Emerson Network Power

Business-Critical Continuity
for Communications

Enterprise Catalog
Outside Plant and DC Power Products & Systems

Emerson Enterprise Catalog : February 2007


Emerson Network Power
Energy Systems, North America
4350 Weaver Parkway, Warrenville, IL 60555
Toll Free OSP Tech Support: 800-800-5260 (USA and Canada)
Toll Free: 800-800-1280 (USA and Canada)
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems
EnergyNet: Secure.EmersonNetworkPower.com

Emerson Network Power.


The global leader in enabling business-critical continuity. EmersonNetworkPower.com

AC Power Embedded Power Precision Cooling


Connectivity Monitoring Racks & Integrated Cabinets
DC Power Outside Plant Services
Embedded Computing Power Switching & Controls Surge Protection

© 2007 Emerson Network Power Energy Systems, North America, Inc. All rights reserved.

This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing)
may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or
services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
conditions of supply of any product or service.

The Emerson logo is a trademark and a service mark of Emerson Electric Co. Emerson Network Power is a division of Emerson Electric Co.

Code: ESNA-102 / 02073M


Enterprise : February 2007
Table of Contents Business-Critical Continuity
for Communications
Enterprise Catalog

OUTSIDE PLANT
Building Entrance BUP Series Indoor/Outdoor Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
BEP Series Building Entrance Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
BEPNC Building Entrance Terminals (Indoor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
PROT300XLBET Extra-Large 300-Pair Protector/Cross-Connect System . . . . . . . . . . . . . . . . 9
Terminal Blocks URLS1010-Pair IDC Terminal Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
RLS Series IDC Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
R66M Series & Category 5 Non-Connectorized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
R66P25 Series 25-Pair Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
CO Connectors & Frames R399URLS 100-Pair Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2500FRAME2 (One Vertical) Single-Sided Distribution System. . . . . . . . . . . . . . . . . . . . . . . . 29
2500 Frame (Two Verticals) Single-Sided Distribution System. . . . . . . . . . . . . . . . . . . . . . . . 31
Protection 5-Pin Protector Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
SuperDuty® JZ380 Series Next Generation Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Reference Standards Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Remote Terminals DEC25/NG “Next Generation” Digital Equipment Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
MESA® 4 NxT Modular Electronic Sealed Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

DC POWER
Small Systems LORAIN® XP 4890 DC Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
LORAIN® XP 48500 DC Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
LORAIN® CIP 4890/48120 DC Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
LORAIN® CSP 48300 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Medium Systems NetSure™ 701NCBB DC Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
NetSure™ 701NVBB DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
LORAIN® VPS 246000 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
LORAIN® VPS 486000 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Large Systems LORAIN® PS 4810000 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
LORAIN® LVS 4810000 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
DC UPS NterpriseIP™ Solution, High Availability Power System for IP Telephony . . . . . . . . . . . . . . 113
Distribution Bays LORAIN® DB 48500 Battery Distribution Fuse/Circuit Breaker Bay. . . . . . . . . . . . . . . . . . . . 119
LORAIN® DB 484800 Battery Distribution Fuse/Circuit Breaker Bay. . . . . . . . . . . . . . . . . . . 121
Inverters LORAIN® IS 6000 Expandable Rack-Mounted Inverter System . . . . . . . . . . . . . . . . . . . . . . . 123

Enterprise : 
February 2007
Notice of Disclaimer Business-Critical Continuity
for Communications

This catalog, all products listed in it, and their availability are subject to change without notice. Emerson Network Power Energy
Systems, North America, Inc. disclaims any responsibility or liability for any damages resulting from the use of these products.
Before using, user shall determine the suitability of the product for its intended use, and user assumes all risk and liability what-
soever in connection therewith.

The following are trademarks of their respective companies:


Ethernet - Trademark of the Xerox Corporation
LORAIN - Registered trademark of Emerson Network Power Energy Systems, North America, Inc.
Megahertz - Registered trademark of 3Com Corporation
MESA - Registered trademark of Emerson Network Power Energy Systems, North America, Inc.
NEBS - Trademark of Telcordia Technologies
NetSure - Trademark of Emerson Network Power Energy Systems, North America, Inc.
NterpriseIP - Trademark of Emerson Network Power Energy Systems, North America, Inc.
SuperDuty - Registered trademark of Emerson Network Power Energy Systems, North America, Inc.
Vortex - Registered Trademark of Emerson Network Power Energy Systems, North America, Inc.

Additionally, this catalog may reference the following company trademarks: 3M®, AT&T®, FIAMM®, GTE® and LORAIN®.
Names of companies and products are trademarks or registered trademarks of the respective companies.

The above trademark listing is complete as we know it. Any questions regarding usage of trademark names should be directed
to the original manufacturer.

The Emerson logo is a trademark and a service mark of Emerson Electric Co.
Emerson Network Power is a division of Emerson Electric Co.

Enterprise : ii
February 2007
BUP Series Outside Plant for
Business-Critical Continuity
Indoor/Outdoor Protectors

Key Features
Description
• Compact size requires minimum
mounting space The BUP is an outdoor-rated, self-contained building entrance protector. Whether used
for indoor or outdoor applications, no additional closures are necessary. The BUP is manu-
factured of heavy gauge mill-galvanized steel treated with a unique finishing process for
• Outdoor mounting capability for
longer life. Input connection options include field splice tail, 3M® 4000-D dry connectors,
greater accessibility
710 filled connectors or cable stub. Outgoing pair distribution options are RLS IDC or
quiet-front binding post screw down terminal blocks.
• Built-in splice chamber provides
enhanced wire management The BUP series utilizes 5-pin protector modules housed in a sealed chamber-within-
and additional environmental a-chamber for maximum environmental protection, which is especially important for
protection outdoor applications. All UL listed standard 5-pin protector modules may be used with the
BUP series. (See section 11 of this catalog, entitled “Protection Arresters & Modules,” for a
• Patented sealed protector module full list of the protector modules offered by Emerson.)
chamber offers a direct outdoor
application of 5-pin protector The BUP is wall or pole-mountable. Units can be ordered as stackable to 300 pairs, or can
be made stackable with the addition of a stacking kit. The units can also be outfitted with
modules; reduces installation and
a cable skirt, providing protection to the feeder and distribution cable from incidental con-
maintenance costs
tact and from the environment. A 216-type can wrench (Emerson catalog no. 15 or 38) is
required in order to open the unit. For further security, each unit is also equipped with a
• Variety of input and output padlock hasp.
connections provides application
flexibility

• UL Listed for documented Application


performance
BUP building entrance
protectors provide a ter-
mination, protection, and
distribution point for 25,
50, or 100 pairs (stackable
to 300 pairs) from the cen-
tral office to the subscriber
premises. Potential appli-
cation locations include
multi-tenant dwelling com-
plexes, hospitals, factories,
shopping strips, schools, and
campus environments. BUPS50SE6

Dimensions
Pair Count H W D
25 & 50 15.00-in. (38.10 cm) 15.41-in. (39.14 cm) 4.70-in. (11.94 cm)
100 24.30-in. (61.75 cm) 15.41-in. (39.14 cm) 4.70-in. (11.94 cm)

Enterprise : 
OSPDS-040100 / 0505
BUP Series Indoor/Outdoor Protectors

Ordering Matrix
Housing BUP = Indoor/Outdoor Building Entrance Protector
Output S = RLS B = BT/CQF
Pair Count 25 = 25 pair 100 = 100 pair
50 = 50 pair
Input FS = Field splice - 18" wire harness bundle SE6 = 6 foot, 24 AWG stub
MM = 3M 4000-D dry, (MS2) SE12 = 12 foot, 24 AWG stub
CF = 710 filled, capless, receptacle SE25 = 25 foot, 24 AWG stub
Options SKT = Skirt compatible STK = Stackable (non-stubbed units)

Accessories
Catalog Number Part Number Description
BUPWM1 F019741 Metal wall-mounting bracket for 25 & 50-pair BUP (optional)
BUPWM2 F019735 Metal wall-mounting bracket for 100-pair BUP (optional)
BUPPM1 F019742 Metal pole-mounting bracket for 25 & 50-pair BUP & BUPNP1
BUPPM2 F019738 Metal pole-mounting bracket for 100-pair BUP & BUPNP2
BUPSKT F787554 Cable skirt for 25, 50, & 100-pair BUP, 28"H x 15.07"W x 6"D
BUPLONGSKT F740098 Cable skirt for 25, 50, & 100-pair BUP, 52"H x 15.07"W x 6"D
LOOSEPARTSNX2 F039419 Stacking kit for 25 & 50-pair BUP*
P52859 F552859 Stacking kit for 100-pair BUP*

* Each stacking kit joins two units only. If stacking three units, order two stacking kits. Also, unless the units have been ordered stackable, the end user may
have to make a hole at the top of the splice chamber for feeding the remaining cable splice through to the upper unit(s).

Pole-Mount Bracket for 25 and Wall-Mount Bracket for 25 and BUPSKT


50-Pair Closure BUPPM1 50-Pair Closure BUPWM1

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
 : Enterprise
OSPDS-040100 / 0505
BEP Series Outside Plant for
Business-Critical Continuity
Building Entrance Protectors

Key Features
Description
• Built-in splice chamber provides
material and installation cost The BEP series combine protection and distribution with a built-in splice chamber, for a
savings single, compact, cost-effective unit designed for indoor building entrance applications.
Central office pairs are connected with the following options: field splice, stub, 710 con-
nectors, 3M® dry connectors, 66 quick-clip block, or 110-style block. The BEP series also
• Lift-out protector panel facilitates
offers a 26AWG fuse link for added protection. Subscriber wires are connected via the
installation; reduces inventory following options: 66 quick-clip, RJ21, 66 quick-clip and RJ21, 110-style block, or binding
costs; is easy to repair posts.

• Compact size requires minimum The BEP series is available in 25, 50, and 100-pair sizes. The 100-pair unit is stackable to
mounting space 300-pair (stacking kit included in 100-pair). The protector modules can be included or
purchased separately. The closure is accessed using a 216-type tool.
• All units are stackable to
accommodate future growth
Application
• Gold-plated protector contacts
minimize noise and customer The BEP series terminate, protect, and distribute central office cable pairs on the subscrib-
complaints er premises. They are ideal for use in multi-tenant dwelling and PABX installations.

• Rugged metal housing made of


mill-galvanized steel for durability
and low maintenance costs

• Designed to meet Telcordia


TR-TSY-000299 and RDUP
(formerly RUS) specifications for
documented performance

• UL Listed with industry standard
5-pin protector modules (gas
or solid-state); for documented
performance

• 26AWG 18-in. fuse link for added Quick-clip In/Quick-clip and RJ21 Out
protection

• Lock hasp provided for added
security

Enterprise : 
OSPDS-080900 / 0605
BEP Series Building Entrance Protectors

Dimensions
Pair — Housing Dimensions —
Count H W D
25/50/100 15.00-in. (38.10 cm)* 15.41-in. (39.14 cm) 4.7-in. (11.94 cm)

* 100-pair with binding posts has a 36-in. (91.44 cm) height.


NOTE: All dimensions are measured in inches, with metric conversions in parentheses.

Ordering Matrix
Housing BEP = Building Entrance Protector
Output C = 66 Quick-clip block
BEPC25C (25-pair) G = RJ21 receptacle connector
Quick-clip In & Out CG = 66 Quick-clip block & RJ21 receptacle connector
B = Binding posts
T = 110-style block
Pair Count 25 = 25-pair
50 = 50-pair
100 = 100-pair**
Input FS = Field Splice, 18-in. tail
CF = 710 connector, capless, receptacle, gel-filled,
18-in. tail, 26AWG fuselink
MM = 3M 4000-D dry (MS2), 18-in. tail, 26AWG fuselink
C = 66 Quick-clip block, 26AWG fuselink
SC = 24AWG cable stub
BEPC100MM (100-pair) T = 110-style block, 26AWG fuselink
3M® Dry Connector In/Quick-clip Out Cable Full Length 6 = 6-ft.
(only if "sc" input) 12 = 12-ft.
25 = 25-ft.
blank = Stubless

** 100-pair includes stacking kit


NOTE: To order with 5 protector modules installed, call customer service.

Accessories
Catalog Part
Number Number Description
P35980 F535980 Grommets for 1-in. diameter hole (pkg. of 20)
P47839 F547839 U-shaped grommet
P47147 F547147 Cup-sems with push nut (pkg. of 10)

NOTE: For additional accessories, see the Accessories section of the catalog.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
 : Enterprise
OSPDS-080900 / 0605
BEPNC Outside Plant for
Business-Critical Continuity
Building Entrance Terminals (Indoor)

Key Features
Description
• Integrated stand-off bracket allows
for easy distribution and cable The BEPNC series combines protection and distribution, for a single, compact, cost
routing effective unit designed for indoor building entrance applications. Central office pairs are
connected with the following options: stub, 66 quick-clip block, 110 style block, or the
Emerson pair-at-a-time tool-less URLS block. The BEPNC also offers a 26 AWG fuse link for
• Wall or frame mountable
added protection. Subscriber connection options include: 66 quick-clip, 110 style block or
Emerson URLS block.
• Compact size requires minimum
mounting space The BEPNC series is available in 100, 50, 25, 10-pair sizes. All BEPNC terminals are stack-
able. Protector modules can be included or purchased separately.
• All units are stackable to
accommodate future growth
Application
• Available in various configurations,
66, 110, URLS, 710 as well as The BEPNC series terminates, protects, and distributes central office cable pairs at the
factory stubbed subscriber premises. They are ideal for use in multi-tenant office buildings, high-rise apart-
ments, campus environments and PABX installations.
• Available pair counts: 100, 50, 25
and 10

• Gold-plated protector contacts


minimize noise and customer
complaints

• The patented Emerson silo


protector block improves
attenuation, cross talk and
insulation resistance and conforms
to Telcordia GR-29lb.

• External ground lug for building


ground or connecting additional
units 100-Pair Wall-Mount Terminal 100-Pair Wall Mount Terminal
with 110 In/110 Out with 66 In/66 Out
• 26 AWG fuse link for added
protection

• Accommodates industry standard


5-pin protector modules

• Optional panel cover

• Designed to meet or exceed


UL497 requirements

Enterprise : 
OSPDS-081500 / 0605
BEPNC Building Entrance Terminals (Indoor)

Ordering Matrix
Terminal Protector BEPNC = Indoor Wall-Mount
Output C = Quick-clip block
T = 110-style block
U = URLS-style block
Pair Count 100 = 100-pair
50 = 50-pair
25 = 25-pair
10 = 10-pair
Input C = Quick-clip block, 26 AWG fuselink
SC = 26 AWG cable stub
T = 110-style block, 26 AWG fuselink
U = URLS-style block, 26 AWG fuselink
Input Cable Stub Length 25 = 25-ft.
12 = 12-ft.
6 = 6-ft.
Blank = Stubless

NOTE: To order with 5-pin protector modules installed, call customer service.

Three Units Stacked Vertically Wall-Mount Terminal with Cover


(Cover Sold Separately)

 : Enterprise
OSPDS-081500 / 0605
BEPNC Building Entrance Terminals (Indoor)

Ordering Information & Dimensions


Catalog Part Pair
Number Number Count Input Output H W D
Stubless Wall-Mount Terminals
BEPNCT100T F1005281 100 110 110 14.50-in. 10.75-in. 4.75-in.
BEPNCT50T F1005282 50 110 110 8.12-in. 10.75-in. 4.75-in.
BEPNCT25T F1005283 25 110 110 6.12-in. 10.75-in. 4.75-in.
BEPNCT10T F1005284 10 110 110 5.27-in. 5.61-in. 2.75-in.
BEPNCC100C F1005285 100 66 66 11.00-in. 14.50-in. 4.50-in.
BEPNCC50C F1005286 50 66 66 9.65-in. 11.50-in. 4.50-in.
BEPNCC25C F1005287 25 66 66 6.15-in. 10.75-in. 4.50-in.
BEPNCC10C F1005288 10 66 66 3.80-in. 8.10-in. 3.82-in.
BEPNCU100U F1005397 100 URLS URLS 16.15-in. 10.81-in. 4.00-in.
BEPNCU50U F1005398 50 URLS URLS 9.62-in. 10.81-in. 4.00-in.
BEPNCU25U F1005399 25 URLS URLS 8.10-in. 10.81-in. 4.00-in.
BEPNCU10U F1005400 10 URLS URLS 6.00-in. 6.10-in. 3.15-in.
26 AWG Stubbed Wall-Mount Terminals
BEPNCT100SC25 F1005289 100 Stub 110 10.75-in. 10.75-in. 4.75-in.
BEPNCT50SC25 F1005290 50 Stub 110 6.12-in. 10.75-in. 4.75-in.
BEPNCT25SC25 F1005291 25 Stub 110 6.12-in. 10.75-in. 4.75-in.
BEPNCT10SC6 F1006011 10 Stub 110 5.27-in. 5.61-in. 2.75-in.
BEPNCC100SC25 F1005292 100 Stub 66 18.65-in. 8.50-in. 4.50-in.
BEPNCC50SC25 F1005293 50 Stub 66 9.65-in. 8.50-in. 4.50-in.
BEPNCC25SC25 F1005294 25 Stub 66 6.15-in. 8.00-in. 4.50-in.
BEPNCC10SC6 F1006012 10 Stub 66 3.80-in. 6.11-in. 3.82-in.
BEPNCU100SC25 F1005401 100 Stub URLS 12.25-in. 10.81-in. 4.00-in.
BEPNCU50SC25 F1005402 50 Stub URLS 8.12-in. 10.81-in. 4.00-in.
BEPNCU25SC25 F1005403 25 Stub URLS 8.00-in. 7.30-in. 4.00-in.
BEPNCU10SC6 F1005990 10 Stub URLS 6.00-in. 6.10-in. 3.20-in.

NOTE: For more information and other configurations, call customer service.

100-Pair Wall-Mount Terminal 100-Pair Wall Mount Terminal


with Stub In/66 Out with Stub In/110 Out

Enterprise : 
OSPDS-081500 / 0605
BEPNC Building Entrance Terminals (Indoor)

Accessories
Catalog Number Part Number Description
BEPNC110COVER1 F1005299 100-pair BEPNC Cover Kit (Non-Stub)
BEPNC66COVER1 F1005300 100-pair BEPNC Cover Kit (Non-Stub)
BEPNCURLSCOVER1 F1005991 100-pair BEPNC Cover Kit (Non Stub)
BEPNC110COVER2 F1005384 50-pair BEPNC Cover Kit (Non-Stub)
BEPNC66COVER2 F1005385 50-pair BEPNC Cover Kit (Non-Stub)
BEPNCURLSCOVER2 F1005992 50-pair BEPNC Cover Kit (Non Stub)
BEPNC110COVER3 F1005386 25-pair BEPNC Cover Kit (Non-Stub)
BEPNC66COVER3 F1005387 25-pair BEPNC Cover Kit (Non-Stub)
BEPNCURLSCOVER3 F1005993 25-pair BEPNC Cover Kit (Non Stub)
BEPNC110COVER4 F1005388 10-pair BEPNC Cover Kit (Non-Stub)
BEPNC66COVER4 F1005389 10-pair BEPNC Cover Kit (Non-Stub)
BEPNCURLSCOVER4 F1005994 10-pair BEPNC Cover Kit (Non Stub)
BEPNC110COVER5 F1005382 100-pair BEPNC Cover Kit (Stub)
BEPNC66COVER5 F1005383 100-pair BEPNC Cover Kit (Stub)
BEPNCURLSCOVER5 F1005995 100-pair BEPNC Cover Kit (Stub)
BEPNC110COVER6 F1005325 50-pair BEPNC Cover Kit (Stub)
BEPNC66COVER6 F1005326 50-pair BEPNC Cover Kit (Stub)
BEPNCURLSCOVER6 F1005996 50-pair BEPNC Cover Kit (Stub)
BEPNC110COVER7 F1005330 25-pair BEPNC Cover Kit (Stub)
BEPNC66COVER7 F1005327 25-pair BEPNC Cover Kit (Stub)
BEPNCURLSCOVER7 F1005997 25-pair BEPNC Cover Kit (Stub)
BEPNC110COVER8 F1005328 10-pair BEPNC Cover Kit (Stub)
BEPNC66COVER8 F1005329 10-pair BEPNC Cover Kit (Stub)
BEPNCURLSCOVER8 F1005998 10-pair BEPNC Cover Kit (Stub)

NOTE: For more information and other configurations, call customer service.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
 : Enterprise
OSPDS-081500 / 0605
PROT300XLBET Outside Plant for
Business-Critical Continuity
Extra-Large Building Entrance 300-Pair
Protector / Cross-Connect System

Key Features
Description
• Terminates and protects up to
1800 copper pairs in only three The PROT300XLBET is a 300-pair protector and cross-connect panel which provides pro-
square feet of floor space for high tection, termination and cross-connection of copper pairs on opposite sides of a single
23-inch telco relay rack. It is designed for large pair count installations to provide termi-
density applications.
nation and protection up to 1800 copper pairs in only three square feet of floor space.
• Protection for central office Industry standard 5-pin protector modules, 5-pin protector blocks, 110, BIX® or Emerson
applications, building entrance, pair-at-a-time tool-less URLS termination blocks, and 7-foot frames have been incorpo-
and distribution frames with rated in a craft-friendly design that scales from 300 to thousands of copper pairs.
multiple cabling options such as
top or bottom entry, 25 or 50- This product is ideal for applications where future growth is expected, but initial instal-
lation size is minimized to control the cost. The min-imum configuration is one 300-pair
ft. stubs, and 25 or 32-pair RJ21
panel on a 23-inch steel rack and 5-pin protector modules to match the actual pair count.
connectors.
300-pair panels are added as the pair count need increases. The innovative, hinged, split
• Factory wired panels eliminate protector panel allows new cables to be dressed safely into existing panels. Unused rack
cabling errors, decrease installation space can be used for other equipment once growth stops.
time, and reduce project costs. Use
Complete 1800-pair rack systems can be ordered for larger applications. These systems
of standard components reduces
include the 7-foot rack, six of the 300-pair panels, 1800 of the 5-pin protector modules
training time and user errors. The
and horizontal troughs for managing jumper wires between racks. Rack systems may be
PROT300XLBET provides a system mounted side by side to meet growing system requirements.
with minimum jumper runs and
efficient use of space. Telecommunications relay rack applications are easier and more versatile with the com-
bined protection and cross-connect features of the PROT300XLBET.
• Available in various cross-connect
configurations: 110, BIX® and
The PROT300XLBET is the result of continuous design reviews with industry consultants,
URLS. contractors, telecommunication engineers and end users.
• Cable stubs are dressed down the
center of the frame for weight
balance and safety. Application
• Hinged, split protector panel
The PROT300XLBET is intended for
is designed for adding and
building entrance termination, main dis-
rearranging stubs.
tribution frame and building distribution
• Adjustable stub allows for up or frame applications where copper cable
down installation of stub. is terminated and protected in one com-
pact 7- foot frame. Outside plant cable
• The patented Emerson silo is usually terminated in a standard splice
protector block improves case where the cable enters the build-
attenuation, cross talk and ing. The stubs from the PROT300XLBET
insulation resistance and conforms are spliced to the outside plant cable
to Telcordia GR-2916. at the splice case by the installer. The
stubs are factory prewired to the OSP
• Uses industry standard termination side of the 5-pin protector blocks in the
blocks and 5-pin protector PROT300XLBET.
modules.

• Side guards prevent accidental


removal of 5-pin protector modules.

Enterprise : 
OSPDS-084500 / 0906
PROT300XLBET
Extra-Large Building Entrance 300-Pair Protector / Cross-Connect System

Key Features (cont.)

• 26 AWG fuse link cable section is


provided.

• All interconnect wiring and stubs


are 24 AWG for maximum perfor-
mance and life.

• 6 AWG ground cable is provided.

• UL and NEBS™ Seismic Zone 4


compliant. PROT300XLBET PROT300XLBET
Protection Side 110 Cross-Connect Side
• Wire management brackets for
vertical jumpers between panels
are provided.
Dimensions
• Side lift handles further simplify Pair count H W D Estimated weight (lbs.)
rack mounting. ­ 300-pair (25-ft. stub) 11.5-in. 23-in. 18.8-in. 115
300-pair (50-ft. stub) 11.5-in. 23-in. 18.8-in. 155
• Key hole mounting permits fast
1800-pair system (25-ft. stub) 84-in. 23-in. 18.8-in. 995
and easy panel installation.
1800-pair system (50-ft. stub) 84-in. 23-in. 18.8-in. 1235

Ordering Information
Catalog number Part number Description
300-Pair Protector & Cross-Connect Panels with 110 IDC Termination Blocks
PROT300XLBET251A F1005404 Includes 25-ft. stub and 25-pair RJ21 connectors
PROT300XLBET251B F1005405 Includes 25-ft. stub and 32-pair RJ21 connectors
PROT300XLBET501A F1005406 Includes 50-ft. stub and 25-pair RJ21 connectors
PROT300XLBET501B F1005407 Includes 50-ft. stub and 32-pair RJ21 connectors
300-Pair Protector & Cross-Connect Panels w/BIX® IDC Termination Blocks
PROT300XLBET251C F1005849 Includes 25-ft stub and 25-pair RJ21 connectors
PROT300XLBET251D F1005948 Includes 25-ft stub and 32-pair RJ21 connectors
PROT300XLBET501C F1005958 Includes 50-ft stub and 25-pair RJ21 connectors
PROT300XLBET501D F1005959 Includes 50-ft stub and 25-pair RJ21 connectors
300-Pair Protector & Cross-Connect Panels w/URLS Pair-at-a-time Tool-less Termination Blocks
PROT300XLBET251E F1005960 Includes 25-ft stub and 25-pair RJ21 connectors
PROT300XLBET251F F1005961 Includes 25-ft stub and 32-pair RJ21 connectors
PROT300XLBET501E F1005962 Includes 50-ft stub and 25-pair RJ21 connectors
PROT300XLBET501F F1005963 Includes 50-ft stub and 25-pair RJ21 connectors

Caution: All XLBET protector and cross-connect panels and 1,800-pair systems come supplied
with 48-in. 26AWG fuse link cables which must be enclosed in a locally provided splice case or shroud.

10 : Enterprise
OSPDS-084500 / 0906
PROT300XLBET
Extra-Large Building Entrance 300-Pair Protector / Cross-Connect System

Ordering Information
Catalog number Part number Description
1800-Pair Protector & Cross-Connect Frame Systems with 110 IDC Termination Blocks
1800XLBET25SYST1A F1005408 (1) RRACKXLBET relay rack; (6) PROT300XLBET251A 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET25SYST1B F1005409 (1) RRACKXLBET relay rack; (6) PROT300XLBET251B 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1A F1005410 (1) RRACKXLBET relay rack; (6) PROT300XLBET501A 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1B F1005411 (1) RRACKXLBET relay rack; (6) PROT300XLBET501B 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800-Pair Protector & Cross-Connect Frame Systems with BIX® IDC Termination Blocks
1800XLBET25SYST1C F1005850 (1) RRACKXLBET relay rack; (6) PROT300XLBET251C 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET25SYST1D F1004896 (1) RRACKXLBET relay rack; (6) PROT300XLBET251D 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1C F1005951 (1) RRACKXLBET relay rack; (6) PROT300XLBET501C 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBEY50SYST1D F1005952 (1) RRACKXLBET relay rack; (6) PROT300XLBET501D 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800-Pair Protector & Cross-Connect Frame Systems with URLS Pair-at-a-time Tool-less IDC Termination Blocks
1800XLBET25SYST1E F1005953 (1) RRACKXLBET relay rack; (6) PROT300XLBET251E 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET25SYST1F F1005954 (1) RRACKXLBET relay rack; (6) PROT300XLBET251F 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1E F1005955 (1) RRACKXLBET relay rack; (6) PROT300XLBET501E 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1F F1005956 (1) RRACKXLBET relay rack; (6) PROT300XLBET501F 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs

Caution: All XLBET protector and cross-connect panels and 1,800-pair systems come supplied with
48-in. 26AWG fuse link cables which must be enclosed in a locally provided splice case or shroud.

Enterprise : 11
OSPDS-084500 / 0906
PROT300XLBET
Extra-Large Building Entrance 300-Pair Protector / Cross-Connect System

1800XLBET System 1800XLBET System


Protection Side 110 Cross-Connect Side

Accessories
Catalog Number Part Number Description
RRACXLBET F1004898 Steel relay rack 7-ft. x 23-in. x 6-in. ( H x W x D), 500 lbs., NEBS™ Zone 4 load rating: 1000 lbs. static load
R4C1EJZ F013440 5-pin gas protector module with heat coils and front test points
300PRTROUGH F1005412 23-in. horizontal wire management 4-in. x 23-in. x 2-in. ( H x W x D)
FUSELINK F1005740 100-pair connectorized (MS2 both ends) cable tie, 48-in. 26AWG

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
12 : Enterprise
OSPDS-084500 / 0906
URLS10 Outside Plant for
Business-Critical Continuity
10-Pair IDC Terminal Block

Key Features
Description
• No tools required for pair-at-a-time
ActCap connections The URLS10 is an indoor/outdoor 10-pair terminal block for connecting solid copper com-
munications wire. All connections are IDC (insulation displacement connection), made
without removing the insulation from the wire. The contact terminals slice through the
• IDC termination on all connections
insulation and create a gas-tight contact at the copper/terminal interface.
for fast, easy termination and
jumpering with no wire stripping Two models are available – the URLS10 for indoor installations, and the sealant-filled
URLS10S for use in outdoor or environmentally-challenging installations. Both models are
• Sealant-filled connectors on assembled from two primary components – a URLS connector module and a URLS base.
the URLS10S provide moisture
resistance and longer-life The connector module contains metallic contacts that provide electrical and test con-
termination for environmentally- nections. Located on the top of the connector module, ten ActCaps guide single-pair
challenging installations cable into proper terminating position, connecting the cable pair to the metallic contacts.
Wires are then terminated by pressing down on the ActCap, requiring only a push of the
• Half-tap capability permits installer’s thumb. The ActCaps can terminate 20- through 26-gauge (.4 to .8 mm) con-
ductors. Test results verify that ActCaps can terminate 24-gauge wire more than 250
multiple appearances of jumper
times with stable, low contact resistance.
wire
The base can terminate 22- through 26-gauge (.4 to .6 mm) conductors. Up to 10 pairs
• Continuity and directional testers from the incoming cable stub can be terminated on the base using an available termi-
provide more complete testing of nation tool. Wires are cut to the proper length during the termination process. Tools
the circuit are available for either ten-pair-at-a-time (URLSFIXTURE) or single-wire termination
(URLSTOOL1). The single-wire termination tool is perfect for low pair count installations,
• Variety of frame pair counts and cable repair, and maintenance.
sizes for maximum application and
installation flexibility URLS blocks are molded from glass-filled Valox for long-term performance. Electrical
terminals are fabricated from tin-plated phosphor bronze for low contact resistance. The
sealant used in the URLS10S protects against corrosion caused by high humidity and salt
• Compact size makes URLS ideal for
in street-side and coastal installations.
applications where space is limited
URLS blocks can be mounted to industry-standard 4.12-in. (10.4 cm) wide mounting
• Available installed in cross-connect frames in a variety of pair counts. Close-pitch frames are available for higher terminal den-
and building entrance terminals to sity. Rod mount kits are also available.
fit a variety of applications

• UL Listed and CE Marked for


documented performance and
Application
safety compliance
These blocks can be used in a variety
of indoor and outdoor distribution,
cross-connect, and building entrance appli-
cations. The URLS10 is designed for copper
wire terminals and cross connect systems
throughout the communications network.
It is ideal for use in outdoor remote elec-
tronic equipment enclosures with limited
space for wire termination.

