Business-Critical Continuity
for Communications
Enterprise Catalog
Outside Plant and DC Power Products & Systems
© 2007 Emerson Network Power Energy Systems, North America, Inc. All rights reserved.
This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing)
may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or
services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
conditions of supply of any product or service.
The Emerson logo is a trademark and a service mark of Emerson Electric Co. Emerson Network Power is a division of Emerson Electric Co.
OUTSIDE PLANT
Building Entrance BUP Series Indoor/Outdoor Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
BEP Series Building Entrance Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
BEPNC Building Entrance Terminals (Indoor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
PROT300XLBET Extra-Large 300-Pair Protector/Cross-Connect System . . . . . . . . . . . . . . . . 9
Terminal Blocks URLS1010-Pair IDC Terminal Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
RLS Series IDC Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
R66M Series & Category 5 Non-Connectorized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
R66P25 Series 25-Pair Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
CO Connectors & Frames R399URLS 100-Pair Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2500FRAME2 (One Vertical) Single-Sided Distribution System. . . . . . . . . . . . . . . . . . . . . . . . 29
2500 Frame (Two Verticals) Single-Sided Distribution System. . . . . . . . . . . . . . . . . . . . . . . . 31
Protection 5-Pin Protector Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
SuperDuty® JZ380 Series Next Generation Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Reference Standards Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Remote Terminals DEC25/NG “Next Generation” Digital Equipment Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
MESA® 4 NxT Modular Electronic Sealed Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
DC POWER
Small Systems LORAIN® XP 4890 DC Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
LORAIN® XP 48500 DC Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
LORAIN® CIP 4890/48120 DC Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
LORAIN® CSP 48300 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Medium Systems NetSure™ 701NCBB DC Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
NetSure™ 701NVBB DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
LORAIN® VPS 246000 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
LORAIN® VPS 486000 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Large Systems LORAIN® PS 4810000 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
LORAIN® LVS 4810000 DC Power System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
DC UPS NterpriseIP™ Solution, High Availability Power System for IP Telephony . . . . . . . . . . . . . . 113
Distribution Bays LORAIN® DB 48500 Battery Distribution Fuse/Circuit Breaker Bay. . . . . . . . . . . . . . . . . . . . 119
LORAIN® DB 484800 Battery Distribution Fuse/Circuit Breaker Bay. . . . . . . . . . . . . . . . . . . 121
Inverters LORAIN® IS 6000 Expandable Rack-Mounted Inverter System . . . . . . . . . . . . . . . . . . . . . . . 123
Enterprise :
February 2007
Notice of Disclaimer Business-Critical Continuity
for Communications
This catalog, all products listed in it, and their availability are subject to change without notice. Emerson Network Power Energy
Systems, North America, Inc. disclaims any responsibility or liability for any damages resulting from the use of these products.
Before using, user shall determine the suitability of the product for its intended use, and user assumes all risk and liability what-
soever in connection therewith.
Additionally, this catalog may reference the following company trademarks: 3M®, AT&T®, FIAMM®, GTE® and LORAIN®.
Names of companies and products are trademarks or registered trademarks of the respective companies.
The above trademark listing is complete as we know it. Any questions regarding usage of trademark names should be directed
to the original manufacturer.
The Emerson logo is a trademark and a service mark of Emerson Electric Co.
Emerson Network Power is a division of Emerson Electric Co.
Enterprise : ii
February 2007
BUP Series Outside Plant for
Business-Critical Continuity
Indoor/Outdoor Protectors
Key Features
Description
• Compact size requires minimum
mounting space The BUP is an outdoor-rated, self-contained building entrance protector. Whether used
for indoor or outdoor applications, no additional closures are necessary. The BUP is manu-
factured of heavy gauge mill-galvanized steel treated with a unique finishing process for
• Outdoor mounting capability for
longer life. Input connection options include field splice tail, 3M® 4000-D dry connectors,
greater accessibility
710 filled connectors or cable stub. Outgoing pair distribution options are RLS IDC or
quiet-front binding post screw down terminal blocks.
• Built-in splice chamber provides
enhanced wire management The BUP series utilizes 5-pin protector modules housed in a sealed chamber-within-
and additional environmental a-chamber for maximum environmental protection, which is especially important for
protection outdoor applications. All UL listed standard 5-pin protector modules may be used with the
BUP series. (See section 11 of this catalog, entitled “Protection Arresters & Modules,” for a
• Patented sealed protector module full list of the protector modules offered by Emerson.)
chamber offers a direct outdoor
application of 5-pin protector The BUP is wall or pole-mountable. Units can be ordered as stackable to 300 pairs, or can
be made stackable with the addition of a stacking kit. The units can also be outfitted with
modules; reduces installation and
a cable skirt, providing protection to the feeder and distribution cable from incidental con-
maintenance costs
tact and from the environment. A 216-type can wrench (Emerson catalog no. 15 or 38) is
required in order to open the unit. For further security, each unit is also equipped with a
• Variety of input and output padlock hasp.
connections provides application
flexibility
Dimensions
Pair Count H W D
25 & 50 15.00-in. (38.10 cm) 15.41-in. (39.14 cm) 4.70-in. (11.94 cm)
100 24.30-in. (61.75 cm) 15.41-in. (39.14 cm) 4.70-in. (11.94 cm)
Enterprise :
OSPDS-040100 / 0505
BUP Series Indoor/Outdoor Protectors
Ordering Matrix
Housing BUP = Indoor/Outdoor Building Entrance Protector
Output S = RLS B = BT/CQF
Pair Count 25 = 25 pair 100 = 100 pair
50 = 50 pair
Input FS = Field splice - 18" wire harness bundle SE6 = 6 foot, 24 AWG stub
MM = 3M 4000-D dry, (MS2) SE12 = 12 foot, 24 AWG stub
CF = 710 filled, capless, receptacle SE25 = 25 foot, 24 AWG stub
Options SKT = Skirt compatible STK = Stackable (non-stubbed units)
Accessories
Catalog Number Part Number Description
BUPWM1 F019741 Metal wall-mounting bracket for 25 & 50-pair BUP (optional)
BUPWM2 F019735 Metal wall-mounting bracket for 100-pair BUP (optional)
BUPPM1 F019742 Metal pole-mounting bracket for 25 & 50-pair BUP & BUPNP1
BUPPM2 F019738 Metal pole-mounting bracket for 100-pair BUP & BUPNP2
BUPSKT F787554 Cable skirt for 25, 50, & 100-pair BUP, 28"H x 15.07"W x 6"D
BUPLONGSKT F740098 Cable skirt for 25, 50, & 100-pair BUP, 52"H x 15.07"W x 6"D
LOOSEPARTSNX2 F039419 Stacking kit for 25 & 50-pair BUP*
P52859 F552859 Stacking kit for 100-pair BUP*
* Each stacking kit joins two units only. If stacking three units, order two stacking kits. Also, unless the units have been ordered stackable, the end user may
have to make a hole at the top of the splice chamber for feeding the remaining cable splice through to the upper unit(s).
Key Features
Description
• Built-in splice chamber provides
material and installation cost The BEP series combine protection and distribution with a built-in splice chamber, for a
savings single, compact, cost-effective unit designed for indoor building entrance applications.
Central office pairs are connected with the following options: field splice, stub, 710 con-
nectors, 3M® dry connectors, 66 quick-clip block, or 110-style block. The BEP series also
• Lift-out protector panel facilitates
offers a 26AWG fuse link for added protection. Subscriber wires are connected via the
installation; reduces inventory following options: 66 quick-clip, RJ21, 66 quick-clip and RJ21, 110-style block, or binding
costs; is easy to repair posts.
• Compact size requires minimum The BEP series is available in 25, 50, and 100-pair sizes. The 100-pair unit is stackable to
mounting space 300-pair (stacking kit included in 100-pair). The protector modules can be included or
purchased separately. The closure is accessed using a 216-type tool.
• All units are stackable to
accommodate future growth
Application
• Gold-plated protector contacts
minimize noise and customer The BEP series terminate, protect, and distribute central office cable pairs on the subscrib-
complaints er premises. They are ideal for use in multi-tenant dwelling and PABX installations.
• 26AWG 18-in. fuse link for added Quick-clip In/Quick-clip and RJ21 Out
protection
• Lock hasp provided for added
security
Enterprise :
OSPDS-080900 / 0605
BEP Series Building Entrance Protectors
Dimensions
Pair — Housing Dimensions —
Count H W D
25/50/100 15.00-in. (38.10 cm)* 15.41-in. (39.14 cm) 4.7-in. (11.94 cm)
Ordering Matrix
Housing BEP = Building Entrance Protector
Output C = 66 Quick-clip block
BEPC25C (25-pair) G = RJ21 receptacle connector
Quick-clip In & Out CG = 66 Quick-clip block & RJ21 receptacle connector
B = Binding posts
T = 110-style block
Pair Count 25 = 25-pair
50 = 50-pair
100 = 100-pair**
Input FS = Field Splice, 18-in. tail
CF = 710 connector, capless, receptacle, gel-filled,
18-in. tail, 26AWG fuselink
MM = 3M 4000-D dry (MS2), 18-in. tail, 26AWG fuselink
C = 66 Quick-clip block, 26AWG fuselink
SC = 24AWG cable stub
BEPC100MM (100-pair) T = 110-style block, 26AWG fuselink
3M® Dry Connector In/Quick-clip Out Cable Full Length 6 = 6-ft.
(only if "sc" input) 12 = 12-ft.
25 = 25-ft.
blank = Stubless
Accessories
Catalog Part
Number Number Description
P35980 F535980 Grommets for 1-in. diameter hole (pkg. of 20)
P47839 F547839 U-shaped grommet
P47147 F547147 Cup-sems with push nut (pkg. of 10)
NOTE: For additional accessories, see the Accessories section of the catalog.
Key Features
Description
• Integrated stand-off bracket allows
for easy distribution and cable The BEPNC series combines protection and distribution, for a single, compact, cost
routing effective unit designed for indoor building entrance applications. Central office pairs are
connected with the following options: stub, 66 quick-clip block, 110 style block, or the
Emerson pair-at-a-time tool-less URLS block. The BEPNC also offers a 26 AWG fuse link for
• Wall or frame mountable
added protection. Subscriber connection options include: 66 quick-clip, 110 style block or
Emerson URLS block.
• Compact size requires minimum
mounting space The BEPNC series is available in 100, 50, 25, 10-pair sizes. All BEPNC terminals are stack-
able. Protector modules can be included or purchased separately.
• All units are stackable to
accommodate future growth
Application
• Available in various configurations,
66, 110, URLS, 710 as well as The BEPNC series terminates, protects, and distributes central office cable pairs at the
factory stubbed subscriber premises. They are ideal for use in multi-tenant office buildings, high-rise apart-
ments, campus environments and PABX installations.
• Available pair counts: 100, 50, 25
and 10
Enterprise :
OSPDS-081500 / 0605
BEPNC Building Entrance Terminals (Indoor)
Ordering Matrix
Terminal Protector BEPNC = Indoor Wall-Mount
Output C = Quick-clip block
T = 110-style block
U = URLS-style block
Pair Count 100 = 100-pair
50 = 50-pair
25 = 25-pair
10 = 10-pair
Input C = Quick-clip block, 26 AWG fuselink
SC = 26 AWG cable stub
T = 110-style block, 26 AWG fuselink
U = URLS-style block, 26 AWG fuselink
Input Cable Stub Length 25 = 25-ft.
12 = 12-ft.
6 = 6-ft.
Blank = Stubless
NOTE: To order with 5-pin protector modules installed, call customer service.
: Enterprise
OSPDS-081500 / 0605
BEPNC Building Entrance Terminals (Indoor)
NOTE: For more information and other configurations, call customer service.
Enterprise :
OSPDS-081500 / 0605
BEPNC Building Entrance Terminals (Indoor)
Accessories
Catalog Number Part Number Description
BEPNC110COVER1 F1005299 100-pair BEPNC Cover Kit (Non-Stub)
BEPNC66COVER1 F1005300 100-pair BEPNC Cover Kit (Non-Stub)
BEPNCURLSCOVER1 F1005991 100-pair BEPNC Cover Kit (Non Stub)
BEPNC110COVER2 F1005384 50-pair BEPNC Cover Kit (Non-Stub)
BEPNC66COVER2 F1005385 50-pair BEPNC Cover Kit (Non-Stub)
BEPNCURLSCOVER2 F1005992 50-pair BEPNC Cover Kit (Non Stub)
BEPNC110COVER3 F1005386 25-pair BEPNC Cover Kit (Non-Stub)
BEPNC66COVER3 F1005387 25-pair BEPNC Cover Kit (Non-Stub)
BEPNCURLSCOVER3 F1005993 25-pair BEPNC Cover Kit (Non Stub)
BEPNC110COVER4 F1005388 10-pair BEPNC Cover Kit (Non-Stub)
BEPNC66COVER4 F1005389 10-pair BEPNC Cover Kit (Non-Stub)
BEPNCURLSCOVER4 F1005994 10-pair BEPNC Cover Kit (Non Stub)
BEPNC110COVER5 F1005382 100-pair BEPNC Cover Kit (Stub)
BEPNC66COVER5 F1005383 100-pair BEPNC Cover Kit (Stub)
BEPNCURLSCOVER5 F1005995 100-pair BEPNC Cover Kit (Stub)
BEPNC110COVER6 F1005325 50-pair BEPNC Cover Kit (Stub)
BEPNC66COVER6 F1005326 50-pair BEPNC Cover Kit (Stub)
BEPNCURLSCOVER6 F1005996 50-pair BEPNC Cover Kit (Stub)
BEPNC110COVER7 F1005330 25-pair BEPNC Cover Kit (Stub)
BEPNC66COVER7 F1005327 25-pair BEPNC Cover Kit (Stub)
BEPNCURLSCOVER7 F1005997 25-pair BEPNC Cover Kit (Stub)
BEPNC110COVER8 F1005328 10-pair BEPNC Cover Kit (Stub)
BEPNC66COVER8 F1005329 10-pair BEPNC Cover Kit (Stub)
BEPNCURLSCOVER8 F1005998 10-pair BEPNC Cover Kit (Stub)
NOTE: For more information and other configurations, call customer service.
Key Features
Description
• Terminates and protects up to
1800 copper pairs in only three The PROT300XLBET is a 300-pair protector and cross-connect panel which provides pro-
square feet of floor space for high tection, termination and cross-connection of copper pairs on opposite sides of a single
23-inch telco relay rack. It is designed for large pair count installations to provide termi-
density applications.
nation and protection up to 1800 copper pairs in only three square feet of floor space.
• Protection for central office Industry standard 5-pin protector modules, 5-pin protector blocks, 110, BIX® or Emerson
applications, building entrance, pair-at-a-time tool-less URLS termination blocks, and 7-foot frames have been incorpo-
and distribution frames with rated in a craft-friendly design that scales from 300 to thousands of copper pairs.
multiple cabling options such as
top or bottom entry, 25 or 50- This product is ideal for applications where future growth is expected, but initial instal-
lation size is minimized to control the cost. The min-imum configuration is one 300-pair
ft. stubs, and 25 or 32-pair RJ21
panel on a 23-inch steel rack and 5-pin protector modules to match the actual pair count.
connectors.
300-pair panels are added as the pair count need increases. The innovative, hinged, split
• Factory wired panels eliminate protector panel allows new cables to be dressed safely into existing panels. Unused rack
cabling errors, decrease installation space can be used for other equipment once growth stops.
time, and reduce project costs. Use
Complete 1800-pair rack systems can be ordered for larger applications. These systems
of standard components reduces
include the 7-foot rack, six of the 300-pair panels, 1800 of the 5-pin protector modules
training time and user errors. The
and horizontal troughs for managing jumper wires between racks. Rack systems may be
PROT300XLBET provides a system mounted side by side to meet growing system requirements.
with minimum jumper runs and
efficient use of space. Telecommunications relay rack applications are easier and more versatile with the com-
bined protection and cross-connect features of the PROT300XLBET.
• Available in various cross-connect
configurations: 110, BIX® and
The PROT300XLBET is the result of continuous design reviews with industry consultants,
URLS. contractors, telecommunication engineers and end users.
