660 addressable manual call point with wireless node

EN 54-11, MCP for addressable system applications

Description
660 manual call points with wireless node connects to
addressable fire detection control and indicating equipment. Up to
62 devices can be connected to each addressable loop.
660-002 include a wireless node used to connect to wireless
devices to compatible control and indicating equipment.
A pressure-activated displacement element provides a safe and
convenient way for building occupants to manually initiate a fire
alarm condition.
All models have an integral alarm indicator that illuminates when
the manual call point has been activated. The indicator can also
be configured to flash when polled by the fire detection control
and indicating equipment.
Resetting the manual call point is achieved by inserting a key
through the underside of the unit to replace the operating face to
the quiescent position.
The 660 manual call point range provides fire detection and alarm 660-002 addressable manual call point with wireless repeater
system designers with a Standards-compliant, premium product
for life safety and property protection applications.

Features
Specifications
 Pressure activated displacement element provides a safe
user experience 660-002

 Integral indicator to show polling and alarm activation Operating voltage DC (17 ~ 28) V

 Resettable with simple key operation Start-up current 5.5 mA

 Suitable for indoor use Quiescent current 5.5 mA

 Integral wireless transmission path node with internal Alarm current 8 mA


antenna Operation type Direct operation (type A) a
 Electronic loop address setting Red LED
 DC 24 V operation Alarm indicator Visual indication of operating
element displacement
 Compatible with 2-wire fire detection and alarm systems
Number of nodes per alarm loop 62 (max.)
 Monitors for quiescent, alarm and fault conditions
Wireless node ID range 1 ~ 254
 Easy installation and configuration
Wireless radio interconnection
 Low maintenance 433 MHz, 868 MHz, 915 MHz
operating frequencies
Number of selectable radio
24
Compliance channels
Maximum distance between
660 manual call points have the following compliance a. 500 m
interconnected devices b
EN 54-11 b CE c Number of devices connectable to
125
node
660-002  
a Third-party assessment has not been undertaken
Terminal wiring (0.4 ~ 2.5) mm2
b EN 54-11 Manual call points Operating temperature (-10 ~ +55) °C
c Conformité Européenne
Operating humidity (0 ~ 95) % RH, non-condensing
Storage temperature (-25 ~ +80) °C
Storage humidity (0 ~ 98) % RH, non-condensing
Accessories
Dimensions (h × w × d) (87.5 × 87.5 × 56.5) mm
The following accessories are compatible with 660 manual call Ingress protection rating IP-42
points. a As defined in EN 54-11: "a manual call point in which the change to the alarm
Description Part Number Datasheet condition is automatic (i.e. without the need for further manual action when the
frangible element is broken or displaced".
MCP weather proof enclosure 460-009 31-0078 b Distance in free air.

Wireless node to control and 660-003 


indicating equipment cable

Ordering Information
660-002

View the complete range of products at


www.numens.com

1 31-0101-r01_2018-12
Numens
9 Xizhao Road, Innovative Industrial Area, Dong Qian Lake, Ningbo, Zhejiang, China 315121
© 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved. All specifications and other information shown were current at the date of publication
and subject to change without notice.

You might also like