Enterprise : 13
OSPDS-060100 / 0505
URLS10 10-Pair IDC Terminal Block

Figure 1: URLS Block Figure 2: Connector Module and Base


a) Single Pair Tester ActCap
b) Single Pair URLS Half Tap
Incoming Wire
c) Single Pair Disconnect Plug
d) Red Special Service Cap

Ordering Information & Dimensions


Catalog Number Part Number Description H W D
URLS10 F800799 10-pair URLS IDC terminal block 31.75mm (1.25-in.) 129.29mm (5.09-in.) 16.51mm (0.65-in.)
URLS10S F800800 10-pair URLS IDC terminal block w/sealant 31.75mm (1.25-in.) 129.29mm (5.09-in.) 16.51mm (0.65-in.)

NOTE: Dimensions with base assembly installed.

Accessories
Catalog Number Part Number Description Fig.
URLS1TEST1M F800801 Single-pair (continuity-bridge) tester w/one-meter test cord 2 wire # 6 Ring term (Fig. 2) 1a
URLS2TEST1M F800802 Single-pair break tester w/one meter test cord 4 wire # 6 Ring term (Fig. 2) 1a
URLSHALFTAP F800804 Single-pair URLS half-tap, 10/pkg. (Fig. 2) 1b
URLSHALFTAP10S F800572 Single-pair URLS half-tap with sealant, 10/pkg. (Fig. 2) 1b
URLSDISCPLUG1 F800803 Single-pair disconnect plug, 100/pkg. (Fig. 2) 1c
URLSDISCPLUG10 F596092 10-pair disconnect plug 10/pkg. 1c
URLSTOOL1 F1001087 Single-wire incoming cable grooming and terminating tool
URLS10TERMFM F800569 10-pair incoming frame mount cable grooming and terminating tool
RLSBBIDENT1800B F017865 Pair identification plugs for 1-1800 pairs (Blue)
RLSBBIDENT1800G F017866 Pair identification plugs for 1-1800 pairs (Green)
RLSFRAME50 F607095 Metal frame for mounting up to five URLS 10-pair blocks (50 pair)
RLSFRAME60 F017809 Metal frame for mounting up to six URLS 10-pair blocks (60 pair)
URLS10TERMRM F1002830 10-pair feeder termination tool rod mount
URLSCAPRED F800568 Special service caps (Red) 100/pkg. 1d

NOTE: Rear mounted protection cartridge for overvoltage protection available soon. Contact customer service.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
14 : Enterprise
OSPDS-060100 / 0505
RLS Series Outside Plant for
Business-Critical Continuity
IDC Terminal Block

Key Features
Description
• No special tools required for ease
of installation The RLS Series blocks consist of compact, IDC (insulation displacement connection) wire
connectors, which provide fast, easy connection of 22 to 26 gauge ( .4 to .6 mm) wire.
Each connector is silicone-grease filled with tin-plated terminals, providing maximum
• Silicone grease-filled connectors
environmental protection for terminated pairs.
provide moisture resistance and
longer life termination The RLS Series includes blocks for 2 to 50-pairs. Pair-at-a-time wire termination is accom-
plished by lifting the RLS activator, inserting a pair of unstripped wires into the appropriate
• Pair-at-a-time IDC termination slots on the activator, and pressing firmly down on the activator.
allows fast, easy jumpering with no
wire stripping The 2 and 5-pair blocks are internally wired, with RLS input and output. The 10, 25, and
50-pair blocks are potted on the rear side of the block, and are available in a variety of har-
• Half-tap capability permits ness lengths, with or without connectors.
multiple appearances of jumper
wire
Application
• Variety of harness lengths and
connectors for ease of use and The RLS family of blocks is a flexible terminal block that can be employed in a wide variety
consistency with telco standards of cross-connect or building entrance applications. These blocks are ideal for outdoor use.

• Available installed in cross-connect


and building entrance terminals to
fit a variety of applications

• Designed to meet Telcordia 1195


specifications to ensure reliable
performance

RLS50 Wires Inserted into RLS Activator

Enterprise : 15
OSPDS-060700 / 0505
RLS Series IDC Terminal Block

Dimensions
Catalog Number H W D
RLS2X2 1.06-in. (2.69 cm) 2.66-in. (6.76 cm) 1.50-in. (3.81 cm)
RLS5X5 1.06-in. (2.69 cm) 5.50-in. (13.97 cm) 1.50-in. (3.81 cm)
RLS10 1.06-in. (2.69 cm) 5.50-in. (13.97 cm) 1.50-in. (3.81 cm)
RLS25 5.38-in. (13.67 cm) 2.88-in. (7.32 cm) 1.50-in. (3.81 cm)

RLS2X2 RLS50 5.68-in. (13.67 cm) 5.06-in. (12.85 cm) 1.50-in. (3.81 cm)

Ordering Information
Catalog Number Part Number Pair Count Input Description
RLS2X2* F016996 2 RLS IDC Internally wired unit
RLS5X5* F016998 5 RLS IDC Internally wired unit
RLS10 F016997 10 26 AWG harness Equipped with 5.5-ft. (1.68 m) harness
RLS25 F017812 25 26 AWG harness Equipped with 2.5-ft. (0.76 m) harness
RLS254 F001095 25 26 AWG harness Equipped with 4-ft. (1.21 m) harness & 3M® 4005-DPM connector
RLS25DPM F017814 25 MS2 Equipped with 6-ft. (1.82 m) harness & 3M® 4005-DPM connector
RLS255DPM F005313 25 MS2 Equipped with 5-ft. (1.52 m) harness & 3M® 4005-DPM connector
RLS25CF F005315 25 710 Equipped with 6-ft. (1.82 m) harness & 710 connector
RLS50 F016950 50 26 AWG harness Equipped with 7-ft. (2.13 m) harness
RLS50DPM F016945 50 MS2 Equipped with 6-ft. (1.82 m) harness & 3M® 4005-DPM connectors
RLS507FT3M4005 F003043 50 MS2 Equipped with 7-ft. (2.13 m) harness & 3M® 4005-DPM connectors
RLS507FT3M4000 F003044 50 MS2 Equipped with 7-ft. (2.13 m) harness & 3M® 4000-D connectors
RLS50CBM6 F016941 50 MS2 Equipped with 6-ft. (1.82 m) harness & 3M® 4005-CBM connectors
RLS50PVC20 F300300 50 26 AWG stub Equipped with 20-ft. (6.09 m) PVC-sheathed cable stub

* With the exception of the RLS2X2 and RLS5X5, when used in cross-connect applications, the input termination style listed refers to the feeder side
termination. The output termination style would, of course, be reserved for the distribution side.
NOTE: For other harness lengths and/or connector types, please contact your Emerson customer service representative.

Accessories
Catalog Number Part Number Description
RLSACTGRAY10 F567272 Gray replacement activators, 10/pkg.
P71082 F571082 Red RLS activators, 5/pkg.
RLSTEST1 F019128 1-pair tester with 5-ft. leads & ring terminals for RLS and 3M® SS-25
RLSTEST1PKT F019127 1-pair pocket tester w/ring terminals for RLS and 3M® SS-25
TS50RLS1S F019139 50-pair stackable test shoe for RLS50 w/carrying case
P53828 F553828 Red special service caps, 30/pkg.
P60209 F560209 Half-tap activator, 80/pkg.

NOTE: For testing equipment, tools, labels, and other accessories, please see the Accessories section of this catalog.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
16 : Enterprise
OSPDS-060700 / 0505
R66M Series & Category 5 Outside Plant for
Business-Critical Continuity
Non-Connectorized

Key Features
Description
• Impact-resistant molded housings
provide long life and lower R66M series non-connectorized 12, 25 or 50-pair quick-clip blocks are manufactured of UL
maintenance costs Listed 94 V-0 rated material and are designed for fast, easy termination of insulated solid
copper wire. Blocks are easily stackable for higher pair counts.
• Notched fanning strips for ease of
The R66M series has a clip capacity of 50 horizontal rows by 4 vertical rows. Unstripped
wire tracing, identification, and solid 20 to 26-gauge conductors (.4 to .8 mm) can be easily terminated using the industry
good housekeeping standard 714-type punch-down tool (Emerson R714B).

• R66M150 blocks meet The Category 5 R66M150 blocks comply with EIA/TIA-568 Category 5 specifications,
EIA/TIA-568 Category 5 which recognizes only 24-gauge UTP (unshielded twisted pair) horizontal wiring. These
specifications to exceed blocks provide the highest transmission performance for speeds up to 100 Megahertz per
documented performance levels; second, while decreasing attenuation, near-end crosstalk, and return loss.
conforms to state-of-the-art LAN
systems for high speed data R66M series blocks are supplied with integral fanning strips molded on each side of the
block and notched every ten rows for easy identification. The blocks are also available
mounted in gray or beige molded impact-resistant plastic housings.
• Category 5 provides network
flexibility to handle emerging voice
and data applications
Application
• Category 5 supports data rates up
to 100 Megahertz per second for R66M series blocks are used in equipment rooms to cross-con-
network flexibility nect key telephone and PBX systems. The blocks terminate
25 twisted pair station cable and have cross-connect features
from key service units to station equipment. These blocks are
• UL Listed to meet or exceed
also used to connect a private branch exchange to its stations.
documented performance levels The R66M series is used on all types of customer premises and
central office equipment, including T1 and data connections.

The Category 5 series give users the ability to support virtu-


ally all data and voice applications conforming to the level of
wiring used with the block. When used with Level 5 wiring,
the Category 5 series blocks support the most advanced
applications such as FDDI over copper, and other high speed
applications. The Category 5 series blocks with Level 4 wiring
support data up to 20 Megahertz for token ring or equivalent
applications, and with Level 3 wiring, the block supports data
up to 16 Megahertz for T2 equivalent applications.

R66M150X

Enterprise : 17
OSPDS-070100 / 0605
R66M Series & Category 5 Non-Connectorized

Clip Configurations
All dimensions are as measured in inches, R66M112 R66M125X and R66M150X
with centimeter conversions in paren-
theses. Block depth is 1.25-in. (3.18 cm).
Cover depth is 2.34-in. (5.94 cm).

R66M112

R66M125X

R66M125MH and R66M150MH

R66M150X

R66M125MH

R66M150MH

18 : Enterprise
OSPDS-070100 / 0605
R66M Series & Category 5 Non-Connectorized

Clip Configurations
All dimensions are as measured in inches, R66M250MH, R66M275MH and R66M2100MH
with centimeter conversions in parentheses.
Block depth is 1.25-in. (3.18 cm). Cover
depth is 2.34-in. (5.94 cm).

R66M250MH

R66M275MH

R66M2100MH

Enterprise : 19
OSPDS-070100 / 0605
R66M Series & Category 5 Non-Connectorized

Ordering Information
Catalog Part Pair Common Std. Category
Number Number Description Count Clips Pkg. 5
M Series Blocks
R66M112 F015151 12-pair M block 12 2 25
R66M125X F015072 25-pair M block, bulk pack 25 4 50
R66M150X F015213 50-pair M block, bulk pack 50 2 50 √
M Series Blocks With Plastic Base (white) and Cover (gray)*
R66M125MH F015315 25-pair M block 25 4 5
R66M150MH F015317 50-pair M block 50 2 5 √
R66M250MH F015319 (2) 25-pair M block 50 4 5
R66M275MH F015323 (1) 25-pair M block/ (1) 50-pair 75 4-2 —
R66M2100MH F015321 (2) 50-pair M block 100 2 5 √
Empty Housings
P22314 F522314 Small beige housing, accommodates one block
P22315 F522315 Large beige housing, accommodates two blocks
P22338 F522338 Small gray housing, accommodates one block
P22339 F522339 Large gray housing, accommodates two blocks

* If product is desired in a beige closure, place a B at the end of the catalog number.
NOTE: Not all catalog numbers can be configured. For brackets, covers, bridging clips, etc. see the “66 Block Accessories” in the Accessories section
of this catalog.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
20 : Enterprise
OSPDS-070100 / 0605
R66P25 Series Outside Plant for
Business-Critical Continuity
25-Pair Protection

Key Features
Description
• Optional quick-clip, RJ21, or
stub interfaces meet a variety of The R66P25 series of indoor blocks offers protection for 25-pair in a compact, versatile,
installation requirements and cost-effective unit. These blocks have the same mounting dimensions as a 66M150
block, and can be mounted on a wall, backboard, or 89-type bracket (Emerson R891
Series and R89B).
• Provides FCC RJ21X demarcation
for separation of telco central Standard network cable termination options are either quick-clips or a cable stub.
office pairs from customer Customer premise equipment termination options are quick-clips or 50-position RJ21 con-
premises equipment nectors.

• Universal hold-down keeps Unstripped solid 20 to 26-gauge (.4 to .8 mm) conductors can be easily terminated using
connectorized RJ21s mated an industry standard 714-type punch-down tool (Emerson R714B). Each block is supplied
with an integral fanning strip molded on one side of the base, marked every five rows to
• Compact design is high density simplify pair identification.
and has the same mounting
Units may be ordered with or without factory-installed 5-pin protector modules. To order
dimensions as the standard
the R66P25 with factory-installed protection, add selected Emerson protector module
66M150
catalog numbers (R3B1EJZ, 3GUVS, etc.) to the catalog number. The R66P25 series will
accept carbon, gas, or solid-state 5-pin protector modules. One module provides pro-
• Mounts on standard 89-type tection for one pair, and each unit can accommodate 25 modules. Each R66P25 is also
brackets for dynamic allocation of supplied with a ground connector for a 6AWG solid copper wire.
wires on wall- or frame-mounted
applications

• UL Listed to meet or exceed


Application
documented performance levels
The R66P25 series of protected blocks for
indoor use provide protection, protec-
tion/demarcation, and sneak current fuse
protection. Intended for utilization in small
businesses, multiple dwelling units (MDUs),
and medium-density commercial or industrial
buildings, the R66P25 series is used by regu-
lated telcos, interconnects, and contractors.

R66P25QC
Shown with Modules

Enterprise : 21
OSPDS-073500 / 0605
R66P25 Series 25-Pair Protection

Figure 1 Figure 2 Figure 3

22 : Enterprise
OSPDS-073500 / 0605
R66P25 Series 25-Pair Protection

Figure 4 Figure 5
R66P25 with R891 Series Mounting Bracket

Enterprise : 23
OSPDS-073500 / 0605
R66P25 Series 25-Pair Protection

Ordering Information
Catalog Part — Termination Style — R891 Bracket Fig.
Number Number Application In*2 / Out*3 Required*4 Number
R66P25QC F015360 Protection QC / QC Optional 1
R66P25QCC F015361 Protection QC / RJ21 Optional 2
Receptacle
R66P25QCCR3B1EJZ F015421 Protection e/w R3B1EJZ QC / RJ21 Optional 2
Receptacle
R66P25QCP F015391 Protection QC / RJ21 Plug Optional 2
R66P25QCR3B1EJZ F015432 Protection e/w R3B1EJZ QC / QC Optional 1
R66P25QCS10 F015362 Protection 10-ft. stub / QC √ 3,5
R66P25QCS20 F015363 Protection 20-ft. stub / QC √ 3,5
R66P25QCVS F015409 Protection e/w 6U2VS QC / QC Optional 1
R66P25S10CD*1 F015401 Protection/demarcation 10-ft. stub / RJ21 Receptacle √ 4,5
R66P25S20CD*1 F015402 Protection/demarcation 20-ft. stub / RJ21RJ21 Receptacle √ 4,5

Abbreviations:
QC = Quick-connect clips or 66 Clips
RJ21 = 50-position RJ21 connector with universal hold-down, mounted for bottom feed
stub = Cable stub, 25-pair, 24-gauge cable
*1 50 2-position bridging clips (Emerson RA1) are included. Bridging clips are required to connect
protection to customer premises equipment. Bridging is necessary
*2 Central office or network cable pairs across the two outside vertical rows. (see Figure 4)
*3 Customer premises equipment or distribution pairs
*4 R891 Series brackets must be ordered separately
NOTE: See UL card for usage limitations in meeting UL Spec No. 497 or 497A.

Accessories
Catalog Part
Number Number Description
R891S50 F1003918 Stand-off bracket
RA1 F005170 Bridging clips
R66MHCO2 F015380 Hinged covers, 5-in. orange
R66MHCG2 F015381 Hinged covers, 5-in. gray
P17812 F517812 Ground connector
P48723 F548723 Universal hold-down

NOTE: For additional brackets, covers, bridging clips, etc. see the Accessories section of this catalog.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
24 : Enterprise
OSPDS-073500 / 0605
R399URLS 100-Pair Connector Outside Plant for
Business-Critical Continuity

Key Features
Description
• Maximum density saves space;
increases number of protected The latest, state-of-the-art R399URLS protected connector block from Emerson Network
cable pair per frame vertical Power offers tool-less, gas-tight, pair-at-a-time IDC wire termination on the equipment
side jumper field for fast, economical and reliable installations. The R399 is a high density
100-pair connector utilizing industry standard 5-pin protector modules. The R399URLS
• Tool-less pair-at-a-time connection
block is made of 94 V-0 rated, molded plastic and UL Listed to meet specification number
for fast, reliable and economical UL 497. The block's compact design allows maximum density per frame vertical.
terminations
Any connection of 22 to 26-gauge (.63mm to .38mm) solid conductor wire is made by lift-
• Accommodates a wide range of ing the activator, inserting the conductor pair, and pressing the activator down.
distribution wire for application
flexibility For cutovers and applications requiring a second extension or connection, the R399URLS
offers a half-tap module that operates independently from the permanent distribution
• Accepts industry standard activator. Therefore, the distribution half-tap module can be connected and disconnected
protector modules to permit a without disturbing the primary connection.
wide module selection
The R399URLS allows front access for both line testing and line disconnection.
Disconnecting plugs are available for temporary or permanent disconnection of the cir-
• “Look-both-ways testing” provides cuit. Fault isolation is simplified by directional (“look both ways”) access that supports
directional access that supports independent testing on each side of the line.
independent testing on each side
of the line For protection, a full line of 5-pin modules are available. Please see the Protection
Arrestors and Modules section in the OSP catalog.
• Current/overvoltage protection
during circuit testing, half-tap
additions, line connecting or
Application
disconnecting for added safety to
personnel and equipment The R399URLS protects personnel and equip-
ment from abnormal voltages and currents on
• Swivel stub design for up or down incoming cable pairs. R399URLS is mounted
stub configuration facilitates on framework in central office, remote termi-
ordering nal, or building entrance applications.

• UL Listed for documented


performance

R399URLS with 5-pin Modules

Enterprise : 25
OSPDS-090100 / 0106
R399URLS 100-Pair Connector

Dimensions
Connector H W D
R399URLS 8.40-in. 4.10-in. 8.77-in.
(213mm) (104mm) (223mm)

Ordering Matrix
Mounting Configuration blank = Non-angled mount
A = Angled mount
Ground Configuration blank = Conventional ground
S = Isolated ground
Connector Application R399URLS = Standard mount (left mount)
RZ399URLS = For use on right side protector columns
of 2500 frame
Stub Cable Gauge A = 24-gauge, .96 dia. o.d.
B = 22-gauge, 1.17 dia. o.d.
Stub Cable Type A = Alvyn
T = Two 22AWG cables*
Stub Length** (20-ft. minimum in 10-ft. increments)

* T configuration provides an equivalent to T screen-type cable. Two 50-pair cables are secured together every three feet.
**Stubbed units equipped with swivel stub for up or down configuration.
NOTE: Not all catalog numbers can be configured.

26 : Enterprise
OSPDS-090100 / 0106
R399URLS 100-Pair Connector

Ordering Information: Stubless Connectors


Catalog Part
Number Number Description
URLS Equipment Field, Tool-Less
R399URLS F249727 Connector, URLS equipment field
AR399URLS F1001577 Connecotr, angle mount, URLS equipment field

Ordering Information: Stubbed Connectors — 24 AWG


Catalog Part
Number Number Description
URLS Equipment Field, Tool-Less
R399URLSAA20 F1001081 Connector, URLS equipment field, 20-ft. swivel stub
R399URLSAA25 F249614 Connector, URLS equipment field, 25-ft. swivel stub
R399URLSAA30 F1001227 Connector, URLS equipment field, 30-ft. swivel stub
R399URLSAA40 F1001237 Connector, URLS equipment field, 40-ft. swivel stub
R399URLSAA50 F249616 Connector, URLS equipment field, 50-ft. swivel stub
R399URLSAA60 F1001082 Connector, URLS equipment field, 60-ft. swivel stub
R399URLSAA75 F249618 Connector, URLS equipment field, 75-ft. swivel stub
R399URLSAA100 F249620 Connector, URLS equipment field, 100-ft. swivel stub

Ordering Information: Stubbed Connectors — 22 AWG


Catalog Part
Number Number Description
URLS Equipment Field, Tool-Less
R399URLSBA20 F1001244 Connector, URLS equipment field, 20-ft. swivel stub

Enterprise : 27
OSPDS-090100 / 0106
R399URLS 100-Pair Connector

Single Pair URLS Half Tap (F800804)

Red Special Service Cap (F800568)

Single Pair Disconnect Plug (F800803)

Ten Pair Disconnect Plug (F596092)

Single Pair Tester (F800802)

NOTE: Plug in modules ordered separately.

Accessories
Catalog Part
Number Number Description
P48271 F548271 100-pair wall mounting bracket
P46321 F546321 Cable pair ID label
P95770 F595770 Replacement Activators (10 pkg.)
R399LPKIT F568051 Isolated ground kit
URLS1TEST1M F800801 Single pair, one-way break tester w/one meter 4-wire test cord, #6 ring terminals
URLS2TEST1M F800802 Single pair 2-directional continuity (bridge) tester w/one meter, 2-wire test cord #6 ring terminals
URLSCAPRED F800568 Red special service cap (100 per pkg.)
URLSDISCPLUG1 F800803 Single Pair Disconnect Plug (100 per pkg.)
URLSDISCPLUG10 F596092 Ten Pair Disconnect Plug (100 per pkg.)
URLSHALFTAP F800804 Single pair URLS half tap dry (10 per pkg.)
URLSHALFTAP25 F800570 Single pair URLS half tap dry (25 per pkg.)

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
28 : Enterprise
OSPDS-090100 / 0106
2500FRAME2 (One Vertical) Outside Plant for
Business-Critical Continuity
Single-Sided Distribution System

Key Features
Description
• Single-sided system allows all
frame administration to be The 2500FRAME2 from Emerson Network Power Communications is a single vertical,
performed on one side single-sided modular distribution system. Its versatile configuration can meet a variety of
specific pair sizing requirements.
• Common jumper trough permits
For protection, the frame mounts Emerson Communications' R399 100-pair central office
short jumpers for labor savings connectors. For equipment terminations, the frame will mount any conventional front-
facing line terminal blocks with 8-in. mounting centers, including 89 type blocks, the
• Modular design is easily expanded Emerson Communications' 2376 block, or the Emerson Communications' Block 32 and
“G” series. For building entrance applications, the 2500FRAME2 accommodates 66-clip
• Frame is factory pre-assembled for termination.
quick, easy installation
The 2500FRAME2 is a single vertical floor/wall mounted frame comprised of one vertical,
• Versatile block mounting can be one horizontal jumper trough for wire distribution to adjacent verticals, multiple jumper
configured to all pair requirements retainers for wire management, and top trough and bottom guide for conventional wire
routing.
• Can be used as double-sided aisle
Each vertical of the 8-ft. frame has ten block positions, which allows a maximum capac-
mount ity of 1,000 protected pairs per vertical. What makes the frame so flexible is that either a
R399 protected terminal block, a front facing line terminal block, or a horizontal jumper
trough can be mounted in any block position, allowing for any combination of protected
and equipment blocks on each frame.

Multiple frames can be suitably spaced and connected together to meet the required
application size. Each frame module has jumper access to adjacent modules through the
use of horizontal or top jumper troughs.

Splice brackets are provided for multiple frame installations to


tie them together on 9-in. centers.

This frame is also available in a 7-ft. version (25007FRAME2),


with a capacity of nine block positions.

Application
The 2500FRAME2 is designed specifically for small frame appli-
cations from 100 pair up to 15,000 pair. This frame provides
optimum protection/cross connection capabilities for:

Central Office
CLEC Applications
Co-Locations
Building Entrance Installations Three Frames Side-by-side
Remote Terminals

Enterprise : 29
OSPDS-100300 / 0705
2500FRAME2 (One Vertical) Single-Sided Distribution System

Ordering Information & Accessories


Catalog Part — Dimensions —
Number Number Description H W D
2500FRAME2 F151322 8-ft. Frame module 8-ft. 8-in. 14.9-in.
25007FRAME2 F151319 7-ft. Frame module 7-ft. 8-in. 14.9-in.
2500MB F150679 Mounting bracket for terminal blocks–one needed
for each terminal block. Required for 89-style front facing
blocks. Block 32 or “G” series terminal blocks can use
either the 2500MB or 2500SB swivel bracket.
2500SB F151257 Swivel mount bracket for terminal blocks. 7.9-in. 1.69-in. 1.38-in.
Only for use with Block 32 or “G” series terminal blocks.
2500IGND2 F1004497 Isolated Ground Kit

NOTE 1: Mounts all R399 and 89 type blocks.


NOTE 2: The R399 connector and the 2376 and 2378 blocks mount directly to the frame.
NOTE 3: Each Block 32, “G” series or 89-style front facing line terminal block requires a mounting bracket.
NOTE 4: Line terminal blocks are mounted vertically.
NOTE 5: Each Frame Module has 1 horizontal trough, which can mount in any block position.
NOTE 6: Top trough and bottom wire guide, one included with each unit.
NOTE 7: Ground bar & ground splice included.
NOTE 8: Adjacent frames should be mounted on 8-in.centers, but in 9-in. centers are recommended.

Capacities
2500FRAME2 (8-ft. frame) 25007FRAME2 (7-ft. frame)
1 vertical per frame module. 1 vertical per frame module.
Each vertical can mount ten (10) R399s. Each vertical can mount nine (9) R399s.
(9 if using jumper through) (8 if using jumper through)
Each vertical can mount ten (10) 89-style, Each vertical can mount nine (9) 89-style
Block 32, or “G” series terminal blocks. or Block 32 or “G” series terminal blocks.
(9 if using jumper through) (8 if using jumper through)
Each vertical can mount six (6) 2376 or Each vertical can mount five (5) 2376 or
2378 blocks. 2378 blocks.

2500SB Swivel Bracket: 2500SB Swivel Bracket:


If the 2500SB swivel bracket is used to If the 2500SB swivel bracket is used to
mount the Block 32 or “G” series terminal mount the Block 32 or “G” series terminal
blocks, then a horizontal trough can only blocks, then a horizontal trough can only
be located in block positions #1, #3, #4, be located in block positions #1, #2, #3,
#5, and #10 counting from the top. and #8.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
30 : Enterprise
OSPDS-100300 / 0705
2500 Frame (Two Verticals) Outside Plant for
Business-Critical Continuity
Single-Sided Distribution System

Key Features
Description
• Single-sided system allows all
frame administration to be For protection, the frame mounts R399 100-pair central office connectors. For equipment
performed on one side terminations, the frame will mount the Emerson Block 32, Emerson 2376 block, or front-
facing line terminal blocks with 8-in. mounting centers. For building entrance applications,
the 2500 frame accommodates the R366 connector with 66-clip termination.
• Common jumper trough permits
short jumpers for labor savings The 2500 frame is comprised of two adjacent verticals separated by a vertical jumper
trough. Each vertical of the 8-ft. frame has ten block positions, which allows a maximum
• Modular design is easily expanded of 1000 protected pairs per vertical. What makes the frame so flexible, is that either an
R399, a line terminal block, or a horizontal jumper trough can be mounted in any block
• Frame is factory pre-assembled for position, allowing for any combination of protected and equipment blocks on each frame.
quick, easy installation
Multiple frames can be lined up and connected together to meet the required application
• Versatile block mounting can be size. Each frame module has jumper access to adjacent modules.
configured to all pair requirements
Application through the use of horizontal jumper troughs.

The 2500 frame is also available in a 7-ft. version, which has eight block positions.