• Cable stubs are dressed down the
center of the frame for weight
balance and safety. Application
• Hinged, split protector panel
The PROT300XLBET is intended for
is designed for adding and
building entrance termination, main dis-
rearranging stubs.
tribution frame and building distribution
• Adjustable stub allows for up or frame applications where copper cable
down installation of stub. is terminated and protected in one com-
pact 7- foot frame. Outside plant cable
• The patented Emerson silo is usually terminated in a standard splice
protector block improves case where the cable enters the build-
attenuation, cross talk and ing. The stubs from the PROT300XLBET
insulation resistance and conforms are spliced to the outside plant cable
to Telcordia GR-2916. at the splice case by the installer. The
stubs are factory prewired to the OSP
• Uses industry standard termination side of the 5-pin protector blocks in the
blocks and 5-pin protector PROT300XLBET.
modules.
Enterprise :
OSPDS-084500 / 0906
PROT300XLBET
Extra-Large Building Entrance 300-Pair Protector / Cross-Connect System
Ordering Information
Catalog number Part number Description
300-Pair Protector & Cross-Connect Panels with 110 IDC Termination Blocks
PROT300XLBET251A F1005404 Includes 25-ft. stub and 25-pair RJ21 connectors
PROT300XLBET251B F1005405 Includes 25-ft. stub and 32-pair RJ21 connectors
PROT300XLBET501A F1005406 Includes 50-ft. stub and 25-pair RJ21 connectors
PROT300XLBET501B F1005407 Includes 50-ft. stub and 32-pair RJ21 connectors
300-Pair Protector & Cross-Connect Panels w/BIX® IDC Termination Blocks
PROT300XLBET251C F1005849 Includes 25-ft stub and 25-pair RJ21 connectors
PROT300XLBET251D F1005948 Includes 25-ft stub and 32-pair RJ21 connectors
PROT300XLBET501C F1005958 Includes 50-ft stub and 25-pair RJ21 connectors
PROT300XLBET501D F1005959 Includes 50-ft stub and 25-pair RJ21 connectors
300-Pair Protector & Cross-Connect Panels w/URLS Pair-at-a-time Tool-less Termination Blocks
PROT300XLBET251E F1005960 Includes 25-ft stub and 25-pair RJ21 connectors
PROT300XLBET251F F1005961 Includes 25-ft stub and 32-pair RJ21 connectors
PROT300XLBET501E F1005962 Includes 50-ft stub and 25-pair RJ21 connectors
PROT300XLBET501F F1005963 Includes 50-ft stub and 25-pair RJ21 connectors
Caution: All XLBET protector and cross-connect panels and 1,800-pair systems come supplied
with 48-in. 26AWG fuse link cables which must be enclosed in a locally provided splice case or shroud.
10 : Enterprise
OSPDS-084500 / 0906
PROT300XLBET
Extra-Large Building Entrance 300-Pair Protector / Cross-Connect System
Ordering Information
Catalog number Part number Description
1800-Pair Protector & Cross-Connect Frame Systems with 110 IDC Termination Blocks
1800XLBET25SYST1A F1005408 (1) RRACKXLBET relay rack; (6) PROT300XLBET251A 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET25SYST1B F1005409 (1) RRACKXLBET relay rack; (6) PROT300XLBET251B 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1A F1005410 (1) RRACKXLBET relay rack; (6) PROT300XLBET501A 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1B F1005411 (1) RRACKXLBET relay rack; (6) PROT300XLBET501B 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800-Pair Protector & Cross-Connect Frame Systems with BIX® IDC Termination Blocks
1800XLBET25SYST1C F1005850 (1) RRACKXLBET relay rack; (6) PROT300XLBET251C 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET25SYST1D F1004896 (1) RRACKXLBET relay rack; (6) PROT300XLBET251D 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1C F1005951 (1) RRACKXLBET relay rack; (6) PROT300XLBET501C 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBEY50SYST1D F1005952 (1) RRACKXLBET relay rack; (6) PROT300XLBET501D 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800-Pair Protector & Cross-Connect Frame Systems with URLS Pair-at-a-time Tool-less IDC Termination Blocks
1800XLBET25SYST1E F1005953 (1) RRACKXLBET relay rack; (6) PROT300XLBET251E 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET25SYST1F F1005954 (1) RRACKXLBET relay rack; (6) PROT300XLBET251F 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1E F1005955 (1) RRACKXLBET relay rack; (6) PROT300XLBET501E 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
1800XLBET50SYST1F F1005956 (1) RRACKXLBET relay rack; (6) PROT300XLBET501F 300-pair panels 1800 each R4CIEJZ
gas protector modules w/ heat coils & test points; (3) 300PRTROUGH horizontal jumper troughs
Caution: All XLBET protector and cross-connect panels and 1,800-pair systems come supplied with
48-in. 26AWG fuse link cables which must be enclosed in a locally provided splice case or shroud.
Enterprise : 11
OSPDS-084500 / 0906
PROT300XLBET
Extra-Large Building Entrance 300-Pair Protector / Cross-Connect System
Accessories
Catalog Number Part Number Description
RRACXLBET F1004898 Steel relay rack 7-ft. x 23-in. x 6-in. ( H x W x D), 500 lbs., NEBS™ Zone 4 load rating: 1000 lbs. static load
R4C1EJZ F013440 5-pin gas protector module with heat coils and front test points
300PRTROUGH F1005412 23-in. horizontal wire management 4-in. x 23-in. x 2-in. ( H x W x D)
FUSELINK F1005740 100-pair connectorized (MS2 both ends) cable tie, 48-in. 26AWG
Key Features
Description
• No tools required for pair-at-a-time
ActCap connections The URLS10 is an indoor/outdoor 10-pair terminal block for connecting solid copper com-
munications wire. All connections are IDC (insulation displacement connection), made
without removing the insulation from the wire. The contact terminals slice through the
• IDC termination on all connections
insulation and create a gas-tight contact at the copper/terminal interface.
for fast, easy termination and
jumpering with no wire stripping Two models are available – the URLS10 for indoor installations, and the sealant-filled
URLS10S for use in outdoor or environmentally-challenging installations. Both models are
• Sealant-filled connectors on assembled from two primary components – a URLS connector module and a URLS base.
the URLS10S provide moisture
resistance and longer-life The connector module contains metallic contacts that provide electrical and test con-
termination for environmentally- nections. Located on the top of the connector module, ten ActCaps guide single-pair
challenging installations cable into proper terminating position, connecting the cable pair to the metallic contacts.
Wires are then terminated by pressing down on the ActCap, requiring only a push of the
• Half-tap capability permits installer’s thumb. The ActCaps can terminate 20- through 26-gauge (.4 to .8 mm) con-
ductors. Test results verify that ActCaps can terminate 24-gauge wire more than 250
multiple appearances of jumper
times with stable, low contact resistance.
wire
The base can terminate 22- through 26-gauge (.4 to .6 mm) conductors. Up to 10 pairs
• Continuity and directional testers from the incoming cable stub can be terminated on the base using an available termi-
provide more complete testing of nation tool. Wires are cut to the proper length during the termination process. Tools
the circuit are available for either ten-pair-at-a-time (URLSFIXTURE) or single-wire termination
(URLSTOOL1). The single-wire termination tool is perfect for low pair count installations,
• Variety of frame pair counts and cable repair, and maintenance.
sizes for maximum application and
installation flexibility URLS blocks are molded from glass-filled Valox for long-term performance. Electrical
terminals are fabricated from tin-plated phosphor bronze for low contact resistance. The
sealant used in the URLS10S protects against corrosion caused by high humidity and salt
• Compact size makes URLS ideal for
in street-side and coastal installations.
applications where space is limited
URLS blocks can be mounted to industry-standard 4.12-in. (10.4 cm) wide mounting
• Available installed in cross-connect frames in a variety of pair counts. Close-pitch frames are available for higher terminal den-
and building entrance terminals to sity. Rod mount kits are also available.
fit a variety of applications
Enterprise : 13
OSPDS-060100 / 0505
URLS10 10-Pair IDC Terminal Block
Accessories
Catalog Number Part Number Description Fig.
URLS1TEST1M F800801 Single-pair (continuity-bridge) tester w/one-meter test cord 2 wire # 6 Ring term (Fig. 2) 1a
URLS2TEST1M F800802 Single-pair break tester w/one meter test cord 4 wire # 6 Ring term (Fig. 2) 1a
URLSHALFTAP F800804 Single-pair URLS half-tap, 10/pkg. (Fig. 2) 1b
URLSHALFTAP10S F800572 Single-pair URLS half-tap with sealant, 10/pkg. (Fig. 2) 1b
URLSDISCPLUG1 F800803 Single-pair disconnect plug, 100/pkg. (Fig. 2) 1c
URLSDISCPLUG10 F596092 10-pair disconnect plug 10/pkg. 1c
URLSTOOL1 F1001087 Single-wire incoming cable grooming and terminating tool
URLS10TERMFM F800569 10-pair incoming frame mount cable grooming and terminating tool
RLSBBIDENT1800B F017865 Pair identification plugs for 1-1800 pairs (Blue)
RLSBBIDENT1800G F017866 Pair identification plugs for 1-1800 pairs (Green)
RLSFRAME50 F607095 Metal frame for mounting up to five URLS 10-pair blocks (50 pair)
RLSFRAME60 F017809 Metal frame for mounting up to six URLS 10-pair blocks (60 pair)
URLS10TERMRM F1002830 10-pair feeder termination tool rod mount
URLSCAPRED F800568 Special service caps (Red) 100/pkg. 1d
NOTE: Rear mounted protection cartridge for overvoltage protection available soon. Contact customer service.
Key Features
Description
• No special tools required for ease
of installation The RLS Series blocks consist of compact, IDC (insulation displacement connection) wire
connectors, which provide fast, easy connection of 22 to 26 gauge ( .4 to .6 mm) wire.
Each connector is silicone-grease filled with tin-plated terminals, providing maximum
• Silicone grease-filled connectors
environmental protection for terminated pairs.
provide moisture resistance and
longer life termination The RLS Series includes blocks for 2 to 50-pairs. Pair-at-a-time wire termination is accom-
plished by lifting the RLS activator, inserting a pair of unstripped wires into the appropriate
• Pair-at-a-time IDC termination slots on the activator, and pressing firmly down on the activator.
allows fast, easy jumpering with no
wire stripping The 2 and 5-pair blocks are internally wired, with RLS input and output. The 10, 25, and
50-pair blocks are potted on the rear side of the block, and are available in a variety of har-
• Half-tap capability permits ness lengths, with or without connectors.
multiple appearances of jumper
wire
Application
• Variety of harness lengths and
connectors for ease of use and The RLS family of blocks is a flexible terminal block that can be employed in a wide variety
consistency with telco standards of cross-connect or building entrance applications. These blocks are ideal for outdoor use.
Enterprise : 15
OSPDS-060700 / 0505
RLS Series IDC Terminal Block
Dimensions
Catalog Number H W D
RLS2X2 1.06-in. (2.69 cm) 2.66-in. (6.76 cm) 1.50-in. (3.81 cm)
RLS5X5 1.06-in. (2.69 cm) 5.50-in. (13.97 cm) 1.50-in. (3.81 cm)
RLS10 1.06-in. (2.69 cm) 5.50-in. (13.97 cm) 1.50-in. (3.81 cm)
RLS25 5.38-in. (13.67 cm) 2.88-in. (7.32 cm) 1.50-in. (3.81 cm)
RLS2X2 RLS50 5.68-in. (13.67 cm) 5.06-in. (12.85 cm) 1.50-in. (3.81 cm)
Ordering Information
Catalog Number Part Number Pair Count Input Description
RLS2X2* F016996 2 RLS IDC Internally wired unit
RLS5X5* F016998 5 RLS IDC Internally wired unit
RLS10 F016997 10 26 AWG harness Equipped with 5.5-ft. (1.68 m) harness
RLS25 F017812 25 26 AWG harness Equipped with 2.5-ft. (0.76 m) harness
RLS254 F001095 25 26 AWG harness Equipped with 4-ft. (1.21 m) harness & 3M® 4005-DPM connector
RLS25DPM F017814 25 MS2 Equipped with 6-ft. (1.82 m) harness & 3M® 4005-DPM connector
RLS255DPM F005313 25 MS2 Equipped with 5-ft. (1.52 m) harness & 3M® 4005-DPM connector
RLS25CF F005315 25 710 Equipped with 6-ft. (1.82 m) harness & 710 connector
RLS50 F016950 50 26 AWG harness Equipped with 7-ft. (2.13 m) harness
RLS50DPM F016945 50 MS2 Equipped with 6-ft. (1.82 m) harness & 3M® 4005-DPM connectors
RLS507FT3M4005 F003043 50 MS2 Equipped with 7-ft. (2.13 m) harness & 3M® 4005-DPM connectors
RLS507FT3M4000 F003044 50 MS2 Equipped with 7-ft. (2.13 m) harness & 3M® 4000-D connectors
RLS50CBM6 F016941 50 MS2 Equipped with 6-ft. (1.82 m) harness & 3M® 4005-CBM connectors
RLS50PVC20 F300300 50 26 AWG stub Equipped with 20-ft. (6.09 m) PVC-sheathed cable stub
* With the exception of the RLS2X2 and RLS5X5, when used in cross-connect applications, the input termination style listed refers to the feeder side
termination. The output termination style would, of course, be reserved for the distribution side.
NOTE: For other harness lengths and/or connector types, please contact your Emerson customer service representative.
Accessories
Catalog Number Part Number Description
RLSACTGRAY10 F567272 Gray replacement activators, 10/pkg.
P71082 F571082 Red RLS activators, 5/pkg.
RLSTEST1 F019128 1-pair tester with 5-ft. leads & ring terminals for RLS and 3M® SS-25
RLSTEST1PKT F019127 1-pair pocket tester w/ring terminals for RLS and 3M® SS-25
TS50RLS1S F019139 50-pair stackable test shoe for RLS50 w/carrying case
P53828 F553828 Red special service caps, 30/pkg.
P60209 F560209 Half-tap activator, 80/pkg.
NOTE: For testing equipment, tools, labels, and other accessories, please see the Accessories section of this catalog.
Key Features
Description
• Impact-resistant molded housings
provide long life and lower R66M series non-connectorized 12, 25 or 50-pair quick-clip blocks are manufactured of UL
maintenance costs Listed 94 V-0 rated material and are designed for fast, easy termination of insulated solid
copper wire. Blocks are easily stackable for higher pair counts.
• Notched fanning strips for ease of
The R66M series has a clip capacity of 50 horizontal rows by 4 vertical rows. Unstripped
wire tracing, identification, and solid 20 to 26-gauge conductors (.4 to .8 mm) can be easily terminated using the industry
good housekeeping standard 714-type punch-down tool (Emerson R714B).
• R66M150 blocks meet The Category 5 R66M150 blocks comply with EIA/TIA-568 Category 5 specifications,
EIA/TIA-568 Category 5 which recognizes only 24-gauge UTP (unshielded twisted pair) horizontal wiring. These
specifications to exceed blocks provide the highest transmission performance for speeds up to 100 Megahertz per
documented performance levels; second, while decreasing attenuation, near-end crosstalk, and return loss.
conforms to state-of-the-art LAN
systems for high speed data R66M series blocks are supplied with integral fanning strips molded on each side of the
block and notched every ten rows for easy identification. The blocks are also available
mounted in gray or beige molded impact-resistant plastic housings.
• Category 5 provides network
flexibility to handle emerging voice
and data applications
Application
• Category 5 supports data rates up
to 100 Megahertz per second for R66M series blocks are used in equipment rooms to cross-con-
network flexibility nect key telephone and PBX systems. The blocks terminate
25 twisted pair station cable and have cross-connect features
from key service units to station equipment. These blocks are
• UL Listed to meet or exceed
also used to connect a private branch exchange to its stations.
documented performance levels The R66M series is used on all types of customer premises and
central office equipment, including T1 and data connections.
R66M150X
Enterprise : 17
OSPDS-070100 / 0605
R66M Series & Category 5 Non-Connectorized
Clip Configurations
All dimensions are as measured in inches, R66M112 R66M125X and R66M150X
with centimeter conversions in paren-
theses. Block depth is 1.25-in. (3.18 cm).
Cover depth is 2.34-in. (5.94 cm).
R66M112
R66M125X
R66M150X
R66M125MH
R66M150MH
18 : Enterprise
OSPDS-070100 / 0605
R66M Series & Category 5 Non-Connectorized
Clip Configurations
All dimensions are as measured in inches, R66M250MH, R66M275MH and R66M2100MH
with centimeter conversions in parentheses.
Block depth is 1.25-in. (3.18 cm). Cover
depth is 2.34-in. (5.94 cm).
