the FL calculation with
data at a local-terminal only. If the results of the FL
OJ Over junction
calculation with data at a local-terminal and remote-
terminals assumed over the junction, the section notation
will appear instead like “Sec.1” or “Sec.2”.
Since a number of calculation results are scattered, the FL
NC Not converged. chooses one of the result value in order that the scattering
turns to be small.
Communication failures are risen while data recording;
Communication hence the FL calculation with data at a local-terminal
CF
failure only is brought for the fault determination. Note that the
result of the calculation decays.

GRL200 (Soft 033 & 037)


- 391 -
6F2S1914 (0.37)

2.32.5 Preparation and consideration of setting


User should set line impedance for the FL; and these setting points are provided in each
Line_element. User should note that the value of the line impedance is represented as
secondary circuit of VCT.

(i) Setting in each Line_element when three-terminal being applied


As shown in Figure 2.32-8 and Table 2.32-4, when three IEDs are configured at a local-terminal
and the other remote-terminals, the protection sections are divided into three: (1) Local (Line
GJ), (2) Sec. 1 (Line JH), and (3) Sec. 2 (Line JS).

User should set impedance values into Line1_Element when the Local (GJ) is subject to
setting. As for the Sec.1 (JH), user should set impedance values into Line2_Element. Likewise,
as for the Sec. 2 (JS), set impedance values into Line3_Element.2

User should notice that the section configurations are decided by the IED communication
port1; and the section is established when the communication between the IEDs is made. For
example, the Sec.1 is decided by the communication port #1 with which the Local IED (IED G)
is connected to the remote-IED (IED H). On the other hand, the Sec. 2 is decided by the
communication port #2 with which the Local IED is connected to the remote-IED (IED S).
1Note: The configuration for the communication port is discussed separately. (See
Chapter Relay application: Transmission control function)
2Note: The “Line1_Element”, “Line2_Element”, and “Line3_Element” are discussed in
the setting procedure. See section 2.32.6(iii).

(ii) Setting in Line1_Element when two-terminal being applied


The setting items in “Line1_Element” are only used when two IEDs are configured.

(iii) Setting for a signle IED configulation


The setting items in “Line1_Element” are only used when a single IED is configured. In this
case, the FL calculation with data at a local-terminal only is only applicable.

(iv) Computation of impedance when variation being found in respective


phases
When variation of the impedance in respective phases is found, user should get an impedance
in positive-sequence by Equation (2.32-26), an impedance in zero-sequence by Equation
(2.32-27), and a mutual impedance in zero-sequence by Equation (2.32-28).

𝑍𝑎𝑎 + 𝑍𝑏𝑏 + 𝑍𝑐𝑐 − (𝑍𝑎𝑏 +𝑍𝑏𝑐 + 𝑍𝑐𝑎 )


Z1 = (2.32-26)
3

GRL200 (Soft 033 & 037)


- 392 -
6F2S1914 (0.37)

𝑍𝑎𝑎 + 𝑍𝑏𝑏 + 𝑍𝑐𝑐 + 2(𝑍𝑎𝑏 + 𝑍𝑏𝑐 + 𝑍𝑐𝑎 )


Z0 = (2.32-27)
3

𝑍𝑎𝑚 + 𝑍𝑏𝑚 + 𝑍𝑐𝑚


Z0𝑚 = (2.32-28)
3

(v) Computation of impedance when imbalance being found


The compensation factors are provided when impedance imbalances are apparent. Equations
(2.32-29) to (2.32-34) are provided to calculate these factors, but these factors should be set to
100% when the impedance imbalances can be ignored.

𝑍𝑎𝑎 + 𝑍𝑏𝑏
− 𝑍𝑎𝑏
K 𝑎𝑏 = 2 (2.32-29)
𝑍1

𝑍𝑏𝑏 + 𝑍𝑐𝑐
− 𝑍𝑏𝑐
K 𝑏𝑐 = 2 (2.32-30)
𝑍1

𝑍𝑐𝑐 + 𝑍𝑎𝑎
− 𝑍𝑐𝑎
K 𝑐𝑎 = 2 (2.32-31)
𝑍1

𝑍𝑎𝑏 + 𝑍𝑐𝑎
𝑍𝑎𝑎 −
K𝑎 = 2 (2.32-32)
𝑍1

𝑍𝑏𝑐 + 𝑍𝑎𝑏
𝑍𝑏𝑏 − 2
K𝑏 = (2.32-33)
𝑍1

𝑍𝑐𝑎 + 𝑍𝑎𝑏
𝑍𝑐𝑐 − 2
K𝑐 = (2.32-34)
𝑍1

GRL200 (Soft 033 & 037)


- 393 -
6F2S1914 (0.37)

2.32.6 Setting procedure


The FL has a number of operation features and these features are provided with settings,
which can be keyed from the IED screen for operation. (See Chapter User interface: Setting)

(i) FL execution
The FL calculation is carried out when On is set for setting [FL_EN]. The two calculation
groups (which are described in section2.32.1 and section 2.32.2) are subject to this setting.

(ii) FL direction
Note: Set of FL direction is only available for the FL calculation with data at a local-
terminal only.

When considering the fault determination, user can choose the direction in either forward or
reverse. When required to respond to the fault in forward, user should select the direction in
forward if the forward is selected in the elements of the other protection functions
corresponding to the FL; otherwise, the FL calculation fails to start.

The setting [FL_Dir] is provided to select the FL direction; and Forward is set when a
fault is supposed to arise in forward. Inversely, set Reverse for it when a fault is supposed to
arise in reverse direction. Figure 2.32-9 shows the direction of a fault.

Bus Ia F Bus I
a

IED IED

a. Fault in Forward b. Fault in Reverse

Figure 2.32-9 Forward fault and reverse fault

(iii) Selection of either Matrix or Symmetrical component; and impedance


settings
As described in section 2.32.1(i)-3, the FL calculation is carried out in symmetrical component;
hence, setting the line impedance in symmetrical components may be required, but user can
also set the line impedance in resistive and reactive (matrix) components. Thus, prior to setting
of impedance, user should select either Matrix or Symmetrical with scheme switch [FL_ImpSet].

GRL200 (Soft 033 & 037)


- 394 -
6F2S1914 (0.37)

Impedance setting in Matrix components


Matrix setting is required to set numerical values for both self-impedance (Zaa, Zbb and Zcc)
and mutual-impedance (Zab, Zbc and Zca).

As shown in Figure 2.32-8, when we consider the three-terminal application, user should
key values for each Line_Element. When we consider the two-terminal application, as shown
in Figure 2.32-1, user just keys values for Line1_Element setting.

 Setting for Line GJ (Line1_Element)


For instance, consider setting impedance values with respect to the local line (line GJ) in
Figure 2.32-8, setting targets are represented as the Line1_Element. The self-impedances are
one of the subjects in the matrix setting; hence, user should set the self-impedance values for
setting items—that are designated [FL_1Raa] to [FL_1Rcc] and [FL_1Xaa] to [FL_1Xcc].
Likewise, the mutual-impedances values are set for the settings [FL_1Rab] to [FL_1Rca] and
[FL_1Xab] to [FL_1Xca].

 Setting for Line JH (Line2_Element)


On the other hand, considering setting impedance value of line JH, setting targets are
represented as the Line2_Element. In a manner similar to that of Setting of Line GJ, user
should set the self-impedance values for setting items—that are designated [FL_2Raa] to
[FL_2Rcc] and [FL_2Xaa] to [FL_2Xcc]. Likewise, the mutual-impedances values are set for
the settings [FL_2Rab] to [FL_2Rca] and [FL_2Xab] to [FL_2Xca].

 Setting for Line JS (Line3_Element)


For impedance values of line JH, setting targets are represented as the Line3_Element. In a
manner similar to that of Setting of Line GJ, user should set the self-impedance values for
setting items—that are designated [FL_3Raa] to [FL_3Rcc] and [FL_3Xaa] to [FL_3Xcc].
Likewise, the mutual-impedances values are set for the settings [FL_3Rab] to [FL_3Rca] and
[FL_3Xab] to [FL_3Xca].

Impedance setting in Symmetrical components


Symmetrical setting is available when each self-impedance is identical to the other
(Zaa=Zbb=Zcc) and each mutual-impedance is identical to the other (Zab=Zbc=Zca); and then,
set Symmetrical for the scheme switch [FL_ImpSet]. The method of how to obtain the
symmetrical values is discussed earlier with Equations (2.32-10) to (2.32-12).

 Impedance for Line GJ (Line1_Element setting)

GRL200 (Soft 033 & 037)


- 395 -
6F2S1914 (0.37)

The settings [FL_1R0], [FL_1R1], [FL_1X0], and [FL_1X1] are subject to setting items when
user considers the impedance setting of the Line1_Element.

 Impedance for Line JH (Line2_Element setting)


The settings [FL_2R0], [FL_2R1], [FL_2X0], and [FL_2X1] are subject to setting items when
user considers the impedance setting of the Line2_Element.

 Impedance for Line GJ (Line3_Element setting)


The settings [FL_3R0], [FL_3R1], [FL_3X0], and [FL_3X1] are subject to setting items when
user considers the impedance setting of the Line3_Element.

(iv) Compensation setting for earth fault for parallel lines


In order to respond to an earth fault, the FL function operates where the entering current is
compensated by the residual current on an adjacent line when the FL function operates for the
parallel lines. In the FL function, the compensation is also available for the entering current
by the computation using impedance.

As a rule, when the FL function operates in the parallel lines, it is recommended that the
entering current should be compensated by the residual current. This is because the measuring
elements can detect the earth fault securely. Thus, the user should set Off for the scheme
switch [FL-Z0B]; mutual impedance in the parallel lines should be set for the settings
[FL_R0m] and [FL_X0m].1

1Note: The user should use Equation (2.32-28) in order to derive mutual impedance when
the parallel lines are taken into consideration; the user should set their mutual
impedances for the settings [FL_R0m] and [FL_X0m]. Setting values of the mutual
impedance are also found in Equations (2.32-21) and (2.32-22).

If residual current on the parallel line is not provided, the user should set On for the scheme
switch [FL-Z0B]. In this case, settings for impedance looking in reverse are required together
with the settings [FL_R0m] and [FL_X0m]. These impedances looking in reverse are provided
with both settings [FL_Z0B-L] and [FL_Z0B-R]. The setting [FL_Z0B-L] is referred an
impedance looking in reverse at local-end in zero sequence. The setting [FL_Z0B-R] is referred
an impedance looking in reverse at remote-end in zero sequence. Table 2.32-6 summarizes
their compensation means and settings.

GRL200 (Soft 033 & 037)


- 396 -
6F2S1914 (0.37)

Table 2.32-6 Method and setting in earth fault compensation


Setting objects Required power
Compensation
Switch Impedance Decision of compensation method quantities for
method
[FL-Z0B] setting this operation
[FL_R0m] 1. The residual current is available in I0m, Ia, Ib, Ic,
Residual-current Off and the parallel line.
Va, Vb, Vc
[FL_X0m] 2. The single line is considered.
[FL_Z0B_L],
1. The residual current is not
[FL_Z0B_R], Ia, Ib, Ic, Va, Vb,
Impedance available in the parallel line.
On [FL_R0m],
looking in reverse 2. The compensation method above is Vc
and
not preferred.
[FL_X0m]

Note: The user should set Off for the scheme switch [FL-Z0B] when the FL function
operates on a single circuit line.

(v) Setting of the unit of length/distance


As shown in Figure 2.32-7, the fault determination is shown in kilometer when user sets km
for the scheme switch [FL_Unit]. On the other hand, if the fault determiantion in the mile is
preferred, user should set mile for the scheme switch [FL_Unit]. The IED screen for the FL
computaion are subject to this setting. After that, user can set values for the corresponding
settings.

For example, when we consider the Line1_Element setting, if user selects km for the
scheme switch [FL_Unit], setting [FL_1Line_km] is used to set the line length value. On the
other hand, if user selects mile for the scheme switch [FL_Unit], setting [FL_1Line_mile] is
used to set the line length value.

(vi) Setting of compensation factor


As discussed in section 2.32.5(v), if the impedance imbalances are found, user should set
the compensation factors for settings [FL_Kab], [FL_Kbc], [FL_Kca], [FL_Ka], [FL_Kb], and
[FL_Kc]. In order to find how to obtain these factors, see section 2.32.5(v).

(vii) Computation for overreaching


If the user wishes to obtain the result of the FL computation when the fault occurs beyond the
boundary defined with the setting [FL_Line_km] or [FL_Line_mile], the result can be displayed
when On is set for setting [FL_ALL_Zone]. Note that the fault location will be displayed by On
being set for the [FL_ALL_Zone], but the result for overreaching cannot be guaranteed in the
FL computation; thereby, it must be taken carefully.

GRL200 (Soft 033 & 037)


- 397 -
6F2S1914 (0.37)

2.32.7 Setting
Fault Locator (Function ID: 496001) at Common
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
FL_EN Off / On - Fault locator scheme swtich On
FL_Dir Forward / Reverse - Metering direction Forward
Impedance FL_ImpSet Symmetrical / Matrix - Selection in the setting mode of impedance Symmetrical
Zero sequence compensation of the parallel
FL_Z0B Off / On - Off
line
FL_Unit km / mile - Selection of line length unit km
FL_AllZone Off / On - Display the outside of the boundary Off
Line1 0.00 - 0.00 - Reactance component of line zero sequence
FL_1X0 - 34.00 6.80
1000.00 200.00 impedance
0.00 - 0.00 - Resistance component of line zero sequence
FL_1R0 - 3.50 0.70
1000.00 200.00 impedance
FL_Kab 50 - 150 % Impedance imbalance compensation factors 100
FL_Kbc 50 - 150 % Impedance imbalance compensation factors 100
FL_Kca 50 - 150 % Impedance imbalance compensation factors 100
FL_Ka 50 - 150 % Impedance imbalance compensation factors 100
FL_Kb 50 - 150 % Impedance imbalance compensation factors 100
FL_Kc 50 - 150 % Impedance imbalance compensation factors 100
0.00 - 0.00 -
FL_1Xaa - Reactance component of line1 (Xaa) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_1Xbb - Reactance component of line1 (Xbb) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_1Xcc - Reactance component of line1 (Xcc) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_1Xab - Reactance component of line1 (Xab) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_1Xbc - Reactance component of line1 (Xbc) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_1Xca - Reactance component of line1 (Xca) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_1Raa - Resistance component of line1 (Raa) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_1Rbb - Resistance component of line1 (Rbb) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_1Rcc - Resistance component of line1 (Rcc) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_1Rab - Resistance component of line1 (Rab) 0.10 0.01
1000.00 200.00
0.00 - 0.00 -
FL_1Rbc - Resistance component of line1 (Rbc) 0.10 0.01
1000.00 200.00
0.00 - 0.00 -
FL_1Rca - Resistance component of line1 (Rca) 0.10 0.01
1000.00 200.00
0.00 - 0.00 - Reactance component of line1 positive
FL_1X1 - 10.00 2.00
1000.00 200.00 sequence impedance
0.00 - 0.00 - Resistance component of line1 positive
FL_1R1 - 1.00 0.20
1000.00 200.00 sequence impedance
Line2 0.00 - 0.00 -
FL_2Xaa - Reactance component of line2 (Xaa) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_2Xbb - Reactance component of line2 (Xbb) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_2Xcc - Reactance component of line2 (Xcc) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_2Xab - Reactance component of line2 (Xab) 0.50 0.10
1000.00 200.00

GRL200 (Soft 033 & 037)


- 398 -
6F2S1914 (0.37)

Fault Locator (Function ID: 496001) at Common


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
0.00 - 0.00 -
FL_2Xbc - Reactance component of line2 (Xbc) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_2Xca - Reactance component of line2 (Xca) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_2Raa - Resistance component of line2 (Raa) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_2Rbb - Resistance component of line2 (Rbb) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_2Rcc - Resistance component of line2 (Rcc) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_2Rab - Resistance component of line2 (Rab) 0.10 0.01
1000.00 200.00
0.00 - 0.00 -
FL_2Rbc - Resistance component of line2 (Rbc) 0.10 0.01
1000.00 200.00
0.00 - 0.00 -
FL_2Rca - Resistance component of line2 (Rca) 0.10 0.01
1000.00 200.00
0.00 - 0.00 - Reactance component of line1 positive
FL_2X1 - 10.00 2.00
1000.00 200.00 sequence impedance
0.00 - 0.00 - Resistance component of line1 positive
FL_2R1 - 1.00 0.20
1000.00 200.00 sequence impedance
Line3 0.00 - 0.00 -
FL_3Xaa - Reactance component of line3 (Xaa) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_3Xbb - Reactance component of line3 (Xbb) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_3Xcc - Reactance component of line3 (Xcc) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_3Xab - Reactance component of line3 (Xab) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_3Xbc - Reactance component of line3 (Xbc) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_3Xca - Reactance component of line3 (Xca) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_3Raa - Resistance component of line3 (Raa) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_3Rbb - Resistance component of line3 (Rbb) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_3Rcc - Resistance component of line3 (Rcc) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_3Rab - Resistance component of line3 (Rab) 0.10 0.01
1000.00 200.00
0.00 - 0.00 -
FL_3Rbc - Resistance component of line3 (Rbc) 0.10 0.01
1000.00 200.00
0.00 - 0.00 -
FL_3Rca - Resistance component of line3 (Rca) 0.10 0.01
1000.00 200.00
0.00 - 0.00 - Reactance component of line1 positive
FL_3X1 - 10.00 2.00
1000.00 200.00 sequence impedance
0.00 - 0.00 - Resistance component of line1 positive
FL_3R1 - 1.00 0.20
1000.00 200.00 sequence impedance
Z0B 0.00 - 0.00 - Resistance component of line mutual zero
FL_R0m - 1.00 0.20
1000.00 200.00 sequence impedance
0.00 - 0.00 - Reactance component of line mutual zero
FL_X0m - 10.00 2.00
1000.00 200.00 sequence impedance
0.00 - 0.00 - Zero sequence back source impedance at local
FL_Z0B_L - 10.00 2.00
1000.00 200.00 terminal

GRL200 (Soft 033 & 037)


- 399 -
6F2S1914 (0.37)

Fault Locator (Function ID: 496001) at Common


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
0.00 - 0.00 - Zero sequence back source impedance at
FL_Z0B_R - 10.00 2.00
1000.00 200.00 remote terminal
Unit FL_1Line_km 0.0 - 500.0 km Line1 length (km) 50.0
mil
FL_1Line_mile 0.0 - 310.0 Line1 length (mile) 31.0
es
FL_2Line_km 0.0 - 500.0 km Line2 length (km) 50.0
mil
FL_2Line_mile 0.0 - 310.0 Line2 length (mile) 31.0
es
FL_3Line_km 0.0 - 500.0 km Line3 length (km) 50.0
mil
FL_3Line_mile 0.0 - 310.0 Line3 length (mile) 31.0
es

2.32.8 Data ID
 Signal monitoring point
FL-AZ (Function ID: 496001)
Element ID Name Description
8000101349 FLTFLAG Fault locator update flag

3100101348 FLTLOOP Fault loop

3100101005 FLTQUALITY Quality of fault locator

 Connection point in PLC logic


FL-AZ (Function ID: 496001)
Element ID Name Description
310022EC66 FLAZ_LOCF Fault locate start signal (Local and remote end data, forward)

310022EC67 FLAZ_LOCR Fault locate start signal (Local and remote end data, reverse)

310022EC64 FLAZ_RECF Record start signal (Local and remote end data, forward)

310022EC65 FLAZ_RECR Record start signal (Local and remote end data, reverse)

310022EC62 FLZ_LOCF Fault locate start signal (Only local end data, forward)

310022EC63 FLZ_LOCR Fault locate start signal (Only local end data, reverse)

310022EC60 FLZ_RECF Record start signal (Only local end data, forward)

310022EC61 FLZ_RECR Record start signal (Only local end data, reverse)

GRL200 (Soft 033 & 037)


- 400 -
6F2S1914 (0.37)

Trip circuit (TRC)


The trip circuit (TRC) scheme issues trip commands to the circuit breakers (CB#1, CB#2) when
it receives trip signals from the protection functions (which are identified with ‘FC1’, ‘FC2’, etc.
to represent DIFL, DIFGL relay, etc.). The TRC function is able to receive an alternate trip
signal generated by an additional relay external to the IED using PLC connection points via
the binary IO module (BIO)†. If the additional relay can provide a check-signal to condition
tripping, increased reliability can be achieved within the IED when using the check-signal as
an input to the TRC logic (i.e., fail-safe operation is realized by the operation of the additional
relay).

─────────────────────────────────────────────────────────────────
Note: The TRC function is feasible in entire models, which can be enumerated in the IED
ordering number. For more information, see Appendix: Ordering.
Table 2.33-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
– TRC ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 401 -
6F2S1914 (0.37)

Figure 2.33-1 shows that the function is made with following logics:
Collection: The signals, received from the various protection functions (shown as
‘FC18’ and others; see Table 2.33-2 and Table 2.33-6), are gathered in the Trip-signal
collection logic.
Generation: CB trip signal generation, Sub-signal generation for blocking ARC§, and
Alarm-signal generation logics are provided.

A binary output (BO†) circuit must be selected in order to energize the trip coil of the
CB#1 and CB#2. That is, the BOs should be made the connection with the CB#1 and CB#2 trip
coils; the drive signal should be outputted (i.e., ‘TRIP-COMMAND1-A,-B,-C’ and ‘TRIP-
COMMAND2-A,-B,-C’†). The Alarm-signal generation logic operates to provide a trigger signal
for the recording function‡.

†Note:The internal connection between the TRC function and the BIO module should be
performed using the BIO settings or the PLC programming. The user can program
the connection the PLC monitoring point ‘TRIP-COMMAND1-A (8000001B20) etc.’
with preferred BO circuits using the settings [Input signal1] etc. of each BO on the
BIO module. The externally wired connection between the BIO module and trip
coil circuit is made at the IED terminals. For more information with regard to the
BO circuit concerning the Element ID (Data ID), see Chapter Technical
description: Binary IO module.
§Note: Autoreclose (ARC) and other protection functions are discussed separately. See
Chapter Relay application, respectively.
‡Note: For information on recording, see Chapter Recording function.

GRL200 (Soft 033 & 037)


- 402 -
6F2S1914 (0.37)

Protection functions TRC function


FC1-OPT-TRIP-A
FC1-OPT-TRIP-B
FC1-OPT-TRIP-C
FC1-OPT-TRIP
FC1-ARC-BLOCK Binary IO module
FC1
FC1-OPT-ALARM TRIP-COMMAND1-A BO1 CB#1 (bus CB)
FC1-OPT-AR TRIP-COMMAND1-B
BO2 Transmission line
FC1-OPT-BR OPT-TRIP-A TRIP-COMMAND1-C
FC1-OPT-CR BO3
OPT-TRIP-B
CB trip TRIP-COMMAND2-A
FC1-OPT-ABR OPT-TRIP-C BO4
signal CB#2 (center CB)
FC1-OPT-BCR Trip-command TRIP-COMMAND2-B
generation BO5
FC1-OPT-CAR collection TRIP-COMMAND2-C Transmission line
BO6
Busbar
FC2-OPT-TRIP-A A

FC2-OPT-TRIP-B
OPT-TRIP B
FC2-OPT-TRIP-C Protection
GEN.TRIP
FC2-OPT-TRIP functions
GEN.TRIP-A
FC2-ARC-BLOCK
FC2 GEN.TRIP-B ZG
FC2-OPT-ALARM GEN.TRIP-C
Sub-signal
FC2-OPT-AR CBF
generation
FC2-OPT-BR GEN.ARC-BLOCK ARC
FC2-OPT-CR
FC2-OPT-ABR GEN.TRIP_ALARM
FC2-OPT-BCR
FC2-OPT-CAR Alarm signal OPT.PHASE-A Recording
generation OPT.PHASE-B function
OPT.PHASE-C
FC40-OPT-TRIP-A etc.
FC40 OPT.PHASE-N
CBF1_RETRIP
CBF CBF1_ARC-BLOCK

CB1_BRIDGE B

CB2_BRIDGE
ARC
CB1_94TT A
CB2_94TT

Figure 2.33-1 TRC block diagram

GRL200 (Soft 033 & 037)


- 403 -
6F2S1914 (0.37)

2.33.1 Command for tripping CB and signal to block reclosing CB#1/CB#2


The TRC logic is designed to issue per-phase trip or three-phase trip commands when a fault
occurs. Table 2.33-2 shows the receipt of trip signals from the protection functions, which are
identified by ‘Protection function identification numbers (‘*’). Note that an operation block
signal for the ARC function is also provided along with the trip signal.
Table 2.33-2 Trip/ARC block signal inputs to the TRC function
Trip and ARC-block signals provided by the protection functions
Protection ID
‘*’ FC*_OPT FC*_OPT FC*_OPT FC*_OPT FC*_OPT_ARC-
functions Note
_TRIP-A _TRIP-B _TRIP-C _TRIP BLOCK
DIFL 1 X X X – X
DIFGL 2 – – – X X
OSTV 3 – – – X X
DTT 4 – – – X X
N.A. 5 N.A. N.A. N.A. N.A. N.A.
N.A. 6 N.A. N.A. N.A. N.A. N.A.
N.A. 7 N.A. N.A. N.A. N.A. N.A.
N.A. 8 N.A. N.A. N.A. N.A. N.A.
ZS 9 – – – X X
ZS (SOTF) 10 – – – X X
ZG 11 X X X – X
ZG (SOTF) 12 – – – X –
DISCAR 13 X X X – X
DEFCAR 14 X X X – X
N.A. 15 N.A. N.A. N.A. N.A. N.A.
SOTF-OC 16 – – – X X
STUB-OC 17 – – – X X
OC 18 – – – X X
EF 19 – – – X X
OCN 20 – – – X X
UC 21 – – – X X
THM 22 – – – X X
BCD 23 – – – X X
N.A. 24 N.A. N.A. N.A. N.A. N.A.
OV 25 – – – X X
OVS 26 – – – X X
OVG 27 – – – X X
N.A. 28 N.A. N.A. N.A. N.A. N.A.
OVN 29 – – – X X
UV 30 – – – X X
UVS 31 – – – X X
N.A. 32 N.A. N.A. N.A. N.A. N.A.
FRQ 33 – – – X X
DFRQ 34 – – – X X
N.A. 35 N.A. N.A. N.A. N.A. N.A.
N.A. 36 N.A. N.A. N.A. N.A. N.A.
N.A. 37 N.A. N.A. N.A. N.A. N.A.
N.A. 38 N.A. N.A. N.A. N.A. N.A.
N.A. 39 N.A. N.A. N.A. N.A. N.A.
N.A. 40 N.A. N.A. N.A. N.A. N.A.
Note: ‘N.A.’ represents ‘Not available for the IED’, ‘X’ represents a ‘Valid signal received
from the protection function’, ‘–’ represents that no ‘valid signal’ received in the

GRL200 (Soft 033 & 037)


- 404 -
6F2S1914 (0.37)

TRC function. ‘FC*_OPT_TRIP’ represents a three-pole trip signal. ‘ARC-BLOCK’


represents a signal used to block the operation of the ARC function; the ‘ARC-
BLOCK’ signal is transferred to the autoreclose function (ARC). Incidentally, the
term ‘FC*’ represents one of the relay elements connected to the TRC function.

Table 2.33-3 and Table 2.33-4 summarize the operation results in the TRC function. Table
2.33-3, shows the correspondents between the input signals (which are signals provided from
the protection functions) and their reasons (that is, types of faults). For example, if a fault
(1LG in phase A) occurs, ‘FC*_OPT_TRIP-A’ signal may be provided for the TRC function from
a protection function; the TRC function may generates ‘TRIP-COMMAN1-A’ and ‘TRIP-
COMMAND2-A’ signals when the scheme switch [TP-MODE]=PER-PHASE (see Table 2.33-4).
Note that Table 2.33-3 illustrates generic operation rules concerning fault types; the inputs
depend on the practical operation of relay functions. Hence, the user should figure out actual
inputs using Table 2.33-2 together with the characteristics of respective protection functions.

Note the TRC outputs will be influenced by the signals generated in the ARC function.
That is, when a CB1_BRIDGE or a CB1_94TT signal is generated and it is injected into the
TRC function, the TRC function is instructed to output a three-phase tripping (i.e., issuing
CB1_94TT following ARC1 FT or TPAR) or the TRC function is instructed to operate
unconditionally in three-phase tripping mode (i.e., issuing CB1_BRIDGE following ARC1
UNREADT). We shall see a number of operation settings [ARC1-MODE] and [ARC2-MODE] in
the ARC function.
Table 2.33-3 Trip command and its correspondent fault
Trip phase Inputs (See Table 2.33-2) Outputs
(Fault type) Trip signals coming from protection functions (FC*) Trip commands
Phase A (1LG) FC*_OPT_TRIP-A

Phase B (1LG) FC*_OPT_TRIP-B

Phase C (1LG) FC*_OPT_TRIP-C

Phase AB (L-L) FC*_OPT_TRIP-A and FC*_OPT_TRIP-B See Table 2.33-4

Phase BC (L-L) FC*_OPT_TRIP-B and FC*_OPT_TRIP-C

Phase CA (L-L) FC*_OPT_TRIP-C and FC*_OPT_TRIP-A

Phases ABC (3PH) FC*_OPT_TRIP (=FC*_OPT_TRIP-A & B & C)

No trip (Unfaulted) No input No output

GRL200 (Soft 033 & 037)


- 405 -
6F2S1914 (0.37)

Table 2.33-4 Trip commands


Outputs
Inputs
[TP-MODE]= 1- [TP-MODE]= 3- [TP-MODE]=
(see Table 2.33-3)
PHASE† PHASE‡ PER-PHASE
TRIP-COMMAND1-A TRIP-COMMAND1-A
FC*_OPT-TRIP-A
TRIP-COMMAND2-A TRIP-COMMAND2-A
TRIP-COMMAND1-B TRIP-COMMAND1-B
FC*_OPT-TRIP-B
TRIP-COMMAND2-B TRIP-COMMAND2-B
TRIP-COMMAND1-C TRIP-COMMAND1-C
FC*_OPT-TRIP-C
TRIP-COMMAND2-C TRIP-COMMAND2-C
TRIP-COMMAND1-A
FC*_OPT-TRIP-A TRIP-COMMAND1-B
FC*_OPT-TRIP-B TRIP-COMMAND2-A
TRIP-COMMAND1-A
TRIP-COMMAND2-B
TRIP-COMMAND1-B
TRIP-COMMAND1-B
TRIP-COMMAND1-C
FC*_OPT-TRIP-B TRIP-COMMAND1-C
TRIP-COMMAND1-A
FC*_OPT-TRIP-C TRIP-COMMAND2-B
TRIP-COMMAND1-B TRIP-COMMAND2-A
TRIP-COMMAND2-C
TRIP-COMMAND1-C TRIP-COMMAND2-B
TRIP-COMMAND1-C
TRIP-COMMAND2-C
FC*_OPT-TRIP-C TRIP-COMMAND1-A
TRIP-COMMAND2-A
FC*_OPT-TRIP-A TRIP-COMMAND2-C
TRIP-COMMAND2-B
TRIP-COMMAND2-A
TRIP-COMMAND2-C
TRIP-COMMAND1-A
TRIP-COMMAND1-B
FC*_OPT-TRIP-A
TRIP-COMMAND1-C
FC*_OPT-TRIP-B
TRIP-COMMAND2-A
FC*_OPT-TRIP-C
TRIP-COMMAND2-B
TRIP-COMMAND2-C
†Note: the tripping phase does not have the match with the phase of an input signal for
1-PHASE or 3-PHASE being set for the scheme switch [TP-MODE].
‡Note: Three-phase trip command is issued unconditionally for any fault at 3-PHASE.

Table 2.33-5 illustrates CBF function can generate a re-trip signal and an ARC-BLOCK signal.
Table 2.33-5 Signals coming from CBF function
Signals issued in the CBF
Protection function Note
CBF1_RETRIP CBF1_ARC-BLOCK
CBF X X
Note: ‘X’ represents a valid signal for the TRC’. The ‘CBF1_ARC-BLOCK’ signal is
grouped with the ‘FC*_OPT_ARC-BLOCK’ signal in the Sub-signal generation
scheme.

GRL200 (Soft 033 & 037)


- 406 -
6F2S1914 (0.37)

2.33.2 Recording identifiers for respective fault types


Table 2.33-6 shows an identifier signal for the recording function generated when a fault is
detected by the protection functions. That is, the identifier is generated in each protection
function (relay element) and is transferred to the recording function.
Table 2.33-6 Recording identifiers for relay operating elements for different faults
Fault identifier for relay element operated in each phase
Protection ID FC* FC*_OPT_ FC*_OPT_ FC*_OPT_ FC*_OPT_ FC*_OPT_ FC*_OPT_
functions ‘*’ _OPT_ AR BR CR ABR BCR CAR
ALARM Phase-A Phase-B Phase-C Phase-AB Phase-BC Phase-CA
DIFL 1 – X X X – – –
DIFGL 2 – – – – – – –
OSTV 3 – – – – – – –
DTT 4 – – – – – – –
N.A. 5 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. 6 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. 7 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. 8 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
ZS 9 – – – – X X X
ZS (SOTF) 10 – – – – X X X
ZG 11 – X X X – – –
ZG – X X X – – –
12
(SOTF)
DISCAR 13 – X X X X X X
DEFCAR 14 – X X X – – –
N.A. 15 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
SOTF-OC 16 X X X X – – –
STUB-OC 17 – X X X – – –
OC 18 X X X X – – –
EF 19 X – – – – – –
OCN 20 X – – – – – –
UC 21 X X X X – – –
THM 22 X – – – – – –
BCD 23 X – – – – – –
N.A. 24 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
OV 25 X X X X – – –
OVS 26 X – – – X X X
OVG 27 X – – – – – –
N.A. 28 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
OVN 29 X – – – – – –
UV 30 X X X X – – –
UVS 31 X – – – X X X
N.A. 32 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
FRQ 33 X – – – – – –
DFRQ 34 X – – – – – –
N.A. 35 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. 36 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. 37 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. 38 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. 39 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. 40 N.A. N.A. N.A. N.A. N.A. N.A. N.A.
Note: ‘X’ represents a ‘Valid signal’. ‘–’ is not ‘Valid signal’.

GRL200 (Soft 033 & 037)


- 407 -
6F2S1914 (0.37)

2.33.3 Scheme logic


(i) Trip-signal collection
Trip-signal collection gathers the trip signals provided by each protection function and groups
them to the trip operation commands “OPT-TRIP”, “OPT-TRIP-A”, “OPT-TRIP-B”, and “OPT-
TRIP-C” for General-trip-signal production, as shown in Figure 2.33-2.

The TRC logic has PLC connection points, which the user can program for issuing the
trip command. For example, if the user wishes to trip the CBs using signals generated by
external relays, the signals can be connected to the TRC logic using the following PLC
connection points: TRIP-A_ADD, TRIP-B_ADD, TRIP-C_ADD and TRIP_ADD.
Protection 8000001B60
functions FC*-OPT-TRIP_A
OPT-TRIP-A
≥1
FC01
800000EBB3 TRIP-A_ADD
FC02

8100001B61
FC*-OPT-TRIP_B
OPT-TRIP-B
≥1

810000EBB4 TRIP-B_ADD

FC40
8200001B62
FC*-OPT-TRIP_C OPT-TRIP-C
≥1

820000EBB5 TRIP-C_ADD

8300001B63
OPT-TRIP
FC*-OPT-TRIP

≥1

830000EBB6 TRIP_ADD

Figure 2.33-2 Scheme logic for Trip-signal collection

(ii) General-trip-signal production


Figure 2.33-3 illustrates the general-trip-signal production logic. The user can program the
generation of trip signals using the PLC connection point “ADD_OPT_COM”, when trip signals
are not available from the relay functions.

The TRC function has a scheme switch [TP-MODE] to determine a trip mode; hence, the
user can select either single-phase trip mode (1-PHASE) or three-phase trip mode (3-PHASE)
or per-phase trip mode (PER-PHASE) for the CB tripping. Table 2.33-4 has shown the output
signals when the TRC function receives the trip signals from the protection functions. Note
that the scheme switch [TP-MODE] is only applicable when a phase trip mode (1P) is set in a
protection function (i.e., the user should set trip-phase selectors using [TPMD] settings, which
some protection functions have. If single-phase trip signals are not generated in the protection

GRL200 (Soft 033 & 037)


- 408 -
6F2S1914 (0.37)

functions, the scheme switch [TP-MODE] is useless.

The “GEN.TRIP-A,-B,-C” signals are transferred to the ARC function to initiate the
reclose operation of the CBs.
To ARC
8200001BB2 GEN.TRIP-A
820000EBB2 ADD_OPT_COM GEN.TRIP-B

GEN.TRIP-C
Trip-command To ZG
≥1
collection scheme GEN.TRIP
OPT-TRIP-A ≥1
& 8000001B6C
8014281001 To CB#1
≥1
OPT-TRIP-B ≥1
≥1 8100001B6D
≥1 TRIP COMMAND1-A
&
8014291001
≥1
OPT-TRIP-C ≥1 TRIP COMMAND1-B
≥1 8200001B6E ≥1
& 80142A1001
OPT-TRIP ≥1 ≥1
≥1 TRIP COMMAND1-C

≥1 & ≥1
& 80142C1001 To CB#2
&
≥1 TRIP COMMAND2-A
80142D1001
& &
≥1 ≥1 TRIP COMMAND2-B
& 80142E1001
& & ≥1 TRIP COMMAND2-C

&

1-PHASE
TP-MODE 3-PHASE
PER-PHASE
≥1

8000001BB0

800000EBB0 TPMODE_3PH

8100001BB1 To Recording function


810000EBB1 ADD-FS TRIP COMMAND1-A
≥1 ≥1 ≥1
& TRIP COMMAND1-B
From FS
FSRY_OP ≥1 TRIP COMMAND1-C
≥1
& TRIP COMMAND CB2 -A
≥1 TRIP COMMAND CB2 -B
≥1 & TRIP COMMAND CB2 -C
From CBF ≥1
&
CBF1_RETRIP-A
CBF1_RETRIP-B
CBF1_RETRIP-C

CBF2_RETRIP-A
CBF2_RETRIP-B
CBF2_RETRIP-C
From ARC
CB1_BRIDGE
CB2_BRIDGE
CB1_94TT
CB2_94TT

From PROT-COMMON
CB-SYSTEM=1CB
CB-SYSTEM=2CB

Figure 2.33-3 Logic for general trip and CB trip signals


Acquisition of fail-safe signal provided externally
If an external relay is available to provide a fail-safe check for the internal operation of the
IED, and the user wishes to use the output of the external relay in order to enhance the
reliability of tripping further, then the PLC connection points ‘ADD-FS’ can be used in the Trip-
signal generation scheme. That is, the external check signal is connected at the ‘ADD-FS’ point.

Acquisition of external trip command


As the PLC connection point ‘ADD_OPT_COM’ is provided, the TRC function can accept a trip
command that is generated externally.

GRL200 (Soft 033 & 037)


- 409 -
6F2S1914 (0.37)

Provision of trigger signals to Recording functions


The ‘TRIP COMMMAND1-A, -B, -C’ and ‘TRIP COMMMAND2-A, -B, -C’ signals are viable to
operation of Recording function, which we shall see in Chapter Recording function.

Provision for distance relay


The ‘GEN.TRIP’ signal is provided to direct the operation of the UVPWI relay in the distance
protection function, which we shall see in Chapter Relay application: Distance protection.

(iii) CB trip signal production


As illustrated in Figure 2.33-3, the ‘TRIP COMMMAND1-A, -B, -C’ and ‘TRIP COMMMAND2-
A, -B, -C’ signals are transferred to trip coils of the CB#1 and CB#2 when the signals “OPT-
TRIP-A, -B, and -C” or “OPT-TRIP” enter into the TRC function.

CB trip signals for 1CB system


When the TRC function operates in a single CB (1CB) system; the “TRIP COMMMAND1-A, -
B, -C” signals should be connected with BO circuits.
Table 2.33-7 Output signals for single CB#1
Output signals Usage of signals
TRIP-COMMMAND1-A CB trip in phase A
TRIP-COMMMAND1-B CB trip in phase B
TRIP-COMMMAND1-C CB trip in phase C

CBs trip signals for 1.5CB system


When the TRC function can operate in a single-and-a-half breaker system (1.5CB); the other
“TRIP COMMMAND2-A, -B, -C” signals also should be connected with other BO circuits. Table
2.33-8 summarizes the outputs signals of the TRC function in the 1.5CB system.
Table 2.33-8 Output signals for CB#1 and CB#2 in 1.5CB system
Output signals Usage of signals
TRIP-COMMMAND1-A CB#1(Bus CB) trip in phase A
TRIP-COMMMAND1-B CB#1(Bus CB) trip in phase B
TRIP-COMMMAND1-C CB#1(Bus CB) trip in phase C
TRIP-COMMMAND2-A CB#2(Center CB) trip in phase A
TRIP-COMMMAND2-B CB#2(Center CB) trip in phase B
TRIP-COMMMAND2-C CB#2(Center CB) trip in phase C

(iv) Sub-signal generation


In a similar way to the Trip-signal collection, the Sub-signal generation groups the blocking
signals for ARC operation; it groups them into ‘GEN.ARC-BLOCK’ signal, as illustrated in
Figure 2.33-4. Blocking signal from the CBF function is also integrated into the ‘GEN.ARC-
BLOCK’ signal; then it is transferred to the ARC function.

GRL200 (Soft 033 & 037)


- 410 -
6F2S1914 (0.37)

8500001B65
Protection
functions FC*-ARC-BLOCK
FC01 To ARC function
≥1 8500001B79
FC02
GEN.ARC-BLOCK

≥1
FC40
From CBF function

CBF1 CBF1-ARC-BLOCK

CBF2 CBF2-ARC-BLOCK

Figure 2.33-4 Scheme logic for Sub-signal generation

(v) Alarm-signal generation


Figure 2.33-5 shows the alarm-signal generation logic. The signals in Table 2.33-6 are collected
and grouped into OPT.PHASE-A, OPT.PHASE-B, OPT.PHASE-C, OPT.PHASE-N, and
GEN.TRIP_ALARM signals.
8000001B66 To Recording function
8000001B71
Protection OPT-AR ≥1 &
functions FC*-OPT-AR OPT.PHASE-A
≥1
FC01
880000EBB8 OPT.P-A_ADD
FC02
8100001B67

FC*-OPT-BR ≥1 8000001B72
OPT-BR &
≥1 OPT.PHASE-B

890000EBB9 OPT.P-B_ADD

8200001B68
FC40
8000001B73
FC*-OPT-CR OPT-CR ≥1 &
OPT.PHASE-C
≥1

8A0000EBBA OPT.P-C_ADD

8000001B74
8400001B69 &
OPT.PHASE-N
FC*-OPT-ABR OPT-ABR
≥1

8C0000EBBB OPT.P-AB_ADD 8000001B77


GEN.TRIP_ALARM
8500001B6A

FC*-OPT-BCR OPT-BCR
≥1

8D0000EBBC OPT.P-BC_ADD

8600001B6B

FC*-OPT-CAR OPT-CAR
≥1

8E0000EBBD OPT.P-CA_ADD

8400001B64

FC*_OPT-ALARM GEN.ALARM ≥1
≥1

840000EBB7 OPT-ALARM_ADD

Logic for general trip and trip command GEN.TRIP

800000EBBE OPT.P-N_ADD

Figure 2.33-5 Scheme logic for Alarm-signal generation

GRL200 (Soft 033 & 037)


- 411 -
6F2S1914 (0.37)

When an alarm signal indicating a Line-to-Line (LL) fault and others is provided
externally, the user can also record it as the alarm by the use of PLC connection points ‘OPT.P-
A_ADD’ and others. If the additional relay being designed to operate for a ground fault is
available, use the alternative PLC connection point ‘OPT.P-N_ADD’.

GRL200 (Soft 033 & 037)


- 412 -
6F2S1914 (0.37)

2.33.4 Setting
TRC(Function ID: 4A0001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
1-Phase / 3-Phase / Per-
TP-MODE - Trip mode selection Per-Phase
Phase

GRL200 (Soft 033 & 037)


- 413 -
6F2S1914 (0.37)

2.33.5 Data ID
 Signal monitoring point
TRC(Function ID: 4A0001)
Element ID Name Description
8100001BB1 ADD_FS Additional fail-safe command

8200001BB2 ADD_OPT_COM Additional operation command

8400001B64 GEN.ALARM operation (GEN.ALARM)

8300001B6F GEN.TRIP General trip

8000001B6C GEN.TRIP-A General trip (Phase-A)

8100001B6D GEN.TRIP-B General trip (Phase-B)

8200001B6E GEN.TRIP-C General trip (Phase-C)

8000001B77 GEN.TRIP_ALARM General trip or General alarm

8400001B69 OPT-ABR operation (ABR)

8400001BB7 OPT-ALARM_ADD Additional alarm output command

8000001B66 OPT-AR operation (AR)

8500001B65 OPT-ARC-BLOCK operation (ARC-BLOCK)

8500001B6A OPT-BCR operation (BCR)

8100001B67 OPT-BR operation (BR)

8600001B6B OPT-CAR operation (CAR)

8200001B68 OPT-CR operation (CR)

8300001B63 OPT-TRIP operation (trip)

8000001B60 OPT-TRIP-A operation (phase-A)

8100001B61 OPT-TRIP-B operation (phase-B)

8200001B62 OPT-TRIP-C operation (phase-C)

8C00001BBB OPT.P-AB_ADD Additional operated phase-AB command

8800001BB8 OPT.P-A_ADD Additional operated phase-A command

8D00001BBC OPT.P-BC_ADD Additional operated phase-BC command

8900001BB9 OPT.P-B_ADD Additional operated phase-B command

8E00001BBD OPT.P-CA_ADD Additional operated phase-CA command

8A00001BBA OPT.P-C_ADD Additional operated phase-C command

8000001BBE OPT.P-N_ADD Additional operated phase-N command

8000001B71 OPT.PHASE-A Operating phase-A

8100001B72 OPT.PHASE-B Operating phase-B

8200001B73 OPT.PHASE-C Operating phase-C

8300001B74 OPT.PHASE-N Operating phase-N

8000001BB0 TPMODE_3PH 3-phases trip permissive command

8000001BB3 TRIP-A_ADD Additional A-phase trip command

8100001BB4 TRIP-B_ADD Additional B-phase trip command

8200001BB5 TRIP-C_ADD Additional C-phase trip command

8300001BB6 TRIP_ADD Additional trip command

8000001B20 TRIP_COMMAND1-A Trip command 1 (Phase-A)

8100001B21 TRIP_COMMAND1-B Trip command 1 (Phase-B)

8200001B22 TRIP_COMMAND1-C Trip command 1 (Phase-C)

8000001B24 TRIP_COMMAND2-A Trip command 2 (Phase-A)

8100001B25 TRIP_COMMAND2-B Trip command 2 (Phase-B)

8200001B26 TRIP_COMMAND2-C Trip command 2 (Phase-C)

GRL200 (Soft 033 & 037)


- 414 -
6F2S1914 (0.37)

 Connection point in PLC logic


TRC(Function ID: 4A0001)
Element ID Name Description
810000EBB1 ADD_FS Additional fail-safe command

820000EBB2 ADD_OPT_COM Additional operation command

840000EBB7 OPT-ALARM_ADD Additional alarm output command

8C0000EBBB OPT.P-AB_ADD Additional operated phase-AB command

880000EBB8 OPT.P-A_ADD Additional operated phase-A command

8D0000EBBC OPT.P-BC_ADD Additional operated phase-BC command

890000EBB9 OPT.P-B_ADD Additional operated phase-B command

8E0000EBBD OPT.P-CA_ADD Additional operated phase-CA command

8A0000EBBA OPT.P-C_ADD Additional operated phase-C command

800000EBBE OPT.P-N_ADD Additional operated phase-N command

800000EBB0 TPMODE_3PH 3-phases trip permissive command

800000EBB3 TRIP-A_ADD Additional A-phase trip command

810000EBB4 TRIP-B_ADD Additional B-phase trip command

820000EBB5 TRIP-C_ADD Additional C-phase trip command

830000EBB6 TRIP_ADD Additional trip command

GRL200 (Soft 033 & 037)


- 415 -
6F2S1914 (0.37)

Autoreclose (ARC)
The basic objective of auto-reclosing is to restore automatically the transmission line back into
service, after being tripped by line protection relays, without depending on the operator action.
The use of auto-reclosing will improve the system stability and reliability. The choice of the
auto-reclosing type, such as, one or more reclosing shots, high speed or delayed, single-phase
or multi-phase depends on the characteristics of the transmission and protective system
together with the utility practice. The suitability of a particular auto-reclosing scheme may
also be established by conducting a transient analysis study of the interconnected electrical
network.

─────────────────────────────────────────────────────────────────
Note: Several IED models do not have auto-reclosing features. To determine whether the
features are implemented in the IED or not, locate the IED ordering number; and check the
order number at “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 2.34-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
ARC Auto-reclosing ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 416 -
6F2S1914 (0.37)

2.34.1 Overview
Table 2.34-2 summarizes the reclosing operations and the modes in the ARC function. The
ARC function can operate for both a single CB arrangement and double CBs (1.5CB)
arrangement; hence, the ARC function is grouped into two logics: ARC1 for CB#1 and ARC2
for CB#2. Note that multi-shots scheme is only available for 1CB arrangement (CB#1). The
‘ORIGINAL’ is provided for the user’s programing.
Table 2.34-2 ARC operation modes and shot numbers
1CB or 1.5CB arrangement Parallel lines
Reclosing
Shot number 1CB 1.5CB 1CB 2CB
mode
ARC1 ARC2 ARC1&2 ARC1 ARC1&2
SPAR X (N.A) x (N.A) (N.A)
ARC1 SHOT1 TPAR X (N.A) x (N.A) (N.A)
or/and SPAR&TPAR X (N.A) x (N.A) (N.A)
ARC2 SHOT MPAR (N.A) (N.A) (N.A) x x
ORIGINAL X (N.A) x (N.A) (N.A)
ARC1 SHOT2 X (N.A) (N.A) x (N.A)
ARC1 SHOT3 X (N.A) (N.A) x (N.A)
ARC1 SHOT4 X (N.A) (N.A) x (N.A)
ARC1 SHOT5 X (N.A) (N.A) x (N.A)
x: Operation is applicable N.A: Operation is not applicable

(i) Breaker system


The ARC function can operate in several breaker systems, as shown in Figure 2.34-1. For the
1.5CB arrangement, the ARC1 and ARC2 logics operate separately; the user can select
different reclosing scheme (Figure 2.34-1.b). In parallel lines, the ARC function can take
several reclosing schemes when the communication application (COMM_APPL) is available
(Figure 2.34-1.c).

GRL200 (Soft 033 & 037)


- 417 -
6F2S1914 (0.37)

CB#1
Line Busbar G

Line VT Bus VT
CB#1 Reclosing for CB#1
Relay(G)
Bus VT VCHK1(G) VCHK1(G)
Line VT
ARC1(G)
VCHK2(G)
ARC1(G) ARC2(G)
Reclosing CB#1
Line1
Busbar G
CB#2
Reclosing for CB#2

Line VT

Line2

[ARC1-MODE]= FT / SPAR / TPAR / SPAR&TPAR [ARC1-MODE]= FT / SPAR / TPAR / SPAR&TPAR


[ARC2-MODE]= Off [ARC2-MODE]= FT / SPAR / TPAR / SPAR&TPAR

a.1CB arrangement system (CB#1) b. 1.5 CB arrangement (CB#1 and CB#2)

Busbar G CB#1 CB#1 Busbar R


Line GR

Relay(G) Reclosing assisted by Relay(R)


the communication
ARC1(G) ARC1(R)
Reclosing CB#1 Reclosing CB#1

CB#1 CB#1
Line HS

Relay(H) Relay(S)

ARC1(H) ARC1(S)
Reclosing CB#1 Reclosing CB#1

[ARC1-MODE]= MPAR [ARC2-MODE]= Off


[MPAR-MODE]= M2/M3

c. Parallel lines (CB#1)

Figure 2.34-1 Breaker systems

(ii) Reclosing modes in 1CB and 1.5CB


Single-phase auto reclose (Setting [ARC1-MODE]=SPAR)
A faulted phase is tripped by relay applications if a single-phase earth fault occurs; then the
ARC function tries to recloses the CB. In the case that the phase-to-phase (or multi-phases)
fault occurs, the CB is tripped forcibly in three-phases by the instruction of the ARC function
regardless of the fault detection of relay application; the ARC function does not try to reclose
the CB. For the SPAR mode, reclosing the CB is performed without the synchronism check and
voltage check.

Three-phase auto reclose (Setting [ARC1-MODE]=TPAR)

GRL200 (Soft 033 & 037)


- 418 -
6F2S1914 (0.37)

The CB is tripped forcibly in three-phases whether the relay applications detect single-phase
fault type or multi-phase fault type; then, the CB will be reclosed by the ARC function. To
reclose the CB, the permission signal of the voltage and synchronism check (VCHK†) function
is required in the TPAR mode.

†Note:VCHK are automatically applied in the TPAR mode (for ARC1 SHOT1 and ARC2
SHOT). For more information, see Chapter Relay application: Voltage check for
auto reclose.

Single- and three-phase auto reclose (Setting [ARC1-MODE]=SPAR&TPAR)


The CB is tripped in single-phase by the fault detection of relay applications if a single-phase
fault occurs; the ARC function tries to reclose the CB. Three-phase tripping is performed if a
multi-phase fault occurs; then, the CB will be reclosed by the ARC function. Note that the
VCHK permission signal is required to reclose the CB in the three-phase tripping (i.e., TPAR
scheme), but the VCHK permission signal is not required in signal-phase tripping (i.e., SPAR
scheme).

Setting selection about SPAR and TPAR modes


Since power can be transmitted through healthy phases even during the dead time, the SPAR
mode is convenient for maintaining power system stability. On the other hand, the capacitive
coupling effect between the healthy phase and faulty phase may cause a longer de-ionization
time when compared to the TPAR mode. That is, a longer dead time is required in the TPAR
mode. A shorter dead time can be set in the TPAR mode when compared to the SPAR mode.

For the TPAR mode in the 1.5CB arrangement, synchronism check and voltage check
(VCHH) between the bus bar (for bus CB#1) and the line or between the two lines (for center
CB#2) are required. The reclosing order between CB#1 and CB#2 can be selected using setting
[ARC-ORDER]; that is, CB#1 recloses first followed by CB#2 (i.e., [ARC-ORDER]=CB1)or vice
versa (i.e., [ARC-ORDER]=CB2). Simultaneous closure of CB#1 and CB#2 can also be selected
(i.e., [ARC-ORDER]=SIMUL).

(iii) Reclosing mode in parallel lines (Setting [ARC1-MODE]=MPAR)


Only the faulted phases are tripped and reclosed, when the terminals of parallel lines are
interconnected during the dead time, through at least two or three different phases. The MPAR
mode realizes high-speed reclosing for multi-phase faults without synchronism and voltage
check (VCHK) and minimizes the possibility of outages in the case of double faults on parallel
lines. If the interlinking condition is not satisfied, and reclosing is conditionally permitted
based on the result of Link judgment logic. The user has to select a reclosing mode and the
number of healthy phases when the fault occurs (i.e., Settings [ARC-MANOLK] and [MPAR-

- 419 - GRL200 (Soft 033 & 037)


6F2S1914 (0.37)

MODE]).

(iv) User configurable autoreclose (Setting [ARC1-MODE]=Original)


In the user configurable auto reclose mode (ORIGINAL), the user can manage the scheme of
the ARC procedure and it allows the user program the ARC function by the PLC function.

(v) Number of reclosing shots


Single-shot autoreclose (Setting [ARC-NUM]=S1 in 1CB)
In single-shot autoreclose scheme, autoreclose is performed only once. If the fault cannot be
cleared after reclosing, the ARC function reaches final tripping stage (ARC1 FT) and the ARC
function instructs the TRC to make three-phase tripping (94CB1_TT). The first shot (ARC1
SHOT1) is just issued when setting [ARC-NUM]=S1, as described in Table 2.34-2.

Multi-shot autoreclose (Setting [ARC-NUM]=S2/S3/S4/S5 in 1CB)


Any of the two-shot (S2) to five-shot (S5) reclosing can be selected in multi-shot autoreclose
scheme. Successive shots (ARC1 SHOT2 to ARC1 SHOT5) are three-phase tripping and
reclosing, if the first shot (ARC1 SHOT1) fails. For ‘ARC1 SHOT2’ to ‘ARC1 SHOT5’, which
are applied in three-phase reclosure, the user shall introduce a permission signal by PLC
programming or the voltage and synchronism check signal. Closing status of the CB main
contact can be monitored in the PROT_COMM function; the ARC function can evaluate the
successful reclosing-operation after issuing the shots (ARC1 SHOT1 and others). A failure
(ARC1 CLOSE FAIL) is signaled if the CB#1 fails to close after issuing the ‘ARC1 SHOT1 and
others’.

Signle-shot autoreclose (Setting [ARC-NUM]=S1 in 1.5CB)


Note that multi-shot autoreclose will not be applied in the 1.5CB busbar arrangement. The
first shot (ARC1 SHOT1/ARC2 SHOT) is just issued for the CB#1 and the CB#2. Closing status
of the CB#1 and CB#2 main contacts can be monitored in the PROT_COMM function; the ARC
function issues a failure signal (ARC1 CLOSE FAIL or ARC2 CLOSE FAIL) if a CB fails to
close after issuing the ‘ARC1 SHOT1’ or ‘ARC2 SHOT’.

(vi) Operation failure in tripping CB


A check is required to determine whether the CB have been tripped to open properly when the
relay applications detect the fault. If the CB cannot open within the required time, a failure
signal “CB fail to open” is indicated; the ARC function resets the reclose operation of the CB
and a shot is not issued.

(vii) Final trip stage


When the ARC function detects the following conditions, the ARC function goes to ‘Final trip’

GRL200 (Soft 033 & 037)


- 420 -
6F2S1914 (0.37)

stage, which the ARC issues a three-phase trip signal (CB1_94TT or CB2_94TT) for the TRC
function; the ARC function abandons to reclose the CB#1 and CB#2 (ARC1 FT or ARC2 FT).
 CB is not ready for ARC operation
 Failure to issue ARC shot
 ARC block command has come through PLC connection points
 Multi-phase trip in SPAR mode
 Evolving fault (single phase to multiphase) in SPAR and TPAR mode
 No link within parallel lines in MPAR mode; ( final trip selected)
 Final trip selected for 3-phase fault (user settable)
 ARC close fail
 Shot number over

GRL200 (Soft 033 & 037)


- 421 -
6F2S1914 (0.37)

2.34.2 Terminology
The terminology and signals outlined below are applicable for single CB#1 system. Signals
applicable for CB#2 in a two (2) CB system are similar and are not included for clarity.

(i) Relay operation period


The time interval commencing from the instant of the relay picking-up for the fault current to
the instant of the relay dropping-off following the cessation of the fault current.

(ii) Temporary/transient/Arc fault


A transient/temporary fault, the main cause of which is often due to lightning, (an over voltage
induced in a line due to the static electricity caused by the lightning may cause a flash over
across the insulator string), temporary contact with foreign objects, conductor clashing as a
consequence of strong wind.

(iii) Arcing time of CB


When the CB#1 contacts separate during tripping, an arc is produced between the CB#1
contacts; the arc is extinguished by the interrupting medium in the CB#1. The duration of
arcing is called the ‘Arcing time’, which is the time between the instant of separation of the
circuit breaker contacts and the instant of the extinction of the fault arc.

(iv) Permanent fault (Signal ‘ARC1 FT’)


Fallen conductors, tree growth, tree branches that have fallen across lines, as well as other
causes, may all produce permanent faults. As the operation of the ARC function is unable to
restore power transmission for permanent faults, the ARC function abandons the reclosing of
the CB#1, defined as the ‘Final trip (ARC1 FT)’ stage. If the ARC function gets into the ‘ARC1
FT’ stage, closing the CB#1 is only possible by the manual operation.

(v) Signal shot scheme (Signal ‘ARC1 SHOT1’)


The ARC function issues a first auto-reclosing signal ‘ARC1 SHOT1’ when a ‘GEN.TRIP’ signal
is issued in the trip circuit (TRC†) by the first relay operation. When the user programs the
ARC function not to provide subsequent reclosures, this operating sequence provides only one
reclosing operation; then, lockout will occur on subsequent tripping, i.e. the ‘Final trip (ARC1
FT)’ stage.

†Note:For more information, see chapter Relay application: Trip circuit.

(vi) Multi shot scheme (Signals ‘ARC1 SHOT2–5’)


Signals ‘ARC1 SHOT2’ to ‘ARC1 SHOT5’ may be issued after the ‘ARC1 SHOT1’ signal when
a persistent fault occurs.

GRL200 (Soft 033 & 037)


- 422 -
6F2S1914 (0.37)

(vii) Dead time (Delay timers TTPAR† and TD_MS2–5)


The dead time is the time interval from relay operation i.e. the initiation of the auto-reclose
scheme, to the inception of the ‘ARC1 CLOSE COMMAND’ used to energize the circuit breaker
closing circuit and is provided by delay timer [TTPAR1]. A substitute delay timer
[TTPAR1_SUB] is also available when the user wishes to program the inception of the ‘ARC
1SHOT1’ signal using the PLC function instead of [TTPAR1], this feature is only provided in
the event that the user wishes to replace the original logic.

The dead times for sequential operation of the autoreclose scheme ‘ARC1 SHOT2’ to
‘ARC1 SHOT5’, are provided by delay timers [TD_MS2]–[TD_MS5], respectively.

†Note:delay timer [TTPAR] is available when the ARC function operates in TPAR mode.
For the operation in other SPAR, MPAR, and ORGAR modes, the user should also
set values for delay timers [TSPAR1], [TMPAR1], and [TORGAR1].

(viii) Pulse width of ‘ARC1 CLOSE COMMAND’ (Setting TCCW1)


An ‘ARC1 CLOSE COMMAND’ signal is issued after the dead time. Setting [TCCW1] is used
to define the pulse-width of the reclosing commands for respective shots1–5.

(ix) Final trip stage to abandon CB reclosure (Signal ‘ARC1 FT’ and
setting TRR1, TRR_MS2–5)
TRR1 is the time from the ARC1 initiation to abandoning issuing the ‘ARC1 SHOT1’. In TPAR†
mode the permissive signal ‘ARC1-VCHK’ must be issued by the VCHK function within the
time interval of TRR1 at the end of the dead time (i.e., TRR1 has not timed out), otherwise the
ARC function abandons the reclosure of CB#1. That is, if TTPAR1 has timed out and ‘ARC1-
VCHK’ permissive has not been issued within TRR1 time, TRR1 signal yielded in the TPAR
mode ends up ‘Final Trip (ARC1 FT)’. Note that the timer setting of the [TRR1] timer should
be set greater than that applied to the dead time delay timer [TTPAR1] to ensure that the dead
time has fully expired.

Likewise, for shots 2–5 the timers [TRR_MS2] and others issue the signal for ‘Final Trip
(ARC1 FT)’ if the respective shots are not issued within the set time.

†Note:We can see similar ARC behavior in the other SPAR, MPAR, and ORGAR modes.

(x) Reset for tripping failure (Signal ‘ARC1 RESET’ and setting TRESET)
Subsequent to the reception of the ‘GEN.TRIP’ signal, a check is required to determine whether
the CB#1 has opened. If the CB#1 has not opened within the time setting of timer [TRESET],
then “CB#1 failing to be opened” is judeged by the ‘ARC1 RESET’ signal, which also resets the

GRL200 (Soft 033 & 037)


- 423 -
6F2S1914 (0.37)

reclose operation of the CB#1. The duration of the setting applied to the [TRESET] timer must
be less than the setting applied to the ARC dead time delay timers (e.g. [TTPAR] etc.).

(xi) Decision time for successful operation or failure (Setting TARCSUC


and signals ‘ARC1 CLOSE SUCCESS’, ‘ARC1 CLOSE FAIL’, ‘ARC1
SHOT RS’)
The [TARCSUC] timer provides the following functionality depending on the setting of scheme
switch [ARC-SucChk].

Scheme switch [ARC-SucChk]=On


With [ARC-SucChk] set to On, timer [TARCDSUC] is used to define the checkpoint at which
the CB#1 (and #2) are closed successfully after issuing the ‘ARC1(or 2) CLOSE COMMAND’
signal following which, an ‘ARC1( or 2) CLOSE SUCCESS’ signal is issued.

If the CB fails to close within the setting of timer [TARCSUC],an ‘ARC1 CLOSE FAIL’ signal
is issued and the ARC1 function moves to the ‘Final trip (ARC1 FT)’ stage.

Successful reclose of the CB (subsequent to fault clearance) is checked by the ‘Success


check’ logic, which checks for the signal ‘CB1_ALLPH_CLOSE’ provided by the protection
common function (PROT_COMMON). Clearing the fault automatically resets the ARC1
operation.

Scheme switch [ARC-SucChk]=Off


With [ARC-SucChk] set to Off, timer [TARCSUC] may be used to check for a successful closure
following the issue of the ‘ARC1 SHOT’ command. The ‘ARC1 SHOT RS’ signal is generated
which is used for resetting the ARC function about the CB#1 reclosure.

Note: a CB failure to close condition cannot be detected; the user shall incorporate the
check scheme externally.

(xii) Progress of ARC operation (Signals ‘ARC1 IN-PROG’ and others)


Information regarding the progress of an ARC operation is provided following the reception of
the ‘GEN.TRIP-A/B/C’ signals as follows:

Entire ARC progress for all shots (signal ‘ARC1 IN-PROG’)


The ‘ARC1 IN-PROG’ signal is defined for the time from issuing the first ‘GEN.TRIP-A/B/C’ to
the confirmation of the ARC successful operation or the final trip.

Respective progress for respective shots (signal ‘ARC1-S* IN-PROG/OR’)

GRL200 (Soft 033 & 037)


- 424 -
6F2S1914 (0.37)

Respective signals ‘ARC1-S* IN-PROG’ are defined for the operation of respective shots. A
common ‘ARC1 IN-PROG OR’ is also issued.

Trigger for the ARC operation (signal ‘ARC_START’)


The ‘ARC_START’ signal shows the instant at which ‘GEN.TRIP-A/B/C’ signals are given from
the TRC function. If an external relay can generate the ‘ARC_START’ signal, the user can use
it by programing the binary input circuit (BI) in the PLC function.

Tripped phases (signals ‘TRIP-ANYPH’, ‘TRIP-1PH’, ‘TRIP-MPH’, ‘TRIP-3PH’)


Start logic also decides whether the trip mode is single-phase, multi-phase or three-phases.
These signals are used for issuing ARC1 SHOT1 in SPAR/TPAR/MPAR modes.

(xiii) Reclaim timer (Setting ‘TREADY’)


Certain considerations are required to ensure that the ARC function is ready for the next cycle
of operation; the reclaim timer ‘TREADY’ is provided within the ARC function to accommodate
this requirement. When a CB is closed for the first time subsequent to the maintenance of a
distribution line, the closure would normally be expected to be successful (that is, the CB is
closed on to a healthy line). Then the minimum time setting of the [TREADY] reclaim timer
should be longer than the time required to judge that the CB has closed successfully.

Another consideration required for this setting is that after the CB has gone through a
successful ARC cycle; the maximum allowable successive close-open operations are achieved
with the setting. In this case, the minimum time delay required before the CB is ready for the
next ARC cycle becomes the setting criteria for the [TREADY] timer.

Where the incidence of recurrent lightning strikes is experienced, a shorter reclaim time
will prevent the ARC function going into an unnecessary lock out. On the other hand, caution
is required when considering the exposure of the CB to an excessive number of ARC cycles
caused by recurrent faults which will result in an increase in the frequency of the maintenance
cycle.

In summary, the time required for the CB to be ready for the next cycle of ARC is the minimum
setting that can be applied to the reclaim timer [TREADY] in the ARC function.

(xiv) CB bridge (Signal ‘CB1_BRIDGE’)


The ‘CB1_BRIDGE’ signal is thrown into the TRC function when the ARC1 logic fails to be
‘Ready condition’. The ‘CB1_BRIDGE’ signal ensures three-phase tripping in the CB#1 when
a per-phase trip signal is provided in the TRC function.

GRL200 (Soft 033 & 037)


- 425 -
6F2S1914 (0.37)

(xv) Condition logic (Signals ‘ARC1_SPAR_COND’, ‘ARC1_TPAR_COND’)


The ‘Condition’ logic issues the above signals depending on the setting [ARC1 MODE] and the
tripped phases (i.e., signal ‘TRIP-ANYPH’ and others). This logic is available when the setting
[ARC1 MODE] = SPAR, TPAR, or SPAR&TPAR.

(xvi) Link judgment (setting MPAR-MODE and signals ‘MPAR_LINK’)


With regard to the power transmission between terminals, the ‘Link judgment’ logic issues the
healthy phases that are left during a fault in parallel lines. This logic is available when the
settings [ARC1 MODE] = MPAR and [ARC-MANOLK] = TPAR or SPAR&TPAR.

GRL200 (Soft 033 & 037)


- 426 -
6F2S1914 (0.37)

2.34.3 Function block diagram


The function diagrams for respective modes are illustrated; they represents the general flow
of the logic in the ARC1 function. For simplicity, the function block diagrams are represented
for CB1 in a 1CB arrangement in Figure 2.34-2, Figure 2.34-3, and Figure 2.34-4; the logics
are similar for CB2 in the 1.5CB arrangement except that only a single shot is permitted in
the 1.5CB arrangement. Note that the logics are shown for a two (2) shot scheme for simplicity.

Each functional block diagram is grouped into a number of logic blocks; four typical functional
block diagrams are illustrated below:
(i) Issuing ‘ARC SHOT1’ and ‘ARC SHOT2’ in 1 CB of the SPAR mode
(ii) Issuing ‘ARC SHOT1’ and ‘ARC SHOT2’ in 1 CB of the TPAR mode
(iii) Issuing ‘ARC SHOT1’ and ‘ARC SHOT2’ in 1 CB of the SPAR and TPAR mode
(iv) Issuing ‘ARC SHOT1’ and ‘ARC SHOT2’ in MPAR of parallel lines

GRL200 (Soft 033 & 037)


- 427 -
6F2S1914 (0.37)

(i) SPAR mode


Figure 2.34-2 illustrates the ARC function when settings of are performed in both Table 2.34-3
and Table 2.34-4.
Table 2.34-3 Block parts in SPAR mode
Block parts Corresponding logics Detailed logic
[1] ARC1-Mode input Figure 2.34-11
[2] Shot number Figure 2.34-13
[3] Start Figure 2.34-14
[4] Initiation Figure 2.34-15
[5] Shot counter Figure 2.34-16
[6] Condition Figure 2.34-17
[7] ARC1 SPAR Figure 2.34-18
[8] ARC1 SHOT2 Figure 2.34-21
[9] Issuing Figure 2.34-22
[10] Success check Figure 2.34-23

Table 2.34-4 Setting examples in SPAR mode


Categories Items Settings Corresponding logics
ARC1-EN On
ARC1-Mode SPAR Figure 2.34-11
ARC2-EN Off
ARC general
ARC2-Mode Off Figure 2.34-12
Multi Shot-EN On
ARC-NUM S2 Figure 2.34-13
TREADY 60.0s Figure 2.34-15
TSPAR1 0.80s Figure 2.34-18
ARC1 TSPAR1_SUB 300.00s Figure 2.34-18
TRR1 2.00s Figure 2.34-18
TCCW1 0.20s Figure 2.34-22
TD_MS2 20.00s Figure 2.34-21
ARC1 multi-shot
TRR_MS2 30.00s Figure 2.34-21
ARC-SucChk On Figure 2.34-23
TARCSUC 0.30s Figure 2.34-23
FT-3pFault Off Figure 2.34-14
ARC misc.
TRESET 0.30s Figure 2.34-15
TEVLV 0.30s Figure 2.34-17
SHOTNUM-TEST Off Figure 2.34-16
PROT-COMMON CB-System 1CB See Protection common function
VCHK ARC1-VCHK EN Off VCHK signal not required
TRC TP-MODE Per-Phase See Trip circuit

GRL200 (Soft 033 & 037)


- 428 -
800001EBCF ARC1_BLOCK To BO
≥1 ARC1 CLOSE COMMAND
820000EBB4 ARC_BLOCK
ARC1 BLOCK COM
From TRC
GEN.ARC-BLOCK ARC1 RESET
≥1

Start
Multi-phase Trip in SPAR1
GEN.TRIP-A 3
&
GEN.TRIP-B &
GEN.TRIP-C
Condition as to CB#1
800000EBB0 EXT.ARC_START-A ARC1 IN-PROG OR To TRC
6 ARC1 FT
TRIP-MPH
800000EBB1 EXT.ARC_START-B
TRIP-1PH CB1_94TT
TRIP-1PH C
ARC1 SPAR_COND
800000EBB2 EXT.ARC_START-C B SPAR
ARC START ARC1-S1 IN-PROG ≥1

From PROT_COMM NO-OFF

CB1_ALLPH_CLOSE

≥1
CONSTANT_1
TRESET1
≥1 & t 0
810001EBC9 ARC1-S2 COND

Initiation for CB#1


Shot1 for CB#1
Issuing for CB
4 C ARC1 SPAR
9
ARC START 7 Success check
A & ARC1 CLOSE COMMAND
CB1_ALLPH_CLOSE ARC1_SPAR_COND ARC1 10
S ARC1-S1 IN-PROG SHOT1
800001EBB7 CB1-ARC READY CB1-ARC READY & ARC1 SHOT ARC1 SHOT
R ARC1 SPAR ARC1 SHOT1
ARC START
ARC1 IN-PROG SPAR1_COND ARC1 SHOT2
ARC1 RS SPAR1_START CB1_ALLPH_CLOSE
ARC1 NOT-IN-PROG ARC-S1 TRR
D SHOT_1ST ARC1 NOT IN PROG
Shot2–Shot5 for CB#1
≥1
S ARC1 SHOT2
ARC1 CLOSE FAIL
A & R ARC1-S2 IN-PROG
ARC1
ARC1-S2 COND SHOT2
ARC1 CLOSE SUCCESS
ARC1 SHOT2
8
ARC1-Mode input ARC1-S2 TRR
ARC-SucChk
1
ON
SPAR B
≥1 Shot counter
820001EBB2 ARC1_MODE-SPAR
ARC1-MODE=NO-OFF 5
ARC1 NOT_IN-PROG
Shot number
From PROT_COMM ARC1 SHOT1 SHOT_1ST D
2
ARC-NUM
CB-System ARC1 SHOT2 SHOT-2ND
CB-SYSTEM=1CB 1CB A
1CB S2

Figure 2.34-2 ARC SHOT1 and SHOT2’ in SPAR mode of 1CB system
6F2S1914 (0.37)

GRL200 (Soft 033 & 037)


- 429 -
6F2S1914 (0.37)

(ii) TPAR mode


Figure 2.34-3 illustrates the ARC function when settings of are performed in both Table 2.34-5
and Table 2.34-6.

Table 2.34-5 Block parts in TPAR mode


Block parts Corresponding logics Detailed logic
[1] ARC1-Mode input Figure 2.34-11
[2] Shot number Figure 2.34-13
[3] Start Figure 2.34-14
[4] Initiation Figure 2.34-15
[5] Shot counter Figure 2.34-16
[6] Condition Figure 2.34-17
[7] ARC1 TPAR Figure 2.34-19
[8] ARC1 SHOT2 Figure 2.34-21
[9] Issuing Figure 2.34-22
[10] Success check Figure 2.34-23
[11] Reclose sequence Figure 2.34-24

Table 2.34-6 Setting examples in TPAR mode


Categories Items Settings Corresponding logics
ARC1-EN On
ARC1-Mode TPAR Figure 2.34-11
ARC2-EN Off
ARC general ARC2-Mode Off Figure 2.34-12
ARC-ORDER CB1 Figure 2.34-24
Multi Shot-EN On
ARC-NUM S2 Figure 2.34-13
TREADY 60.0s Figure 2.34-15
TTPAR1 0.60s Figure 2.34-19
ARC1 TTPAR1_SUB 300.00s Figure 2.34-19
TRR1 2.00s Figure 2.34-19
TCCW1 0.20s Figure 2.34-22
TD_MS2 20.00s Figure 2.34-21
ARC1 multi-shot
TRR_MS2 30.00s Figure 2.34-21
ARC-SucChk On Figure 2.34-23
TARCSUC 0.30s Figure 2.34-23
FT-3pFault Off Figure 2.34-14
ARC misc.
TRESET 0.30s Figure 2.34-15
TEVLV 0.30s Figure 2.34-17
SHOTNUM-TEST Off Figure 2.34-16
PROT-COMMON CB-System 1CB See Protection common function
VCHK ARC1-VCHK EN On See Voltage check for autoreclose
TRC TP-MODE Per-Phase See Trip circuit

GRL200 (Soft 033 & 037)


- 430 -
800001EBCF ARC1_BLOCK To BO
≥1 ARC1 CLOSE COMMAND
820000EBB4 ARC_BLOCK
ARC1 BLOCK COM
From TRC
GEN.ARC-BLOCK ARC1 RESET
&
Start
GEN.TRIP-A
3
GEN.TRIP-B
GEN.TRIP-C
Condition as to CB#1
800000EBB0 EXT.ARC_START-A ARC1 IN-PROG OR To TRC
6
ARC1 FT
800000EBB1 EXT.ARC_START-B
TRIP-ANYPH TRIP-ANYPH CB1_94TT
ARC1 TPAR_COND C
800000EBB2 EXT.ARC_START-C B TPAR
ARC START ARC1-S1 IN-PROG ≥1

From PROT_COMM NO-OFF

CB1_ALLPH_CLOSE Failure to issue shot


From VCHK ≥1
ARC1-VCHK TRESET1
≥1 & t 0
810001EBC9 ARC1-S2 COND

Initiation for CB#1


Shot1 for CB#1
4 ARC1 TPAR Issuing for CB
ARC START C
7 9 Success check
CB1_ALLPH_CLOSE A & ARC1 CLOSE COMMAND
ARC1 10
800001EBB7 CB1-ARC READY CB1-ARC READY ARC1_TAR_COND
SHOT1
S ARC1-S1 IN-PROG
ARC1 SHOT ARC1 SHOT
& ARC1 TPAR ARC1 SHOT1
R
TPAR1_COND ARC START
ARC1 IN-PROG
TPAR1_START ARC1 SHOT2
ARC1 RS CB1_ALLPH_CLOSE
ARC1 NOT-IN-PROG ARC-S1 TRR
D SHOT_1ST
Shot2–Shot5 for CB#1
ARC1 CLOSE FAIL ≥1
ARC1 SHOT2
S ARC1 NOT IN PROG
A & R ARC1-S2 IN-PROG
ARC1
SHOT2
ARC1-S2 COND
ARC1 SHOT2
8
ARC1-S2 TRR
ARC1-Mode input ARC-SucChk

1
ON
TPAR B Shot Counter
≥1
820001EBB2 ARC1_MODE-TPAR
5 Reclose sequence
ARC1-MODE=NO-OFF ARC1 NOT_IN-PROG
11 TPAR1_START
Shot number ARC-ORDER
From PROT_COMM ARC1 SHOT1 SHOT_1ST D
2 CB1
ARC-NUM
CB-System ARC1 SHOT2 SHOT-2ND
CB-SYSTEM=1CB 1CB A
1CB S2

Figure 2.34-3 ARC SHOT1 and SHOT2 in TPAR mode of 1CB system
6F2S1914 (0.37)

GRL200 (Soft 033 & 037)


- 431 -
6F2S1914 (0.37)

(iii) SPAR and TPAR mode


Figure 2.34-4 illustrates the ARC function when settings of are performed in both Table 2.34-7
and Table 2.34-8.

Table 2.34-7 Block parts in SPAR and TPAR mode


Block parts Corresponding logics Detailed logic
[1] ARC1-Mode input Figure 2.34-11
[2] Shot number Figure 2.34-13
[3] Start Figure 2.34-14
[4] Initiation Figure 2.34-15
[5] Shot counter Figure 2.34-16
[6] Condition Figure 2.34-17
[7] ARC1 TPAR Figure 2.34-20
[8] ARC1 SHOT2 Figure 2.34-21
[9] Issuing Figure 2.34-22
[10] Success check Figure 2.34-23
[11] Reclose sequence Figure 2.34-24

Table 2.34-8 Setting examples in SPAR and TPAR mode


Categories Items Settings Corresponding logics
ARC1-EN On
ARC1-Mode SPAR&TPAR Figure 2.34-11
ARC2-EN Off
ARC general ARC2-Mode Off Figure 2.34-12
ARC-ORDER CB1 Figure 2.34-24
Multi Shot-EN On
ARC-NUM S2 Figure 2.34-13
TREADY 60.0s Figure 2.34-15
TSPAR1 0.80s Figure 2.34-18
TSPAR1_SUB 300.00s Figure 2.34-18
ARC1 TTPAR1 0.60s Figure 2.34-20
TTPAR1_SUB 300.00s Figure 2.34-20
TRR1 2.00s Figure 2.34-20
TCCW1 0.20s Figure 2.34-22
TD_MS2 20.00s Figure 2.34-21
ARC1 multi-shot
TRR_MS2 30.00s Figure 2.34-21
ARC-SucChk On Figure 2.34-23
TARCSUC 0.30s Figure 2.34-23
FT-3pFault Off Figure 2.34-14
ARC misc.
TRESET 0.30s Figure 2.34-15
TEVLV 0.30s Figure 2.34-17
SHOTNUM-TEST Off Figure 2.34-16
PROT-COMMON CB-System 1CB See Protection common function
VCHK ARC1-VCHK EN On See Voltage check for autoreclose
TRC TP-MODE Per-Phase See Trip circuit

GRL200 (Soft 033 & 037)


- 432 -
800001EBCF ARC1_BLOCK To BO
≥1 ARC1 CLOSE COMMAND
820000EBB4 ARC_BLOCK
ARC1 BLOCK COM
From TRC
GEN.ARC-BLOCK ARC1 RESET
&
Start
GEN.TRIP-A
3
GEN.TRIP-B
GEN.TRIP-C Condition as to CB#1

800000EBB0 EXT.ARC_START-A ARC1 IN-PROG OR To TRC


6
ARC1 FT
800000EBB1 EXT.ARC_START-B C
TRIP-MPH ARC1 SPAR_COND CB1_94TT
TRIP-MPH
800000EBB2 EXT.ARC_START-C B SPAR&TPAR
ARC1 TPAR_COND D
ARC START ARC1-S1 IN-PROG ≥1

From PROT_COMM NO-OFF

CB1_ALLPH_CLOSE Failure to issue shot


From VCHK ≥1
ARC1-VCHK TRESET1
≥1 & t 0
810001EBC9 ARC1-S2 COND

Shot1 for CB#1


Initiation for CB#1 Issuing for CB
C ARC1 SPAR&TPAR
4 7 9
D
ARC START A & ARC1_SPAR_COND ARC1 CLOSE COMMAND Success check
ARC1
ARC1_TPAR_COND 10
CB1_ALLPH_CLOSE SHOT1
S ARC1-S1 IN-PROG
ARC1 SHOT ARC1 SHOT
800001EBB7 CB1-ARC READY CB1-ARC READY & ARC1_SPAR ARC1 SHOT1
R ≥1
TPAR1_CONDARC1_TPAR ARC START
ARC1 IN-PROG
TPAR1_START ARC1 SHOT2
ARC1 RS CB1_ALLPH_CLOSE
ARC1 NOT-IN-PROG ARC-S1 TRR
E SHOT_1ST
Shot2–Shot5 for CB#1
ARC1 CLOSE FAIL ≥1
ARC1 SHOT2
S ARC1 NOT IN PROG
A & R ARC1-S2 IN-PROG
ARC1
SHOT2
ARC1-S2 COND
ARC1 SHOT2
8
ARC1-Mode input ARC1-S2 TRR
ARC-SucChk
1
SPAR&TPAR Shot Counter ON
B
≥1
800001EBB7 ARC1_MODE-S&T 5 Reclose sequence
ARC1-MODE=NO-OFF ARC1 NOT_IN-PROG
11
TPAR1_START
Shot number ARC-ORDER
From PROT_COMM ARC1 SHOT1 SHOT_1ST E
2 CB1
ARC-NUM
CB-System ARC1 SHOT2 SHOT-2ND
CB-SYSTEM=1CB 1CB A
1CB S2

Figure 2.34-4 ARC SHOT1 and SHOT2 in SPAR&TPAR mode of 1CB system
6F2S1914 (0.37)

GRL200 (Soft 033 & 037)


- 433 -
6F2S1914 (0.37)

(iv) MPAR mode


Figure 2.34-5 illustrates the ARC function when settings of are performed in both Table 2.34-9
and Table 2.34-10.

Table 2.34-9 Block parts in MPAR mode


Block parts Corresponding logics Detailed logic
[1] ARC1-Mode input Figure 2.34-11
[2] Shot number Figure 2.34-13
[3] Link judgment Figure 2.34-28
[4] Start Figure 2.34-14
[5] Initiation Figure 2.34-15
[6] Shot counter Figure 2.34-16
[7] ARC1 MPAR Figure 2.34-27
[8] ARC1 SHOT2 Figure 2.34-21
[9] Issuing Figure 2.34-22
[10] Success check Figure 2.34-23
[11] Reclose sequence Figure 2.34-24

Table 2.34-10 Setting examples in MPAR mode


Categories Items Settings Corresponding logics
ARC1-EN On
ARC1-MODE MPAR Figure 2.34-11
ARC2-EN Off
ARC2-MOED Off Figure 2.34-12
ARC general
MPAR-MODE M2 Table 2.34-13
ARC-ORDER CB1 Figure 2.34-24
MultiShot-EN On
ARC-NUM S2 Figure 2.34-13
TREADY 60.0s Figure 2.34-15
TSPAR1 0.80s Figure 2.34-18
TSPAR1_SUB 300.00s Figure 2.34-18
TTPAR1 0.60s Figure 2.34-20
ARC1 TTPAR1_SUB 300.00s Figure 2.34-20
TMPAR1 1.00s Figure 2.34-27
TMPAR1_SUB 300.00s Figure 2.34-27
TRR1 2.00s Figure 2.34-20
TCCW1 0.20s Figure 2.34-22
TD_MS2 20.00s Figure 2.34-21
ARC1 multi-shot
TRR_MS2 30.00s Figure 2.34-21
ARC-SucChk On Figure 2.34-23
TARCSUC 0.30s Figure 2.34-23
FT-3pFault Off Figure 2.34-14
ARC misc.
TRESET 0.30s Figure 2.34-15
TEVLV 0.30s Figure 2.34-17
SHOTNUM-TEST Off Figure 2.34-16
PROT-COMMON CB-System 1CB See Protection common function
VCHK ARC1-VCHK EN On See Voltage check for autoreclose
TRC TP-MODE Per-Phase See Trip circuit

GRL200 (Soft 033 & 037)


- 434 -
To BO
From COMM_APPL
INTCONN-A_LR1
INTCONN-A_R1 &
INTCONN-B_R1 INTCONN-B_LR1
&
INTCONN-C_R1 INTCONN-C_LR1
&
INTCONN-A_L Link judgment
&
INTCONN-B_L 3
&
INTCONN-C_L ARC-MANOLK=FT D
From BI &
ARC-MANOLK=TPAR E
800000EBB8 P.INTCONN-A_LR1

800000EBB9 P.INTCONN-B_LR1 B MPAR ARC-MANOLK=S&T F

800000EBBA P.INTCONN-C_LR1 MPAR_LINK G


MPAR-MODE M2
800001EBCF ARC1_BLOCK NO_MPAR_LINK H To BO
M3
≥1 ARC1 CLOSE COMMAND
820000EBB4 ARC_BLOCK ARC1 BLOCK COM

GEN.ARC-BLOCK ARC1 RESET


&
Start
From TRC
GEN.TRIP-A 4
GEN.TRIP-B TRIP-1PH I
GEN.TRIP-C
TRIP-ANYPH J
800000EBB0 EXT.ARC_START-A ARC1 IN-PROG OR To TRC
ARC1 FT
800000EBB1 EXT.ARC_START-B TRIP-MPH K
CB1_94TT
800000EBB2 EXT.ARC_START-C
ARC START
≥1

From PROT_COMM NO-OFF

CB1_ALLPH_CLOSE

≥1
TRESET1
≥1 & t 0
810001EBC9 ARC1-S2 COND

Initiation for CB#1 Shot1 for CB#1


D E F G H MPAR logic Issuing for CB
5 ARC-MANOLK=FT 9 Success check
I J K ARC-MANOLK=TPAR
ARC START ARC-MANOLK=S&T ARC1 CLOSE COMMAND 10
A MPAR_LINK
CB1_ALLPH_CLOSE &
NO_MPAR_LINK ARC1
S TRIP-MPH etc SHOT1
800001EBB7 CB1-ARC READY CB1-ARC READY ARC1 SHOT ARC1 SHOT
& ARC1 SHOT1
R ARC1-S1 IN-PROG
ARC START
ARC1 IN-PROG TPAR1_START
ARC1 SPAR ≥1 ARC1 SHOT2
ARC1 RS ARC1 TPAR CB1_ALLPH_CLOSE
ARC1 NOT-IN-PROG 7 ARC1 MPAR
SHOT_1ST ARC-S1 TRR
ARC1 CLOSE FAIL ≥1
Shot2–Shot5 for CB#1
S ARC1 NOT IN PROG
Shot2
A & R
ARC1-S2 IN-PROG
ARC1 ARC1 CLOSE SUCCESS
ARC1-S2 COND SHOT2
ARC1-Mode input ARC1 SHOT2
8 ARC-SucChk
ARC1-S2 TRR
1
ON
MPAR B
≥1 Shot Counter
820001EBB5 ARC1_MODE-MPAR Reclose sequence
ARC1-MODE=NO-OFF 6
ARC1 NOT_IN-PROG 11
Shot number TPAR1_START
From PROT_COMM ARC1 SHOT1 SHOT_1ST ARC-ORDER
2
CB-System ARC-NUM
ARC1 SHOT2 SHOT-2ND CB1
1CB A
1CB S2

Figure 2.34-5 ARC SHOT and SHOT2 in MPAR mode of parallel lines
6F2S1914 (0.37)

GRL200 (Soft 033 & 037)


- 435 -
6F2S1914 (0.37)

2.34.4 Timing diagram


(i) Single shot scheme for an Arcing fault (Shot1 for CB#1 and
successful operation in TPAR mode)
Figure 2.34-6 illustrates an example for which the single shot scheme has been selected (i.e.
[ARCNUM]=S1); an arcing fault is cleared following the operation of the protection relay and
the issue of the ‘GEN.TRIP-A/B/C’ signals for the tripping of the CB#1. The ‘GEN.TRIP-A/B/C’
also initiates the ARC function and an ‘ARC1 CLOSE COMMAND’ signal is issued following
the expiration of the dead time set for [TTPAR1]. When On is set for [ARC-SucChk], this
scheme will determine that the ARC1 was successful when the ‘CB1 ALLPH CLOSE’ signal is
detected following the issuing of the ‘ARC1 CLOSE COMMAND’ signal; the operation of the
ARC function is reset if it operates successfully (i.e., the ‘ARC1 IN-PROG’ signal is turned off).
Fault current

Closed
CB#1 status
Open

Operated
Relay operation
Issued
GEN.TRIP

ARC1 IN-PROG

ARC1-S1 IN-PROG

ARC1 SHOT1 Dead Time [TTPAR1]


)
ARC1-S2 IN-PROG

ARC1 SHOT2

ARC1-S3 IN-PROG

ARC1 SHOT3

ARC1 CLOSE COMMAND [TCCW1]


)
Closed
CB1_ ALLPH_CLOSE

ARC1 CLOSE SUCCESS


20ms
ARC1 CLOSE FAIL )

ARC1 FT

Figure 2.34-6 Single shot scheme [ARC-NUM]=S1 for an Arcing fault; operation is successful
Note: The permissive signal ‘ARC1-VCHK’ is required in the TPAR mode, but is omitted
here for the sake of clarity. The pulse width of the ‘ARC1 CLOSE COMMAND’
signal is defined using the setting [TCCW1].

(ii) Single shot scheme for an Arcing fault; CB#1 fails to reclose
Figure 2.34-7 also shows the single shot scheme. However, the CB#1 fails to reclose on
receiving the ‘ARC1 CLOSE COMMAND’ so that the ARC function initiates the ‘ARC1 CLOSE
FAIL’ signal within the setting time [TARCDSUC]. Consequently, the ARC function goes to the
final trip (ARC1 FT) stage so that the ARC will not issue another ‘ARC1 CLOSE COMMAND’
signal hereafter.

GRL200 (Soft 033 & 037)


- 436 -
6F2S1914 (0.37)

Fault current

Closed
CB#1 Status CB fails to be closed.
Open

Operated
Relay operation
Issued
GEN.TRIP

ARC1 IN-PROG

ARC1-S1 IN-PROG

ARC1 SHOT1 Dead time [TTPAR1]

ARC1-S2 IN-PROG

ARC1 SHOT2

ARC1-S3 IN-PROG

ARC1 SHOT3

ARC1 CLOSE COMMAND [TCCW1]


)
CB1 ALLPH Closed
CLOSE Open

ARC1 CLOSE SUCCESS

ARC1 CLOSE FAIL [TARCSUC]


)
ARC1 FT

Figure 2.34-7 Single shot scheme [ARC-NUM]=S1 for an Arcing fault; CB#1 fails to reclose
Note: The permissive signal ‘ARC1-VCHK’ is required in the TPAR mode for the ARC1
SHOT1 operation, but is omitted here for the sake of clarity.

(iii) Single shot scheme for Permanent fault


Figure 2.34-8 illustrates the behavior of the single shot scheme for a permanent fault. Tripping
of the CB#1 is executed correctly, but a further trip occurs following the reclosure of the CB#1.
Accordingly, the ARC function determines that the ARC1 operation cannot restore power
transmission in the single shot scheme; subsequently the ARC function goes to the final trip
(ARC1 FT) stage.
Fault current

Closed
CB#1 Status
Open

Operated
Relay operation
Issued
GEN.TRIP

ARC1 IN-PROG

ARC1-S1 IN-PROG

ARC1 SHOT1 Dead time [TTPAR1]

ARC1-S2 IN-PROG

ARC1 SHOT2

ARC1-S3 IN-PROG

ARC1 SHOT3

ARC1 CLOSE [TCCW1]


COMMAND )
CB1 ALLPH Closed
CLOSE Open

ARC1 CLOSE SUCCESS

ARC1 CLOSE FAIL

ARC1 FT

Figure 2.34-8 Single shot ARC scheme [ARC-NUM]=S1 for Permanent fault
Note: The permissive signal ‘ARC1-VCHK’ is required for the ARC SHOT1 operation, but
is omitted here for the sake of clarity.

- 437 - GRL200 (Soft 033 & 037)


6F2S1914 (0.37)

(iv) Single shot scheme for an Arcing fault; fault removed by a backup
CB
Figure 2.34-9 shows the single shot scheme for an Arcing fault, but tripping is not executed
due to the failure of the CB#1. Therefore, the operation of the ARC function is reset in the
setting time [TRESET] before the duration of dead timer [TTPAR1] expires. Consequently, the
ARC function determines that the local CB#1 cannot be tripped to clear the fault.
Fault current
Fault cleared by tripping the backup CB at the remote end†
Closed
CB#1 Status CB at the local end fails to open
Open

Operated
Relay operation
Issued
GEN.TRIP

ARC1 IN-PROG

ARC1-S1 IN-PROG

ARC1 SHOT1 Dead time [TTPAR1]

ARC1-S2 IN-PROG

ARC1 SHOT2

ARC1-S3 IN-PROG

ARC1 SHOT3

ARC1 CLOSE
COMMAND

CB1 ALLPH Closed


CLOSE Open

ARC1 CLOSE SUCCESS

ARC1 CLOSE FAIL

ARC1 FT
Reset
ARC RESET [TRESET]
)

Figure 2.34-9 Single shot scheme [ARC-NUM]=S1 for an Arcing fault; remote CB† tripped
†Note:the fault is removed by the tripping of the CB at the remote end; hence, the fault
current will no longer flow.

(v) Multi shot scheme for Permanent fault


Figure 2.34-10 illustrates the multi-shot scheme (S3); triple reclosing of the CB#1 by the ARC
function is required and executed correctly. However, the ARC function determines that the
fault is permanent as the fault persists after the third tripping (i.e. the shot counter logic
reaches its maximum value and the fault persists). Consequently, the ARC function moves to
the final trip (ARC1 FT) stage so that the ARC will not issue an ‘ARC1 CLOSE COMMAND’
signal hereafter.

- 438 - GRL200 (Soft 033 & 037)


6F2S1914 (0.37)

Fault current

Closed
CB#1 Status
Open

Operated
Relay operation
Issued
GEN.TRIP

ARC1 IN-PROG

ARC1-S1 IN-PROG

ARC1 SHOT1 Dead time [TTPAR1]

ARC1-S2 IN-PROG

ARC1 SHOT2 Dead time [TD_MS2]

ARC1-S3 IN-PROG

ARC1 SHOT3 Dead time [TD_MS3]

ARC1 CLOSE [TCCW1] [TCCW1] [TCCW1]


COMMAND ) ) )

Closed
CB1 ALLPH
Open
CLOSE

ARC1 CLOSE SUCCESS

ARC1 CLOSE FAIL


Lock out
ARC1 FT

Figure 2.34-10 Multi shot scheme [ARC-NUM]=S3 for a Permanent fault


Note:
1. The permissive signal ‘ARC1-VCHK’ is required for ARC SHOT1 operation, but has
been omitted for clarity in this figure.
2. ‘ARC1-VCHK’ permissive signal is introduced automatically in the TPAR mode. For
ARC-SHOT2 and onwards, the user must introduce the permissive signal from the
VCHK function by using PLC programming.

2.34.5 Autoreclosing logics


(i) Setting logic for ARC1 mode – setting (ARC1-MODE)
The ARC1-MODE input setting is illustrated in Figure 2.34-11. The scheme switch [ARC1-
MODE] has seven setting modes as OFF, FT, SPAR, TPAR, SPAR&TPAR, MPAR, and Original.

- 439 - GRL200 (Soft 033 & 037)


6F2S1914 (0.37)

&
≥1

&
≥1
Condition
&
ARC1-MODE=SPAR
≥1

&
OFF ARC1-MODE=TPAR
≥1
FT
SPAR &
TPAR ≥1 ARC1-MODE=S&T
SPAR&TPAR &
ARC1-MODE MPAR ≥1
≥1 ARC1-MODE=SPAR+S&T
ORIGINAL
& ARC1-MODE=MPAR
≥1

Start
ARC1-MODE=NO-OFF
≥1
800001EBB0 ARC1_MODE-OFF &

810001EBB1 ARC1_MODE-FT &

≥1 Initiation
820001EBB2 ARC1_MODE-SPAR
& ARC1-MODE=ON

830001EBB3 ARC1_MODE-TPAR &

ARC1-MODE=OFF
800001EBB7 ARC1_MODE-S&T &
Original

850001EBB5
800001EBB7 ARC1-MODE-MPAR & ARC1-MODE=ORG

860001EBB6
800001EBB7 ARC1_MODE-ORG &
8800011B62 To TRC
≥1
Signal ‘1’ is generated when there is no contradiction between the CB1_BRIDGE
various signals, that is only one signal is picking up.

800001EBB8 CB1 F.BRIDGE


READY

Figure 2.34-11 ARC1-MODE input logic


When FT is selected, the ARC function send ‘CB1_BRIDGE’ signal for the TRC function
to be the CB being tripped in three-phases, regardless of the condition of the tripped phase,
the operation of respective protection elements, and the ARC settings; the ARC function does
not operate (i.e., ARC1-FT).

When TPAR is selected, the TRC and the ARC functions operate by the rule that the CB
is tripped in three-phases and can be reclosed. That is, ‘CB1_BRIDGE’ signal is sent for the
TRC function so that the CB will be tripped in three-phases forcibly even if a GEN.TRIP-A
(TRIP COMMAND-A) signal is only generated in the TRC function (as well as GEN.TRIP-B
and GEN.TRIP-C). Note the CB will be tripped in three-phases forcibly, even if a single-phase
fault is detected and instructed a single-phase tripping by the relay applications.

GRL200 (Soft 033 & 037)


- 440 -
6F2S1914 (0.37)

(ii) Setting logic for ARC2 mode – setting (ARC2-MODE)


The ARC2-MODE input setting is illustrated in Figure 2.34-12. The scheme switch [ARC2-
MODE] is provided similar to the [ARC1-MODE].

&
≥1 &
&
≥1 &
&
≥1 & ARC2-MODE=SPAR

& Condition
OFF
≥1 & ARC2-MODE=TPAR
FT
SPAR &
TPAR ≥1 & ARC2-MODE=S&T
SPAR&TPAR &
ARC2-MODE MPAR ≥1 & ≥1 ARC2-MODE=SPAR+S&T
ORIGINAL
&
ARC2-MODE=MPAR
≥1 &

Start
ARC2-MODE=NO-OFF
800002EBB0 ARC2_MODE-OFF ≥1
&

810002EBB1 ARC2_MODE-FT &

820002EBB2 ARC2_MODE-SPAR ≥1 Initiation


&
ARC2-MODE=ON

830002EBB3 ARC2_MODE-TPAR &

≥1 ARC2-MODE=OFF
800002EBB7 ARC2_MODE-S&T &

Original
850002EBB5
800001EBB7 ARC2-MODE-MPAR & ARC2-MODE=ORG

860002EBB6
800001EBB7 ARC2_MODE-ORG &

Signal ‘1’ is generated when there is no contradiction between


the various signals, that is only one signal is picking up.
From PROT-COMMON
CB-SYSTEM=2CB

CB-SYSTEM=1CB
8800021B62 To TRC
≥1 CB2_BRIDGE
810002EBB9 CB2 F.BRIDGE
READY

Figure 2.34-12 ARC2-MODE input logic

GRL200 (Soft 033 & 037)


- 441 -
6F2S1914 (0.37)

(iii) Setting logic for shot number – setting (ARC-NUM)


The [ARC-NUM] switch is provided to set a number of reclosing CB#1.
To Initiation for CB#1
&
ARC-NUM=S1
≥1

& ARC-NUM=S2

S1
& ARC-NUM=S3
S2
S3
S4 & ARC-NUM=S4
ARC-NUM
S5
& ARC-NUM=S5

From PROT-COMMON
CB-SYSTEM=1 CB

CB-SYSTEM=2 CB

Figure 2.34-13 Shot number

GRL200 (Soft 033 & 037)


- 442 -
6F2S1914 (0.37)

(iv) Start logic – setting (FT-3P FAULT)


Start logic generates ‘ARC START’ signal when the TRC function has any ‘GEN.TRIP-A’, ‘-B’,
‘-C’ signals coming from relay functions. The type of tripping (i.e., single-phase-tripping, two-
or-three-phase-tripping, or three-phase tripping) is also checked in Start logic. Use PLC
connection points ‘EXT.ARC_START-A’ and others if an external relay is available to start the
ARC function.
To TRC

800001EBCE F.CB1_94TT CB1_94TT

810002EBCB F.CB2_94TT CB2_94TT


FT-3PFAULT
On

1
800000EBB5 RYOP-A 8500001B6C

810000EBB6 RYOP-B 1 ARC1 FT CB1_94TT


&
&
820000EBB7 RYOP-C 1
0.02s

≥1 ARC2 FT CB2_94TT
&
0 t
800001EBCF ARC1_BLOCK ≥1 ARC1 FT CB1_94TT
&
0.1s
810002EBB7 ARC2_BLOCK
0 t ARC2 FT CB2_94TT
≥1
820000EBB4 ARC_BLOCK
&
0.1s 8300001B64
From TRC
GEN.ARC-BLOCK & EXT.ARC_START
≥1

8400001B65 Initiation
GEN.TRIP-A
≥1 & 1 ARC START
≥1

GEN.TRIP-B
≥1 & 1

GEN.TRIP-C
≥1 & 1

0.01s
800000EBB0 EXT.ARC_START-A Condition
8000001B66
810000EBB1 EXT.ARC_START-B S
TRIP-ANYPH
≥1
820000EBB2 EXT.ARC_START-C R
To Multiphase
S 8100001B67 trip in SPAR
R & TRIP-1PH
ARC1-MODE input 1 ≥1
S
ARC1-MODE=NO-OFF 1
≥1
R
ARC2-MODE input
ARC2-MODE=NO-OFF &
&
1
800000EBB3 ARC NO ACT 1
1

&
1

To Evolving fault
8200001B68 logic
&
≥1 TRIP-MPH

&

Initiation
&
ARC1 IN-PROG OR

8300001B69

& TRIP-3PH
ARC1-S1 IN-PROG MPAR judgment
≥1
Reclose sequence
ARC2-S1 IN-PROG 1 NON ARC-S1_ IN-PROG

Figure 2.34-14 Start logic

If the scheme switch [FT-3P FAULT] is set to On, ‘CB1_94TT’ and ‘CB2_94TT’ signals are
generated and introduce the three-phase tripping (final trip) for the TRC function during the

GRL200 (Soft 033 & 037)


- 443 -
6F2S1914 (0.37)

ARC1 and ARC2 functions being generating ‘ARC1 IN-PROG OR’ or ‘ARC2-S1 IN-PROG’
signals. The switch [FT-3P FAULT] requires signals of the external relay; PLC connection
points ‘RYOP-A, RYOP-B, and RYOP-C’ are used to get the signals.

Note that the ‘CB1_94TT’ and ‘CB2_94TT’ signals are generated when ‘ARC BLOCK’
signals are injected, provided ‘ARC1 IN-PROG OR’ or ‘ARC2-S1 IN-PROG’ signals is being
generated.

If, with regard to the tripped poles of CBs, there is not consistency between the CB#1 and
the CB#2, the ARC function can generate the ‘CB1_94TT’ and ‘CB2_94TT’ signals when an
external device is able to detect the consistency; use PLC connection points ‘F.CB1_94TT’ and
‘F.CB2_94TT’ for the operation of the inconsistency.

The Start logic can receive a stop signal not to operate the ARC function; use PLC
connection point ‘ARC NO ACT’.

GRL200 (Soft 033 & 037)


- 444 -
6F2S1914 (0.37)

(v) Initiation logic – setting (TREADY1, TRESET)


Figure 2.34-15 illustrates the initiation logic for CB#1, which has ‘ARC1 READY’ signal issued
by the reception of signals ‘ARC1-MODE=ON’ and ‘CB1_ALLPH_CLOSE’. Note that the user
should connect a ready signal of the CB with PLC connection point ‘CB1-ARC READY’ using
the BI circuit. Reclaim timer [TREADY1] is provided; the flip-flop is set to issue ‘ARC1 IN-
PROG’ signal when signals ‘ARC_READY’, ‘SHOT_1ST’ and ‘ARC1 START’ are provided.
‘ARC1-S1 IN-PROG’ signal succeeds followed by the ‘ARC1 IN-PROG’ signal.
8800011B62 To TRC
CB1_BRIDGE

800001EBB7 CB1-ARC READY TREADY1 8000011B60


8000011B6D CB1_94TT
From PROT-COMMON & t 0 ARC1 READY
FT ARC1 UNREADY ARC1 FT
CB1_ALLPH_CLOSE 1 & ARC1 UNREADY To ARC1 Shot
&
0.0-600.0s To Start / Condition
ARC1-MODE input logic
ARC1-MODE=ON ARC1-S1 IN-PROG
ARC1 IN-PROG OR
& S
Start logic 8200011B61
S ARC1-S1 IN-PROG
ARC_START ARC1 IN-PROG R
& R
Shot counter logic S ARC1-S2 IN-PROG
SN TEST ≥1 1 ARC1 NOT_IN-PROG
R
SHOT_1ST
S ARC1-S3 IN-PROG
Initiation for CB#1
SHOT_2ND & R

SHOT_3RD & S ARC1-S4 IN-PROG


R
SHOT_4TH &

S ARC1-S5 IN-PROG
SHOT_5TH &
R
Shot1–Shot5 logics for CB#1
Done issuing
ARC1 SHOT1 TRESET
&
≥1 t 0
A
ARC1 SHOT2 & &
0.0-300.0s
ARC1 SHOT3 &

ARC1 SHOT4 &

ARC1 SHOT5 &

8800021B62 To TRC
CB2_BRIDGE
8000021B69
& FT ARC2 UNREADY ARC2 FT CB2_94TT

From PROT-COMMON
TREADY2
CB2_ALLPH_CLOSE 8000021B60
& t 0
ARC2 READY
810002EBB8 CB2-ARC READY
1 To CB#2 bridge, Final trip logic
0.0-600.0s &
ARC2-MODE input logic
ARC2 UNREADY
ARC2-MODE=ON
To Start
& ARC2-S1 IN-PROG
8200021B61
S
To Shot logic for CB#2
& R
S ARC2-S1 IN-PROG
800000EBB3 ARC NO ACT
1 ≥1
R
Success check
≥1 8700011B70 Initiation for CB#2
ARC1 RS

ARC2 RS TRESET
8700021B6C t 0
A ARC1 RESET ≥1 B
&
B ARC2 RESET
0.0-300.0s

ARC2 SHOT

Figure 2.34-15 Initiation and its outside logics

If the ‘ARC1 UNREADY’ signal is present, Initiation logic abandons to reclose the CB#1;
then, the status of the ARC function reaches the Final Trip stage (FT); three-phase trip signal
(CB1_94TT) is generated transferred for the TRC function.

GRL200 (Soft 033 & 037)


- 445 -
6F2S1914 (0.37)

The ‘CB1-BRIDGE’ signal is used to combine any ‘per-phase trip signal’ into the three-
phase trip signal in the TRC function. Thus, the CB will be tripped in three-phases forcibly
even if a GEN.TRIP-A (TRIP COMMAND-A) signal is only generated in the TRC function
during the ‘ARC1 UNREADY’ being decided (as well as GEN.TRIP-B or GEN.TRIP-C).

GRL200 (Soft 033 & 037)


- 446 -
6F2S1914 (0.37)

(vi) Shot counter- setting (SHOTNUM-TEST)


Figure 2.34-16 illustrates the shot counter logic. Scheme switch [SHOTNUM-TEST] is provided
for the shot number test. For example, if two shots are required for the test, set S2 for the
[SHOTNUM-TEST]. Table 2.34-11 shows the counting up in the shot counter logic. Note that
the ARC function reaches the final trip stage if the counter is over.
Start
ARC START

Shot1 for CB#1 MULTI SHOT


ARC COUNTER
≥1
ARC1 SHOT1

Shot for CB#2 INIT STEP0


S
ARC2 SHOT & ≥1
R
& SHOT
Initiation for CB#1 STEP1 8400001B6B NUMBER OVER
& ≥1
ARC1 IN-PROG ≥1 & &
To TRC
ARC1 NOT_IN-PROG
& STEP2 & ≥1
&
& ARC1 FT CB1_94TT
Initiation for CB#2
ARC2 IN-PROG STEP3 &
≥1
&
ARC2 NOT_IN-PROG
STEP4 &
Shot2–Shot5 for CB#1 ≥1 &
ARC1 SHOT2 ARC2 FT CB2_94TT
STEP5 8500001B72 &
& ≥1
ARC1 SHOT3 ≥1 CLOCK &
ARC1 SHOT4
ARC1 SHOT5

Shot number
8000001B81 To Fault record
ARC-NUM=S1

ARC-NUM=S2 ≥1 ARC IN-PROG


ARC-NUM=S3

ARC-NUM=S4 Initiation for CB#1

ARC-NUM=S5 Initiation for CB#2


8000001B6D
SHOT_1ST
8100001B6E
SHOT_2ND
8200001B6F
1 SHOT_3RD
8300001B70
SHOT_4TH
8400001B71
SHOT_5TH
≥1
SN TEST

OFF
S1
S2
S3
S4
SHOTNUM-TEST S5
S6

Figure 2.34-16 Shot counter

Table 2.34-11 Counting up in Shot counter logic


Output signals for SHOT1–5 logics
Input signals for SHOT
Shot counter logic SHOT_1ST SHOT_2ND SHOT_3RD SHOT_4TH SHOT_5TH NUMBER
OVER
INIT CLOCK STEP0 STEP1 STEP2 STEP3 STEP4 STEP5
0 (Undefined) X
Not turning X
First cycle X
1 Second cycle X
Third cycle X
Fourth cycle X

GRL200 (Soft 033 & 037)


- 447 -
6F2S1914 (0.37)

(vii) Condition logic – setting (TEVLV)


The Condition logic determines the reclosing mode of either SPAR or TPAR by detecting the
tipped-phases if SPAR, TPAR, or SPAR&TPAR mode is selected.
Initiation
ARC1-S1 IN-PROG
ARC2-S1 IN-PROG SPAR
&
ARC1 IN-PROG OR & ARC1_SPAR_COND
ARC2_SPAR_COND
Start TRIP-1PH

& TPAR
&
≥1 ARC1_TPAR_COND
TRIP-ANYPH ARC2_TPAR_COND

&
&

TRIP-MPH

&
&

&
&
≥1
To TRC

CB1_94TT
&
& CB2_94TT
ARC1-MODE input

OFF
MPH-TRIP
FT &
ARC1-MODE=SPAR IN SPAR1 ARC1 FT CB1_94TT
MPAR
ORIGINAL ARC1-MODE=TPAR
SPAR
ARC1-MODE=S&T
ARC1-MODE TPAR
SPAR&TPAR ≥1 ARC1-MODE=SPAR+S&T

ARC2-MODE input
OFF
MPH-TRIP
FT &
ARC2-MODE=SPAR IN SPAR2 ARC2 FT CB2_94TT
MPAR
ORIGINAL ARC2-MODE=TPAR
SPAR ARC2-MODE=S&T
ARC2-MODE TPAR
SPAR&TPAR ARC2-MODE=SPAR+S&T
≥1

&
EVOLV_FAULT
8200001B6A & TIME OVER1 ARC1 FT CB1_94TT
&
TEVLV
t 0 & EVOLV_FAULT
TIME OVER2 ARC2 FT CB2_94TT
&
0.01-300.00s

Figure 2.34-17 Condition logic

When a multiphase fault (TRIP-MPH) occurs in the settings [ARC1-MODE]=SPAR, then


CB1_94TT signal is generated so that the function will reach the final trip stage. When a single
phase fault (TRIP-1PH) evolves to a multiphase fault (TRIP-MPH), then the final trip stage is
also induced; a timer [TEVLV] is provided for this purpose. Note that the timer [TEVLV] should
be lower than the dead timers [TSPAR1].

Note that the ‘CB1_94TT’ and ‘CB2_94TT’ signals are unconditionally generated when a
single phase tripping occurs in TPAR.

GRL200 (Soft 033 & 037)


- 448 -
6F2S1914 (0.37)

(viii) SPAR logic – settings (TSPAR1, TRR1)


The SPAR logic for CB#1 and CB#2 is illustrated in Figure 2.34-18. The ‘ARC1_SPAR’ signal
is generated when the SPAR condition is appeared in the Condition logic; the SPAR logic has
the dead timer [TSPAR1] provided to delay issuing a reclose command, which turns into ‘ARC1
SHOT1’ signal later. The user should set the [TRR1] to have the coordination with the
[TSPAR1]; the final trip will occur when ‘ARC1-S1 TRR’ signal is present. The SPAR logic for
CB#2 is similar to the one for CB#1.
Always ‘1’
Issuing for CB#1/CB#2
TSPAR1
Initiation 8000011B63
t 0
& ARC1_SPAR
ARC1 IN-PROG ARC1-S1 IN-PROG
&
800001EBB9 SPAR1_START 0.01 – 300.00 s
& ≥1

Condition of CB#1
800001EBBA SPAR1_COND
ARC1_SPAR_COND
TSPAR1_SUB
t 0
&
800001EBBB SPAR1_SUB_START
0.01 – 300.00 s &

800001EBBC SPAR1_SUB_COND
Always ‘1’

TSPAR2
ARC2-S1 IN-PROG t 0 8000021B63
& ARC2_SPAR
&
800002EBB9 SPAR2_START 0.01 – 300.00 s
& ≥1

Condition of CB#2
800002EBBA SPAR2_COND
ARC2_SPAR_COND
TSPAR2_SUB
t 0
&
800002EBBB SPAR2_SUB_START
0.01 – 300.00 s &

800002EBBC SPAR2_SUB_COND

TRR1
To TRC
t 0
ARC1-S1 TRR ARC1-FT CB1_94TT

0.01 – 310.00 s
TRR2
t 0
ARC2 TRR ARC2-FT CB2_94TT

0.01 – 310.00 s

Figure 2.34-18 ARC1 SPAR and ARC2 SPAR


Note: Settings [TSPAR1_SUB] and [TSPAR2_SUB] are not required as in the default.

GRL200 (Soft 033 & 037)


- 449 -
6F2S1914 (0.37)

(ix) TPAR logic – settings (TTPAR1, TRR1)


The TPAR logic for CB#1 and CB#2 are illustrated in Figure 2.34-19. To operate in the TPAR
mode in the CB#1, the VCHK function provides a permission signal for the TPAR logic. The
dead timer [TTPAR1] is required to set in the logic. The user should set the [TRR1] to have the
coordination with the [TTPAR1].

From VCHK function

ARC1-VCHK

ARC2-VCHK
For Issuing for CB
From Initiation TTPAR1
8000011B63
t 0
& ARC1_TPAR
ARC1 IN-PROG ARC1-S1 IN-PROG
&
810001EBBD TPAR1_START 0.01 – 300.00 s
& ≥1
From Condition in CB#1
ARC1_TPAR_COND
810001EBBE TPAR1_COND
TTPAR1_SUB
t 0
&
&
810001EBBF TPAR1_SUB_START
0.01 – 300.00 s
810001EBC0 TPAR1_SUB_COND

From Initiation For Issuing for CB


TTPAR2
8100021B64
ARC2-S1 IN-PROG t 0
& ARC2_TPAR
&
810002EBBE TPAR2_START 0.01 – 300.00 s
& ≥1
From Condition in CB#2
ARC2_TPAR_COND
810002EBBF TPAR2_COND
TTPAR2_SUB
t 0
&
&
810002EBC0 TPAR2_SUB_START
0.01 – 300.00 s
From Reclose sequence
810002EBC1 TPAR2_SUB_COND
TPAR1_START

TPAR2_START

TRR1 To TRC
t 0 ARC1-S1 TRR CB1_94TT
ARC1-FT

0.01 – 310.00 s
TRR2
t 0 ARC2 TRR ARC2-FT CB2_94TT

0.01 – 310.00 s

Figure 2.34-19 ARC1 TPAR and ARC2 TPAR


Note: Settings [TTPAR1_SUB], [TTPAR2_SUB] are not required as in the default.

GRL200 (Soft 033 & 037)


- 450 -
6F2S1914 (0.37)

(x) SPAR+TPAR logic – settings (TSPAR1,TTPAR1,and TRR1)


The SPAR&TPAR logic for CB#1 and CB#2 is illustrated in Figure 2.34-18. As for the CB#1,
the dead timers [TSPAR1] and [TTPAR1] should be set in the coordination with the [TRR1].
Always ‘1’
From VCHK function

ARC1-VCHK
ARC2-VCHK Issuing for CB#1
TSPAR1
Condition in CB#1 t 0 8000011B63
ARC1_SPAR_COND & ARC1_SPAR
&
ARC1_TPAR_COND 800001EBB9 SPAR1_START 0.01 – 300.00 s
& ≥1
From Initiation
ARC1 IN-PROG
800001EBBA SPAR1_COND
ARC1-S1 IN-PROG
TSPAR1_SUB
t 0
&
800001EBBB SPAR1_SUB_START 0.01 – 300.00 s &

800001EBBC SPAR1_SUB_COND

TTPAR1
8000011B63
t 0
& & ARC1_TPAR
810001EBBD TPAR1_START 0.01 – 300.00 s
& ≥1

810001EBBE TPAR1_COND
TTPAR1_SUB
t 0
&
&
810001EBBF TPAR1_SUB_START
Condition in CB#2 0.01 – 300.00 s
ARC2_SPAR_COND
810001EBC0 TPAR1_SUB_COND
ARC2_TPAR_COND Issuing for CB#2
TSPAR2
t 0 8000021B63
& ARC2_SPAR
From Initiation &
800001EBB9 SPAR2_START 0.01 – 300.00 s
ARC2-S1 IN-PROG & ≥1

800001EBBA SPAR2_COND
TSPAR2_SUB
t 0
&
800001EBBB SPAR2_SUB_START
0.01 – 300.00 s &

800001EBBC SPAR2_SUB_COND

TTPAR2
8000021B64
t 0
& & ARC2_TPAR
S1 IN-PROG 810002EBBE TPAR2_START 0.01 – 300.00 s
& ≥1

810002EBBF TPAR2_COND
TTPAR2_SUB
t 0
&
From Reclose sequence &
TPAR1_START 810002EBC0 TPAR2_SUB_START
0.01 – 300.00 s

TPAR2_START 810002EBC1 TPAR2_SUB_COND


TRR1 To TRC
t 0 ARC1 TRR ARC1-FT CB1_94TT
TRR2
0.01 – 310.00 s t 0
ARC2 TRR ARC2-FT CB2_94TT

0.01 – 310.00 s

Figure 2.34-20 ARC1 SPAR&TPAR and ARC2 SPAR


Note: Settings [TSPAR1_SUB], [TSPAR2_SUB], [TTPAR1_SUB], [TTPAR2_SUB] are not
required as in the default.

GRL200 (Soft 033 & 037)


- 451 -
6F2S1914 (0.37)

(xi) Shot2 to Shot5 for CB#1 –settings (TD_MS2, TRR2 and others)
The ARC1 logic for shot 2-shot5 is illustrated in Figure 2.34-21. Shots 2-5 are applicable for a
CB#1 only. For example, two shots (Shot2 and Shot3, i.e., [ARC_NUM]=S3) are required
following the Shot1, the user should set the [TS_MS2]/[TS_MS3] and [TRR2]/[TRR3]. The user
should program to inject a permission signal for the Shot2 and Shot3 at PLC connection points
‘ARC1-S2 COND’ and ‘ARC1-S3 COND’, as shown in Figure 2.34-21. Note that the CB will be
tripped in three-phases forcibly even if a GEN.TRIP-A (TRIP COMMAND-A) signal is only
generated, because the ‘CB1_BRIDGE’ signal is generated during the Shot 2-Shot5.
Initiation
TD_MS2
ARC1 IN-PROG ARC1-S2 Issuing
S t 0 8100011B67
& IN-PROG
& ARC1 SHOT2
R
0.01 – 300.00 s
TD_MS3 A
ARC1-S3
& S
IN-PROG t 0 8200011B68
R
& ARC1 SHOT3
0.01 – 300.00 s
& S B
ARC1-S4 TD_MS4
R IN-PROG t 0 8300011B69
Shot counter & ARC1 SHOT4
& S 0.01 – 300.00 s
SHOT_2ND
R C
SHOT_3RD ARC1-S5 TD_MS5
SHOT_4TH IN-PROG t 0 8400011B6A
SHOT_5TH & ARC1 SHOT5
0.01 – 300.00 s
≥1 D
Shot number
TRR2
ARC-NUM To TRC
t 0
ARC1-S2 TRR ARC1 FT CB1_94TT
A Done issuing ARC1 SHOT2
0.01 – 310.00 s
B Done issuing ARC1 SHOT3
TRR3
C Done issuing ARC1 SHOT4
t 0 ARC1 FT CB1_94TT
ARC1-S3 TRR
D Done issuing ARC1 SHOT5
8100011B67 0.01 – 310.00 s
810001EBC9 ARC1-S2 COND
TRR 4
8100011B68
t 0 ARC1-S4 TRR ARC1 FT CB1_94TT
810001EBCA ARC1-S3 COND
8100011B69
810001EBCB ARC1-S4 COND 0.01 – 310.00 s
8100011B6A TRR 5
810001EBCC ARC1-S5 COND t 0 ARC1-S5 TRR ARC1 FT CB1_94TT

0.01 – 310.00 s
8800011B62
CB1_BRIDGE
Shot2–Shot5 for CB#1

Figure 2.34-21 ARC1 logic for Shot2 to Shot5

GRL200 (Soft 033 & 037)


- 452 -
6F2S1914 (0.37)

(xii) Issuing close command – setting (TCCW1)


The logic for issuing close command for ARC1 and ARC2 is illustrated in Figure 2.34-22.
Shot1–Shot5 for CB#1 Success check for CB#1
ARC1 SHOT1
ARC1 SHOT
ARC1 SHOT2 TCCW1
8000011B6C To BO
ARC1 SHOT3 ≥1
ARC1 CLOSE COMMAND
ARC1 SHOT4
0.01-10.00s
ARC1 SHOT5

800001EBCD CB1_MANUAL_CLOSE

Shot for CB#2 Success check for CB#2


ARC2 SHOT
ARC2 SHOT
TCCW2
8100021B68 To BO
≥1
ARC2 CLOSE COMMAND

0.01-10.00s

810002EBCA CB2_MANUAL_CLOSE

Figure 2.34-22 Issuing for CB#1 and CB#2

GRL200 (Soft 033 & 037)


- 453 -
6F2S1914 (0.37)

(xiii) Success check logic – settings (TARCSUC, ARC-SucChk)


Figure 2.34-23 illustrates the success check logic for CB1 and CB2.
Issuing for CB#1 TARCSUC
ARC1 SHOT S t 0
&
R ARC-SUCCHK=ON
Initiation for CB#1 ≥1 0.10-100.00s
ARC1 NOT_IN-PROG 8C00011B71 To TRC
&
Start ARC1 CLOSE FAIL ARC1 FT CB1_94TT
ARC_START 8000011B72
Initiation for CB#1
& ARC1 CLOSE SUCCESS ARC1 RS

0.1s

Issuing for CB#2 TARCSUC


ARC2 SHOT S t 0
&
R
Initiation for CB#2 ≥1 0.10-100.00s
8C00021B6D To TRC
ARC2 NOT_IN-PROG &
ARC2 CLOSE FAIL ARC2 FT CB2_94TT
Start
ARC_START 8000021B6E Initiation for CB#2
& ARC2 CLOSE SUCCESS ARC2 RS

From PROT_COMMON 0.1s

CB1_ALLPH_CLOSE
ARC-SUCCHK=OFF
CB2_ALLPH_CLOSE Initiation
ARC1 SHOT RS ARC1 RS

Off ARC2 SHOT RS ARC2 RS


ARC-SucChk
On

Figure 2.34-23 Success check logic

GRL200 (Soft 033 & 037)


- 454 -
6F2S1914 (0.37)

(xiv) Reclosing sequence for two CBs system– setting (ARC-ORDER)


Figure 2.34-24 shows that the logic determines the reclosing priority between CB#1 and CB#2;
the scheme switch [ARC-ORDER] is provided to set the process priority. For example, the user
should set CB1 for the [ARC-ORDER] if the CB#1 is being closed firstly.
Table 2.34-12 Starting condition for two CBs system
Setting [ARC-
Mode setting Start condition
ORDER]

[ARC1 mode]= CB1 CB#1 recloses first.


TPAR or SPAR&TPAR
CB2 CB#2 recloses first.
[ARC2 mode]=
TPAR or SPAR&TPAR SIMUL Both CB#1 and CB#2 reclose simultaneously.

Shot1 for CB#1


S 8000011B73 ARC1 TPAR
ARC1 SHOT1 ≥1
R 810001EBBD TPAR1-START TPAR1_START
Shot for CB#2
ARC2 SHOT S 8100021B6F ARC2 TPAR
≥1
R 810002EBBD TPAR2-START TPAR2_START

Initiation
FT ARC1 UNREADY S 8800011B74 For user’s programming
≥1
R ARC1-SUB_INIT

FT ARC2 UNREADY S 8900021B70 Not connected


≥1
R ARC2-SUB_INIT
Start
NON ARC-S1_IN-PROG
SIMUL
CB1
ARC-ORDER
CB2

Figure 2.34-24 Reclose sequence logic

GRL200 (Soft 033 & 037)


- 455 -
6F2S1914 (0.37)

(xv) MPAR logic – settings (TMPAR, ARC-MANOLK, MPAR-MODE)


The MPAR logic is consisted of SPAR scheme, TPAR scheme, and MPAR scheme (Figure
2.34-27); the Link judgment logic (Figure 2.34-28) select a scheme when reclosing the CB is
required.

In parallel lines, when power is able to flow in three-phases (i.e., [MPAR-MODE]=M3;


‘MPAR-LINK’ is judged), the MPAR scheme is selected in the MPAR logic; then, the CB will be
reclosed in the MPAR scheme. If the power does not flow in three-phases (i.e., ‘NO-MPAR-
LINK’), either the SPAR or the TPAR scheme is selected in the MPAR logic to reclose the CB.
The user can set the selection rule of the schemes using setting [ARC-MANOLK]=TPAR or
SPAR&TPAR. The behavers of the SPAR scheme and the TPAR scheme are the same as the
one of the SPAR logic and the TPAR logic—that have been discussed previously.

Note that the ARC function abandons to reclose the CB when setting [ARC-MANOLK]=FT
if ‘MPAR-LINK’ is not judged.

The dead times are required to set in the MPAR logic: [TSPAR1]/[TSPAR2],
[TTPAR1]/[TTPAR2], and [TMPAR1]/[TMPAR2]. Setting the [TRR1] and [TRR2] is also required.

Figure 2.34-25 shows the ARC operation in parallel lines (lines RQ and ST). Table 2.34-13
and Table 2.34-14 tabulates every operation result in the MPAR logic when faults occur in the
parallel lines. The user should understand that the selection of reclosing schemes in the MPAR
logic depends on the settings of [MPAR-MODE] and [ARC-MANOLK].

For the MPAR operation at Relay(R), Relay(Q), Relay(S), and Relay(T), the user should set
MPAR for the settings [ARC1-MODE] at respective relays. Additionally, the user should connect
Relay(R) with Relay(S) using the BO and BI circuits with wires. Similarly, the user should
connect Relay(S) with Relay(T). Figure 2.34-26 illustrates the communication flow when the
MPAR operation is required at three-terminals.

GRL200 (Soft 033 & 037)


- 456 -
6F2S1914 (0.37)

Busbar R Busbar Q

Line RQ
R Q

Relay(R) Relay(Q)
CONN-APPL
CONN-APPL
INTCONN-A_R1
ARC
INTCONN-B_R1
G ARC INTCONN-C_R1 G
COM.FAIL_R1
CLOSE_R1 REMOTE1 (R1)
READY_R1

P.INTCONN-A_LR1 INTCONN-A_LR1
BI BO
N
BI P.INTCONN-B_LR1 INTCONN-B_LR1
BO
O
N P.INTCONN-C_LR1 INTCONN-C_LR1
BI BO
O
N LOCAL (L)

Line ST
S T

Relay(S)
CONN-APPL Relay(T)
INTCONN-A_R1
CONN-APPL
INTCONN-B_R1
ARC INTCONN-C_R1 ARC
COM.FAIL_R1
CLOSE_R1
READY_R1 REMOTE1 (R1) in parallel lines

P.INTCONN-A_LR1 INTCONN-A_LR1
BI BO
N
BI P.INTCONN-B_LR1 INTCONN-B_LR1
BO
O
N P.INTCONN-C_LR1 INTCONN-C_LR1
BI BO
O
N LOCAL in parallel lines

Figure 2.34-25 Parallel lines in MPAR

GRL200 (Soft 033 & 037)


- 457 -
6F2S1914 (0.37)

Busbar R Busbar Q

R Q

COMM link with L, R1, and R2

Relay(R) Relay(Q)
CONN-APPL
CONN-APPL
INTCONN-A_R1
ARC
INTCONN-B_R1
G ARC INTCONN-C_R1 G
COM.FAIL_R1
CLOSE_R1 REMOTE1 (R1)
READY_R1

INTCONN-A_R2
INTCONN-B_R2
INTCONN-C_R2
COM.FAIL_R2
CLOSE_R2
READY_R2

P.INTCONN-A_LR1 INTCONN-A_LR1
BI BO
N
BI P.INTCONN-B_LR1 INTCONN-B_LR1
BO
O
N P.INTCONN-C_LR1 INTCONN-C_LR1
BI BO
O
N
P.INTCONN-A_LR2 INTCONN-A_LR2
BI BO
O
N
BI P.INTCONN-B_LR2 INTCONN-B_LR2
BO
O
N P.INTCONN-C_LR2 INTCONN-C_LR2
BI BO
O
N LOCAL (L)

S T

Relay(S) Relay(T)
CONN-APPL
INTCONN-A_R1 CONN-APPL
INTCONN-B_R1 ARC
ARC INTCONN-C_R1
COM.FAIL_R1
CLOSE_R1 REMOTE1(R1) in parallel lines
READY_R1

INTCONN-A_R2
INTCONN-B_R2
INTCONN-C_R2
COM.FAIL_R2
CLOSE_R2
READY_R2

P.INTCONN-A_LR1 INTCONN-A_LR1
BI BO
N
BI P.INTCONN-B_LR1 INTCONN-B_LR1
BO
O
N P.INTCONN-C_LR1 INTCONN-C_LR1
BI BO
O
N
P.INTCONN-A_LR2 INTCONN-A_LR2
BI BO
O
N
BI P.INTCONN-B_LR2 INTCONN-B_LR2
BO
O
N P.INTCONN-C_LR2 INTCONN-C_LR2
BI BO
O
N
LOCAL in parallel lines

Relay(U)

CONN-APPL
U ARC

REMOTE2(R2)

W Relay(W)

CONN-APPL

Busbar O ARC

REMOTE2(R2) in parallel lines

Figure 2.34-26 Three terminals in MPAR

GRL200 (Soft 033 & 037)


- 458 -
6F2S1914 (0.37)

Settings [ARC-MANOLK]=FT/TPAR/SPAR&TPAR in [MPAR-MODE]=M2


Table 2.34-13 shows tripping and reclosing results when the setting [MPAR-MODE] is M2 (i.e.,
‘M2’ means that two or three unfaulted (healthy) phases exist in the parallel lines; respective
unfualted phases are different).

For setting [ARC-MANOLK]=TPAR or SPAR&TPAR, the CB can be reclosed in the TPAR


scheme when the MPAR-LINK condition is not observed.

For setting [ARC-MANOLK]=FT, the ARC function abandons to reclose the CB as when
the MPAR-LINK condition is not achieved in the paralleled lines.

Table 2.34-13 Tripped phases and mode for CB reclosing in [MPAR-MODE]=M2


TRC tripping with [TP-MODE]=PER-PHASE → ARC reclosing mode with setting [MPAR-MODE]=M2

Faulted phases Setting [ARC-MANOLK]

No Line RQ Line ST FT TPAR SPAR&TPAR

A B C A B C Line RQ Line ST Line RQ Line ST Line RQ Line ST

1 x – – – 1ΦT→MPAR – 1ΦT→MPAR – 1ΦT→MPAR –


2 x x – – – 2ΦT→FT – 2ΦT→TPAR – 2ΦT→TPAR –
3 x x x – – – 3ΦT→FT – 3ΦT→TPAR – 3ΦT→TPAR –
4 x 1ΦT→MPAR (N/A) 1ΦT→MPAR (N/A) 1ΦT→MPAR (N/A)
5 x x 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR
6 x x 2ΦT→MPAR (N/A) 2ΦT→MPAR (N/A) 2ΦT→MPAR (N/A)
7 x x 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR
8 x x x 2ΦT→MPAR 1ΦT→MPAR 2ΦT→MPAR 1ΦT→MPAR 2ΦT→MPAR 1ΦT→MPAR
9 x x x x 2ΦT→FT 2ΦT→FT 2ΦT→TPAR 2ΦT→TPAR 2ΦT→TPAR 2ΦT→TPAR
10 x x x 3ΦT→MPAR (N/A) 3ΦT→MPAR (N/A) 3ΦT→MPAR (N/A)
11 x x x 2ΦT→MPAR 1ΦT→MPAR 2ΦT→MPAR 1ΦT→MPAR 2ΦT→MPAR 1ΦT→MPAR
12 x x x x 2ΦT→MPAR 2ΦT→MPAR 2ΦT→MPAR 2ΦT→MPAR 2ΦT→MPAR 2ΦT→MPAR
13 x x x x 3ΦT→MPAR 1ΦT→MPAR 3ΦT→MPAR 1ΦT→MPAR 3ΦT→MPAR 1ΦT→TPAR
14 x x x x x 3ΦT→FT 2ΦT→FT 3ΦT→TPAR 2ΦT→TPAR 3ΦT→TPAR 2ΦT→TPAR
15 x x x x x x 3ΦT→FT 3ΦT→FT 3ΦT→TPAR 3ΦT→TPAR 3ΦT→TPAR 3ΦT→TPAR

x: Occurrence of the fault


–: Not energized (out of service)
MPAR: To issue a reclose command by ARC_MPAR_COND
TPAR: The TPAR scheme issuing three-phases tripping by ARC_TPAR_COND; then, to
issue a reclose command
FT: To abandon reclosing CB after ARC issuing three-phases tripping by FT setting
1ΦT: To issue a single-phase tripping
2ΦT: To issue two-phases tripping
3ΦT: To issue three-phases tripping
(N.A): Tripping and reclosing do not perform

GRL200 (Soft 033 & 037)


- 459 -
6F2S1914 (0.37)

Settings [ARC-MANOLK]=FT/TPAR/SPAR&TPAR in [MPAR-MODE]=M3


Table 2.34-14 shows the operation results when the setting [MPAR-MODE] is M3 (i.e., ‘M3’
means that three unfaulted (healthy) phases exist in the parallel lines; the respective
unfaulted (healthy) phases are different). For setting [ARC-MANOLK]=SPAR&TPAR, the ARC
function operates to recluse the CB in the SPAR scheme when a faulted phase is found in the
paralleled lines.

Table 2.34-14 Tripped phases and mode for CB reclosing in [MPAR-MODE]=M3


TRC tripping with [TP-MODE]=PER-PHASE → ARC reclosing mode with setting [MPAR-MODE]=M3

Faulted phases Setting [ARC-MANOLK]

No Line RQ Line ST FT TPAR SPAR&TPAR

A B C A B C Line RQ Line ST Line RQ Line ST Line RQ Line ST

1 x – – – 1ΦT→FT – 1ΦT→TPAR – 1ΦT→SPAR –


2 x x – – – 2ΦT→FT – 2ΦT→TPAR – 2ΦT→TPAR –
3 x x x – – – 3ΦT→FT – 3ΦT→TPAR – 3ΦT→TPAR –
4 x 1ΦT→MPAR (N/A) 1ΦT→MPAR (N/A) 1ΦT→MPAR (N/A)
5 x x 1ΦT→FT 1ΦT→FT 1ΦT→TPAR 1ΦT→TPAR 1ΦT→SPAR 1ΦT→SPAR
6 x x 2ΦT→MPAR (N/A) 2ΦT→MPAR (N/A) 2ΦT→MPAR (N/A)
7 x x 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR 1ΦT→MPAR
8 x x x 2ΦT→FT 1ΦT→FT 2ΦT→TPAR 1ΦT→TPAR 2ΦT→TPAR 1ΦT→SPAR
9 x x x x 2ΦT→FT 2ΦT→FT 2ΦT→TPAR 2ΦT→TPAR 2ΦT→TPAR 2ΦT→TPAR
10 x x x 3ΦT→MPAR (N/A) 3ΦT→MPAR (N/A) 3ΦT→MPAR (N/A)
11 x x x 2ΦT→MPAR 1ΦT→MPAR 2ΦT→MPAR 1ΦT→MPAR 2ΦT→MPAR 1ΦT→MPAR
12 x x x x 2ΦT→FT 2ΦT→FT 2ΦT→TPAR 2ΦT→TPAR 2ΦT→TPAR 2ΦT→TPAR
13 x x x x 3ΦT→FT 1ΦT→FT 3ΦT→TPAR 1ΦT→TPAR 3ΦT→TPAR 1ΦT→SPAR
14 x x x x x 3ΦT→FT 2ΦT→FT 3ΦT→TPAR 2ΦT→TPAR 3ΦT→TPAR 2ΦT→TPAR
15 x x x x x x 3ΦT→FT 3ΦT→FT 3ΦT→TPAR 3ΦT→TPAR 3ΦT→TPAR 3ΦT→TPAR

x: Occurrence of the fault


–: Not energized (out of service)
MPAR: To issue a reclose command by ARC_MPAR_COND
TPAR: The TPAR scheme issuing three-phases tripping by ARC_TPAR_COND; then, to
issue a reclose command
SPAR: To issue a reclose command by ARC_SPAR_COND
FT: To abandon reclosing CB after ARC issuing three-phases tripping by FT setting
1ΦT: To issue a single-phase tripping
2ΦT: To issue two-phases tripping
3ΦT: To issue three-phases tripping
(N.A): Tripping and reclosing do not perform

GRL200 (Soft 033 & 037)


- 460 -
6F2S1914 (0.37)

Always ‘1’

From VCHK function Decision of ARC_SPAR_COND


ARC1-VCHK Decision of ARC_TPAR_COND
ARC2-VCHK Decision of ARC_MPAR_COND To TRC
ARC_TPAR_COND induces three-phases tripping.
Link judgment
ARC1_TPAR_COND CB1_94TT
FT ARC-MANOLK=FT ARC2_TPAR_COND CB2_94TT
TPAR ARC-MANOLK=TPAR
ARC-MANOLK
SPAR&TPAR
ARC-MANOLK=S&T Issuing for CB#1
SPAR scheme TSPAR1
t 0 8000011B63
Start &
& ARC1_SPAR
TRIP-1PH
& 800001EBB9 SPAR1_START 0.01 – 300.00 s
&
TRIP-ANYPH & ≥1
≥1
&
TRIP-MPH 800001EBBA SPAR1_COND

MPAR_LINK TSPAR1_SUB
t 0
NO_MPAR_LINK &
Initiation
800001EBBB SPAR1_SUB_START
0.01 – 300.00 s &
ARC1-S1 IN-PROG

ARC2-S1 IN-PROG 800001EBBC SPAR1_SUB_COND

TPAR scheme 8000011B63


TTPAR1
& t 0 ARC1_TPAR
&
810001EBBD TPAR1_START
& ≥1
0.01 – 300.00 s
810001EBBE TPAR1_COND
TTPAR1_SUB
t 0
&
&
810001EBBF TPAR1_SUB_START
0.01 – 300.00 s
810001EBC0 TPAR1_SUB_COND

MPAR scheme TMPAR1


8300011B66
t 0
& & ARC1_MPAR
830001EBC5 MPAR1_START 0.01 – 300.00 s
& ≥1 TPAR sc

830001EBC6 MPAR1_COND
TMPAR1_SUB
t 0
&
& To TRC
830001EBC7 MPAR1_SUB_START
0.01 – 300.00 s
830001EBC8 MPAR1_SUB_COND

Issuing for CB#2


SPAR scheme TSPAR2
t 0 8000021B63
& ARC2_SPAR
&
800001EBB9 SPAR2_START 0.01 – 300.00 s
& ≥1

800001EBBA SPAR2_COND
TSPAR2_SUB
t 0
&
800001EBBB SPAR2_SUB_START
0.01 – 300.00 s &

800001EBBC SPAR2_SUB_COND

TPAR scheme TTPAR2


8000021B64
t 0
& & ARC2_TPAR
810002EBBE TPAR2_START 0.01 – 300.00 s
& ≥1

810002EBBF TPAR2_COND
TTPAR2_SUB
t 0
&
&
810002EBC0 TPAR2_SUB_START 0.01 – 300.00 s
810002EBC1 TPAR2_SUB_COND

TMPAR2
MPAR scheme 8300021B66
t 0
& & ARC2_MPAR
830002EBC6 MPAR2_START 0.01 – 300.00 s
& ≥1

830002EBC7 MPAR2_COND
TMPAR2_SUB
t 0
& To TRC
&
830002EBC8 MPAR2_SUB_START
0.01 – 300.00 s
830002EBC9 MPAR2_SUB_COND

TRR1 To TRC
t 0 CB1_94TT
ARC1-S1 TRR ARC1 FT
TRR2
0.01 – 310.00 s t 0
ARC2 TRR ARC2 FT CB2_94TT
0.01 – 310.00 s
& MPAR NO_LINK1 ARC1 FT CB1_94TT
Reclose sequence
TPAR1_START MPAR NO_LINK ARC2 FT CB2_94TT

TPAR2_START

Figure 2.34-27 MPAR logic

GRL200 (Soft 033 & 037)


- 461 -
6F2S1914 (0.37)

PARALLEL LINE
8000001B74
800000EBB8 P.INTCONN-A_LR1
INTCONN-A_LR1
800000EBB9 P.INTCONN-B_LR1 8100001B75
INTCONN-B_LR1
800000EBBA P.INTCONN-C_LR1 8200001B76
INTCONN-C_LR1

800000EBBB 8000001B77
P.INTCONN-A_LR2
INTCONN-A_LR2
800000EBBC P.INTCONN-B_LR2 8100001B78
INTCONN-B_LR2
800000EBBD P.INTCONN-C_LR2 8200001B79
INTCONN-C_LR2

800000EBBE P.INTCONN-A_LR3 8000001B7A


INTCONN-A_LR3
800000EBBF P.INTCONN-B_LR3 8100001B7B
INTCONN-B_LR3
800000EBC0 P.INTCONN-C_LR3 8200001B7C
INTCONN-C_LR3

800000EBC1 P.INTCONN-A_LR4 8000001B7D


INTCONN-A_LR4
800000EBC2 P.INTCONN-B_LR4 8100001B7E
INTCONN-B_LR4
800000EBC3 P.INTCONN-C_LR4 8200001B7F
INTCONN-C_LR4

From COMM_APPL

REMOTE1
INTCONN-A_R1
& & & & ≥1

INTCONN-B_R1 & & &


& &
≥1
INTCONN-C_R1 & & &
&

COM.FAIL_R1 1 &
≥1
CLOSE_R1
READY_R1
&
&
REMOTE2
INTCONN-A_R2
& & & & ≥1

INTCONN-B_R2 & & &


& &
≥1
INTCONN-C_R2 & & &
&

COM.FAIL_R2 1 &
CLOSE_R2
READY_R2
&
&
REMOTE3
INTCONN-A_R3
& & & & ≥1

INTCONN-B_R3 & & &


& &
≥1
INTCONN-C_R3 & & &
&

COM.FAIL_R3 1 &
CLOSE_R3
READY_R3
&
&
REMOTE4
INTCONN-A_R4
& & & & ≥1

INTCONN-B_R4 & & &


& &
≥1
INTCONN-C_R4 & & &
&

COM.FAIL_R4 1 &
CLOSE_R4
READY_R4
&
&
M2
INTCONN-A_L MPAR-MODE
M3
INTCONN-B_L
MPAR
INTCONN-C_L
MPAR_LINK

Start 1 S
NO_MPAR_LINK
NON ARC-S1_ IN-PROG R

Figure 2.34-28 Link judgment logic

GRL200 (Soft 033 & 037)


- 462 -
6F2S1914 (0.37)

2.34.6 Setting
Autoreclose setting (Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ARC1-EN Off / On - ARC1 scheme switch Off
ARC2-EN Off / On - ARC2 scheme swtich Off
MultiShot-EN Off / On - Off
Comm Off / FT / SPAR /
ARC1-MODE TPAR / SPAR&TPAR / - Auto reclose mode in 1CB-system Off
MPAR / Original
Off / FT / SPAR /
Auto reclose mode of Center-CB in 2CB-
ARC2-MODE TPAR / SPAR&TPAR / - Off
system
MPAR / Original
MPAR-MODE M2 / M3 - Multi phase autoreclose mode M2
FT / TPAR / ARC operation in multi phase ARC NO-LINK
ARC-MANOLK - FT
SPAR&TPAR condition
ARC-ORDER SIMUL / CB1 / CB2 - Turn of the 3-phase autoreclosing circuit start SIMUL
ARC-NUM S1 / S2 / S3 / S4 / S5 - Auto reclose maximum shot number S1
ARC-SucChk Off / On - Autoreclose success checking enable On
FT-3pFault Off / On - Execute final trip in 3-phase fault mode Off
TRESET 0.01 - 300.00 s Autoreclose reset time under CB closed 0.30
TEVLV 0.01 - 300.00 s Evolving fault waiting time 0.30
CHK TARCSUC 0.10 - 100.00 s Autoreclose success checking time 0.30
ARC1 TREADY1 0.0 - 600.0 s Autoreclose1 ready check time 60.0
TSPAR1 0.01 - 300.00 s Autoreclose1 SPAR dead time 0.80
TSPAR1_SUB 0.01 - 300.00 s Autoreclose1 sub-SPAR dead time 300.00
TTPAR1 0.01 - 300.00 s Autoreclose1 TPAR dead time 0.60
TTPAR1_SUB 0.01 - 300.00 s Autoreclose1 sub-TPAR dead time 300.00
TMPAR1 0.01 - 300.00 s Autoreclose1 MPAR dead time 1.00
TMPAR1_SUB 0.01 - 300.00 s Autoreclose1 sub-MPAR dead time 300.00
TORGAR1 0.01 - 300.00 s Autoreclose1 user original ARC dead time 300.00
TORGAR1_SU
0.01 - 300.00 s Autoreclose1 sub user original ARC dead time 300.00
B
TRR1 0.01 - 310.00 s Autoreclose1 reset time 2.00
TCCW1 0.01 - 10.00 s Autoreclose1 ARC command pulse width 0.20
ARC2 TREADY2 0.0 - 600.0 s Autoreclose2 ready check time 60.0
TSPAR2 0.01 - 300.00 s Autoreclose2 SPAR dead time 0.80
TSPAR2_SUB 0.01 - 300.00 s Autoreclose2 sub-SPAR dead time 300.00
TTPAR2 0.01 - 300.00 s Autoreclose2 TPAR dead time 0.60
TTPAR2_SUB 0.01 - 300.00 s Autoreclose2 sub-TPAR dead time 300.00
TMPAR2 0.01 - 300.00 s Autoreclose2 MPAR dead time 1.00
TMPAR2_SUB 0.01 - 300.00 s Autoreclose2 sub-MPAR dead time 300.00
TORGAR2 0.01 - 300.00 s Autoreclose2 user original ARC dead time 300.00
TORGAR2_SU
0.01 - 300.00 s Autoreclose2 sub user original ARC dead time 300.00
B
TRR2 0.01 - 310.00 s Autoreclose2 reset time 2.00
TCCW2 0.01 - 10.00 s Autoreclose2 ARC command pulse width 0.20
Multi TD_MS2 0.01 - 300.00 s 2nd shot ARC dead time 20.00
TRR_MS2 0.01 - 310.00 s 2nd shot ARC reset time 30.00
TD_MS3 0.01 - 300.00 s 3rd shot ARC dead time 20.00
TRR_MS3 0.01 - 310.00 s 3rd shot ARC reset time 30.00
TD_MS4 0.01 - 300.00 s 4th shot ARC dead time 20.00
TRR_MS4 0.01 - 310.00 s 4th shot ARC reset time 30.00
TD_MS5 0.01 - 300.00 s 5th shot ARC dead time 20.00
TRR_MS5 0.01 - 310.00 s 5th shot ARC reset time 30.00

GRL200 (Soft 033 & 037)


- 463 -
6F2S1914 (0.37)

Test tool(Function ID: 441001)


Range Default
Items Unit Contents Note
1A rating 5A rating 1A 5A
Function Test SHOTNUM-TEST Off / S1 / S2 / S3 / S4 / S5 / S6 - ARC test shot number Off

GRL200 (Soft 033 & 037)


- 464 -
6F2S1914 (0.37)

2.34.7 Data ID
 Signal monitoring point
ARC(Function ID: 4A6001)
Element ID Name Description

8500001B6C 3PHASE FAULT 3 phase fault

8000001B81 ARC IN-PROG

8000001BB3 ARC NO ACT No action for ARC

8000011B6C ARC1 CLOSE COMMAND CB close command for ARC1

8C00011B71 ARC1 CLOSE FAIL ARC1 fail

8000011B72 ARC1 CLOSE SUCCESS ARC1 success

8400011B6E ARC1 FT Final trip for ARC1

8200011B61 ARC1 IN-PROG ARC1 in progress

8000011B60 ARC1 READY ARC1 ready

8700011B70 ARC1 RESET ARC1 reset when ARC no action or success

8000011B6B ARC1 SHOT1 ARC1 shot1

8100011B67 ARC1 SHOT2 ARC1 shot2

8200011B68 ARC1 SHOT3 ARC1 shot3

8300011B69 ARC1 SHOT4 ARC1 shot4

8400011B6A ARC1 SHOT5 ARC1 shot5

8100011BC9 ARC1-S2 COND ARC1 shot2 condition

8200011BCA ARC1-S3 COND ARC1 shot3 condition

8300011BCB ARC1-S4 COND ARC1 shot4 condition

8400011BCC ARC1-S5 COND ARC1 shot5 condition

8800011B74 ARC1-SUB_INIT ARC1 sub initiation

3000001B82 ARC1_AUTORECST AutoRecSt signal in RREC of IEC61580 LN

8000011BCF ARC1_BLOCK ARC1 block signal

8000011B73 ARC1_INIT ARC1 initiation

8100011BB1 ARC1_MODE-FT Final trip mode for autoreclose 1

8500011BB5 ARC1_MODE-MPAR Multi-phase mode for autoreclose 1

8000011BB0 ARC1_MODE-OFF Off mode for autoreclose 1

8600011BB6 ARC1_MODE-ORG Original mode for autoreclose 1

8400011BB4 ARC1_MODE-S&T Single and three-phase mode for autoreclose 1

8200011BB2 ARC1_MODE-SPAR Single-phase mode for autoreclose 1

8300011BB3 ARC1_MODE-TPAR Three-phase mode for autoreclose 1

8300011B66 ARC1_MPAR For multi-phase ARC1 operation

8200011B65 ARC1_ORGAR For original ARC1 operation

8000011B63 ARC1_SPAR For single-phase ARC1 operation

8100011B64 ARC1_TPAR For three-phase ARC1 operation

8100021B68 ARC2 CLOSE COMMAND CB close command for ARC2

8C00021B6D ARC2 CLOSE FAIL ARC2 fail

8000021B6E ARC2 CLOSE SUCCESS ARC2 success

8400021B6A ARC2 FT Final trip for ARC2

8200021B61 ARC2 IN-PROG ARC2 in progress

8000021B60 ARC2 READY ARC2 ready

8700021B6C ARC2 RESET ARC2 reset when ARC no action or success

8100021B67 ARC2 SHOT ARC2 shot

8900021B70 ARC2-SUB_INIT ARC2 sub initiation

GRL200 (Soft 033 & 037)


- 465 -
6F2S1914 (0.37)

 Signal monitoring point


ARC(Function ID: 4A6001)
Element ID Name Description

3000001B83 ARC2_AUTORECST AutoRecSt signal in RREC of IEC61580 LN

8100021BB7 ARC2_BLOCK ARC2 block signal

8100021B6F ARC2_INIT ARC2 initiation

8100021BB1 ARC2_MODE-FT Final trip mode for autoreclose 2

8500021BB5 ARC2_MODE-MPAR Multi-phase mode for autoreclose 2

8000021BB0 ARC2_MODE-OFF Off mode for autoreclose 2

8600021BB6 ARC2_MODE-ORG Original mode for autoreclose 2

8400021BB4 ARC2_MODE-S&T Single and three-phase mode for autoreclose 2

8200021BB2 ARC2_MODE-SPAR Single-phase mode for autoreclose 2

8300021BB3 ARC2_MODE-TPAR Three-phase mode for autoreclose 2

8300021B66 ARC2_MPAR For multi-phase ARC2 operation

8200021B65 ARC2_ORGAR For original ARC2 operation

8000021B63 ARC2_SPAR For single-phase ARC2 operation

8100021B64 ARC2_TPAR For three-phase ARC2 operation

8200001BB4 ARC_BLOCK ARC1 & ARC2 block signal

8400001B65 ARC_START ARC start by general trip

8000011BB8 CB1 F.BRIDGE Forcible bridge signal for CB1

8000011BB7 CB1-ARC READY CB1 ready signal for ARC1

8500011B6F CB1_94TT Discrepancy trip signal in CB1

8800011B62 CB1_BRIDGE CB1 bridge

8000011BCD CB1_MANUAL_CLOSE CB1 manual close signal

8100021BB9 CB2 F.BRIDGE Forcible bridge signal for CB2

8100021BB8 CB2-ARC READY CB2 ready signal for ARC2

8500021B6B CB2_94TT Discrepancy trip signal in CB2

8800021B62 CB2_BRIDGE CB2 bridge

8100021BCA CB2_MANUAL_CLOSE CB2 manual close signal

8200001B6A EVOLV-FAULT TIME OVER Time over of evolved fault under S&T mode

8300001B64 EXT.ARC_START External ARC operation

8000001BB0 EXT.ARC_START-A External ARC start signal (phase-A)

8100001BB1 EXT.ARC_START-B External ARC start signal (phase-B)

8200001BB2 EXT.ARC_START-C External ARC start signal (phase-C)

8000011BCE F.CB1_94TT Forcible discrepancy trip signal in CB1

8100021BCB F.CB2_94TT Forcible discrepancy trip signal in CB2

8000011B6D FT ARC1 UNREADY Final trip under ARC1 unready condition

8000021B69 FT ARC2 UNREADY Final trip under ARC2 unready condition

8000001B74 INTCONN-A_LR1

8000001B77 INTCONN-A_LR2

8000001B7A INTCONN-A_LR3

8000001B7D INTCONN-A_LR4

8100001B75 INTCONN-B_LR1

8100001B78 INTCONN-B_LR2

8100001B7B INTCONN-B_LR3

8100001B7E INTCONN-B_LR4

8200001B76 INTCONN-C_LR1

GRL200 (Soft 033 & 037)


- 466 -
6F2S1914 (0.37)

 Signal monitoring point


ARC(Function ID: 4A6001)
Element ID Name Description

8200001B79 INTCONN-C_LR2

8200001B7C INTCONN-C_LR3

8200001B7F INTCONN-C_LR4

8300011BC6 MPAR1_COND For multi-phase ARC1 condition

8300011BC5 MPAR1_START For multi-phase ARC1 start

8300011BC8 MPAR1_SUB_COND For multi-phase ARC1 condition (sub)

8300011BC7 MPAR1_SUB_START For multi-phase ARC1 start (sub)

8300021BC7 MPAR2_COND For multi-phase ARC2 condition

8300021BC6 MPAR2_START For multi-phase ARC2 start

8300021BC9 MPAR2_SUB_COND For multi-phase ARC2 condition (sub)

8300021BC8 MPAR2_SUB_START For multi-phase ARC2 start (sub)

8000001B80 MPAR_LINK

8200011BC2 ORGAR1_COND For original ARC1 condition

8200011BC1 ORGAR1_START For original ARC1 start

8200011BC4 ORGAR1_SUB_COND For original ARC1 condition (sub)

8200011BC3 ORGAR1_SUB_START For original ARC1 start (sub)

8200021BC3 ORGAR2_COND For original ARC2 condition

8200021BC2 ORGAR2_START For original ARC2 start

8200021BC5 ORGAR2_SUB_COND For original ARC2 condition (sub)

8200021BC4 ORGAR2_SUB_START For original ARC2 start (sub)

8000001BB8 P.INTCONN-A_LR1

8000001BBB P.INTCONN-A_LR2

8000001BBE P.INTCONN-A_LR3

8000001BC1 P.INTCONN-A_LR4

8100001BB9 P.INTCONN-B_LR1

8100001BBC P.INTCONN-B_LR2

8100001BBF P.INTCONN-B_LR3

8100001BC2 P.INTCONN-B_LR4

8200001BBA P.INTCONN-C_LR1

8200001BBD P.INTCONN-C_LR2

8200001BC0 P.INTCONN-C_LR3

8200001BC3 P.INTCONN-C_LR4

8000001BB5 RYOP-A Relay operation (phase-A)

8100001BB6 RYOP-B Relay operation (phase-B)

8200001BB7 RYOP-C Relay operation (phase-C)

8400001B6B SHOT NUMBER OVER Shot number over

8000001B6D SHOT_1ST 1st shot from Multi shot ARC counter

8100001B6E SHOT_2ND 2ND shot from Multi shot ARC counter

8200001B6F SHOT_3RD 3RD shot from Multi shot ARC counter

8300001B70 SHOT_4TH 4TH shot from Multi shot ARC counter

8400001B71 SHOT_5TH 5TH shot from Multi shot ARC counter

8500001B72 SHOT_6TH 6TH shot from Multi shot ARC counter

8000001B84 SHOT_MULTI Signal of the second and the following ARC shots

8000011BBA SPAR1_COND For single-phase ARC1 condition

GRL200 (Soft 033 & 037)


- 467 -
6F2S1914 (0.37)

 Signal monitoring point


ARC(Function ID: 4A6001)
Element ID Name Description

8000011BB9 SPAR1_START For single-phase ARC1 start

8000011BBC SPAR1_SUB_COND For single-phase ARC1 condition (sub)

8000011BBB SPAR1_SUB_START For single-phase ARC1 start (sub)

8000021BBB SPAR2_COND For single-phase ARC2 condition

8000021BBA SPAR2_START For single-phase ARC2 start

8000021BBD SPAR2_SUB_COND For single-phase ARC2 condition (sub)

8000021BBC SPAR2_SUB_START For single-phase ARC2 start (sub)

8100011BBE TPAR1_COND For three-phase ARC1 condition

8100011BBD TPAR1_START For three-phase ARC1 start

8100011BC0 TPAR1_SUB_COND For three-phase ARC1 condition (sub)

8100011BBF TPAR1_SUB_START For three-phase ARC1 start (sub)

8100021BBF TPAR2_COND For three-phase ARC2 condition

8100021BBE TPAR2_START For three-phase ARC2 start

8100021BC1 TPAR2_SUB_COND For three-phase ARC2 condition (sub)

8100021BC0 TPAR2_SUB_START For three-phase ARC2 start (sub)

8100001B67 TRIP-1PH 1 phase trip signal

8300001B69 TRIP-3PH 3 phase trip signal

8000001B66 TRIP-ANYPH Any phase trip signal

8200001B68 TRIP-MPH Multi-phase trip signal

 Connection point in PLC logic


ARC(Function ID: 4A6001)
Element ID Name Description

800000EBB3 ARC NO ACT No action for ARC

810001EBC9 ARC1-S2 COND ARC1 shot2 condition

820001EBCA ARC1-S3 COND ARC1 shot3 condition

830001EBCB ARC1-S4 COND ARC1 shot4 condition

840001EBCC ARC1-S5 COND ARC1 shot5 condition

800001EBCF ARC1_BLOCK ARC1 block signal

810001EBB1 ARC1_MODE-FT Final trip mode for autoreclose 1

850001EBB5 ARC1_MODE-MPAR Multi-phase mode for autoreclose 1

800001EBB0 ARC1_MODE-OFF Off mode for autoreclose 1

860001EBB6 ARC1_MODE-ORG Original mode for autoreclose 1

840001EBB4 ARC1_MODE-S&T Single and three-phase mode for autoreclose 1

820001EBB2 ARC1_MODE-SPAR Single-phase mode for autoreclose 1

830001EBB3 ARC1_MODE-TPAR Three-phase mode for autoreclose 1

810002EBB7 ARC2_BLOCK ARC2 block signal

810002EBB1 ARC2_MODE-FT Final trip mode for autoreclose 2

850002EBB5 ARC2_MODE-MPAR Multi-phase mode for autoreclose 2

800002EBB0 ARC2_MODE-OFF Off mode for autoreclose 2

860002EBB6 ARC2_MODE-ORG Original mode for autoreclose 2

840002EBB4 ARC2_MODE-S&T Single and three-phase mode for autoreclose 2

820002EBB2 ARC2_MODE-SPAR Single-phase mode for autoreclose 2

GRL200 (Soft 033 & 037)


- 468 -
6F2S1914 (0.37)

 Connection point in PLC logic


ARC(Function ID: 4A6001)
Element ID Name Description

830002EBB3 ARC2_MODE-TPAR Three-phase mode for autoreclose 2

820000EBB4 ARC_BLOCK ARC1 & ARC2 block signal

800001EBB8 CB1 F.BRIDGE Forcible bridge signal for CB1

800001EBB7 CB1-ARC READY CB1 ready signal for ARC1

800001EBCD CB1_MANUAL_CLOSE CB1 manual close siganl

810002EBB9 CB2 F.BRIDGE Forcible bridge signal for CB2

810002EBB8 CB2-ARC READY CB2 ready signal for ARC2

810002EBCA CB2_MANUAL_CLOSE CB2 manual close siganl

800000EBB0 EXT.ARC_START-A External ARC start signal (phase-A)

810000EBB1 EXT.ARC_START-B External ARC start signal (phase-B)

820000EBB2 EXT.ARC_START-C External ARC start signal (phase-C)

800001EBCE F.CB1_94TT Forcible discrepancy trip signal in CB1

810002EBCB F.CB2_94TT Forcible discrepancy trip signal in CB2

830001EBC6 MPAR1_COND For multi-phase ARC1 condition

830001EBC5 MPAR1_START For multi-phase ARC1 start

830001EBC8 MPAR1_SUB_COND For multi-phase ARC1 condition (sub)

830001EBC7 MPAR1_SUB_START For multi-phase ARC1 start (sub)

830002EBC7 MPAR2_COND For multi-phase ARC2 condition

830002EBC6 MPAR2_START For multi-phase ARC2 start

830002EBC9 MPAR2_SUB_COND For multi-phase ARC2 condition (sub)

830002EBC8 MPAR2_SUB_START For multi-phase ARC2 start (sub)

820001EBC2 ORGAR1_COND For original ARC1 condition

820001EBC1 ORGAR1_START For original ARC1 start

820001EBC4 ORGAR1_SUB_COND For original ARC1 condition (sub)

820001EBC3 ORGAR1_SUB_START For original ARC1 start (sub)

820002EBC3 ORGAR2_COND For original ARC2 condition

820002EBC2 ORGAR2_START For original ARC2 start

820002EBC5 ORGAR2_SUB_COND For original ARC2 condition (sub)

820002EBC4 ORGAR2_SUB_START For original ARC2 start (sub)

800000EBB8 P.INTCONN-A_LR1

800000EBBB P.INTCONN-A_LR2

800000EBBE P.INTCONN-A_LR3

800000EBC1 P.INTCONN-A_LR4

810000EBB9 P.INTCONN-B_LR1

810000EBBC P.INTCONN-B_LR2

810000EBBF P.INTCONN-B_LR3

810000EBC2 P.INTCONN-B_LR4

820000EBBA P.INTCONN-C_LR1

820000EBBD P.INTCONN-C_LR2

820000EBC0 P.INTCONN-C_LR3

820000EBC3 P.INTCONN-C_LR4

800000EBB5 RYOP-A Relay operation (phase-A)

810000EBB6 RYOP-B Relay operation (phase-B)

820000EBB7 RYOP-C Relay operation (phase-C)

GRL200 (Soft 033 & 037)


- 469 -
6F2S1914 (0.37)

 Connection point in PLC logic


ARC(Function ID: 4A6001)
Element ID Name Description

800001EBBA SPAR1_COND For single-phase ARC1 condition

800001EBB9 SPAR1_START For single-phase ARC1 start

800001EBBC SPAR1_SUB_COND For single-phase ARC1 condition (sub)

800001EBBB SPAR1_SUB_START For single-phase ARC1 start (sub)

800002EBBB SPAR2_COND For single-phase ARC2 condition

800002EBBA SPAR2_START For single-phase ARC2 start

800002EBBD SPAR2_SUB_COND For single-phase ARC2 condition (sub)

800002EBBC SPAR2_SUB_START For single-phase ARC2 start (sub)

810001EBBE TPAR1_COND For three-phase ARC1 condition

810001EBBD TPAR1_START For three-phase ARC1 start

810001EBC0 TPAR1_SUB_COND For three-phase ARC1 condition (sub)

810001EBBF TPAR1_SUB_START For three-phase ARC1 start (sub)

810002EBBF TPAR2_COND For three-phase ARC2 condition

810002EBBE TPAR2_START For three-phase ARC2 start

810002EBC1 TPAR2_SUB_COND For three-phase ARC2 condition (sub)

810002EBC0 TPAR2_SUB_START For three-phase ARC2 start (sub)

(2.69a)

GRL200 (Soft 033 & 037)


- 470 -
6F2S1914 (0.37)

Voltage check for autoreclose (VCHK)


The voltage-check-for-autoreclose (VCHK) function is used along with the function of
autoreclose (ARC), as Bus-bar between Lines requires the restoration of service after the
clearance of fault.
The ARC covers two breaker systems: single breaker system (1CB) and single-and-a-half
breaker system (1.5CB), and the ARC has two scheme logics: one scheme logic (ARC1) is for
1CB and for Bus-bar CB of 1.5CB, and another scheme logic (ARC2) is for Center CB of 1.5CB.
Thus, the VCHK consist of two scheme logics (VCHK1 and VCHK2), and VCHK1 is applied to
ARC1; on the other hand, VCHK2 is used for ARC2.
Bus-bar Bus-bar

CB (CB#1)
Line
CB#1(Busbar CB)
ARC1 with
ARC1 with VCHK1 Line
VCHK1

CB#2(Center CB)
ARC2 with
VCHK2 Line2

a. Single breaker on system (1CB) b. One-and-a-half breaker on system (1.5CB)

Figure 2.35-1 Single breaker and double breakers on the system

─────────────────────────────────────────────────────────────────
Note: To determine whether the features are implemented in the IED or not, locate the IED
ordering number; and check the order number at “G&T position” referring to the comparison
table below. For more information, see Appendix: Ordering.
Table 2.35-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
VCHK Voltage check for Auto-reclosing ✓ ✓
✓: Applicable NA: Not applicable

- 471 - GRL200 (Soft 033 & 037)


6F2S1914 (0.37)

2.35.1 VCHK1 for 1CB system


(i) Characteristic and elements
VCHK1 does voltage and synchronous check in 1CB system. Four relay elements (OVB, OVB,
UVL, and UVL) are used for voltage check. Tow relay elements (OVB and OVL) are used for
verification of existing voltage; the remaining ones (UVB and UVL) are used for verification of
non-existing voltage.

(ii) Voltage condition and check zone


Figure 2.35-2 shows four zones (A1 to D1) for voltage verification. For example, if both UVB
and OVL elements are active, VHCK1 determines that the Bus-bar is in Dead condition (no-
voltage) and Line is in Live condition (existing voltage). This condition holds true for A1 zone.
If voltage condition matches with B1 zone, synchronous check is carried out on VCHK1. Thus,
this means that Synchronous check is not carried out in A1, C1 or D1 zones.
VL Line voltage
(Incoming voltage)
Dead bus and Live bus and
live line live line
A1 (DB-LL)
B1 (LB-LL)
VCHK-OVL

Dead bus and Live bus and


dead line dead line
(DB-DL) (LB-DL)
VCHK-UVL
C1 D1
VB Bus-bar voltage
0(V) VCHK-UVB VCHK-OVB (Running voltage)

A1, C1, D1: Voltage check


B1: Synchronism check

Figure 2.35-2 Check zones by VCHK1

Table 2.35-2 Voltage condition by VCHK1


Voltage condition DB_LL LB_LL DB_DL LB_DL

Check zone A1 B1 C1 D1

Bus-bar voltage (VB) Dead Live Dead Live

Line voltage (VL) Live Live Dead Dead

GRL200 (Soft 033 & 037)


- 472 -
6F2S1914 (0.37)

2.35.2 VCHK1 and VCHK2 for 1.5CB system


(i) Characteristic and elements
VCHK1 and VCHK2 are used for verification of existence or non-existence of voltage on 1.5CB
system. As shown in Figure 2.35-3(b), VCHK2 is used in the center CB (CB#2). Four elements
(OVL2, UVL2, OVL, and UVL) are configured for VCHK2; they are used for determination of
existence or non-existence of voltage.

(ii) Voltage condition and check zone


Figure 2.35-3(a) shows that VCHK1 checks the presence of voltage between the Bus-bar and
Line; Figure 2.35-3(b) shows that the VCHK2 checks the presence of voltage between Line2
and Line. The result of the VCHK1 and VCHK2 are shown in Table 2.35-3 and Table 2.35-4,
respectively. Sync check is carried out if the result by VCHK1 is B1 zone and if the result by
VCHK2 is B2 zone.
VL Line voltage
VL Line voltage
(Incoming voltage)
(Incoming voltage)
Dead bus and Live bus and
live line live line Live line and Live line and
A1 (DB-LL)
B1 (LB-LL) dead line2 live line2
A2 (DL2-LL)
B2 (LL2-LL)
VCHK-OVL
VCHK-OVL

Dead bus and Live bus and


Dead line and Dead line and
dead line dead line dead line2 Live line2
(DB-DL) (LB-DL) (DL2-DL) (LL2-DL)
VCHK-UVL VCHK-UVL
C1 D1 C2 D2
VB Bus-bar voltage VL2 Line2 voltage
0 (V) VCHK-UVB VCHK-OVB (Running voltage) 0 (V) VCHK-UVL2 VCHK-OVL2 (Running voltage)

A1, C1, D1: Voltage check A2, C2, D2: Voltage check
a. VCHK1 check zone B1: Synchronism check b. VCHK2 check zone B2: Synchronism check

Figure 2.35-3 Check zones by VCHK1 and VCHK2

Table 2.35-3 Voltage condition by VCHK1


Voltage condition DB_LL LB_LL DB_DL LB_DL
Check zone A1 B1 C1 D1
Bus-bar voltage (VB) Dead Live Dead Live
Line voltage (VL) Live Live Dead Dead

Table 2.35-4 Voltage condition by VCHK2


Voltage condition DL2_LL LL2_LL DL2_DL DL2_LL
Check zone A2 B2 C2 D2
Line2 voltage (VL2) Dead Live Dead Dead
Line voltage (VL) Live Live Dead Live

GRL200 (Soft 033 & 037)


- 473 -
6F2S1914 (0.37)

2.35.3 Scheme for synchronism


VCHK has a measuring function, which checks the difference between a running voltage and
an incoming voltage. The measuring function checks phase angles, voltages, and frequencies.
The VCHK1 determines the synchronism based on the presence of voltage on both Bus-bar and
Line, as shown in Figure 2.35-4(a). The VCHK2 also determines the synchronism based on the
presence of voltage on both Line2 and Line, as shown in Figure 2.35-4(b).

S = SYN1-Angle S = SYN2-Angle

VL VL

s VB s VL2
1 2

V1 V2

VCHK-OVB or VCHK-OVL2 or
VCHK-OVL VCHK-OVL
a. SYN1 b. SYN2

Figure 2.35-4 SYN1 and SYN2 characteristics

This function performs three checks: (1) checking voltage difference, (2) checking
frequency difference, and (3) checking phase difference. The following variables represent
algebraic expression used in these checking:
VB = Bus-bar voltage
VL1 = Line voltage
VL2 = Line2 voltage
ΔV1 = Voltage difference between Bus-bar and Line
ΔV2 = Voltage difference between Line2 and Line
fVB = frequency of VB
fVL = frequency of VL
fVL2 = frequency of VL2
f= slip cycle
Δf1 = frequency difference between Bus-bar and Line
Δf2 = frequency difference between Line2 and Line1
θ1= phase difference between VB and VL
θ2 = phase difference between VL2 and VL
SYN1-dV = Voltage difference setting [SYN1-dV]
SYN2-dV = another voltage difference setting [SYN2-dV]
VCHK-OVB = voltage setting for Bus-bar [VCHK-OVB]
VCHK-OVL = voltage setting for Line [VCHK-OVL]
VCHK-OVL2 =voltage setting for Line2 [VCHK-OVL2]

GRL200 (Soft 033 & 037)


- 474 -
6F2S1914 (0.37)

SYN1-Angle = phase difference between VB and VL, set by [SYN1-Angle]


SYN2-Angle = phase difference between VL2 and VL, set by [SYN2-Angle]
SYN1-df = value of frequency difference between Bus-bar and Line, set by [SYN1-df]
SYN2-df = value of frequency difference between Line2 and Line, set by [SYN2-df]
T_SYN1 = setting of synch check timer (second) [T_SYN1]
T_SYN2 = setting of synch check timer (second) [T_SYN2]

Table 2.35-5 VCHK synchronism setting


Scheme switch Set Comment
SYN1-dV 0 - 150 Difference voltage for the checking SYN1
SYN1-df 0.01 - 2.00 Difference frequency for the checking SYN1
SYN1-Angle 0 - 75 Difference angle for the checking SYN1
SYN1-dfEN Off/ On Enabling for df checking in SYN1
SYN2-df 0.01 - 2.00 Difference frequency for the checking SYN2
SYN2-Angle 0 - 75 Difference angle for the checking SYN2
SYN2-dfEN Off/ On Enabling for df checking in SYN2
VCHK-OVL 10 - 150 Voltage for the checking Live-Line
VCHK-UVL 10 - 150 Voltage for the checking Dead-Line
VCHK-OVL2 10 - 150 Voltage for the checking Live-Line2
Voltage check time "SYN1(Live-Bus & Live-
T_SYN1 0.01 - 100.00
Line & Synchro.)"
Voltage check time "SYN2(Live-Line2 & Live-
T_SYN2 0.01 - 100.00
Line & Synchro.)"

The VCHK can have the decision of synchronism between the running voltage and the
incoming voltage when the following items (i) to (iv) are satisfied:
(i) Voltage magnitudes
The magnitude of the running voltage and the incoming voltage are greater than
the SYN1 and SYN2 settings:
For SYN1 setting: VB ≥ [VCHK-OVB] and VL ≥ [VCHK-OVL]
For SYN2 setting: VL2 ≥ [VCHK-OVL2] and VL ≥ [VCHK-OVL]

(ii) Voltage difference


The differences of the magnitude between the running voltage and the incoming
voltage (ΔV1 and ΔV2) are smaller than the SYN1 and SYN2 settings:
For SYN1 setting: ΔV1 ≥ | VB − K × VL | ≤ [SYN1-dV]
For SYN2 setting: ΔV2 ≥ | VL2 − K × VL | ≤ [SYN2-dV]

Note: The VCHK calculation should be achieved correctly even if respective


rating voltages in VB, VL, and VL2 are not identical. Thus, the VCHK
function has a matching factor (K) designed to adjust the respective rating
voltages when they are not identical. The matching factor (K) is calculated
automatically using the setting values of VCT ratios; the K is generated

GRL200 (Soft 033 & 037)


- 475 -
6F2S1914 (0.37)

based on the busbar voltage as shown below:

VT ratio at Line
K = VT ratio at busbar

whereas, ‘VT ratio at Line’ is obtained from the actual value in VCT
ratio setting corresponding with scheme switch [SYN-VLine], and ‘VT ratio
at busbar’ is obtained from the actual one corresponding with the scheme
switch [SYN-VBus]. We shall see the scheme switches in the succeeding
section.

(iii) Frequency difference


The frequency differences between the running voltage and the incoming voltage
(Δf1 and Δf2) are smaller than the SYN1 and SYN2 settings:
For SYN1 setting: Δf1 ≥ | fVB − fVL | ≤ [SYN1-df]
For SYN2 setting: Δf2 ≥ | fL2 − fVL | ≤ [SYN2-df]

Note: When Off is set for the scheme switch [SYN1-dfEN], the VCHK abandons
the frequency difference condition from synchronism requirements.
Similarly, the frequency difference condition is not valid when [SYN2-dfEN]
= Off.

(iv) Phase angle difference


The phase differences between the running voltage and the incoming voltage (θ1
and θ2) are smaller than the SYN1 and SYN2 settings:
For SYN1 setting: VB × VL cosθ1 ≥ 0
VB × VL sin ([SYN1-Angle]) ≥ VB × VL sin θ1
For SYN2 setting: VL2 × VL cosθ2 ≥ 0
VL2 × VL sin ([SYN2-Angle]) ≥ VL2 ×VL sin θ2

(v) Notice and tips


If the frequency difference between the VL and the VB is shown very large, the
VCHK may fail to make the decision for the synchronism, although Off is set for the
[SYN1-dfEN] to abandon checking the frequency difference. This is because; the
vector passes the [SYN1-Angle] zone very quickly. As a result, the VCHK may fail
to issue the permission command. To avoid the failure, the user has to set values for
settings [SYN1-Angle] and [T_SYN1] depending on the assumed frequency
difference (Δf):

Setting [SYN1-Angle]
∆f > (2.35-1)
180° × Setting [T_SYN1]

GRL200 (Soft 033 & 037)


- 476 -
6F2S1914 (0.37)

where,
Δf= Frequency-difference (or cycle-slip in Hertz)

Tips: Cycles for the synchronism closure can be calculated:

Cycle for synchronism = 1⁄∆f[Hz] (2.35-2)

Time length for getting a synchronism:

2 × Setting [SYN1-Angle] 1
Time = × (2.35-3)
360° ∆f[Hz]

Check time for the synchronism:

2 × Setting [SYN1-Angle] 1
Setting [T_SYN1] < × (2.35-4)
360° ∆f[Hz]

Equations rearrangements:

Setting [SYN1-Angle] 1
Setting [T_SYN1] < × (2.35-5)
180° ∆f[Hz]

1 𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [T_SYN1] 1
> ÷ (2.35-6)
∆𝑓[𝐻𝑧] Setting [SYN1-Angle] 180°

𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [SYN1-Angle] 1
𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [T_SYN1] < × (2.35-7)
180° ∆𝑓[𝐻𝑧]

GRL200 (Soft 033 & 037)


- 477 -
6F2S1914 (0.37)

VL : fVL=50.02Hz

VB : fVB=50.00Hz

time

Δf Δf Δf

Example: |fVB – fVL |=|50.00Hz – 50.02Hz| = 0.02Hz = 10s

VL

50s SYN1-Angle

VB Synchronism zone

Figure 2.35-5 Synchronism between VB and VL when system frequency = 50Hz


Note: Settings [SYN2-Angle] and [T_SYN2] are also applicable for these calculations.

GRL200 (Soft 033 & 037)


- 478 -
6F2S1914 (0.37)

2.35.4 VCHK1 setting for 1CB system


When the VCHK1 is applied to 1CB system, OVB and UVB check the voltage of a Bus-bar,
whereas OVL and UVL check the voltage of Line, as described earlier. The Bus-bar and Line
voltages are obtained in the VCT1. Thus, user should set the scheme switches [SYN-VBus] and
[SYN-VLine] in accordance with the phase(s) of input-voltage(s). The following are the setting
examples when VCHK is used in 1CB system.

1Note: For more information on VCT, see Chapter Technical description: Transfer
module. For external connection, see Appendix: Typical external connection.

Table 2.35-6 VCHK line selection setting


Scheme switch Set Comment
V-L1 / V-L2 / V-L3
V-L12 / V-L23 / V-L31
Selection of Bus
SYN-VBus V2-L1 / V2-L2 / V2-L3 voltage(Running Voltage) for
V2-L12 / V2-L23 / V2-L31 SYN1

V3 / V4
V-L1 / V-L2 / V-L3
V-L12 / V-L23 / V-L31
Selection of Line voltage
SYN-VLine V2-L1 / V2-L2 / V2-L3
(Incoming Voltage) for SYN1
V2-L12 / V2-L23 / V2-L31

V3 / V4

GRL200 (Soft 033 & 037)


- 479 -
6F2S1914 (0.37)

(i) Setting example 1 (Bus-bar VT=three phases, Line VT=phase-A)

Line
VCT1

Line VT
(Phase-A)
Va
Va (VL1)

Vb (VL2)
Bus-bar VT
Bus-bar

(Three Phase)
Vc Vb
Vc (VL3)
a. Phasor diagram in Line

Vs (V3)
Vs

Vs2 (V4) b. Phasor diagram in Bus-bar

V Line (Vs)2

VBus-bar (Va)3

Figure 2.35-6 Example 1: Input voltages and respective phasor diagram for SYN1
1Note: The structure of VCT is dependent on the VCT type. (See chapter Technical
description: Transformer module)
2 Note: VBus-bar is Running voltage.
3Note: VLine is Incoming voltage.

Figure 2.35-6 shows the VCT input voltages and phases from Bus-bar and Line, and
shows the phase relationship between the running voltage and the incoming voltage. In this
case, configure the settings in accordance with Figure 2.35-6 and Table 2.35-7.
Table 2.35-7 Setting for example 1
Output voltage at VT Bus-bar VT= Three phase
Line VT= Phase-A
Input voltage at VCHK Running voltage (Va)= Phase-A (Bus-bar VT)
Incoming voltage (Vs)= Phase-A (Line VT)
VCHK Setting4 [SYN-VBus] = V-L1
[SYN-VLine]= V3
4Note: Set V3 for the scheme switch [SYN-VLine]. This is because V3 and V-L1 are in the
same phase.

GRL200 (Soft 033 & 037)


- 480 -
6F2S1914 (0.37)

(ii) Setting example 2 (Bus-bar VT=three phases, Line VT=phase-BC)

Line VCT

Line VT
(Phase B-C)
Va
Va (VL1)

Vb (VL2)
Bus-bar VT Vc
Bus-bar

(Three Phase)
Vb
Vc (VL3) Vbc
a. Phasor diagram in Bus-bar

Vs (V3) Vs

b. Phasor diagram in Line


Vs2 (V4)

VLine (Vs)1

VBus-bar (Vbc)2

Figure 2.35-7 Example 2: Input voltages and respective phasor diagram for SYN1
1 Note: VBus-bar is Running voltage.
2Note: VLine is Incoming voltage.

Similarly, Figure 2.35-7 shows the VCT input voltages and phases from Bus-bar and Line.
In this case, configure the settings in accordance with Figure 2.35-7 and Table 2.35-8.
Table 2.35-8 Setting for example 2
Output voltage at VT Bus-bar VT= Three phase
Line VT= Phase-BC
Input voltage at VCHK Running voltage(Vb and c)= Phase-B and C (Bus-bar VT)
Incoming voltage (Vs)= Phase-BC (Line VT)
VCHK Setting3 [SYN-VBus] = V-L23
[SYN-VLine]= V3
3Note: V3 is set for the scheme switch [SYN-VLine]. This is because the resultant phase
of V-L2, V-L3 and V3 is same.

GRL200 (Soft 033 & 037)


- 481 -
6F2S1914 (0.37)

(iii) Setting example 3 (Bus-bar VT=Phase-C, Line VT= Three-phase)

Line
VCT

Line VT
(Three phase)

Va (VL1) Va

Vb (VL2)
Bus-bar VT
Bus-bar

(Phase C)
Vc Vb
Vc (VL3)
a. Phasor diagram in line

Vs (V3) Vs

b. Phasor diagram in Bus-bar


Vs2 (V4)

VLine (Vc)1

VBus-bar (Vs)2

Figure 2.35-8 Example 3: Input voltages and respective phasor diagram for SYN1
1 Note: VBus-bar is Running voltage.
2Note: VLine is Incoming voltage.

The configuration of inputs voltages and phases is done as shown in Figure 2.35-8. In
this case, configure the settings in accordance with Figure 2.35-8 and Table 2.35-9.

Table 2.35-9 Setting for example 3


Output voltage at VT Bus-bar VT= Phase-C
Line VT= Three phase
Input voltage at VCT Running voltage (Vs)= Phase-C (Bus-bar VT)
Incoming voltage (Vc)= Phsse-C (Line VT)
VCHK Setting [SYN-VBus] = V3
[SYN-VLine]= V-L31
1Note: Set V-L3 for the scheme switch [SYN-VLine]. This is because V3 and V-L3 are in
the same phase.

GRL200 (Soft 033 & 037)


- 482 -
6F2S1914 (0.37)

2.35.5 VCHK1 and VCHK2 settings for 1.5CB system

Bus-bar
VCT
Bus-bar VT
(Phase-B)

Line Va (V-L1) Va

Line VT
(Three-phase) Vb (V-L2)

Vc Vb
Vc (V-L3)
a. Phasor diagram in Line
Line2
Vs (V3) Vs
Line2 VT
(Phase-B) b. Phasor diagram in Bus

Vs2 (V4)
Vs2

c. Phasor diagram in Line2

VLine (Vb) VLine (Vb)

VBus-bar (Vs)
VLine2 (Vs2)

d. Phasor diagram in SYN11 e. Phasor diagram in SYN22

Figure 2.35-9 Input voltages and respective phasor diagram for SYN1 and SYN2
1Note: V
Bus-bar is Running voltage. VLine is Incoming voltage.
2Note: V
Line2 is Running voltage. VLine is Incoming voltage.

GRL200 (Soft 033 & 037)


- 483 -
6F2S1914 (0.37)

When VCHK1 and VCHK2 are used in 1.5CB system, set the scheme switches [SYN-
VBus], [SYN-VLine], and [SYN-VLine2]. For example, the settings in Figure 2.35-9 are applied
when VCHK 1 and VCHK2 are applied in the 1.5CB system.

Table 2.35-10 Setting example for 1.5CB system


Output voltage Bus-bar VT= Phase-B
at VT Line VT= Three phase
Line2 VT= Phase-B
Input voltage Running voltage of SYN1(VS)=Phase-B (Bus-bar VT)
at VCT Incoming voltage of SYN1 and SYN2 (Vb)=Phase-B (Line VT)
Running voltage of SYN2 (VS2)= Phase-B (Line2 VT)
VCHK Setting3 [SYN-VBus] = V3
[SYN-VLine]= V-L2
[SYN-VLine2] = V4
3Note: Set V-L2 for the scheme switch [SYN-VLine]. This is because V3 and VL2 are in
the same phase. Set V4 for the scheme switch [SYN-VLine2]. This is because V3
and V4 are in the same phase.

Table 2.35-11 VCHK line1 and line2 selection setting


Scheme switch Set Comment
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 / Selection of Bus
SYN-VBus V-L31 / V2-L1 / V2-L2 / V2-L3 / V2- voltage(Running Voltage) for
L12 / V2-L23 / V2-L31 / V3 / V4 SYN1
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 / Selection of Line voltage
SYN-VLine V-L31 / V2-L1 / V2-L2 / V2-L3 / V2- (Incoming Voltage) for SYN1
L12 / V2-L23 / V2-L31 / V3 / V4 and SYN2
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 /
Selection of Line2 voltage
SYN-VLine2 V-L31 / V2-L1 / V2-L2 / V2-L3 / V2-
(Running voltage) for SYN2
L12 / V2-L23 / V2-L31 / V3 / V4

GRL200 (Soft 033 & 037)


- 484 -
6F2S1914 (0.37)

2.35.6 Scheme and activation


VCHK1 and VCHK2 provide output signals to the ARC with results of voltage check and
synchronism check as described earlier. The energizing control scheme of VCHK1 is drawn in
Figure 2.35-10, the output signal ARC1-VCHK is fed to ARC1 when one or more of the
following conditions are established: (1) the VCHK1 runs, (2) the OVB and the UVL run, or (3)
the UVB and the OVL run. The activation of VCHK1 is controlled by using the scheme
switches: [ARC1-LB_DL], [ARC1-DB_LL], [ARC1-DB_DL], and [ARC1-SYN1]. For example,
DB_LL in Table 2.35-2 is only the criteria for ARC1 operation, On is set for the scheme switch
[ARC1-DB_LL] while Off is set for other scheme switches. As a result, the system is energized
in the direction from line to bus with ARC1. As shown in Figure 2.35-11, the operation of the
VCHK2 is also applicable in accordance with Figure 2.35-3 similar to VCHK1. Note that the
SYN1-df and SYN2-df operations are nullified when Off are set for the [SYN1-dfEN] and
[SYN2-dfEN].

8200011B62 OVB T_LB_DL


OVB t 0 8000011B6D
&
&
8000011B23
0.01-100.00S
ARC1-LB_DL ON ≥1 ARC1-VCHK
8000011B63
UVB T_DB_LL 8100011B6E
& t 0
&
0.01-100.00S
ARC1-DB_LL ON
8300011B60 OVL
OVL

8C00011B67 T_OVL3P 8F00011B6F


L1 t 0
8D00011B68 & VCHK_OVL3P
OVL L2
8E00011B69 0.01-100.00S
L3

T_DB_DL
8100011B61 UVL 8200011B70
& t 0
UVL &
0.01-100.00S
ARC1-DB_DL ON

8300011B71
OVB
T_SYN1 8300011B72
&
t 0 &
OVL
0.01-100.00S ARC1-SYN1 ON
8400011B64
SYN1-dƟ

8500011B65 ARC1-NOVCHK ON
SYN1-dV

8600011B66
SYN1-df
≥1
SYN1-dfEN OFF

Figure 2.35-10 Logic of VCHK1

GRL200 (Soft 033 & 037)


- 485 -
6F2S1914 (0.37)

8200021B60 OVL2 T_LL2_DL


OVL2 t 0 8024001001
&
&
8100021B23
0.01-100.00S ARC2-VCHK
ARC2-LL2_DL ON ≥1
8000021B61
UVL2 T_DL2_LL 8124011001
& t 0
&
0.01-100.00S
ARC2-DL2_LL ON

OVL

T_DL2_DL
UVL 8200021B6A
& t 0
&
0.01-100.00S
ARC2-DL2_DL ON

8300021B6B
OVL2
T_SYN2 8300021B6C
&
t 0 &
OVL
0.01-100.00S ARC2-SYN2 ON
8400021B62
SYN2-dƟ

8500021B63 ARC2-NOVCHK ON
SYN2-dV

8600021B64
SYN2-df

≥1
SYN2-dfEN OFF

Figure 2.35-11 Logic of VCHK2

GRL200 (Soft 033 & 037)


- 486 -
6F2S1914 (0.37)

2.35.7 Setting
VCHK(Function ID: 4A8001) at Autoreclose
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ARC1-VCHK-
Off / On - VCHK1 scheme switch Off
EN
ARC2-VCHK-
Off / On - VCHK2 scheme switch Off
EN
ARC1 Voltage V-L1 / V-L2 / V-L3 / V-
check L12 / V-L23 / V-L31 /
SYN-Vbus V2-L1 / V2-L2 / V2-L3 - Running Voltage V3
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
SYN-Vline V2-L1 / V2-L2 / V2-L3 - Incoming Voltage V-L1
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
VCHK-OVB 10 - 150 V Voltage for the checking Live-Bus 51
VCHK-UVB 10 - 150 V Voltage for the checking Dead-Bus 13
VCHK-OVL 10 - 150 V Voltage for the checking Live-Line 51
VCHK-UVL 10 - 150 V Voltage for the checking Dead-Line 13
SYN1-Angle 0 - 75 deg Difference angle for the checking SYN1 30
SYN1-dV 0 - 150 V Difference voltage for the checking SYN1 150
SYN1-df 0.01 - 2.00 Hz Difference frequency for the checking SYN1 1.00
Voltage check Live-Bus & Dead-Line is
ARC1-LB_DL Off / On - Off
applied to ARC1
Voltage check Dead-Bus & Live-Line is
ARC1-DB_LL Off / On - Off
applied to ARC1
Voltage check Dead-Bus & Dead-Line is
ARC1-DB_DL Off / On - Off
applied to ARC1
ARC1-SYN1 Off / On - Voltage check SYN1 is applied to ARC1 Off
ARC1-
Off / On - Voltage check is not applied to ARC1 On
NOVCHK
T_LB_DL 0.01 - 100.00 s Voltage check time Live-Bus and Dead-Line 0.05
T_DB_LL 0.01 - 100.00 s Voltage check time Dead-Bus and Live-Line 0.05
T_DB_DL 0.01 - 100.00 s Voltage check time Dead-Bus and Dead-Line 0.05
T_SYN1 0.01 - 100.00 s Voltage check time SYN1 1.00
T_OVL3P 0.01 - 100.00 s Voltage check time 3phase Live-line 0.05
ARC2 Voltage V-L1 / V-L2 / V-L3 / V-
check L12 / V-L23 / V-L31 /
SYN-Vline2 V2-L1 / V2-L2 / V2-L3 - Running Voltage V4
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
VCHK-OVL2 10 - 150 V Voltage for the checking Live-Line2 51
VCHK-UVL2 10 - 150 V Voltage for the checking Dead-Line2 13
SYN2-Angle 0 - 75 deg Difference angle for the checking SYN2 30
SYN2-dV 0 - 150 V Difference voltage for the checking SYN2 150
SYN2-df 0.01 - 2.00 Hz Difference frequency for the checking SYN2 1.00
Voltage check Live-Line2 & Dead-Line is
ARC2-LL2_DL Off / On - Off
applied to ARC2
Voltage check Dead-Line2 & Live-Line is
ARC2-DL2_LL Off / On - Off
applied to ARC2
Voltage check Dead-Line2 & Dead-Line is
ARC2-DL2_DL Off / On - Off
applied to ARC2
ARC2-SYN2 Off / On - Voltage check SYN2 is applied to ARC2 Off

GRL200 (Soft 033 & 037)


- 487 -
6F2S1914 (0.37)

VCHK(Function ID: 4A8001) at Autoreclose


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ARC2-
Off / On - Voltage check is not applied to ARC2 On
NOVCHK
T_LL2_DL 0.01 - 100.00 s Voltage check time Live-Line2 and Dead-Line 0.05
T_DL2_LL 0.01 - 100.00 s Voltage check time Dead-Line2 and Live-Line 0.05
T_DL2_DL 0.01 - 100.00 s Voltage check time Dead-Line2 and Dead-Line 0.05
T_SYN2 0.01 - 100.00 s Voltage check time SYN2 1.00

GRL200 (Soft 033 & 037)


- 488 -
6F2S1914 (0.37)

2.35.8 Data ID
 Signal monitoring point
VCHK(Function ID: 4A8001)
Element ID Name Description
8000011B23 ARC1-VCHK Voltage check for autoreclose 1

8100021B23 ARC2-VCHK Voltage check for autoreclose 2

8200011B62 OVB OVB relay element operated

8300011B60 OVL OVL relay element operated

8C00011B67 OVL-L1 OVL relay element operated (phase-L1)

8D00011B68 OVL-L2 OVL relay element operated (phase-L2)

8E00011B69 OVL-L3 OVL relay element operated (phase-L3)

8200021B60 OVL2 OVL2 relay element operated

8300011B71 SYN1 Synchronous voltage 1(before timer)

8400011B64 SYN1-ANGLE SYN1-Angle relay element operated

8800011B6B SYN1-ANGLE LOSS SYN1 Angle check(loss)

8700011B6A SYN1-ANGLE ZERO SYN1 Angle check(zero)

8600011B66 SYN1-DF SYN1-df relay element operated

8500011B65 SYN1-DV SYN1-dV relay element operated

8B00011B6C SYN1-V5PER SYN1 Voltage check(V5per)

8300021B6B SYN2 Synchronous voltage 2(before timer)

8400021B62 SYN2-ANGLE SYN2-Angle relay element operated

8800021B66 SYN2-ANGLE LOSS SYN2 Angle check(loss)

8700021B65 SYN2-ANGLE ZERO SYN2 Angle check(zero)

8600021B64 SYN2-DF SYN2-df relay element operated

8500021B63 SYN2-DV SYN2-dV relay element operated

8B00021B67 SYN2-V5PER SYN2 Voltage check(V5per)

8000011B63 UVB UVB relay element operated

8100011B61 UVL UVL relay element operated

8000021B61 UVL2 UVL2 relay element operated

8200011B70 VCHK_DB-DL Voltage check(Dead Bus & Dead Line)

8100011B6E VCHK_DB_LL Voltage check(Dead Bus & Live Line)

8200021B6A VCHK_DL2-DL Voltage check(Dead Line2 & Dead Line)

8100021B69 VCHK_DL2-LL Voltage check(Dead Line2 & Live Line)

8000011B6D VCHK_LB-DL Voltage check(Live Bus & Dead Line)

8000021B68 VCHK_LL2-DL Voltage check(Live Line2 & Dead Line)

8F00011B6F VCHK_OVL3P Voltage check(Live 3phase Line)

8300011B72 VCHK_SYN1 Synchronous voltage 1(after timer)

8300021B6C VCHK_SYN2 Synchronous voltage 2(after timer)

GRL200 (Soft 033 & 037)


- 489 -
6F2S1914 (0.37)

Transmission control function (DIF_COMM)


In order that several protection functions can handle their computation diversely, the
transmission control (DIF_COMM) function is provided along with protection signalling
modules†. The DIF_COMM function operates with the telecommunication system; the
telecommunication medium is provided such as dark fiber (dedicated fiber-optic cable),
multiplexed fiber-optics, digital microwave, and others. Accordingly, the protection functions
linked with the remote-terminals can exchange their data mutually.

For the DIF_COMM operation, the user should arrange communication interface†,
synchronization method, and topology consideration: the communication interface provides the
link means physically; the synchronization method provides accuracy in their computation;
the topology provides the network configuration philosophy
†Note:For more information about the protection signaling modules, see Chapter
Technical description: Signal processing module: Communication modules. .

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the “G&T position” referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 2.36-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Features
33 37
Main features Communication for protection ✓ ✓
Number of terminals Available maximum terminals 3 3
Number of channels Maximum channel number per IED 2 2
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 490 -
6F2S1914 (0.37)

2.36.1 Data communication interface


Communication interface is relevant to the property and capacity of channels; hence, IEEE
C37.94 (either N=1 or N=3) is provided in the DIF_COMM function. Securing clock recovery,
jitter tolerance, physical connection, and spuriousness are specified by the international
standard.

(i) IEEE C37.94 (N=1)


The C37.94 (N=1) link provides transmission format. Thereby, the DIF_COMM function uses
the transmission format for sending. The data which is sent for the remote-terminal is current
values, command signals and others:
 Current data in phase–a, –b, and –c at sampling time
 Residual current data at sampling time
 Output signals in phase-a, -b, and –c from the differential protection function
 Statuses of breaker and disconnector in phase–a, –b, and –c
 Statuses of scheme switches such as test and others
 Blocking commands for reclosing
 Sampling synchronization control signals
 Synchronized test trigger signals
 User configurable data

The current data are represented in instantaneous values; the values are sampled every
30-electrical degree. For instance, provided the power system frequency is 60 Hz, the 30-
electrical degree means that the sampling interval is 1.38 milliseconds (=1/720Hz). Twelve bits
(11 data bits plus a sign bit) are used to present a current data. The IED determines the current
data in the every 30-electrical degree; hence the DIF_COMM function can send the data in the
every 30-electrical degree. The DIF_COMM function also sends commands and other data; the
data are made of several signals: a signal of the differential current function, a signal of the
direct transfer trip function, a test signal, and a sync signal. Note that the DIF_COMM
function sends a signal per the 30-electrical degree with regard to the differential current
function the direct the transfer trip function. On the other hand, the DIF_COMM function
sends the other signals per 360-electrcal degree (=a cycle of the power system frequency)

The transmission format includes cyclic redundancy check (CRC) bits and check bit solid.
In case of communication failure, the DIF_COMM function set zero data for the format so as
not to operate the differential and other protection functions. Consequently, the protection
function corresponding to the DIF_COMM function can halt.

When the user wishes to use a communication module for the protection in the IEEE
C37.94 (N=1) at the channel#1, set Normal for the scheme switch [CH1_COM_WIDTH], for

GRL200 (Soft 033 & 037)


- 491 -
6F2S1914 (0.37)

example.

(ii) IEEE C37.94 (N=3)


The IEEE C37.94 (N=3) is provided when the transmission capacity is wider† than the IEEE
(N=1); the DIF_COMM function can also transmit current data at pre-sampling time;
consequently the computation range is extended dynamically. Thus, the computation
performance and accuracy are improved in the differential and other protection functions.

The transmission capacity in the IEEE C37.94 (N=3) is wider than the one in the IEEE
C37.94 (N=1). Followings are added newly when the IEEE C37.94 (N=3) is applied for the
communication:
 Current data at pre-sampling time in phase–a, –b, and –c
 Residual current data at pre-sampling time

In order to apply for the IEEE C37.94 (N=3) at the channel#1, the user should set Wide for the
scheme switch [CH1_COM_WIDTH].

†Note:Transmission data, which is carried with N=3 extended frame, are made of analog
input quantities that are exclusively entailed in WDE element. For more detail,
see Chapter Relay application: CT saturation countermeasure in DIFL.).

2.36.2 Synchronization control


All the IEDs are required to examine the data sampled at the same time and to keep handing
this data at the same address. Thus, the DIF_COMM function has synchronization control
functions that are referred as timing, addressing, delaying, master-and-slave, and re-
synchronization functions. That is, it is not until the entire IEDs start sampling their data
simultaneously. The synchronization control function does not require an external reference
clock or a synchronized internal clock because the channel delay in the telecommunication is
equalized automatically in the IEDs. This equalization method is performed by the master-
and-slave setup and delay compensation technique. These also bring the IED to recover when
the master-and-slave setup function is broken abruptly for the operation. Consequently, the
entire IEDs can stay in their synchronization state as possible.

(i) IEDs arrangement and setup


The synchronization starts when all IEDs are connected. Note that the user is forbidden to
change the IED arrangement while the IEDs operate. This is because, it is impossible to change
all IED arrangements at the same time.

2Term mode

GRL200 (Soft 033 & 037)


- 492 -
6F2S1914 (0.37)

Figure 2.36-1 shows two IEDs arrangement when two IEDs connect with a channel. In the
arrangement, the user can select IED_G as the master and should set 1 for the scheme switch
[TERM_ID], whereas the user should select another IED_H as the slave and set 2 for the
scheme switch [TERM_ID]. The user should also set 2Term for the scheme switch
[TERM_TOPOLOGY] in both IEDs.
IED_G IED_H
Property: Master Property: Slave
[TERM_TOPOLOGY] =2Term [TERM_TOPOLOGY] =2Term
[TERM_ID] =1 [TERM_ID] =2
CH1 CH2 CH1 CH2

Figure 2.36-1 Two IEDs and setup for a single channel

2Term-Dual mode
When two IEDs are linked with dual channels, the user set 2Term-Dual for the scheme switch
[TERM_TOPOLOGY] respectively, as shown in Figure 2.36-2. Note that IEDs will have
incorrect relay computations and improper communication, if the IEDs do not have the same
data communication interface. Thus, the user shall set either Normal or Wide for the scheme
switches [CH1_COM_WIDTH] and [CH2_COM_WIDTH] at both IEDs.

IED_G IED_H
Property: Master Property: Slave
[TERM_TOPOLOGY] =2Term-Dual [TERM_TOPOLOGY] =2Term-Dual
[TERM_ID] =1 [TERM_ID] =2
CH1 CH2 CH1 CH2

Figure 2.36-2 Two IEDs and setup for dual channels

3Term mode
Figure 2.36-3 shows three IEDs arrangement; the three IEDs are linked with three channels.
Based on the IED’s property, IED_G can run as the master while IED_H and IED_R can run
as the slave. Thus, the user should set 1 for the scheme switch [TERM_ID] in IED_G. On the
other hand, set 2 and 3 for the IED_H’s [TERM_ID] and the IED_R’s [TERM_ID], respectively;
then, the user can set 3Term for the scheme switch [TERM_TOPOLOGY] at three IEDs. Either
Normal or Wide shall be set for the [CH*_COM_WIDTH] at all IEDs unconditionally in order
that the communication interface between IEDs are united.

GRL200 (Soft 033 & 037)


- 493 -
6F2S1914 (0.37)

IED_G IED_H
Property: Master Property: Slave
[TERM_TOPOLOGY] =3Term [TERM_TOPOLOGY] =3Term
[TERM_ID] =1 [TERM_ID] =2
CH1 CH2 CH1 CH2
IED_R

CH1

[TERM_TOPOLOGY] =3Term
[TERM_ID] =3

Property: Slave
CH2
Figure 2.36-3 Three IEDs and setup

4Term mode
Figure 2.36-4 shows four arrangements. Their settings can be treated with the same manner.
IED_G IED_H
Property: Master Property: Slave
[TERM_TOPOLOGY] =4Term [TERM_TOPOLOGY] =4Term
[TERM_ID] =1 [TERM_ID] =2
CH1 CH2 CH3 CH4 CH1 CH2 CH3 CH4

IED_R
CH1

[TERM_TOPOLOGY] =4Term
[TERM_ID] =3

Property: Slave
CH2
CH3
CH4

IED_S
CH1 CH2 CH3 CH4
Property: Slave
[TERM_TOPOLOGY] =4Term
[TERM_ID] =4

Figure 2.36-4 Four IEDs and setup

5Term mode
Figure 2.36-5s five IEDs arrangements. Their settings can be treated with the same manner.

GRL200 (Soft 033 & 037)


- 494 -
6F2S1914 (0.37)

IED_G IED_H
Property: Master Property: Slave
[TERM_TOPOLOGY] =5Term [TERM_TOPOLOGY] =5Term
[TERM_ID] =1 [TERM_ID] =2
CH1 CH2 CH3 CH4 CH1 CH2 CH3 CH4

IED_R

CH1

[TERM_TOPOLOGY] =5Term
[TERM_ID] =3

Property: Slave
CH2
CH3
CH4
CH1 CH2 CH3 CH4 CH1 CH2 CH3 CH4
Property: Slave Property: Slave
[TERM_TOPOLOGY] =5Term [TERM_TOPOLOGY] =5Term
[TERM_ID] =4 [TERM_ID] =5
IED_S IED_L

Figure 2.36-5 Five IEDs and setup

(ii) Time synchronization


When the user selects an IED as the master; the IED becomes the time reference. After the
selection, the sampling time difference between (∆T) is determined between the master and
the slave, as shown in Figure 2.36-6.

(2) IED_G receives the signal. (3) IED_G replay to IED_H with the signal received.

TM Td2
Master
IED_G t

T T T

Slave
t
IED_H Td1 TF

(1) IED_H sends a signal to IED_G. (4) IED_H receives its own signal.

Sampling timing at IED_G


Sampling timing at IED_H
A signal in downstream (IED_H to IED_G)
A signal in upstream (IED_G to IED_H)

Figure 2.36-6 Sampling timing before synchronization

GRL200 (Soft 033 & 037)


- 495 -
6F2S1914 (0.37)

Figure 2.36-6 shows pre-synchronization circumstance between the master IED_G and
the slave IDE_H. The user can find that the sampling timings between are different. In order
that the IED_H synchronizes with the IED_G, accounting for the synchronization is provided
with process (1) to (4) of Figure 2.36-6.
1. The IED_H send a signal to the IED_G at sampling time of IED_H.
2. The IED_G receives this signal.
3. The IED_G replies to the IED_H at sampling time of IED_G.
4. This signal reverts to the IED_H.

As seen from Figure 2.36-6(2), the IED_G can determine the time TM with the clock in
the IED_G and the arrival time of this signal. On the other hand, in Figure 2.36-6(4), the
IED_H can determine the time TF with the clock in the IED_H. The IED_H also can determine
the arrival time of that signal.

Figure 2.36-7 shows a communication for the protection; the channel is provided at both
the master IED_G and the slave IED_H.

IED_G IED_H
Communication channel
CH1 Downstream line with propagation delay CH1
Rx Tx
Tx Upstream line with propagation delay Rx

Master Slave

Figure 2.36-7 Communication channel between IEDs

When provided delay time of channel #1 provided by the telecommunication carrier, the
∆T can be obtained from the following equations:

(𝑇𝐹 − 𝑇𝑀 ) + (𝑇𝑑1 − 𝑇𝑑2 )


∆T = (2.36-1)
2

where,
TM: Sampling displacement between IEDs on the master IED (TM= Td1−∆T)
TF: Sampling displacement between IEDs on the slave IED (TF= Td2+∆T)
Td1: Propagation time of the downstream line
Td2: Propagation time of the upstream line

GRL200 (Soft 033 & 037)


- 496 -
6F2S1914 (0.37)

Sampling pulses are generated by the clock in the slave IED_H; hence, the slave IED_H
can carry out its sampling in advance on its discretion because the slave IED_H can vary its
sampling interval with its own clock. As a result, the slave IED_H move its sampling time in
advance based on the ∆T calculated with equation (2.36-1); and the ∆T of the master IED_G
can be close to zero. The slave IED_H can of course reduce its sampling time with equation
(2.36-1).

(𝑇𝐹 − 𝑇𝑀 ) + (𝑇𝑑1 − 𝑇𝑑2 )


∆T = (2.36-2)
2

Tdd = Td1 − Td2 (2.36-3)

The delay difference (Tdd) between sending and receiving is determined with Equation
(2.36-2); you should set the difference (Tdd) as zero in all the IEDs when the upstream and the
downstream are carried out with the same route. On the other hand, suppose the route
between the upstream and the downstream is divided and their propagation times are different,
you are required that the values of Tdd in all the IEDs are identical. Note that the Tdd should
be less than 6000µs (6ms). When the user wishes to set Tdd for the IED channel#1, use setting
[CH1_TCDT]. Likewise, the settings of other channels are treated as same to the channel#1
setting.

When three IEDs are operated on lines, their communications are linked as shown in
Figure 2.36-8. When IED_G is set as the master seen from Figure 2.36-3, the synchronization
control is performed between the master IED_G and the slave IED_H; likewise, the
synchronization control is performed between the master IED_G and the slave IED_R. The
slave IED_H and the slave IED_R both carry out the follow-up control with their channel#2.
Terminal G Terminal H

CH1 CH1
IED G IED H
CH2 CH2

Master Slave

CH1 CH2

IED R Slave

Terminal R
Figure 2.36-8 Communication link in three terminal lines

GRL200 (Soft 033 & 037)


- 497 -
6F2S1914 (0.37)

(iii) Sampling address synchronization


Once the synchronization between IEDs is established, all the IEDs start sampling address
synchronization function. This principle is shown in Figure 1.1-8; and this function is to make
symmetrical sampling addresses in the eniter IEDs. Keep in mind here that the sampling is
synchronized in the entire IEDs.

In Figure 2.36-9, the slave IED_H sends a timing reference signal at point (1). The master
IED_G receives this signal at point (2). You can find that the master IED_G replies this signal
at point (3). Finally, at point (4), this signal reverts to the slave IED_H again. When the δ is
placed in Figure 2.36-9, the following equation is obtained with the Td1, the Td2, and the TM:

To − δ = Td1 + Td2 (2.36-4)

The δ is delivered with the T and the TM as follows:

δ = T − TM (2.36-5)

Substituting Equation (2.36-5) and Equation (2.36-3) for Equation (2.36-4) yields

To − (T − Tm ) Tdd
Td1 = + (2.36-6)
2 2

The Td1 calculated is distributed into the T and the TM, as can be seen from Figure
2.36-9. The mantissa is truncated and the quotient is expressed as an integer. If the integer is
set to “P”, the reception at the slave IED_H of the signal sent from the master IED_G occurs
at P sampling intervals from the transmission. Accordingly, by performing control so that the
sampling address of the slave IED_H equals integer P when the sampling address is 0 signal
is received from the master IED_G, the sampling address of the slave IED_H can be made the
same as the master IED_G.

GRL200 (Soft 033 & 037)


- 498 -
6F2S1914 (0.37)

(2) IED_G
T
receives the
signal.
TM (3) IED_G replay to IED_H with the signal received.
Master
T IED_G t
T

Slave
IED_H t
TF
Td1 Td2
(4) IED_H receives its own signal.
(1) IED_H
sends a signal To
to IED_G.

Sampling timing at IED_G


Sampling timing at IED_H
A signal in downstream (IED_H to IED_G)
A signal in upstream (IED_G to IED_H)

Figure 2.36-9 Sampling address after synchronization

(iv) Delay compensation


Synchronized sampling allows compensating the differential protection calculation even if a
transmission delay exists. The compensation is shown in Figure 2.36-10.
0 1 2 3 4
IED G t

iA(0) iB(1)

iB(0) iA(1)

IED H t
0 1 2 3 4
iA(0) Sampling address number

iB(0) Differential current calculation

Figure 2.36-10 Calculation of differential current with transmission delay time

Suppose sampling synchronization is made between the IED_G and the IED_H, their
sampling timing and their sampling address is match between; and their instantaneous
current data and their sampling address are sent each other. Consequently, the IEDs between
can use instant data sampled at the same time and they can compute the differential current
irrelevant to large transmission delay.

GRL200 (Soft 033 & 037)


- 499 -
6F2S1914 (0.37)

(v) Resynchronization
Even when any of the IEDs is taken out-of-service, the other IEDs except the out-of-service
IEDs can operate the differential protection function, in which case the logic of out-of-service
detection is provided.

As for the operation of two IEDs on a line, suppose an IED is taken out-of-service, another
IED can continue to operate the differential protection function with the local current data. It
is required that another IED is neither the master nor the slave.

On the other hand, when an IED on a three-terminal line is taken out-of-service,


synchronized sampling is established between the remaining two IEDs; hence, the two IEDs
keeps operating the differential protection function.

Note: If the master IED is taken out-of-service, one of the slave IEDs takes over the
master IED synchronized sampling function and enables the differential
protection function operates between the remaining IEDs. If the slave IED is
taken out-of-service, the master and another slave IED can maintain operating
the differential protection function.

2.36.3 Topology of telecommunication


The DIF_COMM function has two topologies for telecommunication network: a peer-to-peer
connection and a star connection. The peer-to-peer connection is used in a two-terminal line
(dual mode), whereas the star connection is used where there being less than five terminals
(star mode).

(i) Dual mode


When an application is applied for a two-terminal line, the application may operate in the dual
mode between the IEDs. As illustrated in Figure 2.36-11, each IED is connected with two
bidirectional channels. The second channel provides a redundancy as a backup line with
automatic switchover, if the first channel is lost. As a result, it’s possible to continue sampling
and calculating simultaneously at each other. For the dual mode, the user should set the
scheme switch [TERM_TOPOLOGY] =2Term-Dual.

Channel 1
CH1 CH1
IED G IED H
Channel 2
CH2 CH2

Figure 2.36-11 Dual communication mode

GRL200 (Soft 033 & 037)


- 500 -
6F2S1914 (0.37)

(ii) Star mode


When a multi terminal line application is applied, the star mode is selected. As seen from
Figure 2.36-12, the IED is connected with the others with a bidirectional channel, provided
two or more IEDs exist.

When switching of channel route is occurred, and the fluctuation of channel delay is
appeared, the IED corrects the channel delay automatically. As a result, the switching does
not influence the synchronized sampling, and the IED can take sending and receiving data as
usual. When a difference exists on the communication route, the difference of channel delay
should be set and calibrated.

Bus G Bus H

IED G IED H

IED R
Bus R

Figure 2.36-12 Star communication mode (example of Three-terminal line)

2.36.4 Communication setup


(i) Setting of Channel exchange
In the case of the two-terminal line arrangement, the communication is interlinked with
channel#1 and channel#2, as shown in Figure 2.36-1. In the case of three-terminal line
agreement, the IED at terminal G is linked with the channel#1 and the channel#2 as
shown in Figure 2.36-3. Suppose the IEDs have the normal linkages, the user should set
Off for scheme switch [CHCON]. However, the user should set On for the scheme switch
[CHCON] when the change of the channels is required.

(ii) Setting in multiplexer


Scheme switches are provided so that the IED is able to connect with the multiplexer
(MUX) properly.
 Scheme switches [CH*_T.SFT] are used to synchronize the IED with MUX by
shifting the send signal by a half-bit provided the IED is placed far from the MUX.
Suppose electrical interface ITU-T G.703-1.2.3 is applied and the distance (cable
length from relay to multiplexer) is 300m or more, you should place a set of On

GRL200 (Soft 033 & 037)


- 501 -
6F2S1914 (0.37)

for the scheme swathes [CH*_T.SFT]

 Note that On should be set for the scheme switches [CH*_B.SYN] when the IED
connects to the MUX. On the other hand, the user should set OFF for the scheme
switches when the IED is linked with the MUX absent. The setting is available
for the ITU-T G703-1.2.1, 1.2.3 and optical interface (short distance: 2km class).
In the case of optical interface 30km and 80km class, this setting is neglected.

GRL200 (Soft 033 & 037)


- 502 -
6F2S1914 (0.37)

2.36.5 Setting
DIF_COMM (Function ID: 250001) at Telecommunicaiton
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Telecommunication TERM_ID 1-5 - Terminal ID 1
TERM_TOPOL 2Term / 2Term-dual /
- Topology selection 2Term
OGY 3Term
CHCON Off / On - Exchange ch1 to ch2 Off
SPCHKLVL 100 - 1000 μs SP error detection level 200
CH1 CH1_COM_WI
Normal / Wide - Normal(N=1)/Wide(N=3) Normal
DTH
CH1_T.SFT Off / On - Bit Phase shift switch Off
CH1_B.SYN Off / On - TX bit syncing mode Off
CH1_TCDT -6000 - 6000 μs Fixed TX-RX delay difference 0
CH2 CH2_COM_WI
Normal / Wide - Normal(N=1)/Wide(N=3) Normal
DTH
CH2_T.SFT Off / On - Bit Phase shift switch Off
CH2_B.SYN Off / On - TX bit syncing mode Off
CH2_TCDT -6000 - 6000 μs Fixed TX-RX delay difference 0

GRL200 (Soft 033 & 037)


- 503 -
6F2S1914 (0.37)

2.36.6 Data ID
 Signal monitoring point
DIF_COMM (Function ID: 250001)
Element ID Name Description
3201001322 CH1 DELAY CH1 communication channel delay

2201001323 CH1 DT CH1 sampling timing difference

3101101320 CH1_ACT CH1 channel active

8601101326 CH1_CF_B CH1 communication fail

8C01001321 CH1_RDY_B CH1 ready info (BIT)

3101001327 CH1_SPERR CH1 SP syncing error

3101001324 CH1_TERMN CH1 terminal number

3202001322 CH2 DELAY CH2 communication channel delay

2202001323 CH2 DT CH2 sampling timing difference

3102101320 CH2_ACT CH2 channel active

8602101326 CH2_CF_B CH2 communication fail

8C02001321 CH2_RDY_B CH2 ready info (BIT)

3102001327 CH2_SPERR CH2 SP syncing error

3102001324 CH2_TERMN CH2 terminal number

310000132F FG_OUT FG output

8C00001321 MY_RDY_B Ready info (BIT)

310000132A MY_SA Sampling address

3100011001 SYSTEM_F 50/60Hz toggle signal

3100001328 TERMDUPER Terminal number duplicate error

GRL200 (Soft 033 & 037)


- 504 -
6F2S1914 (0.37)

Communication application (COMM_APPL)


Communication channels can be switched when new configuration is introduced into the
communication network; there is a possibility that the data carried with the new configuration
is not transferred to the correct destination. Communication application (COMM_APPL)
function can assign a unique relay-address to each IED; consequently, respective IEDs can
check the received data either true or false using the relay-address.

Using the COMM_APPL function the user can send and receive an arbitrary data in a
bit. Auxiliary areas of the transmission frame are used for sending the arbitrary bit-data; they
are named “sub-communication channels”. Several relay applications requires the user to send
some data for the remote terminals; thus, the user may be required to set up the sub-
communication channels using the COMM_APPL function. The transmission frames and
others are discussed separately. (See Chapter Relay application: Transmission control
function)

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the “G&T position” referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 2.37-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
RYID Relay address ✓ ✓
Sub-channel Sub-communication channel ✓ ✓
Number of channels Maximum channel number 2 2
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 505 -
6F2S1914 (0.37)

2.37.1 Relay-address configuration


To apply the relay-address for the IED, the user should set ON for scheme switch [RYID-EN].

(i) Address configuration


The user should set relay-addresses for the respective IEDs. Figure 2.37-1 (a) shows the relay-
address number for terminals A and B; Figure 2.37-1 (c) shows for three-terminals A, B, and C
on star network. With regard to the relay-address number, 64 unique addresses (0 to 63) are
provided for the network.
Terminal A Terminal B

LOCAL_RYID =0 CH1 CH1 LOCAL_RYID =1


CH1_RYID=1 CH1_RYID=0

(a) 2 term communication (Terminal A and B)

Terminal A Terminal B

LOCAL_RYID =0 CH1 CH1 LOCAL_RYID =1


CH1_RYID=1 CH1_RYID=0
CH2_RYID=1 CH2_RYID=0
CH2 CH2

(b) Pair network / 2 term-dual communication (Terminal A and B)

Terminal A Terminal B

LOCAL_RYID =0 CH1 CH1 LOCAL_RYID =1


CH1_RYID=1 CH1_RYID=0
CH2_RYID=2 CH2_RYID=2
CH2 CH2

CH1 CH2 LOCAL_RYID =2


CH1_RYID=0
CH2_RYID=1

Terminal C
(c) Star network communication (Terminal A, B and C)
Figure 2.37-1 Example for relay addresses
ID numbering for two-terminals
For two-terminal mode (Figure 2.37-1 a), an IED at terminal A is required to set 0 for setting
[LOCAL_RYID]; the user should set 1 for both settings [CH1_RYID] and [CH2_RYID]. Another
IED at terminal B should be set 1 for setting [LOCAL_RYID]; then 0 for both settings
[CH1_RYID] and [CH2_RYID]. Do not touch the [CH*_RYID] if one of the settings need not
operate (zero (0) is set as default).

Three-terminal application
As for setting for the relay-addresses in the star network in Figure 2.37-1 (c), the user should
pick respective relay-address numbers at remote terminals; then set them for the settings
[CH1_RYID] and [CH2_RYID].

GRL200 (Soft 033 & 037)


- 506 -
6F2S1914 (0.37)

2.37.2 Sub-communication channel for 1CB arrangement


(i) Narrow (N=1) communication
Figure 2.37-2 shows the Narrow (N=1)† frame in the IEEE C37.94 standard. When Narrow is
applied, sub-communication channels are provided at bits: COM1(2bits). The use of the sub-
communication channels are not restricted, hence the user can use them for sending user-
wishing data.
a. IEEE C37.94 frame
N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

ICOM1 ICOM2 ICOM3 ICOM4 VCOM1 VCOM2 VCOM3 VCOM4 SCOM1 SCOM2 SCOM3 SCOM4 COM1 R S S S C 1
SA0 MS0 MS1 MS2 1 1 D A P P R bit
SA1 RA0 RA1 RA2 bit bit Y 1 2 C
SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

Figure 2.37-2 Sub communication channels at N=1 in C37.94 for 1CB


†Note:For the operation of the sub-communication channels, the user is required to set
Narrow for scheme switch [CH*_COM_WIDTH]. For more information, see Chapter
Relay application: Transmission control.

GRL200 (Soft 033 & 037)


- 507 -
6F2S1914 (0.37)

(ii) Wide (N=3) communication


Figure 2.37-3 shows the Wide (N=3)† frames in the IEEE C37.94 standard. When Wide is
applied, sub-communication channels are provided at bits: COM1(2bits), COM2(2bits),
COM3(2bits), COM4(2bits), and COM6(6bits). The use of the sub-communication channels are
not restricted, hence the user can use them for sending user-wishing data.
a. IEEE C37.94 frame
N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

ICOM1 ICOM2 ICOM3 ICOM4 VCOM1 VCOM2 VCOM3 VCOM4 SCOM1 SCOM2 SCOM3 SCOM4 COM1 R S S S C 1
SA0 MS0 MS1 MS2 1 1 D A P P R bit
SA1 RA0 RA1 RA2 bit bit Y 1 2 C
SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

DIF-A
DIF-B
N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC

I0 COM6 C 1
1 1 1 1 1 R bit
bit bit bit bit bit C

N=3 Header COM2 COM3 COM4 COM5‡ CRC

COM2 (1 – 8) COM3 (1 – 8) COM4 (1 – 8) COM5 (1 –6)


1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
CRC
bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit

COM2 (9 – 16) COM3 (9 – 16) COM4 (9 – 16)

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit

Figure 2.37-3 Sub communication channels at N=1,2, and 3† in C37.94 for 1CB
†Note:Set Wide for scheme switch [CH*_COM_WIDTH]. For more information, see
Chapter Relay application: Transmission control.
‡Note:Three bits in the COM2 (1–3) are pre-assigned for sending signals “CBDS-A, -B,-
C”.

GRL200 (Soft 033 & 037)


- 508 -
6F2S1914 (0.37)

2.37.3 Sub-communication channel for 1.5CB arrangement


(i) Narrow (N=1) communication
Figure 2.37-4 shows the Narrow (N=1)† frame in the IEEE C37.94 standard. When Narrow is
applied, sub-communication channels are provided at bits: COM1(2bits).
a. IEEE C37.94 frame
N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

ICOM1 ICOM2 ICOM3 ICOM4 VCOM1 VCOM2 VCOM3 VCOM4 SCOM1 SCOM2 SCOM3 SCOM4 COM1 R S S S C 1
SA0 MS0 MS1 MS2 1 1 D A P P R bit
SA1 RA0 RA1 RA2 bit bit Y 1 2 C
SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

Figure 2.37-4 Sub communication channels at N=1 in C37.94† for 1.5CB


†Note:Set Narrow for scheme switch [CH*_COM_WIDTH].

GRL200 (Soft 033 & 037)


- 509 -
6F2S1914 (0.37)

(ii) Wide (N=3) communication


Figure 2.37-5 shows the Wide (N=3)† frames in the IEEE C37.94 standard. When Wide is
applied, sub-communication channels are provided at bits: COM1(2bits), COM2(2bits),
COM3(2bits), COM4(2bits), and COM6(6bits).

a. IEEE C37.94 frame


N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

ICOM1 ICOM2 ICOM3 ICOM4 VCOM1 VCOM2 VCOM3 VCOM4 SCOM1 SCOM2 SCOM3 SCOM4 COM1 R S S S C 1
SA0 MS0 MS1 MS2 1 1 D A P P R bit
SA1 RA0 RA1 RA2 bit bit Y 1 2 C
SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC

I0 COM6 C 1
1 1 1 1 1 R bit
bit bit bit bit bit C

N=3 Header COM2 Ia3 COM3 Ib3 COM4 Ic3 COM5 CRC

COM2 COM3 COM4 COM5


1 1 1 1 1 1 1 1 1 1 1 1
CRC
bit bit bit bit bit bit bit bit bit bit bit bit

Figure 2.37-5 Sub communication channels at N=1,2, and 3 in C37.94 for 1.5CB
†Note:Set Wide for scheme switch [CH*_COM_WIDTH]. For more information, see
Chapter Relay application: Transmission control.
‡Note:Three bits in the COM5 (1–3) are pre-assigned for sending signals “CBDS-A,-B,-
C”. Other three bits in the COM5 (4–6) are pre-assigned for sending signals “DIF-
A, -B,-C”.

2.37.4 Integral communication bits


The user can send integral communion data (ICOM1 to 4) by using the area of the ‘I0‘ when
the ‘I0‘ is not required for the relay operation. To send the integral communication, the user is
required to set On for the scheme switch [INTCOM]. Note that this scheme switch does not
have meaning when sending zero-sequence current data is requisite in a function such as zero-
sequence current differential protection (DIFGL).

GRL200 (Soft 033 & 037)


- 510 -
6F2S1914 (0.37)

2.37.5 Communication bits for OSTV


When the function ‘Out of step tripping by voltage (OSTV)’ operates, the area of the ‘V0’ is used
for the communication for the OSTV function in place of sending the zero-sequence voltage.
For more information about the OSTV function, see Chapter Relay application: Out of step
tripping by voltage.

2.37.6 Usage of sub-communication channel


Figure 2.37-6 shows the connection and monitoring points in the COM3_1bit to COM3_8bit of
Wide (N=3) communication. For example, when the user wishes to send a bit-signal using the
COM3_1 sub-channel, the user should connect the signal with PLC connection point “COM3-
1_S”. On the other hand, when the user wishes to retrieve a bit-signal from the COM3_1 sub-
channel of the remote terminal-1, the user should use PLC monitoring point “COM3-1_R1”.
With regard to the reception from the remote terminal-2, other PLC monitoring points are
provided. Entire PLC connection points and monitoring points for the sub-communication
channels are shown later.

a. PLC connection points


800214EBB0 COM3-1_S

810214EBB1 COM3-2_S

820214EBB2 COM3-3_S

830214EBB3 COM3-4_S

840214EBB4 COM3-5_S

850214EBB5 COM3-6_S

860214EBB6 COM3-7_S

870214EBB7 COM3-8_S

b. PLC monitoring points c. PLC monitoring


as to the reception COM3 (8bits) points as to the COM3 (8bits)
from remote terminal 1 1 2 3 4 5 6 7 8 reception from 1 2 3 4 5 6 7 8
remote terminal 2

8710051CF8 8710071C91
COM3-8-R1 COM3-8-R2
8610051CF7 8610071C90
COM3-7-R1 COM3-7-R2
8510051CF6 8510071C8F
COM3-6-R1 COM3-6-R2
8410051CF5 8410071C8E
COM3-5-R1 COM3-5-R2

8310051CF4 8310071C8D
COM3-4-R1 COM3-4-R2
8210051CF3 8210071C8C
COM3-3-R1 COM3-3-R2
8110051CF3 8110071C8AB
COM3-2-R1 COM3-2-R2
8010051CF2 8010071C8A
COM3-1-R1 COM3-1-R2

Figure 2.37-6 Connection and monitoring points for COM3 (1 to 8 bits)

2.37.7 Setting of open terminal detection


The open terminal detection (OTD) function is provided and a set of Off is placed for scheme
switch [OTD] as a default.