Application
Multiple frames can be lined up and
connected together to meet the required
application size. Each frame module
has jumper access to adjacent modules
through the use of horizontal jumper
troughs.

The 2500 frame is also available in a 7-ft.


version, which has eight block positions.

Two 2500 Frames Side-by-side

Enterprise : 31
OSPDS-100500 / 0906
2500 Frame (Two Verticals) Single-Sided Distribution System

Ordering Information & Accessories


Catalog Part — Dimensions —
Number Number Description H W D
2500FRAME F151250 8-ft. Frame module 8-in. 16-in. 15.5-in.
25007FRAME F151276 7-ft. Frame module 7-in. 16-in. 15.5-in.
2500MB F150679 Mounting bracket for terminal blocks–one needed for each
terminal block. Required for 89-style front facing blocks.
Block 32 terminal blocks can use either the 2500MB or 2500SB
swivel bracket.
2500SB F151257 Swivel mount bracket for terminal blocks can only be used with Block 32 terminal blocks.
2500IGND2 F1004497 Isolated Ground Kit

NOTE 1: The right vertical of the frame requires right mounted connectors (RZ399) and right mounted vertical terminal blocks.
NOTE 2: The R399 connector and the 2376 and 2378 blocks mount directly to the frame.
NOTE 3: Each Block 32 or 89-style front facing line terminal block requires a mounting bracket.
NOTE 4: Line terminal blocks are mounted vertically.
NOTE 5: Each Frame Module has 2 horizontal troughs.
NOTE 6: Ground bar & ground splice included.
NOTE 7: Adjacent frames should be mounted on 20-in. centers.

Capacities
2500FRAME (8-ft. frame) 25007FRAME (7-ft. frame)
2 verticals per frame module. 2 verticals per frame module.
Each vertical can mount ten (10) R399s. Each vertical can mount eight (8) R399s.
(9 if using jumper through) (7 if using jumper through)
Each vertical can mount ten (10) 89-style Each vertical can mount eight (8) 89-style
or Block 32 terminal blocks. or Block 32 terminal blocks.
(9 if using jumper through) (7 if using jumper through)
Each vertical can mount six (6) 2376 or Each vertical can mount five (5) 2376 or
2378 blocks. 2378 blocks.

2500SB Swivel Bracket:


If the 2500SB swivel bracket is used to 2500SB Swivel Bracket:
mount the Block 32 terminal blocks, then If the 2500SB swivel bracket is used to
a horizontal trough can only be located mount the Block 32 terminal blocks, then
in block positions #1, #3, #4, #5, and #10 a horizontal trough can only be located in
counting from the top. block positions #1, #2, #3, and #8.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
32 : Enterprise
OSPDS-100500 / 0906
5-Pin Protector Modules Outside Plant for
Business-Critical Continuity

Key Features
Description
• The 5-pin protector modules
protect personnel and equipment The 5-pin protector modules protect personnel and equipment from excessive voltages
from excessive voltages and and currents induced on telephone lines or local ground by lightning and AC power system
faults. All modules feature industry standard 5-pin bases for use in central office, remote
currents
terminal, building entrance, and customer premises applications. All modules are avail-
able with or without a heat coil to protect against sneak currents. When a sneak current is
• Modules feature industry standard induced on the line, the heat coil responds by permanently grounding the line to prevent
5-pin bases for use in central damage to line cards and sensitive equipment.
office, remote terminal, building
entrance, and customer premises Carbon Protector Modules feature a carbon air gap and fail-safe mechanism that shorts to
applications ground when a voltage exceeds its rating. A detent position disconnects the equipment
side while protecting the line side (OSP cable). These modules are used where transients
• All modules are available with are not frequent or cost is a major factor.
or without a heat coil to protect
against sneak currents Gas-Tube Protector Modules contain two-electrode high amperage ceramic non radioac-
tive gas-tube surge arresters and a fail-safe mechanism. These are used in areas where
frequent transient over voltages are a problem or where tightly controlled breakdown
• Carbon Protector Modules feature
values are required. The gas-tube will recover repeatedly from the overvoltage, providing
a carbon air gap and fail-safe 30 to 40 times longer life than carbon. The detent position disconnects the equipment
mechanism that shorts to ground side while protecting the line side (OSP cables). Modules are available with a secondary
when a voltage exceeds its rating vent-safe backup gap. Modules equipped with patented vent-safe gap are UL Listed (VS in
catalog). If a module is specified as a JZ-type, it is a next generation new gas-type version
• Gas-Tube Protector Modules that provides extended life and environmentally robust protection.
contain two-electrode high
amperage ceramic non radioactive Solid-state Modules contain state-of-the-art diodes intended for use with sensitive equip-
gas-tube surge arresters and a ment. They are available with 4 ohm (350mA) or 20 ohm (150 mA) heat coils. The diode
fail-safe mechanism is a fast semiconductor switch with operating voltage nearly independent of transient rise
time.
• Solid-state Modules contain
“RXXXX” Protector Modules have either a “B” or “C” as the third character in the catalog
state-of-the-art diodes intended number to denote special characteristics. Those with a B as the third character, i.e., R3B1E,
for use with sensitive equipment have a triangular-shaped recess molded into the base to accommodate the raised struc-
ture molded into the panel of AT&T® building entrance protectors.

Those modules with a C as the third character, i.e.,


R3C1E, have two circular holes in the shoulder of the
housing to provide access for test points.

Application
These protector modules provide overvoltage and
overcurrent protection for central office, remote
terminal, and building entrance/customer premises
applications. All protector modules provide a vent-
safe gap, are fail-safe, and meet UL requirements.
Specific models are designed to meet RDUP (for-
merly RUS) and Telcordia specifications.

Enterprise : 33
OSPDS-110500 / 0705
5-Pin Protector Modules

Ordering Information
Low Voltage Standard
Housing Solid-State Solid-State (300V)
Color & Size JZ Carbon (240V) R3B1S Service
Modules for Bell Operating Companies, No Heat Coil, Gold Plated Pins
Black, S R3B1EJZ R3B1A R3B1FS R3C1S Standard
Black w/test point, L R3C1EJZ R3C1FS R3B2S Standard
Green, S R3B2A R3B2FS R3C2S Service denial
Green w/test point, L R3C2FS R3B3S Service denial
Red, S R3B3EJZ R3B3A R3B3FS R3C3S Special
Red w/test point, L R3C3EJZ R3C3FS R3B4S Special
Yellow, S R3B4A R3B4FS R3C4S PBX battery
Yellow w/test point, L R3C4FS PBX battery
Gray, S R3B12A Continuity only

NOTE: Size: S = short & L = long

Ordering Information
Low Voltage Standard
— Solid-State (240V) — — Solid-State (300V) —
Housing Color JZ Carbon 4 Ohm 20 Ohm 4 Ohm 20 Ohm Service
Modules for Bell Operating Companies, Long Housing, with 4 or 20 Ohm Heat Coil, Gold Plated Pins
Black R4B1EJZ R4B1C R4B1FS RT4B1FS R4B1S RT4B1S Standard
Black w/test point R4C1EJZ R4C1C R4C1FS RT4C1FS R4C1S RT4C1S Standard
Green R4B2C R4B2FS RT4B2FS R4B2S RT4B2S Service denial
Green w/test point R4B3EJZ R4C2C R4C2FS RT4C2FS R4C2S RT4C2S Service denial
Red R4C3EJZ R4B3C R4B3FS RT4B3FS R4B3S RT4B3S Special
Red w/test point R4B4EJZ R4C3C R4C3FS RT4C3FS R4C3S RT4C3S Special
Yellow R4B4C R4B4FS RT4B4FS R4B4S RT4B4S PBX battery
Yellow with test point R4C4C R4C4FS RT4C4FS R4C4S RT4C4S PBX battery
White R4B9C R4B9FS RT4B9FS R4B9S RT4B9S Reverse tip & ring
White with test point R4C9C R4C9FS RT4C9FS R4C9S RT4C9S Reverse tip & ring
Gray R4B12C Continuity
Gray w/test point R4C12C Continuity only

34 : Enterprise
OSPDS-110500 / 0705
5-Pin Protector Modules

Ordering Information
Low Voltage Standard
Housing Three Solid-State Solid-State
Color Carbon Gas Element (240V) (300V) Specification
Other Modules—Short Housing, No Heat Coil, Tin Plated Pins
Black 3AB UL, RDUP (formerly RUS), GTE®
Red 3GURVS UL
Orange 6A20 RDUP (formerly RUS), GTE®
Black 6A20B RDUP (formerly RUS), GTE®
Red 6A20R RDUP (formerly RUS), GTE®
Black 3GB RDUP (formerly RUS)
Red 3GR RDUP (formerly RUS)
Orange 3G RDUP (formerly RUS)
Orange 6U2VS UL, RDUP (formerly RUS), GTE®
Black 6U2BVS UL, GTE®
Red 6U2RVS UL, GTE®
Orange 3GUVS UL, RDUP (formerly RUS)
Black 3GUBVS UL
Black S3ABF S3AB* UL, RDUP (formerly RUS)
Red S3ARF S3AR UL
Other Modules—Long Housing, with Heat Coil, Tin Plated Pins
Black 4AB UL, GTE®
Red S4ARF S4AR UL
Orange G4AVS UL, GTE®
Black G4ABVS UL, GTE®
Red G4ARVS UL, GTE®
Black S4ABF S4AB UL

* S3AB is RDUP (formerly RUS) accepted in our R399 connector and available for use in connector equivalents.
NOTE 1: See the Reference Standards Chart at the end of this section.
NOTE 2: Designed to meet Telcordia TR-TSY-000070, GR-1361-CORE, GR-974-CORE, and RDUP (formerly RUS) PE-80, PEG-1, PEG-3, PEG-7.
NOTE 3: All RDUP (formerly RUS) modules meet the criteria in Government Publication RDUP (formerly RUS) TE&CM 823.

Enterprise : 35
OSPDS-110500 / 0705
5-Pin Protector Modules

Ordering Matrix RBOC Catalog Numbers


Pin Type R = Gold pins
RT = Gold pins, 20 Ohm (used with solid-state)
Heat Coil 3 = Without heat coil
4 = With heat coil
Generic Internal Design B = Fail short
C = Has 2 circle-shaped holes for test points
Housing Type 1 = Black, standard service
2 = Green, service denial
3 = Red, special service
4 = Yellow, PBX
9 = White, reverse tip & ring
10 = Gray, continuity (switch through)
Technology A = Carbon (short housing)
C = Carbon (standard housing)
E = Gas-tube
S = Standard solid-state
FS = Low voltage solid-state

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
36 : Enterprise
OSPDS-110500 / 0705
SuperDuty® JZ380 Series Outside Plant for
Business-Critical Continuity
Next Generation Protectors

Key Features
Description
• Extended service life reduces
maintenance costs and subscriber The SuperDuty® JZ380 Series Next Generation of gas-tube station arresters and protec-
complaints tors incorporate an environmentally robust form of gas-tube technology in applications
that have an uncontrolled environment and severe lightning exposure. The electrical surge
endurance exceeds 3000 strikes without incidence.
• Vent-safe and fail-safe mechanisms
on arresters provide continued The 1305VSB and R108VSB arresters/protectors feature patented vent-safe and fail-safe
surge protection under adverse mechanisms that insure an automatic short to ground in the event of sustained or high
conditions current conditions. The components protect against moisture, corrosion and contami-
nants to provide an environmentally hardened protector that reduces service calls and
• Low noise eliminates noise extends protector life. The protectors comply with the specifications listed in the Telcordia
associated with carbon protectors Technical Audit Report #AU-148, Iss. 1, of September 1994.

• Environmentally robust to provide SuperDuty® JZ380 series 5-pin gas-tube protector modules are used in areas of frequent
extended life and protect against transient over voltages with controlled breakdown values, and where adverse environmen-
tal conditions are encountered. Gas-tube modules are available with or without heat coils
induced moisture corrosion per
that protect against sneak currents.
Telcordia Technical Audit Report
#AU-148, Iss. 1, September 1994

• Designed to meet Telcordia Application


standards to assure quality
performance The SuperDuty® JZ380 series arresters and protectors provide excellent transient
protection for all telecommunications systems. Units are designed to meet specific con-
figurations and voltage requirements at the customer premises, remote cabinets, as well
• UL Listed, RDUP (formerly RUS)
as at the central office.
accepted, and CSA Certified to
assure quality performance; CAT5
compatible

R3B1EJZ

Enterprise : 37
OSPDS-111500 / 0705
SuperDuty® JZ380 Series Next Generation Protectors

5-Pin Protector Modules Without Heat Coil


Catalog Part Test Housing Pin Solid-State
Number Number Specifications Point Color Service Plating Upgrade
R3B1EJZ F014031 Telcordia, UL, CSA Black Standard Gold R3B1S
R3C1EJZ F013445 Telcordia, UL √ Black Standard Gold R3C1S
R3B3EJZ F013456 Telcordia, UL Red Special service Gold R3B3S
R3C3EJZ F013446 Telcordia, UL √ Red Special service Gold R3C3S
R3B1E90JZ F013808 Telcordia, UL Black Standard Gold
R3B3E90JZ F013982 Telcordia, UL Red Special service Gold
R3B1ET1JZ F014002 Telcordia, UL Red Special service Gold S3AB

NOTE 1: See the Reference Standards Chart at the end of this section.
NOTE 2: Designed to meet Telcordia TR-TSY-000070, TR-TSY-000072, GR-1361-CORE, and GTE® GTS-8345.

5-Pin Protector Modules With Heat Coil


Catalog Part Test Housing Pin Solid-State
Number Number Specifications Point Color Service Plating Upgrade
R4B1EJZ F013450 Telcordia, UL, CSA Black Standard Gold R4B1S
R4C1EJZ F013440 Telcordia, UL √ Black Standard Gold R4C1S
R4B3EJZ F013451 Telcordia, UL Red Special service Gold R4B3S
R4C3EJZ F013444 Telcordia, UL √ Red Special service Gold R4C3S
R4B4EJZ F013453 Telcordia, UL Yellow PBX battery Gold R4B4S

NOTE 1: See the Reference Standards Chart at the end of this section.
NOTE 2: Designed to meet Telcordia TR-TSY-000070, TR-TSY-000072, GR-1361-CORE, and RDUP (formerly RUS) PE-80, and GTE® GTS-8345.
NOTE 3: All RDUP (formerly RUS) modules meet the criteria in Government Publication RDUP (formerly RUS) TE&CM 823.
NOTE 4: Heat coil R4_ _ _ Series = 4 Ohms.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
38 : Enterprise
OSPDS-111500 / 0705
Reference Standards Chart Outside Plant for
Business-Critical Continuity

Specifications
VSR2-types
VSB-types RDUP (formerly RUS) T-types International Specs
Electrical Telcordia Specs & GTE® Specs Telcordia Specs South America
Specifications TR-TSY-000070 & GR-1361-CORE PE-80 & GTS GR-974-CORE Pacific Rim
JZ Standard & Standard Standard
Standard Gas Performance JZ Performance Solid-State Low Voltage Gas
DC Breakdown 265V-600V 265V-600V 300V-500V 265V-400V 200V-300V
@ ≤ 2000V/s @ 1 mA
(400V nominal) (350V-380V nom) (350V-400V nom) (300V nominal) (250V-260V nom)
Impulse 1000V max. 650V max. 300V-750V 400V max. 700V max.
@ 100V/µs
DC Holdover < 150 ms < 150 ms < 150 ms < 150 ms
@ 150V min. Typical < 10 ms Typical < 10 ms Typical < 10 ms Typical < 10 ms N/A
DC Holdover < 200 ms
@ 115V min. N/A N/A N/A N/A Typical < 200 ms
Insulation > 100 MΩ > 100 MΩ > 100 MΩ > 100 MΩ > 100 MΩ
Resistance
Capacitance
< 5 pf < 5 pf < 5 pf N/A N/A
<30 pf < 20 pf < 30 pf < 200 pf < 20 pf
Impulse Life 1000 LTS @ 10A *Unlimited @ 10A 400 LTS @ 500A *Unlimited @ 10A N/A
LTS = Surges 100 LTS @ 100A 300 LTS @ 100A *Unlimited @ 100A
@ (10/1000 µs) 50 LTS @ 300A 50 LTS @ 300A Failsafe @ 10KA
@ (10/250 µs) 25 LTS @ 2000A 25 LTS @ 2000A
@ (20/100 µs) 2 LTS @ 5000A 2 LTS @ 5000A
@ (8/20 µs) 1 LTS @ 20KA 1 LTS @ 20KA
AC Surge Life 0.5Arms 30s 0.5Arms 30s 65Arms 11 cycles 0.5Arms 30s 0.5Arms 30s
10Arms 1s, 60Hz 65Arms 11 cycles 10Arms 1s, 60Hz 65Arms 11 cycles
1Arms 1s, 60Hz 10Arms 1s, 60Hz 1Arms 1s, 60Hz 15Arms 15 min.
1Arms 1s, 60Hz
End Life Limits
<10 MΩ <10 MΩ <1 MΩ <10 MΩ <10 MΩ
<265V or >750V <265V or >600V <180V or >600V <265V <200V
>1000V >800V >900V >400V >900V
Vented >1000V (95%) >1000V (95%) <1500V N/A N/A
(back-up) 1200V max. 1200V max. (avg. 1000V-1200V)
Breakdown @ 100V/µs @ 100V/µs

*Unlimited ≥3000 surges


NOTE: Models are designed to meet various industry reference standards.

Enterprise : 39
OSPDS-113700 / 0705
Reference Standards Chart

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
40 : Enterprise
OSPDS-113700 / 0705
DEC25/NG Outside Plant for
Business-Critical Continuity
“Next Generation” Digital
Equipment Cabinet

Key Features
Description
• Sealed or Ventilated Design —
provides superior protection of The DEC25 “Next Generation” family of enclosures have been specifically designed with
equipment, cables, and splices today's distributed network architecture in mind. New “urban design guidelines” now require
network providers to make their POPs smaller, quieter and more cosmetically pleasing, while

still maintaining the same levels of network reliability and service, as in the past. The DEC25
• Small, lightweight cabinets —
family offers the user the unique ability to customise your network deployment to meet
meet or exceed new “Urban these stringent new requirements. The different sizes, compact profiles, low operating noise
Design Guideline” requirements levels, and clean lines make the deployment of the DEC25 family much easier than traditional
larger enclosures.
• Multiple Cooling Options —
cost effective solutions for any Three sizes of the DEC25 are available. All enclosures are constructed of welded heavy gauge
application aluminium and are designed to withstand the most severe environmental conditions. They
each will economically house a wide variety of sensitive electronic equipment in any outdoor
• Welded Aluminum environment.
Construction — Dependable,
The DEC25-8 is the smallest unit in the family measuring only 27" tall. The enclosure has (8)
durable, offering a long, corrosion-
EIA 1.75" equipment rack space available for equipment mounting. The DEC25-8 is ideal for
resistant, problem-free service life
small remote sites where up to 150 individual lines may be required. The DEC25-17 is the
mid-size unit and measures 42" tall. This enclosure has (17) EIA 1.75" equipment rack space
• Flexible Design — available for equipment mounting. The DEC25-17 is ideal for remote sites where the line
Applications for wireless, wireline requirements could be as high as 384 individual ports. The largest unit in the family is the
and CATV DEC25-27, which measures 60" tall. This enclosure has (27) EIA 1.75" equipment rack space
available for equipment mounting. Again the DEC25-27 fits most applications needing more
• Modular Design — than 384 lines. Any of these cabinets can be pole or pad mounted using special mounting
provides for craft separation and kits.
configuration flexibility  
Depending on regulatory requirements, the external operating conditions and the equip-
ment operating parameters, any of the DEC25 enclosures can be equipped with one of four
optional cooling options. These include convection cooling, forced air cooling, heat exchang-
er cooling and HVAC cooling.

Application
The DEC25-8, DEC25-17 or DEC25-27 cabinets are a family of durable yet economical priced
enclosures. They are specifically designed to house a wide variety of sensitive electronic
equipment in any outdoor application. The cabinets are designed with optional cooling
modules that allow equipment to be housed in a sealed, dust free environment. Or for appli-
cations where less stringent environmental requirements are needed, any of the cabinets can
be equipped with less costly fans and baffles for cooling the cabinet. Our simple yet innova-
tive cooling designs have been tested and verified to the highest industry standards.

Specific applications for the DEC25 family include: DSLAM adjunct sites, digital loop carrier
systems, microwave sites, auxiliary battery cabinets, fibre optic hub sites and radio equip-
ment cabinets for wireless applications.

Enterprise : 41
OSPDS-127100 / 1005
DEC25/NG “Next Generation” Digital Equipment Cabinet

Table A: Main Cabinet Equipment Chamber Dimensions


Catalog Number Height* Width Depth Rack Spaces Rack Width Weight**
DEC25-8/NG 21.0-in. 25-in. 25-in. 8 x 1.75-in. 23.0-in. 82 lb.
533-mm 635-mm 635-mm 36.4 kg
DEC25-17/NG 36.75-in 25.0-in. 25.0-in. 17 X 1.75-in. 23.0-in. 110 lb.
934-mm 635-mm 635-mm 48.8 kg
DEC25-27/NG 54.25-in in. 25.0-in. 25.0-in. 27 x 1.75-in. 23.0-in. 145 lb.
1378-mm 635-mm 635-mm 64.4 kg

* To obtain the overall height of the cabinet, all three of these component heights must be added together.
** To obtain the overall weight of the cabinet, all three of these component weights must be added together.

Table B: Cabinet Pad-Mounting Dimensions


Cabinet Pad-Mounting Options Height* Weight**
List 07 Pad-Mount Baseframe 11.0-in. 32 lb.
533-mm 14.2 kg
List 08 Pad-Mount Feet 6.0-in. 10 lb.
152-mm 4.4 kg

* To obtain the overall height of the cabinet, both of these component heights must be added together.
** To obtain the overall weight of the cabinet, both of these component weights must be added together.

Table C: Cabinet Cooling Options


Cooling Options Height* Weight**
Fan 5.75-in. 15 lb. /6.7 kg
Heat Exchanger 8.25-in. 30 lb. /13.3 kg
HVAC: 1500 BTU/Hr 14.25-in. 110 lb. /48.9 kg
HVAC: 3500 BTU/Hr 14.25-in. 110 lb. /48.9 kg
HVAC: 5500 BTU/Hr 18.0-in. 130 lb. /57.7 kg

* To obtain the overall height of the cabinet, all of these component heights must be added together.
** To obtain the overall weight of the cabinet, all of these component weights must be added together.

42 : Enterprise
OSPDS-127100 / 1005
DEC25/NG “Next Generation” Digital Equipment Cabinet

Specifications
Finish
Platinum gray
Access
Front door
Rear door
Removable battery chamber panels
Cooling
Options Convection cooling kit
330 cfm fan kit (-48, +24 vdc or 120 vac)
Heat exchanger kit (600 watt or 1200 watt)
HVAC kit (1500, 3500 or 5000 BTU)
Electrical
Standard 4-in. x 4-in junction box with surge protector and GFI receptacle
Optional 4 or 8 position 120/240 vac, 60 Hz, load center
Alarms
High temperature = 49˚C
Low temperature = 5˚C
Front Door Intrusion
Rear Door Intrusion
Mounting
Pad-mount (optional kits required)
Pole-mount
Wall-mount
Rack Space
Single, center mount 23-in. wide rack system (19-in. optional)
1.75-in. EIA spacing standard (1.00-in. spacing optional)
untapped holes for 12-24 hardware
DEC25-8 = 14.00-in. of rack space (8 RU)
DEC25-17 = 29.75-in. of rack space (17 RU)
DEC25-27 = 47.25-in. of rack space (27 RU)
Approvals
CSA
UL
GR-487 (as applicable)

Enterprise : 43
OSPDS-127100 / 1005
DEC25/NG “Next Generation” Digital Equipment Cabinet

Ordering Information
Model Number Part Number List Number Description
DEC25-8/NG F787652 Common equipment wiring and assembly for a basic DEC25 cabinet. Including racks, wind
DEC25-17/NG F787653 List 00 latches, ground bar, single point cabinet ground lug, frame ground system, weather
DEC25/27/NG F787654 gasketing, insulation, document holder, lifting eyelets, solar shield
Next Generation Mounting brackets, alarm termination strip, grounded cable entry plate,
DEC25 cabinet assemblies (1) cable nozzle, assembly labour
List 05 115 vac, 60 Hz Cabinet AC Kit; wiring and assembly of a 4-in. x 4-in. splice box, (1) 15 amp, 115 vac
duplex receptacle and (1) 15 amp 115 vac GFI receptacle, (1) surge arrestor, sealed flexible AC con-
duit.
List 06 220 vac, 50 hz Cabinet AC Kit; wiring and assembly of a 4-in. x 4-in. splice box, (1) 3 position AC ter-
minal block, (1) Joslyn surge arrestor, sealed flexible AC conduit.
List 07 11.00-in. Welded Pad-Mounting Base Assembly
List 08 6.00-in. Pad-Mounting Feet Assembly
List 09 Side Mounted, Pole-Mounting Kit
List 12 Fixed Battery Tray for use with List 07 Base Frame
List 20 DEC25 Alarm Kit e/w (2) intrusion alarms, (1) high temp alarm, (1) low temp alarm, (1) 8 pair screw-
down termination strip
List 21 Cabinet Sealing Kit
List 22 Cabinet Filter Kit
List 29 Insulation Kit for the DEC25-17/NG
List 41 Cabinet Entry and Installation Tool Kit
List 45 +24 vdc fan kit for use in List 00
List 46 -48 vdc fan kit for use in List 00
List 47 120 vac fan kit for use in List 00
List 50 8 amp, -48 vdc Modular Rectifier System
List 51 2 amp, -48 vdc Rectifier Module for list 50
List 52 Air Circulation Fan Rack System for list 50
List 56 Battery Temperature Compensation Unit for list 50
List 60 -48 vdc, 600 watt Heat Exchanger
List 70 1500 BTU HVAC Kit
List 71 3500 BTU HVAC Kit
List 72 5000 BTU HVAC Kit
List 75 Pole-Mount Chair Assembly Kit
List 80 Battery Tray Heater Kit for list 12
List 82 Slide Out Battery Tray for use with List 07 Base Frame
List 84 Battery Tray Heater Kit for list 82
List 86 4 Position, 30 amp, 120/240 vac Load Center
List 95 110 pair Protection Panel Assembly
List 100 18 amp, -48 vdc Modular Rectifier System
List 105 60 amp, -48 vdc Modular Rectifier System
List 120 8 Position, 60 amp, 120/240 vac Load Center

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
122 Edward Street The Emerson logo is a trademark and a service mark
St. Thomas, Ontario N5P 1Z2 of Emerson Electric Co. Emerson Network Power is a division
Telephone: 800-265-9243 Fax: 519-631-1994 of Emerson Electric Co.
EmersonNetworkPower.com/OSP
Printed in USA
44
OSPDS-127100 / 1005
MESA® 4 NxT Outside Plant for
Business-Critical Continuity
Modular Electronic Sealed Architecture

Key Features
Description
• Sealed design — protects
equipment from water and dust, The MESA® 4 closure is the latest solution to today's outside plant demands. Due to the
while maintaining a cool operating sophisticated nature of electronic systems being deployed in today’s outside environ-
ment, efficient thermal management is increasingly critical to their operation. Emerson
environment
has created an innovative heat exchanger cooling system, which keeps electronics from
exceeding their optimal temperatures, yet never introduces outside air and pollutants into
• Flexible design — cabinet the equipment chamber.
modules can be configured to
accommodate most telephone, In addition, MESA® is designed to withstand the most severe environmental conditions,
CATV, and wireless applications providing maximum protection for your equipment investment. MESA® is thoroughly
tested against dust and water intrusion and exceeds even the most stringent industry
• Powder paint process — provides standards.
a harder finish while eliminating
the release of harmful VOCs into MESA® is also extremely flexible. A modular approach is taken wherever possible so the
the environment cabinet can be quickly configured to meet your exact requirements. Optional “modules”
include a battery drawer, commercial power panel, fiber splicing system, and overvoltage
protection panels.
• Separate battery compartment — 
provides additional space for
revenue-producing equipment
and separates batteries from heat Application
generating electronics
The MESA® 4 Cabinet can economically house a variety of next generation electronic
• Compartmentalized design — equipment including Digital Loop Carriers (DLCs), fiber optic transport systems, and radio
equipment for wireless applications.
for craft separation and
configuration flexibility

• Low maintenance — cabinet does


not utilize any fans or filters that
require routine maintenance

• Innovative cooling system —


keeps electronics from exceeding
their optimal temperatures

• Meets all industry standard


requirements — to ensure
documented performance

• Telcordia GR-487 —
CORE Issue 2 compliant

Enterprise : 45
OSPDS-122500 / 1005
MESA® 4 NxT Modular Electronic Sealed Architecture

Dimensions
Catalog
Number H W D
MESA® 4 (overall exterior dimensions) 75-in. 93-in. 46-in.
Chamber Area Dimensions
Equipment Chamber (interior dimensions) 52.5-in. 55.5-in. 42-in.
End Chamber (splice & power chamber) 52.5-in. 42-in. 13.7-in.

