Professional Documents
Culture Documents
Applications
z Switch Centers
z Data Centers
z Large Fiber Repeaters
Key Features
z Providing up to 6000A
z Full current available to -58Vdc
z Wide input voltage window and enhanced AC
surge protection
z AC distribution and DC distribution cabinets
enable easy expansion
z LCD display for alarm and components status
z Optional remote monitor and control
3
DC Power System
PSM-A Controller
PSM-A is a microprocessor based monitoring and control unit that is used in PS481000-5/100 DC power
system. This unit has been specifically developed to provide DC power systems with monitoring,
management and indication. LCD front display and keyboard provide the system with operational
condition, setting and control. RS232 provides connectivity for remote monitoring via modem or
Monitoring Module PSNA card; meanwhile, dry contact provides remote alarms for the system. Multi-level password
PSM-A access is provided for safety operation
AC Distribution Cabinet
AC distribution cabinet is a stand-alone unit with two AC mains inputs. The mains power supply
mode is 3 phase / 5 line. There are three types of AC distribution cabinet, PD380/400AFH-2 and
PD380/600AFH-2 in manual switchover mode,PD380/630AFA in automatic switchover mode.
Lighting and surge protection system is integrated
AC Distribution Cabinet
PD380/400AFH-2
Key Features
z Integrated with local monitor, providing RS485 interface to communicate with controller
z Local display LCD shows all parameters, such as AC voltage, current, frequency, and status of lightning
protection
z Two AC mains input in manual or automatic switchover mode
DC Distribution Cabinet
DC distribution cabinet is a stand-alone unit with two battery inputs. There are two types of DC
distribution cabinet, PD48/2000DF and PD48/2500DF. Battery current and total load current are
detectable and the system also has local monitor, providing RS485 to communicate with controller
Key Features
DC Low Ohmic Distribution Cabinet z Integrated with local monitor, providing RS485 interface to communicate with controller
PD48/2000DF z Local display LCD shows all parameters, such as DC voltage, current, status of MCB and fuses
4
Business-Critical Continuity
Key Features
z Integrated with local monitor, providing RS485 interface to communicate with controller
z Local display LCD shows all parameters, such as DC voltage, current, frequency, status MCB and
fuses
z Up to 120 branches high ohmic output
Key Features
z Integrated with local monitor, providing RS485 interface to communicate with controller
z Local display LCD shows all parameters, such as AC and DC voltage, AC and DC current, frequency,
status of lightning protection, status of MCB and fuses
z Two AC mains input in manual or automatic switchover mode
z A combined cabinet can reduce the system's footprint.