GRL200 (Soft 033 & 037)


- 511 -
6F2S1914 (0.37)

2.37.8 Communication test


(i) Local test (Local-test)
When setting [Local-test]=On, ‘1’ is set for Local test bit of SCOM4 frame so that zero-ampere
control is executed at the remote end. The zero-ampere control is the one of test functions that
a local IED can treat the remote current data as zero.
a. IEEE C37.94 frame
N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

SCOM1 SCOM2 SCOM3 SCOM4


SA0 MS0 MS1 MS2
SA1 RA0 RA1 RA2
SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

Figure 2.37-7 Location of local test bit

For example, during the test, suppose that setting [Local-test]=Off (as a default condition);
and CB and DSs are open at the local end. Remote CB can be tripped by the remote IED, if
currents are injected at the local IED while the communication is established between IEDs.
That is, the user needs to set [Local-test]=On for the test. Note that Test LED is lit while the
setting is On.

(ii) Local loop test (Loop-test)


Suppose that GRL200s at local and remote ends are connected with TX and RX fiber optical
cables. If setting [Loop-test]=On, the user can have loop-back test at the local IED by disabling
sampling synchronization supervision function. Note other supervision functions are not
disabled, but there are following limitations during the test.
 Sensitivity of DIF and DIFG elements becomes double. (If the injection of test current at
one terminal is 1A, the differential current Id becomes 2A.)
 “Test LED” is On (“In service LED” is Off.)

(iii) Open test (OPEN 1/OPEN 2)


If communication channels between IEDs should not be connected for testing, the user can cut
the channel when On is set setting [OPEN *]. For example, when setting [OPEN 1]=On, the
communication channel#1 will be cut at the local end. The default setting is Off.

GRL200 (Soft 033 & 037)


- 512 -
6F2S1914 (0.37)

2.37.9 Setting
COMM_APPL(Function ID: 4A9001) at Telecommunication
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Telecommunicaion OTD Off / On - Open-terminal-detection function enable Off
INTCOM Off / On - Integral communication enable On
MSCHK-EN Off / On - master and slave check Switch Off
Relay RYID-EN Off / On - relay ID check Switch Off
LOCAL_RYID 0 - 63 - Local RYID setting for RYID SV 0
CH1_RYID 0 - 63 - ch1 RYID setting for RYID SV 0

Test tool (Function ID: 4A9001)


Range Default
Items Unit Contents Note
1A rating 5A rating 1A 5A
Function test Local-Test Off / On – Local Test Switch Off
Loop-Test Off / On – Switch for external Loop test Off
Open 1 Off / On – Switch for CH1 Open Test Off

GRL200 (Soft 033 & 037)


- 513 -
6F2S1914 (0.37)

2.37.10 Data ID
 Signal monitoring point
COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8B30041B67 CANCEL CODE_R1

8B30051B67 CANCEL CODE_R2

8B30061B67 CANCEL CODE_R3

8B30071B67 CANCEL CODE_R4

8020001BB0 CB1 CLOSE COMMAND

8120001BB1 CB2 CLOSE COMMAND

8010051CF0 COM1-1_R1 Transmission On/Off signal to receive from remote-1

8010071C78 COM1-1_R2 Transmission On/Off signal to receive from remote-2

8110051CF1 COM1-2_R1 Transmission On/Off signal to receive from remote-1

8110071C79 COM1-2_R2 Transmission On/Off signal to receive from remote-2

8010051CF2 COM2-1_R1 Transmission On/Off signal to receive from remote-1

8010071C7A COM2-1_R2 Transmission On/Off signal to receive from remote-2

8110051CF3 COM2-2_R1 Transmission On/Off signal to receive from remote-1

8110071C7B COM2-2_R2 Transmission On/Off signal to receive from remote-2

8210051CF4 COM2-3_R1 Transmission On/Off signal to receive from remote-1

8210071C7C COM2-3_R2 Transmission On/Off signal to receive from remote-2

8310051CF5 COM2-4_R1 Transmission On/Off signal to receive from remote-1

8310071C7D COM2-4_R2 Transmission On/Off signal to receive from remote-2

8410051CF6 COM2-5_R1 Transmission On/Off signal to receive from remote-1

8410071C7E COM2-5_R2 Transmission On/Off signal to receive from remote-2

8510051CF7 COM2-6_R1 Transmission On/Off signal to receive from remote-1

8510071C7F COM2-6_R2 Transmission On/Off signal to receive from remote-2

8610051CF8 COM2-7_R1 Transmission On/Off signal to receive from remote-1

8610071C80 COM2-7_R2 Transmission On/Off signal to receive from remote-2

8710051CF9 COM2-8_R1 Transmission On/Off signal to receive from remote-1

8710071C81 COM2-8_R2 Transmission On/Off signal to receive from remote-2

8810051CFA COM2-9_R1 Transmission On/Off signal to receive from remote-1

8810071C82 COM2-9_R2 Transmission On/Off signal to receive from remote-2

8910051CFB COM2-10_R1 Transmission On/Off signal to receive from remote-1

8910071C83 COM2-10_R2 Transmission On/Off signal to receive from remote-2

8A10051CFC COM2-11_R1 Transmission On/Off signal to receive from remote-1

8A10071C84 COM2-11_R2 Transmission On/Off signal to receive from remote-2

8B10051CFD COM2-12_R1 Transmission On/Off signal to receive from remote-1

8B10071C85 COM2-12_R2 Transmission On/Off signal to receive from remote-2

8C10051CFE COM2-13_R1 Transmission On/Off signal to receive from remote-1

8C10071C86 COM2-13_R2 Transmission On/Off signal to receive from remote-2

8D10051CFF COM2-14_R1 Transmission On/Off signal to receive from remote-1

8D10071C87 COM2-14_R2 Transmission On/Off signal to receive from remote-2

8E10061C60 COM2-15_R1 Transmission On/Off signal to receive from remote-1

8E10071C88 COM2-15_R2 Transmission On/Off signal to receive from remote-2

8F10061C61 COM2-16_R1 Transmission On/Off signal to receive from remote-1

8F10071C89 COM2-16_R2 Transmission On/Off signal to receive from remote-2

8010061C62 COM3-1_R1 Transmission On/Off signal to receive from remote-1

GRL200 (Soft 033 & 037)


- 514 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8010071C8A COM3-1_R2 Transmission On/Off signal to receive from remote-2

8110061C63 COM3-2_R1 Transmission On/Off signal to receive from remote-1

8110071C8B COM3-2_R2 Transmission On/Off signal to receive from remote-2

8210061C64 COM3-3_R1 Transmission On/Off signal to receive from remote-1

8210071C8C COM3-3_R2 Transmission On/Off signal to receive from remote-2

8310061C65 COM3-4_R1 Transmission On/Off signal to receive from remote-1

8310071C8D COM3-4_R2 Transmission On/Off signal to receive from remote-2

8410061C66 COM3-5_R1 Transmission On/Off signal to receive from remote-1

8410071C8E COM3-5_R2 Transmission On/Off signal to receive from remote-2

8510061C67 COM3-6_R1 Transmission On/Off signal to receive from remote-1

8510071C8F COM3-6_R2 Transmission On/Off signal to receive from remote-2

8610061C68 COM3-7_R1 Transmission On/Off signal to receive from remote-1

8610071C90 COM3-7_R2 Transmission On/Off signal to receive from remote-2

8710061C69 COM3-8_R1 Transmission On/Off signal to receive from remote-1

8710071C91 COM3-8_R2 Transmission On/Off signal to receive from remote-2

8810061C6A COM3-9_R1 Transmission On/Off signal to receive from remote-1

8810071C92 COM3-9_R2 Transmission On/Off signal to receive from remote-2

8910061C6B COM3-10_R1 Transmission On/Off signal to receive from remote-1

8910071C93 COM3-10_R2 Transmission On/Off signal to receive from remote-2

8A10061C6C COM3-11_R1 Transmission On/Off signal to receive from remote-1

8A10071C94 COM3-11_R2 Transmission On/Off signal to receive from remote-2

8B10061C6D COM3-12_R1 Transmission On/Off signal to receive from remote-1

8B10071C95 COM3-12_R2 Transmission On/Off signal to receive from remote-2

8C10061C6E COM3-13_R1 Transmission On/Off signal to receive from remote-1

8C10071C96 COM3-13_R2 Transmission On/Off signal to receive from remote-2

8D10061C6F COM3-14_R1 Transmission On/Off signal to receive from remote-1

8D10071C97 COM3-14_R2 Transmission On/Off signal to receive from remote-2

8E10061C70 COM3-15_R1 Transmission On/Off signal to receive from remote-1

8E10071C98 COM3-15_R2 Transmission On/Off signal to receive from remote-2

8F10061C71 COM3-16_R1 Transmission On/Off signal to receive from remote-1

8F10071C99 COM3-16_R2 Transmission On/Off signal to receive from remote-2

8010061C72 COM4-1_R1 Transmission On/Off signal to receive from remote-1

8010071C9A COM4-1_R2 Transmission On/Off signal to receive from remote-2

8110061C73 COM4-2_R1 Transmission On/Off signal to receive from remote-1

8110071C9B COM4-2_R2 Transmission On/Off signal to receive from remote-2

8210061C74 COM4-3_R1 Transmission On/Off signal to receive from remote-1

8210071C9C COM4-3_R2 Transmission On/Off signal to receive from remote-2

8310061C75 COM4-4_R1 Transmission On/Off signal to receive from remote-1

8310071C9D COM4-4_R2 Transmission On/Off signal to receive from remote-2

8410061C76 COM4-5_R1 Transmission On/Off signal to receive from remote-1

8410071C9E COM4-5_R2 Transmission On/Off signal to receive from remote-2

8510061C77 COM4-6_R1 Transmission On/Off signal to receive from remote-1

8510071C9F COM4-6_R2 Transmission On/Off signal to receive from remote-2

8610061C78 COM4-7_R1 Transmission On/Off signal to receive from remote-1

GRL200 (Soft 033 & 037)


- 515 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8610071CA0 COM4-7_R2 Transmission On/Off signal to receive from remote-2

8710061C79 COM4-8_R1 Transmission On/Off signal to receive from remote-1

8710071CA1 COM4-8_R2 Transmission On/Off signal to receive from remote-2

8810061C7A COM4-9_R1 Transmission On/Off signal to receive from remote-1

8810071CA2 COM4-9_R2 Transmission On/Off signal to receive from remote-2

8910061C7B COM4-10_R1 Transmission On/Off signal to receive from remote-1

8910071CA3 COM4-10_R2 Transmission On/Off signal to receive from remote-2

8A10061C7C COM4-11_R1 Transmission On/Off signal to receive from remote-1

8A10071CA4 COM4-11_R2 Transmission On/Off signal to receive from remote-2

8B10061C7D COM4-12_R1 Transmission On/Off signal to receive from remote-1

8B10071CA5 COM4-12_R2 Transmission On/Off signal to receive from remote-2

8C10061C7E COM4-13_R1 Transmission On/Off signal to receive from remote-1

8C10071CA6 COM4-13_R2 Transmission On/Off signal to receive from remote-2

8D10061C7F COM4-14_R1 Transmission On/Off signal to receive from remote-1

8D10071CA7 COM4-14_R2 Transmission On/Off signal to receive from remote-2

8E10061C80 COM4-15_R1 Transmission On/Off signal to receive from remote-1

8E10071CA8 COM4-15_R2 Transmission On/Off signal to receive from remote-2

8F10061C81 COM4-16_R1 Transmission On/Off signal to receive from remote-1

8F10071CA9 COM4-16_R2 Transmission On/Off signal to receive from remote-2

8010061C82 COM5-1_R1 Transmission On/Off signal to receive from remote-1

8010071CAA COM5-1_R2 Transmission On/Off signal to receive from remote-2

8110061C83 COM5-2_R1 Transmission On/Off signal to receive from remote-1

8110071CAB COM5-2_R2 Transmission On/Off signal to receive from remote-2

8210061C84 COM5-3_R1 Transmission On/Off signal to receive from remote-1

8210071CAC COM5-3_R2 Transmission On/Off signal to receive from remote-2

8310061C85 COM5-4_R1 Transmission On/Off signal to receive from remote-1

8310071CAD COM5-4_R2 Transmission On/Off signal to receive from remote-2

8410061C86 COM5-5_R1 Transmission On/Off signal to receive from remote-1

8410071CAE COM5-5_R2 Transmission On/Off signal to receive from remote-2

8510061C87 COM5-6_R1 Transmission On/Off signal to receive from remote-1

8510071CAF COM5-6_R2 Transmission On/Off signal to receive from remote-2

3140001B60 COMM.DATA FAIL

80300A1B60 COMM.DATA FAIL_R1

81300A1B61 COMM.DATA FAIL_R2

82300A1B62 COMM.DATA FAIL_R3

83300A1B63 COMM.DATA FAIL_R4

8030081B60 COMM.FAIL_R1

8130081B61 COMM.FAIL_R2

8230081B62 COMM.FAIL_R3

8330081B63 COMM.FAIL_R4

8030041B60 CRC FAIL_R1

8030051B60 CRC FAIL_R2

8030061B60 CRC FAIL_R3

8030071B60 CRC FAIL_R4

GRL200 (Soft 033 & 037)


- 516 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
3140011B60 EXECUTE-CH

8000181C60 FG_OUT FG Output for BO

8130041B61 FIXED BIT FAIL_R1

8130051B61 FIXED BIT FAIL_R2

8130061B61 FIXED BIT FAIL_R3

8130071B61 FIXED BIT FAIL_R4

8230041B62 FRAME SYNCHRO.FAIL_R1

8230051B62 FRAME SYNCHRO.FAIL_R2

8230061B62 FRAME SYNCHRO.FAIL_R3

8230071B62 FRAME SYNCHRO.FAIL_R4

8010051C60 ICOM1-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061C88 ICOM1-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051C61 ICOM1-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061C89 ICOM1-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051C62 ICOM1-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061C8A ICOM1-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051C63 ICOM1-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061C8B ICOM1-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051C64 ICOM1-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061C8C ICOM1-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051C65 ICOM1-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061C8D ICOM1-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051C66 ICOM1-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061C8E ICOM1-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051C67 ICOM1-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061C8F ICOM1-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051C68 ICOM1-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061C90 ICOM1-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051C69 ICOM1-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061C91 ICOM1-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051C6A ICOM1-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061C92 ICOM1-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051C6B ICOM1-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061C93 ICOM1-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051C6C ICOM2-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061C94 ICOM2-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051C6D ICOM2-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061C95 ICOM2-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051C6E ICOM2-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061C96 ICOM2-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051C6F ICOM2-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061C97 ICOM2-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051C70 ICOM2-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061C98 ICOM2-SA4_R2 Transmission On/Off signal to receive from remote-2

GRL200 (Soft 033 & 037)


- 517 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8510051C71 ICOM2-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061C99 ICOM2-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051C72 ICOM2-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061C9A ICOM2-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051C73 ICOM2-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061C9B ICOM2-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051C74 ICOM2-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061C9C ICOM2-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051C75 ICOM2-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061C9D ICOM2-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051C76 ICOM2-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061C9E ICOM2-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051C77 ICOM2-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061C9F ICOM2-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051C78 ICOM3-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061CA0 ICOM3-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051C79 ICOM3-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061CA1 ICOM3-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051C7A ICOM3-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061CA2 ICOM3-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051C7B ICOM3-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061CA3 ICOM3-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051C7C ICOM3-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061CA4 ICOM3-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051C7D ICOM3-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061CA5 ICOM3-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051C7E ICOM3-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061CA6 ICOM3-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051C7F ICOM3-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061CA7 ICOM3-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051C80 ICOM3-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061CA8 ICOM3-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051C81 ICOM3-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061CA9 ICOM3-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051C82 ICOM3-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061CAA ICOM3-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051C83 ICOM3-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061CAB ICOM3-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051C84 ICOM4-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061CAC ICOM4-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051C85 ICOM4-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061CAD ICOM4-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051C86 ICOM4-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061CAE ICOM4-SA2_R2 Transmission On/Off signal to receive from remote-2

GRL200 (Soft 033 & 037)


- 518 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8310051C87 ICOM4-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061CAF ICOM4-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051C88 ICOM4-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061CB0 ICOM4-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051C89 ICOM4-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061CB1 ICOM4-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051C8A ICOM4-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061CB2 ICOM4-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051C8B ICOM4-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061CB3 ICOM4-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051C8C ICOM4-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061CB4 ICOM4-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051C8D ICOM4-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061CB5 ICOM4-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051C8E ICOM4-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061CB6 ICOM4-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051C8F ICOM4-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061CB7 ICOM4-SA11_R2 Transmission On/Off signal to receive from remote-2

8030001B60 INTCONN-A1_L

8030011B60 INTCONN-A2_L

8030021B60 INTCONN-A_L

8020021BB0 INTCONN-A_R1

8020031BB0 INTCONN-A_R2

8020041BB0 INTCONN-A_R3

8020051BB0 INTCONN-A_R4

8130001B61 INTCONN-B1_L

8130011B61 INTCONN-B2_L

8130021B61 INTCONN-B_L

8120021BB1 INTCONN-B_R1

8120031BB1 INTCONN-B_R2

8120041BB1 INTCONN-B_R3

8120051BB1 INTCONN-B_R4

8230001B62 INTCONN-C1_L

8230011B62 INTCONN-C2_L

8230021B62 INTCONN-C_L

8220021BB2 INTCONN-C_R1

8220031BB2 INTCONN-C_R2

8220041BB2 INTCONN-C_R3

8220051BB2 INTCONN-C_R4

3140031B60 INTCONN_R1

3140041B60 INTCONN_R2

3140051B60 INTCONN_R3

3140061B60 INTCONN_R4

2101001A60 LOCAL_DATA_SUM_IA

GRL200 (Soft 033 & 037)


- 519 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
2101001A61 LOCAL_DATA_SUM_IB

2101001A62 LOCAL_DATA_SUM_IC

8130031B60 LOCAL_TEST=ON

8020061BB0 LOCAL_TEST_R1

8120061BB1 LOCAL_TEST_R2

8220061BB2 LOCAL_TEST_R3

8320061BB3 LOCAL_TEST_R4

3140021B60 OPEN_R

8C30041B68 READY_R1

8C30051B68 READY_R2

8C30061B68 READY_R3

8C30071B68 READY_R4

8330041B63 RECEIVED INTERRUPT_R1

8330051B63 RECEIVED INTERRUPT_R2

8330061B63 RECEIVED INTERRUPT_R3

8330071B63 RECEIVED INTERRUPT_R4

8E30041B6A RECEIVED LEVEL_R1

8E30051B6A RECEIVED LEVEL_R2

8E30061B6A RECEIVED LEVEL_R3

8E30071B6A RECEIVED LEVEL_R4

3100091C2D RELAY BLOCK 31 Relay block 31: Relay block(for each CH)

8020011BB0 REMOTE_DATA_ZERO

8730041B64 RSA SYNCHRO.FAIL_R1

8730051B64 RSA SYNCHRO.FAIL_R2

8730061B64 RSA SYNCHRO.FAIL_R3

8730071B64 RSA SYNCHRO.FAIL_R4

8E00111C34 RYBLK-AND Relay block AND

8000111C30 RYBLK-CH1 Relay block CH1

8100111C31 RYBLK-CH2 Relay block CH2

8F00111C35 RYBLK-OR Relay block OR

8930041B66 SA SYNCHRO.FAIL_R1

8930051B66 SA SYNCHRO.FAIL_R2

8930061B66 SA SYNCHRO.FAIL_R3

8930071B66 SA SYNCHRO.FAIL_R4

8010051CC0 SCOM1-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061CE8 SCOM1-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051CC1 SCOM1-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061CE9 SCOM1-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051CC2 SCOM1-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061CEA SCOM1-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051CC3 SCOM1-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061CEB SCOM1-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051CC4 SCOM1-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061CEC SCOM1-SA4_R2 Transmission On/Off signal to receive from remote-2

GRL200 (Soft 033 & 037)


- 520 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8510051CC5 SCOM1-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061CED SCOM1-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051CC6 SCOM1-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061CEE SCOM1-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051CC7 SCOM1-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061CEF SCOM1-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051CC8 SCOM1-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061CF0 SCOM1-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051CC9 SCOM1-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061CF1 SCOM1-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051CCA SCOM1-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061CF2 SCOM1-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051CCB SCOM1-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061CF3 SCOM1-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051CCC SCOM2-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061CF4 SCOM2-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051CCD SCOM2-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061CF5 SCOM2-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051CCE SCOM2-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061CF6 SCOM2-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051CCF SCOM2-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061CF7 SCOM2-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051CD0 SCOM2-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061CF8 SCOM2-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051CD1 SCOM2-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061CF9 SCOM2-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051CD2 SCOM2-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061CFA SCOM2-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051CD3 SCOM2-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061CFB SCOM2-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051CD4 SCOM2-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061CFC SCOM2-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051CD5 SCOM2-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061CFD SCOM2-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051CD6 SCOM2-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061CFE SCOM2-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051CD7 SCOM2-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061CFF SCOM2-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051CD8 SCOM3-SA0_R1 Transmission On/Off signal to receive from remote-1

8010071C60 SCOM3-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051CD9 SCOM3-SA1_R1 Transmission On/Off signal to receive from remote-1

8110071C61 SCOM3-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051CDA SCOM3-SA2_R1 Transmission On/Off signal to receive from remote-1

8210071C62 SCOM3-SA2_R2 Transmission On/Off signal to receive from remote-2

GRL200 (Soft 033 & 037)


- 521 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8310051CDB SCOM3-SA3_R1 Transmission On/Off signal to receive from remote-1

8310071C63 SCOM3-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051CDC SCOM3-SA4_R1 Transmission On/Off signal to receive from remote-1

8410071C64 SCOM3-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051CDD SCOM3-SA5_R1 Transmission On/Off signal to receive from remote-1

8510071C65 SCOM3-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051CDE SCOM3-SA6_R1 Transmission On/Off signal to receive from remote-1

8610071C66 SCOM3-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051CDF SCOM3-SA7_R1 Transmission On/Off signal to receive from remote-1

8710071C67 SCOM3-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051CE0 SCOM3-SA8_R1 Transmission On/Off signal to receive from remote-1

8810071C68 SCOM3-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051CE1 SCOM3-SA9_R1 Transmission On/Off signal to receive from remote-1

8910071C69 SCOM3-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051CE2 SCOM3-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10071C6A SCOM3-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051CE3 SCOM3-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10071C6B SCOM3-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051CE4 SCOM4-SA0_R1 Transmission On/Off signal to receive from remote-1

8010071C6C SCOM4-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051CE5 SCOM4-SA1_R1 Transmission On/Off signal to receive from remote-1

8110071C6D SCOM4-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051CE6 SCOM4-SA2_R1 Transmission On/Off signal to receive from remote-1

8210071C6E SCOM4-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051CE7 SCOM4-SA3_R1 Transmission On/Off signal to receive from remote-1

8310071C6F SCOM4-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051CE8 SCOM4-SA4_R1 Transmission On/Off signal to receive from remote-1

8410071C70 SCOM4-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051CE9 SCOM4-SA5_R1 Transmission On/Off signal to receive from remote-1

8510071C71 SCOM4-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051CEA SCOM4-SA6_R1 Transmission On/Off signal to receive from remote-1

8610071C72 SCOM4-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051CEB SCOM4-SA7_R1 Transmission On/Off signal to receive from remote-1

8710071C73 SCOM4-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051CEC SCOM4-SA8_R1 Transmission On/Off signal to receive from remote-1

8810071C74 SCOM4-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051CED SCOM4-SA9_R1 Transmission On/Off signal to receive from remote-1

8910071C75 SCOM4-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051CEE SCOM4-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10071C76 SCOM4-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051CEF SCOM4-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10071C77 SCOM4-SA11_R2 Transmission On/Off signal to receive from remote-2

8D30041B69 SENT LEVEL_R1

8D30051B69 SENT LEVEL_R2

GRL200 (Soft 033 & 037)


- 522 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8D30061B69 SENT LEVEL_R3

8D30071B69 SENT LEVEL_R4

8830041B65 SP SYNCHRO.FAIL_R1

8830051B65 SP SYNCHRO.FAIL_R2

8830061B65 SP SYNCHRO.FAIL_R3

8830071B65 SP SYNCHRO.FAIL_R4

8030091B60 SYNC.FAIL_R1

8130091B61 SYNC.FAIL_R2

8230091B62 SYNC.FAIL_R3

8330091B63 SYNC.FAIL_R4

8010051C90 VCOM1-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061CB8 VCOM1-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051C91 VCOM1-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061CB9 VCOM1-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051C92 VCOM1-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061CBA VCOM1-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051C93 VCOM1-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061CBB VCOM1-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051C94 VCOM1-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061CBC VCOM1-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051C95 VCOM1-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061CBD VCOM1-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051C96 VCOM1-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061CBE VCOM1-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051C97 VCOM1-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061CBF VCOM1-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051C98 VCOM1-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061CC0 VCOM1-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051C99 VCOM1-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061CC1 VCOM1-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051C9A VCOM1-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061CC2 VCOM1-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051C9B VCOM1-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061CC3 VCOM1-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051C9C VCOM2-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061CC4 VCOM2-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051C9D VCOM2-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061CC5 VCOM2-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051C9E VCOM2-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061CC6 VCOM2-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051C9F VCOM2-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061CC7 VCOM2-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051CA0 VCOM2-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061CC8 VCOM2-SA4_R2 Transmission On/Off signal to receive from remote-2

GRL200 (Soft 033 & 037)


- 523 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8510051CA1 VCOM2-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061CC9 VCOM2-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051CA2 VCOM2-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061CCA VCOM2-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051CA3 VCOM2-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061CCB VCOM2-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051CA4 VCOM2-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061CCC VCOM2-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051CA5 VCOM2-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061CCD VCOM2-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051CA6 VCOM2-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061CCE VCOM2-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051CA7 VCOM2-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061CCF VCOM2-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051CA8 VCOM3-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061CD0 VCOM3-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051CA9 VCOM3-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061CD1 VCOM3-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051CAA VCOM3-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061CD2 VCOM3-SA2_R2 Transmission On/Off signal to receive from remote-2

8310051CAB VCOM3-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061CD3 VCOM3-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051CAC VCOM3-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061CD4 VCOM3-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051CAD VCOM3-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061CD5 VCOM3-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051CAE VCOM3-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061CD6 VCOM3-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051CAF VCOM3-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061CD7 VCOM3-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051CB0 VCOM3-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061CD8 VCOM3-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051CB1 VCOM3-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061CD9 VCOM3-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051CB2 VCOM3-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061CDA VCOM3-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051CB3 VCOM3-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061CDB VCOM3-SA11_R2 Transmission On/Off signal to receive from remote-2

8010051CB4 VCOM4-SA0_R1 Transmission On/Off signal to receive from remote-1

8010061CDC VCOM4-SA0_R2 Transmission On/Off signal to receive from remote-2

8110051CB5 VCOM4-SA1_R1 Transmission On/Off signal to receive from remote-1

8110061CDD VCOM4-SA1_R2 Transmission On/Off signal to receive from remote-2

8210051CB6 VCOM4-SA2_R1 Transmission On/Off signal to receive from remote-1

8210061CDE VCOM4-SA2_R2 Transmission On/Off signal to receive from remote-2

GRL200 (Soft 033 & 037)


- 524 -
6F2S1914 (0.37)

 Signal monitoring point


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
8310051CB7 VCOM4-SA3_R1 Transmission On/Off signal to receive from remote-1

8310061CDF VCOM4-SA3_R2 Transmission On/Off signal to receive from remote-2

8410051CB8 VCOM4-SA4_R1 Transmission On/Off signal to receive from remote-1

8410061CE0 VCOM4-SA4_R2 Transmission On/Off signal to receive from remote-2

8510051CB9 VCOM4-SA5_R1 Transmission On/Off signal to receive from remote-1

8510061CE1 VCOM4-SA5_R2 Transmission On/Off signal to receive from remote-2

8610051CBA VCOM4-SA6_R1 Transmission On/Off signal to receive from remote-1

8610061CE2 VCOM4-SA6_R2 Transmission On/Off signal to receive from remote-2

8710051CBB VCOM4-SA7_R1 Transmission On/Off signal to receive from remote-1

8710061CE3 VCOM4-SA7_R2 Transmission On/Off signal to receive from remote-2

8810051CBC VCOM4-SA8_R1 Transmission On/Off signal to receive from remote-1

8810061CE4 VCOM4-SA8_R2 Transmission On/Off signal to receive from remote-2

8910051CBD VCOM4-SA9_R1 Transmission On/Off signal to receive from remote-1

8910061CE5 VCOM4-SA9_R2 Transmission On/Off signal to receive from remote-2

8A10051CBE VCOM4-SA10_R1 Transmission On/Off signal to receive from remote-1

8A10061CE6 VCOM4-SA10_R2 Transmission On/Off signal to receive from remote-2

8B10051CBF VCOM4-SA11_R1 Transmission On/Off signal to receive from remote-1

8B10061CE7 VCOM4-SA11_R2 Transmission On/Off signal to receive from remote-2

31000A1C2E ZERO CTRL 31 Zero ctrl 31: Zero control(for each CH)

GRL200 (Soft 033 & 037)


- 525 -
6F2S1914 (0.37)

 Connection point in PLC logic


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
800220EC60 APPL-CTSELECT Selection of CT

800217EBB0 CB1 CLOSE COMMAND

810217EBB1 CB2 CLOSE COMMAND

800212EBB0 COM1-1_S Transmission On/Off signal to send

810212EBB1 COM1-2_S Transmission On/Off signal to send

800213EBB0 COM2-1_S Transmission On/Off signal to send

810213EBB1 COM2-2_S Transmission On/Off signal to send

820213EBB2 COM2-3_S Transmission On/Off signal to send

830213EBB3 COM2-4_S Transmission On/Off signal to send

840213EBB4 COM2-5_S Transmission On/Off signal to send

850213EBB5 COM2-6_S Transmission On/Off signal to send

860213EBB6 COM2-7_S Transmission On/Off signal to send

870213EBB7 COM2-8_S Transmission On/Off signal to send

880213EBB8 COM2-9_S Transmission On/Off signal to send

890213EBB9 COM2-10_S Transmission On/Off signal to send

8A0213EBBA COM2-11_S Transmission On/Off signal to send

8B0213EBBB COM2-12_S Transmission On/Off signal to send

8C0213EBBC COM2-13_S Transmission On/Off signal to send

8D0213EBBD COM2-14_S Transmission On/Off signal to send

8E0213EBBE COM2-15_S Transmission On/Off signal to send

8F0213EBBF COM2-16_S Transmission On/Off signal to send

800214EBB0 COM3-1_S Transmission On/Off signal to send

810214EBB1 COM3-2_S Transmission On/Off signal to send

820214EBB2 COM3-3_S Transmission On/Off signal to send

830214EBB3 COM3-4_S Transmission On/Off signal to send

840214EBB4 COM3-5_S Transmission On/Off signal to send

850214EBB5 COM3-6_S Transmission On/Off signal to send

860214EBB6 COM3-7_S Transmission On/Off signal to send

870214EBB7 COM3-8_S Transmission On/Off signal to send

880214EBB8 COM3-9_S Transmission On/Off signal to send

890214EBB9 COM3-10_S Transmission On/Off signal to send

8A0214EBBA COM3-11_S Transmission On/Off signal to send

8B0214EBBB COM3-12_S Transmission On/Off signal to send

8C0214EBBC COM3-13_S Transmission On/Off signal to send

8D0214EBBD COM3-14_S Transmission On/Off signal to send

8E0214EBBE COM3-15_S Transmission On/Off signal to send

8F0214EBBF COM3-16_S Transmission On/Off signal to send

800215EBB0 COM4-1_S Transmission On/Off signal to send

810215EBB1 COM4-2_S Transmission On/Off signal to send

820215EBB2 COM4-3_S Transmission On/Off signal to send

830215EBB3 COM4-4_S Transmission On/Off signal to send

840215EBB4 COM4-5_S Transmission On/Off signal to send

850215EBB5 COM4-6_S Transmission On/Off signal to send

860215EBB6 COM4-7_S Transmission On/Off signal to send

GRL200 (Soft 033 & 037)


- 526 -
6F2S1914 (0.37)

 Connection point in PLC logic


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
870215EBB7 COM4-8_S Transmission On/Off signal to send

880215EBB8 COM4-9_S Transmission On/Off signal to send

890215EBB9 COM4-10_S Transmission On/Off signal to send

8A0215EBBA COM4-11_S Transmission On/Off signal to send

8B0215EBBB COM4-12_S Transmission On/Off signal to send

8C0215EBBC COM4-13_S Transmission On/Off signal to send

8D0215EBBD COM4-14_S Transmission On/Off signal to send

8E0215EBBE COM4-15_S Transmission On/Off signal to send

8F0215EBBF COM4-16_S Transmission On/Off signal to send

800216EBB0 COM5-1_S Transmission On/Off signal to send

810216EBB1 COM5-2_S Transmission On/Off signal to send

820216EBB2 COM5-3_S Transmission On/Off signal to send

830216EBB3 COM5-4_S Transmission On/Off signal to send

840216EBB4 COM5-5_S Transmission On/Off signal to send

850216EBB5 COM5-6_S Transmission On/Off signal to send

800200EBB0 ICOM1-SA0_S Transmission On/Off signal to send

810200EBB1 ICOM1-SA1_S Transmission On/Off signal to send

820200EBB2 ICOM1-SA2_S Transmission On/Off signal to send

830200EBB3 ICOM1-SA3_S Transmission On/Off signal to send

840200EBB4 ICOM1-SA4_S Transmission On/Off signal to send

850200EBB5 ICOM1-SA5_S Transmission On/Off signal to send

860200EBB6 ICOM1-SA6_S Transmission On/Off signal to send

870200EBB7 ICOM1-SA7_S Transmission On/Off signal to send

880200EBB8 ICOM1-SA8_S Transmission On/Off signal to send

890200EBB9 ICOM1-SA9_S Transmission On/Off signal to send

8A0200EBBA ICOM1-SA10_S Transmission On/Off signal to send

8B0200EBBB ICOM1-SA11_S Transmission On/Off signal to send

800201EBB0 ICOM2-SA0_S Transmission On/Off signal to send

810201EBB1 ICOM2-SA1_S Transmission On/Off signal to send

820201EBB2 ICOM2-SA2_S Transmission On/Off signal to send

830201EBB3 ICOM2-SA3_S Transmission On/Off signal to send

840201EBB4 ICOM2-SA4_S Transmission On/Off signal to send

850201EBB5 ICOM2-SA5_S Transmission On/Off signal to send

860201EBB6 ICOM2-SA6_S Transmission On/Off signal to send

870201EBB7 ICOM2-SA7_S Transmission On/Off signal to send

880201EBB8 ICOM2-SA8_S Transmission On/Off signal to send

890201EBB9 ICOM2-SA9_S Transmission On/Off signal to send

8A0201EBBA ICOM2-SA10_S Transmission On/Off signal to send

8B0201EBBB ICOM2-SA11_S Transmission On/Off signal to send

800202EBB0 ICOM3-SA0_S Transmission On/Off signal to send

810202EBB1 ICOM3-SA1_S Transmission On/Off signal to send

820202EBB2 ICOM3-SA2_S Transmission On/Off signal to send

830202EBB3 ICOM3-SA3_S Transmission On/Off signal to send

840202EBB4 ICOM3-SA4_S Transmission On/Off signal to send

GRL200 (Soft 033 & 037)


- 527 -
6F2S1914 (0.37)

 Connection point in PLC logic


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
850202EBB5 ICOM3-SA5_S Transmission On/Off signal to send

860202EBB6 ICOM3-SA6_S Transmission On/Off signal to send

870202EBB7 ICOM3-SA7_S Transmission On/Off signal to send

880202EBB8 ICOM3-SA8_S Transmission On/Off signal to send

890202EBB9 ICOM3-SA9_S Transmission On/Off signal to send

8A0202EBBA ICOM3-SA10_S Transmission On/Off signal to send

8B0202EBBB ICOM3-SA11_S Transmission On/Off signal to send

800203EBB0 ICOM4-SA0_S Transmission On/Off signal to send

810203EBB1 ICOM4-SA1_S Transmission On/Off signal to send

820203EBB2 ICOM4-SA2_S Transmission On/Off signal to send

830203EBB3 ICOM4-SA3_S Transmission On/Off signal to send

840203EBB4 ICOM4-SA4_S Transmission On/Off signal to send

850203EBB5 ICOM4-SA5_S Transmission On/Off signal to send

860203EBB6 ICOM4-SA6_S Transmission On/Off signal to send

870203EBB7 ICOM4-SA7_S Transmission On/Off signal to send

880203EBB8 ICOM4-SA8_S Transmission On/Off signal to send

890203EBB9 ICOM4-SA9_S Transmission On/Off signal to send

8A0203EBBA ICOM4-SA10_S Transmission On/Off signal to send

8B0203EBBB ICOM4-SA11_S Transmission On/Off signal to send

800219EBB0 INTCONN-A_R1

80021AEBB0 INTCONN-A_R2

80021BEBB0 INTCONN-A_R3

80021CEBB0 INTCONN-A_R4

810219EBB1 INTCONN-B_R1

81021AEBB1 INTCONN-B_R2

81021BEBB1 INTCONN-B_R3

81021CEBB1 INTCONN-B_R4

820219EBB2 INTCONN-C_R1

82021AEBB2 INTCONN-C_R2

82021BEBB2 INTCONN-C_R3

82021CEBB2 INTCONN-C_R4

80021DEBB0 LOCAL_TEST_R1

81021DEBB1 LOCAL_TEST_R2

82021DEBB2 LOCAL_TEST_R3

83021DEBB3 LOCAL_TEST_R4

800218EBB0 REMOTE_DATA_ZERO

800208EBB0 SCOM1-SA0_S Transmission On/Off signal to send

810208EBB1 SCOM1-SA1_S Transmission On/Off signal to send

820208EBB2 SCOM1-SA2_S Transmission On/Off signal to send

830208EBB3 SCOM1-SA3_S Transmission On/Off signal to send

840208EBB4 SCOM1-SA4_S Transmission On/Off signal to send

850208EBB5 SCOM1-SA5_S Transmission On/Off signal to send

860208EBB6 SCOM1-SA6_S Transmission On/Off signal to send

870208EBB7 SCOM1-SA7_S Transmission On/Off signal to send

GRL200 (Soft 033 & 037)


- 528 -
6F2S1914 (0.37)

 Connection point in PLC logic


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
880208EBB8 SCOM1-SA8_S Transmission On/Off signal to send

890208EBB9 SCOM1-SA9_S Transmission On/Off signal to send

8A0208EBBA SCOM1-SA10_S Transmission On/Off signal to send

8B0208EBBB SCOM1-SA11_S Transmission On/Off signal to send

800209EBB0 SCOM2-SA0_S Transmission On/Off signal to send

810209EBB1 SCOM2-SA1_S Transmission On/Off signal to send

820209EBB2 SCOM2-SA2_S Transmission On/Off signal to send

830209EBB3 SCOM2-SA3_S Transmission On/Off signal to send

840209EBB4 SCOM2-SA4_S Transmission On/Off signal to send

850209EBB5 SCOM2-SA5_S Transmission On/Off signal to send

860209EBB6 SCOM2-SA6_S Transmission On/Off signal to send

870209EBB7 SCOM2-SA7_S Transmission On/Off signal to send

880209EBB8 SCOM2-SA8_S Transmission On/Off signal to send

890209EBB9 SCOM2-SA9_S Transmission On/Off signal to send

8A0209EBBA SCOM2-SA10_S Transmission On/Off signal to send

8B0209EBBB SCOM2-SA11_S Transmission On/Off signal to send

800210EBB0 SCOM3-SA0_S Transmission On/Off signal to send

810210EBB1 SCOM3-SA1_S Transmission On/Off signal to send

820210EBB2 SCOM3-SA2_S Transmission On/Off signal to send

830210EBB3 SCOM3-SA3_S Transmission On/Off signal to send

840210EBB4 SCOM3-SA4_S Transmission On/Off signal to send

850210EBB5 SCOM3-SA5_S Transmission On/Off signal to send

860210EBB6 SCOM3-SA6_S Transmission On/Off signal to send

870210EBB7 SCOM3-SA7_S Transmission On/Off signal to send

880210EBB8 SCOM3-SA8_S Transmission On/Off signal to send

890210EBB9 SCOM3-SA9_S Transmission On/Off signal to send

8A0210EBBA SCOM3-SA10_S Transmission On/Off signal to send

8B0210EBBB SCOM3-SA11_S Transmission On/Off signal to send

800211EBB0 SCOM4-SA0_S Transmission On/Off signal to send

810211EBB1 SCOM4-SA1_S Transmission On/Off signal to send

820211EBB2 SCOM4-SA2_S Transmission On/Off signal to send

830211EBB3 SCOM4-SA3_S Transmission On/Off signal to send

840211EBB4 SCOM4-SA4_S Transmission On/Off signal to send

850211EBB5 SCOM4-SA5_S Transmission On/Off signal to send

860211EBB6 SCOM4-SA6_S Transmission On/Off signal to send

870211EBB7 SCOM4-SA7_S Transmission On/Off signal to send

880211EBB8 SCOM4-SA8_S Transmission On/Off signal to send

890211EBB9 SCOM4-SA9_S Transmission On/Off signal to send

8A0211EBBA SCOM4-SA10_S Transmission On/Off signal to send

8B0211EBBB SCOM4-SA11_S Transmission On/Off signal to send

800204EBB0 VCOM1-SA0_S Transmission On/Off signal to send

810204EBB1 VCOM1-SA1_S Transmission On/Off signal to send

820204EBB2 VCOM1-SA2_S Transmission On/Off signal to send

830204EBB3 VCOM1-SA3_S Transmission On/Off signal to send

GRL200 (Soft 033 & 037)


- 529 -
6F2S1914 (0.37)

 Connection point in PLC logic


COMM_APPL(Function ID: 4A9001)
Element ID Name Description
840204EBB4 VCOM1-SA4_S Transmission On/Off signal to send

850204EBB5 VCOM1-SA5_S Transmission On/Off signal to send

860204EBB6 VCOM1-SA6_S Transmission On/Off signal to send

870204EBB7 VCOM1-SA7_S Transmission On/Off signal to send

880204EBB8 VCOM1-SA8_S Transmission On/Off signal to send

890204EBB9 VCOM1-SA9_S Transmission On/Off signal to send

8A0204EBBA VCOM1-SA10_S Transmission On/Off signal to send

8B0204EBBB VCOM1-SA11_S Transmission On/Off signal to send

800205EBB0 VCOM2-SA0_S Transmission On/Off signal to send

810205EBB1 VCOM2-SA1_S Transmission On/Off signal to send

820205EBB2 VCOM2-SA2_S Transmission On/Off signal to send

830205EBB3 VCOM2-SA3_S Transmission On/Off signal to send

840205EBB4 VCOM2-SA4_S Transmission On/Off signal to send

850205EBB5 VCOM2-SA5_S Transmission On/Off signal to send

860205EBB6 VCOM2-SA6_S Transmission On/Off signal to send

870205EBB7 VCOM2-SA7_S Transmission On/Off signal to send

880205EBB8 VCOM2-SA8_S Transmission On/Off signal to send

890205EBB9 VCOM2-SA9_S Transmission On/Off signal to send

8A0205EBBA VCOM2-SA10_S Transmission On/Off signal to send

8B0205EBBB VCOM2-SA11_S Transmission On/Off signal to send

800206EBB0 VCOM3-SA0_S Transmission On/Off signal to send

810206EBB1 VCOM3-SA1_S Transmission On/Off signal to send

820206EBB2 VCOM3-SA2_S Transmission On/Off signal to send

830206EBB3 VCOM3-SA3_S Transmission On/Off signal to send

840206EBB4 VCOM3-SA4_S Transmission On/Off signal to send

850206EBB5 VCOM3-SA5_S Transmission On/Off signal to send

860206EBB6 VCOM3-SA6_S Transmission On/Off signal to send

870206EBB7 VCOM3-SA7_S Transmission On/Off signal to send

880206EBB8 VCOM3-SA8_S Transmission On/Off signal to send

890206EBB9 VCOM3-SA9_S Transmission On/Off signal to send

8A0206EBBA VCOM3-SA10_S Transmission On/Off signal to send

8B0206EBBB VCOM3-SA11_S Transmission On/Off signal to send

800207EBB0 VCOM4-SA0_S Transmission On/Off signal to send

810207EBB1 VCOM4-SA1_S Transmission On/Off signal to send

820207EBB2 VCOM4-SA2_S Transmission On/Off signal to send

830207EBB3 VCOM4-SA3_S Transmission On/Off signal to send

840207EBB4 VCOM4-SA4_S Transmission On/Off signal to send

850207EBB5 VCOM4-SA5_S Transmission On/Off signal to send

860207EBB6 VCOM4-SA6_S Transmission On/Off signal to send

870207EBB7 VCOM4-SA7_S Transmission On/Off signal to send

880207EBB8 VCOM4-SA8_S Transmission On/Off signal to send

890207EBB9 VCOM4-SA9_S Transmission On/Off signal to send

GRL200 (Soft 033 & 037)


- 530 -
6F2S1914 (0.37)

Protection common (PROT_COMMON)


The contact states of the circuit breaker (CB) and the disconnector (DS) provided are grouped
in the protection common function (PROT_COMMON) and are used in a number of relay
applications to decide conditions. The PROT_COMMON function also examines whether a line
is dead (de-energizing), as the PROT_COMMON has an under-voltage detection (UV) relay.
The PROT_COMMON function is operated as the common function.

─────────────────────────────────────────────────────────────────
Note: The PROT_COMMON function is feasible in entire models, which can be enumerated
in the IED ordering number. For more information, see Appendix: Ordering.
Table 2.38-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
feature
33 37
PROT_COMM Protection common ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 531 -
6F2S1914 (0.37)

2.38.1 Selection of breaker system


A single breaker arrangement (1CB) is applied and the protection function is required to
operate in the 1CB, the user should set 1CB for the scheme switch [CB-System]. When a single-
and-a-half breaker arrangement system (1.5CB) is applied, the user should set 2CB for the
scheme switch. (2.84.8)

2.38.2 Decision of CB open/close status


Circuit-breaker auxiliary-contact is used to state the CB status; a normal-open contact (N/O)
and a normal-close contact (N/C) can be furnished in the CB. Thus, as to the phase-A contact
of the CB, signals “CB1-A_NO_CONT” and “CB1-A_NC_CONT” can be used to represent the
CB status in phase-A (i.e., tripped or closed in phase-A). The PROT_COMM function can decide
the CB status using the both signals; the decision generated will be provided for other
protection functions so that the IED can operate in accordance with the CB status.

(i) Signal option


As the CB auxiliary-contacts (N/O and/or N/C) may generate the signals, the user should set
the rule for the decision. When the N/O signal is generated but the N/C signal is not generated,
set NO for the scheme switch [CB1-Contact] so that the PROT_COMMON function can decide
the CB state using only the N/O. Conversely, the decision should be made with only the N/C,
NC is set for this scheme switch. When both N/O and the N/C used, set Both for the scheme
switch [CB1-Contact]†.

†Note:When the IED operates for the 1.5CB arrangement (i.e., two CBs are connected
with the IED), the user should set the scheme switches [CB1-Contact] and [CB2-
Contact] both.

(ii) Contact supervision


Table 2.38-2 exemplifies the rules between the CB main-contact and the CB auxiliary-contact.
Given that the main-contact is open, the N/O is open and the N/C is closed; however if the both
are open when the main contact is open, we should decide the information generated in the
PROT_COMMON is not true (say, an incorrect signal is generated). The contact supervision
can find the inconsistency in the decisions using the rule of Table 2.38-2.
Table 2.38-2 Main and Auxiliary contacts within CB
Main contact
OPEN CLOSED
N/O OPEN CLOSED
Auxiliary contacts
N/C CLOSED OPEN

The user should set On for the scheme switch [CB-SV] when the operation of the contact

GRL200 (Soft 033 & 037)


- 532 -
6F2S1914 (0.37)

supervision feature is required; set the time for the setting [TCBSV] to define the monitoring
period, which the user can have an option among 0 to 100 sec.

(iii) CB decision logic


Figure 2.38-1 shows the decision logic of the PROT_COMMON and outputs the decision state
of the CB: CB-A_CLOSE, CB-B_CLOSE, and others.

For the operation, the user should inject signals of CB states for the following PLC
connection points: ‘CB1-A NO CONT’, ‘CB1-A NC CONT’ and others. Note that a common point
is ready for the CB designed to three-phase tripping: CB1-NO CONT’ and ‘CB1-NC CONT’.

GRL200 (Soft 033 & 037)


- 533 -
6F2S1914 (0.37)

8000001BB0
8300001BBE ≥1
TCBSV
8000001B93
=1 1 t 0
8000001B87 & CB1-A_FAIL
8300001BBF ≥1
0–100S
8100001BB1
8300001BBE ≥1 TCBSV
8100001B94
8100001B88 =1 1 t 0
&
8300001BBF ≥1 CB1-B_FAIL
0–100S
8200001BB2
8300001BBE ≥1 TCBSV
t 0 8200001B95
8200001B89 =1 1
& CB1-C_FAIL
8300001BBF ≥1
0–100S 8300001B96
& ≥1 CB1-FAIL

800000EBB0 CB1-A_NO_CONT To Common of DISCAR, DEFCAR


≥1 &
8000001B73
≥1 8000001B88
≥1
800000EBB7 CB1-A_NC_CONT ≥1 1
& CB-A_CLOSE

810000EBB1 CB1-B_NO_CONT ≥1 &


8000001B74
≥1 8100001B89
≥1
810000EBB8 CB1-B_NC_CONT ≥1 1 CB-B_CLOSE
&

820000EBB2 CB1-C_NO_CONT ≥1 & 8000001B75


≥1 8200001B8A
≥1 CB-C_CLOSE
820000EBB9 CB1-C_NC_CONT ≥1 1
& 8000001B76
&
830000EBBE CB1-NO_CONT
To VTF, CTF, ZG
8000001B77 8300001B8B
830000EBBF CB1-NC_CONT 1 ≥1
CB-ALLPH_CLOSE
≥1 8000001B78
1
NO To CLP
8000001B79
NC ≥1 1 CB-ALLPH_CLOSE
Both 8800001B90
& 8000001B7A ≥1 CB-ANYPH_CLOSE
CB1-Contact
On
8400001B97
CB-SV CB2-A_FAIL CB2-A_FAIL

8400001BB3 8500001B98
CB2-B_FAIL CB2-B_FAIL
8400001B8A

8500001BB4 8600001B99
CB2-C_FAIL CB2-C_FAIL
8500001B8B
8700001B9A
8600001BB5
CB2-FAIL CB2-FAIL
8600001B8C

To ARC
840000EBB3 CB2-A_NO_CONT
CB2-A_CLOSE CB1-ALLPH_CLOSE
840000EBBA CB2-A_NC_CONT CB2-B_CLOSE CB2-ALLPH_CLOSE

CB2-C_CLOSE CB-SYSTEM=1CB

850000EBB4 CB2-B_NO_CONT CB2-ALLPH_CLOSE CB-SYSTEM=2CB

8400001B8C To TRC, CBF


850000EBBB CB2-B_NC_CONT CB2-A_OPEN & CB-A_OPEN
8500001B8D
& CB-B_OPEN
CB2-B_OPEN
860000EBB5 CB2-C_NO_CONT 8600001B8E
& CB-C_OPEN
CB2-C_OPEN
860000EBBC CB2-C_NC_CONT &
CB2-ALLPH_OPEN To Dead line
detection logic
Note: CB2 logic is similar to CB1
logic; OPEN signals are 8700001B8F
CB-ALLPH_OPEN
TRUE (1) and CLOSE
signals are FALSE (0) when
this logic is used in 1CB
system.

≥1 &
To OVG, OVN, UVP, DEFCAR
NO &
≥1 TCBLOSPH 8900001B91
NC ≥1 & ≥1 t 0 CB-LOSS_PHASE
Both 1 0.00 to 0.10s
CB2-Contact
&
CB2-CONTACT=BOTH
1CB
2CB

CB-System

Figure 2.38-1 CB decision logic with supervision feature in 1.5CB system

GRL200 (Soft 033 & 037)


- 534 -
6F2S1914 (0.37)

2.38.3 Decision of DS open/close status


The PROT_COMMON function can determine the behavior and position status of a DS. Signal
configuration and settings for the DS position status are similar to that of the CB. Note that
settings and logics cited below are just available for the DS.

(i) Signal selection


Set either NO, NC, or Both for scheme switch [DS-Contact].

(ii) Contact supervision


When Both is set for scheme switch [DS-Contact], the auxiliary switch contact state of the DS
is supervised. Set On for scheme switch [DS-SV] when contact supervision is required. The
supervision period has to be set between 0 to 100 seconds for the setting [TDSSV].

(iii) Logic
Figure 2.38-2 shows the logic used to determine DS status and generates the output signal of
the DS state: DS_CLOSE or DS_OPEN. The supervision scheme logic to supervise the status
of the DS auxiliary switch contacts. This scheme logic is applied when BOTH is set for the
scheme switch [DS-Contact]. For the operation, the user should inject signals of DS states for
the following PLC connection points: ‘DS-NO CONT’, ‘DS NC CONT’ and others.

8C00001BB6 TDSSV 8C00001B9B


8C00001BBD
=1 1 t 0
&
DS-FAIL
0–100s
8C0000EBB6 DS-NO_CONT & 8E00001B85 To STUB-OC
≥1 DS_CLOSE
8C0000EBBD DS-NC_CONT 1
& 8F00001B86

1 DS_OPEN
≥1
NO
NC ≥1
Both

DS-Contact &
Both
DS-SV

Figure 2.38-2 Scheme logic to determine DS status

GRL200 (Soft 033 & 037)


- 535 -
6F2S1914 (0.37)

2.38.4 Dead line detection


The dead line detection (DLD) determinates whether the line is out-of-service or not. Checking
for the voltage existence in three-phase is required when all CBs are closed; hence, the output
signal of the DLD is being checked. (2.84.3)

(i) Under-voltage relay


A phase-to-phase (UVLS) element and a phase-to-ground (UVLG) element are provide in the
UV relay. Both elements operate when On is set for scheme switch [DLDbyUV]. (2.84.3.5)

(ii) Decision of CB operation


Deciding the dead line state is carried out by examining the CB position. The user should set
On for the scheme switch [DLDbyCB] for the decision. (2.84.3.2)

(iii) Detection time


The examining period for DLD detection is required to set using the setting [TDSSV], the value
of the detection time can be set between 0 to 100 seconds. (2.84.3.3)

(iv) Dead line detection logic


Figure 2.38-3 shows the scheme logic for the detection of an under voltage condition. It is also
used to determine whether the line is dead or not.
To Common of DISCAR, DEFCAR
UVLG-A
UVLG-B
UVLG-C

UVLG-AB
UVLG-BC
UVLG-CA
8000001B60 DEAD_LINE_DETECT
A & TDLD
8100001B61 & t 0
UVLG 8000001B9C To SOTF-OC
B ≥1
8200001B62 DEAD_LINE_DETECT
t 0
C

0.00 to 3000.00s
≥1
UVLG-OR

& UVLG-AND

8400001B63
AB
8500001B64
UVLS BC
8600001B65
CA
≥1
UVLS-OR

&
UVLS-AND

DLDbyUV On
From
DLDbyCB On
CB decision logic &
CB_ALLPH_OPEN

Figure 2.38-3 Dead line detection logic with under voltage relays

GRL200 (Soft 033 & 037)


- 536 -
6F2S1914 (0.37)

2.38.5 Detection of current change (OCD)


(i) Current change detection relay
Suppose that the difference exists between the latest current vector (IM) and the last current
vector (IN). The OCD function will operate if the difference is larger than the setting. The IN is
measured for the last two-cycles; the difference is decided using Equation (2.38-1):
|𝐼𝑀 − 𝐼𝑁 | > 𝐼𝑠 (2.38-1)
where a criteria for the decision is given by the pick-up threshold value (Is).

The pick-up threshold is defined using setting [OCD], which is from 0.05 A to 0.20 A at 1 A
rating†. At 5 A rating, 0.25 A to 1.00 A is applied.

IM
IS

IN

Figure 2.38-4 Current change detection

(ii) OCD logic


Figure 2.38-5 shows the OCD logic and its output signals.
To Common of DISCAR, DEFCAR
8000001B66 0 t 8000001B6F To VTF
A OCD-A
8100001B67 8100001B70
0 t
OCD B OCD-B
8200001B68 8200001B71
C 0 t OCD-C

0.1s
Figure 2.38-5 Scheme logic for current change check
(2.84.4)

GRL200 (Soft 033 & 037)


- 537 -
6F2S1914 (0.37)

2.38.6 User logic switches


PROT_COMMON function has four general-purpose switches; they are ready for the user’s
PLC logic. For example, the user can select a mode using [UserLogicSW1] when the PLC#1
logic operates in S1 mode (Purposes: the user can select one of modes in accordance with the
time, location, condition, etc.). Figure 2.38-6 shows the switches have connecting points for the
user’s logics.

PLC logic #1 made by the user


8000001C60
S1 USR_LG1_S1 xxxxxxxx1 XXXX_XXXX1
S2 8100001C61
USR_LG1_S2 xxxxxxxx2 XXXX_XXXX2
S3 8200001C62
USR_LG1_S3 xxxxxxxx3 XXXX_XXXX3
UserLogicSW1
PLC logic #2 made by the user
8000001C63
S1 USR_LG2_S1 xxxxxxxx1 XXXX_XXXX1
S2 8100001C64
USR_LG2_S2 xxxxxxxx2 XXXX_XXXX2
S3 8200001C65
USR_LG2_S3 xxxxxxxx3 XXXX_XXXX3
UserLogicSW2
PLC logic #3 made by the user
8000001C66
S1 USR_LG3_S1 xxxxxxxx1 XXXX_XXXX1
S2 8100001C67
USR_LG3_S2 xxxxxxxx2 XXXX_XXXX2
S3 8200001C68
USR_LG3_S3 xxxxxxxx3 XXXX_XXXX3
UserLogicSW3
PLC logic #4 made by the user
8000001C69
S1 USR_LG4_S1 xxxxxxxx1 XXXX_XXXX1
S2 8100001C6A
USR_LG4_S2 xxxxxxxx2 XXXX_XXXX2
S3 8200001C6B
USR_LG4_S3 xxxxxxxx3 XXXX_XXXX3
UserLogicSW4
Connections made by the user

Figure 2.38-6 Mode selected with UserLogicSWs


Note: For more information about the PLC programing, see Chapter PLC function.

GRL200 (Soft 033 & 037)


- 538 -
6F2S1914 (0.37)

2.38.7 Setting
PROT_COMMON (Function ID: 48A001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
UVLS 5.0 - 130.0 V UV phase-phase relay operating value 77.0
UVLG 5.0 - 130.0 V UV phase-ground relay operating value 45.0
0.05 - 0.25 -
OCD A OCD relay operating value 0.10 0.50
0.20 1.00
CB CB-System 1CB / 2CB - Single CB or One-and-a-half CB system 1CB
CB1-Contact NO / NC / Both - Kind of injected CB contact NO
CB2-Contact NO / NC / Both - Kind of injected CB2 contact NO
TCBLOSPH 0.00 - 0.10 s CB loss phase time 0.03
CB-SV Off / On - CB contact supervisor enable Off
TCBSV 0 - 100 s CB contact supervisor time 10
DS DS-Contact NO / NC / Both - Kind of injected DS contact NO
DS-SV Off / On - DS contact supervisor enable Off
TDSSV 0 - 100 s DS contact supervisor time 60
DL DLDbyUV Off / On - Dead line detection by under voltage Off
DLDbyCB Off / On - Dead line detection by CB open Off
TDLD 0.00 - 300.00 s Dead line detection timer 10.00
UserLogicSW1 S1 / S2 / S3 - User Logic Switch for General purpose S1
UserLogicSW2 S1 / S2 / S3 - User Logic Switch for General purpose S1
UserLogicSW3 S1 / S2 / S3 - User Logic Switch for General purpose S1
UserLogicSW4 S1 / S2 / S3 - User Logic Switch for General purpose S1

GRL200 (Soft 033 & 037)


- 539 -
6F2S1914 (0.37)

2.38.8 Data ID
 Signal monitoring point
PROT_COMMON(48A001)
Element ID Name Description
8000001B88 CB-A_CLOSE Main contact closed in phase-A of CB1 and CB2

8400001B8C CB-A_OPEN Main contact opening in phase-A of CB1 and CB2

8100001B89 CB-B_CLOSE Main contact closed in phase-B of CB1 and CB2

8500001B8D CB-B_OPEN Main contact opening in phase-B of CB1 and CB2

8200001B8A CB-C_CLOSE Main contact closed in phase-C of CB1 and CB2

8600001B8E CB-C_OPEN Main contact opening in phase-C of CB1 and CB2

8000001B73 CB1-A_CLOSE Main contact closed in phase-A of CB1

8000001B93 CB1-A_FAIL States of the CB1 not to be defined in phase-A

8000001BB7 CB1-A_NC_CONT Aux normally-close-contact in phase-A of CB1

8000001BB0 CB1-A_NO_CONT Aux normally-open-contact in phase-A of CB1

8400001B77 CB1-A_OPEN Main contact opening in phase-A of CB1

8100001B74 CB1-B_CLOSE Main contact closed in phase-B of CB1

8100001B94 CB1-B_FAIL States of the CB1 not to be defined in phase-B

8100001BB8 CB1-B_NC_CONT Aux normally-close-contact in phase-B of CB1

8100001BB1 CB1-B_NO_CONT Aux normally-open-contact in phase-B of CB1

8500001B78 CB1-B_OPEN Main contact opening in phase-B of CB1

8200001B75 CB1-C_CLOSE Main contact closed in phase-C of CB1

8200001B95 CB1-C_FAIL States of the CB1 not to be defined in phase-C

8200001BB9 CB1-C_NC_CONT Aux normally-close-contact in phase-C of CB1

8200001BB2 CB1-C_NO_CONT Aux normally-open-contact in phase-C of CB1

8600001B79 CB1-C_OPEN Main contact opening in phase-C of CB1

8300001B76 CB1_ALLPH_CLOSE Main contact closed in three-phases of CB1

8700001B7A CB1_ALLPH_OPEN Main contact opening in three-phases of CB1

8300001B96 CB1_FAIL States of the CB1 not to be defined in three-phase

8300001BBF CB1_NC_CONT Aux normally-close-contact in three-phase of CB1

8300001BBE CB1_NO_CONT Aux normally-open-contact in three-phase of CB1

8000001B7C CB2-A_CLOSE Main contact closed in phase-A of CB2

8400001B97 CB2-A_FAIL States of the CB2 not to be defined in phase-A

8400001BBA CB2-A_NC_CONT Aux normally-close-contact in phase-A of CB2

8400001BB3 CB2-A_NO_CONT Aux normally-open-contact in phase-A of CB2

8400001B80 CB2-A_OPEN Main contact opening in phase-A of CB2

8100001B7D CB2-B_CLOSE Main contact closed in phase-B of CB2

8500001B98 CB2-B_FAIL States of the CB2 not to be defined in phase-B

8500001BBB CB2-B_NC_CONT Aux normally-close-contact in phase-B of CB2

8500001BB4 CB2-B_NO_CONT Aux normally-open-contact in phase-B of CB2

8500001B81 CB2-B_OPEN Main contact opening in phase-B of CB2

8200001B7E CB2-C_CLOSE Main contact closed in phase-C of CB2

8600001B99 CB2-C_FAIL States of the CB2 not to be defined in phase-C

8600001BBC CB2-C_NC_CONT Aux normally-close-contact in phase-C of CB2

8600001BB5 CB2-C_NO_CONT Aux normally-open-contact in phase-C of CB2

8600001B82 CB2-C_OPEN Main contact opening in phase-C of CB2

8300001B7F CB2_ALLPH_CLOSE Main contact closed in three-phases of CB2

8700001B83 CB2_ALLPH_OPEN Main contact opening in three-phases of CB2

GRL200 (Soft 033 & 037)


- 540 -
6F2S1914 (0.37)

 Signal monitoring point


PROT_COMMON(48A001)
Element ID Name Description
8700001B9A CB2_FAIL States of the CB2 not to be defined in three-phase

8300001B8B CB_ALLPH_CLOSE Three-phase contacts closed in CB

8700001B8F CB_ALLPH_OPEN Three-phase contacts not closed in CB

8800001B90 CB_ANYPH_CLOSE Any one of three-phase contacts closed in CB

8900001B91 CB_LOSS_PHASE Any one of three-phase contacts opening in CB

8000001B9C DEAD_LINE_DETECT Detected the line not being energized

8E00001B85 DS_CLOSE Main contacts closed in DS

8C00001B9B DS_FAIL States of the DS not to be defined

8C00001BBD DS_NC_CONT Aux normally-close-contact in DS

8C00001BB6 DS_NO_CONT Aux normally-open-contact in DS

8F00001B86 DS_OPEN Main contact opening in DS

8000001B66 OCD-A OCD element operated in phase-A

8000001B6F OCD-AT Off-delay timer after OCD element in phase-A

8100001B67 OCD-B OCD element operated in phase-B

8100001B70 OCD-BT Off-delay timer after OCD element in phase-B

8200001B68 OCD-C OCD element operated in phase-C

8200001B71 OCD-CT Off-delay timer after OCD element in phase-C

8000001B60 UVLG-A UVLG element operated in phase-A

8900001B6B UVLG-AND UVLG elements operated in three-phase

8100001B61 UVLG-B UVLG element operated in phase-B

8200001B62 UVLG-C UVLG element operated in phase-C

8800001B6A UVLG-OR Any UVLG element operated in three-phases

8400001B63 UVLS-AB UVLS elements operated in phase-AB

8D00001B6D UVLS-AND UVLS elements operated in three-phase

8500001B64 UVLS-BC UVLS elements operated in phase-BC

8600001B65 UVLS-CA UVLS elements operated in phase-CA

8C00001B6C UVLS-OR Any UVLS element operated in three-phase

2200001BAD CB2_OPCNT Aux normally-close-contact in three-phase of CB2

3000001BA5 CB2_POS Aux normally-open-contact in three-phase of CB2

 Connection point in PLC logic


PROT_COMMON (48A001)
Element ID Name Description
800000EBB7 CB1-A_NC_CONT CB1-A normally close contact

800000EBB0 CB1-A_NO_CONT CB1-A normally open contact

810000EBB8 CB1-B_NC_CONT CB1-B normally close contact

810000EBB1 CB1-B_NO_CONT CB1-B normally open contact

820000EBB9 CB1-C_NC_CONT CB1-C normally close contact

820000EBB2 CB1-C_NO_CONT CB1-C normally open contact

830000EBBF CB1_NC_CONT CB1 normally close contact

830000EBBE CB1_NO_CONT CB1 normally open contact

840000EBBA CB2-A_NC_CONT CB2-A normally close contact

840000EBB3 CB2-A_NO_CONT CB2-A normally open contact

850000EBBB CB2-B_NC_CONT CB2-B normally close contact

850000EBB4 CB2-B_NO_CONT CB2-B normally open contact

GRL200 (Soft 033 & 037)


- 541 -
6F2S1914 (0.37)

 Connection point in PLC logic


PROT_COMMON (48A001)
Element ID Name Description
860000EBBC CB2-C_NC_CONT CB2-C normally close contact

860000EBB5 CB2-C_NO_CONT CB2-C normally open contact

8C0000EBBD DS_NC_CONT DS normally close contact

8C0000EBB6 DS_NO_CONT DS normally open contact

 Mapping points in IEC 61850


PROT_COMMON (48A001)
Element ID Name Description
2200001BA6 CB1-A_OPCNT IEC61850 OpCnt of CB1-A in XCBR

3000001B9E CB1-A_POS IEC61580 Pos-signal of CB1-A in XCBR of LN

2200001BA7 CB1-B_OPCNT IEC61850 OpCnt of CB1-B in XCBR

3000001B9F CB1-B_POS IEC61580 Pos-signal of CB1-B in XCBR of LN

2200001BA8 CB1-C_OPCNT IEC61850 OpCnt of CB1-C in XCBR

3000001BA0 CB1-C_POS IEC61580 Pos-signal of CB1-C in XCBR of LN

2200001BA9 CB1_OPCNT IEC61850 OpCnt in three-phase of CB1 in XCBR

3000001BA1 CB1_POS LN Pos-signal of three-phase of CB1 in XCBR

2200001BAA CB2-A_OPCNT IEC61850 OpCnt of CB2-A in XCBR

3000001BA2 CB2-A_POS IEC61580 Pos-signal of CB2-A in XCBR of LN

2200001BAB CB2-B_OPCNT IEC61850 OpCnt of CB2-B in XCBR

3000001BA3 CB2-B_POS IEC61580 Pos-signal of CB2-B in XCBR of LN

2200001BAC CB2-C_OPCNT IEC61850 OpCnt of CB2-C in XCBR

3000001BA4 CB2-C_POS IEC61580 Pos-signal of CB2-C in XCBR of LN

GRL200 (Soft 033 & 037)


- 542 -
6F2S1914 (0.37)

Cold load protection (CLP)


The function of cold load protection (CLP) can have a number of disparate groups for setting.
The CLP can switch a group setting from one operation to another operation at which
protection functions in the IED are required to shift their settings from steady state to
particular state. For instance, the setting group for the particular state is good for a period
after energizing the system.

In the steady state operation, the load current through a transmission-line is smaller
than the total of the rated loads that connected to the transmission-line. The load current can
reach as high as times of the maximum load current for a moment when the entire loads are
energized after a long interruption, but the load current can decreases within three or four
seconds. It is accounted that the load current at the energizing time is 1.5 times larger than a
normal peak load. Thus, it is necessary for some protective functions to have a few setting
groups that discriminate between the inrush current on cold load restoration and the fault
current. For instance, the function of overcurrent protection (OC) with the CLP is immune
during the inrush period. The OC is discussed separately. (See chapter Relay application:
Overcurrent protection)

The CLP can have eight setting groups for cold load state in order that the CLP can
follows the transition from one state to another state. Thus, the CLP can make some protective
functions switch to another higher setting group including time delay. The CLP also can halt
with setting. The group selection of the CLP is performed with scheme switch [CLP-SG].

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.39-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 543 -
6F2S1914 (0.37)

2.39.1 Scheme logic


State transition diagram and scheme logic are shown in Figure 2.39-1 and Figure 2.39-2. It
should be noted that the scheme logic requires two binary inputs: circuit breaker (CB) OPEN
and circuit breaker (CB) CLOSED.

Under the normal operation, where the CB is closed, the CLP stays in STATE 0, and the
OC operates with a normal setting group.

When the CB opens, the scheme moves into STATE_1, then Cold-load-enable-timer
(TCLP) runs. If the CB closes again while the TCLP is running, the scheme will re-enter into
STATE_0. If the TCLP expires and the load is in cold, the scheme moves into STATE_2. When
the CB closes again, the scheme moves into STATE_3.

Cold-road-reset-timer (TCLP) runs at STATE_3. If the CB re-opens while the TCLP is


running, the scheme returns into STATE_2. If the TCLP is time out, the scheme moves into
STATE_0, where the load is considered as warm, and the setting of normal operation is applied
again.

At STATE_2 and STATE_3, the setting group of the CLP is applied. The operation of the
CLP is forbidden by placing set of OFF for the scheme switch [CLP-EN].

Accelerated reset of the CLP is also possible. As being at STATE_3, poly-phase currents
are monitored by the function of inrush current detection (ICD). If poly-phase currents plunge
below the setting of ICD threshold, and when the duration of the plunge is longer than setting
[TCLP_DO], then the scheme automatically reverts into STATE_0. By placing set of ON for
scheme switch [CLP-DOEN], it is possible for the reset function to accelerate.

GRL200 (Soft 033 & 037)


- 544 -
6F2S1914 (0.37)

STATE 0
CB status: Closed
Settings: Normal

Monitor CB status

CB opens CB closes
within
T CLE time

STATE 1
CB status: Open
Settings: Normal

Run T CLE timer


I L<ICLDO for
Monitor CB status T CLR timer T CLDO time
expires
T CLE timer
expires
STATE 3
STATE 2 CB closes CB status: Closed
CB status: Open Settings: Cold Load
Settings: Cold Load
Run T CLR timer
Monitor CB status CB opens Monitor CB status
within Monitor load current I L
CLR time

Figure 2.39-1 State transition diagram for cold load protection

From PROT_COMM
CB-DS_CONDITION

CB_ALLPH_OPEN

CB_ANYPH_CLOSE
STATE CONDITION
8000001B60 Change to
& & STATE 1
STATE 0
TCLP_EN
8100001B61 t 0 Change to
& 1 STATE 2
STATE 1 &
0 - 10000s 1
& Change to
& Change to
1 STATE 0
Setting Group1
8200001B62
STATE 2 & Change to
& Change to
& Setting Group2
STATE 3

8300001B63 & Change to


Setting Group3
STATE 3 & &
TCLP_RESET Change to
t 0 &
[CLP-EN] &
Setting Group4

+
"ON" 0 - 10000s TCLP_DO & Change to
Setting Group5
t 0
& Group1
8000001C20
A 0.00 - 100.00s
Group2 & Change to
1 1 Group3 Setting Group6
OCCLP 8100001C21
B Group4
8200001022 Group5 & Change to
C CLP-Test Group6 Setting Group7

+ CLP-SG Group7
[CLP-DOEN] Group8 & Change to
+ Setting Group8
+
"ON"

Figure 2.39-2 Scheme logic for cold load protection

GRL200 (Soft 033 & 037)


- 545 -
6F2S1914 (0.37)

2.39.2 Setting
CLP(Function ID: 481001) at Common
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
CLP-EN Off / On - Cold load protection scheme switch Off
CLP Group1 / Group2 /
Group3 / Group4 /
CLP-SG - Applied setting group at cold load mode Group1
Group5 / Group6 /
Group7 / Group8
TCLP-EN 0 - 10000 s Cold load enable time 100
TCLP-RESET 0 - 10000 s Cold load reset time 100
DOEN CLP-DOEN Off / On - Cold load drop-out enable Off
0.02 - 0.10 -
OCCLP A Cold load drop-out current threshold 0.50 2.50
3.00 15.00
TCLP-DO 0.00 - 100.00 s Cold load drop-out time 0.00

Test tool(Function ID: 481001)


Range Default
Item Unit Contents Note
1A rating 5A rating 1A 5A
Function test Off / STATE0 /
CLP-Test - Forcibly changing to CLP state Off
STATE3

GRL200 (Soft 033 & 037)


- 546 -
6F2S1914 (0.37)

2.39.3 Data ID
 PLC monitoring point
CLP(Function ID: 481001)
Element ID Name Description
8000001C20 OCCLP-A OCCLP relay element operated (phase-A)

8100001C21 OCCLP-B OCCLP relay element operated (phase-B)

8200001C22 OCCLP-C OCCLP relay element operated (phase-C)

8000001B60 CLP STATE0 The scheme is in STATE0

8100001B61 CLP STATE1 The scheme is in STATE1

8200001B62 CLP STATE2 The scheme is in STATE2

8300001B63 CLP STATE3 The scheme is in STATE3

3100001B64 CLP STATE2OR3 The scheme is in STATE2OR3

GRL200 (Soft 033 & 037)


- 547 -
6F2S1914 (0.37)

3 General control function


Contents Pages Pages
Common controls (CMNCTRL) 558 LED reset function (LEDR) 571
Control hierarchy 555 Local control 568
Control level and control point 556 Mode control function (MDCTRL) 605
Control right 556 Select-before-operation mode (SBO) 552
Control scheme 549 PLC_BIT/UNIT/BOOL signals 561
Counter function for the general (GCNT) 585 Programmable logic control (PLC) 568
Direct-operation mode (DIR) 553 Remote control 568
Double command blocking (DCB) 559

GRL200 (Soft 033 & 037)


- 548 -
6F2S1914 (0.37)

Control scheme
Figure 3.1-1 shows the control overview for the control function; there are two control stages:
“Wait for a command” and “Receiving commands”. The function will wait for a command from
the server in the first stage. During the receiving stage, the function will respond to “Select”,
“Cancel”, and “Operate” commands. Specific logic is provided for each command for each
receiving stage. A decision is required from each logic block to move to the next step (i.e., ‘Failed’
or ‘Success’). When a ‘success’ decision is determined in the operate logic, the respective
command is issued to the relevant device; the device commences with its operation (for example,
a 43-switch is changed to “ON” from “OFF”). The waiting and receiving stages loop around at
the receipt of every command.

Wait for a command

Waiting stage

Selection stage Failed

Receiving “select command” Select logic Wait for next command


Success

Failed (Do nothing)

Receiving “cancel command” Cancel logic


Success Cancel of “Select command”
Failed

Receiving “operate command” Operate logic Operation completed


Success

Figure 3.1-1 Stages in control function

The type of control can be categorized in accordance with its origin, (Remote/Local/PLC)
and modes (SBO/DIR). That is, the respective control scheme should respond to the respective
origin and mode. The user should be aware of the context of the control action, “On (or Closing)
control” and “Off (or Open) control” in relationship to its origin and mode†.

†Note:The “On control” and “Off control” can be found in the SPOS, DPSY and other
functions. For more information on these functions, see the explanations provided
for each respective function.

GRL200 (Soft 033 & 037)


- 549 -
6F2S1914 (0.37)

(i) Command reception in SBO mode


In the SBO receiving stage shown in Figure 3.1-1 we can find three processes: select, cancel,
and operate command flows.

Reception of “select command”


Figure 3.1-2 shows a schematic process flow diagram when receiving a “select command”
following the “Wait for a command”. The receipt “select command” is divided into “select
command ‘On’ (Closing)” and “select command ‘Off ’ (Open)”. The select command is carried out
based on its origin: “Remote”, “Local”, and “PLC”. If the “select command” is successful, the
process will wait for the receipt of the next command.

Wait for a command

Receiving “Select command”


Failed
When On is issued Select logic F/S Waiting for a next
Success
from the remote-end “Remote-On-control” “operate command”
or
“cancel command”
When Off is issued Select logic
from the remote-end “Remote-OFF-control”

When On is issued Select logic


from the local-end “Local-On-control”

When Off is issued Select logic


from the local-end “Local-OFF-control”

When On is issued by Select logic


the PLC function “PLC-On-control”

When Off is issued by Select logic


the PLC function “PLC-OFF-control”

Figure 3.1-2 Schemes for “Select command”

Reception of “cancel command”


If the “select command” proceeds successfully following the receiving stage, the function can
subsequently receive a “cancel command”. Figure 3.1-3 shows the reception of a “cancel
command”. If the “cancel command” is successful, the “select command” is discarded and the
function returns to the “Wait for a command” stage (i.e., the initial stage). In other words, the
function waits for a new “select command” so that the other control functions can receive a
command.

GRL200 (Soft 033 & 037)


- 550 -
6F2S1914 (0.37)

Wait for a command

Receiving “Cancel command”


Success Discarding of Return to “Wait
Cancel logic F/S
When Cancel is issued “select command” for a command”
from the remote-end “Remote-cancel”
Failed
When Cancel is issued Cancel logic Do nothing
from the local-end “Local-cancel”

Figure 3.1-3 Scheme “Cancel command”

Reception of “operate command”


Following successful completion of the “select command”, the control function is ready to
receive an “operate command” in order to control a device. The receipt of “operate command”
is divided into “Operate command ‘On’ (Closing)” and “Control command ‘Off ’ (Open)”; each of
the two commands is carried out based upon its origin i.e. “Remote”, “Local”, and “PLC”. If the
“operate command” is completed, the “select command” can be released; then a new “Wait for
a command” stage can commence for receipt of a new “select command”.

Wait for a command Failed

Receiving “Select command” Receiving “Operate command”


Failed
Return to “Wait
Release of
F/S for a command”
Select logic Operate logic Success “select command”
“Remote-On-control” “Remote-On-control”

Select logic Operate logic


“Remote-OFF-control “Remote-OFF-control
” ”
Select logic Operate logic
“Local-On-control” “Local-On-control”

Select logic Operate logic


“Local-OFF-control” “Local-OFF-control”

Select logic Operate logic


“PLC-On-control” “PLC-On-control”

Select logic Operate logic


“PLC-OFF-control” “PLC-OFF-control”

Figure 3.1-4 Scheme “Operate command”

(ii) Command reception in DIR mode


In DIR mode, issuing an “operate command” is possible without the reception of the “select
command”. Thus, the reception of an “operation command” only features in the control scheme†.
We shall see the DIR mode later.
†Note:We can encompass the operation of the “select command” being performed
internally in the control scheme. Thus, the user is not required to take account of
the reception of the “select command”.

GRL200 (Soft 033 & 037)


- 551 -
6F2S1914 (0.37)

Control mode
Either Select-Before-operation (SBO) or Direct-Operate-control (DIR) is provided as a control
mode for the device. The user can select the preferred control mode.

3.2.1 Select-before-operation mode (SBO)


The user should be aware that in the SBO mode a signal is returned from the target device in
the form of a response signal, (answer). When the target device sends a response to the IED
after receiving a command, the server (and the IED) can send another command to the target
device if the criterion of the response (answer) is satisfied. A safe SBO operation (SBOns) is
normally utilized; however, the user can opt to select an enhanced-security SBO operation
(SBOes), if additional safety is deemed necessary.

(i) SBO with enhanced security (SBOes)


In the SBOes, an operation process (Oper) commences after the completion of a selection
process (SBOw). Figure 3.2-1 exemplifies the exchange of commands and responses; the server
receives a response (answer#1) from the IED with regard to a SBOw command. Then, provided
that the response, (answer#1) received from the IED is satisfied, the server can send an Oper
request to the IED to control the device. If the target device completes the operation
successfully, the server will receive an operation result. Figure 3.2-1 shows the communication
flow between the server (remote-end) and the IED, note that the user will also see the same
process flow when using the IED-front-panel key-operations. That is, the IED-front-panel
(local-end) takes the place of the server (remote-end).
Server IED
Process (SAS) (Control function) Target device

SBOw
Selection Command

Answer#1 Response

Oper. Command
Operation

Answer#2 Response

Device status changed


Operation result Command
Result termination

Figure 3.2-1 SBO with enhanced security

(ii) SBO with normal security (SBOns)


Figure 3.2-2 shows normal SBOns control. The difference between the SBOes and the SBOns
is that the IED does not send an operation result in response to the request Oper.

GRL200 (Soft 033 & 037)


- 552 -
6F2S1914 (0.37)

Process Server IED


(SAS) (Control function) Target device

Selection SBOw
Command
Answer Response

Oper.
Operation
Command
Answer
Response

Figure 3.2-2 SBO with normal security

3.2.2 Direct-operation mode (DIR)


In the DIR mode, a target device is controlled without the reception of the select command. An
enhanced security mode (DOes) is also provided when the user wishes to control a device with
additional security rather than the normal level of security experienced with mode (DOns) .

(i) DIR with enhanced security (DOes)


Figure 3.2-3 illustrates the server sending the Oper request to the IED; the server receives a
response, (answer#1) from the IED. The result is notified when the operation of the target
device is complete. The result includes status information; it informs whether the target device
has operated normally or not. Note that the control start of the target device is initiated
regardless of the state of the target device.

Process SAS IED


(Server) (Control function) Target device

Oper.
Operation Command

Answer#1 Response
Device status changed

Answer#2 Command
termination
Result

Figure 3.2-3 Direct control with enhanced security

(ii) DIR with normal security (DOns)


A response (answer#2) from the target device is not sent to the SAS in DOns, as shown in
Figure 3.2-4.

GRL200 (Soft 033 & 037)


- 553 -
6F2S1914 (0.37)

SAS IED
Process (Server) Control function Target device

Operation
Control
Command
Answer#1

Response

Figure 3.2-4 Direct control with normal security

GRL200 (Soft 033 & 037)


- 554 -
6F2S1914 (0.37)

Control hierarchy
It is important that the user understand the meaning of the terms ‘control-right’ and ‘control-
hierarchy’ in connection with the functioning of the control and monitoring applications in the
sub-station automation system (SAS) and the sub-station control and monitoring system
(SCMS). For instance, when we wish to operate a device (such as a piece of switchgear or
others), the system has the device forbidden to operate if the system is unable to give a ‘control-
right’ for the device using the ‘control-hierarchy’. Figure 3.3-1 depicts the control-hierarchy;
the control-hierarchy is made of three control-levels, two selector-switches, and three control-
points. Either control command of three control-points is permitted so that the other
commands will be forbidden in the system. On this account, no collision of control-points exists
within the system.
Control-point in RCC

Network level

Control-point in OWS/EWS
Communication
EWS OWS

Selector switch
(43R) RCC EWS/OWS

Station level

Control-point on LCD(MIMIC)
ON/OFF operation on LCD

Selector switch (43BCU‡ ) Remote (R) Local (L)


L Operation
R KEY

Bay level

Control-right
Switchgear and others

Control levels Selector switches Control points and positions of selector switches

Figure 3.3-1 Control hierarchy and selector switches


‡Note: The L|R key on the IED is used for the 43BCU switch. The L|R key
can be programmed during manufacture using the PLC function before shipment,
but it can also be programmed by the user.
§Note: The user can implement a hierarchy by programming the PLC. For more
details, see Chapter PLC function.

GRL200 (Soft 033 & 037)


- 555 -
6F2S1914 (0.37)

3.3.1 Control level and control point


As shown in Figure 3.3-1, the control hierarchy is distributed across three levels; the network
level having a remote-control center (RCC); the station level having operator and engineering
work stations (OWS/EWS); and the bay level† having an IED equipped with an LCD screen.
One of the three control-points (RCC, OWS/EWS, and LCD) is available to issue a control-
command.
†Note:We, hereafter, discuss only the operations at the bay level; that is, we focus only
on operations made from the bay level. The scope of this discussion does not
include operations from either the remote control center or the network levels.

3.3.2 Selector switches and bay operations


At the bay level, the 43BCU switch opens a path to permit the flow of the control-right.

(i) LCD operation


When the user sets the 43BCU switch to “Local (L)”, the issuing of a control-command from
the LCD is possible for the device.

(ii) RCC, EWS, or OWS operation


Alternatively, suppose that the position “Remote (R)” is selected at the 43BCU switch. In this
case, the issuing of the control-command from the LCD is not possible.

3.3.3 Programming of control-right distributions


Figure 3.3-2 illustrates that the PLC function provides the means to distribute the control-
right for the control functions.

The part ○
1 and ○
2 logics are programmed so that, the control-right signal can be

distributed to the respective control applications. With regard to the DPSY01 function, PLC
connection point “DPSY01IN_TMP_28” has been programmed using DOUT_BOOL feature (for
example). Therefore, the control-right signal is transferred to the select and operate-condition
logic‡ when the user connects the control-hierarchy with the DPSY01 function using
“DPSY01IN_TMP_28”.

‡Note:The select-condition and operate-condition logic are used to decide upon the
execution of a select command or an operate command in the DPSY01 function.
For more detail, see chapter Control and monitoring application: DPSY function:
Operate condition and Select condition. As per the DPSY function, other functions,
such as SPOS, DPOS, and TOPS, have the same logic; the user is required to do
the connection.

GRL200 (Soft 033 & 037)


- 556 -
6F2S1914 (0.37)


1 Checking the bay level ○
2 Distribution of the control-right
RemoteLocalKey_43BCU
From LOCMT
DIN_UNIT UNIT_TO_BOOL SPOS01_CTRL_RIGHT
LRSW01_LR_ST FID DO
DTYPE ST DOUT_BOOL
(530001 3109001001) FID ST
DID
DTYPE
DID
DI
To SPOS01
510001 820101ED50 SPOS01IN_TMP_28 Select
condition logic
SPOS02_CTRL_RIGHT
DOUT_BOOL
Operate
FID ST
condition logic
DTYPE
DID
DI
To SPOS02
510001 820102ED50 SPOS02IN_TMP_28 Select
condition logic
Operate
condition logic

DPSY01_CTRL_RIGHT
DOUT_BOOL
FID ST
DTYPE
DID
DI
To DPSY01
511001 820201ED50 DPSY01IN_TMP_28 Select
condition logic
DPSY02_CTRL_RIGHT Operate
DOUT_BOOL condition logic
FID ST
DTYPE
DID
DI
To DPSY02
511001 820202ED50 DPSY02IN_TMP_28 Select
condition logic
TPOS02_CTRL_RIGHT Operate
DOUT_BOOL condition logic
FID ST
DTYPE
DID
DI
To TPOS02
513001 810402EE57 TPOS02IN_TMP_21 Select
condition logic
Operate
condition logic

To other control functions

Figure 3.3-2 Programmed Control-right on the bay level

GRL200 (Soft 033 & 037)


- 557 -
6F2S1914 (0.37)

Common controls (CMNCTRL)


The CMNCTRL function consists of two parts. The former part (CMNCTRL1) is used to
prevent double-commands, which are forbidden, by the use of select-states for the respective
control functions. The latter part (CMNCTRL2) is served as a mediator to provide a bridge
between functions.

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.4-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 558 -
6F2S1914 (0.37)

3.4.1 Double command blocking (DCB)


For control functions, the operating principle is that priority is given to the first command
received and shall be executed first. In other words, successive commands received do not have
the right to run until the first command received has failed to complete its operation (that is,
the principle of double command blocking (DCB) is established). The principle is significant for
protection and control devices in the sub-station†. Figure 3.4-1 illustrates how each control
function generates a SLD_RPT signal; the aggregation of SLD_RPT signals is performed in the
CMNCTRL1 function. The resultant signal is output at PLC connection point “DCB SND OR”.
Command “P2-Control” from the rem
The resultant signal is returned to the respective control function as feedback.
“From 61850 CMNCTRL1 function
communication 510001 0001011001 DCB RCV OR
“stVal” message 2
SPOS function
SPOS01 function
To 61850
Reception of “DCB”
communication

Output of “StSeld” SPOS01_STD_RPT DCB SND OR “stVal” message 1

SPOS02 function SPOS02_STD_RPT To control functions


(510001 0008001F42) in its own
SPOS03 function SPOS03_STD_RPT

SPOS20 function
SPOS20_STD_RPT

DPOS function
≥1
Reception of “DCB”

Output of “StSeld” DPOS01_STD_RPT

DPOS01 function

DPOS72 function
DPOS72_STD_RPT

DPSY function

TPOS function

SOFTSW function

Figure 3.4-1 DCB operation in CMNCTRL1 function


†Note:Let us assume that the control function in IED-1 controls CB1, as shown in Figure
3.4-2. IEDs -2 to -10 are forbidden to operate their CBs throughout the period that
IED-1 is in operation. Control functions are also forbidden to operate CB1 when
the automatic sequence controlling function (ASEQ) is in operation. We discuss
the ASEQ function later. (See Chapter Control and monitoring application:

GRL200 (Soft 033 & 037)


- 559 -
6F2S1914 (0.37)

Automatic sequence controlling function)

In Figure 3.4-1, the CMNCTRL1 function generates a message denoted with the number
1; Figure 3.4-2 exemplifies that the IED-1 generates the “stVal” message 1. In addition, IEDs-
2 to -10 are also required to receive message 1, this is denoted with the number 2. For
IEC61850 communication, the “stVal” messages 1 and 2 are carried by GOOSE publish and
GOOSE subscribe. Thus, for all IEDs (i.e., IED-1 to IED-10 of Figure 3.4-2), it is required to
set the GOOSE publish destination corresponding to the message.

Ring LAN network constructed for the SAS


stVal message

1 2 2 2

IED-1 IED-2 IED-3 IED-10

CB1 CB2 CB3 CB10

Figure 3.4-2 Sending and reception of stVal message

Figure 3.4-3 demonstrates how the GOOSE publish destination is set with regard to the
DCB message. The user is required to set the destination for each respective IED by selecting
the signal “DCB SND OR”, corresponding to the GOOSE publish, this must be performed at
the respective screens in GR-TIEMS†. That is, the user should select the “stVal” item for each
IED. After setting, the user should write the setting date for each respective IED.


1 Selected IED

○2 Required settings in
the respective IEDs.

Figure 3.4-3 Example of DCB setting for IED-1 using GR-TIEMS


†Note:For more operation information on GR-TIEMS, see Chapter Engineering tool.

GRL200 (Soft 033 & 037)


- 560 -
6F2S1914 (0.37)

3.4.2 PLC_BIT/UNIT/BOOL signal


The control and monitoring functions are mutually interconnected within the IED; hence,
cascading features are provided to transfer information between them so that the user does
not need to check the interconnections. Approximately 1500 signals are included to facilitate
the internal connection of the control and monitoring functions; their signals are distributed
into BIT, UNIT, BOOLEAN types, which are listed later. Figure 3.4-4 exemplifies the
“PLC_BIT_0201” signal, which may be used for recording events and other purposes.
CMNCTRL2
function
PLC_O_BIT_0201 For
・Event record function
5A0101 800200EF40 PLC_BIT_0201 (5A0101 8002001F40)
・Communication (required mapping)
Information ・LEDs
cascaded§ ・IED screen display
・Binary output module
etc…

Figure 3.4-4 Cascading information using signal “PLC_BIT_0201”

3.4.3 Provision of selected status


Let us assume that a select-command is sent for an IED to control a target-device by the
substation automation system (SAS†), but the target-device is not ready to be controlled. The
unready condition might be due to the target-device already being in operation (e.g., CB
tripping) or a failure of the device may have occurred; thus, the IED has to drop the select-
command. If this occurs, the IED is required to send a message stating the reason to the SAS†.
Table 3.4-2 lists the messages generated in the CMNCTRL1 function describing the failure.
Table 3.4-2 Reason messages due to the release of the select-command
Signal Number Signal Name Description

5A0001 3008001FB4 SCS_CTLNUM

5A0001 2008001008 SCS_ORCAT

5A0001 2208001001 SCS_ADDCAUSE Reason codes for the SAS†

5A0001 6A08001009 SCS_ORIDENT

5A0001 3008001FB4 SCS_CTLNUM

†Note:The user should recognize that the reason messages are only available for
operation with the GCS1000 control system manufactured by Toshiba.

3.4.4 Miscellaneous settings


The CMNCTRL1 function has the following five common settings:
1. Control direction: The [SDCEN] can configure the control directions of the SPOS,
DPOS and TPOS functions. If required these functions can be in the
same control direction, set On for the scheme switch [SDCEN].
2. Return value: When the number of the counter reaches its maximum value (in case
of the default setting, 999,999), it can return and begin

GRL200 (Soft 033 & 037)


- 561 -
6F2S1914 (0.37)

incrementing from either 0 or 1. The return number can be set with


[CNTRV].
3. Select-cancel timer: If the selection of a target device is made, but the control operation
of the selected device is not carried out in a predetermined time
limit, the selection is canceled. The time limit can be set using
[TSC]; the range is between 30 and 300sec. having a 1sec. step.
4. Time out: When the selection of the target device and its control execution is
made, the selection will be canceled automatically after the setting
time [EXEWAIT] if the control result is not received at the IED from
the target device. The setting time ranges from 30 to 300sec. in 1
sec. steps.
5. Counter limit: The maximum value of the counters can be set between 9 and
2,147,483,647 using [CNTVALMAX]. The default setting is 999,999.
6. Quality signal: If “q” or “Quality” information should not be taken to control, set On
for setting [QBLK]. The QBLK clears the content of quality
information so that control operation can be achieved with the
absence of quality information.

3.4.5 Setting
CMNCTRL (FunctionID:5A0001)
Setting items Range Unit Contents Default Note

SDCEN Off / On - Setting of the control to the same direction Off


CNTRV 0-1 - Next value of the counter[CNTVALMAX] level 0
TSC 30 - 300 - Selection cancel time-out timer 30
EXEWAIT 30 - 300 - Waiting execute operation time-out timer 30
CNTVALMAX 9 - 2147483647 - Upper limit level of the counter 999999
QBLK Off / On - Behavior of quality for DCB Off
TRV-BLK Off / On - To block non-selectable behavior on TRAVELLING Off

GRL200 (Soft 033 & 037)


- 562 -
6F2S1914 (0.37)

3.4.6 Signal
 PLC connection points
CMNCTRL (Function ID: 5A0001)
Element ID Name Description
800800EDE1 ADD_DCB_SND Additional condition for double command blocking

800800EFB7 LAN_CONN_FAIL_IN

800800EF40 PLC_I_001 PLC event information 1

800800EF41 PLC_I_002 PLC event information 2

800800EF42 PLC_I_003 PLC event information 3

800800EF43 PLC_I_004 PLC event information 4

800800EF44 PLC_I_005 PLC event information 5

800800EF45 PLC_I_006 PLC event information 6

800800EF46 PLC_I_007 PLC event information 7

800800EF47 PLC_I_008 PLC event information 8

800800EF48 PLC_I_009 PLC event information 9

800800EF49 PLC_I_010 PLC event information 10

… …. …

800800EFA2 PLC_I_099 PLC event information 99

800800EFA3 PLC_I_100 PLC event information 100

800800EFB8 TIME_SYN_FAIL_IN

800800EDE0 TRAVELLING_PLC travelling signal for PLC

 PLC monitoring point


CMNCTRL (Function ID: 5A0001)
Element ID Name Description
0008001F45 AUTO SEL LOCK OR SEL Lock OR for AUTOSEQ

0008001F43 CNT CTRL OR CNT CTRL OR for Event Message

0008001F41 DCB RCV OR DCB RCV OR for SEL Lock

0008001F42 DCB SND OR DCB SND OR for GOOSE

8008001FB7 LAN_CONN_FAIL

0008001F44 OPE_TIME RST OR Operation Time RST OR for Event Message

0008001F46 RELAYTRIP EXTENSION Relay Trip signal

2208001001 SCS_ADDCAUSE Self-cancellation signal(AddCause)

8008001FB8 TIME_SYN_FAIL

0008001F40 TRAVELING OR Traveling OR for SEL Lock

0008001F50 PLC_O_001 PLC event output 1

0008001F51 PLC_O_002 PLC event output 2

0008001F52 PLC_O_003 PLC event output 3

0008001F53 PLC_O_004 PLC event output 4

0008001F54 PLC_O_005 PLC event output 5

0008001F55 PLC_O_006 PLC event output 6

0008001F56 PLC_O_007 PLC event output 7

0008001F57 PLC_O_008 PLC event output 8

0008001F58 PLC_O_009 PLC event output 9

0008001F59 PLC_O_010 PLC event output 10

… …. …

0008001FB2 PLC_O_099 PLC event output 99

GRL200 (Soft 033 & 037)


- 563 -
6F2S1914 (0.37)

 PLC monitoring point


CMNCTRL (Function ID: 5A0001)
Element ID Name Description
0008001FB3 PLC_O_100 PLC event output 100

 PLC connection points


CMNCTRL 2(Function ID: 5A0101)
Element ID Name Description
320000EF43 CHK_NMI_M MainCPU Monitoring Siganal1

320001EF43 CHK_ROMRAM_M MainCPU Monitoring Siganal2

320002EF43 CHK_SUM_M MainCPU Monitoring Siganal3

320003EF43 CHK_PROGRAM_M MainCPU Monitoring Siganal4

320004EF43 CHK_RAM_M MainCPU Monitoring Siganal5

320005EF43 CHK_ECC_M MainCPU Monitoring Siganal6

320006EF43 CHK_SAMPLING_M MainCPU Monitoring Siganal7

320007EF43 CHK_ACC1_M MainCPU Monitoring Siganal8

320008EF43 CHK_ACC2_M MainCPU Monitoring Siganal9

320009EF43 CHK_ACC3_M MainCPU Monitoring Siganal10

320010EF43 CHK_GOOSERCV_M MainCPU Monitoring Siganal11

320011EF43 CHK_PING1_M MainCPU Monitoring Siganal12

320012EF43 CHK_PING2_M MainCPU Monitoring Siganal13

320013EF43 CHK_CMLV_DAT_M MainCPU Monitoring Siganal14

800000EF40 PLC_BIT_0001 PLC event bit information 1

800001EF40 PLC_BIT_0002 PLC event bit information 2

800002EF40 PLC_BIT_0003 PLC event bit information 3

800003EF40 PLC_BIT_0004 PLC event bit information 4

800004EF40 PLC_BIT_0005 PLC event bit information 5

800005EF40 PLC_BIT_0006 PLC event bit information 6

800006EF40 PLC_BIT_0007 PLC event bit information 7

800007EF40 PLC_BIT_0008 PLC event bit information 8

800008EF40 PLC_BIT_0009 PLC event bit information 9

800009EF40 PLC_BIT_0010 PLC event bit information 10

…. …. ….

801398EF40 PLC_BIT_1399 PLC event bit information 1399

801399EF40 PLC_BIT_1400 PLC event bit information 1400

000000EF42 PLC_BOOL_1 PLC event bool information 1

000001EF42 PLC_BOOL_2 PLC event bool information 2

000002EF42 PLC_BOOL_3 PLC event bool information 3

000003EF42 PLC_BOOL_4 PLC event bool information 4

000004EF42 PLC_BOOL_5 PLC event bool information 5

000005EF42 PLC_BOOL_6 PLC event bool information 6

000006EF42 PLC_BOOL_7 PLC event bool information 7

000007EF42 PLC_BOOL_8 PLC event bool information 8

000008EF42 PLC_BOOL_9 PLC event bool information 9

000009EF42 PLC_BOOL_10 PLC event bool information 10

000010EF42 PLC_BOOL_11 PLC event bool information 11

000011EF42 PLC_BOOL_12 PLC event bool information 12

GRL200 (Soft 033 & 037)


- 564 -
6F2S1914 (0.37)

 PLC connection points


CMNCTRL 2(Function ID: 5A0101)
Element ID Name Description
000012EF42 PLC_BOOL_13 PLC event bool information 13

000013EF42 PLC_BOOL_14 PLC event bool information 14

000014EF42 PLC_BOOL_15 PLC event bool information 15

320014EF43 PLC_UINT32_15 PLC event uint32 information 15

320015EF43 PLC_UINT32_16 PLC event uint32 information 16

320016EF43 PLC_UINT32_17 PLC event uint32 information 17

320017EF43 PLC_UINT32_18 PLC event uint32 information 18

320018EF43 PLC_UINT32_19 PLC event uint32 information 19

320019EF43 PLC_UINT32_20 PLC event uint32 information 20

310000EF41 PLC_UINT_1 PLC event unit information 1

310001EF41 PLC_UINT_2 PLC event unit information 2

310002EF41 PLC_UINT_3 PLC event unit information 3

310003EF41 PLC_UINT_4 PLC event unit information 4

310004EF41 PLC_UINT_5 PLC event unit information 5

310005EF41 PLC_UINT_6 PLC event unit information 6

310006EF41 PLC_UINT_7 PLC event unit information 7

310007EF41 PLC_UINT_8 PLC event unit information 8

310008EF41 PLC_UINT_9 PLC event unit information 9

310009EF41 PLC_UINT_10 PLC event unit information 10

310010EF41 PLC_UINT_11 PLC event unit information 11

310011EF41 PLC_UINT_12 PLC event unit information 12

310012EF41 PLC_UINT_13 PLC event unit information 13

310013EF41 PLC_UINT_14 PLC event unit information 14

310014EF41 PLC_UINT_15 PLC event unit information 15

310015EF41 PLC_UINT_16 PLC event uint32 information 16

310016EF41 PLC_UINT_17 PLC event uint32 information 17

310017EF41 PLC_UINT_18 PLC event uint32 information 18

310018EF41 PLC_UINT_19 PLC event uint32 information 19

310019EF41 PLC_UINT_20 PLC event uint32 information 20

 PLC monitoring point


CMNCTRL 2(Function ID: 5A0101)
Element ID Name Description
0000001F42 PLC_O_BOOL_1 PLC event bool output 1

0000011F42 PLC_O_BOOL_2 PLC event bool output 2

0000021F42 PLC_O_BOOL_3 PLC event bool output 3

0000031F42 PLC_O_BOOL_4 PLC event bool output 4

0000041F42 PLC_O_BOOL_5 PLC event bool output 5

0000051F42 PLC_O_BOOL_6 PLC event bool output 6

0000061F42 PLC_O_BOOL_7 PLC event bool output 7

0000071F42 PLC_O_BOOL_8 PLC event bool output 8

0000081F42 PLC_O_BOOL_9 PLC event bool output 9

0000091F42 PLC_O_BOOL_10 PLC event bool output 10

0000101F42 PLC_O_BOOL_11 PLC event bool output 11

GRL200 (Soft 033 & 037)


- 565 -
6F2S1914 (0.37)

 PLC monitoring point


CMNCTRL 2(Function ID: 5A0101)
Element ID Name Description
0000111F42 PLC_O_BOOL_12 PLC event bool output 12

0000121F42 PLC_O_BOOL_13 PLC event bool output 13

0000131F42 PLC_O_BOOL_14 PLC event bool output 14

0000141F42 PLC_O_BOOL_15 PLC event bool output 15

8000001F40 PLC_O_BIT_001 PLC event bit output 1

8000011F40 PLC_O_BIT_002 PLC event bit output 2

8000021F40 PLC_O_BIT_003 PLC event bit output 3

8000031F40 PLC_O_BIT_004 PLC event bit output 4

8000041F40 PLC_O_BIT_005 PLC event bit output 5

8000051F40 PLC_O_BIT_006 PLC event bit output 6

8000061F40 PLC_O_BIT_007 PLC event bit output 7

8000071F40 PLC_O_BIT_008 PLC event bit output 8

8000081F40 PLC_O_BIT_009 PLC event bit output 9

8000091F40 PLC_O_BIT_010 PLC event bit output 10

…. …. ….

8013981F40 PLC_O_BIT_1399 PLC event bit output 1399

8013991F40 PLC_O_BIT_1400 PLC event bit output 1400

GRL200 (Soft 033 & 037)


- 566 -
6F2S1914 (0.37)

Local, remote and PLC control


The user can select either local or remote control by pressing the L│R key on the front
panel of the IED. Selection is executed within the LOCRMT function. Control logic is provided
by default, but the user can customize each application using the PLC function and PLC
connection points. Generally, the LOCRMT function is applied within all IEDs. Figure 3.5-1
shows the LOCRMT logic. Note that the LOCRMT function changes for the remote control
unconditionally if the operation/function keys on the front panel are not touched within 35
minutes in the local control.
From KEYINPUT function
LOCRMT function (Function ID: 530001) LRSW01_LR_ST
L/R CHG (530001 3109001001)
Remote to local S
(240001 31000A1735)
LRSW01_CH_LR_LCD & 1≥
R

Local to remote

&
1≥
If the user does not touch the
operation/function keys on the front panel &
within 35 min. in the local control, the IED
will be changed for the remote control
unconditionally.

530001 800901EDE0 LRSW01_PLC_SGN01


Disable default logic
530001 800901EDE1 LRSW01_PLC_SGN02
Users can fully customize logic by PLC.

Figure 3.5-1 LOCRMT logic

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.5-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 567 -
6F2S1914 (0.37)

3.5.1 Local control


Local control refers to control operation from the front panel of the IED. Either the DIR or the
SBO modes are available depending on the configuration selected by the user.

3.5.2 Remote control


Remote control refers to control operation from a remote control center or the SAS server.
Either the DIR or the SBO modes are available depending on the configuration selected by the
user. Note that the parameters used in the control commands are defined in international
standards†. The parameter details are provided in the communication profiles. See Chapter
Communication protocol or Appendices.

†Note:As a rule, the control commands have parameters. For example, the “Off to On”
and “On to Off” control directions that are used in commands are pre-configured
as parameters in the communication protocol. Note that the parameters vary
depending upon the respective protocol used, such as IEC61850 and others. For
IEC61850, Table 3.5-2 shows the parameters defined: the rule for control direction
can be found in “ctlVal”, the command publisher is recognized using the parameter
“origin”. For more information about the parameters, see Appendix IEC61850
MICS, PICS, PIXIT and TICS.

Table 3.5-2 Defined command parameters in IEC61850-7-2


Parameter Types Descriptions
ctlVal Control direction (On or Off)
origin Indicates the command publisher
ctlNum Sequential Number
T Time that the command is sent
Test Test information (Test/On)
Check Interlock synchronizing

3.5.3 Programmable logic control (PLC)


PLC function should be used in order that user can have preferred control schemes. The user
can find several connection points to control applications in the functions. Automatic sequence
control (ASEQ) function is required in order that the user-preferred control scheme will start,
as shown in Figure 3.5-2.

GRL200 (Soft 033 & 037)


- 568 -
6F2S1914 (0.37)

ASEQ User’s PLC SPOS User’s PLC DPOS


logic logic

PLC monitoring point PLC connection point

Figure 3.5-2 Example of user-preferred control scheme using PLC user logic
Note: The user-preferred control scheme implemented by users can only be operated in
the DIR mode.

3.5.4 Signal for Local/Remote control


Note: The user should note the meaning of the following references used in the column
“M/O” in Tables 1.4-2 to 1.4-4:
“O” means the signal is optional.
“M” means the user should map/set/configure the signal; otherwise, the user
may experience an operational failure if the default settings are used.
“N/A” means that the user cannot change the state of the signal.
Table 3.5-3 PLC connection point (Input point for LOCRMT)
Signal Number Signal Name Description M/O
240001 31000A1735 L/R CHG [L/R] key “push” N/A
530001 800901EDE0 LRSW01_PLC_SGN01 Disable condition by PLC O
530001 800901EDE1 LRSW01_PLC_SGN02 User configurable condition by PLC O

Table 3.5-4 Mapping points for LOCRMT


Signal Number Signal Name Description M/O
530001 3009011008 LRSW01_LR_ORCAT Mapping data for “originator” in IEC61850 N/A
530001 6A09011009 LRSW01_LR_ORIDENT Mapping data for “originator” in IEC61850 N/A

Table 3.5-5 PLC monitoring point (LOCRMT)


Signal Number Signal Name Description
530001 3109001001 LRSW01_LR_ST Local(T) / Remote(F) status (single bit expression)
530001 3009011001 LRSW01_LR_ST_RMT Local(0x80) / Remote(0x40) status (double bit expression)

GRL200 (Soft 033 & 037)


- 569 -
6F2S1914 (0.37)

3.5.5 Signal
 Signal monitoring points
LOCRMT_SW (Function ID: 530001)
Element ID Name Description
3109001001 LRSW01_LR_ST S43BCU state

3009011001 LRSW01_LR_ST_RMT S43BCU state for SAS

 Connection points in PLC logic


LOCRMT_SW (Function ID: 530001)
Element ID Name Description
800901EDE0 LRSW01_PLC_SGN01 PLC signal 1(PLC use)

800901EDE1 LRSW01_PLC_SGN02 PLC signal 2(change mode LOCAL or REMOTE)

GRL200 (Soft 033 & 037)


- 570 -
6F2S1914 (0.37)

LED reset function (LEDR)


The IED has a number of LEDs on the front panel. For example, a “TRIP” LED is provided as
an indicator for tripping operation. The status of the “TRIP” LED is maintained until the user
has been able to confirm that tripping was initiated by the IED; hence, by inspection the user
is able to reliably determine that the IED initiated tripping. The LED reset (LEDR) function
is furnished within the IED so that the following operations are available to reset the LED
status:
1 Pushing “CLEAR” key1
2 Operation by GR-TIEMS2
3 Operation by the SAS

1Note: For the operation, see Chapter User interface: Outline. Note that pressing the
“CLEAR” key causes the Reset of the LEDs.
2Note: For more information, see Chapter Engineering tool.

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.6-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 571 -
6F2S1914 (0.37)

3.6.1 Select logic for resetting LEDs


The user should set scheme switch [LEDDR1] to On prior to the LEDR operation. Figure 3.6-1
shows selection logic in the LEDR function.
Wait for a command

Wait for a next command


Select logic
Cancel logic

Resetting LED by remote-SAS Cancel command


Failed
Cancel logic
Signal reception Select
Selection logic Signal output
IEC61850 decision Success
Operate logic
Operate command

Operate logic

Figure 3.6-1 Outline of selection command for resetting LEDs

(i) Input signal required mapping


Figure 3.6-2 shows the select logic when a “Select command (reset)” signal is applied to the
LEDR function. The logic has an input-point “LEDR01_CONTROL_REQ” for the reception;
the input-point must be mapped for IEC61850 communication. The function will fail to operate
if mapping is not performed correctly. We will discuss how to map the input points for the
IEC61850 communication in section 3.6.5.

Input Selection logic in LEDR Output

LEDR function (Function ID: 528001)


LEDR01_FSE_RCV
Command “Reset”
For SBO operation (528001 8007011F42)
528001 7007016D08 LEDR01_CONTROL_REQ Selection
command & 1≥
&
For DIR operation
Operation
command &
LEDR01_NSD_CSF
To “Wait for a next command”
(528001 8307011F41)
0 t
528001 0007011001 LEDR01_STSELD
0.2s

0 t
Failed
0.3s

Either “SBO mode” or “DIR mode” In SBO operation


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function
(AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 3.6-2 Selection logic for resetting LEDs


‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 3.6-8.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals
for automatic control. The LEDR function is blocked for the ASEQ function when
it is in operation. For more information of the ASEQ function, see Chapter Control

GRL200 (Soft 033 & 037)


- 572 -
6F2S1914 (0.37)

and monitoring application: Automatic sequence control function.


*Note:The LEDR function can run on either “the SBO mode” or “the DIR mode” using a
“ctlmodel” signal when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.

(ii) Output signal required mapping


The LEDR function can issue a “Select success” signal at the output point
“LEDR01_NSD_CSF”, when the LEDR function determines that the input signal “Select
command (reset)” is true. If the LEDR function determines that the “LEDR01_NSD_CSF” is
not true, the LEDR function returns to the “Wait for a next command” stage.

(iii) Select condition


Figure 3.6-3 shows the select condition logic in the LEDR function.
LEDR function (Function ID: 528001)
Command blocking*1 (S4301 defines ”Blocked”)
S4301_STATE To selection logic
1≥ & Select condition
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR Unmatched condition detected *4

Function “Automatic sequence control” is in progress


ASEQ_MULTI_SEL

Users must setup this condition correctly


Control hierarchy (e.g. 43RL) (PLC connection point) *5
528001 820701ED50 LEDR01_CTRL_RIGHT
&
IED serious error detected
SERI_ERR

[LEDDR1_EN]

On

Figure 3.6-3 Select condition logic in LEDR*6


*1Note: “command blocking” disables any operation except its own: the “command
blocking” is initiated by the status of “S4301” in a software controller (SOFTSW).
The IEC 61850 standard defines “command blocking” as “CmdBlk”. For more
information on S4301, see Chapter Control and monitoring application: Software
switch control function. See the signal “S4301_STATE” of Table 3.6-2.
*2Note: “Double Command Blocking (DCB)” is an operation philosophy in the
common control function (CMNCTRL). It can be used to protect the substation.
The user can program it using GR-TIEMS. The DCB operating signal is denoted
as “DCB RCV_OR in Table 3.6-2. For more information, see Chapter Control and
monitoring application: Common controls.
*3Note: If the event “device-travelling” is detected in the CMNCTRL function, it
indicates that another operator is changing the status of a device. Thus, the IED
should inhibit the operation of any device for the duration that the event is

GRL200 (Soft 033 & 037)


- 573 -
6F2S1914 (0.37)

detected. The detecting signal is denoted as “Traveling OR” in Table 3.6-2.


*4Note: Criteria “unmatched conditions” are decided when the “Test-bit status” in a
command is not identical to the “IED test status”.
*5Note: The user needs to program the PLC logic “Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection point “LEDR01_CTRL_RIGHT”. For more information, see
chapter Control and monitoring application: Control hierarchy.
“LEDR01_CTRL_RIGHT” is provided in Table 3.6-3.
*6Note: To identify the input point of the LEDR function, see Table 3.6-2.

Table 3.6-2 Input signals for condition logic


Signal Number Signal Name Description M/O
522001 000A011001 S4301_STATE Command Blocking status ( Off / Blocked) N/A
5A0001 0008001F41 DCB RCV OR Double Command Blocking(DCB) is in progress. N/A
5A0001 0008001F40 Traveling OR Travelling events are detected. N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A
523001 000D001F40 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A

Table 3.6-3 PLC connection point (Input point on select condition logic)
Signal Number Signal Name Description M/O
528001 820701ED50 LEDR01_CTRL_RIGHT LED Reset control hierarchy M

Table 3.6-4 Setting of LEDR


Setting Name Description Default Setting item or value
LEDDR1_EN Activate LED reset control On Off / On

GRL200 (Soft 033 & 037)


- 574 -
6F2S1914 (0.37)

3.6.2 Cancel logic in SBO mode


In the SBO mode the reception of a cancel command is possible when the cancel conditions are
satisfied. Accordingly, the function can discard the select command; finally, the operation
returns to the initial stage (i.e., “Wait for a command”.)

(i) Receiving “Cancel” from the remote-end


Figure 3.6-4 depicts the cancel command procedure for a cancel command initiated from the
remote-end.

Wait for a command

Select logic Wait for a next command

Cancel by the remote-end


Success

Command Reset from the Signal reception in Cancel


Cancel logic Do nothing
remote-end IEC61850 decision Failed

Operate logic
Operate command

Operate logic

Figure 3.6-4 Outline of ‘cancel’ command from the remote-end

(ii) Input signal required mapping


Figure 3.6-6 depicts the cancel logic when a “Cancel command (Remote-Cancel)” signal is
applied to the LEDR function. The input-point “LEDR01_CONTROL_REQ” is the same the
same as that for the signal as shown in Figure 3.6-2.
510001 7001016D08

Input Cancel logic in LEDR Output

LEDR function (Function ID: 528001)


Command “Cancel”
Cancel command
528001 7007016D08 LEDR01_CONTROL_REQ
&

Unmatched condition To “Wait for a command”


detected† &
Successes to cancel

“Do nothing”
Operation Failed

Figure 3.6-5 ‘Cancel’ from the remote-end


†Note:The criteria “unmatched conditions” are determined when the “Test-bit status” in
a command is not identical to the “IED test status”.

GRL200 (Soft 033 & 037)


- 575 -
6F2S1914 (0.37)

3.6.3 Operate logic for SBO/DIR mode


Once the operation of the select logic is completed, the operate logic is applied to reset LEDs.
Resetting LEDs is executed when the operate conditions are satisfied.

Wait for a command

Select logic Wait for a next command

LED resetting by the remote-end


LED resetting from the Success
Operation
remote-end Signal reception in Operate logic Resetting LEDs
decision
IEC61850

Failed Do nothing

LED resetting by the local-end


Success
Operation
Pushing “CLEAR” key Operate logic Resetting LEDs
decision

Failed Do nothing

Cancel logic

Cancel command

Cancel logic

Figure 3.6-6 Outline of operation command for resetting LEDs


†Note: For more information, see Chapter User interface: Outline.

(i) Mapping required Input signal


Figure 3.6-7 illustrates the operate logic when an “Operation command (reset)” signal is
applied to the LEDR function. The input-point “LEDR_CONTROL_REQ” is used for the
reception of the “Operation command (reset)” signal. Pressing “CLEAR” key or the operation
on GR-TIEMS will reset LEDs.
Input Select logic in LEDR Output

LEDR function (Function ID: 528001) To LED3–LED26†


Command “Operating reset”
Operation
528001 7007016D08 LEDR01_CONTROL_REQ 528001 3107011EA1 LED_RST_CMD
command & ≥

Operate condition‡
“Automatic sequence control function (AQEQ)§”
in progress
ASEQ_MULTI_SEL

From KEYINPUT

240001 31000E1730
LEDR_KEY_CLEAR
CLEAR

From TOOL_COM (GR-TIMES) 1≥


201501 3101001001
LEDR_TOOL_CLEAR
LED_RESET_TOOL

Figure 3.6-7 Operation logic for resetting LEDs

(ii) Output signal required mapping


The operation logic issues a “LED_RST_COM” signal to clear the LEDs†. The signal
“LED_RST_COM” is also transferred to the remote-end, when signal mapping is executed in
IEC61850 communication. (See section 3.6.5)

GRL200 (Soft 033 & 037)


- 576 -
6F2S1914 (0.37)

†Note:Although the “LED_RST_COM” signal is connected previously with several LEDs,


by the manufacturer, user can also connect the signal with the LEDs. See section
3.6.4 for how to connect.

(iii) Operate condition


Figure 3.6-8 shows the operate condition logic of the LEDR function, which is used to determine
a reset-condition for the operation.
LEDR function (Function ID: 528001)
Command blocking*1 (S4301 defines ”Blocked”)
S4301_STATE To operate logic
1≥ & Operate condition
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR Unmatched condition detected *4

Function “Automatic sequence control” is in progress


ASEQ_MULTI_SEL
Users must setup this condition correctly
Control hierarchy (e.g. 43RL) (PLC connection point) *5
528001 820701ED50 LEDR01_CTRL_RIGHT
&
IED serious error detected
SERI_ERR

[LEDDR1_EN]

On

Figure 3.6-8 Operate condition logic in LEDR*6


*1Note: “Command blocking” disables all operation except for its own: the “command
blocking” function is initiated by the status of “S4301” in a software controller
(SOFTSW). The IEC 61850 standard defines the “command blocking” function as
“CmdBlk”. For more information on S4301, see Chapter Control and monitoring
application: Software switch control function. See the signal “S4301_STATE” of
Table 3.6-2.
*2Note: “Double Command Blocking (DCB)” is an operation philosophy in the
common control function (CMNCTRL). It can be used to protect the substation.
The user can program it using GR-TIEMS. The DCB operating signal is denoted
as “DCB RCV_OR in Table 3.6-2. For more information, see Chapter Control and
monitoring application: Common controls.
*3Note: If the event “device-travelling” is detected in the CMNCTRL function, it
indicates that another operator is changing the status of a device. Thus, the IED
should inhibit the operation of any device for the duration that the event is
detected. The detecting signal is denoted as “Traveling OR” in Table 3.6-2.
*4Note: Criteria “unmatched conditions” are decided when the “Test-bit status” in a
command is not identical to the “IED test status”.
*5Note: The user must program the PLC logic for “Control hierarchy condition”. The
user must connect that to the select condition logic using the connection point
“LEDR01_CTRL_RIGHT”. For more information, see chapter Control and

GRL200 (Soft 033 & 037)


- 577 -
6F2S1914 (0.37)

monitoring application: Control hierarchy. “LEDR01_CTRL_RIGHT” is provided


in Table 3.6-3.

3.6.4 Settings in LED logics


The user can program the status and the signal of the LED, so that the LEDs are possible to
switch off upon occurrence of the reset. As shown in the logic relating to the LED†, each logic
has a timer and a setting; accordingly, setting Latch should be set for the operation of the
LEDR function. Additionally, the user should connect the signal LED_RST_CMD with the LED
logic.
†Note:For more information on LED logics, see Chapter Technical description: Human
machine interface: LED indicators.

(i) Settings using GR-TIEMS


Figure 3.6-9 shows how to connect the reset signal LED_RST_CMD for the LED-03 logic. The
user can assign a reset signal for the respective LED logics by the drag and drop operation.
The user should also select Latch for the behavior from the pull-down menu.

Set [Behavior] to Latch


Choose the signal
LED_RST_CMD for the
LED-03 logic

Figure 3.6-9 Settings for LED-03 circuit provided by “Setting I/O menu” of GR-TIEMS

(ii) Settings using IED screen


The operation from the IED screen can also be set. See Chapter User interface: I/O setting sub-
menu.

GRL200 (Soft 033 & 037)


- 578 -
6F2S1914 (0.37)

3.6.5 Mapping for IEC61850 communication


The user can operate the LEDR function over IEC 61850 communication following mapping
using GR-TIEMS. Note that the LEDR function is designed for “LEDRs” in the IEC 61850
standard for communication. The user should follow these steps, each of which is discussed
below:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user will need to create a logical node (LN) for the LEDR function. Figure 3.6-10
exemplifies the editing of a LN; the LN “logical node zero (LLN0)” is chosen for the LERD
function. Either the SBO mode or the DIR mode should be chosen in the editing for the LN.

SBO defined in LN

Figure 3.6-10 Defining “LEDRs” object in LLN0 logic node

Defining SBO mode


Figure 3.6-11 exemplifies the LEDR logic node saved as “LLN0”. In the SBO mode, the user
should select the following items in the “LLN0$LEDRs” using GR-TIEMS:

GRL200 (Soft 033 & 037)


- 579 -
6F2S1914 (0.37)

 SBOw
 Oper
 Cancel
 Origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.

Figure 3.6-11 LN editing for SBO mode (for example)

Defining DIR mode


Figure 3.6-12 exemplifies the LEDR logic node saved as LLN0. In the DIR mode, the following
three items should be selected using GR-TIEMS:

 Oper
 origin
 ctlmodel (choice ”DOes or DOns” )

Figure 3.6-12 LN editing for DIR mode (for example)

(ii) Mapping output data


The user should group the LEDR signals with regard to GOOSE and Report; the user should
map them for IEC61850 communication using GR-TIEMS. Figure 3.6-13 illustrates how to
map a signal for IEC61850 communication; it indicates that the signals for the LEDR function

GRL200 (Soft 033 & 037)


- 580 -
6F2S1914 (0.37)

are required to be mapped for IEC 61850 communication


Table 3.6-5 Mapping signals for SPC object
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/LLN0$LEDRs$origin orCat orCategory ST 5280013107011008 LEDR01_ORCAT
Ctrl/LLN0$LEDRs$origin orIdent Octet64 ST 5280016A07011009 LEDR01_ORIDENT
Ctrl/LLN0$LEDRs stVal BOOLEAN ST 5280013107011EA1 LED_RST_CMD
Ctrl/LLN0$LEDRs q Quality ST 3010013110041005 Qual_Val
Ctrl/LLN0$LEDRs t Timestamp ST 2003019010001006 SYS_TIME
Ctrl/LLN0$LEDRs stSeld BOOLEAN ST 5280010007011001 LEDR01_STSELD

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850.

Figure 3.6-13 orCat attribute mapped for LEDRs object of LLN0

(iii) Mapping input data


The LEDR function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “LED01_CONTROL_REQ” to the IEC61850 communication. Table
3.6-6 shows the input-point “LED01_CONTROL_REQ” and the Object reference
“Ctrl/LLN0$LEDRs”; the user should map the input-point to the Object references having
attributes CO and CF†. Figure 3.6-14 shows how to map a signal.
†Note: The attribute is defined in the IEC 61850; “CO” stands for “Control” and “CF”
stands for “Configuration” in the functional constraint (FC).

GRL200 (Soft 033 & 037)


- 581 -
6F2S1914 (0.37)

Table 3.6-6 Mapping signals required for LEDRs object for LLN0
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/LLN0$LEDRs$Oper ctlVal BOOLEAN CO
Ctrl/LLN0$LEDRs$Oper ctlNum INT8U CO
Ctrl/LLN0$LEDRs$Oper T Timestamp CO
Ctrl/LLN0$LEDRs$Oper Test BOOLEAN CO
Ctrl/LLN0$LEDRs$Oper Check Check CO 5280017007016D08 LEDR01_CONTROL_REQ
Ctrl/LLN0$LEDRs$Oper$origin orCat orCategory CO
Ctrl/LLN0$LEDRs$Oper$origin orIdent Octet64 CO
Ctrl/LLN0$LEDRs ctlModel ctlModel CF
Ctrl/LLN0$LEDRs sboClass sboClass CF

Drag and drop

Figure 3.6-14 Input-point mapped for LLN0

GRL200 (Soft 033 & 037)


- 582 -
6F2S1914 (0.37)

3.6.6 Setting
Reset Control (Function ID: 528001)
Setting items Range Unit Contents Default Note

LEDDR1-EN Off / On - LEDR01 Reset Control Enable Off

GRL200 (Soft 033 & 037)


- 583 -
6F2S1914 (0.37)

3.6.7 Signal
 Signal monitoring points
TLEDRSTCTRL (Function ID: 528001)
Element ID Name Description
8007011D53 LEDR01_SC Select command

0007011001 LEDR01_STSELD The controllable data is in the status selected (StSeld)

3107011EA1 LED_RST_CMD LEDR reset command output

8007011D57 LEDR01_EC Execute command

8007011D55 LEDR01_EC_OWS Execute command by OWS(HMI)

8007011D56 LEDR01_EC_RCC Execute command by RCC

8007011D51 LEDR01_SC_OWS Select command by OWS(HMI)

8007011D52 LEDR01_SC_RCC Select command by RCC

8E07011F47 LEDR01_SLD_TM0 Signal after MCTLEDR_SC001

8607011F46 LEDR01_SLF_FCT_FLG1 Signal before MCTLEDR_SC001

8307011F41 LEDR01_NSD_CSF Signal after KC_LEDR_SA001

8607011F45 LEDR01_TMP3 Signal after KC_LEDR_SC001

8007011F42 LEDR01_FSE_RCV Signal before LC_LEDR_SA002

8B07011F44 LEDR01_CTR_SGU Signal before KC_LEDR_SC001

8207011F40 LEDR01_TMP1 Signal before KC_LEDR_SA001

8707011F48 LEDR01_SLF_FCT_FLG2 Signal before MCTLEDR_SC002

8F07011F49 LEDR01_EX_CMP_TM0 Signal after MCTLEDR_SC002

8607011F43 LEDR01_TMP2 Signal after KC_LEDR_SA002

 Connection point in PLC logic


TLEDRSTCTRL (Function ID: 528001)
Element ID Name Description
820701ED50 LEDR01_CTRL_RIGHT LEDR01 control right from PLC

 Mapping point
TLEDRSTCTRL (Function ID: 528001)
Element ID Name Description
7007016D08 LEDR01_CONTROL_REQ Dev01 control request

GRL200 (Soft 033 & 037)


- 584 -
6F2S1914 (0.37)

Counter function for the general (GCNT)


When a signal is generated and it is received by the generic counter function (GCNT), the
GCNT function can count the transition of signals. For example, as shown in Figure 3.7-1, a
signal is issued repeatedly and if it is required that the number of signals is reported, the
GCNT function is able to count the number of signal transitions and report them. When an
object is in a device state, a binary input-circuit (BI) is provided to receive the signal.

Closed/Open signals
GCNT01_CNT_VAL
Inputs 320E011D20
Changes in device status
(e.g., operations of 43S) BI 540001 800E01EDE0 GCNT01_PLC_SGNL GCNT01

Operations at the local or Control commands GCNT06_CNT_VAL


remote-end 320E061D20
540001 800E06EDE0 GCNT06_PLC_SGNL GCNT06
(e.g., issuing commands)

Changes in a function Status signals GCNT32_CNT_VAL


status 320E201D20
(e.g., function operations)
540001 800E20EDE0 GCNT32_PLC_SGNL
GCNT32

Count objects Signals generated GCNT functions

Figure 3.7-1 Reception of signals at the GCNT functions

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.7-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features ✓ ✓
– Number of counters 32 32
✓: Applicable NA: Not applicable

Signal acquisition timing must be adjusted in accordance with the application, in that the
acquisition should be regulated for the nature of the signal; hence, several settings are

GRL200 (Soft 033 & 037)


- 585 -
6F2S1914 (0.37)

provided in the GCNT functions. Thirty-two independent GCNT counters† are available. That
is, counters GCNT01 to GCNT32† can operate simultaneously. The values counted are stored
in the non-volatile memory so that they are not erased if the power supply to the IED is
interrupted.

For simplicity, only the GCNT01 function is discussed; the features in the remaining GCNT02–
GCNT32 functions are identical to the GCNT01 function.

3.7.1 Counter setting for a signal


(i) Setting for count timing
In the GCNT01 function count timing is grouped into three, as shown in Figure 3.7-2 (a, b, and
c). When the user wishes to count the On(Closed), set On for the scheme switch [GCNT01-
CNTS]; conversely, set Off for the scheme switch when the Off(Open) is to be counted.
Additionally, OnOff is provided for counting the number of pulses. If the GCNT01 function is
not required, set NA for the scheme switch.

a. On (Closed) signals

“On” is counted on the rising edge of the pulse

Counter 1 2 … n …

b. Off (Open) signals

“Off” is counted on the falling edge of the pulse

Counter 1 2 … n …

c. OnOff (Closed-Open) signals

“OnOff” is counted in response to pulses.

Counter 1 2 … n …

Figure 3.7-2 Count types

(ii) Setting the maximum value


The GCNT01 function is able to count to 2147483647 (=231−1). When the count-value reaches
the value “2147483647”, the count-value returns to an initial-value. If the user wishes to set a
different maximum number in place of “2147483647”, the user can use the setting [GCNT01-
CNTMAX] and set a user-preferred value. Note that the user can set the maximum number
from 9 to 2147483647.

GRL200 (Soft 033 & 037)


- 586 -
6F2S1914 (0.37)

(iii) Setting the initial-value


The counter returns to an initial-value when the counter reaches the maximum value;
generally, the initial-value is set to either zero or one (0 or 1); hence, the number is re-counted
from either “0 (or 1)” following the maximum value. If the user wishes to set an alternative
initial number, setting [GCNT01-CNTRV] can be used. Note that the user can select the initial-
value from zero (0) to 999999.

Counter

Max set by [GCNT01-CNTMAX]

Initial-value set by [GCNT01-CNTRV]


0
Time

Figure 3.7-3 Maximum-value and initial-value

(iv) Setting for the report (Dead band)


The counter-value can be reported to the remote-end; the user can set the report-timing using
the setting [GCNT01-SDB]. For example, if the counter-value is to be reported for every change,
the user should set 0 for the setting [GCNT01-SDB]. When five(5) is set for the [GCNT01-SDB],
reporting is performed when the counter has incremented by six(6) following the previously
reported counter-value.

Counter Counter Counter

10 10 10

5 5 5

0 Time 0 Time 0 Time

Reporting………………. Reporting Reporting………………. Reporting Reporting Reporting

a. 0 set for [GCNT01-SDB] b. 1 set for [GCNT01-SDB] c. 5 set for [GCNT01-SDB]

Figure 3.7-4 Counter value and report timing

GRL200 (Soft 033 & 037)


- 587 -
6F2S1914 (0.37)

3.7.2 Select logics for SBO/DIR modes


The user should set scheme switch [GCNT01-EN] to On prior to counting.

(i) Receiving “Select command Reset” from the remote-end


Figure 3.7-5 outlines the reception of the Select command ‘Reset’ from the remote-end.
Wait for a command

Select stage Wait for a next command

Select command Reset from the remote-end Cancel logic


Failed

Signal Cancel command


Select
reception Select logic Signal output
decision Success
IEC61850
Cancel logic

Operate logic
Operate command

Operate logic

Figure 3.7-5 Outline of Select command ‘Reset’

Input point required mapping


Figure 3.7-6 shows the select logic when a “Select command Reset (Remote-Reset-Control)”
signal is applied to the GCNT01 function. The logic has an input-point “GCNT01_CMM_REQ”
for the reception of the select command. That is, the input-point must be mapped for IEC61850
communication. The function will fail to operate if mapping is not performed correctly. We will
discuss how to map the input-points for IEC61850 communication in section 3.7.5.

Output signal to BO
The GCNT01 function can issue a “Complete” signal at the output point
“GCNT01_SLD_CSCN”, when the GCNT01 function determines that the input signal
“Remote-Reset-Control” is true. If the GCNT01 function determines that the “Remote-Reset-
Control” is not true, the GCNTS01 function returns to the “Wait for a command” stage.

GRL200 (Soft 033 & 037)


- 588 -
6F2S1914 (0.37)

Input Select logic in GCNT01 Output

GCNT01 function (Function ID: 54001)


Command “Remote-Reset-Control”
For SBO operation
540001 700E016D09 GCNT01_CMM_REQ Select command
& 1≥ &
To “Wait for a next
For DIR operation command”
To BO connection
Operate command
& “GCNT01_SLD_CSCN”
(540001 8A0E011E76)

Either “SBO mode” or “DIR mode” 0 t


In SBO operate Complete
(e.g., “ctlmodel” in IEC61850*)
0.2s
In DIR operate
To “Wait for a command”
“GCNT01_SLF_CSCN”
Select condition‡ (540001 8B0E011E7B)
“Automatic sequence control function (AQEQ)§” in progress 0 t
Select “Failed”
ASEQ_MULTI_SEL
0.3s

Figure 3.7-6 Select ‘Reset’ in GCNT01††


‡Note:A “select condition” signal is provided from the select condition logic. For more
information, see Figure 3.7-7.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The GCNT01 operation is blocked for the ASEQ function when
it is in operation. For more information on the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
*Note:The GNCT01 function can run in either the “SBO mode” or the “DIR mode” using
a signal called “ctlmodel” when communication is implemented using IEC61850.
To use this signal, the user should map it for IEC61850 communication.
††Note: To identify the input and output points of the other GCNT02–GCNT32 logics, see
Table 3.7-2 for the inputs and Table 3.7-5 for the outputs.

GRL200 (Soft 033 & 037)


- 589 -
6F2S1914 (0.37)

(ii) Select condition


Figure 3.7-8 shows the select condition logic in the GCNT01 function. The GCNT01 function
checks the condition for the select command using the signal “S4301_STATE” and other signals.
When resetting the counter is performed from the “Statics sub-menu” in the HMI operation†,
the user should set On for scheme switch [GCNT01-HMI].
†Note: The HMI operation is discussed in Chapter User interface: Monitoring sub-menu.

From SOTFSW*1 GCNT01 function (Function ID: 540001)


Command blocking*1(S4301 defines ”Blocked”)
S4301_STATE To select logic
1≥ & Select condition
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR Unmatched condition detected *4

Function “Automatic sequence control” is in progress


ASEQ_MULTI_SEL
From Control hierarchy *5

540001 800E00ED5A GCNT00IN_TMP_51


&
From CMNCTRL
Serious error detection
SERI_ERR

[GCNT01-HMI]

On

[DPOS01-EN]

On

Figure 3.7-7 Select condition logic for Reset in GCNT01


1Note: “Command blocking” disables any operation except its own; the “command
blocking” is initiated by the status of “S4301” in a software switch controller
function (SOFTSW). The IEC 61850 standard defines “Command Blocking” as
“CmdBlk”. For more information on “S4301”, see Chapter Control and monitoring
application: Software switch control function. (Table 3.7-3)
2Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCB OR” in Table 3.7-3.
3Note: If the event “device-travelling” is detected, it indicates that another operator is
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detected signal is denoted
as “Traveling OR” in Table 3.7-3.
4Note: Criteria “unmatched conditions” are decided when the “Test-bit status” in a
command is not identical to the “IED test status”.
5Note: The user will need to program the PLC logic “Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection pint “GCNT00IN_TMP_51” (see Table 3.7-4). For more
information, see Chapter Control and monitoring application: Control hierarchy .

GRL200 (Soft 033 & 037)


- 590 -
6F2S1914 (0.37)

(iii) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicates that the signal is provided for optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” indicates that the user cannot change the state of the signal.
Table 3.7-2 Mapping points for the reception of control command
Signal Number Signal Name Description M/O
540001 700E016D09 GCNT01_CMM_REQ GCNT01 control request(Mapping data) M
540001 700E026D09 GCNT02_CMM_REQ GCNT02 control request(Mapping data) M
540001 700E036D09 GCNT03_CMM_REQ GCNT03 control request(Mapping data) M
… … …
540001 700E206D09 GCNT32_CMM_REQ GCNT32 control request(Mapping data) M

Table 3.7-3 Input signals to condition logic


Signal Number Signal Name Description M/O
522001 000A011001 S4301_STATE Command Blocking status ( Off / Blocked) N/A
523001 000D001F40 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A
5A0001 0008001F41 DCB RCV OR Double Command Blocking(DCB) is in progress. N/A
5A0001 0008001F40 Traveling OR Travelling events are detected. N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A

Table 3.7-4 PLC Connection point (Input signals from the control hierarchy logic)
Signal Number Signal Name Description M/O
540001 800E00ED5A GCNT00IN_TMP_51 Control hierarchy for GCNT01–32 M

Table 3.7-5 PLC Monitoring points (Signal “select complete/ failed” for BIO)
Signal Number Signal Name Description
540001 8A0E011E76 GCNT01_SLD_CSCN GCNT01 Selection completed (Mapping)
540001 8A0E021E76 GCNT02_SLD_CSCN GCNT02 Selection completed (Mapping)
540001 8A0E031E76 GCNT03_SLD_CSCN GCNT03 Selection completed (Mapping)
… … …
540001 8A0E201E76 GCNT32_SLD_CSCN GCNT32 Selection completed (Mapping)
5400018B0E011E7B GCNT01_SLF_CSCN GCNT01 select failed
5400018B0E021E7B GCNT02_SLF_CSCN GCNT02 select failed
5400018B0E031E7B GCNT03_SLF_CSCN GCNT03 select failed
…. … …
5400018B0E201E7B GCNT32_SLF_CSCN GCNT32 select failed

Table 3.7-6 PLC Monitoring points (Signal “stSeld” for BIO)


Signal Number Signal Name Description
540001 000E011D91 GCNT01_TMP_01 GCNT01 count change selected signal(stSeld) for SAS
540001 000E021D91 GCNT02_TMP_01 GCNT02 count change selected signal(stSeld) for SAS
540001 000E031D91 GCNT03_TMP_01 GCNT03 count change selected signal(stSeld) for SAS

GRL200 (Soft 033 & 037)


- 591 -
6F2S1914 (0.37)

Signal Number Signal Name Description


540001 000E041D91 GCNT04_TMP_01 GCNT04 count change selected signal(stSeld) for SAS
… … …
540001 000E201D91 GCNT32_TMP_01 GCNT32 count change selected signal(stSeld) for SAS

(iv) Setting names

Table 3.7-7 Settings of select logics for GCNT01 to GCNT32


Setting Name Description Default Setting item or value
GCNTxx-EN Activation of the GCNTxx function On Off / On
GCNTxx- Counter is used for the HMI operation in the GCNTxx function Off Off / On
HMI

GRL200 (Soft 033 & 037)


- 592 -
6F2S1914 (0.37)

3.7.3 Cancel logic for SBO mode


In the SBO control mode the reception of a cancel command is possible when the cancel
conditions are satisfied; accordingly, the function can discard the select command; finally, the
operation returns to the initial stage (i.e., “Wait for a command”.)

(i) Receiving “Cancel” from the remote-end


Figure 3.7-8 depicts the cancel command procedure for a cancel command initiated from the
remote-end.

Wait for a command

Select logics Wait for a next command

Cancel from the remote-end


Select command Success
Reset from the
Signal reception Cancel
remote-end Cancel logic Do nothing
in IEC61850 decision Failed

Operate logic
Operate command

Operate logic

Figure 3.7-8 Outline of ‘cancel’ command from the remote-end

Input point required mapping


Figure 3.7-9 depicts the cancel logic when a “Cancel command (Remote-Cancel)” signal is
applied to the GCNT01 function. The input-point “GCNT01_CMM_REQ” is the same as that
for the signal “Select command Reset (Remote-Reset-Control)”.

Output signal to BO
The GCNT01 function can issue a “Success to cancel” signal at the monitoring point
“GCNT01_CC_SSCN”, when the GCNT01 function has determined that the signal “Remote-
cancel” is true. Another signal “Operation failed” is issued if the function is able to determine
that the signal “Remote-cancel” is not true.
Input Cancel logic in GCNT01 Output

GCNT01 function (Function ID: 540001) To “Wait for a command”


Command “Remote-cancel”
“GCNT01_CC_SSCN”
Cancel command
540001 700E016D09 GCNT01_CMM_REQ (540001 840E011E95)
&
Successes to cancel

Unmatched condition detected *1 &

“Do nothing”
Operation Failed

Figure 3.7-9 ‘Cancel’ from the remote-end in GCNT01


1Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in

GRL200 (Soft 033 & 037)


- 593 -
6F2S1914 (0.37)

a command is not identical to the “IED test status”.

(ii) Signal name and number


Table 3.7-8 PLC monitoring points (Output signal for ‘cancel’ logic)
Signal Number Signal Name Description
540001 840E011E95 GCNT01_CC_SSCN GCNT01 cancel success signal
540001 840E021E95 GCNT02_CC_SSCN GCNT02 cancel success signal
540001 840E031E95 GCNT03_CC_SSCN GCNT03 cancel success signal
… … …
540001 840E201E95 GCNT32_CC_SSCN GCNT32 cancel success signal

GRL200 (Soft 033 & 037)


- 594 -
6F2S1914 (0.37)

3.7.4 Operate logic for SBO/DIR modes


After the operation of the select logic, the operate logic starts to clear the counters.

(i) Receiving “Operate command Reset” from the remote-end


Figure 3.7-10 depicts the reception of the operate command ‘Reset’ from the remote-end.

Wait for a command

Select stage Wait for a next command

Select command Operate command Reset from the remote-end


Success
Reset from the Operation
Signal reception Operate logic Signal output
remote-end decision
in the IEC61850

Failed Do nothing

Operate command Reset from the local-end


Success
Operation
Signal reception Operate logic Signal output
decision
from
the front panel
Failed Do nothing

Figure 3.7-10 Outline of Operate command ‘Reset’

Mapping required for Input point


Figure 3.7-11 illustrates the operation logic when an “Operate command Reset (Remote-Reset-
Control)” signal is applied to the GCNT01 function. The input-point “GCNT01_CMM_REQ” is
used for the reception of the “Operate command Reset (Remote-Reset-Control)”.

Output signal to BO
The GCNT01 function, in Figure 3.7-11, can provide a signal at the point “GCNT01_OK_CSC”,
when the GCNT01 function determines that the signal “Remote-Reset-Control” is true.
Input Operate logic in GCNT01 Output

GCNT01 function (Function ID: 540001) “GCNT01_EC_OK_CSC”


Command “Remote-Reset-Control” (540001 820E011E84)
Operate Cmd.
540001 700E016D09 GCNT01_CMM_REQ
& 1≥

Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL

Statics-counter

Figure 3.7-11 Operate ‘On’ from the remote-end ††


§Note:The ASEQ function can provide sequential signals for automatic control.
††Note: To identify the input and output signal-points of the GCNT02–32 logics, see Table
3.7-2 for the mapping points, Table 3.7-9 for the outputs.

(ii) Receiving “Operate command Reset” from the local-end


Figure 3.7-12 depicts the reception of the operate command ‘Reset’ from the local-end.

GRL200 (Soft 033 & 037)


- 595 -
6F2S1914 (0.37)

Wait for a command

Select stage Wait for a next command

Select command Operate command Reset from the remote-end


Success
Reset from the Operation
Signal reception Operate logic Signal output
remote-end decision
in the IEC61850

Failed Do nothing

Operate command Reset from the local-end


Success
Operation
Signal reception Operate logic Signal output
decision
from
the front panel
Failed Do nothing

Figure 3.7-12 Outline of Operate command ‘Reset’

New counter value


Figure 3.7-13 shows that the user can set a new value for the counter using the statics sub-
menu†. The new value is applied into “Statics counter” point in Figure 3.7-11.

Counter
10:48 1/8
COUNT1 (No Assign) +
0
COUNT2 (No Assign) +
0
COUNT3 (No Assign) +
0

Figure 3.7-13 Counter menu in the statics sub-menu


†Note: For the operation, see Chapter User interface: Monitoring sub-menu.

Output signal to BO
The GCNT01 function can provide a signal at the point “GCNT01_OK_CSC”, when the new
value applied from the sub-menu is appropriate.

GRL200 (Soft 033 & 037)


- 596 -
6F2S1914 (0.37)

(iii) Select condition


Similar to the select condition (see sec.3.7.2(ii)), the GCNT01 function has an operate-condition
logic. Figure 3.7-14 shows the operate-condition logic.
From SOTFSW*1 GCNT01 function (Function ID: 540001)
Command blocking*1(S4301 defines ”Blocked”)
S4301_STATE To operate logic
1≥ & Operate condition
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR Unmatched condition detected *4

Function “Automatic sequence control” is in progress


ASEQ_MULTI_SEL
From Control hierarchy *5

540001 800E00ED5A GCNT00IN_TMP_51


&
From CMNCTRL
Serious error detection
SERI_ERR

[GCNT01-HMI]

On

[DPOS01-EN]

On

Figure 3.7-14 Operate condition logic for GCNT01


1–5Note: The signals and settings in Figure 3.7-14 are same as the signals shown in
Figure 3.7-7.

(iv) Signal names and number


Table 3.7-9 PLC monitoring points (Output signal for BIO)
Signal Number Signal Name Description
540001 820E011E84 GCNT01_EC_OK_CSCN GCNT01 execute command OK condition signal
540001 820E021E84 GCNT02_EC_OK_CSCN GCNT02 execute command OK condition signal
540001 820E031E84 GCNT03_EC_OK_CSCN GCNT03 execute command OK condition signal
…. …. ….
540001 820E201E84 GCNT32_EC_OK_CSCN GCNT32 execute command OK condition signal

GRL200 (Soft 033 & 037)


- 597 -
6F2S1914 (0.37)

3.7.5 Mapping for IEC61850 communication


The user can operate the GCNT function over IEC 61850 communication following mapping
using GR-TIEMS. Note that the GCNT function is designed for the class of “Integer Status
Controller (ISC)” in the IEC 61850 standard for communication. The user should follow these
steps, each of which is discussed below:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user will need to create a logical node (LN) for the GCNT01 function. Figure 3.7-15
exemplifies the editing of a LN; the LN “Integer Status controller (ISCSO)” is chosen for the
GCNT01 function. After the user has defined an object “ISCSO”, the GCNT01 logical node can
be saved with the name “GIGO” plus “LN Instance”. Create a definition of the object “ISCSO”
in the GGIO logical node. Either the SBO mode or the DIR mode can be chosen in the editing
for the LN.

SBO defined in LN

Figure 3.7-15 Defining “ISCSO” object in GIGO3302 logic node

GRL200 (Soft 033 & 037)


- 598 -
6F2S1914 (0.37)

Defining SBO mode


Figure 3.7-16 exemplifies the GCNT01 logic node saved as “GIGO3302”; in the SBO mode, the
user should select the following items for the “GIGO3302$ISCSO” using GR-TIEMS:

 SBOw
 Oper
 Cancel
 Origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.

Figure 3.7-16 LN editing screen for SBO mode (for example)

Defining DIR mode


Figure 3.7-17 exemplifies the GCNT01 logic node saved as save as “GIGO3302”; in the DIR
mode, the following three items should be selected using GR-TIEMS.

 Oper
 Origin
 ctlmodel (choice ”SBOes or SBOns” )

Figure 3.7-17 LN editing screen for DIR mode (for example)

GRL200 (Soft 033 & 037)


- 599 -
6F2S1914 (0.37)

(ii) Mapping output data


The user should group the GCNT01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS (Figure 3.7-18 illustrates
how to map a signal); it indicates that the signals for the GCNT01 function are required to
map the IEC 61850 communications.

Table 3.7-10 Mapping signals required for GIGO3302 object in GCNT01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO3302$ISCSO$origin orCat orCategory ST 540001300e011D23 GCNT01_CNT_ORCAT
Ctrl/GGIO3302$ISCSO$origin orIdent Octet64 ST 5400016A0e011FA7 GCNT01_CNT_ORIDENT
Ctrl/GGIO3302$ISCSO stVal INT32 ST 540001320e011D20 GCNT01_CNT_VAL
Ctrl/GGIO3302$ISCSO q Quality ST 3010013110041005 Qual_Val
Ctrl/GGIO3302$ISCSO t Timestamp ST 2003019010001006 SYS_TIME
Ctrl/GGIO3302$ISCSO stSeld BOOLEAN ST 540001000E011D91 GCNT01_TMP_01

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850.

Drag and drop

Figure 3.7-18 orCat attribute mapped into ISCSO object of GIGO3302

(iii) Mapping input data


The GCNT01 function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “GCNT01_CMM_REQ”. Table 3.7-11 shows the input-point
“GCNT01_CMM_REQ” and the Object reference “Ctrl/GIGO3302$ISCSO1”; the user should map
the input-point to the Object reference having attributes CO and CF in FC†. Figure 3.7-19 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850; “CO” stands for “Control” in the
functional constraint (FC).

GRL200 (Soft 033 & 037)


- 600 -
6F2S1914 (0.37)

Table 3.7-11 Mapping signals required for ISCSO object for GIGO3302
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO3302$ISCSO$Oper ctlVal INT32 CO
Ctrl/GGIO3302$ISCSO$Oper ctlNum INT8U CO
Ctrl/GGIO3302$ISCSO$Oper T Timestamp CO
Ctrl/GGIO3302$ISCSO$Oper Test BOOLEAN CO
Ctrl/GGIO3302$ISCSO$Oper Check Check CO 540001 700E016D09 GCNT01_CMM_REQ
Ctrl/GGIO3302$ISCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO3302$ISCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO3302$ISCSO ctlModel ctlModel CF
Ctrl/GGIO3302$ISCSO sboClass sboClass CF

Drag and drop

Check “Input”

Figure 3.7-19 Input-point mapped for GIGO3302

GRL200 (Soft 033 & 037)


- 601 -
6F2S1914 (0.37)

3.7.6 Setting
Counter (Function ID: 540001)
Setting items Range Unit Contents Default Note

GCNT01-EN Off / On - Switch for counter01 On


GCNT02-EN Off / On - Switch for counter02 On
GCNT03-EN Off / On - Switch for counter03 On
…. …. …. …..
GCNT31-EN Off / On - Switch for counter31 Off
GCNT32-EN Off / On - Switch for counter32 Off
Counter 01 NA / On / Off /
GCNT01-CNTS - Condition to count at GCNT01 NA
OnOff
GCNT01-SDB 0 - 999 - Value about Sending Dead Band at Counter01 0
GCNT01-CNTRV 0/1 - Set number when the counter is rolled up 0
GCNT01-CNTMAX 9 - 2147483647 - Largest number for counting 999999
ARC CLOSE
GCNT01-DEVNAME [Preferred name] - Name of Counter01 !
COMMAND
GCNT01-HMI Off / On - Display switch of Counter01 Off
Counter 02 NA / On / Off /
GCNT02-CNTS - Condition to count at GCNT02 NA
OnOff
GCNT02-SDB 0 - 999 - Value about Sending Dead Band at Counter02 0
GCNT02-CNTRV 0/1 - Set number when the counter is rolled up 0
GCNT02-CNTMAX 9 - 2147483647 - Largest number for counting 999999
Count2 (Not
GCNT02-DEVNAME [Preferred name] - Name of Counter02 !
Assigned)
GCNT02-HMI Off / On - Display switch of Counter02 Off
Counter 03 NA / On / Off /
GCNT03-CNTS - Condition to count at GCNT03 NA
OnOff
GCNT03-SDB 0 - 999 - Value about Sending Dead Band at Counter03 0
GCNT03-CNTRV 0/1 - Set number when the counter is rolled up 0
GCNT03-CNTMAX 9 - 2147483647 - Largest number for counting 999999
Count3 (Not
GCNT03-DEVNAME [Preferred name] - Name of Counter03 !
Assigned)
GCNT03-HMI Off / On - Display switch of Counter03 Off
…. …. …. ….
Counter 31 NA / On / Off /
GCNT31-CNTS - Condition to count at GCNT31 NA
OnOff
GCNT31-SDB 0 - 999 - Value about Sending Dead Band at Counter31 0
GCNT31-CNTRV 0/1 - Set number when the counter is rolled up 0
GCNT31-CNTMAX 9 - 2147483647 - Largest number for counting 999999
Count31 (Not
GCNT31-DEVNAME [Preferred name] - Name of Counter31 !
Assigned)
GCNT31-HMI Off / On - Display switch of Counter31 Off
Counter 32 NA / On / Off /
GCNT32-CNTS - Condition to count at GCNT32 NA
OnOff
GCNT32-SDB 0 - 999 - Value about Sending Dead Band at Counter32 0
GCNT32-CNTRV 0/1 - Set number when the counter is rolled up 0
GCNT32-CNTMAX 9 - 2147483647 - Largest number for counting 999999
Count32 (Not
GCNT32-DEVNAME [Preferred name] - Name of Counter32 !
Assigned)
GCNT32-HMI Off / On - Display switch of Counter32 Off

!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The number of counters in the GCNT depends on IED model. We omit the setting
tables of GCNT04 etc. because the setting items are the same except the device
number.

GRL200 (Soft 033 & 037)


- 602 -
6F2S1914 (0.37)

3.7.7 Signal
 Signal monitoring points in GCNT01
GCNT (Function ID: 540001)
Element ID Name Description
000E001F41 GCNT00_CCTRL_COUNTER GCNT00 cmnctrl counter correction summarize

800E001D58 GCNT00_CH_EC_LCD GCNT00 count change execute command by LCD

800E001D5E GCNT00_CH_EC_OWS GCNT00 count change execute command by OWS(HMI)

800E001D5F GCNT00_CH_EC_RCC GCNT00 count change execute command by RCC

800E001D60 GCNT00_CH_EC_RMT GCNT00 count change execute command by Remote

800E001D54 GCNT00_CH_SC_LCD GCNT00 count change select command by LCD

800E001D5B GCNT00_CH_SC_OWS GCNT00 count change select command by OWS(HMI)

800E001D5C GCNT00_CH_SC_RCC GCNT00 count change select command by RCC

800E001D5D GCNT00_CH_SC_RMT GCNT00 count change select command by Remote

840E011E95 GCNT01_CC_SSCN GCNT01 cancel success signal

310E011D21 GCNT01_CNT_QLT GCNT01 count quality

320E011D20 GCNT01_CNT_VAL GCNT01 count value

000E011F42 GCNT01_CORR_INS GCNT01 correction instruction

890E011EA2 GCNT01_CTR_SGUCN GCNT01 control logic stage(under selection)

830E011E8B GCNT01_EC_F_CSCN GCNT01 execute command fail condition signal

820E011E84 GCNT01_EC_OK_CSCN GCNT01 execute command OK condition signal

8A0E011E76 GCNT01_SLD_CSCN GCNT01 selected condition signal

8B0E011E7B GCNT01_SLF_CSCN GCNT01 select fail condition signal

000E011D91 GCNT01_TMP_01 GCNT01 count change selected signal(stSeld) for SAS

 Connection points in PLC logics in GCNT01


GCNT (Function ID: 540001)
Element ID Name Description
800E00ED5A GCNT00IN_TMP_51 GCNT00IN_TMP_51

800E01EDE0 GCNT01_PLC_SGNL GCNT01 plc signal

 Mapping point in GCNT01


GCNT (Function ID: 540001)
Element ID Name Description
700E016D09 GCNT01_CMM_REQ GCNT01 control request(Mapping data)

Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the GCNT function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.

Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “GCNT02_CTR_SGUCN” point
for the 2nd device, use the description of “GCNT01_CTR_SGUCN” in place
of “GCNT02_CTR_SGUCN”. The user can obtain the ID value of

GRL200 (Soft 033 & 037)


- 603 -
6F2S1914 (0.37)

“GCNT02_CTR_SGUCN” by using the following steps:


Step 1 Find the element ID for GCNT01_CTR_SGUCN (i.e.,
“890E011EA2”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “890E021EA2” of
“GCNT02_CTR_SGUCN”) The ID is expressed in
hexadecimal notation. Thus, the user must change the
device number from decimal notation to hexadecimal
notation.

GRL200 (Soft 033 & 037)


- 604 -
6F2S1914 (0.37)

Mode control function (MDCTRL)


The mode control (MDCTRL) function provides an interface for testing. It’s a command for
changing a mode for test functions (TEST-FB). The MDCTRL function consists of two parts:
(1) On-mode or Test-mode sensing in IED and (2) interface between the IED and the SAS.

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.8-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 605 -
6F2S1914 (0.37)

3.8.1 Function
(i) Mode sensor
The MDCTRL function can monitor the state change (On to TEST / TEST to Off) in the IED.
To use this monitoring function, On should be set for the scheme switch [MDCTRL-EN] prior to
operation. During the operation, a select signal and an operate signal are provided for the
TEST-FB when the SAS provides a test command for the IED; hence, the MDCTRL function
comes with two time-out timers. Setting [MDCTRL-SELRST] provides a time-out timer for
canceling a select command; setting [MDCTRL-EXERST] provides a time-out timer for
canceling an operate command.

(ii) Interface for IEC61850


The MDCTRL function can fulfil the two operation modes (On and Test) specified in the IEC
61850 communication, as shown in Table 3.8-2; the MDCTRL function can carry a signal for
changing for the TEST-FB; the signal is generated in the select and control logics in the
MDCTRL function. The change signal is initiated by the mode change command that is
received at the communication interface. Note that control operations from a SAS is only taken
account.

Table 3.8-2 Values of mode and behavior in IEC 61850


Value Mode Definition in IEC 61850
The application represented by the LN works. All communication
1 On
services work and get updated values.
The application represented by the LN works. All communication
services work and get updated values. Data objects will be transmitted
with quality “test”. Control commands with quality test will be
3 Test
accepted only by LNs in “test” or “test-blocked” mode. “Processed as
valid” means that the application should react in the manner what is
foreseen for “test”.

(iii) Input signal from control hierarchy


Note PLC logic “Control hierarchy condition” is required to operate the MDCTRL function; the
user should notice that the connection with the Control hierarchy is made using the connection
point “MDCTRL01IN_TMP_28” (see Table 3.8-3). For more information, see chapter Control
and monitoring application: Control hierarchy.

Table 3.8-3 PLC connection point (Input signal for select condition logic)
Signal Number Signal Name Description M/O
550001 821301ED50 MDCTRL01IN_TMP_28 MDCTRL control hierarchy condition M

GRL200 (Soft 033 & 037)


- 606 -
6F2S1914 (0.37)

3.8.2 Mapping for IEC61850 communication


The user can operate the MDCTRL function over the IEC61850 communication after the
mapping using GR-TIEMS. The user should follow steps,
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user should make a logical node (LN) for the MDCTRL function. Figure 3.8-1exemplifies
LN editing; the LN “LLNO” is chosen for the MDCTRL01 for IEC61850 communication. After
the user defining an object “MOD”, the MDCTRL01 logical node can be saved with the name
“LLNO”. Make a definition of the object “MOD” in MDCTRL01 logical node. Either the SBO
mode or the DIR mode can be chosen in the LN editing.

Figure 3.8-1 Defining “MOD” object in LLNO logic node

Defining SBO mode


Figure 3.8-2 exemplifies the settings in LN “LLNO” when the SBO mode is required for the
MDCTRL01 function. In the SBO control, the user should select the following items for the
“LLNO$MOD” using the GR-TIEMS;

GRL200 (Soft 033 & 037)


- 607 -
6F2S1914 (0.37)

SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.

Figure 3.8-2 LN editing screen for SBO mode (for example)


Defining DIR mode
Figure 3.8-3 exemplifies the settings in LN “LLNO” when the DIR mode is required for the
MDCTRL01 function. In the DIR mode, the following three items should be selected using the
GR-TIEMS:

Oper
origin
ctlmodel (choice ”DOes or DOns” )

Figure 3.8-3 LN editing screen for DIR mode (for example)

(ii) Mapping output data


The user should group the MDCTRL01 signals with regard to GOOSE and REPORT; the user
should map them for the IEC 61850 communication using GR-TIEMS.
Table 3.8-4 shows the required mapping signals in MDCTRL01 function to the IEC 61850
communications. Figure below shows how to map a signal.
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.

GRL200 (Soft 033 & 037)


- 608 -
6F2S1914 (0.37)

Table 3.8-4 Mapping signals for MOD object.


Object_reference Attribute Type FC Signal Number Signal Name
System/LLN0$Mod$origin orCat orCategory ST 5500013013011000 MDCTRL01_ORCAT
System/LLN0$Mod$origin orIdent Octet64 ST 5500016A13011009 MDCTRL01_ORIDENT
System/LLN0$Mod stSeld BOOLEAN ST 5500010013011D90 MDCTRL01_SLD_RPT

Drag and drop

Figure 3.8-4 orCat attribute mapped into MOD object of LLNO

(iii) Mapping input data


The MDCTRL01 function can receive three commands “select, operate, and cancel. Thus, the
user should map the input-point “MDCTRL01_CONTROL_REQ”. Table 3.8-5 shows the input-
point “MDCTRL01_CONTROL_REQ” and the Object reference “System/LLN0$Mod$”; the user
should map the Object reference having attributes CO and CF in FC to the input-point. Note that
the user should map the input-point to all attributes having CO and CF. Figure below shows
how to map a signal.

GRL200 (Soft 033 & 037)


- 609 -
6F2S1914 (0.37)

Table 3.8-5 Mapping signals required for LLNO object in MDCTRL01 function
Object_reference Attribute Type FC Signal Number Signal Name
System/LLN0$Mod$SBOw ctlVal Mod CO
System/LLN0$Mod$SBOw ctlNum INT8U CO
System/LLN0$Mod$SBOw T Timestamp CO
System/LLN0$Mod$SBOw Test BOOLEAN CO
System/LLN0$Mod$SBOw Check Check CO
System/LLN0$Mod$SBOw$origin orCat orCategory CO
System/LLN0$Mod$SBOw$origin orIdent Octet64 CO
System/LLN0$Mod$Oper ctlVal Mod CO
System/LLN0$Mod$Oper ctlNum INT8U CO
System/LLN0$Mod$Oper T Timestamp CO
System/LLN0$Mod$Oper Test BOOLEAN CO
System/LLN0$Mod$Oper Check Check CO 5500017013016D08 MDCTRL01_CONTROL_REQ
System/LLN0$Mod$Oper$origin orCat orCategory CO
System/LLN0$Mod$Oper$origin orIdent Octet64 CO
System/LLN0$Mod$Cancel ctlVal Mod CO
System/LLN0$Mod$Cancel ctlNum INT8U CO
System/LLN0$Mod$Cancel T Timestamp CO
System/LLN0$Mod$Cancel Test BOOLEAN CO
System/LLN0$Mod$Cancel$origin orCat orCategory CO
System/LLN0$Mod$Cancel$origin orIdent Octet64 CO
System/LLN0$Mod ctlModel ctlModel CF
System/LLN0$Mod sboTimeout INT32U CF
System/LLN0$Mod sboClass sboClass CF

†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).

Check “Input”

Figure 3.8-5 Input-point mapped for LLNO

GRL200 (Soft 033 & 037)


- 610 -
6F2S1914 (0.37)

3.8.3 Setting

MDCTRL (Function ID: 550001)


Setting items Range Unit Contents Default Note

MDCTRL-EN Off/On Switch for Mode change operation Off !


MDCTRL-SELRST 10-100 s Selection cancel time-out timer 30 !
MDCTRL-EXERST 10-100 s Waiting execute operation time-out timer 30 !
!Note: The user can set an item on Test sub-menu (see Chapter Communication and
maintenance: Test operations or User interface: Test sub-menu).

GRL200 (Soft 033 & 037)


- 611 -
6F2S1914 (0.37)

3.8.4 Signal
 Signal monitoring point
MDCTRL(Function ID: 550001)
Element ID Name Description
8013011D55 MDCTRL01_EC_OWS MDCTRL01 execute command by OWS(HMI)

8013011D56 MDCTRL01_EC_RCC MDCTRL01 execute command by RCC

8013011D57 MDCTRL01_EC_RMT MDCTRL01 execute command by Remote

2013011001 MDCTRL01_MODE MDCTRL01 mode

8013011D51 MDCTRL01_SC_OWS MDCTRL01 select command by OWS(HMI)

8013011D52 MDCTRL01_SC_RCC MDCTRL01 select command by RCC

8013011D53 MDCTRL01_SC_RMT MDCTRL01 select command by Remote

0013011F75 MDCTRL01_SE_RCV MDCTRL01 select or execute command received

0013011D90 MDCTRL01_SLD_RPT MDCTRL01 selected signal(stSeld) for SAS

3113011D80 MDCTRL01_TMP_06 MDCTRL01 control event data (selected)

3113011D81 MDCTRL01_TMP_07 MDCTRL01 control event data (select fail)

3113011D82 MDCTRL01_TMP_08 MDCTRL01 control event data (select release)

3113011D83 MDCTRL01_TMP_09 MDCTRL01 control event data (execute output on)

3113011D84 MDCTRL01_TMP_10 MDCTRL01 control event data (execute command ng)

3113011D86 MDCTRL01_TMP_11 MDCTRL01 control event data (execute fail)

0013011F52 MDCTRL01_TRA MDCTRL01 travelling info

0013011F53 MDCTRL01_TRA_CTR MDCTRL01 travelling info for control

8713011E96 MODE01_CC_FS MDCTRL01 cancel command fail signal

8613011E95 MODE01_CC_SS MDCTRL01 cancel command success signal

8813011E9B MODE01_CC_ST_ERR MDCTRL01 cancel command mode err

8313011E9C MODE01_CCF_FCT_CS MDCTRL01 cancel command fail factor condition signal

8313011E9D MODE01_CTR_SGN MDCTRL01 control logic stage(unselected)

8B13011EA2 MODE01_CTR_SGU MDCTRL01 control logic stage(under selection)

8113011E9A MODE01_ECF_FCT_EIS MDCTRL01 execute command fail factor signalcheck

8013011E93 MODE01_EX_CMP MDCTRL01 execute complete signal

8F13011F58 MODE01_EX_CMP_TMO MDCTRL01 timeout after execute completion

8913011F6C MODE01_EX_CS01 MDCTRL01 execute condition signal 01

8A13011F6D MODE01_EX_CS02 MDCTRL01 execute condition signal 02

8B13011F6E MODE01_EX_CS03 MDCTRL01 execute condition signal 03

8613011E91 MODE01_EX_FFL MDCTRL01 execute fail signal

8213011F44 MODE01_EX_OUT MDCTRL01 execute output signal

8513011E8F MODE01_EX_SFL MDCTRL01 execute success signal

8213011E88 MODE01_FEC_F_CS MDCTRL01 On direction execute command fail condition signal

8013011E81 MODE01_FEC_OK_CS MDCTRL01 On direction execute command OK condition signal

8D13011F42 MODE01_FSD_CSF MDCTRL01 On direction selected condition signal

8513011F60 MODE01_FSL_CS19 MDCTRL01 On direction select condition signal 19

8A13011F61 MODE01_FSL_CS20 MDCTRL01 On direction select condition signal 20

8113011F64 MODE01_FSL_CS21 MDCTRL01 On direction select condition signal 21

8313011F41 MODE01_NSD_CSF MDCTRL01 no direction selected condition signal

8013011F56 MODE01_NSL_CS06 MDCTRL01 no direction select condition signal 06

8613011F5E MODE01_NSL_CS07 MDCTRL01 no direction select condition signal 07

8213011F5F MODE01_NSL_CS10 MDCTRL01 no direction select condition signal 10

8313011E89 MODE01_OEC_F_CS MDCTRL01 Test direction execute command fail condition signal

GRL200 (Soft 033 & 037)


- 612 -
6F2S1914 (0.37)

 Signal monitoring point


MDCTRL(Function ID: 550001)
Element ID Name Description
8113011E82 MODE01_OEC_OK_CS MDCTRL01 Test direction execute command OK condition signal

8F13011F43 MODE01_OSD_CSF MDCTRL01 Test direction selected condition signal

8513011F65 MODE01_OSL_CS40 MDCTRL01 Test direction select condition signal 40

8813011F5D MODE01_OSL_CS41 MDCTRL01 Test direction select condition signal 41

8513011F5B MODE01_OSL_CS42 MDCTRL01 Test direction select condition signal 42

8013011F54 MODE01_SC_ST_ERR MDCTRL01 select command mode err

8013011E76 MODE01_SLD_CS MDCTRL01 selected condition signal

8013011F66 MODE01_SLD_CS04 MDCTRL01 selected condition signal 04

8E13011F57 MODE01_SLD_TMO MDCTRL01 time out after selected

8113011E7B MODE01_SLF_CS MDCTRL01 select fail condition signal

8713011E98 MODE01_SLF_FCT_EIS MDCTRL01 select fail factor signal

8613011F62 MODE01_SLF_FCT_FLG03 MDCTRL01 select fail factor signal by fixedlogic 03

8713011F63 MODE01_SLF_FCT_FLG04 MDCTRL01 select fail factor signal by fixedlogic 04

8813011F6B MODE01_SLF_FCT_FLG07 MDCTRL01 select fail factor signal by fixedlogic 07

8913011F72 MODE01_SLF_FCT_FLG08 MDCTRL01 select fail factor signal by fixedlogic 08

8013011E7D MODE01_SLR_CS MDCTRL01 select release condition signal

 Connection point in PLC logic


MDCTRL(Function ID: 550001)
Element ID Name Description
821301ED50 MDCTRL01IN_TMP_28 MDCTRL01IN_TMP_28

 Mapping point
MDCTRL(Function ID: 550001)
Element ID Name Description
7013016D08 MDCTRL01_CONTROL_REQ MDCTRL01 correction request from cmm

GRL200 (Soft 033 & 037)


- 613 -
6F2S1914 (0.37)

4 Control and monitoring application


Contents Pages Pages
Automatic sequence control (ASEQ) 992 Operating time reset (OPTIM) 765
Double pos. control with SYNDIF (DPSY) 666 Single position control (SPOS) 615
Double position control (DPOS) 837 Switch control by software (SOFTSW) 730
Event detection using BIs (GENBI) 983 Synch check for difference (SYNDIF) 792
Interlock with software (ILK) 819 Three position control (TPOS) 903
Total time measurement (TOTALTIM) 779

GRL200 (Soft 033 & 037)


- 614 -
6F2S1914 (0.37)

Single position device function (SPOS)


The single position device function (SPOS) is used when the user wishes to control a device
from On or Off state. When a select command is provided for the IED, the SPOS function can
issue a control command if the SPOS function obtains the response from the device. The SPOS
function also can accept a cancel command after issuing the selection command. In the SPOS
function, issuing and receiving a command and a response are performed via a binary IO
module †; hence, the user should connect the BI and BO circuits with the SPOS function. The
SPOS function includes three logic groups: 1. Select logic, 2. Cancel logic, and 3. Operate logic.

A number of devices can be controlled separately, i.e. the SPOS function has separate sets
of logic for control (i.e., SPOS01, SPOS02 etc. functions). For simplicity, only the SPOS01
function is discussed here; the features in the SPOS02 etc. functions are identical to the
SPOS01 function.

†Note:Binary IO module has binary input circuits (BIs) and binary output circuits (BOs);
the user makes the connection between the SPOS01 function and the binary IO
module using a signal number (is made of a function ID and an “Element ID”).The
signal name and number of the SPOS01 function are listed later.

Tips: If the user wishes to apply the SPOS function quickly, go to sections 4.1.4 and
4.1.5, where setting of the BI and BO circuits and the mapping of signals for IEC
61850 communication is described.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features depends on the selection of hardware and the
configuration of functions. Several IED models do not have its features. To determine whether
its features are implemented in the IED, locate the IED ordering number; and check the order
number at the “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 4.1-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
– Number of functions – 20
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 615 -
6F2S1914 (0.37)

4.1.1 Selection logic for SBO/DIR modes


The user should set scheme switch [SPOS01-CTREN] to On prior to SPOS01 operation. Table
4.1-10 shows all of the scheme switches in the SPOS function.

(i) Receiving “select command ON” from the remote-end


Figure 4.1-1 outlines the reception of the select command ‘On’ from the remote-end.

Wait for a command

Select stage Wait for a next command

Select command On from remote-end Cancel logic


Failed
Cancel command
Signal reception Select
Selection logic Signal output
IEC61850 decision Success

Cancel logic
Select command Off from remote-end

Select command On from local-end


Operate logic
Select command Off from local-end
Operate command

Select command On by the PLC function Operate logic

Select command Off by the PLC function

Figure 4.1-1 Outline of select command ‘On’

Input point required mapping


Figure 4.1-2 shows the select logic when a “Select command ON (Remote-ON-Control)” signal
applied to the SPOS01 function. This logic has the input-point “DEV01_CONTROL_REQ” for
the reception of the selection command. That is, the input-point must be mapped for IEC 61850
communication. The function will fail to operate if mapping is not performed correctly. We will
discuss how to map the input-points for IEC61850 communication in section 4.1.5.

GRL200 (Soft 033 & 037)


- 616 -
6F2S1914 (0.37)
510001 7001016D08

Input Selection logic in SPOS01 Output

SPOS01 function (Function ID: 510001)


Command “Remote-On-Control”
For SBO operation
510001_7001016D08 DEV01_CONTROL_REQ Select command
with ILK† condition & 1≥ &
To “Wait for a next
command”
For DIR operation
To BO connection
Operate command
with ILK† condition & “SPOS01_OSL_BO_CSF”
(510001_8601011DC6)
ILK† condition (“ON”) passed
SPOS01-On 0 t Selection “success”

For SBO operation 0.1s

Select command &


without ILK† condition
To “Wait for a command”
For DIR operation 0 t
Selection “Failed”
Operate command
& 0.6s
without ILK† condition

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate
510001 8601011DC
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.1-2 Select ON from the remote-end in SPOS01††


†Note:The software interlocking (ILK) function can provide the operation criteria for
“On”. The ILK function is discussed separately; note that the operation criteria is
defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SPOS01 operation is blocked for the ASEQ function being
in the operation. For more information of the ASEQ function, see Chapter Control
and monitoring application: Automatic sequence control function.
*Note:The SPOS01 function can run in either the “SBO mode” or the “DIR mode”. The
user can use a signal called “ctlmodel” when communication is implemented using
IEC61850. To use this signal, the user must map it for IEC61850 communication.
††Note: To identify the input and output points of the other SPOS logics, see Table 4.1-5
and Table 4.1-9.

Output signal to BO
The SPOS01 function can issue an output “Selection success” signal at the output point
“SPOS01_OSL_BO_CSF”, when the SPOS01 function determines that the “Remote-ON-
Control” signal received is true. If the SPOS01 function determines that the “Remote-ON-
Control” signal is not true, the SPOS01 function returns to the “Wait for a command” stage.

GRL200 (Soft 033 & 037)


- 617 -
6F2S1914 (0.37)

(ii) Receiving “select command Off” from the remote-end


Figure 4.1-3 outlines the reception of the select command ‘Off ’ from the remote- end.

Wait for a command

Select stage Wait for a next command

Cancel logic

Select command On from remote-end Cancel command

Select command Off from remote-end


Failed
Cancel logic
Signal reception Select
Selection logic Signal output
IEC61850 decision Success

Select command On from front panel


Operate logic
Select command Off from front panel
Operate command

Select command On by the PLC Operate logic

Select command Off by the PLC

Figure 4.1-3 Outline of select command ‘Off’

Input point required mapping


Figure 4.1-4 shows the select logic when a “Select command Off (Remote-OFF-Control)” signal
is received at the input-point “DEV01_CONTROL_REQ”.
Input Selection logic in SPOS01 Output

SPOS01 function (Function ID: 510001)


Command “Remote-Off-Control”
For SBO operation
510001_7001016D08 DEV01_CONTROL_REQ Select command
with ILK† condition & 1≥ &

For DIR operation


To BO connection
Operate command
with ILK† condition & “SPOS01_FSL_BO_CSF”
ILK† condition (“Off”) passed (510001_8A01011DC4)
SPOS01-Off 0 t Selection “success”

For SBO operation 0.1s

Select command &


without ILK† condition
To “Wait for a command”
For DIR operation 0 t
Selection “Failed”
Operate command
& 0.6s
without ILK† condition

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.1-4 Select ‘OFF’ from the remote-end in SPOS01††


†Note:The ILK function provides the operation criteria for “Off”.
‡Note:The “select condition” signal is provided. See Figure 4.1-13.
††Note: To identify the input and output points of the other SPOS logics, see Table 4.1-5

GRL200 (Soft 033 & 037)


- 618 -
6F2S1914 (0.37)

and Table 4.1-9.

Output signal to BO
The SPOS01 function, in Figure 4.1-4, can issue a “Select success” signal at the output point
“SPOS01_FSL_BO_CSF” when the SPOS01 function determines that the “Select command Off
(Remote-OFF-Control)” signal is true. If the SPOS01 function determines that the “Remote-
OFF-Control” signal is not true, the SPOS01 function returns to the “Wait for a command”
stage.

(iii) Receiving “Selection command On” from the local-end


Figure 4.1-5 outlines the reception of the selection command ‘On’ from the local-end.

Wait for a command

Selection logics Wait for a next command

Cancel logic

Cancel command
Select command On from remote-end

Select command Off from remote-end


Cancel logic

Select command On from front panel


Failed

Signal reception Select


Selection logic Signal output
from the front panel decision Success
Operate logic

Select command Off from front panel Operate command

Select command On by the PLC Operate logic

Select command Off by the PLC

Figure 4.1-5 Outline of selection command ‘On’

Input signal generated at the local-end.


Figure 4.1-6 shows the select logic when a “Select command On (Local-ON-Control)” signal is
applied to the SPOS01 function. The signal is provided when an “On” key is pressed on the
IED front panel; the user is not required to map the signal from the IEC61850 communication.
Note that the user should set the scheme switch [SPOS01-CTRAHMI] to SBO when operation
from the IED front panel is required; we discuss how to set this in chapter User interface:
Control sub-menu.

GRL200 (Soft 033 & 037)


- 619 -
6F2S1914 (0.37)

Input Select logic in SPOS01 Output

SPOS01 function (Function ID: 510001)


For SBO operation
Command “Local-On-Control” Select command
with ILK† condition & 1≥ &
To “Wait for a next
For DIR operation SBO command”
Operate command To BO connection
ILK† condition (“ON”) passed with ILK† condition & “SPOS01_OSL_BO_CSF”
SPOS01-On (510001_8601011DC6)
DIR
ILK† bypassing (“Interlock Bypass”) 1≥ 0 t
Selection “success”
ICB_STATE
0.1s

To “Wait for a command”


0 t
Selection “Failed”

0.6s

[SPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.1-6 Select ‘On’ on the front panel in SPOS01††


†Note:The ILK function provides the operation criteria for “On”. For testing, nullifying
the ILK function is possible using “Interlock bypassing”. “Interlock bypassing” is
indicated by the status “ICB” in a software switch controller (SOFTSW).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the other SPOS logic, see Table 4.1-9.

Output signal to BO
When the “select condition” signal is true, the SPOS01 function can issue a “Selection success”
signal at the output-point “SPOS01_OSL_BO_CSF”.
Note: The signal “SPOS01_OSL_BO_CSF” is the same as the signal shown in Figure
4.1-2. If the “Local-ON-Control” signal is not true, the SPOS01 function returns to
the “Wait for a command” stage.

GRL200 (Soft 033 & 037)


- 620 -
6F2S1914 (0.37)

(iv) Receiving “Select command Off” from the local-end


Figure 4.1-7 outlines the reception of the select command ‘Off ’ from the local-end.

Wait for a command

Selection logics Wait for a next command

Cancel logic
Select command On from remote-end Cancel command

Select command Off from remote-end

Cancel logic
Select command On from front panel

Select command Off from front panel


Failed

Signal reception Select


Selection logic Signal output Operate logic
from the front panel decision Success
Operate command

Select command On by the PLC Operate logic

Select command Off by the PLC

Figure 4.1-7 Outline of select command ‘Off’

Input signal generated at the local-end.


Figure 4.1-8 shows the select logic when a “Select command Off (Local-OFF-Control)” signal is
applied to the SPOS01 function. The signal is provided when the user presses a “OFF” key on
the IED front panel; the user is not required to map the signal from IEC61850 communication.
Input Select logic in SPOS01 Output

SPOS01 function (Function ID: 510001)


For SBO operation
Command “Local-Off-Control” Select command
with ILK† condition & 1≥ &
For DIR operation SBO
Operate command To BO connection

ILK† condition (“Off”) passed with ILK† condition & “SPOS01_FSL_BO_CSF”


SPOS01-Off (510001_8601011DC6)
DIR
ILK† bypassing (“Interlock Bypass”) 1≥ 0 t
Selection “success”
ICB_STATE
0.1s

To “Wait for a command”


0 t Selection “Failed”

0.6s

[SPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.1-8 Select ‘Off’ on the front panel in SPOS01††


†Note: The software interlocking (ILK) function can provide the operation criteria for
“Off”. The ILK function is discussed separately; note that the operation criteria is

GRL200 (Soft 033 & 037)


- 621 -
6F2S1914 (0.37)

defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the other SPOS logics, see Table 4.1-9.

Output signal to BO
When the “select condition” signal is true, the SPOS01 function can issue a “Selection success”
signal at the output-point “SPOS01_FSL_BO_CSF”.
1Note: The signal “SPOS01_FSL_BO_CSF” is the same as the signal shown in Figure
4.1-4. If the “Local-OFF-Control” signal is not true, the SPOS01 function returns
to the “Wait for a command” stage.

(v) Receiving “Selection command for ON” by PLC function


Figure 4.1-9 outlines the reception of the select command ‘On’ by the PLC function.

Wait for a command

Selection logics Wait for a next command

Cancel logic

Cancel command
Select command On from remote-end

Select command Off from remote-end


Cancel logic
Select command On from front panel

Select command Off from front panel

Operate logic
Select command On by PLC
Failed Operate command
function

PLC logic programmed Select


Selection logic Signal output
by the user decision Success
Operate logic

Select command Off by the PLC

Figure 4.1-9 Outline of select command ‘On’

Input signal required from the PLC function.


Figure 4.1-10 shows the select logic when a “Select command On (PLC-ON-Control)” signal is
generated by the PLC function. There are two input points for reception of this signal: The
former connection point (PLC#1) is used for the reception of the select-command requiring the
interlock check, the latter connection point (PLC#2) is used for the reception of the select-

GRL200 (Soft 033 & 037)


- 622 -
6F2S1914 (0.37)

command not requiring the interlock check. That is, for the SPOS01 function, when the “select
command ‘On’ (PLC-On-Control) signal generated in the user-programmed logic is applied, and
when the interlock check is required in the select logic, use the connection point (PLC#1;e.g.,
DEV01_CL_INTERLOCK). Alternatively, if the interlock check is not required, use the
connection point (PLC#2); e.g., DEV01_CL_COMMAND”. PLC#1 and PLC#2 are shown in
510001 7001016D08
Table 4.1-2.
Signals from user-PLC logic Selection logic in SPOS01 Output

SPOS01 function (Function ID: 510001)

1≥ &
ON-control command requiring ILK checking† To “Wait for a next
For DIR operation
(PLC#1 connection point) command”
Operate command
To BO connection
510001 800101EE33 DEV01_CL_INTERLOCK with ILK† condition
& “SPOS01_OSL_BO_CSF”
(510001_8601011DC6)
ILK† condition (“ON”) passed DIR
SPOS01-On 0 t Selection “success”
0.1s

ON-control command requiring no ILK checking† For DIR operation To “Wait for a command”
(PLC#2 connection point) 0 t
Operate command Selection “Failed”
510001 800101EE32 DEV01_CL_COMMAND
without ILK† condition & 0.6s

DIR

PLC in DIR operate


510001 8601011DC
Select condition‡

Figure 4.1-10 Select ‘On’ using the PLC function in SPOS01††


†Note:The software interlocking (ILK) function can provide the operation criteria for
“On”. The ILK function is discussed separately; note that the operation criteria is
defined in the ILK function itself (i.e., the user cannot set the condition).
††Note: To identify the input and output signals of the other SPOS logics, see Table 4.1-2
and Table 4.1-9.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.

Output signal to BO
The SPOS01 function, in Figure 4.1-10, can issue a “Select success” signal at the output-point
“SPOS01_OSL_BO_CSF”1.
1Note: The signal “SPOS01_OSL_BO_CSF” is the same as that shown in Figure 4.1-2.

GRL200 (Soft 033 & 037)


- 623 -
6F2S1914 (0.37)

(vi) Receiving “Select command Off” by PLC function


Figure 4.1-9 outlines the reception of the select command ‘Off ’ by the PLC function.

Wait for a command

Selection logics Wait for a next command

Cancel logic

Cancel command
Select command On from remote-end

Select command Off from remote-end


Cancel logic
Select command On from front panel

Select command Off from front panel

Operate logic
Select command On by the PLC
function Operate command

Select command Off by PLC


Failed
function
Operate logic
PLC logic programmed Select
Selection logic Signal output
by the user decision Success

Figure 4.1-11 Outline of select command ‘Off’

Input signal from the PLC function


Figure 4.1-12 shows the select logic when a “Select command Off (PLC-OFF-Control)” signal
is generated by the PLC function. There are two input points for the reception of this signal,
like in the signal “Select command On (PLC-On-Control)” where four are available. That is, if
interlock checking is required, use the connection point (PLC#1:e.g.,
DEV01_OP_INTERLOCK). Alternatively, if the interlock-check is not required, use the
connection point (PLC#2; e.g., DEV01_OP_COMMAND). PLC#1 and PLC#2 is shown Table
4.1-3.

GRL200 (Soft 033 & 037)


- 624 -
6F2S1914 (0.37)

Signals from user PLC logic Select logic in SPOS01 Output

SPOS01 function (Function ID: 510001)

1≥ &
OFF-control command requiring ILK† checking For DIR operation
(PLC#1 connection point)
510001 800101EE31 Operate command with To BO connection
DEV01_OP_INTERLOCK
ILK† condition & “SPOS01_FSL_BO_CSF”
ILK† condition (“OFF”) passed (510001_8601011DC6)
SPOS01-Off 0 t Selection “success”

0.1s

OFF-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point)
0 t
Operate command Selection “Failed”
510001 800101EE30 DEV01_OP_COMMAND &
without ILK† condition 0.6s

PLC in DIR operate

Select condition‡

Figure 4.1-12 Selection logic for ‘Off’ by PLC in SPOS01††


†Note:The software interlocking (ILK) function can provide the operation criteria for
“Off”. The ILK function is discussed separately; note that the operation criteria is
defined in the ILK function itself (i.e., the user cannot set the condition).
††Note: To identify the input and output points of the other SPOS logic, see Table 4.1-3
for the input (PLC#1 and PLC#2) and Table 4.1-9 for the outputs.

Output signal to BO
The SPOS01 function, in Figure 4.1-12, can issue a “Select success” signal at the output point
“SPOS01_FSL_BO_CSF”1.
1Note: The output point “SPOS01_FSL_BO_CSF” is the same signal as shown in Figure
4.1-4.

(vii) Select condition


Figure 4.1-13 shows the select condition logic in the SPOS01 function. The SPOS01 function
checks the condition for the select command using the signal “SPOS01_STATE” (Table 4.1-25).
If the original logic does not meet with the requirements of the user, the following alternatives
are available:
1. The user can replace the original logic with alternative logic.
2. The user can add additional logic to the original logic.

How to add another select condition signal


If adding another condition is required, the user can add a signal to the select condition logic
using the PLC connection point “User Additional condition”.
1. Add a user-preferred signal using SPOS01IN_TMP_31, which is listed as PLC#1 in
Table 4.1-7.

GRL200 (Soft 033 & 037)


- 625 -
6F2S1914 (0.37)

2. Set the scheme switch [SPOS01-LGSLFFCT] to Fixed logic.

How to replace the original logic


If the user wishes to replace the select condition logic completely, the user can replace it using
the PLC connection point “User configurable condition”.
1. Connect the user-customized logic using SPOS01IN_TMP_32, which is listed as
PLC#2 in Table 4.1-7.
2. Set the scheme switch [SPOS01-LGSLFFCT] to PLC.
SPOS01 function (Function ID: 510001)
Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Traveling OR Select condition

Function “Automatic sequence control” is in progress Unmatched condition detected *5


ASEQ_MULTI_SEL Event suppression detected *6
= SPOS01_F_QLT_SPP
Tripping *4 (“General trip”)
GEN. TRIP (510001 810101F59)
BI board connection error detected*7
= SPOS01_F_BI_ERR
BI board connect
(510001 820101F5A)
Event supp

Unmatched co
Command “ON control” received &
Command “OFF control” received &
received
SPOS01_STATE
(510001 0001011001)
[SCDEN]*8 Same Directional
Controlling Event
OFF
Additional condition (PLC#1 connection point)
510001 800101EE61 SPOS01IN_TMP_31
[SPOS01-LGSLFFCT]
User configurable condition (PLC #2connection point)
Fixedlogic
510001 810101EE62 SPOS01IN_TMP_32 &

Users must setup this condition correctly


From Control hierarchy (e.g. 43RL) (PLC#3 connection point)*9
510001 820101ED50 SPOS01IN_TMP_28
&
From CMNCTRL serious error detection
SERI_ERR

[SPOS01-CTREN]

On

Figure 4.1-13 Select condition logic for ON/OFF in SPOS01*10


1Note: “Command blocking” disables any operation except its own; the “Command
blocking” is initiated by the status of “CBK” in a software switch controller
(SOFTSW).The IEC 61850 standard defines command blocking as “CmdBlk”. For
more information on “CBK”, see Chapter Control and monitoring application:
Software switch controller. See the signal “S4301_STAEE of Table 4.1-6.
2Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS.
3Note: If the event “device-travelling is detected, it indicates that another operator is
changing the statuses of a device. Thus, the IED should inhibit the operation of
any device for the duration that the event is detected. The detecting signal is
donated as “Travelling OR” in Table 4.1-6.

GRL200 (Soft 033 & 037)


- 626 -
6F2S1914 (0.37)

4Note: If the issue of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issued at the output point “GEN.TRIP” in Table
4.1-6.
5Note: Criteria “unmatched conditions” are decided when “Test-bit status” in a command
is not identical to “IED test status”.
6Note: The “Event suppression” function can detect chattering on BI circuits. (See section
4.1.4(i)-2)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The common control (CMNCTRL) function can test and check the ‘On’ and ‘Off”
operations performed by the logic. When the user sets Off for scheme switch
(SCDEN), the operation of the logic is blocked if the logic is running in the same
operation- direction compared with the previous operation direction. (i.e., when
On (Off) is performed sequentially). On the other hand, if On is set for the scheme
switch, the logic is not blocked.
9Note: The user will need to program the PLC logic “Control hierarchy condition” The
user is also required to connect the logic condition with the select condition logic
using the connection point “SPOS01IN_TMP_28”. For more information, see
chapter “Control and monitoring application: Control hierarchy” see PLC#3 of
Table 4.1-7.
10Note: To identify the input point of the other SPOS, see Table 4.1-7 for PLC#1 and
PLC#2.

(viii) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicates that the signal is provided for optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” indicates that the user cannot change the state of the signal.

Table 4.1-2 PLC connection points (Input points for command ‘On’)
Signal Number Signal Name Description M/O
510001 800101EE32 DEV01_CL_COMMAND SPOS01 PLC On-control without checking O
510001 800102EE32 DEV02_CL_COMMAND SPOS02 PLC On-control without checking O
510001 800103EE32 DEV03_CL_COMMAND SPOS03 PLC On-control without checking O
…. …. ….
510001 800114EE32 DEV20_CL_COMMAND SPOS20 PLC On-control without checking O
510001 800101EE33 DEV01_CL_INTERLOCK SPOS01 PLC On-control checking with interlock O
510001 800102EE33 DEV02_CL_INTERLOCK SPOS02 PLC On-control checking with interlock O

GRL200 (Soft 033 & 037)


- 627 -
6F2S1914 (0.37)

Signal Number Signal Name Description M/O


510001 800103EE33 DEV03_CL_INTERLOCK SPOS03 PLC On-control checking with interlock O
…. …. ….
510001 800114EE33 DEV20_CL_INTERLOCK SPOS20 PLC On-control checking with interlock O

Table 4.1-3 PLC connection points (Input points for command ‘Off’)
Signal Number Signal Name Description M/O
510001 800101EE31 DEV01_OP_INTERLOCK SPOS01 PLC Off-control checking with interlock O
510001 800102EE31 DEV02_OP_INTERLOCK SPOS02 PLC Off-control checking with interlock O
510001 800103EE31 DEV03_OP_INTERLOCK SPOS03 PLC Off-control checking with interlock O
…. …. ….
510001 800114EE31 DEV20_OP_INTERLOCK SPOS20 PLC Off-control checking with interlock O
510001 800101EE30 DEV01_OP_COMMAND SPOS01 PLC Off-control without checking O
510001 800102EE30 DEV02_OP_COMMAND SPOS02 PLC Off-control without checking O
510001 800103EE30 DEV03_OP_COMMAND SPOS03 PLC Off-control without checking O
…. …. ….
510001 800114EE30 DEV20_OP_COMMAND SPOS20 PLC Off-control without checking O

Table 4.1-4 PLC connection points (Interlock for command ‘On/Off’)


Signal Number Signal Name Description M/O
570001 3101011DA0 SPOS01-Off SPOS01 interlock condition for Off control. N/A
570001 3101021DA0 SPOS02-Off SPOS02 interlock condition for Off control. N/A
570001 3101031DA0 SPOS03-Off SPOS03 interlock condition for Off control. N/A
…. …. ….
570001 3101141DA0 SPOS020-Off SPOS20 interlock condition for Off control. N/A
570001 3101011DA2 SPOS01-On SPOS01 interlock condition for On control. N/A
570001 3101021DA2 SPOS02-On SPOS02 interlock condition for On control. N/A
570001 3101031DA2 SPOS03-On SPOS03 interlock condition for On control. N/A
…. …. ….
570001 3101141DA2 SPOS20-On SPOS20 interlock condition for On control. N/A

Table 4.1-5 Mapping points for the reception of control commands


Signal Number Signal Name Description M/O
510001 7001016D08 DEV01_CONTROL_REQ SPOS01 control command received. (Mapping Data) M
510001 7001026D08 DEV02_CONTROL_REQ SPOS02 control command received. (Mapping Data) M
510001 7001036D08 DEV03_CONTROL_REQ SPOS03 control command received. (Mapping Data) M
…. …. ….
510001 7001146D08 DEV20_CONTROL_REQ SPOS20 control command received. (Mapping Data) M

Table 4.1-6 Input signals to condition logic


Signal Number Signal Name Description M/O
522001 000A011001 CBK_STATE Command Blocking status ( Off / Blocked) N/A
522001 000A021001 ICB_STATE Interlock bypassing status(On / Bypass) N/A
523001 000D001F40 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A
5A0001 0008001F41 DCB RCV OR Double Command Blocking(DCB) is in progress. N/A
5A0001 0008001F40 Traveling OR Travelling events are detected. N/A
4A0001 8300001B6F GEN.TRIP General trip N/A
5A0001 3108003F40 SDCEN (This is setting of CMNCTRL) N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A
523001 000D001F40 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A

GRL200 (Soft 033 & 037)


- 628 -
6F2S1914 (0.37)

Table 4.1-7 PLC connection points (Input signal for select condition logic)
Signal Number Signal Name Description M/O
510001 800101EE61 SPOS01IN_TMP_31 SPOS01 additional failure condition (PLC#1) O
510001 800102EE61 SPOS02IN_TMP_31 SPOS02 additional failure condition (PLC#1) O
510001 800103EE61 SPOS03IN_TMP_31 SPOS03 additional failure condition (PLC#1) O
…. …. ….
510001 800114EE61 SPOS20IN_TMP_31 SPOS20 additional failure condition (PLC#1) O
510001 810101EE62 SPOS01IN_TMP_32 SPOS01 user configurable select condition (PLC#2) O
510001 810102EE62 SPOS02IN_TMP_32 SPOS02 user configurable select condition (PLC#2) O
510001 810103EE62 SPOS03IN_TMP_32 SPOS03 user configurable select condition (PLC#2) O
…. …. ….
510001 810114EE62 SPOS20IN_TMP_32 SPOS20 user configurable select condition (PLC#2) O
510001 820101ED50 SPOS01IN_TMP_28 SPOS01 control hierarchy condition (PLC#3) M
510001 820102ED50 SPOS02IN_TMP_28 SPOS02 control hierarchy condition (PLC#3) M
510001 820103ED50 SPOS03IN_TMP_28 SPOS03 control hierarchy condition (PLC#3) M
…. …. ….
510001 820114ED50 SPOS20IN_TMP_28 SPOS20 control hierarchy condition (PLC#3) M

Table 4.1-8 PLC monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
510001 8001011F54 SPOS01_SC_ST_ERR SPOS01 select command mode is invalid.
510001 8001021F54 SPOS02_SC_ST_ERR SPOS02 select command mode is invalid.
510001 8001031F54 SPOS03_SC_ST_ERR SPOS03 select command mode is invalid.
…. …. ….
510001 8001141F54 SPOS20_SC_ST_ERR SPOS20 select command mode is invalid.
510001 8101011F59 SPOS01_F_QLT_SPP Event suppression detected (SPOS01)
510001 8101021F59 SPOS02_F_QLT_SPP Event suppression detected (SPOS02)
510001 8101031F59 SPOS03_F_QLT_SPP Event suppression detected (SPOS03)
…. …. ….
510001 81010A1F59 SPOS20_F_QLT_SPP Event suppression detected (SPOS20)
510001 8201011F5A SPOS01_F_BI_ERR BI connection error detected(SPOS01)
510001 8201021F5A SPOS02_F_BI_ERR BI connection error detected(SPOS02)
510001 8201031F5A SPOS03_F_BI_ERR BI connection error detected(SPOS03)
…. …. ….
510001 8201141F5A SPOS20_F_BI_ERR BI connection error detected(SPOS20)

Table 4.1-9 PLC monitoring points (On/Off Output-signal)


Signal Number Signal Name Description
510001 8601011DC6 SPOS01_OSL_BO_CSF SPOS01 select (ON) command for Binary Output.
510001 8601021DC6 SPOS02_OSL_BO_CSF SPOS02 select (ON) command for Binary Output.
510001 8601031DC6 SPOS03_OSL_BO_CSF SPOS03 select (ON) command for Binary Output.
…. …. ….
510001 8601141DC6 SPOS20_OSL_BO_CSF SPOS20 select (ON) command for Binary Output.
510001 8A01011DC4 SPOS01_FSL_BO_CSF SPOS01 select (OFF) command for Binary Output.
510001 8A01021DC4 SPOS02_FSL_BO_CSF SPOS02 select (OFF) command for Binary Output.
510001 8A01031DC4 SPOS03_FSL_BO_CSF SPOS03 select (OFF) command for Binary Output.
…. …. ….
510001 8A01141DC4 SPOS020_FSL_BO_CSF SPOS20 select (OFF) command for Binary Output.

GRL200 (Soft 033 & 037)


- 629 -
6F2S1914 (0.37)

(ix) Setting names


Note: The “xx” of “SPOSxx” represents the SPOS function number. (e.g., if the SPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented from
“01” to “20”.)

Table 4.1-10 Setting of SBO control in SPOSxx


Setting Name Description Default Setting item or value
SPOSxx-CTREN Activate control function in SPOSxx On Off / On
SPOSxx-LGSLFFCT Logic selector for select condition in SPOSxx Fixedlogic Fixedlogic / PLC
SPOSxx-CTRAHMI Activate local panel control in SPOSxx SBO DIR / SBO

GRL200 (Soft 033 & 037)


- 630 -
6F2S1914 (0.37)

4.1.2 Cancel logic for SBO mode


In SBO control mode the reception of a cancel command is possible; the function can discard
the select command when the cancel conditions are satisfied; finally, the operation returns to
the initial stage (i.e., waiting state “Wait for a command”.)

(i) Receiving “Cancel” from the remote-end


Figure 4.1-14 depicts the cancel command procedure for a cancel command initiated from the
remote-end.

Wait for a command

Select logics Wait for a next command

Select command On from remote-end Cancel from remote-end


Success

Select command Off from remote-end Cancel


Signal reception in
Cancel logic Do nothing
IEC61850 decision Failed
Select On from front panel

Select command Off from front panel


Cancel from front panel
Select command On by the PLC
function
Select command Off by the PLC
function
Operate logic
Operate command

Operate logic

Figure 4.1-14 Outline of ‘cancel’ command from the remote-end

Input point required mapping


Figure 4.1-15 depicts the cancel logic when a “Cancel command (Remote-Cancel)” signal is
applied to the SPOS01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the signal “Select command On (Remote-On-Control)”.
510001 7001016D08

Input Cancel logic in SPOS01 Output

SPOS01 function (Function ID: 510001)


To “Wait for a command”
Command “Remote-cancel”
Cancel command
510001_7001016D08 DEV01_CONTROL_REQ “SPOS01_ CC_SS” (510001_8601011E95)
&
Successes to cancel

“Do nothing”
Cancel condition† &
“SPOS01_CC_FS” (510001_8701011E96)

Operation Failed

Figure 4.1-15 ‘Cancel’ from the remote-end in SPOS01


†Note: The logic “cancel condition” is shown in Figure 4.1-18

Output signal to BO
The SPOS01 function can issue an output signal “Success to cancel” at the monitoring point
“SPOS01_CC_SS”, when the SPOS01 function has determined that the “Remote-cancel” signal

GRL200 (Soft 033 & 037)


- 631 -
6F2S1914 (0.37)

is true. Another “Operation failed” signal is issued at the monitoring point “SPOS01_CC_FS”
if the SPOS01 function is able to determine that the “Remote-cancel” signal is not true.

(ii) Receiving “Cancel” from the local-end


Figure 4.1-16 outlines the reception of the cancel command from the local end.

Wait for a command

Select logics Wait for a next command

Cancel from the remote end


Selecting On from remote-end

Selecting Off from remote-end


Cancel from the front panel
Success
Selecting On from front panel
Press cancel Cancel
Selecting Off from front panel Cancel logic Do nothing
command decision Failed

Selecting On by the PLC function

Selecting Off by the PLC function


Operate logic
Operate command

Operate logic

Figure 4.1-16 Outline of ‘cancel’ command from the local-end

Input signal generated at the local-end


Figure 4.1-17 depicts the cancel logic when a “Cancel command (Local-cancel)” signal is applied
to the SPOS01 function. The signal is generated when the “Cancel” key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
“Local-cancel” signal, the logic is able to output a result signal; provided that the “cancel
condition” checking is satisfied. 510001 7001016D08

Input Cancel logic in SPOS01 Output

SPOS01 function (Function ID: 510001)


To “Wait for a command”
Cancel command
Command “Local-cancel” “SPOS01_ CC_SS” (510001_8601011E95)
&
Successes to cancel

Cancel condition† & “Do nothing”


“SPOS01_CC_FS” (510001_8701011E96)

Operation Failed

Figure 4.1-17 ‘Cancel’ from the front panel

Output signal to BO
The SPOS01 function, illustrated in Figure 4.1-17, is able to issue a “Select to cancel” signal
at the monitoring point “SPOS01_CC_SS”, when the SPOS01 function determines that the
“Local-Cancel” signal is true.

GRL200 (Soft 033 & 037)


- 632 -
6F2S1914 (0.37)

(iii) Cancel condition logic


Figure 4.1-18 shows the cancel condition logic. As the criteria, “unmatched condition detected”
is connected normally for the cancel logic, set Fixlogic for the scheme switch
[SPOS01_LGCNFFC].

SPOS01 function (Function ID: 510001)

Unmatched condition detected *1 To cancel logic in


& 1≥ SPOS01

[SPOS01-LGSLFFCT]
User configurable condition (PLC connection point)
Fixedlogic
510001 800101EE69 SPOS01IN_TMP_46 &

Figure 4.1-18 Logic “Cancel condition” in SPOS01


1Note: The Criteria “unmatched conditions” are determined when the “Test-bit status” in
the cancel command is not identical to the “IED test status”, like in Figure 4.1-13.
2Note: With the exception of the above ‘cancel’ condition logic, there is an operate-
condition logic within the SPOS01 function; the operate-condition logic will always
checks conditions. That is, the user is required to set either the “operate-
condition” or the “cancel-condition” logic.

If the original logic does not meet with the requirements of the user, it can be replaced
with another logic using the connection point “User Configurable condition”:
1. Connect the user-customized logic with the “SPOS01IN_TMP_46”.
2. Set scheme switch [SPOS01-LGCNFFCT] to PLC.

(iv) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” in
each table:
“O” indicates that the signal is provided for optional use.
“M” indicates that the user should map/set/configure using the signal;
otherwise, the user may experience an operational failure for the default
settings.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.1-11 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number Signal Name Description M/O
510001 800101EE69 SPOS01IN_TMP_46 SPOS01 user configurable cancel condition O
510001 800102EE69 SPOS02IN_TMP_46 SPOS02 user configurable cancel condition O
510001 800103EE69 SPOS03IN_TMP_46 SPOS03 user configurable cancel condition O
… … …
510001 800114EE69 SPOS20IN_TMP_46 SPOS20 user configurable cancel condition O

Table 4.1-12 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
510001 8601011E95 SPOS01_CC_SS Cancel succeed in SPOS01

GRL200 (Soft 033 & 037)


- 633 -
6F2S1914 (0.37)

Signal Number Signal Name Description


510001 8601021E95 SPOS02_CC_SS Cancel succeed in SPOS02
510001 8601031E95 SPOS03_CC_SS Cancel succeed in SPOS03
… … …
510001 8601141E95 SPOS20_CC_SS Cancel succeed in SPOS20
510001 8701011E96 SPOS01_CC_FS Cancel failed in SPOS01
510001 8701021E96 SPOS02_CC_FS Cancel failed in SPOS02
510001 8701031E96 SPOS03_CC_FS Cancel failed in SPOS03
… … …
510001 8701141E96 SPOS20_CC_FS Cancel failed in SPOS20

(v) Setting name


Note: The “xx” within of “SPOSxx” represents the SPOS function number. (e.g., if
SPOS03 is considered, the “xx” is equal to “03”. The numbers used for “xx” can be
represented by “01” to “20”.)
Table 4.1-13 Setting for ‘Cancel’ in SPOSxx
Setting Name Description Default Setting item or value

SPOSxx-LGCNFFCT Logic selector for cancel condition in SPOSxx Fixedlogic Fixedlogic / PLC

GRL200 (Soft 033 & 037)


- 634 -
6F2S1914 (0.37)

4.1.3 Operate logic for SBO/DIR modes


Once the operation of the select logic is completed, the operate logic start to control the device.

(i) Receiving “operate command On” from the remote- end


Figure 4.1-19 depicts the reception of the operate command ‘On’ from the remote- end.

Wait for a command

Select logics Wait for a next command

On control from remote-end


Success
Select command On from remote-end Operation
Signal reception in Operate logic Signal output
decision
IEC61850

Failed Do nothing

Select command Off from remote-end Off control from remote-end

Select command On from front panel On control from front-panel

Select command Off from front panel Off control from front-panel

Select command On by the PLC On control by PLC function


function
Select command Off by the PLC Off control by PLC function
function

Figure 4.1-19 Outline of operate command for ‘On’

Mapping required for Input point


Figure 4.1-20 illustrates the operate logic when an “Operate command On (Remote-ON-
Control)” signal is applied to the SPOS01 function. The input-point “DEV01_CONTROL_REQ”
is used for the reception of the “Operate command On (Remote-On-Control)”.

GRL200 (Soft 033 & 037)


- 635 -
6F2S1914 (0.37)

Input Operate logic in SPOS01 Output

SPOS01 function (Function ID: 510001)

“SPOS01-OEC_OK_CSF”
Command “Remote-On-Control” (510001_8001011E7F)
[SPOS01-CPW]
510001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operation Cmd.
without ILK† condition

ILK† condition (“ON”) passed S


&
SPOS01-On R

User configurable condition


(PLC#1 connection point)
S
510001 810101EE57 SPOS01IN_TMP_35 &
[SPOS01-LGCTRCON] R
& To BO connection
Fixedlogic
“SPOS01_OEX_BO”
Operate condition‡
(510001_8201011DD3) §§

[SPOS01-LGCFEXOT]
User configurable condition
(PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ function§” is in progress PLC#2
ASEQ_MULTI_SEL

[SPOS01-PLSM]*
Var To “Wait for a command”
Fix
Latch “SPOS01_EX_FFL”
[SPOS01-RST]
0 t (510001_8601011E91) ††
“SPOS01-EX_CMP”
(5A0101_8001011E93) 1.0s- 100.0s Operation Failed
“SPOS01-FEX_BO”
(510001_8101011DD0)

Figure 4.1-20 Operate ‘On’ logic by remote SAS in SPOS01††


†Note:The ILK function can provide the operation criteria for “ON”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.1-29) when Fixlogic is set for scheme switch [SPOS01-LGCTRCON]. If an
alternative “Operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative ”Operate-condition” can be connected to the above logic using
connection point #1 ”User configurable condition”. That is, set the scheme switch
[SPOS01-LGCTRCON] to PLC and use “SPOS01IN_TMP_38”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of the output signal. When Var is set for scheme switch
[SPOS01-PLSM], the output period of the signal is defined by the setting
[SPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
When Latch is set, the output signal is kept issuing until the reception of
“Command Off”.
††Note: To identify the input and output signal-points of the other SPOS logics, see Table
4.1-14 for PLC#1, Table 4.1-15 for PLC#2, Table 4.1-19, and Table 4.1-20 for
output signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by [SPOS01-RST] has been reached.

GRL200 (Soft 033 & 037)


- 636 -
6F2S1914 (0.37)

§§Note: The “SPOS01_OEX-BO” signal is issued when Fixlogic is set for scheme switch
[SPOS01-LGCFEXOT]. The “Operate completed “signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.1-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point # 2 “user-configurable condition”. That is, set the scheme switch [SPOS01-
LGCFEXOT] to PLC and use “SPOS01IN_TMP_42”.

Output signal to BO
The SPOS01 function, in Figure 4.1-20, can issue an “Operate” signal at the output point
“SPOS01_OEX_BO”, when the SPOS01 function determines that the received signal “Remote-
On-Control” is true.

GRL200 (Soft 033 & 037)


- 637 -
6F2S1914 (0.37)

(ii) Receiving “operate command Off” from the remote end


Figure 4.1-21 depicts the reception of the operate command for ‘Off ’ from the remote-end.

Wait for a command

Select logics Wait for a next command

Select command On from remote-end On control from remote-end

Off control from remote-end


Success
Operation
Signal reception in Operate logic Signal output
Select command Off from remote-end decision
IEC61850

Failed Do nothing

Select command On from front panel On control from front-panel

Select command Off from front panel


Off control from front-panel

Select command On by the PLC On control by PLC function


function
Select command Off by the PLC Off control by PLC function
function

Figure 4.1-21 Outline of operate command ‘Off’

Mapping required for Input point from communication


Figure 4.1-22 illustrates the operate logic when an “Operate command Off (Remote-Off-
Control)” signal is applied to the SPOS01 logic. The input-point “DEV01_CONTROL_REQ” is
used for the reception of the “Operate command Off (Remote-Off-Control)”.

Input Operate logic in SPOS01 Output

SPOS01 function (Function ID: 510001)


“SPOS01-FEC_OK_CSF”
(510001_8001011E7F)
Command “Remote-Off-Control”
[SPOS01-CPW]
510001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operation Cmd.
without ILK† condition
ILK† condition (“Off”) passed S
&
SPOS01-Off R

User Configurable condition


(PLC#3 connection point)

510001 800101EE56 SPOS01IN_TMP_34


[SPOS01-LGCTRCON]
&
Fixedlogic To BO connection

Operate condition‡ “SPOS01_FEX_BO” §§


(510001_8101011DD0)

[SPOS01-LGCFEXOT]
User Configurable condition
(PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ§ function is in progress
ASEQ_MULTI_SEL
To “Wait for a command”
[SPOS01-PLSM]*
“SPOS01_EX_FFL” † †
Var [SPOS01-RST] (510001_8601011E91)
Fix
0 t
“SPOS01-EX_CMP
(5A0101_8001011E93) 1.0s- 100.0s Operation Failed

Figure 4.1-22 Operate ‘Off’ from the remote -end in SPOS01††


†Note:The ILK function can provide the operation criteria for “Off”.

GRL200 (Soft 033 & 037)


- 638 -
6F2S1914 (0.37)

‡Note:An “operate condition” is generated in the operate-condition logic( see Figure


4.1-29) when Fixlogic is set for scheme switch[SPOS01-LGCTRCON], If an
alternative “Operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative ”Operate-condition” can be connected to the above logic using
connection point #3 ”User configurable condition”. That is, set the scheme switch
[SPOS01-LGCTRCON] to PLC and use SPOS01IN_TMP_34.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by [SPOS01-RST] has been reached.
§§Note: The signal “SPOS01_OEX-BO” is issued when Fixlogic is set for scheme switch
[SPOS01-LGCFEXOT]. The “Operate completed “signal can also be issued from
logic programmed by the user in place of the logic shown in Figure 4.1-20. The
user-programmed logic is connected internally to the signal “Operate completed”.
Hence, this signal is now generated by the user-programmed logic at connection
point # 2 “user-configurable condition”. That is, set the scheme switch [SPOS01-
LGCFEXOT] to PLC and use “SPOS01IN_TMP_42”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of the output signal. When Var is set for scheme switch
[SPOS01-PLSM], the output period of the signal is defined by the setting
[SPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
When Latch is set, the output signal is kept issuing until the reception of
“Command Off”.
††Note: To identify the input and output signal-points of the other SPOS logics, see Table
4.1-14, Table 4.1-15, Table 4.1-19, and Table 4.1-20.

Output signal to BO
The SPOS01 function, in Figure 4.1-22, can issue an “Operate” signal at the output-point
“SPOS01_FEX_BO”, when the SPOS01 function determines that the signal “Remote-Off-
Control” is true.

(iii) Receiving “operate command On” from the local-end


Figure 4.1-23 depicts the reception of the operate command for ‘On’ from the local-end.

GRL200 (Soft 033 & 037)


- 639 -
6F2S1914 (0.37)

Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Operate command On from the local-end

Select command Off from the remote-end Operate command Off from the local-end

Operate command On from the local-end


Select command On from the local-end Success
Operation
Signal reception from Operate logic Signal output
decision
the front panel

Failed Do nothing

Select command Off from the local-end Operate command Off from the local-end

Select command On by the PLC function Operate command On by the PLC function

Select command Off by the PLC function Operate command Off by the PLC function

Figure 4.1-23 Outline of operate command ‘On’

Input signal generated at the local-end.


Figure 4.1-24 illustrates the operate logic when an “Operate command On (Local-ON-Control)”
signal is applied to the SPOS01 function. The signal is generated when “Execution of On” is
keyed on the IED front panel.

Input Operate logic in SPOS01 Output

SPOS1 function (Function ID: 510001)

“SPOS01-OEC_OK_CSF”
(510001_8001011E7F)
Operate Cmd.
Command “Local-On-Control” [SPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operation Cmd.
without ILK† condition
ILK† condition (“ON”) passed
SPOS01-On
S
&
ILK† bypassing ( Bypass) 1≥
R
ICB_STATE

User configurable condition (PLC#1 connection point) S


510001 810101EE57 SPOS01IN_TMP_35 &
[SPOS01-LGCTRCON] R
&
Fixedlogic To BO connection
PLC#1
“SPOS01_OEX_BO”
Operate condition‡
(510001_8201011DD3) §§

[SPOS01-LGCFEXOT]
User configurable condition (PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ function§” is in progress PLC#2
ASEQ_MULTI_SEL

[SPOS01-PLSM]* To “Wait for a command”


Var
Fix “SPOS01_EX_FFL”
Latch
[SPOS01-RST] (510001_8601011E91) ††
0 t
“SPOS01-EX_CMP”
(5A0101_8001011E93) 1.0s- 100.0s
Operation Failed
“SPOS01-FEX_BO”
(510001_8101011DD0)

Figure 4.1-24 Operate ‘On’ on the front panel


†Note:The ILK function provides the operation criteria for “On”.

GRL200 (Soft 033 & 037)


- 640 -
6F2S1914 (0.37)

‡Note:An “operate condition” signal is generated in the operate-condition logic( see


Figure 4.1-29) when Fixlogic is set for scheme switch [SPOS01-LGCTRCON], If an
alternative “Operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative ”Operate-condition” can be connected to the above logic using
connection point #1 ”User configurable condition”. That is, set the scheme switch
[SPOS01-LGCTRCON] to PLC and use SPOS01IN_TMP_38.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for scheme switch
[SPOS01-PLSM], the output period of the signal is defined by the setting
[SPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
When Latch is set, the output signal is kept issuing until the reception of
“Command Off”.
††Note: To identify the input and output signal-points of the other SPOS logics, see Table
4.1-14, Table 4.1-15, Table 4.1-19, and Table 4.1-20.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [SPOS01-RST].
§§Note: The signal “SPOS01_OEX-BO” is issued when Fixlogic is set for the scheme
logic [SPOS01-LGCFEXOT]. If the signal is to be issued from the logic
programmed by the user in place of the logic shown in Figure 4.1-20, connect the
signal “Operate completed” generated in the user-programmed logic at the
connection point # 2 “user configurable condition”. That is, set the scheme switch
[SPOS01-LGCFEXOT] to PLC and use “SPOS01IN_TMP_42”.

Output signal to BO
The SPOS01 function, in Figure 4.1-24, can issue an “Operate” signal at the output point
“SPOS01_OEX_BO”, when the SPOS01 function determines that the signal “Local-On-Control”
is true.

GRL200 (Soft 033 & 037)


- 641 -
6F2S1914 (0.37)

(iv) Receiving “operate command Off” from the local-end


Figure 4.1-25 depicts the reception of the operate command for ‘Off ’ from the local-end.

Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Operate command On from remote-end

Select command Off from the remote-end Operate command Off from remote-end

Select command On from the local-end Operate command On from the local-end

Operate command Off from the local-end


Select command Off from the local-end Success
Operate
Signal reception from Operate logic Signal output
decision
the front panel

Failed Do nothing

Select command On by the PLC function Operate command On by the PLC function

Select command Off by the PLC function Operate command Off by the PLC function

Figure 4.1-25 Outline of operate command ‘Off’

Input signal generated at the local-end.


Figure 4.1-26 illustrates the operate logic when an “Operate command Off (Local-OFF-Control)”
signal is applied to the SPOS01 function. The input signal is generated when “Execution for
Off” is keyed on the IED front panel.

GRL200 (Soft 033 & 037)


- 642 -
6F2S1914 (0.37)

Input Operate logic in SPOS01 Output

SPOS1 function (Function ID: 510001)


“SPOS01-FEC_OK_CSF”
(510001_8001011E7F)
Operate Cmd. [SPOS01-CPW]
Command “Remote-Off-Control” with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operation Cmd.
without ILK† condition
ILK† condition (“Off”) passed
SPOS01-Off S
&
ILK† bypassing 1≥ R
ICB_STATE

User configurable condition (PLC#3 connection point)


510001 800101EE56 SPOS01IN_TMP_34
[SPOS01-LGCTRCON]
&
Fixedlogic To BO connection
PLC#3
“SPOS01_FEX_BO”
Operate condition‡
“510001_8101011DD0 §§

[SPOS01-LGCFEXOT]
User configurable condition (PLC#2 connection point)
& Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
PLC#2
ASEQ function§” is in progress
ASEQ_MULTI_SEL

[SPOS01-PLSM]* To “Wait for a command”


Var
Fix “SPOS01_EX_FFL”
[SPOS01-RST] “510001_8601011E91 ††

0 t
“SPOS01-EX_CMP
(5A0101_8001011E93)
1.0s- 100.0s Operation Failed

Figure 4.1-26 Operate ‘Off’ on the front panel in SPOS01††


†Note:The ILK function provides the operation criteria for “Off”.
‡Note:An “operate condition” signal is generated in the operate-condition logic( see
Figure 4.1-29), when Fixlogic is set for scheme switch [SPOS01-LGCTRCON], If
an alternative “Operate-condition” is required it can be programmed by the user
and used to replace the signal generated by the original operated-condition logic.
The alternative ”Operate-condition” can be connected to the above logic using
connection point #3 ”User configurable condition”. That is, set the scheme switch
[SPOS01-LGCTRCON] to PLC and use SPOS01IN_TMP_34.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for the scheme switch
[SPOS01-PLSM], the output period of the signal is defined by the setting
[SPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
When Latch is set, the output signal is kept issuing until the reception of
“Command Off”.
††Note: To identify the input and output signal-points of the other SPOS logics, see Table
4.1-14, Table 4.1-15, Table 4.1-19, and Table 4.1-20.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [SPOS01-RST].
§§Note: The signal “SPOS01_OEX-BO” is issued when Fixlogic is set for scheme switch
[SPOS01-LGCFEXOT]. The “Operate completed” signal can also be issued from
logic programmed by the user in place of the logic shown in Figure 4.1-20. The

GRL200 (Soft 033 & 037)


- 643 -
6F2S1914 (0.37)

user-programmed logic is connected internally to the signal “Operate completed”,


hence this signal is now generated by the user-programmed logic at connection
point # 2 “user- configurable condition”. That is, set the scheme switch [SPOS01-
LGCFEXOT] to PLC and use “SPOS01IN_TMP_42”.

Output signal to BO
The SPOS01 function, in Figure 4.1-26, can issue a signal “Operate” at the output point
“SPOS01_FEX_BO”, when the SPOS01 function determines that the input signal “Local-Off-
Control” is true.

(v) Receiving “operate command On” using the PLC function

Wait for a command

Select logics Wait for a next command

Select command On from remote-end Operate command On from the remote-end

Select command Off from remote-end Operate command Off control from remote-end

Select command On from front panel Operate command On control from front-panel

Select command Off from front panel Operate command Off control from front-panel

On control by PLC function


Success
Select command On by the PLC Operate
PLC logic programmed Operate logic Signal output
function decision
by the user

Failed Do nothing

Select command Off by the PLC Operate command Off control


function by PLC function

Figure 4.1-27 Outline of operate command for ‘On’


Figure 4.1-27 outlines the reception of the operate command ‘On’ with the PLC function; it
describes the operate logic when an “Operate command On (PLC-On Control)” signal is
generated by the PLC function. There are two input points for reception of this command signal,
unlike the signal “operate command closing” (PLC-On Control).; the former connection point
(PLC#3) is used for the reception of the operate-command requiring the interlock check, the
latter connection point (PLC#4) is used or the reception of the operate-command not requiring
interlocking check. That is, for the SPOS01 function, when the user wishes to apply for the
operate logic the signal “Operate command On (PLC-On-Control)” generated in the user-
programmed logic and when the interlock check is required in the operate logic, apply the
signal at the connection point (PLC#3; is DEV01_CL_COMMAND). Alternatively, if the
interlock check is not required, apply the signal at the other connection point (PLC#4 i.e.
DEV01_CL_INTERLOCK); The PLC#3 and PLC#4 is denoted as the PLC#1 and PLC#2 in
Table 4.1-2. Note that the user should set PLC for scheme switch [SPOS01-LGCTRCON].

GRL200 (Soft 033 & 037)


- 644 -
6F2S1914 (0.37)

(vi) Receiving “operate command Off” using PLC logic


Figure 4.1-28 outlines the reception of the operate command for Off using the PLC function.
Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Operate command On from the remote-end

Select command Off from the remote-end Operate command Off from the remote-end

Select command On from the local-end Operate command On from the local-end

Select command Off from the local-end Operate command Off from the local-end

Select command On by the PLC Operate command On by the PLC

Operate command Off by the PLC


Success
Select command Off by the PLC Operation
PLC logic programmed Operate logic Signal output
decision
by the user

Failed Do nothing

Figure 4.1-28 Outline of operate command for Off

Figure 4.1-28 depicts the operate logic when a signal “Operate Command Off (PLC-Off-
Control)” is generated by the PLC function. There are two input points for reception of this
command signal, unlike the signal “Operate Command On (PLC-On-Control)”. That is, if an
inter-lock check is required, apply the signal at connection point (PLC#3; i.e.,
DEV01_OP_INTERLOCK). If, on the other hand an interlock check is not required, apply the
signal at connection point (PLC#4; i.e., DEV01_OP_COMMAND).

PLC#1 an PLC#2 shown in Table 4.1-3 should be treated as PLC#3 and PLC#4 here.
Note that the user should set PLC for scheme switch [SPOS01-LGCFEXOT]

(vii) Operate condition


In a manner similar to which the conditions have been examined for the select command, the
conditions for an operate command should be understood. Figure 4.1-29 illustrates the logic to
examine an operate condition; the operate condition is determined by signal “SPOS01_STATE”,
if the functionality of the original logic does not meet with user-requirements, the following
alternatives are available:
1. The user can replace the original logic with alternative logic.
2. The user can add another signal to the original logic.

Adding another operate condition signal


If the addition of another signal is required, the user can add the signal to the operate condition
logic using connection point “Additional Condition”
1. Add a user-preferred signal using “SPOS01IN_TMP_31”, listed as PLC#1 in Table

GRL200 (Soft 033 & 037)


- 645 -
6F2S1914 (0.37)

4.1-17.
2. Set scheme switch [SPOS01-LGEXFFCT] to Fixedlogic.

Replacing the original logic


If the user wishes to replace the operate condition logic completely, it can be achieved using
PLC connection point “User configurable condition”:
1. Connect the user-customized logic using “SPOS01IN_TMP_41”, listed as PLC#2 in
Table 4.1-17.
2. Set scheme switch [SPOS01-LGEXFFCT] to PLC.

Note: The user must program PLC logic “Control hierarchy condition”. The Control
hierarchy condition to be provided with the user-programmed PLC logic may be
43R/L; it may be connected using PLC connection point “SPOS01IN_TMP_28” in
Figure 4.1-29.
Note: The output of the operate condition logic is provided separately for On-execution
and for Off-execution. To see the outputs, refer to Table 4.1-18.
SPOS01 function (Function ID: 510001)
Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Operate condition
Traveling OR
Unmatched condition detected *5
Function “Automatic sequence control” is in progress
ASEQ_MULTI_SEL Event suppression detected *6
= SPOS01_F_QLT_SPP
Tripping *4 (“General trip”)
(510001 810101F59)
GEN. TRIP
BI board connection error detected*7
= SPOS01_F_BI_ERR
(510001 820101F5A)

Command “ON-control” received &


Command “OFF control” received &
received
SPOS01_STATE
(510001 0001011001)
[SCDEN]*8 Same Directional
Controlling Event
OFF
Additional condition (PLC#1 connection point)
510001 800101EE61 SPOS01IN_TMP_31
[SPOS01- LGEXFFCT]
User configurable operate condition (PLC#2 connection
Fixedlogic
point)510001 810101EE66
SPOS01IN_TMP_41 &
Users must setup this condition correctly
Control hierarchy (e.g. 43RL) (PLC connection point)*9
510001 820101ED50 SPOS01IN_TMP_28
&
IED serious error detected
SERI_ERR

[SPOS01-CTREN]

On

Figure 4.1-29 Operate condition logic for ON/OFF in SPOS01


1Note: “Command blocking” disables any operation except for itself; “Command
Blocking” is implemented as “CBK”in software switch controller (SOFTSW).The
IEC 61850 standard defines communication blocking as “CmdBlk”. For more

GRL200 (Soft 033 & 037)


- 646 -
6F2S1914 (0.37)

information, see Chapter Control and monitoring application: Software switch


controller. See the signal “CBK_STATE in Table 4.1-6.
2Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS.
3Note: Detection of event “device-travelling signifies that other operators are changing
the status of one or more devices. Thus, device operation by the IED should be
inhibited whilst ever the events is detected. The detection signal is donated as
“Travelling OR” in Table 4.1-6.
4Note: If an IED is in the process of issuing a trip command, all control operation is
blocked until the trip operation has been completed. If the IED has a relay
application, the trip command is issued at the output point.
5Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
“GEN.TRIP” in Table 4.1-6 command is not identical to “IED test status”.
6Note: The function “Event suppression” can detect chattering in BI circuits. (See section
4.1.4(i)-2)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The common control (CMNCTRL) function can test and check the operation –
direction of logic. When the user sets off for scheme switch (SCDEN), operation of
the logic is blocked if the logic is running in the same operation – direction
compared with the previous operation direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
9Note: The user must program the PLC logic for “Control hierarchy condition” The user
must connect the “Control hierarchy condition” to the select condition logic using
the connection point “SPOS01IN_TMP_28”. For more information, see chapter
“Control and monitoring application: Control hierarchy” see PLC#3 of Table 4.1-7.
Note that the logic outputs are generated separately for both the On and the Off.

(viii) Signal name and number


Note: The user should note the meaning of the following abbreviations shown in column
“M/O” of each table:
“O” signifies that the signal is provided for optional use.
“M” signifies that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings is used.
“N/A” signifies that the user cannot change the state of the signal.

Table 4.1-14 PLC connection points (Input point for PLC#1 user a configurable condition)
Signal Number Signal Name Description M/O
510001 830101EE5B SPOS01IN_TMP_38 SPOS01 user configurable condition(PLC#1) O
510001 830102EE5B SPOS02IN_TMP_38 SPOS02 user configurable condition(PLC#1) O
510001 830103EE5B SPOS03IN_TMP_38 SPOS03 user configurable condition(PLC#1) O

GRL200 (Soft 033 & 037)


- 647 -
6F2S1914 (0.37)

Signal Number Signal Name Description M/O


…. …. ….
510001 830114EE5B SPOS20IN_TMP_38 SPOS20 user configurable condition(PLC#1) O

Table 4.1-15 PLC connection points (Input point for PLC#2 user configurable condition)
Signal Number Signal Name Description M/O
510001 810101EDDA SPOS01IN_TMP_42 SPOS01 user configurable condition(PLC#2) O
510001 810102EDDA SPOS02IN_TMP_42 SPOS02 user configurable condition(PLC#2) O
510001 810103EDDA SPOS03IN_TMP_42 SPOS03 user configurable condition(PLC#2) O
…. …. ….
510001 810114EDDA SPOS20IN_TMP_42 SPOS20 user configurable condition(PLC#2) O

Table 4.1-16 PLC connection points (Input point for PLC#3 user configurable condition)
Signal Number Signal Name Description M/O
510001 800101EE56 SPOS01IN_TMP_34 SPOS01 user configurable condition(PLC#3) O
510001 800102EE56 SPOS02IN_TMP_34 SPOS02 user configurable condition(PLC#3) O
510001 800103EE56 SPOS03IN_TMP_34 SPOS03 user configurable condition(PLC#3) O
…. …. ….
510001 800114EE56 SPOS20IN_TMP_34 SPOS20 user configurable condition(PLC#3) O

Table 4.1-17 PLC connection points (Input point PLC#1/#2 of additional and operate
conditions)
Signal Number Signal Name Description M/O
510001 800101EE61 SPOS01IN_TMP_31 SPOS01 additional failure condition (PLC#1) O
510001 800102EE61 SPOS02IN_TMP_31 SPOS02 additional failure condition (PLC#1) O
510001 800103EE61 SPOS03IN_TMP_31 SPOS03 additional failure condition (PLC#1) O
… … …
510001 800114EE61 SPOS20IN_TMP_31 SPOS20 additional failure condition (PLC#1) O
510001 810101EE66 SPOS01IN_TMP_41 SPOS01 user configurable operate condition (PLC#2) O
510001 810102EE66 SPOS02IN_TMP_41 SPOS02 user configurable operate condition (PLC#2) O
510001 810103EE66 SPOS03IN_TMP_41 SPOS03 user configurable operate condition (PLC#2) O
… … …
510001 810114EE66 SPOS20IN_TMP_41 SPOS20 user configurable operate condition (PLC#2) O

Table 4.1-18 PLC monitoring points (Output signal for BIO)


Signal Number Signal Name Description
510001 8201011DD3 SPOS01_OEX_BO SPOS01 operate (ON) command for Binary Output.
510001 8201021DD3 SPOS02_OEX_BO SPOS02 operate (ON) command for Binary Output.
510001 8201031DD3 SPOS03_OEX_BO SPOS03 operate (ON) command for Binary Output.
…. …. ….
510001 8201141DD3 SPOS20_OEX_BO SPOS20 operate (ON) command for Binary Output.
510001 8101011DD0 SPOS01_FEX_BO SPOS01 operate (OFF) command for Binary Output.
510001 8101021DD0 SPOS02_FEX_BO SPOS02 operate (OFF) command for Binary Output.
510001 8101031DD0 SPOS03_FEX_BO SPOS03 operate (OFF) command for Binary Output.