R66M250MH
R66M275MH
R66M2100MH
Enterprise : 19
OSPDS-070100 / 0605
R66M Series & Category 5 Non-Connectorized
Ordering Information
Catalog Part Pair Common Std. Category
Number Number Description Count Clips Pkg. 5
M Series Blocks
R66M112 F015151 12-pair M block 12 2 25
R66M125X F015072 25-pair M block, bulk pack 25 4 50
R66M150X F015213 50-pair M block, bulk pack 50 2 50 √
M Series Blocks With Plastic Base (white) and Cover (gray)*
R66M125MH F015315 25-pair M block 25 4 5
R66M150MH F015317 50-pair M block 50 2 5 √
R66M250MH F015319 (2) 25-pair M block 50 4 5
R66M275MH F015323 (1) 25-pair M block/ (1) 50-pair 75 4-2 —
R66M2100MH F015321 (2) 50-pair M block 100 2 5 √
Empty Housings
P22314 F522314 Small beige housing, accommodates one block
P22315 F522315 Large beige housing, accommodates two blocks
P22338 F522338 Small gray housing, accommodates one block
P22339 F522339 Large gray housing, accommodates two blocks
* If product is desired in a beige closure, place a B at the end of the catalog number.
NOTE: Not all catalog numbers can be configured. For brackets, covers, bridging clips, etc. see the “66 Block Accessories” in the Accessories section
of this catalog.
Key Features
Description
• Optional quick-clip, RJ21, or
stub interfaces meet a variety of The R66P25 series of indoor blocks offers protection for 25-pair in a compact, versatile,
installation requirements and cost-effective unit. These blocks have the same mounting dimensions as a 66M150
block, and can be mounted on a wall, backboard, or 89-type bracket (Emerson R891
Series and R89B).
• Provides FCC RJ21X demarcation
for separation of telco central Standard network cable termination options are either quick-clips or a cable stub.
office pairs from customer Customer premise equipment termination options are quick-clips or 50-position RJ21 con-
premises equipment nectors.
• Universal hold-down keeps Unstripped solid 20 to 26-gauge (.4 to .8 mm) conductors can be easily terminated using
connectorized RJ21s mated an industry standard 714-type punch-down tool (Emerson R714B). Each block is supplied
with an integral fanning strip molded on one side of the base, marked every five rows to
• Compact design is high density simplify pair identification.
and has the same mounting
Units may be ordered with or without factory-installed 5-pin protector modules. To order
dimensions as the standard
the R66P25 with factory-installed protection, add selected Emerson protector module
66M150
catalog numbers (R3B1EJZ, 3GUVS, etc.) to the catalog number. The R66P25 series will
accept carbon, gas, or solid-state 5-pin protector modules. One module provides pro-
• Mounts on standard 89-type tection for one pair, and each unit can accommodate 25 modules. Each R66P25 is also
brackets for dynamic allocation of supplied with a ground connector for a 6AWG solid copper wire.
wires on wall- or frame-mounted
applications
R66P25QC
Shown with Modules
Enterprise : 21
OSPDS-073500 / 0605
R66P25 Series 25-Pair Protection
22 : Enterprise
OSPDS-073500 / 0605
R66P25 Series 25-Pair Protection
Figure 4 Figure 5
R66P25 with R891 Series Mounting Bracket
Enterprise : 23
OSPDS-073500 / 0605
R66P25 Series 25-Pair Protection
Ordering Information
Catalog Part — Termination Style — R891 Bracket Fig.
Number Number Application In*2 / Out*3 Required*4 Number
R66P25QC F015360 Protection QC / QC Optional 1
R66P25QCC F015361 Protection QC / RJ21 Optional 2
Receptacle
R66P25QCCR3B1EJZ F015421 Protection e/w R3B1EJZ QC / RJ21 Optional 2
Receptacle
R66P25QCP F015391 Protection QC / RJ21 Plug Optional 2
R66P25QCR3B1EJZ F015432 Protection e/w R3B1EJZ QC / QC Optional 1
R66P25QCS10 F015362 Protection 10-ft. stub / QC √ 3,5
R66P25QCS20 F015363 Protection 20-ft. stub / QC √ 3,5
R66P25QCVS F015409 Protection e/w 6U2VS QC / QC Optional 1
R66P25S10CD*1 F015401 Protection/demarcation 10-ft. stub / RJ21 Receptacle √ 4,5
R66P25S20CD*1 F015402 Protection/demarcation 20-ft. stub / RJ21RJ21 Receptacle √ 4,5
Abbreviations:
QC = Quick-connect clips or 66 Clips
RJ21 = 50-position RJ21 connector with universal hold-down, mounted for bottom feed
stub = Cable stub, 25-pair, 24-gauge cable
*1 50 2-position bridging clips (Emerson RA1) are included. Bridging clips are required to connect
protection to customer premises equipment. Bridging is necessary
*2 Central office or network cable pairs across the two outside vertical rows. (see Figure 4)
*3 Customer premises equipment or distribution pairs
*4 R891 Series brackets must be ordered separately
NOTE: See UL card for usage limitations in meeting UL Spec No. 497 or 497A.
Accessories
Catalog Part
Number Number Description
R891S50 F1003918 Stand-off bracket
RA1 F005170 Bridging clips
R66MHCO2 F015380 Hinged covers, 5-in. orange
R66MHCG2 F015381 Hinged covers, 5-in. gray
P17812 F517812 Ground connector
P48723 F548723 Universal hold-down
NOTE: For additional brackets, covers, bridging clips, etc. see the Accessories section of this catalog.
Key Features
Description
• Maximum density saves space;
increases number of protected The latest, state-of-the-art R399URLS protected connector block from Emerson Network
cable pair per frame vertical Power offers tool-less, gas-tight, pair-at-a-time IDC wire termination on the equipment
side jumper field for fast, economical and reliable installations. The R399 is a high density
100-pair connector utilizing industry standard 5-pin protector modules. The R399URLS
• Tool-less pair-at-a-time connection
block is made of 94 V-0 rated, molded plastic and UL Listed to meet specification number
for fast, reliable and economical UL 497. The block's compact design allows maximum density per frame vertical.
terminations
Any connection of 22 to 26-gauge (.63mm to .38mm) solid conductor wire is made by lift-
• Accommodates a wide range of ing the activator, inserting the conductor pair, and pressing the activator down.
distribution wire for application
flexibility For cutovers and applications requiring a second extension or connection, the R399URLS
offers a half-tap module that operates independently from the permanent distribution
• Accepts industry standard activator. Therefore, the distribution half-tap module can be connected and disconnected
protector modules to permit a without disturbing the primary connection.
wide module selection
The R399URLS allows front access for both line testing and line disconnection.
Disconnecting plugs are available for temporary or permanent disconnection of the cir-
• “Look-both-ways testing” provides cuit. Fault isolation is simplified by directional (“look both ways”) access that supports
directional access that supports independent testing on each side of the line.
independent testing on each side
of the line For protection, a full line of 5-pin modules are available. Please see the Protection
Arrestors and Modules section in the OSP catalog.
• Current/overvoltage protection
during circuit testing, half-tap
additions, line connecting or
Application
disconnecting for added safety to
personnel and equipment The R399URLS protects personnel and equip-
ment from abnormal voltages and currents on
• Swivel stub design for up or down incoming cable pairs. R399URLS is mounted
stub configuration facilitates on framework in central office, remote termi-
ordering nal, or building entrance applications.
Enterprise : 25
OSPDS-090100 / 0106
R399URLS 100-Pair Connector
Dimensions
Connector H W D
R399URLS 8.40-in. 4.10-in. 8.77-in.
(213mm) (104mm) (223mm)
Ordering Matrix
Mounting Configuration blank = Non-angled mount
A = Angled mount
Ground Configuration blank = Conventional ground
S = Isolated ground
Connector Application R399URLS = Standard mount (left mount)
RZ399URLS = For use on right side protector columns
of 2500 frame
Stub Cable Gauge A = 24-gauge, .96 dia. o.d.
B = 22-gauge, 1.17 dia. o.d.
Stub Cable Type A = Alvyn
T = Two 22AWG cables*
Stub Length** (20-ft. minimum in 10-ft. increments)
* T configuration provides an equivalent to T screen-type cable. Two 50-pair cables are secured together every three feet.
**Stubbed units equipped with swivel stub for up or down configuration.
NOTE: Not all catalog numbers can be configured.
26 : Enterprise
OSPDS-090100 / 0106
R399URLS 100-Pair Connector
Enterprise : 27
OSPDS-090100 / 0106
R399URLS 100-Pair Connector
Accessories
Catalog Part
Number Number Description
P48271 F548271 100-pair wall mounting bracket
P46321 F546321 Cable pair ID label
P95770 F595770 Replacement Activators (10 pkg.)
R399LPKIT F568051 Isolated ground kit
URLS1TEST1M F800801 Single pair, one-way break tester w/one meter 4-wire test cord, #6 ring terminals
URLS2TEST1M F800802 Single pair 2-directional continuity (bridge) tester w/one meter, 2-wire test cord #6 ring terminals
URLSCAPRED F800568 Red special service cap (100 per pkg.)
URLSDISCPLUG1 F800803 Single Pair Disconnect Plug (100 per pkg.)
URLSDISCPLUG10 F596092 Ten Pair Disconnect Plug (100 per pkg.)
URLSHALFTAP F800804 Single pair URLS half tap dry (10 per pkg.)
URLSHALFTAP25 F800570 Single pair URLS half tap dry (25 per pkg.)
Key Features
Description
• Single-sided system allows all
frame administration to be The 2500FRAME2 from Emerson Network Power Communications is a single vertical,
performed on one side single-sided modular distribution system. Its versatile configuration can meet a variety of
specific pair sizing requirements.
• Common jumper trough permits
For protection, the frame mounts Emerson Communications' R399 100-pair central office
short jumpers for labor savings connectors. For equipment terminations, the frame will mount any conventional front-
facing line terminal blocks with 8-in. mounting centers, including 89 type blocks, the
• Modular design is easily expanded Emerson Communications' 2376 block, or the Emerson Communications' Block 32 and
“G” series. For building entrance applications, the 2500FRAME2 accommodates 66-clip
• Frame is factory pre-assembled for termination.
quick, easy installation
The 2500FRAME2 is a single vertical floor/wall mounted frame comprised of one vertical,
• Versatile block mounting can be one horizontal jumper trough for wire distribution to adjacent verticals, multiple jumper
configured to all pair requirements retainers for wire management, and top trough and bottom guide for conventional wire
routing.
• Can be used as double-sided aisle
Each vertical of the 8-ft. frame has ten block positions, which allows a maximum capac-
mount ity of 1,000 protected pairs per vertical. What makes the frame so flexible is that either a
R399 protected terminal block, a front facing line terminal block, or a horizontal jumper
trough can be mounted in any block position, allowing for any combination of protected
and equipment blocks on each frame.
Multiple frames can be suitably spaced and connected together to meet the required
application size. Each frame module has jumper access to adjacent modules through the
use of horizontal or top jumper troughs.
Application
The 2500FRAME2 is designed specifically for small frame appli-
cations from 100 pair up to 15,000 pair. This frame provides
optimum protection/cross connection capabilities for:
Central Office
CLEC Applications
Co-Locations
Building Entrance Installations Three Frames Side-by-side
Remote Terminals
Enterprise : 29
OSPDS-100300 / 0705
2500FRAME2 (One Vertical) Single-Sided Distribution System
Capacities
2500FRAME2 (8-ft. frame) 25007FRAME2 (7-ft. frame)
1 vertical per frame module. 1 vertical per frame module.
Each vertical can mount ten (10) R399s. Each vertical can mount nine (9) R399s.
(9 if using jumper through) (8 if using jumper through)
Each vertical can mount ten (10) 89-style, Each vertical can mount nine (9) 89-style
Block 32, or “G” series terminal blocks. or Block 32 or “G” series terminal blocks.
(9 if using jumper through) (8 if using jumper through)
Each vertical can mount six (6) 2376 or Each vertical can mount five (5) 2376 or
2378 blocks. 2378 blocks.
Key Features
Description
• Single-sided system allows all
frame administration to be For protection, the frame mounts R399 100-pair central office connectors. For equipment
performed on one side terminations, the frame will mount the Emerson Block 32, Emerson 2376 block, or front-
facing line terminal blocks with 8-in. mounting centers. For building entrance applications,
the 2500 frame accommodates the R366 connector with 66-clip termination.
• Common jumper trough permits
short jumpers for labor savings The 2500 frame is comprised of two adjacent verticals separated by a vertical jumper
trough. Each vertical of the 8-ft. frame has ten block positions, which allows a maximum
• Modular design is easily expanded of 1000 protected pairs per vertical. What makes the frame so flexible, is that either an
R399, a line terminal block, or a horizontal jumper trough can be mounted in any block
• Frame is factory pre-assembled for position, allowing for any combination of protected and equipment blocks on each frame.
quick, easy installation
Multiple frames can be lined up and connected together to meet the required application
• Versatile block mounting can be size. Each frame module has jumper access to adjacent modules.
configured to all pair requirements
Application through the use of horizontal jumper troughs.
The 2500 frame is also available in a 7-ft. version, which has eight block positions.
Application
Multiple frames can be lined up and
connected together to meet the required
application size. Each frame module
has jumper access to adjacent modules
through the use of horizontal jumper
troughs.
Enterprise : 31
OSPDS-100500 / 0906
2500 Frame (Two Verticals) Single-Sided Distribution System
NOTE 1: The right vertical of the frame requires right mounted connectors (RZ399) and right mounted vertical terminal blocks.
NOTE 2: The R399 connector and the 2376 and 2378 blocks mount directly to the frame.
NOTE 3: Each Block 32 or 89-style front facing line terminal block requires a mounting bracket.
NOTE 4: Line terminal blocks are mounted vertically.
NOTE 5: Each Frame Module has 2 horizontal troughs.
NOTE 6: Ground bar & ground splice included.
NOTE 7: Adjacent frames should be mounted on 20-in. centers.
Capacities
2500FRAME (8-ft. frame) 25007FRAME (7-ft. frame)
2 verticals per frame module. 2 verticals per frame module.
Each vertical can mount ten (10) R399s. Each vertical can mount eight (8) R399s.
(9 if using jumper through) (7 if using jumper through)
Each vertical can mount ten (10) 89-style Each vertical can mount eight (8) 89-style
or Block 32 terminal blocks. or Block 32 terminal blocks.
(9 if using jumper through) (7 if using jumper through)
Each vertical can mount six (6) 2376 or Each vertical can mount five (5) 2376 or
2378 blocks. 2378 blocks.
Key Features
Description
• The 5-pin protector modules
protect personnel and equipment The 5-pin protector modules protect personnel and equipment from excessive voltages
from excessive voltages and and currents induced on telephone lines or local ground by lightning and AC power system
faults. All modules feature industry standard 5-pin bases for use in central office, remote
currents
terminal, building entrance, and customer premises applications. All modules are avail-
able with or without a heat coil to protect against sneak currents. When a sneak current is
• Modules feature industry standard induced on the line, the heat coil responds by permanently grounding the line to prevent
5-pin bases for use in central damage to line cards and sensitive equipment.
office, remote terminal, building
entrance, and customer premises Carbon Protector Modules feature a carbon air gap and fail-safe mechanism that shorts to
applications ground when a voltage exceeds its rating. A detent position disconnects the equipment
side while protecting the line side (OSP cable). These modules are used where transients
• All modules are available with are not frequent or cost is a major factor.
or without a heat coil to protect
against sneak currents Gas-Tube Protector Modules contain two-electrode high amperage ceramic non radioac-
tive gas-tube surge arresters and a fail-safe mechanism. These are used in areas where
frequent transient over voltages are a problem or where tightly controlled breakdown
• Carbon Protector Modules feature
values are required. The gas-tube will recover repeatedly from the overvoltage, providing
a carbon air gap and fail-safe 30 to 40 times longer life than carbon. The detent position disconnects the equipment
mechanism that shorts to ground side while protecting the line side (OSP cables). Modules are available with a secondary
when a voltage exceeds its rating vent-safe backup gap. Modules equipped with patented vent-safe gap are UL Listed (VS in
catalog). If a module is specified as a JZ-type, it is a next generation new gas-type version
• Gas-Tube Protector Modules that provides extended life and environmentally robust protection.
contain two-electrode high
amperage ceramic non radioactive Solid-state Modules contain state-of-the-art diodes intended for use with sensitive equip-
gas-tube surge arresters and a ment. They are available with 4 ohm (350mA) or 20 ohm (150 mA) heat coils. The diode
fail-safe mechanism is a fast semiconductor switch with operating voltage nearly independent of transient rise
time.