Splice Chamber MESA® 4 Front View Power Chamber

46 : Enterprise
OSPDS-122500 / 1005
MESA® 4 NxT Modular Electronic Sealed Architecture

Specifications
Enclosure Mounting
Enclosure Pad-mounted
Equipment Mounting
Total mounting space 216-inches of rack space
(two 49.5-inch and two 48-inch EIA rack units in the equipment
chamber and one 21-inch mini rack in the power chamber)
Hole spacing on racks 1.0-inch spacing (EIA 1.75-in spacing available)
untapped holes for 12-24 thread forming hardware
Rack widths 23-inch EIA standard
Center mounting Accepts standard 12-inch deep, center mount equipment
(5-inch front, 7-inch rear)
Environmental Protection
Finish Off-white, polyester powder coat
Thermal Protection
Heat exchanger Two, 23-inch Heat Exchanger
Temperature fans turn on at: 90° F
High temperature alarm will sound at: 150° F
Heat dissipation 3200/ 3600/ 4600 Watt options
(based upon impedance of installed equipment)
Electrical
AC System 8-position power distribution panel with AC distribution to power shelf
Convenience Outlets (GFCI protected) Two in the equipment chamber (one per side)
One each in the power chamber and splice chamber
Battery heater pad kit (optional) Thermostat control “On” at 40° F, “Off” at 60° F
Compatible batteries & amp-hour reserve Quantity (6) strings of 4-12 VDC 155 A-Hr front post batteries (48VDC string)
FIAMM®, GNB, C & D, etc.
Security
Padlockable 216-type tool
Intrusion alarm Intrusion alarm with local indication and remote location options
Bonding and Grounding
Two 10-position, dual holed L49, copper buss, 3/16-in. thick,
1/4-20 hardware. One each in power chamber and splice chamber
Cable Entrance
Four, 4-inch cable entrance ports in splice chamber
Two, 4-inch cable entrance ports in power chamber
(cable dressing bracket provided with protection panel kit)
Dimensions and Weights
Overall Exterior (H x W x D) 75" x 93" x 46.0"
Equipment Chamber (H x W x D) 52.5" x 55.5" x 42.0"
End Chambers (H x W x D) 52.5" x 42.0" x 13.7"
Weight 1485 lbs. (unequipped)

Enterprise : 47
OSPDS-122500 / 1005
MESA® 4 NxT Modular Electronic Sealed Architecture

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

Emerson Network Power © 2007 Emerson Network Power Energy Systems,


Energy Systems North America, Inc. All rights reserved.
4350 Weaver Parkway, Warrenville, IL 60555 The Emerson logo is a trademark and a service mark
Toll Free: 800-800-1280 (USA and Canada) of Emerson Electric Co. Emerson Network Power is a division
Telephone: 440-246-6999 Fax: 440-246-4876 of Emerson Electric Co.
Web: EmersonNetworkPower.com/EnergySystems
Printed in USA
48 : Enterprise
OSPDS-122500 / 1005
LORAIN® XP 4890 DC Power for
Business-Critical Continuity
DC Power System

Key Features
LORAIN® eXpandable, Integrated Power —
• Compact integrated system — the next generation small power platform from
holds up to 96 amps at 54.48V
(9kw) in 2 rack spaces Emerson providing expandable power, distribution,
control and monitoring in a compact package.
• Constant power option —
delivers more current at lower
voltages to meet load or
recharge demand
Description
The LORAIN® eXpandable Power (LXP) System is composed of one to three rectifier
• Rugged design — rated for modules, each arranged for up to three 1750 watt constant power rectifier modules. A
continuous operation from -40°C centralized controller forms the heart of the system, featuring web-based software, user-
to +80°C programmable inputs and alarms, remote access and battery management. The integrated
distribution shelf is designed for up to four plug-in fuse holders or breakers rated 1 to
• Complies with industry 100 amps to meet load distribution requirements as well as ten GMT fuse positions. An
standards — NEBS™ level 3 optional 6-position GMT fuse module is available for additional GMT loads. A low-voltage
certified and UL Listed disconnect circuit can be configured for battery or load disconnect. The LXP system is a
cost-effective solution for loads under 5.2 Kw. This system is designed for tighter cabinet
• Extensive battery powering needs as well as Customer Premise FTTx applications.
management — includes health,
reserve time remaining, and
discharge test capability

• Four user definable binary


inputs — for external alarm or
control functions

• Alarm and event logs —


record system history

• User programmable — six sets LXP 4890 System


of Form C alarm relay contacts
are available

• Remote access — TCP/IP, Ethernet

Enterprise : 49
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System

Application
LXP systems are rated for continuous opera- integrated system. The system is designed shelters. Specific applications include: DLC,
tion from -40°C to +80°C and are NEBS™ for deployment in central office, POP sites, xDSL, DSLAM, FITL electronics, broadband
Level 3 certified and UL Listed. 23-inch co-location sites, customer premises, out- communications, multiplexers, PCS, micro-
cabinet configurations are available for this door cabinets, CEVs, vaults or portable wave and PBX.

50 : Enterprise
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System

Rectifier Shelves
LXP Integrated rectifier shelves are 3.5" (2
RU) high, 12" deep and are available in 23"
widths. The 23" rack mounts up to 3 recti-
fier modules or 2 rectifier modules plus
a modular ring generator. These shelves
provide front to back ventilation and
can be mounted directly above or below
other electronic equipment, maximizing
LXP Integrated System revenue-generating space. Each unit will
operate from 120/208/240VAC and is
equipped with a single input to accommo-
date a line cord or hard wiring. DC output
connection options for each shelf include
dual two-hole compression lugs or bus
bar terminations for connection to local or
remote distribution and batteries. The shelf
with rectifiers is NEBS™ Level 3 certified,
UL Listed and meets FCC Class B EMI/RFI
requirements.

Rectifier Modules
LXP rectifiers are rated for up to 1750-watt
constant output power when operated at
208/240VAC nominal input, 38.0 amps
at 46VDC to 30.1 amps at 58VDC. When
operated at 120VAC nominal input the out-
put power is rated at 750 watts, 16.3 amps
at 46VDC to 12.9 amps at 58VDC. The
rectifier will provide up to 100% of rated
power at 65°C. As the temperature increas-
es from 65°C to 80°C, the thermal power
limit circuit linearly decreases power. In
LXP Rectifier Module
the typical operating range, these recti-
fiers have a power factor greater than .99,
total harmonic distortion less than 5% and
efficiencies greater than 91%. Each hot-
swappable rectifier has an integral cooling
fan and a tri-color LED status indicator.

Enterprise : 51
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System

As load demand grows, the system can be easily


expanded with additional modular components.

Battery Management Batteries


The following enhanced battery manage- LXP systems can be configured with a wide
ment functions are available as add on range of batteries to suit specific load and
options: reserve time remaining, float cur- reserve time requirements. Battery connec-
rent monitoring, impedance imbalance, tions can be made directly to the rectifier
individual cell monitoring and multiple shelf or the distribution cabinet. Optional
string monitoring. battery maintenance disconnects are avail-
able if required.

Controller and a sequential rectifier start capability.


The LXP controller is designed for fail safe The controller features web-based soft-
operation and includes a two-line 20-char- ware and an RJ45 connection for remote
acter display, three menu navigation keys access via TCP/IP or Ethernet. The base
and five LED status indicators. The LEDs controller provides the following battery
display the status of AC power, minor and management capabilities: temperature
major alarms, fault conditions and battery compensation, thermal runaway manage-
conditions. Four binary inputs and six form ment, system conditions, functionality
C alarm contacts, all user programmable, testing, battery recharge current limit, half-
are provided. In addition to traditional sys- string monitoring and discharge testing.
tem alarms and controls, the LXP system
LXP Controller features a loss of redundancy alarm, activity
and alarm history logs, inventory functions,

52 : Enterprise
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System

Specifications
Input
Voltage Nominal 120/208/240 volts AC, single phase, 50/60 Hz, with a range of 84 to 286 volts.
Extended range to 300 volt AC without damage.
Current 9.23 amps@208VAC, 8.01 amps@240VAC per PCU, 54.48VDC, 1750 watts output
8.09 amps@208VAC, 7.00 amps@240VAC per PCU, 54.48VDC, 1500 watts output
20.38 amps@208VAC, 20.59 amps@240VAC per feed (3 PCUs), 54.48VDC, 4500 watts output
23.79 amps@208VAC, 24.03 amps@240VAC per feed (3 PCUs), 54.48VDC, 5250 watts output
35 amp breaker recommended per feed (1750W rectifier), 30 amp breaker recommended per feed (1500W rectifier)
10.91 amps@176VAC, 1750 watts output (worst case) 32.76 amps@176VAC (worst case) per feed (3 PCU’s)
9.35 amps@176VAC, 1500 watts output (worst case) 28.05 amps@176VAC (worst case) per feed (3 PCU’s)
6.94 amps@120VAC per PCU, 54.48VDC, 750 watts output
20.83 amps@120VAC per feed, 54.48VDC, 2250 watts output
9.92 amps@84VAC, 750 watts output (worst case) per PCU; 29.75 per feed
Inrush Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage within the
rated input voltage range.
Frequency 45-65 Hz
Protection Shelf input is wired for a Single AC input. The first feed will power PCU’s 1, 2, and 3. If the AC input voltage
decreases or increases beyond a non-adjustable predetermined value, the PCU power conversion circuitry
inhibits, disabling PCU output. The PCU will recover automatically when the AC input voltage is re-established
within specifications limits.
Power Factor Typical power factor greater than or equal to 99% for any load greater than or equal to 50% of rated full load
at nominal line. Meets IEC 1000–3–2.
Operating Efficiency Typical operating efficiency 92%
Output
Voltage Nominal -48 volts DC, positive ground, adjustable from -46.0 to -58.0 volts DC
Current 29 to 38.0 amps per PCU (1750 Watt ), 25 to 32.6 amps per PCU (1500 Watt),
up to a total of 87 to 114 amps per shelf with three PCUs installed in the main shelf.
Power 1,750 watts maximum (1750 Watt PCU) and 1,500 watts maximum (1500 Watt PCU). The PCU employs a
constant power limiting feature which limits the maximum output power to 1,750 or 1500 watts over the
output voltage range of -46.0 to -58.0VDC.
Regulation Steady state output voltage remains within ±0.5% of any voltage within the range of 46.0 to 58.0 volts DC
for any combination of frequency, input voltage, and load from no load to full load over the temperature
range of -20°C to +65°C (-4°F to +149°F).
Filtering On or off battery
Voice Band Noise Less than 32 dBrnC
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 30 mv rms
Psophometric Noise Does not exceed 1 mv

Enterprise : 53
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System

Specifications (continued)
Protection
Current Limiting Maximum output current of each PCU can be set from 2.5 to 32.6 amps (1500 Watt) or 38.0 amps (1750 Watt)
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately three
seconds, the PCU automatically restarts.
Monitoring
Status/Alarm Indicators Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed
on the 2 Line 20-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature -40°C to +65°C (-4°F to +149°F); -40°C to +80°C (-40°F to +176°F) derated to zero output linearly
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation of 10,000
feet (3,048m) above sea level. For elevations between 3,000 feet (914m) and 10,000 feet (3,048m), derate
the maximum operating ambient temperature linearly.
Ventilation Variable speed fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class B and EN55022 Class B, radiated and conducted.
Audible Noise 2 feet from any vertical surface; does not exceed 65dBA, 55dBA with low fan speed selected.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 3.5" (8.89cm) x 3.125" (7.937cm) x 12" (30.48cm)
Weight 6 lbs. (2.239 kg)
Safety Compliance UL recognized (UL 1950), CSA 22.2, No.950, CE

Additional Information
For additional specification, engineering and
installation information, request specification
number 589800300 for the 23" (58.42 cm)
option.

For ordering information, request


589200300.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
54 : Enterprise
PPB-SDCP-068 / 1206
LORAIN® XP 48500 DC Power for
Business-Critical Continuity
DC Power System

Key Features
LORAIN® eXpandable Power (LXP), the next
• Compact expandable
system — holds up to 165 amps at
generation small power platform from Emerson
54.48V (9kw) in 2 rack spaces and providing expandable power, distribution,
468 amps at 54.48V (25.5kw) in 6
rack spaces
control and monitoring.

• Constant power option —


delivers more current at lower Description
voltages to meet load or
recharge demand The LORAIN® eXpandable Power (LXP) System is composed of one to three rectifier
shelves, each arranged for up to six 1500 watt constant power rectifier modules. A
• Rugged design — rated for centralized controller forms the heart of the system, featuring web-based software,
continuous operation from -40°C user-programmable inputs and alarms, remote access and battery management. The
distribution cabinet is designed for up to eighteen plug-in fuse holders or breakers rated
to +80°C
1 to 100 amps to meet load distribution requirements. For smaller loads, an optional 10-
position GMT fuse module is available. An optional low-voltage disconnect circuit can be
• Complies with industry configured for battery or load disconnect. The LXP system is a cost-effective solution for
standards — NEBS™ level 3 loads under 24 Kw. As load demand grows, the system can be easily expanded with addi-
certified and UL Listed tional modular components.

• Extensive battery
management — includes health,
reserve time, and
test capability

• Four user definable binary


inputs — for external alarm or
control functions

• Alarm and event logs — record


system history

• User programmable — six sets


of form C alarm relay contacts are
available
LXP System
• Remote access — TCP/IP, Ethernet

Enterprise : 55
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System

Application
LXP systems are rated for continuous opera- The system is designed for deployment in applications include: DLC, xDSL, DSLAM,
tion from -40°C to +80°C and are NEBS™ central office, POP sites, co-location sites, FITL electronics, broadband communica-
Level 3 certified and UL Listed. 19 or 23- customer premises, outdoor cabinets, tions, multiplexers, PCS, microwave and
inch cabinet configurations are available. CEVs, vaults or portable shelters. Specific PBX.

56 : Enterprise
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System

Rectifier Shelves
LXP rectifier shelves are 3.5" (2 RU) high,
12" deep and are available in 19" or 23"
widths. The 19" rack mounts up to 5 rec-
tifier modules and the 23" rack mounts
up to 6 rectifier modules. These shelves
provide front to back ventilation and can
be stacked up to 3 high with zero clear-
ance above or below units, maximizing
revenue-generating space. Each unit will
operate from 120/208/240VAC and is
equipped with dual inputs to accommo-
date line cords or hard wiring. DC output
connection options for each shelf include
LXP System
dual two-hole compression lugs or bus
bar terminations for connection to local or
remote distribution and batteries. The shelf
with rectifiers is NEBS™ Level 3 certified,
UL Listed and meets FCC Class B EMI/RFI
requirements.

Rectifier Modules
LXP rectifiers are rated for 1500 watt
constant output power when operated at
208/240VAC nominal input, 32.6 amps
at 46VDC to 25.8 amps at 58VDC. When
operated at 120VAC nominal input the out-
put power is rated at 750 watts, 16.3 amps
at 46VDC to 12.9 amps at 58VDC. The
rectifier will provide up to 100% of rated
power at 65°C. As the temperature increas-
es from 65°C to 80°C, the thermal power
LXP Rectifier Module limit circuit linearly decreases power. In
the typical operating range, these recti-
fiers have a power factor greater than .99,
total harmonic distortion less than 5% and
efficiencies greater than 91%. Each hot-
swappable rectifier has an integral cooling
fan and a tri-color LED status indicator.

Enterprise : 57
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System

As load demand grows, the system can be easily


expanded with additional modular components.

Controller activity and alarm history logs, inventory


The LXP controller is designed for functions, and a sequential rectifier start
fail safe operation and includes a two-line capability. The controller features web-
20-character display, three menu naviga- based software and an RJ45 connection for
tion keys and five LED status indicators. The remote access via TCP/IP or Ethernet. The
LEDs display the status of AC power, minor base controller provides the following bat-
and major alarms, fault conditions and bat- tery management capabilities: temperature
tery conditions. Four binary inputs and six compensation, thermal runaway manage-
form C alarm contacts, all user programma- ment, system conditions, functionality
ble, are provided. In addition to traditional testing, battery recharge current
system alarms and controls, the LXP sys- limit, half-string monitoring and
LXP Controller tem features a loss of redundancy alarm, discharge testing.

Battery Management Batteries


The following enhanced battery manage- LXP systems can be configured with a wide
ment functions are available as add on range of batteries to suit specific load and
options: reserve time, float current moni- reserve time requirements. Battery connec-
toring, impedance imbalance, individual tions can be made directly to the rectifier
cell monitoring and multiple string moni- shelf or the distribution cabinet. Optional
toring. battery maintenance disconnects are avail-
able if required.

Distribution Cabinet in fuse holders at 23" and 13 plug-in fuse


The front access LXP distribution holders at 19" or breakers rated 1 to 100
cabinet is 5.25" (3 RU) high, 12" deep, 23" or amps. An optional block of 10 GMT-type
19" configuration, with a maximum current fuse positions is available for smaller loads.
capacity of 300 amps. The cabinet includes An optional LVD circuit is available with dual
LXP Distribution Cabinet a main load shunt, a ground return bar, and redundant controls, configurable for bat-
an alarm circuit for local and remote fuses. tery or load disconnect.
The cabinet is designed for up to 18 plug-

58 : Enterprise
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System

Specifications
Input
Voltage Nominal 120/208/240 volts AC, single phase, 50/60 Hz, with a range of 84 to 286 volts.
Extended range to 300 volt AC without damage.
Current 7.92 amps@208VAC, 6.87 amps@240VAC per PCU, 54.48VDC, 1500 watts output
23.76 amps@208VAC, 20.6 amps@240VAC per feed (3 PCUs), 54.48VDC, 4500 watts output
30 amp breaker recommended per feed
9.36 amps@176VAC, 1500 watts output (worst case) 28 amps@176VAC (worst case) per feed (3 PCUs)
6.94 amps@120VAC per PCU, 54.48VDC, 750 watts output
20.83 amps@120VAC per feed, 54.48VDC, 2250 watts output
9.92 amps@84VAC, 750 watts output (worst case) per PCU; 29.75 per feed
Inrush Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage within the rated
input voltage range.
Frequency 45-65 Hz
Protection Shelf input is wired for a Dual AC input. The first feed will power PCUs 1, 3, and 5, while the second feed
will power PCU’s 2, 4, and 6. If the AC input voltage decreases or increases beyond a non-adjustable
predetermined value, the PCU power conversion circuitry inhibits, disabling PCU output. The PCU will
recover automatically when the AC input voltage is re-established within specifications limits.
Power Factor Typical power factor greater than or equal to 99% for any load greater than or equal to 50% of rated full load
at nominal line. Meets IEC 1000–3–2.
Operating Efficiency Typical operating efficiency 91% at full load
Output
Voltage Nominal -48 volts DC, positive ground, adjustable from -46.0 to -58.0 volts DC
Current 25 to 32.6 amps per PCU, up to a total of 125 to 163 amps per shelf with five PCUs installed in the main
shelf and up to a total of 150 to 195.6 amps per shelf with six PCUs installed in each supplemental shelf.
Power 1,500 watts maximum. The PCU employs a constant power limiting feature which limits the maximum output
power to 1,500 watts over the output voltage range of –46.0 to -58.0VDC.
Regulation Steady state output voltage remains within ±0.5% of any voltage within the range of 46.0 to 58.0 volts DC
for any combination of frequency, input voltage, and load from no load to full load over the temperature
range of -20°C to +65°C (-4°F to +149°F).
Filtering On or off battery
Voice Band Noise Less than 32 dBrnC
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 30 mv rms
Psophometric Noise Does not exceed 1 mv

Enterprise : 59
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System

Specifications (continued)
Protection
Current Limiting Maximum output current of each PCU can be set from 2.5 to 32.6 amps
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately three
seconds, the PCU automatically restarts.
Monitoring
Status/Alarm Indicators Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed
on the 2 Line 20-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature -40°C to +65°C (-4°F to +149°F); -40°C to +80°C (-40°F to +176°F) derated to zero output linearly
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation of 10,000
feet (3,048m) above sea level. For elevations between 3,000 feet (914m) and 10,000 feet (3,048m), derate
the maximum operating ambient temperature linearly.
Ventilation Fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class B and EN55022 Class B, radiated and conducted
Audible Noise 2 feet from any vertical surface; does not exceed 65dBA, 55dBA with low fan speed selected.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 3.5" (8.89cm) x 3.125" (7.937cm) x 12" (30.48cm)
Weight 6 lbs. (2.239 kg)
Safety Compliance UL recognized (UL 1950), CSA 22.2, No.950, CE

Additional Information
For additional specification, engineering and installation information, request specification number 582135100 for the 19" (48.26 cm) option
and number 582135000 for the 23" (58.42 cm) option.

For ordering information, request SAG582135000 for the 23" and SAG582135100 for the 19" option.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
60 : Enterprise
PPB-SDCP-001 / 1206
LORAIN® CIP 4890/48120 DC Power for
Business-Critical Continuity
DC Power System

Key Features

• Compact flexibility — provides


rectifiers, distribution, and
controller in one shelf

• Constant power — delivers more


current at lower voltages to meet
load or recharge demand

• Wide operating range —


operates in the most demanding
environments with operating input LORAIN® CIP 4890
voltage from 85VAC to 300VAC

• Meets industry standards —


Description
NEBS™ Level 3 certified and
UL 1801 The LORAIN® CIP power system is a modular integrated -48VDC power system contained
in a single shelf. Two shelf configurations are available. The LORAIN® CIP 48120 consists
of a 23" shelf that incorporates up to four 750W or 1500W plug-in rectifiers and a Multi
• Eight binary inputs (5 user
Function Unit that contains a basic or advanced controller, a distribution module with 6
programmable) — form C plug-in load positions, and three battery connections. The LORAIN® CIP 4890 consists
contacts for external alarm or of a 19" shelf that incorporates up to three 750W or 1500W plug-in rectifiers and a Multi
control functions Function Unit that contains a basic or advanced controller and a distribution module with
6 plug-in load positions and three battery connections. Each of the 6 load positions in
• Eight user programmable the distribution module accommodates bullet nose plug-in circuit breakers rated 1 to
outputs — eight sets of form C 100 amps or bullet nose plug-in fuse holders for TPS fuses rated 1 to 50 amps. For smaller
alarm relay contacts are available loads, an optional plug-in 10 position fuse module is available occupying 3 mounting posi-
tion, offering fuses rated 0.18 to 20 amps.
• Remote Access — TCP/IP, web
browser, SNMP compatible

• Compliant with global


standards — delivers quality,
performance and dependability
no matter what the application or
location demands

Enterprise : 61
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

Application

The LORAIN® CIP power system is The system is designed to supply a filtered
designed to be mounted in standard 19" or and regulated -48Vdc source to any tele-
23" frames, or used in embedded applica- communication equipment requiring up
tions with standard 19" or 23" mounting, to 80 amps redundant capacity in a 23"
with or without batteries. The system is shelf or up to 54 amps redundant capacity
rated for full continuous operation from - in a 19" shelf, such as POP sites, customer
40°C to +65°C and is NEBS™ Level 3 certified premises, outdoor cabinets, CEVs, vaults or
and UL(60950 & 1801). shelters. Specific applications include: DLC,
xDSL, DSLAM, broadband communications,
multiplexers, microwave and PBX.

System Shelf
The LORAIN® CIP shelves are 5.25" (3U) high, nectivity options for single phase 110/120
13" deep and 23" or 19" wide. The 23" wide and 208/240VAC feeds. The AC supply can
shelf mounts four rectifier modules and be connected to the shelf through IEC320
a Multi-Function Module. The 19" wide AC receptacles at rear side of the shelf, or
shelf mounts three rectifier modules and a through an AC interface box with IEC320 AC
Multi-Function Module. The shelves provide receptacles at the front left of the shelf for
front to back ventilation with zero clearance front access applications. The 23" wide shelf
LORAIN® CIP 4890 System Shelf required above or below. can also be configured with four connections
for conduits at the rear or with dual or single
Each rectifier position provides interconnec- connectivity at the front for conduit(s). The
tion points for the AC input, the DC output, 19" wide shelf offers a single AC rear access
and the control and alarm data bus (CAN connectivity, with conduit.
protocol). Each shelf provides a variety of con-

62 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

Rectifier Modules
The LORAIN® CIP system uses 1500W or In the typical operating range, the recti-
750W constant power switch mode rectifier fiers have a power factor greater than .99,
modules. Both rectifiers have a DC operat- total harmonic distortion less than 5% and
ing range of -43.0 to -58.5VDC. The 1500W efficiencies of 91%. The rectifiers are hot
module provides 1500W from 200 to swappable and have an integrated speed
300VAC with current limiting at 34 amps. controlled field replaceable fan. Each recti-
Output power is de-rated to 90% from 176 fier can optionally be equipped with a field
to 200VAC, to 60% at 120VAC, and to 50% replaceable air filter. Three LED indicators
at 100VAC. The 750W module provides provide visual status of normal operation,
750W from 100 to 300VAC with current alarm, rectifier failure alarm, and fan failure
limiting at 17 amps. Both rectifiers provide alarm.
up to 100% of rated output up to 75°C.
1500W Rectifier Module

Controller Modules
Two controller modules are available for use (RJ45 jack). The following battery manage-
in the LORAIN® CIP system – a basic control- ment capabilities are provided: battery
ler and an advanced controller. The System database, temperature compensation,
Manager IP is the advanced controller. It has equalize, battery discharge test, and charge
a graphical LCD display with four navigation control.
keys. The local alarm display uses LED indica-
tors for controller status and system major The Controller IP is the basic controller
and minor alarms. Eight user programmable available with the LORAIN® CIP system. The
input ports and eight user programmable operational features of the Controller IP are
Controller IP output ports with form C contacts are as follows: local alarm display by means of
included. In addition to traditional system three LED indicators, three alarm outputs
alarms and controls, the System Manager (dry C contacts), and two sets of local test
IP provides event and alarm history logs, an points for the measurement of the system’s
inventory log, and delivered DC power calcu- voltage and current. DIP switches are used
lation. The System Manager IP can to adjust float voltage, temperature com-
be accessed locally or remotely using a built- pensation, and the optional low voltage
in web based Graphical User Interface. Local disconnect.
connection is made through the Ethernet
port using a computer equipped with a web
browser and crossover cable. Remote con-
nection is made through a dial up network
System Manager IP connection with a modem connected to
the system’s RS-232 port, or through a
network LAN connection to the TCP/IP port

Enterprise : 63
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

Multi-Functional Unit Batteries


The Multi-Functional Unit located at the The LORAIN® CIP system can be configured
right side of the shelf contains a controller with a wide range of batteries to suit
position and a distribution unit. specific load and reserve requirements.
Battery connections are made to the distri-
Distribution Unit bution unit through three Anderson type
The distribution unit can be equipped connectors.
either with:
Temperature Probe Interface (TPI)
• up to six bullet-type single-pole circuit
The Temperature Probe Interface is
breakers in capacities from 1 to 100 A or
a module that can monitor an ambient
fuses in capacities from 1 to 50 A, or
temperature probe and up to eight bat-
• up to three bullet-type single-pole circuit tery temperature probes, then retransmit
Multi-Functional Unit breakers in capacities from 1 to 100 A the ambient temperature and the highest
or fuses in capacities from 1 to 50 A, battery temperature measurements to the
and one 10-position fuse kit for fuses in controller. The added number of measuring
capacities from 0.180 to 20 A, or points improves the accuracy of the tem-
perature compensation function and the
• t wo 10-position fuse kits for fuses in precision of the high battery temperature.
capacities from 0.180 to 20 A. The TPI has two visual indications, Power
Load clips are used to accommodate the ON (green) and Probe Fail alarm (yellow),
bullet-type single-pole circuit breakers or as well as one set of “fail safe” output relay
fuse blocks, as well as 1-hole lugs with anti- contacts for the Probe Fail alarm.
Single-position TPS Fuse rotation device for cable sizes up to No. 6
AWG. The circuit breakers are of the mid-
trip type. Breaker guards are also available
(optional) to prevent accidental tripping of
the circuit breakers.

The distribution unit contains a battery shunt


and an optional battery or load LVD.

Single-position Circuit Breaker

3-position Block for 10 SAN-O Fuses

64 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

LORAIN® CIP 4890/120 General Specifications


System Characteristics
Nominal system voltage -48Vdc
Rated output capacity
LORAIN® CIP 4890 90 amps
LORAIN® CIP 48120 120 amps
Rectifiers Rectifier -48Vdc, 1500W or Rectifier -48Vdc, 750W
Controller
Basic Controller IP
Advanced System Manager IP
Distribution Bullet nose type circuit breakers or fuse, and/or
SAN-O type fuses
Environmental
Operating temperature -40°F to 149°F (-40°C to 65°C) continuous operation
Storage -40°F to 167°F (-40°C to 75°C) Relative humidity
and transportation below 95% (non-condensing)
Seismic rating Telcordia GR-63-CORE, zone 4
NEBS™ Level 3 certified
Safety UL per subject letter 1801, UL60950, CE marked, FCC part 15, subpart B and Telcordia GR-1089-CORE &
Emissions for Class B , EN 300 386

System Shelf Specifications


Capacity
LORAIN® CIP 4890 90 amps
LORAIN® CIP 48120 120 amps
Dimensions (H x W x D)
LORAIN® CIP 4890 5.25" (133mm) x 19" (483mm) x 12" (308mm)
LORAIN® CIP 48120 5.25" (133mm) x 23" (584mm) x 12" (308mm)
Weight
LORAIN® CIP 4890 19.8 lbs. (9 kg)
LORAIN® CIP 48120 22 lbs. (10 kg)
AC connections
LORAIN® CIP 4890 Individual connections per rectifier with IEC connectors, rear and front access
Single AC Rear access with conduit
LORAIN® CIP 48120 Individual connections per rectifier with IEC connectors, rear and front access
Individual connections per rectifier with conduit, rear access
Single and Dual AC front access, with conduit(s)
Recommended AC 15 amp, 2-pole AC breaker per rectifier per 208/240V or 110/120V feed for individual feed
20 amp, 2-pole AC breaker per conduit per 208/240V or 110/120V feed for LORAIN® CIP 48120 Dual AC front access
30 amp, 2-pole AC breaker for 208/240V or 110/120V feed for LORAIN® CIP 4890 Single AC rear access
40 amp, 2-pole AC breaker for 208/240V or 110/120V feed for LORAIN® CIP 48120 Single AC front access

Enterprise : 65
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

Rectifier -48Vdc, 1500W Specifications


Electrical Specifications
AC input
Nominal Voltage Single phase, 110/120VAC or 208/240VAC
Can be used in the following AC configurations:
• phase-to-phase to 120/240V single phase AC source
• phase-to-phase to a 120/208V 3-phase AC source
• phase-to-neutral to a 220/380V, 230/400V, 240/415V, or 277/480V 3-phase AC source
• phase-to-neutral to a 120/240V single phase AC source
• phase-to-neutral to a 120/208V 3-phase AC source
Operating Voltage Range 85VAC to 300VAC
Frequency 47 Hz to 63 Hz
Power factor (PF) >0.99 from 80% to 100% load at 208 & 240VAC
>0.97 from 50% to 80% load at 208 & 240VAC
Total Harmonic Distortion <5% from 70% to 100% load at 208 & 240VAC
Meets IEC 1000-3-2
Input Current 7.0 amp at 240VAC (Max 9.0 amp)
8.7 amp at 120VAC (Max 9.0 amp)
Inrush Current Peak does not exceed 2.5 times the RMS input at any load under input voltage within rated input
voltage range.
Input Protection If the input voltage decreases or increases beyond a non-adjustable predetermined value, the rectifier
circuitry inhibits, disabling the output. The rectifier will recover automatically when the AC input is
re-established within specification limits. Over current is protected by an internal fuse
Operating Efficiency 91.5% at 80% load and 240VAC
>90% from 40% to 100% load at 240VAC
DC Output
Output Voltage Range -43.0Vdc to -58.5Vdc
Output Power Constant power limiting operation
1500W maximum from 200VAC to 300VAC
900W @ 120VAC
600W @ 85VAC
Output Current 25 to 34 amps
Regulation Voltage is regulated within ±0.5% for all specified input and load variations Voltage drift ±0.2% in any
eight-hour period, with constant input voltage, constant load, and less than –5 °C change in ambient
temperature
Voice Band Noise The voice-frequency noise generated by a rectifier does not exceed 38dBrnC output noise
Wide Band Noise Wide band noise generated by a rectifier is less than 100mVrms in any 3 kHz band between 10kHz
and 20MHz and less than 50mVrms over 20Mhz
Peak to peak ripple voltage is less than 125mV from dc up to 100Mhz
Psophometric Noise Does not exceed 1 mV
Protection
Current Limiting The output current is limited to 34 amp
Over current Internal fuse
High Voltage Shutdown If rectifier detects over voltage, it will turn off. After 10 seconds, it will restart and if it encounters an over
voltage within 5 minutes it will turn off and remain off until reset.