510001 8101141DD0 SPOS20_FEX_BO SPOS20 operate (OFF) command for Binary Output.

GRL200 (Soft 033 & 037)


- 648 -
6F2S1914 (0.37)

Table 4.1-19 PLC monitoring points (signals with in operate logic)


Signal Number Signal Name Description
510001 8101011E82 SPOS01_OEC_OK_CS SPOS01 on direction execute command
510001 8101021E82 SPOS02_OEC_OK_CS SPOS02 on direction execute command
510001 8101031E82 SPOS03_OEC_OK_CS SPOS03 on direction execute command
… …. ….
510001 8101141E82 SPOS20_OEC_OK_CS SPOS20 on direction execute command
510001 8001011E81 SPOS01_FEC_OK_CS SPOS01 off direction execute command
510001 8001021E81 SPOS02_FEC_OK_CS SPOS02 off direction execute command
510001 8001031E81 SPOS03_FEC_OK_CS SPOS03 off direction execute command
… … …
510001 8001141E81 SPOS20_FEC_OK_CS SPOS20 off direction execute command

Table 4.1-20 PLC monitoring points (Output signal for response)


Signal Number Signal Name Description
510001 8601011E91 SPOS01_EX_FFL SPOS01 execute fail signal by fixedlogic
510001 8601021E91 SPOS02_EX_FFL SPOS02 execute fail signal by fixedlogic
510001 8601031E91 SPOS03_EX_FFL SPOS03 execute fail signal by fixedlogic
…. …. ….
510001 8601141E91 SPOS20_EX_FFL SPOS20 execute fail signal by fixedlogic

(ix) Setting names


Note: The “xx” of “SPOSxx” represents the SPOS function number. (e.g., if the SPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented by either
a “01” to “20”).

Table 4.1-21 Setting of Operate in SPOSxx


Setting Name Description Default Setting item or value
SPOSxx-PLSM Method of command output(SPOS01-20) Fix Fix/Var/Latch
SPOSxx-CPW Duration of command output(SPOS01-20) 1.0[sec] 0.1~50.0[sec]
SPOSxx-RST Detection time for terminating control (SPOS01-20) 30.0[sec] 0.1~100.0[sec]
SPOSxx-LGCTRCON Logic selector for operate condition (SPOS01-20) Fixedlogic Fixedlogic/PLC
SPOSxx-LGCFEXOT Logic selector for command output (SPOS01-20) Fixedlogic Fixedlogic/PLC
SPOSxx-CTREN Activate control function of SPOS01-20 On Off / On
SPOSxx-LGEXFFCT Logic selector for operate condition (SPOS01-20) Fixedlogic Fixedlogic / PLC

GRL200 (Soft 033 & 037)


- 649 -
6F2S1914 (0.37)

4.1.4 Setup for BIO module


The user should connect the SPOS input/output points with the BI and the BO circuits;
subsequently, the SPOS function is able to issue select and operate commands. The user should
execute the following four steps below.
i BI connection for status-signals
ii BO connection for “Select command On/Off”
iii BO connection for “operate command”
iv Contact health check

Note that the SPOS01 function commences operation when the scheme switch [SPOS01-EN]
is set to On.

(i) BI connection for status-signals


Figure 4.1-30 exemplifies the reception of signals at the SPOS01 function; the user can set a
input-point using the setting [SPOS01-NOPSG]†.

†Note:Normally an input-signal corresponding to phase-A is generated using a normally-


open contact (NO). If the signal is generated by the normally-closed contact, the
user is required to set scheme switch [SPOS01-NSOSGI] On in order that the
input-signal should be decided in inversion.

Connection with Binary input circuit


Suppose an input signal is provided on the first BI circuit at IO#1 slot. In this case, the user
should set the input point (200B01 8001001110†) for the setting [SPOS01-NOPSG], otherwise,
the SPOS01 function cannot run correctly.
Signals by Binary input circuits Signal acquisition logic in SPOS01 Output ‡

“SPOS01_STATE”
Event suppression detector (510001_0001011001)
BI signal connected by
setting [SPOS01-NOPSG]
& 1≥
&
[SPOS01-EN] Status before chattering S

R “SPOS01_F_QLT_SPP”
On
(510001_8101011F59)

[SPOS01-SPPEN] Chattering detector

On
& To select and operate
condition logics

Figure 4.1-30 Acquisition of binary input signal in SPOS01


†Note: The user should set the actual input-points. For Input points see in Chapter
Technical description: Binary IO module.
‡Note: In Figure 4.1-30 two signals can be issued: “SPOS01_STATE” and
“SPOS01_F_QLT_SPP”. One is used in the select condition logic and the operate
condition logic (see Figure 4.1-13 and Figure 4.1-29). Another is used for operation
in the event suppression detector.

GRL200 (Soft 033 & 037)


- 650 -
6F2S1914 (0.37)

Event suppression
If the status of a device “chatters” for a short time, the SPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the SPOS function;
hence, event suppression can be required to reduce the additional burden created.

[SPOS-NELD]

Signal 2 4 6 8
from device On On On On On On On
1 3 5 7

Suppressed
On On On On
signal

[SPOS-TELD] [SPOS-TELR]
Time................. A B C D E

Figure 4.1-31 Iterative signals and signals suppressed

Figure 4.1-31 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time A, the setting [SPOS-NELD] is provided so
that the suppression commences at Time B. The setting [SPOS-TELD] is pertains to the
operation of the detection function from Time A (e.g., Time A to Time C).

The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [SPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time D to E).

To initiate event suppression the user should set On for scheme switch [SPOS01-SPPEN].

(ii) BO connection for “Select command On/Off”


Figure 4.1-32 exemplifies the connection for the select command On and Off. Suppose that
connection with the BOs is achieved by the PLC function using connection point
“SPOS01_SL_BO_FLG”†; as a result, the “ Select command On” and the “Select command Off”
signals are issued at the BOI.

GRL200 (Soft 033 & 037)


- 651 -
6F2S1914 (0.37)

Terminal and
Selection logic in SPOS01 BO1 circuit at IO#1 (Function ID: 200B01) wire

“SPOS01_SL_BO_FLG”
(510001_8501011F76)
“SPOS01_OSL_BO_CSF”

Select command in “BO1”


Signal designated by Select
SPOS01 setting [Input signal 1] ≥1 (200B01_8002001112) command
1≥
On/Off
[Input signal 2] DRIVER BO1
“SPOS01_FSL_BO_CSF” & ≥1
Select command OFF in [Input signal 3]
“BO1-RB”
SPOS01 [Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO1

200B01 310200E11D BO1_SOURCE

Figure 4.1-32 Example of select command connection with BO1


†Note: Table 4.1-26 shows the remaining signals with the excepting
“SPOS01_SL_BO_FLG”.

(iii) BO connection for “operate command On/Off”


Figure 4.1-33 exemplifies the connection for operate command On/Off. Suppose that
connections with the BOs are achieved by the PLC function using connection
point ”SPOS01_OEX_BO” and ”SPOS01_FEX_BO” as a result, the “Operate command On” and
the “Operate command Off” signal is issued at BO2 or BO3.

Terminal and
Operate logic in SPOS01 BO2 and BO3 circuit at IO#1 (Function ID: 200B01) wire

“SPOS01_OEX_BO”
(510001_8201011DD3)
“BO2”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8102011112) command
“Operate command On
[Input signal 2] DRIVER BO2
On” & ≥1
[Input signal 3]
“BO2-RB”
[Input signal 4] [BO2_CPL] On &
Connected by (200B01_8102011113)
Off
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO2


“SPOS01_FEX_BO” 200B01 310201E11D BO2_SOURCE
(510001_8101011DD0)
“BO3”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8202021112) command
“Operate command Off
[Input signal 2] DRIVER BO3
Off” & ≥1
[Input signal 3]
“BO3-RB”
[Input signal 4] [BO3_CPL] On &
Connected by Off
(200B01_8202021113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO3

200B01 310202E11D BO3_SOURCE

Figure 4.1-33 Example of operate commands connected with BO2 and BO3 at IO#1
†Note:Table 4.1-27 shows the remaining signals excepting “SPOS01_OEX_BO” and
“SPOS01_FEX_BO”.

GRL200 (Soft 033 & 037)


- 652 -
6F2S1914 (0.37)

(iv) Contact health check


The SPOS01 function has contact health check feature for the BO circuits; hence, the user is
able to connect an output signal to the contact health check function when Fixedlogic is set for
scheme switch [SPOS01-LGXFEOT]†. Consequently, the SPOS01 function can determine
whether the signal has been successfully output from the BO. If a failure is reported, the
SPOS01 function determines that the signal has not been output successfully to the BO; then,
the command On or Off is canceled immediately and the SPOS01 function returns to the “Wait
for a command” stage.

†Note:Table 4.1-29 shows settings for the health check feature in the other SPOS
functions.

Setting for “Select command On/Off”


For example, the point “SPOS01_SL_BO_FLG” is connected to the BO1 circuit for the issuing
of the command, the user can connect point “BO1-RB” with the contact health check function
using the setting [SPOS01-SLBORD]. Do not key the point “SPOS01_SL_BO_FLG”.
Selection logic in
SPOS01

Contact health check


“SPOS01_SL_BO_FLG”
logic in SPOS01
(510001_8501011F76)

Result of contact
BO1 circuit at & health check in SPOS01 selection
IO_SLOT1

“BO1-RB”
(200B01_8002001113)
Signal connected by
setting [SPOS01-SLBORD]

Connection made by the user

Figure 4.1-34 Example of connection of “Select command On” for the health check feature

Setting for “Operate Command On”


Similarly the point “BO2-RB” must be applied for the setting [SPOS01-OEXBORD].

Operate logic in
SPOS01

“SPOS01_OEX_BO” Contact health check


“510001_8201011DD3” logic in SPOS01

Result of contact
BO2 circuit at & Health check
IO_#1

“BO2-RB”
“200B01_8102011113”
Signal designated by
setting [SPOS01-OEXBORD]

Connection made by the user

Figure 4.1-35 Example connection of “Operate Command On” for the health check

GRL200 (Soft 033 & 037)


- 653 -
6F2S1914 (0.37)

Operate-Off command check


Similarly, the point “BO3-RB” must be applied for the setting [SPOS01-FEXBORD].
Operate logic in
SPOS01

Contact health check


“SPOS01_FEX_BO”
logic in SPOS01
“510001_8101011DD0”

Result of contact
BO3 circuit at & health check
IO_#1

“BO3-RB”
“200B01_8102021113”
Signal designated by
setting [SPOS01-FEXBORD]

Connection made by the user

Figure 4.1-36 Example connection of “Operate command off” for the health check feature

Proper setting for the contact health check (normal setting, example #1)
Figure 4.1-37 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1, BO2 and BO3 contacts. To check that the contact health check function is
working correctly, the respective points of the BO-RBs should be connected as shown in Table
4.1-22, to demonstrate that the settings are physically matched with the BO contacts.

Table 4.1-22 Setting example for contact health check


Example #1 Health check setting for Example #1

“SPOS01_SL_BO_FLG” is connected to “BO1” at IO#1 200B01 8002001113(BO1-RB) set for [SPOS01-SLBORD] OK

“SPOS01_OEX_BO_CSF” is connected to “BO2” at IO#1 200B01 8102011113(BO2-RB) set for [SPOS01-OEXBORD] OK

“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK
BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“SPOS01_SL_BO_FLG”
(510001_8501011F76) SW1 driven with
BO1 at IO_SLOT1
Select BO1 SW 1
command ON/OFF
“BO1-RB”
(200B01_8002001113) SW 2 On
Command
“SPOS01_OEX_BO”
(510001_8201011DD3)
SW 3 Off
Operate-On BO2 SW2 driven with Command
command BO2 at IO_SLOT1
“BO2-RB”
Minus (−)
(200B01_8102011113)
“SPOS01_FEX_BO”
(510001_8101011DD0)
BO3 SW3 driven with
Operate-Off BO3 at IO_SLOT1
command “BO3-RB”
(200B01_8202021113)

Figure 4.1-37 Contact health check setting and 43SW scheme for example #1

Setting for erroneous contact health check (improper setting, example #2)
Figure 4.1-38 shows a setting example for an improper setting of the 43SW scheme. The

GRL200 (Soft 033 & 037)


- 654 -
6F2S1914 (0.37)

settings are implemented incorrectly, as shown in Table 4.1-23. BO1-RB is not chosen,
instead BO1 is actually chosen. In this case, the setting [SPOS01-SLBORD] is meaningless;
hence, the issue of a select command is blocked.

Table 4.1-23 Erroneous setting example for contact health check


Example #2 Health check setting in example #2

“SPOS01_SL_BO_FLG” is connected to “BO1” at IO#1 200B01 8002001112(BO1) set for [SPOS01-SLBORD] NG

“SPOS01_OEX_BO_CSF” is connected to “BO2” at IO#1 200B01 8102011113(BO2-RB) set for [SPOS01-OEXBORD] OK

“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK
BIO module
43SW
Remote/Local-end “BO1” (not BO1-RB) Plus (+)
“SPOS01_SL_BO_FLG” mistakenly chosen with
(510001_8501011F76) “200B01_8002001112” SW1 driven with
BO1at IO_SLOT1
Select BO1 SW 1
Command
ON/OFF
SW 2 On
“SPOS01_OEX_BO” Command
(510001_8201011DD3)
SW 3 Off
Operate-On BO2 SW2 driven with Command
command BO2 at IO_SLOT1
“BO2-RB” designated with Minus (−)
“SPOS01_FEX_BO” “200B01_8102011113”
(510001_8101011DD0)

BO3 SW3 driven with


Operate-Off BO3 at IO_SLOT1
command
“BO3-RB” designated with
“200B01_8202021113”

Figure 4.1-38 Contact health check setting and 43SW diagram for example #2

Setting for extra contact health check (special setting, example #3)
Figure 4.1-39 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “SPOS01_SL_BO_FLG” is actually chosen for the
setting [SPOS01-SLBORD]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command; which is called “operated by internal select function”. The user
does not need to consider of a BO circuit for a select command, when there are no BO circuits
available.
Table 4.1-24 Extra setting example for contact health check
Example #3 Setting for example #3

“SPOS01_SL_BO_FLG” is not connected to any “BO” “SPOS01_SL_BO_FLG” set for [SPOS01-SLBORD] OK

“SPOS01_OEX_BO_CSF” is connected to “BO2” at IO#1 200B01 8102011113(BO2-RB) set for [SPOS01-OEXBORD] OK

“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK

GRL200 (Soft 033 & 037)


- 655 -
6F2S1914 (0.37)

BIO module
43SW
Remote/Local end “SPOS01_SL_BO_FLG” Plus (+)
SW1 is not driven with
(510001_8501011F76) Plus (+)
any BO1
SW 1
Select
command Physical BO is
ON/OFF
virtualized.
“SPOS01_OEX_BO”
(510001_8201011DD3)
SW2 is driven with
BO2 at IO#1
Operate-On BO2 SW 2 On
command Command
“BO2-RB”
“SPOS01_FEX_BO” (200B01_8102011113) SW3 is driven with SW 3 Off
(510001_8101011DD0) BO3 at IO#1 Command

BO3 Minus (−)


Operate-Off
command “BO3-RB”
(200B01_8202021113)

Figure 4.1-39 Contact health check setting and 43SW diagram for example #3

Table 4.1-25 PLC monitoring points (Output signal for event suppression function in SPOSxx)
Signal Number Signal Name Description
510001 0001011001 SPOS01_STATE Status of SPOS01
510001 0001021001 SPOS02_STATE Status of SPOS02
510001 0001031001 SPOS03_STATE Status of SPOS03
…. …. ….
510001 0001141001 SPOS20_STATE Status of SPOS20
510001 8101011F59 SPOS01_F_QLT_SPP Event suppression detected (SPOS01)
510001 8101021F59 SPOS02_F_QLT_SPP Event suppression detected (SPOS02)
510001 8101031F59 SPOS03_F_QLT_SPP Event suppression detected (SPOS03)
…. …. ….
510001 8101141F59 SPOS20_F_QLT_SPP Event suppression detected (SPOS20)

Table 4.1-26 PLC monitoring points (Output of select signal in SPOSxx)


Signal Number Signal Name Description
510001 8501011F76 SPOS01_SL_BO_FLG Select command signal in SPOS01
510001 8501021F76 SPOS02_SL_BO_FLG Select command signal in SPOS02
510001 8501031F76 SPOS03_SL_BO_FLG Select command signal in SPOS03
…. …. ….
510001 8501141F76 SPOS20_SL_BO_FLG Select command signal in SPOS20

Table 4.1-27 PLC monitoring points (Output of operate signal in SPOSxx)


Signal Number Signal Name Description
510001 8201011DD3 SPOS01_OEX_BO SPOS01 operate (ON) command for Binary Output.
510001 8201021DD3 SPOS02_OEX_BO SPOS02 operate (ON) command for Binary Output.
510001 8201031DD3 SPOS03_OEX_BO SPOS03 operate (ON) command for Binary Output.
… … …
510001 8201141DD3 SPOS20_OEX_BO SPOS20 operate (ON) command for Binary Output.
510001 8101011DD0 SPOS01_FEX_BO SPOS01 operate (OFF) command for Binary Output.
510001 8101021DD0 SPOS02_FEX_BO SPOS02 operate (OFF) command for Binary Output.
510001 8101031DD0 SPOS03_FEX_BO SPOS03 operate (OFF) command for Binary Output.
… …. ….
510001 8101141DD0 SPOS20_FEX_BO SPOS20 operate (OFF) command for Binary Output.

GRL200 (Soft 033 & 037)


- 656 -
6F2S1914 (0.37)

(v) Setting names


Note: The “xx” of “SPOSxx” represents the SPOS function number. (e.g., if the SPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented from
“01” to “20”.)

Table 4.1-28 Settings for Binary input signals in SPOSxx


Setting Name Description Default Setting item or value
SPOSxx-EN Activate monitoring function of SPOS01-20 On Off / On
SPOSxx-NOPSG BI position for SPOS01-20 *none BI signal
SPOSxx-SPPEN Activate event suppression for SPOS01-20 On Off / On
SPOS-NELD Number of change to lock status 10 0~99
SPOS-TELD Time to lock status( sliding window ) 10[sec] 1~99[sec]
SPOS-TELR Time to unlock status( sliding window ) 10[sec] 1~99[sec]

Table 4.1-29 Settings for health check function in SPOSxx


Setting Name Description Default Setting item or value
SPOSxx-SLBORD Select BO signal (BO*-RB) from signal list *user-preferred BO readback signal
SPOSxx-OEXBORD Select BO signal (BO*-RB) from signal list *user-preferred BO readback signal
SPOSxx-FEXBORD Select BO signal (BO*-RB) from signal list *user-preferred BO readback signal

GRL200 (Soft 033 & 037)


- 657 -
6F2S1914 (0.37)

4.1.5 Mapping for IEC 61850 communication


The user can operate the SPOS function over IEC 61850 communications† following mapping
using GR-TIEMS. Note that the SPOS function is designed for the class of “Single Point
Controller (SPC)” in the IEC 61850 standard for communication. The user should follow these
steps, each of which is discussed below,
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user will need to create a logical node (LN) for the SPOS01 function. Figure 4.1-40
exemplifies the editing of a LN; the LN “General Input/output (GGIO)” is chosen for the
SPOS01 function. After the user has defined an object “SPCSO”, the SPOS01 logical node can
be available with the name “GGIO” plus “LN Instance”. Create a definition of the object
“SPCSO” in the SPOS01 logical node. Either the SBO mode or the DIR mode can be chosen in
the editing for the LN.

SBO defined in LN

Figure 4.1-40 Defining “SPCSO” object in GGIO1501 logic node

Defining SBO mode


Figure 4.1-41 exemplifies the SPOS01 logic node saved as “GGIO1501”. In the SBO mode, the
user should select the following items for the “GGIO1501$SPCSO” using GR-TIEMS:

GRL200 (Soft 033 & 037)


- 658 -
6F2S1914 (0.37)

 SBOw
 Oper
 Cancel
 Origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns” )

†”sboClass” can be found by scrolling down.

Figure 4.1-41 LN editing screen for SBO (for example)

Defining DIR setting mode


Figure 4.1-42 exemplifies the SPOS01 logic node saved as “GGIO1501”. In the DIR mode, the
following three items should be selected using GR-TIEMS:

 Oper
 origin
 ctlmodel (choice ”DOes or DOns” )

Figure 4.1-42 LN editing screen for DIR mode (for example)

(ii) Mapping output data


The user should group the SPOS01 signals with regard to GOOSE and Report; the user should
map them for IEC 61850 communication using GR-TIEMS. Figure 4.1-43 illustrates how to
map a signal; it indicates that the signals for the SPOS01 function are required to be mapped
for IEC 61850 communication.

GRL200 (Soft 033 & 037)


- 659 -
6F2S1914 (0.37)

Table 4.1-30 Mapping signals for SPCSO object


Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO1501$SPCSO$origin orCat orCategory ST 510001 3001011008 SPOS01_ORCAT
Ctrl/GGIO1501$SPCSO$origin orIdent Octet64 ST 510001 6A01011009 SPOS01_ORIDENT
Ctrl/GGIO1501$SPCSO stVal BOOLEAN ST 510001 0001011001 SPOS01_STATE
Ctrl/GGIO1501$SPCSO q Quality ST 510001 3101011005 SPOS01_QUALITY
Ctrl/GGIO1501$SPCSO t Timestamp ST 510001 9001011006 SPOS01_TIMESTAMP
Ctrl/GGIO1501$SPCSO stSeld BOOLEAN ST 510001 0001011D90 SPOS01_STD_RPT

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.

Drag and drop

Figure 4.1-43 ocCat attribute mapped for SPCSO object of GGIO1501

(iii) Mapping input data


The SPOS01 function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “DEV01_CONTROL_REQ” to the IEC 61850 communication. Table
4.1-31 shows the input-point “DEV01_CONTROL_REQ” and the Object reference
“Ctrl/GGIO1501$SPCSO”; the user should map the input point to the Object reference having
attributes CO and CF†. Figure 4.1-44 shows how to map a signal.

GRL200 (Soft 033 & 037)


- 660 -
6F2S1914 (0.37)

Table 4.1-31 Mapping signals required for SPCSO object for GIG01501
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO1501$SPCSO$SBOw ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$SBOw T Timestamp CO
Ctrl/GGIO1501$SPCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO1501$SPCSO$SBOw Check Check CO
Ctrl/GGIO1501$SPCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO$Oper ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Oper ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$Oper T Timestamp CO
Ctrl/GGIO1501$SPCSO$Oper Test BOOLEAN CO
5100017 001016D08 DEV01_CONTROL_REQ
Ctrl/GGIO1501$SPCSO$Oper Check Check CO
Ctrl/GGIO1501$SPCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO$Cancel ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$Cancel T Timestamp CO
Ctrl/GGIO1501$SPCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO ctlModel ctlModel CF
Ctrl/GGIO1501$SPCSO sboClass sboClass CF

†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).

Drag and drop

Check “Input”

Figure 4.1-44 Input-point mapped for GGIO1501

GRL200 (Soft 033 & 037)


- 661 -
6F2S1914 (0.37)

4.1.6 Setting
SPOS01 (FunctionID:510001)
Setting items Range Unit Contents Default Note

Common items SPOS-NELD 0 - 99 - Number of Event lock detect time 10


SPOS-TELD 1 - 99 s Timer of detect event lock 10
SPOS-TELR 1 - 99 s Timer of recovery from event lock 10
SPOS01-EN Off / On - SPOS01 switch for Device01 Off
DEV01 items SPOS01-DEVNAME [Preferred text] - item name of Dev1 SPOS_Dev1 !
SPOS01-OFFNAME [Preferred text] - state name of state(off) Off !
SPOS01-ONNAME [Preferred text] - state name of state(on) On !
SPOS01-NOPSG [Preferred Signal] - Normally Open Signal of Dev1 Not Assigned
SPOS01-SPPEN Off / On - Automatic event suppression function Off
SPOS01-CTREN Off / On - control mode (control enable) Off
SPOS01-CTRMENU Off / On - control by MENU enable Off
SPOS01-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
SPOS01-SLBORD [Preferred Signal] - select binary output read data(DataID) 5100018501011F76
on direction execute binary output read
SPOS01-OEXBORD [Preferred Signal] - Not Assigned
data(DataID)
off direction execute binary output read
SPOS01-FEXBORD [Preferred Signal] - Not Assigned
data(DataID)
on/off direction execute binary output read
SPOS01-OFEXBORD [Preferred Signal] - Not Assigned
data(DataID)
FixedLogic /
SPOS01-LGCTRCON - Change logic about control condition FixedLogic
PLC
FixedLogic /
SPOS01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
SPOS01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about off direction execute
SPOS01-LGFEXOT - FixedLogic
PLC output
FixedLogic /
SPOS01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
SPOS01-PLSM Fix / Var / Latch - pulse mode Var
SPOS01-CPW 0.1 - 50.0 s control pulse width 1.0
SPOS01-RST 1.0 - 100.0 s response check timer 30.0
SPOS01-APBD Process / Bay - status change origin Process
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The SPOS function is available for a 2nd Device and other devices. We have
omitted the others because their setting tables are the same as the 1st device table
with the exception of the device number.

GRL200 (Soft 033 & 037)


- 662 -
6F2S1914 (0.37)

4.1.7 Signal
 Signal monitoring points in SPOS01
SPOS01(FunctionID:510001)
Element ID Name Description
8001011DE0 DEV1PLCCTRLFAIL DEV1PLCCTRLFAIL
0001001F74 SPOS_SEL_OR SPOS multi select check signal for Auto sequence
0001011001 SPOS01_STATE SPOS01 state
0001011D90 SPOS01_SLD_RPT SPOS01 selected signal(stSeld) for SAS
0001011D97 SPOS01_EX_BO_OPOK SPOS01 execute binary output signal for SAS
0001011F52 SPOS01_TRA SPOS01 travelling info
0001011F53 SPOS01_TRA_CTR SPOS01 travelling info for control
0001011F75 SPOS01_SE_RCV SPOS01 select or execute command received
3101011D00 SPOS01_MMC_ST SPOS01 state for MIMIC
3101011D01 SPOS01_LCD_ST SPOS01 state for LCD
3101011D80 SPOS01_TMP_06 SPOS01 control event data (selected)
3101011D81 SPOS01_TMP_07 SPOS01 control event data (select fail)
3101011D82 SPOS01_TMP_08 SPOS01 control event data (select release)
3101011D83 SPOS01_TMP_09 SPOS01 control event data (execute output on)
3101011D84 SPOS01_TMP_10 SPOS01 control event data (execute command ng)
3101011D86 SPOS01_TMP_11 SPOS01 control event data (execute fail)
8001011D02 SPOS01_ST_OFF SPOS01 status Off
8001011D51 SPOS01_SC_OWS SPOS01 select command by OWS(HMI)
8001011D52 SPOS01_SC_RCC SPOS01 select command by RCC
8001011D53 SPOS01_SC_RMT SPOS01 select command by Remote
8001011D54 SPOS01_SC_LCD SPOS01 select command by LCD
8001011D55 SPOS01_EC_OWS SPOS01 execute command by OWS(HMI)
8001011D56 SPOS01_EC_RCC SPOS01 execute command by RCC
8001011D57 SPOS01_EC_RMT SPOS01 execute command by Remote
8001011D58 SPOS01_EC_LCD SPOS01 execute command by LCD
8001011D59 SPOS01_EC_PLC SPOS01 execute command by PLC
8001011E76 SPOS01_SLD_CS SPOS01 selected condition signal
8001011E7D SPOS01_SLR_CS SPOS01 select release condition signal
8001011E7E SPOS01_FEC_OK_CSF SPOS01 off direction execute command OK condition signal by fixedlogic
8001011E7F SPOS01_OEC_OK_CSF SPOS01 on direction execute command OK condition signal by fixedlogic
8001011E81 SPOS01_FEC_OK_CS SPOS01 off direction execute command OK condition signal
8001011E93 SPOS01_EX_CMP SPOS01 execute complete signal
8001011F54 SPOS01_SC_ST_ERR SPOS01 select command mode err
8001011F55 SPOS01_EC_ST_ERR SPOS01 execute command mode err
8001011F56 SPOS01_NSL_CS06 SPOS01 no direction select condition signal 06
8001011F66 SPOS01_SLD_CS04 SPOS01 selected condition signal 04
8101011D03 SPOS01_ST_ON SPOS01 status On
8101011DD0 SPOS01_FEX_BO SPOS01 off direction execute binary output signal
8101011E7B SPOS01_SLF_CS SPOS01 no direction select fail condition signal
8101011E82 SPOS01_OEC_OK_CS SPOS01 on direction execute command OK condition signal
8101011E85 SPOS01_FEC_F_CSF SPOS01 off direction execute command fail condition signal by fixedlogic
8101011E86 SPOS01_OEC_F_CSF SPOS01 on direction execute command fail condition signal by fixedlogic
8101011E9A SPOS01_ECF_FCT_EIS SPOS01 execute command fail factor signal except interlock/synchronism check
8101011F59 SPOS01_F_QLT_SPP TEMP31
8101011F64 SPOS01_FSL_CS21 SPOS01 off direction select condition signal 21
8201011DD3 SPOS01_OEX_BO SPOS01 on direction execute binary output signal
8201011E88 SPOS01_FEC_F_CS SPOS01 off direction execute command fail condition signal
8201011F5A SPOS01_F_BI_ERR TEMP32
8201011F5F SPOS01_NSL_CS10 SPOS01 no direction select condition signal 10
8301011E89 SPOS01_OEC_F_CS SPOS01 on direction execute command fail condition signal
8301011E9C SPOS01_CCF_FCT_CS TEMP21

GRL200 (Soft 033 & 037)


- 663 -
6F2S1914 (0.37)

 Signal monitoring points in SPOS01


SPOS01(FunctionID:510001)
Element ID Name Description
8301011E9D SPOS01_CTR_SGN SPOS01 control logic stage(unselected)
8401011F77 SPOS01_OFEX_BO SPOS01 on/off direction execute binary output signal
8501011E8F SPOS01_EX_SFL SPOS01 execute success signal by fixedlogic
8501011F5B SPOS01_OSL_CS42 SPOS01 on direction select condition signal 42
8501011F60 SPOS01_FSL_CS19 SPOS01 off direction select condition signal 19
8501011F65 SPOS01_OSL_CS40 SPOS01 on direction select condition signal 40
8501011F76 SPOS01_SL_BO_FLG SPOS01 select binary output signal by fixedlogic
8601011DC6 SPOS01_OSL_BO_CSF SPOS01 on direction select binary output condition signal by fixedlogic
8601011E91 SPOS01_EX_FFL SPOS01 execute fail signal by fixedlogic
8601011E95 SPOS01_CC_SS TEMP18
8601011F5C SPOS01_OSL_CS43 SPOS01 on direction select condition signal 43
8601011F5E SPOS01_NSL_CS07 SPOS01 no direction select condition signal 07
8601011F62 SPOS01_SLF_FCT_FLG03 SPOS01 select fail factor signal by fixedlogic 03
8701011E96 SPOS01_CC_FS TEMP19
8701011E98 SPOS01_SLF_FCT_EIS SPOS01 select fail factor signal except interlock/synchronism check
8701011F63 SPOS01_SLF_FCT_FLG04 SPOS01 select fail factor signal by fixedlogic 04
8801011E9B SPOS01_CC_ST_ERR TEMP20
8801011F5D SPOS01_OSL_CS41 SPOS01 on direction select condition signal 41
8801011F6B SPOS01_SLF_FCT_FLG07 SPOS01 select fail factor signal by fixedlogic 07
8901011DC0 SPOS01_NSL_BO_CSF SPOS01 select binary output condition signal by fixedlogic
8901011F6C SPOS01_EX_CS01 SPOS01 execute condition signal 01
8901011F72 SPOS01_SLF_FCT_FLG08 SPOS01 select fail factor signal by fixedlogic 08
8A01011DC4 SPOS01_FSL_BO_CSF SPOS01 off direction select binary output condition signal by fixedlogic
8A01011F61 SPOS01_FSL_CS20 SPOS01 off direction select condition signal 20
8A01011F6D SPOS01_EX_CS02 SPOS01 execute condition signal 02
8B01011EA2 SPOS01_CTR_SGU SPOS01 control logic stage(under selection)
8B01011F68 SPOS01_EX_CS05 SPOS01 execute condition signal 05
8B01011F6E SPOS01_EX_CS03 SPOS01 execute condition signal 03
8E01011F57 SPOS01_SLD_TMO SPOS01 time out after selected
8E01011F67 SPOS01_EX_CS04 SPOS01 execute condition signal 04
8F01011F58 SPOS01_EX_CMP_TMO SPOS01 timeout after execute completion

 Connection point in PLC logic


SPOS01(Function ID: 510001)
Element ID Name Description
800101EE32 DEV01_CL_COMMAND dev01 close command

800101EE33 DEV01_CL_INTERLOCK dev01 close command with interlock bypass

800101EE30 DEV01_OP_COMMAND dev01 open command

800101EE31 DEV01_OP_INTERLOCK dev01 open command with interlock bypass

820101ED50 SPOS01IN_TMP_28 SPOS01IN_TMP_28

800101EE53 SPOS01IN_TMP_29 SPOS01IN_TMP_29

810101EE54 SPOS01IN_TMP_30 SPOS01IN_TMP_30

800101EE61 SPOS01IN_TMP_31 SPOS01IN_TMP_31

810101EE62 SPOS01IN_TMP_32 SPOS01IN_TMP_32

800101EE55 SPOS01IN_TMP_33 SPOS01IN_TMP_33

800101EE56 SPOS01IN_TMP_34 SPOS01IN_TMP_34

810101EE57 SPOS01IN_TMP_35 SPOS01IN_TMP_35

820101EE5A SPOS01IN_TMP_37 SPOS01IN_TMP_37

830101EE5B SPOS01IN_TMP_38 SPOS01IN_TMP_38

GRL200 (Soft 033 & 037)


- 664 -
6F2S1914 (0.37)

 Connection point in PLC logic


SPOS01(Function ID: 510001)
Element ID Name Description
800101EE65 SPOS01IN_TMP_40 SPOS01IN_TMP_40

810101EE66 SPOS01IN_TMP_41 SPOS01IN_TMP_41

810101EDDA SPOS01IN_TMP_42 SPOS01IN_TMP_42

820101EE5E SPOS01IN_TMP_44 SPOS01IN_TMP_44

830101EE5F SPOS01IN_TMP_45 SPOS01IN_TMP_45

800101EE69 SPOS01IN_TMP_46 SPOS01IN_TMP_46

 Mapping points in SPOS01


SPOS(FunctionID:510001)
Element ID Name Description
7001016D08 DEV01_CONTROL_REQ SPOS01 control command received. (Mapping Data)

Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the SPOS function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.

Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “SPOS01_SC_OWS” point for
the 2nd device, use the description of “SPOS01_SC_OWS” in place of
“SPOS02_SC_OWS”. The user can obtain the ID value of
“SPOS02_SC_OWS” by using the following steps:
Step 1 Find the element ID for SPOS01_SC_OWS (i.e.,
“8001011D51”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8001021D51” of
“SPOS02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.

GRL200 (Soft 033 & 037)


- 665 -
6F2S1914 (0.37)

Double position controller with synchronizing-checking (DPSY)


The double position controller with synchronizing-check (DPSY†) function is used when the
user wishes to control a device from the “Closed” or “Open” condition. Generally, the device
controlled by the DPSY function is either a 43-switch or a CB. The DPSY function has two
measurements: an operation counter and an operation timer. The two features are useful when
the user wishes to assess the operating time of the device and the total service duration in the
operated state; these features are performed by counting the state-changes for the device.

†Note:The DPSY function is similar to the DPOS function; the DPSY function is required
to operate together with the synchronizing function (SYNDIF), which has relay
elements corresponding to voltages, and can coordinate the timing for closing or
opening. For more detailed information with regard to the SYNDIF function, see
Chapter Control and monitoring application: Synchronizing check for different
network.

The BO circuits are used for issuing commands; the BI circuits are used for receiving
responses; hence, the user should set the BIO† together with the DPSY function. The DPSY
function includes three logic groups: 1. Selection logic, 2. Cancel logic, and 3. Operate logic.

Tips: If the user wishes to apply the DPSY function quickly, go to sections 4.2.6 and
4.2.7, where setting of the BI and BO circuits and the mapping of signals for
IEC61850 communication is described.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features depends on the selection of hardware and the
configuration of functions. Several IED models do not have its features. To determine whether
its features are implemented in the IED, locate the IED ordering number; and check the order
number at the “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 4.2-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
– Number of functions – 2
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 666 -
6F2S1914 (0.37)

Two devices can be controlled separately; i.e., the DPSY function has two separate sets of logic
for control (i.e., DPSY01 and DPSY02 functions). For simplicity, only the DPSY01 function is
discussed here; the features in the DPSY02 function are identical to the DPSY01 function.

4.2.1 Select logic for SBO/DIR modes


The user should set scheme switch [DPSY01-CTREN] On prior to DPSY01 operation. Table
4.2-11 shows all of the scheme switches in the DPSY function.

(i) Receiving “select command Closing” from the remote-end


Figure 4.2-1 outlines the reception of the select command ‘Closing’ from the remote- end.

Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end Cancel logic


Failed
Cancel command
Signal reception Select
Selection logic Signal output
IEC61850 decision Success

Cancel logic
Select command Open from the remote-end

Select command Closing from the local-end Operate logic


Operate command
Select command Open from the local-end

Select command Closing by the PLC function


Operate logic
Select command Open by the PLC function

Figure 4.2-1 Outline of select command ‘Closing’

Input point required mapping


Figure 4.2-2 shows the select logic when a “Select command closing (Remote-Closing-Control)”
signal is applied to the DPSY01 function.

GRL200 (Soft 033 & 037)


- 667 -
6F2S1914 (0.37)

Input Selection logic in DPSY01 Output

DPSY01 function (Function ID: 511001)


Command “Remote-Closing Control”
For SBO operation
511001 7002016D08 DEV01_CONTROL_REQ Select command with ILK†
condition & synchro-check‡‡ & 1≥ &
To “Wait for a next
For DIR operation command”
Operate command with ILK† To BO connection
condition & synchro-check‡‡ & DPSY01_OSL_BO_FLG”
ILK† condition (“Closeing”) passed (511001 8602011DC6)
From SYNCHK DPSY01-Close
0 t
Voltage condition Select “Closing”
SYNC01-SLD_VCS‡‡
(560001 840B011F58) For SBO operation 0.1s
Select command with
synchro-check‡‡ &
Timer§§ To “Wait for a command”
For DIR operation 0 t 0 t
Select “Failed”
Operate command with & 0.0 to 5.0 s 0.6s
synchro-check‡‡

For SBO operation


Select command with ILK†
condition &

For DIR operation


Operate command with ILK†
&
condition

For SBO operation


Select command without condition
&

For DIR operation


Operate command without &
condition

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (ASEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.2-2 Select logic ‘Closing’ from the remote-end in DPSY01††


†Note:The Software interlocking (ILK) function can provide the operation criteria for
“Closing”. The ILK function is discussed separately; note that the operation
criteria is defined by the ILK function itself (i.e., the user cannot set the
condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPSY01 operation is blocked for the ASEQ function being
in operation. For more information of the ASEQ function, see Chapter Control and
monitoring application: Automatic sequence control function.
*Note:The DPSY01 function can run in either the “SBO mode” or the “DIR mode”. The
user can use a signal called “ctlmodel” when communication is implemented using
IEC61850. To use this signal, the user must map it for IEC61850 communication.
††Note: To identify the input and output points of the DPSY02 logic, see Table 4.2-6 and
Table 4.2-10.

GRL200 (Soft 033 & 037)


- 668 -
6F2S1914 (0.37)

‡‡Note: The synchronism voltage check is executed by the SYNCHK function.


§§Note: A timer is provided to determine an operation failure. The maximum value of the
settings [SYNC01_TLRDIDRLI] or [SYNC01_TDRDI] is used as the decision time.
For more information on settings, see the SYNDIF function.

This logic has the input-point “DEV01_CONTROL_REQ” for the reception of a select
command. That is, the input-point must be mapped for communication. The function will fail
to operate if mapping is not performed correctly. We will discuss how to map the input-points
for IEC61850 communication in section 4.2.7.

Output signal to BO
The DPSY01 function can issue an output signal “Selection success” at the output point
“DPSY01_OSL_BO_FLG”, when the DPSY01 function determines that the “Remote-Closing-
Control” signal received is true. If the DPSY01 function determines that the “Remote-Closing-
Control” signal is not true, the DPSY01 function returns to the “Wait for a command” stage.

The user should note that the operation decision of the SYNDIF01 function is required
for the DPSY01 function; the operation decision is determined by the measurement of running
voltage and incoming voltage. Table 4.2-2 shows the relay-elements used in the SYNDIF01
function.

Table 4.2-2 Voltage checking elements in SYNDIF01


Relay-Element Description
SyncRy1-VR Running Voltage channel selector for DPSY01
SyncRy1-VI Incoming Voltage channel selector for DPSY01
OVR1 Voltage for checking Live-Running Voltage for DPSY01
UVR1 Voltage for checking Dead-Running Voltage for DPSY01
OVI1 Voltage for checking Live-Incoming Voltage for DPSY01
UVI1 Voltage for checking Dead-Incoming Voltage for DPSY01

GRL200 (Soft 033 & 037)


- 669 -
6F2S1914 (0.37)

(ii) Receiving “select command Open” from the remote-end


Figure 4.2-3 outlines the reception of the select command ‘Open’ from the remote-end.

Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end


Cancel logic
Select command Open from the remote-end Cancel command
Failed

Signal reception Select


Select logic Signal output
IEC61850 decision Success Cancel logic

Select command Closing from the local-end


Operate logic

Select command Open from the local-end Operate command

Select command Closing by the PLC function


Operate logic
Select command Open by the PLC function

Figure 4.2-3 Outline of select command for Open

Input point required mapping


Figure 4.2-4 shows the select logic when a “Select command (Remote-Open-Control)” signal is
applied to the DPSY01 function. The input-point “DEV01_CONTROL_REQ” is used for the
reception of the “select command (Remote-Open-Control)” signal.
Input Selection logic in DPSY01 Output

DPSY01 function (Function ID: 511001)


Command “Remote-Open-Control”
For SBO operation
511001_7002016D08 DEV01_CONTROL_REQ Select command
with ILK† condition & 1≥ &

For DIR operation


To BO connection
Operate command
with ILK† condition & “DPSY01_FSL_BO_FLG”
ILK† condition (“Open”) passed (511001 8A02011DC4)
DPSY01-Open 0 t Select “success”

For SBO operation 0.1s

Select command &


without ILK† condition
To “Wait for a command”
For DIR operation 0 t
Select “Failed”
Operate command
& 0.6s
without ILK† condition

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (ASEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.2-4 Select ‘Open’ from the remote-end in DPSY01††


†Note:The ILK function can provide the operation criteria for “Open”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPSY01 operation is blocked for the ASEQ function when

GRL200 (Soft 033 & 037)


- 670 -
6F2S1914 (0.37)

it is in operation. For more information of the ASEQ function, see Chapter Control
and monitoring application: Automatic sequence control function.
††Note: To know the input and output points of the DPSY02 logic, see Table 4.2-6 and
Table 4.2-10.

Output signal to BO
The DPSY01 function, in Figure 4.2-4, can issue a “Select success” signal at the output point
“DPSY01_FSL_BO_FLG” when the DPSY01 function determines that the “Selection command
Open (Remote-Open-Control)” signal is true. If the DPSY01 function determines that the
“Remote-Open-Control” signal is not true, the DPSY01 function returns to the “Wait for a
command” stage.

(iii) Receiving “Select command Closing” from the local-end


Figure 4.2-5 outlines the reception of the select command ‘Closing’ from the local-end.

Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end


Cancel logic
Select command Open from the remote-end
Cancel command

Select command Closing from the local-end


Failed
Cancel logic
Signal reception Select
Select logic Signal output
from the front panel decision Success
Operate logic
Select command Open from the local-end Operate command

Select command Closing by the PLC function

Select command Open by the PLC function Operate logic

Figure 4.2-5 Outline of select command for ‘Closing’

Input signal generated at the local-end


Figure 4.2-6 shows the select logic when a “Select command Closing (Local-Closing-Control)”
signal is applied to the DPSY01 function. The signal is provided when a “Selection for Closing”
key is pressed on the IED front panel; the user is not required to map the signal from the
IEC61850 communication. Note that the user should set the scheme switch [DPSY01-
CTRAHMI] to SBO when operation from the IED front panel is required, we discuss how to set
this in chapter User interface: Control sub-menu.

GRL200 (Soft 033 & 037)


- 671 -
6F2S1914 (0.37)

Input Selection logic in DPSY01 Output

DPSY01 function (Function ID: 511001)


For SBO operation
Command “Local-Closing-Control” Selection command
with ILK† condition & 1≥ &
For DIR operation SBO To “Wait for a next
Operation command command”
ILK† condition (“Closing”) passed with ILK† condition & To BO connection
DPSY01-Close DPSY01_OSL_BO_FLG”
DIR
(511001 8602011DC6)
ILK† bypassing 1≥
ICB_STATE 0 t
Selection “Closing”
From SYNCHK 0.1s

SYNC01-SLD_VCS‡‡
(560001 840B011F58)
1≥ Timer§§ To “Wait for a command”
SYNC‡‡ bypassing 0 t 0 t
Selection “Failed”
SCB_STATE
0.0 to 5.0 s 0.6s

[DPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.2-6 Select ‘Closing’ on the front panel in DPSY01††


†Note:The ILK function provides the operation criterion for “On”. For testing, nullifying
the ILK function is possible using “Interlock bypassing”. “Interlock bypassing” is
indicated by the status “ICB” in a software switch controller (SOFTSW).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPSY01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the DPSY02 logic, see Table 4.2-10.
‡‡Note: The SYNDIF function provides the synchronism criteria for “Closing”. For
testing, nullifying the SYNDIF function is possible using “Synchro-check
bypassing”. “Synchro-check bypassing” is indicated by the status “SCB” in the
SOFTSW.

Output signal to BO
When the signal “select condition” is true, the DPSY01 function can issue a “Selection success”
signal at the output-point “DPSY01_OSL_BO_CSF”.
Note: The signal “DPSY01_OSL_BO_CSF” is the same as the signal shown in Figure
4.2-2. If the “Local-Closing-Control” signal is not true, the DPSY01 function
returns to the “Wait for a command” stage.

GRL200 (Soft 033 & 037)


- 672 -
6F2S1914 (0.37)

(iv) Receiving “Select command Open” from the local-end


Figure 4.2-7 outlines the reception of the select command ‘Open’ from the local-end.

Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end


Cancel logic
Select command Open from the remote-end
Cancel command
Select command Closing from the local-end

Select command Open from the local-end Cancel logic


Failed

Signal reception Select


Select logic Signal output
from the front panel decision Success Operate logic
Operate command

Select command Closing by the PLC function

Select command Open by the PLC function Operate logic

Figure 4.2-7 Outline of select command ‘Open’

Input signal generated at the local-end


Figure 4.2-8 shows the select logic when a “Select command open (Local-Open-Control)” signal
is applied to the DPSY01 function. The signal is provided when the user presses a “Selection
for Open” key on the IED front panel; the user is not required to map the signal from IEC61850
communication.
Input Selection logic in DPSY01 Output

DPSY01 function (Function ID: 511001)


For SBO operation
Command “Local-Open-Control” Selection command
with ILK condition & 1≥ &
For DIR operation SBO
Operation command To BO connection

ILK condition (“Open”) passed with ILK condition & “DPSY01_FSL_BO_FLG”


DPSY01-Open (511001 8A02011DC4)
DIR
ILK bypassing 1≥ 0 t
Selection “success”
ICB_STATE
0.1s

To “Wait for a command”


0 t Selection “Failed”

0.6s

[DPSY01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850) SBO

Select condition‡
“Automatic sequence control function (ASEQ§)” in progress
ASEQ_MULTI_SEL

Figure 4.2-8 Select ‘Open’ on the front panel in DPSY01††


‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPSY01 operation is blocked for the ASEQ function when

GRL200 (Soft 033 & 037)


- 673 -
6F2S1914 (0.37)

it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the DPSY02 logic, see Table 4.2-10.

Output signal to BO
When the “select condition” signal is true, the DPSY01 function can issue a “Select success”
signal at the output-point “DPSY01_FSL_BO_FLG”.
1Note: The signal “DPSY01_FSL_BO_FLG” is the same as the signal shown in Figure
4.2-4. If the signal “Local-Open-Control” is not true, the DPSY01 function returns
to the “Wait for a command” stage.

(v) Receiving “Select command Closing” by PLC function


Figure 4.2-9 outlines the reception of the select command ‘Closing’ by the PLC function.

Wait for a command

Select stage Wait for a next command


Select command Closing from the remote-end
Cancel logic
Select command Open from the remote-end
Cancel command
Select command Closing from the local-end

Select command Open from the local-end


Cancel logic
Select command Closing by PLC function
Failed
Operate logic
PLC logic programmed Select
Select logic Signal output Operate command
by the user decision Success

Select command Open by the PLC function Operate logic

Figure 4.2-9 Outline of select command ‘Closing’

Input signal from the PLC function


Figure 4.2-10 shows the select logic when a “Select command Closing (PLC-Closing-Control)”
signal is generated by the PLC function. There are four input points for reception of this signal.
The first connecting point, (PLC#1) is used for the reception of the select-command requiring
the ILK and the SYNDIF check. The second connection point, (PLC#2) is used for the reception
of the select-command requiring the SYNDIF check only. The third connection point (PLC#3)
is used for the reception of the select-command requiring the ILK check only and the fourth
connection point (PLC#4) is used for the reception of the select command with no check. That
is, for example, for the DPSY01 function, when the “Select command ‘Closing’ (PLC-Closing-
Control)” signal generated in the user-programmed logic is applied and when the ILK and the
SYNDIF checks are both required in the select logic, use the connection point (PLC#1: e.g.,
DEV01_CL_SYNC_INTER). PLC#1 to PLC#4 are shown in Table 4.2-3.

GRL200 (Soft 033 & 037)


- 674 -
6F2S1914 (0.37)

Signals from user-PLC logic Select logic in DPSY01 Output

DPSY01 function (Function ID: 511001)

Closing-control command requiring ILK† and synchro 1≥ &


checks (PLC#1 connection point) For DIR operation (PLC#1)
Operate command with ILK† To “Wait for a next
511001 800201EE35 DEV01_CL_SYNC_INTER condition & synchro-checking command”
& To BO connection
Closing-control command requiring synchro check
For DIR operation (PLC#2) DPSY01_OSL_BO_FLG”
(PLC#2 connection point)
Operate command with (511001 8602011DC6)
511001 800201EE34 DEV01_CL_SYNC synchro-checking & 0 t Select “Closing”
From SYNCHK
0.1s
SYNC01-SLD_VCS
(560001 840B011F58)
Closing-control command requiring ILK† check
For DIR operation (PLC#3) Timer§§
(PLC#3 connection point) To “Wait for a command”
Operate command with ILK† 0 t 0 t
511001 800201EE33 DEV01_CL_INTERLOCK & Select “Failed”
condition
0.0 to 5.0 s 0.6s
Closing-control command with no check For DIR operation (PLC#4)
(PLC#4 connection point)
Operate command without
511001 800201EE32 DEV01_CL_COMMAND condition

Select condition‡
ILK condition (“Closing”) passed
DPSY01-Close

Figure 4.2-10 Select ‘Closing’ using the PLC function in DPSY01††


††Note: To identify the input and output signals of the DPSY02 logic, see Table 4.2-3 and
Table 4.2-10.
†Note:The Software interlocking (ILK) function can provide the operation criteria for
“Closing”. The ILK function is discussed separately; note that the operation
criteria is defined in the ILK function itself (i.e., the user cannot set the
condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§§Note: A timer is provided to determine a failure to operate. The maximum value of the
settings [SYNC01_TLRDIDRLI] or [SYNC01_TDRDI] is used for the decision time.
For more information on settings, see the SYNDIF function.

Output signal to BO
The DPSY01 function, in Figure 4.2-10, can issue a “Select success” signal at the output-point
“DPSY01_OSL_BO_CSF”1.
1Note: The signal “DPSY01_OSL_BO_CSF” is the same signal as that shown in Figure
4.2-2.

GRL200 (Soft 033 & 037)


- 675 -
6F2S1914 (0.37)

(vi) Receiving “Select command Open” by PLC function


Figure 4.2-11 outlines the reception of the select command ‘Open’ by the PLC function.

Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end Cancel logic


Select command Open from the remote-end Cancel command

Select command Closing from the local-end

Select command Open from the local-end Cancel logic

Select command Closing by the PLC function


Operate logic
Select command Open by the PLC function Operate command
Failed

PLC logic programmed Select


Select logic Signal output
by the user decision Success Operate logic

Figure 4.2-11 Outline of select command ‘Open’

Input signal from the PLC function


Figure 4.2-12 shows the select logic when a “Select command Open (PLC-Open-Control)” signal
is generated by the PLC function There are two input-points for the reception of this signal,
unlike in the signal “Select command Closing (PLC-Closing-Control)” where four are available.
That is, if interlock checking is required, use the connection point (PLC#1:e.g.,
DEV01_OP_INTERLOCK). Alternatively, if the interlock check is not required, use the
connection point (PLC#2:e.g., DEV01_OP_COMMAND). PLC#1 and the PLC#2 are shown in
Table 4.2-4.

Signals from user PLC logic Select logic in DPSY01 Output

DPSY01 function (Function ID: 511001)


1≥ &
Open-control command requiring ILK checking For DIR operation
(PLC#1 connection point)
Operation command To BO connection
511001 800201EE31 DEV01_OP_INTERLOCK
with ILK condition
& “DPSY01_FSL_BO_CSF”
ILK† condition (“Open”) passed (511001_8A02011DC4)
DPSY01-Open 0 t Select “success”
Open-control command requiring no ILK checking For DIR operation 0.1s
(PLC#2 connection point)
Operation command
511001 800201EE30 DEV01_OP_COMMAND
without ILK condition &
To “Wait for a command”

Select “Failed”

PLC in DIR operate

Select condition

Figure 4.2-12 Select Open by PLC function in DPSY01††


††Note: To identify the input and output points of the DPSY02 logic, see Table 4.2-4 for
the inputs (PLC#1 and PLC#2) and Table 4.2-11 for the outputs.
Output signal to BO

GRL200 (Soft 033 & 037)


- 676 -
6F2S1914 (0.37)

The DPSY01 function, in Figure 4.2-12, can issue a “Select success” signal at the output point
“DPSY01_FSL_BO_CSF”1.
1Note: The output point “DPSY01_FSL_BO_CSF” is the same signal as shown in Figure
4.2-4.

(vii) Select condition


Figure 4.2-13 shows the select condition logic in the DPSY01 function. The DPSY01 function
checks the condition for the select command using the signal “DPSY01_3PH_STATE” (See
Table 4.2-34). If the original logic does not meet with the requirements of the user, the following
alternatives are available:
1. The user can replace the original logic with alternative logic.
2. The user can add additional logic to the original logic.

How to replace the original logic


If the user wishes to replace the select condition logic completely, the user can replace it using
the PLC connection point “User Configurable Condition”.
1. Connect the user-customized logic using “DPSY01IN_TMP_32”, which is listed as
PLC#2 in Table 4.2-8.
2. Set the scheme switch [DPSY01-LGSLFFCT] to PLC.

How to add another select condition signal


If adding another condition is required, the user can add a signal to the select condition logic
using the PLC condition point “User Additional Condition”.
1. Add a user-preferred signal using “DPSY01IN_TMP_31”, which is listed as PLC#1 in
Table 4.2-8.
2. Set the scheme switch [DPSY01-LGSLFFCT] to Fixedlogic.

GRL200 (Soft 033 & 037)


- 677 -
6F2S1914 (0.37)

From SOFTSW*1 DPSY01 function (Function ID: 511001)


Command blocking
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Traveling OR Unmatched condition detected *5 Select condition

Function “Automatic sequence control” is in progress


ASEQ_MULTI_SEL Event suppression detected *6
From TRC*4 = DPSY01_F_QLT_SPP
Tripping *4 (“General trip”)
(511001 8102011F5F)
GEN. TRIP
BI board connection error detected*7
= DPSY01_F_BI_ERR
BI board connecti
(511001 8202011F60)
Event supp

Unmatched con
Command “Open control” received &
Command “Closing control” received &
received
DPSY01_3PH_STATE
(511001 3102011001)
[SCDEN]*8 Same Directional
Controlling Event
OFF
Additional condition (PLC#1 connection point)
511001 800201EE61 DPSY01IN_TMP_31
[DPOS01-LGSLFFCT]
User configurable condition (PLC#2 connection point)
Fixedlogic
511001 810201EE62 DPSY01IN_TMP_32 &

Users must setup this condition correctly


Control hierarchy (e.g. 43RL) (PLC#3 connection point)*9
511001 820201ED50 DPSY01IN_TMP_28
From CMNCTRL
&
IED serious error detected
SERI_ERR

[DPSY01-CTREN]

On

Figure 4.2-13 Select condition logic for ‘Closing/Open’ in DPSY01*10


1Note: “Command Blocking” disables any operation except its own; the “Command
Blocking” is initiated by the status of “CBK” in a software switch controller
(SOTFSW). The IEC 61850 standard defines “Command Blocking” as “CmdBlk”.
For more information on “CBK”, see Chapter Control and monitoring application:
Software switch controller. See the signal ““S4301_STATE” of Table 4.2-7.
2Note: “Double Command Blocking” (DCB) is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCV OR) in Table 4.2-7.
3Note: If the event “device-travelling” is detected, it indicates that another operator is
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detecting signal is denoted
as “Travelling OR” in Table 4.2-7.
4Note: If the issue of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
4.2-7.
5Note: Criteria “unmatched conditions” are decided when “Test-bit status” in a command
is not identical to the “IED test status”.
6Note: The “Event suppression” function can detect chattering on BI circuits. (See section

GRL200 (Soft 033 & 037)


- 678 -
6F2S1914 (0.37)

4.2.6(i)-3)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The Common control (CMNCTRL) function can test and check the ‘Opening’ and
‘Closing’ operations performed by the logic. When the user sets Off for scheme
switch [SCDEN], the operation of the logic is blocked if the logic is running in the
same operation-direction compared with the previous operation-direction (i.e.,
when closing (opening) is performed sequentially). On the other hand, if On is set
for the scheme switch, the logic is not blocked.
9Note: The user will need to program the PLC logic “Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection point “DPSY01IN_TMP_28”. For more information, see
Chapter Control and monitoring application: Control hierarchy . See PLC#3 of
Table 4.2-8.
10Note: To identify the input points of the DPSY02, see Table 4.2-8.

(viii) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicates that the signal is provided for optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” indicates that the user cannot change the state of the signal.

Table 4.2-3 PLC connection points (Input points for Command ‘Closing’)
Signal Number Signal Name Description M/O
5A0101 800527EF40 DEV01_CL_SYNC_INTER DPSY01 PLC Close-control checking with interlock & Sync (PLC#1) O
5A0101 800551EF40 DEV02_CL_SYNC_INTER DPSY02 PLC Close-control checking with interlock & Sync (PLC#1) O
5A0101 800526EF40 DEV01_CL_SYNC DPSY01 PLC Close-control with Sync (PLC#2) O
5A0101 800550EF40 DEV02_CL_SYNC DPSY02 PLC Close-control with Sync (PLC#2) O
5A0101 800525EF40 DEV01_CL_INTERLOCK DPSY01 PLC Close-control checking with interlock(PLC#3) O
5A0101 800549EF40 DEV02_CL_INTERLOCK DPSY02 PLC Close-control checking with interlock(PLC#3) O
5A0101 800524EF40 DEV01_CL_COMMAND DPSY01 PLC Close-control none checking (PLC#4) O
5A0101 800548EF40 DEV02_CL_COMMAND DPSY02 PLC Close-control none checking (PLC#4) O

Table 4.2-4 PLC connection points (Input points for Command ‘Open’)
Signal Number Signal Name Description M/O
5A0101 800523EF40 DEV01_OP_INTERLOCK DPSY01 PLC Open-control checking with interlock(PLC#1) O
5A0101 800547EF40 DEV02_OP_INTERLOCK DPSY02 PLC Open-control checking with interlock(PLC#1) O
5A0101 800522EF40 DEV01_OP_COMMAND DPSY01 PLC Open-control without checking(PLC#2) O
5A0101 800546EF40 DEV02_OP_COMMAND DPSY02 PLC Open-control without checking(PLC#2) O

GRL200 (Soft 033 & 037)


- 679 -
6F2S1914 (0.37)

Table 4.2-5 PLC connection points (Interlock for Command ‘Closing/Open’)


Signal Number Signal Name Description M/O
570001 3102011DA2 DPSY01-Open DPSY01 interlock condition for Open control. N/A
570001 3102021DA2 DPSY02-Open DPSY02 interlock condition for Open control. N/A
570001 3102011DA0 DPSY01-Close DPSY01 interlock condition for Close control. N/A
570001 3102021DA0 DPSY02-Close DPSY02 interlock condition for Close control. N/A

Table 4.2-6 Mapping points for the reception of control commands


Signal Number Signal Name Description M/O
511001 7002016D08 DEV01_CONTROL_REQ DPSY01 control command received.(Mapping Data) M
511001 7002026D08 DEV02_CONTROL_REQ DPSY02 control command received. (Mapping Data) M

Table 4.2-7 Input signals to condition logic


Signal Number Signal Name Description M/O
570001 3103011DA2 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A
522001 000A011001 CBK_STATE Command Blocking status ( Open / Blocked) N/A
522001 000A021001 ICB_STATE Interlock-Bypassing Switch N/A
522001 000A031001 SCB_STATE Synch-Bypassing Switch N/A
5A0001 0008001F41 DCB RCV OR Double Command Blocking(DCB) is in progress. N/A
5A0001 0008001F40 Traveling OR Travelling events are detected. N/A
4A0001 8300001B6F GEN. TRIP General trip N/A
5A0001 3108003F40 SDCEN (This is setting of CMNCTRL) N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A

Table 4.2-8 PLC connection points (Input signals for select condition logic)
Signal Number Signal Name Description M/O
511001 800531EF40 DPSY01IN_TMP_31 DPSY01 additional failure condition(PLC#1) O
511001 800554EF40 DPSY02IN_TMP_31 DPSY02 additional failure condition(PLC#1) O
511001 800532EF40 DPSY01IN_TMP_32 DPSY01 user configurable select condition(PLC#2) O
511001 800555EF40 DPSY02IN_TMP_32 DPSY02 user configurable select condition(PLC#2) O
511001 800516EF40 DPSY01IN_TMP_28 DPSY01 control hierarchy condition(PLC#3) M
511001 800519EF40 DPSY02IN_TMP_28 DPSY02 control hierarchy condition(PLC#3) M

Table 4.2-9 PLC monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
511001 8002011F5A DPSY01_SC_ST_ERR DPSY01 Unmatched condition.
511001 8002021F5A DPSY02_SC_ST_ERR DPSY02 Unmatched condition.
511001 8102011F5F DPSY01_F_QLT_SPP Event suppression detected (DPSY01)
511001 8102021F5F DPSY02_F_QLT_SPP Event suppression detected (DPSY02)
511001 8202011F60 DPSY01_F_BI_ERR BI connection error detected(DPSY01)
511001 8202021F60 DPSY02_F_BI_ERR BI connection error detected(DPSY02)

Table 4.2-10 PLC monitoring points (Closing/Open output signals for BIO)
Signal Number Signal Name Description
511001 8602011DC6 DPSY01_OSL_BO_FLG DPSY01 select (Closing) command for Binary Output.
511001 8602021DC6 DPSY02_OSL_BO_FLG DPSY02 select (Closing) command for Binary Output.
511001 8A02011DC4 DPSY01_FSL_BO_FLG DPSY01 select (Open) command for Binary Output.
511001 8A02021DC4 DPSY02_FSL_BO_FLG DPSY02 select (Open) command for Binary Output.

GRL200 (Soft 033 & 037)


- 680 -
6F2S1914 (0.37)

(ix) Setting names


Table 4.2-11 Setting of SBO control in DPSY
Setting Name Description Default Setting item or value
DPSY01-CTREN Activate control function Close Open / Close
DPSY01-LGSLFFCT Logic selector for select condition Fixedlogic Fixedlogic / PLC
DPSY01-CTRAHMI Activate local panel control SBO DIR / SBO
DPSY02-CTREN Activate control function Close Open / Close
DPSY02-LGSLFFCT Logic selector for select condition Fixedlogic Fixedlogic / PLC
DPSY02-CTRAHMI Activate local panel control SBO DIR / SBO

GRL200 (Soft 033 & 037)


- 681 -
6F2S1914 (0.37)

4.2.2 Cancel logic for SBO mode


In the SBO control mode, the reception of a cancel command is possible; when the cancel
conditions are satisfied, accordingly, the IED can discard the select command; finally, the
operation returns to the initial stage (i.e., “Wait for a command”.)

(i) Receiving “Cancel” from the remote-end


Figure 4.2-14 depicts the cancel command procedure for a cancel command initiated from the
remote-end.

Wait for a command

Select logics Wait for a next command

Select command Closing from the remote-end Cancel from the remote-end
Success

Select command Open from the remote-end Cancel


Signal reception in
Cancel logic Do nothing
IEC61850 decision Failed
Select command Closing from the local-end

Select command Open from the local-end


Cancel from the local-end
Select command Closing by the PLC function

Select command Open by the PLC function


Operate logic
Operate command

Operate logic

Figure 4.2-14 Outline of ‘cancel’ command from the remote-end

Input point required mapping


Figure 4.2-15 depicts the cancel logic when a “Cancel command (Remote-Cancel)” signal is
applied to the DPSY01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the signal “Select command Closing (Remote-Closing-Control)”.
510001 7001016D08

Input Cancel logic in DPSY01 Output

DPSY01 function (Function ID: 511001)


Command “Remote-cancel”
Cancel command
511001_7002016D08 DEV01_CONTROL_REQ
& To “Wait for a command”
“DPSY01_ CC_SS” (511001
8602011E95)
Cancel condition† &
Successes to cancel

“Do nothing”

“DPSY01_CC_FS”
(511001 8702011E96)

Operation Failed

Figure 4.2-15 ‘Cancel’ from the remote-end in DPSY01


†Note: The “cancel condition” logic is shown in Figure 4.2-18.

GRL200 (Soft 033 & 037)


- 682 -
6F2S1914 (0.37)

Output signal to BO
The DPSY01 function can issue a “Success to cancel” signal at the monitoring point
“DPSY01_CC_SS”, when the DPSY01 function has determined that the “Remote-cancel” signal
is true. Another “Operation failed” signal is issued at monitoring point DPSY01_CC_FS” “if
the DPSY01 function is able to determine that the “Remote-cancel” signal is not true.

(ii) Receiving “Cancel” from the local-end


Figure 4.2-16 outlines the reception of the cancel command from the local-end.

Wait for a command

Select logics Wait for a next command

Cancel from the remote end


Selecting Closing from the remote-end

Selecting Open from the remote-end


Cancel from the local-end
Success
Selecting Closing from the local-end
Press cancel Cancel
Selecting Open from the local-end Cancel logic Do nothing
command decision Failed

Selecting Closing by the PLC function

Selecting Open by the PLC function


Operate logic
Operate command

Operate logic

Figure 4.2-16 Outline of ‘cancel’ command from the local-end

Input signal generated at the local-end


Figure 4.2-17 depicts the cancel logic when a “Cancel command (Local-cancel)” signal is applied
to the DPSY01 function. The signal is generated when the “Cancel” key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
“Local-cancel” signal, the logic is able to output a result signal, provided that the “cancel
condition” checking is satisfied.

Input Cancel logic in DPSY01 Output

DPSY01 function (Function ID: 511001)

Cancel command
Command “Local-cancel”
& To “Wait for a command”
“DPSY01_ CC_SS”
(511001 8602011E95)
Cancel condition &
Successes to cancel

“Do nothing”
“DPSY01_CC_FS”
(511001 8702011E96)

Operation Failed

Figure 4.2-17 ‘Cancel’ from the front panel

GRL200 (Soft 033 & 037)


- 683 -
6F2S1914 (0.37)

Output signal to BO
The DPSY01 function, illustrated in Figure 4.2-17, is able to issue a “Select to cancel” signal
at the monitoring point “DPSY01_CC_SS”, when the DPSY01 function determines that the
“Local-Cancel” signal is true.

(iii) Cancel condition logic


Figure 4.2-18 shows the cancel condition logic. As the criteria “Unmatched condition detected”
is connected normally for the cancel logic, set Fixlogic for the scheme switch [DPSY01-
LGCNFFCT].

DPSY01 function (Function ID: 511001)

Unmatched conditions detected *1 To cancel logic in


& 1≥ DPSY01

[DPSY01-LGSLFFCT]
User configurable condition (PLC connection point)
Fixedlogic
511001 800201EE69 DPSY01IN_TMP_46 &
PLC#1

Figure 4.2-18 Logic “Cancel condition” in DPSY01


1Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”.
2Note: With the exception of the above ‘cancel’ logic, there is an operate-condition logic
within the DPSY01 function; the operate-condition logic will always checks
conditions. That is, the user is only required to set either the “operate-condition”
or the “cancel-condition” logic.

If the original logic does not meet with the requirements of the user, it can be replaced
using the connection point “User configurable condition”:
1. Connect the user-customized logic with the “DPSY01IN_TMP_46”, which is listed
in Table 4.2-12.
2. Set scheme switch [DPSY01-LGCNFFCT] to PLC.

(iv) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” in
each table:
“O” indicates that the signal is provided for optional usage.
“M” indicates that the user should map/set/configure using the signal;
otherwise, the user may experience an operational failure for the default
settings.
“N/A” indicates that the user cannot change the state of the signal.

GRL200 (Soft 033 & 037)


- 684 -
6F2S1914 (0.37)

Table 4.2-12 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number Signal Name Description M/O
511001 800201EE69 DPSY01IN_TMP_46 DPSY01 user configurable cancel condition O
511001 800202EE69 DPSY02IN_TMP_46 DPSY02 user configurable cancel condition O

Table 4.2-13 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
511001 8602011E95 DPSY01_CC_SS DPSY01 cancel succeed
511001 8602021E95 DPSY02_CC_SS DPSY02 cancel succeed
511001 8702011E96 DPSY01_CC_FS DPSY01 cancel failed
511001 8702021E96 DPSY02_CC_FS DPSY02 cancel failed

(v) Setting name


Note: The “xx” within “DPSYxx” represents the DPSY function number. (e.g., if DPSY01
is considered, the “xx” is equal to “01”. The numbers used for “xx” can be
represented by either “01” or “02”.)
Table 4.2-14 Setting for ‘Cancel’ in DPSYxx
Setting Name Description Default Setting item or value
DPSYxx-LGCNFFCT Logic selector for cancel condition (DPSY01-02) Fixedlogic Fixedlogic / PLC

GRL200 (Soft 033 & 037)


- 685 -
6F2S1914 (0.37)

4.2.3 Operate logic for SBO/DIR modes


Once the operation of the select logic is complete, the operate logic start to control the device.

(i) Receiving “operate command Closing” from the remote-end


Figure 4.2-19 depicts the reception of the operate command ‘Closing’ from the remote-end.
Wait for a command

Select stage Wait for a next command

Operate command Closing from the remote-end


Success
Select command Closing from the remote-end Operation
Signal reception in Operate logic Signal output
decision
IEC61850

Failed Do nothing

Select command Open from the remote-end Operate command Open from the remote-end

Select command Closing from the local-end Operate command Closing from the local-end

Select command Open from the local-end Operate command Open from the local-end

Select command Closing by the PLC function Operate command Closing by the PLC function

Select command Open by the PLC function Operate command Open by the PLC function

Figure 4.2-19 Outline of operate command ‘Closing’

Mapping required for Input point


Figure 4.2-20 illustrates the operate logic when an “Operate command (Remote-Closing-
Control)” signal is applied to the DPSY01 function. The input-point “DEV01_CONTROL_REQ”
is used for the reception of the “Operate command Closing (Remote-Closing-Control)”.

GRL200 (Soft 033 & 037)


- 686 -
6F2S1914 (0.37)

Input Operate logic in DPSY01 Output

“DPSY01_OEC_OK_CSF”
DPSY01 function (Function ID: 511001) (511001 8002011E7F)

“DPSY01_OEC_OK_CS”
(511001 8102011E82)
Command “Remote-Closing-Control”
[DPSY01-CPW]
511001_7002016D08 DEV01_CONTROL_REQ Operate Command with ILK†
condition & synchro-checking & 1≥ & 1≥
& 0.1 – 50.0 s 1≥

Operate Command with


synchro-checking &
ILK condition (“Closing”) passed S
&
DPSY01-Close R
From SYNCHK

SYNC01-SYN_CLC
(560001 850B011F59)
Operate Command with ILK†
condition &

Operate Command without


User configurable condition condition
(PLC#1 connection point)

511001 810201EE57 DPSY01IN_TMP_35


[DPSY01-LGCTRCON] &
Fixedlogic To BO connection
“DPSY01_OEX_BO” §§
Operate condition ‡
(511001 8202011DD3)

[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ§ function” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”

“DPSY01_EX_CMP”
Detection of state-change in (511001 8002011E93)
a device S &
User configurable condition “DPSY01_EX_CMP” R Operate Completed
1≥
(PLC#2 connection point)
(511001 8002011E93)
511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL” ‡‡
[DPSY01-RST] PLC
(511001 8602011E91)
“DPSY01_OEC_OK_CSF”
0 t
(511001 8002011E7F)
&
1.0s- 100.0s Operate Failed

Figure 4.2-20 Operate ‘Closing’ from the remote-end in DPSY01††


†Note:The ILK function can provide the operation criteria for “Closing”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative “operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #1 “User-configurable condition”. That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use “DPSY01IN_TMP_35”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when Fixlogic is set for scheme switch
[DPSY01-LGCFEXOT]. The “Operate completed” signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.2-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point #2 “User-configurable condition”. That is, set the scheme switch [DPSY01-
LGCFEXOT] to PLC and use “DPSY01IN_TMP_44”.

GRL200 (Soft 033 & 037)


- 687 -
6F2S1914 (0.37)

*Note:The user can set the type of the output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
††Note: To identify the input and output signal-points of the DPSY02 logic, see Table
4.2-15 for PLC#1, Table 4.2-16 for PLC#2, Table 4.2-20, and Table 4.2-21 for
output signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by the [DPSY01-RST] has been reached.

Output signal to BO
The DPSY01 function, in Figure 4.2-20, can issue an “Operate” signal at the output point
“DPSY01_OEX_BO”, when the DPSY01 function determines that the received signal “Remote-
Closing-Control” is true.

(ii) Receiving “operate command Open” from the remote-end


Figure 4.2-21 depicts the reception of the operate command ‘Open’ from the remote-end.
Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end Operate command Closing from the remote-end

Operate command Open from the remote-end


Success
Operation
Signal reception in Operate logic Signal output
Select command Open from the remote-end decision
IEC61850

Failed Do nothing

Select command Closing from the local-end Operate command Closing l from the local-end

Select command Open from the local-end Operate command Open from the local-end

Select command Closing by the PLC function Operate command Closing by the PLC function

Select command Open by the PLC function Operate command Open by the PLC function

Figure 4.2-21 Outline of operate command ‘Open’

Mapping required for Input point from communication


Figure 4.2-22 illustrates the operate logic when an “Operate command (Remote-Open-Control)”
signal is applied to the DPSY01 logic. The input-point “DEV01_CONTROL_REQ” is used for
the reception of the “Operate command Open (Remote-Open-Control)”.

GRL200 (Soft 033 & 037)


- 688 -
6F2S1914 (0.37)

Input Operate logic in DPSY01 Output

DPSY01 function (Function ID: 511001)

“DPSY01_FEC_OK_CSF” “DPYS01_FEC_OK_CS”
Command “Remote-On-Control” (511001 8002011E7E) (511001 8002011E7E)
[DPSY01-CPW]
511001_7002016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ & 1≥
& 0.1 – 50.0 s 1≥

Operation Cmd.
without ILK† condition

ILK condition (“Open”) passed S


&
DPSY01-Open R
User configurable condition
(PLC#3 connection point)

511001 800201EE56 DPSY01IN_TMP_34


[DPSY01-LGCTRCON] &
Fixedlogic To BO connection
“DPSY01_FEX_BO” §§
Operate condition‡
(511001 8102011DD0)

[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”

“DPSY01_EX_CMP”
(511001 8002011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL”


[DPSY01-RST]
(511001 8602011E91)
“DPSY01_FEC_OK_CSF” 0 t
(511001 8002011E7E)
&
1.0s- 100.0s Operate Failed

Figure 4.2-22 ‘Open’ operate from the remote-end in DPSY01††


†Note:The ILK function can provide the operation criteria for “Open”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative “operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #3 “User-configurable condition”. That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use “DPSY01IN_TMP_34”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when Fixlogic is set for scheme switch
[DPSY01-LGCFEXOT]. The “Operate completed” signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.2-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point #2 “User-configurable condition”. That is, set the scheme switch [DPSY01-
LGCFEXOT] to PLC and use “DPSY01IN_TMP_44”.
*Note:The user can set the type of output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
††Note: To identify the input and output signals of the DPSY02 logic, see Table 4.2-16 for

GRL200 (Soft 033 & 037)


- 689 -
6F2S1914 (0.37)

PLC#2, Table 4.2-17 for PLC#3, Table 4.2-19, and Table 4.2-21 for the outputs.

Output signal to BO
The DPSY01 function, in Figure 4.2-22, can issue an “Operate” signal at the output-point
“DPSY01_FEX_BO”, when the DPSY01 function determines that the input signal “Remote-
Open-Control” is true.

(iii) Receiving “operate command Closing” from the local-end


Figure 4.2-23 depicts the reception of the operate command ‘Closing’ from the local-end.
Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end Operate command Closing from the remote-end

Select command Open from the remote-end Operate command Open from the remote-end

Select command Closing from the local-end Operate command Closing l from the local-end Success
Operation
Signal reception from Operate logic Signal output
decision
the front panel

Failed Do nothing

Select command Open from the local-end Operate command Open from the local-end

Select command Closing by the PLC function Operate command Closing by the PLC function

Select command Open by the PLC function Operate command Open by the PLC function

Figure 4.2-23 Outline of operate command Closing

Input signal generated at the local-end


Figure 4.2-24 illustrates the operate logic when an “Operate command Closing (Local-Closing-
Control)” signal is applied to the DPSY01 function. The signal is generated when “Execution
of Closing” is keyed on the IED front panel.

GRL200 (Soft 033 & 037)


- 690 -
6F2S1914 (0.37)

Input Operate logic in DPSY01 Output

DPSY01 function (Function ID: 511001)

“DPSY01_OEC_OK_CSF” “DPSY01_OEC_OK_CS”
(511001 8002011E7F) (511001 8102011E82)
Command “Local-Closing-Control”
[DPSY01-CPW]
511001_7002016D08 DEV01_CONTROL_REQ Operate Command with ILK
condition & synchro-checking & 1≥ & 1≥
& 0.1 – 50.0 s 1≥
ILK condition (“Closing”) passed
DPSY01-Close

ILK bypassing 1≥ S
&
ICB_STATE
R
From SYNCHK

SYNC01-SYN_CLC
(560001 850B011F59)
1≥
SYNC‡‡ bypassing
SCB_STATE

User configurable condition


(PLC#1 connection point)

511001 810201EE57 DPSY01IN_TMP_35


[DPSY01-LGCTRCON] &
Fixedlogic To BO connection
††
“DPSY01_OEX_BO”
Operate condition‡
(511001 8202011DD3)

[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”

“DPSY01_EX_CMP”
Detection of state-change in (511001 8002011E93)
a device S &
User configurable condition “DPSY01_EX_CMP” R Operation Completed
1≥
(PLC#2 connection point)
(511001 8002011E93)
511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL”
[DPSY01-RST] PLC
(511001 8602011E91)
“DPSY01_OEC_OK_CSF”
0 t
(511001 8002011E7F)
&
1.0s- 100.0s Operation Failed

Figure 4.2-24 Operate closing on the front panel in DPSY01


†Note:The ILK function can provide the operation criteria for “Closing”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative “operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #1 “User-configurable condition”. That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use “DPSY01IN_TMP_35”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when Fixlogic is set for scheme switch
[DPSY01-LGCFEXOT]. The “Operate completed” signal can also be issued from
logic programmed by the user in place of the logic shown in Figure 4.2-20., The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point #2 “User-configurable condition”. That is, set the scheme switch [DPSY01-
LGCFEXOT] to PLC and use “DPSY01IN_TMP_44”.

GRL200 (Soft 033 & 037)


- 691 -
6F2S1914 (0.37)

*Note:The user can set the type of output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
††Note: To identify the input and output signal-points of the DPSY02 logic, see Table
4.2-15 for PLC#1, Table 4.2-16 for PLC#2, Table 4.2-20, and Table 4.2-21 for
output signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPSY01-RST].

Output signal to BO
The DPSY01 function, in Figure 4.2-24, can issue an “Operate” signal at the output point
“DPSY01_OEX_BO”, if the DPSY01 function determines that the signal “Local-Closing-
Control” is true.

(iv) Receiving “operate command Open” from front panel


Figure 4.2-25 depicts the reception of the operate command for ‘Open’ from the front panel.
These input and output signals and the procedure are highlighted in the figure below.
Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end Operate command Closing from the remote-end

Select command Open from the remote-end Operate command Open from the remote-end

Select command Closing from the local-end Operate command Closing l from the local-end

Operate command Open from the local-end


Success
Operation
Signal reception from Operate logic Signal output
decision
Select command Open from the local-end the front panel

Failed Do nothing

Select command Closing by the PLC function Operate command Closing by the PLC function

Select command Open by the PLC function Operate command Open by the PLC function

Figure 4.2-25 Outline of operate command Open

Input signal generated at the local-end


Figure 4.2-26 illustrates the operate logic when an “Operate command Open (Local-Open-
Control)” signal is applied to the DPSY01 function. The signal is generated when “Execution
for Open” is keyed on the IED front panel.

GRL200 (Soft 033 & 037)


- 692 -
6F2S1914 (0.37)
To BO connection

Input Operate logic in DPSY01 Output

“DPSY01_FEC_OK_CSF”
DPSY01 function (Function ID: 511001) (511001 8002011E7E)

“DPSY01_FEC_OK_CS”
(511001 8002011E7E)
Operate Cmd.
Command “Local-Open-Control” [DPSY01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operation Cmd.
without ILK† condition
ILK condition (“Open”) passed
DPSY01--Open
S
&
ILK bypassing 1≥
R
ICB_STATE

User configurable condition (PLC#3 connection point)


511001 800201EE56 DPSY01IN_TMP_34 &
[DPSY01-LGCTRCON]
Fixedlogic To BO connection
PLC#3 ††
“DPSY01_FEX_BO”
Operate condition‡
(511001 8102011DD0)

[DPSY01-LGCFEXOT]
& Assign to BOs
ASEQ§ function” is in progress Fixedlogic
ASEQ_MULTI_SEL
[DPOS01-PLSM]
Var
Fix To “Wait for a command”

“DPSY01_EX_CMP”
(511001 8002011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)

511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL”


PLC#2 [DPSY01-RST]
(511001 8602011E91)
“DPSY01_FEC_OK_CSF”
(512001 8003011E7E) 0 t
&
1.0s- 100.0s Operation Failed

Figure 4.2-26 Operate Open logic at local in DPSY01


†Note:The ILK function can provide the operation criteria for “Open”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative “operate-condition” is required it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #3 “User-configurable condition”. That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use “DPSY01IN_TMP_34”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when Fixlogic is set for the scheme
switch [DPSY01-LGCFEXOT]. The “Operate completed” signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.2-20. The user-programmed logic is connected internally to the signal “Operate
completed”, hence this signal is now generated by the user-programmed logic at
connection point #2 “User configurable condition”. That is, set the scheme switch
[DPSY01-LGCFEXOT] to PLC and use “DPSY01IN_TMP_44”.
*Note:The user can set the type of output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
††Note: To identify the input and output signals of the DPSY02 logic, see Table 4.2-16 for

GRL200 (Soft 033 & 037)


- 693 -
6F2S1914 (0.37)

PLC#2, Table 4.2-17 for PLC#3, Table 4.2-19, and Table 4.2-21 for the outputs.

Output signal to BO
The DPSY01 function, in Figure 4.2-31, can issue an “Operate” signal at the output point
“DPSY01_FEX_BO”, when the DPSY01 function determines that the signal “Local-Open-
Control” is true.

(v) Receiving “operate command Closing” using the PLC logic


Figure 4.2-27 outlines the reception of the operate command closing with the PLC function.

Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end Operate command Closing from the remote-end

Select command Open from the remote-end Operate command Open from the remote-end

Select command Closing from the local-end Operate command Closing l from the local-end

Select command Open from the local-end Operate command Open from the local-end

Select command Closing by the PLC function Operate command Closing by the PLC function Success
Operation
PLC logic programmed Operate logic Signal output
decision
by the user l

Failed Do nothing

Select command Open by the PLC function Operate command Open by the PLC function

Figure 4.2-27 Outline of operate command closing

Input signal from the PLC function


Figure 4.2-28 describes the operate logic when an “Operate command Closing (PLC-Closing-
Control)” signal is generated by the PLC function. There are four input points for reception of
the signal “operate command closing”. The input point is selected in accordance with one of the
following four conditions: for the first condition, the issue of the operate command to the device
is decided in coordination with checks for both the ILK and the SYNCHK functions, the signal
is applied at connection point (PLC#1: i.e., “DEV01_CL_SYNC_INTER”) (Table 4.2-3). For the
second condition, the issue of the operate command for the device is determined in coordination
with a check using the SYCHK function only, the signal is applied at connection point (“PLC#2:
i.e., “DEV01_CL_SYNC”) (Table 4.2-3). If the third condition is used, the issue of the operate
command for the device is determined in coordination with a check using the ILK function only,
apply the signal at connection point (“PLC#3: i.e., DEV01_CL_INTERLOCK”) (Table 4.2-3).
Regarding the fourth condition, the issue of the operate command to the device is made with
no check, the signal is applied at connection point (“PLC#4: i.e., DEV01_CL_COMMAND”)
(Table 4.2-3). Note that the user should set PLC for scheme switch [DPSY-LGCTRCON].

GRL200 (Soft 033 & 037)


- 694 -
6F2S1914 (0.37)

Input Operate logic in DPSY01 Output

“DPSY01_OEC_OK_CSF”
DPSY01 function (Function ID: 511001) (511001 8002011E7F)

“DPSY01_OEC_OK_CS”
Closing control command with ILK† and synchro checks (511001 8102011E82)
(PLC#1 connection point) [DPSY01-CPW]
511001 800201EE35 DEV01_CL_SYNC_INTER Operate Command with ILK†
condition & synchro-checking & 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Closing control command with synchro check
(PLC#2 connection point)
Operate Command with
511001 800201EE34 DEV01_CL_SYNC
synchro-checking &
ILK condition (“Closing”) passed S
&
DPSY01-Close R
From SYNCHK
Closing control command SYNC01-SYN_CLC
with interlock check (560001 850B011F59)
(PLC#3 connection point)
Operate Command with ILK†
511001 800201EE33 DEV01_CL_INTERLOCK &
condition
Closing control command with no check
(PLC#4 connection point) Operate Command without
511001 800201EE32 DEV01_CL_COMMAND condition
User configurable condition
(PLC#1 connection point)
511001 810201EE57 DPSY01IN_TMP_35
[DPSY01-LGCTRCON] &
Fixedlogic To BO connection
“DPSY01_OEX_BO” §§
Operate condition‡
(511001 8202011DD3)

[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”

“DPSY01_EX_CMP”
Detection of state-change in (511001 8002011E93)
a device S &
User configurable condition “DPSY01_EX_CMP” R Operate Completed
1≥
(PLC#2 connection point)
(511001 8002011E93)
511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL” ‡‡
[DPSY01-RST] PLC
(511001 8602011E91)
“DPSY01_OEC_OK_CSF”
0 t
(511001 8002011E7F)
&
1.0s- 100.0s Operate Failed

Figure 4.2-28 Closing operation logic with PLC in DPSY01††


†Note:The ILK function can provide the criteria for operation for “Closing” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operated-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 1.10-28 using
connection point #1 “User-configurable condition”. That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use “DPSY01IN_TMP_35”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when Fixlogic is set for scheme switch
[DPSY01-LGCFEXOT]. If the signal to be issued from the logic programmed by the
user instead of the logic shown in Figure 4.2-20, connect the signal “Operate
completed” generated in the user-programmed logic to connection point #2 “User
configurable condition”. That is, set the scheme switch [DPSY01-LGCFEXOT] to
PLC and use “DPSY01IN_TMP_44”.
*Note:The user can set the type of output signal. When Var is set for scheme switch

GRL200 (Soft 033 & 037)


- 695 -
6F2S1914 (0.37)

[DPSY01-PLSM], the output period of the signal is defined by the setting applied
to [DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
††Note: To identify the input and output signal-points in the DPSY02 logic, see Table
4.2-3 and Table 4.2-4 for PLC#1 to PLC#4, Table 4.2-15 and Table 4.2-16 for
PLC#1/#2 for user configurable conditions, Table 4.2-20, and Table 4.2-21 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when a state-change remains undetected
following expiration of the setting applied to timer [DPSY01-RST].

Output signal to BO
The DPSY01 function, in Figure 4.2-28, can issue an “Operate” signal at output point
“DPSY01_OEX_BO”, when the DPSY01 function determines that the “PLC-Closing-Control”
signal is true.

(vi) Receiving “operate command Open” using PLC logic


Figure 4.2-29 depicts the reception of the operate command for Open using the PLC function.
These input and output signals and the process are highlighted in the figure below.

Wait for a command

Select stage Wait for a next command

Select command Closing from the remote-end Operate command Closing from the remote-end

Select command Open from the remote-end Operate command Open from the remote-end

Select command Closing from the local-end Operate command Closing from the local-end

Select command Open from the local-end Operate command Open from the local-end

Select command Closing with the PLC Operate command Closing with the PLC function
function
Operate command Open with the PLC function Success
Operation
PLC logic programmed Operate logic Signal output
decision
Select command Open with the PLC function by the user

Failed Do nothing

Figure 4.2-29 Outline of operate command for Open

Input signal from the PLC function


Figure 4.2-30 depicts the operate logic when an “Operate command Open (PLC-Open-Control)”
signal is generated by the PLC function. There are two points for reception of this command
signal, unlike the signal (“Operate command Closing (PLC-Closing-Control)”. That is, if an
interlock check is required, apply the signal at connection point (“PLC#4: i.e.,
DEV01_OP_INTERLOCK”). If, on the other hand an interlock check is not required, apply the
signal at connection point (“PLC#5: i.e., DEV01_OP_COMMAND”). PLC#1 and PLC#2 shown
in Table 4.2-4 should be treated as PLC#3 and PLC#4 here.

GRL200 (Soft 033 & 037)


- 696 -
6F2S1914 (0.37)

Input Operate logic in DPSY01 Output

“DPSY01_FEC_OK_CSF”
(511001 8002011E7E)
DPSY01 function (Function ID: 511001)

“DPSY01_FEC_OK_CS”
Command “PLC-Open-Control” with ILK†
(511001 8002011E7E)
(PLC#4 connection point) [DPSY01-CPW]
511001 800201EE31 DEV01_OP_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-Open-Control” without ILK† 0.1 – 50.0 s
(PLC#5 connection point)
511001 800201EE30 DEV01_OP_COMMAND Operation Cmd.
without ILK† condition
S
ILK† condition (“Open”) passed &
DPSY01-Open R
User configurable condition
(PLC#3 connection point)

511001 800201EE56 DPSY01IN_TMP_34


[DPSY01-LGCTRCON] &
Fixedlogic To BO connection
PLC#1
“DPSY01_FEX_BO” §§
Operate condition‡
(511001 8102011DD0)

[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”

“DPSY01_EX_CMP”
(511001 8002011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL” ††


PLC#2 [DPSY01-RST]
(511001 8602011E91)
“DPSY01_FEC_OK_CSF”
0 t
(511001 8002011E7E)
&
1.0s- 100.0s Operate Failed

Figure 4.2-30 Open operation logic by PLC in DPSY01††


†Note:The ILK function can provide the criteria for operation for control of the “Open”
operation.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operated-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 1.10-30 using
connection point #3 “User-configurable condition”. That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use “DPSY01IN_TMP_34”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when Fixlogic is set for the scheme
switch [DPSY01-LGCFEXOT]. If the signal to be issued from the programmed
logic by the user in place of Figure 4.2-20 logic, connect the signal “Operate
completed” generated in the programmed logic to the connection point #2 “User
configurable condition”. That is, the set the scheme switch [DPSY01-LGCFEXOT]
to PLC and use “DPSY01IN_TMP_44”.
*Note:The user can set the type of the output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting applied
to [DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.

GRL200 (Soft 033 & 037)


- 697 -
6F2S1914 (0.37)

††Note: To identify the input and output signal-points in the DPSY02 logic, see Table
4.2-16 for PLC#2, Table 4.2-17 for PLC#3, Table 4.2-19, and Table 4.2-21 for the
outputs.

Output signal to BO
The DPSY01 function, in Figure 4.2-30, can issue an “Operate” signal at output-point
“DPSY01_FEX_BO”, when the DPSY01 function determines that the “PLC-Open-Control”
signal is true.

(vii) Operate condition


In a manner similar to which the conditions have been examined for the select command, the
conditions for an operate command should be understood. Figure 4.2-31 illustrates the logic to
examine an operate condition; the operate condition is determined by signal “DPSY01_STATE”.
If the functionality of the original logic does not meet with user-requirements, the following
alternatives are available:
1. The user can replace the original logic with alternative logic.
2. The user can add another signal to the original logic.

Replacing the original logic


If the user wishes to replace the operate condition logic completely, it can be achieved using
PLC connection point “User configurable condition”:
1. Connect the user-customized logic using DPSY01IN_TMP_41, listed as PLC#2 in
Table 4.2-18.
2. Set scheme switch [DPSY01-LGEXFFCT] to PLC.

Adding another operate condition signal


If the addition of another operate condition is required, the user can add the signal to the
operate condition logic using PLC connection point “Additional condition”:
1. Add a user-preferred signal using “DPSY01IN_TMP_40”, listed as PLC#1 in Table
4.2-18.
2. Set scheme switch [DPSY01-LGEXFFCT] to Fixedlogic. (Table 4.2-22)

Note: The user must program PLC logic “Control hierarchy condition”. The Control
hierarchy condition to be provided with the user-programmed PLC logic may be
43R/L; it may be connected using PLC connection point “DPSY01IN_TMP_28” in
Figure 4.2-31.
Note: The output of the operate condition logic is provided separately for Closing-
execution and for Open-execution. To see the outputs, refer to Table 4.2-19.

GRL200 (Soft 033 & 037)


- 698 -
6F2S1914 (0.37)

DPSY01 function (Function ID: 511001)


Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Operate condition
Traveling OR Unmatched condition detected *5
Function “Automatic sequence control” is in progress
ASEQ_MULTI_SEL Event suppression detected *6
= DPSY01_F_QLT_SPP
Tripping *4 (“General trip”)
(511001 8102011F5F)
GEN. TRIP
BI board connection error detected*7
= DPSY01_F_BI_ERR
(511001 8202011F60)

Command “Closing-control” received &


Command “Open control” received &
received
DPSY01_3PH_STATE
(511001 3102011001)
[SCDEN]*8 Same Directional
Controlling Event
OFF
Additional condition (PLC#1 connection point)
511001 800201EE65 DPSY01IN_TMP_40
[DPSY01- LGEXFFCT]
User configurable operate condition (PLC#2 connection point)
Fixedlogic
511001 810201EE66 DPSY01IN_TMP_41 &
Users must setup this condition correctly
Control hierarchy (e.g. 43RL) (PLC connection point)*9
511001 820201ED50 DPSY01IN_TMP_28
&
IED serious error detected
SERI_ERR
[DPSY01-CTREN]

On

Figure 4.2-31 Operate condition logic for ‘Closing/Open’ in DPSY01


1Note: “Command Blocking” disables any operation except for itself; “Command
Blocking” is implemented as “CBK” in a software switch controller (SOTFSW).
The IEC 61850 standard defines “Command Blocking” as “CmdBlk”. For more
information on “CBK”, see Chapter Control and monitoring application: Software
switch controller. See the signal ““S4301_STATE” in Table 4.2-7.
2Note: “Double Command Blocking” (DCB) is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCV OR) in Table 4.2-7.
3Note: Detection of event “device-travelling”, signifies that other operators are changing
the status of one or more devices. Thus, device operation by the IED should be
inhibited whilst ever the event is detected. The detection signal is denoted as
“Travelling OR” in Table 4.2-7.
4Note: If an IED is in the process of issuing a trip command, all control operation is
blocked until the trip operation has been completed. If the IED has a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
4.2-7.
5Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to the “IED test status”.
6Note: The “Event suppression” function can detect chattering in BI circuits. (See section

GRL200 (Soft 033 & 037)


- 699 -
6F2S1914 (0.37)

4.2.6(i)-3)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The “Common control” (CMNCTRL) function can test and check the operation-
direction of logic. When the user sets Off for scheme switch [SCDEN], operation of
the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
9Note: The user must program the PLC logic for “Control hierarchy condition”. The user
must connect the “Control hierarchy condition” to the select condition logic using
the connection point “DPSY01IN_TMP_28”. For more information, see Chapter
Control and monitoring application: Control hierarchy . See PLC#3 of Table 4.2-8.
Note that the logic outputs are generated separately for both the Closing-
execution and the Open-execution.

(viii) Signal name and number


Note: The user should note the meaning of the following abbreviations shown in column
“M/O” of each table:
“O” signifies that the signal is provided for optional use.
“M” signifies that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” signifies that the user cannot change the state of the signal.

Table 4.2-15 PLC connection points (Input point for PLC#1 user a configurable condition)
Signal Number Signal Name Description M/O
511001 810201EE57 DPSY01IN_TMP_35 DPSY01 user configurable condition(PLC#1) O
511001 810202EE57 DPSY02IN_TMP_35 DPSY02 user configurable condition(PLC#1) O

Table 4.2-16 PLC connection points (Input point for PLC#2 operate command Closing)
Signal Number Signal Name Description M/O
511001 820201EE5E DPSY01IN_TMP_44 DPSY01 user configurable condition(PLC#2) O
511001 820202EE5E DPSY02IN_TMP_44 DPSY02 user configurable condition(PLC#2) O

Table 4.2-17 PLC connection points (Input point for PLC#3 operate command Closing)
Signal Number Signal Name Description M/O
511001 800201EE56 DPSY01IN_TMP_34 DPSY01 user configurable condition(PLC#3) O
511001 800202EE56 DPSY02IN_TMP_34 DPSY02 user configurable condition(PLC#3) O

Table 4.2-18 PLC connection points (Input point for operate condition logic)
Signal Number Signal Name Description M/O
511001 800201EE65 DPSY01IN_TMP_40 DPSY01 user additional condition(PLC#1) O

GRL200 (Soft 033 & 037)


- 700 -
6F2S1914 (0.37)

Signal Number Signal Name Description M/O


511001 800202EE65 DPSY02IN_TMP_40 DPSY02 user additional condition(PLC#1) O
511001 810201EE66 DPSY01IN_TMP_41 DPSY01 user configurable operate condition(PLC#2) O
511001 810202EE66 DPSY02IN_TMP_41 DPSY02 user configurable operate condition(PLC#2) O
511001 820201ED50 DPSY01IN_TMP_28 DPSY01 control hierarchy condition(PLC#3) M
511001 820202ED50 DPSY02IN_TMP_28 DPSY02 control hierarchy condition(PLC#3) M

Table 4.2-19 PLC monitoring points (Output signal for BIO)


Signal Number Signal Name Description
511001 8202011DD3 DPSY01_OEX_BO DPSY01 operate (CLOSE) command for Binary Output.
511001 8202021DD3 DPSY02_OEX_BO DPSY02 operate (CLOSE) command for Binary Output.
511001 8102011DD0 DPSY01_FEX_BO DPSY01 operate (OPEN) command for Binary Output.
511001 8102021DD0 DPSY02_FEX_BO DPSY02 operate (OPEN) command for Binary Output.

Table 4.2-20 PLC monitoring points (Signals within operate logic)


Signal Number Signal Name Description
511001 8002011E7F DPSY01_OEC_OK_CSF DPSY01 Close direction execute command
511001 8002021E7F DPSY02_OEC_OK_CSF DPSY02 Close direction execute command
511001 8102011E82 DPSY01_OEC_OK_CS DPSY01 Close direction execute command
511001 8102021E82 DPSY02_OEC_OK_CS DPSY02 Close direction execute command
511001 8002011E7E DPSY01_FEC_OK_CSF DPSY01 Open direction execute command
511001 8002021E7E DPSY02_FEC_OK_CSF DPSY02 Open direction execute command
511001 8002011E7E DPSY01_FEC_OK_CS DPSY01 Open direction execute command
511001 8002021E7E DPSY02_FEC_OK_CS DPSY02 Open direction execute command

Table 4.2-21 PLC monitoring points (Output signal for response)


Signal Number Signal Name Description
511001 8002011E93 DPSY01_EX_CMP DPSY01 completed control
511001 8002021E93 DPSY02_EX_CMP DPSY02 completed control
511001 8602011E91 DPSY01_EX_FFL DPSY01 failed control
511001 8602021E91 DPSY02_EX_FFL DPSY02 failed control

(ix) Setting names


Note: The “xx” of “DPSYxx” represents the DPSY function number. (e.g., if the DPSY01
is considered, the “xx” is equal to “01”. The suffix “xx” can be represented by either
a “01” or “02”.)
Table 4.2-22 Setting of Operate in DPSYxx
Setting Name Description Default Setting item or value
DPSYxx-PLSM Method of command output (DPSY01-02) Fix Fix/Var
DPSYxx-CPW Duration of command output (DPSY01-02) 1.0[sec] 0.1~50.0[sec]
DPSYxx-RST Detection time for terminating control (DPSY01-02) 30.0[sec] 0.1~100.0[sec]
DPSYxx-LGCTRCON Logic selector for operate condition (DPSY01 -02) Fixedlogic Fixedlogic/PLC
DPSYxx-LGCFEXOT Logic selector for command output (DPSY01 -02) Fixedlogic Fixedlogic/PLC
DPSYxx-CTREN Activate control function (DPSY01 -02) Close Open / Close
DPSYxx-LGEXFFCT Logic selector for operate condition (DPSY01 -02) Fixedlogic Fixedlogic / PLC

GRL200 (Soft 033 & 037)


- 701 -
6F2S1914 (0.37)

4.2.4 Operation counter


The DPSY01 function has an operation-counter†; the user can utilize the operation-counter to
predict the lifespan of switchgear and other functions. The user can select a count mode using
a setting. Table 4.2-23 and Figure 4.2-32 show the modes for which a user is required to change
a mode in response to a device signal. For instance in the DPSY01 function, a user can select
the mode using scheme switch [DPSY01-CNTS] ,which is set to C-On; counting-up is performed
when a switchgear signal gives rise to a change in state from “Open to Closing”.
Table 4.2-23 Mode of operation counter
Mode Description
Counting-up is performed when a signal changes to closed (ON). When the signal
C-On
is changed from “Open to Closed”, the counter value is incremented.
Counting-up is performed when a signal changes to open (OFF). When the signal
C-Off
is changed from “Closed to Open”, the counter value is incremented.
Counting-up occurs when any state change occurs: “Open to Closed” and “Closed
C-OnOff
to Open”.
NA Stops the count function
†Note:The operation-counter value is not cleared when power is removed from the IED.
This counter is available in the DPSY01 and DPSY02 functions.

Closed

Open

Figure 4.2-32 Device Signal

The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation Counter, the user can set a user-
preferred value for the operation-counter. See Chapter User interface: Monitoring sub-menu
on how to operate the sub-menu.

Operation Counter DPSY1-CNT1


10:48 1/25 10:48 1/4
_DPSY1-CNT > DPSY_Dev1-3Ph +
DPSY2-CNT > CANCEL
0
DPOS1-CNT >
DPSY_Dev1-APh +
DPOS2-CNT >
DPOS3-CNT > 0
ENTER DPSY_Dev1-BPh +
DPOS4-CNT >

Figure 4.2-33 Operation counter sub-menu


Note: With regard to the signal “DPSY01_3PH_STATE”, the sub-menu represents it as
“DPSY_Dev1-3Ph”. Analogous to signal “DPSY01_3PH_STATE”, the signal
“DPSY01_APH_STATE” is represented as “DPSY_Dev1-APh”. The signals
“DPSY01_BPH_STATE” and “DPSY01_CPH_STATE” are displayed in a similar
manner.

GRL200 (Soft 033 & 037)


- 702 -
6F2S1914 (0.37)

(i) Receiving “change value for counter” from the remote end
Mapping of Input point required
Figure 4.2-34 depicts the logic when a “change value for counter” command is received at the
DPSY01 logic. With regard to a three-phase counter, the input-point
“DEV01_3PH_CONTROL_REQ” is used. With regard to a phase-A counter, the input-point
“DEV01_APH_CONTROL_REQ” is used. For phase-B and phase-C, the input-points
“DEV01_BPH_CONTROL_REQ” and “DEV01_CPH_CONTROL_REQ” are used.

Input Operate logic in DPSY01 Output

DPSY01 function (Function ID: 511001)

“DPSY01_SLD_CSCN”
(511001 8A02011F88)
Command “change value for counter”
511001_7002016D09 DEV01_3PH_REQ Operate Command
&

Operate condition‡

Figure 4.2-34 Change counter value for three-phase† with operation from the remote-end in
DPSY01
‡Note: The “operate condition” signal is provided from the operate condition logic shown
in Figure 4.2-36.
†Note: The user can apply other counter change commands for phase-A, -B, and –C as
shown in Table 4.2-24. The resultant signals for the DPSY02 logic are shown in
Table 4.2-25.

Output signal to BO
The DPSY01 function can issue a “Result” signal at output point “DPSY01_SLD_CSCN”. The
counter values are issued at points “DPSY01_CNT_VAL", “DPSY01A_CNT_VAL",
“DPSY01B_CNT_VAL", and “DPSY01C_CNT_VAL".

(ii) Receiving “change value for counter” from the local-end


Input signal from the front panel
Figure 4.2-35 depicts the logic when a “change value for counter” command is provided in the
DPSY01 function. The command is provided from the sub-menu (see Figure 4.2-33).

Input Operate logic in DPYS01 Output

DPSY01 function (Function ID: 511001)


“DPSY01_SLD_CSCN”
(511001 8A02011F88)

Command “Change value”

Figure 4.2-35 Changing counter value by operation from the front panel in DPSY01

Output signal to BO

GRL200 (Soft 033 & 037)


- 703 -
6F2S1914 (0.37)

The DPSY01 function can issue a “Result” signal at the output point “DPSY01_SLD_CSCN”.

(iii) Operate condition for the counter


Figure 4.2-36 illustrates the operate condition logic. The DPSY01 function can determine an
operate-condition using a signal received from “Control hierarchy”. The Control hierarchy
condition is provided by user-programmed PLC logic (i.e., 43R/L); the user must connect the
control-hierarchy with the DPSY01 function using connection point “DPSY01IN_TMP_47” (see
Table 4.2-26).

DPSY01 function (Function ID: 511001)


Command blocking*1 To counter logic
CBK_STATE
1≥ Operate condition
&
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR
From CMNCTRL
Detection of serious errors
SERI_ERR

Unmatched condition detected *4


= DPSY01_SC_ST_ERR

From Control hierarchy


511001 800201ED5A DPSY01IN_TMP_47

Figure 4.2-36 Operate condition logic for changing the counter in DPSY01
1Note: “Command Blocking” disables all operation except for its own; the “Command
Blocking” function is initiated by the status of “CBK” in a software switch
controller (SOTFSW). The IEC 61850 standard defines the “Command Blocking”
function as “CmdBlk”. For more information on “CBK”, see Chapter Control and
monitoring application: Software switch controller. See the signal
““S4301_STATE” of Table 4.2-7.
2Note: “Double Command Blocking” (DCB) is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCV OR) in Table 4.2-7.
3Note: If the event “device-travelling” is detected, it indicates that another operator is
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detecting signal is denoted
as “Travelling OR” in Table 4.2-7.
4Note: If the issue of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
4.2-7.

GRL200 (Soft 033 & 037)


- 704 -
6F2S1914 (0.37)

(iv) Signal names and number


Table 4.2-24 Mapping points
Signal Number Signal Name Description
511001 7002016D09 DEV01_3PH_REQ DPSY01 change command received.(Mapping Data) for 3-phase counter value
511001 7002016D0A DEV01_APH_REQ DPSY01 change command received.(Mapping Data) for phase-A counter value
511001 7002016D0B DEV01_BPH_REQ DPSY01 change command received.(Mapping Data) for phase-B counter value
511001 7002016D0C DEV01_CPH_REQ DPSY01 change command received.(Mapping Data) for phase-C counter value
511001 7002026D09 DEV02_3PH_REQ DPSY02 change command received.(Mapping Data) for 3-phase counter value
511001 7002026D0A DEV02_APH_REQ DPSY02 change command received.(Mapping Data) for phase-A counter value
511001 7002026D0B DEV02_BPH_REQ DPSY02 change command received.(Mapping Data) for phase-B counter value
511001 7002026D0C DEV02_CPH_REQ DPSY02 change command received.(Mapping Data) for phase-C counter value

Table 4.2-25 PLC monitoring points and output results


Signal Number Signal Name Description
511001 8A02011F88 DPSY01_SLD_CSCN DPSY01 select command for Binary Output.
511001 3202011D20 DPSY01_CNT_VAL DPSY01 operation counter value
511001 3202011D24 DPSY01A_CNT_VAL DPSY01 phase-A operation counter value
511001 3202011D28 DPSY01B_CNT_VAL DPSY01 phase-B operation counter value
511001 3202011D2C DPSY01C_CNT_VAL DPSY01 phase-C operation counter value
511001 8A02021F88 DPSY02_SLD_CSCN DPSY02 select command for Binary Output.
511001 3202021D20 DPSY02_CNT_VAL DPSY02 operation counter value
511001 3202021D24 DPSY02A_CNT_VAL DPSY02 phase-A operation counter value
511001 3202021D28 DPSY02B_CNT_VAL DPSY02 phase-B operation counter value
511001 3202021D2C DPSY02C_CNT_VAL DPSY02 phase-C operation counter value

Table 4.2-26 PLC connection points for control hierarchy


Signal Number Signal Name Description M/O
511001 800201ED5A DPSY01IN_TMP_47 DPSY01 CNT control hierarchy condition M
511001 800202ED5A DPSY02IN_TMP_47 DPSY02 CNT control hierarchy condition M

(v) Setting name


Table 4.2-27 Setting for pulse counter in DPSYxx
Setting Name Description Default Setting item or value
DPSYxx-CNTS Mode selection of the counter in DPSYxx *user-preferred NA / C-Close / C-Open / C-OnOff

GRL200 (Soft 033 & 037)


- 705 -
6F2S1914 (0.37)

4.2.5 Measurement of operation intervals


The DPSY01 function can measure operation intervals (OT1 to OT4)†; the intervals OT1 to
OT2 can represent the period of time when a switch changes from “Closed” to “open”. In the
DPSY01 function the operation period is grouped into sub-time periods, as shown in Table
4.2-28. The user should set scheme switch [DPSY01-OPETMEN] to On.

Table 4.2-28 Intervals measured in the DPSY01 function


Intervals Trigger Events for measurement
Start Signal “DPSY01_FEX_BO” sensed
OT1 Switch status is changed from “Closed” to
End
“Intermediate”
Start Switch status “Intermediate” sensed
OT2 Switch status is changed from “Intermediate” to
End
“Open”
Start Signal “DPSY01_OEX_BO” sensed
OT3 Switch status is changed from “Open” to
End
“Intermediate”
Start Switch status “Intermediate” sensed
OT4 Switch status is changed from “Intermediate” to
End
“Closed”
†Note:The function “operation time measurement” is also available in the DPSY02
function.

Signal “DPSY01_FEX_BO”

Sensing Intermediate state


Closed Intermediate Open

Device status for Open


OT1 OT2

Figure 4.2-37 Two intervals (OT1 and OT2) for Open-control

Signal “DPSY01_OEX_BO”

Un sensed period
Open Intermediate Closed

Device status for Closed


OT3 OT4

Figure 4.2-38 Two intervals (OT3 and OT4) for Closing-control

The user can clear the operation interval (OT1 to OT4) by key-operation of the “Operation
time” sub-menu (Figure 4.2-39) or operation from the remote-end. See chapter User interface:

GRL200 (Soft 033 & 037)


- 706 -
6F2S1914 (0.37)

Monitoring sub-menu.
Operation Time DPSY1-OT1
10:48 1/26 10:48 1/5
_DPSY1-OT > DPSY_SYN-Dev1-OT1
DPSY2-OT > CANCEL ******.*** ms
DPOS1-OT > DPSY_SYN-Dev1-OT2
DPOS2-OT >
******.*** ms
DPOS3-OT > ENTER DPSY_SYN-Dev1-OT3
DPOS4-OT >

Figure 4.2-39 Operation time sub-menu

(i) Signal names and numbers


Table 4.2-29 Mapping points
Signal Number Signal Name Description
511001 7002016D0D DEV01_RESET_REQ DPSY01 operation time reset command received (Mapping Data)
511001 7002026D0D DEV02_RESET_REQ DPSY02 operation time reset command received (Mapping Data)

(ii) Setting names


Table 4.2-30 Setting of operation time function in DPSY
Setting Name Description Default Setting item or value

DPSY01-OPETMEN Activation of the operation time measurement in DPSY01 On Off / On


DPSY02-OPETMEN Activation of the operation time measurement in DPSY02 On Off / On

GRL200 (Soft 033 & 037)


- 707 -
6F2S1914 (0.37)

4.2.6 Setup for BIO module


The user should connect the DPSY input/output points with the BI and the BO circuits;
subsequently, the DPSY function is able to issue select and operate commands. In order to set
up the DPSY function the user should execute the following four steps. Do not confuse setting
BOs between step (ii) and step (iii).
i BI connection for status
ii BO connection for “select command”
iii BO connection for “operate command”
iv Contact health check

Note that the DPSY01 function commences operation when the scheme switch [DPSY01-
EN] is set to On.

(i) BI connection for status signals


Figure 4.2-40 exemplifies the reception of signals at the DPSY01 function; to acquire the
status§ signal for phase-A, the user should set two input-points for settings [DPSY01A-
NOPSG] and [DPSY01A-NCLSG]†.

†Note:Normally an input-signal corresponding to phase-A is generated using a normally-


open contact (NO) and a normally-closed contact (NC). If a NO and a NC contact
are exchanged, the input-signal should be determined by inversion; that is, the
user is required to set On for both scheme switches [DPSY01A-NOPSGI] and
[DPSY01A-NCLSGI].
§Note: The state signal acquired can be monitored. For more information, see Chapter
Automatic supervision.

Grouping three-phase signals corresponding to a state


Suppose that status signals are acquired on the six BI circuits at IO#1 slot. The signals
corresponding to phase-A can be acquired via N/C and N/O contacts; thus, the user should set
two input-points (8001001110 and 810101110 in 200B01†) for the settings [DPSY01A-NOPSG]
and [DPSY01A-NCLSG], respectively, as shown in Figure 4.2-40. For input points
corresponding to phase-B and phase-C, the user must also apply input-points via settings. The
user sets And for scheme switches [DPSY01-OPC] and [DPSY01-CLC], respectively; finally, the
scheme switch [DPSY01-DEVTYPE] should be set to 3-Pole.

GRL200 (Soft 033 & 037)


- 708 -
6F2S1914 (0.37)

Signals from the


BI circuit and DPSY01 Signal acquisition logic in DPSY01
devices Output ‡

DPSY01
To select and operate
condition logics

“DPSY01_3PH_STATE”
(511001 3102011001)
Phase-A signals BI signal selected by
N/O contact setting [DPSY01A-NOPSG]
Event
signal &
& Suppression
&
1≥ detector
BI signal selected by Open
N/C contact setting [DPSY01A-NCLSG]
“DPSY01_ F_QLT_SPP”
signal & (511001 8102011F5F)
&
Phase-B signals
BI signal selected by & Faulty
N/O contact setting [DPSY01B-NOPSG]
signal &

BI signal selected by &


N/C contact setting [DPSY01B-NCLSG]
signal & Intermediate

Phase-C signals
BI signal selected by
N/O contact setting [DPSY01C-NOPSG]
signal & &

Close
BI signal selected by
N/C contact setting [DPSY01C-NCLSG]
signal &

[DPSY01-EN]
On &
[DPSY01-DEVTYPE]
3-Pole
[DPSY01-OPC]
And
&
[DPSY01-CLC]
And

Figure 4.2-40 Acquisition of a state signal


†Note:The user should set the actual input-points. See chapter Technical description:
Binary IO module.
‡Note:In Figure 4.2-40 two signals can be issued: “DPSY01_3PH_STATE” and
“DPSY01_F_QLT_SPP”. One is used in the select condition logic and operate
condition logic (see Figure 4.2-13 and Figure 4.2-28). Another is used for operation
in the event suppression function. Other signals are also provided:
DPSY01_APH_STATE, DPSY01_BPH_STATE, and DPSY01_CPH_STATE.

Acquisition of a signal corresponding to a phase


Suppose that a state-signal is acquired on the two BI circuits at IO#1 slot. An individual phase
signal can be taken using the N/C and the N/O contacts; thus, the user should set two input-
points (8001001110 and 810101110 in 200B01†) for the settings [DPSY01A-NOPSG] and
[DPSY01A-NCLSG], respectively, as shown in Figure 4.2-41. The user should set the scheme
switch [DPSY01-DEVTYPE] to 1-Pole.

GRL200 (Soft 033 & 037)


- 709 -
6F2S1914 (0.37)

Signals from the


BI circuit and DPSY01 Signal acquisition logic in DPSY01
devices Output ‡

DPSY01
To select and operate
condition logics

“DPSY01_3PH_STATE”
(511001 3102011001)
Single phase signals BI signal selected by
N/O contact setting [DPSY01A-NOPSG]
Event
signal &
& Suppression
1≥ detector
BI signal selected by Open
N/C contact setting [DPSY01A-NCLSG]
“DPSY01_ F_QLT_SPP”
signal & (511001 8102011F5F)
&
Faulty

&
Intermediate

&

Close

[DPSY01-EN]
On &
[DPSY01-DEVTYPE]
1-Pole

Figure 4.2-41 Acquisition of single-phase signal at DPSY01


‡Note:In Figure 4.2-41 two signals can be issued “DPSY01_3PH_STATE” and
“DPSY01_F_QLT_SPP”, which are the same as the signals in the Figure 4.2-40.

Event suppression
If the status of a device “chatters” for a short time, the DPSY function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPSY function;
hence, event suppression can be required to reduce the additional burden created.

[DPSY-NELD]

Signal 2 4 6 8
from device
1 3 5 7

Suppressed
signal

[DPSY-TELD] [DPSY-TELR]
Time................. A B C D E

Figure 4.2-42 Iterative signals and signals suppressed

Figure 4.2-42 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time ‘B’). This is because the function can count the iterative number of
incoming signals. Detection commences at Time ‘A’, the setting [DPSY-NELD] is provided so
that the suppression commences at Time B. The setting [DPSY-TELD] is pertains to the

GRL200 (Soft 033 & 037)


- 710 -
6F2S1914 (0.37)

operation of the detection function from Time ‘A’ (e.g., Time ‘A’ to Time ‘C’).

The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [DPSY-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time ‘D’ to ‘E’).

To initiate event suppression the user should set On for scheme switch [DPSY01-SPPEN].

(ii) BO connection for “select command Open/Closing”


Figure 4.2-43 exemplifies the connection for the select command Open/Closing. Suppose that
connection with the BOs is achieved by the PLC function using connection points
“DPSY01_OSL_BO_FLG” and “DPSY01_FSL_BO_FLG”†; as a result, the “Select command
Closing” and the “Select command Open” signals are issued at BO1 and BO2 respectively.

Terminal and
Select logic in DPSY01 BO1 circuit at IO#1(Function ID: 200B01) wire

“DPSY01_OSL_BO_FLG”
(5110018602011DC6)
Select logic for Select Command “BO1” Select
Signal captured by Command
Closing in DPSY01 setting [Input signal 1] ≥1 (200B01_8002001112)
Closing
[Input signal 2] DRIVER BO1
To contact health & ≥1
check [Input signal 3]
“BO1-RB”
[Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
Select logic for Select Command check
Open in DPSY01 [Input signal 7]
[Input signal 8]

PLC connection point on BO1

200B01 310200E11D BO1_SOURCE

Terminal and
BO2 circuit at IO#1 (Function ID: 200B01) wire
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4)
“BO2” Select
Signal captured by Command
setting [Input signal 1] ≥1 (200B01_8102011112)
Open
[Input signal 2] DRIVER BO2
& ≥1
To contact health
[Input signal 3]
check “BO2-RB”
[Input signal 4] [BO2_CPL] On &
(200B01_8102011113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]

PLC connection point on BO2

200B01 310201E11D BO2_SOURCE

Figure 4.2-43 Example for select commands connection with BO1 & BO2 at IO#1
†Note:Table 4.2-10 shows the remaining signals with the excepting
“DPSY01_OSL_BO_FLG” and “DPSY01_FSL_BO_FLG”.

(iii) BO connection for “operate command Open/Closing”


Figure 4.2-44 exemplifies the connection for “Operate command Closing” or “Operate command
Open”. Suppose that connection with the BOs is achieved by the PLC function using connection

GRL200 (Soft 033 & 037)


- 711 -
6F2S1914 (0.37)

points “DPSY01_OEX_BO” and “DPSY01_FEX_BO”; as a result, the “Operate command


Closing” and the “Operate command Open” signals are issued at BO3 and BO4 respectively.

Terminal and
Operate logic in DPSY01 BO3 and BO4 circuit at IO#1 (Function ID: 200B01) wire

“DPSY01_OEX_BO”
(511001 8202011DD3)
Operate
“BO3” command
Signal captured by
Operate logic for setting [Input signal 1] ≥1 (200B01_8202021112) Closing to
the device
“Operate command [Input signal 2] DRIVER BO3
Closing” & ≥1
[Input signal 3]
“BO3-RB”
[Input signal 4] [BO3_CPL] On &
Connected by Off
(200B01_8202021113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO3


“DPSY01_FEX_BO” 200B01 310202E11D BO3_SOURCE
(511001 8102011DD0)
Operate
“BO4” command
Signal captured by
Operate logic for setting [Input signal 1] ≥1 (200B01_8302031112) Open to the
device
“Operate command [Input signal 2] DRIVER BO4
Open” & ≥1
[Input signal 3]
“BO4-RB”
[Input signal 4] [BO4_CPL] On &
Connected by Off
(200B01_8302031113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO4

200B01 310203E11D BO4_SOURCE

Figure 4.2-44 Example of operate commands connected with BO2 and BO3 at IO#1
†Note:Table 4.2-36 shows the remaining signals excepting “DPSY01_OEX_BO” and
“DPSY01_FEX_BO”.

(iv) Contact health check


The DPSY01 function has a contact health check feature for the BO circuits; hence, the user is
able to connect an output signal to the contact health check function when Fixedlogic is set for
scheme switch [DPSY01-LGXFEOT]†. Consequently, the DPSY01 function can determine
whether the signal has been successfully output from the BO. If a failure is reported, the
DPSY01 function determines that the signal has not been output successfully to the BO; then,
the Closing- or Open-command is canceled immediately and the DPSY01 function returns to
the “Wait for a command” stage.

†Note:Table 4.2-38 shows settings for the health check feature in the DPSY02 function.

GRL200 (Soft 033 & 037)


- 712 -
6F2S1914 (0.37)

Setting for “Select command Closing”


For example, the point “DPSY01_OSL_BO_FLG” is connected to the BO1 circuit for the issuing
of the command; the user can connect point “BO1-RB” with the contact health check function
using the setting [DPSY01-OSLBORD]. Do not key the point “DPSY01_OSL_BO_FLG”.

Selection logic in
DPSY01

Contact health check


“DPSY01_OSL_BO_FLG”
logic in DPSY01
(511001 8602011DC6)

Result of contact
BO1 circuit at & health check
IO#1

“BO1-RB”
(200B01_8002001113)
Signal connected by
setting [DPSY01-OSLBORD]

Connection made by the user

Figure 4.2-45 Example connection of “Select command Closing” for the health check feature

Setting the “Select command Open”


Similar to “select command Closing”, the point “DPSY01_FSL_BO_FLG” is connected with the
BO2 circuit; the user is required to key point “BO2-RB” for the setting [DPSY01-FSLBORD].
Do not key the point “DPSY01_FSL_BO_FLG”.
Selection logic in
DPSY01

Contact health check


“DPSY01_FSL_BO_FLG”
logic in DPSY01
(511001 8A02011DC4)

Result of contact
BO1 circuit at & health check
IO#1

“BO2-RB”
(200B01_8102001113)
Signal connected by
setting [DPSY01-FSLBORD]

Connection made by the user

Figure 4.2-46 Example connection of “Select command Open” for the health check feature

Setting for “Operate command Closing”


Similarly, the point “BO3-RB” must be applied for the setting [DPSY01-OEXBORD].

GRL200 (Soft 033 & 037)


- 713 -
6F2S1914 (0.37)

Selection logic in
DPSY01

“DPSY01_OEX_BO” Contact health check


“511001 8202011DD3” logic in DPSY01

Result of contact
BO3circuit at & health check
IO#1

“BO3-RB”
“200B01_8202021113”
Signal designated by
setting [DPSY01-OEXBORD]

Connection made by the user

Figure 4.2-47 Example connection of “Operate command Closing” for the health check feature

Setting for “Operate command Open”


Similarly, the point “BO4-RB” must be applied for the setting [DPSY01-FEXBORD].
Selection logic in
DPSY01

Contact health check


“DPSY01_FEX_BO”
logic in DPSY01
“511001 8102011DD0”

Result of contact
BO4 circuit at & health check
IO#1

“BO4-RB”
“200B01_8302031113”
Signal designated by
setting [DPSY01-FEXBORD]

Connection made by the user

Figure 4.2-48 Example connection of “Operate command Open” for the health check feature

GRL200 (Soft 033 & 037)


- 714 -
6F2S1914 (0.37)

Setting for the contact health check (normal setting, example)


Figure 4.2-49 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1 to BO4 contacts. To check that the contact health check function is working
correctly, the respective points of the BO-RBs should be connected as shown in Table 4.2-31, to
demonstrate that the settings are physically matched with the BO contacts.

Table 4.2-31 Setting example for contact health check


Example #1 Contact health check settings for example #1

“DPSY01_OSL_BO_FLG” is connected to “BO1” at IO#1 [DPSY01-OSLBORD] =” 200B018002001113”(BO1-RB) OK

“DPSY01_FSL_BO_FLG” is connected to “BO2” at IO#1 [DPSY01-FSLBORD]=” 200B018102011113” (BO2-RB) OK

“DPSY01_OEX_BO_CSF” is connected to “BO3” at IO#1 [DPSY01-OEXBORD]=” 200B018202021113” (BO3-RB) OK

“DPSY01_FEX_BO_CSF” is connected to “BO4” at IO#1 [DPSY01-OEXBORD]=” 200B018302031113” (BO4-RB) OK

BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“DPSY01_OSL_BO_FLG”
(511001 8602011DC6) SW1 is driven with
BO1 at IO#1
Select-Closing BO1 SW 1
command
“BO1-RB”
(200B01_8002001113) SW 3 Closing
“DPSY01_FSL_BO_FLG”
SW2 is driven with
(511001 8A02011DC4)
BO2 at IO#1
Select-Open BO2 SW 2
command
“BO2-RB”
(200B01_8102011113) SW 4 Open
“DPSY01_OEX_BO”
SW3 is driven with
(511001 8202011DD3)
BO3 at IO#1
Operate-Closing BO3
Minus (−)
command
“BO3-RB”
(200B01_8202021113)
“DPSY01_FEX_BO”
(511001 8102011DD0) SW4 is driven with
BO4 BO4 at IO#1
Operate-Open
command “BO4-RB”
(200B01_8302031113)

Figure 4.2-49 Contact health check setting and 43SW diagram for example #1

GRL200 (Soft 033 & 037)


- 715 -
6F2S1914 (0.37)

Settings for erroneous contact health check (improper setting, example #2)
Figure 4.2-50 shows a setting example an improper setting of the 43SW scheme. The settings
are implemented incorrectly as shown in Table 4.2-32, BO1-RB is not chosen, instead BO1 is
actually chosen, which is incorrect. In this case, the setting [DPSY01-OSLBORD] is
meaningless; hence, the issue of a select command is blocked.

Table 4.2-32 Erroneous setting example for contact health check


Example #2 Contact health check setting for example #2

“DPSY01_OSL_BO_FLG” is connected to “BO1” Close SLOT1 [DPSY01-OSLBORD] =” 200B018002001112”(BO1) NG

“DPSY01_FSL_BO_FLG” is connected to “BO2” Close SLOT1 [DPSY01-FSLBORD]=” 200B018102011113” (BO2-RB) OK

“DPSY01_OEX_BO_CSF” is connected to “BO3” Close SLOT1 [DPSY01-OEXBORD]=” 200B018202021113” (BO3-RB) OK

“DPSY01_FEX_BO_CSF” is connected to “BO4” Close SLOT1 [DPSY01-OEXBORD]=” 200B018302031113” (BO4-RB) OK

BIO module
Local/remote-end “BO1” (not BO1-RB) Drivers 43SW
Plus (+)
“DPSY01_OSL_BO_FLG” mistakenly chosen with
“200B01_8002001112”
(511001 8602011DC6) SW1 is driven with
BO1 at IO#1
Select command BO1 SW 1
Closing

SW 3 Closing
“DPSY01_FSL_BO_FLG” command
SW2 is driven with
(511001 8A02011DC4)
BO2 at IO#1
Select command BO2 SW 2
Open
“BO2-RB”
(200B01_8102011113) SW 4 Open
“DPSY01_OEX_BO” command
(511001 8202011DD3) SW3 is driven with
BO3 at IO#1
Operate command BO3
Minus (−)
Closing
“BO3-RB”
(200B01_8202021113)
“DPSY01_FEX_BO”
(511001 8102011DD0) SW4 is driven with
BO4 BO4 at IO#1
Operate command
Open “BO4-RB”
(200B01_8302031113)

Figure 4.2-50 Contact health check setting and 43SW diagram for example #2

GRL200 (Soft 033 & 037)


- 716 -
6F2S1914 (0.37)

Settings for extra contact health check (special setting, example #3)
Figure 4.2-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “DPSY01_OSL_BO_FLG” is actually chosen for the
setting [DPSY01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command, which is called “operated by internal select function”. The user
does not need to consider the use of a BO circuit for a select command, when there are no BO
circuits available.
Table 4.2-33 Extra setting example for contact health check
Example #3 Setting for example #3

“DPSY01_OSL_BO_FLG” is not connected to any BO [DPSY01-OSLBORD] =” DPSY01_OSL_BO_FLG” OK

“DPSY01_FSL_BO_FLG” is not connected to any BO [DPSY01-FSLBORD]=” ” DPSY01_OSL_BO_FLG” OK

“DPSY01_OEX_BO_CSF” is connected to “BO3” at IO#1 [DPSY01-OEXBORD]=” 200B018202021113” (BO3-RB) OK

“DPSY01_FEX_BO_CSF” is connected to “BO4” at IO#1 [DPSY01-OEXBORD]=” 200B018202031113” (BO4-RB) OK

BIO module
Local/Remote-end Drivers 43SW
Plus (+)
“DPSY01_OSL_BO_FLG”
(511001 8602011DC6)
SW1 is not driven with
Select command any BO
SW 1
Closing
Physical BOs
SW 3 Closing
are virtualized. command
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4) SW2 is not driven with
any BO
Select command
SW 2
Open

SW 4 Open
“DPSY01_OEX_BO” command
(511001 8202011DD3) SW3 is driven with
BO3 at IO#1
Operate command BO3
Closing Minus (−)
“BO3-RB”
(200B01_8202021113)
“DPSY01_FEX_BO”
(511001 8102011DD0) SW4 is driven with
Operate command BO4 BO4 at IO#1
Open “BO4-RB”
(200B01_8302031113)

Figure 4.2-51 Contact health check setting and 43SW diagram for example #3
Table 4.2-34 PLC monitoring points (Output signal for event suppression function in DPSY)
Signal Number Signal Name Description
511001 3102011001 DPSY01_3PH_STATE DPSY01 3ph_state
511001 3102021001 DPSY02_3PH_STATE DPSY02 3ph_state
511001 8102011F5F DPSY01_F_QLT_SPP Event suppression detected (DPSY01)
511001 8102021F5F DPSY02_F_QLT_SPP Event suppression detected (DPSY02)

Table 4.2-35 PLC monitoring points (Output of select signal in DPSY)


Signal Number Signal Name Description
511001 8602011DC6 DPSY01_OSL_BO_FLG DPSY01 select (CLOSE) command for Binary Output.
511001 8602021DC6 DPSY02_OSL_BO_FLG DPSY02 select (CLOSE) command for Binary Output.
511001 8A02011DC4 DPSY01_FSL_BO_FLG DPSY01 select (OPEN) command for Binary Output.
511001 8A02021DC4 DPSY02_FSL_BO_FLG DPSY02 select (OPEN) command for Binary Output.

GRL200 (Soft 033 & 037)


- 717 -
6F2S1914 (0.37)

Table 4.2-36 PLC monitoring points (Output of operate signal in DPSY)


Signal Number Signal Name Description
511001 8202011DD3 DPSY01_OEX_BO DPSY01 operate (CLOSE) command for Binary Output.
511001 8202021DD3 DPSY02_OEX_BO DPSY02 operate (CLOSE) command for Binary Output.
511001 8102011DD0 DPSY01_FEX_BO DPSY01 operate (OPEN) command for Binary Output.
511001 8102021DD0 DPSY02_FEX_BO DPSY2 operate (OPEN) command for Binary Output.

(v) Setting names


Table 4.2-37 Setting for Binary input signals in DPSY
Setting Name Description Default Setting item or value
DPSY01-CTREN Activate control function (DPSY01) On Off / On
DPSY01-CTRAHMI Activate local panel control(DPSY01) SBO DIR / SBO
DPSY01-EN Activate monitoring function (DPSY01) Close Open / Close
DPSY01-DEVTYPE Phase selector switch 3-pole 3-pole/1-pile/ switch
DPSY01-OPC Activate monitoring function (DPSY01) Close Open / Close
DPSY01-CPC Activate monitoring function (DPSY01) Close Open / Close
DPSY01A-NOPSG BI position for DPSY01 *none BI signal
DPSY01A-NCLSG BI position for DPSY01 *none BI signal
DPSY01B-NOPSG BI position for DPSY01 *none BI signal
DPSY01B-NCLSG BI position for DPSY01 *none BI signal
DPSY01C-NOPSG BI position for DPSY01 *none BI signal
DPSY01C-NCLSG BI position for DPSY01 *none BI signal
DPSY01-SPPEN Activate event suppression for DPSY01 On On / Off (Close/Open)
DPSY02-CTREN Activate control function (DPSY02) On Off / On
DPSY02-CTRAHMI Activate local panel control(DPSY02) SBO DIR / SBO
DPSY02-EN Activate monitoring function (DPSY02) Close Open / Close
DPSY02-DEVTYPE Phase selector switch 3-pole 3-pole/1-pile/ switch
DPSY02-OPC Activate monitoring function (DPSY02) Close Open / Close
DPSY02-CPC Activate monitoring function (DPSY02) Close Open / Close
DPSY02A-NOPSG BI position for DPSY02 *none BI signal
DPSY02A-NCLSG BI position for DPSY02 *none BI signal
DPSY02B-NOPSG BI position for DPSY02 *none BI signal
DPSY02B-NCLSG BI position for DPSY02 *none BI signal
DPSY02C-NOPSG BI position for DPSY02 *none BI signal
DPSY02C-NCLSG BI position for DPSY02 *none BI signal
DPSY02-SPPEN Activate event suppression for DPSY02 On On / Off (Close/Open)
DPSY-NELD Number of change to lock status. 10 0~99
DPSY-TELD Time to locking state( sliding window ) 10[sec] 1~99[sec]
DPSY-TELR Time to unlocking state( sliding window ) 10[sec] 1~99[sec]

Table 4.2-38 Settings for health check function in DPSY


Setting Name Description Default Setting item or value
DPSY01-OSLBORD Select BO signal (BO*-RB) from signal list *User-preferred BO read-back signal
DPSY01-FSLBORD Select BO signal (BO*-RB) from signal list *User-preferred BO read-back signal
DPSY01-OEXBORD Select BO signal (BO*-RB) from signal list *User-preferred BO read-back signal
DPSY01-FEXBORD Select BO signal (BO*-RB) from signal list *User-preferred BO read-back signal
DPSY02-OSLBORD Select BO signal (BO*-RB) from signal list *User-preferred BO read-back signal
DPSY02-FSLBORD Select BO signal (BO*-RB) from signal list *User-preferred BO read-back signal
DPSY02-OEXBORD Select BO signal (BO*-RB) from signal list *User-preferred BO read-back signal
DPSY02-FEXBORD Select BO signal (BO*-RB) from signal list *User-preferred BO read-back signal

GRL200 (Soft 033 & 037)


- 718 -
6F2S1914 (0.37)

4.2.7 Mapping for IEC 61850 communication


The user can operate the DPSY function over IEC 61850 communications† following mapping
using GR-TIEMS. Note that the DPSY function is designed for the class of “Double Point
Controller (DPC)” in the IEC 61850 standard for communication. The user should follow these
steps, each of which is discussed below:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user will need to create a logical node (LN) for the DPSY01 function. Figure 4.2-52
exemplifies the editing of a LN; the LN “Common Switch controller (CSWI)” is chosen for the
DPSY01 function. After the user has defined an object “DPC”, the DPSY01 logical node can be
saved with the name “CSWI” plus “LN Instance”. Create a definition of object “DPC” in the
DPSY01 logical node. Either the SBO mode or the DIR mode should be chosen in the editing
for the LN.

SBO defined in LN

Figure 4.2-52 Defining “DPC” object in CSWI1 logic node

Defining SBO mode


Figure 4.2-53 exemplifies the DPSY01 logic node saved as “CSWI1”. In the SBO mode, the user
should select the following items for the “CSWI1$Pos” using GR-TIEMS:

GRL200 (Soft 033 & 037)


- 719 -
6F2S1914 (0.37)

 SBOw
 Oper
 Cancel
 origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.

Figure 4.2-53 LN editing screen for SBO mode

Defining DIR mode


Figure 4.2-54 exemplifies the SPOS logic node saved as “CSWI1”. In the DIR mode, the
following three items should be selected using GR-TIEMS.

 Oper
 origin
 ctlmodel (choice ”DOes or DOns” )

Figure 4.2-54 LN editing screen for DIR mode

(ii) Mapping output data


The user should group the DPSY01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS. Figure 4.2-55 illustrates
how to map a signal; it indicates that the signals for the DPSY01 function are required to be
mapped for IEC 61850 communications.

GRL200 (Soft 033 & 037)


- 720 -
6F2S1914 (0.37)

Table 4.2-39 Mapping signals for CSWI1 object


Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/CSWI1$Pos$origin orCat orCategory ST 511001 3102011008 DPSY01_3PH_ORCAT

Ctrl/CSWI1$Pos$origin orIdent Octet64 ST 511001 6A02011009 DPSY01_3PH_ORIDENT

Ctrl/CSWI1$Pos stVal Dbpos ST 511001 3102011001 DPSY01_3PH_STATE

Ctrl/CSWI1$Pos q Quality ST 511001 3102011005 DPSY01_3PH_QUALITY

Ctrl/CSWI1$Pos t Timestamp ST 511001 9002011006 DPSY01_3PH_TIMESTAMP

Ctrl/CSWI1$Pos stSeld BOOLEAN ST 511001 0002011D90 DPSY01_STD_RPT

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850.

Drag and drop

Figure 4.2-55 orCat attribute mapped into DPC object of CSWI1

(iii) Mapping input data


The DPSY01 function can receive three commands “select, operate and cancel.” Thus, the user
should map the input-point “DEV01_CONTROL_REQ” to the IEC 61850 configuration. Table
4.2-40 shows the input-point “DEV01_CONTROL_REQ” and the Object reference
“Ctrl/CSWI1$Pos”; the user should map the input-point to the Object reference having attribute
CO†.. Figure 4.2-56 shows how to map a signal.

†Note: The attribute is defined in the IEC 61850; “CO” stands for “Control” in the
functional constraint (FC).

GRL200 (Soft 033 & 037)


- 721 -
6F2S1914 (0.37)

Table 4.2-40 Mapping signals required for DPC object for CSWI1
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/CSWI1$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI1$Pos$SBOw ctlNum INT8U CO
Ctrl/CSWI1$Pos$SBOw T Timestamp CO
Ctrl/CSWI1$Pos$SBOw Test BOOLEAN CO
Ctrl/CSWI1$Pos$SBOw Check Check CO
Ctrl/CSWI1$Pos$SBOw$origin orCat orCategory CO
Ctrl/CSWI1$Pos$SBOw$origin orIdent Octet64 CO
Ctrl/CSWI1$Pos$Oper ctlVal BOOLEAN CO
Ctrl/CSWI1$Pos$Oper ctlNum INT8U CO
Ctrl/CSWI1$Pos$Oper T Timestamp CO
Ctrl/CSWI1$Pos$Oper Test BOOLEAN CO
5110017002016D08 DEV01_CONTROL_REQ
Ctrl/CSWI1$Pos$Oper Check Check CO
Ctrl/CSWI1$Pos$Oper$origin orCat orCategory CO
Ctrl/CSWI1$Pos$Oper$origin orIdent Octet64 CO
Ctrl/CSWI1$Pos$Cancel ctlVal BOOLEAN CO
Ctrl/CSWI1$Pos$Cancel ctlNum INT8U CO
Ctrl/CSWI1$Pos$Cancel T Timestamp CO
Ctrl/CSWI1$Pos$Cancel Test BOOLEAN CO
Ctrl/CSWI1$Pos$Cancel$origin orCat orCategory CO
Ctrl/CSWI1$Pos$Cancel$origin orIdent Octet64 CO
Ctrl/CSWI1$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI1$Pos$SBOw ctlNum INT8U CO

Drag and drop

Check “Input”

Figure 4.2-56 Input-point mapped for CSWI1

GRL200 (Soft 033 & 037)


- 722 -
6F2S1914 (0.37)

4.2.8 Setting
DPSY01(FunctionID:511001)
Setting items Range Unit Contents Default Note

Common DPSY-NELD 0 - 99 - Number of Event lock detect time 10


DPSY-TELD 1 - 99 s Timer of detect event lock 10
DPSY-TELR 1 - 99 s Timer of recovery from event lock 10
DPSY01-EN Off / On - DPSY switch for DEV01 Off
DEV01 DPSY01-DEVNAME [Preferred text] - item name of DPOSSY_Dev1 DPOS_SYN_Dev1 !
DPSY01-00NAME [Preferred text] - state name of (0,0)state Travelling0 !
DPSY01-01NAME [Preferred text] - state name of (0,1)state Off !
DPSY01-10NAME [Preferred text] - state name of (1,0)state On !
DPSY01-11NAME [Preferred text] - state name of (1,1)state Travelling1 !
DPSY01-UDFNAME [Preferred text] - state name of undefined Undefine !
DPSY01-FLTNAME [Preferred text] - state name of faulty Faulty !
DPSY01-DEVTYPE 1-Pole / 3-Pole - Device Type 1-Pole
Normally Open Signal of the single-pole or
DPSY01A-NOPSG [Preferred signal] - Not Assigned
phase A
DPSY01A-NOPSGI Off / On - Signal inverse or not Off
Normally Close Signal of the single-pole or
DPSY01A-NCLSG [Preferred signal] - Not Assigned
phase A
DPSY01A-NCLSGI Off / On - Signal inverse or not Off
DPSY01B-NOPSG [Preferred signal] - Normally Open Signal of phase B Not Assigned
DPSY01B-NOPSGI Off / On - Signal inverse or not Off
DPSY01B-NCLSG [Preferred signal] - Normally Close Signal of phase B Not Assigned
DPSY01B-NCLSGI Off / On - Signal inverse or not Off
DPSY01C-NOPSG [Preferred signal] - Normally Open Signal of phase C Not Assigned
DPSY01C-NOPSGI Off / On - Signal inverse or not Off
DPSY01C-NCLSG [Preferred signal] - Normally Close Signal of phase C Not Assigned
DPSY01C-NCLSGI Off / On - Signal inverse or not Off
DPSY01-OPC And / Or - Normally Open contact grouping And
DPSY01-CLC And / Or - Normally Close contact grouping Or
DPSY01-SPPEN Off / On - Automatic event suppression function Off
Off / On /
DPSY01-UDFEN - undefined pallet check function Off
CHKONLY
DPSY01-UDFTIM 0.1 - 100.0 s palette undefined check timer 30.0
Off / On /
DPSY01-FLTEN - faulty pallet check function Off
CHKONLY
DPSY01-FLTTIM 0.1 - 100.0 s palette faulty check timer 30.0
DPSY01-CTREN Off / On - control mode (control enable) Off
DPSY01-SYNEN APPLY / Bypass - Synchronism Check Apply or Bypass APPLY
DPSY01-CTRMENU Off / On - control by MENU enable Off
DPSY01-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
select binary output read data(DataID)1 for no
DPSY01-NSLBORD1 [Preferred signal] - 5110018902011DC0
direction command
select binary output read data(DataID)2 for no
DPSY01-NSLBORD2 [Preferred signal] - 5110018902011DC0
direction command
select binary output read data(DataID) for off
DPSY01-FSLBORD [Preferred signal] - 5110018A02011DC4
direction select command
select binary output read data(DataID) for on
DPSY01-OSLBORD [Preferred signal] - 5110018602011DC6
direction select command
execute binary output read data(DataID) for
DPSY01-FEXBORD [Preferred signal] - Not Assigned
off direction execute command
execute binary output read data(DataID) for
DPSY01-OEXBORD [Preferred signal] - Not Assigned
on direction execute command

GRL200 (Soft 033 & 037)


- 723 -
6F2S1914 (0.37)

DPSY01(FunctionID:511001)
Setting items Range Unit Contents Default Note

FixedLogic /
DPSY01-LGCTRCON - Change logic about control condition FixedLogic
PLC
FixedLogic /
DPSY01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
DPSY01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about off direction execute
DPSY01-LGFEXOT - FixedLogic
PLC output
FixedLogic / Change logic about on direction execute
DPSY01-LGOEXOT - FixedLogic
PLC output
FixedLogic /
DPSY01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
DPSY01-PLSM Fix / Var - pulse mode Fix
DPSY01-CPW 0.1 - 50.0 s control pulse width 1.0
DPSY01-RST 1.0 - 100.0 s response check timer 30.0
NA / C-On / C-
DPSY01-CNTS - count status NA
Off / C-OnOff
DPSY01-OPETMEN Off / On - Operation Time Measurement enable Off
DPSY01-APBD Process / Bay - status change origin Process
DPSY01-CTRDIR Off / On - Capable control direction On
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The DPSY function is also available for the second device; hence, the table for 2nd
device is available, but we have omitted the 2nd table because it is similar to the
table for the 1st device with the exception of the device number.

GRL200 (Soft 033 & 037)


- 724 -
6F2S1914 (0.37)

4.2.9 Signal
 Signal monitoring points in DPSY01
DPSY(Function ID: 511001)
Element ID Name Description
8002011DE0 DEV1PLCCTRLFAIL DEV1PLCCTRLFAIL
8002001F99 DPSY00_CH_EC_LCD DPSY00 count change execute command by LCD
8002001D5E DPSY00_CH_EC_OWS DPSY00 count change execute command by OWS(HMI)
8002001D5F DPSY00_CH_EC_RCC DPSY00 count change execute command by RCC
8002001D60 DPSY00_CH_EC_RMT DPSY00 count change execute command by Remote
8002001F98 DPSY00_CH_SC_LCD DPSY00 count change select command by LCD
8002001D5B DPSY00_CH_SC_OWS DPSY00 count change select command by OWS(HMI)
8002001D5C DPSY00_CH_SC_RCC DPSY00 count change select command by RCC
8002001D5D DPSY00_CH_SC_RMT DPSY00 count change select command by Remote
0002011FB6 DPSY01A_CNT_SEL DPSY01 A count change selected signal(stSeld) for SAS
3202011D24 DPSY01A_CNT_VAL DPSY01 A-phase count value
8302011F49 DPSY01A_FLT_DET DPSY01 A-phase Faulty Detected
8302011F48 DPSY01A_FLT_STA DPSY01 A-phase Faulty Start
3102011D14 DPSY01A_LCD_ST DPSY01 A-phase state for LCD
8202011F47 DPSY01A_UDF_DET DPSY01 A-phase Undefined Detected
8202011F46 DPSY01A_UDF_STA DPSY01 A-phase Undefined Start
0002011FB7 DPSY01B_CNT_SEL DPSY01 B count change selected signal(stSeld) for SAS
3202011D28 DPSY01B_CNT_VAL DPSY01 B-phase count value
8502011F4D DPSY01B_FLT_DET DPSY01 B-phase Faulty Detected
8502011F4C DPSY01B_FLT_STA DPSY01 B-phase Faulty Start
3102011D19 DPSY01B_LCD_ST DPSY01 B-phase state for LCD
8402011F4B DPSY01B_UDF_DET DPSY01 B-phase Undefined Detected
8402011F4A DPSY01B_UDF_STA DPSY01 B-phase Undefined Start
0002011FB8 DPSY01C_CNT_SEL DPSY01 C count change selected signal(stSeld) for SAS
3202011D2C DPSY01C_CNT_VAL DPSY01 C-phase count value
8702011F51 DPSY01C_FLT_DET DPSY01 C-phase Faulty Detected
8702011F50 DPSY01C_FLT_STA DPSY01 C-phase Faulty Start
3102011D1E DPSY01C_LCD_ST DPSY01 C-phase state for LCD
8602011F4F DPSY01C_UDF_DET DPSY01 C-phase Undefined Detected
8602011F4E DPSY01C_UDF_STA DPSY01 C-phase Undefined Start
3102011001 DPSY01_3PH_STATE DPSY01 3ph_state
3102011FE5 DPSY01_APH_STATE DPSY01 aph_state
0002011F58 DPSY01_AUTO_SIG DPSY01 Auto sequence signal
3102011FEA DPSY01_BPH_STATE DPSY01 bph_state
8302011E9C DPSY01_CCF_FCT_CS DPSY01 Release poor factor
8702011E96 DPSY01_CC_FS DPSY01 cancel fail signal
8602011E95 DPSY01_CC_SS DPSY01 cancel success signal
8802011E9B DPSY01_CC_ST_ERR DPSY01 Disagreement in the mode (the test in a release command)
0002011F59 DPSY01_CMNCTRL_SIG DPSY01 control receive signal
8602011F8A DPSY01_CNT_CS07 DPSY01 count change selected fail condition signal
0002011D91 DPSY01_CNT_SEL DPSY01 count change selected signal(stSeld) for SAS
0002011F56 DPSY01_CNT_SIG DPSY01 Count correction signal
3202011D20 DPSY01_CNT_VAL DPSY01 count value
3102011FEF DPSY01_CPH_STATE DPSY01 cph_state
8002011E9E DPSY01_CTR_SGC DPSY01 control logic stage(select command check)
8002011EA0 DPSY01_CTR_SGE DPSY01 control logic stage(execute command check)
8302011E9D DPSY01_CTR_SGN DPSY01 control logic stage(unselected)
8002011E9F DPSY01_CTR_SGS DPSY01 control logic stage(selected)
8B02011F79 DPSY01_CTR_SGU DPSY01 selected signal
8902011F9B DPSY01_CTR_SGUCN DPSY01 count change selected signal
8902011FA1 DPSY01_CTR_SGURS DPSY01 reset time selected signal

GRL200 (Soft 033 & 037)


- 725 -
6F2S1914 (0.37)

 Signal monitoring points in DPSY01


DPSY(Function ID: 511001)
Element ID Name Description
8002011EA1 DPSY01_CTR_SGW DPSY01 control logic stage(wait for change)
8102011E9A DPSY01_ECF_FCT_EIS DPSY01 execute command fail factor signal except interlock/synchronism check
8002011D58 DPSY01_EC_LCD DPSY01 execute command by LCD
8002011D55 DPSY01_EC_OWS DPSY01 execute command by OWS(HMI)
8002011D59 DPSY01_EC_PLC DPSY01 execute command by PLC
8002011D56 DPSY01_EC_RCC DPSY01 execute command by RCC
8002011D57 DPSY01_EC_RMT DPSY01 execute command by Remote
8002011F5B DPSY01_EC_ST_ERR DPSY01 execute command mode err
0002011D97 DPSY01_EX_BO_OPOK DPSY01 execute binary output signal for SAS
8002011E93 DPSY01_EX_CMP DPSY01 execute complete signal
8F02011F5E DPSY01_EX_CMP_TMO DPSY01 timeout after execute completion
8902011FA0 DPSY01_EX_CMP_TMOCN DPSY01 count change timeout after execute completion
8902011FA6 DPSY01_EX_CMP_TMORS DPSY01 reset time timeout after execute completion
8902011F6D DPSY01_EX_CS01 DPSY01 response supervisory timer for open
8A02011F6E DPSY01_EX_CS02 DPSY01 response supervisory timer for close
8B02011F6F DPSY01_EX_CS03 DPSY01 open timer for under execution
8C02011F70 DPSY01_EX_CS04 DPSY01 close timer for under execution
8602011E91 DPSY01_EX_FFL DPSY01 execute fail signal by fixedlogic
8502011E8F DPSY01_EX_SFL DPSY01 execute success signal by fixedlogic
8202011E88 DPSY01_FEC_F_CS DPSY01 off direction execute command fail condition signal
8102011E85 DPSY01_FEC_F_CSF DPSY01 off direction execute command fail condition signal by fixedlogic
8002011E81 DPSY01_FEC_OK_CS DPSY01 off direction execute command OK condition signal
8002011E7E DPSY01_FEC_OK_CSF DPSY01 off direction execute command OK condition signal by fixedlogic
8102011DD0 DPSY01_FEX_BO DPSY01 off direction execute binary output signal
8102011F41 DPSY01_FLT_DET0 DPSY01 Faulty Detected
8102011F45 DPSY01_FLT_DET1 DPSY01 Faulty Detected (3 phase concentration data only)
8102011F44 DPSY01_FLT_STA DPSY01 Faulty Start
8A02011DC4 DPSY01_FSL_BO_FLG DPSY01 off direction select binary output signal
8A02011F81 DPSY01_FSL_CS19 DPSY01 select receive open signal check answer
8202011F60 DPSY01_F_BI_ERR DPSY01 Inside of connection poor of binary input
8102011F5F DPSY01_F_QLT_SPP DPSY01 Under a lock of change of state
3102011D01 DPSY01_LCD_ST DPSY01 state for LCD
3102011D00 DPSY01_MMC_ST DPSY01 state for MIMIC
8902011DC0 DPSY01_NSL_BO_FLG DPSY01 select binary output signal
8602011F7E DPSY01_NSL_CS07 DPSY01 select receive signal check answer
8302011E89 DPSY01_OEC_F_CS DPSY01 on direction execute command fail condition signal
8102011E86 DPSY01_OEC_F_CSF DPSY01 on direction execute command fail condition signal by fixedlogic
8102011E82 DPSY01_OEC_OK_CS DPSY01 on direction execute command OK condition signal
8002011E7F DPSY01_OEC_OK_CSF DPSY01 on direction execute command OK condition signal by fixedlogic
8B02011E48 DPSY01_OEC_RCV DPSY01 on direction execute command received
8202011DD3 DPSY01_OEX_BO DPSY01 on direction execute binary output signal
8002011E45 DPSY01_OSE_RCV DPSY01 on direction select or execute command received
8602011DC6 DPSY01_OSL_BO_FLG DPSY01 on direction select binary output signal
8802011F73 DPSY01_OSL_CS41 DPSY01 on direction select condition signal 41
8902011F74 DPSY01_OSL_CS42 DPSY01 on direction select condition signal 42
8A02011F75 DPSY01_OSL_CS43 DPSY01 on direction select condition signal 43
8402011F76 DPSY01_OSL_CS44 DPSY01 selected condition signal 44
8502011F77 DPSY01_OSL_CS45 DPSY01 selected condition signal 45
8602011F78 DPSY01_OSL_CS46 DPSY01 selected condition signal 46
3102011F91 DPSY01_OT1_SIGNAL DPSY01 operation time1 reset signal
3102011D30 DPSY01_OT1_VAL DPSY01 operation time1 value
3102011F93 DPSY01_OT2_SIGNAL DPSY01 operation time2 reset signal
3102011D33 DPSY01_OT2_VAL DPSY01 operation time2 value

GRL200 (Soft 033 & 037)


- 726 -
6F2S1914 (0.37)

 Signal monitoring points in DPSY01


DPSY(Function ID: 511001)
Element ID Name Description
3102011F95 DPSY01_OT3_SIGNAL DPSY01 operation time3 reset signal
3102011D36 DPSY01_OT3_VAL DPSY01 operation time3 value
3102011F97 DPSY01_OT4_SIGNAL DPSY01 operation time4 reset signal
3102011D39 DPSY01_OT4_VAL DPSY01 operation time4 value
8002011F98 DPSY01_RE_EC_LCD DPSY01 reset time execute command by LCD
8002011D7B DPSY01_RE_EC_OWS DPSY01 reset time execute command by OWS(HMI)
8002011D7C DPSY01_RE_EC_RCC DPSY01 reset time execute command by RCC
8002011D7D DPSY01_RE_EC_RMT DPSY01 reset time execute command by Remote
8002011F9A DPSY01_RE_SC_LCD DPSY01 reset time select command by LCD
8002011D78 DPSY01_RE_SC_OWS DPSY01 reset time select command by OWS(HMI)
8002011D79 DPSY01_RE_SC_RCC DPSY01 reset time select command by RCC
8002011D7A DPSY01_RE_SC_RMT DPSY01 reset time select command by Remote
8602011F8E DPSY01_RST_CS07 DPSY01 reset time selected fail condition signal
0002011F57 DPSY01_RST_SIG DPSY01 Reset time signal
8002011D54 DPSY01_SC_LCD DPSY01 select command by LCD
8002011D51 DPSY01_SC_OWS DPSY01 select command by OWS(HMI)
8002011D52 DPSY01_SC_RCC DPSY01 select command by RCC
8002011D53 DPSY01_SC_RMT DPSY01 select command by Remote
8002011F5A DPSY01_SC_ST_ERR DPSY01 select command mode err
0002011F55 DPSY01_SEL_SIG DPSY01 Selected signal
8502011F89 DPSY01_SE_RCV_RMTCN DPSY01 count change selected fail condition signal check
8502011F8D DPSY01_SE_RCV_RMTRS DPSY01 reset time selected fail condition signal check
8002011E76 DPSY01_SLD_CS DPSY01 selected condition signal
8002011F67 DPSY01_SLD_CS04 DPSY01 selected condition signal 04
8102011F68 DPSY01_SLD_CS05 DPSY01 selected condition signal 05
8202011F69 DPSY01_SLD_CS06 DPSY01 selected condition signal 06
8A02011F88 DPSY01_SLD_CSCN DPSY01 count change selected condition signal
8A02011F8C DPSY01_SLD_CSRS DPSY01 reset time selected condition signal
0002011D90 DPSY01_SLD_RPT DPSY01 selected signal(stSeld) for SAS
8E02011F5D DPSY01_SLD_TMO DPSY01 time out after selected
8A02011F9F DPSY01_SLD_TMOCN DPSY01 count change time out after selected
8A02011FA5 DPSY01_SLD_TMORS DPSY01 reset time out after selected
8102011E7B DPSY01_SLF_CS DPSY01 no direction select fail condition signal
8702011E98 DPSY01_SLF_FCT_EIS DPSY01 select fail factor signal except interlock/synchronism check
8802011F9D DPSY01_SLF_FCT_F03CN DPSY01 count change select fail factor signal by fixedlogic 03
8802011FA3 DPSY01_SLF_FCT_F03RS DPSY01 reset time select fail factor signal by fixedlogic 03
8702011F9E DPSY01_SLF_FCT_F04CN DPSY01 count change select fail factor signal by fixedlogic 04
8702011FA4 DPSY01_SLF_FCT_F04RS DPSY01 reset time select fail factor signal by fixedlogic 04
8302011F9C DPSY01_SLF_FCT_F07CN DPSY01 count change selected timer for a check
8302011FA2 DPSY01_SLF_FCT_F07RS DPSY01 reset time selected timer for a check
8602011F63 DPSY01_SLF_FCT_FLG03 DPSY01 select fail factor signal by fixedlogic 03
8702011F64 DPSY01_SLF_FCT_FLG04 DPSY01 select fail factor signal by fixedlogic 04
8502011F65 DPSY01_SLF_FCT_FLG05 DPSY01 select fail factor signal by fixedlogic 05
8802011F6C DPSY01_SLF_FCT_FLG07 DPSY01 selected timer for a check
8002011E7D DPSY01_SLR_CS DPSY01 select release condition signal
8302011D02 DPSY01_ST_OFF DPSY01 Normal open state
8102011D03 DPSY01_ST_ON DPSY01 Normal close state
8C02011E4B DPSY01_SYNC_OPT_TRIG DPSY01 start to synchronizing
8D02011E4A DPSY01_SYNC_SEL_TRIG DPSY01 start to check voltage condition(Dead or Live)
8202011ED1 DPSY01_SYNEN DPSY01 Synchronism Check Apply or Bypass
0002011D95 DPSY01_TMP_02 DPSY01 time reset selected signal(stSeld) for SAS
3102011D80 DPSY01_TMP_06 DPSY01 control event data (selected)
3102011D81 DPSY01_TMP_07 DPSY01 control event data (select fail)

GRL200 (Soft 033 & 037)


- 727 -
6F2S1914 (0.37)

 Signal monitoring points in DPSY01


DPSY(Function ID: 511001)
Element ID Name Description
3102011D82 DPSY01_TMP_08 DPSY01 control event data (select release)
3102011D83 DPSY01_TMP_09 DPSY01 control event data (execute output on)
3102011D84 DPSY01_TMP_10 DPSY01 control event data (execute command ng)
3102011D86 DPSY01_TMP_11 DPSY01 control event data (execute fail)
8202011F7C DPSY01_TMP_61 DPSY01 select bo signal check
8002011F7D DPSY01_TMP_62 DPSY01 select receive signal check
8102011F7F DPSY01_TMP_64 DPSY01 select bo open signal check
8502011F80 DPSY01_TMP_65 DPSY01 select receive open signal check
8502011F82 DPSY01_TMP_67 DPSY01 select bo close signal check
8602011F83 DPSY01_TMP_68 DPSY01 select bo close(synchronism) signal check
8702011F84 DPSY01_TMP_69 DPSY01 select bo close(interlock) signal check
8502011F85 DPSY01_TMP_70 DPSY01 select receive closed signal check
8602011F86 DPSY01_TMP_71 DPSY01 select receive closed signal check answer
8002011F87 DPSY01_TMP_72 DPSY01 count change selected condition signal check
8002011F8B DPSY01_TMP_73 DPSY01 reset time selected condition signal check
0002011F53 DPSY01_TRA DPSY01 travelling info
0002011F54 DPSY01_TRA_CTR DPSY01 travelling info for control
8002011F40 DPSY01_UDF_DET0 DPSY01 Undefined Detected
8002011F43 DPSY01_UDF_DET1 DPSY01 Undefined Detected (3 phase concentration data only)
8002011F42 DPSY01_UDF_STA DPSY01 Undefined Start

 Connection point in PLC logic


DPSY(Function ID: 511001)
Element ID Name Description
800201EE32 DEV01_CL_COMMAND dev01 close command

800201EE33 DEV01_CL_INTERLOCK dev01 close command with interlock bypass

800201EE34 DEV01_CL_SYNC dev01 close command with synchronism check bypass

800201EE35 DEV01_CL_SYNC_INTER dev01 close command with interlock and synchronism check bypass

800201EE30 DEV01_OP_COMMAND dev01 open command

800201EE31 DEV01_OP_INTERLOCK dev01 open command with interlock bypass

830201EF56 DPSY01IN_TMP_25 DPSY01IN_TMP_25

820201ED50 DPSY01IN_TMP_28 DPSY01IN_TMP_28

800201EE53 DPSY01IN_TMP_29 DPSY01IN_TMP_29

810201EE54 DPSY01IN_TMP_30 DPSY01IN_TMP_30

800201EE61 DPSY01IN_TMP_31 DPSY01IN_TMP_31

810201EE62 DPSY01IN_TMP_32 DPSY01IN_TMP_32

800201EE55 DPSY01IN_TMP_33 DPSY01IN_TMP_33

800201EE56 DPSY01IN_TMP_34 DPSY01IN_TMP_34

810201EE57 DPSY01IN_TMP_35 DPSY01IN_TMP_35

820201EE5A DPSY01IN_TMP_37 DPSY01IN_TMP_37

830201EE5B DPSY01IN_TMP_38 DPSY01IN_TMP_38

800201EE65 DPSY01IN_TMP_40 DPSY01IN_TMP_40

810201EE66 DPSY01IN_TMP_41 DPSY01IN_TMP_41

800201EDDA DPSY01IN_TMP_42 DPSY01IN_TMP_42

810201EDDB DPSY01IN_TMP_43 DPSY01IN_TMP_43

820201EE5E DPSY01IN_TMP_44 DPSY01IN_TMP_44

830201EE5F DPSY01IN_TMP_45 DPSY01IN_TMP_45

GRL200 (Soft 033 & 037)


- 728 -
6F2S1914 (0.37)

 Connection point in PLC logic


DPSY(Function ID: 511001)
Element ID Name Description
800201EE69 DPSY01IN_TMP_46 DPSY01IN_TMP_46

800201ED5A DPSY01IN_TMP_47 DPSY01IN_TMP_47

800201ED77 DPSY01IN_TMP_48 DPSY01IN_TMP_48

 Mapping points in DPSY01


DPSY(Function ID: 511001)
Element ID Name Description
7002016D08 DEV01_CONTROL_REQ DPSY01 control command received. (Mapping Data)

Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the DPSY function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.

Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “DPSY01_SC_OWS” point for
the 2nd device, use the description of “DPSY01_SC_OWS” in place of
“DPSY02_SC_OWS”. The user can obtain the ID value of
“DPSY02_SC_OWS” by using the following steps:
Step 1 Find the element ID for DPSY01_SC_OWS (i.e.,
“8002011D51”).
Step 2 Identify the number at the fifth digit from the ID. (i.e.,
“1”).
Step 3 Choose a new device number. (i.e. pick the number “2” for
the 2nd device).
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8002021D51” of
“DPSY02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.

GRL200 (Soft 033 & 037)


- 729 -
6F2S1914 (0.37)

Software switch controller function (SOFTSW)


Sixty-four position software-switches (CBK, ICB, SCB, and -01 to -61) are provided in the IED
memory as virtual switches; they are used to determine the operation of internal processes in
the IED. Either the criteria “Enable (On)” or “Disable (Off)” may be applied for each software
switch, S43. Three software switches have already been defined for special purposes; the three
are controlled by command blocking (CBK), interlock bypassing (ICB), and synchronism
bypass (SCB) functions. On the other hand, switches S43-01 to S43-61 are provided for general-
purpose usage.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features depends on the selection of hardware and the
configuration of functions. Several IED models do not have its features. To determine whether
its features are implemented in the IED, locate the IED ordering number; and check the order
number at the “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 4.3-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
– CBK, ICB, SCB functions NA ✓
– Programmable switches (S43) NA 61
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 730 -
6F2S1914 (0.37)

Figure 4.3-1 shows the eight switches and their controller functions. The statuses of the S43
switches are stored in the IED non-volatile memory; hence, the IED can retrieve their status
while power is not being supplied to the IED.

Switches for
CMDBLK ILKBYP SCBYP special purposes
(CBK) (ICB) (SCB)

SOFTSW1 SOFTSW2 SOFTSW3 SOFTSW61 General purpose


(S43-01) (S43-02) (S43-03) (S43-61) switches

Figure 4.3-1 Software switches (S43s) and their controller

The SOFTSW function can control a number of S43 software switches separately. To
simplify the explanation provided below only the SOFTSW1 function is discussed. The features
provided in CBK, ICB, SCB and SOFTSW2–61 switches are similar to the SOFTSW1 switch.
Tips: The user can operate CBK, ICB and SCB without user programming. Jump to
section 4.3.5 where we discuss how to map their signals for IEC61850
communication. When the user wishes to program the SOFTSW functions using
the S43-01–S43-61 switches, the user is required to read from section 4.3.2
onwards.

4.3.1 SOFTSW controlling


(i) Command blocking (CBK)
When the user wishes to avoid the control of devices by mistake during test and maintenance,
the user can use the command blocking function so that mal-operation can be avoided. The
execution of command blocking is available from the IED front panel. Additionally, the IEC
61850 standard provides command blocking (CmdBlk) for remote operation and the CBK
function is defined at the logical node (LN) given in IEC 61850-7-1 (Edition 2.0). Thus, the IED
can override all commands received when the command blocking function is engaged from the
local-end and the remote-end. With regard to the command “CmdBlk” from the remote-end,
the command is received at the input point “CBK_CONROL_REQ”, as shown in Table 4.3-2.
For SOFTSW1 operation, the user should set the scheme switch [CBK-EN] to On.
Input CBK logic Output

To “Select condition logic” and


Reception of CMDBLK “Operate condition logic” †
CBK_STATE
All control commands must be blocked simultaneously
Blocking of all commands is (522001 000A011001)
522001 700A016D08 CBK__CONTROL_REQ
performed.

Figure 4.3-2 Logic “CBK” and response “CBK_STATE”


†Note:The user is required to map a communication signal to the input-point. For
mapping, see section 4.3.5. The “CBK_STATE” signal is used in control
applications so that control applications can determine their operational

GRL200 (Soft 033 & 037)


- 731 -
6F2S1914 (0.37)

conditions. (See control and operation logic for the respective control applications.)

(ii) Interlock bypassing (ICB) provided


When the user executes control applications from the IED front panel, the Interlock bypassing
(ICB) function enables control applications to bypass their interlock conditions if required.
When the ICB is engaged, all control processes, operated from the IED front panel, are able to
bypass their interlock conditions. The user should note that operation of the ICB function is
available for five minutes following its initiation. For operation of the ICB function, the user
should set the scheme switch [ICB-EN] to On.
Input ICB logic Output
To “Select logic” and
Reception of ILKBYP in S4302 ICB_STATE “Operation logic”†
All interlocking condition shall be bypassed Interlock bypassing is (522001 000A021001
on the operation from the IED front panel performed. )

Figure 4.3-3 Logic “ICB” and response “ICB_STATE”


†Note:The ICB_STATE is provided for the “Select logic” and “Operate logic” in the
control applications.

(iii) Synchronism bypassing (SCB)


Synchronism bypass (SCB) enables control applications to bypass synchronizing conditions if
the user wishes control applications to bypass synchronizing conditions, if the user executes
the control applications from the IED front panel. If the SCB is executed, all control processes,
operated from the IED front panel, will bypass their respective synchronizing conditions. Note
that the bypass operation is available for five minutes following initiation of the SCB function.
For operation of the SCB function, the user should set the scheme switch [SCB-EN] to On.
Input SCB logic Output
To select/operate condition logics†
Reception of SCBYP in S4303 SCB_STATE
All synchronizing conditions shall be Synchronism bypassing is (522001 000A031001)
bypassed on operation from the IED front
performed.
panel
)

Figure 4.3-4 Logic “SCB” and response “SCB_STATE”


†Note:The SCB_STATE is provided for the “Select logic” and “Operate logic” relating to
the control applications including synchronism-check features.

(iv) S43-01 to S43-61 controlling provided by SOFTSW1 to SOFTSW61†


The SOFTSW1 to SOFTSW61 functions are provided for control of the S43-01 to S43-61
switches, as described previously. For example, Figure 4.3-5 shows the SOFTSW1 function
controlling the S43-01 switch; control of the S43-01 switch is enabled when the user sets the
scheme switch [S4301-EN]† to On. Likewise, the user is required to set On for scheme switches
[S4302-EN] to [S4361-EN] with regard to the SOFTSW2–61 operations, respectively.

GRL200 (Soft 033 & 037)


- 732 -
6F2S1914 (0.37)

Input SOFTSW1 logic Output


To user-programmed logic
Command reception in S4301 S4301_STATE
Command provided by the PLC function
Software switch operation is (522001 000A041001)
522001 700A046D08 S4301__CONTROL_REQ performed.

Figure 4.3-5 Logic “SOFTSW1” and response “S4301_STATE”

(v) SOFTSW output-status


Table 4.3-2 shows the list of output signals of the SOFTSW functions.
Table 4.3-2 Output signals of SOFTSW function
Signal Number Signal Name Description
522001 000A011001 CBK_STATE CBK status ( Off / Blocked)
522001 000A021001 ICB_STATE IBK switch status
522001 000A031001 SCB_STATE SCB switch status
522001 000A041001 S4301_STATE S43-01 switch status
522001 000A051001 S4302_STATE S43-02 switch status
522001 000A061001 S4303_STATE S43-03 switch status
…. …. ….
522001 000A401001 S4361_STATE S43-61 switch status

GRL200 (Soft 033 & 037)


- 733 -
6F2S1914 (0.37)

4.3.2 Control logics for SBO/DIR modes


For example, the user should set scheme switch [S4301-EN] to On when the SOFTSW1
function is required to be operated. Table 4.3-10 shows all scheme switches for the SOFTSW
functions.

(i) Receiving “select command for On operation” from the remote-end


Input point required mapping
Figure 4.3-6 shows the logic when a “Select command (Remote-ON-Control)” signal is applied
to the SOFTSW1 function. The logic has an input-point “S4301_CONTROL_REQ” for the
reception of the select command. That is, the input-point should be mapped for the IEC61850
communication. The input-point “S4301_CONTROL_REQ” is significant for the SOFTSW1
operation; hence, an operation failure in the IED is indicated if mapping is not performed
correctly. Section 4.3.5 discusses how to map the information of the IEC61850 to the input-
510001 7001016D08
points.
Input Select logic in SOFTSW1 Output

SOTFSW1 function (Function ID: 522001)


Command “Remote-On-Control”
For SBO operation
522001_700A046D08 S4301_CONTROL_REQ Select command
& 1≥ &

For DIR operation


For monitoring
Operate command
& “S4301_OSD_CSF”
(522001_8F0A041F49)

0 t Select “success”
0.1s

To “Wait for a command”


0 t
Select “Failed”
0.6s

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate
510001 8601011DC
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.3-6 Select logic for ‘ON’ operation from remote end in SOFTSW1†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-6 and Table 4.3-9.
‡Note:“Select condition” signal is provided from select condition scheme. For more
information, see Figure 4.3-12.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SOFTSW1 function is blocked for the ASEQ function when
it is in operation. For more information of the ASEQ function, see Chapter Control
and monitoring application: Automatic sequence control function.
*Note:The SOFTSW1 function can run on either the “SBO mode” or the “DIR mode”. The
user can use the signal “ctlmodel” in the IEC61850 communication.

GRL200 (Soft 033 & 037)


- 734 -
6F2S1914 (0.37)

Output signal for monitoring


The user can monitor a “Select success” signal at the output point “S4301_OSL_CSF”, when
the SOFTSW1 function determines that the received “Remote-ON-Control” signal is true. If
the SOFTSW1 function determines that the “Remote-ON-Control” is not true, the SOFTSW1
function returns to the “Wait for a command” stage.

(ii) Receiving “select command for Off operation” from the remote end
Input point required mapping
Figure 4.3-7 shows the logic when a “Select command (Remote-OFF-Control)” signal is applied
at the SOFTSW1 function. The input-point “S4301_CONTROL_REQ” is used for the reception
of the select command (Remote-OFF-Control).
Input Select logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)


Command “Remote-Off-Control”
For SBO operation
522001_700A046D08 S4301_CONTROL_REQ Select command
& 1≥ &

For DIR operation


For monitoring
Operate command
& “S4301_FSD_CSF”
(522001_8D0A041F45)
0 t Select “success”
0.1s

To “Wait for a command”


0 t
Select “Failed”
0.6s

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.3-7 Select logic for ‘OFF’ operation from remote end in SOFTSW1†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-6 and Table 4.3-9.
‡Note:“Select condition” signal is provided in Figure 4.3-12.

Output signal for monitoring


The SOFTSW1 function, in Figure 4.3-7, can issue a “Select success” signal at output point
“S4301_FSL_CSF” when the SOFTSW1 function determines that the input signal “Select
command (Remote-OFF-Control)” is true. If the SOFTSW1 function determines that the
“Remote-OFF-Control” is not true, the SOFTSW1 function returns to the “Wait for a command”
stage.

(iii) Receiving “Selection command for On operation” from the front

GRL200 (Soft 033 & 037)


- 735 -
6F2S1914 (0.37)

panel
Input signal
Figure 4.3-8 shows the logic when a “Select command (Local-ON-Control)” signal is applied to
the SOFTSW1 function. The input signal is provided when “On” key is pressed on the IED
front panel; the input-point is not required to be mapped. Note that the user should set scheme
switch [S4301-CTRAHMI] to SBO when the operation from the IED front panel is performed;
chapter User interface: Control sub-menu discusses how to operate.
Input Select logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)


For SBO operation
Command “Local-On-Control” Select command
& 1≥ &
For DIR operation SBO
Operate command For monitoring
& “S4301_OSD_CSF”
(522001_8F0A041F49)
DIR
0 t
Select “success”
0.1s

To “Wait for a command”


0 t
Select “Failed”

0.6s

[S4301-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.3-8 Select logic for ‘ON’ operation at the IED locally in SOFTSW1†
†Note: To identify the output points of the other SOFTSW logics, see Table 4.3-9.
‡Note:Signal “select condition” is provided. See Figure 4.3-12.
§Note:The SOFTSW1 function is blocked when the ASEQ function is in operation.

Output signal for monitoring


When the state of “select condition” is true, the SOFTSW1 function can issue an output signal
“Select success” at the output-point “S4301_OSD_CSF”.
Note: The signal “S4301_OSD_CSF” is the same signal as shown in Figure 4.3-6. If the
input signal “Local-ON-Control” is not true, the SOFTSW1 function returns to the
“Wait for a command” stage.

(iv) Receiving “Select command for Off operation” from the front panel
Input signal
Figure 4.3-9 shows the logic when a “Select command (Local-OFF-Control)” signal is applied
to the SOFTSW1 logic. The input signal is provided when the user presses “OFF” key on the
IED front panel; the input-point is not required to be mapped.

GRL200 (Soft 033 & 037)


- 736 -
6F2S1914 (0.37)

Input Select logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)


For SBO operation
Command “Local-Off-Control” Select command
& 1≥ &
For DIR operation SBO
Operate command For monitoring

& “S4301_FSD_CSF”
(522001_8D0A041F45)
DIR
0 t
Select “success”

0.1s

To “Wait for a command”


0 t Select “Failed”

0.6s

[S4301-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.3-9 Select logic for ‘OFF’ operation at the IED locally in SOFTSW1†
†Note: Figure 4.3-9 is used for the discussion of SOFTSW1 logic. To identify the output
points of the other SOFTSW logics, see Table 4.3-9.
‡Note:Signal “select condition” is provided. See Figure 4.3-12.

Output signal for monitoring


When the state of “select condition” is true, the SOFTSW1 function can issue a “Select success”
signal at the output-point “S4301_FSD_CSF”.
Note: The “S4301_FSD_CSF” signal is the same as the signal shown in Figure 4.3-7.
That is, this signal of the logic appears at the same PLC monitoring point. If the
input signal “Local-OFF-Control” is not true, the SOFTSW1 function returns to
the “Wait for a command” stage.

(v) Receiving “Select command for On operation” using the PLC


function
Input signal required to connect
Figure 4.3-10 shows that the select logic when a “Select command (PLC-ON-Control)” signal
is applied to the SOFTSW1 logic. The input signal is generated using the user-programmed
PLC logic; the user can connect the signal for the PLC connection point “S4301_CHG_TO_ON”.

GRL200 (Soft 033 & 037)


- 737 -
6F2S1914 (0.37)
510001 7001016D08

Signals from user-PLC logic Select logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)


ON-control command
For DIR operation†
(PLC connection point #1)
Operate command
522001 850A04EDE1 S4301_CHG_TO_ON For monitoring

& “S4301_OSD_CSF”
(522001_8F0A411F49)

0 t Select “success”
0.1s

To “Wait for a command”


Select condition‡ 0 t
Select “Failed”
0.6s

Figure 4.3-10 Select logic for ON operation by PLC in SOFTSW1††


†Note:Direct operation mode (DIR) is only available.
‡Note:“select condition” signal is provided. See Figure 4.3-12.
††Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-3 and Table 4.3-9.

Output signal for monitoring


The SOFTSW1 function shown in Figure 4.3-10, can issue a “Select success” signal at output-
point “S4301_OSD_CSF”.
Note: The signal “S4301_OSD_CSF” is the same as the signal shown in Figure 4.3-6.

(vi) Receiving “Select command for Off operation” using PLC function
Input signal required to connect
Figure 4.3-11 shows the SOFTSW1 logic for a “Select command (PLC-OFF-Control)” signal.
The input signal is generated using the user-programmed PLC logic; the user can connect the
signal for the PLC connection point “S4301_CHG_TO_OFF”.
510001 7001016D08

Signals from user-PLC logic Selection logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)


OFF-control command
For DIR operation†
(PLC connection point #2)
Operate command
522001 860A04EDE0 S4301_CHG_TO_OFF For monitoring

& “S4301_FSD_CSF”
(522001_8D0A411F45)

0 t Select “success”
0.1s

To “Wait for a command”


Select condition‡ 0 t
Select “Failed”
0.6s

Figure 4.3-11 Select logic for OFF operation by PLC in SOFTSW1††


†Note:Direct operation mode (DIR) is available only.
‡Note:Signal “select condition” is provided. See Figure 4.3-12.
††Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-4 and Table 4.3-9.

GRL200 (Soft 033 & 037)


- 738 -
6F2S1914 (0.37)

Output signal to monitoring


The SOFTSW1 function shown in Figure 4.3-11, can issue a “Select success” signal at the
output point “S4301_FSD_CSF”.
Note: The output point “S4301_FSD_CSF” is the same as the signal shown in Figure
4.3-7.

(vii) Select condition


Figure 4.3-12 shows the select condition logic of the SOFTSW1 function. The SOFTSW1
function can examine an operate-condition using “Command Blocking” signal1.

SOFTSW1 function (Function ID: 522001)


Command blocking*1 defined as ”CBK”)
To selection logic
CBK_STATE
1≥ Select condition
&
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR

Function “Automatic sequence control” is in progress


Unmatched condition detected *5
ASEQ_MULTI_SEL

Tripping *4 (“General trip”)


GEN.TRIP

Command “ON control” received &


Command “OFF control” received &
received
S4301_STATE
(522001 000A411001)
Same Directional
Controlling Event

Users must setup this condition correctly


Control hierarchy (e.g. 43RL) (PLC connection point #3)*6
522001 820A04ED50 S4301_CTRL_RIGHT
&
IED serious error detected
SERI_ERR

[S4301-EN]

On

Figure 4.3-12 Select condition logic for ‘ON/OFF’ in SOFTSW1


1Note: “Command Blocking” disables any operation except its own; see the signal
“S4301_STATE (Table 4.3-2)” as the state of “Command Blocking” in the SOFTSW
function.
2Note: “Double Command Blocking (DCB_RCV_OR in Table 4.3-8)” is an operation
philosophy. It can be used to protect a substation. The user can configure it using
GR-TIEMS.
3Note: If the event “device-travelling (Traveling OR in Table 4.3-8)” is detected in the
IED, it indicated that another operator is changing the status of a device. Thus,
the IED should inhibit the operation of any device for the duration that the event
is detected.
4Note: If tripping (GEN.TRIP in Table 4.3-8) is executed in the IED, any control
operation is blocked upon the trip operation. Tripping can be introduced by the
protection function if the IED has protection functions.

GRL200 (Soft 033 & 037)


- 739 -
6F2S1914 (0.37)

5Note: Criteria “unmatched conditions” are decided when “Test-bit status” in command is
not identical to “IED test status”.
6Note: The user will need to program the PLC logic “Control hierarchy condition”. The
Control hierarchy condition provided by the user-programmed PLC logic may be
43R/L; the user can connect it at PLC connection point “S4301_CTRL_RIGHT” of
Table 4.3-5.

(viii) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicates that the signal is provided for optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.3-3 PLC connection point #1 (Inputs point for ‘On’ control)
Signal Number Signal Name Description M/O
522001 850A01EDE1 CBK_CHG_TO_ON PLC ON control for CBK O
522001 850A02EDE1 ICB_CHG_TO_ON PLC ON control for ICB O
522001 850A03EDE1 SCB_CHG_TO_ON PLC ON control for SCB O
522001 850A04EDE1 S4301_CHG_TO_ON PLC ON control for SOFTSW1 (S43-01) O
522001 850A05EDE1 S4302_CHG_TO_ON PLC ON control for SOFTSW2 (S43-02) O
522001 850A06EDE1 S4303_CHG_TO_ON PLC ON control for SOFTSW3 (S43-03) O
…. ….. ….
522001 850A40EDE1 S4361_CHG_TO_ON PLC ON control for SOFTSW61 (S43-61) O

Table 4.3-4 PLC connection point #2 (Input points for ‘Off’ control)
Signal Number Signal Name Description M/O
522001 860A01EDE0 CBK_CHG_TO_OFF PLC OFF control for CBK O
522001 860A02EDE0 ICB_CHG_TO_OFF PLC OFF control for ICB O
522001 860A03EDE0 SCB_CHG_TO_OFF PLC OFF control for SCB O
522001 860A04EDE0 S4301_CHG_TO_OFF PLC OFF control for SOFTSW1 (S43-01) O
522001 860A05EDE0 S4302_CHG_TO_OFF PLC OFF control for SOFTSW2 (S43-02) O
522001 860A06EDE0 S4303_CHG_TO_OFF PLC OFF control for SOFTSW3 (S43-03) O
…. ….. ….
522001 860A40EDE0 S4361_CHG_TO_OFF PLC OFF control for SOFTSW61 (S43-61) O

Table 4.3-5 PLC connection point #3 (Input points on select condition logic)
Signal Number Signal Name Description M/O
522001 820A01ED50 CBK_CTRL_RIGHT Control hierarchy condition in CBK M
522001 820A02ED50 ICB_CTRL_RIGHT Control hierarchy condition in ICB M
522001 820A03ED50 SCB_CTRL_RIGHT Control hierarchy condition in SCB M
522001 820A04ED50 S4301_CTRL_RIGHT Control hierarchy condition in SOFTSW1 (S43-01) M
522001 820A05ED50 S4302_CTRL_RIGHT Control hierarchy condition in SOFTSW2 (S43-02) M
522001 820A06ED50 S4303_CTRL_RIGHT Control hierarchy condition in SOFTSW3 (S43-03) M
…. ….. ….

GRL200 (Soft 033 & 037)


- 740 -
6F2S1914 (0.37)

Signal Number Signal Name Description M/O


522001 820A40ED50 S4303_CTRL_RIGHT Control hierarchy condition in SOFTSW61 (S43-61) M

Table 4.3-6 Mapping points for the command reception in SOFTSWx


Signal Number Signal Name Description M/O

522001 700A016D08 CBK_CONTROL_REQ Control command received in CBK M


522001 700A026D08 ICB_CONTROL_REQ Control command received in ICB M
522001 700A036D08 SCB_CONTROL_REQ Control command received in SCB M
522001 700A046D08 S4301_CONTROL_REQ Control command received in SOFTSW1 (S43-01) M
522001 700A056D08 S4302_CONTROL_REQ Control command received in SOFTSW2 (S43-02) M
522001 700A066D08 S4303_CONTROL_REQ Control command received in SOFTSW3 (S43-03) M
…. ….. ….
522001 700A406D08 S4361_CONTROL_REQ Control command received in SOFTSW61 (S43-61) M

Table 4.3-7 Mapping points for the output signals of SOFTSWx


Signal Number Signal Name Description M/O
522001 000A011D90 CBK_STSELD Selection completed signal in CBK M
522001 000A021D90 ICB_STSELD Selection completed signal in ICB M
522001 000A031D90 SCB_STSELD Selection completed signal in SCB M
522001 000A041D90 S4301_STSELD Selection completed signal in SOFTSW1 (S43-01) M
522001 000A051D90 S4302_STSELD Selection completed signal in SOFTSW2 (S43-02) M
522001 000A061D90 S4303_STSELD Selection completed signal in SOFTSW3 (S43-03) M
…. ….. ….
522001 000A401D90 S4361_STSELD Selection completed signal in SOFTSW61 (S43-61) M

Table 4.3-8 Input signals for condition logic


Signal Number Signal Name Description M/O
5A0001 0008001F41 DCB RCV OR Double Command Blocking (DCB) is in progress. N/A
5A0001 0008001F40 Traveling OR Travelling events are detected. N/A
4A0001 8300001B6F GEN. TRIP General trip N/A
5A0001 3108003F40 SDCEN (This is setting of CMNCTRL) N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A
523001 000D001F40 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A

Table 4.3-9 PLC monitoring points (ON and OFF selection completion)
Signal Number Signal Name Description
522001 8F0A011F49 CBK_OSD_CSF On Selection completed in CBK
522001 8F0A021F49 ICB_OSD_CSF On Selection completed in ICB
522001 8F0A031F49 SCB_OSD_CSF On Selection completed in SCB
522001 8F0A041F49 S4301_OSD_CSF On Selection completed in SOFTSW1 (S43-01)
522001 8F0A051F49 S4302_OSD_CSF On Selection completed in SOFTSW2 (S43-02)
522001 8F0A061F49 S4303_OSD_CSF On Selection completed in SOFTSW3 (S43-03)
…. …. …..
522001 8F0A401F49 S4361_OSD_CSF On Selection completed in SOFTSW61 (S43-61)
522001 8D0A011F45 CBK_FSD_CSF Off Selection completed in CBK
522001 8D0A021F45 ICB_FSD_CSF Off Selection completed in ICB
522001 8D0A031F45 SCB_FSD_CSF Off Selection completed in SCB
522001 8D0A041F45 S4301_FSD_CSF Off Selection completed in SOFTSW1 (S43-01)
522001 8D0A051F45 S4302_FSD_CSF Off Selection completed in SOFTSW2 (S43-02)
522001 8D0A061F45 S4303_FSD_CSF Off Selection completed in SOFTSW3 (S43-03)

GRL200 (Soft 033 & 037)


- 741 -
6F2S1914 (0.37)

Signal Number Signal Name Description


…. …. ….
522001 8D0A401F45 S4361_FSD_CSF Off Selection completed in SOFTSW61 (S43-61)

(ix) Setting names

Table 4.3-10 Setting of SOFTSWx control


Setting Name Description Default Setting item or value
CBK-EN Function activation in CBK On Off / On
ICB-EN Function activation in ICB On Off / On
SCB-EN Function activation in SCB On Off / On
S4301-EN Function activation in SOFTSW1 (S43-01) On Off / On
S4302-EN Function activation in SOFTSW2 (S43-02) On Off / On
S4303-EN Function activation in SOFTSW3 (S43-03) On Off / On
…. …. … ….
S4361-EN Function activation in SOFTSW61 (S43-61) On Off / On
CBK-CTRAHMI HMI activation in CBK On Off / On
ICB-CTRAHMI HMI activation in ICB On Off / On
SCB-CTRAHMI HMI activation in SCB On Off / On
S4301-CTRAHMI HMI activation in SOFTSW1 (S43-01) On Off / On
S4302-CTRAHMI HMI activation in SOFTSW2 (S43-02) On Off / On
S4303-CTRAHMI HMI activation in SOFTSW3 (S43-03) On Off / On
…. …. … …
S4361-CTRAHMI HMI activation in SOFTSW61 (S43-61) On Off / On

GRL200 (Soft 033 & 037)


- 742 -
6F2S1914 (0.37)

4.3.3 Cancel logic for SBO mode


In the SBO control mode, the reception of a cancel command is possible; when the cancel
conditions are satisfied, accordingly, the function can discard the select command.

(i) Receiving “Cancel” from remote-end


Figure 4.3-13 shows the logic when a “Cancel command (Remote-Cancel)” signal is applied to
the SOFTSW1 function. The input-point “S4301_CONTROL_REQ” is the same as the
“Selection command (Remote-On-Control)”510001
signal.
7001016D08

Input Cancel logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)


Command “Remote-cancel”
Cancel command
522001 700A046D08 S4301_CONTROL_REQ
Successes to cancel
&

Operation Failed
Unmatched condition &
detected†

Figure 4.3-13 Cancel logic by the reception of the command from the remote end
†Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”.

(ii) Receiving “Cancel” from local-end


Figure 4.3-14 shows the logic when a “Cancel command (Local-cancel)” signal is applied to the
SOFTSW1 function. The input signal is provided when the “Cancel” key is pressed on the IED
front panel; the user is not required to map it. When the logic receives input “Local-cancel”
signal, the logic is able to output a result signal, provided that the “unmatched condition
detected” checking is satisfied.
510001 7001016D08

Input Cancel logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)

Cancel command
Command “Local-cancel”
Successes to cancel
&

Unmatched condition
& Operation Failed
detected†

Figure 4.3-14 Cancel logic by the reception of the command at local end
†Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”.

4.3.4 Operate logic for SBO/DIR modes


The user should map the operation command to the operate logic. If the operation conditions
are satisfied, the IED is able to change the state in the S4301 to S4308.

GRL200 (Soft 033 & 037)


- 743 -
6F2S1914 (0.37)

(i) Receiving “operate command On” from remote-end


Figure 4.3-15 shows the logic when an “Operate command (Remote-ON-Control)” signal is
applied to the SOFTSW1 logic. The input-point “S4301_CONTROL_REQ” is used for the
reception of the “Select command (Remote-On-Control)”.

Input Operate logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)

“S4301_OEC_CHG”
Command “Remote-On-Control” (522001_890A041F5A)

522001 700A046D08 S4301_CONTROL_REQ Operate Command


& OFF to ON

Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)

522001_810A041D03 Operate completed


S4301_ST_ON &

0 t
Operate failed
& d
1.0s

Figure 4.3-15 ‘ON’ Operation logic by remote end in SOFTSW1†


†Note: To identify the input and output signal-points of the other SOFTSW logics, see
Table 4.3-6, Table 4.3-8, Table 4.3-11, Table 4.3-14, and Table 4.3-15.
‡Note:“operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note:The ASEQ function can provide sequential signals for automatic control.

(ii) Receiving “operate command Off” from remote-end


Figure 4.3-16 shows the logic when an “Operate command (Remote-Off-Control)” signal is
applied to the SOFTSW1 logic. The input-point “S4301_CONTROL_REQ” is used for the
reception of the signal “Operate command (Remote-Off-Control)”.

Input Operate logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)

“S4301_FEC_CHG”
Command “Remote-OFF-Control” (522001_8A0A041F5B)

522001 700A046D08 S4301_CONTROL_REQ Operate Command


& ON to OFF

Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)

522001_830A041D02 Operate completed


S4301_ST_OFF &

0 t
Operate failed
& d
1.0s

Figure 4.3-16 ‘OFF’ Operation logic by remote end in SOFTSW1†


†Note: To identify the input and output signals of the other SOFTSW logics, see Table
4.3-6, Table 4.3-12, Table 4.3-13, and Table 4.3-14.
‡Note:“operate condition” signal is provided from operate condition scheme. For more

GRL200 (Soft 033 & 037)


- 744 -
6F2S1914 (0.37)

information, see Figure 4.3-21.


§Note: The ASEQ function can provide sequential signals for automatic control.

(iii) Receiving “operate command On” from the local end


Figure 4.3-17 shows the logic when an “Operate command (Local-ON-Control)” signal is
applied to the SOFTSW1 logic. The input signal is provided when “Execution of On” key is
pressed on the IED front panel.

Input Operate logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)

“S4301_OEC_CHG”
(522001_890A041F5A)
Operate Command
Command “Local-On-Control”
& OFF to ON

Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)

522001_810A041D03 Operate completed


S4301_ST_ON &

0 t
Operate failed
& d
1.0s

Figure 4.3-17 ‘ON’ Operation logic at local in SOFTSW1†


†Note: To identify the input and output signal-points of the other SOFTSW logics, see
Table 4.3-11, Table 4.3-13, and Table 4.3-15.
‡Note:“operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note:The ASEQ function can provide sequential signals for automatic control.

(iv) Receiving “operate command Off” from the local end


Figure 4.3-18 shows the logic when an “Operation command (Local-OFF-Control)” signal is
applied to the SOFTSW1 logic. The input signal is provided when “Execution for Off” key is
pressed on the IED front panel.

Input Operate logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)

“S4301_FEC_CHG”
(522001_8A0A041F5B)

Command “Local-Off-Control” Operate Command


& ON to OFF

Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)

522001_830A041D02 Operate completed


S4301_ST_OFF &

0 t
Operate failed
& d
1.0s

Figure 4.3-18 ‘OFF’ Operation logic at local in SOFTSW1†

GRL200 (Soft 033 & 037)


- 745 -
6F2S1914 (0.37)

†Note: To identify the input and output signals of the other SOFTSW logics, see Table
4.3-12, Table 4.3-13, and Table 4.3-14.
‡Note: “operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.

(v) Receiving “operate command On” using PLC logic


Figure 4.3-19 shows the logic when an “Operate command (PLC-ON-Control)” signal is applied
to the SOFTSW1 logic. The input signal is generated using the user-programmed PLC logic;
the user can connect the signal for the PLC connection point “S4301_CHG_TO_ON”.
Input Operate logic in SOFTSW1 Output

SOTFSW1 function (Function ID: 522001)

ON-control command “S4301_OEC_CHG_PLC”


(PLC connection point #1) (522001_8C0A041F5D)

522001 850A04EDE1 S4301_CHG_TO_ON Operate Command


& OFF to ON

Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL
“S4301_EX_SS”
(522001_870A041F62)
522001_810A041D03 Operate completed
S4301_ST_ON &
“S4301_PLC_CTRL_FAIL”
(522001_870A041F62)
0 t Operate failed
& d
1.0s

Figure 4.3-19 ‘ON’ Operation logic using PLC logic†


†Note: To identify the input and output signal-points of the other SOFTSW logics, see
Table 4.3-3, Table 4.3-13, Table 4.3-15, Table 4.3-16, and Table 4.3-17.
‡Note:“operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note:The ASEQ function can provide sequential signals for automatic control.

(vi) Receiving “operate command Off” using PLC logic


Figure 4.3-20 shows the logic when an “Operation command (PLC-Off-Control)” signal is
applied to the SOFTSW1 logic. The input signal is generated using the user-programmed PLC
logic; the user can connect the signal for the PLC connection point “S4301_CHG_TO_OFF”.

GRL200 (Soft 033 & 037)


- 746 -
6F2S1914 (0.37)

Input Operate logic in SOFTSW1 Output

SOFTSW1 function (Function ID: 522001)

ON-control command “S4301_FEC_CHG_PLC”


(PLC connection point #2) (522001_8C0A041F5D)

522001 860A04EDE0 S4301_CHG_TO_OFF Operate Command


& ON to OFF

Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL
“S4301_EX_SS”
(522001_870A041F62)
522001_830A041D02 Operate completed
S4301_ST_OFF &
“S4301_PLC_CTRL_FAIL”
(522001_870A041F62)
0 t Operate failed
& d
1.0s

Figure 4.3-20 ‘Off’ Operation logic using PLC logic†


†Note: To identify the input and output signal-points of the other SOFTSW logics, see
Table 4.3-4, Table 4.3-13, Table 4.3-14, Table 4.3-16, and Table 4.3-18.
‡Note:“operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note:The ASEQ function can provide sequential signals for automatic control.

(vii) Operate condition


Figure 4.3-21 shows the operate condition logic of the SOFTSW1 function. The SOFTSW1
function can examine an operate-condition using “Command Blocking” signal1.

SOFTSW1 function (Function ID: 522001)


Command blocking*1 (defined as ”CBK”)
To operate logic
CBK_STATE
1≥ operate condition
&
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR

Function “Automatic sequence control” is in progress


Unmatched condition detected *5
ASEQ_MULTI_SEL

Tripping *4 (“General trip”)


GEN.TRIP

Command “ON control” received &


Command “OFF control” received &
received
S4301_STATE
(522001 000A041001)
Same Directional
Controlling Event

Users must setup this condition correctly


Control hierarchy (e.g. 43RL) (PLC connection point #3)*6
522001 820A04ED50 S4301_CTRL_RIGHT
&
IED serious error detected
SERI_ERR

[S4301-EN]

On

Figure 4.3-21 Operate condition logic for ON/OFF in SOFTSW1*7


1Note: “Command Blocking” disables any operation except for itself; See the signal
“S4301_STATE (Table 4.3-2)” as the state of “Command Blocking” in the SOFTSW
function.

GRL200 (Soft 033 & 037)


- 747 -
6F2S1914 (0.37)

2Note: “Double Command Blocking (DCB_RCV_OR in Table 4.3-8)” is an operation


philosophy. It can be used to protect the substation. The user can configure it
using GR-TIEMS.
3Note: Detection of event “device-travelling (Traveling OR in Table 4.3-8)” signifies that
other operators are changing the status of one or more devices. Thus, device
operation by the IED should be inhibited whilst the event is detected.
4Note: If an IED is in the process of issuing a trip (GEN.TRIP in Table 4.3-8) command,
all control operation is blocked until the trip operation has been completed.
Tripping can be introduced by the protection function if the IED has protection
functions.
5Note: The criteria “unmatched conditions” is determined when the “Test-bit status” in a
command is not identical to the “IED test status”.
6Note: The user must program the PLC logic “Control hierarchy condition”. The Control
hierarchy condition provided by the user-programmed PLC logic may be 43R/L;
the user can connect it with PLC connection point “S4301_CTRL_RIGHT” of
Figure 4.3-21.
7Note: To identify the PLC connection points of the other SOFTSW logics, see Table 4.3-5.

(viii) Signal name and number


Note: The user should note the meaning of the following abbreviations as shown in
column “M/O” of each table:
“O” indicates that the signal is provided for the optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings is used.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.3-11 Output signals on starting operation “Off to On”
Signal Number Signal Name Description
522001 890A011F5A CBK_OEC_CHG “Off to On” operation start in CBK
522001 890A021F5A ICB_OEC_CHG “Off to On” operation start in ICB
522001 890A031F5A SCB_OEC_CHG “Off to On” operation start in SCB
522001 890A041F5A S4301_OEC_CHG “Off to On” operation start in SOFTSW1 (S43-01)
522001 890A051F5A S4302_OEC_CHG “Off to On” operation start in SOFTSW2 (S43-02)
522001 890A061F5A S4303_OEC_CHG “Off to On” operation start in SOFTSW3 (S43-03)
… …. ….
522001 890A401F5A S4361_OEC_CHG “Off to On” operation start in SOFTSW61 (S43-61)

Table 4.3-12 Output signals on starting operation “On to Off”


Signal Number Signal Name Description
522001 8A0A011F5B CBK_FEC_CHG “On to Off” operation start in CBK
522001 8A0A021F5B ICB_FEC_CHG “On to Off” operation start in ICB
522001 8A0A031F5B SCB_FEC_CHG “On to Off” operation start in SCB
522001 8A0A041F5B S4301_FEC_CHG “On to Off” operation start in SOFTSW1 (S43-01)
522001 8A0A051F5B S4302_FEC_CHG “On to Off” operation start in SOFTSW2 (S43-02)

GRL200 (Soft 033 & 037)


- 748 -
6F2S1914 (0.37)

Signal Number Signal Name Description


522001 8A0A061F5B S4303_FEC_CHG “On to Off” operation start in SOFTSW3 (S43-03)
… … …
522001 8C0A401F5D S4361_FEC_CHG “On to Off” operation start in SOFTSW61 (S43-61)

Table 4.3-13 Success signals of the operation


Signal Number Signal Name Description
522001 870A011F62 CBK_EX_SS Operation succeeded in CBK
522001 870A021F62 ICB_EX_SS Operation succeeded in ICB
522001 870A031F62 SCB_EX_SS Operation succeeded in SCB
522001 870A041F62 S4301_EX_SS Operation succeeded in SOFTSW1 (S43-01)
522001 870A051F62 S4302_EX_SS Operation succeeded in SOFTSW2 (S43-02)
522001 870A061F62 S4303_EX_SS Operation succeeded in SOFTSW3 (S43-03)
… … …
522001 870A401F62 S4361_EX_SS Operation succeeded in SOFTSW61 (S43-61)

Table 4.3-14 OFF status signals on the operation


Signal Number Signal Name Description
522001 830A011D02 CBK_ST_OFF “Off” status of CBK
522001 830A021D02 ICB_OFF “Off” status of ICB
522001 830A031D02 SCB_ST_OFF “Off” status of SCB
522001 830A041D02 S4301_ST_OFF “Off” status of SOFTSW1 (S43-01)
522001 830A051D02 S4302_ST_OFF “Off” status of SOFTSW2 (S43-02)
522001 830A061D02 S4303_ST_OFF “Off” status of SOFTSW3 (S43-03)
… … …
522001 830A401D02 S4361_ST_OFF “Off” status of SOFTSW61 (S43-61)

Table 4.3-15 ON status signals on the operation


Signal Number Signal Name Description
522001 810A011D03 CBK_ST_ON “On” status of CBK
522001 810A021D03 ICB_ST_ON “On” status of ICB
522001 810A031D03 SCB_ST_ON “On” status of SCB
522001 810A041D03 S4301_ST_ON “On” status of SOFTSW1 (S43-01)
522001 810A051D03 S4302_ST_ON “On” status of SOFTSW2 (S43-02)
522001 810A061D03 S4303_ST_ON “On” status of SOFTSW3 (S43-03)
… … …
522001 810A401D03 S4361_ST_ON “On” status of SOFTSW61 (S43-61)

Table 4.3-16 Failure signals generated by PLC control


Signal Number Signal Name Description
522001 800A011DE0 CBK_PLC_CTRL_FAIL Control failure in CBK
522001 800A021DE0 ICB_PLC_CTRL_FAIL Control failure in ICB
522001 800A031DE0 SCB_PLC_CTRL_FAIL Control failure in SCB
522001 800A041DE0 S4301_PLC_CTRL_FAIL Control failure in SOFTSW1 (S43-01)
522001 800A051DE0 S4302_PLC_CTRL_FAIL Control failure in SOFTSW2 (S43-02)
522001 800A061DE0 S4303_PLC_CTRL_FAIL Control failure in SOFTSW3 (S43-03)
… … …
522001 800A401DE0 S4361_PLC_CTRL_FAIL Control failure in SOFTSW61 (S43-61)

GRL200 (Soft 033 & 037)


- 749 -
6F2S1914 (0.37)

Table 4.3-17 Output signals on starting operation “Off to On” by PLC


Signal Number Signal Name Description
522001 8B0A011F5C CBK_OEC_CHG_PLC CBK signal after KC_S43_SA022
522001 8B0A021F5C ICB_OEC_CHG_PLC ICB signal after KC_S43_SA022
522001 8B0A031F5C SCB_OEC_CHG_PLC SCB signal after KC_S43_SA022
522001 8B0A041F5C S4301_OEC_CHG_PLC SOFTSW1 signal after KC_S43_SA022
522001 8B0A051F6C S4302_OEC_CHG_PLC SOFTSW2 signal after KC_S43_SA022
522001 8B0A061F7C S4303_OEC_CHG_PLC SOFTSW3 signal after KC_S43_SA022
… … …
522001 8B0A401F9C S4361_OEC_CHG_PLC SOFTSW61 signal after KC_S43_SA022

Table 4.3-18 Output signals on starting operation “On to Off” by PLC


Signal Number Signal Name Description
522001 8C0A011F5D CBK_FEC_CHG_PLC CBK signal after KC_S43_SA023
522001 8C0A021F5D ICB_FEC_CHG_PLC ICB signal after KC_S43_SA023
522001 8C0A031F5D SCB_FEC_CHG_PLC SCB signal after KC_S43_SA023
522001 8C0A041F5D S4301_FEC_CHG_PLC SOFTSW1 signal after KC_S43_SA023
522001 8C0A051F5D S4302_FEC_CHG_PLC SOFTSW2 signal after KC_S43_SA023
522001 8C0A061F5D S4303_FEC_CHG_PLC SOFTSW3 signal after KC_S43_SA023
… … …
522001 8C0A401F5D S4361_FEC_CHG_PLC SOFTSW61 signal after KC_S43_SA023

GRL200 (Soft 033 & 037)


- 750 -
6F2S1914 (0.37)

4.3.5 Mapping for IEC 61850 communication


The user can operate the SOFTSW1 function over IEC 61850 communications following
mapping using GR-TIEMS. Note that the SOFTSW1 function is designed for the class of
“Single Point Controller (SPC)” in the IEC 61850 standard for communication. The user should
follow these steps, each of which is discussed below:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user will need to create a logical node (LN) for the SOFTSW1 function. Figure 4.3-22
exemplifies the editing of a LN; the LN “General Input/Output (GGIO)” is chosen for the
SOFTSW1 function for IEC 61850 communication. After the user has defined an object
“SPCSO”, the SOFTSW1 logical node can be saved with the name “GGIO” plus “LN Instance”.
Create a definition of the object “SPCSO” in SOFTSW1 logical node. Either the SBO mode or
the DIR mode can be chosen in the editing for the LN.

SBO defined in LN

Figure 4.3-22 Defining “SPCSO” object in GGIO701 logic node

Defining SBO mode


Figure 4.3-23 exemplifies the settings in LN “GGIO701” when the SBO mode is required for
the SOFTSW1 function. In the SBO control, the user should select the following items for the
“GGIO701$SPCSO” using GR-TIEMS;

GRL200 (Soft 033 & 037)


- 751 -
6F2S1914 (0.37)

 SBOw
 Oper
 Cancel
 Origin
 stSeld
 sboClass (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns” )

Figure 4.3-23 LN editing screen for SBO mode (for example)

Defining DIR mode


Figure 4.3-24 exemplifies the settings in LN “GGIO701” when the DIR mode is required for
the SOFTSW1 function. In the DIR mode, the following three items should be selected using
GR-TIEMS:

 Oper
 origin
 ctlmodel (choice ”DOes or DOns” )

Figure 4.3-24 LN editing screen for DIR mode (for example)

(ii) Mapping output data


The user should group the SOFTSW1 (S4301) signals with regard to GOOSE and REPORT;
the user should map them for IEC 61850 communication using GR-TIEMS.

GRL200 (Soft 033 & 037)


- 752 -
6F2S1914 (0.37)

Table 4.3-19 shows the required mapping signals in SOFTSW1 function to the IEC 61850
communications. Figure 4.3-25 shows how to map a signal.

Table 4.3-19 Mapping signals for SPCSO object.


Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO701$SPCSO$origin orCat orCategory ST 522001 310A041008 S4301_ORCAT
Ctrl/GGIO701$SPCSO$origin orIdent Octet64 ST 522001 6A0A041009 S4301_ORIDENT
Ctrl/GGIO701$SPCSO stVal INT32 ST 522001 000A041001 S4301_STATE
Ctrl/GGIO701$SPCSO q Quality ST 522001 310A041005 S4301_QUALITY
Ctrl/GGIO701$SPCSO t Timestamp ST 522001 900A041006 S4301_TIME
Ctrl/GGIO701$SPCSO stSeld BOOLEAN ST 522001 000A041D90 S4301_STSELD

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.

Figure 4.3-25 orCat attribute mapped into SPCSO object of GGIO701

(iii) Mapping input data


The SOFTSW1 function can receive three commands “select, operate, and cancel. Thus, the
user should map the input-point “S4301_CONTROL_REQ”. Table 4.3-20 shows the input-point
“S4301_CONTROL_REQ” and the Object reference “Ctrl/GGIO701$SPCSO”; the user should map
the Object reference having attributes CO and CF in FC† to the input-point. Figure 4.3-26 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).

GRL200 (Soft 033 & 037)


- 753 -
6F2S1914 (0.37)

Table 4.3-20 Mapping signals required for SPCSO object in SOFTSW1 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO701$SPCSO$SBOw ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$SBOw T Timestamp CO
Ctrl/GGIO701$SPCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO701$SPCSO$SBOw Check Check CO
Ctrl/GGIO701$SPCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO$Oper ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$Oper ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$Oper T Timestamp CO
Ctrl/GGIO701$SPCSO$Oper Test BOOLEAN CO
522001 700A046D08 S4301_CONTROL_REQ
Ctrl/GGIO701$SPCSO$Oper Check Check CO
Ctrl/GGIO701$SPCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO$Cancel ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$Cancel T Timestamp CO
Ctrl/GGIO701$SPCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO701$SPCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO ctlModel ctlModel CF
Ctrl/GGIO701$SPCSO sboClass sboClass CF

Drag and drop

Check “Input”

Figure 4.3-26 Input-point mapped for GGIO701

GRL200 (Soft 033 & 037)


- 754 -
6F2S1914 (0.37)

4.3.6 Setting
SOTFSW(FunctionID:522001)
Setting items Range Unit Contents Default Note

CBK-EN Off / On - control command block switch Enable Off


ICB-EN Off / On - Interlock check bypass in controlled on LCD Off
SCB-EN Off / On - Synchro check bypass in controlled on LCD Off
S4301-EN Off / On - Soft 43 switch1 Enable Off
S4302-EN Off / On - Soft 43 switch2 Enable Off
S4303-EN Off / On - Soft 43 switch3 Enable Off
… …. …. ….
S4360-EN Off / On - Soft 43 switch60 Enable Off
S4361-EN Off / On - Soft 43 switch61 Enable Off
CBK CBK-NAME [Preferred text] - item name of control command block signal CMDBLK !
CBK-OFFNAME [Preferred text] - state name of state(off) Off !
CBK-ONNAME [Preferred text] - state name of state(on) Blocked !
CBK-CTRMENU Off / On - control by MENU enable Off
CBK-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
ICB ICB-NAME [Preferred text] - item name of interlock bypass signal ILKBYP !
ICB-OFFNAME [Preferred text] - state name of state(off) Off !
ICB-ONNAME [Preferred text] - state name of state(on) Bypass !
ICB-CTRMENU Off / On - control by MENU enable Off
ICB-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
SCB SCB-NAME [Preferred text] - item name of interlock bypass signal SYNCBYP !
SCB-OFFNAME [Preferred text] - state name of state(off) Off !
SCB-ONNAME [Preferred text] - state name of state(on) Bypass !
SCB-CTRMENU Off / On - control by MENU enable Off
SCB-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
S43 SW1 S4301-SWNAME [Preferred text] - item name of soft 43 switch signal SOFTSW1 !
S4301-OFFNAME [Preferred text] - state name of state(off) Off !
S4301-ONNAME [Preferred text] - state name of state(on) On !
S4301-CTRMENU Off / On - control by MENU enable Off
S4301-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
SW2 S4302-SWNAME [Preferred text] - item name of soft 43 switch signal SOFTSW2 !
S4302-OFFNAME [Preferred text] - state name of state(off) Off !
S4302-ONNAME [Preferred text] - state name of state(on) On !
S4302-CTRMENU Off / On - control by MENU enable Off
S4302-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
SW3 S4303-SWNAME [Preferred text] - item name of soft 43 switch signal SOFTSW3 !
S4303-OFFNAME [Preferred text] - state name of state(off) Off !
S4303-ONNAME [Preferred text] - state name of state(on) On !
S4303-CTRMENU Off / On - control by MENU enable Off
S4303-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
… … …. ….
SW60 S4360-SWNAME [Preferred text] - item name of soft 43 switch signal SOFTSW60 !
S4360-OFFNAME [Preferred text] - state name of state(off) Off !
S4360-ONNAME [Preferred text] - state name of state(on) On !
S4360-CTRMENU Off / On - control by MENU enable Off
S4360-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
SW61 S4361-SWNAME [Preferred text] - item name of soft 43 switch signal SOFTSW61 !
S4361-OFFNAME [Preferred text] - state name of state(off) Off !
S4361-ONNAME [Preferred text] - state name of state(on) On !
S4361-CTRMENU Off / On - control by MENU enable Off
S4361-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
!Note: The user can enter a preferred setting name using GR-TIEMS.

GRL200 (Soft 033 & 037)


- 755 -
6F2S1914 (0.37)

4.3.7 Signal
 Signal monitoring points
SOFTSW(Function ID:522001)
Element ID Name Description
000A011001 CBK_STATE CMDBLK status

000A011D90 CBK_STSELD CMDBLK the controllable data is in the status

310A011D00 CBK_STS_MIMIC CMDBLK status

310A011D01 CBK_STS CMDBLK status

800A011D51 CBK_SC_OWS CMDBLK select command by OWS(HMI)

800A011D52 CBK_SC_RCC CMDBLK select command by RCC

800A011D53 CBK_SC CMDBLK select command

800A011D54 CBK_SC_LCD CMDBLK select command by LCD

800A011D55 CBK_EC_OWS CMDBLK execute command by OWS(HMI)

800A011D56 CBK_EC_RCC CMDBLK execute command by RCC

800A011D57 CBK_EC CMDBLK execute command

800A011D58 CBK_EC_LCD CMDBLK execute command by LCD

800A011DE0 CBK_PLC_CTRL_FAIL CMDBLK PLC control fail

800A011F42 CBK_TMP2 CMDBLK signal before KC_S43_SA002

810A011D03 CBK_ST_ON CMDBLK On state

810A011F44 CBK_TMP4 CMDBLK signal before KC_S43_SA003

820A011F40 CBK_TMP1 CMDBLK signal before KC_S43_SA001

830A011D02 CBK_ST_OFF CMDBLK Off state

830A011F41 CBK_NSD_CSF CMDBLK signal after KC_S43_SA001

850A011F46 CBK_TMP5 CMDBLK signal before KC_S43_SA004

850A011F48 CBK_TMP7 CMDBLK signal before KC_S43_SA005

850A011F4A CBK_TMP8 CMDBLK signal before KC_S43_SA006

850A011F5E CBK_TMP11 CMDBLK signal before KC_S43_SA013

860A011F43 CBK_TMP3 CMDBLK signal after KC_S43_SA002

860A011F4E CBK_SLF_FCT_FLG01 CMDBLK signal before MCTS43_SC001

870A011F50 CBK_SLF_FCT_FLG02 CMDBLK signal before MCTS43_SC002

870A011F60 CBK_TMP13 CMDBLK signal before KC_S43_SA014

870A011F62 CBK_EX_SS CMDBLK signal execute success

880A011F4B CBK_TMP9 CMDBLK signal after KC_S43_SA006

880A011F4D CBK_TMP10 CMDBLK signal after KC_S43_SC001

880A011F5F CBK_TMP12 CMDBLK signal after KC_S43_SA013

890A011F5A CBK_OEC_CHG CMDBLK signal after KC_S43_SA011

890A011F61 CBK_TMP14 CMDBLK signal after KC_S43_SA014

8A0A011F47 CBK_TMP6 CMDBLK signal after KC_S43_SA004

8A0A011F5B CBK_FEC_CHG CMDBLK signal after KC_S43_SA012

8B0A011F4C CBK_CTR_SGU CMDBLK signal before KC_S43_SC001

8B0A011F5C CBK_OEC_CHG_PLC CMDBLK signal after KC_S43_SA022

8C0A011F5D CBK_FEC_CHG_PLC CMDBLK signal after KC_S43_SA023

8D0A011F45 CBK_FSD_CSF CMDBLK signal after KC_S43_SA003

8E0A011F4F CBK_SLD_TM0 CMDBLK signal after MCTS43_SC001

8F0A011F49 CBK_OSD_CSF CMDBLK signal after KC_S43_SA005

8F0A011F51 CBK_EX_CMP_TM0 CMDBLK signal after MCTS43_SC002

000A021001 ICB_STATE ILKBYP status

000A021D90 ICB_STSELD ILKBYP the controllable data is in the status

GRL200 (Soft 033 & 037)


- 756 -
6F2S1914 (0.37)

 Signal monitoring points


SOFTSW(Function ID:522001)
Element ID Name Description
310A021D00 ICB_STS_MIMIC ILKBYP status

310A021D01 ICB_STS ILKBYP status

800A021D51 ICB_SC_OWS ILKBYP select command by OWS(HMI)

800A021D52 ICB_SC_RCC ILKBYP select command by RCC

800A021D53 ICB_SC ILKBYP select command

800A021D54 ICB_SC_LCD ILKBYP select command by LCD

800A021D55 ICB_EC_OWS ILKBYP execute command by OWS(HMI)

800A021D56 ICB_EC_RCC ILKBYP execute command by RCC

800A021D57 ICB_EC ILKBYP execute command

800A021D58 ICB_EC_LCD ILKBYP execute command by LCD

800A021DE0 ICB_PLC_CTRL_FAIL ILKBYP PLC control fail

800A021F42 ICB_TMP2 ILKBYP signal before KC_S43_SA002

800A021F63 ICB_FLG1 ILKBYP signal after KC_S43_SA015

810A021D03 ICB_ST_ON ILKBYP On state

810A021F44 ICB_TMP4 ILKBYP signal before KC_S43_SA003

820A021F40 ICB_TMP1 ILKBYP signal before KC_S43_SA001

830A021D02 ICB_ST_OFF ILKBYP Off state

830A021F41 ICB_NSD_CSF ILKBYP signal after KC_S43_SA001

840A021F65 ICB_RST ILKBYP signal after KC_S43_SA017

850A021F46 ICB_TMP5 ILKBYP signal before KC_S43_SA004

850A021F48 ICB_TMP7 ILKBYP signal before KC_S43_SA005

850A021F4A ICB_TMP8 ILKBYP signal before KC_S43_SA006

850A021F5E ICB_TMP11 ILKBYP signal before KC_S43_SA013

860A021F43 ICB_TMP3 ILKBYP signal after KC_S43_SA002

860A021F4E ICB_SLF_FCT_FLG01 ILKBYP signal before MCTS43_SC001

870A021F50 ICB_SLF_FCT_FLG02 ILKBYP signal before MCTS43_SC002

870A021F60 ICB_TMP13 ILKBYP signal before KC_S43_SA014

870A021F62 ICB_EX_SS ILKBYP signal execute success

870A021F64 ICB_FLG2 ILKBYP signal after KC_S43_SA016

880A021F4B ICB_TMP9 ILKBYP signal after KC_S43_SA006

880A021F4D ICB_TMP10 ILKBYP signal after KC_S43_SC001

880A021F5F ICB_TMP12 ILKBYP signal after KC_S43_SA013

890A021F5A ICB_OEC_CHG ILKBYP signal after KC_S43_SA011

890A021F61 ICB_TMP14 ILKBYP signal after KC_S43_SA014

8A0A021F47 ICB_TMP6 ILKBYP signal after KC_S43_SA004

8A0A021F5B ICB_FEC_CHG ILKBYP signal after KC_S43_SA012

8B0A021F4C ICB_CTR_SGU ILKBYP signal before KC_S43_SC001

8B0A021F5C ICB_OEC_CHG_PLC ILKBYP signal after KC_S43_SA022

8C0A021F5D ICB_FEC_CHG_PLC ILKBYP signal after KC_S43_SA023

8D0A021F45 ICB_FSD_CSF ILKBYP signal after KC_S43_SA003

8E0A021F4F ICB_SLD_TM0 ILKBYP signal after MCTS43_SC001

8F0A021F49 ICB_OSD_CSF ILKBYP signal after KC_S43_SA005

8F0A021F51 ICB_EX_CMP_TM0 ILKBYP signal after MCTS43_SC002

8B0A031F4C SCB_CTR_SGU SYNCBYP signal before KC_S43_SC001

800A031D57 SCB_EC SYNCBYP execute command

GRL200 (Soft 033 & 037)


- 757 -
6F2S1914 (0.37)

 Signal monitoring points


SOFTSW(Function ID:522001)
Element ID Name Description
800A031D58 SCB_EC_LCD SYNCBYP execute command by LCD

800A031D55 SCB_EC_OWS SYNCBYP execute command by OWS(HMI)

800A031D56 SCB_EC_RCC SYNCBYP execute command by RCC

8F0A031F51 SCB_EX_CMP_TM0 SYNCBYP signal after MCTS43_SC002

870A031F62 SCB_EX_SS SYNCBYP signal execute success

8A0A031F5B SCB_FEC_CHG SYNCBYP signal after KC_S43_SA012

8C0A031F5D SCB_FEC_CHG_PLC SYNCBYP signal after KC_S43_SA023

810A031F63 SCB_FLG1 SYNCBYP signal after KC_S43_SA018

880A031F64 SCB_FLG2 SYNCBYP signal after KC_S43_SA019

8D0A031F45 SCB_FSD_CSF SYNCBYP signal after KC_S43_SA003

830A031F41 SCB_NSD_CSF SYNCBYP signal after KC_S43_SA001

890A031F5A SCB_OEC_CHG SYNCBYP signal after KC_S43_SA011

8B0A031F5C SCB_OEC_CHG_PLC SYNCBYP signal after KC_S43_SA022

8F0A031F49 SCB_OSD_CSF SYNCBYP signal after KC_S43_SA005

800A031DE0 SCB_PLC_CTRL_FAIL SYNCBYP PLC control fail

850A031F65 SCB_RST SYNCBYP signal after KC_S43_SA020

800A031D53 SCB_SC SYNCBYP select command

800A031D54 SCB_SC_LCD SYNCBYP select command by LCD

800A031D51 SCB_SC_OWS SYNCBYP select command by OWS(HMI)

800A031D52 SCB_SC_RCC SYNCBYP select command by RCC

8E0A031F4F SCB_SLD_TM0 SYNCBYP signal after MCTS43_SC001

860A031F4E SCB_SLF_FCT_FLG01 SYNCBYP signal before MCTS43_SC001

870A031F50 SCB_SLF_FCT_FLG02 SYNCBYP signal before MCTS43_SC002

000A031001 SCB_STATE SYNCBYP status

310A031D01 SCB_STS SYNCBYP status

000A031D90 SCB_STSELD SYNCBYP the controllable data is in the status

310A031D00 SCB_STS_MIMIC SYNCBYP status

830A031D02 SCB_ST_OFF SYNCBYP Off state

810A031D03 SCB_ST_ON SYNCBYP On state

820A031F40 SCB_TMP1 SYNCBYP signal before KC_S43_SA001

880A031F4D SCB_TMP10 SYNCBYP signal after KC_S43_SC001

850A031F5E SCB_TMP11 SYNCBYP signal before KC_S43_SA013

880A031F5F SCB_TMP12 SYNCBYP signal after KC_S43_SA013

870A031F60 SCB_TMP13 SYNCBYP signal before KC_S43_SA014

890A031F61 SCB_TMP14 SYNCBYP signal after KC_S43_SA014

800A031F42 SCB_TMP2 SYNCBYP signal before KC_S43_SA002

860A031F43 SCB_TMP3 SYNCBYP signal after KC_S43_SA002

810A031F44 SCB_TMP4 SYNCBYP signal before KC_S43_SA003

850A031F46 SCB_TMP5 SYNCBYP signal before KC_S43_SA004

8A0A031F47 SCB_TMP6 SYNCBYP signal after KC_S43_SA004

850A031F48 SCB_TMP7 SYNCBYP signal before KC_S43_SA005

850A031F4A SCB_TMP8 SYNCBYP signal before KC_S43_SA006

880A031F4B SCB_TMP9 SYNCBYP signal after KC_S43_SA006

000A041001 S4301_STATE SOFT 43 switch1 status

000A041D90 S4301_STSELD SOFT 43 switch1 the controllable data is in the status

GRL200 (Soft 033 & 037)


- 758 -
6F2S1914 (0.37)

 Signal monitoring points


SOFTSW(Function ID:522001)
Element ID Name Description
310A041D00 S4301_STS_MIMIC SOFT 43 switch1 status

310A041D01 S4301_STS SOFT 43 switch1 status

800A041D51 S4301_SC_OWS SOFT 43 switch1 select command by OWS(HMI)

800A041D52 S4301_SC_RCC SOFT 43 switch1 select command by RCC

800A041D53 S4301_SC SOFT 43 switch1 select command

800A041D54 S4301_SC_LCD SOFT 43 switch1 select command by LCD

800A041D55 S4301_EC_OWS SOFT 43 switch1 execute command by OWS(HMI)

800A041D56 S4301_EC_RCC SOFT 43 switch1 execute command by RCC

800A041D57 S4301_EC SOFT 43 switch1 execute command

800A041D58 S4301_EC_LCD SOFT 43 switch1 execute command by LCD

800A041DE0 S4301_PLC_CTRL_FAIL SOFT 43 switch1 PLC control fail

800A041F42 S4301_TMP2 SOFT 43 switch1 signal before KC_S43_SA002

810A041D03 S4301_ST_ON SOFT 43 switch1 On state

810A041F44 S4301_TMP4 SOFT 43 switch1 signal before KC_S43_SA003

820A041F40 S4301_TMP1 SOFT 43 switch1 signal before KC_S43_SA001

830A041D02 S4301_ST_OFF SOFT 43 switch1 Off state

830A041F41 S4301_NSD_CSF SOFT 43 switch1 signal after KC_S43_SA001

850A041F46 S4301_TMP5 SOFT 43 switch1 signal before KC_S43_SA004

850A041F48 S4301_TMP7 SOFT 43 switch1 signal before KC_S43_SA005

850A041F4A S4301_TMP8 SOFT 43 switch1 signal before KC_S43_SA006

850A041F5E S4301_TMP11 SOFT 43 switch1 signal before KC_S43_SA013

860A041F43 S4301_TMP3 SOFT 43 switch1 signal after KC_S43_SA002

860A041F4E S4301_SLF_FCT_FLG01 SOFT 43 switch1 signal before MCTS43_SC001

870A041F50 S4301_SLF_FCT_FLG02 SOFT 43 switch1 signal before MCTS43_SC002

870A041F60 S4301_TMP13 SOFT 43 switch1 signal before KC_S43_SA014

870A041F62 S4301_EX_SS SOFT 43 switch1 signal execute success

880A041F4B S4301_TMP9 SOFT 43 switch1 signal after KC_S43_SA006

880A041F4D S4301_TMP10 SOFT 43 switch1 signal after KC_S43_SC001

880A041F5F S4301_TMP12 SOFT 43 switch1 signal after KC_S43_SA013

890A041F5A S4301_OEC_CHG SOFT 43 switch1 signal after KC_S43_SA011

890A041F61 S4301_TMP14 SOFT 43 switch1 signal after KC_S43_SA014

8A0A041F47 S4301_TMP6 SOFT 43 switch1 signal after KC_S43_SA004

8A0A041F5B S4301_FEC_CHG SOFT 43 switch1 signal after KC_S43_SA012

8B0A041F4C S4301_CTR_SGU SOFT 43 switch1 signal before KC_S43_SC001

8B0A041F5C S4301_OEC_CHG_PLC SOFT 43 switch1 signal after KC_S43_SA022

8C0A041F5D S4301_FEC_CHG_PLC SOFT 43 switch1 signal after KC_S43_SA023

8D0A041F45 S4301_FSD_CSF SOFT 43 switch1 signal after KC_S43_SA003

8E0A041F4F S4301_SLD_TM0 SOFT 43 switch1 signal after MCTS43_SC001

8F0A041F49 S4301_OSD_CSF SOFT 43 switch1 signal after KC_S43_SA005

8F0A041F51 S4301_EX_CMP_TM0 SOFT 43 switch1 signal after MCTS43_SC002

000A051001 S4302_STATE SOFT 43 switch2 status

000A051D90 S4302_STSELD SOFT 43 switch2 the controllable data is in the status

310A051D00 S4302_STS_MIMIC SOFT 43 switch2 status

310A051D01 S4302_STS SOFT 43 switch2 status

800A051D51 S4302_SC_OWS SOFT 43 switch2 select command by OWS(HMI)

GRL200 (Soft 033 & 037)


- 759 -
6F2S1914 (0.37)

 Signal monitoring points


SOFTSW(Function ID:522001)
Element ID Name Description
800A051D52 S4302_SC_RCC SOFT 43 switch2 select command by RCC

800A051D53 S4302_SC SOFT 43 switch2 select command

800A051D54 S4302_SC_LCD SOFT 43 switch2 select command by LCD

800A051D55 S4302_EC_OWS SOFT 43 switch2 execute command by OWS(HMI)

800A051D56 S4302_EC_RCC SOFT 43 switch2 execute command by RCC

800A051D57 S4302_EC SOFT 43 switch2 execute command

800A051D58 S4302_EC_LCD SOFT 43 switch2 execute command by LCD

800A051DE0 S4302_PLC_CTRL_FAIL SOFT 43 switch2 PLC control fail

800A051F42 S4302_TMP2 SOFT 43 switch2 signal before KC_S43_SA002

810A051D03 S4302_ST_ON SOFT 43 switch2 On state

810A051F44 S4302_TMP4 SOFT 43 switch2 signal before KC_S43_SA003

820A051F40 S4302_TMP1 SOFT 43 switch2 signal before KC_S43_SA001

830A051D02 S4302_ST_OFF SOFT 43 switch2 Off state

830A051F41 S4302_NSD_CSF SOFT 43 switch2 signal after KC_S43_SA001

850A051F46 S4302_TMP5 SOFT 43 switch2 signal before KC_S43_SA004

850A051F48 S4302_TMP7 SOFT 43 switch2 signal before KC_S43_SA005

850A051F4A S4302_TMP8 SOFT 43 switch2 signal before KC_S43_SA006

850A051F5E S4302_TMP11 SOFT 43 switch2 signal before KC_S43_SA013

860A051F43 S4302_TMP3 SOFT 43 switch2 signal after KC_S43_SA002

860A051F4E S4302_SLF_FCT_FLG01 SOFT 43 switch2 signal before MCTS43_SC001

870A051F50 S4302_SLF_FCT_FLG02 SOFT 43 switch2 signal before MCTS43_SC002

870A051F60 S4302_TMP13 SOFT 43 switch2 signal before KC_S43_SA014

870A051F62 S4302_EX_SS SOFT 43 switch2 signal execute success

880A051F4B S4302_TMP9 SOFT 43 switch2 signal after KC_S43_SA006

880A051F4D S4302_TMP10 SOFT 43 switch2 signal after KC_S43_SC001

880A051F5F S4302_TMP12 SOFT 43 switch2 signal after KC_S43_SA013

890A051F5A S4302_OEC_CHG SOFT 43 switch2 signal after KC_S43_SA011

890A051F61 S4302_TMP14 SOFT 43 switch2 signal after KC_S43_SA014

8A0A051F47 S4302_TMP6 SOFT 43 switch2 signal after KC_S43_SA004

8A0A051F5B S4302_FEC_CHG SOFT 43 switch2 signal after KC_S43_SA012

8B0A051F4C S4302_CTR_SGU SOFT 43 switch2 signal before KC_S43_SC001

8B0A051F5C S4302_OEC_CHG_PLC SOFT 43 switch2 signal after KC_S43_SA022

8C0A051F5D S4302_FEC_CHG_PLC SOFT 43 switch2 signal after KC_S43_SA023

8D0A051F45 S4302_FSD_CSF SOFT 43 switch2 signal after KC_S43_SA003

8E0A051F4F S4302_SLD_TM0 SOFT 43 switch2 signal after MCTS43_SC001

8F0A051F49 S4302_OSD_CSF SOFT 43 switch2 signal after KC_S43_SA005

8F0A051F51 S4302_EX_CMP_TM0 SOFT 43 switch2 signal after MCTS43_SC002

000A061001 S4303_STATE SOFT 43 switch3 status

000A061D90 S4303_STSELD SOFT 43 switch3 the controllable data is in the status

310A061D00 S4303_STS_MIMIC SOFT 43 switch3 status

310A061D01 S4303_STS SOFT 43 switch3 status

800A061D51 S4303_SC_OWS SOFT 43 switch3 select command by OWS(HMI)

800A061D52 S4303_SC_RCC SOFT 43 switch3 select command by RCC

800A061D53 S4303_SC SOFT 43 switch3 select command

800A061D54 S4303_SC_LCD SOFT 43 switch3 select command by LCD

GRL200 (Soft 033 & 037)


- 760 -
6F2S1914 (0.37)

 Signal monitoring points


SOFTSW(Function ID:522001)
Element ID Name Description
800A061D55 S4303_EC_OWS SOFT 43 switch3 execute command by OWS(HMI)

800A061D56 S4303_EC_RCC SOFT 43 switch3 execute command by RCC

800A061D57 S4303_EC SOFT 43 switch3 execute command

800A061D58 S4303_EC_LCD SOFT 43 switch3 execute command by LCD

800A061DE0 S4303_PLC_CTRL_FAIL SOFT 43 switch3 PLC control fail

800A061F42 S4303_TMP2 SOFT 43 switch3 signal before KC_S43_SA002

810A061D03 S4303_ST_ON SOFT 43 switch3 On state

810A061F44 S4303_TMP4 SOFT 43 switch3 signal before KC_S43_SA003

820A061F40 S4303_TMP1 SOFT 43 switch3 signal before KC_S43_SA001

830A061D02 S4303_ST_OFF SOFT 43 switch3 Off state

830A061F41 S4303_NSD_CSF SOFT 43 switch3 signal after KC_S43_SA001

850A061F46 S4303_TMP5 SOFT 43 switch3 signal before KC_S43_SA004

850A061F48 S4303_TMP7 SOFT 43 switch3 signal before KC_S43_SA005

850A061F4A S4303_TMP8 SOFT 43 switch3 signal before KC_S43_SA006

850A061F5E S4303_TMP11 SOFT 43 switch3 signal before KC_S43_SA013

860A061F43 S4303_TMP3 SOFT 43 switch3 signal after KC_S43_SA002

860A061F4E S4303_SLF_FCT_FLG01 SOFT 43 switch3 signal before MCTS43_SC001

870A061F50 S4303_SLF_FCT_FLG02 SOFT 43 switch3 signal before MCTS43_SC002

870A061F60 S4303_TMP13 SOFT 43 switch3 signal before KC_S43_SA014

870A061F62 S4303_EX_SS SOFT 43 switch3 signal execute success

880A061F4B S4303_TMP9 SOFT 43 switch3 signal after KC_S43_SA006

880A061F4D S4303_TMP10 SOFT 43 switch3 signal after KC_S43_SC001

880A061F5F S4303_TMP12 SOFT 43 switch3 signal after KC_S43_SA013

890A061F5A S4303_OEC_CHG SOFT 43 switch3 signal after KC_S43_SA011

890A061F61 S4303_TMP14 SOFT 43 switch3 signal after KC_S43_SA014

8A0A061F47 S4303_TMP6 SOFT 43 switch3 signal after KC_S43_SA004

8A0A061F5B S4303_FEC_CHG SOFT 43 switch3 signal after KC_S43_SA012

8B0A061F4C S4303_CTR_SGU SOFT 43 switch3 signal before KC_S43_SC001

8B0A061F5C S4303_OEC_CHG_PLC SOFT 43 switch3 signal after KC_S43_SA022

8C0A061F5D S4303_FEC_CHG_PLC SOFT 43 switch3 signal after KC_S43_SA023

8D0A061F45 S4303_FSD_CSF SOFT 43 switch3 signal after KC_S43_SA003

8E0A061F4F S4303_SLD_TM0 SOFT 43 switch3 signal after MCTS43_SC001

8F0A061F49 S4303_OSD_CSF SOFT 43 switch3 signal after KC_S43_SA005

8F0A061F51 S4303_EX_CMP_TM0 SOFT 43 switch3 signal after MCTS43_SC002

…. …. ….