• Solid-state Modules contain
“RXXXX” Protector Modules have either a “B” or “C” as the third character in the catalog
state-of-the-art diodes intended number to denote special characteristics. Those with a B as the third character, i.e., R3B1E,
for use with sensitive equipment have a triangular-shaped recess molded into the base to accommodate the raised struc-
ture molded into the panel of AT&T® building entrance protectors.
Application
These protector modules provide overvoltage and
overcurrent protection for central office, remote
terminal, and building entrance/customer premises
applications. All protector modules provide a vent-
safe gap, are fail-safe, and meet UL requirements.
Specific models are designed to meet RDUP (for-
merly RUS) and Telcordia specifications.
Enterprise : 33
OSPDS-110500 / 0705
5-Pin Protector Modules
Ordering Information
Low Voltage Standard
Housing Solid-State Solid-State (300V)
Color & Size JZ Carbon (240V) R3B1S Service
Modules for Bell Operating Companies, No Heat Coil, Gold Plated Pins
Black, S R3B1EJZ R3B1A R3B1FS R3C1S Standard
Black w/test point, L R3C1EJZ R3C1FS R3B2S Standard
Green, S R3B2A R3B2FS R3C2S Service denial
Green w/test point, L R3C2FS R3B3S Service denial
Red, S R3B3EJZ R3B3A R3B3FS R3C3S Special
Red w/test point, L R3C3EJZ R3C3FS R3B4S Special
Yellow, S R3B4A R3B4FS R3C4S PBX battery
Yellow w/test point, L R3C4FS PBX battery
Gray, S R3B12A Continuity only
Ordering Information
Low Voltage Standard
— Solid-State (240V) — — Solid-State (300V) —
Housing Color JZ Carbon 4 Ohm 20 Ohm 4 Ohm 20 Ohm Service
Modules for Bell Operating Companies, Long Housing, with 4 or 20 Ohm Heat Coil, Gold Plated Pins
Black R4B1EJZ R4B1C R4B1FS RT4B1FS R4B1S RT4B1S Standard
Black w/test point R4C1EJZ R4C1C R4C1FS RT4C1FS R4C1S RT4C1S Standard
Green R4B2C R4B2FS RT4B2FS R4B2S RT4B2S Service denial
Green w/test point R4B3EJZ R4C2C R4C2FS RT4C2FS R4C2S RT4C2S Service denial
Red R4C3EJZ R4B3C R4B3FS RT4B3FS R4B3S RT4B3S Special
Red w/test point R4B4EJZ R4C3C R4C3FS RT4C3FS R4C3S RT4C3S Special
Yellow R4B4C R4B4FS RT4B4FS R4B4S RT4B4S PBX battery
Yellow with test point R4C4C R4C4FS RT4C4FS R4C4S RT4C4S PBX battery
White R4B9C R4B9FS RT4B9FS R4B9S RT4B9S Reverse tip & ring
White with test point R4C9C R4C9FS RT4C9FS R4C9S RT4C9S Reverse tip & ring
Gray R4B12C Continuity
Gray w/test point R4C12C Continuity only
34 : Enterprise
OSPDS-110500 / 0705
5-Pin Protector Modules
Ordering Information
Low Voltage Standard
Housing Three Solid-State Solid-State
Color Carbon Gas Element (240V) (300V) Specification
Other Modules—Short Housing, No Heat Coil, Tin Plated Pins
Black 3AB UL, RDUP (formerly RUS), GTE®
Red 3GURVS UL
Orange 6A20 RDUP (formerly RUS), GTE®
Black 6A20B RDUP (formerly RUS), GTE®
Red 6A20R RDUP (formerly RUS), GTE®
Black 3GB RDUP (formerly RUS)
Red 3GR RDUP (formerly RUS)
Orange 3G RDUP (formerly RUS)
Orange 6U2VS UL, RDUP (formerly RUS), GTE®
Black 6U2BVS UL, GTE®
Red 6U2RVS UL, GTE®
Orange 3GUVS UL, RDUP (formerly RUS)
Black 3GUBVS UL
Black S3ABF S3AB* UL, RDUP (formerly RUS)
Red S3ARF S3AR UL
Other Modules—Long Housing, with Heat Coil, Tin Plated Pins
Black 4AB UL, GTE®
Red S4ARF S4AR UL
Orange G4AVS UL, GTE®
Black G4ABVS UL, GTE®
Red G4ARVS UL, GTE®
Black S4ABF S4AB UL
* S3AB is RDUP (formerly RUS) accepted in our R399 connector and available for use in connector equivalents.
NOTE 1: See the Reference Standards Chart at the end of this section.
NOTE 2: Designed to meet Telcordia TR-TSY-000070, GR-1361-CORE, GR-974-CORE, and RDUP (formerly RUS) PE-80, PEG-1, PEG-3, PEG-7.
NOTE 3: All RDUP (formerly RUS) modules meet the criteria in Government Publication RDUP (formerly RUS) TE&CM 823.
Enterprise : 35
OSPDS-110500 / 0705
5-Pin Protector Modules
Key Features
Description
• Extended service life reduces
maintenance costs and subscriber The SuperDuty® JZ380 Series Next Generation of gas-tube station arresters and protec-
complaints tors incorporate an environmentally robust form of gas-tube technology in applications
that have an uncontrolled environment and severe lightning exposure. The electrical surge
endurance exceeds 3000 strikes without incidence.
• Vent-safe and fail-safe mechanisms
on arresters provide continued The 1305VSB and R108VSB arresters/protectors feature patented vent-safe and fail-safe
surge protection under adverse mechanisms that insure an automatic short to ground in the event of sustained or high
conditions current conditions. The components protect against moisture, corrosion and contami-
nants to provide an environmentally hardened protector that reduces service calls and
• Low noise eliminates noise extends protector life. The protectors comply with the specifications listed in the Telcordia
associated with carbon protectors Technical Audit Report #AU-148, Iss. 1, of September 1994.
• Environmentally robust to provide SuperDuty® JZ380 series 5-pin gas-tube protector modules are used in areas of frequent
extended life and protect against transient over voltages with controlled breakdown values, and where adverse environmen-
tal conditions are encountered. Gas-tube modules are available with or without heat coils
induced moisture corrosion per
that protect against sneak currents.
Telcordia Technical Audit Report
#AU-148, Iss. 1, September 1994
R3B1EJZ
Enterprise : 37
OSPDS-111500 / 0705
SuperDuty® JZ380 Series Next Generation Protectors
NOTE 1: See the Reference Standards Chart at the end of this section.
NOTE 2: Designed to meet Telcordia TR-TSY-000070, TR-TSY-000072, GR-1361-CORE, and GTE® GTS-8345.
NOTE 1: See the Reference Standards Chart at the end of this section.
NOTE 2: Designed to meet Telcordia TR-TSY-000070, TR-TSY-000072, GR-1361-CORE, and RDUP (formerly RUS) PE-80, and GTE® GTS-8345.
NOTE 3: All RDUP (formerly RUS) modules meet the criteria in Government Publication RDUP (formerly RUS) TE&CM 823.
NOTE 4: Heat coil R4_ _ _ Series = 4 Ohms.
Specifications
VSR2-types
VSB-types RDUP (formerly RUS) T-types International Specs
Electrical Telcordia Specs & GTE® Specs Telcordia Specs South America
Specifications TR-TSY-000070 & GR-1361-CORE PE-80 & GTS GR-974-CORE Pacific Rim
JZ Standard & Standard Standard
Standard Gas Performance JZ Performance Solid-State Low Voltage Gas
DC Breakdown 265V-600V 265V-600V 300V-500V 265V-400V 200V-300V
@ ≤ 2000V/s @ 1 mA
(400V nominal) (350V-380V nom) (350V-400V nom) (300V nominal) (250V-260V nom)
Impulse 1000V max. 650V max. 300V-750V 400V max. 700V max.
@ 100V/µs
DC Holdover < 150 ms < 150 ms < 150 ms < 150 ms
@ 150V min. Typical < 10 ms Typical < 10 ms Typical < 10 ms Typical < 10 ms N/A
DC Holdover < 200 ms
@ 115V min. N/A N/A N/A N/A Typical < 200 ms
Insulation > 100 MΩ > 100 MΩ > 100 MΩ > 100 MΩ > 100 MΩ
Resistance
Capacitance
< 5 pf < 5 pf < 5 pf N/A N/A
<30 pf < 20 pf < 30 pf < 200 pf < 20 pf
Impulse Life 1000 LTS @ 10A *Unlimited @ 10A 400 LTS @ 500A *Unlimited @ 10A N/A
LTS = Surges 100 LTS @ 100A 300 LTS @ 100A *Unlimited @ 100A
@ (10/1000 µs) 50 LTS @ 300A 50 LTS @ 300A Failsafe @ 10KA
@ (10/250 µs) 25 LTS @ 2000A 25 LTS @ 2000A
@ (20/100 µs) 2 LTS @ 5000A 2 LTS @ 5000A
@ (8/20 µs) 1 LTS @ 20KA 1 LTS @ 20KA
AC Surge Life 0.5Arms 30s 0.5Arms 30s 65Arms 11 cycles 0.5Arms 30s 0.5Arms 30s
10Arms 1s, 60Hz 65Arms 11 cycles 10Arms 1s, 60Hz 65Arms 11 cycles
1Arms 1s, 60Hz 10Arms 1s, 60Hz 1Arms 1s, 60Hz 15Arms 15 min.
1Arms 1s, 60Hz
End Life Limits
<10 MΩ <10 MΩ <1 MΩ <10 MΩ <10 MΩ
<265V or >750V <265V or >600V <180V or >600V <265V <200V
>1000V >800V >900V >400V >900V
Vented >1000V (95%) >1000V (95%) <1500V N/A N/A
(back-up) 1200V max. 1200V max. (avg. 1000V-1200V)
Breakdown @ 100V/µs @ 100V/µs
Enterprise : 39
OSPDS-113700 / 0705
Reference Standards Chart
Key Features
Description
• Sealed or Ventilated Design —
provides superior protection of The DEC25 “Next Generation” family of enclosures have been specifically designed with
equipment, cables, and splices today's distributed network architecture in mind. New “urban design guidelines” now require
network providers to make their POPs smaller, quieter and more cosmetically pleasing, while
still maintaining the same levels of network reliability and service, as in the past. The DEC25
• Small, lightweight cabinets —
family offers the user the unique ability to customise your network deployment to meet
meet or exceed new “Urban these stringent new requirements. The different sizes, compact profiles, low operating noise
Design Guideline” requirements levels, and clean lines make the deployment of the DEC25 family much easier than traditional
larger enclosures.
• Multiple Cooling Options —
cost effective solutions for any Three sizes of the DEC25 are available. All enclosures are constructed of welded heavy gauge
application aluminium and are designed to withstand the most severe environmental conditions. They
each will economically house a wide variety of sensitive electronic equipment in any outdoor
• Welded Aluminum environment.
Construction — Dependable,
The DEC25-8 is the smallest unit in the family measuring only 27" tall. The enclosure has (8)
durable, offering a long, corrosion-
EIA 1.75" equipment rack space available for equipment mounting. The DEC25-8 is ideal for
resistant, problem-free service life
small remote sites where up to 150 individual lines may be required. The DEC25-17 is the
mid-size unit and measures 42" tall. This enclosure has (17) EIA 1.75" equipment rack space
• Flexible Design — available for equipment mounting. The DEC25-17 is ideal for remote sites where the line
Applications for wireless, wireline requirements could be as high as 384 individual ports. The largest unit in the family is the
and CATV DEC25-27, which measures 60" tall. This enclosure has (27) EIA 1.75" equipment rack space
available for equipment mounting. Again the DEC25-27 fits most applications needing more
• Modular Design — than 384 lines. Any of these cabinets can be pole or pad mounted using special mounting
provides for craft separation and kits.
configuration flexibility
Depending on regulatory requirements, the external operating conditions and the equip-
ment operating parameters, any of the DEC25 enclosures can be equipped with one of four
optional cooling options. These include convection cooling, forced air cooling, heat exchang-
er cooling and HVAC cooling.
Application
The DEC25-8, DEC25-17 or DEC25-27 cabinets are a family of durable yet economical priced
enclosures. They are specifically designed to house a wide variety of sensitive electronic
equipment in any outdoor application. The cabinets are designed with optional cooling
modules that allow equipment to be housed in a sealed, dust free environment. Or for appli-
cations where less stringent environmental requirements are needed, any of the cabinets can
be equipped with less costly fans and baffles for cooling the cabinet. Our simple yet innova-
tive cooling designs have been tested and verified to the highest industry standards.
Specific applications for the DEC25 family include: DSLAM adjunct sites, digital loop carrier
systems, microwave sites, auxiliary battery cabinets, fibre optic hub sites and radio equip-
ment cabinets for wireless applications.
Enterprise : 41
OSPDS-127100 / 1005
DEC25/NG “Next Generation” Digital Equipment Cabinet
* To obtain the overall height of the cabinet, all three of these component heights must be added together.
** To obtain the overall weight of the cabinet, all three of these component weights must be added together.
* To obtain the overall height of the cabinet, both of these component heights must be added together.
** To obtain the overall weight of the cabinet, both of these component weights must be added together.
* To obtain the overall height of the cabinet, all of these component heights must be added together.
** To obtain the overall weight of the cabinet, all of these component weights must be added together.
42 : Enterprise
OSPDS-127100 / 1005
DEC25/NG “Next Generation” Digital Equipment Cabinet
Specifications
Finish
Platinum gray
Access
Front door
Rear door
Removable battery chamber panels
Cooling
Options Convection cooling kit
330 cfm fan kit (-48, +24 vdc or 120 vac)
Heat exchanger kit (600 watt or 1200 watt)
HVAC kit (1500, 3500 or 5000 BTU)
Electrical
Standard 4-in. x 4-in junction box with surge protector and GFI receptacle
Optional 4 or 8 position 120/240 vac, 60 Hz, load center
Alarms
High temperature = 49˚C
Low temperature = 5˚C
Front Door Intrusion
Rear Door Intrusion
Mounting
Pad-mount (optional kits required)
Pole-mount
Wall-mount
Rack Space
Single, center mount 23-in. wide rack system (19-in. optional)
1.75-in. EIA spacing standard (1.00-in. spacing optional)
untapped holes for 12-24 hardware
DEC25-8 = 14.00-in. of rack space (8 RU)
DEC25-17 = 29.75-in. of rack space (17 RU)
DEC25-27 = 47.25-in. of rack space (27 RU)
Approvals
CSA
UL
GR-487 (as applicable)
Enterprise : 43
OSPDS-127100 / 1005
DEC25/NG “Next Generation” Digital Equipment Cabinet
Ordering Information
Model Number Part Number List Number Description
DEC25-8/NG F787652 Common equipment wiring and assembly for a basic DEC25 cabinet. Including racks, wind
DEC25-17/NG F787653 List 00 latches, ground bar, single point cabinet ground lug, frame ground system, weather
DEC25/27/NG F787654 gasketing, insulation, document holder, lifting eyelets, solar shield
Next Generation Mounting brackets, alarm termination strip, grounded cable entry plate,
DEC25 cabinet assemblies (1) cable nozzle, assembly labour
List 05 115 vac, 60 Hz Cabinet AC Kit; wiring and assembly of a 4-in. x 4-in. splice box, (1) 15 amp, 115 vac
duplex receptacle and (1) 15 amp 115 vac GFI receptacle, (1) surge arrestor, sealed flexible AC con-
duit.
List 06 220 vac, 50 hz Cabinet AC Kit; wiring and assembly of a 4-in. x 4-in. splice box, (1) 3 position AC ter-
minal block, (1) Joslyn surge arrestor, sealed flexible AC conduit.