66 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

Rectifier -48Vdc, 1500W Specifications (continued)


Operating Specifications
Temperature -40°F to 167°F (-40°C to 75°C) at full rated output
Altitude -200 ft to 13,000 ft (-60 m to 4000 m)
Humidity 0 to 95% relative humidity (non-condensing)
Storage conditions -40°F to 167°F (-40°C to 75°C) Relative humidity below 95% (non-condensing)
Ventilation Front to back speed-controlled fan (field replaceable)
Seismic Telcordia GR-63-CORE for Zone 4
Electromagnetic
Interference (EMI) FCC part 15, subpart B, class B
and compatibility (EMC) EN 300 386-2, class B
Audible noise The rectifier does not produce sound levels above 60dBA, measured 1.5m above the floor and 0.5m from
the equipment
Operation without Yes
batteries
Status / Alarm Indicators and Monitoring
Visual indicators Status Visual indicator color
Normal operation Green
Alarm Yellow
Rectifier failure alarm Red
Fan failure alarm Flashing red
Rectifier alarms & Transmitted to System Manager IP or Controller IP on the communication bus using the CAN protocol
Status Settings The Controller IP or System Manager IP establishes all rectifier settings
Miscellaneous data Each rectifier provides the System Manager IP a complete set of identification information about
itself (product code, serial number, alarm history, etc.)
Rectifier Physical Specifications
Mounting Plug-in installation
Dimensions (H x W x D) 5.25" (133mm) x 3.35" (85mm) x 11.00" (279mm)
Weight 5.5 lbs. (2.5kg)
Fire Resistance All materials have flammability rating -UL 94 V0 or better
All electrical components meet the Needle Flame Test per IEC 695-2-2
Safety The rectifier is UL recognized (UL60950) for USA & Canada and is CE marked

Enterprise : 67
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

Rectifier -48Vdc, 750W Specifications


Electrical Specifications
AC Input
Nominal Voltage Single phase, 110/120VAC or 208/240VAC
Can be used in the following AC configurations:
• phase-to-phase to 120/240V single phase AC source
• phase-to-phase to a 120/208V 3-phase AC source
• phase-to-neutral to a 220/380V, 230/400V, 240/415V, or 277/480V 3-phase AC source
• phase-to-neutral to a 120/240V single phase AC source
• phase-to-neutral to a 120/208V 3-phase AC source
Operating Voltage Range 85VAC to 300VAC
Frequency 45 Hz to 65 Hz
Power Factor (PF) >.99 from 40% to 100% load at 120V
Total Harmonic Distortion <6% from 40% to 100% load at 120V
Meets IEC 1000-3-2
Input Current 7.1 amp at 120VAC (Max 9.0 amp)
3.5 amp at 240VAC
Input Protection If the input voltage decreases or increases beyond a non-adjustable predetermined value, the rectifier
circuitry inhibits, disabling the output. The rectifier will recover automatically when the AC input is
re-established within specification limits. Over current is protected by an internal fuse
Operating Efficiency 91.5% at 100% load and 240VAC
89% at 100% load and 120VAC
DC Output
Output Voltage Range -43.0Vdc to -58.5Vdc
Output Power Constant power limiting feature
750W maximum from 100VAC to 300VAC
600W at 85VAC
Output Current 12 to 17 amps
Regulation Voltage is regulated within ±0.5% for all specified input and load variations Voltage drift ±0.2% in any
eight-hour period, with constant input voltage, constant load, and less than -5°C change in ambient
temperature
Voice-Frequency The voice-frequency noise generated by a rectifier does not exceed 38dBrnC output noise
High Frequency Wide band noise generated by a rectifier is less than 100mVrms in any 3 kHz band between 10kHz and
Output Noise 20MHz and less than 50mVrms over 20Mhz
Peak to peak ripple voltage is less than 200mV from dc up to 100Mhz
Psophometric Noise Does not exceed 1 mV
Protection
Current Limiting The output current is limited to 17 amp
Over current Internal fuse
High Voltage Shutdown If rectifier detects over voltage, it will turn off. After 10 seconds, it will restart and if it encounters an over
voltage within 5 minutes it will turn off and remain off until reset.

68 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

Rectifier -48Vdc, 750W Specifications (continued)


Operating Specifications
Temperature -40°F to 167°F (-40°C to 75°C) at full rated power
Altitude -200 ft to 13,000 ft (-60 m to 4000 m)
Humidity 0 to 95% relative humidity (non-condensing)
Storage conditions -40°F to 167°F (-40°C to 75°C) Relative humidity below 95% (non-condensing)
Ventilation Front to back speed-controlled fan (field replaceable)
Seismic Telcordia GR-63-CORE for Zone 4
Electromagnetic FCC part 15, subpart B, class B
Interference (EMI)
and compatibility (EMC) EN 300 386-2, class B
Audible noise The rectifier does not produce sound levels above 60dBA, measured 1.5 m above the floor and 0.5 m
from the equipment
Operation without Yes
batteries
Status / Alarm Indicators and Monitoring
Visual indicators Status Visual indicator color
Normal operation Green
Alarm Yellow
Rectifier failure alarm Red
Fan failure alarm Flashing red
Rectifier alarms & Transmitted to System Manager IP or Controller IP on the communication bus using the CAN protocol
Status Settings The Controller IP or System Manager IP establishes all rectifier settings
Miscellaneous data Each rectifier provides the System Manager IP a complete set of identification information about itself
(product code, serial number, alarm history, etc.)
Rectifier Physical Specifications
Mounting Plug-in installation
Dimensions (H x W x D) 5.25" (133mm) x 3.35" (85mm) x 11.00" (279mm)
Weight 5.5 lbs. (2.5 kg)
Fire Resistance All materials have flammability rating -UL 94 V0 or better
All electrical components meet the Needle Flame Test per IEC 695-2-2
Safety The rectifier is UL recognized (UL60950) for USA & Canada and is CE marked

Enterprise : 69
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System

Controller Specifications
Controller IP
Display LED status interface
Alarm output 3 dry C contacts outputs (Major, Minor, AC failure/BOD)
Alarm input One external input for distribution and battery fuse alarm
Control of rectifiers Digital CAN bus
System configuration Dip switches for:
System (float) voltage
Temperature compensation battery charging
Low voltage disconnect
Battery management Low Voltage Disconnect (LVLD or LVBD)
Temperature compensation battery charging
System Manager IP
Display LCD display with four navigation buttons
Alarm output 8 dry C contacts (5 programmable)
SNMP & Web (HTML)
Alarm input 8 programmable inputs
Control of rectifiers Digital CAN bus
Battery management Battery Discharge Test
Charge Control
Low Voltage Disconnect (LVLD or LVBD)
Temperature compensation battery charging
Equalize (boost)
System configuration Embedded Web Browser (HTTP)
Communications ports RJ45 jack for Ethernet port (TCP/IP)
DB9 connector for RS-232
Remote access All essential functions and operational parameters through RS-232 modem and TCP/IP Ethernet with
password security

Distribution Unit Specifications


Capacity 6 load positions, 3 battery string connections, 120 amp
Battery shunt, optional LVD
Protection devices
Circuit breaker Bullet Nose Type –1 to 100 amp
Fuses Bullet Nose Type –1 to 50 amp
SAN-O type 0.18 to 20 amp with 10 Position Fuse Block
Battery connections 3 pairs (- &+) Anderson type connectors

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
70 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CSP 48300 DC Power for
Business-Critical Continuity
DC Power System

Key Features

• Compact flexibility — provides


more space for revenue generating
equipment

• Constant power — delivers more


current at lower voltages to meet
load or recharge demand

• Wide operating range —


operates in the most demanding
environments with operating input
voltage from 85VAC to 300VAC

• Meets industry standards —


NEBS™ Level 3 certified and
UL 1801

• Eight binary inputs (5 user


programmable) — form C
contacts for external alarm or Description
control functions
The LORAIN® CSP 48300 power system is a modular -48VDC power system available in var-
• Eight user programmable ious configurations and capacities up to 300 amps. A basic system consists of a power shelf
outputs — eight sets of form C that incorporates a basic or advanced controller and up to five 750W or 1500W plug-in
rectifiers, and an initial distribution panel with 18 plug-in positions accommodating bullet
alarm relay contacts are available
nose type fuse holders rated 1 to 100 amps or circuit breakers rated 1 to 250 amps and 8
positions for connecting batteries with or without protection devices. For smaller loads, an
• Remote Access — TCP/IP, web optional plug-in 10 position fuse module is available occupying 3 mounting position, offer-
browser, SNMP compatible ing fuses rated 0.18 to 10 amps.

• Compliant with global A second power shelf that accommodates up to six 750W or 1500W plug-in rectifiers and
standards — delivers quality, a second distribution panel with 26 plug-in positions for load protection devices can be
performance and dependability added to increase the distribution position capacity. An optional low voltage disconnect
no matter what the application or can be configured for battery or load disconnect.
location demands

Enterprise : 71
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

Application
The LORAIN® CSP power system is a The system is designed to supply a filtered
front access system designed to be and regulated -48VDC source to any tele-
mounted in standard 23" frames or used in communication equipment requiring up to
embedded applications with standard 23" 300 amps capacity such as POP sites, cus-
mounting, with or without batteries. The tomer premises, outdoor cabinets, CEVs,
system is rated for full continuous opera- vaults or shelters, and small Central Offices.
tion from -40°C to +50°C (with excursions Specific applications include: DLC, xDSL,
to 65°C) and is NEBS™ Level 3 certified and DSLAM, broadband communications, mul-
UL(60950 & 1801). tiplexers, radio base stations, microwave
and PBX.

Power Shelves
The LORAIN® CSP power shelves are feeds, one for rectifiers 1, 3 and 5, and one
5.25" (3U) high, 13" deep and 23" wide. for rectifiers 2, 4 and 6 (on the initial power
The initial power shelf mounts five rectifier shelf, position No. 6 is for the controller).
modules and a controller module. The AC supply can be brought into the shelf
LORAIN® CSP power shelves The supplementary shelf mounts 6 rectifier through knockouts at the left rear side of
modules. The shelves provide front to back the shelf, or through an optional AC inter-
ventilation with zero clearance required face box at the front left of the shelf for
above or below. front access applications. DC output con-
nection between shelves and distribution
Each rectifier position provides intercon- panels is made through internal bussing.
nection points for the AC input, the DC
output, and the control and alarm data bus
(CAN protocol). The total output capacity
is 150 amps for the initial shelf and 180
amps for the supplementary shelf. Each
shelf provides connecting points for dual
single phase 110/120 and 208/240VAC

72 : Enterprise
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

Rectifier Modules
The LORAIN® CSP system uses 1500W In the typical operating range, the recti-
or 750W constant power switch mode fiers have a power factor greater than
rectifier modules. Both rectifiers have a .99, total harmonic distortion less than
DC operating range of -43.0 to -58.5VDC. 5% and efficiencies of 91%. The rectifiers
The 1500W module provides 1500W are hot swappable and have an integrat-
from 200 to 300VAC with current limit- ed speed controlled field replaceable fan.
ing at 34 amps. Output power is de-rated Each rectifier can optionally be equipped
to 90% from 176 to 200VAC, to 60% at with a field replaceable air filter. Three
120VAC, and to 50% at 100VAC. The LED indicators provide visual status of
1500W Rectifier Module
750W module provides 750W from 100 normal operation, alarm, rectifier failure
to 300VAC with current limiting at 17 alarm, and fan failure alarm.
amps. Both rectifiers provide up to 100%
of rated output up to 75°C.

Controller Modules
Two controller modules are available for network connection with a modem con-
use in the LORAIN® CSP system – a basic nected to the system’s RS-232 port, or
controller and an advanced controller. through a network LAN connection to
The System Manager SP is the advanced the TCP/IP port (RJ45 jack). The follow-
controller. It has a graphical LCD display ing battery management capabilities are
with four navigation keys. The local alarm provided: battery database, temperature
display uses LED indicators for control- compensation, equalize, battery dis-
ler status and system major and minor charge test, and charge control.
alarms. Eight user programmable input
ports and eight user programmable The Controller SP is the basic control-
output ports with form C contacts are ler available with the LORAIN® CSP System Manager SP
included. In addition to traditional sys- system. The operational features of the
tem alarms and controls, the System Controller SP are as follows: local alarm
Manager SP provides event and alarm display by means of three LED indicators,
history logs, an inventory log, and deliv- three alarm outputs (dry C contacts),
ered DC power calculation. The System and two sets of local test points for the
Manager SP can be accessed locally or measurement of the system’s voltage
remotely using a built-in web based and current. DIP switches are used to
Graphical User Interface. Local connec- adjust float voltage, temperature com-
tion is made through the Ethernet port pensation, and the optional low voltage
using a computer equipped with a web disconnect.
browser and crossover cable. Remote
connection is made through a dial up
Controller SP

Enterprise : 73
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

Distribution Panel

Distribution Panels Batteries


Two distribution panels are available for the LED indicator, and one side of the protec- The LORAIN® CSP system can be configured
LORAIN® CSP system. The initial panel is tion device plugs into a main rail bus, while with a wide range of batteries to suit spe-
5.25" (3RU) high, 13.5" deep and 23" wide, the other side plugs into a removable load cific load and reserve requirements. Battery
with a discharge capacity of 300 amps and clip designed to facilitate cabling opera- connections are made to the initial distribu-
a charge capacity of 330 amps. The panel tions. Load clips are available in three sizes tion panel through protection devices or
is equipped with 18 positions for load pro- – single, double or quadruple position. directly using the factory installed Battery
tection devices (circuit breakers or fuses), The single position accommodates circuit Connection Module.
8 positions for battery protective devices breakers or fuse holders with TPS fuses
or a battery connection kit, a battery cur- from 1 to 60 amps. Double position load Temperature Probe Interface (TPI)
rent shunt, and an optional LVD circuit clips accommodate circuit breakers from The Temperature Probe Interface is
factory-wired for either load disconnect 65 to 150 amps and fuses from 65 to 100 a module that can monitor an ambient
or battery disconnect. The supplementary amps. Quadruple position load clips accom- temperature probe and up to eight bat-
panel has the same dimensions as the initial modate 225 & 250 amp circuit breakers. tery temperature probes, then retransmit
panel and is equipped with 26 positions for the ambient temperature and the highest
load protection devices (circuit breakers battery temperature measurements to the
or fuses) and no battery positions. Both controller. The added number of measuring
the initial and supplementary distribution points improves the accuracy of the tem-
panels provide local fuse and/or circuit perature compensation function and the
breaker alarm indication by means of a red precision of the high battery temperature.
The TPI has two visual indications, Power
ON (green) and Probe Fail alarm (yellow),
as well as one set of “fail safe” output relay
contacts for the Probe Fail alarm.

74 : Enterprise
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

LORAIN® CSP 48300 General Specifications


System Characteristics
Nominal system voltage -48VDC
Rated output capacity 300 amps discharge, 330 amps charge
Rectifiers Rectifier –48VDC, 1500W or Rectifier –48VDC, 750W
Controller
Basic Controller SP
Advanced System manager SP
Distribution Initial and Supplementary Distribution Panels
Environmental
Operating temperature -40°F to 122°F (-40°C to 50°C) continuous operation
Storage -40°F to 167°F (-40°C to 75 °C) Relative humidity
and transportation below 95% (non-condensing)
Seismic rating Telcordia GR-63-CORE, zone 4
NEBS™ Level 3 certified
Safety UL per subject letter 1801, UL60950, CE marked, FCC part 15, subpart B and Telcordia GR-1089-CORE &
Emissions for Class B , EN 300 386

Rectifier -48VDC, 1500W Specifications


Electrical Specifications
AC input
Nominal Voltage Single phase, 110/120VAC or 208/240VAC
Can be used in the following AC configurations:
• phase-to-phase to 120/240V single phase AC source
• phase-to-phase to a 120/208V 3-phase AC source
• phase-to-neutral to a 220/380V, 230/400V, 240/415V, or 277/480V 3-phase AC source
• phase-to-neutral to a 120/240V single phase AC source
• phase-to-neutral to a 120/208V 3-phase AC source
Operating Voltage Range 85VAC to 300VAC
Frequency 47 Hz to 63 Hz
Power factor (PF) >0.99 from 80% to 100% load at 208 & 240VAC
>0.97 from 50% to 80% load at 208 & 240VAC
Total Harmonic Distortion <5% from 70% to 100% load at 208 & 240VAC
Meets IEC 1000-3-2
Input Current 7.0 amp at 240VAC (Max 9.0 amp)
8.7 amp at 120VAC (Max 9.0 amp)
Inrush Current Peak does not exceed 2.5 times the RMS input current at any load under input current within rated input
voltage range.
Input Protection If the input voltage decreases or increases beyond a non-adjustable predetermined value, the rectifier
circuitry inhibits, disabling the output. The rectifier will recover automatically when the AC input is
re-established within specification limits. Over current is protected by an internal fuse
Operating Efficiency 91.5% at 80% load and 240VAC
>90% from 40% to 100% load at 240VAC

Enterprise : 75
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

Rectifier -48VDC, 1500W Specifications (continued)


DC Output
Output Voltage Range -43.0VDC to -58.5VDC
Output Power Constant power limiting operation
1500W maximum from 200VAC to 300VAC
900W @ 120VAC
600W @ 85VAC
Output Current 25 to 34 amps
Regulation Voltage is regulated within ±0.5% for all specified input and load variations Voltage drift ±0.2% in any
eight-hour period, with constant input voltage, constant load, and less than –5 °C change in ambient
temperature
Voice Band Noise The voice-frequency noise generated by a rectifier does not exceed 38dBrnC output noise
Wide Band Noise Wide band noise generated by a rectifier is less than 100mVrms in any 3 kHz band between 10kHz
and 20MHz and less than 50mV rms over 20Mhz
Peak to peak ripple voltage is less than 125mV from dc up to 100Mhz
Psophometric Noise Does not exceed 1 mV
Protection
Current Limiting The output current is limited to 34 amp
Over current Internal fuse
High Voltage Shutdown If rectifier detects over voltage, it will turn off. After 10 seconds, it will restart and if it encounters an over
voltage within 5 minutes it will turn off and remain off until reset.
Operating Specifications
Temperature -40°F to 167°F (-40°C to 75°C) at full rated output
Altitude -200 ft to 13,000 ft (-60 m to 4000 m)
Humidity 0 to 95% relative humidity (non-condensing)
Storage conditions -40°F to 167°F (-40°C to 75 °C) Relative humidity below 95% (non-condensing)
Ventilation Front to back speed-controlled fan (field replaceable)
Seismic Telcordia GR-63-CORE for Zone 4
Electromagnetic
Interference (EMI) FCC part 15, subpart B, class B
and compatibility (EMC) EN 300 386-2, class B
Audible noise The rectifier does not produce sound levels above 60dBA, measured 1.5m above the floor and 0.5 m
from the equipment
Operation without Yes
batteries
Status / Alarm Indicators and Monitoring
Visual indicators Status Visual indicator color
Normal operation Green
Alarm Yellow
Rectifier failure alarm Red
Fan failure alarm Flashing red
Rectifier alarms & Transmitted to System Manager SP or Controller SP on the communication bus using the CAN protocol
Status Settings The Controller SP or System Manager SP establishes all rectifier settings
Miscellaneous data Each rectifier provides the System Manager SP a complete set of identification information about
itself (product code, serial number, alarm history, etc.)

76 : Enterprise
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

Rectifier -48VDC, 1500W Specifications (continued)


Rectifier Physical Specifications
Mounting Plug-in installation
Dimensions (H x W x D) 5.25" (133mm) x 3.35" (85mm) x 11.00" (279mm)
Weight 5.5 lbs. (2.5kg)
Fire Resistance All materials have flammability rating -UL 94 V0 or better
All electrical components meet the Needle Flame Test per IEC 695-2-2
Safety The rectifier is UL recognized (UL60950) for USA & Canada and is CE marked

Rectifier -48VDC, 750W Specifications


Electrical Specifications
AC Input
Nominal Voltage Single phase, 110/120VAC or 208/240VAC
Can be used in the following AC configurations:
• phase-to-phase to 120/240V single phase AC source
• phase-to-phase to a 120/208V 3-phase AC source
• phase-to-neutral to a 220/380V, 230/400V, 240/415V, or 277/480V 3-phase AC source
• phase-to-neutral to a 120/240V single phase AC source
• phase-to-neutral to a 120/208V 3-phase AC source
Operating Voltage Range 85VAC to 300VAC
Frequency 47 Hz to 63 Hz
Power Factor (PF) >.99 from 40% to 100% load at 120V
Total Harmonic Distortion >6% from 40% to 100% load at 120V
Meets IEC 1000-3-2
Input Current 7.1 amp at 120VAC (Max 9.0 amp)
3.5 amp at 240VAC
Inrush Current Peak does not exceed 2.5 times the RMS input at any load at 120VAC input voltage
Input Protection If the input voltage decreases or increases beyond a non-adjustable predetermined value, the rectifier
circuitry inhibits, disabling the output. The rectifier will recover automatically when the AC input is
re-established within specification limits. Over current is protected by an internal fuse
Operating Efficiency 91.5% at 100% load and 240VAC
89% at 100% load and 120VAC
DC Output
Output Voltage Range -43.0VDC to -58.5VDC
Output Power Constant power limiting feature
750W maximum from 100VAC to 300VAC
600W at 85VAC
Output Current 12 to 17 amps
Regulation Voltage is regulated within ±0.5% for all specified input and load variations Voltage drift ±0.2% in any
eight-hour period, with constant input voltage, constant load, and less than –5 °C change in ambient
temperature
Voice-Frequency The voice-frequency noise generated by a rectifier does not exceed 38dBrnC output noise
High Frequency Wide band noise generated by a rectifier is less than
Output Noise 100mVrms in any 3 kHz band between 10kHz and 20MHz and less than 50mV rms over 20Mhz
Peak to peak ripple voltage is less than 200mV from dc up to 100Mhz
Psophometric Noise Does not exceed 1 mV

Enterprise : 77
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

Rectifier -48VDC, 750W Specifications (continued)


Protection
Current Limiting The output current is limited to 17 amp
Over current Internal fuse
High Voltage Shutdown If rectifier detects over voltage, it will turn off. After 10 seconds, it will restart and if it encounters an over
voltage within 5 minutes it will turn off and remain off until reset.
Operating Specifications
Temperature -40°F to 167°F (-40°C to 75°C) at full rated power
Altitude -200 ft to 13,000 ft (-60 m to 4000 m)
Humidity 0 to 95% relative humidity (non-condensing)
Storage conditions -40°F to 167°F (-40°C to 75 °C) Relative humidity below 95% (non-condensing)
Ventilation Front to back speed-controlled fan (field replaceable)
Seismic Telcordia GR-63-CORE for Zone 4
Electromagnetic FCC part 15, subpart B, class B
Interference (EMI)
and compatibility (EMC) EN 300 386-2, class B
Audible noise The rectifier does not produce sound levels above 60dBA, measured 1.5m above the floor and 0.5 m
from the equipment
Operation without Yes
batteries
Status / Alarm Indicators and Monitoring
Visual indicators Status Visual indicator color
Normal operation Green
Alarm Yellow
Rectifier failure alarm Red
Fan failure alarm Flashing red
Rectifier alarms & Transmitted to System Manager SP or Controller SP on the communication bus using the CAN protocol
Status Settings The Controller SP or System Manager SP establishes all rectifier settings
Miscellaneous data Each rectifier provides the System Manager SP a complete set of identification information about itself
(product code, serial number, alarm history, etc.)
Rectifier Physical Specifications
Mounting Plug-in installation
Dimensions (H x W x D) 5.25" (133mm) x 3.35" (85mm) x 11.00" (279mm)
Weight 5.5 lbs. (2.5kg)
Fire Resistance All materials have flammability rating -UL 94 V0 or better
All electrical components meet the Needle Flame Test per IEC 695-2-2
Safety The rectifier is UL recognized (UL60950) for USA & Canada and is CE marked

78 : Enterprise
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

Power Shelf Specifications


Capacity
Initial shelf 5 Rectifiers, Controller position, 150 amp
Supplementary Shelf 6 Rectifiers, 180 amp
Dimensions (H x W x D) 5.25" (133mm) x 23" (584mm) x 13" (330 mm)
Weight Initial – 11.8 lbs. (5.35kg)
Supplementary – 11.25 lbs. (5.1kg)
AC connections Two connections per shelf (odd & even rectifiers)
Recommended AC 30 amp, 2-pole AC breaker per 208/240V feed (3 rectifiers)
Service input 30 amp, 2-pole AC breaker per 110/120V feed (3 rectifiers)

Controller Specifications
Controller SP
Display LED status interface
Alarm output 3 dry C contacts outputs (Major, Minor, AC failure/BOD)
Alarm input One external input for distribution and battery fuse alarm
Control of rectifiers Digital CAN bus
System configuration Dip switches for:
System (float) voltage
Temperature compensation battery charging
Low voltage disconnect
Battery management Low Voltage Disconnect (LVLD or LVBD)
Temperature compensation battery charging
System Manager SP
Display LCD display with four navigation buttons
Alarm output 8 dry C contacts (5 programmable)
SNMP & Web (HTML)
Alarm input 8 programmable inputs
Control of rectifiers Digital CAN bus
Battery management Battery Discharge Test
Charge Control
Low Voltage Disconnect (LVLD or LVBD)
Temperature compensation battery charging
Equalize (boost)
System configuration Embedded Web Browser (HTTP)
Communications ports RJ45 jack for Ethernet port (TCP/IP)
DB9 connector for RS-232
Remote access All essential functions and operational parameters through RS-232 modem and TCP/IP Ethernet with
password security

Enterprise : 79
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System

Distribution Panel Specifications


Capacity
Initial panel 18 load position, 8 battery connections, 300 amp
Battery shunt, optional LVD (LVBD or LVLD)
Supplementary panel 26 load positions, 300 amp
Protection devices
Circuit breaker Bullet Nose type with load clip
1 to 60 amp use single position load clip
65 to 150 amp use double position load clip with spacing restrictions
225 and 250 amp use quadruple position load clip with spacing restrictions
Fuses Bullet Nose type with load clip
TPS type 1 to 60 amp use single load clip
TPS & TLS Type 65 to 100 amp use double load clip
SAN-O type 0.18 to 10 amp with 10 Position Fuse Block
Battery connections Protected using circuit breakers up to 200 amp
Hardwired using optional Battery Connection Kit
Dimensions (H x W x D) 7.0" (177.8mm) x 23.0" (584mm) x 13.5" (343mm)
Weight
Initial panel 27.5 lbs. (12.5kg) with LVD
24.3 lbs. (11.0kg) without LVD
Supplementary panel 24.3 lbs. (11.0kg)

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
80 : Enterprise
PPB-ES-71100 / 1206
NetSure™ 701NCBB DC Power for
Business-Critical Continuity
DC Power System

Key Features
Description
• Compact flexibility — provides
more space for revenue generating The NetSure™ 701NCBB power system is a modular -48VDC power system available in vari-
ous configurations and capacities up to 600 amps. A basic system consists of a power shelf
equipment
that incorporates a standard or advanced controller and up to five 3200W plug-in recti-
fiers, and an initial distribution panel with up to 20 plug-in positions accommodating bullet
• Constant power — delivers more nose type fuse holders rated 1 to 100 amps or circuit breakers rated 1 to 250 amps and
current at lower voltages to meet up to 10 positions for connecting batteries with or without protection devices. For smaller
load or recharge demand loads, an optional plug-in 10 position fuse module (up to 20A fuses) is available occupying
3 mounting position.
• Wide operating range —
operates in the most demanding A second power shelf that accommodates
environments with operating input up to six 3200W plug-in rectifiers and a
voltage from 85VAC second distribution panel with plug-in
to 290VAC positions for load & battery protection
devices can be added to increase the
system capacity to 600A. An optional low
• Meets industry standards —
voltage disconnect can be configured for
Designed to NEBS™ Level 3 battery disconnect in each distribution.
and UL 1801

• Eight programmable binary NetSure™ 701NCBB View


inputs — form C contacts for Application 300 amp
external alarm or control functions
The NetSure™ 701NCBB power system
is a front access system designed to be
• Eight user programmable
mounted in standard 23" frames or used in
outputs — eight sets of form C
embedded applications with standard 23"
alarm relay contacts are available mounting, with or without batteries. The
system is rated for full continuous opera-
• Remote Access — TCP/IP, web tion from -40°C to +40°C (with excursions
browser, SNMP compatible with to 55°C) and is designed to meet NEBS™
the advanced controller Level 3.