000A3F1001 S4360_STATE SOFT 43 switch60 status

000A3F1D90 S4360_STSELD SOFT 43 switch60 the controllable data is in the status

310A3F1D00 S4360_STS_MIMIC SOFT 43 switch60 status

310A3F1D01 S4360_STS SOFT 43 switch60 status

800A3F1D51 S4360_SC_OWS SOFT 43 switch60 select command by OWS(HMI)

800A3F1D52 S4360_SC_RCC SOFT 43 switch60 select command by RCC

800A3F1D53 S4360_SC SOFT 43 switch60 select command

800A3F1D54 S4360_SC_LCD SOFT 43 switch60 select command by LCD

800A3F1D55 S4360_EC_OWS SOFT 43 switch60 execute command by OWS(HMI)

GRL200 (Soft 033 & 037)


- 761 -
6F2S1914 (0.37)

 Signal monitoring points


SOFTSW(Function ID:522001)
Element ID Name Description
800A3F1D56 S4360_EC_RCC SOFT 43 switch60 execute command by RCC

800A3F1D57 S4360_EC SOFT 43 switch60 execute command

800A3F1D58 S4360_EC_LCD SOFT 43 switch60 execute command by LCD

800A3F1DE0 S4360_PLC_CTRL_FAIL SOFT 43 switch60 PLC control fail

800A3F1F42 S4360_TMP2 SOFT 43 switch60 signal before KC_S43_SA002

810A3F1D03 S4360_ST_ON SOFT 43 switch60 On state

810A3F1F44 S4360_TMP4 SOFT 43 switch60 signal before KC_S43_SA003

820A3F1F40 S4360_TMP1 SOFT 43 switch60 signal before KC_S43_SA001

830A3F1D02 S4360_ST_OFF SOFT 43 switch60 Off state

830A3F1F41 S4360_NSD_CSF SOFT 43 switch60 signal after KC_S43_SA001

850A3F1F46 S4360_TMP5 SOFT 43 switch60 signal before KC_S43_SA004

850A3F1F48 S4360_TMP7 SOFT 43 switch60 signal before KC_S43_SA005

850A3F1F4A S4360_TMP8 SOFT 43 switch60 signal before KC_S43_SA006

850A3F1F5E S4360_TMP11 SOFT 43 switch60 signal before KC_S43_SA013

860A3F1F43 S4360_TMP3 SOFT 43 switch60 signal after KC_S43_SA002

860A3F1F4E S4360_SLF_FCT_FLG01 SOFT 43 switch60 signal before MCTS43_SC001

870A3F1F50 S4360_SLF_FCT_FLG02 SOFT 43 switch60 signal before MCTS43_SC002

870A3F1F60 S4360_TMP13 SOFT 43 switch60 signal before KC_S43_SA014

870A3F1F62 S4360_EX_SS SOFT 43 switch60 signal execute success

880A3F1F4B S4360_TMP9 SOFT 43 switch60 signal after KC_S43_SA006

880A3F1F4D S4360_TMP10 SOFT 43 switch60 signal after KC_S43_SC001

880A3F1F5F S4360_TMP12 SOFT 43 switch60 signal after KC_S43_SA013

890A3F1F5A S4360_OEC_CHG SOFT 43 switch60 signal after KC_S43_SA011

890A3F1F61 S4360_TMP14 SOFT 43 switch60 signal after KC_S43_SA014

8A0A3F1F47 S4360_TMP6 SOFT 43 switch60 signal after KC_S43_SA004

8A0A3F1F5B S4360_FEC_CHG SOFT 43 switch60 signal after KC_S43_SA012

8B0A3F1F4C S4360_CTR_SGU SOFT 43 switch60 signal before KC_S43_SC001

8B0A3F1F5C S4360_OEC_CHG_PLC SOFT 43 switch60 signal after KC_S43_SA022

8C0A3F1F5D S4360_FEC_CHG_PLC SOFT 43 switch60 signal after KC_S43_SA023

8D0A3F1F45 S4360_FSD_CSF SOFT 43 switch60 signal after KC_S43_SA003

8E0A3F1F4F S4360_SLD_TM0 SOFT 43 switch60 signal after MCTS43_SC001

8F0A3F1F49 S4360_OSD_CSF SOFT 43 switch60 signal after KC_S43_SA005

8F0A3F1F51 S4360_EX_CMP_TM0 SOFT 43 switch60 signal after MCTS43_SC002

000A401001 S4361_STATE SOFT 43 switch61 status

000A401D90 S4361_STSELD SOFT 43 switch61 the controllable data is in the status

310A401D00 S4361_STS_MIMIC SOFT 43 switch61 status

310A401D01 S4361_STS SOFT 43 switch61 status

800A401D51 S4361_SC_OWS SOFT 43 switch61 select command by OWS(HMI)

800A401D52 S4361_SC_RCC SOFT 43 switch61 select command by RCC

800A401D53 S4361_SC SOFT 43 switch61 select command

800A401D54 S4361_SC_LCD SOFT 43 switch61 select command by LCD

800A401D55 S4361_EC_OWS SOFT 43 switch61 execute command by OWS(HMI)

800A401D56 S4361_EC_RCC SOFT 43 switch61 execute command by RCC

800A401D57 S4361_EC SOFT 43 switch61 execute command

800A401D58 S4361_EC_LCD SOFT 43 switch61 execute command by LCD

GRL200 (Soft 033 & 037)


- 762 -
6F2S1914 (0.37)

 Signal monitoring points


SOFTSW(Function ID:522001)
Element ID Name Description
800A401DE0 S4361_PLC_CTRL_FAIL SOFT 43 switch61 PLC control fail

800A401F42 S4361_TMP2 SOFT 43 switch61 signal before KC_S43_SA002

810A401D03 S4361_ST_ON SOFT 43 switch61 On state

810A401F44 S4361_TMP4 SOFT 43 switch61 signal before KC_S43_SA003

820A401F40 S4361_TMP1 SOFT 43 switch61 signal before KC_S43_SA001

830A401D02 S4361_ST_OFF SOFT 43 switch61 Off state

830A401F41 S4361_NSD_CSF SOFT 43 switch61 signal after KC_S43_SA001

850A401F46 S4361_TMP5 SOFT 43 switch61 signal before KC_S43_SA004

850A401F48 S4361_TMP7 SOFT 43 switch61 signal before KC_S43_SA005

850A401F4A S4361_TMP8 SOFT 43 switch61 signal before KC_S43_SA006

850A401F5E S4361_TMP11 SOFT 43 switch61 signal before KC_S43_SA013

860A401F43 S4361_TMP3 SOFT 43 switch61 signal after KC_S43_SA002

860A401F4E S4361_SLF_FCT_FLG01 SOFT 43 switch61 signal before MCTS43_SC001

870A401F50 S4361_SLF_FCT_FLG02 SOFT 43 switch61 signal before MCTS43_SC002

870A401F60 S4361_TMP13 SOFT 43 switch61 signal before KC_S43_SA014

870A401F62 S4361_EX_SS SOFT 43 switch61 signal execute success

880A401F4B S4361_TMP9 SOFT 43 switch61 signal after KC_S43_SA006

880A401F4D S4361_TMP10 SOFT 43 switch61 signal after KC_S43_SC001

880A401F5F S4361_TMP12 SOFT 43 switch61 signal after KC_S43_SA013

890A401F5A S4361_OEC_CHG SOFT 43 switch61 signal after KC_S43_SA011

890A401F61 S4361_TMP14 SOFT 43 switch61 signal after KC_S43_SA014

8A0A401F47 S4361_TMP6 SOFT 43 switch61 signal after KC_S43_SA004

8A0A401F5B S4361_FEC_CHG SOFT 43 switch61 signal after KC_S43_SA012

8B0A401F4C S4361_CTR_SGU SOFT 43 switch61 signal before KC_S43_SC001

8B0A401F5C S4361_OEC_CHG_PLC SOFT 43 switch61 signal after KC_S43_SA022

8C0A401F5D S4361_FEC_CHG_PLC SOFT 43 switch61 signal after KC_S43_SA023

8D0A401F45 S4361_FSD_CSF SOFT 43 switch61 signal after KC_S43_SA003

8E0A401F4F S4361_SLD_TM0 SOFT 43 switch61 signal after MCTS43_SC001

8F0A401F49 S4361_OSD_CSF SOFT 43 switch61 signal after KC_S43_SA005

8F0A401F51 S4361_EX_CMP_TM0 SOFT 43 switch61 signal after MCTS43_SC002

 Connection points in PLC logic


SOFTSW(Function ID:522001)
Element ID Name Description
860A01EDE0 CBK_CHG_TO_OFF CMDBLK change to off

850A01EDE1 CBK_CHG_TO_ON CMDBLK change to on

820A01ED50 CBK_CTRL_RIGHT CMDBLK control right from PLC

860A02EDE0 ICB_CHG_TO_OFF ILKBYP change to off

850A02EDE1 ICB_CHG_TO_ON ILKBYP change to on

820A02ED50 ICB_CTRL_RIGHT ILKBYP control right from PLC

860A03EDE0 SCB_CHG_TO_OFF SYNCBYP change to off

850A03EDE1 SCB_CHG_TO_ON SYNCBYP change to on

820A03ED50 SCB_CTRL_RIGHT SYNCBYP control right from PLC

860A04EDE0 S4301_CHG_TO_OFF SOFT 43 switch1 change to off

GRL200 (Soft 033 & 037)


- 763 -
6F2S1914 (0.37)

 Connection points in PLC logic


SOFTSW(Function ID:522001)
Element ID Name Description
850A04EDE1 S4301_CHG_TO_ON SOFT 43 switch1 change to on

820A04ED50 S4301_CTRL_RIGHT SOFT 43 switch1 control right from PLC

860A05EDE0 S4302_CHG_TO_OFF SOFT 43 switch2 change to off

850A05EDE1 S4302_CHG_TO_ON SOFT 43 switch2 change to on

820A05ED50 S4302_CTRL_RIGHT SOFT 43 switch2 control right from PLC

860A06EDE0 S4303_CHG_TO_OFF SOFT 43 switch3 change to off

850A06EDE1 S4303_CHG_TO_ON SOFT 43 switch3 change to on

820A06ED50 S4303_CTRL_RIGHT SOFT 43 switch3 control right from PLC

….. …. …..
860A3FEDE0 S4360_CHG_TO_OFF SOFT 43 switch60 change to off

850A3FEDE1 S4360_CHG_TO_ON SOFT 43 switch60 change to on

820A3FED50 S4360_CTRL_RIGHT SOFT 43 switch60 control right from PLC

860A40EDE0 S4361_CHG_TO_OFF SOFT 43 switch61 change to off

850A40EDE1 S4361_CHG_TO_ON SOFT 43 switch61 change to on

820A40ED50 S4361_CTRL_RIGHT SOFT 43 switch61 control right from PLC

Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the SOFTSW function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.

Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “S4301_EC_LCD” point for the
2nd device, use the description of “S4302_EC_LCD” in place of
“S4301_EC_LCD”. The user can obtain the ID value of “S4302_EC_LCD” by
using the following steps:
Step 1 Find the element ID for S4301_EC_LCD (i.e.,
“8C00041F45”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “4”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8C00051F45” of
“S4302_EC_LCD”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.

GRL200 (Soft 033 & 037)


- 764 -
6F2S1914 (0.37)

Operation time reset function (OPTIM)


As shown in Figure 4.4-1, all operation-times measured by the DPOS, DPSY, and TPOS
functions† can be cleared when the operation time reset controller (OPTIM) function issues a
reset command “OPTR01_RST_CMD”. That is, within the respective functions the measured
time intervals (OT1 and the others‡) are entirely cleared upon occurrence of the reset command.
DPSY01 function
Sending reset command Clearing measured time-intervals
OPTIM function “OPTR01_RST_CMD” “OT1”, “OT2”, “OT3” and “OT4”

Sending reset command


“OPTR01_RST_CMD” DPOS01 function
Clearing measured time-intervals
“OT1”, “OT2”, “OT3” and “OT4”
Sending reset
command
“OPTR01_RST_CMD”

TPOS01 function
Clearing measured time-intervals
“OT1”, “OT2”, “OT3” and “OT4”

Figure 4.4-1 Reception of a reset command


†Note:For more information with regard to measurement, refer to the section
“Measurement of operation intervals” for the respective DPOS, DPSY, and TPOS
functions. The user should note that all interval OTs specific to a particular
function are cleared by the OPTIM reset command.

GRL200 (Soft 033 & 037)


- 765 -
6F2S1914 (0.37)

‡Note:The measurements in the DPOS and the DPSY functions are grouped into four
intervals in each respective device. Measurement is possible by sensing the device
events. The measured intervals are accumulated; they are grouped into four
intervals (OT1–OT4), which the user can monitor from the IED screen. Figure
4.4-2 and Figure 4.4-3 exemplify the four intervals upon occurrence of On
(Closing)-control event and Off (Open)-control event, provided that the DPOS
function operates.

Issuing Off control

Sensing
intermediate state On Intermediate Off

Device status for “Off”


OT1 OT2

Figure 4.4-2 Two intervals (OT1 and OT2) for Off-control event

Issuing On control

Sensing
intermediate state Off Intermediate On

Device status for “On”


OT3 OT4

Figure 4.4-3 Two intervals (OT3 and OT4) for On-control event
Tips: If the user wishes to implement the OPTIM function quickly, go to section 4.4.4,
which discusses how to map signal-points for the IEC 61850 communication.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features depends on the selection of hardware and the
configuration of functions. Several IED models do not have its features. To determine whether
its features are implemented in the IED, locate the IED ordering number; and check the order
number at the “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 4.4-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 766 -
6F2S1914 (0.37)

4.4.1 Select logic for SBO/DIR modes


The user should set the scheme switch [OPTR01-EN] to On prior to the OPTIM operation.
Figure 4.4-4 shows select logic in the OPTIM function.
Wait for a command

Wait for a next command


Select logic
Cancel logic

Resetting OTs from the remote-end Cancel command


Failed
Cancel logic
Signal reception Select
Selection logic Signal output
IEC61850 decision Success
Operate logic
Operate command

Operate logic

Figure 4.4-4 Outline of select command for resetting

(i) Input point required mapping


Figure 4.4-5 shows the select logic when a “Select command (Reset)” signal enters the OPTIM
function. The logic has the input-point “OPTR01_CONTROL_REQ” for the reception. That is,
the input-point should be mapped for the IEC61850 communication. The function encounters
an operation failure if mapping is not performed correctly. We discuss how to map the input-
points for the IEC61850 communication in section 4.4.4.
Input Select logic in OPTR Output

OPTIM function (Function ID: 529001)


OPTR01_FSE_RCV
Command “Reset”
For SBO operation (529001 800C011F42)
529001 700C016D08 OPTR01_CONTROL_REQ Select
command & 1≥
&
For DIR operation
Operate
command &
OPTR01_NSD_CSF
To “Wait for a next command”
(529001 830C011F41)
0 t
529001 000C011D90 OPTR01_STSELD
0.2s

0 t
Failed
0.3s

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function
(AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.4-5 Select logic for resetting intervals OT1 to OT4


‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.4-6.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
the automatic control. The OPTIM operation is blocked for the ASEQ function
being in the operation. For more information of the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.

GRL200 (Soft 033 & 037)


- 767 -
6F2S1914 (0.37)

*Note:The OPTIM function can run on either “the SBO mode” or “the DIR mode” using a
signal “ctlmodel” when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.

(ii) Output signal required to map


The OPTIM function can issue a “Select success” signal at the output point
“OPTR01_NSD_CSF”, when the OPTIM function can decide that the input signal “Select
command (Reset)” is true. If the OPTIM function decides that the “Select command (Reset)” is
not true, the OPTIM function returns to the “Wait for a command” stage.

(iii) Select condition


Figure 4.4-6 shows the select condition logic in the OPTIM function.

OPTIM function (Function ID: 529001)


Command blocking*1
CBK_STATE To selection logic
1≥ & Select condition
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR Unmatched condition detected *4

Function “Automatic sequence control” is in progress


ASEQ_MULTI_SEL

Users must setup this condition correctly


Control hierarchy (e.g. 43RL) (PLC connection point) *5
529001 820C01ED50 OPTR01_CTRL_RIGHT
&
IED serious error detected
SERI_ERR

[OPTR1_EN]

On

Figure 4.4-6 Select condition logic in the OPTIM function*6


*1Note: The “command blocking” disables any operation except for itself: the
“command blocking” is stated with “CBK” in a software controller (SOFTSW). The
IEC61850 defines the “command blocking” as “CmdBlk”. For more information on
CBK, see Chapter Control and monitoring application: Software switch control
function. See the signal “CBK_STATE” of Table 4.4-2.
*2Note: “Double Command Blocking (DCB)” is operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
should program it using the GR-TIEMS. The DCB operating signal is denoted as
“DCB RCV_OR in Table 4.4-2. For more information, see Chapter Control and
monitoring application: Common controls.
*3Note: If events “device-travelling” are detected in the CMNCTRL function, we can
see that some statuses of the devices are being changed by other operators. Thus,
the IED should stop any operation while the events are being detected. The
detecting signal is denoted by “Traveling OR” in Table 4.4-2.

GRL200 (Soft 033 & 037)


- 768 -
6F2S1914 (0.37)

*4Note: Criteria “unmatched conditions” are decided when “Test-bit status” in a


command is not identical to “IED test status”.
*5Note: The user should program the PLC logic “Control hierarchy condition”. The
user should connect its condition with the select condition logic using the
connection point “OPTR01_CTRL_RIGHT”. For more information, see chapter
Control and monitoring application: Control hierarchy. “OPTR01_CTRL_RIGHT”
is provided in Table 4.4-3.
*6Note: To know the input point of the OPTIM function, see Table 4.4-3.

Table 4.4-2 Input signal for condition logic


Signal Number Signal Name Description M/O
522001 000A011001 CBK_STATE Command Blocking status ( Off / Blocked) N/A
5A0001 0008001F41 DCB RCV OR Double Command Blocking(DCB) is in progress. N/A
5A0001 0008001F40 Traveling OR Travelling events are detected. N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A
523001 000D001F40 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A

Table 4.4-3 PLC connection point (Input point on select condition logic)
Signal Number Signal Name Description M/O
529001 820C01ED50 OPTR01_CTRL_RIGHT OPTIM control hierarchy M

Table 4.4-4 Setting of the OPTIM function


Setting Name Description Default Setting item or value
OPTR01_EN Enabling the OPTIM function On Off / On

GRL200 (Soft 033 & 037)


- 769 -
6F2S1914 (0.37)

4.4.2 Cancel logic in SBO mode


In the SBO control mode the reception of the cancel command is possible when the cancel
conditions are satisfied. Accordingly, the function can discard the select command; finally, the
operation returns to the initial stage (i.e., “Wait for a command”.)

(i) Receiving “Cancel” from the remote-end


Figure 4.4-7 outlines the reception of the cancel command from the remote end.

Wait for a command

Select logic Wait for a next command

Cancel by the remote-end


Success

Command Reset from the Signal reception in Cancel


Cancel logic Do nothing
remote-end IEC61850 decision Failed

Operate logic
Operate command

Operate logic

Figure 4.4-7 Outline of cancel command from the remote-end

(ii) Input point required mapping


Figure 4.4-8 shows the cancel logic when a “Cancel command (Remote-Cancel)” signal enters
the OPTIM function. The input-point “OPTR01_CONTROL_REQ” is the same point of the
Figure 4.4-5.
510001 7001016D08

Input Cancel logic in OPTR Output

OPTIM function (Function ID: 529001)


Command “Cancel”
Cancel command
529001 700C016D08 OPTR01_CONTROL_REQ
&

Unmatched condition To “Wait for a command”


detected† &
Successes to cancel

“Do nothing”
Operation Failed

Figure 4.4-8 Cancel from the remote-end


†Note:The criteria “unmatched conditions” are determined when “Test-bit status” in a
command is not identical to “IED test status”.

GRL200 (Soft 033 & 037)


- 770 -
6F2S1914 (0.37)

4.4.3 Operate logic for SBO/DIR modes


After the completion of the operation of the select logic, the operate logic enters to clear all
interval OTs.

Wait for a command

Select logic Wait for a next command

Operate command from the remote-end


Command Reset from the Success
Operation
remote-end Signal reception in Operate logic Resetting OTs
decision
IEC61850

Failed Do nothing

Operate command from the local-end


Success
Operation
Selecting “Reset All” Operate logic Resetting OTs
decision

Failed Do nothing

Cancel logic

Cancel command

Cancel logic

Figure 4.4-9 Outline of operate command for resetting intervals OT1 to OT4

(i) Input signal required mapping


Figure 4.4-10 shows the operate logic when an “Operation command (Reset)” signal enters the
OPTIM function. The input-point “OPTR_CONTROL_REQ” is used for the reception of the
“Operation command (Reset)” signal, which is the same point of the select logic.
Input Selection logic in OPTR Output

OPTIM function (Function ID: 529001)

OPTR01_RST_CMD
Command “Operating reset”
529001 310C011EA1
529001 700C016D08 OPTR01_CONTROL_REQ Operate command
& Reset all OTs

Operate condition‡
“Automatic sequence control function (AQEQ)§”
in progress
ASEQ_MULTI_SEL

From the operation on the front panel

Reset All

Figure 4.4-10 Operate logic for resetting intervals OT1 to OT4

(ii) Output signal required to map


The operate logic issues a “OPRT_RST_CMD” signal to clear all intervals OT1 to OT4. The
signal “OTS_RST_CMD” can be transferred to the remote-end, when mapping the signal is
carried out in the IEC61850 communication. (See section 4.4.4)

GRL200 (Soft 033 & 037)


- 771 -
6F2S1914 (0.37)

(iii) Operate condition


Figure 4.4-11 shows the operate condition logic, which is used to examine a reset-condition in
the OPTIM function.
OPTIM function (Function ID: 529001)
Command blocking*1
CBK_STATE To operate logic
1≥ & Operate condition
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR Unmatched condition detected *4

Function “Automatic sequence control” is in progress


ASEQ_MULTI_SEL
Users must setup this condition correctly
Control hierarchy (e.g. 43RL) (PLC connection point) *5
529001 820C01ED50 OPTR01_CTRL_RIGHT
&
IED serious error detected
SERI_ERR

[OPTR1_EN]

On

Figure 4.4-11 Operate condition logic in OPTIM


*1to5Note: The signals and settings of the Figure 4.4-11 are same as the ones of the
Figure 4.4-6.

GRL200 (Soft 033 & 037)


- 772 -
6F2S1914 (0.37)

4.4.4 Mapping for IEC61850 communication


The user can operate the OPTIM function over the IEC61850 communication after the
mapping using the GR-TIEMS. Note that the OPTIM function is designed for “Single Point
Controller (SPC) class” in the IEC61850 communication. The user should follow steps:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user should make a logical node (LN) for the OPTIM function. Figure 4.4-12 exemplifies
LN editing; the LN “General Input / Output (GGIO)” is chosen for the OPTIM function. After
the user defining an object “SPCSO”, the OPTIM logical node can be saved with the name
“GIGO” plus “LN Instance”. Make a definition of the object “SPCSO” in the OPTIM logical node.
“Either the SBO mode or the DIR mode can be chosen in the LN editing.

SBO defined in LN

Figure 4.4-12 Defining “SPCSO” object in GIGO3302 logic node

GRL200 (Soft 033 & 037)


- 773 -
6F2S1914 (0.37)

Defining SBO mode


Figure 4.4-13 exemplifies the OPTIM logic node saved as “GGIO3302”. In the SBO mode, the
user should select the following items for the “GGIO3302$SCPSO” using the GR-TIEMS:

 SBOw
 Oper
 Cancel
 Origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.

Figure 4.4-13 LN editing for SBO (for example)

Defining DIR mode


Figure 4.4-14 exemplifies the OPTIM logic node saved as GGIO3302. In the DIR mode, the
following three items should be selected using the GR-TIEMS:

 Oper
 origin
 ctlmodel (choice ”DOes or DOns” )

Figure 4.4-14 LN editing for DIR mode (for example)

GRL200 (Soft 033 & 037)


- 774 -
6F2S1914 (0.37)

(ii) Mapping output data


The user should group the OPTIM signals with regard to GOOSE and REPORT; the user
should map them for the IEC61850 communication using the GR-TIEMS. Figure 4.4-15 shows
how to map a signal; it shows that the signals of the OPTIM function are required to map for
the IEC61850 communication.
Table 4.4-5 Mapping signals for SPC object
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO3302$SPCSO1$origin orCat orCategory ST 529001 200C011008 OPTR01_ORCAT
Ctrl/GGIO3302$SPCSO1$origin orIdent Octet64 ST 529001 310C01170A OPTR01_ORIDENT
Ctrl/GGIO3302$SPCSO1 stVal BOOLEAN ST 529001 310C011EA1 OPT_RST_CMD
Ctrl/GGIO3302$SPCSO1 Q Quality ST 301001 3110041005 Qual_Val
Ctrl/GGIO3302$SPCSO1 T Timestamp ST 200301 9010001006 SYS_TIME
Ctrl/GGIO3302$SPCSO1 stSeld BOOLEAN ST 529001 000C011D90 OPTR01_STSELD

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.

Figure 4.4-15 orCat attribute mapped into SPCSO object of GGIO3302

(iii) Mapping input data


The OPTIM function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “OPTR01_CONTROL_REQ”. Table 4.4-6 shows the input-point
“OPTR01_CONTROL_REQ” and the Object reference “Ctrl/GGIO3302$SCPSO”; the user should

GRL200 (Soft 033 & 037)


- 775 -
6F2S1914 (0.37)

map the input-point to the Object references having attributes CO and CF†. Figure 4.4-16 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850; “CO” stands for “Control” and “CF”
stands for “Configuration” in the functional constraint (FC).

Table 4.4-6 Mapping signals required for SPCSO object of GGIO3302


Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO3302$SPCSO1$Oper ctlVal BOOLEAN CO
Ctrl/GGIO3302$SPCSO1$Oper ctlNum INT8U CO
Ctrl/GGIO3302$SPCSO1$Oper T Timestamp CO
Ctrl/GGIO3302$SPCSO1$Oper Test BOOLEAN CO
Ctrl/GGIO3302$SPCSO1$Oper Check Check CO 529001 700C016D08 OPTR01_CONTROL_REQ
Ctrl/GGIO3302$SPCSO1$Oper$origin orCat orCategory CO
Ctrl/GGIO3302$SPCSO1$Oper$origin orIdent Octet64 CO
Ctrl/GGIO3302$SPCSO1 ctlModel ctlModel CF
Ctrl/GGIO3302$SPCSO1 sboClass sboClass CF

Check “Input”

Figure 4.4-16 Input-point mapped for GGIO3302

GRL200 (Soft 033 & 037)


- 776 -
6F2S1914 (0.37)

4.4.5 Setting
OPTIMRSTCTRL (Function ID: 529001)
Setting items Range Unit Contents Default Note

OPTR01-EN Off / On - Reset Control Enable in OPTR Off

GRL200 (Soft 033 & 037)


- 777 -
6F2S1914 (0.37)

4.4.6 Signal
 Signal monitoring points
OPTIMRSTCTRL (Function ID: 529001)
Element ID Name Description
8B0C011F44 OPTR01_CTR_SGU OPTR01 signal before KC_OPTR_SC001

800C011D57 OPTR01_EC OPTR01 execute command

800C011D55 OPTR01_EC_OWS OPTR01 execute command by OWS(HMI)

800C011D56 OPTR01_EC_RCC OPTR01 execute command by RCC

8F0C011F49 OPTR01_EX_CMP_TM0 OPTR01 signal after MCTOPTR_SC002

800C011F42 OPTR01_FSE_RCV OPTR01 signal before LC_OPTR_SA002

830C011F41 OPTR01_NSD_CSF OPTR01 signal after KC_OPTR_SA001

310C011EA1 OPTR01_RST_CMD OPTR01 select command output

800C011D53 OPTR01_SC OPTR01 select command

800C011D51 OPTR01_SC_OWS OPTR01 select command by OWS(HMI)

800C011D52 OPTR01_SC_RCC OPTR01 select command by RCC

8E0C011F47 OPTR01_SLD_TM0 OPTR01 signal after MCTOPTR_SC001

860C011F46 OPTR01_SLF_FCT_FLG1 OPTR01 signal before MCTOPTR_SC001

870C011F48 OPTR01_SLF_FCT_FLG2 OPTR01 signal before MCTOPTR_SC002

000C011D90 OPTR01_STSELD OPTR01 the controllable data is in the status selected (StSeld)

820C011F40 OPTR01_TMP1 OPTR01 signal before KC_OPTR_SA001

860C011F43 OPTR01_TMP2 OPTR01 signal after KC_OPTR_SA002

860C011F45 OPTR01_TMP3 OPTR01 signal after KC_OPTR_SC001

 Connection point in PLC logic


OPTIMRSTCTRL (Function ID: 529001)
Element ID Name Description
820C01ED50 OPTR01_CTRL_RIGHT OPTR01 control right from PLC

 Mapping point
OPTIMRSTCTRL (Function ID: 529001)
Element ID Name Description
700C016D08 OPTR01_CTRL_RIGHT Control command

GRL200 (Soft 033 & 037)


- 778 -
6F2S1914 (0.37)

Total time measurement function (TOTALTIM)


The total time measurement function (TOTALTIM) measures the time of the On state using a
signal which is selected with the logic programmed by the PLC function. The TOTALTIM
function increments the time for which the signal is in the “ON” state and stores it as a
cumulative time. The TOTALTIM function can monitor up to 12 signals simultaneously. This
function also has correction processes.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features depends on the selection of hardware and the
configuration of functions. Several IED models do not have its features. To determine whether
its features are implemented in the IED, locate the IED ordering number; and check the order
number at the “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 4.5-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
– Number of functions – 12
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 779 -
6F2S1914 (0.37)

4.5.1 Operation feature


(i) Time accumulation process
Figure 4.5-1 outlines the time accumulation process within the TOTALTIM function. The
TOTALTIM function accumulates the time for which the state of the operating signal is in the
“ON” status every second. The accumulation process continues until the maximum
accumulated time reaches 10,000 days (almost 27 years).
Operation
signal
The value returns to zero if the
time counter reaches the
Cumulative maximum value.
time

864,000,000sec

60sec

Operation time
0sec The TOTALTIM function
checks the state of the
operation signal every
second. If the operation
signal is in the “On” state,
TOTALTIM accumulates
TOTALTIM process the “On” time.

Figure 4.5-1 Cumulative time process

(ii) Acquisition of operation signal


The user should connect the binary input circuit (BI) to the TOTALTIM function.

Figure 4.5-2 illustrates that 12 signals can be accommodated from external devices using
BIs. For example, when binary input circuit BI1 receives operating signal1, provided signal-
monitoring point “BI1” is applied for the acquisition of the signal, the user can make the logic
to connect “BI1” with TT01 of the TOTALTIM function using the PLC function.

GRL200 (Soft 033 & 037)


- 780 -
6F2S1914 (0.37)

IED TOTALTIM
Device
TOTAL12_PLC_SGNL

TT12
PLC
SAS
Device #12 BI12-NC BI12 BI12-CPL
Photo- Filter CPL
Operating signal #12
coupler

TOTAL02_PLC_SGNL

TT02
PLC

Device #2 BI2-NC BI2 BI2-CPL IED


TOTAL01_PLC_SGNL IED
Photo- front
Operating signal #2 Filter CPL screen
coupler screen
TT01
PLC
Device #1 BI1-NC BI1 BI1-CPL

Operating signal #1
Photo- Filter CPL
coupler
Contact-switch Binary IO module (BIO)

Figure 4.5-2 Acquisition of operation signals

(iii) Setting for the report (Dead band)


For sending data for the network, the TOTALTIM function will get a new accumulated data
every cycle that is defined with the setting [TTIM*-SDB]. For example, if the user wishes to
report the operation time about the device #1, the user should set ‘1’ to the setting [TTIM01-
SDB], provided the report cycle is required every one second.
Table 4.5-2 Setting for data revision
Scheme switch Set Comment
TTIM01-SDB 1 to 720sec Data revision period for operating signal 1
TTIM02-SDB 1 to 720sec Data revision period for operating signal 2
(omitted) (omitted) (omitted)
TTIM12-SDB 1 to 720sec Data revision period for operating signal 12

(iv) Data correction


In the TOTALTIM function the user can correct the accumulation time using either IED front
panel operation or GR-TIEMS operation (For IED screen operation, see Chapter User interface.
For GR-TIEMS operation, see Chapter Engineering tool)

GRL200 (Soft 033 & 037)


- 781 -
6F2S1914 (0.37)

4.5.2 Preparation for operation


The TOTALTIM function is enabled when the user sets [TTIM*-EN] On.

Table 4.5-3 TOTALTIM operation


Scheme switch Set Comment
TTIM01-EN On / Off Operation enable for operating signal #1
TTIM02-EN On / Off Operation enable for operating signal #2
(omitted) (omitted) (omitted)
TTIM12-EN On / Off Operation enable for operating signal #12

GRL200 (Soft 033 & 037)


- 782 -
6F2S1914 (0.37)

4.5.3 Mapping for IEC 61850 communication


The user can operate the TTIM01 function using IEC 61850 communications after first
mapping the function using GR-TIEMS. The user should proceed as follows
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user must make a logical node (LN) for the TTIM01 function. Figure 4.5-3 exemplifies LN
editing; LN “GGIO1301” is selected for the TTIM01 function for IEC 61850 communication.
After the user has defined an object “ISCSO1”, the TTIM01 logical node can be saved with the
name “GGIO1301”. Define the object “ISCSO1” in the TTIM01 logical node. Either the SBO
mode or the DIR mode can be chosen when editing the LN.

SBO defined in LN

Figure 4.5-3 Defining “ISCSO1” object in GGIO1301 logic node

Defining SBO mode


Figure 4.5-4 exemplifies the settings in LN “GGIO1301” when the SBO mode is required for
the TTIM01 function. For SBO control, the user should select the following items for the
“GGIO1301$ISCSO1” using GR-TIEMS;

GRL200 (Soft 033 & 037)


- 783 -
6F2S1914 (0.37)

 SBOw
 Oper
 Cancel
 Origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns”)

†”sboClass” can be found by scrolling down.

Figure 4.5-4 LN editing screen for SBO mode (for example)

Defining DIR mode


Figure 4.5-5 exemplifies the settings in LN “GGIO1301” when the DIR mode is required for
the TTIM01 function. In the DIR mode, the following three items should be selected using GR-
TIEMS:

 Oper
 origin
 ctlmodel (choice ”DOes or DOns”)

Figure 4.5-5 LN editing screen for DIR mode (for example)

(ii) Mapping output data


The user should group the TTIM01 signals with regard to GOOSE and REPORT; the user
should map them for IEC 61850 communication using GR-TIEMS.
Table 4.5-4 shows the mapping signals within the TTIM01 function required for IEC
61850 communication. Figure 4.5-6 shows how to map a signal.

GRL200 (Soft 033 & 037)


- 784 -
6F2S1914 (0.37)

Table 4.5-4 Mapping signals for ISCSO1 object.


Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO1301$ISCSO1$origin orCat orCategory ST 5410013015011D23 TTIM01_TIM_ORCAT
Ctrl/GGIO1301$ISCSO1$origin orIdent Octet64 ST 5410016A15011FA7 TTIM01_TIM_ORIDENT
Ctrl/GGIO1301$ISCSO1 stVal INT32 ST 5410013215011D20 TTIM01_TIM_SEC_VAL
Ctrl/GGIO1301$ISCSO1 q Quality ST 5410013115011D21 TTIM01_TIM_QLT
Ctrl/GGIO1301$ISCSO1 t Timestamp ST 5410019015011D22 TTIM01_TIM_TIM
Ctrl/GGIO1301$ISCSO1 stSeld BOOLEAN ST 5410010015011D91 TTIM01_TMP_01
Ctrl/GGIO1301$AnIn1$mag f FLOAT32 MX 5410013215011D20 TTIM01_TIM_SEC_VAL
Ctrl/GGIO1301$AnIn1 q Quality MX 5410013115011D21 TTIM01_TIM_QLT
Ctrl/GGIO1301$AnIn1 t Timestamp MX 5410019015011D22 TTIM01_TIM_TIM

Note: “Status (ST)” and “Measurement (MX)” are defined in the function constraint (FC)
of the IEC 61850 standard.

Drag and drop

Figure 4.5-6 orCat attribute mapped into ISCSO1 object of GGIO1301

(iii) Mapping input data


The TTIM01 function can receive three commands “select, operate, and cancel. Thus, the user
will need to map the input-point “TOTAL01_CMM_REQ”. Table 4.5-5 shows the input-point
“TOTAL01_CMM_REQ” and the Object reference “Ctrl/GGIO1301$ISCSO1$”; the user should
map the input-point to the Object reference having attributes CO and CF in FC†. Figure 4.5-7
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).

GRL200 (Soft 033 & 037)


- 785 -
6F2S1914 (0.37)

Table 4.5-5 Mapping signals required for GGIO1301 object in TTIM01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO1301$ISCSO1$SBOw ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$SBOw ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$SBOw T Timestamp CO
Ctrl/GGIO1301$ISCSO1$SBOw Test BOOLEAN CO
Ctrl/GGIO1301$ISCSO1$SBOw Check Check CO
Ctrl/GGIO1301$ISCSO1$SBOw$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1$Oper ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$Oper ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$Oper T Timestamp CO
Ctrl/GGIO1301$ISCSO1$Oper Test BOOLEAN CO
5410017015016D08 TOTAL01_CMM_REQ
Ctrl/GGIO1301$ISCSO1$Oper Check Check CO
Ctrl/GGIO1301$ISCSO1$Oper$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$Oper$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1$Cancel ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$Cancel ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$Cancel T Timestamp CO
Ctrl/GGIO1301$ISCSO1$Cancel Test BOOLEAN CO
Ctrl/GGIO1301$ISCSO1$Cancel$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1 ctlModel ctlModel CF
Ctrl/GGIO1301$ISCSO1 sboClass sboClass CF

Drag and drop

Figure 4.5-7 Input-point mapped for GGIO1301

GRL200 (Soft 033 & 037)


- 786 -
6F2S1914 (0.37)

4.5.4 Setting
TOTALTIM(Function ID: 541001)
Setting items Range Unit Contents Default Note

TTIM01-EN Off / On - Switch for total time metering at Dev.01 Off


TTIM02-EN Off / On - Switch for total time metering at Dev.02 Off
TTIM03-EN Off / On - Switch for total time metering at Dev.03 Off
TTIM04-EN Off / On - Switch for total time metering at Dev.04 Off
TTIM05-EN Off / On - Switch for total time metering at Dev.05 Off
TTIM06-EN Off / On - Switch for total time metering at Dev.06 Off
TTIM07-EN Off / On - Switch for total time metering at Dev.07 Off
TTIM08-EN Off / On - Switch for total time metering at Dev.08 Off
TTIM09-EN Off / On - Switch for total time metering at Dev.09 Off
TTIM010-EN Off / On - Switch for total time metering at Dev.10 Off
TTIM011-EN Off / On - Switch for total time metering at Dev.11 Off
TTIM012-EN Off / On - Switch for total time metering at Dev.12 Off
Dev. 01 TTIM01-SDB 0 - 720 - Sending Dead Band number 0
TTIM01-DEVNAME [Preferred name] - Device name for Total Time1 TOTAL TIME 1 !
02 TTIM02-SDB 0 - 720 - Sending Dead Band number 0
TTIM02-DEVNAME [Preferred name] - Device name for Total Time2 TOTAL TIME 2 !
03 TTIM03-SDB 0 - 720 - Sending Dead Band number 0
TTIM03-DEVNAME [Preferred name] - Device name for Total Time3 TOTAL TIME 3 !
04 TTIM04-SDB 0 - 720 - Sending Dead Band number 0
TTIM04-DEVNAME [Preferred name] - Device name for Total Time4 TOTAL TIME 4 !
05 TTIM05-SDB 0 - 720 - Sending Dead Band number 0
TTIM05-DEVNAME [Preferred name] - Device name for Total Time5 TOTAL TIME 5 !
06 TTIM06-SDB 0 - 720 - Sending Dead Band number 0
TTIM06-DEVNAME [Preferred name] - Device name for Total Time6 TOTAL TIME 6 !
07 TTIM07-SDB 0 - 720 - Sending Dead Band number 0
TTIM07-DEVNAME [Preferred name] - Device name for Total Time7 TOTAL TIME 7 !
08 TTIM08-SDB 0 - 720 - Sending Dead Band number 0
TTIM08-DEVNAME [Preferred name] - Device name for Total Time8 TOTAL TIME 8 !
09 TTIM09-SDB 0 - 720 - Sending Dead Band number 0
TTIM09-DEVNAME [Preferred name] - Device name for Total Time9 TOTAL TIME 9 !
10 TTIM010-SDB 0 - 720 - Sending Dead Band number 0
TTIM010-DEVNAME [Preferred name] - Device name for Total Time10 TOTAL TIME 10 !
11 TTIM011-SDB 0 - 720 - Sending Dead Band number 0
TTIM011-DEVNAME [Preferred name] - Device name for Total Time11 TOTAL TIME 11 !
12 TTIM012-SDB 0 - 720 - Sending Dead Band number 0
TTIM012-DEVNAME [Preferred name] - Device name for Total Time12 TOTAL TIME 12 !
!Note: The user can enter a preferred setting name using GR-TIEMS.

GRL200 (Soft 033 & 037)


- 787 -
6F2S1914 (0.37)

4.5.5 Signal
 Signal monitoring points
TOTALTIM(Function ID: 541001)
Element ID Name Description
0015001F41 TTIM00_CCTRL_TIME TTIM00 total time correction summarize

8015001D58 TTIM00_CH_EC_LCD TTIM00 total time change execute command by LCD

8015001D55 TTIM00_CH_EC_OWS TTIM00 total time change execute command by OWS(HMI)

8015001D56 TTIM00_CH_EC_RCC TTIM00 total time change execute command by RCC

8015001D57 TTIM00_CH_EC_RMT TTIM00 total time change execute command by Remote

8015001D54 TTIM00_CH_SC_LCD TTIM00 total time change select command by LCD

8015001D51 TTIM00_CH_SC_OWS TTIM00 total time change select command by OWS(HMI)

8015001D52 TTIM00_CH_SC_RCC TTIM00 total time change select command by RCC

8015001D53 TTIM00_CH_SC_RMT TTIM00 total time change select command by Remote

8415011E95 TTIM01_CC_SS TTIM01 cancel success signal

8915011EA2 TTIM01_CTR_SGU TTIM01 control logic stage(under selection)

8315011E8B TTIM01_EC_F_CN TTIM01 execute command fail condition signal

8215011E84 TTIM01_EC_OK_CS TTIM01 execute command OK condition signal

8A15011E76 TTIM01_SLD_CS TTIM01 selected condition signal

8B15011E7B TTIM01_SLF_CS TTIM01 select fail condition signal

3215011F41 TTIM01_TIM_MIN TTIM01 total time (minutes)

0015011D91 TTIM01_TMP_01 TTIM01 total time change selected signal(stSeld) for SAS

8415021E95 TTIM02_CC_SS TTIM02 cancel success signal

8915021EA2 TTIM02_CTR_SGU TTIM02 control logic stage(under selection)

8315021E8B TTIM02_EC_F_CS TTIM02 execute command fail condition signal

8215021E84 TTIM02_EC_OK_CS TTIM02 execute command OK condition signal

8A15021E76 TTIM02_SLD_CS TTIM02 selected condition signal

8B15021E7B TTIM02_SLF_CS TTIM02 select fail condition signal

3215021F41 TTIM02_TIM_MIN TTIM02 total time (minutes)

0015021D91 TTIM02_TMP_01 TTIM02 total time change selected signal(stSeld) for SAS

8415031E95 TTIM03_CC_SS TTIM03 cancel success signal

8915031EA2 TTIM03_CTR_SGU TTIM03 control logic stage(under selection)

8315031E8B TTIM03_EC_F_CS TTIM03 execute command fail condition signal

8215031E84 TTIM03_EC_OK_CS TTIM03 execute command OK condition signal

8A15031E76 TTIM03_SLD_CS TTIM03 selected condition signal

8B15031E7B TTIM03_SLF_CS TTIM03 select fail condition signal

3215031F41 TTIM03_TIM_MIN TTIM03 total time (minutes)

0015031D91 TTIM03_TMP_01 TTIM03 total time change selected signal(stSeld) for SAS

8415041E95 TTIM04_CC_SS TTIM04 cancel success signal

8915041EA2 TTIM04_CTR_SGU TTIM04 control logic stage(under selection)

8315041E8B TTIM04_EC_F_CS TTIM04 execute command fail condition signal

8215041E84 TTIM04_EC_OK_CS TTIM04 execute command OK condition signal

8A15041E76 TTIM04_SLD_CS TTIM04 selected condition signal

8B15041E7B TTIM04_SLF_CS TTIM04 select fail condition signal

3215041F41 TTIM04_TIM_MIN TTIM04 total time (minutes)

0015041D91 TTIM04_TMP_01 TTIM04 total time change selected signal(stSeld) for SAS

8415051E95 TTIM05_CC_SS TTIM05 cancel success signal

8915051EA2 TTIM05_CTR_SGU TTIM05 control logic stage(under selection)

GRL200 (Soft 033 & 037)


- 788 -
6F2S1914 (0.37)

 Signal monitoring points


TOTALTIM(Function ID: 541001)
Element ID Name Description
8315051E8B TTIM05_EC_F_CS TTIM05 execute command fail condition signal

8215051E84 TTIM05_EC_OK_CS TTIM05 execute command OK condition signal

8A15051E76 TTIM05_SLD_CS TTIM05 selected condition signal

8B15051E7B TTIM05_SLF_CS TTIM05 select fail condition signal

3215051F41 TTIM05_TIM_MIN TTIM05 total time (minutes)

0015051D91 TTIM05_TMP_01 TTIM05 total time change selected signal(stSeld) for SAS

8415061E95 TTIM06_CC_SS TTIM06 cancel success signal

8915061EA2 TTIM06_CTR_SGU TTIM06 control logic stage(under selection)

8315061E8B TTIM06_EC_F_CS TTIM06 execute command fail condition signal

8215061E84 TTIM06_EC_OK_CS TTIM06 execute command OK condition signal

8A15061E76 TTIM06_SLD_CS TTIM06 selected condition signal

8B15061E7B TTIM06_SLF_CS TTIM06 select fail condition signal

3215061F41 TTIM06_TIM_MIN TTIM06 total time (minutes)

0015061D91 TTIM06_TMP_01 TTIM06 total time change selected signal(stSeld) for SAS

8415071E95 TTIM07_CC_SS TTIM07 cancel success signal

8915071EA2 TTIM07_CTR_SGU TTIM07 control logic stage(under selection)

8315071E8B TTIM07_EC_F_CS TTIM07 execute command fail condition signal

8215071E84 TTIM07_EC_OK_CS TTIM07 execute command OK condition signal

8A15071E76 TTIM07_SLD_CS TTIM07 selected condition signal

8B15071E7B TTIM07_SLF_CS TTIM07 select fail condition signal

3215071F41 TTIM07_TIM_MIN TTIM07 total time (minutes)

0015071D91 TTIM07_TMP_01 TTIM07 total time change selected signal(stSeld) for SAS

8415081E95 TTIM08_CC_SS TTIM08 cancel success signal

8915081EA2 TTIM08_CTR_SGU TTIM08 control logic stage(under selection)

8315081E8B TTIM08_EC_F_CS TTIM08 execute command fail condition signal

8215081E84 TTIM08_EC_OK_CS TTIM08 execute command OK condition signal

8A15081E76 TTIM08_SLD_CS TTIM08 selected condition signal

8B15081E7B TTIM08_SLF_CS TTIM08 select fail condition signal

3215081F41 TTIM08_TIM_MIN TTIM08 total time (minutes)

0015081D91 TTIM08_TMP_01 TTIM08 total time change selected signal(stSeld) for SAS

8415091E95 TTIM09_CC_SS TTIM09 cancel success signal

8915091EA2 TTIM09_CTR_SGU TTIM09 control logic stage(under selection)

8315091E8B TTIM09_EC_F_CS TTIM09 execute command fail condition signal

8215091E84 TTIM09_EC_OK_CS TTIM09 execute command OK condition signal

8A15091E76 TTIM09_SLD_CS TTIM09 selected condition signal

8B15091E7B TTIM09_SLF_CS TTIM09 select fail condition signal

3215091F41 TTIM09_TIM_MIN TTIM09 total time (minutes)

0015091D91 TTIM09_TMP_01 TTIM09 total time change selected signal(stSeld) for SAS

84150A1E95 TTIM10_CC_SS TTIM10 cancel success signal

89150A1EA2 TTIM10_CTR_SGU TTIM10 control logic stage(under selection)

83150A1E8B TTIM10_EC_F_CS TTIM10 execute command fail condition signal

82150A1E84 TTIM10_EC_OK_CS TTIM10 execute command OK condition signal

8A150A1E76 TTIM10_SLD_CS TTIM10 selected condition signal

8B150A1E7B TTIM10_SLF_CS TTIM10 select fail condition signal

GRL200 (Soft 033 & 037)


- 789 -
6F2S1914 (0.37)

 Signal monitoring points


TOTALTIM(Function ID: 541001)
Element ID Name Description
32150A1F41 TTIM10_TIM_MIN TTIM10 total time (minutes)

00150A1D91 TTIM10_TMP_01 TTIM10 total time change selected signal(stSeld) for SAS

84150B1E95 TTIM11_CC_SS TTIM11 cancel success signal

89150B1EA2 TTIM11_CTR_SGU TTIM11 control logic stage(under selection)

83150B1E8B TTIM11_EC_F_CS TTIM11 execute command fail condition signal

82150B1E84 TTIM11_EC_OK_CS TTIM11 execute command OK condition signal

8A150B1E76 TTIM11_SLD_CS TTIM11 selected condition signal

8B150B1E7B TTIM11_SLF_CS TTIM11 select fail condition signal

32150B1F41 TTIM11_TIM_MIN TTIM11 total time (minutes)

00150B1D91 TTIM11_TMP_01 TTIM11 total time change selected signal(stSeld) for SAS

84150C1E95 TTIM12_CC_SS TTIM12 cancel success signal

89150C1EA2 TTIM12_CTR_SGU TTIM12 control logic stage(under selection)

83150C1E8B TTIM12_EC_F_CS TTIM12 execute command fail condition signal

82150C1E84 TTIM12_EC_OK_CS TTIM12 execute command OK condition signal

8A150C1E76 TTIM12_SLD_CS TTIM12 selected condition signal

8B150C1E7B TTIM12_SLF_CS TTIM12 select fail condition signal

32150C1F41 TTIM12_TIM_MIN TTIM12 total time (minutes)

00150C1D91 TTIM12_TMP_01 TTIM12 total time change selected signal(stSeld) for SAS

 Connection points in PLC logic


TOTALTIM(Function ID: 541001)
Element ID Name Description
801500ED5A TOTAL00IN_TMP_51 TOTAL00IN_TMP_51

801501EDE0 TOTAL01_PLC_SGNL TOTAL01 plc signal

801502EDE0 TOTAL02_PLC_SGNL TOTAL02 plc signal

801503EDE0 TOTAL03_PLC_SGNL TOTAL03 plc signal

801504EDE0 TOTAL04_PLC_SGNL TOTAL04 plc signal

801505EDE0 TOTAL05_PLC_SGNL TOTAL05 plc signal

801506EDE0 TOTAL06_PLC_SGNL TOTAL06 plc signal

801507EDE0 TOTAL07_PLC_SGNL TOTAL07 plc signal

801508EDE0 TOTAL08_PLC_SGNL TOTAL08 plc signal

801509EDE0 TOTAL09_PLC_SGNL TOTAL09 plc signal

80150AEDE0 TOTAL10_PLC_SGNL TOTAL10 plc signal

80150BEDE0 TOTAL11_PLC_SGNL TOTAL11 plc signal

80150CEDE0 TOTAL12_PLC_SGNL TOTAL12 plc signal

 Mapping point in TTIM01


TOTALTIM (Function ID: 541001)
Element ID Name Description
7015016D08 TOTAL01_CMM_REQ TOTAL01 correction request from cmm

7015026D08 TOTAL02_CMM_REQ TOTAL02 correction request from cmm

7015036D08 TOTAL03_CMM_REQ TOTAL03 correction request from cmm

7015046D08 TOTAL04_CMM_REQ TOTAL04 correction request from cmm

7015056D08 TOTAL05_CMM_REQ TOTAL05 correction request from cmm

GRL200 (Soft 033 & 037)


- 790 -
6F2S1914 (0.37)

 Mapping point in TTIM01


TOTALTIM (Function ID: 541001)
Element ID Name Description
7015066D08 TOTAL06_CMM_REQ TOTAL06 correction request from cmm

7015076D08 TOTAL07_CMM_REQ TOTAL07 correction request from cmm

7015086D08 TOTAL08_CMM_REQ TOTAL08 correction request from cmm

7015096D08 TOTAL09_CMM_REQ TOTAL09 correction request from cmm

70150A6D08 TOTAL10_CMM_REQ TOTAL10 correction request from cmm

70150B6D08 TOTAL11_CMM_REQ TOTAL11 correction request from cmm

70150C6D08 TOTAL12_CMM_REQ TOTAL12 correction request from cmm

GRL200 (Soft 033 & 037)


- 791 -
6F2S1914 (0.37)

Synchronizing check for different network (SYNDIF)


The Synchronizing check function (SYNCHK) is provided for checking for the presence of
voltage or the voltage/frequency-variance when connection between two parts of a network is
required. The SYNCHK function is of benefit where the “Double position controller with
synchronizing-check (DPSY†)” function is used for connection between two parts of a network.
This is because operation of the DPSY function to close the circuit breaker is inhibited until
the SYNCHK function gives permission. The SYNCHK function is made up of two group
functions (SYNCHK01 and SYNCHK02‡). The group function consists of two logic elements:
the former part is to check for the voltage-presence (or absence) on an incoming line and a
running line; the latter part is to check the synchronizing condition between two energized
lines.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features depends on the selection of hardware and the
configuration of functions. Several IED models do not have its features. To determine whether
its features are implemented in the IED, locate the IED ordering number; and check the order
number at the “G&T position” referring to the comparison table below. For more information,
see Appendix: Ordering.
Table 4.6-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
– Number of functions – 2
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 792 -
6F2S1914 (0.37)

The SYNCHK_RY function consists of several over-voltage and under-voltage and


synchronizing relays (OV, UV, and SyncRys) integrated within the synchronization check
feature (SYNCHK). The SYNCHK function issues permissive signals to the DPSY functions;
hence, ensuring that the DPSY functions are only able to close the CB when the required
conditions for closure have been satisfied.
SYNCHK_Ry: SYNCHK; Function
Function ID: 561001 ID: 560001

OVr relay (59r) for running line Verification of voltage Permission signal
conditions and issued to DPSY
OVi relay (59i) for incoming line synchronization between logics

UVr relay (27r) for running line networks

UVi relay (27i) for incoming line


SyncRy (ΔV)
SyncRy (Δθ)
DPSY function†
SyncRy (Δf)
SyncRy (θ≈0)

Issue CB closing
command

Figure Outline of SYNCHK function


†Note:The DPSY function is discussed separately. See Chapter Control and monitoring
application: Double position controller with synchronizing-check.
‡Note:To simplify the description, only the SYNCHK1 (SYNCHK_Ry1) function is
discussed; however, the same description is applicable to the SYNCHK2
(SYNCHK_Ry2) function. The user should read the expression for SYNCHK1 as
SYNCHK2 unless a special explanation or instruction has been provided (e.g., the
user can reason by analogy that the feature in the OVr2 relay is identical to the
OVr1 relay).

4.6.1 Relays to check line-outage


The voltage condition for either line being out of service or being in service is verified using OV
and UV relays in the SYNCHK_Ry1 function.

Table 4.6-2 Settings in SYNCHK_Ry1


Setting Name Description Default Range
OVR1 Checking Live-Running Voltage 51V 10 to 150 V
UVR1 Checking Dead-Running Voltage 13V 10 to 150 V
OVI1 Checking Live-Incoming Voltage 51V 10 to 150 V
UVI1 Checking Dead-Incoming Voltage 13V 10 to 150 V

(i) Overvoltage-relay elements (OVr1, OVi1)


Two overvoltage-relay elements (OVr1 and OVi1) are provided to determine the voltage
presence between running and incoming lines. In Figure 4.6-1 the hatched area depicts the

GRL200 (Soft 033 & 037)


- 793 -
6F2S1914 (0.37)

operating area of OV characteristic. The OVr1 element is used to check for the presence of
voltage on the running-line; similarly, the OVi1 element is used to check for the presence of
voltage on the incoming-line. The user can set pick-up thresholds using the settings [OVR1]
and [OVI1].

Vr†, Vi‡

0 V

Pickup Voltage

Figure 4.6-1 Characteristics of OVr1 and OVi1

(ii) Undervoltage-relay elements (UVr1, UVi1)


Two undervoltage-relay elements (UVr1 and UVi1) are provided to determine the absence of
voltage on the running and incoming lines. In Figure 4.6-2 the hatched area depicts the
operating area of the UV characteristic. The UVr1 element is used to check for the absence of
voltage on the running-line; similarly, the UVi1 element is used to check for the absence of
voltage on the incoming-line. The user can set drop-off thresholds using the settings [UVR1]
and [UVI1].

Vr†, Vi‡

0 V

Drop-off Voltage

Figure 4.6-2 Characteristics of UVr1 and UVi1


†Note: Settings [OVR1] and [UVR1] are applied for the measurement of voltage on the
running line (Vr).
‡Note: Settings [OVI1] and [UVI1] are applied for the measurement of voltage on the
incoming line (Vi).

GRL200 (Soft 033 & 037)


- 794 -
6F2S1914 (0.37)

4.6.2 Synchronization check relays


Figure 4.6-3 shows the variance of voltages, phase-angles and frequencies for Vr and Vi.

Settings [OVR1]
and [OVI1]

Setting [SyncRy1-Angle]

Vi
Δ

Vr

V

Setting [SyncRy1-dV]

Figure 4.6-3 Permissible ranges for connections between synchronous networks

The provision of a signal for CB closure between two networks may be required subject
to the variance of the two voltages, phase-angles and frequencies being small. Therefore, the
SYNCHK function continuously monitors the Δθ, ΔV and Δf; subsequently the SYNCHK
function issues an operate-permission signal to the DPSY function when the variance is less
than the permissible range. For this purpose, synchronism-relays (SyncRy1-dV, SyncRy1-df,
SyncRy1-dθ) are provided; the user can set them in accordance with their specific requirements.

Figure 4.6-4 shows the angle-variance between Vi and Vr; the increment or decrement of
the angle-variance (Δθ) is shown based upon the running voltage Vr.

When connection between asynchronous networks is required, the split-synchronism-


check elements (SyncRy-θ=0 and SyncRy-θless) are used so that the connection will be
performed when the angle-variance Δθ is small.

GRL200 (Soft 033 & 037)


- 795 -
6F2S1914 (0.37)

Δ increasing

Vi

Vi‡ Δ reducing

Δ near
Vi zero

Δ Vi
Vr†

Figure 4.6-4 Permissible ranges for connections between asynchronous networks


†Note: Vr is the voltage on a running line.
‡Note: Vi is the voltage on an incoming line.

Table 4.6-3 Settings in SYNCHK_Ry1


Setting Name Description Default Setting item or value
SyncRy1-Angle Checking angle variance 30 degrees 0 to 75 degrees
SyncRy1-dV Checking voltage variance 150V 0 to 150 V
SyncRy1-df Checking frequency variance 1Hz 0.01 to 2 Hz
SyncRy1-TCB Advance time for SYNCHK01 – Seconds
SYNC01_TSYN Sync check timer for loop system 10s 0.00 to 100.00 s
SyncRy1-dfEN Diff. frequency for the checking SyncRy1 enable Off Off / On

(i) Synchronism-relays (SyncRy1-dV, SyncRy1-df, SyncRy1-dθ)


Synchronism-relays, SyncRy1-dV, SyncRy1-df, and SyncRy1-dθ are provided; the setting
ranges for these relays are shown in Table 4.6-3.

Voltage-variance (ΔV) (see Figure 4.6-3)


The voltage-variance between Vr and Vi (|𝑉𝑟 − 𝑉𝑖 |) is measured by the voltage-variance relay-
element having a setting [SyncRy1-dV]. If equation (4.6-3) is satisfied together with the
conditions stipulated in equations (4.6-2) and (4.6-3), the SyncRy1-dV relay determines that
the voltage-variance is inside the permissible range.

𝑉r ≥ Setting [OVR1] (4.6-1)

𝑉i ≥ Setting [OVI1] (4.6-2)

|𝑉𝑟 − 𝑉𝑖 | ≤ Setting [SyncRy1-dV] (4.6-3)

GRL200 (Soft 033 & 037)


- 796 -
6F2S1914 (0.37)

Phase-angle variance (Δθ) (see Figure 4.6-4)


The phase-angle variance of Vr and Vi (Δθ) is measured by the phase-angle variance-relay
having the setting [SyncRy1-Angle]. If the following equations are satisfied, the SyncRy1-
Angle relay determines that the phase-angle variance is inside the permissible range.

Vr × Vi cos ∆θ > 0 (4.6-4)

Vr × Vi sin(setting[SyncRy1-Angle]) ≥ Vr × Vi sin ∆θ (4.6-5)

Frequency-variance (Δf)
The frequency-variance of Vr and Vi (Δf) is measured by the frequency-variance relay having
the setting [SyncRy1-df]. If the following equations are satisfied, the SyncRy1-df relay
determines that the frequency-variance is inside the permissible range.

∆f = |fVi − fVr | ≤ setting [SyncRy1-df] (4.6-6)

where,
fVr Frequency of Vr
fVi Frequency of Vi
Δf Frequency-variance between Vr and Vi

Notice and tips


If the frequency-variance between the Vr and the Vi is shown very large, the SYNCHK may
fail to make the decision of the synchronism, although Off is set for the setting [SyncRy1-dfEN]
to abandon to checking the frequency-variance. This is because; the vector passes the [SyncR1-
Angle] zone very quickly. As a result, the SYNCHK relay may fail to issue the permission
command. To avoid the failure, the user has to set values for settings [SyncR1-Angle] and
[SYNC01_TSYN] depending on the assumed frequency-variance (Δf):

Setting [SyncR1-Angle]
∆f > (4.6-7)
180° × Setting [SYNC01_TSYN]

where,
Δf= Frequency-variance (or cycle-slip in Hertz)

Tips: Cycles for the synchronism closure can be calculated:

Cycle for synchronism = 1⁄∆f[Hz] (4.6-8)

Time length for getting a synchronism:

GRL200 (Soft 033 & 037)


- 797 -
6F2S1914 (0.37)

2 × Setting [SyncR1-Angle] 1
Time = × (4.6-9)
360° ∆f[Hz]

Check time for the synchronism:

2 × Setting [SyncR1-Angle] 1
Setting [SYNC01_TSYN] < × (4.6-10)
360° ∆f[Hz]

Equations rearrangements:

Setting [SyncR1-Angle] 1
Setting [SYNC01_TSYN] < × (4.6-11)
180° ∆f[Hz]

1 𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [SYNC01_TSYN] 1
> ÷ (4.6-12)
∆𝑓[𝐻𝑧] Setting [SyncR1-Angle] 180°

𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [SyncR1-Angle] 1
𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [SYNC01_TSYN] < × (4.6-13)
180° ∆𝑓[𝐻𝑧]

Vr :Frequency: f1

Vi :Frequency: f2

time

Δf Δf Δf

Example: Δf= f1–f2 = 50.02Hz–50.00Hz=0.02Hz=50s

Vi

50s SyncR1-Angle

Vr Synchronism zone

Figure 4.6-5 Synchronism between Vi and Vr when system frequency = 50Hz

GRL200 (Soft 033 & 037)


- 798 -
6F2S1914 (0.37)

(ii) Split-synchronism-check element (SyncRy1-θ=0, SyncRy1-θless)


With regard to the connection of asynchronous networks, it is necessary to use the technique
of split synchronism to avoid the occurrence of cycle-slip on the system. The technique consists
of three parts: (1) calculation of the synchronization point (SyncRy1-θ=0), (2) check for slip
cycle (SyncRy1-θless), and (3) advance time for issuing the closure command.

Calculation of synchronization point


Issuing a closure command for the CB is appropriate when the variance of Vr and Vi is
small. Hence, the timing of when it should be issued is calculated in the SyncRy1-θ=0 element
so that the prediction of coincident timing between the running, (Vr) and the incoming, (Vi)
voltages can be introduced. Figure 4.6-6(c) shows the coincident point (zero point).

Check for slip cycle


Checking the decrease in Δθ is a suitable means for controlling the issue of a closure command
to a CB at the requisite timing. The SyncRy1-θless element calculates the for reducing Δθ; it
assists in the computation of the SyncRy1-θ=0 element.

Advance time
The user shall consider the actual device operation time. For an asynchronous network, the
issue of the CB closure command should be initiated such that it is coordinated with the actual
closing. Figure 4.6-6 shows the advancing time; it is introduced with setting [SyncRy1-TCB],
closing time (Tcb) and compensation time:

Setting[SyncRy1-TCB] = α + TCB + 𝛽 (4.6-14)

where,
α: Operation time of the element
β: Compensation (i.e., tolerance) time
Tcb: Closing time of CB

GRL200 (Soft 033 & 037)


- 799 -
6F2S1914 (0.37)

Vr

Vi

(b) Incoming voltage (Vi)

Vr − Vi

Zero point (Δθ=0)


Advance time

(c) Beat wave provided by Vr + Vi

Δθ
Start to close CB

End of closing CB

Time
α TCB β

Setting

CB closing command
Tolerance for synchronism
CB contact

Zero point (Δθ=0)


CB closed point
CB closing command issued

(d) Advance time and CB closing command

Figure 4.6-6 Advance time to close CB for an asynchronous system

GRL200 (Soft 033 & 037)


- 800 -
6F2S1914 (0.37)

4.6.3 Line-outage check


(i) Voltage conditions
In the SYNCHK function the OVr, OVi, UVr, and UVi elements are used to verify the line-
condition. For example, when the user wishes to connect an incoming-line (i.e., transmission
line) with the running-line (i.e., a busbar), the voltage conditions on either lines may be
examined prior to connection. Alternatively, the absence of voltage on both lines may be
required before connection. In order to provide this functionality, the SYNCHK function has
four check zones to test for the line being either in-service or out-of-service; the four zones are
illustrated in Figure 4.6-7.
Vi on the incoming line

DRLI LRLI
Setting [OVI1]

Setting [UVI1]
DRDI LRDI
Vr on the running line
Setting [UVR1] Setting [OVR1]

Figure 4.6-7 Four voltage conditions examined in SYNCHK_Ry1

For example, “DRLI” zone covers the case when the running-line is out-of-service (DR)
and the incoming-line is in-service (LI). Table 4.6-4 exemplifies the areas in accordance with
the voltage conditions.
Table 4.6-4 Four voltage conditions and zones
Voltage condition 1 2 3 4

Area D○
R L○
I L○
R L○
I D○
R D○
I L○
R D○
I


R unning line (Vr) (Dead) (Live) (Dead) (Live)


I ncoming line (Vi) (Live) (Live) (Dead) (Dead)

Figure 4.6-8 and Figure 4.6-9 show the voltage-presence (or voltage-absence) check logic
used in the SYNCHK_Ry1 and Ry2 functions.

GRL200 (Soft 033 & 037)


- 801 -
6F2S1914 (0.37)

OVR1 561001 8201001B62 To SYNCHK


59r &
LDLI1: Both Running-line and Incoming-line in-service

UVR1 561001 8001001B63


27r & LRDI1: Running-line in service & Incoming-line out-of-service

OVI1 561001 8301001B60


59i
&
DRLI1: Running-line out-of-service & Incoming-line in-service
561001 8101001B61
UVI1
27i &
DRDI1: Both Running-line and Incoming-line out-of-service

Figure 4.6-8 Line-outage check logic in SYNCHK_Ry1


OVR2 561001 8202001B62 To SYNCHK
59r &
LDLI2: Both Running-line and Incoming-line in-service

UVR2 561001 8002001B63


27r & LRDI2: Running-line in service & Incoming-line out-of-service

OVI2 561001 8302001B60


59i
&
DRLI2: Running-line out-of-service & Incoming-line in-service
561001 8102001B61
UVI2
27i &
DRDI2: Both Running-line and Incoming-line out-of-service

Figure 4.6-9 Line-outage check logic in SYNCHK_Ry2

Table 4.6-5 Voltage condition settings in SYNCHK1


Setting Name Description Default Setting item or value
SYNC01_TLRDIDRLI Voltage check timer (LRDI, DRLI) 5s 0.00 to 5.00s
SYNC01_TDRDI Voltage check timer (DRDI) 5s 0.00 to 5.00s
SYNC01_LRDIEN CB close enable for LRDI On Off/On
SYNC01_DRLIEN CB close enable for DRLI On Off/On
SYNC01_DRDIEN CB close enable for DRDI On Off/On

(ii) Check logic and settings


Figure 4.6-10 shows the SYNCHK1 logic. When the DPSY01 function confirms the reception
of a selection-command, the DPSY01 function issues a “DPSY01_OSE_RCV” signal to the
SYNCHK1 function. Then the SYNCHK1 function commences with the check for the voltage
condition by introducing the results of the SYNCHK_Ry function. As described previously, four
voltage conditions are considered, the user should select the voltage-conditions required by the
application. The SYNCHK1 logic provides two permissive signals: “SYNC01_SLD_VCS” signal
and “SYNC01_SYN_CLC” signal.

GRL200 (Soft 033 & 037)


- 802 -
6F2S1914 (0.37)

Input SYNCHK logic in SYNCHK1 Output

DPSY01 (Function ID: 511001)


From DPSY01

511001 8002011E45
Close command (Select)
DPSY01_OSE_RCV

SYNCHK_Ry (Function ID: 561001)


From SYNCHK_Ry1
i LRLI1
&
DRLI1 LRLI1
OVi LRDI1
&

DRLI1
UVi &
DRDI1 LRDI1 SYNCHK1 (Function ID: 560001)

UVr OVr r DRDI1


& SYNC01_SCK_CS05
SYNC01_SCK_CS11
560001 880B011F63
From SYNCHK_Ry2 560001 820B011F69 0.5s
t 0 To DPSY01
i LRLI2
& ≥ & & ≥
SYNC01_SCK_CS06 SYNC01_SCK_CS12
DRLI2 LRLI2 560001 890B011F64 560001 830B011F6A 560001 840B011F58
OVi LRDI2 SYNC01_TLRDIDRLI
& ≥ & & t 0
SYNC01_SCK_CS07 SYNC01_SCK_CS13 SYNC01_SLD_VCS
560001 8A0B011F65 560001 840B011F6B
Select permission
UVi
DRLI2
& ≥ & t 0

DRDI2 LRDI2 SYNC01_SCK_CS08


&
560001 8B0B011F66 SYNC01_SCK_CS14 0.0 to 0.5s
r DRDI2 560001 850B011F6C SYNC01_TLRDIDRLI
UVr OVr
& ≥ & t 0
&
PLC signals for relay selection relating to SYNCHK1 0.0 to 0.5s

560001 800B01EDED SYNC01_RY1_USE_STS

560001 800B01EDEE SYNC01_RY2_USE_STS



PLC signals importation from external conditions
560001 850B011F59
560001 800B01EDEA SYNC01_DDV_CL_ECP
SYNC01_SYN_CLC
560001 800B01EDE9 SYNC01_DLV_CL_ECP
Operate permission

560001 800B01EDE8 SYNC01_LDV_CL_ECP

560001 800B01EDE7 SYNC01_LLV_CL_ECP


Bypassing condition
560001 800B01EDEC SYNC01_SS_VCS_PLC

On
SYNC01-LRDIEN

On
SYNC01-DRLIEN
On

SYNC01-DRDIEN

Figure 4.6-10 Voltage-condition check logic in SYNCHK1

GRL200 (Soft 033 & 037)


- 803 -
6F2S1914 (0.37)

Input SYNCHK2 logic Output

DPSY02 (Function ID: 511001)


From DPSY02

511001 8002021E45

Close command (Select)


DPSY02_OSE_RCV

SYNCHK_Ry (Function ID: 561001)


From SYNCHK_Ry1
i LRLI1
&
DRLI1 LRLI1
OVi LRDI1
&

DRLI1
UVi &
DRDI1 LRDI1 SYNCHK2 (Function ID: 560001)

UVr OVr r DRDI1


& SYNC02_SCK_CS05
SYNC02_SCK_CS11
560001 880B021F63
From SYNCHK_Ry2 560001 820B021F69 0.5s
t 0 To DPSY02
i LRLI2
& ≥ & SYNC02_SCK_CS06
& ≥
SYNC02_SCK_CS12
DRLI2 LRLI2 560001 890B021F64 560001 830B021F6A 560001 840B021F58
OVi LRDI2 SYNC02_TLRDIDRLI
& ≥ & & t 0
SYNC02_SCK_CS07 SYNC02_SCK_CS13 SYNC02_SLD_VCS
560001 8A0B021F65 560001 840B021F6B Select permission
t 0
UVi
DRLI2
& ≥ &
DRDI2 LRDI2 & 0.0 to 0.5s
SYNC02_SCK_CS08 SYNC02_SCK_CS14
r DRDI2 560001 8B0B021F66 560001 850B021F6C SYNC02_TLRDIDRLI
UVr OVr
& ≥ & t 0
&
PLC signals for relay selection relating to SYNCHK2 0.0 to 0.5s

560001 800B02EDED SYNC02_RY1_USE_STS

560001 800B02EDEE SYNC02_RY2_USE_STS

PLC signals importation from external conditions ≥


560001 800B02EDEA SYNC02_DDV_CL_ECP 560001 850B021F59

560001 800B02EDE9 SYNC02_DLV_CL_ECP SYNC02_SYN_CLC


Operate permission
560001 800B02EDE8 SYNC02_LDV_CL_ECP

560001 800B02EDE7 SYNC02_LLV_CL_ECP


Bypassing condition
560001 800B02EDEC SYNC02_SS_VCS_PLC

On
SYNC02-LRDIEN

On
SYNC02-DRLIEN
On

SYNC02-DRDIEN

Figure 4.6-11 Voltage-condition check logic in SYNCHK2

GRL200 (Soft 033 & 037)


- 804 -
6F2S1914 (0.37)

Permission signal “SYNC01_SLD_VCS”†


The “SYNC01_SLD_VCS” signal is transferred to the DPSY01 select-logic. For example,
suppose the DPSY01 function is given permission to operate when any voltage-condition is
satisfied, then the user should set On for the scheme switches [SYNCHK01-LRDIEN],
[SYNCHK01-DRLIEN], and [SYNCHK01-DRDIEN].

For example, if the DPSY01 function is required to operate when the voltage condition
“LRDI” is confirmed (Table 4.6-4.(4)), just set On for the scheme switch [SYNCHK01-LRDIEN].

User programmable pick-up delay timers are available for the conditions “LRDI” and
“DRLI” (Table 4.6-4.(1 and 4)); hence the user can set a desired value for the setting
[SYNC01_TLRDIDRLI]; similarly, a desired value can be applied for the setting
[SYNC01_TDRDI] for the condition “DRDI” (Table 4.6-4.(3)).
†Note:This signal is required for CB closing in the select logic. For more information, see
separate section DPSY: Control logics.

Permission signal “SYNC01_SYN_CLC”‡


The “SYNC01_SYN_CLC” signal is input to the DPSY01 operate-closing-logic as a permissive
signal. The DPSY01 function is allowed to operate when any voltage-conditions except “LRLI”
is satisfied in the DPSY01 operation.
‡Note:This signal is required only for CB closing in the operate-closing logic. For more
information, see separate section DPSY: Operate logics.

(iii) Adding other voltage-conditions using PLC signals


The user can add a user-preferred condition to the logic signal using PLC connection points.
In the SYNCHK1 logic, points “SYNC01_LLV_CL_ECP, _LDV_CL_ECP, _DLV_CL_ECP, and
_DDV_CL_ECP” are provided†. Similarly, points “SYNC02_LLV_CL_ECP, _LDV_CL_ECP,
_DLV_CL_ECP, and _DDV_CL_ECP” are provided in the SYNCHK2 function.
†Note:For more information on PLC programing, see chapter PLC function, separately.

(iv) Relay selection using PLC signals


Either SYNCHK_Ry1 or SYNCHK_Ry2 function can be chosen for SYNCHK1 operation. On
this account, points “SYNC01_RY1_USE_STS and _RY2_USE_STS” are provided and the user
can choose either for use in conjunction with SYNCHK1 operation; similarly,
“SYNC02_RY1_USE_STS and _RY2_USE_STS” are provided for SYNCHK2 operation. The
purpose of the choice is discussed in section 4.6.5.

GRL200 (Soft 033 & 037)


- 805 -
6F2S1914 (0.37)

4.6.4 Synchronization check


The user should set On for scheme switch [SYNC01-SYNCHK1EN] when synchronization check
is required.

(i) Synchronization conditions


The synchronizing relays are used to check the respective conditions of the incoming-line and
the running-line. For example, the ∆V, ∆θ, and ∆f variances of Vi and Vr may be examined
when the SYNCHK function is used in a synchronous network. Conversely, the ∆θ reducing-
degree feature can be applied for asynchronous networks; the SYNCHK function can use
signals ‘∆θ1≈0’ and ‘∆θ1_less’ in order to decide whether the difference-angle is reducing. Thus,
the SYNCHK function is required to have two sets of check logic covering both (1) synchronous
conditions and (2) asynchronous conditions.
56001 8501001B65 To check for Synchronous network
SyncRy1
-dV ΔV1: Voltage-variance of Running and Incoming

SyncRy1 56001 8601001B65


-df Δf1: Frequency-variance of Running and Incoming

SyncRy1 56001 8401001B64


-dƟ ΔƟ1: Phase-variance of Running and Incoming

To check for Asynchronous network


SyncRy1 56001 8701001B6A
-Ɵ≈0 ΔƟ1≈0: Phase-variance being near zero between Running and Incoming

SyncRy1 56001 8801001B6B


-Ɵ less ΔƟ1 less: Reducing in phase-valiance

Figure 4.6-12 Synchronization check relays in SYNCHK_Ry1

561001 8502001B65 To check for Synchronous network


SyncRy2
-dV ΔV2: Voltage-variance of Running and Incoming

561001 8602001B66
SyncRy2
-df Δf2: Frequency-variance of Running and Incoming

561001 8402001B64
SyncRy2
-dƟ ΔƟ2: Phase-variance of Running and Incoming

561001 8702001B6A To check for Asynchronous network


SyncRy2
-Ɵ≈0 ΔƟ2≈0: Phase-variance being near zero between Running and Incoming

SyncRy2 561001 8802001B6B


-Ɵ less ΔƟ2 less: Reducing in phase-valiance

Figure 4.6-13 Synchronization check relays in SYNCHK_Ry2

Figure 4.6-14 shows the synchronization check logic in the SYNCHK1 function. The user
should note that the logic has been separated for (1) the synchronous condition and (2) the
asynchronous condition; the synchronization check logic is initiated when the
“DPSY01_OEC_RCV” signal is received, which is identical to an operate-command in the On-
direction.

GRL200 (Soft 033 & 037)


- 806 -
6F2S1914 (0.37)

Table 4.6-6 Synchronization settings in SYNCHK1


Setting Name Description Default Setting item or value
SYNC01_SYNCHK1EN SYNCHK1 synchronization checking enable Off On / Off
Synchronism check timer for synchronous
SYNC01_TSYN 10s 0.00–100.00s
system
SYNC01_TSYN2 Timer to give up the synchronization 60s 30.0–1800.0s
SYNC01_Split_EN SYNCHK1 async. checking enable Off Off/On
SYNC01_SYNCTEST Test in SYNCHK1 synchronism check Off Off/On

Input SYNCHK logic in SYNCHK1 Output

DPSY01 (Function ID: 511001)


From DPSY01
511001 8B02011E48

Close command (Operate)


DPSY01_OEC_RCV

SYNCHK1 (Function ID: 560001)


From SYNCHK1
560001 850B011F59

SYNC01_SYN_CLC

SYNCHK_Ry (Function ID: 561001)


From SYNCHK_Ry1

SyncRy1-dV ΔV1 SYNCHK1 (Function ID: 560001)


& SYNC01_SCK_CS16
On 560001 880B011F6E
SyncRy1-df Δf1
SYNC01_TSYN2 SYNC01_SCK_CS01
SyncRy1-dfEN & t 0 560001 840B011F5F 560001 820B011F56
SyncRy1-dƟ ΔƟ1 &
& 1 0.0 to 1800.0s
&
SYNC01_SCL_F
SyncRy1-Ɵ≈0 ΔƟ1≈0
& Sync Failed
SyncRy1-Ɵ less ΔƟ1 less Check for synchronous network
&
SYNC01_SCK_CS04
From SYNCHK_Ry2 560001 870B011F62 SYNC01_SCK_CS09
560001 8C0B011F67 SYNC01_LPS_CLC
& 560001 840B011F58 ≥
SyncRy2-dV ΔV2 & SYNC01_SCK_CS03 To DPSY01
On
& ≥ 560001 860B011F61
SYNC01_TSYN
t 0
SyncRy2-df Δf2 560001 850B011F59
SyncRy2-dfEN & ≥ & 0.0 to 100.0s
SYNC01_SCK_CS02 SYNC01_SYN_CLC
ΔƟ2
SyncRy2-dƟ
& ≥ 560001 850B011F60 Sync success
SyncRy2-Ɵ≈0 ΔƟ2≈0
&
&
SyncRy2-Ɵ less ΔƟ2 less
&
Check for asynchronous network
SYNC01_SPS_CLC
SYNC01_Ry_Ang_0Time 1 & 560001 8D0B011F51
560001 870B011F77
PLC signals for relay selection relating to SYNCHK1
&
560001 800B01EDED SYNC01_RY1_USE_STS ≥ SYNC01_Ry_Ang_RDC
560001 880B011F78
≥ &
560001 800B01EDEE SYNC01_RY2_USE_STS

PLC signals importation from external conditions On

560001 800B01EDE2 SYNC01_SCL_F_ECP SYNC01-Split_SYN_EN

560001 800B01EDE6 SYNC01_LPS_CL_ECP

560001 800B01EDE5 SYNC01_SPS_CL_ECP 560001 800B011F54

Off SYNC01_SBP
560001 800B01EDE1 SYNC01_SBP_SSP Bypassing condition
SYNC01-SYNCHK1EN Sync bypass

Figure 4.6-14 Synchronization check logic in SYNCHK1

GRL200 (Soft 033 & 037)


- 807 -
6F2S1914 (0.37)

Input SYNCHK logic in SYNCHK2 Output

DPSY01 (Function ID: 511001)


From DPSY02
511001 8B02021E48

DPSY02_OEC_RCV Close command (Operate)

SYNCHK2 (Function ID: 560001)


From SYNCHK2
560001 850B021F59

SYNC02_SYN_CLC

SYNCHK_Ry (Function ID: 561001)


From SYNCHK_Ry1

SyncRy1-dV ΔV1 SYNCHK2 (Function ID: 560001) SYNC02_SCK_CS16


& 560001 880B021F6E
On
SyncRy1-df Δf1
SyncRy1-dfEN & SYNC02_TSYN2
SYNC02_SCK_CS01
t 0
560001 840B021F5F 560001 820B021F56
SyncRy1-dƟ ΔƟ1 &
& 1 0.0 to 1800.0s
&
SYNC02_SCL_F
SyncRy1-Ɵ≈0 ΔƟ1≈0
& Sync Failed
SyncRy1-Ɵ less ΔƟ1 less Check for synchronous network
&
SYNC02_SCK_CS04
From SYNCHK_Ry2 560001 870B021F62 SYNC02_SCK_CS09
SYNC02_LPS_CLC
& 560001 8C0B021F67
560001 890B021F53 ≥
SyncRy2-dV ΔV2 & SYNC02_SCK_CS03 To DPSY02
& ≥ 560001 860B021F61
SYNC02_TSYN
t 0
On 560001 850B021F59
SyncRy2-df Δf2
SyncRy2-dfEN & ≥ & SYNC02_SCK_CS02
0.0 to 100.0s SYNC02_SYN_CLC
ΔƟ2
SyncRy2-dƟ
& ≥ 560001 850B021F60 Sync success
SyncRy2-Ɵ≈0 ΔƟ2≈0
&
&
SyncRy2-Ɵ less ΔƟ2 less
&
Check for asynchronous network
SYNC02_SPS_CLC
SYNC02_Ry_Ang_0Time 1 & 5600018 D0B021F51
560001 870B021F77
PLC signals for relay selection relating to SYNCHK2
&
560001 800B02EDED SYNC02_RY1_USE_STS ≥ SYNC02_Ry_Ang_RDC
560001 880B021F78
≥ &
560001 800B02EDEE SYNC02_RY2_USE_STS

PLC signals importation from external conditions On


560001 800B02EDE2 SYNC02_SCL_F_ECP SYNC02-Split_SYN_EN

560001 800B02EDE6 SYNC02_LPS_CL_ECP

560001 800B021F54
560001 800B02EDE5 SYNC02_SPS_CL_ECP
Off SYNC02_SBP
SYNC02-SYNCHK2EN Sync bypass
560001 800B02EDE1 SYNC02_SBP_SSP Bypassing condition

Figure 4.6-15 Synchronization check logic in SYNCHK2

(ii) Check logic and settings for synchronous network


As shown in Figure 4.6-14, the ∆V, ∆θ, and ∆f signals are required to check the synchronous
condition; the three signals are input to the logic. The sync-success signal “SYNC01_SYN_CLC”
is provided after the operation of the delay timer “SYNC01_TSYN”. The user can regulate the
timer using the setting [SYNC01_TSYN].

(iii) Check logic and settings for asynchronous network


In Figure 4.6-14, the ‘∆θ1≈0’ and ‘∆θ1_less’ signals are used to check the synchronization
condition when the user sets On for scheme switch [SYNC01-Split_SYN_EN]; subsequently
sequentially the sync-success signal “SYNC01_SYN_CLC” is issued for the DPSY01 function.

(iv) Bypassing synchronization check


If the user wishes to remove the synchronization check, set Off for the scheme switch [SYNC01-
SYNCHK1EN]. The DPSY01 function can operate with the absence of the sync-success signal
“SYNC01_SYN_CLC”.

GRL200 (Soft 033 & 037)


- 808 -
6F2S1914 (0.37)

(v) Unsuccessful synchronization check


If the injected signal “DPSY01_OEC_RCV” persists for longer than a pre-determined time, the
check logic determines that synchronization has not occurred; hence, the check logic can issue
a failure signal for the DPSY01 function. Consequently, the DPSY01 function abandons the
attempt to close the CB due to the failure in the synchronization process. The user can set the
time using the setting [SYNC01_TSYN2].

(vi) Adding other sync-conditions using PLC signals


When required, a user-preferred sync-condition can be added to the SYNCHK function using
the PLC connection points. For the SYNCHK1 logic, points “SYNC01_SCL_F_ECP,
_LPS_CL_ECP, and _SPS_CL_ECP” are provided. Similar points are also provided in the
SYNCHK2 function.

(vii) Relay selection using PLC signals


As described in 4.6.3(iv), either the SYNCHK_Ry1 or SYNCHK_Ry2 function can be chosen for
check synchronization in addition to checking the voltage condition. For the purpose of the
choice provided, see section 4.6.5.

(viii) Synchronization logic test


When required, a hypothetical sync-success signal can be issued for testing, the user can set
On for the scheme switch [SYNC01_SYNCTEST]. Note that Off should be set for the scheme
switch after testing.

GRL200 (Soft 033 & 037)


- 809 -
6F2S1914 (0.37)

4.6.5 Relay selection for checking synchronization


Figure 4.6-16 exemplifies a bus-bar arrangement used as an example for check synchronization.
In this example, the SYNCHK_Ry1 relays require the voltage signals† V3, V4, and V1. This is
because DS1 and DS3 are closed, but DS2 is open; the selection of SYNCHK_Ry1 is initiated
by the reception of the “SYNCHK_Ry1_selection” signal. The “SYNCHK_Ry1_selection” and
“SYNCHK_Ry2_selection” signals are generated by logic programmed by the user; hence, here
the signal “SYNCHK_Ry1_selection” is connected with the PLC connection point
“SYNC01_RY1_USE_STS”‡.

Running
Busbar#1 ✔Selection of SYNCHK_Ry1
Busbar#2 DS1 closed SYNCHK_Ry1_selection
&
line
✔ SYNC01_RY1_USE_STS ✔
DS1 DS2 DS3 closed

V3 V4

DS1 open & Selection of SYNCHK_Ry2


CB1
& SYNCHK_Ry2_selection
DS2 closed
Incoming DS3 SYNC01_RY1_USE_STS
line DS3 closed

V1
Relay selection logic programmed by the user
SYNCHK01 function
using the PLC function


Ry2
Ry1 Line

Figure 4.6-16 Relay-selection-signal provided by DPSY function (an example)


†Note:The relationship between the injected voltage-signals and the SYNCHK_Ry
function is discussed in section 4.6.6.
‡Note:The user should also connect the “SYNCHK_Ry2_selection” signal with the PLC
connection point “SYNC01_RY2_USE_STS”. Users should note that Figure 4.6-16
is provided for explanation/information; the user is required to program relay-
selection logic using the PLC function that responds dynamically to configuration
changes that occur as a consequence of CB and DS operations.

In Figure 4.6-16 , two signals are used for relay selection, but the user should note that
the selection-signals are provided in accordance with the actual line and bus-bar arrangement.
Figure 4.6-17 shows the overall logic used for the selection. The user can program the selection-
signals using the PLC function.

GRL200 (Soft 033 & 037)


- 810 -
6F2S1914 (0.37)

SYNCHK_Ry (Function ID: 561001)


SYNCHK_Ry1
SyncRy1-dV ΔV1
&
SyncRy1-df Δf1
&
SyncRy1-dƟ ΔƟ1
&
SyncRy1-Ɵ≈0 ΔƟ1≈0
&
SyncRy1-Ɵ less ΔƟ1 less
&
SYNCHK_Ry (Function ID: 561001) ≥
SYNCHK_Ry2
SyncRy2-dV ΔV2 To DPSY01
& ≥ 560001 850B011F59
SyncRy2-df Δf2
&
SYNC01_SYN_CLC
SyncRy2-dƟ ΔƟ2
& ≥ SYNCHK1 Sync success
(Function ID: 560001)
SyncRy2-Ɵ≈0 ΔƟ2≈0
&
SyncRy2-Ɵ less ΔƟ2 less ≥
&

&
&
&
&
&

& To DPSY02
& ≥ 560001 850B021F59
SYNCHK2
SYNC02_SYN_CLC
& ≥ (Function ID: 560001) Sync success
&
& ≥

PLC signals for relay selection relating to SYNCHK2



560001 800B02EDED SYNC02_RY1_USE_STS

560001 800B02EDEE SYNC02_RY2_USE_STS


Selection signals are
injected by PLC logic made
by the user. PLC signals for relay selection relating to SYNCHK1

560001 800B01EDED SYNC01_RY1_USE_STS

560001 800B01EDEE SYNC01_RY2_USE_STS

Figure 4.6-17 Relay selection made using PLC signals

Table 4.6-7 PLC connection point (Relay selection)


Signal Number Signal Name Description M/O
560001 800B01EDED SYNC01_RY1_USE_STS SYNCHK1 use SYNCHK_RY1 M
560001 800B01EDEE SYNC01_RY2_USE_STS SYNCHK1 use SYNCHK_RY2 M
560001 800B02EDED SYNC02_RY1_USE_STS SYNCHK2 use SYNCHK_RY1 M
560001 800B02EDEE SYNC02_RY2_USE_STS SYNCHK2 use SYNCHK_RY2 M

GRL200 (Soft 033 & 037)


- 811 -
6F2S1914 (0.37)

4.6.6 Voltage selection for line arrangement


As shown in Figure 4.6-16, input-voltage signals are required in response to the line and bus-
bar arrangement. Incidentally, the input-voltage signals supplied by the VTs are applied to the
IED via the transformer module (VCT†); hence, the input-voltage signal should correspond
with the required relay-element. On this account, settings are provided in the SYNCHK_Ry
function.

Signal Setting
V2a →
names names SYNCHK_Ry1
Va →V-L1 V2b →

Vb →V-L2 Relays for V2c →

Vc →V-L3 running voltage

Relays for
incoming voltage

Scheme switches [SyncRy1-VR] etc. select a running


voltage and an incoming voltage.

Vs →V3

Vs2 →V4 SYNCHK_Ry2

Relays for
running voltage

Relays for
incoming voltage

VCT

Scheme switches [SyncRy2-VR] etc. select a running


voltage and an incoming voltage.

Figure 4.6-18 Voltage signals selected using scheme switches


†Note:For the actual terminal arrangement and signals injected, see chapter Technical
description: Transformer module for AC analog input.

Figure 4.6-18 illustrates that the signals injected are distributed using scheme switches:
[SyncRy1-VR], [SyncRy1-VI], [SyncRy1-VR], and [SyncRy1-VI]. Examples below show how to
apply a voltage signal for the required relay-element.

(i) Setting example


Figure 4.6-19 depicts an example of a busbar arrangement and S43P logic programmed by the
user. In this case, only the SYNCHK_Ry1 function is used; therefore, the user need only select
the signal provided by the S43P logic for the SYNCHK_Ry1 function.

GRL200 (Soft 033 & 037)


- 812 -
6F2S1914 (0.37)

Busbar#1
Busbar#2 ✔
DS1 closed
& SYNC01_RY1_USE_STS
DS2 closed
V1 V2 DS1 DS2
S43P logic programmed Selection of SYNCHK_Ry1
CB1 by the user

SYNCHK01 and 02 functions

Figure 4.6-19 Bus-bar arrangement and PLC setting

Voltage selection should be considered in accordance with the arrangement of VTs.


Voltages V1 and V2 represent the running voltage (VR) and the incoming voltage (VI),
respectively. Consequently, V-L1 and V2-L1 are set for the scheme switches [SyncRy1-VR] and
[SyncRy1-VI], respectively. Table 4.6-8 shows the setting example for this arrangement.
Table 4.6-8 Setting example
Setting Name Description Default Setting item or value
SyncRy1-VR Selection of running voltage V-L1 Either of V-L1 / V-L2 / V-L3
SyncRy1-VI Selection of incoming voltage V2-L1 Either of V2-L1 / V2-L2 / V2-L3
SyncRy2-VR Selection of running voltage N.A N.A
SyncRy2-VI Selection of incoming voltage N.A N.A

GRL200 (Soft 033 & 037)


- 813 -
6F2S1914 (0.37)

4.6.7 Setting
Synchronism (Function ID: 560001)
Setting items Range Unit Contents Default Note

SYNC01_SYNCHK1EN Off / On - SYNC DEV1 synchronism check switch Off


SYNC02_SYNCHK2EN Off / On - SYNC DEV2 synchronism check switch Off
SYNC 01 V check timer(Live Run. & Dead Incom., Dead
SYNC01_TLRDIDRLI 0.00 - 5.00 s 5.00
Run. & Live Incom.)
SYNC01_TDRDI 0.00 - 5.00 s V check timer(Dead Run. & Dead Incom.) 5.00
SYNC01_TSYN 0.00 - 100.00 s synchronism check timer(Loop) 10.00
SYNC01_TSYN2 30 - 1800 s Synchronism check time up 60
SYNC DEV1 split synchronism check mode
SYNC01_Split_EN Off / On - Off
enable
SYNC DEV1 Live Run. & Dead Incom. close
SYNC01_LRDIEN Off / On - On
mode enable
SYNC DEV1 Dead Run. & Live Incom. close
SYNC01_DRLIEN Off / On - On
mode enable
SYNC DEV1 Dead Run. & Dead Incom. close
SYNC01_DRDIEN Off / On - On
mode enable
SYNC 02 V check timer(Live Run. & Dead Incom., Dead
SYNC02_TLRDIDRLI 0.00 - 5.00 s 5.00
Run. & Live Incom.)
SYNC02_TDRDI 0.00 - 5.00 s V check timer(Dead Run. & Dead Incom.) 5.00
SYNC02_TSYN 0.00 - 100.00 s synchronism check timer(Loop) 10.00
SYNC02_TSYN2 30 - 1800 s Synchronism check time up 60
SYNC DEV2 split synchronism check mode
SYNC02_Split_EN Off / On - Off
enable
SYNC DEV2 Live Run. & Dead Incom. close
SYNC02_LRDIEN Off / On - On
mode enable
SYNC DEV2 Dead Run. & Live Incom. close
SYNC02_DRLIEN Off / On - On
mode enable
SYNC DEV2 Dead Run. & Dead Incom. close
SYNC02_DRDIEN Off / On - On
mode enable

GRL200 (Soft 033 & 037)


- 814 -
6F2S1914 (0.37)

Synchk_Ry (Function ID: 561001)


Setting items Range Unit Contents Default Note

Synchronizing V-L1 / V-L2 / V-


check relay 1 L3 / V-L12 / V-
L23 / V-L31 /
SyncRy1-VR V2-L1 / V2-L2 / - Running Voltage V3
V2-L3 / V2-L12 /
V2-L23 / V2-L31
/ V3 / V4
V-L1 / V-L2 / V-
L3 / V-L12 / V-
L23 / V-L31 /
SyncRy1-VI V2-L1 / V2-L2 / - Incoming Voltage V-L1
V2-L3 / V2-L12 /
V2-L23 / V2-L31
/ V3 / V4
OVR1 10 - 150 V Voltage for the checking Live-Running Voltage 51
Voltage for the checking Dead-Running
UVR1 10 - 150 V 13
Voltage
Voltage for the checking Live-Incoming
OVI1 10 - 150 V 51
Voltage
Voltage for the checking Dead-Incoming
UVI1 10 - 150 V 13
Voltage
SyncRy1-Angle 0 - 75 deg Difference angle for the checking SyncRy1 30
SyncRy1-dV 0 - 150 V Difference voltage for the checking SyncRy1 150
SyncRy1-df 0.01 - 2.00 Hz Difference frequency for the checking SyncRy1 1.00
SyncRy1-TCB 10 - 500 ms CB Operate timer for SyncRy1 100
Synchronizing V-L1 / V-L2 / V-
check relay 2 L3 / V-L12 / V-
L23 / V-L31 /
SyncRy2-VR V2-L1 / V2-L2 / - Running Voltage V4
V2-L3 / V2-L12 /
V2-L23 / V2-L31
/ V3 / V4
V-L1 / V-L2 / V-
L3 / V-L12 / V-
L23 / V-L31 /
SyncRy2-VI V2-L1 / V2-L2 / - Incoming Voltage V-L1
V2-L3 / V2-L12 /
V2-L23 / V2-L31
/ V3 / V4
OVR2 10 - 150 V Voltage for the checking Live-Running Voltage 51
Voltage for the checking Dead-Running
UVR2 10 - 150 V 13
Voltage
Voltage for the checking Live-Incoming
OVI2 10 - 150 V 51
Voltage
Voltage for the checking Dead-Incoming
UVI2 10 - 150 V 13
Voltage
SyncRy2-Angle 0 - 75 deg Difference angle for the checking SyncRy2 30
SyncRy2-dV 0 - 150 V Difference voltage for the checking SyncRy2 150
SyncRy2-df 0.01 - 2.00 Hz Difference frequency for the checking SyncRy2 1.00
SyncRy2-TCB 10 - 500 ms CB Operate timer for SyncRy2 100

GRL200 (Soft 033 & 037)


- 815 -
6F2S1914 (0.37)

4.6.8 Signal
 Signal monitoring points
SYNDIF (Function ID: 560001)
Element ID Name Description
880B011F5C SYNC01_DDV_CS SYNC DEV1 27Vr & 27Vi condition signal

870B011F5B SYNC01_DLV_CS SYNC DEV1 27Vr & 84Vi condition signal

890B011F5D SYNC01_LDV_CS SYNC DEV1 84Vr & 27Vi condition signal

860B011F5A SYNC01_LLV_CS SYNC DEV1 84Vr & 84Vi condition signal

890B011F53 SYNC01_LPS_CLC SYNC DEV1 loop synchronism close command

800B011F81 SYNC01_RY1_USE_STS SYNC DEV1 Relay Module1 use status from PLC

800B011F82 SYNC01_RY2_USE_STS SYNC DEV1 Relay Module2 use status from PLC

870B011F77 SYNC01_RY_ANG_0TIME SYNC DEV1 Relay Output(Ang 0Time)

880B011F78 SYNC01_RY_ANG_RDC SYNC DEV1 Relay Output(Ang RDC)

800B011F54 SYNC01_SBP SYNC DEV1 synchronism bypath

830B011F57 SYNC01_SCD_CS SYNC DEV1 synchronism checked condition signal

840B011F5F SYNC01_SCK_CS01 SYNC DEV1 synchronism check condition signal 01

850B011F60 SYNC01_SCK_CS02 SYNC DEV1 synchronism check condition signal 02

860B011F61 SYNC01_SCK_CS03 SYNC DEV1 synchronism check condition signal 03

870B011F62 SYNC01_SCK_CS04 SYNC DEV1 synchronism check condition signal 04

880B011F63 SYNC01_SCK_CS05 SYNC DEV1 synchronism check condition signal 05

890B011F64 SYNC01_SCK_CS06 SYNC DEV1 synchronism check condition signal 06

8A0B011F65 SYNC01_SCK_CS07 SYNC DEV1 synchronism check condition signal 07

8B0B011F66 SYNC01_SCK_CS08 SYNC DEV1 synchronism check condition signal 08

8C0B011F67 SYNC01_SCK_CS09 SYNC DEV1 synchronism check condition signal 09

8E0B011F68 SYNC01_SCK_CS10 SYNC DEV1 synchronism check condition signal 10

820B011F69 SYNC01_SCK_CS11 SYNC DEV1 synchronism check condition signal 11

830B011F6A SYNC01_SCK_CS12 SYNC DEV1 synchronism check condition signal 12

840B011F6B SYNC01_SCK_CS13 SYNC DEV1 synchronism check condition signal 13

850B011F6C SYNC01_SCK_CS14 SYNC DEV1 synchronism check condition signal 14

870B011F6D SYNC01_SCK_CS15 SYNC DEV1 synchronism check condition signal 15

880B011F6E SYNC01_SCK_CS16 SYNC DEV1 synchronism check condition signal 16

8A0B011F6F SYNC01_SCK_CS17 SYNC DEV1 synchronism check condition signal 17

8B0B011F70 SYNC01_SCK_CS18 SYNC DEV1 synchronism check condition signal 18

8C0B011F71 SYNC01_SCK_CS19 SYNC DEV1 synchronism check condition signal 19

8D0B011F72 SYNC01_SCK_CS20 SYNC DEV1 synchronism check condition signal 20

8A0B011F73 SYNC01_SCK_CS21 SYNC DEV1 synchronism check condition signal 21

8B0B011F74 SYNC01_SCK_CS22 SYNC DEV1 synchronism check condition signal 22

8C0B011F75 SYNC01_SCK_CS23 SYNC DEV1 synchronism check condition signal 23

8D0B011F76 SYNC01_SCK_CS24 SYNC DEV1 synchronism check condition signal 24

810B011F85 SYNC01_SCK_CS25 SYNC DEV1 synchronism check condition signal 25

820B011F86 SYNC01_SCK_CS26 SYNC DEV1 synchronism check condition signal 26

810B011F55 SYNC01_SCK_STA SYNC DEV1 synchronism check start command

820B011F56 SYNC01_SCL_F SYNC DEV1 synchronism closed fail

840B011F58 SYNC01_SLD_VCS SYNC DEV1 selected voltage condition signal

860B011F52 SYNC01_SLF_VCS SYNC DEV1 select fail voltage condition signal

8D0B011F51 SYNC01_SPS_CLC SYNC DEV1 split synchronism close command

800B011F80 SYNC01_SS_VCS_PLC SYNC DEV1 success voltage condition signal from PLC

GRL200 (Soft 033 & 037)


- 816 -
6F2S1914 (0.37)

 Signal monitoring points


SYNDIF (Function ID: 560001)
Element ID Name Description
850B011F59 SYNC01_SYN_CLC SYNC DEV1 synchronism close command

880B021F5C SYNC02_DDV_CS SYNC DEV2 27Vr & 27Vi condition signal

870B021F5B SYNC02_DLV_CS SYNC DEV2 27Vr & 84Vi condition signal

890B021F5D SYNC02_LDV_CS SYNC DEV2 84Vr & 27Vi condition signal

860B021F5A SYNC02_LLV_CS SYNC DEV2 84Vr & 84Vi condition signal

890B021F53 SYNC02_LPS_CLC SYNC DEV2 loop synchronism close command

800B021F81 SYNC02_RY1_USE_STS SYNC DEV2 Relay Module1 use status from PLC

800B021F82 SYNC02_RY2_USE_STS SYNC DEV2 Relay Module2 use status from PLC

870B021F77 SYNC02_RY_ANG_0TIME SYNC DEV2 Relay Output(Ang 0Time)

880B021F78 SYNC02_RY_ANG_RDC SYNC DEV2 Relay Output(Ang RDC)

800B021F54 SYNC02_SBP SYNC DEV2 synchronism bypath

830B021F57 SYNC02_SCD_CS SYNC DEV2 synchronism checked condition signal

840B021F5F SYNC02_SCK_CS01 SYNC DEV2 synchronism check condition signal 01

850B021F60 SYNC02_SCK_CS02 SYNC DEV2 synchronism check condition signal 02

860B021F61 SYNC02_SCK_CS03 SYNC DEV2 synchronism check condition signal 03

870B021F62 SYNC02_SCK_CS04 SYNC DEV2 synchronism check condition signal 04

880B021F63 SYNC02_SCK_CS05 SYNC DEV2 synchronism check condition signal 05

890B021F64 SYNC02_SCK_CS06 SYNC DEV2 synchronism check condition signal 06

8A0B021F65 SYNC02_SCK_CS07 SYNC DEV2 synchronism check condition signal 07

8B0B021F66 SYNC02_SCK_CS08 SYNC DEV2 synchronism check condition signal 08

8C0B021F67 SYNC02_SCK_CS09 SYNC DEV2 synchronism check condition signal 09

8E0B021F68 SYNC02_SCK_CS10 SYNC DEV2 synchronism check condition signal 10

820B021F69 SYNC02_SCK_CS11 SYNC DEV2 synchronism check condition signal 11

830B021F6A SYNC02_SCK_CS12 SYNC DEV2 synchronism check condition signal 12

840B021F6B SYNC02_SCK_CS13 SYNC DEV2 synchronism check condition signal 13

850B021F6C SYNC02_SCK_CS14 SYNC DEV2 synchronism check condition signal 14

870B021F6D SYNC02_SCK_CS15 SYNC DEV2 synchronism check condition signal 15

880B021F6E SYNC02_SCK_CS16 SYNC DEV2 synchronism check condition signal 16

8A0B021F6F SYNC02_SCK_CS17 SYNC DEV2 synchronism check condition signal 17

8B0B021F70 SYNC02_SCK_CS18 SYNC DEV2 synchronism check condition signal 18

8C0B021F71 SYNC02_SCK_CS19 SYNC DEV2 synchronism check condition signal 19

8D0B021F72 SYNC02_SCK_CS20 SYNC DEV2 synchronism check condition signal 20

8A0B021F73 SYNC02_SCK_CS21 SYNC DEV2 synchronism check condition signal 21

8B0B021F74 SYNC02_SCK_CS22 SYNC DEV2 synchronism check condition signal 22

8C0B021F75 SYNC02_SCK_CS23 SYNC DEV2 synchronism check condition signal 23

8D0B021F76 SYNC02_SCK_CS24 SYNC DEV2 synchronism check condition signal 24

810B021F85 SYNC02_SCK_CS25 SYNC DEV2 synchronism check condition signal 25

820B021F86 SYNC02_SCK_CS26 SYNC DEV2 synchronism check condition signal 26

810B021F55 SYNC02_SCK_STA SYNC DEV2 synchronism check start command

820B021F56 SYNC02_SCL_F SYNC DEV2 synchronism closed fail

840B021F58 SYNC02_SLD_VCS SYNC DEV2 selected voltage condition signal

860B021F52 SYNC02_SLF_VCS SYNC DEV2 select fail voltage condition signal

8D0B021F51 SYNC02_SPS_CLC SYNC DEV2 split synchronism close command

800B021F80 SYNC02_SS_VCS_PLC SYNC DEV2 success voltage condition signal from PLC

GRL200 (Soft 033 & 037)


- 817 -
6F2S1914 (0.37)

 Signal monitoring points


SYNDIF (Function ID: 560001)
Element ID Name Description
850B021F59 SYNC02_SYN_CLC SYNC DEV2 synchronism close command

 Connection points in PLC logic


SYNCHK (Function ID: 560001)
Element ID Name Description
800B01EDEA SYNC01_DDV_CL_ECP SYNC DEV1 27Vr & 27Vi close enable condition signal from PLC

800B01EDE9 SYNC01_DLV_CL_ECP SYNC DEV1 27Vr & 84Vi close enable condition signal from PLC

800B01EDE8 SYNC01_LDV_CL_ECP SYNC DEV1 84Vr & 27Vi close enable condition signal from PLC

800B01EDE7 SYNC01_LLV_CL_ECP SYNC DEV1 84Vr & 84Vi close enable condition signal from PLC

800B01EDE6 SYNC01_LPS_CL_ECP SYNC DEV1 loop synchronism close enable condition signal from PLC

800B01EDED SYNC01_RY1_USE_STS SYNC DEV1 Relay Module1 use status from PLC

800B01EDEE SYNC01_RY2_USE_STS SYNC DEV1 Relay Module2 use status from PLC

800B01EDEB SYNC01_SBK_CSP SYNC DEV1 synchronism block condition signal from PLC

800B01EDE0 SYNC01_SBP_ECP SYNC DEV1 synchronism bypath enable condition signal from PLC

800B01EDE1 SYNC01_SBP_SSP SYNC DEV1 synchronism bypath success condition signal from PLC

800B01EDE4 SYNC01_SCL_CSP SYNC DEV1 synchronism close condition signal from PLC

800B01EDE2 SYNC01_SCL_F_ECP SYNC DEV1 synchronism close fail condition signal from PLC

800B01EDE3 SYNC01_SCL_SSP SYNC DEV1 synchronism close success condition signal from PLC

800B01EDE5 SYNC01_SPS_CL_ECP SYNC DEV1 split SYNC. close enable condition signal from PLC

800B01EDEC SYNC01_SS_VCS_PLC SYNC DEV1 success voltage condition signal from PLC

800B02EDEA SYNC02_DDV_CL_ECP SYNC DEV2 27Vr & 27Vi close enable condition signal from PLC

800B02EDE9 SYNC02_DLV_CL_ECP SYNC DEV2 27Vr & 84Vi close enable condition signal from PLC

800B02EDE8 SYNC02_LDV_CL_ECP SYNC DEV2 84Vr & 27Vi close enable condition signal from PLC

800B02EDE7 SYNC02_LLV_CL_ECP SYNC DEV2 84Vr & 84Vi close enable condition signal from PLC

800B02EDE6 SYNC02_LPS_CL_ECP SYNC DEV2 loop synchronism close enable condition signal from PLC

800B02EDED SYNC02_RY1_USE_STS SYNC DEV2 Relay Module1 use status from PLC

800B02EDEE SYNC02_RY2_USE_STS SYNC DEV2 Relay Module2 use status from PLC

800B02EDEB SYNC02_SBK_CSP SYNC DEV2 synchronism block condition signal from PLC

800B02EDE0 SYNC02_SBP_ECP SYNC DEV2 synchronism bypath enable condition signal from PLC

800B02EDE1 SYNC02_SBP_SSP SYNC DEV2 synchronism bypath success condition signal from PLC

800B02EDE4 SYNC02_SCL_CSP SYNC DEV2 synchronism close condition signal from PLC

800B02EDE2 SYNC02_SCL_F_ECP SYNC DEV2 synchronism close fail condition signal from PLC

800B02EDE3 SYNC02_SCL_SSP SYNC DEV2 synchronism close success condition signal from PLC

800B02EDE5 SYNC02_SPS_CL_ECP SYNC DEV2 split SYNC. close enable condition signal from PLC

800B02EDEC SYNC02_SS_VCS_PLC SYNC DEV2 success voltage condition signal from PLC

GRL200 (Soft 033 & 037)


- 818 -
6F2S1914 (0.37)

Software interlock function (ILK)


Devices must be controlled in accordance with the prevailing operational condition of the
electric power system. If a device does not act or behave in accordance with the operational
circumstances, inappropriate device control can result in outages or fatal incidents for the
network. In order to avoid such circumstances, software interlock (ILK) function is provided
that is able to examine the current operational situation and determine whether to permit the
control of a particular device.

When using the ILK function, an interlock-check formula is required. The interlock-check
formula examines the operational conditions for all devices, and is stored in the ILK database.
The ILK function provides an output signal “OK/NG decision information”; the “OK/NG
decision information” is transferred to the control functions†, which control the external
devices. Following which, the control functions can commence with the control of the selected
devices in response to the respective “OK/NG decision information”.

†Note:Details of SPOS, DPSY, and TPOS features are discussed separately elsewhere in
the instruction manual under the Chapter Control and monitoring applications.

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.7-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 819 -
6F2S1914 (0.37)

Prior to controlling a device, the interlock-check function is used to determine whether the
control of a device is correct or not. If the interlock-check finds that the conditions for device
control have not been satisfied in accordance with the appropriate interlock condition, control
of the device is forbidden. Figure 4.7-1 provides an overview of the interlock-check process.
Formulae for interlock-check are stored in an ILK database; these formulae are used in order
to enable the interlock-check function to output a decision. If the proposed operation of a
particular device is deemed correct then an “OK-decision” is determined by the formulae, and
device control is allowed. However, if the proposed operation of the device is deemed incorrect
then an “NG-decision” is determined by the formulae, and device control is not allowed.

Device IED
Binary
Circuit input Control
breaker Interlock Control
Device status circuits Device status Functions Device status Function (ILK)
(CB)
SPOS
DPOS
Dis- Binary OK/NG decision Interlock
and
connector Output
others
(DS) circuits
Device control Control Database

Other IEDs
GOOSE GOOSE receiving information
GOOSE subscription
data
transmission

data

PC(GR-TIEMS)

Interlock formulas

Figure 4.7-1 Interlock–check process

4.7.1 ILK specification


(i) Maximum number of interlock-checks
Since the maximum number of interlock-checks is 83, ILK can be used to supervise 83 control
devices. An interlock-check can include up to 500 nodes; an interlock operator and input/output
signals are configured for each node; a node can accept up to 64 input signals. (Nodes are
discussed separately. See section 4.7.3)

(ii) GOOSE receiving information


When an interlock-check is required to determine an “OK/NG-decision”, the interlock-check
function collects the device status from all of the other IEDs during the interlock-check process.
In this case, GOOSE subscription information is used to acquire the device status required;
configuration of the interlock-check formula, including quality information corresponding to

GRL200 (Soft 033 & 037)


- 820 -
6F2S1914 (0.37)

other IEDs and GOOSE, is necessary.

4.7.2 Interlock-check formula


Figure 4.7-2 shows a device (Q0) in the feeder bay, if a control action to operate (Q0) is required,
an interlock-check will be necessary. To control the device (Q0), the interlock-check must verify
the status of several devices in the busbar and the bay.
Busbar1-A
Busbar2-A

Q1B Q2B Q15 Q25


Q1 Q2
Q52

Q0 Q0B
Q53

Q9 Q8

Q69
F52VT
F27L

Figure 4.7-2 Example of device status and Interlock-check

In accordance with the arrangement of the devices shown in Figure 4.7-2, interlock-check
formulae can be configured from equations (4.7-1) to (4.7-9). The status of respective devices,
(stVal) and interlock operators (“•” and “+”) are placed on the right-hand side of the equations;
and the interlock condition (e.g. Q0(Closing)) is placed on the left-hand side of the equations.
The interlock operators are also shown in Table 4.7-2.
̅̅̅̅ ∙ Q2
Q1 = (Q0 ̅̅̅̅̅ ∙ Q52
̅̅̅̅ ∙ Q15 ̅̅̅̅̅ ∙ Q53
̅̅̅̅̅)
(4.7-1)
+ (Q2 ∙ Q0 ∙ Q9 ∙ Q0B ∙ Q1B ∙ Q2B)
̅̅̅̅ ∙ Q1
Q2 = (Q0 ̅̅̅̅̅ ∙ Q52
̅̅̅̅ ∙ Q25 ̅̅̅̅̅ ∙ Q53
̅̅̅̅̅)
(4.7-2)
+ (Q1 ∙ Q0 ∙ Q9 ∙ Q0B ∙ Q1B ∙ Q2B)
Q9 = (Q0 ̅̅̅̅̅ ∙ Q53
̅̅̅̅ ∙ Q52 ̅̅̅̅̅ ∙ Q8
̅̅̅̅) (4.7-3)
Q0(Closing ‡)
= ̅̅̅̅̅̅̅̅̅ ̅̅̅̅̅̅̅̅̅
63QBE ∙ 63GBE

̅̅̅̅ ∙ ̅̅̅̅
∙ ((Q1 Q2 ∙ ̅̅̅̅
Q9) + ((Q1 + Q2) ∙ Q9)) (4.7-4)

∙ Closing Blocking
̅̅̅̅̅̅̅̅̅ ∙ 63GBE
Q0(Opening‡ ) = 63QBF ̅̅̅̅̅̅̅̅̅ (4.7-5)
̅̅̅̅ ∙ Q69 ∙ F27L(No voltage) ∙ F52VT)
Q8 = (Q9 (4.7-6)
̅̅̅̅ ∙ ̅̅̅̅
Q52 = (Q9 Q1 ∙ ̅̅̅̅
Q2) (4.7-7)
̅̅̅̅ ∙ Q1
Q53 = (Q9 ̅̅̅̅ ∙ Q2
̅̅̅̅) (4.7-8)
Q69 = Q8 (4.7-9)
where,

GRL200 (Soft 033 & 037)


- 821 -
6F2S1914 (0.37)

Q0: Circuit breaker (CB)†


Q1, Q2, Q9: Disconnecting switch (DS)
Q52, Q53, Q8, Q15, Q25: Earthing switch (ES)
63QBE: OIL Pressure switch (e.g., “Off” state is shown at 270 bar or above.)
63QBF: OIL Pressure switch (e.g., “On” state is shown at 255 bar or below.)
63GBE: GAS Pressure switch (e.g., “On” state is shown at 6.5 bar or below.)
Closing Blocking: State of Protection lockout relay (“Off” state means active.)
F27L: State of under voltage relay (“On” state means no voltage.)
F52VT: State of VT MCB switch
Sign “•”: Interlock operator “AND”
Sign “+”: Interlock operator “OR”

̅̅̅̅
†Note: When CB (𝑄0) is open, logic level of 𝑄0 is “1”. On the other hand, when CB
(𝑄0) is closed, logic level of 𝑄0 is “1”.
‡Note: For example, on the left-hand side of equation (4.7-5), “Opening” reflects the
control direction of CB (𝑄0).

For example in equation (4.7-12), the interlock condition for DS (Q1) is satisfied when CB
(Q0), DS (Q2), ES for the Bus-bar1-A (Q15), ES (Q52) and ES (Q53) are open. In addition, the
interlock condition for DS (Q1) is also satisfied when DS (Q2), CB (Q0), DS (Q9), CB (Q0), DS
(Q1), and DS (Q2) are closed.

GRL200 (Soft 033 & 037)


- 822 -
6F2S1914 (0.37)

Table 4.7-2 Names of operators used in the Interlock-check formulae


Sign of Example of
Interlock
interlock Description‡ interlock
operator
operator formula†
If both input signals are “1”, the resultant
AND(•) output signal is “1”. If not, the output signal Q1 • Q2
is “0”.
If either input signals is “1”, the resultant
OR(+) output signal is “1”. If not, the output signal Q1 + Q2
is “0”.
If the input signal is “1”, the resultant output
NOT(!) !(Q1)
signal is “0”. If not, the output signal is “1”.
Two input signals are compared. If the input
COMP signals are identical, the output signal is “1”. (Q1) COMP (1)
If not, the output signal is “0”.
†Note: Q1 and Q2 represent controllable objects.
‡Note: For further information, see section 4.7.3(iii).

4.7.3 Interlock-check method


(i) Node and input/output signals
A node is represented by an interlock-operator, input signals (stVal and Quality), and output
signals (stVal and Quality). For example, Figure 4.7-3 shows a node with an “OR” interlock-
operator, input signals, and an output signal. When stVal and ‘Quality’ are applied to the
inputs of the node, the resultant output signal is in accordance with the operation rule of “OR”.
(For details, see 4.7.3(iii)-2)

Node

stVal OR (+)
Input(A)
stVal
Quality
Output
Quality

Input(B) stVal
Quality

Figure 4.7-3 Input/output signals


Note: A bold line reflects a signal “stVal”. A thin line reflects a signal “Quality”. The user
should note that the signal format generated by control functions should be
transposed for the stVal format, as shown in Table 4.7-8.

GRL200 (Soft 033 & 037)


- 823 -
6F2S1914 (0.37)

(ii) Nodes and formulae for interlock-check


Figure 4.7-4 illustrates that an interlock-check is realized by using a number of nodes. For
each node, the user is required to configure input signals, interlock-operators, and links
between nodes. Following that, an interlock-check can be run.

Node #1
Node #2 Node #7
OR(+) AND(•)
Input A AND(•)
Input B
Output

Input C
Input D Node #4
Node #3
OR(+)
AND(•)
Input E
Input F

Input G
Node #5 Node #6
AND(•)
OR(+)
Input H
Input I

Input J

Users can see signals at signal monitoring Users can see


points using the GR-TIEMS. signals by IED
screens.

Signal monitoring point

Figure 4.7-4 Operation of interlock-check

We can see that equation (4.7-10) is a representation of Figure 4.7-4. This equation is computed
in accordance with the priority order of the interlock-operators: the first is parentheses [()], the
second is AND [•], followed by OR [+].
Output = ((A+B) •C) + (D+E•F) + (G•(H+I) •J) (4.7-10)

GRL200 (Soft 033 & 037)


- 824 -
6F2S1914 (0.37)

(iii) Purpose of Quality information in the output signal


In the output signal, the quality information will affect the control of the device. Table 4.7-3
shows four types of output signal. When the quality information (Quality) of an output signal
issued by a node is indicated as being “NG”, it signifies that device control is forbidden. On the
other hand, quality information (Quality) “OK” means that that device control is allowed.

Table 4.7-3 Device status, quality information in the output signal


Output signal
Meaning
(stVal–Quality)
0–OK Control forbidden
0–NG Control forbidden
1–OK Control allowed
1–NG Control forbidden
Note: With regard to the value of ‘Quality’, we define “OK” as ‘0’ and “NG” as ‘1’ in the
logic operation.

AND interlock operator


When quality information (Quality) is applied to the interlock operator “AND”, the “AND”
operator outputs the quality information intact. That is, the output quality information is not
affected by device status (stVal). Table 4.7-4 shows two-input-signals (A, B) and the output
signal for “AND”.
Table 4.7-4 Output signals (stVal–Quality) for AND
Input B (stVal–Quality)
0–OK 0–NG 1–OK 1–NG
0–OK 0–OK – – –
Input A 0–NG 0–OK 0–NG – –
(stVal–Quality) 1–OK 0–OK 0–NG 1–OK –
1–NG 0–OK 0–NG 1–NG 1–NG

Figure 4.7-5 shows the logic symbol for the interlock operator “AND” with input signals
and an output signal. Figure 4.7-5 can be represented by equations (4.7-11) and (4.7-12).
stVal = stVa(A) • stVa(B) (4.7-11)
Quality=(Quality(A)+Quality(B))•(stVa(A)+ Quality(A))
(4.7-12)
•(stVa(B)+Quality(B))
For example, when the interlock operator “AND” has two input signals (0–NG, 0–OK), it
has to generate a signal (0–OK) using the equations (4.7-11) and (4.7-12). This is because the
quality “NG (i.e., 1)” and the quality “OK (i.e., 0)” are entered into the AND operator; the AND
operator produces zero (0) which is defined as “OK” in ‘Quality’. A note regarding the values

GRL200 (Soft 033 & 037)


- 825 -
6F2S1914 (0.37)

used for ‘Quality’ can be found immediately below Table 4.7-3.

AND (•)
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B)
Quality

Figure 4.7-5 Logic of interlock operator (AND) and Input/Output signals

OR interlock operator
When quality information (Quality) is applied to the interlock operator “OR”, the quality
information is affected by device status (stVal). Table 4.7-5 shows two-input-signals (A, B) and
the output signal for “OR”
Table 4.7-5 Output signals (stVal–Quality) of OR
Input B (stVal–Quality)
0–OK 0–NG 1–OK 1–NG
0–OK 0–OK – – –
Input A 0–NG 0–NG 0–NG – –
(stVal–Quality) 1–OK 1–OK 1–OK 1–OK –
1–NG 1–NG 1–NG 1–OK 1–NG
As shown in Table 4.7-5, if ‘0’ represents the status value “stVal” for all input signals, and
if the quality information of “NG” is given for an input signal, then the output signal “Quality”
is represented as “NG”. On the other hand, if all input signals “stVal” are represented by “1”,
and if the quality information for the input signals “stVal(1)” is given, then the representation
“OK” can be weighted for the output signal “Quality” . Note that quality information (OK) for
input signals with “stVal(1)” get priority if there are two or more input signals, which are
represented as “stVal(1)”.

Figure 4.7-6 shows the logic symbol for the interlock operator “OR” with input signals and an
output signal, which can be represented by equations (4.7-13) and (4.7-14).

OR (+)
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B) Quality

Figure 4.7-6 Interlock operator (OR) and Input/Output signals


stVal=stVa(A)+stVa(B) (4.7-13)
Quality=!((stVal(A)•!Quality(A))•(stVa(B)•!Quality(B))+
(4.7-14)
!(stVal(A)+Quality(A)+stVal(B)+Quality(B)))

GRL200 (Soft 033 & 037)


- 826 -
6F2S1914 (0.37)

For example, when the interlock operator “OR” has two input signals (0–NG, 0–OK), it
has to generate a signal (0–NG) using the equations (4.7-13) and (4.7-14). This is because the
quality “NG (i.e., 1)” and the quality “OK (i.e., 0)” are entered into the OR operator; the OR
operator produces one (1) which is defined as “NG” in ‘Quality’. A note regarding the values
used for Quality can be found immediately below Table 4.7-3

NOR interlock operator


When quality information (Quality) is applied to the interlock operator “NOR”, the “NOR”
operator outputs the quality information intact. That is, the “NOR” interlock operator outputs
quality information, which is not influenced by device status (stVal). Table 4.7-6 shows an
input-signal (A) and the output signal for the “NOR” interlock operator.
Table 4.7-6 Output signals (stVal–Quality) of NOT
Output (stVal–Quality)
0–OK 1–OK
Input A 0–NG 1–NG
(stVal–Quality) 1–OK 0–OK
1–NG 0–NG

Figure 4.7-7 depicts the logic symbol for the interlock operator “NOT” with input signals
and an output signal, which can be represented by equations (4.7-15) and (4.7-16).

NOT(!)
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B) Quality

Figure 4.7-7 Interlock operator (NOT) and In/Output signals


stVal=!stVa(A) (4.7-15)
Quality=Quality(A) (4.7-16)

GRL200 (Soft 033 & 037)


- 827 -
6F2S1914 (0.37)

COMP interlock operator


When quality information (Quality) is applied to the interlock operator “COMP”, the “COMP”
operator outputs the original quality information intact. That is, the “COMP” interlock
operator outputs quality information, which is not influenced by device status (stVal). Table
4.7-7 shows two input-signals (A and B) and the output signal for the “COMP” interlock
operator.
Table 4.7-7 Output signals (stVal–Quality) of COMP
Input B (stVal)†
0 1
0–OK 1–OK 0–OK
Input A 0–NG 1–NG 0–NG
(stVal–Quality) 1–OK 0–OK 1–OK
1–NG 0–NG 1–NG

Figure 4.7-8 depicts the logic symbol for the interlock operator “COMP” with input signals
and an output signal, which can be represented by equations (4.7-17) and (4.7-18).
stVal=stVa(A) COMP stVa(B) (4.7-17)
Quality=Quality(A) † (4.7-18)
†Note: Input signal (B) does not have quality information because its signal is a
threshold value.

COMP
Input(A) stVal
Quality
stVal
Output
Quality
Input(B) stVal

Figure 4.7-8 Interlock operator (COMP) and Input/Output signals

Device status output by control functions transposed


As shown in Figure 4.7-3, a node inputs a value (stVal). The user should be aware that the
node cannot directly read the value of device status generated by the control functions. This is
because each control function generates the device status in a different format. Thus, for the
ILK operation, the device status generated should be transposed to the stVal so that the node
can read the device status. The right-hand column of Table 4.7-8 shows the transposed “stVal”
in each node.

GRL200 (Soft 033 & 037)


- 828 -
6F2S1914 (0.37)

Table 4.7-8 Signals generated in control functions


Control Device status generated by the control
“stVal” transposed in the node
function function described on the left column
0(off) 0
SPOS
1(on) 1
0x40(Open) 0† 0x40‡ 1§
DPOS 0x80(Close) 1† 0x80‡ 0§
“device status” except “0x40” and “0x80” 0
0x01(P1) 1
0x02(P2) 2
TPOS 0x04(P3) 4
“device status” except “0x01”, “0x02” and
0
“0x04”
BI
0(off) 0
signal
†Note: Values are altered when “AND”, “OR”, or “NOT” is applied as an interlock
operator.
‡Note: Values are altered when “COMP” is applied as an interlock operator.
§Note: Values are altered when the DPOS output is an inverted signal.

4.7.4 Configuration of Interlock formulae


Interlock-check formulae should be stored in the Interlock database, as shown in Figure 4.7-1.
These formulae are configured using GR-TIEMS†, and are uploaded into the ILK interlock
database.

†Note:The configuration of interlock-check formulae is discussed separately. See chapter


Engineering tool: Interlock configurator.

GRL200 (Soft 033 & 037)


- 829 -
6F2S1914 (0.37)

4.7.5 Signal
 Signal monitoring point
ILK (Function ID: 570001)
Element ID Name Description
3100A11001 ILK_MID_UPDATING ILK condition number during counting

3101011DA0 SPOS01-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV01

3101011DA2 SPOS01-ON Result of interlock judgement in On(closed) direction at SPOS DEV01

3101021DA0 SPOS02-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV02

3101021DA2 SPOS02-ON Result of interlock judgement in On(closed) direction at SPOS DEV02

3101031DA0 SPOS03-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV03

3101031DA2 SPOS03-ON Result of interlock judgement in On(closed) direction at SPOS DEV03

3101041DA0 SPOS04-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV04

3101041DA2 SPOS04-ON Result of interlock judgement in On(closed) direction at SPOS DEV04

3101051DA0 SPOS05-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV05

3101051DA2 SPOS05-ON Result of interlock judgement in On(closed) direction at SPOS DEV05

3101061DA0 SPOS06-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV06

3101061DA2 SPOS06-ON Result of interlock judgement in On(closed) direction at SPOS DEV06

3101071DA0 SPOS07-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV07

3101071DA2 SPOS07-ON Result of interlock judgement in On(closed) direction at SPOS DEV07

3101081DA0 SPOS08-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV08

3101081DA2 SPOS08-ON Result of interlock judgement in On(closed) direction at SPOS DEV08

3101091DA0 SPOS09-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV09

3101091DA2 SPOS09-ON Result of interlock judgement in On(closed) direction at SPOS DEV09

31010A1DA0 SPOS10-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV10

31010A1DA2 SPOS10-ON Result of interlock judgement in On(closed) direction at SPOS DEV10

31010B1DA0 SPOS11-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV11

31010B1DA2 SPOS11-ON Result of interlock judgement in On(closed) direction at SPOS DEV11

31010C1DA0 SPOS12-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV12

31010C1DA2 SPOS12-ON Result of interlock judgement in On(closed) direction at SPOS DEV12

31010D1DA0 SPOS13-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV13

31010D1DA2 SPOS13-ON Result of interlock judgement in On(closed) direction at SPOS DEV13

31010E1DA0 SPOS14-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV14

31010E1DA2 SPOS14-ON Result of interlock judgement in On(closed) direction at SPOS DEV14

31010F1DA0 SPOS15-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV15

31010F1DA2 SPOS15-ON Result of interlock judgement in On(closed) direction at SPOS DEV15

3101101DA0 SPOS16-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV16

3101101DA2 SPOS16-ON Result of interlock judgement in On(closed) direction at SPOS DEV16

3101111DA0 SPOS17-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV17

3101111DA2 SPOS17-ON Result of interlock judgement in On(closed) direction at SPOS DEV17

3101121DA0 SPOS18-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV18

3101121DA2 SPOS18-ON Result of interlock judgement in On(closed) direction at SPOS DEV18

3101131DA0 SPOS19-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV19

3101131DA2 SPOS19-ON Result of interlock judgement in On(closed) direction at SPOS DEV19

3101141DA0 SPOS20-OFF Result of interlock judgement in OFF(open) direction at SPOS DEV20

3101141DA2 SPOS20-ON Result of interlock judgement in On(closed) direction at SPOS DEV20

3102011DA0 DPSY1-OPEN Result of interlock judgement in close direction at DPSY DEV01

3102011DA2 DPSY1-CLOSE Result of interlock judgement in open direction at DPSY DEV01

GRL200 (Soft 033 & 037)


- 830 -
6F2S1914 (0.37)

 Signal monitoring point


ILK (Function ID: 570001)
Element ID Name Description
3102021DA0 DPSY2-OPEN Result of interlock judgement in close direction at DPSY DEV02

3102021DA2 DPSY2-CLOSE Result of interlock judgement in open direction at DPSY DEV02

3103011DA0 DPOS01-OPEN Result of interlock judgement in open direction at DPOS DEV01

3103011DA2 DPOS01-CLOSE Result of interlock judgement in close direction at DPOS DEV01

3103021DA0 DPOS02-OPEN Result of interlock judgement in open direction at DPOS DEV02

3103021DA2 DPOS02-CLOSE Result of interlock judgement in close direction at DPOS DEV02

3103031DA0 DPOS03-OPEN Result of interlock judgement in open direction at DPOS DEV03

3103031DA2 DPOS03-CLOSE Result of interlock judgement in close direction at DPOS DEV03

3103041DA0 DPOS04-OPEN Result of interlock judgement in open direction at DPOS DEV04

3103041DA2 DPOS04-CLOSE Result of interlock judgement in close direction at DPOS DEV04

3103051DA0 DPOS05-OPEN Result of interlock judgement in open direction at DPOS DEV05

3103051DA2 DPOS05-CLOSE Result of interlock judgement in close direction at DPOS DEV05

3103061DA0 DPOS06-OPEN Result of interlock judgement in open direction at DPOS DEV06

3103061DA2 DPOS06-CLOSE Result of interlock judgement in close direction at DPOS DEV06

3103071DA0 DPOS07-OPEN Result of interlock judgement in open direction at DPOS DEV07

3103071DA2 DPOS07-CLOSE Result of interlock judgement in close direction at DPOS DEV07

3103081DA0 DPOS08-OPEN Result of interlock judgement in open direction at DPOS DEV08

3103081DA2 DPOS08-CLOSE Result of interlock judgement in close direction at DPOS DEV08

3103091DA0 DPOS09-OPEN Result of interlock judgement in open direction at DPOS DEV09

3103091DA2 DPOS09-CLOSE Result of interlock judgement in close direction at DPOS DEV09

31030A1DA0 DPOS10-OPEN Result of interlock judgement in open direction at DPOS DEV10

31030A1DA2 DPOS10-CLOSE Result of interlock judgement in close direction at DPOS DEV10

31030B1DA0 DPOS11-OPEN Result of interlock judgement in open direction at DPOS DEV11

31030B1DA2 DPOS11-CLOSE Result of interlock judgement in close direction at DPOS DEV11

31030C1DA0 DPOS12-OPEN Result of interlock judgement in open direction at DPOS DEV12

31030C1DA2 DPOS12-CLOSE Result of interlock judgement in close direction at DPOS DEV12

31030D1DA0 DPOS13-OPEN Result of interlock judgement in open direction at DPOS DEV13

31030D1DA2 DPOS13-CLOSE Result of interlock judgement in close direction at DPOS DEV13

31030E1DA0 DPOS14-OPEN Result of interlock judgement in open direction at DPOS DEV14

31030E1DA2 DPOS14-CLOSE Result of interlock judgement in close direction at DPOS DEV14

31030F1DA0 DPOS15-OPEN Result of interlock judgement in open direction at DPOS DEV15

31030F1DA2 DPOS15-CLOSE Result of interlock judgement in close direction at DPOS DEV15

3103101DA0 DPOS16-OPEN Result of interlock judgement in open direction at DPOS DEV16

3103101DA2 DPOS16-CLOSE Result of interlock judgement in close direction at DPOS DEV16

3103111DA0 DPOS17-OPEN Result of interlock judgement in open direction at DPOS DEV17

3103111DA2 DPOS17-CLOSE Result of interlock judgement in close direction at DPOS DEV17

3103121DA0 DPOS18-OPEN Result of interlock judgement in open direction at DPOS DEV18

3103121DA2 DPOS18-CLOSE Result of interlock judgement in close direction at DPOS DEV18

3103131DA0 DPOS19-OPEN Result of interlock judgement in open direction at DPOS DEV19

3103131DA2 DPOS19-CLOSE Result of interlock judgement in close direction at DPOS DEV19

3103141DA0 DPOS20-OPEN Result of interlock judgement in open direction at DPOS DEV20

3103141DA2 DPOS20-CLOSE Result of interlock judgement in close direction at DPOS DEV20

3103151DA0 DPOS21-OPEN Result of interlock judgement in open direction at DPOS DEV21

3103151DA2 DPOS21-CLOSE Result of interlock judgement in close direction at DPOS DEV21

GRL200 (Soft 033 & 037)


- 831 -
6F2S1914 (0.37)

 Signal monitoring point


ILK (Function ID: 570001)
Element ID Name Description
3103161DA0 DPOS22-OPEN Result of interlock judgement in open direction at DPOS DEV22

3103161DA2 DPOS22-CLOSE Result of interlock judgement in close direction at DPOS DEV22

3103171DA0 DPOS23-OPEN Result of interlock judgement in open direction at DPOS DEV23

3103171DA2 DPOS23-CLOSE Result of interlock judgement in close direction at DPOS DEV23

3103181DA0 DPOS24-OPEN Result of interlock judgement in open direction at DPOS DEV24

3103181DA2 DPOS24-CLOSE Result of interlock judgement in close direction at DPOS DEV24

3103191DA0 DPOS25-OPEN Result of interlock judgement in open direction at DPOS DEV25

3103191DA2 DPOS25-CLOSE Result of interlock judgement in close direction at DPOS DEV25

31031A1DA0 DPOS26-OPEN Result of interlock judgement in open direction at DPOS DEV26

31031A1DA2 DPOS26-CLOSE Result of interlock judgement in close direction at DPOS DEV26

31031B1DA0 DPOS27-OPEN Result of interlock judgement in open direction at DPOS DEV27

31031B1DA2 DPOS27-CLOSE Result of interlock judgement in close direction at DPOS DEV27

31031C1DA0 DPOS28-OPEN Result of interlock judgement in open direction at DPOS DEV28

31031C1DA2 DPOS28-CLOSE Result of interlock judgement in close direction at DPOS DEV28

31031D1DA0 DPOS29-OPEN Result of interlock judgement in open direction at DPOS DEV29

31031D1DA2 DPOS29-CLOSE Result of interlock judgement in close direction at DPOS DEV29

31031E1DA0 DPOS30-OPEN Result of interlock judgement in open direction at DPOS DEV30

31031E1DA2 DPOS30-CLOSE Result of interlock judgement in close direction at DPOS DEV30

31031F1DA0 DPOS31-OPEN Result of interlock judgement in open direction at DPOS DEV31

31031F1DA2 DPOS31-CLOSE Result of interlock judgement in close direction at DPOS DEV31

3103201DA0 DPOS32-OPEN Result of interlock judgement in open direction at DPOS DEV32

3103201DA2 DPOS32-CLOSE Result of interlock judgement in close direction at DPOS DEV32

3103211DA0 DPOS33-OPEN Result of interlock judgement in open direction at DPOS DEV33

3103211DA2 DPOS33-CLOSE Result of interlock judgement in close direction at DPOS DEV33

3103221DA0 DPOS34-OPEN Result of interlock judgement in open direction at DPOS DEV34

3103221DA2 DPOS34-CLOSE Result of interlock judgement in close direction at DPOS DEV34

3103231DA0 DPOS35-OPEN Result of interlock judgement in open direction at DPOS DEV35

3103231DA2 DPOS35-CLOSE Result of interlock judgement in close direction at DPOS DEV35

3103241DA0 DPOS36-OPEN Result of interlock judgement in open direction at DPOS DEV36

3103241DA2 DPOS36-CLOSE Result of interlock judgement in close direction at DPOS DEV36

3103251DA0 DPOS37-OPEN Result of interlock judgement in open direction at DPOS DEV37

3103251DA2 DPOS37-CLOSE Result of interlock judgement in close direction at DPOS DEV37

3103261DA0 DPOS38-OPEN Result of interlock judgement in open direction at DPOS DEV38

3103261DA2 DPOS38-CLOSE Result of interlock judgement in close direction at DPOS DEV38

3103271DA0 DPOS39-OPEN Result of interlock judgement in open direction at DPOS DEV39

3103271DA2 DPOS39-CLOSE Result of interlock judgement in close direction at DPOS DEV39

3103281DA0 DPOS40-OPEN Result of interlock judgement in open direction at DPOS DEV40

3103281DA2 DPOS40-CLOSE Result of interlock judgement in close direction at DPOS DEV40

3103291DA0 DPOS41-OPEN Result of interlock judgement in open direction at DPOS DEV41

3103291DA2 DPOS41-CLOSE Result of interlock judgement in close direction at DPOS DEV41

31032A1DA0 DPOS42-OPEN Result of interlock judgement in open direction at DPOS DEV42

31032A1DA2 DPOS42-CLOSE Result of interlock judgement in close direction at DPOS DEV42

31032B1DA0 DPOS43-OPEN Result of interlock judgement in open direction at DPOS DEV43

31032B1DA2 DPOS43-CLOSE Result of interlock judgement in close direction at DPOS DEV43

GRL200 (Soft 033 & 037)


- 832 -
6F2S1914 (0.37)

 Signal monitoring point


ILK (Function ID: 570001)
Element ID Name Description
31032C1DA0 DPOS44-OPEN Result of interlock judgement in open direction at DPOS DEV44

31032C1DA2 DPOS44-CLOSE Result of interlock judgement in close direction at DPOS DEV44

31032D1DA0 DPOS45-OPEN Result of interlock judgement in open direction at DPOS DEV45

31032D1DA2 DPOS45-CLOSE Result of interlock judgement in close direction at DPOS DEV45

31032E1DA0 DPOS46-OPEN Result of interlock judgement in open direction at DPOS DEV46

31032E1DA2 DPOS46-CLOSE Result of interlock judgement in close direction at DPOS DEV46

31032F1DA0 DPOS47-OPEN Result of interlock judgement in open direction at DPOS DEV47

31032F1DA2 DPOS47-CLOSE Result of interlock judgement in close direction at DPOS DEV47

3103301DA0 DPOS48-OPEN Result of interlock judgement in open direction at DPOS DEV48

3103301DA2 DPOS48-CLOSE Result of interlock judgement in close direction at DPOS DEV48

3103311DA0 DPOS49-OPEN Result of interlock judgement in open direction at DPOS DEV49

3103311DA2 DPOS49-CLOSE Result of interlock judgement in close direction at DPOS DEV49

3103321DA0 DPOS50-OPEN Result of interlock judgement in open direction at DPOS DEV50

3103321DA2 DPOS50-CLOSE Result of interlock judgement in close direction at DPOS DEV50

3103331DA0 DPOS51-OPEN Result of interlock judgement in open direction at DPOS DEV51

3103331DA2 DPOS51-CLOSE Result of interlock judgement in close direction at DPOS DEV51

3103341DA0 DPOS52-OPEN Result of interlock judgement in open direction at DPOS DEV52

3103341DA2 DPOS52-CLOSE Result of interlock judgement in close direction at DPOS DEV52

3103351DA0 DPOS53-OPEN Result of interlock judgement in open direction at DPOS DEV53

3103351DA2 DPOS53-CLOSE Result of interlock judgement in close direction at DPOS DEV53

3103361DA0 DPOS54-OPEN Result of interlock judgement in open direction at DPOS DEV54

3103361DA2 DPOS54-CLOSE Result of interlock judgement in close direction at DPOS DEV54

3103371DA0 DPOS55-OPEN Result of interlock judgement in open direction at DPOS DEV55

3103371DA2 DPOS55-CLOSE Result of interlock judgement in close direction at DPOS DEV55

3103381DA0 DPOS56-OPEN Result of interlock judgement in open direction at DPOS DEV56

3103381DA2 DPOS56-CLOSE Result of interlock judgement in close direction at DPOS DEV56

3103391DA0 DPOS57-OPEN Result of interlock judgement in open direction at DPOS DEV57

3103391DA2 DPOS57-CLOSE Result of interlock judgement in close direction at DPOS DEV57

31033A1DA0 DPOS58-OPEN Result of interlock judgement in open direction at DPOS DEV58

31033A1DA2 DPOS58-CLOSE Result of interlock judgement in close direction at DPOS DEV58

31033B1DA0 DPOS59-OPEN Result of interlock judgement in open direction at DPOS DEV59

31033B1DA2 DPOS59-CLOSE Result of interlock judgement in close direction at DPOS DEV59

31033C1DA0 DPOS60-OPEN Result of interlock judgement in open direction at DPOS DEV60

31033C1DA2 DPOS60-CLOSE Result of interlock judgement in close direction at DPOS DEV60

31033D1DA0 DPOS61-OPEN Result of interlock judgement in open direction at DPOS DEV61

31033D1DA2 DPOS61-CLOSE Result of interlock judgement in close direction at DPOS DEV61

31033E1DA0 DPOS62-OPEN Result of interlock judgement in open direction at DPOS DEV62

31033E1DA2 DPOS62-CLOSE Result of interlock judgement in close direction at DPOS DEV62

31033F1DA0 DPOS63-OPEN Result of interlock judgement in open direction at DPOS DEV63

31033F1DA2 DPOS63-CLOSE Result of interlock judgement in close direction at DPOS DEV63

3103401DA0 DPOS64-OPEN Result of interlock judgement in open direction at DPOS DEV64

3103401DA2 DPOS64-CLOSE Result of interlock judgement in close direction at DPOS DEV64

3103411DA0 DPOS65-OPEN Result of interlock judgement in open direction at DPOS DEV65

3103411DA2 DPOS65-CLOSE Result of interlock judgement in close direction at DPOS DEV65

GRL200 (Soft 033 & 037)


- 833 -
6F2S1914 (0.37)

 Signal monitoring point


ILK (Function ID: 570001)
Element ID Name Description
3103421DA0 DPOS66-OPEN Result of interlock judgement in open direction at DPOS DEV66

3103421DA2 DPOS66-CLOSE Result of interlock judgement in close direction at DPOS DEV66

3103431DA0 DPOS67-OPEN Result of interlock judgement in open direction at DPOS DEV67

3103431DA2 DPOS67-CLOSE Result of interlock judgement in close direction at DPOS DEV67

3103441DA0 DPOS68-OPEN Result of interlock judgement in open direction at DPOS DEV68

3103441DA2 DPOS68-CLOSE Result of interlock judgement in close direction at DPOS DEV68

3103451DA0 DPOS69-OPEN Result of interlock judgement in open direction at DPOS DEV69

3103451DA2 DPOS69-CLOSE Result of interlock judgement in close direction at DPOS DEV69

3103461DA0 DPOS70-OPEN Result of interlock judgement in open direction at DPOS DEV70

3103461DA2 DPOS70-CLOSE Result of interlock judgement in close direction at DPOS DEV70

3103471DA0 DPOS71-OPEN Result of interlock judgement in open direction at DPOS DEV71

3103471DA2 DPOS71-CLOSE Result of interlock judgement in close direction at DPOS DEV71

3103481DA0 DPOS72-OPEN Result of interlock judgement in open direction at DPOS DEV72

3103481DA2 DPOS72-CLOSE Result of interlock judgement in close direction at DPOS DEV72

3104011DA0 TPOS1-P1 Result of interlock judgement to switch for P1 at TPOS DEV01

3104011DA2 TPOS1-P2 Result of interlock judgement to switch for P2 at TPOS DEV01

3104011DA4 TPOS1-P3 Result of interlock judgement to switch for P3 at TPOS DEV01

3104021DA0 TPOS2-P1 Result of interlock judgement to switch for P1 at TPOS DEV02

3104021DA2 TPOS2-P2 Result of interlock judgement to switch for P2 at TPOS DEV02

3104021DA4 TPOS2-P3 Result of interlock judgement to switch for P3 at TPOS DEV02

3104031DA0 TPOS3-P1 Result of interlock judgement to switch for P1 at TPOS DEV03

3104031DA2 TPOS3-P2 Result of interlock judgement to switch for P2 at TPOS DEV03

3104031DA4 TPOS3-P3 Result of interlock judgement to switch for P3 at TPOS DEV03

3104041DA0 TPOS4-P1 Result of interlock judgement to switch for P1 at TPOS DEV04

3104041DA2 TPOS4-P2 Result of interlock judgement to switch for P2 at TPOS DEV04

3104041DA4 TPOS4-P3 Result of interlock judgement to switch for P3 at TPOS DEV04

3104051DA0 TPOS5-P1 Result of interlock judgement to switch for P1 at TPOS DEV05

3104051DA2 TPOS5-P2 Result of interlock judgement to switch for P2 at TPOS DEV05

3104051DA4 TPOS5-P3 Result of interlock judgement to switch for P3 at TPOS DEV05

3104061DA0 TPOS6-P1 Result of interlock judgement to switch for P1 at TPOS DEV06

3104061DA2 TPOS6-P2 Result of interlock judgement to switch for P2 at TPOS DEV06

3104061DA4 TPOS6-P3 Result of interlock judgement to switch for P3 at TPOS DEV06

3104071DA0 TPOS7-P1 Result of interlock judgement to switch for P1 at TPOS DEV07

3104071DA2 TPOS7-P2 Result of interlock judgement to switch for P2 at TPOS DEV07

3104071DA4 TPOS7-P3 Result of interlock judgement to switch for P3 at TPOS DEV07

3104081DA0 TPOS8-P1 Result of interlock judgement to switch for P1 at TPOS DEV08

3104081DA2 TPOS8-P2 Result of interlock judgement to switch for P2 at TPOS DEV08

3104081DA4 TPOS8-P3 Result of interlock judgement to switch for P3 at TPOS DEV08

3104091DA0 TPOS9-P1 Result of interlock judgement to switch for P1 at TPOS DEV09

3104091DA2 TPOS9-P2 Result of interlock judgement to switch for P2 at TPOS DEV09

3104091DA4 TPOS9-P3 Result of interlock judgement to switch for P3 at TPOS DEV09

31040A1DA0 TPOS10-P1 Result of interlock judgement to switch for P1 at TPOS DEV10

31040A1DA2 TPOS10-P2 Result of interlock judgement to switch for P2 at TPOS DEV10

31040A1DA4 TPOS10-P3 Result of interlock judgement to switch for P3 at TPOS DEV10

GRL200 (Soft 033 & 037)


- 834 -
6F2S1914 (0.37)

 Signal monitoring point


ILK (Function ID: 570001)
Element ID Name Description
31040B1DA0 TPOS11-P1 Result of interlock judgement to switch for P1 at TPOS DEV11

31040B1DA2 TPOS11-P2 Result of interlock judgement to switch for P2 at TPOS DEV11

31040B1DA4 TPOS11-P3 Result of interlock judgement to switch for P3 at TPOS DEV11

31040C1DA0 TPOS12-P1 Result of interlock judgement to switch for P1 at TPOS DEV12

31040C1DA2 TPOS12-P2 Result of interlock judgement to switch for P2 at TPOS DEV12

31040C1DA4 TPOS12-P3 Result of interlock judgement to switch for P3 at TPOS DEV12

31040D1DA0 TPOS13-P1 Result of interlock judgement to switch for P1 at TPOS DEV13

31040D1DA2 TPOS13-P2 Result of interlock judgement to switch for P2 at TPOS DEV13

31040D1DA4 TPOS13-P3 Result of interlock judgement to switch for P3 at TPOS DEV13

31040E1DA0 TPOS14-P1 Result of interlock judgement to switch for P1 at TPOS DEV14

31040E1DA2 TPOS14-P2 Result of interlock judgement to switch for P2 at TPOS DEV14

31040E1DA4 TPOS14-P3 Result of interlock judgement to switch for P3 at TPOS DEV14

31040F1DA0 TPOS15-P1 Result of interlock judgement to switch for P1 at TPOS DEV15

31040F1DA2 TPOS15-P2 Result of interlock judgement to switch for P2 at TPOS DEV15

31040F1DA4 TPOS15-P3 Result of interlock judgement to switch for P3 at TPOS DEV15

3104101DA0 TPOS16-P1 Result of interlock judgement to switch for P1 at TPOS DEV16

3104101DA2 TPOS16-P2 Result of interlock judgement to switch for P2 at TPOS DEV16

3104101DA4 TPOS16-P3 Result of interlock judgement to switch for P3 at TPOS DEV16

3104111DA0 TPOS17-P1 Result of interlock judgement to switch for P1 at TPOS DEV17

3104111DA2 TPOS17-P2 Result of interlock judgement to switch for P2 at TPOS DEV17

3104111DA4 TPOS17-P3 Result of interlock judgement to switch for P3 at TPOS DEV17

3104121DA0 TPOS18-P1 Result of interlock judgement to switch for P1 at TPOS DEV18

3104121DA2 TPOS18-P2 Result of interlock judgement to switch for P2 at TPOS DEV18

3104121DA4 TPOS18-P3 Result of interlock judgement to switch for P3 at TPOS DEV18

3104131DA0 TPOS19-P1 Result of interlock judgement to switch for P1 at TPOS DEV19

3104131DA2 TPOS19-P2 Result of interlock judgement to switch for P2 at TPOS DEV19

3104131DA4 TPOS19-P3 Result of interlock judgement to switch for P3 at TPOS DEV19

3104141DA0 TPOS20-P1 Result of interlock judgement to switch for P1 at TPOS DEV20

3104141DA2 TPOS20-P2 Result of interlock judgement to switch for P2 at TPOS DEV20

3104141DA4 TPOS20-P3 Result of interlock judgement to switch for P3 at TPOS DEV20

3104151DA0 TPOS21-P1 Result of interlock judgement to switch for P1 at TPOS DEV21

3104151DA2 TPOS21-P2 Result of interlock judgement to switch for P2 at TPOS DEV21

3104151DA4 TPOS21-P3 Result of interlock judgement to switch for P3 at TPOS DEV21

3104161DA0 TPOS22-P1 Result of interlock judgement to switch for P1 at TPOS DEV22

3104161DA2 TPOS22-P2 Result of interlock judgement to switch for P2 at TPOS DEV22

3104161DA4 TPOS22-P3 Result of interlock judgement to switch for P3 at TPOS DEV22

3104171DA0 TPOS23-P1 Result of interlock judgement to switch for P1 at TPOS DEV23

3104171DA2 TPOS23-P2 Result of interlock judgement to switch for P2 at TPOS DEV23

3104171DA4 TPOS23-P3 Result of interlock judgement to switch for P3 at TPOS DEV23

3104181DA0 TPOS24-P1 Result of interlock judgement to switch for P1 at TPOS DEV24

3104181DA2 TPOS24-P2 Result of interlock judgement to switch for P2 at TPOS DEV24

3104181DA4 TPOS24-P3 Result of interlock judgement to switch for P3 at TPOS DEV24

3105011DA0 TAP LOWER Result of interlock judgement in down direction at TAP-BCD DEV01

3105011DA2 TAP RAISE Result of interlock judgement in up direction at TAP-BCD DEV01

GRL200 (Soft 033 & 037)


- 835 -
6F2S1914 (0.37)

 Signal monitoring point


ILK (Function ID: 570001)
Element ID Name Description
3105021DA0 TAP2 LOWER Result of interlock judgement in down direction at TAP-BCD DEV02

3105021DA2 TAP2 RAISE Result of interlock judgement in up direction at TAP-BCD DEV02

3105031DA0 TAP3 LOWER Result of interlock judgement in down direction at TAP-BCD DEV03

3105031DA2 TAP3 RAISE Result of interlock judgement in up direction at TAP-BCD DEV03

3105041DA0 TAP4 LOWER Result of interlock judgement in down direction at TAP-BCD DEV04

3105041DA2 TAP4 RAISE Result of interlock judgement in up direction at TAP-BCD DEV04

GRL200 (Soft 033 & 037)


- 836 -
6F2S1914 (0.37)

Double position device function (DPOS)


The double position device (DPOS) function is used when the user wishes to control a device
having On and Off states, which is equivalent to controlling a device from the “Closed” or “Open”
condition; the device is represented as DS or an ES. The DPOS function provides “Operation
counters” and “Operation time measurement”; these features are used for the examination of
the devices, these features are useful when the user wishes to assess the operating time of the
device, which is performed by counting the state-change of the device. The BO circuits
connected with the DPOS function are used for issuing commands; the BI circuits are used for
receiving responses; hence, the user should connect the BI and BO circuits with the DPOS
function(†). The DPOS function includes three logic groups: 1. Select logic, 2. Cancel logic, and
3. Operate logic.
For simplicity, only the DPOS01 function is discussed here; the features in the other
DPOS02–72 functions are identical to the DPOS01 function.
†Note:A binary IO module has binary input circuits (BIs) and binary output circuits
(BOs); the user makes the connection between the DPOS01 function and the
binary IO module using a signal number (is made of a “Function ID” and an
“Element ID”). The signal name and number of the DPOS01 function are listed
later.
Tips: If the user wishes to apply the DPOS function quickly, go to sections 4.8.6 and
4.8.7, where setting of the BI and BO circuits and the mapping of signal-points for
IEC61850 communication is described.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the “G&T position” referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 4.8-1 Comparative table for respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
– Total number of functions‡ – 72
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 837 -
6F2S1914 (0.37)

4.8.1 Select logic for SBO/DIR modes


The user should set scheme switch [DPOS01-CTREN] to On prior to DPOS01 operation. Table
4.8-10 shows all of the scheme switches in the DPOS function.

(i) Receiving “Select command On” from the remote-end


Figure 4.8-1 outlines the reception of the select command ‘On’ from the remote-end.

Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Cancel logic


Failed
Cancel command
Signal reception Select
Selection logic Signal output
IEC61850 decision Success

Cancel logic
Select command Off from the remote-end

Select command On from the local-end


Operate logic
Select command Off from the local-end
Operate command

Select command On by the PLC function Operate logic

Select command Off by the PLC function

Figure 4.8-1 Outline of Select command ‘On’

Input point required mapping


Figure 4.8-2 shows the Select logic when a “Select command On (Remote-ON-Control)” signal
is applied to the DPOS01 function. The logic has the input-point “DEV01_CONTROL_REQ”
for the reception of the select command. That is, the input-point must be mapped for IEC61850
communication. The function will fail to operate if mapping is not performed correctly. We will
discuss how to map the input-points for IEC61850 communication in section 4.8.7.

Output signal to BO
The DPOS01 function can issue a “Select success” signal at the output point
“DPOS01_OSL_BO_FLG”, when the DPOS01 function determines that the “Remote-ON-
Control” signal is true. If the DPOS01 function determines that the “Remote-ON-Control”
signal is not true, the DPOS01 function returns to the “Wait for a command” stage.

GRL200 (Soft 033 & 037)


- 838 -
6F2S1914 (0.37)

Input Select logic in DPOS01 Output

DPOS01 function (Function ID: 512001)


Command “Remote-On-Control”
For SBO operation
512001_7003016D08 DEV01_CONTROL_REQ Select command
with ILK† condition & 1≥ &
To “Wait for a next
For DIR operation command”
To BO connection
Operate command
with ILK† condition & DPOS01_OSL_BO_CSF”
(512001_8603011DC6)
ILK† condition (“ON”) passed
DPOS01-Close 0 t
Select on “Success”

For SBO operation 0.1s

Select command &


without ILK† condition
To “Wait for a command”
For DIR operation 0 t
Select “Failed”
Operate command
& 0.6s
without ILK† condition

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.8-2 Select ‘On’ from the remote-end in DPOS01††


†Note:The software interlocking (ILK) function provides the operation criteria for “On”.
The ILK function is discussed separately; note that the operation criteria is
defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPOS01 operation is blocked for the ASEQ function being
in operation. For more information of the ASEQ function, see Chapter Control and
monitoring application: Automatic sequence control function.
*Note:The DPOS01 function can run in either the “SBO mode” or the “DIR mode” using
a signal called “ctlmodel” when communication is implemented using IEC61850.
To use this signal, the user must map it for IEC61850 communication.
††Note: To identify the input and output points of the other DPOS logics, see Table 4.8-5
and Table 4.8-9.

GRL200 (Soft 033 & 037)


- 839 -
6F2S1914 (0.37)

(ii) Receiving “Select command Off” from the remote-end


Figure 4.8-3 outlines the reception of the Select command ‘Off ’ from the remote-end.

Wait for a command

Select stage Wait for a next command

Cancel logic

Select command On from the remote-end Cancel command

Select command Off from the remote-end


Failed
Cancel logic
Signal reception Select
Select logic Signal output
IEC61850 decision Success

Select command On from the local-end


Operate logic
Select command Off from the local-end
Operate command

Select command On by the PLC function Operate logic

Select command Off by the PLC function

Figure 4.8-3 Outline of Select command ‘Off’

Input point mapped from the communication


Figure 4.8-4 shows the Select logic when a “Select command Off (Remote-OFF-Control)” signal
is applied at the input-point “DEV01_CONTROL_REQ”.

Output signal to BO
The DPOS01 function, in Figure 4.8-4, can issue a “Select success” signal at the output point
“DPOS01_FSL_BO_FLG” when the DPOS01 function determines that the received “Select
command Off (Remote-OFF-Control)” signal is true. If the DPOS01 function determines that
the “Remote-OFF-Control” signal is not true, the DPOS01 function returns to the “Wait for a
command” stage.

GRL200 (Soft 033 & 037)


- 840 -
6F2S1914 (0.37)

Input Selection logic in DPOS01 Output

DPOS01 function (Function ID: 512001)


Command “Remote-Off-Control”
For SBO operation
512001_7001016D08 DEV01_CONTROL_REQ Select command
with ILK† condition & 1≥ &

For DIR operation


To BO connection
Operate command
with ILK† condition & “DPOS01_FSL_BO_FLG”
ILK† condition (“Off”) passed (512001_8A01011DC4)
DPOS01-Open 0 t
Select “success”

For SBO operation 0.1s

Select command &


without ILK† condition
To “Wait for a command”
For DIR operation 0 t
Select “Failed”
Operate command
& 0.6s
without ILK† condition

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.8-4 Select ‘Off’ from the remote-end in DPOS01††


†Note:The ILK function provides the operation criteria for “Off”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information of the ASEQ function, see Chapter Control
and monitoring application: Automatic sequence control function.
††Note: To know the input and output points of the other DPOS logics, see Table 4.8-5
and Table 4.8-9.

GRL200 (Soft 033 & 037)


- 841 -
6F2S1914 (0.37)

(iii) Receiving “Select command On” from the local-end


Figure 4.8-5 outlines the reception of the Select command ‘On’ from the local-end.

Wait for a command

Select stage Wait for a next command

Cancel logic

Cancel command
Select command On from the remote-end

Select command Off from the remote-end


Cancel logic

Select command On from the local-end


Failed

Signal reception Select


Select logic Signal output
from the front panel decision Success
Operate logic

Select command Off from the local-end Operate command

Select command On by the PLC function Operate logic

Select command Off by the PLC function

Figure 4.8-5 Outline of Select command ‘On’

Input signal generated at the local-end


Figure 4.8-6 shows the Select logic when “Select command On (Local-ON-Control)” signal is
applied to the DPOS01 function. The signal is provided when an “On” key is pressed on the
IED front panel; the user is not required to take account of mapping. Note that the user should
set the scheme switch [DPOS01-CTRAHMI] to SBO when operation from the IED front panel
is required, we discuss how to set this in chapter User interface: Control sub-menu.

Output signal to BO
When the “select condition” signal is true, the DPOS01 function can issue a “Select success”
signal at the output-point “DPOS01_OSL_BO_CSF”.
Note: The “DPOS01_OSL_BO_CSF” signal is the same as the signal shown in Figure
4.8-2. If the input signal “Local-ON-Control” is not true, the DPOS01 function
returns to the “Wait for a command” stage.

GRL200 (Soft 033 & 037)


- 842 -
6F2S1914 (0.37)

Input Selection logic in DPOS01 Output

DPOS01 function (Function ID: 512001)


For SBO operation
Command “Local-On-Control” Select command
with ILK† condition & 1≥ &
To “Wait for a next
For DIR operation SBO command”
Operate command To BO connection
ILK† condition (“ON”) passed with ILK† condition & “DPOS01_OSL_BO_CSF”
DPOS01-Close (512001_8603011DC6)
DIR
ILK† bypassing 1≥ 0 t
Select “success”
ICB_STATE
0.1s

To “Wait for a command”


0 t
Select “Failed”

0.6s

[DPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.8-6 Select ‘On’ on the front panel in DPOS01††


†Note:The ILK function provides the operation criterion for “On”. For testing, nullifying
the ILK function is possible using “Interlock bypassing”. “Interlock bypassing” is
indicated by the status “ICB” in a software switch controller (SOFTSW).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the other DPOS logics, see Table 4.8-9.

GRL200 (Soft 033 & 037)


- 843 -
6F2S1914 (0.37)

(iv) Receiving “Select command Off” from the local-end


Figure 4.8-7 outlines the reception of the Select command ‘Off ’ from the local-end.

Wait for a command

Select stage Wait for a next command

Cancel logic
Select command On from the remote-end Cancel command

Select command Off from the remote-end

Cancel logic
Select command On from the local-end

Select command Off from the local-end


Failed

Signal reception Select


Select logic Signal output Operate logic
from the front panel decision Success
Operate command

Select command On by the PLC function Operate logic

Select command Off by the PLC function

Figure 4.8-7 Outline of Select command ‘Off’

Input signal generated at the local-end


Figure 4.8-8 shows the Select logic when a “Select command Off (Local-OFF-Control)” signal
is received is applied to the DPOS01 function. The signal is provided when the user presses
the “OFF” key on the IED front panel; the user is not required to map the signal from IEC61850
communication.

Output signal to BO
When the “select condition” signal is true, the DPOS01 function can issue a “Select success”
signal at the output-point “DPOS01_FSL_BO_FLG”.
1Note: The signal “DPOS01_FSL_BO_FLG” is the same as the signal shown in Figure
4.8-4. If the signal “Local-OFF-Control” is not true, the DPOS01 function returns
to the “Wait for a command” stage.

GRL200 (Soft 033 & 037)


- 844 -
6F2S1914 (0.37)

Input Selection logic in DPOS01 Output

DPOS01 function (Function ID: 512001)


For SBO operation
Command “Local-Off-Control” Select command
with ILK† condition & 1≥ &
For DIR operation SBO
Operate command To BO connection

ILK† condition (“Off”) passed with ILK† condition & “DPOS01_FSL_BO_FLG”


DPOS01-Open (512001_8A03011DC4)
DIR
ILK† bypassing 1≥ 0 t
Select “success”
ICB_STATE
0.1s

To “Wait for a command”


0 t Select “Failed”

0.6s

[DPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.8-8 Select ‘Off’ on the front panel in DPOS01††


†Note:The ILK function provides the operation criteria for “Off”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the other DPOS logics, see Table 4.8-9.

GRL200 (Soft 033 & 037)


- 845 -
6F2S1914 (0.37)

(v) Receiving “Select command On” by PLC function


Figure 4.8-9 outlines the reception of the select command ‘On’ by the PLC function.

Wait for a command

Select stage Wait for a next command

Cancel logic

Cancel command
Select command On from the remote-end

Select command Off from the remote-end


Cancel logic
Select command On from the local-end

Select command Off from the local-end

Operate logic
Select command On by PLC function
Failed Operate command

PLC logic programmed Select


Select logic Signal output
by the user decision Success
Operate logic

Select command Off by the PLC function

Figure 4.8-9 Outline of Select command ‘On’

Input signal from the PLC function


Figure 4.8-10 shows the Select logic when a “select command On (PLC-On-Control)” signal is
generated by the PLC function. There are two input points for reception of this signal: the
former connection point, (PLC#1) is used for the reception of the select-command requiring the
interlock check, the later connection point, (PLC#2) is used for the reception of the select-
command not requiring the interlock check. That is, for the DPOS01 function, when the “Select
command On (PLC-ON-Control)” signal generated in the user-programmed logic is applied for
the select logic and when the interlock check is required in the select logic, use the connection
point (PLC#1: e.g.DEV01_CL_INTERLOCK). Alternatively, if the interlock check is not
required, use the other connection point (PLC# 2: e.g., DEV01_CL_COMMAND) for the
injection. PLC#1 and PLC#2 is shown in Table 4.8-2.

Output signal to BO
The DPOS01 function, in Figure 4.8-10, can issue a “Select success” signal at the output-point
“DPOS01_OSL_BO_CSF”1.
1Note: The “DPOS01_OSL_BO_CSF” signal is the same signal as that shown in Figure
4.8-2.

GRL200 (Soft 033 & 037)


- 846 -
6F2S1914 (0.37)

Signals from user-PLC logic Select logic in DPOS01 Output

DPOS01 function (Function ID: 512001)

1≥ &
ON-control command requiring ILK† checking To “Wait for a next
For DIR operation
(PLC #1 connection point) command”
Operate command
512001 800301EE33 DEV01_CL_INTERLOCK To BO connection
with ILK† condition
& “DPOS01_OSL_BO_CSF”
(512001_8603011DC6)
ILK† condition (“ON”) passed
DPOS01-Close 0 t
Select “success”
0.1s

ON-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point) 0 t
Operate command Select “Failed”
512001 800301EE32 DEV01_CL_COMMAND
without ILK† condition & 0.6s

PLC in DIR operate

Select condition‡

Figure 4.8-10 Select ‘On’ using the PLC function in DPOS01††


†Note:The software interlocking (ILK) function provides the operation criteria for “On”.
The ILK function is discussed separately; note that the operation criteria is
defined in the ILK function itself (i.e., the user cannot set the condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
††Note: To identify the input and output points of the other DPOS logics, see Table 4.8-2
for the inputs (PLC#1 and PLC#2) and Table 4.8-9 for the outputs.

GRL200 (Soft 033 & 037)


- 847 -
6F2S1914 (0.37)

(vi) Receiving “Select command Off” by PLC function


Figure 4.8-11 outlines the reception of the Select command ‘Off ’ by the PLC function.

Wait for a command

Select stage Wait for a next command

Cancel logic

Cancel command
Select command On from the remote-end

Select command Off from the remote-end


Cancel logic
Select command On from the local-end

Select command Off from the local-end

Operate logic
Select command On by the PLC function
Operate command

Select command Off by the PLC function


Failed
Operate logic
PLC logic programmed Select
Select logic Signal output
by the user decision Success

Figure 4.8-11 Outline of Select command Off

Input signal from the PLC function


Figure 4.8-12 shows the Select logic when a “select command Off (PLC-Off-Control)” signal is
generated by the PLC function. There are two input points for the reception of this signal: like
in signal “select command On (PLC-On-Control): That is, if interlock checking is required, use
the connection point (PLC#1: e.g. DEV01_OP_INTERLOCK). Alternatively, if the interlock
check is not required, use the connection point (PLC# 2: e.g. DEV01_OP_COMMAND). PLC#1
and PLC#2 are shown in Table 4.8-3.

Output signal to BO
The DPOS01 function, in Figure 4.8-12, can issue a “Select success” signal at the output point
“DPOS01_FSL_BO_CSF”1.
1Note: The output point “DPOS01_FSL_BO_CSF” is the same signal as that shown in
Figure 4.8-4.

GRL200 (Soft 033 & 037)


- 848 -
6F2S1914 (0.37)

Signals from user PLC logic Select logic in DPOS01 Output

DPOS01 function (Function ID: 512001)

1≥ &
OFF-control command requiring ILK† checking For DIR operation
(PLC#1 connection point)
Operate command with To BO connection
512001 800301EE31 DEV01_OP_INTERLOCK
ILK† condition & “DPOS01_FSL_BO_CSF”
ILK† condition (“OFF”) passed (512001_8A03011DC4)
DPOS01-Open 0 t
Select “success”
0.1s

OFF-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point)
0 t
Operate command Select “Failed”
512001 800301EE30 DEV01_OP_COMMAND
without ILK† condition & 0.6s

PLC in DIR operate

Select condition‡

Figure 4.8-12 Select ‘Off’ by the PLC function in DPOS01††


†Note:The ILK function provides the operation criteria for “Off”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
††Note: To identify the input and output points of the other DPOS logics, see Table 4.8-3
for the inputs (PLC#1 and PLC#2) and Table 4.8-9 for the outputs.

GRL200 (Soft 033 & 037)


- 849 -
6F2S1914 (0.37)

(vii) Select condition


Figure 4.8-13 shows the select condition logic in the DPOS01 function. The DPOS01 function
checks the condition for the Select command using the signal “DPOS1_3PH_STATE” (see Table
4.8-32). If the original logic does not meet with the requirements of the user, the following
alternatives are available:
1. The user can replace the original logic with alternative logic,
2. The user can add additional logic to the original logic.

How to replace the original logic


If the user wishes to replace the select condition logic, the user can replace it using the PLC
connection point “User configurable condition”:
1. Connect the user-customized logic using “DPOS01IN_TMP_31”, which is listed as
PLC#2 in Table 4.8-7.
2. Set the scheme switch [DPOS01-LGSLFFCT] to PLC.

How to add another select condition signal


If adding another condition is required, the user can add a signal using the PLC connection
point “Additional condition”.
1. Add a user-preferred signal using “DPOS01IN_TMP_32”, which is listed as PLC#1 in
Table 4.8-7.
2. Set the scheme switch [DPOS01-LGSLFFCT] to Fixedlogic.

GRL200 (Soft 033 & 037)


- 850 -
6F2S1914 (0.37)

From SOTFSW*1 DPOS01 function (Function ID: 512001)


Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To select logic
Other devices traveling detected*3
Traveling OR Unmatched condition detected *5 Select condition

Function “Automatic sequence control” is in progress


ASEQ_MULTI_SEL Event suppression detected *6
From TRC*4 = DPOS01_F_QLT_SPP
General trip (512001 8103011F5F)
GEN.TRIP
BI board connection error detected*7
= DPOS01_F_BI_ERR
(512001 8203011F60)

Command “ON control” received &


Command “OFF control” received &
received
DPOS01_3PH_STATE
(512001 3103011001)
[SCDEN]*8 Appearance of the
controls in the same
OFF direction
Additional condition (PLC#1 connection point)
512001 810301EE62 DPOS01IN_TMP_32
[DPOS01-LGSLFFCT]
User configurable condition (PLC#2 connection point)
Fixedlogic
512001 800301EE61 DPOS01IN_TMP_31 &

From Control hierarchy *9 (PLC#3 connection point)

512001 820301ED50 DPOS01IN_TMP_28


&
From CMNCTRL
Serious error detection
SERI_ERR
[DPOS01-CTREN]

On

Figure 4.8-13 Select condition logic for ‘ON/OFF’ in DPOS01*10


1Note: “Command Blocking” disables any operation except its own; the “Command
Blocking” is initiated by the status “CBK” in a software switch controller
(SOTFSW). The IEC61850 standard defines “Command Blocking” as “CmdBlk”.
For more information on “CBK”, see Chapter Control and monitoring application:
Software switch controller. See the signal ““CBK_STATE” of Table 4.8-6.
2Note: “Double Command Blocking” (DCB) is an operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as “DCB
RCV OR” in Table 4.8-6. For more information see Chapter Control and
monitoring application:Common controls.
3Note: If the event “device-travelling” is detected in the CMNCTRL function, it indicates
that another operator is changing the status of a device. Thus, the IED should
inhibit the operation of any device for the duration that the event is detected. The
detected signal is denoted as “Travelling OR” in Table 4.8-6.
4Note: If the issue of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issues at the output_point “GEN.TRIP” in Table
4.8-6.
5Note: Criteria “unmatched conditions” are decided when “Test-bit status” in a command

GRL200 (Soft 033 & 037)


- 851 -
6F2S1914 (0.37)

is not identical to “IED test status”.


6Note: The function “Event suppression” can detect chattering on BI circuits. (See section
4.8.6(i)-3)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The Common control (CMNCTRL) function can test and check the ‘On and Off
operations performed by the logic. When the user sets Off for scheme switch
[SCDEN], the operation of the logic is blocked if the logic is running in the same
operation-direction compared with the previous operation-direction (i.e., when on
(off) is performed sequentially). On the other hand, if On is set for the scheme
switch, the logic is not blocked.
9Note: The user will need to program the PLC logic “Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection point “DPOS01IN_TMP_28”. For more information, see
Chapter Control and monitoring application: Control hierarchy . See PLC#3 of
Table 4.8-7.
10Note: To identify the input point of the other DPOS, see Table 4.8-7 for PLC#1 and
PLC#2.

GRL200 (Soft 033 & 037)


- 852 -
6F2S1914 (0.37)

(viii) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicated that the signal is provided for optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.8-2 PLC Connection points (Input points for Command ‘On’)
Signal Number Signal Name Description M/O
512001 800301EE32 DEV01_CL_COMMAND DPOS01 PLC On-control checking with interlock(PLC#1) O
512001 800302EE32 DEV02_CL_COMMAND DPOS02 PLC On-control checking with interlock(PLC#1) O
512001 800303EE32 DEV03_CL_COMMAND DPOS03 PLC On-control checking with interlock(PLC#1) O
…. …. ….
512001 800348EE32 DEV72_CL_COMMAND DPOS72 PLC On-control checking with interlock(PLC#1) O
512001 800301EE33 DEV01_CL_INTERLOCK DPOS01 PLC On-control without checking(PLC#2) O
512001 800302EE33 DEV02_CL_INTERLOCK DPOS02 PLC On-control without checking(PLC#2) O
512001 800303EE33 DEV03_CL_INTERLOCK DPOS03 PLC On-control without checking(PLC#2) O
…. …. ….
512001 800348EE33 DEV72_CL_INTERLOCK DPOS72 PLC On-control without checking(PLC#2) O

Table 4.8-3 PLC Connection points (Input points for Command ‘Off’)
Signal Number Signal Name Description M/O
512001 800301EE30 DEV01_OP_COMMAND DPOS01 PLC Off-control checking with interlock(PLC#1) O
512001 800302EE30 DEV02_OP_COMMAND DPOS02 PLC Off-control checking with interlock(PLC#1) O
512001 800303EE30 DEV03_OP_COMMAND DPOS03 PLC Off-control checking with interlock(PLC#1) O
…. …. ….
512001 800348EE30 DEV72_OP_COMMAND DPOS72 PLC Off-control checking with interlock(PLC#1) O
512001 800301EE31 DEV01_OP_INTERLOCK DPOS01 PLC Off-control without checking(PLC#2) O
512001 800302EE31 DEV02_OP_INTERLOCK DPOS02 PLC Off-control without checking(PLC#2) O
512001 800303EE31 DEV03_OP_INTERLOCK DPOS03 PLC Off-control without checking(PLC#2) O
…. …. ….
512001 800348EE31 DEV72_OP_INTERLOCK DPOS72 PLC Off-control without checking(PLC#2) O

Table 4.8-4 PLC Connection points (Interlock for Command ‘On/Off’)


Signal Number Signal Name Description M/O
570001 3103021DA2 DPOS01-Close DPOS01 interlock condition for On control. N/A
570001 3103031DA2 DPOS02-Close DPOS02 interlock condition for On control. N/A
570001 3103041DA2 DPOS03-Close DPOS03 interlock condition for On control. N/A
… … …
570001 3103481DA2 DPOS72-Close DPOS72 interlock condition for On control. N/A
570001 3103011DA0 DPOS01-Open DPOS01 interlock condition for Off control. N/A
570001 3103021DA0 DPOS02-Open DPOS02 interlock condition for Off control. N/A
570001 3103031DA0 DPOS03-Open DPOS03 interlock condition for Off control. N/A
…. …. ….
570001 3103481DA0 DPOS72-Open DPOS72 interlock condition for Off control. N/A

GRL200 (Soft 033 & 037)


- 853 -
6F2S1914 (0.37)

Table 4.8-5 Mapping points for the reception of control commands


Signal Number Signal Name Description M/O
512001 7003016D08 DEV01_CONTROL_REQ DPOS01 control command received. (Mapping Data) M
512001 7003026D08 DEV02_CONTROL_REQ DPOS02 control command received. (Mapping Data) M
512001 7003036D08 DEV03_CONTROL_REQ DPOS03 control command received. (Mapping Data) M
… … …
512001 7003486D08 DEV72_CONTROL_REQ DPOS72 control command received. (Mapping Data) M

Table 4.8-6 Input signals to condition logic


Signal Number Signal Name Description M/O
522001 000A011001 CBK_STATE Command Blocking status ( Off / Blocked) N/A
523001 000D001F40 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A
5A0001 0008001F41 DCB RCV OR Double Command Blocking(DCB) is in progress. N/A
5A0001 0008001F40 Travelling OR Travelling events are detected. N/A
4A0001 8300001B6F GEN.TRIP General trip N/A
5A0001 3108003F40 SDCEN (This is setting of CMNCTRL) N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A

Table 4.8-7 PLC Connection points (Input signals for select condition logic)
Signal Number Signal Name Description M/O
512001 810301EE62 DPOS01IN_TMP_32 DPOS01 additional failure condition(PLC#1) O
512001 810302EE62 DPOS02IN_TMP_32 DPOS02 additional failure condition(PLC#1) O
512001 810303EE62 DPOS03IN_TMP_32 DPOS03 additional failure condition(PLC#1) O
…. …. ….
5A0101 801016EF40 DPOS72IN_TMP_32 DPOS72 additional failure condition(PLC#1) O
512001 800301EE61 DPOS01IN_TMP_31 DPOS01 user configurable select condition(PLC#2) O
512001 800302EE61 DPOS02IN_TMP_31 DPOS02 user configurable select condition(PLC#2) O
512001 800303EE61 DPOS03IN_TMP_31 DPOS03 user configurable select condition(PLC#2) O
… … …
512001 800348EE61 DPOS72IN_TMP_31 DPOS72 user configurable select condition(PLC#2) O
512001 820301ED50 DPOS01IN_TMP_28 DPOS01 control hierarchy condition(PLC#3) M
512001 820302ED50 DPOS02IN_TMP_28 DPOS02 control hierarchy condition(PLC#3) M
512001 820303ED50 DPOS03IN_TMP_28 DPOS03 control hierarchy condition(PLC#3) M
…. …. ….
512001 820348ED50 DPOS04IN_TMP_28 DPOS20 control hierarchy condition(PLC#3) M

Table 4.8-8 PLC Monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
512001 8003011F5A DPOS01_SC_ST_ERR DPOS01 select command mode is invalid.
512001 8003021F5A DPOS02_SC_ST_ERR DPOS02 select command mode is invalid.
512001 8003031F5A DPOS03_SC_ST_ERR DPOS03 select command mode is invalid.
…. …. ….
512001 8003481F5A DPOS72_SC_ST_ERR DPOS72 select command mode is invalid.
512001 8103011F5F DPOS01_F_QLT_SPP Event suppression detected (DPOS01)
512001 8103021F5F DPOS02_F_QLT_SPP Event suppression detected (DPOS02)
512001 8103031F5F DPOS03_F_QLT_SPP Event suppression detected (DPOS03)
…. …. ….
512001 8103481F5F DPOS72_F_QLT_SPP Event suppression detected (DPOS72)
512001 8203011F60 DPOS01_F_BI_ERR BI connection error detected(DPOS01)
512001 8203021F60 DPOS02_F_BI_ERR BI connection error detected(DPOS02)
512001 8203031F60 DPOS03_F_BI_ERR BI connection error detected(DPOS03)

GRL200 (Soft 033 & 037)


- 854 -
6F2S1914 (0.37)

Signal Number Signal Name Description


…. …. ….
512001 8203481F60 DPOS72_F_BI_ERR BI connection error detected(DPOS72)

Table 4.8-9 PLC Monitoring points (On/Off output-signal for BIO)


Signal Number Signal Name Description
512001 8A03011DC4 DPOS01_FSL_BO_FLG DPOS01 select (Off) command for Binary Output.
512001 8A03021DC4 DPOS02_FSL_BO_FLG DPOS02 select (Off) command for Binary Output.
512001 8A03031DC4 DPOS03_FSL_BO_FLG DPOS03 select (Off) command for Binary Output.
…. …. ….
512001 8A03481DC4 DPOS72_FSL_BO_FLG DPOS72 select (Off) command for Binary Output.
512001 8603011DC6 DPOS01_OSL_BO_FLG DPOS01 select (ON) command for Binary Output.
512001 8603021DC6 DPOS02_OSL_BO_FLG DPOS02 select (ON) command for Binary Output.
512001 8603031DC6 DPOS03_OSL_BO_FLG DPOS03 select (ON) command for Binary Output.
…. …. …..
512001 8603481DC6 DPOS72_OSL_BO_FLG DPOS72 select (On) command for Binary Output.

(ix) Setting names


Note: The “xx” within “DPOSxx” represents the DPOS function number. (e.g., if DPOS03
is considered, the “xx” is equal to “03”. The numbers used for “xx” can be
represented from “01” to “72”.)

Table 4.8-10 Settings for select logics


Setting Name Description Default Setting item or value
DPOSxx-CTREN Activate control function of DPOSxx On Off / On
DPOSxx-LGSLFFCT Logic selector for select condition in DPOSxx Fixedlogic Fixedlogic / PLC
DPOSxx-CTRAHMI Activate local panel control in DPOSxx SBO DIR/ SBO

GRL200 (Soft 033 & 037)


- 855 -
6F2S1914 (0.37)

4.8.2 Cancel logic for SBO mode


In the SBO control mode the reception of a cancel command is possible; when the cancel
conditions are satisfied, accordingly the function can discard the select command; finally, the
operation returns to the initial stage (i.e., “Wait for a command”.)

(i) Receiving “Cancel” from the remote-end


Figure 4.8-14 depicts the cancel command procedure for a cancel command initiated from the
remote-end.

Wait for a command

Select logics Wait for a next command

Select command On from the remote-end Cancel from the remote-end


Success

Select command Off from the remote-end Cancel


Signal reception in
Cancel logic Do nothing
IEC61850 decision Failed
Select command On from the local-end

Select command Off from the local-end


Cancel from the local-end
Select command On by the PLC function

Select command Off by the PLC function


Operate logic
Operate command

Operate logic

Figure 4.8-14 Outline of ‘cancel’ command from the remote-end

Input point required mapping


Figure 4.8-15 depicts the cancel logic when a “Cancel command (Remote-Cancel)” signal is
applied to the DPOS01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the signal “Select command On (Remote-ON-Control)”.

Output signal to BO
The DPOS01 function can issue a “Success to cancel” signal at the monitoring point
“DPOS01_CC_SS”, when the DPOS01 function has determined that the signal “Remote-cancel”
is true. Another signal “Operation failed” is issued at monitoring point “DPOS01_CC_FS” if
the DPOS01 function is able to determine that the signal “Remote-cancel” is not true.

GRL200 (Soft 033 & 037)


- 856 -
6F2S1914 (0.37)
510001 7001016D08

Input Cancel logic in DPOS01 Output

DPOS01 function (Function ID: 512001) To “Wait for a command”


Command “Remote-cancel”
“DPOS01_ CC_SS”
Cancel command
510001_7001016D08 DEV01_CONTROL_REQ (512001_8603011E95)
&
Successes to cancel

Cancel condition† & “Do nothing”

“DPOS01_CC_FS”
(512001_8703011E96)

Operation Failed

Figure 4.8-15 ‘Cancel’ from the remote-end in DPOS01


†Note: The “cancel condition” logic shall be seen in Figure 4.8-18.

(ii) Receiving “Cancel” from the local-end


Figure 4.8-16 depicts the cancel command procedure for a cancel command initiated from the
local-end.

Wait for a command

Select logics Wait for a next command

Cancel from the remote end


Selecting On from remote-end

Selecting Off from remote-end


Cancel from the front panel
Success
Selecting On from front panel
Press cancel Cancel
Selecting Off from front panel Cancel logic Do nothing
command decision Failed

Selecting On by the PLC function

Selecting Off by the PLC function


Operate logic
Operate command

Operate logic

Figure 4.8-16 Outline of ‘cancel’ command from the local-end

Input signal generated at the local-end


Figure 4.8-17 depicts the cancel logic when a “Cancel command (Local-cancel)” signal is applied
to the DPOS01 function. The signal is generated when the “Cancel” key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
“Local-cancel” signal, the logic ia able to output a result signal, provided that the “cancel
condition” checking is satisfied.

GRL200 (Soft 033 & 037)


- 857 -
6F2S1914 (0.37)
510001 7001016D08

Input Cancel logic in DPOS01 Output

DPOS01 function (Function ID: 512001) To “Wait for a command”


“DPOS01_ CC_SS”
Cancel command (512001_8603011E95)
Command “Local-cancel”
& Successes of cancel

Cancel condition & “Do nothing”


“DPOS01_CC_FS”
(512001_8703011E96)

Operation Failed

Figure 4.8-17 ‘Cancel’ from the front panel

Output signal to BO
The DPOS01 function, illustrated in Figure 4.8-17, is able to issue a “Success of cancel” signal
at the monitoring point “DPOS01_CC_SS”, when the DPOS01 function determines that the
signal “Local-Cancel” is true.

(iii) Cancel condition logic


Figure 4.8-18 shows the cancel condition logic. As the criteria, “Unmatched condition detected”
is connected normally for the cancel logic, set Fixedlogic for the scheme switch [DPOS01-
LGCNFFCT].
DPOS01 function (Function ID: 512001)

Unmatched condition detected *1 To cancel logic in


& 1≥ DPOS01

[DPOS01-LGCNFFCT]
PLC#1
User configurable condition (PLC connection point)
Fixedlogic
512001 800301EE69 DPOS01IN_TMP_44 &

Figure 4.8-18 Logic “Cancel condition” in DPOS01


1Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status” as in Figure 4.8-13.
2Note: With the exception of the above ‘cancel-condition’ logic, there is an operate-
condition logic within the DPOS01 function; the operate-condition logic will
always checks conditions. That is, the user is required to set either the “operate-
condition” or the “cancel-condition” logic.

If the original logic does not meet with the requirement of the user, it can be relpced using
the connection point “User configurable condition”.

1. Connect the user-customized logic with the “DPOS01IN_TMP_44”, which is listed


in Table 4.8-11.
2. Set scheme switch [DPOS01-LGCNFFCT] to PLC.

GRL200 (Soft 033 & 037)


- 858 -
6F2S1914 (0.37)

(iv) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicates that the signal is provided for the optional use.
“M” indicates that the user should map/set/configure using the signal;
otherwise, the user may experience an operational failure if the default
settings are used.
“N/A” indicates that the user cannot change the state of the signal.

Table 4.8-11 PLC connection points (Input signal for ‘cancel’ condition logic)
Signal Number Signal Name Description M/O
512001 800301EE69 DPOS01IN_TMP_44 DPOS01 user configurable cancel condition O
512001 800302EE69 DPOS02IN_TMP_44 DPOS02 user configurable cancel condition O
512001 800303EE69 DPOS03IN_TMP_44 DPOS03 user configurable cancel condition O
… … … O
512001 800348EE69 DPOS72IN_TMP_44 DPOS72 user configurable cancel condition O

Table 4.8-12 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
512001 8603011E95 DPOS01_CC_SS DPOS01 cancel success
512001 8603021E95 DPOS02_CC_SS DPOS02 cancel success
512001 8603031E95 DPOS03_CC_SS DPOS03 cancel success
… … …
512001 8603481E95 DPOS72_CC_SS DPOS72 cancel success
512001 8703011E96 DPOS01_CC_FS DPOS01 cancel failed
512001 8703021E96 DPOS02_CC_FS DPOS02 cancel failed
512001 8703031E96 DPOS03_CC_FS DPOS03 cancel failed
…. … …
512001 8703481E96 DPOS72_CC_FS DPOS72 cancel failed

(v) Setting name


Note: The “xx” within “DPOSxx” represents the DPOS function number. (e.g., if
DPOS03 is considered, the “xx” is equal to “03”. The numbers used for “xx” can be
represented by “01” to “72”.)

Table 4.8-13 Setting for ‘Cancel’ in DPOSxx


Setting Name Description Default Setting item or value

DPOSxx-LGCNFFCT Logic selector for cancel condition in DPOSxx Fixedlogic Fixedlogic / PLC

GRL200 (Soft 033 & 037)


- 859 -
6F2S1914 (0.37)

4.8.3 Operate logic for SBO/DIR modes


Once the operation of the select logic is complete, the operate logic start to control the device.

(i) Receiving “Operate command On” from the remote-end


Figure 4.8-19 depicts the reception of the operate command ‘On’ from the remote-end.
Wait for a command

Select stage Wait for a next command

Operate command On from the remote-end


Success
Select command On from the remote-end Operation
Signal reception in Operate logic Signal output
decision
IEC61850

Failed Do nothing

Select command Off from the remote-end Operate command Off from the remote-end

Select command On from the local-end Operate command On from the local-end

Select command Off from the local-end Operate command Off from the local-end

Select command On by the PLC function Operate command On by the PLC function

Select command Off by the PLC function Operate command Off by the PLC function

Figure 4.8-19 Outline of Operate command ‘On’

Mapping required for Input point


Figure 4.8-20 illustrates the operate logic when an “Operate command On (Remote-ON-
Control)” signal is applied to the DPOS01 function. The input-point “DEV01_CONTROL_REQ”
is used for the reception of the “Operate command On (Remote-On-Control)”.

Output signal to BO
The DPOS01 function, in Figure 4.8-20, can issue an “Operate” signal at the output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the received signal “Remote-
On-Control” is true.

GRL200 (Soft 033 & 037)


- 860 -
6F2S1914 (0.37)

Input Operate logic in DPOS01 Output

“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS01 function (Function ID: 512001)

“DPOS01_OEC_OK_CS”
Command “Remote-On-Control” (512001 8103011E82)
[DPOS01-CPW]
512001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operation Cmd.
without ILK† condition

ILK† condition (“ON”) passed S


&
DPOS01-Close R
User configurable condition
(PLC#1 connection point)

512001 810301EE57 DPOS01IN_TMP_35


[DPOS01-LGCTRCON] &
Fixedlogic To BO connection
“DPOS01_OEX_BO” §§
Operate condition‡ (512001 8203011DD3)

[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”

“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

512001 820301EE5E DPOS01IN_TMP_42 & “DPOS01_EX_FFL” ‡‡


[DPOS01-RST]
(512001 8603011E91)
0 t
“DPOS01_OEC_OK_CSF” &
1.0s- 100.0s Operate Failed

Figure 4.8-20 Operate On from the remote-end in DPOS01††


†Note:The ILK function can provide the operation criteria for “On”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative “operate-condition” can be connected to the above logic using
connection point “#1” user configurable condition. That is set the scheme switch
[DPOS01-LGCTRCON] to PLC and use “DPOS01IN_TMP_35”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for scheme
switch [DPOS01-LGCFEXOT]. The “Operate-completed” signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.8-20. The user-programmed logic is connected internally to the signal “Operate
completed”, hence this signal is now generated by the user-programmed logic at
the connection point #2 “User configurable condition”. That is, set the scheme
switch [DPOS01-LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”.
*Note:The user can select the type of the output signal. When Fix is set for scheme
switch [DPOS01-PLSM], the output period of the signal is defined by the setting
[DPOS01-CPW]. When Var is set, the signal ceases when the 43-switch is changed.

GRL200 (Soft 033 & 037)


- 861 -
6F2S1914 (0.37)

††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.8-14 for PLC#1, Table 4.8-15 for PLC#2, Table 4.8-18 and Table 4.8-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by the [DPOS01-RST] has been reached.

(ii) Receiving “Operate command Off” from the remote-end


Figure 4.8-21 depicts the reception of the operate command ‘Off ’ from the remote-end.
Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Operate command On from the remote-end

Operate command Off from the remote-end


Success
Operation
Signal reception in Operate logic Signal output
Select command Off from the remote-end decision
IEC61850

Failed Do nothing

Select command On from the local-end Operate command On l from the local-end

Select command Off from the local-end Operate command Off from the local-end

Select command On by the PLC function Operate command On by the PLC function

Select command Off by the PLC function Operate command Off by the PLC function

Figure 4.8-21 Outline of Operate command ‘Off’

Mapping required for Input point


Figure 4.8-22 illustrates the operate logic when an “Operate command Off (Remote-Off-
Control)” signal is applied to the DPOS01 logic. The input-point “DEV01_CONTROL_REQ” is
used for the reception of the “Operate command Off (Remote-Off-Control)”.

Output signal to BO
The DPOS01 function, in Figure 4.8-22, can issue an “Operate” signal at the output-point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the input signal “Remote-
Off-Control” is true.

GRL200 (Soft 033 & 037)


- 862 -
6F2S1914 (0.37)

Input Operate logic in DPOS01 Output

“DPOS01_FEC_OK_CSF”
(512001 8003011E7E)
DPOS01 function (Function ID: 512001)

“DPOS01_FEC_OK_CS”
Command “Remote-Off-Control” (512001 8003011E81)
[DPOS01-CPW]
512001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operation Cmd.
without ILK† condition

ILK† condition (“OFF”) passed S


&
DPOS01-Open R
User configurable condition
(PLC#3 connection point)

512001 800301EE56 DPOS01IN_TMP_34


[DPOS01-LGCTRCON] &
Fixedlogic To BO connection
“DPOS01_FEX_BO” §§
Operate condition‡ (512001 8103011DD0)

[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”

“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

512001 820301EE5E DPOS01IN_TMP_42 & “DPOS01_EX_FFL”


[DPOS01-RST]
(512001 8603011E91)
0 t

“DPOS01_FEC_OK_CSF &
1.0s- 100.0s Operate Failed

Figure 4.8-22 Operate Off from the remote-end in DPOS01††


†Note:The ILK function can provide the operation criteria for “Off”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative “operate-condition” can be connected to the above logic using
connection point #3 “User-configurable condition”. That is set the [DPOS01-
LGCTRCON] to PLC and use “DPOS01IN_TMP_34”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for scheme
switch [DPOS01-LGCFEXOT]. The “Operate completed” signal can also be issued
from logic programmed by the user in place of the logic shown in Figure 4.8-20.
The user programmed logic is connected internally to the signal “Operate
completed”, hence this signal is now generated the user-programmed logic at
connection point #2 “User-configurable condition”. That is, set the scheme switch
[DPOS01-LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”.
*Note:The user can select a type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting
[DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.

GRL200 (Soft 033 & 037)


- 863 -
6F2S1914 (0.37)

††Note: To identify the input and output signals of the other DPOS logics, see Table
4.8-15 for PLC#2, Table 4.8-16 for PLC#3, Table 4.8-18 and Table 4.8-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].

(iii) Receiving “Operate command On” from the local-end


Figure 4.8-23 depicts the reception of the operate command ‘On’ from the local-end.

Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Operate command On from the local-end

Select command Off from the remote-end Operate command Off from the local-end

Operate command On from the local-end


Select command On from the local-end Success
Operation
Signal reception from Operate logic Signal output
decision
the front panel

Failed Do nothing

Select command Off from the local-end Operate command Off from the local-end

Select command On by the PLC function Operate command On by the PLC function

Select command Off by the PLC function Operate command Off by the PLC function

Figure 4.8-23 Outline of Operate command ‘On’

Input signal generated at the local-end


Figure 4.8-24 illustrates the operate logic when an “Operate command signal On (Local-ON-
Control)” is applied to the DPOS01 function. The signal is generated when “Execution of On”
is keyed on the IED front panel.

Output signal to BO
The DPOS01 function, in Figure 4.8-24, can issue an “Operate” signal at the output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the signal “Local-On-Control”
is true.

GRL200 (Soft 033 & 037)


- 864 -
6F2S1914 (0.37)

To BO connection

Input Operate logic in DPOS01 Output

“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS1 function (Function ID: 512001)

“DPOS01_OEC_OK_CS”
(512001 8103011E82)
Operate Cmd.
Command “Local-On-Control” [DPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operate Cmd.
without ILK† condition
ILK† condition (“ON”) passed
DPOS01-Close
S
&
ILK† bypassing 1≥
R
ICB_STATE

User configurable condition (PLC#1 connection point)


512001 810301EE57 DPOS01IN_TMP_35 &
[DPOS01-LGCTRCON]
Fixedlogic To BO connection
“DPOS01_OEX_BO” §§
Operate condition‡
(512001 8203011DD3)

[DPOS01-LGCFEXOT]
& Assign to BOs
ASEQ function§” is in progress Fixedlogic
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”

“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

512001 820301EE5E DPOS01IN_TMP_42 & “DPOS01_EX_FFL” ††


[DPOS01-RST]
(512001 8603011E91)
0 t
“DPOS01_OEC_OK_CSF” &
1.0s- 100.0s Operate Failed

Figure 4.8-24 Operate On on the front panel in DPOS01††


†Note:The ILK function can provide the operation criteria for “On”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative “operate-condition” can be connected to the above using
connection point #1” user configurable condition”. That is set the [DPOS01-
LGCTRCON] to PLC and use “DPOS01IN_TMP_35”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for scheme
switch [DPOS01-LGCFEXOT]. The “Operate comleted” signal can also be issued
from logic programmed by the user in place of the logic shown in Figure 4.8-20.
The user-programmed logic is connected internally to the signal “Operate
completed”, hence this is now generated by the user-programmed logic at
connection point #2 “User configurable condition”. That is, set the scheme switch
[DPOS01-LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”.
*Note:The user can set the type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting
[DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.

GRL200 (Soft 033 & 037)


- 865 -
6F2S1914 (0.37)

††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.8-14 for PLC#1, Table 4.8-15 for PLC#2, Table 4.8-18 and Table 4.8-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].

(iv) Receiving “Operate command Off” from the local-end


Figure 4.8-25 outlines the reception of the operate command ‘Off ’ from the local-end.
Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Operate command On from remote-end

Select command Off from the remote-end Operate command Off from remote-end

Select command On from the local-end Operate command On from the local-end

Operate command Off from the local-end


Select command Off from the local-end Success
Operate
Signal reception from Operate logic Signal output
decision
the front panel

Failed Do nothing

Select command On by the PLC function Operate command On by the PLC function

Select command Off by the PLC function Operate command Off by the PLC function

Figure 4.8-25 Outline of Operate command ‘Off’

Input signal generated at the local-end


Figure 4.8-26 illustrates the operate logic when an “Operate command Off (Local-OFF-Control)”
signal is applied to the DPOS01 logic. The input signal is provided when “Execution for Off” is
keyed on the IED front panel.

Output signal to BO
The DPOS01 function, in Figure 4.8-26, can issue an “Operate” signal at the output point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the input signal “Local-Off-
Control” is true.

GRL200 (Soft 033 & 037)


- 866 -
6F2S1914 (0.37)

Input Operate logic in DPOS01 Output

“DPOS01_FEC_OK_CSF”
DPOS1 function (Function ID: 512001) (512001 8003011E7E)

“DPOS01_FEC_OK_CS”
Operate Cmd. (512001 8003011E81)
Command “Local-Off-Control” [DPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operate Cmd.
without ILK† condition
ILK† condition (“Off”) passed
DPOS01-Open
S
&
ILK† bypassing 1≥
R
ICB_STATE

User configurable condition (PLC#3 connection point)


512001 800301EE56 DPOS01IN_TMP_34 &
[DPOS01-LGCTRCON]
Fixedlogic To BO connection
“DPOS01_FEX_BO” §§
Operate condition‡
(512001 8103011DD0)

[DPOS01-LGCFEXOT]
& Assign to BOs
ASEQ function§” is in progress Fixedlogic
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”

“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

512001 820301EE5E DPOS01IN_TMP_42 & “DPOS01_EX_FFL” ††


[DPOS01-RST]
(512001 8603011E91)
0 t
“DPOS01_FEC_OK_CSF” &
1.0s- 100.0s Operate Failed

Figure 4.8-26 Operate Off on the front panel in DPOS01††


†Note:The ILK function can provide the operation criteria for “Off”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative “operate-condition” can be connected to the above logic using
connection point #3 “User configurable condition”. That is, set the [DPOS01-
LGCTRCON] to PLC and use “DPOS01IN_TMP_34”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for the scheme
switch [DPOS01-LGCFEXOT]. The “Operate completed” signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.8-20. The user-programmed logic is connected internally to the signal “Operate
completed”, hence this signal is now generated by the user-programmed logic at
connection point #2 “User configurable condition”. That is, set the scheme switch
[DPOS01-LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”.
*Note:The user can select a type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting
[DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.

GRL200 (Soft 033 & 037)


- 867 -
6F2S1914 (0.37)

††Note: To identify the input and output signals of the other DPOS logics, see Table
4.8-15 for PLC#2, Table 4.8-16 for PLC#3, Table 4.8-18 and Table 4.8-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].

(v) Receiving “Operate command On” using the PLC function


Figure 4.8-27 outlines the reception of the operate command ‘On’ with the PLC function.
Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Operate command On from the remote-end

Select command Off from the remote-end Operate command Off from the remote-end

Select command On from the local-end Operate command On from the local-end

Select command Off from the local-end Operate command Off from the local-end

Operate command On by the PLC


Success
Select command On by the PLC function Operate
Signal generation by the Operate logic Signal output
decision
PLC function

Failed Do nothing

Select command Off by the PLC function Operate command Off by the PLC

Figure 4.8-27 Outline of Operate command ‘On’

Input signal from the PLC function


Figure 4.8-28 describes the operate logic when an “Operate command On (PLC-On-control)”
signal is generated by the PLC function. There are two input points for reception of the signal
“Operate command On (PLC-On-control)”: the former connection point (PLC#3) is used for the
reception of the operate-command when the interlock check is required, the later connection
point (PLC#4) is used for the reception of the operate-command when the interlock check is
not required. That is, for the DPOS01 function when the “Operate command On (PLC-On-
Control)” signal generated in the user-programmed logic and when the interlock check is
required in the operate logic, user should apply the signal at connection point (PLC#3: i.e.
DEV01_CL_INTERLOCK). Alternatively, if the interlock check is not required, apply the
signal at connection point (PLC#4: i.e. DEV01_CL_COMMAND). The PLC#3 and PLC#4 are
denoted as PLC#1 and PLC#2 in Table 4.8-2. Note that the user should set PLC for scheme
switch [DPOS01-LGCTRCON].

Output signal to BO
The DPOS01 function, in Figure 4.8-28, can issue an “Operate” signal at output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the signal “PLC-On-Control”

GRL200 (Soft 033 & 037)


- 868 -
6F2S1914 (0.37)

is true.

Input Operate logic in DPOS01 Output

“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS01 function (Function ID: 512001)

“DPOS01_OEC_OK_CS”
Command “PLC-On-Control” requiring ILK† check
(512001 8103011E82)
(PLC#3 connection point) [DPOS01-CPW]
512001 800301EE33 DEV01_CL_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-On-Control” not requiring ILK† check 0.1 – 50.0 s
(PLC#4 connection point)
512001 800301EE32 DEV01_CL_COMMAND Operate Cmd.
without ILK† condition

ILK† condition (“ON”) passed S


&
DPOS01-Close R
User configurable condition
(PLC#1 connection point)

512001 810301EE57 DPOS01IN_TMP_35


[DPOS01-LGCTRCON] &
Fixedlogic To BO connection
“DPOS01_OEX_BO” §§
Operate condition‡
(512001 8203011DD3)

[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”

“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

512001 820301EE5E DPOS01IN_TMP_42 & “DPOS01_EX_FFL” ††


[DPOS01-RST]
(512001 8603011E91)
0 t
“DPOS01_OEC_OK_CSF” &
1.0s- 100.0s Operate Failed

Figure 4.8-28 Operate On by the PLC function in DPOS01††


†Note:The ILK function can provide the operation criteria for “On”.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operate-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 4.8-28 using
connection point #1 “User configurable condition”. That is set the scheme switch
[DPOS01-LGCTRCON] to PLC and use “DPOS01IN_TMP_35”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for scheme
switch [DPOS01-LGCFEXOT]. If the signal is to be issued from the logic
programmed by the user instead of the logic shown in Figure 4.8-20, connect the
“Operate completed” signal generated in the user-programmed logic to connection
point #2 “User configurable condition”. That is, set the scheme switch [DPOS01-
LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”.
*Note:The user can select a type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting applied

GRL200 (Soft 033 & 037)


- 869 -
6F2S1914 (0.37)

to [DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
††Note: To identify the input and output signal-points in the other DPOS logics, see Table
4.8-14 for PLC#1, Table 4.8-15 for PLC#2, Table 4.8-18 and Table 4.8-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when a state-change remains undetected
following expiration of the setting to timer [DPOS01-RST].

(vi) Receiving “Operate command Off” using PLC function


Figure 4.8-29 outlines the reception of the operate command ‘Off ’ by the PLC function.
Wait for a command

Select stage Wait for a next command

Select command On from the remote-end Operate command On from the remote-end

Select command Off from the remote-end Operate command Off from the remote-end

Select command On from the local-end Operate command On from the local-end

Select command Off from the local-end Operate command Off from the local-end

Select command On by the PLC Operate command On by the PLC

Operate command Off by the PLC


Success
Select command Off by the PLC Operation
PLC logic programmed Operate logic Signal output
decision
by the user l

Failed Do nothing

Figure 4.8-29 Outline of Operate command ‘Off’

Input signal from the PLC function


Figure 4.8-30 depicts the operate logic when an “Operate command Off (PLC-Off-control)”
signal is generated by the PLC function. There are two input points for reception of this
command signal, like the signal “Operate command On (PLC-On-control)”, That is, if an
interlock check is required, apply the signal at connection point (PLC#3: i.e.
DEV01_OP_INTERLOCK). If, on the other hand an interlock check is not required, apply the
signal at the other connection point (PLC#4: i.e. DEV01_OP_COMMAND). PLC#3 and PLC#4
are denoted as PLC#1 and PLC#2 in Table 4.8-3.

Output signal to BO
The DPOS01 function, in Figure 4.8-30, can issue an “Operate” signal at output-point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the signal “PLC-Off-Control”
is true.

GRL200 (Soft 033 & 037)


- 870 -
6F2S1914 (0.37)

Input Operate logic in DPOS01 Output

DPOS01 function (Function ID: 512001)

“DPOS01_FEC_OK_CSF” “DPOS01_FEC_OK_CS”
Command “PLC-On-Control” with ILK†
(512001 8003011E7E) (512001 8003011E81)
(PLC#3 connection point) [DPOS01-CPW]
512001 800301EE31 DEV01_OP_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-On-Control” without ILK† 0.1 – 50.0 s
(PLC#4 connection point)
512001 800301EE30 DEV01_OP_COMMAND Operation Cmd.
without ILK† condition

ILK† condition (“Open”) passed S


&
DPOS01-Open R
User configurable condition
(PLC#1 connection point)

512001 800301EE56 DPOS01IN_TMP_34


[DPOS01-LGCTRCON] &
Fixedlogic To BO connection
PLC#1
“DPOS01_FEX_BO”
Operate condition‡
(512001 8103011DD0)

[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”

“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

512001 820301EE5E DPOS01IN_TMP_42 & “DPOS01_EX_FFL”


PLC#2 [DPOS01-RST]
(512001 8603011E91)
“DPOS01_FEC_OK_CSF” 0 t
(512001 8003011E7E)
&
1.0s- 100.0s Operate Failed

Figure 4.8-30 Operate ‘Off’ by the PLC function in DPOS01††


†Note:The ILK function can provide the criteria for operation for control of the “Off”
operation.
‡Note:An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operate-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 4.8-30 using
connection point #1 “User configurable condition”. That is set the scheme switch
[DPOS01-LGCTRCON] to PLC and use “DPOS01IN_TMP_34”.
§Note:The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for the scheme
switch [DPOS01-LGCFEXOT]. If the signal is to be issued from the programmed
logic by the user in place of the logic in Figure 4.8-20, connect the signal “Operate
completed” generated in the programmed logic to the connection point #2 “User
configurable condition”. That is, set the scheme switch [DPOS01-LGCFEXOT] to
PLC and use “DPOS01IN_TMP_42”.
*Note:The user can select a type of the output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting applied
to [DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is

GRL200 (Soft 033 & 037)


- 871 -
6F2S1914 (0.37)

changed.
††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.8-15 for PLC#2, Table 4.8-16 for PLC#3, Table 4.8-18 and Table 4.8-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].

(vii) Operate condition


In a manner similar to which the conditions have been examined for the select command, the
conditions for an operate command should be understood. Figure 4.8-31 illustrates the logic to
examine an operate condition; the operate condition is determined by signal
“DPOS01_3PH_STATE”. If the functionality of the original logic does not meet with user-
requirements, the following alternatives are available:
3. The user can replace the original logic with alternative logic.
4. The user can add another signal to the original logic.

Replacing the original logic


If the user wishes to replace the operate condition logic completely, it can be achieved using
connection point “User configurable condition”:
1. Connect the user-customized logic using “DPOS01IN_TMP_39”, listed as PLC#2 in
Table 4.8-17.
2. Set scheme switch [DPOS01-LGEXFFCT] to PLC.

Adding another operate condition signal


If the addition of another signal is required, the user can add the signal to the operate condition
logic using connection point “Additional condition”
1. Add a user-preferred signal using DPOS01IN_TMP_38, listed as PLC#1 in Table
4.8-17.
2. Set scheme switch [DPOS01-LGEXFFCT] to Fixedlogic.

GRL200 (Soft 033 & 037)


- 872 -
6F2S1914 (0.37)

From SOTFSW*1 DPOS01 function (Function ID: 512001)


Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Operate condition
Traveling OR Unmatched condition detected *5
Function “Automatic sequence control” is in progress
ASEQ_MULTI_SEL Event suppression detected *6
From TRC*4 = DPOS01_F_QLT_SPP
General trip (512001 8103011F5F)
GEN.TRIP
BI board connection error detected*7
= DPOS01_F_BI_ERR
(512001 8203011F60)

Command “ON-control” received &


Command “OFF control” received &
received
DPOS01_3PH_STATE
(512001 3103011001)
[SCDEN]*8 Same Directional
Controlling Event
OFF
Additional condition (PLC#1 connection point)
512001 800301EE65 DPOS01IN_TMP_38
[DPOS01- LGEXFFCT]
User configurable operate condition (PLC#2 connection point)
Fixedlogic
512001 810301EE66 DPOS01IN_TMP_39 &

From Control hierarchy *9

512001 820301ED50 DPOS01IN_TMP_28


&
From CMNCTRL
Serious error detection
SERI_ERR
[DPOS01-CTREN]
On

Figure 4.8-31 Operate condition logic for On/Off in DPOS01

1Note: “Command Blocking” disables all operation except for its own; “Command
Blocking” is implemented as “CBK” in a software switch controller (SOTFSW).
The IEC61850 standard defines “Command Blocking” as “CmdBlk”. For more
information on “CBK”, see Chapter Control and monitoring application: Software
switch controller. See the signal ““CBK_STATE” in Table 4.8-6.
2Note: “Double Command Blocking” (DCB) is an operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as “DCB
RCV OR” in Table 4.8-6. For more information see Chapter Control and
monitoring application:Common controls.
3Note: Detection of event “device-travelling” signifies that other operators are changing
the status of one or more devices. Thus, device operation by the IED should be
inhibited whilst ever the event is being detected. The detection signal is denoted
as “Travelling OR” in Table 4.8-6.
4Note: If an IED in the process of issuing a trip command, all control operation is blocked
until the trip operation has been completed. If the IED has a relay application, the
trip command is issued at the output point “GEN.TRIP” in Table 4.8-6.
5Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a

GRL200 (Soft 033 & 037)


- 873 -
6F2S1914 (0.37)

command is not identical to “IED test status”.


6Note: The “Event suppression” function can detect chattering in BI circuits. (See section
4.8.6(i)-3)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The Common control (CMNCTRL) function can test and check the operation-
direction of logic. When the user sets Off for scheme switch [SCDEN], operation of
the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
9Note: The user must program the PLC logic “Control hierarchy condition”. The user
must connect the “Control hierarchy condition” to the select condition logic using
the connection point “DPOS01IN_TMP_28”. For more information, see Chapter
Control and monitoring application: Control hierarchy . See PLC#3 of Table
4.8-7.Note that the logic outputs are generated separately for both On and Off.

(viii) Signal name and number


Note: The user should note the meaning of the following descriptions as shown in
column “M/O” of each table:
“O” indicates that the signal is provided for optional use.
“M” indicated that the user should map/set/configure the signal; otherwise, the
user experience an operational failure if the default settings are used.
“N/A” indicates that that the user cannot change the state of the signal.

Table 4.8-14 PLC connection points (Input point for PLC#1 User configurable condition)
Signal Number Signal Name Description M/O
512001 810301EE57 DPOS01IN_TMP_35 DPOS01 user configurable condition(PLC#1) O
512001 810302EE57 DPOS01IN_TMP_35 DPOS02 user configurable condition(PLC#1) O
512001 810303EE57 DPOS01IN_TMP_35 DPOS03 user configurable condition(PLC#1) O
…. …. …..
512001 810348EE57 DPOS72IN_TMP_35 DPOS72 user configurable condition(PLC#1) O

Table 4.8-15 PLC connection points (Input point for PLC#2 User configurable condition)
Signal Number Signal Name Description M/O
512001 820301EE5E DPOS01IN_TMP_42 DPOS01 user configurable condition(PLC#2) O
512001 820302EE5E DPOS02IN_TMP_42 DPOS02 user configurable condition(PLC#2) O
512001 820303EE5E DPOS03IN_TMP_42 DPOS03 user configurable condition(PLC#2) O
… … …
512001 820348EE5E DPOS72IN_TMP_42 DPOS72 user configurable condition(PLC#2) O

Table 4.8-16 PLC connection points (Input point for PLC#3 User configurable condition)
Signal Number Signal Name Description M/O
512001 800301EE53 DPOS01IN_TMP_34 DPOS01 user configurable condition(PLC#3) O

GRL200 (Soft 033 & 037)


- 874 -
6F2S1914 (0.37)

Signal Number Signal Name Description M/O


512001 800302EE53 DPOS02IN_TMP_34 DPOS02 user configurable condition(PLC#3) O
512001 800303EE53 DPOS03IN_TMP_34 DPOS03 user configurable condition(PLC#3) O
… … …
512001 800348EE53 DPOS72IN_TMP_34 DPOS72 user configurable condition(PLC#3) O

Table 4.8-17 PLC connection points (Input point for PLC#1 and PLC#2 for additional and
operate condition)
Signal Number Signal Name Description M/O
512001 800301EE65 DPOS01IN_TMP_38 DPOS01 user additional condition(PLC#1) O
512001 800302EE65 DPOS02IN_TMP_38 DPOS02 user additional condition(PLC#1) O
512001 800303EE65 DPOS03IN_TMP_38 DPOS03 user additional condition(PLC#1) O
… … …
512001 800348EE65 DPOS72IN_TMP_38 DPOS72 user additional condition(PLC#1) O
512001 810302EE66 DPOS01IN_TMP_39 DPOS01 user configurable operate condition(PLC#2) O
512001 810303EE66 DPOS01IN_TMP_39 DPOS02 user configurable operate condition(PLC#2) O
512001 810304EE66 DPOS01IN_TMP_39 DPOS03 user configurable operate condition(PLC#2) O
…. …. ….
512001 810348EE66 DPOS72IN_TMP_39 DPOS72 user configurable operate condition(PLC#2) O

Table 4.8-18 PLC monitoring points (Output signal for BIO)


Signal Number Signal Name Description
512001 8203011DD3 DPOS01_OEX_BO DPOS01 operate (ON) command for Binary Output.
512001 8203021DD3 DPOS02_OEX_BO DPOS02 operate (ON) command for Binary Output.
512001 8203031DD3 DPOS03_OEX_BO DPOS03 operate (ON) command for Binary Output.
… …. …
512001 8203481DD3 DPOS72_OEX_BO DPOS72 operate (ON) command for Binary Output.
512001 8103011DD0 DPOS01_FEX_BO DPOS01 operate (OFF) command for Binary Output.
512001 8103021DD0 DPOS02_FEX_BO DPOS02 operate (OFF) command for Binary Output.
512001 8103031DD0 DPOS03_FEX_BO DPOS03 operate (OFF) command for Binary Output.
…. …. ….
512001 8103481DD0 DPOS72_FEX_BO DPOS72 operate (OFF) command for Binary Output.

Table 4.8-19 PLC monitoring points (Signals within operate logic)


Signal Number Signal Name Description
512001 8003011E7F DPOS01_OEC_OK_CSF DPOS01 On-direction execute command
512001 8003021E7F DPOS02_OEC_OK_CSF DPOS02 On-direction execute command
512001 8003031E7F DPOS03_OEC_OK_CSF DPOS03 On-direction execute command
…. …. ….
512001 8003481E7F DPOS72_OEC_OK_CSF DPOS72 On-direction execute command
512001 8003011E7E DPOS01_FEC_OK_CSF DPOS01 Off-direction execute command
512001 8003021E7E DPOS02_FEC_OK_CSF DPOS02 Off-direction execute command
512001 8003031E7E DPOS03_FEC_OK_CSF DPOS03 Off-direction execute command
…. …. ….
512001 8003481E7E DPOS72_FEC_OK_CSF DPOS72 Off-direction execute command
512001 8103011E82 DPOS01_OEC_OK_CS DPOS01 On-direction execute command
512001 8103021E82 DPOS02_OEC_OK_CS DPOS02 On-direction execute command
512001 8103031E82 DPOS03_OEC_OK_CS DPOS03 On-direction execute command
… …. ….
512001 8103481E82 DPOS72_OEC_OK_CS DPOS72 On-direction execute command
512001 8003011E81 DPOS01_FEC_OK_CS DPOS01 Off-direction execute command

GRL200 (Soft 033 & 037)


- 875 -
6F2S1914 (0.37)

Signal Number Signal Name Description


512001 8003021E81 DPOS02_FEC_OK_CS DPOS02 Off-direction execute command
512001 8003031E81 DPOS03_FEC_OK_CS DPOS03 Off-direction execute command
… …. ….
512001 8003481E81 DPOS72_FEC_OK_CS DPOS72 Off-direction execute command

Table 4.8-20 PLC monitoring points (Output signals for response)


Signal Number Signal Name Description
512001 8003011E93 DPOS01_EX_CMP DPOS01 completed control
512001 8003021E93 DPOS02_EX_CMP DPOS02 completed control
512001 8003031E93 DPOS03_EX_CMP DPOS03 completed control
… … …
512001 8003481E93 DPOS72_EX_CMP DPOS72 completed control
512001 8603011E91 DPOS01_EX_FFL DPOS01 failed control
512001 8603021E91 DPOS02_EX_FFL DPOS02 failed control
512001 8603031E91 DPOS03_EX_FFL DPOS03 failed control
…. …. ….
512001 8603481E91 DPOS72_EX_FFL DPOS72 failed control

(ix) Setting names


Note: The “xx” of “DPOSxx” represents the DPOS function number. (e.g., if the DPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented by “01”
to “72”.)

Table 4.8-21 Setting of Operate in DPOSxx


Setting Name Description Default Setting item or value
DPOSxx-PLSM Methods of command output(DPOS1-72) Fix Fix/Var/Latch
DPOSxx-CPW Duration of command output(DPOS1-72) 1.0[sec] 0.1~50.0[sec]
DPOSxx-RST Detection time for terminating control (DPOS1-72) 30.0[sec] 0.1~100.0[sec]
DPOSxx-LGCTRCON Logic selector for operate condition (DPOS01-72) Fixedlogic Fixedlogic/PLC
DPOSxx-LGCFEXOT Logic selector for command output (DPOS01-72) Fixedlogic Fixedlogic/PLC
DPOSxx-CTREN Activate control function of DPOS01-72 On Off / On
DPOSxx-LGEXFFCT Logic selector for operate condition (DPOS01-72) Fixedlogic Fixedlogic / PLC

GRL200 (Soft 033 & 037)


- 876 -
6F2S1914 (0.37)

4.8.4 Operation counter


The DPOS01 function has an operation-counter†; the user can utilize the operation-counter to
predict the lifespan of switchgear and other functions. The user can select a count mode using
a setting. Table 4.8-22 and Figure 4.8-32 show the modes, for which a user is required to change
a mode in response to a device signal. For instance for the DPOS01 function, a user can select
the mode using scheme switch [DPOS01-CNTS], which is set to C-On; counting-up is performed
when a switchgear signal gives rise to a change in state from “Off to On”.