List 07 11.00-in. Welded Pad-Mounting Base Assembly
List 08 6.00-in. Pad-Mounting Feet Assembly
List 09 Side Mounted, Pole-Mounting Kit
List 12 Fixed Battery Tray for use with List 07 Base Frame
List 20 DEC25 Alarm Kit e/w (2) intrusion alarms, (1) high temp alarm, (1) low temp alarm, (1) 8 pair screw-
down termination strip
List 21 Cabinet Sealing Kit
List 22 Cabinet Filter Kit
List 29 Insulation Kit for the DEC25-17/NG
List 41 Cabinet Entry and Installation Tool Kit
List 45 +24 vdc fan kit for use in List 00
List 46 -48 vdc fan kit for use in List 00
List 47 120 vac fan kit for use in List 00
List 50 8 amp, -48 vdc Modular Rectifier System
List 51 2 amp, -48 vdc Rectifier Module for list 50
List 52 Air Circulation Fan Rack System for list 50
List 56 Battery Temperature Compensation Unit for list 50
List 60 -48 vdc, 600 watt Heat Exchanger
List 70 1500 BTU HVAC Kit
List 71 3500 BTU HVAC Kit
List 72 5000 BTU HVAC Kit
List 75 Pole-Mount Chair Assembly Kit
List 80 Battery Tray Heater Kit for list 12
List 82 Slide Out Battery Tray for use with List 07 Base Frame
List 84 Battery Tray Heater Kit for list 82
List 86 4 Position, 30 amp, 120/240 vac Load Center
List 95 110 pair Protection Panel Assembly
List 100 18 amp, -48 vdc Modular Rectifier System
List 105 60 amp, -48 vdc Modular Rectifier System
List 120 8 Position, 60 amp, 120/240 vac Load Center
Key Features
Description
• Sealed design — protects
equipment from water and dust, The MESA® 4 closure is the latest solution to today's outside plant demands. Due to the
while maintaining a cool operating sophisticated nature of electronic systems being deployed in today’s outside environ-
ment, efficient thermal management is increasingly critical to their operation. Emerson
environment
has created an innovative heat exchanger cooling system, which keeps electronics from
exceeding their optimal temperatures, yet never introduces outside air and pollutants into
• Flexible design — cabinet the equipment chamber.
modules can be configured to
accommodate most telephone, In addition, MESA® is designed to withstand the most severe environmental conditions,
CATV, and wireless applications providing maximum protection for your equipment investment. MESA® is thoroughly
tested against dust and water intrusion and exceeds even the most stringent industry
• Powder paint process — provides standards.
a harder finish while eliminating
the release of harmful VOCs into MESA® is also extremely flexible. A modular approach is taken wherever possible so the
the environment cabinet can be quickly configured to meet your exact requirements. Optional “modules”
include a battery drawer, commercial power panel, fiber splicing system, and overvoltage
protection panels.
• Separate battery compartment —
provides additional space for
revenue-producing equipment
and separates batteries from heat Application
generating electronics
The MESA® 4 Cabinet can economically house a variety of next generation electronic
• Compartmentalized design — equipment including Digital Loop Carriers (DLCs), fiber optic transport systems, and radio
equipment for wireless applications.
for craft separation and
configuration flexibility
• Telcordia GR-487 —
CORE Issue 2 compliant
Enterprise : 45
OSPDS-122500 / 1005
MESA® 4 NxT Modular Electronic Sealed Architecture
Dimensions
Catalog
Number H W D
MESA® 4 (overall exterior dimensions) 75-in. 93-in. 46-in.
Chamber Area Dimensions
Equipment Chamber (interior dimensions) 52.5-in. 55.5-in. 42-in.
End Chamber (splice & power chamber) 52.5-in. 42-in. 13.7-in.
46 : Enterprise
OSPDS-122500 / 1005
MESA® 4 NxT Modular Electronic Sealed Architecture
Specifications
Enclosure Mounting
Enclosure Pad-mounted
Equipment Mounting
Total mounting space 216-inches of rack space
(two 49.5-inch and two 48-inch EIA rack units in the equipment
chamber and one 21-inch mini rack in the power chamber)
Hole spacing on racks 1.0-inch spacing (EIA 1.75-in spacing available)
untapped holes for 12-24 thread forming hardware
Rack widths 23-inch EIA standard
Center mounting Accepts standard 12-inch deep, center mount equipment
(5-inch front, 7-inch rear)
Environmental Protection
Finish Off-white, polyester powder coat
Thermal Protection
Heat exchanger Two, 23-inch Heat Exchanger
Temperature fans turn on at: 90° F
High temperature alarm will sound at: 150° F
Heat dissipation 3200/ 3600/ 4600 Watt options
(based upon impedance of installed equipment)
Electrical
AC System 8-position power distribution panel with AC distribution to power shelf
Convenience Outlets (GFCI protected) Two in the equipment chamber (one per side)
One each in the power chamber and splice chamber
Battery heater pad kit (optional) Thermostat control “On” at 40° F, “Off” at 60° F
Compatible batteries & amp-hour reserve Quantity (6) strings of 4-12 VDC 155 A-Hr front post batteries (48VDC string)
FIAMM®, GNB, C & D, etc.
Security
Padlockable 216-type tool
Intrusion alarm Intrusion alarm with local indication and remote location options
Bonding and Grounding
Two 10-position, dual holed L49, copper buss, 3/16-in. thick,
1/4-20 hardware. One each in power chamber and splice chamber
Cable Entrance
Four, 4-inch cable entrance ports in splice chamber
Two, 4-inch cable entrance ports in power chamber
(cable dressing bracket provided with protection panel kit)
Dimensions and Weights
Overall Exterior (H x W x D) 75" x 93" x 46.0"
Equipment Chamber (H x W x D) 52.5" x 55.5" x 42.0"
End Chambers (H x W x D) 52.5" x 42.0" x 13.7"
Weight 1485 lbs. (unequipped)
Enterprise : 47
OSPDS-122500 / 1005
MESA® 4 NxT Modular Electronic Sealed Architecture
Key Features
LORAIN® eXpandable, Integrated Power —
• Compact integrated system — the next generation small power platform from
holds up to 96 amps at 54.48V
(9kw) in 2 rack spaces Emerson providing expandable power, distribution,
control and monitoring in a compact package.
• Constant power option —
delivers more current at lower
voltages to meet load or
recharge demand
Description
The LORAIN® eXpandable Power (LXP) System is composed of one to three rectifier
• Rugged design — rated for modules, each arranged for up to three 1750 watt constant power rectifier modules. A
continuous operation from -40°C centralized controller forms the heart of the system, featuring web-based software, user-
to +80°C programmable inputs and alarms, remote access and battery management. The integrated
distribution shelf is designed for up to four plug-in fuse holders or breakers rated 1 to
• Complies with industry 100 amps to meet load distribution requirements as well as ten GMT fuse positions. An
standards — NEBS™ level 3 optional 6-position GMT fuse module is available for additional GMT loads. A low-voltage
certified and UL Listed disconnect circuit can be configured for battery or load disconnect. The LXP system is a
cost-effective solution for loads under 5.2 Kw. This system is designed for tighter cabinet
• Extensive battery powering needs as well as Customer Premise FTTx applications.
management — includes health,
reserve time remaining, and
discharge test capability
Enterprise : 49
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System
Application
LXP systems are rated for continuous opera- integrated system. The system is designed shelters. Specific applications include: DLC,
tion from -40°C to +80°C and are NEBS™ for deployment in central office, POP sites, xDSL, DSLAM, FITL electronics, broadband
Level 3 certified and UL Listed. 23-inch co-location sites, customer premises, out- communications, multiplexers, PCS, micro-
cabinet configurations are available for this door cabinets, CEVs, vaults or portable wave and PBX.
50 : Enterprise
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System
Rectifier Shelves
LXP Integrated rectifier shelves are 3.5" (2
RU) high, 12" deep and are available in 23"
widths. The 23" rack mounts up to 3 recti-
fier modules or 2 rectifier modules plus
a modular ring generator. These shelves
provide front to back ventilation and
can be mounted directly above or below
other electronic equipment, maximizing
LXP Integrated System revenue-generating space. Each unit will
operate from 120/208/240VAC and is
equipped with a single input to accommo-
date a line cord or hard wiring. DC output
connection options for each shelf include
dual two-hole compression lugs or bus
bar terminations for connection to local or
remote distribution and batteries. The shelf
with rectifiers is NEBS™ Level 3 certified,
UL Listed and meets FCC Class B EMI/RFI
requirements.
Rectifier Modules
LXP rectifiers are rated for up to 1750-watt
constant output power when operated at
208/240VAC nominal input, 38.0 amps
at 46VDC to 30.1 amps at 58VDC. When
operated at 120VAC nominal input the out-
put power is rated at 750 watts, 16.3 amps
at 46VDC to 12.9 amps at 58VDC. The
rectifier will provide up to 100% of rated
power at 65°C. As the temperature increas-
es from 65°C to 80°C, the thermal power
limit circuit linearly decreases power. In
LXP Rectifier Module
the typical operating range, these recti-
fiers have a power factor greater than .99,
total harmonic distortion less than 5% and
efficiencies greater than 91%. Each hot-
swappable rectifier has an integral cooling
fan and a tri-color LED status indicator.
Enterprise : 51
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System
52 : Enterprise
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System
Specifications
Input
Voltage Nominal 120/208/240 volts AC, single phase, 50/60 Hz, with a range of 84 to 286 volts.
Extended range to 300 volt AC without damage.
Current 9.23 amps@208VAC, 8.01 amps@240VAC per PCU, 54.48VDC, 1750 watts output
8.09 amps@208VAC, 7.00 amps@240VAC per PCU, 54.48VDC, 1500 watts output
20.38 amps@208VAC, 20.59 amps@240VAC per feed (3 PCUs), 54.48VDC, 4500 watts output
23.79 amps@208VAC, 24.03 amps@240VAC per feed (3 PCUs), 54.48VDC, 5250 watts output
35 amp breaker recommended per feed (1750W rectifier), 30 amp breaker recommended per feed (1500W rectifier)
10.91 amps@176VAC, 1750 watts output (worst case) 32.76 amps@176VAC (worst case) per feed (3 PCU’s)
9.35 amps@176VAC, 1500 watts output (worst case) 28.05 amps@176VAC (worst case) per feed (3 PCU’s)
6.94 amps@120VAC per PCU, 54.48VDC, 750 watts output
20.83 amps@120VAC per feed, 54.48VDC, 2250 watts output
9.92 amps@84VAC, 750 watts output (worst case) per PCU; 29.75 per feed
Inrush Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage within the
rated input voltage range.
Frequency 45-65 Hz
Protection Shelf input is wired for a Single AC input. The first feed will power PCU’s 1, 2, and 3. If the AC input voltage
decreases or increases beyond a non-adjustable predetermined value, the PCU power conversion circuitry
inhibits, disabling PCU output. The PCU will recover automatically when the AC input voltage is re-established
within specifications limits.
Power Factor Typical power factor greater than or equal to 99% for any load greater than or equal to 50% of rated full load
at nominal line. Meets IEC 1000–3–2.
Operating Efficiency Typical operating efficiency 92%
Output
Voltage Nominal -48 volts DC, positive ground, adjustable from -46.0 to -58.0 volts DC
Current 29 to 38.0 amps per PCU (1750 Watt ), 25 to 32.6 amps per PCU (1500 Watt),
up to a total of 87 to 114 amps per shelf with three PCUs installed in the main shelf.
Power 1,750 watts maximum (1750 Watt PCU) and 1,500 watts maximum (1500 Watt PCU). The PCU employs a
constant power limiting feature which limits the maximum output power to 1,750 or 1500 watts over the
output voltage range of -46.0 to -58.0VDC.
Regulation Steady state output voltage remains within ±0.5% of any voltage within the range of 46.0 to 58.0 volts DC
for any combination of frequency, input voltage, and load from no load to full load over the temperature
range of -20°C to +65°C (-4°F to +149°F).
Filtering On or off battery
Voice Band Noise Less than 32 dBrnC
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 30 mv rms
Psophometric Noise Does not exceed 1 mv
Enterprise : 53
PPB-SDCP-068 / 1206
LORAIN® XP 4890
DC Power System
Specifications (continued)
Protection
Current Limiting Maximum output current of each PCU can be set from 2.5 to 32.6 amps (1500 Watt) or 38.0 amps (1750 Watt)
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately three
seconds, the PCU automatically restarts.
Monitoring
Status/Alarm Indicators Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed
on the 2 Line 20-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature -40°C to +65°C (-4°F to +149°F); -40°C to +80°C (-40°F to +176°F) derated to zero output linearly
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation of 10,000
feet (3,048m) above sea level. For elevations between 3,000 feet (914m) and 10,000 feet (3,048m), derate
the maximum operating ambient temperature linearly.
Ventilation Variable speed fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class B and EN55022 Class B, radiated and conducted.
Audible Noise 2 feet from any vertical surface; does not exceed 65dBA, 55dBA with low fan speed selected.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 3.5" (8.89cm) x 3.125" (7.937cm) x 12" (30.48cm)
Weight 6 lbs. (2.239 kg)
Safety Compliance UL recognized (UL 1950), CSA 22.2, No.950, CE
Additional Information
For additional specification, engineering and
installation information, request specification
number 589800300 for the 23" (58.42 cm)
option.
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
54 : Enterprise
PPB-SDCP-068 / 1206
LORAIN® XP 48500 DC Power for
Business-Critical Continuity
DC Power System
Key Features
LORAIN® eXpandable Power (LXP), the next
• Compact expandable
system — holds up to 165 amps at
generation small power platform from Emerson
54.48V (9kw) in 2 rack spaces and providing expandable power, distribution,
468 amps at 54.48V (25.5kw) in 6
rack spaces
control and monitoring.
• Extensive battery
management — includes health,
reserve time, and
test capability
Enterprise : 55
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System
Application
LXP systems are rated for continuous opera- The system is designed for deployment in applications include: DLC, xDSL, DSLAM,
tion from -40°C to +80°C and are NEBS™ central office, POP sites, co-location sites, FITL electronics, broadband communica-
Level 3 certified and UL Listed. 19 or 23- customer premises, outdoor cabinets, tions, multiplexers, PCS, microwave and
inch cabinet configurations are available. CEVs, vaults or portable shelters. Specific PBX.
56 : Enterprise
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System
Rectifier Shelves
LXP rectifier shelves are 3.5" (2 RU) high,
12" deep and are available in 19" or 23"
widths. The 19" rack mounts up to 5 rec-
tifier modules and the 23" rack mounts
up to 6 rectifier modules. These shelves
provide front to back ventilation and can
be stacked up to 3 high with zero clear-
ance above or below units, maximizing
revenue-generating space. Each unit will
operate from 120/208/240VAC and is
equipped with dual inputs to accommo-
date line cords or hard wiring. DC output
connection options for each shelf include
LXP System
dual two-hole compression lugs or bus
bar terminations for connection to local or
remote distribution and batteries. The shelf
with rectifiers is NEBS™ Level 3 certified,
UL Listed and meets FCC Class B EMI/RFI
requirements.
Rectifier Modules
LXP rectifiers are rated for 1500 watt
constant output power when operated at
208/240VAC nominal input, 32.6 amps
at 46VDC to 25.8 amps at 58VDC. When
operated at 120VAC nominal input the out-
put power is rated at 750 watts, 16.3 amps
at 46VDC to 12.9 amps at 58VDC. The
rectifier will provide up to 100% of rated
power at 65°C. As the temperature increas-
es from 65°C to 80°C, the thermal power
LXP Rectifier Module limit circuit linearly decreases power. In
the typical operating range, these recti-
fiers have a power factor greater than .99,
total harmonic distortion less than 5% and
efficiencies greater than 91%. Each hot-
swappable rectifier has an integral cooling
fan and a tri-color LED status indicator.
Enterprise : 57
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System
58 : Enterprise
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System
Specifications
Input
Voltage Nominal 120/208/240 volts AC, single phase, 50/60 Hz, with a range of 84 to 286 volts.
Extended range to 300 volt AC without damage.
Current 7.92 amps@208VAC, 6.87 amps@240VAC per PCU, 54.48VDC, 1500 watts output
23.76 amps@208VAC, 20.6 amps@240VAC per feed (3 PCUs), 54.48VDC, 4500 watts output
30 amp breaker recommended per feed
9.36 amps@176VAC, 1500 watts output (worst case) 28 amps@176VAC (worst case) per feed (3 PCUs)
6.94 amps@120VAC per PCU, 54.48VDC, 750 watts output
20.83 amps@120VAC per feed, 54.48VDC, 2250 watts output
9.92 amps@84VAC, 750 watts output (worst case) per PCU; 29.75 per feed
Inrush Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage within the rated
input voltage range.