• Compliant with global The system is designed to supply a filtered


standards — delivers quality, and regulated -48VDC source to any tele-
performance and dependability communication equipment requiring up to
600 amps capacity such as POP sites, cus-
no matter what the application
tomer premises, outdoor cabinets, CEVs,
or location demands to meet
vaults or shelters, and small Central Offices.
changing demands Specific applications include: DLC, xDSL,
DSLAM, broadband communications, mul-
tiplexers, radio base stations, microwave
and PBX.
NetSure™ 701NCBB Front View
600 amp

Enterprise : 81
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System

In the typical operating range, the recti-


fiers have a power factor greater than .99,
total harmonic distortion less than 5% and
efficiencies of up to 92%. The rectifiers
are hot swappable and have an integrated
Power Shelves speed controlled field replaceable fan.
Three LED indicators provide visual status
Power Shelves of normal operation, alarm, rectifier failure Distribution Panel
The NetSure™ 701 power shelves are 5.25" alarm, and fan failure alarm.
(3U) high, 14.5" deep and 23" wide. The Distribution Panels
initial power shelf mounts five rectifier Three models of distribution are available
modules and a controller module. The for the NetSure™ 701 system. The panels
supplementary shelf mounts 6 rectifier are 5.25" (3RU) high, 14.5" deep and 23"
modules. The shelves provide front to back wide, with a discharge capacity of 300
ventilation with zero clearance required amps and a charge capacity of 330 amps.
above or below. Each panel is equipped with either 16,18
or 20 positions for load protection (circuit
Each rectifier position provides interconnec- breakers or fuses), 10, 8 or 6 positions for
tion points for the AC input, the DC output, battery protective devices or a battery con-
and the control and alarm data bus (CAN Standard Control Unit nection kit, a battery current shunt, and an
protocol). The total output capacity is 330 optional LVD circuit factory-wired for bat-
amps for the initial shelf and 400 amps for Controller Modules tery disconnect. Two panels are required to
the supplementary shelf. Each shelf provides Two controller modules will be available for operate above 300A of load and will offer
connecting points for individual single phase use in the NetSure™ 701NCBB system — the the added benefit of allowing for load shed-
208/240VAC feeds, one per rectifiers. standard controller (SCU) is available now ding functionality.
and the advanced controller (ACU) will be
The AC supply can be brought into the available later. Both controllers have a Each distribution panels provide local fuse
shelf through knockouts at the left rear graphical LCD display with six navigation and/or circuit breaker alarm indication by
or front side of the first shelf and at the keys. The local alarm display uses LED indi- means of a red LED indicator. One side of the
right rear or front of the second shelf to cators for controller status and system protection device plugs into a main rail bus,
accommodate both front and rear access major and minor alarms. Eight user pro- while the other side plugs into a remov-
applications. DC output connection grammable input ports and eight user able load clip designed to facilitate cabling
between shelves and distribution panels is programmable output ports with form C operations. Load clips are available in three
made through internal bussing and cables. contacts are included. In addition to tradi- sizes – single, double or quad position.
tional system alarms and controls, the The single position accommodates circuit
controllers provide event and alarm history breakers or fuse holders with TPS fuses
logs and an inventory log. The SCU can be from 1 to 65 amps. Double position load
accessed locally and the ACU can be accessed clips accommodate circuit breakers from
remotely using a built-in web based multi- 70 to 150 amps and fuses from 70 to 100
language Graphical User Interface. Local amps. Quad load clips accommodate circuit
connection on the SCU is made through the breakers from 225 to 250 amps.
RS-232 port. The ACU can be locally
accessed through the RS-232 or the Batteries
TCP/IP port. The NetSure™ 701 system can
R48-3200 Rectifier be configured with a wide range of bat-
Remote access is made through a dial up net- teries to suit specific load and reserve
R48-3200 Rectifier Modules work connection with a modem connected requirements. Battery connections are
The NetSure™ 701 system uses 3200W to the system’s RS-232 port, or through a made to the initial distribution panel
constant power switch mode rectifier network LAN connection to the TCP/IP port through protection devices or directly
modules. Rectifiers have a DC operating (RJ45 jack). The following battery manage- using the factory installed Battery
range of -42.0 to -58VDC. The 3200W ment capabilities are provided on both Connection Module.
module provides 3200W from 176 to controllers: battery database, temperature
290VAC with current limiting at 67 amps. compensation, battery discharge test, low
Output power is linearly de-rated from voltage disconnect and charge control. The
176VAC to 85VAC and above 45°C. ACU also offers advanced site monitoring
and control features including statistics,
PLC functions and advanced Energy
Savings algorithms.
82 : Enterprise
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System

Battery Asymmetry Unit (BAU 48/4)


BAU 48/4 detects battery backup system that activate a preset voltage difference
failures by comparing the total and the alarm. The unit can be connected to
central point voltages in battery strings. Emerson Network Power Controllers
Battery cell failures, open circuit or short (SCU, ACU, System Manager SP/IP).
circuit failures causes voltage changes

BAU 48/4

NetSure™ 701NCBB General Specifications


System Characteristics
Nominal system voltage -48VDC
Rated output capacity 600 amps discharge, 730 amps charge with two distribution panels
Rectifiers Up to 11 -48VDC, 3200W rectifiers
Controller
Standard SCU (available now)
Advanced ACU (available later)
Distribution 16/10, 18/8 or 20/6 Distribution Panels (Load/Batteries)
Environmental
Operating temperature -40°F to 104°F (-40°C to 40°C) continuous operation
Storage -40°F to 167°F (-40°C to 75°C) Relative humidity
and transportation below 95% (non-condensing)
Seismic rating Telcordia GR-63-CORE, zone 4
NEBS™ Designed to meet NEBS™ Level 3
Safety UL per subject letter 1801, UL60950 (for US and Canada), CE marked, FCC part 15, subpart B and
Telcordia GR-1089-CORE & Emissions for Class B , EN 300 386

R48-3200 Rectifier Specifications


Electrical Specifications
AC input
Nominal Voltage Single phase 208/240VAC
Operating Voltage Range 85VAC to 290VAC
Frequency 45 Hz to 65 Hz
Power factor (PF) >0.99 from 50% to 100% load
Total Harmonic Distortion <5% from 50% to 100% load
Input Current 14.5 amp at 240VAC (Max 20.0 amp)
Inrush Current Peak does not exceed 1.5 times the RMS input current at any load under input current within rated input
voltage range.

Enterprise : 83
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System

R48-3200 Rectifier Specifications (continued)


Input Protection If the input voltage decreases or increases beyond a non-adjustable predetermined value, the rectifier circuitry
inhibits, disabling the output. The rectifier will recover automatically when the AC input is re-established within
specification limits. Over current is protected by an internal fuse
Operating Efficiency 92% peak
>90% from 40% to 100% load at 240VAC
DC Output
Output Voltage Range -42.0VDC to -58.0VDC
Output Power Constant power limiting operation
3200W maximum from 176VAC to 290VAC
1450W @ 120VAC
540W @ 85VAC
Output Current 50 to 67amps
Regulation Voltage is regulated within ±0.5% for all specified input and load variations Voltage drift ±0.2% in any eight-hour
period, with constant input voltage, constant load, and less than -5°C change in ambient temperature
Voice Band Noise The voice-frequency noise generated by a rectifier does not exceed 32dBrnC output noise
Wide Band Noise Wide band noise generated by a rectifier is less than 100mVrms in any 3 kHz band between 10kHz
and 20MHz and less than 50mV rms over 20Mhz
Peak to peak ripple voltage is less than 100mV from dc up to 100Mhz
Psophometric Noise <1mV at 5% to 100% of rated load
Protection
Current Limiting The output current is limited to 67 amp
Over current Internal fuse
High Voltage Shutdown If rectifier detects over voltage, it will turn off. After 5 seconds, it will restart and if it encounters an over voltage
within 5 minutes it will turn off and remain off until reset.
Operating Specifications
Temperature -40°F to 131°F (-40°C to 45°C) at full rated output. Output is derated up to 167°F (75°C)
Altitude -200 ft to 6,500 ft (-60 m to 2000 m) at full rated output
Output power is derated above 6,500 ft (2000 m)
Humidity 0 to 95% relative humidity (non-condensing)
Storage conditions -40°F to 167°F (-40°C to 75°C) Relative humidity below 95% (non-condensing)
Ventilation Front to back speed-controlled fan (field replaceable)
Seismic Telcordia GR-63-CORE for Zone 4

Output power vs. Input voltage Output Power vs. Temperature Output voltage vs. Output current,
at Tamb <45°C at Uin>176VAC max. output power 3200W
85 176 290 45 5055 65
70
55A 67A
120 120 70
% of max output power

Output Voltage (V)


% of max output power

100 100 60
50
80 80
40
60 60 30
40 40 20
20 20 10
0
0 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0 50 100 150 200 250 300 350 -40 -20 0 20 40 60 80 100
Output Current (A)
Input Voltage (VAC) Temperature (C°)

84 : Enterprise
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System

R48-3200 Rectifier Specifications (continued)


Electromagnetic
Interference (EMI) FCC part 15, subpart B, class B
and compatibility (EMC) EN 300 386-2, class B
Audible noise The rectifier does not produce sound levels above 50dBA, measured 1.5m above the floor and 0.5 m from
the equipment
Operation without batteries Yes
Status / Alarm Indicators and Monitoring
Visual indicators Status Visual indicator color
Normal operation Green
Alarm (V,T,unbalance) Yellow
Rectifier failure alarm Red
Fan failure alarm Flashing red
Rectifier alarms & Transmitted to SCU or ACU on the communication bus using the CAN protocol
Status Settings The SCU or ACU controller establishes all rectifier settings
Miscellaneous data Each rectifier provides the controller a complete set of identification information about itself (product code,
serial number, alarm history, etc.)
Rectifier Physical Specifications
Mounting Plug-in installation
Dimensions (H x W x D) 132 x 85.3 x 287 mm, 5.20 x 3.36 x 11.3 inches
Weight 7.7 lbs. (3.5kg)
Fire Resistance All materials have flammability rating -UL 94 V0 or better
All electrical components meet the Needle Flame Test per IEC 695-2-2
Safety The rectifier is UL recognized (UL60950) for USA & Canada and is CE marked

Distribution Panel Specifications


Capacity
Initial panel 16,18 or 20 load positions, 6, 8 or 10 battery connections, 300 amp Battery shunt, optional LVD
Supplementary panel Same as initial panel
Protection devices
Circuit breaker Bullet Nose type with load clip
1 to 65 amp use single position load clip
70 to 150 amp use double position load clip with spacing restrictions, 200 to 250 amp use quad position load clip
Fuses Bullet Nose type with load clip
TPS type 1 to 65 amp use double load clip
TPS & TLS Type 70 to 100 amp use double load clip
SAN-O type 0.18 to 20 amp with 10 Position Fuse Block
Battery connections Protected using circuit breakers up to 200 amp
Hardwired using optional Battery Connection Kit
Dimensions (H x W x D) 7.0" (177.8mm) x 23.0" (584mm) x 14.5" (368mm)
Weight
Initial panel 27.5 lbs. (12.5kg) with LVD
24.3 lbs. (11.0kg) without LVD
Supplementary panel Same

Enterprise : 85
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System

Controller Specifications
Standard Control Unit (SCU)
Display LED status interface
Alarm output 8 programmable dry C contacts outputs
Alarm input 8 digital inputs
Control of rectifiers Digital CAN bus
System configuration 6 navigational keys
Battery management Low Voltage Disconnect, equalize (boost)
Temperature compensation battery charging, charge current limiting, battery discharge testing
Advanced Control Unit (ACU)
Display LCD display with six navigation buttons
Alarm output 8 programmable dry C contacts
SNMP & Web (HTML)
Alarm input 8 programmable inputs
Control of rectifiers Digital CAN bus
Management Battery Discharge Test Equalize (boost)
Charge Control Statistics
Low Voltage Disconnect (up to two LVDs) Energy savings algorithm
Temperature compensation battery charging
System configuration Embedded Web Browser (HTTP)
Communications ports RJ45 jack for Ethernet port (TCP/IP)
DB9 connector for RS-232
Remote access All essential functions and operational parameters through RS-232 modem and TCP/IP Ethernet with password security

Power Shelf Specifications


Capacity
Initial shelf 5 Rectifiers, Controller position, 300 amp
Supplementary Shelf 6 Rectifiers, 360 amp
Dimensions (H x W x D) 5.25" (133mm) x 23" (584mm) x 14.5" (368mm)
Weight Initial – 11.8 lbs. (5.35kg)
Supplementary – 11.25 lbs. (5.1kg)
AC connections Connections are made through 2 flexible conduits of 1". Each conduit can handle up to 3 individual
rectifier wiring sets. Wires are terminated to a terminal block on the side of the shelf.
Recommended AC 25 or 30 amp, 2-pole AC breaker per 208/240V feed
Service input

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
86 : Enterprise
PPB-SDCP-059 / 1206
NetSure™ 701NVBB DC Power for
Business-Critical Continuity
DC Power System

Key Features
New 3,200 watt constant power conversion units provide 55 to
• Modular Design — simple 67 amps (59 amps at 54.0VDC and 62 amps at 52.0VDC) with a cur-
to install and operate; allows rent limit of 67 amps. With six units per shelf, these rectifiers provide
incremental cost-effective
system growth
330 to 402 amps in three rack units (5.25-in.) of space.

• Single Point Adjustment — Description


no tools required to change
The modular NetSure™ 701NVBB power system with 3,200 watt power conversion units
settings and make adjustments;
(PCUs) provides up to 4,000 amps of power for -48 volt systems.
MCA controls up to 72 PCUs
The basic components of the power system include the meter-control alarm unit (MCA),
• Remote Access — options rectifier shelves which house the PCUs, and up to two modular distribution cabinets with
allow users to view, control and rear copper bus inter-bay power connections, allowing the system to be expanded to
interact with the system using either side of the main bay.
an Ethernet, modem, RS 232 or
LMS1000 interface The NetSure™ 701 power system contains a powerful, microprocessor-based meter-con-
trol alarm system capable of monitoring and controlling up to 72 PCUs. The MCA provides
• Plug’n’Play — add PCUs a 16-character alphanumeric display,
without changing the settings which can be activated at the touch of
a keypad.
and making adjustments; no
system interruption
Each rectifier shelf can accommodate
up to six plug’n’play PCUs, which are
• Front Accessible — allows for controlled by the MCA. Additional
easy installation, additions shelves can be added as load require-
and maintenance ments increase.

• High Density — compact design The NetSure™ 701 distribution cabinet


takes up less floor space; houses is modular by row and position. Four
six 3200 watt PCUs per rectifier distinct distribution cabinet sizes are
shelf (3RU), system can be available to accommodate from one to
four distribution panels. This allows the
configured with up to two bays
system to be configured in relay racks
of various heights for installation in low-
• Constant Power — delivers more profile sites or atop batteries or other
current at lower voltages to meet equipment to make more effective
load or recharge demand use of floor space. Several distribution
panels are available offering different
• Safety Compliance — Designed combinations of distribution positions,
to NEBS™ Level 3 compliance; UL low voltage disconnect and battery dis-
Listed to UL subject 1801 connect options.

NetSure™ 701NVBB

Enterprise : 87
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System

Application
The NetSure™ 701NVBB system is ideal for The system can also be expanded with
wireline and wireless applications such as additional bays that are not adjacent to
switch sites, co-location, huts and large each other via extended length communi-
vaults or enclosures. cations cables and inter-bay power cabling.
The distribution cabinet can be factory
AC Input mounted in a relay rack or shipped loose
Each rectifier shelf in the NetSure™ 701 for mounting in a customer supplied relay
power system allows for an AC input feed rack or cabinet rails.
to each power conversion unit. There are
conduit knockout openings on the rear and A wide variety of panels provide multiple
side of each shelf. Each conduit opening combinations of distribution positions, Top AC Wireway Input
allows for installation of the (3) circuits nec- low voltage disconnect and battery dis- (cover removed)
essary to power up the (3) PCUs on that connect. Distribution cabinets are front
side of the shelf. If space is a problem then accessible, modular in design and are
an AC wireway option is available that will initially configured in the factory. Circuit
allow for the connection of the AC cables breakers and/or fuse modules plug into
at the top of the bay. At the factory, cables the multi-position distribution panels to
are run from this connection point down provide for easy installation. Distribution
into the shelves and enclosed in a sheet device options include 1 to 250 amp plug-
metal cover. Once again conduit knockouts in circuit breakers, 3 to 100 amp TPS-style
are provided at that top of this cover. fuses in plug-in holders, 100 to 600 amp
GJ/218-style circuit breakers and 70 to 600
Distribution amp TPH-style fuses. These devices can
The NetSure™ 701 power system includes be configured for both load and battery
a modular distribution product line that disconnect. A GMT fuse module is also
can be designed with one to two distribu- available.
tion cabinets – sized to accommodate Bottom AC Wireway Input
from one to four distribution panels each. (cover removed)
Each panel is rated at 500 amps load. The
maximum load per distribution cabinet is
2000 amps. The two, three and four-row
distribution cabinets can be intercon-
nected via copper inter-bay bus bars for a
total system capacity of up to 4,000 amps
with two bays.

Modular Distribution Cabinets

88 : Enterprise
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System

The NetSure™ 701NVBB


power system’s extensive
MCA
monitoring capabilities,
easy configuration and Monitoring/Control
The MCA provides a single point of adjust- MCA provides local indicators and the ability
maintenance are all ment for such features as float voltage, to transmit various alarm conditions such as
test/equalize voltage, high voltage shut- PCU failure, high voltage shutdown and AC
backed by the resources down and current limit for all PCUs in the failure. Remote and local communication
entire power system. The rugged, tem- is available using an Ethernet connection
and quality reputation perature hardened LED display allows users (web browser (HTTP) or SNMP), modem or
to view specific alarm conditions, system RS-232 interface. In addition, the LORAIN®
of a nationwide service measurements and system settings. All Monitoring System, LMS1000, can be con-
measurements and adjustments can be per- figured into this system (refer to 586505500
organization. formed locally via the alphanumeric display documentation for specifications).
on the front of the MCA panel or remotely
via optional software and hardware. The

Battery Stand or Trays


The NetSure™ 701 power system can be and battery recharge current limit (refer to
configured with a NEBS™ Level 3 certified 588820000 documentation for specifica-
modular front access battery stand to tions). Rack-mount battery trays are also
provide an entire power plant in one bay. available with optional battery disconnect
Available options include manual battery circuit breakers.
disconnect/protection, low voltage battery
disconnect, battery current monitoring

-48VDC NetSure™ 701NVBB


with Battery Trays

Enterprise : 89
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System

Power Conversion Unit


The modular R48-3200 is a high frequency current. The PCUs are monitored and con-
constant power PCU designed with the latest trolled by the MCA. The PCUs allow the user
patented switch-mode technology using to appropriately size a power plant to meet
DSP (Digital Signaling Processor) function- specific applications.
ality. Use of DSP technology results in
fewer components and optimized operation. Rectifier Shelf
Plug’n’play technology allows for easy sys- The NetSure™ 701 power conversion units
tem configuration. System capacity can are housed in modular rectifier shelves
be increased by simply plugging an addi- each of which accommodates six PCUs.
tional PCU into an existing rectifier shelf or a The rectifier shelves are 23" (58.42cm)
newly added expansion shelf — no adjust- wide and 5.25" (13.33cm) high. System
ments or setup are required. The capacity can be easily expanded with addi-
Power Conversion Unit NetSure™ 701 power system can house up tional shelves. A maximum of six rectifier
1R483200 to 72 PCUs, which provide load power, bat- shelves can be installed in each bay. An indi-
tery float current and battery recharge vidual AC feed is provided for each rectifier
on each rectifier shelf.

NetSure™ 701NVBB General Specifications


System Characteristics
Nominal System Voltage -48VDC
Rated Output Capacity
System 4000 amps
Bay 2000 amps
PCU 3200W PCU (R48-3200)
Shelf 330 amps to 402 amps
Distribution Panel 500 amps
Framework Type Relay Rack (can be mounted in enclosures)
Mounting Width 23 Inches
Mounting Depth 18 Inches Single Bay
21 Inches Two Bays
Access Front, sides and rear for installation, front for operation and maintenance
Control Microprocessor (MCA)
Environmental
Operating Temperature -40°F to 104°F (-40°C to 40°C) continuous operation
Storage -40°F to 185°F (-40°C to 85°C)
Humidity 0% to 95% relative humidity, non-condensing
Ventilation Fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class A and EN55022 Class A, radiated and conducted
Safety Compliance UL Listed 1801, cUL, designed to NEBS™ Level 3

90 : Enterprise
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System

R48-3200 Rectifier Specifications


Electrical Specifications
AC Input
Nominal Voltage Single phase 208/240VAC
Operating Voltage Range 186VAC to 256VAC
Frequency 45 Hz to 65 Hz
Power Factor (PF) >0.98 from 50% to 100% load
Total Harmonic Distortion ≤5% from 50% to 100% load
Input Current Max 20 amp
Inrush Current Inrush current does not exceed 150% of the rated input steady state peak value.
Input Protection If the input voltage decreases or increases beyond a non-adjustable predetermined value, the rectifier circuitry
shuts down, disabling the output. The rectifier will recover automatically when the AC input is re-established
and exceeds 95VAC (low voltage restart point) or when it decreases to 285VAC (high voltage restart point).
Overcurrent is protected by an internal fuse.
Operating Efficiency 92% peak
90% minimum at full load
DC Output
Output Voltage Range -42.0VDC to -58.0VDC
Output Power Constant power limiting operation
3200W maximum from 176VAC to 290VAC
1600W @ 120VAC
600W @ 85VAC
Output Current 55 to 67 amps
Regulation Steady state output voltage remains within +/-0.25% for any combination of input voltage from 5% to 100% load
Voice Band Noise The voice-frequency noise generated by a rectifier does not exceed 32dBrnC output noise from 10% to 100% load
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 100 mv rms per Telcordia GR-947-CORE
Psophometric Noise Does not exceed 1 mv
10% to 100% load
Protection
Current Limiting The output current is limited to 67 amp
Over Current Internal fuse
High Voltage Shutdown If rectifier detects over voltage it will turn off. After 5 seconds it will restart; if it encounters an over voltage within 5
minutes it will turn off and remain off until reset.

Enterprise : 91
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System

R48-3200 Rectifier Specifications (continued)


Environmental
Temperature -40°F to 113°F (-40°C to 45°C) at full rated output
Altitude Up to 6562' (2000m) at full rated output
Ventilation Front to back with speed-controlled fan (field replaceable)
Audible Noise The rectifier does not produce sound levels above 53dB(A), measured 0.6m in front of the rectifier, at the
same horizontal line as the middle of the rectifier at 25°C
Status / Alarm Indicators and Monitoring
Visual Indicators Status Visual indicator color
Normal operation Green
Alarm Yellow
Rectifier failure alarm Red
Fan failure alarm Flashing red
Status Settings The MCA controller establishes all rectifier settings)
Rectifier Physical Specifications
Mounting Plug-in installation
Dimensions (H x W x D) 5.20 x 3.36 x 11.3 inches (132 x 85.3 x 287mm)
Weight 7.7 lbs. (3.5kg)
Safety Compliance UL recognized (UL60950) for USA & Canada, CE marked

Output power vs. Input voltage Output Power vs. Temperature Output voltage vs. Output current,
at Tamb <45°C at Uin>176VAC max. output power 3200W
85 176 290 45 5055 65
70
55A 67A
120 120 70
% of max output power

Output Voltage (V)


% of max output power

100 100 60
50
80 80
40
60 60 30
40 40 20
20 20 10
0
0 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0 50 100 150 200 250 300 350 -40 -20 0 20 40 60 80 100
Output Current (A)
Input Voltage (VAC) Temperature (C°)

Additional Information
For additional specification, engineering and installation information use specification
numbers 582126000 (power system) and 588705000 (power shelf for 3200W PCUs).

For ordering information, request SAG582126000, PD588705000.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
92 : Enterprise
PPB-MDCP-073 / 1206
LORAIN® VPS 246000 DC Power for
Business-Critical Continuity
DC Power System

Key Features
New 4,275 watt power conversion units provide 150 amps at
• Modular Design — simple to 28.5VDC and 180 amps at 23.8VDC each with a constant power
install and operate; allows users limiting feature. With four units per shelf, these rectifiers provide
to grow system in cost-effective
increments
600 to 720 amps in three rack units (5.25-in.) of space.

• Single Point Adjustment — no Description


tools required to make settings
The LORAIN® VPS with 130 amp or 150/180 amp 4,275 watt power conversion units (PCUs)
and adjustments; the MCA
is a modular power system providing up to 6,000 amps of power for +24 volt systems.
controls up to 72 PCUs
The basic components of the power system include the meter–control alarm unit (MCA),
• Remote Access — options allow rectifier shelves which house the PCUs and up to three modular distribution cabinets with
users to view, control and interact rear copper bus inter-bay power connections, allowing the system to be expanded to either
with all power systems in a side of the main bay.
network from a remote location
The LORAIN® VPS contains a powerful,
• Plug’n’Play — add PCUs without microprocessor-based meter–control alarm
adjustments and settings; no system, capable of monitoring and control-
system interruption ling up to 72 PCUs. The MCA provides a
16-character alphanumeric display, which
can be activated at the touch of a keypad.
• Front Accessible — allows for
easy installation, additions Each rectifier shelf can accommodate up to
and maintenance four plug’n’play PCUs, which are controlled
by the MCA. The shelves are modular, so
• High Density — compact design additional shelves can be added as load
takes up less floor space; houses requirements increase.
four 150/180 amp 4,275 watt
PCUs per rectifier shelf (3RU), The VPS distribution cabinet is modular by
system can be configured with up row and position. Four distinct distribution
to three bays cabinet sizes are available to accommodate
from one to four distribution panels. This
allows the system to be configured in relay
• Optional Temperature
racks of various heights for installation in
Compensation — provides low-profile sites or atop batteries or other
automatic adjustment of PCU equipment to make more effective use of
output voltage when battery floor space. Several distribution panels are
temperature increases or available offering different combinations of
decreases distribution positions, low voltage discon-
nect and battery disconnect options.
+24VDC 2,000 amp LORAIN® VPS with
• Safety Compliance — NEBS™ -48VDC Converters and
Level 3 certified; UL listed to LMS1000 Monitoring System
UL subject 1801

Enterprise : 93
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System

Application Distribution
The LORAIN® VPS includes a modular dis- A wide variety of panels provide multiple
The LORAIN® VPS is ideal for wireless tribution product line that can be designed combinations of distribution positions, low
applications such as cell sites, huts and with one to three distribution cabinets voltage disconnect and battery disconnect.
large CUE sites. – sized to accommodate from one to four Distribution cabinets are front accessible,
distribution panels each. Each panel is modular in design and are initially config-
rated at 500 amps load. The maximum ured in the factory. Circuit breakers and/or
load per distribution cabinet is 2000 amps. fuse modules plug into the multi-position
Additional Information The two, three and four-row distribution distribution panels to provide for easy
cabinets can be interconnected via copper installation. Distribution device options
For additional specification, engineer- inter-bay bus bars for a total system capac- include 1 to 250 amp plug-in circuit break-
ing and installation information, specify ity of up to 6,000 amps with three bays. ers, 3 to 100 amp TPS-style fuses,100 to
spec. numbers 581125000 (power 600 amp GJ/218-style circuit breakers
system), 588703800 (520 amp power The system can also be expanded with and 70 to 600 amp TPH-style fuses. These
shelf and 130 amp PCUs), 588704900 additional bays that are not adjacent to devices can be configured for both load
(600/720 amp shelf and 150/180 each other via extended length communi- and battery disconnect. A GMT fuse mod-
amp PCUs), 588248700 (40 amp con- cations cables and inter-bay power cabling. ule is also available.
verter frames and 10 amp modules), The distribution cabinet can be factory
588249400 (80 amp converter shelf mounted in a relay rack or shipped loose
and 10 amp modules). for mounting in a customer supplied relay
rack or cabinet rails.
For ordering information, request
SAG581125000, PD588703800,
PD588704900.

Modular Distribution Cabinets Copper Inter-bay Bus Bars


(shown with cover removed for detail)

94 : Enterprise
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System

Monitoring/Control
The MCA provides a single point of adjust-
ment for such features as float voltage,
test/equalize voltage,high voltage shut-
down and current limit for all PCUs in the MCA
entire power system. The rugged, tem-
perature hardened LED display allows users
to view specific alarm conditions, system via optional software and hardware. The available via an ethernet, modem, RS-232 or
measurements and system settings. All MCA provides local indicators and the ability RS-485 interface. In addition, the LMS1000
measurements and adjustments can be per- to transmit various alarm conditions such as monitoring product can be configured into
formed locally via the alphanumeric display PCU failure, high voltage shutdown and AC this system (refer to 586505000 documen-
on the front of the MCA panel or remotely failure. Remote and local communication is tation for specifications).