Table 4.8-22 Mode of operation counter


Mode Description
Counting-up is performed when a signal changes to closed (On). When the signal
C-On
is changed from “Off to On”, the counter value is incremented.
Counting-up is performed when a signal changes to open (Off). When the signal
C-Off
is changed from “On to Off”, the counter value is incremented.
Counting-up occurs when any state change occurs: that is, “Off to On” or “On to
C-OnOff
Off”.
NA Stop the count function
†Note:The operation-counter value is not cleared when power is removed from the IED.
The operation-counter is available in the DPOS01 to DPOS72 functions.
On state

Off state

Figure 4.8-32 Device signal

The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation counter”, the user can set a user-
preferred value for the operation-counter. See chapter User interface: Monitoring sub-menu.

Operation Counter DPOS1-CNT1


10:48 1/25 10:48 1/4
DPSY1-CNT > DPOS_Dev1-3Ph +
DPSY2-CNT > CANCEL
0
_DPOS1-CNT >
DPOS_Dev1-APh +
DPOS2-CNT >
DPOS3-CNT > 0
ENTER DPOS_Dev1-BPh +
DPOS4-CNT >

Figure 4.8-33 Operation counter sub-menu


Note: With regard to signal “DPOS01_3PH_STATE”, the sub-menu represents it as
“DPOS_Dev1-3Ph”. Analogous to the signal “DPOS01_3PH_STATE”,
“DPOS01_APH_STATE” is represented as “DPOS_Dev1-APh”. Signals
“DPOS01_BPH_STATE” and “DPOS01_CPH_STATE” are displayed in a similar
manner.

GRL200 (Soft 033 & 037)


- 877 -
6F2S1914 (0.37)

(i) Receiving “change value for counter” from the remote-end


Mapping of Input signal required
Figure 4.8-34 depicts the logic when a command “change value for counter” is received at the
DPOS01 logic. With regard to a three-phase counter, the input-point
“DEV01_3PH_CONTROL_REQ” is used. With regard to a phase-A counter, the input-point
“DEV01_APH_CONTROL_REQ” is used. For phase-B and phase-C, the input-points
“DEV01_BPH_CONTROL_REQ” and “DEV01_CPH_CONTROL_REQ” are used.
Input Operate logic in DPOS01 Output

DPOS01 function (Function ID: 512001)

“DPOS01_SLD_CSCN”
(512001 8A03031F86)
Command “change value for counter”
512001_7003016D09 DEV01_3PH_REQ Operate Command
&

Operate condition‡

Figure 4.8-34 Changing counter value for three-phase† with operation from the remote-end in
DPOS01
‡Note:The “operate condition” signal is provided from the operate condition logic of
Figure 4.8-36.
†Note: The user can apply other counter change commands for phase-A, -B, and –C as
shown in Table 4.8-23. The resultant signals for the other DPOS02-72 logics are
shown in Table 4.8-24.

Output signal to BO
The DPOS01 function can issue a “Result” signal at output point “DPOS01_SLD_CSCN”.

(ii) Receiving “change value for counter” from the local-end


Input signal from the front panel
Figure 4.8-35 depicts the logic when a “change value for counter” command is provided in the
DPOS01 function. The command is provided from the sub-menu, as shown in Figure 4.8-33.

Input Operate logic in DPOS01 Output

DPOS01 function (Function ID: 512001)


“DPOS01_SLD_CSCN”
(512001 8A03031F86)

Command “Change value”

Figure 4.8-35 Changing counter value by operation from the front panel in DPOS01

Output signal to BO
The DPOS01 function can issue a “Result” signal at output point “DPOS01_SLD_CSCN”.

GRL200 (Soft 033 & 037)


- 878 -
6F2S1914 (0.37)

(iii) Operate condition for the counter


Figure 4.8-36 illustrates the operate condition logic. The DPOS01 function can determine an
operate-condition using a signal received from “Control-hierarchy”. The control-hierarchy
condition is provided by user-programmed PLC logic; the user must connect the control-
hierarchy with the DPOS01 function using connection point “DPOS01IN_TMP_28” (see Table
4.8-7).
DPOS01 function (Function ID: 512001)
Command blocking*1 To counter logic
CBK_STATE
1≥ Operate condition
&
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR
From CMNCTRL
Serious error detection Unmatched condition detected *4
SERI_ERR = DPOS01_SC_ST_ERR
From Control hierarchy

512001 820301ED50 DPOS01IN_TMP_28

Figure 4.8-36 Operate condition logic for changing the counter in DPOS01
1Note: “Command Blocking” disables all operation except for its own; the “Command
Blocking” function is initiated by the status of “CBK” in a software switch
controller (SOTFSW). The IEC 61850 standard defines the “Command Blocking”
function as “CmdBlk”. For more information on “CBK”, see Chapter Control and
monitoring application: Software switch controller. See the signal ““CBK_STATE”
of Table 4.8-6.
2Note: “Double Command Blocking” (DCB) is an operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as “DCB
RCV OR” in Table 4.8-6. For more information see Chapter Control and
monitoring application:Common controls.
3Note: If the event “device-travelling” is detected in the CMNCTRL function, it indicates
that another operator is changing the status of a device. Thus, the IED should
inhibit the operation of any device for the duration that the event is detected. The
detected signal is denoted by “Travelling OR” in Table 4.8-6.
4Note: If the issuing of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issues at the output point “GEN.TRIP” in Table
4.8-6.

(iv) Signal names and number


Table 4.8-23 Mapping points
Signal Number Signal Name Description
512001 7003016D09 DEV01_3PH_REQ DPOS01 change command received. (Mapping Data) for 3-phase counter value
512001 7003026D09 DEV02_3PH_REQ DPOS02 change command received. (Mapping Data) for 3-phase counter value
512001 7003036D09 DEV03_3PH_REQ DPOS03 change command received. (Mapping Data) for 3-phase counter value

GRL200 (Soft 033 & 037)


- 879 -
6F2S1914 (0.37)

Signal Number Signal Name Description


… … …
512001 7003486D09 DEV72_3PH_REQ DPOS72 change command received. (Mapping Data) for 3-phase counter value
512001 7003016D0A DEV01_APH_REQ DPOS01 change command received. (Mapping Data) for A-phase counter value
512001 7003026D0A DEV02_APH_REQ DPOS02 change command received. (Mapping Data) for A-phase counter value
512001 7003036D0A DEV03_APH_REQ DPOS03 change command received. (Mapping Data) for A-phase counter value
… … …
512001 7003486D0A DEV72_APH_REQ DPOS72 change command received. (Mapping Data) for A-phase counter value
512001 7003016D0B DEV01_BPH_REQ DPOS01 change command received. (Mapping Data) for B-phase counter value
512001 7003026D0B DEV02_BPH_REQ DPOS02 change command received. (Mapping Data) for B-phase counter value
512001 7003036D0B DEV03_BPH_REQ DPOS03 change command received. (Mapping Data) for B-phase counter value
… … ….
512001 7003486D0B DEV72_BPH_REQ DPOS72 change command received. (Mapping Data) for B-phase counter value
512001 7003016D0C DEV01_CPH_REQ DPOS01 change command received. (Mapping Data) for C-phase counter value
512001 7003026D0C DEV02_CPH_REQ DPOS02 change command received. (Mapping Data) for C-phase counter value
512001 7003036D0C DEV03_CPH_REQ DPOS03 change command received. (Mapping Data) for C-phase counter value
… … …
512001 7003486D0C DEV72_CPH_REQ DPOS72 change command received. (Mapping Data) for C-phase counter value

Table 4.8-24 Results of changing counter


Signal Number Signal Name Description
512001 8A03011F86 DPOS01_SLD_CSCN DPOS01 select command for Binary Output.
512001 8A03021F86 DPOS02_SLD_CSCN DPOS02 select command for Binary Output.
512001 8A03051F86 DPOS03_SLD_CSCN DPOS03 select command for Binary Output.
… … …
512001 8A03481F86 DPOS72_SLD_CSCN DPOS20 select command for Binary Output.

(v) Setting name


Table 4.8-25 Setting for operation counter in DPOSxx
Setting Name Description Default Setting item or value
DPOSxx-CNTS Mode selection of the counter in DPOSxx *user-preferred NA / C-On / C-Off / C-OnOff

GRL200 (Soft 033 & 037)


- 880 -
6F2S1914 (0.37)

4.8.5 Measurement of operation intervals


The DPOS01 function can measure operation intervals (OT1 to OT4) †; the intervals OT1 to
OT2 can represent the period of time when a switch changes from “Closed” to “open”. In the
DPOS01 function the operation period is grouped into sub-time periods, as shown in Table
4.8-26. The user should set scheme switch [DPOS01-OPETMEN] to On.

Table 4.8-26 Four intervals measured in DPOS01 function


Intervals Trigger Events for measurement
Start Signal “DPOS01_FEX_BO” sensed
OT1 End Switch status is changed from “On” to
“Intermediate”
Start Device status “Intermediate” sensed
OT2 End Switch status is changed from “Intermediate” to
“Off”
Start Signal “DPOS01_OEX_BO” sensed
OT3 End Switch status is changed from “Off” to
“Intermediate”
Start Device status “Intermediate” sensed
OT4 End Switch status is changed from “Intermediate” to
“On”
†Note:The function “operation time measurement” is available in the DPOS01 to
DPOS72 functions.

Signal “DPOS01_FEX_BO”

Sensing
intermediate state
On Intermediate Off

Device status for Off


OT1 OT2

Figure 4.8-37 Two intervals (OT1 and OT2) for Off-control

Signal POS01_FEX_BO”

Sensing
intermediate state
Off Intermediate On

Device status for On


OT3 OT4

Figure 4.8-38 Two intervals (OT3 and OT4) for On-control

GRL200 (Soft 033 & 037)


- 881 -
6F2S1914 (0.37)

The user can clear the intervals (OT1 to OT4) by key-operation of the “Operation time”
sub-menu Figure 4.8-39 or operation from the remote-end. See chapter User interface:
Monitoring sub-menu.

Operation Time DPOS1-OT1


10:48 1/26 10:48 1/5
DPSY1-OT > DPOS_SYN-Dev1-OT1
DPSY2-OT > CANCEL ******.*** ms
_DPOS1-OT > DPOS_SYN-Dev1-OT2
DPOS2-OT >
******.*** ms
DPOS3-OT > ENTER DPOS_SYN-Dev1-OT3
DPOS4-OT >

Figure 4.8-39 Operation time sub-menu

(i) Signal names and numbers


Table 4.8-27 Mapping points
Signal Number Signal Name Description
512001 7003006D0D DEV01_RESET_REQ DPOS01 operation time reset command received (Mapping Data)
512001 7003016D0D DEV02_RESET_REQ DPOS02 operation time reset command received (Mapping Data)
512001 7003026D0D DEV03_RESET_REQ DPOS03 operation time reset command received (Mapping Data)

512001 7003486D0D DEV48_RESET_REQ DPOS72 operation time reset command received (Mapping Data)

(ii) Setting name


Table 4.8-28 Setting of operation time function in DPOSxx
Setting Name Description Default Setting item or value
DPOSxx-OPETMEN Activation of the operation time measurement in DPOSxx On Off / On

GRL200 (Soft 033 & 037)


- 882 -
6F2S1914 (0.37)

4.8.6 Setup for BIO module


The user should connect the DPOS input/output points with the BI and the BO circuits;
subsequently, the DPOS function is able to issue select and operate commands. In order to set
up the DPOS function the user should execute the following four steps.
i BI connection for status signal
ii BO connection for “Select command On/Off”
iii BO connection for “Operate command”
iv Contact health check

Note that the DPOS01 function commences operation when the scheme switch [DPOS01-EN]
is set to On.

(i) BI connection for status signals


Figure 4.8-40 exemplifies the reception of signals at the DPOS01 function. To acquire the
status signal§ for phase-A, the user should set two input points for settings [DPOS01A-
NOPSG] and [DPOS01A-NCLSG].†

†Note:Normally an input-signal corresponding to phase-A is generated using a normally-


open contact (NO) and a normally-closed contact (NC). If a NO and a NC contact
are exchanged, the input-signal should be determined by inversion; that is, the
user is required to set On for both scheme switches [DPOS01A-NOPSGI] and
[DPOS01A-NCLSGI].
§Note: The state signal acquired can be monitored. For more information, see Chapter
Automatic supervision.

Grouping three-phase signals corresponding to a state


Suppose the status signals are acquired on the six BI circuits at IO#1 slot. The signals
corresponding to phase-A can be acquired via N/C and N/O contacts; thus, the user should set
two input-points (8001001110 and 810101110 at 200B01†) for the settings [DPOS01A-NOPSG]
and [DPOS01A-NCLSG], respectively, as shown in Figure 4.8-40. For input points
corresponding to phase-B and phase-C, the user must also apply input-points via settings. The
user sets And for both the scheme switches [DPOS01-OPC] and [DPOS01-CLC] respectively;
finally the scheme switch [DPOS01-DEVTYPE] should be set to 3-Pole.

GRL200 (Soft 033 & 037)


- 883 -
6F2S1914 (0.37)

Signals from the


BI circuit and DPOS01 Signal acquisition logic in DPOS01
devices Output ‡

DPOS01
To select and operate
condition logics

“DPOS01_3PH_STATE”
(512001 3103011001)
Phase-A signals BI signal selected by
N/O contact setting [DPOS01A-NOPSG]
Event
signal &
& Suppression
&
1≥ detector
BI signal selected by Open
N/C contact setting [DPOS01A-NCLSG]
“DPOS01_ F_QLT_SPP”
signal & (512001 8103011F5F)
&
Phase-B signals
BI signal selected by & Faulty
N/O contact setting [DPOS01B-NOPSG]
signal &

BI signal selected by &


N/C contact setting [DPOS01B-NCLSG]
signal & Intermediate

Phase-C signals
BI signal selected by
N/O contact setting [DPOS01C-NOPSG]
signal & &

Close
BI signal selected by
N/C contact setting [DPOS01C-NCLSG]
signal &

[DPOS01-EN]
On &
[DPOS01-DEVTYPE]
3-Pole
[DPOS01-OPC]
And
&
[DPOS01-CLC]
And

Figure 4.8-40 Acquisition of a state signal


†Note:The user should set the actual input-points. See chapter Technical description:
Binary IO module.
‡Note:In Figure 4.8-40 two signals can be issued: “DPOS01_3PH_STATE” and
“DPOS01_F_QLT_SPP”. One is used in the select condition logic and the operate
condition logic (see Figure 4.8-13 and Figure 4.8-28). Another is used for operation
in the event suppression function. Other signals are also provided:
DPOS01_APH_STATE, DPOS01_BPH_STATE, and DPOS01_CPH_STATE.

Acquisition of a signal corresponding to a phase


Suppose that a state signal is acquired on the two BI circuits at IO#1 slot. An individual phase
signal can be taken using the N/C and the N/O contacts; thus, the user should set two input-
points (8001001110 and 810101110 in 200B01†) for the settings [DPOS01A-NOPSG] and
[DPOS01A-NCLSG]. The user should set the scheme switch [DPOS01-DEVTYPE] to 1-Pole.

GRL200 (Soft 033 & 037)


- 884 -
6F2S1914 (0.37)

Signals from the


BI circuit and DPOS01 Signal acquisition logic in DPOS01
devices Output ‡

DPOS01
To select and operate
condition logics

“DPOS01_3PH_STATE”
(512001 3103011001)
Single phase signals BI signal selected by
N/O contact setting [DPOS01A-NOPSG]
Event
signal &
& Suppression
1≥ detector
BI signal selected by Open
N/C contact setting [DPOS01A-NCLSG]
“DPOS01_ F_QLT_SPP”
signal & (512001 8103011F5F)
&
Faulty

&
Intermediate

&

Close

[DPOS01-EN]
On &
[DPOS01-DEVTYPE]
1-Pole

Figure 4.8-41 Acquisition of single-phase signal at DPOS01


‡Note:In Figure 4.8-41 two signals can be issued “DPOS01_3PH_STATE” and
“DPOS01_F_QLT_SPP”, which are the same as the ones of the Figure 4.8-40.

Event suppression
If the status of a device “chatters” for a short time, the DPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPOS function;
hence, event suppression can be required to reduce additional burden created.

The DPOS function has an event suppression detector. The user should take into account
of the scheme switches [DPOS-NELD], [DPOS-TELD] and [DPOS-TELR]†. Set On for scheme
switch [DPOS01-SPPEN].

[DPOS-NELD]

Signal 2 4 6 8
from device On On On On On On On
1 3 5 7

Suppressed
On On On On
signal

[DPOS-TELD] [DPOS-TELR]
Time................. A B C D E

Figure 4.8-42 Iterative signals and signals suppressed

GRL200 (Soft 033 & 037)


- 885 -
6F2S1914 (0.37)

Figure 4.8-42 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time ‘A’, the setting [DPOS-NELD] is provided so
that the suppression commences at Time ‘B’. The setting [DPOS-TELD] pertains to the
operation of the detection function from Time ‘A’ (e.g., Time ‘A’ to Time ‘C’).

The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [DPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time ‘D’ to Time ‘E’).

To initiate the event suppression the user should set On for scheme switch [DPOS01-
SPPEN].

(ii) BO connection for “Select command On/Off”


Figure 4.8-43 exemplifies the connection for the select command On and Off. Suppose that
connection with the BOs is achieved by the PLC function using connection points
“DPOS01_OSL_BO_FLG” and “DPOS01_FSL_BO_FLG”†; as a result, the “Select command
On” and the “Select command Off” signals are issued at BO1 and BO2 respectively.
Terminal and
Select logic in DPOS01 BO1 circuit at IO#1 (Function ID: 200B01) wire

“DPOS01_OSL_BO_FLG”
(512001 8603011DC6)
Select logic for select command On “BO1” Select
Signal captured by command
in DPOS01 setting [Input signal 1] ≥1 (200B01_8002001112)
On to the
DRIVER BO1 device
[Input signal 2]
To contact health & ≥1
check [Input signal 3]
“BO1-RB”
[Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
Select logic for select command check
Off in DPOS01 [Input signal 7]
[Input signal 8]

PLC connection point on BO1

200B01 310200E11D BO1_SOURCE

Terminal and
BO2 circuit at IO#1 (Function ID: 200B01) wire
“DPOS01_FSL_BO_FLG”
(512001 8A03011DC4) Select
“BO2”
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8102011112) Off to the
device
[Input signal 2] DRIVER BO2
& ≥1
To contact health
[Input signal 3]
check “BO2-RB”
[Input signal 4] [BO2_CPL] On &
(200B01_8102011113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]

PLC connection point on BO2

200B01 310201E11D BO2_SOURCE

Figure 4.8-43 Example of select commands connected with BO1 & BO2 at IO#1
†Note:Table 4.8-9 shows the remaining signals with the exception of

GRL200 (Soft 033 & 037)


- 886 -
6F2S1914 (0.37)

“DPOS01_OSL_BO_FLG” and “DPOS01_FSL_BO_FLG”.

(iii) BO connection for “Operate command On/Off”


Figure 4.8-44 exemplifies the connection for operate command On/Off. Suppose that connection
with the BOs is achieved by the PLC function using connection points “DPOS01_OEX_BO” and
“DPOS01_FEX_BO”; as a result, the “Operate command On” and the “Operate command Off”
signals are issued at BO3 and BO4 respectively.

Terminal and
Operate logic in DPOS01 BO3 and BO4 circuit at IO#1 (Function ID: 200B01) wire

“DPOS01_OEX_BO”
(512001 8203011DD3)
Operate
“BO3” command
Signal captured by
Operate logic for setting [Input signal 1] ≥1 (200B01_8202021112) On to the
device
“Operate command [Input signal 2] DRIVER BO3
On” & ≥1
[Input signal 3]
“BO3-RB”
[Input signal 4] [BO3_CPL] On &
Connected by Off
(200B01_8202021113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO3


“DPOS01_FEX_BO” 200B01 310202E11D BO3_SOURCE
(512001 8103011DD0)
Operate
“BO4” command
Signal captured by
Operate logic for setting [Input signal 1] ≥1 (200B01_8302031112) Off to the
device
“Operate command [Input signal 2] DRIVER BO4
Off” & ≥1
[Input signal 3]
“BO4-RB”
[Input signal 4] [BO4_CPL] On &
Connected by (200B01_8302031113)
Off
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO4

200B01 310203E11D BO4_SOURCE

Figure 4.8-44 Example of operate commands connected with BO3 and BO4 at IO#1
†Note:Table 4.8-18 shows the remaining signals with the exception of
“DPOS01_OEX_BO” and “DPOS01_FEX_BO”.

(iv) Contact health check


The DPOS01 function has a contact health check feature for the BO circuits; hence, the user
is able to connect an output signal to the contact health check function when Fixedlogic is set
for scheme switch [DPOS01-LGXFEOT]†. Consequently, the DPOS01 function can determine
whether the signal has been successfully output from the BO. If a failure is reported, the
DPOS01 function determines that the signal has not been output successfully to the BO; then,
the command On or Off is canceled immediately and the DPOS01 function returns to the “Wait
for a command” stage.
†Note:Table 4.8-34 shows settings for the health check feature in the other DPOS
functions.

GRL200 (Soft 033 & 037)


- 887 -
6F2S1914 (0.37)

Setting for “Select command On”


For example, the point “DPOS01_OSL_BO_FLG” is connected to the BO1 circuit for the issuing
of the command; the user can connect point “BO1-RB” with the contact health check function
using the setting [DPOS01-OSLBORD]. Do not key the point “DPOS01_OSL_BO_FLG” .
Selecte logic in
DPOS01

Contact health check


“DPOS01_OSL_BO_FLG”
logic in DPOS01
(512001 8603011DC6)

BO1 circuit at & Result of contact health check


IO#1

“BO1-RB”
(200B01_8002001113)
Signal connected by
setting [DPOS01-OSLBORD]

Connection made by the user

Figure 4.8-45 Example connection of “Select command On” for the health check feature

Setting for “Select command Off”


Similar to “select command On”, the point “DPOS01_FSL_BO_FLG” is connected with the BO2
circuit; the user is required to key point “BO2-RB” for the setting [DPOS01-FSLBORD]. Do not
key the point “DPOS01_FSL_BO_FLG”.
Selection logic in
DPOS01

Contact health check


“DPOS01_FSL_BO_FLG”
logic in DPOS01
(55120018 A03011DC4)

BO1 circuit at & Result of contact health check


IO#1

“BO2-RB”
(200B01_8102001113)
Signal connected by
setting [DPOS01-FSLBORD]

Connection made by the user

Figure 4.8-46 Example connection of “Select command Off” for the health check feature

GRL200 (Soft 033 & 037)


- 888 -
6F2S1914 (0.37)

Setting for “Operate command On”


Similarly, the point “BO3-RB” must be applied for the setting [DPOS01-OEXBORD].
Operate logic in
DPOS01

“DPOS01_OEX_BO” Contact health check


“510001_8201011DD3” logic in DPOS01

BO3circuit at & Result of contact health check


IO#1

“BO3-RB”
“200B01_8202021113”
Signal designated by
setting [DPOS01-OEXBORD]

Connection made by the user

Figure 4.8-47 Example connection of “Operate command On” for the health check feature

Setting for “Operate command Off”


Similarly, the point “BO4-RB” must be applied for the setting [DPOS01-FEXBORD].
Operate logic in
DPOS01

Contact health check


“DPOS01_FEX_BO”
logic in DPOS01
“512001 8103011DD0”

BO4 circuit at & Result of contact health check


IO#1

“BO4-RB”
“200B01_8302031113”
Signal designated by
setting [DPOS01-FEXBORD]

Connection made by the user

Figure 4.8-48 Example connection of “Operate command Off” for the health check feature

GRL200 (Soft 033 & 037)


- 889 -
6F2S1914 (0.37)

Setting for the contact health check (normal setting, example #1)
Figure 4.8-49 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1 to BO4 contacts. To check that the contact health check function is working
correctly, the respective points of the BO-RBs should be connected as shown in Table 4.8-29, to
demonstrate that the settings are physically matched with the BO contacts.

Table 4.8-29 Setting example for contact health check


Example #1 Contact health check settings for example #1

“DPOS01_OSL_BO_FLG” is connected to “BO1” at IO#1 200B01 8002001113(BO1-RB) set for [DPOS01-OSLORD] OK

“DPOS01_FSL_BO_FLG” is connected to “BO2” at IO#1 200B01 8102011113 (BO2-RB) set for [DPOS01-FSLBORD] OK

“DPOS01_OEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113(BO3-RB) set for [DPOS01-OEXBORD] OK

“DPOS01_FEX_BO_CSF” is connected to “BO4” atIO#1 200B01 8302031113(BO4-RB) set for [DPOS01-FEXBORD] OK


BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“DPOS01_OSL_BO_FLG”
(512001 8603011DC6) SW1 driven with
Select command On BO1 at IO#1
BO1 SW 1
On
“BO1-RB” command
(200B01_8002001113) SW 3
“DPOS01_FSL_BO_FLG”
SW2 driven with
(512001 8A03011DC4)
BO2 at IO#1
Select command Off BO2 SW 2
Off
“BO2-RB” command
(200B01_8102011113) SW 4
“DPOS01_OEX_BO”
SW3 driven with
(512001 8203011DD3)
BO3 at IO#1
Operate command On BO3
Minus (−)
“BO3-RB”
(200B01_8202021113)
“DPOS01_FEX_BO”
(512001 8103011DD0) SW4 driven with
BO4 BO4 at IO#1
Operate command Off
“BO4-RB”
(200B01_8302031113)

Figure 4.8-49 Contact health check setting and 43SW scheme for example #1

GRL200 (Soft 033 & 037)


- 890 -
6F2S1914 (0.37)

Settings for erroneous contact health check (improper setting, example #2)
Figure 4.8-50 shows a setting example of an improper setting of the 43SW scheme. The settings
are implemented incorrectly as shown in Table 4.8-30, BO1-RB is not chosen, instead BO1 is
actually chosen, which is incorrect. In this case, the setting [DPOS01-OSLBORD] is
meaningless ; hence, the issue of a select command is blocked.

Table 4.8-30 Erroneous setting example for contact health check


Example #2 Contact health check setting for example #2

“DPOS01_OSL_BO_FLG” is connected to “BO1” at IO#1 200B01 8002001112 (BO1) set for [DPOS01-OSLORD] NG

“DPOS01_FSL_BO_FLG” is connected to “BO2” at IO#1 200B01 8102011113 (BO2-RB) set for [DPOS01-FSLBORD] OK

“DPOS01_OEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113(BO3-RB) set for [DPOS01-OEXBORD] OK

“DPOS01_FEX_BO_CSF” is connected to “BO4” at IO#1 200B01 8302031113(BO4-RB) set for [DPOS01-FEXBORD] OK


BIO module
Local/Remote-end “BO1” (not BO1-RB) Drivers 43SW
Plus (+)
mistakenly chosen with
“DPOS01_OSL_BO_FLG”
“200B01_8002001112”
(512001 8603011DC6) SW1 is driven with
BO1 at IO#1
Select command On BO1 SW 1
On
command
SW 3
“DPOS01_FSL_BO_FLG”
SW2 is driven with
(512001 8A03011DC4)
BO2 at IO#1
Select command Off BO2 SW 2
Off
“BO2-RB” command
(200B01_8102011113) SW 4
“DPOS01_OEX_BO”
SW3 is driven with
(512001 8203011DD3)
BO3 at IO#1
BO3
Operate command On Minus (−)
“BO3-RB”
(200B01_8202021113)
“DPOS01_FEX_BO”
(512001 8103011DD0) SW4 is driven with
BO4 BO4 at IO#1
Operate command Off
“BO4-RB”
(200B01_8302031113)

Figure 4.8-50 Contact health check setting and 43SW scheme for example#2

GRL200 (Soft 033 & 037)


- 891 -
6F2S1914 (0.37)

Settings for extra contact health check (special setting, example #3)
Figure 4.8-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “DPOS01_OSL_BO_FLG” is actually chosen for the
setting [DPOS01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special setting
can issue a select command, which is called “operated by internal select function”. The user
does not need to consider the use of a BO circuit for a select command, when there are no BIO
circuits available.

Table 4.8-31 Extra setting example for contact health check


Example #3 Contact health check setting for example #3

“DPOS01_OSL_BO_FLG” is not connected to any “BO” “DPOS01_OSL_BO_FLG” set for [DPOS01-OSLBORD] OK

“DPOS01_FSL_BO_FLG” is not connected to any “BO” “DPOS01_OSL_BO_FLG” set for [DPOS01-FSLBORD] OK

“DPOS01_OEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8102011113(BO2-RB) set for [DPOS01-OEXBORD] OK

“DPOS01_FEX_BO_CSF” is connected to “BO4” at IO#1 200B01 8202021113 (BO3-RB) set for [DPOS01-FEXBORD] OK
BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“DPOS01_OSL_BO_FLG”
(512001 8603011DC6)
Select command On SW1 is not driven with any BO
SW 1
On
command
Physical BOs
are virtualized. SW 3
“DPOS01_FSL_BO_FLG”
(512001 8A03011DC4) SW2 is not driven with any BO
Select command Off SW 2
Off
command
SW 4
“DPOS01_OEX_BO”
SW3 is driven with
(512001 8203011DD3)
BO3 at IO#1
Operate command On BO3
Minus (−)
“BO3-RB”
(200B01_8202021113)
“DPOS01_FEX_BO”
(512001 8103011DD0) SW4 is driven with
BO4 BO4 at IO#1
Operate command Off
“BO4-RB”
(200B01_8302031113)

Figure 4.8-51 Contact health check setting and 43SW scheme for example#3

GRL200 (Soft 033 & 037)


- 892 -
6F2S1914 (0.37)

(v) Signal name and number

Table 4.8-32 PLC monitoring points (Output signal for event suppression function in DPOSxx)
Signal Number Signal Name Description
512001 3103011001 DPOS01_3PH_STATE DPOS01 3ph_state
512001 3103021001 DPOS02_3PH_STATE DPOS02 3ph_state
512001 3103031001 DPOS03_3PH_STATE DPOS03 3ph_state
…. …. ….
512001 3103481001 DPOS72_3PH_STATE DPOS72 3ph_state
512001 8103011F5F DPOS01_F_QLT_SPP Event suppression detected (DPOS01)
512001 8103021F5F DPOS02_F_QLT_SPP Event suppression detected (DPOS02)
512001 8103031F5F DPOS03_F_QLT_SPP Event suppression detected (DPOS03)
…. …. ….
512001 8103481F5F DPOS72_F_QLT_SPP Event suppression detected (DPOS72)

(vi) Setting names


Note: The “xx” of “DPOSxx” represents the DPOS function number. (e.g., if the DPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented as “01”
to “72” for control (monitor).

Table 4.8-33 Setting for Binary input signals in DPOSxx


Setting Name Description Default Setting item or value
DPOSxx-CTREN Activate control function of DPOS01-72 On Off / On
DPOSxx-CTRAHMI Activate local panel control of DPOS01-72 SBO DIR / SBO
DPOSxx-EN Activate monitoring function of DPOS01-72 On Off / On
DPOSxx-DEVTYPE Selection of device type 3-pole 3-pole/1-pile/ switch
DPOSxx-OPC Activate monitoring function of DPOS01-72 On Off / On
DPOSxx-CPC Activate monitoring function of DPOS01-72 On Off / On
DPOSxxA-NOPSG BI position for DPOS01-72 *none BI signal
DPOSxxA-NCLSG BI position for DPOS01-72 *none BI signal
DPOSxxB-NOPSG BI position for DPOS01-72 *none BI signal
DPOSxxB-NCLSG BI position for DPOS01-72 *none BI signal
DPOSxxC-NOPSG BI position for DPOS01-72 *none BI signal
DPOSxxC-NCLSG BI position for DPOS01-72 *none BI signal
DPOSxx-SPPEN Activate event suppression for DPOS01-72 On Off / On
DPOS-NELD Number of change to lock status. 10 0~99
DPOS-TELD Time to locking state( sliding window ) 10[sec] 1~99[sec]
DPOS-TELR Time to unlocking state (sliding window ) 10[sec] 1~99[sec]

Table 4.8-34 Setting for health check feature in DPOSxx


Setting Name Description Default Setting item or value
DPOSxx-OSLBORD Select BO signal (BO*-RB) from signal list *user- BO read-back number
preferred
DPOSxx-FSLBORD Select BO signal (BO*-RB) from signal list *user- BO read-back number
preferred
DPOSxx-OEXBORD Select BO signal (BO*-RB) from signal list *user- BO read-back number
preferred
DPOSxx-FEXBORD Select BO signal (BO*-RB) from signal list *user- BO read-back number
preferred

GRL200 (Soft 033 & 037)


- 893 -
6F2S1914 (0.37)

4.8.7 Mapping for IEC61850 communication


The user can operate the DPOS function over IEC 61850 communications following mapping
using GR-TIEMS. Note that the DPOS function is designed for the class of “Double Point
Controller (DPC)” in the IEC 61850 standard for communication. The user should follow these
steps, each of which is discussed below:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user will need to create a logical node (LN) for the DPOS01 function. Figure 4.8-52
exemplifies the editing of a LN; the LN “Common Switch controller (CSWI)” is chosen for the
DPOS01 function. After the user has defined an object “DPC”, the DPOS01 logical node can be
saved with the name “CSWI” plus “LN Instance”. Create a definition of the object “DPC” in the
DPOS01 logical node. Either the SBO mode or the DIR mode can be chosen in the editing for
the LN.

SBO defined in LN

Figure 4.8-52 Defining “DPC” object in CSWI4 logic node

GRL200 (Soft 033 & 037)


- 894 -
6F2S1914 (0.37)

Defining SBO mode


Figure 4.8-53 exemplifies the DPOS01 logic node saved as “CSWI4”. In the SBO mode, the user
should select the following items for the “CSWI4$Pos” using GR-TIEMS:

 SBOw
 Oper
 Cancel
 Origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.

Figure 4.8-53 LN editing screen for SBO mode (for example)

Defining DIR mode


Figure 4.8-54 exemplifies the DPOS01 logic node saved as save as “CSWI4”. In the DIR mode,
the following three items should be selected using GR-TIEMS.

 Oper
 origin
 ctlmodel (choice ”DOes or DOns” )

Figure 4.8-54 LN editing screen for DIR mode (for example)

GRL200 (Soft 033 & 037)


- 895 -
6F2S1914 (0.37)

(ii) Mapping output data


The user should group the DPOS01 signals with regard to GOOSE and REPORT; the user
should map them for IEC 61850 communication using GR-TIEMS. (Figure 4.8-55 illustrates
how to map a signal); it indicates that the signals for the DPOS01 function are required to map
for IEC 61850 communications.
Table 4.8-35 Mapping signals required for CSWI4 object in DPOS01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/CSWI4$Pos$origin orCat orCategory ST 512001 3103011008 DPOS01_3PH_ORCAT
Ctrl/CSWI4$Pos$origin orIdent Octet64 ST 512001 6A03011009 DPOS01_3PH_ORIDENT
Ctrl/CSWI4$Pos stVal Dbpos ST 512001 3103011001 DPOS01_3PH_STATE
Ctrl/CSWI4$Pos q Quality ST 512001 3103011005 DPOS01_3PH_QUALITY
Ctrl/CSWI4$Pos t Timestamp ST 512001 9003011006 DPOS01_3PH_TIMESTAMP
Ctrl/CSWI4$Pos stSeld BOOLEAN ST 512001 0003011D90 DPOS01_STD_RPT

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.

Drag and drop

Figure 4.8-55 Attribute mapped into DPCSO object of CSWI4

(iii) Mapping input data


The DPOS01 function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “DEV01_CONTROL_REQ” to the IEC61850 communication. Table
4.8-36 shows the input “DEV01_CONTROL_REQ” and the Object reference “Ctrl/CSWI4$Pos”;
the user should map the input-point to the Object reference having attribute CO†. Figure 4.8-56
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control” in
the functional constraint (FC).

GRL200 (Soft 033 & 037)


- 896 -
6F2S1914 (0.37)

Table 4.8-36 Mapping signals required for DPC object for CSWI4
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/CSWI4$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw ctlNum INT8U CO
Ctrl/CSWI4$Pos$SBOw T Timestamp CO
Ctrl/CSWI4$Pos$SBOw Test BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw Check Check CO
Ctrl/CSWI4$Pos$SBOw$origin orCat orCategory CO
Ctrl/CSWI4$Pos$SBOw$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$Oper ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$Oper ctlNum INT8U CO
Ctrl/CSWI4$Pos$Oper T Timestamp CO
Ctrl/CSWI4$Pos$Oper Test BOOLEAN CO
512001 7003016D08 DEV01_CONTROL_REQ
Ctrl/CSWI4$Pos$Oper Check Check CO
Ctrl/CSWI4$Pos$Oper$origin orCat orCategory CO
Ctrl/CSWI4$Pos$Oper$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$Cancel ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$Cancel ctlNum INT8U CO
Ctrl/CSWI4$Pos$Cancel T Timestamp CO
Ctrl/CSWI4$Pos$Cancel Test BOOLEAN CO
Ctrl/CSWI4$Pos$Cancel$origin orCat orCategory CO
Ctrl/CSWI4$Pos$Cancel$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw ctlNum INT8U CO

Drag and drop

Check “Input”

Figure 4.8-56 Input-point mapped for CSWI4

GRL200 (Soft 033 & 037)


- 897 -
6F2S1914 (0.37)

4.8.8 Setting
DPOS01(Function ID: 512001)
Setting items Range Unit Contents Default Note

Common DPOS-NELD 0 - 99 - Number of Event lock detect time 10


DPOS-TELD 1 - 99 s Timer of detect event lock 10
DPOS-TELR 1 - 99 s Timer of recovery from event lock 10
DPOS01-EN Off / On - DPOS01 switch for Device01 Off
Dev01 DPOS01-DEVNAME [Preferred text] - item name of DPOS_Dev1 DPOS_Dev1 !
DPOS01-00NAME [Preferred text] - state name of (0,0)state Travelling0 !
DPOS01-01NAME [Preferred text] - state name of (0,1)state Off !
DPOS01-10NAME [Preferred text] - state name of (1,0)state On !
DPOS01-11NAME [Preferred text] - state name of (1,1)state Travelling1 !
DPOS01-UDFNAME [Preferred text] - state name of undefined Undefine !
DPOS01-FLTNAME [Preferred text] - state name of faulty Faulty !
1-Pole / 3-Pole /
DPOS01-DEVTYPE - Device Type 1-Pole
switch
Normally Open Signal of the single-pole or
DPOS01A-NOPSG [Preferred signal] - Not assigned
phase A
DPOS01A-NOPSGI Off / On - Signal inverse or not Off
Normally Close Signal of the single-pole or
DPOS01A-NCLSG [Preferred signal] - Not assigned
phase A
DPOS01A-NCLSGI Off / On - Signal inverse or not Off
DPOS01B-NOPSG [Preferred signal] - Normally Open Signal of phase B Not assigned
DPOS01B-NOPSGI Off / On - Signal inverse or not Off
DPOS01B-NCLSG [Preferred signal] - Normally Close Signal of phase B Not assigned
DPOS01B-NCLSGI Off / On - Signal inverse or not Off
DPOS01C-NOPSG [Preferred signal] - Normally Open Signal of phase C Not assigned
DPOS01C-NOPSGI Off / On - Signal inverse or not Off
DPOS01C-NCLSG [Preferred signal] - Normally Close Signal of phase C Not assigned
DPOS01C-NCLSGI Off / On - Signal inverse or not Off
DPOS01-OPC And / Or - Normally Open contact grouping And
DPOS01-CLC And / Or - Normally Close contact grouping Or
DPOS01-SPPEN Off / On - Automatic event suppression function Off
Off / On /
DPOS01-UDFEN - undefined pallet check function Off
CHKONLY
DPOS01-UDFTIM 0.1 - 100.0 s palette Undefined check timer 30.0
Off / On /
DPOS01-FLTEN - faulty pallet check function Off
CHKONLY
DPOS01-FLTTIM 0.1 - 100.0 s palette faulty check timer 30.0
DPOS01-CTREN Off / On - control mode (control enable) Off
DPOS01-CTRMENU Off / On - control by MENU enable Off
DPOS01-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
select binary output read data(DataID)1 for no
DPOS01-NSLBORD1 [Preferred signal] - 5120018903011DC0
direction select command
select binary output read data(DataID)1 for no
DPOS01-NSLBORD2 [Preferred signal] - 5120018903011DC0
direction select command
select binary output read data(DataID) for off
DPOS01-FSLBORD [Preferred signal] - 5120018A03011DC4
direction select command
select binary output read data(DataID) for on
DPOS01-OSLBORD [Preferred signal] - 5120018603011DC6
direction select command
execute binary output read data(DataID) for
DPOS01-FEXBORD [Preferred signal] - Not assigned
off direction execute command
execute binary output read data(DataID) for
DPOS01-OEXBORD [Preferred signal] - Not assigned
on direction execute command

GRL200 (Soft 033 & 037)


- 898 -
6F2S1914 (0.37)

DPOS01(Function ID: 512001)


Setting items Range Unit Contents Default Note

FixedLogic /
DPOS01-LGCTRCON - Change logic about control condition FixedLogic
PLC
FixedLogic /
DPOS01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
DPOS01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about off direction execute
DPOS01-LGFEXOT - FixedLogic
PLC output
FixedLogic / Change logic about on direction execute
DPOS01-LGOEXOT - FixedLogic
PLC output
FixedLogic /
DPOS01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
DPOS01-PLSM Fix / Var - pulse mode Fix
DPOS01-CPW 0.1 - 50.0 s control pulse width 1.0
DPOS01-RST 1.0 - 100.0 s response check timer 30.0
NA / C-On / C-
DPOS01-CNTS - count status NA
Off / C-OnOff
DPOS01-OPETMEN Off / On - Operation Time Measurement enable Off
DPOS01-APBD Process / Bay - status change origin Process
DPOS01-CTRDIR Off / On - Capable control direction On
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The DPOS function is available for a 2nd Device and other devices. We have
omitted the other tables because this will be the same as the table for the 1st
device with the exception of the device number.

GRL200 (Soft 033 & 037)


- 899 -
6F2S1914 (0.37)

4.8.9 Signal
 Signal monitoring points in DPOS01
DPOS01(Function ID: 512001)
Element ID Name Description
8003011DE0 DEV1PLCCTRLFAIL DEV1PLCCTRLFAIL
3103011001 DPOS01_3PH_STATE DPOS01 3ph_state
3103011FE5 DPOS01_APH_STATE DPOS01 aph_state
3103011FEA DPOS01_BPH_STATE DPOS01 bph_state
8603011F7B DPOS01_CNT_CS07 DPOS01 count change selected fail condition signal
0003011D91 DPOS01_CNT_SEL DPOS01 count change selected signal(stSeld) for SAS
3203011D20 DPOS01_CNT_VAL DPOS01 count value
3103011FEF DPOS01_CPH_STATE DPOS01 cph_state
8B03011F79 DPOS01_CTR_SGU DPOS01 selected signal
8903011F99 DPOS01_CTR_SGUCN DPOS01 count change selected signal
8203011E8B DPOS01_EC_F_CS DPOS01 execute command fail condition signal
8103011E9A DPOS01_ECF_FCT_EIS DPOS01 execute command fail factor signal except interlock/synchronism check
0003011D97 DPOS01_EX_BO_OPOK DPOS01 execute binary output signal for SAS
8003011E93 DPOS01_EX_CMP DPOS01 execute complete signal
8F03011F5E DPOS01_EX_CMP_TMO DPOS01 timeout after execute completion
8903011F9E DPOS01_EX_CMP_TMOCN DPOS01 count change timeout after execute completion
8603011E91 DPOS01_EX_FFL DPOS01 execute fail signal by fixedlogic
8503011E8F DPOS01_EX_SFL DPOS01 execute success signal by fixedlogic
8003011E81 DPOS01_FEC_OK_CS DPOS01 off direction execute command OK condition signal
8103011DD0 DPOS01_FEX_BO DPOS01 off direction execute binary output signal
8403011F45 DPOS01_FLT_DET1 DPOS01 Faulty Detected (3 phase concentration data only)
8A03011DC4 DPOS01_FSL_BO_FLG DPOS01 off direction select binary output signal
8A03011F81 DPOS01_FSL_CS19 DPOS01 select receive open signal check answer
3103011D01 DPOS01_LCD_ST DPOS01 state for LCD
3103011D00 DPOS01_MMC_ST DPOS01 state for MIMIC
8903011DC0 DPOS01_NSL_BO_FLG DPOS01 select binary output signal
8603011F7E DPOS01_NSL_CS07 DPOS01 select receive signal check answer
8103011E82 DPOS01_OEC_OK_CS DPOS01 on direction execute command OK condition signal
8203011DD3 DPOS01_OEX_BO DPOS01 on direction execute binary output signal
8603011DC6 DPOS01_OSL_BO_FLG DPOS01 on direction select binary output signal
8803011F73 DPOS01_OSL_CS41 DPOS01 on direction select condition signal 41
8603011F8B DPOS01_RST_CS07 DPOS01 reset time selected fail condition signal
0003011F57 DPOS01_RST_SIG DPOS01 reset time signal
8503011F87 DPOS01_SE_RCV_RMTCN DPOS01 count change selected fail condition signal check
8503011F8A DPOS01_SE_RCV_RMTRT DPOS01 reset time selected fail condition signal check
8003011E76 DPOS01_SLD_CS DPOS01 selected condition signal
8003011F67 DPOS01_SLD_CS04 DPOS01 selected condition signal 04
8103011F68 DPOS01_SLD_CS05 DPOS01 selected condition signal 05
8203011F69 DPOS01_SLD_CS06 DPOS01 selected condition signal 06
8A03011F86 DPOS01_SLD_CSCN DPOS01 count change selected condition signal
8A03011F89 DPOS01_SLD_CSRT DPOS01 reset time selected condition signal
0003011D90 DPOS01_SLD_RPT DPOS01 selected signal(stSeld) for SAS
8E03011F5D DPOS01_SLD_TMO DPOS01 time out after selected
8A03011F9D DPOS01_SLD_TMOCN DPOS01 count change time out after selected
8103011E7B DPOS01_SLF_CS DPOS01 no direction select fail condition signal
8703011E98 DPOS01_SLF_FCT_EIS DPOS01 select fail factor signal except interlock/synchronism check
8803011F9B DPOS01_SLF_FCT_F03CN DPOS01 count change select fail factor signal by fixedlogic 03
8703011F9C DPOS01_SLF_FCT_F04CN DPOS01 count change select fail factor signal by fixedlogic 04
8303011F9A DPOS01_SLF_FCT_F07CN DPOS01 count change selected timer for a check
8503011F65 DPOS01_SLF_FCT_FLG05 DPOS01 select fail factor signal by fixedlogic 05
8803011F6C DPOS01_SLF_FCT_FLG07 DPOS01 selected timer for a check

GRL200 (Soft 033 & 037)


- 900 -
6F2S1914 (0.37)

 Signal monitoring points in DPOS01


DPOS01(Function ID: 512001)
Element ID Name Description
8003011E7D DPOS01_SLR_CS DPOS01 select release condition signal
8303011D02 DPOS01_ST_OFF DPOS01 Normal open state
8103011D03 DPOS01_ST_ON DPOS01 Normal close state
0003011D95 DPOS01_TMP_02 DPOS01 time reset selected signal(stSeld) for SAS
3103011D80 DPOS01_TMP_06 DPOS01 control event data (selected)
3103011D81 DPOS01_TMP_07 DPOS01 control event data (select fail)
3103011D82 DPOS01_TMP_08 DPOS01 control event data (select release)
3103011D83 DPOS01_TMP_09 DPOS01 control event data (execute output on)
3103011D84 DPOS01_TMP_10 DPOS01 control event data (execute command ng)
3103011D86 DPOS01_TMP_11 DPOS01 control event data (execute fail)
0003011F53 DPOS01_TRA DPOS01 travelling info
8203011F43 DPOS01_UDF_DET1 DPOS01 Undefined Detected (3 phase concentration data only)
0003011FB6 DPOS01A_CNT_SEL DPOS01 A count change selected signal(stSeld) for SAS
3203011D24 DPOS01A_CNT_VAL DPOS01 A-phase count value
0003011FB7 DPOS01B_CNT_SEL DPOS01 B count change selected signal(stSeld) for SAS
3203011D28 DPOS01B_CNT_VAL DPOS01 B-phase count value
0003011FB8 DPOS01C_CNT_SEL DPOS01 C count change selected signal(stSeld) for SAS
3203011D2C DPOS01C_CNT_VAL DPOS01 C-phase count value

 Common signal monitoring points


DPOS01(Function ID: 512001)
Element ID Name Description
800301EE32 DEV01_CL_COMMAND dev01 close command
800301EE33 DEV01_CL_INTERLOCK dev01 close command with interlock bypass
800301EE30 DEV01_OP_COMMAND dev01 open command
800301EE31 DEV01_OP_INTERLOCK dev01 open command with interlock bypass
820301ED50 DPOS01IN_TMP_28 DPOS01IN_TMP_28
800301EE53 DPOS01IN_TMP_29 DPOS01IN_TMP_29
810301EE54 DPOS01IN_TMP_30 DPOS01IN_TMP_30
800301EE61 DPOS01IN_TMP_31 DPOS01IN_TMP_31
810301EE62 DPOS01IN_TMP_32 DPOS01IN_TMP_32
800301EE55 DPOS01IN_TMP_33 DPOS01IN_TMP_33
800301EE56 DPOS01IN_TMP_34 DPOS01IN_TMP_34
810301EE57 DPOS01IN_TMP_35 DPOS01IN_TMP_35
820301EE5A DPOS01IN_TMP_36 DPOS01IN_TMP_36
830301EE5B DPOS01IN_TMP_37 DPOS01IN_TMP_37
800301EE65 DPOS01IN_TMP_38 DPOS01IN_TMP_38
810301EE66 DPOS01IN_TMP_39 DPOS01IN_TMP_39
800301EDDA DPOS01IN_TMP_40 DPOS01IN_TMP_40
810301EDDB DPOS01IN_TMP_41 DPOS01IN_TMP_41
820301EE5E DPOS01IN_TMP_42 DPOS01IN_TMP_42
830301EE5F DPOS01IN_TMP_43 DPOS01IN_TMP_43
800301EE69 DPOS01IN_TMP_44 DPOS01IN_TMP_44
800301ED5A DPOS01IN_TMP_45 DPOS01IN_TMP_45
800301ED77 DPOS01IN_TMP_46 DPOS01IN_TMP_46

 Mapping points in DPOS01


DPOS(Function ID: 512001)
Element ID Name Description
7003016D08 DEV01_CONTROL_REQ DPOS01 control command received. (Mapping Data)

GRL200 (Soft 033 & 037)


- 901 -
6F2S1914 (0.37)

Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the DPOS function. We have
omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device; hence, the
user can find the same ones for all of the other devices. For example, when the user
wishes to find the “DPOS02A_FLT_DET” point provided for the 2nd device, use the
description of “DPOS01A_FLT_DET”. The user can obtain the ID value of
“DPOS02A_FLT_DET” by using the following steps:
Step 1 Find the element ID for DPOS01A_FLT_DET (i.e., “8303011F49”)
Step 2 Identify the numbers at the fifth and sixth digit from the ID. (i.e.,
“01”)
Step 3 Choose a new device number. (i.e., pick the number “2” for the 2nd
device)
Step 4 Replace the sixth and fifth digit numbers with the new device
number. (i.e., get new ID “8303021F49” of “DPOS02A_FLT_DET”) The
ID is expressed in hexadecimal notation. Thus, the user must change
the device number from decimal notation to hexadecimal notation.

GRL200 (Soft 033 & 037)


- 902 -
6F2S1914 (0.37)

Three position device function (TPOS)


The three-position device function (TPOS) is used when it is required to control a device having
a triple selector (e.g., the selector has three positions: P1, P2, or P3). The user can experience
the following devices as the triple selector: A 43-switch (43S), an earth-switch (ES) with a
disconnector (DS) and others.

a. P1–control b. P2–control c. P3–control

P1 P2 P3

Operation as DS Neutral position Operation as ES

Figure 4.9-1 Example of switch positions in EDS operation

The TPOS function has “Operation counters” and “Operation time measurement”; these
features are used to examine the devices; these features are useful when the user wishes to
assess the operating time of the device; these features are performed by counting the state-
changes for the device. The BO circuits connected with the TPOS function are used for issuing
commands; the BI circuits are used for receiving responses; hence, the user should connect the
BO and BI circuits with the TPOS function†. The TPOS function includes three logic groups:
1. Select logic, 2. Cancel logic, and 3. Operate logic.

EDS devices (43-switches) can be controlled separately; i.e., the function has a number of
separate sets for control (i.e., TPOS01, TPOS02, etc.). For simplicity, only the TPOS01 function
is discussed here; the features in the other TPOS functions are identical to the TPOS01
function.

†Note:A binary IO module has binary input circuits (BIs) and binary output circuits
(BOs); the user makes the connection between the TPOS01 function and the
binary IO module using a signal number (is made of a “Function_ID” and an
“Element_ID”). The signal numbers and names in the TPOS01 function are listed
later.

Tips: If the user wishes to apply the TPOS function quickly, go to sections 4.9.6 and
4.9.5, where settings of the BI and BO circuits and the mapping of signal-points
for IEC61850 communication is described.

GRL200 (Soft 033 & 037)


- 903 -
6F2S1914 (0.37)

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the “G&T position” referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 4.9-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
– Number of functions – 24
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 904 -
6F2S1914 (0.37)

4.9.1 Select logic for SBO/DIR modes


The user should set scheme switch [TPOS01-CTREN] to On prior to TPOS01 operation. Table
4.9-11 shows all of the scheme switches in the TPOS function.

(i) Receiving “select command P1-control” from the remote-end


Figure 4.9-2 outlines the reception of the select command ‘P1-control’ from the remote-end.

Wait for a command

Select stage Wait for a next command

P1 control from the remote-end Cancel logic


Failed
Cancel command
Signal reception Select
Selection logic Signal output
IEC61850 decision Success

Cancel logic
P2 control from the remote-end

P3 control from the remote-end

P1 control from the local-end


Operate logic
P2 control from the local-end
Operate command
P3 control from the local-end

P1 control by the PLC function Operate logic

P2 control by the PLC function

P3 control by the PLC function

Figure 4.9-2 Outline of select command ‘P1-control’

Input point required mapping


Figure 4.9-3 shows the select logic when a “Selection command (Remote-P1-Control)” signal is
applied to the TPOS01 function. This logic has the input-point “DEV01_CONTROL_REQ” for
the reception of a select command; the input-point should be mapped for IEC 61850
communication. The function will fail to operate if mapping is not performed correctly. We will
discuss how to map the input-points for IEC 61850 communication in section 4.9.7.

GRL200 (Soft 033 & 037)


- 905 -
6F2S1914 (0.37)

Input Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)


Command “P1-Control” from the remote
For SBO operation
513001 7004016D08 DEV01_CONTROL_REQ Select command
with ILK† condition & 1≥ &
To “Wait for a next
command”
For DIR operation
To BO connection
Operate command
with ILK† condition & “TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
ILK† condition (“P1”) passed
TPOS1-P1 0 t Select “success”

For SBO operation 0.1s

Select command &


without ILK† condition
To “Wait for a command”
For DIR operation 0 t
Select “Failed”
Operate command
& 0.6s
without ILK† condition

Either “SBO mode” or “DIR mode” In SBO operation


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.9-3 Select P1-control from the remote-end in TPOS01††


†Note:The software interlocking (ILK) function provides the operation criteria for “P1
control”. The ILK function is discussed separately; note that the operation criteria
is defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function being
in the operation. For more information of the ASEQ function, see Chapter Control
and monitoring application: Automatic sequence control function.
*Note:The TPOS01 function can run in either the “SBO mode” or the “DIR mode”. The
user can use signal called “ctlmodel” when communication is implemented using
IEC61850. To use this signal, the user must map for IEC61850 communication.
††Note: To identify the input and output points of the other TPOS logics, see Table 4.9-5,
Table 4.9-7, and Table 4.9-10.

Output signal to BO
The TPOS01 function can issue an signal “Select success” at the output point
“TPOS01_P1SL_BO_FLG”, when the TPOS01 function determines that the input signal
“Remote-P1-Control” received is true. If the TPOS01 function determines that the “Remote-
P1-Control” is not true, the TPOS01 function returns to the “Wait for a command” stage.

GRL200 (Soft 033 & 037)


- 906 -
6F2S1914 (0.37)

(ii) Receiving “select command P2-control” from the remote-end


Figure 4.9-4 outlines the reception of the select command ‘P2-control’ from the remote-end.

Wait for a command

Select stage Wait for a command

P1 control from the remote-end


Cancel logic

P2 control from the remote-end Cancel command


Failed

Signal reception Select


Selection logic Signal output
IEC61850 decision Success Cancel logic

P3 control from the remote-end

P1 control from the local-end


Operate logic
P2 control from the local-end
Operate command
P3 control from the local-end

P1 control by the PLC function Operate logic

P2 control by the PLC function

P3 control by the PLC function

Figure 4.9-4 Outline of select command ‘P2-control’

Input point mapped from the communication


Figure 4.9-5 shows the select logic when a “Select command P2 (Remote-P2-Control)” signal is
received at the input-point “DEV01_CONTROL_REQ”.
Input Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)


Command “P2-Control” from the remote
For SBO operation
513001 7004016D08 DEV01_CONTROL_REQ Select command
with ILK† condition & 1≥ &

For DIR operation


To BO connection
Operate command
with ILK† condition & “TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
ILK† condition (“P2”) passed
TPOS1-P2 0 t Select “success”

For SBO operation 0.1s

Select command &


without ILK† condition
To “Wait for a command”
For DIR operation 0 t
Select “Failed”
Operate command
& 0.6s
without ILK† condition

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.9-5 Select P2-control from the remote-end in TPOS01††


†Note:The ILK function provides the operation criteria for “P2-control”.
††Note: To identify the input and output points of the other TPOS logics, see Table

GRL200 (Soft 033 & 037)


- 907 -
6F2S1914 (0.37)

4.9-5,Table 4.9-7, and Table 4.9-10.


§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.

Output signal to BO
The TPOS01 function, in Figure 4.9-5, can issue a “Select success” signal at the output point
“TPOS01_P2SL_BO_FL” when the TPOS01 function determines that the received signal
“Select command (Remote-P2-Control)” is true. If the TPOS01 function determines that the
“Remote-P2-Control” signal is not true, the TPOS01 function returns to the “Wait for a
command” stage.

(iii) Receiving “select command P3-control” from the remote-end


Figure 4.9-6 outlines the reception of the select command e in P3-control from the remote end.

Wait for a command

Select stage Wait for a command

P1 control from the remote-end


Cancel logic

P2control from the remote-end Cancel command

P3 control from the remote-end


Failed
Cancel logic
Signal reception Select
Selection logic Signal output
IEC61850 decision Success

P1 control from the local-end


Operate logic
P2 control from the local-end
Operate command
P3 control from the local-end

P1 control by the PLC function Operate logic

P2 control by the PLC function

P3 control by the PLC function

Figure 4.9-6 Outline of select command for ‘P3-control’

Input point mapped from the communication.


Figure 4.9-7 shows the select logic when a “Select command P3 (Remote-P3-Control)” signal is
received at the input-point “DEV01_CONTROL_REQ”.

GRL200 (Soft 033 & 037)


- 908 -
6F2S1914 (0.37)

Input Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)


Command “P3-Control” from the remote
For SBO operation
513001 7004016D08 DEV01_CONTROL_REQ Select command
with ILK† condition & 1≥ &

For DIR operation


To BO connection
Operate command
with ILK† condition & “TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
ILK† condition (“P3”) passed
TPOS1-P3 0 t Select “success”

For SBO operation 0.1s

Select command &


without ILK† condition
To “Wait for a command”
For DIR operation 0 t
Operate command Select “Failed”
& 0.6s
without ILK† condition

Either “SBO mode” or “DIR mode” In SBO operate


(e.g., “ctlmodel” in IEC61850*)
In DIR operate

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.9-7 Select ‘P3-control’ from the remote-end in TPOS01††


†Note:The ILK function provides the operation criteria for “P3 control”.
††Note: To identify the input and output points of the other TPOS logics, see Table 4.9-5,
Table 4.9-7 and Table 4.9-10.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.

Output signal to BO
The TPOS01 function, in Figure 4.9-7, can issue a signal “Select success” at the output point
“TPOS01_P3SL_BO_FL” when the TPOS01 function determines that the received signal
“Select command P3 (Remote-P3-Control)” is true. If the TPOS01 function determines that the
“Remote-P3-Control” is not true, the TPOS01 function returns to the “Wait for a command”
stage.

GRL200 (Soft 033 & 037)


- 909 -
6F2S1914 (0.37)

(iv) Receiving “Select command P1-control” from the local-end.


Figure 4.9-8 outlines the reception of the select command ‘P1-control’ from the local-end.

Wait for a command

Select stage Wait for a command

P1 control from the remote-end Cancel logic

P2controlfromthe remote-end Cancel command

P3 control from the remote-end


Cancel logic
P1 control from the local-end
Failed

Keying “Select Select


Selection logic Signal output
command” decision Success

Operate logic
P2 control from the local-end
Operate command
P3 control from the local-end

P1 control by the PLC function Operate logic

P2 control by the PLC function

P3 control by the PLC function

Figure 4.9-8 Outline of select command ’P1-control’

Input signal generated at the local-end


Figure 4.9-9 shows the select logic when a “Select command (Local-P1-Control)” signal is
applied to the TPOS01 function. The signal is provided when a “Local-P1-control” key is
pressed on the IED front panel; the user is not required to map the signal from IEC61850. Note
that the user should set scheme switch [TPOS01-CTRAHMI] to SBO when the operation from
the IED front panel is required, we will discuss how to set in chapter User interface: Control
sub-menu.

GRL200 (Soft 033 & 037)


- 910 -
6F2S1914 (0.37)

Input Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)


For SBO operation
Command “Local-P1-Control” Select command
with ILK† condition & 1≥ &
To “Wait for a next
For DIR operation SBO command”
Operate command To BO connection
ILK† condition (“P1”) passed with ILK† condition & “TPOS01_P1SL_BO_FL”
TPOS01-P1 (513001_8A04011DC4)
DIR
ILK† bypassing 1≥ 0 t
Select “success”
ICB_STATE
0.1s

To “Wait for a command”


0 t
Select “Failed”

0.6s

[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.9-9 Selection logic for P1-control at the IED locally in TPOS01††
†Note:The ILK function provides the operation criteria for “P1-control”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the input/output signals of the other TPOS logics, see Table 4.9-6,
Table 4.9-7 and Table 4.9-10.

Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P1SL_BO_FL”.
Note: The signal “TPOS01_P1SL_BO_FL” is the same as the signal shown in Figure
4.9-3. If the input signal “Local-P1-Control” is not true, the TPOS01 function
returns to the “Wait for a command” stage.

(v) Receiving “Select command P2-control” from the local-end.


Figure 4.9-10 outlines the reception of the select command ‘P2-control’ from the local-end.

GRL200 (Soft 033 & 037)


- 911 -
6F2S1914 (0.37)

Wait for a command

Select stage Wait for a command

P1 control from the remote-end Cancel logic

P2 control from the remote-end Cancel command

P3 control from the remote-end


Cancel logic
P1 control from the local-end

P2control from the local-end


Failed

Keying “Select Select


Selection logic Signal output
command” decision Success Operate logic
Operate command

P3 control from the local-end

P1 control by the PLC function Operate logic

P2 control by the PLC function

P3 control by the PLC function

Figure 4.9-10 Outline of select command for ‘P2-control’

Input signal generated at the local-end


Figure 4.9-11 shows the select logic when a “Select command P2 (Local-P2-Control)” signal is
applied to the TPOS01 function. The signal is provided when the user presses a “Local-P2-
control” key on the IED front panel; the user is not required to take account of mapping.
Input Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)


For SBO operation
Command “Local-P2-Control” Select command
with ILK† condition & 1≥ &
For DIR operation SBO
Operate command To BO connection
ILK† condition (“P2”) passed with ILK† condition & “TPOS01_P2SL_BO_FLG”
TPOS1-P2 (513001_8A04011DC6)
DIR
ILK† bypassing 1≥ 0 t
Select “success”
ICB_STATE
0.1s

To “Wait for a command”


0 t
Select “Failed”

0.6s

[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.9-11 Select P2-control on the front panel in TPOS01††


†Note:The ILK function provides the operation criteria for “P2-control”.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when

GRL200 (Soft 033 & 037)


- 912 -
6F2S1914 (0.37)

it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
††Note: To identify the input/output signals of the other TPOS logics, see Table 4.9-6,
Table 4.9-7, and Table 4.9-10.

Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue “Select success”
signal at the output-point “TPOS01_P2SL_BO_FLG”.
1Note: The “TPOS01_P2SL_BO_FLG” signal is the same as the signal shown in Figure
4.9-5. If the “Local-P2-Control” signal is not true, the TPOS01 function returns to
the “Wait for a command” stage.

(vi) Receiving “Select command P3-control” from the local-end


Figure 4.9-12 outlines the reception of the select command ‘P3-control’ from the local-end.

Wait for a command

Select stage Wait for a command

P1 control from the remote-end Cancel logic

P2 control from the remote-end Cancel command

P3 control from the remote-end


Cancel logic
P1 control from the local-end

P2 control from the local-end

P3control from the local-end


Failed
Operate logic
Keying “Select Select
Selection logic Signal output Operate command
command” decision Success

P1 control by the PLC function Operate logic

P2 control by the PLC function

P3 control by the PLC function

Figure 4.9-12 Outline of select command ’P3-control’

Input signal generated at the local-end


Figure 4.9-13 shows the select logic when a “Select command (Local-P3-Control)” signal is
applied to the TPOS01 function. The signal is provided when the user press a “Local-P3-control”
key on the IED front panel; the user is not required to take account of mapping.

GRL200 (Soft 033 & 037)


- 913 -
6F2S1914 (0.37)

Input Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)


For SBO operation
Command “Local-P3-Control” Select command
with ILK† condition & 1≥ &
For DIR operation SBO
Operat command To BO connection
ILK† condition (“P3”) passed with ILK† condition & “TPOS01_P3SL_BO_FLG”
TPOS1-P3 (513001_8A04011DC8)
DIR
ILK† bypassing 1≥ 0 t
Select “success”
ICB_STATE
0.1s

To “Wait for a command”


0 t
Select “Failed”

0.6s

[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO

Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL

Figure 4.9-13 Select ‘P3-control’ on the front panel in TPOS01††


†Note:The ILK function provides the operation criteria for “P3-control”.
††Note: To identify the input/output signals of the other TPOS logics, see Table
4.9-6,Table 4.9-7 , and Table 4.9-10.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.

Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P3SL_BO_FLG”.
1Note: The “TPOS01_P3SL_BO_FLG” signal is the same signal as shown in Figure 4.9-7.
If the “Local-P3-Control” signal is not true, the TPOS01 function returns to the
“Wait for a command” stage.

(vii) Receiving “Select command P1-control” by PLC function


Figure 4.9-14 outlines the reception of the select command ‘P1-control’ by the PLC function.

GRL200 (Soft 033 & 037)


- 914 -
6F2S1914 (0.37)

Wait for a command

Select stage Wait for a command

P1 control from the remote-end Cancel logic

P2 control from the remote-end Cancel command

P3 control from the remote-end


Cancel logic
P1 control from the local-end

P2 control from the local-end

P3 control from the local-end

Operate logic
P1control by the PLC function
Failed Operate command

PLC logic programmed Select


Selection logic Signal output
by the user decision Success
Operate logic

P2 control by the PLC function

P3 control by the PLC function

Figure 4.9-14 Outline of select command ’P1-control’

Input signal from the PLC function


Figure 4.9-15 shows the select logic when a “Select command P1-Control (PLC-P1-Control)”
signal is generated by the PLC function. There are two input points for the reception: the
former connection point(PLC#1) is used for the reception of the select-command when the
interlock check is required, the later connection point(PLC#2) is used for the reception of the
select-command when the interlock check is not required. That is, for the TPOS01 function,
when the signal “Select command P1-Contol (PLC-P1-Control)” generated in the user-
programmed logic is applied for the select logic, and when interlock-check is required in the
select-logic, use connection point (PLC#1:e.g.,DEV01_P1_INTERLOCK)”. Alternatively, if the
interlock check is not required, use the other connection point (PLC#2:e.g.,
DEV01_P1_COMMAND)”. PLC#1 and PLC#2 are shown in Table 4.9-2.

GRL200 (Soft 033 & 037)


- 915 -
6F2S1914 (0.37)

510001 7001016D08

Signals from user-PLC logic Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

1≥ &
P1-control command requiring ILK† check To “Wait for a next
For DIR operation
(PLC connection point #1) command”
Operate command
513001 800401EE31 DEV01_P1_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
ILK† condition (“P1”) passed
TPOS1-P1 0 t Select “success”
0.1s

P1-control command not requiring ILK† checking For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE30 DEV01_P1_COMMAND
without ILK† condition & 0.6s

PLC in DIR operate

Select condition‡

Figure 4.9-15 Select ‘P1-control’ by the PLC function in TPOS01††


†Note:The ILK function provides the operation criteria for “P1-control”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
*Note:The TPOS01 function can run in either the “SBO mode” or the “DIR mode”. The
user can use signal called “ctlmodel” when communication is implemented using
IEC61850. To use this signal, the user must map for IEC61850 communication.
††Note: To identify the input and output point of the other TPOS logics, see Table 4.9-8
for the inputs PLC#1 and PLC#2, Table 4.9-10 for the outputs.

Output signal to BO
The TPOS01 function, in Figure 4.9-15, can issue a “Select success” signal at the output-point
“TPOS01_P1SL_BO_FLG”1.
1Note: The “TPOS01_P1SL_BO_FLG” signal is the same as the signal shown in Figure
4.9-13.

(viii) Receiving “Select command P2-control” by PLC function


Figure 4.9-16 outlines the reception of the select command ‘P2-control’ by the PLC function.

GRL200 (Soft 033 & 037)


- 916 -
6F2S1914 (0.37)

Wait for a command

Select stage Wait for a command

P1 control from the remote-end Cancel logic

P2 control from the remote-end Cancel command

P3 control from the remote-end


Cancel logic
P1 control from the local-end

P2 control from the local-end

P3 control from the local-end

Operate logic
P1 control by the PLC function
Operate command

P2control by the PLC function


Failed

Operate logic
PLC logic programmed Select
Selection logic Signal output
by the user decision Success

P3 control by the PLC function

Figure 4.9-16 Outline of select command ’P2-control’

Input signal from the PLC function


Figure 4.9-17 shows the select logic when a signal “Selection command P2-Control (PLC-P2-
Control)” is generated by the PLC function. There are two input points for the reception, like
in the “Select command P1-Control (PLC-P1-Control)” signal. That is, if interlock checking is
required, use connection point (PLC#1:e.g., DEV01_P2_INTERLOCK). Alternatively, if the
inter-lock check is not required, use the connection point (PLC#2:e.g., DEV01_P2_COMMAND).
PLC#1 and the PLC#2 are shown in Table 4.9-3.

GRL200 (Soft 033 & 037)


- 917 -
6F2S1914 (0.37)

510001 7001016D08

Signals from user-PLC logic Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

1≥ &
P2-control command requiring ILK †check
For DIR operation
(PLC connection point #1)
Operate command
513001 800401EE33 DEV01_P2_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
ILK† condition (“P2”) passed
TPOS1-P2 0 t Select “success”
0.1s

P2-control command not requiring ILK† check For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE32 DEV01_P2_COMMAND
without ILK† condition & 0.6s

PLC in DIR operate


510001 8601011DC
Select condition‡

Figure 4.9-17 Select logic ‘P2-control’ using the PLC function in TPOS01††
††Note: To identify the input and output points of the other TPOS logics, see Table 4.9-3
for PLC#1 and #2, and Table 4.9-10 for the outputs.
†Note:The ILK function provides the operation criteria for “P2-control”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.

Output signal to BO
The TPOS01 function, in Figure 4.9-17, can issue a “Select success” signal at the output point
“TPOS01_P2SL_BO_FLG”1.
1Note: The output point “TPOS01_P2SL_BO_FLG” is the same as the signal shown in
Figure 4.9-5.

(ix) Receiving “Select command P3-control” by the PLC function


Figure 4.9-18 outlines the reception of the select command ‘P3-control’ by the PLC function.

GRL200 (Soft 033 & 037)


- 918 -
6F2S1914 (0.37)

Wait for a command

Select stage Wait for a command

P1 control from the remote-end Cancel logic

P2 control from the remote-end Cancel command

P3 control from the remote-end


Cancel logic
P1 control from the local-end

P2 control from the local-end

P3 control from the local-end

Operate logic
P1 control by the PLC function
Operate command
P2 control by the PLC function

P3control by the PLC function Operate logic


Failed

PLC logic programmed Select


Selection logic Signal output
by the user decision Success

Figure 4.9-18 Outline of select command ’P3-control’

Input signal from the PLC function


Figure 4.9-9 shows the select logic when a “Select command P3-Control (PLC-P3-Control)”
signal is generated by the PLC function. There are two input points for the reception of this
signal, like in the “Select Command P1-Control (PLC-P1-Contol)” signal. That is, if interlock
checking is required, use the connection point (PLC#1; e.g., DEV01_P3_INTERLOCK).
Alternatively, if the interlock check is not required, use the connection point (PLC#2; e.g.,
DEV01_P3_COMMAND). PLC#1 and PLC#2 are shown in Table 4.9-4.

GRL200 (Soft 033 & 037)


- 919 -
6F2S1914 (0.37)

510001 7001016D08

Signals from user-PLC logic Selection logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

1≥ &
P3-control command requiring with ILK† check
For DIR operation
(PLC connection point #1)
Operate command
513001 800401EE37 DEV01_P3_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
ILK† condition (“P3”) passed
TPOS1-P3 0 t Select “success”
0.1s

P3-control command not requiring without ILK† check For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE36 DEV01_P3_COMMAND
without ILK† condition & 0.6s

PLC in DIR operate

Select condition‡

Figure 4.9-19 Select ‘P3-control’ using the PLC function in TPOS01††


††Note: To know the input and output points of the other TPOS logics, see Table 4.9-4 for
the input PLC#1 and PLC#2 and Table 4.9-10 for the outputs.

Output signal to BO
The TPOS01 function, in Figure 4.9-19, can issue a “Select success” signal at the output point
“TPOS01_P3SL_BO_FLG”1.
1Note: The output point “TPOS01_P3SL_BO_FLG” is the same as the signal shown in
Figure 4.9-7.

(x) Select condition


Figure 4.9-20 shows the select condition logic in the TPOS01 function. The TPOS01 function
can check the condition for the select command using the signals “TPOS01_ST_P1”,
“TPOS01_ST_P2”, and “TPOS01_ST_P3” (see Table 4.9-35). If the original logic does not meet
with the requirements of the user, the following alternatives are available:
1. The user can replace the original logic with alternative logic,
2. The user can add additional logic to the original logic.

How to replace the original logic


If the user wishes to replace the select condition logic, the user can replace it using the PLC
connection point “User configurable condition” set items:
1. Connect the user-customized logic with TPOS01IN_TMP_25, which is listed as PLC#2
in Table 4.9-8.
2. Set the scheme switch [TPOS01-LGSLFFCT] to PLC.

GRL200 (Soft 033 & 037)


- 920 -
6F2S1914 (0.37)

How to add another select condition signal


If adding another condition is required, the user can add a signal to the select condition logic
using the PLC condition point “User Additional Condition”.
1. Add a user-preferred signal using TPOS01IN_TMP_24, which is listed as PLC#1 in
Table 4.9-8.
2. Set the scheme switch [TPOS01-LGSLFFCT] to Fixed logic.

TPOS01 function (Function ID: 513001)


Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Traveling OR Unmatched condition detected *5 Select condition

Function “Automatic sequence control” is in progress Event suppression detected *6


= TPOS01_QLT_SPP
ASEQ_MULTI_SEL
(513001 8204011F59)
Tripping *4 (“General trip”)
BI board connection error detected*7
GEN. TRIP = TPOS01_QLT_BI_ERR
(513001 8604011F5A)
[SCDEN]*8
Same Directional
OFF Controlling Event
P1-control command received
(513001 8304011D02) &
TPOS01_ST_P1
P2-control command received
&
(513001 8104011D03)

TPOS01_ST_P2
“EDS” never permit to control
P3-control command received from “P1 to P3” and “P3 to P1”.
(513001 8504011D04) &
TPOS01_ST_P3

&

[TPOS01-DEVTYPE]*9
&
EDS

Additional condition (PLC#1 connection point)


513001 800401EE61 TPOS01IN_TMP_24
[TPOS01-LGSLFFCT]
User configurable condition (PLC#2 connection point)
Fixedlogic
513001 810401EE62 TPOS01IN_TMP_25 &

Users must setup this condition correctly


Control hierarchy (e.g. 43RL) (PLC#3 connection point) *10
513001 820401ED50 TPOS01IN_TMP_21
&
IED serious error detected
SERI_ERR

[TPOS01-CTREN]

On

Figure 4.9-20 Select condition logic for ‘P1–P3 control’ in TPOS01*11


*1Note: “Command Blocking” disables any operation except its own; the “Command
blocking” is initiated by the status of “CBK” in a software switch controller
(SOFTSW). The IEC 61850 standard defines “Command Blocking” as “CmdBlk”.
For more information of “CBK”, see Chapter Control and monitoring application:
Software switch control. See the signal “S4301_STATE” of Table 4.9-6.
*2Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used
to protect the substation. The user can program it using GR-TIEMS.

GRL200 (Soft 033 & 037)


- 921 -
6F2S1914 (0.37)

*3Note: If the event “device-travelling is detected, it indicates that another operator


is changing the states of a device. Thus, the IED should inhibit the operation of
any device for the duration that the event is detected. The detecting signal is
denoted as “Traveling OR” in Table 4.9-6.
*4Note: If the issue of a trip command is executed by the IED, any control operation
is blocked until the trip operation is completed. If an IED operates a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
4.9-6.
*5Note: Criteria “unmatched conditions” are decided when “Test-bit status” in a
command is not identical to “IED test status”.
*6Note: The “Event suppression” function can detect chattering on BI circuits. (See
4.9.6(i)-3)
*7Note: A supervision of the Binary IO module can detect connection errors for BI
circuits.
*8Note: The Common control (CMNCTRL) function can test or check the P1–P3
control operations performed by the logic. When the user sets Off for scheme
switch [SCDEN], the operation of the logic is blocked if the logic is running in the
same operation-direction compared with the previous operation-direction. On the
other hand, if On is set for the scheme switch, the logic is not blocked.
*9Note: The user should set scheme switch [TPOS01-DEVTYPE] to EDS when the
earth-switch(ES) is applied for the TPOS01 function.
*10Note: The user will need to program the PLC logic “Control hierarchy condition”
The user is also required to connect the logic condition with the select condition
logic using the connection point “TPOS01IN_TMP_21”. For more information, see
chapter Control and monitoring application: Control hierarchy”. See PLC#3 of
Table 4.9-8.
*11Note: To identify the input points of the other TPOS, see Table 4.9-8 for PLC#1 to
#3.

GRL200 (Soft 033 & 037)


- 922 -
6F2S1914 (0.37)

(xi) Signal name and number


Note: The user should note that the following descriptions shown in the column “M/O”
for each table:
“O” indicates that the signal is provided for the optional usage.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may face an operational failure if the default settings are used.
“N/A” indicates that the user cannot change the state of the signal.

Table 4.9-2 PLC connection points (Input points for ‘P1-control’)


Signal Number Signal Name Description M/O
513001 800401EE31 DEV01_P1_INTERLOCK P1-control checking with interlock in TPOS01 (for PLC#1) O
513001 800402EE31 DEV02_P1_INTERLOCK P1-control checking with interlock in TPOS02 (for PLC#1) O
513001 800403EE31 DEV03_P1_INTERLOCK P1-control checking with interlock in TPOS03 (for PLC#1) O
… …. ….
513001 800418EE31 DEV24_P1_INTERLOCK P1-control checking with interlock in TPOS24 (for PLC#1) O
513001 800401EE30 DEV01_P1_COMMAND P1-control without checking in TPOS01 (for PLC#2) O
513001 800402EE30 DEV02_P1_COMMAND P1-control without checking in TPOS02 (for PLC#2) O
513001 800403EE30 DEV03_P1_COMMAND P1-control without checking in TPOS03 (for PLC#2) O
…. …. ….
513001 800418EE30 DEV24_P1_COMMAND P1-control without checking in TPOS24 (for PLC#2) O

Table 4.9-3 PLC connection points (Input point for ‘P2-control’)


Signal Number Signal Name Description M/O
513001 800401EE33 DEV01_P2_INTERLOCK P2-control checking with interlock in TPOS01 (for PLC#1) O
513001 800402EE33 DEV02_P2_INTERLOCK P2-control checking with interlock in TPOS02 (for PLC#1) O
513001 800403EE33 DEV03_P2_INTERLOCK P2-control checking with interlock in TPOS03 (for PLC#1)
… …. ….
513001 800418EE33 DEV24_P2_INTERLOCK P2-control checking with interlock in TPOS24 (for PLC#1) O
513001 800401EE32 DEV01_P2_COMMAND P2-control without checking in TPOS01 (for PLC#2) O
513001 800402EE32 DEV02_P2_COMMAND P2-control without checking in TPOS02 (for PLC#2) O
513001 800403EE32 DEV03_P2_COMMAND P2-control without checking in TPOS03 (for PLC#2) O
…. …. ….
513001 800418EE32 DEV24_P2_COMMAND P2-control without checking in TPOS24 (for PLC#2) O

Table 4.9-4 PLC connection points (Input point for ‘P3-control’)


Signal Number Signal Name Description M/O
513001 800401EE37 DEV01_P3_INTERLOCK P3-control checking with interlock in TPOS01 (for PLC#1) O
513001 800402EE37 DEV02_P3_INTERLOCK P3-control checking with interlock in TPOS02 (for PLC#1) O
513001 800403EE37 DEV03_P3_INTERLOCK P3-control checking with interlock in TPOS03 (for PLC#1) O
… …. ….
513001 800418EE37 DEV24_P3_INTERLOCK P3-control checking with interlock in TPOS24 (for PLC#1) O
513001 800401EE36 DEV01_P3_COMMAND P3-control without checking in TPOS01 (for PLC#2) O
513001 800402EE36 DEV02_P3_COMMAND P3-control without checking in TPOS02 (for PLC#2) O
513001 800403EE36 DEV03_P3_COMMAND P3-control without checking in TPOS03 (for PLC#2) O
…. …. ….
513001 800418EE36 DEV24_P3_COMMAND P3-control without checking in TPOS24 (for PLC#2) O

GRL200 (Soft 033 & 037)


- 923 -
6F2S1914 (0.37)

Table 4.9-5 Mapping points for the reception of control commands


Signal Number Signal Name Description M/O
513001 7004016D08 DEV01_CONTROL_REQ TPOS01 control command received. (Mapping Data) M
513001 7004026D08 DEV02_CONTROL_REQ TPOS02 control command received. (Mapping Data) M
513001 7004036D08 DEV03_CONTROL_REQ TPOS02 control command received. (Mapping Data) M
… … …
513001 7004186D08 DEV24_CONTROL_REQ TPOS24 control command received. (Mapping Data) M

Table 4.9-6 Input signals to condition logic


Signal Number Signal Name Description M/O
522001 000A011001 CBK_STATE Command Blocking status ( Off / Blocked) N/A
522001 000A021001 ICB_STATE Interlock bypassing switch N/A
5A0001 0008001F41 DCB RCV OR Double Command Blocking (DCB) is in progress. N/A
5A0001 0008001F40 Traveling OR Travelling events are detected. N/A
4A0001 8300001B6F GEN. TRIP General trip N/A
5A0001 3108003F40 SDCEN (This is setting of CMNCTRL) N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A
570001 3103011DA2 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A

Table 4.9-7 PLC connection points Interlock for P1, P2, and P3-control
Signal Number Signal Name Description M/O
570001 3104011DA0 TPOS1-P1 Interlock condition for P1 control in TPOS01. N/A
570001 3104021DA0 TPOS2-P1 Interlock condition for P1 control in TPOS02 N/A
570001 3104031DA0 TPOS3-P1 Interlock condition for P1 control in TPOS03 N/A
… … …
570001 3104181DA0 TPOS24-P1 Interlock condition for P1 control in TPOS24 N/A
570001 3104011DA2 TPOS1-P2 Interlock condition for P2 control in TPOS01. N/A
570001 3104021DA2 TPOS2-P2 Interlock condition for P2 control in TPOS02 N/A
570001 3104031DA2 TPOS3-P2 Interlock condition for P2 control in TPOS03 N/A

570001 3104181DA2 TPOS24-P2 Interlock condition for P2 control in TPOS24 N/A


570001 3104011DA4 TPOS1-P3 Interlock condition for P3 control in TPOS01. N/A
570001 3104021DA4 TPOS2-P3 Interlock condition for P3 control in TPOS02 N/A
570001 3104031DA4 TPOS3-P3 Interlock condition for P3 control in TPOS03 N/A
… … …
570001 3104181DA4 TPOS24-P3 Interlock condition for P3 control in TPOS24 N/A

Table 4.9-8 PLC connection points (Input signals for select condition logic)
Signal Number Signal Name Description M/O
513001 800401EE61 TPOS01IN_TMP_24 TPOS01 additional failure condition(PLC#1) O
513001 800402EE61 TPOS02IN_TMP_24 TPOS02 additional failure condition(PLC#1) O
513001 800403EE61 TPOS03IN_TMP_24 TPOS03 additional failure condition(PLC#1) O
… … …
513001 800418EE61 TPOS24IN_TMP_24 TPOS03 additional failure condition(PLC#1) O
513001 810401EE62 TPOS01IN_TMP_25 TPOS01 user configurable select condition(PLC#2) O
513001 810402EE62 TPOS02IN_TMP_25 TPOS02 user configurable select condition(PLC#2) O
513001 810403EE62 TPOS03IN_TMP_25 TPOS03 user configurable select condition(PLC#2) O
… … …
513001 810418EE62 TPOS24IN_TMP_25 TPOS24 user configurable select condition(PLC#2) O
513001 820401ED50 TPOS01IN_TMP_21 TPOS01 control hierarchy condition(PLC#3) M
513001 820402ED50 TPOS02IN_TMP_21 TPOS02 control hierarchy condition(PLC#3) M

GRL200 (Soft 033 & 037)


- 924 -
6F2S1914 (0.37)

Signal Number Signal Name Description M/O


513001 820403ED50 TPOS03IN_TMP_21 TPOS03 control hierarchy condition(PLC#3) M
… … ….
513001 820418ED50 TPOS24IN_TMP_21 TPOS24 control hierarchy condition(PLC#3) M

Table 4.9-9 PLC monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
513001 8004011F54 TPOS01_SC_ST_ERR TPOS01 select command mode is invalid.
513001 8004021F54 TPOS02_SC_ST_ERR TPOS02 select command mode is invalid.
513001 8004031F54 TPOS03_SC_ST_ERR TPOS03 select command mode is invalid.
… … …
513001 8004181F54 TPOS24_SC_ST_ERR TPOS24 select command mode is invalid.
513001 8204011F59 TPOS01_QLT_SPP Event suppression detected (TPOS01)
513001 8204021F59 TPOS02_QLT_SPP Event suppression detected (TPOS02)
513001 8204031F59 TPOS03_QLT_SPP Event suppression detected (TPOS03)
… … …
513001 8204181F59 TPOS24_QLT_SPP Event suppression detected (TPOS24)
513001 8604011F5A TPOS01_QLT_BI_ERR BI connection error detected(TPOS01)
513001 8604021F5A TPOS02_QLT_BI_ERR BI connection error detected(TPOS02)
513001 8604031F5A TPOS03_QLT_BI_ERR BI connection error detected(TPOS03)
… … ….
513001 8604181F5A TPOS24_QLT_BI_ERR BI connection error detected(TPOS24)

Table 4.9-10 PLC monitoring points (Output signal for BIO)


Signal Number Signal Name Description
513001 8A04011DC4 TPOS01_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS01
513001 8A04021DC4 TPOS02_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS02
513001 8A04021DC4 TPOS03_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS03
… … …
513001 8A04181DC4 TPOS241SL_BO_FLG Select command (P1) for Binary Output in TPOS24
513001 8A04011DC6 TPOS01_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS01
513001 8A04021DC6 TPOS02_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS02
513001 8A04031DC6 TPOS03_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS03
… …. ….
513001 8A04181DC6 TPOS24_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS24
513001 8A04011DC8 TPOS01_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS01
513001 8A04021DC8 TPOS02_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS02
513001 8A04031DC8 TPOS03_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS03
… …. ….
513001 8A04181DC8 TPOS24_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS24

(xii) Setting names


Table 4.9-11 Settings for ‘SBO control in TPOSxx
Setting Name Description Default Setting item or value

TPOSxx-CTREN Activation of the control function in TPOS01–24 On Off / On


TPOSxx-LGSLFFCT Logic selector for select condition (TPOS01–24) Fixedlogic Fixedlogic / PLC
TPOSxx-DEVTYPE Equipment(EDS or 43SW) type selector switch switch / EDS
TPOSxx-CTRHMI Activation for the panel control locally (TPOS01–24) On Off / On
Note: The “xx” within “TPOSxx” represents the function number. If TPOS03 is
considered, “xx” is equal to “03”. The suffix “xx” can be represented from 01 to 24.)

GRL200 (Soft 033 & 037)


- 925 -
6F2S1914 (0.37)

4.9.2 Cancel logic for SBO mode


In the SBO control mode, the reception of a cancel command can be possible when the cancel
conditions are satisfied, the function can discard the select command; finally, the operation
returns to the initial stage (i.e., “wait for a command”).

(i) Receiving “Cancel” from the remote-end


Figure 4.9-21 depicts the cancel command procedure for a cancel command initiated from the
remote-end.
Wait for a command

Select stage Wait for a next command

P1 control from the remote-end Cancel from remote-end


Success

P2 control from the remote-end Signal reception in Cancel


Cancel logic Do nothing
IEC61850 decision Failed
P3 control from the remote-end

P1 control from the local-end


Cancel from the local-end
P2 control from the local-end

P3 control from the local-end


Operate logic
P1 control by the PLC function Operate command

P2 control by the PLC function

Operate logic
P3 control by the PLC function

Figure 4.9-21 Outline of ‘cancel’ command from remote-end

Input point required mapping


Figure 4.9-22 depicts the cancel logic when a “Cancel command (Remote-Cancel)” signal is
applied to the TPOS01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the “Selection command P1 (Remote-P1-Control)” signal.
510001 7001016D08

Input Cancel logic in TPOS01 Output

TPOS01 function (Function ID: 513001)


Command “Remote-cancel”
Cancel command
513001_7004016D08 DEV01_CONTROL_REQ
& To “Wait for a command”
“TPOS01_ CC_SS”
(513001_8604011E95)
Cancel condition† &
Successes to cancel

“Do nothing”

“TPOS01_CC_FS”
(513001_8704011E96)

Operation Failed

Figure 4.9-22 ‘Cancel’ from the remote-end in TPOS01


†Note: The logic “cancel condition” is shown in Figure 4.9-25.

Output signal to BO

GRL200 (Soft 033 & 037)


- 926 -
6F2S1914 (0.37)

The TPOS01 function can issue a “Success to cancel” signal at the monitoring, point
“TPOS01_CC_SS”, when the TPOS01 function has determined that the “Remote-cancel” signal
is true. Another “Operate failed” signal is issued at monitoring point “TPOS01_CC_FS” if the
TPOS01 function is able to determine that the “Remote-cancel” signal is not true.

(ii) Receiving “Cancel” from the local-end


Figure 4.9-23 outlines the reception of the ‘cancel’ command from the local-end.
Wait for a command

Select stage
Wait for a next command
P1 control from remote-end
Cancel from the remote-end
P2 control from remote-end
Cancel from the local-end
Success
P3 control from remote-end

P1 control from front panel Keying “Cancel Cancel


Cancel logic Do nothing
command” decision Failed
P2 control from front panel

P3 control from front panel


Operate logic
P1 control by PLC function Operate command

P2 control by PLC function

Operate logic
P3 control by PLC function

Figure 4.9-23 Outline of ‘cancel’ command from the local-end

Input signal
Figure 4.9-24 depicts the cancel logic when a “Cancel command (Local-cancel)” signal is applied
to the TPOS01 function. The signal is generated when the “Cancel” key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
“Local-cancel” signal, the logic is able to output a result signal, provided that the “cancel
condition” checking is satisfied.
510001 7001016D08

Input Cancel logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

Cancel command
Command “Local-cancel”
& To “Wait for a command”
“TPOS01_ CC_SS”
(513001_8604011E95)
Cancel condition &
Successes to cancel

“Do nothing”
“TPOS01_CC_FS”
(513001_8704011E96)

Operation Failed

Figure 4.9-24 ‘Cancel’ from the front panel


Output signal to BO
The TPOS01 function, illustrated in Figure 4.9-24, is able to issue a “Selection to cancel” signal

GRL200 (Soft 033 & 037)


- 927 -
6F2S1914 (0.37)

at the monitoring point “TPOS01_CC_SS”, when the TPOS01 function determines that the
“Local-Cancel” signal is true.

(iii) Cancel condition logic


Figure 4.9-25 shows the cancel condition logic. As the criteria “Unmatched condition detected”
is connected normally for the cancel condition logic, set Fixedlogic for the scheme switch
[TPOS01-LGCNFFCT].

TPOS01 function (Function ID: 513001)

Unmatched condition detected *1 To cancel logic in


& 1≥ TPOS01

[TPOS01-LGCNFFCT]
User configurable condition (PLC connection point)
Fixedlogic
513001 800401EE69 TPOS01IN_TMP_40 &

Figure 4.9-25 Logic “Cancel condition” in TPOS01


1Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”, like in Figure 4.9-20.
2Note: With the exception of the above ‘cancel’ logic, there is an operate-condition logic
within the TPOS01 function; the operate-condition logic will always checks
conditions. That is, the user is required to set either the “Operate-condition” or the
“cancel-condition” logic.

If the original logic does not meet with the requirements of the user, it can be replaced
using the connection point “User Configurable condition”:
 Connect the user-customized logic, with the “TPOS01IN_TMP_40”, which is listed
in Table 4.9-12.
 Set scheme switch [TPOS01-LGCNFFCT] to PLC.

(iv) Signal name and number


Note: The user should note the following descriptions shown in the column “M/O” in
each table:
“O” indicates that the signal is provided for the optional use.
“M” indicates that the user should map/set/configure using the signal;
otherwise, the user may experience an operational failure for the default
settings.
“N/A” indicates that the user cannot change the state of the signal.

Table 4.9-12 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number Signal Name Description M/O
513001 800401EE69 TPOS01IN_TMP_40 TPOS1 user configurable cancel condition O
513001 800401EE69 TPOS02IN_TMP_40 TPOS2 user configurable cancel condition O
513001 800401EE69 TPOS03IN_TMP_40 TPOS3 user configurable cancel condition O

GRL200 (Soft 033 & 037)


- 928 -
6F2S1914 (0.37)

Signal Number Signal Name Description M/O


… … …
513001 800418EE69 TPOS24IN_TMP_40 TPOS3 user configurable cancel condition O

Table 4.9-13 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
513001 8604011E95 TPOS01_CC_SS Cancel succeed in TPOS01
513001 8604021E95 TPOS02_CC_SS Cancel succeed in TPOS02
513001 8604031E95 TPOS03_CC_SS Cancel succeed in TPOS03
… … …
513001 8604181E95 TPOS24_CC_SS Cancel succeed in TPOS24
513001 8704011E96 TPOS01_CC_FS Cancel failed in TPOS01
513001 8704021E96 TPOS02_CC_FS Cancel failed in TPOS02
513001 8704031E96 TPOS03_CC_FS Cancel failed in TPOS03
… … …
513001 8704181E96 TPOS24_CC_FS Cancel failed in TPOS24

(v) Setting name


Note: The “xx” within “TPOSxx” represents the TPOS function number. (e.g., if TPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented from
“01” to “24”.)

Table 4.9-14 Setting for ‘Cancel’ in TPOSxx


Setting Name Description Default Setting item or value

TPOSxx-LGCNFFCT Logic selector for cancel condition (TPOS01-24) Fixedlogic Fixedlogic / PLC

GRL200 (Soft 033 & 037)


- 929 -
6F2S1914 (0.37)

4.9.3 Operate logic for SBO/DIR modes


After the completion of the operation of the select logic, the operate logic starts to control the
device.

(i) Receiving “Operate command for P1-control” from the remote-end


Figure 4.9-26 depicts the reception of the operate command ‘P1-control’ from the remote-end.

Wait for a command

Select stage Wait for a next command

P1 control from the remote-end


P1 control from the remote-end Success
Operation
Signal reception in Operate logic Signal output
decision
IEC61850

Failed Do nothing

P2 control from the remote-end P2 control from the remote-end

P3 control from the remote-end P3 control from the remote-end

P1 control from the local-end P1 control from the local-end

P2 control from the local-end P2 control from the local-end

P3 control from the local-end P3 control from the local-end

P1 control by the PLC function P1 control by the PLC function

P2 control by the PLC function P2 control by the PLC function

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-26 Outline of operate command ‘P1-control’

Mapping required for Input point


Figure 4.9-27 illustrates the operate logic when a “Operate command P1 (Remote-P1-Control)”
signal is applied to the TPOS01 function. The input-point “DEV01_CONTROL_REQ” is used
for the reception of the “Operate command P1 (Remote-P1-Control)”.

GRL200 (Soft 033 & 037)


- 930 -
6F2S1914 (0.37)

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

“TPOS01_P1EC_OK_CSF” “TPOS01_P1EC_OK_CS”
Command “Remote-P1-Control” (513001 8004011E7E) (5130018004011E81)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operate Cmd.
without ILK† condition

ILK† condition (“P1”) passed S


&
TPOS1-P1 R
User configurable condition
(PLC#1 connection point)

513001 800401EE56 TPOS01IN_TMP_27


[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
“TPOS01_P1EX_BO”
Operate condition‡
(5130018104011DD0) §§

[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


[TPOS01-RST]
“TPOS01_P1EC_OK_CSF” (513001 8604011E91) ‡‡
0 t
(513001 8004011E7E)
&
1.0s- 100.0s Operate Failed

Figure 4.9-27 Operate ‘P1-control’ from the remote-end in TPOS01††


†Note:The ILK function can provide the operation criteria for “P1” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” signal is required, it can be programmed by the
user and used to replace the signal the signal generated by the original operate-
condition logic. The alternative “operate-condition” can be connected to the above
logic using connection point #1 “User configurable condition” That is, set the
scheme switch [TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_27”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of the output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by the [TPOS01-RST] has been reached.
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for scheme switch

GRL200 (Soft 033 & 037)


- 931 -
6F2S1914 (0.37)

[TPOS01-LGP1EXOT]. The “Operate-completed” signal can also be issued from


logic programmed by the user, in place of the logic shown in Figure 4.9-26. The
user-programmed logic is connected internally to the signal “operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User-configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.

Output signal to BO
The TPOS01 function, in Figure 4.9-27, can issue an “Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the received “Remote-P1-
Control” signal is true.

(ii) Receiving “Operate command P2-control” from the remote-end


Figure 4.9-28 depicts the reception of the operate command ‘P2-control’ from the remote-end.

Wait for a command

Select logics Wait for a next command.

P1 control from the remote-end P1 control from the remote-end

P2 control from the remote-end


P2 control from the remote-end Success
Operation
Signal reception in Operate logic Signal output
decision
IEC61850

Failed Do nothing

P3 control from the remote-end P3 control from the remote-end

P1 control from the local-end P1 control from the local-end

P2 control from the local-end P2 control from the local-end

P3 control from the local-end P3 control from the local-end

P1 control by the PLC function P1 control by the PLC function

P2 control by the PLC function P2 control by the PLC function

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-28 Outline of operate command ‘P2-control’

Input signal required mapping


Figure 4.9-19 illustrates the operate logic when an “Operate command P2 (Remote-P2-Control)”
signal is applied to the TPOS01 function. The input-point “DEV01_CONTROL_REQ” is used
for the reception of the “Operate command P2 (Remote-P2-Control)”.

GRL200 (Soft 033 & 037)


- 932 -
6F2S1914 (0.37)

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command “Remote-P2-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operate Cmd.
without ILK† condition

ILK† condition (“P2”) passed S


&
TPOS1-P2 R
User configurable condition
(PLC#3 connection point)

513001 810401EE57 TPOS01IN_TMP_28


[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
“TPOS01_P2EX_BO”
Operate condition‡
(513001 8204011DD3) §§

[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


[TPOS01-RST]
(513001 8604011E91) ‡‡
“TPOS01_P2EC_OK_CSF”
0 t
(513001 8004011E7F)
&
1.0s- 100.0s Operation Failed

Figure 4.9-29 Operate ‘P2-control’ from the remote-end in TPOS01††


†Note:The ILK function can provide the operation criteria for “P2” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” signal is required, it can be programmed by the
user and used to replace the signal generated by the original operate-condition
logic. The alternative “operate-condition” can be connected to the above logic using
connection point #3 “User configurable condition” That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_28”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST].
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. The “operate-completed” signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.9-26. connect
the signal “operate completed” generated in the programmed logic to the

GRL200 (Soft 033 & 037)


- 933 -
6F2S1914 (0.37)

connection point#2 “User configurable condition”. That is, set the scheme switch
[TPOS01-LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-17 for PLC#3 and Table 4.9-20 for the outputs.

Output signal to BO
The TPOS01 function, in Figure 4.9-29, can issue an “Operate” signal at the output-point
“TPOS01_P2EX_BO”, when the TPOS01 function determine that the input signal “Remote-P2-
Control” is true.

(iii) Receiving “Operate command P3-control” from the remote-end


Figure 4.9-28 depicts the reception of the operate command ‘P3-control’ from the remote-end.

Wait for a command

Select logics Wait for a next command

P1 control from the remote-end P1 control from the remote-end

P2 control from the remote-end P2 control from the remote-end

P3 control from the remote-end


P3 control from the remote-end Success
Operation
Signal reception in Control logic Signal output
decision
IEC61850

Failed Do nothing

P1 control from the local-end P1 control from the local-end

P2 control from the local-end P2 control from the local-end

P3 control from the local-end P3 control from the local-end

P1 control by the PLC function P1 control by the PLC function

P2 control by the PLC function P2 control by the PLC function

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-30 Outline of operate command ‘P3-control’

Input signal required mapping


Figure 4.9-31 illustrate the operate logic when an “Operate command P3 (Remote-P3-Control)”
signal is applied to the TPOS01 function. The input-point “DEV01_CONTROL_REQ” is used
for the reception of the “Operate command P3 (Remote-P3-Control)”.

GRL200 (Soft 033 & 037)


- 934 -
6F2S1914 (0.37)

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

“TPOS01_P3EC_OK_CSF” “TPOS01_P3EC_OK_CS”
Command “Remote-P3-Control” (5513001 8004011E80) (513001 8404011E83)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operation Cmd.
without ILK† condition

ILK† condition (“P3”) passed S


&
TPOS1-P3 R
User configurable condition
(PLC#4 connection point)

513001 840401EE58 TPOS01IN_TMP_29


[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
“TPOS01_P3EX_BO”
Operate condition‡
(513001 8204011DD6) §§

[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


[TPOS01-RST] (513001 8604011E91) ‡‡
“TPOS01_P3EC_OK_CSF”
0 t
(513001 8004011E80)
&
1.0s- 100.0s Operation Failed

Figure 4.9-31 Operate ‘P3-control’ from the remote-end in TPOS01††


†Note:The ILK function can provide the operation criteria for “P3” control.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-18 for PLC#4, and Table 4.9-20 for the outputs.
‡Note:An “operate condition” signal is generated inthe operate-condition logic (Figure
4.9-44) when Fix logic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative “operate-condition” can be connected to the above logic using
connection point #4 “User configurable condition” That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_29”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST]
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. The “Operate-completed” signal can also be issued from

GRL200 (Soft 033 & 037)


- 935 -
6F2S1914 (0.37)

logic programmed by the user in place of the logic shown in Figure 4.9-26. The
user-programmed logic is connected internally to the “operate completed” signal,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.

Output signal to BO
The TPOS01 function, in Figure 4.9-31, can issue an “Operate” signal at the output-point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the input signal “Remote-
P3-Control” is true.

(iv) Receiving “Operate command P1-control” from the local-end


Figure 4.9-32 depicts the operation logic of the operate command ‘P1-control’ from the local-
end.

Wait for a command

Select logics Wait for a next command

P1 control from the remote-end P1 control from the remote-end

P2 control from the remote-end P2 control from the remote-end

P3 control from the remote end P3 control from the remote end

P1 control from the local-end


P1 control from the local-end Success
Operation
Signal reception from the Operate logic Signal output
decision
front panel

Failed Do nothing

P2 control from the local-end P2 control from the local-end

P3 control from the local-end P3 control from the local-end

P1 control by the PLC function P1 control by the PLC function

P2 control by the PLC function P2 control by the PLC function

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-32 Outline of Operate command ‘P1-control’

Input signal generated at the local-end


Figure 4.9-33 illustrates the operate logic when an “Operate command P1 (Local-P1-Control)”
signal is applied to the TPOS01 function. The signal is provided when “P1-control” is keyed on
the IED front panel.

GRL200 (Soft 033 & 037)


- 936 -
6F2S1914 (0.37)

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

“TPOS01_P1EC_OK_CSF” “TPOS01_P1EC_OK_CS”
Command Local-P1-Control” (513001 8004011E7E) (5130018004011E81)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operate Cmd.
without ILK† condition
ILK† condition (“P1”) passed
S
TPOS1-P1 &
ILK† bypassing R
ICB_STATE
1≥

User configurable condition (PLC#3 connection point)


513001 810401EE57 TPOS01IN_TMP_28
[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
PLC#3
“TPOS01_P1EX_BO”
Operate condition‡
(5130018104011DD0) §§

[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


PLC#2 [TPOS01-RST] (513001 8604011E91) ‡‡
“TPOS01_P1EC_OK_CSF”
0 t
(513001 8004011E7E)
&
1.0s- 100.0s Operate Failed

Figure 4.9-33 Operate ‘P1-control’ on the front panel TPOS01††

†Note:The ILK function can provide the operation criteria for “P1” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #3 “User configurable condition” That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_28”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST].

GRL200 (Soft 033 & 037)


- 937 -
6F2S1914 (0.37)

§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for the scheme
switch [TPOS01-LGP1EXOT]. The “Operate completed” signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.9-26. The user-programmed logic is connected internally to the “operate
completed”, hence this signal is now generated by the user-programmed logic at
connection point#2 “User configurable condition”. That is, set the scheme switch
[TPOS01-LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.

Output signal to BO
The TPOS01 function, in Figure 4.9-33, can issue an “Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the “Local-P1-Control”
signal is true.

(v) Receiving “operate command P2-control” from the local-end


Figure 4.9-34 depicts the reception of the operate command ‘P2-control’ from the local-end.

Wait for a command

Select logics Wait for a next command

P1 control from the remote-end P1 control from the remote-end

P2 control from the remote-end P2 control from the remote-end

P3 control from the remote end P3 control from the remote end

P1 control from the local-end P1 control from the local-end

P2 control from the local-end


P2 control from the local-end Success
Operation
Signal reception from Operate logic Signal output
decision
the front panel

Failed Do nothing

P3 control from the local-end P3 control from the local-end

P1 control by the PLC function P1 control by the PLC function

P2 control by the PLC function P2 control by the PLC function

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-34 Outline of Operate command ‘P2-control’

Input signal generated at the local-end.


Figure 4.9-35 illustrates the operate logic when an “Operation command P2 (Local-P2-Control)”
signal is applied to the TPOS01 function. The input signal is provided when “P2-control” is
keyed on the IED front panel.

GRL200 (Soft 033 & 037)


- 938 -
6F2S1914 (0.37)

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command Local-P2-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operate Cmd.
without ILK† condition
ILK† condition (“P2”) passed
S
TPOS1-P2 &
ILK† bypassing R
ICB_STATE
1≥

User configurable condition (PLC#3 connection point)


513001 810401EE57 TPOS01IN_TMP_28
[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
“TPOS01_P2EX_BO”
Operate condition‡
(513001 8204011DD3) §§

[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(513001 8004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


[TPOS01-RST] (513001 8604011E91) ‡‡
“TPOS01_P2EC_OK_CSF”
0 t
(513001 8004011E7F)
&
1.0s- 100.0s Operate Failed

Figure 4.9-35 Operate ‘P2-control’ on the front panel in TPOS01††


†Note:The ILK function can provide the operation criteria for “P2” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the to the above logic using
connection point #3 “User configurable condition” That is, set the [TPOS01-
LGCTRCON] to PLC and using “ TPOS01IN_TMP_28”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [TPOS01-RST].
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for the [TPOS01-
LGP1EXOT]. The “Operate completed” signal can also be issued from the logic
programmed by the user in place of the logic shown in Figure 4.9-26 . The user-
programmed logic is connected internally to the signal “operate completed”, hence

GRL200 (Soft 033 & 037)


- 939 -
6F2S1914 (0.37)

this signal is now generated by the user-programmed logic at connection point#2


“User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-17 for PLC#3 and Table 4.9-20 for the outputs.

Output signal to BO
The TPOS01 function, in Figure 4.9-35, can issue an “Operate” signal at the output point
“TPOS01_P2EX_BO”, when the TPOS01 function determines that the “Local-P2-Control”
signal is true.

(vi) Receiving “operate command P3-control” from the local-end


Figure 4.9-36 depicts the reception of the operate command ‘P3-control’ from the local-end.

Wait for a command

Select logics Wait for a next command

P1 control from the remote-end P1 control from the remote-end

P2 control from the remote-end P2 control from the remote-end

P3 control from the remote end P3 control from the remote end

P1 control from the local-end P1 control from the local-end

P2 control from the local-end P2 control from the local-end

P3 control from the local-end


P3 control from the local-end Success
Operation
Signal reception from Operate logic Signal output
decision
front panel

Failed Do nothing

P1 control by the PLC function P1 control by the PLC function

P2 control by the PLC function P2 control by the PLC function

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-36 Outline of Operate command ‘P3-control’

Input signal generated at the local-end


Figure 4.9-37 illustrates the operate logic when an “Operate command P3 (Local-P3-Control)”
signal is applied to the TPOS01 function. The input signal is provided when “P3-control” is
keyed on the IED front panel.

GRL200 (Soft 033 & 037)


- 940 -
6F2S1914 (0.37)

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command Local-P3-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s

Operation Cmd.
without ILK† condition
ILK† condition (“P2”) passed
S
TPOS1-P2 &
ILK† bypassing R
ICB_STATE
1≥

User configurable condition (PLC#3 connection point)


513001 810401EE57 TPOS01IN_TMP_28
[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
“TPOS01_P2EX_BO”
Operate condition‡
(513001 8204011DD3) §§

[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(513001 8004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


[TPOS01-RST] (513001 8604011E91) ‡‡
“TPOS01_P2EC_OK_CSF”
0 t
(513001 8004011E7F)
&
1.0s- 100.0s Operation Failed

Figure 4.9-37 Operate ‘P3-control’ on the front panel in TPOS01


†Note:The ILK function can provide the operation criteria for “P3” control.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-18 for PLC#4, and Table 4.9-20 for the outputs.
‡Note:An “operate condition signal” is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #3 “User configurable condition” That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_28”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST].
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. The “Operate completed” signal can also be issued from the

GRL200 (Soft 033 & 037)


- 941 -
6F2S1914 (0.37)

logic programmed by the user in place of the logic shown in Figure 4.9-26. The
user-programmed logic is connected internally to the signal “operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.

Output signal to BO
The TPOS01 function, in Figure 4.9-37, can issue an “Operate” signal at the output point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the “Local-P3-Control”
signal is true.

(vii) Receiving “operate command P1-control” using the PLC function


Figure 4.9-38 outlines the reception of the operate command ‘P1-control’ using the PLC
function.

Wait for a command

Select logics Wait for a next command

P1 control from the remote-end P1 control from the remote-end

P2 control from the remote-end P2 control from the remote-end

P3 control from the remote end P3 control from the remote end

P1 control from the local-end P1 control from the local-end

P2 control from the local-end P2 control from the local-end

P3 control from the local-end P3 control from the local-end

P1 control by the PLC function


P1 control by the PLC function Success
Operation
Signal generation by the Operate logic Signal output
decision
PLC function

Failed Do nothing

P2 control by the PLC function P2 control by the PLC function

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-38 Outline of Operate command ‘P1-control’

Input signal from the PLC function


Figure 4.9-39 describes the operate logic when an “Operate command P1 (PLC-P1-Control)”
signal is generated by the PLC function. There are two input points for the reception: the
former connection point (PLC#3) is used for the reception of the operate-command when the
interlock-check is required, the latter connection point (PLC#4) is used for the reception of the
operate-command when the interlock check is not required. That is, for the TPOS01 function
“Operate command P1 (PLC-P1-Control)” signal generated in the user-programmed logic and
when the interlock check is required in the operate logic, apply the signal at connection point
(PLC#3; i.e., DEV01_P1_INTERLOCK).Alternatively, if the interlock check is not required,

GRL200 (Soft 033 & 037)


- 942 -
6F2S1914 (0.37)

apply the signal at other connection point (PLC#4; i.e., DEV01_P1_COMMAND). We should
assume the PLC#3 and PLC#4 as PLC#1 and PLC#2 in Table 4.9-2. Note that the user should
set PLC for scheme switch [TPOS01-LGP1EXOT].

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

Command “PLC-P1-Control” requiring ILK check “TPOS01_P1EC_OK_CSF” “TPOS01_P1EC_OK_CS”


(PLC#3 connection point) (513001 8004011E7E) (5130018004011E81)
[TPOS01-CPW]
513001 800401EE31 DEV01_P1_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-P1-Control” not requiring ILK check 0.1 – 50.0 s
(PLC#4 connection point)
Operate Cmd.
513001 800401EE30 DEV01_P1_COMMAND
without ILK† condition

ILK† condition (“P1”) passed S


&
TPOS1-P1 R
User configurable condition
(PLC#1 connection point)

513001 800401EE56 TPOS01IN_TMP_27


[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
“TPOS01_P1EX_BO”
Operate condition‡
(5130018104011DD0) §§

[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


[TPOS01-RST] (513001 8604011E91) ‡‡
“TPOS01_P1EC_OK_CSF”
0 t
(513001 8004011E7E)
&
1.0s- 100.0s Operate Failed

Figure 4.9-39 Operate P1- control using the PLC function in TPOS01††
†Note:The ILK function can provide the criteria for operation for “P1” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.9-39 using connection point #1
“User configurable condition” That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and use “TPOS01IN_TMP_27”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.

GRL200 (Soft 033 & 037)


- 943 -
6F2S1914 (0.37)

‡‡Note: The “Operate failed” signal is issued when a state-change remains undetected
failing expiration of the setting applied to timer [TPOS01-RST]
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set the scheme switch
[TPOS01-LGP1EXOT]. If the signal to be issued from the logic programmed by the
user instead of the logic shown in Figure 4.9-26, connect the “operate completed”
signal generated in the user-programmed logic to connection point#2 “User
configurable condition”. That is, set PLC to the scheme switch [TPOS01-
LGP1EXOT] and use “TPOS01IN_TMP_38”.

Output signal to BO
The TPOS01 function, in Figure 4.9-39, can issue a “Operate P1-control” signal at output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the signal “PLC-P1-Control”
is true.

(viii) Receiving “operate command P2-control” using the PLC function


Figure 4.9-40 depicts the reception of the operate command “P2-control’ using the PLC function.

Wait for a command

Select logics Wait for a next command

P1 control from the remote-end P1 control from the remote-end

P2 control from the remote-end P2 control from the remote-end

P3 control from the remote end P3 control from the remote end

P1 control from the local-end P1 control from the local-end

P2 control from the local-end P2 control from the local-end

P3 control from the local-end P3 control from the local-end

P1 control by the PLC function P1 control by the PLC function

P2 control by the PLC function


P2 control by the PLC function Success
Operation
Signal generation by the Operate logic Signal output
decision
PLC function

Failed Do nothing

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-40 Outline of Operate command ‘P2-control’ function

Input signal from the PLC function


Figure 4.9-41 depicts the operation logic when an “Operate command P2 (PLC-P2-Control)”
signal is generated by the PLC function. There are two input points for the reception of this
command signal, like in the “Operate command P2 (PLC-P2-Control)” signal. That is, if an
interlock check is required, apply the signal at connection point (PLC#3:i.e.,
DEV01_P2_INTERLOCK). On the other hand, if an interlock check is not required, apply the
signal at connection point (PLC#4:i.e., DEV01_P2_COMMAND). PLC#3 and PLC#4 here are

GRL200 (Soft 033 & 037)


- 944 -
6F2S1914 (0.37)

to be treated as PLC#1 and PLC#2 in Table 4.9-3. Note that the user should set PLC for scheme
switch [TPOS01-LGP2EXOT].

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

Command “PLC-P2-Control” requiring ILK check “TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”


(PLC#3 connection point) (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001 800401EE33 DEV01_P2_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-P2-Control” not requiring ILK check 0.1 – 50.0 s
(PLC#4 connection point)
513001 800401EE32 DEV01_P2_COMMAND Operate Cmd.
without ILK† condition

ILK† condition (“P2”) passed S


&
TPOS1-P2 R
User configurable condition
(PLC#3 connection point)

513001 810401EE57 TPOS01IN_TMP_28


[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
“TPOS01_P2EX_BO”
Operate condition‡
(513001 8204011DD3) §§

[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


[TPOS01-RST] (513001 8604011E91 ‡‡
“TPOS01_P2EC_OK_CSF”
0 t
(513001 8004011E7F)
&
1.0s- 100.0s Operation Failed

Figure 4.9-41 Operate P2-Control by the PLC function in TPOS01††


†Note:The ILK function can provide the criteria foe operation for “P2” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.9-41 using connection point #3
“User configurable condition” That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and use “TPOS01IN_TMP_28”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST]
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for [TPOS01-

GRL200 (Soft 033 & 037)


- 945 -
6F2S1914 (0.37)

LGP1EXOT]. If the signal is to be issued from the logic programmed by the user
instead of the logic shown in Figure 4.9-26, connect the “operate completed” signal
generated in the user-programmed logic to connection point#2 “User configurable
condition”. That is, set the scheme switch [TPOS01-LGP1EXOT] to PLC and use
“TPOS01IN_TMP_38”.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-17 for PLC#3 and Table 4.9-20 for the outputs.

Output signal to BO
The TPOS01 function, in Figure 4.9-41, can issue a signal “Operate P2-control” at output point
“TPOS01_P2EX_BO”, when the TPOS01 function determines that the “PLC-P2-Control” signal
is true.

(ix) Receiving “operate command P3-control” using the PLC function


Figure 4.9-42 outlines the reception of the operate command P3-control by the PLC function.

Wait for a command

Select logics Wait for a next command

P1 control from the remote-end P1 control from the remote-end

P2 control from the remote-end P2 control from the remote-end

P3 control from the remote end P3 control from the remote end

P1 control from the local-end P1 control from the local-end

P2 control from the local-end P2 control from the local-end

P3 control from the local-end P3 control from the local-end

P1 control by the PLC function P1 control by the PLC function

P2 control by the PLC function


P2 control by the PLC function Success
Operation
Signal generation by Operate logic Signal output
decision
the PLC function

Failed Do nothing

P3 control by the PLC function P3 control by the PLC function

Figure 4.9-42 Outline of operate command ‘P3-control’

Input signal required to connect


Figure 4.9-43 depicts the operate logic when an “Operate command P3 (PLC-P3-Control)”
signal is generated by the PLC function. There are two input points for reception of this
command signal, like the signal “Operate command P1 (PLC-P1-Control)”. That is, if an
interlock check is required, apply the signal at connection point (PLC#3:i.e.,
DEV01_P3_INTERLOCK). If, on the other hand, an interlock check is not required, apply the
signal at connection point (PLC#4:i.e., DEV01_P3_COMMAND). We shall assume the PLC#3
and PLC#4 as PLC#1 and PLC#2 in Table 4.9-4. Note that the user should set PLC for scheme

GRL200 (Soft 033 & 037)


- 946 -
6F2S1914 (0.37)

switch [TPOS01-LGP3EXOT].

Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

“TPOS01_P3EC_OK_CSF” “TPOS01_P3EC_OK_CS”
Command “PLC-P3-Control”requiring ILK check (PLC#3
connection point) (5513001 8004011E80) (513001 8404011E83)
[TPOS01-CPW]
Operate Cmd.
513001 800401EE37 DEV01_P3_INTERLOCK
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-P3-Control ”not requiring ILK check 0.1 – 50.0 s
(PLC#4 connection point)
513001 800401EE36 DEV01_P3_COMMAND Operation Cmd.
without ILK† condition

ILK† condition (“P3”) passed S


&
TPOS1-P3 R
User configurable condition
(PLC#4 connection point)

513001 840401EE58 TPOS01IN_TMP_29


[TPOS01-LGCTRCON] &
Fixedlogic To BO connection
“TPOS01_P3EX_BO”
Operate condition‡
(513001 8204011DD6) §§

[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”

“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)

513001 820401EE5E TPOS01IN_TMP_38 & “TPOS01_EX_FFL”


[TPOS01-RST] (513001 8604011E91) ‡‡
“TPOS01_P3EC_OK_CSF”
0 t
(513001 8004011E80)
&
1.0s- 100.0s Operation Failed

Figure 4.9-43 Operate ‘P3-control’ using the PLC function TPOS01††


†Note:The ILK function can provide the criteria for operation for “P3” control.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-18 for PLC#4, and Table 4.9-20 for the outputs.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.9-43 using connection point #4
“User configurable condition” That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and using “TPOS01IN_TMP_29”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S switch or an
ES is changed.
‡‡Note: The Operate failed” signal “is issued when a state-change remains undetected
following expiration of the setting applied to timer [TPOS01-RST].

GRL200 (Soft 033 & 037)


- 947 -
6F2S1914 (0.37)

§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. If the signal is to be issued from the programmed logic by
the user instead of the logic shown in Figure 4.9-26, connect the “operate
completed” signal generated in the user-programmed logic to connection point#2
“User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.

Output signal to BO
The TPOS01 function, in Figure 4.9-43, can issue a signal “Operate P3-control” at output point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the signal “PLC-P3-Control”
is true.

(x) Operate condition


In a manner similar to which the conditions have been examined for the select command, the
conditions for an operate command should be understood. Figure 4.9-44 illustrates the logic to
examine an operate condition. The operate condition is determined by signal
“TPOS01_STATE”. If the functionality of the original logic does not meet with user-
requirements, the following alternatives are provided:
1. The user can replace the original logic with alternative logic,
2. The user can add another signal to the original logic.

Replacing the original logic


If the user wishes to replace the operate condition logic completely, it can be achieved using
PLC connect point “User configurable operate condition”.
1. Connect the user-customized logic using “TPOS01IN_TMP_34”, listed as PLC#2 in
Table 4.9-19.
2. Set scheme switch [TPOS01-LGEXFFCT] to PLC.

Adding another operate condition signal


If the addition of another operate condition is required, the user can add the signal to operate
condition logic using PLC connection point “Additional condition”.
1. Add a user-preferred signal using “TPOS01IN_TMP_33”, listed as PLC#1 in Table
4.9-19.
2. Set scheme switch [TPOS01-LGEXFFCT] to Fixed logic.

GRL200 (Soft 033 & 037)


- 948 -
6F2S1914 (0.37)

TPOS01 function (Function ID: 513001)


Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Traveling OR Unmatched condition detected *5 Operate condition

Function “Automatic sequence control” is in progress Event suppression detected *6


= TPOS01_QLT_SPP
ASEQ_MULTI_SEL
(513001 8204011F59)
Tripping *4 (“General trip”)
BI board connection error detected*7
GEN. TRIP = TPOS01_QLT_BI_ERR
(513001 8604011F5A)
[SCDEN]*8
Same Directional
OFF Controlling Event
P1-control command received
(513001 8304011D02) &
TPOS01_ST_P1
P2-control command received
&
(513001 8104011D03)

TPOS01_ST_P2
“EDS” never permit to control
P3-control command received from “P1 to P3” and “P3 to P1”.
(513001 8504011D04) &
TPOS01_ST_P3

&

[TPOS01-DEVTYPE]*9
&
EDS

Additional condition (PLC connection point #1)


513001 800401EE65 TPOS01IN_TMP_33
[TPOS01-LGSLFFCT]
User configurable condition (PLC connection point#2)
Fixedlogic
513001 810401EE66 TPOS01IN_TMP_34 &

Users must setup this condition correctly


Control hierarchy (e.g. 43RL) (PLC connection point#3) *10
513001 820401ED50 TPOS01IN_TMP_21
TPOS01IN_TMP_41 &
IED serious error detected
SERI_ERR

[TPOS01-CTREN]

On

Figure 4.9-44 Operate condition logic for P1–3 control in TPOS01*11


*1Note: “Command Blocking” disables any operation except for itself; “Command
blocking” is implemented as “CBK” in a software switch controller (SOFTSW);.
The IEC 61850 defines “Command Blocking” as “CmdBlk”. For more information
of “CBK”, see Chapter Control and monitoring application: Software switch
control function. See the signal “CBK_STATE” in Table 4.9-6.
*2Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used
to protect the substation. The user can program it using GR-TIEMS.
*3Note: Detection of event “device-travelling signifies that other operators are
changing the status of one or more devices. Thus, device operation by the IED
should be inhibited whilst ever the event is detected. The detection signal is
denoted as “Traveling OR” in Table 4.9-6.
*4Note: If an IED is in the process of issuing a trip command, all control operation is
blocked until the trip operation has been completed. If the IED has a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table

GRL200 (Soft 033 & 037)


- 949 -
6F2S1914 (0.37)

4.9-6.
*5Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to “IED test status”.
*6Note: The Function “Event suppression” can detect chattering in BI circuits. (See
4.9.6(i)-3)
*7Note: A supervision of the Binary IO module can detect connection errors for BI
circuits.
*8Note: The “Common control” (CMNCTRL) function can test or check the operation
– direction of logic. When the user sets off for scheme switch [SCDEN], operation
of the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
*9Note: The user should set scheme switch [TPOS01-DEVTYPE] EDS when the earth-
switch(ES) is applied for the TPOS01 function.
*10Note: The user must program the PLC logic for “Control hierarchy condition” The
user must connect the “Control hierarchy” condition to the select condition logic
using the connection point TPOS01IN_TMP_21” for more information, see chapter
Control and monitoring application: Control hierarchy” see PLC#3 of Table 4.9-8.
*11Note: To identify the input points of the other TPOS, see Table 4.9-8 for PLC#1 to
#3. Note that the logic outputs are generated separately for P1, P2 and P3-
control.

(xi) Signal name and number


Note: The user should note the meaning of the following abbreviations as shown in
column “M/O” of each table:
“O” signifies that the signal is provided for the optional use.
“M” signifies that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings is used.
“N/A” signifies that the user cannot change the state of the signal.

Table 4.9-15 PLC connection points (Input signal PLC#1 user a configurable condition)
Signal Number Signal Name Description M/O
513001 800401EE56 TPOS01IN_TMP_27 TPOS01 operate condition configured by the user (for PLC#1) O
513001 800402EE56 TPOS02IN_TMP_27 TPOS02 operate condition configured by the user (for PLC#1) O
513001 800403EE56 TPOS03IN_TMP_27 TPOS03 operate condition configured by the user (for PLC#1) O
… … …
513001 800418EE56 TPOS24IN_TMP_27 TPOS24 operate condition configured by the user (for PLC#1) O

Table 4.9-16 PLC connection points (Input signal PLC#2 user configurable condition)
Signal Number Signal Name Description M/O
513001 820401EE5E TPOS01IN_TMP_38 TPOS01 operate condition configured by the user (for PLC#2) O

GRL200 (Soft 033 & 037)


- 950 -
6F2S1914 (0.37)

Signal Number Signal Name Description M/O


513001 820402EE5E TPOS02IN_TMP_38 TPOS02 operate condition configured by the user (for PLC#2) O
513001 820403EE5E TPOS03IN_TMP_38 TPOS03 operate condition configured by the user (for PLC#2) O
… … …
513001 820418EE5E TPOS24IN_TMP_38 TPOS24 operate condition configured by the user (for PLC#2) O

Table 4.9-17 PLC connection points (Input signal PLC#3 user configurable condition)
Signal Number Signal Name Description M/O
513001 810401EE57 TPOS01IN_TMP_28 TPOS01 operate condition configured by the user (for PLC#3) O
513001 810402EE57 TPOS02IN_TMP_28 TPOS02 operate condition configured by the user (for PLC#3) O
513001 810403EE57 TPOS03IN_TMP_28 TPOS03 operate condition configured by the user (for PLC#3) O
…. …. …
513001 810418EE57 TPOS24IN_TMP_28 TPOS24 operate condition configured by the user (for PLC#3) O

Table 4.9-18 PLC connection points (Input signal PLC#4 user configurable condition)
Signal Number Signal Name Description M/O
513001 840401EE58 TPOS01IN_TMP_29 TPOS01 operate condition configured by the user (for PLC#4) O
513001 840402EE58 TPOS02IN_TMP_29 TPOS02 operate condition configured by the user (for PLC#4) O
513001 840403EE58 TPOS03IN_TMP_29 TPOS03 operate condition configured by the user (for PLC#4) O
… … …
513001 840418EE58 TPOS24IN_TMP_29 TPOS24 operate condition configured by the user (for PLC#4) O

Table 4.9-19 PLC connection points (Input point additional, user configurable condition)
Signal Number Signal Name Description M/O
513001 800401EE65 TPOS01IN_TMP_33 Condition added by the user in TPOS01 (for PLC#1) O
513001 800402EE65 TPOS02IN_TMP_33 Condition added by the user in TPOS02 (for PLC#1) O
513001 800403EE65 TPOS03IN_TMP_33 Condition added by the user in TPOS03 (for PLC#1) O
… … …
513001 800418EE65 TPOS24IN_TMP_33 Condition added by the user in TPOS24 (for PLC#1) O
513001 810401EE66 TPOS01IN_TMP_34 Condition added by the user in TPOS01 (for PLC#2) O
513001 810402EE66 TPOS02IN_TMP_34 Condition added by the user in TPOS02 (for PLC#2) O
513001 810403EE66 TPOS03IN_TMP_34 Condition added by the user in TPOS03 (for PLC#2) O
… … …
513001 810418EE66 TPOS24IN_TMP_34 Condition added by the user in TPOS24 (for PLC#2) O

Table 4.9-20 PLC monitoring points (Output signal for BIO)


Signal Number Signal Name Description
513001 8104011DD0 TPOS01_P1EX_BO Operate command (P1) for Binary Output in TPOS01
513001 8104021DD0 TPOS02_P1EX_BO Operate command (P1) for Binary Output in TPOS02
513001 8104031DD0 TPOS03_P1EX_BO Operate command (P1) for Binary Output in TPOS03
… … …
513001 8104181DD0 TPOS24_P1EX_BO Operate command (P1) for Binary Output in TPOS24
513001 8204011DD3 TPOS01_P2EX_BO Operate command (P2) for Binary Output in TPOS01
513001 8204021DD3 TPOS02_P2EX_BO Operate command (P2) for Binary Output in TPOS02
513001 8204031DD3 TPOS03_P2EX_BO Operate command (P2) for Binary Output in TPOS03
…. …. ….
513001 8204181DD3 TPOS24_P2EX_BO Operate command (P2) for Binary Output in TPOS24
513001 8204011DD6 TPOS01_P3EX_BO Operate command (P3) for Binary Output in TPOS01
513001 8204021DD6 TPOS02_P3EX_BO Operate command (P3) for Binary Output in TPOS02
513001 8204031DD6 TPOS03_P3EX_BO Operate command (P3) for Binary Output in TPOS03

GRL200 (Soft 033 & 037)


- 951 -
6F2S1914 (0.37)

Signal Number Signal Name Description


… … …
513001 8204181DD6 TPOS24_P3EX_BO Operate command (P3) for Binary Output in TPOS24
513001 8004011E7E TPOS01_P1EC_OK_CSF TPOS01 P1 direction execute command
513001 8004021E7E TPOS02_P1EC_OK_CSF TPOS02 P1 direction execute command
513001 8004031E7E TPOS03_P1EC_OK_CSF TPOS03 P1 direction execute command
… … …
513001 8004181E7E TPOS24_P1EC_OK_CSF TPOS24 P1 direction execute command
513001 8004011E7F TPOS01_P2EC_OK_CSF TPOS01 P2 direction execute command
513001 8004021E7F TPOS02_P2EC_OK_CSF TPOS02 P2 direction execute command
513001 8004031E7F TPOS03_P2EC_OK_CSF TPOS03 P2 direction execute command
… … …
513001 8004181E7F TPOS24_P2EC_OK_CSF TPOS24 P2 direction execute command
513001 8004011E80 TPOS01_P3EC_OK_CSF TPOS01 P3 direction execute command
513001 8004021E80 TPOS02_P3EC_OK_CSF TPOS02 P3 direction execute command
513001 8004031E80 TPOS03_P3EC_OK_CSF TPOS03 P3 direction execute command
… … …
513001 8004181E80 TPOS24_P3EC_OK_CSF TPOS24 P3 direction execute command
513001 8004011E81 TPOS01_P1EC_OK_CS TPOS01 P1 direction execute command
513001 8004021E81 TPOS02_P1EC_OK_CS TPOS02 P1 direction execute command
513001 8004031E81 TPOS03_P1EC_OK_CS TPOS03 P1 direction execute command
… … …
513001 8004181E81 TPOS24_P1EC_OK_CS TPOS24 P1 direction execute command
513001 8304011E82 TPOS01_P2EC_OK_CS TPOS01 P2 direction execute command
513001 8304021E82 TPOS02_P2EC_OK_CS TPOS02 P2 direction execute command
513001 8304031E82 TPOS03_P2EC_OK_CS TPOS03 P2 direction execute command
… … …
513001 8304181E82 TPOS24_P2EC_OK_CS TPOS24 P2 direction execute command
513001 8404011E83 TPOS01_P3EC_OK_CS TPOS01 P3 direction execute command
513001 8404021E83 TPOS02_P3EC_OK_CS TPOS02 P3 direction execute command
513001 8404031E83 TPOS03_P3EC_OK_CS TPOS03 P3 direction execute command
… … …
513001 8404181E83 TPOS24_P3EC_OK_CS TPOS24 P3 direction execute command
513001 8004011E93 TPOS01_EX_CMP TPOS01 completed control
513001 8004021E93 TPOS02_EX_CMP TPOS02 completed control
513001 8004031E93 TPOS03_EX_CMP TPOS03 completed control
… … …
513001 8004181E93 TPOS24_EX_CMP TPOS24 completed control
513001 8604011E91 TPOS01_EX_FFL TPOS01 failed control
513001 8604021E91 TPOS02_EX_FFL TPOS02 failed control
513001 8604031E91 TPOS03_EX_FFL TPOS03 failed control
… … …
513001 8604181E91 TPOS24_EX_FFL TPOS24 failed control

(xii) Setting names


Note: The “xx” of “TPOSxx” represents the TPOS function number. (e.g., if the TPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented from
“01” to “24”.)
Table 4.9-21 Setting of Operate in TPOSxx
Setting Name Description Default Setting item or value
TPOSxx-PLSM Method of command output(TPOS01–24) Fix Fix/Var
TPOSxx-CPW Duration of command output(TPOS01–24) 1.0[sec] 0.1~50.0[sec]

GRL200 (Soft 033 & 037)


- 952 -
6F2S1914 (0.37)

Setting Name Description Default Setting item or value


TPOSxx-RST Detection time for terminating control (TPOS01–24) 30.0[sec] 0.1~100.0[sec]
TPOSxx-LGCTRCON Logic selector for operate condition (TPOS01–24) Fixedlogic Fixedlogic/PLC
TPOSxx-LGP1EXOT Logic selector for command output (TPOS01–24) Fixedlogic Fixedlogic/PLC
TPOSxx-LGP2EXOT Logic selector for command output (TPOS01–24) Fixedlogic Fixedlogic/PLC
TPOSxx-LGP3EXOT Logic selector for command output (TPOS01–24) Fixedlogic Fixedlogic/PLC
TPOSxx-LGEXFFCT Logic selector for operate condition (TPOS01–24) Fixedlogic Fixedlogic/PLC

GRL200 (Soft 033 & 037)


- 953 -
6F2S1914 (0.37)

4.9.4 Operation counter


The TPOS01 function has an operation-counter†; the user can utilize the operation counter to
predict the lifespan of an EDS. The user can select a count mode in response to a device signal.
Table 4.9-22 and Figure 4.9-45 show the mode, for which a user is required to change a mode
in response to a device signal and the signal of the device such as the EDS. For instance of the
P1-control in the TPOS01 function, a user can select the mode using scheme switch [TPOS01-
P1CNTS], which is set to C-On; counting-up is performed when a switch-gear signal gives rise
to a change in state from “Open to Closing”.

Table 4.9-22 Mode of operation counter


Mode Description
Counting-up is performed when a signal changes to closed (ON). When the signal
C-On
is changed from “Open to Closed”, the counter value is incremented.
Counting-up is performed when a signal changes to open (OFF). When the signal
C-Off
is changed from “Closed to Open”, the counter value is incremented.
Counting-up is made when any state change occurs: “Open to Closed” and
C-OnOff
“Closed to Open”.
NA Stop the count function
†Note:The operation-counter value is not cleared when power is removed from the IED.
This counter is available in the TPOS01 to TPOS03 functions.

Closed

Open

Figure 4.9-45 Device signal

The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation counter”, the user can set a user-
preferred value for the operation-counter. See Chapter User interface: Monitoring sub-menu
on how to operate the sub-menu.

Operation Counter TPOS1-CNT


10:48 1/3 10:48 1/4
_TPOS1-CNT > TPOS_Dev1-All +
TPOS2-CNT > CANCEL
0
TPOS3-CNT >
TPOS_Dev1-P1 +
0
ENTER TPOS_Dev1-P2 +

Figure 4.9-46 Operation counter sub-menu


Note: With regard to the signal “TPOS01_ST_P1”, the sub-menu represents it as
“TPOS_Dev1-P1”. Analogous to the signal “TPOS01_ST_P1”, the signals
“TPOS01_ST_P2” and “TPOS01_ST_P3” are represented as “TPOS_Dev1-P2” and

GRL200 (Soft 033 & 037)


- 954 -
6F2S1914 (0.37)

“TPOS_Dev1-P3”, respectively. The “TPOS_Dev1-All” represents the net counter


of “TPOS01_ST_P1”, “TPOS01_ST_P2” and “TPOS01_ST_P3”.

(i) Receiving “change value for counter” from the remote-end


Mapping of Input point required
Figure 4.9-47 depicts the logic when a “change value for counter” command is received at the
TPOS01 function. With regard to the net counter, the input-point “DEV01_ALLCNT_REQ” is
used. With regard to a P1-control counter, the input-point “DEV01_P1CNT_REQ” is used. For
P2-control and P3-control, the input-points “DEV01_P2CNT_REQ” and “DEV01_P3CNT_REQ”
are used.
Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)

“TPOS01_SLD_CSCN”
(513001 8A04011F8B)
Command “change value for counter”
513001_7004016D09 DEV01_ALLCNT_REQ Operate Command
&

Operate condition‡

Figure 4.9-47 Change counter value in net counter† by the remote-end in TPOS01
‡Note:The “operate condition” signal is provided from the operate condition logic shown
in Figure 4.9-49.
†Note: The user can apply the other counter change commands for P1-control, P2-control
and P3-control as shown in Table 4.9-24. The resultant signals for the other
TPOS02-24 logics are shown in Table 4.9-23.

Output signal to BO
The TPOS01 function can issue a “Result” signal at output point “TPOS01_SLD_CSCN”.

(ii) Receiving “change value for counter” from the local-end


Input signal from the front panel
Figure 4.9-48 depicts the logic when a “change value for counter” command is provided in the
TPOS01 function. The command is provided from the sub-menu (see Figure 4.9-46).
Input Operate logic in TPOS01 Output

TPOS01 function (Function ID: 513001)


“TPOS01_SLD_CSCN”
(513001 8A04011F8B)

Command “Change value”

Figure 4.9-48 Changing value by the operation of the front panel in TPOS01

GRL200 (Soft 033 & 037)


- 955 -
6F2S1914 (0.37)

Output signal to BO
The TPOS01 function can issue a “Result” signal at output point “TPOS01_SLD_CSCN”.

(iii) Operate condition for the counter


Figure 4.9-49 illustrates the operate condition logic. The TPOS01 function can determine an
operate-condition using a signal received from “Control hierarchy”. The Control hierarchy
condition is provided by user-programmed PLC logic; the user must connect the control-
hierarchy with the TPOS01 function using connection point “TPOS01IN_TMP_41” (see Table
4.9-25).

TPOS01 function (Function ID: 513001)


Command blocking*1 To counter logic
CBK_STATE
1≥ Operate condition
&
Double Command Blocking detected*2
DCB RCV OR

Other devices traveling detected*3


Traveling OR

Detection of serious errors


SERI_ERR

Unmatched condition detected *4

Control hierarchy (e.g. 43RL) (PLC connection point)


513001 800401ED5A TPOS01IN_TMP_41

Figure 4.9-49 Operate condition logic for changing the counter in TPOS01
*1Note: “Command Blocking” disables all operation except for its own; the
“Command blocking” function is initiated by the status of “CBK” in a software
switch controller (SOFTSW). The IEC 61850 standard defines the “Command
Blocking” function as “CmdBlk”. For more information on “CBK”, see Chapter
Control and monitoring application: Software switch control function. See the
signal “CBK_STATE” of Table 4.9-6.
*2Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used
to protect the substation. The user can program it using GR-TIEMS.
*3Note: If the event “device-travelling is detected, it indicates that another operator
is changing the status of a device. Thus, the IED should inhibit the operation of
any device for the duration that the event is detected. The detecting signal is
denoted as “Traveling OR” in Table 4.9-6.
*4Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to “IED test status”.

(iv) Signal names and number


Table 4.9-23 Results of changing counter
Signal Number Signal Name Description
513001 8A04011F8B TPOS01_SLD_CSCN TPOS01 counter selected
513001 8A04021F8B TPOS02_SLD_CSCN TPOS02 counter selected
513001 8A04031F8B TPOS03_SLD_CSCN TPOS03 counter selected

GRL200 (Soft 033 & 037)


- 956 -
6F2S1914 (0.37)

Signal Number Signal Name Description


… … …
513001 8A04181F8B TPOS24_SLD_CSCN TPOS24 counter selected
Table 4.9-24 Mapping points
Signal Number Signal Name Description
513001 7004016D09 DEV01_ALLCNT_REQ TPOS01 counter correction request for summation counter value
513001 7004026D09 DEV02_ALLCNT_REQ TPOS02 counter correction request for summation counter value
513001 7004036D09 DEV03_ALLCNT_REQ TPOS03 counter correction request for summation counter value
… … …
513001 7004186D09 DEV24_ALLCNT_REQ TPOS24 counter correction request for summation counter value
513001 7004016D0A DEV01_P1CNT_REQ TPOS01 counter correction request for P1 counter value
513001 7004026D0A DEV02_P1CNT_REQ TPOS02 counter correction request for P1 counter value
513001 7004036D0A DEV03_P1CNT_REQ TPOS03 counter correction request for P1 counter value
… … …
513001 7004186D0A DEV24_P1CNT_REQ TPOS24 counter correction request for P1 counter value
513001 7004016D0B DEV01_P2CNT_REQ TPOS01 counter correction request for P2 counter value
513001 7004026D0B DEV02_P2CNT_REQ TPOS02 counter correction request for P2 counter value
513001 7004036D0B DEV03_P2CNT_REQ TPOS03 counter correction request for P2 counter value
… … …
513001 7004186D0B DEV24_P2CNT_REQ TPOS24 counter correction request for P2 counter value
513001 7004016D0C DEV01_P3CNT_REQ TPOS01 counter correction request for P3 counter value
513001 7004026D0C DEV02_P3CNT_REQ TPOS02 counter correction request for P3 counter value
513001 7004036D0C DEV03_P3CNT_REQ TPOS03 counter correction request for P3 counter value
… … …
513001 7004186D0C DEV24_P3CNT_REQ TPOS24 counter correction request for P3 counter value

Table 4.9-25 PLC connection points for control hierarchy


Signal Number Signal Name Description M/O
513001 800401ED5A TPOS01IN_TMP_41 TPOS01 control hierarchy condition(PLC#1) for counters M
513001 800402ED5A TPOS02IN_TMP_41 TPOS02 control hierarchy condition(PLC#1) for counters M
513001 800403ED5A TPOS03IN_TMP_41 TPOS03 control hierarchy condition(PLC#1) for counters M
… … …
513001 800418ED5A TPOS24IN_TMP_41 TPOS24 control hierarchy condition(PLC#1) for counters M

(v) Setting name


Table 4.9-26 Setting for pulse counter in TPOSxx
Setting Name Description Default Setting item or value
TPOSxx-P1CNTS Mode selection of the counter in P1-control *user-preferred NA / C-On / C-Off / C-OnOff
TPOSxx-P2CNTS Mode selection of the counter in P2-control *user-preferred NA / C-On / C-Off / C-OnOff
TPOSxx-P3CNTS Mode selection of the counter in P3-control *user-preferred NA / C-On / C-Off / C-OnOff

GRL200 (Soft 033 & 037)


- 957 -
6F2S1914 (0.37)

4.9.5 Measurement of operation Intervals


The TPOS01 function can measure operation intervals time†, the intervals OT1 and OT2 can
represent the period of time when an earth-switch changes a position from another position.
As shown in Table 4.9-27 the eight intervals are defined as switching as shown in Figure 4.9-50
Intermediate

to Figure 4.9-53. The user should set scheme switch [TPOS01-OPETMEN] On.

Signal “TPOS01_P2EX_BO”
Intermediate

Sensing intermediate state


P1
P2
Signal “TPOS01_PT_P1”

P3
Signal “TPOS01_PT_P2”
P2-control

Signal “TPOS01_PT_P3”
OT1 OT2

a. Switch motion (P1 to P2) b. Operate command and signals with regard to the switch motion (P1 to P2)

Figure 4.9-50 Two Intervals (OT1 and OT2) for P2 control


Intermediate

Signal “TPOS01_P1EX_BO”
Intermediate

Sensing intermediate state


P1
P2
Signal “TPOS01_PT_P1”

P3
Signal “TPOS01_PT_P2”
P1-control

Signal “TPOS01_PT_P3”
OT3 OT4

a. Switch motion (P2 to P1) b. Operate command and signals with regard to the switch motion (P2 to P1)

Figure 4.9-51 Two Intervals (OT3 and OT4) for P1 control


Intermediate

Signal “TPOS01_P2EX_BO”
Intermediate

Sensing Intermediate state


P1
P2
Signal “TPOS01_PT_P1”

P3
Signal “TPOS01_PT_P2”
P2-control

Signal “TPOS01_PT_P3”
OT5 OT6

a. Switch motion (P3 to P2) b. Operate command and signals with regard to the switch motion (P3 to P2)

Figure 4.9-52 Two Intervals (OP5 and OP6) for P2 control

GRL200 (Soft 033 & 037)


- 958 -
Intermediate 6F2S1914 (0.37)

Signal “TPOS01_P3EX_BO”
Intermediate

Sensing intermediate state


P1
P2
Signal “TPOS01_PT_P1”

P3
Signal “TPOS01_PT_P2”
P3-control

Signal “TPOS01_PT_P3”
OT5 OT6

a. Switch motion (P2 to P3) b. Operate command and signals with regard to the switch motion (P2 to P3)

Figure 4.9-53 Two intervals (OP7 and OP8) for P3 control

Table 4.9-27 Eight intervals measured in TPOS01 function


Intervals Trigger Events for measurement
Start Signal “TPOS01_P2EX_BO” sensed
OT1
End Signal “TPOS01_PT_P1” unsensed
Start Signal “TPOS01_PT_P1” sensed
OT2
End Signal “TPOS01_PT_P2” unsensed
Start Signal “TPOS01_P1EX_BO” sensed
OT3
End Signal “TPOS01_PT_P2” unsensed
Start Signal “TPOS01_PT_P2” is sensed
OT4
End Signal “TPOS01_PT_P1” unsensed
Start Signal “TPOS01_P2EX_BO” sensed
OT5
End Signal “TPOS01_PT_P3” unsensed
Start Signal “TPOS01_PT_P3” sensed
OT6
End Signal “TPOS01_PT_P2” unsensed
Start Signal “TPOS01_P3EX_BO” sensed
OT7
End Signal “TPOS01_PT_P2” unsensed
Start Signal “TPOS01_PT_P2” sensed
OT8
End Signal “TPOS01_PT_P3” unsensed
†Note:The function “operation time measurement” is also available in the TPOS02 and
TPOS03 functions.

The user can clear the operation-intervals (OT1 to OT8) by key-operation of the
“Operation time” sub-menu or operation from the remote-end. Figure 4.9-54 shows that the
user can clear the eight operation times using this screen. See chapter User interface:
Monitoring sub-menu for the operation.

GRL200 (Soft 033 & 037)


- 959 -
6F2S1914 (0.37)

Operation Time TPOS1-OT


10:48 1/26 10:48 1/5
_TPOS1-OT > TPOS_Dev1- OT1
TPOS2-OT > CANCEL ******.*** ms
TPOS3-OT > TPOS_Dev1- OT2
TPOS4-OT >
******.*** ms
TPOS5-OT > ENTER TPOS_Dev1- OT3
TPOS6-OT >

Figure 4.9-54 Operation time sub-menu

(i) Signal names and numbers


Table 4.9-28 Mapping point for clearance of operation times
Signal Number Signal Name Description
513001 7004016D0D DEV01_RESET_REQ TPOS01 operation time reset command (Mapping Data)
513001 7004026D0D DEV02_RESET_REQ TPOS02 operation time reset command (Mapping Data)
513001 7004036D0D DEV03_RESET_REQ TPOS03 operation time reset command (Mapping Data)
… … …
513001 7004186D0D DEV24_RESET_REQ TPOS24 operation time reset command (Mapping Data)

(ii) Setting names


Table 4.9-29 Setting of operation time function in TPOSxx
Setting Name Description Default Setting item or value
TPOSxx-OPETMEN Activation of the operation time measurement in TPOSxx On Off / On

GRL200 (Soft 033 & 037)


- 960 -
6F2S1914 (0.37)

4.9.6 Setup for BIO module


The user should connect the TPOS input /output points with the BI and the BO circuits;
subsequently, the TPOS function is able to issue select and operate commands. The user should
execute the following four steps.
i BI connection for status signals
ii BO connection for “select command”
iii BO connection for “operate command”
iv Contact health check

Note that the TPOS01 function commences operation when the scheme switch [TPOS01-EN]
is set to On.

(i) BI connection for status signals


Figure 4.9-55 exemplifies the reception of signals at the TPOS01 function; to acquire the status
signal§, the user should set input-point for the settings [TPOS01-P1NOPSG], [TPOS01-
P2NOPSG], and [TPOS01-P3NOPSG].
†Note:Normally the input-signals (P1, P2, P3) are generated using normally-open
contacts (NOs). If the P1 signal is generated by the normal-closed contact (NC),
the user should set scheme switch [TPOS01- P1NOPSGI] to On in order that the
P1 input-signal is inverted.
§Note: The state signal acquired can be monitored. For more information, see Chapter
Automatic supervision.

Connection with Binary input circuits


For example, as shown in Figure 4.9-1, suppose three kinds of signals (P1, P2, or P3) are
provided on the first (BI1), second (BI2), and third BI (BI3) circuits at IO#1 slot. In this case,
the user should set three input-points (200B01–8001001110, 8101011110, and 8201021110†)
for the settings [TPOS01-P1NOPSG], [TPOS01-P2NOPSG], and [TPOS01-P3NOPSG].
Signals by Binary input circuits Signal acquisition logic in TPOS01 Output ‡

“TPOS01_STATE”
Event suppression detector (513001_3104011001)
BI1, BI2, and BI3 signals desig
nated by settings
[TPOS01-P1NOPSG], & 1≥
[TPOS01-P2NOPSG],
and [TPOS01-P3NOPSG] S
Status before chattering

R “TPOS01_ QLT_SPP”
(513001_8204011F59)

[TPOS01-SPPEN] Chattering detector

On
& To select and operate
condition logics

Figure 4.9-55 BI1, BI2 and BI3 signals provided into TPOS01
†Note:The user should set the actual input- points, see Chapter Technical description:
Binary IO module.
‡Note:In Figure 4.9-55 two signals can be issued: “TPOS01_STATE” and

GRL200 (Soft 033 & 037)


- 961 -
6F2S1914 (0.37)

“TPOS01_QLT_SPP”. The former one is used in the select condition logic and the
operate condition (see Figure 4.9-20 and Figure 4.9-44). The latter is used for an
event suppression detector.

Decision by input signals


The logic in Figure 4.9-55 can give a decision in response to the reception of the signals; the
decision is of either “P1”, “P2”, “P3”, “Faulty”, and “Intermediate”. Table 4.9-30 exemplifies the
decisions in response to the BI1 - BI3 input signals; the decision can be acquired at the
monitoring point “TPOS01_STATE”.

Suppose, the BI1–BI3 circuits receive “On–Off–Off” signals when an earth-switch is


located at “P1” (see Figure 4.9-1); the value “1” is given, because the decision can be made with
the “On–Off–Off” signals.

If “On–On–Off” signals are applied to the BI1–BI3 circuits, the decision cannot be made
because the earth switch is still kinetic and is not standstill; thus, the decision is given as
“Intermediate”, the value “3” is given at the connection point ”TPOS01_STATE”.

If “On–On–On” signals are applied to the BI1–BI3 circuits, the decision cannot be made
because the earth-switch may be broken; hence, the value “7” is given.
Table 4.9-30 Decision made by the TPOS01 function
Input signals at IO#1 (200B01) Generated value
Decision by
BI1 BI2 BI3 “TPOS01_STATE”
TPOS01
(8001001110) (8101011110) (8201021110) (513001 3104011001)
Off (0) Off (0) Off (0) Intermediate 0
On (1) Off (0) Off (0) P1 1
Off (0) On (1) Off (0) P2 2
On (1) On (1) Off (0) Intermediate 3
Off (0) Off (0) On (1) P3 4
On (1) Off (0) On (1) Intermediate 5
Off (0) On (1) On (1) Intermediate 6
On (1) On (1) On (1) Faulty 7
Note: When handling the raw information other than the decision, the user can take
respective states of binary input circuits using other monitoring points. That is,
the user can take either state On (1) or state Off (0) corresponding to the BI1
circuit using the monitoring point “TOPS01_PT_P1”. Likewise, the BI2 and BI3
states can be taken using the monitoring points “TOPS01_PT_P2” and
“TOPS01_PT_P3”. (See Table 4.9-35)

GRL200 (Soft 033 & 037)


- 962 -
6F2S1914 (0.37)

Event suppression detector


If the status of a device “chatters” for a short time, the TPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the TPOS function;
hence, event suppression can be required to reduce the additional burden created.

[TPOS-NELD]

Signal 2 4 6 8
from device On On On On On On On
1 3 5 7

Suppressed
On On On On
signal

[TPOS-TELD] [TPOS-TELR]
Time................. A B C D E

Figure 4.9-56 Iterative signals and signals suppressed

Figure 4.9-56 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time A, the setting [TPOS-NELD] is provided so
that the suppression commences at Time B. The setting [TPOS-TELD] is pertains to the
operation of the detection function from Time A (e.g., Time A to Time C).

The event suppression ceases when the iterative signal stops. The user can adjust the
point at which event suppression stops using the setting [TPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time D to E).

To initiate event suppression the user should set On for scheme switch [TPOS01-SPPEN].

(ii) BO connection for “select commands”


Figure 4.9-57 exemplifies the connections for operate commands P1/P2/P3. Suppose that
connection with the BOs is achieved by the PLC function using connection points
“TPOS01_P1SL_BO_FLG” to “TPOS01_P3SL_BO_FLG”; as a result, either of the signals
“Operate command P1 to P3” is issued at one of the BOs.

GRL200 (Soft 033 & 037)


- 963 -
6F2S1914 (0.37)

Terminal and
Selection logic in TPOS01 BO1 circuit at IO#1 (Function ID: 200B01) wire

“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
Selection logic for select “BO1” Select
Signal captured by command
command P1 in TPOS01 setting [Input signal 1] ≥1 (200B01_8002001112)
P1
[Input signal 2] DRIVER BO1
To contact health & ≥1
check [Input signal 3]
“BO1-RB”
[Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
Selection logic for select check
command P2 in TPOS01 [Input signal 7]
[Input signal 8]

PLC connection point on BO1

200B01 310200E11D BO1_SOURCE

Terminal and
Selection logic for select BO2 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P2SL_BO_FLG”
command P3 in TPOS01
(513001 8A04011DC6)
“BO2” Select
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8102011112)
P2
[Input signal 2] DRIVER BO2
& ≥1
To contact health
[Input signal 3]
check “BO2-RB”
[Input signal 4] [BO2_CPL] On &
(200B01_8102011113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]

PLC connection point on BO2

200B01 310201E11D BO2_SOURCE

Terminal and
BO3 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
“BO3” Select
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8202021112)
P3
[Input signal 2] DRIVER BO3
& ≥1
To contact health
[Input signal 3]
check “BO3-RB”
[Input signal 4] [BO3_CPL] On &
(200B01_8102021113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]

PLC connection point on BO3

200B01 310202E11D BO3_SOURCE

Figure 4.9-57 Example select connected with BO1-BO3

(iii) BO connection for “operate command”


Figure 4.9-58 exemplifies the connections for operate commands P1/P2/P3; the BO4–BO6
circuits issue the operate command.

GRL200 (Soft 033 & 037)


- 964 -
6F2S1914 (0.37)

Terminal and
Operate logic in TPOS01 BO4–BO6 circuit at IO#1 (Function ID: 200B01) wire

“TPOS01_P1EX_BO”
(513001_8104011DD0)
“BO4”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8302031112)
command
P1-control P1
[Input signal 2] DRIVER BO4
in TPOS01 & ≥1
[Input signal 3]
“BO4-RB”
[Input signal 4] [BO4_CPL] On &
Connected by (200B01_8302031113)
Off
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO4


“TPOS01_P2EX_BO” 200B01 310203E11D BO4_SOURCE
(513001_8204011DD3)
“BO5”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8402041112) command
P2-control P2
[Input signal 2] DRIVER BO5
in TPOS01 & ≥1
[Input signal 3]
“BO5-RB”
[Input signal 4] [BO5_CPL] On &
Connected by (200B01_8402041113)
Off
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO5


“TPOS01_P3EX_BO” 200B01 310204E11D BO5_SOURCE
(513001_8204011DD6)
“BO6”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8502051112) command
P3-control P3
[Input signal 2] DRIVER BO6
in TPOS01 & ≥1
[Input signal 3]
“BO6-RB”
[Input signal 4] [BO6_CPL] On &
Connected by (200B01_8502051113)
Off
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]

PLC connection point in BO6

200B01 310205E11D BO6_SOURCE

Figure 4.9-58 Example of operate commands connected with BO4-BO2


†Note:Table 4.9-20 shows the remaining signals except for “TPOS01”.

(iv) Contact health check


The TPOS01 function has contact health check feature for the BO circuits; hence, the user is
able to connect an output signal to the contact health check function when Fixedlogic is set for
scheme switches [TPOS01- LGP1EXOT] to [TPOS01-LGP3EXOT]†. Consequently, the TPOS01
function can determine whether the signal has been successfully output from the BO. If a
failure is reported, the TPOS01 function determines that the signal is not output successfully
to the BO; then the command is canceled immediately and the TPOS01 function returns to the
“Wait for a command” stage.

†Note:Table 4.9-21 shows settings for the health check feature in the other TPOS
functions.

Setting for “select command P1/P2/P3”


For example, the point”TPOS01_P1SL_BO” is connected to the BO1 circuit for the issuing of

GRL200 (Soft 033 & 037)


- 965 -
6F2S1914 (0.37)

the command, the user can connect point “BO1-RB “ with the contact health check function
using the setting [TPOS01-P1SLBORD]. Do not key the point “TPOS01_P1SL_BO”. Likewise,
BO2-RB and BO3-RB are required to be set.
Contact health check
Selection logic in TPOS01 logic in TPOS01
“TPOS01_P1SL_BO” (513001 8A04011DC4)

BO1 circuit at & Result of contact health check of


IO_SLOT1 P1-select in TPOS01
“BO1-RB”
(200B01_8002001113) Signal connected by
setting [TPOS01-P1SLBORD]

Connection made by the user


“TPOS01_P2SL_BO” (513001 8A04011DC6)

BO2 circuit at & Result of contact health check of


IO_SLOT1 P2-select in TPOS01
“BO2-RB”
(200B01_8102011113) Signal connected by
setting [TPOS01-P2SLBORD]

Connection made by the user

“TPOS01_P3SL_BO” (513001 8A04011DC8)

BO3 circuit at & Result of contact health check of


IO_SLOT1 P3-select in TPOS01
“BO3-RB”
(200B01_8202021113) Signal connected by
setting [TPOS01-P3SLBORD]

Connection made by the user

Figure 4.9-59 Example contact health check feature for P1–P3 select commands

Setting for “Operate command P1/P2/P3”


Similarly, the points “BO4-RB” and “BO6-RB” are required to be set for the settings [TPOS01-
P1EXBORD] to [TPOS01-P3EXBORD].

Selection logic in TPOS01

Contact health check logic in TPOS01


“TPOS01_P1EX_BO” (513001 8104011DD0)

BO4 circuit at & Result of contact health check of


IO_SLOT1 P1-operate in TPOS01

“BO4-RB” Signal connected by


(200B01_8302031113) setting [TPOS01-P1EXBORD]

Connection made by the user

“TPOS01_P2EX_BO” (513001 8204011DD3)

BO5 circuit at & Result of contact health check of


IO_SLOT1 P2-operate in TPOS01

“BO5-RB” Signal connected by


(200B01_8402041113) setting [TPOS01-P2EXBORD]

Connection made by the user

“TPOS01_P3EX_BO” (513001 8204011DD6)

BO6 circuit at & Result of contact health check of


IO_SLOT1 P3-operate in TPOS01

“BO6-RB” Signal connected by


(200B01_8502051113) setting [TPOS01-P3EXBORD]

Connection made by the user

Figure 4.9-60 Contact health check logic for P1–P3 operate commands

GRL200 (Soft 033 & 037)


- 966 -
6F2S1914 (0.37)

Proper setting for the contact health check (normal setting, example #1)
Figure 4.9-61 shows a setting example for 43S/EDS driving. Select and operate commands
drive the BO1–BO6 contacts. To check that the contact health check function is working
correctly, the respective points of the BO (RBs) should be connected, as shown in Table 4.9-31,
to demonstrate that the settings are physically matched with the BO contacts.

Table 4.9-31 Setting example for contact health check


Example #1 Health check settings for example #1

“TPOS01_P1SL_BO_FLG” is connected to “BO1” at IO#1 200B01 8002001113(BO1-RB) set for [TPOS01-P1SLBORD] OK

“TPOS01_P2SL_BO_FLG” is connected to “BO2” at IO#1 200B01 8102011113(BO2-RB) set for [TPOS01-P2SLBORD] OK

“TPOS01_P3SL_BO_FLG” is connected to “BO3” at IO#1 200B01 8202021113(BO3-RB) set for [TPOS01-P3SLBORD] OK

“TPOS01_P1EX_BO” is connected to “BO4” at IO#1 200B01 8302031113(BO4-RB) set for [TPOS01-P1EXBORD] OK

“TPOS01_P2EX_BO” is connected to “BO5” at IO#1 200B01 8402041113(BO5-RB) set for [TPOS01-P2EXBORD] OK

“TPOS01_P3EX_BO” is connected to “BO6” at IO#1 200B01 8502051113(BO6-RB) set for [TPOS01-P3EXBORD] OK

GRL200 (Soft 033 & 037)


- 967 -
6F2S1914 (0.37)

Remote/Local-end BIO module


“TPOS01_P1SL_BO_FLG” Drivers
(513001 8A04011DC4)

P1-select BO1
command “BO1-RB”
(200B01 8002001113)
“TPOS01_P1EX_BO”
(513001 8104011DD0)

P1-operate BO4
command “BO4-RB”
(200B01 8302031113)

“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)

P2-select BO2
command “BO2-RB”
(200B01 8102011113)
“TPOS01_P2EX_BO”
(513001 8204011DD3)

P2-operate BO5
command “BO5-RB”
(200B01 8402041113)

“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)

P3-select BO3
command “BO3-RB”
(200B01 8202021113)
“TPOS01_P3EX_BO” EDS
(513001 8204031DD3) Plus (+)

P3-operate BO6
command “BO6-RB” P1-Selection P2-Selection P3-Selection
(200B01 8502051113)

P1-Operate P2-Operate P3-Operate

Minus (−)

Figure 4.9-61 Contact health check setting and EDS scheme for example #1

Setting for erroneous in contact health check (improper setting, example #2)
Figure 4.9-62 shows a setting example for an improper setting of the 43S/EDS scheme. The
settings are implemented incorrectly as shown in Table 4.9-32, BO1-RB is not chosen, instead
BO1 is actually chosen, which is incorrect. In this case, the setting [TPOS01-SLBORD] is
meaningless; hence, the issue of a select command is blocked.

GRL200 (Soft 033 & 037)


- 968 -
6F2S1914 (0.37)

Table 4.9-32 Erroneous setting example for contact health check


Example #2 Health check setting for example #2

“TPOS01_P1SL_BO_FLG” is connected to “BO1” on SLOT1 200B01 8002001112 (BO1) set for [TPOS01-P1SLBORD] NG

“TPOS01_P2SL_BO_FLG” is connected to “BO2” on SLOT1 200B01 8102011113(BO2-RB) set for [TPOS01-P2SLBORD] OK

“TPOS01_P3SL_BO_FLG” is connected to “BO3” on SLOT1 200B01 8202021113(BO3-RB) set for [TPOS01-P3SLBORD] OK

“TPOS01_P1EX_BO” is connected to “BO4” on SLOT1 200B01 8302031113(BO4-RB) set for [TPOS01-P1EXBORD] OK

“TPOS01_P2EX_BO” is connected to “BO5” on SLOT1 200B01 8402041113(BO5-RB) set for [TPOS01-P2EXBORD] OK

“TPOS01_P3EX_BO” is connected to “BO6” on SLOT1 200B01 8502051113(BO6-RB) set for [TPOS01-P3EXBORD] OK


Remote/Local-end “BO1” (not BO1-RB)
BIO module
“TPOS01_P1SL_BO_FLG” mistakenly chosen with
(513001 8A04011DC4) 200B01 8002001112 Drivers

P1-select BO1
command

“TPOS01_P1EX_BO”
(513001 8104011DD0)

P1-operate BO4
command “BO4-RB”
(200B01 8302031113)

“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)

P2-select BO2
command “BO2-RB”
(200B01 8102011113)
“TPOS01_P2EX_BO”
(513001 8204011DD3)

P2-operate BO5
command “BO5-RB”
(200B01 8402041113)

“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)

P3-select BO3
command “BO3-RB”
(200B01 8202021113)
“TPOS01_P3EX_BO” EDS
(513001 8204031DD3) Plus (+)

P3-operate BO6
command “BO6-RB” P1-Selection P2-Selection P3-Selection
(200B01 8502051113)

P1-Operate P2-Operate P3-Operate

Minus (−)

Figure 4.9-62 Contact health check setting and EDS diagram for example #2

Setting for extra contact health check (special setting, example #3)
Figure 4.9-63 shows an additional setting example for the EDS scheme; one of the settings is
made hypothetically. That is, the point “SPO01_P1*SL_BO_FLG” is actually chosen for the
setting [TPOS01-P1*SLBORD]; i.e. BO1-RB is not chosen for this selection. This special

GRL200 (Soft 033 & 037)


- 969 -
6F2S1914 (0.37)

example can issue a select command; which is called “operated by internal select function”.
The user does not need to consider the use of a BO circuit for a select command, when there
are no BO circuits available.
Table 4.9-33 Extra setting example for contact health check
Example #3 Setting for example #3

“TPOS01_P1SL_BO_FLG” is not connected to any BO “TPOS01_P1SL_BO_FLG” set for [TPOS01-P1SLBORD] OK

“TPOS01_P2SL_BO_FLG” is not connected to any BO “TPOS01_P2SL_BO_FLG” set for [TPOS01-P2SLBORD] OK

“TPOS01_P3SL_BO_FLG” is not connected to any BO “TPOS01_P3SL_BO_FLG” set for [TPOS01-P3SLBORD] OK

“TPOS01_P1EX_BO” is connected to “BO4” on SLOT1 200B01 8302031113(BO4-RB) set for [TPOS01-P1EXBORD] OK

“TPOS01_P2EX_BO” is connected to “BO5” on SLOT1 200B01 8402041113(BO5-RB) set for [TPOS01-P2EXBORD] OK

“TPOS01_P3EX_BO” is connected to “BO6” on SLOT1 200B01 8502051113(BO6-RB) set for [TPOS01-P3EXBORD] OK

Remote/Local end
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
P1-select
command
“TPOS01_P2SL_BO_FLG” BOs are not connected but virtualized.
(513001 8A04011DC6)

P2-select
command “TPOS01_P3SL_BO_FLG”
EDS
(513001 8A04011DC8)

P3-select
command
Plus (+)

SAS/Local IED
BIO module P1-Operate P2-Operate P3-Operate
“TPOS01_P1EX_BO”
(513001 8104011DD0) Drivers

P1-operate BO4
command “BO4-RB”
(200B01 8302031113) Minus (−)

“TPOS01_P2EX_BO”
(513001 8204011DD3)

P2-operate BO5
command “BO5-RB”
(200B01 8402041113)

“TPOS01_P3EX_BO”
(513001 8204031DD3

P3-operate BO6
command “BO6-RB”
(200B01 8502051113)

Figure 4.9-63 Contact health check setting and EDS diagram for example #3

(v) Signal name and number


Table 4.9-34 PLC monitoring points (Output signal for event suppression function in TPOSxx)
Signal Number Signal Name Description
513001 8204011F59 TPOS01_QLT_SPP Event suppression detected (TPOS01)

GRL200 (Soft 033 & 037)


- 970 -
6F2S1914 (0.37)

Signal Number Signal Name Description


513001 8204021F59 TPOS02_QLT_SPP Event suppression detected (TPOS02)
513001 8204031F59 TPOS03_QLT_SPP Event suppression detected (TPOS03)
… … …
513001 8204181F59 TPOS24_QLT_SPP Event suppression detected (TPOS24)

Table 4.9-35 PLC monitoring points (P1–P3 state signals in TPOSxx)


Signal Number Signal Name Description
513001 8304011D02 TPOS01_ST_P1 TPOS01 P1 On(0/1)
513001 8104011D03 TPOS01_ST_P2 TPOS01 P2 On(0/1)
513001 8504011D04 TPOS01_ST_P3 TPOS01 P3 On(0/1)
513001 8304021D02 TPOS02_ST_P1 TPOS02 P1 On(0/1)
513001 8104021D03 TPOS02_ST_P2 TPOS02 P2 On(0/1)
513001 8504021D04 TPOS02_ST_P3 TPOS02 P3 On(0/1)
513001 8104031D03 TPOS03_ST_P2 TPOS03 P2 On(0/1)
513001 8304031D02 TPOS03_ST_P1 TPOS03 P1 On(0/1)
513001 8504031D04 TPOS03_ST_P3 TPOS03 P3 On(0/1)
… … …
513001 8304181D02 TPOS24_ST_P1 TPOS24 P1 On(0/1)
513001 8104181D03 TPOS24_ST_P2 TPOS24 P2 On(0/1)
513001 8504181D04 TPOS24_ST_P3 TPOS24 P3 On(0/1)

(vi) Setting names


Note: The “xx” of “TPOSxx” represents the TPOS function number. (e.g., if the TPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented from
“01” to “24”.)
Table 4.9-36 Setting for Binary input signals in TPOSxx
Setting Name Description Default Setting item or value
TPOSxx-EN Activate monitoring function of TPOS01-24 On Off / On
TPOSxx-DEVTYPE Equipment type selector. switch switch/EDS
TPOSxxP1-NOPSG BI position for TPOS01-24 *none BI signal
TPOSxxP2-NOPSG BI position for TPOS01-24 *none BI signal
TPOSxxP3-NOPSG BI position for TPOS01-24 *none BI signal
TPOSxx-SPPEN Activate event suppression for TPOS01-24 On Off / On
TPOS-NELD Number of change to lock status. 10 0~99
TPOS-TELD Time to locking state( sliding window ) 10[sec] 1~99[sec]
TPOS-TELR Time to unlocking state( sliding window ) 10[sec] 1~99[sec]

Table 4.9-37 Settings for health check function in TPOSxx


Setting Name Description Default Setting item or value
TPOSxx-P1SLBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P2SLBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P3SLBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P1EXBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P2EXBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P3EXBORD Select BO signal (BO*-RB) from signal list *none BO readback signal

GRL200 (Soft 033 & 037)


- 971 -
6F2S1914 (0.37)

4.9.7 Mapping for IEC61850 commination


The user can operate the TPOS function over IEC 61850 communications† following mapping
using GR-TIEMS. Note that the TPOS function is designed for the class of “Integer Status
Controller (ISC)” in the IEC 61850 standard for communication. The user should follow these
steps, each of which is discussed below:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user will need to create a logical node (LN) for the TPOS01 function. Figure 4.9-64
exemplifies the editing of a LN; the LN “Integer Status Controllable Status Output (ISCSO)”
is chosen for the TPOS01 function. After the user defined an object “ISCSO”, the TPOS01
logical node can be available with the name “GGIO” plus “LN Instance”. Create a definition of
the object “ISCSO” in the TPOS01 logical node. Either the SBO mode or the DIR mode can be
chosen in the editing of the LN.

SBO defined in LN

Figure 4.9-64 Defining “ISCSO” object in GGIO2701 logic node

Defining SBO mode


Figure 4.9-65 exemplifies the TPOS01 logic node saved as “GGIO2701”. For the SBO mode, the
user should select the following items for the “GGIO2701$ISCSO” using GR-TIEMS:

GRL200 (Soft 033 & 037)


- 972 -
6F2S1914 (0.37)

 SBOw
 Oper
 Cancel
 origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.

Figure 4.9-65 LN editing screen for SBO (for example)

Defining DIR mode


Figure 4.9-66 exemplifies the TPOS logic node saved as “GGIO2701”. In the DIR mode, the
following three items should be selected using GR-TIEMS:

 Oper
 origin
 ctlmodel (choice ”DOes or DOns” )

Figure 4.9-66 LN editing screen for DIR mode (for example)

(ii) Mapping output data


The user should group the TPOS01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS. Figure 4.9-43 illustrates
how to map a signal; it indicates that the signals for the TPOS01 function are required to map
for IEC 61850 communication.

GRL200 (Soft 033 & 037)


- 973 -
6F2S1914 (0.37)

Table 4.9-38 Mapping signals for ISCSO object


Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO2701$ISCSO$origin orCat orCategory ST 513001 3104011008 TPOS01_ORCAT
Ctrl/GGIO2701$ISCSO$origin orIdent Octet64 ST 513001 6A04011009 TPOS01_ORIDENT
Ctrl/GGIO2701$ISCSO stVal INT32 ST 513001 3104011001 TPOS01_STATE
Ctrl/GGIO2701$ISCSO q Quality ST 513001 3104011005 TPOS01_QUALITY
Ctrl/GGIO2701$ISCSO t Timestamp ST 513001 9004011006 TPOS01_TIMESTAMP
Ctrl/GGIO2701$ISCSO stSeld BOOLEAN ST 513001 0004011D90 TPOS01_SLD_RPT

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.

Drag and drop

Figure 4.9-67 ocCat attribute mapped for ISCSO object of GGIO2701

(iii) Mapping input data


The TPOS01 function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “DEV01_CONTROL_REQ” to the IEC61850 communication. Table
4.9-39 shows the input-point “DEV01_CONTROL_REQ” and the Object reference
“Ctrl/GGIO2701$ISCSO”; the user should map the input-point to the Object references having
attributes CO and CF†. Figure 4.9-68 shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).

GRL200 (Soft 033 & 037)


- 974 -
6F2S1914 (0.37)

Table 4.9-39 Mapping signals required for ISCSO object for GIGO2701
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO2701$ISCSO$SBOw ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$SBOw T Timestamp CO
Ctrl/GGIO2701$ISCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO2701$ISCSO$SBOw Check Check CO
Ctrl/GGIO2701$ISCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO$Oper ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$Oper ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$Oper T Timestamp CO
Ctrl/GGIO2701$ISCSO$Oper Test BOOLEAN CO
5130017 004016D08 DEV01_CONTROL_REQ
Ctrl/GGIO2701$ISCSO$Oper Check Check CO
Ctrl/GGIO2701$ISCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO$Cancel ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$Cancel T Timestamp CO
Ctrl/GGIO2701$ISCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO2701$ISCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO ctlModel ctlModel CF
Ctrl/GGIO2701$ISCSO sboClass sboClass CF

Drag and drop

Check “Input”

Figure 4.9-68 Input-point mapped for GGIO2701

GRL200 (Soft 033 & 037)


- 975 -
6F2S1914 (0.37)

4.9.8 Setting
TPOS01(FunctionID:513001)
Setting items Range Unit Contents Default Note

Common TPOS-NELD 0 - 99 - Number of Event lock detect time 10


TPOS-TELD 1 - 99 s Timer of detect event lock 10
TPOS-TELR 1 - 99 s Timer of recovery from event lock 10
TPOS01-EN Off / On - TPOS01 switch for Device01 Off
Dev01 TPOS01-DEVNAME [Preferred text] - item name of TPOS_Dev1 TPOS_Dev1 !
TPOS01-000NAME [Preferred text] - state name of (0,0,0)state Travelling0 !
TPOS01-001NAME [Preferred text] - state name of (0,0,1)state P1 !
TPOS01-010NAME [Preferred text] - state name of (0,1,0)state P2 !
TPOS01-011NAME [Preferred text] - state name of (0,1,1)state Travelling1 !
TPOS01-100NAME [Preferred text] - state name of (1,0,0)state P3 !
TPOS01-101NAME [Preferred text] - state name of (1,0,1)state Travelling2 !
TPOS01-110NAME [Preferred text] - state name of (1,1,0)state Travelling3 !
TPOS01-111NAME [Preferred text] - state name of (1,1,1)state Travelling4 !
TPOS01-UDFNAME [Preferred text] - state name of undefined Undefine !
TPOS01-FLTNAME [Preferred text] - state name of faulty Faulty !
TPOS01-DEVTYPE switch / EDS - Device Type switch
TPOS01-P1NOPSG [Preferred signal] - P1 Normally Open Signal of Dev1 Not assigned
TPOS01-P1NOPSGI Off / On - Signal inverse or not Off
TPOS01-P2NOPSG [Preferred signal] - P2 Normally Open Signal of Dev1 Not assigned
TPOS01-P2NOPSGI Off / On - Signal inverse or not Off
TPOS01-P3NOPSG [Preferred signal] - P3 Normally Open Signal of Dev1 Not assigned
TPOS01-P3NOPSGI Off / On - Signal inverse or not Off
TPOS01-SPPEN Off / On - Automatic event suppression function Off
Off / On /
TPOS01-UDFEN - undefined pallet check function Off
CHKONLY
TPOS01-UDFTIM 0.1 - 100.0 s palette undefined check timer 30.0
Off / On /
TPOS01-FLTEN - faulty pallet check function Off
CHKONLY
TPOS01-FLTTIM 0.1 - 100.0 s palette faulty check timer 30.0
TPOS01-CTREN Off / On - control mode (control enable) Off
TPOS01-CTRMENU Off / On - control by MENU enable Off
TPOS01-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
select binary output read data(DataID)1 for no
TPOS01-NSLBORD1 [Preferred signal] - 5130018904011DC0
direction command
select binary output read data(DataID)2 for no
TPOS01-NSLBORD2 [Preferred signal] - 5130018904011DC0
direction command
select binary output read data(DataID)3 for no
TPOS01-NSLBORD3 [Preferred signal] - 5130018904011DC0
direction command
select binary output read data(DataID) for P1
TPOS01-P1SLBORD [Preferred signal] - 5130018A04011DC4
direction command
select binary output read data(DataID) for P2
TPOS01-P2SLBORD [Preferred signal] - 5130018A04011DC6
direction command
select binary output read data(DataID) for P3
TPOS01-P3SLBORD [Preferred signal] - 5130018A04011DC8
direction command
execute binary output read data(DataID) for
TPOS01-P1EXBORD [Preferred signal] - Not assigned
P1 direction command
execute binary output read data(DataID) for
TPOS01-P2EXBORD [Preferred signal] - Not assigned
P2 direction command
execute binary output read data(DataID) for
TPOS01-P3EXBORD [Preferred signal] - Not assigned
P3 direction command
FixedLogic /
TPOS01-LGCTRCON - Change logic about control condition FixedLogic
PLC

GRL200 (Soft 033 & 037)


- 976 -
6F2S1914 (0.37)

TPOS01(FunctionID:513001)
Setting items Range Unit Contents Default Note

FixedLogic /
TPOS01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
TPOS01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about P1 direction execute
TPOS01-LGP1EXOT - FixedLogic
PLC output
FixedLogic / Change logic about P2 direction execute
TPOS01-LGP2EXOT - FixedLogic
PLC output
FixedLogic / Change logic about P3 direction execute
TPOS01-LGP3EXOT - FixedLogic
PLC output
FixedLogic /
TPOS01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
TPOS01-PLSM Fix / Var - pulse mode Fix
TPOS01-CPW 0.1 - 50.0 s control pulse width 1.0
TPOS01-RST 1.0 - 100.0 s response check timer 30.0
TPOS01-CTRDIR P1 / P2 / P3 - Capable control direction P2
TPOS01-P1CNTS Off / On - P1 count status Off
TPOS01-P2CNTS Off / On - P2 count status Off
TPOS01-P3CNTS Off / On - P3 count status Off
TPOS01-OPETMEN Off / On - Operation Time Measurement enable Off
TPOS01-APBD Process / Bay - status change origin Process
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The TPOS function is available for a 2nd Device and other devices. We have
omitted the others because this will be the same as the 1st device with the
exception of the device number.

GRL200 (Soft 033 & 037)


- 977 -
6F2S1914 (0.37)

4.9.9 Signal
 Signal monitoring points in TPOS01
TPOS(FunctionID:513001)
Element ID Name Description
8004001FA3 TPOS00_CH_EC_LCD TPOS00 count change execute command by LCD
8004001D5E TPOS00_CH_EC_OWS TPOS00 count change execute command by OWS(HMI)
8004001D5F TPOS00_CH_EC_RCC TPOS00 count change execute command by RCC
8004001D60 TPOS00_CH_EC_RMT TPOS00 count change execute command by Remote
8004001FA2 TPOS00_CH_SC_LCD TPOS00 count change select command by LCD
8004001D5B TPOS00_CH_SC_OWS TPOS00 count change select command by OWS(HMI)
8004001D5C TPOS00_CH_SC_RCC TPOS00 count change select command by RCC
8004001D5D TPOS00_CH_SC_RMT TPOS00 count change select command by Remote
3204011D20 TPOS01_ALL_CNT_VAL TPOS01 all count value
0004011F7C TPOS01_AUTO_SIG TPOS01 Auto sequence signal
8304011E9C TPOS01_CCF_FCT_CS TEMP21
8704011E96 TPOS01_CC_FS TEMP19
8604011E95 TPOS01_CC_SS TEMP18
8804011E9B TPOS01_CC_ST_ERR TEMP39
0004011F7D TPOS01_CMNCTRL_SIG TPOS01 control receive signal
8604011F8D TPOS01_CNT_CS07 TPOS01 count change selected fail condition signal
0004011D91 TPOS01_CNT_SEL TPOS01 count change selected signal(stSeld) for SAS
0004011F7A TPOS01_CNT_SIG TPOS01 Count correction signal
8004011E9E TPOS01_CTR_SGC TPOS01 control logic stage(select command check)
8004011EA0 TPOS01_CTR_SGE TPOS01 control logic stage(execute command check)
8304011E9D TPOS01_CTR_SGN TPOS01 control logic stage(unselected)
8004011E9F TPOS01_CTR_SGS TPOS01 control logic stage(selected)
8B04011EA2 TPOS01_CTR_SGU TPOS01 control logic stage(under selection)
8904011FAB TPOS01_CTR_SGUCN TPOS01 count change selected signal
8904011FB1 TPOS01_CTR_SGURS TPOS01 reset time selected signal
8004011EA1 TPOS01_CTR_SGW TPOS01 control logic stage(wait for change)
8104011E9A TPOS01_ECF_FCT_EIS TPOS01 execute command fail factor signal except interlock/synchronism check
8004011D58 TPOS01_EC_LCD TPOS01 execute command by LCD
8004011D55 TPOS01_EC_OWS TPOS01 execute command by OWS(HMI)
8004011D59 TPOS01_EC_PLC TPOS01 execute command by PLC
8004011D56 TPOS01_EC_RCC TPOS01 execute command by RCC
8004011D57 TPOS01_EC_RMT TPOS01 execute command by Remote
8004011F55 TPOS01_EC_ST_ERR TPOS01 execute command mode err
0004011D97 TPOS01_EX_BO_OPOK TPOS01 execute binary output signal for SAS
8004011E93 TPOS01_EX_CMP TPOS01 execute complete signal
8F04011F58 TPOS01_EX_CMP_TMO TPOS01 timeout after execute completion
8904011FB0 TPOS01_EX_CMP_TMOCN TPOS01 count change timeout after execute completion
8904011FB6 TPOS01_EX_CMP_TMORS TPOS01 reset time timeout after execute completion
8904011F6F TPOS01_EX_CS01 TPOS01 response supervisory timer for P1
8A04011F70 TPOS01_EX_CS02 TPOS01 response supervisory timer for P2
8B04011F72 TPOS01_EX_CS03 TPOS01 P1 timer for under execution
8C04011F73 TPOS01_EX_CS04 TPOS01 P2 timer for under execution
8A04011F71 TPOS01_EX_CS05 TPOS01 response supervisory timer for P3
8C04011F74 TPOS01_EX_CS06 TPOS01 P3 timer for under execution
8604011E91 TPOS01_EX_FFL TPOS01 execute fail signal by fixedlogic
8504011E8F TPOS01_EX_SFL TPOS01 execute success signal by fixedlogic
8404011F43 TPOS01_FLT_DET1 TPOS01 Faulty Detected (3 phase concentration data only)
8104011F42 TPOS01_FLT_STA TPOS01 Faulty Start
8204011E8B TPOS01_F_CS TPOS01 execute command fail condition signal
3104011D01 TPOS01_LCD_ST TPOS01 state for LCD
3104011D00 TPOS01_MMC_ST TPOS01 state for MIMIC

GRL200 (Soft 033 & 037)


- 978 -
6F2S1914 (0.37)

 Signal monitoring points in TPOS01


TPOS(FunctionID:513001)
Element ID Name Description
8904011DC0 TPOS01_NSL_BO_FLG TPOS01 no direction select binary output signal
8604011F80 TPOS01_NSL_CS07 TPOS01 select receive signal check answer
3104011F93 TPOS01_OT1_SIGNAL TPOS01 operation time1 reset signal
3104011D30 TPOS01_OT1_VAL TPOS01 operation time1 value
3104011F95 TPOS01_OT2_SIGNAL TPOS01 operation time1 reset signal
3104011D33 TPOS01_OT2_VAL TPOS01 operation time2 value
3104011F97 TPOS01_OT3_SIGNAL TPOS01 operation time3 reset signal
3104011D36 TPOS01_OT3_VAL TPOS01 operation time3 value
3104011F99 TPOS01_OT4_SIGNAL TPOS01 operation time4 reset signal
3104011D39 TPOS01_OT4_VAL TPOS01 operation time4 value
3104011F9B TPOS01_OT5_SIGNAL TPOS01 operation time5 reset signal
3104011D3C TPOS01_OT5_VAL TPOS01 operation time5 value
3104011F9D TPOS01_OT6_SIGNAL TPOS01 operation time6 reset signal
3104011D40 TPOS01_OT6_VAL TPOS01 operation time6 value
3104011F9F TPOS01_OT7_SIGNAL TPOS01 operation time7 reset signal
3104011D43 TPOS01_OT7_VAL TPOS01 operation time7 value
3104011FA1 TPOS01_OT8_SIGNAL TPOS01 operation time8 reset signal
3104011D46 TPOS01_OT8_VAL TPOS01 operation time8 value
8104011E85 TPOS01_P1EC_F_CSF TPOS01 P1 direction execute command fail condition signal
8004011E81 TPOS01_P1EC_OK_CS TPOS01 P1 direction execute command OK condition signal
8004011E7E TPOS01_P1EC_OK_CSF TPOS01 P1 direction execute command OK condition signal
8104011DD0 TPOS01_P1EX_BO TPOS01 P1 direction execute binary output signal
8A04011DC4 TPOS01_P1SL_BO_FLG TPOS01 P1 direction select binary output signal
8A04011F83 TPOS01_P1SL_CS19 TPOS01 select receive P1 signal check answer
0004011FCB TPOS01_P1_CNT_SEL TPOS01 P1 count change selected signal(stSeld) for SAS
3204011D24 TPOS01_P1_CNT_VAL TPOS01 P1phase count value
8104011E86 TPOS01_P2EC_F_CSF TPOS01 P2 direction execute command fail condition signal
8304011E82 TPOS01_P2EC_OK_CS TPOS01 P2 direction execute command OK condition signal
8004011E7F TPOS01_P2EC_OK_CSF TPOS01 P2 direction execute command OK condition signal
8204011DD3 TPOS01_P2EX_BO TPOS01 P2 direction execute binary output signal
8A04011DC6 TPOS01_P2SL_BO_FLG TPOS01 P2 direction select binary output signal
8A04011F86 TPOS01_P2SL_CS19 TPOS01 select receive P2 signal check answer
0004011FCC TPOS01_P2_CNT_SEL TPOS01 P2 count change selected signal(stSeld) for SAS
3204011D28 TPOS01_P2_CNT_VAL TPOS01 P2phase count value
8104011E87 TPOS01_P3EC_F_CSF TPOS01 P3 direction execute command fail condition signal
8404011E83 TPOS01_P3EC_OK_CS TPOS01 P3 direction execute command OK condition signal
8004011E80 TPOS01_P3EC_OK_CSF TPOS01 P3 direction execute command OK condition signal
8204011DD6 TPOS01_P3EX_BO TPOS01 P3 direction execute binary output signal
8A04011DC8 TPOS01_P3SL_BO_FLG TPOS01 P3 direction select binary output signal
8A04011F89 TPOS01_P3SL_CS19 TPOS01 select receive P3 signal check answer
0004011FCD TPOS01_P3_CNT_SEL TPOS01 P3 count change selected signal(stSeld) for SAS
3204011D2C TPOS01_P3_CNT_VAL TPOS01 P3phase count value
8004011DE0 TPOS01_PLC_CTRL_FAIL TPOS01 PLC control fail
8604011F5A TPOS01_QLT_BI_ERR TEMP32
8204011F59 TPOS01_QLT_SPP TEMP31
8004011FA5 TPOS01_RE_EC_LCD TPOS01 reset time execute command by LCD
8004011D7B TPOS01_RE_EC_OWS TPOS01 reset time execute command by OWS(HMI)
8004011D7C TPOS01_RE_EC_RCC TPOS01 reset time execute command by RCC
8004011D7D TPOS01_RE_EC_RMT TPOS01 reset time execute command by Remote
8004011FA4 TPOS01_RE_SC_LCD TPOS01 reset time select command by LCD
8004011D78 TPOS01_RE_SC_OWS TPOS01 reset time select command by OWS(HMI)
8004011D79 TPOS01_RE_SC_RCC TPOS01 reset time select command by RCC
8004011D7A TPOS01_RE_SC_RMT TPOS01 reset time select command by Remote

GRL200 (Soft 033 & 037)


- 979 -
6F2S1914 (0.37)

 Signal monitoring points in TPOS01


TPOS(FunctionID:513001)
Element ID Name Description
8604011F91 TPOS01_RST_CS07 TPOS01 reset time selected fail condition signal
0004011F7B TPOS01_RST_SIG TPOS01 Reset time signal
8004011D54 TPOS01_SC_LCD TPOS01 select command by LCD
8004011D51 TPOS01_SC_OWS TPOS01 select command by OWS(HMI)
8004011D52 TPOS01_SC_RCC TPOS01 select command by RCC
8004011D53 TPOS01_SC_RMT TPOS01 select command by Remote
8004011F54 TPOS01_SC_ST_ERR TPOS01 select command mode err
0004011F79 TPOS01_SEL_SIG TPOS01 Selected signal
8504011F8C TPOS01_SE_RCV_RMTCN TPOS01 count change selected fail condition signal check
8504011F90 TPOS01_SE_RCV_RMTRS TPOS01 reset time selected fail condition signal check
8004011E76 TPOS01_SLD_CS TPOS01 selected condition signal
8004011F66 TPOS01_SLD_CS04 TPOS01 selected condition signal 04
8104011F67 TPOS01_SLD_CS05 TPOS01 selected condition signal 05
8204011F68 TPOS01_SLD_CS06 TPOS01 selected condition signal 06
8304011F69 TPOS01_SLD_CS08 TPOS01 selected condition signal 07
8A04011F8B TPOS01_SLD_CSCN TPOS01 count change selected condition signal
8A04011F8F TPOS01_SLD_CSRS TPOS01 reset time selected condition signal
0004011D90 TPOS01_SLD_RPT TPOS01 selected signal(stSeld) for SAS
8E04011F57 TPOS01_SLD_TMO TPOS01 time out after selected
8A04011FAF TPOS01_SLD_TMOCN TPOS01 count change time out after selected
8A04011FB5 TPOS01_SLD_TMORS TPOS01 reset time out after selected
8104011E7B TPOS01_SLF_CS TPOS01 select fail condition signal
8704011E98 TPOS01_SLF_FCT_EIS TPOS01 select fail factor signal except interlock/synchronism check
8804011FAD TPOS01_SLF_FCT_F03CN TPOS01 count change select fail factor signal by fixedlogic 03
8804011FB3 TPOS01_SLF_FCT_F03RS TPOS01 reset time select fail factor signal by fixedlogic 03
8704011FAE TPOS01_SLF_FCT_F04CN TPOS01 count change select fail factor signal by fixedlogic 04
8704011FB4 TPOS01_SLF_FCT_F04RS TPOS01 reset time select fail factor signal by fixedlogic 04
8304011FAC TPOS01_SLF_FCT_F07CN TPOS01 count change selected timer for a check
8304011FB2 TPOS01_SLF_FCT_F07RS TPOS01 reset time selected timer for a check
8604011F62 TPOS01_SLF_FCT_FLG03 TPOS01 select fail factor signal by fixedlogic 03
8704011F63 TPOS01_SLF_FCT_FLG04 TPOS01 select fail factor signal by fixedlogic 04
8804011F6E TPOS01_SLF_FCT_FLG07 TPOS01 selected timer for a check
8004011E7D TPOS01_SLR_CS TPOS01 select release condition signal
3104011001 TPOS01_STATE TPOS01 all_state
8304011D02 TPOS01_ST_P1 TEMP36
8104011D03 TPOS01_ST_P2 TEMP37
8504011D04 TPOS01_ST_P3 TEMP38
0004011D95 TPOS01_TMP_02 TPOS01 time reset selected signal(stSeld) for SAS
3104011D80 TPOS01_TMP_06 TPOS01 control event data (selected)
3104011D81 TPOS01_TMP_07 TPOS01 control event data (select fail)
3104011D82 TPOS01_TMP_08 TPOS01 control event data (select release)
3104011D83 TPOS01_TMP_09 TPOS01 control event data (execute output on)
3104011D84 TPOS01_TMP_10 TPOS01 control event data (execute command ng)
3104011D86 TPOS01_TMP_11 TPOS01 control event data (execute fail)
8204011F7E TPOS01_TMP_63 TPOS01 select bo signal check
8004011F7F TPOS01_TMP_64 TPOS01 select receive signal check
8104011F81 TPOS01_TMP_66 TPOS01 select bo P1 signal check
8504011F82 TPOS01_TMP_67 TPOS01 select receive P1 signal check
8104011F84 TPOS01_TMP_69 TPOS01 select bo P2 signal check
8504011F85 TPOS01_TMP_70 TPOS01 select receive P2 signal check
8104011F87 TPOS01_TMP_72 TPOS01 select bo P3 signal check
8504011F88 TPOS01_TMP_73 TPOS01 select receive P3 signal check
8004011F8A TPOS01_TMP_74 TPOS01 count change selected condition signal check

GRL200 (Soft 033 & 037)


- 980 -
6F2S1914 (0.37)

 Signal monitoring points in TPOS01


TPOS(FunctionID:513001)
Element ID Name Description
8004011F8E TPOS01_TMP_75 TPOS01 reset time selected condition signal check
0004011F77 TPOS01_TRA TPOS01 travelling info
0004011F78 TPOS01_TRA_CTR TPOS01 travelling info for control
3104011D49 TPOS01_TRST_S TPOS01 operation time reset signal
8204011F41 TPOS01_UDF_DET1 TPOS01 Undefined Detected (3 phase concentration data only)
8004011F40 TPOS01_UDF_STA TPOS01 Undefined Start

 Connection point in PLC logic


TPOS(Function ID: 513001)
Element ID Name Description
800401EE30 DEV01_P1_COMMAND dev01 P1 command
800401EE31 DEV01_P1_INTERLOCK dev01 P1 command with interlock bypass
800401EE32 DEV01_P2_COMMAND dev01 P2 command
800401EE33 DEV01_P2_INTERLOCK dev01 P2 command with interlock bypass
800401EE36 DEV01_P3_COMMAND dev01 P3 command
800401EE37 DEV01_P3_INTERLOCK dev01 P3 command with interlock bypass
820401ED50 TPOS01IN_TMP_21 TPOS01IN_TMP_21
800401EE53 TPOS01IN_TMP_22 TPOS01IN_TMP_22
810401EE54 TPOS01IN_TMP_23 TPOS01IN_TMP_23
800401EE61 TPOS01IN_TMP_24 TPOS01IN_TMP_24
810401EE62 TPOS01IN_TMP_25 TPOS01IN_TMP_25
800401EE55 TPOS01IN_TMP_26 TPOS01IN_TMP_26
800401EE56 TPOS01IN_TMP_27 TPOS01IN_TMP_27
810401EE57 TPOS01IN_TMP_28 TPOS01IN_TMP_28
840401EE58 TPOS01IN_TMP_29 TPOS01IN_TMP_29
820401EE5A TPOS01IN_TMP_30 TPOS01IN_TMP_30
830401EE5B TPOS01IN_TMP_31 TPOS01IN_TMP_31
850401EE5C TPOS01IN_TMP_32 TPOS01IN_TMP_32
800401EE65 TPOS01IN_TMP_33 TPOS01IN_TMP_33
810401EE66 TPOS01IN_TMP_34 TPOS01IN_TMP_34
800401EDDA TPOS01IN_TMP_35 TPOS01IN_TMP_35
810401EDDB TPOS01IN_TMP_36 TPOS01IN_TMP_36
840401EDDC TPOS01IN_TMP_37 TPOS01IN_TMP_37
820401EE5E TPOS01IN_TMP_38 TPOS01IN_TMP_38
830401EE5F TPOS01IN_TMP_39 TPOS01IN_TMP_39
800401EE69 TPOS01IN_TMP_40 TPOS01IN_TMP_40
800401ED5A TPOS01IN_TMP_41 TPOS01IN_TMP_41
800401ED77 TPOS01IN_TMP_42 TPOS01IN_TMP_42

 Mapping points in TPOS01


TPOS(FunctionID:513001)
Element ID Name Description
7004016D08 DEV01_CONTROL_REQ DPOS01 control command received. (Mapping Data)

Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the TPOS function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.

GRL200 (Soft 033 & 037)


- 981 -
6F2S1914 (0.37)

Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “TPOS01_SC_OWS” point for
the 2nd device, use the description of “TPOS01_SC_OWS” in place of
“TPOS02_SC_OWS”. The user can obtain the ID value of
“TPOS02_SC_OWS” by using the following steps:
Step 1 Find the element ID for TPOS01_SC_OWS (i.e.,
“8001011D51”)
Step 2 identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8001021D51” of
“TPOS02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.

GRL200 (Soft 033 & 037)


- 982 -
6F2S1914 (0.37)

Event detection function for general BIs (GENBI)


The general BI event detection (GENBI) function examines the signals generated on the binary
input circuits (BIs); the GENBI function verifies the signals generated in terms of time, state,
and quality. Accordingly, the GENBI function can elevate the value of the BI signals that are
generated using external devices; the GENBI function can provide the IED functions with a
variety of information. Figure 4.10-1 shows the block diagram of the GENBI function; it shows
signals from external devices received at the BI circuits. The operation of the GENBI function
is available for all BI circuits. For simplicity, hereafter, the setting and operation of the GENBI
function is discussed for binary input circuit #1 (BI1) at IO#1 slot in the IED.
IED
Output Output from BI1
signal of BI1 Acquisition
Time at state State data
Binary Output changed (current value)
input signal of BI2 Direction information Time data
circuit#1 at state changed. (time stamp)
Quality information
Suppression when (accumulated)
Binary input
appearance of
circuit#2
States on external devices

repetitive signals Output from BI2


Output
signal of BIn Process #1
Binary input Process #2
circuit #n† Output from BIn†

BIO module Process #n†


(Slot #1) GENBI for slot #1
Respective
output signals
BIO module Output from BI1 to BIn†
(Slot #2) GENBI for slot #2

Respective
BIO module output signals
Output from BI1 to BIn†
(Slot #n‡) GENBI for slot #n‡

Figure 4.10-1 Block diagram of GENBI

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the “G&T position” whilst referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 4.10-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


983
6F2S1914 (0.37)

4.10.1 Operation features


The operation process of the GENBI function is divided into an acquisition part and a
suppression part.

(i) Signal acquisition process


The acquisition process checks for the occurrence of state changes in each BI circuit. If a state
change is detected, the acquisition process determines the direction of the state change and
observes the time that the state change occurred.

The user needs to apply a signal as a setting so that signal acquisition will be carried out.
Figure 4.10-1 outlines the settings when BI1 circuits at IO#1 are considered. For example,
when a signal is received at BI1, the GENBI function can acquire the signal when the user has
set 200B001 8001001110† for the setting [SLOT1 GB01-SG]. After acquisition, the GENBI
function generates “SLOT1 GBI01_STATE (580001 0010001001)” signal in Boolean form; it
consists of “time stamp information” and “quality information”.

IED
Binary IO module (BIO) Function
IO_SLOT#1 0010001001
SLOT1 GBI01_STATE
[SLOT1 GBI01-SG]
800100111 8001001110† 8001001172
0010011001
BI1 [SLOT1 GBI02-SG SLOT1 GBI02_STATE
BI1-NC Filter BI1 CPL BI1-CPL

Binary input circuit#1


00101F1001
SLOT1 GBI32_STATE
[SLOT1 GBI32-SG] ‡
Binary input circuit#2

Binary input circuit #32

IO#1 (Function ID: 200B001) GEN_BI (Function ID: 580001) Func

Func

Figure 4.10-2 Setting method with Data ID at BI1 at IO#1


†Note:The BI1 (200B001 8001001110) is used purely by way of explanation; the user can
select either BI1-NC, BI1, or BI1-CPL so that the GENBI function acquire the
received signal. For more information of the signal acquisition points and the
meaning of the BI logic, see chapter Technical description: Binary IO module.

(ii) Event suppression process


When the signal switches between the “On” and “Off” state frequently over a short period of
time, the GENBI function will receive these repetitive signals. When these repetitive signals
are converted into event information, repetitive events are issued on occurrence of the
repetitive signals. The event suppression function is provided to suppress event appearance

GRL200 (Soft 033 & 037)


- 984 -
6F2S1914 (0.37)

when the GENBI function determines that the signal is being generated repetitively.

Signal
from
On On On On On On On On
device
Event No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

[GBI-TELD] [GBI-TELR]

Event suppression

Time................. A B C D E

Figure 4.10-3 Example of signals and events suppressed by setting

Figure 4.10-3 illustrates the case where a device produces repetitive signals. From this
figure, it can be seen that the start of event suppression occurs at the tenth state-change (point
B) because the GENBI function counts the number of state-changes. The GENBI function
detects the commencement of the signal repeated from the signal initiation point ‘A’. Scheme
switch [GBI-NELD] is provided to set the number of state-changes so that this function will
start to suppress the signal from this point. The user can set [GBI-TELD] pertaining to the
detection period of the repetitive signals (point A to point C). For example, the user can set the
value “10” for the scheme switch [GBI-NELD]; period A–C is set for the setting [GBI-TELD].

The GENBI function should remove event suppressed operation when the repetitive
signals disappear, (that is, the operation of the device is steady); event suppression operation
is cleared when no repetitive signal is found for a set period. The user can set the period using
scheme switch [GBI-TELR]; this reset operation clears the event suppression function at point
E when the last state change is confirmed at point D. Here, the period D–E is set for the Scheme
switch [GBI-TELR].

The event suppression function is provided for every device; the user should set On for
the scheme switch [SLOT1 GBI01-SPPEN], for example.

Table 4.10-2 Example of event list screened


Event Event contents screened
Off No.1 event
On No.2 event
Off No.3 event
On No.4 event
Off No.5 event
On No.6 event
Off No.7 event
On No.8 event
Off No.9 event
On No.10 event suppression SET
On Event suppression RESET

GRL200 (Soft 033 & 037)


- 985 -
6F2S1914 (0.37)

Table 4.10-2 shows the event list screen. This event list is in response to the signals shown
in Figure 4.10-3. Table 4.10-3 lists the common settings for event suppression. Table 4.10-4
shows the settings for a particular slot.

Table 4.10-3 Common settings for event suppression


Scheme switch Set Comment
GBI-NELD 0 – 99 sec Number of Event lock detect time
GBI-TELD 1 – 99 sec Timer of detect event lock
GBI-TELR 1 – 99 sec Timer of recovery from event lock

Table 4.10-4 Sets for event suppression in each slot


Scheme switch Set Comment
SLOT1 GBI01-SPPEN Off / On SLOT#1 BI-1 Automatic event suppression function
SLOT1 GBI02-SPPEN Off / On SLOT#1 BI-2 Automatic event suppression function
. . .
. . .
. . .
SLOT1 GBI32-SPPEN Off / On SLOT#1 BI-32 Automatic event suppression function
SLOT2 GBI01-SPPEN Off / On SLOT#2 BI-1 Automatic event suppression function
SLOT2 GBI02-SPPEN Off / On SLOT#2 BI-2 Automatic event suppression function
. . .
. . .
. . .
SLOT2 GBI32-SPPEN Off / On SLOT#2 BI-32 Automatic event suppression function
. . .
. . .
. . .
SLOTnGBI01-SPPEN Off / On SLOT#n BI-1 Automatic event suppression function‡
SLOTnGBI02-SPPEN Off / On SLOT#n BI-2 Automatic event suppression function‡
. . .
. . .
. . .
SLOTnGBI32-SPPEN Off / On SLOT#n BI-32 Automatic event suppression function‡
†Note:The specification and the number of binary input circuits depend upon the model
of BIO module. One of the BIO modules can provide 32 input circuits; thus, the
total number (n) for the process and the circuit is represented up to 32.
‡Note:The number of slots and the structure of the binary input circuits is influenced by
the IED model and the size of the case. For example, when a 1/1 case size is
available, eight slots are furnished within the IED. When the 1/3 case size is used,
two slots are provided in the IED. Hence, the user should distinguish these
configurations in accordance with the number of slots and the type of BIO
modules. (For further information, see Chapter Technical description: Binary IO
module)

GRL200 (Soft 033 & 037)


- 986 -
6F2S1914 (0.37)

4.10.2 Mapping for IEC61850 communication


Sending a report to the client is possible after the mapping is performed for IEC 61850
communication using GR-TIEMS. The user should proceed as follows,

Step1: Editing Logical Node


Step2: Mapping output data

(i) Editing Logical Node


The user must make a logical node (LN) for the GENBI function. Figure 4.10-4 exemplifies LN
making; LN “GGIO101” is selected for the GENBI function. After editing, the GENBI logical
node can be saved with the name “GGIO101”. Object “Ind1” is defined in the GENBI function.

Figure 4.10-4 Defining “Ind1” object in GGIO101 logic node

(ii) Mapping output data


With the IEC 61850 communications standard a GOOSE message can be used to send a signal
to a client. The user will need to collect the signals corresponding to the GENBI function and
then map them for IEC 61850 communication using GR-TIEMS.

Table 4.10-5 shows the mapping signals that are required within the GENBI function for
IEC 61850 communications. Figure 4.10-5 shows how to map a signal.

Table 4.10-5 Mapping signals for Ind1 object in GENBI function


Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO101$Ind1 stVal BOOLEAN ST 580001 0010001001 SLOT1 GBI01_STATE
Ctrl/GGIO101$Ind1 q Quality ST 580001 3110001005 SLOT1 GBI01_QUALITY
Ctrl/GGIO101$Ind1 t Timestamp ST 580001 9010001006 SLOT1 GBI01_TIMESTAM

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.

GRL200 (Soft 033 & 037)


- 987 -
6F2S1914 (0.37)

Drag and drop

Figure 4.10-5 Quality signal being mapped into Ind1 object of GGIO101

GRL200 (Soft 033 & 037)


- 988 -
6F2S1914 (0.37)

4.10.3 Setting
General BI (Function ID: 580001)
Setting items Range Unit Contents Default Note

GBI-NELD 0 - 99 - Number of Event lock detect time 10


GBI-TELD 1 - 99 s Timer of detect event lock 10
GBI-TELR 1 - 99 s Timer of recovery from event lock 10
IO#1 BI#1 SLOT1 GBI01-BIEVT Off / On - Switch to detect an event on BI circuit01 at Slot1 Off
SLOT1 GBI01-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#2 SLOT1 GBI02-BIEVT Off / On - Switch to detect an event on BI circuit02 at Slot1 Off
SLOT1 GBI02-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#3 SLOT1 GBI03-BIEVT Off / On - Switch to detect an event on BI circuit03 at Slot1 Off
SLOT1 GBI03-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
…. …. …. ….
BI#31 SLOT1 GBI31-BIEVT Off / On - Switch to detect an event on BI circuit31 at Slot1 Off
SLOT1 GBI31-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#32 SLOT1 GBI32-BIEVT Off / On - Switch to detect an event on BI circuit32 at Slot1 Off
SLOT1 GBI32-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
IO#2 BI#1 SLOT2 GBI01-BIEVT Off / On - Switch to detect an event on BI circuit01 at SLOT2 Off
SLOT2 GBI01-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#2 SLOT2 GBI02-BIEVT Off / On - Switch to detect an event on BI circuit02 at SLOT2 Off
SLOT2 GBI02-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#3 SLOT2 GBI03-BIEVT Off / On - Switch to detect an event on BI circuit03 at SLOT2 Off
SLOT2 GBI03-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
…. …. …. ….
BI#31 SLOT2 GBI31-BIEVT Off / On - Switch to detect an event on BI circuit31 at SLOT2 Off
SLOT2 GBI31-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#32 SLOT2 GBI32-BIEVT Off / On - Switch to detect an event on BI circuit32 at SLOT2 Off
SLOT2 GBI32-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
IO#3 BI#1 SLOT3 GBI01-BIEVT Off / On - Switch to detect an event on BI circuit01 at SLOT3 Off
SLOT3 GBI01-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#2 SLOT3 GBI02-BIEVT Off / On - Switch to detect an event on BI circuit02 at SLOT3 Off
SLOT3 GBI02-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#3 SLOT3 GBI03-BIEVT Off / On - Switch to detect an event on BI circuit03 at SLOT3 Off
SLOT3 GBI03-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
…. …. …. ….
BI#31 SLOT3 GBI31-BIEVT Off / On - Switch to detect an event on BI circuit31 at SLOT3 Off
SLOT3 GBI31-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#32 SLOT3 GBI32-BIEVT Off / On - Switch to detect an event on BI circuit32 at SLOT3 Off
SLOT3 GBI32-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
…. …. …. ….
IO#8 BI#1 SLOT8 GBI01-BIEVT Off / On - Switch to detect an event on BI circuit01 at SLOT8 Off
SLOT8 GBI01-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#2 SLOT8 GBI02-BIEVT Off / On - Switch to detect an event on BI circuit02 at SLOT8 Off
SLOT8 GBI02-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#3 SLOT8 GBI03-BIEVT Off / On - Switch to detect an event on BI circuit03 at SLOT8 Off
SLOT8 GBI03-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
…. …. …. ….
BI#31 SLOT8 GBI31-BIEVT Off / On - Switch to detect an event on BI circuit31 at SLOT8 Off
SLOT8 GBI31-SPPEN Off / On - Switch to suppress events by itself at BI circuit On
BI#32 SLOT8 GBI32-BIEVT Off / On - Switch to detect an event on BI circuit32 at SLOT8 Off
SLOT8 GBI32-SPPEN Off / On - Switch to suppress events by itself at BI circuit On

GRL200 (Soft 033 & 037)


- 989 -
6F2S1914 (0.37)

4.10.4 Signals
 Signal monitoring points in BI module at IO#1 slot
GENBI (Function ID: 580001)
Element ID Name Description
0010001001 SLOT1 GBI01_STATE Status of binary input circuit BI1 at IO#1 slot

0010011001 SLOT1 GBI02_STATE Status of binary input circuit BI2 at IO#1 slot

0010021001 SLOT1 GBI03_STATE Status of binary input circuit BI3 at IO#1 slot

…. …. ….
00101F1001 SLOT1 GBI32_STATE Status of binary input circuit BI32 at IO#1 slot

 Mapping points in BI module at IO#1 slot


GENBI (Function ID: 580001)
Element ID Name Description
3110001005 SLOT1 GBI01_QUALITY SLOT1 GBI01 quality

3110011005 SLOT1 GBI02_QUALITY SLOT1 GBI02 quality

3110021005 SLOT1 GBI03_QUALITY SLOT1 GBI03 quality

… … …

31101F1005 SLOT1 GBI32_QUALITY SLOT1 GBI32 quality

0010001001 SLOT1 GBI01_STATE SLOT1 GBI01 state

0010011001 SLOT1 GBI02_STATE SLOT1 GBI02 state

0010021001 SLOT1 GBI03_STATE SLOT1 GBI03 state

… … ….

00101F1001 SLOT1 GBI32_STATE SLOT1 GBI32 state

9010001006 SLOT1 GBI01_TIMESTAM SLOT1 GBI01 timestamp

9010011006 SLOT1 GBI02_TIMESTAM SLOT1 GBI02 timestamp

9010021006 SLOT1 GBI03_TIMESTAM SLOT1 GBI03 timestamp

…. …. ….

90101F1006 SLOT1 GBI32_TIMESTAM SLOT1 GBI32 timestamp

Note: In the table above, the user will only find Element IDs and their names for the 1st
slot, but a 2nd and other slots are also provided in the GENBI function. We have
omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.

Rule: The same types of signal monitoring points are provided in every circuit;
hence, the user can find the same ones for all of the other circuits. For
example, when the user wishes to find the “SLOT2 GBI02_STATE” point
for the 2nd circuit, use the description of SLOT1 GBI01_STATE in place of
“SLOT2 GBI02_STATE”. The user can obtain the ID value of “SLOT2
GBI02_STATE” by using the following steps:
Step 1 Find the element ID for SLOT1 GBI01_STATE (i.e.,
“0010001001”)
Step 2 Identify the number at the fifth and sixth digits from the

GRL200 (Soft 033 & 037)


- 990 -
6F2S1914 (0.37)

ID. (i.e., “0”)


Step 3 Choose a new circuit number. (i.e., pick the number “1” for
the 2nd circuit)
Step 4 Replace the number that occurs at the fifth and sixth
digits with the new device number. (i.e., get new ID
“0010111001” of “SLOT2 GBI02_STATE”) The ID is
expressed in hexadecimal notation. Thus, the user must
change the device number from decimal notation to
hexadecimal notation.

GRL200 (Soft 033 & 037)


- 991 -
6F2S1914 (0.37)

Automatic sequence control function (ASEQ)


The function of the automatic sequence controller (ASEQ) is to control the PLC function that
is used within the automatic sequence control function, which can be coded by the user. This
control logic has software signals; the status of these software signals are changed by control
commands that are sent from upstream devices. One of the upstream devices is a SAS server.
Another is the front panel of the IED, which means that the user can operate the device locally
using the ASEQ function. The ASEQ function is divided into a couple parts, these are referred
to as “ASEQ01 etc.” functions (i.e., ASEQ01, ASEQ02 and others). Therefore, some PLC
functions are controlled by the ASEQ functions at the same time. For simplicity, only the
ASEQ01 function is discussed here, the features in the other ASEQ02 etc. functions are
identical to the ASEQ01 function.

─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number for the “G&T position” referring to the
comparison table below. For more information, see Appendix: Ordering.
Table 4.11-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features NA ✓
– Number of functions – 15
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 992 -
6F2S1914 (0.37)

4.11.1 Function setup


Figure 4.11-1 outlines the command reception in the ASEQ01 function. The ASEQ01 function
can generate a start command at the PLC monitoring point “ASEQ01_EXEC_START” (see
Table 4.11-5), when the start command is provided for the ‘ASEQ01_CONTROL_REQ’.
Similarly, when a stop command is received in the ASEQ01 function, the stop command will
be generated at the PLC monitoring point “ASEQ01_EXEC_STOP” (see Table 4.11-6) †.
†Note: Create “IN1” and “IN2”points in the user programming logic; make the connection
between the ASEQ01 function and the user programing logic. Refer to chapter
PLC function. The user-programming logic is also required to have output points.
For example, if the user wishes to control a CB using the logic, the logic should
have two output points for two binary output circuits (BOs). Figure 4.11-1 shows
how two BOs are used for CB closing and CB opening.
‡Note: The ASEQ01 function does not have the responsibility to restart the programmed
logic after an emergency stop signal has been applied. Therefore, the user should
program the logic to generate an operation result signal in case of the emergency
stop signal being applied in the logic. See section 4.11.5 for the emergency
operation.
‡Note: PLC connection point “ASEQ01_EXEC_RESET” is provided for stopping the
ASEQ01 operation, as shown in Table 4.11-4.

IED

ASEQ01 User programming logic for


CB control
logic
In Out In Out
Binary Output Device
ASEQ01_ Circuit4
523001 700D016D08 ASEQ01_CONTROL_REQ EXEC_START OUT1

Remote operation Xxxxxx 8xxxxxxxxx IN1 Driver Close


523001 820D10ED50 EMERSTOP_CONTROL_REQ

ASEQ01_
OUT2 Binary Output
EXEC_STOP circuit4
IED front panel
operation Xxxxxx 8xxxxxxxxx IN2
“Reply Signal” Driver
Open

EMERSTOP_
EXEC_STOP
“Emergency stop”

523001 800D01EDF2 ASEQ01-EXEC_RESET‡

Figure 4.11-1 ASEQ01 controls the user programing logic to operate a CB

Table 4.11-2 Mapping points for the r remote control commands


Signal Number Signal Name Description M/O
523001 700D016D08 ASEQ01_CONTROL_REQ ASEQ01 control command received. (Mapping Data) M
523001 700D026D08 ASEQ02_CONTROL_REQ ASEQ02 control command received. (Mapping Data) M
523001 700D036D08 ASEQ03_CONTROL_REQ ASEQ03 control command received. (Mapping Data) M
… … …
523001 700D0F6D08 ASEQ15_CONTROL_REQ ASEQ15 control command received. (Mapping Data) M

GRL200 (Soft 033 & 037)


- 993 -
6F2S1914 (0.37)

Table 4.11-3 Mapping points for Emergency command


Signal Number Signal Name Description M/O
523001 820D10ED50 EMERSTOP_CONTROL_REQ Emergency control for stopping the operation M

Table 4.11-4 PLC connection points (Inputs for stopping ASEQ operation)
Signal Number Signal Name Description M/O

523001 800D01EDF2 ASEQ01_EXEC_RESET Instruction to stop ASEQ01 operation O


523001 800D02EDF2 ASEQ02_EXEC_RESET Instruction to stop ASEQ02 operation O
523001 800D03EDF2 ASEQ03_EXEC_RESET Instruction to stop ASEQ03 operation O
… … …
523001 800D0FEDF2 ASEQ15_EXEC_RESET Instruction to stop ASEQ15 operation O

Table 4.11-5 PLC monitoring points (Outputs to start ASEQ operation)


Signal Number Signal Name Description
523001 820D011F50 ASEQ01_EXEC_START Start instruction provided for ASEQ01 operation
523001 820D021F50 ASEQ02_EXEC_START Start instruction provided for ASEQ02 operation
523001 820D031F50 ASEQ03_EXEC_START Start instruction provided for ASEQ03 operation
… … …
523001 820D0F1F50 ASEQ15_EXEC_START Start instruction provided for ASEQ15 operation

Table 4.11-6 PLC monitoring points (Outputs to stop ASEQ operation)


Signal Number Signal Name Description
523001 810D011F51 ASEQ01_EXEC_STOP Stop instruction provided for ASEQ01 operation
523001 810D021F51 ASEQ02_EXEC_STOP Stop instruction provided for ASEQ02 operation
523001 810D031F51 ASEQ03_EXEC_STOP Stop instruction provided for ASEQ03 operation
… … …
523001 810D0F1F51 ASEQ15_EXEC_STOP Stop instruction provided for ASEQ15 operation

Table 4.11-7 PLC monitoring points (Outputs of ASEQ operation status)


Signal Number Signal Name Description
523001 000D011001 ASEQ01_ACC_EXEC Status of ASEQ01 operation
523001 000D021001 ASEQ02_ACC_EXEC Status of ASEQ02 operation
523001 000D031001 ASEQ03_ACC_EXEC Status of ASEQ03 operation
… … …
523001 000D0F1001 ASEQ15_ACC_EXEC Status of ASEQ15 operation

4.11.2 Preparation of the operation


The ASEQ01 function has three scheme switches: [ASEQ01-EN], [ASEQ01-CTRMENU] and
[ASEQ01-CTRAHMI].

The scheme switch [ASEQ01-CTRMENU] is used for a local operation (e.g., the front panel
operation on the IED). When On is set for the scheme switch [ASEQ01-CTRMENU], the PLC
sequence #1 can be instructed locally. The scheme switch [ASEQ01-CTRAHMI] is used to select
either a select-before-operation command (SBO) or a direct command (DIR) when the local

GRL200 (Soft 033 & 037)


- 994 -
6F2S1914 (0.37)

instruction is applied.

4.11.3 Example of automatic sequence operation


Figure 4.11-2 exemplifies some sequence logic programmed using the PLC function; the logic
is coded to operate two disconnector (DS1 and DS2) and a circuit breaker (CB). The logic can
provide an instruction to close DS1 (i.e., device #2), close DS2 (i.e., device #3), and then close
the CB (i.e., device #1) in a prescribed order.

Input signals Output signals


5Reset ASEQ01 execution

t 0 4ASEQ01 in execution
1Start command for ASEQ01 S Q
1s R 5s

S Q t 0 &
Closing Command for Device #2
End of execution of ASEQ01 1s R
≧1 2s 1
Termination of ASEQ01 on Level_1
≥1
Temporary signal 001
5Reset of ASEQ01 execution
Temporary signal 002

Control failure In closing switch at device #1 &


Termination of ASEQ01 on Level_1
UTOSEQ01)
Travelling detection & In selecting device #1 1

4ASEQ01 in execution & t 0


S Q &
Termination of ASEQ01 at level #1 Closing Command for Device #3
1s R 2s 1

Termination of ASEQ01 on Level_2 ≥1

5Reset of ASEQ01 execution

In closing switch at device #2 &


Termination of ASEQ01 on Level_2
In selecting device #2 1

& t 0
S Q &
Closing Command for Device #3
Termination of ASEQ01 on Level_2 1s R 2s
1

Complete termination of ATSQ01 ≥1

5Reset of ASEQ01 execution

In closing switch at device #1 &


Complete termination of ATSQ01
In selecting device #1 1
2Stop command for ASEQ01 S Q & Temporary signal 001
1s R
Complete termination of ATSQ01

In selecting device #1 &

In selecting device #2 1

In selecting device #3

3Emergency stop for ASEQ01 S Q & Temporary signal 002


1s R
Complete termination of ATSQ01

In closing switch at device #1 &

In selecting device #2 1

In selecting device #3

1DEV1PLCCTRLFAIL ≥1
6Control failure
1DEV2PLCCTRLFAIL
UTOSEQ01)
1DEV3PLCCTRLFAIL

Figure 4.11-2 Example of control logic programmed for device #1 to #3


1Note: If a start command is applied to the ASEQ01 function, the control logic

GRL200 (Soft 033 & 037)


- 995 -
6F2S1914 (0.37)

commences to operate the devices. Table 4.11-5 shows start commands.


2Note: If a stop command is applied to the ASEQ01 function, the operation of the control
logic will be canceled promptly provided that the control logic is not operating the
device. Alternatively, the control logic can wait for the operation being completed,
if the control logic is able to determine to continue the operation. Table 4.11-4
shows the stop commands.
3Note: See section 4.11.5. Table 4.11-9 and Table 4.11-10 show the emergency commands.
4Note: After the reception of the start command, the execution state can be monitored.
Table 4.11-7 shows the execution states.
5Note: The stop signal is provided for the logic. Table 4.11-6 shows the results of the stop
signals.
6Note: Following the generation of a control command by the control logic, if the control
command fails to initiate the operation of a device, the control logic determines
that the control command has failed. The control logic will generate signals in
order to express “Control failure”.

When a stop command is generated during the selection of Device #3, the control logic
will clear the operation if the control logic can determine that the operation of Device #3 is
complete. Figure 4.11-3 shows that Device #3 unable to operate following reception of the stop
command.
ON

Control logic in service.


Operating state OFF

*3The operating state turns to OFF, when the operation of Device#3 finishes
following the reception of a stop command from the ASEQ01 function.

Selection signal for Device #2


Start to close Completion of closing

Selection signal for Device #3


Start to close Completion of closing

Selection signal for Device #1


*4The operation of Device#3 failed.

*2The ASEQ01 function generates an operate signal for stopping the control logic.

*1The ASEQ01 function generates a select signal for stopping the control logic.

Figure 4.11-3 Timing chart for an automatic sequence when a stop command is injected during
the operation of Device#3

Figure 4.11-4 depicts the operating sequence when an emergency command is input; the
control logic will cancel the operation in accordance with the execution state given from a
device. If the operation signal is not controlling the device, the control logic will clear the
operation promptly. If the operation signal is controlling the device, the control logic will clear
the operation when the control logic function can determine that the operation of the device is
complete, in this case Device#1.

GRL200 (Soft 033 & 037)


- 996 -
6F2S1914 (0.37)

ON

OFF
Operating state
*4The operation state turns to OFF, when the control logic cancels the
selection of Device#1 following the reception of a stop command from
the ASEQ01 function.
Selection signal for Device #2

Selection signal for Device #3


*3The control logic turns the selection
signal to OFF when the control signal is
not sent for the device.

Selection signal for Device #1

*2The ASEQ01 function generates an emergency


command for the control logic.

*1The ASEQ01 function generates a selection signal for


the emergency stop for the control logic.

Figure 4.11-4 Time chart of automatic sequence when emergency stop command is applied
during the operation of Device#1

4.11.4 Control hierarchy conditions


The user should program the “Control hierarchy” for the ASEQ01 function. The user should
connect the condition with the select condition logic using the connection point
“ASEQ01IN_TMP_28”. For more information, see Chapter Control and monitoring application:
Control hierarchy. Table 4.11-8 shows the respective points in the ASEQ functions.
Table 4.11-8 Control hierarchy points on ASEQ functions
Signal Number Signal Name Description M/O
523001 820D01ED50 ASEQ01IN_TMP_28 ASEQ01 control hierarchy condition M
523001 820D02ED50 ASEQ02IN_TMP_28 ASEQ02 control hierarchy condition M
523001 820D03ED50 ASEQ03IN_TMP_28 ASEQ03 control hierarchy condition M
… … …
523001 820D0FED50 ASEQ15IN_TMP_28 ASEQ15 control hierarchy condition M

Table 4.11-9 Control hierarchy point for Emergency stop


Signal Number Signal Name Description M/O
523001 820D10ED50 EMERSTOPIN_TMP_28 Emergency control for stopping the operation M

4.11.5 Input for emergency stop


The ASEQ functions are able to receive an “EMERSTOP_EXEC_STOP” command (see Table
4.11-3); the user should program to acquire the sign so that the ASEQ logics can abandon for
controlling devices. The operation will stop instantly even if the control logic is waiting for
some condition (i.e., synchronization or others).

Table 4.11-10 PLC monitoring points (Outputs for ASEQ emergency status)
Signal Number Signal Name Description
523001 000D0D1001 EMERSTOP_ACC_EXEC Reception of an emergency signal
523001 800D0D1D58 EMERSTOP_EC_LCD Emergency signal generated on the LCD scream
523001 800D0D1D55 EMERSTOP_EC_OWS Emergency signal generated from OWS(HMI)
523001 800D0D1D56 EMERSTOP_EC_RCC Emergency signal generated from RCC
523001 800D0D1D57 EMERSTOP_EC_RMT Emergency signal generated at Remote

GRL200 (Soft 033 & 037)


- 997 -
6F2S1914 (0.37)

Signal Number Signal Name Description


523001 810D0D1F50 EMERSTOP_EXEC_STOP Command received for emergency stop
523001 310D0D1D01 EMERSTOP_LCD_ST State signal about LCD screen
523001 310D0D1D00 EMERSTOP_MMC_ST State signal about MIMIC screen
523001 800D0D1D54 EMERSTOP_SC_LCD Select command generated on the LCD
523001 800D0D1D51 EMERSTOP_SC_OWS Select command generated at OWS(HMI)
523001 800D0D1D52 EMERSTOP_SC_RCC Select command generated at RCC
523001 800D0D1D53 EMERSTOP_SC_RMT Select command generated at Remote

GRL200 (Soft 033 & 037)


- 998 -
6F2S1914 (0.37)

4.11.6 Mapping for IEC61850 communication


The user can operate the ASEQ function using IEC 61850 communications after first
completing the appropriate mapping using the GR-TIEMS software. Note that the ASEQ01
function is designed for the “Single Point Controller (SPC) class” described in the IEC 61850
communications standard. The user should follow steps:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data

(i) Editing Logical Node


The user should implement a logical node (LN) for the ASEQ01 function. Figure 4.11-5
exemplifies LN editing; the LN “(GAPC1)” is chosen for the ASEQ01 function. After the user
has defined an object “SPCSO1”, the ASEQ01 logical node is saved with the name “SPCSO1”
plus “LN Instance”. A definition for the object “SPCSO1” is made in the ASEQ01 logical node.
Choose either the SBO mode or the DIR mode when editing the LN.

SBO defined in LN

Figure 4.11-5 Defining “SPCSO1” object in GAPC1 logic node

Defining SBO mode


Figure 4.11-6 exemplifies the settings in LN “GAPC1” when the SBO mode is required for the
ASEQ01 function. In SBO control, the user should select the following items for the object
reference “GAPC1$SPCSO1” using the GR-TIEMS software;

GRL200 (Soft 033 & 037)


- 999 -
6F2S1914 (0.37)

 SBOw
 Oper
 Cancel
 Origin
 stSeld
 sboClass† (choice ”operate-once”)
 ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down

Figure 4.11-6 LN editing screen for SBO mode (for example)

Defining DIR mode


Figure 4.11-7exemplifies the settings in LN “GAPC1” when the DIR mode is required for the
ASEQ01 function. In the DIR mode, the following three items should be selected using the GR-
TIEMS software:

 Oper
 Origin
 ctlmodel (choice ”DOes or DOns”)

Figure 4.11-7 LN editing screen for DIR mode (for example)

(ii) Mapping output data


The user should group the ASEQ01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS.

Table 4.11-11 shows the signals in the ASEQ01 function that require mapping to the IEC
61850 communications. Figure 4.11-8 shows how to map a signal.

GRL200 (Soft 033 & 037)


- 1000 -
6F2S1914 (0.37)

Table 4.11-11 Mapping signals for SPCSO1 object


Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GAPC1$SPCSO1$origin orCat orCategory ST 523001 300D011008 ASEQ01_ORCAT
Ctrl/GAPC1$SPCSO1$origin orIdent Octet64 ST 523001 6A0D011009 ASEQ01_ORIDENT
Ctrl/GAPC1$SPCSO1 stVal BOOLEAN ST 523001 000D011001 ASEQ01_ACC_EXEC
Ctrl/GAPC1$SPCSO1 q Quality ST 523001 310D011005 ASEQ01-QUALITY
Ctrl/GAPC1$SPCSO1 t Timestamp ST 523001 900D011006 ASEQ01_TIME
Ctrl/GAPC1$SPCSO1 stSeld BOOLEAN ST 523001 000D011D90 ASEQ01_STSELD

Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.

Drag and drop

Figure 4.11-8 orCat attribute mapped into SPCSO1 object of GAPC1

(iii) Mapping input data


The ASEQ1 function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “ASEQ01_CONTROL_REQ”. Table 4.11-12 shows the input-point
“ASEQ01_CONTROL_REQ” and the Object reference “Ctrl/GAPC1$SPCSO1”; the user should
map the input-point to the Object references with attributes CO and CF under FC†. Figure 4.11-9
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).