Frequency 45-65 Hz
Protection Shelf input is wired for a Dual AC input. The first feed will power PCUs 1, 3, and 5, while the second feed
will power PCU’s 2, 4, and 6. If the AC input voltage decreases or increases beyond a non-adjustable
predetermined value, the PCU power conversion circuitry inhibits, disabling PCU output. The PCU will
recover automatically when the AC input voltage is re-established within specifications limits.
Power Factor Typical power factor greater than or equal to 99% for any load greater than or equal to 50% of rated full load
at nominal line. Meets IEC 1000–3–2.
Operating Efficiency Typical operating efficiency 91% at full load
Output
Voltage Nominal -48 volts DC, positive ground, adjustable from -46.0 to -58.0 volts DC
Current 25 to 32.6 amps per PCU, up to a total of 125 to 163 amps per shelf with five PCUs installed in the main
shelf and up to a total of 150 to 195.6 amps per shelf with six PCUs installed in each supplemental shelf.
Power 1,500 watts maximum. The PCU employs a constant power limiting feature which limits the maximum output
power to 1,500 watts over the output voltage range of –46.0 to -58.0VDC.
Regulation Steady state output voltage remains within ±0.5% of any voltage within the range of 46.0 to 58.0 volts DC
for any combination of frequency, input voltage, and load from no load to full load over the temperature
range of -20°C to +65°C (-4°F to +149°F).
Filtering On or off battery
Voice Band Noise Less than 32 dBrnC
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 30 mv rms
Psophometric Noise Does not exceed 1 mv
Enterprise : 59
PPB-SDCP-001 / 1206
LORAIN® XP 48500 DC Power System
Specifications (continued)
Protection
Current Limiting Maximum output current of each PCU can be set from 2.5 to 32.6 amps
High Voltage Shutdown If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately three
seconds, the PCU automatically restarts.
Monitoring
Status/Alarm Indicators Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed
on the 2 Line 20-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature -40°C to +65°C (-4°F to +149°F); -40°C to +80°C (-40°F to +176°F) derated to zero output linearly
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation of 10,000
feet (3,048m) above sea level. For elevations between 3,000 feet (914m) and 10,000 feet (3,048m), derate
the maximum operating ambient temperature linearly.
Ventilation Fan-cooled front to rear
EMI/RFI Suppression Conforms to FCC rules Part 15, Subpart B, Class B and EN55022 Class B, radiated and conducted
Audible Noise 2 feet from any vertical surface; does not exceed 65dBA, 55dBA with low fan speed selected.
Physical Characteristics
Mounting Plug-in installation
Dimensions (H x W x D) 3.5" (8.89cm) x 3.125" (7.937cm) x 12" (30.48cm)
Weight 6 lbs. (2.239 kg)
Safety Compliance UL recognized (UL 1950), CSA 22.2, No.950, CE
Additional Information
For additional specification, engineering and installation information, request specification number 582135100 for the 19" (48.26 cm) option
and number 582135000 for the 23" (58.42 cm) option.
For ordering information, request SAG582135000 for the 23" and SAG582135100 for the 19" option.
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
60 : Enterprise
PPB-SDCP-001 / 1206
LORAIN® CIP 4890/48120 DC Power for
Business-Critical Continuity
DC Power System
Key Features
Enterprise : 61
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
Application
The LORAIN® CIP power system is The system is designed to supply a filtered
designed to be mounted in standard 19" or and regulated -48Vdc source to any tele-
23" frames, or used in embedded applica- communication equipment requiring up
tions with standard 19" or 23" mounting, to 80 amps redundant capacity in a 23"
with or without batteries. The system is shelf or up to 54 amps redundant capacity
rated for full continuous operation from - in a 19" shelf, such as POP sites, customer
40°C to +65°C and is NEBS™ Level 3 certified premises, outdoor cabinets, CEVs, vaults or
and UL(60950 & 1801). shelters. Specific applications include: DLC,
xDSL, DSLAM, broadband communications,
multiplexers, microwave and PBX.
System Shelf
The LORAIN® CIP shelves are 5.25" (3U) high, nectivity options for single phase 110/120
13" deep and 23" or 19" wide. The 23" wide and 208/240VAC feeds. The AC supply can
shelf mounts four rectifier modules and be connected to the shelf through IEC320
a Multi-Function Module. The 19" wide AC receptacles at rear side of the shelf, or
shelf mounts three rectifier modules and a through an AC interface box with IEC320 AC
Multi-Function Module. The shelves provide receptacles at the front left of the shelf for
front to back ventilation with zero clearance front access applications. The 23" wide shelf
LORAIN® CIP 4890 System Shelf required above or below. can also be configured with four connections
for conduits at the rear or with dual or single
Each rectifier position provides interconnec- connectivity at the front for conduit(s). The
tion points for the AC input, the DC output, 19" wide shelf offers a single AC rear access
and the control and alarm data bus (CAN connectivity, with conduit.
protocol). Each shelf provides a variety of con-
62 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
Rectifier Modules
The LORAIN® CIP system uses 1500W or In the typical operating range, the recti-
750W constant power switch mode rectifier fiers have a power factor greater than .99,
modules. Both rectifiers have a DC operat- total harmonic distortion less than 5% and
ing range of -43.0 to -58.5VDC. The 1500W efficiencies of 91%. The rectifiers are hot
module provides 1500W from 200 to swappable and have an integrated speed
300VAC with current limiting at 34 amps. controlled field replaceable fan. Each recti-
Output power is de-rated to 90% from 176 fier can optionally be equipped with a field
to 200VAC, to 60% at 120VAC, and to 50% replaceable air filter. Three LED indicators
at 100VAC. The 750W module provides provide visual status of normal operation,
750W from 100 to 300VAC with current alarm, rectifier failure alarm, and fan failure
limiting at 17 amps. Both rectifiers provide alarm.
up to 100% of rated output up to 75°C.
1500W Rectifier Module
Controller Modules
Two controller modules are available for use (RJ45 jack). The following battery manage-
in the LORAIN® CIP system – a basic control- ment capabilities are provided: battery
ler and an advanced controller. The System database, temperature compensation,
Manager IP is the advanced controller. It has equalize, battery discharge test, and charge
a graphical LCD display with four navigation control.
keys. The local alarm display uses LED indica-
tors for controller status and system major The Controller IP is the basic controller
and minor alarms. Eight user programmable available with the LORAIN® CIP system. The
input ports and eight user programmable operational features of the Controller IP are
Controller IP output ports with form C contacts are as follows: local alarm display by means of
included. In addition to traditional system three LED indicators, three alarm outputs
alarms and controls, the System Manager (dry C contacts), and two sets of local test
IP provides event and alarm history logs, an points for the measurement of the system’s
inventory log, and delivered DC power calcu- voltage and current. DIP switches are used
lation. The System Manager IP can to adjust float voltage, temperature com-
be accessed locally or remotely using a built- pensation, and the optional low voltage
in web based Graphical User Interface. Local disconnect.
connection is made through the Ethernet
port using a computer equipped with a web
browser and crossover cable. Remote con-
nection is made through a dial up network
System Manager IP connection with a modem connected to
the system’s RS-232 port, or through a
network LAN connection to the TCP/IP port
Enterprise : 63
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
64 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
Enterprise : 65
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
66 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
Enterprise : 67
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
68 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
Enterprise : 69
PPB-ES-73400 / 1206
LORAIN® CIP 4890/48120
DC Power System
Controller Specifications
Controller IP
Display LED status interface
Alarm output 3 dry C contacts outputs (Major, Minor, AC failure/BOD)
Alarm input One external input for distribution and battery fuse alarm
Control of rectifiers Digital CAN bus
System configuration Dip switches for:
System (float) voltage
Temperature compensation battery charging
Low voltage disconnect
Battery management Low Voltage Disconnect (LVLD or LVBD)
Temperature compensation battery charging
System Manager IP
Display LCD display with four navigation buttons
Alarm output 8 dry C contacts (5 programmable)
SNMP & Web (HTML)
Alarm input 8 programmable inputs
Control of rectifiers Digital CAN bus
Battery management Battery Discharge Test
Charge Control
Low Voltage Disconnect (LVLD or LVBD)
Temperature compensation battery charging
Equalize (boost)
System configuration Embedded Web Browser (HTTP)
Communications ports RJ45 jack for Ethernet port (TCP/IP)
DB9 connector for RS-232
Remote access All essential functions and operational parameters through RS-232 modem and TCP/IP Ethernet with
password security
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
70 : Enterprise
PPB-ES-73400 / 1206
LORAIN® CSP 48300 DC Power for
Business-Critical Continuity
DC Power System
Key Features
• Compliant with global A second power shelf that accommodates up to six 750W or 1500W plug-in rectifiers and
standards — delivers quality, a second distribution panel with 26 plug-in positions for load protection devices can be
performance and dependability added to increase the distribution position capacity. An optional low voltage disconnect
no matter what the application or can be configured for battery or load disconnect.
location demands
Enterprise : 71
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
Application
The LORAIN® CSP power system is a The system is designed to supply a filtered
front access system designed to be and regulated -48VDC source to any tele-
mounted in standard 23" frames or used in communication equipment requiring up to
embedded applications with standard 23" 300 amps capacity such as POP sites, cus-
mounting, with or without batteries. The tomer premises, outdoor cabinets, CEVs,
system is rated for full continuous opera- vaults or shelters, and small Central Offices.
tion from -40°C to +50°C (with excursions Specific applications include: DLC, xDSL,
to 65°C) and is NEBS™ Level 3 certified and DSLAM, broadband communications, mul-
UL(60950 & 1801). tiplexers, radio base stations, microwave
and PBX.
Power Shelves
The LORAIN® CSP power shelves are feeds, one for rectifiers 1, 3 and 5, and one
5.25" (3U) high, 13" deep and 23" wide. for rectifiers 2, 4 and 6 (on the initial power
The initial power shelf mounts five rectifier shelf, position No. 6 is for the controller).
modules and a controller module. The AC supply can be brought into the shelf
LORAIN® CSP power shelves The supplementary shelf mounts 6 rectifier through knockouts at the left rear side of
modules. The shelves provide front to back the shelf, or through an optional AC inter-
ventilation with zero clearance required face box at the front left of the shelf for
above or below. front access applications. DC output con-
nection between shelves and distribution
Each rectifier position provides intercon- panels is made through internal bussing.
nection points for the AC input, the DC
output, and the control and alarm data bus
(CAN protocol). The total output capacity
is 150 amps for the initial shelf and 180
amps for the supplementary shelf. Each
shelf provides connecting points for dual
single phase 110/120 and 208/240VAC
72 : Enterprise
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
Rectifier Modules
The LORAIN® CSP system uses 1500W In the typical operating range, the recti-
or 750W constant power switch mode fiers have a power factor greater than
rectifier modules. Both rectifiers have a .99, total harmonic distortion less than
DC operating range of -43.0 to -58.5VDC. 5% and efficiencies of 91%. The rectifiers
The 1500W module provides 1500W are hot swappable and have an integrat-
from 200 to 300VAC with current limit- ed speed controlled field replaceable fan.
ing at 34 amps. Output power is de-rated Each rectifier can optionally be equipped
to 90% from 176 to 200VAC, to 60% at with a field replaceable air filter. Three
120VAC, and to 50% at 100VAC. The LED indicators provide visual status of
1500W Rectifier Module
750W module provides 750W from 100 normal operation, alarm, rectifier failure
to 300VAC with current limiting at 17 alarm, and fan failure alarm.
amps. Both rectifiers provide up to 100%
of rated output up to 75°C.
Controller Modules
Two controller modules are available for network connection with a modem con-
use in the LORAIN® CSP system – a basic nected to the system’s RS-232 port, or
controller and an advanced controller. through a network LAN connection to
The System Manager SP is the advanced the TCP/IP port (RJ45 jack). The follow-
controller. It has a graphical LCD display ing battery management capabilities are
with four navigation keys. The local alarm provided: battery database, temperature
display uses LED indicators for control- compensation, equalize, battery dis-
ler status and system major and minor charge test, and charge control.
alarms. Eight user programmable input
ports and eight user programmable The Controller SP is the basic control-
output ports with form C contacts are ler available with the LORAIN® CSP System Manager SP
included. In addition to traditional sys- system. The operational features of the
tem alarms and controls, the System Controller SP are as follows: local alarm
Manager SP provides event and alarm display by means of three LED indicators,
history logs, an inventory log, and deliv- three alarm outputs (dry C contacts),
ered DC power calculation. The System and two sets of local test points for the
Manager SP can be accessed locally or measurement of the system’s voltage
remotely using a built-in web based and current. DIP switches are used to
Graphical User Interface. Local connec- adjust float voltage, temperature com-
tion is made through the Ethernet port pensation, and the optional low voltage
using a computer equipped with a web disconnect.
browser and crossover cable. Remote
connection is made through a dial up
Controller SP
Enterprise : 73
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
Distribution Panel
74 : Enterprise
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
Enterprise : 75
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
76 : Enterprise
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
Enterprise : 77
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
78 : Enterprise
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
Controller Specifications
Controller SP
Display LED status interface
Alarm output 3 dry C contacts outputs (Major, Minor, AC failure/BOD)
Alarm input One external input for distribution and battery fuse alarm
Control of rectifiers Digital CAN bus
System configuration Dip switches for:
System (float) voltage
Temperature compensation battery charging
Low voltage disconnect
Battery management Low Voltage Disconnect (LVLD or LVBD)
Temperature compensation battery charging
System Manager SP
Display LCD display with four navigation buttons
Alarm output 8 dry C contacts (5 programmable)
SNMP & Web (HTML)
Alarm input 8 programmable inputs
Control of rectifiers Digital CAN bus
Battery management Battery Discharge Test
Charge Control
Low Voltage Disconnect (LVLD or LVBD)
Temperature compensation battery charging
Equalize (boost)
System configuration Embedded Web Browser (HTTP)
Communications ports RJ45 jack for Ethernet port (TCP/IP)
DB9 connector for RS-232
Remote access All essential functions and operational parameters through RS-232 modem and TCP/IP Ethernet with
password security
Enterprise : 79
PPB-ES-71100 / 1206
LORAIN® CSP 48300
DC Power System
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
80 : Enterprise
PPB-ES-71100 / 1206
NetSure™ 701NCBB DC Power for
Business-Critical Continuity
DC Power System
Key Features
Description
• Compact flexibility — provides
more space for revenue generating The NetSure™ 701NCBB power system is a modular -48VDC power system available in vari-
ous configurations and capacities up to 600 amps. A basic system consists of a power shelf
equipment
that incorporates a standard or advanced controller and up to five 3200W plug-in recti-
fiers, and an initial distribution panel with up to 20 plug-in positions accommodating bullet
• Constant power — delivers more nose type fuse holders rated 1 to 100 amps or circuit breakers rated 1 to 250 amps and
current at lower voltages to meet up to 10 positions for connecting batteries with or without protection devices. For smaller
load or recharge demand loads, an optional plug-in 10 position fuse module (up to 20A fuses) is available occupying
3 mounting position.
• Wide operating range —
operates in the most demanding A second power shelf that accommodates
environments with operating input up to six 3200W plug-in rectifiers and a
voltage from 85VAC second distribution panel with plug-in
to 290VAC positions for load & battery protection
devices can be added to increase the
system capacity to 600A. An optional low
• Meets industry standards —
voltage disconnect can be configured for
Designed to NEBS™ Level 3 battery disconnect in each distribution.
and UL 1801
Enterprise : 81
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System
BAU 48/4
Enterprise : 83
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System
Output power vs. Input voltage Output Power vs. Temperature Output voltage vs. Output current,
at Tamb <45°C at Uin>176VAC max. output power 3200W
85 176 290 45 5055 65
70
55A 67A
120 120 70
% of max output power
100 100 60
50
80 80
40
60 60 30
40 40 20
20 20 10
0
0 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0 50 100 150 200 250 300 350 -40 -20 0 20 40 60 80 100
Output Current (A)
Input Voltage (VAC) Temperature (C°)
84 : Enterprise
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System
Enterprise : 85
PPB-SDCP-059 / 1206
NetSure™ 701NCBB
DC Power System
Controller Specifications
Standard Control Unit (SCU)
Display LED status interface
Alarm output 8 programmable dry C contacts outputs
Alarm input 8 digital inputs
Control of rectifiers Digital CAN bus
System configuration 6 navigational keys
Battery management Low Voltage Disconnect, equalize (boost)
Temperature compensation battery charging, charge current limiting, battery discharge testing
Advanced Control Unit (ACU)
Display LCD display with six navigation buttons
Alarm output 8 programmable dry C contacts
SNMP & Web (HTML)
Alarm input 8 programmable inputs
Control of rectifiers Digital CAN bus
Management Battery Discharge Test Equalize (boost)
Charge Control Statistics
Low Voltage Disconnect (up to two LVDs) Energy savings algorithm
Temperature compensation battery charging
System configuration Embedded Web Browser (HTTP)
Communications ports RJ45 jack for Ethernet port (TCP/IP)
DB9 connector for RS-232
Remote access All essential functions and operational parameters through RS-232 modem and TCP/IP Ethernet with password security
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
86 : Enterprise
PPB-SDCP-059 / 1206
NetSure™ 701NVBB DC Power for
Business-Critical Continuity
DC Power System
Key Features
New 3,200 watt constant power conversion units provide 55 to
• Modular Design — simple 67 amps (59 amps at 54.0VDC and 62 amps at 52.0VDC) with a cur-
to install and operate; allows rent limit of 67 amps. With six units per shelf, these rectifiers provide
incremental cost-effective
system growth
330 to 402 amps in three rack units (5.25-in.) of space.