Battery Stand or Trays Rectifier Shelf


The LORAIN® VPS can be configured with a The power conversion units are housed
NEBS™ Level 3 certified modular front access in modular rectifier shelves each of which
battery stand to provide an entire power accommodates four PCUs. The rectifier
plant in one bay. Available options include shelves are 23" (58.42cm) wide by 10.5"
manual battery disconnect/protection, low (26.67cm) high for 130 amp PCUs or 5.25"
voltage battery disconnect, battery current (13.33cm) high for 150/180 amp 4,275
monitoring and battery recharge current watt PCUs. System capacity can be easily
limit (refer to 588810000 documentation expanded with additional shelves. AC con-
for specifications). Rack mount battery nection options are available to provide an
trays are also available with optional battery AC feed for each rectifier or for each pair of
disconnect circuit breakers. rectifiers. Twist-lock line cords can be pro-
vided for the individual PCU AC feed option
(130 amp PCUs only).

DC to DC Converters
A modular DC to DC converter system
provides up to 320 amps at -48VDC via
high frequency switch mode converters
rated at 10 amps each. A unique frame
design mounts into a slot in the rectifier
+24VDC 1,040 amp
VPS with Battery Stand shelf and can accommodate four converter
modules. Four of these frames can be con-
figured in a system. The system can also
accommodate two rack-mount shelves,
each of which houses eight 10 amp mod-
ules. Distribution devices for the -48 volt
output are located in the main distribution
cabinet and are available in various quanti-
ties (refer to 588248700 documentation
Converter Frame -48V, 40 amp for specifications).

Enterprise : 95
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System

Power Conversion Unit


The modular, high frequency, switch-mode
PCU is the foundation of the VPS platform.
Plug’n’play technology allows for easy sys-
tem configuration. System capacity can
be increased by simply plugging an addi-
tional PCU into an existing rectifier shelf or
a newly added expansion shelf — no adjust-
ments or setup are required. The LORAIN®
VPS can house up to 72 PCUs, which pro-
150/180 amp, 4,275 watt, vide load power, battery float current and
+24 Power Conversion Unit
battery recharge current. The PCUs are moni-
tored and controlled by the MCA. The PCUs
130 amp, +24 Power Conversion Unit allow the user to appropriately size a power
plant to meet specific applications.

150/180 amp, 4,275 watt Power Conversion Unit Specifications


Input
Voltage Nominal 208/240 volts AC, single phase, 50/60 Hz, with a range of 176 to 264 volts.
Extended range to 300 volt AC without damage.
Current 23.0 amps@208VAC, 19.8 amps@240VAC, 27.24VDC, 4275 watts output
28.8 amps@176VAC, 4275 watts output (worst case)
Inrush Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage
within the rated input voltage range
Frequency 47-65 Hz
Protection Each PCU is individually wired; connections for individual AC input branch circuits are provided.
If the AC input voltage decreases or increases beyond a non-adjustable predetermined value, the PCU
power conversion circuitry inhibits, disabling PCU output. The PCU will recover automatically when the AC
input voltage is re-established within specifications limits.
Power Factor Typical power factor greater than or equal to 98% for any load greater than or equal to 50%
of rated full load at nominal line. Meets IEC 1000–3–2.
Operating Efficiency Typical operating efficiency 90% at full load
Output
Voltage Nominal +24 volts DC, positive ground, adjustable from +23.0 to +29.0VDC
Current 150 to 180 amps per PCU, up to a total of 600 to 720 amps per shelf with four PCUs installed.
Power 4,275 watts maximum. The PCU employs a constant power limiting feature which limits the maximum
output power to 4,275 watts over the output voltage range of +23.8 to +29.0 VDC.
Regulation Steady state output voltage remains within ±0.02% of any voltage within the range of +23.0 to +29.0 volts DC
for any combination of input voltage, input frequency and load from no load to full load
Filtering On or off battery
Voice Band Noise Less than 32 dBrnC
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 30 mv rms
Psophometric Noise Does not exceed 1 mv

96 : Enterprise
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System

150/180 amp, 4,275 watt Power Conversion Unit Specifications (continued)


Protection
Current Limiting Maximum output current of each PCU can be set from 15 to 180 amps.
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down.
After approximately three seconds, the PCU automatically restarts.
Status/Alarm Indicators and Monitoring
Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are
displayed on the 16-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature -40°C to +50°C (-40°F to +122°F); -40°C to +65°C (-40°F to +149°F) derate linearly to
3,200 watts output at 65°C (149°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation of 10,000 feet (
3,048m) above sea level. For elevations between 3,000 feet (914m) and 10,000 feet (3,048m), derate the
maximum operating ambient temperature linearly.
Ventilation Fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class B and EN55022 Class B, radiated and conducted
Audible Noise 2 feet from any vertical surface; does not exceed 77dBA, 65dBA with low fan speed selected.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 5.10" (12.95cm) x 5.13" (13.02cm) x 14.5" (36.83cm)
Weight 17 lbs. (7.73 kg)
Safety Compliance UL recognized (UL 1950), CSA 22.2, No.950, CE

130 amp Power Conversion Unit Specifications


Input
Voltage Nominal 208/240 volts AC, single phase, 50/60 Hz, with a range of 176 to 264 volts. Extended range to
290 volt AC
Current 19.9 amps@208VAC, 17.1 amps@240VAC, 27.24VDC, 130 amps output
24.8 amps@176VAC, 28.5VDC, 136 amps output (worst case)
Inrush Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage
within the rated input voltage range
Frequency 45-70 Hz
Protection Each PCU is individually wired and connections for individual AC input branch circuits are provided. If the
AC input voltage decreases or increases beyond a non-adjustable predetermined value, the PCU power
conversion circuitry inhibits, disabling PCU output. The PCU will recover automatically when the AC input
voltage is re-established within specifications limits.
Power Factor Typical power factor greater than or equal to 98% for any load greater than or equal to 50% of rated full
load at nominal line. Meets IEC 1000–3–2.
Operating Efficiency Typical operating efficiency 89% at full load

Enterprise : 97
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System

130 amp Power Conversion Unit Specifications (continued)


Output
Voltage Nominal +24 volts DC, negative ground, adjustable from 23.0 to 28.5 volts DC
Current 130 amps per PCU, up to a total of 520 amps per shelf with four PCUs installed.
Regulation Steady state output voltage remains within ±0.02% of any voltage within the range of 23.0 to 28.5 volts DC
for an combination of input voltage, input frequency and load from no load to full load
Filtering On or off battery
Voice Band Noise Less than 32 dBrnC
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 25 mv rms
Psophometric Noise Does not exceed 1 mv
Protection
Current Limiting Maximum output current of each PCU can be set from 10% to 105% of full load current.
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately
three seconds, the PCU automatically restarts.
Status/Alarm Indicators and Monitoring
Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed on
the 16-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature -40°C to +50°C (-40°F to +122°F);-40°C to +65°C (-40°F to +149°F) at 110 amps output
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be derated by 10 °C (18 °F) at an elevation
of 10,000' (3,048m) above sea level. For elevations between 3,000' (914m) and 10,000' (3,048m),
derate the maximum operating ambient temperature linearly.
Ventilation Fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class A, with an option for FCC and CISPR22 Class B emission ratings.
Audible Noise 3' from any vertical surface does not exceed 65dBA; 55dBA with low fan speed selected.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 9.88" (25.08cm) x 5.13" (13.02cm) x 14.5" (36.83cm)
Weight 18 lbs. (8.16 kgs)
Safety Compliance UL recognized (UL 1950), CSA 22.2, No.950, CE

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
98 : Enterprise
PPB-MDCP-008 / 1206
LORAIN® VPS 486000 DC Power for
Business-Critical Continuity
DC Power System

Key Features
New 5,000 watt power conversion units provide 85 amps at
• Modular Design — simple to 58.0VDC and 105 amps at 48.0VDC each with a constant power
install and operate; allows users limiting feature. With four units per shelf, these rectifiers provide
to grow system in cost-effective
increments
340 to 420 amps in three rack units (5.25-in.) of space.

• Single Point Adjustment — Description


no tools required to make settings
The LORAIN® VPS with 65 amp or 85/105 amp 5,000 watt power conversion units (PCUs) is a
and adjustments; the MCA
modular power system providing up to 6,000 amps of power for -48 volt systems.
controls up to 72 PCUs
The basic components of the power system include the meter–control alarm unit (MCA),
• Remote Access — options allow rectifier shelves which house the PCUs and up to three modular distribution cabinets with
users to view, control and interact rear copper bus inter-bay power connections, allowing the system to be expanded to either
with all power systems in a side of the main bay.
network from a remote location
The LORAIN® VPS contains a powerful,
• Plug’n’Play — add PCUs without microprocessor-based meter–control alarm
adjustments and settings; no system, capable of monitoring and control-
system interruption ling up to 72 PCUs. The MCA provides a
16-character alphanumeric display, which
can be activated at the touch of a keypad.
• Front Accessible — allows for
easy installation, additions Each rectifier shelf can accommodate up to
and maintenance four plug’n’play PCUs, which are controlled
by the MCA. The shelves are modular, so
• High Density — compact design additional shelves can be added as load
takes up less floor space; houses requirements increase.
four 85/105 amp 5,000 watt PCUs
per rectifier shelf (3RU), system The VPS distribution cabinet is modular by
can be configured with up to row and position. Four distinct distribution
three bays cabinet sizes are available to accommodate
from one to four distribution panels. This
allows the system to be configured in relay
• Optional Temperature
racks of various heights for installation in
Compensation — provides low-profile sites or atop batteries or other
automatic adjustment of PCU equipment to make more effective use of
output voltage when battery floor space. Several distribution panels are
temperature increases or available offering different combinations of
decreases distribution positions, low voltage discon-
nect and battery disconnect options.
• Safety Compliance — -48VDC 1,600 amp LORAIN® VPS with
+24VDC Converters and
NEBS™ Level 3 certified; LMS1000 Monitoring System
UL listed to UL subject 1801

Enterprise : 99
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System

Application Distribution
The LORAIN® VPS includes a modular dis- A wide variety of panels provide multiple
The LORAIN® VPS is ideal for wireline and tribution product line that can be designed combinations of distribution positions, low
wireless applications such as switch sites, with one to three distribution cabinets voltage disconnect and battery disconnect.
co-location, huts and large CUE sites. – sized to accommodate from one to four Distribution cabinets are front acces-
distribution panels each. Each panel is sible, modular in design and are initially
rated at 500 amps load. The maximum configured in the factory. Circuit breakers
Additional Information load per distribution cabinet is 2000 amps. and/or fuse modules plug into the multi-
The two, three and four-row distribution position distribution panels to provide
For additional specification, engineering cabinets can be interconnected via copper for easy installation. Distribution device
and installation information, specify spec. inter-bay bus bars for a total system capac- options include 1 to 250 amp plug-in circuit
numbers 582125000 (power system), ity of up to 6,000 amps with three bays. breakers, 3 to 100 amp TPS-style fuses,100
588703600 (260 amp power shelf and 65 to 600 amp GJ/218-style circuit breakers
amp PCUs), 588704800 (340/420 amp The system can also be expanded with and 70 to 600 amp TPH-style fuses. These
shelf and 85/105 amp PCUs), 588249600 additional bays that are not adjacent to devices can be configured for both load and
(80 amp converter frame and 20 amp mod- each other via extended length communi- battery disconnect. A GMT fuse module is
ules), 588249700 (160 amp converter shelf cations cables and inter-bay power cabling. also available.
and 20 amp modules), 588250100 (40 amp The distribution cabinet can be factory
converter frame and 20 amp modules). mounted in a relay rack or shipped loose
for mounting in a customer supplied relay
For ordering information, request rack or cabinet rails.
SAG582125000, PD588703600,
PD588704800.

Modular Distribution Cabinets Copper Inter-bay Bus Bars


(shown with cover removed for detail)

100 : Enterprise
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System

Monitoring/Control
The MCA provides a single point of adjust-
ment for such features as float voltage,
test/equalize voltage,high voltage shut-
down and current limit for all PCUs in the MCA
entire power system. The rugged, tem-
perature hardened LED display allows users via optional software and hardware. The RS-485 interface. In addition, the LMS1000
to view specific alarm conditions, system MCA provides local indicators and the ability monitoring product can be configured into
measurements and system settings. All to transmit various alarm conditions such as this system (refer to 586505000 documenta-
measurements and adjustments can be per- PCU failure, high voltage shutdown and AC tion for specifications).
formed locally via the alphanumeric display failure. Remote and local communication is
on the front of the MCA panel or remotely available via an Ethernet, modem, RS-232 or

Battery Stand or Trays


The LORAIN® VPS can be configured with
a NEBS™ Level 3 certified modular front
access battery stand to provide an entire
power plant in one bay. Available options
include manual battery disconnect/
protection, low voltage battery discon-
nect, battery current monitoring and
battery recharge current limit (refer to
588820000 documentation for specifica-
tions). Rack mount battery trays are also
available with optional battery disconnect
circuit breakers.

-48VDC 520 amp VPS -48VDC 500 amp VPS


with Battery Stand with Battery Trays

+24V, 80 amp Converter Frame


DC to DC Converters
A modular DC to DC converter system pro- can accommodate four converter modules eight 20 amp modules. Distribution devices
vides up to 320 amps at +24VDC via high (260 amp rectifier shelf) or two converter for the +24 volt output are located in the
frequency switch mode converters rated modules (340/420 amp rectifier shelf). The main distribution cabinet and are available
at 20 amps each. A unique frame design system can also accommodate up to two in various quantities.
mounts into a slot in the rectifier shelf and rack-mount shelves, each of which houses

Enterprise : 101
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System

Power Conversion Unit Rectifier Shelf


The modular, high frequency, switch-mode The power conversion units are housed
PCU is the foundation of the LORAIN® VPS in modular rectifier shelves each of which
platform. Plug’n’play technology allows for accommodates four PCUs. The rectifier
easy system configuration. System capacity shelves are 23" (58.42cm) wide by 10.5"
can be increased by simply plugging an addi- (26.67cm) high for 65 amp PCUs or 5.25"
tional PCU into an existing rectifier shelf or (13.33cm) high for 85/105 amp 5,000
a newly added expansion shelf — no adjust- watt PCUs. System capacity can be easily
65 amp, -48 Power Conversion Unit ments or setup are required. The LORAIN® expanded with additional shelves. AC con-
VPS can house up to 72 PCUs, which provide nection options are available to provide an
load power, battery float current and battery AC feed for each rectifier or for each pair of
recharge current. The PCUs are monitored rectifiers. Twist-lock line cords can be pro-
and controlled by the MCA. The PCUs allow vided for the individual PCU AC feed option
the user to appropriately size a power plant (65 amp PCUs only).
to meet specific applications.

85/105 amp, 5000 watt,


-48 Power Conversion Unit

85/105 amp, 5000 watt, Power Conversion Unit Specifications


Input
Voltage Nominal 208/240 volts AC, single phase, 50/60 Hz, with a range of 176 to 264 volts. Extended range to
300 volt AC without damage.
Current 26.9 amps@208VAC, 23.3 amps@240VAC, 54.48VDC, 5000 watts output
33.0 amps @176VAC, 5000 watts output (worst case)
Inrush Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage within the rated
input voltage range.
Frequency 47-65 Hz
Protection Each PCU is individually wired; connections for individual AC input branch circuits are provided. If the AC input
voltage decreases or increases beyond a non-adjustable predetermined value, the PCU power conversion
circuitry inhibits, disabling PCU output. The PCU will recover automatically when the AC input voltage is re-
established within specifications limits.
Power Factor Typical power factor greater than or equal to 98% for any load greater than or equal to 50% of rated full load at
nominal line. Meets IEC 1000–3–2.
Operating Efficiency Typical operating efficiency 91% at full load
Output
Voltage Nominal -48 volts DC, positive ground, adjustable from -44.0 to -58.0 volts DC
Current 85 to 105 amps per PCU, up to a total of 340 to 420 amps per shelf with four PCUs installed.
Power 5,000 watts maximum. The PCU employs a constant power limiting feature which limits the maximum output
power to 5,000 watts over the output voltage range of -47.6 to -58.0VDC.
Regulation Steady state output voltage remains within ±0.02% of any voltage within the range of 44.0 to 58.0 volts DC for
any combination of input voltage, input frequency and load from no load to full load
Filtering On or off battery
Voice Band Noise Less than 32 dBrnC
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 30 mv rms
Psophometric Noise Does not exceed 1 mv

102 : Enterprise
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System

85/105 amp, 5000 watt, Power Conversion Unit Specifications (continued)


Protection
Current Limiting Maximum output current of each PCU can be set from 8.5 to 105 amps.
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately three
seconds, the PCU automatically restarts.
Monitoring
Status/Alarm Indicators Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed on
the 16-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature -40°C to +50°C (-40°F to +122°F); -40°C to +65°C (-40°F to +149°F) derate linearly to 4,000 watts output
at 65°C (149°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation of 10,000 feet
(3,048m) above sea level. For elevations between 3,000 feet (914m) and 10,000 feet (3,048m), derate the
maximum operating ambient temperature linearly.
Ventilation Fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class B and EN55022 Class B, radiated and conducted
Audible Noise 2 feet from any vertical surface; does not exceed 77dBA, 65dBA with low fan speed selected.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 5.10" (12.95cm) x 5.13" (13.02cm) x 14.5" (36.83cm)
Weight 17 lbs. (7.73 kg)
Safety Compliance UL recognized (UL 1950), CSA 22.2, No.950, CE

65 amp Power Conversion Unit Specifications


Input
Voltage Nominal 208/240 volts AC, single phase, 50/60 Hz, with a range of 176 to 264 volts.
Extended range to 290 volt AC without damage.
Current 19.3 amps@208VAC, 16.6 amps@240VAC, 54.48VDC, 65 amps output
25.1 amps@176VAC, 57VDC, 69 amps output (worst case)
Inrush Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage
within the rated input voltage range
Frequency 45-70 Hz
Protection Each PCU is individually wired; connections for individual AC input branch circuits are provided.
If the AC input voltage decreases or increases beyond a non-adjustable predetermined value, the PCU
power conversion circuitry inhibits, disabling PCU output. The PCU will recover automatically when the AC
input voltage is re-established within specifications limits.
Power Factor Typical power factor greater than or equal to 98% for any load greater than or equal to 50%
of rated full load at nominal line. Meets IEC 1000–3–2.
Operating Efficiency Typical operating efficiency 89% at full load

Enterprise : 103
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System

65 amp Power Conversion Unit Specifications (continued)


Output
Voltage Nominal -48 volts DC, positive ground, adjustable from -44.0 to -57.0 volts DC
Current 65 amps per PCU, up to a total of 260 amps per shelf with four PCUs installed.
Regulation Steady state output voltage remains within ±0.02% of any voltage within the range of 44.0 to 57.0 volts DC
for any combination of input voltage, input frequency and load from no load to full load
Filtering On or off battery
Voice Band Noise Less than 32 dBrnC
Wide Band Noise Does not exceed 250 mv peak-to-peak,or 25 mv rms
Psophometric Noise Does not exceed 1 mv
Protection
Current Limiting Maximum output current of each PCU can be set from 10% to 105% of full load current.
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down.
After approximately three seconds, the PCU automatically restarts.
Monitoring
Status/Alarm Indicators Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are
displayed on the 16-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature -40°C to +50°C (-40°F to +122°F); -40°C to +65°C (-40°F to +149°F) at 55 amps output
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation
of 10,000 feet (3,048m) above sea level. For elevations between 3,000 feet (914m) and 10,000 feet
(3,048m), derate the maximum operating ambient temperature linearly.
Ventilation Fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class A, with an option for FCC and CISPR22 Class B emission ratings.
Audible Noise 3 feet from any vertical surface; does not exceed 65dBA, 55dBA with low fan speed selected.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 9.88" (25.08cm) x 5.13" (13.02cm) x 14.5" (36.83cm)
Weight 18 lbs. (8.16kgs)
Safety Compliance UL recognized (UL 1950), CSA 22.2, No.950, CE

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
104 : Enterprise
PPB-MDCP-003 / 1206
LORAIN® PS 4810000 DC Power for
Business-Critical Continuity
DC Power System

Key Features
Emerson Network Power’s next generation power platform
• NEBS™ Level 3 certified is now available with 208/240VAC rectifier, providing
integrated power, distribution, control and monitoring.
• Single frame design provides
power conversion, distribution,
control and monitoring in a
Description
small footprint
The LORAIN® Power System (LPS) utilizes a highly integrated revolutionary design to pack
• Patented, laminated internal bus unparalleled capacity and features into a small footprint.
work improves AC and DC cable
routing options The LPS is a -48VDC digital power plant that operates with 200 amp Power Conversion Units
(PCUs) powered from 480VAC or 208/240VAC. Each bay provides power conversion and dis-
• Modular distribution design tribution — up to ten PCUs (2000 amps total) along with 2400 amps of distribution. Adding
includes built-in automatic additional bays creates larger plants, up to 10,000 amps.
monitoring for all distribution
devices
Application
• Integrated Internal DC bus
eliminates costly overhead busses The LPS is ideal for use in central
and eases plant expansion office, switch site, MSO, and data
center applications. The LPS works
• Integrated LMS1000 design in both centralized and distributed
features a distributed I/O architecture plant layouts and is
architecture, an internet port and suitable for any -48VDC applica-
web page to simplify monitoring tion with 3-Phase commercial AC
of internal/external equipment service. The advanced monitoring
and control features allow the LPS
• Controller backplane accepts to fit into new office locations or
plug-in alarm cards and LMS simply be migrated into existing
I/O cards power plants. Due to the weight
distribution of the LPS, an entire
• Optional integrated AC Power DC power plant can be installed in
Distribution Service Cabinet a raised floor environment, subject
(PDSC) for protected bulk AC to floor loading limitations.
service feeds

• TCP/IP, SNMP, Ethernet, modem, LPS, -48VDC, 10,000A Modular Power Plant
and RS232 compatible

• Supports distributed and bulk


plant architectures

Enterprise : 105
PPB-CODCP-004 / 1206
LORAIN® PS 4810000
DC Power System

Power Conversion Unit


The heart of this system is the LPS200 class AC service is wired internally to each PCU.
PCUs. A true three-phase, four-wire recti- A horizontal terminal strip is located on
fier, the unit operates at 0.998 power factor the left top of the bay. An optional Power
with less than 5% THD. It can deliver 110% Distribution Service Cabinet (PDSC)
of rated current up to 40°C, and a reduced bolted to the left side of the bay facilitates
amount up to 80°C by virtue of its thermal bulk wiring in one or two AC branch circuit
current limit feature. Designed for positive applications per bay. Each LSP200 PCU is
Power Conversion Unit ground applications, the normal output equipped with individual alarm and status
voltage ranges from -47 to -58 volts, with a LEDs as well as a 10-segment output power
test voltage adjustable down to -45 volts. LED display.

Distribution
Distribution is divided into two rows,
top and bottom. Each row has a flexible
design that accommodates any combina-
tion of breakers and fuses, up to a 1200
amp maximum per row. There can be up
to 24 (1-100A) breakers/fuses or up to 12
(100-800A) devices, or any combination.
Each distribution device used in the LPS
is designed for complete plug-n-play and
automatic registration with the system con-
troller. This patented unique design allows
total flexibility to configure each frame
per required device without costly kits and
restrictive panels.

Distribution Cabinet

Monitoring
All distribution elements of 100 amps and an LMS CPU for modem and Ethernet
greater include a monitoring shunt, iden- access, plus LMS I/O cards for other
tification to the controller, and integrated monitoring points. As a system, the MCA
alarming to the plant controller. The MCA controls the steady state output voltage to
consists of a multi-line vacuum fluorescent within 0.05% of any setting, from no load
display, plus a removable CPU and alarm to full load. The MCA also uses a patented
cards located in a shelf below the distribu- algorithm to balance the PCU output cur-
tion. The shelf is dual-purpose and accepts rents to within 1% of their rated current.
MCA

106 : Enterprise
PPB-CODCP-004 / 1206
LORAIN® PS 4810000
DC Power System

System Specifications
Operating Ambient 0°C to +40°C (+32°F to +104°F)
Temperature Range
Storage Ambient -40°C to +85°C (-40°F to +149°F)
Temperature Range
Output Capacity 10,000A per System, 2000A per bay (Rectifiers), 2400A per bay (Distribution)
Primary/Secondary 24"W x 30"D x 84"H
Frame Dimensions
Frame Weight 830 lbs. Per Frame (less PCUs)
PDSC Dimensions 10"W x 30"D x 84"H
PDSC Weight 190 lbs.
Safety UL Listed (UL1801), CSA 22.2 (No. 225), c UL, NEBS™ Level 3

Power Conversion Unit Specifications


Input
Voltage 408VAC - 528VAC (480VAC nominal line) or 176VAC - 264VAC (208/240VAC nominal line)
Current 17.6A @ 480VAC nominal line, 35A @ 208VAC nominal line
Inrush Not to exceed 6 time RMS input current at full load
Frequency 47-63 Hz.
Protection Fused (internally)
Power Factor >0.97 at nominal line, full load
Harmonic Content <5% THD
Operating Efficiency 92% at >50% load (nominal input voltage)
Output
Voltage 42VDC – 60VDC
Current 2000A per bay (Power Conversion)
2400A per bay (Distribution)
6000A Inter-bay Bus
10,000A per System / 10 frames max
Regulation + 0.05% at output terminals
Altitude 0-10,000 feet (derated from 3000-10,000 feet)

Enterprise : 107
PPB-CODCP-004 / 1206
LORAIN® PS 4810000
DC Power System

Power Conversion Unit Specifications (continued)


Ventilation Forced air, front-to-back
EMI/RFI Suppression Compliant to FCC Part 15, Subpart B, Class A
Audible Noise 65 dBA (full load operation)
Protection
Current limiting 110% (Digitally controlled)
Status/Alarm Indicators and Monitoring
Bays LEDs (Green, Amber, Red)
PCU 10-segment LED output display (current), multi-function LEDs
Physical Characteristics
Mounting Frame mounted, 2 set screw secured, safety catch release
PCU Dimensions 3.5"H x 22"W x 20"D
PCU Weight 42 lbs. (17.7 kg.)
Safety Compliance UL Recognized (1950), CSA 22.2 (cUL)

Additional Information
For additional specification, engineering installation information, specify 582140000 (power system),
486532600 (200 amp PCUs 480VAC) or 486534000 (200 amp PCUs 208/240VAC).

For ordering information, request SAG582140000.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
108 : Enterprise
PPB-CODCP-004 / 1206
LORAIN® LVS 4810000 DC Power for
Business-Critical Continuity
DC Power System

Key Features
Description
 ingle point adjustment — no
•S
tools required to make settings Built on the heritage of the LORAIN® brand name, the Large Vortex® power platform, with 200
and adjustments amp power conversion units (PCUs) is a modular power system providing up to 10,000 amps of
power for -48 volt systems. The components of a Vortex® power system include the power bay,
• LMS1000 Remote Monitoring — the meter–control–alarm microprocessor (MCA), LMS1000 Remote Monitoring, the PCUs and
options allow users to view, modular distribution.
control and interact with all
power systems in a network
Each power bay can accommodate up to seven PCUs and is capable of controlling the PCUs
from a remote location via
through the powerful microprocessor based MCA.
TCP/IP, Modem, SNMP or Web

• Plug’n’play — add PCUs without The front of the MCA panel provides a 16-character alpha-numeric display which can be acti-
adjustments and settings; no vated at the touch of a keypad.
system shutdown
The Vortex® distribution is modular, expandable and offers a variety of fuse/circuit breaker
• Front accessible — easy distribution modules up to 600 amps. The system is designed to provide DC power to loads
installation, additions and of up to 5,000 amps per bay. The Vortex® distribution main bay features a total system
maintenance solution by providing a flexible, modul ar hardware design, along with a variety of monitor-
ing and control options.
• NEBS™ Level 3 compliant — power
bay (UL1950), distribution The LMS1000 is included in the main distribution frame, providing unparalleled monitoring
(UL1801) and remote access capability. All branch loads are now factory connected to the LMS1000
chassis, ensuring rapid installation and ultimate user control over the power plant.
• Distribution — distribution bays
are available in 5000A capacities
per bay
Application
• Modular design — simple to
The Vortex® power system, pow-
install and operate; allows users
ered with 200 amp PCUs, is ideal
to grow system in cost-effective
for applications such as switch
increments
sites and large customer prem-
ise installations requiring up to
• High density — compact design
10,000 amps.
takes up less floor space; power
bay houses seven PCUs in a 18" x
24" (45.72cm x 60.96cm) footprint

• Optional temperature
compensation — provides
automatic adjustment of PCU
output voltage when battery LORAIN® LVS 4810000
temperature increases or
decreases

• AC input protection — single or


dual feed circuit breakers with
up to 65KA interrupt capacity,
eliminating local PDSC’s within the
office

Enterprise : 109
PPB-CODCP-023 / 0107
LORAIN® LVS 4810000
DC Power System

MCA Module
The MCA module can be housed in the
power bay or the main distribution bay. The
MCA provides a single point of adjustment
MCA Module for such features as float voltage, test/
equalize voltage, high voltage shutdown
and current limit adjustments for all PCUs
in the entire power system. The MCA allows
users to view specific alarm conditions, sys-
tem measurements and system settings. All
adjustments can be performed locally via
the alpha-numeric display panel or remote-
ly via optional software and hardware.
The MCA provides local indicators and the Distribution Unit
ability to transmit various alarm conditions
such as PCU failure, high voltage shutdown
and AC failure. Distribution
• Modular Design — wide variety of
distribution modules allows for maximum
Power Bay configuration flexibility
The modular, high frequency, switch-mode
• High Capacity — offers up to 5,000 amp
Vortex® PCUs are the foundation of the
capacity per bay
Vortex® platform. Plug’n’play technology
allows for easy system configuration. System • Complete System Control — full range
capacity can be increased by simply plugging of monitoring and control
an additional PCU into an existing mounting options available
space in the power bay — no adjustments or
PCU • System Interbay Bus — modular external
setup are required. The PCUs allow the user to
bus systems designed for incremental
appropriately size a power plant (200 - 10,000
growth and minimal installation time
amps) to provide load power, battery float
current and battery recharge current. An • Fuse Protection — utilizing TPL, TPJ, TPS
optional AC input feature provides a prewired and TPA type fuses protecting circuits up
input to a terminal block at the top of each to 800 amps
cabinet and each rectifier is terminated with
a circuit breaker. This design eliminates the The Vortex® distribution is a fully integrated
cost of secondary AC distribution panels and modular solution that enables you to begin
saves installation costs. The power bay is 24" with the capacity you need today, and
(60.96cm) wide x 84" (213.36cm) high x 18" incrementally expand to meet future capac-
(45.72cm) deep. ity requirements. The main bay can house
up to six distribution modules, with eight
modules for each supplemental bay. The
vertical design results in ease of installation
and cable flow with plant shunt, ground
and battery termination bars internal or
external to the bay. This results in further
reduction in cable congestion, while facili-
tating expansion. The physical dimensions
are 7' (213.36cm) high x 31.38" (79.69cm)
wide x 24" (60.96 cm) deep.