GRL200 (Soft 033 & 037)


- 1001 -
6F2S1914 (0.37)

Table 4.11-12 Mapping signals required for SPCSO1 object in ASEQ01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GAPC1$SPCSO1$SBOw ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$SBOw ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$SBOw T Timestamp CO
Ctrl/GAPC1$SPCSO1$SBOw Test BOOLEAN CO
Ctrl/GAPC1$SPCSO1$SBOw Check Check CO
Ctrl/GAPC1$SPCSO1$SBOw$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$SBOw$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1$Oper ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Oper ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$Oper T Timestamp CO
Ctrl/GAPC1$SPCSO1$Oper Test BOOLEAN CO
523001 700D016D08 ASEQ01_CONTROL_REQ
Ctrl/GAPC1$SPCSO1$Oper Check Check CO
Ctrl/GAPC1$SPCSO1$Oper$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$Oper$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1$Cancel ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Cancel ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$Cancel T Timestamp CO
Ctrl/GAPC1$SPCSO1$Cancel Test BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Cancel$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$Cancel$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1 ctlModel ctlModel CF
Ctrl/GAPC1$SPCSO1 sboClass sboClass CF

Drag and drop

Check “Input”

Figure 4.11-9 Input-point mapped for GAPC1

GRL200 (Soft 033 & 037)


- 1002 -
6F2S1914 (0.37)

4.11.7 Setting
Auto Sequence(Function ID: 523001)
Setting items Range Unit Contents Default Note

ASEQ01-EN Off / On - ASEQ01 switch Off


ASEQ02-EN Off / On - ASEQ02 switch Off
ASEQ03-EN Off / On - ASEQ03 switch Off
…. …. …. …..
ASEQ15-EN Off / On - ASEQ15 switch Off
EMERS EMERSTOP-EN Off / On - CTRL EMERSTOP Enable Off
EMERSTOP-DEVNAME [Preferred name] - item name of Auto Control EMERSTOP EMERSTOP !
EMERSTOP-OFFNAME [Preferred name] - state name of state(off) Stop !
EMERSTOP-ONNAME [Preferred name] - state name of state(on) Start !
EMERSTOP-CTRMENU Off / On - control by MENU enable Off
EMERSTOP-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
ASEQ01 ASEQ01-DEVNAME [Preferred name] - item name of Auto Control Seqence01 ASC1 !
ASEQ01-OFFNAME [Preferred name] - state name of state(off) Stop !
ASEQ01-ONNAME [Preferred name] - state name of state(on) Start !
ASEQ01-CTRMENU Off / On - control by MENU enable Off
ASEQ01-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
ASEQ02 ASEQ02-DEVNAME [Preferred name] - item name of Auto Control Seqence02 ASC2 !
ASEQ02-OFFNAME [Preferred name] - state name of state(off) Stop !
ASEQ02-ONNAME [Preferred name] - state name of state(on) Start !
ASEQ02-CTRMENU Off / On - control by MENU enable Off
ASEQ02-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
ASEQ03 ASEQ03-DEVNAME [Preferred name] - item name of Auto Control Seqence03 ASC3 !
ASEQ03-OFFNAME [Preferred name] - state name of state(off) Stop !
ASEQ03-ONNAME [Preferred name] - state name of state(on) Start !
ASEQ03-CTRMENU Off / On - control by MENU enable Off
ASEQ03-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO
…. …. …. …..
ASEQ15 ASEQ15-DEVNAME [Preferred name] - item name of Auto Control Seqence15 ASC15 !
ASEQ15-OFFNAME [Preferred name] - state name of state(off) Stop !
ASEQ15-ONNAME [Preferred name] - state name of state(on) Start !
ASEQ15-CTRMENU Off / On - control by MENU enable Off
ASEQ15-CTRAHMI DIR / SBO - control action(Direct or SBO)by HMI SBO

! Note: The user can enter a preferred setting name using GR-TIEMS.

GRL200 (Soft 033 & 037)


- 1003 -
6F2S1914 (0.37)

4.11.8 Signal
 Signal monitoring points in ASEQ01
ASEQ(Function ID: 523001)
Element ID Name Description
000D001F40 ASEQ_MULTI_SEL Status flag to not be selected for multiple operations

000D011001 ASEQ01_ACC_EXEC Reception state of the automatic sequence instruction command

000D011D90 ASEQ01_STSELD ASEQ01 selected signal(stSeld) for SAS

310D011D00 ASEQ01_MMC_ST ASEQ01 state for MIMIC

310D011D01 ASEQ01_LCD_ST ASEQ01 state for LCD

800D011D51 ASEQ01_SC_OWS ASEQ01 select command by OWS(HMI)

800D011D52 ASEQ01_SC_RCC ASEQ01 select command by RCC

800D011D53 ASEQ01_SC_RMT ASEQ01 select command by Remote

800D011D54 ASEQ01_SC_LCD ASEQ01 select command by LCD

800D011D55 ASEQ01_EC_OWS ASEQ01 execute command by OWS(HMI)

800D011D56 ASEQ01_EC_RCC ASEQ01 execute command by RCC

800D011D57 ASEQ01_EC_RMT ASEQ01 execute command by Remote

800D011D58 ASEQ01_EC_LCD ASEQ01 execute command by LCD

810D011F51 ASEQ01_EXEC_STOP Commencing command for automatic sequence

820D011F50 ASEQ01_EXEC_START Stop command for automatic sequence

000D0D1001 EMERSTOP_ACC_EXEC Reception state of an emergency signal to stop the operation

000D0D1D90 EMERSTOP_STSELD EMERSTOP selected signal (stSeld) for SAS

310D0D1D00 EMERSTOP_MMC_ST EMERSTOP state for MIMIC

310D0D1D01 EMERSTOP_LCD_ST EMERSTOP state for LCD

800D0D1D51 EMERSTOP_SC_OWS EMERSTOP select command from OWS(HMI)

800D0D1D52 EMERSTOP_SC_RCC EMERSTOP select command from RCC

800D0D1D53 EMERSTOP_SC_RMT EMERSTOP select command by Remote

800D0D1D54 EMERSTOP_SC_LCD EMERSTOP select command from LCD

800D0D1D55 EMERSTOP_EC_OWS EMERSTOP execute command from OWS(HMI)

800D0D1D56 EMERSTOP_EC_RCC EMERSTOP execute command from RCC

800D0D1D57 EMERSTOP_EC_RMT EMERSTOP execute command by Remote

800D0D1D58 EMERSTOP_EC_LCD EMERSTOP execute command from LCD

810D0D1F50 EMERSTOP_EXEC_STOP Commencing command for emergency stop

 Connection points in PLC logic in ASEQ01


ASEQ(Function ID: 523001)
Element ID Name Description
820D01ED50 ASEQ01IN_TMP_28 Reception of control right for ASEQ01

800D01EDF2 ASEQ01_EXEC_RESET Reception of reset signal for ASEQ01 operation

820D10ED50 EMERSTOPIN_TMP_28 EMERSTOPIN_TMP_28

 Mapping point in ASEQ01


ASEQ(Function ID: 523001)
Element ID Name Description
700D016D08 ASEQ01_CONTROL_REQ ASEQ01 control command received. (Mapping Data)

Note: In the table above, the user will only find Element IDs and their names for the 1st

GRL200 (Soft 033 & 037)


- 1004 -
6F2S1914 (0.37)

device, but a 2nd and other devices are also provided in the ASEQ function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “ASEQ01_EC_LCD” point for
the 2nd device, use the description of “ASEQ02_EC_LCD” in place of
“ASEQ01_EC_LCD”. The user can obtain the ID value of
“ASEQ02_EC_LCD” by using the following steps:
Step 1 Find the element ID for ASEQ01_EC_LCD (i.e.,
“800D011D58”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “800D021D58” of
“ASEQ02_EC_LCD”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.

GRL200 (Soft 033 & 037)


- 1005 -
6F2S1914 (0.37)

5 Technical Description
Contents Pages Pages
Case structure and slot layout 1009 CPU 1028
-1/1 Case for 19 inch rack 1009 -Configuration switch 1029
-1/2 Case for 19 inch rack 1013 Date and time 1089
-3/4 Case for 19 inch rack 1011 -Time synchronization 1090
Binary IO module (BI, BO, and BIO) 1038 -DST(Summer time) 1095
-Input circuits 1040 -Time zone 1094
-Input features 1039 Function keys with LEDs 1076
-Output circuits 1051 Group setting for relays 1098
-Output features 1049 LED indicators 1076
-BI1A module 1058 Monitoring jacks 1086
-BI2A module 1059 Operation keys 1088
-BI3A module 1058 Power supply module (PWS) 1072
-BO1A module 1060 Transformer module for AC (VCT) 1015
-BO2A module 1060 -1CB setting 1024
-BIO1A module 1061 -1.5CB setting 1025
-BIO2A module 1061 -Change rated current 1020
-BIO3A module 1062 -CT polarity setting 1026
-BIO4A module 1062 -VCT11B terminals 1016
Communication modules 1030 -VCT12B terminals 1017
-100Base-TX/1000Base-T 1030 -Ratio 1019
-100Base-FX 1030 -Residual voltage setting 1023
-1000Base-LX 1030 -Reference voltage setting 1023
-RS485 1030
-Fiber optic 1030
-IRIG-B000 1030

GRL200 (Soft 033 & 037)


- 1006 -
6F2S1914 (0.37)

The IED hardware consists of a case, modules, and a human machine interface (HMI). For
instance, Figure 5-1 shows the structure of the GR-series IED which is mounted in 3/4×19”
rack. The user can find that the IED consists of a transformer module (VCT), a signal
processing and communication module (CPU), binary input and output modules (BI, BI, and
BIO, and a power supply module (PWS), which can be mounted in an order from left to right.
The IED case, which is designed for rack mount as shown in Figure 5-1, has two flanges
attached on the IED sides. Figure 5-2 shows hardware block diagram. The module structure
depends on the GR-series models, IED cases, and the customer specification. Therefore, the
user should check and confirm the actual modules with the ordering number in advance.

(The description of IED case helps to understand the IED structure and its functions.
Based on slot reference, terminal block, slot reference, GR-Series selects different cases. VCT,
CPU, BI, BO and BIO modules, PWS and HMI are described sequentially in this chapter. The
user is required to understand information provided in this chapter when wiring between the
IED and external devices and setting of the IED are performed. Hence, the user is required to
read this chapter thoroughly.)

BI, BO, and BIO


VCT CPU PWS

Figure 5-1 Modules in 3/4 19” rack’s chassis (Front view, removed the front panel)

GRL200 (Soft 033 & 037)


- 1007 -
6F2S1914 (0.37)

VCT CPU

Filter CPM2 LAN I/F


A/D Tele-
I CT×n communication
LAN I/F system

PCM Remote IED

V VT×m

BO
Auxiliary
relay Binary output
×18

HMI
BI
LCD/MIMIC
Photo coupler Binary input
×18
LEDs

Operation keys BIO


Auxiliary
relay Binary output
Monitoring jacks ×18

Function Key

Photo coupler Binary input


USB ×18
I/F
Local PC

Power PWS

Figure 5-2 Hardware Block Diagram (for example)

GRL200 (Soft 033 & 037)


- 1008 -
6F2S1914 (0.37)

IED case and module slot


5.1.1 1/1 Case
Figure 5.1-1 shows diagrams of the IED case structure for 1/1 size: (a) IED internal structure
seen from the front, (b) Terminal block arrangement seen from the rear, and (c) schematic
diagram.

(i) Viewing from the front side (Figure 5.1-1.a)


Thirteen slots are provided for mounting modules. The transformer module (VCT), the signal
processing and communication module (CPU), and the power supply module (PWS) are
mounted at predefined locations in the case. The binary IO modules (BI, BO, and BIO) are
placed in slots (IO#1 to IO#8), these slot locations are determined before factory shipment. For
detailed information on slot locations, module types and their connections for all IEDs, see
external connection figures. (See Appendix: Typical external connection).

(ii) Viewing from the rear side (Figure 5.1-1.b)


The group of terminal blocks for the 1/1 case viewed from the rear is shown. With respect to
BI, BO, and BIO, the terminal blocks are designed with both upper and lower terminals and
are labeled with alpha-numeric reference “T1”, “T2” and so on. Note that both the upper and
lower terminals are provided in the form of a single terminal block for respective BIs, BOs, or
BIOs. The terminal screw numbers for each terminal block relate to the individual circuits and
the user should check the configuration for each circuit. (For details, see section 5.4 or later).
Each slot is identified by its alpha-numeric reference (or slot reference) on the IED case. For
example, the user can identify that slot “IO#1” is linked with alpha-numeric reference “T1”.

For PWS, note that the terminal blocks are placed on the left hand side. The user can
also find alpha-numeric reference “T9” for PWS. The PWS circuits and relevant terminals are
discussed later. (For details, see section 5.5 or later)

The communication modules, which are between the VCT slot and BIO slot, are labeled
“C11” to “C15”. These communication modules are used for LAN, IEC61850 communication,
and external devices.

(iii) Schematic figure (Figure 5.1-1.c)


The slots and terminal blocks in the IED are shown. Using this figure, the user can find the
location of VCT, BIO, and PWS. This figure is useful when the user sets binary IO modules
using the setting tables. (For setting of binary IO modules, see section 5.4)

GRL200 (Soft 033 & 037)


- 1009 -
6F2S1914 (0.37)

a. View from front side

T9 T8 T7 T6 T5 T4 T3 T2 T1 VC1 VC2
1 1 1 1 1 1 1 1 1
C11
2 2 2 2 2 2 2 2 2
3 3 3 3 3 3 3 3 3
4 4 4 4 4 4 4 4 4
5 5 5 5 5 5 5 5 5
6 6 6 6 6 6 6 6 6
7 7 7 7 7 7 7 7 7
8 8 8 8 8 8 8 8 8
9 9 9 9 9 9 9 9 9
10 10 10 10 10 10 10 10 10 C12
11 11 11 11 11 11 11 11 11
12 12 12 12 12 12 12 12 12
13 13 13 13 13 13 13 13 13
14 14 14 14 14 14 14 14 14
15 15 15 15 15 15 15 15 15
16 16 16 16 16 16 16 16 16
17 17 17 17 17 17 17 17 17
18 18 18 18 18 18 18 18 18
19 19 19 19 19 19 19 19 19
C13
20 20 20 20 20 20 20 20 20

21 21 21 21 21 21 21 21 21
22 22 22 22 22 22 22 22 22
23 23 23 23 23 23 23 23 23
24 24 24 24 24 24 24 24 24
25 25 25 25 25 25 25 25 25 C14
26 26 26 26 26 26 26 26 26
27 27 27 27 27 27 27 27 27
28 28 28 28 28 28 28 28 28
29 29 29 29 29 29 29 29 29
30 30 30 30 30 30 30 30 30
31 31 31 31 31 31 31 31 31
32 32 32 32 32 32 32 32 32
33 33 33 33 33 33 33 33 33
34 34 34 34 34 34 34 34 34 C15 FG1 FG2
35 35 35 35 35 35 35 35 35
36 36 36 36 36 36 36 36 36
37 37 37 37 37 37 37 37 37
38 38 38 38 38 38 38 38 38
E
39 39 39 39 39 39 39 39 39
40 40 40 40 40 40 40 40 40

FG FGE FGD FGC FGB FGA

b. View from rear side

T9 T8 T7 T6 T5 T4 T3 T2 T1 VC1 VC2
C11

C12

C13

C14

C15

●FG ●FGE ●FGD ●FGC ●FGB ●FGA ●FG1 ●FG2 ●E

c. Schematic diagram

Figure 5.1-1 Slots and terminal blocks in 1/1 case

GRL200 (Soft 033 & 037)


- 1010 -
6F2S1914 (0.37)

5.1.2 3/4 case


Figure 5.1-2 shows diagrams of the IED case structure for 3/4 size: (a) IED internal structure
seen from the front, (b) Terminal block arrangement seen from the rear, and (c) schematic
diagram. For PWS, note that the terminal blocks are placed on the left hand side. The user can
also find alpha-numeric reference “T7” for PWS.

GRL200 (Soft 033 & 037)


- 1011 -
6F2S1914 (0.37)

a. View from front side

T7 T6 T5 T4 T3 T2 T1 VC1
1 1 1 1 1 1 1 C11
2 2 2 2 2 2 2
3 3 3 3 3 3 3
4 4 4 4 4 4 4
5 5 5 5 5 5 5
6 6 6 6 6 6 6
7 7 7 7 7 7 7
8 8 8 8 8 8 8
9 9 9 9 9 9 9
10 10 10 10 10 10 10 C12
11 11 11 11 11 11 11
12 12 12 12 12 12 12
13 13 13 13 13 13 13
14 14 14 14 14 14 14
15 15 15 15 15 15 15
16 16 16 16 16 16 16
17 17 17 17 17 17 17
18 18 18 18 18 18 18
19 19 19 19 19 19 19 C13
20 20 20 20 20 20 20

21 21 21 21 21 21 21
22 22 22 22 22 22 22
23 23 23 23 23 23 23
24 24 24 24 24 24 24
25 25 25 25 25 25 25 C14
26 26 26 26 26 26 26
27 27 27 27 27 27 27
28 28 28 28 28 28 28
29 29 29 29 29 29 29
30 30 30 30 30 30 30
31 31 31 31 31 31 31
32 32 32 32 32 32 32
33 33 33 33 33 33 33
34 34 34 34 34 34 34 C15 FG1
35 35 35 35 35 35 35
36 36 36 36 36 36 36
37 37 37 37 37 37 37
38 38 38 38 38 38 38
E
39 39 39 39 39 39 39
40 40 40 40 40 40 40

FG FGD FGC FGB FGA

b. View from rear side

T7 T6 T5 T4 T3 T2 T1 VC1
C11

C12

C13

C14

C15

c. Schematic figure

Figure 5.1-2 Slots and terminal blocks in 3/4 case

GRL200 (Soft 033 & 037)


- 1012 -
6F2S1914 (0.37)

5.1.3 1/2 case


Figure 5.1-3 shows diagrams of the IED case structure for 1/2 size: (a) IED internal structure
seen from the front, (b) Terminal block arrangement seen from the rear, and (c) schematic
diagram. For PWS, note that the terminal blocks are placed on the left hand side. The user
can also find alpha-numeric reference “T4” for PWS.

GRL200 (Soft 033 & 037)


- 1013 -
6F2S1914 (0.37)

a. View from front side


T4 T3 T2 T1 VC1
C11
1 1 1
2 2 2
3 3 3
4 4 4
5 5 5
6 6 6
7 7 7
8 8 8
9 9 9
10
11
10
11
10
11
C12
12 12 12
13 13 13
14 14 14
15 15 15
16 16 16
17 17 17
18 18 18
19 19 19 C13
20 20 20

21 21 21
22 22 22
23 23 23
24 24 24
25 25 25 C14
26 26 26
27 27 27
28 28 28
29 29 29
30 30 30
31 31 31
32 32 32
33 33 33
34 34 34 C15 FG1
35 35 35
36 36 36
37 37 37
38 38 38
E
39 39 39
40 40 40

FG FGB FGA

b. View from rear side

T4 T3 T2 T1 VC1
C11

C12

C13

C14

C15

c. Schematic diagram

Figure 5.1-3 Slots and terminal blocks in 1/2 case

GRL200 (Soft 033 & 037)


- 1014 -
6F2S1914 (0.37)

Transformer module for AC analog input (VCT)


The transformer module (VCT) of the IED is used to acquire the power system quantities. A
safety feature is available such that all of the VCT current inputs are shorted when a VCT
module is removed from the IED case. Note also that all of the voltage inputs are disconnected.
However, the user should make short circuit all AC current inputs and disconnect all AC
voltage inputs.
Note: We represent respective input signals at the “AC analog input (VCT)” as “Channel
numbers (Ch*)” when settings as to the ratio and others are required. The figure
below shows the operation screen for the AC analog input, which we shall discuss
later. The term “AI#1” in the below figure represents the VC alpha-numeric
references discussed in the preceding section.

The blow figures exemplify the ratio settings for respective channels on the VCT. For more
information about the operation of LCD screen, see chapter User interface. The user can also
set them using GR-TIMES (see chapter Engineering tool).

AC Analog Input AI#1 AI#1


10:48 1/2 10:48 1/12 10:48 1/2
AI#1 > CH1 > AI1_Ch1_Ratio +
AI#2 > CH2 > 2000
CH3 >
CH4 >
CH5 >
CH6 >

Figure 5.2-1 Setting samples about AC analog input (LCD screen)

Figure 5.2-2 Setting sample of AC analog input (GR-TIEMS)

GRL200 (Soft 033 & 037)


- 1015 -
6F2S1914 (0.37)

5.2.1 VCT11B
VCT11B is designed for 1.5 circuit breaker arrangement (1.5CB), as shown in Figure 5.2-3.
VCT11B is available for 1/2 case and larger.

VCT11B
Three-phase voltages
Va Va
Terminal Input Type of Jumper AC analog
Vb Vb
Screw input
Vc Vc
Number signal(3) input position(2) channel(1)
Reference voltage on busbar
Vs Vs
1 2 Va Voltage NA Ch1
Reference voltage on busbar or
residual voltage Vs2/Ve Vs2(or Ve) 3 4 Vb Voltage NA Ch2
The three-phase currents in the
1.5CB arrangement
5 6 Vc Voltage NA Ch3
Ia
Ia 7 8 Vs(4) Voltage NA Ch4
Ib
Ib 9 10 Vs2(4)/Ve(5) Voltage NA Ch5
Ic
Ic 11 12 Ia Current W6 Ch6
Residual current
Ie 13 14 Ib Current W7 Ch7

The other three-phase currents in the 15 16 Ic Current W8 Ch8


1.5CB arrangement
Ia 17 18 Ie Current W13 Ch9
Ia2
Ib 19 20 Ia2 Current W9 Ch10
Ib2
Ic 21 22 Ib2 Current W10 Ch11
Ic2
23 24 Ic2 Current W11 Ch12
Ie2
Residual current
25 26 Ie2 Current W14 Ch13
The other residual current in the
parallel lines
Iem 27 28 Iem Current W12 Ch14

Figure 5.2-3 Transformer module (VCT11B)

(1)Note: The channel number about the AC analog input is used to represent the
terminal location when the user sets the ratio about the CT or the VT. We
shall discuss later in section Setting VCT ratio.
(2)Note: In 5A rated operation, jumpers are inserted on all CTs, whereas no jumper is
inserted for 1A rated. To change it, see section Changing VCT rated current.
(3)Note: For the destination of input signals, see Appendix: Matrix between VCT
terminals and relay applications.
(4)Note: Reference voltages (Vs and Vs2) are used in the Voltage check (VCHK)
function; see Chapter Relay applications: VCHK.
(5)Note: Residual voltage (Ve) can be selected when setting [APPL-Ves2] = Ve. For
more information, see the succeeding section.

GRL200 (Soft 033 & 037)


- 1016 -
6F2S1914 (0.37)

5.2.2 VCT12B
VCT12B is designed for a single circuit breaker arrangement (1CB), as shown in Figure 5.2-4.
VCT12B is available for 1/2 case and larger. When the VCT12B is used in 1.5CB arrangement,
the user should have the Paralleling connected CTs (i.e., summation) at VCT12B.
VCT12B
Three-phase voltages
Va Va

Vb
Vb Terminal Input Type of Jumper AC analog
Vc Vc Screw input
Reference voltage on busbar Number signal(3) input position(2) channel(1)
Vs Vs
Reference voltage on busbar or 1 2 Va Voltage NA Ch1
residual voltage Vs2 Vs2(or Ve)
3 4 Vb Voltage NA Ch2
The three-phase currents in the 1CB
arrangement
Ia
5 6 Vc Voltage NA Ch3
Ia
Ib 7 8 Vs(4) Voltage NA Ch4
Ib
9 10 Vs2(4)/Ve(5) Voltage NA Ch5
Ic
Ic
11 12 Ia Current W6 Ch6
Residual current
Ie 13 14 Ib Current W7 Ch7
15 16 Ic Current W8 Ch8
17 18 Ie Current W13 Ch9
19 20 – – – –
21 22 – – – –
23 24 – – – –
25 26 – – – –
The other residual current in the
27 28 Iem Current W12 Ch14
parallel lines
Iem

Figure 5.2-4 Transformer module (VCT12B)


(1)Note: The cannel number about the AC analog input is used to represent the
terminal location when the user sets the ratio about the CT or the VT. We
shall discuss later in section Setting VCT ratio.
(2)Note: In 5A rated operation, jumpers are inserted on all CTs, whereas no jumper is
inserted for 1A rated. To change it, see section Changing VCT rated current.
(3)Note: For the destination of input signals, see Appendix: Matrix between VCT
terminals and relay applications.
(4)Note: Reference voltage (either Vs or Vs2) is used in the Voltage check (VCHK)
function; see Chapter Relay applications: VCHK.
(5)Note: Residual voltage (Ve) can be selected when setting [APPL-Ves2] = Ve. For
more information, see the succeeding section.

GRL200 (Soft 033 & 037)


- 1017 -
6F2S1914 (0.37)

5.2.3 Constitution of VCT


Figure 5.2-5 shows VCT terminal block together with its schematic diagram (termed ‘VC1’);
the same terminal screw numbers are shown on both the left and the right figures. The user
should note that the last screw (No. 30) and FG terminal are connected with a short-wire by
default.

VC1
VC1
VCT Alpha-
numeric Module type
reference
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Short-wire1
21
22
FG1 23
24
Frame ground 25
terminal on the case
26
27
28
29
30
1
Short-wire

FG1

VC1 terminal Schematic diagram

Figure 5.2-5 VC1 terminals (Rear view)


1Note: Short-wire between screw 30 and FG is connected by the manufacturer.
2Note: The figure is just drawn for general instruction about VCT structure. The number
of VTs and CTs on VCT is dependent on the VCT type ordered.

GRL200 (Soft 033 & 037)


- 1018 -
6F2S1914 (0.37)

5.2.4 Setting VCT ratio


As input sources are transformed with various VTs and CTs in the power system, the user shall
set each VT or CT ratio at each VCT terminal.

(i) Setting a ratio for the VT


When the VT quantity applied at the VCT terminal, a ratio of the primary voltage to the
secondary voltage should be set. A voltage is applied at the first terminal (Ch1) at VC1 alpha-
numeric reference, the user should set the ratio for the setting [AI1_Ch1_Ratio]. For example,
the user is requires to set a value ‘3636’ for the [AI1_Ch1_Ratio] when the primary is 400kV
and the secondary is 110V (i.e., 400kV/110V=3636). The channel position on the VCT is
discussed in the preceding section VCT.

(ii) Setting a ratio for the CT


When the CT quantity flows into the VCT terminal, a ratio of the primary current to the
secondary current should be set. For example, the user is required to set a value ‘4000’ for the
[AI1_Ch1_Ratio] when the primary is 4000A and the secondary is 1A (i.e., 4000/1=4000).

(iii) Setting list


Setting of AC analog input(Function ID: 200201)
Unit Default setting
Setting item Range Contents Notes
s value
VC1 AI1_Ch1_Ratio 1.000 to 20,000.000 – For AC analog input ch#1 at VCT#1 1.000
alpha-numeric AI1_Ch2_Ratio 1.000 to 20,000.000 – For AC analog input ch#2 at VCT#1 1.000
reference AI1_Ch3_Ratio 1.000 to 20,000.000 – For AC analog input ch#3 at VCT#1 1.000
AI1_Ch4_Ratio 1.000 to 20,000.000 – For AC analog input ch#4 at VCT#1 1.000
AI1_Ch5_Ratio 1.000 to 20,000.000 – For AC analog input ch#5 at VCT#1 1.000
AI1_Ch6_Ratio 1.000 to 20,000.000 – For AC analog input ch#6 at VCT#1 1.000
AI1_Ch7_Ratio 1.000 to 20,000.000 – For AC analog input ch#7 at VCT#1 1.000
AI1_Ch8_Ratio 1.000 to 20,000.000 – For AC analog input ch#8 at VCT#1 1.000
AI1_Ch9_Ratio 1.000 to 20,000.000 – For AC analog input ch#9 at VCT#1 1.000
AI1_Ch10_Ratio 1.000 to 20,000.000 – For AC analog input ch#10 at VCT#1 1.000
AI1_Ch11_Ratio 1.000 to 20,000.000 – For AC analog input ch#11 at VCT#1 1.000
AI1_Ch12_Ratio 1.000 to 20,000.000 – For AC analog input ch#12 at VCT#1 1.000
AI1_Ch13_Ratio 1.000 to 20,000.000 – For AC analog input ch#13 at VCT#1 1.000
AI1_Ch14_Ratio 1.000 to 20,000.000 – For AC analog input ch#14 at VCT#1 1.000

†Note: For more information, see Chapter User interface: AC analog input.
‡Note:The number of AC analog input channels depends on the configuration of the VCT
type and the VCT slot. Thereby, the user has to set the value of the VCT ratio
corresponding to a specific auxiliary VT/CT.

GRL200 (Soft 033 & 037)


- 1019 -
6F2S1914 (0.37)

5.2.5 Changing VCT rated current


In accordance with the ordering code, a rated current (either 1 or 5A) has been set previously
in the manufacture. If the user wishes to alter to other rated current, the user can do it by
using jumpers† on the VCT‡. This section illustrates the locations of the jumpers. To see the
actual workflows, jump to Chapter Installation and replacement: Changing rated current.
†Note:The user needs optional jumpers for altering. To get the optional ones, order them
the sales representative with ‘EP-221 optional code’.
‡Note:Remind that the user needs to alter the CPU configuration. See preceding section
Signal processing and communication module (CPU): Configuration switch. One of
EP-221 jumpers is required to use for the initialization.

(i) Rating jumpers


Rating jumpers are provided to determine the CT rated current (1 or 5A) on the VCT circuit.
Figure 5.2-6 shows the locations of the rating jumpers. They are identified with marks “W1”
to “W14” on the VCT circuit board. “W*” letters correspond to the AC analog input channel
numbers, which have been discussed previously.
Front Rear
Tr.1 Tr.2
Rating jumper locations

W1

W2
Connector

W3 Tr.3 Tr.4
Rating jumpers

W4

W5
Tr.5 Tr.6
W6

W7

W8

W9 Tr.7 Tr.8
W10

W11

W12 Tr.9
W13 Tr.10
W14

Tr.11
Tr.12 Tr.13 Tr.14

Layout of VCT components VCT Photograph


receptacle

header header

5 A rated setting (Jumper closed) 1 A rated setting (Jumper open)


Figure 5.2-6 Rating jumpers and locations

(ii) DEP settings


All [AI1_Ch*_Rating] settings are need to have DEP in order that VCT rated current will follow
the CPU configuration. The “DEP” will be set unconditionally when the IED is initialized by

GRL200 (Soft 033 & 037)


- 1020 -
6F2S1914 (0.37)

the GR-TIEMS; thereby, the user need not have [AI1_Ch*_Rating] settings respectively,

Setting of AC analog input(Function ID: 200201)


U Default setting
Range n value
Setting item i Contents Notes
1A 5A t 1A 5A
rating rating s rating rating
VC1 AI1_Ch1_Rating DEP / (1A) / (5A) – Rated current at CH#1 DEP
alpha-numeric AI1_Ch2_Rating DEP / (1A) / (5A) – Rated current at CH#2 DEP
references AI1_Ch3_Rating DEP / (1A) / (5A) – Rated current at CH#3 DEP
AI1_Ch4_Rating DEP / (1A) / (5A) – Rated current at CH#4 DEP
AI1_Ch5_Rating DEP / (1A) / (5A) – Rated current at CH#5 DEP
AI1_Ch6_Rating DEP / (1A) / (5A) – Rated current at CH#6 DEP
AI1_Ch7_Rating DEP / (1A) / (5A) – Rated current at CH#7 DEP
AI1_Ch8_Rating DEP / (1A) / (5A) – Rated current at CH#8 DEP
AI1_Ch9_Rating DEP / (1A) / (5A) – Rated current at CH#9 DEP
AI1_Ch10_Rating DEP / (1A) / (5A) – Rated current at CH#10 DEP
AI1_Ch11_Rating DEP / (1A) / (5A) – Rated current at CH#11 DEP
AI1_Ch12_Rating DEP / (1A) / (5A) – Rated current at CH#12 DEP
AI1_Ch13_Rating DEP / (1A) / (5A) – Rated current at CH#13 DEP
AI1_Ch14_Rating DEP / (1A) / (5A) – Rated current at CH#14 DEP

Note: Channel numbers for rated settings are dependent on VCT type.
1A and 5A are shown above, but neglect them. They are invalid here. Confirm
that all have DEP setting from LCD menu or GR-TIEMS screen.

(iii) Example for VCT12B rated current change


Figure 5.2-7 shows the setting items and corresponding rating jumpers about VCT12B.

VCT jumper: Close or open the circuits named W* numbers corresponding to the
currents. The hatched areas are required to close or open.
For changing to 5A rated, insert jumpers at W6, 7, 8, 12, 13.
For changing to 1A rated, remove jumper at W6, 7, 8, 12, 13.

GRL200 (Soft 033 & 037)


- 1021 -
6F2S1914 (0.37)

AC
Terminal
Input Type of Jumper analog
Screw
signal input position input
Number
channel LCD screen
1 2 Va Voltage NA Ch1 I/O setting sub-menu
3 4 Vb Voltage NA Ch2 AI#1
10:48 1/2
5 6 Vc Voltage NA Ch3 AI1_Ch6_Ratio +
7 8 Vs Voltage NA Ch4 2000
9 10 Vs2/Ve Voltage NA Ch5 AI1_Ch6_Rating +
DEP
11 12 Ia Current W6 Ch6
13 14 Ib Current W7 Ch7
15 16 Ic Current W8 Ch8
17 18 Ie Current W13 Ch9 VCT circuit board
Front Rear
19 20 – – – –
21 22 – – – – W1

Rating jumper locations


Tr.1 Tr.2
W2
23 24 – – – – W3

Connector
25 26 – – – W4 Tr.3 Tr.4

W5
27 28 Iem Current W12 Ch14 W6
W7 Tr.5 Tr.6
W8
W9
Tr.7 Tr.8
W10
W11
W12
W13
W14

Tr.12 Tr.13

Figure 5.2-7 Rating jumpers and settings for VCT12B


Note: The“W12” and “W13” are linked with “CH14” and “Ch9”, respectively.

Configuration switch: Change the CPU to the constrained mode (see Section
Signal processing and communication module).

Writing settings: [AI1_Ch6/7/8/9/14_Rating] settings, corresponding to the CTs,


shall have DEP absolutely. Rewriting the setting items is required with GR-
TIEMS. Confirm that DEP has been set definitely after the rewrite (for more
detail, see Chapter Installation and replacement: Changing rated current).

GRL200 (Soft 033 & 037)


- 1022 -
6F2S1914 (0.37)

5.2.6 Settings for residual voltage, CT polarity, and busbar arrangements


In the IED, the residual voltage represented ‘Ve’ is given by the computation with three-phase
voltages (Va, Vb, and Vc), but the VCT is ready to obtain it exclusively using APPL-VCT
settings when the residual voltage transformer is connected with the VCT. Additionally, the
VCT has the settings for changing the CT polarity so that the user can reverse the polarity
without wiring works. In the 1.5CB arrangement, the IED is required to obtain double three-
phase currents measured at separate current-transforms so that the VCT has a setting for
selecting the current transformers.

APPL-VCT
10:48 1/2
APPL-Ves2 +
Vs2
Polarity Change >

Figure 5.2-8 APPL-VCT setting screen

(i) Setting [APPL-Ves2] = Ve


Set Ve for the setting [APPL-VTes2], when the residual voltage transform is provided. Figure
5.2-9 illustrates the signals from the VTs on the feeder are injected for the ‘Ve’ terminal on the
VCT.

Busbar

VT on busbar

CB#1 IED
VCT VCHK function

VTs on feeder Three-phase voltages


VT
Va VL1

Vb VL2

Vc VL3

Reference voltage
Vs V3
A B C
Feeder Residual voltage
Vs2/Ve Ve (V0)
Setting [APPL-Ves2]=Ve

Figure 5.2-9 Connection with residual VT

(ii) Setting [APPL-Ves2] = Vs2


Figure 5.2-10 illustrates the residual voltage transform is not provided; set Vs2 for the setting
[APPL-VTes2]. Note that the IED computes the voltage in zero-sequence mathematically (3V0)
using the three-phase voltages.

GRL200 (Soft 033 & 037)


- 1023 -
6F2S1914 (0.37)

Busbar

CB#1 VTs on busbar

IED

CB#2 VCT Relay application

VTs on feeder Three-phase voltages


VT
Va VL1

Vb VL2

Vc VL3

Computation

Zero sequence
CB phase voltage (3V0)

Reference voltage
Vs V3

Reference voltage
Vs2/Ve V4
Feeder#1 A B C Feeder#2

Busbar

Figure 5.2-10 Computation of residual voltage

(iii) Setting [APPL-Ves2] = Off


If no voltage is applied at the Vs2/Ve terminal, the user can set Off for the setting [APPL-
VTes2].

Busbar

VTs on busbar

CB#1
IED
VCT Relay application

VTs on feeder Three-phase voltages


VT
Va VL1

Vb VL2

Vc VL3

Computation

Zero sequence
phase voltage (3V0)

Reference voltage
Vs V3
A B C
Feeder

Vs2/Ve
Setting [APPL-Ves2]=Off

Figure 5.2-11 Connection with one VT on the busbar

(iv) Setting [APPL-CTSELECT] = 1CT


Figure 5.2-12 illustrates the operation in 1CB arrangement using the setting [APPL-
CTSELECT]=1CT. Figure 5.2-13 shows that composites currents (Ia, Ib, and Ic) are generated
physically by wiring for the operation in 1.5CB arrangement.

GRL200 (Soft 033 & 037)


- 1024 -
6F2S1914 (0.37)

Busbar

IED
DIF function
VCT
Three-phase currents
CT
Ia Ia

1CT
Ib Ib

Ic Ic
CB

Ia2

Ib2

Ic2

A B C
Feeder Setting [APPL-CTSELECT] = 1CT

Figure 5.2-12 1CB arrangement with [APPL-CTSELECT]=1CT

IED
DIF function
Busbar VCT
Three-phase currents
CT
Ia Ia
1CT

Ib Ib

Ic
CB#1

Ic

Feeder#1 Ia2
CB#2

Ib2

Ic2
2CT

Feeder#2
CB

A B C Busbar Setting [APPL-CTSELECT] = 1CT

Figure 5.2-13 Paralleling connected CTs with [APPL-CTSELECT]=1CT


Note: The setting [APPL-CTSELECT] is just available for VCT11B.

(v) Setting [APPL-CTSELECT] = 2CT


Figure 5.2-14 illustrates the operation in the 1.5CB arrangement when two three-phase
currents can be injected separately for the VCT. The two three-phases currents are composited
in the IED.

GRL200 (Soft 033 & 037)


- 1025 -
6F2S1914 (0.37)

Busbar IED
DIF function
VCT
CT
Ia

1CT
Ib
Three-phase
Ic currents

CB#1
Ia

Feeder#1 Ib
CB#2

Ic
Ia2
2CT

Ib2

Ic2

Feeder#2
CB

Busbar

A B C Setting [APPL-CTSELECT] = 2CT

Figure 5.2-14 1.5CB arrangement with [APPL-CTSELECT]=2CT

(vi) CT polarity settings


The user can reverse the CT polarity using settings. For example, the user wishes to change
the polarity to negative in the first currents group (that is, Ia, Ib, and Ic on the VCT; we term
them ‘1CT’), set Negative for the setting [Pol-1CT]. Similarly, for the second current group
(that is, Ia2, Ib2, and Ic2), set Negative for the setting [Pol-2CT]. The user can also change the
polarity in ‘Ie’, ‘Ie2’, ‘Iem’, as shown in Table 5.2-1.

Busbar VCT

CT
Ia

Ib 1CT

Ic

Setting [Pol-1CT] = Positive


CB#1

Ie 1CT-Ie

Setting [Pol-1CT-Ie] = Positive

Line1
CB#2

Line2
CB

Iem CT-Iem

Setting [Pol-CT-Iem] = Positive


Busbar

Figure 5.2-15 Positive settings for Paralleling connected CTs in VCT12B

GRL200 (Soft 033 & 037)


- 1026 -
6F2S1914 (0.37)

Busbar VCT

CT
Ia

Ib 1CT

Ic

Setting [Pol-1CT] = Positive

CB#1
Ie 1CT-Ie

Setting [Pol-1CT-Ie] = Positive


Line1
CB#2

Ia2

Ib2 2CT

Ic2

Setting [Pol-2CT] = Positive


Line2
Ie2 2CT-Ie
CB

Setting [Pol-2CT-Ie] = Positive

Iem CT-Iem

Setting [Pol-CT-Iem] = Positive


Busbar

Figure 5.2-16 Positive polarity settings in 1.5CB arrangement in VCT11B

Table 5.2-1 VCT settings provided with FEP_COMMON


FEP_COMMON (Function ID: 7F0001) 1CB 1CB or 1.5CB
Uni Settings in Settings in
Setting item Range Contents
ts VCT12B† VCT11B‡
APPL-Ves2 Off / Ve / Vs2 – Voltage input either Ve pr Vs Vs2 Vs2
APPL-CTSELECT 1CT / 2CT – Selection of either 1CB or 1.5CB (Not available) 2CT
Polarity Pol-1CT Negative / Positive – 1CT Polarity Positive Positive
setting Pol-1CT-Ie Negative / Positive – Ie Polarity Positive Positive
Pol-2CT Negative / Positive – 2CT Polarity (Not available) Positive
Pol-2CT-Ie Negative / Positive – Ie2 Polarity (Not available) Positive
Pol-CT-Iem Negative / Positive – Iem Polarity Positive Positive
†Note: For more information about the VCT11B and VCT12B, see the preceding section.

GRL200 (Soft 033 & 037)


- 1027 -
6F2S1914 (0.37)

Signal processing and communication module (CPU)


A signal-processing and communication module (CPU) are made up of a main circuit board for
processing (CPM2) and ‘piggyback’ circuit boards for communication modules (COM#1 to
COM#5). These circuit boards are designed for LAN, time synchronization and others. They
are mounted on the CPU main board by their connectors. Figure 5.3-1 shows a board
implementation example.

CPU

CPM2
COM#1

CPU COM#2

COM#3

COM#4

COM#5

Figure 5.3-1 CUP and their communication modules (COM#1 to COM#5)


Note: The implementation of COM#1 to #5 may vary according to circumstances.

5.3.1 Signal processing


The operation of relay and control applications are achieved with the CPU on the CPM2 board.
The CPU board has SDRAM, MRAM, and NOR-Flash; the NOR-Flash is used to store setting
data and recording data; the MRAM is used to store several counter values. Both are of non-
volatile memory so that the stored data will be not be erased if the power is cut off.
IED

CPU COM#1 LAN network


BIO#1
CPM2
COM#2
VCT#1 VCT#2
Remote IED1
BIO#2 COM#3
BIO#3
BIO#4
BIO#5
BIO#6 COM#4 Remote IED2
BIO#7
BIO#8

COM#5 IRIG-B

Figure 5.3-2 Diagram of processing

GRL200 (Soft 033 & 037)


1028
6F2S1914 (0.37)

5.3.2 Configuration switch


The CPU module has a jumper to change configuration mode (Jumper W6). Figure 5.3-3 shows
the location. For default mode (normal), Pins 1-2 and 3-4 are open (i.e., default configuration
has been set by the manufacture in accordance with the order code). When the user wishes to
alter the other mode particularly, close either Pin 1-2 or Pin 3-4 using a jumper (Optional EP-
221).

CPU
W5
COM#1
2-1
4-3

COM#2
CPM2
W6
2-1
4-3 COM#3

W7 CPU
2-1
4-3
COM#4

W8
2-1 COM#5
4-3

W6 W6
Jumper Configuration mode
(1-2) (3-4)
2-1 Default (normal) mode(i.e.,
Open Open
4-3 manufacture setting mode )

2-1
Closed Open Constrained mode (1A rated)
4-3

2-1
Open Closed Constrained mode (5A rated)
4-3

Figure 5.3-3 Configuration switch


Note: Alter the configuration mode before VCT setting. Using GR-TIEMS, the user
needs to rewrite the settings. See Chapter Installation and replacement:
Changing rated current for more detail.

GRL200 (Soft 033 & 037)


- 1029 -
6F2S1914 (0.37)

5.3.3 Communication modules


The tables below show piggyback-circuit-modules provided for the communication. They are
mounted on CPU module directly. The actual mountings depend on the user ordering; thus,
the user should locate the actual implementations by the ordering using Appendixes: Ordering
and Typical external connection.

Table 5.3-1 Communication modules for Protection


Module Protection signaling Protection signaling
Connector ST type LC type (Duplex)
Medium Fiber optic(GI) Fiber optic(SM/DSF)
Usage Tele-protection (2km class) Tele-Protection (30km / 80 km class)
Protection Protection

Symbol
RX TX

RX
TX

Table 5.3-2 Communication modules for Network


Module 100Base-TX/1000Base-T 100Base-FX 1000Base-LX
Connector RJ45 type SC type LC type (Duplex)
Medium Shielded twist pair Fiber optic Fiber optic
Substation automation Substation automation Substation automation
Usage
system and others system and others system and others
100/1000 100BASE-FX 1000
BASE-T BASE-LX

Symbol
TX

RX

Table 5.3-3 Communication modules for Miscellaneous


Module RS485 Fiber optic interface IRIG-B
Connector PCB connector ST type PCB connector
Medium Shielded twist pair Fiber optic(GI) Shielded twist pair

Data transfer in Data transfer in Time


Usage
IEC103 IEC103 (2km class) synchronization
RS485 Remote IRIG-B000
A1 Comm. A1
B1 B1 SIG
COM-A
A2 A2(Disuse)

Symbol
RX
B2 B2(Disuse)
COM-B
A3 A3
B3 B3
COMM TX GND

GRL200 (Soft 033 & 037)


- 1030 -
6F2S1914 (0.37)

1. Protection signaling module (GI-ST plug or SM/DSF-LC plug)


The protection signaling communication module is to communicate with the remote IED for
relay applications. A fiber optical cable classified in the GI optical fiber is mainly used in short
haul communication (shorter than 2km). In medium haul, an optical fiber in SM is required.
In long haul, an optical fiber in DSF is required.

Figure 5.3-4 Protection signaling module

2. 100Base-TX/1000Base-T module (RJ-45 plug)


A twisted-pair cable is required for the LAN connection. The module is used for the GR-TIEMS
operation or the LAN communication. Use a shielded twisted pair cable so that electric
magnetic compatibility is satisfied.

C11

C12

Figure 5.3-5 100Base-TX/1000Base-T module

3. 100Base-FX module (SC plug)


A fiber optic cable is required for the connection. 100Base-FX module is used for the LAN
communication. Dual slots space (i.e., labeled with “C11” and “C12”) is occupied when a single
(Port A) module is mounted (see Figure 5.3-6; i.e., space “C12” is not blank). Therefore, the
total number for communication ports needs to be cared.

C11 C11

C12 C12

Figure 5.3-6 100Base-FX module (left for single port; right for dual ports)

GRL200 (Soft 033 & 037)


- 1031 -
6F2S1914 (0.37)

4. 1000Base-LX module (LC plug)


A pair of optic fiber cables is required. The 1000Base-LX module can be used for the GR-TIEMS
operation or the LAN communication. Use SM mode fiber when long distance is required.
C11

C12

Figure 5.3-7 1000Base-LX module

5. RS485 module
RS485 module has a PCB connector. The module should be connected with a shielded-twisted-
pair cable; it is used for communication in the IEC60870-5-103, Modbus, and DNP. The
terminal arrangement and references are shown below. The cable sheath should be connected
with the frame ground (FG) in the IED case. For the use of the a shielded-twisted-pair cable,
the user should note that the total length should be less than 1200 meter (0.75 miles); the
terminal resistor (150 ohms) should be connected when any connector is not connected. For
setting the parameters, see Chapter Communication protocol: RS485 communication.
Sheath
Top
PCB connector A1 A cable for

A1 B1 B1 an IED
COM-A(+)
A2
A2 B2 Sheath
COM-B(−) B2
A cable for
A3 B3 A3
another
Bottom
COMM(GND) B3
IED
0V

a. View from connector edge b. Port circuit Frame ground (FG)

C11

C12

Figure 5.3-8 RS485 connection and module

GRL200 (Soft 033 & 037)


- 1032 -
6F2S1914 (0.37)

6. Fiber optic module


Fiber optic module is used for the serial communication in the IEC 60870-5-103 standard.

Figure 5.3-9 Fiber optic module

7. IRIG-B000 module
IRIG-B000 module is used to receive the digital signal generated with an external clock; the
signal is in conformity to serial IRIG-B000 format. Note that the IRIG-B000 module is able to
receive digital signal (TTL) only (i.e., the reception of AM signal is not applicable). This module
is isolated using a photo coupler; the user should note A2 and B2 connectors are not used. The
peak value of IRIG-B000 signal should be greater than 3.5 volts; the IRIG-B000 module has
the input register (about 3k ohm). Thus, the terminal register can be required when the IRIG-
B000 signal is delivered for several devices; the value of the terminal register depends on the
number of deliveries and the performance of the external clocks. For setting of time
synchronization, see Chapter Technical Description: Clock function.
Top
PCB connector A1
A1 B1 B1 SIG

A2 (Disuse)
A2 B2
B2 (Disuse)
A3 B3 A3
Bottom B3 GND
a. View from connector edge b. Port circuit

C11

C12

Figure 5.3-10 IRIG-B000 module

GRL200 (Soft 033 & 037)


- 1033 -
6F2S1914 (0.37)

5.3.4 Location of communication modules


As described earlier, the user should examine the type of communication module and the
location where the module is placed. Therefore, the user is required to understand the
reference, when the user examines the connection figures. (See Appendix: Typical external
connection)

Figure 5.3-11 exemplifies IED has a LAN module (1000BASE-LX) and Protection signaling
module (ST) placed at C11 and C13 locations. IRIG-B and Fiber optic module are located at
C14 and C15. As shown in Table 5.3-4, Fiber Optic module is allowed to stay at C11, C13, or
C15, but 1000BASE-LX and Protection modules must stay at C11 and C13 firstly. Therefore,
Fiber Optic module has to stay at C15.

Com. SLOT VCT SLOT


1000BASE-LX
VC1
VC1
C11 VCT
1000BASE
C11 Blank -LX

C12
Protection
C12 Blank

IRIG-B000 C13
C13 Protection

C14
C14

Fiber Optic.
FG1

E C15
C15 Remote
Comm.

FGE

FG1

Practical communication modules Schematic diagram

Figure 5.3-11 Modules structure (’11 code’ at C&D pos.; ‘6U code’ at E&F pos.)

GRL200 (Soft 033 & 037)


1034
6F2S1914 (0.37)

Figure 5.3-12 illustrates a structure, which has 1000BASE-LX, IRIG-B000, dual Protection
signaling modules, and Fiber Optic module. Table 5.3-4 describes a protection signaling module
cannot stay at C12 alone, because C12 is just ready for dual protections signaling modules
placed at both C11 and C12. Therefore, the dual protections ones shall be located at C13 and
C14, if LAN module is placed at C11. Then, IRIG-B000 is allowed to locate at C12. At last,
Fiber Optic module has to be placed at C15

Com. SLOT VCT SLOT


1000BASE-LX
VC1
VC1
C11 VCT
1000BASE
C11 IRIG-B000 -LX

C12
Protection
C12

Protection C13
C13 Protection

C14
C14 Protection

Fiber Optic
FG1

E C15
C15 Remote
Comm.

FGE

FG1

Practical communication modules Schematic diagram

Figure 5.3-12 Modules structure (’21 code’ at C&D pos.; ‘6U code’ at E&F pos.)

GRL200 (Soft 033 & 037)


1035
6F2S1914 (0.37)

Figure 5.3-13 illustrates the other structure, which has 100BASE-FX, IRIG-B000, Protection
signaling module, and Fiber Optic module. Table 5.3-4 describes a protection module cannot
stay at C12 alone, because that is just ready for dual protections modules at both C11 and C12.
Therefore, the protection signaling one shall be located at C13. Note C12 has been occupied by
100BASE-FX circuit (see Figure 5.3-6). IRIG-B000 is allowed to locate at C14. At last, Fiber
Optic module has to be placed at C15

Com. SLOT VCT SLOT


1000BASE-LX
VC1
VC1
C11 VCT
100BASE
C11 Blank -FX

C12
Protection
C12 Blank

IRIG-B000 C13
C13 Protection

C14
C14

Fiber Optic
FG1

E C15
C15 Remote
Comm.

FGE

FG1

Practical communication modules Schematic diagram

Figure 5.3-13 Modules structure (’11 code’ at C&D pos.; ‘6G code’ at E&F pos.)

GRL200 (Soft 033 & 037)


1036
6F2S1914 (0.37)

5.3.5 Implementation rules


Communication modules are implemented at C11 to C15. The layouts of these communication
modules are matched with Ordering codes at Positions ‘C, D, E, and F’; the implementation
orders are ruled by Table 5.3-4.
Table 5.3-4 Combination rules for communication modules
LAN modules ○
1 LAN module ○
2 Comm. in IEC103
Protection
Single or Double signaling in
ports in Single or Double C37.94 (ST
Comm. 1000Base-LX ports in type) IRIG
RS485 Fiber
Location

I/F 1000Base-T 1000Base-FX or Toshiba signal


100Base-TX property
(LC type)
Primary Secondary Primary Secondary
(Port A) (Port B) (Port A) (Port B) 1 CH 2 CHs (Port1) (Port2) (Port1) (Port2)
C11  NA  NA
LAN
C12 –  NA 
C11  NA
C12 NA 
Protection
C13  NA
signaling
C14 NA 
C15 – –
C11 † NA † NA
C12 NA †× NA †×
Comm. in
C13 † NA † NA
IEC103
C14 NA † NA †
C15 † NA † NA
C11 ‡
C12 ‡×
IRIG C13 ‡
C14 ‡
C15 ‡
Note: Modules are implemented at the locations shown in signs‘, , †, ‡’. The sign
weighed primary is ‘’ so that it appears from the top ‘C11’ (i.e., LAN modules are located
at C11 or C12 firstly). The sign ‘’ is weighted secondary so that one or two of them appear

below the sign ‘’ (i.e., Protection signaling module is located under the LAN model. Notice
that it can be located at C11 or C12 when no LAN module exists). The ‘† and ‡’ are weighted

lightly very much so that Comm. and IRIG module can be located under the LAN or the

protection signaling modules. (i.e.,  >  > † > ‡; the implementing order is ruled by the

importance of the communication from the top positon). Sign ‘–‘ represents a blank slot.
Sign ‘×’ represents that it is not possible to implement a module when a LAN module○
2 is

selected. It is not allowed to mount RS485 and Fiber Optic modules at the same time in the

case.

GRL200 (Soft 033 & 037)


- 1037 -
6F2S1914 (0.37)

Binary IO module (BI, BO, and BIO)


Binary IO modules are provided in the IED to signal a command for external devices. Binary
IO modules are also used to receive status information. Binary IO modules are connected to
external devices with signal wires using terminal blocks on the rear of the IED. There are
standard type and variable type in Binary IO modules as shown in Table 5.4-1.

Table 5.4-1 Number of input and output circuits1


Number of Number of output circuits2
Module Module
# input Fast Semi-fast Auxiliary
name3 Type4 Hybrid Form C
circuits operating operating (Normal)
1 BI1A Standard 18 0 0 0 0 0
2 BI2A Variable 12 0 0 0 0 0
3 BI3A Standard 32 0 0 0 0 0
4 BO1A Standard 0 0 6 0 12 0
5 BO2A Standard 0 0 0 16 0 0
6 BIO1A Standard 7 0 6 0 3 1
7 BIO2A Standard 12 0 3 0 1 1
8 BIO3A Standard 8 6 0 0 1 1
9 BIO4A Variable 6 0 0 6 1 1
1Note: One of two voltages is applied for the binary IO modules: 48Vdc (24 to 60)
and 220Vdc (110 to 250). The DC voltage supplied to the IED determines the
voltage type selection; hence, a combination of different voltage types is not
possible.
2Note: For the structure and the number of binary IO modules, see section 5.4.5.
3Note: For details of the output circuits, see Table 5.4-6.
4Note: For the binary input circuits in the standard type, the user can choice either
a high voltage or a low voltage with regard to the input threshold. For the ones of
the variable type, the user itself can set a threshold value with regard to input
voltage using settings.

GRL200 (Soft 033 & 037)


- 1038 -
6F2S1914 (0.37)

5.4.1 Binary input feature


Binary input circuits have common programmable logic (CPL). Each circuit is independent,
but the circuits in the BI3A module are not independent, as shown in Table 5.4-2.
Table 5.4-2 Input circuits and features associated with binary IO module
Module Input features Example Symbols
type sign
1 BI1A - Isolated using photo
Polarity
coupler Terminal screw number

-Polarity dependent
1
(+)
-Independent circuit 2
BI1
(−)
2 BI2A -Isolated using photo Circuit
number
coupler
Screw on terminal block
-Polarity dependent
- Independent circuit
-Variable threshold
3 BI3A -Isolated using photo
Polarity
coupler Terminal screw
number
-Polarity dependent (+)
1

-Sharing common BI1 BI1


Circuit number
connections (+)
2
BI2

Circuit
Terminal screw
number
number
34
(+)
BI32

35
(−) Photo coupler
36
(−)
37
(−)
38
(−)

Screw on terminal block

4 BIO1A
5 BIO2A Same as BI1A
Same as BI1A and BI2A
6 BIO3A
7 BIO4A Same as BI2A
The user can find the connector of binary IO modules, the terminal number and
arrangement of the binary input circuits in section 5.4.5.

GRL200 (Soft 033 & 037)


- 1039 -
6F2S1914 (0.37)

5.4.2 Binary input circuit


The binary input circuit has a threshold for the input voltage and the user can regulate the
threshold using scheme switches and settings. Additionally, the binary input circuit has a
function in response to chattering signals produced by bouncing contacts, a programmable logic
for retarding and inverting the signal, and the user can set the respective features with
settings. Table 5.4-3 shows the respective settings and ranges in the standard type. Table 5.4-4
shows the ones in the variable types.

Table 5.4-3 Setting items for binary input circuits in the standard type

Units
Setting item1 Range Contents Default

THRES_Lvl Low/High – Threshold level for input voltage Low


Common
CMP_NUM 4 to 9 – Number of times in the filter 4
BI1_CPL Off/On – Switch of programmable operation in BI1 Off
BI1 On Delay Timer 0.000 to 300.000 s Value in the on-delay timer 0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BI1 signal Normal
BI2_CPL Off/On – Switch of programmable operation in BI2 Off
BI2 On Delay Timer 0.000 to 300.000 s Value in the on-delay timer 0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BI2 signal Normal
BI3_CPL Off/On – Switch of programmable operation in BI3 Off
BI3 On Delay Timer 0.000 to 300.000 s Value in the on-delay timer 0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BI3 signal Normal

….. ….. ….. ….. …..

BIn_CPL Off/On – Switch of programmable operation in BIn Off


BIn2 On Delay Timer 0.000 to 300.000 s Value in the on-delay timer 0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BIn signal Normal
1Note: Setting items are provided in each slot; see Figure 5.4-4. Also, see section 5.4.6 (i).
2Note: BIn_CPL and other settings are provided for all binary input circuits. For
example, the user can configure 18 CPLs in BI1A.
3Note: Each setting item above is required to set at every IO_slots.

GRL200 (Soft 033 & 037)


- 1040 -
6F2S1914 (0.37)

Table 5.4-4 Setting items for binary input circuits in the variable type (i.e., BI2A and BIO4A)

Units
Setting devices Range Contents Default

BI1-3_PICKUP 18 to 222 V Guaranteed-minimum-pick-ups at BI1, BI2, and BI3 77


BI4-6_PICKUP 18 to 222 V Guaranteed-minimum-pick-ups at BI4, BI5, and BI6 77
Common BI7-9_PICKUP 18 to 222 V Guaranteed-minimum-pick-ups at BI7 to BI94 77
BI10-12_PICKUP 18 to 222 V Guaranteed-minimum-pick-ups at BI10 to BIn4 77
CMP_NUM 4 to 9 – Number of times in the filter 4
BI1_CPL Off/On – Switch for programmable operation in BI1 Off
BI1 On Delay Timer 0.000 to 300.000 s Value in the on-delay timer 0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BI1 signal Normal
BI2_CPL Off/On – Switch for programmable operation in BI 2 Off
BI2 On Delay Timer 0.000 to 300.000 s Value in the on-delay timer 0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BI2 signal Normal
BI3_CPL Off/On – Switch for programmable operation in BI 3 Off
BI3 On Delay Timer 0.000 to 300.000 s Value in the on-delay timer 0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BI3 signal Normal

….. ….. ….. ….. …..

BIn_CPL Off/On – Switch for programmable operation in BI n Off


BIn4 On Delay Timer 0.000 to 300.000 s Value in the on-delay timer 0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BIn signal Normal
4Note: BIn_CPL and other settings are provided for all binary input circuits. For
example, the user can set for 12 CPLs in BI2A and for 6 CPLs in BIO4A.

As an example, Figure 5.4-1 shows the binary input circuit of BI1A in order to help
understand the settings. BI1A consists of 18 binary input circuits and each circuit has three
settings:
Setting threshold level
Comparison feature for contact chatter
CPL switches (“Delayed pick-up and delayed drop-off signal” and “Logic level
inversion”), used as basis of input signal characteristics.

GRL200 (Soft 033 & 037)


- 1041 -
6F2S1914 (0.37)

From 8001001111 8001001110


External devices For Relay & and
On Delay Timer Off Delay Timer 8001001172 control functions
BI1-NC Filter BI1
t 0 0 t & ≥1
BI1 BI1-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&

Normal On &
[INVERSE-SW]
Inverse [BI1-CPL] Off
8101011111 8101011110
On Delay Timer Off Delay Timer 8101011172
BI2-NC BI2
t 0 0 t & ≥1
BI2 BI2-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&

Normal On &
[INVERSE-SW]
Inverse [BI2-CPL] Off
8201021110 8201021110
On Delay Timer Off Delay Timer
BI3-NC BI3 8201021172
t 0 0 t & ≥1
BI3 BI3-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&

Normal On &
[INVERSE-SW]
Inverse [BI3-CPL] Off

8********** BIn
BIn-NC BIn
On Delay Timer Off Delay Timer 8**********
t 0 0 t & ≥1
BIn BIn-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&

Normal On &
[INVERSE-SW]
Inverse [BIn-CPL] Off

Low
[THRES_Lvl]
High
R1

R1

Figure 5.4-1 Common programmable logic for BI1A

Respective element IDs (i.e., 8001001172 and others) designate respective signal
monitoring points of the binary input circuits (i.e., BI1-CPL and others). Thus, the user can
handle the signals on the binary input circuit using element ID together with function ID.
When we assume that BI1A module is at IO#1 slot in the IED case, and if the user wishes to
see the first circuit signal of this BI1A module, the user can identify its signal† using the
element ID (8001001172) and the function ID of IO#1 slot‡.

GRL200 (Soft 033 & 037)


- 1042 -
6F2S1914 (0.37)

†Note:The user can see the signals of the binary input circuits on the IED screen.
Chapter User interface: Monitoring-sub menu discusses how to see the state of the
binary input circuits.
‡Note:Function IDs identify every IO slots. For example, IO#1 slot has been identified by
the function ID “200B001”. Therefore, when the user wishes to program the signal
“BI1-CPL” on BI1A at IO#1, the user should designate its signal using the
function ID “200B001” and Element ID “8001001172”. On the other hand, when
the signal “BI2-CPL” on BI1A at IO#2 is required to program, the user should
designate that signal using the function ID “200B002” and Element ID
“8001001172”. For more information with regard to the function ID and the Data
ID at IO#1, see sections 5.4.6(i), 5.4.7(i), and others.

GRL200 (Soft 033 & 037)


- 1043 -
6F2S1914 (0.37)

(i) Setting threshold level


For Standard type (BI1A and others)
The selection switch is used to adjust the threshold of an input signal; it is designated as
[THRES_Lvl]. If an external device signal is lower than DC 110V1, the user should set Low for
scheme switch [THRES_Lvl]. Conversely if an external device signal is higher than DC 220V1,
the user should set High for the scheme switch. Note that scheme switch [THRES_Lvl] is used
to control all binary input circuits. The user must ensure that the input voltage is higher than
DC 77V1 when the setting ‘Low’ is applied; the input voltage should be higher than DC 136V1
when the setting ‘High’ is applied.

For Variable type (exclusive for BI2A and BIO4A)


BI2A and BIO4A have a unique feature as a substitute for setting (i)-1 in order that the user
can determine the guaranteed-minimum-pick-up voltages (thresholds) as required. This
unique feature is performed with settings [BI1-3_PICKUP], [BI4-6_PICKUP], [BI7-9_PICKUP],
and [BI10-12_PICKUP]; every setting is applied to a group of three binary input circuits.

Provided that the user uses BI2A, then binary input circuits #1 to #3 follow the setting
[BI1-3_PICKUP] and the user should set the value between 18 to 222V DC2 for this setting. For
the setting [BI4-6_PICKUP], the above mentioned value holds true for #4 to #6 binary input
circuits; similarly the setting [BI7-9_PICKUP] is used for #7 to #9 binary input circuits; and
finally the setting [BI10-12_PICKUP] is used for #10 to #12 binary input circuits.

On the other hand, when BIO4A is used, the binary input circuits #1 to #3 follow the
setting [BI1-3_PICKUP]; and the binary input circuits #4 to #6 follow the setting [BI4-
6_PICKUP]. Since BIO4A has six binary input circuits, the other settings [BI7-9_PICKUP] and
[BI10-12_PICKUP] are not required here.

1Note: The threshold value is fixed for all binary IO module types with the exception of
BI2A and BIO4A. The user should notice that “binary IO module voltage type”
influences these values (see the 1st note in Table 5.4-1). These particular values
are found when 220V dc type is used.
2Note: In the variable type, the user can set the threshold arbitrarily between 18 to 222V
in DC, and can regulate its threshold voltage in a voltage step. Table 5.4-5 shows
the corresponding values with regard to guaranteed and typical thresholds in
response to the setting values. Note that the operation in the variable type is
segmented into ‘Operate’, ‘Intermediate’, ‘and ‘Non-operate’ areas, which are
decided by the guaranteed-pick-up, typical-pick-up, and guaranteed-drop-off
levels, as illustrated in Figure 5.4-2.

GRL200 (Soft 033 & 037)


- 1044 -
6F2S1914 (0.37)

Table 5.4-5 Guaranteed and typical thresholds in the variable type


Guaranteed levels Typical levels
Setting values [V]
Pick-up voltage [V] Drop-off voltage [V] Pick-up voltage [V]
18 17.9 10.5 14.2
19 18.5 11.1 14.8
20 19.9 12.3 16.1
21 20.5 12.9 16.7
22 to 29 21.8 14.0 17.9
30 29.3 20.8 25.0
31 to 32 30.8 22.2 26.5
33 32.5 23.7 28.1
34 to 35 34.0 25.0 29.5
36 to 37 36.0 26.8 31.4
38 to 39 37.5 28.3 32.9
40 39.2 29.8 34.5
41 to 49 40.8 31.2 36.0
50 to 52 49.8 39.4 44.6
53 to 56 53.0 42.2 47.6
57 to 59 56.3 45.3 50.8
60 to 61 59.5 48.1 53.8
62 to 63 61.8 50.2 56.0
64 to 65 63.6 51.8 57.7
66 65.9 53.9 59.9
67 to 70 66.7 54.7 60.7
71 70.1 57.7 63.9
71 to 73 70.3 57.9 64.1
74 73.2 60.6 66.9
75 to 79 74.4 61.6 68.0
80 to 83 79.7 66.4 73.0
84 to 88 83.7 70.1 76.9
89 to 92 88.2 74.0 81.1
93 to 99 92.3 77.8 85.0
100 to 106 99.4 84.2 91.8
107 to 111 106.4 90.6 98.5
112 to 113 111.4 95.0 103.2
114 to 119 114.0 97.4 105.7
120 119.3 102.3 110.8
121 to 127 121.0 103.8 112.4
128 to 130 128.0 110.1 119.0
131 130.1 112.0 121.0
132 to 135 131.9 113.7 122.8
136 to 137 135.9 117.3 126.6
138 to 141 137.1 118.3 127.7
142 to 143 141.5 122.3 131.9
144 143.9 124.5 134.2
145 to 146 144.6 125.2 134.9
147 to 151 146.1 126.5 136.3
152 to 154 151.8 131.6 141.7
155 to 161 154.4 134.0 144.2
162 161.3 140.3 150.8
163 to 165 162.6 141.4 152.0
166 to 170 165.8 144.3 155.0
171 to 173 170.6 148.6 159.6
174 to 176 173.6 151.4 162.5
177 to 183 176.3 153.8 165.0
184 to 189 183.3 160.1 171.7
190 to 193 189.7 165.9 177.8
194 to 200 193.6 169.4 181.5
201 to 203 200.3 175.5 187.9
204 to 211 203.1 178.1 190.6
212 to 221 211.5 185.7 198.6
222 222.0 195.2 208.6

GRL200 (Soft 033 & 037)


- 1045 -
6F2S1914 (0.37)

Input voltage

Operating area

Guaranteed pick up level


Intermediate area
Typical pick up level

Guaranteed drop off level

Non-operating area

Figure 5.4-2 Operating area in the variable type


Note: In practice, the pick-up voltages depend on respective binary circuits physically
This means the characteristics are not affected by the ambient conditions and the
applied voltages.

(ii) Comparison feature for contact chatter


The input circuit incorporates a comparison feature that protects against contact chatter and
this feature is configured using the setting [CMP_NUM]. Figure 5.4-3 illustrates this feature;
the comparison feature removes contact chatter. The period ‘t’ applied for the removal of contact
chatter can be configured by setting a value for [CMP_NUM]. The formula for the calculation
of ‘t’ is,
1
[CPM_NUM]×
System Frequency×12
The setting [CMP_NUM] is provided for all binary input circuits.

Actual input signal

Imported signal by
binary input circuit
t

Figure 5.4-3 Chattering countermeasure (e.g. [CMP_NUM] = 4)

GRL200 (Soft 033 & 037)


- 1046 -
6F2S1914 (0.37)

(iii) CPL switch


If the user needs to operate the CPL for binary input circuit #1, the user should set On for
scheme switch [BI1_CPL]. Conversely, the user should set Off for scheme switch [BI1_CPL] if
CPL is not required. Since the entire range of binary input circuits have CPLs, a setting of On
or Off is a pre-requisite for every binary input circuit. The number of CPL is equal to number
of binary input circuits: that is, if BI1A is selected, the number of CPLs is 18.

(iv) Delayed pick-up and delayed drop-off signal


Both an on-delay timer and an off-delay timer are provided in CPL; both are used to adjust the
timing for input signals, the user should set their respective time values for settings [On Delay
Timer] and [Off Delay Timer].

(v) Logic level inversion


The Logic inversion function can invert the input signal and is provided for each binary input
circuit; the user can invert an input signal by setting Inverse for scheme switch [INVERSE-
SW]. A setting of Normal is also provided when inversion is not required.

(vi) How to set the settings for binary input circuits


Figure 5.4-4 illustrates an example of the binary IO module arrangement for the binary input
circuit printed circuit boards (PCBs); it illustrates the setting targets are on BI1A at IO#1 and
BIO1A at IO#3. The user should key the settings with regard to BI1A and BIO1A using the
setting tables for IO_SLOT1 and IO_SLOT3. As the setting points are for BI1A and BIO1A at
IO#1 and IO#3, the user should take the setting table of the standard type (in sec. 5.4.6).

GRL200 (Soft 033 & 037)


- 1047 -
6F2S1914 (0.37)

IO#n
IO#5
IO#3
IO#1

IO#2

IO#4

IO_SLOT1 IO_SLOT3
Setting table (input) Setting table (in & out)

Setting targets: BI1–BI18


and Common. Setting targets: BI1–BI7
and Common.
a. Setting targets for BI1A (IO#1) c. Setting targets for BIO1A (IO#3)

Figure 5.4-4 BO and BIO setting tables related to IO_slot1 and IO_slot3

The setting table of section 5.4.6 is available for all binary IO modules except for BI2A
and BIO4A; thus, the user should understand and select the setting points that are relevant
to BI1A. That is, for BI1A the user should choose the setting items of reference (i.e., binary
input circuits #1 to #18) from IO_SLOT1 setting table. On the other hand, for BIO1A the user
should choose the setting items of reference (i.e., binary input circuits #1 to #7) from IO_SLOT3
setting table. The IO_SLOT3 setting table for the binary input circuits are shown in sec. 5.4.6.
The setting operation via the IED screen is discussed later. (See chapter User interface: I/O
setting sub-menu)

GRL200 (Soft 033 & 037)


- 1048 -
6F2S1914 (0.37)

5.4.3 Binary output feature


A binary output circuit (BO) along with the CPL drives a single contact. There are five types
of BOs; different types of BOs are provided which are suitable for controlling the speed and
capacity of current in a variety of external devices, as listed below:
(1) Fast operating
(2) Semi-fast operating
(3) Hybrid
(4) Auxiliary
(5) BO with Form-C

The arrangement of the BO types is determined for every binary IO module, as shown in
Table 5.4-1 and Table 5.4-6. The difference in the types and number of BOs are also found in
section 5.4.5.

GRL200 (Soft 033 & 037)


- 1049 -
6F2S1914 (0.37)

Table 5.4-6 Output circuits and features associated with binary IO module
No Type Binary output feature Example Symbol Applied
sign module
1 Fast -Normally open (N/O) Terminal screw BIO3A
-Dry contact BO1(F) number
operating
-Closure is the fastest 1
(F) amongst all of the BO types. 2
Type
-Make & Carry: 5A cont.
BO number
-Break: 0.15A at 290Vdc
-OP Time: 3ms (typical) N/O contact

2 Semi-fast -Normally open (N/O) BO1A


Screw on terminal block
-Dry contact BO1(SF)
operating BIO1A
-Closure is faster than
(SF) normal. BIO2A
Type
-Make and carry: 8A cont. BO number
-Break: 0.1A at 250Vdc
0.2A at 125Vdc
-OP Time: 6ms (typical)
3 Hybrid -Normally open (N/O) Terminal screw BO2A
-Polarity dependent BO1(H) number
(H) (+) BIO4A
-Interruption capability for 1
(−)
high-current (up to 10A) 2
Type
-Consisting of an IGBT BO number
device and a contact
-Make and carry: 8A cont. N/O
-Break: 10A at 220/110Vdc
Screw on terminal block
-OP Time: 1ms
4 Auxiliary -Normally open (N/O) Terminal screw BO1A
-Dry contact BO1 number
BIO1A
-Normal speed closure 1

-Make and carry: 8A cont. 2 BIO2A


-Break: 0.1A at 250Vdc BO number BIO3A
0.2A at 125Vdc
-OP Time: 8ms (typical) N/O contact

Screw on terminal block

5 Form-C -Uses a N/C and a N/O Terminal screw number BIO2A


contact BO1
BIO3A
-Shares a common 35

connections BIO4A
37
-Make and carry: 8A cont. BO number
36
-Break: 0.1A at 250Vdc N/O
0.2A at 125Vdc 38
-OP Time: 8ms (typical) N/C

Contact

Screw on terminal block

GRL200 (Soft 033 & 037)


- 1050 -
6F2S1914 (0.37)

5.4.4 Binary output circuit


Either a CPL logic or a PLC signal can drive a binary output circuit. Table 5.4-7 shows the
settings summary of CPL function.
Table 5.4-7 Setting items in binary output circuits
Setting-range or

Unit
Setting items Contents Default
Data_ID
BO1_CPL Off / On – Switch On for programmable operation Off
BO1 Input signal1 (Preferred Data ID) – Set a Data ID at the first input on BO1. Not assigned1
Input signal2 (Preferred Data ID) – Set a Data ID at the second input on BO1. Not assigned1
Input signal3 (Preferred Data ID) – Set a Data ID at the third input on BO1. Not assigned1
Input signal4 (Preferred Data ID) – Set a Data ID at the forth input on BO1. Not assigned1
Input signal5 (Preferred Data ID) – Set a Data ID at the fifth input on BO1. Not assigned1
Input signal6 (Preferred Data ID) – Set a Data ID at the sixth input on BO1. Not assigned1
Input signal7 (Preferred Data ID) – Set a Data ID at the seventh input on BO1. Not assigned1
Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BO1. Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BO1 AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BO1 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BO1 0.000
INVERSE-SW Normal / Inverse s Inversion operation of BO1 signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO1 OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1
BO2_CPL Off / On – Switch On for programmable operation Off
BO2 Input signal1 (Preferred Data ID) – Set a Data ID at the first input on BO2. Not assigned1
….. ….. ….. …..
Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BO2 Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BO2 AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BO2 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BO2 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BO2 signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO2 OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1

…..

BOn_CPL Off / On – Switch On for programmable operation Off


BOn Input signal1 (Preferred Data ID) – Set a Data ID at the first input on BOn Not assigned1

….. ….. ….. …..

Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BOn Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BOn AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BOn 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BOn 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BOn signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BOn OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1
1Note: The user can set a reset signal and eight input signals with Data IDs. Data IDs
are listed as a signal monitoring point for each function. Setting items are
summarized in each slot. (See sections 5.4.8(i) and 5.4.8(ii))

GRL200 (Soft 033 & 037)


- 1051 -
6F2S1914 (0.37)

Figure 5.4-5 shows the binary output circuits on BO1A in order to help understand the
settings. BO1A consists of 18 binary output circuits and every circuit has timers and switches.
The features of the CPLs are divided into the five components as listed below:
CPL switch
Selection of input signals
Logic gate switch
Delayed pick-up/delayed drop-off
Logic level inversion
Logic timer switch
From relay
application and To external
control functions devices
8002001112 Contact
On Delay Timer Off Delay Timer
[LOGIC-SW] & ≥1
t 0 0 t BO1
Input signal 1 DRIVER BO1
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR & 8002001113
≥1 [INVERSE-SW]
Normal
Off
Inverse On &
XOR Delay &
0.000-300.000s [BO1_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal

310200E11D BO1-SOURCE

810201112 Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BO2
Input signal 1 t 0 0 t DRIVER BO2
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR &
810201113
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BO2 RB
XOR Delay &
0.000-300.000s [BO2_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal

310201E11D BO2-SOURCE

820202112 Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BO3
Input signal 1 t 0 0 t DRIVER BO3
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR & 8202021113
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BO3 RB
XOR Delay &
0.000-300.000s [BO3_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal

310202E11D BO3-SOURCE

8********* Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BOn
Input signal 1 t 0 0 t DRIVER BOn
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR &
8*********
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BOn RB
XOR Delay &
0.000-300.000s [BOn_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal

3102E**11D BOn-SOURCE

Figure 5.4-5 Binary Output Circuit for BO1A (#1 to #n=18)

In Figure 5.4-5 respective element IDs (i.e., 8002001112 and others) designate respective
signal monitoring points of the binary output circuits. The user can monitor the operations of

GRL200 (Soft 033 & 037)


- 1052 -
6F2S1914 (0.37)

the binary output circuit using element ID together with function ID. When we assume that
BO1A module is at IO#2 slot in the IED case, and if the user wishes to monitor the first-circuit
in the BO1A module, the user can see the operation using the element ID (8002001112) and
the function ID† of IO#2 slot.

†Note: A function ID identifies every IO slots. For example, with regard to the function
ID and the Data ID at IO#1 slot, see section 5.4.9(i). On the other hand, for IO#2
slot see section 5.4.9(ii).

(i) CPL switch


When the user needs to operate the CPL for binary output circuit #1, the user should set On
for the scheme switch [BO1_CPL]. Conversely, the user should set Off for the scheme switch
[BO1_CPL] if CPL is not required. Since all binary output circuits have CPLs setting between
On and Off is required for every binary output circuit. The number of CPL is equal to the
number of binary output circuits: that is, if the BO1A module is selected, the number of CPLs
is 18. Note that the subsequent PLC settings described later require that Off be set for the
scheme switch.

(ii) Selection of input signals


Since a binary input circuit is operated by commands introduced from other functions, eight
ports for input signals are provided, designated as input-signal1 to input-signal8. The user
must ensure that input-signal1 to input-signal8 are configured with eight DataIDs. That is,
the user can select input-signals that are available from other functions, these input-signals
are designated using DataIDs. The user can key the DataIDs into settings [Input signal1] to
[Input signal8]. The DataIDs are selected from the Signal monitoring point list, which is
provided for every function.

(iii) Logic gate switch


A binary input circuit has a logic scheme for the eight input signals, and can combine the eight
input signals as required using scheme switch [LOGIC-SW] for which the user should set either
AND, OR or XOR.

(iv) Delayed pick-up/delayed drop-off signal


An on-delay timer and an off-delay timer are provided in the CPL; both are used to adjust the
timing for binary output circuits, the user should set their respective time values for settings
[On Delay Timer] and [Off Delay Timer].

(v) Logic level inversion


The logic inversion function can invert the input signal for each binary output circuit; the user

GRL200 (Soft 033 & 037)


- 1053 -
6F2S1914 (0.37)

can invert an input output when the user sets Inverse for the scheme switch [INVERSE-SW].
Normal setting is also provided when logic inversion is not required for processing.

(vi) Logic timer switch


In order that the binary output circuit can have a programmable reset characteristic, a scheme
switch and a setting are provided. The programmable reset characteristic consists of four types
and the user can select the type required using a scheme switch: (1) dwell type, (2) delay type,
(3) latch type, and (4) instantaneous type:

Instant type
When the user uses a binary output signal without the following characteristics, the user
should set Off for the scheme switch [TIMER-SW].

Delay type
If the user requires a binary output signal with a delayed characteristic, the user should set
Delay for scheme switch [TIMER-SW] and set the value of the pulse width using setting [Logic
timer].

Dwell type
For instance, if the user requires a binary output signal as a one shot pulse, the user should
set Dwell for scheme switch [TIMER-SW] and set the value of the pulse width using setting
[Logic timer]. If the input signals received have a shorter duration than the set value in the
setting [Logic timer], the pulse width will be equal to the setting value. On the other hand, if
the duration of the input signals are longer than that of the set value, the pulse width will be
equal to the width of the input signals.

Latch type
If the user requires a binary output signal to be removed by a reset signal, the user should set
Latch for scheme switch [TIMER-SW] and key the Data ID of the reset signal for setting [Reset
signal]. Since the binary output signal is removed with the Data ID, the user should determine
the Data ID from other functions. The Data ID is designated by the signal monitoring point for
each function and the user should set the [Reset signal] setting.
Note: When Latch is set, the state of BO circuit will be sustained during power turn-
on/off.

GRL200 (Soft 033 & 037)


- 1054 -
6F2S1914 (0.37)

(vii) How to set the settings for binary output circuits

IO#n
IO#3

IO#5
IO#1

IO#4
IO#2

BO1A BIO1A

IO_SLOT2 IO_SLOT3
Setting table (output) Setting table (in & out)

Setting targets: BO1–BO18 Setting targets: BO1–BO10


b. Setting targets for BO1A (IO#2) c. Setting targets for BIO1A (IO#3)

Figure 5.4-6 BO and BIO modules and setting tables related to IO_SLOT2 and IO_SLOT3
Figure 5.4-6 illustrates an example of a binary IO module arrangement and the binary
output circuit printed circuit boards (PCBs). If the user wishes to set the binary output circuits,
the setting targets are on BO1A and BIO1A at locations IO#2 and IO#3. The user should key
the CPL settings from the setting tables for the IO2_SLOT and IO3_SLOT.

The setting table is available for all binary IO modules; thus, the user should understand
and select setting points that are relevant to BO1A and BIO1A. That is, for BO1A the user
should choose the setting terms of reference (i.e., binary output circuits #1 to #18) from

GRL200 (Soft 033 & 037)


- 1055 -
6F2S1914 (0.37)

IO_SLOT2. On the other hand, for BIO1A, the setting terms of reference (i.e., binary output
circuits #1 to #10) are from IO_SLOT3. These setting tables are shown in section 5.4.8(ii).

(viii) PLC and the binary output circuits


The Programmable logic controller (PLC) is also available for the control of binary output
circuits as a substitute for the CPL, and is able to signal an output command directly. In the
case that the binary output circuit is controlled by the PLC, the user is required to connect the
PLC to the binary output circuit. In Figure 5.4-5, the PLC logic connection points are
designated with BO1-SOURCE, BO2-SOURCE, and others. (The PLC is discussed separately.
Note that Connection points on the PLC are shown with the DataIDs of BIO_SLOT. See section
5.4.9(i)-3 and 5.4.9(ii)-3. (For more information of PLC function, see Chapter PLC function)

GRL200 (Soft 033 & 037)


- 1056 -
6F2S1914 (0.37)

5.4.5 Structure of binary IO Module


Binary IO modules consist of a number of module types and the arrangement of the respective
inputs-and-outputs are particular to each binary IO module type, as shown in Figure 5.4-7 to
Figure 5.4-11. Referring to the figures on the left, the user can for example, identify the actual
terminal blocks of the binary IO module. Corresponding circuits are drawn on the right in the
form of schematic diagrams. If the wiring of BI1A is considered, the wiring objects are
designated with terminal screw numbers 1 to 40. The terminal screw numbers are shown next
to the terminal blocks. Here the user can find a slot number labeled with alpha-numeric
reference “T*”. The asterisk sign (*) is substituted for any one of the slot numbers. For the
actual implementation of a binary IO module, the user should examine the arrangement of
binary IO modules from External connection figures, which are shown separately. (See
Appendix: Typical external connection)

Note that some input and output circuits have polarity, which is designated with either
a plus sign (+) or a minus sign (−) respectively.

GRL200 (Soft 033 & 037)


- 1057 -
6F2S1914 (0.37)

Alpha-numeric reference for the BI. Sign “*”


is substituted for the actual slot location
number.

T* T*
Screw
BI1A BI3A
T*
(+) 1 (+) 1 (
1
2 BI1 2 BI1
2 (−) (+) BI2 (
(+) 3 (+) 3
3
4 BI2 4 BI3
4 (−) (+) BI4
(+) 5 (+) 5 (
5 BI3 BI5
6 (−) 6 (+) 6 (
7 7 BI6
7 (+) (+) BI7 (
8 BI4 8
8 (−) (+) (
9 9 BI8
9 (+) (+)
10 BI5 10 BI9
10 (−) (+)
11 11 BI10
11 (+) (+) (
12 BI6 12 BI11
12 (−) (+) (
13 13 BI12
13 (+) (+) (
14 BI7 14 BI13
14 (−) (+) (
15 15 BI14
15 (+) (+)
16 BI8 16 BI15
16 (−) (+)
17 17 BI16
17 (+) (+) (
18 BI9 18 BI17
18 (−) (+) (
BI18
19
20 The same terminal screw
is denoted with the same
number.

21 (+) 21 (+) 21 (+
22 BI10 22 BI19
22 (−) (+) BI20 (−
23 (+) 23 (+) 23
24 BI11 24 BI21
24 (−) (+)
25 25 BI22
25 (+) (+) (+
26 BI12 26 BI23
26 (−) (+) (−
27 27 BI24
27 (+) (+) (+
28 BI13 28 BI25
28 (−) (+) (−
29 29 BI26
29 (+) (+)
30 BI14 30 BI27
30 (−) (+)
31 31 BI28
31 (+) (+) (+
32 BI15 32 BI29
32 (−) (+) (−
33 33 33 BI30
(+) (+) BI31 (+
34 (−) 34 BI16 34
(+) BI32 (−
35 (+) 35 (−) 35
36 (−) 36 BI17 36
(−)
37 (+) 37 (−) 37 (+
38 (−) 38 BI18 38
(−) (−
39
40

Terminal blocks Schematic figures

Figure 5.4-7 Input arrangements for BI1A and BI3A


Note: For more detailed circuit information, refer to Table 5.4-2 or Table 5.4-6.

GRL200 (Soft 033 & 037)


- 1058 -
6F2S1914 (0.37)

Alpha-numeric reference for the BI. Sign “*”


is substituted for the actual slot location
number.

T*
The same terminal screw is denoted with
Screw the same number.
BI2A
T*
(+) 1
1 BI1
(−) 2
2
3
4
5 (+) 5
(−) 6 BI2
6
7 (+) 7
(−) 8 BI3
8
9
10
11 (+) 11
(−) 12 BI4
12
13 (+) 13
(−) 14 BI5
14
15
16
17 (+) 17
18 18 BI6
(−)
19
20

21 (+) 21 BI7
22 (−) 22
23
24
25 (+) 25
26 26 BI8
(−)
27 (+) 27
28 28 BI9
(−)
29
30
31 (+) B31
32 B32 BI10
(−)
33 (+) B33
34 B34 BI11
(−)
35
36
37 (+) B37
BI12
38 (−) B38
39
40

Terminal blocks Schematic figures

FG

Figure 5.4-8 Input arrangements for BI2A


Note: For more detailed circuit information, refer to Table 5.4-2 or Table 5.4-6. Note that
the FG cable (Bold line) is required.
Note: FG cables between BI circuits (drawn in Thin dashed lines) are required in a BI2A
module manufactured in 2017 or earlier. To know the manufactured year, see the
Hardware nameplate.

GRL200 (Soft 033 & 037)


- 1059 -
6F2S1914 (0.37)

Alpha-numeric reference for BO. Sign “*” is substituted for


the slot location number.
T* T*

BO1A BO2A
T*
1 1 1
(+)
2 BO1(SF) 2 BO1(H) 2
(−)
3 3 3
(+)
4 BO2(SF) 4 BO2(H) 4
(−)
5 5 5
(+)
6 BO3(SF) 6 BO3(H) 6
(−)
7 7 7
(+)
8 BO4(SF) 8 BO4(H) 8
(−)
9 9 9
(+)
10 BO5(SF) 10 BO5(H) 10
(−)
11 11 11
(+)
12 BO6(SF) 12 BO6(H) 12
(−)
13 13 13
(+)
14 BO7 14 BO7(H) 14
(−)
15 15 15
(+)
16 BO8 16 BO8(H) 16
(−)
17 17 17
(+)
18 BO9 18 BO9(H) 18
(−)
19
20 The same terminal
screw is denoted
with the same
number.
21 21 21 (+)
22 BO10 22 BO10(H) 22 (−)
23 23 23 (+)
24 BO11 24 BO11(H) 24 (−)
25 25 25 (+)
26 BO12 26 BO12(H) 26 (−)
27 27 27 (+)
28 BO13 28 BO13(H) 28 (−)
29 29 29 (+)
30 BO14 30 BO14(H) 30 (−)
31 31 31 (+)
32 BO15 32 BO15(H) 32 (−)
33 33 33 (+)
34 BO16 34 BO16(H) 34 (−)
35 35
36 BO17 36
37 37
38 BO18 38
39
40

Terminal blocks Schematic figures

Figure 5.4-9 Output arrangements in BO1A and BO2A


Note: For more detailed circuit information, refer to Table 5.4-2 or Table 5.4-6.

GRL200 (Soft 033 & 037)


- 1060 -
6F2S1914 (0.37)

Alpha-numeric reference of BIO. Sign “*” is


substituted for the actual slot location number.

T* T*

BIO1A BIO2A

T* (+) 1 1
BI1 (+) BI1
1 (−) 2 (−) 2
2 (+) 3 (+) 3
4 BI2 4 BI2
3 (−) (−)
4 (+) 5 (+) 5
6 BI3 6 BI3
5 (−) (−)
6 (+) 7 7
BI4 (+) BI4
7 (−) 8 (−) 8
8 (+) 9 (+) 9
9 10 BI5 10 BI5
(−) (−)
10 (+) 11 (+) 11
11 12 BI6 12 BI6
(−) (−)
12 (+) 13 13
BI7 (+) BI7
13 (−) 14 (−) 14
14 15 15
BO1(SF) (+) BI8
15 16 16
17 (−)
16 (+) 17
17 BO2(SF) 18 18 BI9
(−)
18
19
20

The same terminal


21 21 21
screw is denoted with BO3(SF) (+)
22 22 22 BI10
the same number. (−)
23 23 23
BO4(SF) 24 (+) 24 BI11
24 (−)
25 25 25
BO5(SF) 26 (+) 26 BI12
26 (−)
27 27 27
BO6(SF) 28 BO1(SF) 28
28
29 29 29
BO7 30 BO2(SF) 30
30
31 31 31
32 BO8 32 BO3(SF) 32
33 33 33
34 BO9 34 BO4 34
35
36 35 35
37 37 37
38 BO10 36 BO5 36
39
40 38 38

Terminal blocks Schematic figures

Figure 5.4-10 Input and output arrangements in BIO1A and BIO2A


Note: For more detailed circuit information, refer to Table 5.4-2 or Table 5.4-6.

GRL200 (Soft 033 & 037)


- 1061 -
6F2S1914 (0.37)

Alpha-numeric of BIO. Sign “*” is substituted


for the actual slot location number. T* T*

BIO3A BIO4A
T* 1 1
1 (+) (+)
2 BI1 2 BI1
2 (−) (−)
(+) 3 (+) 3
3 BI2 BI2
(−) 4 (−) 4
4
(+) 5 (+) 5
5 BI3 BI3
(−) 6 (−) 6
6
(+) 7 (+) 7
7 BI4 BI4
(−) 8 (−) 8
8
(+) 9 (+) 9
9 BI5 BI5
(−) 10 (−) 10
10
(+) 11 (+) 11
11 BI6 BI6
12 (−) 12 (−) 12
13 (+) 13
14 BI7
14 (−)
15 (+) 15
16 BI8
16 (−) 17 (+)
17 BO1(H) 18 (−)
18
19
20 The same terminal screw
is denoted with the same
number.

21 21 21 (+)
BO1(F) 22 BO2(H) 22
22 (−)
23 23 23 (+)
BO2(F) 24 BO3(H) 24
24 (−)
25 25 25 (+)
BO3(F) 26 BO4(H) 26
26 (−)
27 27 27 (+)
BO4(F) 28 BO5(H) 28
28 (−)
29 29 29 (+)
BO5(F) 30 BO6(H) 30
30 (−)
31 31
32 BO6(F) 32
33 33 33
34 BO7 34 BO7 34
35
36 35 35
37 37 37
38 BO8 36 BO8 36
39
40 38 38

Terminal blocks Schematic figures

Figure 5.4-11 Input and output arrangements in BIO3A and BIO4A

Note: PHOENIX CONTACT ® is the manufacturer of the terminal block. The model of
this terminal is described as “FRONT-MSTB 2.5/20-STF 5.08”. The user can
connect a cable to this terminal directly without a cable ferrule; hence, the
recommended cables are AWG14 and their stripping lengths are 10mm. Use a
cable ferrule made in PHOENIX CONTACT ® when required.

GRL200 (Soft 033 & 037)


- 1062 -
6F2S1914 (0.37)

5.4.6 Settings of binary input circuits


(i) Setting table (IO_SLOT1) at IO#1 (Function ID: 200B01)
For the standard type being furnished
Unit Default setting
Setting item Range Contents Notes
s value

Common THRES_Lvl Low / High - Determination of input threshold Low


CMP_NUM 4-9 - Number of times filtered 4
BI1 BI1_CPL Off / On - Programmable binary input enable Off
On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal
BI2 BI2_CPL Off / On - Programmable binary input enable Off
On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal

…… …… …… …… ……

BI32 BI32_CPL Off / On - Programmable binary input enable Off


On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal

For the variable type being furnished


Unit Default setting
Setting item Range Contents Notes
s value

Common THRES_Lvl Low / High - Determination of input threshold Low


Threshold through BI1 to BI3
THRES_Grp1 10 - 220 V Applicable only in BI-2 module and 75
BIO-4 module
Threshold through BI4 to BI6
THRES_Grp2 10 - 220 V Applicable only in BI-2 module and 75
BIO-4 module
Threshold through BI7 to BI9
THRES_Grp3 10 - 220 V Applicable only in BI-2 module and 75
BIO-4 module
Threshold through BI10 to BI12
THRES_Grp4 10 - 220 V Applicable only in BI-2 module and 75
BIO-4 module
CMP_NUM 4-9 - Number of times filtered 4
BI1 BI1_CPL Off / On - Programmable binary input enable Off
On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal
BI2 BI2_CPL Off / On - Programmable binary input enable Off
On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal

…… …… …… …… ……

BI12 BI12_CPL Off / On - Programmable binary input enable Off


On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal

GRL200 (Soft 033 & 037)


- 1063 -
6F2S1914 (0.37)

(ii) Setting tables (IO_SLOT2 to SLOTn) at IO#2 to IO#n (Function ID:


200B02 to 200B0n)
For the standard type being furnished
Setting table is the same as the table for the IO#1 (in previous section (i)-1)

For the variable type being furnished


Setting table is the same as the table for the IO#2 (in previous section (i)-2)

GRL200 (Soft 033 & 037)


- 1064 -
6F2S1914 (0.37)

5.4.7 Signals (Data ID) of binary input circuits


(i) Table (IO_SLOT1) at IO#1 (Function ID: 200B01)
Before the filer
 Signal monitoring points (before the filter)
Element ID Name Description
8001001111 BI1-NC BI1 signal without filter

8101011111 BI2-NC BI2 signal without filter

8201021111 BI3-NC BI3 signal without filter

8301031111 BI4-NC BI4 signal without filter

8401041111 BI5-NC BI5 signal without filter

8501051111 BI6-NC BI6 signal without filter

8601061111 BI7-NC BI7 signal without filter

8701071111 BI8-NC BI8 signal without filter

8801081111 BI9-NC BI9 signal without filter

8901091111 BI10-NC BI10 signal without filter

8A010A1111 BI11-NC BI5 signal without filter

8B010B1111 BI12-NC BI7 signal without filter

8C010C1111 BI13-NC BI9 signal without filter

8D010D1111 BI14-NC BI11 signal without filter

8E010E1111 BI15-NC BI13 signal without filter

8F010F1111 BI16-NC BI15 signal without filter

8001101111 BI17-NC BI17 signal without filter

8101111111 BI18-NC BI18 signal without filter

8201121111 BI19-NC BI19 signal without filter

8301131111 BI20-NC BI20 signal without filter

8401141111 BI21-NC BI21 signal without filter

8501151111 BI22-NC BI22 signal without filter

8601161111 BI23-NC BI23 signal without filter

8701171111 BI24-NC BI24 signal without filter

8801181111 BI25-NC BI25 signal without filter

8901191111 BI26-NC BI26 signal without filter

8A011A1111 BI27-NC BI27 signal without filter

8B011B1111 BI28-NC BI28 signal without filter

8C011C1111 BI29-NC BI29 signal without filter

8D011D1111 BI30-NC BI30 signal without filter

8F011F1111 BI32-NC BI31 signal without filter

8E011E1111 BI31-NC BI32 signal without filter

After the filter


 Signal monitoring points (after the filer)
Element ID Name Description
8001001110 BI1 BI1 signal with filter

8101011110 BI2 BI2 signal with filter

8201021110 BI3 BI3 signal with filter

8301031110 BI4 BI4 signal with filter

8401041110 BI5 BI5 signal with filter

GRL200 (Soft 033 & 037)


- 1065 -
6F2S1914 (0.37)

 Signal monitoring points (after the filer)


Element ID Name Description
8501051110 BI6 BI6 signal with filter

8601061110 BI7 BI7 signal with filter

8701071110 BI8 BI8 signal with filter

8801081110 BI9 BI9 signal with filter

8901091110 BI10 BI10 signal with filter

8A010A1110 BI11 BI11 signal with filter

8B010B1110 BI12 BI12 signal with filter

8C010C1110 BI13 BI13 signal with filter

8D010D1110 BI14 BI14 signal with filter

8E010E1110 BI15 BI15 signal with filter

8F010F1110 BI16 BI16 signal with filter

8001101110 BI17 BI17 signal with filter

8101111110 BI18 BI18 signal with filter

8201121110 BI19 BI19 signal with filter

8301131110 BI20 BI20 signal with filter

8401141110 BI21 BI21 signal with filter

8501151110 BI22 BI22 signal with filter

8601161110 BI23 BI23 signal with filter

8701171110 BI24 BI24 signal with filter

8801181110 BI25 BI25 signal with filter

8901191110 BI26 BI26 signal with filter

8A011A1110 BI27 BI27 signal with filter

8B011B1110 BI28 BI28 signal with filter

8C011C1110 BI29 BI29 signal with filter

8D011D1110 BI30 BI30 signal with filter

8E011E1110 BI31 BI31 signal with filter

8F011F1110 BI32 BI32 signal with filter

The ends of binary input circuits


 Signal monitoring points (at the end of binary input circuit)
Element ID Name Description
8001001172 BI1-CPL BI1 signal with filter and programmable logic

8101011172 BI2-CPL BI2 signal with filter and programmable logic

8201021172 BI3-CPL BI3 signal with filter and programmable logic

8301031172 BI4-CPL BI4 signal with filter and programmable logic

8401041172 BI5-CPL BI5 signal with filter and programmable logic

8501051172 BI6-CPL BI6 signal with filter and programmable logic

8601061172 BI7-CPL BI7 signal with filter and programmable logic

8701071172 BI8-CPL BI8 signal with filter and programmable logic

8801081172 BI9-CPL BI9 signal with filter and programmable logic

8901091172 BI10-CPL BI10 signal with filter and programmable logic

8A010A1172 BI11-CPL BI11 signal with filter and programmable logic

8B010B1172 BI12-CPL BI12 signal with filter and programmable logic

8C010C1172 BI13-CPL BI13 signal with filter and programmable logic

8D010D1172 BI14-CPL BI14 signal with filter and programmable logic

GRL200 (Soft 033 & 037)


- 1066 -
6F2S1914 (0.37)

 Signal monitoring points (at the end of binary input circuit)


Element ID Name Description
8E010E1172 BI15-CPL BI15 signal with filter and programmable logic

8F010F1172 BI16-CPL BI16 signal with filter and programmable logic

8001101172 BI17-CPL BI17 signal with filter and programmable logic

8101111172 BI18-CPL BI18 signal with filter and programmable logic

8201121172 BI19-CPL BI19signal with filter and programmable logic

8301131172 BI20-CPL BI20ignal with filter and programmable logic

8401141172 BI21-CPL BI21 signal with filter and programmable logic

8501151172 BI22-CPL BI22 signal with filter and programmable logic

8601161172 BI23-CPL BI23 signal with filter and programmable logic

8701171172 BI24-CPL BI24 signal with filter and programmable logic

8801181172 BI25-CPL BI25 signal with filter and programmable logic

8901191172 BI26-CPL BI26 signal with filter and programmable logic

8A011A1172 BI27-CPL BI27 signal with filter and programmable logic

8B011B1172 BI28-CPL BI28 signal with filter and programmable logic

8C011C1172 BI29-CPL BI29 signal with filter and programmable logic

8D011D1172 BI30-CPL BI30 signal with filter and programmable logic

8E011E1172 BI31-CPL BI31 signal with filter and programmable logic

8F011F1172 BI32-CPL BI32 signal with filter and programmable logic

(ii) Tables (IO_SLOT2 to SLOTn) at IO#2 to IO#n


(Function ID: 200B02 to 200B0n)
Before the filter
Table is the same as the table in previous section (i)-1.

After the filter


Table is the same as the table in previous section (i)-2.

The ends of binary input circuits


Table is the same as the table in previous section (i)-3.

GRL200 (Soft 033 & 037)


- 1067 -
6F2S1914 (0.37)

5.4.8 Settings of binary output circuits


(i) Setting table (IO_SLOT1) at IO#1 (Function ID 200B01)
Default setting

Units
Setting item Range Contents Notes
value

BO1 BO1_CPL Off / On - Programmable binary output enable Off


Input signal1 (Data-ID from other FBs) - First Data ID as input signal #1 for Logic gate Not assigned
Input signal2 ditto - Second Data ID as input signal #2 for Logic gate Not assigned
Input signal3 ditto - Third Data ID as input signal #3 for Logic gate Not assigned
Input signal4 ditto - Forth Data ID as input signal #4 for Logic gate Not assigned
Input signal5 ditto - Fifth Data ID as input signal #5 for Logic gate Not assigned
Input signal6 ditto - Sixth Data ID as input signal #6 for Logic gate Not assigned
Input signal7 ditto - Seventh Data ID as input signal #7 for Logic gate Not assigned
Input signal8 ditto - Eighth Data ID as input signal #8 for Logic gate Not assigned
LOGIC-SW AND / OR / XOR - Operation selection in Logic gate AND
On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal
TIMER-SW Off / Delay / Dwell / Latch - Selection of Logic circuit Off
Off delay timer value for "Delay" and "Dwell"
Logic Timer 0.000 - 300.000 s 0.000
circuit
Reset signal (Data-ID from other FBs) - Reset signal selection for "Latch" circuit Not assigned
BO2 BO2_CPL Off / On - Programmable binary output enable Off
Input signal1 (Data-ID from other FBs) - Keying Data ID#1 as input signal for Logic gate Not assigned
Input signal2 ditto - Keying Data ID#2 as input signal for Logic gate Not assigned
Input signal3 ditto - Keying Data ID#3 as input signal for Logic gate Not assigned
Input signal4 ditto - Keying Data ID#4 as input signal for Logic gate Not assigned
Input signal5 ditto - Keying Data ID#5 as input signal for Logic gate Not assigned
Input signal6 ditto - Keying Data ID#6 as input signal for Logic gate Not assigned
Input signal7 ditto - Keying Data ID#7 as input signal for Logic gate Not assigned
Input signal8 ditto - Keying Data ID#8 as input signal for Logic gate Not assigned
LOGIC-SW AND / OR / XOR - Operation selection in Logic gate AND
On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal
TIMER-SW Off / Delay / Dwell / Latch - Selection of Logic circuit Off
Off delay timer value for "Delay" and "Dwell"
Logic Timer 0.000 - 300.000 s 0.000
circuit
Reset signal (Data-ID from other FBs) - Reset signal selection for "Latch" circuit Not assigned

….. …… ……. ……. ……..

BO18 BO18_CPL Off / On - Programmable binary output enable Off


Input signal1 (Data-ID from other FBs) - Keying Data ID#1 as input signal for Logic gate Not assigned
……. ……. ……. …….
Input signal8 ditto - Keying Data ID#8 as input signal for Logic gate Not assigned
LOGIC-SW AND / OR / XOR - Operation selection in Logic gate AND
On Delay Timer 0.000 - 300.000 s On delay timer value 0.000
Off Delay Timer 0.000 - 300.000 s Off delay timer value 0.000
INVERSE-SW Normal / Inverse - Binary signal inversion Normal
TIMER-SW Off / Delay / Dwell / Latch - Selection of Logic circuit Off
Off delay timer value for "Delay" and "Dwell"
Logic Timer 0.000 - 300.000 s 0.000
circuit
Reset signal (Data-ID from other FBs) - Reset signal selection for "Latch" circuit Not assigned

GRL200 (Soft 033 & 037)


- 1068 -
6F2S1914 (0.37)

(ii) Setting tables (IO_SLOT2 to SLOTn) at IO#2 to IO#n (Function ID


200B02 to 200B0n)
Setting table is the same as the table for the IO#1 (in section (i))

GRL200 (Soft 033 & 037)


- 1069 -
6F2S1914 (0.37)

5.4.9 Signals (Data ID) of binary output circuits


(i) Table (IO_SLOT1) at IO#1 (Function ID: 200B01)
Before the contact-driver
 Signal monitoring points (before the contact-driver)
Element ID Name Description
8002001112 BO1 BO1 signal

8102011112 BO2 BO2 signal

8202021112 BO3 BO3 signal

8302031112 BO4 BO4 signal

8402041112 BO5 BO5 signal

8502051112 BO6 BO6 signal

8602061112 BO7 BO7 signal

8702071112 BO8 BO8 signal

8802081112 BO9 BO9 signal

8902091112 BO10 BO10 signal

8A020A1112 BO11 BO11 signal

8B020B1112 BO12 BO12 signal

8C020C1112 BO13 BO13 signal

8D020D1112 BO14 BO14 signal

8E020E1112 BO15 BO15 signal

8F020F1112 BO16 BO16 signal

8002101112 BO17 BO17 signal

8102111112 BO18 BO18 signal

After the contact-driver


 Signal monitoring points (after the contact-driver)
Element ID Name Description
8002001113 BO1 RB BO1 driver read signal

8102011113 BO2 RB BO2 driver read signal

8202021113 BO3 RB BO3 driver read signal

8302031113 BO4 RB BO4 driver read signal

8402041113 BO5 RB BO5 driver read signal

8502051113 BO6 RB BO6 driver read signal

8602061113 BO7 RB BO7 driver read signal

8702071113 BO8 RB BO8 driver read signal

8802081113 BO9 RB BO9 driver read signal

8902091113 BO10 RB BO10 driver read signal

8A020A1113 BO11 RB BO11 driver read signal

8B020B1113 BO12 RB BO12 driver read signal

8C020C1113 BO13 RB BO13 driver read signal

8D020D1113 BO14 RB BO14 driver read signal

8E020E1113 BO15 RB BO15 driver read signal

8F020F1113 BO16 RB BO16 driver read signal

8002101113 BO17 RB BO17 driver read signal

8102111113 BO18 RB BO18 driver read signal

GRL200 (Soft 033 & 037)


- 1070 -
6F2S1914 (0.37)

Connection points for the PLC


 Connection point in PLC logic
Element ID Name Description
310200E11D BO1-SOURCE BO1 output command by PLC-logic

310201E11D BO2-SOURCE BO2 output command by PLC-logic

310202E11D BO3-SOURCE BO3 output command by PLC-logic

310203E11D BO4-SOURCE BO4 output command by PLC-logic

310204E11D BO5-SOURCE BO5 output command by PLC-logic

310205E11D BO6-SOURCE BO6 output command by PLC-logic

310206E11D BO7-SOURCE BO7 output command by PLC-logic

310207E11D BO8-SOURCE BO8 output command by PLC-logic

310208E11D BO9-SOURCE BO9 output command by PLC-logic

310209E11D BO10-SOURCE BO10 output command by PLC-logic

31020AE11D BO11-SOURCE BO11 output command by PLC-logic

31020BE11D BO12-SOURCE BO12 output command by PLC-logic

31020CE11D BO13-SOURCE BO13 output command by PLC-logic

31020DE11D BO14-SOURCE BO14 output command by PLC-logic

31020EE11D BO15-SOURCE BO15 output command by PLC-logic

31020FE11D BO16-SOURCE BO16 output command by PLC-logic

310210E11D BO17-SOURCE BO17 output command by PLC-logic

310211E11D BO18-SOURCE BO18 output command by PLC-logic

(ii) Tables (IO_SLOT2 to SLOTn) at IO#2 to IO#n (Function ID: 200B02 to


200B0n)
Before the contact-driver
Table is the same as the table in previous section (i)-1.

After the contact-driver


Table is the same as the table in previous section (i)-2.

Connection points for the PLC


Table is the same as the table in previous section (i)-3.

GRL200 (Soft 033 & 037)


- 1071 -
6F2S1914 (0.37)

Power supply module (PWS)


The power supply module (PWS) consists of a DC/DC converter and line noise filters. The input
range rating of the PWS is 110 to 250 V DC.
Alpha-numeric reference of PWS. Sign “*” is
substituted for actual slot location number.4

Upper block
is designated
“1 to 20” T*

PWS
*
T
1
2
3
4
5
6
2
7
8
4
9
10 FAIL15
11 3
12 Terminal screw
1
13 number
14 Terminal
15 screw
16 number
17 8
18
19 10
20 Lower block
is FAIL25 9
designated
“21 to 40” 7
21
22
23 Terminal screw
24 number
25 29
26 Positive(+) DC
30
27 /
28
29 Negative(−) 31 DC
30 32
31
35
32
33 36
Short wire1 34 Short wire1
35 E 37
36
37 38
38
Short-wire2 39 Short wire2
40

FG
FG

E3

Frame earth Screw M5 screw for case earthing3

Terminal and Earthing screws Schematic diagram

Figure 5.5-1 PWS terminal block (Rear view)

PWS consists of a pair of terminal blocks4 (which are labeled with alpha-numeric
reference “T*”; a number replaces the asterisk “*” to designate the slot numbers.) The left of
Figure 5.5-1 shows the PWS terminal blocks, and the schematic figure for PWS is also shown
on the right.

Terminal screws No. 1 to 4 (FAIL1) and No. 7 to 10 (FAIL2) are provided to output the

GRL200 (Soft 033 & 037)


1072
6F2S1914 (0.37)

failure results of the automatic supervision function5. Terminal screws No. 29(+) and 31(−) are
linked to the power supply. Other terminal screws No. 30(+) and 31(–) are also provided for the
power terminal and are used when bus distribution is required or when the safety
improvement of the cable capacity is required because the power cable is thin. Terminal screw
No. 38 and FG, by default, are linked with a short-wire and also terminal screw No. 35 and
terminal screw No. 37. The user should connect the IED case to the earth with the earth screw.
The other terminal screws are not used.

The actual terminal slot location is also found in external connection figures. (See
Appendix: Typical External connection)

Table 5.5-1 PWS specifications


Input voltage Voltage fluctuation
Description
rating6 permissible
Input voltage (110/125Vdc, 220/250Vdc) is available
DC: 110 to 250V DC: 88 to 300V where the voltage varies in ±20% of the rated voltage
(110V× 80% to 250V×120%).

CAUTION
1Note: The connection (triplet lines) between terminal screw No. 35 and terminal screw
No. 37 is made with a short-wire, which is installed by the manufacturer. Read
Appendix: Notes for the dielectric voltage test carefully and follow the instructions
during testing.
2Note: The connection (double lines) between terminal screw 38 and screw labeled “FG”
is made with a short-wire by the manufacturer.
3Note: For installation, the user should connect the case earth screw labeled “E” to the
protective earth of the panel or others using earthing wire, such that its cross-
section is AWG9 or larger.
4Note:The user can connect a cable to this terminal directly without a cable ferrule; hence,
the recommended cables are AWG14 and their stripping lengths are 10mm. Use “AI
2.5 -10 BU” ferrule for AWG14 when the user wishes to use a cable ferrule made by
PHOENIX CONTACT®.
5Note: The PWS module monitors DC voltages. The supervision function can issue a power
failure when the DC voltage is less than 85V (default threshold; for more
information about the failure, see Chapter Automatic supervision function). The
user can change the 85V threshold to 170V by inserting a shunt connecter (1-2) at
JP4 on the PWS module (see Figure 5.5-2).
6Note: IED (PWS module) can run on AC power supply (100–220Vac), but the operation is
not guaranteed. Power failure (error) is issued when the supervision function is not

GRL200 (Soft 033 & 037)


1073
6F2S1914 (0.37)

disabled, if the IED runs on AC power supply for testing etc.

JP4 JP4
3 3

2 2

1 1

Setting to 170V (typical) Setting to 85V (typical)


(Position ‘1-2’) (Default position ‘2-3’)

Figure 5.5-2 Alarm threshold for DC voltage dropping on the PWS module

GRL200 (Soft 033 & 037)


1074
6F2S1914 (0.37)

Human Machine Interface (HMI)


5.6.1 Outlook
Figure 5.6-1 shows the outlook of human machine interface module (HMI) on the front panel.
The HMI has a screen (standard LCD or large LCD ‘MIMIC’), LED indicators (#1– #26),
operation keys, function keys (F1–F7), monitoring jacks (Term A/B/C) and a USB receptacle.
The LCD can display information; e.g. IED operation menu, status, setting data, monitoring,
fault records and others. We shall see the menus on the display in Chapter User interface later.
A USB receptacle in B-type is provided for the connection to the PC. Thus, the user can connect
the engineering tools (GR-TIEMS®) or the PLC editor (MULTIPLOG®) with the IED using the
USB receptacle.

LED indicators
(#1–#26) Screen

Indicator label

Operation keys

Function keys
(F1–F7)

Monitoring jacks
(Term A/B/C) USB port

Figure 5.6-1 HMI on front panel

GRL200 (Soft 033 & 037)


- 1075 -
6F2S1914 (0.37)

5.6.2 LED Indicators


The LED indicators #1 and #2 are used to indicate the IED statuses. The others (#3 to #26) are
provided to indicate statuses, which the user wishes to check; the settings or by the PLC
function can control to indicate the statuses. The user can make a new indicator label using
the label maker of the GR-TIEMS®. (See Chapter Engineering tool)

The LED indicators‡ (#3 to #26) are also provided as user-programmable indicators.
Figure 5.6-2 shows the schematic diagrams. Each LED indicator can be lit and controlled using
a logic-gate-switch setting and others. For simplicity, we discuss setting the LED indicator #3
only, but the user can take account that setting the other LED indicators (#4 to #26) is the
same as the #3. Table 5.6-1 shows the LED indicator settings; Table 5.6-2 shows the signal
monitoring points on all LED indicator logics.

‡Note:Setting menus of the LED indicator are also discussed in Chapter User interface:
I/O setting sub-menu.

(i) Selection of input signals


The LED indicator (#3) is lit by entering signals from other functions; eight ports are provided
for the entering signals, designated as input-signal1 to input-signal8. The user should ensure
one or more DataIDs are set for the input-signal1 to input-signal8. Entering signals are
designated using DataIDs, respectively; the user should set respective DataIDs for the settings
[Input signal1] to [Input signal8].

(ii) Logic gate switch


In the LED indicator logic #3 a logic scheme is provide for the eight entering signals; the
entering signals are grouped by the selection using scheme switch [LOGIC-SW] for which the
user should set either AND, OR or XOR.

GRL200 (Soft 033 & 037)


- 1076 -
6F2S1914 (0.37)

LED-03
3100031001
[On Delay Timer] [Off Delay Timer] LED indicator #3
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s
1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
[LOGIC-SW] Dwell & Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]

LED-04
3100041001 LED indicator #4
[On Delay Timer] [Off Delay Timer]
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2]
0.000-300.000s 0.000-300.000s 1
[Input signal 3]
& 0 t
&
≥1 OR 0.000-300.000s
[INVERSE-SW] Normal
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]

LED-26
31001A100
[On Delay Timer] [Off Delay Timer] LED indicator #26
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s 1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]

Figure 5.6-2 LED indicator logics (#3 to #26)

(iii) Delayed pick-up/delayed drop-off signal


For the LED indicator logic #3 the user can use an on-delay timer and an off-delay timer; both
are used to adjust the timing for lighting the LED indicator #3. The user should set their
respective time values for settings [On Delay Timer] and [Off Delay Timer].

(iv) Logic level inversion


On the LED indicator logic #3 the entering signal is inverted by the logic inversion function;
inverting an entering signal is carried out when the user sets Inverse for the scheme switch
[INVERSE-SW]. Set Normal for the scheme switch when logic inversion is not required.

GRL200 (Soft 033 & 037)


- 1077 -
6F2S1914 (0.37)

(v) Logic timer switch


The LED indicator #3 can have programmable reset characteristics using scheme switch
[TIMER-SW]. Four types are available: (1) dwell type, (2) delay type, (3) latch type, and (4)
instantaneous type:

Instant type
When required not to have the below characteristics (v)-2, (v)-3, and (v)-4, the user should set
Off for the scheme switch [TIMER-SW].

Delay type
If the user requires lighting the LED indicator with a delayed characteristic, the user should
set Delay for scheme switch [TIMER-SW] and set the value of the pulse width using setting
[Logic timer].

Dwell type
For instance, if the user requires lighting the LED indicator as a one shot pulse, the user
should set Dwell for scheme switch [TIMER-SW] and set the value of the pulse width using
setting [Logic timer]. If the input signals received have a shorter duration than the set value
in the setting [Logic timer], the pulse width will be equal to the setting value. On the other
hand, if the duration of the input signals are longer than that of the set value, the pulse width
will be equal to the width of the input signals.

Latch type
If the user requires lighting the LED indicator to be removed by a reset signal, the user should
set Latch for scheme switch [TIMER-SW]; the user should set the Data ID of the reset signal
for setting [Reset signal]. Since lighting the LED indicator is cleared with the Data ID, the
user should determine the Data ID from other functions. The Data ID is designated by the
signal monitoring point for each function and the user should set the [Reset signal] setting.

(vi) Selection of the LED color


For the LED indicator #3, color selection of either RED/GREEN/YELLOW is possible using the
setting [Color].

GRL200 (Soft 033 & 037)


- 1078 -
6F2S1914 (0.37)

Table 5.6-1 Settings of LED indictors #3 to #26 (Function ID: 201B01))

Default setting
Setting items Range Units Contents
value

LED#3 Color RED / GREEN / YELLOW - LED#3 color selection RED


Input signal1 (Preferred Data ID) - Set a Data ID at the first input on LED3 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on LED#3. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on LED#3. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on LED#3. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on LED#3. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on LED#3. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on LED#3. (No Assigned)
Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on LED#3. (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on LED#3 AND
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on LED#3 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on LED#3 0.00
INVERSE-SW Normal / Inverse - Inversion operation of LED#3 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on LED#3 Off
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LED#4 Color RED / GREEN / YELLOW - LED#4 color selection RED
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on LED#4 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on LED#4. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on LED#4. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on LED#4. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on LED#4. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on LED#4. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on LED#4. (No Assigned)
Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on LED#4. (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on LED#4 AND
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on LED#4 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on LED#4 0.00
INVERSE-SW Normal / Inverse - Inversion operation of LED#4 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on LED#4 Off
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
……….
LED#26 Color RED / GREEN / YELLOW - LED#26 color selection RED
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on LED#26 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on LED#26. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on LED#26. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on LED#26. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on LED#26. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on LED#26. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on LED#26. (No Assigned)
Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on LED#26. (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on LED#26 AND
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on LED#26 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on LED#26 0.00
INVERSE-SW Normal / Inverse - Inversion operation of LED#26 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on LED#26 Off
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)

GRL200 (Soft 033 & 037)


- 1079 -
6F2S1914 (0.37)

Table 5.6-2 Signal monitoring points on all LED indicator (Function ID: 201B01)
Element ID Name Description
3100021001 ERROR Error LED

3100011001 IN SERV In service LED

3100031001 LED-03 Output signal of the LED indicator #3

3100041001 LED-04 Output signal of the LED indicator #4

3100051001 LED-05 Output signal of the LED indicator #5

3100061001 LED-06 Output signal of the LED indicator #6

3100071001 LED-07 Output signal of the LED indicator #7

3100081001 LED-08 Output signal of the LED indicator #8

3100091001 LED-09 Output signal of the LED indicator #9

31000A1001 LED-10 Output signal of the LED indicator #10

31000B1001 LED-11 Output signal of the LED indicator #11

31000C1001 LED-12 Output signal of the LED indicator #12

31000D1001 LED-13 Output signal of the LED indicator #13

31000E1001 LED-14 Output signal of the LED indicator #14

31000F1001 LED-15 Output signal of the LED indicator #15

3100101001 LED-16 Output signal of the LED indicator #16

3100111001 LED-17 Output signal of the LED indicator #17

3100121001 LED-18 Output signal of the LED indicator #18

3100131001 LED-19 Output signal of the LED indicator #19

3100141001 LED-20 Output signal of the LED indicator #20

3100151001 LED-21 Output signal of the LED indicator #21

3100161001 LED-22 Output signal of the LED indicator #22

3100171001 LED-23 Output signal of the LED indicator #23

3100181001 LED-24 Output signal of the LED indicator #24

3100191001 LED-25 Output signal of the LED indicator #25

31001A1001 LED-26 Output signal of the LED indicator #26

GRL200 (Soft 033 & 037)


- 1080 -
6F2S1914 (0.37)

5.6.3 Function keys with LEDs


The function keys (F1 to F7) are provided to jump to other menus during the LCD operation;
the jump destinations are already set as factory default (see Table 5.6-3). However, the user
can program the F1 to F7 keys to jump to user-preferred menus using settings. Incidentally,
the user can program the function key so that a binary signal is generated when the user
presses the function key.
Table 5.6-3 Function keys and jump destinations (default)
Function LED lit when
Jump destination as default
Key# pressing

F1 Metering menu Yellow


F2 Fault Record menu Yellow
F3 Event Record1 menu Yellow
F4 Event Record2 menu Yellow
F5 Event Record3 menu Yellow
F6 Diagnostics menu Yellow
F7 (Not defined) Yellow

For testing, the user can also program to generate binary signals when the user presses
the F1 to F7 keys. The F1 to F7 circuits have LEDs; accordingly, the user can also program to
light the LEDs using the settings.

(i) Screen jump pressing the function key


The user can program the F1 to F7 keys as the user-preferred jump keys. For example, when
the user wishes to use the F1 key to jump to another screen, set Screen jump for scheme switch
[Function] in the F1 key (see Table 5.6-6). We shall see the setting in Chapter User interface:
Setting sub-menu: Configuration of Function keys.

(ii) Binary signal generated pressing the function key


When the user wishes to generate a binary signal upon occurrence of pressing the F1 key, set
Assign Signal for scheme switch [Function] in the F1 key. For instance, if the user wishes to
send a signal generated pressing F1 to the binary output circuit (BO1‡) at the IO#1 slot, set
the Data ID of “FUNC-KEY1(240001 310001730)” for the setting [Input signal 1] of the BO1‡
circuit. Note that the user should set On for the scheme switch [BO1_CPL] when the connection
is done using the setting [Input signal 1]. Figure 5.6-3 shows that a generate signal is outputted
at the FUNC-KEY1 SIGNAL. Table 5.6-7 shows the other FUNC-KEY2 to 7 points. We shall
see the setting procedure in Chapter User interface: Setting sub-menu: Signal control function.

GRL200 (Soft 033 & 037)


- 1081 -
6F2S1914 (0.37)

Function key logic for F1 Terminal and


(Function ID: 240001) BO1 circuit at IO_SLOT1 (Function ID: 200B01) wire

“BO1”
Setting Data ID “F1 Signal designated by
setting [Input signal 1] ≥1 (200B01_8002001112)
SIGNAL” for the Signal to the
device
“FUNC-KEY1” [Input signal 1] [Input signal 2] DRIVER BO1
& ≥1
Pressing the F1 key (240001_ 3100001730)
[Input signal 3]
“BO1-RB”
F1
& [BO1_CPL] On &
[Input signal 4] (200B01_8002001113)
Off
[Input signal 5]
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
“F1 SIGNAL”
Setting Data ID (240001_ 3100001737) PLC connection point in BO1
“BO1_SOURCE”
&
for the [Signal]† 200B01 310200E11D BO1_SOURCE

[Logic] Instant
Toggle

Figure 5.6-3 F1 key connected with the BO1‡


‡Note:The BO1 circuit is used just for an explanation; it is discussed in Chapter
Technical description: Binary IO module.
†Note:When the user wishes to inject the signal at the PLC connection point of the “BO1-
SOURCE (200B01 31200E11D at the IO#1 slot)”, the user should set the BO1-
SOURCE (200B01 31200E11D) for the setting [Signal] of the F1 key. Then, set Off
for the scheme switch [BO1_CPL]

The user can select either Toggle or Instant modes for the signal generation using scheme
switch [LOGIC], as shown in Table 5.6-4. Thus, the user can substitute “F1-SIGNAL (240001
310001737)” for the “FUNC-KEY1 SIGNAL (240001 310001730)”, provided the Toggle mode
is preferred. In the Table 5.6-7 the other FUNC-KEY2 to FUNC-KEY7 are shown.
Table 5.6-4 Signal mode selection using setting [LOGIC]
Setting Generated signal corresponding to pressing the function key

Pressing Key
Toggle
Binary signal

Pressing Key
Instant
Binary signal

(iii) Lighting LEDs on F1 to F7


Figure 5.6-4 shows the F1 to F7 LED logics. Programing to light the LEDs (F1 to F7) is the
same as the programing of the LED indicators (#3 to #26) (for the programming, see section
5.6.2). As a default, e.g., the “FUNC-KEY1 (240001 310001730)” is set for the setting [Input
signal 1] of the F1 LED logic. The LED-F2 to F7 points are listed in Table 5.6-8.

GRL200 (Soft 033 & 037)


- 1082 -
6F2S1914 (0.37)

31001B1001
[On Delay Timer] [Off Delay Timer] F1 LED logic
& ≥1
t 0 0 t LED-F1
[Input signal 1] DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s
1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
[On Delay Timer] [Off Delay Timer] 31001C1001 F2 LED logic
& ≥1
[Input signal 1] t 0 0 t LED-F2
DRIVER
& AND 0.000-300.000s 0.000-300.000s 1 & [Logic Timer] ≥1
[Input signal 2] & 0 t
[Input signal 3]
[INVERSE-SW]
&
≥1 OR Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]

[On Delay Timer] [Off Delay Timer] 3100211001 F7 LED logic


& ≥1
[Input signal 1] t 0 0 t LED-F7
DRIVER
& AND 0.000-300.000s 0.000-300.000s 1 & [Logic Timer] ≥1
[Input signal 2] & 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]

Figure 5.6-4 LED logics on the function keys F1 to F7

Table 5.6-5 Settings of Function keys (Function ID: 240001)


Default setting
Setting items Range Units Contents
value
Screen Jump / Assign Signal /
Function - Operation mode for the F1 key Screen Jump
No Assign
F1
Signal (Preferred Data ID) - Set a Data ID at the input on F1 key (No Assigned)
Logic Instant / Toggle - Switch for logic-gate operation on F1 Instant
Screen Jump / Assign Signal /
Function - Operation mode for the F2 key Screen Jump
No Assign
F2
Signal (Preferred Data ID) - Set a Data ID at the input on F2 key (No Assigned)
Logic Instant / Toggle - Switch for logic-gate operation on F2 Instant

……….
Screen Jump / Assign Signal /
Function - Operation mode for the F7 key Screen Jump
No Assign
F7
Signal (Preferred Data ID) - Set a Data ID at the input on F7 key (No Assigned)
Logic Instant / Toggle - Switch for logic-gate operation on F7 Instant

GRL200 (Soft 033 & 037)


- 1083 -
6F2S1914 (0.37)

Table 5.6-6 Settings of LEDs on the Function keys (Function ID: 240001)
Default setting
Setting items Range Units Contents
value
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F1 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F1. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F1. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F1. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F1. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F1. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F1. (No Assigned)
F1 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F1. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F1 AND
INVERSE-SW Normal / Inverse - Inversion operation of F1 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F1 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F1 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F1 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F2 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F2. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F2. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F2. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F2. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F2. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F2. (No Assigned)
F2 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F2. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F2 AND
INVERSE-SW Normal / Inverse - Inversion operation of F2 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F2 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F2 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F2 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
……….
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F7 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F7. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F7. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F7. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F7. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F7. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F7. (No Assigned)
F7 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F7. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F7 AND
INVERSE-SW Normal / Inverse - Inversion operation of F7 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F7 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F7 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F7 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00

GRL200 (Soft 033 & 037)


- 1084 -
6F2S1914 (0.37)

Table 5.6-7 Signal monitoring points for KEYINPUT (Function ID: 240001)
Element ID Name Description
3100001737 F1 SIGNAL Signal generated when pressing F1 referring the setting [LOGIC]

3100011737 F2 SIGNAL Signal generated when pressing F2 referring the setting [LOGIC]

3100021737 F3 SIGNAL Signal generated when pressing F3 referring the setting [LOGIC]

3100031737 F4 SIGNAL Signal generated when pressing F4 referring the setting [LOGIC]

3100041737 F5 SIGNAL Signal generated when pressing F5 referring the setting [LOGIC]

3100051737 F6 SIGNAL Signal generated when pressing F6 referring the setting [LOGIC]

3100061737 F7 SIGNAL Signal generated when pressing F7 referring the setting [LOGIC]

3100001730 FUNC-KEY1 Signal generated directly when pressing F1

3100011730 FUNC-KEY2 Signal generated directly when pressing F2

3100021730 FUNC-KEY3 Signal generated directly when pressing F3

3100031730 FUNC-KEY4 Signal generated directly when pressing F4

3100041730 FUNC-KEY5 Signal generated directly when pressing F5

3100051730 FUNC-KEY6 Signal generated directly when pressing F6

3100061730 FUNC-KEY7 Signal generated directly when pressing F7

Table 5.6-8 Signal monitoring points for function LEDs (Function ID: 201B01)
Element ID Name Description
31001B1001 LED-F1 Signal generated during pressing the F1 key

31001C1001 LED-F2 Signal generated during pressing the F2 key

31001D1001 LED-F3 Signal generated during pressing the F3 key

31001E1001 LED-F4 Signal generated during pressing the F4 key

31001F1001 LED-F5 Signal generated during pressing the F5 key

3100201001 LED-F6 Signal generated during pressing the F6 key

3100211001 LED-F7 Signal generated during pressing the F7 key

GRL200 (Soft 033 & 037)


- 1085 -
6F2S1914 (0.37)

5.6.4 Monitoring jacks


A monitoring jack including a LED is provided so that the user can monitor a binary signal on
the logic straightforwardly. For example, when the user wishes to monitor the operating state
of a relay function, set the signal number (Data ID) that the user wishes to monitor; then the
user can see lighting the LED when the relay is operated. Using with an oscilloscope, the user
can also observe the binary signal that comes from the monitoring jack; three monitoring jacks
(Term A, B, and C) are available on the front panel.
Table 5.6-9 Output terminals for signal monitoring (No default setting)
Jack Jack name LED Color Remarks

A Term A Yellow Set user’s preferred signal number


B Term B Yellow Set user’s preferred signal number
C Term C Yellow Set user’s preferred signal number

When the user wishes to test the phase-A element the OC1 relay using an oscilloscope,
for example, set the phase-A monitoring point (44001 8000011C20†) for the setting [Term A],
as shown in Figure 5.6-5. Consequently, the OC1 operating signal is outputted to the jack at
the Term A. The LED at the Term A is also lit in step with the output signal. The user can use
to monitor the phase-B and phase-C signals using by settings respective Data IDs for the [Term
B] and [Term C]. We shall see the menus for the Term A to Term C in Chapter User interface:
Setting sub-menu: Signal monitoring screen.

OC function
(Function ID: 440001) Monitoring jack (Function ID: 201301) Jacks and LEDs

Signal designated by
setting [Term A] DRIVER Term Signal to the
440001 8000011C20
A oscilloscope
A
OC1 440001 8100011C21
B “TEST-A”
440001 8200011C22 (201B01_3100221001)
C
Term A LED

Signal designated by
setting [Term B] DRIVER Term Signal to the
B oscilloscope

“TEST-B”
(201B01_3100231001)

Term B LED

Signal designated by
setting [Term C] DRIVER Term Signal to the
C oscilloscope

“TEST-C”
(201B01_3100241001)

Term C LED

Figure 5.6-5 Monitoring logics A, B and C


†Note:The monitoring point is just selected for the explanation; the user can select a
monitoring point from the relay applications and the control and monitoring
applications. The monitoring points is listed as PLC monitoring points in each
function.

GRL200 (Soft 033 & 037)


- 1086 -
6F2S1914 (0.37)

Table 5.6-10 Settings of Monitoring jacks (Function ID: 201301)


Unit Default setting
Setting items Range Contents
s value
Term A (Preferred Data ID) - Select a signal for Term A (No Assigned)
Term B (Preferred Data ID) - Select a signal for Term B (No Assigned)
Term C (Preferred Data ID) - Select a signal for Term C (No Assigned)

Table 5.6-11 Signal monitoring points for monitoring jack LEDs (Function ID: 201B01)
Element ID Name Description
3100221001 TEST-A TEST-A

3100231001 TEST-B TEST-B

3100241001 TEST-C TEST-C

GRL200 (Soft 033 & 037)


- 1087 -
6F2S1914 (0.37)

5.6.5 Operation keys


(i) L/R key
The IED has two LEDs on the L/R key; either LEDs is lit in response to a local mode or a
remote mode. Lighting the LED is instructed by the LOCRMT function. Table 5.6-12 shows
the signal monitoring points on the L/R LEDs.

Table 5.6-12 Signal monitoring points for L/R LEDs (Function ID: 201B01)
Element ID Name Description
3100251001 LOC LED Local

3100261001 REM LED Remote

(ii) Operation keys except L/R key


Like in the function keys (F1 to F7), the operation keys can provide signals when pressing the
keys; the user can monitor the signals at the signal monitoring points in Table 5.6-13.

Table 5.6-13 Signal monitoring points for KEYINPUT (Function ID: 240001)
Element ID Name Description
3100081730 CANCEL Key situation of CANCEL

31000E1730 CLEAR Key situation of CLEAR

31000D1730 CLOSE Key situation of CLOSE

31000F1730 DOWN Key situation of DOWN

3100071730 ENTER Key situation of ENTER

3100091730 HELP Key situation of HELP

3100111730 LEFT Key situation of LEFT

31000A1730 LOC/REM Key situation of LOC/REM

31000C1730 OPEN Key situation of OPEN

3100121730 RIGHT Key situation of RIGHT

3100101730 UP Key situation of UP

GRL200 (Soft 033 & 037)


- 1088 -
6F2S1914 (0.37)

Clock function
Clock function (or time function) provides the time information for recording upon occurrence
of the fault; it includes a synchronization function when the reference clock is available out of
the IED. The clock is operated referring the Coordinated Universal Time (UTC‡) when the
UTC is selected; the clock can run in accordance with the user’s time zone and summer
time(DST)† by referring the UTC when the time zone and the DST are set. The explanation is
also found in Chapter User interface: Time sub-menu.

†Note:In other words, it is called “daylight saving time (DST)”. For setting, see section
5.7.5.
‡Note:For example, the Internet and World Wide Web standards run in the UTC. For
more information, see section 5.7.4.

5.7.1 Clock setting


The user can set the time using the time sub-menu as shown in Figure 5.7-1. The user also can
set the time using the GR-TIEMS†.
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc] >
SNTP

Figure 5.7-1 Time sub-menu in Clock menu


†Note:Make the calibration the when the clock is set using the GR-TIMES. This is
because the transmission time is required from the PC to the IED.

5.7.2 Selection of date and time formats


The user can select user-preferred date/time format; setting [Data_fmt] is provided for the
selection of the format. For example, ‘March 24th 2014 10:48’ can be displayed when the format
“DDMMYYYY” is selected.
 “2014-03-24 10:48” is displayed upon the selection of “YYYYMMDD”.
 “03-24-2014 10:48” is displayed upon the selection of “MMDDYYYY”.
 “24-03-2014 10:48” is displayed upon the selection of “DDMMYYYY”.
Display Format
10:48 1/4
Date_fmt +
YYYYMMDD
Date_delimiter +
-
Time_delimiter +
:

Figure 5.7-2 Setting screen of Display format

GRL200 (Soft 033 & 037)


- 1089 -
6F2S1914 (0.37)

5.7.3 Time Synchronization


The synchronization function can run when a synchronized signal is provided for respective
IEDs; the user should select one of the following synchronization methods using the setting
[Time_Sync_Src]:
 SNTP method
 IRIG-B method
 Binary Input (BI) method

(i) Synchronization using SNTP


Example of SNTP synchronization
The SNTP method is possible when IEDs connect with time-servers. Figure 5.7-3 exemplifies
two servers are connected with the IEDs using the LAN.
Time server1 Time server2

LAN

………….
IED_1 IED_2 IED_n

Figure 5.7-3 Two time servers connected on the LAN

Setting procedure
The user should make the following steps in respective IEDs.
1) Set SNTP for the setting [Time Sync Src]; then set On for the setting [SNTP].
2) Set the address of a time server using settings [Server1]. The settings [Server2],
[Server3], and [Server4] are provided for other time-servers.
3) Check that the SNTP is shown under the ActivSyncSrc, as shown in Figure 5.7-4.
4) Check to see that the time zone and the DST are set correctly (see 5.7.4 and 5.7.5).
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc] > Check “SNTP” being shown under ActiveSyncSrc.
SNTP

Figure 5.7-4 Time setting for SNTP


Table 5.7-1 Settings for the SNTP synchronization
Setting item Range Contents Setting example Notes
TimeSyncSrc SNTP / BI / IRIG-B Selection of sync method SNTP
SNTP Off /On Operation of SNTP ()On
Server1 000.000.000.000–255.255.255.255 Setting for Time server 1 197.1.23.11
Server2 000.000.000.000–255.255.255.255 Setting for Time server 2 000.000.000.000
Server3 000.000.000.000–255.255.255.255 Setting for Time server 3 000.000.000.000
Server4 000.000.000.000–255.255.255.255 Setting for Time server 4 000.000.000.000

GRL200 (Soft 033 & 037)


- 1090 -
6F2S1914 (0.37)

(ii) Synchronization using IRIG-B


Example of IRIG-B synchronization
The IRIG-B method is possible when a synchronization signal in the IRIG-B format is provided.
The synchronization signal is transferred using the IRIG-B000 module†.

IED

IRIG-B000†
Clock
10:00 1/2
Signal [Time] +
A1 2012-11-21 10:00:05
IRIG-B signal
[Format]
generator Unit GND
A3 YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
IRIG-B

Figure 5.7-5 IED connected with the signal generator unit using IRIG-B000 module
†Note:See Chapter Technical description: Signal processing and communication module .

Setting procedure
The user should make the following steps in respective IEDs.
1) Set IRIG-B for the setting [Time Sync Src]; then set On for the setting [IRIG-SYNC].
2) Check that the IRIG-B is shown under the ActivSyncSrc, as shown in Figure 5.7-6.
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
Check “IRIG-B” being shown under ActiveSyncSrc.
IRIG-B

Figure 5.7-6 Time setting for IRIG-B

Setting year in IRIG-B


When the IRIG-B data is generated in the IEEE C37.118 / IRIG-B000 format, the user should
set On for setting [USE_BCDYEAR]. Conversely, when the IRIG-B data with absence the
C37.118† is generated, Off should be set for the setting [USE_BCDYEAR].
†Note: “Year” is informed from the IED clock itself when the C37.118 is absent.

Setting UTC/local time


When the IRIG-B data is generated in the UTC†, set Off for the setting [USE_LOCALTIME].
Conversely, when the IRIG-B data is generated in the local time‡, set On for setting
[USE_LOCALTIME]; set Off for the setting [IS_UTC_base].
†Note:We shall see the settings of the UTS in section 5.7.4.
‡Note:In the IRIG-B signal generator unit, the DST settings should be corresponded to
the DST settings of the IED. We shall see the DST settings in section 5.7.5.

GRL200 (Soft 033 & 037)


- 1091 -
6F2S1914 (0.37)

Table 5.7-2 Settings for the IRIG-B Time synchronization


Setting
Setting item Range Contents Notes
example
TimeSyncSrc SNTP / BI / IRIG-B Selection of sync method IRIG-B
IRIG-SYNC Off /On Operation of IRIG-B On
USE_BCDYEAR Off / On Selection of IEEE C37.118/IRIG-B000 Off
USE_LOCALTIME Off / On Operation in the local time Off

(iii) Synchronization using BI signal


When accurate1Hz square-wave can be supplied as a reference clock, the clock function can
make the time synchronization. The 1Hz square-wave is transferred using a binary input
circuit (BI).

Example of time synchronization via BI circuit


Figure 5.7-7 exemplifies that the 1Hz square-wave is provided via the BI1 circuit†.

IED
BI1
BI1A (200B01 8001001111)
1
2 BI1
3
4 BI2
5
6 BI3
7
8 BI4
9
10 BI5 Setting [BI_ID]
11
12 BI6
13
14 BI7
15
16 BI8
17
18 BI9 Clock

21
22 BI10
23
24 BI11
25
26 BI12
27
Signal generator 28 BI13
29
30 BI14
31
32 BI15
1Hz squire wave 33
34 BI16
35
36 BI17
37
38 BI18

IO#1

Figure 5.7-7 IED connected with the signal generator via BI module
†Note:The BI1 circuit is just used for the explanation; hence, an actual BI circuit should
be selected in accordance with wiring cables. For more information of the BI
circuit, see Chapter Technical description: Binary IO module.

GRL200 (Soft 033 & 037)


- 1092 -
6F2S1914 (0.37)

Setting procedure
The user should make the following steps in respective IEDs.
1) Set BI for the setting [Time Sync Src]; then set On for the setting [BI-SYNC].
2) Check BI is shown under the ActivSyncSrc, as shown in Figure 5.7-8.
3) Set a Data_ID for setting [BI_ID]. For example, as shown in the Figure 5.7-7, when
the user wishes to inject the signal at the BI1 on the IO#1 slot, the user should set
BI1(200B01 8001001111) for the setting [BI_ID].
4) Set a time adjuster for the setting [SYNC ADJ]. For example, set a value (e.g., −0.050s)
for setting [SYNC ADJ]. The setting is used when the clock function should be
synchronized before reaching the 1Hz square-wave due to the propagation or the
operating time on the BI circuit.

Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
BI

Check “BI ” being shown under ActiveSyncSrc.

Figure 5.7-8 Time setting for BI

Table 5.7-3 Setting items for the BI Time synchronization


Setting item Range Contents Setting example Notes
TimeSyncSrc SNTP / BI / IRIG-B Selection of sync method BI
BI-SYNC Off /On Operation of BI On
BI_ID [Preferred ID] Signal monitoring point 200B01 8001001111
Time adjust factor (in −:Leading the clock
SYNC ADJ −0.050 to +0.050 0.000
sec.) +:Delaying the clock

GRL200 (Soft 033 & 037)


- 1093 -
6F2S1914 (0.37)

5.7.4 Setting time zone


When the clock should run in the UTC, the user should set On for the setting [IS_UTC_base].
Additionally, the user should set the time zone† when the time should be displayed in the Local
standard time. The time zone is divided in every 15 minutes; the user can set it using 0.25
units (i.e., 15 min = 0.25 unit). For example, if that the IED is used in Venezuela (UTC-04:30),
the user should set “−4.50” for the setting, as shown Figure 5.7-9.
Time Zone
10:48 1/1
Time zone +
-4.50hour

Figure 5.7-9 Setting screen of Time zone


Table 5.7-4 Example time offsets and locations
Time offset† Example locations
UTC−10:00 United States (Hawaii)
UTC−09:00 United States (Anchorage)
UTC−08:00 United States (PST)
UTC−06:00 Canada , Costa Rica, El Salvador, Ecuador, Mexico, United States (CST)
UTC−05:00 Brazil (Acre), Colombia, Cuba, Jamaica, Panama, Peru, United States (EST)
UTC−04:30 Venezuela
UTC−04:00 Bolivia, Brazil, Dominican Republic, Puerto Rico, Barbados
UTC−03:00 Argentina, Brazil (Bahia, Pernambuco), Chile
UTC−02:00 Brazil (Fernando de Noronha)
UTC±00:00 United kingdom, Iceland, Ireland, Senegal, Saint Helena, Mali
UTC+01:00 Germany, Hungary, Italy, France, Montenegro
UTC+02:00 Egypt, Estonia, Finland
UTC+03:00 Ethiopia, Iraq, Kenya, Madagascar, Russia, Saudi Arabia, Turkey
UTC+04:00 Armenia, Azerbaijan, Oman, Seychelles, United Arab Emirates
UTC+05:00 Pakistan
UTC+05:30 India, Sri Lanka
UTC+06:00 Bangladesh, Bhutan, Kazakhstan
UTC+06:30 Myanmar
UTC+07:00 Western Indonesia, Thailand, Vietnam, Cambodia, Laos
UTC+08:00 China, Malaysia, Philippines, Australia (Western Australia), Mongolia
UTC+09:00 Japan, South Korea
UTC+10:00 Australia (Queensland)
UTC+12:00 New Zealand
†Note:Time zone is expressed in the difference between UTC and the local standard
time.

Table 5.7-5 Setting time zone


Setting
Setting item Range Contents Notes
example
IS_UTC_base On / Off Selection of either the UTC or the local time On

GRL200 (Soft 033 & 037)


- 1094 -
6F2S1914 (0.37)

5.7.5 DST setting (Summer time setting)


When the summer time (DST) is applied, the user should set the beginning and the ending
dates of the DST in the clock function. The user should set On for the setting [Summer time]
for DST.
Note: The clock function is not designed for particular DSTs such as they are depending
on the religious events and the astronomy.

(i) DST set by the day (Mon to Sun) of week


For example, when the DST starts at 01:00 a.m. on Sunday of the fifth week in March and it
ends at 2:00 a.m. on Sunday of the fourth week in October, the user has the following settings.
Note that transposing the calendar is required, as shown in Figure 5.7-10; accordingly the first
of the month is located at the first row and the first column of the transposed calendar.

Beginning of the DST at 01:00 a.m. in Mar. 29 Ending of the DST at 02:00 a.m. in Oct. 25
March October
Mon Tue Wed Thu Fri Sat Sun Mon Tue Wed Thu Fri Sat Sun
1 1 2 3 4
2 3 4 5 6 7 8 5 6 7 8 9 10 11
9 10 11 12 13 14 15 12 13 14 15 16 17 18
16 17 18 19 20 21 22 19 20 21 22 23 24 25
23 24 25 26 27 28 29 26 27 28 29 30
30 31

Transposed Transposed

March October
Week Sun Mon Tue Wed Thu Fri Sat Week Thu Fri Sat Sun Mon Tue Wed
1 1 2 3 4 5 6 7 1 1 2 3 4 5 6 7
2 8 9 10 11 12 13 14 2 8 9 10 11 12 13 14
3 15 16 17 18 19 20 21 3 15 16 17 18 19 20 21
4 22 23 24 25 26 27 28 4 22 23 24 25 26 27 28
5 29 30 31 5 29 30

Setting 3 for the [Start_Month] Setting 10 for the [End_Month]


Setting 5 for the [Start_Week] Setting 4 for the [End_Week]
Setting Sun for the [Start_Wday] Setting Sun for the [End_Wday]
Setting 1 for the [Start_Hour] Setting 2 for the [End_Hour]

Figure 5.7-10 DST setting examples by the day of week

(ii) DST set by the day (1st or 15th) of month


For example, when the DST starts at 01:00 p.m. on the first day in March and it ends at 3:00
p.m. on the middle day in October; the user has the following settings.

GRL200 (Soft 033 & 037)


- 1095 -
6F2S1914 (0.37)

March October
Week Sun Mon Tue Wed Thu Fri Sat Week Thu Fri Sat Sun Mon Tue Wed
1 1 2 3 4 5 6 7 1 1 2 3 4 5 6 7
2 8 9 10 11 12 13 14 2 8 9 10 11 12 13 14
3 15 16 17 18 19 20 21 3 15 16 17 18 19 20 21
4 22 23 24 25 26 27 28 4 22 23 24 25 26 27 28
5 29 30 31 5 29 30

Beginning of the DST Ending of the DST


at 01:00 p.m. in Mar. 1 at 03:00 p.m. in Oct. 15

Setting 3 for the [Start_Month] Setting 10 for the [End_Month]


Setting 1 for the [Start_Week] Setting 3 for the [End_Week]
Setting – for the [Start_Wday] Setting – for the [End_Wday]
Setting 13 for the [Start_Hour] Setting 15 for the [End_Hour]

Figure 5.7-11 DST setting examples by the day (1st or 15th) of month

(iii) Time shift


After setting the DST, the clock is forwarded by 1 hour at the DST start; the clock is backed by
1 hour at the DST end.
Table 5.7-6 DST settings
Setting
Setting item Range Contents Notes
example

Summer time On / Off Enabling DST operation On

Start_Month 1 to 12 Set the beginning of DST in the month 3

Start_Week 1 to 5 Set the beginning of DST in the week 5


–, Sun, Mon,
Start_Wday Tue, Wed, Thu, Set the beginning of DST in the day Sun
Fri, Sat
Start_Hour 0 to 23 Set the beginning of DST in 24 hour-clock 1

End_Month 1 to 12 Set the end of DST in the month 10

End_Week 1 to 5 Set the end of DST in the week 5


–, Sun, Mon,
End_Wday Tue, Wed, Thu, Set the end of DST in the day Sun
Fri, Sat
End_Hour 0 to 23 Set the beginning of DST in 24 hour-clock 2

GRL200 (Soft 033 & 037)


- 1096 -
6F2S1914 (0.37)

5.7.6 Setting
Setting of CLOCK (Function ID: 200301)
Unit Default setting
Setting item Range Contents Notes
s value
Timezone -14.00 - 14.00 hour Time zone 0.00
--- / SNTP / BI /
TimeSyncSrc - Time sync source SNTP
MODBUS / IRIG-B
YYYYMMDD /
Date_fmt MMDDYYYY / - YMD/MDY/DMY YYYYMMDD
DDMMYYYY
Date_delimiter -///. - - or / or . -
Time_delimiter :/. - : or period :
Sec_delimiter ./, - . or , .
SummerTime Off / On - Summer time enable Off
IS_UTC_base Off / On - Is setting value base on UTC? On
Start_Month 1 - 12 - Start month 3
Start_Week 1-5 - Start week 5
--- / Sun. / Mon. / Tue.
Start_Wday / Wed. / Thr. / Fri. / - Start day of week Sun.
Sat.
Start_Hour 0 - 23 - Start hour 1
End_Month 1 - 12 - End month 10
End_Week 1-5 - End week 5
--- / Sun. / Mon. / Tue.
End_Wday / Wed. / Thr. / Fri. / - End day of week Sun.
Sat.
End_Hour 0 - 23 - End hour 1

Setting of SNTP_SYNC (Function ID: 200A01)


Unit Default setting
Setting item Range Contents Notes
s value
SNTP Off / On - Enabling SNTP synchronization On
Server1 0 - 255 - IP address#1 0. 0. 0. 0
Server2 0 - 255 - IP address#2 0. 0. 0. 0
Server3 0 - 255 - IP address#3 0. 0. 0. 0
Server4 0 - 255 - IP address#4 0. 0. 0. 0

Setting of BI_SYNC (Function ID: 202001)


Unit Default setting
Setting item Range Contents Notes
s value
BI SYNC Off / On - BI sync switch Off
BI_ID [Preferred ID] - Source BI Data ID
SYNC ADJ -0.050 to 0.050 s Time adjust factor 0.000

Setting of IRIG_SYNC (Function ID: 202101)


Unit Default setting
Setting item Range Contents Notes
s value
IRIG SYNC Off / On - IRIGB sync switch Off
USE_BCDYEAR Off / On - Use BCD year code Off
USE_LOCALTIME Off / On - Use local time Off

GRL200 (Soft 033 & 037)


- 1097 -
6F2S1914 (0.37)

Group setting for protection functions


With regard to protection functions (i.e., OC, EF, and others), eight groups are available for
settings, as shown in Figure 5.8-1; different values for the relays can be set as per
circumstances such as operation conditions and others. Note that changing the group cannot
be not carried out instantly.

Settings
Protection (Relay)
Group1 setting
OC
EF
OV
UV
THM

TRC

Group2 setting
OC
EF
OV
UV
THM

TRC

Group8 setting
OC
EF
OV
UV
THM

TRC

Figure 5.8-1 Eight groups for protection settings

(i) Changing group number by menu operation


The user can change the group number using the menu† on the IED screen. See the Chapter
User interface: Setting sub-menu.

(ii) Changing group number by user-programming


Another changing method is provided by programing PLC logics (For more information about
PLC programing, see the Chapter PLC function.) Figure 5.8-2 exemplifies a PLC logic:
changing group2 from group1 is performed while BI1 circuit is energized. The group setting
function “Setting (Function ID 201400)” has a signal reception point ‘PLC_Group_ENUM’ in
UNIT type; thus changing the group is performed when either numbers (1 to 8) enters at the
signal reception point. The example logic, designed for changing to group2 from group1,

GRL200 (Soft 033 & 037)


- 1098 -
6F2S1914 (0.37)

consists of a binary input circuit (BI1), a number generation function (‘Binary selection’
provided in basic functions of the PLC editor), and the signal reception point. That is, when
the B1 switch is closed, a signal enters the BI1 circuit and is carried to the Binary selection;
accordingly the Binary selection, which is programmed to generate a group number ‘2’ in UNIT
when signal ‘1’ is injected in BOOL(BIT), can generates and inject the group number ‘2’ at the
‘PLC_Group_ENUM’. Consequently, the Setting function (201400) starts change the group
from number ‘1’ to ‘2’. Note that changing is only performed during the BI1 is closed in the
example logic; hence, the setting number goes back to ‘1’ when the BI1 is open.
GR200 IED

Binary selection
(+) (–)
IO_SLOT1 (200B01)
BI1 8001001110 Entering → Leaving 201400 314000E1A0 PLC_Group_ENUM Operation of
BI1 changing
‘1’ in BOOL ‘2’ in UNIT
‘0’ in BOOL ‘1’ in UNIT
BI2 8101011110
BI2

PLC basic-function PLC basic-function A group number enters


Binary input circuits BI1 and BI2
(Flip-Flop) (SEL) to “Setting function (FunctionID: 201400)”
at IO#1 (IO_SLOT1)
2 3
2
SEL DOUT_UNIT
1
DIN_BOOL RS
Unit#16#201400 FID ST
DO Q1 G
FID SET Unit#16#31 DTYPE
RESET1 Unit#16#1 IN0 Unit#16#4000E1A0 DID
DTYPE ST
IN1 DI
DID Unit#16#2

1
DIN_BOOL
FID DO

DTYPE ST
DID

Figure 5.8-2 Example for changing a group setting4


1Note: Function block for the binary input circuit (Binary input FB) is provided in User
library of PLC editor. See the Chapter PLC editing in Basic manual
“Programmable Logic Controller and PLC editor” attached the PLC software.
2Note: The SEL and RS functions are the basic functions. In the logic, when signal ‘1’
enters the SEL function, value ‘2’ is generated. For more information, see the help
menu on the PLC editor.
3Note: For your reference, changing to group3 is performed when value ‘3’ enters. In
other words, values ‘1’ to ‘8’ correspond to ‘group1’ to ‘group8’, respectively.
4Note: This example is designed to change ‘group1’ to ‘group2’ or ‘group2’ to ‘group1’.

Figure 5.8-3 exemplifies that selecting a group among eight groups is required by the
usage of three BI circuits (i.e., Group 1→Group2, Group3,… Group8).

GRL200 (Soft 033 & 037)


- 1099 -
6F2S1914 (0.37)

Binary input circuits BI1 to BI3 A group number enters


at IO#3 (IO_SLOT1) PLC basic-function PLC basic-function
to “Setting function
(Ondelay) (SEL)
(Function ID: 201400)”
BI3_1
DIN_BOOL TON
UDINT#16#200B03 FID DO IN Q BOOL_TO_UNIT
UDINT#16#80 DTYPE ST
UDINT#16#01001111 Delay time# PT ET
DID ADD
XX ms

BI3_2
DIN_BOOL TON DOUT_UNIT_1
UDINT#16#200B03 FID DO IN Q BOOL_TO_UNIT MUL
DOUT_UNIT
UDINT#16#80 DTYPE ST Unit#16#201400 FID ST
Delay time# PT ET
UDINT#16#01011111 DID UDINT#16#2 Unit#16#31 DTYPE
XX ms
Unit#16#4000E1A0 DID
DI
BI3_3
DIN_BOOL TON
UDINT#16#200B03 ADD ADD
FID DO IN Q BOOL_TO_UNIT
MUL
UDINT#16#80 DTYPE ST
UDINT#16#01021111 DID Delay time# PT ET
XX ms UDINT#16#4

UDINT#16#1

Figure 5.8-3 Logic for changing a group setting

(iii) Setting
PF (Function ID: 201400) at Setting|Protection
Setting items Range Unit Contents Default Note

Active Group 1 to 8 – Selection of a setting group number 1

(iv) Signal (Data ID)


 Connection point on PLC logic
Setting_PF (Function ID: 201400)
Element ID Name Description
314000E1A0 PLC_Group_ENUM Reception for setting group number

 Signal monitoring points


Setting_PF (Function ID: 201400)
Element ID Name Description
3200001001 ACT_GRP

3010011001 COM_CHG

3010031001 CTRL_CHG

3010021001 PRO_CHG

3010001001 SYS_CHG

GRL200 (Soft 033 & 037)


- 1100 -
6F2S1914 (0.37)

6 Engineering tool
Contents Pages Pages
Common tools 1103 Settings for Relay and control functions 1105
Configuration tools 1105 Settings for Input and output signals 1105
Comparison of settings 1103 Settings for Event recorder 1105
Configuration in IEC 61850 1105 Setting of Interlock (ILK) 1105
Configuration in IEC 60870-5-103 1105 Signal monitor 1104
Connection with PC 1103 Status monitor 1104
Double command blocking (DCB) 1104 Tool for Fault recorder 1104
Tool for Disturbance recorder 1104
Tool for Event recorder 1104
Label creator 1103
Logging management 1103
MIMIC configuration tool 1106
Project management 1103

GRL200 (Soft 033 & 037)


- 1101 -
6F2S1914 (0.37)

Overview of GR-TIEMS
When engineering, monitoring, record viewing, and test support functions are required in the
IED, the user can handle these advanced and integrated functions using GR-Series Toshiba
IED Engineering and Monitoring Software (GR-TIEMS). The GR-TIEMS should be installed
into a PC prior to engineering. After that, the user can view the IED states (Table 6.1-1) on a
PC screen connected with the IED. The user can also program the IED using the GR-TIEMS.

Figure 6.1-1 GR-TIEMS® screen on PC

Table 6.1-1 Information on the GR-TIEMS


Information Displaying format
Display of voltage and current waveform Oscillograph, vector display
Symmetrical component analysis On arbitrary time span
Harmonic analysis On arbitrary time span
Frequency analysis On arbitrary time span

The GR-TIEMS is software to retrieve and analyze power system quantities, fault and
event records. The user can change the settings in the respective IEDs when the PC is
connected with the IED via a USB or a LAN. For more information in the GR-TIEMS
operations, see a separate manual “Operation manual GR-TIEMS (6F2M1082)”.

GRL200 (Soft 033 & 037)


- 1102 -
6F2S1914 (0.37)

Connection
The user can connect the GR-TIEMS with the IED using either the LAN or the USB, as shown
in Figure 6.2-1.

IED

LAN
USB Cable
Personal Computer

Figure 6.2-1 GR-TIEMS connected with IED

Common tools
(i) Project management
Project files are required to engage sub-engineering tolls in the GR-TIEMS. The user can
manage to read/write the project file of the IED using the project management function. The
user can also see the contents of the project files.

(ii) Comparison
When the user wishes to get the comparison between respective IEDs, using the compare
function the user can get the comparison data about Settings, Disturbance record binary
signals, PLCs, Interlock, Large LCD (MIMIC)†, IEC61850, and IEC60870-5-103 data†.

(iii) Pocket label creator


The user can create the name label of LEDs and Function keys for the IED front panel using
a pocket label sheet, which is provided together with the IED. For more information with
regard the LEDs and Function keys, see Chapter Technical description: Human machine
interface.

(iv) Logging
The user can view the recorded data with regard to the logging date/time. As the user can also
find operation recorded when an operator/engineer logs into the IED, analyzing a problem is
possible when an error is detected during the IED operations.

GRL200 (Soft 033 & 037)


- 1103 -
6F2S1914 (0.37)

(v) Double command block


For controlling, there is a principle that a first receiving-command shall be carried out
primarily. In other words, succeeding receiving-commands cannot have the right to run until
the first receiving-command is not completed to operate (that is, the principle of double
command blocking (DCB) is established). The principle is significant for the device protections;
hence, the user should DCB setting. For more information with regard to set the DCB, see
Chapter General control function: Common controls.

Monitoring tools
The user can monitor status and measurement value obtained in the IED using the monitoring
tools. All signals monitored are tabulated in the monitoring list dialog. When the user wishes
to monitor a signal, select a signal in the monitoring list dialog after the operation of the drag-
drop on the monitoring window. The monitoring tools can generate an exporting layout file in
the CSV; it also can obtain the layout file in the CSV.

Record tools
(i) Fault record
Fault records are including measuring information before and after the occurrence of the faults.
Accordingly, the user can see information before the fault so that the user can analyze the fault
more precisely. The user can select a fault from the recorded lists; the user can save it into the
fault information file in the CSV. The user can also view the fault records when the exported
data file in the CSV are retrieved into the IED.

(ii) Disturbance record


Disturbance record is a kind of module information measured so that the user can see them in
several graphs: an oscilloscope chart, a harmonic graph, a 3D harmonic graph, a vector in relay
operation analysis (ROA) chart. The user can see disturbance records when the disturbance
records file in COMTRADE are provided. The user can also save disturbance records into the
COMTRADE file.

(iii) Event list


The event list is recorded events information in the IED. The user can generate events
information file in the CSV; the user can retrieve events data file into the IED to view when
the file is in the CSV.

Note: In the IED the date and time is clocked in the coordinated universal time (UTC)
when the clock is selected to operate in UTC. In the record tools within the PC the
date and time is treated in the UTC. Notice that the time in the UTC is converted

GRL200 (Soft 033 & 037)


- 1104 -
6F2S1914 (0.37)

for the local time when the recording time is displayed on the PC. For the clock
operation if the user selects neither the UTC, the time zone or the daylight saving
time (the summer time), displaying incorrect time may result in between the IED
and the PC. For more information about the clock and time, see Chapter Technical
description: Clock function.

Generic configuration tools


(i) Setting (general setting for the relay and controlling functions)
The user can make the IED settings on the GR-TIEMS; the IED settings are transferred into
the IED by the connection between the IED and the GR-TIEMS.

(ii) Setting I/O


The user can see and make the setting with regard to binary input/output circuits (BIO), LEDs
using the setting I/O function. For more information about the BIO, and the LED, see chapter
Technical description.

(iii) Setting event list


The user can set information with regard to the event of an IED using the event list function.

(iv) Interlock configurator


The user can program conditions for executing to control the primary equipment using the
interlock (ILK) configurator. For example, controlling a circuit breaker (open and closing) is
significant; note not induce mal-operations caused by improper conditions; otherwise a severe
fault/blackout results in. The ILK configurator can provide the user to program conditions
concerning the status of the power system. For more information of the ILK, see chapter
Control and monitoring application.

IEC 61850 configuration tool


The user can configure conversion data for the IEC61850 communication†, provided the IED
exchanges the data with the SAS. The user also configures a logical device, a logical node,
Goose publish information, and Goose subscribe information. For setting and configuration for
the IEC61850 communication see Chapter Communication protocol: IEC 61850
communication”.
†Note:The configuration is possible when the IED software has the IEC61850 protocol.
To confirmed the implementation of IEC61850 protocol, the user needs to check
the IED ordering code (for more information, see Appendix: Ordering code).

IEC 60870-5-103 configuration tool


The user can edit the data of the IEC 60870-5-103 protocol† to perform communications

GRL200 (Soft 033 & 037)


- 1105 -
6F2S1914 (0.37)

between IEDs. The IEC 60870-5-103 data consists of the IEC 60870-5-103 Slave and the
IEC60870-5-103 Master data; the user can edit either the Slave Data or the Master Data‡ at
a time.
†Note:The configuration is possible when the IED software has the IEC 60870-5-103. To
confirmed the implementation of IEC61850 protocol, the user needs to check the
IED ordering code (for more information, see Appendix: Ordering code). The tool is
not shown when the IED software does not have the IEC 60870-5-103.
‡Note:Editing the master data is not available at present.

MIMIC configuration tool


When the IED has a large LCD, the user can create user-preferred screens using the MIMIC
configurator. The large LCD will be able to display measurement values, diagrams and others
after the configuration. Note that the MIMIC is not available when the standard LCD is
equipped for the IED.

GRL200 (Soft 033 & 037)


- 1106 -
6F2S1914 (0.37)

7 PLC function
Contents Pages
Error check 1108
PLC driver 1109
Samples 1113
-DISCAR and DEFCAR programing 1113
-DTT programing 1119
-Remote DIFL/DIFGL programing 1123

GRL200 (Soft 033 & 037)


- 1107 -
6F2S1914 (0.37)

Overview of PLC function


PLC (Programmable Logic Controller) software is used for configuring the Inputs/outputs
(I/Os), alarms, indications, recording and others. PLC logic consist of “timers”, “flip-flops”, and
logic gates “AND, OR, XOR, NOT”. The user can configure PLC-logic using the PLC editor
(MULTIPROG®), which should be installed in the user’s PC. Figure 7.1-1 shows the screen for
the PLC editor.

Figure 7.1-1 PC screen of MULTIPROG®


Note: To handle the PLC editor on the PC, the user shall purchase a software license
(EP-261; see Appendix: Ordering) from Toshiba sales representative. For more
information of PLC and MULTIPROG®, see separate manual Basic manual:
Programmable Logic Controller and PLC editor (6F2S1904)).

PLC data error


The Automatic supervision reports the error information when an error occurs in PLC logic.
The error information† is shown in the Monitoring sub-menu on the IED screen. See Chapter
Automatic supervision: Supervision tasks: Supervision of data in PLC function.
PLC data error 1/1
10:48
[Minor error]

[00000006] [00000000]
[00000000] [00000000]
[00000000] [00000000]

PLC error code†

Figure 7.2-1 Error code at 1st row and 1st column on Monitoring sub-menu

GRL200 (Soft 033 & 037)


- 1108 -
6F2S1914 (0.37)

PLC driver
A PLC driver is provided for starting user-programmed logic; the user can assign several values
for the operation. Three-hundred-and-twenty PLC drivers are grouped for 128 BITs, 32
USINTs, 32 UINTs, 32 UDINTs, 32 SINTs, 32 INTs, and 32 DINTs in the function “PLC_DRV
(Function ID: 230302)”.

(i) BIT type


 Monitoring point at PLC Driver
PLC_DRV in BIT type (Function ID: 230302)
Element ID Name Description
8010101BB0 BIT_00_0 General PLC monitoring point for users
8110101BB1 BIT_00_1 General PLC monitoring point for users
8210101BB2 BIT_00_2 General PLC monitoring point for users
…….. ……….. ………
8710101BB7 BIT_00_7 General PLC monitoring point for users
8810101BB8 BIT_01_0 General PLC monitoring point for users
8910101BB9 BIT_01_1 General PLC monitoring point for users
8A10101BBA BIT_01_2 General PLC monitoring point for users
…….. ……….. ………
8F10101BBF BIT_01_7 General PLC monitoring point for users
8010111BB0 BIT_02_0 General PLC monitoring point for users
8110111BB1 BIT_02_1 General PLC monitoring point for users
8210111BB2 BIT_02_2 General PLC monitoring point for users
8310111BB3 BIT_02_3 General PLC monitoring point for users
…….. ……….. ………
8710111BB7 BIT_02_7 General PLC monitoring point for users
8810111BB8 BIT_03_0 General PLC monitoring point for users
8910111BB9 BIT_03_1 General PLC monitoring point for users
8A10111BBA BIT_03_2 General PLC monitoring point for users
8B10111BBB BIT_03_3 General PLC monitoring point for users
…….. ……….. ………
8F10111BBF BIT_03_7 General PLC monitoring point for users
8010121BB0 BIT_04_0 General PLC monitoring point for users
8110121BB1 BIT_04_1 General PLC monitoring point for users
8210121BB2 BIT_04_2 General PLC monitoring point for users
8310121BB3 BIT_04_3 General PLC monitoring point for users
…….. ……….. ………
8710121BB7 BIT_04_7 General PLC monitoring point for users
8810121BB8 BIT_05_0 General PLC monitoring point for users
8910121BB9 BIT_05_1 General PLC monitoring point for users
8A10121BBA BIT_05_2 General PLC monitoring point for users
8B10121BBB BIT_05_3 General PLC monitoring point for users
…….. ……….. ………
8F10121BBF BIT_05_7 General PLC monitoring point for users

GRL200 (Soft 033 & 037)


- 1109 -
6F2S1914 (0.37)

 Monitoring point at PLC Driver


PLC_DRV in BIT type (Function ID: 230302)
Element ID Name Description
8010131BB0 BIT_06_0 General PLC monitoring point for users
8110131BB1 BIT_06_1 General PLC monitoring point for users
8210131BB2 BIT_06_2 General PLC monitoring point for users
8310131BB3 BIT_06_3 General PLC monitoring point for users
…….. ……….. ………
8710131BB7 BIT_06_7 General PLC monitoring point for users
8810131BB8 BIT_07_0 General PLC monitoring point for users
8910131BB9 BIT_07_1 General PLC monitoring point for users
8A10131BBA BIT_07_2 General PLC monitoring point for users
8B10131BBB BIT_07_3 General PLC monitoring point for users
…….. ……….. ………
8F10131BBF BIT_07_7 General PLC monitoring point for users
8010141BB0 BIT_08_0 General PLC monitoring point for users
8110141BB1 BIT_08_1 General PLC monitoring point for users
8210141BB2 BIT_08_2 General PLC monitoring point for users
8310141BB3 BIT_08_3 General PLC monitoring point for users
…….. ……….. ………
8710141BB7 BIT_08_7 General PLC monitoring point for users
8810141BB8 BIT_09_0 General PLC monitoring point for users
8910141BB9 BIT_09_1 General PLC monitoring point for users
8A10141BBA BIT_09_2 General PLC monitoring point for users
8B10141BBB BIT_09_3 General PLC monitoring point for users
…….. ……….. ………
8F10141BBF BIT_09_7 General PLC monitoring point for users
8010151BB0 BIT_10_0 General PLC monitoring point for users
8110151BB1 BIT_10_1 General PLC monitoring point for users
8210151BB2 BIT_10_2 General PLC monitoring point for users
8310151BB3 BIT_10_3 General PLC monitoring point for users
…….. ……….. ………
8710151BB7 BIT_10_7 General PLC monitoring point for users
8810151BB8 BIT_11_0 General PLC monitoring point for users
8910151BB9 BIT_11_1 General PLC monitoring point for users
8A10151BBA BIT_11_2 General PLC monitoring point for users
8B10151BBB BIT_11_3 General PLC monitoring point for users
…….. ……….. ………
8F10151BBF BIT_11_7 General PLC monitoring point for users
8010161BB0 BIT_12_0 General PLC monitoring point for users
8110161BB1 BIT_12_1 General PLC monitoring point for users
8210161BB2 BIT_12_2 General PLC monitoring point for users
8310161BB3 BIT_12_3 General PLC monitoring point for users
…….. ……….. ………
8710161BB7 BIT_12_7 General PLC monitoring point for users

GRL200 (Soft 033 & 037)


- 1110 -
6F2S1914 (0.37)

 Monitoring point at PLC Driver


PLC_DRV in BIT type (Function ID: 230302)
Element ID Name Description
8810161BB8 BIT_13_0 General PLC monitoring point for users
8910161BB9 BIT_13_1 General PLC monitoring point for users
8A10161BBA BIT_13_2 General PLC monitoring point for users
8B10161BBB BIT_13_3 General PLC monitoring point for users
…….. ……….. ………
8F10161BBF BIT_13_7 General PLC monitoring point for users
8010171BB0 BIT_14_0 General PLC monitoring point for users
8110171BB1 BIT_14_1 General PLC monitoring point for users
8210171BB2 BIT_14_2 General PLC monitoring point for users
8310171BB3 BIT_14_3 General PLC monitoring point for users
…….. ……….. ………
8710171BB7 BIT_14_7 General PLC monitoring point for users
8810171BB8 BIT_15_0 General PLC monitoring point for users
8910171BB9 BIT_15_1 General PLC monitoring point for users
8A10171BBA BIT_15_2 General PLC monitoring point for users
8B10171BBB BIT_15_3 General PLC monitoring point for users
…….. ……….. ………
8F10171BBF BIT_15_7 General PLC monitoring point for users

(ii) USINT type


 Monitoring point at PLC Driver
PLC_DRV in USINT type (Function ID: 230302)
Element ID Name Description
3011001BB0 U08_00 General PLC monitoring point for users
3011011BB0 U08_01 General PLC monitoring point for users
3011021BB0 U08_02 General PLC monitoring point for users
3011031BB0 U08_03 General PLC monitoring point for users
…….. ……….. ………
3011311BB0 U08_31 General PLC monitoring point for users

(iii) UINT type


 Monitoring point at PLC Driver
PLC_DRV in UINT type (Function ID: 230302)
Element ID Name Description
3112001BB0 U16_00 General PLC monitoring point for users
3112011BB0 U16_01 General PLC monitoring point for users
3112021BB0 U16_02 General PLC monitoring point for users
3112031BB0 U16_03 General PLC monitoring point for users
…….. ……….. ………
3112311BB0 U16_31 General PLC monitoring point for users

GRL200 (Soft 033 & 037)


- 1111 -
6F2S1914 (0.37)

(iv) UDINT type


 Monitoring point at PLC Driver
PLC_DRV in UDINT type (Function ID: 230302)
Element ID Name Description
3213001BB0 U32_00 General PLC monitoring point for users
3213011BB0 U32_01 General PLC monitoring point for users
3213021BB0 U32_02 General PLC monitoring point for users
3213031BB0 U32_03 General PLC monitoring point for users
…….. ……….. ………
3213311BB0 U32_31 General PLC monitoring point for users

(v) SINT type


 Monitoring point at PLC Driver
PLC_DRV in USINT type (Function ID: 230302)
Element ID Name Description
2014001BB0 S08_00 General PLC monitoring point for users
2014011BB0 S08_01 General PLC monitoring point for users
2014021BB0 S08_02 General PLC monitoring point for users
2014031BB0 S08_03 General PLC monitoring point for users
…….. ……….. ………
2014311BB0 S08_31 General PLC monitoring point for users

(vi) INT type


 Monitoring point at PLC Driver
PLC_DRV in UINT type (Function ID: 230302)
Element ID Name Description
2115001BB0 S16_00 General PLC monitoring point for users
2115011BB0 S16_01 General PLC monitoring point for users
2115021BB0 S16_02 General PLC monitoring point for users
2115031BB0 S16_03 General PLC monitoring point for users
…….. ……….. ………
2115311BB0 S16_31 General PLC monitoring point for users

(vii) DINT type


 Monitoring point at PLC Driver
PLC_DRV in DINT type (Function ID: 230302)
Element ID Name Description
2216001BB0 S32_00 General PLC monitoring point for users
2216011BB0 S32_01 General PLC monitoring point for users
2216021BB0 S32_02 General PLC monitoring point for users
2216031BB0 S32_03 General PLC monitoring point for users
…….. ……….. ………
2216311BB0 S32_31 General PLC monitoring point for users

GRL200 (Soft 033 & 037)


- 1112 -
6F2S1914 (0.37)

PLC setting samples


7.4.1 Tele-protection scheme using DISCAR and DEFCAR commands
The distance carrier command protection (DISCAR†) or the directional earth fault command
protection (DEFCAR†) can realize permissible transfer tripping (or blocking remote tripping).
Between IEDs at the local and remote terminals, the signals generated in the DISCAR and
DEFCAR functions can be transmitted using the sub-communication bits (COM1, COM3‡, and
COM4‡) of the transmission control function (DIF_COMM), when the user has PLC
connections in the DISCAR, DEFCAR, DIF_COMM functions at the both terminals. Note that
this tele-protection scheme is not programmed for the operation in the narrow frame of the
IEEE C37.94 standard. At both the terminals, the user has to make the transmitter and
receiver tele-protection logic using the PLC editor.

†Note:For more information about the tele-protection, see the DISCAR and DEFCAR
functions in Chapter Relay application.
‡Note:The COM3 and COM4 bits are laid out in Wide frame structure (N=3) when the
DIF_COMM function has setting [CH*_COM_WIDTH] = Wide.
§Note:Other transfer tripping can be achieved using the direct transfer trip (DTT)
function, but the DTT scheme makes tripping the CB unconditionally if a trip
command is generated in trip circuits (TRC) at any terminals. The user is
recommended to set On for the [INTCOM] in case that the scheme does not operate
properly.

(i) Transmitter tele-protection logic


The DISCAR and DEFCAR functions generate carrier commands for the tele-protection; their
commands can be sent for the remote terminal, when the user makes the transmitter logic
with the COMM_APPL function. Table 7.4-1 (and Figure 7.4-1) shows the sample PLC logic,
when the IED has VCT12B arranged for the 1CB system. Table 7.4-2 (Figure 7.4-2) shows the
other PLC logic, when the IED has a VCT11B arranged for the 1.5CB system. Sample PLC
logic for the sub-communication channel (COM1-1-S) is illustrated in Figure 7.4-5; the user is
required to make the similar PLC logics for the other sub-communication channels (i.e., COM1-
2-S, COM3-1-S, etc.) at the local and the remote terminals.

GRL200 (Soft 033 & 037)


- 1113 -
6F2S1914 (0.37)

Table 7.4-1 Connection with transmitter logic for VCT12B designed for 1CB
Signal name Signal name
Function
(Monitoring point)
Data ID → Function
(Connection points)
Data ID

436001 4A9001
INT.DISCAR-S-A§ → COM1-1_S
8000001B78 800212EBB0
436001 4A9001
INT.DISCAR-S-B§ → COM1-2_S
8100001B79 800212EBB1
DISCAR
436001 4A9001
INT.DISCAR-S-C§ → COM3-1_S†
8200001B7A 800214EBB0
436001 4A9001
INT.DISCAR-S-S§ → COMM_APPL COM3-2_S†
8300001B7B 810214EBB1
437001 4A9001
INT.DEFCAR-S-A§ → COM3-3_S†
8000001B79 800212EBB3
437001 4A9001
DEFCAR INT.DEFCAR-S-B§ → COM3-4_S†
8100001B7A 800212EBB4
437001 4A9001
INT.DEFCAR-S-C§ → COM3-5_S†
8200001B7B 800214EBB5

Table 7.4-2 Connection with transmitter logic for VCT11B designed for 1.5CB
Signal name Signal name
Function
(Monitoring point)
Data ID → Function
(Connection points)
Data ID

436001 4A9001
INT.DISCAR-S-A§ → COM1-1_S
8000001B78 800212EBB0
436001 4A9001
INT.DISCAR-S-B§ → COM1-2_S
8100001B79 800212EBB1
DISCAR
436001 4A9001
INT.DISCAR-S-C§ → COM2-1_S‡
8200001B7A 800213EBB0
436001 4A9001
INT.DISCAR-S-S§ → COMM_APPL COM2-2_S‡
8300001B7B 810213EBB1
437001 4A9001
INT.DEFCAR-S-A§ → COM3-1_S‡
8000001B79 800214EBB0
437001 4A9001
DEFCAR INT.DEFCAR-S-B§ → COM3-2_S‡
8100001B7A 800214EBB1
437001 4A9001
INT.DEFCAR-S-C§ → COM4-1_S‡
8200001B7B 800215EBB0
†‡Note: Notice that the signal names should be selected by the rules of the frame
structure, which are dependent on the 1CB system and the 1.5CB system; we
have discussed about the C37.94 frame structure in the discussion of the
DIF_COMM function; the structure depends on the selection of the VCT type.
§Note: The signals are listed in the DISCAR and the DEFCAR functions.

GRL200 (Soft 033 & 037)


- 1114 -
6F2S1914 (0.37)

Wide should be set for the [CH1_COM_WIDTH].


N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

COM1 R S S S C 1
1 1 D A P P R bit
bit bit Y 1 2 C
DISCAR function COMM_APPL function
8000001B78

INT.DISCAR-S-A 800212EBB0 COM1-1_S


8000001B79

INT.DISCAR-S-B 800212EBB1 COM1-2_S

N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC

N=3 Header COM2 COM3 COM4 COM5 CRC

COM3 (1 – 8) COM3 (9 – 16)


1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit
DISCAR function COMM_APPL function
8000001B7A
INT.DISCAR-S-C 800213EBB0 COM3-1_S
8000001B7B
INT.DISCAR-S-S 810213EBB1 COM3-2_S

DEFCAR function COMM_APPL function


8000001B79

INT.DEFCAR-S-A 800212EBB3 COM3-3_S


8000001B7A
800212EBB4 COM3-4_S
INT.DEFCAR-S-B
8000001B7B
INT.DEFCAR-S-C 800214EBB5 COM3-5_S

Figure 7.4-1 Transmitter scheme and communication frame for VCT12B in the 1CB

Wide should be set for the [CH1_COM_WIDTH].


N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

COM1 R S S S C 1
1 1 D A P P R bit
bit bit Y 1 2 C
DISCAR function COMM_APPL function
8000001B78

INT.DISCAR-S-A 800212EBB0 COM1-1_S


8000001B79

INT.DISCAR-S-B 800212EBB1 COM1-2_S

N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC

N=3 Header COM2 Ia3 COM3 Ib3 COM4 Ic3 COM5 CRC

COM2 COM3 COM4


1 1 1 1 1 1
bit bit bit bit bit bit
DISCAR function COMM_APPL function
8000001B7A
INT.DISCAR-S-C 800213EBB0 COM2-1_S
8000001B7B
INT.DISCAR-S-S 810213EBB1 COM2-2_S

DEFCAR function COMM_APPL function


8000001B79

INT.DEFCAR-S-A 800214EBB0 COM3-1_S


8000001B7A
800214EBB1 COM3-2_S
INT.DEFCAR-S-B
8000001B7B
INT.DEFCAR-S-C 800215EBB0 COM4-1_S

Figure 7.4-2 Transmitter scheme and communication frame for VCT11B in the 1.5CB

GRL200 (Soft 033 & 037)


- 1115 -
6F2S1914 (0.37)

(ii) Receiver tele-protection logic


Similarly, the user should make the receiver logics, so that the local IED can revive the carrier
commands sent from the remote terminal. The user should notice that the signals for the
connections are different in the 1CB and 1.5CB system.

Table 7.4-3 Connection with receiver logic for VCT12B designed for 1CB
Signal name Signal name
Function
(Monitoring point)
Data ID → Function
(Connection points)
Data ID

4A9001 436001
COM1-1_R1 → INT.DISCAR-R1-A§
8010051CF0 800000EBB5
4A9001 436001
COM1-2_R1 → INT.DISCAR-R1-B§
8110051CF1 810000EBB6
DISCAR
4A9001 436001
COM3-1_R1† → INT.DISCAR-R1-C§
8010061C62 820000EBB7
4A9001 436001
COMM_APPL COM3-2_R1† → INT.DISCAR-R1-S§
8110061C63 830000EBB8
4A9001 437001
COM3-3_R1† → INT.DEFCAR-R1-A§
8210061C64 800000EBB5
4A9001 437001
COM3-4_R1† → DEFCAR INT.DEFCAR-R1-B§
8310061C65 810000EBB6
4A9001 437001
COM3-5_R1† → INT.DEFCAR-R1-C§
8410061C66 820000EBB7

Table 7.4-4 Connection with receiver logic for VCT11B designed for 1.5CB
Signal name Signal name
Function
(Monitoring point)
Data ID → Function
(Connection points)
Data ID

4A9001 436001
COM1-1_R1 → INT.DISCAR-R1-A§
8010051CF0 800000EBB5
4A9001 436001
COM1-2_R1 → INT.DISCAR-R1-B§
8110051CF1 810000EBB6
DISCAR
4A9001 436001
COM2-1_R1‡ → INT.DISCAR-R1-C§
8010051CF2 820000EBB7
4A9001 436001
COMM_APPL COM2-2_R1‡ → INT.DISCAR-R1-S§
8110051CF3 830000EBB8
4A9001 437001
COM3-1_R1‡ → INT.DEFCAR-R1-A§
8010061C62 800000EBB5
4A9001 437001
COM3-2_R1‡ → DEFCAR INT.DEFCAR-R1-B§
8110061C63 810000EBB6
4A9001 437001
COM4-1_R1‡ → INT.DEFCAR-R1-C§
8010061C72 820000EBB7

GRL200 (Soft 033 & 037)


- 1116 -
6F2S1914 (0.37)

Wide should be set for the [CH1_COM_WIDTH].


N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

COM1 R S S S C 1
1 1 D A P P R bit
bit bit Y 1 2 C

8010051CFO 8000001BB5

COM1-1_R1 800000EBB5 INT.DISCAR-R1-A


8100001BB6
8110051CF1
COM1-2_R1 810000EBB6 INT.DISCAR-R1-B
COMM_APPL function DISCAR function

N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC

N=3 Header COM2 COM3 COM4 COM5 CRC

COM3 (1 – 8) COM3 (9 – 16)


1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit

8010061C62 8000001BB5
COM3-1-R1 800000EBB5 INT.DISCAR-R1-C
8110061C63 8100001BB6
COM3-2-R1 810000EBB6 INT.DISCAR-R1-S

DISCAR function
8000001BB5
8210061C64
COM3-3-R1 800000EBB5 INT.DEFCAR-R1-A
8310061C65 8100001BB6
COM3-4-R1 810000EBB6 INT.DEFCAR-R1-B
8410061C66 8100001BB6
COM3-5-R1 810000EBB6 INT.DEFCAR-R1-C

COMM_APPL function DEFCAR function

Figure 7.4-3 Receiver scheme by communication frame in VCT12B in the 1CB

Wide should be set for the [CH1_COM_WIDTH].


N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC

COM1 R S S S C 1
1 1 D A P P R bit
bit bit Y 1 2 C

8010051CFO 8000001BB5

COM1-1_R1 800000EBB5 INT.DISCAR-R1-A


8110051CF1 8100001BB6
COM1-2_R1 810000EBB6 INT.DISCAR-R1-B
COMM_APPL function DISCAR function

N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC


N=3 Header COM2 Ia3 COM3 Ib3 COM4 Ic3 COM5 CRC

COM2 COM3 COM4


1 1 1 1 1 1
bit bit bit bit bit bit

8010051CF2 8000001BB5
COM2-1-R1 800000EBB5 INT.DISCAR-R1-C
8110051CF3 8100001BB6
COM2-2-R1 810000EBB6 INT.DISCAR-R1-S

DISCAR function
8000001BB5
8010061C62
COM3-1-R1 800000EBB5 INT.DEFCAR-R1-A
8110061C63 8100001BB6
COM3-2-R1 810000EBB6 INT.DEFCAR-R1-B
8010061C72 8100001BB6
COM4-1-R1 810000EBB6 INT.DEFCAR-R1-C

COMM_APPL function DEFCAR function

Figure 7.4-4 Receiver scheme by communication frame in VCT11B in the 1.5CB

GRL200 (Soft 033 & 037)


- 1117 -
6F2S1914 (0.37)

(iii) PLC program


Figure 7.4-5 shows the transmitter logic where the INT.DISCAR-S-A output command is given
to the DIN module; the output (DO) is connected to the input (DI) of the DOUT module in the
COMM_APPL function. The other output commands from the DISCAR and DEFCAR functions
should be connected in the COMM_APPL function. Figure 7.4-6 shows the receiver logic.

COM_1_S
DOUT_BOOL‡
FID ST
INT_DISCAR_S_A DTYPE
DID
DIN_BOOL†
INT.DISCAR-S-A
(436001 8000001B78) FID DO DI
DTYPE ST
DID 4A9001 800212EBB0 COM1-1_S N=1 Frame

Figure 7.4-5 Sample transmitter logic for COM_1 sub-communication channel

INT_DISCAR_R1_A
DOUT_BOOL
FID ST
COM1_1_R1 DTYPE
DID
DIN_BOOL
COM1-1_R1
(4A9001 8010051CF0) FID DO DI
DTYPE ST
N=1 Frame DID 436001 800000EBB5 INT.DISCAR-R1-A

Figure 7.4-6 Receiver logic for COM_1 sub-communication channel

†Note:DIN_BOOL and DOUT_BOOL are used to import and export the information for
the data ID in bit type.

GRL200 (Soft 033 & 037)


- 1118 -
6F2S1914 (0.37)

7.4.2 Transfer trip using DTT scheme


The direct transfer protection (DTT†) is designed to send a trip signal to the remote terminal
using the communication. This DTT scheme makes tripping CBs on the enter lines without
delaying; this operates together with communication application (COMM_APPL‡). The user is
required to program transmitter and receiver logics with the PLC editor at respective
terminals.
†Note:For more information about the transfer trip protection, see Chapter Relay
application: Direct transfer protection.
‡Note:COM1 bits are used, but the COM3 and others are also possible to use when Wide
frame structure (N=3) is selected by setting [CH*_COM_WIDTH] = Wide; see
Chapter Relay application: Communication application.
§Note:Keep in mind that the DTT scheme makes tripping all CBs unconditionally if a
trip signal is generated at any terminals. Set On for the [INTCOM] in order that
the scheme does not to operate incorrectly.

(i) Transmitter and receiver schemes


Figure 2.7-1 shows that DTT can transfer a TRIP signal when entire CBs should be tripped,
because the TRIP signal is injected externally at Terminal J. The DTT scheme can transfer the
TRIP signal to remote terminals G and H; the remote terminals can trip their CBs.
Terminal J Terminal G

Fault
TRIP command TRIP command

Local IED relay COM_APPL DTT1 TRC


TRC Remote1 relay
External TRIP signal
TRIP signal BI COM_APPL

TRIP signal

COM_APPL DTT1 TRC


TRIP

Remote2 relay
Terminal H

Figure 7.4-7 External TRIP signal sending for remote ends

Terminal J
The local TRIP signal, which is injected via a binary input circuit (BI), is transferred in the
IEEE C37.94 communication format to Terminals G and H (Figure 7.4-8). On the other hand,
the local DTT1 function can trip the CB by the remote commands from Terminals G and H.
Table 7.4-5 shows the connections at Terminal J.

GRL200 (Soft 033 & 037)


- 1119 -
6F2S1914 (0.37)

N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC To


Terminal G
N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC and
Terminal H
N=3 Header COM2 COM3 COM4 COM5 CRC
External
Trip signal
Transmitter scheme COM1 R S S S C 1
COMM_APPL function 1 1 D A P P R bit
(+) (–) BIO function (4A9001) bit bit Y 1 2 C

BI1 8001001110
BI1 800212EBB0 COM1-1_S

TRC function (4A0001) External


IO_SLOT1 (200B01)
Trip command
830000EBB5 TRIP_ADD
(at Terminal J)

From N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC


Terminal G N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC
N=3 Header COM2 COM3 COM4 COM5 CRC

COM1 R S S S C 1 Receiver scheme1


1 1 D A P P R bit
bit bit Y 1 2 C COMM_APPL function DTT1 function
8010051CE0
COM1-1_R1 800001EBB0
Transferred
R1.DTT1
Trip command
(at Terminal J)

N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC


From
Terminal H N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC
N=3 Header COM2 COM3 COM4 COM5 CRC

COM1 R S S S C 1 Receiver scheme2


1 1 D A P P R bit
bit bit Y 1 2 C COMM_APPL function DTT1 function
8010071C78 Transferred
COM1-1_R2 810001EBB1 R2.DTT1 Trip command
(at Terminal J)

Figure 7.4-8 DTT transmitter / receivers (at Terminal J)

Table 7.4-5 Connections at Terminal J


Signal name Signal name
Function
(Monitoring point)
Data ID → Function
(Connection points)
Data ID

200B01 COMM 4A9001


IO_SLOT BI1 → COM3-6_S
80010011110 _APPL 850214EBB5
4A0001
TRC (same as the above) → TRC TRIP_ADD
830000EBB6
4A9001 485001
COM3-6_R1 → R1.DTT1
COMM 8510061C67 800001EBB0
DTT
_APPL 4A9001 485001
COM3-6_R2 → R2.DTT1
8510071C8F 810001EBB1

Terminal G
Similarly, the communication format and connections at Terminal G are shown in Figure 7.4-9
and Figure 7.4-10.

GRL200 (Soft 033 & 037)


- 1120 -
6F2S1914 (0.37)

Terminal J Terminal G

Fault
TRIP TRIP
Remote relay1
Local IED relay TRC
TRC External
TRIP signal BI COM_APPL
DTT1
COM_APPL TRIP signal

TRIP signal

COM_APPL DTT2 TRC


TRIP

Remote2 relay
Terminal H

Figure 7.4-9 Eternal Trip signal coming from Terminal G

N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC To


Terminal J
N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC and
Terminal H
N=3 Header COM2 COM3 COM4 COM5 CRC
External
Trip signal
Transmitter scheme COM1 R S S S C 1
COMM_APPL function 1 1 D A P P R bit
(+) (–) BIO function (4A9001) bit bit Y 1 2 C

BI1 8001001110
BI1 800212EBB0 COM1-1_S

TRC function (4A0001) External


IO_SLOT1 (200B01)
Trip command
830000EBB5 TRIP_ADD
(at Terminal G)

From N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC


Terminal J N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC
N=3 Header COM2 COM3 COM4 COM5 CRC

COM1 R S S S C 1 Receiver scheme1


1 1 D A P P R bit
bit bit Y 1 2 C COMM_APPL function DTT1 function
8010051CE0
COM1-1_R1 800001EBB0
Transferred
R1.DTT1
Trip command
(at Terminal G)

N=1 Header I0 Ia V1 Ib SCOM Ic COM1 CRC


From
Terminal H N=2 Header Ia Ia2 Ib Ib2 Ic Ic2 COM6 CRC
N=3 Header COM2 COM3 COM4 COM5 CRC

COM1 R S S S C 1 Receiver scheme2


1 1 D A P P R bit
bit bit Y 1 2 C COMM_APPL function DTT1 function
8010071C78 Transferred
COM1-1_R2 810001EBB1 R2.DTT1 Trip command
(at Terminal G)

Figure 7.4-10 DTT transmitter / receivers (at Terminal G)

GRL200 (Soft 033 & 037)


- 1121 -
6F2S1914 (0.37)

(ii) Sample DTT logics


Figure 7.4-11 shows the DTT1 PLC logics where the BI signal is given to the DIN module; the
output (DO) is connected to the input (DI) of the DOUT module in the COMM_APPL function.
The COM1-1 signals from the remote should be connected with the DTT1 function.

COM_1_S
DOUT_BOOL‡
FID ST
Ext.TRIP DTYPE
DID
DIN_BOOL†
BI1
(200B01 8001001110) FID DO DI
DTYPE ST
DID 4A9001 800212EBB0 COM1-1_S N=1 Frame

4A0001 830000EBB5 TRIP_ADD GEN.TRIP


R1.DTT1
DOUT_BOOL‡
FID ST
COM1-1_R1 DTYPE
DID
DIN_BOOL†
COM1-1_R1
(4A9001 801005CF0) FID DO DI
DTYPE ST
DID 485001 800001EBB0 R1.DTT1 DTT1 logic

R2.DTT1
DOUT_BOOL‡
FID ST
COM1-1_R2 DTYPE
DID
DIN_BOOL†
COM1-1_R2
(4A9001 801007C78) FID DO DI
DTYPE ST
DID 485001 810001EBB1 R2.DTT1 DTT1 logic

Figure 7.4-11 Sample logics for DTT1 function at terminals


†Note:DIN_BOOL and DOUT_BOOL are used to import and export the information for
the data ID in bit type.

GRL200 (Soft 033 & 037)


- 1122 -
6F2S1914 (0.37)

7.4.3 Remote DIFL/DIFGL trip using communication scheme


Remote differential protection (RDIF†) is designed to operate the DIFL/DIFLG relay operation
remotely when a failure occurs on communication channels. If a relay is able to make the DIFL
or DIFGL computation during the communication failure, it is preferable that other relays can
have the computation result during the communication failure; this allows issuing trip
commands on the enter lines by the DIFL/DIFGL relay during the communication failure. Note
the user is required to program transmitter and receiver logics with the PLC editor at
respective terminals with communication application (COMM_APPL‡).
†Note:For more information about the remote trip protection, see Chapter Relay
application: DIFL applied to three-terminal line.
‡Note:For the operation, use Wide frame structure (N=3) by setting [CH*_COM_WIDTH]
= Wide; see Chapter Relay application: Communication application.
§Note:Set On for the [INTCOM] in order that the scheme does not to operate incorrectly.

(i) Transmitter and receiver schemes


Figure 2.7-1 shows that the local relay sends ‘DIFL’ operation signal for opposite remote
Terminal G. Relay1 at the terminal G receives the ‘DIFL’ operation signal; Relay1 can use the
receiving signals to issue trip commands if the Relay1 cannot make DIFL computation itself.
Both Relays at Terminals G and H can receive the ‘DIFL’ operation signals. Figure 2.7-1
illustrates that the DIFL signals are transferred for the remote relays in IEEE C37.94
communication format. Table 7.4-6 shows the format and connections at Terminal J.

Fault
TRIP TRIP
Local relay DIFL-A,DIFL-B, DIFL-C
DIFL DIFL TRC
Relay1
Terminal J Terminal G

DIFL-A,DIFL-B, DIFL-C

Terminal H

DIFL TRC

Relay2

Figure 7.4-12 Remote trip scheme in the three-terminal configuration

GRL200 (Soft 033 & 037)


- 1123 -
6F2S1914 (0.37)

Communication format (N=3) IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC
To Terminal G
N=2 Header Ia2 Ib2 Ic2 I0 CRC To Terminal H

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6

Transmitter scheme in Local relay


8000101C20
A 800216EBB0 COM5-1_S
≥1 8100101C21

DIFL#1 B 810216EBB1 COM5-2_S


≥1 8200101C22
C 820216EBB2 COM5-3_S
≥1
A

DIFL#2† B
C

DIFL function (Function ID: 410001) COMM_APPL function (Function ID: 4A9001)

Communication format (N=3) IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

From Terminal G N=2 Header Ia2 Ib2 Ic2 I0 CRC

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6

Receiver scheme1 in Local relay


8010061C82 8000001BB6 To DIFL
COM5-1-R1 800000EBB8 R1.DIFL-A_OP
8110061C83 8100001BB7
COM5-2-R1 810000EBB9 R1.DIFL-B_OP
8200001BB8
8210061C84
COM5-3-R1 820000EBBA R1.DIFL-C_OP

COMM_APPL function DIFL function (Function ID: 410001)

Communication format (N=3) IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

From Terminal H N=2 Header Ia2 Ib2 Ic2 I0 CRC

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

COM5 (6bits) CRC CRC (8bits)


1 2 3 4 5 6

Receiver scheme2 in Local relay


8010071CAD 8000001BB9 To DIFL

COM5-1-R2 800000EBBB R2.DIFL-A_OP


8100001BBA
8110071CAE
COM5-2-R2 810000EBBC R2.DIFL-B_OP
8200001BBB
8210071CAF
820000EBBD R2.DIFL-C_OP
COM5-3-R2

COMM_APPL function DIFL function (Function ID: 410001)

Figure 7.4-13 Transmitter and receivers for DIFL at Terminals J

GRL200 (Soft 033 & 037)


- 1124 -
6F2S1914 (0.37)

Communication format (N=3) IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC
To Terminal G
N=2 Header Ia2 Ib2 Ic2 I0 CRC To Terminal H

N=3 Header Ia3 Ib3 Ic3 COM5 CRC


SCOM1 SCOM2 SCOM3 SCOM4
SA0 MS0 MS1 MS2
SA1 RA0 RA1 RA2
SA2 MS0 MS1 MS2
SA3 RA3 RA4 RA5
SA4 MS0 MS1 MS2
SA5 Spare Spare Spare
SA6 MS0 MS1 MS2
SA7 RA0 RA1 RA2 Local test
SA8 MS0 MS1 MS2
SA9 RA3 RA4 RA5
SA10 MS0 MS1 MS2
SA11 Spare Spare Spare

Transmitter scheme in Local relay


8000001C23

810211EBB1 SCOM4-SA1_S
DIFGL#1 ≥1

DIFGL#2

DIFGL function COMM_APPL function (Function ID: 4A9001)

Communication format (N=3) IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

From Terminal G N=2 Header Ia2 Ib2 Ic2 I0 CRC

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

SCOM1 SCOM2 SCOM3 SCOM4


8110051CE5
SA0 MS0 MS1 MS2
SA1 RA0 RA1 RA2 SCOM4-SA1-R1

~ ~ ~ ~
SA11 Spare Spare Spare Local test
Receiver scheme1in Local relay

8000001BB5 To DIFGL
800000EBB5 R1.DIFGL_OP

COMM_APPL function DIFGL function (Function ID: 410001)

Communication format (N=3) IEEE C37.94


N=1 Header I0 Ia V Ib SCOM Ic CRC

From Terminal H N=2 Header Ia2 Ib2 Ic2 I0 CRC

N=3 Header Ia3 Ib3 Ic3 COM5 CRC

SCOM1 SCOM2 SCOM3 SCOM4


8110071C6D
SA0 MS0 MS1 MS2
RA0 RA1 RA2 SCOM4-SA1-R2
SA1
~ ~ ~ ~
SA11 Spare Spare Spare Local test
Receiver scheme2in Local relay

8100001BB6 To DIFGL
810000EBB6 R2.DIFGL_OP

COMM_APPL function DIFGL function (Function ID: 410001)

Figure 7.4-14 Transmitter and receivers for DIFGL at Terminals J

GRL200 (Soft 033 & 037)


- 1125 -
6F2S1914 (0.37)

Table 7.4-6 Connections in Local relay at Terminal J


Signal name Signal name
Function
(Monitoring point)
Data ID → Function
(Connection points)
Data ID

410001 4A9001
DIFL-A → COM5-1_S
8000101C20 800216EBB0
410001 4A9001
DIFL DIFL-B → COM5-2_S
8100101C21 COMM 810216EBB1
410001 _APPL 4A9001
DIFL-C → COM5-3_S
8200101C22 820216EBB2
410001 4A9001
DIFGL DIFGL → SCOM4-SA0_S
8000101C23 830211EBB3
4A9001 410001
COM5-1_R1 → R1.DIFL-A.OP
8010061C82 800000EBB8
4A9001 410001
COM5-2_R1 → R1.DIFL-B.OP
8110061C83 810000EBB9
4A9001 410001
COM5-3_R1 → R1.DIFL-C.OP
8210061C84 820000EBBA
DIFL
4A9001 410001
COM5-1_R2 → R2.DIFL-A.OP
COMM 8010071CAA 800000EBBB
_APPL 4A9001 410001
COM5-2_R2 → R2.DIFL-B.OP
8110071CAB 810000EBBC
4A9001 410001
COM5-3_R2 → R2.DIFL-C.OP
8210071CAC 820000EBBD
4A9001 410001
SCOM4-SA1-R1 → R1.DIFGL_OP
8110051CE5 800000EBB5
DIFGL
4A9001 410001
SCOM4-SA1-R2 → R2.DIFGL_OP
8110071C6D 810000EBB6

GRL200 (Soft 033 & 037)


- 1126 -
6F2S1914 (0.37)

(ii) Sample local and remote logics


COM5_1_S
DOUT_BOOL‡
R1.DIFL-A.OP
FID ST DOUT_BOOL‡
DIFL-A DTYPE FID ST
DID COM5-1_R1 DTYPE
DIN_BOOL†
DIFL-A DID
(410001 8000101C20) FID DO DI DIN_BOOL†
COM5-1_R1
DTYPE ST (4A9001 8010061C80 FID DO DI
DID DTYPE ST
4A9001 800216EBB0 COM5-1_S N=3 Frame DID 410001 800000EBB8 R1.DIFL-A.OP DIFL logic
COM5_2_S
DOUT_BOOL‡ R1.DIFL-B.OP
FID ST DOUT_BOOL‡
DIFL-B DTYPE FID ST
DIN_BOOL†
DID COM5-2_R1 DTYPE
DIFL-B
(410001 8100101C21) FID DO DI DID
DIN_BOOL†
COM5-2_R1
DTYPE ST FID DO DI
(4A9001 8110061C81)
DID 4A9001 810216EBB1 COM5-2_S N=3 Frame DTYPE ST
DID 410001 810000EBB9 R1.DIFL-B.OP DIFL logic
COM5_3_S
DOUT_BOOL‡
R1.DIFL-C.OP
FID ST
DOUT_BOOL‡
DIFL-C DTYPE
FID ST
DID
DIN_BOOL† COM5-3_R1 DTYPE
DIFL-C
(410001 8200101C22) FID DO DI
DID
DTYPE ST DIN_BOOL†
COM5-3_R1
(4A9001 8210061C82) FID DO DI
DID 4A9001 820216EBB2 COM5-3_S N=3 Frame DTYPE ST
DID
SCOM4-SA_S
410001 820000EBBA R1.DIFL-C.OP DIFL logic
DOUT_BOOL‡
R1.DIFGL_OP
FID ST
DOUT_BOOL‡
DIFGL DTYPE
FID ST
DID
DIFGL
DIN_BOOL† SCOM4-SA1_R1 DTYPE
(411001 8000001C23) FID DO DI DID
DIN_BOOL†
DTYPE ST SCOM4-SA1-R1
(4A9001 8110051CE5) FID DO DI
DID 4A9001 810211EBB1 SCOM4-SA1_S N=1 Frame DTYPE ST
DID 410001 820000EBBA R1.DIFGL.OP DIFGL logic

R2.DIFL-A.OP
DOUT_BOOL‡
FID ST
COM5-1_R2 DTYPE
DID
DIN_BOOL†
COM5-4_R2
(4A9001 8010071CAA) FID DO DI
DTYPE ST
DID 410001 800000EBBB R2.DIFL-A.OP DIFL logic

R2.DIFL-B.OP
DOUT_BOOL‡
FID ST
COM5-2_R2 DTYPE
DID
DIN_BOOL†
COM5-5_R2
(4A9001 8110071CAB) FID DO DI
DTYPE ST
DID 410001 810000EBBC R2.DIFL-B.OP DIFL logic

R2.DIFL-C.OP
DOUT_BOOL‡
FID ST
COM5-3_R2 DTYPE
DID
DIN_BOOL†
COM5-6_R2
(4A9001 8210071CAC) FID DO DI
DTYPE ST
DID 410001 820000EBBD R2.DIFL-C.OP DIFL logic

R2.DIFGL_OP
DOUT_BOOL‡
FID ST
SCOM4-SA1_R2 DTYPE
DID
DIN_BOOL†
SCOM4-SA1-R2
(4A9001 8110071C6D) FID DO DI
DTYPE ST
DID 410001 810000EBB6 R2.DIFGL.OP DIFGL logic

Figure 7.4-15 Sample logics for RDIF function at terminals


†Note:DIN_BOOL and DOUT_BOOL are used to import and export the information for
the data ID in bit type.

GRL200 (Soft 033 & 037)


- 1127 -
6F2S1914 (0.37)

8 Recording function
Contents Pages Pages
Disturbance recorder 1146 Event recorder 1138
-Data in COMTRADE 1150 -Setup 1144
-Maximum number of recording 1147 -Trigger signals 1138
-Recording signals 1147 -Trigger modes 1143
-Recording time and capacities 1146 Fault recorder 1129
-Relays within disturbance recorder 1146 -Screen information 1132
-Trigger settings for PLC 1150 -Setup 1133
-Types of recording information 1150 Transferring recording information 1154

GRL200 (Soft 033 & 037)


- 1128 -
6F2S1914 (0.37)

The recording function consists of three recording features: (1) Fault recorder, (2) Event
recorder, and (3) Disturbance recorder. The fault recorder collects the information about the
power system quantities when a fault occurs. The event recorder groups state information
when the changes are detected. The disturbance recorder is designed to memory the various
quantities—numerical analog data and logic data (binary data)—from the monitoring function
and the BIO modules; it is possible to analyze the disturbance using the engineering tool (GR-
TIMES), which can draw several chronological waves.

Fault recorder
During the fault, the fault recorder can memorize reasons by equipment failures/operation
states, system information etc. It commences by injecting a signal coming from the TRC alarm-
signal generation logic, but is also started by a trigger provided by PLC function. The fault
recorder captures the following items for each fault:
 Date and time at the fault
 Tripped phase information
 Operating mode information
 FL calculation result (if the FL function operates)
 Evolving faults (if the ARC function operates)
 Fault and pre-fault quantities

8.1.1 Types of recording information


The fault recorder can cyclically memory past eight faults; the oldest memory will be erased
cyclically if another fault occurs. The memorized information has 1ms accuracy. If a fault
occurs, the fault recorder is directed to operate to memory operating modes etc. about the fault.

(i) Date and time at fault


The date and time at the fault is recorded. The date and time information is provided by the
clock function (see Chapter Technical description: Clock function).

(ii) Tripped phase information


Information about tripped phases (i.e., faulted phases) are recorded using the recording
identifiers (‘OPT-PHASE-A,B,C, and -N’ signals), which the TRC function provides.

(iii) Mode information


At the occurrence of a fault, the protection functions gives the fault recorder the reasons of
tripping; the reasons are brought using operation identifiers† and logical signals‡. The fault
recorder can have up to 192 of all identifiers and signals in the IED. The operation identifiers
are chosen using the settings [OP Mode ID1] to [OP Mode ID128]. The settings [OP Mode
ID201] to [OP Mode ID264] are used for general purposes to record the logical signals.

GRL200 (Soft 033 & 037)


- 1129 -
6F2S1914 (0.37)

†Note:A number of the operation identifiers are provided by the protection functions. For
example, the ‘OC1-OPT-A’ operation identifier is used to identify the pickup in the
first element of the overcurrent function (OC1) in phase-A. See respective
protection functions in Chapter Relay application.
‡Note:64 logical signals are selectable for recording. For example in this purpose, the
user may choose an operation signal on the circuits of the BIO modules (BIOs).

(iv) FL calculation result


The location of the fault occurrence is recoded if the fault locator function (FL) operates.

(v) Evolving faults


The fault recorder is able to record evolving faults† during the operation of the ARC function.
Strikes number for reclosing CB is also recorded.
†Note:The evolving faults are found during the ‘ARC_IN_PROG’ signal being generating.
For more information, see Chapter Relay application: Autoreclose.

(vi) Fault quantities and pre-fault-quantities


Several quantity items (amplitude and phase angle of current, etc.) are memorized in the fault
recorder, as exemplified in Table 8.1-1 (for ‘VCT12B’ designed for 1CB†) and Table 8.1-2 (for
‘VCT11B’ designed for 1.5CB†). Quantities just before the fault are also memorized. The pre-
fault quantities are captured 10 seconds before tripping, but it is possible to take back longer
using the setting [Pre-Fault time].
†Note:For more information about the VCT construction, see Chapter Technical
description: Transformer module for AC analog input.
Table 8.1-1 Recording quantities for 1CB arrangement
Abbreviations Displayed quantities

Ia, Ib, Ic,

Iab, Ibc, Ica,


Current in phase, phase-to-phase , symmetrical, residual currents
Ie (2)

I1, I2, I0 (1)

Iem(2) Residual current in the other side of the parallel line

Va, Vb, Vc

Vab, Vbc, Vca Voltage in phase, phase-to-phase, and symmetrical

V1, V2, V0(1)

Vs, Vs2 One or two reference (busbar) voltages

Ia–L, Ib–L, Ic–L, Ie–L


Resultant currents and voltages at local-end (L) and remote-ends (R1 and R2)
Ia–R1, Ib–R1, Ic–R1, Ie–R1

GRL200 (Soft 033 & 037)


- 1130 -
6F2S1914 (0.37)

Abbreviations Displayed quantities

Ia–R2, Ib–R2, Ic–R2, Ie–R2

V1–L, V1–R1, V1–R2


Ida, Idb, Idc DIFL differential currents (Id) in three-phases
Id0 DIFL differential currents(Ido) in zero-sequence
Ira, Irb, Irc DIFGL restraining-currents (Ir) in three-phases
Ir0 DIFGL restraining-currents (Ir) in zero-sequence

Ra, Rb, Rc ,Rab, Rbc, Rca


Impedance and reactance components at Fault
Xa, Xb, Xc ,Xab, Xbc, Xca

CH1 Delay, CH2 Delay(3) Propagation delay times at port1(CH1) and port2(CH2)

CH1 DT, CH2 DT(3) Sampling difference between terminals at port1(CH1) and port2(CH2)

Table 8.1-2 Recording quantities for 1.5CB arrangement


Abbreviations Displayed quantities

IaB, IbB, IcB,

IabB, IbcB, IcaB, Current in phase, phase-to-phase , symmetrical, residual currents at busbar-CB

IeB (2) of 1.5CB arrangement

I1B, I2B, I0B (1)

IaC, IbC, IcC,

IabC, IbcC, IcaC, Current in phase, phase-to-phase , symmetrical, residual currents at center-CB

IeC(2) of 1.5CB arrangement

I1C, I2C, I0C (1)

Iem(2) Residual current in the other side of the parallel line

Va, Vb, Vc

Vab, Vbc, Vca Voltage in phase, phase-to-phase, and symmetrical

V1, V2, V0(1)

Vs, Vs2 One or two reference (busbar) voltages

Ia–L, Ib–L, Ic–L, Ie–L

Ia–R1, Ib–R1, Ic–R1, Ie–R1


Resultant currents and voltages at local-end (L) and remote-ends (R1 and R2)
Ia–R2, Ib–R2, Ic–R2, Ie–R2

V1–L, V1–R1, V1–R2


Ida, Idb, Idc DIFL differential currents (Id) in three-phases
Id0 DIFL differential currents(Ido) in zero-sequence
Ira, Irb, Irc DIFGL restraining-currents (Ir) in three-phases
Ir0 DIFGL restraining-currents (Ir) in zero-sequence

Ra, Rb, Rc ,Rab, Rbc, Rca Impedance and reactance components at Fault

GRL200 (Soft 033 & 037)


- 1131 -
6F2S1914 (0.37)

Abbreviations Displayed quantities

Xa, Xb, Xc ,Xab, Xbc, Xca

CH1 Delay, CH2 Delay(3) Propagation delay times at port1(CH1) and port2(CH2)

CH1 DT, CH2 DT(3) Sampling difference between terminals at port1(CH1) and port2(CH2)
1Note: Terms ‘I0 (i.e., 3I0)’ and ‘V0 (i.e., 3V0)’ are calculated using three-phase quantities.
2Note: The ‘Ie’ and ‘Iem’ are obtained usually with corresponding ‘Ie’ and ‘Iem’ circuits in
the VCT.
3Note: ‘CH2’ is available when two signaling modules exist in the IED, which is
dependent on the hardware. Check the ordering number at the C position
referring to the ordering (See Appendix: Ordering)

8.1.2 Screen information


Figure 8.1-1 illustrates the information displayed on the IED screen†, which can display up to
eight fault records (#1 to #8). Figure 8.1-2 illustrates the structure of the first fault record#1.
The line○
c indicates the tripped phase. The lines○
d show how tripping occurred. The lines○
f

have the information about evolving faults, which is able to memory up to 32 developing faults.
Quantitates when the fault occurred are shown below messages○ h .
g ○

Fault Record Fault Record#1


10:48 1/6 10:48 1/222
#1 2012-07-25 > 2012-07-25
10:48:21.223 10:48:21.223
#2 2012-07-21 > Phase AB
01:15:55.018 OC1, OC2, OC3, OC4
#3 2012/07/21 > SOTF–OC
13:11:29.621 FL 0.0km

List of fault records (#1 to #8) Details of #1 information

Figure 8.1-1 Information of the fault recorder displayed on the IED screen
†Note:For more screen information, see Chapter User interface: Record sub-menu. For
more information about the FL calculation, see Chapter Relay application: Single-
end fault locator.

GRL200 (Soft 033 & 037)


- 1132 -
6F2S1914 (0.37)

Fault Record#1 ○a Record Number (#1)


11:12 1/222
2012-07-25 ○b Date and Time at Fault (YYYY-MM-DD)
10:48:21.223
Phase AB ○c Tripped phase information
OC1, OC2, OC3, OC4 ○d Mode information
SOTF–OC
Screen scroll down FL 0.0km ○e FL calculation results
0% OB/NC
2012-07-25 ○f Detail information about evolving faults
10:48:22.421 ARC Shot#1 issued Deta
ARC-S1
2012-07-25
10:48:22.835 Evolving fault#1; detection made by OC1 relay
OC1
2012-07-25
10:48:23.208 ARC Shot#2 issued
ARC-S2
2012-07-25
10:48:23.649 Evolving fault#2; abandoning to reclose CB (i.e., Final Trip)
OC1, FT
Fault values ○g Fault quantities
Ia
1234.56kVa 123.4deg
Ib
1234.56kVa 123.4deg
Ic
1234.56kVa 123.4deg

PreFault values ○
h Pre-fault quantities
Ia
1234.56kVa 123.4deg
Ib
1234.56kVa 123.4deg
Ic
1234.56kVa 123.4deg

Figure 8.1-2 Screen structure about the information #1.

8.1.3 Setup for the fault recorder


(i) Operation identifiers (ID1–ID128)
The user can select the operation identifies arbitrarily using the settings [OP Mode ID1] etc.
For example, when the operation result with regard to the overcurrent relay element (i.e., OC1
in phase-A) shall be recorded, choose the operated signal ‘OC1-OPT-A (440001 800011B68)”
and set it for the [OP Mode ID1]. Remember to program the displaying name about the OC1-
OPT-A using the setting [OP Mode Name1] (e.g., “OC1-A relay OP-ed”). Note that the length
of the displaying name should be less than 18 letters. The user should find blanks in the setting
list, because several IDs have been already set.

(ii) Logical signals (ID201–ID264)


Wishing to record a logical level ‘1 (TRUE)’ or ‘0 (FALSE)’ on the circuits, the user can pick the

GRL200 (Soft 033 & 037)


- 1133 -
6F2S1914 (0.37)

logical signal using settings the [OP Mode ID265] etc. For example, the user wishes to record
the output level of the binary output circuit#1 (BO1) at the IO#1 slot, set its PLC monitoring
point ‘200B01 8002001112’ for the setting [OP Mode ID265]; set the displaying name using the
[OP Mode Name265].

(iii) Additional triggers for the recording


Wishing to start the fault recorder except for the trip instruction, the user can use the PLC
connection points ‘ADD_F.RECORD_TRIG1’ to ‘ADD_F.RECORD_TRIG4’, respectively.

(iv) Time setting for Pre-fault


The instant before the trip is programmable using the setting [Pre-Fault Time] among 10s, 50s,
100s, 200s, 300s.

(v) Unit setting for the quantities


To change the units of power quantities, go to the metering function discussed in Chapter
Metering function.

GRL200 (Soft 033 & 037)


- 1134 -
6F2S1914 (0.37)

Table 8.1-3 Default settings (ID1–ID128 and ID201–ID264) in’33’ and ‘37’ software
Settings in Fault recorder Actual PLC connection Settings in Fault recorder Actual PLC connection
Data IDs Screen names points Data IDs Screen names points
[OP Mode ID1] 410001 8000001B61 [OP Mode Name1] DIFL-A DIFL-A-OPT [OP Mode ID97] Not assigned [OP Mode Name97] - Not assigned
[OP Mode ID2] 410001 8100001B62 [OP Mode Name2] DIFL-B DIFL-B-OPT [OP Mode ID98] Not assigned [OP Mode Name98] - Not assigned
[OP Mode ID3] 410001 8200001B63 [OP Mode Name3] DIFL-C DIFL-C-OPT [OP Mode ID99] Not assigned [OP Mode Name99] - Not assigned
[OP Mode ID4] 410001 8100001B66 [OP Mode Name4] DIFstub DIFL-STUB-COND [OP Mode ID100] Not assigned [OP Mode Name100] - Not assigned
[OP Mode ID5] 410001 8200001B6E [OP Mode Name5] DIFL-R REMOTE.DIFL-OPT [OP Mode ID101] Not assigned [OP Mode Name101] - Not assigned
[OP Mode ID6] 411001 8000001B23 [OP Mode Name6] DIFGL DIFGL-TRIP [OP Mode ID102] Not assigned [OP Mode Name102] - Not assigned
[OP Mode ID7] 411001 8100001B63 [OP Mode Name7] DIFGL-R REMOTE.DIFGL-OPT [OP Mode ID103] 475001 8000011BB1 [OP Mode Name103] FRQ-S1 FRQ-S1-OPT
[OP Mode ID8] 430001 8000011B23 [OP Mode Name8] Z1S Z1S-OPT [OP Mode ID104] 475001 8100021BB1 [OP Mode Name104] FRQ-S2 FRQ-S2-OPT
[OP Mode ID9] 430001 8100061B23 [OP Mode Name9] Z1XS Z1XS-OPT [OP Mode ID105] 475001 8200031BB1 [OP Mode Name105] FRQ-S3 FRQ-S3-OPT
[OP Mode ID10] 430001 8200021B23 [OP Mode Name10] Z2S Z2S-OPT [OP Mode ID106] 475001 8300041BB1 [OP Mode Name106] FRQ-S4 FRQ-S4-OPT
[OP Mode ID11] 430001 8300031B23 [OP Mode Name11] Z3S Z3S-OPT [OP Mode ID107] 475001 8400051BB1 [OP Mode Name107] FRQ-S5 FRQ-S5-OPT
[OP Mode ID12] 430001 8400041B23 [OP Mode Name12] Z4S Z4S-OPT [OP Mode ID108] 475001 8500061BB1 [OP Mode Name108] FRQ-S6 FRQ-S6-OPT
[OP Mode ID13] 430001 8500051B23 [OP Mode Name13] Z5S Z5S-OPT [OP Mode ID109] 475001 8000111BB1 [OP Mode Name109] DFRQ-S1 DFRQ-S1-OPT
[OP Mode ID14] 430001 8300001B2B [OP Mode Name14] SOTF-ZS SOTF-ZS-TRIP [OP Mode ID110] 475001 8100121BB1 [OP Mode Name110] DFRQ-S2 DFRQ-S2-OPT
[OP Mode ID15] 431001 8000011B69 [OP Mode Name15] Z1G Z1G-OPT [OP Mode ID111] 475001 8200131BB1 [OP Mode Name111] DFRQ-S3 DFRQ-S3-OPT
[OP Mode ID16] 431001 8100061B69 [OP Mode Name16] Z1XG Z1XG-OPT [OP Mode ID112] 475001 8300141BB1 [OP Mode Name112] DFRQ-S4 DFRQ-S4-OPT
[OP Mode ID17] 431001 8200021B69 [OP Mode Name17] Z2G Z2G-OPT [OP Mode ID113] 475001 8400151BB1 [OP Mode Name113] DFRQ-S5 DFRQ-S5-OPT
[OP Mode ID1 8] 431001 8300031B69 [OP Mode Name18] Z3G Z3G-OPT [OP Mode ID114] 475001 8500161BB1 [OP Mode Name114] DFRQ-S6 DFRQ-S6-OPT
[OP Mode ID19] 431001 8400041B69 [OP Mode Name19] Z4G Z4G-OPT [OP Mode ID115] Not assigned [OP Mode Name115] - Not assigned
[OP Mode ID20] 431001 8500051B69 [OP Mode Name20] Z5G Z5G-OPT [OP Mode ID116] Not assigned [OP Mode Name116] - Not assigned
[OP Mode ID21] 431001 8300001B2B [OP Mode Name21] SOTF-ZG SOTF-ZG-TRIP [OP Mode ID117] Not assigned [OP Mode Name117] - Not assigned
[OP Mode ID22] Not assigned [OP Mode Name22] - Not assigned [OP Mode ID118] Not assigned [OP Mode Name118] - Not assigned
[OP Mode ID23] Not assigned [OP Mode Name23] - Not assigned [OP Mode ID119] Not assigned [OP Mode Name119] - Not assigned
[OP Mode ID24] Not assigned [OP Mode Name24] - Not assigned [OP Mode ID120] Not assigned [OP Mode Name120] - Not assigned
[OP Mode ID25] Not assigned [OP Mode Name25] - Not assigned [OP Mode ID121] Not assigned [OP Mode Name121] - Not assigned
[OP Mode ID26] 440001 8000011B68 [OP Mode Name26] OC1 OC1-OPT [OP Mode ID122] Not assigned [OP Mode Name122] - Not assigned
[OP Mode ID27] 440001 8100021B68 [OP Mode Name27] OC2 OC2-OPT [OP Mode ID123] Not assigned [OP Mode Name123] - Not assigned
[OP Mode ID28] 440001 8200031B68 [OP Mode Name28] OC3 OC3-OPT [OP Mode ID124] Not assigned [OP Mode Name124] - Not assigned
[OP Mode ID29] 440001 8300041B68 [OP Mode Name29] OC4 OC4-OPT [OP Mode ID125] Not assigned [OP Mode Name125] - Not assigned
[OP Mode ID30] 441001 8000011B60 [OP Mode Name30] EF1 EF1-OPT [OP Mode ID126] Not assigned [OP Mode Name126] - Not assigned
[OP Mode ID31] 441001 8100021B60 [OP Mode Name31] EF2 EF2-OPT [OP Mode ID127] Not assigned [OP Mode Name127] - Not assigned
[OP Mode ID32] 441001 8200031B60 [OP Mode Name32] EF3 EF3-OPT [OP Mode ID128] Not assigned [OP Mode Name128] - Not assigned
[OP Mode ID33] 441001 8300041B60 [OP Mode Name33] EF4 EF4-OPT [OP Mode ID201] Not assigned [OP Mode Name201] - Not assigned
[OP Mode ID34] 443001 8000011B60 [OP Mode Name34] OCN1 OCN1-OPT [OP Mode ID202] 479001 8200001B61 [OP Mode Name202] OSTV OSTV-OPT
[OP Mode ID35] 443001 8100021B60 [OP Mode Name35] OCN2 OCN2-OPT [OP Mode ID203] 478001 8200001B6A [OP Mode Name203] OSTZ OSTZ-OPT
[OP Mode ID36] 443001 8200031B60 [OP Mode Name36] OCN3 OCN3-OPT [OP Mode ID204] Not assigned [OP Mode Name204] - Not assigned
[OP Mode ID37] 443001 8300041B60 [OP Mode Name37] OCN4 OCN4-OPT [OP Mode ID205] 453001 8B00011B27 [OP Mode Name205] CBF1 CBF1-RETRIP
[OP Mode ID38] Not assigned [OP Mode Name38] - Not assigned [OP Mode ID206] 453001 8300011B23 [OP Mode Name206] CBF1-RE CBF1_TRIP
[OP Mode ID39] Not assigned [OP Mode Name39] - Not assigned [OP Mode ID207] 453001 8B00021B27 [OP Mode Name207] CBF2 CBF2-RETRIP
[OP Mode ID40] 451001 8100021B60 [OP Mode Name40] THM THM-ALARM [OP Mode ID208] 453001 8300021B23 [OP Mode Name208] CBF2-RE CBF2_TRIP
[OP Mode ID41] 451001 8000011B60 [OP Mode Name41] THM-A THM-TRIP [OP Mode ID209] 485001 8000011B60 [OP Mode Name209] DTT1 DTT1-OPT
[OP Mode ID42] 452001 8000001B60 [OP Mode Name42] BCD BCD-OPT [OP Mode ID210] 485001 8100021B60 [OP Mode Name210] DTT2 DTT2-OPT
[OP Mode ID43] 454001 8300001B23 [OP Mode Name43] SOTF-OC SOTFOC-TRIP [OP Mode ID211] Not assigned [OP Mode Name211] - Not assigned
[OP Mode ID44] 455001 8300001B23 [OP Mode Name44] STUB-OC STUBOC-TRIP [OP Mode ID212] Not assigned [OP Mode Name212] - Not assigned
[OP Mode ID45] Not assigned [OP Mode Name45] - Not assigned [OP Mode ID213] Not assigned [OP Mode Name213] - Not assigned
[OP Mode ID46] Not assigned [OP Mode Name46] - Not assigned [OP Mode ID214] Not assigned [OP Mode Name214] - Not assigned
[OP Mode ID47] Not assigned [OP Mode Name47] - Not assigned [OP Mode ID215] Not assigned [OP Mode Name215] - Not assigned
[OP Mode ID48] Not assigned [OP Mode Name48] - Not assigned [OP Mode ID216] Not assigned [OP Mode Name216] - Not assigned
[OP Mode ID49] Not assigned [OP Mode Name49] - Not assigned [OP Mode ID217] Not assigned [OP Mode Name217] - Not assigned
[OP Mode ID50] Not assigned [OP Mode Name50] - Not assigned [OP Mode ID218] Not assigned [OP Mode Name218] - Not assigned
[OP Mode ID51] Not assigned [OP Mode Name51] - Not assigned [OP Mode ID219] Not assigned [OP Mode Name219] - Not assigned
[OP Mode ID52] Not assigned [OP Mode Name52] - Not assigned [OP Mode ID220] Not assigned [OP Mode Name220] - Not assigned
[OP Mode ID53] Not assigned [OP Mode Name53] - Not assigned [OP Mode ID221] Not assigned [OP Mode Name221] - Not assigned
[OP Mode ID54] Not assigned [OP Mode Name54] - Not assigned [OP Mode ID222] Not assigned [OP Mode Name222] - Not assigned
[OP Mode ID55] Not assigned [OP Mode Name55] - Not assigned [OP Mode ID223] Not assigned [OP Mode Name223] - Not assigned
[OP Mode ID56] Not assigned [OP Mode Name56] - Not assigned [OP Mode ID224] Not assigned [OP Mode Name224] - Not assigned
[OP Mode ID57] Not assigned [OP Mode Name57] - Not assigned [OP Mode ID225] Not assigned [OP Mode Name225] - Not assigned
[OP Mode ID58] Not assigned [OP Mode Name58] - Not assigned [OP Mode ID226] Not assigned [OP Mode Name226] - Not assigned
[OP Mode ID59] Not assigned [OP Mode Name59] - Not assigned [OP Mode ID227] Not assigned [OP Mode Name227] - Not assigned
[OP Mode ID60] Not assigned [OP Mode Name60] - Not assigned [OP Mode ID228] Not assigned [OP Mode Name228] - Not assigned
[OP Mode ID61] Not assigned [OP Mode Name61] - Not assigned [OP Mode ID229] Not assigned [OP Mode Name229] - Not assigned
[OP Mode ID62] Not assigned [OP Mode Name62] - Not assigned [OP Mode ID230] Not assigned [OP Mode Name230] - Not assigned
[OP Mode ID63] Not assigned [OP Mode Name63] - Not assigned [OP Mode ID231] Not assigned [OP Mode Name231] - Not assigned
[OP Mode ID64] Not assigned [OP Mode Name64] - Not assigned [OP Mode ID232] Not assigned [OP Mode Name232] - Not assigned
[OP Mode ID65] Not assigned [OP Mode Name65] - Not assigned [OP Mode ID233] 4A6001 8000011B63 [OP Mode Name233] SPAR1 ARC1_MODE_SPAR
[OP Mode ID66] Not assigned [OP Mode Name66] - Not assigned [OP Mode ID234] 4A6001 8100011B64 [OP Mode Name234] TPAR1 ARC1_TPAR
[OP Mode ID67] Not assigned [OP Mode Name67] - Not assigned [OP Mode ID235] 4A6001 8200011B65 [OP Mode Name235] ORGAR1 ARC1_ORGAR
[OP Mode ID68] Not assigned [OP Mode Name68] - Not assigned [OP Mode ID236] Not assigned [OP Mode Name236] - Not assigned
[OP Mode ID69] Not assigned [OP Mode Name69] - Not assigned [OP Mode ID237] 4A6001 8100011B67 [OP Mode Name237] ARC-S2 ARC1 SHOT2
[OP Mode ID70] Not assigned [OP Mode Name70] - Not assigned [OP Mode ID238] 4A6001 8200011B68 [OP Mode Name238] ARC-S3 ARC1 SHOT3
[OP Mode ID71] 460101 8000011B65 [OP Mode Name71] OV1 OV1-OPT [OP Mode ID239] 4A6001 8300011B69 [OP Mode Name239] ARC-S4 ARC1 SHOT4
[OP Mode ID72] 460101 8100021B65 [OP Mode Name72] OV2 OV2-OPT [OP Mode ID240] 4A6001 8400011B6A [OP Mode Name240] ARC-S5 ARC1 SHOT5
[OP Mode ID73] Not assigned [OP Mode Name73] - Not assigned [OP Mode ID241] 4A6001 8400011B6E [OP Mode Name241] FT1 ARC1 FT
[OP Mode ID74] Not assigned [OP Mode Name74] - Not assigned [OP Mode ID242] 4A6001 8700011B70 [OP Mode Name242] AR1 ARC1 RESET
[OP Mode ID75] 461101 8000011B65 [OP Mode Name75] OVS1 OVS1-OPT [OP Mode ID243] 4A6001 8C00011B71 [OP Mode Name243] AF1 ARC1 CLOSE FAIL
[OP Mode ID76] 461101 8100021B65 [OP Mode Name76] OVS2 OVS2-OPT [OP Mode ID244] 4A6001 8000011B72 [OP Mode Name244] AS1 ARC1 CLOSE SUCCESS
[OP Mode ID77] Not assigned [OP Mode Name77] - Not assigned [OP Mode ID245] 4A6001 8000021B63 [OP Mode Name245] SPAR2 ARC2_SPAR
[OP Mode ID78] Not assigned [OP Mode Name78] - Not assigned [OP Mode ID246] 4A6001 8100021B64 [OP Mode Name246] TPAR2 ARC2_TPAR
[OP Mode ID79] 462101 8000011B60 [OP Mode Name79] OVG1 OVG1-OPT [OP Mode ID247] 4A6001 8200021B65 [OP Mode Name247] ORGAR2 ARC2_ORGAR
[OP Mode ID80] 462101 8100021B60 [OP Mode Name80] OVG2 OVG2-OPT [OP Mode ID248] Not assigned [OP Mode Name248] - Not assigned
[OP Mode ID81] Not assigned [OP Mode Name81] - Not assigned [OP Mode ID249] 4A6001 8400021B6A [OP Mode Name249] FT2 ARC2 FT
[OP Mode ID82] Not assigned [OP Mode Name82] - Not assigned [OP Mode ID250] 4A6001 8700021B6C [OP Mode Name250] AR2 ARC2 RESET
[OP Mode ID83] Not assigned [OP Mode Name83] - Not assigned [OP Mode ID251] 4A6001 8C00021B6D [OP Mode Name251] AF2 ARC2 CLOSE FAIL
[OP Mode ID84] Not assigned [OP Mode Name84] - Not assigned [OP Mode ID252] 4A6001 8000021B6E [OP Mode Name252] AS2 ARC2 CLOSE SUCCESS
[OP Mode ID85] Not assigned [OP Mode Name85] - Not assigned [OP Mode ID253] 4A6001 8300001B64 [OP Mode Name253] EXT-STA EXT.ARC_START
[OP Mode ID86] Not assigned [OP Mode Name86] - Not assigned [OP Mode ID254] Not assigned [OP Mode Name254] - Not assigned
[OP Mode ID87] Not assigned [OP Mode Name87] - Not assigned [OP Mode ID255] Not assigned [OP Mode Name255] - Not assigned
[OP Mode ID88] Not assigned [OP Mode Name88] - Not assigned [OP Mode ID256] Not assigned [OP Mode Name256] - Not assigned
[OP Mode ID89] Not assigned [OP Mode Name89] - Not assigned [OP Mode ID257] Not assigned [OP Mode Name257] - Not assigned
[OP Mode ID90] Not assigned [OP Mode Name90] - Not assigned [OP Mode ID258] Not assigned [OP Mode Name258] - Not assigned
[OP Mode ID91] 470101 8000011B65 [OP Mode Name91] UV1 UV1-OPT [OP Mode ID259] Not assigned [OP Mode Name259] - Not assigned
[OP Mode ID92] 470101 8100021B65 [OP Mode Name92] UV2 UV2-OPT [OP Mode ID260] Not assigned [OP Mode Name260] - Not assigned
[OP Mode ID93] Not assigned [OP Mode Name93] - Not assigned [OP Mode ID261] Not assigned [OP Mode Name261] - Not assigned
[OP Mode ID94] Not assigned [OP Mode Name94] - Not assigned [OP Mode ID262] Not assigned [OP Mode Name262] - Not assigned
[OP Mode ID95] 471101 8000011B65 [OP Mode Name95] UVS1 UVS1-OPT [OP Mode ID263] Not assigned [OP Mode Name263] - Not assigned
[OP Mode ID96] 471101 8100021B65 [OP Mode Name96] UVS2 UVS2-OPT [OP Mode ID264] Not assigned [OP Mode Name264] - Not assigned

GRL200 (Soft 033 & 037)


- 1135 -
6F2S1914 (0.37)

8.1.4 Scheme logic


The operation of the fault recorder can be directed by the TRC function, protection functions
(FC1 to FC40†), and the PLC function, as shown in Figure 8.1-3.
Fault recorder
Clock function Date & Time & Date and time at fault

Metering function Quantities in the power system & Quantities at fault

From TRC OPT-PHASE-A OPT/PHASE-A & Operating in phase-A

OPT-PHASE-B OPT/PHASE-B &


Operating in phase-B
Operating
OPT-PHASE-C OPT/PHASE-C & mode
Operating in phase-C

OPT-PHASE-N OPT/PHASE-N & Operating in phase-N

TRIP COMMAND1-A TRIP COMMAND1-A & Tripping in phase-A

TRIP COMMAND1-B TRIP COMMAND1-B Trip phases


& Tripping in phase-B in CB1

TRIP COMMAND1-C TRIP COMMAND1-C & Tripping in phase-C


TRIP COMMAND CB2 -A TRIP COMMAND2-A & Tripping in phase-A
TRIP COMMAND CB2 -B TRIP COMMAND2-B Trip phases
&
Tripping in phase-B in CB2
TRIP COMMAND CB2 -C TRIP COMMAND2-C &
Tripping in phase-C

GEN.TRIP_ALARM OP.MODE-GET

From ARC 0 t
ARC INPROG F.RECORD_TRIG_SPRED
0. 1s
8020001001 1 Drop Off
802000E001 ADD_F.RECORD_TRIG1
8120011001 0.01s
812001E001 ADD_F.RECORD_TRIG2
≥1 ≥1
1 ≥1
8220021001
Drop Off
822002E001 ADD_F.RECORD_TRIG3
8320031001 1s
832003E001 ADD_F.RECORD_TRIG4 Pick Up
1
≥1
Drop Off
0.01s
From protection function #1(FC1)
FC1_OPT_AR Identifier signals &
FC1_OPT_BR (FC*_OPT_*) coming Setting [OP Mode ID1] Operation mode information recorded
FC1_OPT_CR from protection functions when GEN.TRIP_ALARM signal is
(FC*) are detected & generated in the TRC function
FC1_OPT_ABR changing the logic level Setting [OP Mode ID2]
FC1_OPT_BCR “0(Un-operated)” to
FC1_OPT_CAR “1(Operated)”. &
Setting [OP Mode ID3]
From protection function #2(FC2)
FC1_OPT_AR
FC1_OPT_BR
FC1_OPT_CR Signals about the
FC1_OPT_ABR operation modes in the
FC1_OPT_BCR protection functions are &
set. Setting [OP Mode ID128]
FC1_OPT_CAR
Setting [OP Mode ID1]
&
Setting [OP Mode ID2] Setting [OP Mode ID201]

From protection function #40(FC40) &


Setting [OP Mode ID202]
FC40_OPT_AR
FC40_OPT_BR
FC40_OPT_CR
FC40_OPT_ABR
Setting [OP Mode ID264] &
FC40_OPT_BCR Setting [OP Mode ID264]
FC40_OPT_CAR

Figure 8.1-3 Fault record circuit


†Note:The correspondences table for the FC numbers are discussed in Chapter Relay
application: Trip circuit.