NetSure™ 701NVBB
Enterprise : 87
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System
Application
The NetSure™ 701NVBB system is ideal for The system can also be expanded with
wireline and wireless applications such as additional bays that are not adjacent to
switch sites, co-location, huts and large each other via extended length communi-
vaults or enclosures. cations cables and inter-bay power cabling.
The distribution cabinet can be factory
AC Input mounted in a relay rack or shipped loose
Each rectifier shelf in the NetSure™ 701 for mounting in a customer supplied relay
power system allows for an AC input feed rack or cabinet rails.
to each power conversion unit. There are
conduit knockout openings on the rear and A wide variety of panels provide multiple
side of each shelf. Each conduit opening combinations of distribution positions, Top AC Wireway Input
allows for installation of the (3) circuits nec- low voltage disconnect and battery dis- (cover removed)
essary to power up the (3) PCUs on that connect. Distribution cabinets are front
side of the shelf. If space is a problem then accessible, modular in design and are
an AC wireway option is available that will initially configured in the factory. Circuit
allow for the connection of the AC cables breakers and/or fuse modules plug into
at the top of the bay. At the factory, cables the multi-position distribution panels to
are run from this connection point down provide for easy installation. Distribution
into the shelves and enclosed in a sheet device options include 1 to 250 amp plug-
metal cover. Once again conduit knockouts in circuit breakers, 3 to 100 amp TPS-style
are provided at that top of this cover. fuses in plug-in holders, 100 to 600 amp
GJ/218-style circuit breakers and 70 to 600
Distribution amp TPH-style fuses. These devices can
The NetSure™ 701 power system includes be configured for both load and battery
a modular distribution product line that disconnect. A GMT fuse module is also
can be designed with one to two distribu- available.
tion cabinets – sized to accommodate Bottom AC Wireway Input
from one to four distribution panels each. (cover removed)
Each panel is rated at 500 amps load. The
maximum load per distribution cabinet is
2000 amps. The two, three and four-row
distribution cabinets can be intercon-
nected via copper inter-bay bus bars for a
total system capacity of up to 4,000 amps
with two bays.
88 : Enterprise
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System
Enterprise : 89
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System
90 : Enterprise
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System
Enterprise : 91
PPB-MDCP-073 / 1206
NetSure™ 701NVBB
DC Power System
Output power vs. Input voltage Output Power vs. Temperature Output voltage vs. Output current,
at Tamb <45°C at Uin>176VAC max. output power 3200W
85 176 290 45 5055 65
70
55A 67A
120 120 70
% of max output power
100 100 60
50
80 80
40
60 60 30
40 40 20
20 20 10
0
0 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0 50 100 150 200 250 300 350 -40 -20 0 20 40 60 80 100
Output Current (A)
Input Voltage (VAC) Temperature (C°)
Additional Information
For additional specification, engineering and installation information use specification
numbers 582126000 (power system) and 588705000 (power shelf for 3200W PCUs).
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
92 : Enterprise
PPB-MDCP-073 / 1206
LORAIN® VPS 246000 DC Power for
Business-Critical Continuity
DC Power System
Key Features
New 4,275 watt power conversion units provide 150 amps at
• Modular Design — simple to 28.5VDC and 180 amps at 23.8VDC each with a constant power
install and operate; allows users limiting feature. With four units per shelf, these rectifiers provide
to grow system in cost-effective
increments
600 to 720 amps in three rack units (5.25-in.) of space.
Enterprise : 93
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System
Application Distribution
The LORAIN® VPS includes a modular dis- A wide variety of panels provide multiple
The LORAIN® VPS is ideal for wireless tribution product line that can be designed combinations of distribution positions, low
applications such as cell sites, huts and with one to three distribution cabinets voltage disconnect and battery disconnect.
large CUE sites. – sized to accommodate from one to four Distribution cabinets are front accessible,
distribution panels each. Each panel is modular in design and are initially config-
rated at 500 amps load. The maximum ured in the factory. Circuit breakers and/or
load per distribution cabinet is 2000 amps. fuse modules plug into the multi-position
Additional Information The two, three and four-row distribution distribution panels to provide for easy
cabinets can be interconnected via copper installation. Distribution device options
For additional specification, engineer- inter-bay bus bars for a total system capac- include 1 to 250 amp plug-in circuit break-
ing and installation information, specify ity of up to 6,000 amps with three bays. ers, 3 to 100 amp TPS-style fuses,100 to
spec. numbers 581125000 (power 600 amp GJ/218-style circuit breakers
system), 588703800 (520 amp power The system can also be expanded with and 70 to 600 amp TPH-style fuses. These
shelf and 130 amp PCUs), 588704900 additional bays that are not adjacent to devices can be configured for both load
(600/720 amp shelf and 150/180 each other via extended length communi- and battery disconnect. A GMT fuse mod-
amp PCUs), 588248700 (40 amp con- cations cables and inter-bay power cabling. ule is also available.
verter frames and 10 amp modules), The distribution cabinet can be factory
588249400 (80 amp converter shelf mounted in a relay rack or shipped loose
and 10 amp modules). for mounting in a customer supplied relay
rack or cabinet rails.
For ordering information, request
SAG581125000, PD588703800,
PD588704900.
94 : Enterprise
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System
Monitoring/Control
The MCA provides a single point of adjust-
ment for such features as float voltage,
test/equalize voltage,high voltage shut-
down and current limit for all PCUs in the MCA
entire power system. The rugged, tem-
perature hardened LED display allows users
to view specific alarm conditions, system via optional software and hardware. The available via an ethernet, modem, RS-232 or
measurements and system settings. All MCA provides local indicators and the ability RS-485 interface. In addition, the LMS1000
measurements and adjustments can be per- to transmit various alarm conditions such as monitoring product can be configured into
formed locally via the alphanumeric display PCU failure, high voltage shutdown and AC this system (refer to 586505000 documen-
on the front of the MCA panel or remotely failure. Remote and local communication is tation for specifications).
DC to DC Converters
A modular DC to DC converter system
provides up to 320 amps at -48VDC via
high frequency switch mode converters
rated at 10 amps each. A unique frame
design mounts into a slot in the rectifier
+24VDC 1,040 amp
VPS with Battery Stand shelf and can accommodate four converter
modules. Four of these frames can be con-
figured in a system. The system can also
accommodate two rack-mount shelves,
each of which houses eight 10 amp mod-
ules. Distribution devices for the -48 volt
output are located in the main distribution
cabinet and are available in various quanti-
ties (refer to 588248700 documentation
Converter Frame -48V, 40 amp for specifications).
Enterprise : 95
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System
96 : Enterprise
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System
Enterprise : 97
PPB-MDCP-008 / 1206
LORAIN® VPS 246000
DC Power System
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
98 : Enterprise
PPB-MDCP-008 / 1206
LORAIN® VPS 486000 DC Power for
Business-Critical Continuity
DC Power System
Key Features
New 5,000 watt power conversion units provide 85 amps at
• Modular Design — simple to 58.0VDC and 105 amps at 48.0VDC each with a constant power
install and operate; allows users limiting feature. With four units per shelf, these rectifiers provide
to grow system in cost-effective
increments
340 to 420 amps in three rack units (5.25-in.) of space.
Enterprise : 99
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System
Application Distribution
The LORAIN® VPS includes a modular dis- A wide variety of panels provide multiple
The LORAIN® VPS is ideal for wireline and tribution product line that can be designed combinations of distribution positions, low
wireless applications such as switch sites, with one to three distribution cabinets voltage disconnect and battery disconnect.
co-location, huts and large CUE sites. – sized to accommodate from one to four Distribution cabinets are front acces-
distribution panels each. Each panel is sible, modular in design and are initially
rated at 500 amps load. The maximum configured in the factory. Circuit breakers
Additional Information load per distribution cabinet is 2000 amps. and/or fuse modules plug into the multi-
The two, three and four-row distribution position distribution panels to provide
For additional specification, engineering cabinets can be interconnected via copper for easy installation. Distribution device
and installation information, specify spec. inter-bay bus bars for a total system capac- options include 1 to 250 amp plug-in circuit
numbers 582125000 (power system), ity of up to 6,000 amps with three bays. breakers, 3 to 100 amp TPS-style fuses,100
588703600 (260 amp power shelf and 65 to 600 amp GJ/218-style circuit breakers
amp PCUs), 588704800 (340/420 amp The system can also be expanded with and 70 to 600 amp TPH-style fuses. These
shelf and 85/105 amp PCUs), 588249600 additional bays that are not adjacent to devices can be configured for both load and
(80 amp converter frame and 20 amp mod- each other via extended length communi- battery disconnect. A GMT fuse module is
ules), 588249700 (160 amp converter shelf cations cables and inter-bay power cabling. also available.
and 20 amp modules), 588250100 (40 amp The distribution cabinet can be factory
converter frame and 20 amp modules). mounted in a relay rack or shipped loose
for mounting in a customer supplied relay
For ordering information, request rack or cabinet rails.
SAG582125000, PD588703600,
PD588704800.
100 : Enterprise
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System
Monitoring/Control
The MCA provides a single point of adjust-
ment for such features as float voltage,
test/equalize voltage,high voltage shut-
down and current limit for all PCUs in the MCA
entire power system. The rugged, tem-
perature hardened LED display allows users via optional software and hardware. The RS-485 interface. In addition, the LMS1000
to view specific alarm conditions, system MCA provides local indicators and the ability monitoring product can be configured into
measurements and system settings. All to transmit various alarm conditions such as this system (refer to 586505000 documenta-
measurements and adjustments can be per- PCU failure, high voltage shutdown and AC tion for specifications).
formed locally via the alphanumeric display failure. Remote and local communication is
on the front of the MCA panel or remotely available via an Ethernet, modem, RS-232 or
Enterprise : 101
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System
102 : Enterprise
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System
Enterprise : 103
PPB-MDCP-003 / 1206
LORAIN® VPS 486000
DC Power System
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
104 : Enterprise
PPB-MDCP-003 / 1206
LORAIN® PS 4810000 DC Power for
Business-Critical Continuity
DC Power System
Key Features
Emerson Network Power’s next generation power platform
• NEBS™ Level 3 certified is now available with 208/240VAC rectifier, providing
integrated power, distribution, control and monitoring.
• Single frame design provides
power conversion, distribution,
control and monitoring in a
Description
small footprint
The LORAIN® Power System (LPS) utilizes a highly integrated revolutionary design to pack
• Patented, laminated internal bus unparalleled capacity and features into a small footprint.
work improves AC and DC cable
routing options The LPS is a -48VDC digital power plant that operates with 200 amp Power Conversion Units
(PCUs) powered from 480VAC or 208/240VAC. Each bay provides power conversion and dis-
• Modular distribution design tribution — up to ten PCUs (2000 amps total) along with 2400 amps of distribution. Adding
includes built-in automatic additional bays creates larger plants, up to 10,000 amps.
monitoring for all distribution
devices
Application
• Integrated Internal DC bus
eliminates costly overhead busses The LPS is ideal for use in central
and eases plant expansion office, switch site, MSO, and data
center applications. The LPS works
• Integrated LMS1000 design in both centralized and distributed
features a distributed I/O architecture plant layouts and is
architecture, an internet port and suitable for any -48VDC applica-
web page to simplify monitoring tion with 3-Phase commercial AC
of internal/external equipment service. The advanced monitoring
and control features allow the LPS
• Controller backplane accepts to fit into new office locations or
plug-in alarm cards and LMS simply be migrated into existing
I/O cards power plants. Due to the weight
distribution of the LPS, an entire
• Optional integrated AC Power DC power plant can be installed in
Distribution Service Cabinet a raised floor environment, subject
(PDSC) for protected bulk AC to floor loading limitations.
service feeds
• TCP/IP, SNMP, Ethernet, modem, LPS, -48VDC, 10,000A Modular Power Plant
and RS232 compatible
Enterprise : 105
PPB-CODCP-004 / 1206
LORAIN® PS 4810000
DC Power System
Distribution
Distribution is divided into two rows,
top and bottom. Each row has a flexible
design that accommodates any combina-
tion of breakers and fuses, up to a 1200
amp maximum per row. There can be up
to 24 (1-100A) breakers/fuses or up to 12
(100-800A) devices, or any combination.
Each distribution device used in the LPS
is designed for complete plug-n-play and
automatic registration with the system con-
troller. This patented unique design allows
total flexibility to configure each frame
per required device without costly kits and
restrictive panels.
Distribution Cabinet
Monitoring
All distribution elements of 100 amps and an LMS CPU for modem and Ethernet
greater include a monitoring shunt, iden- access, plus LMS I/O cards for other
tification to the controller, and integrated monitoring points. As a system, the MCA
alarming to the plant controller. The MCA controls the steady state output voltage to
consists of a multi-line vacuum fluorescent within 0.05% of any setting, from no load
display, plus a removable CPU and alarm to full load. The MCA also uses a patented
cards located in a shelf below the distribu- algorithm to balance the PCU output cur-
tion. The shelf is dual-purpose and accepts rents to within 1% of their rated current.
MCA
106 : Enterprise
PPB-CODCP-004 / 1206
LORAIN® PS 4810000
DC Power System
System Specifications
Operating Ambient 0°C to +40°C (+32°F to +104°F)
Temperature Range
Storage Ambient -40°C to +85°C (-40°F to +149°F)
Temperature Range
Output Capacity 10,000A per System, 2000A per bay (Rectifiers), 2400A per bay (Distribution)
Primary/Secondary 24"W x 30"D x 84"H
Frame Dimensions
Frame Weight 830 lbs. Per Frame (less PCUs)
PDSC Dimensions 10"W x 30"D x 84"H
PDSC Weight 190 lbs.
Safety UL Listed (UL1801), CSA 22.2 (No. 225), c UL, NEBS™ Level 3
Enterprise : 107
PPB-CODCP-004 / 1206
LORAIN® PS 4810000
DC Power System
Additional Information
For additional specification, engineering installation information, specify 582140000 (power system),
486532600 (200 amp PCUs 480VAC) or 486534000 (200 amp PCUs 208/240VAC).
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
108 : Enterprise
PPB-CODCP-004 / 1206
LORAIN® LVS 4810000 DC Power for
Business-Critical Continuity
DC Power System
Key Features
Description
ingle point adjustment — no
•S
tools required to make settings Built on the heritage of the LORAIN® brand name, the Large Vortex® power platform, with 200
and adjustments amp power conversion units (PCUs) is a modular power system providing up to 10,000 amps of
power for -48 volt systems. The components of a Vortex® power system include the power bay,
• LMS1000 Remote Monitoring — the meter–control–alarm microprocessor (MCA), LMS1000 Remote Monitoring, the PCUs and
options allow users to view, modular distribution.
control and interact with all
power systems in a network
Each power bay can accommodate up to seven PCUs and is capable of controlling the PCUs
from a remote location via
through the powerful microprocessor based MCA.
TCP/IP, Modem, SNMP or Web
• Plug’n’play — add PCUs without The front of the MCA panel provides a 16-character alpha-numeric display which can be acti-
adjustments and settings; no vated at the touch of a keypad.
system shutdown
The Vortex® distribution is modular, expandable and offers a variety of fuse/circuit breaker
• Front accessible — easy distribution modules up to 600 amps. The system is designed to provide DC power to loads
installation, additions and of up to 5,000 amps per bay. The Vortex® distribution main bay features a total system
maintenance solution by providing a flexible, modul ar hardware design, along with a variety of monitor-
ing and control options.