110 : Enterprise
PPB-CODCP-023 / 0107
LORAIN® LVS 4810000
DC Power System

Power Conversion Unit Specifications


Input
Voltage Nominal 208/240VAC, three phase, 50/60 Hz, with a range of 176 to 264 volts.
Nominal 480VAC, three-phase, 50/60Hz, with a range of 408 to 530 volts.
Inrush Current Peak does not exceed 4 times the RMS input at full load, under any conditions of input voltage within the rated input
voltage range.
Frequency 47-63 Hz
Protection Each PCU is individually wired and connections for individual AC input branch circuits are provided. If the AC
input voltage decreases or increases beyond a non adjustable predetermined value, the PCU power conversion
circuitry inhibits, disabling PCU output. The PCU will recover automatically when the AC input voltage is
re-established within specifications limits.
Power Factor Greater than or equal to 94% for any load greater than or equal to 50% of rated full load at nominal line.
Typical Operating Efficiency 90%
Output
Voltage Nominal -48VDC, positive ground.
Current 200 amps per PCU, up to a total of 1,400 amps per power bay with seven PCUs installed.
Regulation Steady state output voltage remains within ±0.5% of any voltage within the range of 45.0 to 58.0VDC.
Filtering On or off battery
Voice Band Noise Less than 22 dBrnC
Wide Band Noise Does not exceed 200 mv peak-to-peak, or 30 mv rms
Psophometric Noise Does not exceed 1 mv
Protection
Current Limiting Output current of each PCU is automatically limited to approx. 110% of full load current.
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down.
After approximately four seconds, the PCU automatically restarts.
DC Output Breakers Connects or disconnects PCU output power to/from the PCUs output terminals.
Metering
Status/Alarm Indicators Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed
on the 16–character numerical display of the MCA module and on the PCUs within the cabinet.
Environmental
Operating Temperature 0° C to +50° C (+32° F to +122° F)
Storage Temperature -40° C to +85° C (-40° F to +185° F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be de-rated by +10°C (+50°F) at an elevation of 10,000'
(3,048m) above sea level. For elevations between 3,000' (914m) and 10,000' (1,048m), de-rate the maximum
operating ambient temperature linearly.
Ventilation Fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class A.
Audible Noise 3' (.91m) from any vertical surface does not exceed 65dBA.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 8.62" (21.89cm) x 23.37" (59.36cm) x 16.76" (42.57cm)
Weight 80 lbs. (36.29 kgs)
Safety Compliance 582121100, 582121300, 582121700 UL Listed (USA), CUL (Canada) to UL 1950, 582122100UL and CE

Enterprise : 111
PPB-CODCP-023 / 0107
LORAIN® LVS 4810000
DC Power System

LVPS Options
Option Function
LMS1000 Remote monitoring and communication system
VLI Vortex®-to-Legacy Interface
Vortex® MCA Microprocessor based meter, control and alarm (if not provided in power bay)
Vortex® Win Link Software and modem for remote Vortex® power system access
Pre-charge Unit For use with TPS, TPJ and TPL type fuse modules and GJ breakers
OH Bus System -48V battery and return bus bar kits, 10,000 amp rated
OH Bus Covers Provides clear, non-conductive bus safety covers for 10,000 amp bus
AC Courtesy Panel 120VAC, 20A ground fault protected receptacle outlet panel

Distribution Modules
Quantity Type Description
5 GJ 125-250 amp circuit breakers with shunts
4 GJ 250-400 amp circuit breakers with shunts
3 GJ 600 amp circuit breakers with shunts
3 TPL 61-600 amp fuseholders
6 TPJ 60-150 amp fuseholders
12 TPS 0-70 amp fuseholders
16 TPA 0-50 amp fuseholders
16 AM1 0-100 amp circuit breakers
1 TPL 1,000 - 1,200 amp fuse holder
2 GJ 800 amp circuit breakers
1 BD 1,200 amp battery disconnect

Additional Information
For additional specification, engineering and installation information, specify spec. number 582121901 (distribution bay),
582121100 (208/240VAC) or 582121300 (480VAC) (power bays).

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
112 : Enterprise
PPB-CODCP-023 / 0107
NterpriseIP™ Solution DC Power for
Business-Critical Continuity
Adaptive, High Availability
Power System for IP Telephony

Key Features
Deploy, Integrate, and Expand VoIP and PoE Applications
• Scalable with built in redundancy More Quickly, Reliably and Cost Effectively than Ever Before
• Two battery trays offer a wide
Description
selection of back-up times
Eliminates the infrastructure issues
The need for a reliable power infrastruc- associated with IP technology
• Extensive monitoring ture has never been more important, and deployment
- Web based interface IT professionals are discovering that DC • Inability to deliver high availability
- Programmable relay contacts Power is the key. These experts are recog- • Footprint constraints in wiring closets
- SNMP interface nizing the benefits a DC UPS can provide, • Lack of monitoring, management
- Local and remote control especially for applications requiring Power and control capabilities
over Ethernet (PoE). But modernizing the • Inability to support future PoE devices
• Pre-wired in factory for maximum infrastructure’s technology has proven to
• Unanticipated equipment
be a challenge in designing high-availabil-
DC system capacity powering issues
ity, cost-efficient data networks that are as
reliable as legacy voice networks.
• Single AC input interface and
TVSS for extra protection Now imagine an integrated DC UPS solu-
tion that offers “Six Nines” (99.9999%) reliability. One that delivers powerful performance
• Integrated grounding for all and efficient thermal management to protect your investment. A complete DC UPS
system components solution that will support all of your current and next generation requirements, while sig-
nificantly reducing costs.
• Rack space for your equipment
At Emerson Network Power, we’ve long realized that DC isn’t just for telecom applications
• Easy to configure and install anymore. We’ve taken the proven, adaptive architecture of DC Power and engineered an
innovative, new, plug-and-play, custom solution. With it, enterprises can deploy, integrate,
or expand Voice over IP (VoIP) and/or PoE applications more quickly, reliably and cost effec-
tively than ever before.
Options

• 1-2 kVA AC UPS (online) for AC


High Performance Power from a “DC UPS” Solution
powered network equipment

• Battery management and failure


Applications
prediction monitor
• Enterprise networks/converged networks –data ,voice, PoE
• Layer 2-4 switches, Sonet, Multiservice Platform switches
• Extended battery back-up time
• IP PBX’s, and hybrid PBX’s for larger Enterprises
• Internal distribution cables for • High density server clusters
specific configurations
• Any other Enterprise switching and network devices (clusters of devices)
which can accept –48VDC

Enterprise : 113
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony

1
6

7
2

8
3 9

5
10

NterpriseIP™ Front View NterpriseIP™ Rear View

1 DC Power System 4 Open Rack Space 8 Optional MPM-100 Battery Monitoring


2 Switch can be shipped integrated with 5 Batteries with customized back-up time 9 Optional Maintenance Bypass for AC UPS
the solution or be installed on site
6 Ground and Alarm Interface Panel 10 Foundation Cabinet
3 Optional AC UPS 7 AC Panel with TVSS

114 : Enterprise
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony

Emerson is proud to announce the first DC NterpriseIP™’s flexible configurations, driv- • DC power distribution cabling
UPS solution on the market, NterpriseIP™. en by your specific business requirements,
• Space for your equipment
are created for easy plug-and-play installa-
NterpriseIP™ is specifically engineered to tion with a minimal footprint. • Provisions for communications
address the special challenges of deploying cable management
• Electronic Industries Alliance (EIA)
equipment in Telco closets and other tight
compliant cabinet factory pre-wired • Heavy-duty casters for easy
spaces. It will soon carve its own special
for maximum output DC power maneuverability
niche within growing data network infra-
structures where performance expectations • Multiple battery strings
are continually rising and budgets • Integrated AC input panel with TVSS
are decreasing. protection

Deploying DC Power Has Never Been Easier


NterpriseIP™ Solutions are available in Scalability
three different DC power output capacities The NterpriseIP™ architecture includes hot
— 4500W, 6000W and 15000W. All three swapability for plug-in components such
systems feature scalable output power and as rectifier modules. This minimizes your
battery back-up. The cabinet’s architecture initial investment by allowing progressive
is easy to configure, deploy and expand. power growth with increasing application
Therefore, costly sizing errors will never be demands.
an issue.
Overload Capability
Simple Installation Designed to operate even with temporary
The NterpriseIP™ ships completely engi- PoE oversubscription (dependent upon bat-
neered to you from our factory floor tery capacity), NterpriseIP™ allows user
already pre-wired for the maximum amount ample time to correct abnormal operation. Maintenance
of power. Easy to configure, just add your
equipment, and connect the AC source. As High Efficiency Solution In multi-site deployments, the consis-
an option, we can integrate and custom- A DC UPS is highly efficient. Therefore it tent design and implementation of the
ize according to your specific application contributes minimally to the overall heat NterpriseIP™ solution provides for a mini-
requirements prior to shipment. load of your network. This efficiency trans- mum of spare parts. The NterpriseIP™’s
lates not only into reduced electricity costs extensive monitoring capabilities, easy con-
Redundant, Fault Tolerant Architecture to operate your power system, but lower figuration, and maintenance, are all backed
Well known for high performance and cooling costs as well. by the resources and quality reputation
dependability, the redundant DC architec- of a nationwide service organization.
ture allows for Six Nines availability. Integrated Cabinet Design
It exceeds current data industry expecta- Developed by engineers with application
tions to provide high performance power expertise, the NterpriseIP™ features a
delivery! Its fault tolerant architecture pro- quality, consistent, plug-and-play design.
vides prolonged, continuous operation in Properly sized and scalable to add compo-
the unlikely event of multiple failures. The nents for the next-generation, this
architecture’s easy accessibility offers plen- integrated solution is ideal for the footprint
ty of time to diagnose and correct issues. constraints in your wiring closets.
In addition, replacing major components
takes just 30 seconds.

Enterprise : 115
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony

System Specifications (NterpriseIP™– standard configurations)

Electrical Parameters Batteries


AC input • Telecommunication grade
Nominal Voltage VRLA technology
Without integral UPS 110/120V or 208/240V, 3 wire
• 10 year design life 25C(77F)
With integral UPS 120/208V, 4 wire (2 phases, neutral and ground)
Operating Voltage range 85VAC to 300VAC • Front terminal construction
Frequency 47 Hz to 63 Hz • Front replaceable
Power factor >.97 (50% load), >.99 (80% to 100% load)
• Flame-retardant reinforced
Harmonic distortion <5% (70% to 100% load) -meets IEC 1000-3-2 container and cover compliant
Input Current Refer to Input AC feeder sizing Table with UL 94 V-0
Surge immunity ANSI C62.41/IEEE Std. 587
Protection Built in TVSS
DC output
Output voltage ratings Cabinet (enclosure)
Nominal –48VDC
• 19" mounting space (per EIA)
Normal operation –54VDC
On battery –42VDC min
for your equiment
Range –42VDC to -58.5VDC (factory set at 42-56V) • Totally enclosed
Regulation +/_ 0.5% for all load and input voltage variations
• Front and rear lockable doors
• Wire channels for Ethernet cables
• Perforated sides for ventilation
Operating and Environmental Parameters
• Casters
Efficiency 90 - 91% from 40-100% load (at 240V)
91.5% max • Internal temperature monitoring
Operating temperature System -40C to +50C
Rectifiers - 40C (-40F) to +75 C (167F) at full rated output
Humidity 0 to 95% non condensing
Storage temperature -40˚C to +75˚C
Monitoring
Local - LCD display with four
Audible noise Less than 60 dBA when measured 0.5m from the
equipment and 1.5m above the floor navigation buttons

Ventilation Speed controlled fans – front to back air flow Remote


EMC/EMI (DC UPS) FCC part 15, subpart B and Telcordia •8 dry C contacts
GR-1089_CORE & emissions for Class B, EN 300386 (5 are programmable)
Operation without batteries Yes • Web (HTML) – embedded
Battery temp comp charging Yes web browser (HTTP)
Battery Low Voltage Disconnect Yes (protects batteries from deep discharges) • SNMP

Communication Ports
• RJ45 jack for Ethernet port
• DB9 connector for RS-232

116 : Enterprise
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony

Agencies Options
• NterpriseIP System - UL 60950 listed • 1-2kVA UPS with maintenance
bypass
• DC UPS - NEBS™ level 3 certified,
meets FCC class B • Battery diagnostic and failure
prediction monitor
• All materials have a flammability
rating of UL94V0 or better • User specific output cables
• Multiple AC input interfaces

Typical Battery Back-Up


3trays 4 trays 3 trays 4 trays 3 trays 4 trays
1 tray 2 trays 105Ah 105Ah 1 tray 2 trays 125Ah 125Ah 1 tray 2 trays 155Ah 155Ah
Load 105Ah 105Ah Batt1 Batt1 125Ah 125Ah Batt2 Batt2 155Ah 155Ah Batt3 Batt3
W Batt1 Batt1 Note1 Note1 Batt2 Batt2 Note1 Note1 Batt3 Batt3 Note1 Note1
Min Min Min Min Min Min Min Min Min Min Min Min
500 570 1320 1620 >1800 700 1600 >1800 >1800 840 1800 >1800 >1800
1000 250 570 1080 1320 330 700 1200 1500 420 840 1440 1800
1500 150 360 570 840 200 480 700 1080 240 600 840 1320
2000 105 250 420 570 140 330 550 700 180 420 680 840
3000 65 150 250 360 90 200 330 480 105 240 420 600
4000 45 105 180 250 60 140 240 330 75 180 300 420
4500 40 80 150 235 50 130 210 300 70 150 270 360
5000 33 85 140 200 45 100 180 270 55 135 220 330
6000 25 65 105 150 35 90 140 200 40 105 180 240
7000 20 55 90 125 29 75 125 180 32 90 150 210
8000 16 45 80 105 22 60 110 140 29 75 125 180
9000 14 39 65 95 16 50 90 130 27 65 105 160
10000 12 33 58 88 14 45 70 120 26 55 85 135

Notes:
1. Requires additional cabinet
2. Contact your representative for longer back-up times

Enterprise : 117
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony

Dimensions and Weights


Space for Max weight
Height Width Depth OEM Weight w/o with
NterpriseIP™ in/cm in/cm in/cm equipment batteries batteries
4500 79.7 29.2 44.9 25U 700 lbs 1650 lbs
6000 79.7 29.2 44.9 20U 750 lbs 1700 lbs
15000 79.7 29.2 44.9 16U 850 lbs 1750 lbs

Input AC Feeder Sizing


Number Initial Rating Max Rating
NterpriseIP™ Size of Rectifiers Redundant Watts Redundant Watts Single Feed 208v
4500 2 1500 4500 20A
6000 3 3000 6000 30A
15000 4 4500 15000 40A
6000 5 6000 6000 50A
15000 15000
15000 6 7500 15000 60A
7 9000 15000 70A
8 10500 15000 80A
9 12000 15000 90A
10 13500 15000 100A
11 15000 15000 120A

Notes:
1. Contact your representative for 120V feeders sizes and multiple AC input option
2. Contact your representative for input sizing when UPS option is selected

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
118 : Enterprise
PPB-UPS-060 / 1206
LORAIN® DB 48500 DC Power for
Business-Critical Continuity
Battery Distribution
Fuse/Circuit Breaker Bay

Key Features
Description
• Modular design — initial and field
installed Battery Distribution Fuse The LORAIN® DB 48500 Battery Distribution Fuse/Circuit Breaker Bay (BDF/CBB) features
and Circuit Breaker Panels (BDF/ high capacity and modularity. These features provide effective secondary load distribu-
tion and protection for multiple -48 VDC feeds up to 800 amps.
CBB Panels)
The LORAIN® DB 48500 system consists of a Digital Meter Panel and up to 13 BDF/CBB
• Mini applications — one BDF/ panels with a maximum of 5 BDF/CBB panels per frame.
CBB panel provides two (2) 500
amp buses for a total 1000 amp The BDF/CBB Panels mount on standard 23-inch frames and each panel is split into two
continuous rating with 16 fuse or sides of load distribution with each side providing 8 distributions for a total of 16 posi-
circuit breaker positions tions per panel. Each side has a capacity of 500 amp for a total of 1000 amp per panel.
Each side of the panel can have an individual power feed, or the left and right sides of the
• High capacity — offers up to ten panel mounted above / below each other can be paralleled for a single input feed of 800
buses with 5,000 amps continuous amp per paralleled side. Each side of the BDF/CBB panels can be parallel for single input
rating per frame, with maximum of 16 positions for 500 amps. Each panel can be equipped with two optional 10-position
GMT fuse blocks for additional distribution.
loading up to 80 fuse or circuit
breaker positions

• Fuse protection — plug-in Application


fuseholders with TPS / TLS fuses
ranging from 1-100 amps and For mini applications the LORAIN®
GMT-A fuses from .18 to 15 amp DB 48500 can be configured with
one BDF/CBB Panel and a Digital
Meter Panel that provides A & B input
• Circuit breaker protection —
feeds and 16 fuse or circuit breaker
bullet nose plug-in breakers from
loads with a total 1000 amp capac-
1-150 amps ity. Multiple BDF/CBB Panels, up to 5
modules on a frame, provide up to 10
• Digital Meter Panel — features input buses 5,000 amp continuous
2 line display, 6 programmable rating with a total 80 fuse or circuit
external alarm relays, audible breaker loads.
alarm and cutoff, and overcurrent
threshold alarms
Additional Information
• Optional LVD function — provides
load-shedding capability For additional specification, engi-
neering and installation information
• NEBS level 3 compliance — meets request document SAG582135200.
or exceeds all relevant GR1089,
GR63 and UL specifications

Enterprise : 119
PDS-PDB-071 / 0107
LORAIN® DB 48500
Battery Distribution Fuse/Circuit Breaker Bay

Options
Option Description
Top or Bottom Feed Top or bottom input power feeds
Internal Ground Internal return / ground bus
Parallel Buses Interpanel parallel feed and ground buses
GMT Fuse Modules Two 10-position GMT fuse blocks per panel (one A and one B)
LVD Function Disconnects each side of BDF/CCB panel with self-latching contactor under control of Meter Panel

BDF / CBB Panel


Specifications
Fuses
Bullet nose-type fuseholder
TPS / TLS fuses 1 –100 amp
GMT fuse module
GMT-A fuses .18 to 15 amp
Circuit Breakers
Bullet nose-type circuit breakers 1 to 150 amp

Monitoring
Specifications
Digital Meter Panel
2 line display with 3 navigation buttons
Visual alarms
Audible alarm and alarm cutoff
6 programmable relays for external alarms
Current threshold alarms
Programmable LVD control

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
120 : Enterprise
PDS-PDB-071 / 0107
LORAIN® DB 484800 DC Power for
Business-Critical Continuity
Battery Distribution
Fuse/Circuit Breaker Bay

Key Features
Description
• 360° access — front access
provides back-to-back or wall The LORAIN® DB 484800 Battery Distribution Fuse/Circuit Breaker Bay (BDF/CBB) fea-
installation, as well as side and tures high capacity, front access, modularity, and simplified installation. These features
provide effective secondary load distribution and protection for multiple -48 VDC feeds
rear access for conventional
up to 600 amps. The base offering is a vertical arrangement of modular distribution
applications
providing 360° access for ease of installation, maintenance and expansion.

• High capacity — offers either an The LORAIN® DB 484800 BDF/CBB system consists of a standard or Zone 4 box frame-
eight bus to 4,800 amps, or six bus work, with either six or eight buses, top or bottom feed/distribution. The system offers
to 3,600 amps continuous rating, a wide variety of options including box frame extensions, internal ground bars and a
with maximum loading up to 168 paralleling feature that permits multiple loads to be tied together, internal input cabling
fuse or circuit breaker positions options and transient voltage surge suppression. The universal ground bars can be
mounted to overhead framing or a cable rack. The physical dimensions are 7' (2.13m)
• Modular design — initial and field high by 26" (66.04cm) wide by 15" (38.10cm) deep.
installed interchangeable fuse
and circuit breaker distribution
modules Application
• Fuse protection — utilizing TPS, The LORAIN® DB 484800 is ideally suited
TPA and TPL fuses protects circuits for central office, co-location, and other
ranging from 0-150 amps applications requiring effective secondary
load distribution and protection of power
• Circuit breaker protection — plants up to 600 amp capacity per load.
LEL plug-in breakers available
in current ratings of 1-150 amps
Additional Information
• Multiple circuit breaker
types — options range from bolt-in For additional specification, engineering
to plug-in and installation information request
drawing SAG582120600.
• NEBS level 3 compliance — meets
or exceeds all relevant GR1089,
GR63 and UL specifications

Enterprise : 121
PDS-PDB-018 / 0107
LORAIN® DB 484800
Battery Distribution Fuse/Circuit Breaker Bay

Options
Option Description
Digital metering Digital metering provides both current and voltage for each bus
Single or parallel buses Paralleled buses provide maximum configuration flexibility
Bus metering Separate bus current and voltage readings
Adjustable dressing bars Sliding dressing bars for reduced output cable installation time
Precharge Precharge module for TPS and TPJ fuseholders
Box framework extension 8'0" (1.37m), 9'0" (2.74m) and 11'6" (3.50m) extensions
In-line fuse kit Provides internal power to alarm and meter circuits
Cable management kit Grooming kit for load cable dressing
Transient voltage
protection Bus voltage protection for sensitive electronic equipment

Distribution Modules
The distribution modules are factory con- 6 Bus Maximum Distribution Module Population
figurable with one or more of the available Quantity Type Description
fuseholders or circuit breakers. Distribution
16 TPS 0-70 amp fuseholders
modules can be populated in varying com-
binations. See “6 Bus” and “8 Bus” charts to 10 TPL 60-150 amp fuseholders
the right for options. 28 LEL/TPS 0-150 amp plug-in circuit breakers or 0-100 amp TPS/TFD fuses

Monitoring
A fuse or breaker alarm (LED) is provided 8 Bus Maximum Distribution Module Population
for each bus, and a bay alarm (LED) is Quantity Type Description
visible from a wide angle. Three form C
contacts are provided for remote alarm 12 TPS 0-70 amp fuseholders
monitoring. ABS or local powering capabili- 6 TPL 60-150 amp fuseholders
ties for monitoring are included. 16 LEL/TPS 0-150 amp plug-in circuit breakers or 0-100 amp TPS/TFD fuses

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
122 : Enterprise
PDS-PDB-018 / 0107
LORAIN® IS 6000 DC Power for
Business-Critical Continuity
Expandable Rack-Mounted
Inverter System

Key Features
Compact modular design offers easy system expansion and
• Modular design permits configurations up to 6kVA in 6U.
expansion of the system in
1kVA increments

• Modules are hot-pluggable and


can be added or removed without
shutting down the system

• Control circuitry built into


each inverter improves system Product Overview
reliability by eliminating the need
for a central controller The LORAIN® IS 6000 provides a pure sine wave 120 VAC, 60 Hertz, 6KVA maximum output
from a 48 VDC input, depending on the configuration. The system is composed of 23-in.
relay rack-mounted cabinets in 2, 4 and 6 inverter configurations. The DC input to the
• Systems can be configured up to
cabinet can be configured to accept multiple feeds or a single input feed. An optional static
5kVA with redundancy switch and maintenance bypass switch combination can be added for ultimate reliability.
The system can be configured to cover the range of loads encountered in data centers,
• Cabinet is pre-wired for wireless sites or central office environments.
system expansion as AC load
requirements increase The modular design of the LORAIN® IS 6000 permits easy expansion as AC load require-
ments increase. System configuration can range from as low as 1kVA up to 6kVA max. Each
• Static transfer switch / inverter module can be field installed live without system interruption.
maintenance bypass panel
available An optional 19" or 23", 100 amp, rack-mounted AC distribution panel is available for cus-
tomers requiring overcurrent protection on the output.
• Field flexibility for DC input

Application
The LORAIN® IS 6000 rack-mounted
Inverter System is ideal for data centers,
wireless sites or central office environments
where flexible expansion capabilities are
necessary.

For additional specification, engineering


or installation information, specify model
LI48AMCAB, spec. number 584805000 for
the system, model LIA102B, spec. number
485501800 for the 1kVA inverter module LI48AMCAB, 584805000 Inverter System
and model LACP100A specification number
426806600 for the AC distribution panel.

Enterprise : 123
PPB-INV-002 / 1206
LORAIN® IS 6000
Expandable Rack-Mounted Inverter System

1kVA to 6kVA Inverter System Specifications


Input 1000VA LIA102B (485501800) HDS50 Transfer Switch (486664500) System (584805000)
Operating Voltage Range 40 to 60 VDC 90 to 150 VAC RMS 40 to 60VDC/95 to 150VAC RMS
Frequency Range N/A 57.5 to 62.5 Hertz AC In see STS
Stopping Voltages 39 and 63 VDC N/A see inverter
Restart Voltages 46 & 60 VDC N/A see inverter
Maximum Input Current 23A @ 800W@ 40VDC N/A 38A @ 40VDC @ 48W
Inrush Current <I nom. N/A see inverter
Static Transfer Switch N Y optional
Max AC Input Current N/A 50A 50A
Output
Nominal Output Voltage 120VAC 120 VAC RMS see inverter
Maximum Voltage Interruption N/A 0 to 6 msec (Typical: 3 msec) see transfer switch
Total Transient Voltage Duration N/A 1msec to 12 msec (Typical: 5 msec) see transfer switch
Output Voltage Tolerance +/-3% adj nom Depends on source Depends on source
Output Frequency 60Hz 57.5 to 62.5 Hertz 57.5 to 62.5 Hertz
Total Harmonic Distortion (lin. load) < 3% see inverter see inverter
Nominal Output Power 800W @ unity pf 4800W @ unity pf. (6kVA unit) Depends on the configuration.
1000VA @ ≤ 0.8 lag/lead 6000VA @ ≤ 0.8 lag/lead (6kVA unit) Available in 2, 4 & 6kVA sizes
Overload (5 sec max) 2000VA 100A 2000VA per inverter
Power Factor for 100% Power 0 to 0.8 lg or ld see inverter see inverter
Efficiency 88% 98% see inverter/STS
Environmental
Operating Temperature °C -20 to 50 -20 to 50 -20 to 40
Storage Temperature °C -40 to 80 -40 to 80 -20 to 80
Safety Compliance UL1950/EN60950 UL1950/EN60950/UL1778 UL/cUL1950/UL/cUL1778
Dielectric Strength Input/Output 4300VDC N/A see inverter
Dielectric Strength Output/Ground 4300VDC N/A see inverter
Dielectric Strength Input/Ground 2100VDC N/A see inverter
Cooling Fan Forced Convection Forced Convection
General
Relay Rack Mounting Arrangement See cabinet See cabinet 6 inch front projection
Dimensions (H x W x D) 1U x 480 x 350 (mm) 1U x 316 x 360 (mm) 2U/4U/6U/8U x 480 x 380 (mm)*
1U x 18.9 x 13.78 (in.) 1U x 12.44 x 14.17 (in.) 2U/4U/6U/8U x 18.9 x 15 (in.)*
Approx. Weight 6 Kgs / 13.2 lbs. 4 Kgs / 8.8 lbs. 3 - 6 Kgs / 6.6 - 13.2 lbs for 2U
5.5 - 8.5 Kgs / 12.1 - 18.7 lbs for 4U
8 - 11 Kgs / 17.6 - 24.2 lbs for 6U
Low value: without HDS
High value: with HDS

*If depth of 6-in. front projected equipment exceeds 12 inches, a 1U mounting space above the inverter is required for adequate ventilation.

Emerson Network Power. • AC Power Embedded Power • Precision Cooling


The global leader in enabling business- • Connectivity • Monitoring • Racks & Integrated Cabinets
critical continuity. • DC Power • Outside Plant • Services
• Embedded Computing • Power Switching & Controls • Surge Protection

© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.

Printed in USA
124 : Enterprise
PPB-INV-002 / 1206
Emerson Network Power
Business-Critical Continuity
for Communications

Enterprise Catalog
Outside Plant and DC Power Products & Systems

Emerson Enterprise Catalog : February 2007


Emerson Network Power
Energy Systems, North America
4350 Weaver Parkway, Warrenville, IL 60555
Toll Free OSP Tech Support: 800-800-5260 (USA and Canada)
Toll Free: 800-800-1280 (USA and Canada)
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems
EnergyNet: Secure.EmersonNetworkPower.com

Emerson Network Power.


The global leader in enabling business-critical continuity. EmersonNetworkPower.com

AC Power Embedded Power Precision Cooling


Connectivity Monitoring Racks & Integrated Cabinets
DC Power Outside Plant Services
Embedded Computing Power Switching & Controls Surge Protection

© 2007 Emerson Network Power Energy Systems, North America, Inc. All rights reserved.

This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing)
may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or
services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
conditions of supply of any product or service.

The Emerson logo is a trademark and a service mark of Emerson Electric Co. Emerson Network Power is a division of Emerson Electric Co.

Code: ESNA-102 / 02073M


Enterprise : February 2007