GRL200 (Soft 033 & 037)


- 1136 -
6F2S1914 (0.37)

8.1.5 Setting
FAULT_RECORD(Function ID: 200602)
Setting items Range Unit Contents Default Note

Pre-Fault Time 10s/ 50 / 100 / 200 /


Sec. Recording time before the fault 10
300
Op Mode Name1 (Preferred name) – Name of the operation mode for ID1
Op Mode ID1 (Preferred DataID) – Signal of the operation identifier
Op Mode Name2 (Preferred name) – Name of the operation mode for ID2
Op Mode ID2 (Preferred DataID) – Signal of the operation identifier2
Op Mode Name3 (Preferred name) – Name of the operation mode for ID3
Op Mode ID3 (Preferred DataID) – Signal of the operation identifier3 See setting table
…… …… – …… in this section
…… …… – ……
…… …… – ……
…… …… – ……
Op Mode Name264 (Preferred name) – Name of the operation mode for ID264
Op Mode ID264 (Preferred DataID) – Signal of the operation identifier264

8.1.6 Signal (Data ID)


 Signal monitoring point
FAULT_RECORD (Function ID: 200602)
Name Element ID Description
ADD_F.RECORD_TRIG1 8020001001 Receiving Trigger1

ADD_F.RECORD_TRIG2 8120011001 Receiving Trigger2

ADD_F.RECORD_TRIG3 8220021001 Receiving Trigger3

ADD_F.RECORD_TRIG4 8320031001 Receiving Trigger4

FAULT RECORD TRIG1 8000011001 TRIG1 signal generated

FAULT RECORD TRIG3 8200031001 TRIG3 signal generated

FLTRCDING 8020101001 Data writing in the fault recorder

FR_CLR 3000001001 Data erasing in the fault recorder

 Connection point on PLC logic


FAULT_RECORD (Function ID: 200602)
Name Element ID Description
ADD_F.RECORD_TRIG1 802000E001 Input1 for the external trigger

ADD_F.RECORD_TRIG2 812001E001 Input2 for the external trigger

ADD_F.RECORD_TRIG3 822002E001 Input3 for the external trigger

ADD_F.RECORD_TRIG4 832003E001 Input4 for the external trigger

GRL200 (Soft 033 & 037)


- 1137 -
6F2S1914 (0.37)

Event recorder
Signals are generated in the logics of BIO modules etc. in the IED. The event recorder can
memory the generated signals as events. To operate the event recorder, the user should pick a
preferred signal as a trigger of the event recorder; the event recorder can have 768 triggers,
some of which have been set as a default. The user can group the triggers into three categories;
consequently, it is possible that a number of the events are divided depending on the degree of
the errors, the meaning of the operations, and the signals of relay elements, etc. The user can
also program how an event is to be detected. An event is recorded with millisecond accuracy.
The information are memorized until the number of the events reaching 1024; the oldest event
will be deleted when a new event appears.

8.2.1 Trigger signals


The event is memorized when the event recorder detects changing the trigger signal that is
connected with the logic signal; they are defined using settings [Trigger ID1] to [Trigger ID768].
Settings [End of E.Record-1] and [End of E.Record-2] are provided for grouping†; the user can
adjust the size of the ‘Event Record1’ group using the [End of E.Record-1]. The next ‘Event
Record2’ group is set with the [End of E.Record-2]. The remains are set for the ‘Event Record3’
group. Remember that the [Trigger ID1] etc. are required to set together with the [Event
Name1] etc.; user’s preferred names should be less than 18 letters.
July 25, 2012 July 26, 2012
10:31:12 Deleting the fault record 12:34:51 Deleting the fault record
Setting [End of E.Record-1] = 256
Setting [End of E.Record-2] = 512 10:56:12 Changing system setting

Pulse train
3000001001
FR_CLR List of ‘Event record1’
FAULT RECORD (200602)
Event #3
On 2012-07-25 10:31:12
Event #3 F.Record clear ‘On’

Setting [Trigger ID14] = 200602 3000001001


Setting [Trigger Mode14] = On
Setting [Event Name14] = F.Record clear

Event #2
3010001001
Active group Active group
2012-07-25 10:56:12
SYS_CHG Set group change
‘3’ Changed to ‘4’
Setting_PF (201400)
Event #2

Setting [Trigger ID7] = 201400 3010001001 Event #1


Setting [Trigger Mode7] = Change On 2012-07-26 12:34:51
Setting [Event Name7] = Set group change
Event #1 F.Record clear ‘On’

Figure 8.2-1 Relation between function signals and triggers for Event record1

Figure 8.2-1 illustrates signals connected with triggers in the event recorder. For example,
‘SYS_CHG’ is connected with trigger#7 using the [Trigger ID7] and ‘FR_CLR’ is connected with

GRL200 (Soft 033 & 037)


- 1138 -
6F2S1914 (0.37)

trigger#14 using the [Trigger ID14]. Note that the both triggers (#7 and #14) are smaller than
the setting [End of E.Record-1]=256; hence, the both are listed in the ‘Event recored1’ list.
Keep in mind that the event names are set by the [Event Name7] and [Event Name14]. All
ones are tabulated in Table 8.2-1 to Table 8.2-3.

†Note:The GR-TIEMS uses terms ‘Level1’, ‘Level2’, and ‘Level3’ to represent the ‘Event
Record1’, ‘Event Record2’, and ‘Event Record3’. The scope of each level is the same
as the scope of each group. The GR-TIEMS does not show unused triggers and
Trigger ID numbers automatically when the triggers are displayed on the screen.

GRL200 (Soft 033 & 037)


- 1139 -
6F2S1914 (0.37)

Table 8.2-1 Event1 group with [End of E.Record-1]=256 in ‘33’ & ‘37’ software
Triggers Data IDs Modes Names Triggers Data IDs Modes Names Triggers Data IDs Modes Names

[Trigger ID1] 220001 3110201001 On-Off Serious error [Trigger ID91] (Not Assigned) Off - [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 220001 3110211001 On-Off ErrorLevel2 [Trigger ID92] (Not Assigned) Off - [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 220001 3110221001 On-Off Minor error [Trigger ID93] (Not Assigned) Off - [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 220001 3110231001 On-Off ErrorLevel4 [Trigger ID94] (Not Assigned) Off - [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 220001 3110241001 On-Off ErrorLevel5 [Trigger ID95] (Not Assigned) Off - [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not Assigned) Off - [Trigger ID96] (Not Assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 201400 3200001001 Change Set. group change [Trigger ID97] (Not Assigned) Off - [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 201400 3010001001 On System set. change [Trigger ID98] (Not Assigned) Off - [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 201400 3010011001 On Comm. set. change [Trigger ID99] (Not Assigned) Off - [Trigger ID189] 432001 8000001BB0 On-Off Z1CNT_MPROT
[Trigger ID10] 201400 3010021001 On Prot. set. change [Trigger ID100] (Not Assigned) Off - [Trigger ID190] 432001 8000001B62 On-Off Z1CNT-TPBLK
[Trigger ID11] 201400 3010031001 On Ctrl. set. change [Trigger ID101] (Not Assigned) Off - [Trigger ID191] 432001 8100001B63 On-Off Z1CNT-3PTP
[Trigger ID12] (Not Assigned) Off - [Trigger ID102] (Not Assigned) Off - [Trigger ID192] 432001 8200001B64 On-Off Z1CNT-ARCBLK
[Trigger ID13] (Not Assigned) Off - [Trigger ID103] (Not Assigned) Off - [Trigger ID193] 432001 8300001B65 On-Off Z1CNT-INSTOP
[Trigger ID14] 200602 3000001001 On F.Record clear [Trigger ID104] (Not Assigned) Off - [Trigger ID194] No Assign Off -
[Trigger ID15] 200710 3001001001 On E.Record1 clear [Trigger ID105] (Not Assigned) Off - [Trigger ID195] 410001 8F00001BB2 On-Off DIFL_BLOCK
[Trigger ID16] 200710 3002001001 On E.Record2 clear [Trigger ID106] (Not Assigned) Off - [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 200710 3003001001 On E.Record3 clear [Trigger ID107] (Not Assigned) Off - [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 20040130A0001001 On D.Record clear [Trigger ID108] (Not Assigned) Off - [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not Assigned) Off - [Trigger ID109] (Not Assigned) Off - [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not Assigned) Off - [Trigger ID110] (Not Assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not Assigned) Off - [Trigger ID111] (Not Assigned) Off - [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not Assigned) Off - [Trigger ID112] (Not Assigned) Off - [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not Assigned) Off - [Trigger ID113] (Not Assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not Assigned) Off - [Trigger ID114] (Not Assigned) Off - [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not Assigned) Off - [Trigger ID115] (Not Assigned) Off - [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not Assigned) Off - [Trigger ID116] (Not Assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not Assigned) Off - [Trigger ID117] (Not Assigned) Off - [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not Assigned) Off - [Trigger ID118] (Not Assigned) Off - [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not Assigned) Off - [Trigger ID119] (Not Assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not Assigned) Off - [Trigger ID120] (Not Assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not Assigned) Off - [Trigger ID121] (Not Assigned) Off - [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not Assigned) Off - [Trigger ID122] (Not Assigned) Off - [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not Assigned) Off - [Trigger ID123] (Not Assigned) Off - [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not Assigned) Off - [Trigger ID124] (Not Assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not Assigned) Off - [Trigger ID125] (Not Assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not Assigned) Off - [Trigger ID126] (Not Assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not Assigned) Off - [Trigger ID127] (Not Assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not Assigned) Off - [Trigger ID128] (Not Assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not Assigned) Off - [Trigger ID129] 48A001 8000001B73 On-Off CB1-A_CLOSE [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not Assigned) Off - [Trigger ID130] 48A001 8100001B74 On-Off CB1-B_CLOSE [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not Assigned) Off - [Trigger ID131] 48A001 8200001B75 On-Off CB1-C_CLOSE [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not Assigned) Off - [Trigger ID132] 48A001 8000001B7C On-Off CB2-A_CLOSE [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not Assigned) Off - [Trigger ID133] 48A001 8100001B7D On-Off CB2-B_CLOSE [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not Assigned) Off - [Trigger ID134] 48A001 8200001B7E On-Off CB2-C_CLOSE [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not Assigned) Off - [Trigger ID135] 48A001 8E00001B85 On-Off DS_CLOSE [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not Assigned) Off - [Trigger ID136] 48A001 8000001B9C On-Off DEAD_LINE_DETECT [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not Assigned) Off - [Trigger ID137] (Not Assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not Assigned) Off - [Trigger ID138] 4A6001 8000011B60 On-Off ARC1 READY [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not Assigned) Off - [Trigger ID139] 4A6001 8000021B60 On-Off ARC2 READY [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not Assigned) Off - [Trigger ID140] 4A6001 8200001BB4 On-Off ARC_BLOCK [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not Assigned) Off - [Trigger ID141] 4A6001 8000001BB3 On-Off ARC NO ACT [Trigger ID231] 453001 8000011BB0 On-Off EXT.CBF1_START-A
[Trigger ID52] (Not Assigned) Off - [Trigger ID142] 4A6001 8000001BB0 On-Off EXT.ARC_START-A [Trigger ID232] 453001 8100011BB1 On-Off EXT.CBF1_START-B
[Trigger ID53] (Not Assigned) Off - [Trigger ID143] 4A6001 8100001BB1 On-Off EXT.ARC_START-B [Trigger ID233] 453001 8200011BB2 On-Off EXT.CBF1_START-C
[Trigger ID54] (Not Assigned) Off - [Trigger ID144] 4A6001 8200001BB2 On-Off EXT.ARC_START-C [Trigger ID234] 453001 8000021BB0 On-Off EXT.CBF2_START-A
[Trigger ID55] (Not Assigned) Off - [Trigger ID145] 4A6001 8000011B6C On-Off ARC1 CLOSE COMMAND [Trigger ID235] 453001 8100021BB1 On-Off EXT.CBF2_START-B
[Trigger ID56] (Not Assigned) Off - [Trigger ID146] 4A6001 8100021B68 On-Off ARC2 CLOSE COMMAND [Trigger ID236] 453001 8200021BB2 On-Off EXT.CBF2_START-C
[Trigger ID57] (Not Assigned) Off - [Trigger ID147] (Not Assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] (Not Assigned) Off - [Trigger ID148] 490001 8000001B61 On-Off VTF DETECT [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] (Not Assigned) Off - [Trigger ID149] 490001 8100001BB1 On-Off EXTERNAL VTF [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] (Not Assigned) Off - [Trigger ID150] (Not Assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not Assigned) Off - [Trigger ID151] 491001 8000001B62 On-Off CTF DETECT [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not Assigned) Off - [Trigger ID152] 491001 8100001BB1 On-Off EXTERNAL CTF [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not Assigned) Off - [Trigger ID153] (Not Assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not Assigned) Off - [Trigger ID154] 4A0001 8000001B6C On-Off GEN.TRIP-A [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not Assigned) Off - [Trigger ID155] 4A0001 8100001B6D On-Off GEN.TRIP-B [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not Assigned) Off - [Trigger ID156] 4A0001 8200001B6E On-Off GEN.TRIP-C [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not Assigned) Off - [Trigger ID157] 4A0001 8300001B6F On-Off GEN.TRIP [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not Assigned) Off - [Trigger ID158] 4A0001 8400001B64 On-Off GEN.ALARM [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not Assigned) Off - [Trigger ID159] 4A0001 8000001B71 On-Off OPT.PHASE-A [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not Assigned) Off - [Trigger ID160] 4A0001 8100001B72 On-Off OPT.PHASE-B [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] (Not Assigned) Off - [Trigger ID161] 4A0001 8200001B73 On-Off OPT.PHASE-C [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] (Not Assigned) Off - [Trigger ID162] 4A0001 8300001B74 On-Off OPT.PHASE-N [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] (Not Assigned) Off - [Trigger ID163] (Not Assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] (Not Assigned) Off - [Trigger ID164] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] (Not Assigned) Off - [Trigger ID165] (Not Assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] (Not Assigned) Off - [Trigger ID166] (Not Assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not Assigned) Off - [Trigger ID167] (Not Assigned) Off -
[Trigger ID78] (Not Assigned) Off - [Trigger ID168] (Not Assigned) Off -
[Trigger ID79] (Not Assigned) Off - [Trigger ID169] (Not Assigned) Off -
[Trigger ID80] (Not Assigned) Off - [Trigger ID170] (Not Assigned) Off -
[Trigger ID81] (Not Assigned) Off - [Trigger ID171] (Not Assigned) Off -
[Trigger ID82] (Not Assigned) Off - [Trigger ID172] (Not Assigned) Off -
[Trigger ID83] (Not Assigned) Off - [Trigger ID173] (Not Assigned) Off -
[Trigger ID84] (Not Assigned) Off - [Trigger ID174] (Not Assigned) Off -
[Trigger ID85] (Not Assigned) Off - [Trigger ID175] (Not Assigned) Off -
[Trigger ID86] (Not Assigned) Off - [Trigger ID176] (Not Assigned) Off -
[Trigger ID87] (Not Assigned) Off - [Trigger ID177] (Not Assigned) Off -
[Trigger ID88] (Not Assigned) Off - [Trigger ID178] (Not Assigned) Off -
[Trigger ID89] (Not Assigned) Off - [Trigger ID179] (Not Assigned) Off -
[Trigger ID90] (Not Assigned) Off - [Trigger ID180] (Not Assigned) Off -

GRL200 (Soft 033 & 037)


- 1140 -
6F2S1914 (0.37)

Table 8.2-2 Event2 group with [End of E.Record-1]=256 and [End of E.Record-2]=512
Triggers Data IDs Modes Names Triggers Data IDs Modes Names Triggers Data IDs Modes Names

[Trigger ID257] (Not Assigned) Off - [Trigger ID347] (Not Assigned) Off - [Trigger ID437] (Not Assigned) Off -
[Trigger ID258] (Not Assigned) Off - [Trigger ID348] (Not Assigned) Off - [Trigger ID438] (Not Assigned) Off -
[Trigger ID259] (Not Assigned) Off - [Trigger ID349] (Not Assigned) Off - [Trigger ID439] (Not Assigned) Off -
[Trigger ID260] (Not Assigned) Off - [Trigger ID350] (Not Assigned) Off - [Trigger ID440] (Not Assigned) Off -
[Trigger ID261] (Not Assigned) Off - [Trigger ID351] (Not Assigned) Off - [Trigger ID441] (Not Assigned) Off -
[Trigger ID262] (Not Assigned) Off - [Trigger ID352] (Not Assigned) Off - [Trigger ID442] (Not Assigned) Off -
[Trigger ID263] (Not Assigned) Off - [Trigger ID353] (Not Assigned) Off - [Trigger ID443] (Not Assigned) Off -
[Trigger ID264] (Not Assigned) Off - [Trigger ID354] (Not Assigned) Off - [Trigger ID444] (Not Assigned) Off -
[Trigger ID265] (Not Assigned) Off - [Trigger ID355] (Not Assigned) Off - [Trigger ID445] (Not Assigned) Off -
[Trigger ID266] (Not Assigned) Off - [Trigger ID356] (Not Assigned) Off - [Trigger ID446] (Not Assigned) Off -
[Trigger ID267] (Not Assigned) Off - [Trigger ID357] (Not Assigned) Off - [Trigger ID447] (Not Assigned) Off -
[Trigger ID268] (Not Assigned) Off - [Trigger ID358] (Not Assigned) Off - [Trigger ID448] (Not Assigned) Off -
[Trigger ID269] (Not Assigned) Off - [Trigger ID359] (Not Assigned) Off - [Trigger ID449] (Not Assigned) Off -
[Trigger ID270] (Not Assigned) Off - [Trigger ID360] (Not Assigned) Off - [Trigger ID450] (Not Assigned) Off -
[Trigger ID271] (Not Assigned) Off - [Trigger ID361] (Not Assigned) Off - [Trigger ID451] (Not Assigned) Off -
[Trigger ID272] (Not Assigned) Off - [Trigger ID362] (Not Assigned) Off - [Trigger ID452] (Not Assigned) Off -
[Trigger ID273] (Not Assigned) Off - [Trigger ID363] (Not Assigned) Off - [Trigger ID453] (Not Assigned) Off -
[Trigger ID274] (Not Assigned) Off - [Trigger ID364] (Not Assigned) Off - [Trigger ID454] (Not Assigned) Off -
[Trigger ID275] (Not Assigned) Off - [Trigger ID365] (Not Assigned) Off - [Trigger ID455] (Not Assigned) Off -
[Trigger ID276] (Not Assigned) Off - [Trigger ID366] (Not Assigned) Off - [Trigger ID456] (Not Assigned) Off -
[Trigger ID277] (Not Assigned) Off - [Trigger ID367] (Not Assigned) Off - [Trigger ID457] (Not Assigned) Off -
[Trigger ID278] (Not Assigned) Off - [Trigger ID368] (Not Assigned) Off - [Trigger ID458] (Not Assigned) Off -
[Trigger ID279] (Not Assigned) Off - [Trigger ID369] (Not Assigned) Off - [Trigger ID459] (Not Assigned) Off -
[Trigger ID280] (Not Assigned) Off - [Trigger ID370] (Not Assigned) Off - [Trigger ID460] (Not Assigned) Off -
[Trigger ID281] (Not Assigned) Off - [Trigger ID371] (Not Assigned) Off - [Trigger ID461] (Not Assigned) Off -
[Trigger ID282] (Not Assigned) Off - [Trigger ID372] (Not Assigned) Off - [Trigger ID462] (Not Assigned) Off -
[Trigger ID283] (Not Assigned) Off - [Trigger ID373] (Not Assigned) Off - [Trigger ID463] (Not Assigned) Off -
[Trigger ID284] (Not Assigned) Off - [Trigger ID374] (Not Assigned) Off - [Trigger ID464] (Not Assigned) Off -
[Trigger ID285] (Not Assigned) Off - [Trigger ID375] (Not Assigned) Off - [Trigger ID465] (Not Assigned) Off -
[Trigger ID286] (Not Assigned) Off - [Trigger ID376] (Not Assigned) Off - [Trigger ID466] (Not Assigned) Off -
[Trigger ID287] (Not Assigned) Off - [Trigger ID377] (Not Assigned) Off - [Trigger ID467] (Not Assigned) Off -
[Trigger ID288] (Not Assigned) Off - [Trigger ID378] (Not Assigned) Off - [Trigger ID468] (Not Assigned) Off -
[Trigger ID289] (Not Assigned) Off - [Trigger ID379] (Not Assigned) Off - [Trigger ID469] (Not Assigned) Off -
[Trigger ID290] (Not Assigned) Off - [Trigger ID380] (Not Assigned) Off - [Trigger ID470] (Not Assigned) Off -
[Trigger ID291] (Not Assigned) Off - [Trigger ID381] (Not Assigned) Off - [Trigger ID471] (Not Assigned) Off -
[Trigger ID292] (Not Assigned) Off - [Trigger ID382] (Not Assigned) Off - [Trigger ID472] (Not Assigned) Off -
[Trigger ID293] (Not Assigned) Off - [Trigger ID383] (Not Assigned) Off - [Trigger ID473] (Not Assigned) Off -
[Trigger ID294] (Not Assigned) Off - [Trigger ID384] (Not Assigned) Off - [Trigger ID474] (Not Assigned) Off -
[Trigger ID295] (Not Assigned) Off - [Trigger ID385] (Not Assigned) Off - [Trigger ID475] (Not Assigned) Off -
[Trigger ID296] (Not Assigned) Off - [Trigger ID386] (Not Assigned) Off - [Trigger ID476] (Not Assigned) Off -
[Trigger ID297] (Not Assigned) Off - [Trigger ID387] (Not Assigned) Off - [Trigger ID477] (Not Assigned) Off -
[Trigger ID298] (Not Assigned) Off - [Trigger ID388] (Not Assigned) Off - [Trigger ID478] (Not Assigned) Off -
[Trigger ID299] (Not Assigned) Off - [Trigger ID389] (Not Assigned) Off - [Trigger ID479] (Not Assigned) Off -
[Trigger ID300] (Not Assigned) Off - [Trigger ID390] (Not Assigned) Off - [Trigger ID480] (Not Assigned) Off -
[Trigger ID301] (Not Assigned) Off - [Trigger ID391] (Not Assigned) Off - [Trigger ID481] (Not Assigned) Off -
[Trigger ID302] (Not Assigned) Off - [Trigger ID392] (Not Assigned) Off - [Trigger ID482] (Not Assigned) Off -
[Trigger ID303] (Not Assigned) Off - [Trigger ID393] (Not Assigned) Off - [Trigger ID483] (Not Assigned) Off -
[Trigger ID304] (Not Assigned) Off - [Trigger ID394] (Not Assigned) Off - [Trigger ID484] (Not Assigned) Off -
[Trigger ID305] (Not Assigned) Off - [Trigger ID395] (Not Assigned) Off - [Trigger ID485] (Not Assigned) Off -
[Trigger ID306] (Not Assigned) Off - [Trigger ID396] (Not Assigned) Off - [Trigger ID486] (Not Assigned) Off -
[Trigger ID307] (Not Assigned) Off - [Trigger ID397] (Not Assigned) Off - [Trigger ID487] (Not Assigned) Off -
[Trigger ID308] (Not Assigned) Off - [Trigger ID398] (Not Assigned) Off - [Trigger ID488] (Not Assigned) Off -
[Trigger ID309] (Not Assigned) Off - [Trigger ID399] (Not Assigned) Off - [Trigger ID489] (Not Assigned) Off -
[Trigger ID310] (Not Assigned) Off - [Trigger ID400] (Not Assigned) Off - [Trigger ID490] (Not Assigned) Off -
[Trigger ID311] (Not Assigned) Off - [Trigger ID401] (Not Assigned) Off - [Trigger ID491] (Not Assigned) Off -
[Trigger ID312] (Not Assigned) Off - [Trigger ID402] (Not Assigned) Off - [Trigger ID492] (Not Assigned) Off -
[Trigger ID313] (Not Assigned) Off - [Trigger ID403] (Not Assigned) Off - [Trigger ID493] (Not Assigned) Off -
[Trigger ID314] (Not Assigned) Off - [Trigger ID404] (Not Assigned) Off - [Trigger ID494] (Not Assigned) Off -
[Trigger ID315] (Not Assigned) Off - [Trigger ID405] (Not Assigned) Off - [Trigger ID495] (Not Assigned) Off -
[Trigger ID316] (Not Assigned) Off - [Trigger ID406] (Not Assigned) Off - [Trigger ID496] (Not Assigned) Off -
[Trigger ID317] (Not Assigned) Off - [Trigger ID407] (Not Assigned) Off - [Trigger ID497] (Not Assigned) Off -
[Trigger ID318] (Not Assigned) Off - [Trigger ID408] (Not Assigned) Off - [Trigger ID498] (Not Assigned) Off -
[Trigger ID319] (Not Assigned) Off - [Trigger ID409] (Not Assigned) Off - [Trigger ID499] (Not Assigned) Off -
[Trigger ID320] (Not Assigned) Off - [Trigger ID410] (Not Assigned) Off - [Trigger ID500] (Not Assigned) Off -
[Trigger ID321] (Not Assigned) Off - [Trigger ID411] (Not Assigned) Off - [Trigger ID501] (Not Assigned) Off -
[Trigger ID322] (Not Assigned) Off - [Trigger ID412] (Not Assigned) Off - [Trigger ID502] (Not Assigned) Off -
[Trigger ID323] (Not Assigned) Off - [Trigger ID413] (Not Assigned) Off - [Trigger ID503] (Not Assigned) Off -
[Trigger ID324] (Not Assigned) Off - [Trigger ID414] (Not Assigned) Off - [Trigger ID504] (Not Assigned) Off -
[Trigger ID325] (Not Assigned) Off - [Trigger ID415] (Not Assigned) Off - [Trigger ID505] (Not Assigned) Off -
[Trigger ID326] (Not Assigned) Off - [Trigger ID416] (Not Assigned) Off - [Trigger ID506] (Not Assigned) Off -
[Trigger ID327] (Not Assigned) Off - [Trigger ID417] (Not Assigned) Off - [Trigger ID507] (Not Assigned) Off -
[Trigger ID328] (Not Assigned) Off - [Trigger ID418] (Not Assigned) Off - [Trigger ID508] (Not Assigned) Off -
[Trigger ID329] (Not Assigned) Off - [Trigger ID419] (Not Assigned) Off - [Trigger ID509] (Not Assigned) Off -
[Trigger ID330] (Not Assigned) Off - [Trigger ID420] (Not Assigned) Off - [Trigger ID510] (Not Assigned) Off -
[Trigger ID331] (Not Assigned) Off - [Trigger ID421] (Not Assigned) Off - [Trigger ID511] (Not Assigned) Off -
[Trigger ID332] (Not Assigned) Off - [Trigger ID422] (Not Assigned) Off - [Trigger ID512] (Not Assigned) Off -
[Trigger ID333] (Not Assigned) Off - [Trigger ID423] (Not Assigned) Off -
[Trigger ID334] (Not Assigned) Off - [Trigger ID424] (Not Assigned) Off -
[Trigger ID335] (Not Assigned) Off - [Trigger ID425] (Not Assigned) Off -
[Trigger ID336] (Not Assigned) Off - [Trigger ID426] (Not Assigned) Off -
[Trigger ID337] (Not Assigned) Off - [Trigger ID427] (Not Assigned) Off -
[Trigger ID338] (Not Assigned) Off - [Trigger ID428] (Not Assigned) Off -
[Trigger ID339] (Not Assigned) Off - [Trigger ID429] (Not Assigned) Off -
[Trigger ID340] (Not Assigned) Off - [Trigger ID430] (Not Assigned) Off -
[Trigger ID341] (Not Assigned) Off - [Trigger ID431] (Not Assigned) Off -
[Trigger ID342] (Not Assigned) Off - [Trigger ID432] (Not Assigned) Off -
[Trigger ID343] (Not Assigned) Off - [Trigger ID433] (Not Assigned) Off -
[Trigger ID344] (Not Assigned) Off - [Trigger ID434] (Not Assigned) Off -
[Trigger ID345] (Not Assigned) Off - [Trigger ID435] (Not Assigned) Off -
[Trigger ID346] (Not Assigned) Off - [Trigger ID436] (Not Assigned) Off -

GRL200 (Soft 033 & 037)


- 1141 -
6F2S1914 (0.37)

Table 8.2-3 Event3 group with [End of E.Record-2]=512


Triggers Data IDs Modes Names Triggers Data IDs Modes Names Triggers Data IDs Modes Names

[Trigger ID513] (Not Assigned) Off - [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] (Not Assigned) Off - [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] (Not Assigned) Off - [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] (Not Assigned) Off - [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] (Not Assigned) Off - [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] (Not Assigned) Off - [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] (Not Assigned) Off - [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] (Not Assigned) Off - [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] (Not Assigned) Off - [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] (Not Assigned) Off - [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] (Not Assigned) Off - [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] (Not Assigned) Off - [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] (Not Assigned) Off - [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] (Not Assigned) Off - [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] (Not Assigned) Off - [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] (Not Assigned) Off - [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] (Not Assigned) Off - [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] (Not Assigned) Off - [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] (Not Assigned) Off - [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] (Not Assigned) Off - [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] (Not Assigned) Off - [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] (Not Assigned) Off - [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] (Not Assigned) Off - [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] (Not Assigned) Off - [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] (Not Assigned) Off - [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] (Not Assigned) Off - [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] (Not Assigned) Off - [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] (Not Assigned) Off - [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] (Not Assigned) Off - [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] (Not Assigned) Off - [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] (Not Assigned) Off - [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] (Not Assigned) Off - [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] (Not Assigned) Off - [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] (Not Assigned) Off - [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] (Not Assigned) Off - [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] (Not Assigned) Off - [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] (Not Assigned) Off - [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] (Not Assigned) Off - [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] (Not Assigned) Off - [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] (Not Assigned) Off - [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] (Not Assigned) Off - [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] (Not Assigned) Off - [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] (Not Assigned) Off - [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] (Not Assigned) Off - [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] (Not Assigned) Off - [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] (Not Assigned) Off - [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] (Not Assigned) Off - [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] (Not Assigned) Off - [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] (Not Assigned) Off - [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] (Not Assigned) Off - [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] (Not Assigned) Off - [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] (Not Assigned) Off - [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] (Not Assigned) Off - [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] (Not Assigned) Off - [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] (Not Assigned) Off - [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] (Not Assigned) Off - [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] (Not Assigned) Off - [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] (Not Assigned) Off - [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] (Not Assigned) Off - [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] (Not Assigned) Off - [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] (Not Assigned) Off - [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] (Not Assigned) Off - [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] (Not Assigned) Off - [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] (Not Assigned) Off - [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] (Not Assigned) Off - [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not Assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not Assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] (Not Assigned) Off - [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] (Not Assigned) Off - [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] (Not Assigned) Off - [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] (Not Assigned) Off - [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] (Not Assigned) Off - [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] (Not Assigned) Off - [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] (Not Assigned) Off - [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] (Not Assigned) Off - [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] (Not Assigned) Off - [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] (Not Assigned) Off - [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] (Not Assigned) Off - [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] (Not Assigned) Off - [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] (Not Assigned) Off - [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] (Not Assigned) Off - [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] (Not Assigned) Off - [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] (Not Assigned) Off - [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] (Not Assigned) Off - [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] (Not Assigned) Off - [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] (Not Assigned) Off - [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] (Not Assigned) Off - [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] (Not Assigned) Off - [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] (Not Assigned) Off - [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not Assigned) Off - [Trigger ID692] (Not Assigned) Off -

GRL200 (Soft 033 & 037)


- 1142 -
6F2S1914 (0.37)

8.2.2 Trigger modes


We can simplify the trigger signals into four: ‘On’, ‘Off ’, ‘On and Off ’, and ‘Change’ modes. Thus,
the user can should set a mode for respective triggers using [Trigger Mode1] and others.

(i) ‘On’ mode


In the ‘On’ mode, the event recorder can take an action when the trigger signal is switched to
‘On’, as shown in Figure 8.2-2. For the operation, set On for the [Trigger Mode*].
On
Pulse train
Off

Triggers generated Triggers generated Triggers generated

Figure 8.2-2 Trigger generated at ‘On’ mode

(ii) ‘Off’ mode


The ‘Off ’ mode is the other way of the ‘On’ mode; set Off for the operation.
On
Pulse train
Off

Triggers generated Triggers generated Triggers generated

Figure 8.2-3 Trigger generated at ‘Off’ mode

(iii) ‘On-Off’ mode


In the ‘On-Off ’ mode, the trigger signal is generated when the pulse train is changed from ‘On
to Off ’ and ‘Off to On’ both, as shown in Figure 8.2-4. Set On-Off for the operation
On
Pulse train
Off

Triggers generated Triggers generated Triggers generated

Figure 8.2-4 Trigger generated at ‘On-Off’ mode

(iv) ‘Change’ mode


The ‘Change mode’ is provided to detect the increment or the decrement of a number, where
the PLC logic generates. For example, this mode allows to detect the change of group settings

GRL200 (Soft 033 & 037)


- 1143 -
6F2S1914 (0.37)

(e.g., the ‘SYS_CHG’ signal; which has been connected with the trigger#9 using the setting
[Trigger ID9], as default; we have been discussed in Chapter Technical description: Group
setting for protection functions.)

8.2.3 Screen information


Figure 8.2-5 illustrates the structure about the ‘Event Recored1’ group, which can be shown
the latest event#1 at the top structure (line ○
b ). The lines ○
c and ○
d describes how an event

occurred for the event#1. Preceding event#2, event#3, etc. are shown below the event#1.
Similarly, the information about the ‘Event Record2’ and ‘Event Record3’ groups are displayed
on the IED screen.
†Note:For more information about the screen operation, see Chapter User interface:
Record sub-menu.

Event Record1 ○
a Event record1 list
10:48 1/4
#1 2012-07-26 ○
b The latest event#1
12:34:51.223
F.Record clear ○
c Trigger information
On ○
d Trigger mode information
#2 2012-07-25
Screen scroll down 10:56:12.021

e Event#2

Set group change


4
#3 2012-07-25 ○
f Event#3
10:31:12.159
F.Record clear
On
#4 2012-07-23 ○
g Event#4
23:56:12.159

Figure 8.2-5 Event information grouped in the Event record1

8.2.4 Setup for the event recorder


Consider that a trip-command, which is denoted with Data ID ‘4A1001 8300001B6F’, should
be sorted into the ‘Event record1’ group. The settings [End of E.Record-1]=256 and [End of
E.Record-2]=512 have been made as default; hence, we may select it with the trigger#157 by
setting the [Trigger ID157]= ‘4A1001 8300001B6F’. Set On-OFF for the [Trigger Mode157],
because the pulse-train of the trip command should be recorded along the pick-up and drop-off
times. Remember that the preferred name for the Trigger ID157 should be set using the [Event
Name157].

GRL200 (Soft 033 & 037)


- 1144 -
6F2S1914 (0.37)

8.2.5 Setting
EVENTRECORD(Function ID: 200710)
Setting items Range Unit Contents Default Note

End of E.Record-1 0 to 768 – The last position of the event group1 (Level1) 256
End of E.Record-2 0 to 768 – The last position of the event group2 (Level2) 512
Trigger ID1 (Preferred DataID) – Trigger signal1 for the operation
On / Off / On-Off /
Tigger Mode1 – Mode setting for the detection
Change
Event name1 (Preferred name) – Name of the trigger signal1
Trigger ID2 (Preferred DataID) – Trigger signal2 for the operation
On / Off / On-Off /
Tigger Mode2 – Mode setting for the detection
Change
See tables in this
Event name2 (Preferred name) – Name of the trigger signal2
section
…… …… – ……
…… …… – ……
…… …… – ……
Trigger ID768 (Preferred DataID) – Trigger signal768 for the operation
On / Off / On-Off /
Tigger Mode768 – Mode setting for the detection
Change
Event name768 (Preferred name) – Name of the trigger signal768

8.2.6 Signal (Data ID)


 Signal monitoring point
EVENTRECORD (Function ID: 200710)
Name Element ID Description
ER1_CLR 3001001001 Clearing the data in Event group1

ER2_CLR 3002001001 Clearing the data in Event group2

ER3_CLR 3003001001 Clearing the data in Event group3

POWER ON 3100001001 Detection of switch On

GRL200 (Soft 033 & 037)


- 1145 -
6F2S1914 (0.37)

Disturbance recorder
Disturbance recorder is to record the phenomenon about the occurrences of the fault with 1ms
accuracy; the disturbance recorder is operated with the reception of the TRC trip command.
The disturbance recorder has exclusive overcurrent and other relays; thus, they can also start
the disturbance recorder when the exclusive relays detects abnormal phenomenon.
Additionally, the disturbance recorder can accept the instruction of the PLC function using
settings. The recording time and the sampling time are programmable; thus, the measuring
values about currents, voltage, frequency, and logic signals are collected in accordance with
the recording and the sampling times. The logic signals are also memorized during the
disturbance phenomenon; the disturbance recorder can hold up to 256 signals. The recording
number of the disturbance phenomena is limited by the recording and sampling times.

8.3.1 Recording time and amount


(i) Time settings
Period of the recording is set using the [Record Time]. The disturbance recorder can operate
before the occurrence of the fault; the time before the fault occurrence can be set using the
[Pre-fault Time]. The user can choose a time among 0.1 sec. to 10.0 sec.
Setting [Record Time]

Setting [Pre-fault time]


Fault

Pre-fault information Succeeding formation

Start of recording Trip command issued End of recording

Figure 8.3-1 Period of recording time


(ii) Sampling rate setting
Sampling time is defined with setting [Sampling rate]; it can be can choose from 7.5 electrical
degree to 15.0 electrical degree. For example, if the user set 7.5 for the [Sampling rate], the
disturbance recorder starts to collect the date in the sampling rate (2400Hz) in 50Hz system.

(iii) Trip command setting


As shown in Figure 8.3-1, the disturbance recorder starts when the trip command is issued,
provided On is set for the [Trip Trig.Sw]. If the disturbance recorder shall not start with the
trip command, set Off.

8.3.2 Relays within disturbance recorder


Four relays are provided in the disturbance recorder exclusively: OC-DRT, EF-DRT, UV-DRT,
and UVS-DRT relays.

GRL200 (Soft 033 & 037)


- 1146 -
6F2S1914 (0.37)

(i) OC-DRT relay setting


An overcurrent relay within the disturbance recorder (OC-DRT) is provided. The user should
set a pick-up value for the relay to commence the disturbance recorder. Use the setting [OC-
DRT]; then set On for the [OC-DRT-EN] if this relay operation is required to commence the
recording.

(ii) EF-DRT relay setting


An earth fault relay (EF-DRT) is provided; set the pick-up value for the [EF-DRT]; then set On
for the [EF-DRT-EN].

(iii) UV-DRT relay setting


An under-voltage relay (Line-ground) (UV-DRT) is provided. Set the value for the [UV-DRT];
then set On for the [UV-DRT-EN].

(iv) UVS-DRT relay setting


An under-voltage relay (Line-Line) (UVS-DRT) is provided. Set the value for the [UVS-DRT];
then set On for the [UVS-DRT-EN].

8.3.3 Maximum number for recording disturbance phenomena


Note that the maximum number for recording the disturbance phenomena depends on the
recording time and the sampling rate. Table 8.3-1 illustrates the maximum number. For
example, the 77 phenomena can be memorized in the disturbance recorder, when the [Record
Time] =1 and the [Sampling Rate] =7.5° elec., if the IED operates in 50Hz system. The user
can also check the maximum number on the IED screen (See Figure 8.3-2).
Table 8.3-1 Max number depending on time settings
Recording Max. recording number for Disturbance phenomena
period set with Setting [Sampling Rate] in 50Hz sys. Setting [Sampling Rate] in 60Hz sys.
[Record Time] 7.5º 15º 7.5º 15º
1 sec 77 151 64 126
3 sec 26 51 21 43
5 sec 15 31 13 26

8.3.4 Number of analog quantities and logical signals for disturbance recorder
Ten analog quantities and 256 logical signals are record in a disturbance phenomenon.
(i) Number of analog quantities
For example, when VCT11B is used in the IED, currents (Ia, Ib, Ic, Ie, Iem) and the voltages
(Va, Vb, Vc, Vs, Vs2) are recorded. For more information about the VCT, see Chapter Technical
description: Transformer module for AC analog input.

GRL200 (Soft 033 & 037)


- 1147 -
6F2S1914 (0.37)

Table 8.3-2 Recording number of logic signals depending on time settings


VCT type 11B 12B
Va Va
Vb Vb
Voltages Vc Vc
Vs Vs
Vs2 Vs2
Ia Ia
Ib Ib
Currents Ic Ic
Ie Ie
Iem Iem
Number of recording 10 10

(ii) Number of logical signals


As mentioned earlier, the disturbance recorder can hold the traces of logic signals during the
recording time. Using settings [Binary Signal*], the user can select 256 logic signal arbitrary.
The logic signals that the user has selected should be termed with user’s preferred names using
settings [Binary Sig.Name*]. For example, ‘CB1-A_CLOSE’ signal of the PROT_COMM
function may be chosen to record using the setting [Binary Signal1]; we should term it ‘CB1-
A_CLOSE’ using the [Binary Sig.Name1]. Table 8.3-3 tabulates the default settings.

GRL200 (Soft 033 & 037)


- 1148 -
6F2S1914 (0.37)

Table 8.3-3 Setting list for logic signals in ’33, 37’ software
[Binar
[Binary Sig. Origi Origin
Settings Data IDs [Binary Sig. Name] Origins Settings Data IDs Settings Data IDs y Sig.
Name] ns s
Name]
[Binary Signal1] 48A001 8000001B73 CB1-A_CLOSE PROT_COMM [Binary Signal91] (Not Assigned) - …. [Binary Signal191] (Not Assigned) - ….
[Binary Signal2] 48A001 8100001B74 CB1-B_CLOSE PROT_COMM [Binary Signal92] (Not Assigned) - …. [Binary Signal192] (Not Assigned) - ….
[Binary Signal3] 48A001 8200001B75 CB1-C_CLOSE PROT_COMM [Binary Signal93] (Not Assigned) - …. [Binary Signal193] (Not Assigned) - ….
[Binary Signal4] 48A001 8000001B7C CB2-A_CLOSE PROT_COMM [Binary Signal94] (Not Assigned) - …. [Binary Signal194] (Not Assigned) - ….
[Binary Signal5] 48A001 8100001B7D CB2-B_CLOSE PROT_COMM [Binary Signal95] (Not Assigned) - …. [Binary Signal195] (Not Assigned) - ….
[Binary Signal6] 48A001 8200001B7E CB2-C_CLOSE PROT_COMM [Binary Signal96] (Not Assigned) - …. [Binary Signal196] (Not Assigned) - ….
[Binary Signal7] 48A001 8E00001B85 DS_CLOSE PROT_COMM [Binary Signal97] (Not Assigned) - …. [Binary Signal197] (Not Assigned) - ….
[Binary Signal8] 4A0001 8300001B6F GEN.TRIP TRC [Binary Signal98] (Not Assigned) - …. [Binary Signal198] (Not Assigned) - ….
[Binary Signal9] 4A0001 8000001B6C GEN.TRIP-A TRC [Binary Signal99] (Not Assigned) - …. [Binary Signal199] (Not Assigned) - ….
[Binary Signal10] 4A0001 8100001B6D GEN.TRIP-B TRC [Binary Signal100] (Not Assigned) - …. [Binary Signal200] (Not Assigned) - ….
[Binary Signal11] 4A0001 8200001B6E GEN.TRIP-C TRC [Binary Signal101] (Not Assigned) - …. [Binary Signal201] (Not Assigned) - ….
[Binary Signal12] 4A0001 8400001B64 GEN.ALARM TRC [Binary Signal102] (Not Assigned) - …. [Binary Signal202] (Not Assigned) - ….
[Binary Signal13] 490001 8000001B61 VTF_DETECT VTF [Binary Signal103] (Not Assigned) - …. [Binary Signal203] (Not Assigned) - ….
[Binary Signal14] 491001 8000001B62 CTF_DETECT CTF [Binary Signal104] (Not Assigned) - …. [Binary Signal204] (Not Assigned) - ….
[Binary Signal15] 410001 8000001B20 DIFL-TRIP-A DIFL [Binary Signal105] (Not Assigned) - …. [Binary Signal205] (Not Assigned) - ….
[Binary Signal16] 410001 8100001B21 DIFL-TRIP-B DIFL [Binary Signal106] (Not Assigned) - …. [Binary Signal206] (Not Assigned) - ….
[Binary Signal17] 410001 8200001B22 DIFL-TRIP-C DIFL [Binary Signal107] (Not Assigned) - …. [Binary Signal207] (Not Assigned) - ….
[Binary Signal18] 411001 8000001B23 DIFLG-TRIP DIFLG [Binary Signal108] (Not Assigned) - …. [Binary Signal208] (Not Assigned) - ….
[Binary Signal19] 4A9001 8000111C30 RY_BLOCK-CH1 COMM_APPL [Binary Signal109] (Not Assigned) - …. [Binary Signal209] (Not Assigned) - ….
[Binary Signal20] 4A9001 8100111C31 RY_BLOCK-CH2 COMM_APPL [Binary Signal110] (Not Assigned) - …. [Binary Signal210] (Not Assigned) - ….
[Binary Signal21] 430001 8300011B63 Z1S-ORX ZS [Binary Signal111] (Not Assigned) - …. [Binary Signal211] (Not Assigned) - ….
[Binary Signal22] 430001 8700061B63 Z1XS-ORX ZS [Binary Signal112] (Not Assigned) - …. [Binary Signal212] (Not Assigned) - ….
[Binary Signal23] 430001 8300021B63 Z2S-ORX ZS [Binary Signal113] (Not Assigned) - …. [Binary Signal213] (Not Assigned) - ….
[Binary Signal24] 430001 8700031B63 Z3S-ORX ZS [Binary Signal114] (Not Assigned) - …. [Binary Signal214] (Not Assigned) - ….
[Binary Signal25] 430001 8B00041B63 Z4S-ORX ZS [Binary Signal115] (Not Assigned) - …. [Binary Signal215] (Not Assigned) - ….
[Binary Signal26] 430001 8B00051B63 Z5S-ORX ZS [Binary Signal116] (Not Assigned) - …. [Binary Signal216] (Not Assigned) - ….
[Binary Signal27] 430001 8000011B23 Z1S-OPT ZS [Binary Signal117] (Not Assigned) - …. [Binary Signal217] (Not Assigned) - ….
[Binary Signal28] 430001 8100061B23 Z1XS-OPT ZS [Binary Signal118] (Not Assigned) - …. [Binary Signal218] (Not Assigned) - ….
[Binary Signal29] 430001 8200021B23 Z2S-OPT ZS [Binary Signal119] (Not Assigned) - …. [Binary Signal219] (Not Assigned) - ….
[Binary Signal30] 430001 8300031B23 Z3S-OPT ZS [Binary Signal120] (Not Assigned) - …. [Binary Signal220] (Not Assigned) - ….
[Binary Signal31] 430001 8400041B23 Default ZS [Binary Signal121] (Not Assigned) - …. [Binary Signal221] (Not Assigned) - ….
[Binary Signal32] 430001 8500051B23 Z5S-OPT ZS [Binary Signal122] (Not Assigned) - …. [Binary Signal222] (Not Assigned) - ….
[Binary Signal33] 430001 8000081B61 PSBS_DET ZS [Binary Signal123] (Not Assigned) - …. [Binary Signal223] (Not Assigned) - ….
[Binary Signal34] 431001 8300011B63 Z1G-ORX ZG [Binary Signal124] (Not Assigned) - …. [Binary Signal224] (Not Assigned) - ….
[Binary Signal35] 431001 8700061B63 Z1XG-ORX ZG [Binary Signal125] (Not Assigned) - …. [Binary Signal225] (Not Assigned) - ….
[Binary Signal36] 431001 8300021B63 Z2G-ORX ZG [Binary Signal126] (Not Assigned) - …. [Binary Signal226] (Not Assigned) - ….
[Binary Signal37] 431001 8700031B63 Z3G-ORX ZG [Binary Signal127] (Not Assigned) - …. [Binary Signal227] (Not Assigned) - ….
[Binary Signal38] 431001 8B00041B63 Z4G-ORX ZG [Binary Signal128] (Not Assigned) - …. [Binary Signal228] (Not Assigned) - ….
[Binary Signal39] 431001 8B00051B63 Z5G-ORX ZG [Binary Signal129] (Not Assigned) - …. [Binary Signal229] (Not Assigned) - ….
[Binary Signal40] 431001 8000011B69 Z1G-OPT ZG [Binary Signal130] (Not Assigned) - …. [Binary Signal230] (Not Assigned) - ….
[Binary Signal41] 431001 8100061B69 Z1XG-OPT ZG [Binary Signal131] (Not Assigned) - …. [Binary Signal231] (Not Assigned) - ….
[Binary Signal42] 431001 8200021B69 Z2G-OPT ZG [Binary Signal132] (Not Assigned) - …. [Binary Signal232] (Not Assigned) - ….
[Binary Signal43] 431001 8300031B69 Z3G-OPT ZG [Binary Signal133] (Not Assigned) - …. [Binary Signal233] (Not Assigned) - ….
[Binary Signal44] 431001 8400041B69 Z4G-OPT ZG [Binary Signal134] (Not Assigned) - …. [Binary Signal234] (Not Assigned) - ….
[Binary Signal45] 431001 8500051B69 Z5G-OPT ZG [Binary Signal135] (Not Assigned) - …. [Binary Signal235] (Not Assigned) - ….
[Binary Signal46] 431001 8000081B70 PSBG_DET ZG [Binary Signal136] (Not Assigned) - …. [Binary Signal236] (Not Assigned) - ….
[Binary Signal47] 4A6001 8000011B60 ARC1_READY ARC [Binary Signal137] (Not Assigned) - …. [Binary Signal237] (Not Assigned) - ….
[Binary Signal48] 4A6001 8000021B60 ARC2_READY ARC [Binary Signal138] (Not Assigned) - …. [Binary Signal238] (Not Assigned) - ….
[Binary Signal49] 4A6001 8000011B6C ARC1_CLOSE_COMMAND ARC [Binary Signal139] (Not Assigned) - …. [Binary Signal239] (Not Assigned) - ….
[Binary Signal50] 4A6001 8100021B68 ARC2_CLOSE_COMMAND ARC [Binary Signal150] (Not Assigned) - …. [Binary Signal250] (Not Assigned) - ….
[Binary Signal51] 4A6001 8400011B6E ARC1_FT ARC [Binary Signal151] (Not Assigned) - …. [Binary Signal251] (Not Assigned) - ….
[Binary Signal52] 4A6001 8400021B6A ARC2_FT ARC [Binary Signal152] (Not Assigned) - …. [Binary Signal252] (Not Assigned) - ….
[Binary Signal53] 4A6001 8200001BB4 ARC_BLOCK ARC [Binary Signal153] (Not Assigned) - …. [Binary Signal253] (Not Assigned) - ….
[Binary Signal54] 440001 8000011B68 OC1-OPT OC [Binary Signal154] (Not Assigned) - …. [Binary Signal254] (Not Assigned) - ….
[Binary Signal55] 440001 8100021B68 OC2-OPT OC [Binary Signal155] (Not Assigned) - …. [Binary Signal255] (Not Assigned) - ….
[Binary Signal56] 440001 8200031B68 OC3-OPT OC [Binary Signal156] (Not Assigned) - …. [Binary Signal256] (Not Assigned) - ….
[Binary Signal57] 440001 8300041B68 OC4-OPT OC [Binary Signal157] (Not Assigned) - ….
[Binary Signal58] 441001 8000011B60 EF1-OPT EF [Binary Signal158] (Not Assigned) - ….
[Binary Signal59] 441001 8100021B60 EF2-OPT EF [Binary Signal159] (Not Assigned) - ….
[Binary Signal60] 441001 8200031B60 EF3-OPT EF [Binary Signal160] (Not Assigned) - ….
[Binary Signal61] 441001 8300041B60 EF4-OPT EF [Binary Signal161] (Not Assigned) - ….
[Binary Signal62] 443001 8000011B60 OCN1-OPT OCN [Binary Signal162] (Not Assigned) - ….
[Binary Signal63] 443001 8100021B60 OCN2-OPT OCN [Binary Signal163] (Not Assigned) - ….
[Binary Signal64] 443001 8200031B60 OCN3-OPT OCN [Binary Signal164] (Not Assigned) - ….
[Binary Signal65] 443001 8300041B60 OCN4-OPT OCN [Binary Signal165] (Not Assigned) - ….
[Binary Signal66] 460101 8000011B65 OV1-OPT OV [Binary Signal166] (Not Assigned) - ….
[Binary Signal67] 460101 8100021B65 OV2-OPT OV [Binary Signal167] (Not Assigned) - ….
[Binary Signal68] (Not Assigned) - …. [Binary Signal168] (Not Assigned) - ….
[Binary Signal69] (Not Assigned) - …. [Binary Signal169] (Not Assigned) - ….
[Binary Signal70] 461101 8000011B65 OVS1-OPT OVS [Binary Signal170] (Not Assigned) - ….
[Binary Signal71] 461101 8100021B65 OVS2-OPT OVS [Binary Signal171] (Not Assigned) - ….
[Binary Signal72] (Not Assigned) - …. [Binary Signal172] (Not Assigned) - ….
[Binary Signal73] (Not Assigned) - …. [Binary Signal173] (Not Assigned) - ….
[Binary Signal74] 462101 8000011B60 OVG1-OPT OVG [Binary Signal174] (Not Assigned) - ….
[Binary Signal75] 462101 8100021B60 OVG2-OPT OVG [Binary Signal175] (Not Assigned) - ….
[Binary Signal76] (Not Assigned) - …. [Binary Signal176] (Not Assigned) - ….
[Binary Signal77] (Not Assigned) - …. [Binary Signal177] (Not Assigned) - ….
[Binary Signal78] 470101 8000011B65 UV1-OPT UV [Binary Signal178] (Not Assigned) - ….
[Binary Signal79] 470101 8100021B65 UV2-OPT UV [Binary Signal179] (Not Assigned) - ….
[Binary Signal80] (Not Assigned) - …. [Binary Signal180] (Not Assigned) - ….
[Binary Signal81] (Not Assigned) - …. [Binary Signal181] (Not Assigned) - ….
[Binary Signal82] 471101 8000011B65 UVS1-OPT UVS [Binary Signal182] (Not Assigned) - ….
[Binary Signal83] 471101 8100021B65 UVS2-OPT UVS [Binary Signal183] (Not Assigned) - ….
[Binary Signal84] 48A001 8000001B73 CB1-A_CLOSE PROT_COMM [Binary Signal184] (Not Assigned) - ….
[Binary Signal85] (Not Assigned) - …. [Binary Signal185] (Not Assigned) - ….
[Binary Signal86] (Not Assigned) - …. [Binary Signal186] (Not Assigned) - ….
[Binary Signal87] (Not Assigned) - …. [Binary Signal187] (Not Assigned) - ….
[Binary Signal88] (Not Assigned) - …. [Binary Signal188] (Not Assigned) - ….
[Binary Signal89] (Not Assigned) - …. [Binary Signal189] (Not Assigned) - ….
[Binary Signal90] (Not Assigned) - …. [Binary Signal190] (Not Assigned) - ….

GRL200 (Soft 033 & 037)


- 1149 -
6F2S1914 (0.37)

8.3.5 Trigger settings for PLC programming


If the PLC program instructs the operation of the disturbance recorder, the user should set the
[Trigger ID1] to [Trigger ID4]. That is, the program-output points should be set for the settings
[Trigger ID1] to [Trigger ID4]; then, set On for the [Trigger SW1] to [Trigger SW4], respectively.

8.3.6 Screen information


Figure 8.3-2 indicates the maximum number of the recording operations as the number is
changed depending on the time settings, which are shown in Table 8.3-1. Figure 8.3-3 shows
the operation time and the date for the disturbance recorder and the figure illustrates five
disturbance phenomena have been memorized in the IED.

Disturbance Record
10:48 1/2
_Record List >
Number of items
5/77
Clear Records +
Max. recording number for Disturbance phenomena
Operating counter

Figure 8.3-2 Running counter and Max number in the disturbance recorder

Disturbance Record
10:48 1/5
#1 2012-07-25 ○
a Disturbance record#1
10:48:21.223
#2 2012-07-21 ○
b Disturbance record#2
01:15:55.018
#3 2012/07/21 ○
c Disturbance record#3
Screen scroll down 13:11:29.621
#4 2012-07-02 ○
d Disturbance record#4
23:32:09.015
#5 2012-06-20 ○
e Disturbance record#5
09:37:48.915

Figure 8.3-3 Detail information in the disturbance recorder

The information in the disturbance recorder are managed in the COMTRADE format,
hence, the user can transferor the disturbance recording file to the PC using the engineering
tool ‘GR-TIEMS’. Figure 8.3-4 shows the example of the GR-TIMES screen. For more
information, see Chapter Engineering tool.

GRL200 (Soft 033 & 037)


- 1150 -
6F2S1914 (0.37)

Figure 8.3-4 Screen shot from GR-TIEMS

8.3.7 Interpolation of transferred data


Information data will be recorded in COMTRADE every cycle defined by the setting [Sampling
Rate]. When remote information is distributed by the telecommunication†, the recorder also
records the remote data along the local data in the COMTRATE. If the remote data is
transferred at different cycle, the recorder cannot record the remote data with own [Sampling
rate] (for example, if remote data is received at every 30 electrical deg., the recorder cannot
record the remote and local data at the same time if the recorder operates in 7.5 deg. cycle). In
order that the recorder can have the coordination between different cycles, the disturbance
recorder can generates complementary data for the data generated at different cycle. The user
should set On for the setting [Interpolate mode] for this operation.
†Note:For the remote information, see Chapter Relay application: Transmission control
function (DIF_COMM).

GRL200 (Soft 033 & 037)


- 1151 -
6F2S1914 (0.37)

8.3.8 Setting
DISTURB_REC(Function ID: 200401)
Setting items Range Unit Contents Default Note

Record Time 0.1 - 10.0 s Time for disturbance recording 3.0


Pre-fault Time 0.1 - 10.0 s Pre-fault time 0.3
Sampling Rate 7.5 / 15 deg Sampling electrical degree for recording 15
Interpolate Mode Off / On – Sampling data interpolated in 15 degree Off
Trip Trig.SW Off / On – Operation with the TRC trip command On

DISTURB_REC(Function ID: 200401)


Setting items Range Unit Contents Default Note

Binary Signal1 (Preferred DataID) – Logic signal1 for the operation


Binary Sig.Name1 (Preferred name) – Name of the logic signal1
Binary Signal2 (Preferred DataID) – Logic signal2 for the operation
Binary Sig.Name2 (Preferred name) – Name of the logic signal2
Binary Signal3 (Preferred DataID) – Logic signal3 for the operation See Setting table
Binary Sig.Name3 (Preferred name) – Name of the logic signal3 in this section
…… …… – ……
…… …… – ……
Binary Signal256 (Preferred DataID) – Mode setting for the detection
Binary Sig.Name256 (Preferred name) – Name of the trigger signal768

DRT_LP(Function ID: 4B0001)


Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OC-DRT-EN Off / On – Disturbance Record Trigger OC-DRT enable Off
OC-DRT 0.10 - 0.50 - OC-DRT relay operating value
A 1.00 5.00
50.00 250.00
EF-DRT-EN Off / On – Disturbance Record Trigger EF-DRT enable Off
EF-DRT 0.10 - 0.50 - EF-DRT relay operating value
A 0.20 1.00
50.00 250.00
UV-DRT-EN Off / On – Disturbance Record Trigger UV-DRT enable Off
UV-DRT 5.0 - 130.0 – UV-DRT relay operating value 0.20
UVS-DRT-EN Off / On – Disturbance Record Trigger UVS-DRT enable Off
UVS-DRT 5.0 - 130.0 V UVS-DRT relay operating value 51.0

GRL200 (Soft 033 & 037)


- 1152 -
6F2S1914 (0.37)

8.3.9 Signal (Data ID)


 Signal monitoring point
DRT_LP (Function ID: 4B0001)
Element ID Name Description
8000001C20 DRT-LP DRT-LP protection operated

8400021C23 EF-DRT EF-DRT relay element operated

8000011C20 OC-DRT-A OC-DRT relay element operated (phase-A)

8100011C21 OC-DRT-B OC-DRT relay element operated (phase-B)

8200011C22 OC-DRT-C OC-DRT relay element operated (phase-C)

8800031C20 UV-DRT-A UV-DRT relay element operated (phase-A)

8900031C21 UV-DRT-B UV-DRT relay element operated (phase-B)

8A00031C22 UV-DRT-C UV-DRT relay element operated (phase-C)

8C00041C20 UVS-DRT-AB UVS-DRT relay element operated (phase-AB)

8D00041C21 UVS-DRT-BC UVS-DRT relay element operated (phase-BC)

8E00041C22 UVS-DRT-CA UVS-DRT relay element operated (phase-CA)

 Signal monitoring point


DISTURB_REC (Function ID: 200401)
Element ID Name Description
80A0041001 DSTRING Writing the disturbance data

30A0001001 DSTR_CLR Data erased

80A0031001 DSTR_MADE Completion for writing the disturbance data

32A0011001 DSTR_MAX Maximum possible number of the operations

32A0021001 DSTR_NUM Operation counter

GRL200 (Soft 033 & 037)


- 1153 -
6F2S1914 (0.37)

Transferred information during fault


The IED can transfer the information during the fault in the IEC61850 communication†.

†Note:The transferring is only available in the IEC61850 Editon1 with option or


Editon2. For the information about the option, see Chapter Communication
protocol: IEC 61850 communication: About protocol, separately.

GRL200 (Soft 033 & 037)


- 1154 -
6F2S1914 (0.37)

8.4.1 Transferred metering values


Table 8.4-1 shows transferring information during the fault†. When the IED is running on the
IEC61850 Edition1 option, these signals should be mapped for Private Object AnInDatUpd.
When the IED is running on the IEC61850 Editon2, they should be mapped for Normal Object
AnIn.
Table 8.4-1 Transferred values taken during the fault
Signals Transferring data (✓) depending on VCT
Items Unit
names VCT12B (for 1CB) VCT11B(for 1.5CB)
Ia or IaB (Primary) FLTMS0001 A ✓(Ia) ✓(IaB)
Ib or IbB (Primary) FLTMS0004 A ✓(Ib) ✓(IbB)
Ic or IcB (Primary) FLTMS0007 A ✓(Ic) ✓(IcB)
Iab or IabB (Primary) FLTMS0010 A ✓(Iab) ✓(IabB)
Ibc or IbcB (Primary) FLTMS0013 A ✓(Ibc) ✓(IbcB)
Ica or IcaB (Primary) FLTMS0016 A ✓(Ica) ✓(IcaB)
Ie or IeB (Primary) FLTMS0019 A ✓(Ie) ✓(IeB)
I1 or I1B (Primary) FLTMS0022 A ✓(I1) ✓(I1B)
I2 or I2B (Primary) FLTMS0025 A ✓(I2) ✓(I2B)
I0 or I0B (Primary) FLTMS0028 A ✓(I0) ✓(I0B)
IaC (Primary) FLTMS0031 A NA ✓
IbC (Primary) FLTMS0034 A NA ✓
IcC (Primary) FLTMS0037 A NA ✓
IabC (Primary) FLTMS0040 A NA ✓
IbcC (Primary) FLTMS0043 A NA ✓
IcaC (Primary) FLTMS0046 A NA ✓
IeC (Primary) FLTMS0049 A NA ✓
I1C (Primary) FLTMS0052 A NA ✓
I2C (Primary) FLTMS0055 A NA ✓
I0C (Primary) FLTMS0058 A NA ✓
Iem (Primary) FLTMS0061 A ✓ ✓
Va (Primary) FLTMS0064 V ✓ ✓
Vb (Primary) FLTMS0067 V ✓ ✓
Vc (Primary) FLTMS0070 V ✓ ✓
Vab (Primary) FLTMS0073 V ✓ ✓
Vbc (Primary) FLTMS0076 V ✓ ✓
Vca (Primary) FLTMS0079 V ✓ ✓
V1 (Primary) FLTMS0082 V ✓ ✓
V2 (Primary) FLTMS0085 V ✓ ✓
V0 (Primary) FLTMS0088 V ✓ ✓
Vs (Primary) FLTMS0091 V ✓ ✓
Vs2 (Primary) FLTMS0094 V ✓ ✓
Ia-L (Primary) FLTMS0097 A ✓ ✓
Ib-L (Primary) FLTMS0100 A ✓ ✓
Ic-L (Primary) FLTMS0103 A ✓ ✓
Ie-L (Primary) FLTMS0106 A ✓ ✓

GRL200 (Soft 033 & 037)


- 1155 -
6F2S1914 (0.37)

Signals Transferring data (✓) depending on VCT


Items Unit
names VCT12B (for 1CB) VCT11B(for 1.5CB)
Ia-R1 (Primary) FLTMS0109 A ✓ ✓
Ib-R1 (Primary) FLTMS0112 A ✓ ✓
Ic-R1 (Primary) FLTMS0115 A ✓ ✓
Ie-R1 (Primary) FLTMS0118 A ✓ ✓
Ia-R2 (Primary) FLTMS0121 A ✓ ✓
Ib-R2 (Primary) FLTMS0124 A ✓ ✓
Ic-R2 (Primary) FLTMS0127 A ✓ ✓
Ie-R2 (Primary) FLTMS0130 A ✓ ✓
V1-L (Primary) FLTMS0133 V ✓ ✓
V1-R1 (Primary) FLTMS0136 V ✓ ✓
V1-R2 (Primary) FLTMS0139 V ✓ ✓
Ida (Primary) FLTMS0142 A ✓ ✓
Idb (Primary) FLTMS0144 A ✓ ✓
Idc (Primary) FLTMS0146 A ✓ ✓
Id0 (Primary) FLTMS0148 A ✓ ✓
Ira (Primary) FLTMS0156 A ✓ ✓
Irb (Primary) FLTMS0158 A ✓ ✓
Irc (Primary) FLTMS0160 A ✓ ✓
Ir0 (Primary) FLTMS0162 A ✓ ✓
Ra (Primary) FLTMS0164 ohm ✓ ✓
Rb (Primary) FLTMS0166 ohm ✓ ✓
Rc (Primary) FLTMS0168 ohm ✓ ✓
Xa (Primary) FLTMS0170 ohm ✓ ✓
Xb (Primary) FLTMS0172 ohm ✓ ✓
Xc (Primary) FLTMS0174 ohm ✓ ✓
Rab (Primary) FLTMS0176 ohm ✓ ✓
Rbc (Primary) FLTMS0178 ohm ✓ ✓
Rca (Primary) FLTMS0180 ohm ✓ ✓
Xab (Primary) FLTMS0182 ohm ✓ ✓
Xbc (Primary) FLTMS0184 ohm ✓ ✓
Xca (Primary) FLTMS0186 ohm ✓ ✓
I2/I1 FLTMS0189 – ✓ ✓
THM-Capacity FLTMS0190 % ✓ ✓
CH1 Delay FLTMS0191 s ✓ ✓
CH2 Delay FLTMS0192 s ✓ ✓
CH1 DT FLTMS0193 s ✓ ✓
CH2 DT FLTMS0194 s ✓ ✓
Note: See section 8.1.1(vi) about the information about fault recording quantities. To
find Data ID, see section 8.4.4.

GRL200 (Soft 033 & 037)


- 1156 -
6F2S1914 (0.37)

8.4.2 Transferred information about tripped phase and mode


Information about the tripped phases and mode can be transferred with the signals in Table
8.4-2. For more information about tripped phases and modes, see sections 8.1.1(ii) and (iii).

Table 8.4-2 Transferred information


Items Signal names
Number of faults recorded FLT_CNT
Time at the fault occurrence FLT_TM
Tripped at phase A FLT_PH_A
Tripped at phase B FLT_PH_B
Tripped at phase C FLT_PH_C
Tripped at phase N FLT_PH_N
Relay element operated at phase A in CB#1 FLT_OP_A
Relay element operated at phase B in CB#1 FLT_OP_B
Relay element operated at phase C in CB#1 FLT_OP_C
Relay element operated at phase A in CB#2 FLT_OP2_A
Relay element operated at phase B in CB#2 FLT_OP2_B
Relay element operated at phase C in CB#2 FLT_OP2_C

8.4.3 Transferred state information


Information collected by setting [OP Mode ID*] can transferred with the signals in Table 8.4-3.
For more information about the statuses, see sections 8.1.3(i) and (ii).

Table 8.4-3 Transferred information by OP mode settings


Items Signal names
State taken by setting [OP Mode ID1] FLTOPM001
State taken by setting [OP Mode ID2] FLTOPM002
State taken by setting [OP Mode ID3] FLTOPM003
…. ….
State taken by setting [OP Mode ID128] FLTOPM128
Logical state taken by setting [OP Mode ID201] FLTOPM201
Logical state taken by setting [OP Mode ID202] FLTOPM202
…. ….
Logical state taken by setting [OP Mode ID264] FLTOPM264

GRL200 (Soft 033 & 037)


- 1157 -
6F2S1914 (0.37)

8.4.4 Transferring record value and information


 Signal generated for transferring
FAULT_RECORD (Function ID: 200602)
Element ID Name Description
3130001180 FLT_CNT Count of Fault Record

9030001006 FLT_TM Fault Time

8030001B60 FLT_PH_A Fault Phase A

8130001B61 FLT_PH_B Fault Phase B

8230001B62 FLT_PH_C Fault Phase C

8330001B63 FLT_PH_N Fault Phase N

8030001B20 FLT_OP_A Operating Phase A in CB#1

8130001B21 FLT_OP_B Operating Phase B in CB#1

8230001B22 FLT_OP_C Operating Phase C in CB#1

8430001B24 FLT_OP2_A Operating Phase A in CB#2

8530001B25 FLT_OP2_B Operating Phase B in CB#2

8630001B26 FLT_OP2_C Operating Phase C in CB#2

8830001B28 FLT_OP_1 Reserved

8930001B29 FLT_OP_2 Reserved

8A30001B2A FLT_OP_3 Reserved

8B30001B2B FLT_OP_4 Reserved

8C30001B2C FLT_OP_5 Reserved

8D30001B2D FLT_OP_6 Reserved

4330001001 FLTMS0001 Value taken during the fault (0001)

4330011001 FLTMS0002 Value taken during the fault (0002)

4330021001 FLTMS0003 Value taken during the fault (0003)

4330031001 FLTMS0004 Value taken during the fault (0004)

4330041001 FLTMS0005 Value taken during the fault (0005)

4330051001 FLTMS0006 Value taken during the fault (0006)

4330061001 FLTMS0007 Value taken during the fault (0007)

4330071001 FLTMS0008 Value taken during the fault (0008)

4330081001 FLTMS0009 Value taken during the fault (0009)

4330091001 FLTMS0010 Value taken during the fault (0010)

43300A1001 FLTMS0011 Value taken during the fault (0011)

43300B1001 FLTMS0012 Value taken during the fault (0012)

43300C1001 FLTMS0013 Value taken during the fault (0013)

43300D1001 FLTMS0014 Value taken during the fault (0014)

43300E1001 FLTMS0015 Value taken during the fault (0015)

43300F1001 FLTMS0016 Value taken during the fault (0016)

4330101001 FLTMS0017 Value taken during the fault (0017)

4330111001 FLTMS0018 Value taken during the fault (0018)

4330121000 FLTMS0019 Value taken during the fault (0019)

4330131001 FLTMS0020 Value taken during the fault (0020)

4330141001 FLTMS0021 Value taken during the fault (0021)

4330151001 FLTMS0022 Value taken during the fault (0022)

4330161001 FLTMS0023 Value taken during the fault (0023)

4330171001 FLTMS0024 Value taken during the fault (0024)

4330181001 FLTMS0025 Value taken during the fault (0025)

GRL200 (Soft 033 & 037)


- 1158 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
4330191001 FLTMS0026 Value taken during the fault (0026)

43301A1001 FLTMS0027 Value taken during the fault (0027)

43301B1001 FLTMS0028 Value taken during the fault (0028)

43301C1001 FLTMS0029 Value taken during the fault (0029)

43301D1001 FLTMS0030 Value taken during the fault (0030)

43301E1001 FLTMS0031 Value taken during the fault (0031)

43301F1001 FLTMS0032 Value taken during the fault (0032)

4330201001 FLTMS0033 Value taken during the fault (0033)

4330211001 FLTMS0034 Value taken during the fault (0034)

4330221001 FLTMS0035 Value taken during the fault (0035)

4330231001 FLTMS0036 Value taken during the fault (0036)

4330241001 FLTMS0037 Value taken during the fault (0037)

4330251001 FLTMS0038 Value taken during the fault (0038)

4330261001 FLTMS0039 Value taken during the fault (0039)

4330271001 FLTMS0040 Value taken during the fault (0040)

4330281001 FLTMS0041 Value taken during the fault (0041)

4330291001 FLTMS0042 Value taken during the fault (0042)

43302A1001 FLTMS0043 Value taken during the fault (0043)

43302B1001 FLTMS0044 Value taken during the fault (0044)

43302C1001 FLTMS0045 Value taken during the fault (0045)

43302D1001 FLTMS0046 Value taken during the fault (0046)

43302E1001 FLTMS0047 Value taken during the fault (0047)

43302F1001 FLTMS0048 Value taken during the fault (0048)

4330301001 FLTMS0049 Value taken during the fault (0049)

4330311001 FLTMS0050 Value taken during the fault (0050)

4330321001 FLTMS0051 Value taken during the fault (0051)

4330331001 FLTMS0052 Value taken during the fault (0052)

4330341001 FLTMS0053 Value taken during the fault (0053)

4330351001 FLTMS0054 Value taken during the fault (0054)

4330361001 FLTMS0055 Value taken during the fault (0055)

4330371001 FLTMS0056 Value taken during the fault (0056)

4330381001 FLTMS0057 Value taken during the fault (0057)

4330391001 FLTMS0058 Value taken during the fault (0058)

43303A1001 FLTMS0059 Value taken during the fault (0059)

43303B1001 FLTMS0060 Value taken during the fault (0060)

43303C1001 FLTMS0061 Value taken during the fault (0061)

43303D1001 FLTMS0062 Value taken during the fault (0062)

43303E1001 FLTMS0063 Value taken during the fault (0063)

43303F1001 FLTMS0064 Value taken during the fault (0064)

4330401001 FLTMS0065 Value taken during the fault (0065)

4330411001 FLTMS0066 Value taken during the fault (0066)

4330421001 FLTMS0067 Value taken during the fault (0067)

4330431001 FLTMS0068 Value taken during the fault (0068)

4330441001 FLTMS0069 Value taken during the fault (0069)

GRL200 (Soft 033 & 037)


- 1159 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
4330451001 FLTMS0070 Value taken during the fault (0070)

4330461001 FLTMS0071 Value taken during the fault (0071)

4330471001 FLTMS0072 Value taken during the fault (0072)

4330481001 FLTMS0073 Value taken during the fault (0073)

4330491001 FLTMS0074 Value taken during the fault (0074)

43304A1001 FLTMS0075 Value taken during the fault (0075)

43304B1001 FLTMS0076 Value taken during the fault (0076)

43304C1001 FLTMS0077 Value taken during the fault (0077)

43304D1001 FLTMS0078 Value taken during the fault (0078)

43304E1001 FLTMS0079 Value taken during the fault (0079)

43304F1001 FLTMS0080 Value taken during the fault (0080)

4330501001 FLTMS0081 Value taken during the fault (0081)

4330511001 FLTMS0082 Value taken during the fault (0082)

4330521001 FLTMS0083 Value taken during the fault (0083)

4330531001 FLTMS0084 Value taken during the fault (0084)

4330541001 FLTMS0085 Value taken during the fault (0085)

4330551001 FLTMS0086 Value taken during the fault (0086)

4330561001 FLTMS0087 Value taken during the fault (0087)

4330571001 FLTMS0088 Value taken during the fault (0088)

4330581001 FLTMS0089 Value taken during the fault (0089)

4330591001 FLTMS0090 Value taken during the fault (0090)

43305A1001 FLTMS0091 Value taken during the fault (0091)

43305B1001 FLTMS0092 Value taken during the fault (0092)

43305C1001 FLTMS0093 Value taken during the fault (0093)

43305D1001 FLTMS0094 Value taken during the fault (0094)

43305E1001 FLTMS0095 Value taken during the fault (0095)

43305F1001 FLTMS0096 Value taken during the fault (0096)

4330601001 FLTMS0097 Value taken during the fault (0097)

4330611001 FLTMS0098 Value taken during the fault (0098)

4330621001 FLTMS0099 Value taken during the fault (0099)

4330631001 FLTMS0100 Value taken during the fault (0100)

4330641001 FLTMS0101 Value taken during the fault (0101)

4330651001 FLTMS0102 Value taken during the fault (0102)

4330661001 FLTMS0103 Value taken during the fault (0103)

4330671001 FLTMS0104 Value taken during the fault (0104)

4330681001 FLTMS0105 Value taken during the fault (0105)

4330691001 FLTMS0106 Value taken during the fault (0106)

43306A1001 FLTMS0107 Value taken during the fault (0107)

43306B1001 FLTMS0108 Value taken during the fault (0108)

43306C1001 FLTMS0109 Value taken during the fault (0109)

43306D1001 FLTMS0110 Value taken during the fault (0110)

43306E1001 FLTMS0111 Value taken during the fault (0111)

43306F1001 FLTMS0112 Value taken during the fault (0112)

4330701001 FLTMS0113 Value taken during the fault (0113)

GRL200 (Soft 033 & 037)


- 1160 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
4330711001 FLTMS0114 Value taken during the fault (0114)

4330721001 FLTMS0115 Value taken during the fault (0115)

4330731001 FLTMS0116 Value taken during the fault (0116)

4330741001 FLTMS0117 Value taken during the fault (0117)

4330751001 FLTMS0118 Value taken during the fault (0118)

4330761001 FLTMS0119 Value taken during the fault (0119)

4330771001 FLTMS0120 Value taken during the fault (0120)

4330781001 FLTMS0121 Value taken during the fault (0121)

4330791001 FLTMS0122 Value taken during the fault (0122)

43307A1001 FLTMS0123 Value taken during the fault (0123)

43307B1001 FLTMS0124 Value taken during the fault (0124)

43307C1001 FLTMS0125 Value taken during the fault (0125)

43307D1001 FLTMS0126 Value taken during the fault (0126)

43307E1001 FLTMS0127 Value taken during the fault (0127)

43307F1001 FLTMS0128 Value taken during the fault (0128)

4330801001 FLTMS0129 Value taken during the fault (0129)

4330811001 FLTMS0130 Value taken during the fault (0130)

4330821001 FLTMS0131 Value taken during the fault (0131)

4330831001 FLTMS0132 Value taken during the fault (0132)

4330841001 FLTMS0133 Value taken during the fault (0133)

4330851001 FLTMS0134 Value taken during the fault (0134)

4330861001 FLTMS0135 Value taken during the fault (0135)

4330871001 FLTMS0136 Value taken during the fault (0136)

4330881001 FLTMS0137 Value taken during the fault (0137)

4330891001 FLTMS0138 Value taken during the fault (0138)

43308A1001 FLTMS0139 Value taken during the fault (0139)

43308B1001 FLTMS0140 Value taken during the fault (0140)

43308C1001 FLTMS0141 Value taken during the fault (0141)

43308D1001 FLTMS0142 Value taken during the fault (0142)

43308E1001 FLTMS0143 Value taken during the fault (0143)

43308F1001 FLTMS0144 Value taken during the fault (0144)

4330901001 FLTMS0145 Value taken during the fault (0145)

4330911001 FLTMS0146 Value taken during the fault (0146)

4330921001 FLTMS0147 Value taken during the fault (0147)

4330931001 FLTMS0148 Value taken during the fault (0148)

4330941001 FLTMS0149 Value taken during the fault (0149)

4330951001 FLTMS0150 Value taken during the fault (0150)

4330961001 FLTMS0151 Value taken during the fault (0151)

4330971001 FLTMS0152 Value taken during the fault (0152)

4330981001 FLTMS0153 Value taken during the fault (0153)

4330991001 FLTMS0154 Value taken during the fault (0154)

43309A1001 FLTMS0155 Value taken during the fault (0155)

43309B1001 FLTMS0156 Value taken during the fault (0156)

43309C1001 FLTMS0157 Value taken during the fault (0157)

GRL200 (Soft 033 & 037)


- 1161 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
43309D1001 FLTMS0158 Value taken during the fault (0158)

43309E1001 FLTMS0159 Value taken during the fault (0159)

43309F1001 FLTMS0160 Value taken during the fault (0160)

4330A01001 FLTMS0161 Value taken during the fault (0161)

4330A11001 FLTMS0162 Value taken during the fault (0162)

4330A21001 FLTMS0163 Value taken during the fault (0163)

4330A31001 FLTMS0164 Value taken during the fault (0164)

4330A41001 FLTMS0165 Value taken during the fault (0165)

4330A51001 FLTMS0166 Value taken during the fault (0166)

4330A61001 FLTMS0167 Value taken during the fault (0167)

4330A71001 FLTMS0168 Value taken during the fault (0168)

4330A81001 FLTMS0169 Value taken during the fault (0169)

4330A91001 FLTMS0170 Value taken during the fault (0170)

4330AA1001 FLTMS0171 Value taken during the fault (0171)

4330AB1001 FLTMS0172 Value taken during the fault (0172)

4330AC1001 FLTMS0173 Value taken during the fault (0173)

4330AD1001 FLTMS0174 Value taken during the fault (0174)

4330AE1001 FLTMS0175 Value taken during the fault (0175)

4330AF1001 FLTMS0176 Value taken during the fault (0176)

4330B01001 FLTMS0177 Value taken during the fault (0177)

4330B11001 FLTMS0178 Value taken during the fault (0178)

4330B21001 FLTMS0179 Value taken during the fault (0179)

4330B31001 FLTMS0180 Value taken during the fault (0180)

4330B41001 FLTMS0181 Value taken during the fault (0181)

4330B51001 FLTMS0182 Value taken during the fault (0182)

4330B61001 FLTMS0183 Value taken during the fault (0183)

4330B71001 FLTMS0184 Value taken during the fault (0184)

4330B81001 FLTMS0185 Value taken during the fault (0185)

4330B91001 FLTMS0186 Value taken during the fault (0186)

4330BA1001 FLTMS0187 Value taken during the fault (0187)

4330BB1001 FLTMS0188 Value taken during the fault (0188)

4330BC1001 FLTMS0189 Value taken during the fault (0189)

4330BD1001 FLTMS0190 Value taken during the fault (0190)

4330BE1001 FLTMS0191 Value taken during the fault (0191)

4330BF1001 FLTMS0192 Value taken during the fault (0192)

4330C01001 FLTMS0193 Value taken during the fault (0193)

4330C11001 FLTMS0194 Value taken during the fault (0194)

4330C21001 FLTMS0195 Value taken during the fault (0195)

4330C31001 FLTMS0196 Value taken during the fault (0196)

4330C41001 FLTMS0197 Value taken during the fault (0197)

4330C51001 FLTMS0198 Value taken during the fault (0198)

4330C61001 FLTMS0199 Value taken during the fault (0199)

4330C71001 FLTMS0200 Value taken during the fault (0200)

4330C81001 FLTMS0201 Value taken during the fault (0201)

GRL200 (Soft 033 & 037)


- 1162 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
4330C91001 FLTMS0202 Value taken during the fault (0202)

4330CA1001 FLTMS0203 Value taken during the fault (0203)

4330CB1001 FLTMS0204 Value taken during the fault (0204)

4330CC1001 FLTMS0205 Value taken during the fault (0205)

4330CD1001 FLTMS0206 Value taken during the fault (0206)

4330CE1001 FLTMS0207 Value taken during the fault (0207)

4330CF1001 FLTMS0208 Value taken during the fault (0208)

4330D01001 FLTMS0209 Value taken during the fault (0209)

4330D11001 FLTMS0210 Value taken during the fault (0210)

4330D21001 FLTMS0211 Value taken during the fault (0211)

4330D31001 FLTMS0212 Value taken during the fault (0212)

4330D41001 FLTMS0213 Value taken during the fault (0213)

4330D51001 FLTMS0214 Value taken during the fault (0214)

4330D61001 FLTMS0215 Value taken during the fault (0215)

4330D71001 FLTMS0216 Value taken during the fault (0216)

4330D81001 FLTMS0217 Value taken during the fault (0217)

4330D91001 FLTMS0218 Value taken during the fault (0218)

4330DA1001 FLTMS0219 Value taken during the fault (0219)

4330DB1001 FLTMS0220 Value taken during the fault (0220)

4330DC1001 FLTMS0221 Value taken during the fault (0221)

4330DD1001 FLTMS0222 Value taken during the fault (0222)

4330DE1001 FLTMS0223 Value taken during the fault (0223)

4330DF1001 FLTMS0224 Value taken during the fault (0224)

4330E01001 FLTMS0225 Value taken during the fault (0225)

4330E11001 FLTMS0226 Value taken during the fault (0226)

4330E21001 FLTMS0227 Value taken during the fault (0227)

4330E31001 FLTMS0228 Value taken during the fault (0228)

4330E41001 FLTMS0229 Value taken during the fault (0229)

4330E51001 FLTMS0230 Value taken during the fault (0230)

4330E61001 FLTMS0231 Value taken during the fault (0231)

4330E71001 FLTMS0232 Value taken during the fault (0232)

4330E81001 FLTMS0233 Value taken during the fault (0233)

4330E91001 FLTMS0234 Value taken during the fault (0234)

4330EA1001 FLTMS0235 Value taken during the fault (0235)

4330EB1001 FLTMS0236 Value taken during the fault (0236)

4330EC1001 FLTMS0237 Value taken during the fault (0237)

4330ED1001 FLTMS0238 Value taken during the fault (0238)

4330EE1001 FLTMS0239 Value taken during the fault (0239)

4330EF1001 FLTMS0240 Value taken during the fault (0240)

4330F01001 FLTMS0241 Value taken during the fault (0241)

4330F11001 FLTMS0242 Value taken during the fault (0242)

4330F21001 FLTMS0243 Value taken during the fault (0243)

4330F31001 FLTMS0244 Value taken during the fault (0244)

4330F41001 FLTMS0245 Value taken during the fault (0245)

GRL200 (Soft 033 & 037)


- 1163 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
4330F51001 FLTMS0246 Value taken during the fault (0246)

4330F61001 FLTMS0247 Value taken during the fault (0247)

4330F71001 FLTMS0248 Value taken during the fault (0248)

4330F81001 FLTMS0249 Value taken during the fault (0249)

4330F91001 FLTMS0250 Value taken during the fault (0250)

4330FA1001 FLTMS0251 Value taken during the fault (0251)

4330FB1001 FLTMS0252 Value taken during the fault (0252)

4330FC1001 FLTMS0253 Value taken during the fault (0253)

4330FD1001 FLTMS0254 Value taken during the fault (0254)

4330FE1001 FLTMS0255 Value taken during the fault (0255)

4330FF1001 FLTMS0256 Value taken during the fault (0256)

8050001135 FLTOPM001 Status at Operation identifier ID1

8150011135 FLTOPM002 Status at Operation identifier ID2

8250021135 FLTOPM003 Status at Operation identifier ID3

8350031135 FLTOPM004 Status at Operation identifier ID4

8450041135 FLTOPM005 Status at Operation identifier ID5

8550051135 FLTOPM006 Status at Operation identifier ID6

8650061135 FLTOPM007 Status at Operation identifier ID7

8750071135 FLTOPM008 Status at Operation identifier ID8

8850081135 FLTOPM009 Status at Operation identifier ID9

8950091135 FLTOPM010 Status at Operation identifier ID10

8A500A1135 FLTOPM011 Status at Operation identifier ID11

8B500B1135 FLTOPM012 Status at Operation identifier ID12

8C500C1135 FLTOPM013 Status at Operation identifier ID13

8D500D1135 FLTOPM014 Status at Operation identifier ID14

8E500E1135 FLTOPM015 Status at Operation identifier ID15

8F500F1135 FLTOPM016 Status at Operation identifier ID16

8050101135 FLTOPM017 Status at Operation identifier ID17

8150111135 FLTOPM018 Status at Operation identifier ID18

8250121135 FLTOPM019 Status at Operation identifier ID19

8350131135 FLTOPM020 Status at Operation identifier ID20

8450141135 FLTOPM021 Status at Operation identifier ID21

8550151135 FLTOPM022 Status at Operation identifier ID22

8650161135 FLTOPM023 Status at Operation identifier ID23

8750171135 FLTOPM024 Status at Operation identifier ID24

8850181135 FLTOPM025 Status at Operation identifier ID25

8950191135 FLTOPM026 Status at Operation identifier ID26

8A501A1135 FLTOPM027 Status at Operation identifier ID27

8B501B1135 FLTOPM028 Status at Operation identifier ID28

8C501C1135 FLTOPM029 Status at Operation identifier ID29

8D501D1135 FLTOPM030 Status at Operation identifier ID30

8E501E1135 FLTOPM031 Status at Operation identifier ID31

8F501F1135 FLTOPM032 Status at Operation identifier ID32

8050201135 FLTOPM033 Status at Operation identifier ID33

GRL200 (Soft 033 & 037)


- 1164 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
8150211135 FLTOPM034 Status at Operation identifier ID34

8250221135 FLTOPM035 Status at Operation identifier ID35

8350231135 FLTOPM036 Status at Operation identifier ID36

8450241135 FLTOPM037 Status at Operation identifier ID37

8550251135 FLTOPM038 Status at Operation identifier ID38

8650261135 FLTOPM039 Status at Operation identifier ID39

8750271135 FLTOPM040 Status at Operation identifier ID40

8850281135 FLTOPM041 Status at Operation identifier ID41

8950291135 FLTOPM042 Status at Operation identifier ID42

8A502A1135 FLTOPM043 Status at Operation identifier ID43

8B502B1135 FLTOPM044 Status at Operation identifier ID44

8C502C1135 FLTOPM045 Status at Operation identifier ID45

8D502D1135 FLTOPM046 Status at Operation identifier ID46

8E502E1135 FLTOPM047 Status at Operation identifier ID47

8F502F1135 FLTOPM048 Status at Operation identifier ID48

8050301135 FLTOPM049 Status at Operation identifier ID49

8150311135 FLTOPM050 Status at Operation identifier ID50

8250321135 FLTOPM051 Status at Operation identifier ID51

8350331135 FLTOPM052 Status at Operation identifier ID52

8450341135 FLTOPM053 Status at Operation identifier ID53

8550351135 FLTOPM054 Status at Operation identifier ID54

8650361135 FLTOPM055 Status at Operation identifier ID55

8750371135 FLTOPM056 Status at Operation identifier ID56

8850381135 FLTOPM057 Status at Operation identifier ID57

8950391135 FLTOPM058 Status at Operation identifier ID58

8A503A1135 FLTOPM059 Status at Operation identifier ID59

8B503B1135 FLTOPM060 Status at Operation identifier ID60

8C503C1135 FLTOPM061 Status at Operation identifier ID61

8D503D1135 FLTOPM062 Status at Operation identifier ID62

8E503E1135 FLTOPM063 Status at Operation identifier ID63

8F503F1135 FLTOPM064 Status at Operation identifier ID64

8050401135 FLTOPM065 Status at Operation identifier ID65

8150411135 FLTOPM066 Status at Operation identifier ID66

8250421135 FLTOPM067 Status at Operation identifier ID67

8350431135 FLTOPM068 Status at Operation identifier ID68

8450441135 FLTOPM069 Status at Operation identifier ID69

8550451135 FLTOPM070 Status at Operation identifier ID70

8650461135 FLTOPM071 Status at Operation identifier ID71

8750471135 FLTOPM072 Status at Operation identifier ID72

8850481135 FLTOPM073 Status at Operation identifier ID73

8950491135 FLTOPM074 Status at Operation identifier ID74

8A504A1135 FLTOPM075 Status at Operation identifier ID75

8B504B1135 FLTOPM076 Status at Operation identifier ID76

8C504C1135 FLTOPM077 Status at Operation identifier ID77

GRL200 (Soft 033 & 037)


- 1165 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
8D504D1135 FLTOPM078 Status at Operation identifier ID78

8E504E1135 FLTOPM079 Status at Operation identifier ID79

8F504F1135 FLTOPM080 Status at Operation identifier ID80

8050501135 FLTOPM081 Status at Operation identifier ID81

8150511135 FLTOPM082 Status at Operation identifier ID82

8250521135 FLTOPM083 Status at Operation identifier ID83

8350531135 FLTOPM084 Status at Operation identifier ID84

8450541135 FLTOPM085 Status at Operation identifier ID85

8550551135 FLTOPM086 Status at Operation identifier ID86

8650561135 FLTOPM087 Status at Operation identifier ID87

8750571135 FLTOPM088 Status at Operation identifier ID88

8850581135 FLTOPM089 Status at Operation identifier ID89

8950591135 FLTOPM090 Status at Operation identifier ID90

8A505A1135 FLTOPM091 Status at Operation identifier ID91

8B505B1135 FLTOPM092 Status at Operation identifier ID92

8C505C1135 FLTOPM093 Status at Operation identifier ID93

8D505D1135 FLTOPM094 Status at Operation identifier ID94

8E505E1135 FLTOPM095 Status at Operation identifier ID95

8F505F1135 FLTOPM096 Status at Operation identifier ID96

8050601135 FLTOPM097 Status at Operation identifier ID97

8150611135 FLTOPM098 Status at Operation identifier ID98

8250621135 FLTOPM099 Status at Operation identifier ID99

8350631135 FLTOPM100 Status at Operation identifier ID100

8450641135 FLTOPM101 Status at Operation identifier ID101

8550651135 FLTOPM102 Status at Operation identifier ID102

8650661135 FLTOPM103 Status at Operation identifier ID103

8750671135 FLTOPM104 Status at Operation identifier ID104

8850681135 FLTOPM105 Status at Operation identifier ID105

8950691135 FLTOPM106 Status at Operation identifier ID106

8A506A1135 FLTOPM107 Status at Operation identifier ID107

8B506B1135 FLTOPM108 Status at Operation identifier ID108

8C506C1135 FLTOPM109 Status at Operation identifier ID109

8D506D1135 FLTOPM110 Status at Operation identifier ID110

8E506E1135 FLTOPM111 Status at Operation identifier ID111

8F506F1135 FLTOPM112 Status at Operation identifier ID112

8050701135 FLTOPM113 Status at Operation identifier ID113

8150711135 FLTOPM114 Status at Operation identifier ID114

8250721135 FLTOPM115 Status at Operation identifier ID115

8350731135 FLTOPM116 Status at Operation identifier ID116

8450741135 FLTOPM117 Status at Operation identifier ID117

8550751135 FLTOPM118 Status at Operation identifier ID118

8650761135 FLTOPM119 Status at Operation identifier ID119

8750771135 FLTOPM120 Status at Operation identifier ID120

8850781135 FLTOPM121 Status at Operation identifier ID121

GRL200 (Soft 033 & 037)


- 1166 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
8950791135 FLTOPM122 Status at Operation identifier ID122

8A507A1135 FLTOPM123 Status at Operation identifier ID123

8B507B1135 FLTOPM124 Status at Operation identifier ID124

8C507C1135 FLTOPM125 Status at Operation identifier ID125

8D507D1135 FLTOPM126 Status at Operation identifier ID126

8E507E1135 FLTOPM127 Status at Operation identifier ID127

8F507F1135 FLTOPM128 Status at Operation identifier ID128

8050801135 FLTOPM201 Status at Logical operation identifier ID201

8150811135 FLTOPM202 Status at Logical operation identifier ID202

8250821135 FLTOPM203 Status at Logical operation identifier ID203

8350831135 FLTOPM204 Status at Logical operation identifier ID204

8450841135 FLTOPM205 Status at Logical operation identifier ID205

8550851135 FLTOPM206 Status at Logical operation identifier ID206

8650861135 FLTOPM207 Status at Logical operation identifier ID207

8750871135 FLTOPM208 Status at Logical operation identifier ID208

8850881135 FLTOPM209 Status at Logical operation identifier ID209

8950891135 FLTOPM210 Status at Logical operation identifier ID210

8A508A1135 FLTOPM211 Status at Logical operation identifier ID211

8B508B1135 FLTOPM212 Status at Logical operation identifier ID212

8C508C1135 FLTOPM213 Status at Logical operation identifier ID213

8D508D1135 FLTOPM214 Status at Logical operation identifier ID214

8E508E1135 FLTOPM215 Status at Logical operation identifier ID215

8F508F1135 FLTOPM216 Status at Logical operation identifier ID216

8050901135 FLTOPM217 Status at Logical operation identifier ID217

8150911135 FLTOPM218 Status at Logical operation identifier ID218

8250921135 FLTOPM219 Status at Logical operation identifier ID219

8350931135 FLTOPM220 Status at Logical operation identifier ID220

8450941135 FLTOPM221 Status at Logical operation identifier ID221

8550951135 FLTOPM222 Status at Logical operation identifier ID222

8650961135 FLTOPM223 Status at Logical operation identifier ID223

8750971135 FLTOPM224 Status at Logical operation identifier ID224

8850981135 FLTOPM225 Status at Logical operation identifier ID225

8950991135 FLTOPM226 Status at Logical operation identifier ID226

8A509A1135 FLTOPM227 Status at Logical operation identifier ID227

8B509B1135 FLTOPM228 Status at Logical operation identifier ID228

8C509C1135 FLTOPM229 Status at Logical operation identifier ID229

8D509D1135 FLTOPM230 Status at Logical operation identifier ID230

8E509E1135 FLTOPM231 Status at Logical operation identifier ID231

8F509F1135 FLTOPM232 Status at Logical operation identifier ID232

8050A01135 FLTOPM233 Status at Logical operation identifier ID233

8150A11135 FLTOPM234 Status at Logical operation identifier ID234

8250A21135 FLTOPM235 Status at Logical operation identifier ID235

8350A31135 FLTOPM236 Status at Logical operation identifier ID236

8450A41135 FLTOPM237 Status at Logical operation identifier ID237

GRL200 (Soft 033 & 037)


- 1167 -
6F2S1914 (0.37)

 Signal generated for transferring


FAULT_RECORD (Function ID: 200602)
Element ID Name Description
8550A51135 FLTOPM238 Status at Logical operation identifier ID238

8650A61135 FLTOPM239 Status at Logical operation identifier ID239

8750A71135 FLTOPM240 Status at Logical operation identifier ID240

8850A81135 FLTOPM241 Status at Logical operation identifier ID241

8950A91135 FLTOPM242 Status at Logical operation identifier ID242

8A50AA1135 FLTOPM243 Status at Logical operation identifier ID243

8B50AB1135 FLTOPM244 Status at Logical operation identifier ID244

8C50AC1135 FLTOPM245 Status at Logical operation identifier ID245

8D50AD1135 FLTOPM246 Status at Logical operation identifier ID246

8E50AE1135 FLTOPM247 Status at Logical operation identifier ID247

8F50AF1135 FLTOPM248 Status at Logical operation identifier ID248

8050B01135 FLTOPM249 Status at Logical operation identifier ID249

8150B11135 FLTOPM250 Status at Logical operation identifier ID250

8250B21135 FLTOPM251 Status at Logical operation identifier ID251

8350B31135 FLTOPM252 Status at Logical operation identifier ID252

8450B41135 FLTOPM253 Status at Logical operation identifier ID253

8550B51135 FLTOPM254 Status at Logical operation identifier ID254

8650B61135 FLTOPM255 Status at Logical operation identifier ID255

8750B71135 FLTOPM256 Status at Logical operation identifier ID256

8850B81135 FLTOPM257 Status at Logical operation identifier ID257

8950B91135 FLTOPM258 Status at Logical operation identifier ID258

8A50BA1135 FLTOPM259 Status at Logical operation identifier ID259

8B50BB1135 FLTOPM260 Status at Logical operation identifier ID260

8C50BC1135 FLTOPM261 Status at Logical operation identifier ID261

8D50BD1135 FLTOPM262 Status at Logical operation identifier ID262

8E50BE1135 FLTOPM263 Status at Logical operation identifier ID263

8F50BF1135 FLTOPM264 Status at Logical operation identifier ID264

GRL200 (Soft 033 & 037)


- 1168 -
6F2S1914 (0.37)

9 Monitoring function
Contents Pages Pages
Accumulated time 1183 Metering features –
Counter features – -Information 1170
-Information in GCNT 1182 -Diminishing small value 1173
Demand features – -Flow settings for P, Q, S 1173
-Information 1179 -Measurement settings 1172
-Demand cycle 1180 -Information on the screen 1171
-Resetting data in demand features 1180 -Polarity setting for PF 1174
-Max/Min/Ave information 1179 Peak Demand features –
Dead band features – -Max/Min/Ave. information 1181
-V, I, P, Q, S, PF, Frequency. 1176 -Reset of peak-demand data 1181
-Wh, Varh, Phase, Voltage difference 1176 Power settings –
-GCNT 1182 -Information on the screen 1178
-TOTALTIM 1184 -Regulating power values 1178
-Power values settings 1178
Total time measurements –
-Information in TOTALTIM 1184

GRL200 (Soft 033 & 037)


- 1169 -
6F2S1914 (0.37)

Outline
The monitoring function is provided to measure the number of power quantities and statistics
data obtained within the VCT and BI circuits†. When the measuring instruments start
measures power quantities, mathematical means is applied to the data from the VCT so that
the data are shown accurately on the IED screen.
†Note:The VCT/BIO structures and their features are discussed in Chapter Technical
description.

Metering data (Metering group)


Several abbreviations are screened for metering data, which is tabulated below Table1–6.
1Note: Terms ‘I0 (i.e., 3I0)’ and ‘V0 (i.e., 3V0)’ are calculated using three-phase quantities.
2Note: The ‘Ie’ and ‘Iem’ are obtained usually with corresponding ‘Ie’ and ‘Iem’ circuits in
the VCT.
3Note: ‘CH2’ is available when two signaling modules exist in the IED, which is
dependent on the model. Check the ordering number at the C position referring to
the ordering (See Appendix: Ordering)
4Note: Those metering items are provided for the special models, which are designated at
ordering made.
5Note: Positive-sequence V1, which represents power system, is used to measure the
frequency.
6Note: Check the ordering number at the G&T position referring to the ordering (See
Appendix: Ordering)

GRL200 (Soft 033 & 037)


- 1170 -
6F2S1914 (0.37)

Table 9.2-1 Metering data for ’33 and 37’ software6


Groups Displayed quantities Abbreviations

Ia, Ib, Ic,

Current in phase, phase-to-phase , symmetrical, residual Iab, Ibc, Ica,

currents Ie (2)

I1, I2, I0 (1)


Residual current in the other side of the parallel line Iem(2)

Va, Vb, Vc
Voltage in phase, phase-to-phase, and symmetrical Vab, Vbc, Vca

V1, V2, V0(1)

One or two reference (busbar) voltages Vs, Vs2

Ia–L, Ib–L, Ic–L, Ie–L

Resultant currents and voltages at local-end (L) and remote- Ia–R1, Ib–R1, Ic–R1, Ie–R1
ends (R1 and R2) Ia–R2, Ib–R2, Ic–R2, Ie–R2

V1–L, V1–R1, V1–R2


Frequency F(5)
Active(real) power in phase-a,-b,-c / three-phase Pa, Pb, Pc / P
Metering
Reactive power in phase-a,-b,-c / three-phase Qa, Qb, Qc / Q

Complex (apparent) power in phase-a,-b,-c / three-phase Sa, Sb, Sc / S

Power factors in phase-a,-b,-c / three-phase PFa, PFb, PFc / PF

Watt-hour (plus/minus), var-hour (plus/minus) Wh, varh

DIFL differential currents (Id) in three-phases Ida, Idb, Idc

DIFL differential currents(Ido) in zero-sequence Id0

Pickup currents in DIFL Idapu, Idbpu, Idcpu, Id0pu

DIFGL restraining-currents (Ir) in three-phases Ira, Irb, Irc

DIFGL restraining-currents (Ir) in zero-sequence Ir0

Propagation delay times at port1(CH1) and port2(CH2) CH1 Delay, CH2 Delay(3)
Sampling difference between terminals at port1(CH1) and CH1 DT, CH2 DT(3)
port2(CH2)

Rate of frequency change Df/dt(4)


Rate of positive-sequence-current to negative-sequence- I2/I1(4)
current

Rate of thermal capacity in % THM-Capacity(4)

9.2.1 Metering information on the screen


The user can examine the values provided by the metering function on the IED screen; Figure

GRL200 (Soft 033 & 037)


- 1171 -
6F2S1914 (0.37)

9.2-1 illustrates the information about currents. A reference phasor is defined to examine a
complex data in the metering and a positive-sequence voltage (V1) is defined as the reference.
The metering function has minimum sensing threshold; thus, the user shall notice that zero
(0) is displayed, if the provided data is lesser than the threshold.

Metering
10:48 1/59
Ia
12.345kA 123.45deg
Ib
12.345kA 123.45deg
Ic
12.345kA 123.45deg

Figure 9.2-1 Current meter on the IED screen


Note: If any quantity does not enter to the VCT, the value on the screen is displayed
such as “***.**” and “–––––”.

9.2.2 Setting for measurements


(i) Selecting either primary/secondary values
In the metering function, the value of the primary side is displayed on the screen; when the
value is greater than 1000 volts, it will be displayed in KV unit. When the user prefers
displaying the value of the secondary side, the user should set Secondary for the setting
[Display_Value].Table 9.2-2 shows the effective digit when Secondary is set.

Metering
10:48 1/2
Display Value +
Primary
I-Display Unit +
kA
V-Display Unit +
kV

Figure 9.2-2 Metering setting in the setting screen


Note: For the operation of the menu, see Chapter User interface: Setting sub-menu.
Table 9.2-2 Significant digits for metering
Maximum number of significant
Metering screen Settings digits after decimal point
Current/Voltage Phase angle
Primary
Voltage 1
Secontray
1
Primary 2
Current
Secontray 3

(ii) Unit setting


The user can select to a metering unit for each metering value. For example, the current is

GRL200 (Soft 033 & 037)


- 1172 -
6F2S1914 (0.37)

preferred to be displayed in kA unit, the user should set kA for the [I-Display Unit]. Table 9.2-3
shows the unit lists in the metering funciton.
Table 9.2-3 Selection of units to display
Metering items Settings Selection of a unit to display

Voltage (V) [V-Display Unit] Volt (V) or kilo-volt (kV)

Current (I) [I-Display Unit] Ampare (A) or kilo-ampare (kA)

Active power (P) [P-Display Unit] Kilo-watt (kW) or Mega-watt (MW)

Reactive power (Q) [Q-Display Unit] Kilo-var (kvar) or Mega-var (Mvar)

Apprent power (S) [S-Display Unit] Kilo-VA (kVA) or Mega-VA (MVA)

9.2.3 Diminishing a very small value to display zero


In the metering function, negligible metering values will be considered as zero. The user can
set the level to diminish in % using settings [I-Valid Level] and [V-Valid Level], at which values
‘4.00’ and ‘0.30’ are set, as default, respectively. Thus, zero (0) will be displayed when the
applied quantities at the VCT, which are lesser than the setting levels.

9.2.4 Flow settings for active/reactive/apparent powers


The user should set the rules for the metering P, Q, and S
(i) Metering in active power (P)
When the metering function measures the value for supplying power, the user should set Send
for the [Power]. Conversely, if the metering function should operate for absorbing power, set
Receive for the setting. Figure 9.2-3 illustrates the sign of the active power (P), which is
polarized with the voltage (V). In Figure 9.2-3.a exemplifies the metering function operating
for the supplying power so that the value P will have plus (+) sign (i.e., the I lags the V, which
shown in Quadrant IV). In Figure 9.2-3.b, the value P will have minus (–) sign when the I lags
the V, provided Receive is set for the setting.
Receiving Sending Receiving Sending

II
(P<0)
I
(P>0)
II
(P>0)
I
(P<0)

V V (+)

III I
IV
(P>0)
III
(P>0)
I
IV
(P<0) (P<0)

a. Metering (P) for supplying power b. Metering (P) for absorbing power
[Power]=Send [Power]=Receive

Figure 9.2-3 Sign of the active power (P) ruled by setting [Power]

GRL200 (Soft 033 & 037)


- 1173 -
6F2S1914 (0.37)

(ii) Metering in reactive power (Q)


Similar to the active power (P), the user should set the metering sign for the reactive power
(Q). The Q value will have the minus sign (–) based on the P value, when Lag is set for setting
[Current] (Figure 9.2-4.a). On the other hand, the Q value will have the plus sign (+) based on
the P value, when Lead set for the setting (Figure 9.2-4.b).

II
(Q>0)
I
(Q>0)
II
(Q<0)
I
(Q<0)

V
V

III
(Q<0)
I
IV
(Q<0)
III I
IV
(Q>0)
(Q>0)

a. Q (shown in quadrant IV) has a minus sign b. Q (shown in quadrant IV) has a plus sign because
because the Q is supplied by the outside source. the Q is absorbed by the outside source. The
The decision is made with the P (shown in the decision is based on the P (shown in the
quadrant IV, defined with [Power]=Send) having quadrant I, defined with [Power]=Receive)
“a plus sign” when the current lags the voltage. having “a minus sign” when the current leads
the voltage.
[Current]=Lag [Current]=Lead

Figure 9.2-4 Sign of the reactive power (Q) ruled by setting [Current]

9.2.5 Polarity setting for power factor values


The power factor (PF) value is shown by the rule to align the plus/minus sign (±) of the P value
(i.e., setting [PF_sign]=AP, default setting). However, the user can change the rule (i.e., setting
[PF_sign]=AP+RP); as a result, the PF value will have the plus sign (+), provided both the P
value and the Q value have the same plus (+) sign or minus (–) sign.

(i) AP setting
When the sign of the PF value is required to match with the sign of the P value, set AP for the
setting [PF_sign].

GRL200 (Soft 033 & 037)


- 1174 -
6F2S1914 (0.37)

II I II I
(PF <0) (PF>0) (PF <0) (PF <0)
[Power]=
V [Current

III
(PF <0)
I
IV III I
IV
(PF >0)
(PF>0) (PF >0) a. Q has a minus sign be
the outside. The deci
[Power]=Send [Power]=Send sending P having “a
[Current]=Lag [Current]=Lead lags the voltage.

[Current]=Lag
II I II I
(PF >0) (PF<0) (PF >0) (PF <0)

V
V

III
(PF >0)
I
IV III I
IV
(PF<0) (PF >0) (PF <0)

[Power]= Receive [Power]=Receive


[Current]=Lag [Current]=Lead

Figure 9.2-5 PF sign matched with the sign of the P value (i.e., [PF sign]=AP)

(ii) AP+PR setting


When the plus or minus sign of the PF value is required to be in conjunction with the states of
the leading current (i.e., supplying power) and the ragging current (i.e., absorbing power), the
user should set AP+RP for the set [PF_sign]. Note that the plus or minus signs of the P and Q
values cause the difference from the sign of the PF value; thus, the user should figure out the
correspondences between the settings [Power] and [Current] of Figure 9.2-6.

II I II I
(PF <0) (PF>0) (PF >0) (PF <0)
[Powe
V [Curr

III
(PF >0)
I
IV III I
IV
(PF >0)
(PF<0) (PF <0) a. Q has a minus sign
the outside. The d
[Power]=Send [Power]=Send sending P having
[Current]=Lag [Current]=Lead lags the voltage.

[Current]=Lag
II I II I
(PF >0) (PF<0) (PF <0) (PF >0)

V
V

III
(PF <0)
I
IV III I
IV
(PF>0) (PF >0) (PF <0)

[Power]= Receive [Power]=Receive


[Current]=Lag [Current]=Lead

Figure 9.2-6 PF corresponding with P and Q (i.e., [PF sign]=AP+RP)

GRL200 (Soft 033 & 037)


- 1175 -
6F2S1914 (0.37)

9.2.6 Setting for the report (Dead band feature)


The data collected in the metering function will be sent to the network upward, but the data
sent may give the network a heavy burden because the amount of the data sent could be larger.
Thus, the dead band (SD) feature is designed not to send unnecessary data will not be sent
(say, the dead band feature regulates not to send the same data repeatedly). In practice the
analog values in the metering are not always the same; hence, the regulation for not sending
is defined by the user can change it using a setting in each power quantity.

(i) Counting operation in SD feature


Figure 9.2-7 illustrates the operation for the SD feature about entering a current. At Time=0,
the current enters into the VCT and it is observed (Time=0). When the entering current is
being beyond the upper limit (Time=a), a repeated number is set for ‘1’. If the entering current
is out of the upper and lower limits (Time=b), the repeat number gets to have ‘2’. Note that the
repeated number is kept to have ‘2’ even if the entering current goes back within the upper
and lower limits (Time=c). The repeated number will be larger than the setting [Period SD]=3,
when the entering current is out of the upper and lower limits again (i.e., Time=d). Then, at
Time=e, the value of the entering current will be sent to the network, because the repeated
number is incremented. After that, the repeated number will be set zero (0); the new positon
for the SD feature is set (i.e., from Time=e).

Entering current (I)

Following SD position with [ISD]


Upper limit

First SD position with [ISD] First SD standardization level

Lower limit

Repeat number
4
3
2
1
0 Time
a b c d e f g h i j k

Figure 9.2-7 Dead band operation with [PeriodSD]=3

(ii) Check cycle in SD feature


The check cycle is defined for 500 milliseconds in the SD feature. (i.e., interval ab in Figure
9.2-7 is equal to 500ms). If the entering current, in Figure 9.2-7, is required to send promptly
when the entering current is beyond the limits, set 0 for the setting [Period SD].

GRL200 (Soft 033 & 037)


- 1176 -
6F2S1914 (0.37)

(iii) Setting bands for the operation


As illustrated in Figure 9.2-7, with regard to the entering current the user can define the upper
limit and lower limit using the setting [ISD] in %. The limit-size of the SD feature is calculated
based on the amount of the entering current. Table 9.2-4 shows respective settings for the
power quantities.
Table 9.2-4 SD settings for respective quantities
Units for
Quantities SD settings Setting ranges
settings
Voltage VSD % 0.00% to 50.00%

Current ISD % 0.00% to 50.00%

Active/Reactive/Apparent power P/Q/SSD – 0.00% to 50.00%

Power factor PFSD – 0.00 to 1.00

Frequencty FSD % 0.00% to 50.00%

Watt-hour/var-hour Wh/varhSD – 0.0 to 999.9

Phase PhaseSD Degree 0.0 deg. to 90 deg.

Difference of voltages† dVSD % 0.00% to 50.00%


†Note:The values are derived in the VCHK function. For more information, see Chapter
Relay application: Voltage check for autoreclose function .

Metering
10:48 1/8
ISD +
5.00 %
VSD +
0.60 %
dVSD +
0.60 %

Figure 9.2-8 Metering setting in the setting screen


Note: For the operation of the menu, see Chapter User interface: Setting sub-menu.

GRL200 (Soft 033 & 037)


- 1177 -
6F2S1914 (0.37)

Statistics data (Power value group)


Table 9.3-1 shows the statistics information and its abbreviation in power value data.
Table 9.3-1 Power value data
Groups Displayed quantities Abbreviations
Power values Watt-hour (plus/minus), var-hour (plus/minus) Wh, varh

9.3.1 Power information on the screen


Figure 9.3-1 shows the information about the watt-hour and var-hour (Wh and varh).

Power Value
10:48 1/4
Wh+ +
0.0MWh
Wh- +
0.0MWh
varh+ +
0.0Mvarh

Figure 9.3-1 Example of Power Value screen


Note: See Chapter User interface: Monitoring sub-menu: Statistics sub-menu.

9.3.2 Setting for power values


The user can select the unit for each power value. For example, set the [Wh-Display Unit]=kWh,
when kWh is perferred to display.
Table 9.3-2 Selection of units for displaying
Statisics items Settings Selection of a unit fot the displaying
Watt-hour Wh-Display Unit Kilo-watt-hour (kWh) or Mega-watt-hour (MWh)

Var-hour Varh-Display Unit Kilo-var-hour (kvarh) or Mega-var-hour (Mvarh)

9.3.3 Regulation of power values


The number of digits for the power value can be reduced based on the units kWh, MWh and
kvarh+. For instance when the power is measured as "123,456kWh" then it is displayed as
"123MWh". If this value has to be changed then the user can key in a new compensated value.
For example, if "78MWh" should be displayed on the IED screen even though the measured
value is "123,456kWh" then the user can set the new value of "78MWh". Note that the
compensated value "78MWh" is "78,000kWh", and it is not "78,456kWh" or "123,456kWh"; the
compensated value will be affected when a change in the setting of VCT ratio. That is, the user
can set a value of "78MW" during the CT ratio of "2000:1", but the CT ratio would be changed
from "2000:1" to "4000:1"; hence, the value will be displayed as "156MW" on the IED screen
later. Therefore, when the CT ratio setting is required to be changed, remember to set the value
of "78MW" again to display the compensated value.

GRL200 (Soft 033 & 037)


- 1178 -
6F2S1914 (0.37)

Statistics data (Demand value group)


The user can keep track of the variable power quantities using the demand feature; the
statistical information (such as maximum load, minimum load, and averaged load) are
collected in every defined period.

Table 9.4-1 Demand data for ’33 and 37’ software3


Groups Displayed quantities Abbreviations
Current in phase-a (Max., Min., and Averaged data) Ia Max, Ia Min, Ia Ave

Current in phase-b (Max., Min., and Averaged data) Ib Max, Ib Min, Ib Ave

Current in phase-c (Max., Min., and Averaged data) Ic Max, Ic Min, Ic Ave

Residual current (Max., Min., and Averaged data) Ie Max, Ie Min, Ie Ave(1)

The other residual current on parallel lines (Max., Min., and Averaged) Iem Max, Iem Min, Iem Ave(1)

Voltage applied at phase-a (Max., Min., and Averaged data) Va Max, Va Min, Va Ave

Voltage applied at phase-b (Max., Min., and Averaged data) Vb Max, Vb Min, Vb Ave
Demand
value Vc Max, Vc Min, Vc Ave
Voltage applied at phase-c (Max., Min., and Averaged data)

Voltage applied between phases-a-to-b (Max., Min., and Averaged data) Vab Max, Vab Min, Vab Ave

Voltage applied between phases-b-to-b (Max., Min., and Averaged data) Vbc Max, Vbc Min, Vbc Ave

Voltage applied between phases-c-to-a (Max., Min., and Averaged data) Vca Max, Vca Min, Vca Ave

Zero-sequence voltage (Max., Min., and Averaged data) V0 Max, V0 Min, V0 Ave(2)

Reference voltages (Max., Min., and Averaged data) Vs Max, Vs Min, Vs Ave

The other reference voltages (Max., Min., and Averaged data) Vs2 Max, Vs2 Min, Vs2 Ave

9.4.1 Demand information on the screen


The statistics feature can provides the information about maximum, minimum, and averaged
values. Figure 9.4-1 shows the example about the current information

Demand Value
10:48 1/42
Ia Max
0.00kA
Ia Min
0.00kA
Ia Ave
0.00kA

Figure 9.4-1 Example of Demand Value screen

9.4.2 Max/Min/Averaged information about the demand feature


The demand feature is used to calculate the active power (P), the reactive power (P), and the
complex power (S) that are weighted with the plus (+) or minus (–) sign; the calculation will be

GRL200 (Soft 033 & 037)


- 1179 -
6F2S1914 (0.37)

made by the following rules:


(i) Maximum and minimum value
For example, the demand feature gets to have both a minus (e.g., –100 watt) and a plus (e.g.,
+50 watt) values, ‘–100 watt’ is taken to the minimum data and ‘+50 watt’ is taken to the
maximum data. Note that given values do not come out as absolute values.

(ii) Averaged value


If the demand feature gets a data (e.g. +100 watt) in the first period and the other data (that
is, –100 watt) in the later period, the data is taken into the absolute value calculation (that is,
|–100W|+|100W|=200W; 200W/2=100W).

9.4.3 Demand cycle


The data is taken into the memory every second; the demand feature will calculate the
Max/Min/Ave values by the function by collecting the latest data in the memory. When setting
15 minutes for the [Demand_period], for example, the calculation is done using the data during
the latest 15 minutes. The user can have the cycle of the demand feature be selected among
1min, 5min, 10min, 15min, 30min, and 60min.

Metering
10:48 21/23
PhaseSD +
0.50 deg
PeriodSD +
0
Demand_period +
10 min

Figure 9.4-2 Demand cycle setting in the setting screen

9.4.4 Resetting data in demand features


The data will be cleared by the following cases:
(a) To energize the IED or to make the initialization about the IED functions
(b) To set a value for the setting [Demand_period]
(c) To operate “Reset All Values” on the IED menu

Demand Value
10:48 1/2
Demand Value >
Reset All Values +

Figure 9.4-3 Reset menu for Demand values

GRL200 (Soft 033 & 037)


- 1180 -
6F2S1914 (0.37)

Statistics data (Peak-demand value group)


Similar to the demand feature (Demand value group), the user can have another peak-demand
feature that provides the Max/Min/Ave data that can be obtained from the initialized time to
the current time; note these data have been calculated from the first energizing moment of the
IED. That is, the data of the peak-demand feature gets to have the latest values in every cycle;
the data will be replaced if the past data is not needed. The user can find that the nature of
the collected values in the peak-demand values being identical to the one of the Demand value
group.

9.5.1 Max/Min/Averaged information about the peak-demand feature


(i) Maximum value
The peak-demand feature starts to collect the data in every cycle after the IED energized; the
peak-demand feature will have the largest data. If the present data is larger than the past one
with the peak-demand feature will replace the past one for the present one. The maximum
value will be cleared when the data is reset.

(ii) Minimum value


Similarly, for the minimum value, the IED displays the smallest data after energizing; the data
will be replaced when the present data is smaller than the past one.

(iii) Averaged value


The averaged value is computed using the data in the IED memory, the data which was
collected after energizing. Collecting data stays on for a long time; hence, when the counter
with regard to the data collection gets to be 2,147,483,647(=0x7FFFFFFF; almost 68 years),
resetting data is performed.

9.5.2 Resetting data of peak-demand features


The data will be cleared by the following operations:
(a) To energize the IED or to make the initialization about the IED functions
(b) To operate “Reset All Values” on the IED menu

Peak Demand
10:48 1/2
Peak Demand Value >
Reset All Values +

Figure 9.5-1 Reset menu for Peak demand values

GRL200 (Soft 033 & 037)


- 1181 -
6F2S1914 (0.37)

Statistics data (Counter group)


The user can check the counting numbers provided by the general counter function†. Table
9.6-1 shows the user to find the count numbers in the counter group.
Table 9.6-1 Counter data
Counter number Correspondences
Group Origin of info (default)
displayed to GCNTs†
ARC1 CLOSE COMMAND ARC function‡ GCNT01

ARC1_SPAR ARC function GCNT02

ARC1_TPAR ARC function GCNT03

ARC1_MPAR ARC function GCNT04

ARC2 CLOSE COMMAND ARC function GCNT05

ARC2_SPAR ARC function GCNT06


Counter
ARC2_TPAR ARC function GCNT07

ARC2_MPAR ARC function GCNT08

COUNT9 (Not assigned) GCNT09

COUNT10 (Not assigned) GCNT10

…. …. ….

COUNT32 (Not assigned) GCNT32

†Note:See Chapter General control function: Counter function for the general (GCNT) .
‡Note:See Chapter Relay application: Autoreclose for more information.

9.6.1 Count information on the screen


The user can see the count number in the counter group. Figure 9.6-1 illustrates the count
numbers provided by the ARC function.

Counter
10:48 1/32
ARC1 CLOSE COMMAND +
0
ARC1_SPAR +
0
ARC1_TPAR +
0

Figure 9.6-1 Example of Counter screen


Note: See Chapter User interface: Monitoring sub-menu: Statistics sub-menu.

9.6.2 Report setting for GCNT (Dead band feature)


The data collected with the GCNT functions will be sent to the network; thus, the user should
set a regulation value using the SD feature in the GCNT function. See section Setting for the
report (Dead band) in the GCNT function.

GRL200 (Soft 033 & 037)


- 1182 -
6F2S1914 (0.37)

Statistics data (Accumulated time)


Over all running time for which the IED has operated is provided in “Accumulated Time”. The
user can see the overall time on the Accumulated Time screen. The time will be cleared when
the IED is switched off.

Accumulated Time
10:48 1/1
ACT_TIME +
***d **h **m

Figure 9.7-1 Example of Accumulated Time screen


Note: The user can also clear the Accumulated time in the screen menu. For key
operation, see Chapter User interface: Monitoring sub-menu: Statistics sub-menu.

GRL200 (Soft 033 & 037)


- 1183 -
6F2S1914 (0.37)

Statistics data (Total time group)


Total times are provided by the total time measurement function†, as shown in Table 9.6-1.
Table 9.8-1 Total time data
Correspondences
Group Displayed quantities Origin of time data
to TOTALTIM†
TOTAL TIME 1 TOTALTIM01 function TT1

TOTAL TIME 2 TOTALTIM02 function TT2

Total time TOTAL TIME 3 TOTALTIM03 function TT3

…. …. ….

TOTAL TIME 12 TOTALTIM03 function TT12

†Note:See Chapter Control and monitoring application: Total time measurement


function

9.8.1 Time information on the screen


The user can see the total times on the IED screen.

Total Time
10:48 1/12
TOTAL TIME 1 +
****d **h **m
TOTAL TIME 2 +
****d **h **m
TOTAL TIME 3 +
****d **h **m

Figure 9.8-1 Example of Total Time screen


Note: See Chapter User interface: Monitoring sub-menu: Statistics sub-menu.

9.8.2 Report setting for TOTALTIM (Dead band feature)


The data collected with the TOTALTIM function will be sent to the network; thus, the user
should set a regulation value using the SD feature in the TOTALTIME function. See section
Setting for the report (Dead band) in the TOTALTIME function.

GRL200 (Soft 033 & 037)


- 1184 -
6F2S1914 (0.37)

Monitoring for miscellaneous functions


Operating status of relay elements, binary IO modules, communication modules, GOOSE, and
diagnostics are displayed in the monitoring function.

(i) Relay element


(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Relay Elements. The relay functions and their characteristics are discussed in Chapter
Relay application).

(ii) Communication
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Communication. The communication features about the LAN port is discussed in
Chapter Communication protocol: LAN communication. The hardware information is
discussed in Chapter Technical description: Signal processing and communication module).

(iii) Binary IO
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Binary I/O. The structure and its operation is discussed in Chapter Technical
description: Binary IO module).

(iv) Goose monitoring


(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Goose monitoring. The information about the GOOSE is discussed in Chapter
Communication protocol: IEC 61850 communication).

(v) Diagnostics
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Diagnostics sub-menu. The information about the diagnostics is discussed in Chapter
Automatic supervision).

GRL200 (Soft 033 & 037)


- 1185 -
6F2S1914 (0.37)

Setting
Metering settings in MES (Function ID: 710001)
Unit Default
Setting item Range Contents Notes
s setting value
Display Value Primary/Secondary – Display selection of primary or secondary Primary
Power Send/Receive – Power flow definition (Supply or absorb) Send
Current Lead/Lag – The angle compared with the voltage Lead
PF Sign AP/AP+RP – Decision of the sign of the power factor AP+RP
I-Valid Level 0.10 to 5.00 % Cutting off small entering current 4.00
V-Valid Level 0.10 to 5.00 % Cutting off small applied voltage 0.30
I-Display Unit A/kA – Current shown in Ampere or Kilo-Ampere kA
V-Display Unit V/kV – Voltage shown in Volt or Kilo-Volt kV
P-Display Unit kW/MW – Active power shown in Kilo- or Mega-watt MW
Q-Display Unit kvar/Mvar – Reactive power shown in Kilo- or Mega-var Mvar
S-Display Unit kVA/MVA – Apparent power shown in Kilo- or Mega-
MVA
VA

Statistics settings in MES (Function ID: 710001)


Unit Default
Setting item Range Contents Notes
s setting value
Wh-Display Unit kWh/MWh – Watt-hour shown in Kilo- or Mega-Wh MWh
varh-Display Unit kvarh/Mvarh – Var-hour shown in Kilo- or Mega-varh Mvarh

Demand settings in MES (Function ID: 712001)


Unit Default
Setting item Range Contents Notes
s setting value
1min / 5min /
Demand_period 10min / 15min / – Period of demand calculation 10min
30min / 60min

Dead-band setting in MES (Function ID: 710001)


Unit Default
Setting item Range Contents Notes
s setting value
ISD 0.00 to 50.00 % Sending Dead Band in current 5.00
VSD 0.00 to 50.00 % Sending Dead Band in voltage 0.60
P/Q/SSD 0.00 to 50.00 % P/Q/S Sending Dead Band 5.00
PFSD 0.00 to 1.00 – PF Sending Dead Band 0.02
FSD 0.00 to 50.00 % F Sending Dead Band 0.50
Wh/varhSD 0.0 to 999.9 – Wh/varh Sending Dead Band 1.0
PhaseSD 0.0 to 90.0 deg Phase Sending Dead Band 0.5
PeriodSD 0 to 4 – Period of Sending Dead band 0
dVSD 0.00 to 50.00 % dV Sending Dead Band 0.60

Setting of Test in MES (Function ID: 710001)


Unit Default
Setting item Range Contents Notes
s setting value
Commercial Test OFF / ON – Commercial Test Switch OFF / ON

GRL200 (Soft 033 & 037)


- 1186 -
6F2S1914 (0.37)

Data ID
 Signal monitoring point
MES_MANAGEMENT (Function ID: 711001)
Element ID Name Description
3100901060 CT-ERR CT Monitoring Result

3100911060 I0-ERR I0 Monitoring Result

3100921060 V0-ERR V0 Monitoring Result

3100961060 V02-ERR V02 Monitoring Result

3100931060 V2-ERR V2 Monitoring Result

3100971060 V22-ERR V22 Monitoring Result

 Signals generated for the 61850


MES_MANAGEMENT (Function ID: 711001)
Element ID Name Description
4201601051 Ia-Angle Ia measurement angle(for IEC61850)
4201601053 Ib-Angle Ib measurement angle(for IEC61850)
4201601055 Ic-Angle Ic measurement angle(for IEC61850)
4201611051 Iab-Angle Iab measurement angle(for IEC61850)
4201611053 Ibc-Angle Ibc measurement angle(for IEC61850)
4201611055 Ica-Angle Ica measurement angle(for IEC61850)
4201691051 Ia2-Angle Ia2 measurement angle(for IEC61850)
4201691053 Ib2-Angle Ib2 measurement angle(for IEC61850)
4201691055 Ic2-Angle Ic2 measurement angle(for IEC61850)
42016a1051 Iab2-Angle Iab2 measurement angle(for IEC61850)
42016a1053 Ibc2-Angle Ibc2 measurement angle(for IEC61850)
42016a1055 Ica2-Angle Ica2 measurement angle(for IEC61850)
4201621051 I1-Angle I1 measurement angle(for IEC61850)
4201621053 I2-Angle I2 measurement angle(for IEC61850)
4201621057 I0-Angle I0 measurement angle(for IEC61850)
42016b1051 I12-Angle I12 measurement angle(for IEC61850)
42016b1053 I22-Angle I22 measurement angle(for IEC61850)
42016b1057 I02-Angle I02 measurement angle(for IEC61850)
4201631057 Iem-Angle Iem measurement angle(for IEC61850)
4202641051 Va-Angle Va measurement angle(for IEC61850)
4202641053 Vb-Angle Vb measurement angle(for IEC61850)
4202641055 Vc-Angle Vc measurement angle(for IEC61850)
4202651051 Vab-Angle Vab measurement angle(for IEC61850)
4202651053 Vbc-Angle Vbc measurement angle(for IEC61850)
4202651055 Vca-Angle Vca measurement angle(for IEC61850)
4202661051 V1-Angle V1 measurement angle(for IEC61850)
4202661053 V2-Angle V2 measurement angle(for IEC61850)
4202661057 V0-Angle V0 measurement angle(for IEC61850)
4202671057 Vs-Angle Vs measurement angle(for IEC61850)
4202681057 Vs2-Angle Vs2 measurement angle(for IEC61850)
4201601076 Ia Ia measurement primary(for IEC61850)
4201601078 Ib Ib measurement primary(for IEC61850)
420160107A Ic Ic measurement primary(for IEC61850)

GRL200 (Soft 033 & 037)


- 1187 -
6F2S1914 (0.37)

 Signals generated for the 61850


MES_MANAGEMENT (Function ID: 711001)
Element ID Name Description
4201611076 Iab Iab measurement primary(for IEC61850)
4201611078 Ibc Ibc measurement primary(for IEC61850)
420161107A Ica Ica measurement primary(for IEC61850)
4201691076 Ia2 Ia2 measurement primary(for IEC61850)
4201691078 Ib2 Ib2 measurement primary(for IEC61850)
420169107A Ic2 Ic2 measurement primary(for IEC61850)
42016a1076 Iab2 Iab2 measurement primary(for IEC61850)
42016a1078 Ibc2 Ibc2 measurement primary(for IEC61850)
42016a107A Ica2 Ica2 measurement primary(for IEC61850)
4201621076 I1 I1 measurement primary(for IEC61850)
4201621078 I2 I2 measurement primary(for IEC61850)
420162107C I0 I0 measurement primary(for IEC61850)
42016b1076 I12 I12 measurement primary(for IEC61850)
42016b1078 I22 I22 measurement primary(for IEC61850)
42016b107C I02 I02 measurement primary(for IEC61850)
420163107C Iem Iem measurement primary(for IEC61850)
4202641076 Va Va measurement primary(for IEC61850)
4202641078 Vb Vb measurement primary(for IEC61850)
420264107A Vc Vc measurement primary(for IEC61850)
4202651076 Vab Vab measurement primary(for IEC61850)
4202651078 Vbc Vbc measurement primary(for IEC61850)
420265107A Vca Vca measurement primary(for IEC61850)
4202661076 V1 V1 measurement primary(for IEC61850)
4202661078 V2 V2 measurement primary(for IEC61850)
420266107C V0 V0 measurement primary(for IEC61850)
420267107C Vs Vs measurement primary(for IEC61850)
420268107C Vs2 Vs2 measurement primary(for IEC61850)
42066c105C f Frequency measurement(for IEC61850)
42016d1051 Ia-R1-Angle Ia Remote CH1 measurement angle(for IEC61850)
42016d1053 Ib-R1-Angle Ib Remote CH1 measurement angle(for IEC61850)
42016d1055 Ic-R1-Angle Ic Remote CH1 measurement angle(for IEC61850)
42016e1057 Ie-R1-Angle Ie Remote CH1 measurement angle(for IEC61850)
42016f1051 Ia2-R1-Angle Ia2 Remote CH1 measurement angle(for IEC61850)
42016f1053 Ib2-R1-Angle Ib2 Remote CH1 measurement angle(for IEC61850)
42016f1055 Ic2-R1-Angle Ic2 Remote CH1 measurement angle(for IEC61850)
4201701057 Ie2-R1-Angle Ie2 Remote CH1 measurement angle(for IEC61850)
4201711051 Ia-R2-Angle Ia Remote CH2 measurement angle(for IEC61850)
4201711053 Ib-R2-Angle Ib Remote CH2 measurement angle(for IEC61850)
4201711055 Ic-R2-Angle Ic Remote CH2 measurement angle(for IEC61850)
4201721057 Ie-R2-Angle Ie Remote CH2 measurement angle(for IEC61850)
4201731051 Ia2-R2-Angle Ia2 Remote CH2 measurement angle(for IEC61850)
4201731053 Ib2-R2-Angle Ib2 Remote CH2 measurement angle(for IEC61850)
4201731055 Ic2-R2-Angle Ic2 Remote CH2 measurement angle(for IEC61850)
4201741057 Ie2-R2-Angle Ie2 Remote CH2 measurement angle(for IEC61850)

GRL200 (Soft 033 & 037)


- 1188 -
6F2S1914 (0.37)

 Signals generated for the 61850


MES_MANAGEMENT (Function ID: 711001)
Element ID Name Description
42016d1076 Ia-R1 Ia Remote CH1 measurement primary(for IEC61850)
42016d1078 Ib-R1 Ib Remote CH1 measurement primary(for IEC61850)
42016d107A Ic-R1 Ic Remote CH1 measurement primary(for IEC61850)
42016e107C Ie-R1 Ie Remote CH1 measurement primary(for IEC61850)
42016f1076 Ia2-R1 Ia2 Remote CH1 measurement primary(for IEC61850)
42016f1078 Ib2-R1 Ib2 Remote CH1 measurement primary(for IEC61850)
42016f107A Ic2-R1 Ic2 Remote CH1 measurement primary(for IEC61850)
420170107C Ie2-R1 Ie2 Remote CH1 measurement primary(for IEC61850)
4201711076 Ia-R2 Ia Remote CH2 measurement primary(for IEC61850)
4201711078 Ib-R2 Ib Remote CH2 measurement primary(for IEC61850)
420171107A Ic-R2 Ic Remote CH2 measurement primary(for IEC61850)
420172107C Ie-R2 Ie Remote CH2 measurement primary(for IEC61850)
4201731076 Ia2-R2 Ia2 Remote CH2 measurement primary(for IEC61850)
4201731078 Ib2-R2 Ib2 Remote CH2 measurement primary(for IEC61850)
420173107A Ic2-R2 Ic2 Remote CH2 measurement primary(for IEC61850)
420174107C Ie2-R2 Ie2 Remote CH2 measurement primary(for IEC61850)
4209751057 Ise-Angle Ise measurement angle(for IEC61850)
420975107C Ise Ise measurement primary(for IEC61850)
4202761051 Va2-Angle Va2 measurement angle(for IEC61850)
4202761053 Vb2-Angle Vb2 measurement angle(for IEC61850)
4202761055 Vc2-Angle Vc2 measurement angle(for IEC61850)
4202771051 Vab2-Angle Vab2 measurement angle(for IEC61850)
4202771053 Vbc2-Angle Vbc2 measurement angle(for IEC61850)
4202771055 Vca2-Angle Vca2 measurement angle(for IEC61850)
4202781051 V12-Angle V12 measurement angle(for IEC61850)
4202781053 V22-Angle V22 measurement angle(for IEC61850)
4202781057 V02-Angle V02 measurement angle(for IEC61850)
4202791057 V4-Angle V4 measurement angle(for IEC61850)
4202761076 Va2 Va2 measurement primary(for IEC61850)
4202761078 Vb2 Vb2 measurement primary(for IEC61850)
420276107A Vc2 Vc2 measurement primary(for IEC61850)
4202771076 Vab2 Vab2 measurement primary(for IEC61850)
4202771078 Vbc2 Vbc2 measurement primary(for IEC61850)
420277107A Vca2 Vca2 measurement primary(for IEC61850)
4202781076 V12 V12 measurement primary(for IEC61850)
4202781078 V22 V22 measurement primary(for IEC61850)
420278107C V02 V02 measurement primary(for IEC61850)
420279107C V4 V4 measurement primary(for IEC61850)
42017a1076 DIFL-Ida Ida measurement primary(for IEC61850)
42017a1078 DIFL-Idb Idb measurement primary(for IEC61850)
42017a107A DIFL-Idc Idc measurement primary(for IEC61850)
42017b1076 DIFL-Ira Ira measurement primary(for IEC61850)
42017b1078 DIFL-Irb Irb measurement primary(for IEC61850)
42017b107A DIFL-Irc Irc measurement primary(for IEC61850)

GRL200 (Soft 033 & 037)


- 1189 -
6F2S1914 (0.37)

 Signals generated for the 61850


MES_MANAGEMENT (Function ID: 711001)
Element ID Name Description
42017c107C DIFGL-Id0 Id0 measurement primary(for IEC61850)
42017d107C DIFGL-Ir0 Ir0 measurement primary(for IEC61850)
42037e1095 Pa Pa measurement primary(for IEC61850)
42037e1096 Pb Pb measurement primary(for IEC61850)
42037e1097 Pc Pc measurement primary(for IEC61850)
42037e1098 P P measurement primary(for IEC61850)
42047f1095 Qa Qa measurement primary(for IEC61850)
42047f1096 Qb Qb measurement primary(for IEC61850)
42047f1097 Qc Qc measurement primary(for IEC61850)
42047f1098 Q Q measurement primary(for IEC61850)
4205801095 Sa Sa measurement primary(for IEC61850)
4205801096 Sb Sb measurement primary(for IEC61850)
4205801097 Sc Sc measurement primary(for IEC61850)
4205801098 S S measurement primary(for IEC61850)
4203811095 Pa2 Pa2 measurement primary(for IEC61850)
4203811096 Pb2 Pb2 measurement primary(for IEC61850)
4203811097 Pc2 Pc2 measurement primary(for IEC61850)
4203811098 P2 P2 measurement primary(for IEC61850)
4204821095 Qa2 Qa2 measurement primary(for IEC61850)
4204821096 Qb2 Qb2 measurement primary(for IEC61850)
4204821097 Qc2 Qc2 measurement primary(for IEC61850)
4204821098 Q2 Q2 measurement primary(for IEC61850)
4205831095 Sa2 Sa2 measurement primary(for IEC61850)
4205831096 Sb2 Sb2 measurement primary(for IEC61850)
4205831097 Sc2 Sc2 measurement primary(for IEC61850)
4205831098 S2 S2 measurement primary(for IEC61850)
420684105C f2 Frequency measurement(for IEC61850)
4200851091 PFa PFa measurement(for IEC61850)
4200851092 PFb PFb measurement(for IEC61850)
4200851093 PFc PFc measurement(for IEC61850)
4200851094 PF PF measurement(for IEC61850)
4200861091 PFa2 PFa measurement(for IEC61850)
4200861092 PFb2 PFb measurement(for IEC61850)
4200861093 PFc2 PFc measurement(for IEC61850)
4200861094 PF2 PF measurement(for IEC61850)
4202871095 VR1 Running voltage of SyncRy1 (for IEC61850)
4202871096 VI1 Incoming voltage of SyncRy1 (for IEC61850)
4202871097 dV-SyncRy1 Differential voltage of SyncRy1's VR and VI (for IEC61850)
4200881099 dAng.-SyncRy1 Differential angle of SyncRy1's VR and VI (for IEC61850)
420689109E df-SyncRy1 Differential frequency of SyncRy1's VR and VI (for IEC61850)
42068a109E VR1-f Frequency of SyncRy1's VR (for IEC61850)
42068b109E VI1-f Frequency of SyncRy1's VI (for IEC61850)
42028a1095 VR2 Running voltage of SyncRy2 (for IEC61850)
42028a1096 VI2 Incoming voltage of SyncRy2 (for IEC61850)

GRL200 (Soft 033 & 037)


- 1190 -
6F2S1914 (0.37)

 Signals generated for the 61850


MES_MANAGEMENT (Function ID: 711001)
Element ID Name Description
42028a1097 dV-SyncRy2 Differential voltage of SyncRy2's VR and VI (for IEC61850)
42008b1099 dAng.-SyncRy2 Differential angle of SyncRy2's VR and VI (for IEC61850)
42068c109E df-SyncRy2 Differential frequency of SyncRy2's VR and VI (for IEC61850)
42068d109E VR2-f Frequency of SyncRy2's VR (for IEC61850)
42068e109E VI2-f Frequency of SyncRy2's VI (for IEC61850)
4317601098 Wh+ Wh+ measurement primary(for IEC61850)
4317611098 Wh- Wh- measurement primary(for IEC61850)
4318621098 varh+ varh+ measurement primary(for IEC61850)
4318631098 varh- varh- measurement primary(for IEC61850)
4317641098 Wh2+ Wh2+ measurement primary(for IEC61850)
4317651098 Wh2- Wh2- measurement primary(for IEC61850)
4318661098 varh2+ varh2+ measurement primary(for IEC61850)
4318671098 varh2- varh2- measurement primary(for IEC61850)
4212681095 VB Busbar Voltage (for IEC61850)
4212681096 VL Line Voltage (for IEC61850)
4212681097 dV-SYN1 Differential voltage of SYN1's VB and VL (for IEC61850)
4210691099 dAng.-SYN1 Differential angle of SYN1's VB and VL (for IEC61850)
42166a109E df-SYN1 Differential frequency of SYN1's VB and VL (for IEC61850)
42126b1095 VL2 Line2 voltage (for IEC61850)
42126b1097 dV-SYN2 Differential voltage of SYN2's VL2 and VL (for IEC61850)
42106c1099 dAng.-SYN2 Differential angle of SYN2's VL2 and VL (for IEC61850)
42166d109E df-SYN2 Differential frequency of SYN2's VL2 and VL (for IEC61850)

GRL200 (Soft 033 & 037)


- 1191 -
6F2S1914 (0.37)

10 Automatic supervision
Contents Pages Pages
61850 irregular data 1233 Interruption 1206
A/D accuracy error on VCT 1210 LAN pinging error 1231
Abnormal currents flowing on CTs 1211 LAN error 1230
Aux. contacts monitoring 1235 LRE error 1232
BIO module#1 error 1216 Master-slave error 1273
BIO module#2 error 1217 MRAM memory error 1202
BIO module#3 error 1218 PLC Data error 1226
BIO module#4 error 1219 Power supply failure 1225
BIO module#5 error 1220 Program code error 1204
BIO module#6 error 1221 Propagation delay 1269
BIO module#7 error 1222 RAM error 1200
BIO module#8 error 1223 Relay ID number error 1274
CB failure 1228 Remote terminal error 1271
CB interruption capability error 1257 ROM and RAM mismatch 1198
Check-sum error 1199 Run error 1205
Clock error 1209 Sampling error 1207
Communication failure 1266 Setting error 1208
Communication configuration error 1270 Sigma Iy error 1259
Communication receive data error 1268 Trip circuit error 1253
Communication send data error 1267 Trip circuit supervision task 1249
Communication synchronization error 1265 Voltage error in negative-sequence 1214
Communication transmission error 1272 Voltage error in zero-sequence 1215
CT failure detected by DIF 1264 VT error 1227
CT open circuit 1212
Current error in zero-sequence 1213
DIF current error 1263
DS failure 1229
ECC memory error 1201
FPGA problem 1203
GOOSE publishing error 1234
HMI malfunction 1224

GRL200 (Soft 033 & 037)


- 1192 -
6F2S1914 (0.37)

Outline of automatic supervision


In power system, the protection function is not required to operate during normal conditions.
That is, the protection function should stay silent for the unfaulty conditions, but it has to start
respond immediately upon the occurrence of the fault. Therefore, as for the operation of the
protection system, the detection of an unhealthy condition, such as malfunction or errors in
the hardware or in the software, is requisite within the IED. The automatic supervision
function is designed to detect the unhealthy condition within the IED; the following concepts
are taken into account:
 The operating performance of the protection system should not be distorted.
 Supervision should be carried out by itself without any failure whenever
possible.
 The protection system should identify the fault instantly upon its occurrence.

Tips: The alarms can be blocked when Off is set for the switch [A.M.F]. The switch can
be used to remove alarms during testing. See Chapter User interface: Test sub-
menu for more information.

(i) Error levels


In the applications and the hardware, the number of items are supervised for detecting the
operation failure; hence, the results of the supervision functions are grouped and they are
classified into five error-levels to identify the error degree directly: warning (level 5=the minor
error) to the serious error (level 1=the critical error). Incidentally, zero (level 0) can be
identified as no error. Table 10.1-1 shows the errors grouped by the error degree. The grouping
is provided, for setting the degree of error, the user can select an user-defined degree for each
error occurs randomly. If a number of failures occur on several levels at same time, the
automatic supervision function selects the critical error among them to represent the error
inside the IED.
Table 10.1-1 Meanings and error degree in the supervision function
Levels Degree of error Example failures and errors
0 No error No error exists
1‡ Serious Fatal failures such as the memory errors within the IED
2†‡ Serious (Comm.) Failures on tele-communication
3†‡ Minor Failure on LAN (Ethernet) communication
4 Alarm Minor errors such as invalid errors by the user using settings
5 Warning Detection of warnings classified by the user using settings
†Note:Level 2 and level 3 are shown, but the difference between the level 2 and the level
3 not given; thus, we can take the both having the same degree.
‡Note: The IEC 61850quality value is also changed depending on the error level. For
more information, see Chapter Communication protocol: IEC 61850
communication: Quality signal.

GRL200 (Soft 033 & 037)


- 1193 -
6F2S1914 (0.37)

(ii) Error LED and LCD error message


The IED has LEDs and LCD screen† so that the automatic supervision function issues a result
for the LEDs and the LCD screen. When the IED is linked with the SAS, it is possible to
transfer the result for the LED and LCD screen using the communication system. Table 10.1-2
shows that which indicators are used for result generation in the function.
Table 10.1-2 Displays on LEDs, LCD, and SAS
Levels “In service” LED “Error” LED Error message on LCD
0: No error On Off (Not displayed)
1: Serious Off On Displayed
2: Serious (Comm.) On On Displayed
3: Minor On On Displayed
4: Alarm On Off Displayed
5: Warning On Off Displayed
†Note:For more information, see Chapter User interface: Outline and Diagnostics.
‡Note:It depends on the degree of the communication failure.

The user can see a current error information in Monitoring sub-menu† on the LCD
screen† (see Figure 10.1-1); Table 10.1-3 shows the six detail information, which the user can
examine carefully using the hexadecimal number. When two or more errors occur at the same
time, an error code is given by the summation of the error codes. That is, when X and Y errors
(e.g., X-error-code ‘00000002’ and Y-error-code ‘00000004’) occur, the sum value ‘00000006’ is
screened.
CP1M(ROM/RAM) error 1/1 Current error indicated by Supervision
10:48 Current local time (Not Error occurring time)
[Serious error] Error degree (level) displayed
Detailed information in Hexadecimal dump
[00000011] [01234567] 7 6 5 4 3 2 1 0
[01234567]
[01234567]
[01234567]
[00000000] [ “Top left” ][ “Top right” ]
[ “Middle left” ][ “Middle right” ]
[ “Bottom left” ][ “Bottom right” ]
Figure 10.1-1 Example error codes and detailed information on Diagnostics sub-menu
†See Chapter User interface: Monitoring sub-menu: Diagnostics. Note that the
information will not be updated automatically. Refresh the information if
required.
Table 10.1-3 Detailed information in Hexadecimal in the ROM and the RAM error (example)
Display Meaning of the detailed information
area Left column Right column
00000001: ROM read error
Top row ROM address
00000002: ROM RAM mismatch
Middle row RAM address ROM value
Bottom row RAM value (No information displayed)

GRL200 (Soft 033 & 037)


- 1194 -
6F2S1914 (0.37)

(iii) Error outputs with contacts and binary output circuits


Automatic supervision function drives a contact of the power supply module (PWS)† when an
error occurs without warning; additionally, binary output circuits (BOs‡) will be locked out to
drive when serious error (Level 1=Critical error) is detected.
Table 10.1-4 FAIL contact, BO, LED outputs depending on levels
PWS† contact outputs
Error FAIL1 terminal FAIL2 terminal Error
BO‡ locked out
Levels Screw No. 1 Screw No. 3 Screw No. 7 Screw No. 9 LED
(N/C) (N/O) (N/C) (N/O)
0: No error Open Closed Open Closed Not locked out Off
1:Serious Closed Open Closed Open Locked out On
2:Serious(Comm.) Open Closed Open Closed Not locked out On
3:Minor Open Closed Open Closed Not locked out On
4:Alarm Open Closed Open Closed Not locked out Off
5:Warning Open Closed Open Closed Not locked out Off

Error output by PWS contact†


If serious error (Level1) is detected by Automatic supervision function, normally-closed-contact
(N/C) on FAIL1 and FAIL2 terminals is closed. On the other hand, the N/O contact is open on
the serious error, as shown in Table 10.1-4.

Locking out of BO circuit operation‡


BO is locked out to operate, when serious error (Level1) occurs. Serious error stops trip signal
generations to the BO circuit. When serious error is removed, the operation will be recovered.
†Note:See Chapter Technical description: Power supply module. FAIL1 (FAIL2) contact
is in Form-C; terminal-screw No. 2 & 4 (8 &10) are provided with the common.
‡Note:BO is discussed in Chapter Technical description: Binary output circuit.

(iv) Affection of application operation by error levels


The error levels influence the operation of relay and control and monitoring application.
Table 10.1-5 Operation states in the IED applications affected by the error levels
Levels Relay applications Control and monitoring applications Notes
0: No error – –
1: Serious Stopped Stopped
2: Serious (Comm.) Not affected† Not affected
3: Minor Not affected Stopped
4: Alarm Not affected Not affected
5: Warning Not affected Not affected
†Note: Serious (Comm.) can be related to communication of tele-protection applications.

GRL200 (Soft 033 & 037)


- 1195 -
6F2S1914 (0.37)

Generic supervision tasks


Displaying errors regarding the common problems are summarized in Table 10.2-1; the error
will be cleared when recovered
Table 10.2-1 Supervision items and error levels for generic
Detailed Error
Sec.No. Supervision items(Screen message) Info. Lvl LED
10.2.1 Mismatch between ROM and RAM data (ROM/RAM error) Displayed 1 ON
10.2.2 Supervision of check-sum error (SUM error) Displayed 1 ON
10.2.3 Supervision of RAM (RAM error) Displayed 1 ON
10.2.4 Supervision of ECC on memory (ECC error) Displayed 1 ON
10.2.5 Supervision of MRAM (MRAM) Displayed 1 ON
10.2.6 Supervision of FPGA (FPGA error) Displayed 1 ON
10.2.7 Supervision of program codes (CPU error) Displayed 1 ON
10.2.8 Supervision of task operation (RUN error) Displayed 1 ON
10.2.9 Detecting non-maskable interrupt (NMI error) Displayed 1 ON
10.2.10 Supervision of sampling period (SMP error) Displayed 1 ON
10.2.11 Supervision of setting data (Setting error) Displayed 1 ON
10.2.12 Supervision of real-time clock (RTC error) Displayed 3 ON
10.2.13 Supervision of analog input data on VCTs (AI ACC error) Displayed 1 ON
10.2.14 Abnormal currents flowing in CTs (CT error) N/A 3 ON
10.2.15 Current transformer failure (CT fail) N/A 3 ON
10.2.16 Supervision of the current in zero-sequence (I0 error) N/A 3 ON
10.2.17 Supervision of voltage in negative-sequence (V2 error) N/A 3 ON
10.2.18 Supervision of voltage in zero-sequence (VZ error) N/A 3 ON
10.2.19 Supervision of binary IO module#1 (BIO#1 error) Displayed 1 ON
10.2.20 Supervision of binary IO module#2 (BIO#2 error) Displayed 1 ON
10.2.21 Supervision of binary IO module#3 (BIO#3 error) Displayed 1 ON
10.2.22 Supervision of binary IO module#4 (BIO#4 error) Displayed 1 ON
10.2.23 Supervision of binary IO module#5 (BIO#5 error) Displayed 1 ON
10.2.24 Supervision of binary IO module#6 (BIO#6 error) Displayed 1 ON
10.2.25 Supervision of binary IO module#7 (BIO#7 error) Displayed 1 ON
10.2.26 Supervision of binary IO module#8 (BIO#8 error) Displayed 1 ON
10.2.27 Supervision of human machine interface (HMI error) Displayed 1 ON
10.2.28 Supervision of power supply module (Power error) N/A 3 ON
10.2.29 Supervision of data in PLC function (PLC data error) Displayed 3 ON
10.2.30 Voltage transformer failure (VT fail) N/A 3 ON
10.2.31 Supervision of circuit breaker contacts (CB1/CB2 fail) N/A 3 ON
10.2.32 Supervision of disconnector contacts (DS fail) N/A 3 ON

GRL200 (Soft 033 & 037)


- 1196 -
6F2S1914 (0.37)

Detailed Error
Sec.No. Supervision items(Screen message) Info. Lvl LED
10.2.33 Supervision of LAN status (LAN error) N/A 3 ON
10.2.34 Supervision of response for pinging (Ping error) Displayed 3 ON
10.2.35 Supervision of link redundant entity (LRE error) Displayed 1 ON
10.2.36 Supervision of data in 61850 settings (Commslv error) Displayed 3 ON
10.2.37 Supervision of GOOSE publishing (LAN(GOOSE)error) Displayed 3 ON
Aux. contacts monitoring (DPSY/DOPS/TOPS faulty or
10.2.38 Displayed 3 ON
undefined)

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.2-2 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Generic tasks except the below ✓ ✓
10.2.38 Aux. Contact monitoring NA ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 1197 -
6F2S1914 (0.37)

10.2.1 Mismatch between ROM and RAM data (ROM/RAM error)


The ROM and RAM on the CPU module are verified every two minutes; when the error is
found, an error message is displayed by the supervision function.

(i) Error level


The error level has been set at level 1 (Serious error) for the supervision, checking error on
the RAM and the ROM is carried out periodically. If the error is detected, the IED restarts its
operation automatically. The supervision function runs on the CPU module1.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-3 Error messages provided by the supervisor in CHK_ROMRAM


Message and level Meaning of the information
Mismatch between the RAM and ROM detected on the following
CP*_ (ROM/RAM) error module instructed with “CP*_” as follows:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-4 Detailed information in CHK_ROMRAM


Display Meaning of the detailed information
area Left column Right column
Top 00000001: Read error in ROM
ROM address
row 00000002: Mismatch between ROM and RAM

Middle
RAM address ROM value
row
Bottom
RAM value (No information displayed)
row

GRL200 (Soft 033 & 037)


- 1198 -
6F2S1914 (0.37)

10.2.2 Supervision of check-sum error (SUM error)


The check sum in the memory on the CPU module is verified every four minutes; when the
error is found the error message is displayed by the supervision function.

(i) Error level


The error level has been set at level 1 (Serious error) for the supervision, the check-sum error
on the memory is carried out periodically. If the error is detected, the IED restarts its operation
automatically. The supervision function runs on the CPU module1. Clearing the error message
is made promptly when the error is cleared.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-5 Error messages provided by the supervisor in CHK_SUM


Message and level Meaning of the information
Sum error in the memory detected on the following module:
CP*_ (SUM) error
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-6 Detailed information in Hexadecimal in CHK_SUM


Display Meaning of the detailed information
area Left column Right column
Top 00000001: Read error in ROM
Sum value calculated
row 00000002: Sum incorrect in ROM RAM

Middle Address information that read error occurs


Sum value pre-programmed
row in the ROM
Bottom
(No information displayed) (No information displayed)
row

GRL200 (Soft 033 & 037)


- 1199 -
6F2S1914 (0.37)

10.2.3 Supervision of RAM (RAM error)


The read-write operation on RAM circuit of the CPU module is verified at any time; when the
error is found an error message is displayed by the supervision function.

(i) Error level


The error level has been set at level 1 (Serious error1) for the supervision; checking errors on
the RAM is carried out at any time. If the error is detected, the IED restarts its operation
automatically. The supervision function runs on the CPU module1. Clearing the error message
is made promptly when the error is cleared.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-7 Error messages provided by the supervisor in CHK_RAM


Message and level Meaning of the information
Error detection in the RAM located on the following module
CP*_(RAM) error instructed with “CP*_” as follows:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-8 Detailed information in Hexadecimal in CHK_RAM


Display Meaning of the detailed information
area Left column Right column
Top
Read value Write value
row
Middle
Error address (No information displayed)
row
Bottom
(No information displayed) (No information displayed)
row

GRL200 (Soft 033 & 037)


- 1200 -
6F2S1914 (0.37)

10.2.4 Supervision of ECC on memory (ECC error)


The error-correcting code memory (ECC memory), in the CPU module, is verified at any time.

(i) Error level


The error level has been set at level 1 (Serious error1) for the supervision; checking error on
the ECC is carried out at any time. If the error is detected, the IED restarts its operation
automatically. The supervision function runs on the CPU module1. Clearing the error message
is made promptly when the error is solved.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-9 Error messages provided by the supervisor in CHK_ECC


Message and level Meaning of the information
Error in the ECC is detected on the following module instructed
CP*_ (ECC) error with “CP*_” as follows:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-10 Detailed information in Hexadecimal in CHK_ECC


Display Meaning of the detailed information
area Left column Right column
Top
err_cnt value Error address
row
Middle Address for rewriting failure occurred after
Number of detections of bit errors
row the correction of single bit error
ECC status
00000001: Completion of correction
Bottom Number of rewriting failure occurred 00000002: Failure of correction
row after the correction of single bit error 00000004: Detection of single error
00000008: Detection of several errors
00000010: Writing failure of data correction

GRL200 (Soft 033 & 037)


- 1201 -
6F2S1914 (0.37)

10.2.5 Supervision of MRAM (MRAM)


The error detection on the Magnetoresistive Random Access Memory (MRAM memory) of the
CPU module is verified every 1 second; when the error is found, an error message is displayed
by the supervision function.

(i) Error level


The error level has been set at level 1 (Serious error1) for the supervision; checking errors on
the ECC is carried out at any time. If the error is detected, the IED restarts its operation
automatically. The function supervise for the MRAM on the CPU module1. Clearing the error
message is made in 1 second when the error is cleared.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-11 Error messages provided by the supervisor in CHK_MRAM


Message and level Meaning of the information
Error detection in the MRAM located on the following module:
CP*_(MRAM) error
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-12 Detailed information in Hexadecimal in CHK_MRAM


Display Meaning of the detailed information
area Left column Right column
Top 00000001: Error detected with 0xaaaaaaaa
Address at error occurs
row 00000002: Error detected with 0x555555555
Middle
(No information is displayed) (No information is displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1202 -
6F2S1914 (0.37)

10.2.6 Supervision of FPGA (FPGA error)


Detecting the error in the FPGA is achieved when the CPU module detects fatal failures.

(i) Error level


The error level is set at level 1 (Serious error1) for the supervision; checking errors on the
FPGA is carried out at any time. If the error is detected, the IED begins to restart its operation
automatically. Clearing the error message is made promptly when the error is cleared.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-13 Error messages provided by the supervisor in CHK_FPGA


Message and level Meaning of the information
Problem detected in the FPGA on the following module
CP*_ (FPAG) error instructed with “CP*_” as follows:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-14 Detailed information in Hexadecimal in CHK_FPGA


Display Meaning of the detailed information
area Left column Right column
Top
00000004: FPGA mode 00000008: FPAG interruption process
row
Middle
(No information displayed) (No information displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1203 -
6F2S1914 (0.37)

10.2.7 Supervision of program codes (CPU error)


The program code in the ROM and RAM on the CPU module is verified every time; when the
error is found an error message is displayed by the supervision function.

(i) Error level


The error level has been set at level 1 (Serious error) for the supervision, detecting Program
errors on the RAM and the ROM are carried out every second. If the error is detected, the IED
restarts its operation automatically. The supervision function runs on the CPU module1.
Clearing the error message is made promptly when the error is cleared.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-15 Error messages provided by the supervisor in CHK_PROGRAM


Message and level Meaning of the information
Error detection in the RAM and ROM located on the following
CP*_(CPU) error module:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-16 Detailed information in Hexadecimal in CHK_PROGRAM


Display Meaning of the detailed information
area Left column Right column
00000000: Add error
Top 00000002: Sub error
00000004: Mul error Task number causing overflow
row 00000008: Div error
00010000: Detection of overflow in Task stack
Middle
Head address of overflowing task (No information displayed)
row
Bottom
(No information displayed) (No information displayed)
row

GRL200 (Soft 033 & 037)


- 1204 -
6F2S1914 (0.37)

10.2.8 Supervision of task operation (RUN error)


The task operations in the IED are monitored every two minutes. Error messages can be
screened when a task stops. The task operation is supervised every 15 minutes if the task is
idling.

(i) Error level


The error level has been set at level 1 (Serious error) unconditionally.

(ii) Error message


When detecting an error, the error message can be shown on the LCD and the LED is lit.

Table 10.2-17 Error messages provided by the supervisor in MNT_LOGIC


Message and level Meaning of the information
CP1M(RUN) error Detection of the stopped task in the IED
Error level Serious error (Level 1)

Table 10.2-18 Detailed information in Hexadecimal in MNT_LOGIC


Display Meaning of the detailed information
area Left column Right column
WW XX YY ZZ
Top 10000000: Supervision function itself
WW: FB index in SSP2(2)
20000000: Idle task (1)
row XX: FB index in SSP2(1)
40000000: Idle task (2)
YY: FB index in SSP1(2)
YY: FB index in SSP1(1)
WW XX YY ZZ WW XX YY ZZ
Middle WW: FB index in PCM(2) WW: FB index in 100MS(2)
row XX: FB index in PCM(1) XX: FB index in 100MS(1)
YY: FB index in SSP3(2) YY: FB index in 10MS
YY: FB index in SSP3(1) YY: FB index in 5MS
WW XX YY ZZ WW XX YY ZZ
Bottom WW: FB index in CONVSET WW: FB index in SUB4
row XX: FB index in NMT XX: FB index in SUB3
YY: FB index in 200MS(2) YY: FB index in SUB2
YY: FB index in 200MS(1) YY: FB index in SUB1

GRL200 (Soft 033 & 037)


- 1205 -
6F2S1914 (0.37)

10.2.9 Detecting non-maskable interrupt (NMI error)


The occurrences of non-maskable-interruptions (NMIs) on the CPU module are examined
every time; when the interruption is triggered, an interruption message is detected and
displayed.

(i) Error level


The error level has been set at level 1 (Serious error) for the supervision; detecting the
interruption carried out at any time. If the interruption is detected, the IED restarts its
operation automatically. The supervision function runs on the CPU module1. Clearing the error
message is made promptly when the error is cleared.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-19 Error messages provided by the supervisor in CHK_NMI


Message and level Meaning of the information
Interruptions occurs on the following module instructed with
CP*_(NMI) error “CP*_” as follows:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-20 Detailed information in Hexadecimal in NMI


Display Meaning of the detailed information
area Left column Right column
Top
NMI code LR register
row
Middle
SRR0 resister SPP1 resister
row
Bottom
Stack pointer FRSCR register
row

GRL200 (Soft 033 & 037)


- 1206 -
6F2S1914 (0.37)

10.2.10 Supervision of sampling period (SMP error)


The sampling error is verified at any time; when the error is found an error message is
displayed by the supervision function.

(i) Error level


The error level has been set at level 1 (Serious error1) for the supervision; sampling errors are
checked every seconds. If the error is detected, the IED restarts its operation automatically.
The supervision function runs on the CPU module1. Clearing the error message is made in a
second when the error is cleared.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-21 Error messages provided by the supervisor in CHK_SMP


Message and level Meaning of the information
Sampling error detected on the following module instructed with
CP*_ (SMP) error “CP*_” as follows:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-22 Detailed information in Hexadecimal in CHK_SMP


Display Meaning of the detailed information
area Left column Right column
Top
00000001: Occurrence of error Diff time
row
Middle
Current timing Pervious timing
row
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1207 -
6F2S1914 (0.37)

10.2.11 Supervision of setting data (Setting error)


The values of the Settings are checked every second; the error message is displayed when the
erroneous value is found.

(i) Error level


The error level has been set at level 1 (Serious error1) for the supervision; the detection is
carried out periodically. If the error is detected, the IED does not try to restart its operation
automatically. The function runs for the saved settings in the CPU module1. When the
erroneous setting is removed, the error messages will be cleared in a second.
1Note: The CPU module is discussed in Chapter Technical description: Signal processing
and communication module: Processing module.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-23 Error messages provided by the supervisor in CHK_SETTING


Message and level Meaning of the information
Setting error detected on the following module instructed with
CP*_ (Setting) error “CP*_” as follows:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-24 Detailed information expressed in Hexadecimal in CHK_SETTING


Display Meaning of the detailed information
area Left column Right column
Top 00000001: Failure exists in the common settings Offset address corresponding to
00000002: Failure exists in the group setting
row 00000004: Error data found in the setting table the failure in the common settings
Middle Offset address corresponding to the failure in Error information about the
row the group setting setting table
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1208 -
6F2S1914 (0.37)

10.2.12 Supervision of real-time clock (RTC error)


The state of the real time clock (RTC) is checked every five minutes; the error message is
displayed when the clock stops.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_RTC:LVl]; then, set On for the setting [CHK_RTC:Sw]. The
manufacturer sets five (5) minutes is set to detect the failure; it is reset within five minutes
when the clock starts to operate again.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-25 Error messages provided by the supervisor in CHK_RTC


Message and level Meaning of the information
Error detection is performed on the RTC on the following
CP*_(RTC) error module:
CP1M: CPU module
Error level Minor error (Level 3)

Table 10.2-26 Detailed information expressed in Hexadecimal in CHK_RTC


Display Meaning of the detailed information
area Left column Right column
Top 00000001: shows that the error exists in
Time in the second when the RTC stopped
row the RTC

Middle Time in the minute when the RTC


(No information displayed)
row stopped
Bottom
(No information displayed) (No information displayed)
row

GRL200 (Soft 033 & 037)


- 1209 -
6F2S1914 (0.37)

10.2.13 Supervision of analog input data on VCTs (AI ACC error)


It is possible to detect the failure of the analog to digital conversion in the VCT module†.
†Note:For more information about the VCT, see Chapter Technical description:
Transformer module for AC analog input. The function can operate for respective
VCTs.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error1). For example, the user
can program the level using setting [CHK_ACC1:LVl] when the VCT module at the VCT#12
slot should be supervised. Set On for the settings [CHK_ACC1:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset within a second when the failure is cleared.
1Note: When the error is detected, the entire operation of the IED is stopped forcibly.
2Note: The location of the VCT is discussed in Alpha-numerical references. See chapter
Technical description: IED case and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-27 Error messages provided by the supervisor in CHK_ACC


Message and level Meaning of the information
AI#x(ACC) error Detection of the conversion deterioration at VCx slot
Error level Serious error (Level 1)

Table 10.2-28 Detailed information in Hexadecimal in CHK_ACC


Display Meaning of the detailed information
area Left column Right column
00000001: P error
00000002: N error
Top 00000004: Neg error
Plus value / Minus value
row 00000010: P(H) error
00000020: N(H) error
00000040: Neg(H) error
Middle
Plus rev value / (none) Plus value / Minus value
row
Bottom
Plus rev value (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1210 -
6F2S1914 (0.37)

10.2.14 Abnormal currents flowing in CTs (CT error)


The CT supervision is to examine whether the three-phase currents are balanced and the
current in zero-sequence is minimum. It secures the operation of the CT circuits†. By
monitoring the currents flowing in the AC analog input circuits, it is also applicable to detect
the failure in the CT circuit. The failure is determined as Equation (10.2-1) is satisfied.

1. Max(|Ia |, |Ib |, |Ic |) − 4 × Min(|Ia |, |Ib |, |Ic |) ≥ k 0 (10.2-1)

where,
Max (|Ia|, |Ib|, |Ic|): The largest amplitude among Ia, Ib, and Ic
Min (|Ia|, |Ib|, |Ic|): The smallest amplitude among Ia, Ib, and Ic
k0: 20% of the rated current†
†Note:When the VCT has double three-phase-CT circuits, the CT supervision may be
required to operate for respective CT circuits. The rated current above the
equation is defined with VCT setting. For more information regarding the VCT,
see Chapter Technical description: Transformer module for AC analog input .
Settings are required to respective groups of the three-phase currents.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using settings [CHK_CT:LVl] and the others; then, set On for the setting [CHK_CT:Sw]
or whatever required. The time to detect can be programmed using [CHK_CT:Timer], etc.,
which can be set for 15 seconds as default. After the error is cleared, resetting will be performed
after the elapse of setting time.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-29 Error messages provided by the supervisor in CHK_CT
Message and level Meaning of the information
CT error the extraordinary current flowing located at the CT
CT2 error the extraordinary current flowing located at the other CT2
Error level Minor error (Level 3)

Table 10.2-30 Detailed information in Hexadecimal in CHK_CT


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1211 -
6F2S1914 (0.37)

10.2.15 Current transformer failure (CT fail)


Detecting the failure in the CT is achieved by the operation of the CT failure detection function
(CTF†). Thus, the failure signal in the CTF is transferred to the automatic supervision function
and it is grouped into the error level together with other error signals.
†Note:For more information about the CTF function, see Chapter Relay application: CT
failure detection.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_CTF:LVl]; then, set On for the setting [CHK_CTF:Sw]. The
manufacturer sets ten (10) seconds to detect the failure; it is reset instantly when the failure
is cleared

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-31 Error messages provided by the supervisor in CHK_CTF
Message and level Meaning of the information
CT fail Detection of the failure in the CT
Error level Minor error (Level 3)

Table 10.2-32 Detailed information in Hexadecimal in CHK_CTF


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1212 -
6F2S1914 (0.37)

10.2.16 Supervision of the current in zero-sequence (I0 error)


The zero-phase-sequence current entering to the input circuit is monitored; it is possible to
provide a high sensitivity to detect the failure using the residual circuit current. Equation
(10.2-2) is represented for the supervision:

|Ia + Ib + Ic − Ie |
1. ≥ 0.1 × Max(|Ia |, |Ib |, |Ic |) + k 0 (10.2-2)
3

where,
Ie Residual current
Max(|Ia|, |Ib|, |Ic|) The largest amplitude among Ia, Ib and Ic
k0: 5% of the rated current†

†Note:The rated current above the equation is defined with the setting of the VCT. For
more information regarding the VCT, see Chapter Technical description:
Transformer module for AC analog input.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using settings [CHK_IZ:LVl] and [CHK_IZ2:LVl]; then, set On for the settings
[CHK_IZ:Sw] and [CHK_IZ2:Sw]. The time to detect can be set using [CHK_IZ:Timer] and
[CHK_IZ2:Timer], each of which is set for 15 seconds as default. If the error is cleared, resetting
will be performed after the elapse of setting time.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-33 Error messages provided by the supervisor in CHK_IZ
Message and level Meaning of the information
I0 error Detection of flowing the zero-sequence current
Error level Minor error (Level 3)

Table 10.2-34 Detailed information in Hexadecimal in CHK_IZ


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1213 -
6F2S1914 (0.37)

10.2.17 Supervision of voltage in negative-sequence (V2 error)


Applying the voltage in negative-sequence is calculated regularly using three-phase voltages
measured in the IED. If Equation (10.2-3) is satisfied over 10 seconds, the supervision function
determines that a failure occurs in the input circuit.

The voltage in negative sequence can be used to detect a failure within the voltage input
circuit in high sensitivity. It facilitates the detection of the incorrect phase sequence if cables
are connected irregularly.

|Va + 𝑎2 Vb + aVc |
1. ≥ 6.35 (V) (10.2-3)
3

where,
a = Phase shift operator of 120

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_V2:LVl]; then, set On for the setting [CHK_V2:Sw]. The time for
the detection can be set using [CHK_V2:Timer], which is set for 15 seconds as default. After
the error is cleared, resetting will be performed after the elapse of setting time.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-35 Error messages provided by the supervisor in CHK_V2
Message and level Meaning of the information
V2 error Detection of the negative-sequence voltage
Error level Minor error (Level 3)

Table 10.2-36 Detailed information in Hexadecimal in CHK_V2


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1214 -
6F2S1914 (0.37)

10.2.18 Supervision of voltage in zero-sequence (VZ error)


Voltage in zero-sequence is automatically calculated using three-phase voltages measured in
the relay. If Equation (10.2-4) is made up, the supervision function can determine that a voltage
in zero-sequence is being applied erroneously.

|Va + Vb + Vc |
1. ≥ 6.35 (V) (10.2-4)
3

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_VZ:LVl]; then, set On for the setting [CHK_VZ:Sw]. The time for
the detection can be set using [CHK_VZ:Timer] , which is set for 15 seconds as default. After
the error is cleared, it is reset in the time that is the same as the setting time to the detection.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-37 Error messages provided by the supervisor in CHK_VZ
Message and level Meaning of the information
V0 error Detection of the zero-sequence voltage
Error level Minor error (Level 3)

Table 10.2-38 Detailed information in Hexadecimal in CHK_VZ


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1215 -
6F2S1914 (0.37)

10.2.19 Supervision of binary IO module#1 (BIO#1 error)


A supervision function is provided to detect the operation failure in the first binary IO modules
(BIO)†.
†Note:The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error1). For example, the user
can program the level using setting [CHK_BIO1:LVl] when the BIO module at the IO#12 slot
should be supervised; then, set On for the setting [CHK_BIO1:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset with in a second when the failure is cleared.
1Note: When the error is detected, the entire operation of the IED is stopped forcibly.
2Note: The location of the IO slot is discussed in Chapter Technical description: IED case
and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-39 Error messages provided by the supervisor in CHK_BIO


Message and level Meaning of the information
BIO#1 error Detection of the BIO failure at IO slot#1
Error level Serious error (Level 1)

Table 10.2-40 Detailed information in Hexadecimal in CHK_BIO


Display Meaning of the detailed information
area Left column Right column
Top 00000001: CRC error
00000002: Connection error Count number by the CRC error
row 00000004: Read back error
Middle
Count number by the connection error Count number by the read-back error
row
Bottom
(No message displayed) (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1216 -
6F2S1914 (0.37)

10.2.20 Supervision of binary IO module#2 (BIO#2 error)


A supervision function is provided to detect the operation failure in the second binary IO
modules (BIO)†.
†Note:The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error1). For example, the user
can program the level using setting [CHK_BIO2:LVl] when the BIO module at the IO#22 slot
should be supervised; then, set On for the setting [CHK_BIO2:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset within a second when the failure is cleared.
1Note: When the error is detected, the entire operation of the IED is stopped forcibly.
2Note: The location of the IO slot is discussed in Chapter Technical description: IED case
and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-41 Error messages provided by the supervisor in CHK_BIO


Message and level Meaning of the information
BIO#2 error Detection of the BIO failure at IO slot#2
Error level Serious error (Level 1)

Table 10.2-42 Detailed information in Hexadecimal in CHK_BIO


Display Meaning of the detailed information
area Left column Right column
Top 00000001: CRC error
00000002: Connection error Count number by the CRC error
row 00000004: Read back error
Middle
Count number by the connection error Count number by the read-back error
row
Bottom
(No message displayed) (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1217 -
6F2S1914 (0.37)

10.2.21 Supervision of binary IO module#3 (BIO#3 error)


A supervision function is provided to detect the operation failure in the third binary IO modules
(BIO)†.
†Note:The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error1). For example, the user
can program the level using setting [CHK_BIO3:LVl] when the BIO module at the IO#32 slot
should be supervised; then, set On for the setting [CHK_BIO3:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset with in a second when the failure is cleared.
1Note: when the error is detected the entire operation of the IED is stopped forcibly.
2Note: The location of the IO slot is discussed in Chapter Technical description: IED case
and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-43 Error messages provided by the supervisor in CHK_BIO


Message and level Meaning of the information
BIO#3 error Detection of the BIO failure at IO slot#3
Error level Serious error (Level 1)

Table 10.2-44 Detailed information in Hexadecimal in CHK_BIO


Display Meaning of the detailed information
area Left column Right column
Top 00000001: CRC error
00000002: Connection error Count number by the CRC error
row 00000004: Read back error
Middle
Count number by the connection error Count number by the read-back error
row
Bottom
(No message displayed) (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1218 -
6F2S1914 (0.37)

10.2.22 Supervision of binary IO module#4 (BIO#4 error)


A supervision function is provided to detect the operation failure in the forth binary IO modules
(BIO)†.
†Note:The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.

(i) Error level


Generally, the error level has been set at level 1 (Serious error1), as default. For example, the
user can program the level using setting [CHK_BIO4:LVl] when the BIO module at the IO#42
slot should be supervised; then, set On for the setting [CHK_BIO4:Sw]. The manufacture sets
one (1) second to detect the failure; it is reset in a second when the failure is cleared.
1Note: The entire operation of the IED is stopped forcibly when the error is detected.
2Note: The location of the IO slot is discussed in Chapter Technical description: IED case
and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-45 Error messages provided by the supervisor in CHK_BIO


Message and level Meaning of the information
BIO#4 error Detection of the BIO failure at IO slot#4
Error level Serious error (Level 1)

Table 10.2-46 Detailed information in Hexadecimal in CHK_BIO


Display Meaning of the detailed information
area Left column Right column
Top 00000001: CRC error
00000002: Connection error Count number by the CRC error
row 00000004: Read back error
Middle
Count number by the connection error Count number by the read-back error
row
Bottom
(No message displayed) (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1219 -
6F2S1914 (0.37)

10.2.23 Supervision of binary IO module#5 (BIO#5 error)


A supervision function is provided to detect the operation failure in the fifth binary IO modules
(BIO)†.
†Note:The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error1). For example, the user
can program the level using setting [CHK_BIO5:LVl] when the BIO module at the IO#52 slot
should be supervised; then, set On for the setting [CHK_BIO5:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset with in a second when the failure is cleared.
1Note: When the error is detected, the entire operation of the IED is stopped forcibly.
2Note: The location of the IO slot is discussed in Chapter Technical description: IED case
and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-47 Error messages provided by the supervisor in CHK_BIO


Message and level Meaning of the information
BIO#5 error Detection of the BIO failure at IO slot#5
Error level Serious error (Level 1)

Table 10.2-48 Detailed information in Hexadecimal in CHK_BIO


Display Meaning of the detailed information
area Left column Right column
Top 00000001: CRC error
00000002: Connection error Count number by the CRC error
row 00000004: Read back error
Middle
Count number by the connection error Count number by the read-back error
row
Bottom
(No message displayed) (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1220 -
6F2S1914 (0.37)

10.2.24 Supervision of binary IO module#6 (BIO#6 error)


A supervision function is provided to detect the operation failure in the sixth binary IO modules
(BIO)†.
†Note:The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error1). For example, the user
can program the level using setting [CHK_BIO6:LVl] when the BIO module at the IO#62 slot
should be supervised; then, set On for the setting [CHK_BIO6:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset with in a second when the failure is cleared.
1Note: when the error is detected the entire operation of the IED is stopped forcibly.
2Note: The location of the IO slot is discussed in Chapter Technical description: IED case
and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-49 Error messages provided by the supervisor in CHK_BIO


Message and level Meaning of the information
BIO#6 error Detection of the BIO failure at IO slot#6
Error level Serious error (Level 1)

Table 10.2-50 Detailed information in Hexadecimal in CHK_BIO


Display Meaning of the detailed information
area Left column Right column
Top 00000001: CRC error
00000002: Connection error Count number by the CRC error
row 00000004: Read back error
Middle
Count number by the connection error Count number by the read-back error
row
Bottom
(No message displayed) (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1221 -
6F2S1914 (0.37)

10.2.25 Supervision of binary IO module#7 (BIO#7 error)


A supervision function is provided to detect the operation failure in the seventh binary IO
modules (BIO)†.
†Note:The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error1). For example, the user
can program the level using setting [CHK_BIO7:LVl] when the BIO module at the IO#72 slot
should be supervised; then, set On for the setting [CHK_BIO7:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset with in a second when the failure is cleared.
1Note: When the error is detected, the entire operation of the IED is stopped forcibly.
2Note: The location of the IO slot is discussed in Chapter Technical description: IED case
and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-51 Error messages provided by the supervisor in CHK_BIO


Message and level Meaning of the information
BIO#7 error Detection of the BIO failure at IO slot#7
Error level Serious error (Level 1)

Table 10.2-52 Detailed information in Hexadecimal in CHK_BIO


Display Meaning of the detailed information
area Left column Right column
Top 00000001: CRC error
00000002: Connection error Count number by the CRC error
row 00000004: Read back error
Middle
Count number by the connection error Count number by the read-back error
row
Bottom
(No message displayed) (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1222 -
6F2S1914 (0.37)

10.2.26 Supervision of binary IO module#8 (BIO#8 error)


A supervision function is provided, to detect the operation failure in the eighth binary IO
modules (BIO)†.
†Note:The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error1). For example, the user
can program the level using setting [CHK_BIO8:LVl] when the BIO module at the IO#82 slot
should be supervised; then, set On for the setting [CHK_BIO8:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset with in a second when the failure is cleared.
1Note: When the error is detected, the entire operation of the IED is stopped forcibly.
2Note: The location of the IO slot is discussed in Chapter Technical description: IED case
and module slot.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-53 Error messages provided by the supervisor in CHK_BIO


Message and level Meaning of the information
BIO#8 error Detection of the BIO failure at IO slot#8
Error level Serious error (Level 1)

Table 10.2-54 Detailed information in Hexadecimal in CHK_BIO


Display Meaning of the detailed information
area Left column Right column
Top 00000001: CRC error
00000002: Connection error Count number by the CRC error
row 00000004: Read back error
Middle
Count number by the connection error Count number by the read-back error
row
Bottom
(No message displayed) (No message displayed)
row

GRL200 (Soft 033 & 037)


- 1223 -
6F2S1914 (0.37)

10.2.27 Supervision of human machine interface (HMI error)


Supervising the failure in the human machine interface (HMI) is provided.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error1). However, the user can
program the level using setting [CHK_HMI:LVl]; then, set On for the setting [CHK_HMI:Sw].
The manufacturer sets ten (10) seconds to detect the failure; it is reset within 10 seconds when
the failure is cleared.
2Note: The functions of the HMI is discussed in Chapter Technical description: Human
machine interface.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 10.2-55 Error messages provided by the supervisor in CHK_HMI
Message and level Meaning of the information
HMI error Detection of the HMI failure
Error level Minor error (Level 3)

Table 10.2-56 Detailed information in Hexadecimal in CHK_HMI


Display Meaning of the detailed information
area Left column Right column
Top 00000001: Timeout of LCD communication Culminated value for the
00000002: Format error in LCD communication
row 00000004: Communication error in MIMIC LCD timeout
Middle Counter of the MIMIC
Counted value for the format error
row communication
Bottom (No information is
(No information is displayed)
row displayed)

GRL200 (Soft 033 & 037)


- 1224 -
6F2S1914 (0.37)

10.2.28 Supervision of power supply module (Power error)


A power error is issued when the DC voltage generated in the power supply module (PWS†) is
less than a threshold. The user can select either 85V or 170V thresholds for issuing the power
error; it is determined by inserting a shut connector (JP4) on the PWS.
†Note:For more information about the PWS, see Chapter Technical description, Power
supply module. When the AC supply—however, the manufacture does not
guarantee the operation in the AC power—is connected with the PWS module, the
user shall set Off for the setting [CHK_POWER:Sw] (that is, the supervision
function concerning to the PWS module are stopped). Remember that the state of
the binary input circuit (BI) will be latched when the Power error occurs anytime.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), as default, but the user
can program the level using setting [CHK_POWER:LVl]; then, set On for the setting
[CHK_POWER:Sw]. The manufacturer sets one (1) second to detect the failure; it is reset with
in a second when the failure is cleared.

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 10.2-57 Error messages provided by the supervisor in CHK_POWER
Message and level Meaning of the information
Power error Detection of the failure in the PWS
Error level Minor error (Level 3)

Table 10.2-58 Detailed information in Hexadecimal in CHK_POWER


Display Meaning of the detailed information
area Left column Right column
Top
00000001: PWS failure (No information displayed)
row
Middle
(No information displayed) (No information displayed)
row
Bottom
(No information displayed) (No information displayed)
row

GRL200 (Soft 033 & 037)


- 1225 -
6F2S1914 (0.37)

10.2.29 Supervision of data in PLC function (PLC data error)


Error in the PLC function is detected because the data coded by PLC editor† has an error.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_PLC_DAT:LVl]; then, set On for the setting [CHK_PLC_DAT:Sw].
The manufacturer sets one-hundred-twenty (120) second to detect the failure; it is reset within
60 seconds when the failure is cleared.

(ii) Error message


When detecting an error, an error message will be shown on the LCD screen and an LED is lit.

Table 10.2-59 Error messages provided by the supervisor in CHK_PLC_DAT


Message and level Meaning of the information
PLC data error Detection of the failure in the PLC function
Error level Minor error (Level 3)

Table 10.2-60 Detailed information in Hexadecimal in CHK_ PLC_DAT


Display Meaning of the detailed information
area Left column Right column
00000001 No PLC data exists in the 00000001 Watch dog error
IED. 00000002 CPU load exceeded
00000002 Error in input Data 00000003 File error
00000004 Error in output Data 00000004 Test info string error
00000008 Time over in computation 00000010 PLC stopped
00000010 PLC stopped by the tool 00000011 No PLC stop Identifier
00010000 Watch dog error 00000012 Output string is too short
00020000 CPU load exceeded 00000013 Input string is too short
00040000 File error 00000014 Invalid input parameter
Top 00080000 Divided by zero 00000015 2nd is of the output string
00100000 Array index out of range 00000016 Invalid string comparison
row 00200000 Stack over flow 00000017 Unsupported type in conversion
00400000 System error 00000018 Error in the format string
00800000 Working memory over flow 00000019 Invalid input for format string
01000000 Internal error 0000001A Error during string conversion
0000001B Mismatch in Flash memory
000003E8 Division by zero
000003E9 Array index out of range
000003EA Stack over flow
000003EB System error
000003EC Working memory over flow
Middle
(No information) (No information)
row
Bottom
(No information) (No information)
row
†See Chapter PLC editing in PLC editor (6F2S1904) separately.

GRL200 (Soft 033 & 037)


- 1226 -
6F2S1914 (0.37)

10.2.30 Voltage transformer failure (VT fail)


Detecting the failure in the VT is achieved by the operation of the VT failure detection function
(VTF†). Thus, the failure signal in the VTF is transferred to the automatic supervision function
and it is grouped into the error level together with other error signals.
†Note:For more information about the VTF function, see Chapter Relay application: VT
failure detection.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_VTF:LVl]; then, set On for the setting [CHK_VTF:Sw]. The
manufacturer sets ten (10) seconds to detect the failure; it is reset instantly when the failure
is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-61 Error messages provided by the supervisor in CHK_VTF
Message and level Meaning of the information
VT fail Detection of the failure in the VT
Error level Minor error (Level 3)

Table 10.2-62 Detailed information in Hexadecimal in CHK_VTF


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1227 -
6F2S1914 (0.37)

10.2.31 Supervision of circuit breaker contacts (CB1/CB2 fail)


Detecting the operation failure in the CB is achieved by the operation of the protection common
function (PROT_COMM†). Thus, the failure signal in the PROT_COMM is transferred to the
automatic supervision function and it is grouped into the error level together with other error
signals.
†Note:For more information about the PROT_COMM function, see Chapter Relay
application: Protection common. When the IED operates for the 1.5CB
arrangements, the detection is carried out for two CBs.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), as default, but the user
can program the level using settings [CHK_CB1:LVl], etc.; then, set On for the setting
[CHK_CB1:Sw] or whatever required. The time to detect can be set using [TCBSV], which is
provided in the PROT_COMM function. If the error is cleared, it is reset instantly.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-63 Error messages provided by the supervisor in CHK_CB
Message and level Meaning of the information
CB1 fail Detection of the failure in the CB
CB2 fail Detection of the failure of the other CB in the 1.5CB system
Error level Minor error (Level 3)

Table 10.2-64 Detailed information in Hexadecimal in CHK_CB


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1228 -
6F2S1914 (0.37)

10.2.32 Supervision of disconnector contacts (DS fail)


Detecting the operation failure in the disconnector (DS) is achieved by the operation of the
protection common function (PROT_COMM†). Thus, the failure signal in the PROT_COMM is
transferred to the automatic supervision function and it is grouped into the error level together
with other error signals.
†Note:For more information about the PROT_COMM function, see Chapter Relay
application: Protection common.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using settings [CHK_DS:LVl]; then, set On for the setting [CHK_DS:Sw]. The time for
the detection can be set using [TDSSV], which is provided in the PROT_COMM function. It is
reset instantly when the error is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-65 Error messages provided by the supervisor in CHK_DS
Message and level Meaning of the information
DS fail Detection of the failure in the DS
Error level Minor error (Level 3)

Table 10.2-66 Detailed information in Hexadecimal in CHK_DS


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1229 -
6F2S1914 (0.37)

10.2.33 Supervision of LAN status (LAN error)


Network communication module is monitored every 60 seconds; the error message is screened
if the one does not operate correctly.
†Note:For more information about the modules with regard to the LAN network, see
Chapter Communication Protocol: LAN communication or Chapter Technical
description: Signal processing and communication module.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using settings [CHK_LAN*:LVl]; then, set On for the settings [CHK_LAN*:Sw].

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 10.2-67 Error messages provided by the supervisor in CHK_LAN
Message and level Meaning of the information
Detection of the failure on the module instructed with
“LAN*” as follows:
LAN* error
LAN1: Communication module (COM#1 at C11)
LAN2: Communication module (COM#2 at C12)
Error level Serious error (Level 1)

Table 10.2-68 Detailed information in Hexadecimal in CHK_LAN


Display Meaning of the detailed information
area Left column Right column
00000001: LAN does not exist
00000010: MAC address error
Top 00000100: Connection failure in 10Mbps
00001000: Double IP addresses First MAC address in four Octets
row 00010000: Internal error occurs
00100000: LAN driver error
01000000: Descriptor error
XXXX YYYY
Middle Number of responses from double IP
row addresses YYYY: Counter of full receptions
XXXX: No. of write-error in reception
When description error occurs:
00000001: Sending error
00000008: Tx error at the head address
XXXX YYYY
Bottom 00000010: Reception error
00000020: Rx error of size definition
row YYYY: Counter for reception halted
00000040: Rx error at the head address
XXXX: Counter for sending halted
When driver error occurs:
State of interruption.

GRL200 (Soft 033 & 037)


- 1230 -
6F2S1914 (0.37)

10.2.34 Supervision of response for pinging (Ping error)


Communication error on the LAN† is detected by pinging for the addresses instructed.
†Note:For more information about the LAN, see Chapter Communication Protocol: LAN
communication. For the information about the LAN hardware, see Chapter
Technical description: Signal processing and communication module. When two
network modules operates, the message is provided for the both.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using settings [CHK_PING*:LVl]; then, set On for the settings [CHK_PING*:Sw]. The
manufacturer sets one-hundred (100) second to detect the failure; it is reset in 20 seconds when
the failure is cleared.

(ii) Error message


When detecting errors, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-69 Error messages provided by the supervisor in CHK_PING


Message and level Meaning of the information
Detection of the pinging failure instructed with “LAN*” as
follows:
LAN* (ping) error
LAN1 (ping): Communication module (COM#1 at C11)
LAN2 (ping): Communication module (COM#2 at C12)
Error level Minor error (Level 3)

Table 10.2-70 Detailed information in Hexadecimal in CHK_PING


Display Meaning of the detailed information
area Left column Right column
Top
Destination address for pinging (No information is displayed)
row
Middle
(No information is displayed) (No information is displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1231 -
6F2S1914 (0.37)

10.2.35 Supervision of link redundant entity (LRE error)


Operation of the LRE is checked and the error message is screened when the LRE does not
operate correctly or wrong data is written in the FPGA.
†Note:For more information about the LRE, see Chapter Communication Protocol: LAN
communication.

(i) Error level


Generally, the default error level has been set at level 1 (Serious error), but the user can
program the level using settings [CHK_LRE:LVl]; then, set On for the settings [CHK_LRE:Sw].

(ii) Error message


When detecting an error, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-71 Error messages provided by the supervisor in CHK_LRE


Message and level Meaning of the information
Detection of the failure in the LRE instructed with “CP*_” as
CP*_(LRE) error follows:
CP1M: CPU module
Error level Serious error (Level 1)

Table 10.2-72 Detailed information in Hexadecimal in CHK_LRE


Display Meaning of the detailed information
area Left column Right column
Top 00000001: Type error in FPGA
00000002: Port state error in redundant module FPGA type number in CPM2
row 00000004: Mode error in redundant module
Middle
(No information is displayed) (No information is displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1232 -
6F2S1914 (0.37)

10.2.36 Supervision of data in 61850 settings (Commslv error)


The error† is detected when an inconsistency is found in the 61850 settings. Note that the
information for the error may vary on the communication protocol.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_CMLV:LVl]; then, set On for the setting [CHK_CMLV:Sw]. The
error can be detected in two minutes after the IED is turned on.

(ii) Error message


When detecting errors, an error message can be shown on the LCD screen and an LED is lit.
Table 10.2-73 Error messages provided by the supervisor in CHK_CMLV
Message and level Meaning of the information
Data(cmmslv) error Detection of the failure in the settings
Error level Minor error (Level 3)
Table 10.2-74 Detailed information in Hexadecimal in CHK_CMLV
Display Meaning of the detailed information
area Left column Right column
Displaying the Data ID relating to
Top row Error reasons code
erroneous mapping
Displaying the Data ID relating to
Middle row Additional information
erroneous mapping
Bottom
Additional information Additional information
row
†Note:In the IEC 61850 communication protocol, LN, DO and DA names are displayed in
ASCII characteristic codes, which instruct wrong mappings performed. In the
below sample, for example, the user can get the error mapping of “GGIO2$STtVal”
when ASCII codes are solved in eight-characters and four-characters.
Top row and left colum: [4747494F] Top row and right column: [32245354]
Middle row: [7456616C]
47 47 49 4F 32 24 53 54 74 56 61 6C = “GGIO2$STtVal”
Table 10.2-75 Error reasons detected by the supervisor in CHK_CMLV
Reasons of errors
Function error found Erroneous index being used in the data for the protocol stack
designated
Failure occurred on going through the selection process with Time out
regard to the protocol
Failure occurred on the initialization in the protocol process Going through the process
Failure for opening file Found invalid arguments
Failure of access Found the data type not being supported
No space left in the buffer Failure of the acquisition of the authority right
No space left in the buffer provided for the SSP mapping Failure occurred on the setting process
Failure of memory allocation in the memory dynamically Failure of the event registration
Check sum errors No event occurred
Not unfound about the searching object Restarting
Failure of the defining of data type Communication error

GRL200 (Soft 033 & 037)


- 1233 -
6F2S1914 (0.37)

10.2.37 Supervision of GOOSE publishing (LAN(GOOSE)error)


Publishing error in the IEC 61850 communication† is detected when a GOOSE message is not
received.
†Note:For more information about GOOSE, see Chapter Communication protocol: IEC
61850 communication.

(i) Error level


Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_GOOSERCV:LVl]; then, set On for the setting
[CHK_GOOSERCV:Sw]. Detecting the error is expressed in five-minutes when the IED detects
no reception of the GOOSE. When the GOOSE is started to receive, it is reset in one-minute.

(ii) Error message


When detecting errors, an error message can be shown on the LCD screen and an LED is lit.

Table 10.2-76 Error messages provided by the supervisor in CHK_GOOSERCV


Message and level Meaning of the information
LAN(GOOSE) error Detection of the failure in GOOSE
Error level Minor error (Level 3)

Table 10.2-77 Detailed information in Hexadecimal in CHK_GOOSERCV


Display Meaning of the detailed information
area Left column Right column
Top Receipt state regarding to the GOOSE Receipt state regarding to the GOOSE
row subscribe information#1† subscribe information#2†
Middle Receipt state regarding to the GOOSE Receipt state regarding to the GOOSE
row subscribe information#3† subscribe information#4†
Bottom Receipt state regarding to the GOOSE Receipt state regarding to the GOOSE
row subscribe information#5† subscribe information#6†
†Note:“c000” is shown when no reception.

GRL200 (Soft 033 & 037)


- 1234 -
6F2S1914 (0.37)

10.2.38 Aux. contacts monitoring (DPSY/DOPS/TOPS faulty or undefined)


When signals of an external device (i.e., a circuit breaker) are provided in a pair of auxiliary
contacts1, the signals may be grouped into four states: Open, Fault, Undefined, and Closed.
This is because, two different kinds of N/C and N/O contacts operates in the other way around;
hence, there is a possibility that the generated signal may have an incorrect condition (Faulty)
or an intermediate condition (Undefined). When receiving the signal by the BI circuit1 of the
IED, a preliminary logic2 starts to group the receiving signals into Open and the other states.
Consequently, the control function is able to operate securely not being affected by improper
signals (i.e., Fault, Undefined). In the supervision function, the received signals are sorted
with the definition of the error levels programmed by the manufacture, but the user can
program the sorting procedure arbitrarily using the settings in CHK functions
(CHK_DPOSSYN, CHK_DPOS, and CHK_TPOS).
1Note: The BI circuit is discussed in the Binary IO module. For more information, see
Chapter Technical description.
2Note: The preliminary logic is designed to acquire a signal coming from the BI circuit
and to sort the signal into the ‘Open’, ‘Fault’, ‘Undefined’, and ‘Closed’ states. The
preliminary logic is furnished in every control functions. For example, we can find
the logic in section “Setup for BIO module” in Chapter Control and monitoring
application: Double position controller with synchronizing-checking.

(i) Correspondence between CHK functions and applications


There are a number of CHK operations in the automatic supervision function; hence, the user
is required so that the control applications correspond with the CHK functions, as shown in
Table 10.2-78.
Table 10.2-78 Correspondence table for the control applications
CHK functions Control applications
Function ID Names Function ID Names
DPSY01 function†
229001 CHK_DPOSSYN 511001
DPSY02 function†
DPOS01 function
DPOS02 function
229101 CHK_DPOS 512001 DPOS03 function
….
DPOS72 function
TPOS01 function
TPOS02 function
229201 CHK_TPOS 513001
….
TPOS24 function
†Note:To detect the “Faulty” and “Undefined” states in the DPSY01 function, the user
can adjust the time for supervision using settings [DPSY01-FLTTIM] and
[DPSY01-UDFTIM], each of which is accommodated in the DPSY1 function. Then,
set [DPSY01-FLTEN] On for the operation. Likewise, settings are available in the
DPSY02 function.

GRL200 (Soft 033 & 037)


- 1235 -
6F2S1914 (0.37)

(ii) Error level


For the operation, the user can set the error level when the function detects the error
concerning the operation. Generally, the default error level has been set at level 3 (Minor error)
and level 4 (Alarm) for the faulty state and the undefined state, respectively. However, the user
can program them using settings. For example, when the user wish to program the fault and
undefined states in the DPSY01 function, use the settings [CHK_DPOSSYN1:FLvl] and
[CHK_DPOSSYN1:ULvl], respectively; then, set On for the setting [CHK_DPOSSYN1:Sw].

(iii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-79 Error messages provided by the supervisor in CHK_PALLET
Message and level Meaning of the information
XXXX* undefine ‘Undefine” detected at * of the XXXX function
Minor error (Level 3) for ‘Faulty’; Alarm (Level 4) for
Error level
‘Undefine’

Table 10.2-80 Detailed information in Hexadecimal in CHK_PALLET


Display Meaning of the detailed information
area Left column Right column
Top 00000001: Detecting ‘Alarm’
(No information is displayed)
row 00000002: Detecting ‘Minor error’

Middle
(No information is displayed) (No information is displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1236 -
6F2S1914 (0.37)

10.2.39 Setting
Setting of CHK_SAMPLING (Function ID: 220701)
Setting item Range Contents Default setting value Notes

CHK_SPSYNC1:Sw Off / On Enable switch On


--- / Serious error / Serious error(Comm) /
CHK_ SPSYNC1:Lvl Error level Serious error(Comm)
Minor error / Alarm/ Warning
CHK_SPSYNC2:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_ SPSYNC2:Lvl Error level Serious error(Comm)
Minor error / Alarm/ Warning

Setting of CHK_ACC (Function ID: 220E01)


Note
Setting item Range Contents Default setting value
s

CHK_ACC1:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ ACC 1:Lvl Error level Serious error
Minor error / Alarm/ Warning

Setting of CHK_BIO (Function ID: 221101 to 221108)


Setting item Range Contents Default setting value Notes

CHK_BIO1:Sw Off / On Enable switch for BIO#1 On

--- / Serious error / Serious error(Comm) /


CHK_ BIO 1:Lvl Error level at BIO#1 Serious error
Minor error / Alarm/ Warning

… … … …

CHK_ BIO8:Sw Off / On Enable switch for BIO#8 On

--- / Serious error / Serious error(Comm) /


CHK_ BIO8:Lvl Error level at BIO#1 Serious error
Minor error / Alarm/ Warning

Setting of CHK_HMI (Function ID: 221301)


Setting item Range Contents Default setting value Notes

CHK_HMI:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ HMI:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_RTC (Function ID: 221701)


Setting item Range Contents Default setting value Notes

CHK_RTC:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_RTC:Lvl Error level Minor error
Minor error / Alarm / Warning

GRL200 (Soft 033 & 037)


- 1237 -
6F2S1914 (0.37)

Setting of CHK_CT (Function ID: 221801 and 221802)


Note
Setting item Range Contents Default setting value
s

CHK_CT1:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_CT1:Lvl Error level Serious error
Minor error / Alarm/ Warning

CHK_CT1:Timer 10 – 60 seconds Checking timer 15 seconds

CHK_CT2:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_CT2:Lvl Error level Serious error
Minor error / Alarm/ Warning

CHK_CT2:Timer 10 – 60 seconds Checking timer 15 seconds

Setting of CHK_IZ (Function ID: 221901 and 221902)


Note
Setting item Range Contents Default setting value
s

CHK_IZ1:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_IZ1:Lvl Error level Minor error
Minor error / Alarm / Warning

CHK_IZ1:Timer 10s – 60s Checking timer 15s

CHK_IZ2:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_IZ2:Lvl Error level Minor error
Minor error / Alarm / Warning

CHK_IZ2:Timer 10s – 60s Checking timer 15s

Setting of CHK_V2 (Function ID: 221A01)


Note
Setting item Range Contents Default setting value
s

CHK_V2:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_V2:Lvl Error level Minor error
Minor error / Alarm / Warning

CHK_V2:Timer 10s – 60s Checking timer 15s

Setting of CHK_VZ (Function ID: 221B01)


Note
Setting item Range Contents Default setting value
s

CHK_VZ:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_VZ:Lvl Error level Minor error
Minor error / Alarm / Warning

CHK_VZ:Timer 10s – 60s Checking timer 15s

GRL200 (Soft 033 & 037)


- 1238 -
6F2S1914 (0.37)

Setting of CHK_VTF (Function ID: 221C01)


Note
Setting item Range Contents Default setting value
s

CHK_VTF:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ VTF:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_POWER (Function ID: 222D01)


Setting item Range Contents Default setting value Notes

CHK_POWER:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_POWER:Lvl Error level Minor error
Minor error / Alarm / Warning

Setting of CHK_CTF (Function ID: 221E01)


Note
Setting item Range Contents Default setting value
s

CHK_CTF:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ CTF:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_CB (Function ID: 222001 and 222002)


Setting item Range Contents Default setting value Notes

CHK_CB1:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ CB1 1:Lvl Error level Minor error
Minor error / Alarm/ Warning

CHK_ CB2:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ CB2:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_DS (Function ID: 221101)


Note
Setting item Range Contents Default setting value
s

CHK_DS:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_DS:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_PLC_DAT (Function PLC_DAT: 223202)


Setting item Range Contents Default setting value Notes

CHK_PLC_DAT:Sw Off / On Enable switch On

GRL200 (Soft 033 & 037)


- 1239 -
6F2S1914 (0.37)

Setting of CHK_PLC_DAT (Function PLC_DAT: 223202)


Setting item Range Contents Default setting value Notes

--- / Serious error / Serious error(Comm) /


CHK_PLC_DAT:Lvl Error level Minor error
Minor error / Alarm / Warning

Setting of CHK_PING (Function ID: 223601 and 223602)


Setting item Range Contents Default setting value Notes

CHK_PING1:Sw Off / On Enable switch Off

--- / Serious error / Serious error(Comm) /


CHK_PING1:Lvl Error level Minor error
Minor error / Alarm / Warning

PING_IP_ADRS 0 - 255 192

PING_IP_ADRS2 0 - 255 168


Ping target IP address
PING_IP_ADRS3 0 - 255 1

PING_IP_ADRS4 0 - 255 1

CHK_PING2:Sw Off / On Enable switch Off

--- / Serious error / Serious error(Comm) /


CHK_PING2:Lvl Error level Minor error
Minor error / Alarm / Warning

PING_IP_ADRS 0 - 255 192

PING_IP_ADRS2 0 - 255 168


Ping target IP address
PING_IP_ADRS3 0 - 255 1

PING_IP_ADRS4 0 - 255 1

Setting of CHK_CMLV (Function ID: 224001)


Setting item Range Contents Default setting value Notes

CHK_CMLV_DAT:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_CMLV_DAT:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_GOOSERCV (Function ID: 223501)


Setting item Range Contents Default setting value Notes

CHK_GOOSERCV:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_GOOSERCV:Lvl Error level Minor error
Minor error / Alarm / Warning

GRL200 (Soft 033 & 037)


- 1240 -
6F2S1914 (0.37)

Setting of CHK_DPOSSYN (Function ID: 229001)


Default setting
Setting item Range Contents Notes
value
CHK_DPOSSYN1:Sw Off / On Enable switch to supervising the DPSY01 On
--- / Serious error / Serious error(Comm) /
CHK_DPOSSYN1:ULvl Error level for undefined error at DPSY01 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_DPOSSYN1:FLvl Error level for faulty error at DPSY01 Minor error
Minor error / Alarm / Warning
CHK_DPOSSYN2:Sw Off / On Enable switch to supervising the DPSY02 On
--- / Serious error / Serious error(Comm) /
CHK_DPOSSYN2:ULvl Error level for undefined error at DPSY02 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_DPOSSYN2:FLvl Error level for faulty error at DPSY02 Minor error
Minor error / Alarm / Warning
CHK_DPOSSYN3:Sw Off / On Enable switch to supervising the DPSY03 On
--- / Serious error / Serious error(Comm) /
CHK_DPOSSYN3:ULvl Error level for undefined error at DPSY03 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_DPOSSYN3:FLvl Error level for faulty error at DPSY03 Minor error
Minor error / Alarm / Warning

Setting of CHK_DPOS (Function ID: 229101)


Default setting
Setting item Range Contents Notes
value
CHK_DPOS1:Sw Off / On Enable switch to supervising the DPOS01 On
--- / Serious error / Serious error(Comm) /
CHK_DPOS1:ULvl Error level for undefined error at DPOS01 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_DPOS1:FLvl Error level for faulty error at DPOS01 Minor error
Minor error / Alarm / Warning
CHK_DPOS2:Sw Off / On Enable switch to supervising the DPOS02 On
--- / Serious error / Serious error(Comm) /
CHK_DPOS2:ULvl Error level for undefined error at DPOS02 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_DPOS2:FLvl Error level for faulty error at DPOS02 Minor error
Minor error / Alarm / Warning
CHK_DPOS3:Sw Off / On Enable switch to supervising the DPOS03 On
--- / Serious error / Serious error(Comm) /
CHK_DPOS3:ULvl Error level for undefined error at DPOS03 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_DPOS3:FLvl Error level for faulty error at DPOS03 Minor error
Minor error / Alarm / Warning
… …. … ….
CHK_DPOS72:Sw Off / On Enable switch to supervising the DPOS72 On
--- / Serious error / Serious error(Comm) /
CHK_DPOS72:ULvl Error level for undefined error at DPOS72 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_DPOS72:FLvl Error level for faulty error at DPOS72 Minor error
Minor error / Alarm / Warning

Setting of CHK_TPOS (Function ID: 229201)


Default setting
Setting item Range Contents Notes
value
CHK_TPOS1:Sw Off / On Enable switch to supervising the TPOS01 On
--- / Serious error / Serious error(Comm) /
CHK_TPOS1:ULvl Error level for undefined error at TPOS01 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_TPOS1:FLvl Error level for faulty error at TPOS01 Minor error
Minor error / Alarm / Warning
CHK_TPOS2:Sw Off / On Enable switch to supervising the TPOS02 On
--- / Serious error / Serious error(Comm) /
CHK_TPOS2:ULvl Error level for undefined error at TPOS02 Alarm
Minor error / Alarm / Warning

GRL200 (Soft 033 & 037)


- 1241 -
6F2S1914 (0.37)

Setting of CHK_TPOS (Function ID: 229201)


Default setting
Setting item Range Contents Notes
value
--- / Serious error / Serious error(Comm) /
CHK_TPOS2:FLvl Error level for faulty error at TPOS02 Minor error
Minor error / Alarm / Warning
CHK_TPOS3:Sw Off / On Enable switch to supervising the TPOS03 On
--- / Serious error / Serious error(Comm) /
CHK_TPOS3:ULvl Error level for undefined error at TPOS03 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_TPOS3:FLvl Error level for faulty error at TPOS03 Minor error
Minor error / Alarm / Warning
… …. … ….
CHK_TPOS24:Sw Off / On Enable switch to supervising the TPOS24 On
--- / Serious error / Serious error(Comm) /
CHK_TPOS24:ULvl Error level for undefined error at TPOS24 Alarm
Minor error / Alarm / Warning
--- / Serious error / Serious error(Comm) /
CHK_TPOS24:FLvl Error level for faulty error at TPOS24 Minor error
Minor error / Alarm / Warning

Setting of PRP_HSR (Function ID: 224101)


Setting item Range Contents Default setting value Notes

CHK_LRE:Sw Off / On Enable switch On


--- / Serious error / Serious error(Comm) /
CHK_LRE:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning

Setting of CHK_LAN1 and CHK_LAN2 (Function ID: 220D01 and 220D02)


Setting item Range Contents Default setting value Notes

CHK_LAN1:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ LAN1:Lvl Error level Minor error
Minor error / Alarm/ Warning

CHK_LAN2:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ LAN2:Lvl Error level Minor error
Minor error / Alarm/ Warning

GRL200 (Soft 033 & 037)


- 1242 -
6F2S1914 (0.37)

10.2.40 Signal (Data ID)


 Signal monitoring point
CHK_ROMRAM (Function ID: 220101)
Element ID Name Description
32FFFF1001 EXEC_CNT Executing counter

3210001001 RESULT Check result

3210011001 RES_INST Check result (instant)

 Signal monitoring point


CHK_SUM (Function ID: 220201)
Element ID Name Description
3210101001 CHECKSUM

3210111001 CHECKSUMC

32E0001001 CHK_POINT

32FFFF1001 EXEC_CNT Executing counter

3210201001 LOADERSUM

3210121001 PROG_SIZE

3210001001 RESULT Check result

3210011001 RES_INST Check result (instant)

 Signal monitoring point


CHK_PROGRAM (Function ID: 220301)
Element ID Name Description
30E0001001 CHKPOINT test point1

30E0011001 CHKPOINT2 test point2

32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_NMI (Function ID: 220401)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_RAM (Function ID: 220601)
Element ID Name Description
32E0001001 CHKPOINT test point

3210021001 ECC_SECNT ECC single error cnt

GRL200 (Soft 033 & 037)


- 1243 -
6F2S1914 (0.37)

 Signal monitoring point


CHK_RAM (Function ID: 220601)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_ECC (Function ID: 220602)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_ SAMPLING (Function ID: 220701)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_ ACC (Function ID: 220E01)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210021001 RES_FAST check result(fast)

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_MRAM (Function ID: 220F01)
Element ID Name Description
32E0001001 CHKPOINT test point

32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

GRL200 (Soft 033 & 037)


- 1244 -
6F2S1914 (0.37)

 Signal monitoring point


CHK_ BIO (Function ID: 221101 to 221108)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_ HMI (Function ID: 2201301)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_SETTING (Function ID: 221501)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_RTC (Function ID: 221701)
Element ID Name Description
32E0001001 CHKPOINT Test point

32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_CT (Function ID: 221801 and 221802)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_IZ (Function ID: 221901 and 221902)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

GRL200 (Soft 033 & 037)


- 1245 -
6F2S1914 (0.37)

 Signal monitoring point


CHK_IZ (Function ID: 221901 and 221902)
Element ID Name Description
3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_V2 (Function ID: 221A01)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_VZ (Function ID: 221B01)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_ VTF (Function ID: 221C01)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_POWER (Function ID: 222D01)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_CTF (Function ID: 221E01)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

GRL200 (Soft 033 & 037)


- 1246 -
6F2S1914 (0.37)

 Signal monitoring point


CHK_CB (Function ID: 222001 and 222002)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_DS (Function ID: 221101)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_PLC_DAT (Function ID: 223202)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210011001 RES_INST check result(instant)

3210001001 RESULT check result

 Signal monitoring point


CHK_PING (Function ID: 223601 and 223602)
Element ID Name Description
EXEC_CNT 32FFFF1001 execute counter

RESULT 3210001001 check result

RES_INST 3210011001 check result(instant)

 Signal monitoring point


CHK_ CMLV (Function ID: 224001)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_DPOSSYN (Function ID: 229001)
Element ID Name Description
32110111B0 CDS1_RES CHK_DPOSSYN1 result

32110211B0 CDS2_RES CHK_DPOSSYN2 result

GRL200 (Soft 033 & 037)


- 1247 -
6F2S1914 (0.37)

 Signal monitoring point


CHK_DPOSSYN (Function ID: 229001)
Element ID Name Description
32110311B0 CDS3_RES CHK_DPOSSYN3 result

 Signal monitoring point


CHK_DPOS (Function ID: 229101)
Element ID Name Description
32110111B0 CDP1_RES CHK_DPOS1 result

32110211B0 CDP2_RES CHK_DPOS2 result

32110311B0 CDP3_RES CHK_DPOS3 result

… … …

32114811B0 CDP72_RES CHK_DPOS72 result

 Signal monitoring point


CHK_TPOS (Function ID: 229201)
Element ID Name Description
32110111B0 CTP1_RES CHK_TPOS1 result

32110211B0 CTP2_RES CHK_TPOS2 result

32110311B0 CTP3_RES CHK_TPOS3 result

… … …

32111811B0 CTP24_RES CHK_TPOS24 result

 Signal monitoring point


CHK_FPGA (Function ID: 220B01)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


PRP_HSR (Function ID: 224101)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_LAN1/2 (Function ID: 220D01, 220D02)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

GRL200 (Soft 033 & 037)


- 1248 -
6F2S1914 (0.37)

Trip circuit supervision task


The TCS function provides an alarm when it detects a failure in the circuit breaker tripping
control circuit. The failure could be caused by loss of power supply in the trip circuit or an open
circuit in the control circuit connection.

Displaying error message founded by the TCS function is shown in Table 10.3-1; the error
is cleared when recovered

Table 10.3-1 Supervision items and error levels for Trip supervision
Detailed Error
Sec.No. Supervision items(Screen message) Info. Lvl LED
10.3.1 Trip circuit error (TC error) N/A 3 On

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.3-2 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 1249 -
6F2S1914 (0.37)

10.3.1 Detecting erroneous operation


(i) Operation logics
The TCS has six sets of monitoring logic (TCS1 to TCS6), as shown in Figure 10.3-1. For
example, the TCS1 logic issues a signal “TC1_Fail” when the following conditions are
determined in the TCS1 logic:
 Both signals at PLC connection points “TC1_FAIL_SIGNAL1” and “TC1_FAIL_SIGNAL2”
being absent for more than 0.4 sec.
 Either On or OPT-On† being set for scheme switch [TCS1-EN].
8000011BB0

800001EBB0 TC1_FAIL_SIGNAL1 1 &


8000011B60

8000011BB1 t 0 0 t TC1_FAIL
800001EBB1 TC1_FAIL_SIGNAL2 1 0.4s 0.4s

8000011BB2

800001EBB2 TC1_FAIL_COND
OPT-On &
≥1
TCS1-EN
On
8100021B60

TCS2 scheme logic (same as TCS1 scheme logic) TC2_FAIL

8200031B60

TCS3 scheme logic (same as TCS1 scheme logic) TC3_FAIL

8300041B60

TCS4 scheme logic (same as TCS1 scheme logic) TC4_FAIL

8400051B60

TCS5 scheme logic (same as TCS1 scheme logic) TC5_FAIL

8500061B60

TCS6 scheme logic (same as TCS1 scheme logic) TC6_FAIL

≥1

8F00001B60

TC_FAIL

Figure 10.3-1 Six sets of TCS scheme logic


†Note:If the user wishes to add a user-programmed condition for the TCS1 decision, set
OPT-On and connect the user-programmed signal at PLC connection point
“TC1_FAIL_COND”. The TCS1 monitor will then only be available when a user-
programmed signal is present at PLC connection point “TC1_FAIL_COND”.

(ii) Applications
Example1
Figure 10.3-2 provides an application example of the TCS function. Two binary-input signals
are assigned to PLC connection points “TC1_FAIL_SIGNAL1” and “TC1_FAIL_SIGNAL2”.
When the trip circuit is healthy, a small current will flow in the BI circuits, the CB auxiliary
contacts, and the trip coil. This small current can be observed to flow in both the CB-open
condition and the CB-closed condition. If the small current supplied to the trip circuit is lost,

GRL200 (Soft 033 & 037)


- 1250 -
6F2S1914 (0.37)

or if the connections between the trip circuit and the BI circuits become open circuit, a signal
"TC1_FAIL" is generated; then, the TCS1 logic will issue a Trip Circuit Fail alarm.

Note: A threshold setting voltage is required for the BI circuits. The user should set the
threshold to one-half of the value of the trip supply voltage. This is because in this
scheme there are two BI circuits connected in series. The supply voltage across the
BI circuit will be divided by two when the 52 contact is closed and the 52b contact
is open. Thus, the BI circuit may fail to operate if the BI sensitivity is only set in
response to the supply voltage. For example, the BI threshold voltage should be
set below 55V when a trip supply voltage of 110V is applied. For the TCS function,
the user should select two BI circuits from the BI2A module or the BIO4 module,
because the BI circuits of both of these modules can have lower threshold voltages
than the BI circuits that are available in other modules.

Trip circuit
()

Protection
8000011BB0
relay R
BI1 Binary input 800001EBB0 TC1_FAIL_SIGNAL1 1
circuit &
8000011B60

R 8000011BB1 t 0 0 t TC1_FAIL

BI2 Binary input 800001EBB1 TC1_FAIL_SIGNAL2 1 0.4s 0.4s


circuit
8000011BB2
52a 52b 800001EBB2 TC1_FAIL_COND
OPT-On &
≥1
TCS1-EN On

Trip coil

()
LCP & GIS

Figure 10.3-2 Connection Example1 for TCS1 logic

Example2
In Example2 a binary input signal is assigned to PLC connection point “TC1_FAIL_SIGNAL1”.
With this arrangement if the CB is open, the small monitoring current will not be able to flow
in the BI circuit. Therefore, it is recommended that setting OPT-On is selected for the scheme
switch [TCS1-EN] and that a CB-closed-status signal is applied to PLC connection point
“TC1_FAIL_COND”. Monitoring is only enabled while the CB is in the closed position when
using this setting. This setting avoids unnecessary monitoring when the circuit breaker is open
when using this scheme.

GRL200 (Soft 033 & 037)


- 1251 -
6F2S1914 (0.37)

Trip circuit
()

Protection
8000011BB0
relay R

BI1 Binary input 800001EBB0 TC1_FAIL_SIGNAL1 1


circuit &
8000011B60

8000011BB1 t 0 0 t TC1_FAIL
800001EBB1 TC1_FAIL_SIGNAL2 1 0.4s 0.4s
52a
8000011BB2

800001EBB2 TC1_FAIL_COND
OPT-On &
≥1
CB closed TCS1-EN On
status signal
Trip coil

()
LCP & GIS

Figure 10.3-3 Connection Example2 for TCS1 logic

GRL200 (Soft 033 & 037)


- 1252 -
6F2S1914 (0.37)

10.3.2 Trip circuit error (TC error)


(i) Error level
For the operation, the user can set the error level when the function detects the error
concerning the operation. Generally, the default error level is set at level 3 (Minor error), but
the user can program the level for the TCS1—6 using settings [CHK_TCS1:LVL] to
[CHK_TCS6:LVL]; then, set On for the setting [CHK_TCS1:Sw] to [CHK_TCS6:Sw].

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.3-3 Error messages provided by the supervisor in TCS
Item Meaning of the information
TCx error Detection of an error located at x
Error level Minor error (Level 3)

Table 10.3-4 Detailed information in TCS


Display area Meaning of the detailed information
N/A (No message is displayed)

GRL200 (Soft 033 & 037)


- 1253 -
6F2S1914 (0.37)

10.3.3 Setting
Setting of TCS(Function ID: 482001)
Note
Setting item Range Units Contents Default setting value
s
TCS1(Trip Circuit Supervision 1)
TCS1-EN Off / On / OPT-On — Off
enable
TCS2(Trip Circuit Supervision 2)
TCS2-EN Off / On / OPT-On — Off
enable
TCS3(Trip Circuit Supervision 3)
TCS3-EN Off / On / OPT-On — Off
enable
TCS4(Trip Circuit Supervision 4)
TCS4-EN Off / On / OPT-On — Off
enable
TCS5(Trip Circuit Supervision 5)
TCS5-EN Off / On / OPT-On — Off
enable
TCS6(Trip Circuit Supervision 6)
TCS6-EN Off / On / OPT-On — Off
enable

Setting of CHK_TCS (Function ID: 223B01 to 223B06)


Default setting
Setting item Range Contents Notes
value
CHK_TCS1:Sw Off / On Enable switch On
--- / Serious error / Serious
CHK_ TCS1:Lvl error(Comm) / Minor error / Alarm/ Error level Minor error
Warning

…. …. …. ….