• NEBS™ Level 3 compliant — power
bay (UL1950), distribution The LMS1000 is included in the main distribution frame, providing unparalleled monitoring
(UL1801) and remote access capability. All branch loads are now factory connected to the LMS1000
chassis, ensuring rapid installation and ultimate user control over the power plant.
• Distribution — distribution bays
are available in 5000A capacities
per bay
Application
• Modular design — simple to
The Vortex® power system, pow-
install and operate; allows users
ered with 200 amp PCUs, is ideal
to grow system in cost-effective
for applications such as switch
increments
sites and large customer prem-
ise installations requiring up to
• High density — compact design
10,000 amps.
takes up less floor space; power
bay houses seven PCUs in a 18" x
24" (45.72cm x 60.96cm) footprint
• Optional temperature
compensation — provides
automatic adjustment of PCU
output voltage when battery LORAIN® LVS 4810000
temperature increases or
decreases
Enterprise : 109
PPB-CODCP-023 / 0107
LORAIN® LVS 4810000
DC Power System
MCA Module
The MCA module can be housed in the
power bay or the main distribution bay. The
MCA provides a single point of adjustment
MCA Module for such features as float voltage, test/
equalize voltage, high voltage shutdown
and current limit adjustments for all PCUs
in the entire power system. The MCA allows
users to view specific alarm conditions, sys-
tem measurements and system settings. All
adjustments can be performed locally via
the alpha-numeric display panel or remote-
ly via optional software and hardware.
The MCA provides local indicators and the Distribution Unit
ability to transmit various alarm conditions
such as PCU failure, high voltage shutdown
and AC failure. Distribution
• Modular Design — wide variety of
distribution modules allows for maximum
Power Bay configuration flexibility
The modular, high frequency, switch-mode
• High Capacity — offers up to 5,000 amp
Vortex® PCUs are the foundation of the
capacity per bay
Vortex® platform. Plug’n’play technology
allows for easy system configuration. System • Complete System Control — full range
capacity can be increased by simply plugging of monitoring and control
an additional PCU into an existing mounting options available
space in the power bay — no adjustments or
PCU • System Interbay Bus — modular external
setup are required. The PCUs allow the user to
bus systems designed for incremental
appropriately size a power plant (200 - 10,000
growth and minimal installation time
amps) to provide load power, battery float
current and battery recharge current. An • Fuse Protection — utilizing TPL, TPJ, TPS
optional AC input feature provides a prewired and TPA type fuses protecting circuits up
input to a terminal block at the top of each to 800 amps
cabinet and each rectifier is terminated with
a circuit breaker. This design eliminates the The Vortex® distribution is a fully integrated
cost of secondary AC distribution panels and modular solution that enables you to begin
saves installation costs. The power bay is 24" with the capacity you need today, and
(60.96cm) wide x 84" (213.36cm) high x 18" incrementally expand to meet future capac-
(45.72cm) deep. ity requirements. The main bay can house
up to six distribution modules, with eight
modules for each supplemental bay. The
vertical design results in ease of installation
and cable flow with plant shunt, ground
and battery termination bars internal or
external to the bay. This results in further
reduction in cable congestion, while facili-
tating expansion. The physical dimensions
are 7' (213.36cm) high x 31.38" (79.69cm)
wide x 24" (60.96 cm) deep.
110 : Enterprise
PPB-CODCP-023 / 0107
LORAIN® LVS 4810000
DC Power System
Enterprise : 111
PPB-CODCP-023 / 0107
LORAIN® LVS 4810000
DC Power System
LVPS Options
Option Function
LMS1000 Remote monitoring and communication system
VLI Vortex®-to-Legacy Interface
Vortex® MCA Microprocessor based meter, control and alarm (if not provided in power bay)
Vortex® Win Link Software and modem for remote Vortex® power system access
Pre-charge Unit For use with TPS, TPJ and TPL type fuse modules and GJ breakers
OH Bus System -48V battery and return bus bar kits, 10,000 amp rated
OH Bus Covers Provides clear, non-conductive bus safety covers for 10,000 amp bus
AC Courtesy Panel 120VAC, 20A ground fault protected receptacle outlet panel
Distribution Modules
Quantity Type Description
5 GJ 125-250 amp circuit breakers with shunts
4 GJ 250-400 amp circuit breakers with shunts
3 GJ 600 amp circuit breakers with shunts
3 TPL 61-600 amp fuseholders
6 TPJ 60-150 amp fuseholders
12 TPS 0-70 amp fuseholders
16 TPA 0-50 amp fuseholders
16 AM1 0-100 amp circuit breakers
1 TPL 1,000 - 1,200 amp fuse holder
2 GJ 800 amp circuit breakers
1 BD 1,200 amp battery disconnect
Additional Information
For additional specification, engineering and installation information, specify spec. number 582121901 (distribution bay),
582121100 (208/240VAC) or 582121300 (480VAC) (power bays).
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
112 : Enterprise
PPB-CODCP-023 / 0107
NterpriseIP™ Solution DC Power for
Business-Critical Continuity
Adaptive, High Availability
Power System for IP Telephony
Key Features
Deploy, Integrate, and Expand VoIP and PoE Applications
• Scalable with built in redundancy More Quickly, Reliably and Cost Effectively than Ever Before
• Two battery trays offer a wide
Description
selection of back-up times
Eliminates the infrastructure issues
The need for a reliable power infrastruc- associated with IP technology
• Extensive monitoring ture has never been more important, and deployment
- Web based interface IT professionals are discovering that DC • Inability to deliver high availability
- Programmable relay contacts Power is the key. These experts are recog- • Footprint constraints in wiring closets
- SNMP interface nizing the benefits a DC UPS can provide, • Lack of monitoring, management
- Local and remote control especially for applications requiring Power and control capabilities
over Ethernet (PoE). But modernizing the • Inability to support future PoE devices
• Pre-wired in factory for maximum infrastructure’s technology has proven to
• Unanticipated equipment
be a challenge in designing high-availabil-
DC system capacity powering issues
ity, cost-efficient data networks that are as
reliable as legacy voice networks.
• Single AC input interface and
TVSS for extra protection Now imagine an integrated DC UPS solu-
tion that offers “Six Nines” (99.9999%) reliability. One that delivers powerful performance
• Integrated grounding for all and efficient thermal management to protect your investment. A complete DC UPS
system components solution that will support all of your current and next generation requirements, while sig-
nificantly reducing costs.
• Rack space for your equipment
At Emerson Network Power, we’ve long realized that DC isn’t just for telecom applications
• Easy to configure and install anymore. We’ve taken the proven, adaptive architecture of DC Power and engineered an
innovative, new, plug-and-play, custom solution. With it, enterprises can deploy, integrate,
or expand Voice over IP (VoIP) and/or PoE applications more quickly, reliably and cost effec-
tively than ever before.
Options
Enterprise : 113
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony
1
6
7
2
8
3 9
5
10
114 : Enterprise
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony
Emerson is proud to announce the first DC NterpriseIP™’s flexible configurations, driv- • DC power distribution cabling
UPS solution on the market, NterpriseIP™. en by your specific business requirements,
• Space for your equipment
are created for easy plug-and-play installa-
NterpriseIP™ is specifically engineered to tion with a minimal footprint. • Provisions for communications
address the special challenges of deploying cable management
• Electronic Industries Alliance (EIA)
equipment in Telco closets and other tight
compliant cabinet factory pre-wired • Heavy-duty casters for easy
spaces. It will soon carve its own special
for maximum output DC power maneuverability
niche within growing data network infra-
structures where performance expectations • Multiple battery strings
are continually rising and budgets • Integrated AC input panel with TVSS
are decreasing. protection
Enterprise : 115
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony
Communication Ports
• RJ45 jack for Ethernet port
• DB9 connector for RS-232
116 : Enterprise
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony
Agencies Options
• NterpriseIP System - UL 60950 listed • 1-2kVA UPS with maintenance
bypass
• DC UPS - NEBS™ level 3 certified,
meets FCC class B • Battery diagnostic and failure
prediction monitor
• All materials have a flammability
rating of UL94V0 or better • User specific output cables
• Multiple AC input interfaces
Notes:
1. Requires additional cabinet
2. Contact your representative for longer back-up times
Enterprise : 117
PPB-UPS-060 / 1206
NterpriseIP™ Solution
Adaptive, High Availability Power System for IP Telephony
Notes:
1. Contact your representative for 120V feeders sizes and multiple AC input option
2. Contact your representative for input sizing when UPS option is selected
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
118 : Enterprise
PPB-UPS-060 / 1206
LORAIN® DB 48500 DC Power for
Business-Critical Continuity
Battery Distribution
Fuse/Circuit Breaker Bay
Key Features
Description
• Modular design — initial and field
installed Battery Distribution Fuse The LORAIN® DB 48500 Battery Distribution Fuse/Circuit Breaker Bay (BDF/CBB) features
and Circuit Breaker Panels (BDF/ high capacity and modularity. These features provide effective secondary load distribu-
tion and protection for multiple -48 VDC feeds up to 800 amps.
CBB Panels)
The LORAIN® DB 48500 system consists of a Digital Meter Panel and up to 13 BDF/CBB
• Mini applications — one BDF/ panels with a maximum of 5 BDF/CBB panels per frame.
CBB panel provides two (2) 500
amp buses for a total 1000 amp The BDF/CBB Panels mount on standard 23-inch frames and each panel is split into two
continuous rating with 16 fuse or sides of load distribution with each side providing 8 distributions for a total of 16 posi-
circuit breaker positions tions per panel. Each side has a capacity of 500 amp for a total of 1000 amp per panel.
Each side of the panel can have an individual power feed, or the left and right sides of the
• High capacity — offers up to ten panel mounted above / below each other can be paralleled for a single input feed of 800
buses with 5,000 amps continuous amp per paralleled side. Each side of the BDF/CBB panels can be parallel for single input
rating per frame, with maximum of 16 positions for 500 amps. Each panel can be equipped with two optional 10-position
GMT fuse blocks for additional distribution.
loading up to 80 fuse or circuit
breaker positions
Enterprise : 119
PDS-PDB-071 / 0107
LORAIN® DB 48500
Battery Distribution Fuse/Circuit Breaker Bay
Options
Option Description
Top or Bottom Feed Top or bottom input power feeds
Internal Ground Internal return / ground bus
Parallel Buses Interpanel parallel feed and ground buses
GMT Fuse Modules Two 10-position GMT fuse blocks per panel (one A and one B)
LVD Function Disconnects each side of BDF/CCB panel with self-latching contactor under control of Meter Panel
Monitoring
Specifications
Digital Meter Panel
2 line display with 3 navigation buttons
Visual alarms
Audible alarm and alarm cutoff
6 programmable relays for external alarms
Current threshold alarms
Programmable LVD control
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
120 : Enterprise
PDS-PDB-071 / 0107
LORAIN® DB 484800 DC Power for
Business-Critical Continuity
Battery Distribution
Fuse/Circuit Breaker Bay
Key Features
Description
• 360° access — front access
provides back-to-back or wall The LORAIN® DB 484800 Battery Distribution Fuse/Circuit Breaker Bay (BDF/CBB) fea-
installation, as well as side and tures high capacity, front access, modularity, and simplified installation. These features
provide effective secondary load distribution and protection for multiple -48 VDC feeds
rear access for conventional
up to 600 amps. The base offering is a vertical arrangement of modular distribution
applications
providing 360° access for ease of installation, maintenance and expansion.
• High capacity — offers either an The LORAIN® DB 484800 BDF/CBB system consists of a standard or Zone 4 box frame-
eight bus to 4,800 amps, or six bus work, with either six or eight buses, top or bottom feed/distribution. The system offers
to 3,600 amps continuous rating, a wide variety of options including box frame extensions, internal ground bars and a
with maximum loading up to 168 paralleling feature that permits multiple loads to be tied together, internal input cabling
fuse or circuit breaker positions options and transient voltage surge suppression. The universal ground bars can be
mounted to overhead framing or a cable rack. The physical dimensions are 7' (2.13m)
• Modular design — initial and field high by 26" (66.04cm) wide by 15" (38.10cm) deep.
installed interchangeable fuse
and circuit breaker distribution
modules Application
• Fuse protection — utilizing TPS, The LORAIN® DB 484800 is ideally suited
TPA and TPL fuses protects circuits for central office, co-location, and other
ranging from 0-150 amps applications requiring effective secondary
load distribution and protection of power
• Circuit breaker protection — plants up to 600 amp capacity per load.
LEL plug-in breakers available
in current ratings of 1-150 amps
Additional Information
• Multiple circuit breaker
types — options range from bolt-in For additional specification, engineering
to plug-in and installation information request
drawing SAG582120600.
• NEBS level 3 compliance — meets
or exceeds all relevant GR1089,
GR63 and UL specifications
Enterprise : 121
PDS-PDB-018 / 0107
LORAIN® DB 484800
Battery Distribution Fuse/Circuit Breaker Bay
Options
Option Description
Digital metering Digital metering provides both current and voltage for each bus
Single or parallel buses Paralleled buses provide maximum configuration flexibility
Bus metering Separate bus current and voltage readings
Adjustable dressing bars Sliding dressing bars for reduced output cable installation time
Precharge Precharge module for TPS and TPJ fuseholders
Box framework extension 8'0" (1.37m), 9'0" (2.74m) and 11'6" (3.50m) extensions
In-line fuse kit Provides internal power to alarm and meter circuits
Cable management kit Grooming kit for load cable dressing
Transient voltage
protection Bus voltage protection for sensitive electronic equipment
Distribution Modules
The distribution modules are factory con- 6 Bus Maximum Distribution Module Population
figurable with one or more of the available Quantity Type Description
fuseholders or circuit breakers. Distribution
16 TPS 0-70 amp fuseholders
modules can be populated in varying com-
binations. See “6 Bus” and “8 Bus” charts to 10 TPL 60-150 amp fuseholders
the right for options. 28 LEL/TPS 0-150 amp plug-in circuit breakers or 0-100 amp TPS/TFD fuses
Monitoring
A fuse or breaker alarm (LED) is provided 8 Bus Maximum Distribution Module Population
for each bus, and a bay alarm (LED) is Quantity Type Description
visible from a wide angle. Three form C
contacts are provided for remote alarm 12 TPS 0-70 amp fuseholders
monitoring. ABS or local powering capabili- 6 TPL 60-150 amp fuseholders
ties for monitoring are included. 16 LEL/TPS 0-150 amp plug-in circuit breakers or 0-100 amp TPS/TFD fuses
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
122 : Enterprise
PDS-PDB-018 / 0107
LORAIN® IS 6000 DC Power for
Business-Critical Continuity
Expandable Rack-Mounted
Inverter System
Key Features
Compact modular design offers easy system expansion and
• Modular design permits configurations up to 6kVA in 6U.
expansion of the system in
1kVA increments
Application
The LORAIN® IS 6000 rack-mounted
Inverter System is ideal for data centers,
wireless sites or central office environments
where flexible expansion capabilities are
necessary.
Enterprise : 123
PPB-INV-002 / 1206
LORAIN® IS 6000
Expandable Rack-Mounted Inverter System
*If depth of 6-in. front projected equipment exceeds 12 inches, a 1U mounting space above the inverter is required for adequate ventilation.
© 2007 Emerson Network Power Energy Systems, This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North
North America, Inc. All rights reserved. America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a
representation relating to the products or services concerned.
Emerson Network Power Energy Systems
1122 F St. Lorain, OH 44052 Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
Toll Free: 800-800-1280 (USA and Canada) conditions of supply of any product or service.
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems The Emerson logo is a trademark and a service mark of Emerson
Electric Co. Emerson Network Power is a division of Emerson
Electric Co. Vortex®, and LORAIN® are trademarks of Emerson
Network Power Energy Systems, North America, Inc.
Printed in USA
124 : Enterprise
PPB-INV-002 / 1206
Emerson Network Power
Business-Critical Continuity
for Communications
Enterprise Catalog
Outside Plant and DC Power Products & Systems
© 2007 Emerson Network Power Energy Systems, North America, Inc. All rights reserved.
This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing)
may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or
services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or
conditions of supply of any product or service.
The Emerson logo is a trademark and a service mark of Emerson Electric Co. Emerson Network Power is a division of Emerson Electric Co.