CHK_TCS6:Sw Off / On Enable switch On


--- / Serious error / Serious
CHK_ TCS6:Lvl error(Comm) / Minor error / Alarm/ Error level Minor error
Warning

GRL200 (Soft 033 & 037)


- 1254 -
6F2S1914 (0.37)

10.3.4 Signal (Data ID)


 Signal monitoring point
TCS(Function ID: 482001)
Element ID Name Description
8000011B60 TC1_FAIL Trip circuit1 fail
8000011BB0 TC1_FAIL_SIGNAL1 Trip circuit1 fail signal1
8000011BB1 TC1_FAIL_SIGNAL2 Trip circuit1 fail signal2
8000011BB2 TC1_FAIL_COND TC1 fail condition
8100021B60 TC2_FAIL Trip circuit2 fail
8100021BB0 TC2_FAIL_SIGNAL1 Trip circuit2 fail signal1
8100021BB1 TC2_FAIL_SIGNAL2 Trip circuit2 fail signal2
8100021BB2 TC2_FAIL_COND TC2 fail condition
8200031B60 TC3_FAIL Trip circuit3 fail
8200031BB0 TC3_FAIL_SIGNAL1 Trip circuit3 fail signal1
8200031BB1 TC3_FAIL_SIGNAL2 Trip circuit3 fail signal2
8200031BB2 TC3_FAIL_COND TC3 fail condition
8300041B60 TC4_FAIL Trip circuit4 fail
8300041BB0 TC4_FAIL_SIGNAL1 Trip circuit4 fail signal1
8300041BB1 TC4_FAIL_SIGNAL2 Trip circuit4 fail signal2
8300041BB2 TC4_FAIL_COND TC4 fail condition
8400051B60 TC5_FAIL Trip circuit5 fail
8400051BB0 TC5_FAIL_SIGNAL1 Trip circuit5 fail signal1
8400051BB1 TC5_FAIL_SIGNAL2 Trip circuit5 fail signal2
8400051BB2 TC5_FAIL_COND TC5 fail condition
8500061B60 TC6_FAIL Trip circuit6 fail
8500061BB0 TC6_FAIL_SIGNAL1 Trip circuit6 fail signal1
8500061BB1 TC6_FAIL_SIGNAL2 Trip circuit6 fail signal2
8500061BB2 TC6_FAIL_COND TC6 fail condition
8F00001B60 TC_FAIL Trip circuit fail

 Signal Connection point


TCS(Function ID: 482001)
Element ID Name Description
800001EBB2 TC1_FAIL_COND TC1 fail condition

800001EBB0 TC1_FAIL_SIGNAL1 Trip circuit1 fail signal1

800001EBB1 TC1_FAIL_SIGNAL2 Trip circuit1 fail signal2

810002EBB2 TC2_FAIL_COND TC2 fail condition

810002EBB0 TC2_FAIL_SIGNAL1 Trip circuit2 fail signal1

810002EBB1 TC2_FAIL_SIGNAL2 Trip circuit2 fail signal2

820003EBB2 TC3_FAIL_COND TC3 fail condition

820003EBB0 TC3_FAIL_SIGNAL1 Trip circuit3 fail signal1

820003EBB1 TC3_FAIL_SIGNAL2 Trip circuit3 fail signal2

830004EBB2 TC4_FAIL_COND TC4 fail condition

830004EBB0 TC4_FAIL_SIGNAL1 Trip circuit4 fail signal1

830004EBB1 TC4_FAIL_SIGNAL2 Trip circuit4 fail signal2

840005EBB2 TC5_FAIL_COND TC5 fail condition

840005EBB0 TC5_FAIL_SIGNAL1 Trip circuit5 fail signal1

GRL200 (Soft 033 & 037)


- 1255 -
6F2S1914 (0.37)

 Signal Connection point


TCS(Function ID: 482001)
Element ID Name Description
840005EBB1 TC5_FAIL_SIGNAL2 Trip circuit5 fail signal2

850006EBB2 TC6_FAIL_COND TC6 fail condition

850006EBB0 TC6_FAIL_SIGNAL1 Trip circuit6 fail signal1

850006EBB1 TC6_FAIL_SIGNAL2 Trip circuit6 fail signal2

 Signal monitoring point


CHK_TCS (Function ID: 223B01 to 223B06)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

GRL200 (Soft 033 & 037)


- 1256 -
6F2S1914 (0.37)

Supervision task of interruption capability on CB


For the supervision of the circuit breaker, the sigma_Iy function is provided so that the broken
current quantities at respective tripping are accumulated. Thereby, the user can monitor the
interrupting capability using the sigma_Iy function. When trip commands are issued, the
sigma_Iy function monitors the maximum current (I at CT primary) in every occurrence of the
fault, the sigma_Iy function accumulates each maximum fault current powered by a parameter
‘y’. Thus, the user can find a synthesized broken current value using the sigma_Iy function.

Displaying error message founded by the sigma_Iy function is shown in Table 10.4-1.

Table 10.4-1 Supervision items and error levels for Sigma_Iy


Detailed Error
Sec.No. Supervision items(Screen message) Info. Lvl LED
10.4.1 Sigma Iy error (CHK_SGMIY error) N/A 3 On

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.4-2 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Main features ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 1257 -
6F2S1914 (0.37)

10.4.1 Operation of sigma Iy


When the value ‘n’ is provided as the number of the fault currents, equation (10.4-1) is satisfied:

y y y y
∑ IY =I1 +I2 +I3 +⋯+In (10.4-1)

As setting for a conventional CB with regard to the parameter ‘y’, the user can set a value
‘2.0’ for the [SIGMA_IY-Y]; that is, the accumulation is performed with the fault currents
squared (I 2). On the other hand, the user can be required to set a less value (say ‘1.0’) for the
[SIGMA_IY-Y] when a special CB is required (that is, for the high voltage system).

I1 Maximum broken current


at the first

In Maximum broken current


at the nth

Tripping CB
Command issuing #1
Command issuing #2 Tripping CB
Command issuing #n

y y y y
∑ IY =I1 +I2 +I3 +⋯+In

Figure 10.4-1 Concept of Sigma_Iy function

The sigma_Iy function can designed to issue an alarm when the synthesized broken
current value reaches an alarm level set by [SIGMA_IY-Alarm]; issuing an alarm is ready when
the user sets On for scheme switch [SIGMA_IY-AEN].

GRL200 (Soft 033 & 037)


- 1258 -
6F2S1914 (0.37)

10.4.2 Sigma Iy error (CHK_SGMIY error)


(i) Error level
For the operation, the user can set the error level when the function detects the error
concerning the operation. Generally, the default error level is set at level 3 (Minor error), but
the user can program the level using settings [CHK_SGMIY-A:LVL] to [CHK_SGMIY-C:LVL] in
respective phase A, B, and C; then, set On for the setting [CHK_SGMIY-A:Sw] to [CHK_SGMIY-
C:Sw].

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.4-3 Error messages provided by the supervisor in SIGMIY
Item Meaning of the information
CHK_SGMIY-x error Detection of an error located at x-phase
Error level Minor error (Level 3)

Table 10.4-4 Detailed information in SIGMIY


Display area Meaning of the detailed information
N/A (No message is displayed)

GRL200 (Soft 033 & 037)


- 1259 -
6F2S1914 (0.37)

10.4.3 Setting
Setting of SIGMA_IY (Function ID: 713001)
Note
Setting item Range Units Contents Default setting value
s
SIGMA_IY-EN Off / On — Enabling Sigma Iy function operation Off
SIGMA_IY-AEN Off / On — Enabling Sigma Iy alarming Off
SIGMA_IY-Alarm 1.0 to 100000000.0 — Alarm level in Sigma Iy function 10000.0
SIGMA_IY-Y 1.0 to 2.0 — Y parameter for in Sigma Iy 1.0

Setting of CHK_SGMIY (Function ID: 223A01 to 223A03)


Default
Setting item Range Contents setting Notes
value
CHK_SGMIY-A:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) / Minor error / Alarm/
CHK_SGMIY-A:Lvl Error level Minor error
Warning
CHK_SGMIY-B:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) / Minor error / Alarm/
CHK_SGMIY-B:Lvl Error level Minor error
Warning
CHK_SGMIY-C:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) / Minor error / Alarm/
CHK_SGMIY-C:Lvl Error level Minor error
Warning

GRL200 (Soft 033 & 037)


- 1260 -
6F2S1914 (0.37)

10.4.4 Signal (Data ID)


 Signal monitoring point
SIGMA_IY (Function ID: 713001)
Element ID Name Description
8000001C20 SGMIY-A Monitoring SIGMA_IY relay element output (phase-A)
8100001C21 SGMIY-B Monitoring SIGMA_IY relay element output (phase-B)
8200001C22 SGMIY-C Monitoring SIGMA_IY relay element output (phase-C)

 Signal monitoring point


CHK_SGMIY-A to C (Function ID: 223A01 to 223A03)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

GRL200 (Soft 033 & 037)


- 1261 -
6F2S1914 (0.37)

Supervision tasks for device dependent features


Displaying errors regarding to special problems are summarized in Table 10.2-1; the error is
cleared when recovered

Table 10.5-1 Supervision items and error levels for device-dependent


Detailed ERROR
Sec. Supervision items(Screen message) Info. LVL. LED
No.
10.5.1 Error detection of differential current in DIF (Id) N/A 3 On
10.5.2 Current transformer failure detected with DIF (DIF-CT) N/A 3 On
10.5.3 Synchronizing and sampling error (Com sync fail) N/A 2 On
10.5.4 Communication failure (Com fail) N/A 2 On
10.5.5 Error signal level for sending (TX level) N/A 3 On
10.5.6 Error signal level for receiving (RX level) N/A 3 On
10.5.7 Propagation delay error (Com Td) Displayed 3 On
10.5.8 Error terminal configuration (Term ID) N/A 2 On
10.5.9 Monitoring ready state at the remote (Term rdy) N/A 2 On
10.5.10 Transmission error (Com fail-R) N/A 2 On
10.5.11 Master-slave monitoring (MSCHK) N/A 2 On
10.5.12 Supervision of Relay ID (RYID) Displayed 2 On

─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.5-2 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
33 37
– Device dependent supervision tasks ✓ ✓
✓: Applicable NA: Not applicable

GRL200 (Soft 033 & 037)


- 1262 -
6F2S1914 (0.37)

10.5.1 Error detection of differential current in DIF (Id)


Error operations are monitored by the operation of DIFL-SV element† in the current
differential function (DIF); the automatic supervision function can alarm its erroneous
operation by the notification from the DIF function.
†Note:The DIF function has the supervision feature itself; hence, the user can program
the criteria for the supervision using settings [DIFL-IdSV] and [TDIFL-IdSV]; then
set On for the scheme switch [DIFL-IdSV-EN]. For more information about the DIF
supervision, see Chapter Relay application: Current differential protection for the
line: Differential current monitor.

(i) Error level


Generally, the default error level is set at level 3 (Minor error), but the user can program the
level using setting [CHK_ID:LVl]; then, set On for the setting [CHK_ID:Sw]. The manufacture
sets 10 seconds for the detection using the [TDIFL-IdSV]. It is reset instantly when the error is
cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-3 Error messages provided by the supervisor in CHK_ID
Message and level Meaning of the information
Id error Detection of the erroneous differential current
Error level Minor error (Level 3)

Table 10.5-4 Detailed information in Hexadecimal in CHK_ID


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1263 -
6F2S1914 (0.37)

10.5.2 Current transformer failure detected with DIF (DIF-CT)


The CT failure can be monitored by the operation of DIFL-CTF element† in the current
differential function (DIF); the automatic supervision function can alarm its erroneous
operation by the notification from the DIF function.
†Note:The DIF function has the supervision feature itself; hence, the user can program
the criteria for the supervision using setting [DIFL-CTF]; then set On for the
scheme switch [CTFL-EN]. For more information about the DIF supervision, see
Chapter Relay application: Current differential protection for the line: Differential
current monitor.

(i) Error level


Generally, the default error level is set at level 3 (Minor error), but the user can program the
level using setting [CHK_DIF_CTF:LVl]; then, set On for the setting [CHK_DIF_CTF:Sw]. The
manufacturer sets the time for the detection for 10 seconds. The function resets instantly after
the error is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-5 Error messages provided by the supervisor in CHK_DIF_CTF
Message and level Meaning of the information
DIF-CT fail Failure detection on the CT
Error level Minor error (Level 3)

Table 10.5-6 Detailed information in Hexadecimal in CHK_DIF_CTF


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1264 -
6F2S1914 (0.37)

10.5.3 Synchronizing and sampling error (Com sync fail)


In the dual communication mode† (i.e., either 2Term-Dual, 2Term–4Term is set for setting
[TERM_TOPOLGY]), synchronization between two IEDs is monitored. If the error is detected
for ten seconds, the synchronizing error is issued.
†Note:See chapter Relay application: Transmission control function.

(i) Error level


Generally, the default error level is set at level 2 (Serious error (Comm)), as default, but the
user can program the level using settings [CHK_SPSYNC1:LVL] and [CHK_SPSYNC2:LVL];
then, set On for the settings [CHK_SPSYNC1:Sw] and [CHK_SPSYNC2:Sw]. The
manufacturer sets ten (10) seconds to detect the failure; it is reset with in one second when the
failure is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-7 Error messages provided by the supervisor in CHK_SPSYNC
Message and level Meaning of the information
ComX sync fail Detection of an error located at X
Error level Serious error (Level 2)

Table 10.5-8 Detailed information in CHK_SPSYNC


Code No. Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1265 -
6F2S1914 (0.37)

10.5.4 Communication failure (Com fail)


The transmission between two IEDs is also monitored. If the error is detected for ten seconds,
the communication failure is issued.

(i) Error level


Generally, the default error level is set at level 2 (Serious error (Comm)), but the user can
program the level using settings [CHK_CM_FAIL1:Lvl] and [CHK_CM_FAIL2:Lvl]; then, set On
for the setting [CHK_CM_FAIL1:Sw] and [CHK_CM_FAIL2:Sw]. The manufacture sets ten (10)
seconds to detect the failure; it is reset in 12 ssp (i.e., 12×48×Power_system_frequency (Hz))
when the failure is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-9 Error messages provided by the supervisor in CHK_CM_FAIL
Message and level Meaning of the information
ComX fail Detection of an error located at X†
Error level Serious error (Level 2) †
†Note:Level 2 is set as default, but the user can change the error level above using the
settings [CHK_CM_FAIL*:Lvl].

Table 10.5-10 Detailed information in CHK_CM_FAIL


Code No. Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1266 -
6F2S1914 (0.37)

10.5.5 Error signal level for sending (TX level)


When the communication module operates for the medium or long distance, the signal level
for sending can be monitored when On is set for the setting. The error signal is issued when
the erroneous signal is sensed for ten seconds. Note that this monitoring is not available for
the communication module for the short distance.

(i) Error level


Generally, the default error level is set at level 3 (Minor error), as default, but the user can
program the level using settings [CHK_TX_LVL1:Lvl] and [CHK_TX_LVL2:Lvl]; then, set On
for the settings [CHK_TX_LVL1:Sw] and [CHK_TX_LVL:Sw]. The manufacturer sets ten (10)
seconds set to detect the failure; it is reset in a second when the failure is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-11 Error messages provided by the supervisor in CHK_TX_LVL
Message and level Meaning of the information
TXx level error Detection for sending level improperly at x module
Error level Minor error (Level 3)

Table 10.5-12 Detailed information in Hexadecimal in CHK_TX_LVL


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1267 -
6F2S1914 (0.37)

10.5.6 Error signal level for receiving (RX level)


Similarly, the signal level for receiving can be monitored when On is set for the setting. The
error signal is issued when the erroneous signal is sensed for ten seconds. Note that this
monitoring is not available for the communication module for the short distance.

(i) Error level


Generally, the default error level is set at level 3 (Minor error), but the user can program the
level using settings [CHK_RX_LVL1:Lvl] and [CHK_RX_LVL2:Lvl]; then, set On for the setting
[CHK_RX_LVL1:Sw] and [CHK_RX_LVL:Sw]. The manufacturer sets ten (10) seconds to detect
the failure; it is reset with in a second when the failure is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-13 Error messages provided by the supervisor in CHK_RX_LVL
Message and level Meaning of the information
RXx level error Detection for receiving level improperly at x module
Error level Minor error (Level 3)

Table 10.5-14 Detailed information in Hexadecimal in CHK_RX_LVL


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1268 -
6F2S1914 (0.37)

10.5.7 Propagation delay error (Com Td)


Propagation delay on the communication can be monitored; it can be detected when the
propagation delay is examined beyond the setting. The delay error is issued when the delay is
detected for ten seconds.

(i) Error level


Generally, the default error level is set at level 3 (Minor error) when the delay is 6000 micro
seconds larger. However, the user can program the criterion time using settings
[CHK_TD_OVER1:Td] and [CHK_TD_OVER2:Td] in micro seconds; then, set On for the
settings [CHK_TD_OVER1:Sw] and [CHK_TD_OVER2:Sw] after set preferred error levels of
the settings [CHK_TD_OVER1:Lvl] and [CHK_TD_OVER2: Lvl]. The manufacturer sets ten
(10) seconds to detect the failure; it is reset with in a second when the failure is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-15 Error messages provided by the supervisor in CHK_TD_OVER
Message and level Meaning of the information
ComX Td over Detection for delay time being over at X module
Error level Minor error (Level 3)

Table 10.5-16 Detailed information in Hexadecimal in CHK_TD_OVER


Display Meaning of the detailed information
area Left column Right column
Top Delay time expressed in the
Setting time expressed in the hexadecimal
row hexadecimal

Middle
(No information is displayed) (No information is displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1269 -
6F2S1914 (0.37)

10.5.8 Error terminal configuration (Term ID)


The user can monitor the network configuration between terminals. The error signal is issued
when the erroneous configuration is observed for ten seconds. For monitoring, the user should
set Off for the settings [MSCHK-EN] and set On for the [CHK_TERM_CNF:Sw]. For more
information about the master-slave relationship, see chapter Relay application:
Communication application.

(i) Error level


Generally, the default error level is set at level 2 (Serious error (Comm)), but the user can
program the level using setting [CHK_TERM_CNF:Lvl]; then, set On for the setting
[CHK_TERM_CNF:Sw]. The manufacturer sets ten (10) seconds to detect the failure; it is reset
with in a second when the failure is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-17 Error messages provided by the supervisor in CHK_TERM_CNF
Message and level Meaning of the information
Term ID error Detection for error ID in the network configuration
Error level Serious error (Level 2)

Table 10.5-18 Detailed information in Hexadecimal in CHK_TERM_CNF


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1270 -
6F2S1914 (0.37)

10.5.9 Monitoring ready state at the remote (Term rdy)


Monitor of the ready state at the remote IED is performed when the user sets On for the setting.
If the IED at the remote cannot stay in the ready state for ten seconds, an error signal is issued.

(i) Error level


Generally, the default error level is set at level 2 (Serious error (Comm)), but the user can
program the level using settings [CHK_READY1:Lvl] and [CHK_READY2:Lvl]; then, set On for
the settings [CHK_READY1:Sw] and [CHK_READY2:Sw]. The manufacture sets ten (10)
seconds to detect the failure; it is reset with in a second when the failure is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-19 Error messages provided by the supervisor in CHK_READY
Message and level Meaning of the information
Term rdy error Detection for remote terminal not being ready
Error level Serious error (Level 2)

Table 10.5-20 Detailed information in Hexadecimal in CHK_READY


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1271 -
6F2S1914 (0.37)

10.5.10 Transmission error (Com fail-R)


An error occurred at the remote can be detected when the user sets On for the setting
[CHK_CMRFAIL1:Sw]. The error signal is issued when the remote IED cannot sense the signal
coming from the opposite IED for ten seconds.

(i) Error level


Generally, the default error level is set at level 2 (Serious error (Comm)), as default, but the
user can program the level using settings [CHK_CMRFAIL1:Lvl] and [CHK_CMRFAIL2:Lvl];
then, set On for the settings [CHK_CMRFAIL1:Sw] and [CHK_CMRFAIL2:Sw]. The
manufacture sets ten (10) seconds to detect the failure; it is reset with in a second when the
failure is cleared.

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-21 Error messages provided by the supervisor in CHK_CMRFAIL
Message and level Meaning of the information
ComX fail-R Detection for communication failure at remote terminal
Error level Serious error (Level 2)

Table 10.5-22 Detailed information in Hexadecimal in CHK_CMRFAIL


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1272 -
6F2S1914 (0.37)

10.5.11 Master-slave monitoring (MSCHK)


The user can monitor the relationship between the master and the slave terminals when the
IEDs operate in the master-slave configuration. The error signal will be issued instantly when
the erroneous configuration is observed. For monitoring, the user set On for the settings
[MSCHK-EN] and [CHK_CM_MS:Sw]. For more information about the master-slave
relationship, see chapter Relay application: Communication application.

(i) Error level


Generally, the default error level is set at level 2 (Serious error (Comm)), but the user can
program the level using settings [CHK_CM_MS1:Lvl] and [CHK_CM_MS2:Lvl]; then, set On
for the settings [CHK_CM_MS1:Sw] and [CHK_CM_MS2:Sw].

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-23 Error messages provided by the supervisor in CHK_CM_MS
Message and level Meaning of the information
MSCHKx error Detection for master/slave failure at X module
Error level Serious error (Level 2)

Table 10.5-24 Detailed information in Hexadecimal in CHK_CM_MS


Display area Meaning of the detailed information
N/A (No information is displayed)

GRL200 (Soft 033 & 037)


- 1273 -
6F2S1914 (0.37)

10.5.12 Supervision of Relay ID (RYID)


When the IED is designated with relay addresses (relay ID), the relay ID can be monitored by
the communication application when the user set On for the settings [CHK_RYID:Sw]. For
more information with regard to the relay address, see chapter Relay application:
Communication application.

(i) Error level


Generally, the default error level is set at level 2 (Serious error (Comm)), but the user can
program the level using settings [CHK_RYID1:Lvl] and [CHK_RYID2:Lvl]; then, set On for the
settings [CHK_RYID1:Sw] and [CHK_RYID 2:Sw].

(ii) Error message


When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-25 Error messages provided by the supervisor in CHK_RYID
Message and level Meaning of the information
RYIDx error Detection for erroneous Relay ID at x module
Error level Serious error (Level 2)

Table 10.5-26 Detailed information in Hexadecimal in CHK_RYID


Display Meaning of the detailed information
area Left column Right column
Top
Relay ID expecting Relay ID received in practice
row
Middle
(No information is displayed) (No information is displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row

GRL200 (Soft 033 & 037)


- 1274 -
6F2S1914 (0.37)

10.5.13 Setting
Setting of CHK_ID (Function ID: 221401)
Note
Setting item Range Contents Default setting value
s

CHK_ID:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_ID:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_DIF_CTF (Function ID: 221F01)


Note
Setting item Range Contents Default setting value
s

CHK_DIF_CTF:Sw Off / On Enable switch On

--- / Serious error / Serious error(Comm) /


CHK_DIF_CTF:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_SPSYNC (Function ID: 2205001)


Note
Setting item Range Contents Default setting value
s
CHK_SPSYNC1:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_ SPSYNC1:Lvl Error level Serious error(Comm)
Minor error / Alarm/ Warning
CHK_SPSYNC2:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_ SPSYNC2:Lvl Error level Serious error(Comm)
Minor error / Alarm/ Warning

Setting of CHK_CM_FAIL (Function ID: 225101 and 225102)


Note
Setting item Range Contents Default setting value
s
CHK_CM_FAIL1:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_ CM_FAIL1:Lvl Error level Serious error(Comm)
Minor error / Alarm/ Warning
CHK_CM_FAIL2:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_ CM_FAIL2:Lvl Error level Serious error(Comm)
Minor error / Alarm/ Warning

Setting of CHK_TX_LVL (Function ID: 225401 and 225402)


Note
Setting item Range Contents Default setting value
s
CHK_TX_LVL1:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_TX_LVL1:Lvl Error level Minor error
Minor error / Alarm/ Warning
CHK_TX_LVL2:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_TX_LVL2:Lvl Error level Minor error
Minor error / Alarm/ Warning

GRL200 (Soft 033 & 037)


- 1275 -
6F2S1914 (0.37)

Setting of CHK_RX_LVL (Function ID: 225501 and 225502)


Note
Setting item Range Contents Default setting value
s
CHK_RX_LVL1:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_RX_LVL1:Lvl Error level Minor error
Minor error / Alarm/ Warning
CHK_RX_LVL2:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_RX_LVL2:Lvl Error level Minor error
Minor error / Alarm/ Warning

Setting of CHK_TD_OVER1 and 2 (Function ID: 225601 and 225602)


Default setting Note
Setting item Range Units Contents
value s
CHK_TD_OVER1:Sw Off / On — Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_TD_OVER1:Lvl — Error level Minor error
Minor error / Alarm/ Warning
telecomm delay
CHK_TD_OVER1:Td 100 - 16000 Micro sec 6000
time
CHK_TD_OVER2:Sw Off / On — Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_TD_OVER2:Lvl — Error level Minor error
Minor error / Alarm/ Warning
telecomm delay
CHK_TD_OVER2:Td 100 - 16000 Micro sec 6000
time

Setting of CHK_TERM_CNF (Function ID: 225701)


Note
Setting item Range Contents Default setting value
s
CHK_TERM_CNF:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_TERM_CNF:Lvl Error level Serious error(Comm)
Minor error / Alarm/ Warning

Setting of CHK_READY (Function ID: 225801 and 225802)


Note
Setting item Range Contents Default setting value
s
CHK_READY1:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_READY1:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning
CHK_READY2:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_READY2:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning

Setting of CHK_CMRFAIL (Function ID: 225901 and 225902)


Note
Setting item Range Contents Default setting value
s
CHK_CMRFAIL1:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_CMRFAIL1:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning
CHK_CMRFAIL2:Sw Off / On Enable switch On

GRL200 (Soft 033 & 037)


- 1276 -
6F2S1914 (0.37)

Setting of CHK_CMRFAIL (Function ID: 225901 and 225902)


Note
Setting item Range Contents Default setting value
s
--- / Serious error / Serious error(Comm) /
CHK_CMRFAIL2:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning

Setting of CHK_CM_MS (Function ID: 225A01 and 225A02)


Note
Setting item Range Contents Default setting value
s
CHK_CM_MS1:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_CM_MS1:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning
CHK_CM_MS2:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_CM_MS2:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning

Setting of CHK_RYID (Function ID: 222901 and 222902)


Note
Setting item Range Contents Default setting value
s
CHK_RYID1:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_RYID1:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning
CHK_RYID2:Sw Off / On Enable switch On
--- / Serious error / Serious error(Comm) /
CHK_RYID2:Lvl Error level Serious error (Comm)
Minor error / Alarm/ Warning

GRL200 (Soft 033 & 037)


- 1277 -
6F2S1914 (0.37)

10.5.14 Signal (Data ID)


 Signal monitoring point
CHK_ID (Function ID: 221401)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_DIF_CTF (Function ID: 221F01)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_ SPSYNC (Function ID: 225001 – 225002)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_CM_FAIL (Function ID: 225101 – 225102)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_TX_LVL1 and 2 (Function ID: 225401 and 225402)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_RX_LVL1 and 2 (Function ID: 225501 and 225502)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

GRL200 (Soft 033 & 037)


- 1278 -
6F2S1914 (0.37)

 Signal monitoring point


CHK_RX_LVL1 and 2 (Function ID: 225501 and 225502)
Element ID Name Description
3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_TD_OVER1 and 2 (Function ID: 225601 and 225602)
Element ID Name Description
32FFFF1001 EXEC_CNT

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_TERM_CNF (Function ID: 225701)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_READY1 and 2 (Function ID: 225801 and 225802)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_CMRFAIL1 and 2 (Function ID: 225901 and 225902)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

 Signal monitoring point


CHK_CM_MS1 and 2 (Function ID: 225A01 and 225A02)
Element ID Name Description
32FFFF1001 EXEC_CNT

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

GRL200 (Soft 033 & 037)


- 1279 -
6F2S1914 (0.37)

 Signal monitoring point


CHK_RYID1 and 2 (Function ID: 222901 and 222902)
Element ID Name Description
32FFFF1001 EXEC_CNT executing counter

3210001001 RESULT check result

3210011001 RES_INST check result(instant)

GRL200 (Soft 033 & 037)


- 1280 -
6F2S1914 (0.37)

11 Communication protocol
Contents Pages Pages
IEC 60870-5-103 operation – LAN operation –
-Interface 1352 -IP address 1283
-Interoperability 1355 -Hot standby operation 1284
-Operation 1375 -PRP/HSR operation 1291
IEC 61850 operation 1301 -RSTP operation 1295
-About protocol 1303 -Monitoring (Hot standby) 1286
-Communication service 1306 -Monitoring (PRP/HSR) 1293
-Engineering work 1309 Protocol selection 1282
-Goose monitoring status 1332 RS485operation 1380
-Protocol selection 1330 USB operation 1379
-Quality signal 1331
-Setting 1328
-Supervise 1330
-61850 Editon1 option 1305
-61850 Editon2 1305

─────────────────────────────────────────────────────────────────
Note: The implementation of such protocols depends on the selection of protocols. Several
IED models do not have the protocols. To determine whether the protocols are implemented in
the IED, locate the IED ordering number; and check the order number at the “U position”
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.5-1 Comparative table in respective ordering numbers
Ordering No. at “U”
Sec. Feature
1 2
11.2.1 TCP/IP ✓ ✓
11.2.2 Hot-standby ✓ ✓
11.2.3 PRP/HSR NA ✓1
11.2.4 RSTP NA ✓1
11.3 IEC 61850 ✓2 ✓
11.4 IEC 60870-5-103 ✓2 NA
✓: Applicable NA: Not applicable
1 LAN modules, designed for PRP/HSR/RSTP marked with “L or N” code at position “E”, shall
be mounted in IED, if network operation in PRP/HSR/RSTP is required.
2 Either 61850 or 103 shall be selected during the operation.

GRL200 (Soft 033 & 037)


- 1281 -
6F2S1914 (0.37)

Interface setting and protocol selection


Ethernet and Serial ports can be provided at IED for the communication. The protocol is
selectable† using settings§. IEC 61850 standard is conventional choice for the substation
communication, but the user can select IEC 60870-5-103 standard† so that the IED can have
the communication with the legacy apparatuses. Some communication modules are provided
such as LAN, USB, or RS485 interfaces‡, so the user can specify transmission specifications
(i.e., speed and error check parity) at the IED.

Figure 11.1-1 illustrates the LAN and USBCOM sub-menus provided for the connection
to the LAN, whereas the SLAVE PROTOCOL sub-menu is for the selection of either the
IEC61850 or the IEC103 protocols. The IEC61850 sub-menu has its own settings, so does the
IEC103 menu. The RS485 sub-menu is screened when the IED has the one used for the IEC103
in the serial communication.

Communication
10:48 1/6
LAN >
USBCOM >
RS485 >
SLAVE PROTOCOL >
IEC61850 >
IEC103 SLV >

Figure 11.1-1 Example of Setting menu ‘IEC61850, IEC103, RS485 and USB’
†Note:The select operation is dependent on the IED configurations, which the customer
has determined with the ordering code. Accordingly, the select operation can be
unavailable if the protocol is not provided in the IED. To examine the IED
configuration, check your ordering code referring Appendix: Ordering.
‡Note:We have discussed the specifications regarding the communication interface. See
Technical description: Signal processing and communication module.
§Note:The setting function is provided with the function ‘CNN_SLAVE’. The setting list
and Signal monitoring point (in Data ID) are shown below:
CNN_SLAVE (Function ID: 300001)
Setting item Range Contents Default setting value
Slave Protocol IEC61850 / IEC103 Protocol selection IEC61850
S-TestFlagCancel Off / On Canceling Test-flag in the slave communication Off

Element ID Name Description


3100013406 ProcType Selected a type in the protocol

GRL200 (Soft 033 & 037)


- 1282 -
6F2S1914 (0.37)

LAN operation
11.2.1 LAN address (IP address)
The IED can have the communication with “Transmission Control Protocol/Internet Protocol
(TCP/IP)”. The user can set IP addresses and other TCP/IP information. Table 11.2-1 shows
the setting items provided for the LAN†.

Table 11.2-1 TCP/IP settings at LAN modules


Ports Setting items Range Setting meaning Default value
IPADDRESS1 0.0.0.0–255.255.255.255 First IP address 192.l68.1.11
Port A
SUBNETMASK1 0.0.0.0–255.255.255.255 Subnet mask 255.255.255.0
at C11
GATEWAY1 0.0.0.0–255.255.255.255 Default gateway 192.168.1.1
IPADDRESS2‡ 0.0.0.0–255.255.255.255 Second IP address 192.l68.1.12
Port B
SUBNETMASK2‡ 0.0.0.0–255.255.255.255 Subnet mask 255.255.255.0
at C12
GATEWAY2‡ 0.0.0.0–255.255.255.255 Default gateway 192.168.1.1

When wishing to change addresses, enter the new address at LAN setting sub-menu.
Figure 11.2-1 shows the setting menu provided to change the addresses‡.

LAN
10:48 1/6
IPADDRESS1 +
192.168.1.11
SUBNETMASK1 +
255.255.255.1
GATEWAY1 +
192.168.1.1

Figure 11.2-1 Local LAN setting menu (on IED screen)

†Note:For the location of the LAN communication modules, see Chapter Technical
description: Signal processing and communication module.
‡Note:IP address setting is dependent on the selection of the communication protocols.
For setting [RedundantMode]=Hot-standby, an IP address should be assigned for
the both A and B pots (i.e., a single one is set for the both; see Table 11.2-4).
Similarly, for [RedundantMode]=PRP/HSR/RSTP, an IP address will be assigned
for the both (see Table 11.2-5).
When setting [RedundantMode]=Fixed, two IP addresses can be assigned for the
respective ports, provided two ports are sited (see Table 11.2-5).
‡Note:Chapter User interface: Setting sub-menu describes how to set the address on the
IED screen.

GRL200 (Soft 033 & 037)


- 1283 -
6F2S1914 (0.37)

11.2.2 Redundant LAN (Hot-standby)


Hot-standby is designed to change to another LAN path if an error occurs on the LAN
communication; accordingly, the LAN communication can have more security (i.e. “Redundant
communication”). The “Hot-standby (HOTST)” operation is possible when the IED has dual
communication modules for the LAN network. The Hot-standby runs when the user sets
Hot_Standby for scheme switch [RedundantMode]†.

†Note: When the user wishes not to operate Hot-standby, or the network is not ready for
the redundant, set Fixed for the [RedundantMode]. Port B (located at C12 if
provided) can only operate for the connection with the engineering tool (GR-
TIEMS®) or the PLC editor (MULTIPLOG®).
‡Note: See Chapter Technical description: Signal processing and communication
module.

(i) Overview
For the Hot-standby communication, the first communication module for Network is used as
the primary port, (i.e. Port A at C11) while a second communication module for Network, (i.e.
Port B at C12) is used as the secondary port; the IED will communicate using Port A for normal
operation. If a communications failure occurs at Port A, the IED can automatically switch
communication from Port A to Port B.

When the IED detects the occurrence of a communications failure, for which the LAN
module is unable to respond to the IED (i.e. a communications link is down), the IED starts a
timer. When the timer exceeds a setting [DownTime], the IED will switch ports. Thus, Port B
is then used for communications. (Note that Port A can be determined to be the secondary port
on the occurrence of the failure. If Port B is unable to continue to operate, then Port A will be
re-switched to run after a predetermined setting [UpTime]. Then, Port B will be discriminated
as the secondary port.)

(ii) Primary port selection


The user can select any one of the ports to be the primary port although the Port A is normally
used as the primary port. For example, provided that both Port A and Port B are physically
connected to the LAN, when the user wishes to use Port B as the primary port, the user should
set Port2(i.e., Port B) for the [PrimaryPort]. If the user wishes not to select the primary port,
set None for the [PrimaryPort].

(iii) Llink-down timer


As mentioned earlier, the occurrence of a communication failure is determined when the timer
exceeds the setting [DownTime]. Thus, the user should set a time setting for this decision.

GRL200 (Soft 033 & 037)


- 1284 -
6F2S1914 (0.37)

(iv) Link-up timer


Another timer is provided in the Hot-standby function. Let us assume that the communication
on Port A is changed to Port B. If the failure of Port A is removed after changing to Port B, the
IED will try to re-start using Port A as the primary port. In this case, the user can define a
time to revert to the original port and re-start communication on the original port by applying
a re-start time for setting [UpTime].

Table 11.2-2 Summary of Hot-standby communication setting


Setting Items Range Meaning Default
Fixed / Fixed: Hot-standby is not activated..
RedundantMode Fixed
Hot_Standby Hot_Standby: Hot-standby activated.
A timer starts upon the occurrence of the communication
DownTime 0–10000ms failure (link down). The standby port commences 5ms
communication in the DownTime.
Selection of priority port
None / Port1 / None: No selection for the priority port.
PrimaryPort None
Port2 Port1: Port A selected as the priority port.
Port2: Port B selected as the priority port.
A timer starts when the primary port is ready to commence
UpTime 0–10000ms 5ms
communication after switching port.

The user should be aware of the following three facts prior to the Hot-standby operation:
1 The IED uses the IP/MAC address of Port A for the Hot-standby operation. The
IP/MAC address of Port B is not used even if communication is carried out on Port
B.
2 The user should ensure that an optical fiber is correctly connected when a 100Base-
FX module is used, otherwise a repeat communication failure (link-down) will be
experienced continuously. If the period for which the link-down is shorter than the
setting [DownTime], another port cannot be switched as the primary port. Thus,
the user should determine the setting value to be applied for [DownTime] on the
basis of the system requirement. It is allowable for the user to apply a setting of
zero for [DownTime] so that the switching of the ports will be performed
immediately; conversely, the user can set any value less than 3000ms in order that
the system need not experience chattering failures if the optical fiber were not
connected securely. Switching between the primary and the secondary ports is not
carried out during a value is setting for the [DownTime]. The user should consider
the setting approach for [UpTime] in the same manner as when setting [DownTime].
3 The auto-negotiation function is executed when the 100Base-TX modules establish
communication over the communications network. The auto-negotiation function
selects a mode for communication; the auto-negotiation function adjusts the
communication speed. In the case of a link-down condition, the auto-negotiation

GRL200 (Soft 033 & 037)


- 1285 -
6F2S1914 (0.37)

function will run again immediately. The link-down condition continues until auto-
negotiation has been completed (it may continue for 1 or 2 seconds). The user can
apply a setting for [DownTime] for any value of time less than that required by the
auto-negotiation function in response to the system requirement (i.e. the user can
set [DownTime] to be zero milliseconds). In this case, switching between the
primary and secondary ports is performed immediately i.e. prior to the auto-
negotiation function running. If switching between ports is not required before the
completion of the auto-negotiation function, the user can set the setting
[DownTime] longer than the time required by the auto-negotiation function. The
user can consider the setting for [UpTime] in the same manner as when setting
[DownTime].

(v) PLC switching


Compulsory signals may be used to switch the ports. For example, if a compulsory signal is
issued via PLC connection point “CH1_CH_CHG”, communication is switched from Port A to
Port B. On the other hand, changing from Port B to Port A can be executed upon the reception
of a signal via PLC signal “CH2_CH_CHG”.

(vi) Monitor
LCD screen: The user can examine the statuses about the communion modules by
the monitoring function. Figure 11.2-2 shows the port status about the modules; terms
‘Up’ and ‘Down’ mean running and stopping, respectively. For menus operations, see
Chapter User interface: Monitoring sub-menu.

PortStatus PortStatus
10:48 1/2 10:48 1/2
*Port1_Link UP *Port1_Link UP
Port2_Link DOWN Port2_Link UP

Port 1 (i.e., Port A) is connected. Ports 1&2 (i.e., Port A&B) are connected.
Port 2 (i.e., Port B) is not connected.

Figure 11.2-2 Communication status

Status signals for Port A and Port B: The user can also examine the LAN status
using PLC signal monitoring points ‘Port1_Link (3100061001)’ and ‘Port2_Link
(3100061001)’ of the HOTST function. For example, when the user wishes to monitor
the status of the Prot1_Link, use the ‘Port1_Link’. Consequently, the user can get the
physical information about the Port A: the value ‘1’ is issued when the communication

GRL200 (Soft 033 & 037)


- 1286 -
6F2S1914 (0.37)

is made (Linkup), whereas value ‘0’ is issued when the communication is not made
(Linkdown).

When Hot_Standby is set for the [RedundantMode], the user can find a running port
using the PLC signal monitoring point ‘Using_CH (3100081001)’ of the HOTST
function. Value ‘1’ is provided when the Port A is running, whereas value ‘2’ is
provided when the Port B is running.

Monitor setting: The Hot-standby (HOTST) function can send PING packets to
remote devices thus enabling the Hot-standby function to monitor the state of the
network. The Hot-standby function checks for a response signal from the remote
device. If the Hot-standby function does not receive a response signal, the Hot-
standby function will switch to the other port. The operation is performed when
the user sets the [RedundantMode]= Hot_Standby and [NetMonitor_EN] = On.

Settings [Ping_IP1] to [Ping_IP12] are provided in the Hot-standby function for the
monitoring of remote devices on the network. When the user sets plural remote IP
addresses for the settings [Ping_IP*], and if the Hot-standby function does not receive
a response from any one of these remote devices, the Hot-standby function determines
that a communication failure has occurred. Table 11.2-3 shows the network
monitoring settings for Hot-standby operation.

Table 11.2-3 Settings network monitoring on Hot-standby


Setting items Range Meaning Default
NetMonitor_EN Off/On Enabling switch for monitoring Off
The user can set twelve IP addresses at 12 remote
Ping_IP1 0.0.0.0
terminals.
to to 0.0.0.0
Value “0.0.0.0”should be set respectively when
Ping_IP12 255.255.255.255
the remote IP addresses are not provided.
Waiting time to PING response; if any one of the
responses is not received, after the setting time
Ping_Wait 1–10 (sec) 1
has elapsed, the function will determine that there
has been no-response.
Interval of PING send; a PING packet is sent
Ping_Interval 1–120 (sec) 5
sequentially in accordance with this setting.
Number of PING packets for checking; the “no-
response “condition is determined when the IED is
unable to obtain a number of responses from the
Chk_Count 1–10 3
same IP address. The user can set the number of
responses required to determine the “no-response”
condition using the setting [Chk_Count].

The user should note that the use of network monitoring could increase the burden
on the network. This is because a number of PING packets are repeatedly transmitted
over the network. Thus, the user should choose the setting values carefully in

GRL200 (Soft 033 & 037)


- 1287 -
6F2S1914 (0.37)

accordance with the network capacity, the burden, and the required time. Examples
1 and 2 below show the respective results using the network monitoring function with
for different settings.

Example1: There is a remote device on the network with the address Ping_IP1.
The Hot-standby function sends ping packets to the remote device every five
seconds; then the Hot-standby function waits for one second until the Hot-
standby function receives a response signal from the remote device. The Hot-
standby function will determine that a communication failure has occurred if two
sequential response signals are not received from the remote device. Subsequently,
the Hot-Standby function will switch from one port to the other port (See Figure
11.2-3). The following settings are required in this example 1:

・ The IP address of the remote device1 is set for setting [Ping_IP1]. (the setting of
IP addresses in the other remote devices is not required.)
・ One second is set for setting [Ping_Wait].
・ Number “5” is set for [Ping_Interval].
・ Number “2” is set for [Check_Count].
Local IED Remote device with
Ping_IP1 address
Ping_Interval Ping_Wait
: 5sec : 1sec Sending Ping Packet for Ping_IP1.

OK: Response received

Sending Ping Packet for Ping_IP1.


1sec

5sec NG: due to delayed response

Sending Ping Packet for Ping_IP1.


1sec

5sec
NG: due to no response
Switching LAN ports is
performed if a response signal is
Sending Ping Packet for Ping_IP1.
not received for setting
[Chk_Count]. 1sec

5sec

Figure 11.2-3 Time chart for Example 1

Example2: It is assumed that there are three remote devices on the network:

GRL200 (Soft 033 & 037)


- 1288 -
6F2S1914 (0.37)

Ping_IP1, Ping_IP2, and Ping_IP3. The Hot-standby function sends a Ping packet to
every remote device every 10 second (i.e., the IED sends a ping packet to a remote
device every 30 second). Suppose that “1” is set for [Check_Count]. The Hot-standby
function can determine a communication failure after 30 seconds if one of the remote
devices is unable to send a response. Figure 11.2-4 shows the operation. Switching is
not executed, because the IED cannot confirm all no-responses from the remote
addresses in the milled of the figure. Switching is performed after no-response is
confirmed from all remote devices.
・ The IP addresses of the remote devices are set for [Ping_IP1] to [Ping_IP3].
(Setting IP addresses for other remote devices is not required.)
・ 10seconds is set for [Ping_Wait].
・ Number “5” is set for [Ping_Interval].
・ Number “1” is set for [Check_Count].

Device with Ping_IP3

Device with Ping_IP2

Device with Ping_IP1


IED
Ping_Interval Ping_Wait
Sending Ping Packet for Ping_IP1.
: 5sec : 10sec
OK: Response received

Sending Ping Packet for Ping_IP2.

5sec

10sec OK: Response received

Sending Ping Packet for Ping_IP3.

5sec
10sec
NG: due to no response

LAN switching is not performed because the IED has not confirmed a response from the IP3.
Sending Ping Packet for Ping_IP1.

5sec NG: due to no response


10sec

Sending Ping Packet for Ping_IP2.


5sec

10sec NG: due to no response

Sending Ping Packet for Ping_IP3.


5sec
10sec
NG: due to no response

LAN switching is performed because the IED has not confirmed all response.

Figure 11.2-4 Time chart for Example 2

GRL200 (Soft 033 & 037)


- 1289 -
6F2S1914 (0.37)

(vii) IP setting example [RedundantMode]=Hot_standby


When Hot_standby is set for the setting [RedundantMode], the user can apply single IP
address in the IED. The table below shows that both Port A and B have the same IP address.
Table 11.2-4 Default IP address for Hot standby operation
GR-TIEMS® /
Protocol IEC61850(GOOSE) SNTP
MULTIPLOG®
IP address at
Port A†
192.168.1.11 192.168.1.11 192.168.1.11
IP address at
Port B†
†Note:Address ‘192.168.1.11’ is set as default. Setting [IPADDRESS2] will be neglected.

(viii) IP setting example [RedundantMode]=Fixed


If Fixed is set for the setting [RedundantMode], the user can apply IP addresses in the IED.
The table below shows that both Port A and B can have different IP addresses.
Table 11.2-5 Default IP address for Fix operation
GR-TIEMS® /
Protocol IEC61850(GOOSE) SNTP
MULTIPLOG®
IP address at
192.168.1.11 192.168.1.11 192.168.1.11
Port A†

IP address at
Not applicable 192.168.1.12‡ 192.168.1.12§
Port B
†Note:Port A ‘192.168.1.11 (default)’ is ready for IEC61850 (GOOSE), but Port B is not
ready for IEC61850.
‡Note: Single IP address is generally set in SNTP. The user is not recommended to have
Time synchronization using different IP addresses with ‘Port A’ and ‘Port B’.
§Note: For the local PC engineering, the use of Port B (192.168.1.12, default) is
recommended, but the user can also use Port A (192.168.1.11, default) for that.

GRL200 (Soft 033 & 037)


- 1290 -
6F2S1914 (0.37)

11.2.3 Redundant LAN (PRP/HSR operation)


The user can allow the IED operate in the redundant LAN communication (IEC 62439-3). To
operate, the user should set either PRP or HSR for scheme switch [RedundantMode].

(i) Overview
‘Parallel redundancy protocol (PRP)’ is designed for double LAN networks in order to construct
high availability automation networks. Figure 11.2-5 shows an IED (i.e., Source, IED1 with
Port A and Port B†) and a server (i.e., Destination, Substation computer with Port A and Port
B). They are connected through LAN_A and LAN_B. For duplicating data, the IED have Link
redundancy entity (LRE) so that the IED can transfer data with A-Frame packet and B-Frame
packet at the same time. At the destination, either frames being arrived later is removed.
Substation computer
CPU
Operator
workstation
Data

Port A Port B

Rx Tx Rx Tx

Destination RedBox‡

A-Frame
LAN_A

B-Frame
LAN_B

TOSHIBA
IN SERVICE
ERROR

Tx Rx Tx Rx
RedBox‡

Port A Port B TOSHIBA


IN SERVICE
ERROR
LAN module LAN module Rx Rx
(C11) (C12) Tx Tx
Port A Port B
TOSHIBA
LAN module LAN module IN SERVICE
Data (C11) (C12) Rx
ERROR

Tx
I Port A
R Data LAN module
L (C11)
CPU I
O Help Cancel ENTER

R
IED1 F1 F2 F3 F4 F5 F6 F7 L Data
CPU
Source O Help Cancel ENTER
I
IED2 F1 F2 F3 F4 F5 F6 F7
R
L
CPU
O Help Cancel ENTER

F1 F2 F3 F4 F5 F6 F7
IED3

Figure 11.2-5 PRP example for redundant LAN_A and LAN_B with DANP
†Note:For the locations about the LAN module, see Chapter Technical description:
Signal processing and communication modules.
‡Note: IED3 and Operator workstation (connected with singly attached node) can join
the network with Redundancy boxes (RedBox).

‘High-availability Seamless redundancy (HSR)’, for the ring topology, is designed to achieve
high reliability communication. Figure 11.2-6 illustrates IEDs connected over the ring LAN.
As doubly ports (Port A and Port B) are embedded in an IED, the IED can transfer the data
packet (A-Frame and B-Frame) for the destination over the ring LAN.

GRL200 (Soft 033 & 037)


- 1291 -
6F2S1914 (0.37)

Source Destination
TOSHIBA
IED1 IN SERVICE
ERROR Substation Computer Operator Workstation

CPU CPU
CPU

Data Data

Data
I Port B Port A Port B Port A
R
L Rx Tx Rx Tx Rx Tx Rx Tx
Port B Port A
O Help Cancel ENTER

Rx Tx Rx Tx
F1 F2 F3 F4 F5 F6 F7

B-Frame B-Frame
A-Frame A-Frame A-Frame
Ring LAN1
A-Frame A-Frame
B-Frame B-Frame B-Frame
TOSHIBA TOSHIBA
IN SERVICE
IN SERVICE
ERROR
ERROR
Tx Rx Tx Rx Tx
Rx
Tx
Rx
Port A Port B QuadBox QuadBox Port A Port B
LAN module LAN module LAN module LAN module
(C11) (C12) (C11) (C12)

Data Data
I I
R R
L Ring LAN2 L
CPU CPU
O Help Cancel ENTER
O Help Cancel ENTER

IED2 F1 F2 F3 F4 F5 F6 F7 IED4 F1 F2 F3 F4 F5 F6 F7
A-Frame

B-Frame
TOSHIBA
IN SERVICE
ERROR

Tx Rx Tx Rx
Port A Port B
LAN module LAN module
(C11) (C12)

Data

R
L
CPU
O Help Cancel ENTER

IED3 F1 F2 F3 F4 F5 F6 F7

Figure 11.2-6 HSR example for ring-LAN with DANH


Note: Prohibition symbol () shows the frame is removed by the next terminals.

(ii) LRE switches


The user should set On for both settings [LRE_PortA_EN] and [LRE_PortB_EN] so that the
LRE can duplicate the data for A-Frame and B-Frame.

(iii) Entry Forget Time


Packets are transferred in A-Frame and B-Frame over the LAN. The user should set the
[EntryForgetTime] to delete a duplicated frame listed in the duplicating table. The duplicated
frame will be erased when it stays longer than the setting time.

For Figure 11.2-5 example, the IED1 (Source) duplicates data by the LRE. The duplicated
data (in A and B-Frames) are transferred simultaneously over the LAN_A and LAN_B. In the
meantime, both frames cannot arrive at Substation computer (Destination). If the duplicated
frame is older than the setting [EntryForgetTime], the duplicated frame will be removed.

The [EntryForgetTime] has default 400ms setting, but the user can change it for an
appropriate value among 100 to 10,000ms. The setting value should be taken account of the

GRL200 (Soft 033 & 037)


- 1292 -
6F2S1914 (0.37)

time after the entry removed from the duplicate table. The setting value also should be taken
account of the differences of the communication speeds between LANs.

(iv) Supervision
The communication supervisor function is available in PRP and HSR. The user can have
following settings:
Setting [LineCheckInterval]: is the setting of the interval time to send supervision frames
cyclically. The user is able to choice the time among 100ms to 100,000ms, but the
setting has default 2000ms values.
Setting [SV_Dst_MACAddr]: is for a reserved multicast address ’01-15-4E-00-01-xx’. By
default, ‘00’ is set for the ‘xx’. However, if conflict arises, the use can configure to
set any value between 0x00 and 0xFF for the ‘xx’.
Setting [SV_VLAN_EN]: can have On setting when the supervision frame is used in VLAN.
Additionally, the user can set identification specifying the VLAN to which the
supervision frame belongs and the priority of the supervision frame. Use the
settings [SV_VLAN_ID] and [SV_VLAN_Priority]. By default, Off is set for the
[SV_LAN_EN].

(v) Monitor
It is possible for the user to watch the communion statuses about Port A and Port B. Figure
11.2-7 shows the numbers of transferred packets via ports.
RedundantPacketNum
10:48 1/6
PortA_Send 12345
PortA_Recv 12345
PortA_ErrLANID 12345
PortB_Send 12345
PortB_Recv 12345
PortB_ErrLANID 12345

Figure 11.2-7 PRP/HSR status


Note: For the operations, see Chapter User interface: Monitoring sub-menu.
Note: PortA_ErrLANID and PortB_ErrLANID do not increase in HSR, because the both
can receive A-frame and B-frame.
PortA_Send: is the number of sending packets for ‘LAN_A’.
PortA_Recv: is the actual number of receiving packets from ‘LAN_A’.
PortA_ErrLANID: is the number of errors that receives packets coming from ‘LAN_B’
PortB_Send: is the number of sending packets for ‘LAN_B’.
PortB_Recv: is the actual number of receiving packets from ‘LAN_B’.
PortB_ErrLANID: is the number of errors that packets coming from ‘LAN_A’.

GRL200 (Soft 033 & 037)


- 1293 -
6F2S1914 (0.37)

(vi) IP setting example [RedundantMode]=PRP or HSR


When PRP or HSR is set for the setting [RedundantMode], the user can apply single IP address
in the IED. The table below shows that both Port A and B have the same IP address.
Table 11.2-6 Default IP address for PRP/HSR operation
GR-TIEMS® /
Protocol IEC61850(GOOSE) SNTP
MULTIPLOG®
IP address at
Port A†
192.168.1.11 192.168.1.11 192.168.1.11
IP address at
Port B†
†Note:Address ‘192.168.1.11’ is set as default. Either port A or B is allowed to operate.

GRL200 (Soft 033 & 037)


- 1294 -
6F2S1914 (0.37)

11.2.4 Redundant LAN (RSTP operation)


Rapid Spanning Tree Protocol (RSTP), defined in the IEEE 802.1D, is ready to operate in the
IED, when the user set RSTP for scheme switch [RedundantMode].

(i) Overview
‘Rapid Spanning Tree Protocol (RSTP)’ is designed to achieve LAN bridge connections in stable.
The RSTP choose one of bridges as the root and BPDU data (called ‘Bridge Protocol Data Unit)
is exchanged periodically over RPST network. Each bridge can listen and learn the BPDU data
so that all bridges in the network can find the shortest path for the root location (we call it
“Path-cost”). Consequently, the RTSP operation clear and recover the network failure if
occurred; no temporary loop will not occur in the network (that is, all terminals can have loop-
free LAN).

(ii) Parameters
When RSTP is set for the [RedundantMode], the user should enter several PSTP parameters
so that the IED is able to enjoy the Spanning Tree topology by the RSTP:
Setting [BridgeHelloTime]: is used to set a BPDU transferring cycle for other terminals
(i.e., BPDU sending interval; they are sent for IEDs, Network bridges, etc.)

Setting [BridgeMaxAge]: instructs the terminal (IED) to listen to a BPDU cyclically. When
a terminal (IED) cannot listen to BPDUs within the setting, the terminal (IED) starts the
computation to make new spanning tree.

Setting [BridgePrioriy]: is allowed for the user to make priority tables in the IEDs. When
a terminal has the smallest number, the terminal can become the root bridge with high
possibility Note that a number can be set in 4096 steps.

Setting [BridgeFedDelay]: is the time to wait for Listening and Learning.

Note: the user shall take the above settings based on the IEEE 802.1w equations below:

2× [BridgeFwdDelay] − 1.0𝑠𝑒𝑐. ≥ [BridgeMaxAge] (11.2-1)

[BridgeMaxAge] ≥ 2 × ([BridgeHellowTime] + 1.0𝑠𝑒𝑐. (11.2-2)

GRL200 (Soft 033 & 037)


- 1295 -
6F2S1914 (0.37)

Settings [PortA_AdminEdge] and [PortA_AutoEdge] †: are provided for a port, which is


able to operate as ‘Edge’. Edge will not be joined for the spanning tree computation, so
Edge port is able to have the communication immediately when the LAN connection is
started (link-up; Notice that the user has to know that no loop will occur in the network,
in advance). When On is set for the [PortA_AdminEdge], the Port A unconditionally
operates as Edge. PortA can detect Edge port itself, when On is set for the
[PortA_AutoEdge].

Setting [PortA_PathCost]: is used to set the distance for the root bridge (path cost), when
the port is used in the LAN network, actually. As a rule, the setting value depends on the
communication bandwidth.

Setting [PortA_Priority]: is set a priority value for the port. Similar to the setting
[BridgePrioriy], a port having the smallest number can have the highest priority. Note
that a number can be set in 16 steps

†Note: Port A (connection for LAN_A) is located at C11 of IED. The second Port B
(connection for Port B) is located at C12 and has similar settings. See Table 11.2-6
for the IP addresses examples. The user can find the contents about LAN
communication module in Chapter Technical description: Signal processing and
communication module.

GRL200 (Soft 033 & 037)


- 1296 -
6F2S1914 (0.37)

11.2.5 Settings
Setting of TCPIP_DRV (Function ID: 230201)
Setting item Range Units Contents Default setting value Notes
IPADDRESS1 0 – 255 – First IP address in the local IED 192.168.1.11
Port A SUBNETMASK1 0 – 255 – Subnet mask 255.255.255.1
GATEWAY1 0 – 255 – Gateway 192.168.1.1
IPADDRESS1 0 – 255 – Second IP address in the local IED 192.168.1.11
Port B SUBNETMASK1 0 – 255 – Subnet mask 255.255.255.1
GATEWAY1 0 – 255 – Gateway 192.168.1.1

Setting of PRP_HSR(Function ID: 342001)


Setting item Range Units Contents Default setting value Notes
RedundantMode PRP/HSR/RSTP – Selection of either PRP/HSR/RSTP PRP
LRE_PortA_EN Off / On – Administrative action at PortA On
LRE_PortB_EN Off / On – Administrative action at PortB On
P LifeCheckInterval 100-100000 ms How often the node sends PRP_Supervision 2000ms
R 01-15-4E-00-01-00
P SV_Dst_MACAddr to – Destination Mac address of supervision frame 01-15-4E-00-01-00
& 01-15-4E-00-01-FF
H SV_VLAN_EN Off / On – Enable or Disable VLAN of supervision frame Off
S SV_VLAN_ID A 12-bit field specifying the VLAN to which the
0-4094 – 0
R frame belongs
SV_VLAN_Priority 0-7 – VLAN Priority of supervision frame 0
EntryForgetTime 100-10000 ms Entry is removed from the duplicate table 400
BridgeHelloTime 1 - 10 s Sending interval of BPUD from Root Bridge 2
BridgeMaxAge 6 - 40 s Receiving interval of BPUD 20
BridgeFwdDelay 4 - 30 S Waiting times for Listening and Learning 15
BridgePriority 0-61440 (4096steps) - Priority number in Bridge 32768
R PortA_AdminEdge Off / On - Operation of ‘Edge port’ at PortA Off
S PortA_AutoEdge Off / On - Auto detection for ‘Edge port’ at PortA On
T PortA_PathCost 1–200000000 - Root Path Cost at PortA 20000
P PortA_Priority 0 – 240 (16steps) - Priority number at PortA 128
PortB_AdminEdge Off / On - Operation of ‘Edge port’ at PortB Off
PortB_AutoEdge Off / On - Auto detection for ‘Edge port’ at PortB On
PortB_PathCost 1–200000000 - Root Path Cost at PortB 20000
PortB_Priority 0 – 240 (16steps) - Priority number at PortB 128

Setting of REDLAN(Function ID: 340001)


Setting item Range Units Contents Default setting value Notes
Fixed / Enabling Hot-standby operation
RedundantMode – Fixed
Hot_Standby

Setting of HOTST(Function ID: 341001)


Setting item Range Units Contents Default setting value Notes
None / Port1 (Port
PrimaryPort – Selection of the primary port None
A) / Port2 (Port B)
DownTime 0 – 10000 ms Determination time for link-down 5
UpTime 0 – 10000 ms Determination time for link-up 5

GRL200 (Soft 033 & 037)


- 1297 -
6F2S1914 (0.37)

Setting of Net_MONITOR (Function ID: 351001)


Setting item Range Units Contents Default setting value Notes

NetMonitor_EN Off / On – Enable switch for net monitoring Off


Ping_IP1 0 – 255 – Ping address of first target 0.0.0.0
Ping_IP2 0 – 255 – Ping address of second target 0.0.0.0
Ping_IP3 0 – 255 – Ping address of third target 0.0.0.0
Ping_IP4 0 – 255 – Ping address of forth target 0.0.0.0
Ping_IP5 0 – 255 – Ping address of fifth target 0.0.0.0
Net Ping_IP6 0 – 255 – Ping address of sixth target 0.0.0.0
Monitor Ping_IP7 0 – 255 – Ping address of seventh target 0.0.0.0
Ping_IP8 0 – 255 – Ping address of eighth target 0.0.0.0
Ping_IP9 0 – 255 – Ping address of ninth target 0.0.0.0
Ping_IP10 0 – 255 – Ping address of tenth target 0.0.0.0
Ping_IP11 0 – 255 – Ping address of eleventh target 0.0.0.0
Ping_IP12 0 – 255 – Ping address of twelfth target 0.0.0.0
Ping_Wait 1 – 10 sec Ping packet waiting time 1
Ping Ping_Interval 1 – 120 sec Ping packet interval time 5
Chk_Count 1 – 10 sec Number of ping check count 3

GRL200 (Soft 033 & 037)


- 1298 -
6F2S1914 (0.37)

11.2.6 Signals (DataID)


 Signal monitoring points
TCPIP_DRV (Function ID: 230201)
Element ID Name Description
3130001001 CH1_USING Port A is operating

3130011001 CH2_USING Port B is operating

3010001150 MAC1_OCT1 MAC1 address octet 1

3010001151 MAC1_OCT2 MAC1 address octet 2

3010001152 MAC1_OCT3 MAC1 address octet 3

3010001153 MAC1_OCT4 MAC1 address octet 4

3010001154 MAC1_OCT5 MAC1 address octet 5

3010001155 MAC1_OCT6 MAC1 address octet 6

3011001150 MAC2_OCT1 MAC2 address octet 1

3011001151 MAC2_OCT2 MAC2 address octet 2

3011001152 MAC2_OCT3 MAC2 address octet 3

3011001153 MAC2_OCT4 MAC2 address octet 4

3011001154 MAC2_OCT5 MAC2 address octet 5

3011001155 MAC2_OCT6 MAC2 address octet 6

3012001150 MAC3_OCT1 MAC3 address octet 1

3012001151 MAC3_OCT2 MAC3 address octet 2

3012001152 MAC3_OCT3 MAC3 address octet 3

3012001153 MAC3_OCT4 MAC3 address octet 4

3012001154 MAC3_OCT5 MAC3 address octet 5

3012001155 MAC3_OCT6 MAC3 address octet 6

3013001150 MAC4_OCT1 MAC4 address octet 1

3013001151 MAC4_OCT2 MAC4 address octet 2

3013001152 MAC4_OCT3 MAC4 address octet 3

3013001153 MAC4_OCT4 MAC4 address octet 4

3013001154 MAC4_OCT5 MAC4 address octet 5

3013001155 MAC4_OCT6 MAC4 address octet 6

3110101001 RX1_CNT receive packet counter

3110111001 RX1ER_CNT receive error counter

3111101001 RX2_CNT

3111111001 RX2ER_CNT

3110201001 TX1_CNT send packet counter

3110211001 TX1ER_CNT send error counter

3111201001 TX2_CNT

3111211001 TX2ER_CNT

 Signal monitoring points


PRP_HSR (Function ID: 342001)
Element ID Name Description
3211011001 PortA_Send frames sent over A(only HSR tagged or with PRP RCT)

3211021001 PortB_Send frames sent over B(only HSR tagged or with PRP RCT)

3211041001 PortA_ErrLANID frames with wrong LAN id received on Port A

3211051001 PortB_ErrLANID frames with wrong LAN id received on Port B

GRL200 (Soft 033 & 037)


- 1299 -
6F2S1914 (0.37)

 Signal monitoring points


PRP_HSR (Function ID: 342001)
Element ID Name Description
3211061001 PortA_Recv frames received over Port A(only HSR tagged or with PRP RCT)

3211071001 PortB_Recv frames received over Port B(only HSR tagged or with PRP RCT)

 Signal monitoring points


HOTST (Function ID: 341001)
Element ID Name Description
3100061001 Port1_Link LAN_A (Port A) Link Status

3100071001 Port2_Link LAN_B (Port B) Link Status

3100081001 Using_CH LAN (port) information in used

 Connection point on PLC logic


HOTST (Function ID: 341001)
Element ID Name Description
310000E001 CH1_CH_CHG Change to LAN_A (Port A) from LAN_B (Port B)

310001E001 CH2_CH_CHG Change to LAN_B (Port B) from LAN_A (Port A)

 Signal monitoring points


NET_MONITOR (Function ID: 351001)
Element ID Name Description
3121001001 NETMONITOR Change to Network monitoring function

3120001460 Ping_IP1 Decision output of PING1 response w.r.t IP1 address

3120011460 Ping_IP2 Decision output of PING2 response w.r.t IP2 address

3120021460 Ping_IP3 Decision output of PING3 response w.r.t IP3 address

3120031460 Ping_IP4 Decision output of PING4 response w.r.t IP4 address

3120041460 Ping_IP5 Decision output of PING5 response w.r.t IP5 address

3120051460 Ping_IP6 Decision output of PING6 response w.r.t IP6 address

3120061460 Ping_IP7 Decision output of PING7 response w.r.t IP7 address

3120071460 Ping_IP8 Decision output of PING8 response w.r.t IP8 address

3120081460 Ping_IP9 Decision output of PING9 response w.r.t IP9 address

3120091460 Ping_IP10 Decision output of PING10 response w.r.t IP10 address

31200A1460 Ping_IP11 Decision output of PING11 response w.r.t IP11 address

31200B1460 Ping_IP12 Decision output of PING12 response w.r.t IP12 address

GRL200 (Soft 033 & 037)


- 1300 -
6F2S1914 (0.37)

IEC 61850 communication


Figure 11.3-1 shows a substation automation system (SAS) and a number of IEDs connected
via a Ring LAN (100BASE-FX). The IEDs can have communication with other devices using
the international standard protocol (IEC 61850 standard‡); additionally, the ring network
topology is used to achieve network redundancy in the system. The user should use the GR-
TIEMS to configure the protocol in the IEC 61850 standard. That is, the functions for the
protection, the measurement, monitoring at local and remote, controlling and logging the data
are required to program in the IEC 61850 standard.

Remote
Monitoring
GPS

Communication Substation
Operator Network
Workstation Computer
Engineering
Workstation Printer Router/
Modem

SNTP Ethernet LAN (TCP/IP)

Fiber Optic Ring: 100BASE-FX


CONTROL
MEASUREMENT

GBU GRT GRG GBU GRL GRB GBU GRG GRZ GBU GRT GRL

GOOSE

Figure 11.3-1 SAS network using IEC 61850 protocol

†Note:When applying IEC 61850 communications, the user should map application
signals with the required logical-nodes (LNs) within the IED. In this manual, we
show the application signals as Data IDs; hence, the user is able to connect the
Data IDs with the required LNs using the engineering tool (GR-TIEMS) provided
by Toshiba. For the GR-TIEMS, see Chapter Engineering tool.
‡Note:Before using the IEC 61850 communications feature provided within the IED, the
user should verify its IEC 61850 capability by reviewing both the protocol-
implementation-conformance-statement (PICS) and the model-implementation-

GRL200 (Soft 033 & 037)


- 1301 -
6F2S1914 (0.37)

conformance-statement (MICS). The MICS provides the user with information for
the LNs provided within the IED; the PICS provides the user with information to
enable the IED to communicate with both SAS and other devices. See
Appendix:IEC61850 MICS, PICS, PIXIT and TICS. It explains how the user can
obtain this information.

When TCP/IP operates, the IEDs can communicate with SAS computer, operator
workstation (OWS), engineering workstation (EWS), remote monitoring system, SNTP server.
In the SAS, the communication is served with the method of data transfer:
 Report method of sending event messages like measurement, status, alarm and so on
 GOOSE (Generic Object Oriented Substation Event) method of communication
between IEDs like interlock
 Control method like controlling the circuit breaker (CB), the disconnector (DS), the
selector device (43), the transformer tap (TAP) and so on

GRL200 (Soft 033 & 037)


- 1302 -
6F2S1914 (0.37)

11.3.1 About protocol


The IED dynamically generates Logical Nodes, Data sets and control blocks defined in CID file
upon boot-up. We shall discuss the configuration procedure to set the data in CID files later.

For the IEC 61850 communication, the IED consists of multiple logical devices and logical
nodes. The user should configure the 61850 Data Model to perform a required function for the
protection and control.

Modular approach achieves data transfer between devices in the IEC 61850 standard. All
function in the IEC 61850 network are grouped into smaller objects called Logical Nodes (LNs),
which contains process objects related data and attributes of a logical device protection and
control function. Logical Node Zero (LLN0) represents specific information of the logical device.
Logical Node Physical Device (LPHD) represents specific information of a physical device. A
generic device is called Physical device (PD). The LPHD contains the properties of the PD. A
specific function in the IED is represented as domain specific LN. The domain specific LN
contains the essential function for target devices in the IEC 61850 network.

LN data model defines the abstract syntax and semantics of the information exchanged
between PDs. The relation between data object classes, data types, data attributes and
abstract data objects are provided in the LN data model. The LN data model is mapped to
Manufacturing Message Specification (MMS) and Generic Object Oriented Substation Event
(GOOSE) functions. Table 11.3-1shows the description of LNs.

Table 11.3-1 LN descripion


Actual device
LN Description
corresponding to LN
Logical node zero represents logical device specific Operation state of BCU
LLNO
information State of 43 switch
Logical node physical device represents physical
LPHD BCU,BCPU
device specific information
Domain Domain specific LN represents protection relay
XCBR,CSWI
specific LN specific function
Generic input output logical node is used if essential Based on client
GGIO
signals are not defined in the extended logical nodes. requirements

All LN classes (LLN0 and domain specific LN) receive the mandatory data of the common LN
except LPHD. Table 11.3-2 exemplifies Function, Logical node and Communication service
used in the IEC 61850 communication.

GRL200 (Soft 033 & 037)


- 1303 -
6F2S1914 (0.37)

Table 11.3-2 Function groups in 61850


Examples of IED applications Logical
Functions grouped in to provide protection/control node Communication methods
61850 functions for the power defined in serviced in 61850
system 61850
Overvoltage relay (OV) PTOV Buffered Report
Overcurrent relay (OC) PTOC Buffered Report
Monitor
Trip circuit (TRC) XCBR GOOSE
Generic functions SIMG GOOSE
Control SPOS etc. CSWI Enhanced-security Control
Measurement MMXU Unbuffered Report
Measurement
Harmonics MHAI Unbuffered Report
Time Simple Network Time
NA SNTP
Synchronization Protocol
Figure 11.3-2 shows Physical Model, which is equivalent to the IEC 61850 Model. The Physical
Model illustrates that both the IED and its functions are communicating with the SAS using
the Ethernet. The equivalent IEC 61850 Model represents communication at LNs in both the
PD using different Communication services, which we shall discuss in section 11.3.2.
Monitoring
x Control IED SAS
×
Over current Server / Work
CB Open/Close
relay station
CB Status
Measuring

Monitoring Under voltage


relay Ethernet
Substation

Harmonics
measurement

Measuring
Control / Monitoring Protection function

Physical Model
“Logical Node” “Communication Service”
IEC 61850 Model Physical Device
LN Physical Device

LN LPHD LN
GOOSE
CB XCBR CALH

LN Enhanced-security Control
LN
CSWI
IHMI

LN Buffered Report
LN
CT PTOC
LN IARC
GOOSE
PTRC
LN
Buffered Report
VT PTUV

LN Unbuffered Report
MHAI

LN GOOSE
Binary
SIMG
Input

Figure 11.3-2 Example of Physical model and its equivalent IEC 61850 model

GRL200 (Soft 033 & 037)


- 1304 -
6F2S1914 (0.37)

(i) Legacy IEC61850 (i.e., 61850 Editon1)


It is early edition for the IEC61850 standard. This edition is bundled in all 61850 software.

(ii) 61850 Edition1 with option


When the IED has the IEC61850 Edition1 with Option, the IED can have private object, which
can handle DataUpdate Trigger. For more information, see section 11.3.9.

(iii) 61850 Edition2


When the 61850 edition2 is available in the IED, the IED has LN LGOS, which shall be used
monitoring of GOOSE message. Note that there shall be one instance of LGOS per GOOSE
subscription for a given GOOSE source.

The user can handle LGOS with signals shown in Table 11.3-3. The signals are provided for
mapping in the 61850 Editon2. Figure 11.3-3 shows an example that they are mapped for the
LGOS.

Table 11.3-3 GOOSE message for the monitor or the diagnostic


Signals (Data ID) Signal names Descriptions
305101 7400006470 SUB_GOOSE_MONITOR #0 Monitor/Diagnose GOOSE Message
305101 7400016470 SUB_GOOSE_MONITOR #1 Monitor/Diagnose GOOSE Message
… … …
305101 7400016470 SUB_GOOSE_MONITOR #319 Monitor/Diagnose GOOSE Message

Figure 11.3-3 Example of Editon2 LGOS mapping

GRL200 (Soft 033 & 037)


- 1305 -
6F2S1914 (0.37)

11.3.2 Communication service


All essential data transmission methods are summarized in Abstract communication service
interface (ACSI); the IED application from communication stack is separated by the ACSI. The
user can map an interface to a communication stack using Specific communication service
mapping (SCSM).

The LN contains data list with their attributes based on their functionality in SAS. A
data has a well-defined structure and information of SAS. The data and attributes of the LN
in a logical device are exchanged by the communication services according to IEC 61850
protocol. The communication services are implemented by SCSM using Ethernet TCP/IP
protocol.

(i) Report for SAS


In the IED, ‘report’ is a method of sending status data, alarm data, measurement data and so
on. Using server-client communication, ‘Report’ is a ‘data set’ transferred from the IED to the
SAS. The ‘reports’ generated by the predefined ‘triggers’ are issued regularly in interval; the
‘reports’ are also generated upon a change in the event. The ‘reports’ are grouped into two
types: (1) Buffered-report-control-block and (2) Unbuffered-report-control-block. Note that the
system achieved by the unbuffered-report-service cannot start an event recover function
during the communication failure.

(ii) GOOSE for peer-to-peer communication


‘Generic Object Oriented Substation Event (GOOSE) ’ is a faster method to transfer the data
in ‘Generic substation event (GSE)’ between IEDs. In all IEDs, multicast GOOSE message is
published from the ‘GOOSE_control_block (GCB)’. The GOOSE communication methods are
grouped into two: (1) GOOSE publish and (2) GOOSE subscribe.

The data structures of the GOOSE are illustrated in Table 11.3-4; they are grouped for
the system (say, SAS) and other logical devices (say, a relay); they are used in the applications
in the SAS and the IED.

GRL200 (Soft 033 & 037)


- 1306 -
6F2S1914 (0.37)

Table 11.3-4 Data structures in the GOOSE


Logical Device
Category “System” Other Logical device (e.g., “Relay”)
Data Model System Relay
DataSet “GOOSEDS” LLN0
GGIO1 Ind1..16 GoCB
LLN0 LPHD1
GoCB PTRC
The DataSet “GOOSEDS” is fixed ….
LPHD1
GGIO
Data set Fixed (Not configurable) Configurable
Performance GOOSE data sent communication time GOOSE data sent, communication
is < 3msec time is around 10msec

(iii) System
The data model in the LN named “System” is not allowed to modify (that is, a data model is
fixed; other LN data models are configurable to meet the system requirement). Mapping
signals to the GGIO1 is required when the GOOSE should send data faster.

(iv) Control mode using GOOSE


In the IED, signals generated on the binary output circuit (BO) can be controlled by the SAS,
if the user makes the link between a reviving control message and a control function block that
changes the state of the output element. Four control modes are provided:
DOes: Direct control with normal security (direct-operate)
SBOns: SBO control with normal security (operate-once or operate-many)
DOes: Direct control with enhanced security (direct-operate)
SBOes: SBO control with enhanced security (operate-once or operate-many)

(v) Time synchronization using IEC 61850 protocol / SNTP


SNTP (Simple network time protocol) is used to synchronize clocks of all IEDs in SAS. Time
synchronization is required to maintain common time across all IEDs in the network. This
makes it easier to analyze the Time stamped event data generated by the IEDs in chronological
order. In the system, IEDs are synchronized with the device having precision time source (for
example, GPS).

(vi) File transfer (COMTRADE)


To send data of the disturbance records, file transfer service is used, which is the operated in
COMTRADE format.

GRL200 (Soft 033 & 037)


- 1307 -
6F2S1914 (0.37)

(vii) Manufacturing Message Specification (MMS)


MMS is an application layer protocol that provides data transmission between IEDs, which
performs monitoring and controlling; it can provide reliability for the data transmission. The
MMS operates in the international standardized messaging system that are made of TCP/IP
and Ethernet.

(viii) Generic Substation Events (GSE)


GSE is a control model defined in the IEC 61850 standard; it provides a fast and reliable
method for transferring the event data over the SAS. The GSE provides facility to transfer the
same event message to multiple physical devices using multicast or broadcast service.

GRL200 (Soft 033 & 037)


- 1308 -
6F2S1914 (0.37)

11.3.3 How to manage engineering work


An IED can have multiple logical devices, which represents protection and control functions.
Each logical device has Logical Nodes (LN), Datasets, Report Control Block (RCB), GOOSE
Control Block (GCB), GOOSE Publish and GOOSE Subscribe function. Figure 11.3-4
illustrates the data structure in the IED.

IED

*IEC 61850-7-4
Logical device1 CONTROL
Logical Node

*Set of LN variables REPORT


Logical Node (Event,

VCT Report Measurement)


DataSet
Voltage Control Block
Logical Node
Input / Output Signals

Current
Application
Data Logical device2
BIO ・・・ GOOSE GOOSE
DataSet
Binary
Control Block (outgoing)
Logical Node
Input

Binary
Input
2. Mapping 1. icd(cid)
data
GOOSE
GOOSE subscribe function
(incoming)

3. GOOSE subscribe

Figure 11.3-4 IED Data Structure


To configure an IED data structure, the user should edit the following items using GR-TIEMS.
Figure 11.3-5 shows the flow diagram for IEC 61850 configuration.
 Edit Signal mapping
 Edit Logical Node
 Edit DataSet
 Edit Report Control Block
 Edit GOOSE Control Block
 Edit GOOSE Publish
 Edit GOOSE Subscribe
 Edit Control function

GRL200 (Soft 033 & 037)


- 1309 -
6F2S1914 (0.37)

Connect PC to IED via LAN or USB

Start GR-TIEMS engineering tool

Add Substation, Voltage level, Bay and IED to the project tree
(→cf. sec. 11.3.3(i))

Select an IED to manage IEC61850 configuration file


(→cf. sec. 11.3.3(i))

Choose a required 61850 edition from the pull-down list


(→cf. sec. 11.3.3(ii))

Import ICD/CID file from the selected IED


(→cf. sec.11.3.3(iii))

Map the signals to Logical Nodes


(→cf. sec.11.3.3(iv))

Edit Data set, RCB and GCB


(→cf. sec. 11.3.3(iv))

Edit signals for GOOSE Publish and GOOSE Subscribe


(→cf. sec. 11.3.3(iv))

Write configured data to IED


(→cf. sec.11.3.3(v))

Figure 11.3-5 Flow diagram

GRL200 (Soft 033 & 037)


- 1310 -
6F2S1914 (0.37)

(i) Creating and opening project


Creation of project file
If the user has an existing project, it can be found in user’s project folder. If the
user does not have the project, create a new project. Figure 11.3-6 shows how to
open an existing project or create a new project.

Figure 11.3-6 File menu

Selection of IED
When user’s project has been created or is opened, the user can add new IEDs.
Figure 11.3-7 illustrates new IED has been added on the project tree.

Figure 11.3-7 Adding IED

GRL200 (Soft 033 & 037)


- 1311 -
6F2S1914 (0.37)

(ii) Choice of 61850 edition number


Select IEC 61850 tool from the menu of Configuration tool, as shown in Figure 11.3-8. When
the user can see the edition list†, select a required one from the list‡. Then, the user can see
the edition number at the header on IEC61850 tool screen, or the bottom of the GR-TIEMS
main screen.

Selection of IEC61850 tool

Edition list
Edition 1

Edition1 display

Edition 1-Opetion

Edition1_Option display

Edition 2

Edition2 display

Figure 11.3-8 Choice of IEC61850 edition number


†Note:When the user has purchased the products supporting for Editon1-Option or later
edition, the GR-TIEMS can display the Edition list menu, as shown in Figure
11.3-8; thus, the user should select one from the edition list. However, if neither is
supported in your products, then the menu is not displayed, and default Edition1
will be selected directly. The user can check it through the IED screen if the IED
has Edition1_Option or later edition. See sec 11.3.3(vi) for the confirmation.
Regarding ‘Edition1_Option’, see section 11.3.1(ii) and 11.3.9.
‡Note:Be aware that your edition selection cannot be undone. If you fail to select a
correct one, make the project again. You are not able to change the edition after
the choice.

GRL200 (Soft 033 & 037)


- 1312 -
6F2S1914 (0.37)

Check to see that four engineering screens are appeared:


 Logical Node Screen
 Signal List Screen
 GOOSE Publish Screen
 GOOSE Subscribe Screen

Figure 11.3-9 IEC 61850 screens

GRL200 (Soft 033 & 037)


- 1313 -
6F2S1914 (0.37)

(iii) IEC 61850 configuration files


Substation configuration language (SCL) files are generated by the configuration in the IEC
61850 protocol. The SCL files are used to exchange the configuration data in different
manufacture tools. Two types of files are used for exchanging data in Table 11.3-5.

Table 11.3-5 Types of SCL files


SCL file Description
.ICD This file describes the capabilities of an IED. It contains the
IED Capability Description communication data and function of LN in an IED.
.CID Every device configured for IEC 61850 in the GR-TIEMS tool
Configured IED Description generates a CID file. This file is then written to the IED. This
file contains configuration information of the IED to which it is
connected.

Exporting and Importing CID/ICD file


The user can export or / import a CID/ICD file as a CSV file. The user can edit
the exported CSV file using the MS-EXCEL®; the user can import the edited CSV
file back to the GR-TIEMS. Figure 11.3-10 shows the options available to
import/export CID/ICD file. The user can either click the icons on the menu bar
or select the required option form the File menu drop down list.

Import CID/ICD
Export CID
Export ICD

Figure 11.3-10 Export / Import of CID / ICD file

Manage third party CID file


The GR-TIEMS can have third party CID file. In the project tree of the GR-TIEMS,
the user can use the device information for creating a third Party IED. To
configure dataset, RCB, GCB, GOOSE publish and GOOSE subscribe settings
and so on, the data attributes are used after the creation of the data.

Mapping application data in IEC 61850


For any IED, the IEC61850 configuration* is available by default. The user

GRL200 (Soft 033 & 037)


- 1314 -
6F2S1914 (0.37)

should check whether the required signals are mapped in the default
configuration.

*Note: There is no default configuration for GOOSE subscription. If GOOSE subscribe


function is required, then a new configuration has to be done.

To verify the signals configured for the IEC 61850 protocol, the user should check
the mapped data, Dataset or Report Control list. If they have existed, the signals
in the signal list should be matched with the attributes of LNs.

Figure 11.3-11 shows an example to check if the signals are mapped in default
configuration. For example, to check for mapping of the primary element signal
in earth fault protection (EF1), follow the steps below:
1. To check if the EF1 signal is already mapped in the LN, key ‘EF1’ under Signal
Name in the Signal List screen.

Mapped data

“EF1” in signal list

Figure 11.3-11 Signal mapping


As shown in the above figure, the “EF1” signal is already mapped to LN
attribute Prot/EF_PTOC1$Str1, general.

2. To check if “Prot/EF_PTOC1$Str1, general” is already added in Dataset. Right


click on “LLN0” and select Edit DataSet, then DataSet List screen appears as
shown in Figure 11.3-12.

GRL200 (Soft 033 & 037)


- 1315 -
6F2S1914 (0.37)

Figure 11.3-12 DataSet list

As shown in the above figure, “Prot/EF_PTOC1$Str1, general” is already


mapped in the Dataset “STAT1”.

3. To check, if the DataSet is already assigned to RCB, Right click on “LLN0” and
select Edit Report Control, then Report Control List screen appears as shown in
Figure 11.3-13.

Figure 11.3-13 Report Control List


As shown in the above figure, the DataSet “STAT1” is already assigned to
RCB “brcbST-A”.

GRL200 (Soft 033 & 037)


- 1316 -
6F2S1914 (0.37)

(iv) Mapping signals in signal list to Logical Nodes


The user can add or modify signal mapping to the LN variable. The following section describes
how to modify the mapped data if the user wants to add signals, which are sent using Report
or GOOSE.

Edit Mapping Data


1. Search the signal to be sent from the Signal List window as shown in Figure
11.3-14.
2. Drag and Drop the selected signal to the logical node variable.

Mapped data

Drop

Drag
Signals

Figure 11.3-14 Signal mapping


Note: To optimize the performance of the IED, “Period” should be 100 if the signal is not
required to be sent immediately.
“301001 3110041005 (Qual_Validity)” should be mapped to “q” with Period=100.
“200301 9010001006 (SYS_TIME)” should be mapped to “t”.

Export / Import Mapping Data


The user can export mapped data in the CSV file; the user can edit the exported
CSV file by the MS-Excel® and import back into the GR-TIEMS. Figure 11.3-15
shows the export / import options.

Export Mapping Data


Import Mapping Data

Figure 11.3-15 Export / Import mapping data

GRL200 (Soft 033 & 037)


- 1317 -
6F2S1914 (0.37)

Edit Logical Node


If the required LN or variable is not available in the IED, the user should follow the
steps below to add or modify the Logical Node:
1. To add new LN or to edit the variable of an existing LN, Right click Prot and
select Add Logical Node or select Edit Logical Node.
2. In the Edit Logical Node screen, select LN Class, Prefix and LN Instance and
check the required variable check boxes as shown in Figure 11.3-16 below.

To Add Logical Node

To add optional variable


To choose a proper Logical Node*

Figure 11.3-16 Add or Edit Logical Node

*Note: Refer to IEC 61850-7-4 to choose a proper Logical Node.

GRL200 (Soft 033 & 037)


- 1318 -
6F2S1914 (0.37)

Edit DataSet
Dataset can be edited or a new dataset can be added for the LNs as shown in
Figure 11.3-17. For editing the DataSet, follow the steps below:
1. Right click LLNO and select Edit DataSet, DataSet List window appears as
shown in Figure 11.3-17.
2. Choose the variables to be added to the DataSet and click OK.

Users can choose the existing


Dataset*, or enter a new
DataSet name.

Figure 11.3-17 Edit DataSet screen

*Note: 100 DataSets can be added in the DataSet List and each DataSet can have
maximum of 32 elements.

GRL200 (Soft 033 & 037)


- 1319 -
6F2S1914 (0.37)

Edit Report Control Block (RCB)


Report Control Block (RCB) is used to send report from IEDs to client. If the user
wishes to assign the DataSet to Report Control Block, follow the steps below:
1. Under the LN tree structure, select Prot, Right click LLN0 and select Edit
Report Control. Report Control List screen appears as shown in Figure 11.3-18.
2. Click Add or Edit to add a new dataset or to edit the existing dataset in the
Report Control List window as shown in Figure 11.3-18.

Figure 11.3-18 Edit Report Control screen

GRL200 (Soft 033 & 037)


- 1320 -
6F2S1914 (0.37)

Edit GOOSE Control Block


GOOSE control block is used to exchange information between IEDs. GOOSE
messages are used for interlock operation between IEDs in order to protect the
electrical system. GGIO1 is used for sending high-speed GOOSE messages. The
DataID assigned to GGIO1 is sent within 3ms.

If the user wishes to assign the DataID for GOOSE operation, follow the steps
below:
1. Click GGIO1 and select Ind1 as shown in Figure 11.3-19.
2. Drag and Drop the required signals to be sent by GOOSE.

Note: The user can assign any signal to GGIO1->Ind1~16 for high-speed GOOSE, as
required.

Drop

Drag

Figure 11.3-19 Signal mapping for high speed GOOSE

As shown in the above figure, signals are assigned to “System/GGIO1$Ind1”. The


user can assign signals to other GGIOs (for example, GGIO2, GGIO3 and so on)
which are not meant for high-speed GOOSE operation.

GRL200 (Soft 033 & 037)


- 1321 -
6F2S1914 (0.37)

Edit GOOSE Publish


The signals assigned to GGIO1 variables are published automatically by default.
The GGIO1 data set is fixed and is pre-configured in GOOSE Publish screen. If
the user assign signals to other GGIO variables (for example, GGIO2, GGIO3) for
GOOSE publish operation, then the user needs to add those variables in the
GOOSE Publish screen.

Figure 11.3-20 shows the GOOSE Publish screen, where “System” is fixed and is
not configurable for GGIO1, whereas “Ctrl” (Control) and “Prot” (Protection) are
configurable. The user can add new variables from the “Logical Node” screen to
the GOOSE Publish screen using drag & drop* method. Figure 11.3-20 shows an
example for GOOSE Publish, where “System/GGIO2$Ind1$stVal” is added to the
GOOSE Publish screen.

*Note: Only “stVal” and “q” variables can be added to GOOSE Publish screen.

Drag

Fixed

Drop

Figure 11.3-20 GOOSE Publish

GRL200 (Soft 033 & 037)


- 1322 -
6F2S1914 (0.37)

Edit GOOSE subscribe


GOOSE subscribe function is configured to receive GOOSE messages published
by other IEDs. Figure 11.3-21 exemplifies the GOOSE Subscribe screen; the user
can select the necessary signals to be added. For example, “Bay1 GBU200” is the
current IED; “Bay2 GRZ200” is the other IED. “List 1” is GOOSE publisher of
GRZ200; “List 2” is GOOSE subscriber for GBU200. The user can select the
GOOSE publisher from GRZ200 and add to the GOOSE subscriber of GBU200.

In the example shown below, select the required variable and click Add. Similarly,
the user can delete the variables.

When the user adds a signal to the GOOSE subscribe list from the other IED,
then the same signal is automatically added in the Signal List of the current
IED.

List 2
List 1 List 2

Figure 11.3-21 GOOSE Subscribe


Note: The user can monitor about the GOOSE message on the LCD screen. See sec.
11.3.8.

Edit Control function


The Data IDs (i.e., Signal Number) starting with “5” is used for control function
when the IED has the control function by default. The user should check whether
the required signals are mapped in the default configuration. The user can edit
and add the control signals to the LN as described in section 11.3.3(iv).

In an IED, usually an output Data ID of a protection function is assigned to LN


variable. However, for the control application, the IED is capable of receiving
command from the SAS server. To control a device (such as a circuit breaker), the
input point* (Data ID) in the control application should be configured to receive
commands from the SAS sever (that is, selecting, operating or cancel command).

GRL200 (Soft 033 & 037)


- 1323 -
6F2S1914 (0.37)

For example, to let a device execute “Select”, “Operate” and “Cancel” commands
from the sever through “CSWI4” and transmit the information to an IED, the user
should map an input point (Data ID) to several variables of “CSWI4” (See Figure
11.3-22). Mapping period for Control shall be 100.

*Note: For more information of the input points, see chapter General control function or
Control and monitoring application, if available.

SBOW

Mapping Input DataID

Oper
DEV01_CONTROL_REQ

Cancel

Figure 11.3-22 Control function mapping


To complete the setting for control function, after mapping data, the user needs
to set BI, BO† in the GR-TIEMS ->Setting.

†Note:For more information for the BI, BO, see Chapter Technical description: Binary IO
module.

GRL200 (Soft 033 & 037)


- 1324 -
6F2S1914 (0.37)

(v) Writing the configuration file to IED


When the user has completed editing the configuration files, the user can write the
IEC61850 configuration files, as shown in

Figure 11.3-23 Write to IED


Follow the below steps to write the file in the IED.
1. Save the current project in the PC.
2. Right click on the target IED and select “Write to IED”.
3. Click items to write: Signal list†, GOOSE Subscribe†, CID, and
Mapping Data.
4. Click Write to transfer the files to the IED.

Figure 11.3-24 Selection of CFD writing items


†Note:If GOOSE subscribe operation is required, the user shall select Signal List and
GOOSE Subscribe.

GRL200 (Soft 033 & 037)


- 1325 -
6F2S1914 (0.37)

5. Set communication parameters, if needed.

Figure 11.3-25 Communication parameter settings

6. Confirm the edition number written in the IED.

Note: The user can check the edition number through on the LCD screen. Therefore, the
user should confirm the edition number written in the IED too. See sec. 11.3.3(vi)
to show the LCD screen.

GRL200 (Soft 033 & 037)


- 1326 -
6F2S1914 (0.37)

(vi) Confirmation of the edition number of IEC61850


Figure 11.3-26 shows how to confirm the edition number, if the IED is supporting several
editions of IEC61850. The user can also confirm the version, when the IED is running in
IEC61850 configuration file. For example, in accordance with on the below information of LCD
screen, the IED can handle three editions and the IED is running on the Edition2 (Ed2).

Main Menu Information


10:48 8/10 10:48 1/xx
Record [IED TYPE]
Monitoring G**
Setting -**-***-**-**-**-***
I/O setting -****-***-**
Control [Serial No.]
Time 1234567890
Test [Plant name]
0Information ABCD station
Security Setting [Description]
Login/Logout ABCDEFG
[CP1M Software]
ABCD***
[IEC61850 eng]
G2M8500**
[IEC61850 Support] Information about the IED is
Ed1/Ed1op/Ed2
[IEC61850 Data Model] supporting 61850 editions.
W2GR_200.***
[IEC61850 SCL Ver.] The IED is running based on the
Edition 2(2007B)
[IEC61850 Mapping] edition of 61850 SCL version.
X2GR_00****
[GOOSE Subscribe]
No data

Scroll downward

Figure 11.3-26 Display sample of 61850 edition information


Note: The edition information will be displayed when the IED has several edition
numbers. If the IED does not have Edition 2 or later, the above texts will not be
screened.

GRL200 (Soft 033 & 037)


- 1327 -
6F2S1914 (0.37)

11.3.4 Settings for 61850 communications


(i) Setting time for re-sending GOOSE subscribe information
The user can configure the maximum duration time for the case when the IED fails to re-send
GOOSE subscribe information. Set the time in seconds using setting [GOINT].

(ii) Setting for 61850 authentication


When the IED is to be authenticated for starting the IEC 61850 communications, the user
should set scheme switch [850AUT] On.

(iii) Blocking 61850 communication


If the user does not want the IED to start the IEC 61850 communications, the user should set
scheme switch [850BLK] On.

(iv) Setting ‘keep-alive’ time for TCP


When applying IEC 61850 communications with TCP/IP, the user should set a time for the
‘keep-alive’ signal. The user should set the time in seconds using the setting [850KEEPALIVE].

(v) Setting ‘CommTerm’


If the user wishes to receive a ‘CommTerm’ signal carrying an actual operation time from a
device outside the IED, the user should set scheme switch [TCMD] On. Note that the
‘CommTerm’ signal† will not conform to the IEC 61850 standard when the user turns on this
function. That is, this function can be availed on the server communication provided by
TOSHIBA.

†Note:For example, Figure 11.3-27 shows the signal flow between a substation computer
(SC), an IED and a target device (e.g. CB). If the requirement is to close the CB on
request of the SC, the SC will send the operation command “Operate” to the IED;
the time information (T) is also sent along with the operation command. When
receiving the operation command and observing that the CB has closed, the IED
will send a response signal “CommTerm” to the SC along with the time
information. However, this time information is not the actual operation time of the
CB, but the same time information originally sent with the operation command.
The IEC 61850 standard defines this rule; hence, general operations in the IEC
61850 standard are subject to this rule. However, the server communication
provided by Toshiba is able to accept the actual operation time; hence, the setting
‘CommTerm’ is required in the Toshiba communication. The user should also note
that Off is set for the scheme switch [TCMD] as the default setting.

GRL200 (Soft 033 & 037)


- 1328 -
6F2S1914 (0.37)

Station computer (SC) IED Target device (e.g. CB)

Command “CB closed” Operate+(T)

Command Open
Response

Process Closed
CommTerm+(T) Response

Figure 11.3-27 Example of CB operation flow

(vi) Setting test mode


With regard to the reception test for GOOSE subscribe information, the user can simulate a
bad condition passively by using both GOSNDBLK and GOSUBBLK functions†.

GOOSE sending block (GOSNDBLK)


For the test using the GOOSE sending block function (GOSNDBLK), the user can disable the
IED so that it does not send the GOOSE message. The GOSNDBLK function is useful when
there is a conflict in the communication with another active IED on sending a GOOSE signal.
To block the sending of the GOOSE message, the user should set On for scheme switch
[GOSNDBLK].

GOOSE receive block (GOSUBBLK)


Suppose the user wishes to simulate a bad reception condition with regard to the GOOSE
signal, the user can apply a setting that will prevent an IED from receiving the GOOSE
message from another IED using this test. The user can perform this test using the test setting
On for scheme switch [GOSUBBLK]. Consequently, the IED rejects the GOOSE messages from
other IEDs. The GOOSE receive block function (GOSUBBLK) is also useful for the validation
of switchgear interlocking determination.

†Note:The user may wish to perform bad reception tests from a remote terminal using
the GOSNDBLK function. However, carrying out the GOSNDBLK function at a
remote terminal may influence the overall operation of other IEDs, because
communication packets will not be received from the remote terminal. In order to
avoid the influence, we recommend the user to test bad receptions for a particular
IED using the GOSUBBLK function. As a result, testing will only affect the
particular IED under test i.e. all other terminals will not be influenced by the

GRL200 (Soft 033 & 037)


- 1329 -
6F2S1914 (0.37)

tests.

11.3.5 Selection of IEC61850 protocol among IED embedded protocols


Figure 11.3-28 shows the selection menu for the IEC61850 communication protocol. The user
should set IEC61850 for the [Slave Protocol] so that the IED communication is carried out in
in the IEC61850 standard. Note that the user shall restart the IED (i.e., the IED power should
be cut off and turned on) if the user has switched to the IEC61850 protocol from the others†.

SLAVE PROTOCOL
10:48 1/1
Slave protocol +
IEC61850

Figure 11.3-28 Slave protection for the IEC61850 protocol (on IED setting menu)
†Note:The menu is just screened when the IED has IEC61850 and other communication
protocols ((e.g., IEC60870-5-103 protocol, etc.). The above one will not screened
when the IED has only the IEC61850 protocol.

11.3.6 How to supervise in 61850 communications


The IED can monitor the status of the IEC 61850 communications. Discussions on IEC 61850
communications status monitoring are provided separately. (See Chapter Automatic
supervision)

GRL200 (Soft 033 & 037)


- 1330 -
6F2S1914 (0.37)

11.3.7 Quality signal in 61850 communication


The IED can send the quality signal of the IEC 61850 communications. Table 11.3-6 shows the
structure of the quality signal; a value is set for the ‘Validity’ bits in accordance with ‘Error
level’ in the IED†. ‘Test mode’ bit is set when the IED is set for the test operation‡.
Table 11.3-6 Quality signal in the IEC 61850-7-3
Definitions in the IEC 61850 7-3
Bit(s) Value Definitions in the IED
Attribute Name Attribute Value
Good 00 No error(Level0)†
Serious Error, Serious
Invalid 01
Error(Comm.) (Level1 and Level2)†
0-1 Validity
Reserved 10 Not applicable
Minor Error, Alarm, Warning
questionable 11
(Level3, Level4, Level5)†
2 Overflow – – Not applicable (Default ‘0’ setting)
3 OutofRange – – Not applicable (Default ‘0’ setting)
4 BadReference – – Not applicable (Default ‘0’ setting)
5 Oscillatory – – Not applicable (Default ‘0’ setting)
6 Failure – – Not applicable (Default ‘0’ setting)
7 Olddata – – Not applicable (Default ‘0’ setting)
8 Inconsistent – – Not applicable (Default ‘0’ setting)
9 Inaccurate – – Not applicable (Default ‘0’ setting)
Process 0 ‘0’ setting, unconditionally
10 Source
Substituted 1 Not used
0 Operation in ‘Test mode’
11 Test –
1 Normal operation
12 OperatorBlocked – 0 ‘0’ setting, unconditionally
†Note: For more information about the meanings about the error levels, see Chapter
Automatic supervision: Outline of automatic supervision .
‡Note: The user can change the IED the test mode by the screen operation. See Chapter
User interface: Test sub-menu and Chapter Commissioning and Maintenance.

GRL200 (Soft 033 & 037)


- 1331 -
6F2S1914 (0.37)

11.3.8 Goose monitoring status in 61850 communication


IED is able to monitor the communication using GOOSE packets, which other IEDs have sent
their information via the network. If the IED can receive the GOOSE packets, the IED can
display them on the information list. Figure 11.3-29 illustrates an example of the GOOSE
monitoring list; it shows all IEDs have reported good status (OK) message, except one IED.
GOOSE Monitoring
11:12 1/320 Signal names
GRZ200_Bay1 OK SUB_QUAL#0
GRT200_Bay1 OK SUB_QUAL#1
GRD200_Bay1 OK SUB_QUAL#2
GRL200_Bay1 NG SUB_QUAL#3
GRZ200_Bay2 OK SUB_QUAL#4
Screen scroll down GRT200_Bay2 OK SUB_QUAL#5
GRD200_Bay2 OK SUB_QUAL#6
GRL200_Bay2 OK SUB_QUAL#7
GRZ200_Bay3 OK SUB_QUAL#8
GRT200_Bay3 OK SUB_QUAL#9
GRD200_Bay3 OK SUB_QUAL#10
GRL200_Bay3 OK SUB_QUAL#11

GRZ200_Bay99 OK SUB_QUAL#316
GRT200_Bay99 OK SUB_QUAL#317
GRD200_Bay99 OK SUB_QUAL#318
GRL200_Bay99 OK SUB_QUAL#319

Figure 11.3-29 Screen example of GOOSE Monitoring


Note: The IED shall be managed with own subscription information to receive the
GOOSE packets regarding the other IEDs. Thus, the user should edit the
subscription contents (see Figure 11.3-21). The LCD displays the statuses based
on that the user has edited the list of the subscription contents.
Note: Jump to Monitoring sub-menu (see Chapter User interface) to display the GOOSE
mentoring screen. The user can also find the GOOSE information on the test
screen on GR-TIEMS.

On the LCD screen, the user can find either OK or NG message regarding other IEDs. The
OK/NG message is generated with the information of the GOOSE packet received. Table 11.3-7
illustrates the messages displayed on LCD screen and GR-TIEMS screen.

GRL200 (Soft 033 & 037)


- 1332 -
6F2S1914 (0.37)

Table 11.3-7 GOOSE statutes and signal outputs


Signal values LCD screen messages GR-TIEMS screen messages
0x0000 OK GOOD
0xC000 NG QUESTIONABLE
0xC010 NG QUESTIONABLE | TEST
0xC040 NG QUESTIONABLE | INACCURATE
0xC080 NG QUESTIONABLE | INCONSISTENT

If the user wishes to see the GOOSE outputs except the LCD screen, the user can find the
outputs through user’s PLC logic, but the user should build it using the PLC function by
selecting a signal in Table 11.3-8. For example, in order to get GRL200_Bay1 information, the
user should take GOOSE content using SUB_QUAL#3 output.

Table 11.3-8 GOOSE output signals


Data ID Signal names Descriptions
301101 3100001001 SUB_QUAL#0 GOOSE subscription quality status
301101 3100011001 SUB_QUAL#1 GOOSE subscription quality status
301101 3100021001 SUB_QUAL#2 GOOSE subscription quality status
301101 3100031001 SUB_QUAL#3 GOOSE subscription quality status
301101 3100041001 SUB_QUAL#4 GOOSE subscription quality status
~~~ ~~~ ~~~
301101 31013E1001 SUB_QUAL#318 GOOSE subscription quality status
301101 31013F1001 SUB_QUAL#319 GOOSE subscription quality status
Note: The above information is not presented from GR-TIMES engineering.

11.3.9 Feature of IEC61850 Edition1 option


The IED can have Private logical nodes, which are provided in Editon1_option, which are
designed in Toshiba private specification exclusively. The user can select and add the following
Data object:
Table 11.3-9 LD class in Editon1 option
LD Class DO Content
GGIO AnInDatUpd DataUpdate Trigger is provided for general Data
Object. The structure is the same as AnIn.

Note: The option1 is designed to transfer the metering values during the fault on the
IEC61850 Edition1.

GRL200 (Soft 033 & 037)


- 1333 -
6F2S1914 (0.37)

11.3.10 Setting
Setting of 61850(Function ID: 301001)
Unit Default setting
Setting item Range Contents Notes
s value

GOINT 1 to 120 sec. Maximum GOOSE resend interval 2


850BLK Off/On IEC 61850 enable/disable Off
850AUT Off/On Authentication of IEC 61850 association Off
850KEEPALIVE 1 to 120 sec. TCP ‘KeepAlive’ time for IEC 61850 20
TCMD Off/On Set ‘T’ in ‘CommTerm’ as actual Time Off

GRL200 (Soft 033 & 037)


- 1334 -
6F2S1914 (0.37)

11.3.11 Signal (Data ID)


 Monitoring point (for Editio1 and Editon2)
61850 (Function ID: 301001)
Element ID Name Description
0010001001 61850STAT Status of IEC 61850(T:Running, F:Stop)
3100001440 INCOMINGPKT#0 Incoming packet number from IEC 61850 client#0
3100011440 INCOMINGPKT#1 Incoming packet number from IEC 61850 client#1
3100021440 INCOMINGPKT#2 Incoming packet number from IEC 61850 client#2
3100031440 INCOMINGPKT#3 Incoming packet number from IEC 61850 client#3
3100041440 INCOMINGPKT#4 Incoming packet number from IEC 61850 client#4
3100051440 INCOMINGPKT#5 Incoming packet number from IEC 61850 client#5
3100001441 OUTGOINGPKT#0 Outgoing packet number to IEC 61850 client#0
3100011441 OUTGOINGPKT#1 Outgoing packet number to IEC 61850 client#1
3100021441 OUTGOINGPKT#2 Outgoing packet number to IEC 61850 client#2
3100031441 OUTGOINGPKT#3 Outgoing packet number to IEC 61850 client#3
3100041441 OUTGOINGPKT#4 Outgoing packet number to IEC 61850 client#4
3100051441 OUTGOINGPKT#5 Outgoing packet number to IEC 61850 client#5
3100001001 REMOTEPORTNUM#0 Port number of IEC 61850 client #0
3100011001 REMOTEPORTNUM#1 Port number of IEC 61850 client #1
3100021001 REMOTEPORTNUM#2 Port number of IEC 61850 client #2
3100031001 REMOTEPORTNUM#3 Port number of IEC 61850 client #3
3100041001 REMOTEPORTNUM#4 Port number of IEC 61850 client #4
3100051001 REMOTEPORTNUM#5 Port number of IEC 61850 client #5
3110041005 Qual_Validity IEC 61850 validity of quality

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
3110001001 GOOSESUB_STATUS 0 if all GOOSE being subscribed are not subscribed.
3100001001 SUB_QUAL#0 GOOSE subscription quality status
3100011001 SUB_QUAL#1 GOOSE subscription quality status
3100021001 SUB_QUAL#2 GOOSE subscription quality status
3100031001 SUB_QUAL#3 GOOSE subscription quality status
3100041001 SUB_QUAL#4 GOOSE subscription quality status
3100051001 SUB_QUAL#5 GOOSE subscription quality status
3100061001 SUB_QUAL#6 GOOSE subscription quality status
3100071001 SUB_QUAL#7 GOOSE subscription quality status
3100081001 SUB_QUAL#8 GOOSE subscription quality status
3100091001 SUB_QUAL#9 GOOSE subscription quality status
31000A1001 SUB_QUAL#10 GOOSE subscription quality status
31000B1001 SUB_QUAL#11 GOOSE subscription quality status
31000C1001 SUB_QUAL#12 GOOSE subscription quality status
31000D1001 SUB_QUAL#13 GOOSE subscription quality status
31000E1001 SUB_QUAL#14 GOOSE subscription quality status
31000F1001 SUB_QUAL#15 GOOSE subscription quality status

GRL200 (Soft 033 & 037)


- 1335 -
6F2S1914 (0.37)

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
3100101001 SUB_QUAL#16 GOOSE subscription quality status
3100111001 SUB_QUAL#17 GOOSE subscription quality status
3100121001 SUB_QUAL#18 GOOSE subscription quality status
3100131001 SUB_QUAL#19 GOOSE subscription quality status
3100141001 SUB_QUAL#20 GOOSE subscription quality status
3100151001 SUB_QUAL#21 GOOSE subscription quality status
3100161001 SUB_QUAL#22 GOOSE subscription quality status
3100171001 SUB_QUAL#23 GOOSE subscription quality status
3100181001 SUB_QUAL#24 GOOSE subscription quality status
3100191001 SUB_QUAL#25 GOOSE subscription quality status
31001A1001 SUB_QUAL#26 GOOSE subscription quality status
31001B1001 SUB_QUAL#27 GOOSE subscription quality status
31001C1001 SUB_QUAL#28 GOOSE subscription quality status
31001D1001 SUB_QUAL#29 GOOSE subscription quality status
31001E1001 SUB_QUAL#30 GOOSE subscription quality status
31001F1001 SUB_QUAL#31 GOOSE subscription quality status
3100201001 SUB_QUAL#32 GOOSE subscription quality status
3100211001 SUB_QUAL#33 GOOSE subscription quality status
3100221001 SUB_QUAL#34 GOOSE subscription quality status
3100231001 SUB_QUAL#35 GOOSE subscription quality status
3100241001 SUB_QUAL#36 GOOSE subscription quality status
3100251001 SUB_QUAL#37 GOOSE subscription quality status
3100261001 SUB_QUAL#38 GOOSE subscription quality status
3100271001 SUB_QUAL#39 GOOSE subscription quality status
3100281001 SUB_QUAL#40 GOOSE subscription quality status
3100291001 SUB_QUAL#41 GOOSE subscription quality status
31002A1001 SUB_QUAL#42 GOOSE subscription quality status
31002B1001 SUB_QUAL#43 GOOSE subscription quality status
31002C1001 SUB_QUAL#44 GOOSE subscription quality status
31002D1001 SUB_QUAL#45 GOOSE subscription quality status
31002E1001 SUB_QUAL#46 GOOSE subscription quality status
31002F1001 SUB_QUAL#47 GOOSE subscription quality status
3100301001 SUB_QUAL#48 GOOSE subscription quality status
3100311001 SUB_QUAL#49 GOOSE subscription quality status
3100321001 SUB_QUAL#50 GOOSE subscription quality status
3100331001 SUB_QUAL#51 GOOSE subscription quality status
3100341001 SUB_QUAL#52 GOOSE subscription quality status
3100351001 SUB_QUAL#53 GOOSE subscription quality status
3100361001 SUB_QUAL#54 GOOSE subscription quality status
3100371001 SUB_QUAL#55 GOOSE subscription quality status
3100381001 SUB_QUAL#56 GOOSE subscription quality status
3100391001 SUB_QUAL#57 GOOSE subscription quality status

GRL200 (Soft 033 & 037)


- 1336 -
6F2S1914 (0.37)

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
31003A1001 SUB_QUAL#58 GOOSE subscription quality status
31003B1001 SUB_QUAL#59 GOOSE subscription quality status
31003C1001 SUB_QUAL#60 GOOSE subscription quality status
31003D1001 SUB_QUAL#61 GOOSE subscription quality status
31003E1001 SUB_QUAL#62 GOOSE subscription quality status
31003F1001 SUB_QUAL#63 GOOSE subscription quality status
3100401001 SUB_QUAL#64 GOOSE subscription quality status
3100411001 SUB_QUAL#65 GOOSE subscription quality status
3100421001 SUB_QUAL#66 GOOSE subscription quality status
3100431001 SUB_QUAL#67 GOOSE subscription quality status
3100441001 SUB_QUAL#68 GOOSE subscription quality status
3100451001 SUB_QUAL#69 GOOSE subscription quality status
3100461001 SUB_QUAL#70 GOOSE subscription quality status
3100471001 SUB_QUAL#71 GOOSE subscription quality status
3100481001 SUB_QUAL#72 GOOSE subscription quality status
3100491001 SUB_QUAL#73 GOOSE subscription quality status
31004A1001 SUB_QUAL#74 GOOSE subscription quality status
31004B1001 SUB_QUAL#75 GOOSE subscription quality status
31004C1001 SUB_QUAL#76 GOOSE subscription quality status
31004D1001 SUB_QUAL#77 GOOSE subscription quality status
31004E1001 SUB_QUAL#78 GOOSE subscription quality status
31004F1001 SUB_QUAL#79 GOOSE subscription quality status
3100501001 SUB_QUAL#80 GOOSE subscription quality status
3100511001 SUB_QUAL#81 GOOSE subscription quality status
3100521001 SUB_QUAL#82 GOOSE subscription quality status
3100531001 SUB_QUAL#83 GOOSE subscription quality status
3100541001 SUB_QUAL#84 GOOSE subscription quality status
3100551001 SUB_QUAL#85 GOOSE subscription quality status
3100561001 SUB_QUAL#86 GOOSE subscription quality status
3100571001 SUB_QUAL#87 GOOSE subscription quality status
3100581001 SUB_QUAL#88 GOOSE subscription quality status
3100591001 SUB_QUAL#89 GOOSE subscription quality status
31005A1001 SUB_QUAL#90 GOOSE subscription quality status
31005B1001 SUB_QUAL#91 GOOSE subscription quality status
31005C1001 SUB_QUAL#92 GOOSE subscription quality status
31005D1001 SUB_QUAL#93 GOOSE subscription quality status
31005E1001 SUB_QUAL#94 GOOSE subscription quality status
31005F1001 SUB_QUAL#95 GOOSE subscription quality status
3100601001 SUB_QUAL#96 GOOSE subscription quality status
3100611001 SUB_QUAL#97 GOOSE subscription quality status
3100621001 SUB_QUAL#98 GOOSE subscription quality status
3100631001 SUB_QUAL#99 GOOSE subscription quality status

GRL200 (Soft 033 & 037)


- 1337 -
6F2S1914 (0.37)

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
3100641001 SUB_QUAL#100 GOOSE subscription quality status
3100651001 SUB_QUAL#101 GOOSE subscription quality status
3100661001 SUB_QUAL#102 GOOSE subscription quality status
3100671001 SUB_QUAL#103 GOOSE subscription quality status
3100681001 SUB_QUAL#104 GOOSE subscription quality status
3100691001 SUB_QUAL#105 GOOSE subscription quality status
31006A1001 SUB_QUAL#106 GOOSE subscription quality status
31006B1001 SUB_QUAL#107 GOOSE subscription quality status
31006C1001 SUB_QUAL#108 GOOSE subscription quality status
31006D1001 SUB_QUAL#109 GOOSE subscription quality status
31006E1001 SUB_QUAL#110 GOOSE subscription quality status
31006F1001 SUB_QUAL#111 GOOSE subscription quality status
3100701001 SUB_QUAL#112 GOOSE subscription quality status
3100711001 SUB_QUAL#113 GOOSE subscription quality status
3100721001 SUB_QUAL#114 GOOSE subscription quality status
3100731001 SUB_QUAL#115 GOOSE subscription quality status
3100741001 SUB_QUAL#116 GOOSE subscription quality status
3100751001 SUB_QUAL#117 GOOSE subscription quality status
3100761001 SUB_QUAL#118 GOOSE subscription quality status
3100771001 SUB_QUAL#119 GOOSE subscription quality status
3100781001 SUB_QUAL#120 GOOSE subscription quality status
3100791001 SUB_QUAL#121 GOOSE subscription quality status
31007A1001 SUB_QUAL#122 GOOSE subscription quality status
31007B1001 SUB_QUAL#123 GOOSE subscription quality status
31007C1001 SUB_QUAL#124 GOOSE subscription quality status
31007D1001 SUB_QUAL#125 GOOSE subscription quality status
31007E1001 SUB_QUAL#126 GOOSE subscription quality status
31007F1001 SUB_QUAL#127 GOOSE subscription quality status
3100801001 SUB_QUAL#128 GOOSE subscription quality status
3100811001 SUB_QUAL#129 GOOSE subscription quality status
3100821001 SUB_QUAL#130 GOOSE subscription quality status
3100831001 SUB_QUAL#131 GOOSE subscription quality status
3100841001 SUB_QUAL#132 GOOSE subscription quality status
3100851001 SUB_QUAL#133 GOOSE subscription quality status
3100861001 SUB_QUAL#134 GOOSE subscription quality status
3100871001 SUB_QUAL#135 GOOSE subscription quality status
3100881001 SUB_QUAL#136 GOOSE subscription quality status
3100891001 SUB_QUAL#137 GOOSE subscription quality status
31008A1001 SUB_QUAL#138 GOOSE subscription quality status
31008B1001 SUB_QUAL#139 GOOSE subscription quality status
31008C1001 SUB_QUAL#140 GOOSE subscription quality status
31008D1001 SUB_QUAL#141 GOOSE subscription quality status

GRL200 (Soft 033 & 037)


- 1338 -
6F2S1914 (0.37)

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
31008E1001 SUB_QUAL#142 GOOSE subscription quality status
31008F1001 SUB_QUAL#143 GOOSE subscription quality status
3100901001 SUB_QUAL#144 GOOSE subscription quality status
3100911001 SUB_QUAL#145 GOOSE subscription quality status
3100921001 SUB_QUAL#146 GOOSE subscription quality status
3100931001 SUB_QUAL#147 GOOSE subscription quality status
3100941001 SUB_QUAL#148 GOOSE subscription quality status
3100951001 SUB_QUAL#149 GOOSE subscription quality status
3100961001 SUB_QUAL#150 GOOSE subscription quality status
3100971001 SUB_QUAL#151 GOOSE subscription quality status
3100981001 SUB_QUAL#152 GOOSE subscription quality status
3100991001 SUB_QUAL#153 GOOSE subscription quality status
31009A1001 SUB_QUAL#154 GOOSE subscription quality status
31009B1001 SUB_QUAL#155 GOOSE subscription quality status
31009C1001 SUB_QUAL#156 GOOSE subscription quality status
31009D1001 SUB_QUAL#157 GOOSE subscription quality status
31009E1001 SUB_QUAL#158 GOOSE subscription quality status
31009F1001 SUB_QUAL#159 GOOSE subscription quality status
3100A01001 SUB_QUAL#160 GOOSE subscription quality status
3100A11001 SUB_QUAL#161 GOOSE subscription quality status
3100A21001 SUB_QUAL#162 GOOSE subscription quality status
3100A31001 SUB_QUAL#163 GOOSE subscription quality status
3100A41001 SUB_QUAL#164 GOOSE subscription quality status
3100A51001 SUB_QUAL#165 GOOSE subscription quality status
3100A61001 SUB_QUAL#166 GOOSE subscription quality status
3100A71001 SUB_QUAL#167 GOOSE subscription quality status
3100A81001 SUB_QUAL#168 GOOSE subscription quality status
3100A91001 SUB_QUAL#169 GOOSE subscription quality status
3100AA1001 SUB_QUAL#170 GOOSE subscription quality status
3100AB1001 SUB_QUAL#171 GOOSE subscription quality status
3100AC1001 SUB_QUAL#172 GOOSE subscription quality status
3100AD1001 SUB_QUAL#173 GOOSE subscription quality status
3100AE1001 SUB_QUAL#174 GOOSE subscription quality status
3100AF1001 SUB_QUAL#175 GOOSE subscription quality status
3100B01001 SUB_QUAL#176 GOOSE subscription quality status
3100B11001 SUB_QUAL#177 GOOSE subscription quality status
3100B21001 SUB_QUAL#178 GOOSE subscription quality status
3100B31001 SUB_QUAL#179 GOOSE subscription quality status
3100B41001 SUB_QUAL#180 GOOSE subscription quality status
3100B51001 SUB_QUAL#181 GOOSE subscription quality status
3100B61001 SUB_QUAL#182 GOOSE subscription quality status
3100B71001 SUB_QUAL#183 GOOSE subscription quality status

GRL200 (Soft 033 & 037)


- 1339 -
6F2S1914 (0.37)

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
3100B81001 SUB_QUAL#184 GOOSE subscription quality status
3100B91001 SUB_QUAL#185 GOOSE subscription quality status
3100BA1001 SUB_QUAL#186 GOOSE subscription quality status
3100BB1001 SUB_QUAL#187 GOOSE subscription quality status
3100BC1001 SUB_QUAL#188 GOOSE subscription quality status
3100BD1001 SUB_QUAL#189 GOOSE subscription quality status
3100BE1001 SUB_QUAL#190 GOOSE subscription quality status
3100BF1001 SUB_QUAL#191 GOOSE subscription quality status
3100C01001 SUB_QUAL#192 GOOSE subscription quality status
3100C11001 SUB_QUAL#193 GOOSE subscription quality status
3100C21001 SUB_QUAL#194 GOOSE subscription quality status
3100C31001 SUB_QUAL#195 GOOSE subscription quality status
3100C41001 SUB_QUAL#196 GOOSE subscription quality status
3100C51001 SUB_QUAL#197 GOOSE subscription quality status
3100C61001 SUB_QUAL#198 GOOSE subscription quality status
3100C71001 SUB_QUAL#199 GOOSE subscription quality status
3100C81001 SUB_QUAL#200 GOOSE subscription quality status
3100C91001 SUB_QUAL#201 GOOSE subscription quality status
3100CA1001 SUB_QUAL#202 GOOSE subscription quality status
3100CB1001 SUB_QUAL#203 GOOSE subscription quality status
3100CC1001 SUB_QUAL#204 GOOSE subscription quality status
3100CD1001 SUB_QUAL#205 GOOSE subscription quality status
3100CE1001 SUB_QUAL#206 GOOSE subscription quality status
3100CF1001 SUB_QUAL#207 GOOSE subscription quality status
3100D01001 SUB_QUAL#208 GOOSE subscription quality status
3100D11001 SUB_QUAL#209 GOOSE subscription quality status
3100D21001 SUB_QUAL#210 GOOSE subscription quality status
3100D31001 SUB_QUAL#211 GOOSE subscription quality status
3100D41001 SUB_QUAL#212 GOOSE subscription quality status
3100D51001 SUB_QUAL#213 GOOSE subscription quality status
3100D61001 SUB_QUAL#214 GOOSE subscription quality status
3100D71001 SUB_QUAL#215 GOOSE subscription quality status
3100D81001 SUB_QUAL#216 GOOSE subscription quality status
3100D91001 SUB_QUAL#217 GOOSE subscription quality status
3100DA1001 SUB_QUAL#218 GOOSE subscription quality status
3100DB1001 SUB_QUAL#219 GOOSE subscription quality status
3100DC1001 SUB_QUAL#220 GOOSE subscription quality status
3100DD1001 SUB_QUAL#221 GOOSE subscription quality status
3100DE1001 SUB_QUAL#222 GOOSE subscription quality status
3100DF1001 SUB_QUAL#223 GOOSE subscription quality status
3100E01001 SUB_QUAL#224 GOOSE subscription quality status
3100E11001 SUB_QUAL#225 GOOSE subscription quality status

GRL200 (Soft 033 & 037)


- 1340 -
6F2S1914 (0.37)

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
3100E21001 SUB_QUAL#226 GOOSE subscription quality status
3100E31001 SUB_QUAL#227 GOOSE subscription quality status
3100E41001 SUB_QUAL#228 GOOSE subscription quality status
3100E51001 SUB_QUAL#229 GOOSE subscription quality status
3100E61001 SUB_QUAL#230 GOOSE subscription quality status
3100E71001 SUB_QUAL#231 GOOSE subscription quality status
3100E81001 SUB_QUAL#232 GOOSE subscription quality status
3100E91001 SUB_QUAL#233 GOOSE subscription quality status
3100EA1001 SUB_QUAL#234 GOOSE subscription quality status
3100EB1001 SUB_QUAL#235 GOOSE subscription quality status
3100EC1001 SUB_QUAL#236 GOOSE subscription quality status
3100ED1001 SUB_QUAL#237 GOOSE subscription quality status
3100EE1001 SUB_QUAL#238 GOOSE subscription quality status
3100EF1001 SUB_QUAL#239 GOOSE subscription quality status
3100F01001 SUB_QUAL#240 GOOSE subscription quality status
3100F11001 SUB_QUAL#241 GOOSE subscription quality status
3100F21001 SUB_QUAL#242 GOOSE subscription quality status
3100F31001 SUB_QUAL#243 GOOSE subscription quality status
3100F41001 SUB_QUAL#244 GOOSE subscription quality status
3100F51001 SUB_QUAL#245 GOOSE subscription quality status
3100F61001 SUB_QUAL#246 GOOSE subscription quality status
3100F71001 SUB_QUAL#247 GOOSE subscription quality status
3100F81001 SUB_QUAL#248 GOOSE subscription quality status
3100F91001 SUB_QUAL#249 GOOSE subscription quality status
3100FA1001 SUB_QUAL#250 GOOSE subscription quality status
3100FB1001 SUB_QUAL#251 GOOSE subscription quality status
3100FC1001 SUB_QUAL#252 GOOSE subscription quality status
3100FD1001 SUB_QUAL#253 GOOSE subscription quality status
3100FE1001 SUB_QUAL#254 GOOSE subscription quality status
3100FF1001 SUB_QUAL#255 GOOSE subscription quality status
3101001001 SUB_QUAL#256 GOOSE subscription quality status
3101011001 SUB_QUAL#257 GOOSE subscription quality status
3101021001 SUB_QUAL#258 GOOSE subscription quality status
3101031001 SUB_QUAL#259 GOOSE subscription quality status
3101041001 SUB_QUAL#260 GOOSE subscription quality status
3101051001 SUB_QUAL#261 GOOSE subscription quality status
3101061001 SUB_QUAL#262 GOOSE subscription quality status
3101071001 SUB_QUAL#263 GOOSE subscription quality status
3101081001 SUB_QUAL#264 GOOSE subscription quality status
3101091001 SUB_QUAL#265 GOOSE subscription quality status
31010A1001 SUB_QUAL#266 GOOSE subscription quality status
31010B1001 SUB_QUAL#267 GOOSE subscription quality status

GRL200 (Soft 033 & 037)


- 1341 -
6F2S1914 (0.37)

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
31010C1001 SUB_QUAL#268 GOOSE subscription quality status
31010D1001 SUB_QUAL#269 GOOSE subscription quality status
31010E1001 SUB_QUAL#270 GOOSE subscription quality status
31010F1001 SUB_QUAL#271 GOOSE subscription quality status
3101101001 SUB_QUAL#272 GOOSE subscription quality status
3101111001 SUB_QUAL#273 GOOSE subscription quality status
3101121001 SUB_QUAL#274 GOOSE subscription quality status
3101131001 SUB_QUAL#275 GOOSE subscription quality status
3101141001 SUB_QUAL#276 GOOSE subscription quality status
3101151001 SUB_QUAL#277 GOOSE subscription quality status
3101161001 SUB_QUAL#278 GOOSE subscription quality status
3101171001 SUB_QUAL#279 GOOSE subscription quality status
3101181001 SUB_QUAL#280 GOOSE subscription quality status
3101191001 SUB_QUAL#281 GOOSE subscription quality status
31011A1001 SUB_QUAL#282 GOOSE subscription quality status
31011B1001 SUB_QUAL#283 GOOSE subscription quality status
31011C1001 SUB_QUAL#284 GOOSE subscription quality status
31011D1001 SUB_QUAL#285 GOOSE subscription quality status
31011E1001 SUB_QUAL#286 GOOSE subscription quality status
31011F1001 SUB_QUAL#287 GOOSE subscription quality status
3101201001 SUB_QUAL#288 GOOSE subscription quality status
3101211001 SUB_QUAL#289 GOOSE subscription quality status
3101221001 SUB_QUAL#290 GOOSE subscription quality status
3101231001 SUB_QUAL#291 GOOSE subscription quality status
3101241001 SUB_QUAL#292 GOOSE subscription quality status
3101251001 SUB_QUAL#293 GOOSE subscription quality status
3101261001 SUB_QUAL#294 GOOSE subscription quality status
3101271001 SUB_QUAL#295 GOOSE subscription quality status
3101281001 SUB_QUAL#296 GOOSE subscription quality status
3101291001 SUB_QUAL#297 GOOSE subscription quality status
31012A1001 SUB_QUAL#298 GOOSE subscription quality status
31012B1001 SUB_QUAL#299 GOOSE subscription quality status
31012C1001 SUB_QUAL#300 GOOSE subscription quality status
31012D1001 SUB_QUAL#301 GOOSE subscription quality status
31012E1001 SUB_QUAL#302 GOOSE subscription quality status
31012F1001 SUB_QUAL#303 GOOSE subscription quality status
3101301001 SUB_QUAL#304 GOOSE subscription quality status
3101311001 SUB_QUAL#305 GOOSE subscription quality status
3101321001 SUB_QUAL#306 GOOSE subscription quality status
3101331001 SUB_QUAL#307 GOOSE subscription quality status
3101341001 SUB_QUAL#308 GOOSE subscription quality status
3101351001 SUB_QUAL#309 GOOSE subscription quality status

GRL200 (Soft 033 & 037)


- 1342 -
6F2S1914 (0.37)

 Monitoring point (for Editio1 and Editon2)


GOOSE (Function ID: 301101)
Element ID Name Description
3101361001 SUB_QUAL#310 GOOSE subscription quality status
3101371001 SUB_QUAL#311 GOOSE subscription quality status
3101381001 SUB_QUAL#312 GOOSE subscription quality status
3101391001 SUB_QUAL#313 GOOSE subscription quality status
31013A1001 SUB_QUAL#314 GOOSE subscription quality status
31013B1001 SUB_QUAL#315 GOOSE subscription quality status
31013C1001 SUB_QUAL#316 GOOSE subscription quality status
31013D1001 SUB_QUAL#317 GOOSE subscription quality status
31013E1001 SUB_QUAL#318 GOOSE subscription quality status
31013F1001 SUB_QUAL#319 GOOSE subscription quality status

 Monitoring point (for Edition 2)


GOOSEed2 (Function ID: 305101)
Element ID Name Description
7400006470 SUB_GOOSE_MONITOR#0 Monitor/Diagnose GOOSE Message
7400016470 SUB_GOOSE_MONITOR#1 Monitor/Diagnose GOOSE Message
7400026470 SUB_GOOSE_MONITOR#2 Monitor/Diagnose GOOSE Message
7400036470 SUB_GOOSE_MONITOR#3 Monitor/Diagnose GOOSE Message
7400046470 SUB_GOOSE_MONITOR#4 Monitor/Diagnose GOOSE Message
7400056470 SUB_GOOSE_MONITOR#5 Monitor/Diagnose GOOSE Message
7400066470 SUB_GOOSE_MONITOR#6 Monitor/Diagnose GOOSE Message
7400076470 SUB_GOOSE_MONITOR#7 Monitor/Diagnose GOOSE Message
7400086470 SUB_GOOSE_MONITOR#8 Monitor/Diagnose GOOSE Message
7400096470 SUB_GOOSE_MONITOR#9 Monitor/Diagnose GOOSE Message
74000A6470 SUB_GOOSE_MONITOR#10 Monitor/Diagnose GOOSE Message
74000B6470 SUB_GOOSE_MONITOR#11 Monitor/Diagnose GOOSE Message
74000C6470 SUB_GOOSE_MONITOR#12 Monitor/Diagnose GOOSE Message
74000D6470 SUB_GOOSE_MONITOR#13 Monitor/Diagnose GOOSE Message
74000E6470 SUB_GOOSE_MONITOR#14 Monitor/Diagnose GOOSE Message
74000F6470 SUB_GOOSE_MONITOR#15 Monitor/Diagnose GOOSE Message
7400106470 SUB_GOOSE_MONITOR#16 Monitor/Diagnose GOOSE Message
7400116470 SUB_GOOSE_MONITOR#17 Monitor/Diagnose GOOSE Message
7400126470 SUB_GOOSE_MONITOR#18 Monitor/Diagnose GOOSE Message
7400136470 SUB_GOOSE_MONITOR#19 Monitor/Diagnose GOOSE Message
7400146470 SUB_GOOSE_MONITOR#20 Monitor/Diagnose GOOSE Message
7400156470 SUB_GOOSE_MONITOR#21 Monitor/Diagnose GOOSE Message
7400166470 SUB_GOOSE_MONITOR#22 Monitor/Diagnose GOOSE Message
7400176470 SUB_GOOSE_MONITOR#23 Monitor/Diagnose GOOSE Message
7400186470 SUB_GOOSE_MONITOR#24 Monitor/Diagnose GOOSE Message
7400196470 SUB_GOOSE_MONITOR#25 Monitor/Diagnose GOOSE Message
74001A6470 SUB_GOOSE_MONITOR#26 Monitor/Diagnose GOOSE Message
74001B6470 SUB_GOOSE_MONITOR#27 Monitor/Diagnose GOOSE Message

GRL200 (Soft 033 & 037)


- 1343 -
6F2S1914 (0.37)

 Monitoring point (for Edition 2)


GOOSEed2 (Function ID: 305101)
Element ID Name Description
74001C6470 SUB_GOOSE_MONITOR#28 Monitor/Diagnose GOOSE Message
74001D6470 SUB_GOOSE_MONITOR#29 Monitor/Diagnose GOOSE Message
74001E6470 SUB_GOOSE_MONITOR#30 Monitor/Diagnose GOOSE Message
74001F6470 SUB_GOOSE_MONITOR#31 Monitor/Diagnose GOOSE Message
7400206470 SUB_GOOSE_MONITOR#32 Monitor/Diagnose GOOSE Message
7400216470 SUB_GOOSE_MONITOR#33 Monitor/Diagnose GOOSE Message
7400226470 SUB_GOOSE_MONITOR#34 Monitor/Diagnose GOOSE Message
7400236470 SUB_GOOSE_MONITOR#35 Monitor/Diagnose GOOSE Message
7400246470 SUB_GOOSE_MONITOR#36 Monitor/Diagnose GOOSE Message
7400256470 SUB_GOOSE_MONITOR#37 Monitor/Diagnose GOOSE Message
7400266470 SUB_GOOSE_MONITOR#38 Monitor/Diagnose GOOSE Message
7400276470 SUB_GOOSE_MONITOR#39 Monitor/Diagnose GOOSE Message
7400286470 SUB_GOOSE_MONITOR#40 Monitor/Diagnose GOOSE Message
7400296470 SUB_GOOSE_MONITOR#41 Monitor/Diagnose GOOSE Message
74002A6470 SUB_GOOSE_MONITOR#42 Monitor/Diagnose GOOSE Message
74002B6470 SUB_GOOSE_MONITOR#43 Monitor/Diagnose GOOSE Message
74002C6470 SUB_GOOSE_MONITOR#44 Monitor/Diagnose GOOSE Message
74002D6470 SUB_GOOSE_MONITOR#45 Monitor/Diagnose GOOSE Message
74002E6470 SUB_GOOSE_MONITOR#46 Monitor/Diagnose GOOSE Message
74002F6470 SUB_GOOSE_MONITOR#47 Monitor/Diagnose GOOSE Message
7400306470 SUB_GOOSE_MONITOR#48 Monitor/Diagnose GOOSE Message
7400316470 SUB_GOOSE_MONITOR#49 Monitor/Diagnose GOOSE Message
7400326470 SUB_GOOSE_MONITOR#50 Monitor/Diagnose GOOSE Message
7400336470 SUB_GOOSE_MONITOR#51 Monitor/Diagnose GOOSE Message
7400346470 SUB_GOOSE_MONITOR#52 Monitor/Diagnose GOOSE Message
7400356470 SUB_GOOSE_MONITOR#53 Monitor/Diagnose GOOSE Message
7400366470 SUB_GOOSE_MONITOR#54 Monitor/Diagnose GOOSE Message
7400376470 SUB_GOOSE_MONITOR#55 Monitor/Diagnose GOOSE Message
7400386470 SUB_GOOSE_MONITOR#56 Monitor/Diagnose GOOSE Message
7400396470 SUB_GOOSE_MONITOR#57 Monitor/Diagnose GOOSE Message
74003A6470 SUB_GOOSE_MONITOR#58 Monitor/Diagnose GOOSE Message
74003B6470 SUB_GOOSE_MONITOR#59 Monitor/Diagnose GOOSE Message
74003C6470 SUB_GOOSE_MONITOR#60 Monitor/Diagnose GOOSE Message
74003D6470 SUB_GOOSE_MONITOR#61 Monitor/Diagnose GOOSE Message
74003E6470 SUB_GOOSE_MONITOR#62 Monitor/Diagnose GOOSE Message
74003F6470 SUB_GOOSE_MONITOR#63 Monitor/Diagnose GOOSE Message
7400406470 SUB_GOOSE_MONITOR#64 Monitor/Diagnose GOOSE Message
7400416470 SUB_GOOSE_MONITOR#65 Monitor/Diagnose GOOSE Message
7400426470 SUB_GOOSE_MONITOR#66 Monitor/Diagnose GOOSE Message
7400436470 SUB_GOOSE_MONITOR#67 Monitor/Diagnose GOOSE Message
7400446470 SUB_GOOSE_MONITOR#68 Monitor/Diagnose GOOSE Message
7400456470 SUB_GOOSE_MONITOR#69 Monitor/Diagnose GOOSE Message

GRL200 (Soft 033 & 037)


- 1344 -
6F2S1914 (0.37)

 Monitoring point (for Edition 2)


GOOSEed2 (Function ID: 305101)
Element ID Name Description
7400466470 SUB_GOOSE_MONITOR#70 Monitor/Diagnose GOOSE Message
7400476470 SUB_GOOSE_MONITOR#71 Monitor/Diagnose GOOSE Message
7400486470 SUB_GOOSE_MONITOR#72 Monitor/Diagnose GOOSE Message
7400496470 SUB_GOOSE_MONITOR#73 Monitor/Diagnose GOOSE Message
74004A6470 SUB_GOOSE_MONITOR#74 Monitor/Diagnose GOOSE Message
74004B6470 SUB_GOOSE_MONITOR#75 Monitor/Diagnose GOOSE Message
74004C6470 SUB_GOOSE_MONITOR#76 Monitor/Diagnose GOOSE Message
74004D6470 SUB_GOOSE_MONITOR#77 Monitor/Diagnose GOOSE Message
74004E6470 SUB_GOOSE_MONITOR#78 Monitor/Diagnose GOOSE Message
74004F6470 SUB_GOOSE_MONITOR#79 Monitor/Diagnose GOOSE Message
7400506470 SUB_GOOSE_MONITOR#80 Monitor/Diagnose GOOSE Message
7400516470 SUB_GOOSE_MONITOR#81 Monitor/Diagnose GOOSE Message
7400526470 SUB_GOOSE_MONITOR#82 Monitor/Diagnose GOOSE Message
7400536470 SUB_GOOSE_MONITOR#83 Monitor/Diagnose GOOSE Message
7400546470 SUB_GOOSE_MONITOR#84 Monitor/Diagnose GOOSE Message
7400556470 SUB_GOOSE_MONITOR#85 Monitor/Diagnose GOOSE Message
7400566470 SUB_GOOSE_MONITOR#86 Monitor/Diagnose GOOSE Message
7400576470 SUB_GOOSE_MONITOR#87 Monitor/Diagnose GOOSE Message
7400586470 SUB_GOOSE_MONITOR#88 Monitor/Diagnose GOOSE Message
7400596470 SUB_GOOSE_MONITOR#89 Monitor/Diagnose GOOSE Message
74005A6470 SUB_GOOSE_MONITOR#90 Monitor/Diagnose GOOSE Message
74005B6470 SUB_GOOSE_MONITOR#91 Monitor/Diagnose GOOSE Message
74005C6470 SUB_GOOSE_MONITOR#92 Monitor/Diagnose GOOSE Message
74005D6470 SUB_GOOSE_MONITOR#93 Monitor/Diagnose GOOSE Message
74005E6470 SUB_GOOSE_MONITOR#94 Monitor/Diagnose GOOSE Message
74005F6470 SUB_GOOSE_MONITOR#95 Monitor/Diagnose GOOSE Message
7400606470 SUB_GOOSE_MONITOR#96 Monitor/Diagnose GOOSE Message
7400616470 SUB_GOOSE_MONITOR#97 Monitor/Diagnose GOOSE Message
7400626470 SUB_GOOSE_MONITOR#98 Monitor/Diagnose GOOSE Message
7400636470 SUB_GOOSE_MONITOR#99 Monitor/Diagnose GOOSE Message
7400646470 SUB_GOOSE_MONITOR#100 Monitor/Diagnose GOOSE Message
7400656470 SUB_GOOSE_MONITOR#101 Monitor/Diagnose GOOSE Message
7400666470 SUB_GOOSE_MONITOR#102 Monitor/Diagnose GOOSE Message
7400676470 SUB_GOOSE_MONITOR#103 Monitor/Diagnose GOOSE Message
7400686470 SUB_GOOSE_MONITOR#104 Monitor/Diagnose GOOSE Message
7400696470 SUB_GOOSE_MONITOR#105 Monitor/Diagnose GOOSE Message
74006A6470 SUB_GOOSE_MONITOR#106 Monitor/Diagnose GOOSE Message
74006B6470 SUB_GOOSE_MONITOR#107 Monitor/Diagnose GOOSE Message
74006C6470 SUB_GOOSE_MONITOR#108 Monitor/Diagnose GOOSE Message
74006D6470 SUB_GOOSE_MONITOR#109 Monitor/Diagnose GOOSE Message
74006E6470 SUB_GOOSE_MONITOR#110 Monitor/Diagnose GOOSE Message
74006F6470 SUB_GOOSE_MONITOR#111 Monitor/Diagnose GOOSE Message

GRL200 (Soft 033 & 037)


- 1345 -
6F2S1914 (0.37)

 Monitoring point (for Edition 2)


GOOSEed2 (Function ID: 305101)
Element ID Name Description
7400706470 SUB_GOOSE_MONITOR#112 Monitor/Diagnose GOOSE Message
7400716470 SUB_GOOSE_MONITOR#113 Monitor/Diagnose GOOSE Message
7400726470 SUB_GOOSE_MONITOR#114 Monitor/Diagnose GOOSE Message
7400736470 SUB_GOOSE_MONITOR#115 Monitor/Diagnose GOOSE Message
7400746470 SUB_GOOSE_MONITOR#116 Monitor/Diagnose GOOSE Message
7400756470 SUB_GOOSE_MONITOR#117 Monitor/Diagnose GOOSE Message
7400766470 SUB_GOOSE_MONITOR#118 Monitor/Diagnose GOOSE Message
7400776470 SUB_GOOSE_MONITOR#119 Monitor/Diagnose GOOSE Message
7400786470 SUB_GOOSE_MONITOR#120 Monitor/Diagnose GOOSE Message
7400796470 SUB_GOOSE_MONITOR#121 Monitor/Diagnose GOOSE Message
74007A6470 SUB_GOOSE_MONITOR#122 Monitor/Diagnose GOOSE Message
74007B6470 SUB_GOOSE_MONITOR#123 Monitor/Diagnose GOOSE Message
74007C6470 SUB_GOOSE_MONITOR#124 Monitor/Diagnose GOOSE Message
74007D6470 SUB_GOOSE_MONITOR#125 Monitor/Diagnose GOOSE Message
74007E6470 SUB_GOOSE_MONITOR#126 Monitor/Diagnose GOOSE Message
74007F6470 SUB_GOOSE_MONITOR#127 Monitor/Diagnose GOOSE Message
7400806470 SUB_GOOSE_MONITOR#128 Monitor/Diagnose GOOSE Message
7400816470 SUB_GOOSE_MONITOR#129 Monitor/Diagnose GOOSE Message
7400826470 SUB_GOOSE_MONITOR#130 Monitor/Diagnose GOOSE Message
7400836470 SUB_GOOSE_MONITOR#131 Monitor/Diagnose GOOSE Message
7400846470 SUB_GOOSE_MONITOR#132 Monitor/Diagnose GOOSE Message
7400856470 SUB_GOOSE_MONITOR#133 Monitor/Diagnose GOOSE Message
7400866470 SUB_GOOSE_MONITOR#134 Monitor/Diagnose GOOSE Message
7400876470 SUB_GOOSE_MONITOR#135 Monitor/Diagnose GOOSE Message
7400886470 SUB_GOOSE_MONITOR#136 Monitor/Diagnose GOOSE Message
7400896470 SUB_GOOSE_MONITOR#137 Monitor/Diagnose GOOSE Message
74008A6470 SUB_GOOSE_MONITOR#138 Monitor/Diagnose GOOSE Message
74008B6470 SUB_GOOSE_MONITOR#139 Monitor/Diagnose GOOSE Message
74008C6470 SUB_GOOSE_MONITOR#140 Monitor/Diagnose GOOSE Message
74008D6470 SUB_GOOSE_MONITOR#141 Monitor/Diagnose GOOSE Message
74008E6470 SUB_GOOSE_MONITOR#142 Monitor/Diagnose GOOSE Message
74008F6470 SUB_GOOSE_MONITOR#143 Monitor/Diagnose GOOSE Message
7400906470 SUB_GOOSE_MONITOR#144 Monitor/Diagnose GOOSE Message
7400916470 SUB_GOOSE_MONITOR#145 Monitor/Diagnose GOOSE Message
7400926470 SUB_GOOSE_MONITOR#146 Monitor/Diagnose GOOSE Message
7400936470 SUB_GOOSE_MONITOR#147 Monitor/Diagnose GOOSE Message
7400946470 SUB_GOOSE_MONITOR#148 Monitor/Diagnose GOOSE Message
7400956470 SUB_GOOSE_MONITOR#149 Monitor/Diagnose GOOSE Message
7400966470 SUB_GOOSE_MONITOR#150 Monitor/Diagnose GOOSE Message
7400976470 SUB_GOOSE_MONITOR#151 Monitor/Diagnose GOOSE Message
7400986470 SUB_GOOSE_MONITOR#152 Monitor/Diagnose GOOSE Message
7400996470 SUB_GOOSE_MONITOR#153 Monitor/Diagnose GOOSE Message

GRL200 (Soft 033 & 037)


- 1346 -
6F2S1914 (0.37)

 Monitoring point (for Edition 2)


GOOSEed2 (Function ID: 305101)
Element ID Name Description
74009A6470 SUB_GOOSE_MONITOR#154 Monitor/Diagnose GOOSE Message
74009B6470 SUB_GOOSE_MONITOR#155 Monitor/Diagnose GOOSE Message
74009C6470 SUB_GOOSE_MONITOR#156 Monitor/Diagnose GOOSE Message
74009D6470 SUB_GOOSE_MONITOR#157 Monitor/Diagnose GOOSE Message
74009E6470 SUB_GOOSE_MONITOR#158 Monitor/Diagnose GOOSE Message
74009F6470 SUB_GOOSE_MONITOR#159 Monitor/Diagnose GOOSE Message
7400A06470 SUB_GOOSE_MONITOR#160 Monitor/Diagnose GOOSE Message
7400A16470 SUB_GOOSE_MONITOR#161 Monitor/Diagnose GOOSE Message
7400A26470 SUB_GOOSE_MONITOR#162 Monitor/Diagnose GOOSE Message
7400A36470 SUB_GOOSE_MONITOR#163 Monitor/Diagnose GOOSE Message
7400A46470 SUB_GOOSE_MONITOR#164 Monitor/Diagnose GOOSE Message
7400A56470 SUB_GOOSE_MONITOR#165 Monitor/Diagnose GOOSE Message
7400A66470 SUB_GOOSE_MONITOR#166 Monitor/Diagnose GOOSE Message
7400A76470 SUB_GOOSE_MONITOR#167 Monitor/Diagnose GOOSE Message
7400A86470 SUB_GOOSE_MONITOR#168 Monitor/Diagnose GOOSE Message
7400A96470 SUB_GOOSE_MONITOR#169 Monitor/Diagnose GOOSE Message
7400AA6470 SUB_GOOSE_MONITOR#170 Monitor/Diagnose GOOSE Message
7400AB6470 SUB_GOOSE_MONITOR#171 Monitor/Diagnose GOOSE Message
7400AC6470 SUB_GOOSE_MONITOR#172 Monitor/Diagnose GOOSE Message
7400AD6470 SUB_GOOSE_MONITOR#173 Monitor/Diagnose GOOSE Message
7400AE6470 SUB_GOOSE_MONITOR#174 Monitor/Diagnose GOOSE Message
7400AF6470 SUB_GOOSE_MONITOR#175 Monitor/Diagnose GOOSE Message
7400B06470 SUB_GOOSE_MONITOR#176 Monitor/Diagnose GOOSE Message
7400B16470 SUB_GOOSE_MONITOR#177 Monitor/Diagnose GOOSE Message
7400B26470 SUB_GOOSE_MONITOR#178 Monitor/Diagnose GOOSE Message
7400B36470 SUB_GOOSE_MONITOR#179 Monitor/Diagnose GOOSE Message
7400B46470 SUB_GOOSE_MONITOR#180 Monitor/Diagnose GOOSE Message
7400B56470 SUB_GOOSE_MONITOR#181 Monitor/Diagnose GOOSE Message
7400B66470 SUB_GOOSE_MONITOR#182 Monitor/Diagnose GOOSE Message
7400B76470 SUB_GOOSE_MONITOR#183 Monitor/Diagnose GOOSE Message
7400B86470 SUB_GOOSE_MONITOR#184 Monitor/Diagnose GOOSE Message
7400B96470 SUB_GOOSE_MONITOR#185 Monitor/Diagnose GOOSE Message
7400BA6470 SUB_GOOSE_MONITOR#186 Monitor/Diagnose GOOSE Message
7400BB6470 SUB_GOOSE_MONITOR#187 Monitor/Diagnose GOOSE Message
7400BC6470 SUB_GOOSE_MONITOR#188 Monitor/Diagnose GOOSE Message
7400BD6470 SUB_GOOSE_MONITOR#189 Monitor/Diagnose GOOSE Message
7400BE6470 SUB_GOOSE_MONITOR#190 Monitor/Diagnose GOOSE Message
7400BF6470 SUB_GOOSE_MONITOR#191 Monitor/Diagnose GOOSE Message
7400C06470 SUB_GOOSE_MONITOR#192 Monitor/Diagnose GOOSE Message
7400C16470 SUB_GOOSE_MONITOR#193 Monitor/Diagnose GOOSE Message
7400C26470 SUB_GOOSE_MONITOR#194 Monitor/Diagnose GOOSE Message
7400C36470 SUB_GOOSE_MONITOR#195 Monitor/Diagnose GOOSE Message

GRL200 (Soft 033 & 037)


- 1347 -
6F2S1914 (0.37)

 Monitoring point (for Edition 2)


GOOSEed2 (Function ID: 305101)
Element ID Name Description
7400C46470 SUB_GOOSE_MONITOR#196 Monitor/Diagnose GOOSE Message
7400C56470 SUB_GOOSE_MONITOR#197 Monitor/Diagnose GOOSE Message
7400C66470 SUB_GOOSE_MONITOR#198 Monitor/Diagnose GOOSE Message
7400C76470 SUB_GOOSE_MONITOR#199 Monitor/Diagnose GOOSE Message
7400C86470 SUB_GOOSE_MONITOR#200 Monitor/Diagnose GOOSE Message
7400C96470 SUB_GOOSE_MONITOR#201 Monitor/Diagnose GOOSE Message
7400CA6470 SUB_GOOSE_MONITOR#202 Monitor/Diagnose GOOSE Message
7400CB6470 SUB_GOOSE_MONITOR#203 Monitor/Diagnose GOOSE Message
7400CC6470 SUB_GOOSE_MONITOR#204 Monitor/Diagnose GOOSE Message
7400CD6470 SUB_GOOSE_MONITOR#205 Monitor/Diagnose GOOSE Message
7400CE6470 SUB_GOOSE_MONITOR#206 Monitor/Diagnose GOOSE Message
7400CF6470 SUB_GOOSE_MONITOR#207 Monitor/Diagnose GOOSE Message
7400D06470 SUB_GOOSE_MONITOR#208 Monitor/Diagnose GOOSE Message
7400D16470 SUB_GOOSE_MONITOR#209 Monitor/Diagnose GOOSE Message
7400D26470 SUB_GOOSE_MONITOR#210 Monitor/Diagnose GOOSE Message
7400D36470 SUB_GOOSE_MONITOR#211 Monitor/Diagnose GOOSE Message
7400D46470 SUB_GOOSE_MONITOR#212 Monitor/Diagnose GOOSE Message
7400D56470 SUB_GOOSE_MONITOR#213 Monitor/Diagnose GOOSE Message
7400D66470 SUB_GOOSE_MONITOR#214 Monitor/Diagnose GOOSE Message
7400D76470 SUB_GOOSE_MONITOR#215 Monitor/Diagnose GOOSE Message
7400D86470 SUB_GOOSE_MONITOR#216 Monitor/Diagnose GOOSE Message
7400D96470 SUB_GOOSE_MONITOR#217 Monitor/Diagnose GOOSE Message
7400DA6470 SUB_GOOSE_MONITOR#218 Monitor/Diagnose GOOSE Message
7400DB6470 SUB_GOOSE_MONITOR#219 Monitor/Diagnose GOOSE Message
7400DC6470 SUB_GOOSE_MONITOR#220 Monitor/Diagnose GOOSE Message
7400DD6470 SUB_GOOSE_MONITOR#221 Monitor/Diagnose GOOSE Message
7400DE6470 SUB_GOOSE_MONITOR#222 Monitor/Diagnose GOOSE Message
7400DF6470 SUB_GOOSE_MONITOR#223 Monitor/Diagnose GOOSE Message
7400E06470 SUB_GOOSE_MONITOR#224 Monitor/Diagnose GOOSE Message
7400E16470 SUB_GOOSE_MONITOR#225 Monitor/Diagnose GOOSE Message
7400E26470 SUB_GOOSE_MONITOR#226 Monitor/Diagnose GOOSE Message
7400E36470 SUB_GOOSE_MONITOR#227 Monitor/Diagnose GOOSE Message
7400E46470 SUB_GOOSE_MONITOR#228 Monitor/Diagnose GOOSE Message
7400E56470 SUB_GOOSE_MONITOR#229 Monitor/Diagnose GOOSE Message
7400E66470 SUB_GOOSE_MONITOR#230 Monitor/Diagnose GOOSE Message
7400E76470 SUB_GOOSE_MONITOR#231 Monitor/Diagnose GOOSE Message
7400E86470 SUB_GOOSE_MONITOR#232 Monitor/Diagnose GOOSE Message
7400E96470 SUB_GOOSE_MONITOR#233 Monitor/Diagnose GOOSE Message
7400EA6470 SUB_GOOSE_MONITOR#234 Monitor/Diagnose GOOSE Message
7400EB6470 SUB_GOOSE_MONITOR#235 Monitor/Diagnose GOOSE Message
7400EC6470 SUB_GOOSE_MONITOR#236 Monitor/Diagnose GOOSE Message
7400ED6470 SUB_GOOSE_MONITOR#237 Monitor/Diagnose GOOSE Message

GRL200 (Soft 033 & 037)


- 1348 -
6F2S1914 (0.37)

 Monitoring point (for Edition 2)


GOOSEed2 (Function ID: 305101)
Element ID Name Description
7400EE6470 SUB_GOOSE_MONITOR#238 Monitor/Diagnose GOOSE Message
7400EF6470 SUB_GOOSE_MONITOR#239 Monitor/Diagnose GOOSE Message
7400F06470 SUB_GOOSE_MONITOR#240 Monitor/Diagnose GOOSE Message
7400F16470 SUB_GOOSE_MONITOR#241 Monitor/Diagnose GOOSE Message
7400F26470 SUB_GOOSE_MONITOR#242 Monitor/Diagnose GOOSE Message
7400F36470 SUB_GOOSE_MONITOR#243 Monitor/Diagnose GOOSE Message
7400F46470 SUB_GOOSE_MONITOR#244 Monitor/Diagnose GOOSE Message
7400F56470 SUB_GOOSE_MONITOR#245 Monitor/Diagnose GOOSE Message
7400F66470 SUB_GOOSE_MONITOR#246 Monitor/Diagnose GOOSE Message
7400F76470 SUB_GOOSE_MONITOR#247 Monitor/Diagnose GOOSE Message
7400F86470 SUB_GOOSE_MONITOR#248 Monitor/Diagnose GOOSE Message
7400F96470 SUB_GOOSE_MONITOR#249 Monitor/Diagnose GOOSE Message
7400FA6470 SUB_GOOSE_MONITOR#250 Monitor/Diagnose GOOSE Message
7400FB6470 SUB_GOOSE_MONITOR#251 Monitor/Diagnose GOOSE Message
7400FC6470 SUB_GOOSE_MONITOR#252 Monitor/Diagnose GOOSE Message
7400FD6470 SUB_GOOSE_MONITOR#253 Monitor/Diagnose GOOSE Message
7400FE6470 SUB_GOOSE_MONITOR#254 Monitor/Diagnose GOOSE Message
7400FF6470 SUB_GOOSE_MONITOR#255 Monitor/Diagnose GOOSE Message
7401006470 SUB_GOOSE_MONITOR#256 Monitor/Diagnose GOOSE Message
7401016470 SUB_GOOSE_MONITOR#257 Monitor/Diagnose GOOSE Message
7401026470 SUB_GOOSE_MONITOR#258 Monitor/Diagnose GOOSE Message
7401036470 SUB_GOOSE_MONITOR#259 Monitor/Diagnose GOOSE Message
7401046470 SUB_GOOSE_MONITOR#260 Monitor/Diagnose GOOSE Message
7401056470 SUB_GOOSE_MONITOR#261 Monitor/Diagnose GOOSE Message
7401066470 SUB_GOOSE_MONITOR#262 Monitor/Diagnose GOOSE Message
7401076470 SUB_GOOSE_MONITOR#263 Monitor/Diagnose GOOSE Message
7401086470 SUB_GOOSE_MONITOR#264 Monitor/Diagnose GOOSE Message
7401096470 SUB_GOOSE_MONITOR#265 Monitor/Diagnose GOOSE Message
74010A6470 SUB_GOOSE_MONITOR#266 Monitor/Diagnose GOOSE Message
74010B6470 SUB_GOOSE_MONITOR#267 Monitor/Diagnose GOOSE Message
74010C6470 SUB_GOOSE_MONITOR#268 Monitor/Diagnose GOOSE Message
74010D6470 SUB_GOOSE_MONITOR#269 Monitor/Diagnose GOOSE Message
74010E6470 SUB_GOOSE_MONITOR#270 Monitor/Diagnose GOOSE Message
74010F6470 SUB_GOOSE_MONITOR#271 Monitor/Diagnose GOOSE Message
7401106470 SUB_GOOSE_MONITOR#272 Monitor/Diagnose GOOSE Message
7401116470 SUB_GOOSE_MONITOR#273 Monitor/Diagnose GOOSE Message
7401126470 SUB_GOOSE_MONITOR#274 Monitor/Diagnose GOOSE Message
7401136470 SUB_GOOSE_MONITOR#275 Monitor/Diagnose GOOSE Message
7401146470 SUB_GOOSE_MONITOR#276 Monitor/Diagnose GOOSE Message
7401156470 SUB_GOOSE_MONITOR#277 Monitor/Diagnose GOOSE Message
7401166470 SUB_GOOSE_MONITOR#278 Monitor/Diagnose GOOSE Message
7401176470 SUB_GOOSE_MONITOR#279 Monitor/Diagnose GOOSE Message

GRL200 (Soft 033 & 037)


- 1349 -
6F2S1914 (0.37)

 Monitoring point (for Edition 2)


GOOSEed2 (Function ID: 305101)
Element ID Name Description
7401186470 SUB_GOOSE_MONITOR#280 Monitor/Diagnose GOOSE Message
7401196470 SUB_GOOSE_MONITOR#281 Monitor/Diagnose GOOSE Message
74011A6470 SUB_GOOSE_MONITOR#282 Monitor/Diagnose GOOSE Message
74011B6470 SUB_GOOSE_MONITOR#283 Monitor/Diagnose GOOSE Message
74011C6470 SUB_GOOSE_MONITOR#284 Monitor/Diagnose GOOSE Message
74011D6470 SUB_GOOSE_MONITOR#285 Monitor/Diagnose GOOSE Message
74011E6470 SUB_GOOSE_MONITOR#286 Monitor/Diagnose GOOSE Message
74011F6470 SUB_GOOSE_MONITOR#287 Monitor/Diagnose GOOSE Message
7401206470 SUB_GOOSE_MONITOR#288 Monitor/Diagnose GOOSE Message
7401216470 SUB_GOOSE_MONITOR#289 Monitor/Diagnose GOOSE Message
7401226470 SUB_GOOSE_MONITOR#290 Monitor/Diagnose GOOSE Message
7401236470 SUB_GOOSE_MONITOR#291 Monitor/Diagnose GOOSE Message
7401246470 SUB_GOOSE_MONITOR#292 Monitor/Diagnose GOOSE Message
7401256470 SUB_GOOSE_MONITOR#293 Monitor/Diagnose GOOSE Message
7401266470 SUB_GOOSE_MONITOR#294 Monitor/Diagnose GOOSE Message
7401276470 SUB_GOOSE_MONITOR#295 Monitor/Diagnose GOOSE Message
7401286470 SUB_GOOSE_MONITOR#296 Monitor/Diagnose GOOSE Message
7401296470 SUB_GOOSE_MONITOR#297 Monitor/Diagnose GOOSE Message
74012A6470 SUB_GOOSE_MONITOR#298 Monitor/Diagnose GOOSE Message
74012B6470 SUB_GOOSE_MONITOR#299 Monitor/Diagnose GOOSE Message
74012C6470 SUB_GOOSE_MONITOR#300 Monitor/Diagnose GOOSE Message
74012D6470 SUB_GOOSE_MONITOR#301 Monitor/Diagnose GOOSE Message
74012E6470 SUB_GOOSE_MONITOR#302 Monitor/Diagnose GOOSE Message
74012F6470 SUB_GOOSE_MONITOR#303 Monitor/Diagnose GOOSE Message
7401306470 SUB_GOOSE_MONITOR#304 Monitor/Diagnose GOOSE Message
7401316470 SUB_GOOSE_MONITOR#305 Monitor/Diagnose GOOSE Message
7401326470 SUB_GOOSE_MONITOR#306 Monitor/Diagnose GOOSE Message
7401336470 SUB_GOOSE_MONITOR#307 Monitor/Diagnose GOOSE Message
7401346470 SUB_GOOSE_MONITOR#308 Monitor/Diagnose GOOSE Message
7401356470 SUB_GOOSE_MONITOR#309 Monitor/Diagnose GOOSE Message
7401366470 SUB_GOOSE_MONITOR#310 Monitor/Diagnose GOOSE Message
7401376470 SUB_GOOSE_MONITOR#311 Monitor/Diagnose GOOSE Message
7401386470 SUB_GOOSE_MONITOR#312 Monitor/Diagnose GOOSE Message
7401396470 SUB_GOOSE_MONITOR#313 Monitor/Diagnose GOOSE Message
74013A6470 SUB_GOOSE_MONITOR#314 Monitor/Diagnose GOOSE Message
74013B6470 SUB_GOOSE_MONITOR#315 Monitor/Diagnose GOOSE Message
74013C6470 SUB_GOOSE_MONITOR#316 Monitor/Diagnose GOOSE Message
74013D6470 SUB_GOOSE_MONITOR#317 Monitor/Diagnose GOOSE Message
74013E6470 SUB_GOOSE_MONITOR#318 Monitor/Diagnose GOOSE Message
74013F6470 SUB_GOOSE_MONITOR#319 Monitor/Diagnose GOOSE Message

GRL200 (Soft 033 & 037)


- 1350 -
6F2S1914 (0.37)

IEC 60870-5-103 communication


The IEC 60870-5-103 standard† is one of the communication protocols when measuring data
is required to communicate between the control system and the IED; the communication is
carried out with the RS485 or the Fiber optic interface‡. The following data are transferred by
the IEC 60870-5-103 communication; the user is required create the configuration using the
GR-TIEMS, as cited in the previous section:
• Measured data: current, voltage, active power, reactive power, frequency
• Status data: events, fault indications, etc.

†Note: The selection of the IEC 60870-5-103 communication is dependent on the


ordering code in the communication protocols. For the selection, see Appendix:
Ordering.
‡Note: The selection concerning to the communication module (interface) is
dependent on the ordering in the hardware selection. We shall see the description
with regard to the communication specification in Chapter Technical description:
Signal processing and communication module.

GRL200 (Soft 033 & 037)


- 1351 -
6F2S1914 (0.37)

11.4.1 Overview
For the communication in the IEC 60870-5-103 standard, the user should create the data with
regard the protocol, which is grouped into a slave and a master. The user can edit the slave
Data or the master Data using the GR-TIEMS.

(i) Management
As cited earlier, the IEC 60870-5-103 standard is grouped into the slave and the master. In an
IED the user should select either the master mode or the slave mode; the user should edit
either the master data or the slave Data. The both modes can provide the same functions
equally. The GR-TIEMS can provide the user the management means for the following data.

Data management
Import data are provided in the CSV file. The data are categorized as “adding items”,
“editing items”, “deleting items”, and “arranging items”.

Process management
Creation of the new data
Registration, clear, and change name of a slave IED
Registration and clear of signals
Edition of the dialog prototype
External Interfaces
Logging and Access Security

Manage IEC 60870-5-103 display


Tree view style
List view style

(ii) Configuration†
Table 11.4-1 and Table 11.4-2 show that the items should be programmed using the GR-TIEMS.
We shall see how to set and edit data of the IEC 60870-5-103 configuration in section 11.4.5

†Note:Configuration for the master Data is not available in the GR200-serises.

GRL200 (Soft 033 & 037)


- 1352 -
6F2S1914 (0.37)

Table 11.4-1 Configuration items in IEC 60870-5-103


Items Contents
Type ID(1/2), INF, FUN,
Time-tagged message
Transmission condition(Data ID), COT
INF, FUN, Transmission condition(Data ID),
Time-tagged measurands
COT, Type of measurands quantities
General command INF, FUN, Control condition(Data ID)
Type ID(3/9), INF, FUN, Number of measurands,
Measurands
Type of measurands quantities

Table 11.4-2 Common settings in IEC 60870-5-103


Items Notice
Transmission cycle of
To perform to write the settings in the IED effectively, the
Measurands frame
user should turn off the DC supplying to the IED; then turn
FUN of System function
on the DC again.
Test mode

GRL200 (Soft 033 & 037)


- 1353 -
6F2S1914 (0.37)

11.4.2 Requirements in the Master station


In the master station of the IEC 60870-5-103 standard, the following specifications should be
followed in the respective IEDs:
1) Polling cycle: 150ms or longer
2) Timeout time (time to re-sending the request frame to the IED): 100ms
IEC103 master IED

Data request

Polling cycle: Response frame


150ms or more

Data request

Response frame

Figure 11.4-1 Ping cycles between the master station and the IED

GRL200 (Soft 033 & 037)


- 1354 -
6F2S1914 (0.37)

11.4.3 Interoperability
The IEC 60870-5-103 protocol provides a physical layer and an application layer for the
communication to secure the interoperability.

(i) Physical layer


Either an electrical or an optical interface† is defined in the IEC 60870-5-103 standard.

Electrical interface in the RS-485


A maximum number of 32 relays is possible in the IEC 60870-5-103 standard.

Optic interface
Several optic communication modules are available

†Note:Either interface is provided with a communication module in the IED; the


specification is discussed separately. See chapter Technical description: Signal
processing and communication module.

(ii) Application Layer


The following layers are provided on the application layer:
COMMON ADDRESS of ASDU
One COMMON ADDRESS OF ASDU (identical with station address)

GRL200 (Soft 033 & 037)


- 1355 -
6F2S1914 (0.37)

11.4.4 Communication interface in the IEC 60870-5-103 standard


(i) Spontaneous events
When events are generated in the IED, they are transferred to the master station. The event
transferred is grouped into the Function-type (FUN) and the Information numbers (INF).

(ii) General interrogation1


“GI request” is used when it is required to read the IED status, the Function-types (FUNs),
and the Information numbers (INFs). The status and others are reported during the GI cycle.

(iii) Cyclic measurements


Measured values are cyclically generated using Type ID=3 or 9; they are read in the IED using
a Class 2 poll. The generating rate of new measured values is possible to program.

(iv) Commands2
The user can customize the supported commands. The IED can replay for unsupported
commands using the cause of transmission (COT) negative acknowledgement of a command.

(v) Test mode3


For the process in the control system, both spontaneous messages and polled measured values
are designated by the means in the ‘test mode’ of “CAUSE OF TRANSMISSION”. The means
denoted the ‘test mode’ of “CAUSE OF TRANSMISSION = 7” is normally used for the messages
transmitted with COT=1 (spontaneous) or COT=2 (cyclic).

(vi) Blocking of monitor direction4


If blocking the monitor direction is activated in the protection equipment, all indications and
measurands are never transmitted.

1Note: With regard to the GI list, see Appendix IEC 60870-5-103 interoperability. When
the user wishes to understand the details, refer to the section 7.4.3 of the IEC
60870-5-103 standard.
2Note: For details, refer to the section 7.4.4 of the IEC 60870-5-103 standard.
3Note: For details, refer to the section 7.4.5 of the IEC 60870-5-103 standard.
4Note: For details, refer to the section 7.4.6 of the IEC 60870-5-103 standard.

GRL200 (Soft 033 & 037)


- 1356 -
6F2S1914 (0.37)

11.4.5 Editing data of the configuration


(i) Common setting
When the “Common setting” item is selected on the start screen of the IEC 60870-5-103
configuration, the “Common setting” setting screen is displayed. Settings common to each
frame can be performed in this screen.

Setting file remark


The remark of the setting file is used for managing the version of the configuration data file.
A comment with the maximum of 12 characters can be entered in the box. The comment can
be viewed on the IED screen.

Remote operation valid time


When “Time-tagged message” or “Time-tagged measured” occurs during the period from the
receiving any command (which is provided by “General command” setting) to the setting
time of “Remote Operation valid time”, its COT is set to COT=12 (Remote operation). This
setting for the event is enabled when the COT=12 and COT=1 or 11 are checked in “Time-
tagged message” or “Time-tagged measurand” setting. The setting range of “Remote
Operation valid time” is 0 to 60000ms. The default setting is 4000ms. In the following case,
the “Time-tagged measurand” with COT=12 occurs.

Remote operation valid time = TR[ms]

Command Time tagged measurand with


receive COT=11, 12 checked occurs.

Figure 11.4-2 Time setting for the remote operation

Local operation valid time


When “Time-tagged message” or “Time-tagged measurand” occurs during the period from
the start of local operation (described in 11.4.5(ii)-7) to the setting time of “Local Operation
valid time”, its COT is set to COT=11 (Local operation). This setting for the event is enabled
when the COT=11 and COT=1 or 12 are checked in “Time-tagged message” or “Time-tagged
measurand” setting. The setting range of “Remote Operation valid time” is 0 to 60000ms.
The default setting is 4000ms. In the following case, the “Time-tagged message” with
COT=11 occurs.
Local operation valid time = TL[ms]
(Off-delay time after finish of local operation)

Start of Finish of Time tagged measurand with


local operation local operation COT=1, 11, 12 checked occurs.

Figure 11.4-3 Time setting for the local operation

Measurand period
This setting is used to set the transmission cycle (s) of Measurand frame. The setting range
is 0 to 60s. If no Measurand frame is provided by measurand setting, this setting is disabled.

GRL200 (Soft 033 & 037)


- 1357 -
6F2S1914 (0.37)

Function type of system functions


This setting is used to set Function type (FUN) of System functions† (INF=0 to 5). The FUN
can be set individually per the frame provided. When clicking the “Change all FUNs”,
confirmation dialog box appears. When clicking “OK”, FUNs of all frames are changed to
these setting values.
†Note:We mean the following frames: end of general interrogation, time
synchronization, reset FCB, reset CU, start/restart, power on.

Signal No. of test mode


This setting is used to set a Data ID in the test mode. The relevant Data ID should be
selected from the signal list, which can be found in Chapters “Relay” or “Control and
monitoring” applications. Usually, the default setting is not changed.

The test mode in the IEC 60870-5-103 standard is enabled by the operation on the IED
screen or the GR-TIEMS. When the set signal changes “ON” and Time-tagged message or
Time-tagged measured of spontaneous cause (COT=1) or measurand frame or cyclic
transmission (Type ID=3 or 9) occurs, its COT shifts COT=7 (Test mode).

Signal No. for relative time and fault number


This setting is used to set the trigger signal which is attached the frame of Type ID=2 or 4.
The trigger signal is selected from the signal list. (This setting is not related to the frame of
Type ID=1.)

The time (ms), which is from the establishment of a set signal to the detection of a
status change, is added the set frame as RET value. FAN (Fault number), attached the
frame of Type ID=2 or 4, has the same number during the set signal ON. (Whenever the set
signal is ON, the FAN increases.) When setting to “0”, RET value is always “0” (RET=0).
The default setting is set to the OR signal of elements operation. When Type ID=2 frame is
provided with OC trip as send condition, for example, the time from OC element operation
to OC tripping is attached to the frame as RET. Though, the RET of GI frame is always “0”
in spite of this setting.

In the following case, T1[ms] is attached to i as RET, T2[ms] is attached to ii ,


and T3[ms] is attached to iii , as shown in Figure 11.4-4.

T1
T2
T3 t

Signal “ON” Type ID=2 Type ID=4 Signal “OFF” Type ID=2
i occurs ii occurs iii occurs
Figure 11.4-4 Occurrences after the signal “ON”

GRL200 (Soft 033 & 037)


- 1358 -
6F2S1914 (0.37)

(ii) Setting of time-tagged messages


In Time-tagged message frame in the IEC 60870-5-103 standard, event information and
status information are responded for Class 1 request from the upper system (station). The
GR-series relay can provide event information and status information by Time-tagged
message frame about the signal assigned to a Data ID of the signal list.

When the “Time-tagged message” tab is selected, the “Time-tagged message” setting
screen is displayed on the start screen.

Figure 11.4-5 Time-tagged message in the GR-TIEMS

Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative
time) can be set in this screen. In one frame of Time-tagged message, the Type ID, INF,
FUN, DPI and COT must be set and the maximum 256 frames of Time-tagged message can
be set. The information number of the frame is determined by the INF setting. The most
left item “No.” is only serial number and can be skipped.

Common address is linked with the address setting† in the IEC 60870-5-103 standard.
†Note:For more information, see Appendix: IEC 60870-5-103 interoperability.

In the transmission format of Type ID=1 (Time-tagged message) and Type ID=2 (Time-
tagged message with relative time), customized items are shown in Table 11.4-3 and Table
11.4-4.
Table 11.4-3 Time-tagged message (Type ID=1)
Oct. Item Value Remarks
1 Start 68H
2 Length 14
3 Length 14
4 Start 68H
5 Control field 08H+ACD+D
FC
6 Address 1-254 Setting from the relay
7 Type identification (Type ID) 1 Customized by GR-TIEMS
8 Variable structure qualifier 81H
9 Cause of transmission (COT) 1/9/11/12 Customized by GR-TIEMS

GRL200 (Soft 033 & 037)


- 1359 -
6F2S1914 (0.37)

Oct. Item Value Remarks


10 Common address of ASDU Linked with Address
1-254
setting
11 Function type (FUN) 0-255 Customized by GR-TIEMS
12 Information number (INF) 0-255 Customized by GR-TIEMS
13 Double point information (DPI) -/(0)/1/2/(3)/DP Customized by GR-TIEMS
14 Millisecond (low)
0-59999
15 Millisecond (high)
16 Minutes + Invalid flag (MSB) 0-59+80H
17 Hours + Summer time flag (MSB) 0-23+80H
18 Supplementary information (SIN) 0-255
19 Checksum
20 End 16H

Table 11.4-4 Time-tagged message with relative time (Type ID=2)


Oct. Item Value Remarks
1 Start 68H
2 Length 18
3 Length 18
4 Start 68H
08H+ACD+D
5 Control field
FC
6 Address 1-254 Setting from the relay
7 Type identification (Type ID) 2 Customized by GR-TIEMS
8 Variable structure qualifier 81H
9 Cause of transmission (COT) 1/9/11/12 Customized by GR-TIEMS
10 Common address of ASDU 1-254 Linked with Address setting
11 Function type (FUN) 0-255 Customized by GR-TIEMS
12 Information number (INF) 0-255 Customized by GR-TIEMS
13 Double point information (DPI) -/(0)/1/2/(3)/DP Customized by GR-TIEMS
Trigger condition to
14 Relative time (RET) 0-65535 calculate RET is customized
by GR-TIEMS.
Trigger condition of FAN
16 Fault number (FAN) 0-65535 increment is customized by
GR-TIEMS.
18 Millisecond 0-59999
20 Minutes + Invalid flag (MSB) 0-59+80H
21 Hours + Summer time flag (MSB) 0-23+80H
22 Supplementary information (SIN) 0-255
23 Checksum
24 End 16H

Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function of IEC 60870-5-103 communication.

Signal name / signal description


The Data ID† (Sig. No.) showing the status of the frame is set from the signal list of the

GRL200 (Soft 033 & 037)


- 1360 -
6F2S1914 (0.37)

relay. If the setting value (signal No.) is “0”, all setting items related events are disable and
the frame is not provided.
†Note:A relevant Data ID is required to select; the description is obtained
automatically.

Type ID
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative time)
is selected to set the frame type. It is recommended that the frame related to status is set
to Type ID=1 and the frame related to faults is set to Type ID=2. In Type ID=2, the trigger
signal for the relative time should be set. For the setting, see Section 11.4.5(i).

INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided, the INF according to the Appendix† is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-5 and the
Appendix†.
Table 11.4-5 INF category of Monitor direction
INF Category
0 to 15 system functions
16 to 31 Status
32 to 47 Supervision
48 to 63 earth fault
64 to 127 short circuit
128 to 143 auto-reclosure
144 to 159 Measurands
160 to 239 not used
240 to 255 generic functions
†Note:See Appendix: IEC 60870-5-103 interoperability: Semantics of Information
number.

FUN
Function type (FUN) is set referring to Table 11.4-6. The FUN can be set to 0 to 255. When
clicking the “Change all FUNs” on the Common setting screen, all FUNs are changed to the
setting values at Common setting.
Table 11.4-6 Semantics of Function type
0 - 127 private range
128 distance protection
129 not used
144 not used
145 not used
160 overcurrent protection
161 not used
176 transformer differential protection
177 not used
192 Line differential protection

GRL200 (Soft 033 & 037)


- 1361 -
6F2S1914 (0.37)

193 not used


208 not used
209 not used
224 not used
225 not used
240 not used
241 not used
254 Generic function type
255 Global function type

DPI/Off, DPI/On
Double-point information (DPI) is set using the menu as follows:
DPI/Off: The frame is transmitted when the DPI/Sig.No. signal is OFF.
DPI/On: The frame is transmitted when the DPI/Sig.No. signal is ON.

Note: If selecting “-”(=don’t care), the frame is not transmitted even though the
DPI/Sig.No. signal set change to the set status. In general, the frames related
to tripping such as “Time-tagged message” and Time-tagged measurand”, etc.,
which are not an object of GI (General Interrogation), are not transmitted
when the DPI changes “On” to “Off”. In this case, set the “DPI/Off” to “-”(=don’t
care).
Note: When selecting “DP” for both “DPI/Off” and “DPI/On”, the DPI number is
transmitted as the number (=0/1/2/3) using the same information number
(INF). Regarding the frame related to a device control, the “undefined/failed”
status may be required in addition to the “close/open” status for the extension.
When selecting “DP”, “undefined(00)/close(01)/open(10)/failed(11)” status is
applied in the same information number (INF).

COT
Cause of Transmission (COT) of the frame is set. Not only one COT but also two or more
COT can be selected each No. (frame). COT setting pattern and COT supplemented the
frame are as follows:
(1) If two or all of COT=1, 11 and 12 are checked per No., each frame of the No. become
the following conditions.
Table 11.4-7 COT
COT Conditions
COT=12
TR[ms] after receiving any command of the IEC 60870-5-1031
(remote operation)
COT=11
TL[ms] after Key operation on the relay front panel1
(local operation)

COT=1 Conditions except above COT=11 and 12


(spontaneous) The relay is in test mode2, the COT=1(Spontaneous) is shifted to 7(Test mode)
1Note: TR and TL are set in Common setting.
2Note: Settings of the test mode is described later.

(2) If one of COT is specified per No., the frame is always supplemented with the

GRL200 (Soft 033 & 037)


- 1362 -
6F2S1914 (0.37)

specified COT regardless of cause of transmission.


(3) If COT=9 is specified, the frame become the object of GI and is sent back when the
GI request frame is received. Time-tagged message is sent back in order of No.
instead of order of INF.

Table 11.4-8 shows the summary of (1), (2) and (3) above.
Table 11.4-8 COT setting pattern and COT supplemented frame
COT setting
pattern COT supplemented frame when status changes GI
1 9 11 12
 Always “1” No
 Events don’t occur. Yes
 Always “11” No
 Always “12” No
  Always “1” Yes
  “11” (cause at local) or “1” (other causes) No
  “12” (cause at remote) or “1” (other causes) No
  Always “11” Yes
  Always “12” Yes
“11” (cause at local) or “12” (cause at remote) or “1”
  (other causes) No
   “11” (cause at local) or “1” (other causes) Yes
   “12” (cause at remote) or “1” (other causes) Yes
“11” (cause at local) or “12” (cause at remote) or “1”
   (other causes) No
“11” (cause at local) or “12” (cause at remote) or “1”
   (other causes) Yes
“11” (cause at local) or “12” (cause at remote) or “1”
    (other causes) Yes
Always “1” in spite of cause of event occurrence No
Note: When being in the test mode, the COT=1(Spontaneous) is shifted to 7(Test
mode)

GRL200 (Soft 033 & 037)


- 1363 -
6F2S1914 (0.37)

(iii) Setting for time-tagged measurands


For Time-tagged measurand frame in the IEC 60870-5-103 standard, event information
supplemented with numerical information are responded for Class 1 request from upper
system (station). The GR200-series relay can provide event information, which is converted
the numerical information in metering table according to user setting weight, by using
Time-tagged measurand frame about the signal assigned (i.e., the Data ID).

When the “Time-tagged measurand” item is selected on the GR-TIEMS, the setting
screen is displayed.

Figure 11.4-6 Time-tagged measurands

Type ID=4 (Time-tagged measurand with relative time) can be set in this screen. In
one frame of Time-tagged measurand, the INF, FUN, Sig No., Rev, COT and SCL must be
set and the maximum eight frames of Time-tagged measurand can be set. The information
number of the frame is determined by the INF setting. The most left item “No.” is only serial
number and can be skipped.

Common address is linked with the address setting† of the relay.


†For more information, see Appendix: IEC 60870-5-103 interoperability.

In the transmission format of Type ID=4 (Time-tagged measurand with relative time),
customized items are shown in Table 11.4-9.

Table 11.4-9 Time-tagged measurand with relative time (Type ID=4)


Oct. Item Value Remarks
1 Start 68H
2 Length 20
3 Length 20
4 Start 68H
5 Control field 08H+ACD+DFC
6 Address 1-254 Setting from the relay
7 Type identification (Type ID) 4
8 Variable structure qualifier 81H
9 Cause of transmission (COT) 1/7/11/12 Customized by GR-TIEMS
10 Common address of ASDU 1-254 Linked with Address setting

GRL200 (Soft 033 & 037)


- 1364 -
6F2S1914 (0.37)

Oct. Item Value Remarks


11 Function type (FUN) 0-255 Customized by GR-TIEMS
12 Information number (INF) 0-255 Customized by GR-TIEMS
13 Short-circuit location (SCL) Customized by GR-TIEMS
Trigger condition to calculate RET is
17 Relative time (RET) 0-65535
customized by GR-TIEMS.
Trigger condition of FAN increment is
19 Fault number (FAN) 0-65535
customized by GR-TIEMS.
21 Millisecond 0-59999
23 Minutes + Invalid flag (MSB) 0-59+80H
24 Hours + Summer time flag (MSB) 0-23+80H
25 Checksum
26 End 16H

Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.

Signal name / signal description


The Data ID† (Sig. No.) showing the trigger of the frame is set from the signal list. If the
setting value (signal No.) is “0”, all setting items related the “Time-tagged measurand” are
disable and the frame is not provided.

The frame cannot be set to the object of GI and cannot be transmitted even though the
status of set signal changes from ON to OFF. If the metering values at the newest fault
record are transmitted as the status change frame, select the Data ID of “F.Record_DONE”
or “FAULT RECORD DONE” in the signal list of the relay.

†Note:A relevant Data ID is required to select in the signal list. The description of the
Data ID is obtained automatically on the setting.

Inverse
This setting is used to invert the logic of the signal assigned to the Data ID above. If the
frame is transmitted when the signal assigned to the Data ID is ON, leave the Inverse check
box blank. If the frame is transmitted when the signal is OFF, click the inverse check box
to be marked with “”.

Type ID
Type ID=4 (Time-tagged measurand with Relative time) is fixed. In Type ID=4, the trigger
signal for the relative time should be set. For the setting, see Section 11.4.5(i).

INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the fame
out of the standard is provided, the INF should be set referring Table 11.4-3 and the
Appendix†.
†Note:For more information, see Appendix: IEC 60870-5-103 interoperability.

GRL200 (Soft 033 & 037)


- 1365 -
6F2S1914 (0.37)

FUN
Function type (FUN) is set referring to the Table 11.4-4. The FUN can be set to 0 to 255.
When clicking the “Change all FUNs” on the Common setting screen, all FUNs are changed
to the setting values at Common setting.

COT
Cause of Transmission (COT) of the frame is set. Not only one COT but two or more COT
can be selected each No. (frame). COT setting pattern and COT supplemented the frame
are according to Table 11.4-6. Though, the COT=9 (General Interrogation) cannot be
selected.

SCL Measurement Name/Measurement Description


The Data ID corresponding to a measurand is required to select.

Coefficient
Set the conversion coefficient, multiplied the power system quantities by, using floating-
point number. The SCL is a value which the power system quantity specified as above is
multiplied by this setting value.

GRL200 (Soft 033 & 037)


- 1366 -
6F2S1914 (0.37)

(iv) Setting for General commands


Using General command frame in the IEC 60870-5-103 standard, relay applications can be
performed by the remote control. For the GR200-series relay, a Data ID in the signal list is
controlled when receiving general command frame.

When the “General command” item is selected on the GR-TIEMS, the setting screen
is displayed.

Figure 11.4-7 “General command” setting screen

The frame of Type ID=20 (General command) and Command ACK/NACK can be set
in this screen. In one command of General command, the INF, FUN and DCO must be set.
The Command ACK/NACK is for detail setting and must not be set usually. (If do not check
the Ext check box, the setting of Command ACK/NACK is disabled and the Command ACK
and Command NACK respond according to the default response.)

The maximum 32 frames of General command and Command ACK/NACK can be set.
The information number of the frame is determined by the INF setting. The most left item
“No.” is only serial number and can be skipped.

Common address is linked with the address setting† of the relay.


†For more information, see Appendix: IEC 60870-5-103 interoperability.

In this setting screen, if a Data ID except “0” is set to “Sig Off” and “Sig On”, the
command at INF setting value is provided and Command ACK or Command NACK is sent
back when receiving the command from upper station. If both “Sig Off” and “Sig On” have
“0”, the fixed length NACK is always sent back then and the command is not provided.

Though the command is provided, however, Command NACK is always sent back and
no control is performed in the following cases:
(1): When receiving any General command from the upper station before Command
ACK/NACK is sending back from the relay.
(2): Under Monitor direction block condition (“IECBLK” setting is “blocked”.) when
receiving General command.
(3): When receiving an incorrect value of DCO of General command, that is DCO is neither
“1” nor “2”.

General command receiving sequence is as follows:

GRL200 (Soft 033 & 037)


- 1367 -
6F2S1914 (0.37)

Primary Secondary
station station

General
Command

ACK

Class 1

Command
ACK/NACK

Figure 11.4-8 Command receiving sequence

In the transmission format of General command (Type ID=20), customized items are
shown in Table 11.4-10.

Table 11.4-10 General command (Type ID=20)


Oct. Item Value Remarks
1 Start 68H
2 Length 10
3 Length 10
4 Start 68H
5 Control field 73H/53H
6 Address 1-254 Setting from the relay
7 Type identification (Type ID) 20
8 Variable structure qualifier 81H
9 Cause of transmission (COT) 20
10 Common address of ASDU 1-254 Linked with Address setting
11 Function type (FUN) 0-255
12 Information number (INF) 0-255 Customized by the GR-TIEMS
13 Double command (DCO) 1/2
14 Return Information identifier (RII) 0-65535
15 Checksum
16 End 16H

In the transmission format of Command ACK/NACK (Type ID=1), customized items


are shown in Table 11.4-11. The frame type of Command ACK/NACK is Time-tagged
message.
Table 11.4-11 Time-tagged message (Type ID=1)
Oct. Item Value Remarks
1 Start 68H
2 Length 14
3 Length 14

GRL200 (Soft 033 & 037)


- 1368 -
6F2S1914 (0.37)

Oct. Item Value Remarks


4 Start 68H
Control field 08H+ACD+
5
DFC
6 Address 1-254 Setting from the relay
7 Type identification (Type ID) 1 Customized by GR-TIEMS
8 Variable structure qualifier 81H
9 Cause of transmission (COT) 20/21 Customized by GR-TIEMS
10 Common address of ASDU 1-254 Linked with Address setting
11 Function type (FUN) 0-255 Customized by GR-TIEMS
Customized by GR-TIEMS.
12 Information number (INF) 0-255 Answer back of receiving
command INF
Double point information (DPI) Answer back of receiving
13 1/2
command DCO
14 Millisecond (low)
0-59999
15 Millisecond (high)
16 Minutes + Invalid flag (MSB) 0-59+80H
17 Hours + Summer time flag (MSB) 0-23+80H
Supplementary information (SIN) Answer back of receiving
18 0-255
command RII
19 Checksum
20 End 16H

Any comment with maximum 16 characters can be entered. This setting does not affect
the function in the IEC 60870-5-103 communication.

Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.

Type ID
Type ID=20 (General command) is fixed.

INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-12 and the
appendix†.
Table 11.4-12 INF category of Monitor direction
INF Category
0 to 15 system functions
16 to 31 status
32 to 239 not used
240 to 255 generic functions

†Note:For more information, see Appendix: IEC 60870-5-103 interoperability.

GRL200 (Soft 033 & 037)


- 1369 -
6F2S1914 (0.37)

FUN
Function type (FUN) applied to a command response frame is set referring to Table 11.4-13.
The FUN can be set to 0 to 255. When clicking the “Change all FUNs” on the Common
setting screen, all FUNs are changed to the setting values at Common setting.

DCO/Sig Off Name, Signal Off Desc., DCO Signal On Name, Signal On Desc.,
Inverse
“Sig off” and “Sig On” are used to set the Data ID of control object in General command.
(Hereafter, these are described as “command output signal”.) “Inverse” is used to reverse
the logic when controlling the command output signal.

When the command output signal is treated as two signals (Sig Off  Sig On), the
control scheme is shown as the following table by the combination of the receiving command
DCO and Inverse setting.

For example, when the DCO=Off command is received under “Inverse” no-checked,
the command output signal of “Sig Off” is controlled to “1”. “Sig On” is not controlled.

Table 11.4-13 Control Scheme of Command Output Signal (Sig Off  Sig On)
“Inverse” checked Checked No-checked

Control object
Signal specified Signal specified Signal specified Signal specified to
Receiving
to Sig.off to Sig.on to Sig.off Sig.on
command DCO

Off Controlled to “1” Not controlled Controlled to “0” Not controlled

On Not controlled Controlled to “1” Not controlled Controlled to “0”

When the command output signal is treated as one signal (Sig Off  Sig On), the
control scheme is shown in Table 11.4-14. For example, when the DCO=On command is
received under “Inverse” checked, the command output signals of “Sig On” and “Sig Off” are
controlled to “0”. “Sig On” is not controlled.

Table 11.4-14 Control Scheme of Command Output Signal (Sig Off = Sig On)
“Inverse” checked Checked No-checked

Control object
Signal specified Signal specified Signal specified Signal specified
Receiving
to Sig.off to Sig.on to Sig.off to Sig.on
command DCO

Off Controlled to “0” Controlled to ”1”

On Controlled to ”1” Controlled to “0”

When setting the “Sig Off”, “Sig On” and “Inverse”, check the specifications of the
command output signals of communication and others, and then set them.

Valid time

GRL200 (Soft 033 & 037)


- 1370 -
6F2S1914 (0.37)

Valid time is used to set the time (ms) to control the command output signal. The command
output signal is controlled based on the control scheme described in section 11.4.5(iv)-5 for
the setting time after receiving General command, and is reset by communication side after
the set time. However, if the time is set to “0”, the control is not reset and is continued. Set
the time with a margin for interface of other applications.

ACK/NACK / Ext
This setting is used to enable the extension setting of Command ACK/NACK response
scheme or not. If “Ext” is not specified (Ext check box is not checked.), Command NACK (in
cases of (1)–(3) of the section 11.4.5(iii) and Command ACK (in case of others) respond
according to the default response. If “Ext” is specified, the setting of Command ACK/NACK
described later is enabled and the response scheme can be customized. When required the
stricter handshake by using Command ACK/NACK, it is better to specify the “Ext”. This
setting is not influenced by the control scheme of the command output signal.

Signal ACK Name/Signal ACK Desc./Signal NACK Name/Signal NACK


Desc./Inverse
“ACK Sig” and “NACK Sig” are used to set the Data ID for judgment of command response.
(Hereafter, these are described as “command response signal”.) “Inverse” is used to reverse
the logic of the command response signal, and “Timeout” is used to set the timeout time for
judgment of command response. Under specified “Ext” (Ext check box is checked.),
Command ACK or Command NACK responds based on the logic of command response
signal against General command.

When the command response signal is treated as two signals (ACK Sig  NACK Sig),
the judgment scheme is shown as the following table by the combination of the receiving
command DCO and Inverse setting. The judgment timing is when (1), (2), (3) or (4) in Table
11.4-15 is established. If the neither (1), (2), (3) nor (4) is established (that is ACK sig =
NACK Sig = 1 or ACK sig = NACK Sig = 0) for the period from the command receiving to
the timeout setting time, Command NACK responds at that time.

For example, when the DCO=On command is received under “Inverse” no-checked,
Command ACK responds in case of “ACK Sig = 0” and NACK Sig = 1”.

Table 11.4-15 Judgment Scheme of Command Response (ACK Sig  NACK Sig)
“Inverse” checked No-checked Checked

Command response signal


(1)NACK Sig=1 (2)NACK Sig=0 (3)NACK Sig=1 (4) NACK Sig=0
Receiving
ACK Sig=0 ACK Sig=1 ACK Sig=0 ACK Sig=1
command DCO

Command NACK Command ACK Command ACK Command NACK


Off
responds. responds. responds. responds.

Command NACK Command ACK Command ACK Command NACK


On
responds. responds. responds. responds.

When the command response signal is treated as one signal (ACK Sig = NACK Sig),
the judgment scheme is shown as the following table by the combination of the receiving
command DCO and Inverse setting. The judgment timing is after the timeout setting time

GRL200 (Soft 033 & 037)


- 1371 -
6F2S1914 (0.37)

from the command receiving.

For example, when the DCO=On command is received under “Inverse” checked,
Command ACK responds in case of “ACK Sig = NACK Sig = 1” after the timeout setting
time.

Table 11.4-16 Judgment Scheme of Command Response (ACK Sig = NACK Sig)
“Inverse” checked No-checked Checked

Command response signal


(1)NACK Sig= (2)NACK Sig = (3) NACK Sig = (4) NACK Sig =
Receiving
ACK Sig = 0 ACK Sig = 1 ACK Sig = 0 ACK Sig = 1
command DCO

Command ACK Command NACK Command NACK Command ACK


Off
responds. responds. responds. responds.

Command NACK Command ACK Command ACK Command NACK


On
responds. responds. responds. responds.

GRL200 (Soft 033 & 037)


- 1372 -
6F2S1914 (0.37)

(v) Setting of Measurands


In Measurand frame of the IEC 60870-5-103 standard, numerical information such as power
system quantities are responded for Class 2 cyclic request from upper system (station). The
GR200-series relay can provide numerical information, which is converted the numerical
information in metering table according to user setting weight.

When the “Measurands” item is selected on the start screen of the GR-TIEMS, the
setting screen is displayed.

Figure 11.4-9 “Measurands” setting screen

Figure 11.4-10 “Measurand1” setting screen

In one frame of Measurand, the Type ID, INF, FUN settings, and its position setting
(Measurement Name/Measurement Description/Lower Limit/Upper Limit/Coefficient)
must be set. “No.” shows the position of power system quantity. (For details, describe later.)
The maximum 16 items of Measurands and the maximum 32 power system quantities per
one frame can be set.

Common address is linked with the address setting† of the relay.


†For more information, see Appendix: IEC 60870-5-103 interoperability.

GRL200 (Soft 033 & 037)


- 1373 -
6F2S1914 (0.37)

In the transmission format of Measurand I (Type ID=3) and Measurand II (Type ID=9),
customized items are shown in Table 11.4-17.

Table 11.4-17 Measurand I/Measurand II (Type ID=3/9)


Oct. Item Value Remarks
1 Start 68H
2 Length 8+2N
3 Length 8+2N
4 Start 68H
08H+ACD+
5 Control field
DFC
6 Address 1-254 Setting from the relay
7 Type identification(Type ID) 3/9 Customized by GR-TIEMS
8 Variable structure qualifier 81H
9 Cause of transmission(COT) 2/7
10 Common address of ASDU 1-254 Linked with Address setting
11 Function type(FUN) 0-255 Customized by GR-TIEMS
12 Information number(INF) 0-255 Customized by GR-TIEMS
Measurand with quality
13+2(N-1) Customized by GR-TIEMS
descriptor(MEA) + IV + OV
15+2(N-1) Checksum
16+2(N-1) End 16H

Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function of the IEC 60870-5-103 communication.

Type ID
Type ID=3 (Measurands I) or Type ID=9 (Measurands II) can be selected to set the frame
type of Measurand frame. In general, the maximum MEA number of Type ID=3 uses 1 or 2
or 4 and that of Type ID=9 uses 9. (However, the maximum MEA number of both types can
extend up to 32 in the GR-TIEMS. In this case, there are no difference between the
transmission format of Type ID=3 and that of Type ID=9.)

INF
Information number (INF) of the Measurand frame is set. The INF can be set to 0 to 255.
When the standard frame† is provided, the INF according to the standard is recommended.

If the fame out of standard is provided, the INF should be set referring Table 11.4-3
and the appendix†.

†Note:For more information, see Appendix: IEC 60870-5-103 interoperability.

FUN
Function type (FUN) of the Measurand frame is set referring to the Table 11.4-4. The FUN
can be set to 0 to 255. If click the “Change all FUNs” on the Common setting screen, all
FUNs are changed to the setting values at Common setting.

GRL200 (Soft 033 & 037)


- 1374 -
6F2S1914 (0.37)

Name
Any comment with maximum eight characters can be entered. This setting does not affect
the function in the IEC 60870-5-103 communication.

Measurement Name/Measurement Description


The Data ID corresponding to a measurand is required to select.

Lower Limit/Upper Limit


The established condition of IV flag is set per MEA. IV flag is established when MEA value
exceeds a Lower limit or an Upper limit. If Lower limit = Upper limit =0 is set, The IV flag
is always established and it becomes MEA=0.
Table 11.4-18 MEA Bit Arrangement
High Octet Low Octet

Sign B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 RES IV OV

If MEA value exceeds the full scale (if the value expressed as B1 to B12 is less than
4096 or more than 4095), the MEA is clamped at 4096 or 4095 and OV flag is established.
However, if IV flag is established, OV flag is not established.

Coefficient
Set the conversion coefficient, multiplied the power system quantities by, using floating-
point number. The MEA is a value which the power system quantity specified as above is
multiplied by this setting value.

11.4.6 Protocol selection


As shown in the setting menu for the Communication (Figure 11.4-11), the user should set
IEC103 for the [Slave Protocol] so that the communication in the IEC60870-5-103 standard is
carried out in the IED. Note that the restarting the IED (i.e., resetting the IED power) is
required after the user turns to the IEC60870-5-103 protocol.

SLAVE PROTOCOL
10:48 1/1
Slave protocol +
IEC103

Figure 11.4-11 Slave protection for the IEC103 protocol (on IED setting menu)
Note: The menu is just screened when a couple of communication protocols are
embedded in the IED.

GRL200 (Soft 033 & 037)


- 1375 -
6F2S1914 (0.37)

11.4.7 Tips for settings


During the GR-TIEMS operation, we recommend the user to choose an appropriate file-name
for the setting-file. That is, for example, when the user creates the setting file for an IED at
the first time, the user is required to make it with the name “IED#1-model_01.map”. Likewise,
the user can create the other setting file with the name “IED#2-model_01.map” for the other
IED. If the user is required to modify the “IED#1-model_01.map”, the user should replace the
name by new name “IED#1-model_02.map”. Consequently, the user can easily discriminate the
setting files in the IED model2 (i.e., IED#1-model or IED#2-model) and the revision number
(i.e., 01 or 02).

Figure 11.4-12 shows the editing screen of the GR-TIEMS; the screen has a remark field
concerning to the IEC 60870-5-103 communication. Note the available length of the remark
field is up to 12 in the one-byte character. The remark field is utilized for the control of the
setting data.

Figure 11.4-12 Common setting screen in the GR-TIEMS


Note: We recommend to make the backup file of the setting data.

GRL200 (Soft 033 & 037)


- 1376 -
6F2S1914 (0.37)

11.4.8 Setting
Setting of 103_SLAVE (Function ID: 304001)
Unit Default setting
Setting item Range Contents Notes
s value

103ADDR 0 to 254 Slave address 2


103TST Off/On – IEC 60780-5-103 test mode Off
103BLK Off/On – IEC 60780-5-103 slave block Off

GRL200 (Soft 033 & 037)


- 1377 -
6F2S1914 (0.37)

11.4.9 Signal (Data ID)


 Monitoring point
103_SLAVE (Function ID: 304001)
Element ID Name Description
3100011001 103SLV STAT 103SLV STATUS
8020011001 AG1STAT Active Group 1 status
8120021001 AG2STAT Active Group 2 status
8220031001 AG3STAT Active Group 3 status
8320041001 AG4STAT Active Group 4 status
8420051001 AG5STAT Active Group 5 status
8520061001 AG6STAT Active Group 6 status
8620071001 AG7STAT Active Group 7 status
8720081001 AG8STAT Active Group 8 status
3120001001 AGNUM Active Group Number
8030001001 GPCMD00STAT General Purpose Command 0 status
8130011001 GPCMD01STAT General Purpose Command 1 status
8230021001 GPCMD02STAT General Purpose Command 2 status
8330031001 GPCMD03STAT General Purpose Command 3 status
8430041001 GPCMD04STAT General Purpose Command 4 status
8530051001 GPCMD05STAT General Purpose Command 5 status
8630061001 GPCMD06STAT General Purpose Command 6 status
8730071001 GPCMD07STAT General Purpose Command 7 status
8830081001 GPCMD08STAT General Purpose Command 8 status
8930091001 GPCMD09STAT General Purpose Command 9 status
8A300A1001 GPCMD10STAT General Purpose Command 10 status
8B300B1001 GPCMD11STAT General Purpose Command 11 status
8C300C1001 GPCMD12STAT General Purpose Command 12 status
8D300D1001 GPCMD13STAT General Purpose Command 13 status
8E300E1001 GPCMD14STAT General Purpose Command 14 status
8F300F1001 GPCMD15STAT General Purpose Command 15 status
8030101001 GPCMD16STAT General Purpose Command 16 status
8130111001 GPCMD17STAT General Purpose Command 17 status
8230121001 GPCMD18STAT General Purpose Command 18 status
8330131001 GPCMD19STAT General Purpose Command 19 status
8430141001 GPCMD20STAT General Purpose Command 20 status
8530151001 GPCMD21STAT General Purpose Command 21 status
8630161001 GPCMD22STAT General Purpose Command 22 status
8730171001 GPCMD23STAT General Purpose Command 23 status
8830181001 GPCMD24STAT General Purpose Command 24 status
8930191001 GPCMD25STAT General Purpose Command 25 status
8A301A1001 GPCMD26STAT General Purpose Command 26 status
8B301B1001 GPCMD27STAT General Purpose Command 27 status
8C301C1001 GPCMD28STAT General Purpose Command 28 status
8D301D1001 GPCMD29STAT General Purpose Command 29 status
8E301E1001 GPCMD30STAT General Purpose Command 30 status
8F301F1001 GPCMD31STAT General Purpose Command 31 status
3110001001 LEDRST_STAT LED Reset status

GRL200 (Soft 033 & 037)


- 1378 -
6F2S1914 (0.37)

USB communication
The IED front panel has an USB receptacle in a B-type to connect with a local PC for
engineering. The user can select a transmission speed, which is shown below, by the operation
of the setting menu, as shown in Figure 11.5-1.

USBCOM
10:48 1/1
USBCOM_BRATE_SW +
921.6kbps

Figure 11.5-1 USB setting menu (on IED screen)

Setting of USB (Function ID: 231701)


Unit Default setting
Setting item Range Contents Notes
s value

USBCOM_BRATE_SW 115.2 / 921.6 kbps Baud rate Switch for USB Com port 921.6

GRL200 (Soft 033 & 037)


- 1379 -
6F2S1914 (0.37)

RS485 communication
When the IED has an RS485 module for the communication, the user can select and set its
transmission and error check parity codes. Figure 11.6-1 shows the setting screen when the
RS485 module (#1) operates.

RS485
10:48 1/2
RS485_1_BRATE_SW +
19.2kbps
RS485_1_BRATE_SW +
NONE

Figure 11.6-1 RS485 setting menu (on IED screen)

Setting of RS485 (Function ID: 232201)


Unit Default setting
Setting item Range Contents Notes
s value

Module RS485_1_BRATE_SW 9.6 / 19.2 / 38.4 /57.6 / 115.2 kbps Transmission speed 19.2
#1 RS485_1_PAR_SW NONE / ODD /EVEN – Parity check code NONE

GRL200 (Soft 033 & 037)


- 1380 -
6F2S1914 (0.37)

12 User interface
Contents Pages Pages
Outline 1382 Time sub-menu 1422
-Front panel 1382 -Clock 1422
-LCD screen 1382 -Time zone 1423
-LEDs 1382 -Time synchronization 1423
-Function Keys 1383 -Display format 1425
-Operation Keys 1383 -Summer time(DST) 1427
HMI operation 1385 Test sub-menu 1428
-General operation 1385 -Test screen 1428
-Main-menu and sub-menu 1385 -Test mode screen 1428
Record sub-menu 1388 -Test flag enabling screen 1432
-Fault record 1388 -Mode change screen 1433
-Event record 1390 -Signal monitoring screen 1433
-Disturbance record 1391 Information sub-menu 1434
Monitoring sub-menu 1393 Security setting sub-menu 1435
-Metering 1393 Control sub-menu 1437
-Binary I/O 1393 -CB open / Close 1438
-Communication 1394
-Relay elements 1396
-Statistics 1397
-Goose monitoring 1399
-Diagnostics 1400
Setting sub-menu 1401
-Setting method 1401
-Confirmation dialog 1405
-On/Off 1408
- Group setting 1408
-Function key 1410
I/O setting 1414
-AC analog input 1414
-Binary input 1416
-Binary output 1418
-LED 1420

GRL200 (Soft 033 & 037)


- 1381 -
6F2S1914 (0.37)

Outline
Users can perform maintenance on the IED from the front panel. Monitoring is also possible
locally by using a PC connected through the USB cable. This section discusses the
configuration of the front panel and the basic configuration of the screen-menu hierarchy of
the Human Machine Interface (HMI).

(i) Front Panel


The front panel is provided with a screen (LCD Screen), 26 light emitting diodes (LEDs), 11
operation keys, seven function keys (in the later section the function keys are referred to as F1
to F7.), monitoring jacks and a USB receptacle.

LEDs
LCD screen

Operation keys
Function keys
with LEDs

Monitoring jacks with USB


LEDs (A, B, and C)

Figure 12.1-1 Front Panel


(ii) LCD screen
The LCD screen provides the user with detailed internal information provided by the IED such
as records, monitoring and settings. Normally, the LCD screen appears blank unless an
operation key is pressed, by pressing any of the operation keys, the LCD screen will display
the top menu. If the top menu is shown on the LCD screen, the user can turn off the screen
backlight by pressing the operation key ◄. When operation is idle for some time, the screen
backlight turns off. By pressing any key except the CLEAR key, the backlight turns on, and
the previous menu will be displayed on the LCD screen.

(iii) LEDs
As shown in Table 12.1-1, 26 LEDs, each having signal labels and colors, are defined:

GRL200 (Soft 033 & 037)


- 1382 -
6F2S1914 (0.37)

Table 12.1-1 LED labels and their color


LED User configurable
Label Color Remarks
No. setting2
Lit up when the IED
1 IN SERVICE Green N/A
is in service.
Lit up when an error
2 ERROR Red N/A
is occurred.
31 N/A N/A ✔

41 TRIP Red ✔ Default


51 N/A N/A ✔

61 TEST Yellow ✔ Default


71 N/A N/A ✔

. N/A N/A ✔ .
. . . . .
. . . . .
. . . . .
261 N/A N/A ✔
1Note: LEDs are user-configurable. Users can use them with or without latch function.
2Note: For setting LEDs, see section 12.6(iv).

(iv) Function keys


Seven function keys (F1 to F7) have the following two features.
 Skip to a specific screen directly, set by the user.
Used for skipping to a set page by pressing the function keys. Press again to return to the
previous page. Set by pressing the function key for 2 seconds on the selected page. (See
section 12.5(v)-1)
 Test signal generator.
A convenient method that can be used for operating binary signals. Set by assigning the
signal in the settings menu. (See section 12.5(v)-2)
Table 12.1-2 Features of Function keys (F1 to F7)
Labels on Keys Feature and Remark

LED† Skip to a specific screen directly.


Control for the operation of pre-assigned
F1 to F7 binary signals.

†Note: The user can program to light the LEDs by itself. Setting are similar to the ones
of the Table 12.1-1 (For setting, see section 12.6(iv)). Note the manufacture
programs to light the respective LEDs in default prior to shipping.

(v) Operation keys


By using the operation keys, the user can display records, relay status etc. Input of setting

GRL200 (Soft 033 & 037)


- 1383 -
6F2S1914 (0.37)

values is performed using these keys. The operation keys are tabulated in Table 12.1-3.
Table 12.1-3 Features of operation keys
Label Functions and Remarks

Move the cursor up / Scroll up / Count up1

Move the cursor down / Scroll down / Count down1

Previous page / Move to the left digit.

Next page / Move to the right digit

ENTER Enter edit mode, if item is active / Executive operation / Accept alarm
message.

CANCEL Exit edit mode / Cancel operation.

CLEAR Clear all latched LEDs (Except [In service] and [Error] LEDs).

HELP Display the help message, for cases where the active item has a help
function.

L
R
Switch between Local mode and Remote mode.

I Control key. (Close)

O Control key. (Open)

MENU Switch for using MIMIC2 mode or for returning back to the menu screen.
MIMIC
This key is not provided for standard LCD screen2.
1Note: To scroll up or scroll down quickly, press keys ▲ or ▼ respectively along with key
►.
2Note: The MIMIC key is only available when Large LCD screen is mounted on the front
panel. The pixel resolution (dot) is 240(W) × 320(H). Note that this mode is only
provided when the user has programmed MIMIC feature using GR-TIEMS. See
chapter Engineering tool: MIMIC configuration tool.

GRL200 (Soft 033 & 037)


- 1384 -
6F2S1914 (0.37)

HMI operation
By using the LCD screen, the operation keys and the function keys, the user can access
functions such as recording, monitoring, relay setting and testing.
Note: The operation of the LCD screen is more or less common in all IED models.
However, the contents of the LCD screen depend upon the IED model.

(i) Screen and LEDs during normal HMI operation


When the IED is operating normally, the green "IN SERVICE" LED is lit. Press any key except
the key CLEAR; and then the backlight of the LCD screen is turned on1. If the IED detects a
fault, the fault message will appear in a pop-up screen. At the same time, the “TRIP”2 LED is
lit.
1Note: If another fault occurs during the period of time for which the previous fault pop-
up screen, is displayed, the previous fault information will be overwritten by the
new fault on the pop-up screen. Press the key CANCEL to remove the pop-up
screen for “Latest Fault” to return to the previous screen.
2Note: Press the key CLEAR to turn off the LED.

(ii) Main-menu and Sub-menu


 Main-menu
If LCD screen is turned off, press any key, except the key CLEAR. “Main-Menu" will
appear on the LCD screen (see the left of Figure 12.2-1). To go to the next level of
hierarchy, press the key ►.

 Sub-menu
An example of setting the sub-menu screen is shown in the right of Figure 12.2-1. By
using the key ▼ and the key ▲, the user can move the cursor downward or upward
to view all of the items. By using the keys ◄ ►, the user can return to a previous
level of hierarchy or go to the next level of hierarchy.

 Screen structure
The screen is composed of a title area and a data area. The title area is fixed on the
top two lines. The first line displays the screen title. The second line on the left-hand
side displays local time, whereas the right-hand side displays either the current line
number, cursor position number and the maximum page number, or the item number.
For example, the display “2/4” means the current cursor position, which is at the
second item of a maximum of four items.

GRL200 (Soft 033 & 037)


- 1385 -
6F2S1914 (0.37)

Main Menu OC
10:48 1/8 10:48 2/4
_Record > OC1EN +>
Monitoring > On
Setting > _OC2EN +>
I/O Setting > On
Time > OC3EN +
Test > Off
a. Main Menu b. Sub Menu

Figure 12.2-1 LCD screen for Main-Menu and Sub-menu

Figure 12.2-2 shows the menu hierarchy. The menu consists of a Main-Menu and several
Sub-menus. Table 12.2-1 shows the configuration of Main-Menu.

Main Menu Sub-menu Sub-menu Sub-menu Main Menu Sub-menu Sub-menu Sub-menu
Main Menu Record Record List Main Menu
Fault Record Clear Records
Event Record1 Record List
Clear Records Setting
Event Record2 Record List
Clear Records Statistics Counter(GCNT01~)
Event Record3 Record List Sigma Iy
Clear Records Function Key F1 Key ~ F7 Key
Disturbance Record Record List
Clear Records Diagnostics Detail
Clear All Records

Monitoring Metering IO Setting AC Analog Input AI (#1~)

Binary I/O Slot#n Binary Input Slot (#1~)

Communication LAN Binary Output Slot (#1~)


61850STAT
Relay Element CLP OV LED LED (3~26)
DIF_LP OVS F1 Key ~ F7 Key
DIFG_LP OVG
OSTV UV
Distance_ZS UVS Control
Distance_ZG FRQ
Distance_Common OSTZ
OC ICD Time Clock ActiveSyncSrc
EF PROT_Common
OCN FS Time Zone
THM VTF
BCD CTF Time Sync SNTP
CBF VCHK BI SYNC
SOTFOC Display Format IRIG SYNC
STUBOC
Statistics Power Value Accumulated Time Summer Time
Demand Operation Time
Interlock Peak Demand Operation Counter
Counter Total Time Test Test Mode Test Option
GOOSE Monitoring Sigma Iy Function Test
Binary Input (Slot#n)
Diagnostics Binary Output (Slot#n)
Simultaneous Fault

Setting Record Fault Record Mode Change F1 Key ~ F7 Key


Event Record
Metering Disturbance Record Security
Communication LAN
USBCOM
RS485 Information
IEC61850
IEC SLV

Protection Common
Security Setting Change Password
Active Group
Copy Group(A->B)
Security
Group1
Group2
Group3 Login / Logout
Group4
Group5
Group6
Group7
Group8

Control Common Control


Circuit Breaker
Synchronism
Synchk_Ry
Change Over Switch
Software Switch
Reset Control
Auto Sequence
Total Time Mar
General BI

Figure 12.2-2 Menu hierarchy

GRL200 (Soft 033 & 037)


- 1386 -
6F2S1914 (0.37)

Table 12.2-1 Outline of Main-menu and their purposes


Sub-menu Purpose and functions
The "Record" sub-menu provides fault record, event record and disturbance
record. The user can erase each record individually or can clear all records at
Record
the same time. The user can assign event records to three distributed “Event
Record” sub-menus as required.
The "Monitoring" sub-menu displays all of the status values for the IED, such
Monitoring as Metering, Binary I/O, Communication, Relay Element, Statistics,
Interlock, GOOSE Monitoring, and Diagnostics.
The "Setting" sub-menu is used to view or change the settings: Record,
Setting
Metering, Communication and Protection.
The "I/O Setting" sub-menu is used to view or change the settings for inputs,
I/O Setting configurable binary inputs, configurable binary outputs, and configurable
LEDs.
The “Control” sub-menu is used to manipulate an external gear such as circuit
Control
breaker (CB), isolator, etc.
The "Time" sub-menu provides settings for calendar clock, time zone, the
Time
source of time synchronization and the display format of the calendar clock.
The "Test" sub-menu is used to set and to test the following: a trip circuit,
Test forcible operation of binary outputs from the IED, time measurement of
variable timers, and observation of the binary signals in logic circuits.
The "Information" sub-menu displays information about the IED such as
Information
hardware, software, communication, etc.
The "Security Setting" sub-menu is used to change the password and access
Security
level, providing high levels of security by assigning users different levels of
Setting
access.
When the "Security Setting” sub-menu is ON, the “Login/Logout” sub-menu
Login/Logout
is displayed.

GRL200 (Soft 033 & 037)


- 1387 -
6F2S1914 (0.37)

Record sub-menu
The Record sub-menu is composed of several sub-menus: fault record, event record,
disturbance record, and clearance of all records. In each sub-menu, the user can clear records
separately.
Record
10:48 1/6
_Fault Record >
Event Record1 >
Event Record2 >
Event Record3 >
Disturbance Record >
Clear All Records +

Figure 12.3-1 Display of Record


Table 12.3-1 Operation and display in Record sub-menu
Display Operation key Remark
[>] ► Press the key ► to go to the sub-menu
[+] ENTER Press the key ENTER for executing “Clear all records”.
Confirmation dialog screen will be displayed.
(i) Fault Record
The “Fault Record” sub-menu displays the date and time of fault occurrence, fault phase,
tripping mode, and the power system quantities, as shown in Figure 12.3-2.

Fault Record Fault Record#1


10:48 1/6 10:48 1/222
#1 2012-07-25 > 2012-07-25
10:48:21.223 10:48:21.223
#2 2012-07-21 > Phase AB
01:15:55.018 Trip 1,2,3,4,5,6
#3 2012/07/21 > OC1
13:11:29.621 2012-07-25

Fault Record List Details of Fault Record

Figure 12.3-2 Display of Fault Record

Display fault record


Record 1). Move cursor to the Fault Record menu and press ►.
10:48 1/6
_Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +

Fault Record
10:48 1/2 2). Fault Record screen is displayed. Press ► at the Record List sub
_Record List >
Clear Records + menu.

GRL200 (Soft 033 & 037)


- 1388 -
6F2S1914 (0.37)

Fault Record
3). Fault record list in the Fault Record screen is displayed. Move
10:48 1/6 cursor to a desired item by ▲ or ▼ and press ►.
#1 2012-07-25 >
10:48:21.223
#2 2012-07-21 >
01:15:55.018
#3 2012/07/20 >
13:11:29.621

Fault Record#2
10:48 1/222 4). Press ▲ or ▼ to move display items.
2012-07-21
01:15:55.018
Phase AB
Trip AB
OC1
53.4km (23%)

Clear fault record

Record
1). Move cursor to the Fault Record menu and press ►.
10:48 1/6
_Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +

Fault Record
10:48 1/2 2). Move cursor to Clear Records and press ENTER.
Record List >
_Clear Records +

Fault Record 3). Clear records if ENTER is pressed. Back to display of “Fault

Clear records? Record” directly if CANCEL is pressed.


ENTER=Yes CANCEL=No

Clear all information in Fault Record


Record 1). Move cursor to the Clear all Records sub menu and press
10:48 1/6
ENTER.
Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
_Clear all Records +

GRL200 (Soft 033 & 037)


- 1389 -
6F2S1914 (0.37)

Clear Records
2). Clear all records if ENTER is pressed. Back to display of “Record”
Clear All records?
ENTER=Yes CANCEL=No
directly if CANCEL is pressed.

(ii) Event Record


The “Event Record” sub-menu provides three parts namely, “Event Record1”, “Event Record2”
and “Event Record3”. In each Event Record sub-menu, the data and time, device name, and
the operation of the device are displayed as shown in the example below.

Event record1
10:48 1/3
#1 2012-07-25
10:48:21.223
Set.Group change
2
#2 2012-07-25
10:20:21.021

Figure 12.3-3 Display of Event Record

Display of Event Record


Record 1). Move cursor to Event Record 1, 2, or 3 sub menu and press ►.
10:48 2/6
To clear all records, refer to section (i)-3.
Fault Record >
_Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
2). Event Record screen is displayed. Press ► at the Record List
Event Record1 sub menu.
10:48 1/2
_Record List >
Clear Records +

3). Press ▲ or ▼ to move display items.


Event Record1
10:48 1/3
#1 2012-07-25
10:48:21.223
Set. Group change
2
#2 2012-07-25
10:20:11.021

GRL200 (Soft 033 & 037)


- 1390 -
6F2S1914 (0.37)

Clear of Event Records


1). Move cursor to Event Record 1, 2, or 3 sub menu and press ►.
Record
10:48 2/6 To clear all records, refer to section (i)-3.
Fault Record >
_Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
2). Event Record screen is displayed. Press ENTER at the Clear
Event Record1
Records sub menu.
10:48 1/2
Record List >
_Clear Records +

Event Record1 3). Clear all Event records if ENTER is pressed. Back to display of

Clear records?
Event Record directly if CANCEL is pressed.
ENTER=Yes CANCEL=No

(iii) Disturbance Record


Disturbance Records can be displayed graphically on the PC screen by using GR-TIEMS. The
IED screen displays only the recorded date and times, which are stored in the IED as the entire
disturbance data, as shown in the following example:

Disturbance record
10:48 1/6
#1 2012-07-25
10:48:04.223
#2 2012-07-21
01:15:55.018
#3 2012-07-20
13:11:29.621

Figure 12.3-4 Display of Disturbance Record


The following shows the steps to display and erase disturbance records.

GRL200 (Soft 033 & 037)


- 1391 -
6F2S1914 (0.37)

Display of disturbance Record


Record 1). Move cursor to Disturbance Record sub menu and press ►.
10:48 2/6
Fault Record >
To clear all records, refer to section (i)-3.
Event Record 1 >
Event Record 2 >
Event Record 3 >
_Disturbance Record >
Clear all Records +

Disturbance Record
10:48 1/2 2). Disturbance Record screen is displayed. Press ► at the Record
_Record List >
Clear Records + List sub menu.

Disturbance Record
10:48 1/6
#1 2012-07-25 3). Press ▲ or ▼ to move display items.
10:48:21.223
#2 2012-07-21
01:15:55.018
#3 2012-07-20
13:11:29.621

Clear of Disturbance Records

Record
10:48 2/6 1). Move cursor to Disturbance Record sub menu and press ►.
Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
_Disturbance Record >
Clear all Records +

Disturbance Record 2). Disturbance Record screen is displayed. Press ENTER at the
10:48 1/2
Record List > Clear Records sub menu.
_Clear Records +

Disturbance Record 3). Clear all Disturbance records if ENTER is pressed. Back to
display of “Disturbance Record” directly if CANCEL is pressed.
Clear records?
ENTER=Yes CANCEL=No

GRL200 (Soft 033 & 037)


- 1392 -
6F2S1914 (0.37)

Monitoring sub-menu
“Monitoring” sub-menu is used to display the current status of the IED. The data is updated
every second on the LCD screen. The user can view the following functions from the Monitoring
sub-menu:
i. Metering sub-menu
ii. Binary I/O sub-menu
iii. Communication sub-menu
iv. Relay Elements sub-menu
v. Statistics sub-menu
vi. GOOSE Monitoring sub-menu
vii. Diagnostics sub-menu

(i) Metering
The value and direction of current, voltage etc. can be displayed. The user can change the units
as required by using the appropriate setting. Figure 12.4-1 shows an example of the Metering
sub-menu.

Metering
10:48 1/25
Va
23.231kV 121.34deg
Vb
23.200kV 120.14deg
Vc
22.713kV 121.50deg

Figure 12.4-1 Display for Metering

(ii) Binary I/O


“Binary I/O” sub-menu can be used to display the respective status of the binary IO module
circuits. The LCD displays the binary input or output signal number, the signal name1
assigned to the circuits of the binary IO modules and their status in a line. The status for the
binary output circuit is shown by a logic level (“1” or “0”). Figure 12.4-2 provides an example
for binary IO module at IO#1 (Slot#1).

Slot#1
10:48 1/12
BI1 0 CB1 contact
BI2 0 DC power sup.
BI3 0 Trans-T Comm1
BI3 0 Trans-T Comm2
BI4 0 ARC-Block1
BI5 0 Indi. Reset

Figure 12.4-2 Display of Binary I/O status


1Note: The user can set the names of binary signals with GR-TIEMS.
GRL200 (Soft 033 & 037)
- 1393 -
6F2S1914 (0.37)

Figure 12.4-3 shows the steps required to display the status of the binary inputs and outputs.

Main Menu Monitoring Binary I/O


10:48 2/9 10:48 2/14 10:48 1/4
Record > ► Statistics > ► _Slot#1 >
_Monitoring > Metering > Slot#2 >
Setting > _Binary I/O >
IO setting >
◄ ◄ Slot#3 >
Operation Time > Slot#4 >
Time > Relay Element >
Test > Communication >

► ◄

Slot#1 Slot#1
10:48 2/12 10:48 1/12
BI1 0 CB1 contact ▲ BI1 0 CB1 contact
BI2 0 DC power sup. BI2 0 DC power sup.
BI3 0 Trans-T Comm1 BI3 0 Trans-T Comm1

BI3 0 Trans-T Comm2 BI3 0 Trans-T Comm2
BI4 0 ARC-Block1 BI4 0 ARC-Block1
BI5 0 Indi. Reset BI5 0 Indi. Reset

Figure 12.4-3 Steps to display Binary I/O status

(iii) Communication
The “Communication” sub-menu provides several sub-menus as shown in Figure 12.4-4.

Sub-menu sub-menu sub-menu


Monitoring Communication LAN

61580STAT

Figure 12.4-4 Menu hierarchy for Communication sub-menu


The display structure for each sub-menu is explained in the following sections:

LAN sub-menu: the communication port name and status are shown in a line.
When the IED has single communication module, or when the IED has
communication modules but a communication module is allowed to operate in
the IED, an operation status of the communication ports is shown, as shown
in Figure 12.4-5.

“LAN” sub-menu can display “PortStatus” and “NetMonitor status”. If


“NetMonitor” is running (active), the LCD screen will display a “>”mark.

GRL200 (Soft 033 & 037)


- 1394 -
6F2S1914 (0.37)

LAN
10:48 1/2
PortStatus >
NetMonitor Inactive

Figure 12.4-5 Display for LAN


If the status of a port is “UP”, it means that the communication link is working;
if the status of a port is “DOWN, it means that the LAN cable is not connected to
the port.

The following two sub-menus are displayed to show the communication status
when the IED has dual LAN communication modules.

PortStatus PortStatus
10:48 1/2 10:48 1/2
*Port1_Link UP *Port1_Link UP
Port2_Link DOWN Port2_Link UP

Port 1(Port A) is connected. Port 1&2 (Port A&B) are connected.


Port 2(Port B) is not connected.

Figure 12.4-6 Communication status

IEC61850 sub-menu: IP addresses of the devices connecting in IEC61850 are


shown in a straight line. Configurations of those IP addresses are available
with GR-TIEMS.

GRL200 (Soft 033 & 037)


- 1395 -
6F2S1914 (0.37)

61850STAT
10:48 1/6
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0

Figure 12.4-7 Display of IEC61850


(iv) Relay Elements
The names of relay elements and statuses of the operation are shown in respective columns.
To view all of the relay elements, the user has to press keys ▲ and ▼.

OC
10:48 1/25
OC1-A 0
OC1-B 0
OC1-C 0
OC2-A 0
OC2-B 0
OC2-C 0

Figure 12.4-8 Displaying Relay Elements


Figure 12.4-9 shows the steps necessary to display the status of the measuring elements.

Main Menu Main Menu Relay Element


10:48 2/9 10:48 2/9 10:48 1/4
Record > ► Metering > ► CBF >
_Monitoring > Binary I/O > EFP >
Setting > Communication > _OC >
IO setting >
◄ _Relay Element > ◄ EF >
Time > Statistics >
Test > GOOSE Monitoring >

► ◄

OC
10:48 1/25
OC1-A 0
OC1-B 0
OC1-C 0
OC2-A 0
OC2-B 0
OC2-C 0

Figure 12.4-9 Steps to display the status of measuring elements


GRL200 (Soft 033 & 037)
- 1396 -
6F2S1914 (0.37)

(v) Statistics
“Statistics” sub-menu has several sub-menus.

Sub-menu Sub-menu Sub-menu


Monitoring Statistics Power value

Counter
Accumulated Time
Operation Time
Operation Counter
Total Time

Figure 12.4-10 Menu hierarchy for Statistics


For each statistical item, with the exception of displaying their status, the data can be
reset or revised.

Power Value sub-menu: With regard to statistics item, the name and its value
are shown below. The user can also change the unit of each value by the
setting1. It is allowed to reset or revise the statistics value2.

Power Value
10:48 1/4
Wh+ +
0.0MWh
Wh- +
0.0MWh
varh+ +
0.0Mvarh

Figure 12.4-11 Display of Power Value


Table 12.4-1 Operation means for data reset or data revise
Step Display Operation key Remark
1 [>] ► Press ► key to go to the sub-menu
Press ENTER key to execute reset or revise. After
2 [+] ENTER
executing, a confirmation dialog screen displays.
1Note: In order to secure the reliability, the reset and revision items are controlled by the
vendor.
2Note: The number of digits for the power value can be reduced based on the units kW,
MW and kvar+. For instance, when the power is measured as "123,456kW" then it
is displayed as "123MW". If this value has to be changed then the user can key in a
new compensated value. For example, if "78MW" should be displayed on the IED
screen even though the measured value is "123,456kW" then the user should key in
the new value of "78MW". Note that the compensated value "78MW" is "78,000kW",

GRL200 (Soft 033 & 037)


- 1397 -
6F2S1914 (0.37)

and it is not "78,456kW" or "123,456kW". Note that the compensated value will be
affected when there is a change in CT ratio setting. That is, when the user key in a
value of "78MW" for the CT ratio of "2000:1" and later when the CT ratio is changed
from "2000:1" to "4000:1", then the value is displayed as "156MW" on the IED screen.
Therefore when the CT ratio setting is changed, the user should key in the value of
"78MW" again to display the compensated value.

Counter sub-menu: the name and number of statistical items are shown in
two lines. When an item is revised, a [+] mark is shown at the end of the first
line.

Counter
10:48 1/32
COUNT1 (No Assign) +
0
COUNT2 (No Assign) +
0
COUNT3 (No Assign) +
0

Figure 12.4-12 Display for Counter sub-menu


To change the counter number, follow the steps as shown in Figure 12.4-13.

GRL200 (Soft 033 & 037)


- 1398 -
6F2S1914 (0.37)

Main Menu Monitoring

You might also like